Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:51

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880

Simulation Timestamp: 2023-10-16 08:51:31


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 29447.89 635.74 635.74
Net Site Energy 29447.89 635.74 635.74
Total Source Energy 91762.30 1981.04 1981.04
Net Source Energy 91762.30 1981.04 1981.04


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 74.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4601.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2456.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 350.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1909.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2082.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 671.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1590.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11792.10
Humidification 338.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 126.10
Heat Recovery 50.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 644.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 28728.18 719.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14198.37
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 74.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 4601.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2456.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 350.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 54.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2082.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 671.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1590.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11792.10
Humidification General 338.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 126.10
Heat Recovery General 50.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 644.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 74.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 4601.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 2456.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 350.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1909.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2082.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 671.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1590.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11792.10
Humidification Unassigned 338.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 126.10
Heat Recovery Unassigned 50.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 644.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 60.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 200.46 15.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Other 359.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 620.21 15.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 60.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 200.46 15.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Other 359.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 620.21 15.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 28728.177 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 28728.177 100.00
     
Total On-Site and Utility Electric Sources 28728.177 100.00
Total Electricity End Uses 28728.177 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 2655.23 99.37
Air to Air Heat Recovery for Heating 16.90 0.63
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2672.13 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 14198.37 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 14198.37 100.00
Total Water End Uses 14198.37 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1.33
Time Setpoint Not Met During Occupied Cooling 803.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:51
RunPeriod RUNPERIOD 1
Weather File Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Latitude [deg] 27.85
Longitude [deg] -82.5
Elevation [m] 8.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 6.5999 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 6.5999 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 6.6297 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 6.6297 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 6.5999 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 6.5999 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 6.5999 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 6.5999 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 6.5999 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 6.5999 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 6.5999 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 6.5999 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 6.5999 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 6.5999 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 6.5999 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 6.5999 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 6.5999 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 6.5999 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 6.5999 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 6.5999 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 9.7790 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 9.7790 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 9.7790 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 6.5999 18.58 484.4232  
Total 46320.38             6.6297 9.29 17.8789  
Conditioned Total 46320.38             6.6297 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.0382 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 03-AUG-15:30 06-FEB-06:10 - - - - - - - - - - 13-JUN-14:09
Heating 0.00 481266.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 416425.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 212815.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 82829.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 139498.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 48900.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 84322.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 4520.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 7280.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1767684.12 488547.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 481266.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 416425.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 212815.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3394.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 139498.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 48900.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 84322.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 4520.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 7280.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 81.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 14574.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 7779.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1110.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6046.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6593.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2127.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 5037.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 1073.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 159.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 699.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 90982.14 780.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 314.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 167.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 23.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 142.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 45.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 108.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 23.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1964.19 16.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 314.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 167.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 23.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 142.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 45.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 108.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 23.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1964.19 16.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.22
DATACENTER_BOT_ZN_6 DIRECT AIR 0.464980
DATACENTER_MID_ZN_6 DIRECT AIR 4.43
DATACENTER_TOP_ZN_6 DIRECT AIR 0.452021
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.29
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.42 0.350822 0.298000 1.62 0.935525 0.500000 0.001086 0.000142 1.62 12.80 0.008000
CORE_MID VAV BOX COMPONENT 50.68 0.375269 0.319000 16.17 1.00 0.500000 0.001015 0.002988 16.17 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.01 0.379306 0.322000 1.61 1.00 0.500000 0.001004 0.000519 1.76 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.914449 0.261163 0.222000 0.203008 0.696436 0.500000 0.001459 0.000044 0.203008 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.03 0.149740 0.127000 0.130533 0.399306 0.500000 0.002544 0.000031 0.130533 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.14 0.208656 0.177000 0.202592 0.556417 0.500000 0.001826 0.000058 0.202592 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.30 0.118196 0.100000 0.130212 0.315189 0.500000 0.003223 0.000019 0.130212 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 8.59 0.277887 0.236000 2.03 0.741032 0.500000 0.001371 0.001275 4.35 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 10.70       0.383446 0.500000 0.002650 0.000851 2.90 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 10.99 0.217310 0.185000 2.03 0.579492 0.500000 0.001753 0.001267 4.32 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 11.35 0.135571 0.115000 1.31 0.361524 0.500000 0.002810 0.000754 2.57 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.981705 0.243271 0.207000 0.203213 0.648723 0.500000 0.001566 0.000168 0.573847 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.09 0.141627 0.120000 0.130403 0.377671 0.500000 0.002690 0.000111 0.378953 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.21 0.196804 0.167000 0.202658 0.524811 0.500000 0.001936 0.000167 0.571197 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.22 0.126500 0.108000 0.131397 0.337334 0.500000 0.003012 0.000104 0.353943 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 16254.26 0.000142 327.67
CORE_MID VAV BOX REHEAT COIL 341535.22 0.002988 7729.94
CORE_TOP VAV BOX REHEAT COIL 59375.28 0.000519 1569.20
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 4994.59 0.000044 117.67
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 3506.42 0.000031 84.89
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 6605.56 0.000058 172.13
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 2132.03 0.000019 45.82
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 145764.75 0.001275 3846.13
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 97272.91 0.000851 2566.54
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 144832.07 0.001267 3821.55
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 86146.19 0.000754 2273.24
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 19231.19 0.000168 507.28
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 12699.03 0.000111 334.96
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 19142.58 0.000167 504.94
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11862.62 0.000104 312.92
VAV_BOT WITH REHEAT HEATING COIL 24424.57 0.000214 423.48
VAV_MID WITH REHEAT HEATING COIL 162991.86 0.001426 2869.31
VAV_TOP WITH REHEAT HEATING COIL 13781.02 0.000121 244.94
CAV_BAS HEATING COIL 245852.61 0.002151 5581.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 4.91 2.28 9.81 2.28 8.71 8.71 0.300000 0.262115 8.71
VAV_MID WITH REHEAT 46.16 22.84 92.32 24.91 80.57 80.57 0.300000 0.309203 80.57
VAV_TOP WITH REHEAT 4.76 2.28 9.51 3.64 8.90 8.90 0.300000 0.409099 8.90
CAV_BAS 5.22 5.22 5.22 5.22 5.22 5.22 1.00 1.00 5.22
AIRLOOP DATACENTER BASEMENT 21.29 21.29 21.29 21.29 21.29 21.29 1.00 0.999991 21.29
AIRLOOP DATACENTER BOT 0.464980 0.464980 0.464980 0.464980 0.464980 0.464980 1.00 1.00 0.464980
AIRLOOP DATACENTER MID 4.43 4.43 4.43 4.43 4.43 4.43 1.00 1.00 4.43
AIRLOOP DATACENTER TOP 0.452021 0.452021 0.452021 0.452021 0.452021 0.452021 1.00 1.00 0.452021
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 8.71  
VAV_MID WITH REHEAT_OA_CONTROLLER 80.57  
VAV_TOP WITH REHEAT_OA_CONTROLLER 8.90  
CAV_BAS_OA_CONTROLLER 5.22 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.29 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.464980 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.43 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.452021 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.03
VAV_MID WITH REHEAT OA HEAT RECOVERY 20.31
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.03
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.37 6.67 11.05 0.010747 0.008500 223867.45 0.006403 8.71
VAV_MID WITH REHEAT COOLING COIL 26.64 6.67 11.05 0.011045 0.008500 2172434.89 0.062131 80.57
VAV_TOP WITH REHEAT COOLING COIL 26.24 6.67 11.05 0.010717 0.008500 226710.01 0.006484 8.90
CAV_BAS COOLING COIL 25.05 6.67 11.42 0.010722 0.008500 122936.12 0.003516 5.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 8.71
VAV_MID WITH REHEAT FAN 80.57
VAV_TOP WITH REHEAT FAN 8.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.006403 0.000074
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000214  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.062131 0.000008
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.001426  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.006484 0.000073
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000121  
CAV_BAS_COOLC_CONTROLLER 0.003516 0.000135
CAV_BAS_HEATC_CONTROLLER 0.002151  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.29 433557.94 311756.50 0.010618
AIRLOOP DATACENTER BOT COOLING COIL 0.464980 9487.43 6810.56 0.000232
AIRLOOP DATACENTER MID COOLING COIL 4.43 90681.08 65006.51 0.002221
AIRLOOP DATACENTER TOP COOLING COIL 0.452021 9240.33 6626.61 0.000226
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.29 21.29 21.29 21.29 433557.94 433557.94 14482.89 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.464980 0.464980 0.464980 0.464980 9487.43 9487.43 669.05 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.43 4.43 4.43 4.43 90681.08 90681.08 6690.49 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.452021 0.452021 0.452021 0.452021 9240.33 9240.33 669.05 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.29
AIRLOOP DATACENTER BOT SUPPLY FAN 0.464980
AIRLOOP DATACENTER MID SUPPLY FAN 4.43
AIRLOOP DATACENTER TOP SUPPLY FAN 0.452021
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.29 433557.94 0.010618
AIRLOOP DATACENTER BOT HEATING COIL 0.464980 9487.43 0.000232
AIRLOOP DATACENTER MID HEATING COIL 4.43 90681.08 0.002221
AIRLOOP DATACENTER TOP HEATING COIL 0.452021 9240.33 0.000226
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 14482.89
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 669.05
AIRLOOP DATACENTER MID_SUPPHEATCOIL 6690.49
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 669.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000080 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.078534 12695.21  
HEATSYS1 PUMP 0.012409 3699.99 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.078534 9.42
HEATSYS1 0.012409 1.49
COOLSYS1_SUPPLY 0.078534 9.42
SINGLE WATER PLANT LOOP 0.013297 1.60
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.078534 0.078534 329645.67 8.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1418404.75 1418404.75 0.012409
CENTRAL BOILER 547731.54 537157.99 0.013297
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.039267 4394.66
COOLSYS1 CHILLER2 PUMP 0.039267 4394.66
PLANT CIRC PUMP 0.013297 3357.88
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.078534 0.039610 1388362.79 1394947.47 0.069031
COOLSYS1 CHILLER2 0.078534 0.039610 1388362.79 1394947.47 0.069031
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013297 139666.47 59258.00 69833.23 7004.20 21413.62
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.138062 16.57
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.138062 33842.56
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 53.40 1655100.84 10.68 206887.61
TOWERWATERSYS COOLTOWER 2 53.40 1655100.84 10.68 206887.61
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.071703
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 24.20 18.90 15.70 13.60 15.50 17.10 21.20 26.90 27.60 27.90 27.40 26.20


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tampa-MacDill AFB FL USA TMY3 WMO#=747880 27.85 -82.52 -5.00 8.00 101229 1.2032


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.85 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 6.600 4.842 0.000 0.000 0.000 0.000 11.442 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 6.600 484.423 0.000 0.000 0.000 0.000 491.023 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 18343.827 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18343.827
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 5172.174 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5172.174
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.452 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.400 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.662 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.5215
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5467
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4343
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.81534556E-15 0.47534309E-16 -0.12491808E-09 -0.15651055E-17
51 8 0.18376575E-07 0.18892299E-12 0.33997552E-03 -0.20894799E-09
52 7 -0.11109444E-01 0.10222184E-07 -0.21454547E-01 0.12631841E-03
53 6 0.37458360 0.36213810E-05 0.44579641 -0.43850983E-02
54 5 -4.8902522 0.13734403E-03 -4.2389002 0.59460182E-01
55 4 31.674104 0.11393769E-02 20.648451 -0.40448134
56 3 -108.39803 0.25142476E-02 -54.058051 1.4743366
57 2 194.32686 0.14299560E-02 76.440274 -2.8561868
58 1 -170.12819 0.15421596E-03 -54.840647 2.7274244
59 0 57.057407 0.88766417E-06 15.629571  
60 9 0.15527634E-14 0.48972640E-16 -0.12737755E-09 -0.48559044E-17
61 8 0.18724477E-07 0.18300980E-12 0.34384059E-03 -0.21290374E-09
62 7 -0.11225506E-01 0.98577958E-08 -0.21621905E-01 0.12763808E-03
63 6 0.37773826 0.34860306E-05 0.44850155 -0.44222837E-02
64 5 -4.9210508 0.13200769E-03 -4.2597582 0.59842059E-01
65 4 31.810414 0.10936068E-02 20.730162 -0.40629104
66 3 -108.68827 0.24103335E-02 -54.219675 1.4785295
67 2 194.61479 0.13693941E-02 76.588171 -2.8607587
68 1 -170.23464 0.14753937E-03 -54.883028 2.7292902
69 0 57.057407 0.84836289E-06 15.622061  
70 9 0.10580992E-14 0.52916478E-16 -0.11479962E-09 -0.26242945E-17
71 8 0.16943687E-07 0.21219816E-12 0.32378363E-03 -0.19265555E-09
72 7 -0.10622292E-01 0.11706466E-07 -0.20751735E-01 0.12077931E-03
73 6 0.36134106 0.41796623E-05 0.43441658 -0.42290030E-02
74 5 -4.7609497 0.15957712E-03 -4.1510514 0.57856955E-01
75 4 31.101728 0.13316855E-02 20.304070 -0.39688243
76 3 -107.17897 0.29539374E-02 -53.376774 1.4567269
77 2 193.11717 0.16877407E-02 75.817308 -2.8369794
78 1 -169.68078 0.18278585E-03 -54.662957 2.7195831
79 0 57.057407 0.10570564E-05 15.661738  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.455_SHGC_EAST_0.249 35 1 VerySmooth 2.586 2.586 1.000 0.250    
2 WINDOW_U_0.455_SHGC_SOUTH_0.249 36 1 VerySmooth 2.586 2.586 1.000 0.250    
3 WINDOW_U_0.455_SHGC_WEST_0.249 37 1 VerySmooth 2.586 2.586 1.000 0.250    
4 WINDOW_U_0.455_SHGC_NORTH_0.249 38 1 VerySmooth 2.586 2.586 1.000 0.250    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.486 6.0748E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.6847E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6860E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.8818E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8829E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9924E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9931E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7516E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7521E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.7154E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8001E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.9067E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.9772E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0116E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0681E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7664E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8035E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 9.1920E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6854E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1006
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8760E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.2933E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6417E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1496E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.0924E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.7233E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8383E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.9152E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.0185E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0194E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0976E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7668E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8046E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.6846E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6862E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.8817E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.8831E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.9923E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9934E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7515E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7521E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.9759E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.1286E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8196E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.9773E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5901E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.6698E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9952E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0209E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.5185E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1055E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.2851E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.9265E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.3008E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.7275E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.2799E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.2243E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.9415E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.0029E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.7769E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.8221E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5667E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5861E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9953E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0213E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7132E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7146E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4753E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4765E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3125E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3134E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7516E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7522E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7456E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8245E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5020E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5652E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3339E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3802E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7668E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8046E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6290E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3597E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0389E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0404E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8205E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 7.0923E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1496E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0921E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7429E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8213E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4984E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5582E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3278E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3618E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7664E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8035E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7131E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7144E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4752E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4762E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3124E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3130E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7515E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7521E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2773E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.3420E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9736E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0203E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9448E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.9618E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9954E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0213E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3704E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.6802E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9096E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.4183E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.1697E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.3027E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2799E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.2243E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3031E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4167E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0063E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.1165E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9664E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0342E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9952E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0208E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 9.8268E-002
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.4412E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1055
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.7165E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.1592E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.0480E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.8633E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.9092E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.3778E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.0518E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.1188E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.8366E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.1059E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.5769E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.9603E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9312E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.3109E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.1835E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.6391E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.7446E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.3925E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.3248E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.8633E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.9088E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.0772E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.4619E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.5589E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.1293E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.8349E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.0028E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.9603E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.9312E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 9.8394E-002
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.4529E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1057
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.7296E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.1744E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.0581E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.8716E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.9134E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.3832E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.0568E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.1250E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.8414E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.1147E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.5824E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.9686E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9354E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.3115E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.1860E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.6399E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.7466E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.3963E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.3272E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.8716E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.9131E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.0799E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.4654E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.5618E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.1323E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.8411E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.0068E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.9686E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.9354E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 72486.33304 72486.33304 5.22177 5.22177 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016   00:10:00 4.60000 5.25715E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 75268.26535 75268.26535 5.42168 5.42168 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782   00:10:00 4.60000 5.25715E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 703866.54600 703866.54600 50.68485 50.68485 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 178873.28890 178873.28890 7.48994 10.77825 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 69640.03840 69640.03840 5.01454 5.01454 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 41625.15625 41625.15625 1.76435 1.76435 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 12575.11896 12575.11896 0.91445 0.91445 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 33.90000 1.65364E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 2956.16406 2956.16406 0.12440 0.13533 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 14134.18542 14134.18542 1.02782 1.02782 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 30.22650 1.65295E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 2195.48401 2195.48401 9.25703E-002 9.25703E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 15739.95448 15739.95448 1.14459 1.14459 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 33.76833 1.65361E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 4570.13840 4570.13840 0.19350 0.19350 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 17906.42393 17906.42393 1.30212 1.30212 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79400 1.65343E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 825.57409 825.57409 3.50739E-002 8.72129E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 118175.97672 118175.97672 8.59416 8.59416 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 33.90000 1.65364E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 102071.53484 102071.53484 4.34665 4.34665 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 147179.48530 147179.48530 10.70330 10.70330 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 30.67417 1.65303E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 68112.18998 68112.18998 2.90087 2.90087 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 151122.80238 151122.80238 10.99012 10.99012 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 33.83417 1.65363E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 101419.45529 101419.45529 4.31877 4.31877 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 156104.41303 156104.41303 11.35232 11.35232 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 32.66233 1.65340E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 60332.62421 60332.62421 2.56836 2.56836 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 13498.87332 13498.87332 0.98171 0.98171 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 33.82100 1.65362E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 13461.41067 13461.41067 0.57385 0.57385 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 14942.62117 14942.62117 1.08670 1.08670 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 30.89800 1.65307E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 8888.80223 8888.80223 0.37895 0.37895 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 16686.49947 16686.49947 1.21352 1.21352 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 33.90000 1.65364E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 13399.47505 13399.47505 0.57120 0.57120 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 16729.44568 16729.44568 1.21664 1.21664 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79400 1.65343E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 8304.14824 8304.14824 0.35394 0.35394 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8107.21864 8107.21864 0.46498 0.46498 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 77287.35015 77287.35015 4.43276 4.43276 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7881.25509 7881.25509 0.45202 0.45202 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 371274.15509 371274.15509 21.29357 21.29357 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 26.71100 1.65229E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839   00:10:00 4.60000 5.25715E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 138934.20 8.70613 8.70613 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 15727.81 1.58644 1.58644 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1271697.33 80.57137 80.57137 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 201288.10 24.91290 24.91290 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:30:00
5 VAV_TOP WITH REHEAT Cooling Sensible 144319.65 8.90320 8.90320 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 19839.11 3.64229 3.64229 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00
7 CAV_BAS Cooling Sensible 77062.69 5.22177 5.22177 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 CAV_BAS Heating Sensible 51365.55 1.20016 1.20016 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 367890.01 21.29375 21.29375 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 14482.89 0.33839 0.33839 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8061.53 0.46498 0.46498 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 669.05 1.56323E-002 1.56323E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 76888.99 4.43276 4.43276 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 6690.49 0.15632 0.15632 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 7840.04 0.45202 0.45202 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 669.05 1.56323E-002 1.56323E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.22177
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.42168
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35082
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.29800
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61566
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.93552
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.08602E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.42199E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.61566
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16254.26114
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.42199E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 327.67315
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 50.68485
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.37527
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.31900
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 16.16847
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.01527E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.98790E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 16.16847
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 341535.21501
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.98790E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7729.94399
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.01454
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.37931
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32200
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61468
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 1.00000
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.00447E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.19441E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.76435
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 59375.27514
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.19441E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1569.19507
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.91445
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26116
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22200
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20301
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.69644
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.45886E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.36949E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20301
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4994.59493
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.36949E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 117.66534
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.02782
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14974
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.12700
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13053
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39931
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.54441E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.06757E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13053
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3506.42346
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.06757E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 84.88646
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.14459
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20866
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.17700
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20259
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55642
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.82597E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.77883E-005
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20259
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6605.56019
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.77883E-005
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 172.12865
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.30212
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11820
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13021
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31519
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.22346E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.86519E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13021
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2132.02740
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.86519E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 45.81826
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.59416
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27789
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23600
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.02822
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.74103
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.37106E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.27521E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.34665
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 145764.74658
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.27521E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3846.12946
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.70330
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.38345
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.64966E-003
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.50986E-004
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.90087
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
122 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 97272.91006
123 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.50986E-004
124 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2566.53912
125 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.99012
126 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21731
127 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.18500
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.03317
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57949
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.75326E-003
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.26705E-003
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.31877
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
136 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 144832.07362
137 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.26705E-003
138 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3821.54702
139 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.35232
140 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13557
141 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11500
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.30552
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36152
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.81033E-003
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.53644E-004
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.56836
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
150 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 86146.19400
151 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.53644E-004
152 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2273.23993
153 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.98171
154 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24327
155 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20700
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20321
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.64872
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.56615E-003
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.68243E-004
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.57385
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
164 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19231.18650
165 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.68243E-004
166 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 507.27769
167 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.08670
168 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14163
169 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.12000
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13040
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37767
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.69017E-003
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.11097E-004
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.37895
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
178 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12699.03161
179 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.11097E-004
180 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 334.96446
181 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.21352
182 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19680
183 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.16700
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20266
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.52481
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.93594E-003
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.67468E-004
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.57120
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
192 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19142.57844
193 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.67468E-004
194 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 504.94299
195 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.21664
196 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12650
197 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10800
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13140
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33733
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.01185E-003
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.03779E-004
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.35394
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
206 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11862.61716
207 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.03779E-004
208 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 312.92263
209 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46498
210 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.43276
211 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.45202
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.29357
213 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.90533
214 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28201
215 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 9.81065
216 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.28201
217 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.70613
218 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.70613
219 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
220 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.26211
221 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 46.16237
222 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 22.84118
223 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 92.32474
224 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 24.91290
225 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 80.57137
226 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 80.57137
227 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
228 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.30920
229 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.75655
230 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28235
231 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 9.51310
232 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.64229
233 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.90320
234 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.90320
235 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
236 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.40910
237 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.22177
238 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.22177
239 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.22177
240 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.22177
241 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.22177
242 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.22177
243 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
244 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
245 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.29357
246 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.29357
247 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.29357
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.29357
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.29375
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.29375
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
253 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46498
254 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46498
255 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46498
256 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.46498
257 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.46498
258 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.46498
259 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
260 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
261 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.43276
262 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.43276
263 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.43276
264 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.43276
265 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.43276
266 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.43276
267 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
268 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
269 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.45202
270 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.45202
271 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.45202
272 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.45202
273 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.45202
274 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.45202
275 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
276 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
277 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.70613
278 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 80.57137
279 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.90320
280 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.22177
281 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.29375
282 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.46498
283 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.43276
284 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.45202
285 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.70613
286 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.03050
287 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.37325
288 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04745
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.07469E-002
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 223867.44809
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.40258E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.70613
295 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 24424.56681
296 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.13677E-004
297 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 423.48177
298 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.70613
299 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.40258E-003
300 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.43748E-005
301 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.13677E-004
302 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 80.57137
303 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 20.30600
304 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.64470
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04839
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.10453E-002
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2172434.88837
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.21314E-002
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 80.57137
312 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 162991.85899
313 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.42592E-003
314 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2869.31381
315 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 80.57137
316 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.21314E-002
317 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.66425E-006
318 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.42592E-003
319 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.90320
320 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.03050
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.24458
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04735
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.07172E-002
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 226710.01334
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.48388E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.90320
329 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 13781.01980
330 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.20562E-004
331 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 244.94235
332 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.90320
333 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.48388E-003
334 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.34422E-005
335 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.20562E-004
336 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.22177
337 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 25.04936
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.42474
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.07224E-002
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 122936.11505
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.51596E-003
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.22177
346 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 245852.60575
347 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.15083E-003
348 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 5581.80148
349 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.22177
350 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.51596E-003
351 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.35437E-004
352 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.15083E-003
353 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.29375
354 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
355 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.29375
356 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 433557.94453
357 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 311756.49795
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.06178E-002
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.29375
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.29375
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.29375
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.29375
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 433557.94453
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 433557.94453
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 14482.88751
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
367 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.29375
368 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.29375
369 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 433557.94453
370 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.06178E-002
371 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 14482.88751
372 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 8.00013E-005
373 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
374 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
376 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46498
377 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
378 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.46498
379 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9487.43005
380 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6810.56072
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.32347E-004
382 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.46498
383 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.46498
384 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.46498
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.46498
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9487.43005
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9487.43005
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 669.04940
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
390 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.46498
391 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.46498
392 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9487.43005
393 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.32347E-004
394 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 669.04940
395 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.43276
396 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
397 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.43276
398 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 90681.08263
399 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 65006.50969
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.22077E-003
401 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.43276
402 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.43276
403 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.43276
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.43276
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 90681.08263
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 90681.08263
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 6690.49404
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
409 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.43276
410 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.43276
411 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 90681.08263
412 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.22077E-003
413 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 6690.49404
414 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.45202
415 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
416 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.45202
417 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9240.33246
418 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6626.60908
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.26295E-004
420 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.45202
421 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.45202
422 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.45202
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.45202
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9240.33246
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9240.33246
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 669.04940
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
428 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.45202
429 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.45202
430 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9240.33246
431 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.26295E-004
432 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 669.04940
433 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 7.85338E-002
434 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 12695.21416
435 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 7.85338E-002
436 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 9.42405
437 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 7.85338E-002
438 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 7.85338E-002
439 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 329645.67405
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 8.33000
441 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.24088E-002
442 PlantLoop HEATSYS1 Plant Loop Volume [m3] 1.48906
443 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.24088E-002
444 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 3699.99277
445 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
446 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1418404.74661
447 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1418404.75000
448 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.24088E-002
449 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 7.85338E-002
450 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 9.42405
451 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 3.92669E-002
452 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 4394.66245
453 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 3.92669E-002
454 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 4394.66245
455 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 7.85338E-002
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.96097E-002
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1388362.78819
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1394947.46500
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 6.90308E-002
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 7.85338E-002
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.96097E-002
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1388362.78819
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1394947.46500
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 6.90308E-002
465 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.32972E-002
466 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.59567
467 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.32972E-002
468 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3357.87773
469 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.32972E-002
470 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
471 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 59258.00218
472 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
473 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7004.19857
474 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21413.62202
475 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 547731.53765
476 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 537157.99000
477 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.32972E-002
478 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
479 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
480 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
481 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
482 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
483 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.13806
484 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 16.56739
485 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.13806
486 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 33842.56204
487 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 53.40126
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1655100.84056
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 10.68025
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 206887.60507
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 53.40126
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1655100.84056
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 10.68025
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 206887.60507
495 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.17025E-002
496 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.17025E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 15412.20
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 323645.06
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 56275.99
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 4731.80
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 3321.54
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 6254.97
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 2020.83
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 138114.70
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 92167.21
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 137231.16
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 81626.38
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 18220.86
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 12031.82
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 18136.93
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11239.49
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 20835.79
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 143062.13
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 12312.12
19 Coil:Heating:Water CAV_BAS HEATING COIL 199457.08


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 232842.37 160801.19 72041.18 0.69 34797.56 352.94
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2196875.42 1506119.25 690756.18 0.69 324728.13 3293.57
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 237174.00 164042.65 73131.36 0.69 35541.83 360.48
4 Coil:Cooling:Water CAV_BAS COOLING COIL 133773.40 93893.32 39880.08 0.70 20054.85 203.41


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.47 22.07
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.47 22.07


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2053613833 0.2072190310 Pass Pass 0.7204638811 0.6837858787 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 0.2305619287 0.2543156090 Pass Pass 0.2464052886 0.4306069845 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 0.1488286445 0.2039253023 Pass Pass 0.2103511266 0.4071988635 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 0.1329000680 0.1930098380 Pass Pass 0.1960753140 0.3964330785 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 0.1951017582 0.2251579564 Pass Pass 0.2457078080 0.4296346123 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.2493253051 0.3010067242 Pass Pass 0.2617070238 0.4582711430 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.4162540101 0.6297637339 Pass Pass 0.2897352270 0.5172632585 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.2766782925 0.4000146090 Pass Pass 0.2728364762 0.4977096102 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.1302843599 0.1829891457 Pass Pass 0.2097444455 0.4058997680 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.1786407240 0.2216403481 Pass Pass 0.2249805307 0.4373418833 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.3757754997 0.6520481268 Pass Pass 0.2630667685 0.4901998427 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.1812666746 0.2878476933 Pass Pass 0.2257957466 0.4402852591 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.1268613915 0.1783052511 Pass Pass 0.1958398065 0.3952717174 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.1750812303 0.2002775155 Pass Pass 0.1962993912 0.3975022856 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.3752740997 0.6500373521 Pass Pass 0.2392271509 0.4808225791 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.1820427519 0.2908004141 Pass Pass 0.2114265309 0.4312448573 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.3045217797E-002 3.8268922583E-002 Pass Pass 0.2618933082 0.4148696743 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.2690477545E-002 3.3507412218E-002 Pass Pass 0.2214552515 0.4115355595 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.1300337497E-002 6.3591650009E-002 Pass Pass 0.1959176811 0.3823784559 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 9.5512452816E-006 1.6283580889E-005 Pass Pass 3.3304267285E-003 4.4797648347E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 9.2869311754E-006 1.6310844666E-005 Pass Pass 4.7585560368E-003 5.3597744181E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 9.1958188771E-006 1.6425921586E-005 Pass Pass 7.7483970022E-003 5.5083912495E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 1.4457098691E-004 2.6130312273E-004 Pass Pass 6.4911965848E-005 1.1301514234E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 5701.88 -53.8 0.00 4982.23 30362.22 40992.52



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 4.60 0.00 4.60 Wetbulb [C] 2.50 10.00
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 33.90 7.90 25.10 Wetbulb [C] 3.10 270.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 66.00 12      
Feb 66.00 22      
Mar 126.00 32      
Apr 206.00 19      
May 144.00 46      
Jun 99.00 30      
Jul 192.00 52      
Aug 240.00 34      
Sep 310.00 44      
Oct 34.00 10      
Nov 63.00 12      
Dec 35.00 24      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.158 1.400 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.158 1.400 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.158 1.400 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.158 1.400 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.455_SHGC_EAST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.455_SHGC_EAST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.455_SHGC_EAST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.455_SHGC_WEST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.455_SHGC_WEST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.455_SHGC_WEST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.455_SHGC_NORTH_0.249   115.90 0.00 0.00 115.90 1158.95 2.586 0.250 0.275             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.455_SHGC_EAST_0.249   77.26 0.00 0.00 77.26 772.63 2.586 0.250 0.275             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.455_SHGC_SOUTH_0.249   115.90 0.00 0.00 115.90 1158.95 2.586 0.250 0.275             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.455_SHGC_WEST_0.249   77.26 0.00 0.00 77.26 772.63 2.586 0.250 0.275             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.455_SHGC_NORTH_0.249   115.90 0.00 0.00 115.90 115.90 2.586 0.250 0.275             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.455_SHGC_EAST_0.249   77.26 0.00 0.00 77.26 77.26 2.586 0.250 0.275             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.455_SHGC_SOUTH_0.249   115.90 0.00 0.00 115.90 115.90 2.586 0.250 0.275             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.455_SHGC_WEST_0.249   77.26 0.00 0.00 77.26 77.26 2.586 0.250 0.275             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 2.586 0.250 0.275                      
North Total or Average             1390.74 2.586 0.250 0.275                      
Non-North Total or Average             3245.06 2.586 0.250 0.275                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 6.5999 2779.43 18343.83 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 165.73
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 6.5999 2496.12 16474.05 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 148.84
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 6.5999 24961.20 164740.46 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 1488.36
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 6.5999 2496.12 16474.05 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 148.84
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 6.5999 313.41 2068.48 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.16 0.0000 Y 10.55
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.02 0.0000 Y 6.76
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 6.5999 313.42 2068.53 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.86 0.0000 Y 10.43
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.01 0.0000 Y 6.76
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 6.5999 3134.13 20684.81 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.11 0.0000 Y 105.25
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 6.5999 2019.75 13330.08 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.99 0.0000 Y 67.54
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 6.5999 3134.20 20685.26 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.83 0.0000 Y 104.19
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 6.5999 2019.75 13330.08 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.97 0.0000 Y 67.49
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 6.5999 313.41 2068.48 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.10 0.0000 Y 10.52
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.99 0.0000 Y 6.75
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 6.5999 313.42 2068.53 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.83 0.0000 Y 10.42
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.97 0.0000 Y 6.75
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 6.5999 783.68 5172.17 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 47.61
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 9.7790 36.20 354.03 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.63
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 9.7790 362.03 3540.27 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 36.26
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 9.7790 36.20 354.03 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.63
Interior Lighting Total       6.6297 46320.38 307089.14               774.12


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 13271.55 AstronomicalClock -   41.73 41.73 103.95
EXTERIOR_LIGHTS_B 989.48 AstronomicalClock -   83.73 62.73 11.65
EXTERIOR_LIGHTS_C 26594.85 AstronomicalClock -   83.73 47.05 234.89
Exterior Lighting Total 40855.88           350.49



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2737490.70          
HEATSYS1 BOILER Boiler:HotWater 1418404.75 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1394947.47 6.28 1221222.46 5.58 6.47 22.07
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1394947.47 6.28 1221222.46 5.58 6.47 22.07
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 537157.99 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1655100.84          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1655100.84          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 223867.45 232842.37 160801.19 72041.18 0.69 - 34797.56 352.94
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2172434.89 2196875.42 1506119.25 690756.18 0.69 - 324728.13 3293.57
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 226710.01 237174.00 164042.65 73131.36 0.69 - 35541.83 360.48
CAV_BAS COOLING COIL Coil:Cooling:Water 122936.12 133773.40 93893.32 39880.08 0.70 - 20054.85 203.41
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   433557.94 311756.50 121801.45 0.72 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9487.43 6810.56 2676.87 0.72 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   90681.08 65006.51 25674.57 0.72 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9240.33 6626.61 2613.72 0.72 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 16254.26 15412.20 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 341535.22 323645.06 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 59375.28 56275.99 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 4994.59 4731.80 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 3506.42 3321.54 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 6605.56 6254.97 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 2132.03 2020.83 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 145764.75 138114.70 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 97272.91 92167.21 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 144832.07 137231.16 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 86146.19 81626.38 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 19231.19 18220.86 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 12699.03 12031.82 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 19142.58 18136.93 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 11862.62 11239.49 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 24424.57 20835.79 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 162991.86 143062.13 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 13781.02 12312.12 -
CAV_BAS HEATING COIL Coil:Heating:Water 245852.61 199457.08 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   433557.94 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9487.43 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   90681.08 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9240.33 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   14482.89 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   669.05 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   6690.49 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   669.05 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 8.71 18813.48 2160.95 1.00 1.12 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 80.57 174110.43 2160.95 1.00 1.08 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 8.90 19239.34 2160.95 1.00 1.12 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.22 8854.31 1695.65 1.00 1.16 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.61 1018.41 21.29 35304.47 1657.97 1.00 1.13 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.46 520.83 1120.11 1.00 1.64 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.43 4965.17 1120.11 1.00 1.16 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.45 506.31 1120.11 1.00 1.65 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.078534 12695.21 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.012409 3699.99 298174.34 0.91 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.039267 4394.66 111917.77 0.91 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.039267 4394.66 111917.77 0.91 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013297 3357.88 252524.76 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.138062 33842.56 245126.60 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.49 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 72486.33 72486.33 26.08 5.222 5.222 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00898 28.05 0.01653 1.200 0.00
CORE_BOTTOM 75268.27 75268.27 30.15 5.422 5.422 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00892 28.05 0.01653 1.078 0.00
CORE_MID 703866.55 703866.55 281.98 50.685 50.685 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00894 28.05 0.01653 10.778 0.00
CORE_TOP 69640.04 69640.04 27.90 5.015 5.015 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00895 28.05 0.01653 1.078 0.00
PERIMETER_BOT_ZN_3 12575.12 12575.12 40.12 0.914 0.914 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 24.00 24.00 0.00895 33.90 0.01654 0.135 0.00
PERIMETER_BOT_ZN_2 14134.19 14134.19 69.98 1.028 1.028 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:30:00 24.00 24.00 0.00876 30.23 0.01653 0.087 0.00
PERIMETER_BOT_ZN_1 15739.95 15739.95 50.22 1.145 1.145 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 24.00 24.00 0.00886 33.77 0.01654 0.135 0.00
PERIMETER_BOT_ZN_4 17906.42 17906.42 88.66 1.302 1.302 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00871 32.79 0.01653 0.087 0.00
PERIMETER_MID_ZN_3 118175.98 118175.98 377.06 8.594 8.594 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00917 33.90 0.01654 1.353 0.00
PERIMETER_MID_ZN_2 147179.49 147179.49 728.70 10.703 10.703 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 24.00 24.00 0.00886 30.67 0.01653 0.872 0.00
PERIMETER_MID_ZN_1 151122.80 151122.80 482.17 10.990 10.990 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00903 33.83 0.01654 1.353 0.00
PERIMETER_MID_ZN_4 156104.41 156104.41 772.89 11.352 11.352 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.00 24.00 0.00884 32.66 0.01653 0.872 0.00
PERIMETER_TOP_ZN_3 13498.87 13498.87 43.07 0.982 0.982 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00916 33.82 0.01654 0.135 0.00
PERIMETER_TOP_ZN_2 14942.62 14942.62 73.98 1.087 1.087 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 24.00 24.00 0.00890 30.90 0.01653 0.087 0.00
PERIMETER_TOP_ZN_1 16686.50 16686.50 53.24 1.214 1.214 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 24.00 24.00 0.00904 33.90 0.01654 0.135 0.00
PERIMETER_TOP_ZN_4 16729.45 16729.45 82.83 1.217 1.217 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00886 32.79 0.01653 0.087 0.00
DATACENTER_BOT_ZN_6 8107.22 8107.22 223.94 0.465 0.465 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00859 31.21 0.01653 0.016 0.00
DATACENTER_MID_ZN_6 77287.35 77287.35 2134.85 4.433 4.433 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00859 31.21 0.01653 0.156 0.00
DATACENTER_TOP_ZN_6 7881.26 7881.26 217.70 0.452 0.452 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00859 31.21 0.01653 0.016 0.00
DATACENTER_BASEMENT_ZN_6 371274.16 371274.16 473.76 21.294 21.294 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 27.00 27.00 0.00854 26.71 0.01652 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200   00:10:00 15.60 25.44 0.00526 4.60 0.00526 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078   00:10:00 15.60 23.06 0.00526 4.60 0.00526 1.078 0.00
CORE_MID 178873.29 178873.29 71.66 7.490 10.778 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 4.60 0.00526 10.778 0.00
CORE_TOP 41625.16 41625.16 16.68 1.764 1.764 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 4.60 0.00526 1.078 0.00
PERIMETER_BOT_ZN_3 2956.16 2956.16 9.43 0.124 0.135 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00701 4.60 0.00526 0.135 0.00
PERIMETER_BOT_ZN_2 2195.48 2195.48 10.87 0.093 0.093 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00712 4.60 0.00526 0.087 0.00
PERIMETER_BOT_ZN_1 4570.14 4570.14 14.58 0.193 0.193 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00733 4.60 0.00526 0.135 0.00
PERIMETER_BOT_ZN_4 825.57 825.57 4.09 0.035 0.087 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00656 4.60 0.00526 0.087 0.00
PERIMETER_MID_ZN_3 102071.53 102071.53 325.68 4.347 4.347 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00763 4.60 0.00526 1.353 0.00
PERIMETER_MID_ZN_2 68112.19 68112.19 337.23 2.901 2.901 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00764 4.60 0.00526 0.872 0.00
PERIMETER_MID_ZN_1 101419.46 101419.46 323.59 4.319 4.319 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00762 4.60 0.00526 1.353 0.00
PERIMETER_MID_ZN_4 60332.62 60332.62 298.71 2.568 2.568 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00755 4.60 0.00526 0.872 0.00
PERIMETER_TOP_ZN_3 13461.41 13461.41 42.95 0.574 0.574 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00775 4.60 0.00526 0.135 0.00
PERIMETER_TOP_ZN_2 8888.80 8888.80 44.01 0.379 0.379 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00775 4.60 0.00526 0.087 0.00
PERIMETER_TOP_ZN_1 13399.48 13399.48 42.75 0.571 0.571 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00774 4.60 0.00526 0.135 0.00
PERIMETER_TOP_ZN_4 8304.15 8304.15 41.11 0.354 0.354 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00771 4.60 0.00526 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 27.00 0.00850 4.60 0.00526 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156   00:10:00 18.00 24.97 0.00801 4.60 0.00526 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 24.09 0.00553 4.60 0.00526 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338   00:10:00 18.00 27.00 0.00850 4.60 0.00526 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 8.71 8.71 1.59 1.59 8.7061 2.2820 8.7061 0.2621 0.3000
VAV_MID WITH REHEAT 80.57 80.57 24.91 24.91 80.5714 24.9129 80.5714 0.3092 0.3000
VAV_TOP WITH REHEAT 8.90 8.90 3.64 3.64 8.9032 3.6423 8.9032 0.4091 0.3000
CAV_BAS 5.22 5.22 1.20 1.20 5.2218 5.2218 5.2218 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.29 21.29 0.34 0.34 21.2938 21.2936 21.2938 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.46 0.46 0.02 0.02 0.4650 0.4650 0.4650 1.0000 1.0000
AIRLOOP DATACENTER MID 4.43 4.43 0.16 0.16 4.4328 4.4328 4.4328 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.45 0.45 0.02 0.02 0.4520 0.4520 0.4520 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 16254.261 16254.261 1.615661 0.00014220 327.673   1/21 00:10:00   1/21 00:10:00 16254.26 16254.26 1.615661 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 0.00 0.00 16314.19 16314.19
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 341535.215 341535.215 16.168466 0.00298790 7729.944 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 341535.22 341535.22 16.168466 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 178873.29 0.00 342699.81 342699.81
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 59375.275 59375.275 1.764348 0.00051944 1569.195 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 59375.28 59375.28 1.764348 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 41625.16 0.00 59593.84 59593.84
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 4994.595 4994.595 0.203008 0.00004369 117.665 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4994.59 4994.59 0.203008 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00701233 45.3685 2956.16 0.00 5010.94 5010.94
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 3506.423 3506.423 0.130533 0.00003068 84.886 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3506.42 3506.42 0.130533 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00711975 46.0560 2195.48 0.00 3517.75 3517.75
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 6605.560 6605.560 0.202592 0.00005779 172.129 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6605.56 6605.56 0.202592 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00733049 47.4033 4570.14 0.00 6625.76 6625.76
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 2132.027 2132.027 0.130212 0.00001865 45.818 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2132.03 2132.03 0.130212 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00655722 42.4538 825.57 0.00 2139.49 2139.49
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 145764.747 145764.747 4.346652 0.00127521 3846.129 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 145764.75 145764.75 4.346652 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00762834 49.3064 102071.53 0.00 146256.86 146256.86
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 97272.910 97272.910 2.900868 0.00085099 2566.539 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 97272.91 97272.91 2.900868 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00764147 49.3903 68112.19 0.00 97600.66 97600.66
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 144832.074 144832.074 4.318773 0.00126705 3821.547 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 144832.07 144832.07 4.318773 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00762426 49.2804 101419.46 0.00 145321.24 145321.24
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 86146.194 86146.194 2.568360 0.00075364 2273.240 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 86146.19 86146.19 2.568360 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00755344 48.8286 60332.62 0.00 86438.45 86438.45
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 19231.187 19231.187 0.573847 0.00016824 507.278 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19231.19 19231.19 0.573847 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00774524 50.0521 13461.41 0.00 19295.01 19295.01
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 12699.032 12699.032 0.378953 0.00011110 334.964 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12699.03 12699.03 0.378953 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00774823 50.0712 8888.80 0.00 12741.11 12741.11
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 19142.578 19142.578 0.571197 0.00016747 504.943 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19142.58 19142.58 0.571197 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00774325 50.0395 13399.48 0.00 19206.12 19206.12
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 11862.617 11862.617 0.353943 0.00010378 312.923 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11862.62 11862.62 0.353943 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00771023 49.8290 8304.15 0.00 11902.07 11902.07
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 223867.448 -999.000 8.706128 0.00640258 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 223867.45 162266.28 8.706128 26.37 19.02 0.01074693 11.05 11.05 0.00850000 33.90 0.01653638 25.13 23.3227 24.00 0.00892036 47.9513 116427.52 0.00 224222.56 160151.47
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 24424.567 24424.567 2.611838 0.00021368 423.482 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24424.57 24424.57 2.611838 5.07 5.01 0.00538686 12.80 11.59 0.00800000 4.60 0.00525715 4.60 77.7422 22.01 0.00618576 37.6627 10547.36 0.00 25223.97 25223.97
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2172434.888 -999.000 80.571365 0.06213136 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 2172434.89 1527333.52 80.571365 26.64 19.33 0.01104529 11.05 11.05 0.00850000 33.90 0.01653638 25.13 25.2025 24.00 0.00904233 48.5986 1044762.04 0.00 2175824.18 1510432.02
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 162991.859 162991.859 24.171410 0.00142592 2869.314 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:30:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 162991.86 162991.86 24.171410 7.22 6.45 0.00567254 12.80 11.59 0.00800000 4.60 0.00525715 4.60 84.0083 21.00 0.00778325 50.2931 317305.64 0.00 173198.62 173198.62
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 226710.013 -999.000 8.903198 0.00648388 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 226710.01 164538.70 8.903198 26.24 18.95 0.01071715 11.05 11.05 0.00850000 33.82 0.01653623 25.11 22.8064 24.00 0.00899178 48.3310 122093.49 0.00 227006.28 162329.45
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 13781.020 13781.020 2.670959 0.00012056 244.942 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13781.02 13781.02 2.670959 8.53 7.34 0.00587640 12.80 11.59 0.00800000 4.60 0.00525715 4.60 76.0214 20.26 0.00780385 52.7922 39251.06 0.00 14905.95 14905.95
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 122936.115 -999.000 5.221766 0.00351596 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 122936.12 87064.07 5.221766 25.05 18.57 0.01072245 11.42 11.42 0.00850000 28.55 0.01652632 23.72 22.9837 24.00 0.00898254 48.2805 71558.87 0.00 123129.48 86477.13
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 245852.606 245852.606 5.221766 0.00215083 5581.801 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 245852.61 245852.61 5.221766 1.06 1.06 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 22.9837 25.44 0.00525715 26.0830 0.00 0.00 211015.05 211015.05
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 433557.945 311756.498 21.293754 0.01061781 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 406219.74 396286.59 -999.0 28.51 18.07 0.00866952 12.80 12.09 0.00850000 33.90 0.01653638 25.13 -999.0000 27.00 0.00854233 38.4508 370799.80 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9487.430 6810.561 0.464980 0.00023235 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 8891.68 8436.04 -999.0 28.09 18.08 0.00885628 12.80 12.09 0.00850000 31.21 0.01653132 24.43 -999.0000 27.00 0.00858927 38.6570 8107.22 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 90681.083 65006.510 4.432758 0.00222077 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 85024.17 80469.36 -999.0 28.09 18.10 0.00887353 12.80 12.09 0.00850000 31.21 0.01653132 24.43 -999.0000 27.00 0.00859361 38.6765 77287.35 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9240.332 6626.609 0.452021 0.00022630 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 8662.88 8207.23 -999.0 28.10 18.09 0.00886646 12.80 12.09 0.00850000 31.41 0.01653169 24.48 -999.0000 27.00 0.00859178 38.6682 7878.46 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 433557.945 433557.945 21.293754 0.01061781 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 433557.94 433557.94 21.293754 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 1.5892 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9487.430 9487.430 0.464980 0.00023235 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9487.43 9487.43 0.464980 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.3619 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 90681.083 90681.083 4.432758 0.00222077 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 90681.08 90681.08 4.432758 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.5266 24.97 0.00801468 40.7015 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9240.332 9240.332 0.452021 0.00022630 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9240.33 9240.33 0.452021 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.4583 24.09 0.00552860 29.7080 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 14482.888 14482.888 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 14482.89 14482.89 21.293754 0.07 0.07 0.00844847 40.00 21.17 0.00800000 4.60 0.00525715 4.60 1.5892 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 669.049 669.049 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 669.05 669.05 0.464980 0.15 0.15 0.00839098 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.3619 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 6690.494 6690.494 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 6690.49 6690.49 4.432758 0.16 0.16 0.00791743 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.5266 24.97 0.00801468 40.7015 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 669.049 669.049 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 669.05 669.05 0.452021 0.16 0.16 0.00551921 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.4583 24.09 0.00552860 29.7080 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 16254.261 16254.261 1.615661 0.00014220 327.673 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 1.1233 1.145954   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 16254.26 16254.26 1.0000 1.94390940 1.615661 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.14218486 60.00 32.22 27.78 0.000 16254.26 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6744 0.00 0.00 16314.19 16314.19 1.94390940 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 341535.215 341535.215 16.168466 0.00298790 7729.944 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 23.6038 24.078826 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 341535.22 341535.22 1.0000 19.45336333 16.168466 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 2.98759426 60.00 32.22 27.78 0.000 341535.22 4.60 0.00525715 4.60 0.00000000 0.0000 20.58 0.00800000 21.00 0.00800000 51.6744 178873.29 0.00 342699.81 342699.81 19.45336333 12.80 11.60 0.00800000 33059.8 30.08 18.06 0.00800000 50676.3
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 59375.275 59375.275 1.764348 0.00051944 1569.195 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 4.1035 4.186060 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 59375.28 59375.28 1.0000 2.12280477 1.764348 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.51938782 60.00 32.22 27.78 0.000 59375.28 4.60 0.00525715 4.60 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 51.6744 41625.16 0.00 59593.84 59593.84 2.12280477 12.80 11.60 0.00800000 33059.8 40.33 21.28 0.00800000 61133.0
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 4994.595 4994.595 0.203008 0.00004369 117.665 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 0.3452 0.352128 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 4994.59 4994.59 1.0000 0.24425207 0.203008 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.04369044 60.00 32.22 27.78 0.000 4994.59 4.60 0.00525715 4.60 0.00000000 0.0000 20.83 0.00701233 21.00 0.00701233 45.3685 2956.16 0.00 5010.94 5010.94 0.24425207 12.80 11.60 0.00800000 33059.8 32.92 18.99 0.00800000 53575.3
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 3506.423 3506.423 0.130533 0.00003068 84.886 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 0.2423 0.247209 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 3506.42 3506.42 1.0000 0.15705256 0.130533 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.03067259 60.00 32.22 27.78 0.000 3506.42 4.60 0.00525715 4.60 0.00000000 0.0000 20.87 0.00711975 21.00 0.00711975 46.0560 2195.48 0.00 3517.75 3517.75 0.15705256 12.80 11.60 0.00800000 33059.8 34.77 19.58 0.00800000 55458.4
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 6605.560 6605.560 0.202592 0.00005779 172.129 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 0.4565 0.465703 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 6605.56 6605.56 1.0000 0.24375216 0.202592 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.05778243 60.00 32.22 27.78 0.000 6605.56 4.60 0.00525715 4.60 0.00000000 0.0000 20.87 0.00733049 21.00 0.00733049 47.4033 4570.14 0.00 6625.76 6625.76 0.24375216 12.80 11.60 0.00800000 33059.8 39.46 21.02 0.00800000 60242.2
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 2132.027 2132.027 0.130212 0.00001865 45.818 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 0.1473 0.150312 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 2132.03 2132.03 1.0000 0.15666669 0.130212 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.01865000 60.00 32.22 27.78 0.000 2132.03 4.60 0.00525715 4.60 0.00000000 0.0000 20.93 0.00655722 21.00 0.00655722 42.4538 825.57 0.00 2139.49 2139.49 0.15666669 12.80 11.60 0.00800000 33059.8 26.19 16.73 0.00800000 46716.2
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 145764.747 145764.747 4.346652 0.00127521 3846.129 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 10.0739 10.276668 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 145764.75 145764.75 1.0000 5.22974729 4.346652 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 1.27508351 60.00 32.22 27.78 0.000 145764.75 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00762834 21.00 0.00762834 49.3064 102071.53 0.00 146256.86 146256.86 5.22974729 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61026.2
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 97272.910 97272.910 2.900868 0.00085099 2566.539 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 6.7226 6.857909 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 97272.91 97272.91 1.0000 3.49022778 2.900868 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.85089904 60.00 32.22 27.78 0.000 97272.91 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00764147 21.00 0.00764147 49.3903 68112.19 0.00 97600.66 97600.66 3.49022778 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61023.8
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 144832.074 144832.074 4.318773 0.00126705 3821.547 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 10.0095 10.210913 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 144832.07 144832.07 1.0000 5.19620487 4.318773 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 1.26692491 60.00 32.22 27.78 0.000 144832.07 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00762426 21.00 0.00762426 49.2804 101419.46 0.00 145321.24 145321.24 5.19620487 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61026.6
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 86146.194 86146.194 2.568360 0.00075364 2273.240 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 5.9536 6.073456 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 86146.19 86146.19 1.0000 3.09016607 2.568360 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.75356761 60.00 32.22 27.78 0.000 86146.19 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00755344 21.00 0.00755344 48.8286 60332.62 0.00 86438.45 86438.45 3.09016607 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61031.9
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 19231.187 19231.187 0.573847 0.00016824 507.278 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 1.3291 1.355832 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19231.19 19231.19 1.0000 0.69043371 0.573847 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.16822565 60.00 32.22 27.78 0.000 19231.19 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00774524 21.00 0.00774524 50.0521 13461.41 0.00 19295.01 19295.01 0.69043371 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61006.0
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 12699.032 12699.032 0.378953 0.00011110 334.964 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 0.8776 0.895304 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12699.03 12699.03 1.0000 0.45594428 0.378953 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.11108534 60.00 32.22 27.78 0.000 12699.03 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00774823 21.00 0.00774823 50.0712 8888.80 0.00 12741.11 12741.11 0.45594428 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61004.3
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 19142.578 19142.578 0.571197 0.00016747 504.943 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 1.3230 1.349585 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19142.58 19142.58 1.0000 0.68724482 0.571197 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.16745054 60.00 32.22 27.78 0.000 19142.58 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00774325 21.00 0.00774325 50.0395 13399.48 0.00 19206.12 19206.12 0.68724482 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61006.4
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 11862.617 11862.617 0.353943 0.00010378 312.923 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 0.8198 0.836335 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 11862.62 11862.62 1.0000 0.42585306 0.353943 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.10376876 60.00 32.22 27.78 0.000 11862.62 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00771023 21.00 0.00771023 49.8290 8304.15 0.00 11902.07 11902.07 0.42585306 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61008.6
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 223867.448 -999.000 8.706128 0.00640258 -999.000 -999.0000 1.00000 1.00000 1024.8180 1004.8586 1.2032 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.706128 10.47492514   4197.9300 999.8980 78.52576724 15.00 6.67 8.33 2745948.46 8.1526 8.152646 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 223867.45 162266.28 1.0000 10.47492514 8.706128 26.37 19.02 0.01074693 53905.2 11.05 11.05 0.00850000 32533.5 6.40192755 6.67 15.00 8.33 18813.479 205053.97 33.90 0.01653638 25.13 2.03050000 23.3227 24.00 0.00892036 24.00 0.00892036 47.9513 116427.52 0.00 224222.56 160151.47 10.47492514 26.37 19.03 0.01074693 53905.2 11.45 11.36 0.00832185 32499.6
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 24424.567 24424.567 2.611838 0.00021368 423.482 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.706128 10.47492514   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 1.6880 1.721974 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24424.57 24424.57 1.0000 3.14247754 2.611838 5.07 5.01 0.00538686 18612.6 12.80 11.59 0.00800000 33059.8 0.21365497 60.00 32.22 27.78 0.000 24424.57 4.60 0.00525715 4.60 2.03050000 77.7422 6.69 0.00583992 22.01 0.00618576 37.6627 10547.36 0.00 25223.97 25223.97 3.14247754 2.80 2.80 0.00538686 16313.8 10.71 7.81 0.00538686 24340.6
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2172434.888 -999.000 80.571365 0.06213136 -999.000 -999.0000 1.00000 1.00000 1025.3726 1004.8586 1.2032 VAV_MID WITH REHEAT FAN Fan:VariableVolume 80.571365 96.94079934   4197.9300 999.8980 78.52576724 15.00 6.67 8.33 2745948.46 79.1142 79.114190 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 2172434.89 1527333.52 1.0000 96.94079934 80.571365 26.64 19.33 0.01104529 54944.3 11.05 11.05 0.00850000 32534.4 62.12502476 6.67 15.00 8.33 174110.429 1998324.46 33.90 0.01653638 25.13 20.30600000 25.2025 24.00 0.00904233 24.00 0.00904233 48.5986 1044762.04 0.00 2175824.18 1510432.02 96.94079934 26.64 19.34 0.01104529 54944.3 11.45 11.36 0.00832392 32499.5
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 162991.859 162991.859 24.171410 0.00142592 2869.314 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_MID WITH REHEAT FAN Fan:VariableVolume 80.571365 96.94079934   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 11.2645 11.491209 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:30:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 162991.86 162991.86 1.0000 29.08223980 24.171410 7.22 6.45 0.00567254 21520.4 12.80 11.59 0.00800000 33059.8 1.42577843 60.00 32.22 27.78 0.000 162991.86 4.60 0.00525715 4.60 20.30600000 84.0083 21.00 0.00785472 21.00 0.00778325 50.2931 317305.64 0.00 173198.62 173198.62 29.08223980 2.80 2.80 0.00567254 17029.8 8.67 7.17 0.00567254 22985.2
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 226710.013 -999.000 8.903198 0.00648388 -999.000 -999.0000 1.00000 1.00000 1024.7627 1004.8586 1.2032 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.903198 10.71203308   4197.9300 999.8980 78.52576724 15.00 6.67 8.33 2745948.46 8.2562 8.256164 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 Sensible 226710.01 164538.70 1.0000 10.71203308 8.903198 26.24 18.95 0.01071715 53697.4 11.05 11.05 0.00850000 32533.4 6.48321626 6.67 15.00 8.33 19239.337 207470.68 33.82 0.01653623 25.11 2.03050000 22.8064 24.00 0.00899178 24.00 0.00899178 48.3310 122093.49 0.00 227006.28 162329.45 10.71203308 26.24 18.96 0.01071715 53697.4 11.46 11.36 0.00832334 32505.7
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 13781.020 13781.020 2.670959 0.00012056 244.942 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.903198 10.71203308   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 0.9524 0.971586 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 22:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13781.02 13781.02 1.0000 3.21360992 2.670959 8.53 7.34 0.00587640 23363.4 12.80 11.59 0.00800000 33059.8 0.12055007 60.00 32.22 27.78 0.000 13781.02 4.60 0.00525715 4.60 2.03050000 76.0214 21.00 0.00783966 20.26 0.00780385 52.7922 39251.06 0.00 14905.95 14905.95 3.21360992 2.80 2.80 0.00587640 17540.7 7.37 6.78 0.00587640 22179.0
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 122936.115 -999.000 5.221766 0.00351596 -999.000 -999.0000 1.00000 1.00000 1024.7725 1004.8586 1.2032 CAV_BAS FAN Fan:ConstantVolume 5.221766 6.28265578   4197.9300 999.8980 78.52576724 15.00 6.67 8.33 2745948.46 4.4770 4.477000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 122936.12 87064.07 1.0000 6.28265578 5.221766 25.05 18.57 0.01072245 52486.1 11.42 11.42 0.00850000 32918.6 3.51559866 6.67 15.00 8.33 8854.310 114081.81 28.55 0.01652632 23.72 1.20015641 22.9837 24.00 0.00898254 24.00 0.00898254 48.2805 71558.87 0.00 123129.48 86477.13 6.28265578 25.05 18.58 0.01072245 52486.1 11.62 11.52 0.00840974 32887.8
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 245852.606 245852.606 5.221766 0.00215083 5581.801 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 CAV_BAS FAN Fan:ConstantVolume 5.221766 6.28265578   4197.9300 999.8980 12.40755766 54.44 82.22 27.78 1446950.71 16.9911 17.333036 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 245852.61 245852.61 1.0000 6.28265578 5.221766 1.06 1.06 0.00525715 14220.5 40.00 21.17 0.00800000 60796.0 2.15060644 60.00 32.22 27.78 0.000 245852.61 4.60 0.00525715 4.60 1.20015641 22.9837 0.00 0.00525715 25.44 0.00525715 26.0830 0.00 0.00 211015.05 211015.05 6.28265578 12.80 8.65 0.00525715 26134.9 45.90 20.94 0.00525715 59721.8
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 433557.945 311756.498 21.293754 0.01061781 -999.000 -999.0000 -999.00000 -999.00000 1020.9562 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 Sensible 406219.74 396286.59 0.9369 -999.0 -999.0 28.51 18.07 0.00866952 50788.3 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 406219.74 33.90 0.01653638 25.13 0.33839277 -999.0000 27.00 0.00854233 27.00 0.00854233 38.4508 370799.80 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9487.430 6810.561 0.464980 0.00023235 -999.000 -999.0000 -999.00000 -999.00000 1021.3034 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 8891.68 8436.04 0.9372 -999.0 -999.0 28.09 18.08 0.00885628 50834.5 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8891.68 31.21 0.01653132 24.43 0.01563234 -999.0000 27.00 0.00858927 27.00 0.00858927 38.6570 8107.22 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 90681.083 65006.510 4.432758 0.00222077 -999.000 -999.0000 -999.00000 -999.00000 1021.3355 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 85024.17 80469.36 0.9376 -999.0 -999.0 28.09 18.10 0.00887353 50885.6 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 85024.17 31.21 0.01653132 24.43 0.15632344 -999.0000 27.00 0.00859361 27.00 0.00859361 38.6765 77287.35 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9240.332 6626.609 0.452021 0.00022630 -999.000 -999.0000 -999.00000 -999.00000 1021.3223 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 8662.88 8207.23 0.9375 -999.0 -999.0 28.10 18.09 0.00886646 50871.7 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8662.88 31.41 0.01653169 24.48 0.01563234 -999.0000 27.00 0.00859178 27.00 0.00859178 38.6682 7878.46 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 433557.945 433557.945 21.293754 0.01061781 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 433557.94 433557.94 1.0000 25.61993968 21.293754 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 433557.94 4.60 0.00525715 4.60 0.33839277 1.5892 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9487.430 9487.430 0.464980 0.00023235 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9487.43 9487.43 1.0000 0.55944816 0.464980 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9487.43 4.60 0.00525715 4.60 0.01563234 3.3619 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 90681.083 90681.083 4.432758 0.00222077 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 90681.08 90681.08 1.0000 5.33334793 4.432758 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 90681.08 4.60 0.00525715 4.60 0.15632344 3.5266 0.00 0.00801468 24.97 0.00801468 40.7015 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9240.332 9240.332 0.452021 0.00022630 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9240.33 9240.33 1.0000 0.54385720 0.452021 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9240.33 4.60 0.00525715 4.60 0.01563234 3.4583 0.00 0.00552860 24.09 0.00552860 29.7080 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 14482.888 14482.888 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.293754 25.61993968   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 14482.89 14482.89 1.0000 25.61993968 21.293754 0.07 0.07 0.00844847 21203.7 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 14482.89 4.60 0.00525715 4.60 0.33839277 1.5892 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 669.049 669.049 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.464980 0.55944816   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 669.05 669.05 1.0000 0.55944816 0.464980 0.15 0.15 0.00839098 21143.1 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 669.05 4.60 0.00525715 4.60 0.01563234 3.3619 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 6690.494 6690.494 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.432758 5.33334793   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 6690.49 6690.49 1.0000 5.33334793 4.432758 0.16 0.16 0.00791743 19966.4 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6690.49 4.60 0.00525715 4.60 0.15632344 3.5266 0.00 0.00801468 24.97 0.00801468 40.7015 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 669.049 669.049 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.452021 0.54385720   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 669.05 669.05 1.0000 0.54385720 0.452021 0.16 0.16 0.00551921 13964.7 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 669.05 4.60 0.00525715 4.60 0.01563234 3.4583 0.00 0.00552860 24.09 0.00552860 29.7080 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 8.71 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 80.57 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 8.90 -      
CAV_BAS_OA_CONTROLLER DifferentialEnthalpy 1.20 5.22 -      
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER DifferentialEnthalpy 0.34 21.29 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 4930.67 2123.17 2050.83
CORE_BOTTOM 4843.17 159.67 0.00
CORE_MID 3205.83 1113.67 0.00
CORE_TOP 3430.33 1642.17 44.33
PERIMETER_BOT_ZN_3 4191.83 1167.33 55.83
PERIMETER_BOT_ZN_2 4309.67 1175.67 250.00
PERIMETER_BOT_ZN_1 4771.17 881.00 277.17
PERIMETER_BOT_ZN_4 5133.17 814.17 520.33
PERIMETER_MID_ZN_3 3626.17 2202.83 333.67
PERIMETER_MID_ZN_2 3387.00 1639.33 450.83
PERIMETER_MID_ZN_1 4502.33 1316.50 430.67
PERIMETER_MID_ZN_4 4310.33 1598.33 426.67
PERIMETER_TOP_ZN_3 3867.67 2455.67 727.50
PERIMETER_TOP_ZN_2 4114.00 2049.50 638.00
PERIMETER_TOP_ZN_1 4414.50 1610.67 591.33
PERIMETER_TOP_ZN_4 4286.50 1879.83 621.67
DATACENTER_BOT_ZN_6 5943.00 1525.00 1525.00
DATACENTER_MID_ZN_6 5937.17 130.83 130.83
DATACENTER_TOP_ZN_6 5877.33 429.00 413.00
DATACENTER_BASEMENT_ZN_6 5943.00 5943.00 5943.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 71.17 0.00 3.33
CORE_BOTTOM 0.00 0.50 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 4.50 0.00 1.83
PERIMETER_BOT_ZN_2 0.00 51.83 0.00 50.67
PERIMETER_BOT_ZN_1 0.00 78.17 0.00 74.00
PERIMETER_BOT_ZN_4 0.00 249.17 0.00 101.67
PERIMETER_MID_ZN_3 0.17 1.17 0.00 1.17
PERIMETER_MID_ZN_2 0.00 62.67 0.00 60.00
PERIMETER_MID_ZN_1 0.00 87.00 0.00 85.17
PERIMETER_MID_ZN_4 0.00 69.00 0.00 40.67
PERIMETER_TOP_ZN_3 7.67 24.67 1.33 19.00
PERIMETER_TOP_ZN_2 5.17 75.83 0.33 66.17
PERIMETER_TOP_ZN_1 2.50 83.00 0.00 75.17
PERIMETER_TOP_ZN_4 2.17 87.00 0.00 50.33
DATACENTER_BOT_ZN_6 0.00 41.50 0.00 41.50
DATACENTER_MID_ZN_6 0.00 35.17 0.00 35.17
DATACENTER_TOP_ZN_6 0.00 21.00 0.00 21.00
DATACENTER_BASEMENT_ZN_6 0.00 640.33 0.00 557.67
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 7.67 1094.83 1.33 803.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.01 149.60 6779.02 0.960 0.000 0.000 0.000
CORE_BOTTOM 55.69 134.35 6849.35 0.581 0.000 0.000 0.000
CORE_MID 55.69 134.35 6849.35 0.501 0.000 0.000 0.000
CORE_TOP 55.69 134.35 6849.35 0.485 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.99 16.87 860.00 0.624 0.034 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 0.771 0.035 0.000 0.000
PERIMETER_BOT_ZN_1 6.99 16.87 860.02 0.916 0.034 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 1.207 0.035 0.000 0.000
PERIMETER_MID_ZN_3 6.99 16.87 860.00 0.589 0.079 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 0.725 0.087 0.000 0.000
PERIMETER_MID_ZN_1 6.99 16.87 860.02 0.891 0.079 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 0.839 0.082 0.000 0.000
PERIMETER_TOP_ZN_3 6.99 16.87 860.00 0.585 0.098 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 0.769 0.101 0.000 0.000
PERIMETER_TOP_ZN_1 6.99 16.87 860.02 0.861 0.098 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 0.817 0.101 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.48 42.18 1911.37 11.850 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.01 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.69 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.94 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.99 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.51 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.99 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.51 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.48 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.01 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.69 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.94 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.99 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.99 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.51 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.48 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1027.73 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 39344000.68 0.00 39344000.68 0.00 39344000.68 37848132.68 4146.85 2805.75 1807.40 179.43
CORE_BOTTOM 23933009.63 0.00 23933009.63 0.00 23933009.63 33990283.35 6734.12 65.59 1960.30 122.42
CORE_MID 0.20E+09 0.00 0.20E+09 0.00 0.20E+09 0.34E+09 6723.32 240.65 1796.04 21.13
CORE_TOP 19527483.05 0.00 19527483.05 0.00 19527483.05 33990283.35 6789.37 257.92 1712.71 41.63
PERIMETER_BOT_ZN_3 3212996.22 0.00 3212996.22 328931.10 3541927.32 4267819.30 4515.74 106.01 4138.24 122.42
PERIMETER_BOT_ZN_2 2544245.66 0.00 2544245.66 219287.25 2763532.91 2750345.05 4450.73 76.49 4232.77 122.42
PERIMETER_BOT_ZN_1 4678432.51 0.00 4678432.51 328931.10 5007363.61 4267912.63 4191.86 50.35 4517.79 122.42
PERIMETER_BOT_ZN_4 3968751.15 0.00 3968751.15 219287.25 4188038.40 2750345.05 4090.26 22.43 4647.31 122.42
PERIMETER_MID_ZN_3 29654088.50 0.00 29654088.50 771421.61 30425510.11 42678193.03 4731.65 247.35 3781.00 21.13
PERIMETER_MID_ZN_2 24169644.42 0.00 24169644.42 514280.72 24683925.15 27503450.52 4595.75 183.16 3981.09 844.48
PERIMETER_MID_ZN_1 44785397.45 0.00 44785397.45 771421.61 45556819.06 42679126.28 4282.62 101.38 4376.00 21.13
PERIMETER_MID_ZN_4 27180526.29 0.00 27180526.29 514280.72 27694807.02 27503450.52 4288.20 102.11 4369.68 21.13
PERIMETER_TOP_ZN_3 2955945.75 0.00 2955945.75 957784.80 3913730.55 4267819.30 4677.51 209.92 3872.57 41.63
PERIMETER_TOP_ZN_2 2497954.91 0.00 2497954.91 638522.76 3136477.67 2750345.05 4327.10 239.65 4193.24 41.63
PERIMETER_TOP_ZN_1 4336112.98 0.00 4336112.98 957784.80 5293897.78 4267912.63 4316.22 160.32 4283.46 41.63
PERIMETER_TOP_ZN_4 2650677.20 0.00 2650677.20 638522.76 3289199.96 2750345.05 4309.45 34.03 4416.52 41.63
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.19E+09 0.00 0.19E+09 0.00 0.19E+09 10671554.30 2699.67 2875.83 3184.50 1095.67
Total Facility 0.36E+10 0.00 0.36E+10 30003098.57 0.36E+10 0.50E+10 7616.98 4354.14 6117.40 1960.20


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.7689 0.0000 1.7689 0.0000 1.7689 1.2002 1447.88 2805.38 1689.74
CORE_BOTTOM 1.0837 0.0000 1.0837 0.0000 1.0837 1.0778 4033.72 64.69 1844.59
CORE_MID 9.3390 0.0000 9.3390 0.0000 9.3390 10.7782 3922.55 240.48 1779.97
CORE_TOP 0.9061 0.0000 0.9061 0.0000 0.9061 1.0778 3986.17 257.42 1699.41
PERIMETER_BOT_ZN_3 0.1462 0.0000 0.1462 0.0079 0.1541 0.1353 1814.65 105.13 4023.21
PERIMETER_BOT_ZN_2 0.1164 0.0000 0.1164 0.0053 0.1216 0.0872 1749.64 75.45 4117.91
PERIMETER_BOT_ZN_1 0.2147 0.0000 0.2147 0.0079 0.2226 0.1353 1490.77 49.30 4402.93
PERIMETER_BOT_ZN_4 0.1821 0.0000 0.1821 0.0053 0.1874 0.0872 1389.20 21.31 4532.49
PERIMETER_MID_ZN_3 1.3796 0.0000 1.3796 0.0185 1.3981 1.3533 1931.26 247.18 3764.56
PERIMETER_MID_ZN_2 1.0938 0.0000 1.0938 0.0131 1.1069 0.8721 1530.69 176.50 3326.81
PERIMETER_MID_ZN_1 2.0869 0.0000 2.0869 0.0185 2.1054 1.3533 1481.79 101.38 4359.83
PERIMETER_MID_ZN_4 1.2656 0.0000 1.2656 0.0123 1.2780 0.8721 1487.44 101.95 4353.61
PERIMETER_TOP_ZN_3 0.1372 0.0000 0.1372 0.0229 0.1601 0.1353 1880.74 209.55 3852.71
PERIMETER_TOP_ZN_2 0.1161 0.0000 0.1161 0.0153 0.1314 0.0872 1528.75 239.11 4175.14
PERIMETER_TOP_ZN_1 0.2018 0.0000 0.2018 0.0229 0.2247 0.1353 1515.52 159.72 4267.76
PERIMETER_TOP_ZN_4 0.1232 0.0000 0.1232 0.0153 0.1385 0.0872 1508.40 33.64 4400.96
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 6.1202 0.0000 6.1202 0.0000 6.1202 0.3384 978.33 2875.83 2088.83
Total Facility 163.9303 0.0000 163.9303 0.7263 164.6566 158.4706 4799.98 4351.49 4982.26


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 55497110.01 0.00 55497110.01 48026705.38 4053.09 0.00 4706.91 122.42
VAV_MID WITH REHEAT 0.47E+09 0.00 0.47E+09 0.48E+09 4209.08 0.62 4550.30 21.13
VAV_TOP WITH REHEAT 46277392.13 0.00 46277392.13 48026705.38 4228.22 1.08 4530.70 41.63
CAV_BAS 56954791.69 0.00 56954791.69 37848132.68 4122.22 1.21 4636.56 179.43
AIRLOOP DATACENTER BASEMENT 0.28E+09 0.00 0.28E+09 10671554.30 2699.67 0.00 6060.33 1095.67
AIRLOOP DATACENTER BOT 353645.50 0.00 353645.50 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3536455.01 0.00 3536455.01 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 353645.50 0.00 353645.50 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 2.5234 0.0000 2.5234 1.5229 1358.50 0.00 4584.50
VAV_MID WITH REHEAT 21.9990 0.0000 21.9990 15.2292 1413.21 0.50 4529.29
VAV_TOP WITH REHEAT 2.1488 0.0000 2.1488 1.5229 1439.65 1.01 4502.34
CAV_BAS 2.5607 0.0000 2.5607 1.2002 1442.80 0.09 4500.11
AIRLOOP DATACENTER BASEMENT 8.8596 0.0000 8.8596 0.3384 978.33 0.00 4964.67
AIRLOOP DATACENTER BOT 0.0165 0.0000 0.0165 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1653 0.0000 0.1653 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0165 0.0000 0.0165 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 108.63 1640.50 0.00 0.00 0.00 2957.79 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 277.52 1343.53 0.00 0.00 0.00 2929.87 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 90.81 1422.38 0.00 0.00 0.00 3043.46 0.00 0.00 0.00
CAV_BAS 0.00 2805.08 1877.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 2875.83 3184.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 2.7283 4.9364 0.0000 0.0000 0.0000 2.4370 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 28.2626 38.4190 0.0000 0.0000 0.0000 24.6233 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 2.6994 3.7125 0.0000 0.0000 0.0000 2.4320 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.7374 6.0960 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4900 24.5422 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0226 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2263 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0226 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1524
Defaulted Fields 1183
Fields with Defaults 3919
Autosized Fields 336
Autosizable Fields 414
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 28728.18 308703.76 15-JAN-05:00 1767684.12 03-AUG-15:30
Electricity:Building 17132.70 216479.19 14-MAY-17:20 1017136.67 12-DEC-08:10
Electricity:Zone:BASEMENT 590.13 14055.89 01-JAN-00:10 28201.58 02-JAN-08:10
Electricity:SpaceType:GENERAL 17132.70 216479.19 14-MAY-17:20 1017136.67 12-DEC-08:10
InteriorLights:Electricity 2456.31 9223.03 23-APR-17:20 239317.20 25-OCT-07:10
InteriorLights:Electricity:Zone:BASEMENT 165.73 598.35 01-JAN-00:10 14744.03 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2456.31 9223.03 23-APR-17:20 239317.20 25-OCT-07:10
LightsWired:InteriorLights:Electricity 2456.31 9223.03 23-APR-17:20 239317.20 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 165.73 598.35 01-JAN-00:10 14744.03 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2456.31 9223.03 23-APR-17:20 239317.20 25-OCT-07:10
Electricity:Zone:CORE_BOTTOM 438.45 4990.59 01-JAN-00:10 30447.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
Electricity:Zone:CORE_MID 4384.49 49905.77 01-JAN-00:10 304477.41 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1488.37 5373.60 01-JAN-00:10 132411.79 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1488.37 5373.60 01-JAN-00:10 132411.79 02-JAN-08:10
Electricity:Zone:CORE_TOP 438.45 4990.58 01-JAN-00:10 30447.74 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 46.91 603.11 26-MAR-17:10 3634.69 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 10.55 43.94 01-JAN-08:50 1474.14 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 10.55 43.94 01-JAN-08:50 1474.14 25-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_2 30.20 388.67 26-MAR-17:10 2318.44 12-DEC-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 6.76 28.32 01-JAN-07:50 926.10 12-DEC-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 6.76 28.32 01-JAN-07:50 926.10 12-DEC-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 46.79 603.12 12-MAR-17:10 3622.90 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 10.43 43.94 01-JAN-07:50 1462.32 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 10.43 43.94 01-JAN-07:50 1462.32 25-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_4 30.19 388.67 26-FEB-18:10 2351.32 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 6.76 28.32 01-JAN-08:50 958.99 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 6.76 28.32 01-JAN-08:50 958.99 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_3 468.91 6031.15 12-MAR-17:10 36324.65 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 105.25 439.44 01-JAN-08:50 14719.13 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 105.25 439.44 01-JAN-08:50 14719.13 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_2 301.89 3886.70 26-MAR-17:10 23149.02 12-DEC-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 67.54 283.19 01-JAN-07:50 9225.60 12-DEC-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 67.54 283.19 01-JAN-07:50 9225.60 12-DEC-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 467.85 6031.24 12-MAR-17:10 36206.18 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 104.19 439.45 01-JAN-07:50 14600.33 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 104.19 439.45 01-JAN-07:50 14600.33 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_4 301.84 3886.68 26-FEB-18:10 23483.74 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 67.49 283.19 01-JAN-08:50 9560.41 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 67.49 283.19 01-JAN-08:50 9560.41 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_3 46.89 603.11 12-MAR-17:10 3632.08 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 10.52 43.94 01-JAN-08:50 1471.53 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 10.52 43.94 01-JAN-08:50 1471.53 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_2 30.19 388.67 26-MAR-17:10 2314.61 12-DEC-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 6.75 28.32 01-JAN-07:50 922.27 12-DEC-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 6.75 28.32 01-JAN-07:50 922.27 12-DEC-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 46.78 603.12 12-MAR-17:10 3620.22 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 10.42 43.94 01-JAN-07:50 1459.63 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 10.42 43.94 01-JAN-07:50 1459.63 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_4 30.18 388.67 26-FEB-18:10 2348.14 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 6.75 28.32 01-JAN-08:50 955.81 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 6.75 28.32 01-JAN-08:50 955.81 25-OCT-07:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7542.47 95139.07 01-JAN-00:10 383789.71 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 47.61 230.94 01-JAN-00:10 4157.19 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 47.61 230.94 01-JAN-00:10 4157.19 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 157.51 1966.20 01-JAN-00:10 8111.05 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1575.07 19661.97 01-JAN-00:10 81110.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 36.26 175.92 01-JAN-00:10 3166.31 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 36.26 175.92 01-JAN-00:10 3166.31 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 157.51 1966.20 01-JAN-00:10 8111.05 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 4647.09 3784.11 10-JAN-05:00 408407.02 16-AUG-14:10
HeatRejection:Electricity 1590.46 268.71 05-JAN-08:00 84322.72 02-JAN-11:00
General:HeatRejection:Electricity 1590.46 268.71 05-JAN-08:00 84322.72 02-JAN-11:00
Electricity:HVAC 4743.27 46080.62 15-JAN-06:00 384155.50 18-APR-15:10
ExteriorEquipment:Electricity 1909.29 28161.90 01-JAN-00:10 116886.75 25-OCT-07:20
Transformer:ExteriorEquipment:Electricity 54.67 979.82 01-JAN-00:10 3408.78 25-OCT-07:20
ElectricityPurchased:Facility 28728.18 308703.76 15-JAN-05:00 1767684.12 03-AUG-15:30
ElectricityPurchased:Plant 28728.18 308703.76 15-JAN-05:00 1767684.12 03-AUG-15:30
Cogeneration:ElectricityPurchased 28728.18 308703.76 15-JAN-05:00 1767684.12 03-AUG-15:30
General:Cogeneration:ElectricityPurchased 28728.18 308703.76 15-JAN-05:00 1767684.12 03-AUG-15:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 28728.18 308703.76 15-JAN-05:00 1767684.12 03-AUG-15:30
ElectricityNet:Plant 28728.18 308703.76 15-JAN-05:00 1767684.12 03-AUG-15:30
Cogeneration:ElectricityNet 28728.18 308703.76 15-JAN-05:00 1767684.12 03-AUG-15:30
General:Cogeneration:ElectricityNet 28728.18 308703.76 15-JAN-05:00 1767684.12 03-AUG-15:30
Fans:Electricity 2082.09 41296.78 01-JAN-10:10 262229.47 05-MAY-13:00
General:Fans:Electricity 2082.09 41296.78 01-JAN-10:10 262229.47 05-MAY-13:00
ExteriorLights:Electricity 350.49 0.00 01-JAN-07:30 40855.88 01-JAN-06:10
General:ExteriorLights:Electricity 350.49 0.00 01-JAN-07:30 40855.88 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 50.51 0.00 01-JAN-00:10 4520.72 02-JAN-10:10
General:HeatRecovery:Electricity 50.51 0.00 01-JAN-00:10 4520.72 02-JAN-10:10
Cooling:Electricity 4601.90 2604.72 23-JAN-07:10 425649.67 10-AUG-12:10
General:Cooling:Electricity 4601.90 2604.72 23-JAN-07:10 425649.67 10-AUG-12:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 338.97 0.00 01-JAN-00:10 100000.00 04-FEB-17:10
General:Humidifier:Electricity 338.97 0.00 01-JAN-00:10 100000.00 04-FEB-17:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 671.76 3357.88 01-JAN-00:10 58762.75 05-JUN-09:30
General:Pumps:Electricity 671.76 3357.88 01-JAN-00:10 58762.75 05-JUN-09:30
WIRED_LTG_ELECTRICITY 69.02 0.00 01-JAN-00:10 6724.81 25-OCT-07:20
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 719.71 7280.88 29-MAY-16:00 488547.59 06-FEB-06:10
NaturalGas:Plant 719.71 7280.88 29-MAY-16:00 488547.59 06-FEB-06:10
Heating:NaturalGas 74.83 0.00 01-JAN-00:10 481266.71 06-FEB-06:10
Boiler:Heating:NaturalGas 74.83 0.00 01-JAN-00:10 481266.71 06-FEB-06:10
WaterSystems:NaturalGas 644.87 7280.88 23-JAN-05:20 74962.80 23-JAN-12:20
Water Heater:WaterSystems:NaturalGas 644.87 7280.88 23-JAN-05:20 74962.80 23-JAN-12:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 24980.99 9068.80 23-JAN-07:10 2389555.32 07-AUG-14:50
PlantLoopCoolingDemand:HVAC 24980.99 9068.80 23-JAN-07:10 2389555.32 07-AUG-14:50
CoolingCoils:PlantLoopCoolingDemand 24980.99 9068.80 23-JAN-07:10 2389555.32 07-AUG-14:50


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 14198.37 0.00 01-JAN-00:10 0.00 13-JUN-14:10
Water:HVAC 126.10 0.00 01-JAN-00:10 0.00 13-FEB-05:20
Humidifier:Water 126.10 0.00 01-JAN-00:10 0.00 13-FEB-05:20
General:Humidifier:Water 126.10 0.00 01-JAN-00:10 0.00 13-FEB-05:20
MainsWater:Facility 14198.37 0.00 01-JAN-00:10 0.00 13-JUN-14:10
MainsWater:HVAC 126.10 0.00 01-JAN-00:10 0.00 13-FEB-05:20
Humidifier:MainsWater 126.10 0.00 01-JAN-00:10 0.00 13-FEB-05:20
General:Humidifier:MainsWater 126.10 0.00 01-JAN-00:10 0.00 13-FEB-05:20
Water:Plant 14072.27 0.00 01-JAN-00:10 0.00 13-JUN-14:10
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 14072.27 0.00 01-JAN-00:10 0.00 13-JUN-14:10
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 11792.10 0.00 01-JAN-00:10 0.00 13-JUN-14:10
General:HeatRejection:Water 11792.10 0.00 01-JAN-00:10 0.00 13-JUN-14:10
HeatRejection:MainsWater 11792.10 0.00 01-JAN-00:10 0.00 13-JUN-14:10
General:HeatRejection:MainsWater 11792.10 0.00 01-JAN-00:10 0.00 13-JUN-14:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 96642.84 104334.55 10-JAN-05:40 9409797.36 06-OCT-14:10
EnergyTransfer:Building 20813.85 92573.88 22-JAN-08:00 1570392.32 30-AUG-16:00
EnergyTransfer:Zone:BASEMENT 692.43 0.00 01-JAN-00:10 77900.88 13-NOV-06:10
Heating:EnergyTransfer 34.20 0.00 01-JAN-00:10 257062.08 06-FEB-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.28 0.00 01-JAN-00:10 23527.41 22-JUL-16:10
General:Heating:EnergyTransfer 34.20 0.00 01-JAN-00:10 257062.08 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.28 0.00 01-JAN-00:10 23527.41 22-JUL-16:10
Cooling:EnergyTransfer 20779.65 92060.98 22-JAN-08:00 1570392.32 30-AUG-16:00
Cooling:EnergyTransfer:Zone:BASEMENT 688.15 0.00 01-JAN-00:10 77900.88 13-NOV-06:10
General:Cooling:EnergyTransfer 20779.65 92060.98 22-JAN-08:00 1570392.32 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:BASEMENT 688.15 0.00 01-JAN-00:10 77900.88 13-NOV-06:10
EnergyTransfer:Zone:CORE_BOTTOM 706.11 0.00 01-JAN-00:10 53016.57 13-NOV-06:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 706.11 0.00 01-JAN-00:10 53016.57 13-NOV-06:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 706.11 0.00 01-JAN-00:10 53016.57 13-NOV-06:10
EnergyTransfer:Zone:CORE_MID 5206.69 0.00 01-JAN-00:10 419594.97 25-FEB-06:10
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 5206.69 0.00 01-JAN-00:10 419594.97 25-FEB-06:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 5206.69 0.00 01-JAN-00:10 419594.97 25-FEB-06:10
EnergyTransfer:Zone:CORE_TOP 526.73 0.00 01-JAN-00:10 53793.79 16-MAY-16:00
Heating:EnergyTransfer:Zone:CORE_TOP 0.40 0.00 01-JAN-00:10 45530.16 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 0.40 0.00 01-JAN-00:10 45530.16 06-FEB-05:20
Cooling:EnergyTransfer:Zone:CORE_TOP 526.33 0.00 01-JAN-00:10 53793.79 16-MAY-16:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 526.33 0.00 01-JAN-00:10 53793.79 16-MAY-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 103.14 0.00 01-JAN-00:10 11492.76 21-AUG-14:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 103.14 0.00 01-JAN-00:10 11492.76 21-AUG-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 103.14 0.00 01-JAN-00:10 11492.76 21-AUG-14:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 80.28 0.00 01-JAN-00:10 11653.00 12-JUN-08:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 171.54 21-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 171.54 21-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 80.28 0.00 01-JAN-00:10 11653.00 12-JUN-08:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 80.28 0.00 01-JAN-00:10 11653.00 12-JUN-08:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 136.41 0.00 01-JAN-00:10 17444.74 06-NOV-14:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 346.10 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 346.10 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 136.41 0.00 01-JAN-00:10 17444.74 06-NOV-14:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 136.41 0.00 01-JAN-00:10 17444.74 06-NOV-14:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 121.36 0.00 01-JAN-00:10 16797.78 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 121.36 0.00 01-JAN-00:10 16797.78 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 121.36 0.00 01-JAN-00:10 16797.78 30-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 796.82 0.00 01-JAN-00:10 101674.49 21-AUG-14:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 4.48 0.00 01-JAN-00:10 64042.28 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 4.48 0.00 01-JAN-00:10 64042.28 06-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 792.34 0.00 01-JAN-00:10 101674.49 21-AUG-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 792.34 0.00 01-JAN-00:10 101674.49 21-AUG-14:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 687.56 0.00 01-JAN-00:10 122372.38 20-JUL-10:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.86 0.00 01-JAN-00:10 34363.40 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.86 0.00 01-JAN-00:10 34363.40 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 685.70 0.00 01-JAN-00:10 122372.38 20-JUL-10:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 685.70 0.00 01-JAN-00:10 122372.38 20-JUL-10:10
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1166.58 0.00 01-JAN-00:10 171757.18 06-NOV-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.92 0.00 01-JAN-00:10 37325.88 21-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.92 0.00 01-JAN-00:10 37325.88 21-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1165.66 0.00 01-JAN-00:10 171757.18 06-NOV-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1165.66 0.00 01-JAN-00:10 171757.18 06-NOV-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 752.64 0.00 01-JAN-00:10 138302.94 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.85 0.00 01-JAN-00:10 26066.23 21-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.85 0.00 01-JAN-00:10 26066.23 21-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 751.79 0.00 01-JAN-00:10 138302.94 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 751.79 0.00 01-JAN-00:10 138302.94 30-AUG-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 84.08 0.00 01-JAN-00:10 13144.61 06-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.91 0.00 01-JAN-00:10 13144.61 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.91 0.00 01-JAN-00:10 13144.61 06-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 81.18 0.00 01-JAN-00:10 11177.88 21-AUG-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 81.18 0.00 01-JAN-00:10 11177.88 21-AUG-14:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 74.27 0.00 01-JAN-00:10 12447.56 03-MAY-09:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 1.25 0.00 01-JAN-00:10 9241.76 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 1.25 0.00 01-JAN-00:10 9241.76 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 73.02 0.00 01-JAN-00:10 12447.56 03-MAY-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 73.02 0.00 01-JAN-00:10 12447.56 03-MAY-09:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 118.11 0.00 01-JAN-00:10 18441.28 06-NOV-13:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 1.20 0.00 01-JAN-00:10 13162.22 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 1.20 0.00 01-JAN-00:10 13162.22 06-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 116.91 0.00 01-JAN-00:10 18441.28 06-NOV-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 116.91 0.00 01-JAN-00:10 18441.28 06-NOV-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 77.65 0.00 01-JAN-00:10 14592.31 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.83 0.00 01-JAN-00:10 7958.60 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.83 0.00 01-JAN-00:10 7958.60 06-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 76.82 0.00 01-JAN-00:10 14592.31 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 76.82 0.00 01-JAN-00:10 14592.31 30-AUG-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 80.04 0.00 01-JAN-00:10 9178.32 10-OCT-09:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.74 0.00 01-JAN-00:10 3391.14 31-DEC-10:30
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.74 0.00 01-JAN-00:10 3391.14 31-DEC-10:30
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 79.31 0.00 01-JAN-00:10 9178.32 10-OCT-09:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 79.31 0.00 01-JAN-00:10 9178.32 10-OCT-09:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 565.56 0.00 01-JAN-00:10 78152.49 16-MAY-15:50
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 8.81 0.00 01-JAN-00:10 27020.87 31-DEC-11:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 8.81 0.00 01-JAN-00:10 27020.87 31-DEC-11:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 556.75 0.00 01-JAN-00:10 78152.49 16-MAY-15:50
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 556.75 0.00 01-JAN-00:10 78152.49 16-MAY-15:50
EnergyTransfer:Zone:TOPFLOOR_PLENUM 97.91 0.00 01-JAN-00:10 22026.79 03-MAY-13:50
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 5.54 0.00 01-JAN-00:10 15521.52 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 5.54 0.00 01-JAN-00:10 15521.52 06-FEB-06:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 92.37 0.00 01-JAN-00:10 22026.79 03-MAY-13:50
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 92.37 0.00 01-JAN-00:10 22026.79 03-MAY-13:50
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.86 1001.04 05-JAN-08:00 8003.70 16-APR-18:20
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.86 1001.04 05-JAN-08:00 8003.70 16-APR-18:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.86 1001.04 05-JAN-08:00 8003.70 16-APR-18:20
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1299.31 2285.36 10-JAN-06:20 74927.77 16-APR-18:20
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1299.31 2285.36 10-JAN-06:20 74927.77 16-APR-18:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1299.31 2285.36 10-JAN-06:20 74927.77 16-APR-18:20
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 126.84 0.95 08-JAN-21:10 7684.36 23-APR-18:10
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.14 0.00 01-JAN-00:10 527.15 10-JAN-04:20
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.14 0.00 01-JAN-00:10 527.15 10-JAN-04:20
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 126.70 0.00 04-JAN-03:30 7684.36 23-APR-18:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 126.70 0.00 04-JAN-03:30 7684.36 23-APR-18:10
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7171.48 88002.39 22-JAN-06:00 369861.43 09-AUG-21:10
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7171.48 88002.39 22-JAN-06:00 369861.43 09-AUG-21:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7171.48 88002.39 22-JAN-06:00 369861.43 09-AUG-21:10
PlantLoopHeatingDemand:Facility 373.89 0.00 01-JAN-00:10 384329.53 06-FEB-06:10
PlantLoopHeatingDemand:Plant 321.87 0.00 01-JAN-00:10 40632.95 23-JAN-12:50
WaterSystems:PlantLoopHeatingDemand 321.87 0.00 01-JAN-00:10 40632.95 23-JAN-12:50
General:WaterSystems:PlantLoopHeatingDemand 321.87 0.00 01-JAN-00:10 40632.95 23-JAN-12:50
EnergyTransfer:HVAC 25488.11 11287.13 23-JAN-05:50 2660222.75 07-AUG-13:00
HeatingCoils:EnergyTransfer 52.02 0.00 01-JAN-00:10 379392.58 06-FEB-06:10
PlantLoopHeatingDemand:HVAC 52.02 0.00 01-JAN-00:10 379392.58 06-FEB-06:10
HeatingCoils:PlantLoopHeatingDemand 52.02 0.00 01-JAN-00:10 379392.58 06-FEB-06:10
CoolingCoils:EnergyTransfer 22763.96 6464.08 23-JAN-07:10 2247480.00 07-AUG-14:50
HeatRecoveryForHeating:EnergyTransfer 16.90 0.00 01-JAN-00:10 178656.89 20-DEC-08:00
HeatRecoveryForCooling:EnergyTransfer 2655.23 0.00 01-JAN-00:10 687620.67 22-JUL-16:00
EnergyTransfer:Plant 50340.88 0.00 01-JAN-00:10 5830582.42 16-AUG-14:10
LoopToLoop:EnergyTransfer 15868.36 0.00 01-JAN-00:10 1740722.74 06-OCT-14:10
WaterSystems:EnergyTransfer 321.87 0.00 01-JAN-00:10 40632.95 23-JAN-12:50
WaterUse:WaterSystems:EnergyTransfer 321.87 0.00 01-JAN-00:10 40632.95 23-JAN-12:50
Boilers:EnergyTransfer 51.36 0.00 01-JAN-00:10 392504.32 06-FEB-06:10
Chillers:EnergyTransfer 15857.21 0.00 01-JAN-00:10 1923036.79 16-AUG-14:10
HeatRejection:EnergyTransfer 18242.08 0.00 01-JAN-00:10 2197083.17 16-AUG-14:10
General:HeatRejection:EnergyTransfer 18242.08 0.00 01-JAN-00:10 2197083.17 16-AUG-14:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.278 -688.155 0.000 0.000 92.688 165.729 424.397 0.000 0.000 0.000 1.063 0.000 0.000 0.000 0.000 -0.001
CORE_BOTTOM 0.000 0.000 0.000 -706.106 0.000 0.000 83.479 148.837 289.614 0.000 0.000 0.000 184.177 0.000 0.000 0.000 0.000 -0.003
CORE_MID 0.000 0.000 0.000 -5206.679 0.000 0.000 839.375 1488.366 2896.128 0.000 0.000 0.000 0.087 0.000 0.000 0.000 0.000 -17.190
CORE_TOP 0.000 0.000 0.398 -526.328 0.000 0.000 85.135 148.837 289.613 0.000 0.000 0.000 2.345 0.000 0.000 0.000 0.000 -0.002
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -103.134 0.000 0.000 10.563 10.545 36.365 41.147 0.000 0.399 36.137 0.000 -30.235 0.000 -1.788 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -80.276 0.000 0.000 6.779 6.762 23.435 59.966 0.000 0.259 2.768 0.000 -18.492 0.000 -1.201 -0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.000 -136.406 0.000 0.000 10.500 10.429 36.366 103.524 0.000 0.378 5.777 0.000 -28.665 0.000 -1.903 -0.001
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -121.360 0.000 0.000 6.742 6.759 23.435 57.135 0.000 0.217 52.205 0.000 -23.663 0.000 -1.470 -0.001
PERIMETER_MID_ZN_3 0.000 0.000 4.478 -792.320 0.000 0.000 108.040 105.252 363.654 423.080 0.000 8.898 84.271 0.000 -268.704 0.000 -36.649 0.000
PERIMETER_MID_ZN_2 0.000 0.000 1.856 -685.685 0.000 0.000 50.089 67.539 234.352 594.959 0.000 5.185 0.016 0.000 -176.919 0.000 -26.898 -64.478
PERIMETER_MID_ZN_1 0.000 0.000 0.924 -1165.633 0.000 0.000 105.497 104.189 363.660 1032.486 0.000 8.198 0.044 0.000 -276.844 0.000 -43.440 -129.036
PERIMETER_MID_ZN_4 0.000 0.000 0.846 -751.773 0.000 0.000 68.603 67.492 234.351 584.569 0.000 5.145 16.680 0.000 -197.342 0.000 -28.570 -0.004
PERIMETER_TOP_ZN_3 0.000 0.000 2.906 -81.173 0.000 0.000 10.912 10.524 36.365 42.137 0.000 1.027 6.991 0.000 -25.457 0.000 -4.234 0.000
PERIMETER_TOP_ZN_2 0.000 0.000 1.253 -73.019 0.000 0.000 6.888 6.754 23.435 59.635 0.000 0.621 0.003 0.000 -16.811 0.000 -3.105 -5.652
PERIMETER_TOP_ZN_1 0.000 0.000 1.203 -116.904 0.000 0.000 10.627 10.419 36.366 102.973 0.000 0.952 0.001 0.000 -26.552 0.000 -5.103 -13.981
PERIMETER_TOP_ZN_4 0.000 0.000 0.832 -76.814 0.000 0.000 6.919 6.749 23.435 58.236 0.000 0.611 2.316 0.000 -18.920 0.000 -3.364 -0.000
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -141.864 0.000 0.000 0.948 3.626 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -16.592
DATACENTER_MID_ZN_6 0.000 0.000 0.000 -1299.313 0.000 0.000 9.486 36.263 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -285.242
DATACENTER_TOP_ZN_6 0.000 0.000 0.140 -126.701 0.000 0.000 0.949 3.626 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -31.895
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7171.490 0.000 0.000 20.099 47.611 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -391.078
GROUNDFLOOR_PLENUM 0.738 -79.307 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.681 81.908 0.000 0.000 0.000 -4.021 0.000
MIDFLOOR_PLENUM 8.809 -556.740 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 12.574 602.679 0.000 0.000 0.000 -67.322 0.000
TOPFLOOR_PLENUM 5.539 -92.367 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.070 92.711 0.000 0.000 0.000 -6.953 0.000
Total Facility 15.086 -728.414 19.114 -20051.135 0.000 0.000 1534.319 2456.309 14676.396 3159.846 0.000 46.214 1172.182 0.000 -1108.603 0.000 -236.020 -955.155


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 26-DEC-05:11 0.00 0.00 0.00 -108224.63 0.00 0.00 0.00 598.35 13457.54 0.00 0.00 0.00 94168.74 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 02-OCT-04:13 0.00 0.00 0.00 -90246.51 0.00 0.00 0.00 537.36 5937.65 0.00 0.00 0.00 83771.51 0.00 -0.00 0.00 0.00 0.00
CORE_MID 16-MAY-04:13 0.00 0.00 0.00 -770977.85 0.00 0.00 0.00 5373.60 59376.23 0.00 0.00 0.00 706228.02 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 31-MAY-04:13 0.00 0.00 0.00 -75080.38 0.00 0.00 0.00 537.36 5937.62 0.00 0.00 0.00 68605.39 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 25-JUN-16:21 0.00 0.00 0.00 -15762.91 0.00 0.00 42.43 43.94 720.18 5577.75 0.00 45.65 9332.95 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24-SEP-09:32 0.00 0.00 0.00 -19269.65 0.00 0.00 22.46 28.32 464.11 12664.64 0.00 10.62 6079.49 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 11-NOV-13:51 0.00 0.00 0.00 -22600.59 0.00 0.00 33.03 43.94 720.19 18787.67 0.00 0.00 3099.44 0.00 -0.00 0.00 -83.70 0.00
PERIMETER_BOT_ZN_4 25-JUN-16:21 0.00 0.00 0.00 -25261.27 0.00 0.00 19.50 28.32 464.11 12000.94 0.00 20.18 12728.22 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 10-SEP-14:31 0.00 0.00 0.00 -148148.21 0.00 0.00 425.50 439.44 7201.84 53265.85 0.00 2796.61 84018.98 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 23-APR-09:32 0.00 0.00 0.00 -204052.43 0.00 0.00 216.78 283.19 4641.14 128988.27 0.00 0.00 70900.11 0.00 -0.00 0.00 -977.06 0.00
PERIMETER_MID_ZN_1 16-JAN-14:32 0.00 0.00 0.00 -213663.15 0.00 0.00 344.62 439.45 7201.95 192714.30 0.00 0.00 13859.11 0.00 -0.00 0.00 -896.27 0.00
PERIMETER_MID_ZN_4 09-OCT-16:31 0.00 0.00 0.00 -211904.61 0.00 0.00 220.74 283.19 4641.11 92802.82 0.00 0.00 114310.16 0.00 -0.00 0.00 -353.42 0.00
PERIMETER_TOP_ZN_3 10-SEP-14:31 0.00 0.00 0.00 -17589.17 0.00 0.00 39.78 43.94 720.18 5126.31 0.00 322.01 11336.94 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 29-MAY-10:01 0.00 0.00 0.00 -21442.82 0.00 0.00 20.09 28.32 464.11 10494.17 0.00 0.00 10437.24 0.00 -0.00 0.00 -1.13 0.00
PERIMETER_TOP_ZN_1 10-DEC-14:11 0.00 0.00 0.00 -25081.87 0.00 0.00 29.72 43.94 720.19 20282.49 0.00 0.00 4145.91 0.00 -0.00 0.00 -140.40 0.00
PERIMETER_TOP_ZN_4 10-SEP-14:31 0.00 0.00 0.00 -23162.37 0.00 0.00 20.64 28.32 464.11 10730.42 0.00 188.93 11729.95 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 16-APR-18:12 0.00 0.00 0.00 -8003.66 0.00 0.00 0.00 17.59 7794.42 0.00 0.00 0.00 191.65 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 16-APR-18:12 0.00 0.00 0.00 -74927.39 0.00 0.00 0.00 175.92 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -3192.75
DATACENTER_TOP_ZN_6 23-APR-18:04 0.00 0.00 0.00 -7684.36 0.00 0.00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -127.65
DATACENTER_BASEMENT_ZN_6 09-AUG-21:02 0.00 0.00 0.00 -370757.38 0.00 0.00 109.55 461.93 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -9446.61
GROUNDFLOOR_PLENUM 05-SEP-05:13 0.00 -12110.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12165.95 0.00 -0.00 0.00 -55.02 0.00
MIDFLOOR_PLENUM 25-SEP-05:02 0.00 -85239.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85780.21 0.00 -0.00 0.00 -540.97 0.00
TOPFLOOR_PLENUM 03-MAY-13:50 0.00 -22025.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 77.87 21947.77 0.00 -0.00 0.00 0.00 0.00
Total Facility 31-AUG-05:02 0.00 -66771.62 0.00 -1757785.70 0.00 0.00 16298.36 10593.62 616289.16 0.00 0.00 0.03 1219162.65 0.00 -37776.18 0.00 -10.31 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 22-JUL-16:01 0.00 0.00 25148.33 0.00 0.00 0.00 520.12 819.05 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -39945.05
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 06-FEB-05:11 0.00 0.00 55613.14 0.00 0.00 0.00 0.00 537.36 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -62088.12
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 21-DEC-06:01 0.00 0.00 1200.80 0.00 0.00 0.00 90.12 43.48 618.82 0.00 0.00 0.00 1760.00 0.00 -3645.03 0.00 -68.19 0.00
PERIMETER_BOT_ZN_1 06-FEB-06:03 0.00 0.00 1384.40 0.00 0.00 0.00 139.94 67.47 960.26 0.00 0.00 0.00 2104.18 0.00 -4603.23 0.00 -53.02 0.00
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 06-FEB-05:11 0.00 0.00 112859.74 0.00 0.00 0.00 0.00 674.71 7455.61 0.00 0.00 0.00 0.00 0.00 -40551.26 0.00 -4467.68 -75971.11
PERIMETER_MID_ZN_2 06-FEB-05:11 0.00 0.00 90119.67 0.00 0.00 0.00 0.00 434.81 4804.68 0.00 0.00 0.00 0.00 0.00 -27966.28 0.00 -3092.64 -64300.24
PERIMETER_MID_ZN_1 21-JAN-06:02 0.00 0.00 114950.02 0.00 0.00 0.00 1456.45 674.72 9602.60 0.00 0.00 0.00 0.00 0.00 -52790.22 0.00 -3507.94 -70385.63
PERIMETER_MID_ZN_4 10-JAN-05:01 0.00 0.00 74806.55 0.00 0.00 0.00 0.00 434.81 4804.65 0.00 0.00 0.00 0.00 0.00 -33432.35 0.00 -5928.56 -40685.10
PERIMETER_TOP_ZN_3 05-FEB-08:63 0.00 0.00 14740.32 0.00 0.00 0.00 88.54 61.02 720.18 0.00 0.00 0.00 0.00 0.00 -4024.53 0.00 -2188.57 -9396.96
PERIMETER_TOP_ZN_2 06-FEB-05:11 0.00 0.00 13038.37 0.00 0.00 0.00 0.00 43.48 480.47 0.00 0.00 0.00 0.00 0.00 -2225.85 0.00 -318.14 -11018.33
PERIMETER_TOP_ZN_1 06-FEB-05:11 0.00 0.00 17124.24 0.00 0.00 0.00 0.00 67.47 745.57 0.00 0.00 0.00 0.00 0.00 -3455.93 0.00 -484.14 -13997.22
PERIMETER_TOP_ZN_4 06-FEB-05:11 0.00 0.00 12503.86 0.00 0.00 0.00 0.00 43.48 480.46 0.00 0.00 0.00 0.00 0.00 -2414.62 0.00 -332.93 -10280.25
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 05-JAN-04:45 0.00 0.00 528.31 0.00 0.00 0.00 0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2494.50
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 26-DEC-05:11 9970.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -785.08 -9185.53
MIDFLOOR_PLENUM 16-JAN-15:52 82445.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 485.00 0.00 0.00 -0.00 0.00 0.00 -82930.07
TOPFLOOR_PLENUM 06-FEB-05:42 17811.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -723.21 -17087.83
Total Facility 21-DEC-06:01 -846465.05 801812.81 466202.95 -801812.81 0.00 0.00 19273.63 10593.62 616289.16 0.00 0.00 0.00 0.00 0.00 -206987.73 0.00 -13690.52 -45216.06



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 9.8107 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.7061 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 92.3247 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 80.5714 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 9.5131 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.9032 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.2218 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.2218 0.2298 1.0000 Not calculated 1.2002 0.2298    
AIRLOOP DATACENTER BASEMENT 21.2936 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.2938 0.0159 1.0000 Not calculated 0.3384 0.0159    
AIRLOOP DATACENTER BOT 0.4650 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4650 0.0336 1.0000 Not calculated 0.0156 0.0336    
AIRLOOP DATACENTER MID 4.4328 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.4328 0.0353 1.0000 Not calculated 0.1563 0.0353    
AIRLOOP DATACENTER TOP 0.4520 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4520 0.0346 1.0000 Not calculated 0.0156 0.0346    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 4.9053 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2820 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 46.1624 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.8412 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 4.7565 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2824 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.2218 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.2218 1.0000 1.0000 Not calculated 1.2002 0.2298    
AIRLOOP DATACENTER BASEMENT 21.2936 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.2936 1.0000 1.0000 Not calculated 0.3384 0.0159    
AIRLOOP DATACENTER BOT 0.4650 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4650 1.0000 1.0000 Not calculated 0.0156 0.0336    
AIRLOOP DATACENTER MID 4.4328 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.4328 1.0000 1.0000 Not calculated 0.1563 0.0353    
AIRLOOP DATACENTER TOP 0.4520 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4520 1.0000 1.0000 Not calculated 0.0156 0.0346    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.2218 5.2218 5.2218 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.4217 5.4217 1.6157 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 50.6848 50.6848 16.1685 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.0145 5.0145 1.6147 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9144 0.9144 0.2030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0278 1.0278 0.1305 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1446 1.1446 0.2026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3021 1.3021 0.1302 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.5942 8.5942 2.0282 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.7033 10.7033 1.3058 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.9901 10.9901 2.0332 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.3523 11.3523 1.3055 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9817 0.9817 0.2032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0867 1.0867 0.1304 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2135 1.2135 0.2027 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2166 1.2166 0.1314 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4650 0.4650 0.4650 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.4328 4.4328 4.4328 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4520 0.4520 0.4520 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.2936 21.2936 21.2936 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 9.8107 8.7061 9.8107 2.2820 0.0000 1.0000
VAV_MID WITH REHEAT 92.3247 80.5714 92.3247 22.8412 0.0000 1.0000
VAV_TOP WITH REHEAT 9.5131 8.9032 9.5131 2.2824 0.0000 1.0000
CAV_BAS 5.2218 5.2218 5.2218 5.2218 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.2936 21.2938 21.2936 21.2936 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4650 0.4650 0.4650 0.4650 0.0156 1.0000
AIRLOOP DATACENTER MID 4.4328 4.4328 4.4328 4.4328 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4520 0.4520 0.4520 0.4520 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.2218 5.2218 5.2218 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.7108 2.7108 1.6157 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 25.3424 25.3424 16.1685 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.5073 2.5073 1.6147 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4572 0.4572 0.2030 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5139 0.5139 0.1305 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5723 0.5723 0.2026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6511 0.6511 0.1302 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.2971 4.2971 2.0282 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.3516 5.3516 1.3058 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.4951 5.4951 2.0332 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.6762 5.6762 1.3055 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4909 0.4909 0.2032 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5433 0.5433 0.1304 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6068 0.6068 0.2027 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6083 0.6083 0.1314 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4650 0.4650 0.4650 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.4328 4.4328 4.4328 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4520 0.4520 0.4520 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.2936 21.2936 21.2936 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 4.9053 2.2820 2.2820 2.2820 0.0000 1.0000
VAV_MID WITH REHEAT 46.1624 22.8412 22.8412 22.8412 0.0000 1.0000
VAV_TOP WITH REHEAT 4.7565 2.2824 2.2824 2.2824 0.0000 1.0000
CAV_BAS 5.2218 5.2218 5.2218 5.2218 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.2936 21.2936 21.2936 21.2936 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4650 0.4650 0.4650 0.4650 0.0156 1.0000
AIRLOOP DATACENTER MID 4.4328 4.4328 4.4328 4.4328 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4520 0.4520 0.4520 0.4520 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1.33
Number of hours cooling loads not met 803.17
Number of hours not met 804.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 74.83 481266.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 4601.90 425649.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 2456.31 239317.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 350.49 40855.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 54.67 3408.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2082.09 262229.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 671.76 58762.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1590.46 84322.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 338.97 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 50.51 4520.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 644.87 74962.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 28728.18
Natural Gas 0.00 719.71
Additional 0.00 0.00
Total 14676.40 29447.89


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 53.03
Space Heating 0.00
Space Cooling 99.35
Fans (All) 44.95
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 620.21
Subtotal 620.21


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 1.62
Service Water Heating 13.92
Miscellaneous (All) 15.54
Subtotal 15.54


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 8.34
Space Heating 0.25
Space Cooling 15.63
Fans (All) 7.07
Service Water Heating 2.19
Receptacle Equipment 49.84
Miscellaneous 16.68


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2625. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 955. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 7471.50 1288.50 0.00 0.00 0.00
CORE_BOTTOM 8731.33 28.67 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8726.33 33.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8594.67 165.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8576.67 183.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7358.50 1401.50 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8694.67 65.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8429.50 330.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8458.33 301.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7947.17 812.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8582.50 177.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8329.67 430.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8357.33 402.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7878.50 881.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 3539.67 5220.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 3622.00 5138.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 3574.83 5185.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 2179.00 6581.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8488.00 272.00 0.00 0.00 0.00
Min 2179.00 0.00 0.00 0.00 0.00
Max 8760.00 6581.00 0.00 0.00 0.00
Average 7503.49 1256.51 0.00 0.00 0.00
Sum 172580.17 28899.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 364945.67 3670.33 0.00 0.00 0.00
CORE_BOTTOM 330771.00 42.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 543.83 1724.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 540.33 1727.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 534.17 1733.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 25089.83 78305.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 364945.67 78305.17 0.00 0.00 0.00
Average 76543.47 3791.44 0.00 0.00 0.00
Sum 1760499.83 87203.17 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 3946.50 4813.50 0.00 0.00 0.00
CORE_BOTTOM 8437.83 322.17 0.00 0.00 0.00
CORE_MID 8751.00 9.00 0.00 0.00 0.00
CORE_TOP 8725.67 34.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8013.83 746.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 7927.50 832.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 7795.33 964.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 6329.67 2430.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 6946.50 1813.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 6770.17 1989.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 6696.67 2063.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 6546.83 2213.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 6852.33 1907.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 6708.17 2051.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 6628.17 2131.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 6519.17 2240.83 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 5772.83 2987.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 5761.67 2998.33 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 5733.00 3027.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 4382.50 4377.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8485.67 274.33 0.00 0.00 0.00
MIDFLOOR_PLENUM 7773.33 986.67 0.00 0.00 0.00
TOPFLOOR_PLENUM 7363.67 1396.33 0.00 0.00 0.00
Min 3946.50 9.00 0.00 0.00 0.00
Max 8751.00 4813.50 0.00 0.00 0.00
Average 6907.30 1852.70 0.00 0.00 0.00
Sum 158868.00 42612.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 269140.50 99475.50 0.00 0.00 0.00
CORE_BOTTOM 330434.00 379.00 0.00 0.00 0.00
CORE_MID 330760.00 53.00 0.00 0.00 0.00
CORE_TOP 330740.00 73.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38924.67 0.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24908.67 0.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38924.67 0.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38904.83 20.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18335.50 18.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38907.33 17.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24895.67 13.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38896.33 28.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24881.17 27.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38897.50 27.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24886.00 23.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 744.50 1523.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 735.50 1532.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 721.50 1546.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 30754.83 72640.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 330760.00 99475.50 0.00 0.00 0.00
Average 72621.83 7713.08 0.00 0.00 0.00
Sum 1670302.17 177400.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:31

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.551205E+11 105120.73 09-JAN-05:11 7.67 5.62 0.566742E+10 7499.33 12-JAN-10:09 18.17 17.41
February 0.483212E+11 106438.71 13-FEB-05:11 5.53 1.73 0.513959E+10 7499.16 07-FEB-10:09 5.53 1.73
March 0.556503E+11 106693.06 20-MAR-04:12 12.27 8.01 0.613227E+10 7499.56 23-MAR-09:09 16.78 14.63
April 0.511346E+11 106031.03 17-APR-04:11 12.83 10.47 0.544848E+10 7499.28 12-APR-13:20 12.83 10.47
May 0.553703E+11 78135.42 29-MAY-18:40 28.67 23.49 0.590171E+10 7517.75 31-MAY-09:39 28.70 23.62
June 0.552846E+11 79959.40 12-JUN-03:02 23.90 21.55 0.588098E+10 7608.75 05-JUN-09:39 23.90 21.55
July 0.571989E+11 76319.07 05-JUL-03:13 25.60 24.04 0.547300E+10 7498.96 14-JUL-09:20 24.27 23.35
August 0.669427E+11 81566.65 21-AUG-03:02 26.27 23.88 0.613906E+10 7498.94 11-AUG-09:20 26.27 23.88
September 0.597162E+11 80036.43 04-SEP-12:28 26.70 24.76 0.545387E+10 7514.49 25-SEP-09:00 25.50 23.54
October 0.628831E+11 102293.16 17-OCT-04:12 17.33 12.72 0.567295E+10 7608.90 10-OCT-09:30 17.33 12.72
November 0.612826E+11 105194.28 24-NOV-05:12 11.23 9.85 0.561707E+10 7580.87 06-NOV-10:00 11.23 9.85
December 0.592466E+11 108228.75 26-DEC-05:11 6.97 3.20 0.547324E+10 7499.62 08-DEC-10:00 6.97 3.20
                     
Annual Sum or Average 0.688152E+12         0.679997E+11        
Minimum of Months 0.483212E+11 76319.07   5.53 1.73 0.513959E+10 7498.94   5.53 1.73
Maximum of Months 0.669427E+11 108228.75   28.67 24.76 0.613906E+10 7608.90   28.70 23.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.460543E+11 89293.25 02-JAN-05:13 16.67 15.63 0.506114E+10 6734.82 05-JAN-14:20 14.33 9.84
February 0.442522E+11 89854.16 27-FEB-05:13 17.77 17.77 0.459917E+10 6734.75 27-FEB-14:09 25.60 20.00
March 0.558681E+11 86053.83 06-MAR-05:13 19.07 18.30 0.549557E+10 6796.94 07-MAR-14:09 25.32 22.37
April 0.617380E+11 85326.87 04-APR-04:13 16.67 14.88 0.487601E+10 6816.89 26-APR-13:39 28.30 21.72
May 0.580530E+11 82063.38 16-MAY-04:13 23.30 22.20 0.528269E+10 6786.13 05-MAY-13:09 23.30 22.20
June 0.635100E+11 87122.00 01-JUN-04:13 21.50 20.44 0.526338E+10 6790.08 05-JUN-09:39 27.93 23.67
July 0.686022E+11 77020.87 17-JUL-05:03 23.98 22.54 0.488814E+10 6734.61 24-JUL-09:20 30.37 25.95
August 0.761456E+11 77969.94 07-AUG-05:03 24.17 23.42 0.549008E+10 6734.77 15-AUG-09:39 26.10 21.97
September 0.569339E+11 82865.54 22-SEP-04:13 21.70 20.03 0.487778E+10 6734.64 22-SEP-09:39 26.07 21.63
October 0.616502E+11 90251.74 02-OCT-04:13 18.03 15.02 0.507305E+10 6734.93 10-OCT-09:30 26.80 21.61
November 0.566709E+11 89116.55 13-NOV-05:11 9.93 8.14 0.502654E+10 6734.96 06-NOV-10:09 9.93 8.14
December 0.566275E+11 89542.52 26-DEC-05:12 6.97 3.20 0.489638E+10 6734.84 13-DEC-14:00 6.97 3.20
                     
Annual Sum or Average 0.706106E+12         0.608299E+11        
Minimum of Months 0.442522E+11 77020.87   6.97 3.20 0.459917E+10 6734.61   6.97 3.20
Maximum of Months 0.761456E+11 90251.74   24.17 23.42 0.549557E+10 6816.89   30.37 25.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.348209E+11 74121.26 02-JAN-05:12 16.67 15.63 0.496246E+10 6734.79 05-JAN-14:20 14.33 9.84
February 0.327225E+11 74261.38 28-FEB-05:12 18.50 18.07 0.451935E+10 6734.75 14-FEB-10:20 18.50 18.07
March 0.400948E+11 74267.55 31-MAR-04:12 16.90 16.90 0.542860E+10 6735.02 07-MAR-14:09 16.90 16.90
April 0.413781E+11 74706.77 26-APR-04:12 21.10 20.64 0.485481E+10 6734.99 26-APR-13:39 28.30 21.72
May 0.496631E+11 77102.93 16-MAY-04:13 23.30 22.20 0.527039E+10 6778.65 05-MAY-13:09 23.30 22.20
June 0.499167E+11 75694.10 07-JUN-04:12 21.10 18.59 0.525264E+10 6735.00 06-JUN-13:50 21.10 18.59
July 0.498454E+11 72864.86 12-JUL-04:12 23.50 23.01 0.487657E+10 6734.63 12-JUL-13:20 25.03 23.05
August 0.518816E+11 74996.27 17-AUG-04:12 21.93 21.62 0.548279E+10 6734.64 25-AUG-13:20 27.90 24.42
September 0.470245E+11 74240.52 28-SEP-04:12 22.20 20.76 0.485965E+10 6734.63 22-SEP-13:20 22.20 20.76
October 0.468354E+11 76268.47 17-OCT-04:12 17.33 12.72 0.505677E+10 6734.83 17-OCT-13:09 22.17 15.50
November 0.399858E+11 75343.39 07-NOV-05:11 20.63 19.75 0.498739E+10 6734.80 13-NOV-10:20 16.83 13.24
December 0.364999E+11 74670.93 14-DEC-05:11 20.00 20.00 0.481951E+10 6734.75 13-DEC-14:39 20.00 20.00
                     
Annual Sum or Average 0.520669E+12         0.603709E+11        
Minimum of Months 0.327225E+11 72864.86   16.67 12.72 0.451935E+10 6734.63   14.33 9.84
Maximum of Months 0.518816E+11 77102.93   23.50 23.01 0.548279E+10 6778.65   28.30 24.42



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.298125E+11 70466.58 20-JAN-06:03 17.00 17.00 0.458429E+10 6734.65 19-JAN-14:39 17.00 17.00
February 0.297958E+11 69692.91 03-FEB-06:03 18.90 18.50 0.429933E+10 6734.66 02-FEB-14:09 18.90 18.50
March 0.368270E+11 73106.10 30-MAR-05:04 20.83 19.77 0.524327E+10 6735.21 07-MAR-14:09 20.83 19.77
April 0.412304E+11 74282.85 15-APR-05:03 21.00 20.13 0.482677E+10 6819.87 26-APR-13:39 28.30 21.72
May 0.543452E+11 75084.65 31-MAY-04:13 23.17 21.09 0.527730E+10 6892.82 05-MAY-13:09 23.17 21.09
June 0.556528E+11 74489.28 07-JUN-04:12 21.10 18.59 0.526191E+10 6744.20 06-JUN-13:50 21.10 18.59
July 0.555690E+11 73153.90 12-JUL-04:12 23.50 23.01 0.488759E+10 6734.61 13-JUL-09:20 24.63 23.37
August 0.570107E+11 73616.78 17-AUG-04:12 21.93 21.62 0.548962E+10 6734.61 22-AUG-13:20 31.47 25.51
September 0.498903E+11 73512.16 22-SEP-04:12 21.70 20.03 0.486440E+10 6734.61 25-SEP-09:20 25.17 23.40
October 0.482987E+11 73825.97 02-OCT-04:11 18.03 15.02 0.504081E+10 6734.79 17-OCT-13:09 22.17 15.50
November 0.362940E+11 73460.15 08-NOV-05:12 19.80 19.09 0.486799E+10 6734.68 07-NOV-10:20 19.80 19.09
December 0.316036E+11 71622.39 15-DEC-06:04 21.00 21.00 0.452986E+10 6734.72 13-DEC-14:39 21.00 21.00
                     
Annual Sum or Average 0.526330E+12         0.591731E+11        
Minimum of Months 0.297958E+11 69692.91   17.00 15.02 0.429933E+10 6734.61   17.00 15.50
Maximum of Months 0.570107E+11 75084.65   23.50 23.01 0.548962E+10 6892.82   31.47 25.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.453639E+10 8535.70 02-JAN-05:12 16.67 15.63 0.600478E+09 845.62 19-JAN-14:39 25.00 21.54
February 0.474792E+10 8094.02 28-FEB-05:12 18.50 18.07 0.560707E+09 845.64 27-FEB-14:09 18.50 18.07
March 0.635923E+10 8467.56 28-MAR-12:30 27.45 22.17 0.677416E+09 854.69 07-MAR-14:09 27.45 22.17
April 0.856353E+10 10876.45 24-APR-05:02 20.08 20.03 0.610693E+09 858.17 26-APR-13:39 28.30 21.72
May 0.104418E+11 14282.73 07-MAY-14:42 32.98 23.21 0.664629E+09 864.95 05-MAY-13:09 32.98 23.21
June 0.119047E+11 15763.41 25-JUN-16:21 32.50 24.76 0.662314E+09 859.06 05-JUN-09:39 32.50 24.76
July 0.124373E+11 15408.04 23-JUL-16:22 31.95 26.59 0.615793E+09 845.61 14-JUL-13:20 31.95 26.59
August 0.132115E+11 13681.91 13-AUG-16:22 30.50 26.21 0.690603E+09 845.63 15-AUG-09:39 26.10 21.97
September 0.934830E+10 12358.05 24-SEP-15:31 30.50 25.57 0.613597E+09 845.63 20-SEP-13:50 30.50 25.57
October 0.927458E+10 15361.97 08-OCT-14:51 31.00 25.74 0.636464E+09 845.65 10-OCT-09:30 26.80 21.61
November 0.651678E+10 11947.28 01-NOV-04:11 22.53 22.30 0.625739E+09 845.65 06-NOV-10:09 24.08 20.08
December 0.579328E+10 7791.87 12-DEC-06:03 20.17 20.17 0.597971E+09 845.64 13-DEC-14:00 30.00 21.84
                     
Annual Sum or Average 0.103135E+12         0.755640E+10        
Minimum of Months 0.453639E+10 7791.87   16.67 15.63 0.560707E+09 845.61   18.50 18.07
Maximum of Months 0.132115E+11 15763.41   32.98 26.59 0.690603E+09 864.95   32.98 26.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.366154E+10 9670.45 16-JAN-10:03 19.67 17.45 0.401712E+09 544.96 24-JAN-14:20 17.00 10.45
February 0.392556E+10 15652.41 26-FEB-10:32 23.50 19.85 0.367791E+09 544.97 27-FEB-14:09 25.60 20.00
March 0.544209E+10 17838.98 26-MAR-09:32 24.77 20.03 0.439018E+09 551.17 07-MAR-14:09 24.77 20.03
April 0.691002E+10 17752.31 23-APR-09:02 24.68 20.67 0.393727E+09 553.52 26-APR-13:39 28.30 21.72
May 0.865300E+10 19255.94 14-MAY-08:42 27.93 23.47 0.428743E+09 550.07 05-MAY-13:09 27.93 23.47
June 0.921824E+10 17689.85 04-JUN-09:22 28.90 24.82 0.427009E+09 552.36 05-JUN-09:39 27.93 23.67
July 0.931190E+10 19242.53 16-JUL-09:41 30.73 25.53 0.397078E+09 544.94 14-JUL-13:20 30.73 25.53
August 0.941277E+10 16338.17 06-AUG-09:42 29.83 26.91 0.445044E+09 544.97 15-AUG-09:39 26.10 21.97
September 0.726888E+10 19266.85 24-SEP-09:32 29.03 25.00 0.395866E+09 544.97 22-SEP-09:39 29.03 25.00
October 0.728997E+10 17935.88 15-OCT-08:53 23.00 19.57 0.410706E+09 545.01 10-OCT-09:30 23.00 19.57
November 0.508313E+10 17668.81 11-NOV-09:13 24.40 21.68 0.404853E+09 545.01 06-NOV-10:09 24.40 21.68
December 0.409989E+10 7416.09 10-DEC-09:03 20.67 17.88 0.386586E+09 544.96 13-DEC-14:00 30.00 21.84
                     
Annual Sum or Average 0.802770E+11         0.489813E+10        
Minimum of Months 0.366154E+10 7416.09   19.67 17.45 0.367791E+09 544.94   17.00 10.45
Maximum of Months 0.941277E+10 19266.85   30.73 26.91 0.445044E+09 553.52   30.73 25.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.952263E+10 21429.73 01-JAN-13:32 25.67 18.12 0.626928E+09 909.28 19-JAN-14:39 25.00 21.54
February 0.909105E+10 21776.56 26-FEB-13:52 26.60 19.72 0.572361E+09 904.72 27-FEB-14:09 25.60 20.00
March 0.917872E+10 20484.94 05-MAR-13:23 27.70 18.32 0.678962E+09 861.78 07-MAR-14:09 25.32 22.37
April 0.100892E+11 14665.71 23-APR-11:43 27.10 20.37 0.610927E+09 867.42 26-APR-13:39 28.30 21.72
May 0.106621E+11 19119.78 07-MAY-14:42 32.98 23.21 0.664646E+09 860.72 05-MAY-13:09 32.98 23.21
June 0.115246E+11 19457.22 25-JUN-15:41 32.70 24.21 0.662216E+09 853.92 05-JUN-09:39 32.70 24.21
July 0.123509E+11 19263.83 30-JUL-14:12 28.70 24.43 0.615795E+09 845.63 14-JUL-13:20 28.70 24.43
August 0.143588E+11 19430.02 27-AUG-12:23 32.00 23.77 0.690853E+09 845.65 15-AUG-09:39 32.00 23.77
September 0.115272E+11 20507.12 17-SEP-14:42 31.60 25.84 0.614341E+09 845.66 20-SEP-13:50 26.60 22.72
October 0.142680E+11 21566.97 08-OCT-14:51 31.00 25.74 0.639526E+09 878.83 13-OCT-13:39 32.73 23.24
November 0.123499E+11 22601.03 11-NOV-13:51 26.10 22.85 0.633559E+09 950.90 06-NOV-14:20 26.10 22.85
December 0.114841E+11 21246.67 31-DEC-14:22 22.50 16.59 0.609636E+09 900.17 15-DEC-14:20 22.50 16.59
                     
Annual Sum or Average 0.136407E+12         0.761975E+10        
Minimum of Months 0.909105E+10 14665.71   22.50 16.59 0.572361E+09 845.63   22.50 16.59
Maximum of Months 0.143588E+11 22601.03   32.98 25.84 0.690853E+09 950.90   32.98 24.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.514027E+10 20044.73 01-JAN-15:32 25.00 18.55 0.404702E+09 544.97 19-JAN-14:39 25.00 21.54
February 0.626758E+10 23015.45 26-FEB-15:12 25.90 20.05 0.371849E+09 544.98 27-FEB-14:09 25.60 20.00
March 0.878693E+10 21252.91 26-MAR-15:32 25.33 20.03 0.445510E+09 553.13 07-MAR-14:09 25.33 20.03
April 0.120167E+11 23702.54 23-APR-16:22 27.45 21.85 0.396590E+09 557.14 26-APR-13:39 28.30 21.72
May 0.101945E+11 23357.99 29-MAY-16:12 32.07 23.52 0.429271E+09 550.82 05-MAY-13:09 32.07 23.52
June 0.122318E+11 25265.04 25-JUN-16:21 32.50 24.76 0.427919E+09 551.62 05-JUN-09:39 32.50 24.76
July 0.133265E+11 23893.92 30-JUL-16:52 27.20 24.74 0.398245E+09 544.94 14-JUL-13:20 27.20 24.74
August 0.159857E+11 23043.57 06-AUG-16:22 25.00 22.52 0.446514E+09 544.98 15-AUG-09:39 26.10 21.97
September 0.946098E+10 24646.37 17-SEP-15:21 31.90 25.65 0.396490E+09 544.96 20-SEP-13:50 26.60 22.72
October 0.106092E+11 24413.86 08-OCT-14:51 31.00 25.74 0.412306E+09 544.98 10-OCT-09:30 26.80 21.61
November 0.874196E+10 24256.00 11-NOV-14:31 26.43 22.96 0.407963E+09 544.99 06-NOV-10:09 26.43 22.96
December 0.859929E+10 22994.22 10-DEC-15:42 27.17 20.20 0.397552E+09 544.99 13-DEC-14:00 30.00 21.84
                     
Annual Sum or Average 0.121361E+12         0.493491E+10        
Minimum of Months 0.514027E+10 20044.73   25.00 18.55 0.371849E+09 544.94   25.00 20.00
Maximum of Months 0.159857E+11 25265.04   32.50 25.74 0.446514E+09 557.14   32.50 24.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.308116E+10 5231.09 31-JAN-14:40 25.00 21.54 0.543810E+09 845.61 02-JAN-14:20 25.00 21.54
February 0.333275E+10 5473.24 22-FEB-14:30 25.55 20.41 0.519779E+09 845.61 02-FEB-14:09 25.55 20.41
March 0.434548E+10 7034.45 30-MAR-13:30 28.55 22.55 0.634607E+09 845.66 07-MAR-14:09 28.55 22.55
April 0.573245E+10 9290.84 28-APR-05:03 22.80 21.69 0.600495E+09 845.67 26-APR-13:39 22.80 21.69
May 0.935682E+10 11147.17 13-MAY-04:12 22.20 20.38 0.664421E+09 865.76 05-MAY-13:09 22.20 20.38
June 0.101587E+11 12983.51 29-JUN-03:02 25.60 24.37 0.662440E+09 845.68 05-JUN-09:39 25.60 24.37
July 0.100089E+11 14430.23 23-JUL-16:22 31.95 26.59 0.616137E+09 845.61 14-JUL-13:20 31.95 26.59
August 0.994247E+10 13682.07 13-AUG-15:12 30.50 25.96 0.690940E+09 845.61 25-AUG-13:20 27.90 24.42
September 0.798397E+10 14813.07 10-SEP-14:31 35.67 27.27 0.612664E+09 845.61 20-SEP-13:50 26.60 22.72
October 0.726119E+10 10759.24 06-OCT-03:02 26.67 25.46 0.631535E+09 845.64 17-OCT-13:09 22.17 15.50
November 0.450163E+10 9969.94 02-NOV-05:03 23.38 22.55 0.598199E+09 845.61 06-NOV-14:20 28.30 20.91
December 0.352871E+10 5924.20 15-DEC-14:10 29.00 22.01 0.540355E+09 845.62 13-DEC-14:00 29.00 22.01
                     
Annual Sum or Average 0.792342E+11         0.731538E+10        
Minimum of Months 0.308116E+10 5231.09   22.20 20.38 0.519779E+09 845.61   22.17 15.50
Maximum of Months 0.101587E+11 14813.07   35.67 27.27 0.690940E+09 865.76   31.95 26.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.239071E+10 8765.59 19-JAN-11:05 24.92 21.49 0.284115E+09 548.49 24-JAN-13:09 17.00 10.00
February 0.287815E+10 10938.62 26-FEB-11:23 25.55 19.96 0.263590E+09 548.50 09-FEB-11:09 25.55 19.96
March 0.421510E+10 18395.91 26-MAR-09:43 25.13 20.13 0.315900E+09 548.52 15-MAR-12:09 25.13 20.13
April 0.572333E+10 20405.71 23-APR-09:32 25.53 20.92 0.289827E+09 548.51 10-APR-14:09 25.53 20.92
May 0.833117E+10 20392.01 14-MAY-09:22 28.60 23.59 0.316846E+09 548.50 09-MAY-14:09 28.60 23.59
June 0.865830E+10 19509.05 04-JUN-10:22 30.00 23.98 0.315350E+09 548.49 12-JUN-12:09 31.70 20.35
July 0.849161E+10 18836.35 16-JUL-09:52 31.10 25.83 0.294457E+09 548.49 05-JUL-12:09 31.10 25.83
August 0.832547E+10 18580.68 06-AUG-08:32 28.67 26.43 0.328819E+09 548.48 30-AUG-12:09 31.18 24.70
September 0.666264E+10 20066.53 10-SEP-08:32 33.30 26.76 0.292548E+09 548.48 01-SEP-10:09 33.30 26.76
October 0.638912E+10 19972.55 09-OCT-09:12 27.73 22.40 0.302599E+09 548.51 17-OCT-12:09 21.17 14.63
November 0.388269E+10 10477.59 02-NOV-10:05 27.88 24.05 0.295426E+09 548.49 13-NOV-11:09 18.77 14.38
December 0.262196E+10 7337.00 16-DEC-11:05 26.17 21.93 0.273360E+09 548.49 01-DEC-11:09 26.17 21.93
                     
Annual Sum or Average 0.685702E+11         0.357284E+10        
Minimum of Months 0.239071E+10 7337.00   24.92 19.96 0.263590E+09 548.48   17.00 10.00
Maximum of Months 0.865830E+10 20405.71   33.30 26.76 0.328819E+09 548.52   33.30 26.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.882670E+10 21365.24 16-JAN-14:32 26.67 18.75 0.618767E+09 939.97 19-JAN-14:39 25.00 21.54
February 0.816773E+10 19828.60 26-FEB-11:23 25.55 19.96 0.564781E+09 917.77 27-FEB-14:09 25.60 20.00
March 0.748909E+10 19671.27 05-MAR-13:53 27.70 18.31 0.662984E+09 845.72 07-MAR-14:09 25.32 22.37
April 0.754455E+10 16604.24 23-APR-14:51 28.80 21.57 0.605254E+09 845.72 26-APR-13:39 28.30 21.72
May 0.962166E+10 13510.81 03-MAY-04:12 23.13 21.53 0.664467E+09 860.42 05-MAY-13:09 31.10 21.78
June 0.974156E+10 13316.11 29-JUN-05:02 25.18 24.55 0.662218E+09 845.69 06-JUN-13:50 25.18 24.55
July 0.993241E+10 16553.30 23-JUL-16:22 31.95 26.59 0.616026E+09 845.62 14-JUL-13:20 31.95 26.59
August 0.112367E+11 18468.27 13-AUG-14:32 30.33 26.08 0.691252E+09 845.63 25-AUG-13:20 27.90 24.42
September 0.104756E+11 20525.66 10-SEP-14:31 35.67 27.27 0.613919E+09 845.64 20-SEP-13:50 26.60 22.72
October 0.128825E+11 21175.04 01-OCT-13:42 27.87 18.52 0.640023E+09 906.51 13-OCT-13:50 32.87 23.24
November 0.109918E+11 21182.51 26-NOV-13:32 20.90 15.43 0.631798E+09 966.40 06-NOV-14:20 20.90 15.43
December 0.965559E+10 20773.45 10-DEC-14:22 27.50 20.13 0.598543E+09 920.52 01-DEC-14:20 27.50 20.13
                     
Annual Sum or Average 0.116566E+12         0.757003E+10        
Minimum of Months 0.748909E+10 13316.11   20.90 15.43 0.564781E+09 845.62   20.90 15.43
Maximum of Months 0.128825E+11 21365.24   35.67 27.27 0.691252E+09 966.40   32.87 26.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.321659E+10 17082.55 16-JAN-15:52 25.00 17.90 0.374798E+09 544.95 24-JAN-14:39 17.00 10.58
February 0.363224E+10 18029.82 26-FEB-16:42 24.58 19.86 0.352061E+09 544.95 14-FEB-14:20 24.58 19.86
March 0.458498E+10 19957.44 26-MAR-15:42 25.72 20.08 0.424225E+09 544.99 07-MAR-14:09 25.72 20.08
April 0.639093E+10 20671.86 23-APR-16:51 27.20 21.71 0.393216E+09 545.00 26-APR-13:39 28.30 21.72
May 0.820995E+10 20814.81 14-MAY-18:02 28.12 22.73 0.428784E+09 550.00 05-MAY-13:09 28.12 22.73
June 0.885211E+10 20574.09 11-JUN-16:42 33.12 21.82 0.427539E+09 544.99 06-JUN-13:50 33.12 21.82
July 0.853315E+10 19693.18 16-JUL-15:52 31.70 25.48 0.397783E+09 544.94 14-JUL-13:20 31.70 25.48
August 0.906582E+10 19172.13 13-AUG-14:32 30.33 26.08 0.446009E+09 544.94 25-AUG-13:20 27.90 24.42
September 0.725179E+10 21019.10 10-SEP-14:31 35.67 27.27 0.395919E+09 544.95 20-SEP-13:50 26.60 22.72
October 0.715046E+10 21187.37 09-OCT-16:31 28.00 21.42 0.410073E+09 544.96 17-OCT-13:09 22.17 15.50
November 0.456702E+10 17013.03 05-NOV-16:33 26.47 19.73 0.397104E+09 544.95 14-NOV-14:20 19.20 12.67
December 0.372416E+10 16960.49 10-DEC-15:42 27.17 20.20 0.368957E+09 544.95 13-DEC-14:00 30.00 21.84
                     
Annual Sum or Average 0.751792E+11         0.481647E+10        
Minimum of Months 0.321659E+10 16960.49   24.58 17.90 0.352061E+09 544.94   17.00 10.58
Maximum of Months 0.906582E+10 21187.37   35.67 27.27 0.446009E+09 550.00   33.12 25.48



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.238056E+10 5516.46 31-JAN-15:00 25.00 21.54 0.523448E+09 845.60 02-JAN-14:20 25.00 21.54
February 0.294189E+10 5925.67 22-FEB-14:30 25.55 20.41 0.503606E+09 845.61 02-FEB-14:09 25.55 20.41
March 0.405836E+10 7498.45 30-MAR-13:30 28.55 22.55 0.614135E+09 845.68 07-MAR-14:09 28.55 22.55
April 0.582018E+10 9146.70 28-APR-15:00 33.30 23.06 0.592857E+09 850.25 26-APR-13:39 33.30 23.06
May 0.100847E+11 16925.75 29-MAY-14:42 32.70 23.12 0.664660E+09 869.14 05-MAY-13:09 32.70 23.12
June 0.110787E+11 16916.57 04-JUN-16:12 29.60 24.64 0.662647E+09 845.69 05-JUN-09:39 27.93 23.67
July 0.109571E+11 17044.98 23-JUL-16:22 31.95 26.59 0.616480E+09 845.61 14-JUL-13:20 31.95 26.59
August 0.107642E+11 16622.27 20-AUG-14:12 33.67 24.98 0.691041E+09 845.60 25-AUG-13:20 27.90 24.42
September 0.846132E+10 17586.69 10-SEP-14:31 35.67 27.27 0.612503E+09 845.62 20-SEP-13:50 26.60 22.72
October 0.753465E+10 17167.89 08-OCT-13:01 32.17 26.14 0.627173E+09 845.64 17-OCT-13:09 22.17 15.50
November 0.416829E+10 10965.19 01-NOV-05:02 22.62 22.36 0.579327E+09 845.62 06-NOV-14:20 28.30 20.91
December 0.292586E+10 6444.82 15-DEC-15:00 29.00 21.56 0.519111E+09 845.62 13-DEC-14:00 29.00 21.56
                     
Annual Sum or Average 0.811757E+11         0.720699E+10        
Minimum of Months 0.238056E+10 5516.46   22.62 20.41 0.503606E+09 845.60   22.17 15.50
Maximum of Months 0.110787E+11 17586.69   35.67 27.27 0.691041E+09 869.14   33.30 26.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.224220E+10 7264.85 19-JAN-10:20 23.57 21.08 0.369501E+09 544.95 19-JAN-14:39 25.00 21.54
February 0.280393E+10 7648.84 27-FEB-10:30 21.90 19.28 0.349452E+09 544.95 27-FEB-14:09 25.60 20.00
March 0.419659E+10 12063.42 26-MAR-09:13 24.03 19.81 0.421138E+09 545.01 07-MAR-14:09 24.03 19.81
April 0.598668E+10 18996.97 23-APR-09:42 25.82 20.99 0.391351E+09 547.19 26-APR-13:39 28.30 21.72
May 0.914594E+10 21444.21 29-MAY-10:01 29.08 23.08 0.428949E+09 553.14 05-MAY-13:09 29.08 23.08
June 0.959673E+10 20526.93 04-JUN-09:32 29.27 24.89 0.427433E+09 545.03 05-JUN-09:39 27.93 23.67
July 0.946690E+10 21202.71 16-JUL-09:41 30.73 25.53 0.397783E+09 544.94 14-JUL-13:20 30.73 25.53
August 0.920728E+10 18915.56 06-AUG-08:32 28.67 26.43 0.445777E+09 544.94 25-AUG-13:20 27.90 24.42
September 0.729670E+10 20550.57 10-SEP-08:32 33.30 26.76 0.395674E+09 544.95 20-SEP-13:50 26.60 22.72
October 0.684134E+10 20325.66 09-OCT-09:12 27.73 22.40 0.408115E+09 544.96 17-OCT-13:09 22.17 15.50
November 0.375596E+10 14855.15 11-NOV-09:43 24.40 21.68 0.396545E+09 544.95 13-NOV-10:39 17.57 13.65
December 0.248085E+10 6027.05 16-DEC-10:00 24.00 21.18 0.356668E+09 544.95 13-DEC-14:00 24.00 21.18
                     
Annual Sum or Average 0.730211E+11         0.478839E+10        
Minimum of Months 0.224220E+10 6027.05   21.90 19.28 0.349452E+09 544.94   17.57 13.65
Maximum of Months 0.959673E+10 21444.21   33.30 26.76 0.445777E+09 553.14   30.73 25.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.748421E+10 23228.98 16-JAN-15:12 26.33 18.42 0.604830E+09 921.34 19-JAN-14:39 25.00 21.54
February 0.747300E+10 21684.02 26-FEB-14:02 26.52 19.79 0.553052E+09 893.80 27-FEB-14:09 25.60 20.00
March 0.705223E+10 21535.19 05-MAR-13:53 27.70 18.31 0.646796E+09 845.76 07-MAR-14:09 25.32 22.37
April 0.763825E+10 16820.84 23-APR-15:02 28.62 21.65 0.599037E+09 865.18 26-APR-13:39 28.30 21.72
May 0.103643E+11 20846.28 29-MAY-14:42 32.70 23.12 0.664616E+09 865.39 05-MAY-13:09 32.70 23.12
June 0.106477E+11 20537.16 04-JUN-16:12 29.60 24.64 0.662392E+09 845.70 05-JUN-09:39 27.93 23.67
July 0.108694E+11 20712.04 23-JUL-16:22 31.95 26.59 0.616335E+09 845.62 14-JUL-13:20 31.95 26.59
August 0.121035E+11 20779.41 27-AUG-12:23 32.00 23.77 0.691304E+09 845.62 25-AUG-13:20 32.00 23.77
September 0.110653E+11 23407.65 10-SEP-14:31 35.67 27.27 0.613689E+09 845.65 20-SEP-13:50 26.60 22.72
October 0.132615E+11 24055.67 08-OCT-13:01 32.17 26.14 0.636172E+09 889.56 13-OCT-13:50 32.87 23.24
November 0.103167E+11 24469.31 11-NOV-13:41 26.18 22.83 0.622794E+09 945.58 06-NOV-14:20 26.18 22.83
December 0.863077E+10 25083.01 10-DEC-14:11 27.33 20.16 0.582194E+09 894.80 15-DEC-14:39 29.00 21.74
                     
Annual Sum or Average 0.116907E+12         0.749321E+10        
Minimum of Months 0.705223E+10 16820.84   26.18 18.31 0.553052E+09 845.62   25.00 20.00
Maximum of Months 0.132615E+11 25083.01   35.67 27.27 0.691304E+09 945.58   32.87 26.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.277048E+10 15929.58 16-JAN-15:52 25.00 17.90 0.363087E+09 544.94 19-JAN-14:39 25.00 21.54
February 0.339243E+10 18063.25 26-FEB-16:42 24.58 19.86 0.343460E+09 544.95 27-FEB-14:09 25.60 20.00
March 0.439954E+10 18607.18 26-MAR-15:13 24.57 19.90 0.412402E+09 545.01 07-MAR-14:09 24.57 19.90
April 0.647029E+10 22580.82 16-APR-16:52 19.40 13.58 0.389910E+09 547.26 26-APR-13:39 28.30 21.72
May 0.873795E+10 22579.34 29-MAY-16:41 30.97 23.75 0.428881E+09 553.20 05-MAY-13:39 30.97 23.75
June 0.951349E+10 22337.64 04-JUN-16:12 29.60 24.64 0.427586E+09 545.00 05-JUN-09:39 27.93 23.67
July 0.922328E+10 21398.14 16-JUL-16:22 30.55 25.08 0.397865E+09 544.94 14-JUL-13:20 30.55 25.08
August 0.964673E+10 20623.85 20-AUG-16:51 30.00 24.17 0.446051E+09 544.94 25-AUG-13:20 27.90 24.42
September 0.763489E+10 23160.39 10-SEP-14:31 35.67 27.27 0.395835E+09 544.95 20-SEP-13:50 26.60 22.72
October 0.737757E+10 23117.26 01-OCT-15:51 27.70 18.29 0.408259E+09 544.96 17-OCT-13:09 22.17 15.50
November 0.432520E+10 21699.26 11-NOV-15:01 26.52 22.99 0.388249E+09 544.96 06-NOV-14:09 26.52 22.99
December 0.332458E+10 21969.87 10-DEC-15:31 27.33 20.16 0.356114E+09 544.96 13-DEC-14:00 30.00 21.84
                     
Annual Sum or Average 0.768164E+11         0.475770E+10        
Minimum of Months 0.277048E+10 15929.58   19.40 13.58 0.343460E+09 544.94   22.17 15.50
Maximum of Months 0.964673E+10 23160.39   35.67 27.27 0.446051E+09 553.20   30.97 25.08



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.339760E+10 11693.21 02-JAN-06:03 16.00 15.39 0.00 0.00 01-JAN-00:10 16.00 15.39
February 0.374439E+10 7803.33 27-FEB-16:50 24.58 20.33 0.00 0.00 01-FEB-00:10 24.58 20.33
March 0.494493E+10 7669.45 07-MAR-14:00 25.50 22.43 0.00 0.00 01-MAR-00:10 25.50 22.43
April 0.636466E+10 7504.19 26-APR-13:30 28.30 21.49 0.00 0.00 01-APR-00:10 28.30 21.49
May 0.778549E+10 11395.76 30-MAY-05:02 25.50 24.21 0.00 0.00 01-MAY-00:10 25.50 24.21
June 0.835528E+10 8970.87 14-JUN-05:02 25.00 22.88 0.00 0.00 01-JUN-00:10 25.00 22.88
July 0.890441E+10 11219.83 05-JUL-05:02 26.10 24.88 0.00 0.00 01-JUL-00:10 26.10 24.88
August 0.990303E+10 10305.19 21-AUG-05:15 26.00 23.88 0.00 0.00 01-AUG-00:10 26.00 23.88
September 0.744794E+10 12112.26 05-SEP-05:13 22.80 22.80 0.00 0.00 01-SEP-00:10 22.80 22.80
October 0.780426E+10 9817.00 10-OCT-05:03 21.98 20.05 0.00 0.00 01-OCT-00:10 21.98 20.05
November 0.586028E+10 8190.43 07-NOV-06:02 20.50 19.70 0.00 0.00 01-NOV-00:10 20.50 19.70
December 0.479480E+10 7499.57 11-DEC-06:02 20.83 20.26 0.00 0.00 01-DEC-00:10 20.83 20.26
                     
Annual Sum or Average 0.793071E+11         0.00        
Minimum of Months 0.339760E+10 7499.57   16.00 15.39 0.00 0.00   16.00 15.39
Maximum of Months 0.990303E+10 12112.26   28.30 24.88 0.00 0.00   28.30 24.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.174079E+10 7388.50 05-JAN-06:02 0.17 0.10 0.00 0.00 01-JAN-00:10 0.17 0.10
February 0.199550E+10 4736.65 27-FEB-16:50 24.58 20.33 0.00 0.00 01-FEB-00:10 24.58 20.33
March 0.272860E+10 4050.01 07-MAR-14:00 25.50 22.43 0.00 0.00 01-MAR-00:10 25.50 22.43
April 0.404151E+10 5540.89 28-APR-15:30 32.75 24.38 0.00 0.00 01-APR-00:10 32.75 24.38
May 0.660561E+10 7815.25 16-MAY-15:50 26.57 21.73 0.00 0.00 01-MAY-00:10 26.57 21.73
June 0.685295E+10 6894.31 20-JUN-05:02 24.90 23.36 0.00 0.00 01-JUN-00:10 24.90 23.36
July 0.693551E+10 8049.59 01-JUL-05:02 24.50 23.30 0.00 0.00 01-JUL-00:10 24.50 23.30
August 0.715018E+10 6972.01 01-AUG-05:02 23.90 22.91 0.00 0.00 01-AUG-00:10 23.90 22.91
September 0.598416E+10 8524.36 25-SEP-05:02 23.38 22.59 0.00 0.00 01-SEP-00:10 23.38 22.59
October 0.589386E+10 7611.82 11-OCT-05:03 23.20 22.16 0.00 0.00 01-OCT-00:10 23.20 22.16
November 0.333620E+10 5227.17 07-NOV-16:00 27.20 23.87 0.00 0.00 01-NOV-00:10 27.20 23.87
December 0.240998E+10 6219.66 20-DEC-06:02 2.83 1.61 0.00 0.00 01-DEC-00:10 2.83 1.61
                     
Annual Sum or Average 0.556749E+11         0.00        
Minimum of Months 0.174079E+10 4050.01   0.17 0.10 0.00 0.00   0.17 0.10
Maximum of Months 0.715018E+10 8524.36   32.75 24.38 0.00 0.00   32.75 24.38



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.191716E+10 11167.76 19-JAN-15:10 25.00 21.42 0.00 0.00 01-JAN-00:10 25.00 21.42
February 0.297456E+10 11751.01 27-FEB-15:00 26.10 20.43 0.00 0.00 01-FEB-00:10 26.10 20.43
March 0.415836E+10 12556.28 06-MAR-15:50 26.10 21.44 0.00 0.00 01-MAR-00:10 26.10 21.44
April 0.723595E+10 18238.78 26-APR-13:30 28.30 21.49 0.00 0.00 01-APR-00:10 28.30 21.49
May 0.118984E+11 22026.79 03-MAY-13:50 32.62 22.35 0.00 0.00 01-MAY-00:10 32.62 22.35
June 0.131461E+11 19551.03 07-JUN-14:30 30.00 21.25 0.00 0.00 01-JUN-00:10 30.00 21.25
July 0.125927E+11 18360.58 07-JUL-14:40 34.63 24.19 0.00 0.00 01-JUL-00:10 34.63 24.19
August 0.127246E+11 17660.93 03-AUG-15:00 35.00 24.85 0.00 0.00 01-AUG-00:10 35.00 24.85
September 0.966678E+10 16336.11 01-SEP-14:00 32.20 22.62 0.00 0.00 01-SEP-00:10 32.20 22.62
October 0.919972E+10 16120.16 05-OCT-15:00 34.00 24.05 0.00 0.00 01-OCT-00:10 34.00 24.05
November 0.423075E+10 12778.07 02-NOV-14:20 29.40 24.36 0.00 0.00 01-NOV-00:10 29.40 24.36
December 0.262379E+10 10885.83 15-DEC-15:00 29.00 21.56 0.00 0.00 01-DEC-00:10 29.00 21.56
                     
Annual Sum or Average 0.923689E+11         0.00        
Minimum of Months 0.191716E+10 10885.83   25.00 20.43 0.00 0.00   25.00 20.43
Maximum of Months 0.131461E+11 22026.79   35.00 24.85 0.00 0.00   35.00 24.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.396930E+10 2149.84 01-JAN-17:20 22.67 19.00 95232057.79 126.85 02-JAN-10:00 24.00 19.35
February 0.835644E+10 4231.61 26-FEB-17:56 23.30 19.29 86405412.62 126.85 24-FEB-14:00 23.30 19.29
March 0.144170E+11 7189.17 31-MAR-24:00 20.70 19.78 0.103242E+09 126.84 27-MAR-09:09 20.70 19.78
April 0.189751E+11 8003.70 16-APR-18:20 18.07 13.19 91650844.47 128.82 28-APR-13:00 32.70 23.02
May 0.460393E+10 3476.40 31-MAY-24:00 23.00 21.40 99235836.67 126.85 08-MAY-13:00 23.00 21.40
June 0.931946E+10 5344.73 30-JUN-24:00 25.10 23.16 98980526.06 126.87 26-JUN-09:09 25.10 23.16
July 0.146861E+11 7222.03 31-JUL-24:00 25.20 23.65 91894021.68 126.85 13-JUL-09:09 25.20 23.65
August 0.197894E+11 7799.67 06-AUG-18:00 25.00 23.59 0.104873E+09 135.77 28-AUG-13:00 33.00 25.67
September 0.448199E+10 3491.75 30-SEP-24:00 22.30 21.22 91605920.61 126.82 05-SEP-13:09 22.30 21.22
October 0.965724E+10 5351.01 31-OCT-24:00 21.60 20.90 95247918.47 126.87 24-OCT-09:00 21.60 20.90
November 0.141102E+11 6035.79 12-NOV-17:10 14.53 8.53 94306800.78 126.85 01-NOV-09:09 14.53 8.53
December 0.194971E+11 7894.74 10-DEC-16:53 25.00 19.63 91882676.49 126.83 28-DEC-10:09 18.33 18.33
                     
Annual Sum or Average 0.141863E+12         0.114456E+10        
Minimum of Months 0.396930E+10 2149.84   14.53 8.53 86405412.62 126.82   14.53 8.53
Maximum of Months 0.197894E+11 8003.70   25.20 23.65 0.104873E+09 135.77   33.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.265429E+10 1846.63 18-JAN-17:00 22.00 19.94 95231123.59 126.84 02-JAN-14:09 22.00 19.94
February 0.709034E+10 3860.10 26-FEB-17:56 23.30 19.29 86404937.23 126.85 24-FEB-14:00 23.30 19.29
March 0.130357E+11 6733.01 31-MAR-24:00 20.70 19.78 0.103242E+09 126.84 07-MAR-14:00 20.70 19.78
April 0.178988E+11 7492.78 16-APR-18:20 18.07 13.19 91654412.59 129.24 28-APR-13:00 32.70 23.02
May 0.421283E+10 3257.80 31-MAY-24:00 23.00 21.40 99234099.45 126.84 03-MAY-13:30 23.00 21.40
June 0.881696E+10 5171.25 30-JUN-24:00 25.10 23.16 98979572.46 126.86 01-JUN-13:09 25.10 23.16
July 0.139644E+11 6921.52 31-JUL-24:00 25.20 23.65 91894094.52 126.85 14-JUL-13:00 25.20 23.65
August 0.187572E+11 7276.40 06-AUG-17:40 25.33 23.69 0.104709E+09 134.53 28-AUG-13:00 33.00 25.67
September 0.400674E+10 3232.93 30-SEP-24:00 22.30 21.22 91605413.05 126.82 05-SEP-13:09 22.30 21.22
October 0.895615E+10 4963.97 31-OCT-24:00 21.60 20.90 95247144.11 126.87 24-OCT-09:09 21.60 20.90
November 0.128577E+11 5671.82 06-NOV-17:00 26.60 19.72 94306602.22 126.84 03-NOV-09:09 26.60 19.72
December 0.176801E+11 7389.05 15-DEC-17:00 28.00 21.24 91882353.50 126.83 28-DEC-14:09 19.17 19.17
                     
Annual Sum or Average 0.129931E+12         0.114439E+10        
Minimum of Months 0.265429E+10 1846.63   18.07 13.19 86404937.23 126.82   19.17 19.17
Maximum of Months 0.187572E+11 7492.78   28.00 23.69 0.104709E+09 134.53   33.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.170977E+10 1910.22 18-JAN-17:00 22.00 19.94 95053314.80 126.84 02-JAN-14:09 22.00 19.94
February 0.628798E+10 3889.26 26-FEB-17:43 23.48 19.39 86405174.91 126.85 24-FEB-14:00 23.48 19.39
March 0.124718E+11 6638.38 31-MAR-24:00 20.70 19.78 0.103242E+09 126.85 07-MAR-14:00 20.70 19.78
April 0.177637E+11 7684.36 23-APR-18:04 25.13 21.19 91639368.53 127.83 28-APR-13:00 32.70 23.02
May 0.433875E+10 3227.07 31-MAY-24:00 23.00 21.40 99235348.53 126.85 08-MAY-13:00 23.00 21.40
June 0.896216E+10 5200.47 30-JUN-24:00 25.10 23.16 98980620.38 126.87 01-JUN-13:09 25.10 23.16
July 0.141202E+11 6909.58 31-JUL-24:00 25.20 23.65 91894784.81 126.85 12-JUL-13:09 25.20 23.65
August 0.188916E+11 7544.83 06-AUG-17:40 25.33 23.69 0.104175E+09 133.43 28-AUG-13:00 33.00 25.67
September 0.410400E+10 3254.86 30-SEP-24:00 22.30 21.22 91605505.89 126.82 05-SEP-13:09 22.30 21.22
October 0.889056E+10 4899.21 31-OCT-24:00 21.60 20.90 95247721.75 126.87 24-OCT-13:00 21.60 20.90
November 0.123463E+11 5736.17 06-NOV-17:00 26.60 19.72 94306893.02 126.85 01-NOV-09:00 26.60 19.72
December 0.168141E+11 7459.53 15-DEC-17:00 28.00 21.24 91882663.80 126.83 28-DEC-14:09 19.17 19.17
                     
Annual Sum or Average 0.126701E+12         0.114367E+10        
Minimum of Months 0.170977E+10 1910.22   20.70 19.39 86405174.91 126.82   19.17 19.17
Maximum of Months 0.188916E+11 7684.36   28.00 23.69 0.104175E+09 133.43   33.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.240551E+12 93010.01 02-JAN-17:00 26.00 18.38 0.206150E+10 2746.59 19-JAN-14:09 25.00 21.54
February 0.436778E+12 183706.24 27-FEB-17:00 24.40 20.28 0.187039E+10 2747.68 10-FEB-10:30 24.40 20.28
March 0.728561E+12 358528.34 31-MAR-24:00 20.70 19.78 0.223520E+10 2749.11 16-MAR-13:00 20.70 19.78
April 0.940360E+12 368174.57 18-APR-16:05 27.75 17.06 0.204517E+10 3341.69 28-APR-13:00 32.70 23.02
May 0.240639E+12 175657.17 31-MAY-24:00 23.00 21.40 0.214894E+10 2747.09 26-MAY-09:09 23.00 21.40
June 0.469028E+12 267281.88 30-JUN-23:55 25.10 23.16 0.214274E+10 2746.54 01-JUN-13:09 25.10 23.16
July 0.731135E+12 359537.52 31-JUL-24:00 25.20 23.65 0.198923E+10 2745.89 12-JUL-13:09 25.20 23.65
August 0.972340E+12 370785.51 09-AUG-21:02 22.58 22.41 0.260964E+10 3591.89 28-AUG-13:00 33.00 25.67
September 0.236732E+12 176557.23 30-SEP-24:00 22.30 21.22 0.198388E+10 2747.08 18-SEP-13:00 22.30 21.22
October 0.488459E+12 268649.70 31-OCT-24:00 21.60 20.90 0.206195E+10 2747.61 30-OCT-09:50 21.60 20.90
November 0.709505E+12 276565.10 06-NOV-17:00 26.60 19.72 0.204206E+10 2750.51 20-NOV-10:09 20.18 16.15
December 0.977390E+12 368062.46 26-DEC-17:00 12.70 5.60 0.201674E+10 3162.14 13-DEC-14:00 12.70 5.60
                     
Annual Sum or Average 0.717148E+13         0.252075E+11        
Minimum of Months 0.236732E+12 93010.01   12.70 5.60 0.187039E+10 2745.89   12.70 5.60
Maximum of Months 0.977390E+12 370785.51   27.75 23.65 0.260964E+10 3591.89   33.00 25.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.170544E+09 12692.40 16-JAN-14:32 26.67
February 0.202258E+09 11222.26 25-FEB-17:02 26.55
March 97772468.49 10704.31 15-MAR-04:15 9.87
April 0.164660E+09 16644.41 22-APR-16:01 30.08
May 0.338097E+09 18547.41 27-MAY-16:02 31.60
June 0.337968E+09 21865.08 10-JUN-16:01 33.72
July 0.441516E+09 25146.50 22-JUL-16:01 35.92
August 0.449927E+09 19475.32 19-AUG-16:02 32.63
September 0.521254E+09 24819.23 09-SEP-16:01 35.73
October 0.554434E+09 18775.01 07-OCT-16:01 31.58
November 0.528166E+09 11841.09 11-NOV-17:53 24.40
December 0.471524E+09 12541.97 25-DEC-09:43 11.83
         
Annual Sum or Average 0.427812E+10      
Minimum of Months 97772468.49 10704.31   9.87
Maximum of Months 0.554434E+09 25146.50   35.92



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 81875431.54 48154.11 10-JAN-06:02 3.00
February 0.271607E+09 55613.11 06-FEB-05:11 2.97
March 21645486.03 47849.33 13-MAR-05:03 6.68
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 22931317.50 48003.30 21-DEC-06:01 0.83
         
Annual Sum or Average 0.398059E+09      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 0.271607E+09 55613.11   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 102925.52 1200.80 21-DEC-06:01 0.83
         
Annual Sum or Average 102925.52      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 102925.52 1200.80   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 207658.58 1384.39 06-FEB-06:03 2.88
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 207658.58      
Minimum of Months 0.00 0.00   2.88
Maximum of Months 207658.58 1384.39   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.196830E+09 10931.86 10-JAN-05:01 1.33
February 96935190.02 11286.03 06-FEB-05:11 2.97
March 45454403.60 10298.43 09-MAR-06:02 1.10
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 1828.80 15.24 16-NOV-06:02 9.40
December 0.108536E+09 10879.67 21-DEC-05:01 0.17
         
Annual Sum or Average 0.447758E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.196830E+09 11286.03   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 76325186.38 8715.21 10-JAN-05:01 1.33
February 36191274.88 9012.06 06-FEB-05:11 2.97
March 18189011.43 8248.64 09-MAR-06:02 1.10
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 54855653.03 8731.09 21-DEC-05:01 0.17
         
Annual Sum or Average 0.185561E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 76325186.38 9012.06   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 32949862.21 11495.00 21-JAN-06:02 1.00
February 13646424.46 11136.10 06-FEB-06:03 2.88
March 11867756.07 11102.42 11-MAR-06:02 6.60
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 33971770.08 11337.00 21-DEC-06:01 0.83
         
Annual Sum or Average 92435812.81      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 33971770.08 11495.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 42547285.97 7480.56 10-JAN-05:01 1.33
February 16036261.23 7475.72 06-FEB-05:11 2.97
March 3837571.40 6372.23 11-MAR-06:02 6.60
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 22158996.14 7143.89 21-DEC-06:01 0.83
         
Annual Sum or Average 84580114.74      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 42547285.97 7480.56   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.110268E+10 13914.01 23-JAN-05:11 7.67
February 0.648865E+09 14740.45 05-FEB-08:63 -2.9
March 0.385822E+09 13150.09 13-MAR-04:11 7.00
April 133378.71 838.51 03-APR-05:03 12.28
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 1757754.12 4298.25 28-OCT-05:03 10.00
November 74832893.96 11949.12 24-NOV-05:12 11.23
December 0.692054E+09 13415.95 21-DEC-04:03 1.67
         
Annual Sum or Average 0.290614E+10      
Minimum of Months 0.00 0.00   -2.9
Maximum of Months 0.110268E+10 14740.45   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.453911E+09 12224.62 23-JAN-05:11 7.67
February 0.243410E+09 13038.37 06-FEB-05:11 2.97
March 0.194172E+09 11380.31 10-MAR-05:11 5.77
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 355020.57 1599.70 28-OCT-05:03 10.00
November 20393533.24 10126.69 16-NOV-06:02 9.40
December 0.341101E+09 11955.43 20-DEC-05:11 4.33
         
Annual Sum or Average 0.125334E+10      
Minimum of Months 0.00 0.00   2.97
Maximum of Months 0.453911E+09 13038.37   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.420457E+09 15703.69 10-JAN-05:01 1.33
February 0.256234E+09 17124.25 06-FEB-05:11 2.97
March 0.241913E+09 15120.02 10-MAR-05:11 5.77
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 4880163.04 13739.60 16-NOV-06:02 9.40
December 0.279174E+09 15875.98 20-DEC-05:11 4.33
         
Annual Sum or Average 0.120266E+10      
Minimum of Months 0.00 0.00   1.33
Maximum of Months 0.420457E+09 17124.25   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.346505E+09 11391.11 10-JAN-05:01 1.33
February 0.190155E+09 12503.87 06-FEB-05:11 2.97
March 0.107784E+09 10516.79 10-MAR-05:11 5.77
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 5183340.05 9308.89 16-NOV-06:02 9.40
December 0.182539E+09 11267.96 21-DEC-05:01 0.17
         
Annual Sum or Average 0.832166E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.346505E+09 12503.87   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 65346358.29 9169.37 09-JAN-05:11 7.67
February 64474719.64 9231.19 21-FEB-05:12 17.27
March 68249068.00 9153.66 13-MAR-04:11 7.00
April 71708542.75 9363.72 03-APR-04:12 12.43
May 39976322.58 5872.44 02-MAY-03:02 24.13
June 38970784.67 7756.65 25-JUN-15:41 32.70
July 41829322.97 5688.59 30-JUL-14:52 28.30
August 34676390.45 6977.50 06-AUG-15:02 30.67
September 48614056.49 6983.70 29-SEP-04:12 23.80
October 66807853.74 8905.66 30-OCT-04:12 16.67
November 85077833.67 9055.02 27-NOV-05:12 14.33
December 0.112081E+09 9970.48 26-DEC-05:11 6.97
         
Annual Sum or Average 0.737812E+09      
Minimum of Months 34676390.45 5688.59   6.97
Maximum of Months 0.112081E+09 9970.48   32.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.249396E+09 8244.56 16-JAN-15:52 25.00
February 0.146553E+09 5761.24 26-FEB-16:42 24.58
March 98308392.00 5649.74 20-MAR-04:12 12.27
April 27232912.23 5166.86 23-APR-14:51 28.80
May 28673574.76 5936.44 22-MAY-03:02 26.10
June 22769220.59 4649.78 25-JUN-15:52 32.80
July 28042376.74 5012.82 07-JUL-03:02 26.02
August 24745721.40 5170.68 23-AUG-03:02 26.48
September 36455949.27 7968.00 10-SEP-15:51 34.30
October 43187255.87 5277.01 01-OCT-15:02 27.95
November 47530985.82 5549.61 26-NOV-16:12 20.87
December 0.127972E+09 6017.66 10-DEC-15:42 27.17
         
Annual Sum or Average 0.880867E+09      
Minimum of Months 22769220.59 4649.78   12.27
Maximum of Months 0.249396E+09 8244.56   34.30



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.161153E+10 12088.63 10-JAN-06:02 3.00
February 0.102146E+10 17811.01 06-FEB-05:42 2.77
March 0.884995E+09 13807.40 08-MAR-06:02 11.00
April 0.182754E+09 10978.08 17-APR-05:02 12.70
May 29785592.57 8091.74 16-MAY-04:11 23.30
June 24256361.84 7782.56 07-JUN-04:12 21.10
July 20178690.80 6281.56 10-JUL-03:02 25.60
August 20563757.56 6568.66 17-AUG-04:12 21.93
September 26469545.52 7279.30 01-SEP-04:12 23.93
October 0.107787E+09 12340.83 18-OCT-05:02 15.17
November 0.387202E+09 10938.32 06-NOV-06:03 18.80
December 0.122206E+10 12950.81 21-DEC-06:03 0.83
         
Annual Sum or Average 0.553905E+10      
Minimum of Months 20178690.80 6281.56   0.83
Maximum of Months 0.161153E+10 17811.01   25.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.139467E+09 528.31 05-JAN-04:45 1.00
February 229508.70 389.52 05-FEB-08:40 -1.5
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.139697E+09      
Minimum of Months 0.00 0.00   -1.5
Maximum of Months 0.139467E+09 528.31   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:10 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:10 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.138227E+11 14744.03 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.125395E+11 14744.03 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.149226E+11 14744.03 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.133065E+11 14744.03 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.143726E+11 14744.03 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.143114E+11 14744.03 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.133677E+11 14744.03 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.149224E+11 14744.03 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.133065E+11 14744.03 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.138228E+11 14744.03 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.136668E+11 14744.03 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.133678E+11 14744.03 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.165729E+12     0.424397E+12    
Minimum of Months 0.125395E+11 14744.03   0.325565E+11 13457.54  
Maximum of Months 0.149226E+11 14744.03   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289614E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.63  
Maximum of Months 0.134015E+11 13241.18   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289613E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.56  
Maximum of Months 0.134015E+11 13241.18   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289613E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.56  
Maximum of Months 0.134015E+11 13241.18   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.940155E+09 1350.49 31-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.822343E+09 1401.26 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.947511E+09 1281.30 27-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.826122E+09 1320.95 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.863984E+09 918.00 23-MAY-07:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.850022E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.802353E+09 889.97 14-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.910263E+09 922.55 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.836172E+09 1277.51 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.891081E+09 1474.14 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.925583E+09 1409.70 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.929655E+09 1461.33 12-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.105452E+11     0.363654E+11    
Minimum of Months 0.802353E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.947511E+09 1474.14   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.595875E+09 810.19 31-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.523996E+09 865.06 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.605472E+09 755.79 27-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.531183E+09 812.31 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.559748E+09 574.48 30-MAY-15:30 0.201177E+10 1392.34 01-MAY-07:10
June 0.551981E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.519755E+09 509.78 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.587109E+09 570.19 21-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.537338E+09 750.61 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.569956E+09 924.70 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.589147E+09 920.23 21-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.590770E+09 926.10 12-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.676233E+10     0.234352E+11    
Minimum of Months 0.519755E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.605472E+09 926.10   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.903098E+09 1305.22 31-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.802510E+09 1372.93 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.939031E+09 1265.80 27-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.828268E+09 1326.99 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.871965E+09 924.74 23-MAY-07:30 0.312179E+10 2160.58 01-MAY-07:10
June 0.859644E+09 862.14 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.809445E+09 909.81 14-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.914073E+09 930.76 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.834071E+09 1272.90 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.880877E+09 1462.32 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.894077E+09 1364.76 21-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.891583E+09 1444.67 12-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.104286E+11     0.363660E+11    
Minimum of Months 0.802510E+09 862.14   0.277013E+10 2160.58  
Maximum of Months 0.939031E+09 1462.32   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.591026E+09 884.21 31-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.523256E+09 911.40 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.609556E+09 861.21 27-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.534316E+09 875.00 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.561016E+09 715.17 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.551497E+09 582.63 16-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.520841E+09 597.17 14-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.589734E+09 780.56 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.541246E+09 862.22 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.572264E+09 958.99 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.582507E+09 930.38 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.581949E+09 942.77 12-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.675921E+10     0.234351E+11    
Minimum of Months 0.520841E+09 582.63   0.178514E+10 1392.33  
Maximum of Months 0.609556E+09 958.99   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.936882E+09 1346.59 31-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.820268E+09 1398.12 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.945590E+09 1276.68 27-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.825181E+09 1316.92 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.863249E+09 912.08 23-MAY-07:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.848846E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.801857E+09 882.55 14-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.909564E+09 916.96 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.834915E+09 1272.73 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.889723E+09 1471.91 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.922708E+09 1406.36 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.926412E+09 1459.03 12-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.105252E+11     0.363654E+11    
Minimum of Months 0.801857E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.945590E+09 1471.91   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.594705E+09 804.04 31-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.523064E+09 860.10 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.604821E+09 749.74 27-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.530711E+09 807.07 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.559251E+09 570.10 23-MAY-07:30 0.201177E+10 1392.34 01-MAY-07:10
June 0.551615E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.519241E+09 509.78 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.586684E+09 566.10 21-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.536739E+09 745.00 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.569377E+09 921.41 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.588148E+09 916.29 21-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.589569E+09 922.56 12-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.675392E+10     0.234352E+11    
Minimum of Months 0.519241E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.604821E+09 922.56   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.902654E+09 1301.04 31-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.802131E+09 1369.61 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.937995E+09 1261.10 27-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.827443E+09 1322.99 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.871033E+09 919.14 23-MAY-07:30 0.312179E+10 2160.58 01-MAY-07:10
June 0.858780E+09 852.92 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.808688E+09 903.37 14-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.913287E+09 925.56 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.833242E+09 1268.07 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.880163E+09 1460.03 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.892786E+09 1361.60 21-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.890738E+09 1442.32 12-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.104189E+11     0.363660E+11    
Minimum of Months 0.802131E+09 852.92   0.277013E+10 2160.58  
Maximum of Months 0.937995E+09 1460.03   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.590159E+09 879.31 31-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.522473E+09 907.22 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.608504E+09 855.65 27-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.533535E+09 869.83 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.560258E+09 705.04 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.550940E+09 578.35 16-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.520115E+09 593.75 14-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.588942E+09 773.10 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.540283E+09 856.67 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.571465E+09 956.04 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.581595E+09 926.72 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.580905E+09 939.42 12-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.674917E+10     0.234351E+11    
Minimum of Months 0.520115E+09 578.35   0.178514E+10 1392.33  
Maximum of Months 0.608504E+09 956.04   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.936700E+09 1345.96 31-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.820220E+09 1397.58 01-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.945545E+09 1275.94 27-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.825154E+09 1316.23 14-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.863200E+09 911.84 23-MAY-07:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.848796E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.801834E+09 882.24 14-JUL-07:10 0.300989E+10 2160.55 03-JUL-07:10
August 0.909536E+09 916.73 21-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.834853E+09 1271.98 26-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.889679E+09 1471.53 25-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.922585E+09 1405.89 01-NOV-07:10 0.299314E+10 2160.55 01-NOV-07:10
December 0.926341E+09 1458.60 12-DEC-08:09 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.105244E+11     0.363654E+11    
Minimum of Months 0.801834E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.945545E+09 1471.53   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.594686E+09 803.57 31-JAN-08:09 0.197184E+10 1392.34 02-JAN-08:09
February 0.523030E+09 859.71 01-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.604803E+09 749.19 27-MAR-07:10 0.205169E+10 1392.34 01-MAR-08:09
April 0.530697E+09 806.58 14-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.559211E+09 569.90 23-MAY-07:30 0.201177E+10 1392.34 01-MAY-07:10
June 0.551584E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.519201E+09 509.78 03-JUL-07:10 0.193969E+10 1392.34 03-JUL-07:10
August 0.586665E+09 565.89 21-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.536713E+09 744.44 26-SEP-07:10 0.190321E+10 1392.34 01-SEP-07:10
October 0.569359E+09 921.14 25-OCT-07:10 0.197228E+10 1392.34 02-OCT-07:10
November 0.588087E+09 915.99 21-NOV-16:00 0.192889E+10 1392.34 01-NOV-07:10
December 0.589525E+09 922.27 12-DEC-08:09 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.675356E+10     0.234352E+11    
Minimum of Months 0.519201E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.604803E+09 922.27   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.902644E+09 1300.34 31-JAN-08:09 0.305983E+10 2160.58 02-JAN-08:09
February 0.802113E+09 1369.03 01-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.937963E+09 1260.34 27-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.827416E+09 1322.31 14-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.870999E+09 918.92 23-MAY-07:30 0.312179E+10 2160.58 01-MAY-07:10
June 0.858698E+09 852.58 16-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.808653E+09 903.12 14-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.913247E+09 925.35 21-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.833213E+09 1267.31 26-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.880126E+09 1459.63 25-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.892767E+09 1361.04 21-NOV-16:00 0.299318E+10 2160.58 01-NOV-07:10
December 0.890712E+09 1441.87 12-DEC-08:09 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.104186E+11     0.363660E+11    
Minimum of Months 0.802113E+09 852.58   0.277013E+10 2160.58  
Maximum of Months 0.937963E+09 1459.63   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.590104E+09 878.93 31-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.522455E+09 906.88 01-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.608481E+09 855.22 27-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.533499E+09 869.42 14-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.560235E+09 704.44 24-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.550925E+09 578.20 16-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.520068E+09 593.62 14-JUL-07:10 0.193968E+10 1392.33 03-JUL-07:10
August 0.588904E+09 772.71 23-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.540251E+09 856.25 26-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.571435E+09 955.81 25-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.581576E+09 926.46 01-NOV-07:10 0.192888E+10 1392.33 01-NOV-07:10
December 0.580878E+09 939.15 12-DEC-08:09 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.674881E+10     0.234351E+11    
Minimum of Months 0.520068E+09 578.20   0.178514E+10 1392.33  
Maximum of Months 0.608481E+09 955.81   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.397259E+10 4157.19 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.360343E+10 4157.19 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.428189E+10 4157.19 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.382459E+10 4157.19 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.412724E+10 4157.19 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.410728E+10 4157.19 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.384455E+10 4157.19 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.428189E+10 4157.19 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.382459E+10 4157.19 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.397259E+10 4157.19 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.392603E+10 4157.19 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.384455E+10 4157.19 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.476112E+11     0.749486E+13    
Minimum of Months 0.360343E+10 4157.19   0.246344E+12 94908.13  
Maximum of Months 0.428189E+10 4157.19   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.138227E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.125395E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.149226E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.133065E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.143726E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.143114E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.133677E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.149224E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.133065E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.138228E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.136668E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.133678E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.165729E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.125395E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.149226E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.940155E+09 0.305979E+10 0.00 0.00 0.00 0.00 975395.60 0.369771E+09
February 0.136985E+10 0.822343E+09 0.277008E+10 0.00 0.00 0.00 0.00 1862252.40 0.287571E+09
March 0.163685E+10 0.947511E+09 0.318369E+10 0.00 0.00 0.00 0.00 5899950.51 0.300827E+09
April 0.145243E+10 0.826122E+09 0.295462E+10 0.00 0.00 0.00 0.00 12876787.28 0.125092E+09
May 0.157338E+10 0.863984E+09 0.312174E+10 0.00 0.00 0.00 0.00 55169338.39 18371405.24
June 0.156900E+10 0.850022E+09 0.306580E+10 0.00 0.00 0.00 0.00 52084547.39 10733161.27
July 0.145680E+10 0.802353E+09 0.300989E+10 0.00 0.00 0.00 0.00 76230187.67 1629960.14
August 0.163685E+10 0.910263E+09 0.318369E+10 0.00 0.00 0.00 0.00 72388345.11 9508131.08
September 0.145243E+10 0.836172E+09 0.295328E+10 0.00 0.00 0.00 0.00 62150561.55 31613024.78
October 0.150991E+10 0.891081E+09 0.306046E+10 0.00 0.00 0.00 0.00 50569065.80 0.105493E+09
November 0.149516E+10 0.925583E+09 0.299314E+10 0.00 0.00 0.00 0.00 5121215.09 0.191354E+09
December 0.145680E+10 0.929655E+09 0.300922E+10 0.00 0.00 0.00 0.00 3386495.17 0.336204E+09
                   
Annual Sum or Average 0.181194E+11 0.105452E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.398714E+09 0.178817E+10
Minimum of Months 0.136985E+10 0.802353E+09 0.277008E+10 0.00 0.00 0.00 0.00 975395.60 1629960.14
Maximum of Months 0.163685E+10 0.947511E+09 0.318369E+10 0.00 0.00 0.00 0.00 76230187.67 0.369771E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.595875E+09 0.197184E+10 0.00 0.00 0.00 0.00 509627.66 0.254366E+09
February 0.882782E+09 0.523996E+09 0.178515E+10 0.00 0.00 0.00 0.00 1072378.89 0.196131E+09
March 0.105485E+10 0.605472E+09 0.205169E+10 0.00 0.00 0.00 0.00 3321858.42 0.201069E+09
April 0.936002E+09 0.531183E+09 0.190407E+10 0.00 0.00 0.00 0.00 8250138.08 82995313.80
May 0.101394E+10 0.559748E+09 0.201177E+10 0.00 0.00 0.00 0.00 35031114.72 12508971.92
June 0.101113E+10 0.551981E+09 0.197572E+10 0.00 0.00 0.00 0.00 34487578.07 6706304.61
July 0.938820E+09 0.519755E+09 0.193969E+10 0.00 0.00 0.00 0.00 50901132.15 1031732.32
August 0.105485E+10 0.587109E+09 0.205169E+10 0.00 0.00 0.00 0.00 50011772.72 4803406.80
September 0.936002E+09 0.537338E+09 0.190321E+10 0.00 0.00 0.00 0.00 38842851.61 21038440.01
October 0.973041E+09 0.569956E+09 0.197228E+10 0.00 0.00 0.00 0.00 31240152.80 70805889.90
November 0.963541E+09 0.589147E+09 0.192889E+10 0.00 0.00 0.00 0.00 3047668.50 0.129097E+09
December 0.938820E+09 0.590770E+09 0.193926E+10 0.00 0.00 0.00 0.00 2023310.76 0.220708E+09
                   
Annual Sum or Average 0.116768E+11 0.676233E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.258740E+09 0.120126E+10
Minimum of Months 0.882782E+09 0.519755E+09 0.178515E+10 0.00 0.00 0.00 0.00 509627.66 1031732.32
Maximum of Months 0.105485E+10 0.605472E+09 0.205169E+10 0.00 0.00 0.00 0.00 50901132.15 0.254366E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.903098E+09 0.305983E+10 0.00 0.00 0.00 0.00 567454.99 0.398268E+09
February 0.136988E+10 0.802510E+09 0.277013E+10 0.00 0.00 0.00 0.00 1469572.39 0.305718E+09
March 0.163688E+10 0.939031E+09 0.318374E+10 0.00 0.00 0.00 0.00 4574046.18 0.306510E+09
April 0.145246E+10 0.828268E+09 0.295467E+10 0.00 0.00 0.00 0.00 11672659.25 0.129265E+09
May 0.157341E+10 0.871965E+09 0.312179E+10 0.00 0.00 0.00 0.00 55012757.49 18262298.87
June 0.156904E+10 0.859644E+09 0.306585E+10 0.00 0.00 0.00 0.00 52685073.17 10447445.14
July 0.145684E+10 0.809445E+09 0.300994E+10 0.00 0.00 0.00 0.00 75935881.22 1705798.65
August 0.163688E+10 0.914073E+09 0.318374E+10 0.00 0.00 0.00 0.00 70542411.57 10258082.88
September 0.145246E+10 0.834071E+09 0.295333E+10 0.00 0.00 0.00 0.00 57046380.98 34628883.15
October 0.150994E+10 0.880877E+09 0.306051E+10 0.00 0.00 0.00 0.00 41942361.40 0.120803E+09
November 0.149520E+10 0.894077E+09 0.299318E+10 0.00 0.00 0.00 0.00 3931275.46 0.208912E+09
December 0.145684E+10 0.891583E+09 0.300927E+10 0.00 0.00 0.00 0.00 2555414.41 0.357831E+09
                   
Annual Sum or Average 0.181198E+11 0.104286E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.377935E+09 0.190261E+10
Minimum of Months 0.136988E+10 0.802510E+09 0.277013E+10 0.00 0.00 0.00 0.00 567454.99 1705798.65
Maximum of Months 0.163688E+10 0.939031E+09 0.318374E+10 0.00 0.00 0.00 0.00 75935881.22 0.398268E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.591026E+09 0.197183E+10 0.00 0.00 0.00 0.00 440473.56 0.276174E+09
February 0.882782E+09 0.523256E+09 0.178514E+10 0.00 0.00 0.00 0.00 1009996.50 0.219988E+09
March 0.105485E+10 0.609556E+09 0.205168E+10 0.00 0.00 0.00 0.00 3063899.39 0.237797E+09
April 0.936002E+09 0.534316E+09 0.190406E+10 0.00 0.00 0.00 0.00 6820441.99 0.112969E+09
May 0.101394E+10 0.561016E+09 0.201175E+10 0.00 0.00 0.00 0.00 31972777.41 21657123.70
June 0.101113E+10 0.551497E+09 0.197570E+10 0.00 0.00 0.00 0.00 29061502.83 15319174.12
July 0.938820E+09 0.520841E+09 0.193968E+10 0.00 0.00 0.00 0.00 38741788.00 7296846.19
August 0.105485E+10 0.589734E+09 0.205168E+10 0.00 0.00 0.00 0.00 39197770.90 21645594.69
September 0.936002E+09 0.541246E+09 0.190319E+10 0.00 0.00 0.00 0.00 35015443.16 32724711.28
October 0.973041E+09 0.572264E+09 0.197226E+10 0.00 0.00 0.00 0.00 27248635.29 97868175.66
November 0.963541E+09 0.582507E+09 0.192888E+10 0.00 0.00 0.00 0.00 2744760.82 0.154811E+09
December 0.938820E+09 0.581949E+09 0.193924E+10 0.00 0.00 0.00 0.00 1770575.18 0.271541E+09
                   
Annual Sum or Average 0.116768E+11 0.675921E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.217088E+09 0.146979E+10
Minimum of Months 0.882782E+09 0.520841E+09 0.178514E+10 0.00 0.00 0.00 0.00 440473.56 7296846.19
Maximum of Months 0.105485E+10 0.609556E+09 0.205168E+10 0.00 0.00 0.00 0.00 39197770.90 0.276174E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.936882E+09 0.305979E+10 0.00 0.00 0.00 0.00 5073831.74 0.733264E+09
February 0.136985E+10 0.820268E+09 0.277008E+10 0.00 0.00 0.00 0.00 6546585.91 0.564411E+09
March 0.163685E+10 0.945590E+09 0.318369E+10 0.00 0.00 0.00 0.00 17471848.39 0.609830E+09
April 0.145243E+10 0.825181E+09 0.295462E+10 0.00 0.00 0.00 0.00 29825511.85 0.274474E+09
May 0.157338E+10 0.863249E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.122180E+09 45835178.77
June 0.156900E+10 0.848846E+09 0.306580E+10 0.00 0.00 0.00 0.00 0.112338E+09 35139802.16
July 0.145680E+10 0.801857E+09 0.300989E+10 0.00 0.00 0.00 0.00 0.157891E+09 13655566.34
August 0.163685E+10 0.909564E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.153436E+09 45447515.12
September 0.145243E+10 0.834915E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.143882E+09 70399809.51
October 0.150991E+10 0.889723E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.115086E+09 0.232192E+09
November 0.149516E+10 0.922708E+09 0.299314E+10 0.00 0.00 0.00 0.00 15490882.76 0.381225E+09
December 0.145680E+10 0.926412E+09 0.300922E+10 0.00 0.00 0.00 0.00 10597055.77 0.659000E+09
                   
Annual Sum or Average 0.181194E+11 0.105252E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.889819E+09 0.366487E+10
Minimum of Months 0.136985E+10 0.801857E+09 0.277008E+10 0.00 0.00 0.00 0.00 5073831.74 13655566.34
Maximum of Months 0.163685E+10 0.945590E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.157891E+09 0.733264E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.594705E+09 0.197184E+10 0.00 0.00 0.00 0.00 1159271.75 0.536418E+09
February 0.649041E+09 0.523064E+09 0.178515E+10 0.00 0.00 0.00 0.00 2333788.25 0.412968E+09
March 0.773965E+09 0.604821E+09 0.205169E+10 0.00 0.00 0.00 0.00 6814242.12 0.442416E+09
April 0.688021E+09 0.530711E+09 0.190407E+10 0.00 0.00 0.00 0.00 16551408.31 0.205218E+09
May 0.744847E+09 0.559251E+09 0.201177E+10 0.00 0.00 0.00 0.00 73039024.55 36262113.94
June 0.742030E+09 0.551615E+09 0.197572E+10 0.00 0.00 0.00 0.00 69856210.75 26457921.93
July 0.690839E+09 0.519241E+09 0.193969E+10 0.00 0.00 0.00 0.00 95330368.87 12291043.26
August 0.773965E+09 0.586684E+09 0.205169E+10 0.00 0.00 0.00 0.00 94851437.77 34276393.23
September 0.688021E+09 0.536739E+09 0.190321E+10 0.00 0.00 0.00 0.00 83487947.06 53619821.84
October 0.715730E+09 0.569377E+09 0.197228E+10 0.00 0.00 0.00 0.00 64454393.71 0.173587E+09
November 0.708685E+09 0.588148E+09 0.192889E+10 0.00 0.00 0.00 0.00 6380826.49 0.283703E+09
December 0.690839E+09 0.589569E+09 0.193926E+10 0.00 0.00 0.00 0.00 4225545.48 0.472546E+09
                   
Annual Sum or Average 0.858171E+10 0.675392E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.518484E+09 0.268976E+10
Minimum of Months 0.649041E+09 0.519241E+09 0.178515E+10 0.00 0.00 0.00 0.00 1159271.75 12291043.26
Maximum of Months 0.773965E+09 0.604821E+09 0.205169E+10 0.00 0.00 0.00 0.00 95330368.87 0.536418E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.902654E+09 0.305983E+10 0.00 0.00 0.00 0.00 999266.14 0.896132E+09
February 0.136988E+10 0.802131E+09 0.277013E+10 0.00 0.00 0.00 0.00 3095201.33 0.679358E+09
March 0.163688E+10 0.937995E+09 0.318374E+10 0.00 0.00 0.00 0.00 10043178.60 0.672091E+09
April 0.145246E+10 0.827443E+09 0.295467E+10 0.00 0.00 0.00 0.00 26174421.23 0.300790E+09
May 0.157341E+10 0.871033E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.122080E+09 46444279.80
June 0.156904E+10 0.858780E+09 0.306585E+10 0.00 0.00 0.00 0.00 0.115163E+09 33502184.32
July 0.145684E+10 0.808688E+09 0.300994E+10 0.00 0.00 0.00 0.00 0.159453E+09 13424441.50
August 0.163688E+10 0.913287E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.149191E+09 48431539.45
September 0.145246E+10 0.833242E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.127934E+09 83213724.34
October 0.150994E+10 0.880163E+09 0.306051E+10 0.00 0.00 0.00 0.00 91567888.35 0.298530E+09
November 0.149520E+10 0.892786E+09 0.299318E+10 0.00 0.00 0.00 0.00 8512437.74 0.471814E+09
December 0.145684E+10 0.890738E+09 0.300927E+10 0.00 0.00 0.00 0.00 5541649.59 0.800310E+09
                   
Annual Sum or Average 0.181198E+11 0.104189E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.819756E+09 0.434404E+10
Minimum of Months 0.136988E+10 0.802131E+09 0.277013E+10 0.00 0.00 0.00 0.00 999266.14 13424441.50
Maximum of Months 0.163688E+10 0.937995E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.159453E+09 0.896132E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.590159E+09 0.197183E+10 0.00 0.00 0.00 0.00 1356853.43 0.552928E+09
February 0.882782E+09 0.522473E+09 0.178514E+10 0.00 0.00 0.00 0.00 2639194.44 0.425833E+09
March 0.105485E+10 0.608504E+09 0.205168E+10 0.00 0.00 0.00 0.00 8381318.61 0.455778E+09
April 0.936002E+09 0.533535E+09 0.190406E+10 0.00 0.00 0.00 0.00 15754739.45 0.224656E+09
May 0.101394E+10 0.560258E+09 0.201175E+10 0.00 0.00 0.00 0.00 74765918.61 43243485.35
June 0.101113E+10 0.550940E+09 0.197570E+10 0.00 0.00 0.00 0.00 67915305.89 33939090.69
July 0.938820E+09 0.520115E+09 0.193968E+10 0.00 0.00 0.00 0.00 91939798.45 18099340.71
August 0.105485E+10 0.588942E+09 0.205168E+10 0.00 0.00 0.00 0.00 92998975.34 45731055.71
September 0.936002E+09 0.540283E+09 0.190319E+10 0.00 0.00 0.00 0.00 81781294.28 64485061.73
October 0.973041E+09 0.571465E+09 0.197226E+10 0.00 0.00 0.00 0.00 64972152.80 0.197211E+09
November 0.963541E+09 0.581595E+09 0.192888E+10 0.00 0.00 0.00 0.00 7190762.23 0.293241E+09
December 0.938820E+09 0.580905E+09 0.193924E+10 0.00 0.00 0.00 0.00 4782116.77 0.501897E+09
                   
Annual Sum or Average 0.116768E+11 0.674917E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.514478E+09 0.285704E+10
Minimum of Months 0.882782E+09 0.520115E+09 0.178514E+10 0.00 0.00 0.00 0.00 1356853.43 18099340.71
Maximum of Months 0.105485E+10 0.608504E+09 0.205168E+10 0.00 0.00 0.00 0.00 92998975.34 0.552928E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.936700E+09 0.305979E+10 0.00 0.00 0.00 0.00 8134172.01 0.822391E+09
February 0.136985E+10 0.820220E+09 0.277008E+10 0.00 0.00 0.00 0.00 8830169.16 0.630730E+09
March 0.163685E+10 0.945545E+09 0.318369E+10 0.00 0.00 0.00 0.00 20842642.73 0.704598E+09
April 0.145243E+10 0.825154E+09 0.295462E+10 0.00 0.00 0.00 0.00 33840737.49 0.330078E+09
May 0.157338E+10 0.863200E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.141710E+09 63912091.66
June 0.156900E+10 0.848796E+09 0.306580E+10 0.00 0.00 0.00 0.00 0.130076E+09 48787083.27
July 0.145680E+10 0.801834E+09 0.300989E+10 0.00 0.00 0.00 0.00 0.178649E+09 21287463.91
August 0.163685E+10 0.909536E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.178674E+09 62227534.35
September 0.145243E+10 0.834853E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.162280E+09 93819911.12
October 0.150991E+10 0.889679E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.130677E+09 0.276990E+09
November 0.149516E+10 0.922585E+09 0.299314E+10 0.00 0.00 0.00 0.00 19289678.22 0.432751E+09
December 0.145680E+10 0.926341E+09 0.300922E+10 0.00 0.00 0.00 0.00 13991818.36 0.745992E+09
                   
Annual Sum or Average 0.181194E+11 0.105244E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.102700E+10 0.423356E+10
Minimum of Months 0.136985E+10 0.801834E+09 0.277008E+10 0.00 0.00 0.00 0.00 8134172.01 21287463.91
Maximum of Months 0.163685E+10 0.945545E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.178674E+09 0.822391E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.594686E+09 0.197184E+10 0.00 0.00 0.00 0.00 2004539.72 0.597939E+09
February 0.882782E+09 0.523030E+09 0.178515E+10 0.00 0.00 0.00 0.00 3314576.45 0.459158E+09
March 0.105485E+10 0.604803E+09 0.205169E+10 0.00 0.00 0.00 0.00 8530427.24 0.513546E+09
April 0.936002E+09 0.530697E+09 0.190407E+10 0.00 0.00 0.00 0.00 19927098.31 0.248232E+09
May 0.101394E+10 0.559211E+09 0.201177E+10 0.00 0.00 0.00 0.00 87802587.69 49357989.33
June 0.101113E+10 0.551584E+09 0.197572E+10 0.00 0.00 0.00 0.00 83572134.84 36147325.12
July 0.938820E+09 0.519201E+09 0.193969E+10 0.00 0.00 0.00 0.00 0.112190E+09 18030095.62
August 0.105485E+10 0.586665E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.113613E+09 46098545.71
September 0.936002E+09 0.536713E+09 0.190321E+10 0.00 0.00 0.00 0.00 99251580.96 70293859.87
October 0.973041E+09 0.569359E+09 0.197228E+10 0.00 0.00 0.00 0.00 77242824.50 0.207583E+09
November 0.963541E+09 0.588087E+09 0.192889E+10 0.00 0.00 0.00 0.00 7960866.93 0.326496E+09
December 0.938820E+09 0.589525E+09 0.193926E+10 0.00 0.00 0.00 0.00 5461072.97 0.532408E+09
                   
Annual Sum or Average 0.116768E+11 0.675356E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.620871E+09 0.310529E+10
Minimum of Months 0.882782E+09 0.519201E+09 0.178515E+10 0.00 0.00 0.00 0.00 2004539.72 18030095.62
Maximum of Months 0.105485E+10 0.604803E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.113613E+09 0.597939E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.902644E+09 0.305983E+10 0.00 0.00 0.00 0.00 1215821.44 0.103157E+10
February 0.136988E+10 0.802113E+09 0.277013E+10 0.00 0.00 0.00 0.00 3693432.07 0.769680E+09
March 0.163688E+10 0.937963E+09 0.318374E+10 0.00 0.00 0.00 0.00 11676912.39 0.784042E+09
April 0.145246E+10 0.827416E+09 0.295467E+10 0.00 0.00 0.00 0.00 30180046.85 0.363909E+09
May 0.157341E+10 0.870999E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.141718E+09 64745037.17
June 0.156904E+10 0.858698E+09 0.306585E+10 0.00 0.00 0.00 0.00 0.132765E+09 46737818.18
July 0.145684E+10 0.808653E+09 0.300994E+10 0.00 0.00 0.00 0.00 0.180624E+09 20935445.37
August 0.163688E+10 0.913247E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.174977E+09 66160167.57
September 0.145246E+10 0.833213E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.149402E+09 0.110027E+09
October 0.150994E+10 0.880126E+09 0.306051E+10 0.00 0.00 0.00 0.00 0.108764E+09 0.363432E+09
November 0.149520E+10 0.892767E+09 0.299318E+10 0.00 0.00 0.00 0.00 10511126.18 0.555737E+09
December 0.145684E+10 0.890712E+09 0.300927E+10 0.00 0.00 0.00 0.00 6761409.83 0.925702E+09
                   
Annual Sum or Average 0.181198E+11 0.104186E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.952289E+09 0.510268E+10
Minimum of Months 0.136988E+10 0.802113E+09 0.277013E+10 0.00 0.00 0.00 0.00 1215821.44 20935445.37
Maximum of Months 0.163688E+10 0.937963E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.180624E+09 0.103157E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.590104E+09 0.197183E+10 0.00 0.00 0.00 0.00 1829016.04 0.636330E+09
February 0.882782E+09 0.522455E+09 0.178514E+10 0.00 0.00 0.00 0.00 3176998.68 0.486202E+09
March 0.105485E+10 0.608481E+09 0.205168E+10 0.00 0.00 0.00 0.00 10028600.61 0.535289E+09
April 0.936002E+09 0.533499E+09 0.190406E+10 0.00 0.00 0.00 0.00 18681050.43 0.272629E+09
May 0.101394E+10 0.560235E+09 0.201175E+10 0.00 0.00 0.00 0.00 88544391.83 57931177.39
June 0.101113E+10 0.550925E+09 0.197570E+10 0.00 0.00 0.00 0.00 81063417.29 45151989.38
July 0.938820E+09 0.520068E+09 0.193968E+10 0.00 0.00 0.00 0.00 0.108688E+09 24974628.05
August 0.105485E+10 0.588904E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.110743E+09 60353171.01
September 0.936002E+09 0.540251E+09 0.190319E+10 0.00 0.00 0.00 0.00 97046517.30 83615685.38
October 0.973041E+09 0.571435E+09 0.197226E+10 0.00 0.00 0.00 0.00 76692882.69 0.238831E+09
November 0.963541E+09 0.581576E+09 0.192888E+10 0.00 0.00 0.00 0.00 8737674.93 0.342199E+09
December 0.938820E+09 0.580878E+09 0.193924E+10 0.00 0.00 0.00 0.00 5921766.31 0.580246E+09
                   
Annual Sum or Average 0.116768E+11 0.674881E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.611153E+09 0.336375E+10
Minimum of Months 0.882782E+09 0.520068E+09 0.178514E+10 0.00 0.00 0.00 0.00 1829016.04 24974628.05
Maximum of Months 0.105485E+10 0.608481E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.110743E+09 0.636330E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.397259E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.360343E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.428189E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.382459E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.412724E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.410728E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.384455E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.428189E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.382459E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.397259E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.392603E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.384455E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.476112E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.360343E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.428189E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 710804.22 0.828681E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1980597.63 0.641631E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8189541.52 0.662408E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19725993.08 0.285289E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96600508.05 36021072.97
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90289757.84 26890517.60
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.137169E+09 6995654.08
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.123002E+09 34067858.30
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.108495E+09 68720620.18
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83451317.74 0.247281E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6879283.38 0.431305E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4582464.93 0.751357E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.681076E+09 0.402065E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 710804.22 6995654.08
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.137169E+09 0.828681E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2897737.67 0.137949E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5411627.09 0.106687E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19698140.80 0.110870E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37098137.98 0.488636E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.176647E+09 61719868.88
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.162564E+09 49672366.14
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.247320E+09 15001288.68
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.221892E+09 68774123.36
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.206098E+09 0.112433E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.153130E+09 0.422677E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14780160.83 0.720329E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9876325.27 0.123794E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.125741E+10 0.673225E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2897737.67 15001288.68
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.247320E+09 0.137949E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1354655.87 0.136727E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2046759.77 0.105592E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10225982.11 0.116377E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22884696.29 0.550903E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.150999E+09 80586285.73
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.143108E+09 62146904.20
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.212073E+09 24798536.17
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.204394E+09 86558028.61
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.186486E+09 0.133689E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.119154E+09 0.454802E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10054302.45 0.733417E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7074942.76 0.123911E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.106985E+10 0.695297E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1354655.87 24798536.17
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.212073E+09 0.136727E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 14744.03 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 14744.03 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 14744.03 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 14744.03 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 14744.03 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 14744.03 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 14744.03 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 14744.03 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 14744.03 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 14744.03 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 14744.03 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 14744.03 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   14744.03   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   14744.03   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1350.49 31-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 46.57 16-JAN-15:00 698.04 09-JAN-05:00
February 2010.79 01-FEB-10:09 1401.26 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 49.90 02-FEB-13:00 972.75 05-FEB-08:00
March 2010.79 01-MAR-10:09 1281.30 27-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 92.15 05-MAR-13:00 836.00 20-MAR-22:00
April 2010.79 03-APR-09:09 1320.95 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 154.02 29-APR-17:01 507.90 01-APR-21:00
May 2010.79 01-MAY-09:09 918.00 23-MAY-07:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 222.40 21-MAY-14:00 113.61 14-MAY-12:00
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 266.55 10-JUN-17:02 151.94 06-JUN-22:00
July 2010.79 03-JUL-09:09 889.97 14-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 240.30 22-JUL-18:50 72.17 30-JUL-10:53
August 2010.79 01-AUG-09:09 922.55 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 332.95 20-AUG-14:00 156.20 26-AUG-00:10
September 2010.79 01-SEP-09:09 1277.51 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 328.61 09-SEP-22:53 195.95 05-SEP-03:10
October 2010.79 02-OCT-09:09 1474.14 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 359.88 09-OCT-13:51 412.46 29-OCT-02:00
November 2010.79 01-NOV-09:09 1409.70 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 65.34 05-NOV-13:00 594.41 12-NOV-08:00
December 2010.79 01-DEC-10:09 1461.33 12-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 59.38 10-DEC-15:10 903.42 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 46.57   72.17  
Maximum of Months 2010.79   1474.14   2160.55   0.00 0.00 0.00 0.00 359.88   972.75  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 810.19 31-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 20.51 16-JAN-15:00 475.12 22-JAN-08:00
February 1295.83 01-FEB-10:09 865.06 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 33.27 02-FEB-13:00 712.02 05-FEB-10:00
March 1295.83 01-MAR-10:09 755.79 27-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 52.85 26-MAR-14:00 549.92 20-MAR-22:00
April 1295.83 03-APR-09:09 812.31 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 101.65 29-APR-17:01 327.15 01-APR-21:00
May 1295.83 01-MAY-09:09 574.48 30-MAY-15:30 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 150.12 21-MAY-14:00 102.38 14-MAY-12:00
June 1295.83 01-JUN-09:09 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 183.08 10-JUN-17:02 95.09 06-JUN-22:00
July 1295.83 03-JUL-09:09 509.78 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 163.00 22-JUL-18:50 68.96 30-JUL-10:53
August 1295.83 01-AUG-09:09 570.19 21-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 221.03 20-AUG-14:00 96.00 26-AUG-00:10
September 1295.83 01-SEP-09:09 750.61 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 218.71 09-SEP-22:53 131.46 05-SEP-03:10
October 1295.83 02-OCT-09:09 924.70 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 234.80 09-OCT-14:06 271.21 29-OCT-02:00
November 1295.83 01-NOV-09:09 920.23 21-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 32.75 05-NOV-13:00 458.91 12-NOV-08:15
December 1295.83 01-DEC-10:09 926.10 12-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 33.48 10-DEC-15:10 582.28 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   509.78   1392.34   0.00 0.00 0.00 0.00 20.51   68.96  
Maximum of Months 1295.83   926.10   1392.34   0.00 0.00 0.00 0.00 234.80   712.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1305.22 31-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 15.08 19-JAN-12:10 697.44 26-JAN-03:00
February 2010.83 01-FEB-10:09 1372.93 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 49.90 02-FEB-13:00 973.63 05-FEB-10:00
March 2010.83 01-MAR-10:09 1265.80 27-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 69.61 26-MAR-13:55 842.09 20-MAR-22:00
April 2010.83 03-APR-09:09 1326.99 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 136.31 29-APR-17:01 511.38 01-APR-21:00
May 2010.83 01-MAY-09:09 924.74 23-MAY-07:30 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 218.41 21-MAY-14:00 121.05 14-MAY-12:00
June 2010.83 01-JUN-09:09 862.14 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 276.74 10-JUN-17:02 150.02 06-JUN-22:00
July 2010.83 03-JUL-09:09 909.81 14-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 246.11 22-JUL-18:50 81.03 30-JUL-10:53
August 2010.83 01-AUG-09:09 930.76 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 326.99 20-AUG-14:00 158.83 26-AUG-00:10
September 2010.83 01-SEP-09:09 1272.90 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 315.56 09-SEP-22:53 205.93 05-SEP-03:10
October 2010.83 02-OCT-09:09 1462.32 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 328.50 09-OCT-13:44 426.08 29-OCT-02:00
November 2010.83 01-NOV-09:09 1364.76 21-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 34.92 28-NOV-13:00 650.37 12-NOV-08:00
December 2010.83 01-DEC-10:09 1444.67 12-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 36.29 13-DEC-14:00 882.23 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   862.14   2160.58   0.00 0.00 0.00 0.00 15.08   81.03  
Maximum of Months 2010.83   1462.32   2160.58   0.00 0.00 0.00 0.00 328.50   973.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 884.21 31-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 12.22 19-JAN-12:05 493.35 26-JAN-03:00
February 1295.83 01-FEB-10:09 911.40 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 33.27 02-FEB-13:00 689.05 05-FEB-08:00
March 1295.83 01-MAR-10:09 861.21 27-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 47.58 26-MAR-13:35 623.64 20-MAR-22:00
April 1295.83 03-APR-09:09 875.00 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 55.47 29-APR-17:10 423.21 01-APR-21:00
May 1295.83 01-MAY-09:09 715.17 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 136.49 21-MAY-13:40 93.38 14-MAY-12:00
June 1295.83 01-JUN-09:09 582.63 16-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 160.18 10-JUN-17:07 142.32 06-JUN-22:00
July 1295.83 03-JUL-09:09 597.17 14-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 147.70 02-JUL-11:38 81.17 31-JUL-02:10
August 1295.83 01-AUG-09:09 780.56 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 209.29 20-AUG-14:00 161.76 26-AUG-00:10
September 1295.83 01-SEP-09:09 862.22 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 195.82 09-SEP-17:07 157.13 05-SEP-03:10
October 1295.83 02-OCT-09:09 958.99 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 225.39 09-OCT-14:04 322.52 29-OCT-02:00
November 1295.83 01-NOV-09:09 930.38 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 25.82 07-NOV-13:00 438.78 12-NOV-08:00
December 1295.83 01-DEC-10:09 942.77 12-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 24.20 13-DEC-14:00 690.40 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   582.63   1392.33   0.00 0.00 0.00 0.00 12.22   81.17  
Maximum of Months 1295.83   958.99   1392.33   0.00 0.00 0.00 0.00 225.39   690.40  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1346.59 31-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 178.01 16-JAN-15:00 1409.74 21-JAN-05:53
February 2010.79 01-FEB-10:09 1398.12 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 231.16 20-FEB-15:00 1938.68 05-FEB-07:53
March 2010.79 01-MAR-10:09 1276.68 27-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 324.23 05-MAR-13:00 1731.10 20-MAR-22:00
April 2010.79 03-APR-09:09 1316.92 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 389.44 29-APR-17:01 1014.05 01-APR-17:53
May 2010.79 01-MAY-09:09 912.08 23-MAY-07:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 515.53 07-MAY-14:00 251.38 14-MAY-12:00
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 629.02 10-JUN-17:02 309.19 06-JUN-21:20
July 2010.79 03-JUL-09:09 882.55 14-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 561.50 22-JUL-18:50 206.56 30-JUL-11:00
August 2010.79 01-AUG-09:09 916.96 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 770.40 20-AUG-14:00 439.73 25-AUG-23:55
September 2010.79 01-SEP-09:09 1272.73 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 762.57 09-SEP-22:53 421.98 05-SEP-02:55
October 2010.79 02-OCT-09:09 1471.91 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 858.77 09-OCT-14:00 810.00 29-OCT-02:00
November 2010.79 01-NOV-09:09 1406.36 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 201.45 11-NOV-12:50 1217.65 12-NOV-06:55
December 2010.79 01-DEC-10:09 1459.03 12-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 193.22 10-DEC-15:10 1752.54 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 178.01   206.56  
Maximum of Months 2010.79   1471.91   2160.55   0.00 0.00 0.00 0.00 858.77   1938.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 804.04 31-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 70.99 16-JAN-15:00 940.59 21-JAN-05:53
February 1239.33 01-FEB-08:09 860.10 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 99.09 20-FEB-15:00 1452.24 05-FEB-10:00
March 1239.33 01-MAR-08:09 749.74 27-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 125.08 26-MAR-13:53 1185.02 20-MAR-22:00
April 1239.33 03-APR-07:10 807.07 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 222.77 29-APR-17:01 711.82 01-APR-17:53
May 1239.33 01-MAY-07:10 570.10 23-MAY-07:30 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 316.13 07-MAY-13:52 263.75 14-MAY-12:00
June 1239.33 01-JUN-07:10 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 412.72 10-JUN-17:02 219.31 11-JUN-08:00
July 1239.33 03-JUL-07:10 509.78 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 346.73 22-JUL-18:50 264.45 30-JUL-11:00
August 1239.33 01-AUG-07:10 566.10 21-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 497.44 20-AUG-14:00 302.60 25-AUG-23:55
September 1239.33 01-SEP-07:10 745.00 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 493.51 09-SEP-22:53 303.58 05-SEP-02:55
October 1239.33 02-OCT-07:10 921.41 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 583.56 09-OCT-13:54 564.06 29-OCT-02:00
November 1239.33 01-NOV-07:10 916.29 21-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 70.09 05-NOV-13:00 1004.97 12-NOV-08:50
December 1239.33 01-DEC-08:09 922.56 12-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 79.10 10-DEC-15:10 1183.93 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   509.78   1392.34   0.00 0.00 0.00 0.00 70.09   219.31  
Maximum of Months 1239.33   922.56   1392.34   0.00 0.00 0.00 0.00 583.56   1452.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1301.04 31-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 28.30 19-JAN-12:00 1643.55 22-JAN-16:55
February 2010.83 01-FEB-10:09 1369.61 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 114.06 02-FEB-13:00 2070.53 05-FEB-08:00
March 2010.83 01-MAR-10:09 1261.10 27-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 157.87 26-MAR-13:58 1811.90 20-MAR-22:00
April 2010.83 03-APR-09:09 1322.99 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 336.13 29-APR-17:01 1088.50 01-APR-17:53
May 2010.83 01-MAY-09:09 919.14 23-MAY-07:30 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 493.77 07-MAY-13:52 271.58 14-MAY-12:00
June 2010.83 01-JUN-09:09 852.92 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 654.89 10-JUN-17:02 308.17 06-JUN-21:20
July 2010.83 03-JUL-09:09 903.37 14-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 581.44 22-JUL-18:50 219.53 30-JUL-11:00
August 2010.83 01-AUG-09:09 925.56 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 760.24 20-AUG-14:00 450.66 25-AUG-23:55
September 2010.83 01-SEP-09:09 1268.07 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 727.10 09-SEP-22:53 459.77 05-SEP-02:55
October 2010.83 02-OCT-09:09 1460.03 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 780.91 09-OCT-13:57 933.68 29-OCT-02:00
November 2010.83 01-NOV-09:09 1361.60 21-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 79.83 28-NOV-13:00 1518.28 12-NOV-11:00
December 2010.83 01-DEC-10:09 1442.32 12-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 83.26 13-DEC-14:00 1834.49 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   852.92   2160.58   0.00 0.00 0.00 0.00 28.30   219.53  
Maximum of Months 2010.83   1460.03   2160.58   0.00 0.00 0.00 0.00 780.91   2070.53  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 879.31 31-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 54.08 16-JAN-13:23 987.75 22-JAN-17:00
February 1295.83 01-FEB-10:09 907.22 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 76.05 02-FEB-13:00 1329.33 05-FEB-07:53
March 1295.83 01-MAR-10:09 855.65 27-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 162.48 05-MAR-12:45 1240.01 20-MAR-22:00
April 1295.83 03-APR-09:09 869.83 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 125.65 29-APR-17:06 819.06 01-APR-17:53
May 1295.83 01-MAY-09:09 705.04 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 316.13 07-MAY-13:52 182.24 14-MAY-12:00
June 1295.83 01-JUN-09:09 578.35 16-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 367.40 10-JUN-17:07 243.82 06-JUN-21:20
July 1295.83 03-JUL-09:09 593.75 14-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 329.41 02-JUL-11:28 176.12 30-JUL-11:00
August 1295.83 01-AUG-09:09 773.10 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 494.62 20-AUG-14:00 335.50 25-AUG-23:55
September 1295.83 01-SEP-09:09 856.67 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 445.29 09-SEP-17:07 326.78 05-SEP-02:55
October 1295.83 02-OCT-09:09 956.04 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 559.95 09-OCT-13:53 612.54 29-OCT-02:00
November 1295.83 01-NOV-09:09 926.72 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 97.06 11-NOV-12:10 861.61 12-NOV-06:55
December 1295.83 01-DEC-10:09 939.42 12-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 85.31 10-DEC-11:10 1227.56 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   578.35   1392.33   0.00 0.00 0.00 0.00 54.08   176.12  
Maximum of Months 1295.83   956.04   1392.33   0.00 0.00 0.00 0.00 559.95   1329.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1345.96 31-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 259.01 15-JAN-13:52 1790.94 21-JAN-06:00
February 2010.79 01-FEB-10:09 1397.58 01-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 317.67 20-FEB-15:00 2252.42 05-FEB-07:50
March 2010.79 01-MAR-10:09 1275.94 27-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 404.44 05-MAR-13:00 2024.53 20-MAR-22:00
April 2010.79 03-APR-09:09 1316.23 14-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 414.38 29-APR-17:01 1243.63 01-APR-17:53
May 2010.79 01-MAY-09:09 911.84 23-MAY-07:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 596.88 07-MAY-13:52 278.96 14-MAY-11:53
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 712.02 10-JUN-17:02 396.43 06-JUN-21:20
July 2010.79 03-JUL-09:09 882.24 14-JUL-07:10 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 620.42 02-JUL-11:58 323.36 30-JUL-11:00
August 2010.79 01-AUG-09:09 916.73 21-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 887.00 20-AUG-14:00 537.00 25-AUG-23:55
September 2010.79 01-SEP-09:09 1271.98 26-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 886.63 09-SEP-17:02 567.34 05-SEP-02:55
October 2010.79 02-OCT-09:09 1471.53 25-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 1033.97 09-OCT-13:54 867.18 29-OCT-02:00
November 2010.79 01-NOV-09:09 1405.89 01-NOV-07:10 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 240.88 05-NOV-12:52 1432.07 12-NOV-06:55
December 2010.79 01-DEC-10:09 1458.60 12-DEC-08:09 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 231.15 10-DEC-11:00 1892.70 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 231.15   278.96  
Maximum of Months 2010.79   1471.53   2160.55   0.00 0.00 0.00 0.00 1033.97   2252.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 803.57 31-JAN-08:09 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 100.98 15-JAN-13:52 1193.97 21-JAN-06:00
February 1295.83 01-FEB-10:09 859.71 01-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 152.20 20-FEB-15:00 1524.68 05-FEB-07:53
March 1295.83 01-MAR-10:09 749.19 27-MAR-07:10 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 162.32 26-MAR-14:00 1396.71 20-MAR-21:25
April 1295.83 03-APR-09:09 806.58 14-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 234.03 29-APR-17:01 872.73 01-APR-17:53
May 1295.83 01-MAY-09:09 569.90 23-MAY-07:30 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 386.47 07-MAY-13:52 276.13 14-MAY-12:10
June 1295.83 01-JUN-09:09 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 469.58 10-JUN-17:02 279.72 11-JUN-08:00
July 1295.83 03-JUL-09:09 509.78 03-JUL-07:10 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 432.88 02-JUL-11:58 355.10 30-JUL-11:00
August 1295.83 01-AUG-09:09 565.89 21-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 591.32 20-AUG-14:00 368.65 25-AUG-23:55
September 1295.83 01-SEP-09:09 744.44 26-SEP-07:10 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 577.02 09-SEP-17:02 399.15 05-SEP-02:55
October 1295.83 02-OCT-09:09 921.14 25-OCT-07:10 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 722.48 09-OCT-13:54 606.94 29-OCT-02:00
November 1295.83 01-NOV-09:09 915.99 21-NOV-16:00 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 79.90 05-NOV-13:10 1174.83 12-NOV-08:50
December 1295.83 01-DEC-10:09 922.27 12-DEC-08:09 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 93.62 10-DEC-15:00 1272.27 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   509.78   1392.34   0.00 0.00 0.00 0.00 79.90   276.13  
Maximum of Months 1295.83   922.27   1392.34   0.00 0.00 0.00 0.00 722.48   1524.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1300.34 31-JAN-08:09 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 42.12 19-JAN-12:05 1916.86 22-JAN-16:55
February 2010.83 01-FEB-10:09 1369.03 01-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 137.94 02-FEB-13:00 2271.33 05-FEB-07:53
March 2010.83 01-MAR-10:09 1260.34 27-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 192.57 26-MAR-13:58 2138.73 20-MAR-21:25
April 2010.83 03-APR-09:09 1322.31 14-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 347.35 29-APR-17:01 1341.39 01-APR-17:53
May 2010.83 01-MAY-09:09 918.92 23-MAY-07:30 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 579.72 07-MAY-13:52 299.09 14-MAY-11:53
June 2010.83 01-JUN-09:09 852.58 16-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 742.33 10-JUN-17:02 396.30 06-JUN-21:20
July 2010.83 03-JUL-09:09 903.12 14-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 629.65 02-JUL-11:58 338.75 30-JUL-11:00
August 2010.83 01-AUG-09:09 925.35 21-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 886.99 20-AUG-14:00 550.94 25-AUG-23:55
September 2010.83 01-SEP-09:09 1267.31 26-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 833.05 09-SEP-17:08 605.87 05-SEP-02:55
October 2010.83 02-OCT-09:09 1459.63 25-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 944.36 09-OCT-13:57 1034.46 29-OCT-02:00
November 2010.83 01-NOV-09:09 1361.04 21-NOV-16:00 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 97.55 07-NOV-13:00 1739.64 12-NOV-10:53
December 2010.83 01-DEC-10:09 1441.87 12-DEC-08:09 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 101.07 13-DEC-14:00 1973.80 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   852.58   2160.58   0.00 0.00 0.00 0.00 42.12   299.09  
Maximum of Months 2010.83   1459.63   2160.58   0.00 0.00 0.00 0.00 944.36   2271.33  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 878.93 31-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 76.23 16-JAN-13:23 1198.86 21-JAN-05:57
February 1295.83 01-FEB-10:09 906.88 01-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 91.96 02-FEB-13:00 1508.49 05-FEB-07:53
March 1295.83 01-MAR-10:09 855.22 27-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 198.85 05-MAR-12:45 1467.88 20-MAR-21:25
April 1295.83 03-APR-09:09 869.42 14-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 151.39 29-APR-16:00 1005.47 01-APR-17:53
May 1295.83 01-MAY-09:09 704.44 24-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 386.48 07-MAY-13:52 238.87 06-MAY-20:00
June 1295.83 01-JUN-09:09 578.20 16-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 439.26 10-JUN-17:07 311.48 06-JUN-21:20
July 1295.83 03-JUL-09:09 593.62 14-JUL-07:10 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 429.63 02-JUL-11:58 254.80 30-JUL-11:00
August 1295.83 01-AUG-09:09 772.71 23-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 591.35 20-AUG-14:00 410.87 25-AUG-23:55
September 1295.83 01-SEP-09:09 856.25 26-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 544.62 09-SEP-17:10 420.88 05-SEP-02:55
October 1295.83 02-OCT-09:09 955.81 25-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 673.69 09-OCT-13:53 684.38 29-OCT-02:00
November 1295.83 01-NOV-09:09 926.46 01-NOV-07:10 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 108.35 11-NOV-11:52 1018.26 12-NOV-06:55
December 1295.83 01-DEC-10:09 939.15 12-DEC-08:09 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 108.74 10-DEC-11:00 1349.23 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   578.20   1392.33   0.00 0.00 0.00 0.00 76.23   238.87  
Maximum of Months 1295.83   955.81   1392.33   0.00 0.00 0.00 0.00 673.69   1508.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 4157.19 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 4157.19 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 4157.19 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 4157.19 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 4157.19 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 4157.19 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 4157.19 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 4157.19 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 4157.19 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 4157.19 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 4157.19 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 4157.19 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   4157.19   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   4157.19   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64.23 16-JAN-15:00 1522.62 26-JAN-03:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.31 02-FEB-13:00 2190.54 05-FEB-07:53
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 186.64 26-MAR-14:00 1846.80 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 292.58 29-APR-17:01 1080.64 01-APR-21:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 483.73 21-MAY-14:00 176.65 14-MAY-12:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 576.31 10-JUN-17:02 286.78 06-JUN-21:20
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 491.53 22-JUL-18:53 113.13 31-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 686.60 20-AUG-14:00 393.02 25-AUG-23:55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 653.12 09-SEP-17:02 369.85 05-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 745.69 09-OCT-13:51 908.50 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.49 05-NOV-13:00 1283.54 12-NOV-08:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 89.86 10-DEC-14:51 2027.93 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64.23   113.13  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 745.69   2190.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 200.23 16-JAN-15:00 2617.02 21-JAN-05:53
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 190.23 20-FEB-15:00 3753.55 05-FEB-07:53
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 410.67 05-MAR-13:00 3172.30 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 562.72 29-APR-17:01 1809.99 01-APR-21:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 884.92 21-MAY-14:00 295.95 14-MAY-12:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1058.71 10-JUN-17:02 495.53 06-JUN-21:20
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 921.79 22-JUL-18:53 213.66 31-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1258.21 20-AUG-14:00 732.72 25-AUG-23:55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1199.51 09-SEP-17:02 598.05 05-SEP-02:55
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1357.80 09-OCT-14:00 1538.50 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 210.38 05-NOV-13:00 2193.46 12-NOV-08:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 210.49 10-DEC-14:51 3433.32 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 190.23   213.66  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1357.80   3753.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 164.58 16-JAN-15:00 2583.52 21-JAN-06:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 129.41 02-FEB-13:00 3378.25 05-FEB-07:53
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 287.37 05-MAR-13:00 3336.47 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 371.11 29-APR-17:01 2027.13 01-APR-17:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 700.47 21-MAY-14:00 610.84 14-MAY-11:53
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 962.82 10-JUN-17:02 523.44 06-JUN-21:20
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 728.20 02-JUL-10:53 575.52 30-JUL-11:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1150.26 20-AUG-14:00 803.49 25-AUG-23:55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1313.13 09-SEP-22:53 796.03 05-SEP-02:55
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 941.55 08-OCT-14:00 1430.11 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 141.37 05-NOV-12:52 2270.84 12-NOV-06:55
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 111.14 10-DEC-15:00 3208.34 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 111.14   523.44  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1313.13   3378.25  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 105120.73 09-JAN-05:11 0.00 4188.45 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
February 106438.71 13-FEB-05:11 0.00 4188.45 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
March 106693.06 20-MAR-04:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
April 106031.03 17-APR-04:11 0.00 4188.45 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
May 78135.42 29-MAY-18:40 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
June 79959.40 12-JUN-03:02 0.00 2991.75 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 76319.07 05-JUL-03:13 0.00 1795.05 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
August 81566.65 21-AUG-03:02 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
September 80036.43 04-SEP-12:28 3590.45 3276.21 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
October 102293.16 17-OCT-04:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
November 105194.28 24-NOV-05:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
December 108228.75 26-DEC-05:11 0.00 4786.80 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 76319.07   0.00 1795.05 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 108228.75   3590.45 4786.80 107660.35 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 89293.25 02-JAN-05:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
February 89854.16 27-FEB-05:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
March 86053.83 06-MAR-05:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
April 85326.87 04-APR-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
May 82063.38 16-MAY-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
June 87122.00 01-JUN-04:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
July 77020.87 17-JUL-05:03 9673.43 3224.16 45884.34 0.00 0.00 0.00 0.00 0.00 0.00
August 77969.94 07-AUG-05:03 9673.43 3224.16 45884.34 0.00 0.00 0.00 0.00 0.00 0.00
September 82865.54 22-SEP-04:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
October 90251.74 02-OCT-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
November 89116.55 13-NOV-05:11 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
December 89542.52 26-DEC-05:12 0.00 4298.88 47501.16 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 77020.87   0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 90251.74   9673.43 4298.88 47501.16 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 74121.26 02-JAN-05:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
February 74261.38 28-FEB-05:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
March 74267.55 31-MAR-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
April 74706.77 26-APR-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
May 77102.93 16-MAY-04:13 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
June 75694.10 07-JUN-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 72864.86 12-JUL-04:12 0.00 2149.44 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
August 74996.27 17-AUG-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
September 74240.52 28-SEP-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
October 76268.47 17-OCT-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
November 75343.39 07-NOV-05:11 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
December 74670.93 14-DEC-05:11 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 72864.86   0.00 2149.44 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 77102.93   0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 70466.58 20-JAN-06:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
February 69692.91 03-FEB-06:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
March 73106.10 30-MAR-05:04 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
April 74282.85 15-APR-05:03 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
May 75084.65 31-MAY-04:13 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
June 74489.28 07-JUN-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 73153.90 12-JUL-04:12 0.00 2149.44 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
August 73616.78 17-AUG-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
September 73512.16 22-SEP-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
October 73825.97 02-OCT-04:11 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
November 73460.15 08-NOV-05:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
December 71622.39 15-DEC-06:04 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 69692.91   0.00 2149.44 23750.49 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 75084.65   9673.43 3761.52 45884.17 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8535.70 02-JAN-05:12 0.00 404.83 4473.37 0.00 0.00 0.00 0.00 0.00 61.60
February 8094.02 28-FEB-05:12 0.00 404.83 4473.37 0.00 0.00 0.00 0.00 0.00 47.47
March 8467.56 28-MAR-12:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 20.19 0.00
April 10876.45 24-APR-05:02 1214.60 404.83 5761.47 0.00 0.00 0.00 0.00 0.00 1.21
May 14282.73 07-MAY-14:42 506.08 219.72 3600.92 0.00 0.00 0.00 0.00 124.52 0.00
June 15763.41 25-JUN-16:21 809.73 351.55 5761.47 0.00 0.00 0.00 0.00 45.65 0.00
July 15408.04 23-JUL-16:22 506.08 219.72 3600.92 0.00 0.00 0.00 0.00 136.05 0.00
August 13681.91 13-AUG-16:22 506.08 219.72 3600.92 0.00 0.00 0.00 0.00 47.80 0.00
September 12358.05 24-SEP-15:31 708.51 307.61 5041.29 0.00 0.00 0.00 0.00 95.58 0.00
October 15361.97 08-OCT-14:51 708.51 307.61 5041.29 0.00 0.00 0.00 0.00 212.11 0.00
November 11947.28 01-NOV-04:11 0.00 472.30 5218.93 0.00 0.00 0.00 0.00 0.00 29.36
December 7791.87 12-DEC-06:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 18.78
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7791.87   0.00 219.72 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15763.41   1923.11 791.05 5761.47 0.00 0.00 0.00 0.00 212.11 61.60



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9670.45 16-JAN-10:03 195.68 84.96 1392.34 0.00 0.00 0.00 0.00 0.00 109.81
February 15652.41 26-FEB-10:32 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 10.57
March 17838.98 26-MAR-09:32 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 30.33
April 17752.31 23-APR-09:02 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 31.65
May 19255.94 14-MAY-08:42 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 1.53
June 17689.85 04-JUN-09:22 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 30.12 0.00
July 19242.53 16-JUL-09:41 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 39.65 0.00
August 16338.17 06-AUG-09:42 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 32.36 0.00
September 19266.85 24-SEP-09:32 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 10.62 0.00
October 17935.88 15-OCT-08:53 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 109.78
November 17668.81 11-NOV-09:13 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 29.86
December 7416.09 10-DEC-09:03 195.68 84.96 1392.34 0.00 0.00 0.00 0.00 0.00 105.48
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7416.09   195.68 84.96 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19266.85   456.59 198.23 3248.80 0.00 0.00 0.00 0.00 39.65 109.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 21429.73 01-JAN-13:32 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 31.71
February 21776.56 26-FEB-13:52 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 38.13
March 20484.94 05-MAR-13:23 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 6.97 0.00
April 14665.71 23-APR-11:43 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 4.85 0.00
May 19119.78 07-MAY-14:42 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 123.07 0.00
June 19457.22 25-JUN-15:41 809.75 351.56 5761.56 0.00 0.00 0.00 0.00 42.50 0.00
July 19263.83 30-JUL-14:12 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 88.72 0.00
August 19430.02 27-AUG-12:23 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 112.99 0.00
September 20507.12 17-SEP-14:42 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 122.90 0.00
October 21566.97 08-OCT-14:51 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 126.75 0.00
November 22601.03 11-NOV-13:51 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 0.00 83.70
December 21246.67 31-DEC-14:22 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 72.95
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 14665.71   404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22601.03   809.75 351.56 5761.56 0.00 0.00 0.00 0.00 126.75 83.70



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20044.73 01-JAN-15:32 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 15.02
February 23015.45 26-FEB-15:12 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 18.90
March 21252.91 26-MAR-15:32 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 37.54
April 23702.54 23-APR-16:22 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 4.38
May 23357.99 29-MAY-16:12 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 54.81 0.00
June 25265.04 25-JUN-16:21 521.82 226.55 3712.89 0.00 0.00 0.00 0.00 20.18 0.00
July 23893.92 30-JUL-16:52 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 10.90
August 23043.57 06-AUG-16:22 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 36.72
September 24646.37 17-SEP-15:21 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 80.71 0.00
October 24413.86 08-OCT-14:51 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 87.10 0.00
November 24256.00 11-NOV-14:31 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 0.00 31.41
December 22994.22 10-DEC-15:42 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 1.46
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 20044.73   326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25265.04   521.82 226.55 3712.89 0.00 0.00 0.00 0.00 87.10 37.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5231.09 31-JAN-14:40 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 23.13 0.00
February 5473.24 22-FEB-14:30 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 12.03 0.00
March 7034.45 30-MAR-13:30 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 50.32 0.00
April 9290.84 28-APR-05:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 6.85
May 11147.17 13-MAY-04:12 0.00 404.83 3355.02 0.00 0.00 0.00 0.00 0.00 93.22
June 12983.51 29-JUN-03:02 0.00 337.35 3727.80 0.00 0.00 0.00 0.00 0.00 1.50
July 14430.23 23-JUL-16:22 506.08 219.72 3600.92 0.00 0.00 0.00 0.00 312.52 0.00
August 13682.07 13-AUG-15:12 506.08 219.72 3600.92 0.00 0.00 0.00 0.00 250.20 0.00
September 14813.07 10-SEP-14:31 708.51 307.61 5041.29 0.00 0.00 0.00 0.00 279.66 0.00
October 10759.24 06-OCT-03:02 0.00 337.35 3727.80 0.00 0.00 0.00 0.00 54.48 0.00
November 9969.94 02-NOV-05:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 5.25
December 5924.20 15-DEC-14:10 4021.58 1582.09 4321.10 0.00 0.00 0.00 0.00 44.33 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5231.09   0.00 219.72 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14813.07   4021.58 1582.09 5041.29 0.00 0.00 0.00 0.00 312.52 93.22



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8765.59 19-JAN-11:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 10.58 0.00
February 10938.62 26-FEB-11:23 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 25.60
March 18395.91 26-MAR-09:43 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 65.98
April 20405.71 23-APR-09:32 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 97.71
May 20392.01 14-MAY-09:22 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 6.34 0.00
June 19509.05 04-JUN-10:22 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 51.13 0.00
July 18836.35 16-JUL-09:52 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 131.43 0.00
August 18580.68 06-AUG-08:32 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 51.19 0.00
September 20066.53 10-SEP-08:32 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 177.25 0.00
October 19972.55 09-OCT-09:12 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 44.65
November 10477.59 02-NOV-10:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 11.98 0.00
December 7337.00 16-DEC-11:05 782.73 339.85 1547.05 0.00 0.00 0.00 0.00 21.49 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7337.00   260.91 113.28 1547.05 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20405.71   2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 177.25 97.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 21365.24 16-JAN-14:32 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 89.63
February 19828.60 26-FEB-11:23 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 61.77
March 19671.27 05-MAR-13:53 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 10.60 0.00
April 16604.24 23-APR-14:51 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 165.40 0.00
May 13510.81 03-MAY-04:12 0.00 404.83 4473.43 0.00 0.00 0.00 0.00 0.00 53.98
June 13316.11 29-JUN-05:02 1012.19 337.36 4801.30 0.00 0.00 0.00 0.00 0.65 0.00
July 16553.30 23-JUL-16:22 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 322.39 0.00
August 18468.27 13-AUG-14:32 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 340.81 0.00
September 20525.66 10-SEP-14:31 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 239.48 0.00
October 21175.04 01-OCT-13:42 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 43.48
November 21182.51 26-NOV-13:32 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 284.49
December 20773.45 10-DEC-14:22 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 35.31
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13316.11   0.00 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21365.24   1012.19 404.83 5041.36 0.00 0.00 0.00 0.00 340.81 284.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 17082.55 16-JAN-15:52 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 44.29
February 18029.82 26-FEB-16:42 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 66.82
March 19957.44 26-MAR-15:42 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 91.71
April 20671.86 23-APR-16:51 521.82 226.55 3712.89 0.00 0.00 0.00 0.00 0.00 28.68
May 20814.81 14-MAY-18:02 0.00 169.91 2162.09 0.00 0.00 0.00 0.00 9.95 0.00
June 20574.09 11-JUN-16:42 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 116.48 0.00
July 19693.18 16-JUL-15:52 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 258.40 0.00
August 19172.13 13-AUG-14:32 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 222.12 0.00
September 21019.10 10-SEP-14:31 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 162.72 0.00
October 21187.37 09-OCT-16:31 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 0.00 35.34
November 17013.03 05-NOV-16:33 260.91 113.28 1856.44 0.00 0.00 0.00 0.00 0.00 7.93
December 16960.49 10-DEC-15:42 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 8.08 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16960.49   0.00 113.28 1856.44 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21187.37   521.82 226.55 3712.89 0.00 0.00 0.00 0.00 258.40 91.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5516.46 31-JAN-15:00 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 25.21 0.00
February 5925.67 22-FEB-14:30 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 13.81 0.00
March 7498.45 30-MAR-13:30 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 60.95 0.00
April 9146.70 28-APR-15:00 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 188.11 0.00
May 16925.75 29-MAY-14:42 607.30 263.66 4321.10 0.00 0.00 0.00 0.00 150.70 0.00
June 16916.57 04-JUN-16:12 607.30 263.66 4321.10 0.00 0.00 0.00 0.00 107.73 0.00
July 17044.98 23-JUL-16:22 506.08 219.72 3600.92 0.00 0.00 0.00 0.00 346.33 0.00
August 16622.27 20-AUG-14:12 607.30 263.66 4321.10 0.00 0.00 0.00 0.00 734.69 0.00
September 17586.69 10-SEP-14:31 708.51 307.61 5041.29 0.00 0.00 0.00 0.00 322.01 0.00
October 17167.89 08-OCT-13:01 708.51 307.61 5041.29 0.00 0.00 0.00 0.00 633.29 0.00
November 10965.19 01-NOV-05:02 1012.16 337.35 4801.23 0.00 0.00 0.00 0.00 0.00 12.94
December 6444.82 15-DEC-15:00 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 64.02 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5516.46   506.08 219.72 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17586.69   2010.79 791.05 5041.29 0.00 0.00 0.00 0.00 734.69 12.94



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7264.85 19-JAN-10:20 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 11.53
February 7648.84 27-FEB-10:30 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 16.66
March 12063.42 26-MAR-09:13 195.68 84.96 1392.34 0.00 0.00 0.00 0.00 0.00 91.20
April 18996.97 23-APR-09:42 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 59.70
May 21444.21 29-MAY-10:01 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 1.13
June 20526.93 04-JUN-09:32 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 32.55 0.00
July 21202.71 16-JUL-09:41 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 81.85 0.00
August 18915.56 06-AUG-08:32 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 58.96 0.00
September 20550.57 10-SEP-08:32 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 208.29 0.00
October 20325.66 09-OCT-09:12 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 70.05
November 14855.15 11-NOV-09:43 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 90.63
December 6027.05 16-DEC-10:00 391.37 169.93 773.52 0.00 0.00 0.00 0.00 0.00 1.97
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6027.05   195.68 84.96 773.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21444.21   1295.83 509.78 3248.80 0.00 0.00 0.00 0.00 208.29 91.20



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 23228.98 16-JAN-15:12 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 115.60
February 21684.02 26-FEB-14:02 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 65.21
March 21535.19 05-MAR-13:53 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 15.12 0.00
April 16820.84 23-APR-15:02 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 170.54 0.00
May 20846.28 29-MAY-14:42 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 152.07 0.00
June 20537.16 04-JUN-16:12 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 120.12 0.00
July 20712.04 23-JUL-16:22 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 365.03 0.00
August 20779.41 27-AUG-12:23 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 306.62 0.00
September 23407.65 10-SEP-14:31 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 274.67 0.00
October 24055.67 08-OCT-13:01 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 366.90 0.00
November 24469.31 11-NOV-13:41 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 0.00 281.05
December 25083.01 10-DEC-14:11 809.75 351.56 5761.56 0.00 0.00 0.00 0.00 0.00 140.40
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16820.84   404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25083.01   809.75 351.56 5761.56 0.00 0.00 0.00 0.00 366.90 281.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 15929.58 16-JAN-15:52 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 57.76
February 18063.25 26-FEB-16:42 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 86.81
March 18607.18 26-MAR-15:13 260.91 113.28 1856.44 0.00 0.00 0.00 0.00 0.00 166.14
April 22580.82 16-APR-16:52 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 634.71
May 22579.34 29-MAY-16:41 521.82 226.55 3712.89 0.00 0.00 0.00 0.00 111.44 0.00
June 22337.64 04-JUN-16:12 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 40.75 0.00
July 21398.14 16-JUL-16:22 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 195.67 0.00
August 20623.85 20-AUG-16:51 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 158.68 0.00
September 23160.39 10-SEP-14:31 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 188.93 0.00
October 23117.26 01-OCT-15:51 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 0.00 41.52
November 21699.26 11-NOV-15:01 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 0.00 57.98
December 21969.87 10-DEC-15:31 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 0.00 17.96
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15929.58   260.91 113.28 1856.44 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23160.39   521.82 226.55 3712.89 0.00 0.00 0.00 0.00 195.67 634.71



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11693.21 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 46.30
February 7803.33 27-FEB-16:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.94
March 7669.45 07-MAR-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.97 0.00
April 7504.19 26-APR-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.57 0.00
May 11395.76 30-MAY-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 8970.87 14-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.92
July 11219.83 05-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.83 0.00
August 10305.19 21-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.54 0.00
September 12112.26 05-SEP-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 55.02
October 9817.00 10-OCT-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64.06
November 8190.43 07-NOV-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.55
December 7499.57 11-DEC-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.08
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 7499.57   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12112.26   0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.57 85.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7388.50 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 321.51
February 4736.65 27-FEB-16:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.33
March 4050.01 07-MAR-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.79 0.00
April 5540.89 28-APR-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 187.97 0.00
May 7815.25 16-MAY-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61.84 0.00
June 6894.31 20-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.26
July 8049.59 01-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.94
August 6972.01 01-AUG-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 8524.36 25-SEP-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.10
October 7611.82 11-OCT-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 64.17
November 5227.17 07-NOV-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.05 0.00
December 6219.66 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 576.15
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4050.01   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8524.36   0.00 0.00 0.00 0.00 0.00 0.00 0.00 187.97 576.15



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11167.76 19-JAN-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 37.04
February 11751.01 27-FEB-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.03 0.00
March 12556.28 06-MAR-15:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16.84 0.00
April 18238.78 26-APR-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.34 0.00
May 22026.79 03-MAY-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 77.87 0.00
June 19551.03 07-JUN-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 102.59 0.00
July 18360.58 07-JUL-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 116.63 0.00
August 17660.93 03-AUG-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 299.82 0.00
September 16336.11 01-SEP-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 112.56 0.00
October 16120.16 05-OCT-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 153.51 0.00
November 12778.07 02-NOV-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 81.56 0.00
December 10885.83 15-DEC-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.58 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 10885.83   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22026.79   0.00 0.00 0.00 0.00 0.00 0.00 0.00 299.82 37.04



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2149.84 01-JAN-17:20 11.69 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 4231.61 26-FEB-17:56 58.46 87.96 19486.06 0.00 0.00 0.00 0.00 0.00 0.00
March 7189.17 31-MAR-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8003.70 16-APR-18:20 0.00 70.37 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
May 3476.40 31-MAY-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5344.73 30-JUN-24:00 0.00 35.18 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7222.03 31-JUL-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 7799.67 06-AUG-18:00 0.00 70.37 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3491.75 30-SEP-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5351.01 31-OCT-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6035.79 12-NOV-17:10 23.38 35.18 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
December 7894.74 10-DEC-16:53 70.15 105.55 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2149.84   0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8003.70   70.15 105.55 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1846.63 18-JAN-17:00 222.14 316.63 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3860.10 26-FEB-17:56 58.46 87.96 19486.06 0.00 0.00 0.00 0.00 0.00 0.00
March 6733.01 31-MAR-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7492.78 16-APR-18:20 0.00 70.37 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
May 3257.80 31-MAY-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5171.25 30-JUN-24:00 0.00 35.18 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 6921.52 31-JUL-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 7276.40 06-AUG-17:40 0.00 105.55 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 3232.93 30-SEP-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4963.97 31-OCT-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5671.82 06-NOV-17:00 222.14 316.63 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7389.05 15-DEC-17:00 222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1846.63   0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7492.78   222.14 316.63 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1910.22 18-JAN-17:00 222.14 316.63 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3889.26 26-FEB-17:43 70.15 105.55 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
March 6638.38 31-MAR-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7684.36 23-APR-18:04 0.00 87.96 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
May 3227.07 31-MAY-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5200.47 30-JUN-24:00 0.00 35.18 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 6909.58 31-JUL-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 7544.83 06-AUG-17:40 0.00 105.55 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 3254.86 30-SEP-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4899.21 31-OCT-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5736.17 06-NOV-17:00 222.14 316.63 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7459.53 15-DEC-17:00 222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1910.22   0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7684.36   222.14 316.63 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 93010.01 02-JAN-17:00 4808.68 4157.19 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 183706.24 27-FEB-17:00 4808.68 4157.19 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358528.34 31-MAR-24:00 0.00 230.94 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 368174.57 18-APR-16:05 3037.06 4619.06 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
May 175657.17 31-MAY-24:00 0.00 230.94 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267281.88 30-JUN-23:55 0.00 461.88 569448.78 0.00 0.00 0.00 0.00 0.00 0.00
July 359537.52 31-JUL-24:00 0.00 230.94 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
August 370785.51 09-AUG-21:02 1518.53 2771.56 2277795.13 0.00 0.00 0.00 0.00 0.00 0.00
September 176557.23 30-SEP-24:00 0.00 230.94 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268649.70 31-OCT-24:00 0.00 230.94 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 276565.10 06-NOV-17:00 4808.68 4157.19 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 368062.46 26-DEC-17:00 4808.68 4157.19 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 93010.01   0.00 230.94 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 370785.51   4808.68 4619.06 2277795.13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.154664E+13 1259731.04 18-JAN-16:30 0.868894E+11 425796.93 05-JAN-07:10
February 0.180003E+13 1427285.41 27-FEB-16:49 0.671643E+11 488547.59 06-FEB-06:10
March 0.245402E+13 1542761.15 07-MAR-09:50 0.723971E+11 348686.66 09-MAR-07:10
April 0.287853E+13 1751633.97 18-APR-15:09 0.536261E+11 163337.13 18-APR-14:50
May 0.201444E+13 1397081.72 16-MAY-15:50 0.536110E+11 68041.12 03-MAY-11:39
June 0.239811E+13 1510537.07 07-JUN-14:30 0.506129E+11 64080.80 06-JUN-11:50
July 0.286342E+13 1616609.33 18-JUL-15:30 0.488563E+11 61746.78 06-JUL-11:20
August 0.332759E+13 1767684.12 03-AUG-15:30 0.518511E+11 62301.44 21-AUG-11:30
September 0.194375E+13 1286546.95 01-SEP-15:09 0.497612E+11 65037.24 19-SEP-11:00
October 0.232720E+13 1456628.64 06-OCT-15:09 0.536453E+11 69080.32 25-OCT-11:30
November 0.241432E+13 1572541.15 02-NOV-15:09 0.556422E+11 102255.32 16-NOV-06:10
December 0.276014E+13 1706180.64 15-DEC-16:19 0.756524E+11 478283.73 21-DEC-07:10
             
Annual Sum or Average 0.287282E+14     0.719709E+12    
Minimum of Months 0.154664E+13 1259731.04   0.488563E+11 61746.78  
Maximum of Months 0.332759E+13 1767684.12   0.868894E+11 488547.59  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.206690E+12 0.361342E+11 0.766053E+12 0.162121E+12 0.157993E+12 0.319367E+11 0.00 0.932422E+11 0.420262E+11 0.484046E+11 0.203855E+10 0.00 0.00
February 0.186592E+12 0.301979E+11 0.978954E+12 0.146439E+12 0.145584E+12 0.359541E+11 0.00 0.158134E+12 0.597592E+11 0.559666E+11 0.244903E+10 0.00 0.00
March 0.221104E+12 0.302873E+11 0.141687E+13 0.162292E+12 0.164416E+12 0.436052E+11 0.00 0.252385E+12 0.860360E+11 0.745135E+11 0.250487E+10 0.00 0.00
April 0.196634E+12 0.263337E+11 0.165903E+13 0.156876E+12 0.166122E+12 0.558940E+11 0.00 0.461555E+12 0.132208E+12 0.199089E+11 0.397010E+10 0.00 0.00
May 0.211412E+12 0.244441E+11 0.774844E+12 0.162206E+12 0.187438E+12 0.644446E+11 0.00 0.403572E+12 0.179989E+12 0.00 0.608670E+10 0.00 0.00
June 0.210129E+12 0.222460E+11 0.106252E+13 0.157035E+12 0.185883E+12 0.698730E+11 0.00 0.503738E+12 0.180602E+12 0.00 0.608670E+10 0.00 0.00
July 0.196589E+12 0.239207E+11 0.139340E+13 0.162046E+12 0.188016E+12 0.760716E+11 0.00 0.622772E+12 0.194826E+12 0.00 0.577748E+10 0.00 0.00
August 0.219919E+12 0.260564E+11 0.173200E+13 0.162291E+12 0.195328E+12 0.785553E+11 0.00 0.712702E+12 0.194405E+12 1332189.38 0.633082E+10 0.00 0.00
September 0.196974E+12 0.279381E+11 0.740713E+12 0.156875E+12 0.178041E+12 0.636213E+11 0.00 0.396195E+12 0.177611E+12 0.00 0.577748E+10 0.00 0.00
October 0.205325E+12 0.319743E+11 0.108340E+13 0.162121E+12 0.185959E+12 0.630541E+11 0.00 0.418512E+12 0.156103E+12 0.160164E+11 0.473455E+10 0.00 0.00
November 0.204295E+12 0.340165E+11 0.135889E+13 0.156940E+12 0.164995E+12 0.477194E+11 0.00 0.295996E+12 0.101885E+12 0.471610E+11 0.241979E+10 0.00 0.00
December 0.200647E+12 0.369432E+11 0.170972E+13 0.162046E+12 0.162312E+12 0.410288E+11 0.00 0.283100E+12 0.850122E+11 0.770019E+11 0.233119E+10 0.00 0.00
                           
Annual Sum or Average 0.245631E+13 0.350492E+12 0.146764E+14 0.190929E+13 0.208209E+13 0.671758E+12 0.00 0.460190E+13 0.159046E+13 0.338974E+12 0.505073E+11 0.00 0.00
Minimum of Months 0.186592E+12 0.222460E+11 0.740713E+12 0.146439E+12 0.145584E+12 0.319367E+11 0.00 0.932422E+11 0.420262E+11 0.00 0.203855E+10 0.00 0.00
Maximum of Months 0.221104E+12 0.369432E+11 0.173200E+13 0.162292E+12 0.195328E+12 0.785553E+11 0.00 0.712702E+12 0.194826E+12 0.770019E+11 0.633082E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.280036E+11 0.00 0.588858E+11 0.00 0.00
February 0.00 0.00 0.140484E+11 0.00 0.531159E+11 0.00 0.00
March 0.00 0.00 0.127619E+11 0.00 0.596352E+11 0.00 0.00
April 0.00 0.00 0.445598E+09 0.00 0.531805E+11 0.00 0.00
May 0.00 0.00 0.00 0.00 0.536110E+11 0.00 0.00
June 0.00 0.00 0.00 0.00 0.506129E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.488563E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.518511E+11 0.00 0.00
September 0.00 0.00 0.00 0.00 0.497612E+11 0.00 0.00
October 0.00 0.00 26362791.20 0.00 0.536189E+11 0.00 0.00
November 0.00 0.00 0.958869E+09 0.00 0.546834E+11 0.00 0.00
December 0.00 0.00 0.185895E+11 0.00 0.570628E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.748343E+11 0.00 0.644875E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.488563E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.280036E+11 0.00 0.596352E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 233583.75 31-JAN-08:09 40855.88 01-JAN-06:10 423497.50 02-JAN-08:09 116883.71 31-JAN-08:20 136396.65 18-JAN-16:30 58527.07 18-JAN-16:30 0.00 01-JAN-00:10
February 236029.24 01-FEB-08:09 40855.88 01-FEB-06:10 541788.89 01-FEB-08:09 116885.00 01-FEB-08:20 156931.80 27-FEB-16:49 58688.53 27-FEB-16:49 0.00 01-FEB-00:10
March 231331.41 27-MAR-07:10 40855.88 01-MAR-06:10 660080.29 01-MAR-08:09 116882.52 27-MAR-07:19 148551.50 07-MAR-13:00 58694.52 07-MAR-13:00 0.00 01-MAR-00:10
April 233412.91 14-APR-07:10 40855.88 01-APR-05:10 778371.69 03-APR-07:10 116883.62 14-APR-07:19 166863.50 26-APR-13:30 58407.94 26-APR-13:30 0.00 01-APR-00:10
May 218666.17 23-MAY-07:30 40855.88 01-MAY-05:10 423497.50 01-MAY-07:10 116875.81 23-MAY-07:40 262229.47 05-MAY-12:00 58752.01 31-MAY-09:30 0.00 01-MAY-00:10
June 214393.11 16-JUN-07:10 40855.88 01-JUN-05:10 541788.89 01-JUN-07:10 116873.55 16-JUN-07:19 262229.47 07-JUN-14:30 58762.75 05-JUN-09:30 0.00 01-JUN-00:10
July 216284.93 14-JUL-07:10 40855.88 01-JUL-05:10 660080.29 03-JUL-07:10 116874.55 14-JUL-07:19 134358.81 07-JUL-15:00 52507.95 13-JUL-14:50 0.00 01-JUL-00:10
August 219406.04 21-AUG-07:10 40855.88 01-AUG-05:10 778371.69 01-AUG-07:10 116876.20 21-AUG-07:19 143781.99 30-AUG-15:00 52089.39 03-AUG-16:19 0.00 01-AUG-00:10
September 231322.85 26-SEP-07:10 40855.88 01-SEP-05:10 423497.50 01-SEP-07:10 116882.51 26-SEP-07:19 134477.97 01-SEP-14:00 58545.43 13-SEP-12:39 0.00 01-SEP-00:10
October 239317.20 25-OCT-07:10 40855.88 01-OCT-05:10 541788.89 02-OCT-07:10 116886.75 25-OCT-07:19 143313.99 11-OCT-15:30 58701.42 10-OCT-09:20 0.00 01-OCT-00:10
November 236006.70 21-NOV-16:00 40855.88 01-NOV-05:10 660080.29 01-NOV-07:10 116884.75 01-NOV-07:19 132807.63 06-NOV-13:00 58643.51 29-NOV-16:30 0.00 01-NOV-00:10
December 238764.99 12-DEC-08:09 40855.88 01-DEC-06:10 778371.69 01-DEC-08:09 116886.45 12-DEC-08:20 130396.25 13-DEC-15:09 58408.14 12-DEC-16:40 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 214393.11   40855.88   423497.50   116873.55   130396.25   52089.39   0.00  
Maximum of Months 239317.20   40855.88   778371.69   116886.75   262229.47   58762.75   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 290924.89 31-JAN-15:30 84322.72 02-JAN-10:00 100000.00 06-JAN-12:00 4520.72 02-JAN-10:09 0.00 0.00
February 320141.10 27-FEB-16:00 84322.72 01-FEB-13:30 100000.00 04-FEB-17:10 4520.72 01-FEB-11:50 0.00 0.00
March 362549.62 30-MAR-14:30 84322.72 06-MAR-09:30 100000.00 03-MAR-22:10 4520.72 06-MAR-07:10 0.00 0.00
April 408328.52 28-APR-16:00 84322.72 04-APR-14:00 100000.00 10-APR-04:19 4520.72 01-APR-06:10 0.00 0.00
May 309919.65 05-MAY-13:39 84322.72 01-MAY-06:19 0.00 01-MAY-00:10 4520.72 01-MAY-06:10 0.00 0.00
June 356849.10 28-JUN-12:09 84322.72 01-JUN-06:49 0.00 01-JUN-00:10 4520.72 01-JUN-06:10 0.00 0.00
July 405531.57 21-JUL-12:09 84322.72 01-JUL-06:19 0.00 01-JUL-00:10 4520.72 01-JUL-06:10 0.00 0.00
August 425649.67 10-AUG-12:09 84322.72 01-AUG-06:19 1231.83 20-AUG-14:09 4520.72 01-AUG-06:10 0.00 0.00
September 319860.91 09-SEP-15:00 84322.72 01-SEP-06:19 0.00 01-SEP-00:10 4520.72 01-SEP-06:10 0.00 0.00
October 365871.49 06-OCT-14:09 84322.72 02-OCT-09:30 100000.00 27-OCT-04:19 4520.72 02-OCT-08:50 0.00 0.00
November 375816.65 07-NOV-13:09 84322.72 01-NOV-06:19 100000.00 09-NOV-05:19 4520.72 01-NOV-06:10 0.00 0.00
December 393751.88 14-DEC-12:30 84322.72 08-DEC-14:30 100000.00 06-DEC-05:30 4520.72 02-DEC-13:39 0.00 0.00
                     
Annual Sum or Average                 0.00 0.00
Minimum of Months 290924.89   84322.72   0.00   4520.72   0.00 0.00
Maximum of Months 425649.67   84322.72   100000.00   4520.72   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1259731.04 18-JAN-16:30 214098.33 423497.50 0.00 82829.38 136396.65 58527.07 0.00 255538.68 84322.72
February 1427285.41 27-FEB-16:49 212815.01 541788.89 0.00 82829.33 156931.80 58688.53 0.00 285388.40 84322.72
March 1542761.15 07-MAR-09:50 212815.01 660080.29 0.00 82829.33 94191.18 49019.55 0.00 354982.34 84322.72
April 1751633.97 18-APR-15:09 212815.01 778371.69 0.00 82829.33 137289.66 47618.53 0.00 349834.66 47637.57
May 1397081.72 16-MAY-15:50 212815.01 423497.50 0.00 82829.33 262229.47 58529.69 0.00 268337.28 84322.72
June 1510537.07 07-JUN-14:30 212815.01 541788.89 0.00 37438.14 262229.47 58401.03 0.00 309021.09 84322.72
July 1616609.33 18-JUL-15:30 212815.01 660080.29 0.00 82829.33 132441.48 48771.99 0.00 390827.80 84322.72
August 1767684.12 03-AUG-15:30 212815.01 778371.69 0.00 82829.33 139498.75 48900.65 0.00 416425.25 84322.72
September 1286546.95 01-SEP-15:09 212815.01 423497.50 0.00 82829.33 132957.54 48681.56 0.00 296922.57 84322.72
October 1456628.64 06-OCT-15:09 212815.01 541788.89 0.00 82829.33 131293.69 49024.55 0.00 350033.72 84322.72
November 1572541.15 02-NOV-15:09 212815.01 660080.29 0.00 82829.33 126415.14 48421.04 0.00 353136.90 84322.72
December 1706180.64 15-DEC-16:19 214379.53 778371.69 0.00 82830.02 119079.07 48154.82 0.00 374522.07 84322.72
                       
Annual Sum or Average                      
Minimum of Months 1259731.04   212815.01 423497.50 0.00 37438.14 94191.18 47618.53 0.00 255538.68 47637.57
Maximum of Months 1767684.12   214379.53 778371.69 0.00 82830.02 262229.47 58688.53 0.00 416425.25 84322.72



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 396853.32 10-JAN-06:10 0.00 74962.80 23-JAN-12:20 0.00
February 0.00 0.00 481266.71 06-FEB-06:10 0.00 74774.60 07-FEB-12:20 0.00
March 0.00 0.00 318793.19 09-MAR-07:10 0.00 73497.42 08-MAR-12:00 0.00
April 0.00 0.00 130489.52 18-APR-14:50 0.00 71227.56 04-APR-11:00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 68041.12 03-MAY-11:39 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 64080.80 06-JUN-11:50 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 61746.78 06-JUL-11:20 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 62301.44 21-AUG-11:30 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 65037.24 19-SEP-11:00 0.00
October 0.00 0.00 3088.02 28-OCT-06:49 0.00 69080.32 25-OCT-11:30 0.00
November 0.00 0.00 74192.22 16-NOV-06:10 0.00 72050.19 21-NOV-12:39 0.00
December 0.00 0.00 448288.57 21-DEC-07:10 0.00 74404.23 28-DEC-12:20 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 61746.78   0.00
Maximum of Months 0.00 0.00 481266.71   0.00 74962.80   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 3.67 26.76 0.17 26.79
February 0.00 0.00 0.00 0.00 3.67 27.13 0.00 27.13
March 0.00 0.00 0.00 0.00 0.50 25.76 0.00 25.76
April 0.00 0.00 0.00 0.00 0.67 25.71 0.00 25.71
May 0.00 0.00 0.00 0.00 3.00 26.21 0.00 26.21
June 0.00 0.00 0.00 0.00 2.17 25.84 0.00 25.84
July 0.00 0.00 0.00 0.00 5.33 26.27 0.00 26.27
August 0.00 0.00 0.00 0.00 8.00 26.41 0.17 26.43
September 0.00 0.00 0.00 0.00 9.50 26.74 1.00 26.76
October 0.00 0.00 0.00 0.00 11.67 27.01 0.17 26.99
November 0.00 0.00 0.00 0.00 12.83 27.20 1.00 27.21
December 0.00 0.00 0.00 0.00 10.17 27.21 0.83 27.22
                 
Annual Sum or Average 0.00   0.00   71.17 26.82 3.33 26.83
Minimum of Months 0.00 0.00 0.00 0.00 0.50 25.71 0.00 25.71
Maximum of Months 0.00 0.00 0.00 0.00 12.83 27.21 1.00 27.22



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
December 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
                 
Annual Sum or Average 0.00   0.00   0.50 25.57 0.00 25.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.33 18.95 0.00 18.95 0.00 18.95 0.00 18.95
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 18.95 0.00 18.95 0.00 18.95 0.00 18.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 18.95 0.00 18.95 0.00 18.95 0.00 18.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.50 27.33 0.50 27.33
July 0.00 0.00 0.00 0.00 1.67 26.16 0.50 26.43
August 0.00 0.00 0.00 0.00 2.00 26.35 0.83 26.63
September 0.00 0.00 0.00 0.00 0.33 25.58 0.00 25.58
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   4.50 26.33 1.83 26.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.00 27.33 0.83 27.33



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.17 27.52 1.17 27.52
February 0.00 0.00 0.00 0.00 0.67 27.52 0.67 27.52
March 0.00 0.00 0.00 0.00 1.67 27.62 1.67 27.62
April 0.00 0.00 0.00 0.00 2.17 27.74 2.17 27.74
May 0.00 0.00 0.00 0.00 8.50 27.82 8.50 27.82
June 0.00 0.00 0.00 0.00 5.50 27.60 5.50 27.60
July 0.00 0.00 0.00 0.00 9.00 27.61 8.50 27.65
August 0.00 0.00 0.00 0.00 6.00 27.41 5.67 27.46
September 0.00 0.00 0.00 0.00 9.67 27.65 9.33 27.69
October 0.00 0.00 0.00 0.00 5.50 27.70 5.50 27.70
November 0.00 0.00 0.00 0.00 1.67 27.49 1.67 27.49
December 0.00 0.00 0.00 0.00 0.33 27.45 0.33 27.45
                 
Annual Sum or Average 0.00   0.00   51.83 27.64 50.67 27.66
Minimum of Months 0.00 0.00 0.00 0.00 0.33 27.41 0.33 27.45
Maximum of Months 0.00 0.00 0.00 0.00 9.67 27.82 9.33 27.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 8.83 27.45 8.83 27.45
February 0.00 0.00 0.00 0.00 5.50 27.37 5.50 27.37
March 0.00 0.00 0.00 0.00 3.00 27.61 3.00 27.61
April 0.00 0.00 0.00 0.00 0.67 27.42 0.67 27.42
May 0.00 0.00 0.00 0.00 0.17 27.37 0.17 27.37
June 0.00 0.00 0.00 0.00 0.67 27.29 0.67 27.29
July 0.00 0.00 0.00 0.00 2.50 26.78 1.67 27.00
August 0.00 0.00 0.00 0.00 6.17 27.13 4.83 27.28
September 0.00 0.00 0.00 0.00 9.00 27.63 8.00 27.70
October 0.00 0.00 0.00 0.00 12.00 27.87 11.00 27.90
November 0.00 0.00 0.00 0.00 16.67 26.74 16.67 26.74
December 0.00 0.00 0.00 0.00 13.00 26.87 13.00 26.87
                 
Annual Sum or Average 0.00   0.00   78.17 27.24 74.00 27.27
Minimum of Months 0.00 0.00 0.00 0.00 0.17 26.74 0.17 26.74
Maximum of Months 0.00 0.00 0.00 0.00 16.67 27.87 16.67 27.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 3.33 27.75 3.33 27.75
February 0.00 0.00 0.00 0.00 4.17 27.62 3.50 27.75
March 0.00 0.00 0.00 0.00 8.00 27.40 4.17 27.60
April 0.00 0.00 0.00 0.00 21.17 27.40 7.83 27.58
May 0.00 0.00 0.00 0.00 16.33 27.02 6.33 27.26
June 0.00 0.00 0.00 0.00 29.50 27.11 10.33 27.29
July 0.00 0.00 0.00 0.00 45.50 27.35 16.00 27.50
August 0.00 0.00 0.00 0.00 57.17 27.45 15.67 27.54
September 0.00 0.00 0.00 0.00 18.17 27.29 7.83 27.51
October 0.00 0.00 0.00 0.00 22.67 27.33 10.67 27.53
November 0.00 0.00 0.00 0.00 11.83 27.43 8.00 27.62
December 0.00 0.00 0.00 0.00 11.33 27.57 8.00 27.71
                 
Annual Sum or Average 0.00   0.00   249.17 27.35 101.67 27.51
Minimum of Months 0.00 0.00 0.00 0.00 3.33 27.02 3.33 27.26
Maximum of Months 0.00 0.00 0.00 0.00 57.17 27.75 16.00 27.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 19.34 0.00 19.34 0.00 19.34 0.00 19.34
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 27.30 0.33 27.30
August 0.00 0.00 0.00 0.00 0.17 27.29 0.17 27.29
September 0.00 0.00 0.00 0.00 0.67 27.31 0.67 27.31
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 19.34 0.00 19.34 1.17 26.31 1.17 26.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.34 0.00 19.34 0.67 27.31 0.67 27.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 27.26 0.17 27.26
February 0.00 0.00 0.00 0.00 0.33 27.46 0.33 27.46
March 0.00 0.00 0.00 0.00 1.33 27.59 1.33 27.59
April 0.00 0.00 0.00 0.00 2.67 27.76 2.67 27.76
May 0.00 0.00 0.00 0.00 9.67 27.91 9.17 27.93
June 0.00 0.00 0.00 0.00 7.83 27.72 7.50 27.73
July 0.00 0.00 0.00 0.00 14.00 27.71 13.00 27.73
August 0.00 0.00 0.00 0.00 7.83 27.66 7.50 27.67
September 0.00 0.00 0.00 0.00 10.50 27.81 10.00 27.82
October 0.00 0.00 0.00 0.00 7.33 27.71 7.33 27.71
November 0.00 0.00 0.00 0.00 0.83 27.60 0.83 27.60
December 0.00 0.00 0.00 0.00 0.17 27.36 0.17 27.36
                 
Annual Sum or Average 0.00   0.00   62.67 27.75 60.00 27.76
Minimum of Months 0.00 0.00 0.00 0.00 0.17 27.26 0.17 27.26
Maximum of Months 0.00 0.00 0.00 0.00 14.00 27.91 13.00 27.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 11.33 26.90 11.33 26.90
February 0.00 0.00 0.00 0.00 6.67 26.66 6.67 26.66
March 0.00 0.00 0.00 0.00 2.33 27.60 2.33 27.60
April 0.00 0.00 0.00 0.00 0.83 27.36 0.83 27.36
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 27.35 0.33 27.35
August 0.00 0.00 0.00 0.00 3.50 27.39 3.50 27.39
September 0.00 0.00 0.00 0.00 8.00 27.80 7.33 27.81
October 0.00 0.00 0.00 0.00 16.17 27.01 15.17 27.00
November 0.00 0.00 0.00 0.00 22.00 26.33 21.83 26.33
December 0.00 0.00 0.00 0.00 15.83 26.36 15.83 26.36
                 
Annual Sum or Average 0.00   0.00   87.00 26.79 85.17 26.78
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 22.00 27.80 21.83 27.81



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.17 27.57 1.17 27.57
February 0.00 0.00 0.00 0.00 0.83 28.07 0.83 28.07
March 0.00 0.00 0.00 0.00 2.00 27.72 1.83 27.73
April 0.00 0.00 0.00 0.00 4.83 27.91 3.00 27.93
May 0.00 0.00 0.00 0.00 7.17 27.79 3.50 27.92
June 0.00 0.00 0.00 0.00 9.00 27.55 4.00 27.72
July 0.00 0.00 0.00 0.00 15.33 27.38 7.83 27.53
August 0.00 0.00 0.00 0.00 8.50 27.33 4.50 27.50
September 0.00 0.00 0.00 0.00 9.00 27.85 5.33 27.96
October 0.00 0.00 0.00 0.00 7.50 27.85 5.17 27.93
November 0.00 0.00 0.00 0.00 2.50 27.64 2.33 27.64
December 0.00 0.00 0.00 0.00 1.17 27.66 1.17 27.66
                 
Annual Sum or Average 0.00   0.00   69.00 27.62 40.67 27.74
Minimum of Months 0.00 0.00 0.00 0.00 0.83 27.33 0.83 27.50
Maximum of Months 0.00 0.00 0.00 0.00 15.33 28.07 7.83 28.07



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 19.00 0.00 19.00 0.00 19.00 0.00 19.00
February 3.67 17.22 1.33 17.12 0.00 17.12 0.00 17.12
March 0.67 19.19 0.00 19.19 0.00 19.19 0.00 19.19
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 3.83 27.36 2.67 27.39
June 0.00 0.00 0.00 0.00 3.83 27.50 2.50 27.50
July 0.00 0.00 0.00 0.00 8.17 27.48 6.00 27.49
August 0.00 0.00 0.00 0.00 4.17 27.45 3.67 27.46
September 0.00 0.00 0.00 0.00 2.50 27.53 2.00 27.54
October 0.00 0.00 0.00 0.00 2.17 27.45 2.17 27.45
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.17 19.00 0.00 19.00 0.00 19.00 0.00 19.00
                 
Annual Sum or Average 7.67 18.17 1.33 17.97 24.67 24.92 19.00 25.85
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.67 19.19 1.33 19.19 8.17 27.53 6.00 27.54



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.83 19.07 0.00 19.07 0.00 19.07 0.00 19.07
February 1.67 17.32 0.33 16.92 0.00 16.92 0.00 16.92
March 0.67 19.28 0.00 19.28 1.17 24.54 1.17 25.71
April 0.00 0.00 0.00 0.00 2.67 27.80 2.67 27.80
May 0.00 0.00 0.00 0.00 11.33 27.98 9.50 28.03
June 0.00 0.00 0.00 0.00 10.00 27.82 8.50 27.85
July 0.00 0.00 0.00 0.00 17.00 27.82 14.00 27.87
August 0.00 0.00 0.00 0.00 10.17 27.72 8.50 27.77
September 0.00 0.00 0.00 0.00 13.33 27.89 12.00 27.91
October 0.00 0.00 0.00 0.00 9.50 27.71 9.17 27.72
November 0.00 0.00 0.00 0.00 0.67 27.49 0.67 27.49
December 1.00 19.00 0.00 19.00 0.00 19.00 0.00 19.00
                 
Annual Sum or Average 5.17 18.52 0.33 18.30 75.83 27.18 66.17 27.50
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.92 0.00 16.92
Maximum of Months 1.83 19.28 0.33 19.28 17.00 27.98 14.00 28.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 19.18 0.00 19.18 7.50 26.20 7.50 26.64
February 0.50 18.62 0.00 18.62 3.00 26.22 3.00 26.81
March 0.50 19.38 0.00 19.38 2.17 26.13 2.17 26.83
April 0.00 0.00 0.00 0.00 1.00 27.50 1.00 27.50
May 0.00 0.00 0.00 0.00 4.67 27.43 3.67 27.47
June 0.00 0.00 0.00 0.00 3.50 27.44 2.67 27.45
July 0.00 0.00 0.00 0.00 8.17 27.48 7.00 27.48
August 0.00 0.00 0.00 0.00 6.67 27.59 5.67 27.60
September 0.00 0.00 0.00 0.00 10.67 27.90 8.83 27.94
October 0.00 0.00 0.00 0.00 12.17 28.10 10.33 28.14
November 0.00 0.00 0.00 0.00 15.33 26.67 15.33 26.67
December 0.50 18.91 0.00 18.91 8.17 27.13 8.00 27.38
                 
Annual Sum or Average 2.50 19.05 0.00 19.05 83.00 27.22 75.17 27.34
Minimum of Months 0.00 0.00 0.00 0.00 1.00 26.13 1.00 26.64
Maximum of Months 1.00 19.38 0.00 19.38 15.33 28.10 15.33 28.14



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.17 19.18 0.00 19.18 1.17 23.37 1.17 24.77
February 0.50 18.82 0.00 18.82 0.83 24.61 0.83 25.94
March 0.00 0.00 0.00 0.00 2.00 27.82 1.67 27.84
April 0.00 0.00 0.00 0.00 5.17 27.95 3.17 27.98
May 0.00 0.00 0.00 0.00 9.83 27.80 5.50 27.89
June 0.00 0.00 0.00 0.00 12.17 27.61 6.00 27.75
July 0.00 0.00 0.00 0.00 19.83 27.51 10.00 27.65
August 0.00 0.00 0.00 0.00 11.83 27.34 6.00 27.53
September 0.00 0.00 0.00 0.00 12.50 27.91 7.17 28.00
October 0.00 0.00 0.00 0.00 8.83 27.91 6.00 27.99
November 0.00 0.00 0.00 0.00 1.83 27.75 1.83 27.75
December 0.50 18.95 0.00 18.95 1.00 24.84 1.00 26.02
                 
Annual Sum or Average 2.17 19.05 0.00 19.05 87.00 27.47 50.33 27.66
Minimum of Months 0.00 0.00 0.00 0.00 0.83 23.37 0.83 24.77
Maximum of Months 1.17 19.18 0.00 19.18 19.83 27.95 10.00 28.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.17 27.62 1.17 27.62
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 40.33 27.75 40.33 27.75
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   41.50 27.75 41.50 27.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 40.33 27.75 40.33 27.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.17 27.64 1.17 27.64
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 34.00 27.73 34.00 27.73
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   35.17 27.73 35.17 27.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 34.00 27.73 34.00 27.73



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 27.60 0.50 27.60
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 20.50 27.71 20.50 27.71
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   21.00 27.70 21.00 27.70
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 20.50 27.71 20.50 27.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 101.17 28.21 99.83 28.21
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 498.33 28.88 417.00 28.96
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 40.83 28.03 40.83 28.03
                 
Annual Sum or Average 0.00   0.00   640.33 28.72 557.67 28.77
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 498.33 28.88 417.00 28.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 60.00 24.53 237.50 24.99 39.67 24.97
February 86.50 24.53 309.33 24.68 64.83 24.68
March 109.50 24.54 309.67 24.62 83.50 24.63
April 206.00 24.62 430.00 24.57 205.83 24.58
May 356.83 24.70 508.00 24.58 356.83 24.62
June 296.50 24.71 496.00 24.54 296.50 24.58
July 261.00 25.13 497.00 24.78 261.00 24.87
August 204.50 25.18 514.00 24.68 204.50 24.79
September 230.67 25.18 485.00 24.76 230.67 24.86
October 171.00 25.44 452.67 24.89 171.00 25.01
November 76.67 25.35 381.00 24.89 76.67 24.95
December 64.00 25.04 310.50 24.97 59.83 24.99
             
Annual Sum or Average 2123.17 24.92 4930.67 24.72 2050.83 24.77
Minimum of Months 60.00 24.53 237.50 24.54 39.67 24.58
Maximum of Months 356.83 25.44 514.00 24.99 356.83 25.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 91.67 23.69 201.17 24.28 0.00 24.28
February 38.83 23.77 286.50 24.30 0.00 24.30
March 19.67 23.76 314.00 24.35 0.00 24.35
April 0.00 0.00 431.83 24.22 0.00 24.22
May 0.00 0.00 493.33 24.24 0.00 24.24
June 0.00 0.00 490.50 24.15 0.00 24.15
July 0.00 0.00 495.50 24.15 0.00 24.15
August 0.00 0.00 514.00 24.12 0.00 24.12
September 0.00 0.00 476.67 24.24 0.00 24.24
October 0.00 0.00 449.67 24.31 0.00 24.31
November 0.00 0.00 380.17 24.41 0.00 24.41
December 9.50 23.85 309.83 24.45 0.00 24.45
             
Annual Sum or Average 159.67 23.73 4843.17 24.25 0.00 24.25
Minimum of Months 0.00 0.00 201.17 24.12 0.00 24.12
Maximum of Months 91.67 23.85 514.00 24.45 0.00 24.45



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 294.17 23.26 86.17 23.47 0.00 23.47
February 203.50 23.28 138.67 23.65 0.00 23.65
March 182.67 23.32 161.50 23.76 0.00 23.76
April 45.67 23.41 260.17 24.20 0.00 24.20
May 7.00 23.28 395.67 24.20 0.00 24.20
June 5.67 23.28 371.67 24.18 0.00 24.18
July 6.67 23.29 358.00 24.20 0.00 24.20
August 3.50 23.30 409.50 24.20 0.00 24.20
September 17.00 23.30 334.17 24.15 0.00 24.15
October 27.83 23.39 352.67 24.21 0.00 24.21
November 113.33 23.39 208.67 23.96 0.00 23.96
December 206.67 23.22 129.00 23.64 0.00 23.64
             
Annual Sum or Average 1113.67 23.29 3205.83 23.99 0.00 23.99
Minimum of Months 3.50 23.22 86.17 23.47 0.00 23.47
Maximum of Months 294.17 23.41 409.50 24.21 0.00 24.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 395.50 22.22 76.67 22.44 12.50 22.39
February 291.67 22.36 116.83 22.67 17.17 22.54
March 270.17 22.73 155.83 23.21 6.50 23.16
April 82.67 23.26 272.50 24.04 0.00 24.04
May 0.33 23.31 452.83 24.24 0.00 24.24
June 0.00 0.00 451.50 24.23 0.00 24.23
July 0.00 0.00 448.67 24.26 0.00 24.26
August 0.00 0.00 464.33 24.24 0.00 24.24
September 0.00 0.00 383.67 24.24 0.00 24.24
October 52.17 23.01 359.83 24.14 0.00 24.14
November 217.67 22.95 152.17 23.44 0.00 23.44
December 332.00 22.44 95.50 22.76 8.17 22.72
             
Annual Sum or Average 1642.17 22.55 3430.33 23.65 44.33 23.62
Minimum of Months 0.00 0.00 76.67 22.44 0.00 22.39
Maximum of Months 395.50 23.31 464.33 24.26 17.17 24.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 330.17 22.67 109.50 23.07 0.00 23.07
February 204.83 22.83 154.50 23.39 4.00 23.36
March 189.67 23.12 209.83 23.72 0.00 23.72
April 26.83 23.55 367.00 24.15 0.00 24.15
May 8.50 26.07 508.00 24.42 8.50 24.44
June 2.83 26.89 496.00 24.35 2.83 24.36
July 13.67 26.76 496.50 24.48 13.67 24.54
August 10.83 26.76 514.00 24.34 10.83 24.38
September 11.83 26.06 483.17 24.43 11.83 24.47
October 34.83 23.85 426.50 24.34 4.17 24.36
November 122.50 23.48 250.00 23.99 0.00 23.99
December 210.83 23.05 176.83 23.57 0.00 23.57
             
Annual Sum or Average 1167.33 23.14 4191.83 24.06 55.83 24.08
Minimum of Months 2.83 22.67 109.50 23.07 0.00 23.07
Maximum of Months 330.17 26.89 514.00 24.48 13.67 24.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 260.67 22.95 144.83 23.52 5.17 23.56
February 166.33 23.02 190.83 23.72 3.83 23.72
March 168.17 23.12 238.67 23.88 7.17 23.93
April 47.17 23.94 366.00 24.25 7.33 24.29
May 43.00 26.77 506.67 24.65 43.00 24.80
June 23.33 26.88 494.17 24.48 23.33 24.59
July 45.17 26.84 494.17 24.66 45.17 24.83
August 25.00 26.81 508.50 24.41 25.00 24.52
September 48.33 26.77 481.17 24.68 48.33 24.86
October 54.83 25.39 430.83 24.57 32.50 24.70
November 93.83 23.59 280.33 24.22 7.00 24.27
December 199.83 22.91 173.50 23.59 2.17 23.61
             
Annual Sum or Average 1175.67 23.79 4309.67 24.27 250.00 24.38
Minimum of Months 23.33 22.91 144.83 23.52 2.17 23.56
Maximum of Months 260.67 26.88 508.50 24.68 48.33 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 189.50 23.41 232.33 24.07 26.83 24.25
February 118.83 23.39 267.67 24.11 19.17 24.18
March 151.67 23.16 269.83 23.95 10.83 24.02
April 32.67 23.83 372.50 24.26 3.67 24.28
May 13.67 26.29 507.83 24.44 13.67 24.49
June 3.17 26.91 494.83 24.34 3.17 24.35
July 18.67 26.76 495.83 24.50 18.67 24.58
August 22.17 26.80 513.83 24.41 22.17 24.51
September 44.67 26.70 484.67 24.66 44.67 24.82
October 61.33 26.08 454.17 24.74 45.83 24.92
November 76.33 25.15 382.67 24.69 37.00 24.86
December 148.33 23.85 295.00 24.37 31.50 24.55
             
Annual Sum or Average 881.00 24.17 4771.17 24.40 277.17 24.51
Minimum of Months 3.17 23.16 232.33 23.95 3.17 24.02
Maximum of Months 189.50 26.91 513.83 24.74 45.83 24.92



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 185.33 23.61 222.83 24.14 13.33 24.23
February 78.67 24.12 319.33 24.45 13.50 24.53
March 51.50 24.94 369.50 24.62 18.83 24.72
April 45.33 26.96 468.17 24.84 45.33 25.01
May 43.67 26.86 508.00 24.75 43.67 24.90
June 49.00 26.94 496.00 24.75 49.00 24.93
July 83.83 26.92 497.00 25.00 83.83 25.24
August 80.17 26.91 514.00 24.87 80.17 25.11
September 57.17 26.87 485.00 24.83 57.17 25.02
October 53.67 26.78 472.50 24.88 50.50 25.06
November 33.33 26.77 425.00 24.81 30.67 24.94
December 52.50 25.90 355.83 24.95 34.33 25.11
             
Annual Sum or Average 814.17 25.69 5133.17 24.76 520.33 24.93
Minimum of Months 33.33 23.61 222.83 24.14 13.33 24.23
Maximum of Months 185.33 26.96 514.00 25.00 83.83 25.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 436.67 21.72 93.00 21.79 53.50 21.70
February 347.33 22.00 98.33 22.10 36.83 21.94
March 334.00 22.33 116.50 22.64 17.33 22.56
April 151.00 23.27 252.00 23.87 10.83 23.91
May 29.00 25.63 508.00 24.44 29.00 24.50
June 12.83 26.18 493.67 24.41 12.83 24.46
July 42.00 26.20 494.33 24.61 42.00 24.72
August 29.00 25.86 510.17 24.43 29.00 24.50
September 39.67 25.32 460.83 24.42 39.67 24.48
October 108.83 23.76 382.33 24.22 33.83 24.30
November 285.50 22.58 126.00 23.05 2.17 23.05
December 387.00 21.99 91.00 22.22 26.67 22.17
             
Annual Sum or Average 2202.83 22.50 3626.17 23.55 333.67 23.56
Minimum of Months 12.83 21.72 91.00 21.79 2.17 21.70
Maximum of Months 436.67 26.20 510.17 24.61 53.50 24.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 311.67 22.30 88.00 22.63 22.33 22.59
February 223.17 22.43 112.00 22.86 18.67 22.76
March 200.33 22.60 162.17 23.36 14.50 23.35
April 80.00 24.01 283.33 24.39 22.67 24.50
May 62.33 26.58 430.00 24.83 62.33 25.03
June 43.67 26.76 416.50 24.74 43.67 24.92
July 69.83 26.79 421.00 24.99 69.83 25.21
August 51.00 26.54 432.00 24.72 51.00 24.90
September 65.33 26.44 404.17 24.82 65.33 25.02
October 92.67 24.92 345.50 24.67 51.33 24.86
November 166.83 23.07 181.00 23.81 7.33 23.86
December 272.50 22.39 111.33 22.83 21.83 22.80
             
Annual Sum or Average 1639.33 23.45 3387.00 24.15 450.83 24.28
Minimum of Months 43.67 22.30 88.00 22.63 7.33 22.59
Maximum of Months 311.67 26.79 432.00 24.99 69.83 25.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 229.67 23.00 222.00 23.74 37.67 23.88
February 168.83 22.90 233.00 23.74 23.17 23.77
March 209.50 22.65 221.33 23.46 17.33 23.47
April 99.00 23.51 311.67 24.15 14.50 24.22
May 32.17 25.69 508.00 24.45 32.17 24.52
June 12.17 26.02 492.17 24.38 12.17 24.42
July 44.50 26.15 490.50 24.60 44.50 24.72
August 42.17 26.20 512.00 24.52 42.17 24.64
September 64.83 26.23 478.00 24.66 64.83 24.83
October 89.17 25.59 444.33 24.76 62.33 24.96
November 124.83 24.28 332.67 24.53 39.67 24.72
December 199.67 23.20 256.67 24.00 40.17 24.16
             
Annual Sum or Average 1316.50 23.76 4502.33 24.29 430.67 24.40
Minimum of Months 12.17 22.65 221.33 23.46 12.17 23.47
Maximum of Months 229.67 26.23 512.00 24.76 64.83 24.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 319.33 22.23 135.33 22.74 24.00 22.72
February 215.33 22.35 188.00 23.09 19.00 22.99
March 213.67 22.69 233.33 23.47 17.00 23.48
April 69.50 24.53 380.33 24.45 26.00 24.57
May 47.50 26.36 508.00 24.64 47.50 24.78
June 35.00 26.79 495.50 24.63 35.00 24.76
July 70.17 26.69 497.00 24.86 70.17 25.06
August 47.17 26.60 514.00 24.65 47.17 24.80
September 62.83 26.32 483.17 24.70 62.83 24.86
October 83.83 25.11 434.00 24.60 51.00 24.76
November 170.17 23.20 252.50 23.89 11.83 23.96
December 263.83 22.44 189.17 23.20 15.17 23.21
             
Annual Sum or Average 1598.33 23.40 4310.33 24.14 426.67 24.26
Minimum of Months 35.00 22.23 135.33 22.74 11.83 22.72
Maximum of Months 319.33 26.79 514.00 24.86 70.17 25.06



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 447.17 21.27 183.50 21.22 146.50 21.06
February 370.00 21.61 145.67 21.59 87.67 21.35
March 357.83 21.96 159.17 22.20 56.50 22.02
April 172.33 22.95 246.67 23.70 10.67 23.75
May 48.17 25.96 506.50 24.53 48.17 24.65
June 31.67 26.28 491.83 24.51 30.33 24.62
July 61.67 26.41 491.00 24.73 61.67 24.90
August 48.00 26.08 508.00 24.52 48.00 24.65
September 66.83 25.60 452.83 24.54 65.00 24.67
October 129.17 23.55 377.33 24.16 43.00 24.26
November 321.17 22.15 137.00 22.58 24.50 22.51
December 401.67 21.53 168.17 21.65 105.50 21.49
             
Annual Sum or Average 2455.67 22.31 3867.67 23.30 727.50 23.24
Minimum of Months 31.67 21.27 137.00 21.22 10.67 21.06
Maximum of Months 447.17 26.41 508.00 24.73 146.50 24.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 400.50 21.86 155.17 21.99 81.00 21.80
February 287.33 22.02 148.17 22.30 44.00 22.07
March 248.00 22.22 227.33 22.94 45.17 22.81
April 100.67 23.55 335.67 24.20 22.17 24.30
May 67.00 26.55 507.00 24.74 67.00 24.93
June 50.33 26.66 493.00 24.67 49.17 24.84
July 70.50 26.83 494.33 24.88 70.50 25.10
August 55.33 26.47 511.50 24.64 55.33 24.80
September 74.83 26.28 469.33 24.73 74.00 24.92
October 121.83 24.50 406.67 24.51 59.67 24.70
November 223.00 22.74 205.50 23.45 14.50 23.45
December 350.17 21.96 160.33 22.33 55.50 22.20
             
Annual Sum or Average 2049.50 23.01 4114.00 23.83 638.00 23.88
Minimum of Months 50.33 21.86 148.17 21.99 14.50 21.80
Maximum of Months 400.50 26.83 511.50 24.88 81.00 25.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 264.17 22.40 208.67 23.06 63.83 23.04
February 204.83 22.31 225.50 23.11 40.50 23.00
March 248.33 22.31 229.33 22.97 47.00 22.87
April 128.50 23.18 300.83 24.00 15.67 24.07
May 51.17 25.96 504.17 24.54 51.17 24.66
June 30.50 26.18 490.17 24.49 29.00 24.58
July 61.50 26.37 488.50 24.72 61.50 24.88
August 51.00 26.21 510.50 24.56 51.00 24.70
September 73.33 26.13 466.67 24.70 72.17 24.87
October 99.33 25.17 434.67 24.68 63.83 24.89
November 163.67 23.59 301.67 24.23 38.00 24.40
December 234.33 22.56 253.83 23.41 57.67 23.42
             
Annual Sum or Average 1610.67 23.38 4414.50 24.09 591.33 24.17
Minimum of Months 30.50 22.31 208.67 22.97 15.67 22.87
Maximum of Months 264.17 26.37 510.50 24.72 72.17 24.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 355.50 21.82 164.50 22.13 75.00 22.00
February 255.00 21.97 190.67 22.51 50.33 22.31
March 250.50 22.30 234.33 23.01 41.33 22.91
April 101.33 23.93 355.00 24.32 26.67 24.45
May 58.33 26.36 508.00 24.68 58.33 24.84
June 45.33 26.77 493.67 24.68 45.33 24.84
July 76.83 26.72 496.50 24.90 76.83 25.11
August 54.33 26.59 514.00 24.68 54.33 24.85
September 73.33 26.25 480.50 24.72 73.33 24.90
October 99.17 24.71 425.17 24.54 55.17 24.71
November 212.17 22.71 224.50 23.54 15.00 23.60
December 298.00 21.98 199.67 22.63 50.00 22.53
             
Annual Sum or Average 1879.83 23.07 4286.50 23.92 621.67 23.98
Minimum of Months 45.33 21.82 164.50 22.13 15.00 22.00
Maximum of Months 355.50 26.77 514.00 24.90 76.83 25.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.17 27.00 502.00 27.00 6.17 27.00
February 19.17 27.00 454.00 27.00 19.17 27.00
March 53.83 27.00 514.00 27.00 53.83 27.00
April 242.67 27.01 485.00 27.01 242.67 27.01
May 16.00 27.00 508.00 27.00 16.00 27.00
June 94.33 27.00 496.00 27.00 94.33 27.00
July 253.67 27.00 497.00 27.00 253.67 27.00
August 466.50 27.13 514.00 27.13 466.50 27.13
September 40.83 27.00 485.00 27.00 40.83 27.00
October 92.67 27.00 502.00 27.00 92.67 27.00
November 92.67 27.00 489.00 27.00 92.67 27.00
December 146.50 27.00 497.00 27.00 146.50 27.00
             
Annual Sum or Average 1525.00 27.04 5943.00 27.02 1525.00 27.02
Minimum of Months 6.17 27.00 454.00 27.00 6.17 27.00
Maximum of Months 466.50 27.13 514.00 27.13 466.50 27.13



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 1.17 27.00 448.17 27.00 1.17 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 10.33 27.17 485.00 27.01 10.33 27.01
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 2.83 27.00 497.00 27.00 2.83 27.00
August 104.67 27.48 514.00 27.17 104.67 27.21
September 0.00 0.00 485.00 27.00 0.00 27.00
October 3.17 27.00 502.00 27.00 3.17 27.00
November 2.33 27.00 489.00 27.00 2.33 27.00
December 6.33 27.00 497.00 27.00 6.33 27.00
             
Annual Sum or Average 130.83 27.39 5937.17 27.02 130.83 27.03
Minimum of Months 0.00 0.00 448.17 27.00 0.00 27.00
Maximum of Months 104.67 27.48 514.00 27.17 104.67 27.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 9.83 26.07 471.00 26.98 0.50 26.98
February 8.67 27.01 434.00 27.00 2.00 27.00
March 1.83 27.00 506.50 27.00 1.83 27.00
April 44.00 27.03 485.00 27.01 44.00 27.01
May 24.33 27.00 508.00 27.00 24.33 27.00
June 45.50 27.00 496.00 27.00 45.50 27.00
July 78.67 27.00 497.00 27.00 78.67 27.00
August 134.17 27.26 514.00 27.11 134.17 27.14
September 27.00 27.00 485.00 27.00 27.00 27.00
October 36.00 27.00 502.00 27.00 36.00 27.00
November 8.50 27.00 489.00 27.00 8.50 27.00
December 10.50 27.00 489.83 27.00 10.50 27.00
             
Annual Sum or Average 429.00 27.06 5877.33 27.01 413.00 27.02
Minimum of Months 1.83 26.07 434.00 26.98 0.50 26.98
Maximum of Months 134.17 27.26 514.00 27.11 134.17 27.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 27.00 502.00 27.00 502.00 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.28 485.00 27.28 485.00 27.28
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 28.69 514.00 28.69 514.00 28.69
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.11 497.00 27.11 497.00 27.11
             
Annual Sum or Average 5943.00 27.18 5943.00 27.18 5943.00 27.18
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 28.69 514.00 28.69 514.00 28.69



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00018 32.36893 0.88409 21.63936
February 454.00000 27.00091 33.55156 0.93789 23.70133
March 514.00000 27.00052 33.87159 0.97664 25.21948
April 485.00000 27.00390 36.56015 1.04780 28.20753
May 508.00000 27.00033 42.24153 0.34321 7.49244
June 496.00000 27.00221 40.64622 0.37735 8.00431
July 497.00000 27.00132 39.90007 0.41846 8.68680
August 514.00000 27.12196 39.20578 0.49998 10.38924
September 485.00000 27.00020 42.63720 0.34902 7.58312
October 502.00000 27.00172 38.47306 1.01130 26.64746
November 489.00000 27.00062 35.42502 1.00474 26.37125
December 497.00000 27.00019 33.46452 1.00710 26.49541
           
Annual Sum or Average 5943.00000 27.01155 37.38379 0.73617 18.31047
Minimum of Months 454.00000 27.00018 32.36893 0.34321 7.49244
Maximum of Months 514.00000 27.12196 42.63720 1.04780 28.20753



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00012 32.49384 0.80039 18.71733
February 454.00000 27.00087 33.58991 0.84191 20.18235
March 514.00000 27.00050 33.85138 0.87259 21.21439
April 485.00000 27.00416 36.52290 0.95188 24.19595
May 508.00000 27.00018 42.46832 0.29278 6.83355
June 496.00000 27.00214 40.72351 0.30620 6.99547
July 497.00000 27.00131 39.92526 0.32256 7.20407
August 514.00000 27.10774 39.21813 0.36825 7.98427
September 485.00000 27.00012 42.96648 0.28898 6.79501
October 502.00000 27.00166 38.53838 0.94988 24.13498
November 489.00000 27.00060 35.40683 0.90244 22.29082
December 497.00000 27.00015 33.42034 0.86931 21.11733
           
Annual Sum or Average 5943.00000 27.01029 37.44869 0.64525 15.58649
Minimum of Months 454.00000 27.00012 32.49384 0.28898 6.79501
Maximum of Months 514.00000 27.10774 42.96648 0.95188 24.19595



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.96686 32.62301 0.74319 17.09833
February 454.00000 27.00098 33.64486 0.80354 19.04785
March 514.00000 27.00052 33.88118 0.84671 20.41641
April 485.00000 27.00304 36.55093 0.94994 24.17522
May 508.00000 27.00028 42.37444 0.31289 7.12830
June 496.00000 27.00223 40.69982 0.33208 7.38401
July 497.00000 27.00138 39.93215 0.34936 7.62392
August 514.00000 27.07010 39.26239 0.38162 8.21377
September 485.00000 27.00013 42.89076 0.30436 7.03010
October 502.00000 27.00171 38.54424 0.95200 24.28902
November 489.00000 27.00063 35.44272 0.87652 21.40813
December 497.00000 27.00018 33.45549 0.82489 19.67490
           
Annual Sum or Average 5943.00000 27.00418 37.46327 0.63795 15.24388
Minimum of Months 454.00000 26.96686 32.62301 0.30436 7.03010
Maximum of Months 514.00000 27.07010 42.89076 0.95200 24.28902



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00035 36.93193 1.13592 32.29813
February 454.00000 27.00097 37.84910 1.28584 39.61440
March 514.00000 27.00246 34.45537 1.39377 45.20656
April 485.00000 27.28372 36.07889 1.59425 55.97330
May 508.00000 27.00390 40.24415 0.57008 11.84876
June 496.00000 27.00275 39.74790 0.77955 17.82271
July 497.00000 27.00132 39.49640 0.99155 25.77990
August 514.00000 28.69174 37.85336 1.67236 59.86151
September 485.00000 27.00438 40.29714 0.63071 13.39928
October 502.00000 27.00247 38.35249 1.33041 41.85873
November 489.00000 27.00404 35.43476 1.44102 47.72419
December 497.00000 27.10638 32.87081 1.56105 54.20463
           
Annual Sum or Average 5943.00000 27.18025 37.46230 1.19915 37.15481
Minimum of Months 454.00000 27.00035 32.87081 0.57008 11.84876
Maximum of Months 514.00000 28.69174 40.29714 1.67236 59.86151



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.53705 38.07010 0.48829 10.85882
February 454.00000 24.50698 46.39203 0.53690 11.81829
March 514.00000 24.40444 45.40916 0.50857 11.15356
April 485.00000 24.48871 57.18097 0.60947 13.48904
May 508.00000 24.49515 65.35943 -0.1810 6.90262
June 496.00000 24.43864 64.82716 -0.2001 6.78939
July 497.00000 24.59374 64.01922 -0.1498 6.98622
August 514.00000 24.48711 62.01886 -0.1777 6.93829
September 485.00000 24.56362 62.77603 -0.1559 7.05484
October 502.00000 24.61504 57.19235 0.66005 15.26550
November 489.00000 24.61814 47.77793 0.59157 13.23547
December 497.00000 24.60231 42.97553 0.54836 12.31493
           
Annual Sum or Average 5943.00000 24.52885 54.54779 0.25349 10.21063
Minimum of Months 454.00000 24.40444 38.07010 -0.2001 6.78939
Maximum of Months 514.00000 24.61814 65.35943 0.66005 15.26550



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.18576 37.94017 0.40852 8.92816
February 454.00000 24.25175 41.59807 0.45642 9.74542
March 514.00000 24.23358 40.86581 0.45639 9.65814
April 485.00000 24.19634 46.46173 0.49899 10.36034
May 508.00000 24.22261 49.54737 -0.3465 7.78779
June 496.00000 24.14604 49.53800 -0.3638 7.89596
July 497.00000 24.15155 49.28570 -0.3551 7.73274
August 514.00000 24.12325 49.21320 -0.3478 7.59887
September 485.00000 24.23500 49.38280 -0.3403 7.72093
October 502.00000 24.27274 46.90107 0.52011 10.87800
November 489.00000 24.32921 43.33415 0.50658 10.67332
December 497.00000 24.29698 40.06372 0.47130 9.98390
           
Annual Sum or Average 5943.00000 24.21984 45.36413 0.12706 9.07011
Minimum of Months 454.00000 24.12325 37.94017 -0.3638 7.59887
Maximum of Months 514.00000 24.32921 49.54737 0.52011 10.87800



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.59508 40.28252 0.24898 6.88770
February 454.00000 23.69300 43.83515 0.30240 7.55891
March 514.00000 23.80720 43.10839 0.33217 7.80028
April 485.00000 24.04967 47.83671 0.43533 9.20725
May 508.00000 24.09574 50.24619 -0.4075 8.77158
June 496.00000 24.06731 50.23392 -0.4160 8.88766
July 497.00000 24.06427 50.20721 -0.4192 8.97774
August 514.00000 24.10151 50.23465 -0.4042 8.69268
September 485.00000 24.03303 50.39834 -0.4293 9.15253
October 502.00000 24.11199 47.94513 0.46195 9.70973
November 489.00000 23.94141 45.42167 0.38941 8.48520
December 497.00000 23.72616 42.76803 0.30635 7.59923
           
Annual Sum or Average 5943.00000 23.94211 46.89126 0.03046 8.48019
Minimum of Months 454.00000 23.59508 40.28252 -0.4293 6.88770
Maximum of Months 514.00000 24.11199 50.39834 0.46195 9.70973



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.59801 42.56662 0.00216 6.99054
February 454.00000 22.94286 45.41407 0.11829 7.91607
March 514.00000 23.36419 44.30774 0.22189 7.67297
April 485.00000 23.98033 48.26894 0.42260 9.11101
May 508.00000 24.19101 49.76490 -0.3589 7.99984
June 496.00000 24.18756 49.61505 -0.3556 7.91575
July 497.00000 24.21293 49.54109 -0.3514 7.88139
August 514.00000 24.19658 49.74800 -0.3549 7.93572
September 485.00000 24.13445 50.05380 -0.3845 8.37282
October 502.00000 24.08104 48.03935 0.45922 9.95849
November 489.00000 23.54082 46.76853 0.28850 7.57488
December 497.00000 22.95811 44.78043 0.11432 7.21553
           
Annual Sum or Average 5943.00000 23.70392 47.41218 -0.0168 8.04346
Minimum of Months 454.00000 22.59801 42.56662 -0.3845 6.99054
Maximum of Months 514.00000 24.21293 50.05380 0.45922 9.95849



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.16613 39.81598 0.14134 7.11957
February 454.00000 23.52082 42.19113 0.25594 7.91820
March 514.00000 23.77203 41.24665 0.32122 8.23388
April 485.00000 24.11504 46.00550 0.47187 9.90789
May 508.00000 24.38917 49.33540 -0.2434 7.02495
June 496.00000 24.33381 48.38154 -0.2436 6.85110
July 497.00000 24.41978 48.47589 -0.2107 6.86117
August 514.00000 24.28473 48.57982 -0.2487 6.93050
September 485.00000 24.38707 49.77907 -0.2579 7.28304
October 502.00000 24.29101 47.21935 0.53399 11.56576
November 489.00000 23.97793 43.71565 0.39572 8.82562
December 497.00000 23.65878 41.31471 0.28560 7.77512
           
Annual Sum or Average 5943.00000 24.02930 45.52168 0.09801 8.02015
Minimum of Months 454.00000 23.16613 39.81598 -0.2579 6.85110
Maximum of Months 514.00000 24.41978 49.77907 0.53399 11.56576



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.57607 38.56054 0.25322 8.24731
February 454.00000 23.76627 41.35229 0.33506 8.86992
March 514.00000 23.85286 40.61285 0.37057 9.48309
April 485.00000 24.15170 45.54140 0.51274 11.09588
May 508.00000 24.46485 48.68184 -0.1627 7.11416
June 496.00000 24.36866 48.01675 -0.1869 6.78883
July 497.00000 24.45980 48.12864 -0.1584 7.04901
August 514.00000 24.28483 48.44525 -0.2214 7.00772
September 485.00000 24.46675 49.09409 -0.1929 7.51494
October 502.00000 24.36860 46.64670 0.58000 13.02322
November 489.00000 24.11797 43.06641 0.45002 10.12492
December 497.00000 23.67040 41.15178 0.30005 8.35513
           
Annual Sum or Average 5943.00000 24.13095 44.96055 0.15434 8.71537
Minimum of Months 454.00000 23.57607 38.56054 -0.2214 6.78883
Maximum of Months 514.00000 24.46675 49.09409 0.58000 13.02322



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.89556 37.14518 0.37966 10.50887
February 454.00000 24.01793 40.23908 0.43656 10.99361
March 514.00000 23.89585 40.34204 0.38801 9.85175
April 485.00000 24.18892 45.59502 0.51073 10.93058
May 508.00000 24.38897 49.31904 -0.2395 7.04213
June 496.00000 24.32081 48.48086 -0.2561 6.99265
July 497.00000 24.41617 48.49563 -0.2138 6.94716
August 514.00000 24.31036 48.36956 -0.2189 6.82272
September 485.00000 24.47314 49.11872 -0.1848 7.29068
October 502.00000 24.49061 45.97213 0.64790 14.99416
November 489.00000 24.41932 41.83289 0.58091 13.39875
December 497.00000 24.13811 39.32877 0.47611 11.97419
           
Annual Sum or Average 5943.00000 24.24673 44.54534 0.18926 9.79358
Minimum of Months 454.00000 23.89556 37.14518 -0.2561 6.82272
Maximum of Months 514.00000 24.49061 49.31904 0.64790 14.99416



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.04632 37.09710 0.39072 9.70797
February 454.00000 24.32673 39.51603 0.51524 11.87818
March 514.00000 24.41312 38.79247 0.56210 12.67596
April 485.00000 24.60817 43.91820 0.71511 16.72099
May 508.00000 24.56517 48.22508 -0.0899 6.83812
June 496.00000 24.53694 47.26279 -0.0537 6.69519
July 497.00000 24.67768 47.02672 0.01088 7.08938
August 514.00000 24.55197 46.97302 0.02153 6.67660
September 485.00000 24.58828 48.35837 -0.0913 7.17719
October 502.00000 24.62186 45.43436 0.70061 16.43570
November 489.00000 24.57166 41.36666 0.62810 14.24729
December 497.00000 24.57954 38.11914 0.59650 13.76434
           
Annual Sum or Average 5943.00000 24.50781 43.52939 0.32324 10.79934
Minimum of Months 454.00000 24.04632 37.09710 -0.0913 6.67660
Maximum of Months 514.00000 24.67768 48.35837 0.71511 16.72099



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.00494 43.26486 -0.1460 7.87407
February 454.00000 22.44879 45.35020 -0.0095 8.19699
March 514.00000 22.91222 44.21918 0.10402 7.57943
April 485.00000 23.82884 48.58838 0.38639 8.92302
May 508.00000 24.36875 51.42117 -0.2555 7.18186
June 496.00000 24.36235 50.03294 -0.2472 7.05308
July 497.00000 24.46942 51.06998 -0.2090 7.15958
August 514.00000 24.34649 51.51432 -0.2560 7.23025
September 485.00000 24.31026 52.74752 -0.2894 7.60030
October 502.00000 24.09925 50.42767 0.48660 11.09579
November 489.00000 23.17055 46.97355 0.19268 7.28737
December 497.00000 22.41944 45.61872 -0.0192 7.54832
           
Annual Sum or Average 5943.00000 23.56919 48.45031 -0.0229 7.89001
Minimum of Months 454.00000 22.00494 43.26486 -0.2894 7.05308
Maximum of Months 514.00000 24.46942 52.74752 0.48660 11.09579



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 22.82314 41.21572 0.06004 7.86370
February 385.00000 23.14078 42.95318 0.16818 8.34583
March 433.00000 23.46852 41.88308 0.25874 9.17844
April 410.00000 24.19903 46.81785 0.50648 11.49214
May 430.00000 24.58218 50.22489 -0.1304 7.46859
June 418.00000 24.52981 49.11499 -0.1448 7.10905
July 422.00000 24.68558 49.94611 -0.0922 7.63459
August 433.00000 24.50828 50.60326 -0.1606 7.22755
September 410.00000 24.54999 51.43846 -0.1731 7.97574
October 427.00000 24.38160 49.08556 0.58030 13.76630
November 417.00000 23.78745 44.55854 0.35418 9.16043
December 422.00000 23.00268 43.91153 0.12770 8.15489
           
Annual Sum or Average 5034.00000 23.97582 46.83013 0.11193 8.78047
Minimum of Months 385.00000 22.82314 41.21572 -0.1731 7.10905
Maximum of Months 433.00000 24.68558 51.43846 0.58030 13.76630



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.64271 38.42981 0.31871 10.43580
February 454.00000 23.73798 41.33435 0.36485 10.73022
March 514.00000 23.53487 41.90845 0.29208 9.34377
April 485.00000 24.05279 47.49922 0.46387 10.39610
May 508.00000 24.37312 51.37545 -0.2493 7.18128
June 496.00000 24.33792 50.22967 -0.2640 7.18040
July 497.00000 24.45523 51.14634 -0.2155 7.20943
August 514.00000 24.37940 51.12780 -0.2208 7.08087
September 485.00000 24.44226 51.53557 -0.1960 7.51446
October 502.00000 24.47163 48.01938 0.64626 15.31463
November 489.00000 24.25374 42.99259 0.53493 12.88166
December 497.00000 23.82621 41.16463 0.39484 11.72594
           
Annual Sum or Average 5943.00000 24.12714 46.42947 0.15308 9.73358
Minimum of Months 454.00000 23.53487 38.42981 -0.2640 7.08087
Maximum of Months 514.00000 24.47163 51.53557 0.64626 15.31463



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.92469 40.64459 0.09785 8.21486
February 454.00000 23.30003 42.67631 0.22474 9.40264
March 514.00000 23.54309 42.09743 0.28871 9.24530
April 485.00000 24.26887 46.69304 0.54596 12.30440
May 508.00000 24.47953 50.53938 -0.1585 7.03278
June 496.00000 24.47385 49.24020 -0.1452 6.99319
July 497.00000 24.59919 50.05796 -0.1072 7.30245
August 514.00000 24.47246 50.30261 -0.1403 6.92209
September 485.00000 24.48275 51.35912 -0.1705 7.48797
October 502.00000 24.37634 48.73283 0.60011 13.89160
November 489.00000 23.83479 44.60226 0.38264 9.54108
December 497.00000 23.26757 43.03932 0.21130 8.78501
           
Annual Sum or Average 5943.00000 24.00597 46.68828 0.13411 8.91434
Minimum of Months 454.00000 22.92469 40.64459 -0.1705 6.92209
Maximum of Months 514.00000 24.59919 51.35912 0.60011 13.89160



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.55598 44.51887 -0.2808 10.07744
February 454.00000 22.03441 46.51632 -0.1233 9.91321
March 514.00000 22.58347 45.02972 0.01699 8.62803
April 485.00000 23.69011 49.16297 0.35895 9.00106
May 508.00000 24.39638 51.62028 -0.2264 7.15258
June 496.00000 24.39356 50.08746 -0.2133 7.02281
July 497.00000 24.51511 51.10618 -0.1712 7.27812
August 514.00000 24.36825 51.73470 -0.2275 7.20795
September 485.00000 24.33737 53.18219 -0.2640 7.76689
October 502.00000 24.02069 51.01151 0.47586 11.55953
November 489.00000 22.78669 48.06418 0.09640 7.67968
December 497.00000 21.99794 46.95656 -0.1400 9.00794
           
Annual Sum or Average 5943.00000 23.39927 49.09238 -0.0587 8.51436
Minimum of Months 454.00000 21.55598 44.51887 -0.2808 7.02281
Maximum of Months 514.00000 24.51511 53.18219 0.47586 11.55953



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.33004 42.60967 -0.0735 8.74296
February 454.00000 22.76616 44.37292 0.07592 9.29263
March 514.00000 23.22730 42.81509 0.20199 9.66370
April 485.00000 24.06500 47.26653 0.49382 11.43931
May 508.00000 24.50064 50.36095 -0.1178 7.28926
June 496.00000 24.45789 49.22135 -0.1223 6.93500
July 497.00000 24.59631 49.96284 -0.0768 7.51021
August 514.00000 24.43521 50.70994 -0.1431 7.05485
September 485.00000 24.46095 51.68980 -0.1685 7.91858
October 502.00000 24.24226 49.38227 0.56650 13.76545
November 489.00000 23.52888 45.65873 0.29311 8.83138
December 497.00000 22.60093 45.25001 0.01893 8.82093
           
Annual Sum or Average 5943.00000 23.77399 47.45684 0.07807 8.93115
Minimum of Months 454.00000 22.33004 42.60967 -0.1685 6.93500
Maximum of Months 514.00000 24.59631 51.68980 0.56650 13.76545



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.24750 39.62447 0.19830 10.45936
February 454.00000 23.34909 42.37526 0.25827 10.90359
March 514.00000 23.23932 42.72508 0.21302 9.83200
April 485.00000 23.92343 48.08768 0.43903 10.41990
May 508.00000 24.39572 51.59377 -0.2215 7.16744
June 496.00000 24.37054 50.28643 -0.2297 7.13308
July 497.00000 24.49900 51.18948 -0.1782 7.31510
August 514.00000 24.39435 51.36928 -0.1942 7.08672
September 485.00000 24.44337 52.01159 -0.1776 7.72663
October 502.00000 24.39364 48.57100 0.63614 15.47421
November 489.00000 24.01465 43.71325 0.46890 12.23267
December 497.00000 23.46016 42.35612 0.28823 11.50072
           
Annual Sum or Average 5943.00000 23.98075 47.02083 0.12285 9.75576
Minimum of Months 454.00000 23.23932 39.62447 -0.2297 7.08672
Maximum of Months 514.00000 24.49900 52.01159 0.63614 15.47421



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.49341 41.83085 -0.0237 9.20647
February 454.00000 22.91856 43.73369 0.12460 10.17647
March 514.00000 23.23609 42.89806 0.21068 9.70390
April 485.00000 24.15148 47.25089 0.52390 12.23708
May 508.00000 24.49245 50.78806 -0.1346 7.10834
June 496.00000 24.48475 49.36697 -0.1184 7.07365
July 497.00000 24.61422 50.18004 -0.0797 7.47503
August 514.00000 24.47997 50.56808 -0.1170 6.98800
September 485.00000 24.48336 51.85292 -0.1534 7.67293
October 502.00000 24.30495 49.28094 0.59142 14.14402
November 489.00000 23.52891 45.46523 0.30580 9.35182
December 497.00000 22.86106 44.27009 0.10135 9.28302
           
Annual Sum or Average 5943.00000 23.84304 47.30956 0.10140 9.18718
Minimum of Months 454.00000 22.49341 41.83085 -0.1534 6.98800
Maximum of Months 514.00000 24.61422 51.85292 0.59142 14.14402



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.670759E+11 199057.69 19-JAN-14:00 284.53 0.424530E+12 0.00 0.491606E+12 2.13 7.53 02-JAN-11:50 0.00 0.00
February 0.890805E+11 196820.03 24-FEB-15:10 331.73 0.578250E+12 0.00 0.667330E+12 2.88 7.52 01-FEB-16:40 0.00 0.00
March 0.107234E+12 201355.56 30-MAR-12:00 417.22 0.696299E+12 0.00 0.803533E+12 3.22 7.55 24-MAR-16:00 0.00 0.00
April 0.159503E+12 199072.30 28-APR-16:10 555.24 0.108204E+13 0.00 0.124154E+13 4.65 7.57 18-APR-14:10 0.00 0.00
May 0.221079E+12 206756.41 01-MAY-07:20 541.76 0.150299E+13 0.00 0.172407E+13 4.75 7.52 02-MAY-05:04 0.00 0.00
June 0.226669E+12 215953.08 24-JUN-10:30 604.84 0.151402E+13 0.00 0.174069E+13 5.24 7.56 07-JUN-05:05 0.00 0.00
July 0.235046E+12 218361.48 22-JUL-09:20 667.84 0.153439E+13 0.00 0.176943E+13 5.38 7.36 12-JUL-15:00 0.00 0.00
August 0.239812E+12 218976.34 05-AUG-11:40 680.52 0.158835E+13 0.00 0.182816E+13 5.53 7.45 16-AUG-04:13 0.00 0.00
September 0.218139E+12 210816.44 02-SEP-11:30 537.83 0.146773E+13 0.00 0.168587E+13 4.80 7.54 23-SEP-05:04 0.00 0.00
October 0.191808E+12 217036.73 14-OCT-11:00 554.49 0.128184E+13 0.00 0.147365E+13 4.60 7.57 26-OCT-14:30 0.00 0.00
November 0.125404E+12 200739.90 01-NOV-11:20 455.13 0.817266E+12 0.00 0.942670E+12 3.71 7.56 08-NOV-06:05 0.00 0.00
December 0.905311E+11 199093.58 11-DEC-13:00 382.60 0.588261E+12 0.00 0.678792E+12 2.89 7.51 15-DEC-06:04 0.00 0.00
                         
Annual Sum or Average 0.197138E+13     6013.73 0.130760E+14 0.00 0.150473E+14 4.15     0.00 0.00
Minimum of Months 0.670759E+11 196820.03   284.53 0.424530E+12 0.00 0.491606E+12 2.13 7.36   0.00 0.00
Maximum of Months 0.239812E+12 218976.34   680.52 0.158835E+13 0.00 0.182816E+13 5.53 7.57   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.253863E+10 162670.11 19-JAN-14:53 7.03 0.178314E+11 0.00 0.203700E+11 0.06 7.28 02-JAN-11:40 0.00 0.00
February 0.556030E+10 143078.65 24-FEB-15:53 17.47 0.392210E+11 0.00 0.447813E+11 0.17 7.33 22-FEB-15:03 0.00 0.00
March 0.711384E+10 154563.95 07-MAR-11:23 21.17 0.495731E+11 0.00 0.566869E+11 0.19 7.32 17-MAR-14:25 0.00 0.00
April 0.136574E+11 167634.71 14-APR-15:32 38.81 0.947394E+11 0.00 0.108397E+12 0.36 7.36 20-APR-14:05 0.00 0.00
May 0.535284E+11 180562.26 24-MAY-05:04 139.06 0.363268E+12 0.00 0.416797E+12 1.26 7.22 03-MAY-10:23 0.00 0.00
June 0.605125E+11 148841.28 13-JUN-15:33 154.31 0.405170E+12 0.00 0.465683E+12 1.42 7.26 12-JUN-12:25 0.00 0.00
July 0.692115E+11 146677.24 21-JUL-12:05 171.17 0.457986E+12 0.00 0.527197E+12 1.52 7.12 12-JUL-15:20 0.00 0.00
August 0.753343E+11 153596.41 16-AUG-14:05 188.00 0.501842E+12 0.00 0.577176E+12 1.67 7.07 16-AUG-14:05 0.00 0.00
September 0.546967E+11 155525.32 22-SEP-12:23 141.30 0.368454E+12 0.00 0.423151E+12 1.31 7.20 22-SEP-12:23 0.00 0.00
October 0.473292E+11 170314.64 03-OCT-13:43 119.56 0.319064E+12 0.00 0.366393E+12 1.08 7.43 02-OCT-12:23 0.00 0.00
November 0.148531E+11 153918.33 07-NOV-09:43 39.31 0.100977E+12 0.00 0.115830E+12 0.37 7.38 06-NOV-09:33 0.00 0.00
December 0.915626E+10 165218.61 13-DEC-14:23 24.08 0.631195E+11 0.00 0.722758E+11 0.22 7.28 08-DEC-15:50 0.00 0.00
                         
Annual Sum or Average 0.413492E+12     1061.25 0.278125E+13 0.00 0.319474E+13 0.81     0.00 0.00
Minimum of Months 0.253863E+10 143078.65   7.03 0.178314E+11 0.00 0.203700E+11 0.06 7.07   0.00 0.00
Maximum of Months 0.753343E+11 180562.26   188.00 0.501842E+12 0.00 0.577176E+12 1.67 7.43   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.356348E+11 744.00 43776.24 01-JAN-08:43 281490.29 31-JAN-13:00 20.17 19.30 14.16
February 0.508041E+11 672.00 43776.24 01-FEB-00:10 428747.19 24-FEB-10:30 22.90 20.23 14.16
March 0.735322E+11 744.00 43776.24 01-MAR-00:10 612371.90 31-MAR-24:00 27.03 21.87 14.16
April 0.107241E+12 720.00 43776.24 01-APR-00:10 691669.09 28-APR-17:20 37.09 26.29 14.16
May 0.117250E+12 744.00 43776.24 01-MAY-00:05 335901.97 31-MAY-23:40 32.98 28.75 14.16
June 0.113468E+12 720.00 43776.24 01-JUN-00:10 485835.99 30-JUN-23:55 38.05 30.80 14.16
July 0.117250E+12 744.00 43776.24 01-JUL-00:10 634183.12 31-JUL-23:45 42.72 32.48 14.16
August 0.117250E+12 744.00 43776.24 01-AUG-00:03 699650.09 06-AUG-15:31 46.28 33.25 14.16
September 0.113468E+12 720.00 43776.24 01-SEP-00:10 335119.36 30-SEP-23:50 32.34 28.09 14.16
October 0.108002E+12 744.00 43776.24 01-OCT-00:10 473845.66 31-OCT-24:00 33.26 27.19 14.16
November 0.838112E+11 720.00 43776.24 01-NOV-00:10 540608.40 01-NOV-14:05 28.85 22.95 14.16
December 0.719364E+11 744.00 43776.24 01-DEC-09:50 674012.48 13-DEC-17:10 29.03 22.06 14.16
                   
Annual Sum or Average 0.110965E+13 8760.00         32.62 26.14 14.16
Minimum of Months 0.356348E+11 672.00 43776.24   281490.29   20.17 19.30 14.16
Maximum of Months 0.117250E+12 744.00 43776.24   699650.09   46.28 33.25 14.16



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.519427E+10 203.97 20273.24 01-JAN-16:53 1544860.75 02-JAN-14:00 21.98 21.33 22.68
February 0.674325E+10 270.35 20273.24 01-FEB-12:40 1449694.46 27-FEB-10:00 22.51 21.54 30.64
March 0.941013E+10 331.54 20273.24 06-MAR-08:30 1432180.56 30-MAR-08:40 22.60 21.54 34.08
April 0.192574E+11 476.90 20273.24 01-APR-04:12 1576107.01 19-APR-13:50 23.55 21.87 48.22
May 0.393619E+11 541.68 20273.24 01-MAY-01:10 1314590.54 17-MAY-04:13 27.07 24.85 41.91
June 0.431113E+11 604.84 20273.24 01-JUN-04:12 1337307.93 13-JUN-15:33 27.17 24.84 49.54
July 0.487415E+11 667.84 20273.24 01-JUL-00:10 1208222.22 12-JUL-12:05 28.06 25.75 51.52
August 0.487838E+11 678.69 20273.24 01-AUG-00:20 1262168.36 16-AUG-17:20 27.52 25.14 53.73
September 0.392386E+11 537.83 20273.24 01-SEP-00:10 1306456.17 22-SEP-07:20 27.73 25.47 41.97
October 0.309136E+11 533.30 20273.24 02-OCT-08:50 1518021.16 02-OCT-10:30 25.62 23.69 45.28
November 0.127073E+11 395.14 20273.24 01-NOV-03:03 1463595.59 06-NOV-08:50 23.22 21.94 39.68
December 0.949653E+10 289.68 20273.24 08-DEC-10:50 1486031.02 08-DEC-16:30 22.39 21.49 30.35
                   
Annual Sum or Average 0.312960E+12 5531.76         24.97 23.30 40.84
Minimum of Months 0.519427E+10 203.97 20273.24   1208222.22   21.98 21.33 22.68
Maximum of Months 0.487838E+11 678.69 20273.24   1576107.01   28.06 25.75 53.73



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.119713E+10 16.40 20273.24 02-JAN-11:00 1130734.86 19-JAN-14:05 21.98 21.89 1.08
February 0.221181E+10 30.31 20273.24 01-FEB-13:30 1133130.92 22-FEB-15:03 22.51 22.32 2.38
March 0.309370E+10 42.39 20273.24 06-MAR-09:30 1139034.11 07-MAR-11:23 22.60 22.37 2.94
April 0.571010E+10 78.39 20273.24 04-APR-15:00 1200138.39 18-APR-15:10 23.55 23.12 5.55
May 0.233768E+11 320.30 20273.24 01-MAY-05:05 1150690.76 03-MAY-10:05 27.07 25.48 21.45
June 0.240230E+11 329.16 20273.24 01-JUN-06:50 1337307.93 13-JUN-15:33 27.17 25.48 23.22
July 0.288346E+11 395.08 20273.24 01-JUL-05:06 1208222.22 12-JUL-12:05 28.06 26.18 26.32
August 0.283708E+11 388.73 20273.24 01-AUG-06:20 1184508.68 10-AUG-12:05 27.52 25.63 26.78
September 0.249043E+11 341.23 20273.24 01-SEP-05:08 1173357.87 11-SEP-12:05 27.73 26.02 23.20
October 0.171872E+11 235.49 20273.24 02-OCT-09:30 1210843.09 02-OCT-14:23 25.62 24.48 16.41
November 0.536633E+10 73.53 20273.24 01-NOV-06:20 1161711.60 07-NOV-13:05 23.22 22.84 5.39
December 0.357924E+10 49.04 20273.24 08-DEC-14:30 1168739.54 13-DEC-14:23 22.39 22.14 3.40
                   
Annual Sum or Average 0.167855E+12 2300.05         24.97 24.01 13.25
Minimum of Months 0.119713E+10 16.40 20273.24   1130734.86   21.98 21.89 1.08
Maximum of Months 0.288346E+11 395.08 20273.24   1337307.93   28.06 26.18 26.78



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.193519E+11 0.00 199.51 933550.74 05-JAN-06:02 0.00 28.16 42.89 0.04 0.00 0.01 0.66 05-JAN-06:02
February 0.974013E+10 0.00 108.25 835074.97 17-FEB-06:02 0.00 23.12 32.04 0.02 0.00 0.00 0.59 17-FEB-06:02
March 0.861809E+10 0.00 82.52 880587.67 11-MAR-06:02 0.00 26.14 32.22 0.02 0.00 0.00 0.62 11-MAR-06:02
April 0.302436E+09 0.00 10.71 88972.93 18-APR-14:10 0.00 51.70 52.30 0.00 0.00 0.00 0.06 18-APR-14:10
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 67.30 67.30 0.00 0.00 0.00 0.00 01-MAY-00:05
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 67.30 67.30 0.00 0.00 0.00 0.00 01-JUN-00:10
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 67.30 67.30 0.00 0.00 0.00 0.00 01-JUL-00:10
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 67.30 67.30 0.00 0.00 0.00 0.00 01-AUG-00:03
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 67.30 67.30 0.00 0.00 0.00 0.00 01-SEP-00:10
October 16668603.92 0.00 6.17 3298.74 28-OCT-05:03 0.00 65.99 66.18 0.00 0.00 0.00 0.00 28-OCT-05:03
November 0.608448E+09 0.00 37.45 130346.61 16-NOV-06:02 0.00 37.88 40.52 0.00 0.00 0.00 0.09 16-NOV-06:02
December 0.127245E+11 0.00 147.36 906570.56 21-DEC-06:01 0.00 23.41 34.60 0.02 0.00 0.00 0.64 21-DEC-06:01
                           
Annual Sum or Average 0.513621E+11 0.00 591.97     0.00 49.55 53.24 0.01 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 23.12 32.04 0.00 0.00 0.00 0.00  
Maximum of Months 0.193519E+11 0.00 199.51 933550.74   0.00 67.30 67.30 0.04 0.00 0.01 0.66  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 20.17 20.17 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 22.90 22.90 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 27.03 27.03 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 37.09 37.09 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 32.98 32.98 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 38.05 38.05 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 42.72 42.72 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 46.28 46.28 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 32.34 32.34 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 33.26 33.26 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 28.85 28.85 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 29.03 29.03 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 32.62 32.62 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 20.17 20.17 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 46.28 46.28 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.407378E+11 0.00 271.39 0.308916E+11 0.00 0.00 0.00 0.00 138188.76 19-JAN-06:03 115957.65 19-JAN-06:03 0.00 0.00 0.00
February 0.584076E+11 0.00 319.31 0.430563E+11 0.00 0.00 0.00 0.00 159909.45 28-FEB-05:12 146405.59 27-FEB-05:11 0.00 0.00 0.00
March 0.732320E+11 0.00 410.05 0.584088E+11 0.00 0.00 0.00 0.00 162850.83 28-MAR-04:12 142506.67 27-MAR-04:11 0.00 0.00 0.00
April 0.117939E+12 0.00 544.12 0.944472E+11 0.00 0.00 0.00 0.00 160127.44 01-APR-04:12 142566.48 24-APR-05:02 0.00 0.00 0.00
May 0.147724E+12 0.00 517.22 0.114421E+12 0.00 0.00 0.00 0.00 181164.58 24-MAY-05:02 148563.45 31-MAY-04:11 0.00 0.00 0.00
June 0.160087E+12 0.00 579.14 0.126973E+12 0.00 0.00 0.00 0.00 174175.25 07-JUN-04:12 146536.51 26-JUN-05:02 0.00 0.00 0.00
July 0.173226E+12 0.00 630.12 0.135507E+12 0.00 0.00 0.00 0.00 168705.62 24-JUL-05:03 150845.55 24-JUL-05:02 0.00 0.00 0.00
August 0.190555E+12 0.00 655.39 0.150761E+12 0.00 0.00 0.00 0.00 180830.56 07-AUG-05:02 152899.72 21-AUG-05:02 0.00 0.00 0.00
September 0.148453E+12 0.00 506.08 0.108723E+12 0.00 0.00 0.00 0.00 193598.36 13-SEP-04:12 147953.25 11-SEP-05:02 0.00 0.00 0.00
October 0.139552E+12 0.00 530.04 0.110234E+12 0.00 0.00 0.00 0.00 177768.34 21-OCT-04:11 147235.94 10-OCT-05:03 0.00 0.00 0.00
November 0.888054E+11 0.00 439.44 0.720086E+11 0.00 0.00 0.00 0.00 170741.58 01-NOV-04:11 142350.77 01-NOV-04:11 0.00 0.00 0.00
December 0.665451E+11 0.00 369.97 0.528524E+11 0.00 0.00 0.00 0.00 142768.02 11-DEC-06:02 132056.14 11-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.140526E+13 0.00 5772.29 0.109828E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.407378E+11 0.00 271.39 0.308916E+11 0.00 0.00 0.00 0.00 138188.76   115957.65   0.00 0.00 0.00
Maximum of Months 0.190555E+12 0.00 655.39 0.150761E+12 0.00 0.00 0.00 0.00 193598.36   152899.72   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.332217E+12 0.00 267.08 0.246422E+12 0.00 0.00 0.00 0.00 1155518.78 19-JAN-06:03 879237.68 19-JAN-06:03 0.00 0.00 0.00
February 0.464006E+12 0.00 302.51 0.328919E+12 0.00 0.00 0.00 0.00 1230508.54 03-FEB-06:03 1047878.38 28-FEB-06:03 0.00 0.00 0.00
March 0.552730E+12 0.00 367.68 0.418524E+12 0.00 0.00 0.00 0.00 1514413.17 27-MAR-05:03 1215482.09 27-MAR-05:03 0.00 0.00 0.00
April 0.859903E+12 0.00 416.61 0.647282E+12 0.00 0.00 0.00 0.00 1608013.40 28-APR-04:12 1308523.45 28-APR-04:12 0.00 0.00 0.00
May 0.134360E+13 0.00 480.61 0.996848E+12 0.00 0.00 0.00 0.00 2214100.04 24-MAY-05:02 1357535.91 24-MAY-05:02 0.00 0.00 0.00
June 0.137170E+13 0.00 489.89 0.103037E+13 0.00 0.00 0.00 0.00 1748296.06 06-JUN-04:11 1314322.02 16-JUN-05:02 0.00 0.00 0.00
July 0.142114E+13 0.00 503.47 0.102297E+13 0.00 0.00 0.00 0.00 1653600.79 27-JUL-03:02 1342827.31 07-JUL-03:02 0.00 0.00 0.00
August 0.147730E+13 0.00 504.26 0.106397E+13 0.00 0.00 0.00 0.00 1910958.76 16-AUG-04:12 1307543.79 09-AUG-04:12 0.00 0.00 0.00
September 0.132294E+13 0.00 467.78 0.912273E+12 0.00 0.00 0.00 0.00 2191988.12 05-SEP-04:12 1340882.84 01-SEP-04:12 0.00 0.00 0.00
October 0.116523E+13 0.00 451.99 0.866095E+12 0.00 0.00 0.00 0.00 1912477.80 21-OCT-04:11 1313224.81 04-OCT-04:12 0.00 0.00 0.00
November 0.679224E+12 0.00 394.42 0.527059E+12 0.00 0.00 0.00 0.00 1614567.92 01-NOV-05:02 1295769.24 03-NOV-05:03 0.00 0.00 0.00
December 0.474759E+12 0.00 303.66 0.351327E+12 0.00 0.00 0.00 0.00 1554466.10 11-DEC-06:02 1206692.06 11-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.114647E+14 0.00 4949.96 0.841206E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.332217E+12 0.00 267.08 0.246422E+12 0.00 0.00 0.00 0.00 1155518.78   879237.68   0.00 0.00 0.00
Maximum of Months 0.147730E+13 0.00 504.26 0.106397E+13 0.00 0.00 0.00 0.00 2214100.04   1357535.91   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.315440E+11 0.00 253.58 0.225974E+11 0.00 0.00 0.00 0.00 133018.20 19-JAN-14:53 89601.81 19-JAN-15:10 0.00 0.00 0.00
February 0.459332E+11 0.00 296.86 0.322335E+11 0.00 0.00 0.00 0.00 128048.22 24-FEB-15:53 95113.15 28-FEB-06:03 0.00 0.00 0.00
March 0.561534E+11 0.00 362.57 0.420828E+11 0.00 0.00 0.00 0.00 152911.17 07-MAR-06:02 117874.57 30-MAR-05:02 0.00 0.00 0.00
April 0.904892E+11 0.00 409.15 0.688264E+11 0.00 0.00 0.00 0.00 159180.14 29-APR-05:03 122597.43 28-APR-05:03 0.00 0.00 0.00
May 0.148399E+12 0.00 485.46 0.112583E+12 0.00 0.00 0.00 0.00 243053.13 24-MAY-05:02 148565.01 08-MAY-03:02 0.00 0.00 0.00
June 0.153675E+12 0.00 497.42 0.118620E+12 0.00 0.00 0.00 0.00 192582.62 06-JUN-04:11 144122.01 21-JUN-05:02 0.00 0.00 0.00
July 0.158838E+12 0.00 515.62 0.117322E+12 0.00 0.00 0.00 0.00 199546.16 27-JUL-03:02 151057.50 20-JUL-03:02 0.00 0.00 0.00
August 0.163099E+12 0.00 510.96 0.120310E+12 0.00 0.00 0.00 0.00 198634.17 23-AUG-03:02 151515.37 22-AUG-03:02 0.00 0.00 0.00
September 0.142381E+12 0.00 471.08 0.998051E+11 0.00 0.00 0.00 0.00 243868.02 05-SEP-04:12 143301.64 01-SEP-04:12 0.00 0.00 0.00
October 0.124186E+12 0.00 452.93 0.934297E+11 0.00 0.00 0.00 0.00 195721.90 11-OCT-04:12 143916.58 06-OCT-03:02 0.00 0.00 0.00
November 0.656816E+11 0.00 387.99 0.506500E+11 0.00 0.00 0.00 0.00 179237.47 01-NOV-05:02 129204.67 01-NOV-05:02 0.00 0.00 0.00
December 0.452225E+11 0.00 297.57 0.329973E+11 0.00 0.00 0.00 0.00 150290.81 15-DEC-06:02 111116.12 11-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.122560E+13 0.00 4941.21 0.911457E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.315440E+11 0.00 253.58 0.225974E+11 0.00 0.00 0.00 0.00 128048.22   89601.81   0.00 0.00 0.00
Maximum of Months 0.163099E+12 0.00 515.62 0.120310E+12 0.00 0.00 0.00 0.00 243868.02   151515.37   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.218475E+11 0.00 153.48 0.172309E+11 0.00 0.00 0.00 0.00 123828.33 19-JAN-05:12 106249.63 16-JAN-15:17 0.00 0.00 0.00
February 0.262581E+11 0.00 198.93 0.213851E+11 0.00 0.00 0.00 0.00 121212.94 03-FEB-05:12 104920.98 21-FEB-05:12 0.00 0.00 0.00
March 0.351738E+11 0.00 243.20 0.300003E+11 0.00 0.00 0.00 0.00 145405.44 07-MAR-05:13 97154.79 06-MAR-05:11 0.00 0.00 0.00
April 0.551412E+11 0.00 352.35 0.481061E+11 0.00 0.00 0.00 0.00 145147.09 26-APR-04:13 87932.85 24-APR-04:53 0.00 0.00 0.00
May 0.100822E+12 0.00 429.90 0.778183E+11 0.00 0.00 0.00 0.00 169711.73 29-MAY-09:21 89950.66 29-MAY-18:40 0.00 0.00 0.00
June 0.105783E+12 0.00 427.11 0.793112E+11 0.00 0.00 0.00 0.00 168665.26 19-JUN-03:02 92657.71 12-JUN-03:02 0.00 0.00 0.00
July 0.114257E+12 0.00 420.04 0.804793E+11 0.00 0.00 0.00 0.00 168800.15 03-JUL-03:02 90854.51 05-JUL-03:13 0.00 0.00 0.00
August 0.127008E+12 0.00 467.45 0.919942E+11 0.00 0.00 0.00 0.00 171448.85 06-AUG-14:30 93673.20 21-AUG-03:02 0.00 0.00 0.00
September 0.108262E+12 0.00 432.59 0.786903E+11 0.00 0.00 0.00 0.00 171644.83 17-SEP-15:11 93122.04 04-SEP-12:28 0.00 0.00 0.00
October 0.933220E+11 0.00 408.39 0.715622E+11 0.00 0.00 0.00 0.00 174912.56 15-OCT-14:42 106196.53 01-OCT-14:25 0.00 0.00 0.00
November 0.521962E+11 0.00 308.41 0.432891E+11 0.00 0.00 0.00 0.00 145963.86 29-NOV-05:12 96072.02 05-NOV-15:07 0.00 0.00 0.00
December 0.339305E+11 0.00 207.87 0.275982E+11 0.00 0.00 0.00 0.00 146195.00 15-DEC-05:11 88360.07 12-DEC-05:14 0.00 0.00 0.00
                               
Annual Sum or Average 0.874001E+12 0.00 4049.73 0.667465E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.218475E+11 0.00 153.48 0.172309E+11 0.00 0.00 0.00 0.00 121212.94   87932.85   0.00 0.00 0.00
Maximum of Months 0.127008E+12 0.00 467.45 0.919942E+11 0.00 0.00 0.00 0.00 174912.56   106249.63   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.385540E+11 0.125152E+11 534.17 0.343611E+11 0.419286E+10 0.00 0.50 31-JAN-12:50 0.01 28-JAN-10:07 207721.47 31-JAN-12:50 128334.97 02-JAN-15:00 81731.46 31-JAN-12:50 53027.87 31-JAN-12:50 0.00
February 0.147646E+12 0.403847E+11 498.57 0.137761E+12 0.988461E+10 0.00 0.72 24-FEB-10:30 0.01 19-FEB-07:20 311463.84 24-FEB-10:30 218603.48 24-FEB-13:05 112743.84 24-FEB-10:20 76251.69 24-FEB-10:30 0.00
March 0.361275E+12 0.977015E+11 697.86 0.334693E+12 0.265820E+11 0.00 0.96 31-MAR-24:00 0.01 11-MAR-17:13 393832.87 31-MAR-24:00 393832.87 31-MAR-24:00 169854.45 29-MAR-08:40 101826.60 30-MAR-13:00 0.00
April 0.854292E+12 0.229491E+12 719.83 0.779038E+12 0.752539E+11 0.00 1.00 04-APR-12:05 0.01 11-APR-06:50 428918.24 05-APR-07:15 403808.89 28-APR-21:02 220829.85 05-APR-07:10 134902.18 28-APR-15:00 0.00
May 0.348758E+12 0.106809E+12 744.00 0.336045E+12 0.127122E+11 0.00 0.56 31-MAY-23:20 0.34 07-MAY-01:00 212651.97 31-MAY-23:10 210965.91 31-MAY-24:00 14562.22 23-MAY-16:00 57839.06 31-MAY-23:20 0.00
June 0.575869E+12 0.177331E+12 720.00 0.561926E+12 0.139426E+11 0.00 0.78 30-JUN-23:55 0.55 01-JUN-05:00 302788.65 30-JUN-24:00 302586.36 30-JUN-23:55 17688.10 29-JUN-15:00 86852.01 30-JUN-23:20 0.00
July 0.841916E+12 0.259935E+12 744.00 0.826960E+12 0.149562E+11 0.00 0.99 31-JUL-23:20 0.78 01-JUL-04:10 394842.00 31-JUL-24:00 394842.00 31-JUL-24:00 16556.99 12-JUL-12:50 122564.72 21-JUL-16:00 0.00
August 0.108022E+13 0.322613E+12 744.00 0.106640E+13 0.138225E+11 0.00 1.00 01-AUG-06:40 0.39 31-AUG-24:00 424119.82 07-AUG-14:00 409862.02 06-AUG-15:54 89389.35 20-AUG-04:10 141752.78 30-AUG-16:00 0.00
September 0.341849E+12 0.102540E+12 720.00 0.328234E+12 0.136145E+11 0.00 0.55 30-SEP-23:20 0.34 22-SEP-06:10 213138.38 30-SEP-24:00 211863.19 30-SEP-24:00 14088.02 18-SEP-10:40 57196.67 30-SEP-23:20 0.00
October 0.486348E+12 0.143456E+12 706.50 0.471394E+12 0.149540E+11 0.00 0.76 31-OCT-24:00 0.01 18-OCT-04:12 303954.33 31-OCT-24:00 303954.33 31-OCT-24:00 81208.04 31-OCT-11:00 83607.53 05-OCT-15:00 0.00
November 0.418573E+12 0.114674E+12 680.96 0.381731E+12 0.368414E+11 0.00 0.86 28-NOV-09:00 0.01 26-NOV-09:40 359241.92 28-NOV-09:00 312444.70 03-NOV-14:00 133034.99 28-NOV-08:50 104659.59 02-NOV-13:00 0.00
December 0.499724E+12 0.131665E+12 716.82 0.448220E+12 0.515047E+11 0.00 1.00 08-DEC-11:10 0.01 19-DEC-21:30 432248.89 28-DEC-09:50 403545.92 13-DEC-18:00 236509.99 28-DEC-09:40 126891.74 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.599502E+13 0.173912E+13 8226.72 0.570676E+13 0.288262E+12 0.00                         0.00
Minimum of Months 0.385540E+11 0.125152E+11 498.57 0.343611E+11 0.419286E+10 0.00 0.50   0.01   207721.47   128334.97   14088.02   53027.87   0.00
Maximum of Months 0.108022E+13 0.322613E+12 744.00 0.106640E+13 0.752539E+11 0.00 1.00   0.78   432248.89   409862.02   236509.99   141752.78   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.516755E+10 0.122776E+10 744.00 0.506154E+10 0.106008E+09 0.00 0.35 19-JAN-17:00 0.14 05-JAN-07:55 2819.46 19-JAN-17:00 2670.67 01-JAN-17:20 402.53 31-JAN-17:00 765.08 02-JAN-15:00 0.00
February 0.958665E+10 0.219726E+10 672.00 0.940003E+10 0.186619E+09 0.00 0.58 26-FEB-17:42 0.39 17-FEB-07:10 4754.10 27-FEB-17:00 4752.44 26-FEB-17:58 396.62 24-FEB-17:00 1353.10 02-FEB-13:10 0.00
March 0.157883E+11 0.365018E+10 744.00 0.155833E+11 0.205016E+09 0.00 0.87 31-MAR-24:00 0.60 11-MAR-07:30 7710.00 31-MAR-24:00 7710.00 31-MAR-24:00 478.65 07-MAR-15:00 2025.69 30-MAR-13:00 0.00
April 0.205283E+11 0.515875E+10 720.00 0.202357E+11 0.292538E+09 0.00 1.00 21-APR-15:48 0.31 30-APR-23:53 8674.62 28-APR-17:30 8524.55 16-APR-18:17 556.34 28-APR-17:30 2849.85 28-APR-15:00 0.00
May 0.654416E+10 0.196608E+10 744.00 0.603806E+10 0.506104E+09 0.00 0.50 31-MAY-23:20 0.26 02-MAY-06:10 4086.11 31-MAY-23:10 3997.59 31-MAY-24:00 553.74 23-MAY-16:00 1092.12 31-MAY-23:20 0.00
June 0.113157E+11 0.341995E+10 720.00 0.107335E+11 0.582223E+09 0.00 0.70 30-JUN-23:55 0.48 01-JUN-06:00 5881.08 30-JUN-23:05 5865.57 30-JUN-24:00 685.60 29-JUN-15:00 1716.65 29-JUN-14:00 0.00
July 0.167920E+11 0.509460E+10 744.00 0.161394E+11 0.652550E+09 0.00 0.90 31-JUL-24:00 0.70 15-JUL-06:00 7744.82 31-JUL-24:00 7742.86 31-JUL-24:00 666.51 12-JUL-10:00 2517.95 21-JUL-16:00 0.00
August 0.218913E+11 0.653424E+10 744.00 0.212343E+11 0.656992E+09 0.00 1.00 01-AUG-10:05 0.33 31-AUG-24:00 8897.58 07-AUG-13:50 8320.50 06-AUG-17:55 737.96 07-AUG-13:40 2994.50 30-AUG-16:00 0.00
September 0.637524E+10 0.187413E+10 720.00 0.583158E+10 0.543666E+09 0.00 0.49 30-SEP-23:50 0.26 07-SEP-21:00 4043.58 30-SEP-24:00 4012.66 30-SEP-24:00 585.52 18-SEP-14:40 1080.78 09-SEP-17:00 0.00
October 0.114759E+11 0.317667E+10 744.00 0.110236E+11 0.452333E+09 0.00 0.69 31-OCT-24:00 0.43 28-OCT-07:00 5880.86 31-OCT-24:00 5871.84 31-OCT-24:00 686.22 24-OCT-14:05 1694.67 05-OCT-15:00 0.00
November 0.155700E+11 0.369128E+10 720.00 0.153168E+11 0.253168E+09 0.00 0.80 02-NOV-16:00 0.62 15-NOV-07:10 6808.86 07-NOV-16:40 6556.65 12-NOV-17:10 560.73 01-NOV-11:00 2100.84 01-NOV-14:00 0.00
December 0.208309E+11 0.467468E+10 744.00 0.206506E+11 0.180317E+09 0.00 1.00 14-DEC-16:50 0.78 20-DEC-07:20 8768.81 14-DEC-17:00 8415.57 10-DEC-16:53 565.63 12-DEC-15:00 2665.16 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.161866E+12 0.426656E+11 8760.00 0.157249E+12 0.461753E+10 0.00                         0.00
Minimum of Months 0.516755E+10 0.122776E+10 672.00 0.506154E+10 0.106008E+09 0.00 0.35   0.14   2819.46   2670.67   396.62   765.08   0.00
Maximum of Months 0.218913E+11 0.653424E+10 744.00 0.212343E+11 0.656992E+09 0.00 1.00   0.78   8897.58   8524.55   737.96   2994.50   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.378445E+11 0.920388E+10 744.00 0.368141E+11 0.103041E+10 0.00 0.34 19-JAN-17:00 0.05 10-JAN-07:10 26455.61 19-JAN-17:00 23107.43 01-JAN-17:20 3974.38 31-JAN-17:00 7139.29 19-JAN-17:00 0.00
February 0.826001E+11 0.191557E+11 672.00 0.807514E+11 0.184868E+10 0.00 0.56 27-FEB-17:00 0.28 06-FEB-07:10 45075.79 27-FEB-17:00 43566.17 26-FEB-17:56 3945.33 24-FEB-17:00 12704.14 02-FEB-13:20 0.00
March 0.143409E+12 0.334367E+11 744.00 0.141369E+12 0.204032E+10 0.00 0.86 31-MAR-24:00 0.51 13-MAR-06:55 72295.27 31-MAR-24:00 72295.27 31-MAR-24:00 4771.96 07-MAR-15:00 19348.66 30-MAR-13:00 0.00
April 0.193889E+12 0.488631E+11 720.00 0.190964E+12 0.292448E+10 0.00 1.00 27-APR-15:30 0.29 30-APR-23:53 82871.64 28-APR-17:20 79893.15 16-APR-18:15 5519.51 28-APR-17:30 27240.27 28-APR-15:00 0.00
May 0.608180E+11 0.183108E+11 744.00 0.558173E+11 0.500069E+10 0.00 0.49 31-MAY-23:20 0.25 02-MAY-06:10 38556.55 31-MAY-23:10 37547.20 31-MAY-24:00 5467.02 23-MAY-16:00 10308.07 31-MAY-23:20 0.00
June 0.107471E+12 0.324999E+11 720.00 0.101679E+12 0.579195E+10 0.00 0.71 30-JUN-23:55 0.46 07-JUN-06:10 56835.61 30-JUN-23:55 56677.80 30-JUN-24:00 6803.72 29-JUN-15:00 16458.69 29-JUN-14:00 0.00
July 0.160035E+12 0.485663E+11 744.00 0.153526E+12 0.650930E+10 0.00 0.91 31-JUL-24:00 0.69 11-JUL-21:20 74212.12 31-JUL-24:00 74180.39 31-JUL-24:00 6657.27 12-JUL-10:00 24107.24 21-JUL-16:00 0.00
August 0.207945E+12 0.621319E+11 744.00 0.201375E+12 0.657008E+10 0.00 1.00 01-AUG-09:40 0.29 31-AUG-24:00 84576.85 07-AUG-13:40 78063.33 03-AUG-18:00 7347.15 07-AUG-13:40 28620.06 30-AUG-16:00 0.00
September 0.582875E+11 0.171867E+11 720.00 0.529319E+11 0.535563E+10 0.00 0.48 30-SEP-23:50 0.24 28-SEP-06:10 37619.10 30-SEP-24:00 37295.48 30-SEP-24:00 5828.37 18-SEP-14:30 10042.09 09-SEP-17:00 0.00
October 0.107068E+12 0.297619E+11 744.00 0.102574E+12 0.449379E+10 0.00 0.67 31-OCT-24:00 0.38 28-OCT-07:00 54720.83 31-OCT-24:00 54604.94 31-OCT-24:00 6837.67 24-OCT-14:05 16185.49 05-OCT-15:00 0.00
November 0.142529E+12 0.340547E+11 720.00 0.140013E+12 0.251598E+10 0.00 0.80 02-NOV-16:00 0.56 15-NOV-07:30 64981.67 07-NOV-16:50 61623.28 06-NOV-17:00 5602.64 01-NOV-11:00 20086.21 01-NOV-14:00 0.00
December 0.189489E+12 0.429242E+11 744.00 0.187685E+12 0.180376E+10 0.00 1.00 15-DEC-17:00 0.70 20-DEC-07:10 83370.98 14-DEC-17:00 79051.45 15-DEC-17:00 5642.70 12-DEC-15:00 25358.84 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.149138E+13 0.396096E+12 8760.00 0.144550E+13 0.458851E+11 0.00                         0.00
Minimum of Months 0.378445E+11 0.920388E+10 672.00 0.368141E+11 0.103041E+10 0.00 0.34   0.05   26455.61   23107.43   3945.33   7139.29   0.00
Maximum of Months 0.207945E+12 0.621319E+11 744.00 0.201375E+12 0.657008E+10 0.00 1.00   0.70   84576.85   79893.15   7347.15   28620.06   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.272664E+10 0.680856E+09 687.75 0.262507E+10 0.101570E+09 0.00 0.34 19-JAN-17:00 0.00 04-JAN-07:10 2721.93 19-JAN-17:00 2378.77 01-JAN-17:20 401.00 31-JAN-17:00 734.69 19-JAN-16:50 0.00
February 0.748019E+10 0.175587E+10 671.86 0.729625E+10 0.183945E+09 0.00 0.56 27-FEB-17:00 0.00 05-FEB-08:25 4572.10 27-FEB-17:00 4395.57 26-FEB-17:43 395.08 24-FEB-17:00 1291.19 02-FEB-13:53 0.00
March 0.138028E+11 0.324837E+10 744.00 0.135993E+11 0.203450E+09 0.00 0.84 31-MAR-24:00 0.38 12-MAR-07:50 7144.70 31-MAR-24:00 7144.70 31-MAR-24:00 477.37 07-MAR-15:00 1957.19 30-MAR-13:00 0.00
April 0.192787E+11 0.488189E+10 720.00 0.189868E+11 0.291958E+09 0.00 1.00 28-APR-13:05 0.28 30-APR-23:53 8411.01 28-APR-17:20 8190.68 23-APR-18:04 549.91 28-APR-17:30 2775.33 28-APR-15:00 0.00
May 0.623627E+10 0.187932E+10 744.00 0.573394E+10 0.502335E+09 0.00 0.48 31-MAY-23:20 0.24 02-MAY-06:10 3841.73 31-MAY-23:10 3733.79 31-MAY-24:00 552.97 23-MAY-16:00 1029.03 31-MAY-23:20 0.00
June 0.109185E+11 0.330494E+10 720.00 0.103385E+11 0.580028E+09 0.00 0.70 30-JUN-23:55 0.44 07-JUN-06:10 5722.62 30-JUN-23:55 5706.79 30-JUN-24:00 683.93 29-JUN-15:00 1682.94 29-JUN-14:00 0.00
July 0.161857E+11 0.491829E+10 744.00 0.155347E+11 0.650972E+09 0.00 0.89 31-JUL-24:00 0.67 15-JUL-06:00 7419.27 31-JUL-24:00 7415.90 31-JUL-24:00 666.76 12-JUL-10:00 2457.93 21-JUL-16:00 0.00
August 0.209567E+11 0.627634E+10 744.00 0.202993E+11 0.657343E+09 0.00 1.00 01-AUG-11:00 0.29 31-AUG-24:00 8571.73 14-AUG-16:00 8051.14 06-AUG-17:35 729.68 09-AUG-17:00 2915.98 30-AUG-16:00 0.00
September 0.595322E+10 0.175833E+10 720.00 0.541588E+10 0.537343E+09 0.00 0.48 30-SEP-23:30 0.22 28-SEP-06:10 3792.90 30-SEP-24:00 3761.27 30-SEP-24:00 583.24 18-SEP-14:40 1070.71 09-SEP-17:00 0.00
October 0.106674E+11 0.298002E+10 744.00 0.102180E+11 0.449390E+09 0.00 0.66 31-OCT-24:00 0.31 28-OCT-07:00 5417.63 31-OCT-24:00 5405.53 31-OCT-24:00 685.05 24-OCT-14:05 1652.59 05-OCT-15:00 0.00
November 0.137660E+11 0.331935E+10 720.00 0.135153E+11 0.250652E+09 0.00 0.80 02-NOV-16:00 0.48 16-NOV-07:05 6558.16 07-NOV-16:40 6236.48 06-NOV-17:00 560.68 01-NOV-11:00 2031.48 01-NOV-14:00 0.00
December 0.181086E+11 0.414875E+10 744.00 0.179288E+11 0.179761E+09 0.00 0.99 15-DEC-17:00 0.61 20-DEC-07:10 8403.99 14-DEC-17:00 7987.24 15-DEC-17:00 564.24 12-DEC-15:00 2555.79 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.146081E+12 0.391523E+11 8703.61 0.141492E+12 0.458875E+10 0.00                         0.00
Minimum of Months 0.272664E+10 0.680856E+09 671.86 0.262507E+10 0.101570E+09 0.00 0.34   0.00   2721.93   2378.77   395.08   734.69   0.00
Maximum of Months 0.209567E+11 0.627634E+10 744.00 0.202993E+11 0.657343E+09 0.00 1.00   0.67   8571.73   8190.68   729.68   2915.98   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.45 0.00 110.45 70.03 435.82 0.00 0.00 0.00
February 130.31 0.00 130.31 98.87 370.66 0.00 0.00 0.00
March 151.17 0.00 151.17 147.01 314.72 0.00 0.00 0.00
April 178.41 0.73 177.68 240.34 187.94 0.00 0.00 0.00
May 202.09 7.39 194.70 408.74 51.13 0.00 0.00 0.00
June 229.82 15.91 213.90 483.62 40.54 0.00 0.00 0.00
July 223.02 8.50 214.53 464.52 25.97 0.00 0.00 0.00
August 199.72 1.57 198.15 417.17 38.76 0.00 0.00 0.00
September 172.51 0.01 172.50 333.17 61.37 0.00 0.00 0.00
October 149.91 0.00 149.91 266.33 117.64 0.00 0.00 0.00
November 113.81 0.00 113.81 114.70 283.16 0.00 0.00 0.00
December 102.68 0.00 102.68 75.44 384.34 0.00 0.00 0.00
                 
Annual Sum or Average 163.82 2.85 160.97 260.96 191.75 0.00 0.00 0.00
Minimum of Months 102.68 0.00 102.68 70.03 25.97 0.00 0.00 0.00
Maximum of Months 229.82 15.91 214.53 483.62 435.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.45 0.00 110.45 70.03 435.82 0.00 0.00 0.00
February 130.31 0.00 130.31 98.87 370.66 0.00 0.00 0.00
March 151.17 0.00 151.17 147.01 314.72 0.00 0.00 0.00
April 178.41 0.73 177.68 240.34 187.94 0.00 0.00 0.00
May 202.09 7.39 194.70 408.74 51.13 0.00 0.00 0.00
June 229.82 15.91 213.90 483.62 40.54 0.00 0.00 0.00
July 223.02 8.50 214.53 464.52 25.97 0.00 0.00 0.00
August 199.72 1.57 198.15 417.17 38.76 0.00 0.00 0.00
September 172.51 0.01 172.50 333.17 61.37 0.00 0.00 0.00
October 149.91 0.00 149.91 266.33 117.64 0.00 0.00 0.00
November 113.81 0.00 113.81 114.70 283.16 0.00 0.00 0.00
December 102.68 0.00 102.68 75.44 384.34 0.00 0.00 0.00
                 
Annual Sum or Average 163.82 2.85 160.97 260.96 191.75 0.00 0.00 0.00
Minimum of Months 102.68 0.00 102.68 70.03 25.97 0.00 0.00 0.00
Maximum of Months 229.82 15.91 214.53 483.62 435.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.45 0.00 110.45 70.03 435.82 0.00 0.00 0.00
February 130.31 0.00 130.31 98.87 370.66 0.00 0.00 0.00
March 151.17 0.00 151.17 147.01 314.72 0.00 0.00 0.00
April 178.41 0.73 177.68 240.34 187.94 0.00 0.00 0.00
May 202.09 7.39 194.70 408.74 51.13 0.00 0.00 0.00
June 229.82 15.91 213.90 483.62 40.54 0.00 0.00 0.00
July 223.02 8.50 214.53 464.52 25.97 0.00 0.00 0.00
August 199.72 1.57 198.15 417.17 38.76 0.00 0.00 0.00
September 172.51 0.01 172.50 333.17 61.37 0.00 0.00 0.00
October 149.91 0.00 149.91 266.33 117.64 0.00 0.00 0.00
November 113.81 0.00 113.81 114.70 283.16 0.00 0.00 0.00
December 102.68 0.00 102.68 75.44 384.34 0.00 0.00 0.00
                 
Annual Sum or Average 163.82 2.85 160.97 260.96 191.75 0.00 0.00 0.00
Minimum of Months 102.68 0.00 102.68 70.03 25.97 0.00 0.00 0.00
Maximum of Months 229.82 15.91 214.53 483.62 435.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.45 0.00 110.45 70.03 435.82 0.00 0.00 0.00
February 130.31 0.00 130.31 98.87 370.66 0.00 0.00 0.00
March 151.17 0.00 151.17 147.01 314.72 0.00 0.00 0.00
April 178.41 0.73 177.68 240.34 187.94 0.00 0.00 0.00
May 202.09 7.39 194.70 408.74 51.13 0.00 0.00 0.00
June 229.82 15.91 213.90 483.62 40.54 0.00 0.00 0.00
July 223.02 8.50 214.53 464.52 25.97 0.00 0.00 0.00
August 199.72 1.57 198.15 417.17 38.76 0.00 0.00 0.00
September 172.51 0.01 172.50 333.17 61.37 0.00 0.00 0.00
October 149.91 0.00 149.91 266.33 117.64 0.00 0.00 0.00
November 113.81 0.00 113.81 114.70 283.16 0.00 0.00 0.00
December 102.68 0.00 102.68 75.44 384.34 0.00 0.00 0.00
                 
Annual Sum or Average 163.82 2.85 160.97 260.96 191.75 0.00 0.00 0.00
Minimum of Months 102.68 0.00 102.68 70.03 25.97 0.00 0.00 0.00
Maximum of Months 229.82 15.91 214.53 483.62 435.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.45 0.00 110.45 70.02 435.80 0.00 0.00 0.00
February 130.30 0.00 130.30 98.86 370.64 0.00 0.00 0.00
March 151.16 0.00 151.16 147.01 314.71 0.00 0.00 0.00
April 178.41 0.73 177.67 240.33 187.93 0.00 0.00 0.00
May 202.08 7.39 194.69 408.72 51.13 0.00 0.00 0.00
June 229.81 15.91 213.90 483.61 40.53 0.00 0.00 0.00
July 223.01 8.50 214.52 464.50 25.97 0.00 0.00 0.00
August 199.71 1.57 198.14 417.15 38.76 0.00 0.00 0.00
September 172.51 0.01 172.49 333.16 61.36 0.00 0.00 0.00
October 149.91 0.00 149.91 266.32 117.64 0.00 0.00 0.00
November 113.80 0.00 113.80 114.69 283.15 0.00 0.00 0.00
December 102.68 0.00 102.68 75.44 384.32 0.00 0.00 0.00
                 
Annual Sum or Average 163.82 2.85 160.97 260.95 191.74 0.00 0.00 0.00
Minimum of Months 102.68 0.00 102.68 70.02 25.97 0.00 0.00 0.00
Maximum of Months 229.81 15.91 214.52 483.61 435.80 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 315.85 160.83 155.02 362.90 444.15 0.00 0.00 0.00
February 351.71 169.80 181.91 430.70 375.05 0.00 0.00 0.00
March 413.73 199.53 214.20 555.30 318.57 0.00 0.00 0.00
April 454.02 205.34 248.68 699.69 194.97 0.00 0.00 0.00
May 467.97 202.92 265.05 865.40 56.35 0.00 0.00 0.00
June 474.60 188.21 286.39 909.34 42.63 0.00 0.00 0.00
July 457.58 167.45 290.13 878.42 25.11 0.00 0.00 0.00
August 421.65 144.97 276.68 810.56 37.02 0.00 0.00 0.00
September 373.50 128.41 245.09 682.17 66.56 0.00 0.00 0.00
October 369.10 155.76 213.34 640.37 123.09 0.00 0.00 0.00
November 326.78 166.70 160.08 448.70 285.19 0.00 0.00 0.00
December 257.29 116.55 140.74 309.47 387.98 0.00 0.00 0.00
                 
Annual Sum or Average 390.45 167.13 223.32 633.84 195.46 0.00 0.00 0.00
Minimum of Months 257.29 116.55 140.74 309.47 25.11 0.00 0.00 0.00
Maximum of Months 474.60 205.34 290.13 909.34 444.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 315.85 160.83 155.02 362.90 444.15 0.00 0.00 0.00
February 351.71 169.80 181.91 430.70 375.05 0.00 0.00 0.00
March 413.73 199.53 214.20 555.30 318.57 0.00 0.00 0.00
April 454.02 205.34 248.68 699.69 194.97 0.00 0.00 0.00
May 467.97 202.92 265.05 865.40 56.35 0.00 0.00 0.00
June 474.60 188.21 286.39 909.34 42.63 0.00 0.00 0.00
July 457.58 167.45 290.13 878.42 25.11 0.00 0.00 0.00
August 421.65 144.97 276.68 810.56 37.02 0.00 0.00 0.00
September 373.50 128.41 245.09 682.17 66.56 0.00 0.00 0.00
October 369.10 155.76 213.34 640.37 123.09 0.00 0.00 0.00
November 326.78 166.70 160.08 448.70 285.19 0.00 0.00 0.00
December 257.29 116.55 140.74 309.47 387.98 0.00 0.00 0.00
                 
Annual Sum or Average 390.45 167.13 223.32 633.84 195.46 0.00 0.00 0.00
Minimum of Months 257.29 116.55 140.74 309.47 25.11 0.00 0.00 0.00
Maximum of Months 474.60 205.34 290.13 909.34 444.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 315.84 160.83 155.01 362.89 444.14 0.00 0.00 0.00
February 351.70 169.79 181.91 430.70 375.04 0.00 0.00 0.00
March 413.72 199.52 214.19 555.29 318.56 0.00 0.00 0.00
April 454.01 205.33 248.67 699.68 194.97 0.00 0.00 0.00
May 467.96 202.92 265.04 865.39 56.35 0.00 0.00 0.00
June 474.59 188.21 286.38 909.32 42.62 0.00 0.00 0.00
July 457.57 167.45 290.13 878.40 25.11 0.00 0.00 0.00
August 421.64 144.96 276.68 810.55 37.02 0.00 0.00 0.00
September 373.49 128.41 245.09 682.16 66.56 0.00 0.00 0.00
October 369.09 155.75 213.33 640.35 123.09 0.00 0.00 0.00
November 326.77 166.70 160.07 448.69 285.18 0.00 0.00 0.00
December 257.28 116.54 140.74 309.46 387.97 0.00 0.00 0.00
                 
Annual Sum or Average 390.44 167.13 223.31 633.83 195.46 0.00 0.00 0.00
Minimum of Months 257.28 116.54 140.74 309.46 25.11 0.00 0.00 0.00
Maximum of Months 474.59 205.33 290.13 909.32 444.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 638.45 455.32 183.12 906.91 391.14 0.00 0.00 0.00
February 579.04 374.80 204.24 839.18 338.66 0.00 0.00 0.00
March 369.67 166.83 202.84 549.37 300.04 0.00 0.00 0.00
April 273.99 64.20 209.79 450.50 192.11 0.00 0.00 0.00
May 209.35 8.90 200.45 428.42 52.73 0.00 0.00 0.00
June 206.80 1.93 204.88 436.34 42.12 0.00 0.00 0.00
July 216.49 3.98 212.51 452.90 25.89 0.00 0.00 0.00
August 254.69 30.57 224.12 534.29 41.51 0.00 0.00 0.00
September 305.58 80.53 225.05 594.65 65.49 0.00 0.00 0.00
October 474.12 246.97 227.15 848.18 122.63 0.00 0.00 0.00
November 603.34 415.41 187.94 929.53 266.19 0.00 0.00 0.00
December 623.84 448.01 175.83 919.04 353.01 0.00 0.00 0.00
                 
Annual Sum or Average 395.31 190.51 204.81 656.55 181.80 0.00 0.00 0.00
Minimum of Months 206.80 1.93 175.83 428.42 25.89 0.00 0.00 0.00
Maximum of Months 638.45 455.32 227.15 929.53 391.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 638.45 455.32 183.12 906.90 391.14 0.00 0.00 0.00
February 579.04 374.80 204.24 839.18 338.66 0.00 0.00 0.00
March 369.67 166.83 202.84 549.37 300.04 0.00 0.00 0.00
April 273.99 64.20 209.79 450.50 192.11 0.00 0.00 0.00
May 209.35 8.90 200.45 428.42 52.73 0.00 0.00 0.00
June 206.80 1.93 204.88 436.34 42.12 0.00 0.00 0.00
July 216.49 3.98 212.51 452.90 25.89 0.00 0.00 0.00
August 254.69 30.57 224.12 534.28 41.51 0.00 0.00 0.00
September 305.58 80.53 225.05 594.65 65.49 0.00 0.00 0.00
October 474.12 246.97 227.15 848.18 122.63 0.00 0.00 0.00
November 603.34 415.41 187.93 929.53 266.19 0.00 0.00 0.00
December 623.84 448.01 175.83 919.04 353.01 0.00 0.00 0.00
                 
Annual Sum or Average 395.31 190.51 204.81 656.55 181.80 0.00 0.00 0.00
Minimum of Months 206.80 1.93 175.83 428.42 25.89 0.00 0.00 0.00
Maximum of Months 638.45 455.32 227.15 929.53 391.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 638.45 455.32 183.12 906.91 391.14 0.00 0.00 0.00
February 579.04 374.80 204.24 839.18 338.66 0.00 0.00 0.00
March 369.67 166.83 202.84 549.37 300.04 0.00 0.00 0.00
April 273.99 64.20 209.79 450.50 192.11 0.00 0.00 0.00
May 209.35 8.90 200.45 428.42 52.73 0.00 0.00 0.00
June 206.80 1.93 204.88 436.34 42.12 0.00 0.00 0.00
July 216.49 3.98 212.51 452.90 25.89 0.00 0.00 0.00
August 254.69 30.57 224.12 534.29 41.51 0.00 0.00 0.00
September 305.58 80.53 225.05 594.65 65.49 0.00 0.00 0.00
October 474.12 246.97 227.15 848.18 122.63 0.00 0.00 0.00
November 603.34 415.41 187.94 929.53 266.19 0.00 0.00 0.00
December 623.84 448.01 175.83 919.04 353.01 0.00 0.00 0.00
                 
Annual Sum or Average 395.31 190.51 204.81 656.55 181.80 0.00 0.00 0.00
Minimum of Months 206.80 1.93 175.83 428.42 25.89 0.00 0.00 0.00
Maximum of Months 638.45 455.32 227.15 929.53 391.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 638.45 455.32 183.12 906.90 391.14 0.00 0.00 0.00
February 579.04 374.80 204.24 839.18 338.66 0.00 0.00 0.00
March 369.67 166.83 202.84 549.37 300.04 0.00 0.00 0.00
April 273.99 64.20 209.79 450.50 192.11 0.00 0.00 0.00
May 209.35 8.90 200.45 428.42 52.73 0.00 0.00 0.00
June 206.80 1.93 204.88 436.34 42.12 0.00 0.00 0.00
July 216.49 3.98 212.51 452.90 25.89 0.00 0.00 0.00
August 254.69 30.57 224.12 534.28 41.51 0.00 0.00 0.00
September 305.58 80.53 225.05 594.65 65.49 0.00 0.00 0.00
October 474.12 246.97 227.15 848.18 122.63 0.00 0.00 0.00
November 603.34 415.41 187.93 929.53 266.19 0.00 0.00 0.00
December 623.84 448.01 175.83 919.04 353.01 0.00 0.00 0.00
                 
Annual Sum or Average 395.31 190.51 204.81 656.55 181.80 0.00 0.00 0.00
Minimum of Months 206.80 1.93 175.83 428.42 25.89 0.00 0.00 0.00
Maximum of Months 638.45 455.32 227.15 929.53 391.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 638.42 455.31 183.12 906.87 391.13 0.00 0.00 0.00
February 579.01 374.79 204.23 839.15 338.64 0.00 0.00 0.00
March 369.65 166.83 202.83 549.35 300.02 0.00 0.00 0.00
April 273.98 64.20 209.78 450.48 192.11 0.00 0.00 0.00
May 209.34 8.90 200.45 428.41 52.73 0.00 0.00 0.00
June 206.80 1.93 204.87 436.32 42.12 0.00 0.00 0.00
July 216.48 3.98 212.50 452.88 25.89 0.00 0.00 0.00
August 254.68 30.57 224.11 534.26 41.51 0.00 0.00 0.00
September 305.57 80.53 225.04 594.63 65.49 0.00 0.00 0.00
October 474.10 246.96 227.14 848.15 122.63 0.00 0.00 0.00
November 603.32 415.39 187.93 929.50 266.18 0.00 0.00 0.00
December 623.82 447.99 175.83 919.00 352.99 0.00 0.00 0.00
                 
Annual Sum or Average 395.30 190.50 204.80 656.52 181.79 0.00 0.00 0.00
Minimum of Months 206.80 1.93 175.83 428.41 25.89 0.00 0.00 0.00
Maximum of Months 638.42 455.31 227.14 929.50 391.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 335.96 181.67 154.29 410.09 504.87 0.00 0.00 0.00
February 380.38 192.52 187.85 481.08 446.73 0.00 0.00 0.00
March 374.90 165.96 208.94 491.82 396.29 0.00 0.00 0.00
April 465.64 214.20 251.43 700.77 263.68 0.00 0.00 0.00
May 387.23 126.14 261.09 722.78 80.98 0.00 0.00 0.00
June 430.17 150.84 279.33 815.65 74.61 0.00 0.00 0.00
July 392.66 108.92 283.75 738.40 59.33 0.00 0.00 0.00
August 397.03 121.54 275.50 742.57 84.66 0.00 0.00 0.00
September 365.60 125.42 240.18 661.24 93.06 0.00 0.00 0.00
October 374.30 161.73 212.57 644.17 166.61 0.00 0.00 0.00
November 320.82 161.23 159.59 445.29 361.01 0.00 0.00 0.00
December 308.60 164.11 144.49 387.97 481.94 0.00 0.00 0.00
                 
Annual Sum or Average 377.56 155.82 221.74 603.92 250.12 0.00 0.00 0.00
Minimum of Months 308.60 108.92 144.49 387.97 59.33 0.00 0.00 0.00
Maximum of Months 465.64 214.20 283.75 815.65 504.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 335.96 181.67 154.29 410.09 504.87 0.00 0.00 0.00
February 380.38 192.52 187.85 481.08 446.73 0.00 0.00 0.00
March 374.90 165.96 208.94 491.82 396.29 0.00 0.00 0.00
April 465.64 214.20 251.43 700.77 263.68 0.00 0.00 0.00
May 387.23 126.14 261.09 722.78 80.98 0.00 0.00 0.00
June 430.17 150.84 279.33 815.65 74.61 0.00 0.00 0.00
July 392.66 108.92 283.75 738.40 59.33 0.00 0.00 0.00
August 397.03 121.54 275.50 742.57 84.66 0.00 0.00 0.00
September 365.60 125.42 240.18 661.24 93.06 0.00 0.00 0.00
October 374.30 161.73 212.57 644.17 166.61 0.00 0.00 0.00
November 320.82 161.23 159.59 445.29 361.01 0.00 0.00 0.00
December 308.60 164.11 144.49 387.97 481.94 0.00 0.00 0.00
                 
Annual Sum or Average 377.56 155.82 221.74 603.92 250.12 0.00 0.00 0.00
Minimum of Months 308.60 108.92 144.49 387.97 59.33 0.00 0.00 0.00
Maximum of Months 465.64 214.20 283.75 815.65 504.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 335.95 181.66 154.29 410.08 504.87 0.00 0.00 0.00
February 380.37 192.52 187.85 481.08 446.72 0.00 0.00 0.00
March 374.89 165.96 208.94 491.81 396.28 0.00 0.00 0.00
April 465.63 214.20 251.43 700.76 263.68 0.00 0.00 0.00
May 387.22 126.14 261.08 722.77 80.97 0.00 0.00 0.00
June 430.16 150.83 279.33 815.63 74.61 0.00 0.00 0.00
July 392.66 108.92 283.74 738.39 59.33 0.00 0.00 0.00
August 397.03 121.53 275.49 742.56 84.66 0.00 0.00 0.00
September 365.59 125.42 240.18 661.23 93.06 0.00 0.00 0.00
October 374.29 161.73 212.56 644.15 166.60 0.00 0.00 0.00
November 320.81 161.23 159.59 445.28 361.01 0.00 0.00 0.00
December 308.59 164.11 144.49 387.97 481.93 0.00 0.00 0.00
                 
Annual Sum or Average 377.55 155.81 221.74 603.91 250.12 0.00 0.00 0.00
Minimum of Months 308.59 108.92 144.49 387.97 59.33 0.00 0.00 0.00
Maximum of Months 465.63 214.20 283.74 815.63 504.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 552.27 0.00 552.27 417.00 1921.49 0.00 0.00 0.00
February 651.54 0.00 651.54 560.58 1613.61 0.00 0.00 0.00
March 755.84 0.00 755.84 795.23 1389.02 0.00 0.00 0.00
April 892.06 3.66 888.40 1236.50 870.34 0.00 0.00 0.00
May 1010.43 36.96 973.47 2050.53 246.07 0.00 0.00 0.00
June 1149.07 79.56 1069.51 2423.87 209.55 0.00 0.00 0.00
July 1115.10 42.48 1072.62 2333.42 137.13 0.00 0.00 0.00
August 998.59 7.85 990.74 2109.32 193.92 0.00 0.00 0.00
September 862.56 0.07 862.49 1681.73 279.46 0.00 0.00 0.00
October 749.55 0.00 749.55 1356.96 539.25 0.00 0.00 0.00
November 569.03 0.00 569.03 632.51 1230.14 0.00 0.00 0.00
December 513.39 0.00 513.39 445.32 1641.96 0.00 0.00 0.00
                 
Annual Sum or Average 819.11 14.26 804.85 1341.58 852.05 0.00 0.00 0.00
Minimum of Months 513.39 0.00 513.39 417.00 137.13 0.00 0.00 0.00
Maximum of Months 1149.07 79.56 1072.62 2423.87 1921.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 947.54 482.49 465.05 1102.34 1229.41 0.00 0.00 0.00
February 1055.12 509.38 545.73 1303.02 1038.52 0.00 0.00 0.00
March 1241.16 598.58 642.58 1659.13 900.97 0.00 0.00 0.00
April 1362.03 616.01 746.02 2072.66 589.73 0.00 0.00 0.00
May 1403.89 608.75 795.14 2563.42 175.77 0.00 0.00 0.00
June 1423.78 564.63 859.15 2695.00 149.09 0.00 0.00 0.00
July 1372.73 502.34 870.38 2599.29 99.18 0.00 0.00 0.00
August 1264.93 434.89 830.03 2399.52 139.01 0.00 0.00 0.00
September 1120.49 385.22 735.27 2023.76 198.18 0.00 0.00 0.00
October 1107.28 467.27 640.01 1898.09 366.58 0.00 0.00 0.00
November 980.33 500.11 480.23 1344.62 802.71 0.00 0.00 0.00
December 771.86 349.63 422.22 940.93 1072.87 0.00 0.00 0.00
                 
Annual Sum or Average 1171.32 501.38 669.94 1886.60 561.01 0.00 0.00 0.00
Minimum of Months 771.86 349.63 422.22 940.93 99.18 0.00 0.00 0.00
Maximum of Months 1423.78 616.01 870.38 2695.00 1229.41 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3192.21 2276.60 915.61 4498.54 1902.15 0.00 0.00 0.00
February 2895.15 1873.98 1021.17 4171.26 1630.79 0.00 0.00 0.00
March 1848.33 834.15 1014.17 2742.74 1419.16 0.00 0.00 0.00
April 1369.96 321.01 1048.94 2255.45 925.11 0.00 0.00 0.00
May 1046.75 44.49 1002.26 2145.86 255.24 0.00 0.00 0.00
June 1034.01 9.64 1024.37 2192.06 213.94 0.00 0.00 0.00
July 1082.44 19.90 1062.54 2279.53 133.55 0.00 0.00 0.00
August 1273.43 152.85 1120.58 2682.61 209.52 0.00 0.00 0.00
September 1527.90 402.67 1125.23 2963.48 313.58 0.00 0.00 0.00
October 2370.55 1234.83 1135.72 4212.04 607.37 0.00 0.00 0.00
November 3016.68 2077.02 939.66 4622.45 1284.64 0.00 0.00 0.00
December 3119.17 2240.02 879.15 4574.42 1687.28 0.00 0.00 0.00
                 
Annual Sum or Average 1976.55 952.52 1024.03 3273.99 877.87 0.00 0.00 0.00
Minimum of Months 1034.01 9.64 879.15 2145.86 133.55 0.00 0.00 0.00
Maximum of Months 3192.21 2276.60 1135.72 4622.45 1902.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1007.86 544.99 462.86 1269.64 1331.50 0.00 0.00 0.00
February 1141.12 577.56 563.55 1491.62 1143.10 0.00 0.00 0.00
March 1124.69 497.87 626.82 1524.17 990.68 0.00 0.00 0.00
April 1396.89 642.60 754.30 2151.15 664.25 0.00 0.00 0.00
May 1161.68 378.42 783.26 2185.48 209.76 0.00 0.00 0.00
June 1290.49 452.51 837.99 2474.34 185.80 0.00 0.00 0.00
July 1177.98 326.75 851.23 2261.68 129.42 0.00 0.00 0.00
August 1191.09 364.61 826.48 2289.45 176.16 0.00 0.00 0.00
September 1096.79 376.25 720.54 2001.11 233.57 0.00 0.00 0.00
October 1122.89 485.19 637.70 1963.12 423.09 0.00 0.00 0.00
November 962.45 483.69 478.76 1387.96 895.80 0.00 0.00 0.00
December 925.79 492.32 433.47 1228.46 1159.22 0.00 0.00 0.00
                 
Annual Sum or Average 1132.66 467.45 665.21 1853.66 625.77 0.00 0.00 0.00
Minimum of Months 925.79 326.75 433.47 1228.46 129.42 0.00 0.00 0.00
Maximum of Months 1396.89 642.60 851.23 2474.34 1331.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 552.27 0.00 552.27 452.88 1768.13 0.00 0.00 0.00
February 651.54 0.00 651.54 590.91 1487.83 0.00 0.00 0.00
March 755.84 0.00 755.84 813.38 1305.81 0.00 0.00 0.00
April 892.06 3.66 888.40 1231.88 846.84 0.00 0.00 0.00
May 1010.43 36.96 973.47 2017.80 261.14 0.00 0.00 0.00
June 1149.07 79.56 1069.51 2385.34 226.21 0.00 0.00 0.00
July 1115.10 42.48 1072.62 2289.82 153.12 0.00 0.00 0.00
August 998.59 7.85 990.74 2074.64 208.06 0.00 0.00 0.00
September 862.56 0.07 862.49 1649.06 291.46 0.00 0.00 0.00
October 749.55 0.00 749.55 1343.39 528.26 0.00 0.00 0.00
November 569.03 0.00 569.03 656.83 1141.31 0.00 0.00 0.00
December 513.39 0.00 513.39 474.32 1511.06 0.00 0.00 0.00
                 
Annual Sum or Average 819.11 14.26 804.85 1336.14 807.22 0.00 0.00 0.00
Minimum of Months 513.39 0.00 513.39 452.88 153.12 0.00 0.00 0.00
Maximum of Months 1149.07 79.56 1072.62 2385.34 1768.13 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 947.54 482.49 465.05 1145.73 1128.15 0.00 0.00 0.00
February 1055.12 509.38 545.73 1337.32 959.10 0.00 0.00 0.00
March 1241.16 598.58 642.58 1676.24 852.00 0.00 0.00 0.00
April 1362.03 616.01 746.02 2072.49 577.08 0.00 0.00 0.00
May 1403.89 608.75 795.14 2546.67 184.48 0.00 0.00 0.00
June 1423.78 564.63 859.15 2676.66 159.55 0.00 0.00 0.00
July 1372.73 502.34 870.38 2578.52 109.20 0.00 0.00 0.00
August 1264.93 434.89 830.03 2383.13 147.79 0.00 0.00 0.00
September 1120.49 385.22 735.27 2009.74 204.76 0.00 0.00 0.00
October 1107.28 467.27 640.01 1893.72 359.59 0.00 0.00 0.00
November 980.33 500.11 480.23 1364.93 754.26 0.00 0.00 0.00
December 771.86 349.63 422.22 971.47 987.86 0.00 0.00 0.00
                 
Annual Sum or Average 1171.32 501.38 669.94 1891.01 533.06 0.00 0.00 0.00
Minimum of Months 771.86 349.63 422.22 971.47 109.20 0.00 0.00 0.00
Maximum of Months 1423.78 616.01 870.38 2676.66 1128.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 3192.21 2276.60 915.61 4532.25 1775.08 0.00 0.00 0.00
February 2895.15 1873.98 1021.17 4201.77 1522.75 0.00 0.00 0.00
March 1848.33 834.15 1014.17 2753.90 1344.56 0.00 0.00 0.00
April 1369.96 321.01 1048.94 2245.11 903.10 0.00 0.00 0.00
May 1046.75 44.49 1002.26 2112.97 270.56 0.00 0.00 0.00
June 1034.01 9.64 1024.37 2154.77 231.87 0.00 0.00 0.00
July 1082.44 19.90 1062.54 2234.18 148.90 0.00 0.00 0.00
August 1273.43 152.85 1120.58 2646.90 224.37 0.00 0.00 0.00
September 1527.90 402.67 1125.23 2931.72 325.47 0.00 0.00 0.00
October 2370.55 1234.83 1135.72 4192.24 599.62 0.00 0.00 0.00
November 3016.68 2077.02 939.66 4634.23 1222.65 0.00 0.00 0.00
December 3119.17 2240.02 879.15 4598.21 1578.27 0.00 0.00 0.00
                 
Annual Sum or Average 1976.55 952.52 1024.03 3265.25 841.95 0.00 0.00 0.00
Minimum of Months 1034.01 9.64 879.15 2112.97 148.90 0.00 0.00 0.00
Maximum of Months 3192.21 2276.60 1135.72 4634.23 1775.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1007.86 544.99 462.86 1286.26 1245.56 0.00 0.00 0.00
February 1141.12 577.56 563.55 1503.71 1071.22 0.00 0.00 0.00
March 1124.69 497.87 626.82 1527.88 941.57 0.00 0.00 0.00
April 1396.89 642.60 754.30 2140.36 648.64 0.00 0.00 0.00
May 1161.68 378.42 783.26 2164.25 217.75 0.00 0.00 0.00
June 1290.49 452.51 837.99 2450.25 194.66 0.00 0.00 0.00
July 1177.98 326.75 851.23 2235.88 137.63 0.00 0.00 0.00
August 1191.09 364.61 826.48 2267.13 184.71 0.00 0.00 0.00
September 1096.79 376.25 720.54 1981.86 239.58 0.00 0.00 0.00
October 1122.89 485.19 637.70 1951.46 416.69 0.00 0.00 0.00
November 962.45 483.69 478.76 1395.22 847.65 0.00 0.00 0.00
December 925.79 492.32 433.47 1240.96 1084.11 0.00 0.00 0.00
                 
Annual Sum or Average 1132.66 467.45 665.21 1846.64 599.94 0.00 0.00 0.00
Minimum of Months 925.79 326.75 433.47 1240.96 137.63 0.00 0.00 0.00
Maximum of Months 1396.89 642.60 851.23 2450.25 1245.56 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.295841E+09 0.00 0.295841E+09 0.187556E+09 0.116731E+10
February 0.315245E+09 0.00 0.315245E+09 0.239175E+09 0.896700E+09
March 0.404895E+09 0.00 0.404895E+09 0.393760E+09 0.842947E+09
April 0.462450E+09 1898057.14 0.460552E+09 0.622951E+09 0.487128E+09
May 0.541273E+09 19798542.17 0.521475E+09 0.109476E+10 0.136957E+09
June 0.595687E+09 41246703.62 0.554440E+09 0.125356E+10 0.105069E+09
July 0.597345E+09 22757759.15 0.574588E+09 0.124418E+10 69551883.94
August 0.534933E+09 4207320.32 0.530726E+09 0.111735E+10 0.103814E+09
September 0.447157E+09 34439.89 0.447123E+09 0.863578E+09 0.159059E+09
October 0.401523E+09 0.00 0.401523E+09 0.713333E+09 0.315099E+09
November 0.294987E+09 0.00 0.294987E+09 0.297294E+09 0.733952E+09
December 0.275018E+09 0.00 0.275018E+09 0.202062E+09 0.102941E+10
           
Annual Sum or Average 0.516636E+10 89942822.29 0.507641E+10 0.822955E+10 0.604699E+10
Minimum of Months 0.275018E+09 0.00 0.275018E+09 0.187556E+09 69551883.94
Maximum of Months 0.597345E+09 41246703.62 0.574588E+09 0.125356E+10 0.116731E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.295841E+09 0.00 0.295841E+09 0.187556E+09 0.116731E+10
February 0.315244E+09 0.00 0.315244E+09 0.239175E+09 0.896700E+09
March 0.404895E+09 0.00 0.404895E+09 0.393759E+09 0.842947E+09
April 0.462450E+09 1898054.86 0.460552E+09 0.622950E+09 0.487128E+09
May 0.541273E+09 19798518.42 0.521474E+09 0.109476E+10 0.136957E+09
June 0.595687E+09 41246654.13 0.554440E+09 0.125355E+10 0.105069E+09
July 0.597345E+09 22757731.84 0.574587E+09 0.124418E+10 69551798.78
August 0.534933E+09 4207315.27 0.530726E+09 0.111735E+10 0.103814E+09
September 0.447157E+09 34439.85 0.447122E+09 0.863577E+09 0.159059E+09
October 0.401523E+09 0.00 0.401523E+09 0.713332E+09 0.315099E+09
November 0.294987E+09 0.00 0.294987E+09 0.297294E+09 0.733952E+09
December 0.275018E+09 0.00 0.275018E+09 0.202061E+09 0.102941E+10
           
Annual Sum or Average 0.516635E+10 89942714.37 0.507641E+10 0.822954E+10 0.604699E+10
Minimum of Months 0.275018E+09 0.00 0.275018E+09 0.187556E+09 69551798.78
Maximum of Months 0.597345E+09 41246654.13 0.574587E+09 0.125355E+10 0.116731E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.295841E+09 0.00 0.295841E+09 0.187556E+09 0.116731E+10
February 0.315245E+09 0.00 0.315245E+09 0.239175E+09 0.896700E+09
March 0.404895E+09 0.00 0.404895E+09 0.393760E+09 0.842947E+09
April 0.462450E+09 1898057.14 0.460552E+09 0.622951E+09 0.487128E+09
May 0.541273E+09 19798542.17 0.521475E+09 0.109476E+10 0.136957E+09
June 0.595687E+09 41246703.62 0.554440E+09 0.125356E+10 0.105069E+09
July 0.597345E+09 22757759.15 0.574588E+09 0.124418E+10 69551883.94
August 0.534933E+09 4207320.32 0.530726E+09 0.111735E+10 0.103814E+09
September 0.447157E+09 34439.89 0.447123E+09 0.863578E+09 0.159059E+09
October 0.401523E+09 0.00 0.401523E+09 0.713333E+09 0.315099E+09
November 0.294987E+09 0.00 0.294987E+09 0.297294E+09 0.733952E+09
December 0.275018E+09 0.00 0.275018E+09 0.202062E+09 0.102941E+10
           
Annual Sum or Average 0.516636E+10 89942822.29 0.507641E+10 0.822955E+10 0.604699E+10
Minimum of Months 0.275018E+09 0.00 0.275018E+09 0.187556E+09 69551883.94
Maximum of Months 0.597345E+09 41246703.62 0.574588E+09 0.125356E+10 0.116731E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.295841E+09 0.00 0.295841E+09 0.187556E+09 0.116731E+10
February 0.315244E+09 0.00 0.315244E+09 0.239175E+09 0.896700E+09
March 0.404895E+09 0.00 0.404895E+09 0.393759E+09 0.842947E+09
April 0.462450E+09 1898054.86 0.460552E+09 0.622950E+09 0.487128E+09
May 0.541273E+09 19798518.42 0.521474E+09 0.109476E+10 0.136957E+09
June 0.595687E+09 41246654.13 0.554440E+09 0.125355E+10 0.105069E+09
July 0.597345E+09 22757731.84 0.574587E+09 0.124418E+10 69551798.78
August 0.534933E+09 4207315.27 0.530726E+09 0.111735E+10 0.103814E+09
September 0.447157E+09 34439.85 0.447122E+09 0.863577E+09 0.159059E+09
October 0.401523E+09 0.00 0.401523E+09 0.713332E+09 0.315099E+09
November 0.294987E+09 0.00 0.294987E+09 0.297294E+09 0.733952E+09
December 0.275018E+09 0.00 0.275018E+09 0.202061E+09 0.102941E+10
           
Annual Sum or Average 0.516635E+10 89942714.37 0.507641E+10 0.822954E+10 0.604699E+10
Minimum of Months 0.275018E+09 0.00 0.275018E+09 0.187556E+09 69551798.78
Maximum of Months 0.597345E+09 41246654.13 0.574587E+09 0.125355E+10 0.116731E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.295829E+09 0.00 0.295829E+09 0.187549E+09 0.116726E+10
February 0.315232E+09 0.00 0.315232E+09 0.239166E+09 0.896664E+09
March 0.404879E+09 0.00 0.404879E+09 0.393744E+09 0.842913E+09
April 0.462432E+09 1897980.64 0.460534E+09 0.622926E+09 0.487108E+09
May 0.541251E+09 19797744.20 0.521454E+09 0.109471E+10 0.136952E+09
June 0.595663E+09 41245041.19 0.554418E+09 0.125350E+10 0.105065E+09
July 0.597321E+09 22756841.91 0.574564E+09 0.124413E+10 69549080.70
August 0.534912E+09 4207150.75 0.530705E+09 0.111730E+10 0.103810E+09
September 0.447139E+09 34438.50 0.447104E+09 0.863543E+09 0.159053E+09
October 0.401507E+09 0.00 0.401507E+09 0.713304E+09 0.315086E+09
November 0.294975E+09 0.00 0.294975E+09 0.297282E+09 0.733922E+09
December 0.275007E+09 0.00 0.275007E+09 0.202053E+09 0.102937E+10
           
Annual Sum or Average 0.516615E+10 89939197.20 0.507621E+10 0.822922E+10 0.604675E+10
Minimum of Months 0.275007E+09 0.00 0.275007E+09 0.187549E+09 69549080.70
Maximum of Months 0.597321E+09 41245041.19 0.574564E+09 0.125350E+10 0.116726E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.845971E+09 0.430772E+09 0.415200E+09 0.971984E+09 0.118962E+10
February 0.850854E+09 0.410770E+09 0.440084E+09 0.104196E+10 0.907324E+09
March 0.110812E+10 0.534417E+09 0.573705E+09 0.148730E+10 0.853255E+09
April 0.117681E+10 0.532238E+09 0.644570E+09 0.181361E+10 0.505373E+09
May 0.125340E+10 0.543500E+09 0.709904E+09 0.231790E+10 0.150931E+09
June 0.123016E+10 0.487847E+09 0.742311E+09 0.235700E+10 0.110486E+09
July 0.122558E+10 0.448497E+09 0.777086E+09 0.235275E+10 67260943.12
August 0.112934E+10 0.388275E+09 0.741062E+09 0.217101E+10 99146211.85
September 0.968114E+09 0.332835E+09 0.635280E+09 0.176819E+10 0.172533E+09
October 0.988586E+09 0.417180E+09 0.571406E+09 0.171516E+10 0.329688E+09
November 0.847016E+09 0.432096E+09 0.414920E+09 0.116303E+10 0.739202E+09
December 0.689122E+09 0.312157E+09 0.376965E+09 0.828881E+09 0.103917E+10
           
Annual Sum or Average 0.123131E+11 0.527058E+10 0.704249E+10 0.199888E+11 0.616399E+10
Minimum of Months 0.689122E+09 0.312157E+09 0.376965E+09 0.828881E+09 67260943.12
Maximum of Months 0.125340E+10 0.543500E+09 0.777086E+09 0.235700E+10 0.118962E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.845971E+09 0.430772E+09 0.415200E+09 0.971984E+09 0.118962E+10
February 0.850854E+09 0.410770E+09 0.440084E+09 0.104196E+10 0.907324E+09
March 0.110812E+10 0.534417E+09 0.573705E+09 0.148730E+10 0.853255E+09
April 0.117681E+10 0.532238E+09 0.644570E+09 0.181361E+10 0.505373E+09
May 0.125340E+10 0.543500E+09 0.709904E+09 0.231790E+10 0.150931E+09
June 0.123016E+10 0.487847E+09 0.742311E+09 0.235700E+10 0.110486E+09
July 0.122558E+10 0.448497E+09 0.777086E+09 0.235275E+10 67260943.12
August 0.112934E+10 0.388275E+09 0.741062E+09 0.217101E+10 99146211.85
September 0.968114E+09 0.332835E+09 0.635280E+09 0.176819E+10 0.172533E+09
October 0.988586E+09 0.417180E+09 0.571406E+09 0.171516E+10 0.329688E+09
November 0.847016E+09 0.432096E+09 0.414920E+09 0.116303E+10 0.739202E+09
December 0.689122E+09 0.312157E+09 0.376965E+09 0.828881E+09 0.103917E+10
           
Annual Sum or Average 0.123131E+11 0.527058E+10 0.704249E+10 0.199888E+11 0.616399E+10
Minimum of Months 0.689122E+09 0.312157E+09 0.376965E+09 0.828881E+09 67260943.12
Maximum of Months 0.125340E+10 0.543500E+09 0.777086E+09 0.235700E+10 0.118962E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.845956E+09 0.430764E+09 0.415192E+09 0.971966E+09 0.118960E+10
February 0.850839E+09 0.410762E+09 0.440076E+09 0.104194E+10 0.907308E+09
March 0.110810E+10 0.534407E+09 0.573695E+09 0.148728E+10 0.853240E+09
April 0.117679E+10 0.532228E+09 0.644558E+09 0.181357E+10 0.505363E+09
May 0.125338E+10 0.543490E+09 0.709891E+09 0.231785E+10 0.150929E+09
June 0.123014E+10 0.487838E+09 0.742298E+09 0.235695E+10 0.110484E+09
July 0.122556E+10 0.448489E+09 0.777071E+09 0.235271E+10 67259714.12
August 0.112932E+10 0.388268E+09 0.741048E+09 0.217097E+10 99144400.23
September 0.968097E+09 0.332828E+09 0.635268E+09 0.176816E+10 0.172530E+09
October 0.988568E+09 0.417173E+09 0.571395E+09 0.171513E+10 0.329682E+09
November 0.847001E+09 0.432088E+09 0.414912E+09 0.116301E+10 0.739189E+09
December 0.689109E+09 0.312151E+09 0.376958E+09 0.828866E+09 0.103915E+10
           
Annual Sum or Average 0.123128E+11 0.527049E+10 0.704236E+10 0.199884E+11 0.616388E+10
Minimum of Months 0.689109E+09 0.312151E+09 0.376958E+09 0.828866E+09 67259714.12
Maximum of Months 0.125338E+10 0.543490E+09 0.777071E+09 0.235695E+10 0.118960E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.171002E+10 0.121954E+10 0.490479E+09 0.242906E+10 0.104764E+10
February 0.140081E+10 0.906719E+09 0.494088E+09 0.203015E+10 0.819278E+09
March 0.990124E+09 0.446844E+09 0.543280E+09 0.147143E+10 0.803616E+09
April 0.710194E+09 0.166416E+09 0.543778E+09 0.116769E+10 0.497961E+09
May 0.560728E+09 23830137.60 0.536897E+09 0.114749E+10 0.141240E+09
June 0.536035E+09 4996364.11 0.531039E+09 0.113098E+10 0.109170E+09
July 0.579847E+09 10657518.52 0.569189E+09 0.121305E+10 69341348.81
August 0.682159E+09 81879609.18 0.600279E+09 0.143103E+10 0.111182E+09
September 0.792074E+09 0.208745E+09 0.583329E+09 0.154134E+10 0.169749E+09
October 0.126987E+10 0.661484E+09 0.608389E+09 0.227177E+10 0.328463E+09
November 0.156387E+10 0.107674E+10 0.487128E+09 0.240935E+10 0.689965E+09
December 0.167090E+10 0.119995E+10 0.470949E+09 0.246156E+10 0.945494E+09
           
Annual Sum or Average 0.124666E+11 0.600780E+10 0.645882E+10 0.207049E+11 0.573310E+10
Minimum of Months 0.536035E+09 4996364.11 0.470949E+09 0.113098E+10 69341348.81
Maximum of Months 0.171002E+10 0.121954E+10 0.608389E+09 0.246156E+10 0.104764E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.171002E+10 0.121954E+10 0.490479E+09 0.242905E+10 0.104764E+10
February 0.140081E+10 0.906718E+09 0.494088E+09 0.203015E+10 0.819278E+09
March 0.990123E+09 0.446843E+09 0.543279E+09 0.147143E+10 0.803616E+09
April 0.710194E+09 0.166416E+09 0.543778E+09 0.116769E+10 0.497961E+09
May 0.560727E+09 23830109.01 0.536897E+09 0.114749E+10 0.141240E+09
June 0.536035E+09 4996358.11 0.531038E+09 0.113098E+10 0.109170E+09
July 0.579846E+09 10657505.73 0.569189E+09 0.121305E+10 69341266.73
August 0.682158E+09 81879510.93 0.600279E+09 0.143103E+10 0.111182E+09
September 0.792073E+09 0.208745E+09 0.583328E+09 0.154134E+10 0.169749E+09
October 0.126987E+10 0.661483E+09 0.608389E+09 0.227177E+10 0.328462E+09
November 0.156386E+10 0.107674E+10 0.487127E+09 0.240935E+10 0.689965E+09
December 0.167090E+10 0.119995E+10 0.470948E+09 0.246155E+10 0.945494E+09
           
Annual Sum or Average 0.124666E+11 0.600780E+10 0.645882E+10 0.207049E+11 0.573310E+10
Minimum of Months 0.536035E+09 4996358.11 0.470948E+09 0.113098E+10 69341266.73
Maximum of Months 0.171002E+10 0.121954E+10 0.608389E+09 0.246155E+10 0.104764E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.171002E+10 0.121954E+10 0.490479E+09 0.242906E+10 0.104764E+10
February 0.140081E+10 0.906719E+09 0.494088E+09 0.203015E+10 0.819278E+09
March 0.990124E+09 0.446844E+09 0.543280E+09 0.147143E+10 0.803616E+09
April 0.710194E+09 0.166416E+09 0.543778E+09 0.116769E+10 0.497961E+09
May 0.560728E+09 23830137.60 0.536897E+09 0.114749E+10 0.141240E+09
June 0.536035E+09 4996364.11 0.531039E+09 0.113098E+10 0.109170E+09
July 0.579847E+09 10657518.52 0.569189E+09 0.121305E+10 69341348.81
August 0.682159E+09 81879609.18 0.600279E+09 0.143103E+10 0.111182E+09
September 0.792074E+09 0.208745E+09 0.583329E+09 0.154134E+10 0.169749E+09
October 0.126987E+10 0.661484E+09 0.608389E+09 0.227177E+10 0.328463E+09
November 0.156387E+10 0.107674E+10 0.487128E+09 0.240935E+10 0.689965E+09
December 0.167090E+10 0.119995E+10 0.470949E+09 0.246156E+10 0.945494E+09
           
Annual Sum or Average 0.124666E+11 0.600780E+10 0.645882E+10 0.207049E+11 0.573310E+10
Minimum of Months 0.536035E+09 4996364.11 0.470949E+09 0.113098E+10 69341348.81
Maximum of Months 0.171002E+10 0.121954E+10 0.608389E+09 0.246156E+10 0.104764E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.171002E+10 0.121954E+10 0.490479E+09 0.242905E+10 0.104764E+10
February 0.140081E+10 0.906718E+09 0.494088E+09 0.203015E+10 0.819278E+09
March 0.990123E+09 0.446843E+09 0.543279E+09 0.147143E+10 0.803616E+09
April 0.710194E+09 0.166416E+09 0.543778E+09 0.116769E+10 0.497961E+09
May 0.560727E+09 23830109.01 0.536897E+09 0.114749E+10 0.141240E+09
June 0.536035E+09 4996358.11 0.531038E+09 0.113098E+10 0.109170E+09
July 0.579846E+09 10657505.73 0.569189E+09 0.121305E+10 69341266.73
August 0.682158E+09 81879510.93 0.600279E+09 0.143103E+10 0.111182E+09
September 0.792073E+09 0.208745E+09 0.583328E+09 0.154134E+10 0.169749E+09
October 0.126987E+10 0.661483E+09 0.608389E+09 0.227177E+10 0.328462E+09
November 0.156386E+10 0.107674E+10 0.487127E+09 0.240935E+10 0.689965E+09
December 0.167090E+10 0.119995E+10 0.470948E+09 0.246155E+10 0.945494E+09
           
Annual Sum or Average 0.124666E+11 0.600780E+10 0.645882E+10 0.207049E+11 0.573310E+10
Minimum of Months 0.536035E+09 4996358.11 0.470948E+09 0.113098E+10 69341266.73
Maximum of Months 0.171002E+10 0.121954E+10 0.608389E+09 0.246155E+10 0.104764E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170995E+10 0.121949E+10 0.490460E+09 0.242896E+10 0.104760E+10
February 0.140075E+10 0.906682E+09 0.494068E+09 0.203007E+10 0.819245E+09
March 0.990084E+09 0.446826E+09 0.543258E+09 0.147137E+10 0.803583E+09
April 0.710166E+09 0.166409E+09 0.543756E+09 0.116765E+10 0.497941E+09
May 0.560705E+09 23829177.14 0.536876E+09 0.114744E+10 0.141234E+09
June 0.536013E+09 4996162.73 0.531017E+09 0.113094E+10 0.109165E+09
July 0.579823E+09 10657088.97 0.569166E+09 0.121300E+10 69338554.05
August 0.682131E+09 81876309.07 0.600255E+09 0.143097E+10 0.111178E+09
September 0.792042E+09 0.208737E+09 0.583305E+09 0.154128E+10 0.169742E+09
October 0.126982E+10 0.661457E+09 0.608365E+09 0.227168E+10 0.328449E+09
November 0.156380E+10 0.107669E+10 0.487108E+09 0.240926E+10 0.689937E+09
December 0.167083E+10 0.119990E+10 0.470930E+09 0.246146E+10 0.945456E+09
           
Annual Sum or Average 0.124661E+11 0.600756E+10 0.645856E+10 0.207041E+11 0.573287E+10
Minimum of Months 0.536013E+09 4996162.73 0.470930E+09 0.113094E+10 69338554.05
Maximum of Months 0.170995E+10 0.121949E+10 0.608365E+09 0.246146E+10 0.104760E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.899823E+09 0.486575E+09 0.413249E+09 0.109839E+10 0.135226E+10
February 0.920207E+09 0.465752E+09 0.454455E+09 0.116384E+10 0.108073E+10
March 0.100413E+10 0.444504E+09 0.559628E+09 0.131728E+10 0.106142E+10
April 0.120693E+10 0.555209E+09 0.651718E+09 0.181639E+10 0.683469E+09
May 0.103716E+10 0.337857E+09 0.699303E+09 0.193589E+10 0.216887E+09
June 0.111500E+10 0.390971E+09 0.724027E+09 0.211416E+10 0.193396E+09
July 0.105171E+10 0.291728E+09 0.759983E+09 0.197774E+10 0.158914E+09
August 0.106341E+10 0.325525E+09 0.737888E+09 0.198890E+10 0.226752E+09
September 0.947636E+09 0.325084E+09 0.622551E+09 0.171394E+10 0.241212E+09
October 0.100252E+10 0.433179E+09 0.569344E+09 0.172533E+10 0.446240E+09
November 0.831563E+09 0.417910E+09 0.413653E+09 0.115418E+10 0.935744E+09
December 0.826555E+09 0.439551E+09 0.387004E+09 0.103915E+10 0.129084E+10
           
Annual Sum or Average 0.119066E+11 0.491384E+10 0.699280E+10 0.190452E+11 0.788785E+10
Minimum of Months 0.826555E+09 0.291728E+09 0.387004E+09 0.103915E+10 0.158914E+09
Maximum of Months 0.120693E+10 0.555209E+09 0.759983E+09 0.211416E+10 0.135226E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.899823E+09 0.486575E+09 0.413249E+09 0.109839E+10 0.135226E+10
February 0.920207E+09 0.465752E+09 0.454455E+09 0.116384E+10 0.108073E+10
March 0.100413E+10 0.444504E+09 0.559628E+09 0.131728E+10 0.106142E+10
April 0.120693E+10 0.555209E+09 0.651718E+09 0.181639E+10 0.683469E+09
May 0.103716E+10 0.337857E+09 0.699303E+09 0.193589E+10 0.216887E+09
June 0.111500E+10 0.390971E+09 0.724027E+09 0.211416E+10 0.193396E+09
July 0.105171E+10 0.291728E+09 0.759983E+09 0.197774E+10 0.158914E+09
August 0.106341E+10 0.325525E+09 0.737888E+09 0.198890E+10 0.226752E+09
September 0.947636E+09 0.325084E+09 0.622551E+09 0.171394E+10 0.241212E+09
October 0.100252E+10 0.433179E+09 0.569344E+09 0.172533E+10 0.446240E+09
November 0.831563E+09 0.417910E+09 0.413653E+09 0.115418E+10 0.935744E+09
December 0.826555E+09 0.439551E+09 0.387004E+09 0.103915E+10 0.129084E+10
           
Annual Sum or Average 0.119066E+11 0.491384E+10 0.699280E+10 0.190452E+11 0.788785E+10
Minimum of Months 0.826555E+09 0.291728E+09 0.387004E+09 0.103915E+10 0.158914E+09
Maximum of Months 0.120693E+10 0.555209E+09 0.759983E+09 0.211416E+10 0.135226E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.899807E+09 0.486566E+09 0.413241E+09 0.109837E+10 0.135223E+10
February 0.920190E+09 0.465743E+09 0.454447E+09 0.116382E+10 0.108071E+10
March 0.100411E+10 0.444496E+09 0.559617E+09 0.131726E+10 0.106140E+10
April 0.120690E+10 0.555199E+09 0.651706E+09 0.181636E+10 0.683456E+09
May 0.103714E+10 0.337850E+09 0.699290E+09 0.193586E+10 0.216883E+09
June 0.111498E+10 0.390964E+09 0.724014E+09 0.211412E+10 0.193393E+09
July 0.105169E+10 0.291723E+09 0.759969E+09 0.197771E+10 0.158911E+09
August 0.106339E+10 0.325519E+09 0.737874E+09 0.198886E+10 0.226748E+09
September 0.947618E+09 0.325078E+09 0.622540E+09 0.171391E+10 0.241208E+09
October 0.100250E+10 0.433171E+09 0.569333E+09 0.172530E+10 0.446232E+09
November 0.831548E+09 0.417903E+09 0.413645E+09 0.115416E+10 0.935727E+09
December 0.826540E+09 0.439543E+09 0.386997E+09 0.103913E+10 0.129081E+10
           
Annual Sum or Average 0.119064E+11 0.491376E+10 0.699267E+10 0.190449E+11 0.788771E+10
Minimum of Months 0.826540E+09 0.291723E+09 0.386997E+09 0.103913E+10 0.158911E+09
Maximum of Months 0.120690E+10 0.555199E+09 0.759969E+09 0.211412E+10 0.135223E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.147919E+10 0.00 0.147919E+10 0.111689E+10 0.514652E+10
February 0.157620E+10 0.00 0.157620E+10 0.135615E+10 0.390365E+10
March 0.202445E+10 0.00 0.202445E+10 0.212993E+10 0.372035E+10
April 0.231222E+10 9490170.94 0.230273E+10 0.320502E+10 0.225591E+10
May 0.270633E+10 98991513.86 0.260734E+10 0.549214E+10 0.659064E+09
June 0.297840E+10 0.206231E+09 0.277217E+10 0.628267E+10 0.543162E+09
July 0.298669E+10 0.113787E+09 0.287290E+10 0.624983E+10 0.367293E+09
August 0.267463E+10 21036347.24 0.265360E+10 0.564961E+10 0.519392E+09
September 0.223576E+10 172197.38 0.223559E+10 0.435905E+10 0.724352E+09
October 0.200759E+10 0.00 0.200759E+10 0.363447E+10 0.144433E+10
November 0.147492E+10 0.00 0.147492E+10 0.163947E+10 0.318852E+10
December 0.137507E+10 0.00 0.137507E+10 0.119275E+10 0.439782E+10
           
Annual Sum or Average 0.258315E+11 0.449709E+09 0.253818E+11 0.423080E+11 0.268704E+11
Minimum of Months 0.137507E+10 0.00 0.137507E+10 0.111689E+10 0.367293E+09
Maximum of Months 0.298669E+10 0.206231E+09 0.287290E+10 0.628267E+10 0.514652E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253789E+10 0.129230E+10 0.124559E+10 0.295251E+10 0.329285E+10
February 0.255254E+10 0.123230E+10 0.132024E+10 0.315227E+10 0.251239E+10
March 0.332433E+10 0.160323E+10 0.172110E+10 0.444382E+10 0.241315E+10
April 0.353039E+10 0.159670E+10 0.193369E+10 0.537234E+10 0.152858E+10
May 0.376017E+10 0.163048E+10 0.212969E+10 0.686586E+10 0.470784E+09
June 0.369044E+10 0.146352E+10 0.222691E+10 0.698545E+10 0.386441E+09
July 0.367671E+10 0.134548E+10 0.233123E+10 0.696194E+10 0.265632E+09
August 0.338798E+10 0.116481E+10 0.222316E+10 0.642687E+10 0.372330E+09
September 0.290431E+10 0.998493E+09 0.190582E+10 0.524558E+10 0.513686E+09
October 0.296573E+10 0.125153E+10 0.171420E+10 0.508383E+10 0.981848E+09
November 0.254102E+10 0.129628E+10 0.124475E+10 0.348526E+10 0.208062E+10
December 0.206734E+10 0.936461E+09 0.113088E+10 0.252020E+10 0.287358E+10
           
Annual Sum or Average 0.369388E+11 0.158116E+11 0.211273E+11 0.594959E+11 0.176919E+11
Minimum of Months 0.206734E+10 0.936461E+09 0.113088E+10 0.252020E+10 0.265632E+09
Maximum of Months 0.376017E+10 0.163048E+10 0.233123E+10 0.698545E+10 0.329285E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.855001E+10 0.609764E+10 0.245237E+10 0.120489E+11 0.509472E+10
February 0.700395E+10 0.453354E+10 0.247041E+10 0.100911E+11 0.394521E+10
March 0.495056E+10 0.223419E+10 0.271637E+10 0.734615E+10 0.380107E+10
April 0.355093E+10 0.832070E+09 0.271886E+10 0.584613E+10 0.239788E+10
May 0.280360E+10 0.119149E+09 0.268445E+10 0.574746E+10 0.683639E+09
June 0.268014E+10 24981518.47 0.265516E+10 0.568183E+10 0.554527E+09
July 0.289920E+10 53286948.24 0.284591E+10 0.610548E+10 0.357694E+09
August 0.341075E+10 0.409393E+09 0.300136E+10 0.718511E+10 0.561165E+09
September 0.396032E+10 0.104371E+10 0.291661E+10 0.768135E+10 0.812791E+09
October 0.634929E+10 0.330738E+10 0.304191E+10 0.112815E+11 0.162678E+10
November 0.781924E+10 0.538363E+10 0.243561E+10 0.119814E+11 0.332978E+10
December 0.835440E+10 0.599968E+10 0.235471E+10 0.122521E+11 0.451920E+10
           
Annual Sum or Average 0.623324E+11 0.300386E+11 0.322937E+11 0.103249E+12 0.276844E+11
Minimum of Months 0.268014E+10 24981518.47 0.235471E+10 0.568183E+10 0.357694E+09
Maximum of Months 0.855001E+10 0.609764E+10 0.304191E+10 0.122521E+11 0.509472E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.269944E+10 0.145971E+10 0.123973E+10 0.340060E+10 0.356629E+10
February 0.276059E+10 0.139724E+10 0.136335E+10 0.360853E+10 0.276540E+10
March 0.301236E+10 0.133350E+10 0.167887E+10 0.408234E+10 0.265345E+10
April 0.362074E+10 0.166561E+10 0.195513E+10 0.557577E+10 0.172174E+10
May 0.311145E+10 0.101356E+10 0.209789E+10 0.585360E+10 0.561811E+09
June 0.334496E+10 0.117290E+10 0.217206E+10 0.641350E+10 0.481598E+09
July 0.315510E+10 0.875176E+09 0.227992E+10 0.605767E+10 0.346648E+09
August 0.319021E+10 0.976566E+09 0.221364E+10 0.613207E+10 0.471831E+09
September 0.284288E+10 0.975243E+09 0.186763E+10 0.518686E+10 0.605419E+09
October 0.300754E+10 0.129952E+10 0.170801E+10 0.525803E+10 0.113322E+10
November 0.249466E+10 0.125372E+10 0.124095E+10 0.359760E+10 0.232192E+10
December 0.247964E+10 0.131864E+10 0.116100E+10 0.329030E+10 0.310487E+10
           
Annual Sum or Average 0.357196E+11 0.147414E+11 0.209782E+11 0.584569E+11 0.197342E+11
Minimum of Months 0.247964E+10 0.875176E+09 0.116100E+10 0.329030E+10 0.346648E+09
Maximum of Months 0.362074E+10 0.166561E+10 0.227992E+10 0.641350E+10 0.356629E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.147919E+10 0.00 0.147919E+10 0.121299E+10 0.473577E+10
February 0.157620E+10 0.00 0.157620E+10 0.142952E+10 0.359936E+10
March 0.202445E+10 0.00 0.202445E+10 0.217857E+10 0.349747E+10
April 0.231222E+10 9490170.94 0.230273E+10 0.319303E+10 0.219501E+10
May 0.270633E+10 98991513.86 0.260734E+10 0.540447E+10 0.699444E+09
June 0.297840E+10 0.206231E+09 0.277217E+10 0.618281E+10 0.586346E+09
July 0.298669E+10 0.113787E+09 0.287290E+10 0.613305E+10 0.410117E+09
August 0.267463E+10 21036347.24 0.265360E+10 0.555672E+10 0.557261E+09
September 0.223576E+10 172197.38 0.223559E+10 0.427435E+10 0.755455E+09
October 0.200759E+10 0.00 0.200759E+10 0.359813E+10 0.141488E+10
November 0.147492E+10 0.00 0.147492E+10 0.170251E+10 0.295828E+10
December 0.137507E+10 0.00 0.137507E+10 0.127041E+10 0.404721E+10
           
Annual Sum or Average 0.258315E+11 0.449709E+09 0.253818E+11 0.421366E+11 0.254566E+11
Minimum of Months 0.137507E+10 0.00 0.137507E+10 0.121299E+10 0.410117E+09
Maximum of Months 0.298669E+10 0.206231E+09 0.287290E+10 0.618281E+10 0.473577E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.253789E+10 0.129230E+10 0.124559E+10 0.306873E+10 0.302163E+10
February 0.255254E+10 0.123230E+10 0.132024E+10 0.323525E+10 0.232026E+10
March 0.332433E+10 0.160323E+10 0.172110E+10 0.448963E+10 0.228200E+10
April 0.353039E+10 0.159670E+10 0.193369E+10 0.537190E+10 0.149579E+10
May 0.376017E+10 0.163048E+10 0.212969E+10 0.682100E+10 0.494113E+09
June 0.369044E+10 0.146352E+10 0.222691E+10 0.693790E+10 0.413554E+09
July 0.367671E+10 0.134548E+10 0.233123E+10 0.690630E+10 0.292485E+09
August 0.338798E+10 0.116481E+10 0.222316E+10 0.638297E+10 0.395849E+09
September 0.290431E+10 0.998493E+09 0.190582E+10 0.520925E+10 0.530740E+09
October 0.296573E+10 0.125153E+10 0.171420E+10 0.507214E+10 0.963135E+09
November 0.254102E+10 0.129628E+10 0.124475E+10 0.353790E+10 0.195505E+10
December 0.206734E+10 0.936461E+09 0.113088E+10 0.260199E+10 0.264590E+10
           
Annual Sum or Average 0.369388E+11 0.158116E+11 0.211273E+11 0.596350E+11 0.168105E+11
Minimum of Months 0.206734E+10 0.936461E+09 0.113088E+10 0.260199E+10 0.292485E+09
Maximum of Months 0.376017E+10 0.163048E+10 0.233123E+10 0.693790E+10 0.302163E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.855001E+10 0.609764E+10 0.245237E+10 0.121392E+11 0.475438E+10
February 0.700395E+10 0.453354E+10 0.247041E+10 0.101649E+11 0.368383E+10
March 0.495056E+10 0.223419E+10 0.271637E+10 0.737604E+10 0.360126E+10
April 0.355093E+10 0.832070E+09 0.271886E+10 0.581931E+10 0.234084E+10
May 0.280360E+10 0.119149E+09 0.268445E+10 0.565938E+10 0.724675E+09
June 0.268014E+10 24981518.47 0.265516E+10 0.558515E+10 0.601007E+09
July 0.289920E+10 53286948.24 0.284591E+10 0.598404E+10 0.398824E+09
August 0.341075E+10 0.409393E+09 0.300136E+10 0.708947E+10 0.600963E+09
September 0.396032E+10 0.104371E+10 0.291661E+10 0.759903E+10 0.843614E+09
October 0.634929E+10 0.330738E+10 0.304191E+10 0.112285E+11 0.160603E+10
November 0.781924E+10 0.538363E+10 0.243561E+10 0.120119E+11 0.316911E+10
December 0.835440E+10 0.599968E+10 0.235471E+10 0.123158E+11 0.422724E+10
           
Annual Sum or Average 0.623324E+11 0.300386E+11 0.322937E+11 0.102973E+12 0.265518E+11
Minimum of Months 0.268014E+10 24981518.47 0.235471E+10 0.558515E+10 0.398824E+09
Maximum of Months 0.855001E+10 0.609764E+10 0.304191E+10 0.123158E+11 0.475438E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.269944E+10 0.145971E+10 0.123973E+10 0.344512E+10 0.333611E+10
February 0.276059E+10 0.139724E+10 0.136335E+10 0.363778E+10 0.259151E+10
March 0.301236E+10 0.133350E+10 0.167887E+10 0.409226E+10 0.252190E+10
April 0.362074E+10 0.166561E+10 0.195513E+10 0.554782E+10 0.168127E+10
May 0.311145E+10 0.101356E+10 0.209789E+10 0.579674E+10 0.583225E+09
June 0.334496E+10 0.117290E+10 0.217206E+10 0.635105E+10 0.504565E+09
July 0.315510E+10 0.875176E+09 0.227992E+10 0.598858E+10 0.368616E+09
August 0.319021E+10 0.976566E+09 0.221364E+10 0.607228E+10 0.494731E+09
September 0.284288E+10 0.975243E+09 0.186763E+10 0.513699E+10 0.620989E+09
October 0.300754E+10 0.129952E+10 0.170801E+10 0.522678E+10 0.111605E+10
November 0.249466E+10 0.125372E+10 0.124095E+10 0.361642E+10 0.219711E+10
December 0.247964E+10 0.131864E+10 0.116100E+10 0.332379E+10 0.290369E+10
           
Annual Sum or Average 0.357196E+11 0.147414E+11 0.209782E+11 0.582356E+11 0.189198E+11
Minimum of Months 0.247964E+10 0.875176E+09 0.116100E+10 0.332379E+10 0.368616E+09
Maximum of Months 0.362074E+10 0.166561E+10 0.227992E+10 0.635105E+10 0.333611E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 350.12 2179.09 552.27 0.00 552.27 0.00 0.00
February 494.32 1853.28 651.54 0.00 651.54 0.00 0.00
March 735.06 1573.59 755.85 0.00 755.85 0.00 0.00
April 1201.67 939.67 892.06 3.66 888.40 0.00 0.00
May 2043.66 255.67 1010.43 36.96 973.47 0.00 0.00
June 2418.10 202.68 1149.08 79.56 1069.51 0.00 0.00
July 2322.59 129.84 1115.11 42.48 1072.62 0.00 0.00
August 2085.83 193.80 998.60 7.85 990.74 0.00 0.00
September 1665.84 306.82 862.56 0.07 862.50 0.00 0.00
October 1331.63 588.22 749.55 0.00 749.55 0.00 0.00
November 573.48 1415.79 569.03 0.00 569.03 0.00 0.00
December 377.20 1921.68 513.40 0.00 513.40 0.00 0.00
               
Annual Sum or Average 1304.78 958.74 819.11 14.26 804.85 0.00 0.00
Minimum of Months 350.12 129.84 513.40 0.00 513.40 0.00 0.00
Maximum of Months 2418.10 2179.09 1149.08 79.56 1072.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1088.69 1332.45 947.54 482.49 465.05 0.00 0.00
February 1292.10 1125.15 1055.12 509.38 545.74 0.00 0.00
March 1665.88 955.70 1241.17 598.58 642.59 0.00 0.00
April 2099.07 584.92 1362.04 616.01 746.03 0.00 0.00
May 2596.20 169.05 1403.89 608.76 795.14 0.00 0.00
June 2727.99 127.88 1423.79 564.63 859.15 0.00 0.00
July 2635.23 75.34 1372.73 502.35 870.39 0.00 0.00
August 2431.68 111.05 1264.93 434.89 830.04 0.00 0.00
September 2046.51 199.69 1120.50 385.22 735.27 0.00 0.00
October 1921.09 369.27 1107.28 467.27 640.01 0.00 0.00
November 1346.09 855.55 980.34 500.11 480.23 0.00 0.00
December 928.40 1163.94 771.86 349.64 422.23 0.00 0.00
               
Annual Sum or Average 1901.51 586.37 1171.33 501.38 669.94 0.00 0.00
Minimum of Months 928.40 75.34 771.86 349.64 422.23 0.00 0.00
Maximum of Months 2727.99 1332.45 1423.79 616.01 870.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4534.49 1955.70 3192.22 2276.61 915.61 0.00 0.00
February 4195.87 1693.27 2895.16 1873.99 1021.17 0.00 0.00
March 2746.82 1500.17 1848.33 834.16 1014.18 0.00 0.00
April 2252.48 960.57 1369.96 321.02 1048.95 0.00 0.00
May 2142.10 263.66 1046.75 44.49 1002.26 0.00 0.00
June 2181.67 210.59 1034.01 9.64 1024.37 0.00 0.00
July 2264.49 129.44 1082.44 19.90 1062.55 0.00 0.00
August 2671.40 207.55 1273.43 152.85 1120.58 0.00 0.00
September 2973.25 327.45 1527.91 402.67 1125.24 0.00 0.00
October 4240.88 613.16 2370.56 1234.84 1135.72 0.00 0.00
November 4647.63 1330.94 3016.69 2077.02 939.67 0.00 0.00
December 4595.16 1765.02 3119.19 2240.03 879.15 0.00 0.00
               
Annual Sum or Average 3282.71 908.97 1976.55 952.52 1024.03 0.00 0.00
Minimum of Months 2142.10 129.44 1034.01 9.64 879.15 0.00 0.00
Maximum of Months 4647.63 1955.70 3192.22 2276.61 1135.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1230.27 1514.61 1007.86 545.00 462.87 0.00 0.00
February 1443.25 1340.18 1141.12 577.57 563.56 0.00 0.00
March 1475.44 1188.86 1124.69 497.87 626.82 0.00 0.00
April 2102.30 791.05 1396.90 642.60 754.30 0.00 0.00
May 2168.32 242.93 1161.69 378.42 783.26 0.00 0.00
June 2446.92 223.84 1290.50 452.51 837.99 0.00 0.00
July 2215.20 177.99 1177.98 326.75 851.23 0.00 0.00
August 2227.70 253.98 1191.09 364.61 826.48 0.00 0.00
September 1983.72 279.18 1096.79 376.25 720.54 0.00 0.00
October 1932.49 499.82 1122.89 485.19 637.70 0.00 0.00
November 1335.85 1083.03 962.45 483.69 478.76 0.00 0.00
December 1163.91 1445.82 925.80 492.33 433.47 0.00 0.00
               
Annual Sum or Average 1811.75 750.36 1132.66 467.45 665.22 0.00 0.00
Minimum of Months 1163.91 177.99 925.80 326.75 433.47 0.00 0.00
Maximum of Months 2446.92 1514.61 1396.90 642.60 851.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 417.00 1921.49 552.27 0.00 552.27 0.00 0.00
February 560.58 1613.61 651.54 0.00 651.54 0.00 0.00
March 795.23 1389.02 755.84 0.00 755.84 0.00 0.00
April 1236.50 870.34 892.06 3.66 888.40 0.00 0.00
May 2050.53 246.07 1010.43 36.96 973.47 0.00 0.00
June 2423.87 209.55 1149.07 79.56 1069.51 0.00 0.00
July 2333.42 137.13 1115.10 42.48 1072.62 0.00 0.00
August 2109.32 193.92 998.59 7.85 990.74 0.00 0.00
September 1681.73 279.46 862.56 0.07 862.49 0.00 0.00
October 1356.96 539.25 749.55 0.00 749.55 0.00 0.00
November 632.51 1230.14 569.03 0.00 569.03 0.00 0.00
December 445.32 1641.96 513.39 0.00 513.39 0.00 0.00
               
Annual Sum or Average 1341.58 852.05 819.11 14.26 804.85 0.00 0.00
Minimum of Months 417.00 137.13 513.39 0.00 513.39 0.00 0.00
Maximum of Months 2423.87 1921.49 1149.07 79.56 1072.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1102.34 1229.41 947.54 482.49 465.05 0.00 0.00
February 1303.02 1038.52 1055.12 509.38 545.73 0.00 0.00
March 1659.13 900.97 1241.16 598.58 642.58 0.00 0.00
April 2072.66 589.73 1362.03 616.01 746.02 0.00 0.00
May 2563.42 175.77 1403.89 608.75 795.14 0.00 0.00
June 2695.00 149.09 1423.78 564.63 859.15 0.00 0.00
July 2599.29 99.18 1372.73 502.34 870.38 0.00 0.00
August 2399.52 139.01 1264.93 434.89 830.03 0.00 0.00
September 2023.76 198.18 1120.49 385.22 735.27 0.00 0.00
October 1898.09 366.58 1107.28 467.27 640.01 0.00 0.00
November 1344.62 802.71 980.33 500.11 480.23 0.00 0.00
December 940.93 1072.87 771.86 349.63 422.22 0.00 0.00
               
Annual Sum or Average 1886.60 561.01 1171.32 501.38 669.94 0.00 0.00
Minimum of Months 940.93 99.18 771.86 349.63 422.22 0.00 0.00
Maximum of Months 2695.00 1229.41 1423.78 616.01 870.38 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4498.54 1902.15 3192.21 2276.60 915.61 0.00 0.00
February 4171.26 1630.79 2895.15 1873.98 1021.17 0.00 0.00
March 2742.74 1419.16 1848.33 834.15 1014.17 0.00 0.00
April 2255.45 925.11 1369.96 321.01 1048.94 0.00 0.00
May 2145.86 255.24 1046.75 44.49 1002.26 0.00 0.00
June 2192.06 213.94 1034.01 9.64 1024.37 0.00 0.00
July 2279.53 133.55 1082.44 19.90 1062.54 0.00 0.00
August 2682.61 209.52 1273.43 152.85 1120.58 0.00 0.00
September 2963.48 313.58 1527.90 402.67 1125.23 0.00 0.00
October 4212.04 607.37 2370.55 1234.83 1135.72 0.00 0.00
November 4622.45 1284.64 3016.68 2077.02 939.66 0.00 0.00
December 4574.42 1687.28 3119.17 2240.02 879.15 0.00 0.00
               
Annual Sum or Average 3273.99 877.87 1976.55 952.52 1024.03 0.00 0.00
Minimum of Months 2145.86 133.55 1034.01 9.64 879.15 0.00 0.00
Maximum of Months 4622.45 1902.15 3192.21 2276.60 1135.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1269.64 1331.50 1007.86 544.99 462.86 0.00 0.00
February 1491.62 1143.10 1141.12 577.56 563.55 0.00 0.00
March 1524.17 990.68 1124.69 497.87 626.82 0.00 0.00
April 2151.15 664.25 1396.89 642.60 754.30 0.00 0.00
May 2185.48 209.76 1161.68 378.42 783.26 0.00 0.00
June 2474.34 185.80 1290.49 452.51 837.99 0.00 0.00
July 2261.68 129.42 1177.98 326.75 851.23 0.00 0.00
August 2289.45 176.16 1191.09 364.61 826.48 0.00 0.00
September 2001.11 233.57 1096.79 376.25 720.54 0.00 0.00
October 1963.12 423.09 1122.89 485.19 637.70 0.00 0.00
November 1387.96 895.80 962.45 483.69 478.76 0.00 0.00
December 1228.46 1159.22 925.79 492.32 433.47 0.00 0.00
               
Annual Sum or Average 1853.66 625.77 1132.66 467.45 665.21 0.00 0.00
Minimum of Months 1228.46 129.42 925.79 326.75 433.47 0.00 0.00
Maximum of Months 2474.34 1331.50 1396.89 642.60 851.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 452.88 1768.13 552.27 0.00 552.27 0.00 0.00
February 590.91 1487.83 651.54 0.00 651.54 0.00 0.00
March 813.38 1305.81 755.84 0.00 755.84 0.00 0.00
April 1231.88 846.84 892.06 3.66 888.40 0.00 0.00
May 2017.80 261.14 1010.43 36.96 973.47 0.00 0.00
June 2385.34 226.21 1149.07 79.56 1069.51 0.00 0.00
July 2289.82 153.12 1115.10 42.48 1072.62 0.00 0.00
August 2074.64 208.06 998.59 7.85 990.74 0.00 0.00
September 1649.06 291.46 862.56 0.07 862.49 0.00 0.00
October 1343.39 528.26 749.55 0.00 749.55 0.00 0.00
November 656.83 1141.31 569.03 0.00 569.03 0.00 0.00
December 474.32 1511.06 513.39 0.00 513.39 0.00 0.00
               
Annual Sum or Average 1336.14 807.22 819.11 14.26 804.85 0.00 0.00
Minimum of Months 452.88 153.12 513.39 0.00 513.39 0.00 0.00
Maximum of Months 2385.34 1768.13 1149.07 79.56 1072.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1145.73 1128.15 947.54 482.49 465.05 0.00 0.00
February 1337.32 959.10 1055.12 509.38 545.73 0.00 0.00
March 1676.24 852.00 1241.16 598.58 642.58 0.00 0.00
April 2072.49 577.08 1362.03 616.01 746.02 0.00 0.00
May 2546.67 184.48 1403.89 608.75 795.14 0.00 0.00
June 2676.66 159.55 1423.78 564.63 859.15 0.00 0.00
July 2578.52 109.20 1372.73 502.34 870.38 0.00 0.00
August 2383.13 147.79 1264.93 434.89 830.03 0.00 0.00
September 2009.74 204.76 1120.49 385.22 735.27 0.00 0.00
October 1893.72 359.59 1107.28 467.27 640.01 0.00 0.00
November 1364.93 754.26 980.33 500.11 480.23 0.00 0.00
December 971.47 987.86 771.86 349.63 422.22 0.00 0.00
               
Annual Sum or Average 1891.01 533.06 1171.32 501.38 669.94 0.00 0.00
Minimum of Months 971.47 109.20 771.86 349.63 422.22 0.00 0.00
Maximum of Months 2676.66 1128.15 1423.78 616.01 870.38 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 4532.25 1775.08 3192.21 2276.60 915.61 0.00 0.00
February 4201.77 1522.75 2895.15 1873.98 1021.17 0.00 0.00
March 2753.90 1344.56 1848.33 834.15 1014.17 0.00 0.00
April 2245.11 903.10 1369.96 321.01 1048.94 0.00 0.00
May 2112.97 270.56 1046.75 44.49 1002.26 0.00 0.00
June 2154.77 231.87 1034.01 9.64 1024.37 0.00 0.00
July 2234.18 148.90 1082.44 19.90 1062.54 0.00 0.00
August 2646.90 224.37 1273.43 152.85 1120.58 0.00 0.00
September 2931.72 325.47 1527.90 402.67 1125.23 0.00 0.00
October 4192.24 599.62 2370.55 1234.83 1135.72 0.00 0.00
November 4634.23 1222.65 3016.68 2077.02 939.66 0.00 0.00
December 4598.21 1578.27 3119.17 2240.02 879.15 0.00 0.00
               
Annual Sum or Average 3265.25 841.95 1976.55 952.52 1024.03 0.00 0.00
Minimum of Months 2112.97 148.90 1034.01 9.64 879.15 0.00 0.00
Maximum of Months 4634.23 1775.08 3192.21 2276.60 1135.72 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1286.26 1245.56 1007.86 544.99 462.86 0.00 0.00
February 1503.71 1071.22 1141.12 577.56 563.55 0.00 0.00
March 1527.88 941.57 1124.69 497.87 626.82 0.00 0.00
April 2140.36 648.64 1396.89 642.60 754.30 0.00 0.00
May 2164.25 217.75 1161.68 378.42 783.26 0.00 0.00
June 2450.25 194.66 1290.49 452.51 837.99 0.00 0.00
July 2235.88 137.63 1177.98 326.75 851.23 0.00 0.00
August 2267.13 184.71 1191.09 364.61 826.48 0.00 0.00
September 1981.86 239.58 1096.79 376.25 720.54 0.00 0.00
October 1951.46 416.69 1122.89 485.19 637.70 0.00 0.00
November 1395.22 847.65 962.45 483.69 478.76 0.00 0.00
December 1240.96 1084.11 925.79 492.32 433.47 0.00 0.00
               
Annual Sum or Average 1846.64 599.94 1132.66 467.45 665.21 0.00 0.00
Minimum of Months 1240.96 137.63 925.79 326.75 433.47 0.00 0.00
Maximum of Months 2450.25 1245.56 1396.89 642.60 851.23 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.937774E+09 0.583648E+10 0.147919E+10 0.00 0.147919E+10 0.00 0.00
February 0.119587E+10 0.448346E+10 0.157621E+10 0.00 0.157621E+10 0.00 0.00
March 0.196878E+10 0.421470E+10 0.202446E+10 0.00 0.202446E+10 0.00 0.00
April 0.311473E+10 0.243562E+10 0.231223E+10 9490204.64 0.230274E+10 0.00 0.00
May 0.547374E+10 0.684780E+09 0.270634E+10 98991865.38 0.260735E+10 0.00 0.00
June 0.626772E+10 0.525340E+09 0.297841E+10 0.206232E+09 0.277218E+10 0.00 0.00
July 0.622083E+10 0.347756E+09 0.298670E+10 0.113788E+09 0.287291E+10 0.00 0.00
August 0.558670E+10 0.519066E+09 0.267464E+10 21036421.94 0.265361E+10 0.00 0.00
September 0.431785E+10 0.795289E+09 0.223577E+10 172197.99 0.223559E+10 0.00 0.00
October 0.356663E+10 0.157548E+10 0.200760E+10 0.00 0.200760E+10 0.00 0.00
November 0.148646E+10 0.366973E+10 0.147492E+10 0.00 0.147492E+10 0.00 0.00
December 0.101030E+10 0.514702E+10 0.137508E+10 0.00 0.137508E+10 0.00 0.00
               
Annual Sum or Average 0.411474E+11 0.302347E+11 0.258316E+11 0.449710E+09 0.253818E+11 0.00 0.00
Minimum of Months 0.937774E+09 0.347756E+09 0.137508E+10 0.00 0.137508E+10 0.00 0.00
Maximum of Months 0.626772E+10 0.583648E+10 0.298670E+10 0.206232E+09 0.287291E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.291593E+10 0.356883E+10 0.253790E+10 0.129231E+10 0.124559E+10 0.00 0.00
February 0.312585E+10 0.272196E+10 0.255255E+10 0.123230E+10 0.132024E+10 0.00 0.00
March 0.446188E+10 0.255975E+10 0.332435E+10 0.160324E+10 0.172110E+10 0.00 0.00
April 0.544079E+10 0.151611E+10 0.353040E+10 0.159670E+10 0.193370E+10 0.00 0.00
May 0.695365E+10 0.452792E+09 0.376019E+10 0.163049E+10 0.212970E+10 0.00 0.00
June 0.707095E+10 0.331455E+09 0.369045E+10 0.146353E+10 0.222692E+10 0.00 0.00
July 0.705820E+10 0.201782E+09 0.367673E+10 0.134548E+10 0.233124E+10 0.00 0.00
August 0.651300E+10 0.297437E+09 0.338799E+10 0.116482E+10 0.222317E+10 0.00 0.00
September 0.530455E+10 0.517597E+09 0.290433E+10 0.998497E+09 0.190583E+10 0.00 0.00
October 0.514544E+10 0.989059E+09 0.296574E+10 0.125153E+10 0.171421E+10 0.00 0.00
November 0.348908E+10 0.221759E+10 0.254103E+10 0.129628E+10 0.124475E+10 0.00 0.00
December 0.248663E+10 0.311749E+10 0.206735E+10 0.936465E+09 0.113089E+10 0.00 0.00
               
Annual Sum or Average 0.599660E+11 0.184919E+11 0.369390E+11 0.158117E+11 0.211273E+11 0.00 0.00
Minimum of Months 0.248663E+10 0.201782E+09 0.206735E+10 0.936465E+09 0.113089E+10 0.00 0.00
Maximum of Months 0.707095E+10 0.356883E+10 0.376019E+10 0.163049E+10 0.233124E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.121452E+11 0.523816E+10 0.855004E+10 0.609766E+10 0.245238E+10 0.00 0.00
February 0.101507E+11 0.409636E+10 0.700398E+10 0.453355E+10 0.247042E+10 0.00 0.00
March 0.735709E+10 0.401805E+10 0.495058E+10 0.223420E+10 0.271638E+10 0.00 0.00
April 0.583842E+10 0.248979E+10 0.355094E+10 0.832073E+09 0.271887E+10 0.00 0.00
May 0.573740E+10 0.706193E+09 0.280361E+10 0.119150E+09 0.268446E+10 0.00 0.00
June 0.565488E+10 0.545844E+09 0.268015E+10 24981607.18 0.265517E+10 0.00 0.00
July 0.606520E+10 0.346704E+09 0.289921E+10 53287137.46 0.284592E+10 0.00 0.00
August 0.715509E+10 0.555907E+09 0.341077E+10 0.409395E+09 0.300137E+10 0.00 0.00
September 0.770665E+10 0.848738E+09 0.396034E+10 0.104372E+10 0.291662E+10 0.00 0.00
October 0.113588E+11 0.164230E+10 0.634931E+10 0.330739E+10 0.304192E+10 0.00 0.00
November 0.120467E+11 0.344980E+10 0.781926E+10 0.538364E+10 0.243562E+10 0.00 0.00
December 0.123077E+11 0.472743E+10 0.835443E+10 0.599970E+10 0.235472E+10 0.00 0.00
               
Annual Sum or Average 0.103524E+12 0.286653E+11 0.623326E+11 0.300388E+11 0.322939E+11 0.00 0.00
Minimum of Months 0.565488E+10 0.346704E+09 0.268015E+10 24981607.18 0.235472E+10 0.00 0.00
Maximum of Months 0.123077E+11 0.523816E+10 0.855004E+10 0.609766E+10 0.304192E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.329515E+10 0.405674E+10 0.269945E+10 0.145972E+10 0.123974E+10 0.00 0.00
February 0.349150E+10 0.324216E+10 0.276060E+10 0.139725E+10 0.136336E+10 0.00 0.00
March 0.395183E+10 0.318424E+10 0.301238E+10 0.133350E+10 0.167887E+10 0.00 0.00
April 0.544915E+10 0.205039E+10 0.362076E+10 0.166562E+10 0.195514E+10 0.00 0.00
May 0.580764E+10 0.650658E+09 0.311146E+10 0.101356E+10 0.209789E+10 0.00 0.00
June 0.634243E+10 0.580186E+09 0.334497E+10 0.117291E+10 0.217207E+10 0.00 0.00
July 0.593319E+10 0.476738E+09 0.315511E+10 0.875179E+09 0.227993E+10 0.00 0.00
August 0.596666E+10 0.680253E+09 0.319022E+10 0.976570E+09 0.221365E+10 0.00 0.00
September 0.514180E+10 0.723632E+09 0.284289E+10 0.975247E+09 0.186764E+10 0.00 0.00
October 0.517597E+10 0.133871E+10 0.300755E+10 0.129953E+10 0.170802E+10 0.00 0.00
November 0.346252E+10 0.280722E+10 0.249467E+10 0.125372E+10 0.124095E+10 0.00 0.00
December 0.311743E+10 0.387248E+10 0.247965E+10 0.131864E+10 0.116101E+10 0.00 0.00
               
Annual Sum or Average 0.571353E+11 0.236634E+11 0.357197E+11 0.147414E+11 0.209783E+11 0.00 0.00
Minimum of Months 0.311743E+10 0.476738E+09 0.247965E+10 0.875179E+09 0.116101E+10 0.00 0.00
Maximum of Months 0.634243E+10 0.405674E+10 0.362076E+10 0.166562E+10 0.227993E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.111689E+10 0.514652E+10 0.147919E+10 0.00 0.147919E+10 0.00 0.00
February 0.135615E+10 0.390365E+10 0.157620E+10 0.00 0.157620E+10 0.00 0.00
March 0.212993E+10 0.372035E+10 0.202445E+10 0.00 0.202445E+10 0.00 0.00
April 0.320502E+10 0.225591E+10 0.231222E+10 9490170.94 0.230273E+10 0.00 0.00
May 0.549214E+10 0.659064E+09 0.270633E+10 98991513.86 0.260734E+10 0.00 0.00
June 0.628267E+10 0.543162E+09 0.297840E+10 0.206231E+09 0.277217E+10 0.00 0.00
July 0.624983E+10 0.367293E+09 0.298669E+10 0.113787E+09 0.287290E+10 0.00 0.00
August 0.564961E+10 0.519392E+09 0.267463E+10 21036347.24 0.265360E+10 0.00 0.00
September 0.435905E+10 0.724352E+09 0.223576E+10 172197.38 0.223559E+10 0.00 0.00
October 0.363447E+10 0.144433E+10 0.200759E+10 0.00 0.200759E+10 0.00 0.00
November 0.163947E+10 0.318852E+10 0.147492E+10 0.00 0.147492E+10 0.00 0.00
December 0.119275E+10 0.439782E+10 0.137507E+10 0.00 0.137507E+10 0.00 0.00
               
Annual Sum or Average 0.423080E+11 0.268704E+11 0.258315E+11 0.449709E+09 0.253818E+11 0.00 0.00
Minimum of Months 0.111689E+10 0.367293E+09 0.137507E+10 0.00 0.137507E+10 0.00 0.00
Maximum of Months 0.628267E+10 0.514652E+10 0.298669E+10 0.206231E+09 0.287290E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.295251E+10 0.329285E+10 0.253789E+10 0.129230E+10 0.124559E+10 0.00 0.00
February 0.315227E+10 0.251239E+10 0.255254E+10 0.123230E+10 0.132024E+10 0.00 0.00
March 0.444382E+10 0.241315E+10 0.332433E+10 0.160323E+10 0.172110E+10 0.00 0.00
April 0.537234E+10 0.152858E+10 0.353039E+10 0.159670E+10 0.193369E+10 0.00 0.00
May 0.686586E+10 0.470784E+09 0.376017E+10 0.163048E+10 0.212969E+10 0.00 0.00
June 0.698545E+10 0.386441E+09 0.369044E+10 0.146352E+10 0.222691E+10 0.00 0.00
July 0.696194E+10 0.265632E+09 0.367671E+10 0.134548E+10 0.233123E+10 0.00 0.00
August 0.642687E+10 0.372330E+09 0.338798E+10 0.116481E+10 0.222316E+10 0.00 0.00
September 0.524558E+10 0.513686E+09 0.290431E+10 0.998493E+09 0.190582E+10 0.00 0.00
October 0.508383E+10 0.981848E+09 0.296573E+10 0.125153E+10 0.171420E+10 0.00 0.00
November 0.348526E+10 0.208062E+10 0.254102E+10 0.129628E+10 0.124475E+10 0.00 0.00
December 0.252020E+10 0.287358E+10 0.206734E+10 0.936461E+09 0.113088E+10 0.00 0.00
               
Annual Sum or Average 0.594959E+11 0.176919E+11 0.369388E+11 0.158116E+11 0.211273E+11 0.00 0.00
Minimum of Months 0.252020E+10 0.265632E+09 0.206734E+10 0.936461E+09 0.113088E+10 0.00 0.00
Maximum of Months 0.698545E+10 0.329285E+10 0.376017E+10 0.163048E+10 0.233123E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.120489E+11 0.509472E+10 0.855001E+10 0.609764E+10 0.245237E+10 0.00 0.00
February 0.100911E+11 0.394521E+10 0.700395E+10 0.453354E+10 0.247041E+10 0.00 0.00
March 0.734615E+10 0.380107E+10 0.495056E+10 0.223419E+10 0.271637E+10 0.00 0.00
April 0.584613E+10 0.239788E+10 0.355093E+10 0.832070E+09 0.271886E+10 0.00 0.00
May 0.574746E+10 0.683639E+09 0.280360E+10 0.119149E+09 0.268445E+10 0.00 0.00
June 0.568183E+10 0.554527E+09 0.268014E+10 24981518.47 0.265516E+10 0.00 0.00
July 0.610548E+10 0.357694E+09 0.289920E+10 53286948.24 0.284591E+10 0.00 0.00
August 0.718511E+10 0.561165E+09 0.341075E+10 0.409393E+09 0.300136E+10 0.00 0.00
September 0.768135E+10 0.812791E+09 0.396032E+10 0.104371E+10 0.291661E+10 0.00 0.00
October 0.112815E+11 0.162678E+10 0.634929E+10 0.330738E+10 0.304191E+10 0.00 0.00
November 0.119814E+11 0.332978E+10 0.781924E+10 0.538363E+10 0.243561E+10 0.00 0.00
December 0.122521E+11 0.451920E+10 0.835440E+10 0.599968E+10 0.235471E+10 0.00 0.00
               
Annual Sum or Average 0.103249E+12 0.276844E+11 0.623324E+11 0.300386E+11 0.322937E+11 0.00 0.00
Minimum of Months 0.568183E+10 0.357694E+09 0.268014E+10 24981518.47 0.235471E+10 0.00 0.00
Maximum of Months 0.122521E+11 0.509472E+10 0.855001E+10 0.609764E+10 0.304191E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.340060E+10 0.356629E+10 0.269944E+10 0.145971E+10 0.123973E+10 0.00 0.00
February 0.360853E+10 0.276540E+10 0.276059E+10 0.139724E+10 0.136335E+10 0.00 0.00
March 0.408234E+10 0.265345E+10 0.301236E+10 0.133350E+10 0.167887E+10 0.00 0.00
April 0.557577E+10 0.172174E+10 0.362074E+10 0.166561E+10 0.195513E+10 0.00 0.00
May 0.585360E+10 0.561811E+09 0.311145E+10 0.101356E+10 0.209789E+10 0.00 0.00
June 0.641350E+10 0.481598E+09 0.334496E+10 0.117290E+10 0.217206E+10 0.00 0.00
July 0.605767E+10 0.346648E+09 0.315510E+10 0.875176E+09 0.227992E+10 0.00 0.00
August 0.613207E+10 0.471831E+09 0.319021E+10 0.976566E+09 0.221364E+10 0.00 0.00
September 0.518686E+10 0.605419E+09 0.284288E+10 0.975243E+09 0.186763E+10 0.00 0.00
October 0.525803E+10 0.113322E+10 0.300754E+10 0.129952E+10 0.170801E+10 0.00 0.00
November 0.359760E+10 0.232192E+10 0.249466E+10 0.125372E+10 0.124095E+10 0.00 0.00
December 0.329030E+10 0.310487E+10 0.247964E+10 0.131864E+10 0.116100E+10 0.00 0.00
               
Annual Sum or Average 0.584569E+11 0.197342E+11 0.357196E+11 0.147414E+11 0.209782E+11 0.00 0.00
Minimum of Months 0.329030E+10 0.346648E+09 0.247964E+10 0.875176E+09 0.116100E+10 0.00 0.00
Maximum of Months 0.641350E+10 0.356629E+10 0.362074E+10 0.166561E+10 0.227992E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.121299E+10 0.473577E+10 0.147919E+10 0.00 0.147919E+10 0.00 0.00
February 0.142952E+10 0.359936E+10 0.157620E+10 0.00 0.157620E+10 0.00 0.00
March 0.217857E+10 0.349747E+10 0.202445E+10 0.00 0.202445E+10 0.00 0.00
April 0.319303E+10 0.219501E+10 0.231222E+10 9490170.94 0.230273E+10 0.00 0.00
May 0.540447E+10 0.699444E+09 0.270633E+10 98991513.86 0.260734E+10 0.00 0.00
June 0.618281E+10 0.586346E+09 0.297840E+10 0.206231E+09 0.277217E+10 0.00 0.00
July 0.613305E+10 0.410117E+09 0.298669E+10 0.113787E+09 0.287290E+10 0.00 0.00
August 0.555672E+10 0.557261E+09 0.267463E+10 21036347.24 0.265360E+10 0.00 0.00
September 0.427435E+10 0.755455E+09 0.223576E+10 172197.38 0.223559E+10 0.00 0.00
October 0.359813E+10 0.141488E+10 0.200759E+10 0.00 0.200759E+10 0.00 0.00
November 0.170251E+10 0.295828E+10 0.147492E+10 0.00 0.147492E+10 0.00 0.00
December 0.127041E+10 0.404721E+10 0.137507E+10 0.00 0.137507E+10 0.00 0.00
               
Annual Sum or Average 0.421366E+11 0.254566E+11 0.258315E+11 0.449709E+09 0.253818E+11 0.00 0.00
Minimum of Months 0.121299E+10 0.410117E+09 0.137507E+10 0.00 0.137507E+10 0.00 0.00
Maximum of Months 0.618281E+10 0.473577E+10 0.298669E+10 0.206231E+09 0.287290E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.306873E+10 0.302163E+10 0.253789E+10 0.129230E+10 0.124559E+10 0.00 0.00
February 0.323525E+10 0.232026E+10 0.255254E+10 0.123230E+10 0.132024E+10 0.00 0.00
March 0.448963E+10 0.228200E+10 0.332433E+10 0.160323E+10 0.172110E+10 0.00 0.00
April 0.537190E+10 0.149579E+10 0.353039E+10 0.159670E+10 0.193369E+10 0.00 0.00
May 0.682100E+10 0.494113E+09 0.376017E+10 0.163048E+10 0.212969E+10 0.00 0.00
June 0.693790E+10 0.413554E+09 0.369044E+10 0.146352E+10 0.222691E+10 0.00 0.00
July 0.690630E+10 0.292485E+09 0.367671E+10 0.134548E+10 0.233123E+10 0.00 0.00
August 0.638297E+10 0.395849E+09 0.338798E+10 0.116481E+10 0.222316E+10 0.00 0.00
September 0.520925E+10 0.530740E+09 0.290431E+10 0.998493E+09 0.190582E+10 0.00 0.00
October 0.507214E+10 0.963135E+09 0.296573E+10 0.125153E+10 0.171420E+10 0.00 0.00
November 0.353790E+10 0.195505E+10 0.254102E+10 0.129628E+10 0.124475E+10 0.00 0.00
December 0.260199E+10 0.264590E+10 0.206734E+10 0.936461E+09 0.113088E+10 0.00 0.00
               
Annual Sum or Average 0.596350E+11 0.168105E+11 0.369388E+11 0.158116E+11 0.211273E+11 0.00 0.00
Minimum of Months 0.260199E+10 0.292485E+09 0.206734E+10 0.936461E+09 0.113088E+10 0.00 0.00
Maximum of Months 0.693790E+10 0.302163E+10 0.376017E+10 0.163048E+10 0.233123E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.121392E+11 0.475438E+10 0.855001E+10 0.609764E+10 0.245237E+10 0.00 0.00
February 0.101649E+11 0.368383E+10 0.700395E+10 0.453354E+10 0.247041E+10 0.00 0.00
March 0.737604E+10 0.360126E+10 0.495056E+10 0.223419E+10 0.271637E+10 0.00 0.00
April 0.581931E+10 0.234084E+10 0.355093E+10 0.832070E+09 0.271886E+10 0.00 0.00
May 0.565938E+10 0.724675E+09 0.280360E+10 0.119149E+09 0.268445E+10 0.00 0.00
June 0.558515E+10 0.601007E+09 0.268014E+10 24981518.47 0.265516E+10 0.00 0.00
July 0.598404E+10 0.398824E+09 0.289920E+10 53286948.24 0.284591E+10 0.00 0.00
August 0.708947E+10 0.600963E+09 0.341075E+10 0.409393E+09 0.300136E+10 0.00 0.00
September 0.759903E+10 0.843614E+09 0.396032E+10 0.104371E+10 0.291661E+10 0.00 0.00
October 0.112285E+11 0.160603E+10 0.634929E+10 0.330738E+10 0.304191E+10 0.00 0.00
November 0.120119E+11 0.316911E+10 0.781924E+10 0.538363E+10 0.243561E+10 0.00 0.00
December 0.123158E+11 0.422724E+10 0.835440E+10 0.599968E+10 0.235471E+10 0.00 0.00
               
Annual Sum or Average 0.102973E+12 0.265518E+11 0.623324E+11 0.300386E+11 0.322937E+11 0.00 0.00
Minimum of Months 0.558515E+10 0.398824E+09 0.268014E+10 24981518.47 0.235471E+10 0.00 0.00
Maximum of Months 0.123158E+11 0.475438E+10 0.855001E+10 0.609764E+10 0.304191E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.344512E+10 0.333611E+10 0.269944E+10 0.145971E+10 0.123973E+10 0.00 0.00
February 0.363778E+10 0.259151E+10 0.276059E+10 0.139724E+10 0.136335E+10 0.00 0.00
March 0.409226E+10 0.252190E+10 0.301236E+10 0.133350E+10 0.167887E+10 0.00 0.00
April 0.554782E+10 0.168127E+10 0.362074E+10 0.166561E+10 0.195513E+10 0.00 0.00
May 0.579674E+10 0.583225E+09 0.311145E+10 0.101356E+10 0.209789E+10 0.00 0.00
June 0.635105E+10 0.504565E+09 0.334496E+10 0.117290E+10 0.217206E+10 0.00 0.00
July 0.598858E+10 0.368616E+09 0.315510E+10 0.875176E+09 0.227992E+10 0.00 0.00
August 0.607228E+10 0.494731E+09 0.319021E+10 0.976566E+09 0.221364E+10 0.00 0.00
September 0.513699E+10 0.620989E+09 0.284288E+10 0.975243E+09 0.186763E+10 0.00 0.00
October 0.522678E+10 0.111605E+10 0.300754E+10 0.129952E+10 0.170801E+10 0.00 0.00
November 0.361642E+10 0.219711E+10 0.249466E+10 0.125372E+10 0.124095E+10 0.00 0.00
December 0.332379E+10 0.290369E+10 0.247964E+10 0.131864E+10 0.116100E+10 0.00 0.00
               
Annual Sum or Average 0.582356E+11 0.189198E+11 0.357196E+11 0.147414E+11 0.209782E+11 0.00 0.00
Minimum of Months 0.332379E+10 0.368616E+09 0.247964E+10 0.875176E+09 0.116100E+10 0.00 0.00
Maximum of Months 0.635105E+10 0.333611E+10 0.362074E+10 0.166561E+10 0.227992E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.57 11.02 8.64 3.24 3.13 48.31 209.17 0.01
February 15.49 12.82 10.40 2.82 4.36 58.07 218.23 0.02
March 17.07 13.58 10.72 3.68 7.24 76.61 186.08 0.03
April 21.23 17.54 15.23 2.65 11.47 90.28 216.86 0.02
May 26.90 22.82 21.10 3.11 19.64 106.10 173.47 0.04
June 27.61 23.37 21.62 2.44 19.77 115.40 187.69 0.03
July 27.94 24.58 23.34 2.53 20.70 123.49 154.05 0.05
August 27.43 23.90 22.52 3.20 20.40 118.51 145.78 0.03
September 26.23 23.37 22.24 3.39 19.02 101.73 135.58 0.05
October 24.23 20.47 18.40 4.11 16.60 78.24 178.15 0.01
November 18.91 15.31 12.62 2.63 7.99 49.56 205.43 0.01
December 15.68 12.88 10.53 3.17 6.01 45.08 191.18 0.02
                 
Annual Sum or Average 21.89 18.50 16.48 3.09 13.08 84.44 183.16 0.03
Minimum of Months 13.57 11.02 8.64 2.44 3.13 45.08 135.58 0.01
Maximum of Months 27.94 24.58 23.34 4.11 20.70 123.49 218.23 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 27.00 02-JAN-14:00 18.67 14.00 1.50 17.75 146.50 0.00
February 28.30 02-FEB-12:00 20.78 17.20 6.60 17.93 127.50 748.50
March 30.00 26-MAR-13:00 19.88 14.40 3.00 19.52 288.50 548.00
April 33.30 28-APR-14:00 23.06 18.80 4.10 23.15 150.50 762.50
May 33.90 07-MAY-13:00 23.76 19.40 4.10 23.15 287.50 507.50
June 35.00 14-JUN-13:00 23.95 19.40 2.10 24.16 194.50 712.50
July 36.10 21-JUL-15:00 25.96 22.20 1.50 26.65 216.00 245.00
August 36.30 30-AUG-15:00 23.74 18.50 2.40 25.33 116.00 698.50
September 36.40 09-SEP-16:00 26.65 23.40 4.40 26.48 114.00 401.50
October 34.00 05-OCT-14:00 24.05 20.00 2.60 29.55 169.50 606.00
November 30.00 01-NOV-13:00 25.01 23.30 2.00 26.48 216.50 118.00
December 30.00 13-DEC-14:00 21.84 18.00 3.10 20.92 101.50 682.50
                 
Annual Sum or Average                
Minimum of Months 27.00   18.67 14.00 1.50 17.75 101.50 0.00
Maximum of Months 36.40   26.65 23.40 6.60 29.55 288.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.00 05-JAN-05:00 -0.0 -0.0 2.10 -16.0 0.00 0.00
February -3.4 05-FEB-07:10 -5.4 -9.4 4.68 -21.3 0.00 0.00
March 1.10 09-MAR-05:00 -2.1 -7.3 3.60 -14.4 0.00 0.00
April 8.30 11-APR-05:00 6.95 5.50 0.00 -6.9 0.00 0.00
May 21.10 07-MAY-00:00 19.58 18.90 0.00 11.46 0.00 0.00
June 20.60 07-JUN-01:00 18.00 16.70 3.60 10.50 0.00 0.00
July 22.20 11-JUL-19:00 21.37 21.10 2.10 20.22 0.00 0.00
August 20.20 25-AUG-23:00 20.20 20.20 5.30 11.84 0.00 0.00
September 19.20 07-SEP-17:00 19.20 19.20 2.50 16.85 35.00 7.00
October 10.00 28-OCT-04:00 5.56 0.00 3.60 -0.1 0.00 0.00
November 7.20 12-NOV-07:49 4.12 0.18 4.60 -9.0 36.00 517.00
December 0.00 21-DEC-04:00 -0.9 -2.0 2.10 -16.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -3.4   -5.4 -9.4 0.00 -21.3 0.00 0.00
Maximum of Months 22.20   21.37 21.10 5.30 20.22 36.00 517.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 22.11 31-JAN-12:00 25.00 21.00 5.70 20.92 336.50 96.00
February 21.49 24-FEB-12:00 27.70 18.80 4.10 17.75 165.00 746.50
March 22.77 30-MAR-12:00 29.40 20.00 2.50 27.14 340.00 0.00
April 25.55 28-APR-15:00 32.20 23.30 3.60 22.47 156.00 575.50
May 25.84 27-MAY-13:00 31.70 23.90 3.10 22.13 168.50 735.50
June 26.52 29-JUN-16:00 29.40 25.60 1.50 26.32 164.00 36.00
July 27.17 22-JUL-10:00 32.20 25.60 2.10 21.96 191.00 719.50
August 27.24 07-AUG-12:00 31.00 26.00 3.10 27.95 473.00 200.00
September 27.79 10-SEP-12:00 35.00 25.50 2.90 24.66 239.50 662.00
October 28.18 07-OCT-07:00 29.00 28.00 2.60 21.09 95.00 500.50
November 25.01 01-NOV-13:00 30.00 23.30 2.00 26.48 216.50 118.00
December 24.12 12-DEC-13:00 27.00 23.00 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 21.49   25.00 18.80 1.50 17.75 95.00 0.00
Maximum of Months 28.18   35.00 28.00 5.70 27.95 473.00 746.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.00 31-JAN-12:00 25.00 22.11 5.70 20.92 336.50 96.00
February 20.20 02-FEB-22:00 21.50 20.56 4.80 14.65 0.00 0.00
March 21.10 07-MAR-08:00 23.30 21.69 2.00 13.91 126.00 566.50
April 23.30 28-APR-15:00 32.20 25.55 3.60 22.47 156.00 575.50
May 24.40 26-MAY-08:20 27.07 25.09 3.10 23.71 252.67 47.33
June 25.60 29-JUN-14:00 27.20 26.00 5.10 24.16 335.00 238.00
July 25.60 02-JUL-05:00 26.10 25.71 2.60 19.52 30.50 8.50
August 26.60 09-AUG-18:00 26.60 26.60 1.90 19.52 26.00 23.00
September 25.50 10-SEP-12:00 35.00 27.79 2.90 24.66 239.50 662.00
October 28.00 07-OCT-07:00 29.00 28.18 2.60 21.09 95.00 500.50
November 23.80 01-NOV-10:00 26.10 24.39 2.00 22.64 228.50 113.00
December 23.00 12-DEC-13:00 27.00 24.12 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 20.20   21.50 20.56 1.90 13.91 0.00 0.00
Maximum of Months 28.00   35.00 28.18 5.70 24.66 336.50 662.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 20.46 29.60 0.00
February 18.00 13.00 16.00 20.78 36.65 0.00
March 18.00 13.00 16.00 22.23 38.94 0.00
April 18.00 13.00 16.00 24.49 49.11 0.00
May 18.00 13.00 16.00 26.95 46.95 0.00
June 18.00 13.00 16.00 28.93 51.71 0.00
July 18.00 13.00 16.00 29.89 48.43 0.00
August 18.00 13.00 16.00 29.58 45.50 0.00
September 18.00 13.00 16.00 28.08 39.22 0.00
October 18.00 13.00 16.00 25.80 37.51 0.00
November 18.00 13.00 16.00 23.35 31.26 0.00
December 18.00 13.00 16.00 21.40 27.18 0.00
             
Annual Sum or Average 18.00 13.00 16.00 25.18 40.17 0.00
Minimum of Months 18.00 13.00 16.00 20.46 27.18 0.00
Maximum of Months 18.00 13.00 16.00 29.89 51.71 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.316643E+11 -0.306425E+11 0.00 0.00 744.00 0.00 -0.102181E+10 58.98 0.00 0.00
February 0.285432E+11 -0.276193E+11 0.00 0.00 672.00 0.00 -923848190.5 58.98 0.00 0.00
March 0.322680E+11 -0.312419E+11 0.00 0.00 744.00 0.00 -0.102613E+10 58.97 0.00 0.00
April 0.275763E+11 -0.265865E+11 0.00 0.00 720.00 0.00 -989885755.3 58.97 0.00 0.00
May 0.274186E+11 -0.263952E+11 0.00 0.00 744.00 0.00 -0.102339E+10 58.97 0.00 0.00
June 0.255252E+11 -0.245330E+11 0.00 0.00 720.00 0.00 -992199503.3 58.97 0.00 0.00
July 0.235924E+11 -0.225729E+11 0.00 0.00 744.00 0.00 -0.101944E+10 58.97 0.00 0.00
August 0.260123E+11 -0.249899E+11 0.00 0.00 744.00 0.00 -0.102235E+10 58.96 0.00 0.00
September 0.248295E+11 -0.238427E+11 0.00 0.00 720.00 0.00 -986794641.7 58.97 0.00 0.00
October 0.274236E+11 -0.264055E+11 0.00 0.00 744.00 0.00 -0.101813E+10 58.97 0.00 0.00
November 0.287890E+11 -0.278040E+11 0.00 0.00 720.00 0.00 -985033764.7 58.97 0.00 0.00
December 0.301989E+11 -0.291805E+11 0.00 0.00 744.00 0.00 -0.101836E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.333841E+12 -0.321814E+12 0.00 0.00 8760.00 0.00 -0.120274E+11 58.97 0.00 0.00
Minimum of Months 0.235924E+11 -0.312419E+11 0.00 0.00 672.00 0.00 -0.102613E+10 58.96 0.00 0.00
Maximum of Months 0.322680E+11 -0.225729E+11 0.00 0.00 744.00 0.00 -923848190.5 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.50 0.48 01-JAN-07:49 7755.15 36.97 300.33 296.17 1434.31 25.98 217.00 278.67
February 295.50 0.50 0.48 01-FEB-11:39 3369.40 28.26 173.67 279.67 1244.31 23.23 186.33 266.33
March 296.00 0.50 0.48 02-MAR-12:39 1582.52 20.02 56.00 319.67 923.77 21.35 174.17 281.00
April 347.33 0.52 0.48 01-APR-07:49 1258.74 19.22 29.50 323.33 725.51 20.52 172.33 284.33
May 353.67 0.51 0.48 01-MAY-07:19 1125.05 19.46 8.50 349.50 632.91 20.81 166.17 299.83
June 394.00 0.51 0.48 01-JUN-06:00 1068.89 19.10 2.50 350.33 605.06 20.47 166.17 303.67
July 390.00 0.51 0.48 01-JUL-06:49 1178.73 19.47 15.00 360.00 647.27 20.81 195.00 313.33
August 380.83 0.51 0.48 01-AUG-07:10 1368.33 19.76 42.67 346.67 736.37 21.08 240.83 307.67
September 342.17 0.51 0.48 01-SEP-07:19 1609.71 20.05 88.00 317.50 851.55 21.28 225.33 281.83
October 330.00 0.50 0.48 01-OCT-07:10 2775.33 23.94 167.83 314.17 1154.73 22.37 237.67 283.33
November 308.00 0.50 0.48 01-NOV-07:00 7827.42 36.40 297.33 288.67 1366.65 24.17 202.00 270.67
December 282.83 0.50 0.48 01-DEC-07:49 7905.21 37.74 279.33 284.33 1821.31 27.87 206.83 267.17
                         
Annual Sum or Average 4027.67 0.51     3028.53 24.45 1460.67 3830.00 977.62 22.31 2389.83 3437.83
Minimum of Months 282.83 0.50 0.48   1068.89 19.10 2.50 279.67 605.06 20.47 166.17 266.33
Maximum of Months 394.00 0.52 0.48   7905.21 37.74 300.33 360.00 1821.31 27.87 240.83 313.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.53 0.48 01-JAN-07:49 1992.23 23.66 104.50 271.00 1073.98 23.73 125.50 222.83
February 295.50 0.51 0.48 01-FEB-11:39 2205.56 23.74 91.00 261.50 1169.87 23.89 114.00 228.00
March 296.00 0.50 0.48 02-MAR-12:39 2297.05 23.70 86.33 315.33 1213.61 23.84 122.67 276.17
April 347.33 0.51 0.48 01-APR-07:10 2350.89 22.79 96.00 326.33 1247.80 23.15 121.83 293.33
May 353.67 0.50 0.48 01-MAY-06:40 2660.08 24.08 112.00 359.83 1066.29 23.06 127.67 314.83
June 394.00 0.50 0.48 01-JUN-06:10 2392.43 23.70 122.83 358.83 1009.20 22.95 145.33 320.83
July 390.00 0.50 0.48 01-JUL-06:19 2303.45 23.16 112.83 365.17 990.92 22.42 158.50 318.00
August 380.83 0.51 0.48 01-AUG-06:49 2122.09 23.07 106.17 347.17 1104.79 23.47 171.50 308.00
September 342.17 0.51 0.48 01-SEP-06:49 2027.04 23.20 101.17 314.17 1035.72 23.49 171.17 278.33
October 330.00 0.50 0.48 01-OCT-06:49 2109.35 23.42 93.17 303.00 1078.59 23.56 160.67 269.83
November 308.00 0.51 0.48 01-NOV-07:49 1752.12 22.80 86.00 266.83 897.81 22.84 124.00 230.50
December 282.83 0.52 0.48 01-DEC-07:40 1885.48 23.39 91.50 257.50 1004.69 23.42 111.00 208.00
                         
Annual Sum or Average 4027.67 0.51     2188.11 23.39 1203.50 3746.67 1072.92 23.29 1653.83 3268.67
Minimum of Months 282.83 0.50 0.48   1752.12 22.79 86.00 257.50 897.81 22.42 111.00 208.00
Maximum of Months 394.00 0.53 0.48   2660.08 24.08 122.83 365.17 1247.80 23.89 171.50 320.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.55 0.48 01-JAN-08:50 544.72 16.25 0.00 251.67 352.43 17.93 0.00 164.00
February 295.50 0.53 0.48 01-FEB-11:50 629.09 17.42 0.00 248.17 408.48 19.01 2.83 184.17
March 296.00 0.51 0.48 02-MAR-12:39 735.30 18.42 0.00 306.33 462.02 19.81 11.00 236.67
April 347.33 0.51 0.48 01-APR-07:49 875.26 18.83 0.00 326.50 532.86 20.12 79.67 284.83
May 353.67 0.49 0.48 01-MAY-06:00 1074.01 21.05 56.50 370.33 618.05 22.22 188.50 330.67
June 394.00 0.50 0.48 01-JUN-06:30 1242.28 22.16 108.17 374.00 654.87 21.35 217.33 338.17
July 390.00 0.49 0.48 01-JUL-06:40 1214.98 20.86 80.83 376.50 659.51 22.13 241.67 340.17
August 380.83 0.50 0.48 01-AUG-07:10 1066.39 19.59 11.33 353.17 598.95 20.89 175.83 317.50
September 342.17 0.51 0.48 01-SEP-07:19 893.27 18.81 0.17 315.50 513.67 20.10 75.50 264.83
October 330.00 0.51 0.48 01-OCT-07:30 771.07 18.58 0.00 296.50 471.76 20.03 13.83 244.17
November 308.00 0.53 0.48 01-NOV-09:50 559.79 16.86 0.00 242.83 364.10 18.51 0.00 169.00
December 282.83 0.54 0.48 01-DEC-08:39 545.21 16.51 0.00 242.83 354.44 18.24 0.00 148.50
                         
Annual Sum or Average 4027.67 0.51     871.71 18.95 257.00 3704.33 510.62 20.16 1006.17 3022.67
Minimum of Months 282.83 0.49 0.48   544.72 16.25 0.00 242.83 352.43 17.93 0.00 148.50
Maximum of Months 394.00 0.55 0.48   1242.28 22.16 108.17 376.50 659.51 22.22 241.67 340.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.52 0.48 01-JAN-08:50 2280.62 24.58 112.67 275.83 1263.44 24.48 128.00 230.00
February 295.50 0.51 0.48 01-FEB-11:39 2036.90 23.84 89.33 266.00 1073.39 23.83 128.83 234.17
March 296.00 0.51 0.48 02-MAR-12:39 2184.74 23.22 81.00 311.67 1146.46 23.53 115.17 269.00
April 347.33 0.51 0.48 01-APR-08:20 2468.66 21.70 82.83 327.00 1295.37 22.11 108.67 293.67
May 353.67 0.50 0.48 01-MAY-07:40 2045.61 18.24 1.17 356.33 904.53 20.35 102.50 317.50
June 394.00 0.51 0.48 01-JUN-07:19 2165.45 18.10 0.67 359.00 922.97 20.14 103.67 318.00
July 390.00 0.50 0.48 01-JUL-07:10 2003.70 18.58 6.50 365.83 890.49 20.40 122.33 322.33
August 380.83 0.51 0.48 01-AUG-07:40 2069.13 20.52 59.17 349.17 947.33 20.62 137.50 309.67
September 342.17 0.51 0.48 01-SEP-07:40 1919.80 21.94 82.33 314.67 983.40 22.33 153.00 278.17
October 330.00 0.50 0.48 01-OCT-07:49 2455.72 24.58 110.67 309.33 1014.45 23.45 166.67 273.00
November 308.00 0.52 0.48 01-NOV-09:50 1978.57 23.73 96.67 266.50 1063.11 23.78 124.83 231.33
December 282.83 0.51 0.48 01-DEC-08:39 2124.31 25.20 106.67 271.00 1147.23 24.95 124.33 219.00
                         
Annual Sum or Average 4027.67 0.51     2142.81 21.78 829.67 3772.33 1045.16 22.32 1515.50 3295.83
Minimum of Months 282.83 0.50 0.48   1919.80 18.10 0.67 266.00 890.49 20.14 102.50 219.00
Maximum of Months 394.00 0.52 0.48   2468.66 25.20 112.67 365.83 1295.37 24.95 166.67 322.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.50 0.48 01-JAN-07:49 7818.77 36.47 297.33 296.17 1535.46 21.75 92.17 281.67
February 295.50 0.50 0.48 01-FEB-11:39 3425.14 24.68 165.33 280.00 1336.98 18.93 36.50 268.00
March 296.00 0.50 0.48 02-MAR-12:39 1621.49 13.81 0.00 319.83 991.74 17.38 0.00 286.00
April 347.33 0.52 0.48 01-APR-07:49 1284.11 13.39 0.00 323.83 775.30 16.80 0.00 289.67
May 353.67 0.50 0.48 01-MAY-07:19 1142.90 13.60 0.00 350.00 673.87 17.05 0.00 305.50
June 394.00 0.51 0.48 01-JUN-06:49 1085.60 13.25 0.00 350.67 644.09 16.68 0.00 308.17
July 390.00 0.50 0.48 01-JUL-06:49 1195.27 13.48 0.00 360.00 688.40 16.89 0.00 318.83
August 380.83 0.51 0.48 01-AUG-07:10 1386.82 13.75 0.00 346.83 783.48 17.12 0.00 312.50
September 342.17 0.51 0.48 01-SEP-07:10 1629.69 13.91 3.67 318.17 906.66 17.13 0.00 286.67
October 330.00 0.49 0.48 01-OCT-07:10 2814.82 18.77 80.67 314.50 1241.50 18.27 10.50 287.83
November 308.00 0.50 0.48 01-NOV-07:00 7883.76 35.88 296.00 289.00 1496.85 21.56 90.83 276.33
December 282.83 0.50 0.48 01-DEC-07:49 7967.38 37.33 279.33 284.33 1927.93 23.98 110.83 268.50
                         
Annual Sum or Average 4027.67 0.50     3062.68 19.94 1122.33 3833.33 1046.51 18.44 340.83 3489.67
Minimum of Months 282.83 0.49 0.48   1085.60 13.25 0.00 280.00 644.09 16.68 0.00 268.00
Maximum of Months 394.00 0.52 0.48   7967.38 37.33 297.33 360.00 1927.93 23.98 110.83 318.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.53 0.48 01-JAN-07:49 2025.64 21.16 100.17 272.67 1118.26 21.82 72.33 229.67
February 295.50 0.51 0.48 01-FEB-11:39 2247.37 20.99 89.67 262.67 1218.85 21.80 64.33 231.67
March 296.00 0.50 0.48 02-MAR-12:39 2322.08 19.46 74.33 316.00 1274.62 21.39 56.50 282.17
April 347.33 0.51 0.48 01-APR-07:10 2380.85 19.75 95.67 327.17 1303.95 20.73 68.00 296.67
May 353.67 0.50 0.48 01-MAY-06:40 2679.10 20.41 106.00 361.17 1125.28 20.39 55.00 320.50
June 394.00 0.50 0.48 01-JUN-06:10 2420.29 19.85 114.00 359.50 1064.00 20.35 62.67 326.67
July 390.00 0.50 0.48 01-JUL-06:19 2333.56 20.10 112.33 366.33 1045.23 19.74 53.67 323.50
August 380.83 0.51 0.48 01-AUG-06:49 2144.89 20.01 105.17 347.67 1156.72 21.11 75.50 312.50
September 342.17 0.51 0.48 01-SEP-06:49 2063.30 20.20 96.00 314.67 1085.54 21.13 67.50 282.17
October 330.00 0.50 0.48 01-OCT-06:49 2156.18 20.45 87.67 303.17 1130.67 21.24 57.00 273.17
November 308.00 0.51 0.48 01-NOV-07:49 1786.71 19.96 84.00 267.83 942.70 20.65 55.50 234.17
December 282.83 0.52 0.48 01-DEC-07:40 1915.03 20.90 89.17 258.50 1045.95 21.56 61.67 213.67
                         
Annual Sum or Average 4027.67 0.51     2219.26 20.25 1154.17 3757.33 1124.75 20.94 749.67 3326.50
Minimum of Months 282.83 0.50 0.48   1786.71 19.46 74.33 258.50 942.70 19.74 53.67 213.67
Maximum of Months 394.00 0.53 0.48   2679.10 21.16 114.00 366.33 1303.95 21.82 75.50 326.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.54 0.48 01-JAN-08:50 554.53 10.76 0.00 252.67 375.65 14.39 0.00 179.67
February 295.50 0.52 0.48 01-FEB-11:50 641.40 11.98 0.00 249.33 435.66 15.61 0.00 193.83
March 296.00 0.51 0.48 02-MAR-12:39 750.69 13.17 0.00 307.67 492.99 16.68 0.00 248.83
April 347.33 0.51 0.48 01-APR-07:49 893.47 13.44 0.00 327.33 568.46 16.87 0.00 291.50
May 353.67 0.49 0.48 01-MAY-06:00 1093.61 15.68 27.17 370.67 658.39 19.00 27.50 336.00
June 394.00 0.49 0.48 01-JUN-06:19 1263.02 17.19 58.00 374.33 707.06 20.31 59.33 348.67
July 390.00 0.49 0.48 01-JUL-06:40 1234.24 15.30 23.50 376.67 701.51 18.62 24.50 343.33
August 380.83 0.50 0.48 01-AUG-06:00 1083.71 13.86 0.00 353.33 637.21 17.27 0.00 322.00
September 342.17 0.51 0.48 01-SEP-07:19 908.54 13.25 0.00 316.00 546.69 16.60 0.00 271.17
October 330.00 0.51 0.48 01-OCT-07:30 784.88 13.18 0.00 297.33 502.55 16.68 0.00 252.33
November 308.00 0.53 0.48 01-NOV-09:39 570.14 11.28 0.00 244.33 388.17 14.97 0.00 180.50
December 282.83 0.53 0.48 01-DEC-08:30 554.52 10.91 0.00 243.67 377.66 14.62 0.00 162.33
                         
Annual Sum or Average 4027.67 0.51     887.19 13.51 108.67 3713.33 544.86 16.96 111.33 3130.17
Minimum of Months 282.83 0.49 0.48   554.52 10.76 0.00 243.67 375.65 14.39 0.00 162.33
Maximum of Months 394.00 0.54 0.48   1263.02 17.19 58.00 376.67 707.06 20.31 59.33 348.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.52 0.48 01-JAN-08:50 2314.52 22.16 109.33 276.83 1309.65 22.68 81.83 237.00
February 295.50 0.51 0.48 01-FEB-11:39 2056.29 19.85 79.17 266.83 1126.49 21.64 60.17 237.67
March 296.00 0.51 0.48 02-MAR-12:39 2235.47 20.17 81.00 313.33 1200.28 21.13 56.67 276.50
April 347.33 0.51 0.48 01-APR-08:09 2497.62 18.40 82.00 327.67 1352.65 19.42 53.00 297.83
May 353.67 0.50 0.48 01-MAY-07:40 2069.90 13.72 0.00 357.33 955.03 17.13 0.00 320.67
June 394.00 0.50 0.48 01-JUN-07:10 2193.28 13.62 0.00 359.17 973.97 16.95 0.00 324.00
July 390.00 0.50 0.48 01-JUL-07:10 2026.98 14.18 3.67 366.67 939.37 17.25 0.00 327.33
August 380.83 0.51 0.48 01-AUG-07:40 2092.83 16.85 59.00 350.67 997.72 17.53 5.50 316.50
September 342.17 0.51 0.48 01-SEP-07:40 1954.55 18.73 80.50 315.67 1032.02 19.80 51.67 282.83
October 330.00 0.50 0.48 01-OCT-07:40 2502.37 21.91 108.83 310.17 1066.59 21.07 53.50 276.83
November 308.00 0.51 0.48 01-NOV-09:39 2013.78 21.06 95.17 268.17 1108.33 21.76 66.67 236.00
December 282.83 0.51 0.48 01-DEC-08:30 2159.94 22.85 103.00 271.50 1194.42 23.17 74.00 226.00
                         
Annual Sum or Average 4027.67 0.51     2174.37 18.32 801.67 3784.00 1095.57 19.74 503.00 3359.17
Minimum of Months 282.83 0.50 0.48   1954.55 13.62 0.00 266.83 939.37 16.95 0.00 226.00
Maximum of Months 394.00 0.52 0.48   2502.37 22.85 109.33 366.67 1352.65 23.17 81.83 327.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.50 0.48 01-JAN-07:49 7820.39 36.46 297.33 296.17 1537.13 21.74 92.17 281.67
February 295.50 0.50 0.48 01-FEB-11:39 3427.36 24.66 165.33 280.00 1338.57 18.92 36.50 268.00
March 296.00 0.50 0.48 02-MAR-12:39 1623.59 13.78 0.00 320.33 993.08 17.37 0.00 286.00
April 347.33 0.52 0.48 01-APR-07:49 1285.78 13.36 0.00 323.83 776.38 16.79 0.00 289.83
May 353.67 0.50 0.48 01-MAY-07:19 1144.44 13.57 0.00 350.33 674.86 17.04 0.00 305.67
June 394.00 0.51 0.48 01-JUN-06:49 1087.04 13.22 0.00 350.67 645.02 16.67 0.00 308.17
July 390.00 0.50 0.48 01-JUL-06:49 1197.01 13.45 0.00 360.17 689.47 16.87 0.00 318.83
August 380.83 0.51 0.48 01-AUG-07:10 1388.97 13.72 0.00 346.83 784.75 17.11 0.00 312.50
September 342.17 0.51 0.48 01-SEP-07:10 1632.29 13.88 3.67 318.17 908.20 17.12 0.00 286.67
October 330.00 0.49 0.48 01-OCT-07:10 2817.67 18.74 80.67 314.67 1243.35 18.26 10.50 288.00
November 308.00 0.50 0.48 01-NOV-07:00 7885.67 35.88 296.00 289.00 1498.51 21.55 90.83 276.50
December 282.83 0.50 0.48 01-DEC-07:49 7968.96 37.33 279.33 284.33 1929.71 23.97 110.83 268.50
                         
Annual Sum or Average 4027.67 0.50     3064.63 19.92 1122.33 3834.50 1047.88 18.43 340.83 3490.33
Minimum of Months 282.83 0.49 0.48   1087.04 13.22 0.00 280.00 645.02 16.67 0.00 268.00
Maximum of Months 394.00 0.52 0.48   7968.96 37.33 297.33 360.17 1929.71 23.97 110.83 318.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.53 0.48 01-JAN-07:49 2026.36 21.14 100.17 272.67 1119.11 21.81 72.33 229.67
February 295.50 0.51 0.48 01-FEB-11:39 2248.17 20.97 89.67 262.67 1219.82 21.79 64.33 231.83
March 296.00 0.50 0.48 02-MAR-12:39 2323.21 19.43 74.33 316.17 1275.78 21.37 56.50 282.17
April 347.33 0.51 0.48 01-APR-07:10 2382.24 19.72 95.67 327.17 1305.15 20.72 68.00 297.00
May 353.67 0.50 0.48 01-MAY-06:40 2680.73 20.38 106.00 361.17 1126.63 20.38 55.00 320.83
June 394.00 0.50 0.48 01-JUN-06:10 2422.08 19.82 114.00 359.50 1065.36 20.33 62.67 326.83
July 390.00 0.50 0.48 01-JUL-06:19 2335.59 20.07 112.33 366.67 1046.70 19.73 53.67 323.67
August 380.83 0.51 0.48 01-AUG-06:49 2146.90 19.98 105.17 347.67 1158.18 21.09 75.50 312.67
September 342.17 0.51 0.48 01-SEP-06:49 2065.24 20.18 96.00 314.67 1086.96 21.12 67.50 282.17
October 330.00 0.50 0.48 01-OCT-06:49 2157.53 20.42 87.67 303.17 1131.94 21.22 57.00 273.17
November 308.00 0.51 0.48 01-NOV-07:49 1787.48 19.93 84.00 267.83 943.59 20.63 55.50 234.33
December 282.83 0.52 0.48 01-DEC-07:40 1915.74 20.88 89.17 258.50 1046.79 21.55 61.67 213.67
                         
Annual Sum or Average 4027.67 0.51     2220.67 20.22 1154.17 3757.83 1125.96 20.93 749.67 3328.00
Minimum of Months 282.83 0.50 0.48   1787.48 19.43 74.33 258.50 943.59 19.73 53.67 213.67
Maximum of Months 394.00 0.53 0.48   2680.73 21.14 114.00 366.67 1305.15 21.81 75.50 326.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.54 0.48 01-JAN-08:50 554.85 10.72 0.00 252.67 376.05 14.37 0.00 179.83
February 295.50 0.52 0.48 01-FEB-11:50 641.78 11.95 0.00 249.67 436.11 15.59 0.00 194.00
March 296.00 0.51 0.48 02-MAR-12:39 751.28 13.14 0.00 307.83 493.55 16.66 0.00 249.00
April 347.33 0.51 0.48 01-APR-07:49 894.31 13.41 0.00 327.33 569.17 16.85 0.00 291.83
May 353.67 0.49 0.48 01-MAY-06:00 1094.90 15.65 27.17 370.83 659.33 18.98 27.50 336.00
June 394.00 0.49 0.48 01-JUN-06:19 1264.52 17.16 58.00 374.33 708.10 20.30 59.33 348.67
July 390.00 0.49 0.48 01-JUL-06:40 1235.87 15.27 23.50 376.67 702.59 18.60 24.50 343.50
August 380.83 0.50 0.48 01-AUG-06:00 1085.11 13.83 0.00 353.33 638.17 17.25 0.00 322.00
September 342.17 0.51 0.48 01-SEP-07:19 909.61 13.22 0.00 316.00 547.48 16.58 0.00 271.33
October 330.00 0.51 0.48 01-OCT-07:30 785.55 13.15 0.00 297.33 503.17 16.67 0.00 252.33
November 308.00 0.53 0.48 01-NOV-09:39 570.46 11.24 0.00 244.33 388.57 14.95 0.00 181.17
December 282.83 0.53 0.48 01-DEC-08:30 554.82 10.88 0.00 243.83 378.05 14.60 0.00 162.33
                         
Annual Sum or Average 4027.67 0.51     888.10 13.48 108.67 3714.17 545.58 16.95 111.33 3132.00
Minimum of Months 282.83 0.49 0.48   554.82 10.72 0.00 243.83 376.05 14.37 0.00 162.33
Maximum of Months 394.00 0.54 0.48   1264.52 17.16 58.00 376.67 708.10 20.30 59.33 348.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.52 0.48 01-JAN-08:50 2315.23 22.13 109.33 276.83 1310.50 22.67 81.83 237.33
February 295.50 0.51 0.48 01-FEB-11:39 2057.17 19.82 79.17 266.83 1127.49 21.62 60.17 237.67
March 296.00 0.51 0.48 02-MAR-12:39 2236.62 20.14 81.00 313.33 1201.37 21.12 56.67 276.83
April 347.33 0.51 0.48 01-APR-08:09 2499.05 18.37 82.00 327.67 1353.89 19.40 53.00 297.83
May 353.67 0.50 0.48 01-MAY-07:40 2071.62 13.69 0.00 357.33 1137.83 17.11 0.00 320.83
June 394.00 0.50 0.48 01-JUN-07:10 2195.02 13.58 0.00 359.17 975.26 16.94 0.00 324.17
July 390.00 0.50 0.48 01-JUL-07:10 2029.01 14.14 3.67 366.83 948.38 17.24 0.00 327.50
August 380.83 0.51 0.48 01-AUG-07:40 2094.90 16.82 59.00 350.67 1125.48 17.52 5.50 316.67
September 342.17 0.51 0.48 01-SEP-07:40 1956.38 18.71 80.50 315.67 1033.37 19.78 51.67 282.83
October 330.00 0.50 0.48 01-OCT-07:40 2503.78 21.88 108.83 310.17 1067.87 21.06 53.50 277.00
November 308.00 0.51 0.48 01-NOV-09:39 2014.51 21.03 95.17 268.17 1109.21 21.74 66.67 236.17
December 282.83 0.51 0.48 01-DEC-08:30 2160.65 22.82 103.00 271.50 1195.27 23.16 74.00 226.00
                         
Annual Sum or Average 4027.67 0.51     2175.78 18.29 801.67 3784.17 1125.37 19.72 503.00 3360.83
Minimum of Months 282.83 0.50 0.48   1956.38 13.58 0.00 266.83 948.38 16.94 0.00 226.00
Maximum of Months 394.00 0.52 0.48   2503.78 22.82 109.33 366.83 1353.89 23.16 81.83 327.50



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 41583746.57 11217.40 05-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 17039723.14 10552.36 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 9355482.56 10612.36 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 9921841.32 2415.11 18-APR-15:20 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 35210.31 117.00 18-NOV-13:05 0.00 0.00 0.00 0.00 0.00
December 21665679.56 12233.09 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 99601683.45     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 41583746.57 12233.09   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 11381089.64 1700.34 05-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 1258293.33 429.35 06-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 1841135.25 602.23 21-DEC-07:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 14480518.21     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 11381089.64 1700.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 7545438.46 1109.11 05-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 2086446.01 641.53 06-FEB-06:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 10004165.29 2441.44 21-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 19636049.77     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 10004165.29 2441.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 15888379.20 1557.64 21-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 7650642.59 3292.65 06-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 11262831.91 1475.21 20-DEC-07:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 34801853.70     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 15888379.20 3292.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.786990E+09 152461.07 03-JAN-10:05 0.00 0.00 0.00 0.00 0.00
February 0.365695E+09 111677.52 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.870195E+09 160733.57 09-MAR-10:30 0.00 0.00 0.00 0.00 0.00
April 0.114867E+09 97566.86 18-APR-14:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 6405761.77 17272.80 15-NOV-10:05 0.00 0.00 0.00 0.00 0.00
December 0.380559E+09 131959.08 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.252471E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.870195E+09 160733.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.731173E+10 142652.91 23-JAN-05:12 0.00 0.00 0.00 0.00 0.00
February 0.345882E+10 142615.28 07-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.237009E+10 142652.30 13-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.264231E+09 19283.94 16-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.458375E+10 142692.64 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.179886E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.731173E+10 142692.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.231849E+10 130468.00 11-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.949211E+09 130464.22 06-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.955695E+09 130255.94 11-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 21560622.48 10472.95 16-NOV-06:17 0.00 0.00 0.00 0.00 0.00
December 0.184692E+10 130427.48 20-DEC-05:11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.609188E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.231849E+10 130468.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.168024E+10 164238.37 09-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.792160E+09 163992.49 06-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.131605E+10 164045.86 11-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.119655E+10 164086.63 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.498500E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.168024E+10 164238.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.190288E+10 123643.73 23-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.807114E+09 123622.68 06-FEB-05:11 0.00 0.00 0.00 0.00 0.00
March 0.645548E+09 92773.37 11-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.926566E+09 123606.97 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.428211E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.190288E+10 123643.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 65322103.90 13656.86 05-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 25527697.35 13315.08 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 18221294.02 13253.06 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 395706.03 397.16 18-APR-15:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 649547.00 982.64 15-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 38015325.18 14002.82 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.148132E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 65322103.90 14002.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.881644E+09 70947.87 09-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.817535E+09 71098.74 06-FEB-06:08 0.00 0.00 0.00 0.00 0.00
March 0.472926E+09 70942.80 13-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.509347E+09 71051.78 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.268145E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.881644E+09 71098.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.229513E+10 16406.84 23-JAN-06:05 0.00 0.00 0.00 0.00 0.00
February 0.126019E+10 16358.02 09-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.826585E+09 16355.56 11-MAR-05:13 0.00 0.00 0.00 0.00 0.00
April 23309775.07 2877.78 03-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 28914293.18 6325.13 28-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.255108E+09 16314.48 15-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.154498E+10 16367.00 21-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.623421E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.229513E+10 16406.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.851304E+09 15280.80 05-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.459420E+09 15266.48 06-FEB-05:16 0.00 0.00 0.00 0.00 0.00
March 0.392617E+09 15273.34 13-MAR-04:12 0.00 0.00 0.00 0.00 0.00
April 4330700.28 982.32 03-APR-05:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 9086984.77 2901.06 28-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 72573417.44 15267.59 13-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.701050E+09 15270.25 22-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.249038E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.851304E+09 15280.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.796328E+09 19780.75 09-JAN-05:13 0.00 0.00 0.00 0.00 0.00
February 0.473487E+09 19758.08 06-FEB-05:16 0.00 0.00 0.00 0.00 0.00
March 0.542401E+09 19758.64 22-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 8471462.24 984.06 11-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 8890541.01 1632.37 28-OCT-05:08 0.00 0.00 0.00 0.00 0.00
November 45735860.70 19743.74 16-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.616768E+09 19761.73 20-DEC-05:13 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.249208E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.796328E+09 19780.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.750119E+09 15472.20 05-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.391018E+09 15445.24 06-FEB-05:15 0.00 0.00 0.00 0.00 0.00
March 0.277264E+09 15441.97 11-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 4563580.53 643.82 28-OCT-06:40 0.00 0.00 0.00 0.00 0.00
November 46779439.62 14583.89 16-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.464565E+09 15452.45 20-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.193431E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.750119E+09 15472.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 86.00 0.86 12-APR-04:12 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 176.94 0.84 25-DEC-14:28 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 262.94     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 176.94 0.86   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.407378E+11 0.308916E+11 138188.76 19-JAN-06:03 115957.65 0.27
February 0.00 0.00 0.584076E+11 0.430563E+11 159909.45 28-FEB-05:12 143583.15 0.43
March 0.00 0.00 0.732320E+11 0.584088E+11 162850.83 28-MAR-04:12 126436.20 0.42
April 0.00 0.00 0.117939E+12 0.944472E+11 160127.44 01-APR-04:12 124287.13 0.70
May 0.00 0.00 0.147724E+12 0.114421E+12 181164.58 24-MAY-05:02 139602.38 0.70
June 0.00 0.00 0.160087E+12 0.126973E+12 174175.25 07-JUN-04:12 141187.77 0.80
July 0.00 0.00 0.173226E+12 0.135507E+12 168705.62 24-JUL-05:03 147409.03 0.85
August 0.00 0.00 0.190555E+12 0.150761E+12 180830.56 07-AUG-05:02 151559.69 0.88
September 0.00 0.00 0.148453E+12 0.108723E+12 193598.36 13-SEP-04:12 133273.24 0.70
October 0.00 0.00 0.139552E+12 0.110234E+12 177768.34 21-OCT-04:11 138638.41 0.66
November 0.00 0.00 0.888054E+11 0.720086E+11 170741.58 01-NOV-04:11 142350.77 0.53
December 0.00 0.00 0.665451E+11 0.528524E+11 142768.02 11-DEC-06:02 132056.14 0.40
                 
Annual Sum or Average 0.00 0.00 0.140526E+13 0.109828E+13       0.61
Minimum of Months 0.00 0.00 0.407378E+11 0.308916E+11 138188.76   115957.65 0.27
Maximum of Months 0.00 0.00 0.190555E+12 0.150761E+12 193598.36   151559.69 0.88



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.332217E+12 0.246422E+12 1155518.78 19-JAN-06:03 879237.68 0.26
February 0.00 0.00 0.464006E+12 0.328919E+12 1230508.54 03-FEB-06:03 865207.05 0.40
March 0.00 0.00 0.552730E+12 0.418524E+12 1514413.17 27-MAR-05:03 1215482.09 0.38
April 0.00 0.00 0.859903E+12 0.647282E+12 1608013.40 28-APR-04:12 1308523.45 0.52
May 0.00 0.00 0.134360E+13 0.996848E+12 2214100.04 24-MAY-05:02 1357535.91 0.65
June 0.00 0.00 0.137170E+13 0.103037E+13 1748296.06 06-JUN-04:11 1279513.60 0.68
July 0.00 0.00 0.142114E+13 0.102297E+13 1653600.79 27-JUL-03:02 1230378.46 0.68
August 0.00 0.00 0.147730E+13 0.106397E+13 1910958.76 16-AUG-04:12 1212746.64 0.68
September 0.00 0.00 0.132294E+13 0.912273E+12 2191988.12 05-SEP-04:12 1127695.79 0.65
October 0.00 0.00 0.116523E+13 0.866095E+12 1912477.80 21-OCT-04:11 1179012.48 0.56
November 0.00 0.00 0.679224E+12 0.527059E+12 1614567.92 01-NOV-05:02 1225954.24 0.47
December 0.00 0.00 0.474759E+12 0.351327E+12 1554466.10 11-DEC-06:02 1206692.06 0.32
                 
Annual Sum or Average 0.00 0.00 0.114647E+14 0.841206E+13       0.52
Minimum of Months 0.00 0.00 0.332217E+12 0.246422E+12 1155518.78   865207.05 0.26
Maximum of Months 0.00 0.00 0.147730E+13 0.106397E+13 2214100.04   1357535.91 0.68



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.315440E+11 0.225974E+11 133018.20 19-JAN-14:53 88109.94 0.26
February 0.00 0.00 0.459332E+11 0.322335E+11 128048.22 24-FEB-15:53 88917.32 0.40
March 0.00 0.00 0.561534E+11 0.420828E+11 152911.17 07-MAR-06:02 103783.58 0.37
April 0.00 0.00 0.904892E+11 0.688264E+11 159180.14 29-APR-05:03 122193.20 0.52
May 0.00 0.00 0.148399E+12 0.112583E+12 243053.13 24-MAY-05:02 143961.96 0.65
June 0.00 0.00 0.153675E+12 0.118620E+12 192582.62 06-JUN-04:11 136776.77 0.69
July 0.00 0.00 0.158838E+12 0.117322E+12 199546.16 27-JUL-03:02 147045.32 0.69
August 0.00 0.00 0.163099E+12 0.120310E+12 198634.17 23-AUG-03:02 143755.93 0.69
September 0.00 0.00 0.142381E+12 0.998051E+11 243868.02 05-SEP-04:12 121750.19 0.65
October 0.00 0.00 0.124186E+12 0.934297E+11 195721.90 11-OCT-04:12 133277.34 0.56
November 0.00 0.00 0.656816E+11 0.506500E+11 179237.47 01-NOV-05:02 129204.67 0.46
December 0.00 0.00 0.452225E+11 0.329973E+11 150290.81 15-DEC-06:02 107059.35 0.31
                 
Annual Sum or Average 0.00 0.00 0.122560E+13 0.911457E+12       0.52
Minimum of Months 0.00 0.00 0.315440E+11 0.225974E+11 128048.22   88109.94 0.26
Maximum of Months 0.00 0.00 0.163099E+12 0.120310E+12 243868.02   147045.32 0.69



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.218475E+11 0.172309E+11 123828.33 19-JAN-05:12 44851.61 0.18
February 0.00 0.00 0.262581E+11 0.213851E+11 121212.94 03-FEB-05:12 45368.71 0.29
March 0.00 0.00 0.351738E+11 0.300003E+11 145405.44 07-MAR-05:13 88000.49 0.27
April 0.00 0.00 0.551412E+11 0.481061E+11 145147.09 26-APR-04:13 83240.91 0.45
May 0.00 0.00 0.100822E+12 0.778183E+11 169711.73 29-MAY-09:21 85269.98 0.58
June 0.00 0.00 0.105783E+12 0.793112E+11 168665.26 19-JUN-03:02 84269.67 0.59
July 0.00 0.00 0.114257E+12 0.804793E+11 168800.15 03-JUL-03:02 81826.19 0.56
August 0.00 0.00 0.127008E+12 0.919942E+11 171448.85 06-AUG-14:30 85067.77 0.63
September 0.00 0.00 0.108262E+12 0.786903E+11 171644.83 17-SEP-15:11 85753.07 0.60
October 0.00 0.00 0.933220E+11 0.715622E+11 174912.56 15-OCT-14:42 83097.32 0.52
November 0.00 0.00 0.521962E+11 0.432891E+11 145963.86 29-NOV-05:12 88834.52 0.39
December 0.00 0.00 0.339305E+11 0.275982E+11 146195.00 15-DEC-05:11 88219.68 0.25
                 
Annual Sum or Average 0.00 0.00 0.874001E+12 0.667465E+12       0.44
Minimum of Months 0.00 0.00 0.218475E+11 0.172309E+11 121212.94   44851.61 0.18
Maximum of Months 0.00 0.00 0.127008E+12 0.919942E+11 174912.56   88834.52 0.63



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.385540E+11 0.343611E+11 207721.47 31-JAN-12:50 125990.01 0.00
February 0.00 0.00 0.147646E+12 0.137761E+12 311463.84 24-FEB-10:30 216556.54 0.00
March 0.00 0.00 0.361275E+12 0.334693E+12 393832.87 31-MAR-24:00 393832.87 0.00
April 0.00 0.00 0.854292E+12 0.779038E+12 428918.24 05-APR-07:15 396964.66 0.00
May 0.00 0.00 0.348758E+12 0.336045E+12 212651.97 31-MAY-23:10 210368.29 0.00
June 0.00 0.00 0.575869E+12 0.561926E+12 302788.65 30-JUN-24:00 302586.36 0.00
July 0.00 0.00 0.841916E+12 0.826960E+12 394842.00 31-JUL-24:00 394842.00 0.00
August 0.00 0.00 0.108022E+13 0.106640E+13 424119.82 07-AUG-14:00 403440.19 0.00
September 0.00 0.00 0.341849E+12 0.328234E+12 213138.38 30-SEP-24:00 211863.19 0.00
October 0.00 0.00 0.486348E+12 0.471394E+12 303954.33 31-OCT-24:00 303954.33 0.00
November 0.00 0.00 0.418573E+12 0.381731E+12 359241.92 28-NOV-09:00 308820.23 0.00
December 0.00 0.00 0.499724E+12 0.448220E+12 432248.89 28-DEC-09:50 398579.97 0.00
                 
Annual Sum or Average 0.00 0.00 0.599502E+13 0.570676E+13       0.00
Minimum of Months 0.00 0.00 0.385540E+11 0.343611E+11 207721.47   125990.01 0.00
Maximum of Months 0.00 0.00 0.108022E+13 0.106640E+13 432248.89   403440.19 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.516755E+10 0.506154E+10 2819.46 19-JAN-17:00 2458.00 0.00
February 0.00 0.00 0.958665E+10 0.940003E+10 4754.10 27-FEB-17:00 4396.78 0.00
March 0.00 0.00 0.157883E+11 0.155833E+11 7710.00 31-MAR-24:00 7710.00 0.00
April 0.00 0.00 0.205283E+11 0.202357E+11 8674.62 28-APR-17:30 8118.28 0.00
May 0.00 0.00 0.654416E+10 0.603806E+10 4086.11 31-MAY-23:10 3943.65 0.00
June 0.00 0.00 0.113157E+11 0.107335E+11 5881.08 30-JUN-23:05 5837.89 0.00
July 0.00 0.00 0.167920E+11 0.161394E+11 7744.82 31-JUL-24:00 7742.86 0.00
August 0.00 0.00 0.218913E+11 0.212343E+11 8897.58 07-AUG-13:50 8161.00 0.00
September 0.00 0.00 0.637524E+10 0.583158E+10 4043.58 30-SEP-24:00 4012.66 0.00
October 0.00 0.00 0.114759E+11 0.110236E+11 5880.86 31-OCT-24:00 5871.84 0.00
November 0.00 0.00 0.155700E+11 0.153168E+11 6808.86 07-NOV-16:40 6273.73 0.00
December 0.00 0.00 0.208309E+11 0.206506E+11 8768.81 14-DEC-17:00 8300.84 0.00
                 
Annual Sum or Average 0.00 0.00 0.161866E+12 0.157249E+12       0.00
Minimum of Months 0.00 0.00 0.516755E+10 0.506154E+10 2819.46   2458.00 0.00
Maximum of Months 0.00 0.00 0.218913E+11 0.212343E+11 8897.58   8300.84 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.378445E+11 0.368141E+11 26455.61 19-JAN-17:00 22864.42 0.00
February 0.00 0.00 0.826001E+11 0.807514E+11 45075.79 27-FEB-17:00 41522.90 0.00
March 0.00 0.00 0.143409E+12 0.141369E+12 72295.27 31-MAR-24:00 72295.27 0.00
April 0.00 0.00 0.193889E+12 0.190964E+12 82871.64 28-APR-17:20 77555.98 0.00
May 0.00 0.00 0.608180E+11 0.558173E+11 38556.55 31-MAY-23:10 37001.89 0.00
June 0.00 0.00 0.107471E+12 0.101679E+12 56835.61 30-JUN-23:55 56677.75 0.00
July 0.00 0.00 0.160035E+12 0.153526E+12 74212.12 31-JUL-24:00 74180.39 0.00
August 0.00 0.00 0.207945E+12 0.201375E+12 84576.85 07-AUG-13:40 77229.70 0.00
September 0.00 0.00 0.582875E+11 0.529319E+11 37619.10 30-SEP-24:00 37295.48 0.00
October 0.00 0.00 0.107068E+12 0.102574E+12 54720.83 31-OCT-24:00 54604.94 0.00
November 0.00 0.00 0.142529E+12 0.140013E+12 64981.67 07-NOV-16:50 59669.99 0.00
December 0.00 0.00 0.189489E+12 0.187685E+12 83370.98 14-DEC-17:00 78694.02 0.00
                 
Annual Sum or Average 0.00 0.00 0.149138E+13 0.144550E+13       0.00
Minimum of Months 0.00 0.00 0.378445E+11 0.368141E+11 26455.61   22864.42 0.00
Maximum of Months 0.00 0.00 0.207945E+12 0.201375E+12 84576.85   78694.02 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.272664E+10 0.262507E+10 2721.93 19-JAN-17:00 2361.53 0.00
February 0.00 0.00 0.748019E+10 0.729625E+10 4572.10 27-FEB-17:00 4216.62 0.00
March 0.00 0.00 0.138028E+11 0.135993E+11 7144.70 31-MAR-24:00 7144.70 0.00
April 0.00 0.00 0.192787E+11 0.189868E+11 8411.01 28-APR-17:20 7875.05 0.00
May 0.00 0.00 0.623627E+10 0.573394E+10 3841.73 31-MAY-23:10 3687.02 0.00
June 0.00 0.00 0.109185E+11 0.103385E+11 5722.62 30-JUN-23:55 5706.79 0.00
July 0.00 0.00 0.161857E+11 0.155347E+11 7419.27 31-JUL-24:00 7415.90 0.00
August 0.00 0.00 0.209567E+11 0.202993E+11 8571.73 14-AUG-16:00 7909.76 0.00
September 0.00 0.00 0.595322E+10 0.541588E+10 3792.90 30-SEP-24:00 3761.27 0.00
October 0.00 0.00 0.106674E+11 0.102180E+11 5417.63 31-OCT-24:00 5405.53 0.00
November 0.00 0.00 0.137660E+11 0.135153E+11 6558.16 07-NOV-16:40 6024.62 0.00
December 0.00 0.00 0.181086E+11 0.179288E+11 8403.99 14-DEC-17:00 7936.26 0.00
                 
Annual Sum or Average 0.00 0.00 0.146081E+12 0.141492E+12       0.00
Minimum of Months 0.00 0.00 0.272664E+10 0.262507E+10 2721.93   2361.53 0.00
Maximum of Months 0.00 0.00 0.209567E+11 0.202993E+11 8571.73   7936.26 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 7225.17 933550.74 05-JAN-06:02
February 0.00 0.00 01-FEB-00:10 4026.18 835074.97 17-FEB-06:02
March 0.00 0.00 01-MAR-00:10 3217.62 880587.67 11-MAR-06:02
April 0.00 0.00 01-APR-00:10 116.68 88972.93 18-APR-14:10
May 0.00 0.00 01-MAY-00:05 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 6.22 3298.74 28-OCT-05:03
November 0.00 0.00 01-NOV-00:10 234.74 130346.61 16-NOV-06:02
December 0.00 0.00 01-DEC-00:10 4750.77 906570.56 21-DEC-06:01
             
Annual Sum or Average 0.00     1628.68    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   7225.17 933550.74  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 167215.42 2342465.07 19-JAN-14:53 0.00 0.00 01-JAN-00:05
February 263105.39 2095464.09 22-FEB-15:03 0.00 0.00 01-FEB-00:10
March 284803.57 2187808.00 07-MAR-11:23 0.00 0.00 01-MAR-00:10
April 464071.96 2408420.20 14-APR-15:32 0.00 0.00 01-APR-00:10
May 710349.26 2491131.39 24-MAY-05:04 0.00 0.00 01-MAY-00:05
June 750522.24 2131112.45 13-JUN-15:33 0.00 0.00 01-JUN-00:10
July 750137.85 1932540.85 21-JUL-12:05 0.00 0.00 01-JUL-00:10
August 787642.97 2170619.85 16-AUG-14:05 0.00 0.00 01-AUG-00:03
September 719812.41 2238599.07 22-SEP-12:23 0.00 0.00 01-SEP-00:10
October 605530.25 2455193.73 03-OCT-13:43 0.00 0.00 01-OCT-00:10
November 358371.15 2196299.69 06-NOV-09:33 0.00 0.00 01-NOV-00:10
December 245690.72 2354823.48 13-DEC-14:23 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 510254.12     0.00    
Minimum of Months 167215.42 1932540.85   0.00 0.00  
Maximum of Months 787642.97 2491131.39   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 169711.95 2998579.73 18-JAN-16:30 0.00 0.00 01-JAN-00:05
February 273610.65 2975668.88 23-FEB-16:20 0.00 0.00 01-FEB-00:10
March 293189.24 3014157.17 07-MAR-14:00 0.00 0.00 01-MAR-00:10
April 476838.99 2966214.28 26-APR-13:30 0.00 0.00 01-APR-00:10
May 738990.83 3292157.34 20-MAY-05:02 0.00 0.00 01-MAY-00:05
June 771684.18 3122106.43 08-JUN-05:02 0.00 0.00 01-JUN-00:10
July 757068.21 3138649.19 25-JUL-05:03 0.00 0.00 01-JUL-00:10
August 797305.62 3261455.20 26-AUG-05:02 0.00 0.00 01-AUG-00:03
September 738255.46 3347885.25 05-SEP-05:02 0.00 0.00 01-SEP-00:10
October 622476.36 3255158.60 21-OCT-05:03 0.00 0.00 01-OCT-00:10
November 366799.44 3025612.64 01-NOV-05:02 0.00 0.00 01-NOV-00:10
December 251743.72 2830913.99 12-DEC-16:40 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 522776.73     0.00    
Minimum of Months 169711.95 2830913.99   0.00 0.00  
Maximum of Months 797305.62 3347885.25   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 90985.71 750384.55 02-JAN-15:00 0.00 0.00 01-JAN-00:05
February 226495.30 1021650.35 02-FEB-13:05 0.00 0.00 01-FEB-00:10
March 432968.19 1316550.57 30-MAR-13:00 0.00 0.00 01-MAR-00:10
April 939511.51 1733308.67 28-APR-15:00 0.00 0.00 01-APR-00:10
May 729316.14 1093088.68 18-MAY-16:00 0.00 0.00 01-MAY-00:05
June 985893.36 1408648.46 14-JUN-14:00 0.00 0.00 01-JUN-00:10
July 1224783.09 1716604.18 21-JUL-16:00 0.00 0.00 01-JUL-00:10
August 1408488.59 1884368.38 30-AUG-16:10 0.00 0.00 01-AUG-00:03
September 697076.09 1255203.33 09-SEP-17:00 0.00 0.00 01-SEP-00:10
October 744760.28 1360671.54 05-OCT-15:00 0.00 0.00 01-OCT-00:10
November 524240.66 1362556.60 02-NOV-13:00 0.00 0.00 01-NOV-00:10
December 533670.37 1552012.87 13-DEC-15:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 714678.52     0.00    
Minimum of Months 90985.71 750384.55   0.00 0.00  
Maximum of Months 1408488.59 1884368.38   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 12861.20 42458.14 24-JAN-12:10
February 0.00 0.00 01-FEB-00:10 12836.61 42348.23 01-FEB-12:50
March 0.00 0.00 01-MAR-00:10 13081.12 41419.80 01-MAR-12:10
April 0.00 0.00 01-APR-00:10 11678.96 39130.17 03-APR-11:50
May 0.00 0.00 01-MAY-00:05 11281.75 36764.65 01-MAY-12:00
June 0.00 0.00 01-JUN-00:10 10890.43 34300.59 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 9857.49 32709.76 03-JUL-11:10
August 0.00 0.00 01-AUG-00:03 10755.65 33323.92 30-AUG-11:10
September 0.00 0.00 01-SEP-00:10 10628.06 35278.82 28-SEP-11:10
October 0.00 0.00 01-OCT-00:10 11282.93 37988.95 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 12146.80 40381.78 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 12314.87 41955.33 29-DEC-12:20
             
Annual Sum or Average 0.00     11628.05    
Minimum of Months 0.00 0.00   9857.49 32709.76  
Maximum of Months 0.00 0.00   13081.12 42458.14  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 234596.06 4014990.14 19-JAN-14:05 1414.10 163436.26 04-JAN-09:10
February 361835.55 3838190.02 24-FEB-13:05 1121.24 145718.63 04-FEB-08:40
March 428717.55 4501991.51 07-MAR-11:23 1619.85 168680.07 09-MAR-09:40
April 768012.36 5259705.56 28-APR-16:00 887.88 119201.66 10-APR-04:40
May 1785510.76 5759366.02 24-MAY-12:05 0.00 0.00 01-MAY-00:05
June 2088935.51 6248012.84 23-JUN-10:05 0.00 0.00 01-JUN-00:10
July 2454087.79 6569175.91 12-JUL-12:05 0.00 0.00 01-JUL-00:10
August 2380055.22 6308345.19 07-AUG-12:05 0.27 2448.82 20-AUG-04:40
September 1962776.09 5941165.23 18-SEP-14:05 0.00 0.00 01-SEP-00:10
October 1491334.40 6211309.49 06-OCT-14:05 194.09 98355.78 27-OCT-20:00
November 640527.19 5616826.75 01-NOV-14:05 728.60 128218.30 16-NOV-08:40
December 412202.63 4581787.35 12-DEC-14:20 1931.13 153318.02 20-DEC-11:40
             
Annual Sum or Average 1256768.67     657.07    
Minimum of Months 234596.06 3838190.02   0.00 0.00  
Maximum of Months 2454087.79 6569175.91   1931.13 168680.07  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.138133E+11 0.81 8854.31 01-JAN-00:13 1.37
February 0.119958E+11 0.77 8854.31 01-FEB-05:12 1.38
March 0.138322E+11 0.81 8854.31 01-MAR-05:12 1.38
April 0.126440E+11 0.76 8854.31 01-APR-04:12 1.38
May 0.139599E+11 0.81 8854.31 01-MAY-03:02 1.38
June 0.138225E+11 0.83 8854.31 01-JUN-04:12 1.38
July 0.136817E+11 0.79 8854.31 01-JUL-03:02 1.38
August 0.152234E+11 0.88 8854.31 01-AUG-03:02 1.38
September 0.142034E+11 0.85 8854.31 01-SEP-04:12 1.38
October 0.145671E+11 0.85 8854.31 01-OCT-14:23 1.36
November 0.139983E+11 0.84 8854.31 01-NOV-04:11 1.38
December 0.140037E+11 0.82 8854.31 01-DEC-05:12 1.38
           
Annual Sum or Average 0.165745E+12 0.82      
Minimum of Months 0.119958E+11 0.76 8854.31   1.36
Maximum of Months 0.152234E+11 0.88 8854.31   1.38



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.373762E+10 0.33 18805.95 02-JAN-05:12 1.76
February 0.394690E+10 0.35 18805.95 27-FEB-05:11 1.76
March 0.493319E+10 0.39 18805.95 07-MAR-14:00 1.75
April 0.586625E+10 0.47 18805.95 24-APR-05:02 1.76
May 0.592298E+10 0.44 18805.95 02-MAY-04:12 1.76
June 0.655657E+10 0.51 18805.95 01-JUN-04:12 1.76
July 0.704055E+10 0.53 18805.95 01-JUL-05:02 1.76
August 0.841054E+10 0.59 18805.95 01-AUG-05:02 1.76
September 0.564865E+10 0.44 18805.95 02-SEP-05:02 1.76
October 0.648926E+10 0.47 18805.95 03-OCT-04:11 1.76
November 0.551836E+10 0.42 18805.95 01-NOV-04:11 1.76
December 0.506289E+10 0.40 15740.36 11-DEC-06:02 1.57
           
Annual Sum or Average 0.691338E+11 0.45      
Minimum of Months 0.373762E+10 0.33 15740.36   1.57
Maximum of Months 0.841054E+10 0.59 18805.95   1.76



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.272883E+11 0.30 125552.13 21-JAN-06:02 1.44
February 0.271216E+11 0.31 122635.66 17-FEB-06:02 1.42
March 0.319894E+11 0.32 162677.36 27-MAR-05:03 1.68
April 0.368760E+11 0.34 174040.79 28-APR-05:03 1.76
May 0.513004E+11 0.41 174040.79 02-MAY-04:12 1.76
June 0.525413E+11 0.43 174040.79 06-JUN-04:11 1.76
July 0.509876E+11 0.42 174040.79 01-JUL-05:02 1.76
August 0.550313E+11 0.43 174040.79 01-AUG-05:02 1.76
September 0.463086E+11 0.40 174040.79 01-SEP-04:12 1.76
October 0.492775E+11 0.39 174040.79 04-OCT-05:02 1.76
November 0.352696E+11 0.33 174040.79 02-NOV-05:03 1.76
December 0.299024E+11 0.31 155512.91 11-DEC-06:02 1.64
           
Annual Sum or Average 0.493894E+12 0.37      
Minimum of Months 0.271216E+11 0.30 122635.66   1.42
Maximum of Months 0.550313E+11 0.43 174040.79   1.76



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.254471E+10 0.29 8925.85 02-JAN-06:03 1.09
February 0.261481E+10 0.30 8825.20 27-FEB-16:50 1.08
March 0.305208E+10 0.32 14388.48 30-MAR-05:02 1.46
April 0.369436E+10 0.33 19231.64 26-APR-13:30 1.76
May 0.564534E+10 0.41 19231.64 03-MAY-04:12 1.76
June 0.592128E+10 0.44 19231.64 14-JUN-05:02 1.76
July 0.569688E+10 0.43 19231.64 06-JUL-05:02 1.76
August 0.605336E+10 0.44 19231.64 03-AUG-05:02 1.76
September 0.483942E+10 0.39 19231.64 01-SEP-04:12 1.76
October 0.501545E+10 0.38 19231.64 04-OCT-05:02 1.76
November 0.316727E+10 0.31 18998.78 01-NOV-05:02 1.74
December 0.273382E+10 0.29 12043.52 11-DEC-06:02 1.31
           
Annual Sum or Average 0.509788E+11 0.36      
Minimum of Months 0.254471E+10 0.29 8825.20   1.08
Maximum of Months 0.605336E+10 0.44 19231.64   1.76



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.945595E+11 1.35 35304.47 01-JAN-00:05 1.34
February 0.854086E+11 1.35 35304.47 01-FEB-00:10 1.35
March 0.945595E+11 1.35 35304.47 01-MAR-00:20 1.34
April 0.915092E+11 1.35 35304.47 01-APR-00:10 1.35
May 0.945595E+11 1.35 35304.47 01-MAY-00:05 1.35
June 0.915092E+11 1.35 35304.47 01-JUN-00:10 1.35
July 0.945595E+11 1.35 35304.47 01-JUL-00:10 1.35
August 0.945595E+11 1.35 35304.47 01-AUG-00:03 1.35
September 0.915092E+11 1.35 35304.47 01-SEP-00:10 1.35
October 0.945595E+11 1.35 35304.47 01-OCT-00:10 1.35
November 0.915092E+11 1.35 35304.47 01-NOV-00:20 1.35
December 0.945595E+11 1.35 35304.47 01-DEC-00:20 1.35
           
Annual Sum or Average 0.111336E+13 1.35      
Minimum of Months 0.854086E+11 1.35 35304.47   1.34
Maximum of Months 0.945595E+11 1.35 35304.47   1.35



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.139498E+10 0.91 520.83 01-JAN-00:05 0.91
February 0.125999E+10 0.91 520.83 01-FEB-00:10 0.91
March 0.139498E+10 0.91 520.83 01-MAR-00:10 0.91
April 0.134998E+10 0.91 520.83 01-APR-00:10 0.91
May 0.139498E+10 0.91 520.83 01-MAY-00:05 0.91
June 0.134998E+10 0.91 520.83 01-JUN-00:10 0.91
July 0.139498E+10 0.91 520.83 01-JUL-00:10 0.91
August 0.139498E+10 0.91 520.83 01-AUG-00:03 0.91
September 0.134998E+10 0.91 520.83 01-SEP-00:10 0.91
October 0.139498E+10 0.91 520.83 01-OCT-00:10 0.91
November 0.134998E+10 0.91 520.83 01-NOV-00:10 0.91
December 0.139498E+10 0.91 520.83 01-DEC-00:10 0.91
           
Annual Sum or Average 0.164248E+11 0.91      
Minimum of Months 0.125999E+10 0.91 520.83   0.91
Maximum of Months 0.139498E+10 0.91 520.83   0.91



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.132987E+11 0.91 4965.17 01-JAN-00:05 0.91
February 0.120117E+11 0.91 4965.17 01-FEB-00:10 0.91
March 0.132987E+11 0.91 4965.17 01-MAR-00:10 0.91
April 0.128697E+11 0.91 4965.17 01-APR-00:10 0.91
May 0.132987E+11 0.91 4965.17 01-MAY-00:05 0.91
June 0.128697E+11 0.91 4965.17 01-JUN-00:10 0.91
July 0.132987E+11 0.91 4965.17 01-JUL-00:10 0.91
August 0.132987E+11 0.91 4965.17 01-AUG-00:03 0.91
September 0.128697E+11 0.91 4965.17 01-SEP-00:10 0.91
October 0.132987E+11 0.91 4965.17 01-OCT-00:10 0.91
November 0.128697E+11 0.91 4965.17 01-NOV-00:10 0.91
December 0.132987E+11 0.91 4965.17 01-DEC-00:10 0.91
           
Annual Sum or Average 0.156582E+12 0.91      
Minimum of Months 0.120117E+11 0.91 4965.17   0.91
Maximum of Months 0.132987E+11 0.91 4965.17   0.91



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.135611E+10 0.91 506.31 01-JAN-00:05 0.91
February 0.122487E+10 0.91 506.31 01-FEB-00:20 0.91
March 0.135611E+10 0.91 506.31 01-MAR-00:10 0.91
April 0.131236E+10 0.91 506.31 01-APR-00:10 0.91
May 0.135611E+10 0.91 506.31 01-MAY-00:05 0.91
June 0.131236E+10 0.91 506.31 01-JUN-00:20 0.91
July 0.135611E+10 0.91 506.31 01-JUL-00:10 0.91
August 0.135611E+10 0.91 506.31 01-AUG-00:03 0.91
September 0.131236E+10 0.91 506.31 01-SEP-00:10 0.91
October 0.135611E+10 0.91 506.31 01-OCT-00:10 0.91
November 0.131236E+10 0.91 506.31 01-NOV-00:10 0.91
December 0.135611E+10 0.91 506.31 01-DEC-00:10 0.91
           
Annual Sum or Average 0.159671E+11 0.91      
Minimum of Months 0.122487E+10 0.91 506.31   0.91
Maximum of Months 0.135611E+10 0.91 506.31   0.91



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 83513734.98 75913985.10 2637.86 09-JAN-06:03 2397.82 2397.82 40.26 5.13
February 42742867.62 38853266.67 2639.21 06-FEB-06:03 2399.04 2399.04 45.77 5.13
March 36518162.77 33195009.95 2548.57 11-MAR-06:02 2316.65 2316.65 37.12 4.69
April 2114550.35 1922126.27 756.35 18-APR-15:00 687.52 687.52 63.01 0.85
May 0.00 0.00 0.00 01-MAY-00:05 0.00 0.00 67.30 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 67.30 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 67.30 0.00
August 0.00 0.00 0.00 01-AUG-00:03 0.00 0.00 67.30 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 67.30 0.00
October 193117.54 175543.85 52.13 28-OCT-05:03 47.38 47.38 67.16 0.05
November 2815451.34 2559245.27 536.32 16-NOV-06:02 487.52 487.52 29.30 0.59
December 53709729.73 48822144.33 2636.50 21-DEC-06:01 2396.58 2396.58 39.68 5.12
                 
Annual Sum or Average 0.221608E+09 0.201441E+09            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 29.30 0.00
Maximum of Months 83513734.98 75913985.10 2639.21   2399.04 2399.04 67.30 5.13



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.412944E+09 0.375366E+09 12620.72 18-JAN-16:30 11472.23 11472.23 11.58 78.13
February 0.790646E+09 0.718697E+09 12770.12 27-FEB-16:50 11608.04 11608.04 12.22 78.53
March 0.846924E+09 0.769854E+09 12745.02 06-MAR-15:50 11585.22 11585.22 12.07 78.43
April 0.140074E+10 0.127328E+10 12472.22 26-APR-13:30 11337.25 11337.25 11.43 77.77
May 0.269367E+10 0.244855E+10 12770.12 02-MAY-05:04 11608.04 11608.04 10.74 78.53
June 0.261667E+10 0.237855E+10 12770.12 05-JUN-09:30 11608.04 11608.04 11.61 78.53
July 0.240861E+10 0.218943E+10 12770.12 06-JUL-05:02 11608.04 11608.04 9.39 78.53
August 0.266923E+10 0.242633E+10 12770.12 12-AUG-05:04 11608.04 11608.04 11.20 78.53
September 0.244066E+10 0.221856E+10 12770.12 05-SEP-05:02 11608.04 11608.04 9.61 78.53
October 0.216026E+10 0.196368E+10 12770.12 02-OCT-10:50 11608.04 11608.04 10.86 78.53
November 0.103766E+10 0.943233E+09 12770.12 01-NOV-05:02 11608.04 11608.04 9.33 78.53
December 0.713279E+09 0.648370E+09 12472.70 12-DEC-16:20 11337.68 11337.68 12.42 77.77
                 
Annual Sum or Average 0.201913E+11 0.183539E+11            
Minimum of Months 0.412944E+09 0.375366E+09 12472.22   11337.25 11337.25 9.33 77.77
Maximum of Months 0.269367E+10 0.244855E+10 12770.12   11608.04 11608.04 12.42 78.53



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.450145E+10 0.409182E+10 4394.66 01-JAN-04:13 3994.75 3994.75 6.92 39.26
February 0.524828E+10 0.477069E+10 4394.66 01-FEB-05:12 3994.75 3994.75 9.49 39.26
March 0.660074E+10 0.600007E+10 4394.66 01-MAR-05:12 3994.75 3994.75 10.14 39.26
April 0.878426E+10 0.798490E+10 4394.66 01-APR-04:12 3994.75 3994.75 9.63 39.26
May 0.857113E+10 0.779116E+10 4394.66 01-MAY-00:05 3994.75 3994.75 6.94 39.26
June 0.956903E+10 0.869824E+10 4394.66 01-JUN-04:12 3994.75 3994.75 12.99 39.26
July 0.105658E+11 0.960429E+10 4394.66 01-JUL-00:10 3994.75 3994.75 6.96 39.26
August 0.107664E+11 0.978666E+10 4394.66 01-AUG-00:20 3994.75 3994.75 6.97 39.26
September 0.850884E+10 0.773453E+10 4394.66 01-SEP-00:10 3994.75 3994.75 6.96 39.26
October 0.877249E+10 0.797420E+10 4394.66 01-OCT-07:30 3994.75 3994.75 8.26 39.26
November 0.720053E+10 0.654528E+10 4394.66 01-NOV-03:03 3994.75 3994.75 8.68 39.26
December 0.605299E+10 0.550217E+10 4394.66 01-DEC-05:12 3994.75 3994.75 7.21 39.26
                 
Annual Sum or Average 0.951419E+11 0.864840E+11            
Minimum of Months 0.450145E+10 0.409182E+10 4394.66   3994.75 3994.75 6.92 39.26
Maximum of Months 0.107664E+11 0.978666E+10 4394.66   3994.75 3994.75 12.99 39.26



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.145463E+09 0.132226E+09 4394.66 02-JAN-11:05 3994.75 3994.75 11.15 39.26
February 0.373107E+09 0.339154E+09 4394.66 01-FEB-13:40 3994.75 3994.75 15.43 19.63
March 0.416614E+09 0.378702E+09 4394.66 06-MAR-09:30 3994.75 3994.75 15.53 19.63
April 0.747093E+09 0.679107E+09 4394.66 04-APR-14:30 3994.75 3994.75 15.32 19.63
May 0.240836E+10 0.218920E+10 4394.66 01-MAY-07:30 3994.75 3994.75 15.47 19.63
June 0.257703E+10 0.234252E+10 4394.66 01-JUN-07:05 3994.75 3994.75 10.91 39.26
July 0.279533E+10 0.254096E+10 4394.66 03-JUL-07:40 3994.75 3994.75 15.44 19.63
August 0.306528E+10 0.278634E+10 4394.66 01-AUG-07:50 3994.75 3994.75 15.45 19.63
September 0.237918E+10 0.216268E+10 4394.66 01-SEP-07:20 3994.75 3994.75 15.50 19.63
October 0.201232E+10 0.182920E+10 4394.66 02-OCT-09:30 3994.75 3994.75 15.35 19.63
November 0.676778E+09 0.615191E+09 4394.66 01-NOV-07:20 3994.75 3994.75 15.61 19.63
December 0.423206E+09 0.384694E+09 4394.66 08-DEC-14:50 3994.75 3994.75 15.31 19.63
                 
Annual Sum or Average 0.180198E+11 0.163800E+11            
Minimum of Months 0.145463E+09 0.132226E+09 4394.66   3994.75 3994.75 10.91 19.63
Maximum of Months 0.306528E+10 0.278634E+10 4394.66   3994.75 3994.75 15.61 39.26



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.899374E+10 0.817531E+10 3357.88 01-JAN-00:05 3052.31 3052.31 18.99 14.16
February 0.812338E+10 0.738415E+10 3357.88 01-FEB-00:10 3052.31 3052.31 26.96 14.16
March 0.899374E+10 0.817531E+10 3357.88 01-MAR-00:10 3052.31 3052.31 30.33 14.16
April 0.870362E+10 0.791159E+10 3357.88 01-APR-00:10 3052.31 3052.31 38.37 14.16
May 0.899374E+10 0.817531E+10 3357.88 01-MAY-00:05 3052.31 3052.31 28.49 14.16
June 0.870362E+10 0.791159E+10 3357.88 01-JUN-00:10 3052.31 3052.31 32.63 14.16
July 0.899374E+10 0.817531E+10 3357.88 01-JUL-00:10 3052.31 3052.31 39.07 14.16
August 0.899374E+10 0.817531E+10 3357.88 01-AUG-00:03 3052.31 3052.31 43.38 14.16
September 0.870362E+10 0.791159E+10 3357.88 01-SEP-00:10 3052.31 3052.31 31.35 14.16
October 0.899374E+10 0.817531E+10 3357.88 01-OCT-00:10 3052.31 3052.31 31.85 14.16
November 0.870362E+10 0.791159E+10 3357.88 01-NOV-00:10 3052.31 3052.31 35.31 14.16
December 0.899374E+10 0.817531E+10 3357.88 01-DEC-00:10 3052.31 3052.31 22.60 14.16
                 
Annual Sum or Average 0.105894E+12 0.962577E+11            
Minimum of Months 0.812338E+10 0.738415E+10 3357.88   3052.31 3052.31 18.99 14.16
Maximum of Months 0.899374E+10 0.817531E+10 3357.88   3052.31 3052.31 43.38 14.16



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:05 16.86 16.86 56.11 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:02 16.86 16.86 57.25 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:03 16.86 16.86 56.78 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:02 16.86 16.86 56.49 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:03 16.86 16.86 57.61 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 56.34 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:02 16.86 16.86 56.70 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:02 16.86 16.86 57.53 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 56.84 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 57.00 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:02 16.86 16.86 56.17 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:02 16.86 16.86 56.30 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 56.11 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.61 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.176867E+11 0.160772E+11 33774.71 19-JAN-14:05 30701.21 30701.21 28.09 137.50
February 0.212740E+11 0.193381E+11 33765.99 24-FEB-13:05 30693.29 30693.29 27.78 137.50
March 0.265978E+11 0.241774E+11 33795.18 07-MAR-11:23 30719.82 30719.82 28.93 137.50
April 0.361469E+11 0.328575E+11 33795.18 25-APR-13:05 30719.82 30719.82 29.04 137.50
May 0.416648E+11 0.378733E+11 33795.18 01-MAY-09:00 30719.82 30719.82 28.98 137.50
June 0.462974E+11 0.420843E+11 33795.18 01-JUN-11:10 30719.82 30719.82 28.88 137.50
July 0.511953E+11 0.465365E+11 33795.18 03-JUL-08:70 30719.82 30719.82 29.60 137.50
August 0.529477E+11 0.481295E+11 33795.18 01-AUG-08:20 30719.82 30719.82 29.25 137.50
September 0.414797E+11 0.377051E+11 33795.18 01-SEP-07:50 30719.82 30719.82 29.44 137.50
October 0.410021E+11 0.372709E+11 33795.18 04-OCT-09:40 30719.82 30719.82 28.83 137.50
November 0.299887E+11 0.272598E+11 33795.18 01-NOV-10:50 30719.82 30719.82 29.05 137.50
December 0.246789E+11 0.224332E+11 33795.18 12-DEC-13:50 30719.82 30719.82 28.90 137.50
                 
Annual Sum or Average 0.430960E+12 0.391743E+12            
Minimum of Months 0.176867E+11 0.160772E+11 33765.99   30693.29 30693.29 27.78 137.50
Maximum of Months 0.529477E+11 0.481295E+11 33795.18   30719.82 30719.82 29.60 137.50



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 82.00 82.00 7225.17 933550.74 05-JAN-06:02
February 0.00 0.00 01-FEB-00:10 21.43 21.43 4026.18 835074.97 17-FEB-06:02
March 0.00 0.00 01-MAR-00:10 21.59 21.59 3217.62 880587.67 11-MAR-06:02
April 0.00 0.00 01-APR-00:10 21.11 21.11 116.68 88972.93 18-APR-14:10
May 0.00 0.00 01-MAY-00:05 67.30 67.30 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 67.30 67.30 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 67.30 67.30 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 67.30 67.30 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:10 67.30 67.30 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 67.30 67.30 6.22 3298.74 28-OCT-05:03
November 0.00 0.00 01-NOV-00:10 56.25 56.25 234.74 130346.61 16-NOV-06:02
December 0.00 0.00 01-DEC-00:10 24.62 24.62 4750.77 906570.56 21-DEC-06:01
                 
Annual Sum or Average 0.00         1628.68    
Minimum of Months 0.00 0.00   21.11 21.11 0.00 0.00  
Maximum of Months 0.00 0.00   82.00 82.00 7225.17 933550.74  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 167215.42 2342465.07 19-JAN-14:53 13.83 6.70 0.00 0.00 01-JAN-00:05
February 263105.39 2095464.09 22-FEB-15:03 13.07 6.70 0.00 0.00 01-FEB-00:10
March 284803.57 2187808.00 07-MAR-11:23 13.35 6.70 0.00 0.00 01-MAR-00:10
April 464071.96 2408420.20 14-APR-15:32 14.03 6.70 0.00 0.00 01-APR-00:10
May 710349.26 2491131.39 24-MAY-05:04 14.28 6.70 0.00 0.00 01-MAY-00:05
June 750522.24 2131112.45 13-JUN-15:33 13.18 6.70 0.00 0.00 01-JUN-00:10
July 750137.85 1932540.85 21-JUL-12:05 12.58 6.70 0.00 0.00 01-JUL-00:10
August 787642.97 2170619.85 16-AUG-14:05 13.30 6.70 0.00 0.00 01-AUG-00:03
September 719812.41 2238599.07 22-SEP-12:23 13.51 6.70 0.00 0.00 01-SEP-00:10
October 605530.25 2455193.73 03-OCT-13:43 14.17 6.70 0.00 0.00 01-OCT-00:10
November 358371.15 2196299.69 06-NOV-09:33 13.38 6.70 0.00 0.00 01-NOV-00:10
December 245690.72 2354823.48 13-DEC-14:23 13.86 6.70 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 510254.12         0.00    
Minimum of Months 167215.42 1932540.85   12.58 6.70 0.00 0.00  
Maximum of Months 787642.97 2491131.39   14.28 6.70 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 169711.95 2998579.73 18-JAN-16:30 15.87 11.58 0.00 0.00 01-JAN-00:05
February 273610.65 2975668.88 23-FEB-16:20 15.86 11.55 0.00 0.00 01-FEB-00:10
March 293189.24 3014157.17 07-MAR-14:00 15.89 11.61 0.00 0.00 01-MAR-00:10
April 476838.99 2966214.28 26-APR-13:30 15.81 11.54 0.00 0.00 01-APR-00:10
May 738990.83 3292157.34 20-MAY-05:02 16.72 11.70 0.00 0.00 01-MAY-00:05
June 771684.18 3122106.43 08-JUN-05:02 16.20 11.44 0.00 0.00 01-JUN-00:10
July 757068.21 3138649.19 25-JUL-05:03 16.37 11.46 0.00 0.00 01-JUL-00:10
August 797305.62 3261455.20 26-AUG-05:02 16.63 11.65 0.00 0.00 01-AUG-00:03
September 738255.46 3347885.25 05-SEP-05:02 16.89 11.78 0.00 0.00 01-SEP-00:10
October 622476.36 3255158.60 21-OCT-05:03 16.61 11.64 0.00 0.00 01-OCT-00:10
November 366799.44 3025612.64 01-NOV-05:02 15.91 11.29 0.00 0.00 01-NOV-00:10
December 251743.72 2830913.99 12-DEC-16:40 15.40 11.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 522776.73         0.00    
Minimum of Months 169711.95 2830913.99   15.40 11.29 0.00 0.00  
Maximum of Months 797305.62 3347885.25   16.89 11.78 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 90985.71 750384.55 02-JAN-15:00 33.41 28.95 0.00 0.00 01-JAN-00:05
February 226495.30 1021650.35 02-FEB-13:05 38.76 31.43 0.00 0.00 01-FEB-00:10
March 432968.19 1316550.57 30-MAR-13:00 44.51 34.05 0.00 0.00 01-MAR-00:10
April 939511.51 1733308.67 28-APR-15:00 52.54 39.28 0.00 0.00 01-APR-00:10
May 729316.14 1093088.68 18-MAY-16:00 40.16 35.40 0.00 0.00 01-MAY-00:05
June 985893.36 1408648.46 14-JUN-14:00 46.29 38.48 0.00 0.00 01-JUN-00:10
July 1224783.09 1716604.18 21-JUL-16:00 52.22 41.10 0.00 0.00 01-JUL-00:10
August 1408488.59 1884368.38 30-AUG-16:10 55.42 42.10 0.00 0.00 01-AUG-00:03
September 697076.09 1255203.33 09-SEP-17:00 43.32 38.53 0.00 0.00 01-SEP-00:10
October 744760.28 1360671.54 05-OCT-15:00 45.37 37.50 0.00 0.00 01-OCT-00:10
November 524240.66 1362556.60 02-NOV-13:00 45.40 34.75 0.00 0.00 01-NOV-00:10
December 533670.37 1552012.87 13-DEC-15:00 49.06 35.90 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 714678.52         0.00    
Minimum of Months 90985.71 750384.55   33.41 28.95 0.00 0.00  
Maximum of Months 1408488.59 1884368.38   55.42 42.10 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.62 57.62 12861.20 42458.14 24-JAN-12:10
February 0.00 0.00 01-FEB-00:10 57.61 57.61 12836.61 42348.23 01-FEB-12:50
March 0.00 0.00 01-MAR-00:10 57.29 57.29 13081.12 41419.80 01-MAR-12:10
April 0.00 0.00 01-APR-00:10 56.91 56.91 11678.96 39130.17 03-APR-11:50
May 0.00 0.00 01-MAY-00:05 58.21 58.21 11281.75 36764.65 01-MAY-12:00
June 0.00 0.00 01-JUN-00:10 56.78 56.78 10890.43 34300.59 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 57.00 57.00 9857.49 32709.76 03-JUL-11:10
August 0.00 0.00 01-AUG-00:03 58.22 58.22 10755.65 33323.92 30-AUG-11:10
September 0.00 0.00 01-SEP-00:10 57.19 57.19 10628.06 35278.82 28-SEP-11:10
October 0.00 0.00 01-OCT-00:10 57.75 57.75 11282.93 37988.95 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 56.57 56.57 12146.80 40381.78 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 56.91 56.91 12314.87 41955.33 29-DEC-12:20
                 
Annual Sum or Average 0.00         11628.05    
Minimum of Months 0.00 0.00   56.57 56.57 9857.49 32709.76  
Maximum of Months 0.00 0.00   58.22 58.22 13081.12 42458.14  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 234596.06 4014990.14 19-JAN-14:05 28.09 24.15 1414.10 163436.26 04-JAN-09:10
February 361835.55 3838190.02 24-FEB-13:05 27.78 23.99 1121.24 145718.63 04-FEB-08:40
March 428717.55 4501991.51 07-MAR-11:23 28.93 24.97 1619.85 168680.07 09-MAR-09:40
April 768012.36 5259705.56 28-APR-16:00 30.25 27.11 887.88 119201.66 10-APR-04:40
May 1785510.76 5759366.02 24-MAY-12:05 31.12 27.24 0.00 0.00 01-MAY-00:05
June 2088935.51 6248012.84 23-JUN-10:05 31.97 27.99 0.00 0.00 01-JUN-00:10
July 2454087.79 6569175.91 12-JUL-12:05 32.53 28.33 0.00 0.00 01-JUL-00:10
August 2380055.22 6308345.19 07-AUG-12:05 32.08 28.02 0.27 2448.82 20-AUG-04:40
September 1962776.09 5941165.23 18-SEP-14:05 31.44 28.08 0.00 0.00 01-SEP-00:10
October 1491334.40 6211309.49 06-OCT-14:05 31.91 28.34 194.09 98355.78 27-OCT-20:00
November 640527.19 5616826.75 01-NOV-14:05 30.87 26.99 728.60 128218.30 16-NOV-08:40
December 412202.63 4581787.35 12-DEC-14:20 29.07 25.84 1931.13 153318.02 20-DEC-11:40
                 
Annual Sum or Average 1256768.67         657.07    
Minimum of Months 234596.06 3838190.02   27.78 23.99 0.00 0.00  
Maximum of Months 2454087.79 6569175.91   32.53 28.34 1931.13 168680.07  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 76398653.87 0.00 0.407378E+11 0.373762E+10 0.00 0.00
February 28035105.07 0.00 0.584076E+11 0.394690E+10 0.00 0.00
March 9355482.56 0.00 0.732320E+11 0.493319E+10 0.00 0.00
April 9921841.32 0.00 0.117939E+12 0.586625E+10 0.00 0.00
May 0.00 0.00 0.147724E+12 0.592298E+10 0.00 0.00
June 0.00 0.00 0.160087E+12 0.655657E+10 0.00 0.00
July 0.00 0.00 0.173226E+12 0.704055E+10 0.00 0.00
August 0.00 0.00 0.190555E+12 0.841054E+10 0.00 0.00
September 0.00 0.00 0.148453E+12 0.564865E+10 0.00 0.00
October 0.00 0.00 0.139552E+12 0.648926E+10 0.00 0.00
November 35210.31 0.00 0.888054E+11 0.551836E+10 0.00 0.00
December 44773812.01 0.00 0.665451E+11 0.506289E+10 0.00 0.00
             
Annual Sum or Average 0.168520E+09 0.00 0.140526E+13 0.691338E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.407378E+11 0.373762E+10 0.00 0.00
Maximum of Months 76398653.87 0.00 0.190555E+12 0.841054E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.140003E+11 0.00 0.332217E+12 0.272883E+11 0.00 0.00
February 0.637300E+10 0.00 0.464006E+12 0.271216E+11 0.00 0.00
March 0.615758E+10 0.00 0.552730E+12 0.319894E+11 0.00 0.00
April 0.114867E+09 0.00 0.859903E+12 0.368760E+11 0.00 0.00
May 0.00 0.00 0.134360E+13 0.513004E+11 0.00 0.00
June 0.00 0.00 0.137170E+13 0.525413E+11 0.00 0.00
July 0.00 0.00 0.142114E+13 0.509876E+11 0.00 0.00
August 0.00 0.00 0.147730E+13 0.550313E+11 0.00 0.00
September 0.00 0.00 0.132294E+13 0.463086E+11 0.00 0.00
October 0.00 0.00 0.116523E+13 0.492775E+11 0.00 0.00
November 0.292197E+09 0.00 0.679224E+12 0.352696E+11 0.00 0.00
December 0.893435E+10 0.00 0.474759E+12 0.299024E+11 0.00 0.00
             
Annual Sum or Average 0.358723E+11 0.00 0.114647E+14 0.493894E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.332217E+12 0.271216E+11 0.00 0.00
Maximum of Months 0.140003E+11 0.00 0.147730E+13 0.550313E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.563984E+10 0.00 0.315440E+11 0.254471E+10 0.00 0.00
February 0.342717E+10 0.00 0.459332E+11 0.261481E+10 0.00 0.00
March 0.253002E+10 0.00 0.561534E+11 0.305208E+10 0.00 0.00
April 36507643.62 0.00 0.904892E+11 0.369436E+10 0.00 0.00
May 0.00 0.00 0.148399E+12 0.564534E+10 0.00 0.00
June 0.00 0.00 0.153675E+12 0.592128E+10 0.00 0.00
July 0.00 0.00 0.158838E+12 0.569688E+10 0.00 0.00
August 0.00 0.00 0.163099E+12 0.605336E+10 0.00 0.00
September 0.00 0.00 0.142381E+12 0.483942E+10 0.00 0.00
October 51455399.49 0.00 0.124186E+12 0.501545E+10 0.00 0.00
November 0.420846E+09 0.00 0.656816E+11 0.316727E+10 0.00 0.00
December 0.387473E+10 0.00 0.452225E+11 0.273382E+10 0.00 0.00
             
Annual Sum or Average 0.159806E+11 0.00 0.122560E+13 0.509788E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.315440E+11 0.254471E+10 0.00 0.00
Maximum of Months 0.563984E+10 0.00 0.163099E+12 0.605336E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.218475E+11 0.138133E+11 0.00 0.00
February 0.00 0.00 0.262581E+11 0.119958E+11 0.00 0.00
March 0.00 0.00 0.351738E+11 0.138322E+11 0.00 0.00
April 86.00 0.00 0.551412E+11 0.126440E+11 0.00 0.00
May 0.00 0.00 0.100822E+12 0.139599E+11 0.00 0.00
June 0.00 0.00 0.105783E+12 0.138225E+11 0.00 0.00
July 0.00 0.00 0.114257E+12 0.136817E+11 0.00 0.00
August 0.00 0.00 0.127008E+12 0.152234E+11 0.00 0.00
September 0.00 0.00 0.108262E+12 0.142034E+11 0.00 0.00
October 0.00 0.00 0.933220E+11 0.145671E+11 0.00 0.00
November 0.00 0.00 0.521962E+11 0.139983E+11 0.00 0.00
December 176.94 0.00 0.339305E+11 0.140037E+11 0.00 0.00
             
Annual Sum or Average 262.94 0.00 0.874001E+12 0.165745E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.218475E+11 0.119958E+11 0.00 0.00
Maximum of Months 176.94 0.00 0.127008E+12 0.152234E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.510692E+11 0.155479E+12 0.00 18.01
February 0.00 0.00 0.188031E+12 0.181760E+12 0.00 20.82
March 0.00 0.00 0.458976E+12 0.266775E+12 0.00 27.72
April 0.00 0.00 0.108378E+13 0.340909E+12 0.00 7.41
May 0.00 0.00 0.455567E+12 0.201368E+12 0.00 0.00
June 0.00 0.00 0.753200E+12 0.268841E+12 0.00 0.00
July 0.00 0.00 0.110185E+13 0.354495E+12 0.00 0.00
August 0.00 0.00 0.140283E+13 0.417174E+12 0.00 0.00
September 0.00 0.00 0.444389E+12 0.194049E+12 0.00 0.00
October 0.00 0.00 0.629805E+12 0.254032E+12 0.00 5.96
November 0.00 0.00 0.533247E+12 0.253344E+12 0.00 17.54
December 0.00 0.00 0.631389E+12 0.303226E+12 0.00 28.64
             
Annual Sum or Average 0.00 0.00 0.773414E+13 0.319145E+13 0.00 126.10
Minimum of Months 0.00 0.00 0.510692E+11 0.155479E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.140283E+13 0.417174E+12 0.00 28.64



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.639531E+10 0.262275E+10 0.00 0.00
February 0.00 0.00 0.117839E+11 0.345725E+10 0.00 0.00
March 0.00 0.00 0.194385E+11 0.504516E+10 0.00 0.00
April 0.00 0.00 0.256870E+11 0.650874E+10 0.00 0.00
May 0.00 0.00 0.851024E+10 0.336106E+10 0.00 0.00
June 0.00 0.00 0.147356E+11 0.476994E+10 0.00 0.00
July 0.00 0.00 0.218866E+11 0.648958E+10 0.00 0.00
August 0.00 0.00 0.284255E+11 0.792923E+10 0.00 0.00
September 0.00 0.00 0.824938E+10 0.322412E+10 0.00 0.00
October 0.00 0.00 0.146526E+11 0.457165E+10 0.00 0.00
November 0.00 0.00 0.192613E+11 0.504127E+10 0.00 0.00
December 0.00 0.00 0.255056E+11 0.606966E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.204532E+12 0.590904E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.639531E+10 0.262275E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.284255E+11 0.792923E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.470484E+11 0.225026E+11 0.00 0.00
February 0.00 0.00 0.101756E+12 0.311674E+11 0.00 0.00
March 0.00 0.00 0.176846E+12 0.467354E+11 0.00 0.00
April 0.00 0.00 0.242752E+12 0.617328E+11 0.00 0.00
May 0.00 0.00 0.791288E+11 0.316095E+11 0.00 0.00
June 0.00 0.00 0.139971E+12 0.453696E+11 0.00 0.00
July 0.00 0.00 0.208601E+12 0.618650E+11 0.00 0.00
August 0.00 0.00 0.270077E+12 0.754306E+11 0.00 0.00
September 0.00 0.00 0.754742E+11 0.300564E+11 0.00 0.00
October 0.00 0.00 0.136830E+12 0.430606E+11 0.00 0.00
November 0.00 0.00 0.176584E+12 0.469244E+11 0.00 0.00
December 0.00 0.00 0.232413E+12 0.562229E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.188748E+13 0.552677E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.470484E+11 0.225026E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.270077E+12 0.754306E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.340750E+10 0.203696E+10 0.00 0.00
February 0.00 0.00 0.923607E+10 0.298075E+10 0.00 0.00
March 0.00 0.00 0.170512E+11 0.460448E+10 0.00 0.00
April 0.00 0.00 0.241606E+11 0.619425E+10 0.00 0.00
May 0.00 0.00 0.811559E+10 0.323543E+10 0.00 0.00
June 0.00 0.00 0.142235E+11 0.461730E+10 0.00 0.00
July 0.00 0.00 0.211039E+11 0.627440E+10 0.00 0.00
August 0.00 0.00 0.272330E+11 0.763245E+10 0.00 0.00
September 0.00 0.00 0.771155E+10 0.307069E+10 0.00 0.00
October 0.00 0.00 0.136474E+11 0.433613E+10 0.00 0.00
November 0.00 0.00 0.170853E+11 0.463171E+10 0.00 0.00
December 0.00 0.00 0.222573E+11 0.550486E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.185233E+12 0.551194E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.340750E+10 0.203696E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.272330E+11 0.763245E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.373762E+10 0.407378E+11 76398653.87 0.371027E+09 0.786168E+09 0.00 0.00 0.00
February 0.394690E+10 0.584076E+11 28035105.07 0.122969E+09 0.131824E+10 0.00 0.00 0.00
March 0.493319E+10 0.732320E+11 9355482.56 73741737.39 0.253549E+10 0.00 0.00 0.00
April 0.586625E+10 0.117939E+12 9921841.32 0.00 0.724492E+10 0.00 0.00 0.00
May 0.592298E+10 0.147724E+12 0.00 0.00 0.307043E+11 0.00 0.00 0.00
June 0.655657E+10 0.160087E+12 0.00 0.00 0.374962E+11 0.00 0.00 0.00
July 0.704055E+10 0.173226E+12 0.00 0.00 0.410566E+11 0.00 0.00 0.00
August 0.841054E+10 0.190555E+12 0.00 0.00 0.400281E+11 0.00 0.00 0.00
September 0.564865E+10 0.148453E+12 0.00 0.00 0.266989E+11 0.00 0.00 0.00
October 0.648926E+10 0.139552E+12 0.00 0.00 0.226731E+11 0.00 0.00 0.00
November 0.551836E+10 0.888054E+11 35210.31 0.00 0.526649E+10 0.00 0.00 0.00
December 0.506289E+10 0.665451E+11 44773812.01 0.194017E+09 0.300058E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.691338E+11 0.140526E+13 0.168520E+09 0.761755E+09 0.218809E+12 0.00 0.00 0.00
Minimum of Months 0.373762E+10 0.407378E+11 0.00 0.00 0.786168E+09 0.00 0.00 0.00
Maximum of Months 0.841054E+10 0.190555E+12 76398653.87 0.371027E+09 0.410566E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.272883E+11 0.332217E+12 0.140003E+11 0.561632E+10 0.920915E+10 0.00 0.00 0.00
February 0.271216E+11 0.464006E+12 0.637300E+10 0.244923E+10 0.154801E+11 0.00 0.00 0.00
March 0.319894E+11 0.552730E+12 0.615758E+10 0.143425E+10 0.288072E+11 0.00 0.00 0.00
April 0.368760E+11 0.859903E+12 0.114867E+09 17572415.10 0.726479E+11 0.00 0.00 0.00
May 0.513004E+11 0.134360E+13 0.00 0.00 0.309344E+12 0.00 0.00 0.00
June 0.525413E+11 0.137170E+13 0.00 0.00 0.378448E+12 0.00 0.00 0.00
July 0.509876E+11 0.142114E+13 0.00 0.00 0.415311E+12 0.00 0.00 0.00
August 0.550313E+11 0.147730E+13 0.00 0.00 0.406363E+12 0.00 0.00 0.00
September 0.463086E+11 0.132294E+13 0.00 0.00 0.272367E+12 0.00 0.00 0.00
October 0.492775E+11 0.116523E+13 0.00 0.00 0.230157E+12 0.00 0.00 0.00
November 0.352696E+11 0.679224E+12 0.292197E+09 11185106.54 0.575297E+11 0.00 0.00 0.00
December 0.299024E+11 0.474759E+12 0.893435E+10 0.416481E+10 0.318927E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.493894E+12 0.114647E+14 0.358723E+11 0.136934E+11 0.222756E+13 0.00 0.00 0.00
Minimum of Months 0.271216E+11 0.332217E+12 0.00 0.00 0.920915E+10 0.00 0.00 0.00
Maximum of Months 0.550313E+11 0.147730E+13 0.140003E+11 0.561632E+10 0.415311E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.254471E+10 0.315440E+11 0.563984E+10 0.989687E+09 0.198736E+09 0.00 0.00 0.00
February 0.261481E+10 0.459332E+11 0.342717E+10 0.452610E+09 0.727099E+09 0.00 0.00 0.00
March 0.305208E+10 0.561534E+11 0.253002E+10 0.290626E+09 0.185947E+10 0.00 0.00 0.00
April 0.369436E+10 0.904892E+11 36507643.62 0.00 0.612280E+10 0.00 0.00 0.00
May 0.564534E+10 0.148399E+12 0.00 0.00 0.294211E+11 0.00 0.00 0.00
June 0.592128E+10 0.153675E+12 0.00 0.00 0.360639E+11 0.00 0.00 0.00
July 0.569688E+10 0.158838E+12 0.00 0.00 0.395052E+11 0.00 0.00 0.00
August 0.605336E+10 0.163099E+12 0.00 0.00 0.386973E+11 0.00 0.00 0.00
September 0.483942E+10 0.142381E+12 0.00 0.00 0.259587E+11 0.00 0.00 0.00
October 0.501545E+10 0.124186E+12 51455399.49 0.00 0.221322E+11 0.00 0.00 0.00
November 0.316727E+10 0.656816E+11 0.420846E+09 1976253.21 0.542858E+10 0.00 0.00 0.00
December 0.273382E+10 0.452225E+11 0.387473E+10 0.705733E+09 0.275343E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.509788E+11 0.122560E+13 0.159806E+11 0.244063E+10 0.208868E+12 0.00 0.00 0.00
Minimum of Months 0.254471E+10 0.315440E+11 0.00 0.00 0.198736E+09 0.00 0.00 0.00
Maximum of Months 0.605336E+10 0.163099E+12 0.563984E+10 0.989687E+09 0.395052E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.138133E+11 0.218475E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.119958E+11 0.262581E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138322E+11 0.351738E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.126440E+11 0.551412E+11 86.00 0.00 0.00 0.00 0.00 0.00
May 0.139599E+11 0.100822E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.138225E+11 0.105783E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.136817E+11 0.114257E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.152234E+11 0.127008E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142034E+11 0.108262E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.145671E+11 0.933220E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139983E+11 0.521962E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140037E+11 0.339305E+11 176.94 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.165745E+12 0.874001E+12 262.94 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119958E+11 0.218475E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.152234E+11 0.127008E+12 176.94 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.945595E+11 0.385540E+11 0.00 0.00 0.00 0.481877E+11 0.00 0.00
February 0.854086E+11 0.147646E+12 0.00 0.00 0.00 0.557158E+11 0.00 0.00
March 0.945595E+11 0.361275E+12 0.00 0.00 0.00 0.741796E+11 0.00 0.00
April 0.915092E+11 0.854292E+12 0.00 0.00 0.00 0.198197E+11 0.00 0.00
May 0.945595E+11 0.348758E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.915092E+11 0.575869E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.945595E+11 0.841916E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.945595E+11 0.108022E+13 0.00 0.00 0.00 1326219.53 0.00 0.00
September 0.915092E+11 0.341849E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.945595E+11 0.486348E+12 0.00 0.00 0.00 0.159447E+11 0.00 0.00
November 0.915092E+11 0.418573E+12 0.00 0.00 0.00 0.469497E+11 0.00 0.00
December 0.945595E+11 0.499724E+12 0.00 0.00 0.00 0.766568E+11 0.00 0.00
                 
Annual Sum or Average 0.111336E+13 0.599502E+13 0.00 0.00 0.00 0.337455E+12 0.00 0.00
Minimum of Months 0.854086E+11 0.385540E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.945595E+11 0.108022E+13 0.00 0.00 0.00 0.766568E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.139498E+10 0.516755E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125999E+10 0.958665E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.139498E+10 0.157883E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134998E+10 0.205283E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139498E+10 0.654416E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134998E+10 0.113157E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.139498E+10 0.167920E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.139498E+10 0.218913E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134998E+10 0.637524E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.139498E+10 0.114759E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134998E+10 0.155700E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.139498E+10 0.208309E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.164248E+11 0.161866E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125999E+10 0.516755E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139498E+10 0.218913E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.132987E+11 0.378445E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.120117E+11 0.826001E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.132987E+11 0.143409E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128697E+11 0.193889E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132987E+11 0.608180E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.128697E+11 0.107471E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.132987E+11 0.160035E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.132987E+11 0.207945E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128697E+11 0.582875E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.132987E+11 0.107068E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.128697E+11 0.142529E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.132987E+11 0.189489E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.156582E+12 0.149138E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.120117E+11 0.378445E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.132987E+11 0.207945E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.135611E+10 0.272664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.122487E+10 0.748019E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.135611E+10 0.138028E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.131236E+10 0.192787E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135611E+10 0.623627E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.131236E+10 0.109185E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.135611E+10 0.161857E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.135611E+10 0.209567E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.131236E+10 0.595322E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.135611E+10 0.106674E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.131236E+10 0.137660E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.135611E+10 0.181086E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.159671E+11 0.146081E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122487E+10 0.272664E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135611E+10 0.209567E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.373762E+10 76398653.87 0.407378E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.394690E+10 28035105.07 0.584076E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.493319E+10 9355482.56 0.732320E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.586625E+10 9921841.32 0.117939E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.592298E+10 0.00 0.147724E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.655657E+10 0.00 0.160087E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.704055E+10 0.00 0.173226E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.841054E+10 0.00 0.190555E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.564865E+10 0.00 0.148453E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.648926E+10 0.00 0.139552E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.551836E+10 35210.31 0.888054E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.506289E+10 44773812.01 0.665451E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.691338E+11 0.168520E+09 0.140526E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.373762E+10 0.00 0.407378E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.841054E+10 76398653.87 0.190555E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.272883E+11 0.140003E+11 0.332217E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.271216E+11 0.637300E+10 0.464006E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.319894E+11 0.615758E+10 0.552730E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.368760E+11 0.114867E+09 0.859903E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.513004E+11 0.00 0.134360E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.525413E+11 0.00 0.137170E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.509876E+11 0.00 0.142114E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.550313E+11 0.00 0.147730E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.463086E+11 0.00 0.132294E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.492775E+11 0.00 0.116523E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.352696E+11 0.292197E+09 0.679224E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.299024E+11 0.893435E+10 0.474759E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.493894E+12 0.358723E+11 0.114647E+14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.271216E+11 0.00 0.332217E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.550313E+11 0.140003E+11 0.147730E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.254471E+10 0.563984E+10 0.315440E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.261481E+10 0.342717E+10 0.459332E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.305208E+10 0.253002E+10 0.561534E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.369436E+10 36507643.62 0.904892E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.564534E+10 0.00 0.148399E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.592128E+10 0.00 0.153675E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.569688E+10 0.00 0.158838E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.605336E+10 0.00 0.163099E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.483942E+10 0.00 0.142381E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.501545E+10 51455399.49 0.124186E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.316727E+10 0.420846E+09 0.656816E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.273382E+10 0.387473E+10 0.452225E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.509788E+11 0.159806E+11 0.122560E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.254471E+10 0.00 0.315440E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.605336E+10 0.563984E+10 0.163099E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.138133E+11 0.00 0.218475E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.119958E+11 0.00 0.262581E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138322E+11 0.00 0.351738E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.126440E+11 86.00 0.551412E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139599E+11 0.00 0.100822E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.138225E+11 0.00 0.105783E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.136817E+11 0.00 0.114257E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.152234E+11 0.00 0.127008E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142034E+11 0.00 0.108262E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.145671E+11 0.00 0.933220E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139983E+11 0.00 0.521962E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140037E+11 176.94 0.339305E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.165745E+12 262.94 0.874001E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119958E+11 0.00 0.218475E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.152234E+11 176.94 0.127008E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.945595E+11 0.00 0.510692E+11 0.00 0.125152E+11 0.00 0.00 0.00 0.484046E+11 0.00 0.00 0.00
February 0.854086E+11 0.00 0.188031E+12 0.00 0.403847E+11 0.00 0.00 0.00 0.559666E+11 0.00 0.00 0.00
March 0.945595E+11 0.00 0.458976E+12 0.00 0.977015E+11 0.00 0.00 0.00 0.745135E+11 0.00 0.00 0.00
April 0.915092E+11 0.00 0.108378E+13 0.00 0.229491E+12 0.00 0.00 0.00 0.199089E+11 0.00 0.00 0.00
May 0.945595E+11 0.00 0.455567E+12 0.00 0.106809E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.915092E+11 0.00 0.753200E+12 0.00 0.177331E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.945595E+11 0.00 0.110185E+13 0.00 0.259935E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.945595E+11 0.00 0.140283E+13 0.00 0.322613E+12 0.00 0.00 0.00 1332189.38 0.00 0.00 0.00
September 0.915092E+11 0.00 0.444389E+12 0.00 0.102540E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.945595E+11 0.00 0.629805E+12 0.00 0.143456E+12 0.00 0.00 0.00 0.160164E+11 0.00 0.00 0.00
November 0.915092E+11 0.00 0.533247E+12 0.00 0.114674E+12 0.00 0.00 0.00 0.471610E+11 0.00 0.00 0.00
December 0.945595E+11 0.00 0.631389E+12 0.00 0.131665E+12 0.00 0.00 0.00 0.770019E+11 0.00 0.00 0.00
                         
Annual Sum or Average 0.111336E+13 0.00 0.773414E+13 0.00 0.173912E+13 0.00 0.00 0.00 0.338974E+12 0.00 0.00 0.00
Minimum of Months 0.854086E+11 0.00 0.510692E+11 0.00 0.125152E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.945595E+11 0.00 0.140283E+13 0.00 0.322613E+12 0.00 0.00 0.00 0.770019E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.139498E+10 0.00 0.639531E+10 0.00 0.122776E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125999E+10 0.00 0.117839E+11 0.00 0.219726E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.139498E+10 0.00 0.194385E+11 0.00 0.365018E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134998E+10 0.00 0.256870E+11 0.00 0.515875E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139498E+10 0.00 0.851024E+10 0.00 0.196608E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134998E+10 0.00 0.147356E+11 0.00 0.341995E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.139498E+10 0.00 0.218866E+11 0.00 0.509460E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.139498E+10 0.00 0.284255E+11 0.00 0.653424E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134998E+10 0.00 0.824938E+10 0.00 0.187413E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.139498E+10 0.00 0.146526E+11 0.00 0.317667E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134998E+10 0.00 0.192613E+11 0.00 0.369128E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.139498E+10 0.00 0.255056E+11 0.00 0.467468E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.164248E+11 0.00 0.204532E+12 0.00 0.426656E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125999E+10 0.00 0.639531E+10 0.00 0.122776E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139498E+10 0.00 0.284255E+11 0.00 0.653424E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.132987E+11 0.00 0.470484E+11 0.00 0.920388E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.120117E+11 0.00 0.101756E+12 0.00 0.191557E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.132987E+11 0.00 0.176846E+12 0.00 0.334367E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128697E+11 0.00 0.242752E+12 0.00 0.488631E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132987E+11 0.00 0.791288E+11 0.00 0.183108E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.128697E+11 0.00 0.139971E+12 0.00 0.324999E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.132987E+11 0.00 0.208601E+12 0.00 0.485663E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.132987E+11 0.00 0.270077E+12 0.00 0.621319E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128697E+11 0.00 0.754742E+11 0.00 0.171867E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.132987E+11 0.00 0.136830E+12 0.00 0.297619E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.128697E+11 0.00 0.176584E+12 0.00 0.340547E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.132987E+11 0.00 0.232413E+12 0.00 0.429242E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.156582E+12 0.00 0.188748E+13 0.00 0.396096E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.120117E+11 0.00 0.470484E+11 0.00 0.920388E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.132987E+11 0.00 0.270077E+12 0.00 0.621319E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.135611E+10 0.00 0.340750E+10 0.00 0.680856E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.122487E+10 0.00 0.923607E+10 0.00 0.175587E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.135611E+10 0.00 0.170512E+11 0.00 0.324837E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.131236E+10 0.00 0.241606E+11 0.00 0.488189E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135611E+10 0.00 0.811559E+10 0.00 0.187932E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.131236E+10 0.00 0.142235E+11 0.00 0.330494E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.135611E+10 0.00 0.211039E+11 0.00 0.491829E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.135611E+10 0.00 0.272330E+11 0.00 0.627634E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.131236E+10 0.00 0.771155E+10 0.00 0.175833E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.135611E+10 0.00 0.136474E+11 0.00 0.298002E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.131236E+10 0.00 0.170853E+11 0.00 0.331935E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.135611E+10 0.00 0.222573E+11 0.00 0.414875E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.159671E+11 0.00 0.185233E+12 0.00 0.391523E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122487E+10 0.00 0.340750E+10 0.00 0.680856E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135611E+10 0.00 0.272330E+11 0.00 0.627634E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.279368E+09 0.152358E+10 0.00 0.107464E+09 0.00 0.00 0.538933E+11 0.00 0.93
February 0.203171E+09 0.153524E+10 0.00 85085475.22 4083793.90 0.00 0.403927E+11 0.00 1.02
March 0.118092E+09 0.314732E+10 0.00 91289313.20 6520587.70 0.00 0.434997E+11 0.00 1.02
April 0.126409E+09 0.542491E+10 0.00 61925515.93 72042479.35 0.00 0.192829E+11 0.00 0.89
May 0.00 0.257634E+11 0.00 1588352.37 0.145719E+09 0.00 5088268.63 0.00 0.33
June 3106222.87 0.311490E+11 0.00 2272032.17 0.207342E+09 0.00 95340522.45 0.00 0.35
July 0.00 0.380237E+11 0.00 0.00 0.401555E+09 0.00 0.00 0.00 0.31
August 0.00 0.389618E+11 0.00 207598.52 0.229528E+09 0.00 14804261.11 0.00 0.34
September 0.00 0.291637E+11 0.00 1394292.55 0.290000E+09 0.00 76636654.17 0.00 0.33
October 0.111924E+09 0.219932E+11 0.00 40334485.07 0.229766E+09 0.00 0.115565E+11 0.00 0.64
November 0.201776E+09 0.657596E+10 0.00 99636100.23 7638927.75 0.00 0.347602E+11 0.00 1.07
December 0.324190E+09 0.414262E+10 0.00 0.105811E+09 11495095.65 0.00 0.481995E+11 0.00 0.91
                   
Annual Sum or Average 0.136804E+10 0.207404E+12 0.00 0.597009E+09 0.160569E+10 0.00 0.251777E+12 0.00 0.68
Minimum of Months 0.00 0.152358E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.324190E+09 0.389618E+11 0.00 0.107464E+09 0.401555E+09 0.00 0.538933E+11 0.00 1.07



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.240118E+10 0.221691E+10 0.00 60671054.28 0.00 0.00 0.305337E+11 0.00 0.51
February 0.182987E+10 0.258494E+10 0.00 51384847.71 35343703.76 0.00 0.188923E+11 0.00 0.51
March 0.180063E+10 0.400594E+10 0.00 69461380.25 83602790.00 0.00 0.255760E+11 0.00 0.57
April 0.268637E+10 0.635278E+10 0.00 36178957.74 80858056.52 0.00 0.711790E+10 0.00 0.50
May 0.00 0.134307E+11 0.00 0.00 0.143461E+09 0.00 0.00 0.00 0.26
June 0.00 0.138940E+11 0.00 0.00 0.147289E+09 0.00 0.00 0.00 0.27
July 0.00 0.159169E+11 0.00 0.00 0.252691E+09 0.00 0.00 0.00 0.24
August 3967650.24 0.166629E+11 0.00 0.00 0.171623E+09 0.00 0.00 0.00 0.27
September 0.00 0.164266E+11 0.00 0.00 0.293399E+09 0.00 0.00 0.00 0.26
October 0.432930E+09 0.107000E+11 0.00 22029665.26 0.176500E+09 0.00 0.573613E+10 0.00 0.36
November 0.246178E+10 0.520523E+10 0.00 63964516.88 51176474.45 0.00 0.177381E+11 0.00 0.58
December 0.266601E+10 0.441761E+10 0.00 72924700.79 79081312.43 0.00 0.295785E+11 0.00 0.56
                   
Annual Sum or Average 0.142827E+11 0.111814E+12 0.00 0.376615E+09 0.151502E+10 0.00 0.135173E+12 0.00 0.41
Minimum of Months 0.00 0.221691E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.24
Maximum of Months 0.268637E+10 0.166629E+11 0.00 72924700.79 0.293399E+09 0.00 0.305337E+11 0.00 0.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.112548E+12 0.178559E+11 0.00 0.241487E+09 0.389133E+10 0.00 0.132679E+12 0.00 0.40
February 0.700529E+11 0.219524E+11 0.00 0.202589E+09 0.341920E+10 0.00 0.768946E+11 0.00 0.40
March 0.640391E+11 0.337305E+11 0.00 0.309843E+09 0.460634E+10 0.00 0.131653E+12 0.00 0.45
April 0.152381E+11 0.584640E+11 0.00 0.202146E+09 0.444706E+10 0.00 0.454013E+11 0.00 0.39
May 0.00 0.128356E+12 0.00 0.00 0.505912E+10 0.00 0.00 0.00 0.26
June 0.00 0.134507E+12 0.00 697156.73 0.432792E+10 0.00 0.00 0.00 0.27
July 0.00 0.153885E+12 0.00 0.00 0.635478E+10 0.00 0.00 0.00 0.25
August 0.00 0.160611E+12 0.00 0.00 0.380255E+10 0.00 0.00 0.00 0.27
September 0.00 0.153325E+12 0.00 0.00 0.901890E+10 0.00 0.00 0.00 0.26
October 0.651238E+10 0.101045E+12 0.00 0.134349E+09 0.435226E+10 0.00 0.419284E+11 0.00 0.32
November 0.437492E+11 0.468276E+11 0.00 0.300689E+09 0.201573E+10 0.00 0.912799E+11 0.00 0.44
December 0.857123E+11 0.402281E+11 0.00 0.254708E+09 0.267494E+10 0.00 0.120586E+12 0.00 0.39
                   
Annual Sum or Average 0.397852E+12 0.105079E+13 0.00 0.164651E+10 0.539701E+11 0.00 0.640421E+12 0.00 0.34
Minimum of Months 0.00 0.178559E+11 0.00 0.00 0.201573E+10 0.00 0.00 0.00 0.25
Maximum of Months 0.112548E+12 0.160611E+12 0.00 0.309843E+09 0.901890E+10 0.00 0.132679E+12 0.00 0.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.167022E+11 0.183674E+10 0.00 5555597.63 0.554089E+09 0.162021E+09 0.410820E+10 0.00 0.38
February 0.904936E+10 0.216843E+10 0.00 8214719.23 0.618838E+09 0.129574E+09 0.389160E+10 0.00 0.38
March 0.981825E+10 0.330093E+10 0.00 14934380.33 0.813265E+09 51818540.61 0.703274E+10 0.00 0.42
April 0.209222E+10 0.592047E+10 0.00 15572020.82 0.432145E+09 0.00 0.339085E+10 0.00 0.38
May 0.00 0.129234E+11 0.00 0.00 0.200707E+09 0.00 0.00 0.00 0.26
June 0.00 0.134373E+11 0.00 0.00 0.140333E+09 0.00 0.00 0.00 0.27
July 0.00 0.155674E+11 0.00 0.00 0.336835E+09 0.00 0.00 0.00 0.25
August 0.00 0.160150E+11 0.00 0.00 0.214115E+09 0.00 0.00 0.00 0.27
September 0.00 0.157259E+11 0.00 0.00 0.341319E+09 0.00 0.00 0.00 0.26
October 0.133248E+10 0.100026E+11 0.00 9471921.86 0.272005E+09 0.00 0.283156E+10 0.00 0.32
November 0.623838E+10 0.428573E+10 0.00 15769167.42 0.585835E+09 0.00 0.545755E+10 0.00 0.42
December 0.143510E+11 0.350684E+10 0.00 5026519.48 0.746283E+09 47466116.52 0.276647E+10 0.00 0.37
                   
Annual Sum or Average 0.595839E+11 0.104691E+12 0.00 74544326.78 0.525577E+10 0.390879E+09 0.294790E+11 0.00 0.33
Minimum of Months 0.00 0.183674E+10 0.00 0.00 0.140333E+09 0.00 0.00 0.00 0.25
Maximum of Months 0.167022E+11 0.160150E+11 0.00 15769167.42 0.813265E+09 0.162021E+09 0.703274E+10 0.00 0.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.253901E+10 0.277343E+09 0.00 1178330.22 2961932.50 0.00 0.672812E+09 0.00 0.41
February 0.138100E+10 0.335329E+09 0.00 1884908.79 5016371.65 0.00 0.679461E+09 0.00 0.43
March 0.134346E+10 0.574722E+09 0.00 3562471.75 10719672.30 0.00 0.132877E+10 0.00 0.50
April 0.514817E+09 0.986448E+09 0.00 2937874.50 10442086.41 0.00 0.560405E+09 0.00 0.53
May 0.00 0.252954E+10 0.00 0.00 18025829.29 0.00 0.00 0.00 0.40
June 0.00 0.287543E+10 0.00 0.00 18506806.69 0.00 0.00 0.00 0.44
July 0.00 0.323973E+10 0.00 0.00 31750577.13 0.00 0.00 0.00 0.40
August 498534.96 0.312116E+10 0.00 0.00 21564382.84 0.00 0.00 0.00 0.40
September 0.00 0.277095E+10 0.00 0.00 36865604.11 0.00 0.00 0.00 0.36
October 0.208635E+09 0.180735E+10 0.00 1667943.69 22177239.81 0.00 0.462403E+09 0.00 0.41
November 0.916873E+09 0.710886E+09 0.00 3774107.21 6430320.21 0.00 0.107789E+10 0.00 0.50
December 0.184831E+10 0.565931E+09 0.00 2353805.77 11442837.94 0.00 0.103889E+10 0.00 0.44
                   
Annual Sum or Average 0.875260E+10 0.197948E+11 0.00 17359441.94 0.195904E+09 0.00 0.582064E+10 0.00 0.43
Minimum of Months 0.00 0.277343E+09 0.00 0.00 2961932.50 0.00 0.00 0.00 0.36
Maximum of Months 0.253901E+10 0.323973E+10 0.00 3774107.21 36865604.11 0.00 0.132877E+10 0.00 0.53



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.106507E+10 0.206423E+09 0.00 3158716.05 3730798.37 0.00 0.149981E+10 0.00 0.50
February 0.676846E+09 0.271057E+09 0.00 2846337.96 3584089.33 0.00 0.102086E+10 0.00 0.54
March 0.755565E+09 0.460402E+09 0.00 4288007.59 10372475.30 0.00 0.151886E+10 0.00 0.67
April 0.319165E+09 0.793009E+09 0.00 3027194.41 10463417.92 0.00 0.692117E+09 0.00 0.68
May 0.00 0.208016E+10 0.00 0.00 11590496.23 0.00 0.00 0.00 0.51
June 0.00 0.224705E+10 0.00 0.00 11899761.71 0.00 0.00 0.00 0.53
July 0.00 0.248659E+10 0.00 0.00 20415423.81 0.00 0.00 0.00 0.47
August 320554.88 0.223995E+10 0.00 0.00 13865764.17 0.00 0.00 0.00 0.45
September 0.00 0.212697E+10 0.00 0.00 23704354.38 0.00 0.00 0.00 0.43
October 0.118528E+09 0.142612E+10 0.00 1707094.02 14259827.40 0.00 0.413711E+09 0.00 0.51
November 0.516808E+09 0.520168E+09 0.00 3909428.66 5395311.17 0.00 0.115551E+10 0.00 0.62
December 0.113268E+10 0.356934E+09 0.00 2635565.10 12977980.25 168257.75 0.105698E+10 0.00 0.50
                   
Annual Sum or Average 0.458499E+10 0.152148E+11 0.00 21572343.79 0.142260E+09 168257.75 0.735784E+10 0.00 0.53
Minimum of Months 0.00 0.206423E+09 0.00 0.00 3584089.33 0.00 0.00 0.00 0.43
Maximum of Months 0.113268E+10 0.248659E+10 0.00 4288007.59 23704354.38 168257.75 0.151886E+10 0.00 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.130812E+10 0.445694E+09 0.00 12148867.56 3848206.10 0.00 0.510715E+10 0.00 0.85
February 0.806422E+09 0.661325E+09 0.00 7931214.15 4668565.14 429731.59 0.282012E+10 0.00 0.79
March 0.117082E+10 0.789154E+09 0.00 7144947.63 10789713.01 0.00 0.245004E+10 0.00 0.73
April 0.512938E+09 0.116503E+10 0.00 3610369.99 10337704.45 0.00 0.674745E+09 0.00 0.62
May 0.00 0.254980E+10 0.00 0.00 17988935.97 0.00 0.00 0.00 0.41
June 0.00 0.274740E+10 0.00 0.00 18468928.96 0.00 0.00 0.00 0.42
July 0.00 0.319604E+10 0.00 0.00 31685593.47 0.00 0.00 0.00 0.39
August 497514.61 0.339140E+10 0.00 0.00 21520247.19 0.00 0.00 0.00 0.44
September 0.00 0.338894E+10 0.00 0.00 36790151.58 0.00 0.00 0.00 0.44
October 0.155108E+09 0.266875E+10 0.00 3543899.87 18788503.24 0.00 0.785446E+09 0.00 0.64
November 0.468755E+09 0.115938E+10 0.00 14001939.63 6417159.32 0.00 0.329214E+10 0.00 0.97
December 0.109996E+10 0.933083E+09 0.00 13074189.67 9916223.94 0.00 0.429318E+10 0.00 0.90
                   
Annual Sum or Average 0.552261E+10 0.230960E+11 0.00 61455428.50 0.191220E+09 429731.59 0.194228E+11 0.00 0.63
Minimum of Months 0.00 0.445694E+09 0.00 0.00 3848206.10 0.00 0.00 0.00 0.39
Maximum of Months 0.130812E+10 0.339140E+10 0.00 14001939.63 36790151.58 429731.59 0.510715E+10 0.00 0.97



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.771139E+09 0.328574E+09 0.00 5254077.14 0.00 0.00 0.239485E+10 0.00 0.69
February 0.262067E+09 0.463650E+09 0.00 6153504.58 1135797.96 0.00 0.207390E+10 0.00 0.84
March 0.153210E+09 0.752680E+09 0.00 9762672.71 1758672.76 0.00 0.339752E+10 0.00 1.10
April 0.111573E+09 0.148146E+10 0.00 8665934.19 1084949.60 0.00 0.133849E+10 0.00 1.17
May 0.00 0.250746E+10 0.00 0.00 6969505.26 0.00 0.00 0.00 0.62
June 0.00 0.299542E+10 0.00 0.00 2194440.82 0.00 0.00 0.00 0.72
July 0.00 0.357653E+10 0.00 0.00 2703606.02 0.00 0.00 0.00 0.67
August 144776.19 0.390886E+10 0.00 7290.84 2306009.10 0.00 212221.74 0.00 0.78
September 0.00 0.288352E+10 0.00 0.00 11456830.59 0.00 0.00 0.00 0.58
October 32001011.55 0.207913E+10 0.00 3071400.53 9694975.88 0.00 0.751777E+09 0.00 0.76
November 0.162936E+09 0.937763E+09 0.00 9624579.44 280205.18 0.00 0.244098E+10 0.00 1.07
December 0.184538E+09 0.830991E+09 0.00 10326097.65 2954801.24 0.00 0.377825E+10 0.00 1.02
                   
Annual Sum or Average 0.167761E+10 0.227460E+11 0.00 52865557.08 42539794.41 0.00 0.161760E+11 0.00 0.83
Minimum of Months 0.00 0.328574E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.771139E+09 0.390886E+10 0.00 10326097.65 11456830.59 0.00 0.377825E+10 0.00 1.17



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.241659E+11 0.169691E+10 0.00 303908.53 0.966567E+09 0.424342E+10 0.367745E+09 0.00 0.37
February 0.146040E+11 0.226501E+10 0.00 2225696.58 0.895669E+09 0.151698E+10 0.956901E+09 0.00 0.37
March 0.182831E+11 0.420956E+10 0.00 6416092.33 0.932775E+09 0.125460E+10 0.211391E+10 0.00 0.41
April 0.459044E+10 0.858764E+10 0.00 12970235.17 0.742178E+09 0.00 0.220839E+10 0.00 0.42
May 0.00 0.252967E+11 0.00 0.00 0.179689E+09 0.00 0.00 0.00 0.41
June 27897.66 0.294852E+11 0.00 0.00 0.209688E+09 0.00 0.00 0.00 0.46
July 0.00 0.338247E+11 0.00 0.00 0.321387E+09 0.00 0.00 0.00 0.42
August 0.00 0.321528E+11 0.00 0.00 0.204129E+09 0.00 0.00 0.00 0.43
September 0.00 0.269073E+11 0.00 0.00 0.419585E+09 0.00 0.00 0.00 0.36
October 0.301818E+10 0.173053E+11 0.00 9176480.38 0.462643E+09 0.00 0.241596E+10 0.00 0.38
November 0.125267E+11 0.563652E+10 0.00 9848416.18 0.834060E+09 3042754.09 0.242702E+10 0.00 0.40
December 0.209699E+11 0.401965E+10 0.00 1104007.32 0.127765E+10 0.254977E+10 0.307603E+09 0.00 0.36
                   
Annual Sum or Average 0.981582E+11 0.191387E+12 0.00 42044836.50 0.744602E+10 0.956781E+10 0.107975E+11 0.00 0.40
Minimum of Months 0.00 0.169691E+10 0.00 0.00 0.179689E+09 0.00 0.00 0.00 0.36
Maximum of Months 0.241659E+11 0.338247E+11 0.00 12970235.17 0.127765E+10 0.424342E+10 0.242702E+10 0.00 0.46



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103132E+11 0.166045E+10 0.00 11632826.82 0.367680E+09 0.151342E+10 0.557679E+10 0.00 0.36
February 0.594743E+10 0.263145E+10 0.00 14171500.36 0.191930E+09 0.522332E+09 0.481530E+10 0.00 0.43
March 0.707830E+10 0.465818E+10 0.00 26938004.99 0.225080E+09 0.536714E+09 0.885009E+10 0.00 0.56
April 0.190892E+10 0.882375E+10 0.00 24703948.61 0.162539E+09 0.00 0.565551E+10 0.00 0.64
May 0.00 0.221166E+11 0.00 0.00 0.115687E+09 0.00 0.00 0.00 0.56
June 17960.97 0.248803E+11 0.00 0.00 0.119968E+09 0.00 0.00 0.00 0.60
July 0.00 0.287642E+11 0.00 0.00 0.206915E+09 0.00 0.00 0.00 0.56
August 0.00 0.267230E+11 0.00 0.00 0.131422E+09 0.00 0.00 0.00 0.56
September 0.00 0.220004E+11 0.00 0.00 0.223144E+09 0.00 0.00 0.00 0.46
October 0.140060E+10 0.152390E+11 0.00 12920330.67 0.193027E+09 0.00 0.287171E+10 0.00 0.51
November 0.527376E+10 0.508600E+10 0.00 23919966.24 0.324066E+09 0.00 0.648086E+10 0.00 0.50
December 0.953353E+10 0.327001E+10 0.00 11279868.97 0.459550E+09 0.117617E+10 0.378740E+10 0.00 0.37
                   
Annual Sum or Average 0.414557E+11 0.165853E+12 0.00 0.125566E+09 0.272101E+10 0.374864E+10 0.380377E+11 0.00 0.51
Minimum of Months 0.00 0.166045E+10 0.00 0.00 0.115687E+09 0.00 0.00 0.00 0.36
Maximum of Months 0.103132E+11 0.287642E+11 0.00 26938004.99 0.459550E+09 0.151342E+10 0.885009E+10 0.00 0.64



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.122822E+11 0.479049E+10 0.00 0.110170E+09 0.214440E+09 0.934521E+09 0.429739E+11 0.00 0.78
February 0.788416E+10 0.746034E+10 0.00 66198374.04 88297535.02 0.371913E+09 0.217843E+11 0.00 0.73
March 0.127549E+11 0.753831E+10 0.00 51891821.08 0.363171E+09 0.636086E+09 0.164400E+11 0.00 0.65
April 0.390801E+10 0.112754E+11 0.00 24906759.47 0.404297E+09 0.00 0.439134E+10 0.00 0.54
May 0.00 0.256693E+11 0.00 0.00 0.180128E+09 0.00 0.00 0.00 0.42
June 27965.75 0.279144E+11 0.00 0.00 0.228228E+09 0.00 0.00 0.00 0.44
July 0.00 0.333579E+11 0.00 0.00 0.322172E+09 0.00 0.00 0.00 0.42
August 0.00 0.360424E+11 0.00 0.00 0.204628E+09 0.00 0.00 0.00 0.49
September 0.00 0.348757E+11 0.00 0.00 0.347442E+09 0.00 0.00 0.00 0.47
October 0.197102E+10 0.285153E+11 0.00 28528187.70 0.181379E+09 0.00 0.606590E+10 0.00 0.66
November 0.487968E+10 0.121328E+11 0.00 0.126137E+09 0.159019E+09 0.00 0.257415E+11 0.00 0.90
December 0.114847E+11 0.980687E+10 0.00 0.110426E+09 0.295794E+09 0.848627E+09 0.310712E+11 0.00 0.78
                   
Annual Sum or Average 0.551648E+11 0.239379E+12 0.00 0.518258E+09 0.298899E+10 0.279115E+10 0.148468E+12 0.00 0.61
Minimum of Months 0.00 0.479049E+10 0.00 0.00 88297535.02 0.00 0.00 0.00 0.42
Maximum of Months 0.127549E+11 0.360424E+11 0.00 0.126137E+09 0.404297E+09 0.934521E+09 0.429739E+11 0.00 0.90



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.128708E+11 0.260923E+10 0.00 16784217.51 0.100673E+09 0.120371E+10 0.758124E+10 0.00 0.47
February 0.747454E+10 0.355955E+10 0.00 16605348.52 91047510.50 0.359655E+09 0.562115E+10 0.00 0.52
March 0.888388E+10 0.482598E+10 0.00 28748284.29 80030464.49 0.174587E+09 0.953401E+10 0.00 0.63
April 0.165727E+10 0.103338E+11 0.00 32588703.35 82979242.11 0.00 0.468277E+10 0.00 0.70
May 0.00 0.220789E+11 0.00 0.00 76287080.96 0.00 0.00 0.00 0.57
June 0.00 0.255140E+11 0.00 38457.54 37557054.62 0.00 0.00 0.00 0.63
July 0.00 0.292839E+11 0.00 0.00 59426061.58 0.00 0.00 0.00 0.56
August 0.00 0.299588E+11 0.00 0.00 62626998.14 0.00 0.00 0.00 0.63
September 0.00 0.244936E+11 0.00 0.00 0.124492E+09 0.00 0.00 0.00 0.51
October 0.135019E+10 0.167385E+11 0.00 13400170.77 0.103791E+09 0.00 0.321181E+10 0.00 0.58
November 0.578638E+10 0.623586E+10 0.00 27791966.57 19945592.99 0.00 0.635617E+10 0.00 0.57
December 0.120564E+11 0.502873E+10 0.00 16045868.82 0.104715E+09 0.540132E+09 0.467795E+10 0.00 0.48
                   
Annual Sum or Average 0.500794E+11 0.180661E+12 0.00 0.152003E+09 0.943571E+09 0.227808E+10 0.416651E+11 0.00 0.57
Minimum of Months 0.00 0.260923E+10 0.00 0.00 19945592.99 0.00 0.00 0.00 0.47
Maximum of Months 0.128708E+11 0.299588E+11 0.00 32588703.35 0.124492E+09 0.120371E+10 0.953401E+10 0.00 0.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.168067E+10 0.174373E+09 0.00 14266.09 0.127830E+09 0.975114E+09 4669197.37 0.00 0.38
February 0.104373E+10 0.225408E+09 0.00 125514.45 0.128617E+09 0.490401E+09 89428462.90 0.00 0.38
March 0.151266E+10 0.444519E+09 0.00 512590.67 0.110917E+09 0.349292E+09 0.177711E+09 0.00 0.42
April 0.426938E+09 0.838536E+09 0.00 1316920.91 0.107615E+09 677889.45 0.235241E+09 0.00 0.41
May 0.00 0.245483E+10 0.00 0.00 18225907.89 0.00 0.00 0.00 0.40
June 0.00 0.282485E+10 0.00 0.00 22725309.88 0.00 0.00 0.00 0.45
July 0.00 0.328650E+10 0.00 0.00 37060555.98 0.00 0.00 0.00 0.41
August 0.00 0.311941E+10 0.00 0.00 35768224.71 0.00 0.00 0.00 0.42
September 0.00 0.262495E+10 0.00 0.00 85398032.52 0.00 0.00 0.00 0.36
October 0.271794E+09 0.167411E+10 0.00 785756.21 50776506.31 17530119.72 0.205644E+09 0.00 0.38
November 0.109703E+10 0.507466E+09 1351721.18 669521.40 0.135481E+09 75000320.38 0.224145E+09 7451.04 0.40
December 0.144911E+10 0.363375E+09 327983.07 55133.12 0.168935E+09 0.707261E+09 22505658.46 7326.38 0.37
                   
Annual Sum or Average 0.748194E+10 0.185383E+11 1679704.25 3479702.85 0.102935E+10 0.261528E+10 0.959344E+09 14777.41 0.40
Minimum of Months 0.00 0.174373E+09 0.00 0.00 18225907.89 0.00 0.00 0.00 0.36
Maximum of Months 0.168067E+10 0.328650E+10 1351721.18 1316920.91 0.168935E+09 0.975114E+09 0.235241E+09 7451.04 0.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.117167E+10 0.200803E+09 0.00 284560.98 48071915.64 0.324331E+09 0.218902E+09 0.00 0.40
February 0.618559E+09 0.292859E+09 0.00 938156.79 39475970.88 0.146124E+09 0.342370E+09 0.00 0.45
March 0.702185E+09 0.527032E+09 0.00 2259472.93 33205378.58 0.162832E+09 0.745653E+09 0.00 0.58
April 0.163320E+09 0.921589E+09 0.00 2498834.94 29836850.72 0.00 0.595202E+09 0.00 0.65
May 0.00 0.220150E+10 0.00 0.00 11695711.60 0.00 0.00 0.00 0.56
June 0.00 0.245043E+10 0.00 0.00 13459544.41 0.00 0.00 0.00 0.61
July 0.00 0.288446E+10 0.00 0.00 22246324.39 0.00 0.00 0.00 0.56
August 0.00 0.268176E+10 0.00 0.00 18319624.74 0.00 0.00 0.00 0.57
September 0.00 0.225771E+10 0.00 0.00 32219776.46 0.00 0.00 0.00 0.48
October 0.134203E+09 0.153412E+10 0.00 1167358.41 23494805.93 4718122.13 0.259565E+09 0.00 0.52
November 0.487515E+09 0.521451E+09 74092.02 1855231.75 46155507.65 23872022.10 0.552217E+09 135.90 0.51
December 0.950631E+09 0.329619E+09 0.00 554044.99 74972683.43 0.301438E+09 0.184972E+09 0.00 0.41
                   
Annual Sum or Average 0.422808E+10 0.168033E+11 74092.02 9557660.79 0.393154E+09 0.963315E+09 0.289888E+10 135.90 0.52
Minimum of Months 0.00 0.200803E+09 0.00 0.00 11695711.60 0.00 0.00 0.00 0.40
Maximum of Months 0.117167E+10 0.288446E+10 74092.02 2498834.94 74972683.43 0.324331E+09 0.745653E+09 135.90 0.65



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.958199E+09 0.545387E+09 0.00 8191117.12 36526469.86 0.334930E+09 0.338978E+10 0.00 0.72
February 0.665936E+09 0.791769E+09 0.00 5097372.13 27515535.05 0.163141E+09 0.185592E+10 0.00 0.70
March 0.104909E+10 0.792679E+09 0.00 4456635.85 60194906.27 0.234124E+09 0.156280E+10 0.00 0.64
April 0.339451E+09 0.108653E+10 0.00 2565172.40 78775980.69 0.00 0.500038E+09 0.00 0.53
May 0.00 0.248871E+10 0.00 0.00 18176130.78 0.00 0.00 0.00 0.41
June 0.00 0.267973E+10 0.00 0.00 26740200.99 0.00 0.00 0.00 0.43
July 0.00 0.323296E+10 0.00 0.00 42960674.12 0.00 0.00 0.00 0.41
August 0.00 0.346737E+10 0.00 0.00 35670537.46 0.00 0.00 0.00 0.47
September 0.00 0.340435E+10 0.00 0.00 45902357.22 0.00 0.00 0.00 0.46
October 0.193728E+09 0.271666E+10 0.00 2589858.10 21942826.72 0.00 0.547324E+09 0.00 0.64
November 0.482923E+09 0.117447E+10 0.00 10354215.30 33923476.36 9373867.20 0.244152E+10 0.00 0.88
December 0.946605E+09 0.936842E+09 0.00 8745938.31 60592390.34 0.266401E+09 0.255184E+10 0.00 0.77
                   
Annual Sum or Average 0.463593E+10 0.233175E+11 0.00 42000309.22 0.488921E+09 0.100797E+10 0.128492E+11 0.00 0.59
Minimum of Months 0.00 0.545387E+09 0.00 0.00 18176130.78 0.00 0.00 0.00 0.41
Maximum of Months 0.104909E+10 0.346737E+10 0.00 10354215.30 78775980.69 0.334930E+09 0.338978E+10 0.00 0.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.100421E+10 0.279013E+09 0.00 1183192.88 25972974.81 0.318205E+09 0.620366E+09 0.00 0.46
February 0.600619E+09 0.369051E+09 0.00 1337486.67 27845503.26 0.140135E+09 0.522087E+09 0.00 0.52
March 0.770025E+09 0.496971E+09 0.00 2556859.44 25560214.50 0.121399E+09 0.933318E+09 0.00 0.63
April 0.158523E+09 0.100802E+10 0.00 3195001.84 19976728.19 0.00 0.506351E+09 0.00 0.68
May 0.00 0.209669E+10 0.00 0.00 6862315.88 0.00 0.00 0.00 0.54
June 0.00 0.238452E+10 0.00 0.00 3154584.63 0.00 0.00 0.00 0.60
July 0.00 0.279409E+10 0.00 0.00 5583384.64 0.00 0.00 0.00 0.54
August 0.00 0.285816E+10 0.00 0.00 7569778.30 0.00 0.00 0.00 0.60
September 0.00 0.238527E+10 0.00 0.00 15895917.28 0.00 0.00 0.00 0.50
October 0.135738E+09 0.159185E+10 0.00 1241194.82 12395547.07 0.00 0.287752E+09 0.00 0.56
November 0.555320E+09 0.590025E+09 0.00 2289672.10 20687006.86 14754432.22 0.629094E+09 0.00 0.58
December 0.962139E+09 0.468600E+09 216522.93 1240850.00 38462391.14 0.203778E+09 0.425270E+09 286.99 0.49
                   
Annual Sum or Average 0.418658E+10 0.173223E+11 216522.93 13044257.75 0.209966E+09 0.798271E+09 0.392424E+10 286.99 0.56
Minimum of Months 0.00 0.279013E+09 0.00 0.00 3154584.63 0.00 0.00 0.00 0.46
Maximum of Months 0.100421E+10 0.285816E+10 216522.93 3195001.84 38462391.14 0.318205E+09 0.933318E+09 286.99 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 31476655.81 0.00 3029805.54 0.00 0.00 0.325845E+09 0.00 0.28
February 0.00 48627540.56 0.00 4960140.07 0.00 0.00 0.174217E+09 0.00 0.29
March 0.00 83315622.58 0.00 9437239.25 0.00 0.00 0.218702E+09 0.00 0.31
April 0.00 0.159260E+09 0.00 5218824.98 0.00 0.00 49876563.77 0.00 0.29
May 0.00 0.422041E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.519350E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.601479E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.605591E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.427376E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.348387E+09 0.00 1668260.07 0.00 0.00 44681610.12 0.00 0.28
November 0.00 0.123816E+09 0.00 7448062.13 0.00 0.00 0.123938E+09 0.00 0.28
December 0.00 90443738.27 0.00 12327196.67 0.00 0.00 0.239026E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.346116E+10 0.00 44089528.70 0.00 0.00 0.117629E+10 0.00 0.29
Minimum of Months 0.00 31476655.81 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.605591E+09 0.00 12327196.67 0.00 0.00 0.325845E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.297556E+09 0.00 21100198.45 0.00 0.00 0.327321E+10 0.00 0.28
February 0.00 0.479328E+09 0.00 42595406.23 0.00 0.00 0.175019E+10 0.00 0.29
March 0.00 0.830960E+09 0.00 85405041.51 0.00 0.00 0.219226E+10 0.00 0.31
April 0.00 0.159408E+10 0.00 49129251.71 0.00 0.00 0.499808E+09 0.00 0.29
May 0.00 0.418010E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.517794E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.600734E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.606232E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.421814E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.346964E+10 0.00 15189544.38 0.00 0.00 0.447318E+09 0.00 0.28
November 0.00 0.123564E+10 0.00 68133404.86 0.00 0.00 0.124295E+10 0.00 0.28
December 0.00 0.904290E+09 0.00 0.111811E+09 0.00 0.00 0.239653E+10 0.00 0.28
                   
Annual Sum or Average 0.00 0.344573E+11 0.00 0.393364E+09 0.00 0.00 0.118023E+11 0.00 0.29
Minimum of Months 0.00 0.297556E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.606232E+10 0.00 0.111811E+09 0.00 0.00 0.327321E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 56920976.73 29429358.44 0.00 1351059.25 0.00 0.00 0.271472E+09 0.00 0.28
February 0.00 47662457.26 0.00 3821176.33 0.00 0.00 0.175990E+09 0.00 0.29
March 0.00 82940085.99 0.00 8105433.93 0.00 0.00 0.219986E+09 0.00 0.31
April 0.00 0.159203E+09 0.00 4847243.41 0.00 0.00 50167870.73 0.00 0.29
May 0.00 0.419735E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.518276E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.600685E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.608610E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.423197E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.347019E+09 0.00 1445364.15 0.00 0.00 44898205.40 0.00 0.28
November 0.00 0.123340E+09 0.00 6519604.62 0.00 0.00 0.124891E+09 0.00 0.28
December 0.00 90218591.44 0.00 10546535.94 0.00 0.00 0.240614E+09 0.00 0.28
                   
Annual Sum or Average 56920976.73 0.345032E+10 0.00 36636417.62 0.00 0.00 0.112802E+10 0.00 0.29
Minimum of Months 0.00 29429358.44 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 56920976.73 0.608610E+09 0.00 10546535.94 0.00 0.00 0.271472E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.423463E+09 0.00 0.511873E+09 0.00 0.00 0.347086E+12 0.00 15.66
February 0.00 0.884798E+09 0.00 0.741281E+09 0.00 0.00 0.432690E+12 0.00 21.50
March 0.00 0.177606E+10 0.00 0.109087E+10 0.00 0.00 0.539393E+12 0.00 25.16
April 0.00 0.306569E+10 0.00 0.110516E+10 0.00 0.00 0.201532E+12 0.00 17.36
May 0.00 0.994453E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.33
June 0.00 0.116434E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.34
July 0.00 0.132504E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.31
August 0.00 0.112225E+11 0.00 4026714.74 0.00 0.00 78838161.79 0.00 0.40
September 0.00 0.101571E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.33
October 0.00 0.779264E+10 0.00 0.272018E+09 0.00 0.00 0.123453E+12 0.00 8.37
November 0.00 0.269839E+10 0.00 0.114283E+10 0.00 0.00 0.433613E+12 0.00 25.21
December 0.00 0.181541E+10 0.00 0.171986E+10 0.00 0.00 0.651032E+12 0.00 27.14
                   
Annual Sum or Average 0.00 0.746743E+11 0.00 0.658793E+10 0.00 0.00 0.272888E+13 0.00 11.77
Minimum of Months 0.00 0.423463E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.00 0.132504E+11 0.00 0.171986E+10 0.00 0.00 0.651032E+12 0.00 27.14



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:51:31

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.401127E+12 0.952717E+10 0.00 0.186063E+13 0.693071E+12
February 0.431235E+12 0.726638E+10 0.00 0.148912E+13 0.110879E+13
March 0.495645E+12 0.649713E+10 0.00 0.166566E+13 0.165994E+13
April 0.555123E+12 -382835189.9 0.00 0.585409E+12 0.290997E+13
May 0.554256E+12 -0.134927E+11 0.00 -0.685179E+12 0.290701E+13
June 0.552099E+12 -0.108816E+11 0.00 -0.795462E+12 0.335265E+13
July 0.570379E+12 -0.183484E+11 0.00 -0.898103E+12 0.390350E+13
August 0.525371E+12 -0.176102E+11 0.00 -0.887259E+12 0.439346E+13
September 0.452983E+12 -0.168591E+11 0.00 -0.696279E+12 0.286199E+13
October 0.454998E+12 -0.105264E+11 0.00 -0.337313E+11 0.283460E+13
November 0.348920E+12 0.329392E+10 0.00 0.138077E+13 0.194600E+13
December 0.359747E+12 0.769551E+10 0.00 0.199651E+13 0.179123E+13
           
Annual Sum or Average 0.570188E+13 -0.538211E+11 0.00 0.498210E+13 0.303622E+14
Minimum of Months 0.348920E+12 -0.183484E+11 0.00 -0.898103E+12 0.693071E+12
Maximum of Months 0.570379E+12 0.952717E+10 0.00 0.199651E+13 0.439346E+13