Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:51
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2023-10-16 08:51:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 30043.96 | 648.61 | 648.61 |
Net Site Energy | 30043.96 | 648.61 | 648.61 |
Total Source Energy | 93620.76 | 2021.16 | 2021.16 |
Net Source Energy | 93620.76 | 2021.16 | 2021.16 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 86.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3858.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 350.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1909.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2725.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 564.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1158.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13739.15 |
Humidification | 1609.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.80 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 647.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29310.18 | 733.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16618.12 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 86.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3858.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 350.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2725.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 564.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1158.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13739.15 |
Humidification | General | 1609.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.80 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 647.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 86.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3858.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 350.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1909.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2725.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 564.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1158.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13739.15 |
Humidification | Unassigned | 1609.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.80 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 647.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 214.08 | 15.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Other | 358.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 632.77 | 15.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 214.08 | 15.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Other | 358.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 632.77 | 15.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 29310.182 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 29310.182 | 100.00 |
Total On-Site and Utility Electric Sources | 29310.182 | 100.00 |
Total Electricity End Uses | 29310.182 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 16618.12 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 16618.12 | 100.00 |
Total Water End Uses | 16618.12 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 1140.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5789.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:51 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 25-AUG-15:09 | 06-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 27-JUN-11:00 |
Heating | 0.00 | 531907.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 432855.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82829.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 248049.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 39745.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 77358.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 30046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1972025.41 | 561954.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 531907.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 432855.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 248049.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 39745.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 77358.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 30046.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 94.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12219.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7783.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1110.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6046.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8630.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1787.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5097.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 701.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 92825.35 | 795.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 263.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 186.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 38.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 79.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 110.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2003.99 | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 263.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 186.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 38.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 79.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 110.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2003.99 | 17.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.68 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.510289 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.87 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.498535 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 23.41 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.06 | 0.313807 | 0.267000 | 1.62 | 0.836820 | 0.500000 | 0.001214 | 0.000129 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 57.18 | 0.332665 | 0.283000 | 16.18 | 0.887108 | 0.500000 | 0.001145 | 0.003053 | 16.18 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.71 | 0.333388 | 0.283000 | 1.61 | 0.889035 | 0.500000 | 0.001143 | 0.000611 | 2.29 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.18 | 0.203229 | 0.173000 | 0.203297 | 0.541945 | 0.500000 | 0.001875 | 0.000055 | 0.205410 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.17 | 0.131975 | 0.112000 | 0.130611 | 0.351933 | 0.500000 | 0.002887 | 0.000041 | 0.155265 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.32 | 0.180849 | 0.154000 | 0.203369 | 0.482265 | 0.500000 | 0.002107 | 0.000080 | 0.298428 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.50 | 0.102470 | 0.087000 | 0.130669 | 0.300000 | 0.500000 | 0.003718 | 0.000027 | 0.130669 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.61 | 0.205686 | 0.175000 | 2.03 | 0.548497 | 0.500000 | 0.001852 | 0.001487 | 5.58 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 12.37 | 0.331787 | 0.500000 | 0.003062 | 0.000996 | 3.74 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 13.04 | 0.183211 | 0.156000 | 2.03 | 0.488561 | 0.500000 | 0.002080 | 0.001499 | 5.63 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.45 | 0.114441 | 0.097000 | 1.30 | 0.305175 | 0.500000 | 0.003329 | 0.000912 | 3.42 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.33 | 0.179177 | 0.152000 | 0.202597 | 0.477805 | 0.500000 | 0.002126 | 0.000191 | 0.718683 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.27 | 0.120956 | 0.103000 | 0.131058 | 0.322549 | 0.500000 | 0.003150 | 0.000127 | 0.477475 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.46 | 0.163109 | 0.139000 | 0.203526 | 0.434957 | 0.500000 | 0.002336 | 0.000193 | 0.723597 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.46 | 0.105545 | 0.090000 | 0.131237 | 0.300000 | 0.500000 | 0.003610 | 0.000120 | 0.451934 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 14793.03 | 0.000129 | 298.22 |
CORE_MID VAV BOX REHEAT COIL | 348924.61 | 0.003053 | 8136.47 |
CORE_TOP VAV BOX REHEAT COIL | 69854.32 | 0.000611 | 1844.78 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6280.03 | 0.000055 | 165.96 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4743.01 | 0.000041 | 125.30 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9106.45 | 0.000080 | 240.44 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3123.49 | 0.000027 | 75.11 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 169975.23 | 0.001487 | 4483.71 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 113858.05 | 0.000996 | 3003.29 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 171359.31 | 0.001499 | 4520.18 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 104241.24 | 0.000912 | 2749.87 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21873.29 | 0.000191 | 576.85 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14531.20 | 0.000127 | 383.21 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22022.54 | 0.000193 | 580.78 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13755.20 | 0.000120 | 362.76 |
VAV_BOT WITH REHEAT HEATING COIL | 31993.74 | 0.000280 | 547.55 |
VAV_MID WITH REHEAT HEATING COIL | 216417.78 | 0.001893 | 3772.86 |
VAV_TOP WITH REHEAT HEATING COIL | 20993.96 | 0.000184 | 368.70 |
CAV_BAS HEATING COIL | 248933.04 | 0.002178 | 5597.64 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.61 | 2.29 | 11.23 | 2.29 | 10.03 | 10.03 | 0.300000 | 0.227921 | 10.03 |
VAV_MID WITH REHEAT | 53.82 | 22.86 | 107.64 | 29.15 | 94.45 | 94.45 | 0.300000 | 0.308617 | 94.45 |
VAV_TOP WITH REHEAT | 5.62 | 2.28 | 11.23 | 4.66 | 10.78 | 10.78 | 0.300000 | 0.432169 | 10.78 |
CAV_BAS | 5.68 | 5.68 | 5.68 | 5.68 | 5.68 | 5.68 | 1.00 | 1.00 | 5.68 |
AIRLOOP DATACENTER BASEMENT | 23.41 | 23.41 | 23.41 | 23.41 | 23.41 | 23.41 | 1.00 | 0.999989 | 23.41 |
AIRLOOP DATACENTER BOT | 0.510289 | 0.510289 | 0.510289 | 0.510289 | 0.510289 | 0.510289 | 1.00 | 1.00 | 0.510289 |
AIRLOOP DATACENTER MID | 4.87 | 4.87 | 4.87 | 4.87 | 4.87 | 4.87 | 1.00 | 1.00 | 4.87 |
AIRLOOP DATACENTER TOP | 0.498535 | 0.498535 | 0.498535 | 0.498535 | 0.498535 | 0.498535 | 1.00 | 1.00 | 0.498535 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.03 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 94.45 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.78 | |
CAV_BAS_OA_CONTROLLER | 5.68 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 23.41 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.510289 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.87 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.498535 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.46 | 6.67 | 10.86 | 0.008164 | 0.008164 | 185653.92 | 0.005310 | 10.03 |
VAV_MID WITH REHEAT COOLING COIL | 27.76 | 6.67 | 10.86 | 0.008100 | 0.008100 | 1779365.98 | 0.050890 | 94.45 |
VAV_TOP WITH REHEAT COOLING COIL | 27.18 | 6.67 | 10.87 | 0.008160 | 0.008160 | 196088.44 | 0.005608 | 10.78 |
CAV_BAS COOLING COIL | 27.86 | 6.67 | 11.28 | 0.008224 | 0.008224 | 105042.04 | 0.003004 | 5.68 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.03 |
VAV_MID WITH REHEAT FAN | 94.45 |
VAV_TOP WITH REHEAT FAN | 10.78 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005310 | 0.000090 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000280 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.050890 | 0.000009 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.001893 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005608 | 0.000085 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000184 | |
CAV_BAS_COOLC_CONTROLLER | 0.003004 | 0.000159 |
CAV_BAS_HEATC_CONTROLLER | 0.002178 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.68 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 23.41 | 440678.32 | 288368.91 | 0.010792 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.510289 | 9391.96 | 6211.81 | 0.000230 |
AIRLOOP DATACENTER MID COOLING COIL | 4.87 | 89724.67 | 59321.21 | 0.002197 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.498535 | 9178.76 | 6069.72 | 0.000225 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 23.41 | 23.41 | 23.41 | 23.41 | 440678.32 | 440678.32 | 14683.19 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.510289 | 0.510289 | 0.510289 | 0.510289 | 9391.96 | 9391.96 | 678.30 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.87 | 4.87 | 4.87 | 4.87 | 89724.67 | 89724.67 | 6783.03 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.498535 | 0.498535 | 0.498535 | 0.498535 | 9178.76 | 9178.76 | 678.30 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 23.41 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.510289 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.87 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.498535 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 23.41 | 440678.32 | 0.010792 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.510289 | 9391.96 | 0.000230 |
AIRLOOP DATACENTER MID HEATING COIL | 4.87 | 89724.67 | 0.002197 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.498535 | 9178.76 | 0.000225 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 14683.19 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 678.30 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6783.03 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 678.30 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000103 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.064812 | 10476.99 | |
HEATSYS1 PUMP | 0.014057 | 4191.38 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.064812 | 7.78 |
HEATSYS1 | 0.014057 | 1.69 |
COOLSYS1_SUPPLY | 0.064812 | 7.78 |
SINGLE WATER PLANT LOOP | 0.013444 | 1.61 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.064812 | 0.064812 | 272046.86 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1606779.52 | 1606779.52 | 0.014057 |
CENTRAL BOILER | 553791.17 | 541988.62 | 0.013444 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.032406 | 3626.79 |
COOLSYS1 CHILLER2 PUMP | 0.032406 | 3626.79 |
PLANT CIRC PUMP | 0.013444 | 3395.03 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.064812 | 0.032807 | 1149936.58 | 1155391.87 | 0.057176 |
COOLSYS1 CHILLER2 | 0.064812 | 0.032807 | 1149936.58 | 1155391.87 | 0.057176 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013444 | 139666.47 | 58688.01 | 69833.23 | 7004.20 | 21356.73 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.114352 | 13.72 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.114352 | 28030.75 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 48.68 | 1371359.74 | 9.74 | 171419.97 |
TOWERWATERSYS COOLTOWER 2 | 48.68 | 1371359.74 | 9.74 | 171419.97 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.059388 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.452 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.400 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.662 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5215 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5467 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4343 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.81534556E-15 | 0.47534309E-16 | -0.12491808E-09 | -0.15651055E-17 |
51 | 8 | 0.18376575E-07 | 0.18892299E-12 | 0.33997552E-03 | -0.20894799E-09 |
52 | 7 | -0.11109444E-01 | 0.10222184E-07 | -0.21454547E-01 | 0.12631841E-03 |
53 | 6 | 0.37458360 | 0.36213810E-05 | 0.44579641 | -0.43850983E-02 |
54 | 5 | -4.8902522 | 0.13734403E-03 | -4.2389002 | 0.59460182E-01 |
55 | 4 | 31.674104 | 0.11393769E-02 | 20.648451 | -0.40448134 |
56 | 3 | -108.39803 | 0.25142476E-02 | -54.058051 | 1.4743366 |
57 | 2 | 194.32686 | 0.14299560E-02 | 76.440274 | -2.8561868 |
58 | 1 | -170.12819 | 0.15421596E-03 | -54.840647 | 2.7274244 |
59 | 0 | 57.057407 | 0.88766417E-06 | 15.629571 | |
60 | 9 | 0.15527634E-14 | 0.48972640E-16 | -0.12737755E-09 | -0.48559044E-17 |
61 | 8 | 0.18724477E-07 | 0.18300980E-12 | 0.34384059E-03 | -0.21290374E-09 |
62 | 7 | -0.11225506E-01 | 0.98577958E-08 | -0.21621905E-01 | 0.12763808E-03 |
63 | 6 | 0.37773826 | 0.34860306E-05 | 0.44850155 | -0.44222837E-02 |
64 | 5 | -4.9210508 | 0.13200769E-03 | -4.2597582 | 0.59842059E-01 |
65 | 4 | 31.810414 | 0.10936068E-02 | 20.730162 | -0.40629104 |
66 | 3 | -108.68827 | 0.24103335E-02 | -54.219675 | 1.4785295 |
67 | 2 | 194.61479 | 0.13693941E-02 | 76.588171 | -2.8607587 |
68 | 1 | -170.23464 | 0.14753937E-03 | -54.883028 | 2.7292902 |
69 | 0 | 57.057407 | 0.84836289E-06 | 15.622061 | |
70 | 9 | 0.10580992E-14 | 0.52916478E-16 | -0.11479962E-09 | -0.26242945E-17 |
71 | 8 | 0.16943687E-07 | 0.21219816E-12 | 0.32378363E-03 | -0.19265555E-09 |
72 | 7 | -0.10622292E-01 | 0.11706466E-07 | -0.20751735E-01 | 0.12077931E-03 |
73 | 6 | 0.36134106 | 0.41796623E-05 | 0.43441658 | -0.42290030E-02 |
74 | 5 | -4.7609497 | 0.15957712E-03 | -4.1510514 | 0.57856955E-01 |
75 | 4 | 31.101728 | 0.13316855E-02 | 20.304070 | -0.39688243 |
76 | 3 | -107.17897 | 0.29539374E-02 | -53.376774 | 1.4567269 |
77 | 2 | 193.11717 | 0.16877407E-02 | 75.817308 | -2.8369794 |
78 | 1 | -169.68078 | 0.18278585E-03 | -54.662957 | 2.7195831 |
79 | 0 | 57.057407 | 0.10570564E-05 | 15.661738 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 35 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 36 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
3 | WINDOW_U_0.455_SHGC_WEST_0.249 | 37 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 | ||
4 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 38 | 1 | VerySmooth | 2.586 | 2.586 | 1.000 | 0.250 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.60359E-002 | 0.16038 | 0.61766 | 0.61766 | 0.27390 | 0.15652 | 0.22642 | 0.00000 | 0.84000 | 0.84000 | 0.12071 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1376E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1391E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4572E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4584E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1322E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1331E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7516E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1706E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2646E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4846E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5652E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1550E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2218E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7664E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8035E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1044 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5954E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1167 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0313E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7338E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9424E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1496E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0924E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1750E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2864E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4893E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5885E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1591E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2376E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7668E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8046E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1375E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1391E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4570E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4584E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1321E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1331E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7515E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7521E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8889E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0741E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7066E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9049E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5250E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6121E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9952E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0209E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3314E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0727E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0514E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8793E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1911E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7152E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2799E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2243E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8387E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9061E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6426E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6916E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4977E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5174E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9953E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0213E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7708E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7722E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5123E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5135E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3404E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3412E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7516E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7522E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8031E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8840E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5387E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6029E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3616E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4079E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7668E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8046E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7726E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4518E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1327E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1023E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9123E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.4449E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1496E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0921E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8016E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8823E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5368E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5993E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3584E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3981E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7664E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8035E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7707E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7721E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5122E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5133E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3403E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3410E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7515E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7521E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4967E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5662E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2212E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2714E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2028E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2211E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9954E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0213E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7376E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8453E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3255E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6013E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6503E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5058E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2799E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2243E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5392E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6917E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2758E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4333E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2287E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3087E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9952E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0208E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1045 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5255E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1133 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.0913E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5061E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4104E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8633E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9092E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1664E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0021E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8539E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7668E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.9793E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5498E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9603E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9312E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4692E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3039E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7423E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8249E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4975E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3745E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8633E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9088E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.4944E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6875E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0317E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3811E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3724E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2693E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9603E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9312E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1046 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5397E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1134 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.1077E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5201E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4215E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8716E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9134E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1707E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0067E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8587E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7712E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.9874E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5552E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9686E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9354E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4696E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3065E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7429E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8270E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5015E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3770E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8716E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9131E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.4974E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6914E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0350E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3847E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3794E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2740E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9686E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9354E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 71618.58861 | 71618.58861 | 5.68027 | 5.68027 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 0.50000 | 4.31558E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 76422.65451 | 76422.65451 | 6.06118 | 6.06118 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 721080.22553 | 721080.22553 | 57.17589 | 57.17589 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 201017.79884 | 201017.79884 | 9.31992 | 10.77825 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 71950.70224 | 71950.70224 | 5.70519 | 5.70519 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 48938.09311 | 48938.09311 | 2.28820 | 2.28820 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14683.86419 | 14683.86419 | 1.17513 | 1.17513 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80000 | 5.63111E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 4404.86292 | 4404.86292 | 0.20541 | 0.20541 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14572.00628 | 14572.00628 | 1.16617 | 1.16617 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 34.99233 | 5.62211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3325.32531 | 3325.32531 | 0.15526 | 0.15526 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 16501.38258 | 16501.38258 | 1.32058 | 1.32058 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 40.57833 | 5.63076E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6380.69067 | 6380.69067 | 0.29843 | 0.29843 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18767.79579 | 18767.79579 | 1.50195 | 1.50195 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1931.56185 | 1931.56185 | 8.95945E-002 | 8.95945E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 145089.66688 | 145089.66688 | 11.61090 | 11.61090 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80000 | 5.63111E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 118978.37238 | 118978.37238 | 5.58184 | 5.58184 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 154573.76490 | 154573.76490 | 12.36980 | 12.36980 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 35.36917 | 5.62269E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 79694.10005 | 79694.10005 | 3.73935 | 3.73935 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 162892.66203 | 162892.66203 | 13.03559 | 13.03559 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 40.68917 | 5.63093E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 119945.86499 | 119945.86499 | 5.62740 | 5.62740 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 168052.69262 | 168052.69262 | 13.44847 | 13.44847 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 72971.49380 | 72971.49380 | 3.42283 | 3.42283 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 16655.83015 | 16655.83015 | 1.33288 | 1.33288 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 15306.88182 | 15306.88182 | 0.71868 | 0.71868 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15900.28390 | 15900.28390 | 1.27241 | 1.27241 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 36.07850 | 5.62379E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10168.64893 | 10168.64893 | 0.47747 | 0.47747 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 18297.04775 | 18297.04775 | 1.46421 | 1.46421 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 15411.22240 | 15411.22240 | 0.72360 | 0.72360 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18221.87024 | 18221.87024 | 1.45819 | 1.45819 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9626.11889 | 9626.11889 | 0.45193 | 0.45193 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8083.94932 | 8083.94932 | 0.51029 | 0.51029 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 35.94550 | 5.62358E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 77173.58100 | 77173.58100 | 4.87153 | 4.87153 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 35.94550 | 5.62358E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7897.71319 | 7897.71319 | 0.49853 | 0.49853 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 36.27800 | 5.62409E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370895.54164 | 370895.54164 | 23.41185 | 23.41185 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 28.69700 | 5.61258E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 0.50000 | 4.31558E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 158730.91 | 10.03102 | 10.03102 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 24679.27 | 1.82652 | 1.82652 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1491197.18 | 94.45246 | 94.45246 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 272529.10 | 29.14968 | 29.14968 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 169358.46 | 10.78258 | 10.78258 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 27309.24 | 4.65989 | 4.65989 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 |
7 | CAV_BAS | Cooling | Sensible | 82943.65 | 5.68027 | 5.68027 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 52075.95 | 1.20016 | 1.20016 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 369829.61 | 23.41211 | 23.41211 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14683.19 | 0.33839 | 0.33839 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8114.89 | 0.51029 | 0.51029 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 678.30 | 1.56323E-002 | 1.56323E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 77521.97 | 4.87153 | 4.87153 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6783.03 | 0.15632 | 0.15632 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7934.94 | 0.49853 | 0.49853 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 678.30 | 1.56323E-002 | 1.56323E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.68027 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.06118 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31381 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26700 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61834 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83682 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21412E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29416E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61834 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14793.02670 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29416E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 298.21581 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 57.17589 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33267 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.18078 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88711 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14530E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.05254E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.18078 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 348924.61074 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.05254E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8136.46949 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.70519 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33339 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61457 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88903 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14281E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.11116E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.28820 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 69854.32448 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.11116E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1844.78225 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17513 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20323 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17300 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20330 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54195 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87473E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.49404E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20541 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6280.02816 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.49404E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 165.96195 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16617 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13197 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11200 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13061 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35193 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88691E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.14939E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15526 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4743.01109 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.14939E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 125.29573 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32058 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18085 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15400 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20337 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48226 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10673E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.96672E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29843 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9106.44661 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.96672E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 240.44389 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.50195 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10247 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 8.70000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13067 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.71815E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.73256E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13067 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3123.48523 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.73256E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 75.10612 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.61090 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20569 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.17500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03191 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54850 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85233E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.48702E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.58184 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 169975.23064 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48702E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4483.71000 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.36980 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33179 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.06221E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.96080E-004 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.73935 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 113858.04841 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.96080E-004 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3003.28904 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.03559 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18321 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15600 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03355 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48856 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.07957E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49913E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.62740 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 171359.31312 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49913E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4520.17975 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.44847 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11444 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.70000E-002 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30450 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30517 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.32924E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.11948E-004 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.42283 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 104241.24200 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.11948E-004 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2749.87226 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.33288 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17918 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15200 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20260 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47781 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.12639E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.91357E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71868 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21873.29058 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.91357E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 576.84628 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27241 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12096 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10300 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13106 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32255 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14991E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27125E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47747 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14531.19719 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27125E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 383.20893 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46421 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16311 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13900 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20353 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43496 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33587E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92663E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72360 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22022.54018 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92663E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 580.77888 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45819 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10555 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.00000E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13124 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.60983E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20337E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.45193 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13755.20284 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20337E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 362.76039 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51029 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.87153 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49853 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 23.41185 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.61250 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28628 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.22500 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28628 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.03102 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.03102 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.22792 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 53.82033 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.86194 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 107.64067 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 29.14968 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 94.45246 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 94.45246 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.30862 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.61644 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28299 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.23288 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.65989 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.78258 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.78258 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.43217 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.68027 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.68027 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.68027 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.68027 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.68027 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.68027 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 23.41185 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 23.41185 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 23.41185 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 23.41185 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 23.41211 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 23.41211 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51029 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51029 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51029 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51029 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51029 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.51029 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.87153 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.87153 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.87153 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.87153 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.87153 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.87153 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49853 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49853 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49853 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49853 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49853 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49853 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.03102 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 94.45246 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.78258 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.68027 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 23.41211 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.51029 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.87153 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49853 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.03102 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.46000 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86206 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.16435E-003 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.16435E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 185653.91635 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.30968E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.03102 |
294 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 31993.73836 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.79895E-004 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 547.55028 |
297 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.03102 |
298 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.30968E-003 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.96835E-005 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.79895E-004 |
301 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 94.45246 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.75840 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86184 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.09969E-003 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.09969E-003 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1779365.97815 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.08896E-002 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 94.45246 |
310 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 216417.77716 |
311 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.89332E-003 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3772.86149 |
313 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 94.45246 |
314 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.08896E-002 |
315 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.35732E-006 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.89332E-003 |
317 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.78258 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.18136 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87235 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.16013E-003 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.16013E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 196088.43665 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.60810E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.78258 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 20993.96087 |
327 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.83664E-004 |
328 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 368.70215 |
329 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.78258 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.60810E-003 |
331 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.49111E-005 |
332 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.83664E-004 |
333 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.68027 |
334 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.86172 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.27950 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.22360E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.22360E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 105042.04097 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.00419E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.68027 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 248933.04305 |
344 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17777E-003 |
345 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5597.64287 |
346 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.68027 |
347 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.00419E-003 |
348 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.58509E-004 |
349 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.17777E-003 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 23.41211 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 23.41211 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 440678.31912 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 288368.90816 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.07922E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 23.41211 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 23.41211 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 23.41211 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 23.41211 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 440678.31912 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 440678.31912 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14683.19080 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 23.41211 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 23.41211 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 440678.31912 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.07922E-002 |
368 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14683.19080 |
369 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.03122E-004 |
370 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51029 |
374 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
375 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51029 |
376 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9391.96124 |
377 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6211.81275 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30009E-004 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51029 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51029 |
381 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51029 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51029 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9391.96124 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9391.96124 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 678.30259 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51029 |
388 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51029 |
389 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9391.96124 |
390 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.30009E-004 |
391 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 678.30259 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.87153 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
394 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.87153 |
395 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 89724.66907 |
396 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 59321.20636 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.19735E-003 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.87153 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.87153 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.87153 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.87153 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 89724.66907 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 89724.66907 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6783.02586 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
406 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.87153 |
407 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.87153 |
408 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 89724.66907 |
409 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.19735E-003 |
410 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6783.02586 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49853 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
413 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49853 |
414 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9178.75948 |
415 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6069.71638 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.24787E-004 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49853 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49853 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49853 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49853 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9178.75948 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9178.75948 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 678.30259 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
425 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49853 |
426 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49853 |
427 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9178.75948 |
428 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.24787E-004 |
429 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 678.30259 |
430 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 6.48116E-002 |
431 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 10476.98624 |
432 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 6.48116E-002 |
433 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 7.77739 |
434 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 6.48116E-002 |
435 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 6.48116E-002 |
436 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 272046.86340 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
438 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.40568E-002 |
439 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.68682 |
440 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.40568E-002 |
441 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4191.37952 |
442 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
443 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1606779.51741 |
444 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1606779.52000 |
445 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.40568E-002 |
446 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 6.48116E-002 |
447 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 7.77739 |
448 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.24058E-002 |
449 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3626.78545 |
450 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.24058E-002 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3626.78545 |
452 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.48116E-002 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.28075E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1149936.57501 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1155391.87000 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.71761E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.48116E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.28075E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1149936.57501 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1155391.87000 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.71761E-002 |
462 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.34443E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.61332 |
464 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.34443E-002 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3395.02641 |
466 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.34443E-002 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 58688.01476 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21356.73356 |
472 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 553791.16998 |
473 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 541988.62000 |
474 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.34443E-002 |
475 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
476 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
477 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
479 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
480 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11435 |
481 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.72226 |
482 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11435 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 28030.74813 |
484 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 48.67890 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1371359.73852 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.73578 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 171419.96732 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 48.67890 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1371359.73852 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.73578 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 171419.96732 |
492 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.93875E-002 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.93875E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 14027.75 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 330644.64 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 66211.62 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5953.30 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4495.93 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8631.25 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2959.52 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 161076.83 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 107896.59 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 162388.18 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 98784.99 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20727.25 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13769.77 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20868.66 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13034.54 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 26623.24 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 186533.39 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 18346.65 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 199745.72 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 246417.83 | 164365.25 | 82052.58 | 0.67 | 55580.34 | 563.73 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2348116.94 | 1558564.38 | 789552.56 | 0.66 | 531605.27 | 5391.84 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 263008.21 | 175969.87 | 87038.34 | 0.67 | 60842.53 | 617.10 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 136696.53 | 91903.80 | 44792.73 | 0.67 | 27683.55 | 280.78 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.47 | 22.07 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.47 | 22.07 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_NORTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_EAST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_SOUTH_0.249 | N/A | 2.586 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.455_SHGC_WEST_0.249 | N/A | 2.586 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3381214283 | 0.2655321521 | Pass | Pass | 1.4280453725 | 4.7372137383 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 7.0082530768E-002 | 0.1339640106 | Pass | Pass | 0.1188249371 | 0.3228745611 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.6262016636E-002 | 7.9350027024E-002 | Pass | Pass | 7.7464100500E-002 | 0.2665843874 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.9715423552E-002 | 3.7006958005E-002 | Pass | Pass | 0.1778148926 | 0.3780912968 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.3946371731E-002 | 8.7287281501E-002 | Pass | Pass | 0.1179924910 | 0.3210667815 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1046769078 | 0.1325032126 | Pass | Pass | 0.1191883001 | 0.3242484000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1877459340 | 0.2944907566 | Pass | Pass | 0.1483273467 | 0.4054013429 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1222594652 | 0.2356998764 | Pass | Pass | 0.1290578367 | 0.3668130393 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.4432538782E-002 | 4.0294796904E-002 | Pass | Pass | 7.6007603998E-002 | 0.2636446939 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.0783441491E-002 | 0.1002752042 | Pass | Pass | 7.7007333949E-002 | 0.2662171701 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1909293791 | 0.2513082413 | Pass | Pass | 9.8055629757E-002 | 0.3183915179 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1028114406 | 0.1355539443 | Pass | Pass | 7.3475829420E-002 | 0.2530931133 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1231427613 | 0.1609013714 | Pass | Pass | 10.2156874955 | 118.7772379151 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.3693183587E-002 | 0.1136853023 | Pass | Pass | 0.5001303396 | 3.5804203031 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1553004949 | 0.1168634193 | Pass | Pass | 0.1867369374 | 0.3896618047 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1228606799 | 0.1179465035 | Pass | Pass | 0.2963723246 | 1.2971337644 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.5786159265E-002 | 2.4650243190E-002 | Pass | Pass | 0.7898795541 | 4.9651901642 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.9798038288E-002 | 3.3286258374E-002 | Pass | Pass | 0.1223829446 | 0.3819077367 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.1283807196E-002 | 6.1271505404E-002 | Pass | Pass | 0.1837700416 | 0.3839690485 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.2848182741E-006 | 5.1518460125E-006 | Pass | Pass | 6.9920477325E-003 | 7.6194284655E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.5249432706E-006 | 6.4749914462E-006 | Pass | Pass | 0.2121677884 | 0.9447370535 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.4168457538E-002 | 3.5638117624E-002 | Pass | Pass | 0.1107690236 | 0.4897622531 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7828220911E-005 | 2.5307929617E-005 | Pass | Pass | 7.9103366814E-005 | 1.0593549381E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5173.47 | 41.86 | 0.00 | 15816.75 | 25114.18 | 46146.28 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.455_SHGC_NORTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.455_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.455_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.455_SHGC_EAST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.455_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.455_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.455_SHGC_WEST_0.249 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.586 | 0.250 | 0.275 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.586 | 0.250 | 0.275 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.455_SHGC_NORTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.455_SHGC_EAST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.455_SHGC_SOUTH_0.249 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.455_SHGC_WEST_0.249 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.586 | 0.250 | 0.275 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
North Total or Average | 1390.74 | 2.586 | 0.250 | 0.275 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.586 | 0.250 | 0.275 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.33 | 0.0000 | Y | 10.61 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.98 | 0.0000 | Y | 6.75 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.89 | 0.0000 | Y | 10.44 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.18 | 0.0000 | Y | 6.80 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.27 | 0.0000 | Y | 105.88 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.95 | 0.0000 | Y | 67.42 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.86 | 0.0000 | Y | 104.30 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.13 | 0.0000 | Y | 67.88 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.27 | 0.0000 | Y | 10.59 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.94 | 0.0000 | Y | 6.74 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.86 | 0.0000 | Y | 10.43 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.13 | 0.0000 | Y | 6.79 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 774.43 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 41.79 | 41.79 | 104.10 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.79 | 62.79 | 11.66 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.79 | 47.06 | 234.94 | |
Exterior Lighting Total | 40855.88 | 350.70 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2259170.43 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1606779.52 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1155391.87 | 6.28 | 1011500.47 | 5.58 | 6.47 | 22.07 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1155391.87 | 6.28 | 1011500.47 | 5.58 | 6.47 | 22.07 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 541988.62 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1371359.74 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1371359.74 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 185653.92 | 246417.83 | 164365.25 | 82052.58 | 0.67 | - | 55580.34 | 563.73 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1779365.98 | 2348116.94 | 1558564.38 | 789552.56 | 0.66 | - | 531605.27 | 5391.84 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 196088.44 | 263008.21 | 175969.87 | 87038.34 | 0.67 | - | 60842.53 | 617.10 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 105042.04 | 136696.53 | 91903.80 | 44792.73 | 0.67 | - | 27683.55 | 280.78 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 440678.32 | 288368.91 | 152309.41 | 0.65 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9391.96 | 6211.81 | 3180.15 | 0.66 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 89724.67 | 59321.21 | 30403.46 | 0.66 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9178.76 | 6069.72 | 3109.04 | 0.66 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 14793.03 | 14027.75 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 348924.61 | 330644.64 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 69854.32 | 66211.62 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 6280.03 | 5953.30 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4743.01 | 4495.93 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9106.45 | 8631.25 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3123.49 | 2959.52 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 169975.23 | 161076.83 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 113858.05 | 107896.59 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 171359.31 | 162388.18 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 104241.24 | 98784.99 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 21873.29 | 20727.25 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14531.20 | 13769.77 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22022.54 | 20868.66 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13755.20 | 13034.54 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 31993.74 | 26623.24 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 216417.78 | 186533.39 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 20993.96 | 18346.65 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 248933.04 | 199745.72 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 440678.32 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9391.96 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 89724.67 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9178.76 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 14683.19 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 678.30 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6783.03 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 678.30 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.03 | 21676.51 | 2160.95 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 94.45 | 204106.75 | 2160.95 | 1.00 | 1.08 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.78 | 23176.78 | 2149.46 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.68 | 9631.77 | 1695.65 | 1.00 | 1.16 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 23.41 | 38612.35 | 1649.25 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 571.58 | 1120.11 | 1.00 | 1.60 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.87 | 5456.63 | 1120.11 | 1.00 | 1.16 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 558.41 | 1120.11 | 1.00 | 1.61 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.064812 | 10476.99 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.014057 | 4191.38 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.032406 | 3626.79 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.032406 | 3626.79 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013444 | 3395.03 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.114352 | 28030.75 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 71618.59 | 71618.59 | 25.77 | 5.680 | 5.680 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00899 | 30.96 | 0.00562 | 1.200 | 0.00 |
CORE_BOTTOM | 76422.65 | 76422.65 | 30.62 | 6.061 | 6.061 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 30.96 | 0.00562 | 1.078 | 0.00 |
CORE_MID | 721080.23 | 721080.23 | 288.88 | 57.176 | 57.176 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 30.96 | 0.00562 | 10.778 | 0.00 |
CORE_TOP | 71950.70 | 71950.70 | 28.83 | 5.705 | 5.705 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 30.96 | 0.00562 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14683.86 | 14683.86 | 46.85 | 1.175 | 1.175 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00869 | 40.80 | 0.00563 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14572.01 | 14572.01 | 72.15 | 1.166 | 1.166 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00862 | 34.99 | 0.00562 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16501.38 | 16501.38 | 52.65 | 1.321 | 1.321 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00867 | 40.58 | 0.00563 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18767.80 | 18767.80 | 92.92 | 1.502 | 1.502 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00860 | 39.12 | 0.00563 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 145089.67 | 145089.67 | 462.93 | 11.611 | 11.611 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00860 | 40.80 | 0.00563 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 154573.76 | 154573.76 | 765.31 | 12.370 | 12.370 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00856 | 35.37 | 0.00562 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 162892.66 | 162892.66 | 519.73 | 13.036 | 13.036 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00859 | 40.69 | 0.00563 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 168052.69 | 168052.69 | 832.05 | 13.448 | 13.448 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00856 | 38.94 | 0.00563 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 16655.83 | 16655.83 | 53.14 | 1.333 | 1.333 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00856 | 40.53 | 0.00563 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15900.28 | 15900.28 | 78.72 | 1.272 | 1.272 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00854 | 36.08 | 0.00562 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18297.05 | 18297.05 | 58.38 | 1.464 | 1.464 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00855 | 40.80 | 0.00563 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18221.87 | 18221.87 | 90.22 | 1.458 | 1.458 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00853 | 38.94 | 0.00563 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8083.95 | 8083.95 | 223.30 | 0.510 | 0.510 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 35.95 | 0.00562 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 77173.58 | 77173.58 | 2131.71 | 4.872 | 4.872 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 35.95 | 0.00562 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7897.71 | 7897.71 | 218.15 | 0.499 | 0.499 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 36.28 | 0.00562 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370895.54 | 370895.54 | 473.27 | 23.412 | 23.412 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 28.70 | 0.00561 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.34 | 0.00432 | 0.50 | 0.00432 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.76 | 0.00432 | 0.50 | 0.00432 | 1.078 | 0.00 | |
CORE_MID | 201017.80 | 201017.80 | 80.53 | 9.320 | 10.778 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 10.778 | 0.00 |
CORE_TOP | 48938.09 | 48938.09 | 19.61 | 2.288 | 2.288 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 4404.86 | 4404.86 | 14.05 | 0.205 | 0.205 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00735 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3325.33 | 3325.33 | 16.46 | 0.155 | 0.155 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00746 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6380.69 | 6380.69 | 20.36 | 0.298 | 0.298 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00763 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1931.56 | 1931.56 | 9.56 | 0.090 | 0.090 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00692 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 118978.37 | 118978.37 | 379.62 | 5.582 | 5.582 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 0.50 | 0.00432 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 79694.10 | 79694.10 | 394.57 | 3.739 | 3.739 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 119945.86 | 119945.86 | 382.70 | 5.627 | 5.627 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 0.50 | 0.00432 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 72971.49 | 72971.49 | 361.29 | 3.423 | 3.423 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | 0.50 | 0.00432 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15306.88 | 15306.88 | 48.84 | 0.719 | 0.719 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10168.65 | 10168.65 | 50.35 | 0.477 | 0.477 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15411.22 | 15411.22 | 49.17 | 0.724 | 0.724 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00781 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9626.12 | 9626.12 | 47.66 | 0.452 | 0.452 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | 0.50 | 0.00432 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 0.50 | 0.00432 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.65 | 0.00672 | 0.50 | 0.00432 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.63 | 0.00459 | 0.50 | 0.00432 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 0.50 | 0.00432 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.03 | 10.03 | 1.83 | 1.83 | 10.0310 | 2.2863 | 10.0310 | 0.2279 | 0.3000 |
VAV_MID WITH REHEAT | 94.45 | 94.45 | 29.15 | 29.15 | 94.4525 | 29.1497 | 94.4525 | 0.3086 | 0.3000 |
VAV_TOP WITH REHEAT | 10.78 | 10.78 | 4.66 | 4.66 | 10.7826 | 4.6599 | 10.7826 | 0.4322 | 0.3000 |
CAV_BAS | 5.68 | 5.68 | 1.20 | 1.20 | 5.6803 | 5.6803 | 5.6803 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 23.41 | 23.41 | 0.34 | 0.34 | 23.4121 | 23.4119 | 23.4121 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.51 | 0.51 | 0.02 | 0.02 | 0.5103 | 0.5103 | 0.5103 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.87 | 4.87 | 0.16 | 0.16 | 4.8715 | 4.8715 | 4.8715 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.50 | 0.50 | 0.02 | 0.02 | 0.4985 | 0.4985 | 0.4985 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 14793.027 | 14793.027 | 1.618335 | 0.00012942 | 298.216 | 12/21 00:10:00 | 12/21 00:10:00 | 14793.03 | 14793.03 | 1.618335 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 14847.57 | 14847.57 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 348924.611 | 348924.611 | 16.180778 | 0.00305254 | 8136.469 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 348924.61 | 348924.61 | 16.180778 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 201017.80 | 0.00 | 350073.12 | 350073.12 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 69854.324 | 69854.324 | 2.288205 | 0.00061112 | 1844.782 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 69854.32 | 69854.32 | 2.288205 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 48938.09 | 0.00 | 70101.75 | 70101.75 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6280.028 | 6280.028 | 0.205410 | 0.00005494 | 165.962 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6280.03 | 6280.03 | 0.205410 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00735091 | 43.1891 | 4404.86 | 0.00 | 6303.08 | 6303.08 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4743.011 | 4743.011 | 0.155265 | 0.00004149 | 125.296 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4743.01 | 4743.01 | 0.155265 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00746318 | 43.8409 | 3325.33 | 0.00 | 4760.08 | 4760.08 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9106.447 | 9106.447 | 0.298428 | 0.00007967 | 240.444 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9106.45 | 9106.45 | 0.298428 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00762684 | 44.7901 | 6380.69 | 0.00 | 9138.36 | 9138.36 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3123.485 | 3123.485 | 0.130669 | 0.00002733 | 75.106 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3123.49 | 3123.49 | 0.130669 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00691939 | 40.6817 | 1931.56 | 0.00 | 3133.61 | 3133.61 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 169975.231 | 169975.231 | 5.581843 | 0.00148702 | 4483.710 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 169975.23 | 169975.23 | 5.581843 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777456 | 45.6468 | 118978.37 | 0.00 | 170540.21 | 170540.21 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 113858.048 | 113858.048 | 3.739350 | 0.00099608 | 3003.289 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 113858.05 | 113858.05 | 3.739350 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00778157 | 45.6875 | 79694.10 | 0.00 | 114235.58 | 114235.58 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 171359.313 | 171359.313 | 5.627405 | 0.00149913 | 4520.180 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 171359.31 | 171359.31 | 5.627405 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777757 | 45.6643 | 119945.86 | 0.00 | 171928.60 | 171928.60 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 104241.242 | 104241.242 | 3.422831 | 0.00091195 | 2749.872 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 104241.24 | 104241.24 | 3.422831 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00774593 | 45.4810 | 72971.49 | 0.00 | 104588.69 | 104588.69 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21873.291 | 21873.291 | 0.718683 | 0.00019136 | 576.846 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21873.29 | 21873.29 | 0.718683 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00780558 | 45.8267 | 15306.88 | 0.00 | 21944.98 | 21944.98 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14531.197 | 14531.197 | 0.477475 | 0.00012713 | 383.209 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14531.20 | 14531.20 | 0.477475 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00780574 | 45.8277 | 10168.65 | 0.00 | 14578.75 | 14578.75 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22022.540 | 22022.540 | 0.723597 | 0.00019266 | 580.779 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22022.54 | 22022.54 | 0.723597 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00780701 | 45.8350 | 15411.22 | 0.00 | 22094.70 | 22094.70 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13755.203 | 13755.203 | 0.451934 | 0.00012034 | 362.760 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13755.20 | 13755.20 | 0.451934 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00779308 | 45.7543 | 9626.12 | 0.00 | 13800.33 | 13800.33 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 185653.916 | -999.000 | 10.031023 | 0.00530968 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 185653.92 | 185653.92 | 10.031023 | 27.46 | 16.30 | 0.00816435 | 10.86 | 10.10 | 0.00816435 | 40.80 | 0.00563111 | 18.58 | 20.2422 | 24.00 | 0.00882161 | 43.0921 | 123160.23 | 0.00 | 200663.21 | 190959.11 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 31993.738 | 31993.738 | 3.009307 | 0.00027990 | 547.550 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 31993.74 | 31993.74 | 3.009307 | 3.12 | 2.50 | 0.00473115 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 67.4740 | 21.64 | 0.00625069 | 35.3634 | 16042.44 | 0.00 | 32224.32 | 32224.32 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1779365.978 | -999.000 | 94.452465 | 0.05088964 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1779365.98 | 1779365.98 | 94.452465 | 27.76 | 16.35 | 0.00809969 | 10.86 | 10.04 | 0.00809969 | 40.80 | 0.00563111 | 18.58 | 21.4986 | 24.00 | 0.00881128 | 43.0418 | 1133966.31 | 0.00 | 1922023.58 | 1837302.20 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 216417.777 | 216417.777 | 28.335739 | 0.00189332 | 3772.861 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 216417.78 | 216417.78 | 28.335739 | 5.85 | 4.58 | 0.00526200 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 71.6621 | 19.61 | 0.00732612 | 46.8939 | 249429.73 | 0.00 | 225803.61 | 225803.61 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 196088.437 | -999.000 | 10.782583 | 0.00560810 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 196088.44 | 196088.43 | 10.782583 | 27.18 | 16.20 | 0.00816013 | 10.87 | 10.10 | 0.00816013 | 40.80 | 0.00563111 | 18.58 | 18.8313 | 24.00 | 0.00875107 | 42.7516 | 133955.29 | 0.00 | 212147.52 | 201904.99 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 20993.961 | 20993.961 | 3.234775 | 0.00018366 | 368.702 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20993.96 | 20993.96 | 3.234775 | 6.89 | 5.47 | 0.00557598 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 62.7710 | 17.60 | 0.00746132 | 54.1694 | 28471.41 | 0.00 | 22210.09 | 22210.09 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 105042.041 | -999.000 | 5.680268 | 0.00300419 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 105042.04 | 105042.04 | 5.680268 | 27.86 | 16.48 | 0.00822360 | 11.28 | 10.34 | 0.00822360 | 40.13 | 0.00563007 | 18.37 | 21.1285 | 24.00 | 0.00903993 | 44.1440 | 62638.36 | 0.00 | 113371.81 | 108962.98 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 248933.043 | 248933.043 | 5.680268 | 0.00217777 | 5597.643 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 248933.04 | 248933.04 | 5.680268 | 0.11 | 0.11 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 21.1285 | 25.34 | 0.00431558 | 19.6025 | 0.00 | 0.00 | 211170.36 | 211170.36 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 440678.319 | 288368.908 | 23.412109 | 0.01079218 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 400754.58 | 400741.56 | -999.0 | 28.73 | 16.99 | 0.00850024 | 12.80 | 11.23 | 0.00850000 | 40.80 | 0.00563111 | 18.58 | -999.0000 | 27.00 | 0.00854237 | 34.9368 | 370426.78 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9391.961 | 6211.813 | 0.510289 | 0.00023001 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8509.22 | 8509.22 | -999.0 | 28.33 | 16.85 | 0.00849868 | 12.80 | 11.23 | 0.00849868 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00858957 | 35.1250 | 8080.49 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89724.669 | 59321.206 | 4.871525 | 0.00219735 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 81301.12 | 81301.12 | -999.0 | 28.34 | 16.86 | 0.00849845 | 12.80 | 11.23 | 0.00849845 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00859381 | 35.1423 | 77120.96 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9178.759 | 6069.716 | 0.498535 | 0.00022479 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8316.54 | 8316.54 | -999.0 | 28.33 | 16.86 | 0.00849863 | 12.80 | 11.23 | 0.00849863 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00859168 | 35.1336 | 7897.71 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 440678.319 | 440678.319 | 23.412109 | 0.01079218 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 440678.32 | 440678.32 | 23.412109 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 1.4454 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9391.961 | 9391.961 | 0.510289 | 0.00023001 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9391.96 | 9391.96 | 0.510289 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0634 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89724.669 | 89724.669 | 4.871525 | 0.00219735 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 89724.67 | 89724.67 | 4.871525 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.2089 | 24.65 | 0.00672007 | 31.6777 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9178.759 | 9178.759 | 0.498535 | 0.00022479 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9178.76 | 9178.76 | 0.498535 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.1357 | 23.63 | 0.00458893 | 23.0671 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14683.191 | 14683.191 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14683.19 | 14683.19 | 23.412109 | 0.01 | 0.01 | 0.00843952 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 1.4454 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 678.30 | 678.30 | 0.510289 | 0.02 | 0.02 | 0.00837181 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0634 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6783.026 | 6783.026 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6783.03 | 6783.03 | 4.871525 | 0.02 | 0.02 | 0.00664291 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.2089 | 24.65 | 0.00672007 | 31.6777 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 678.30 | 678.30 | 0.498535 | 0.02 | 0.02 | 0.00458036 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.1357 | 23.63 | 0.00458893 | 23.0671 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 14793.027 | 14793.027 | 1.618335 | 0.00012942 | 298.216 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 0.9025 | 0.920663 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 14793.03 | 14793.03 | 1.0000 | 1.76915477 | 1.618335 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.12940265 | 60.00 | 32.22 | 27.78 | 0.000 | 14793.03 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | 14847.57 | 14847.57 | 1.76915477 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 348924.611 | 348924.611 | 16.180778 | 0.00305254 | 8136.469 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 21.2874 | 21.715774 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 348924.61 | 348924.61 | 1.0000 | 17.68873284 | 16.180778 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 3.05223332 | 60.00 | 32.22 | 27.78 | 0.000 | 348924.61 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.90 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 201017.80 | 0.00 | 350073.12 | 350073.12 | 17.68873284 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.21 | 18.76 | 0.00800000 | 52850.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 69854.324 | 69854.324 | 2.288205 | 0.00061112 | 1844.782 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 4.2617 | 4.347474 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 69854.32 | 69854.32 | 1.0000 | 2.50145230 | 2.288205 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.61105376 | 60.00 | 32.22 | 27.78 | 0.000 | 69854.32 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 48938.09 | 0.00 | 70101.75 | 70101.75 | 2.50145230 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.28 | 21.27 | 0.00800000 | 61084.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6280.028 | 6280.028 | 0.205410 | 0.00005494 | 165.962 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 0.3831 | 0.390846 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6280.03 | 6280.03 | 1.0000 | 0.22455302 | 0.205410 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.05493482 | 60.00 | 32.22 | 27.78 | 0.000 | 6280.03 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00735091 | 21.00 | 0.00735091 | 43.1891 | 4404.86 | 0.00 | 6303.08 | 6303.08 | 0.22455302 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.33 | 21.28 | 0.00800000 | 61129.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4743.011 | 4743.011 | 0.155265 | 0.00004149 | 125.296 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 0.2894 | 0.295187 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4743.01 | 4743.01 | 1.0000 | 0.16973429 | 0.155265 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.04148970 | 60.00 | 32.22 | 27.78 | 0.000 | 4743.01 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.86 | 0.00746318 | 21.00 | 0.00746318 | 43.8409 | 3325.33 | 0.00 | 4760.08 | 4760.08 | 0.16973429 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61104.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9106.447 | 9106.447 | 0.298428 | 0.00007967 | 240.444 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 0.5556 | 0.566751 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9106.45 | 9106.45 | 1.0000 | 0.32624010 | 0.298428 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.07965904 | 60.00 | 32.22 | 27.78 | 0.000 | 9106.45 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00762684 | 21.00 | 0.00762684 | 44.7901 | 6380.69 | 0.00 | 9138.36 | 9138.36 | 0.32624010 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.27 | 21.26 | 0.00800000 | 61071.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3123.485 | 3123.485 | 0.130669 | 0.00002733 | 75.106 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 0.1906 | 0.194394 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3123.49 | 3123.49 | 1.0000 | 0.14284706 | 0.130669 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.02732282 | 60.00 | 32.22 | 27.78 | 0.000 | 3123.49 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00691939 | 21.00 | 0.00691939 | 40.6817 | 1931.56 | 0.00 | 3133.61 | 3133.61 | 0.14284706 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.31 | 19.44 | 0.00800000 | 54996.6 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 169975.231 | 169975.231 | 5.581843 | 0.00148702 | 4483.710 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 10.3699 | 10.578628 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 169975.23 | 169975.23 | 1.0000 | 6.10203796 | 5.581843 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 1.48686578 | 60.00 | 32.22 | 27.78 | 0.000 | 169975.23 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00777456 | 21.00 | 0.00777456 | 45.6468 | 118978.37 | 0.00 | 170540.21 | 170540.21 | 6.10203796 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.9 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 113858.048 | 113858.048 | 3.739350 | 0.00099608 | 3003.289 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 6.9463 | 7.086103 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 113858.05 | 113858.05 | 1.0000 | 4.08783528 | 3.739350 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.99597827 | 60.00 | 32.22 | 27.78 | 0.000 | 113858.05 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00778157 | 21.00 | 0.00778157 | 45.6875 | 79694.10 | 0.00 | 114235.58 | 114235.58 | 4.08783528 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61005.1 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 171359.313 | 171359.313 | 5.627405 | 0.00149913 | 4520.180 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 10.4544 | 10.664768 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 171359.31 | 171359.31 | 1.0000 | 6.15184613 | 5.627405 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 1.49897310 | 60.00 | 32.22 | 27.78 | 0.000 | 171359.31 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00777757 | 21.00 | 0.00777757 | 45.6643 | 119945.86 | 0.00 | 171928.60 | 171928.60 | 6.15184613 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.3 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 104241.242 | 104241.242 | 3.422831 | 0.00091195 | 2749.872 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 6.3596 | 6.487588 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 104241.24 | 104241.24 | 1.0000 | 3.74181930 | 3.422831 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.91185483 | 60.00 | 32.22 | 27.78 | 0.000 | 104241.24 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00774593 | 21.00 | 0.00774593 | 45.4810 | 72971.49 | 0.00 | 104588.69 | 104588.69 | 3.74181930 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61011.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21873.291 | 21873.291 | 0.718683 | 0.00019136 | 576.846 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 1.3345 | 1.361313 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21873.29 | 21873.29 | 1.0000 | 0.78566048 | 0.718683 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.19133757 | 60.00 | 32.22 | 27.78 | 0.000 | 21873.29 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00780558 | 21.00 | 0.00780558 | 45.8267 | 15306.88 | 0.00 | 21944.98 | 21944.98 | 0.78566048 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14531.197 | 14531.197 | 0.477475 | 0.00012713 | 383.209 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 0.8865 | 0.904368 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14531.20 | 14531.20 | 1.0000 | 0.52197281 | 0.477475 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.12711228 | 60.00 | 32.22 | 27.78 | 0.000 | 14531.20 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00780574 | 21.00 | 0.00780574 | 45.8277 | 10168.65 | 0.00 | 14578.75 | 14578.75 | 0.52197281 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22022.540 | 22022.540 | 0.723597 | 0.00019266 | 580.779 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 1.3436 | 1.370601 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22022.54 | 22022.54 | 1.0000 | 0.79103157 | 0.723597 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.19264314 | 60.00 | 32.22 | 27.78 | 0.000 | 22022.54 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00780701 | 21.00 | 0.00780701 | 45.8350 | 15411.22 | 0.00 | 22094.70 | 22094.70 | 0.79103157 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60991.3 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13755.203 | 13755.203 | 0.451934 | 0.00012034 | 362.760 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 0.8392 | 0.856073 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13755.20 | 13755.20 | 1.0000 | 0.49405207 | 0.451934 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 0.12032424 | 60.00 | 32.22 | 27.78 | 0.000 | 13755.20 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00779308 | 21.00 | 0.00779308 | 45.7543 | 9626.12 | 0.00 | 13800.33 | 13800.33 | 0.49405207 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.8 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 185653.916 | -999.000 | 10.031023 | 0.00530968 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0171 | 1004.8586 | 1.0932 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.031023 | 10.96585673 | 4197.9300 | 999.8980 | 64.80500232 | 15.00 | 6.67 | 8.33 | 2266150.37 | 8.1925 | 8.192480 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 185653.92 | 185653.92 | 1.0000 | 10.96585673 | 10.031023 | 27.46 | 16.30 | 0.00816435 | 48428.2 | 10.86 | 10.10 | 0.00816435 | 31498.1 | 5.30913686 | 6.67 | 15.00 | 8.33 | 21676.507 | 163977.41 | 40.80 | 0.00563111 | 18.58 | 2.03050000 | 20.2422 | 24.00 | 0.00882161 | 24.00 | 0.00882161 | 43.0921 | 123160.23 | 0.00 | 200663.21 | 190959.11 | 10.96585673 | 27.46 | 17.31 | 0.00816435 | 48428.2 | 10.39 | 10.37 | 0.00781322 | 30129.3 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 31993.738 | 31993.738 | 3.009307 | 0.00027990 | 547.550 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.031023 | 10.96585673 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 1.9519 | 1.991172 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 31993.74 | 31993.74 | 1.0000 | 3.28975702 | 3.009307 | 3.12 | 2.50 | 0.00473115 | 14996.7 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 0.27986663 | 60.00 | 32.22 | 27.78 | 0.000 | 31993.74 | 0.50 | 0.00431558 | 0.50 | 2.03050000 | 67.4740 | 8.56 | 0.00559323 | 21.64 | 0.00625069 | 35.3634 | 16042.44 | 0.00 | 32224.32 | 32224.32 | 3.28975702 | 2.80 | 2.80 | 0.00473115 | 14670.5 | 12.46 | 7.88 | 0.00473115 | 24465.9 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1779365.978 | -999.000 | 94.452465 | 0.05088964 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8969 | 1004.8586 | 1.0932 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 94.452465 | 103.25488843 | 4197.9300 | 999.8980 | 64.80500232 | 15.00 | 6.67 | 8.33 | 2266150.37 | 78.5193 | 78.519325 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1779365.98 | 1779365.98 | 1.0000 | 103.25488843 | 94.452465 | 27.76 | 16.35 | 0.00809969 | 48567.6 | 10.86 | 10.04 | 0.00809969 | 31334.8 | 50.88445046 | 6.67 | 15.00 | 8.33 | 204106.747 | 1575259.23 | 40.80 | 0.00563111 | 18.58 | 20.30600000 | 21.4986 | 24.00 | 0.00881128 | 24.00 | 0.00881128 | 43.0418 | 1133966.31 | 0.00 | 1922023.58 | 1837302.20 | 103.25488843 | 27.76 | 17.36 | 0.00809969 | 48567.6 | 10.31 | 10.29 | 0.00777411 | 29953.2 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 216417.777 | 216417.777 | 28.335739 | 0.00189332 | 3772.861 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 94.452465 | 103.25488843 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 13.2033 | 13.469040 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 216417.78 | 216417.78 | 1.0000 | 30.97646653 | 28.335739 | 5.85 | 4.58 | 0.00526200 | 19092.7 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 1.89312399 | 60.00 | 32.22 | 27.78 | 0.000 | 216417.78 | 0.50 | 0.00431558 | 0.50 | 20.30600000 | 71.6621 | 19.37 | 0.00765532 | 19.61 | 0.00732612 | 46.8939 | 249429.73 | 0.00 | 225803.61 | 225803.61 | 30.97646653 | 2.80 | 2.80 | 0.00526200 | 16000.9 | 9.98 | 7.32 | 0.00526200 | 23290.4 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 196088.437 | -999.000 | 10.782583 | 0.00560810 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0093 | 1004.8586 | 1.0932 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.782583 | 11.78745744 | 4197.9300 | 999.8980 | 64.80500232 | 15.00 | 6.67 | 8.33 | 2266150.37 | 8.6529 | 8.652931 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 196088.44 | 196088.43 | 1.0000 | 11.78745744 | 10.782583 | 27.18 | 16.20 | 0.00816013 | 48133.2 | 10.87 | 10.10 | 0.00816013 | 31497.9 | 5.60753238 | 6.67 | 15.00 | 8.33 | 23176.780 | 172911.66 | 40.80 | 0.00563111 | 18.58 | 2.03050000 | 18.8313 | 24.00 | 0.00875107 | 24.00 | 0.00875107 | 42.7516 | 133955.29 | 0.00 | 212147.52 | 201904.99 | 11.78745744 | 27.18 | 17.21 | 0.00816013 | 48133.2 | 10.39 | 10.37 | 0.00781535 | 30135.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20993.961 | 20993.961 | 3.234775 | 0.00018366 | 368.702 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.782583 | 11.78745744 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 1.2808 | 1.306586 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 05:50:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20993.96 | 20993.96 | 1.0000 | 3.53623723 | 3.234775 | 6.89 | 5.47 | 0.00557598 | 20941.9 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 0.18364559 | 60.00 | 32.22 | 27.78 | 0.000 | 20993.96 | 0.50 | 0.00431558 | 0.50 | 2.03050000 | 62.7710 | 17.67 | 0.00770111 | 17.60 | 0.00746132 | 54.1694 | 28471.41 | 0.00 | 22210.09 | 22210.09 | 3.53623723 | 2.80 | 2.80 | 0.00557598 | 16787.8 | 8.99 | 7.21 | 0.00557598 | 23068.5 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 105042.041 | -999.000 | 5.680268 | 0.00300419 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1273 | 1004.8586 | 1.0932 | CAV_BAS FAN | Fan:ConstantVolume | 5.680268 | 6.20963574 | 4197.9300 | 999.8980 | 64.80500232 | 15.00 | 6.67 | 8.33 | 2266150.37 | 4.6353 | 4.635263 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 105042.04 | 105042.04 | 1.0000 | 6.20963574 | 5.680268 | 27.86 | 16.48 | 0.00822360 | 48989.2 | 11.28 | 10.34 | 0.00822360 | 32073.3 | 3.00388262 | 6.67 | 15.00 | 8.33 | 9631.771 | 95410.27 | 40.13 | 0.00563007 | 18.37 | 1.20015641 | 21.1285 | 24.00 | 0.00903993 | 24.00 | 0.00903993 | 44.1440 | 62638.36 | 0.00 | 113371.81 | 108962.98 | 6.20963574 | 27.86 | 17.50 | 0.00822360 | 48989.2 | 10.66 | 10.62 | 0.00794194 | 30731.8 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 248933.043 | 248933.043 | 5.680268 | 0.00217777 | 5597.643 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | CAV_BAS FAN | Fan:ConstantVolume | 5.680268 | 6.20963574 | 4197.9300 | 999.8980 | 14.05537422 | 54.44 | 82.22 | 27.78 | 1639116.59 | 15.1870 | 15.492670 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 248933.04 | 248933.04 | 1.0000 | 6.20963574 | 5.680268 | 0.11 | 0.11 | 0.00431558 | 10900.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | 2.17755270 | 60.00 | 32.22 | 27.78 | 0.000 | 248933.04 | 0.50 | 0.00431558 | 0.50 | 1.20015641 | 21.1285 | 0.00 | 0.00431558 | 25.34 | 0.00431558 | 19.6025 | 0.00 | 0.00 | 211170.36 | 211170.36 | 6.20963574 | 12.80 | 7.56 | 0.00431558 | 23757.7 | 46.38 | 20.38 | 0.00431558 | 57764.5 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 440678.319 | 288368.908 | 23.412109 | 0.01079218 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6415 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 400754.58 | 400741.56 | 0.9094 | -999.0 | -999.0 | 28.73 | 16.99 | 0.00850024 | 50583.8 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 400754.58 | 40.80 | 0.00563111 | 18.58 | 0.33839277 | -999.0000 | 27.00 | 0.00854237 | 27.00 | 0.00854237 | 34.9368 | 370426.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9391.961 | 6211.813 | 0.510289 | 0.00023001 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6386 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8509.22 | 8509.22 | 0.9060 | -999.0 | -999.0 | 28.33 | 16.85 | 0.00849868 | 50164.9 | 12.80 | 11.23 | 0.00849868 | 34318.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8509.22 | 36.28 | 0.00562409 | 17.15 | 0.01563234 | -999.0000 | 27.00 | 0.00858957 | 27.00 | 0.00858957 | 35.1250 | 8080.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 89724.669 | 59321.206 | 4.871525 | 0.00219735 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6382 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 81301.12 | 81301.12 | 0.9061 | -999.0 | -999.0 | 28.34 | 16.86 | 0.00849845 | 50178.1 | 12.80 | 11.23 | 0.00849845 | 34318.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81301.12 | 36.28 | 0.00562409 | 17.15 | 0.15632344 | -999.0000 | 27.00 | 0.00859381 | 27.00 | 0.00859381 | 35.1423 | 77120.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9178.759 | 6069.716 | 0.498535 | 0.00022479 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6385 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8316.54 | 8316.54 | 0.9061 | -999.0 | -999.0 | 28.33 | 16.86 | 0.00849863 | 50171.5 | 12.80 | 11.23 | 0.00849863 | 34318.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8316.54 | 36.28 | 0.00562409 | 17.15 | 0.01563234 | -999.0000 | 27.00 | 0.00859168 | 27.00 | 0.00859168 | 35.1336 | 7897.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 440678.319 | 440678.319 | 23.412109 | 0.01079218 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 440678.32 | 440678.32 | 1.0000 | 25.59398240 | 23.412109 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 440678.32 | 0.50 | 0.00431558 | 0.50 | 0.33839277 | 1.4454 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9391.961 | 9391.961 | 0.510289 | 0.00023001 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9391.96 | 9391.96 | 1.0000 | 0.55784502 | 0.510289 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9391.96 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.0634 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89724.669 | 89724.669 | 4.871525 | 0.00219735 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 89724.67 | 89724.67 | 1.0000 | 5.32552337 | 4.871525 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89724.67 | 0.50 | 0.00431558 | 0.50 | 0.15632344 | 3.2089 | 0.00 | 0.00672007 | 24.65 | 0.00672007 | 31.6777 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9178.759 | 9178.759 | 0.498535 | 0.00022479 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9178.76 | 9178.76 | 1.0000 | 0.54499526 | 0.498535 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9178.76 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.1357 | 0.00 | 0.00458893 | 23.63 | 0.00458893 | 23.0671 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14683.191 | 14683.191 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 23.412109 | 25.59398240 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 14683.19 | 14683.19 | 1.0000 | 25.59398240 | 23.412109 | 0.01 | 0.01 | 0.00843952 | 21114.1 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14683.19 | 0.50 | 0.00431558 | 0.50 | 0.33839277 | 1.4454 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.510289 | 0.55784502 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 678.30 | 678.30 | 1.0000 | 0.55784502 | 0.510289 | 0.02 | 0.02 | 0.00837181 | 20953.0 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 678.30 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.0634 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6783.026 | 6783.026 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.871525 | 5.32552337 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6783.03 | 6783.03 | 1.0000 | 5.32552337 | 4.871525 | 0.02 | 0.02 | 0.00664291 | 16629.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6783.03 | 0.50 | 0.00431558 | 0.50 | 0.15632344 | 3.2089 | 0.00 | 0.00672007 | 24.65 | 0.00672007 | 31.6777 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.498535 | 0.54499526 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 678.30 | 678.30 | 1.0000 | 0.54499526 | 0.498535 | 0.02 | 0.02 | 0.00458036 | 11471.1 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 678.30 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.1357 | 0.00 | 0.00458893 | 23.63 | 0.00458893 | 23.0671 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.03 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 94.45 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.78 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.68 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 23.41 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2464.83 | 1164.83 | 437.83 |
CORE_BOTTOM | 2295.67 | 627.67 | 24.67 |
CORE_MID | 1680.17 | 1899.17 | 137.17 |
CORE_TOP | 1684.00 | 2648.83 | 249.33 |
PERIMETER_BOT_ZN_3 | 2116.33 | 2246.17 | 124.17 |
PERIMETER_BOT_ZN_2 | 2816.50 | 1732.33 | 253.17 |
PERIMETER_BOT_ZN_1 | 3152.67 | 1302.17 | 250.83 |
PERIMETER_BOT_ZN_4 | 3790.17 | 922.50 | 451.17 |
PERIMETER_MID_ZN_3 | 2024.33 | 3000.17 | 358.33 |
PERIMETER_MID_ZN_2 | 2262.83 | 2006.33 | 374.83 |
PERIMETER_MID_ZN_1 | 2983.17 | 1699.83 | 326.83 |
PERIMETER_MID_ZN_4 | 2759.00 | 2222.17 | 355.67 |
PERIMETER_TOP_ZN_3 | 2535.67 | 3190.67 | 843.67 |
PERIMETER_TOP_ZN_2 | 2912.00 | 2540.00 | 620.00 |
PERIMETER_TOP_ZN_1 | 3035.50 | 2025.33 | 503.83 |
PERIMETER_TOP_ZN_4 | 2928.33 | 2521.33 | 629.17 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1295.50 | 1295.50 |
DATACENTER_MID_ZN_6 | 5943.00 | 508.67 | 508.67 |
DATACENTER_TOP_ZN_6 | 5790.67 | 635.50 | 624.00 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5756.33 | 5756.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5913.67 | 5789.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 70.00 | 0.00 | 6.83 |
CORE_BOTTOM | 0.00 | 7.00 | 0.00 | 0.33 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 0.17 | 0.50 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 47.17 | 0.00 | 25.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 95.67 | 0.00 | 77.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 133.67 | 0.00 | 105.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 331.00 | 0.00 | 125.50 |
PERIMETER_MID_ZN_3 | 0.33 | 35.83 | 0.00 | 21.17 |
PERIMETER_MID_ZN_2 | 0.33 | 102.50 | 0.00 | 77.67 |
PERIMETER_MID_ZN_1 | 0.00 | 164.33 | 0.00 | 145.67 |
PERIMETER_MID_ZN_4 | 0.00 | 126.67 | 0.00 | 53.33 |
PERIMETER_TOP_ZN_3 | 5.00 | 63.50 | 0.17 | 36.00 |
PERIMETER_TOP_ZN_2 | 3.50 | 120.33 | 0.00 | 78.17 |
PERIMETER_TOP_ZN_1 | 1.83 | 109.67 | 0.00 | 74.67 |
PERIMETER_TOP_ZN_4 | 1.83 | 142.17 | 0.00 | 57.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 721.00 | 0.00 | 586.00 |
DATACENTER_MID_ZN_6 | 0.00 | 625.17 | 0.00 | 515.50 |
DATACENTER_TOP_ZN_6 | 0.00 | 522.67 | 0.00 | 427.50 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1033.00 | 0.00 | 796.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 5.33 | 1667.50 | 0.17 | 1140.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.29 | 149.60 | 6779.02 | 1.263 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.04 | 134.35 | 6849.35 | 0.887 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.04 | 134.35 | 6849.35 | 0.647 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.04 | 134.35 | 6849.35 | 0.606 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.91 | 16.87 | 860.00 | 0.821 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 1.228 | 0.036 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.91 | 16.87 | 860.02 | 1.433 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 1.784 | 0.036 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.91 | 16.87 | 860.00 | 0.679 | 0.081 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 1.084 | 0.091 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.91 | 16.87 | 860.02 | 1.263 | 0.082 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 1.083 | 0.084 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.91 | 16.87 | 860.00 | 0.666 | 0.101 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 1.090 | 0.105 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.91 | 16.87 | 860.02 | 1.308 | 0.101 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 1.073 | 0.105 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.28 | 42.18 | 1911.37 | 27.035 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.29 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.04 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.88 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.91 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.91 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.45 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.28 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.29 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.04 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.88 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.91 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.91 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.45 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.28 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1015.76 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 53724097.52 | 0.00 | 53724097.52 | 0.00 | 53724097.52 | 37848132.68 | 3848.79 | 2333.17 | 2578.04 | 362.01 |
CORE_BOTTOM | 38816127.41 | 0.00 | 38816127.41 | 0.00 | 38816127.41 | 33990283.35 | 5551.43 | 14.23 | 3194.33 | 576.85 |
CORE_MID | 0.27E+09 | 0.00 | 0.27E+09 | 0.00 | 0.27E+09 | 0.34E+09 | 6113.11 | 110.02 | 2536.87 | 155.74 |
CORE_TOP | 25144317.42 | 0.00 | 25144317.42 | 0.00 | 25144317.42 | 33990283.35 | 6181.31 | 223.15 | 2355.55 | 183.37 |
PERIMETER_BOT_ZN_3 | 4523366.57 | 0.00 | 4523366.57 | 347995.63 | 4871362.19 | 4267819.30 | 3889.09 | 54.14 | 4816.77 | 576.85 |
PERIMETER_BOT_ZN_2 | 4226751.84 | 0.00 | 4226751.84 | 231996.93 | 4458748.76 | 2750345.05 | 3710.10 | 37.77 | 5012.13 | 576.85 |
PERIMETER_BOT_ZN_1 | 7599587.54 | 0.00 | 7599587.54 | 347995.63 | 7947583.17 | 4267912.63 | 3642.96 | 29.91 | 5087.13 | 576.85 |
PERIMETER_BOT_ZN_4 | 6188403.31 | 0.00 | 6188403.31 | 231996.93 | 6420400.24 | 2750345.05 | 3467.97 | 12.61 | 5279.42 | 576.85 |
PERIMETER_MID_ZN_3 | 35189632.02 | 0.00 | 35189632.02 | 816132.14 | 36005764.16 | 42678193.03 | 4573.91 | 129.62 | 4056.47 | 155.74 |
PERIMETER_MID_ZN_2 | 36272969.07 | 0.00 | 36272969.07 | 544087.72 | 36817056.79 | 27503450.52 | 4341.23 | 90.79 | 4327.97 | 1009.24 |
PERIMETER_MID_ZN_1 | 64493851.89 | 0.00 | 64493851.89 | 816132.14 | 65309984.03 | 42679126.28 | 4038.32 | 92.20 | 4629.49 | 155.74 |
PERIMETER_MID_ZN_4 | 35907026.51 | 0.00 | 35907026.51 | 544087.72 | 36451114.23 | 27503450.52 | 4141.18 | 161.03 | 4457.79 | 155.74 |
PERIMETER_TOP_ZN_3 | 3464644.61 | 0.00 | 3464644.61 | 1013296.28 | 4477940.89 | 4267819.30 | 4276.20 | 249.27 | 4234.53 | 183.37 |
PERIMETER_TOP_ZN_2 | 3602295.44 | 0.00 | 3602295.44 | 675530.39 | 4277825.83 | 2750345.05 | 4041.45 | 135.60 | 4582.95 | 183.37 |
PERIMETER_TOP_ZN_1 | 6688549.16 | 0.00 | 6688549.16 | 1013296.28 | 7701845.44 | 4267912.63 | 4055.54 | 132.81 | 4571.65 | 183.37 |
PERIMETER_TOP_ZN_4 | 3569582.16 | 0.00 | 3569582.16 | 675530.39 | 4245112.55 | 2750345.05 | 4031.26 | 123.10 | 4605.64 | 183.37 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.46E+09 | 0.00 | 0.46E+09 | 0.00 | 0.46E+09 | 10671554.30 | 694.45 | 1549.50 | 6516.05 | 2479.53 |
Total Facility | 0.50E+10 | 0.00 | 0.50E+10 | 31742035.64 | 0.51E+10 | 0.50E+10 | 7254.45 | 4360.88 | 8063.10 | 3333.70 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.3314 | 0.0000 | 2.3314 | 0.0000 | 2.3314 | 1.2002 | 1299.24 | 2330.96 | 2312.80 |
CORE_BOTTOM | 1.6537 | 0.0000 | 1.6537 | 0.0000 | 1.6537 | 1.0778 | 3270.03 | 10.22 | 2662.74 |
CORE_MID | 12.0510 | 0.0000 | 12.0510 | 0.0000 | 12.0510 | 10.7782 | 3444.73 | 109.85 | 2388.42 |
CORE_TOP | 1.1293 | 0.0000 | 1.1293 | 0.0000 | 1.1293 | 1.0778 | 3510.85 | 223.15 | 2209.01 |
PERIMETER_BOT_ZN_3 | 0.1922 | 0.0000 | 0.1922 | 0.0081 | 0.2003 | 0.1353 | 1600.25 | 49.53 | 4293.22 |
PERIMETER_BOT_ZN_2 | 0.1853 | 0.0000 | 0.1853 | 0.0054 | 0.1907 | 0.0872 | 1421.15 | 32.76 | 4489.08 |
PERIMETER_BOT_ZN_1 | 0.3357 | 0.0000 | 0.3357 | 0.0081 | 0.3438 | 0.1353 | 1354.12 | 25.34 | 4563.54 |
PERIMETER_BOT_ZN_4 | 0.2690 | 0.0000 | 0.2690 | 0.0054 | 0.2745 | 0.0872 | 1180.79 | 8.25 | 4753.97 |
PERIMETER_MID_ZN_3 | 1.5900 | 0.0000 | 1.5900 | 0.0191 | 1.6090 | 1.3533 | 1905.74 | 129.46 | 3907.80 |
PERIMETER_MID_ZN_2 | 1.6353 | 0.0000 | 1.6353 | 0.0137 | 1.6490 | 0.8721 | 1457.38 | 86.13 | 3490.49 |
PERIMETER_MID_ZN_1 | 2.9576 | 0.0000 | 2.9576 | 0.0191 | 2.9767 | 1.3533 | 1369.82 | 92.03 | 4481.15 |
PERIMETER_MID_ZN_4 | 1.6331 | 0.0000 | 1.6331 | 0.0127 | 1.6458 | 0.8721 | 1472.74 | 160.86 | 4309.39 |
PERIMETER_TOP_ZN_3 | 0.1561 | 0.0000 | 0.1561 | 0.0237 | 0.1798 | 0.1353 | 1607.93 | 249.07 | 4086.00 |
PERIMETER_TOP_ZN_2 | 0.1644 | 0.0000 | 0.1644 | 0.0158 | 0.1802 | 0.0872 | 1372.80 | 135.38 | 4434.82 |
PERIMETER_TOP_ZN_1 | 0.3066 | 0.0000 | 0.3066 | 0.0237 | 0.3303 | 0.1353 | 1385.40 | 132.81 | 4424.79 |
PERIMETER_TOP_ZN_4 | 0.1619 | 0.0000 | 0.1619 | 0.0158 | 0.1777 | 0.0872 | 1361.33 | 123.10 | 4458.57 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13.8832 | 0.0000 | 13.8832 | 0.0000 | 13.8832 | 0.3384 | 356.98 | 1549.50 | 4036.52 |
Total Facility | 220.6033 | 0.0000 | 220.6033 | 0.7512 | 221.3545 | 158.4706 | 4437.45 | 4352.94 | 5582.90 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 73322842.68 | 0.00 | 73322842.68 | 48026705.38 | 3338.63 | 4.02 | 5417.35 | 576.85 |
VAV_MID WITH REHEAT | 0.53E+09 | 0.00 | 0.53E+09 | 0.48E+09 | 3905.35 | 4.85 | 4849.80 | 155.74 |
VAV_TOP WITH REHEAT | 50754048.19 | 0.00 | 50754048.19 | 48026705.38 | 3990.04 | 2.64 | 4767.32 | 183.37 |
CAV_BAS | 64204250.39 | 0.00 | 64204250.39 | 37848132.68 | 3828.34 | 1.89 | 4929.77 | 362.01 |
AIRLOOP DATACENTER BASEMENT | 0.55E+09 | 0.00 | 0.55E+09 | 10671554.30 | 694.45 | 0.00 | 8065.55 | 2479.53 |
AIRLOOP DATACENTER BOT | 291951.72 | 0.00 | 291951.72 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2919517.21 | 0.00 | 2919517.21 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 291951.72 | 0.00 | 291951.72 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.1500 | 0.0000 | 3.1500 | 1.5229 | 1081.10 | 0.92 | 4860.98 |
VAV_MID WITH REHEAT | 23.7698 | 0.0000 | 23.7698 | 15.2292 | 1239.03 | 4.64 | 4699.32 |
VAV_TOP WITH REHEAT | 2.2925 | 0.0000 | 2.2925 | 1.5229 | 1320.11 | 2.58 | 4620.31 |
CAV_BAS | 2.7862 | 0.0000 | 2.7862 | 1.2002 | 1296.97 | 0.31 | 4645.72 |
AIRLOOP DATACENTER BASEMENT | 16.5914 | 0.0000 | 16.5914 | 0.3384 | 356.98 | 0.00 | 5586.02 |
AIRLOOP DATACENTER BOT | 0.0136 | 0.0000 | 0.0136 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1365 | 0.0000 | 0.1365 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0136 | 0.0000 | 0.0136 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 155.98 | 3096.08 | 0.00 | 0.00 | 0.00 | 2195.51 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 551.68 | 2192.90 | 0.00 | 0.00 | 0.00 | 2163.39 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 95.88 | 2429.52 | 0.00 | 0.00 | 0.00 | 2377.15 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2330.58 | 2683.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 1549.50 | 6516.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.3873 | 5.5436 | 0.0000 | 0.0000 | 0.0000 | 1.9824 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 24.0693 | 41.3248 | 0.0000 | 0.0000 | 0.0000 | 20.2285 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.3209 | 3.8662 | 0.0000 | 0.0000 | 0.0000 | 1.9834 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.4346 | 5.6939 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4045 | 24.2755 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1869 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1515 |
Defaulted Fields | 1183 |
Fields with Defaults | 3871 |
Autosized Fields | 333 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 29310.18 | 313969.00 | 21-JAN-04:00 | 1972025.41 | 25-AUG-15:10 |
Electricity:Building | 17133.94 | 216479.19 | 07-MAY-17:20 | 1025582.59 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17133.94 | 216479.19 | 07-MAY-17:20 | 1025582.59 | 01-DEC-16:30 |
InteriorLights:Electricity | 2457.54 | 9223.03 | 02-APR-17:20 | 247210.90 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2457.54 | 9223.03 | 02-APR-17:20 | 247210.90 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity | 2457.54 | 9223.03 | 02-APR-17:20 | 247210.90 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2457.54 | 9223.03 | 02-APR-17:20 | 247210.90 | 28-NOV-16:30 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 46.98 | 603.11 | 02-APR-17:10 | 3823.11 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.61 | 43.94 | 01-JAN-09:30 | 1662.56 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.61 | 43.94 | 01-JAN-09:30 | 1662.56 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.19 | 388.67 | 02-APR-17:10 | 2463.76 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.75 | 28.32 | 01-JAN-07:50 | 1071.42 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.75 | 28.32 | 01-JAN-07:50 | 1071.42 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 46.81 | 603.12 | 12-MAR-17:10 | 3823.18 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.44 | 43.94 | 01-JAN-07:50 | 1662.60 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.44 | 43.94 | 01-JAN-07:50 | 1662.60 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.24 | 388.67 | 12-MAR-17:10 | 2463.75 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.80 | 28.32 | 01-JAN-09:30 | 1071.42 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.80 | 28.32 | 01-JAN-09:30 | 1071.42 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 469.53 | 6031.15 | 02-APR-17:10 | 38231.14 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 105.88 | 439.44 | 01-JAN-09:30 | 16625.62 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 105.88 | 439.44 | 01-JAN-09:30 | 16625.62 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 301.78 | 3886.70 | 02-APR-17:10 | 24637.60 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 67.42 | 283.19 | 01-JAN-07:50 | 10714.18 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 67.42 | 283.19 | 01-JAN-07:50 | 10714.18 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 467.96 | 6031.24 | 12-MAR-17:10 | 38231.83 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.30 | 439.45 | 01-JAN-07:50 | 16625.99 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.30 | 439.45 | 01-JAN-07:50 | 16625.99 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 302.23 | 3886.68 | 12-MAR-17:10 | 24637.51 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 67.88 | 283.19 | 01-JAN-09:20 | 10714.18 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 67.88 | 283.19 | 01-JAN-09:20 | 10714.18 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 46.95 | 603.11 | 02-APR-17:10 | 3823.11 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.59 | 43.94 | 01-JAN-09:30 | 1662.56 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.59 | 43.94 | 01-JAN-09:30 | 1662.56 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.18 | 388.67 | 02-APR-17:10 | 2463.76 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.74 | 28.32 | 01-JAN-07:50 | 1071.42 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.74 | 28.32 | 01-JAN-07:50 | 1071.42 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 46.80 | 603.12 | 12-MAR-17:10 | 3823.18 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.43 | 43.94 | 01-JAN-07:50 | 1662.60 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.43 | 43.94 | 01-JAN-07:50 | 1662.60 | 28-NOV-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.22 | 388.67 | 12-MAR-17:10 | 2463.75 | 28-NOV-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.79 | 28.32 | 01-JAN-09:20 | 1071.42 | 28-NOV-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.79 | 28.32 | 01-JAN-09:20 | 1071.42 | 28-NOV-16:30 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 3554.45 | 3711.47 | 01-JAN-05:50 | 408768.07 | 05-SEP-07:40 |
HeatRejection:Electricity | 1158.60 | 296.07 | 01-JAN-08:00 | 77358.81 | 13-JUL-18:00 |
General:HeatRejection:Electricity | 1158.60 | 296.07 | 01-JAN-08:00 | 77358.81 | 13-JUL-18:00 |
Electricity:HVAC | 6416.48 | 51260.97 | 21-JAN-04:00 | 543236.38 | 25-AUG-15:10 |
ExteriorEquipment:Electricity | 1909.29 | 28161.90 | 01-JAN-00:10 | 116885.78 | 20-JAN-08:40 |
Transformer:ExteriorEquipment:Electricity | 54.68 | 979.82 | 01-JAN-00:10 | 3412.97 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 29310.18 | 313969.00 | 21-JAN-04:00 | 1972025.41 | 25-AUG-15:10 |
ElectricityPurchased:Plant | 29310.18 | 313969.00 | 21-JAN-04:00 | 1972025.41 | 25-AUG-15:10 |
Cogeneration:ElectricityPurchased | 29310.18 | 313969.00 | 21-JAN-04:00 | 1972025.41 | 25-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 29310.18 | 313969.00 | 21-JAN-04:00 | 1972025.41 | 25-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 29310.18 | 313969.00 | 21-JAN-04:00 | 1972025.41 | 25-AUG-15:10 |
ElectricityNet:Plant | 29310.18 | 313969.00 | 21-JAN-04:00 | 1972025.41 | 25-AUG-15:10 |
Cogeneration:ElectricityNet | 29310.18 | 313969.00 | 21-JAN-04:00 | 1972025.41 | 25-AUG-15:10 |
General:Cogeneration:ElectricityNet | 29310.18 | 313969.00 | 21-JAN-04:00 | 1972025.41 | 25-AUG-15:10 |
Fans:Electricity | 2725.16 | 45198.98 | 01-JAN-21:30 | 268224.52 | 19-JUN-15:00 |
General:Fans:Electricity | 2725.16 | 45198.98 | 01-JAN-21:30 | 268224.52 | 19-JUN-15:00 |
ExteriorLights:Electricity | 350.70 | 0.00 | 01-JAN-07:30 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 350.70 | 0.00 | 01-JAN-07:30 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 3858.36 | 2548.03 | 02-JAN-07:10 | 446424.21 | 11-AUG-15:50 |
General:Cooling:Electricity | 3858.36 | 2548.03 | 02-JAN-07:10 | 446424.21 | 11-AUG-15:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1609.69 | 0.00 | 08-JAN-06:00 | 100000.00 | 01-JAN-13:30 |
General:Humidifier:Electricity | 1609.69 | 0.00 | 08-JAN-06:00 | 100000.00 | 01-JAN-13:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 564.44 | 3395.03 | 01-JAN-00:30 | 47736.35 | 02-NOV-13:30 |
General:Pumps:Electricity | 564.44 | 3395.03 | 01-JAN-00:30 | 47736.35 | 02-NOV-13:30 |
WIRED_LTG_ELECTRICITY | 69.06 | 0.00 | 01-JAN-00:10 | 6946.63 | 28-NOV-16:40 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 733.78 | 7280.88 | 18-MAR-16:10 | 561954.11 | 06-DEC-07:10 |
NaturalGas:Plant | 733.78 | 7280.88 | 18-MAR-16:10 | 561954.11 | 06-DEC-07:10 |
Heating:NaturalGas | 86.74 | 0.00 | 01-JAN-00:10 | 531907.45 | 06-DEC-07:10 |
Boiler:Heating:NaturalGas | 86.74 | 0.00 | 01-JAN-00:10 | 531907.45 | 06-DEC-07:10 |
WaterSystems:NaturalGas | 647.04 | 7280.88 | 02-JAN-05:20 | 76823.81 | 23-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 647.04 | 7280.88 | 02-JAN-05:20 | 76823.81 | 23-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 20718.15 | 8730.27 | 02-JAN-07:10 | 2485224.17 | 11-AUG-15:50 |
PlantLoopCoolingDemand:HVAC | 20718.15 | 8730.27 | 02-JAN-07:10 | 2485224.17 | 11-AUG-15:50 |
CoolingCoils:PlantLoopCoolingDemand | 20718.15 | 8730.27 | 02-JAN-07:10 | 2485224.17 | 11-AUG-15:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 16618.12 | 0.00 | 08-JAN-06:00 | 0.00 | 27-JUN-12:00 |
Water:HVAC | 598.80 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:00 |
Humidifier:Water | 598.80 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:00 |
General:Humidifier:Water | 598.80 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:00 |
MainsWater:Facility | 16618.12 | 0.00 | 08-JAN-06:00 | 0.00 | 27-JUN-12:00 |
MainsWater:HVAC | 598.80 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:00 |
Humidifier:MainsWater | 598.80 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:00 |
General:Humidifier:MainsWater | 598.80 | 0.00 | 08-JAN-06:00 | 0.00 | 15-JAN-13:00 |
Water:Plant | 16019.32 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 16019.32 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 13739.15 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-15:00 |
General:HeatRejection:Water | 13739.15 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-15:00 |
HeatRejection:MainsWater | 13739.15 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-15:00 |
General:HeatRejection:MainsWater | 13739.15 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 79853.91 | 100989.79 | 02-JAN-02:50 | 9621376.08 | 28-AUG-12:30 |
EnergyTransfer:Building | 21042.12 | 90822.57 | 02-JAN-02:50 | 1658359.84 | 14-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 706.57 | 0.00 | 01-JAN-00:10 | 76317.04 | 26-DEC-06:10 |
Heating:EnergyTransfer | 39.49 | 0.00 | 01-JAN-17:10 | 270747.87 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.32 | 0.00 | 01-JAN-00:10 | 28415.63 | 26-AUG-16:10 |
General:Heating:EnergyTransfer | 39.49 | 0.00 | 01-JAN-17:10 | 270747.87 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.32 | 0.00 | 01-JAN-00:10 | 28415.63 | 26-AUG-16:10 |
Cooling:EnergyTransfer | 21002.64 | 90030.19 | 01-JAN-10:50 | 1658359.84 | 14-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 702.24 | 0.00 | 01-JAN-00:10 | 76317.04 | 26-DEC-06:10 |
General:Cooling:EnergyTransfer | 21002.64 | 90030.19 | 01-JAN-10:50 | 1658359.84 | 14-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 702.24 | 0.00 | 01-JAN-00:10 | 76317.04 | 26-DEC-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 684.34 | 0.00 | 01-JAN-00:10 | 61415.50 | 14-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 684.34 | 0.00 | 01-JAN-00:10 | 61415.50 | 14-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 684.34 | 0.00 | 01-JAN-00:10 | 61415.50 | 14-AUG-07:20 |
EnergyTransfer:Zone:CORE_MID | 5013.05 | 0.00 | 01-JAN-00:10 | 423544.92 | 11-SEP-10:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5013.05 | 0.00 | 01-JAN-00:10 | 423544.92 | 11-SEP-10:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5013.05 | 0.00 | 01-JAN-00:10 | 423544.92 | 11-SEP-10:00 |
EnergyTransfer:Zone:CORE_TOP | 488.03 | 0.00 | 01-JAN-00:10 | 50146.49 | 19-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.36 | 0.00 | 01-JAN-00:10 | 41311.15 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.36 | 0.00 | 01-JAN-00:10 | 41311.15 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 487.67 | 0.00 | 01-JAN-00:10 | 50146.49 | 19-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 487.67 | 0.00 | 01-JAN-00:10 | 50146.49 | 19-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 97.40 | 0.00 | 01-JAN-00:10 | 11952.99 | 28-AUG-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 97.40 | 0.00 | 01-JAN-00:10 | 11952.99 | 28-AUG-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 97.40 | 0.00 | 01-JAN-00:10 | 11952.99 | 28-AUG-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 87.70 | 0.00 | 01-JAN-00:10 | 13681.41 | 19-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 375.21 | 07-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 375.21 | 07-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 87.70 | 0.00 | 01-JAN-00:10 | 13681.41 | 19-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 87.70 | 0.00 | 01-JAN-00:10 | 13681.41 | 19-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 145.16 | 0.00 | 01-JAN-00:10 | 17637.18 | 20-NOV-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 145.16 | 0.00 | 01-JAN-00:10 | 17637.18 | 20-NOV-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 145.16 | 0.00 | 01-JAN-00:10 | 17637.18 | 20-NOV-14:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 129.97 | 0.00 | 01-JAN-00:10 | 18787.82 | 25-AUG-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 129.97 | 0.00 | 01-JAN-00:10 | 18787.82 | 25-AUG-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 129.97 | 0.00 | 01-JAN-00:10 | 18787.82 | 25-AUG-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 774.44 | 0.00 | 01-JAN-00:10 | 113216.50 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.08 | 0.00 | 01-JAN-00:10 | 67437.55 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.08 | 0.00 | 01-JAN-00:10 | 67437.55 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 771.35 | 0.00 | 01-JAN-00:10 | 113216.50 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 771.35 | 0.00 | 01-JAN-00:10 | 113216.50 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 796.76 | 0.00 | 01-JAN-00:10 | 141324.92 | 19-JUN-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.13 | 0.00 | 01-JAN-00:10 | 40002.14 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.13 | 0.00 | 01-JAN-00:10 | 40002.14 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 795.64 | 0.00 | 01-JAN-00:10 | 141324.92 | 19-JUN-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 795.64 | 0.00 | 01-JAN-00:10 | 141324.92 | 19-JUN-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1302.92 | 0.00 | 01-JAN-00:10 | 177499.29 | 01-NOV-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.42 | 0.00 | 01-JAN-00:10 | 37210.79 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.42 | 0.00 | 01-JAN-00:10 | 37210.79 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1302.51 | 0.00 | 01-JAN-00:10 | 177499.29 | 01-NOV-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1302.51 | 0.00 | 01-JAN-00:10 | 177499.29 | 01-NOV-14:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 841.04 | 0.00 | 01-JAN-00:10 | 154359.85 | 29-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.55 | 0.00 | 01-JAN-00:10 | 26394.56 | 18-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.55 | 0.00 | 01-JAN-00:10 | 26394.56 | 18-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 840.49 | 0.00 | 01-JAN-00:10 | 154359.85 | 29-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 840.49 | 0.00 | 01-JAN-00:10 | 154359.85 | 29-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 81.66 | 0.00 | 01-JAN-00:10 | 13724.46 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.75 | 0.00 | 01-JAN-00:10 | 13724.46 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.75 | 0.00 | 01-JAN-00:10 | 13724.46 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 78.91 | 0.00 | 01-JAN-00:10 | 12774.84 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 78.91 | 0.00 | 01-JAN-00:10 | 12774.84 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 83.67 | 0.00 | 01-JAN-00:10 | 14378.59 | 19-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.10 | 0.00 | 01-JAN-00:10 | 8726.53 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.10 | 0.00 | 01-JAN-00:10 | 8726.53 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 82.56 | 0.00 | 01-JAN-00:10 | 14378.59 | 19-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 82.56 | 0.00 | 01-JAN-00:10 | 14378.59 | 19-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 129.72 | 0.00 | 01-JAN-00:10 | 19376.02 | 28-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.87 | 0.00 | 01-JAN-00:10 | 9335.58 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.87 | 0.00 | 01-JAN-00:10 | 9335.58 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 128.85 | 0.00 | 01-JAN-00:10 | 19376.02 | 28-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 128.85 | 0.00 | 01-JAN-00:10 | 19376.02 | 28-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 85.79 | 0.00 | 01-JAN-00:10 | 16388.97 | 29-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.66 | 0.00 | 01-JAN-00:10 | 6819.02 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.66 | 0.00 | 01-JAN-00:10 | 6819.02 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 85.13 | 0.00 | 01-JAN-00:10 | 16388.97 | 29-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 85.13 | 0.00 | 01-JAN-00:10 | 16388.97 | 29-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 94.20 | 0.00 | 01-JAN-00:10 | 15368.08 | 28-AUG-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.13 | 0.00 | 01-JAN-00:10 | 3320.37 | 17-DEC-10:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.13 | 0.00 | 01-JAN-00:10 | 3320.37 | 17-DEC-10:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 93.07 | 0.00 | 01-JAN-00:10 | 15368.08 | 28-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 93.07 | 0.00 | 01-JAN-00:10 | 15368.08 | 28-AUG-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 653.72 | 0.00 | 01-JAN-00:10 | 94533.42 | 19-JUN-14:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.24 | 0.00 | 01-JAN-00:10 | 43902.27 | 02-JAN-16:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 13.24 | 0.00 | 01-JAN-00:10 | 43902.27 | 02-JAN-16:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 640.48 | 0.00 | 01-JAN-00:10 | 94533.42 | 19-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 640.48 | 0.00 | 01-JAN-00:10 | 94533.42 | 19-JUN-14:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 121.34 | 0.00 | 01-JAN-00:10 | 24168.65 | 28-JUN-14:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.72 | 0.00 | 01-JAN-00:10 | 14438.91 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.72 | 0.00 | 01-JAN-00:10 | 14438.91 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 111.61 | 0.00 | 01-JAN-00:10 | 24168.65 | 28-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 111.61 | 0.00 | 01-JAN-00:10 | 24168.65 | 28-JUN-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.79 | 1197.88 | 21-JAN-08:00 | 7940.85 | 28-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.79 | 1197.88 | 21-JAN-08:00 | 7940.85 | 28-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.79 | 1197.88 | 21-JAN-08:00 | 7940.85 | 28-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1298.51 | 5.77 | 02-JAN-07:40 | 74715.14 | 28-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.07 | 0.00 | 01-JAN-00:10 | 2639.76 | 01-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.07 | 0.00 | 01-JAN-00:10 | 2639.76 | 01-JAN-08:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1298.44 | 0.00 | 01-JAN-02:00 | 74715.14 | 28-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1298.44 | 0.00 | 01-JAN-02:00 | 74715.14 | 28-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.42 | 6.04 | 16-JAN-10:10 | 7533.02 | 26-APR-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.07 | 0.00 | 01-JAN-16:40 | 578.26 | 01-JAN-21:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.07 | 0.00 | 01-JAN-16:40 | 578.26 | 01-JAN-21:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.35 | 0.00 | 01-JAN-00:10 | 7533.02 | 26-APR-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.35 | 0.00 | 01-JAN-00:10 | 7533.02 | 26-APR-18:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.94 | 88052.37 | 14-MAY-05:00 | 382885.91 | 26-AUG-03:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.94 | 88052.37 | 14-MAY-05:00 | 382885.91 | 26-AUG-03:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.94 | 88052.37 | 14-MAY-05:00 | 382885.91 | 26-AUG-03:00 |
PlantLoopHeatingDemand:Facility | 384.79 | 0.00 | 01-JAN-00:10 | 380109.54 | 06-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 323.62 | 0.00 | 01-JAN-00:10 | 42572.21 | 23-JAN-12:50 |
WaterSystems:PlantLoopHeatingDemand | 323.62 | 0.00 | 01-JAN-00:10 | 42572.21 | 23-JAN-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 323.62 | 0.00 | 01-JAN-00:10 | 42572.21 | 23-JAN-12:50 |
EnergyTransfer:HVAC | 18752.36 | 7426.03 | 01-JAN-07:50 | 2300694.08 | 11-AUG-15:50 |
HeatingCoils:EnergyTransfer | 61.17 | 0.00 | 01-JAN-00:10 | 366728.48 | 06-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 61.17 | 0.00 | 01-JAN-00:10 | 366728.48 | 06-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 61.17 | 0.00 | 01-JAN-00:10 | 366728.48 | 06-DEC-07:10 |
CoolingCoils:EnergyTransfer | 18691.20 | 6182.24 | 02-JAN-07:10 | 2300694.08 | 11-AUG-15:50 |
EnergyTransfer:Plant | 40059.43 | 0.00 | 01-JAN-00:10 | 6327401.87 | 05-SEP-07:50 |
LoopToLoop:EnergyTransfer | 12719.21 | 0.00 | 01-JAN-00:10 | 2005453.98 | 05-SEP-07:40 |
WaterSystems:EnergyTransfer | 323.62 | 0.00 | 01-JAN-00:10 | 42572.21 | 23-JAN-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 323.62 | 0.00 | 01-JAN-00:10 | 42572.21 | 23-JAN-12:50 |
Boilers:EnergyTransfer | 60.58 | 0.00 | 01-JAN-00:10 | 442648.09 | 06-DEC-07:10 |
Chillers:EnergyTransfer | 12562.30 | 0.00 | 01-JAN-00:10 | 2007022.51 | 05-SEP-07:50 |
HeatRejection:EnergyTransfer | 14393.71 | 0.00 | 01-JAN-00:10 | 2296675.92 | 05-SEP-07:50 |
General:HeatRejection:EnergyTransfer | 14393.71 | 0.00 | 01-JAN-00:10 | 2296675.92 | 05-SEP-07:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.324 | -702.239 | 0.000 | 0.000 | 92.679 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 15.110 | 0.000 | 0.000 | 0.000 | 0.000 | -0.013 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -684.338 | 0.000 | 0.000 | 83.399 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 162.488 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5013.039 | 0.000 | 0.000 | 835.630 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.029 | 0.000 | 0.000 | 0.000 | 0.000 | -207.085 |
CORE_TOP | 0.000 | 0.000 | 0.363 | -487.665 | 0.000 | 0.000 | 84.394 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -35.541 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -97.394 | 0.000 | 0.000 | 10.528 | 10.613 | 36.365 | 42.897 | 0.000 | 0.786 | 38.781 | 0.000 | -40.555 | 0.000 | -2.021 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -87.702 | 0.000 | 0.000 | 6.763 | 6.750 | 23.435 | 76.300 | 0.000 | 0.520 | 0.020 | 0.000 | -24.730 | 0.000 | -1.357 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -145.157 | 0.000 | 0.000 | 10.475 | 10.441 | 36.366 | 125.392 | 0.000 | 0.772 | 2.827 | 0.000 | -38.994 | 0.000 | -2.121 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -129.968 | 0.000 | 0.000 | 6.736 | 6.800 | 23.435 | 71.562 | 0.000 | 0.478 | 53.645 | 0.000 | -31.106 | 0.000 | -1.582 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.084 | -771.345 | 0.000 | 0.000 | 107.717 | 105.880 | 363.654 | 445.253 | 0.000 | 18.166 | 135.721 | 0.000 | -366.069 | 0.000 | -42.061 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.128 | -795.636 | 0.000 | 0.000 | 49.862 | 67.424 | 234.352 | 759.213 | 0.000 | 11.471 | 0.017 | 0.000 | -236.947 | 0.000 | -30.301 | -60.567 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.418 | -1302.485 | 0.000 | 0.000 | 105.071 | 104.304 | 363.660 | 1252.979 | 0.000 | 17.556 | 0.056 | 0.000 | -378.609 | 0.000 | -48.221 | -114.672 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.553 | -840.466 | 0.000 | 0.000 | 68.461 | 67.884 | 234.351 | 729.801 | 0.000 | 11.194 | 28.305 | 0.000 | -268.396 | 0.000 | -31.685 | -0.005 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.754 | -78.905 | 0.000 | 0.000 | 10.927 | 10.587 | 36.365 | 44.665 | 0.000 | 2.186 | 10.540 | 0.000 | -34.305 | 0.000 | -4.814 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.104 | -82.561 | 0.000 | 0.000 | 6.847 | 6.742 | 23.435 | 76.195 | 0.000 | 1.396 | 0.001 | 0.000 | -22.408 | 0.000 | -3.497 | -7.255 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.866 | -128.848 | 0.000 | 0.000 | 10.604 | 10.430 | 36.366 | 125.295 | 0.000 | 2.112 | 0.001 | 0.000 | -36.054 | 0.000 | -5.639 | -15.133 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.661 | -85.126 | 0.000 | 0.000 | 6.927 | 6.788 | 23.435 | 72.870 | 0.000 | 1.360 | 2.311 | 0.000 | -25.520 | 0.000 | -3.707 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -141.791 | 0.000 | 0.000 | 0.933 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.649 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.068 | -1298.444 | 0.000 | 0.000 | 9.363 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -286.056 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.073 | -125.346 | 0.000 | 0.000 | 0.939 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -33.172 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7158.945 | 0.000 | 0.000 | 19.181 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -402.705 |
GROUNDFLOOR_PLENUM | 1.130 | -93.068 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.475 | 94.941 | 0.000 | 0.000 | 0.000 | -4.478 | 0.000 |
MIDFLOOR_PLENUM | 13.237 | -640.482 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26.980 | 676.883 | 0.000 | 0.000 | 0.000 | -76.618 | -0.004 |
TOPFLOOR_PLENUM | 9.725 | -111.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.731 | 106.926 | 0.000 | 0.000 | 0.000 | -7.769 | -0.000 |
Total Facility | 24.092 | -845.163 | 15.396 | -20157.401 | 0.000 | 0.000 | 1527.436 | 2457.540 | 14676.396 | 3822.423 | 0.000 | 99.184 | 1328.604 | 0.000 | -1503.694 | 0.000 | -265.870 | -1178.860 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 03-JUL-04:11 | 0.00 | 0.00 | 0.00 | -105302.62 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 91246.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 30-MAY-04:13 | 0.00 | 0.00 | 0.00 | -90682.66 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 84207.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 01-JUN-04:13 | 0.00 | 0.00 | 0.00 | -830102.69 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 765352.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 19-JUN-04:13 | 0.00 | 0.00 | 0.00 | -85326.48 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 78851.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 25-JUN-18:31 | 0.00 | 0.00 | 0.00 | -19291.16 | 0.00 | 0.00 | 0.00 | 43.94 | 559.17 | 7247.82 | 0.00 | 369.15 | 11071.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-09:31 | 0.00 | 0.00 | 0.00 | -20301.51 | 0.00 | 0.00 | 20.90 | 28.32 | 464.11 | 12846.15 | 0.00 | 0.00 | 6967.41 | 0.00 | -0.00 | 0.00 | -25.38 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-13:21 | 0.00 | 0.00 | 0.00 | -23503.13 | 0.00 | 0.00 | 32.18 | 43.94 | 720.19 | 19825.58 | 0.00 | 38.19 | 2843.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 23-APR-16:21 | 0.00 | 0.00 | 0.00 | -28896.54 | 0.00 | 0.00 | 14.00 | 28.32 | 464.11 | 15505.62 | 0.00 | 63.19 | 12821.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-18:01 | 0.00 | 0.00 | 0.00 | -193600.53 | 0.00 | 0.00 | 0.00 | 439.44 | 5591.71 | 78543.10 | 0.00 | 9643.08 | 99383.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 13-AUG-08:51 | 0.00 | 0.00 | 0.00 | -223990.27 | 0.00 | 0.00 | 194.62 | 283.19 | 4641.14 | 145928.08 | 0.00 | 580.72 | 72362.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-12:31 | 0.00 | 0.00 | 0.00 | -236069.17 | 0.00 | 0.00 | 316.55 | 439.45 | 7201.95 | 204967.46 | 0.00 | 443.54 | 22700.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -262510.99 | 0.00 | 0.00 | 146.84 | 283.19 | 4641.11 | 155324.49 | 0.00 | 5442.74 | 96672.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-17:31 | 0.00 | 0.00 | 0.00 | -22919.98 | 0.00 | 0.00 | 0.00 | 43.94 | 559.17 | 6083.12 | 0.00 | 1215.86 | 15017.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 18-JUN-08:11 | 0.00 | 0.00 | 0.00 | -23108.92 | 0.00 | 0.00 | 18.58 | 28.32 | 464.11 | 15199.23 | 0.00 | 91.60 | 7307.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:41 | 0.00 | 0.00 | 0.00 | -26566.30 | 0.00 | 0.00 | 30.74 | 43.94 | 720.19 | 18620.19 | 0.00 | 53.71 | 7097.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-JUL-17:31 | 0.00 | 0.00 | 0.00 | -28833.69 | 0.00 | 0.00 | 0.00 | 28.32 | 360.35 | 15158.20 | 0.00 | 630.01 | 12656.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 28-DEC-17:00 | 0.00 | 0.00 | 0.00 | -7940.84 | 0.00 | 0.00 | 100.85 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -271.07 |
DATACENTER_MID_ZN_6 | 28-DEC-17:00 | 0.00 | 0.00 | 0.00 | -74714.95 | 0.00 | 0.00 | 1008.50 | 3166.31 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7404.08 |
DATACENTER_TOP_ZN_6 | 26-APR-18:30 | 0.00 | 0.00 | 0.00 | -7532.90 | 0.00 | 0.00 | 10.41 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -377.48 |
DATACENTER_BASEMENT_ZN_6 | 23-AUG-22:53 | 0.00 | 0.00 | 0.00 | -386587.40 | 0.00 | 0.00 | 105.71 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 6618.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 28-AUG-05:13 | 0.00 | -17219.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 17196.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 28-AUG-05:13 | 0.00 | -128128.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.34 | 127619.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:40 | 0.00 | -24169.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.99 | 23552.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-AUG-05:01 | 0.00 | -73520.89 | 0.00 | -2053805.41 | 0.00 | 0.00 | 15311.66 | 10593.62 | 616289.16 | 8250.51 | 0.00 | 2068.18 | 1475000.31 | 0.00 | -187.13 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 26-AUG-16:01 | 0.00 | 0.00 | 30163.03 | 0.00 | 0.00 | 0.00 | 520.13 | 819.05 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -44959.75 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:11 | 0.00 | 0.00 | 67034.54 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -73509.52 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 07-DEC-06:01 | 0.00 | 0.00 | 2626.48 | 0.00 | 0.00 | 0.00 | 91.56 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 627.67 | 0.00 | -3931.58 | 0.00 | -76.42 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 138380.12 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39298.04 | 0.00 | -2771.59 | -104440.81 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 117169.74 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27351.66 | 0.00 | -1926.06 | -93131.51 |
PERIMETER_MID_ZN_1 | 07-DEC-06:01 | 0.00 | 0.00 | 138785.07 | 0.00 | 0.00 | 0.00 | 1460.99 | 674.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -57694.65 | 0.00 | -2656.90 | -90171.83 |
PERIMETER_MID_ZN_4 | 07-DEC-06:01 | 0.00 | 0.00 | 100676.15 | 0.00 | 0.00 | 0.00 | 941.50 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37200.77 | 0.00 | -1775.69 | -69264.15 |
PERIMETER_TOP_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 17622.22 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3281.38 | 0.00 | -292.47 | -14861.40 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 15757.07 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2250.55 | 0.00 | -198.76 | -13831.71 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 17983.75 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3812.30 | 0.00 | -331.24 | -14653.25 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 15224.50 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2453.24 | 0.00 | -218.60 | -13076.61 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-08:30 | 0.00 | 0.00 | 2639.77 | 0.00 | 0.00 | 0.00 | 53.08 | 175.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22354.82 |
DATACENTER_TOP_ZN_6 | 01-JAN-02:65 | 0.00 | 0.00 | 583.89 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2550.09 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 23-APR-15:41 | 10752.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.53 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11207.38 |
MIDFLOOR_PLENUM | 30-JUL-16:11 | 93265.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13302.38 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -106568.13 |
TOPFLOOR_PLENUM | 02-JAN-06:03 | 17586.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -159.48 | -17426.59 |
Total Facility | 07-DEC-06:01 | -797238.98 | 742645.46 | 572172.90 | -742645.46 | 0.00 | 0.00 | 18892.42 | 10593.62 | 616289.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -224649.00 | 0.00 | -15464.92 | -180595.19 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.2250 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.0310 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 107.6407 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 94.4525 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.2329 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.7826 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.6803 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.6803 | 0.2113 | 1.0000 | Not calculated | 1.2002 | 0.2113 | ||
AIRLOOP DATACENTER BASEMENT | 23.4119 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 23.4121 | 0.0145 | 1.0000 | Not calculated | 0.3384 | 0.0145 | ||
AIRLOOP DATACENTER BOT | 0.5103 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5103 | 0.0306 | 1.0000 | Not calculated | 0.0156 | 0.0306 | ||
AIRLOOP DATACENTER MID | 4.8715 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8715 | 0.0321 | 1.0000 | Not calculated | 0.1563 | 0.0321 | ||
AIRLOOP DATACENTER TOP | 0.4985 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4985 | 0.0314 | 1.0000 | Not calculated | 0.0156 | 0.0314 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.6125 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2863 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 53.8203 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8619 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.6164 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2830 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.6803 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.6803 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2113 | ||
AIRLOOP DATACENTER BASEMENT | 23.4119 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 23.4119 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0145 | ||
AIRLOOP DATACENTER BOT | 0.5103 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5103 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0306 | ||
AIRLOOP DATACENTER MID | 4.8715 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8715 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0321 | ||
AIRLOOP DATACENTER TOP | 0.4985 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4985 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0314 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.6803 | 5.6803 | 5.6803 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0612 | 6.0612 | 1.6183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 57.1759 | 57.1759 | 16.1808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7052 | 5.7052 | 1.6146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1751 | 1.1751 | 0.2033 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1662 | 1.1662 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3206 | 1.3206 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5019 | 1.5019 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.6109 | 11.6109 | 2.0319 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.3698 | 12.3698 | 1.3112 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.0356 | 13.0356 | 2.0336 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.4485 | 13.4485 | 1.3045 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3329 | 1.3329 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2724 | 1.2724 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4642 | 1.4642 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4582 | 1.4582 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5103 | 0.5103 | 0.5103 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8715 | 4.8715 | 4.8715 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4985 | 0.4985 | 0.4985 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 23.4119 | 23.4119 | 23.4119 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.2250 | 10.0310 | 11.2250 | 2.2863 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 107.6407 | 94.4525 | 107.6407 | 22.8619 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.2329 | 10.7826 | 11.2329 | 2.2830 | 0.0000 | 1.0000 |
CAV_BAS | 5.6803 | 5.6803 | 5.6803 | 5.6803 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 23.4119 | 23.4121 | 23.4119 | 23.4119 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5103 | 0.5103 | 0.5103 | 0.5103 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8715 | 4.8715 | 4.8715 | 4.8715 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4985 | 0.4985 | 0.4985 | 0.4985 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.6803 | 5.6803 | 5.6803 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0306 | 3.0306 | 1.6183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.5879 | 28.5879 | 16.1808 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8526 | 2.8526 | 1.6146 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5876 | 0.5876 | 0.2033 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5831 | 0.5831 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6603 | 0.6603 | 0.2034 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7510 | 0.7510 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8055 | 5.8055 | 2.0319 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1849 | 6.1849 | 1.3112 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5178 | 6.5178 | 2.0336 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7242 | 6.7242 | 1.3045 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6664 | 0.6664 | 0.2026 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6362 | 0.6362 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7321 | 0.7321 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7291 | 0.7291 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5103 | 0.5103 | 0.5103 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8715 | 4.8715 | 4.8715 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4985 | 0.4985 | 0.4985 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 23.4119 | 23.4119 | 23.4119 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.6125 | 2.2863 | 2.2863 | 2.2863 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 53.8203 | 22.8619 | 22.8619 | 22.8619 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.6164 | 2.2830 | 2.2830 | 2.2830 | 0.0000 | 1.0000 |
CAV_BAS | 5.6803 | 5.6803 | 5.6803 | 5.6803 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 23.4119 | 23.4119 | 23.4119 | 23.4119 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5103 | 0.5103 | 0.5103 | 0.5103 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8715 | 4.8715 | 4.8715 | 4.8715 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4985 | 0.4985 | 0.4985 | 0.4985 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 1140.17 |
Number of hours not met | 1140.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 86.74 | 531907.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3858.36 | 446424.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2457.54 | 247210.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 350.70 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.68 | 3412.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2725.16 | 268224.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 564.44 | 47736.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1158.60 | 77358.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1609.69 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 647.04 | 76823.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 29310.18 |
Natural Gas | 0.00 | 733.78 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 30043.96 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.06 |
Space Heating | 0.00 |
Space Cooling | 83.30 |
Fans (All) | 58.83 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 632.77 |
Subtotal | 632.77 |
Natural Gas [MJ/m2] | |
Space Heating | 1.87 |
Service Water Heating | 13.97 |
Miscellaneous (All) | 15.84 |
Subtotal | 15.84 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.18 |
Space Heating | 0.29 |
Space Cooling | 12.84 |
Fans (All) | 9.07 |
Service Water Heating | 2.15 |
Receptacle Equipment | 48.85 |
Miscellaneous | 18.62 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 829. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8410.83 | 349.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8733.50 | 26.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8742.33 | 17.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8698.50 | 61.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8650.33 | 109.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8639.33 | 120.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8252.50 | 507.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8697.67 | 62.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8566.33 | 193.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8589.67 | 170.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8434.83 | 325.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8655.00 | 105.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8540.67 | 219.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8566.00 | 194.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8435.17 | 324.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7508.83 | 1251.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7605.17 | 1154.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7663.83 | 1096.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6631.17 | 2044.67 | 84.17 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8745.33 | 14.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8521.17 | 238.83 | 0.00 | 0.00 | 0.00 |
Min | 6631.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2044.67 | 84.17 | 0.00 | 0.00 |
Average | 8382.88 | 373.46 | 3.66 | 0.00 | 0.00 |
Sum | 192806.33 | 8589.50 | 84.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367527.50 | 1088.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330773.00 | 40.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330802.00 | 11.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330791.00 | 22.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1696.50 | 571.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1704.50 | 563.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1724.33 | 543.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 74186.00 | 27768.33 | 1440.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367527.50 | 27768.33 | 1440.67 | 0.00 | 0.00 |
Average | 78941.47 | 1330.80 | 62.64 | 0.00 | 0.00 |
Sum | 1815653.83 | 30608.50 | 1440.67 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8046.33 | 713.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8383.17 | 376.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8439.17 | 320.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8416.67 | 343.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8298.17 | 461.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8340.67 | 419.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8261.17 | 498.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8066.33 | 693.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8260.50 | 499.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8194.00 | 566.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8212.83 | 547.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8141.50 | 618.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8253.50 | 506.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8201.00 | 559.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8213.83 | 546.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8160.17 | 599.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8191.50 | 568.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8233.33 | 526.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8267.00 | 493.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7162.33 | 1593.33 | 4.33 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8192.00 | 568.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8201.67 | 558.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7789.17 | 970.83 | 0.00 | 0.00 | 0.00 |
Min | 7162.33 | 320.83 | 0.00 | 0.00 | 0.00 |
Max | 8439.17 | 1593.33 | 4.33 | 0.00 | 0.00 |
Average | 8170.70 | 589.12 | 0.19 | 0.00 | 0.00 |
Sum | 187926.00 | 13549.67 | 4.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 365838.50 | 2777.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329979.00 | 834.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330269.00 | 544.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330180.00 | 633.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24898.17 | 10.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1927.67 | 340.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1928.50 | 339.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1949.00 | 319.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 82912.50 | 20373.83 | 108.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 365838.50 | 20373.83 | 108.67 | 0.00 | 0.00 |
Average | 79192.24 | 1137.95 | 4.72 | 0.00 | 0.00 |
Sum | 1821421.50 | 26172.83 | 108.67 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:51:38
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.549391E+11 | 102750.74 | 02-JAN-05:11 | 4.00 | 1.01 | 0.566889E+10 | 7499.23 | 23-JAN-14:20 | 21.67 | 11.33 |
February | 0.456864E+11 | 101989.06 | 21-FEB-05:12 | 9.33 | 8.41 | 0.513842E+10 | 7499.28 | 15-FEB-14:00 | 9.33 | 8.41 |
March | 0.536142E+11 | 103219.98 | 20-MAR-04:12 | 11.83 | 7.65 | 0.613197E+10 | 7499.22 | 10-MAR-14:20 | 11.83 | 7.65 |
April | 0.543241E+11 | 102337.13 | 24-APR-04:21 | 16.00 | 5.06 | 0.545135E+10 | 7499.22 | 06-APR-09:20 | 16.00 | 5.06 |
May | 0.547333E+11 | 103380.18 | 08-MAY-04:11 | 22.00 | 10.09 | 0.590117E+10 | 7499.17 | 11-MAY-09:20 | 26.33 | 13.51 |
June | 0.562778E+11 | 103419.32 | 19-JUN-04:12 | 22.67 | 10.74 | 0.588198E+10 | 7499.27 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.612846E+11 | 105301.79 | 03-JUL-04:11 | 20.67 | 7.71 | 0.547549E+10 | 7499.38 | 21-JUL-09:20 | 31.33 | 20.88 |
August | 0.709876E+11 | 103144.26 | 27-AUG-16:16 | 40.00 | 18.14 | 0.613922E+10 | 7499.16 | 15-AUG-09:20 | 40.00 | 18.14 |
September | 0.634091E+11 | 100241.87 | 28-SEP-04:12 | 21.83 | 12.80 | 0.545575E+10 | 7499.23 | 22-SEP-09:20 | 21.83 | 12.80 |
October | 0.650312E+11 | 103627.22 | 23-OCT-04:12 | 11.00 | 9.66 | 0.567345E+10 | 7505.68 | 10-OCT-09:09 | 11.00 | 9.66 |
November | 0.621103E+11 | 102362.40 | 06-NOV-05:12 | 7.67 | 2.51 | 0.561711E+10 | 7499.39 | 16-NOV-14:20 | 18.00 | 11.91 |
December | 0.598438E+11 | 102973.40 | 11-DEC-05:11 | 8.33 | 1.55 | 0.547379E+10 | 7499.11 | 21-DEC-14:20 | 25.33 | 10.67 |
Annual Sum or Average | 0.702241E+12 | 0.680086E+11 | ||||||||
Minimum of Months | 0.456864E+11 | 100241.87 | 4.00 | 1.01 | 0.513842E+10 | 7499.11 | 9.33 | 5.06 | ||
Maximum of Months | 0.709876E+11 | 105301.79 | 40.00 | 18.14 | 0.613922E+10 | 7505.68 | 40.00 | 20.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.455183E+11 | 86351.38 | 17-JAN-05:12 | 11.33 | 3.83 | 0.507725E+10 | 6734.80 | 23-JAN-14:20 | 21.67 | 11.33 |
February | 0.404734E+11 | 86575.69 | 21-FEB-05:12 | 9.33 | 8.41 | 0.460659E+10 | 6735.04 | 15-FEB-14:00 | 9.33 | 8.41 |
March | 0.527648E+11 | 87676.09 | 20-MAR-04:12 | 11.83 | 7.65 | 0.550035E+10 | 6734.87 | 17-MAR-09:00 | 11.83 | 7.65 |
April | 0.644930E+11 | 84404.17 | 28-APR-04:13 | 14.33 | 7.25 | 0.487965E+10 | 6734.83 | 10-APR-09:09 | 14.33 | 7.25 |
May | 0.567469E+11 | 90694.21 | 30-MAY-04:13 | 18.00 | 9.08 | 0.528632E+10 | 6734.80 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.644396E+11 | 88323.36 | 01-JUN-04:13 | 22.33 | 12.88 | 0.526646E+10 | 6734.81 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.670763E+11 | 80507.23 | 29-JUL-04:12 | 21.00 | 17.45 | 0.489536E+10 | 6734.85 | 05-JUL-09:09 | 21.00 | 17.45 |
August | 0.766746E+11 | 83930.17 | 21-AUG-05:05 | 24.67 | 16.53 | 0.549892E+10 | 6772.71 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.569656E+11 | 88309.23 | 29-SEP-04:13 | 20.53 | 11.28 | 0.488323E+10 | 6734.80 | 15-SEP-09:20 | 20.53 | 11.28 |
October | 0.559739E+11 | 90651.56 | 10-OCT-04:13 | 18.00 | 12.03 | 0.508038E+10 | 6734.81 | 10-OCT-09:09 | 26.50 | 15.73 |
November | 0.522973E+11 | 88358.68 | 06-NOV-05:12 | 7.67 | 2.51 | 0.503116E+10 | 6734.99 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.509148E+11 | 89460.58 | 04-DEC-05:12 | 3.00 | 0.78 | 0.490371E+10 | 6734.75 | 19-DEC-10:20 | 13.00 | 5.14 |
Annual Sum or Average | 0.684339E+12 | 0.609094E+11 | ||||||||
Minimum of Months | 0.404734E+11 | 80507.23 | 3.00 | 0.78 | 0.460659E+10 | 6734.75 | 9.33 | 5.14 | ||
Maximum of Months | 0.766746E+11 | 90694.21 | 24.67 | 17.45 | 0.550035E+10 | 6772.71 | 33.33 | 20.35 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333953E+11 | 74714.05 | 27-JAN-06:02 | 12.83 | 5.24 | 0.504106E+10 | 6734.78 | 11-JAN-10:20 | 12.83 | 5.24 |
February | 0.286476E+11 | 74311.25 | 01-FEB-06:02 | 5.00 | 3.59 | 0.458142E+10 | 6734.88 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.371318E+11 | 75592.85 | 20-MAR-04:12 | 11.83 | 7.65 | 0.548620E+10 | 6734.83 | 17-MAR-09:00 | 11.83 | 7.65 |
April | 0.435141E+11 | 77300.54 | 18-APR-04:12 | 16.67 | 9.88 | 0.487550E+10 | 6734.82 | 03-APR-09:30 | 16.67 | 9.88 |
May | 0.483417E+11 | 77558.79 | 31-MAY-04:12 | 19.00 | 9.54 | 0.528291E+10 | 6734.80 | 30-MAY-09:20 | 19.00 | 9.54 |
June | 0.527512E+11 | 82977.06 | 01-JUN-04:13 | 22.33 | 12.88 | 0.526337E+10 | 6734.81 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.506143E+11 | 82680.20 | 03-JUL-04:13 | 20.67 | 7.71 | 0.489160E+10 | 6734.86 | 21-JUL-09:20 | 31.33 | 20.88 |
August | 0.527044E+11 | 76487.84 | 05-AUG-04:12 | 21.67 | 17.87 | 0.549348E+10 | 6734.89 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.465086E+11 | 78389.02 | 26-SEP-04:12 | 20.00 | 15.92 | 0.488129E+10 | 6734.79 | 15-SEP-09:20 | 20.00 | 15.92 |
October | 0.420643E+11 | 78264.18 | 11-OCT-04:12 | 18.00 | 10.82 | 0.507124E+10 | 6734.85 | 03-OCT-13:39 | 18.00 | 10.82 |
November | 0.350364E+11 | 78525.92 | 13-NOV-05:12 | 17.00 | 17.00 | 0.501427E+10 | 6734.93 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.305951E+11 | 73507.84 | 28-DEC-06:02 | 8.67 | 3.60 | 0.486313E+10 | 6734.78 | 13-DEC-10:20 | 8.67 | 3.60 |
Annual Sum or Average | 0.501305E+12 | 0.607455E+11 | ||||||||
Minimum of Months | 0.286476E+11 | 73507.84 | 5.00 | 3.59 | 0.458142E+10 | 6734.78 | 8.67 | 3.60 | ||
Maximum of Months | 0.527512E+11 | 82977.06 | 22.33 | 17.87 | 0.549348E+10 | 6734.93 | 33.33 | 20.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259273E+11 | 35728.87 | 27-JAN-17:00 | 26.00 | 9.22 | 0.488506E+10 | 6734.73 | 09-JAN-10:20 | 26.00 | 9.22 |
February | 0.218771E+11 | 33878.84 | 23-FEB-15:00 | 18.00 | 10.35 | 0.442421E+10 | 6734.78 | 15-FEB-14:00 | 18.00 | 10.35 |
March | 0.307444E+11 | 72024.86 | 17-MAR-05:03 | 13.48 | 9.60 | 0.539168E+10 | 6734.80 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.439130E+11 | 76307.29 | 26-APR-04:12 | 20.00 | 10.45 | 0.486766E+10 | 6734.81 | 03-APR-09:20 | 20.00 | 10.45 |
May | 0.512461E+11 | 84595.62 | 08-MAY-04:13 | 22.00 | 10.09 | 0.528393E+10 | 6734.79 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.600559E+11 | 85336.75 | 19-JUN-04:13 | 22.67 | 10.74 | 0.526760E+10 | 6734.81 | 29-JUN-09:20 | 33.33 | 18.14 |
July | 0.578334E+11 | 84818.26 | 03-JUL-04:13 | 20.67 | 7.71 | 0.489735E+10 | 6734.85 | 05-JUL-09:09 | 31.33 | 16.71 |
August | 0.585246E+11 | 78759.68 | 21-AUG-05:03 | 24.67 | 16.53 | 0.549646E+10 | 6734.89 | 28-AUG-09:20 | 32.00 | 20.57 |
September | 0.497982E+11 | 80378.48 | 05-SEP-04:13 | 22.53 | 18.57 | 0.488372E+10 | 6734.78 | 15-SEP-09:20 | 25.90 | 16.61 |
October | 0.381850E+11 | 77012.85 | 05-OCT-04:12 | 19.67 | 13.65 | 0.503559E+10 | 6734.80 | 10-OCT-09:09 | 26.50 | 15.73 |
November | 0.279500E+11 | 72255.06 | 03-NOV-05:03 | 16.00 | 12.46 | 0.490124E+10 | 6734.86 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.216135E+11 | 33733.37 | 22-DEC-16:50 | 24.17 | 9.62 | 0.457986E+10 | 6734.71 | 12-DEC-14:30 | 24.17 | 9.62 |
Annual Sum or Average | 0.487668E+12 | 0.599144E+11 | ||||||||
Minimum of Months | 0.216135E+11 | 33733.37 | 13.48 | 7.71 | 0.442421E+10 | 6734.71 | 18.00 | 9.22 | ||
Maximum of Months | 0.600559E+11 | 85336.75 | 26.00 | 18.57 | 0.549646E+10 | 6734.89 | 33.33 | 20.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379996E+10 | 5236.82 | 31-JAN-16:30 | 29.00 | 10.73 | 0.623619E+09 | 845.63 | 23-JAN-14:20 | 29.00 | 10.73 |
February | 0.322725E+10 | 5211.48 | 22-FEB-14:00 | 21.00 | 12.01 | 0.565471E+09 | 845.66 | 15-FEB-14:00 | 21.00 | 12.01 |
March | 0.519902E+10 | 7397.15 | 20-MAR-14:00 | 27.70 | 14.42 | 0.682129E+09 | 845.64 | 17-MAR-09:00 | 27.70 | 14.42 |
April | 0.922886E+10 | 18073.25 | 30-APR-16:21 | 32.50 | 11.88 | 0.612590E+09 | 845.63 | 27-APR-13:39 | 32.50 | 11.88 |
May | 0.988732E+10 | 18146.72 | 29-MAY-18:11 | 30.67 | 13.66 | 0.664572E+09 | 845.63 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.138105E+11 | 19291.97 | 25-JUN-18:31 | 36.67 | 14.58 | 0.663109E+09 | 845.74 | 19-JUN-13:00 | 36.67 | 14.58 |
July | 0.132670E+11 | 18952.81 | 04-JUL-18:11 | 36.00 | 14.97 | 0.616672E+09 | 845.66 | 17-JUL-13:50 | 36.67 | 20.83 |
August | 0.138988E+11 | 18500.01 | 13-AUG-16:21 | 38.00 | 20.26 | 0.691596E+09 | 851.55 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.989074E+10 | 18053.44 | 10-SEP-16:42 | 34.00 | 19.47 | 0.614086E+09 | 845.63 | 15-SEP-09:20 | 25.90 | 16.61 |
October | 0.676857E+10 | 14031.51 | 02-OCT-04:23 | 26.00 | 17.05 | 0.634419E+09 | 845.66 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.474807E+10 | 9271.52 | 13-NOV-06:03 | 16.83 | 16.83 | 0.624586E+09 | 845.65 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.366903E+10 | 5465.25 | 26-DEC-15:30 | 23.00 | 10.56 | 0.598727E+09 | 845.62 | 19-DEC-10:20 | 23.00 | 10.56 |
Annual Sum or Average | 0.973951E+11 | 0.759158E+10 | ||||||||
Minimum of Months | 0.322725E+10 | 5211.48 | 16.83 | 10.56 | 0.565471E+09 | 845.62 | 18.00 | 10.56 | ||
Maximum of Months | 0.138988E+11 | 19291.97 | 38.00 | 20.26 | 0.691596E+09 | 851.55 | 36.67 | 20.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391059E+10 | 7730.19 | 17-JAN-09:30 | 16.50 | 6.15 | 0.407017E+09 | 544.96 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.315368E+10 | 10671.26 | 20-FEB-09:03 | 12.33 | 11.58 | 0.367868E+09 | 544.97 | 15-FEB-14:00 | 12.33 | 11.58 |
March | 0.483583E+10 | 17217.37 | 19-MAR-09:32 | 21.80 | 12.11 | 0.441935E+09 | 544.97 | 14-MAR-09:00 | 21.80 | 12.11 |
April | 0.873138E+10 | 19626.92 | 23-APR-08:22 | 23.50 | 8.72 | 0.395365E+09 | 545.91 | 24-APR-09:50 | 26.83 | 10.74 |
May | 0.996235E+10 | 20301.77 | 29-MAY-09:31 | 27.33 | 12.10 | 0.428959E+09 | 545.77 | 11-MAY-09:00 | 27.33 | 12.10 |
June | 0.122030E+11 | 20170.01 | 25-JUN-07:51 | 28.00 | 13.23 | 0.427661E+09 | 545.64 | 09-JUN-09:00 | 28.00 | 13.23 |
July | 0.111006E+11 | 19067.67 | 04-JUL-08:51 | 30.00 | 12.88 | 0.397694E+09 | 545.58 | 13-JUL-09:50 | 31.83 | 20.83 |
August | 0.112496E+11 | 19027.73 | 13-AUG-09:02 | 32.17 | 20.93 | 0.445826E+09 | 550.93 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.861408E+10 | 19940.70 | 10-SEP-09:21 | 30.20 | 19.40 | 0.396012E+09 | 546.33 | 08-SEP-09:00 | 30.20 | 19.40 |
October | 0.658691E+10 | 18792.06 | 15-OCT-08:42 | 23.33 | 9.51 | 0.410196E+09 | 545.45 | 05-OCT-09:09 | 23.33 | 9.51 |
November | 0.421198E+10 | 9026.42 | 19-NOV-09:33 | 21.33 | 10.18 | 0.404243E+09 | 544.98 | 22-NOV-10:50 | 20.00 | 11.34 |
December | 0.314236E+10 | 6784.77 | 26-DEC-09:40 | 16.33 | 7.28 | 0.390540E+09 | 544.95 | 13-DEC-10:09 | 16.33 | 7.28 |
Annual Sum or Average | 0.877023E+11 | 0.491332E+10 | ||||||||
Minimum of Months | 0.314236E+10 | 6784.77 | 12.33 | 6.15 | 0.367868E+09 | 544.95 | 12.33 | 7.28 | ||
Maximum of Months | 0.122030E+11 | 20301.77 | 32.17 | 20.93 | 0.445826E+09 | 550.93 | 31.83 | 20.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124594E+11 | 22628.36 | 22-JAN-13:32 | 18.67 | 11.29 | 0.637316E+09 | 904.01 | 17-JAN-14:20 | 18.67 | 11.29 |
February | 0.738373E+10 | 17043.02 | 26-FEB-11:13 | 14.67 | 9.92 | 0.571380E+09 | 847.69 | 28-FEB-14:09 | 18.17 | 7.92 |
March | 0.880800E+10 | 15819.24 | 26-MAR-14:53 | 17.20 | 5.56 | 0.683943E+09 | 847.31 | 17-MAR-13:09 | 17.20 | 5.56 |
April | 0.125804E+11 | 21341.38 | 23-APR-15:41 | 33.25 | 12.77 | 0.613299E+09 | 847.04 | 25-APR-13:30 | 31.00 | 14.65 |
May | 0.107429E+11 | 20488.08 | 07-MAY-16:21 | 36.00 | 14.22 | 0.664709E+09 | 845.65 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.132874E+11 | 21118.35 | 04-JUN-15:51 | 38.00 | 16.06 | 0.662931E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.134797E+11 | 20976.40 | 04-JUL-16:51 | 37.00 | 15.96 | 0.616693E+09 | 846.05 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.158860E+11 | 21055.45 | 27-AUG-13:41 | 39.67 | 18.22 | 0.691876E+09 | 851.84 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.137726E+11 | 22735.38 | 10-SEP-12:41 | 34.22 | 18.96 | 0.615333E+09 | 901.20 | 28-SEP-13:39 | 36.47 | 16.05 |
October | 0.137053E+11 | 23503.15 | 15-OCT-13:21 | 30.50 | 12.34 | 0.640852E+09 | 903.94 | 31-OCT-13:50 | 26.50 | 11.92 |
November | 0.119732E+11 | 22547.24 | 26-NOV-12:42 | 18.00 | 8.27 | 0.634199E+09 | 913.83 | 20-NOV-14:20 | 18.00 | 8.27 |
December | 0.110807E+11 | 22616.59 | 10-DEC-14:02 | 21.00 | 8.00 | 0.612658E+09 | 894.90 | 27-DEC-14:09 | 19.17 | 9.79 |
Annual Sum or Average | 0.145159E+12 | 0.764519E+10 | ||||||||
Minimum of Months | 0.738373E+10 | 15819.24 | 14.67 | 5.56 | 0.571380E+09 | 845.65 | 17.20 | 5.56 | ||
Maximum of Months | 0.158860E+11 | 23503.15 | 39.67 | 18.96 | 0.691876E+09 | 913.83 | 38.17 | 20.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.564841E+10 | 24377.94 | 29-JAN-16:22 | 24.50 | 9.40 | 0.409641E+09 | 544.98 | 30-JAN-14:00 | 25.00 | 9.66 |
February | 0.485623E+10 | 18040.19 | 20-FEB-16:22 | 17.50 | 9.63 | 0.372305E+09 | 545.00 | 15-FEB-14:00 | 17.50 | 9.63 |
March | 0.827379E+10 | 23157.96 | 26-MAR-16:12 | 18.30 | 6.21 | 0.445669E+09 | 544.97 | 09-MAR-14:00 | 18.30 | 6.21 |
April | 0.151014E+11 | 28896.48 | 23-APR-16:21 | 33.15 | 12.72 | 0.396888E+09 | 544.97 | 27-APR-13:39 | 25.33 | 11.96 |
May | 0.118607E+11 | 27513.08 | 28-MAY-17:01 | 32.83 | 12.78 | 0.429389E+09 | 544.96 | 12-MAY-09:09 | 32.83 | 12.78 |
June | 0.156842E+11 | 28754.76 | 25-JUN-17:11 | 38.00 | 15.21 | 0.428130E+09 | 544.96 | 19-JUN-13:09 | 38.00 | 15.21 |
July | 0.150310E+11 | 28193.33 | 04-JUL-16:51 | 37.00 | 15.96 | 0.398465E+09 | 544.97 | 05-JUL-09:09 | 31.33 | 16.71 |
August | 0.188149E+11 | 27085.93 | 13-AUG-16:21 | 38.00 | 20.26 | 0.446904E+09 | 550.57 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.104356E+11 | 24248.60 | 04-SEP-15:42 | 31.60 | 21.45 | 0.396628E+09 | 544.96 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.920321E+10 | 24844.17 | 15-OCT-14:01 | 31.00 | 12.59 | 0.412149E+09 | 544.99 | 03-OCT-13:39 | 31.00 | 12.59 |
November | 0.795557E+10 | 23052.91 | 26-NOV-14:42 | 18.97 | 9.07 | 0.407745E+09 | 544.99 | 27-NOV-14:39 | 24.97 | 9.27 |
December | 0.710469E+10 | 24160.14 | 25-DEC-16:12 | 25.33 | 11.74 | 0.397184E+09 | 544.95 | 13-DEC-10:09 | 25.33 | 11.74 |
Annual Sum or Average | 0.129970E+12 | 0.494110E+10 | ||||||||
Minimum of Months | 0.485623E+10 | 18040.19 | 17.50 | 6.21 | 0.372305E+09 | 544.95 | 17.50 | 6.21 | ||
Maximum of Months | 0.188149E+11 | 28896.48 | 38.00 | 21.45 | 0.446904E+09 | 550.57 | 38.00 | 20.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263335E+10 | 3953.37 | 31-JAN-16:30 | 29.00 | 10.73 | 0.577529E+09 | 845.62 | 23-JAN-14:20 | 29.00 | 10.73 |
February | 0.208253E+10 | 3210.13 | 22-FEB-14:10 | 21.00 | 11.95 | 0.521805E+09 | 845.62 | 15-FEB-14:00 | 21.00 | 11.95 |
March | 0.331970E+10 | 5661.58 | 16-MAR-16:00 | 28.80 | 13.95 | 0.650834E+09 | 845.63 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.638414E+10 | 17456.02 | 30-APR-16:31 | 32.33 | 11.86 | 0.608773E+09 | 845.63 | 27-APR-13:30 | 32.33 | 11.86 |
May | 0.890570E+10 | 18044.12 | 07-MAY-17:01 | 35.83 | 14.32 | 0.664199E+09 | 845.63 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.127888E+11 | 19361.15 | 25-JUN-18:01 | 37.67 | 14.86 | 0.663229E+09 | 845.64 | 19-JUN-13:09 | 37.67 | 14.86 |
July | 0.114924E+11 | 18950.27 | 30-JUL-18:11 | 37.33 | 18.54 | 0.616834E+09 | 845.65 | 21-JUL-09:20 | 37.33 | 18.54 |
August | 0.108173E+11 | 19202.53 | 13-AUG-16:11 | 38.00 | 20.37 | 0.691289E+09 | 845.64 | 28-AUG-09:39 | 33.00 | 21.02 |
September | 0.866268E+10 | 18029.02 | 10-SEP-16:42 | 34.00 | 19.47 | 0.613895E+09 | 845.63 | 08-SEP-09:20 | 34.00 | 19.47 |
October | 0.504322E+10 | 17753.53 | 01-OCT-13:32 | 37.00 | 19.01 | 0.619824E+09 | 845.67 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.291462E+10 | 5624.07 | 02-NOV-14:00 | 27.00 | 15.44 | 0.592548E+09 | 845.63 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.209077E+10 | 2770.66 | 22-DEC-16:10 | 24.83 | 10.00 | 0.526879E+09 | 845.49 | 22-DEC-14:00 | 24.83 | 10.00 |
Annual Sum or Average | 0.771352E+11 | 0.734764E+10 | ||||||||
Minimum of Months | 0.208253E+10 | 2770.66 | 21.00 | 10.00 | 0.521805E+09 | 845.49 | 18.00 | 10.00 | ||
Maximum of Months | 0.127888E+11 | 19361.15 | 38.00 | 20.37 | 0.691289E+09 | 845.67 | 37.67 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278562E+10 | 7073.99 | 27-JAN-11:05 | 22.33 | 7.96 | 0.294073E+09 | 548.50 | 26-JAN-13:09 | 22.33 | 7.96 |
February | 0.217624E+10 | 7228.57 | 23-FEB-11:05 | 15.83 | 10.67 | 0.265483E+09 | 548.50 | 21-FEB-13:09 | 15.83 | 10.67 |
March | 0.373654E+10 | 13982.39 | 19-MAR-09:23 | 21.35 | 11.96 | 0.320689E+09 | 548.51 | 16-MAR-10:09 | 21.35 | 11.96 |
April | 0.796331E+10 | 21496.07 | 30-APR-09:51 | 28.00 | 10.47 | 0.292227E+09 | 548.51 | 28-APR-10:09 | 28.00 | 10.47 |
May | 0.990685E+10 | 21787.53 | 07-MAY-09:01 | 27.17 | 11.80 | 0.317026E+09 | 548.52 | 22-MAY-10:09 | 25.33 | 9.96 |
June | 0.124050E+11 | 22394.03 | 25-JUN-08:41 | 30.50 | 14.32 | 0.315884E+09 | 548.51 | 29-JUN-10:09 | 34.33 | 18.62 |
July | 0.109717E+11 | 21714.92 | 30-JUL-08:11 | 27.00 | 19.19 | 0.294875E+09 | 548.51 | 03-JUL-14:09 | 27.00 | 19.19 |
August | 0.107324E+11 | 22403.74 | 13-AUG-08:51 | 32.00 | 20.88 | 0.329207E+09 | 548.51 | 22-AUG-10:09 | 32.17 | 19.35 |
September | 0.825948E+10 | 21577.46 | 10-SEP-10:01 | 31.88 | 19.21 | 0.292929E+09 | 548.51 | 22-SEP-10:09 | 25.37 | 17.42 |
October | 0.576292E+10 | 19560.72 | 09-OCT-09:52 | 25.00 | 14.42 | 0.301319E+09 | 548.50 | 18-OCT-10:09 | 26.33 | 11.01 |
November | 0.303708E+10 | 8610.25 | 01-NOV-10:05 | 23.33 | 16.05 | 0.294341E+09 | 548.52 | 22-NOV-11:09 | 19.33 | 11.05 |
December | 0.182653E+10 | 5666.45 | 27-DEC-11:05 | 16.33 | 7.91 | 0.277497E+09 | 548.49 | 27-DEC-13:09 | 19.00 | 10.04 |
Annual Sum or Average | 0.795637E+11 | 0.359555E+10 | ||||||||
Minimum of Months | 0.182653E+10 | 5666.45 | 15.83 | 7.91 | 0.265483E+09 | 548.49 | 15.83 | 7.96 | ||
Maximum of Months | 0.124050E+11 | 22403.74 | 32.00 | 20.88 | 0.329207E+09 | 548.52 | 34.33 | 19.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121945E+11 | 21650.21 | 29-JAN-13:52 | 24.00 | 9.34 | 0.637089E+09 | 931.25 | 30-JAN-14:39 | 24.67 | 9.55 |
February | 0.670911E+10 | 17093.60 | 20-FEB-15:13 | 18.00 | 10.13 | 0.563479E+09 | 863.80 | 28-FEB-14:20 | 18.33 | 7.88 |
March | 0.740762E+10 | 15714.64 | 26-MAR-14:03 | 17.20 | 5.96 | 0.672784E+09 | 846.80 | 17-MAR-13:09 | 17.20 | 5.96 |
April | 0.101909E+11 | 21137.67 | 30-APR-12:32 | 33.00 | 12.07 | 0.611432E+09 | 847.05 | 25-APR-13:20 | 33.00 | 12.07 |
May | 0.992168E+10 | 20422.76 | 07-MAY-16:21 | 36.00 | 14.22 | 0.664375E+09 | 845.65 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.121643E+11 | 20874.83 | 25-JUN-18:01 | 37.67 | 14.86 | 0.663009E+09 | 845.66 | 19-JUN-13:09 | 37.67 | 14.86 |
July | 0.117561E+11 | 21594.69 | 30-JUL-14:51 | 38.00 | 18.95 | 0.616842E+09 | 846.65 | 31-JUL-13:20 | 37.00 | 19.00 |
August | 0.131341E+11 | 22063.58 | 13-AUG-16:11 | 38.00 | 20.37 | 0.691748E+09 | 847.07 | 28-AUG-13:09 | 37.83 | 20.53 |
September | 0.130704E+11 | 22784.35 | 10-SEP-12:41 | 34.22 | 18.96 | 0.615933E+09 | 928.86 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.128884E+11 | 23606.86 | 09-OCT-12:31 | 30.33 | 16.96 | 0.640279E+09 | 930.50 | 31-OCT-13:00 | 27.00 | 12.18 |
November | 0.109199E+11 | 21330.51 | 19-NOV-13:32 | 26.00 | 11.06 | 0.631647E+09 | 926.91 | 20-NOV-14:20 | 27.00 | 11.68 |
December | 0.989354E+10 | 22752.83 | 03-DEC-14:32 | 21.00 | 10.61 | 0.604038E+09 | 907.38 | 28-DEC-14:09 | 19.47 | 8.47 |
Annual Sum or Average | 0.130251E+12 | 0.761266E+10 | ||||||||
Minimum of Months | 0.670911E+10 | 15714.64 | 17.20 | 5.96 | 0.563479E+09 | 845.65 | 17.20 | 5.96 | ||
Maximum of Months | 0.131341E+11 | 23606.86 | 38.00 | 20.37 | 0.691748E+09 | 931.25 | 37.83 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361844E+10 | 14447.62 | 29-JAN-16:32 | 24.33 | 9.38 | 0.390745E+09 | 544.95 | 23-JAN-14:20 | 24.33 | 9.38 |
February | 0.246807E+10 | 10774.24 | 22-FEB-16:30 | 20.50 | 11.47 | 0.351157E+09 | 544.96 | 15-FEB-14:00 | 20.50 | 11.47 |
March | 0.412716E+10 | 15884.79 | 18-MAR-17:05 | 26.92 | 12.85 | 0.430397E+09 | 544.96 | 17-MAR-09:00 | 26.92 | 12.85 |
April | 0.867369E+10 | 24766.66 | 30-APR-16:31 | 32.33 | 11.86 | 0.395248E+09 | 544.96 | 27-APR-13:30 | 32.33 | 11.86 |
May | 0.100773E+11 | 24975.43 | 07-MAY-16:21 | 36.00 | 14.22 | 0.428970E+09 | 544.96 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.128222E+11 | 26070.20 | 25-JUN-17:21 | 38.00 | 15.15 | 0.427926E+09 | 544.96 | 19-JUN-13:09 | 38.00 | 15.15 |
July | 0.106068E+11 | 25936.65 | 30-JUL-17:31 | 38.00 | 19.05 | 0.398098E+09 | 544.97 | 21-JUL-09:20 | 38.00 | 19.05 |
August | 0.108279E+11 | 26257.94 | 13-AUG-16:51 | 38.00 | 19.94 | 0.446165E+09 | 544.96 | 28-AUG-09:39 | 33.00 | 21.02 |
September | 0.830802E+10 | 23543.97 | 04-SEP-16:51 | 31.60 | 21.23 | 0.396259E+09 | 544.96 | 08-SEP-09:20 | 30.73 | 20.63 |
October | 0.597070E+10 | 22827.49 | 09-OCT-16:31 | 32.33 | 17.29 | 0.405484E+09 | 544.99 | 03-OCT-13:39 | 32.33 | 17.29 |
November | 0.393415E+10 | 14254.25 | 19-NOV-15:32 | 27.00 | 11.63 | 0.394998E+09 | 544.97 | 16-NOV-14:09 | 27.00 | 11.63 |
December | 0.261418E+10 | 14962.26 | 25-DEC-16:32 | 24.67 | 11.46 | 0.365284E+09 | 544.95 | 12-DEC-14:00 | 24.67 | 11.46 |
Annual Sum or Average | 0.840486E+11 | 0.483073E+10 | ||||||||
Minimum of Months | 0.246807E+10 | 10774.24 | 20.50 | 9.38 | 0.351157E+09 | 544.95 | 20.50 | 9.38 | ||
Maximum of Months | 0.128222E+11 | 26257.94 | 38.00 | 21.23 | 0.446165E+09 | 544.99 | 38.00 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208391E+10 | 3725.45 | 31-JAN-16:30 | 29.00 | 10.73 | 0.549847E+09 | 845.61 | 27-JAN-14:20 | 29.00 | 10.73 |
February | 0.160644E+10 | 2962.35 | 22-FEB-16:20 | 20.67 | 11.54 | 0.492454E+09 | 845.57 | 22-FEB-14:20 | 20.67 | 11.54 |
March | 0.286660E+10 | 6119.57 | 16-MAR-16:00 | 28.80 | 13.95 | 0.626250E+09 | 845.63 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.656260E+10 | 17346.66 | 30-APR-16:01 | 32.83 | 11.93 | 0.604465E+09 | 845.63 | 27-APR-13:00 | 32.83 | 11.93 |
May | 0.939259E+10 | 20763.89 | 28-MAY-16:51 | 33.00 | 12.91 | 0.663870E+09 | 845.63 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.140539E+11 | 21426.58 | 25-JUN-18:11 | 37.33 | 14.77 | 0.663397E+09 | 845.64 | 19-JUN-13:09 | 37.33 | 14.77 |
July | 0.127784E+11 | 22924.31 | 16-JUL-17:31 | 36.33 | 21.35 | 0.617018E+09 | 845.64 | 05-JUL-09:09 | 36.33 | 21.35 |
August | 0.117501E+11 | 21400.62 | 13-AUG-16:21 | 38.00 | 20.26 | 0.691403E+09 | 845.64 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.919967E+10 | 20594.63 | 24-SEP-15:32 | 33.80 | 18.53 | 0.613659E+09 | 845.63 | 19-SEP-13:20 | 33.80 | 18.53 |
October | 0.480640E+10 | 14762.44 | 02-OCT-03:02 | 25.17 | 16.69 | 0.605566E+09 | 845.66 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.238116E+10 | 5852.17 | 01-NOV-15:30 | 28.50 | 15.96 | 0.568968E+09 | 845.63 | 16-NOV-14:20 | 18.00 | 11.91 |
December | 0.142373E+10 | 2556.13 | 22-DEC-16:40 | 24.33 | 9.71 | 0.495627E+09 | 833.45 | 22-DEC-14:00 | 24.33 | 9.71 |
Annual Sum or Average | 0.789056E+11 | 0.719253E+10 | ||||||||
Minimum of Months | 0.142373E+10 | 2556.13 | 20.67 | 9.71 | 0.492454E+09 | 833.45 | 18.00 | 9.71 | ||
Maximum of Months | 0.140539E+11 | 22924.31 | 38.00 | 21.35 | 0.691403E+09 | 845.66 | 37.33 | 21.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235266E+10 | 4929.59 | 27-JAN-10:30 | 21.00 | 7.83 | 0.393502E+09 | 544.95 | 23-JAN-14:20 | 21.00 | 7.83 |
February | 0.177988E+10 | 5608.34 | 23-FEB-10:20 | 14.67 | 11.08 | 0.353640E+09 | 544.95 | 15-FEB-14:00 | 14.67 | 11.08 |
March | 0.344246E+10 | 7425.87 | 23-MAR-10:20 | 22.33 | 10.61 | 0.430879E+09 | 544.97 | 14-MAR-13:50 | 22.33 | 10.61 |
April | 0.832809E+10 | 20384.74 | 09-APR-10:22 | 26.00 | 9.74 | 0.394981E+09 | 544.99 | 11-APR-09:09 | 25.50 | 10.76 |
May | 0.105086E+11 | 21475.26 | 28-MAY-10:12 | 29.67 | 12.59 | 0.428993E+09 | 545.60 | 11-MAY-09:00 | 29.67 | 12.59 |
June | 0.135516E+11 | 23110.51 | 18-JUN-08:11 | 30.67 | 17.10 | 0.427966E+09 | 545.51 | 08-JUN-09:00 | 30.67 | 17.10 |
July | 0.121605E+11 | 22388.96 | 30-JUL-08:11 | 27.00 | 19.19 | 0.398154E+09 | 545.47 | 28-JUL-09:00 | 27.00 | 19.19 |
August | 0.116911E+11 | 21209.80 | 13-AUG-09:42 | 32.83 | 21.13 | 0.446160E+09 | 545.50 | 01-AUG-09:00 | 32.83 | 21.13 |
September | 0.888975E+10 | 20288.81 | 10-SEP-10:12 | 32.17 | 19.22 | 0.396143E+09 | 546.04 | 08-SEP-09:00 | 32.17 | 19.22 |
October | 0.568674E+10 | 19843.37 | 15-OCT-09:22 | 25.00 | 10.12 | 0.405799E+09 | 544.99 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.268801E+10 | 6508.86 | 01-NOV-10:00 | 23.00 | 16.02 | 0.393893E+09 | 544.98 | 22-NOV-10:50 | 20.00 | 11.34 |
December | 0.148177E+10 | 3126.63 | 22-DEC-10:40 | 20.33 | 8.51 | 0.359843E+09 | 544.95 | 13-DEC-10:20 | 20.33 | 8.51 |
Annual Sum or Average | 0.825611E+11 | 0.482995E+10 | ||||||||
Minimum of Months | 0.148177E+10 | 3126.63 | 14.67 | 7.83 | 0.353640E+09 | 544.95 | 14.67 | 7.83 | ||
Maximum of Months | 0.135516E+11 | 23110.51 | 32.83 | 21.13 | 0.446160E+09 | 546.04 | 32.83 | 21.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109213E+11 | 25863.50 | 29-JAN-14:11 | 24.00 | 9.34 | 0.619057E+09 | 872.92 | 24-JAN-14:00 | 24.00 | 9.34 |
February | 0.565047E+10 | 19554.80 | 26-FEB-14:43 | 17.00 | 9.72 | 0.547802E+09 | 846.72 | 23-FEB-14:00 | 17.00 | 9.72 |
March | 0.658945E+10 | 14425.96 | 23-MAR-14:00 | 25.50 | 11.67 | 0.657471E+09 | 845.98 | 16-MAR-13:00 | 25.50 | 11.67 |
April | 0.104448E+11 | 23532.25 | 02-APR-16:21 | 31.00 | 12.54 | 0.607993E+09 | 846.68 | 25-APR-13:09 | 31.00 | 14.74 |
May | 0.104495E+11 | 22939.21 | 28-MAY-16:51 | 33.00 | 12.91 | 0.663651E+09 | 845.65 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.133995E+11 | 22962.87 | 18-JUN-17:32 | 38.00 | 19.14 | 0.663188E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.130549E+11 | 25170.12 | 30-JUL-14:51 | 38.00 | 18.95 | 0.616983E+09 | 846.02 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.141297E+11 | 23822.36 | 13-AUG-16:21 | 38.00 | 20.26 | 0.691791E+09 | 847.36 | 28-AUG-13:09 | 37.83 | 20.53 |
September | 0.136972E+11 | 24307.75 | 10-SEP-13:32 | 34.80 | 19.48 | 0.615224E+09 | 901.84 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.125352E+11 | 26565.62 | 09-OCT-13:41 | 31.83 | 17.27 | 0.629750E+09 | 890.31 | 02-OCT-13:09 | 31.83 | 17.27 |
November | 0.982083E+10 | 23910.90 | 26-NOV-13:22 | 18.40 | 8.55 | 0.617628E+09 | 885.34 | 01-NOV-13:00 | 18.40 | 8.55 |
December | 0.815809E+10 | 24612.10 | 03-DEC-14:32 | 21.00 | 10.61 | 0.585246E+09 | 857.15 | 22-DEC-14:09 | 25.17 | 10.15 |
Annual Sum or Average | 0.128851E+12 | 0.751578E+10 | ||||||||
Minimum of Months | 0.565047E+10 | 14425.96 | 17.00 | 8.55 | 0.547802E+09 | 845.65 | 17.00 | 8.55 | ||
Maximum of Months | 0.141297E+11 | 26565.62 | 38.00 | 20.26 | 0.691791E+09 | 901.84 | 38.17 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317439E+10 | 20076.17 | 29-JAN-16:12 | 24.67 | 9.41 | 0.375406E+09 | 544.95 | 23-JAN-14:20 | 24.67 | 9.41 |
February | 0.210531E+10 | 10715.77 | 22-FEB-16:30 | 20.50 | 11.47 | 0.335593E+09 | 544.96 | 15-FEB-14:00 | 20.50 | 11.47 |
March | 0.375676E+10 | 17199.12 | 18-MAR-17:05 | 26.92 | 12.85 | 0.417382E+09 | 544.97 | 10-MAR-14:00 | 26.92 | 12.85 |
April | 0.884191E+10 | 27165.16 | 02-APR-16:21 | 31.00 | 12.54 | 0.393781E+09 | 544.97 | 27-APR-13:00 | 26.00 | 12.23 |
May | 0.104488E+11 | 27621.87 | 28-MAY-16:51 | 33.00 | 12.91 | 0.428841E+09 | 544.96 | 30-MAY-09:20 | 27.33 | 13.67 |
June | 0.136869E+11 | 25805.27 | 25-JUN-17:31 | 38.00 | 15.08 | 0.427987E+09 | 544.96 | 19-JUN-13:09 | 38.00 | 15.08 |
July | 0.115410E+11 | 28835.49 | 30-JUL-17:31 | 38.00 | 19.05 | 0.398145E+09 | 544.97 | 05-JUL-09:09 | 38.00 | 19.05 |
August | 0.114926E+11 | 26035.31 | 13-AUG-16:21 | 38.00 | 20.26 | 0.446178E+09 | 544.97 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.870188E+10 | 23850.78 | 24-SEP-15:32 | 33.80 | 18.53 | 0.396212E+09 | 544.96 | 15-SEP-09:20 | 33.80 | 18.53 |
October | 0.580521E+10 | 25120.30 | 09-OCT-15:41 | 32.83 | 17.35 | 0.398369E+09 | 544.98 | 03-OCT-13:30 | 32.83 | 17.35 |
November | 0.348013E+10 | 12446.44 | 01-NOV-16:00 | 28.00 | 15.72 | 0.383783E+09 | 544.97 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.209324E+10 | 13088.74 | 25-DEC-16:12 | 25.33 | 11.74 | 0.347869E+09 | 544.95 | 22-DEC-14:20 | 25.33 | 11.74 |
Annual Sum or Average | 0.851281E+11 | 0.474955E+10 | ||||||||
Minimum of Months | 0.209324E+10 | 10715.77 | 20.50 | 9.41 | 0.335593E+09 | 544.95 | 18.00 | 9.41 | ||
Maximum of Months | 0.136869E+11 | 28835.49 | 38.00 | 20.26 | 0.446178E+09 | 544.98 | 38.00 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.398051E+10 | 6159.60 | 17-JAN-17:00 | 24.00 | 9.10 | 0.00 | 0.00 | 01-JAN-00:10 | 24.00 | 9.10 |
February | 0.302598E+10 | 5299.93 | 21-FEB-16:00 | 21.00 | 11.18 | 0.00 | 0.00 | 01-FEB-00:10 | 21.00 | 11.18 |
March | 0.487319E+10 | 7383.93 | 20-MAR-05:15 | 11.27 | 7.51 | 0.00 | 0.00 | 01-MAR-00:10 | 11.27 | 7.51 |
April | 0.882027E+10 | 9319.85 | 24-APR-14:50 | 33.00 | 13.29 | 0.00 | 0.00 | 01-APR-00:10 | 33.00 | 13.29 |
May | 0.930571E+10 | 11964.53 | 30-MAY-05:15 | 18.00 | 8.93 | 0.00 | 0.00 | 01-MAY-00:10 | 18.00 | 8.93 |
June | 0.118780E+11 | 12046.87 | 05-JUN-05:10 | 23.33 | 12.92 | 0.00 | 0.00 | 01-JUN-00:10 | 23.33 | 12.92 |
July | 0.117630E+11 | 15132.12 | 05-JUL-05:15 | 23.00 | 11.31 | 0.00 | 0.00 | 01-JUL-00:10 | 23.00 | 11.31 |
August | 0.131770E+11 | 17219.69 | 28-AUG-05:13 | 28.67 | 19.85 | 0.00 | 0.00 | 01-AUG-00:10 | 28.67 | 19.85 |
September | 0.952833E+10 | 13994.52 | 05-SEP-05:15 | 21.63 | 18.84 | 0.00 | 0.00 | 01-SEP-00:10 | 21.63 | 18.84 |
October | 0.738933E+10 | 13452.12 | 02-OCT-05:15 | 25.67 | 16.91 | 0.00 | 0.00 | 01-OCT-00:10 | 25.67 | 16.91 |
November | 0.535549E+10 | 9054.68 | 13-NOV-06:15 | 16.67 | 16.67 | 0.00 | 0.00 | 01-NOV-00:10 | 16.67 | 16.67 |
December | 0.397146E+10 | 8889.90 | 26-DEC-06:15 | 8.67 | 3.13 | 0.00 | 0.00 | 01-DEC-00:10 | 8.67 | 3.13 |
Annual Sum or Average | 0.930682E+11 | 0.00 | ||||||||
Minimum of Months | 0.302598E+10 | 5299.93 | 8.67 | 3.13 | 0.00 | 0.00 | 8.67 | 3.13 | ||
Maximum of Months | 0.131770E+11 | 17219.69 | 33.00 | 19.85 | 0.00 | 0.00 | 33.00 | 19.85 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.172992E+10 | 3329.77 | 27-JAN-17:00 | 26.00 | 9.22 | 0.00 | 0.00 | 01-JAN-00:10 | 26.00 | 9.22 |
February | 0.113776E+10 | 3183.66 | 01-FEB-06:08 | 5.00 | 3.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.219080E+10 | 4310.14 | 27-MAR-05:03 | 2.52 | -0.8 | 0.00 | 0.00 | 01-MAR-00:10 | 2.52 | -0.8 |
April | 0.595789E+10 | 7044.22 | 25-APR-15:20 | 33.00 | 15.00 | 0.00 | 0.00 | 01-APR-00:10 | 33.00 | 15.00 |
May | 0.776701E+10 | 7672.61 | 08-MAY-16:00 | 34.00 | 13.77 | 0.00 | 0.00 | 01-MAY-00:10 | 34.00 | 13.77 |
June | 0.101724E+11 | 9638.34 | 26-JUN-05:02 | 22.17 | 10.13 | 0.00 | 0.00 | 01-JUN-00:10 | 22.17 | 10.13 |
July | 0.936587E+10 | 9663.86 | 31-JUL-05:02 | 25.83 | 15.57 | 0.00 | 0.00 | 01-JUL-00:10 | 25.83 | 15.57 |
August | 0.945419E+10 | 12812.67 | 28-AUG-05:13 | 28.67 | 19.85 | 0.00 | 0.00 | 01-AUG-00:10 | 28.67 | 19.85 |
September | 0.789798E+10 | 10573.04 | 05-SEP-05:15 | 21.63 | 18.84 | 0.00 | 0.00 | 01-SEP-00:10 | 21.63 | 18.84 |
October | 0.497491E+10 | 8845.45 | 02-OCT-05:15 | 25.67 | 16.91 | 0.00 | 0.00 | 01-OCT-00:10 | 25.67 | 16.91 |
November | 0.237000E+10 | 4619.41 | 02-NOV-16:00 | 26.00 | 15.13 | 0.00 | 0.00 | 01-NOV-00:10 | 26.00 | 15.13 |
December | 0.102966E+10 | 7311.35 | 06-DEC-06:01 | 0.67 | -4.3 | 0.00 | 0.00 | 01-DEC-00:10 | 0.67 | -4.3 |
Annual Sum or Average | 0.640484E+11 | 0.00 | ||||||||
Minimum of Months | 0.102966E+10 | 3183.66 | 0.67 | -4.3 | 0.00 | 0.00 | 0.67 | -4.3 | ||
Maximum of Months | 0.101724E+11 | 12812.67 | 34.00 | 19.85 | 0.00 | 0.00 | 34.00 | 19.85 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242422E+10 | 8574.41 | 31-JAN-16:00 | 29.00 | 10.73 | 0.00 | 0.00 | 01-JAN-00:10 | 29.00 | 10.73 |
February | 0.137376E+10 | 7726.42 | 23-FEB-14:50 | 18.00 | 10.42 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 10.42 |
March | 0.362260E+10 | 12062.91 | 16-MAR-15:20 | 28.80 | 13.79 | 0.00 | 0.00 | 01-MAR-00:10 | 28.80 | 13.79 |
April | 0.110112E+11 | 19394.92 | 14-APR-15:10 | 35.00 | 14.57 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 14.57 |
May | 0.142776E+11 | 19868.37 | 19-MAY-14:00 | 36.00 | 14.39 | 0.00 | 0.00 | 01-MAY-00:10 | 36.00 | 14.39 |
June | 0.200515E+11 | 24168.65 | 28-JUN-14:40 | 41.67 | 19.29 | 0.00 | 0.00 | 01-JUN-00:10 | 41.67 | 19.29 |
July | 0.176925E+11 | 22619.36 | 20-JUL-14:00 | 39.00 | 20.25 | 0.00 | 0.00 | 01-JUL-00:10 | 39.00 | 20.25 |
August | 0.172928E+11 | 22243.24 | 15-AUG-15:10 | 39.00 | 18.89 | 0.00 | 0.00 | 01-AUG-00:10 | 39.00 | 18.89 |
September | 0.129386E+11 | 19760.21 | 07-SEP-15:20 | 37.37 | 19.77 | 0.00 | 0.00 | 01-SEP-00:10 | 37.37 | 19.77 |
October | 0.702377E+10 | 17355.82 | 02-OCT-14:20 | 35.00 | 19.60 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.60 |
November | 0.285150E+10 | 11084.33 | 01-NOV-15:20 | 28.67 | 16.04 | 0.00 | 0.00 | 01-NOV-00:10 | 28.67 | 16.04 |
December | 0.105486E+10 | 6487.88 | 22-DEC-16:00 | 25.00 | 10.09 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 10.09 |
Annual Sum or Average | 0.111615E+12 | 0.00 | ||||||||
Minimum of Months | 0.105486E+10 | 6487.88 | 18.00 | 10.09 | 0.00 | 0.00 | 18.00 | 10.09 | ||
Maximum of Months | 0.200515E+11 | 24168.65 | 41.67 | 20.25 | 0.00 | 0.00 | 41.67 | 20.25 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414151E+10 | 2269.16 | 29-JAN-17:15 | 23.00 | 8.84 | 95230214.27 | 126.83 | 09-JAN-10:00 | 23.00 | 8.84 |
February | 0.823446E+10 | 4068.56 | 27-FEB-17:40 | 15.67 | 8.53 | 86398657.49 | 126.84 | 16-FEB-10:00 | 15.67 | 8.53 |
March | 0.144140E+11 | 7149.80 | 31-MAR-24:00 | 15.30 | 7.49 | 0.103237E+09 | 126.84 | 06-MAR-10:00 | 15.30 | 7.49 |
April | 0.185555E+11 | 7785.51 | 26-APR-18:50 | 19.33 | 9.57 | 99322857.61 | 159.69 | 24-APR-13:00 | 19.33 | 9.57 |
May | 0.471936E+10 | 3493.39 | 31-MAY-23:55 | 26.00 | 10.61 | 99233117.34 | 126.82 | 19-MAY-09:09 | 26.00 | 10.61 |
June | 0.954770E+10 | 5429.60 | 30-JUN-24:00 | 28.10 | 15.37 | 98957378.99 | 126.83 | 30-JUN-09:00 | 28.10 | 15.37 |
July | 0.148976E+11 | 7341.07 | 31-JUL-23:57 | 29.60 | 17.96 | 91883958.92 | 126.84 | 27-JUL-09:09 | 29.60 | 17.96 |
August | 0.196111E+11 | 7782.77 | 20-AUG-23:50 | 26.17 | 16.39 | 0.112105E+09 | 169.89 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.458685E+10 | 3492.33 | 30-SEP-24:00 | 25.20 | 15.49 | 91612397.87 | 126.85 | 01-SEP-09:00 | 25.20 | 15.49 |
October | 0.963715E+10 | 5321.31 | 31-OCT-24:00 | 17.10 | 9.96 | 95231184.19 | 126.85 | 03-OCT-09:00 | 17.10 | 9.96 |
November | 0.140766E+11 | 6268.13 | 26-NOV-16:53 | 18.00 | 8.58 | 94301954.55 | 126.84 | 13-NOV-10:09 | 18.00 | 8.58 |
December | 0.193696E+11 | 7940.85 | 28-DEC-17:00 | 18.60 | 7.88 | 92185077.12 | 135.84 | 22-DEC-16:00 | 18.60 | 7.88 |
Annual Sum or Average | 0.141791E+12 | 0.115970E+10 | ||||||||
Minimum of Months | 0.414151E+10 | 2269.16 | 15.30 | 7.49 | 86398657.49 | 126.82 | 15.30 | 7.49 | ||
Maximum of Months | 0.196111E+11 | 7940.85 | 29.60 | 17.96 | 0.112105E+09 | 169.89 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304665E+10 | 2061.23 | 24-JAN-17:00 | 24.00 | 10.79 | 95230207.77 | 126.83 | 09-JAN-10:00 | 24.00 | 10.79 |
February | 0.699125E+10 | 3810.85 | 27-FEB-17:40 | 15.67 | 8.53 | 86398559.28 | 126.84 | 16-FEB-10:00 | 15.67 | 8.53 |
March | 0.131340E+11 | 6696.05 | 31-MAR-23:40 | 15.33 | 7.15 | 0.103237E+09 | 126.83 | 06-MAR-10:00 | 15.33 | 7.15 |
April | 0.175603E+11 | 7420.90 | 26-APR-18:50 | 19.33 | 9.57 | 98233959.39 | 155.90 | 24-APR-13:00 | 19.33 | 9.57 |
May | 0.435302E+10 | 3404.56 | 31-MAY-23:55 | 26.00 | 10.61 | 99233117.44 | 126.82 | 26-MAY-09:50 | 26.00 | 10.61 |
June | 0.908428E+10 | 5222.19 | 30-JUN-24:00 | 28.10 | 15.37 | 98957379.66 | 126.83 | 30-JUN-09:00 | 28.10 | 15.37 |
July | 0.141506E+11 | 7013.90 | 31-JUL-23:57 | 29.60 | 17.96 | 91883937.55 | 126.83 | 14-JUL-09:09 | 29.60 | 17.96 |
August | 0.184517E+11 | 7274.42 | 20-AUG-20:52 | 29.00 | 16.20 | 0.110316E+09 | 164.74 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.419680E+10 | 3408.00 | 30-SEP-24:00 | 25.20 | 15.49 | 91611518.36 | 126.85 | 05-SEP-13:09 | 25.20 | 15.49 |
October | 0.877414E+10 | 4928.06 | 31-OCT-24:00 | 17.10 | 9.96 | 95231146.58 | 126.84 | 03-OCT-09:00 | 17.10 | 9.96 |
November | 0.127148E+11 | 5827.19 | 14-NOV-17:00 | 19.00 | 14.11 | 94301864.40 | 126.84 | 13-NOV-14:00 | 19.00 | 14.11 |
December | 0.173868E+11 | 7471.51 | 28-DEC-17:00 | 18.60 | 7.88 | 92033127.78 | 133.78 | 22-DEC-16:00 | 18.60 | 7.88 |
Annual Sum or Average | 0.129844E+12 | 0.115667E+10 | ||||||||
Minimum of Months | 0.304665E+10 | 2061.23 | 15.33 | 7.15 | 86398559.28 | 126.82 | 15.33 | 7.15 | ||
Maximum of Months | 0.184517E+11 | 7471.51 | 29.60 | 17.96 | 0.110316E+09 | 164.74 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216409E+10 | 2077.23 | 24-JAN-17:00 | 24.00 | 10.79 | 95099918.31 | 126.83 | 09-JAN-10:00 | 24.00 | 10.79 |
February | 0.597386E+10 | 3784.95 | 27-FEB-17:40 | 15.67 | 8.53 | 86398550.42 | 126.84 | 16-FEB-10:00 | 15.67 | 8.53 |
March | 0.124763E+11 | 6523.96 | 31-MAR-23:20 | 15.37 | 6.81 | 0.103237E+09 | 126.83 | 06-MAR-10:00 | 15.37 | 6.81 |
April | 0.175939E+11 | 7533.02 | 26-APR-18:30 | 20.00 | 9.88 | 97223852.71 | 155.75 | 24-APR-13:00 | 20.00 | 9.88 |
May | 0.438273E+10 | 3403.52 | 31-MAY-23:55 | 26.00 | 10.61 | 99233117.55 | 126.82 | 04-MAY-09:39 | 26.00 | 10.61 |
June | 0.924050E+10 | 5274.16 | 30-JUN-24:00 | 28.10 | 15.37 | 98957381.71 | 126.83 | 30-JUN-09:00 | 28.10 | 15.37 |
July | 0.143263E+11 | 7058.14 | 31-JUL-23:57 | 29.60 | 17.96 | 91884983.79 | 126.84 | 14-JUL-09:00 | 29.60 | 17.96 |
August | 0.186273E+11 | 7475.90 | 20-AUG-21:03 | 28.83 | 16.12 | 0.109183E+09 | 164.95 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.426440E+10 | 3436.68 | 30-SEP-24:00 | 25.20 | 15.49 | 91611852.07 | 126.85 | 05-SEP-13:09 | 25.20 | 15.49 |
October | 0.840363E+10 | 4740.24 | 31-OCT-23:40 | 16.87 | 9.55 | 95231171.27 | 126.84 | 03-OCT-09:00 | 16.87 | 9.55 |
November | 0.118700E+11 | 5847.14 | 21-NOV-17:00 | 24.00 | 10.76 | 94301923.86 | 126.84 | 13-NOV-14:00 | 24.00 | 10.76 |
December | 0.160235E+11 | 7433.67 | 28-DEC-17:00 | 18.60 | 7.88 | 91934076.93 | 130.43 | 22-DEC-16:00 | 18.60 | 7.88 |
Annual Sum or Average | 0.125346E+12 | 0.115430E+10 | ||||||||
Minimum of Months | 0.216409E+10 | 2077.23 | 15.37 | 6.81 | 86398550.42 | 126.82 | 15.37 | 6.81 | ||
Maximum of Months | 0.186273E+11 | 7533.02 | 29.60 | 17.96 | 0.109183E+09 | 164.95 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240106E+12 | 92349.85 | 17-JAN-17:00 | 24.00 | 9.10 | 0.206145E+10 | 2745.41 | 02-JAN-14:09 | 24.00 | 9.10 |
February | 0.435269E+12 | 182944.37 | 21-FEB-17:00 | 19.00 | 10.37 | 0.187024E+10 | 2746.75 | 17-FEB-14:00 | 19.00 | 10.37 |
March | 0.727234E+12 | 358012.76 | 31-MAR-24:00 | 15.30 | 7.49 | 0.223501E+10 | 2748.84 | 16-MAR-13:00 | 15.30 | 7.49 |
April | 0.934645E+12 | 380835.57 | 03-APR-21:01 | 22.83 | 9.11 | 0.248370E+10 | 4982.13 | 14-APR-13:00 | 34.00 | 14.07 |
May | 0.240612E+12 | 175605.43 | 31-MAY-24:00 | 26.00 | 10.61 | 0.214826E+10 | 2747.10 | 15-MAY-13:00 | 26.00 | 10.61 |
June | 0.469374E+12 | 267480.47 | 30-JUN-23:57 | 28.10 | 15.37 | 0.214272E+10 | 2748.03 | 22-JUN-09:09 | 28.10 | 15.37 |
July | 0.732400E+12 | 356506.24 | 31-JUL-23:13 | 30.33 | 18.19 | 0.200146E+10 | 3312.68 | 14-JUL-09:00 | 30.33 | 18.19 |
August | 0.963396E+12 | 386584.44 | 23-AUG-22:53 | 24.00 | 10.56 | 0.310100E+10 | 5027.92 | 23-AUG-13:09 | 24.00 | 10.56 |
September | 0.238418E+12 | 177154.08 | 30-SEP-24:00 | 25.20 | 15.49 | 0.198321E+10 | 2746.81 | 15-SEP-09:09 | 25.20 | 15.49 |
October | 0.489388E+12 | 269011.04 | 31-OCT-24:00 | 17.10 | 9.96 | 0.206169E+10 | 2748.14 | 16-OCT-13:00 | 17.10 | 9.96 |
November | 0.710151E+12 | 276954.62 | 20-NOV-17:00 | 26.00 | 12.00 | 0.204173E+10 | 2751.10 | 13-NOV-10:09 | 26.00 | 12.00 |
December | 0.977947E+12 | 372186.93 | 25-DEC-16:41 | 24.33 | 11.32 | 0.199499E+10 | 3133.56 | 22-DEC-14:00 | 24.33 | 11.32 |
Annual Sum or Average | 0.715894E+13 | 0.261255E+11 | ||||||||
Minimum of Months | 0.238418E+12 | 92349.85 | 15.30 | 7.49 | 0.187024E+10 | 2745.41 | 15.30 | 7.49 | ||
Maximum of Months | 0.977947E+12 | 386584.44 | 30.33 | 18.19 | 0.310100E+10 | 5027.92 | 34.00 | 18.19 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345531E+09 | 11480.72 | 24-JAN-05:17 | 13.33 |
February | 0.114212E+09 | 11457.45 | 23-FEB-05:15 | 8.67 |
March | 0.109796E+09 | 12834.19 | 18-MAR-16:01 | 27.20 |
April | 0.358108E+09 | 19795.75 | 29-APR-16:01 | 32.67 |
May | 0.364403E+09 | 22668.93 | 20-MAY-16:01 | 34.83 |
June | 0.414399E+09 | 29562.88 | 17-JUN-16:02 | 40.50 |
July | 0.606171E+09 | 26754.97 | 22-JUL-16:01 | 38.00 |
August | 0.429520E+09 | 30163.10 | 26-AUG-16:01 | 40.83 |
September | 0.595242E+09 | 21939.16 | 23-SEP-16:01 | 34.30 |
October | 0.430570E+09 | 17556.14 | 14-OCT-16:01 | 31.00 |
November | 0.292775E+09 | 11064.69 | 01-NOV-04:57 | 20.00 |
December | 0.263541E+09 | 12048.59 | 03-DEC-15:12 | 21.00 |
Annual Sum or Average | 0.432427E+10 | |||
Minimum of Months | 0.109796E+09 | 11064.69 | 8.67 | |
Maximum of Months | 0.606171E+09 | 30163.10 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234595E+09 | 67034.84 | 02-JAN-05:11 | 4.00 |
February | 20012395.13 | 59420.34 | 13-FEB-06:03 | 8.00 |
March | 6468118.00 | 43120.79 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 7686140.74 | 51240.94 | 24-NOV-06:03 | 3.17 |
December | 94282657.12 | 62254.29 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.363045E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.52 | |
Maximum of Months | 0.234595E+09 | 67034.84 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 225126.21 | 2626.47 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 225126.21 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 225126.21 | 2626.47 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 58849591.67 | 13838.04 | 02-JAN-05:11 | 4.00 |
February | 10857130.59 | 8416.82 | 03-FEB-06:02 | 6.83 |
March | 28685826.61 | 12903.71 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 17431990.92 | 12216.02 | 24-NOV-06:03 | 3.17 |
December | 0.192557E+09 | 13258.20 | 07-DEC-05:01 | -1.1 |
Annual Sum or Average | 0.308381E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.192557E+09 | 13838.04 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22948094.39 | 11717.02 | 02-JAN-05:11 | 4.00 |
February | 2737005.38 | 5687.94 | 13-FEB-06:03 | 8.00 |
March | 7211623.46 | 8012.33 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 4616443.52 | 8162.62 | 24-NOV-06:03 | 3.17 |
December | 75282466.87 | 11284.82 | 07-DEC-05:01 | -1.1 |
Annual Sum or Average | 0.112796E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 75282466.87 | 11717.02 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6561180.29 | 12309.42 | 02-JAN-06:03 | 4.33 |
February | 2862509.95 | 7393.08 | 13-FEB-06:03 | 8.00 |
March | 3956493.25 | 10407.65 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 376042.79 | 2506.95 | 24-NOV-06:03 | 3.17 |
December | 28086606.34 | 13878.41 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 41842832.61 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 28086606.34 | 13878.41 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9766344.70 | 8365.44 | 02-JAN-06:03 | 4.33 |
February | 670115.72 | 2652.12 | 13-FEB-06:03 | 8.00 |
March | 779704.00 | 4728.04 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 1375945.65 | 5938.77 | 24-NOV-06:03 | 3.17 |
December | 42677287.00 | 10067.51 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 55269397.07 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 42677287.00 | 10067.51 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511390E+09 | 17622.08 | 02-JAN-05:11 | 4.00 |
February | 0.404352E+09 | 15990.18 | 13-FEB-05:11 | 8.00 |
March | 0.272978E+09 | 16579.41 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 40671639.58 | 14349.37 | 26-OCT-05:02 | 7.17 |
November | 0.311626E+09 | 16785.64 | 24-NOV-05:11 | 3.67 |
December | 0.121247E+10 | 17544.53 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.275348E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.121247E+10 | 17622.08 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197345E+09 | 15756.87 | 02-JAN-05:11 | 4.00 |
February | 0.161348E+09 | 14097.34 | 13-FEB-05:11 | 8.00 |
March | 0.111958E+09 | 14283.72 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 12458711.56 | 9671.21 | 26-OCT-05:02 | 7.17 |
November | 0.113104E+09 | 14738.38 | 24-NOV-05:11 | 3.67 |
December | 0.507905E+09 | 15461.31 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.110412E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.507905E+09 | 15756.87 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98382799.71 | 17983.60 | 02-JAN-05:11 | 4.00 |
February | 0.138413E+09 | 17435.08 | 13-FEB-05:11 | 8.00 |
March | 0.136918E+09 | 16956.91 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 4206499.09 | 6483.74 | 26-OCT-05:02 | 7.17 |
November | 64409358.89 | 16784.12 | 24-NOV-05:11 | 3.67 |
December | 0.424132E+09 | 17666.19 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.866462E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.424132E+09 | 17983.60 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 94560222.23 | 15224.29 | 02-JAN-05:11 | 4.00 |
February | 90244716.29 | 13617.56 | 13-FEB-05:11 | 8.00 |
March | 50957321.74 | 13520.39 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 2220810.58 | 4506.69 | 26-OCT-05:02 | 7.17 |
November | 54972830.83 | 14035.83 | 24-NOV-05:11 | 3.67 |
December | 0.368021E+09 | 14989.32 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.660977E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.368021E+09 | 15224.29 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108086E+09 | 8361.41 | 29-JAN-16:22 | 24.50 |
February | 76987569.43 | 9218.00 | 13-FEB-05:11 | 8.00 |
March | 93106914.35 | 9082.76 | 27-MAR-04:11 | 2.37 |
April | 0.107292E+09 | 10752.99 | 23-APR-15:41 | 33.25 |
May | 69576910.04 | 8837.77 | 07-MAY-15:41 | 35.83 |
June | 52586428.24 | 8572.95 | 25-JUN-16:31 | 38.00 |
July | 77087589.22 | 9184.09 | 30-JUL-16:21 | 38.00 |
August | 95016740.13 | 9203.88 | 27-AUG-15:41 | 40.00 |
September | 58187279.18 | 7714.02 | 10-SEP-14:01 | 35.18 |
October | 92483828.22 | 8398.70 | 15-OCT-14:01 | 31.00 |
November | 0.130956E+09 | 9209.28 | 24-NOV-05:11 | 3.67 |
December | 0.168585E+09 | 10730.75 | 11-DEC-05:11 | 8.33 |
Annual Sum or Average | 0.112995E+10 | |||
Minimum of Months | 52586428.24 | 7714.02 | 2.37 | |
Maximum of Months | 0.168585E+09 | 10752.99 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334017E+09 | 7989.79 | 01-JAN-13:33 | 14.17 |
February | 0.129325E+09 | 6192.75 | 14-FEB-06:02 | 7.83 |
March | 64694194.10 | 7936.06 | 26-MAR-16:01 | 18.30 |
April | 62176280.95 | 9157.64 | 30-APR-15:51 | 33.00 |
May | 59238549.45 | 9287.68 | 07-MAY-15:41 | 35.83 |
June | 58235657.91 | 8826.02 | 04-JUN-16:41 | 38.00 |
July | 73512636.37 | 9326.46 | 30-JUL-16:11 | 38.00 |
August | 52717249.60 | 9065.39 | 27-AUG-15:41 | 40.00 |
September | 48724971.06 | 7981.96 | 10-SEP-14:01 | 35.18 |
October | 63662675.90 | 7762.50 | 15-OCT-15:32 | 31.00 |
November | 69429358.84 | 7417.06 | 19-NOV-15:32 | 27.00 |
December | 0.307945E+09 | 7504.69 | 25-DEC-16:32 | 24.67 |
Annual Sum or Average | 0.132368E+10 | |||
Minimum of Months | 48724971.06 | 6192.75 | 7.83 | |
Maximum of Months | 0.334017E+09 | 9326.46 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175548E+10 | 17586.12 | 02-JAN-06:03 | 4.33 |
February | 0.145718E+10 | 9011.32 | 13-FEB-06:03 | 8.00 |
March | 0.133369E+10 | 12657.49 | 21-MAR-05:03 | 13.53 |
April | 0.402951E+09 | 13589.05 | 27-APR-05:03 | 12.00 |
May | 0.164702E+09 | 12227.14 | 01-MAY-04:12 | 12.33 |
June | 40923042.58 | 11634.08 | 12-JUN-04:12 | 20.00 |
July | 31112667.66 | 12621.14 | 03-JUL-04:11 | 20.67 |
August | 30347356.73 | 8683.62 | 25-AUG-04:12 | 22.00 |
September | 48720311.13 | 10580.54 | 11-SEP-04:11 | 22.37 |
October | 0.721551E+09 | 12494.69 | 18-OCT-05:03 | 15.83 |
November | 0.119634E+10 | 11018.84 | 02-NOV-05:03 | 16.00 |
December | 0.254148E+10 | 15625.54 | 18-DEC-06:03 | 3.83 |
Annual Sum or Average | 0.972448E+10 | |||
Minimum of Months | 30347356.73 | 8683.62 | 3.83 | |
Maximum of Months | 0.254148E+10 | 17586.12 | 22.37 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6754451.68 | 263.98 | 01-JAN-08:30 | 3.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 6754451.68 | |||
Minimum of Months | 0.00 | 0.00 | 3.10 | |
Maximum of Months | 6754451.68 | 263.98 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73102594.11 | 583.89 | 01-JAN-02:65 | 4.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 73102594.11 | |||
Minimum of Months | 0.00 | 0.00 | 4.45 | |
Maximum of Months | 73102594.11 | 583.89 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.960530E+09 | 1483.93 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.850741E+09 | 1384.14 | 03-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.945721E+09 | 1291.50 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.815169E+09 | 888.77 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.861333E+09 | 852.41 | 26-MAY-08:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.839595E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.795360E+09 | 875.04 | 13-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.911639E+09 | 1305.75 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.833039E+09 | 1137.97 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.913581E+09 | 1424.65 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.937834E+09 | 1662.56 | 28-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.948426E+09 | 1662.56 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106130E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.795360E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.960530E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596966E+09 | 947.23 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.535436E+09 | 857.16 | 10-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.603834E+09 | 589.31 | 08-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.522248E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.557115E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.544036E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.516111E+09 | 572.03 | 13-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.586256E+09 | 816.23 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.533831E+09 | 568.78 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.572478E+09 | 685.59 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.589729E+09 | 1071.42 | 28-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.592213E+09 | 1071.42 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.675025E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.516111E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.603834E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.911008E+09 | 1447.58 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.821898E+09 | 1355.67 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.933626E+09 | 1237.32 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.818346E+09 | 896.29 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.870419E+09 | 852.41 | 26-MAY-08:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.850874E+09 | 839.02 | 27-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.806485E+09 | 880.24 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.916923E+09 | 1312.97 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.830153E+09 | 906.35 | 19-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.878990E+09 | 1236.87 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.901388E+09 | 1662.60 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.901245E+09 | 1662.60 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104414E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.806485E+09 | 839.02 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.933626E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.606536E+09 | 968.51 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.541169E+09 | 897.70 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.607010E+09 | 905.19 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.525768E+09 | 702.14 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.559137E+09 | 569.32 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.545430E+09 | 543.10 | 27-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.517353E+09 | 570.33 | 24-JUL-08:20 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.589490E+09 | 856.93 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.536910E+09 | 805.87 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.580099E+09 | 932.09 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.593398E+09 | 1071.42 | 28-NOV-16:30 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.598140E+09 | 1071.42 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.680044E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.517353E+09 | 543.10 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.607010E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.956508E+09 | 1480.95 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.847726E+09 | 1379.52 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.943341E+09 | 1286.17 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.814286E+09 | 879.57 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.861125E+09 | 842.61 | 26-MAY-08:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.839374E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.794857E+09 | 866.52 | 13-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.910329E+09 | 1301.67 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.831871E+09 | 1130.38 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.909964E+09 | 1420.76 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.934337E+09 | 1662.56 | 28-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.944273E+09 | 1662.56 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.105880E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.794857E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.956508E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596262E+09 | 944.01 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.534387E+09 | 851.98 | 10-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.603301E+09 | 585.39 | 08-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.522101E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.556862E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.543673E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.515475E+09 | 567.16 | 13-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.585501E+09 | 810.47 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.533458E+09 | 563.69 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.571481E+09 | 671.44 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.588833E+09 | 1071.42 | 28-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.591086E+09 | 1071.42 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.674242E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.515475E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.603301E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.910792E+09 | 1445.32 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.821194E+09 | 1352.22 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.932693E+09 | 1231.58 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.817506E+09 | 887.78 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.869677E+09 | 842.61 | 26-MAY-08:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.849956E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.805263E+09 | 870.46 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.915522E+09 | 1308.95 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.829257E+09 | 899.61 | 29-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.876999E+09 | 1182.61 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.900557E+09 | 1662.60 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.900950E+09 | 1662.60 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104304E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.805263E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.932693E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.604826E+09 | 966.14 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.539646E+09 | 893.17 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.605903E+09 | 900.60 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.525321E+09 | 693.99 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.558634E+09 | 564.31 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.545020E+09 | 509.78 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.516639E+09 | 565.16 | 24-JUL-08:20 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.588567E+09 | 851.30 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.536202E+09 | 798.69 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.578763E+09 | 929.22 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.592169E+09 | 1071.42 | 28-NOV-16:30 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.596707E+09 | 1071.42 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.678840E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.516639E+09 | 509.78 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.605903E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.956467E+09 | 1480.71 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.847675E+09 | 1378.94 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.943221E+09 | 1285.55 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.814276E+09 | 879.40 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.861120E+09 | 842.22 | 26-MAY-08:30 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.839373E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.794835E+09 | 866.18 | 13-JUL-15:00 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.910303E+09 | 1300.93 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.831805E+09 | 1129.45 | 29-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.909899E+09 | 1420.64 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.934294E+09 | 1662.56 | 28-NOV-16:30 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.944194E+09 | 1662.56 | 01-DEC-16:30 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.105875E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.794835E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.956467E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596252E+09 | 943.75 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.534349E+09 | 851.56 | 10-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.603278E+09 | 585.26 | 08-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.522092E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.556858E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.543663E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.515425E+09 | 566.96 | 13-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.585491E+09 | 809.96 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.533443E+09 | 563.52 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.571445E+09 | 671.36 | 31-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.588810E+09 | 1071.42 | 28-NOV-16:30 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.591073E+09 | 1071.42 | 01-DEC-16:30 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.674218E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.515425E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.603278E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.910758E+09 | 1444.89 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.821173E+09 | 1351.59 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.932663E+09 | 1230.90 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.817468E+09 | 887.62 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.869664E+09 | 842.22 | 26-MAY-08:30 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.849944E+09 | 791.06 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.805239E+09 | 870.31 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.915486E+09 | 1308.21 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.829239E+09 | 899.40 | 29-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.876992E+09 | 1182.19 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.900548E+09 | 1662.60 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.900943E+09 | 1662.60 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104301E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.805239E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.932663E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.604762E+09 | 966.01 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.539622E+09 | 892.81 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.605886E+09 | 900.31 | 21-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.525315E+09 | 693.91 | 04-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.558611E+09 | 564.12 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.545021E+09 | 509.78 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.516636E+09 | 565.00 | 24-JUL-08:20 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.588548E+09 | 850.85 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.536170E+09 | 798.21 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.578752E+09 | 929.08 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.592155E+09 | 1071.42 | 28-NOV-16:30 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.596642E+09 | 1071.42 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.678812E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.516636E+09 | 509.78 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.605886E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.960530E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1024404.48 | 0.335734E+09 |
February | 0.136985E+10 | 0.850741E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268422E+09 |
March | 0.163685E+10 | 0.945721E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2848744.38 | 0.342667E+09 |
April | 0.145243E+10 | 0.815169E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51089651.87 | 0.105764E+09 |
May | 0.157338E+10 | 0.861333E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100148E+09 | 68316089.63 |
June | 0.156900E+10 | 0.839595E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185300E+09 | 15440727.64 |
July | 0.145680E+10 | 0.795360E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183779E+09 | 12456947.41 |
August | 0.163685E+10 | 0.911639E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127642E+09 | 19658835.66 |
September | 0.145243E+10 | 0.833039E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97146646.75 | 44114248.50 |
October | 0.150991E+10 | 0.913581E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34136345.21 | 0.172700E+09 |
November | 0.149516E+10 | 0.937834E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2713995.98 | 0.306141E+09 |
December | 0.145680E+10 | 0.948426E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187435.93 | 0.329574E+09 |
Annual Sum or Average | 0.181194E+11 | 0.106130E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.786016E+09 | 0.202099E+10 |
Minimum of Months | 0.136985E+10 | 0.795360E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12456947.41 |
Maximum of Months | 0.163685E+10 | 0.960530E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185300E+09 | 0.342667E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.596966E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 644770.16 | 0.230156E+09 |
February | 0.882782E+09 | 0.535436E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179764E+09 |
March | 0.105485E+10 | 0.603834E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1838343.93 | 0.228632E+09 |
April | 0.936002E+09 | 0.522248E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33575010.96 | 70943105.62 |
May | 0.101394E+10 | 0.557115E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64670988.30 | 47321892.74 |
June | 0.101113E+10 | 0.544036E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123315E+09 | 10341726.66 |
July | 0.938820E+09 | 0.516111E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123003E+09 | 8045736.85 |
August | 0.105485E+10 | 0.586256E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86562877.07 | 11795100.63 |
September | 0.936002E+09 | 0.533831E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63440295.09 | 29906269.65 |
October | 0.973041E+09 | 0.572478E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21705856.83 | 0.116831E+09 |
November | 0.963541E+09 | 0.589729E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1447707.73 | 0.204573E+09 |
December | 0.938820E+09 | 0.592213E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87480.51 | 0.218555E+09 |
Annual Sum or Average | 0.116768E+11 | 0.675025E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520291E+09 | 0.135686E+10 |
Minimum of Months | 0.882782E+09 | 0.516111E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8045736.85 |
Maximum of Months | 0.105485E+10 | 0.603834E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123315E+09 | 0.230156E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.911008E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 869231.93 | 0.364138E+09 |
February | 0.136988E+10 | 0.821898E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275433E+09 |
March | 0.163688E+10 | 0.933626E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2618527.60 | 0.350783E+09 |
April | 0.145246E+10 | 0.818346E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48359880.10 | 0.110222E+09 |
May | 0.157341E+10 | 0.870419E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98844299.12 | 68535617.86 |
June | 0.156904E+10 | 0.850874E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186845E+09 | 14981740.93 |
July | 0.145684E+10 | 0.806485E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183757E+09 | 12261161.78 |
August | 0.163688E+10 | 0.916923E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125814E+09 | 20244179.12 |
September | 0.145246E+10 | 0.830153E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92161225.22 | 48305067.75 |
October | 0.150994E+10 | 0.878990E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30595612.33 | 0.185775E+09 |
November | 0.149520E+10 | 0.901388E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1566349.42 | 0.324795E+09 |
December | 0.145684E+10 | 0.901245E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72036.38 | 0.345606E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104414E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771503E+09 | 0.212108E+10 |
Minimum of Months | 0.136988E+10 | 0.806485E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12261161.78 |
Maximum of Months | 0.163688E+10 | 0.933626E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186845E+09 | 0.364138E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.606536E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 644141.81 | 0.249244E+09 |
February | 0.882782E+09 | 0.541169E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199997E+09 |
March | 0.105485E+10 | 0.607010E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1729587.86 | 0.262831E+09 |
April | 0.936002E+09 | 0.525768E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29800906.59 | 93022675.38 |
May | 0.101394E+10 | 0.559137E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61015756.20 | 56812928.83 |
June | 0.101113E+10 | 0.545430E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115800E+09 | 15170618.55 |
July | 0.938820E+09 | 0.517353E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112697E+09 | 14547081.11 |
August | 0.105485E+10 | 0.589490E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76980658.20 | 23658918.97 |
September | 0.936002E+09 | 0.536910E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58351083.86 | 39113462.48 |
October | 0.973041E+09 | 0.580099E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20092362.04 | 0.136518E+09 |
November | 0.963541E+09 | 0.593398E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1151206.72 | 0.237901E+09 |
December | 0.938820E+09 | 0.598140E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58655.89 | 0.253334E+09 |
Annual Sum or Average | 0.116768E+11 | 0.680044E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478321E+09 | 0.158215E+10 |
Minimum of Months | 0.882782E+09 | 0.517353E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14547081.11 |
Maximum of Months | 0.105485E+10 | 0.607010E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115800E+09 | 0.262831E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.956508E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5410054.47 | 0.672383E+09 |
February | 0.136985E+10 | 0.847726E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547224E+09 |
March | 0.163685E+10 | 0.943341E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6948606.21 | 0.713765E+09 |
April | 0.145243E+10 | 0.814286E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125004E+09 | 0.242323E+09 |
May | 0.157338E+10 | 0.861125E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230339E+09 | 0.156967E+09 |
June | 0.156900E+10 | 0.839374E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422873E+09 | 44136345.77 |
July | 0.145680E+10 | 0.794857E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417722E+09 | 38240129.51 |
August | 0.163685E+10 | 0.910329E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295870E+09 | 53138504.30 |
September | 0.145243E+10 | 0.831871E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216409E+09 | 0.104342E+09 |
October | 0.150991E+10 | 0.909964E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83150250.04 | 0.364805E+09 |
November | 0.149516E+10 | 0.934337E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10415561.78 | 0.616656E+09 |
December | 0.145680E+10 | 0.944273E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2478921.96 | 0.652128E+09 |
Annual Sum or Average | 0.181194E+11 | 0.105880E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181662E+10 | 0.420611E+10 |
Minimum of Months | 0.136985E+10 | 0.794857E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38240129.51 |
Maximum of Months | 0.163685E+10 | 0.956508E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422873E+09 | 0.713765E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.596262E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1259619.60 | 0.487042E+09 |
February | 0.649041E+09 | 0.534387E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389796E+09 |
March | 0.773965E+09 | 0.603301E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3685935.14 | 0.508661E+09 |
April | 0.688021E+09 | 0.522101E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73928407.39 | 0.180140E+09 |
May | 0.744847E+09 | 0.556862E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144401E+09 | 0.114453E+09 |
June | 0.742030E+09 | 0.543673E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276136E+09 | 31972344.40 |
July | 0.690839E+09 | 0.515475E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270660E+09 | 28551429.30 |
August | 0.773965E+09 | 0.585501E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188236E+09 | 40627770.93 |
September | 0.688021E+09 | 0.533458E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137075E+09 | 76701046.59 |
October | 0.715730E+09 | 0.571481E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47839251.00 | 0.265144E+09 |
November | 0.708685E+09 | 0.588833E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3437854.48 | 0.442037E+09 |
December | 0.690839E+09 | 0.591086E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 470429.48 | 0.464930E+09 |
Annual Sum or Average | 0.858171E+10 | 0.674242E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114713E+10 | 0.303006E+10 |
Minimum of Months | 0.649041E+09 | 0.515475E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28551429.30 |
Maximum of Months | 0.773965E+09 | 0.603301E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276136E+09 | 0.508661E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.910792E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1569631.18 | 0.823977E+09 |
February | 0.136988E+10 | 0.821194E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615943E+09 |
March | 0.163688E+10 | 0.932693E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5782888.79 | 0.780960E+09 |
April | 0.145246E+10 | 0.817506E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111642E+09 | 0.262731E+09 |
May | 0.157341E+10 | 0.869677E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226544E+09 | 0.159677E+09 |
June | 0.156904E+10 | 0.849956E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427375E+09 | 42445338.44 |
July | 0.145684E+10 | 0.805263E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418007E+09 | 37602876.71 |
August | 0.163688E+10 | 0.915522E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288568E+09 | 57063058.35 |
September | 0.145246E+10 | 0.829257E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204233E+09 | 0.119162E+09 |
October | 0.150994E+10 | 0.876999E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68528367.57 | 0.426581E+09 |
November | 0.149520E+10 | 0.900557E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3263231.24 | 0.726593E+09 |
December | 0.145684E+10 | 0.900950E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 132909.06 | 0.769363E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104304E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175565E+10 | 0.482210E+10 |
Minimum of Months | 0.136988E+10 | 0.805263E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37602876.71 |
Maximum of Months | 0.163688E+10 | 0.932693E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427375E+09 | 0.823977E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.604826E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1615772.07 | 0.506852E+09 |
February | 0.882782E+09 | 0.539646E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398226E+09 |
March | 0.105485E+10 | 0.605903E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3828303.71 | 0.525291E+09 |
April | 0.936002E+09 | 0.525321E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70365291.16 | 0.196107E+09 |
May | 0.101394E+10 | 0.558634E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141539E+09 | 0.124716E+09 |
June | 0.101113E+10 | 0.545020E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269753E+09 | 36915866.33 |
July | 0.938820E+09 | 0.516639E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263277E+09 | 33230991.18 |
August | 0.105485E+10 | 0.588567E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182971E+09 | 45803333.31 |
September | 0.936002E+09 | 0.536202E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134268E+09 | 83409475.34 |
October | 0.973041E+09 | 0.578763E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47935260.23 | 0.277218E+09 |
November | 0.963541E+09 | 0.592169E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3577248.68 | 0.461144E+09 |
December | 0.938820E+09 | 0.596707E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 221652.92 | 0.479636E+09 |
Annual Sum or Average | 0.116768E+11 | 0.678840E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111935E+10 | 0.316855E+10 |
Minimum of Months | 0.882782E+09 | 0.516639E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33230991.18 |
Maximum of Months | 0.105485E+10 | 0.605903E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269753E+09 | 0.525291E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.956467E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9957052.40 | 0.746035E+09 |
February | 0.136985E+10 | 0.847675E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608029E+09 |
March | 0.163685E+10 | 0.943221E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7994853.29 | 0.823553E+09 |
April | 0.145243E+10 | 0.814276E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144659E+09 | 0.295565E+09 |
May | 0.157338E+10 | 0.861120E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273980E+09 | 0.195075E+09 |
June | 0.156900E+10 | 0.839373E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512328E+09 | 57151464.55 |
July | 0.145680E+10 | 0.794835E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501251E+09 | 50061461.47 |
August | 0.163685E+10 | 0.910303E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355227E+09 | 67823398.02 |
September | 0.145243E+10 | 0.831805E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258811E+09 | 0.133753E+09 |
October | 0.150991E+10 | 0.909899E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100011E+09 | 0.424825E+09 |
November | 0.149516E+10 | 0.934294E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15788896.37 | 0.689121E+09 |
December | 0.145680E+10 | 0.944194E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5711295.45 | 0.723199E+09 |
Annual Sum or Average | 0.181194E+11 | 0.105875E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218572E+10 | 0.481419E+10 |
Minimum of Months | 0.136985E+10 | 0.794835E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50061461.47 |
Maximum of Months | 0.163685E+10 | 0.956467E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512328E+09 | 0.823553E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.596252E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2307211.48 | 0.544996E+09 |
February | 0.882782E+09 | 0.534349E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438547E+09 |
March | 0.105485E+10 | 0.603278E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4671670.87 | 0.593278E+09 |
April | 0.936002E+09 | 0.522092E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89058823.81 | 0.221667E+09 |
May | 0.101394E+10 | 0.556858E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175055E+09 | 0.142576E+09 |
June | 0.101113E+10 | 0.543663E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337135E+09 | 41254943.63 |
July | 0.938820E+09 | 0.515425E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328151E+09 | 37094056.31 |
August | 0.105485E+10 | 0.585491E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228645E+09 | 51716579.13 |
September | 0.936002E+09 | 0.533443E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166454E+09 | 97800552.88 |
October | 0.973041E+09 | 0.571445E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58243584.31 | 0.312784E+09 |
November | 0.963541E+09 | 0.588810E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5257024.78 | 0.498433E+09 |
December | 0.938820E+09 | 0.591073E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1261864.31 | 0.516532E+09 |
Annual Sum or Average | 0.116768E+11 | 0.674218E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139624E+10 | 0.349668E+10 |
Minimum of Months | 0.882782E+09 | 0.515425E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37094056.31 |
Maximum of Months | 0.105485E+10 | 0.603278E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337135E+09 | 0.593278E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.910758E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2293830.23 | 0.945452E+09 |
February | 0.136988E+10 | 0.821173E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.701012E+09 |
March | 0.163688E+10 | 0.932663E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6738531.26 | 0.916371E+09 |
April | 0.145246E+10 | 0.817468E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132651E+09 | 0.322067E+09 |
May | 0.157341E+10 | 0.869664E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270817E+09 | 0.198196E+09 |
June | 0.156904E+10 | 0.849944E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516531E+09 | 54991500.72 |
July | 0.145684E+10 | 0.805239E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501611E+09 | 49233601.10 |
August | 0.163688E+10 | 0.915486E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347668E+09 | 72891462.50 |
September | 0.145246E+10 | 0.829239E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246285E+09 | 0.152196E+09 |
October | 0.150994E+10 | 0.876992E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82976335.26 | 0.507678E+09 |
November | 0.149520E+10 | 0.900548E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4216364.22 | 0.838811E+09 |
December | 0.145684E+10 | 0.900943E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 192424.03 | 0.879606E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104301E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211198E+10 | 0.563850E+10 |
Minimum of Months | 0.136988E+10 | 0.805239E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49233601.10 |
Maximum of Months | 0.163688E+10 | 0.932663E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516531E+09 | 0.945452E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.604762E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2471248.27 | 0.577954E+09 |
February | 0.882782E+09 | 0.539622E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455224E+09 |
March | 0.105485E+10 | 0.605886E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4481042.87 | 0.618681E+09 |
April | 0.936002E+09 | 0.525315E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84762079.29 | 0.240044E+09 |
May | 0.101394E+10 | 0.558611E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171332E+09 | 0.154694E+09 |
June | 0.101113E+10 | 0.545021E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328952E+09 | 46934425.17 |
July | 0.938820E+09 | 0.516636E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319827E+09 | 42423215.77 |
August | 0.105485E+10 | 0.588548E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222129E+09 | 57848779.16 |
September | 0.936002E+09 | 0.536170E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162424E+09 | 0.105805E+09 |
October | 0.973041E+09 | 0.578752E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57905018.65 | 0.329383E+09 |
November | 0.963541E+09 | 0.592155E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5038596.68 | 0.531119E+09 |
December | 0.938820E+09 | 0.596642E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 531066.20 | 0.546487E+09 |
Annual Sum or Average | 0.116768E+11 | 0.678812E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135985E+10 | 0.370660E+10 |
Minimum of Months | 0.882782E+09 | 0.516636E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42423215.77 |
Maximum of Months | 0.105485E+10 | 0.605886E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328952E+09 | 0.618681E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1181345.54 | 0.752196E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585185E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3985094.40 | 0.746166E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93800948.58 | 0.242776E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188686E+09 | 0.149353E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355442E+09 | 38218355.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353362E+09 | 32690949.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236777E+09 | 51853127.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178637E+09 | 95252727.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59856086.62 | 0.384032E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3127719.98 | 0.675082E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79701.86 | 0.725147E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147493E+10 | 0.447795E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32690949.75 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355442E+09 | 0.752196E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2378891.79 | 0.126363E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100089E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7935774.80 | 0.128440E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177477E+09 | 0.427057E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343436E+09 | 0.264225E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639863E+09 | 70988099.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644011E+09 | 59616961.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441015E+09 | 90987032.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320629E+09 | 0.169438E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112034E+09 | 0.664036E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8351035.37 | 0.114637E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883099.56 | 0.122017E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269801E+10 | 0.766180E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59616961.43 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644011E+09 | 0.128440E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2037516.40 | 0.124245E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100786E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4881148.38 | 0.134044E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154417E+09 | 0.461046E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328819E+09 | 0.273697E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681481E+09 | 75817733.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653615E+09 | 67992835.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461325E+09 | 98392306.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326451E+09 | 0.193186E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109607E+09 | 0.687498E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7591022.91 | 0.113928E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1003496.19 | 0.118093E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273123E+10 | 0.776860E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67992835.77 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681481E+09 | 0.134044E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1483.93 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 | 31-JAN-14:00 | 726.58 | 01-JAN-00:55 |
February | 2010.79 | 01-FEB-10:09 | 1384.14 | 03-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 764.10 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1291.50 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.63 | 18-MAR-17:10 | 663.19 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 888.77 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.52 | 30-APR-15:43 | 323.97 | 21-APR-04:53 |
May | 2010.79 | 01-MAY-09:09 | 852.41 | 26-MAY-08:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.59 | 20-MAY-17:30 | 252.75 | 23-MAY-04:53 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 571.78 | 17-JUN-17:10 | 125.86 | 13-JUN-04:10 |
July | 2010.79 | 03-JUL-09:09 | 875.04 | 13-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 722.15 | 22-JUL-18:00 | 183.09 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 1305.75 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.76 | 13-AUG-16:00 | 306.62 | 05-AUG-17:40 |
September | 2010.79 | 01-SEP-09:09 | 1137.97 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.08 | 17-SEP-12:38 | 232.91 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1424.65 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.67 | 01-OCT-14:40 | 648.25 | 22-OCT-14:00 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 28-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.26 | 19-NOV-15:00 | 660.24 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 25-DEC-16:00 | 552.27 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.86 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 722.15 | 764.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 947.23 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 31-JAN-14:00 | 490.53 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 857.16 | 10-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 508.96 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 589.31 | 08-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.96 | 18-MAR-17:10 | 436.59 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.03 | 30-APR-15:43 | 311.31 | 16-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.82 | 20-MAY-17:30 | 168.23 | 23-MAY-04:53 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.13 | 17-JUN-17:10 | 92.65 | 11-JUN-06:50 |
July | 1295.83 | 03-JUL-09:09 | 572.03 | 13-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 490.20 | 22-JUL-18:00 | 117.54 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 816.23 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.56 | 13-AUG-15:55 | 197.65 | 05-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 568.78 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.26 | 17-SEP-12:38 | 150.42 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 685.59 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.61 | 01-OCT-14:28 | 452.67 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 28-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 | 19-NOV-15:00 | 432.09 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 | 25-DEC-16:00 | 361.93 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.65 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 490.20 | 508.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1447.58 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 31-JAN-15:00 | 733.68 | 01-JAN-00:55 |
February | 2010.83 | 01-FEB-10:09 | 1355.67 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 812.85 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1237.32 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.11 | 15-MAR-13:00 | 660.80 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 896.29 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.31 | 30-APR-15:43 | 327.88 | 16-APR-09:00 |
May | 2010.83 | 01-MAY-09:09 | 852.41 | 26-MAY-08:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.50 | 20-MAY-17:30 | 250.52 | 01-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 839.02 | 27-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 572.13 | 17-JUN-17:10 | 124.78 | 13-JUN-04:10 |
July | 2010.83 | 03-JUL-09:09 | 880.24 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 734.94 | 22-JUL-18:00 | 183.04 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 1312.97 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.75 | 13-AUG-16:00 | 317.39 | 05-AUG-17:40 |
September | 2010.83 | 01-SEP-09:09 | 906.35 | 19-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.46 | 17-SEP-12:35 | 239.09 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 1236.87 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.55 | 01-OCT-14:25 | 722.92 | 22-OCT-14:00 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.30 | 01-NOV-16:00 | 679.40 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 21-DEC-15:00 | 560.59 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 839.02 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.78 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 734.94 | 812.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 968.51 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 31-JAN-14:00 | 519.37 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 897.70 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 580.24 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 905.19 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 | 15-MAR-13:00 | 491.61 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 702.14 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.70 | 30-APR-15:49 | 276.60 | 16-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 569.32 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.11 | 20-MAY-17:45 | 187.72 | 01-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 543.10 | 27-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.69 | 17-JUN-17:10 | 108.19 | 13-JUN-04:10 |
July | 1295.83 | 03-JUL-09:09 | 570.33 | 24-JUL-08:20 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 478.98 | 22-JUL-18:00 | 171.52 | 26-JUL-23:50 |
August | 1295.83 | 01-AUG-09:09 | 856.93 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.74 | 13-AUG-16:00 | 270.73 | 05-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 805.87 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.22 | 17-SEP-12:35 | 185.00 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 932.09 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.15 | 01-OCT-14:25 | 502.58 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 28-NOV-16:30 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 | 01-NOV-16:00 | 499.09 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 21-DEC-15:00 | 408.38 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 543.10 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.19 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 478.98 | 580.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1480.95 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 132.45 | 16-JAN-11:53 | 1240.26 | 01-JAN-00:55 |
February | 2010.79 | 01-FEB-10:09 | 1379.52 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1559.56 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1286.17 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 149.12 | 18-MAR-17:02 | 1364.08 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 879.57 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 891.92 | 30-APR-15:53 | 710.26 | 21-APR-05:00 |
May | 2010.79 | 01-MAY-09:09 | 842.61 | 26-MAY-08:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 838.05 | 20-MAY-17:01 | 585.53 | 23-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1328.27 | 17-JUN-17:10 | 311.19 | 13-JUN-03:55 |
July | 2010.79 | 03-JUL-09:09 | 866.52 | 13-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.69 | 22-JUL-18:00 | 473.10 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 1301.67 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.14 | 13-AUG-16:00 | 698.13 | 05-AUG-17:45 |
September | 2010.79 | 01-SEP-09:09 | 1130.38 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1068.09 | 17-SEP-12:35 | 502.35 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1420.76 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 690.40 | 01-OCT-14:56 | 1313.19 | 22-OCT-13:55 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 28-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.75 | 19-NOV-15:00 | 1325.60 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 143.16 | 25-DEC-16:00 | 1141.64 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.19 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1668.69 | 1559.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 944.01 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.27 | 31-JAN-14:00 | 872.90 | 01-JAN-00:55 |
February | 1239.33 | 01-FEB-08:09 | 851.98 | 10-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1092.12 | 02-FEB-23:00 |
March | 1239.33 | 01-MAR-08:09 | 585.39 | 08-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.04 | 18-MAR-17:02 | 931.45 | 28-MAR-04:00 |
April | 1239.33 | 03-APR-07:10 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 611.81 | 30-APR-15:53 | 728.22 | 16-APR-08:50 |
May | 1239.33 | 01-MAY-07:10 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 520.26 | 20-MAY-17:01 | 397.78 | 23-MAY-05:00 |
June | 1239.33 | 01-JUN-07:10 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 889.26 | 17-JUN-17:10 | 232.89 | 25-JUN-06:00 |
July | 1239.33 | 03-JUL-07:10 | 567.16 | 13-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1123.71 | 22-JUL-17:43 | 327.36 | 26-JUL-24:00 |
August | 1239.33 | 01-AUG-07:10 | 810.47 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.09 | 13-AUG-16:00 | 488.30 | 05-AUG-17:45 |
September | 1239.33 | 01-SEP-07:10 | 563.69 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 718.68 | 17-SEP-12:35 | 342.60 | 03-SEP-05:00 |
October | 1239.33 | 02-OCT-07:10 | 671.44 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.79 | 01-OCT-14:56 | 1008.13 | 22-OCT-13:55 |
November | 1239.33 | 01-NOV-07:10 | 1071.42 | 28-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.76 | 19-NOV-15:00 | 909.29 | 29-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 1071.42 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.11 | 25-DEC-16:00 | 776.70 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.89 | |||||
Maximum of Months | 1239.33 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1123.71 | 1092.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1445.32 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.83 | 31-JAN-15:10 | 1552.74 | 01-JAN-00:55 |
February | 2010.83 | 01-FEB-10:09 | 1352.22 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1784.06 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1231.58 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.39 | 15-MAR-13:00 | 1437.20 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 887.78 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 865.56 | 30-APR-15:53 | 726.07 | 21-APR-05:00 |
May | 2010.83 | 01-MAY-09:09 | 842.61 | 26-MAY-08:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 820.03 | 20-MAY-17:01 | 587.47 | 23-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1329.10 | 17-JUN-17:10 | 306.42 | 13-JUN-03:55 |
July | 2010.83 | 03-JUL-09:09 | 870.46 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.30 | 22-JUL-18:00 | 471.48 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 1308.95 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1509.13 | 13-AUG-16:00 | 732.72 | 05-AUG-17:45 |
September | 2010.83 | 01-SEP-09:09 | 899.61 | 29-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1049.35 | 17-SEP-12:35 | 524.05 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 1182.61 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 655.04 | 01-OCT-14:40 | 1634.27 | 22-OCT-13:55 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.11 | 01-NOV-16:10 | 1458.46 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 21-DEC-15:00 | 1235.37 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.42 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1693.30 | 1784.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 966.14 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 16-JAN-11:53 | 962.34 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 893.17 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1154.56 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 900.60 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.59 | 15-MAR-13:00 | 973.95 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 693.99 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 571.72 | 30-APR-15:13 | 511.90 | 26-APR-21:20 |
May | 1295.83 | 01-MAY-09:09 | 564.31 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 515.77 | 20-MAY-17:45 | 421.67 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 889.23 | 17-JUN-17:10 | 238.33 | 13-JUN-03:55 |
July | 1295.83 | 03-JUL-09:09 | 565.16 | 24-JUL-08:20 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.46 | 22-JUL-18:00 | 375.59 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 851.30 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1006.06 | 13-AUG-16:00 | 511.26 | 05-AUG-17:45 |
September | 1295.83 | 01-SEP-09:09 | 798.69 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 718.33 | 17-SEP-12:35 | 353.32 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 929.22 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 468.51 | 01-OCT-14:54 | 941.10 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 28-NOV-16:30 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.34 | 19-NOV-12:32 | 933.44 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.22 | 25-DEC-13:41 | 796.08 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.33 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.46 | 1154.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1480.71 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.05 | 16-JAN-12:00 | 1287.75 | 01-JAN-01:07 |
February | 2010.79 | 01-FEB-10:09 | 1378.94 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1772.88 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1285.55 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 164.66 | 18-MAR-17:02 | 1539.52 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 879.40 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.66 | 30-APR-15:25 | 841.74 | 26-APR-21:10 |
May | 2010.79 | 01-MAY-09:09 | 842.22 | 26-MAY-08:30 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 967.09 | 20-MAY-17:01 | 695.47 | 23-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1641.17 | 17-JUN-17:10 | 383.63 | 13-JUN-03:55 |
July | 2010.79 | 03-JUL-09:09 | 866.18 | 13-JUL-15:00 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2051.60 | 22-JUL-18:00 | 604.67 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 1300.93 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1855.35 | 13-AUG-16:00 | 891.31 | 05-AUG-17:45 |
September | 2010.79 | 01-SEP-09:09 | 1129.45 | 29-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1311.28 | 17-SEP-12:35 | 637.73 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1420.64 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 825.58 | 01-OCT-14:25 | 1577.72 | 22-OCT-13:55 |
November | 2010.79 | 01-NOV-09:09 | 1662.56 | 28-NOV-16:30 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 546.01 | 19-NOV-12:52 | 1501.30 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1662.56 | 01-DEC-16:30 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 224.02 | 25-DEC-15:52 | 1350.92 | 07-DEC-05:06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 383.63 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2051.60 | 1772.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 943.75 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 16-JAN-14:00 | 863.27 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 851.56 | 10-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1247.54 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 585.26 | 08-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.26 | 18-MAR-17:02 | 1059.22 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 735.41 | 30-APR-15:23 | 850.83 | 16-APR-08:30 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 636.88 | 20-MAY-17:07 | 472.79 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.26 | 17-JUN-17:10 | 288.95 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 566.96 | 13-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1383.93 | 22-JUL-17:43 | 416.55 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 809.96 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.88 | 13-AUG-16:00 | 619.21 | 05-AUG-17:45 |
September | 1295.83 | 01-SEP-09:09 | 563.52 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 885.81 | 17-SEP-12:35 | 432.71 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 671.36 | 31-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 550.65 | 01-OCT-14:25 | 1219.04 | 22-OCT-13:55 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 28-NOV-16:30 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.55 | 19-NOV-15:00 | 1037.67 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:30 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.34 | 25-DEC-16:00 | 909.82 | 07-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.95 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1383.93 | 1247.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1444.89 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.78 | 31-JAN-14:10 | 1618.74 | 01-JAN-00:55 |
February | 2010.83 | 01-FEB-10:09 | 1351.59 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2067.96 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1230.90 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.26 | 15-MAR-13:00 | 1641.81 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 887.62 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.79 | 30-APR-14:55 | 879.48 | 26-APR-21:10 |
May | 2010.83 | 01-MAY-09:09 | 842.22 | 26-MAY-08:30 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 950.64 | 20-MAY-17:47 | 697.67 | 23-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 791.06 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1641.22 | 17-JUN-17:10 | 377.55 | 13-JUN-03:55 |
July | 2010.83 | 03-JUL-09:09 | 870.31 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2057.23 | 22-JUL-17:43 | 602.59 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 1308.21 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1855.27 | 13-AUG-16:00 | 934.76 | 05-AUG-17:45 |
September | 2010.83 | 01-SEP-09:09 | 899.40 | 29-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1280.94 | 17-SEP-12:35 | 664.43 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 1182.19 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.60 | 01-OCT-14:25 | 1979.74 | 22-OCT-13:55 |
November | 2010.83 | 01-NOV-09:09 | 1662.60 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.79 | 01-NOV-16:00 | 1681.86 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1662.60 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.76 | 21-DEC-15:00 | 1404.36 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.55 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2057.23 | 2067.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 966.01 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.34 | 16-JAN-12:00 | 1010.29 | 01-JAN-00:55 |
February | 1295.83 | 01-FEB-10:09 | 892.81 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1334.09 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 900.31 | 21-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.17 | 15-MAR-13:00 | 1124.48 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 693.91 | 04-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 687.86 | 30-APR-15:00 | 633.84 | 26-APR-21:10 |
May | 1295.83 | 01-MAY-09:09 | 564.12 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 628.18 | 20-MAY-17:45 | 504.85 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1091.14 | 17-JUN-17:10 | 293.32 | 13-JUN-03:55 |
July | 1295.83 | 03-JUL-09:09 | 565.00 | 24-JUL-08:20 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.74 | 22-JUL-18:00 | 478.34 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 850.85 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1236.02 | 13-AUG-16:00 | 649.79 | 05-AUG-17:45 |
September | 1295.83 | 01-SEP-09:09 | 798.21 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 885.13 | 17-SEP-12:35 | 445.19 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 929.08 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 545.65 | 01-OCT-14:25 | 1138.60 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 1071.42 | 28-NOV-16:30 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.19 | 19-NOV-12:13 | 1075.07 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1071.42 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.63 | 25-DEC-13:52 | 909.80 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.32 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.74 | 1334.09 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.48 | 31-JAN-14:00 | 1636.90 | 01-JAN-00:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1700.72 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.97 | 18-MAR-17:02 | 1453.10 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 782.93 | 30-APR-14:51 | 722.13 | 21-APR-04:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.97 | 20-MAY-17:01 | 571.11 | 23-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.54 | 17-JUN-17:03 | 269.76 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1489.01 | 22-JUL-18:00 | 414.12 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1269.96 | 13-AUG-16:00 | 637.19 | 05-AUG-17:45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960.12 | 17-SEP-11:53 | 472.22 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.73 | 01-OCT-14:50 | 1281.39 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.00 | 19-NOV-14:52 | 1448.99 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 21-DEC-15:00 | 1218.64 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.76 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1489.01 | 1700.72 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.87 | 31-JAN-14:00 | 2420.24 | 01-JAN-00:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2964.63 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.59 | 18-MAR-17:02 | 2489.17 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1470.74 | 30-APR-15:00 | 1277.63 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1363.10 | 20-MAY-17:01 | 1021.38 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2187.69 | 17-JUN-17:03 | 497.85 | 13-JUN-03:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2692.06 | 22-JUL-18:00 | 752.98 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.48 | 13-AUG-16:00 | 1126.56 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1734.00 | 17-SEP-12:00 | 827.03 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.00 | 01-OCT-14:40 | 2175.29 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.37 | 19-NOV-14:52 | 2458.19 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.14 | 25-DEC-16:00 | 2109.84 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 497.85 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2692.06 | 2964.63 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.13 | 16-JAN-11:53 | 2105.13 | 01-JAN-01:20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2952.58 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.89 | 15-MAR-13:00 | 2467.17 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1193.02 | 30-APR-15:50 | 1291.82 | 26-APR-21:02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1307.93 | 20-MAY-17:01 | 1062.99 | 23-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2344.34 | 17-JUN-17:03 | 526.99 | 13-JUN-03:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2756.65 | 22-JUL-18:00 | 915.85 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2244.05 | 13-AUG-16:00 | 1418.41 | 05-AUG-17:45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1730.84 | 17-SEP-12:20 | 994.60 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1027.14 | 01-OCT-14:12 | 2786.82 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.00 | 19-NOV-15:00 | 2453.23 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.27 | 25-DEC-13:52 | 2046.26 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.99 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2756.65 | 2952.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 102750.74 | 02-JAN-05:11 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 101989.06 | 21-FEB-05:12 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 103219.98 | 20-MAR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 102337.13 | 24-APR-04:21 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 103380.18 | 08-MAY-04:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 103419.32 | 19-JUN-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 105301.79 | 03-JUL-04:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 103144.26 | 27-AUG-16:16 | 8976.13 | 8190.52 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100241.87 | 28-SEP-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 103627.22 | 23-OCT-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 102362.40 | 06-NOV-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 102973.40 | 11-DEC-05:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 100241.87 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 105301.79 | 8976.13 | 8190.52 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 86351.38 | 17-JAN-05:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 86575.69 | 21-FEB-05:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 87676.09 | 20-MAR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 84404.17 | 28-APR-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 90694.21 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88323.36 | 01-JUN-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80507.23 | 29-JUL-04:12 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83930.17 | 21-AUG-05:05 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88309.23 | 29-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90651.56 | 10-OCT-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 88358.68 | 06-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 89460.58 | 04-DEC-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 80507.23 | 0.00 | 2686.80 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 90694.21 | 9673.43 | 3761.52 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 74714.05 | 27-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74311.25 | 01-FEB-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 75592.85 | 20-MAR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77300.54 | 18-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77558.79 | 31-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82977.06 | 01-JUN-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82680.20 | 03-JUL-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76487.84 | 05-AUG-04:12 | 0.00 | 3224.16 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78389.02 | 26-SEP-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78264.18 | 11-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78525.92 | 13-NOV-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 73507.84 | 28-DEC-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 73507.84 | 0.00 | 2686.80 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82977.06 | 8061.19 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 35728.87 | 27-JAN-17:00 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33878.84 | 23-FEB-15:00 | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72024.86 | 17-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76307.29 | 26-APR-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84595.62 | 08-MAY-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85336.75 | 19-JUN-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84818.26 | 03-JUL-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78759.68 | 21-AUG-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80378.48 | 05-SEP-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 77012.85 | 05-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 72255.06 | 03-NOV-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33733.37 | 22-DEC-16:50 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 33733.37 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85336.75 | 16014.58 | 13241.18 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5236.82 | 31-JAN-16:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 | 0.00 |
February | 5211.48 | 22-FEB-14:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.18 |
March | 7397.15 | 20-MAR-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 21.30 | 0.00 |
April | 18073.25 | 30-APR-16:21 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 293.46 | 0.00 |
May | 18146.72 | 29-MAY-18:11 | 0.00 | 395.49 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 167.29 | 0.00 |
June | 19291.97 | 25-JUN-18:31 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 369.15 | 0.00 |
July | 18952.81 | 04-JUL-18:11 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 290.41 | 0.00 |
August | 18500.01 | 13-AUG-16:21 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 569.94 | 0.00 |
September | 18053.44 | 10-SEP-16:42 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.53 | 0.00 |
October | 14031.51 | 02-OCT-04:23 | 0.00 | 269.88 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 0.00 |
November | 9271.52 | 13-NOV-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.19 |
December | 5465.25 | 26-DEC-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5211.48 | 0.00 | 263.66 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19291.97 | 2010.79 | 791.05 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 569.94 | 35.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7730.19 | 17-JAN-09:30 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.09 |
February | 10671.26 | 20-FEB-09:03 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.58 |
March | 17217.37 | 19-MAR-09:32 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.68 |
April | 19626.92 | 23-APR-08:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.12 |
May | 20301.77 | 29-MAY-09:31 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 |
June | 20170.01 | 25-JUN-07:51 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 |
July | 19067.67 | 04-JUL-08:51 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 | 0.00 |
August | 19027.73 | 13-AUG-09:02 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 0.00 |
September | 19940.70 | 10-SEP-09:21 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 25.23 | 0.00 |
October | 18792.06 | 15-OCT-08:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.45 |
November | 9026.42 | 19-NOV-09:33 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.55 |
December | 6784.77 | 26-DEC-09:40 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6784.77 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20301.77 | 1239.33 | 509.78 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 39.00 | 130.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22628.36 | 22-JAN-13:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.45 |
February | 17043.02 | 26-FEB-11:13 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.08 |
March | 15819.24 | 26-MAR-14:53 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.52 |
April | 21341.38 | 23-APR-15:41 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 175.87 | 0.00 |
May | 20488.08 | 07-MAY-16:21 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 236.84 | 0.00 |
June | 21118.35 | 04-JUN-15:51 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 327.55 | 0.00 |
July | 20976.40 | 04-JUL-16:51 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 363.28 | 0.00 |
August | 21055.45 | 27-AUG-13:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 319.18 | 0.00 |
September | 22735.38 | 10-SEP-12:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 165.49 | 0.00 |
October | 23503.15 | 15-OCT-13:21 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 38.19 | 0.00 |
November | 22547.24 | 26-NOV-12:42 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.46 |
December | 22616.59 | 10-DEC-14:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15819.24 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23503.15 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 363.28 | 239.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24377.94 | 29-JAN-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.24 |
February | 18040.19 | 20-FEB-16:22 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.91 |
March | 23157.96 | 26-MAR-16:12 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.81 |
April | 28896.48 | 23-APR-16:21 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 63.19 | 0.00 |
May | 27513.08 | 28-MAY-17:01 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 82.43 | 0.00 |
June | 28754.76 | 25-JUN-17:11 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 160.08 | 0.00 |
July | 28193.33 | 04-JUL-16:51 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 175.24 | 0.00 |
August | 27085.93 | 13-AUG-16:21 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 308.36 | 0.00 |
September | 24248.60 | 04-SEP-15:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 54.93 | 0.00 |
October | 24844.17 | 15-OCT-14:01 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 48.34 | 0.00 |
November | 23052.91 | 26-NOV-14:42 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.85 |
December | 24160.14 | 25-DEC-16:12 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18040.19 | 0.00 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28896.48 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 308.36 | 156.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3953.37 | 31-JAN-16:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 | 0.00 |
February | 3210.13 | 22-FEB-14:10 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.55 |
March | 5661.58 | 16-MAR-16:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 71.70 | 0.00 |
April | 17456.02 | 30-APR-16:31 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 670.86 | 0.00 |
May | 18044.12 | 07-MAY-17:01 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 536.67 | 0.00 |
June | 19361.15 | 25-JUN-18:01 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 964.31 | 0.00 |
July | 18950.27 | 30-JUL-18:11 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1050.70 | 0.00 |
August | 19202.53 | 13-AUG-16:11 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1271.87 | 0.00 |
September | 18029.02 | 10-SEP-16:42 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 813.42 | 0.00 |
October | 17753.53 | 01-OCT-13:32 | 506.08 | 219.72 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 594.91 | 0.00 |
November | 5624.07 | 02-NOV-14:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 67.28 | 0.00 |
December | 2770.66 | 22-DEC-16:10 | 1923.11 | 838.84 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2770.66 | 0.00 | 219.72 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19361.15 | 4021.58 | 1582.09 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1271.87 | 82.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7073.99 | 27-JAN-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.77 |
February | 7228.57 | 23-FEB-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.21 |
March | 13982.39 | 19-MAR-09:23 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.55 |
April | 21496.07 | 30-APR-09:51 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.47 |
May | 21787.53 | 07-MAY-09:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.23 |
June | 22394.03 | 25-JUN-08:41 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 21.74 | 0.00 |
July | 21714.92 | 30-JUL-08:11 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.44 |
August | 22403.74 | 13-AUG-08:51 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 58.07 | 0.00 |
September | 21577.46 | 10-SEP-10:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 98.96 | 0.00 |
October | 19560.72 | 09-OCT-09:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.63 |
November | 8610.25 | 01-NOV-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
December | 5666.45 | 27-DEC-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5666.45 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22403.74 | 2478.65 | 1019.56 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 98.96 | 188.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21650.21 | 29-JAN-13:52 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.23 |
February | 17093.60 | 20-FEB-15:13 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.28 |
March | 15714.64 | 26-MAR-14:03 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.39 |
April | 21137.67 | 30-APR-12:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 409.88 | 0.00 |
May | 20422.76 | 07-MAY-16:21 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 538.43 | 0.00 |
June | 20874.83 | 25-JUN-18:01 | 0.00 | 439.45 | 5591.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1025.85 | 0.00 |
July | 21594.69 | 30-JUL-14:51 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 657.29 | 0.00 |
August | 22063.58 | 13-AUG-16:11 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1227.91 | 0.00 |
September | 22784.35 | 10-SEP-12:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 363.31 | 0.00 |
October | 23606.86 | 09-OCT-12:31 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 44.35 | 0.00 |
November | 21330.51 | 19-NOV-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.01 |
December | 22752.83 | 03-DEC-14:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15714.64 | 0.00 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23606.86 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1227.91 | 558.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14447.62 | 29-JAN-16:32 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.09 |
February | 10774.24 | 22-FEB-16:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.97 |
March | 15884.79 | 18-MAR-17:05 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
April | 24766.66 | 30-APR-16:31 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 189.67 | 0.00 |
May | 24975.43 | 07-MAY-16:21 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 247.66 | 0.00 |
June | 26070.20 | 25-JUN-17:21 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 394.83 | 0.00 |
July | 25936.65 | 30-JUL-17:31 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 541.60 | 0.00 |
August | 26257.94 | 13-AUG-16:51 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 544.27 | 0.00 |
September | 23543.97 | 04-SEP-16:51 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 92.93 | 0.00 |
October | 22827.49 | 09-OCT-16:31 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 159.51 | 0.00 |
November | 14254.25 | 19-NOV-15:32 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 0.00 |
December | 14962.26 | 25-DEC-16:32 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10774.24 | 0.00 | 141.60 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26257.94 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 544.27 | 104.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3725.45 | 31-JAN-16:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 46.72 | 0.00 |
February | 2962.35 | 22-FEB-16:20 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.02 |
March | 6119.57 | 16-MAR-16:00 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 86.96 | 0.00 |
April | 17346.66 | 30-APR-16:01 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 976.47 | 0.00 |
May | 20763.89 | 28-MAY-16:51 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 667.63 | 0.00 |
June | 21426.58 | 25-JUN-18:11 | 0.00 | 351.55 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.29 | 0.00 |
July | 22924.31 | 16-JUL-17:31 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1215.86 | 0.00 |
August | 21400.62 | 13-AUG-16:21 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1590.18 | 0.00 |
September | 20594.63 | 24-SEP-15:32 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 651.42 | 0.00 |
October | 14762.44 | 02-OCT-03:02 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.31 |
November | 5852.17 | 01-NOV-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 76.48 | 0.00 |
December | 2556.13 | 22-DEC-16:40 | 1923.11 | 1060.58 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2556.13 | 0.00 | 263.66 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22924.31 | 1923.11 | 1060.58 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1590.18 | 86.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4929.59 | 27-JAN-10:30 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.91 |
February | 5608.34 | 23-FEB-10:20 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.58 |
March | 7425.87 | 23-MAR-10:20 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.39 |
April | 20384.74 | 09-APR-10:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 |
May | 21475.26 | 28-MAY-10:12 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 39.52 | 0.00 |
June | 23110.51 | 18-JUN-08:11 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 91.60 | 0.00 |
July | 22388.96 | 30-JUL-08:11 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.88 |
August | 21209.80 | 13-AUG-09:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 95.62 | 0.00 |
September | 20288.81 | 10-SEP-10:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 191.32 | 0.00 |
October | 19843.37 | 15-OCT-09:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.90 |
November | 6508.86 | 01-NOV-10:00 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.92 |
December | 3126.63 | 22-DEC-10:40 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3126.63 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23110.51 | 1295.83 | 509.78 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 191.32 | 104.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25863.50 | 29-JAN-14:11 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.50 |
February | 19554.80 | 26-FEB-14:43 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 773.53 |
March | 14425.96 | 23-MAR-14:00 | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 60.88 | 0.00 |
April | 23532.25 | 02-APR-16:21 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 136.53 | 0.00 |
May | 22939.21 | 28-MAY-16:51 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 657.90 | 0.00 |
June | 22962.87 | 18-JUN-17:32 | 0.00 | 219.72 | 2795.90 | 0.00 | 0.00 | 0.00 | 0.00 | 320.17 | 0.00 |
July | 25170.12 | 30-JUL-14:51 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 767.57 | 0.00 |
August | 23822.36 | 13-AUG-16:21 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1561.05 | 0.00 |
September | 24307.75 | 10-SEP-13:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 706.66 | 0.00 |
October | 26565.62 | 09-OCT-13:41 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 53.71 | 0.00 |
November | 23910.90 | 26-NOV-13:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.43 |
December | 24612.10 | 03-DEC-14:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14425.96 | 0.00 | 175.78 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26565.62 | 2010.83 | 791.06 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1561.05 | 773.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20076.17 | 29-JAN-16:12 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.77 |
February | 10715.77 | 22-FEB-16:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.08 |
March | 17199.12 | 18-MAR-17:05 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
April | 27165.16 | 02-APR-16:21 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 0.00 |
May | 27621.87 | 28-MAY-16:51 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 197.41 | 0.00 |
June | 25805.27 | 25-JUN-17:31 | 0.00 | 226.55 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 645.36 | 0.00 |
July | 28835.49 | 30-JUL-17:31 | 0.00 | 283.19 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 630.01 | 0.00 |
August | 26035.31 | 13-AUG-16:21 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 896.52 | 0.00 |
September | 23850.78 | 24-SEP-15:32 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 380.86 | 0.00 |
October | 25120.30 | 09-OCT-15:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 190.82 | 0.00 |
November | 12446.44 | 01-NOV-16:00 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 | 0.00 |
December | 13088.74 | 25-DEC-16:12 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10715.77 | 0.00 | 169.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28835.49 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 896.52 | 111.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6159.60 | 17-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 |
February | 5299.93 | 21-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.48 |
March | 7383.93 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.86 |
April | 9319.85 | 24-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.62 | 0.00 |
May | 11964.53 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.12 |
June | 12046.87 | 05-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.78 |
July | 15132.12 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 |
August | 17219.69 | 28-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 0.00 |
September | 13994.52 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.16 |
October | 13452.12 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 0.00 |
November | 9054.68 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.95 |
December | 8889.90 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5299.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17219.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.62 | 182.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3329.77 | 27-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 0.00 |
February | 3183.66 | 01-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.16 |
March | 4310.14 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.65 |
April | 7044.22 | 25-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.96 | 0.00 |
May | 7672.61 | 08-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.33 | 0.00 |
June | 9638.34 | 26-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.64 |
July | 9663.86 | 31-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 | 0.00 |
August | 12812.67 | 28-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 0.00 |
September | 10573.04 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.02 |
October | 8845.45 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 | 0.00 |
November | 4619.41 | 02-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.08 | 0.00 |
December | 7311.35 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3183.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12812.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.96 | 460.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8574.41 | 31-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.06 | 0.00 |
February | 7726.42 | 23-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.13 |
March | 12062.91 | 16-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.38 | 0.00 |
April | 19394.92 | 14-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.88 | 0.00 |
May | 19868.37 | 19-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.34 | 0.00 |
June | 24168.65 | 28-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.99 | 0.00 |
July | 22619.36 | 20-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.32 | 0.00 |
August | 22243.24 | 15-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.27 | 0.00 |
September | 19760.21 | 07-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.93 | 0.00 |
October | 17355.82 | 02-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.87 | 0.00 |
November | 11084.33 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.64 | 0.00 |
December | 6487.88 | 22-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6487.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24168.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.99 | 230.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2269.16 | 29-JAN-17:15 | 46.77 | 70.37 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4068.56 | 27-FEB-17:40 | 70.15 | 175.91 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7149.80 | 31-MAR-24:00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7785.51 | 26-APR-18:50 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3493.39 | 31-MAY-23:55 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5429.60 | 30-JUN-24:00 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7341.07 | 31-JUL-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7782.77 | 20-AUG-23:50 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3492.33 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5321.31 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6268.13 | 26-NOV-16:53 | 35.07 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7940.85 | 28-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2269.16 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7940.85 | 222.14 | 316.63 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2061.23 | 24-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3810.85 | 27-FEB-17:40 | 70.15 | 175.91 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6696.05 | 31-MAR-23:40 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7420.90 | 26-APR-18:50 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3404.56 | 31-MAY-23:55 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5222.19 | 30-JUN-24:00 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7013.90 | 31-JUL-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7274.42 | 20-AUG-20:52 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3408.00 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4928.06 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5827.19 | 14-NOV-17:00 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7471.51 | 28-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2061.23 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7471.51 | 222.14 | 316.63 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2077.23 | 24-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3784.95 | 27-FEB-17:40 | 70.15 | 175.91 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6523.96 | 31-MAR-23:20 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7533.02 | 26-APR-18:30 | 23.38 | 105.54 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3403.52 | 31-MAY-23:55 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5274.16 | 30-JUN-24:00 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7058.14 | 31-JUL-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7475.90 | 20-AUG-21:03 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3436.68 | 30-SEP-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4740.24 | 31-OCT-23:40 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5847.14 | 21-NOV-17:00 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7433.67 | 28-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2077.23 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7533.02 | 222.14 | 316.63 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92349.85 | 17-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182944.37 | 21-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358012.76 | 31-MAR-24:00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 380835.57 | 03-APR-21:01 | 1771.62 | 3233.49 | 2657427.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175605.43 | 31-MAY-24:00 | 0.00 | 461.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267480.47 | 30-JUN-23:57 | 0.00 | 692.81 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 356506.24 | 31-JUL-23:13 | 0.00 | 692.81 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 386584.44 | 23-AUG-22:53 | 1012.35 | 923.75 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177154.08 | 30-SEP-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269011.04 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276954.62 | 20-NOV-17:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 372186.93 | 25-DEC-16:41 | 2024.71 | 1847.50 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92349.85 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 386584.44 | 4808.68 | 4157.19 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.171476E+13 | 1281223.64 | 27-JAN-16:00 | 0.718621E+11 | 440578.96 | 02-JAN-06:10 |
February | 0.169726E+13 | 1265532.48 | 22-FEB-16:30 | 0.667565E+11 | 242095.69 | 13-FEB-06:10 |
March | 0.248043E+13 | 1657513.44 | 17-MAR-15:30 | 0.722675E+11 | 434805.59 | 27-MAR-06:10 |
April | 0.314970E+13 | 1871957.50 | 10-APR-15:00 | 0.536409E+11 | 71676.18 | 04-APR-11:30 |
May | 0.204891E+13 | 1330275.91 | 08-MAY-07:00 | 0.532374E+11 | 68119.10 | 02-MAY-11:20 |
June | 0.252401E+13 | 1573029.07 | 28-JUN-15:09 | 0.495258E+11 | 62657.83 | 05-JUN-11:20 |
July | 0.293467E+13 | 1739824.55 | 20-JUL-15:09 | 0.474708E+11 | 59342.37 | 03-JUL-11:50 |
August | 0.340205E+13 | 1972025.41 | 25-AUG-15:09 | 0.504413E+11 | 60833.97 | 30-AUG-11:30 |
September | 0.193198E+13 | 1378812.99 | 05-SEP-07:00 | 0.489705E+11 | 64064.95 | 21-SEP-11:50 |
October | 0.224925E+13 | 1479655.96 | 02-OCT-15:00 | 0.556417E+11 | 216027.10 | 25-OCT-06:10 |
November | 0.238411E+13 | 1620699.60 | 09-NOV-16:00 | 0.617120E+11 | 294103.68 | 24-NOV-07:10 |
December | 0.279305E+13 | 1682001.47 | 22-DEC-16:19 | 0.102254E+12 | 561954.11 | 06-DEC-07:10 |
Annual Sum or Average | 0.293102E+14 | 0.733781E+12 | ||||
Minimum of Months | 0.169726E+13 | 1265532.48 | 0.474708E+11 | 59342.37 | ||
Maximum of Months | 0.340205E+13 | 1972025.41 | 0.102254E+12 | 561954.11 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.207218E+12 | 0.373844E+11 | 0.766053E+12 | 0.162121E+12 | 0.185800E+12 | 0.296546E+11 | 0.00 | 0.938919E+11 | 0.445705E+11 | 0.188062E+12 | 0.00 | 0.00 | 0.00 |
February | 0.187494E+12 | 0.309088E+11 | 0.978954E+12 | 0.146439E+12 | 0.164054E+12 | 0.214376E+11 | 0.00 | 0.556073E+11 | 0.198474E+11 | 0.925226E+11 | 0.00 | 0.00 | 0.00 |
March | 0.220964E+12 | 0.303717E+11 | 0.141687E+13 | 0.162292E+12 | 0.197103E+12 | 0.319981E+11 | 0.00 | 0.168627E+12 | 0.606969E+11 | 0.191509E+12 | 0.00 | 0.00 | 0.00 |
April | 0.196181E+12 | 0.256650E+11 | 0.165903E+13 | 0.156875E+12 | 0.237105E+12 | 0.538948E+11 | 0.00 | 0.457136E+12 | 0.109091E+12 | 0.254728E+12 | 0.00 | 0.00 | 0.00 |
May | 0.211321E+12 | 0.232835E+11 | 0.774844E+12 | 0.162206E+12 | 0.260987E+12 | 0.553064E+11 | 0.00 | 0.306840E+12 | 0.114302E+12 | 0.139823E+12 | 0.00 | 0.00 | 0.00 |
June | 0.209743E+12 | 0.213378E+11 | 0.106252E+13 | 0.157035E+12 | 0.286074E+12 | 0.702441E+11 | 0.00 | 0.513677E+12 | 0.137163E+12 | 0.662181E+11 | 0.00 | 0.00 | 0.00 |
July | 0.196377E+12 | 0.226209E+11 | 0.139340E+13 | 0.162046E+12 | 0.276516E+12 | 0.698445E+11 | 0.00 | 0.633468E+12 | 0.160053E+12 | 0.203374E+11 | 0.00 | 0.00 | 0.00 |
August | 0.219938E+12 | 0.251910E+11 | 0.173200E+13 | 0.162291E+12 | 0.285221E+12 | 0.711259E+11 | 0.00 | 0.701863E+12 | 0.161375E+12 | 0.430472E+11 | 0.00 | 0.00 | 0.00 |
September | 0.196801E+12 | 0.275813E+11 | 0.740713E+12 | 0.156875E+12 | 0.245431E+12 | 0.573510E+11 | 0.00 | 0.340383E+12 | 0.147420E+12 | 0.194214E+11 | 0.00 | 0.00 | 0.00 |
October | 0.205647E+12 | 0.325062E+11 | 0.108340E+13 | 0.162121E+12 | 0.216539E+12 | 0.446687E+11 | 0.00 | 0.253405E+12 | 0.939483E+11 | 0.157014E+12 | 0.00 | 0.00 | 0.00 |
November | 0.204663E+12 | 0.352667E+11 | 0.135889E+13 | 0.156940E+12 | 0.188518E+12 | 0.314176E+11 | 0.00 | 0.172123E+12 | 0.618646E+11 | 0.174420E+12 | 0.00 | 0.00 | 0.00 |
December | 0.201192E+12 | 0.385856E+11 | 0.170972E+13 | 0.162047E+12 | 0.181815E+12 | 0.274976E+11 | 0.00 | 0.161339E+12 | 0.482693E+11 | 0.262585E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245754E+13 | 0.350703E+12 | 0.146764E+14 | 0.190929E+13 | 0.272516E+13 | 0.564441E+12 | 0.00 | 0.385836E+13 | 0.115860E+13 | 0.160969E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.187494E+12 | 0.213378E+11 | 0.740713E+12 | 0.146439E+12 | 0.164054E+12 | 0.214376E+11 | 0.00 | 0.556073E+11 | 0.198474E+11 | 0.194214E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220964E+12 | 0.385856E+11 | 0.173200E+13 | 0.162292E+12 | 0.286074E+12 | 0.711259E+11 | 0.00 | 0.701863E+12 | 0.161375E+12 | 0.262585E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.111892E+11 | 0.00 | 0.606730E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.120931E+11 | 0.00 | 0.546634E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.113148E+11 | 0.00 | 0.609527E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 20108203.93 | 0.00 | 0.536208E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.532374E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.495258E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.474708E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.504413E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.489705E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.207547E+10 | 0.00 | 0.535662E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.626402E+10 | 0.00 | 0.554480E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.437819E+11 | 0.00 | 0.584724E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.867386E+11 | 0.00 | 0.647042E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.474708E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.437819E+11 | 0.00 | 0.609527E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 238914.26 | 20-JAN-16:00 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 116885.78 | 20-JAN-08:39 | 157711.12 | 31-JAN-16:00 | 39760.67 | 31-JAN-15:30 | 0.00 | 01-JAN-00:10 |
February | 235332.08 | 10-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 116884.63 | 10-FEB-08:20 | 150691.39 | 22-FEB-16:30 | 21866.63 | 23-FEB-14:20 | 0.00 | 01-FEB-00:10 |
March | 229209.04 | 21-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 116881.39 | 21-MAR-07:19 | 184306.18 | 16-MAR-15:50 | 41049.97 | 20-MAR-15:30 | 0.00 | 01-MAR-00:10 |
April | 217273.89 | 04-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 116875.08 | 04-APR-07:19 | 234029.31 | 25-APR-15:20 | 39448.69 | 14-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 214655.15 | 26-MAY-08:30 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 116873.38 | 26-MAY-07:19 | 236200.91 | 18-MAY-15:09 | 39422.05 | 10-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 212896.29 | 27-JUN-07:10 | 40855.88 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 116872.76 | 27-JUN-07:19 | 268224.52 | 19-JUN-14:00 | 45104.71 | 19-JUN-14:50 | 0.00 | 01-JUN-00:10 |
July | 215376.63 | 13-JUL-15:00 | 40855.88 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 116873.57 | 27-JUL-07:19 | 259721.88 | 21-JUL-15:39 | 41895.69 | 22-JUL-13:39 | 0.00 | 01-JUL-00:10 |
August | 232880.68 | 04-AUG-07:10 | 40855.88 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 116883.34 | 04-AUG-07:19 | 255717.86 | 08-AUG-15:20 | 43410.67 | 23-AUG-15:20 | 0.00 | 01-AUG-00:10 |
September | 221675.32 | 29-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 116877.40 | 29-SEP-07:19 | 237535.01 | 05-SEP-15:00 | 43741.82 | 28-SEP-13:30 | 0.00 | 01-SEP-00:10 |
October | 229737.59 | 27-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 116881.67 | 27-OCT-07:19 | 213845.36 | 02-OCT-15:00 | 43716.17 | 05-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 247210.90 | 28-NOV-16:30 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 116882.02 | 01-NOV-07:19 | 171580.43 | 02-NOV-15:00 | 47736.35 | 02-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 247210.90 | 01-DEC-16:30 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 116884.26 | 12-DEC-08:20 | 144956.13 | 22-DEC-16:00 | 39670.91 | 22-DEC-15:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 212896.29 | 40855.88 | 423497.50 | 116872.76 | 144956.13 | 21866.63 | 0.00 | |||||||
Maximum of Months | 247210.90 | 40855.88 | 778371.69 | 116885.78 | 268224.52 | 47736.35 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 248121.44 | 31-JAN-16:10 | 46206.67 | 26-JAN-13:00 | 100000.00 | 01-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 136011.93 | 21-FEB-15:30 | 45331.80 | 21-FEB-14:00 | 100000.00 | 01-FEB-22:10 | 0.00 | 0.00 | 0.00 |
March | 323597.61 | 20-MAR-14:39 | 77358.81 | 17-MAR-15:30 | 100000.00 | 08-MAR-05:00 | 0.00 | 0.00 | 0.00 |
April | 379003.04 | 14-APR-15:20 | 77358.81 | 10-APR-12:00 | 100000.00 | 01-APR-04:19 | 0.00 | 0.00 | 0.00 |
May | 275799.45 | 18-MAY-15:20 | 77358.81 | 04-MAY-14:20 | 100000.00 | 01-MAY-00:20 | 0.00 | 0.00 | 0.00 |
June | 384899.65 | 19-JUN-14:50 | 77358.81 | 01-JUN-08:20 | 100000.00 | 02-JUN-02:49 | 0.00 | 0.00 | 0.00 |
July | 430306.34 | 19-JUL-14:09 | 77358.81 | 13-JUL-17:00 | 100000.00 | 01-JUL-04:19 | 0.00 | 0.00 | 0.00 |
August | 446424.21 | 11-AUG-15:50 | 77358.81 | 03-AUG-15:20 | 100000.00 | 22-AUG-20:49 | 0.00 | 0.00 | 0.00 |
September | 334213.07 | 01-SEP-12:30 | 77358.81 | 04-SEP-09:20 | 100000.00 | 15-SEP-21:10 | 0.00 | 0.00 | 0.00 |
October | 337092.26 | 02-OCT-14:09 | 77358.81 | 02-OCT-07:19 | 100000.00 | 05-OCT-21:19 | 0.00 | 0.00 | 0.00 |
November | 319225.50 | 01-NOV-14:30 | 77358.81 | 01-NOV-12:20 | 100000.00 | 03-NOV-21:10 | 0.00 | 0.00 | 0.00 |
December | 314755.21 | 22-DEC-15:00 | 45965.68 | 22-DEC-15:09 | 100000.00 | 01-DEC-05:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 136011.93 | 45331.80 | 100000.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 446424.21 | 77358.81 | 100000.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1281223.64 | 27-JAN-16:00 | 214564.27 | 423497.50 | 0.00 | 82829.92 | 145668.13 | 39100.64 | 0.00 | 229951.24 | 45611.95 |
February | 1265532.48 | 22-FEB-16:30 | 212815.01 | 541788.89 | 0.00 | 82829.33 | 150691.39 | 21194.67 | 0.00 | 111338.52 | 44874.66 |
March | 1657513.44 | 17-MAR-15:30 | 212815.01 | 660080.29 | 0.00 | 82829.33 | 174538.51 | 40470.91 | 0.00 | 315815.48 | 77358.81 |
April | 1871957.50 | 10-APR-15:00 | 212815.01 | 778371.69 | 0.00 | 82829.33 | 220716.06 | 39340.77 | 0.00 | 360525.84 | 77358.81 |
May | 1330275.91 | 08-MAY-07:00 | 212815.01 | 423497.50 | 0.00 | 116872.72 | 165597.94 | 39048.78 | 0.00 | 226976.53 | 45467.43 |
June | 1573029.07 | 28-JUN-15:09 | 212815.01 | 541788.89 | 0.00 | 82829.33 | 232508.08 | 43491.96 | 0.00 | 382236.99 | 77358.81 |
July | 1739824.55 | 20-JUL-15:09 | 212815.01 | 660080.29 | 0.00 | 82829.33 | 254159.40 | 41096.27 | 0.00 | 411485.44 | 77358.81 |
August | 1972025.41 | 25-AUG-15:09 | 212815.01 | 778371.69 | 0.00 | 82829.33 | 248049.68 | 39745.71 | 0.00 | 432855.19 | 77358.81 |
September | 1378812.99 | 05-SEP-07:00 | 212815.01 | 423497.50 | 0.00 | 116872.72 | 181960.21 | 41508.87 | 0.00 | 324799.87 | 77358.81 |
October | 1479655.96 | 02-OCT-15:00 | 212815.01 | 541788.89 | 0.00 | 82829.33 | 213845.36 | 40434.06 | 0.00 | 310584.49 | 77358.81 |
November | 1620699.60 | 09-NOV-16:00 | 222068.11 | 660080.29 | 0.00 | 82832.82 | 158544.73 | 39087.11 | 0.00 | 311453.46 | 46633.07 |
December | 1682001.47 | 22-DEC-16:19 | 214131.18 | 778371.69 | 0.00 | 82829.66 | 116007.62 | 39394.20 | 0.00 | 306351.17 | 44915.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1265532.48 | 212815.01 | 423497.50 | 0.00 | 82829.33 | 116007.62 | 21194.67 | 0.00 | 111338.52 | 44874.66 | |
Maximum of Months | 1972025.41 | 222068.11 | 778371.69 | 0.00 | 116872.72 | 254159.40 | 43491.96 | 0.00 | 432855.19 | 77358.81 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 425728.41 | 02-JAN-06:10 | 0.00 | 76823.81 | 23-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 234814.81 | 13-FEB-06:10 | 0.00 | 76768.01 | 01-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 404907.69 | 27-MAR-06:10 | 0.00 | 75573.62 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 15057.97 | 21-APR-06:10 | 0.00 | 71676.18 | 04-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 68119.10 | 02-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 62657.83 | 05-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 59342.37 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 60833.97 | 30-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 64064.95 | 21-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 186366.28 | 25-OCT-06:10 | 0.00 | 70270.44 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 271765.18 | 24-NOV-06:10 | 0.00 | 73022.71 | 20-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 531907.45 | 06-DEC-07:10 | 0.00 | 76246.16 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 59342.37 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 531907.45 | 0.00 | 76823.81 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.31 | 2.00 | 27.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.48 | 0.00 | 26.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.84 | 0.00 | 25.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.68 | 0.00 | 26.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 26.90 | 0.00 | 26.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.16 | 0.00 | 26.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.24 | 0.17 | 26.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 25.86 | 0.33 | 25.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.70 | 1.50 | 26.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.81 | 0.83 | 26.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.86 | 1.50 | 26.96 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 26.89 | 0.50 | 26.94 |
Annual Sum or Average | 0.00 | 0.00 | 70.00 | 26.63 | 6.83 | 26.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.84 | 0.00 | 25.84 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.31 | 2.00 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.69 | 0.00 | 25.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.90 | 0.00 | 25.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.63 | 0.00 | 25.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.61 | 0.00 | 25.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.66 | 0.33 | 25.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.76 | 0.00 | 25.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.67 | 0.00 | 25.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
Annual Sum or Average | 0.00 | 0.00 | 7.00 | 25.65 | 0.33 | 25.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.90 | 0.33 | 25.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.64 | 0.00 | 25.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.08 | 0.00 | 19.08 | 0.50 | 23.98 | 0.00 | 23.98 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.08 | 0.00 | 19.08 | 0.33 | 25.64 | 0.00 | 25.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.31 | 1.00 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.33 | 0.67 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.30 | 5.33 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.11 | 8.33 | 27.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.07 | 5.67 | 27.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.03 | 2.83 | 27.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.97 | 1.17 | 27.13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 47.17 | 27.14 | 25.00 | 27.26 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.33 | 8.33 | 27.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.43 | 1.17 | 27.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.54 | 1.50 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.77 | 10.33 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.84 | 13.17 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 27.81 | 11.17 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.62 | 14.17 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.65 | 9.67 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.53 | 9.00 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.50 | 6.33 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.34 | 0.83 | 27.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
Annual Sum or Average | 0.00 | 0.00 | 95.67 | 27.68 | 77.67 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.84 | 14.17 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.20 | 11.50 | 27.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.62 | 2.33 | 27.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.38 | 1.50 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.72 | 7.67 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.41 | 6.50 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.27 | 6.00 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.23 | 9.83 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.23 | 7.33 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 27.19 | 9.33 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 26.86 | 14.67 | 26.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 26.08 | 16.17 | 26.08 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.91 | 12.83 | 26.91 |
Annual Sum or Average | 0.00 | 0.00 | 133.67 | 27.06 | 105.67 | 27.09 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.08 | 1.50 | 26.08 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.72 | 16.17 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.83 | 4.17 | 27.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.87 | 1.17 | 27.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.71 | 3.83 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 53.33 | 27.77 | 17.67 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.85 | 9.33 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 27.59 | 17.33 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 70.17 | 27.67 | 22.50 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 76.33 | 27.86 | 21.33 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.29 | 10.00 | 27.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.63 | 8.00 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.71 | 4.83 | 27.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.95 | 5.33 | 28.00 |
Annual Sum or Average | 0.00 | 0.00 | 331.00 | 27.71 | 125.50 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.29 | 1.17 | 27.47 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 76.33 | 27.95 | 22.50 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.33 | 0.67 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.38 | 5.83 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.37 | 7.33 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.27 | 3.67 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.42 | 2.83 | 27.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.10 | 0.83 | 27.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Annual Sum or Average | 0.33 | 19.32 | 0.00 | 19.32 | 35.83 | 27.28 | 21.17 | 27.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.38 | 0.00 | 19.38 | 12.00 | 27.42 | 7.33 | 27.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.40 | 0.67 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.84 | 11.67 | 27.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.99 | 13.00 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.90 | 11.33 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.67 | 15.17 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.75 | 10.50 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.73 | 9.17 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.51 | 6.17 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Annual Sum or Average | 0.33 | 19.41 | 0.00 | 19.41 | 102.50 | 27.76 | 77.67 | 27.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.41 | 0.00 | 19.41 | 23.17 | 27.99 | 15.17 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 25.67 | 30.67 | 25.67 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.64 | 2.00 | 27.64 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.83 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.70 | 6.50 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.42 | 6.33 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.35 | 5.67 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.37 | 9.17 | 27.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.51 | 5.83 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.03 | 10.67 | 27.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 25.94 | 27.17 | 25.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 25.70 | 24.33 | 25.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 26.31 | 16.50 | 26.31 |
Annual Sum or Average | 0.00 | 0.00 | 164.33 | 26.45 | 145.67 | 26.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.67 | 0.83 | 25.67 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 27.70 | 30.67 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.70 | 1.67 | 27.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.69 | 0.17 | 27.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.66 | 0.33 | 27.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.28 | 5.17 | 28.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 28.34 | 6.17 | 28.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 27.68 | 8.17 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 27.61 | 11.17 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.54 | 6.83 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.57 | 6.17 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.85 | 4.83 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.67 | 1.67 | 27.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.80 | 1.00 | 27.80 |
Annual Sum or Average | 0.00 | 0.00 | 126.67 | 27.76 | 53.33 | 27.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.54 | 0.17 | 27.67 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 28.34 | 11.17 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 17.95 | 0.17 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
February | 0.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 0.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.38 | 1.33 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.48 | 4.33 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.59 | 8.00 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.46 | 10.33 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.54 | 5.33 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.50 | 5.17 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.36 | 1.50 | 27.45 |
November | 0.50 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
December | 2.83 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
Annual Sum or Average | 5.00 | 18.78 | 0.17 | 18.66 | 63.50 | 26.84 | 36.00 | 27.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.46 | 0.00 | 17.46 |
Maximum of Months | 2.83 | 19.26 | 0.17 | 19.26 | 20.17 | 27.59 | 10.33 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
February | 0.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
March | 0.17 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.85 | 12.00 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 28.06 | 13.00 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 27.95 | 11.67 | 28.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 27.80 | 15.50 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.82 | 10.67 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.79 | 9.17 | 27.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.51 | 6.17 | 27.56 |
November | 0.17 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
December | 2.67 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
Annual Sum or Average | 3.50 | 18.86 | 0.00 | 18.86 | 120.33 | 27.60 | 78.17 | 27.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 0.00 | 18.34 |
Maximum of Months | 2.67 | 19.13 | 0.00 | 19.13 | 28.83 | 28.06 | 15.50 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.50 | 0.00 | 18.50 | 5.83 | 27.90 | 5.83 | 28.03 |
February | 0.17 | 19.17 | 0.00 | 19.17 | 1.17 | 26.42 | 1.17 | 26.90 |
March | 0.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.79 | 7.33 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.61 | 6.83 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.57 | 7.33 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.52 | 10.50 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.65 | 6.83 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.44 | 9.50 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.89 | 8.83 | 27.96 |
November | 0.17 | 19.36 | 0.00 | 19.36 | 5.33 | 27.62 | 5.33 | 27.75 |
December | 1.17 | 19.04 | 0.00 | 19.04 | 5.17 | 26.42 | 5.17 | 27.17 |
Annual Sum or Average | 1.83 | 19.05 | 0.00 | 19.05 | 109.67 | 27.54 | 74.67 | 27.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.23 | 0.00 | 19.23 |
Maximum of Months | 1.17 | 19.36 | 0.00 | 19.36 | 20.17 | 27.90 | 10.50 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.34 | 0.00 | 18.34 | 1.00 | 26.23 | 1.00 | 26.84 |
February | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
March | 0.17 | 19.40 | 0.00 | 19.40 | 0.33 | 24.99 | 0.17 | 25.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.32 | 5.83 | 28.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 28.42 | 6.83 | 28.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 27.82 | 10.50 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 27.75 | 12.83 | 27.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 27.71 | 7.33 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.66 | 7.00 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.88 | 4.50 | 28.01 |
November | 0.17 | 19.28 | 0.00 | 19.28 | 1.00 | 26.41 | 1.00 | 26.96 |
December | 1.17 | 18.97 | 0.00 | 18.97 | 0.67 | 22.11 | 0.67 | 23.57 |
Annual Sum or Average | 1.83 | 19.02 | 0.00 | 19.02 | 142.17 | 27.76 | 57.67 | 27.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.44 | 0.00 | 19.44 |
Maximum of Months | 1.17 | 19.44 | 0.00 | 19.44 | 36.67 | 28.42 | 12.83 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 366.67 | 28.93 | 286.67 | 28.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 328.50 | 28.84 | 274.33 | 28.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 28.13 | 25.00 | 28.14 |
Annual Sum or Average | 0.00 | 0.00 | 721.00 | 28.86 | 586.00 | 28.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 366.67 | 28.93 | 286.67 | 28.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 336.33 | 28.74 | 268.17 | 28.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 280.83 | 28.62 | 239.33 | 28.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.91 | 8.00 | 27.91 |
Annual Sum or Average | 0.00 | 0.00 | 625.17 | 28.67 | 515.50 | 28.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 336.33 | 28.74 | 268.17 | 28.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 280.33 | 28.82 | 223.50 | 28.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.80 | 0.00 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 239.17 | 28.72 | 202.83 | 28.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.79 | 1.17 | 27.79 |
Annual Sum or Average | 0.00 | 0.00 | 522.67 | 28.77 | 427.50 | 28.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 280.33 | 28.82 | 223.50 | 28.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 312.00 | 31.45 | 279.00 | 31.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 44.33 | 28.31 | 20.83 | 28.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 667.33 | 31.07 | 486.83 | 31.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.13 | 9.33 | 28.13 |
Annual Sum or Average | 0.00 | 0.00 | 1033.00 | 31.04 | 796.00 | 31.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 667.33 | 31.45 | 486.83 | 31.53 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 92.17 | 24.00 | 112.83 | 25.25 | 0.00 | 25.25 |
February | 25.00 | 24.00 | 194.50 | 24.96 | 0.00 | 24.96 |
March | 89.17 | 24.00 | 101.83 | 24.90 | 0.00 | 24.90 |
April | 103.67 | 24.00 | 89.83 | 25.15 | 0.00 | 25.15 |
May | 129.83 | 24.00 | 78.33 | 24.93 | 0.00 | 24.93 |
June | 36.17 | 24.00 | 115.33 | 25.38 | 0.00 | 25.38 |
July | 160.50 | 24.39 | 412.83 | 24.65 | 149.00 | 24.60 |
August | 147.83 | 24.54 | 452.50 | 24.55 | 145.67 | 24.55 |
September | 109.83 | 24.88 | 390.50 | 24.75 | 109.83 | 24.78 |
October | 66.33 | 24.07 | 211.33 | 25.09 | 13.83 | 25.05 |
November | 61.67 | 24.64 | 202.17 | 25.26 | 19.50 | 25.31 |
December | 142.67 | 24.00 | 102.83 | 25.07 | 0.00 | 25.07 |
Annual Sum or Average | 1164.83 | 24.24 | 2464.83 | 24.89 | 437.83 | 24.87 |
Minimum of Months | 25.00 | 24.00 | 78.33 | 24.55 | 0.00 | 24.55 |
Maximum of Months | 160.50 | 24.88 | 452.50 | 25.38 | 149.00 | 25.38 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 108.17 | 24.00 | 74.33 | 24.65 | 0.00 | 24.65 |
February | 23.17 | 23.99 | 198.17 | 24.66 | 0.00 | 24.66 |
March | 55.17 | 24.01 | 111.17 | 24.73 | 0.00 | 24.73 |
April | 59.83 | 24.01 | 42.67 | 24.47 | 0.00 | 24.47 |
May | 80.67 | 24.02 | 36.83 | 24.57 | 0.00 | 24.57 |
June | 10.33 | 24.00 | 104.33 | 24.56 | 0.00 | 24.56 |
July | 11.33 | 24.01 | 402.17 | 24.27 | 0.00 | 24.27 |
August | 0.00 | 0.00 | 458.50 | 24.28 | 0.00 | 24.28 |
September | 15.50 | 25.74 | 395.50 | 24.44 | 15.50 | 24.49 |
October | 50.17 | 24.01 | 204.33 | 24.67 | 1.17 | 24.67 |
November | 60.00 | 24.26 | 185.33 | 24.72 | 8.00 | 24.76 |
December | 153.33 | 24.01 | 82.33 | 24.66 | 0.00 | 24.66 |
Annual Sum or Average | 627.67 | 24.07 | 2295.67 | 24.51 | 24.67 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 36.83 | 24.27 | 0.00 | 24.27 |
Maximum of Months | 153.33 | 25.74 | 458.50 | 24.73 | 15.50 | 24.76 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 280.83 | 23.76 | 24.50 | 23.85 | 0.00 | 23.85 |
February | 130.17 | 23.75 | 85.00 | 24.01 | 0.00 | 24.01 |
March | 167.33 | 23.92 | 55.17 | 24.16 | 0.00 | 24.16 |
April | 185.33 | 24.02 | 17.50 | 24.15 | 0.00 | 24.15 |
May | 156.83 | 24.02 | 19.50 | 24.22 | 0.00 | 24.22 |
June | 48.17 | 24.00 | 47.83 | 24.23 | 0.00 | 24.23 |
July | 37.67 | 24.19 | 374.00 | 24.21 | 19.00 | 24.22 |
August | 60.83 | 24.39 | 426.17 | 24.21 | 44.17 | 24.24 |
September | 44.50 | 24.96 | 381.67 | 24.42 | 44.50 | 24.47 |
October | 148.00 | 23.97 | 136.67 | 24.27 | 3.33 | 24.27 |
November | 247.17 | 23.97 | 112.17 | 24.16 | 26.17 | 24.19 |
December | 392.33 | 23.86 | 0.00 | 23.86 | 0.00 | 23.86 |
Annual Sum or Average | 1899.17 | 23.95 | 1680.17 | 24.15 | 137.17 | 24.17 |
Minimum of Months | 37.67 | 23.75 | 0.00 | 23.85 | 0.00 | 23.85 |
Maximum of Months | 392.33 | 24.96 | 426.17 | 24.42 | 44.50 | 24.47 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 437.67 | 23.21 | 20.33 | 23.06 | 18.17 | 22.92 |
February | 340.17 | 23.02 | 14.33 | 23.03 | 3.17 | 23.01 |
March | 300.83 | 23.47 | 22.83 | 23.48 | 4.33 | 23.45 |
April | 178.17 | 23.93 | 23.83 | 24.05 | 0.00 | 24.05 |
May | 146.83 | 24.01 | 27.83 | 24.27 | 0.00 | 24.27 |
June | 28.83 | 23.99 | 107.50 | 24.49 | 0.00 | 24.49 |
July | 46.17 | 24.13 | 396.83 | 24.31 | 30.33 | 24.31 |
August | 71.17 | 24.29 | 440.00 | 24.25 | 61.67 | 24.26 |
September | 68.17 | 24.63 | 392.50 | 24.44 | 68.00 | 24.46 |
October | 220.00 | 23.75 | 119.33 | 23.99 | 7.00 | 23.99 |
November | 327.50 | 23.29 | 89.50 | 23.50 | 27.50 | 23.52 |
December | 483.33 | 22.87 | 29.17 | 22.75 | 29.17 | 22.65 |
Annual Sum or Average | 2648.83 | 23.39 | 1684.00 | 23.72 | 249.33 | 23.71 |
Minimum of Months | 28.83 | 22.87 | 14.33 | 22.75 | 0.00 | 22.65 |
Maximum of Months | 483.33 | 24.63 | 440.00 | 24.49 | 68.00 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 448.33 | 23.55 | 10.33 | 23.58 | 0.00 | 23.58 |
February | 297.67 | 23.35 | 17.83 | 23.39 | 0.00 | 23.39 |
March | 262.83 | 23.58 | 38.33 | 23.71 | 0.00 | 23.71 |
April | 116.50 | 23.97 | 75.50 | 24.47 | 0.00 | 24.47 |
May | 59.83 | 24.00 | 88.67 | 24.98 | 0.00 | 24.98 |
June | 15.50 | 26.52 | 283.67 | 24.83 | 13.00 | 24.92 |
July | 34.67 | 26.53 | 455.83 | 24.70 | 33.50 | 24.82 |
August | 25.83 | 26.71 | 479.33 | 24.53 | 25.17 | 24.64 |
September | 36.67 | 26.35 | 424.83 | 24.65 | 36.67 | 24.78 |
October | 192.33 | 23.86 | 151.83 | 24.21 | 2.50 | 24.23 |
November | 306.83 | 23.72 | 88.67 | 23.87 | 13.33 | 23.90 |
December | 449.17 | 23.48 | 1.50 | 23.48 | 0.00 | 23.48 |
Annual Sum or Average | 2246.17 | 23.75 | 2116.33 | 24.16 | 124.17 | 24.23 |
Minimum of Months | 15.50 | 23.35 | 1.50 | 23.39 | 0.00 | 23.39 |
Maximum of Months | 449.17 | 26.71 | 479.33 | 24.98 | 36.67 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 269.00 | 23.53 | 44.33 | 23.79 | 0.00 | 23.79 |
February | 230.33 | 23.30 | 80.17 | 23.63 | 2.83 | 23.66 |
March | 195.33 | 23.54 | 102.17 | 23.93 | 1.33 | 23.95 |
April | 79.00 | 24.48 | 189.50 | 24.74 | 14.17 | 24.87 |
May | 45.67 | 25.49 | 237.50 | 25.01 | 20.67 | 25.17 |
June | 39.17 | 26.94 | 381.83 | 24.82 | 37.00 | 25.00 |
July | 53.50 | 26.80 | 466.33 | 24.82 | 52.33 | 25.01 |
August | 43.50 | 26.75 | 488.17 | 24.61 | 41.00 | 24.77 |
September | 50.17 | 26.60 | 446.50 | 24.74 | 50.17 | 24.91 |
October | 137.50 | 24.12 | 223.50 | 24.51 | 15.33 | 24.62 |
November | 221.50 | 23.67 | 129.67 | 23.99 | 15.33 | 24.02 |
December | 367.67 | 23.39 | 26.83 | 23.53 | 3.00 | 23.51 |
Annual Sum or Average | 1732.33 | 23.98 | 2816.50 | 24.38 | 253.17 | 24.51 |
Minimum of Months | 39.17 | 23.30 | 26.83 | 23.53 | 0.00 | 23.51 |
Maximum of Months | 367.67 | 26.94 | 488.17 | 25.01 | 52.33 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 174.33 | 23.99 | 205.83 | 24.44 | 22.83 | 24.60 |
February | 174.67 | 23.35 | 153.67 | 23.86 | 5.83 | 23.91 |
March | 159.17 | 23.45 | 142.83 | 23.97 | 0.17 | 23.97 |
April | 88.83 | 24.24 | 183.00 | 24.64 | 7.67 | 24.72 |
May | 72.33 | 24.02 | 118.33 | 24.81 | 0.00 | 24.81 |
June | 24.17 | 25.81 | 270.67 | 24.81 | 14.67 | 24.92 |
July | 40.33 | 26.42 | 448.17 | 24.72 | 35.83 | 24.85 |
August | 32.17 | 26.84 | 486.67 | 24.59 | 31.50 | 24.72 |
September | 47.83 | 26.70 | 446.67 | 24.78 | 47.83 | 24.95 |
October | 113.50 | 24.69 | 285.17 | 24.76 | 32.00 | 24.94 |
November | 137.67 | 24.20 | 265.33 | 24.49 | 30.50 | 24.59 |
December | 237.17 | 23.81 | 146.33 | 24.28 | 22.00 | 24.42 |
Annual Sum or Average | 1302.17 | 24.19 | 3152.67 | 24.52 | 250.83 | 24.64 |
Minimum of Months | 24.17 | 23.35 | 118.33 | 23.86 | 0.00 | 23.91 |
Maximum of Months | 237.17 | 26.84 | 486.67 | 24.81 | 47.83 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 172.83 | 23.98 | 109.50 | 24.36 | 7.00 | 24.43 |
February | 54.17 | 24.04 | 218.67 | 24.47 | 3.00 | 24.50 |
March | 45.00 | 24.61 | 262.67 | 24.74 | 8.67 | 24.81 |
April | 40.67 | 27.02 | 346.83 | 25.14 | 37.50 | 25.33 |
May | 27.33 | 26.83 | 272.00 | 25.24 | 23.83 | 25.38 |
June | 40.00 | 27.10 | 423.67 | 24.88 | 40.00 | 25.06 |
July | 95.83 | 26.97 | 481.67 | 25.10 | 95.83 | 25.37 |
August | 110.67 | 26.54 | 509.67 | 24.95 | 110.67 | 25.19 |
September | 62.50 | 26.90 | 465.67 | 24.91 | 62.50 | 25.12 |
October | 68.50 | 25.22 | 302.17 | 25.00 | 27.00 | 25.14 |
November | 71.00 | 25.06 | 255.83 | 24.95 | 25.00 | 25.09 |
December | 134.00 | 24.27 | 141.83 | 24.89 | 10.17 | 24.97 |
Annual Sum or Average | 922.50 | 25.40 | 3790.17 | 24.91 | 451.17 | 25.09 |
Minimum of Months | 27.33 | 23.98 | 109.50 | 24.36 | 3.00 | 24.43 |
Maximum of Months | 172.83 | 27.10 | 509.67 | 25.24 | 110.67 | 25.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.17 | 22.54 | 30.33 | 22.39 | 30.33 | 22.26 |
February | 422.50 | 22.34 | 6.83 | 22.32 | 5.33 | 22.30 |
March | 407.33 | 22.86 | 23.83 | 22.80 | 16.00 | 22.72 |
April | 209.17 | 23.76 | 39.00 | 24.00 | 0.00 | 24.00 |
May | 102.00 | 23.96 | 62.33 | 24.74 | 0.00 | 24.74 |
June | 14.33 | 26.34 | 251.67 | 24.94 | 11.00 | 25.03 |
July | 47.50 | 26.01 | 447.33 | 24.73 | 45.00 | 24.85 |
August | 45.67 | 25.35 | 458.67 | 24.49 | 39.33 | 24.57 |
September | 48.00 | 25.81 | 406.00 | 24.66 | 44.17 | 24.78 |
October | 284.67 | 23.34 | 108.33 | 23.65 | 5.33 | 23.67 |
November | 420.83 | 22.74 | 80.67 | 22.80 | 52.50 | 22.77 |
December | 497.00 | 21.97 | 109.33 | 21.75 | 109.33 | 21.60 |
Annual Sum or Average | 3000.17 | 22.86 | 2024.33 | 23.42 | 358.33 | 23.39 |
Minimum of Months | 14.33 | 21.97 | 6.83 | 21.75 | 0.00 | 21.60 |
Maximum of Months | 501.17 | 26.34 | 458.67 | 24.94 | 109.33 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 308.50 | 22.93 | 31.50 | 22.97 | 11.83 | 22.88 |
February | 264.00 | 22.63 | 41.33 | 22.86 | 2.83 | 22.84 |
March | 235.33 | 23.09 | 65.67 | 23.42 | 6.83 | 23.36 |
April | 88.67 | 24.48 | 157.33 | 24.94 | 17.83 | 25.10 |
May | 55.67 | 25.49 | 201.33 | 25.25 | 25.67 | 25.44 |
June | 42.00 | 27.07 | 311.83 | 25.08 | 40.67 | 25.29 |
July | 69.83 | 26.70 | 394.00 | 25.09 | 69.17 | 25.30 |
August | 60.33 | 26.51 | 409.17 | 24.84 | 58.17 | 25.03 |
September | 57.67 | 26.60 | 366.33 | 24.96 | 57.33 | 25.15 |
October | 162.17 | 23.75 | 162.67 | 24.36 | 15.50 | 24.47 |
November | 271.50 | 23.14 | 76.83 | 23.37 | 26.83 | 23.38 |
December | 390.67 | 22.74 | 44.83 | 22.57 | 42.17 | 22.41 |
Annual Sum or Average | 2006.33 | 23.54 | 2262.83 | 24.15 | 374.83 | 24.26 |
Minimum of Months | 42.00 | 22.63 | 31.50 | 22.57 | 2.83 | 22.41 |
Maximum of Months | 390.67 | 27.07 | 409.17 | 25.25 | 69.17 | 25.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 216.83 | 23.66 | 210.33 | 24.21 | 29.33 | 24.32 |
February | 233.67 | 22.85 | 142.33 | 23.45 | 6.50 | 23.48 |
March | 229.33 | 23.05 | 121.33 | 23.52 | 5.83 | 23.47 |
April | 124.83 | 23.88 | 155.17 | 24.46 | 4.50 | 24.51 |
May | 97.67 | 23.93 | 101.67 | 24.71 | 0.00 | 24.71 |
June | 25.00 | 25.27 | 240.67 | 24.86 | 10.33 | 24.95 |
July | 58.83 | 25.86 | 440.33 | 24.74 | 52.50 | 24.87 |
August | 55.00 | 25.78 | 476.67 | 24.58 | 48.83 | 24.70 |
September | 56.00 | 26.52 | 438.83 | 24.82 | 56.00 | 24.99 |
October | 143.00 | 24.32 | 266.50 | 24.64 | 34.33 | 24.82 |
November | 190.00 | 23.69 | 241.50 | 24.20 | 41.67 | 24.29 |
December | 269.67 | 23.24 | 147.83 | 23.72 | 37.00 | 23.76 |
Annual Sum or Average | 1699.83 | 23.75 | 2983.17 | 24.33 | 326.83 | 24.42 |
Minimum of Months | 25.00 | 22.85 | 101.67 | 23.45 | 0.00 | 23.47 |
Maximum of Months | 269.67 | 26.52 | 476.67 | 24.86 | 56.00 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 359.83 | 23.02 | 72.67 | 23.17 | 13.33 | 23.10 |
February | 327.83 | 22.75 | 47.83 | 22.95 | 0.17 | 22.96 |
March | 264.83 | 23.12 | 90.00 | 23.43 | 7.00 | 23.40 |
April | 104.17 | 24.43 | 197.50 | 24.77 | 18.83 | 24.92 |
May | 72.83 | 24.95 | 222.33 | 25.07 | 21.17 | 25.22 |
June | 30.17 | 26.84 | 342.50 | 24.95 | 27.33 | 25.10 |
July | 71.33 | 26.64 | 464.50 | 24.96 | 69.67 | 25.16 |
August | 53.33 | 26.47 | 488.00 | 24.71 | 53.33 | 24.86 |
September | 55.67 | 26.51 | 437.67 | 24.82 | 55.67 | 24.99 |
October | 183.17 | 23.82 | 195.17 | 24.26 | 16.17 | 24.37 |
November | 283.67 | 23.22 | 136.00 | 23.59 | 30.83 | 23.62 |
December | 415.33 | 22.67 | 64.83 | 22.63 | 42.17 | 22.49 |
Annual Sum or Average | 2222.17 | 23.49 | 2759.00 | 24.10 | 355.67 | 24.20 |
Minimum of Months | 30.17 | 22.67 | 47.83 | 22.63 | 0.17 | 22.49 |
Maximum of Months | 415.33 | 26.84 | 488.00 | 25.07 | 69.67 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.95 | 106.83 | 21.62 | 106.83 | 21.40 |
February | 442.50 | 21.70 | 77.00 | 21.48 | 77.00 | 21.31 |
March | 434.33 | 22.42 | 53.67 | 22.23 | 48.67 | 22.06 |
April | 215.67 | 23.52 | 54.83 | 23.85 | 2.00 | 23.83 |
May | 105.67 | 23.88 | 89.00 | 24.64 | 0.33 | 24.65 |
June | 28.33 | 26.33 | 307.00 | 24.87 | 21.67 | 25.01 |
July | 66.00 | 25.99 | 451.17 | 24.79 | 61.67 | 24.93 |
August | 68.00 | 25.29 | 470.17 | 24.52 | 60.50 | 24.62 |
September | 84.33 | 25.26 | 412.67 | 24.65 | 68.83 | 24.77 |
October | 307.50 | 22.97 | 131.50 | 23.25 | 32.67 | 23.19 |
November | 439.33 | 22.18 | 132.67 | 22.03 | 114.33 | 21.88 |
December | 497.00 | 21.26 | 249.17 | 20.99 | 249.17 | 20.85 |
Annual Sum or Average | 3190.67 | 22.45 | 2535.67 | 22.96 | 843.67 | 22.83 |
Minimum of Months | 28.33 | 21.26 | 53.67 | 20.99 | 0.33 | 20.85 |
Maximum of Months | 502.00 | 26.33 | 470.17 | 24.87 | 249.17 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 431.33 | 22.78 | 53.67 | 22.50 | 50.83 | 22.26 |
February | 346.50 | 22.28 | 56.50 | 22.17 | 40.33 | 22.00 |
March | 295.17 | 22.86 | 70.50 | 23.00 | 17.67 | 22.88 |
April | 99.33 | 24.35 | 214.17 | 24.72 | 20.83 | 24.87 |
May | 65.50 | 25.55 | 279.00 | 24.99 | 32.67 | 25.19 |
June | 46.50 | 27.05 | 409.67 | 24.88 | 44.50 | 25.08 |
July | 78.17 | 26.69 | 469.50 | 24.97 | 77.17 | 25.18 |
August | 64.67 | 26.42 | 494.00 | 24.72 | 62.00 | 24.90 |
September | 67.17 | 26.34 | 442.50 | 24.82 | 62.00 | 25.01 |
October | 202.83 | 23.48 | 199.83 | 24.02 | 26.00 | 24.03 |
November | 348.67 | 22.77 | 95.83 | 22.77 | 59.17 | 22.66 |
December | 494.17 | 22.24 | 126.83 | 21.89 | 126.83 | 21.66 |
Annual Sum or Average | 2540.00 | 23.19 | 2912.00 | 23.75 | 620.00 | 23.75 |
Minimum of Months | 46.50 | 22.24 | 53.67 | 21.89 | 17.67 | 21.66 |
Maximum of Months | 494.17 | 27.05 | 494.00 | 24.99 | 126.83 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 247.17 | 22.97 | 190.33 | 23.49 | 38.50 | 23.45 |
February | 277.50 | 22.22 | 130.17 | 22.64 | 27.17 | 22.50 |
March | 271.17 | 22.66 | 115.83 | 22.97 | 23.83 | 22.83 |
April | 149.83 | 23.77 | 167.50 | 24.34 | 10.83 | 24.43 |
May | 109.33 | 23.92 | 134.67 | 24.61 | 3.50 | 24.65 |
June | 40.50 | 25.58 | 284.67 | 24.84 | 21.00 | 24.97 |
July | 72.17 | 25.86 | 443.83 | 24.78 | 65.50 | 24.93 |
August | 71.67 | 25.54 | 481.50 | 24.59 | 64.33 | 24.71 |
September | 71.83 | 26.02 | 436.17 | 24.81 | 67.00 | 24.97 |
October | 172.33 | 23.83 | 258.50 | 24.32 | 39.67 | 24.46 |
November | 229.67 | 23.00 | 224.00 | 23.52 | 57.00 | 23.45 |
December | 312.17 | 22.63 | 168.33 | 22.80 | 85.50 | 22.62 |
Annual Sum or Average | 2025.33 | 23.32 | 3035.50 | 23.97 | 503.83 | 23.99 |
Minimum of Months | 40.50 | 22.22 | 115.83 | 22.64 | 3.50 | 22.50 |
Maximum of Months | 312.17 | 26.02 | 481.50 | 24.84 | 85.50 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 381.17 | 22.42 | 92.17 | 22.36 | 53.17 | 22.14 |
February | 363.67 | 22.16 | 52.17 | 22.19 | 24.67 | 22.08 |
March | 314.50 | 22.71 | 100.17 | 22.91 | 26.83 | 22.78 |
April | 132.00 | 24.26 | 198.17 | 24.64 | 22.33 | 24.81 |
May | 92.00 | 24.83 | 231.83 | 24.96 | 24.17 | 25.12 |
June | 36.67 | 26.76 | 362.83 | 24.93 | 32.00 | 25.10 |
July | 83.17 | 26.46 | 464.50 | 24.97 | 79.83 | 25.17 |
August | 66.17 | 26.12 | 489.67 | 24.70 | 63.83 | 24.86 |
September | 70.83 | 26.11 | 437.83 | 24.82 | 69.00 | 24.98 |
October | 223.50 | 23.43 | 195.33 | 23.96 | 26.83 | 24.03 |
November | 317.67 | 22.67 | 148.50 | 22.88 | 65.17 | 22.76 |
December | 440.00 | 22.05 | 155.17 | 21.79 | 141.33 | 21.57 |
Annual Sum or Average | 2521.33 | 23.06 | 2928.33 | 23.71 | 629.17 | 23.70 |
Minimum of Months | 36.67 | 22.05 | 52.17 | 21.79 | 22.33 | 21.57 |
Maximum of Months | 440.00 | 26.76 | 489.67 | 24.97 | 141.33 | 25.17 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 27.00 | 502.00 | 27.00 | 2.50 | 27.00 |
February | 6.33 | 27.00 | 454.00 | 27.00 | 6.33 | 27.00 |
March | 16.50 | 27.00 | 514.00 | 27.00 | 16.50 | 27.00 |
April | 295.50 | 28.81 | 485.00 | 28.39 | 295.50 | 28.51 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 30.33 | 27.00 | 496.00 | 27.00 | 30.33 | 27.00 |
July | 269.50 | 27.00 | 497.00 | 27.00 | 269.50 | 27.00 |
August | 506.67 | 27.98 | 514.00 | 27.98 | 506.67 | 27.98 |
September | 44.50 | 27.00 | 485.00 | 27.00 | 44.50 | 27.00 |
October | 37.17 | 27.00 | 502.00 | 27.00 | 37.17 | 27.00 |
November | 51.83 | 27.00 | 489.00 | 27.00 | 51.83 | 27.00 |
December | 34.67 | 27.78 | 497.00 | 27.12 | 34.67 | 27.16 |
Annual Sum or Average | 1295.50 | 27.82 | 5943.00 | 27.30 | 1295.50 | 27.38 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 506.67 | 28.81 | 514.00 | 28.39 | 506.67 | 28.51 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 189.00 | 28.98 | 485.00 | 28.25 | 189.00 | 28.41 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 1.17 | 27.00 | 496.00 | 27.00 | 1.17 | 27.00 |
July | 27.50 | 27.00 | 497.00 | 27.00 | 27.50 | 27.00 |
August | 270.67 | 28.40 | 514.00 | 27.98 | 270.67 | 28.09 |
September | 6.33 | 27.00 | 485.00 | 27.00 | 6.33 | 27.00 |
October | 2.67 | 27.00 | 502.00 | 27.00 | 2.67 | 27.00 |
November | 5.83 | 27.00 | 489.00 | 27.00 | 5.83 | 27.00 |
December | 5.50 | 27.98 | 497.00 | 27.03 | 5.50 | 27.04 |
Annual Sum or Average | 508.67 | 28.49 | 5943.00 | 27.25 | 508.67 | 27.34 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 270.67 | 28.98 | 514.00 | 28.25 | 270.67 | 28.41 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.50 | 24.57 | 464.67 | 26.94 | 0.00 | 26.94 |
February | 0.00 | 0.00 | 447.67 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 501.17 | 27.00 | 0.00 | 27.00 |
April | 172.50 | 28.97 | 485.00 | 28.14 | 172.50 | 28.31 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 27.00 | 27.00 | 496.00 | 27.00 | 27.00 | 27.00 |
July | 111.50 | 27.00 | 497.00 | 27.00 | 111.50 | 27.00 |
August | 258.00 | 28.31 | 514.00 | 27.89 | 258.00 | 27.99 |
September | 34.67 | 27.00 | 485.00 | 27.00 | 34.67 | 27.00 |
October | 12.33 | 27.00 | 502.00 | 27.00 | 12.33 | 27.00 |
November | 7.00 | 27.00 | 476.17 | 27.00 | 7.00 | 27.00 |
December | 1.00 | 27.83 | 414.00 | 27.01 | 1.00 | 27.01 |
Annual Sum or Average | 635.50 | 28.02 | 5790.67 | 27.22 | 624.00 | 27.30 |
Minimum of Months | 0.00 | 0.00 | 414.00 | 26.94 | 0.00 | 26.94 |
Maximum of Months | 258.00 | 28.97 | 514.00 | 28.14 | 258.00 | 28.31 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 414.83 | 27.00 | 502.00 | 27.00 | 414.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 29.66 | 485.00 | 29.66 | 485.00 | 29.66 |
May | 408.50 | 27.00 | 508.00 | 27.00 | 408.50 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.07 | 497.00 | 27.07 | 497.00 | 27.07 |
August | 514.00 | 31.31 | 514.00 | 31.31 | 514.00 | 31.31 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.02 | 497.00 | 27.02 | 497.00 | 27.02 |
Annual Sum or Average | 5756.33 | 27.62 | 5943.00 | 27.61 | 5756.33 | 27.61 |
Minimum of Months | 408.50 | 27.00 | 454.00 | 27.00 | 408.50 | 27.00 |
Maximum of Months | 514.00 | 31.31 | 514.00 | 31.31 | 514.00 | 31.31 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 22.79556 | 0.81812 | 19.20534 |
February | 454.00000 | 27.00022 | 29.34135 | 0.89120 | 21.83103 |
March | 514.00000 | 27.00003 | 26.49944 | 0.91427 | 22.73576 |
April | 485.00000 | 28.13931 | 18.11040 | 1.11228 | 31.72160 |
May | 508.00000 | 27.00000 | 17.52327 | 0.15330 | 5.55515 |
June | 496.00000 | 27.00000 | 23.67504 | 0.26828 | 6.59703 |
July | 497.00000 | 27.00047 | 33.24134 | 0.38590 | 8.20338 |
August | 514.00000 | 27.97037 | 33.76002 | 0.69860 | 16.77258 |
September | 485.00000 | 27.00067 | 34.57448 | 0.29861 | 6.93359 |
October | 502.00000 | 27.00010 | 25.23280 | 0.89895 | 22.20388 |
November | 489.00000 | 27.00014 | 24.63886 | 0.91251 | 22.70796 |
December | 497.00000 | 27.07284 | 17.32343 | 0.87688 | 21.39296 |
Annual Sum or Average | 5943.00000 | 27.18313 | 25.53937 | 0.68394 | 17.10609 |
Minimum of Months | 454.00000 | 27.00000 | 17.32343 | 0.15330 | 5.55515 |
Maximum of Months | 514.00000 | 28.13931 | 34.57448 | 1.11228 | 31.72160 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 22.77765 | 0.74643 | 16.86030 |
February | 454.00000 | 27.00021 | 29.35685 | 0.79985 | 18.58388 |
March | 514.00000 | 27.00003 | 26.47037 | 0.81845 | 19.25540 |
April | 485.00000 | 27.96502 | 18.17105 | 0.98926 | 26.35454 |
May | 508.00000 | 27.00000 | 17.49716 | 0.10368 | 5.30595 |
June | 496.00000 | 27.00000 | 23.65465 | 0.20300 | 5.96418 |
July | 497.00000 | 27.00030 | 33.25001 | 0.28986 | 6.84856 |
August | 514.00000 | 27.76156 | 33.94892 | 0.49882 | 11.43706 |
September | 485.00000 | 27.00059 | 34.64050 | 0.24365 | 6.31876 |
October | 502.00000 | 27.00010 | 25.21068 | 0.82835 | 19.64882 |
November | 489.00000 | 27.00013 | 24.62455 | 0.80788 | 18.94535 |
December | 497.00000 | 27.02016 | 17.33322 | 0.72424 | 16.22992 |
Annual Sum or Average | 5943.00000 | 27.14642 | 25.55776 | 0.58575 | 14.26469 |
Minimum of Months | 454.00000 | 27.00000 | 17.33322 | 0.10368 | 5.30595 |
Maximum of Months | 514.00000 | 27.96502 | 34.64050 | 0.98926 | 26.35454 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.94182 | 22.97398 | 0.68892 | 15.42011 |
February | 454.00000 | 27.00021 | 29.40099 | 0.74736 | 16.96924 |
March | 514.00000 | 27.00003 | 26.49139 | 0.78665 | 18.28126 |
April | 485.00000 | 27.83823 | 18.25354 | 0.96698 | 25.60862 |
May | 508.00000 | 27.00000 | 17.50870 | 0.11592 | 5.43813 |
June | 496.00000 | 27.00000 | 23.66526 | 0.23114 | 6.28719 |
July | 497.00000 | 27.00132 | 33.25424 | 0.31749 | 7.26052 |
August | 514.00000 | 27.67253 | 34.02598 | 0.49696 | 11.62318 |
September | 485.00000 | 27.00062 | 34.63468 | 0.25735 | 6.51654 |
October | 502.00000 | 27.00010 | 25.22691 | 0.81135 | 19.15359 |
November | 489.00000 | 27.00013 | 24.64446 | 0.76505 | 17.65125 |
December | 497.00000 | 27.00526 | 17.35229 | 0.65342 | 14.28849 |
Annual Sum or Average | 5943.00000 | 27.12230 | 25.59929 | 0.56810 | 13.66885 |
Minimum of Months | 454.00000 | 26.94182 | 17.35229 | 0.11592 | 5.43813 |
Maximum of Months | 514.00000 | 27.83823 | 34.63468 | 0.96698 | 25.60862 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99995 | 25.61923 | 1.03844 | 27.80996 |
February | 454.00000 | 27.00015 | 31.01720 | 1.21377 | 35.94334 |
March | 514.00000 | 27.00146 | 25.76938 | 1.31068 | 40.84948 |
April | 485.00000 | 29.66361 | 16.72575 | 1.88084 | 67.79841 |
May | 508.00000 | 27.00051 | 26.50517 | 0.45113 | 9.34811 |
June | 496.00000 | 27.00303 | 29.56300 | 0.70027 | 15.34272 |
July | 497.00000 | 27.07354 | 36.04589 | 1.00433 | 26.51282 |
August | 514.00000 | 31.31246 | 32.11676 | 2.37732 | 84.41767 |
September | 485.00000 | 27.00127 | 38.34287 | 0.63716 | 13.66609 |
October | 502.00000 | 27.00117 | 27.41613 | 1.24666 | 37.61521 |
November | 489.00000 | 27.00249 | 25.50139 | 1.36304 | 43.60384 |
December | 497.00000 | 27.02458 | 17.87673 | 1.42129 | 46.66255 |
Annual Sum or Average | 5943.00000 | 27.59939 | 27.69055 | 1.22221 | 37.54140 |
Minimum of Months | 454.00000 | 26.99995 | 16.72575 | 0.45113 | 9.34811 |
Maximum of Months | 514.00000 | 31.31246 | 38.34287 | 2.37732 | 84.41767 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.56094 | 20.54499 | 0.36820 | 8.46174 |
February | 454.00000 | 24.48522 | 32.71344 | 0.42868 | 9.46361 |
March | 514.00000 | 24.39428 | 26.07288 | 0.36391 | 8.19813 |
April | 485.00000 | 24.52758 | 18.69869 | 0.34906 | 8.00732 |
May | 508.00000 | 24.48659 | 18.09880 | -0.5236 | 11.56746 |
June | 496.00000 | 24.45330 | 25.57537 | -0.4712 | 10.59146 |
July | 497.00000 | 24.62699 | 45.42845 | -0.2643 | 7.76171 |
August | 514.00000 | 24.49262 | 47.90845 | -0.2663 | 7.63703 |
September | 485.00000 | 24.57848 | 47.01392 | -0.2528 | 7.93828 |
October | 502.00000 | 24.62096 | 26.63217 | 0.44513 | 10.05062 |
November | 489.00000 | 24.62155 | 26.42303 | 0.44194 | 10.08443 |
December | 497.00000 | 24.60830 | 14.63362 | 0.34706 | 8.21877 |
Annual Sum or Average | 5943.00000 | 24.53775 | 29.12387 | 0.07696 | 8.99643 |
Minimum of Months | 454.00000 | 24.39428 | 14.63362 | -0.5236 | 7.63703 |
Maximum of Months | 514.00000 | 24.62699 | 47.90845 | 0.44513 | 11.56746 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.33725 | 21.99624 | 0.33198 | 7.59343 |
February | 454.00000 | 24.34236 | 34.10691 | 0.41498 | 8.98178 |
March | 514.00000 | 24.29166 | 26.92444 | 0.36834 | 8.13171 |
April | 485.00000 | 24.25478 | 19.94500 | 0.33575 | 7.50978 |
May | 508.00000 | 24.27434 | 19.38346 | -0.5407 | 11.42469 |
June | 496.00000 | 24.18869 | 27.40767 | -0.4941 | 10.36468 |
July | 497.00000 | 24.26477 | 45.62088 | -0.3352 | 7.72730 |
August | 514.00000 | 24.25379 | 47.66819 | -0.3015 | 7.29795 |
September | 485.00000 | 24.32109 | 47.10528 | -0.3227 | 7.80001 |
October | 502.00000 | 24.38802 | 27.81068 | 0.40749 | 8.96404 |
November | 489.00000 | 24.40340 | 27.16585 | 0.40346 | 8.98520 |
December | 497.00000 | 24.41522 | 16.19345 | 0.32098 | 7.50879 |
Annual Sum or Average | 5943.00000 | 24.31084 | 30.08488 | 0.04557 | 8.52371 |
Minimum of Months | 454.00000 | 24.18869 | 16.19345 | -0.5407 | 7.29795 |
Maximum of Months | 514.00000 | 24.41522 | 47.66819 | 0.41498 | 11.42469 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.00662 | 23.80714 | 0.23194 | 6.53145 |
February | 454.00000 | 24.04254 | 36.31447 | 0.32105 | 7.33957 |
March | 514.00000 | 24.12976 | 28.21180 | 0.29881 | 7.09239 |
April | 485.00000 | 24.18517 | 20.19483 | 0.28181 | 6.81222 |
May | 508.00000 | 24.21337 | 19.42630 | -0.5863 | 12.43609 |
June | 496.00000 | 24.13621 | 27.17507 | -0.5438 | 11.34079 |
July | 497.00000 | 24.20475 | 46.13451 | -0.3978 | 8.66136 |
August | 514.00000 | 24.17860 | 48.86235 | -0.3839 | 8.38413 |
September | 485.00000 | 24.28671 | 47.33294 | -0.3646 | 8.33950 |
October | 502.00000 | 24.24688 | 28.47832 | 0.34667 | 7.89852 |
November | 489.00000 | 24.17198 | 28.70900 | 0.31367 | 7.61983 |
December | 497.00000 | 23.96321 | 18.22479 | 0.17543 | 5.86184 |
Annual Sum or Average | 5943.00000 | 24.14765 | 31.04052 | -0.0290 | 8.20566 |
Minimum of Months | 454.00000 | 23.96321 | 18.22479 | -0.5863 | 5.86184 |
Maximum of Months | 514.00000 | 24.28671 | 48.86235 | 0.34667 | 12.43609 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.31779 | 24.63715 | 0.04588 | 6.61871 |
February | 454.00000 | 23.26739 | 38.17261 | 0.11486 | 6.21092 |
March | 514.00000 | 23.74210 | 29.19731 | 0.19145 | 6.48940 |
April | 485.00000 | 24.16116 | 20.31946 | 0.27947 | 6.85295 |
May | 508.00000 | 24.23501 | 19.53681 | -0.5640 | 11.97464 |
June | 496.00000 | 24.20697 | 27.12449 | -0.4893 | 10.39267 |
July | 497.00000 | 24.30328 | 45.94137 | -0.3373 | 7.95902 |
August | 514.00000 | 24.22697 | 48.91742 | -0.3437 | 7.87335 |
September | 485.00000 | 24.32988 | 47.53750 | -0.3341 | 8.03618 |
October | 502.00000 | 24.04937 | 28.94063 | 0.29095 | 7.43111 |
November | 489.00000 | 23.58453 | 29.93552 | 0.15661 | 6.89609 |
December | 497.00000 | 22.89711 | 19.31266 | -0.1047 | 6.58291 |
Annual Sum or Average | 5943.00000 | 23.86428 | 31.58946 | -0.0935 | 7.79301 |
Minimum of Months | 454.00000 | 22.89711 | 19.31266 | -0.5640 | 6.21092 |
Maximum of Months | 514.00000 | 24.32988 | 48.91742 | 0.29095 | 11.97464 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.62183 | 22.84264 | 0.12082 | 5.74621 |
February | 454.00000 | 23.58350 | 35.35595 | 0.19051 | 6.26018 |
March | 514.00000 | 23.86230 | 27.14775 | 0.22832 | 6.64557 |
April | 485.00000 | 24.28018 | 19.19750 | 0.33474 | 7.76402 |
May | 508.00000 | 24.38548 | 18.22230 | -0.4734 | 10.42601 |
June | 496.00000 | 24.42671 | 25.83762 | -0.3286 | 8.41175 |
July | 497.00000 | 24.52131 | 44.19102 | -0.1823 | 6.90580 |
August | 514.00000 | 24.39100 | 46.48355 | -0.2065 | 6.89520 |
September | 485.00000 | 24.44619 | 46.05337 | -0.2486 | 7.44436 |
October | 502.00000 | 24.18694 | 27.48484 | 0.33549 | 8.22177 |
November | 489.00000 | 23.87987 | 27.59138 | 0.23319 | 6.89773 |
December | 497.00000 | 23.56210 | 16.90503 | 0.06224 | 5.78101 |
Annual Sum or Average | 5943.00000 | 24.09887 | 29.73893 | 0.00326 | 7.29212 |
Minimum of Months | 454.00000 | 23.56210 | 16.90503 | -0.4734 | 5.74621 |
Maximum of Months | 514.00000 | 24.52131 | 46.48355 | 0.33549 | 10.42601 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.91345 | 21.65327 | 0.22298 | 6.83779 |
February | 454.00000 | 23.73762 | 34.45307 | 0.25609 | 7.32590 |
March | 514.00000 | 23.98075 | 26.51625 | 0.29222 | 7.65990 |
April | 485.00000 | 24.38121 | 18.76504 | 0.42507 | 9.73702 |
May | 508.00000 | 24.49689 | 17.88123 | -0.3270 | 8.96712 |
June | 496.00000 | 24.46354 | 25.62540 | -0.2172 | 7.81309 |
July | 497.00000 | 24.55854 | 43.96729 | -0.0905 | 6.89589 |
August | 514.00000 | 24.40076 | 46.28261 | -0.1329 | 6.92397 |
September | 485.00000 | 24.49379 | 45.66828 | -0.1616 | 7.15858 |
October | 502.00000 | 24.31725 | 26.83286 | 0.41760 | 9.97085 |
November | 489.00000 | 23.99461 | 27.06090 | 0.28963 | 7.64164 |
December | 497.00000 | 23.69048 | 16.38984 | 0.11431 | 6.43008 |
Annual Sum or Average | 5943.00000 | 24.20539 | 29.22340 | 0.08870 | 7.78138 |
Minimum of Months | 454.00000 | 23.69048 | 16.38984 | -0.3270 | 6.43008 |
Maximum of Months | 514.00000 | 24.55854 | 46.28261 | 0.42507 | 9.97085 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.23577 | 20.62274 | 0.38619 | 9.79526 |
February | 454.00000 | 23.87169 | 33.77662 | 0.32312 | 8.33630 |
March | 514.00000 | 24.02400 | 26.33374 | 0.31788 | 8.07090 |
April | 485.00000 | 24.37012 | 18.88037 | 0.40560 | 9.24123 |
May | 508.00000 | 24.39638 | 18.15977 | -0.4532 | 10.30704 |
June | 496.00000 | 24.40125 | 25.89602 | -0.3483 | 8.71887 |
July | 497.00000 | 24.51916 | 44.17014 | -0.1787 | 7.08090 |
August | 514.00000 | 24.41335 | 46.32651 | -0.1625 | 6.79846 |
September | 485.00000 | 24.52826 | 45.59182 | -0.1418 | 7.12449 |
October | 502.00000 | 24.45445 | 26.38972 | 0.49637 | 11.71584 |
November | 489.00000 | 24.30251 | 26.10434 | 0.43660 | 10.33405 |
December | 497.00000 | 24.12768 | 15.17121 | 0.30131 | 9.00936 |
Annual Sum or Average | 5943.00000 | 24.30600 | 28.92116 | 0.11256 | 8.88006 |
Minimum of Months | 454.00000 | 23.87169 | 15.17121 | -0.4532 | 6.79846 |
Maximum of Months | 514.00000 | 24.52826 | 46.32651 | 0.49637 | 11.71584 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.24879 | 21.05007 | 0.33677 | 8.14480 |
February | 454.00000 | 24.29477 | 32.95332 | 0.42161 | 9.21651 |
March | 514.00000 | 24.41308 | 25.47347 | 0.45911 | 10.14757 |
April | 485.00000 | 24.65526 | 18.32676 | 0.59697 | 13.73856 |
May | 508.00000 | 24.58570 | 17.76134 | -0.2572 | 8.42653 |
June | 496.00000 | 24.57300 | 25.42587 | -0.1070 | 7.43561 |
July | 497.00000 | 24.71134 | 43.53655 | 0.04178 | 7.37050 |
August | 514.00000 | 24.59470 | 45.64005 | 0.09031 | 7.41335 |
September | 485.00000 | 24.61849 | 45.32237 | -0.0719 | 7.11578 |
October | 502.00000 | 24.59473 | 26.22477 | 0.53060 | 12.19111 |
November | 489.00000 | 24.52751 | 25.72477 | 0.49024 | 11.17052 |
December | 497.00000 | 24.50099 | 14.80062 | 0.37985 | 8.94013 |
Annual Sum or Average | 5943.00000 | 24.52756 | 28.49099 | 0.24053 | 9.26655 |
Minimum of Months | 454.00000 | 24.24879 | 14.80062 | -0.2572 | 7.11578 |
Maximum of Months | 514.00000 | 24.71134 | 45.64005 | 0.59697 | 13.73856 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.53884 | 25.39695 | -0.1408 | 6.99104 |
February | 454.00000 | 22.45092 | 39.14104 | -0.0810 | 6.23702 |
March | 514.00000 | 23.10953 | 29.22512 | 0.03195 | 6.47522 |
April | 485.00000 | 24.09270 | 19.30479 | 0.25603 | 6.89037 |
May | 508.00000 | 24.34900 | 17.97998 | -0.5089 | 11.16759 |
June | 496.00000 | 24.44337 | 25.19668 | -0.3458 | 8.66943 |
July | 497.00000 | 24.54511 | 44.39435 | -0.2061 | 7.16682 |
August | 514.00000 | 24.36922 | 47.35861 | -0.2622 | 7.32473 |
September | 485.00000 | 24.43502 | 46.32933 | -0.2760 | 7.81026 |
October | 502.00000 | 23.74465 | 28.42862 | 0.21091 | 7.45846 |
November | 489.00000 | 22.92568 | 30.04533 | -0.0087 | 6.93068 |
December | 497.00000 | 21.97088 | 19.18730 | -0.3261 | 8.59167 |
Annual Sum or Average | 5943.00000 | 23.58899 | 30.94577 | -0.1394 | 7.65648 |
Minimum of Months | 454.00000 | 21.97088 | 17.97998 | -0.5089 | 6.23702 |
Maximum of Months | 514.00000 | 24.54511 | 47.35861 | 0.25603 | 11.16759 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.30782 | 23.18704 | 0.06241 | 6.81508 |
February | 385.00000 | 23.13160 | 36.69387 | 0.09983 | 6.84418 |
March | 433.00000 | 23.66686 | 27.13537 | 0.19285 | 7.37730 |
April | 410.00000 | 24.50155 | 17.96333 | 0.42592 | 10.07246 |
May | 430.00000 | 24.61434 | 17.03988 | -0.3112 | 9.27281 |
June | 418.00000 | 24.60809 | 24.41715 | -0.1863 | 8.07681 |
July | 422.00000 | 24.75197 | 43.38610 | -0.0489 | 7.34408 |
August | 433.00000 | 24.56299 | 46.06521 | -0.1091 | 7.25455 |
September | 410.00000 | 24.62298 | 45.32934 | -0.1459 | 7.56079 |
October | 427.00000 | 24.20935 | 26.59936 | 0.36502 | 9.74302 |
November | 417.00000 | 23.53384 | 28.25743 | 0.15900 | 7.08030 |
December | 422.00000 | 22.86252 | 17.42773 | -0.1046 | 7.15544 |
Annual Sum or Average | 5034.00000 | 24.03603 | 29.40248 | 0.03215 | 7.88741 |
Minimum of Months | 385.00000 | 22.86252 | 17.03988 | -0.3112 | 6.81508 |
Maximum of Months | 433.00000 | 24.75197 | 46.06521 | 0.42592 | 10.07246 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.07268 | 21.55026 | 0.35175 | 10.15438 |
February | 454.00000 | 23.52128 | 35.51305 | 0.24160 | 8.19870 |
March | 514.00000 | 23.72109 | 27.24159 | 0.23415 | 7.75363 |
April | 485.00000 | 24.30121 | 18.71937 | 0.36254 | 8.69401 |
May | 508.00000 | 24.37293 | 17.89596 | -0.4803 | 10.91789 |
June | 496.00000 | 24.41300 | 25.26680 | -0.3694 | 9.02043 |
July | 497.00000 | 24.54104 | 44.38391 | -0.2021 | 7.32522 |
August | 514.00000 | 24.41255 | 47.09570 | -0.2032 | 7.09534 |
September | 485.00000 | 24.54296 | 45.70513 | -0.1495 | 7.34630 |
October | 502.00000 | 24.36157 | 26.51115 | 0.46630 | 11.57105 |
November | 489.00000 | 24.08320 | 26.90950 | 0.37734 | 10.01768 |
December | 497.00000 | 23.78112 | 16.02248 | 0.21175 | 9.23589 |
Annual Sum or Average | 5943.00000 | 24.18069 | 29.36382 | 0.06759 | 8.95006 |
Minimum of Months | 454.00000 | 23.52128 | 16.02248 | -0.4803 | 7.09534 |
Maximum of Months | 514.00000 | 24.54296 | 47.09570 | 0.46630 | 11.57105 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.39753 | 23.47050 | 0.10233 | 7.18831 |
February | 454.00000 | 23.13499 | 37.09236 | 0.10609 | 6.59049 |
March | 514.00000 | 23.65184 | 27.76677 | 0.20283 | 7.37616 |
April | 485.00000 | 24.42504 | 18.57529 | 0.43134 | 10.04749 |
May | 508.00000 | 24.51056 | 17.61911 | -0.3355 | 9.42531 |
June | 496.00000 | 24.54124 | 24.92343 | -0.1944 | 7.91989 |
July | 497.00000 | 24.65290 | 44.03367 | -0.0871 | 7.35616 |
August | 514.00000 | 24.48782 | 46.85042 | -0.1198 | 7.13705 |
September | 485.00000 | 24.54827 | 45.82501 | -0.1549 | 7.39665 |
October | 502.00000 | 24.15515 | 27.29607 | 0.36590 | 9.47808 |
November | 489.00000 | 23.65842 | 28.18098 | 0.20894 | 7.87042 |
December | 497.00000 | 22.94140 | 17.63431 | -0.0694 | 7.34900 |
Annual Sum or Average | 5943.00000 | 24.01443 | 29.89301 | 0.03659 | 7.93408 |
Minimum of Months | 454.00000 | 22.94140 | 17.61911 | -0.3355 | 6.59049 |
Maximum of Months | 514.00000 | 24.65290 | 46.85042 | 0.43134 | 10.04749 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.94513 | 25.61733 | -0.3047 | 9.44155 |
February | 454.00000 | 21.75429 | 40.14226 | -0.2684 | 8.31746 |
March | 514.00000 | 22.67499 | 29.80257 | -0.0841 | 7.54016 |
April | 485.00000 | 24.00181 | 19.55505 | 0.23969 | 7.20355 |
May | 508.00000 | 24.33576 | 18.23228 | -0.4987 | 11.31224 |
June | 496.00000 | 24.46073 | 25.47488 | -0.3104 | 8.43490 |
July | 497.00000 | 24.56674 | 44.52395 | -0.1715 | 7.21373 |
August | 514.00000 | 24.38240 | 47.62182 | -0.2353 | 7.28293 |
September | 485.00000 | 24.43673 | 46.76523 | -0.2591 | 7.87866 |
October | 502.00000 | 23.46492 | 28.80282 | 0.13972 | 7.92207 |
November | 489.00000 | 22.36923 | 30.76016 | -0.1575 | 8.59059 |
December | 497.00000 | 21.25709 | 19.10404 | -0.5312 | 12.99373 |
Annual Sum or Average | 5943.00000 | 23.31492 | 31.30865 | -0.2039 | 8.68262 |
Minimum of Months | 454.00000 | 21.25709 | 18.23228 | -0.5312 | 7.20355 |
Maximum of Months | 514.00000 | 24.56674 | 47.62182 | 0.23969 | 12.99373 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.95831 | 23.44215 | -0.0403 | 7.58555 |
February | 454.00000 | 22.70107 | 37.47981 | -0.0245 | 7.36842 |
March | 514.00000 | 23.42655 | 27.76173 | 0.13015 | 7.36755 |
April | 485.00000 | 24.37705 | 18.54941 | 0.42203 | 10.06747 |
May | 508.00000 | 24.51203 | 17.75548 | -0.3037 | 9.02668 |
June | 496.00000 | 24.52238 | 25.20195 | -0.1589 | 7.71320 |
July | 497.00000 | 24.64705 | 44.13090 | -0.0293 | 7.27117 |
August | 514.00000 | 24.47792 | 47.05059 | -0.0852 | 7.04361 |
September | 485.00000 | 24.52600 | 46.13648 | -0.1359 | 7.40607 |
October | 502.00000 | 24.01275 | 27.24839 | 0.32744 | 9.63865 |
November | 489.00000 | 23.14493 | 28.91189 | 0.05469 | 7.32695 |
December | 497.00000 | 22.25146 | 17.99263 | -0.2762 | 9.25702 |
Annual Sum or Average | 5943.00000 | 23.80419 | 30.08951 | -0.0106 | 8.09061 |
Minimum of Months | 454.00000 | 22.25146 | 17.75548 | -0.3037 | 7.04361 |
Maximum of Months | 514.00000 | 24.64705 | 47.05059 | 0.42203 | 10.06747 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.64832 | 21.52177 | 0.22447 | 9.78411 |
February | 454.00000 | 22.99320 | 36.16533 | 0.08997 | 8.33989 |
March | 514.00000 | 23.40251 | 27.72602 | 0.14242 | 7.97553 |
April | 485.00000 | 24.20972 | 18.98669 | 0.34688 | 8.92806 |
May | 508.00000 | 24.34318 | 18.17584 | -0.4746 | 11.22757 |
June | 496.00000 | 24.43197 | 25.54307 | -0.3337 | 8.78638 |
July | 497.00000 | 24.55927 | 44.53025 | -0.1686 | 7.41510 |
August | 514.00000 | 24.42028 | 47.39715 | -0.1780 | 7.14446 |
September | 485.00000 | 24.53733 | 46.20154 | -0.1343 | 7.50982 |
October | 502.00000 | 24.15461 | 26.83676 | 0.41129 | 11.32418 |
November | 489.00000 | 23.69505 | 27.40648 | 0.26440 | 9.46015 |
December | 497.00000 | 23.27380 | 15.84549 | 0.05028 | 9.60321 |
Annual Sum or Average | 5943.00000 | 23.97841 | 29.65436 | 0.01829 | 8.96390 |
Minimum of Months | 454.00000 | 22.99320 | 15.84549 | -0.4746 | 7.14446 |
Maximum of Months | 514.00000 | 24.55927 | 47.39715 | 0.41129 | 11.32418 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.88308 | 23.60783 | -0.0383 | 8.34622 |
February | 454.00000 | 22.54377 | 37.85054 | -0.0525 | 7.36304 |
March | 514.00000 | 23.29390 | 28.27501 | 0.10660 | 7.77633 |
April | 485.00000 | 24.34980 | 18.83536 | 0.41810 | 10.19775 |
May | 508.00000 | 24.49267 | 17.90084 | -0.3273 | 9.67577 |
June | 496.00000 | 24.54739 | 25.24845 | -0.1639 | 7.97499 |
July | 497.00000 | 24.65851 | 44.21417 | -0.0592 | 7.56502 |
August | 514.00000 | 24.48934 | 47.17220 | -0.0981 | 7.28537 |
September | 485.00000 | 24.54742 | 46.28707 | -0.1393 | 7.52592 |
October | 502.00000 | 23.93104 | 27.63374 | 0.30863 | 9.59457 |
November | 489.00000 | 23.22033 | 28.72265 | 0.08969 | 8.30330 |
December | 497.00000 | 22.31089 | 17.52096 | -0.2476 | 9.63648 |
Annual Sum or Average | 5943.00000 | 23.78052 | 30.22316 | -0.0176 | 8.44138 |
Minimum of Months | 454.00000 | 22.31089 | 17.52096 | -0.3273 | 7.28537 |
Maximum of Months | 514.00000 | 24.65851 | 47.17220 | 0.41810 | 10.19775 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.671526E+11 | 142405.74 | 17-JAN-15:30 | 312.19 | 0.442588E+12 | 0.00 | 0.509740E+12 | 2.45 | 7.57 | 18-JAN-14:40 | 0.00 | 0.00 |
February | 0.285266E+11 | 102879.61 | 21-FEB-15:30 | 206.18 | 0.164483E+12 | 0.00 | 0.193010E+12 | 1.58 | 7.45 | 21-FEB-15:30 | 0.00 | 0.00 |
March | 0.658225E+11 | 151690.22 | 17-MAR-12:50 | 350.75 | 0.421225E+12 | 0.00 | 0.487047E+12 | 2.64 | 7.57 | 15-MAR-13:40 | 0.00 | 0.00 |
April | 0.127410E+12 | 148683.99 | 25-APR-17:00 | 592.55 | 0.873578E+12 | 0.00 | 0.100099E+13 | 4.92 | 7.57 | 17-APR-17:10 | 0.00 | 0.00 |
May | 0.149200E+12 | 148808.74 | 30-MAY-09:20 | 543.25 | 0.103707E+13 | 0.00 | 0.118627E+13 | 4.75 | 7.57 | 30-MAY-19:00 | 0.00 | 0.00 |
June | 0.178781E+12 | 160535.00 | 17-JUN-13:20 | 674.75 | 0.123604E+13 | 0.00 | 0.141482E+13 | 6.00 | 7.58 | 19-JUN-04:13 | 0.00 | 0.00 |
July | 0.189087E+12 | 164496.66 | 15-JUL-10:20 | 693.26 | 0.128915E+13 | 0.00 | 0.147824E+13 | 5.85 | 7.57 | 01-JUL-09:40 | 0.00 | 0.00 |
August | 0.189649E+12 | 161359.33 | 29-AUG-18:20 | 694.14 | 0.130289E+13 | 0.00 | 0.149254E+13 | 5.89 | 7.57 | 24-AUG-19:13 | 0.00 | 0.00 |
September | 0.162514E+12 | 159136.59 | 12-SEP-07:30 | 552.54 | 0.112511E+13 | 0.00 | 0.128763E+13 | 4.97 | 7.57 | 28-SEP-08:20 | 0.00 | 0.00 |
October | 0.108895E+12 | 159567.66 | 03-OCT-16:50 | 464.48 | 0.732049E+12 | 0.00 | 0.840944E+12 | 3.78 | 7.57 | 19-OCT-12:05 | 0.00 | 0.00 |
November | 0.673163E+11 | 153440.60 | 01-NOV-16:50 | 337.36 | 0.440489E+12 | 0.00 | 0.507805E+12 | 2.64 | 7.57 | 20-NOV-17:00 | 0.00 | 0.00 |
December | 0.459972E+11 | 153831.43 | 22-DEC-16:30 | 285.15 | 0.277407E+12 | 0.00 | 0.323405E+12 | 2.03 | 7.57 | 22-DEC-14:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.138035E+13 | 5706.60 | 0.934208E+13 | 0.00 | 0.107224E+14 | 3.97 | 0.00 | 0.00 | ||||
Minimum of Months | 0.285266E+11 | 102879.61 | 206.18 | 0.164483E+12 | 0.00 | 0.193010E+12 | 1.58 | 7.45 | 0.00 | 0.00 | ||
Maximum of Months | 0.189649E+12 | 164496.66 | 694.14 | 0.130289E+13 | 0.00 | 0.149254E+13 | 6.00 | 7.58 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.159406E+10 | 108115.70 | 31-JAN-15:05 | 6.08 | 0.109483E+11 | 0.00 | 0.125423E+11 | 0.05 | 7.45 | 31-JAN-15:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.137184E+10 | 105020.84 | 23-MAR-14:05 | 4.75 | 0.967184E+10 | 0.00 | 0.110437E+11 | 0.04 | 7.46 | 16-MAR-14:05 | 0.00 | 0.00 |
April | 0.335551E+11 | 108306.76 | 03-APR-12:05 | 106.42 | 0.242207E+12 | 0.00 | 0.275762E+12 | 1.06 | 7.49 | 03-APR-12:05 | 0.00 | 0.00 |
May | 0.537894E+11 | 110390.67 | 25-MAY-12:05 | 170.17 | 0.388482E+12 | 0.00 | 0.442271E+12 | 1.64 | 7.51 | 25-MAY-12:05 | 0.00 | 0.00 |
June | 0.922441E+11 | 132660.43 | 19-JUN-14:50 | 271.92 | 0.667989E+12 | 0.00 | 0.760233E+12 | 2.72 | 7.50 | 05-JUN-15:10 | 0.00 | 0.00 |
July | 0.836834E+11 | 160171.74 | 18-JUL-05:03 | 235.84 | 0.591107E+12 | 0.00 | 0.674791E+12 | 2.23 | 7.53 | 14-JUL-05:03 | 0.00 | 0.00 |
August | 0.896971E+11 | 160145.86 | 01-AUG-05:02 | 250.64 | 0.634190E+12 | 0.00 | 0.723887E+12 | 2.37 | 7.50 | 24-AUG-15:20 | 0.00 | 0.00 |
September | 0.646133E+11 | 153407.34 | 12-SEP-05:03 | 184.96 | 0.457792E+12 | 0.00 | 0.522405E+12 | 1.81 | 7.47 | 28-SEP-15:20 | 0.00 | 0.00 |
October | 0.269180E+11 | 117760.02 | 03-OCT-11:00 | 81.56 | 0.192597E+12 | 0.00 | 0.219515E+12 | 0.78 | 7.52 | 10-OCT-08:55 | 0.00 | 0.00 |
November | 0.346714E+10 | 113369.28 | 02-NOV-14:05 | 12.25 | 0.244085E+11 | 0.00 | 0.278756E+11 | 0.12 | 7.52 | 02-NOV-14:05 | 0.00 | 0.00 |
December | 0.124429E+09 | 86903.84 | 22-DEC-16:00 | 0.50 | 0.834720E+09 | 0.00 | 0.959149E+09 | 0.00 | 7.21 | 22-DEC-16:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.451058E+12 | 1325.07 | 0.322023E+13 | 0.00 | 0.367128E+13 | 1.07 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.922441E+11 | 160171.74 | 271.92 | 0.667989E+12 | 0.00 | 0.760233E+12 | 2.72 | 7.53 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.439980E+11 | 744.00 | 43776.24 | 02-JAN-12:10 | 232405.61 | 31-JAN-17:30 | 20.48 | 19.62 | 14.32 |
February | 0.196643E+11 | 672.00 | 43776.24 | 06-FEB-14:00 | 184202.30 | 18-FEB-14:05 | 19.66 | 18.48 | 14.32 |
March | 0.596797E+11 | 744.00 | 43776.24 | 01-MAR-10:00 | 522965.50 | 16-MAR-16:00 | 24.21 | 20.62 | 14.32 |
April | 0.106049E+12 | 720.00 | 43776.24 | 01-APR-07:05 | 628853.07 | 25-APR-18:15 | 37.20 | 27.93 | 14.32 |
May | 0.110613E+12 | 744.00 | 43776.24 | 01-MAY-00:10 | 355760.12 | 31-MAY-23:15 | 30.80 | 27.81 | 14.32 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:05 | 516289.04 | 30-JUN-23:13 | 41.25 | 34.36 | 14.32 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:05 | 711619.72 | 13-JUL-17:53 | 45.93 | 35.32 | 14.32 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 739805.22 | 05-AUG-16:43 | 48.65 | 35.78 | 14.32 |
September | 0.112995E+12 | 720.00 | 43776.24 | 01-SEP-00:10 | 338217.29 | 04-SEP-10:20 | 32.89 | 29.36 | 14.32 |
October | 0.847264E+11 | 744.00 | 43776.24 | 01-OCT-00:10 | 500831.53 | 03-OCT-08:30 | 27.75 | 24.01 | 14.32 |
November | 0.598819E+11 | 720.00 | 43776.24 | 01-NOV-00:10 | 541061.33 | 09-NOV-17:00 | 24.21 | 20.48 | 14.32 |
December | 0.480202E+11 | 744.00 | 43776.24 | 01-DEC-09:50 | 597905.96 | 25-DEC-16:01 | 23.79 | 19.66 | 14.32 |
Annual Sum or Average | 0.993596E+12 | 8760.00 | 31.47 | 26.16 | 14.32 | ||||
Minimum of Months | 0.196643E+11 | 672.00 | 43776.24 | 184202.30 | 19.66 | 18.48 | 14.32 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 739805.22 | 48.65 | 35.78 | 14.32 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.563790E+09 | 245.33 | 2430.43 | 26-JAN-14:00 | 1228644.01 | 30-JAN-15:40 | 22.00 | 21.17 | 21.64 |
February | 0.183104E+09 | 137.78 | 1571.37 | 21-FEB-15:05 | 877050.92 | 21-FEB-15:30 | 21.44 | 21.09 | 14.71 |
March | 0.994933E+09 | 255.99 | 16791.28 | 14-MAR-14:00 | 1275759.47 | 17-MAR-13:05 | 21.91 | 21.11 | 23.60 |
April | 0.218734E+10 | 421.25 | 16791.28 | 10-APR-13:00 | 1243627.64 | 27-APR-15:30 | 22.90 | 21.07 | 38.86 |
May | 0.259879E+10 | 496.82 | 16791.28 | 04-MAY-14:20 | 1249427.32 | 24-MAY-16:10 | 23.43 | 21.28 | 40.41 |
June | 0.140102E+11 | 606.64 | 16791.28 | 01-JUN-08:00 | 1250306.97 | 20-JUN-07:30 | 23.94 | 21.40 | 51.42 |
July | 0.281186E+11 | 663.72 | 16791.28 | 01-JUL-13:50 | 1243574.98 | 03-JUL-07:50 | 24.95 | 22.56 | 51.16 |
August | 0.283497E+11 | 656.07 | 16791.28 | 01-AUG-00:23 | 1220450.75 | 26-AUG-10:00 | 24.87 | 22.48 | 51.38 |
September | 0.232550E+11 | 538.14 | 16791.28 | 01-SEP-03:03 | 1245048.73 | 28-SEP-09:00 | 24.58 | 22.44 | 42.73 |
October | 0.620420E+10 | 392.99 | 16791.28 | 01-OCT-10:00 | 1262920.53 | 18-OCT-12:50 | 22.72 | 21.32 | 33.06 |
November | 0.177398E+10 | 246.92 | 16791.28 | 01-NOV-10:00 | 1254872.48 | 01-NOV-17:00 | 21.98 | 21.12 | 23.48 |
December | 0.248494E+09 | 192.40 | 2257.92 | 22-DEC-15:05 | 1246587.47 | 22-DEC-16:30 | 21.63 | 21.11 | 17.87 |
Annual Sum or Average | 0.108488E+12 | 4854.04 | 23.04 | 21.52 | 34.30 | ||||
Minimum of Months | 0.183104E+09 | 137.78 | 1571.37 | 877050.92 | 21.44 | 21.07 | 14.71 | ||
Maximum of Months | 0.283497E+11 | 663.72 | 16791.28 | 1275759.47 | 24.95 | 22.56 | 51.42 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 8619609.11 | 2.67 | 1268.52 | 31-JAN-15:05 | 1089591.52 | 27-JAN-15:30 | 22.00 | 21.98 | 0.20 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.44 | 21.44 | 0.00 |
March | 22297418.96 | 2.25 | 16791.28 | 17-MAR-15:30 | 1140393.51 | 17-MAR-15:30 | 21.91 | 21.89 | 0.17 |
April | 0.854753E+09 | 92.25 | 16791.28 | 10-APR-13:00 | 1180229.29 | 24-APR-14:20 | 22.90 | 22.34 | 7.30 |
May | 0.109037E+10 | 151.75 | 16791.28 | 04-MAY-14:20 | 1185691.60 | 18-MAY-13:40 | 23.43 | 22.55 | 11.61 |
June | 0.968432E+10 | 247.24 | 16791.28 | 01-JUN-08:20 | 1182848.21 | 05-JUN-10:40 | 23.94 | 22.58 | 19.52 |
July | 0.146837E+11 | 258.80 | 16791.28 | 03-JUL-11:30 | 1184959.17 | 03-JUL-10:20 | 24.95 | 23.66 | 18.80 |
August | 0.157749E+11 | 268.73 | 16791.28 | 01-AUG-05:02 | 1109666.69 | 25-AUG-08:15 | 24.87 | 23.55 | 19.73 |
September | 0.111696E+11 | 192.95 | 16791.28 | 01-SEP-05:07 | 1170281.22 | 05-SEP-07:50 | 24.58 | 23.59 | 14.63 |
October | 0.301768E+10 | 74.06 | 16791.28 | 02-OCT-07:20 | 1114748.97 | 20-OCT-12:30 | 22.72 | 22.34 | 5.64 |
November | 0.208640E+09 | 7.83 | 16791.28 | 01-NOV-12:05 | 1108370.00 | 09-NOV-13:40 | 21.98 | 21.93 | 0.61 |
December | 618297.44 | 0.17 | 1030.50 | 22-DEC-16:00 | 1070265.96 | 22-DEC-16:00 | 21.63 | 21.63 | 0.01 |
Annual Sum or Average | 0.565155E+11 | 1298.69 | 23.04 | 22.47 | 8.23 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.44 | 21.44 | 0.00 | ||
Maximum of Months | 0.157749E+11 | 268.73 | 16791.28 | 1185691.60 | 24.95 | 23.66 | 19.73 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.773031E+10 | 0.00 | 96.94 | 808979.61 | 02-JAN-06:03 | 0.00 | 28.52 | 35.32 | 0.01 | 0.00 | 0.00 | 0.50 | 02-JAN-06:03 |
February | 0.805807E+10 | 0.00 | 110.02 | 593950.10 | 13-FEB-06:03 | 0.00 | 29.11 | 37.63 | 0.02 | 0.00 | 0.00 | 0.37 | 13-FEB-06:03 |
March | 0.795739E+10 | 0.00 | 60.18 | 768533.37 | 27-MAR-05:03 | 0.00 | 31.64 | 35.59 | 0.02 | 0.00 | 0.00 | 0.48 | 27-MAR-05:03 |
April | 12883372.82 | 0.00 | 2.42 | 9692.30 | 21-APR-06:10 | 0.00 | 35.95 | 36.10 | 0.00 | 0.00 | 0.00 | 0.01 | 21-APR-06:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 35.34 | 35.34 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 35.34 | 35.34 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 35.34 | 35.34 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 35.34 | 35.34 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 35.34 | 35.34 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.137476E+10 | 0.00 | 24.48 | 135031.84 | 25-OCT-06:10 | 0.00 | 31.64 | 33.33 | 0.00 | 0.00 | 0.00 | 0.08 | 25-OCT-06:10 |
November | 0.419354E+10 | 0.00 | 72.67 | 697355.66 | 24-NOV-06:03 | 0.00 | 28.32 | 33.64 | 0.01 | 0.00 | 0.00 | 0.43 | 24-NOV-06:03 |
December | 0.312571E+11 | 0.00 | 181.07 | 915238.40 | 07-DEC-06:01 | 0.00 | 30.90 | 42.70 | 0.07 | 0.00 | 0.01 | 0.57 | 07-DEC-06:01 |
Annual Sum or Average | 0.605841E+11 | 0.00 | 547.77 | 0.00 | 32.75 | 35.91 | 0.01 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.32 | 33.33 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.312571E+11 | 0.00 | 181.07 | 915238.40 | 0.00 | 35.95 | 42.70 | 0.07 | 0.00 | 0.01 | 0.57 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 20.48 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.66 | 19.66 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 24.21 | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 37.20 | 37.20 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 30.80 | 30.80 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 41.25 | 41.25 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 45.93 | 45.93 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 48.65 | 48.65 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 32.89 | 32.89 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 27.75 | 27.75 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 24.21 | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 23.79 | 23.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 31.47 | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.66 | 19.66 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.65 | 48.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.400784E+11 | 0.00 | 290.75 | 0.400672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96948.95 | 31-JAN-16:50 | 96948.95 | 31-JAN-16:50 | 0.00 | 0.00 | 0.00 |
February | 0.111162E+11 | 0.00 | 176.90 | 0.111162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64164.77 | 21-FEB-15:00 | 64164.77 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.435185E+11 | 0.00 | 332.88 | 0.435185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107628.51 | 20-MAR-14:50 | 107628.51 | 20-MAR-14:50 | 0.00 | 0.00 | 0.00 |
April | 0.112700E+12 | 0.00 | 567.52 | 0.112700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 137615.82 | 24-APR-15:00 | 137615.82 | 24-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.123596E+12 | 0.00 | 518.92 | 0.123596E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 127987.22 | 15-MAY-15:20 | 127987.22 | 15-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.166666E+12 | 0.00 | 627.74 | 0.166666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 152306.17 | 17-JUN-05:02 | 152306.17 | 17-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.173992E+12 | 0.00 | 645.50 | 0.163579E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 280108.03 | 18-JUL-05:03 | 159330.51 | 10-JUL-04:02 | 0.00 | 0.00 | 0.00 |
August | 0.193608E+12 | 0.00 | 658.66 | 0.182811E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 260301.02 | 01-AUG-05:02 | 173030.84 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.138211E+12 | 0.00 | 524.37 | 0.129106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 241536.98 | 08-SEP-05:02 | 160101.82 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.850340E+11 | 0.00 | 434.90 | 0.836065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180156.81 | 03-OCT-04:12 | 157127.26 | 02-OCT-04:23 | 0.00 | 0.00 | 0.00 |
November | 0.467024E+11 | 0.00 | 315.74 | 0.440342E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135727.76 | 13-NOV-05:12 | 108093.11 | 20-NOV-16:00 | 0.00 | 0.00 | 0.00 |
December | 0.297061E+11 | 0.00 | 256.88 | 0.297061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95635.41 | 22-DEC-16:30 | 95635.41 | 22-DEC-16:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.116493E+13 | 0.00 | 5350.76 | 0.113051E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.111162E+11 | 0.00 | 176.90 | 0.111162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64164.77 | 64164.77 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.193608E+12 | 0.00 | 658.66 | 0.182811E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 280108.03 | 173030.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.347440E+12 | 0.00 | 293.16 | 0.347320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 855584.63 | 31-JAN-16:30 | 855584.63 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.140922E+12 | 0.00 | 192.37 | 0.140922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 580089.64 | 21-FEB-15:05 | 580089.64 | 21-FEB-15:05 | 0.00 | 0.00 | 0.00 |
March | 0.331063E+12 | 0.00 | 322.94 | 0.331063E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 910320.52 | 16-MAR-15:50 | 910320.52 | 16-MAR-15:50 | 0.00 | 0.00 | 0.00 |
April | 0.851962E+12 | 0.00 | 438.68 | 0.851962E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1199266.85 | 14-APR-15:20 | 1199266.85 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.111208E+13 | 0.00 | 488.52 | 0.111208E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1209990.38 | 18-MAY-15:10 | 1209990.38 | 18-MAY-15:10 | 0.00 | 0.00 | 0.00 |
June | 0.148257E+13 | 0.00 | 559.98 | 0.148257E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1414742.62 | 09-JUN-05:02 | 1414742.62 | 09-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.141927E+13 | 0.00 | 552.37 | 0.134601E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2670412.88 | 18-JUL-05:03 | 1491611.03 | 07-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.144322E+13 | 0.00 | 546.08 | 0.137549E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2349338.88 | 01-AUG-05:02 | 1508331.81 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.119826E+13 | 0.00 | 470.24 | 0.112308E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2311933.47 | 08-SEP-05:02 | 1481274.09 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.703571E+12 | 0.00 | 397.56 | 0.691608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1717620.31 | 03-OCT-04:12 | 1292920.89 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.343287E+12 | 0.00 | 299.88 | 0.330091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 977721.89 | 13-NOV-05:12 | 932070.46 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.214854E+12 | 0.00 | 236.72 | 0.214854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 744229.52 | 22-DEC-15:05 | 744229.52 | 22-DEC-15:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.958849E+13 | 0.00 | 4798.51 | 0.934704E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.140922E+12 | 0.00 | 192.37 | 0.140922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 580089.64 | 580089.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.148257E+13 | 0.00 | 559.98 | 0.148257E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2670412.88 | 1508331.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.283735E+11 | 0.00 | 281.54 | 0.283656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89351.45 | 31-JAN-16:30 | 89351.45 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.601059E+10 | 0.00 | 163.67 | 0.601059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46684.32 | 22-FEB-16:00 | 46684.32 | 22-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.300810E+11 | 0.00 | 304.77 | 0.300810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103528.63 | 16-MAR-15:30 | 103528.63 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 |
April | 0.931120E+11 | 0.00 | 437.97 | 0.931120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142760.61 | 14-APR-15:20 | 142760.61 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.123028E+12 | 0.00 | 488.10 | 0.123028E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 144111.97 | 18-MAY-15:20 | 144111.97 | 18-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.169010E+12 | 0.00 | 569.50 | 0.169010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 170210.03 | 28-JUN-14:50 | 170210.03 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.161834E+12 | 0.00 | 567.17 | 0.154244E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 282624.52 | 18-JUL-05:03 | 168659.17 | 17-JUL-04:12 | 0.00 | 0.00 | 0.00 |
August | 0.161121E+12 | 0.00 | 554.78 | 0.154140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 277698.34 | 01-AUG-05:02 | 178814.72 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.130021E+12 | 0.00 | 478.04 | 0.122655E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 257179.95 | 08-SEP-05:02 | 164313.92 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.701805E+11 | 0.00 | 390.03 | 0.690767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191406.78 | 03-OCT-04:12 | 147884.02 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.288837E+11 | 0.00 | 284.40 | 0.279932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105529.25 | 01-NOV-15:20 | 105529.25 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.125874E+11 | 0.00 | 194.82 | 0.125874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75608.92 | 22-DEC-16:30 | 75608.92 | 22-DEC-16:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101424E+13 | 0.00 | 4714.78 | 0.990303E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.601059E+10 | 0.00 | 163.67 | 0.601059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46684.32 | 46684.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.169010E+12 | 0.00 | 569.50 | 0.169010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 282624.52 | 178814.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.246559E+11 | 0.00 | 222.99 | 0.246519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83325.99 | 16-JAN-12:20 | 83325.99 | 16-JAN-12:20 | 0.00 | 0.00 | 0.00 |
February | 0.433835E+10 | 0.00 | 92.02 | 0.431611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50183.89 | 17-FEB-06:03 | 47383.34 | 10-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.238974E+11 | 0.00 | 242.66 | 0.238921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62904.85 | 20-MAR-13:20 | 62904.85 | 20-MAR-13:20 | 0.00 | 0.00 | 0.00 |
April | 0.579223E+11 | 0.00 | 343.07 | 0.579223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94211.98 | 25-APR-03:50 | 94211.98 | 25-APR-03:50 | 0.00 | 0.00 | 0.00 |
May | 0.711567E+11 | 0.00 | 398.11 | 0.711567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114979.42 | 29-MAY-18:27 | 114979.42 | 29-MAY-18:27 | 0.00 | 0.00 | 0.00 |
June | 0.868675E+11 | 0.00 | 419.38 | 0.868675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108670.38 | 17-JUN-04:03 | 108670.38 | 17-JUN-04:03 | 0.00 | 0.00 | 0.00 |
July | 0.935453E+11 | 0.00 | 441.34 | 0.902792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159468.80 | 14-JUL-04:33 | 115266.94 | 04-JUL-18:54 | 0.00 | 0.00 | 0.00 |
August | 0.105143E+12 | 0.00 | 481.33 | 0.101123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 152774.24 | 01-AUG-03:02 | 115545.45 | 27-AUG-20:17 | 0.00 | 0.00 | 0.00 |
September | 0.888709E+11 | 0.00 | 435.71 | 0.845644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149135.94 | 02-SEP-03:02 | 107937.14 | 18-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.559904E+11 | 0.00 | 351.75 | 0.554512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114747.35 | 15-OCT-13:15 | 114747.35 | 15-OCT-13:15 | 0.00 | 0.00 | 0.00 |
November | 0.298360E+11 | 0.00 | 237.87 | 0.276546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103586.05 | 13-NOV-05:42 | 84212.27 | 19-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.132625E+11 | 0.00 | 160.92 | 0.132602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76991.29 | 24-DEC-14:40 | 76991.29 | 24-DEC-14:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.655486E+12 | 0.00 | 3827.13 | 0.641139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.433835E+10 | 0.00 | 92.02 | 0.431611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50183.89 | 47383.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.105143E+12 | 0.00 | 481.33 | 0.101123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 159468.80 | 115545.45 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.290146E+11 | 0.117469E+11 | 716.67 | 0.289859E+11 | 28664900.21 | 0.00 | 0.46 | 27-JAN-16:00 | 0.00 | 20-JAN-21:20 | 135188.37 | 27-JAN-16:00 | 135188.37 | 27-JAN-16:00 | 129.61 | 09-JAN-12:00 | 50792.86 | 27-JAN-16:00 | 0.00 |
February | 0.101614E+11 | 0.530922E+10 | 481.36 | 0.957710E+10 | 0.584334E+09 | 0.00 | 0.29 | 18-FEB-14:00 | 0.00 | 12-FEB-14:20 | 100916.56 | 18-FEB-14:00 | 87817.27 | 18-FEB-15:00 | 13982.29 | 18-FEB-14:00 | 29051.41 | 18-FEB-14:00 | 0.00 |
March | 0.193547E+12 | 0.610346E+11 | 722.34 | 0.189645E+12 | 0.390187E+10 | 0.00 | 0.91 | 15-MAR-12:40 | 0.00 | 04-MAR-22:50 | 316930.05 | 17-MAR-15:20 | 316930.05 | 17-MAR-15:20 | 25921.51 | 17-MAR-10:00 | 107047.36 | 16-MAR-12:40 | 0.00 |
April | 0.671619E+12 | 0.230233E+12 | 720.00 | 0.669874E+12 | 0.174440E+10 | 0.00 | 1.00 | 01-APR-09:10 | 0.03 | 30-APR-24:00 | 376228.52 | 15-APR-09:00 | 376228.52 | 15-APR-09:00 | 34192.26 | 16-APR-06:23 | 139440.44 | 14-APR-16:10 | 0.00 |
May | 0.217138E+12 | 0.797727E+11 | 743.50 | 0.217138E+12 | 469821.18 | 0.00 | 0.67 | 31-MAY-23:10 | 0.01 | 26-MAY-03:10 | 213492.39 | 31-MAY-23:10 | 213492.39 | 31-MAY-23:10 | 99.91 | 11-MAY-02:30 | 75902.33 | 31-MAY-23:10 | 0.00 |
June | 0.518437E+12 | 0.195153E+12 | 720.00 | 0.518428E+12 | 9087349.09 | 0.00 | 0.83 | 30-JUN-23:13 | 0.03 | 21-JUN-06:00 | 306092.81 | 30-JUN-23:57 | 306092.81 | 30-JUN-23:57 | 2787.59 | 04-JUN-05:00 | 108558.90 | 16-JUN-16:00 | 0.00 |
July | 0.870333E+12 | 0.295004E+12 | 744.00 | 0.787202E+12 | 0.831307E+11 | 0.00 | 1.00 | 08-JUL-20:25 | 0.29 | 01-JUL-06:00 | 467543.62 | 14-JUL-01:00 | 391570.33 | 31-JUL-24:00 | 312897.41 | 14-JUL-01:00 | 139971.79 | 05-JUL-16:00 | 0.00 |
August | 0.106368E+13 | 0.342460E+12 | 744.00 | 0.932815E+12 | 0.130861E+12 | 0.00 | 1.00 | 01-AUG-00:05 | 0.37 | 31-AUG-23:53 | 451581.52 | 09-AUG-18:30 | 413024.51 | 27-AUG-13:34 | 260887.01 | 28-AUG-17:00 | 155095.75 | 25-AUG-16:10 | 0.00 |
September | 0.265972E+12 | 0.906294E+11 | 679.30 | 0.239486E+12 | 0.264868E+11 | 0.00 | 0.55 | 04-SEP-10:20 | 0.01 | 27-SEP-04:53 | 233665.76 | 04-SEP-10:13 | 174705.80 | 30-SEP-23:10 | 111565.53 | 04-SEP-10:00 | 63953.40 | 04-SEP-10:20 | 0.00 |
October | 0.251066E+12 | 0.838948E+11 | 717.17 | 0.240033E+12 | 0.110321E+11 | 0.00 | 0.79 | 03-OCT-08:30 | 0.00 | 10-OCT-02:43 | 336596.21 | 03-OCT-08:30 | 228622.38 | 16-OCT-10:05 | 128231.86 | 03-OCT-02:55 | 94559.68 | 03-OCT-08:30 | 0.00 |
November | 0.202931E+12 | 0.620182E+11 | 685.21 | 0.175642E+12 | 0.272887E+11 | 0.00 | 0.97 | 09-NOV-13:00 | 0.01 | 02-NOV-02:70 | 320010.05 | 09-NOV-13:05 | 320010.05 | 09-NOV-13:05 | 171810.90 | 12-NOV-14:55 | 113919.33 | 09-NOV-17:00 | 0.00 |
December | 0.202669E+12 | 0.643566E+11 | 737.31 | 0.202282E+12 | 0.386844E+09 | 0.00 | 1.00 | 02-DEC-13:00 | 0.01 | 13-DEC-05:10 | 347312.46 | 25-DEC-13:52 | 347312.46 | 25-DEC-13:52 | 18426.34 | 13-DEC-11:20 | 116806.81 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.449656E+13 | 0.152161E+13 | 8410.85 | 0.421111E+13 | 0.285455E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.101614E+11 | 0.530922E+10 | 481.36 | 0.957710E+10 | 469821.18 | 0.00 | 0.29 | 0.00 | 100916.56 | 87817.27 | 99.91 | 29051.41 | 0.00 | ||||||
Maximum of Months | 0.106368E+13 | 0.342460E+12 | 744.00 | 0.932815E+12 | 0.130861E+12 | 0.00 | 1.00 | 0.37 | 467543.62 | 413024.51 | 312897.41 | 155095.75 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.547763E+10 | 0.138425E+10 | 744.00 | 0.547443E+10 | 3196841.55 | 0.00 | 0.41 | 29-JAN-17:12 | 0.19 | 21-JAN-08:00 | 2840.74 | 29-JAN-17:15 | 2840.74 | 29-JAN-17:15 | 97.66 | 09-JAN-11:20 | 942.24 | 31-JAN-17:00 | 0.00 |
February | 0.940569E+10 | 0.207897E+10 | 672.00 | 0.936189E+10 | 43797068.88 | 0.00 | 0.55 | 25-FEB-18:10 | 0.42 | 08-FEB-07:10 | 4566.17 | 20-FEB-17:03 | 4545.75 | 20-FEB-17:08 | 171.85 | 16-FEB-10:20 | 1045.51 | 22-FEB-17:00 | 0.00 |
March | 0.157473E+11 | 0.363961E+10 | 744.00 | 0.157357E+11 | 11591315.90 | 0.00 | 0.94 | 31-MAR-24:00 | 0.63 | 07-MAR-08:00 | 7721.38 | 31-MAR-24:00 | 7721.38 | 31-MAR-24:00 | 212.14 | 06-MAR-11:05 | 2074.09 | 16-MAR-16:00 | 0.00 |
April | 0.199920E+11 | 0.574688E+10 | 720.00 | 0.199920E+11 | 0.00 | 0.00 | 1.00 | 01-APR-09:00 | 0.37 | 30-APR-23:05 | 8286.92 | 26-APR-18:50 | 8286.92 | 26-APR-18:50 | 0.00 | 11-APR-16:00 | 2875.93 | 14-APR-16:10 | 0.00 |
May | 0.630701E+10 | 0.212992E+10 | 744.00 | 0.630701E+10 | -0.0 | 0.00 | 0.59 | 31-MAY-23:15 | 0.26 | 13-MAY-06:30 | 4064.96 | 31-MAY-23:55 | 4064.96 | 31-MAY-23:55 | 0.00 | 02-MAY-12:00 | 1376.66 | 31-MAY-23:15 | 0.00 |
June | 0.112014E+11 | 0.412853E+10 | 720.00 | 0.111999E+11 | 1546834.43 | 0.00 | 0.79 | 30-JUN-23:13 | 0.49 | 21-JUN-06:10 | 6001.18 | 30-JUN-24:00 | 6001.18 | 30-JUN-24:00 | 92.77 | 30-JUN-10:10 | 2316.54 | 16-JUN-16:00 | 0.00 |
July | 0.167090E+11 | 0.572072E+10 | 744.00 | 0.165582E+11 | 0.150805E+09 | 0.00 | 1.00 | 02-JUL-15:52 | 0.69 | 01-JUL-06:10 | 7925.85 | 31-JUL-23:53 | 7912.67 | 31-JUL-23:57 | 413.29 | 13-JUL-18:00 | 2983.31 | 02-JUL-18:00 | 0.00 |
August | 0.213937E+11 | 0.699834E+10 | 744.00 | 0.212431E+11 | 0.150638E+09 | 0.00 | 1.00 | 01-AUG-08:40 | 0.36 | 31-AUG-24:00 | 8769.85 | 28-AUG-16:45 | 8358.86 | 20-AUG-23:50 | 594.45 | 28-AUG-16:15 | 3186.17 | 25-AUG-16:10 | 0.00 |
September | 0.628059E+10 | 0.201055E+10 | 720.00 | 0.614313E+10 | 0.137459E+09 | 0.00 | 0.54 | 30-SEP-24:00 | 0.25 | 22-SEP-06:10 | 4063.91 | 30-SEP-24:00 | 4063.91 | 30-SEP-24:00 | 298.04 | 11-SEP-15:10 | 1227.77 | 30-SEP-23:20 | 0.00 |
October | 0.111175E+11 | 0.302567E+10 | 744.00 | 0.110869E+11 | 30540408.04 | 0.00 | 0.74 | 15-OCT-17:10 | 0.44 | 25-OCT-06:20 | 5892.89 | 31-OCT-24:00 | 5892.89 | 31-OCT-24:00 | 309.15 | 03-OCT-09:40 | 1855.21 | 15-OCT-17:10 | 0.00 |
November | 0.154143E+11 | 0.356988E+10 | 720.00 | 0.153653E+11 | 48977757.31 | 0.00 | 0.90 | 09-NOV-17:00 | 0.63 | 18-NOV-07:25 | 6839.71 | 26-NOV-16:53 | 6839.71 | 26-NOV-16:53 | 404.98 | 13-NOV-16:10 | 2199.60 | 09-NOV-16:50 | 0.00 |
December | 0.206259E+11 | 0.464366E+10 | 744.00 | 0.206254E+11 | 481613.58 | 0.00 | 1.00 | 01-DEC-14:50 | 0.85 | 14-DEC-07:10 | 8366.15 | 28-DEC-17:00 | 8366.15 | 28-DEC-17:00 | 71.24 | 13-DEC-11:20 | 2418.38 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.159672E+12 | 0.450770E+11 | 8760.00 | 0.159093E+12 | 0.579034E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.547763E+10 | 0.138425E+10 | 672.00 | 0.547443E+10 | -0.0 | 0.00 | 0.41 | 0.19 | 2840.74 | 2840.74 | 0.00 | 942.24 | 0.00 | ||||||
Maximum of Months | 0.213937E+11 | 0.699834E+10 | 744.00 | 0.212431E+11 | 0.150805E+09 | 0.00 | 1.00 | 0.85 | 8769.85 | 8366.15 | 594.45 | 3186.17 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.430650E+11 | 0.111150E+11 | 744.00 | 0.430344E+11 | 30590867.21 | 0.00 | 0.39 | 29-JAN-17:12 | 0.03 | 02-JAN-07:10 | 25547.41 | 24-JAN-17:00 | 25547.41 | 24-JAN-17:00 | 915.67 | 09-JAN-11:30 | 8819.98 | 31-JAN-17:00 | 0.00 |
February | 0.809914E+11 | 0.180841E+11 | 672.00 | 0.805601E+11 | 0.431251E+09 | 0.00 | 0.53 | 25-FEB-18:10 | 0.33 | 13-FEB-07:10 | 42053.06 | 22-FEB-17:00 | 41595.71 | 27-FEB-17:40 | 1702.56 | 16-FEB-10:30 | 9853.13 | 22-FEB-17:00 | 0.00 |
March | 0.143980E+12 | 0.335196E+11 | 744.00 | 0.143864E+12 | 0.116228E+09 | 0.00 | 0.93 | 31-MAR-23:50 | 0.58 | 07-MAR-08:00 | 72417.16 | 31-MAR-23:40 | 72417.16 | 31-MAR-23:40 | 2110.15 | 06-MAR-11:05 | 19725.54 | 16-MAR-16:00 | 0.00 |
April | 0.189327E+12 | 0.546682E+11 | 720.00 | 0.189327E+12 | 0.00 | 0.00 | 1.00 | 01-APR-09:25 | 0.33 | 30-APR-23:05 | 78982.55 | 26-APR-18:50 | 78982.55 | 26-APR-18:50 | 0.00 | 05-APR-01:50 | 27468.78 | 14-APR-16:10 | 0.00 |
May | 0.587126E+11 | 0.199223E+11 | 744.00 | 0.587126E+11 | 0.00 | 0.00 | 0.59 | 31-MAY-23:45 | 0.24 | 13-MAY-06:10 | 39502.21 | 31-MAY-23:55 | 39502.21 | 31-MAY-23:55 | 0.00 | 10-MAY-05:50 | 13303.48 | 31-MAY-23:15 | 0.00 |
June | 0.106710E+12 | 0.393568E+11 | 720.00 | 0.106693E+12 | 17686006.56 | 0.00 | 0.79 | 30-JUN-23:13 | 0.49 | 21-JUN-06:10 | 57678.52 | 30-JUN-24:00 | 57678.52 | 30-JUN-24:00 | 943.21 | 30-JUN-10:00 | 22167.80 | 16-JUN-16:00 | 0.00 |
July | 0.158919E+12 | 0.544456E+11 | 744.00 | 0.157418E+12 | 0.150139E+10 | 0.00 | 1.00 | 01-JUL-18:40 | 0.69 | 01-JUL-06:10 | 75724.87 | 31-JUL-23:53 | 75595.95 | 31-JUL-23:57 | 4107.26 | 13-JUL-18:00 | 28497.78 | 02-JUL-18:00 | 0.00 |
August | 0.201718E+12 | 0.663315E+11 | 744.00 | 0.200195E+12 | 0.152348E+10 | 0.00 | 1.00 | 01-AUG-08:40 | 0.31 | 31-AUG-24:00 | 82772.61 | 28-AUG-16:25 | 78351.16 | 20-AUG-20:52 | 5809.31 | 28-AUG-16:15 | 30426.64 | 25-AUG-16:10 | 0.00 |
September | 0.582084E+11 | 0.187069E+11 | 720.00 | 0.568589E+11 | 0.134955E+10 | 0.00 | 0.55 | 30-SEP-24:00 | 0.23 | 22-SEP-06:10 | 39536.66 | 30-SEP-24:00 | 39536.66 | 30-SEP-24:00 | 2944.21 | 11-SEP-15:10 | 11928.05 | 30-SEP-23:25 | 0.00 |
October | 0.101848E+12 | 0.279397E+11 | 744.00 | 0.101545E+12 | 0.302755E+09 | 0.00 | 0.72 | 15-OCT-17:11 | 0.39 | 25-OCT-06:45 | 54737.28 | 31-OCT-24:00 | 54737.28 | 31-OCT-24:00 | 3077.70 | 03-OCT-09:40 | 17386.70 | 01-OCT-14:00 | 0.00 |
November | 0.139850E+12 | 0.326414E+11 | 720.00 | 0.139364E+12 | 0.485974E+09 | 0.00 | 0.89 | 09-NOV-17:00 | 0.58 | 18-NOV-07:35 | 64584.75 | 14-NOV-17:00 | 63400.08 | 09-NOV-17:00 | 4001.62 | 13-NOV-16:10 | 20816.53 | 09-NOV-16:50 | 0.00 |
December | 0.185735E+12 | 0.422393E+11 | 744.00 | 0.185729E+12 | 5559653.28 | 0.00 | 1.00 | 02-DEC-14:40 | 0.78 | 14-DEC-07:10 | 78709.06 | 28-DEC-17:00 | 78709.06 | 28-DEC-17:00 | 776.50 | 13-DEC-11:10 | 23073.32 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.146907E+13 | 0.418970E+12 | 8760.00 | 0.146330E+13 | 0.576447E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.430650E+11 | 0.111150E+11 | 672.00 | 0.430344E+11 | 0.00 | 0.00 | 0.39 | 0.03 | 25547.41 | 25547.41 | 0.00 | 8819.98 | 0.00 | ||||||
Maximum of Months | 0.201718E+12 | 0.663315E+11 | 744.00 | 0.200195E+12 | 0.152348E+10 | 0.00 | 1.00 | 0.78 | 82772.61 | 78982.55 | 5809.31 | 30426.64 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.339174E+10 | 0.899074E+09 | 712.87 | 0.338894E+10 | 2795178.66 | 0.00 | 0.38 | 31-JAN-17:00 | 0.00 | 01-JAN-00:05 | 2583.50 | 24-JAN-17:00 | 2583.50 | 24-JAN-17:00 | 83.79 | 09-JAN-11:50 | 896.20 | 31-JAN-17:00 | 0.00 |
February | 0.711197E+10 | 0.160835E+10 | 672.00 | 0.706948E+10 | 42490499.89 | 0.00 | 0.53 | 22-FEB-17:00 | 0.21 | 13-FEB-07:10 | 4242.70 | 22-FEB-17:00 | 4189.23 | 22-FEB-17:00 | 170.81 | 16-FEB-10:40 | 995.40 | 22-FEB-17:00 | 0.00 |
March | 0.137743E+11 | 0.323909E+10 | 744.00 | 0.137628E+11 | 11439761.99 | 0.00 | 0.89 | 31-MAR-23:20 | 0.47 | 27-MAR-06:10 | 7082.37 | 31-MAR-23:20 | 7082.37 | 31-MAR-23:20 | 209.50 | 06-MAR-11:05 | 2000.42 | 16-MAR-16:00 | 0.00 |
April | 0.190025E+11 | 0.552368E+10 | 720.00 | 0.190025E+11 | -0.0 | 0.00 | 1.00 | 01-APR-10:30 | 0.34 | 30-APR-24:00 | 8013.25 | 26-APR-18:30 | 8013.25 | 26-APR-18:30 | 0.00 | 12-APR-14:10 | 2809.89 | 14-APR-16:10 | 0.00 |
May | 0.593512E+10 | 0.202615E+10 | 744.00 | 0.593512E+10 | -0.0 | 0.00 | 0.58 | 31-MAY-23:35 | 0.21 | 13-MAY-06:30 | 3961.93 | 31-MAY-23:55 | 3961.93 | 31-MAY-23:55 | 0.00 | 09-MAY-10:10 | 1335.83 | 31-MAY-23:15 | 0.00 |
June | 0.108602E+11 | 0.401351E+10 | 720.00 | 0.108585E+11 | 1641194.03 | 0.00 | 0.78 | 30-JUN-23:13 | 0.47 | 21-JUN-06:10 | 5832.57 | 30-JUN-24:00 | 5832.57 | 30-JUN-24:00 | 93.39 | 30-JUN-10:10 | 2279.23 | 16-JUN-16:00 | 0.00 |
July | 0.161018E+11 | 0.552733E+10 | 744.00 | 0.159516E+11 | 0.150143E+09 | 0.00 | 1.00 | 01-JUL-18:11 | 0.67 | 01-JUL-06:10 | 7629.59 | 31-JUL-23:53 | 7616.59 | 31-JUL-23:57 | 410.74 | 13-JUL-18:00 | 2916.51 | 02-JUL-18:00 | 0.00 |
August | 0.203861E+11 | 0.672774E+10 | 744.00 | 0.202326E+11 | 0.153456E+09 | 0.00 | 1.00 | 01-AUG-09:30 | 0.31 | 31-AUG-24:00 | 8393.63 | 28-AUG-16:15 | 8050.13 | 20-AUG-21:03 | 597.75 | 28-AUG-16:15 | 3112.61 | 25-AUG-16:10 | 0.00 |
September | 0.592197E+10 | 0.190911E+10 | 720.00 | 0.578655E+10 | 0.135426E+09 | 0.00 | 0.55 | 30-SEP-24:00 | 0.20 | 22-SEP-06:30 | 3995.09 | 30-SEP-24:00 | 3995.09 | 30-SEP-24:00 | 296.14 | 11-SEP-15:10 | 1206.92 | 30-SEP-23:25 | 0.00 |
October | 0.984835E+10 | 0.273215E+10 | 744.00 | 0.981819E+10 | 30164834.49 | 0.00 | 0.73 | 15-OCT-17:11 | 0.32 | 25-OCT-06:55 | 5298.65 | 31-OCT-23:40 | 5298.65 | 31-OCT-23:40 | 308.44 | 03-OCT-09:40 | 1809.66 | 01-OCT-14:00 | 0.00 |
November | 0.131729E+11 | 0.311035E+10 | 720.00 | 0.131247E+11 | 48221615.93 | 0.00 | 0.88 | 09-NOV-17:00 | 0.45 | 24-NOV-07:05 | 6486.42 | 14-NOV-17:00 | 6392.32 | 09-NOV-17:00 | 400.01 | 13-NOV-16:20 | 2103.56 | 09-NOV-16:50 | 0.00 |
December | 0.172443E+11 | 0.397778E+10 | 744.00 | 0.172438E+11 | 519502.04 | 0.00 | 1.00 | 21-DEC-15:00 | 0.65 | 18-DEC-07:10 | 7924.14 | 26-DEC-17:10 | 7924.14 | 26-DEC-17:10 | 71.89 | 13-DEC-11:20 | 2358.09 | 25-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.142751E+12 | 0.412943E+11 | 8728.87 | 0.142175E+12 | 0.576298E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.339174E+10 | 0.899074E+09 | 672.00 | 0.338894E+10 | -0.0 | 0.00 | 0.38 | 0.00 | 2583.50 | 2583.50 | 0.00 | 896.20 | 0.00 | ||||||
Maximum of Months | 0.203861E+11 | 0.672774E+10 | 744.00 | 0.202326E+11 | 0.153456E+09 | 0.00 | 1.00 | 0.67 | 8393.63 | 8050.13 | 597.75 | 3112.61 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.37 | 0.00 | 100.37 | 68.33 | 445.21 | 0.00 | 0.00 | 0.00 |
February | 114.37 | 0.00 | 114.37 | 46.75 | 449.02 | 0.00 | 0.00 | 0.00 |
March | 152.00 | 0.00 | 152.00 | 132.02 | 386.26 | 0.00 | 0.00 | 0.00 |
April | 185.19 | 1.92 | 183.27 | 296.44 | 202.80 | 0.00 | 0.00 | 0.00 |
May | 216.79 | 17.36 | 199.43 | 413.41 | 133.34 | 0.00 | 0.00 | 0.00 |
June | 251.92 | 45.77 | 206.15 | 642.81 | 52.97 | 0.00 | 0.00 | 0.00 |
July | 214.84 | 22.38 | 192.46 | 546.56 | 41.27 | 0.00 | 0.00 | 0.00 |
August | 173.41 | 4.31 | 169.11 | 446.60 | 56.17 | 0.00 | 0.00 | 0.00 |
September | 163.61 | 0.04 | 163.57 | 377.58 | 82.36 | 0.00 | 0.00 | 0.00 |
October | 126.58 | 0.00 | 126.58 | 177.41 | 274.56 | 0.00 | 0.00 | 0.00 |
November | 105.47 | 0.00 | 105.47 | 70.28 | 415.46 | 0.00 | 0.00 | 0.00 |
December | 93.76 | 0.00 | 93.76 | 34.31 | 556.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.35 | 7.66 | 150.69 | 272.06 | 257.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.76 | 0.00 | 93.76 | 34.31 | 41.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.92 | 45.77 | 206.15 | 642.81 | 556.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.37 | 0.00 | 100.37 | 68.33 | 445.21 | 0.00 | 0.00 | 0.00 |
February | 114.37 | 0.00 | 114.37 | 46.75 | 449.02 | 0.00 | 0.00 | 0.00 |
March | 152.00 | 0.00 | 152.00 | 132.02 | 386.26 | 0.00 | 0.00 | 0.00 |
April | 185.19 | 1.92 | 183.27 | 296.44 | 202.80 | 0.00 | 0.00 | 0.00 |
May | 216.79 | 17.36 | 199.43 | 413.41 | 133.34 | 0.00 | 0.00 | 0.00 |
June | 251.92 | 45.77 | 206.15 | 642.81 | 52.97 | 0.00 | 0.00 | 0.00 |
July | 214.84 | 22.38 | 192.46 | 546.56 | 41.27 | 0.00 | 0.00 | 0.00 |
August | 173.41 | 4.31 | 169.11 | 446.60 | 56.17 | 0.00 | 0.00 | 0.00 |
September | 163.61 | 0.04 | 163.57 | 377.58 | 82.36 | 0.00 | 0.00 | 0.00 |
October | 126.58 | 0.00 | 126.58 | 177.41 | 274.56 | 0.00 | 0.00 | 0.00 |
November | 105.47 | 0.00 | 105.47 | 70.28 | 415.46 | 0.00 | 0.00 | 0.00 |
December | 93.76 | 0.00 | 93.76 | 34.31 | 556.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.35 | 7.66 | 150.69 | 272.06 | 257.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.76 | 0.00 | 93.76 | 34.31 | 41.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.92 | 45.77 | 206.15 | 642.81 | 556.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.37 | 0.00 | 100.37 | 68.33 | 445.21 | 0.00 | 0.00 | 0.00 |
February | 114.37 | 0.00 | 114.37 | 46.75 | 449.02 | 0.00 | 0.00 | 0.00 |
March | 152.00 | 0.00 | 152.00 | 132.02 | 386.26 | 0.00 | 0.00 | 0.00 |
April | 185.19 | 1.92 | 183.27 | 296.44 | 202.80 | 0.00 | 0.00 | 0.00 |
May | 216.79 | 17.36 | 199.43 | 413.41 | 133.34 | 0.00 | 0.00 | 0.00 |
June | 251.92 | 45.77 | 206.15 | 642.81 | 52.97 | 0.00 | 0.00 | 0.00 |
July | 214.84 | 22.38 | 192.46 | 546.56 | 41.27 | 0.00 | 0.00 | 0.00 |
August | 173.41 | 4.31 | 169.11 | 446.60 | 56.17 | 0.00 | 0.00 | 0.00 |
September | 163.61 | 0.04 | 163.57 | 377.58 | 82.36 | 0.00 | 0.00 | 0.00 |
October | 126.58 | 0.00 | 126.58 | 177.41 | 274.56 | 0.00 | 0.00 | 0.00 |
November | 105.47 | 0.00 | 105.47 | 70.28 | 415.46 | 0.00 | 0.00 | 0.00 |
December | 93.76 | 0.00 | 93.76 | 34.31 | 556.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.35 | 7.66 | 150.69 | 272.06 | 257.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.76 | 0.00 | 93.76 | 34.31 | 41.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.92 | 45.77 | 206.15 | 642.81 | 556.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.37 | 0.00 | 100.37 | 68.33 | 445.21 | 0.00 | 0.00 | 0.00 |
February | 114.37 | 0.00 | 114.37 | 46.75 | 449.02 | 0.00 | 0.00 | 0.00 |
March | 152.00 | 0.00 | 152.00 | 132.02 | 386.26 | 0.00 | 0.00 | 0.00 |
April | 185.19 | 1.92 | 183.27 | 296.44 | 202.80 | 0.00 | 0.00 | 0.00 |
May | 216.79 | 17.36 | 199.43 | 413.41 | 133.34 | 0.00 | 0.00 | 0.00 |
June | 251.92 | 45.77 | 206.15 | 642.81 | 52.97 | 0.00 | 0.00 | 0.00 |
July | 214.84 | 22.38 | 192.46 | 546.56 | 41.27 | 0.00 | 0.00 | 0.00 |
August | 173.41 | 4.31 | 169.11 | 446.60 | 56.17 | 0.00 | 0.00 | 0.00 |
September | 163.61 | 0.04 | 163.57 | 377.58 | 82.36 | 0.00 | 0.00 | 0.00 |
October | 126.58 | 0.00 | 126.58 | 177.41 | 274.56 | 0.00 | 0.00 | 0.00 |
November | 105.47 | 0.00 | 105.47 | 70.28 | 415.46 | 0.00 | 0.00 | 0.00 |
December | 93.76 | 0.00 | 93.76 | 34.31 | 556.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.35 | 7.66 | 150.69 | 272.06 | 257.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.76 | 0.00 | 93.76 | 34.31 | 41.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.92 | 45.77 | 206.15 | 642.81 | 556.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.37 | 0.00 | 100.37 | 68.33 | 445.19 | 0.00 | 0.00 | 0.00 |
February | 114.37 | 0.00 | 114.37 | 46.74 | 449.01 | 0.00 | 0.00 | 0.00 |
March | 152.00 | 0.00 | 152.00 | 132.02 | 386.25 | 0.00 | 0.00 | 0.00 |
April | 185.18 | 1.92 | 183.26 | 296.43 | 202.79 | 0.00 | 0.00 | 0.00 |
May | 216.78 | 17.36 | 199.42 | 413.39 | 133.34 | 0.00 | 0.00 | 0.00 |
June | 251.91 | 45.77 | 206.14 | 642.78 | 52.97 | 0.00 | 0.00 | 0.00 |
July | 214.83 | 22.38 | 192.45 | 546.53 | 41.26 | 0.00 | 0.00 | 0.00 |
August | 173.41 | 4.31 | 169.10 | 446.58 | 56.17 | 0.00 | 0.00 | 0.00 |
September | 163.61 | 0.04 | 163.56 | 377.57 | 82.36 | 0.00 | 0.00 | 0.00 |
October | 126.58 | 0.00 | 126.58 | 177.40 | 274.55 | 0.00 | 0.00 | 0.00 |
November | 105.46 | 0.00 | 105.46 | 70.27 | 415.44 | 0.00 | 0.00 | 0.00 |
December | 93.75 | 0.00 | 93.75 | 34.31 | 556.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 158.35 | 7.66 | 150.68 | 272.04 | 257.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 93.75 | 0.00 | 93.75 | 34.31 | 41.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 251.91 | 45.77 | 206.14 | 642.78 | 556.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 360.28 | 226.01 | 134.27 | 451.65 | 452.91 | 0.00 | 0.00 | 0.00 |
February | 355.13 | 203.15 | 151.98 | 395.87 | 458.44 | 0.00 | 0.00 | 0.00 |
March | 444.43 | 228.62 | 215.81 | 573.30 | 390.55 | 0.00 | 0.00 | 0.00 |
April | 634.39 | 378.11 | 256.29 | 1043.57 | 206.35 | 0.00 | 0.00 | 0.00 |
May | 657.46 | 389.74 | 267.72 | 1154.84 | 148.56 | 0.00 | 0.00 | 0.00 |
June | 685.29 | 425.83 | 259.46 | 1382.65 | 56.19 | 0.00 | 0.00 | 0.00 |
July | 578.77 | 326.34 | 252.42 | 1180.34 | 42.25 | 0.00 | 0.00 | 0.00 |
August | 549.30 | 313.49 | 235.82 | 1110.89 | 54.58 | 0.00 | 0.00 | 0.00 |
September | 450.74 | 217.26 | 233.47 | 877.50 | 85.69 | 0.00 | 0.00 | 0.00 |
October | 452.74 | 275.53 | 177.21 | 704.68 | 279.13 | 0.00 | 0.00 | 0.00 |
November | 348.13 | 208.99 | 139.14 | 435.05 | 420.39 | 0.00 | 0.00 | 0.00 |
December | 317.41 | 191.66 | 125.75 | 344.32 | 551.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 486.77 | 282.43 | 204.34 | 806.49 | 261.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 317.41 | 191.66 | 125.75 | 344.32 | 42.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.29 | 425.83 | 267.72 | 1382.65 | 551.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 360.28 | 226.01 | 134.27 | 451.65 | 452.91 | 0.00 | 0.00 | 0.00 |
February | 355.13 | 203.15 | 151.98 | 395.87 | 458.44 | 0.00 | 0.00 | 0.00 |
March | 444.43 | 228.62 | 215.81 | 573.30 | 390.55 | 0.00 | 0.00 | 0.00 |
April | 634.39 | 378.11 | 256.29 | 1043.57 | 206.35 | 0.00 | 0.00 | 0.00 |
May | 657.46 | 389.74 | 267.72 | 1154.84 | 148.56 | 0.00 | 0.00 | 0.00 |
June | 685.29 | 425.83 | 259.46 | 1382.65 | 56.19 | 0.00 | 0.00 | 0.00 |
July | 578.77 | 326.34 | 252.42 | 1180.34 | 42.25 | 0.00 | 0.00 | 0.00 |
August | 549.30 | 313.49 | 235.82 | 1110.89 | 54.58 | 0.00 | 0.00 | 0.00 |
September | 450.74 | 217.26 | 233.47 | 877.50 | 85.69 | 0.00 | 0.00 | 0.00 |
October | 452.74 | 275.53 | 177.21 | 704.68 | 279.13 | 0.00 | 0.00 | 0.00 |
November | 348.13 | 208.99 | 139.14 | 435.05 | 420.39 | 0.00 | 0.00 | 0.00 |
December | 317.41 | 191.66 | 125.75 | 344.32 | 551.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 486.77 | 282.43 | 204.34 | 806.49 | 261.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 317.41 | 191.66 | 125.75 | 344.32 | 42.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.29 | 425.83 | 267.72 | 1382.65 | 551.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 360.27 | 226.01 | 134.26 | 451.64 | 452.90 | 0.00 | 0.00 | 0.00 |
February | 355.12 | 203.15 | 151.98 | 395.86 | 458.43 | 0.00 | 0.00 | 0.00 |
March | 444.42 | 228.61 | 215.81 | 573.29 | 390.54 | 0.00 | 0.00 | 0.00 |
April | 634.38 | 378.10 | 256.28 | 1043.55 | 206.34 | 0.00 | 0.00 | 0.00 |
May | 657.45 | 389.73 | 267.72 | 1154.82 | 148.56 | 0.00 | 0.00 | 0.00 |
June | 685.27 | 425.82 | 259.45 | 1382.63 | 56.19 | 0.00 | 0.00 | 0.00 |
July | 578.76 | 326.34 | 252.42 | 1180.32 | 42.25 | 0.00 | 0.00 | 0.00 |
August | 549.29 | 313.48 | 235.81 | 1110.87 | 54.58 | 0.00 | 0.00 | 0.00 |
September | 450.73 | 217.26 | 233.47 | 877.49 | 85.69 | 0.00 | 0.00 | 0.00 |
October | 452.73 | 275.53 | 177.20 | 704.67 | 279.12 | 0.00 | 0.00 | 0.00 |
November | 348.13 | 208.98 | 139.14 | 435.04 | 420.39 | 0.00 | 0.00 | 0.00 |
December | 317.40 | 191.66 | 125.74 | 344.31 | 551.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 486.76 | 282.42 | 204.34 | 806.47 | 261.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 317.40 | 191.66 | 125.74 | 344.31 | 42.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.27 | 425.82 | 267.72 | 1382.63 | 551.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 826.48 | 660.09 | 166.39 | 1248.63 | 422.00 | 0.00 | 0.00 | 0.00 |
February | 522.57 | 352.44 | 170.13 | 707.26 | 414.08 | 0.00 | 0.00 | 0.00 |
March | 434.82 | 223.95 | 210.86 | 631.94 | 374.59 | 0.00 | 0.00 | 0.00 |
April | 370.15 | 149.57 | 220.57 | 689.76 | 212.93 | 0.00 | 0.00 | 0.00 |
May | 248.04 | 40.98 | 207.06 | 509.25 | 146.77 | 0.00 | 0.00 | 0.00 |
June | 212.39 | 16.37 | 196.02 | 577.08 | 55.78 | 0.00 | 0.00 | 0.00 |
July | 217.03 | 22.45 | 194.57 | 563.09 | 42.33 | 0.00 | 0.00 | 0.00 |
August | 263.89 | 72.93 | 190.97 | 649.63 | 57.42 | 0.00 | 0.00 | 0.00 |
September | 380.25 | 162.22 | 218.02 | 794.19 | 85.42 | 0.00 | 0.00 | 0.00 |
October | 605.88 | 419.36 | 186.52 | 1007.15 | 265.86 | 0.00 | 0.00 | 0.00 |
November | 706.08 | 540.82 | 165.26 | 1051.46 | 390.06 | 0.00 | 0.00 | 0.00 |
December | 768.38 | 608.28 | 160.10 | 1102.69 | 508.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.01 | 272.40 | 190.60 | 795.24 | 247.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 212.39 | 16.37 | 160.10 | 509.25 | 42.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 826.48 | 660.09 | 220.57 | 1248.63 | 508.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 826.48 | 660.09 | 166.39 | 1248.63 | 422.00 | 0.00 | 0.00 | 0.00 |
February | 522.57 | 352.44 | 170.13 | 707.26 | 414.08 | 0.00 | 0.00 | 0.00 |
March | 434.82 | 223.95 | 210.86 | 631.94 | 374.59 | 0.00 | 0.00 | 0.00 |
April | 370.15 | 149.57 | 220.57 | 689.76 | 212.93 | 0.00 | 0.00 | 0.00 |
May | 248.04 | 40.98 | 207.06 | 509.25 | 146.77 | 0.00 | 0.00 | 0.00 |
June | 212.39 | 16.37 | 196.02 | 577.08 | 55.78 | 0.00 | 0.00 | 0.00 |
July | 217.03 | 22.45 | 194.57 | 563.09 | 42.33 | 0.00 | 0.00 | 0.00 |
August | 263.89 | 72.93 | 190.97 | 649.63 | 57.42 | 0.00 | 0.00 | 0.00 |
September | 380.24 | 162.22 | 218.02 | 794.19 | 85.42 | 0.00 | 0.00 | 0.00 |
October | 605.88 | 419.36 | 186.52 | 1007.15 | 265.86 | 0.00 | 0.00 | 0.00 |
November | 706.08 | 540.82 | 165.26 | 1051.46 | 390.06 | 0.00 | 0.00 | 0.00 |
December | 768.38 | 608.28 | 160.10 | 1102.69 | 508.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.01 | 272.40 | 190.60 | 795.24 | 247.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 212.39 | 16.37 | 160.10 | 509.25 | 42.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 826.48 | 660.09 | 220.57 | 1248.63 | 508.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 826.48 | 660.09 | 166.39 | 1248.63 | 422.00 | 0.00 | 0.00 | 0.00 |
February | 522.57 | 352.44 | 170.13 | 707.26 | 414.08 | 0.00 | 0.00 | 0.00 |
March | 434.82 | 223.95 | 210.86 | 631.94 | 374.59 | 0.00 | 0.00 | 0.00 |
April | 370.15 | 149.57 | 220.57 | 689.76 | 212.93 | 0.00 | 0.00 | 0.00 |
May | 248.04 | 40.98 | 207.06 | 509.25 | 146.77 | 0.00 | 0.00 | 0.00 |
June | 212.39 | 16.37 | 196.02 | 577.08 | 55.78 | 0.00 | 0.00 | 0.00 |
July | 217.03 | 22.45 | 194.57 | 563.09 | 42.33 | 0.00 | 0.00 | 0.00 |
August | 263.89 | 72.93 | 190.97 | 649.63 | 57.42 | 0.00 | 0.00 | 0.00 |
September | 380.25 | 162.22 | 218.02 | 794.19 | 85.42 | 0.00 | 0.00 | 0.00 |
October | 605.88 | 419.36 | 186.52 | 1007.15 | 265.86 | 0.00 | 0.00 | 0.00 |
November | 706.08 | 540.82 | 165.26 | 1051.46 | 390.06 | 0.00 | 0.00 | 0.00 |
December | 768.38 | 608.28 | 160.10 | 1102.69 | 508.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.01 | 272.40 | 190.60 | 795.24 | 247.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 212.39 | 16.37 | 160.10 | 509.25 | 42.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 826.48 | 660.09 | 220.57 | 1248.63 | 508.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 826.48 | 660.09 | 166.39 | 1248.63 | 422.00 | 0.00 | 0.00 | 0.00 |
February | 522.57 | 352.44 | 170.13 | 707.26 | 414.08 | 0.00 | 0.00 | 0.00 |
March | 434.82 | 223.95 | 210.86 | 631.94 | 374.59 | 0.00 | 0.00 | 0.00 |
April | 370.15 | 149.57 | 220.57 | 689.76 | 212.93 | 0.00 | 0.00 | 0.00 |
May | 248.04 | 40.98 | 207.06 | 509.25 | 146.77 | 0.00 | 0.00 | 0.00 |
June | 212.39 | 16.37 | 196.02 | 577.08 | 55.78 | 0.00 | 0.00 | 0.00 |
July | 217.03 | 22.45 | 194.57 | 563.09 | 42.33 | 0.00 | 0.00 | 0.00 |
August | 263.89 | 72.93 | 190.97 | 649.63 | 57.42 | 0.00 | 0.00 | 0.00 |
September | 380.24 | 162.22 | 218.02 | 794.19 | 85.42 | 0.00 | 0.00 | 0.00 |
October | 605.88 | 419.36 | 186.52 | 1007.15 | 265.86 | 0.00 | 0.00 | 0.00 |
November | 706.08 | 540.82 | 165.26 | 1051.46 | 390.06 | 0.00 | 0.00 | 0.00 |
December | 768.38 | 608.28 | 160.10 | 1102.69 | 508.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 463.01 | 272.40 | 190.60 | 795.24 | 247.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 212.39 | 16.37 | 160.10 | 509.25 | 42.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 826.48 | 660.09 | 220.57 | 1248.63 | 508.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 826.45 | 660.06 | 166.39 | 1248.58 | 421.98 | 0.00 | 0.00 | 0.00 |
February | 522.55 | 352.43 | 170.12 | 707.24 | 414.07 | 0.00 | 0.00 | 0.00 |
March | 434.80 | 223.95 | 210.86 | 631.91 | 374.58 | 0.00 | 0.00 | 0.00 |
April | 370.13 | 149.57 | 220.56 | 689.73 | 212.92 | 0.00 | 0.00 | 0.00 |
May | 248.03 | 40.98 | 207.05 | 509.23 | 146.77 | 0.00 | 0.00 | 0.00 |
June | 212.38 | 16.37 | 196.01 | 577.05 | 55.78 | 0.00 | 0.00 | 0.00 |
July | 217.02 | 22.45 | 194.57 | 563.07 | 42.33 | 0.00 | 0.00 | 0.00 |
August | 263.88 | 72.92 | 190.96 | 649.60 | 57.42 | 0.00 | 0.00 | 0.00 |
September | 380.23 | 162.22 | 218.01 | 794.16 | 85.41 | 0.00 | 0.00 | 0.00 |
October | 605.86 | 419.34 | 186.51 | 1007.11 | 265.85 | 0.00 | 0.00 | 0.00 |
November | 706.05 | 540.80 | 165.25 | 1051.42 | 390.05 | 0.00 | 0.00 | 0.00 |
December | 768.35 | 608.25 | 160.10 | 1102.65 | 508.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 462.99 | 272.39 | 190.60 | 795.21 | 247.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 212.38 | 16.37 | 160.10 | 509.23 | 42.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 826.45 | 660.06 | 220.56 | 1248.58 | 508.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.74 | 234.15 | 142.59 | 525.89 | 533.34 | 0.00 | 0.00 | 0.00 |
February | 305.20 | 147.54 | 157.65 | 336.69 | 543.64 | 0.00 | 0.00 | 0.00 |
March | 404.24 | 192.71 | 211.53 | 517.66 | 475.29 | 0.00 | 0.00 | 0.00 |
April | 620.72 | 354.08 | 266.64 | 1020.89 | 288.34 | 0.00 | 0.00 | 0.00 |
May | 622.32 | 348.93 | 273.38 | 1108.13 | 191.44 | 0.00 | 0.00 | 0.00 |
June | 661.59 | 389.12 | 272.47 | 1330.68 | 87.48 | 0.00 | 0.00 | 0.00 |
July | 481.52 | 224.77 | 256.75 | 987.42 | 71.26 | 0.00 | 0.00 | 0.00 |
August | 459.17 | 230.60 | 228.57 | 925.73 | 102.36 | 0.00 | 0.00 | 0.00 |
September | 400.24 | 168.17 | 232.08 | 786.30 | 113.77 | 0.00 | 0.00 | 0.00 |
October | 409.53 | 234.17 | 175.36 | 645.72 | 344.16 | 0.00 | 0.00 | 0.00 |
November | 377.19 | 227.74 | 149.45 | 507.47 | 518.15 | 0.00 | 0.00 | 0.00 |
December | 304.00 | 173.09 | 130.91 | 363.68 | 687.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.39 | 244.10 | 208.29 | 756.41 | 328.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 304.00 | 147.54 | 130.91 | 336.69 | 71.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.59 | 389.12 | 273.38 | 1330.68 | 687.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.74 | 234.15 | 142.59 | 525.89 | 533.34 | 0.00 | 0.00 | 0.00 |
February | 305.20 | 147.54 | 157.65 | 336.69 | 543.64 | 0.00 | 0.00 | 0.00 |
March | 404.24 | 192.71 | 211.53 | 517.66 | 475.29 | 0.00 | 0.00 | 0.00 |
April | 620.72 | 354.08 | 266.64 | 1020.89 | 288.34 | 0.00 | 0.00 | 0.00 |
May | 622.32 | 348.93 | 273.38 | 1108.13 | 191.44 | 0.00 | 0.00 | 0.00 |
June | 661.59 | 389.12 | 272.47 | 1330.68 | 87.48 | 0.00 | 0.00 | 0.00 |
July | 481.52 | 224.77 | 256.75 | 987.42 | 71.26 | 0.00 | 0.00 | 0.00 |
August | 459.17 | 230.60 | 228.57 | 925.73 | 102.36 | 0.00 | 0.00 | 0.00 |
September | 400.24 | 168.17 | 232.08 | 786.30 | 113.77 | 0.00 | 0.00 | 0.00 |
October | 409.53 | 234.17 | 175.36 | 645.72 | 344.16 | 0.00 | 0.00 | 0.00 |
November | 377.19 | 227.74 | 149.45 | 507.47 | 518.15 | 0.00 | 0.00 | 0.00 |
December | 304.00 | 173.09 | 130.91 | 363.68 | 687.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.39 | 244.10 | 208.29 | 756.41 | 328.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 304.00 | 147.54 | 130.91 | 336.69 | 71.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.59 | 389.12 | 273.38 | 1330.68 | 687.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 376.73 | 234.15 | 142.59 | 525.88 | 533.33 | 0.00 | 0.00 | 0.00 |
February | 305.19 | 147.54 | 157.65 | 336.69 | 543.63 | 0.00 | 0.00 | 0.00 |
March | 404.23 | 192.70 | 211.53 | 517.65 | 475.28 | 0.00 | 0.00 | 0.00 |
April | 620.71 | 354.07 | 266.64 | 1020.88 | 288.33 | 0.00 | 0.00 | 0.00 |
May | 622.31 | 348.93 | 273.38 | 1108.11 | 191.43 | 0.00 | 0.00 | 0.00 |
June | 661.57 | 389.11 | 272.46 | 1330.66 | 87.48 | 0.00 | 0.00 | 0.00 |
July | 481.51 | 224.77 | 256.74 | 987.40 | 71.26 | 0.00 | 0.00 | 0.00 |
August | 459.16 | 230.60 | 228.56 | 925.71 | 102.36 | 0.00 | 0.00 | 0.00 |
September | 400.24 | 168.16 | 232.07 | 786.29 | 113.76 | 0.00 | 0.00 | 0.00 |
October | 409.52 | 234.16 | 175.36 | 645.71 | 344.15 | 0.00 | 0.00 | 0.00 |
November | 377.18 | 227.73 | 149.45 | 507.46 | 518.14 | 0.00 | 0.00 | 0.00 |
December | 303.99 | 173.08 | 130.91 | 363.67 | 687.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 452.38 | 244.09 | 208.28 | 756.39 | 328.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 303.99 | 147.54 | 130.91 | 336.69 | 71.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 661.57 | 389.11 | 273.38 | 1330.66 | 687.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 501.86 | 0.00 | 501.86 | 415.52 | 1985.78 | 0.00 | 0.00 | 0.00 |
February | 571.86 | 0.00 | 571.86 | 283.82 | 1988.13 | 0.00 | 0.00 | 0.00 |
March | 760.00 | 0.00 | 760.00 | 717.77 | 1751.88 | 0.00 | 0.00 | 0.00 |
April | 925.95 | 9.61 | 916.34 | 1536.51 | 956.17 | 0.00 | 0.00 | 0.00 |
May | 1083.92 | 86.79 | 997.13 | 2097.08 | 647.17 | 0.00 | 0.00 | 0.00 |
June | 1259.58 | 228.85 | 1030.73 | 3247.02 | 268.05 | 0.00 | 0.00 | 0.00 |
July | 1074.18 | 111.91 | 962.28 | 2771.39 | 204.13 | 0.00 | 0.00 | 0.00 |
August | 867.06 | 21.54 | 845.52 | 2296.77 | 255.36 | 0.00 | 0.00 | 0.00 |
September | 818.06 | 0.22 | 817.84 | 1912.60 | 398.78 | 0.00 | 0.00 | 0.00 |
October | 632.91 | 0.00 | 632.91 | 934.98 | 1258.47 | 0.00 | 0.00 | 0.00 |
November | 527.33 | 0.00 | 527.33 | 413.56 | 1838.05 | 0.00 | 0.00 | 0.00 |
December | 468.78 | 0.00 | 468.78 | 253.62 | 2419.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 791.75 | 38.32 | 753.43 | 1411.89 | 1160.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.78 | 0.00 | 468.78 | 253.62 | 204.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1259.58 | 228.85 | 1030.73 | 3247.02 | 2419.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1080.83 | 678.04 | 402.80 | 1366.89 | 1269.59 | 0.00 | 0.00 | 0.00 |
February | 1065.37 | 609.44 | 455.93 | 1188.50 | 1287.61 | 0.00 | 0.00 | 0.00 |
March | 1333.26 | 685.84 | 647.42 | 1710.47 | 1124.05 | 0.00 | 0.00 | 0.00 |
April | 1903.16 | 1134.31 | 768.85 | 3101.28 | 628.82 | 0.00 | 0.00 | 0.00 |
May | 1972.36 | 1169.20 | 803.16 | 3436.09 | 446.65 | 0.00 | 0.00 | 0.00 |
June | 2055.84 | 1277.47 | 778.37 | 4117.48 | 180.24 | 0.00 | 0.00 | 0.00 |
July | 1736.29 | 979.02 | 757.26 | 3512.08 | 138.15 | 0.00 | 0.00 | 0.00 |
August | 1647.89 | 940.45 | 707.44 | 3310.37 | 174.17 | 0.00 | 0.00 | 0.00 |
September | 1352.20 | 651.79 | 700.42 | 2609.49 | 261.44 | 0.00 | 0.00 | 0.00 |
October | 1358.21 | 826.60 | 531.61 | 2100.52 | 808.34 | 0.00 | 0.00 | 0.00 |
November | 1044.39 | 626.96 | 417.43 | 1309.52 | 1184.06 | 0.00 | 0.00 | 0.00 |
December | 952.21 | 574.97 | 377.24 | 1057.37 | 1540.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1460.30 | 847.28 | 613.02 | 2407.45 | 751.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 952.21 | 574.97 | 377.24 | 1057.37 | 138.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2055.84 | 1277.47 | 803.16 | 4117.48 | 1540.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4132.36 | 3300.40 | 831.96 | 6194.45 | 2076.07 | 0.00 | 0.00 | 0.00 |
February | 2612.84 | 1762.19 | 850.65 | 3511.47 | 1998.67 | 0.00 | 0.00 | 0.00 |
March | 2174.07 | 1119.76 | 1054.31 | 3148.70 | 1804.32 | 0.00 | 0.00 | 0.00 |
April | 1850.70 | 747.87 | 1102.84 | 3453.95 | 1034.11 | 0.00 | 0.00 | 0.00 |
May | 1240.16 | 204.89 | 1035.28 | 2565.33 | 715.08 | 0.00 | 0.00 | 0.00 |
June | 1061.94 | 81.86 | 980.08 | 2927.23 | 275.44 | 0.00 | 0.00 | 0.00 |
July | 1085.12 | 112.26 | 972.85 | 2853.32 | 206.11 | 0.00 | 0.00 | 0.00 |
August | 1319.45 | 364.63 | 954.82 | 3289.82 | 264.81 | 0.00 | 0.00 | 0.00 |
September | 1901.20 | 811.10 | 1090.10 | 3960.44 | 421.34 | 0.00 | 0.00 | 0.00 |
October | 3029.37 | 2096.77 | 932.59 | 5000.47 | 1298.77 | 0.00 | 0.00 | 0.00 |
November | 3530.36 | 2704.07 | 826.29 | 5223.23 | 1890.89 | 0.00 | 0.00 | 0.00 |
December | 3841.87 | 3041.36 | 800.51 | 5494.37 | 2460.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2315.01 | 1362.00 | 953.01 | 3973.17 | 1200.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.94 | 81.86 | 800.51 | 2565.33 | 206.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4132.36 | 3300.40 | 1102.84 | 6194.45 | 2460.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1130.21 | 702.44 | 427.76 | 1611.86 | 1438.49 | 0.00 | 0.00 | 0.00 |
February | 915.58 | 442.63 | 472.95 | 1045.17 | 1396.51 | 0.00 | 0.00 | 0.00 |
March | 1212.71 | 578.12 | 634.59 | 1604.72 | 1234.11 | 0.00 | 0.00 | 0.00 |
April | 1862.16 | 1062.23 | 799.93 | 3113.02 | 750.06 | 0.00 | 0.00 | 0.00 |
May | 1866.94 | 1046.79 | 820.14 | 3336.23 | 536.97 | 0.00 | 0.00 | 0.00 |
June | 1984.74 | 1167.35 | 817.39 | 4026.36 | 234.54 | 0.00 | 0.00 | 0.00 |
July | 1444.54 | 674.31 | 770.23 | 3024.52 | 174.04 | 0.00 | 0.00 | 0.00 |
August | 1377.50 | 691.81 | 685.69 | 2867.92 | 216.14 | 0.00 | 0.00 | 0.00 |
September | 1200.71 | 504.49 | 696.22 | 2381.47 | 303.30 | 0.00 | 0.00 | 0.00 |
October | 1228.58 | 702.50 | 526.08 | 1971.60 | 911.68 | 0.00 | 0.00 | 0.00 |
November | 1131.55 | 683.20 | 448.35 | 1567.26 | 1327.38 | 0.00 | 0.00 | 0.00 |
December | 911.99 | 519.26 | 392.73 | 1156.35 | 1717.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1357.14 | 732.28 | 624.86 | 2314.18 | 851.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 911.99 | 442.63 | 392.73 | 1045.17 | 174.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1984.74 | 1167.35 | 820.14 | 4026.36 | 1717.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 501.86 | 0.00 | 501.86 | 463.82 | 1823.91 | 0.00 | 0.00 | 0.00 |
February | 571.86 | 0.00 | 571.86 | 324.13 | 1793.26 | 0.00 | 0.00 | 0.00 |
March | 760.00 | 0.00 | 760.00 | 751.22 | 1644.77 | 0.00 | 0.00 | 0.00 |
April | 925.95 | 9.61 | 916.34 | 1524.07 | 938.06 | 0.00 | 0.00 | 0.00 |
May | 1083.92 | 86.79 | 997.13 | 2077.51 | 648.06 | 0.00 | 0.00 | 0.00 |
June | 1259.58 | 228.85 | 1030.73 | 3208.59 | 277.09 | 0.00 | 0.00 | 0.00 |
July | 1074.18 | 111.91 | 962.28 | 2727.34 | 214.72 | 0.00 | 0.00 | 0.00 |
August | 867.06 | 21.54 | 845.52 | 2263.63 | 263.11 | 0.00 | 0.00 | 0.00 |
September | 818.06 | 0.22 | 817.84 | 1887.19 | 404.46 | 0.00 | 0.00 | 0.00 |
October | 632.91 | 0.00 | 632.91 | 947.05 | 1190.70 | 0.00 | 0.00 | 0.00 |
November | 527.33 | 0.00 | 527.33 | 453.98 | 1686.60 | 0.00 | 0.00 | 0.00 |
December | 468.78 | 0.00 | 468.78 | 307.19 | 2203.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 791.75 | 38.32 | 753.43 | 1416.33 | 1087.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.78 | 0.00 | 468.78 | 307.19 | 214.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1259.58 | 228.85 | 1030.73 | 3208.59 | 2203.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1080.83 | 678.04 | 402.80 | 1407.71 | 1180.79 | 0.00 | 0.00 | 0.00 |
February | 1065.37 | 609.44 | 455.93 | 1221.22 | 1176.37 | 0.00 | 0.00 | 0.00 |
March | 1333.26 | 685.84 | 647.42 | 1736.21 | 1067.82 | 0.00 | 0.00 | 0.00 |
April | 1903.16 | 1134.31 | 768.85 | 3095.19 | 621.86 | 0.00 | 0.00 | 0.00 |
May | 1972.36 | 1169.20 | 803.16 | 3424.33 | 446.65 | 0.00 | 0.00 | 0.00 |
June | 2055.84 | 1277.47 | 778.37 | 4095.04 | 185.37 | 0.00 | 0.00 | 0.00 |
July | 1736.29 | 979.02 | 757.26 | 3487.74 | 144.44 | 0.00 | 0.00 | 0.00 |
August | 1647.89 | 940.45 | 707.44 | 3292.69 | 178.26 | 0.00 | 0.00 | 0.00 |
September | 1352.20 | 651.79 | 700.42 | 2596.92 | 265.09 | 0.00 | 0.00 | 0.00 |
October | 1358.21 | 826.60 | 531.61 | 2110.23 | 774.27 | 0.00 | 0.00 | 0.00 |
November | 1044.39 | 626.96 | 417.43 | 1344.03 | 1098.93 | 0.00 | 0.00 | 0.00 |
December | 952.21 | 574.97 | 377.24 | 1114.02 | 1410.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1460.30 | 847.28 | 613.02 | 2416.14 | 710.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 952.21 | 574.97 | 377.24 | 1114.02 | 144.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2055.84 | 1277.47 | 803.16 | 4095.04 | 1410.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4132.36 | 3300.40 | 831.96 | 6233.62 | 1953.60 | 0.00 | 0.00 | 0.00 |
February | 2612.84 | 1762.19 | 850.65 | 3549.05 | 1838.98 | 0.00 | 0.00 | 0.00 |
March | 2174.07 | 1119.76 | 1054.31 | 3170.07 | 1713.94 | 0.00 | 0.00 | 0.00 |
April | 1850.70 | 747.87 | 1102.84 | 3435.61 | 1016.56 | 0.00 | 0.00 | 0.00 |
May | 1240.16 | 204.89 | 1035.28 | 2544.00 | 712.02 | 0.00 | 0.00 | 0.00 |
June | 1061.94 | 81.86 | 980.08 | 2888.67 | 283.02 | 0.00 | 0.00 | 0.00 |
July | 1085.12 | 112.26 | 972.85 | 2809.15 | 215.67 | 0.00 | 0.00 | 0.00 |
August | 1319.45 | 364.63 | 954.82 | 3254.98 | 271.36 | 0.00 | 0.00 | 0.00 |
September | 1901.20 | 811.10 | 1090.10 | 3931.61 | 427.65 | 0.00 | 0.00 | 0.00 |
October | 3029.37 | 2096.77 | 932.59 | 5001.91 | 1247.64 | 0.00 | 0.00 | 0.00 |
November | 3530.36 | 2704.07 | 826.29 | 5256.37 | 1777.95 | 0.00 | 0.00 | 0.00 |
December | 3841.87 | 3041.36 | 800.51 | 5548.75 | 2293.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2315.01 | 1362.00 | 953.01 | 3973.09 | 1143.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1061.94 | 81.86 | 800.51 | 2544.00 | 215.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4132.36 | 3300.40 | 1102.84 | 6233.62 | 2293.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1130.21 | 702.44 | 427.76 | 1631.51 | 1345.92 | 0.00 | 0.00 | 0.00 |
February | 915.58 | 442.63 | 472.95 | 1062.20 | 1287.28 | 0.00 | 0.00 | 0.00 |
March | 1212.71 | 578.12 | 634.59 | 1615.97 | 1173.11 | 0.00 | 0.00 | 0.00 |
April | 1862.16 | 1062.23 | 799.93 | 3098.07 | 737.12 | 0.00 | 0.00 | 0.00 |
May | 1866.94 | 1046.79 | 820.14 | 3317.47 | 534.12 | 0.00 | 0.00 | 0.00 |
June | 1984.74 | 1167.35 | 817.39 | 3998.71 | 238.84 | 0.00 | 0.00 | 0.00 |
July | 1444.54 | 674.31 | 770.23 | 2997.28 | 179.34 | 0.00 | 0.00 | 0.00 |
August | 1377.50 | 691.81 | 685.69 | 2846.08 | 219.67 | 0.00 | 0.00 | 0.00 |
September | 1200.71 | 504.49 | 696.22 | 2363.43 | 306.72 | 0.00 | 0.00 | 0.00 |
October | 1228.58 | 702.50 | 526.08 | 1971.11 | 873.29 | 0.00 | 0.00 | 0.00 |
November | 1131.55 | 683.20 | 448.35 | 1581.57 | 1243.81 | 0.00 | 0.00 | 0.00 |
December | 911.99 | 519.26 | 392.73 | 1182.21 | 1594.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1357.14 | 732.28 | 624.86 | 2310.70 | 809.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 911.99 | 442.63 | 392.73 | 1062.20 | 179.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1984.74 | 1167.35 | 820.14 | 3998.71 | 1594.74 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268840E+09 | 0.00 | 0.268840E+09 | 0.183027E+09 | 0.119244E+10 |
February | 0.276691E+09 | 0.00 | 0.276691E+09 | 0.113086E+09 | 0.108628E+10 |
March | 0.407121E+09 | 0.00 | 0.407121E+09 | 0.353607E+09 | 0.103457E+10 |
April | 0.480016E+09 | 4981337.40 | 0.475035E+09 | 0.768383E+09 | 0.525662E+09 |
May | 0.580640E+09 | 46492323.30 | 0.534148E+09 | 0.110728E+10 | 0.357141E+09 |
June | 0.652975E+09 | 0.118639E+09 | 0.534336E+09 | 0.166616E+10 | 0.137296E+09 |
July | 0.575426E+09 | 59947998.39 | 0.515478E+09 | 0.146389E+10 | 0.110526E+09 |
August | 0.464473E+09 | 11538584.38 | 0.452934E+09 | 0.119617E+10 | 0.150441E+09 |
September | 0.424087E+09 | 113210.59 | 0.423974E+09 | 0.978699E+09 | 0.213486E+09 |
October | 0.339043E+09 | 0.00 | 0.339043E+09 | 0.475169E+09 | 0.735390E+09 |
November | 0.273373E+09 | 0.00 | 0.273373E+09 | 0.182160E+09 | 0.107687E+10 |
December | 0.251121E+09 | 0.00 | 0.251121E+09 | 91904253.69 | 0.149089E+10 |
Annual Sum or Average | 0.499381E+10 | 0.241712E+09 | 0.475209E+10 | 0.857954E+10 | 0.811099E+10 |
Minimum of Months | 0.251121E+09 | 0.00 | 0.251121E+09 | 91904253.69 | 0.110526E+09 |
Maximum of Months | 0.652975E+09 | 0.118639E+09 | 0.534336E+09 | 0.166616E+10 | 0.149089E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268840E+09 | 0.00 | 0.268840E+09 | 0.183027E+09 | 0.119244E+10 |
February | 0.276691E+09 | 0.00 | 0.276691E+09 | 0.113086E+09 | 0.108628E+10 |
March | 0.407121E+09 | 0.00 | 0.407121E+09 | 0.353607E+09 | 0.103457E+10 |
April | 0.480016E+09 | 4981331.42 | 0.475035E+09 | 0.768382E+09 | 0.525662E+09 |
May | 0.580640E+09 | 46492267.52 | 0.534148E+09 | 0.110728E+10 | 0.357141E+09 |
June | 0.652974E+09 | 0.118639E+09 | 0.534336E+09 | 0.166616E+10 | 0.137296E+09 |
July | 0.575426E+09 | 59947926.46 | 0.515478E+09 | 0.146389E+10 | 0.110526E+09 |
August | 0.464472E+09 | 11538570.53 | 0.452934E+09 | 0.119617E+10 | 0.150441E+09 |
September | 0.424086E+09 | 113210.45 | 0.423973E+09 | 0.978699E+09 | 0.213486E+09 |
October | 0.339043E+09 | 0.00 | 0.339043E+09 | 0.475169E+09 | 0.735390E+09 |
November | 0.273373E+09 | 0.00 | 0.273373E+09 | 0.182160E+09 | 0.107687E+10 |
December | 0.251121E+09 | 0.00 | 0.251121E+09 | 91904167.02 | 0.149089E+10 |
Annual Sum or Average | 0.499380E+10 | 0.241712E+09 | 0.475209E+10 | 0.857954E+10 | 0.811099E+10 |
Minimum of Months | 0.251121E+09 | 0.00 | 0.251121E+09 | 91904167.02 | 0.110526E+09 |
Maximum of Months | 0.652974E+09 | 0.118639E+09 | 0.534336E+09 | 0.166616E+10 | 0.149089E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268840E+09 | 0.00 | 0.268840E+09 | 0.183027E+09 | 0.119244E+10 |
February | 0.276691E+09 | 0.00 | 0.276691E+09 | 0.113086E+09 | 0.108628E+10 |
March | 0.407121E+09 | 0.00 | 0.407121E+09 | 0.353607E+09 | 0.103457E+10 |
April | 0.480016E+09 | 4981337.40 | 0.475035E+09 | 0.768383E+09 | 0.525662E+09 |
May | 0.580640E+09 | 46492323.30 | 0.534148E+09 | 0.110728E+10 | 0.357141E+09 |
June | 0.652975E+09 | 0.118639E+09 | 0.534336E+09 | 0.166616E+10 | 0.137296E+09 |
July | 0.575426E+09 | 59947998.39 | 0.515478E+09 | 0.146389E+10 | 0.110526E+09 |
August | 0.464473E+09 | 11538584.38 | 0.452934E+09 | 0.119617E+10 | 0.150441E+09 |
September | 0.424087E+09 | 113210.59 | 0.423974E+09 | 0.978699E+09 | 0.213486E+09 |
October | 0.339043E+09 | 0.00 | 0.339043E+09 | 0.475169E+09 | 0.735390E+09 |
November | 0.273373E+09 | 0.00 | 0.273373E+09 | 0.182160E+09 | 0.107687E+10 |
December | 0.251121E+09 | 0.00 | 0.251121E+09 | 91904253.69 | 0.149089E+10 |
Annual Sum or Average | 0.499381E+10 | 0.241712E+09 | 0.475209E+10 | 0.857954E+10 | 0.811099E+10 |
Minimum of Months | 0.251121E+09 | 0.00 | 0.251121E+09 | 91904253.69 | 0.110526E+09 |
Maximum of Months | 0.652975E+09 | 0.118639E+09 | 0.534336E+09 | 0.166616E+10 | 0.149089E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268840E+09 | 0.00 | 0.268840E+09 | 0.183027E+09 | 0.119244E+10 |
February | 0.276691E+09 | 0.00 | 0.276691E+09 | 0.113086E+09 | 0.108628E+10 |
March | 0.407121E+09 | 0.00 | 0.407121E+09 | 0.353607E+09 | 0.103457E+10 |
April | 0.480016E+09 | 4981331.42 | 0.475035E+09 | 0.768382E+09 | 0.525662E+09 |
May | 0.580640E+09 | 46492267.52 | 0.534148E+09 | 0.110728E+10 | 0.357141E+09 |
June | 0.652974E+09 | 0.118639E+09 | 0.534336E+09 | 0.166616E+10 | 0.137296E+09 |
July | 0.575426E+09 | 59947926.46 | 0.515478E+09 | 0.146389E+10 | 0.110526E+09 |
August | 0.464472E+09 | 11538570.53 | 0.452934E+09 | 0.119617E+10 | 0.150441E+09 |
September | 0.424086E+09 | 113210.45 | 0.423973E+09 | 0.978699E+09 | 0.213486E+09 |
October | 0.339043E+09 | 0.00 | 0.339043E+09 | 0.475169E+09 | 0.735390E+09 |
November | 0.273373E+09 | 0.00 | 0.273373E+09 | 0.182160E+09 | 0.107687E+10 |
December | 0.251121E+09 | 0.00 | 0.251121E+09 | 91904167.02 | 0.149089E+10 |
Annual Sum or Average | 0.499380E+10 | 0.241712E+09 | 0.475209E+10 | 0.857954E+10 | 0.811099E+10 |
Minimum of Months | 0.251121E+09 | 0.00 | 0.251121E+09 | 91904167.02 | 0.110526E+09 |
Maximum of Months | 0.652974E+09 | 0.118639E+09 | 0.534336E+09 | 0.166616E+10 | 0.149089E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268829E+09 | 0.00 | 0.268829E+09 | 0.183020E+09 | 0.119239E+10 |
February | 0.276680E+09 | 0.00 | 0.276680E+09 | 0.113082E+09 | 0.108624E+10 |
March | 0.407105E+09 | 0.00 | 0.407105E+09 | 0.353593E+09 | 0.103453E+10 |
April | 0.479997E+09 | 4981136.63 | 0.475016E+09 | 0.768352E+09 | 0.525641E+09 |
May | 0.580617E+09 | 46490449.46 | 0.534127E+09 | 0.110724E+10 | 0.357127E+09 |
June | 0.652949E+09 | 0.118634E+09 | 0.534314E+09 | 0.166610E+10 | 0.137291E+09 |
July | 0.575403E+09 | 59945582.22 | 0.515457E+09 | 0.146384E+10 | 0.110522E+09 |
August | 0.464454E+09 | 11538119.32 | 0.452916E+09 | 0.119612E+10 | 0.150435E+09 |
September | 0.424070E+09 | 113206.03 | 0.423956E+09 | 0.978660E+09 | 0.213477E+09 |
October | 0.339029E+09 | 0.00 | 0.339029E+09 | 0.475150E+09 | 0.735360E+09 |
November | 0.273362E+09 | 0.00 | 0.273362E+09 | 0.182153E+09 | 0.107683E+10 |
December | 0.251111E+09 | 0.00 | 0.251111E+09 | 91900549.54 | 0.149083E+10 |
Annual Sum or Average | 0.499361E+10 | 0.241703E+09 | 0.475190E+10 | 0.857919E+10 | 0.811066E+10 |
Minimum of Months | 0.251111E+09 | 0.00 | 0.251111E+09 | 91900549.54 | 0.110522E+09 |
Maximum of Months | 0.652949E+09 | 0.118634E+09 | 0.534314E+09 | 0.166610E+10 | 0.149083E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.964978E+09 | 0.605357E+09 | 0.359620E+09 | 0.120969E+10 | 0.121308E+10 |
February | 0.859124E+09 | 0.491458E+09 | 0.367666E+09 | 0.957689E+09 | 0.110906E+10 |
March | 0.119035E+10 | 0.612325E+09 | 0.578025E+09 | 0.153553E+10 | 0.104604E+10 |
April | 0.164435E+10 | 0.980052E+09 | 0.664295E+09 | 0.270493E+10 | 0.534852E+09 |
May | 0.176094E+10 | 0.104387E+10 | 0.717070E+09 | 0.309312E+10 | 0.397916E+09 |
June | 0.177626E+10 | 0.110374E+10 | 0.672518E+09 | 0.358384E+10 | 0.145652E+09 |
July | 0.155017E+10 | 0.874079E+09 | 0.676093E+09 | 0.316142E+10 | 0.113158E+09 |
August | 0.147125E+10 | 0.839640E+09 | 0.631608E+09 | 0.297541E+10 | 0.146190E+09 |
September | 0.116832E+10 | 0.563149E+09 | 0.605167E+09 | 0.227449E+10 | 0.222104E+09 |
October | 0.121262E+10 | 0.737992E+09 | 0.474628E+09 | 0.188741E+10 | 0.747622E+09 |
November | 0.902358E+09 | 0.541698E+09 | 0.360661E+09 | 0.112764E+10 | 0.108966E+10 |
December | 0.850139E+09 | 0.513339E+09 | 0.336800E+09 | 0.922225E+09 | 0.147807E+10 |
Annual Sum or Average | 0.153509E+11 | 0.890670E+10 | 0.644415E+10 | 0.254334E+11 | 0.824340E+10 |
Minimum of Months | 0.850139E+09 | 0.491458E+09 | 0.336800E+09 | 0.922225E+09 | 0.113158E+09 |
Maximum of Months | 0.177626E+10 | 0.110374E+10 | 0.717070E+09 | 0.358384E+10 | 0.147807E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.964978E+09 | 0.605357E+09 | 0.359620E+09 | 0.120969E+10 | 0.121308E+10 |
February | 0.859124E+09 | 0.491458E+09 | 0.367666E+09 | 0.957689E+09 | 0.110906E+10 |
March | 0.119035E+10 | 0.612325E+09 | 0.578025E+09 | 0.153553E+10 | 0.104604E+10 |
April | 0.164435E+10 | 0.980052E+09 | 0.664295E+09 | 0.270493E+10 | 0.534852E+09 |
May | 0.176094E+10 | 0.104387E+10 | 0.717070E+09 | 0.309312E+10 | 0.397916E+09 |
June | 0.177626E+10 | 0.110374E+10 | 0.672518E+09 | 0.358384E+10 | 0.145652E+09 |
July | 0.155017E+10 | 0.874079E+09 | 0.676093E+09 | 0.316142E+10 | 0.113158E+09 |
August | 0.147125E+10 | 0.839640E+09 | 0.631608E+09 | 0.297541E+10 | 0.146190E+09 |
September | 0.116832E+10 | 0.563149E+09 | 0.605167E+09 | 0.227449E+10 | 0.222104E+09 |
October | 0.121262E+10 | 0.737992E+09 | 0.474628E+09 | 0.188741E+10 | 0.747622E+09 |
November | 0.902358E+09 | 0.541698E+09 | 0.360661E+09 | 0.112764E+10 | 0.108966E+10 |
December | 0.850139E+09 | 0.513339E+09 | 0.336800E+09 | 0.922225E+09 | 0.147807E+10 |
Annual Sum or Average | 0.153509E+11 | 0.890670E+10 | 0.644415E+10 | 0.254334E+11 | 0.824340E+10 |
Minimum of Months | 0.850139E+09 | 0.491458E+09 | 0.336800E+09 | 0.922225E+09 | 0.113158E+09 |
Maximum of Months | 0.177626E+10 | 0.110374E+10 | 0.717070E+09 | 0.358384E+10 | 0.147807E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.964960E+09 | 0.605346E+09 | 0.359614E+09 | 0.120966E+10 | 0.121306E+10 |
February | 0.859108E+09 | 0.491449E+09 | 0.367659E+09 | 0.957671E+09 | 0.110904E+10 |
March | 0.119033E+10 | 0.612314E+09 | 0.578014E+09 | 0.153551E+10 | 0.104602E+10 |
April | 0.164432E+10 | 0.980034E+09 | 0.664283E+09 | 0.270488E+10 | 0.534842E+09 |
May | 0.176091E+10 | 0.104385E+10 | 0.717057E+09 | 0.309307E+10 | 0.397909E+09 |
June | 0.177623E+10 | 0.110372E+10 | 0.672505E+09 | 0.358377E+10 | 0.145649E+09 |
July | 0.155014E+10 | 0.874063E+09 | 0.676081E+09 | 0.316136E+10 | 0.113156E+09 |
August | 0.147122E+10 | 0.839624E+09 | 0.631596E+09 | 0.297535E+10 | 0.146188E+09 |
September | 0.116829E+10 | 0.563138E+09 | 0.605156E+09 | 0.227444E+10 | 0.222100E+09 |
October | 0.121260E+10 | 0.737979E+09 | 0.474619E+09 | 0.188738E+10 | 0.747608E+09 |
November | 0.902342E+09 | 0.541688E+09 | 0.360654E+09 | 0.112762E+10 | 0.108964E+10 |
December | 0.850123E+09 | 0.513329E+09 | 0.336794E+09 | 0.922208E+09 | 0.147804E+10 |
Annual Sum or Average | 0.153506E+11 | 0.890654E+10 | 0.644403E+10 | 0.254329E+11 | 0.824325E+10 |
Minimum of Months | 0.850123E+09 | 0.491449E+09 | 0.336794E+09 | 0.922208E+09 | 0.113156E+09 |
Maximum of Months | 0.177623E+10 | 0.110372E+10 | 0.717057E+09 | 0.358377E+10 | 0.147804E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221365E+10 | 0.176798E+10 | 0.445670E+09 | 0.334434E+10 | 0.113027E+10 |
February | 0.126421E+10 | 0.852627E+09 | 0.411583E+09 | 0.171101E+10 | 0.100175E+10 |
March | 0.116462E+10 | 0.599841E+09 | 0.564780E+09 | 0.169258E+10 | 0.100331E+10 |
April | 0.959417E+09 | 0.387698E+09 | 0.571719E+09 | 0.178785E+10 | 0.551913E+09 |
May | 0.664339E+09 | 0.109757E+09 | 0.554583E+09 | 0.136397E+10 | 0.393114E+09 |
June | 0.550516E+09 | 42437723.04 | 0.508079E+09 | 0.149578E+10 | 0.144578E+09 |
July | 0.581283E+09 | 60138531.93 | 0.521144E+09 | 0.150817E+10 | 0.113386E+09 |
August | 0.706812E+09 | 0.195328E+09 | 0.511484E+09 | 0.173996E+10 | 0.153799E+09 |
September | 0.985596E+09 | 0.420480E+09 | 0.565116E+09 | 0.205854E+10 | 0.221396E+09 |
October | 0.162279E+10 | 0.112321E+10 | 0.499577E+09 | 0.269756E+10 | 0.712092E+09 |
November | 0.183016E+10 | 0.140181E+10 | 0.428351E+09 | 0.272538E+10 | 0.101105E+10 |
December | 0.205804E+10 | 0.162921E+10 | 0.428824E+09 | 0.295345E+10 | 0.136222E+10 |
Annual Sum or Average | 0.146014E+11 | 0.859052E+10 | 0.601091E+10 | 0.250786E+11 | 0.779887E+10 |
Minimum of Months | 0.550516E+09 | 42437723.04 | 0.411583E+09 | 0.136397E+10 | 0.113386E+09 |
Maximum of Months | 0.221365E+10 | 0.176798E+10 | 0.571719E+09 | 0.334434E+10 | 0.136222E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221365E+10 | 0.176798E+10 | 0.445670E+09 | 0.334433E+10 | 0.113027E+10 |
February | 0.126421E+10 | 0.852626E+09 | 0.411582E+09 | 0.171101E+10 | 0.100175E+10 |
March | 0.116462E+10 | 0.599840E+09 | 0.564780E+09 | 0.169258E+10 | 0.100331E+10 |
April | 0.959416E+09 | 0.387698E+09 | 0.571718E+09 | 0.178785E+10 | 0.551912E+09 |
May | 0.664339E+09 | 0.109756E+09 | 0.554583E+09 | 0.136397E+10 | 0.393113E+09 |
June | 0.550516E+09 | 42437672.12 | 0.508078E+09 | 0.149578E+10 | 0.144578E+09 |
July | 0.581282E+09 | 60138459.77 | 0.521144E+09 | 0.150817E+10 | 0.113386E+09 |
August | 0.706811E+09 | 0.195328E+09 | 0.511483E+09 | 0.173996E+10 | 0.153799E+09 |
September | 0.985595E+09 | 0.420479E+09 | 0.565116E+09 | 0.205854E+10 | 0.221396E+09 |
October | 0.162279E+10 | 0.112321E+10 | 0.499577E+09 | 0.269756E+10 | 0.712092E+09 |
November | 0.183016E+10 | 0.140181E+10 | 0.428351E+09 | 0.272538E+10 | 0.101104E+10 |
December | 0.205804E+10 | 0.162921E+10 | 0.428824E+09 | 0.295345E+10 | 0.136222E+10 |
Annual Sum or Average | 0.146014E+11 | 0.859051E+10 | 0.601091E+10 | 0.250786E+11 | 0.779887E+10 |
Minimum of Months | 0.550516E+09 | 42437672.12 | 0.411582E+09 | 0.136397E+10 | 0.113386E+09 |
Maximum of Months | 0.221365E+10 | 0.176798E+10 | 0.571718E+09 | 0.334433E+10 | 0.136222E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221365E+10 | 0.176798E+10 | 0.445670E+09 | 0.334434E+10 | 0.113027E+10 |
February | 0.126421E+10 | 0.852627E+09 | 0.411583E+09 | 0.171101E+10 | 0.100175E+10 |
March | 0.116462E+10 | 0.599841E+09 | 0.564780E+09 | 0.169258E+10 | 0.100331E+10 |
April | 0.959417E+09 | 0.387698E+09 | 0.571719E+09 | 0.178785E+10 | 0.551913E+09 |
May | 0.664339E+09 | 0.109757E+09 | 0.554583E+09 | 0.136397E+10 | 0.393114E+09 |
June | 0.550516E+09 | 42437723.04 | 0.508079E+09 | 0.149578E+10 | 0.144578E+09 |
July | 0.581283E+09 | 60138531.93 | 0.521144E+09 | 0.150817E+10 | 0.113386E+09 |
August | 0.706812E+09 | 0.195328E+09 | 0.511484E+09 | 0.173996E+10 | 0.153799E+09 |
September | 0.985596E+09 | 0.420480E+09 | 0.565116E+09 | 0.205854E+10 | 0.221396E+09 |
October | 0.162279E+10 | 0.112321E+10 | 0.499577E+09 | 0.269756E+10 | 0.712092E+09 |
November | 0.183016E+10 | 0.140181E+10 | 0.428351E+09 | 0.272538E+10 | 0.101105E+10 |
December | 0.205804E+10 | 0.162921E+10 | 0.428824E+09 | 0.295345E+10 | 0.136222E+10 |
Annual Sum or Average | 0.146014E+11 | 0.859052E+10 | 0.601091E+10 | 0.250786E+11 | 0.779887E+10 |
Minimum of Months | 0.550516E+09 | 42437723.04 | 0.411583E+09 | 0.136397E+10 | 0.113386E+09 |
Maximum of Months | 0.221365E+10 | 0.176798E+10 | 0.571719E+09 | 0.334434E+10 | 0.136222E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221365E+10 | 0.176798E+10 | 0.445670E+09 | 0.334433E+10 | 0.113027E+10 |
February | 0.126421E+10 | 0.852626E+09 | 0.411582E+09 | 0.171101E+10 | 0.100175E+10 |
March | 0.116462E+10 | 0.599840E+09 | 0.564780E+09 | 0.169258E+10 | 0.100331E+10 |
April | 0.959416E+09 | 0.387698E+09 | 0.571718E+09 | 0.178785E+10 | 0.551912E+09 |
May | 0.664339E+09 | 0.109756E+09 | 0.554583E+09 | 0.136397E+10 | 0.393113E+09 |
June | 0.550516E+09 | 42437672.12 | 0.508078E+09 | 0.149578E+10 | 0.144578E+09 |
July | 0.581282E+09 | 60138459.77 | 0.521144E+09 | 0.150817E+10 | 0.113386E+09 |
August | 0.706811E+09 | 0.195328E+09 | 0.511483E+09 | 0.173996E+10 | 0.153799E+09 |
September | 0.985595E+09 | 0.420479E+09 | 0.565116E+09 | 0.205854E+10 | 0.221396E+09 |
October | 0.162279E+10 | 0.112321E+10 | 0.499577E+09 | 0.269756E+10 | 0.712092E+09 |
November | 0.183016E+10 | 0.140181E+10 | 0.428351E+09 | 0.272538E+10 | 0.101104E+10 |
December | 0.205804E+10 | 0.162921E+10 | 0.428824E+09 | 0.295345E+10 | 0.136222E+10 |
Annual Sum or Average | 0.146014E+11 | 0.859051E+10 | 0.601091E+10 | 0.250786E+11 | 0.779887E+10 |
Minimum of Months | 0.550516E+09 | 42437672.12 | 0.411582E+09 | 0.136397E+10 | 0.113386E+09 |
Maximum of Months | 0.221365E+10 | 0.176798E+10 | 0.571718E+09 | 0.334433E+10 | 0.136222E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221356E+10 | 0.176791E+10 | 0.445652E+09 | 0.334420E+10 | 0.113023E+10 |
February | 0.126416E+10 | 0.852593E+09 | 0.411566E+09 | 0.171095E+10 | 0.100171E+10 |
March | 0.116457E+10 | 0.599817E+09 | 0.564758E+09 | 0.169252E+10 | 0.100327E+10 |
April | 0.959378E+09 | 0.387682E+09 | 0.571696E+09 | 0.178778E+10 | 0.551890E+09 |
May | 0.664313E+09 | 0.109752E+09 | 0.554561E+09 | 0.136392E+10 | 0.393098E+09 |
June | 0.550494E+09 | 42436012.61 | 0.508058E+09 | 0.149572E+10 | 0.144572E+09 |
July | 0.581259E+09 | 60136108.09 | 0.521123E+09 | 0.150811E+10 | 0.113381E+09 |
August | 0.706783E+09 | 0.195320E+09 | 0.511463E+09 | 0.173989E+10 | 0.153793E+09 |
September | 0.985556E+09 | 0.420463E+09 | 0.565093E+09 | 0.205846E+10 | 0.221387E+09 |
October | 0.162273E+10 | 0.112317E+10 | 0.499557E+09 | 0.269745E+10 | 0.712064E+09 |
November | 0.183009E+10 | 0.140175E+10 | 0.428334E+09 | 0.272527E+10 | 0.101100E+10 |
December | 0.205795E+10 | 0.162915E+10 | 0.428807E+09 | 0.295333E+10 | 0.136216E+10 |
Annual Sum or Average | 0.146008E+11 | 0.859018E+10 | 0.601067E+10 | 0.250776E+11 | 0.779856E+10 |
Minimum of Months | 0.550494E+09 | 42436012.61 | 0.411566E+09 | 0.136392E+10 | 0.113381E+09 |
Maximum of Months | 0.221356E+10 | 0.176791E+10 | 0.571696E+09 | 0.334420E+10 | 0.136216E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100906E+10 | 0.627146E+09 | 0.381912E+09 | 0.140854E+10 | 0.142849E+10 |
February | 0.738329E+09 | 0.356937E+09 | 0.381392E+09 | 0.814530E+09 | 0.131518E+10 |
March | 0.108272E+10 | 0.516149E+09 | 0.566569E+09 | 0.138650E+10 | 0.127302E+10 |
April | 0.160892E+10 | 0.917776E+09 | 0.691142E+09 | 0.264616E+10 | 0.747368E+09 |
May | 0.166682E+10 | 0.934586E+09 | 0.732231E+09 | 0.296801E+10 | 0.512747E+09 |
June | 0.171483E+10 | 0.100860E+10 | 0.706234E+09 | 0.344913E+10 | 0.226740E+09 |
July | 0.128970E+10 | 0.602026E+09 | 0.687671E+09 | 0.264471E+10 | 0.190854E+09 |
August | 0.122984E+10 | 0.617651E+09 | 0.612190E+09 | 0.247947E+10 | 0.274161E+09 |
September | 0.103743E+10 | 0.435885E+09 | 0.601543E+09 | 0.203809E+10 | 0.294880E+09 |
October | 0.109689E+10 | 0.627199E+09 | 0.469690E+09 | 0.172949E+10 | 0.921792E+09 |
November | 0.977673E+09 | 0.590291E+09 | 0.387383E+09 | 0.131535E+10 | 0.134305E+10 |
December | 0.814229E+09 | 0.463597E+09 | 0.350632E+09 | 0.974070E+09 | 0.184047E+10 |
Annual Sum or Average | 0.142664E+11 | 0.769784E+10 | 0.656859E+10 | 0.238540E+11 | 0.103687E+11 |
Minimum of Months | 0.738329E+09 | 0.356937E+09 | 0.350632E+09 | 0.814530E+09 | 0.190854E+09 |
Maximum of Months | 0.171483E+10 | 0.100860E+10 | 0.732231E+09 | 0.344913E+10 | 0.184047E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100906E+10 | 0.627146E+09 | 0.381912E+09 | 0.140854E+10 | 0.142849E+10 |
February | 0.738329E+09 | 0.356937E+09 | 0.381392E+09 | 0.814530E+09 | 0.131518E+10 |
March | 0.108272E+10 | 0.516149E+09 | 0.566569E+09 | 0.138650E+10 | 0.127302E+10 |
April | 0.160892E+10 | 0.917776E+09 | 0.691142E+09 | 0.264616E+10 | 0.747368E+09 |
May | 0.166682E+10 | 0.934586E+09 | 0.732231E+09 | 0.296801E+10 | 0.512747E+09 |
June | 0.171483E+10 | 0.100860E+10 | 0.706234E+09 | 0.344913E+10 | 0.226740E+09 |
July | 0.128970E+10 | 0.602026E+09 | 0.687671E+09 | 0.264471E+10 | 0.190854E+09 |
August | 0.122984E+10 | 0.617651E+09 | 0.612190E+09 | 0.247947E+10 | 0.274161E+09 |
September | 0.103743E+10 | 0.435885E+09 | 0.601543E+09 | 0.203809E+10 | 0.294880E+09 |
October | 0.109689E+10 | 0.627199E+09 | 0.469690E+09 | 0.172949E+10 | 0.921792E+09 |
November | 0.977673E+09 | 0.590291E+09 | 0.387383E+09 | 0.131535E+10 | 0.134305E+10 |
December | 0.814229E+09 | 0.463597E+09 | 0.350632E+09 | 0.974070E+09 | 0.184047E+10 |
Annual Sum or Average | 0.142664E+11 | 0.769784E+10 | 0.656859E+10 | 0.238540E+11 | 0.103687E+11 |
Minimum of Months | 0.738329E+09 | 0.356937E+09 | 0.350632E+09 | 0.814530E+09 | 0.190854E+09 |
Maximum of Months | 0.171483E+10 | 0.100860E+10 | 0.732231E+09 | 0.344913E+10 | 0.184047E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.100904E+10 | 0.627134E+09 | 0.381906E+09 | 0.140851E+10 | 0.142846E+10 |
February | 0.738315E+09 | 0.356930E+09 | 0.381385E+09 | 0.814515E+09 | 0.131516E+10 |
March | 0.108270E+10 | 0.516140E+09 | 0.566559E+09 | 0.138648E+10 | 0.127300E+10 |
April | 0.160889E+10 | 0.917759E+09 | 0.691130E+09 | 0.264611E+10 | 0.747354E+09 |
May | 0.166679E+10 | 0.934569E+09 | 0.732217E+09 | 0.296795E+10 | 0.512738E+09 |
June | 0.171480E+10 | 0.100858E+10 | 0.706221E+09 | 0.344906E+10 | 0.226736E+09 |
July | 0.128967E+10 | 0.602015E+09 | 0.687658E+09 | 0.264466E+10 | 0.190850E+09 |
August | 0.122982E+10 | 0.617640E+09 | 0.612179E+09 | 0.247943E+10 | 0.274156E+09 |
September | 0.103741E+10 | 0.435877E+09 | 0.601532E+09 | 0.203805E+10 | 0.294875E+09 |
October | 0.109687E+10 | 0.627187E+09 | 0.469682E+09 | 0.172946E+10 | 0.921775E+09 |
November | 0.977655E+09 | 0.590280E+09 | 0.387376E+09 | 0.131533E+10 | 0.134303E+10 |
December | 0.814214E+09 | 0.463589E+09 | 0.350626E+09 | 0.974052E+09 | 0.184043E+10 |
Annual Sum or Average | 0.142662E+11 | 0.769770E+10 | 0.656847E+10 | 0.238536E+11 | 0.103686E+11 |
Minimum of Months | 0.738315E+09 | 0.356930E+09 | 0.350626E+09 | 0.814515E+09 | 0.190850E+09 |
Maximum of Months | 0.171480E+10 | 0.100858E+10 | 0.732217E+09 | 0.344906E+10 | 0.184043E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134418E+10 | 0.00 | 0.134418E+10 | 0.111294E+10 | 0.531871E+10 |
February | 0.138344E+10 | 0.00 | 0.138344E+10 | 0.686615E+09 | 0.480968E+10 |
March | 0.203558E+10 | 0.00 | 0.203558E+10 | 0.192248E+10 | 0.469223E+10 |
April | 0.240005E+10 | 24906385.81 | 0.237515E+10 | 0.398264E+10 | 0.247840E+10 |
May | 0.290317E+10 | 0.232459E+09 | 0.267071E+10 | 0.561683E+10 | 0.173339E+10 |
June | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.841627E+10 | 0.694797E+09 |
July | 0.287710E+10 | 0.299736E+09 | 0.257736E+10 | 0.742289E+10 | 0.546735E+09 |
August | 0.232234E+10 | 57692224.27 | 0.226464E+10 | 0.615167E+10 | 0.683961E+09 |
September | 0.212041E+10 | 566046.10 | 0.211984E+10 | 0.495745E+10 | 0.103363E+10 |
October | 0.169519E+10 | 0.00 | 0.169519E+10 | 0.250426E+10 | 0.337069E+10 |
November | 0.136685E+10 | 0.00 | 0.136685E+10 | 0.107195E+10 | 0.476422E+10 |
December | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.679298E+09 | 0.648052E+10 |
Annual Sum or Average | 0.249687E+11 | 0.120855E+10 | 0.237602E+11 | 0.445253E+11 | 0.366069E+11 |
Minimum of Months | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.679298E+09 | 0.546735E+09 |
Maximum of Months | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.841627E+10 | 0.648052E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289490E+10 | 0.181605E+10 | 0.107885E+10 | 0.366107E+10 | 0.340047E+10 |
February | 0.257735E+10 | 0.147436E+10 | 0.110299E+10 | 0.287521E+10 | 0.311500E+10 |
March | 0.357101E+10 | 0.183696E+10 | 0.173406E+10 | 0.458133E+10 | 0.301066E+10 |
April | 0.493299E+10 | 0.294013E+10 | 0.199286E+10 | 0.803852E+10 | 0.162991E+10 |
May | 0.528277E+10 | 0.313158E+10 | 0.215119E+10 | 0.920321E+10 | 0.119632E+10 |
June | 0.532873E+10 | 0.331120E+10 | 0.201753E+10 | 0.106725E+11 | 0.467182E+09 |
July | 0.465047E+10 | 0.262221E+10 | 0.202826E+10 | 0.940675E+10 | 0.370029E+09 |
August | 0.441370E+10 | 0.251889E+10 | 0.189480E+10 | 0.886650E+10 | 0.466506E+09 |
September | 0.350491E+10 | 0.168943E+10 | 0.181548E+10 | 0.676381E+10 | 0.677642E+09 |
October | 0.363782E+10 | 0.221395E+10 | 0.142387E+10 | 0.562604E+10 | 0.216505E+10 |
November | 0.270705E+10 | 0.162508E+10 | 0.108197E+10 | 0.339427E+10 | 0.306907E+10 |
December | 0.255039E+10 | 0.154000E+10 | 0.101039E+10 | 0.283206E+10 | 0.412692E+10 |
Annual Sum or Average | 0.460521E+11 | 0.267198E+11 | 0.193323E+11 | 0.759213E+11 | 0.236947E+11 |
Minimum of Months | 0.255039E+10 | 0.147436E+10 | 0.101039E+10 | 0.283206E+10 | 0.370029E+09 |
Maximum of Months | 0.532873E+10 | 0.331120E+10 | 0.215119E+10 | 0.106725E+11 | 0.412692E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110681E+11 | 0.883980E+10 | 0.222832E+10 | 0.165912E+11 | 0.556055E+10 |
February | 0.632097E+10 | 0.426308E+10 | 0.205789E+10 | 0.849495E+10 | 0.483518E+10 |
March | 0.582304E+10 | 0.299917E+10 | 0.282387E+10 | 0.843348E+10 | 0.483269E+10 |
April | 0.479703E+10 | 0.193847E+10 | 0.285856E+10 | 0.895263E+10 | 0.268041E+10 |
May | 0.332166E+10 | 0.548776E+09 | 0.277288E+10 | 0.687098E+10 | 0.191527E+10 |
June | 0.275255E+10 | 0.212186E+09 | 0.254036E+10 | 0.758738E+10 | 0.713931E+09 |
July | 0.290638E+10 | 0.300689E+09 | 0.260569E+10 | 0.764233E+10 | 0.552057E+09 |
August | 0.353402E+10 | 0.976628E+09 | 0.255739E+10 | 0.881145E+10 | 0.709264E+09 |
September | 0.492792E+10 | 0.210237E+10 | 0.282555E+10 | 0.102655E+11 | 0.109213E+10 |
October | 0.811386E+10 | 0.561600E+10 | 0.249786E+10 | 0.133932E+11 | 0.347863E+10 |
November | 0.915068E+10 | 0.700895E+10 | 0.214173E+10 | 0.135386E+11 | 0.490119E+10 |
December | 0.102901E+11 | 0.814597E+10 | 0.214409E+10 | 0.147161E+11 | 0.658963E+10 |
Annual Sum or Average | 0.730063E+11 | 0.429521E+11 | 0.300542E+11 | 0.125298E+12 | 0.378609E+11 |
Minimum of Months | 0.275255E+10 | 0.212186E+09 | 0.205789E+10 | 0.687098E+10 | 0.552057E+09 |
Maximum of Months | 0.110681E+11 | 0.883980E+10 | 0.285856E+10 | 0.165912E+11 | 0.658963E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302714E+10 | 0.188142E+10 | 0.114573E+10 | 0.431722E+10 | 0.385285E+10 |
February | 0.221496E+10 | 0.107080E+10 | 0.114416E+10 | 0.252848E+10 | 0.337844E+10 |
March | 0.324812E+10 | 0.154843E+10 | 0.169969E+10 | 0.429807E+10 | 0.330544E+10 |
April | 0.482671E+10 | 0.275330E+10 | 0.207341E+10 | 0.806895E+10 | 0.194415E+10 |
May | 0.500040E+10 | 0.280373E+10 | 0.219667E+10 | 0.893577E+10 | 0.143821E+10 |
June | 0.514444E+10 | 0.302576E+10 | 0.211868E+10 | 0.104363E+11 | 0.607929E+09 |
July | 0.386905E+10 | 0.180606E+10 | 0.206299E+10 | 0.810086E+10 | 0.466150E+09 |
August | 0.368949E+10 | 0.185294E+10 | 0.183655E+10 | 0.768143E+10 | 0.578899E+09 |
September | 0.311225E+10 | 0.130764E+10 | 0.180461E+10 | 0.617278E+10 | 0.786147E+09 |
October | 0.329063E+10 | 0.188158E+10 | 0.140906E+10 | 0.528072E+10 | 0.244185E+10 |
November | 0.293299E+10 | 0.177085E+10 | 0.116214E+10 | 0.406233E+10 | 0.344057E+10 |
December | 0.244266E+10 | 0.139078E+10 | 0.105189E+10 | 0.309716E+10 | 0.459899E+10 |
Annual Sum or Average | 0.427989E+11 | 0.230933E+11 | 0.197056E+11 | 0.729801E+11 | 0.268396E+11 |
Minimum of Months | 0.221496E+10 | 0.107080E+10 | 0.105189E+10 | 0.252848E+10 | 0.466150E+09 |
Maximum of Months | 0.514444E+10 | 0.302576E+10 | 0.219667E+10 | 0.104363E+11 | 0.459899E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134418E+10 | 0.00 | 0.134418E+10 | 0.124230E+10 | 0.488517E+10 |
February | 0.138344E+10 | 0.00 | 0.138344E+10 | 0.784128E+09 | 0.433825E+10 |
March | 0.203558E+10 | 0.00 | 0.203558E+10 | 0.201206E+10 | 0.440534E+10 |
April | 0.240005E+10 | 24906385.81 | 0.237515E+10 | 0.395040E+10 | 0.243145E+10 |
May | 0.290317E+10 | 0.232459E+09 | 0.267071E+10 | 0.556439E+10 | 0.173577E+10 |
June | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.831667E+10 | 0.718211E+09 |
July | 0.287710E+10 | 0.299736E+09 | 0.257736E+10 | 0.730490E+10 | 0.575111E+09 |
August | 0.232234E+10 | 57692224.27 | 0.226464E+10 | 0.606292E+10 | 0.704719E+09 |
September | 0.212041E+10 | 566046.10 | 0.211984E+10 | 0.489160E+10 | 0.104836E+10 |
October | 0.169519E+10 | 0.00 | 0.169519E+10 | 0.253658E+10 | 0.318917E+10 |
November | 0.136685E+10 | 0.00 | 0.136685E+10 | 0.117672E+10 | 0.437166E+10 |
December | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.822779E+09 | 0.590217E+10 |
Annual Sum or Average | 0.249687E+11 | 0.120855E+10 | 0.237602E+11 | 0.446654E+11 | 0.343054E+11 |
Minimum of Months | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.784128E+09 | 0.575111E+09 |
Maximum of Months | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.831667E+10 | 0.590217E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.289490E+10 | 0.181605E+10 | 0.107885E+10 | 0.377041E+10 | 0.316262E+10 |
February | 0.257735E+10 | 0.147436E+10 | 0.110299E+10 | 0.295438E+10 | 0.284588E+10 |
March | 0.357101E+10 | 0.183696E+10 | 0.173406E+10 | 0.465025E+10 | 0.286005E+10 |
April | 0.493299E+10 | 0.294013E+10 | 0.199286E+10 | 0.802274E+10 | 0.161186E+10 |
May | 0.528277E+10 | 0.313158E+10 | 0.215119E+10 | 0.917174E+10 | 0.119632E+10 |
June | 0.532873E+10 | 0.331120E+10 | 0.201753E+10 | 0.106143E+11 | 0.480473E+09 |
July | 0.465047E+10 | 0.262221E+10 | 0.202826E+10 | 0.934157E+10 | 0.386875E+09 |
August | 0.441370E+10 | 0.251889E+10 | 0.189480E+10 | 0.881914E+10 | 0.477440E+09 |
September | 0.350491E+10 | 0.168943E+10 | 0.181548E+10 | 0.673122E+10 | 0.687125E+09 |
October | 0.363782E+10 | 0.221395E+10 | 0.142387E+10 | 0.565203E+10 | 0.207380E+10 |
November | 0.270705E+10 | 0.162508E+10 | 0.108197E+10 | 0.348373E+10 | 0.284843E+10 |
December | 0.255039E+10 | 0.154000E+10 | 0.101039E+10 | 0.298379E+10 | 0.377713E+10 |
Annual Sum or Average | 0.460521E+11 | 0.267198E+11 | 0.193323E+11 | 0.761953E+11 | 0.224080E+11 |
Minimum of Months | 0.255039E+10 | 0.147436E+10 | 0.101039E+10 | 0.295438E+10 | 0.386875E+09 |
Maximum of Months | 0.532873E+10 | 0.331120E+10 | 0.215119E+10 | 0.106143E+11 | 0.377713E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110681E+11 | 0.883980E+10 | 0.222832E+10 | 0.166961E+11 | 0.523253E+10 |
February | 0.632097E+10 | 0.426308E+10 | 0.205789E+10 | 0.858586E+10 | 0.444885E+10 |
March | 0.582304E+10 | 0.299917E+10 | 0.282387E+10 | 0.849071E+10 | 0.459061E+10 |
April | 0.479703E+10 | 0.193847E+10 | 0.285856E+10 | 0.890511E+10 | 0.263492E+10 |
May | 0.332166E+10 | 0.548776E+09 | 0.277288E+10 | 0.681385E+10 | 0.190708E+10 |
June | 0.275255E+10 | 0.212186E+09 | 0.254036E+10 | 0.748744E+10 | 0.733581E+09 |
July | 0.290638E+10 | 0.300689E+09 | 0.260569E+10 | 0.752403E+10 | 0.577660E+09 |
August | 0.353402E+10 | 0.976628E+09 | 0.255739E+10 | 0.871813E+10 | 0.726823E+09 |
September | 0.492792E+10 | 0.210237E+10 | 0.282555E+10 | 0.101907E+11 | 0.110848E+10 |
October | 0.811386E+10 | 0.561600E+10 | 0.249786E+10 | 0.133971E+11 | 0.334167E+10 |
November | 0.915068E+10 | 0.700895E+10 | 0.214173E+10 | 0.136245E+11 | 0.460846E+10 |
December | 0.102901E+11 | 0.814597E+10 | 0.214409E+10 | 0.148618E+11 | 0.614340E+10 |
Annual Sum or Average | 0.730063E+11 | 0.429521E+11 | 0.300542E+11 | 0.125295E+12 | 0.360541E+11 |
Minimum of Months | 0.275255E+10 | 0.212186E+09 | 0.205789E+10 | 0.681385E+10 | 0.577660E+09 |
Maximum of Months | 0.110681E+11 | 0.883980E+10 | 0.285856E+10 | 0.166961E+11 | 0.614340E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302714E+10 | 0.188142E+10 | 0.114573E+10 | 0.436983E+10 | 0.360491E+10 |
February | 0.221496E+10 | 0.107080E+10 | 0.114416E+10 | 0.256967E+10 | 0.311418E+10 |
March | 0.324812E+10 | 0.154843E+10 | 0.169969E+10 | 0.432822E+10 | 0.314206E+10 |
April | 0.482671E+10 | 0.275330E+10 | 0.207341E+10 | 0.803019E+10 | 0.191061E+10 |
May | 0.500040E+10 | 0.280373E+10 | 0.219667E+10 | 0.888551E+10 | 0.143060E+10 |
June | 0.514444E+10 | 0.302576E+10 | 0.211868E+10 | 0.103647E+11 | 0.619068E+09 |
July | 0.386905E+10 | 0.180606E+10 | 0.206299E+10 | 0.802792E+10 | 0.480348E+09 |
August | 0.368949E+10 | 0.185294E+10 | 0.183655E+10 | 0.762293E+10 | 0.588362E+09 |
September | 0.311225E+10 | 0.130764E+10 | 0.180461E+10 | 0.612600E+10 | 0.795025E+09 |
October | 0.329063E+10 | 0.188158E+10 | 0.140906E+10 | 0.527942E+10 | 0.233903E+10 |
November | 0.293299E+10 | 0.177085E+10 | 0.116214E+10 | 0.409943E+10 | 0.322396E+10 |
December | 0.244266E+10 | 0.139078E+10 | 0.105189E+10 | 0.316643E+10 | 0.427136E+10 |
Annual Sum or Average | 0.427989E+11 | 0.230933E+11 | 0.197056E+11 | 0.728702E+11 | 0.255195E+11 |
Minimum of Months | 0.221496E+10 | 0.107080E+10 | 0.105189E+10 | 0.256967E+10 | 0.480348E+09 |
Maximum of Months | 0.514444E+10 | 0.302576E+10 | 0.219667E+10 | 0.103647E+11 | 0.427136E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 341.67 | 2226.01 | 501.86 | 0.00 | 501.86 | 0.00 | 0.00 |
February | 233.72 | 2245.11 | 571.86 | 0.00 | 571.86 | 0.00 | 0.00 |
March | 660.10 | 1931.30 | 760.00 | 0.00 | 760.00 | 0.00 | 0.00 |
April | 1482.21 | 1014.00 | 925.95 | 9.61 | 916.34 | 0.00 | 0.00 |
May | 2067.04 | 666.70 | 1083.92 | 86.79 | 997.13 | 0.00 | 0.00 |
June | 3214.02 | 264.84 | 1259.59 | 228.85 | 1030.73 | 0.00 | 0.00 |
July | 2732.76 | 206.33 | 1074.19 | 111.91 | 962.28 | 0.00 | 0.00 |
August | 2232.97 | 280.84 | 867.06 | 21.54 | 845.52 | 0.00 | 0.00 |
September | 1887.91 | 411.81 | 818.06 | 0.22 | 817.84 | 0.00 | 0.00 |
October | 887.03 | 1372.80 | 632.92 | 0.00 | 632.92 | 0.00 | 0.00 |
November | 351.39 | 2077.28 | 527.34 | 0.00 | 527.34 | 0.00 | 0.00 |
December | 171.56 | 2783.15 | 468.79 | 0.00 | 468.79 | 0.00 | 0.00 |
Annual Sum or Average | 1360.27 | 1285.98 | 791.76 | 38.32 | 753.43 | 0.00 | 0.00 |
Minimum of Months | 171.56 | 206.33 | 468.79 | 0.00 | 468.79 | 0.00 | 0.00 |
Maximum of Months | 3214.02 | 2783.15 | 1259.59 | 228.85 | 1030.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1354.93 | 1358.73 | 1080.84 | 678.04 | 402.80 | 0.00 | 0.00 |
February | 1187.60 | 1375.31 | 1065.38 | 609.44 | 455.93 | 0.00 | 0.00 |
March | 1719.90 | 1171.63 | 1333.27 | 685.84 | 647.43 | 0.00 | 0.00 |
April | 3130.69 | 619.04 | 1903.17 | 1134.31 | 768.86 | 0.00 | 0.00 |
May | 3464.50 | 445.69 | 1972.37 | 1169.20 | 803.17 | 0.00 | 0.00 |
June | 4147.94 | 168.58 | 2055.85 | 1277.47 | 778.37 | 0.00 | 0.00 |
July | 3540.99 | 126.74 | 1736.29 | 979.02 | 757.27 | 0.00 | 0.00 |
August | 3332.65 | 163.74 | 1647.89 | 940.45 | 707.44 | 0.00 | 0.00 |
September | 2632.49 | 257.06 | 1352.21 | 651.79 | 700.42 | 0.00 | 0.00 |
October | 2114.02 | 837.38 | 1358.21 | 826.60 | 531.61 | 0.00 | 0.00 |
November | 1305.13 | 1261.18 | 1044.39 | 626.96 | 417.43 | 0.00 | 0.00 |
December | 1032.95 | 1655.53 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Annual Sum or Average | 2419.45 | 784.19 | 1460.31 | 847.28 | 613.02 | 0.00 | 0.00 |
Minimum of Months | 1032.95 | 126.74 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Maximum of Months | 4147.94 | 1655.53 | 2055.85 | 1277.47 | 803.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6243.11 | 2109.96 | 4132.38 | 3300.42 | 831.96 | 0.00 | 0.00 |
February | 3536.29 | 2070.41 | 2612.85 | 1762.19 | 850.65 | 0.00 | 0.00 |
March | 3159.67 | 1872.94 | 2174.08 | 1119.77 | 1054.32 | 0.00 | 0.00 |
April | 3448.76 | 1064.64 | 1850.71 | 747.87 | 1102.84 | 0.00 | 0.00 |
May | 2546.23 | 733.85 | 1240.17 | 204.89 | 1035.28 | 0.00 | 0.00 |
June | 2885.36 | 278.89 | 1061.94 | 81.86 | 980.08 | 0.00 | 0.00 |
July | 2815.42 | 211.67 | 1085.12 | 112.26 | 972.86 | 0.00 | 0.00 |
August | 3248.11 | 287.11 | 1319.45 | 364.63 | 954.82 | 0.00 | 0.00 |
September | 3970.93 | 427.07 | 1901.21 | 811.10 | 1090.11 | 0.00 | 0.00 |
October | 5035.72 | 1329.31 | 3029.38 | 2096.78 | 932.60 | 0.00 | 0.00 |
November | 5257.25 | 1950.30 | 3530.37 | 2704.08 | 826.29 | 0.00 | 0.00 |
December | 5513.42 | 2542.95 | 3841.88 | 3041.37 | 800.52 | 0.00 | 0.00 |
Annual Sum or Average | 3976.16 | 1236.49 | 2315.02 | 1362.01 | 953.02 | 0.00 | 0.00 |
Minimum of Months | 2546.23 | 211.67 | 1061.94 | 81.86 | 800.52 | 0.00 | 0.00 |
Maximum of Months | 6243.11 | 2542.95 | 4132.38 | 3300.42 | 1102.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1577.65 | 1600.00 | 1130.21 | 702.44 | 427.77 | 0.00 | 0.00 |
February | 1010.08 | 1630.92 | 915.58 | 442.63 | 472.95 | 0.00 | 0.00 |
March | 1552.97 | 1425.86 | 1212.72 | 578.12 | 634.59 | 0.00 | 0.00 |
April | 3062.66 | 865.00 | 1862.16 | 1062.23 | 799.93 | 0.00 | 0.00 |
May | 3324.36 | 574.31 | 1866.94 | 1046.80 | 820.15 | 0.00 | 0.00 |
June | 3992.02 | 262.43 | 1984.75 | 1167.35 | 817.40 | 0.00 | 0.00 |
July | 2962.25 | 213.77 | 1444.54 | 674.31 | 770.24 | 0.00 | 0.00 |
August | 2777.17 | 307.08 | 1377.50 | 691.81 | 685.69 | 0.00 | 0.00 |
September | 2358.89 | 341.29 | 1200.72 | 504.49 | 696.23 | 0.00 | 0.00 |
October | 1937.14 | 1032.47 | 1228.59 | 702.50 | 526.08 | 0.00 | 0.00 |
November | 1522.39 | 1554.45 | 1131.56 | 683.20 | 448.36 | 0.00 | 0.00 |
December | 1091.02 | 2061.44 | 911.99 | 519.26 | 392.73 | 0.00 | 0.00 |
Annual Sum or Average | 2269.21 | 986.37 | 1357.15 | 732.29 | 624.86 | 0.00 | 0.00 |
Minimum of Months | 1010.08 | 213.77 | 911.99 | 442.63 | 392.73 | 0.00 | 0.00 |
Maximum of Months | 3992.02 | 2061.44 | 1984.75 | 1167.35 | 820.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 415.52 | 1985.78 | 501.86 | 0.00 | 501.86 | 0.00 | 0.00 |
February | 283.82 | 1988.13 | 571.86 | 0.00 | 571.86 | 0.00 | 0.00 |
March | 717.77 | 1751.88 | 760.00 | 0.00 | 760.00 | 0.00 | 0.00 |
April | 1536.51 | 956.17 | 925.95 | 9.61 | 916.34 | 0.00 | 0.00 |
May | 2097.08 | 647.17 | 1083.92 | 86.79 | 997.13 | 0.00 | 0.00 |
June | 3247.02 | 268.05 | 1259.58 | 228.85 | 1030.73 | 0.00 | 0.00 |
July | 2771.39 | 204.13 | 1074.18 | 111.91 | 962.28 | 0.00 | 0.00 |
August | 2296.77 | 255.36 | 867.06 | 21.54 | 845.52 | 0.00 | 0.00 |
September | 1912.60 | 398.78 | 818.06 | 0.22 | 817.84 | 0.00 | 0.00 |
October | 934.98 | 1258.47 | 632.91 | 0.00 | 632.91 | 0.00 | 0.00 |
November | 413.56 | 1838.05 | 527.33 | 0.00 | 527.33 | 0.00 | 0.00 |
December | 253.62 | 2419.55 | 468.78 | 0.00 | 468.78 | 0.00 | 0.00 |
Annual Sum or Average | 1411.89 | 1160.80 | 791.75 | 38.32 | 753.43 | 0.00 | 0.00 |
Minimum of Months | 253.62 | 204.13 | 468.78 | 0.00 | 468.78 | 0.00 | 0.00 |
Maximum of Months | 3247.02 | 2419.55 | 1259.58 | 228.85 | 1030.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1366.89 | 1269.59 | 1080.83 | 678.04 | 402.80 | 0.00 | 0.00 |
February | 1188.50 | 1287.61 | 1065.37 | 609.44 | 455.93 | 0.00 | 0.00 |
March | 1710.47 | 1124.05 | 1333.26 | 685.84 | 647.42 | 0.00 | 0.00 |
April | 3101.28 | 628.82 | 1903.16 | 1134.31 | 768.85 | 0.00 | 0.00 |
May | 3436.09 | 446.65 | 1972.36 | 1169.20 | 803.16 | 0.00 | 0.00 |
June | 4117.48 | 180.24 | 2055.84 | 1277.47 | 778.37 | 0.00 | 0.00 |
July | 3512.08 | 138.15 | 1736.29 | 979.02 | 757.26 | 0.00 | 0.00 |
August | 3310.37 | 174.17 | 1647.89 | 940.45 | 707.44 | 0.00 | 0.00 |
September | 2609.49 | 261.44 | 1352.20 | 651.79 | 700.42 | 0.00 | 0.00 |
October | 2100.52 | 808.34 | 1358.21 | 826.60 | 531.61 | 0.00 | 0.00 |
November | 1309.52 | 1184.06 | 1044.39 | 626.96 | 417.43 | 0.00 | 0.00 |
December | 1057.37 | 1540.81 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Annual Sum or Average | 2407.45 | 751.36 | 1460.30 | 847.28 | 613.02 | 0.00 | 0.00 |
Minimum of Months | 1057.37 | 138.15 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Maximum of Months | 4117.48 | 1540.81 | 2055.84 | 1277.47 | 803.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6194.45 | 2076.07 | 4132.36 | 3300.40 | 831.96 | 0.00 | 0.00 |
February | 3511.47 | 1998.67 | 2612.84 | 1762.19 | 850.65 | 0.00 | 0.00 |
March | 3148.70 | 1804.32 | 2174.07 | 1119.76 | 1054.31 | 0.00 | 0.00 |
April | 3453.95 | 1034.11 | 1850.70 | 747.87 | 1102.84 | 0.00 | 0.00 |
May | 2565.33 | 715.08 | 1240.16 | 204.89 | 1035.28 | 0.00 | 0.00 |
June | 2927.23 | 275.44 | 1061.94 | 81.86 | 980.08 | 0.00 | 0.00 |
July | 2853.32 | 206.11 | 1085.12 | 112.26 | 972.85 | 0.00 | 0.00 |
August | 3289.82 | 264.81 | 1319.45 | 364.63 | 954.82 | 0.00 | 0.00 |
September | 3960.44 | 421.34 | 1901.20 | 811.10 | 1090.10 | 0.00 | 0.00 |
October | 5000.47 | 1298.77 | 3029.37 | 2096.77 | 932.59 | 0.00 | 0.00 |
November | 5223.23 | 1890.89 | 3530.36 | 2704.07 | 826.29 | 0.00 | 0.00 |
December | 5494.37 | 2460.28 | 3841.87 | 3041.36 | 800.51 | 0.00 | 0.00 |
Annual Sum or Average | 3973.17 | 1200.56 | 2315.01 | 1362.00 | 953.01 | 0.00 | 0.00 |
Minimum of Months | 2565.33 | 206.11 | 1061.94 | 81.86 | 800.51 | 0.00 | 0.00 |
Maximum of Months | 6194.45 | 2460.28 | 4132.36 | 3300.40 | 1102.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1611.86 | 1438.49 | 1130.21 | 702.44 | 427.76 | 0.00 | 0.00 |
February | 1045.17 | 1396.51 | 915.58 | 442.63 | 472.95 | 0.00 | 0.00 |
March | 1604.72 | 1234.11 | 1212.71 | 578.12 | 634.59 | 0.00 | 0.00 |
April | 3113.02 | 750.06 | 1862.16 | 1062.23 | 799.93 | 0.00 | 0.00 |
May | 3336.23 | 536.97 | 1866.94 | 1046.79 | 820.14 | 0.00 | 0.00 |
June | 4026.36 | 234.54 | 1984.74 | 1167.35 | 817.39 | 0.00 | 0.00 |
July | 3024.52 | 174.04 | 1444.54 | 674.31 | 770.23 | 0.00 | 0.00 |
August | 2867.92 | 216.14 | 1377.50 | 691.81 | 685.69 | 0.00 | 0.00 |
September | 2381.47 | 303.30 | 1200.71 | 504.49 | 696.22 | 0.00 | 0.00 |
October | 1971.60 | 911.68 | 1228.58 | 702.50 | 526.08 | 0.00 | 0.00 |
November | 1567.26 | 1327.38 | 1131.55 | 683.20 | 448.35 | 0.00 | 0.00 |
December | 1156.35 | 1717.07 | 911.99 | 519.26 | 392.73 | 0.00 | 0.00 |
Annual Sum or Average | 2314.18 | 851.08 | 1357.14 | 732.28 | 624.86 | 0.00 | 0.00 |
Minimum of Months | 1045.17 | 174.04 | 911.99 | 442.63 | 392.73 | 0.00 | 0.00 |
Maximum of Months | 4026.36 | 1717.07 | 1984.74 | 1167.35 | 820.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 463.82 | 1823.91 | 501.86 | 0.00 | 501.86 | 0.00 | 0.00 |
February | 324.13 | 1793.26 | 571.86 | 0.00 | 571.86 | 0.00 | 0.00 |
March | 751.22 | 1644.77 | 760.00 | 0.00 | 760.00 | 0.00 | 0.00 |
April | 1524.07 | 938.06 | 925.95 | 9.61 | 916.34 | 0.00 | 0.00 |
May | 2077.51 | 648.06 | 1083.92 | 86.79 | 997.13 | 0.00 | 0.00 |
June | 3208.59 | 277.09 | 1259.58 | 228.85 | 1030.73 | 0.00 | 0.00 |
July | 2727.34 | 214.72 | 1074.18 | 111.91 | 962.28 | 0.00 | 0.00 |
August | 2263.63 | 263.11 | 867.06 | 21.54 | 845.52 | 0.00 | 0.00 |
September | 1887.19 | 404.46 | 818.06 | 0.22 | 817.84 | 0.00 | 0.00 |
October | 947.05 | 1190.70 | 632.91 | 0.00 | 632.91 | 0.00 | 0.00 |
November | 453.98 | 1686.60 | 527.33 | 0.00 | 527.33 | 0.00 | 0.00 |
December | 307.19 | 2203.62 | 468.78 | 0.00 | 468.78 | 0.00 | 0.00 |
Annual Sum or Average | 1416.33 | 1087.82 | 791.75 | 38.32 | 753.43 | 0.00 | 0.00 |
Minimum of Months | 307.19 | 214.72 | 468.78 | 0.00 | 468.78 | 0.00 | 0.00 |
Maximum of Months | 3208.59 | 2203.62 | 1259.58 | 228.85 | 1030.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1407.71 | 1180.79 | 1080.83 | 678.04 | 402.80 | 0.00 | 0.00 |
February | 1221.22 | 1176.37 | 1065.37 | 609.44 | 455.93 | 0.00 | 0.00 |
March | 1736.21 | 1067.82 | 1333.26 | 685.84 | 647.42 | 0.00 | 0.00 |
April | 3095.19 | 621.86 | 1903.16 | 1134.31 | 768.85 | 0.00 | 0.00 |
May | 3424.33 | 446.65 | 1972.36 | 1169.20 | 803.16 | 0.00 | 0.00 |
June | 4095.04 | 185.37 | 2055.84 | 1277.47 | 778.37 | 0.00 | 0.00 |
July | 3487.74 | 144.44 | 1736.29 | 979.02 | 757.26 | 0.00 | 0.00 |
August | 3292.69 | 178.26 | 1647.89 | 940.45 | 707.44 | 0.00 | 0.00 |
September | 2596.92 | 265.09 | 1352.20 | 651.79 | 700.42 | 0.00 | 0.00 |
October | 2110.23 | 774.27 | 1358.21 | 826.60 | 531.61 | 0.00 | 0.00 |
November | 1344.03 | 1098.93 | 1044.39 | 626.96 | 417.43 | 0.00 | 0.00 |
December | 1114.02 | 1410.22 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Annual Sum or Average | 2416.14 | 710.55 | 1460.30 | 847.28 | 613.02 | 0.00 | 0.00 |
Minimum of Months | 1114.02 | 144.44 | 952.21 | 574.97 | 377.24 | 0.00 | 0.00 |
Maximum of Months | 4095.04 | 1410.22 | 2055.84 | 1277.47 | 803.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6233.62 | 1953.60 | 4132.36 | 3300.40 | 831.96 | 0.00 | 0.00 |
February | 3549.05 | 1838.98 | 2612.84 | 1762.19 | 850.65 | 0.00 | 0.00 |
March | 3170.07 | 1713.94 | 2174.07 | 1119.76 | 1054.31 | 0.00 | 0.00 |
April | 3435.61 | 1016.56 | 1850.70 | 747.87 | 1102.84 | 0.00 | 0.00 |
May | 2544.00 | 712.02 | 1240.16 | 204.89 | 1035.28 | 0.00 | 0.00 |
June | 2888.67 | 283.02 | 1061.94 | 81.86 | 980.08 | 0.00 | 0.00 |
July | 2809.15 | 215.67 | 1085.12 | 112.26 | 972.85 | 0.00 | 0.00 |
August | 3254.98 | 271.36 | 1319.45 | 364.63 | 954.82 | 0.00 | 0.00 |
September | 3931.61 | 427.65 | 1901.20 | 811.10 | 1090.10 | 0.00 | 0.00 |
October | 5001.91 | 1247.64 | 3029.37 | 2096.77 | 932.59 | 0.00 | 0.00 |
November | 5256.37 | 1777.95 | 3530.36 | 2704.07 | 826.29 | 0.00 | 0.00 |
December | 5548.75 | 2293.68 | 3841.87 | 3041.36 | 800.51 | 0.00 | 0.00 |
Annual Sum or Average | 3973.09 | 1143.27 | 2315.01 | 1362.00 | 953.01 | 0.00 | 0.00 |
Minimum of Months | 2544.00 | 215.67 | 1061.94 | 81.86 | 800.51 | 0.00 | 0.00 |
Maximum of Months | 6233.62 | 2293.68 | 4132.36 | 3300.40 | 1102.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1631.51 | 1345.92 | 1130.21 | 702.44 | 427.76 | 0.00 | 0.00 |
February | 1062.20 | 1287.28 | 915.58 | 442.63 | 472.95 | 0.00 | 0.00 |
March | 1615.97 | 1173.11 | 1212.71 | 578.12 | 634.59 | 0.00 | 0.00 |
April | 3098.07 | 737.12 | 1862.16 | 1062.23 | 799.93 | 0.00 | 0.00 |
May | 3317.47 | 534.12 | 1866.94 | 1046.79 | 820.14 | 0.00 | 0.00 |
June | 3998.71 | 238.84 | 1984.74 | 1167.35 | 817.39 | 0.00 | 0.00 |
July | 2997.28 | 179.34 | 1444.54 | 674.31 | 770.23 | 0.00 | 0.00 |
August | 2846.08 | 219.67 | 1377.50 | 691.81 | 685.69 | 0.00 | 0.00 |
September | 2363.43 | 306.72 | 1200.71 | 504.49 | 696.22 | 0.00 | 0.00 |
October | 1971.11 | 873.29 | 1228.58 | 702.50 | 526.08 | 0.00 | 0.00 |
November | 1581.57 | 1243.81 | 1131.55 | 683.20 | 448.35 | 0.00 | 0.00 |
December | 1182.21 | 1594.74 | 911.99 | 519.26 | 392.73 | 0.00 | 0.00 |
Annual Sum or Average | 2310.70 | 809.22 | 1357.14 | 732.28 | 624.86 | 0.00 | 0.00 |
Minimum of Months | 1062.20 | 179.34 | 911.99 | 442.63 | 392.73 | 0.00 | 0.00 |
Maximum of Months | 3998.71 | 1594.74 | 1984.74 | 1167.35 | 820.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.915130E+09 | 0.596216E+10 | 0.134419E+10 | 0.00 | 0.134419E+10 | 0.00 | 0.00 |
February | 0.565426E+09 | 0.543136E+10 | 0.138344E+10 | 0.00 | 0.138344E+10 | 0.00 | 0.00 |
March | 0.176802E+10 | 0.517279E+10 | 0.203559E+10 | 0.00 | 0.203559E+10 | 0.00 | 0.00 |
April | 0.384188E+10 | 0.262829E+10 | 0.240006E+10 | 24906474.26 | 0.237516E+10 | 0.00 | 0.00 |
May | 0.553635E+10 | 0.178569E+10 | 0.290318E+10 | 0.232460E+09 | 0.267072E+10 | 0.00 | 0.00 |
June | 0.833075E+10 | 0.686476E+09 | 0.326485E+10 | 0.593189E+09 | 0.267166E+10 | 0.00 | 0.00 |
July | 0.731941E+10 | 0.552627E+09 | 0.287711E+10 | 0.299737E+09 | 0.257737E+10 | 0.00 | 0.00 |
August | 0.598078E+10 | 0.752198E+09 | 0.232234E+10 | 57692429.13 | 0.226465E+10 | 0.00 | 0.00 |
September | 0.489346E+10 | 0.106742E+10 | 0.212042E+10 | 566048.11 | 0.211985E+10 | 0.00 | 0.00 |
October | 0.237583E+10 | 0.367692E+10 | 0.169520E+10 | 0.00 | 0.169520E+10 | 0.00 | 0.00 |
November | 0.910793E+09 | 0.538431E+10 | 0.136685E+10 | 0.00 | 0.136685E+10 | 0.00 | 0.00 |
December | 0.459517E+09 | 0.745438E+10 | 0.125560E+10 | 0.00 | 0.125560E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.428973E+11 | 0.405546E+11 | 0.249688E+11 | 0.120855E+10 | 0.237603E+11 | 0.00 | 0.00 |
Minimum of Months | 0.459517E+09 | 0.552627E+09 | 0.125560E+10 | 0.00 | 0.125560E+10 | 0.00 | 0.00 |
Maximum of Months | 0.833075E+10 | 0.745438E+10 | 0.326485E+10 | 0.593189E+09 | 0.267166E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.362904E+10 | 0.363922E+10 | 0.289492E+10 | 0.181606E+10 | 0.107885E+10 | 0.00 | 0.00 |
February | 0.287305E+10 | 0.332715E+10 | 0.257736E+10 | 0.147437E+10 | 0.110299E+10 | 0.00 | 0.00 |
March | 0.460658E+10 | 0.313811E+10 | 0.357103E+10 | 0.183696E+10 | 0.173406E+10 | 0.00 | 0.00 |
April | 0.811475E+10 | 0.160454E+10 | 0.493301E+10 | 0.294014E+10 | 0.199287E+10 | 0.00 | 0.00 |
May | 0.927931E+10 | 0.119374E+10 | 0.528279E+10 | 0.313159E+10 | 0.215120E+10 | 0.00 | 0.00 |
June | 0.107515E+11 | 0.436953E+09 | 0.532875E+10 | 0.331121E+10 | 0.201754E+10 | 0.00 | 0.00 |
July | 0.948420E+10 | 0.339471E+09 | 0.465049E+10 | 0.262222E+10 | 0.202827E+10 | 0.00 | 0.00 |
August | 0.892616E+10 | 0.438569E+09 | 0.441372E+10 | 0.251890E+10 | 0.189481E+10 | 0.00 | 0.00 |
September | 0.682342E+10 | 0.666309E+09 | 0.350492E+10 | 0.168944E+10 | 0.181549E+10 | 0.00 | 0.00 |
October | 0.566220E+10 | 0.224285E+10 | 0.363784E+10 | 0.221396E+10 | 0.142388E+10 | 0.00 | 0.00 |
November | 0.338289E+10 | 0.326897E+10 | 0.270706E+10 | 0.162508E+10 | 0.108198E+10 | 0.00 | 0.00 |
December | 0.276666E+10 | 0.443418E+10 | 0.255040E+10 | 0.154001E+10 | 0.101039E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.762997E+11 | 0.247301E+11 | 0.460523E+11 | 0.267199E+11 | 0.193323E+11 | 0.00 | 0.00 |
Minimum of Months | 0.276666E+10 | 0.339471E+09 | 0.255040E+10 | 0.147437E+10 | 0.101039E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107515E+11 | 0.443418E+10 | 0.532875E+10 | 0.331121E+10 | 0.215120E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167215E+11 | 0.565131E+10 | 0.110682E+11 | 0.883983E+10 | 0.222833E+10 | 0.00 | 0.00 |
February | 0.855500E+10 | 0.500872E+10 | 0.632100E+10 | 0.426310E+10 | 0.205790E+10 | 0.00 | 0.00 |
March | 0.846285E+10 | 0.501649E+10 | 0.582306E+10 | 0.299918E+10 | 0.282388E+10 | 0.00 | 0.00 |
April | 0.893918E+10 | 0.275954E+10 | 0.479704E+10 | 0.193847E+10 | 0.285857E+10 | 0.00 | 0.00 |
May | 0.681981E+10 | 0.196555E+10 | 0.332167E+10 | 0.548778E+09 | 0.277289E+10 | 0.00 | 0.00 |
June | 0.747886E+10 | 0.722883E+09 | 0.275256E+10 | 0.212187E+09 | 0.254037E+10 | 0.00 | 0.00 |
July | 0.754081E+10 | 0.566925E+09 | 0.290639E+10 | 0.300690E+09 | 0.260570E+10 | 0.00 | 0.00 |
August | 0.869974E+10 | 0.768990E+09 | 0.353403E+10 | 0.976632E+09 | 0.255740E+10 | 0.00 | 0.00 |
September | 0.102926E+11 | 0.110697E+10 | 0.492794E+10 | 0.210238E+10 | 0.282556E+10 | 0.00 | 0.00 |
October | 0.134877E+11 | 0.356043E+10 | 0.811389E+10 | 0.561602E+10 | 0.249787E+10 | 0.00 | 0.00 |
November | 0.136268E+11 | 0.505518E+10 | 0.915072E+10 | 0.700898E+10 | 0.214174E+10 | 0.00 | 0.00 |
December | 0.147671E+11 | 0.681103E+10 | 0.102901E+11 | 0.814600E+10 | 0.214410E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.125392E+12 | 0.389940E+11 | 0.730065E+11 | 0.429523E+11 | 0.300543E+11 | 0.00 | 0.00 |
Minimum of Months | 0.681981E+10 | 0.566925E+09 | 0.275256E+10 | 0.212187E+09 | 0.205790E+10 | 0.00 | 0.00 |
Maximum of Months | 0.167215E+11 | 0.681103E+10 | 0.110682E+11 | 0.883983E+10 | 0.285857E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.422558E+10 | 0.428543E+10 | 0.302716E+10 | 0.188143E+10 | 0.114573E+10 | 0.00 | 0.00 |
February | 0.244358E+10 | 0.394552E+10 | 0.221497E+10 | 0.107080E+10 | 0.114417E+10 | 0.00 | 0.00 |
March | 0.415948E+10 | 0.381904E+10 | 0.324814E+10 | 0.154844E+10 | 0.169970E+10 | 0.00 | 0.00 |
April | 0.793842E+10 | 0.224209E+10 | 0.482673E+10 | 0.275331E+10 | 0.207341E+10 | 0.00 | 0.00 |
May | 0.890397E+10 | 0.153823E+10 | 0.500042E+10 | 0.280374E+10 | 0.219668E+10 | 0.00 | 0.00 |
June | 0.103473E+11 | 0.680217E+09 | 0.514446E+10 | 0.302577E+10 | 0.211869E+10 | 0.00 | 0.00 |
July | 0.793409E+10 | 0.572558E+09 | 0.386907E+10 | 0.180607E+10 | 0.206300E+10 | 0.00 | 0.00 |
August | 0.743837E+10 | 0.822477E+09 | 0.368950E+10 | 0.185294E+10 | 0.183656E+10 | 0.00 | 0.00 |
September | 0.611424E+10 | 0.884636E+09 | 0.311227E+10 | 0.130765E+10 | 0.180462E+10 | 0.00 | 0.00 |
October | 0.518844E+10 | 0.276536E+10 | 0.329065E+10 | 0.188158E+10 | 0.140906E+10 | 0.00 | 0.00 |
November | 0.394603E+10 | 0.402912E+10 | 0.293300E+10 | 0.177086E+10 | 0.116214E+10 | 0.00 | 0.00 |
December | 0.292219E+10 | 0.552137E+10 | 0.244267E+10 | 0.139078E+10 | 0.105189E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.715617E+11 | 0.311061E+11 | 0.427990E+11 | 0.230934E+11 | 0.197056E+11 | 0.00 | 0.00 |
Minimum of Months | 0.244358E+10 | 0.572558E+09 | 0.221497E+10 | 0.107080E+10 | 0.105189E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103473E+11 | 0.552137E+10 | 0.514446E+10 | 0.302577E+10 | 0.219668E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111294E+10 | 0.531871E+10 | 0.134418E+10 | 0.00 | 0.134418E+10 | 0.00 | 0.00 |
February | 0.686615E+09 | 0.480968E+10 | 0.138344E+10 | 0.00 | 0.138344E+10 | 0.00 | 0.00 |
March | 0.192248E+10 | 0.469223E+10 | 0.203558E+10 | 0.00 | 0.203558E+10 | 0.00 | 0.00 |
April | 0.398264E+10 | 0.247840E+10 | 0.240005E+10 | 24906385.81 | 0.237515E+10 | 0.00 | 0.00 |
May | 0.561683E+10 | 0.173339E+10 | 0.290317E+10 | 0.232459E+09 | 0.267071E+10 | 0.00 | 0.00 |
June | 0.841627E+10 | 0.694797E+09 | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.00 | 0.00 |
July | 0.742289E+10 | 0.546735E+09 | 0.287710E+10 | 0.299736E+09 | 0.257736E+10 | 0.00 | 0.00 |
August | 0.615167E+10 | 0.683961E+09 | 0.232234E+10 | 57692224.27 | 0.226464E+10 | 0.00 | 0.00 |
September | 0.495745E+10 | 0.103363E+10 | 0.212041E+10 | 566046.10 | 0.211984E+10 | 0.00 | 0.00 |
October | 0.250426E+10 | 0.337069E+10 | 0.169519E+10 | 0.00 | 0.169519E+10 | 0.00 | 0.00 |
November | 0.107195E+10 | 0.476422E+10 | 0.136685E+10 | 0.00 | 0.136685E+10 | 0.00 | 0.00 |
December | 0.679298E+09 | 0.648052E+10 | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.445253E+11 | 0.366069E+11 | 0.249687E+11 | 0.120855E+10 | 0.237602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.679298E+09 | 0.546735E+09 | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.00 | 0.00 |
Maximum of Months | 0.841627E+10 | 0.648052E+10 | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.366107E+10 | 0.340047E+10 | 0.289490E+10 | 0.181605E+10 | 0.107885E+10 | 0.00 | 0.00 |
February | 0.287521E+10 | 0.311500E+10 | 0.257735E+10 | 0.147436E+10 | 0.110299E+10 | 0.00 | 0.00 |
March | 0.458133E+10 | 0.301066E+10 | 0.357101E+10 | 0.183696E+10 | 0.173406E+10 | 0.00 | 0.00 |
April | 0.803852E+10 | 0.162991E+10 | 0.493299E+10 | 0.294013E+10 | 0.199286E+10 | 0.00 | 0.00 |
May | 0.920321E+10 | 0.119632E+10 | 0.528277E+10 | 0.313158E+10 | 0.215119E+10 | 0.00 | 0.00 |
June | 0.106725E+11 | 0.467182E+09 | 0.532873E+10 | 0.331120E+10 | 0.201753E+10 | 0.00 | 0.00 |
July | 0.940675E+10 | 0.370029E+09 | 0.465047E+10 | 0.262221E+10 | 0.202826E+10 | 0.00 | 0.00 |
August | 0.886650E+10 | 0.466506E+09 | 0.441370E+10 | 0.251889E+10 | 0.189480E+10 | 0.00 | 0.00 |
September | 0.676381E+10 | 0.677642E+09 | 0.350491E+10 | 0.168943E+10 | 0.181548E+10 | 0.00 | 0.00 |
October | 0.562604E+10 | 0.216505E+10 | 0.363782E+10 | 0.221395E+10 | 0.142387E+10 | 0.00 | 0.00 |
November | 0.339427E+10 | 0.306907E+10 | 0.270705E+10 | 0.162508E+10 | 0.108197E+10 | 0.00 | 0.00 |
December | 0.283206E+10 | 0.412692E+10 | 0.255039E+10 | 0.154000E+10 | 0.101039E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.759213E+11 | 0.236947E+11 | 0.460521E+11 | 0.267198E+11 | 0.193323E+11 | 0.00 | 0.00 |
Minimum of Months | 0.283206E+10 | 0.370029E+09 | 0.255039E+10 | 0.147436E+10 | 0.101039E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106725E+11 | 0.412692E+10 | 0.532873E+10 | 0.331120E+10 | 0.215119E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165912E+11 | 0.556055E+10 | 0.110681E+11 | 0.883980E+10 | 0.222832E+10 | 0.00 | 0.00 |
February | 0.849495E+10 | 0.483518E+10 | 0.632097E+10 | 0.426308E+10 | 0.205789E+10 | 0.00 | 0.00 |
March | 0.843348E+10 | 0.483269E+10 | 0.582304E+10 | 0.299917E+10 | 0.282387E+10 | 0.00 | 0.00 |
April | 0.895263E+10 | 0.268041E+10 | 0.479703E+10 | 0.193847E+10 | 0.285856E+10 | 0.00 | 0.00 |
May | 0.687098E+10 | 0.191527E+10 | 0.332166E+10 | 0.548776E+09 | 0.277288E+10 | 0.00 | 0.00 |
June | 0.758738E+10 | 0.713931E+09 | 0.275255E+10 | 0.212186E+09 | 0.254036E+10 | 0.00 | 0.00 |
July | 0.764233E+10 | 0.552057E+09 | 0.290638E+10 | 0.300689E+09 | 0.260569E+10 | 0.00 | 0.00 |
August | 0.881145E+10 | 0.709264E+09 | 0.353402E+10 | 0.976628E+09 | 0.255739E+10 | 0.00 | 0.00 |
September | 0.102655E+11 | 0.109213E+10 | 0.492792E+10 | 0.210237E+10 | 0.282555E+10 | 0.00 | 0.00 |
October | 0.133932E+11 | 0.347863E+10 | 0.811386E+10 | 0.561600E+10 | 0.249786E+10 | 0.00 | 0.00 |
November | 0.135386E+11 | 0.490119E+10 | 0.915068E+10 | 0.700895E+10 | 0.214173E+10 | 0.00 | 0.00 |
December | 0.147161E+11 | 0.658963E+10 | 0.102901E+11 | 0.814597E+10 | 0.214409E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.125298E+12 | 0.378609E+11 | 0.730063E+11 | 0.429521E+11 | 0.300542E+11 | 0.00 | 0.00 |
Minimum of Months | 0.687098E+10 | 0.552057E+09 | 0.275255E+10 | 0.212186E+09 | 0.205789E+10 | 0.00 | 0.00 |
Maximum of Months | 0.165912E+11 | 0.658963E+10 | 0.110681E+11 | 0.883980E+10 | 0.285856E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.431722E+10 | 0.385285E+10 | 0.302714E+10 | 0.188142E+10 | 0.114573E+10 | 0.00 | 0.00 |
February | 0.252848E+10 | 0.337844E+10 | 0.221496E+10 | 0.107080E+10 | 0.114416E+10 | 0.00 | 0.00 |
March | 0.429807E+10 | 0.330544E+10 | 0.324812E+10 | 0.154843E+10 | 0.169969E+10 | 0.00 | 0.00 |
April | 0.806895E+10 | 0.194415E+10 | 0.482671E+10 | 0.275330E+10 | 0.207341E+10 | 0.00 | 0.00 |
May | 0.893577E+10 | 0.143821E+10 | 0.500040E+10 | 0.280373E+10 | 0.219667E+10 | 0.00 | 0.00 |
June | 0.104363E+11 | 0.607929E+09 | 0.514444E+10 | 0.302576E+10 | 0.211868E+10 | 0.00 | 0.00 |
July | 0.810086E+10 | 0.466150E+09 | 0.386905E+10 | 0.180606E+10 | 0.206299E+10 | 0.00 | 0.00 |
August | 0.768143E+10 | 0.578899E+09 | 0.368949E+10 | 0.185294E+10 | 0.183655E+10 | 0.00 | 0.00 |
September | 0.617278E+10 | 0.786147E+09 | 0.311225E+10 | 0.130764E+10 | 0.180461E+10 | 0.00 | 0.00 |
October | 0.528072E+10 | 0.244185E+10 | 0.329063E+10 | 0.188158E+10 | 0.140906E+10 | 0.00 | 0.00 |
November | 0.406233E+10 | 0.344057E+10 | 0.293299E+10 | 0.177085E+10 | 0.116214E+10 | 0.00 | 0.00 |
December | 0.309716E+10 | 0.459899E+10 | 0.244266E+10 | 0.139078E+10 | 0.105189E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.729801E+11 | 0.268396E+11 | 0.427989E+11 | 0.230933E+11 | 0.197056E+11 | 0.00 | 0.00 |
Minimum of Months | 0.252848E+10 | 0.466150E+09 | 0.221496E+10 | 0.107080E+10 | 0.105189E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104363E+11 | 0.459899E+10 | 0.514444E+10 | 0.302576E+10 | 0.219667E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124230E+10 | 0.488517E+10 | 0.134418E+10 | 0.00 | 0.134418E+10 | 0.00 | 0.00 |
February | 0.784128E+09 | 0.433825E+10 | 0.138344E+10 | 0.00 | 0.138344E+10 | 0.00 | 0.00 |
March | 0.201206E+10 | 0.440534E+10 | 0.203558E+10 | 0.00 | 0.203558E+10 | 0.00 | 0.00 |
April | 0.395040E+10 | 0.243145E+10 | 0.240005E+10 | 24906385.81 | 0.237515E+10 | 0.00 | 0.00 |
May | 0.556439E+10 | 0.173577E+10 | 0.290317E+10 | 0.232459E+09 | 0.267071E+10 | 0.00 | 0.00 |
June | 0.831667E+10 | 0.718211E+09 | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.00 | 0.00 |
July | 0.730490E+10 | 0.575111E+09 | 0.287710E+10 | 0.299736E+09 | 0.257736E+10 | 0.00 | 0.00 |
August | 0.606292E+10 | 0.704719E+09 | 0.232234E+10 | 57692224.27 | 0.226464E+10 | 0.00 | 0.00 |
September | 0.489160E+10 | 0.104836E+10 | 0.212041E+10 | 566046.10 | 0.211984E+10 | 0.00 | 0.00 |
October | 0.253658E+10 | 0.318917E+10 | 0.169519E+10 | 0.00 | 0.169519E+10 | 0.00 | 0.00 |
November | 0.117672E+10 | 0.437166E+10 | 0.136685E+10 | 0.00 | 0.136685E+10 | 0.00 | 0.00 |
December | 0.822779E+09 | 0.590217E+10 | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.446654E+11 | 0.343054E+11 | 0.249687E+11 | 0.120855E+10 | 0.237602E+11 | 0.00 | 0.00 |
Minimum of Months | 0.784128E+09 | 0.575111E+09 | 0.125559E+10 | 0.00 | 0.125559E+10 | 0.00 | 0.00 |
Maximum of Months | 0.831667E+10 | 0.590217E+10 | 0.326483E+10 | 0.593187E+09 | 0.267165E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.377041E+10 | 0.316262E+10 | 0.289490E+10 | 0.181605E+10 | 0.107885E+10 | 0.00 | 0.00 |
February | 0.295438E+10 | 0.284588E+10 | 0.257735E+10 | 0.147436E+10 | 0.110299E+10 | 0.00 | 0.00 |
March | 0.465025E+10 | 0.286005E+10 | 0.357101E+10 | 0.183696E+10 | 0.173406E+10 | 0.00 | 0.00 |
April | 0.802274E+10 | 0.161186E+10 | 0.493299E+10 | 0.294013E+10 | 0.199286E+10 | 0.00 | 0.00 |
May | 0.917174E+10 | 0.119632E+10 | 0.528277E+10 | 0.313158E+10 | 0.215119E+10 | 0.00 | 0.00 |
June | 0.106143E+11 | 0.480473E+09 | 0.532873E+10 | 0.331120E+10 | 0.201753E+10 | 0.00 | 0.00 |
July | 0.934157E+10 | 0.386875E+09 | 0.465047E+10 | 0.262221E+10 | 0.202826E+10 | 0.00 | 0.00 |
August | 0.881914E+10 | 0.477440E+09 | 0.441370E+10 | 0.251889E+10 | 0.189480E+10 | 0.00 | 0.00 |
September | 0.673122E+10 | 0.687125E+09 | 0.350491E+10 | 0.168943E+10 | 0.181548E+10 | 0.00 | 0.00 |
October | 0.565203E+10 | 0.207380E+10 | 0.363782E+10 | 0.221395E+10 | 0.142387E+10 | 0.00 | 0.00 |
November | 0.348373E+10 | 0.284843E+10 | 0.270705E+10 | 0.162508E+10 | 0.108197E+10 | 0.00 | 0.00 |
December | 0.298379E+10 | 0.377713E+10 | 0.255039E+10 | 0.154000E+10 | 0.101039E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.761953E+11 | 0.224080E+11 | 0.460521E+11 | 0.267198E+11 | 0.193323E+11 | 0.00 | 0.00 |
Minimum of Months | 0.295438E+10 | 0.386875E+09 | 0.255039E+10 | 0.147436E+10 | 0.101039E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106143E+11 | 0.377713E+10 | 0.532873E+10 | 0.331120E+10 | 0.215119E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166961E+11 | 0.523253E+10 | 0.110681E+11 | 0.883980E+10 | 0.222832E+10 | 0.00 | 0.00 |
February | 0.858586E+10 | 0.444885E+10 | 0.632097E+10 | 0.426308E+10 | 0.205789E+10 | 0.00 | 0.00 |
March | 0.849071E+10 | 0.459061E+10 | 0.582304E+10 | 0.299917E+10 | 0.282387E+10 | 0.00 | 0.00 |
April | 0.890511E+10 | 0.263492E+10 | 0.479703E+10 | 0.193847E+10 | 0.285856E+10 | 0.00 | 0.00 |
May | 0.681385E+10 | 0.190708E+10 | 0.332166E+10 | 0.548776E+09 | 0.277288E+10 | 0.00 | 0.00 |
June | 0.748744E+10 | 0.733581E+09 | 0.275255E+10 | 0.212186E+09 | 0.254036E+10 | 0.00 | 0.00 |
July | 0.752403E+10 | 0.577660E+09 | 0.290638E+10 | 0.300689E+09 | 0.260569E+10 | 0.00 | 0.00 |
August | 0.871813E+10 | 0.726823E+09 | 0.353402E+10 | 0.976628E+09 | 0.255739E+10 | 0.00 | 0.00 |
September | 0.101907E+11 | 0.110848E+10 | 0.492792E+10 | 0.210237E+10 | 0.282555E+10 | 0.00 | 0.00 |
October | 0.133971E+11 | 0.334167E+10 | 0.811386E+10 | 0.561600E+10 | 0.249786E+10 | 0.00 | 0.00 |
November | 0.136245E+11 | 0.460846E+10 | 0.915068E+10 | 0.700895E+10 | 0.214173E+10 | 0.00 | 0.00 |
December | 0.148618E+11 | 0.614340E+10 | 0.102901E+11 | 0.814597E+10 | 0.214409E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.125295E+12 | 0.360541E+11 | 0.730063E+11 | 0.429521E+11 | 0.300542E+11 | 0.00 | 0.00 |
Minimum of Months | 0.681385E+10 | 0.577660E+09 | 0.275255E+10 | 0.212186E+09 | 0.205789E+10 | 0.00 | 0.00 |
Maximum of Months | 0.166961E+11 | 0.614340E+10 | 0.110681E+11 | 0.883980E+10 | 0.285856E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.436983E+10 | 0.360491E+10 | 0.302714E+10 | 0.188142E+10 | 0.114573E+10 | 0.00 | 0.00 |
February | 0.256967E+10 | 0.311418E+10 | 0.221496E+10 | 0.107080E+10 | 0.114416E+10 | 0.00 | 0.00 |
March | 0.432822E+10 | 0.314206E+10 | 0.324812E+10 | 0.154843E+10 | 0.169969E+10 | 0.00 | 0.00 |
April | 0.803019E+10 | 0.191061E+10 | 0.482671E+10 | 0.275330E+10 | 0.207341E+10 | 0.00 | 0.00 |
May | 0.888551E+10 | 0.143060E+10 | 0.500040E+10 | 0.280373E+10 | 0.219667E+10 | 0.00 | 0.00 |
June | 0.103647E+11 | 0.619068E+09 | 0.514444E+10 | 0.302576E+10 | 0.211868E+10 | 0.00 | 0.00 |
July | 0.802792E+10 | 0.480348E+09 | 0.386905E+10 | 0.180606E+10 | 0.206299E+10 | 0.00 | 0.00 |
August | 0.762293E+10 | 0.588362E+09 | 0.368949E+10 | 0.185294E+10 | 0.183655E+10 | 0.00 | 0.00 |
September | 0.612600E+10 | 0.795025E+09 | 0.311225E+10 | 0.130764E+10 | 0.180461E+10 | 0.00 | 0.00 |
October | 0.527942E+10 | 0.233903E+10 | 0.329063E+10 | 0.188158E+10 | 0.140906E+10 | 0.00 | 0.00 |
November | 0.409943E+10 | 0.322396E+10 | 0.293299E+10 | 0.177085E+10 | 0.116214E+10 | 0.00 | 0.00 |
December | 0.316643E+10 | 0.427136E+10 | 0.244266E+10 | 0.139078E+10 | 0.105189E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.728702E+11 | 0.255195E+11 | 0.427989E+11 | 0.230933E+11 | 0.197056E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256967E+10 | 0.480348E+09 | 0.221496E+10 | 0.107080E+10 | 0.105189E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103647E+11 | 0.427136E+10 | 0.514444E+10 | 0.302576E+10 | 0.219667E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.331036E+11 | -0.320831E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102041E+10 | 58.97 | 0.00 | 0.00 |
February | 0.297890E+11 | -0.288642E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -924787838.5 | 58.97 | 0.00 | 0.00 |
March | 0.333167E+11 | -0.322895E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102715E+10 | 58.98 | 0.00 | 0.00 |
April | 0.279355E+11 | -0.269473E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988231299.4 | 58.98 | 0.00 | 0.00 |
May | 0.271240E+11 | -0.261007E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102336E+10 | 58.98 | 0.00 | 0.00 |
June | 0.246442E+11 | -0.236532E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991008761.5 | 58.97 | 0.00 | 0.00 |
July | 0.224788E+11 | -0.214609E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101797E+10 | 58.97 | 0.00 | 0.00 |
August | 0.248816E+11 | -0.238596E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102193E+10 | 58.97 | 0.00 | 0.00 |
September | 0.241961E+11 | -0.232103E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985779608.8 | 58.97 | 0.00 | 0.00 |
October | 0.273846E+11 | -0.263672E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101742E+10 | 58.97 | 0.00 | 0.00 |
November | 0.294002E+11 | -0.284152E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984976351.4 | 58.97 | 0.00 | 0.00 |
December | 0.313335E+11 | -0.303150E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101855E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.335588E+12 | -0.323566E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120216E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.224788E+11 | -0.322895E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102715E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.333167E+11 | -0.214609E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -924787838.5 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9166.72 | 39.08 | 306.50 | 291.50 | 2382.83 | 29.16 | 193.00 | 287.17 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8257.35 | 36.51 | 234.33 | 265.00 | 1310.38 | 23.39 | 146.00 | 223.33 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1590.94 | 19.58 | 47.50 | 328.83 | 927.17 | 20.91 | 180.00 | 286.83 |
April | 380.33 | 0.52 | 0.48 | 01-APR-07:40 | 1238.86 | 19.19 | 19.33 | 333.33 | 777.78 | 20.51 | 129.83 | 302.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:10 | 989.20 | 18.92 | 0.00 | 359.33 | 623.12 | 20.31 | 70.00 | 318.33 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-06:00 | 824.79 | 18.17 | 0.00 | 363.17 | 534.95 | 19.62 | 18.50 | 312.50 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:19 | 950.63 | 18.61 | 0.00 | 363.50 | 574.85 | 20.01 | 78.67 | 296.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 1087.34 | 18.97 | 3.33 | 337.50 | 662.74 | 20.33 | 90.83 | 288.17 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:00 | 1543.34 | 19.93 | 58.00 | 318.83 | 864.62 | 20.88 | 177.33 | 286.33 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3150.25 | 25.23 | 154.67 | 314.67 | 1124.32 | 20.58 | 125.50 | 298.33 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8680.98 | 37.78 | 282.50 | 285.33 | 1589.08 | 24.32 | 149.83 | 263.50 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8492.09 | 39.07 | 289.33 | 280.00 | 2219.15 | 28.88 | 188.17 | 274.33 |
Annual Sum or Average | 4135.50 | 0.51 | 3379.43 | 24.78 | 1395.50 | 3841.00 | 1066.63 | 22.08 | 1547.67 | 3438.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 824.79 | 18.17 | 0.00 | 265.00 | 534.95 | 19.62 | 18.50 | 223.33 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 9166.72 | 39.08 | 306.50 | 363.50 | 2382.83 | 29.16 | 193.00 | 318.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:49 | 2183.39 | 24.58 | 107.50 | 274.67 | 1194.77 | 24.27 | 103.50 | 231.83 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2630.64 | 25.04 | 87.83 | 254.33 | 1459.25 | 24.82 | 100.83 | 190.17 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:19 | 2206.07 | 23.47 | 100.17 | 316.00 | 1158.67 | 23.56 | 130.67 | 282.33 |
April | 380.33 | 0.50 | 0.48 | 01-APR-06:40 | 3083.22 | 23.60 | 112.33 | 348.17 | 1725.66 | 23.89 | 101.00 | 326.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-05:00 | 3501.21 | 24.68 | 134.17 | 380.67 | 1396.04 | 23.54 | 84.83 | 357.33 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:49 | 3514.26 | 24.13 | 134.83 | 386.50 | 1379.14 | 23.02 | 78.00 | 353.33 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 3065.31 | 24.12 | 128.17 | 381.33 | 1243.94 | 23.02 | 90.00 | 325.17 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 2997.07 | 23.91 | 114.50 | 353.33 | 1655.91 | 24.09 | 109.67 | 310.17 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:30 | 2374.39 | 23.56 | 105.00 | 318.67 | 1267.12 | 23.75 | 126.33 | 278.83 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2300.61 | 23.23 | 103.33 | 295.00 | 1232.82 | 23.16 | 114.67 | 256.67 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:30 | 1861.25 | 23.16 | 80.33 | 273.67 | 978.90 | 23.03 | 86.33 | 209.83 |
December | 290.67 | 0.51 | 0.48 | 01-DEC-07:30 | 2172.99 | 25.14 | 106.33 | 260.50 | 1194.23 | 24.72 | 103.00 | 208.67 |
Annual Sum or Average | 4135.50 | 0.50 | 2716.37 | 24.02 | 1314.50 | 3842.83 | 1333.59 | 23.68 | 1228.83 | 3331.17 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 1861.25 | 23.16 | 80.33 | 254.33 | 978.90 | 23.02 | 78.00 | 190.17 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 3514.26 | 25.14 | 134.83 | 386.50 | 1725.66 | 24.82 | 130.67 | 357.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:30 | 478.98 | 15.61 | 0.00 | 229.50 | 329.10 | 17.49 | 0.00 | 145.67 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-09:50 | 585.71 | 16.55 | 0.00 | 227.33 | 376.36 | 18.13 | 0.00 | 135.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:00 | 669.33 | 17.76 | 0.00 | 303.83 | 417.59 | 19.14 | 3.17 | 232.17 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:49 | 793.16 | 18.89 | 0.00 | 336.17 | 519.99 | 20.22 | 46.67 | 304.33 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 931.54 | 19.66 | 25.33 | 388.67 | 609.72 | 20.95 | 93.33 | 373.17 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1074.96 | 22.44 | 108.00 | 400.00 | 633.70 | 22.52 | 139.83 | 391.17 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:00 | 954.44 | 21.81 | 82.67 | 394.17 | 604.04 | 23.01 | 150.83 | 360.50 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-07:10 | 800.66 | 18.98 | 0.33 | 348.50 | 507.62 | 20.30 | 48.00 | 295.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 759.28 | 18.31 | 0.00 | 315.00 | 464.10 | 19.64 | 12.33 | 256.67 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-07:49 | 551.52 | 16.47 | 0.00 | 263.83 | 367.52 | 18.06 | 1.00 | 190.50 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:20 | 518.34 | 16.32 | 0.00 | 238.50 | 343.65 | 18.10 | 0.00 | 138.17 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-08:00 | 481.42 | 15.79 | 0.00 | 216.17 | 322.82 | 17.68 | 0.00 | 117.00 |
Annual Sum or Average | 4135.50 | 0.52 | 741.16 | 18.49 | 216.33 | 3661.67 | 472.35 | 19.83 | 495.17 | 2939.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 478.98 | 15.61 | 0.00 | 216.17 | 322.82 | 17.49 | 0.00 | 117.00 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 1074.96 | 22.44 | 108.00 | 400.00 | 633.70 | 23.01 | 150.83 | 391.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-09:30 | 2347.22 | 23.99 | 107.83 | 248.67 | 1305.43 | 23.75 | 108.67 | 215.67 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-09:50 | 2378.79 | 23.28 | 82.50 | 239.50 | 927.32 | 21.81 | 93.17 | 179.50 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-08:20 | 2017.77 | 22.97 | 95.33 | 315.17 | 1090.39 | 23.26 | 142.33 | 277.50 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 2880.93 | 21.65 | 85.00 | 335.00 | 1595.31 | 22.26 | 85.00 | 309.17 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-07:19 | 3088.07 | 19.73 | 54.50 | 365.33 | 1699.37 | 19.64 | 55.50 | 335.83 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-07:10 | 3142.63 | 16.66 | 0.00 | 372.50 | 1264.94 | 19.26 | 56.17 | 345.00 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:19 | 2353.83 | 17.39 | 3.67 | 371.83 | 1054.96 | 19.59 | 69.50 | 325.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:40 | 2411.80 | 19.54 | 49.17 | 343.33 | 1317.18 | 19.69 | 50.67 | 298.50 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1927.63 | 21.72 | 82.83 | 318.33 | 1034.18 | 22.22 | 116.17 | 282.67 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2335.20 | 23.53 | 112.00 | 288.50 | 1269.65 | 23.57 | 122.67 | 256.83 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-08:30 | 2180.53 | 23.73 | 93.00 | 254.67 | 1175.66 | 23.56 | 96.67 | 210.83 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-08:00 | 1833.59 | 23.24 | 91.83 | 241.33 | 973.90 | 22.92 | 102.33 | 201.83 |
Annual Sum or Average | 4135.50 | 0.51 | 2445.39 | 21.16 | 857.67 | 3694.17 | 1244.96 | 21.63 | 1098.83 | 3239.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1833.59 | 16.66 | 0.00 | 239.50 | 927.32 | 19.26 | 50.67 | 179.50 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3142.63 | 23.99 | 112.00 | 372.50 | 1699.37 | 23.75 | 142.33 | 345.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9256.88 | 38.69 | 306.33 | 291.50 | 2505.87 | 25.50 | 145.33 | 288.17 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8318.88 | 36.07 | 234.00 | 265.00 | 1407.09 | 19.01 | 38.33 | 226.67 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1630.15 | 13.16 | 2.33 | 329.00 | 996.35 | 16.74 | 1.83 | 291.83 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:30 | 1275.21 | 13.41 | 0.00 | 333.83 | 836.27 | 16.97 | 0.00 | 308.50 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:10 | 1014.24 | 13.30 | 0.00 | 360.50 | 667.29 | 16.87 | 0.00 | 325.17 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-06:49 | 846.30 | 12.61 | 0.00 | 363.83 | 572.67 | 16.21 | 0.00 | 322.50 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:10 | 970.53 | 12.87 | 0.00 | 364.83 | 614.13 | 16.41 | 0.00 | 305.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1113.85 | 13.10 | 0.00 | 338.67 | 710.27 | 16.67 | 0.00 | 296.33 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:00 | 1577.54 | 13.87 | 10.83 | 320.00 | 926.40 | 16.82 | 0.00 | 290.50 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3232.10 | 20.63 | 139.83 | 318.17 | 1220.89 | 16.33 | 13.17 | 300.83 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8756.22 | 37.28 | 282.17 | 285.33 | 1739.06 | 21.55 | 89.17 | 268.67 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8573.64 | 38.67 | 289.33 | 280.00 | 2341.09 | 25.02 | 130.50 | 275.33 |
Annual Sum or Average | 4135.50 | 0.51 | 3426.00 | 20.52 | 1264.83 | 3850.67 | 1141.08 | 18.36 | 418.33 | 3500.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 846.30 | 12.61 | 0.00 | 265.00 | 572.67 | 16.21 | 0.00 | 226.67 | |
Maximum of Months | 418.17 | 0.51 | 0.48 | 9256.88 | 38.69 | 306.33 | 364.83 | 2505.87 | 25.50 | 145.33 | 325.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:49 | 2223.78 | 22.19 | 105.17 | 275.00 | 1244.13 | 22.47 | 74.67 | 240.33 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2678.60 | 22.49 | 85.83 | 255.33 | 1514.03 | 22.84 | 62.83 | 197.17 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:19 | 2214.85 | 19.02 | 86.17 | 316.50 | 1215.79 | 21.16 | 69.67 | 286.17 |
April | 380.33 | 0.50 | 0.48 | 01-APR-06:40 | 3128.81 | 20.61 | 112.33 | 348.17 | 1794.46 | 21.46 | 82.33 | 330.50 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-05:00 | 3547.21 | 21.75 | 134.17 | 381.67 | 1469.49 | 20.84 | 72.33 | 361.00 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-05:49 | 3569.44 | 21.13 | 134.83 | 387.17 | 1449.36 | 20.30 | 74.83 | 358.00 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 3109.29 | 21.13 | 128.17 | 382.33 | 1309.21 | 20.31 | 68.33 | 331.33 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 3035.23 | 20.86 | 114.50 | 353.83 | 1721.37 | 21.61 | 83.50 | 314.67 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:30 | 2420.26 | 20.63 | 103.83 | 319.33 | 1323.34 | 21.45 | 75.17 | 283.67 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2351.56 | 20.37 | 102.83 | 296.50 | 1288.59 | 20.89 | 72.17 | 263.33 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:30 | 1899.20 | 20.32 | 80.17 | 274.00 | 1026.09 | 20.86 | 52.83 | 217.33 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:30 | 2208.99 | 22.78 | 105.00 | 261.50 | 1240.38 | 22.98 | 74.00 | 215.33 |
Annual Sum or Average | 4135.50 | 0.50 | 2758.11 | 21.05 | 1293.00 | 3851.33 | 1393.85 | 21.33 | 862.67 | 3398.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 1899.20 | 19.02 | 80.17 | 255.33 | 1026.09 | 20.30 | 52.83 | 197.17 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 3569.44 | 22.78 | 134.83 | 387.17 | 1794.46 | 22.98 | 83.50 | 361.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:30 | 488.59 | 10.03 | 0.00 | 231.33 | 351.23 | 13.84 | 0.00 | 166.67 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-09:39 | 597.62 | 11.03 | 0.00 | 228.83 | 401.50 | 14.64 | 0.00 | 150.33 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:00 | 683.44 | 12.34 | 0.00 | 304.83 | 445.52 | 15.87 | 0.00 | 243.17 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:30 | 813.24 | 13.74 | 0.00 | 337.33 | 556.13 | 17.32 | 0.00 | 310.50 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 955.77 | 14.15 | 2.67 | 389.50 | 651.37 | 17.80 | 2.67 | 375.00 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1101.70 | 17.70 | 81.33 | 400.83 | 700.30 | 20.91 | 81.50 | 395.17 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:49 | 976.42 | 16.91 | 62.50 | 394.17 | 643.54 | 20.14 | 62.83 | 365.67 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:00 | 820.02 | 13.49 | 0.00 | 349.17 | 542.63 | 17.12 | 0.00 | 302.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 774.40 | 12.92 | 0.00 | 316.17 | 494.86 | 16.37 | 0.00 | 268.83 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-07:49 | 564.29 | 11.02 | 0.00 | 266.50 | 392.61 | 14.70 | 0.00 | 205.83 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-08:09 | 528.68 | 10.59 | 0.00 | 240.17 | 366.65 | 14.42 | 0.00 | 157.17 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-08:50 | 490.23 | 10.02 | 0.00 | 220.17 | 344.25 | 13.88 | 0.00 | 140.00 |
Annual Sum or Average | 4135.50 | 0.51 | 758.17 | 13.13 | 146.50 | 3679.00 | 506.62 | 16.70 | 147.00 | 3080.67 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 488.59 | 10.02 | 0.00 | 220.17 | 344.25 | 13.84 | 0.00 | 140.00 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 1101.70 | 17.70 | 81.33 | 400.83 | 700.30 | 20.91 | 81.50 | 395.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-09:20 | 2386.59 | 21.56 | 105.67 | 250.67 | 1356.66 | 21.90 | 74.67 | 221.50 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-09:30 | 2420.04 | 20.74 | 81.17 | 241.17 | 975.34 | 19.48 | 36.50 | 184.83 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-08:09 | 2064.46 | 19.91 | 93.67 | 317.50 | 1142.85 | 20.86 | 65.33 | 283.33 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 2920.61 | 18.19 | 85.00 | 336.67 | 1663.66 | 19.43 | 55.00 | 313.67 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-07:19 | 3126.94 | 15.77 | 54.50 | 366.17 | 1769.88 | 16.17 | 0.00 | 341.67 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-06:00 | 3161.30 | 11.88 | 0.00 | 372.83 | 1333.80 | 15.73 | 0.00 | 350.33 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:19 | 2390.01 | 12.83 | 3.67 | 374.00 | 1110.62 | 16.24 | 0.00 | 333.00 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 2443.40 | 15.63 | 49.17 | 344.17 | 1374.51 | 16.39 | 5.00 | 304.00 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1968.16 | 18.49 | 81.83 | 319.00 | 1085.15 | 19.66 | 53.83 | 286.50 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2369.39 | 20.52 | 109.33 | 290.50 | 1321.06 | 21.41 | 81.17 | 263.50 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-08:20 | 2161.95 | 19.72 | 80.83 | 255.50 | 1228.36 | 21.48 | 62.50 | 216.83 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-08:50 | 1831.33 | 19.71 | 80.67 | 243.50 | 1020.30 | 21.01 | 57.50 | 208.50 |
Annual Sum or Average | 4135.50 | 0.51 | 2475.07 | 17.55 | 825.50 | 3711.67 | 1302.06 | 18.91 | 491.50 | 3307.67 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1831.33 | 11.88 | 0.00 | 241.17 | 975.34 | 15.73 | 0.00 | 184.83 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3161.30 | 21.56 | 109.33 | 374.00 | 1769.88 | 21.90 | 81.17 | 350.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:49 | 9257.89 | 38.68 | 306.33 | 291.50 | 2507.30 | 25.49 | 145.33 | 288.17 |
February | 241.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8320.89 | 36.06 | 234.00 | 265.17 | 1408.65 | 19.00 | 38.33 | 226.83 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:30 | 1632.26 | 13.13 | 2.33 | 329.17 | 997.69 | 16.72 | 1.83 | 292.00 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:30 | 1276.52 | 13.38 | 0.00 | 333.83 | 837.21 | 16.96 | 0.00 | 308.83 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:10 | 1015.19 | 13.27 | 0.00 | 360.67 | 668.03 | 16.85 | 0.00 | 325.67 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-06:49 | 846.98 | 12.58 | 0.00 | 363.83 | 573.26 | 16.19 | 0.00 | 322.50 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:10 | 971.59 | 12.84 | 0.00 | 364.83 | 614.89 | 16.39 | 0.00 | 306.17 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:19 | 1115.10 | 13.07 | 0.00 | 338.67 | 711.13 | 16.65 | 0.00 | 296.50 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:00 | 1579.61 | 13.84 | 10.83 | 320.00 | 927.71 | 16.80 | 0.00 | 290.67 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:10 | 3233.79 | 20.61 | 139.83 | 318.17 | 1222.12 | 16.31 | 13.17 | 300.83 |
November | 288.50 | 0.49 | 0.48 | 01-NOV-07:40 | 8757.50 | 37.27 | 282.17 | 285.33 | 1740.49 | 21.54 | 89.17 | 268.67 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8574.53 | 38.67 | 289.33 | 280.00 | 2342.64 | 25.00 | 130.50 | 275.50 |
Annual Sum or Average | 4135.50 | 0.51 | 3427.33 | 20.50 | 1264.83 | 3851.17 | 1142.18 | 18.35 | 418.33 | 3502.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 846.98 | 12.58 | 0.00 | 265.17 | 573.26 | 16.19 | 0.00 | 226.83 | |
Maximum of Months | 418.17 | 0.51 | 0.48 | 9257.89 | 38.68 | 306.33 | 364.83 | 2507.30 | 25.49 | 145.33 | 325.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.51 | 0.48 | 01-JAN-07:49 | 2224.18 | 22.16 | 105.17 | 275.00 | 1244.74 | 22.45 | 74.67 | 240.33 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2679.37 | 22.46 | 85.83 | 255.50 | 1514.90 | 22.83 | 62.83 | 197.33 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-07:19 | 2215.92 | 18.99 | 86.17 | 316.50 | 1216.82 | 21.15 | 69.67 | 286.17 |
April | 380.33 | 0.50 | 0.48 | 01-APR-06:40 | 3129.66 | 20.59 | 112.33 | 348.17 | 1795.45 | 21.44 | 82.33 | 330.67 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-05:00 | 3548.04 | 21.72 | 134.17 | 381.67 | 1470.46 | 20.83 | 72.33 | 361.17 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 3570.07 | 21.10 | 134.83 | 387.17 | 1450.20 | 20.28 | 74.83 | 358.17 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:49 | 3110.32 | 21.10 | 128.17 | 382.33 | 1310.22 | 20.29 | 68.33 | 331.33 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:10 | 3036.27 | 20.83 | 114.50 | 353.83 | 1722.42 | 21.60 | 83.50 | 314.83 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-06:30 | 2421.59 | 20.60 | 103.83 | 319.50 | 1324.53 | 21.44 | 75.17 | 283.83 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-06:49 | 2352.20 | 20.34 | 102.83 | 296.50 | 1289.38 | 20.88 | 72.17 | 263.50 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:30 | 1899.76 | 20.29 | 80.17 | 274.00 | 1026.79 | 20.84 | 52.83 | 217.67 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:30 | 2209.47 | 22.75 | 105.00 | 261.50 | 1241.04 | 22.96 | 74.00 | 215.33 |
Annual Sum or Average | 4135.50 | 0.50 | 2758.93 | 21.03 | 1293.00 | 3851.67 | 1394.75 | 21.32 | 862.67 | 3400.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 1899.76 | 18.99 | 80.17 | 255.50 | 1026.79 | 20.28 | 52.83 | 197.33 | |
Maximum of Months | 418.17 | 0.52 | 0.48 | 3570.07 | 22.75 | 134.83 | 387.17 | 1795.45 | 22.96 | 83.50 | 361.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:30 | 488.74 | 9.99 | 0.00 | 231.33 | 351.54 | 13.82 | 0.00 | 166.83 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-09:39 | 598.03 | 11.00 | 0.00 | 228.83 | 401.94 | 14.62 | 0.00 | 150.67 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:00 | 684.02 | 12.31 | 0.00 | 304.83 | 446.05 | 15.85 | 0.00 | 243.50 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:30 | 813.75 | 13.70 | 0.00 | 337.33 | 556.69 | 17.31 | 0.00 | 310.50 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 956.44 | 14.11 | 2.67 | 389.50 | 652.02 | 17.78 | 2.67 | 375.00 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:49 | 1102.34 | 17.67 | 81.33 | 400.83 | 700.94 | 20.90 | 81.50 | 395.33 |
July | 399.50 | 0.49 | 0.48 | 01-JUL-05:49 | 977.27 | 16.89 | 62.50 | 394.17 | 644.27 | 20.12 | 62.83 | 365.67 |
August | 361.83 | 0.50 | 0.48 | 01-AUG-06:00 | 820.68 | 13.46 | 0.00 | 349.17 | 543.23 | 17.10 | 0.00 | 302.67 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:00 | 775.11 | 12.89 | 0.00 | 316.17 | 495.47 | 16.35 | 0.00 | 269.00 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-07:49 | 564.60 | 10.99 | 0.00 | 266.50 | 392.98 | 14.69 | 0.00 | 206.50 |
November | 288.50 | 0.53 | 0.48 | 01-NOV-08:09 | 528.95 | 10.56 | 0.00 | 240.17 | 367.02 | 14.41 | 0.00 | 158.33 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-08:50 | 490.44 | 9.99 | 0.00 | 220.33 | 344.58 | 13.86 | 0.00 | 140.33 |
Annual Sum or Average | 4135.50 | 0.51 | 758.69 | 13.10 | 146.50 | 3679.17 | 507.15 | 16.69 | 147.00 | 3084.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 488.74 | 9.99 | 0.00 | 220.33 | 344.58 | 13.82 | 0.00 | 140.33 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 1102.34 | 17.67 | 81.33 | 400.83 | 700.94 | 20.90 | 81.50 | 395.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-09:20 | 2386.99 | 21.54 | 105.67 | 250.67 | 1357.37 | 21.89 | 74.67 | 221.50 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-09:30 | 2420.95 | 20.71 | 81.17 | 241.50 | 976.29 | 19.47 | 36.50 | 184.83 |
March | 344.33 | 0.51 | 0.48 | 01-MAR-08:09 | 2065.56 | 19.89 | 93.67 | 317.50 | 1143.87 | 20.85 | 65.33 | 283.83 |
April | 380.33 | 0.51 | 0.48 | 01-APR-07:00 | 2921.58 | 18.16 | 85.00 | 336.67 | 1664.78 | 19.41 | 55.00 | 313.67 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-07:19 | 3127.85 | 15.73 | 54.50 | 366.17 | 1770.97 | 16.16 | 0.00 | 341.67 |
June | 418.17 | 0.50 | 0.48 | 01-JUN-06:00 | 3160.48 | 11.84 | 0.00 | 372.83 | 1334.75 | 15.71 | 0.00 | 350.33 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-07:19 | 2369.07 | 12.80 | 3.67 | 373.83 | 1111.66 | 16.22 | 0.00 | 333.17 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 2444.37 | 15.60 | 49.17 | 344.33 | 1375.49 | 16.37 | 5.00 | 304.00 |
September | 350.17 | 0.51 | 0.48 | 01-SEP-07:19 | 1969.47 | 18.47 | 81.83 | 319.17 | 1086.28 | 19.65 | 53.83 | 286.67 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2370.07 | 20.49 | 109.33 | 290.50 | 1321.85 | 21.40 | 81.17 | 263.67 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-08:20 | 2162.47 | 19.69 | 80.83 | 255.50 | 1229.14 | 21.46 | 62.50 | 217.00 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-08:50 | 1831.80 | 19.68 | 80.67 | 243.67 | 1021.01 | 20.99 | 57.50 | 208.50 |
Annual Sum or Average | 4135.50 | 0.51 | 2473.64 | 17.52 | 825.50 | 3712.33 | 1303.01 | 18.90 | 491.50 | 3308.83 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1831.80 | 11.84 | 0.00 | 241.50 | 976.29 | 15.71 | 0.00 | 184.83 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3160.48 | 21.54 | 109.33 | 373.83 | 1770.97 | 21.89 | 81.17 | 350.33 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122868E+09 | 8520.11 | 12-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179773E+09 | 7838.75 | 01-FEB-07:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235300E+09 | 13975.59 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24992123.31 | 6770.67 | 25-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40805840.24 | 7249.11 | 04-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.759768E+09 | 19606.24 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.759768E+09 | 19606.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2114787.22 | 3738.10 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2114787.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2114787.22 | 3738.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.300260E+10 | 101344.80 | 02-JAN-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.411065E+10 | 149819.99 | 09-FEB-10:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.470790E+10 | 154483.19 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5888775.72 | 8277.08 | 21-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.933276E+09 | 94008.20 | 25-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194618E+10 | 109359.23 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166034E+11 | 193891.33 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166034E+11 | 193891.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136392E+10 | 156676.46 | 02-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.931468E+09 | 118489.75 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.726299E+09 | 170576.49 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12942690.69 | 5115.51 | 26-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.562345E+09 | 156287.58 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.409521E+10 | 169805.15 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.409521E+10 | 170576.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.428555E+09 | 140551.19 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221470E+09 | 73027.83 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231338E+09 | 102683.93 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115736E+09 | 104644.63 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146938E+10 | 144498.33 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146938E+10 | 144498.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.168375E+09 | 157481.91 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 97990431.30 | 94946.18 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.177097E+09 | 133532.93 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18354154.51 | 37208.69 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.820729E+09 | 174377.38 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.820729E+09 | 174377.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.204419E+09 | 106986.61 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64296505.25 | 34401.30 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 50955830.46 | 60678.35 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 59725741.74 | 76228.93 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105841E+10 | 137778.79 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105841E+10 | 137778.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.595069E+09 | 13082.81 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.826639E+09 | 11990.05 | 28-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.783057E+09 | 18378.65 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9399234.81 | 4039.52 | 21-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.230049E+09 | 11740.78 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.424108E+09 | 14869.18 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246446E+10 | 19228.96 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246446E+10 | 19228.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.366112E+09 | 75731.42 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115823E+09 | 75627.08 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 42449708.54 | 55299.50 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46632708.97 | 65501.25 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347833E+09 | 75479.17 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.918851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.366112E+09 | 75731.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.834937E+09 | 18164.82 | 21-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.740520E+09 | 18165.78 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.478935E+09 | 18167.24 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 993741.42 | 446.23 | 21-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120368E+09 | 18016.13 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.547663E+09 | 18158.62 | 18-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189876E+10 | 18080.10 | 18-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.462218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189876E+10 | 18167.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324298E+09 | 16272.30 | 02-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305658E+09 | 16279.54 | 06-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190847E+09 | 16279.28 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45893271.59 | 12436.74 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191977E+09 | 16243.07 | 24-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.750334E+09 | 16271.90 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.750334E+09 | 16279.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208532E+09 | 19758.69 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318836E+09 | 19955.68 | 13-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271239E+09 | 19946.90 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32923271.61 | 8354.54 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146437E+09 | 19650.49 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.665801E+09 | 19860.62 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.665801E+09 | 19955.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.202880E+09 | 16798.07 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198322E+09 | 16810.26 | 13-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126236E+09 | 16777.59 | 27-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19765724.18 | 5803.29 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133929E+09 | 16773.58 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.604944E+09 | 16822.64 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.604944E+09 | 16822.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 478.65 | 0.96 | 31-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 833.03 | 0.98 | 21-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1186.57 | 0.97 | 28-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 424.75 | 0.96 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 169.71 | 0.85 | 21-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 428.19 | 0.96 | 14-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 603.71 | 0.94 | 25-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 274.22 | 0.97 | 22-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4398.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1186.57 | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.400784E+11 | 0.400672E+11 | 96948.95 | 31-JAN-16:50 | 96948.95 | 0.01 |
February | 0.00 | 0.00 | 0.111162E+11 | 0.111162E+11 | 64164.77 | 21-FEB-15:00 | 64164.77 | 0.09 |
March | 0.00 | 0.00 | 0.435185E+11 | 0.435185E+11 | 107628.51 | 20-MAR-14:50 | 107628.51 | 0.09 |
April | 0.00 | 0.00 | 0.112700E+12 | 0.112700E+12 | 137615.82 | 24-APR-15:00 | 137615.82 | 0.02 |
May | 0.00 | 0.00 | 0.123596E+12 | 0.123596E+12 | 127987.22 | 15-MAY-15:20 | 127987.22 | 0.00 |
June | 0.00 | 0.00 | 0.166666E+12 | 0.166666E+12 | 152306.17 | 17-JUN-05:02 | 152306.17 | 0.11 |
July | 0.00 | 0.00 | 0.173992E+12 | 0.163579E+12 | 280108.03 | 18-JUL-05:03 | 128551.35 | 0.66 |
August | 0.00 | 0.00 | 0.193608E+12 | 0.182811E+12 | 260301.02 | 01-AUG-05:02 | 125324.90 | 0.75 |
September | 0.00 | 0.00 | 0.138211E+12 | 0.129106E+12 | 241536.98 | 08-SEP-05:02 | 140972.23 | 0.58 |
October | 0.00 | 0.00 | 0.850340E+11 | 0.836065E+11 | 180156.81 | 03-OCT-04:12 | 98546.62 | 0.20 |
November | 0.00 | 0.00 | 0.467024E+11 | 0.440342E+11 | 135727.76 | 13-NOV-05:12 | 47962.66 | 0.15 |
December | 0.00 | 0.00 | 0.297061E+11 | 0.297061E+11 | 95635.41 | 22-DEC-16:30 | 95635.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116493E+13 | 0.113051E+13 | 0.22 | |||
Minimum of Months | 0.00 | 0.00 | 0.111162E+11 | 0.111162E+11 | 64164.77 | 47962.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.193608E+12 | 0.182811E+12 | 280108.03 | 152306.17 | 0.75 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.347440E+12 | 0.347320E+12 | 855584.63 | 31-JAN-16:30 | 855584.63 | 0.03 |
February | 0.00 | 0.00 | 0.140922E+12 | 0.140922E+12 | 580089.64 | 21-FEB-15:05 | 580089.64 | 0.13 |
March | 0.00 | 0.00 | 0.331063E+12 | 0.331063E+12 | 910320.52 | 16-MAR-15:50 | 910320.52 | 0.09 |
April | 0.00 | 0.00 | 0.851962E+12 | 0.851962E+12 | 1199266.85 | 14-APR-15:20 | 1199266.85 | 0.01 |
May | 0.00 | 0.00 | 0.111208E+13 | 0.111208E+13 | 1209990.38 | 18-MAY-15:10 | 1209990.38 | 0.00 |
June | 0.00 | 0.00 | 0.148257E+13 | 0.148257E+13 | 1414742.62 | 09-JUN-05:02 | 1414742.62 | 0.09 |
July | 0.00 | 0.00 | 0.141927E+13 | 0.134601E+13 | 2670412.88 | 18-JUL-05:03 | 1222635.99 | 0.57 |
August | 0.00 | 0.00 | 0.144322E+13 | 0.137549E+13 | 2349338.88 | 01-AUG-05:02 | 1142066.98 | 0.62 |
September | 0.00 | 0.00 | 0.119826E+13 | 0.112308E+13 | 2311933.47 | 08-SEP-05:02 | 1347486.38 | 0.52 |
October | 0.00 | 0.00 | 0.703571E+12 | 0.691608E+12 | 1717620.31 | 03-OCT-04:12 | 935653.28 | 0.17 |
November | 0.00 | 0.00 | 0.343287E+12 | 0.330091E+12 | 977721.89 | 13-NOV-05:12 | 343617.22 | 0.13 |
December | 0.00 | 0.00 | 0.214854E+12 | 0.214854E+12 | 744229.52 | 22-DEC-15:05 | 744229.52 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.958849E+13 | 0.934704E+13 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.140922E+12 | 0.140922E+12 | 580089.64 | 343617.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.148257E+13 | 0.148257E+13 | 2670412.88 | 1414742.62 | 0.62 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.283735E+11 | 0.283656E+11 | 89351.45 | 31-JAN-16:30 | 89351.45 | 0.01 |
February | 0.00 | 0.00 | 0.601059E+10 | 0.601059E+10 | 46684.32 | 22-FEB-16:00 | 46684.32 | 0.10 |
March | 0.00 | 0.00 | 0.300810E+11 | 0.300810E+11 | 103528.63 | 16-MAR-15:30 | 103528.63 | 0.08 |
April | 0.00 | 0.00 | 0.931120E+11 | 0.931120E+11 | 142760.61 | 14-APR-15:20 | 142760.61 | 0.01 |
May | 0.00 | 0.00 | 0.123028E+12 | 0.123028E+12 | 144111.97 | 18-MAY-15:20 | 144111.97 | 0.00 |
June | 0.00 | 0.00 | 0.169010E+12 | 0.169010E+12 | 170210.03 | 28-JUN-14:50 | 170210.03 | 0.09 |
July | 0.00 | 0.00 | 0.161834E+12 | 0.154244E+12 | 282624.52 | 18-JUL-05:03 | 127656.12 | 0.58 |
August | 0.00 | 0.00 | 0.161121E+12 | 0.154140E+12 | 277698.34 | 01-AUG-05:02 | 133928.91 | 0.63 |
September | 0.00 | 0.00 | 0.130021E+12 | 0.122655E+12 | 257179.95 | 08-SEP-05:02 | 150247.80 | 0.53 |
October | 0.00 | 0.00 | 0.701805E+11 | 0.690767E+11 | 191406.78 | 03-OCT-04:12 | 104714.98 | 0.16 |
November | 0.00 | 0.00 | 0.288837E+11 | 0.279932E+11 | 105529.25 | 01-NOV-15:20 | 105529.25 | 0.12 |
December | 0.00 | 0.00 | 0.125874E+11 | 0.125874E+11 | 75608.92 | 22-DEC-16:30 | 75608.92 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.101424E+13 | 0.990303E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.601059E+10 | 0.601059E+10 | 46684.32 | 46684.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169010E+12 | 0.169010E+12 | 282624.52 | 170210.03 | 0.63 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.246559E+11 | 0.246519E+11 | 83325.99 | 16-JAN-12:20 | 83325.99 | 0.00 |
February | 0.00 | 0.00 | 0.433835E+10 | 0.431611E+10 | 50183.89 | 17-FEB-06:03 | 21166.76 | 0.06 |
March | 0.00 | 0.00 | 0.238974E+11 | 0.238921E+11 | 62904.85 | 20-MAR-13:20 | 62904.85 | 0.05 |
April | 0.00 | 0.00 | 0.579223E+11 | 0.579223E+11 | 94211.98 | 25-APR-03:50 | 94211.98 | 0.00 |
May | 0.00 | 0.00 | 0.711567E+11 | 0.711567E+11 | 114979.42 | 29-MAY-18:27 | 114979.42 | 0.00 |
June | 0.00 | 0.00 | 0.868675E+11 | 0.868675E+11 | 108670.38 | 17-JUN-04:03 | 108670.38 | 0.07 |
July | 0.00 | 0.00 | 0.935453E+11 | 0.902792E+11 | 159468.80 | 14-JUL-04:33 | 63629.51 | 0.47 |
August | 0.00 | 0.00 | 0.105143E+12 | 0.101123E+12 | 152774.24 | 01-AUG-03:02 | 80069.07 | 0.55 |
September | 0.00 | 0.00 | 0.888709E+11 | 0.845644E+11 | 149135.94 | 02-SEP-03:02 | 79841.03 | 0.48 |
October | 0.00 | 0.00 | 0.559904E+11 | 0.554512E+11 | 114747.35 | 15-OCT-13:15 | 114747.35 | 0.15 |
November | 0.00 | 0.00 | 0.298360E+11 | 0.276546E+11 | 103586.05 | 13-NOV-05:42 | 37123.84 | 0.11 |
December | 0.00 | 0.00 | 0.132625E+11 | 0.132602E+11 | 76991.29 | 24-DEC-14:40 | 76991.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.655486E+12 | 0.641139E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 0.433835E+10 | 0.431611E+10 | 50183.89 | 21166.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.105143E+12 | 0.101123E+12 | 159468.80 | 114979.42 | 0.55 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.290146E+11 | 0.289859E+11 | 135188.37 | 27-JAN-16:00 | 135188.37 | 0.00 |
February | 0.00 | 0.00 | 0.101614E+11 | 0.957710E+10 | 100916.56 | 18-FEB-14:00 | 86934.26 | 0.00 |
March | 0.00 | 0.00 | 0.193547E+12 | 0.189645E+12 | 316930.05 | 17-MAR-15:20 | 316930.05 | 0.00 |
April | 0.00 | 0.00 | 0.671619E+12 | 0.669874E+12 | 376228.52 | 15-APR-09:00 | 376228.52 | 0.00 |
May | 0.00 | 0.00 | 0.217138E+12 | 0.217138E+12 | 213492.39 | 31-MAY-23:10 | 213492.39 | 0.00 |
June | 0.00 | 0.00 | 0.518437E+12 | 0.518428E+12 | 306092.81 | 30-JUN-23:57 | 306092.81 | 0.00 |
July | 0.00 | 0.00 | 0.870333E+12 | 0.787202E+12 | 467543.62 | 14-JUL-01:00 | 154646.21 | 0.00 |
August | 0.00 | 0.00 | 0.106368E+13 | 0.932815E+12 | 451581.52 | 09-AUG-18:30 | 232765.10 | 0.00 |
September | 0.00 | 0.00 | 0.265972E+12 | 0.239486E+12 | 233665.76 | 04-SEP-10:13 | 129506.05 | 0.00 |
October | 0.00 | 0.00 | 0.251066E+12 | 0.240033E+12 | 336596.21 | 03-OCT-08:30 | 223794.62 | 0.00 |
November | 0.00 | 0.00 | 0.202931E+12 | 0.175642E+12 | 320010.05 | 09-NOV-13:05 | 320010.05 | 0.00 |
December | 0.00 | 0.00 | 0.202669E+12 | 0.202282E+12 | 347312.46 | 25-DEC-13:52 | 347312.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.449656E+13 | 0.421111E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.101614E+11 | 0.957710E+10 | 100916.56 | 86934.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106368E+13 | 0.932815E+12 | 467543.62 | 376228.52 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.547763E+10 | 0.547443E+10 | 2840.74 | 29-JAN-17:15 | 2840.74 | 0.00 |
February | 0.00 | 0.00 | 0.940569E+10 | 0.936189E+10 | 4566.17 | 20-FEB-17:03 | 4545.75 | 0.00 |
March | 0.00 | 0.00 | 0.157473E+11 | 0.157357E+11 | 7721.38 | 31-MAR-24:00 | 7721.38 | 0.00 |
April | 0.00 | 0.00 | 0.199920E+11 | 0.199920E+11 | 8286.92 | 26-APR-18:50 | 8286.92 | 0.00 |
May | 0.00 | 0.00 | 0.630701E+10 | 0.630701E+10 | 4064.96 | 31-MAY-23:55 | 4064.96 | 0.00 |
June | 0.00 | 0.00 | 0.112014E+11 | 0.111999E+11 | 6001.18 | 30-JUN-24:00 | 6001.18 | 0.00 |
July | 0.00 | 0.00 | 0.167090E+11 | 0.165582E+11 | 7925.85 | 31-JUL-23:53 | 7912.57 | 0.00 |
August | 0.00 | 0.00 | 0.213937E+11 | 0.212431E+11 | 8769.85 | 28-AUG-16:45 | 8225.80 | 0.00 |
September | 0.00 | 0.00 | 0.628059E+10 | 0.614313E+10 | 4063.91 | 30-SEP-24:00 | 4063.91 | 0.00 |
October | 0.00 | 0.00 | 0.111175E+11 | 0.110869E+11 | 5892.89 | 31-OCT-24:00 | 5892.89 | 0.00 |
November | 0.00 | 0.00 | 0.154143E+11 | 0.153653E+11 | 6839.71 | 26-NOV-16:53 | 6839.71 | 0.00 |
December | 0.00 | 0.00 | 0.206259E+11 | 0.206254E+11 | 8366.15 | 28-DEC-17:00 | 8366.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159672E+12 | 0.159093E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.547763E+10 | 0.547443E+10 | 2840.74 | 2840.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.213937E+11 | 0.212431E+11 | 8769.85 | 8366.15 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.430650E+11 | 0.430344E+11 | 25547.41 | 24-JAN-17:00 | 25547.41 | 0.00 |
February | 0.00 | 0.00 | 0.809914E+11 | 0.805601E+11 | 42053.06 | 22-FEB-17:00 | 41521.74 | 0.00 |
March | 0.00 | 0.00 | 0.143980E+12 | 0.143864E+12 | 72417.16 | 31-MAR-23:40 | 72417.16 | 0.00 |
April | 0.00 | 0.00 | 0.189327E+12 | 0.189327E+12 | 78982.55 | 26-APR-18:50 | 78982.55 | 0.00 |
May | 0.00 | 0.00 | 0.587126E+11 | 0.587126E+11 | 39502.21 | 31-MAY-23:55 | 39502.21 | 0.00 |
June | 0.00 | 0.00 | 0.106710E+12 | 0.106693E+12 | 57678.52 | 30-JUN-24:00 | 57678.52 | 0.00 |
July | 0.00 | 0.00 | 0.158919E+12 | 0.157418E+12 | 75724.87 | 31-JUL-23:53 | 75594.85 | 0.00 |
August | 0.00 | 0.00 | 0.201718E+12 | 0.200195E+12 | 82772.61 | 28-AUG-16:25 | 77121.58 | 0.00 |
September | 0.00 | 0.00 | 0.582084E+11 | 0.568589E+11 | 39536.66 | 30-SEP-24:00 | 39536.66 | 0.00 |
October | 0.00 | 0.00 | 0.101848E+12 | 0.101545E+12 | 54737.28 | 31-OCT-24:00 | 54737.28 | 0.00 |
November | 0.00 | 0.00 | 0.139850E+12 | 0.139364E+12 | 64584.75 | 14-NOV-17:00 | 62339.50 | 0.00 |
December | 0.00 | 0.00 | 0.185735E+12 | 0.185729E+12 | 78709.06 | 28-DEC-17:00 | 78709.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.146907E+13 | 0.146330E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.430650E+11 | 0.430344E+11 | 25547.41 | 25547.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201718E+12 | 0.200195E+12 | 82772.61 | 78982.55 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.339174E+10 | 0.338894E+10 | 2583.50 | 24-JAN-17:00 | 2583.50 | 0.00 |
February | 0.00 | 0.00 | 0.711197E+10 | 0.706948E+10 | 4242.70 | 22-FEB-17:00 | 4189.23 | 0.00 |
March | 0.00 | 0.00 | 0.137743E+11 | 0.137628E+11 | 7082.37 | 31-MAR-23:20 | 7082.37 | 0.00 |
April | 0.00 | 0.00 | 0.190025E+11 | 0.190025E+11 | 8013.25 | 26-APR-18:30 | 8013.25 | 0.00 |
May | 0.00 | 0.00 | 0.593512E+10 | 0.593512E+10 | 3961.93 | 31-MAY-23:55 | 3961.93 | 0.00 |
June | 0.00 | 0.00 | 0.108602E+11 | 0.108585E+11 | 5832.57 | 30-JUN-24:00 | 5832.57 | 0.00 |
July | 0.00 | 0.00 | 0.161018E+11 | 0.159516E+11 | 7629.59 | 31-JUL-23:53 | 7616.48 | 0.00 |
August | 0.00 | 0.00 | 0.203861E+11 | 0.202326E+11 | 8393.63 | 28-AUG-16:15 | 7795.88 | 0.00 |
September | 0.00 | 0.00 | 0.592197E+10 | 0.578655E+10 | 3995.09 | 30-SEP-24:00 | 3995.09 | 0.00 |
October | 0.00 | 0.00 | 0.984835E+10 | 0.981819E+10 | 5298.65 | 31-OCT-23:40 | 5298.65 | 0.00 |
November | 0.00 | 0.00 | 0.131729E+11 | 0.131247E+11 | 6486.42 | 14-NOV-17:00 | 6261.47 | 0.00 |
December | 0.00 | 0.00 | 0.172443E+11 | 0.172438E+11 | 7924.14 | 26-DEC-17:10 | 7924.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142751E+12 | 0.142175E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.339174E+10 | 0.338894E+10 | 2583.50 | 2583.50 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203861E+11 | 0.202326E+11 | 8393.63 | 8013.25 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2886.17 | 808979.61 | 02-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 3330.88 | 593950.10 | 13-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2970.95 | 768533.37 | 27-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.97 | 9692.30 | 21-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.61 | 01-MAY-05:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.54 | 21-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 513.28 | 135031.84 | 25-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1617.88 | 697355.66 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 11670.07 | 915238.40 | 07-DEC-06:01 |
Annual Sum or Average | 0.00 | 1921.11 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 11670.07 | 915238.40 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 174523.31 | 1611526.39 | 31-JAN-15:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 67990.62 | 766158.57 | 21-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 166183.95 | 1565433.42 | 16-MAR-14:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 447649.28 | 1622840.76 | 03-APR-12:05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 554095.09 | 1657143.40 | 25-MAY-12:05 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 752095.20 | 1924392.65 | 19-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 716852.01 | 2957029.41 | 14-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 735001.15 | 2273954.68 | 01-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 627045.71 | 2271421.49 | 12-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 356331.64 | 1727923.12 | 10-OCT-08:55 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 184454.27 | 1704096.38 | 02-NOV-14:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 104444.51 | 1337172.75 | 22-DEC-15:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 408962.88 | 0.00 | ||||
Minimum of Months | 67990.62 | 766158.57 | 0.00 | 0.00 | ||
Maximum of Months | 752095.20 | 2957029.41 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 172605.03 | 1437769.10 | 31-JAN-16:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 67039.05 | 765726.00 | 21-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 164790.57 | 1402622.78 | 17-MAR-14:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 442036.56 | 1649626.34 | 25-APR-05:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 548191.13 | 1723602.22 | 08-MAY-04:11 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 745544.81 | 2296469.95 | 09-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 713575.23 | 3559500.46 | 14-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 732363.22 | 3326058.56 | 28-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 624461.24 | 3218488.66 | 02-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 353697.50 | 3245117.49 | 03-OCT-04:12 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 183393.90 | 2312927.84 | 02-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 103223.76 | 1311712.10 | 22-DEC-15:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 405978.16 | 0.00 | ||||
Minimum of Months | 67039.05 | 765726.00 | 0.00 | 0.00 | ||
Maximum of Months | 745544.81 | 3559500.46 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 107519.01 | 861179.38 | 31-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 66044.38 | 450317.18 | 18-FEB-14:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 294892.00 | 1295566.46 | 16-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 956838.58 | 1753037.35 | 14-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 628601.87 | 1299445.08 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1164572.57 | 1832979.62 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1406839.33 | 1965679.74 | 19-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1549124.87 | 2118031.03 | 27-AUG-14:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 734380.21 | 1379474.72 | 08-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 474994.03 | 1518168.65 | 01-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 295153.87 | 1304197.71 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 273399.75 | 1247943.21 | 25-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 666230.40 | 0.00 | ||||
Minimum of Months | 66044.38 | 450317.18 | 0.00 | 0.00 | ||
Maximum of Months | 1549124.87 | 2118031.03 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 13394.82 | 44380.36 | 26-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13350.03 | 44241.77 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13472.40 | 43015.27 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11814.45 | 39988.42 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 11167.44 | 36793.50 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 10551.60 | 33479.91 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 9444.32 | 31298.69 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 10336.21 | 32147.64 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 10383.40 | 34804.43 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11269.58 | 38404.75 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12383.45 | 41623.34 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12738.54 | 43718.67 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 11683.04 | ||||
Minimum of Months | 0.00 | 0.00 | 9444.32 | 31298.69 | ||
Maximum of Months | 0.00 | 0.00 | 13472.40 | 44380.36 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 200113.36 | 2179183.04 | 27-JAN-15:30 | 946.06 | 96864.22 | 13-JAN-06:40 |
February | 79174.00 | 877050.92 | 21-FEB-15:30 | 974.18 | 80760.29 | 03-FEB-11:40 |
March | 189415.96 | 2301785.11 | 17-MAR-15:30 | 1264.73 | 120502.76 | 25-MAR-06:00 |
April | 572822.32 | 2369736.00 | 12-APR-14:30 | 3543.69 | 96208.89 | 23-APR-02:40 |
May | 738351.31 | 2377723.19 | 16-MAY-14:30 | 425.76 | 88139.56 | 01-MAY-01:30 |
June | 1060650.41 | 3903263.11 | 28-JUN-16:00 | 596.98 | 55390.32 | 07-JUN-03:10 |
July | 1338826.45 | 4725012.47 | 14-JUL-05:07 | 347.98 | 74690.05 | 02-JUL-00:50 |
August | 1363792.62 | 4596172.62 | 16-AUG-11:00 | 317.41 | 75228.37 | 25-AUG-02:50 |
September | 1078238.41 | 4758962.30 | 01-SEP-12:30 | 27.22 | 17668.36 | 20-SEP-00:47 |
October | 493859.55 | 3783872.84 | 03-OCT-10:05 | 912.71 | 103199.60 | 12-OCT-06:40 |
November | 220441.13 | 2227770.78 | 01-NOV-12:50 | 1181.42 | 79352.75 | 24-NOV-07:40 |
December | 120347.43 | 2140531.93 | 22-DEC-16:00 | 2192.17 | 126354.47 | 14-DEC-08:07 |
Annual Sum or Average | 624568.08 | 1058.54 | ||||
Minimum of Months | 79174.00 | 877050.92 | 27.22 | 17668.36 | ||
Maximum of Months | 1363792.62 | 4758962.30 | 3543.69 | 126354.47 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149887E+11 | 0.89 | 9631.77 | 01-JAN-00:20 | 1.53 |
February | 0.129783E+11 | 0.85 | 9631.77 | 01-FEB-05:12 | 1.53 |
March | 0.150256E+11 | 0.89 | 9631.77 | 01-MAR-05:12 | 1.52 |
April | 0.142034E+11 | 0.87 | 9631.77 | 01-APR-04:12 | 1.53 |
May | 0.149221E+11 | 0.89 | 9631.77 | 01-MAY-00:13 | 1.54 |
June | 0.150063E+11 | 0.92 | 9631.77 | 01-JUN-04:11 | 1.53 |
July | 0.157631E+11 | 0.93 | 9631.77 | 01-JUL-04:12 | 1.54 |
August | 0.170677E+11 | 1.00 | 9631.77 | 01-AUG-03:02 | 1.51 |
September | 0.159282E+11 | 0.97 | 9631.77 | 01-SEP-03:03 | 1.51 |
October | 0.161748E+11 | 0.96 | 9631.77 | 01-OCT-11:22 | 1.53 |
November | 0.153659E+11 | 0.94 | 9631.77 | 01-NOV-04:12 | 1.52 |
December | 0.155604E+11 | 0.93 | 9631.77 | 01-DEC-05:12 | 1.53 |
Annual Sum or Average | 0.182984E+12 | 0.92 | |||
Minimum of Months | 0.129783E+11 | 0.85 | 9631.77 | 1.51 | |
Maximum of Months | 0.170677E+11 | 1.00 | 9631.77 | 1.54 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.603735E+10 | 0.42 | 11900.81 | 17-JAN-17:00 | 1.34 |
February | 0.547534E+10 | 0.41 | 12238.59 | 21-FEB-16:00 | 1.36 |
March | 0.836378E+10 | 0.51 | 14638.04 | 20-MAR-15:00 | 1.51 |
April | 0.132559E+11 | 0.76 | 21667.84 | 24-APR-05:02 | 1.96 |
May | 0.121160E+11 | 0.65 | 21667.84 | 08-MAY-04:11 | 1.95 |
June | 0.150238E+11 | 0.82 | 21667.84 | 01-JUN-04:11 | 1.94 |
July | 0.153905E+11 | 0.81 | 21667.84 | 05-JUL-04:11 | 1.95 |
August | 0.182741E+11 | 0.89 | 21667.84 | 01-AUG-05:02 | 1.93 |
September | 0.113392E+11 | 0.65 | 21667.84 | 01-SEP-05:03 | 1.93 |
October | 0.942396E+10 | 0.55 | 21667.84 | 02-OCT-04:23 | 1.93 |
November | 0.793705E+10 | 0.49 | 15517.79 | 20-NOV-17:00 | 1.58 |
December | 0.706253E+10 | 0.45 | 15338.84 | 26-DEC-17:00 | 1.57 |
Annual Sum or Average | 0.129700E+12 | 0.62 | |||
Minimum of Months | 0.547534E+10 | 0.41 | 11900.81 | 1.34 | |
Maximum of Months | 0.182741E+11 | 0.89 | 21667.84 | 1.96 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.402678E+11 | 0.36 | 85267.52 | 31-JAN-17:00 | 1.14 |
February | 0.334844E+11 | 0.35 | 78818.06 | 03-FEB-06:02 | 1.08 |
March | 0.486298E+11 | 0.40 | 104901.39 | 16-MAR-15:50 | 1.28 |
April | 0.842289E+11 | 0.54 | 196210.93 | 25-APR-05:03 | 1.90 |
May | 0.102508E+12 | 0.59 | 204025.10 | 08-MAY-04:11 | 1.95 |
June | 0.125121E+12 | 0.72 | 204025.10 | 01-JUN-04:11 | 1.94 |
July | 0.112045E+12 | 0.65 | 204025.10 | 03-JUL-04:11 | 1.96 |
August | 0.116337E+12 | 0.66 | 204025.10 | 01-AUG-05:02 | 1.93 |
September | 0.916202E+11 | 0.56 | 204025.10 | 02-SEP-05:03 | 1.93 |
October | 0.640942E+11 | 0.45 | 204025.10 | 02-OCT-05:02 | 1.93 |
November | 0.444005E+11 | 0.38 | 97408.33 | 01-NOV-05:03 | 1.22 |
December | 0.351743E+11 | 0.35 | 103972.58 | 05-DEC-06:02 | 1.28 |
Annual Sum or Average | 0.897911E+12 | 0.50 | |||
Minimum of Months | 0.334844E+11 | 0.35 | 78818.06 | 1.08 | |
Maximum of Months | 0.125121E+12 | 0.72 | 204025.10 | 1.96 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.344562E+10 | 0.36 | 7474.25 | 31-JAN-16:40 | 0.97 |
February | 0.277004E+10 | 0.34 | 6843.43 | 22-FEB-16:30 | 0.92 |
March | 0.402323E+10 | 0.37 | 10515.79 | 16-MAR-15:30 | 1.18 |
April | 0.826065E+10 | 0.51 | 16821.39 | 24-APR-15:20 | 1.58 |
May | 0.103805E+11 | 0.57 | 23167.51 | 08-MAY-04:11 | 1.94 |
June | 0.137669E+11 | 0.73 | 23167.51 | 09-JUN-05:02 | 1.94 |
July | 0.122569E+11 | 0.66 | 23167.51 | 07-JUL-05:02 | 1.94 |
August | 0.124808E+11 | 0.65 | 23167.51 | 01-AUG-05:02 | 1.92 |
September | 0.938794E+10 | 0.55 | 23167.51 | 02-SEP-05:03 | 1.92 |
October | 0.578477E+10 | 0.42 | 23167.51 | 02-OCT-05:02 | 1.92 |
November | 0.365913E+10 | 0.36 | 9323.89 | 02-NOV-15:50 | 1.09 |
December | 0.295655E+10 | 0.35 | 6760.23 | 22-DEC-16:50 | 0.92 |
Annual Sum or Average | 0.891730E+11 | 0.49 | |||
Minimum of Months | 0.277004E+10 | 0.34 | 6760.23 | 0.92 | |
Maximum of Months | 0.137669E+11 | 0.73 | 23167.51 | 1.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.103419E+12 | 1.49 | 38612.35 | 01-JAN-00:05 | 1.48 |
February | 0.934110E+11 | 1.48 | 38612.35 | 01-FEB-00:10 | 1.49 |
March | 0.103419E+12 | 1.49 | 38612.35 | 01-MAR-00:10 | 1.48 |
April | 0.100083E+12 | 1.49 | 38612.35 | 01-APR-00:10 | 1.49 |
May | 0.103419E+12 | 1.49 | 38612.35 | 01-MAY-00:10 | 1.49 |
June | 0.100083E+12 | 1.48 | 38612.35 | 01-JUN-00:05 | 1.49 |
July | 0.103419E+12 | 1.48 | 38612.35 | 01-JUL-00:05 | 1.48 |
August | 0.103419E+12 | 1.47 | 38612.35 | 01-AUG-00:05 | 1.48 |
September | 0.100083E+12 | 1.47 | 38612.35 | 01-SEP-00:10 | 1.48 |
October | 0.103419E+12 | 1.49 | 38612.35 | 01-OCT-00:10 | 1.48 |
November | 0.100083E+12 | 1.49 | 38612.35 | 01-NOV-00:10 | 1.49 |
December | 0.103419E+12 | 1.49 | 38612.35 | 01-DEC-00:10 | 1.49 |
Annual Sum or Average | 0.121768E+13 | 1.48 | |||
Minimum of Months | 0.934110E+11 | 1.47 | 38612.35 | 1.48 | |
Maximum of Months | 0.103419E+12 | 1.49 | 38612.35 | 1.49 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153092E+10 | 1.01 | 571.58 | 01-JAN-00:05 | 1.01 |
February | 0.138276E+10 | 1.01 | 571.58 | 01-FEB-00:10 | 1.01 |
March | 0.153092E+10 | 1.01 | 571.58 | 01-MAR-00:10 | 1.01 |
April | 0.148153E+10 | 1.01 | 571.58 | 01-APR-00:10 | 1.01 |
May | 0.153092E+10 | 1.01 | 571.58 | 01-MAY-00:10 | 1.01 |
June | 0.148153E+10 | 1.01 | 571.58 | 01-JUN-00:05 | 1.01 |
July | 0.153092E+10 | 1.00 | 571.58 | 01-JUL-00:05 | 1.01 |
August | 0.153092E+10 | 1.00 | 571.58 | 01-AUG-00:05 | 1.00 |
September | 0.148153E+10 | 1.00 | 571.58 | 01-SEP-00:10 | 1.00 |
October | 0.153092E+10 | 1.01 | 571.58 | 01-OCT-00:10 | 1.01 |
November | 0.148153E+10 | 1.01 | 571.58 | 01-NOV-00:10 | 1.01 |
December | 0.153092E+10 | 1.01 | 571.58 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.180253E+11 | 1.01 | |||
Minimum of Months | 0.138276E+10 | 1.00 | 571.58 | 1.00 | |
Maximum of Months | 0.153092E+10 | 1.01 | 571.58 | 1.01 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146150E+11 | 1.01 | 5456.63 | 01-JAN-00:05 | 1.01 |
February | 0.132007E+11 | 1.01 | 5456.63 | 01-FEB-00:10 | 1.01 |
March | 0.146150E+11 | 1.01 | 5456.63 | 01-MAR-00:10 | 1.01 |
April | 0.141436E+11 | 1.01 | 5456.63 | 01-APR-00:10 | 1.01 |
May | 0.146150E+11 | 1.01 | 5456.63 | 01-MAY-00:10 | 1.01 |
June | 0.141436E+11 | 1.01 | 5456.63 | 01-JUN-00:05 | 1.01 |
July | 0.146150E+11 | 1.00 | 5456.63 | 01-JUL-00:05 | 1.01 |
August | 0.146150E+11 | 1.00 | 5456.63 | 01-AUG-00:05 | 1.00 |
September | 0.141436E+11 | 1.00 | 5456.63 | 01-SEP-00:10 | 1.00 |
October | 0.146150E+11 | 1.01 | 5456.63 | 01-OCT-00:10 | 1.01 |
November | 0.141436E+11 | 1.01 | 5456.63 | 01-NOV-00:10 | 1.01 |
December | 0.146150E+11 | 1.01 | 5456.63 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.172080E+12 | 1.01 | |||
Minimum of Months | 0.132007E+11 | 1.00 | 5456.63 | 1.00 | |
Maximum of Months | 0.146150E+11 | 1.01 | 5456.63 | 1.01 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149565E+10 | 1.01 | 558.41 | 01-JAN-00:05 | 1.00 |
February | 0.135091E+10 | 1.01 | 558.41 | 01-FEB-00:10 | 1.01 |
March | 0.149565E+10 | 1.01 | 558.41 | 01-MAR-00:10 | 1.01 |
April | 0.144741E+10 | 1.01 | 558.41 | 01-APR-00:10 | 1.01 |
May | 0.149565E+10 | 1.01 | 558.41 | 01-MAY-00:10 | 1.01 |
June | 0.144741E+10 | 1.01 | 558.41 | 01-JUN-00:05 | 1.01 |
July | 0.149565E+10 | 1.00 | 558.41 | 01-JUL-00:05 | 1.01 |
August | 0.149565E+10 | 1.00 | 558.41 | 01-AUG-00:05 | 1.00 |
September | 0.144741E+10 | 1.00 | 558.41 | 01-SEP-00:10 | 1.00 |
October | 0.149565E+10 | 1.01 | 558.41 | 01-OCT-00:10 | 1.01 |
November | 0.144741E+10 | 1.01 | 558.41 | 01-NOV-00:10 | 1.01 |
December | 0.149565E+10 | 1.01 | 558.41 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.176101E+11 | 1.01 | |||
Minimum of Months | 0.135091E+10 | 1.00 | 558.41 | 1.00 | |
Maximum of Months | 0.149565E+10 | 1.01 | 558.41 | 1.01 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 35127289.58 | 31930706.23 | 2934.50 | 02-JAN-06:03 | 2667.46 | 2667.46 | 46.94 | 5.52 |
February | 35665278.96 | 32419738.58 | 2250.12 | 13-FEB-06:03 | 2045.36 | 2045.36 | 39.00 | 3.30 |
March | 38231740.60 | 34752652.20 | 2658.67 | 27-MAR-05:03 | 2416.73 | 2416.73 | 40.50 | 4.43 |
April | 64789.54 | 58893.69 | 48.72 | 21-APR-06:10 | 44.29 | 44.29 | 35.85 | 0.05 |
May | 1.34 | 1.22 | 0.00 | 01-MAY-05:02 | 0.00 | 0.00 | 35.34 | 0.00 |
June | 0.54 | 0.49 | 0.00 | 21-JUN-05:03 | 0.00 | 0.00 | 35.34 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 35.34 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 35.34 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 35.34 | 0.00 |
October | 6266270.74 | 5696040.10 | 579.46 | 25-OCT-07:00 | 526.72 | 526.72 | 37.88 | 0.64 |
November | 18842918.24 | 17128212.68 | 2473.07 | 24-NOV-06:03 | 2248.02 | 2248.02 | 38.89 | 3.87 |
December | 0.153053E+09 | 0.139125E+09 | 2931.35 | 07-DEC-06:01 | 2664.60 | 2664.60 | 42.30 | 5.52 |
Annual Sum or Average | 0.287251E+09 | 0.261111E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.34 | 0.00 | |
Maximum of Months | 0.153053E+09 | 0.139125E+09 | 2934.50 | 2667.46 | 2667.46 | 46.94 | 5.52 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.174599E+09 | 0.158711E+09 | 1165.06 | 31-JAN-15:30 | 1059.04 | 1059.04 | 7.73 | 25.98 |
February | 60415084.12 | 54917311.46 | 847.90 | 23-FEB-14:20 | 770.74 | 770.74 | 6.71 | 22.54 |
March | 0.177666E+09 | 0.161498E+09 | 3722.76 | 17-MAR-14:50 | 3383.99 | 3383.99 | 8.51 | 42.65 |
April | 0.394355E+09 | 0.358469E+09 | 1489.64 | 25-APR-05:03 | 1354.09 | 1354.09 | 6.71 | 28.94 |
May | 0.513962E+09 | 0.467192E+09 | 1296.25 | 08-MAY-04:11 | 1178.29 | 1178.29 | 6.70 | 27.23 |
June | 0.108855E+10 | 0.989492E+09 | 6422.22 | 19-JUN-14:50 | 5837.80 | 5837.80 | 6.72 | 53.25 |
July | 0.146098E+10 | 0.132803E+10 | 10538.80 | 10-JUL-05:02 | 9579.77 | 9579.77 | 9.74 | 64.81 |
August | 0.170244E+10 | 0.154751E+10 | 10538.80 | 02-AUG-05:02 | 9579.77 | 9579.77 | 9.73 | 64.81 |
September | 0.140105E+10 | 0.127355E+10 | 10538.80 | 02-SEP-05:03 | 9579.77 | 9579.77 | 10.47 | 64.81 |
October | 0.658856E+09 | 0.598900E+09 | 10538.80 | 02-OCT-05:02 | 9579.77 | 9579.77 | 9.38 | 64.81 |
November | 0.271692E+09 | 0.246968E+09 | 9142.84 | 02-NOV-13:30 | 8310.85 | 8310.85 | 11.24 | 61.26 |
December | 78397442.05 | 71263274.82 | 1073.00 | 22-DEC-15:50 | 975.36 | 975.36 | 7.89 | 25.05 |
Annual Sum or Average | 0.798295E+10 | 0.725650E+10 | ||||||
Minimum of Months | 60415084.12 | 54917311.46 | 847.90 | 770.74 | 770.74 | 6.70 | 22.54 | |
Maximum of Months | 0.170244E+10 | 0.154751E+10 | 10538.80 | 9579.77 | 9579.77 | 11.24 | 64.81 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.407604E+10 | 0.370512E+10 | 3626.79 | 01-JAN-11:30 | 3296.75 | 3296.75 | 6.72 | 32.40 |
February | 0.269202E+10 | 0.244704E+10 | 3626.79 | 01-FEB-08:07 | 3296.75 | 3296.75 | 6.75 | 32.40 |
March | 0.457951E+10 | 0.416277E+10 | 3626.79 | 01-MAR-05:12 | 3296.75 | 3296.75 | 6.95 | 32.40 |
April | 0.773662E+10 | 0.703259E+10 | 3626.79 | 01-APR-04:12 | 3296.75 | 3296.75 | 7.09 | 32.40 |
May | 0.709286E+10 | 0.644741E+10 | 3626.79 | 01-MAY-00:10 | 3296.75 | 3296.75 | 6.82 | 32.40 |
June | 0.880982E+10 | 0.800813E+10 | 3626.79 | 01-JUN-00:05 | 3296.75 | 3296.75 | 6.93 | 32.40 |
July | 0.905150E+10 | 0.822781E+10 | 3626.79 | 01-JUL-00:05 | 3296.75 | 3296.75 | 7.68 | 32.40 |
August | 0.906305E+10 | 0.823831E+10 | 3626.79 | 01-AUG-00:05 | 3296.75 | 3296.75 | 8.46 | 32.40 |
September | 0.721418E+10 | 0.655769E+10 | 3626.79 | 01-SEP-00:10 | 3296.75 | 3296.75 | 6.93 | 32.40 |
October | 0.606438E+10 | 0.551253E+10 | 3626.79 | 01-OCT-00:15 | 3296.75 | 3296.75 | 7.04 | 32.40 |
November | 0.440473E+10 | 0.400390E+10 | 3626.79 | 01-NOV-04:12 | 3296.75 | 3296.75 | 9.05 | 32.40 |
December | 0.372304E+10 | 0.338424E+10 | 3626.79 | 01-DEC-06:02 | 3296.75 | 3296.75 | 6.76 | 32.40 |
Annual Sum or Average | 0.745077E+11 | 0.677275E+11 | ||||||
Minimum of Months | 0.269202E+10 | 0.244704E+10 | 3626.79 | 3296.75 | 3296.75 | 6.72 | 32.40 | |
Maximum of Months | 0.906305E+10 | 0.823831E+10 | 3626.79 | 3296.75 | 3296.75 | 9.05 | 32.40 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.175174E+09 | 0.159233E+09 | 3626.79 | 17-JAN-15:40 | 3296.75 | 3296.75 | 14.69 | 16.20 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.170822E+09 | 0.155277E+09 | 3626.79 | 10-MAR-15:00 | 3296.75 | 3296.75 | 14.48 | 16.20 |
April | 0.172671E+10 | 0.156958E+10 | 3626.79 | 03-APR-09:35 | 3296.75 | 3296.75 | 11.13 | 32.40 |
May | 0.266242E+10 | 0.242014E+10 | 3626.79 | 01-MAY-10:20 | 3296.75 | 3296.75 | 14.89 | 16.20 |
June | 0.386470E+10 | 0.351301E+10 | 3626.79 | 01-JUN-07:20 | 3296.75 | 3296.75 | 14.34 | 16.20 |
July | 0.335311E+10 | 0.304798E+10 | 3626.79 | 01-JUL-09:50 | 3296.75 | 3296.75 | 14.31 | 16.20 |
August | 0.348458E+10 | 0.316749E+10 | 3626.79 | 01-AUG-05:02 | 3296.75 | 3296.75 | 15.08 | 32.40 |
September | 0.270649E+10 | 0.246020E+10 | 3626.79 | 01-SEP-05:07 | 3296.75 | 3296.75 | 15.88 | 16.20 |
October | 0.127917E+10 | 0.116276E+10 | 3626.79 | 02-OCT-07:20 | 3296.75 | 3296.75 | 16.02 | 16.20 |
November | 0.245896E+09 | 0.223520E+09 | 3626.79 | 01-NOV-10:40 | 3296.75 | 3296.75 | 15.40 | 16.20 |
December | 17408570.16 | 15824390.27 | 3626.79 | 22-DEC-15:30 | 3296.75 | 3296.75 | 14.85 | 16.20 |
Annual Sum or Average | 0.196865E+11 | 0.178950E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 | |
Maximum of Months | 0.386470E+10 | 0.351301E+10 | 3626.79 | 3296.75 | 3296.75 | 16.02 | 32.40 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.909324E+10 | 0.826575E+10 | 3395.03 | 01-JAN-00:05 | 3086.08 | 3086.08 | 18.70 | 14.32 |
February | 0.821325E+10 | 0.746584E+10 | 3395.03 | 01-FEB-00:10 | 3086.08 | 3086.08 | 19.55 | 14.32 |
March | 0.909324E+10 | 0.826575E+10 | 3395.03 | 01-MAR-00:10 | 3086.08 | 3086.08 | 19.98 | 14.32 |
April | 0.879991E+10 | 0.799912E+10 | 3395.03 | 01-APR-00:10 | 3086.08 | 3086.08 | 23.08 | 14.32 |
May | 0.909324E+10 | 0.826575E+10 | 3395.03 | 01-MAY-00:10 | 3086.08 | 3086.08 | 20.52 | 14.32 |
June | 0.879991E+10 | 0.799912E+10 | 3395.03 | 01-JUN-00:05 | 3086.08 | 3086.08 | 35.30 | 14.32 |
July | 0.909324E+10 | 0.826575E+10 | 3395.03 | 01-JUL-00:05 | 3086.08 | 3086.08 | 42.42 | 14.32 |
August | 0.909324E+10 | 0.826575E+10 | 3395.03 | 01-AUG-00:05 | 3086.08 | 3086.08 | 48.18 | 14.32 |
September | 0.879991E+10 | 0.799912E+10 | 3395.03 | 01-SEP-00:10 | 3086.08 | 3086.08 | 32.55 | 14.32 |
October | 0.909324E+10 | 0.826575E+10 | 3395.03 | 01-OCT-00:10 | 3086.08 | 3086.08 | 33.63 | 14.32 |
November | 0.879991E+10 | 0.799912E+10 | 3395.03 | 01-NOV-00:10 | 3086.08 | 3086.08 | 21.88 | 14.32 |
December | 0.909324E+10 | 0.826575E+10 | 3395.03 | 01-DEC-00:10 | 3086.08 | 3086.08 | 20.58 | 14.32 |
Annual Sum or Average | 0.107066E+12 | 0.973226E+11 | ||||||
Minimum of Months | 0.821325E+10 | 0.746584E+10 | 3395.03 | 3086.08 | 3086.08 | 18.70 | 14.32 | |
Maximum of Months | 0.909324E+10 | 0.826575E+10 | 3395.03 | 3086.08 | 3086.08 | 48.18 | 14.32 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 55.69 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.73 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 55.87 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.25 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 56.54 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.30 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.23 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 56.70 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 56.79 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.48 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.77 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 57.10 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 55.69 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.30 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.159876E+11 | 0.145327E+11 | 27918.10 | 27-JAN-15:30 | 25377.55 | 25377.55 | 25.68 | 113.89 |
February | 0.103343E+11 | 0.939385E+10 | 13948.91 | 21-FEB-15:30 | 12679.56 | 12679.56 | 24.79 | 56.94 |
March | 0.178258E+11 | 0.162036E+11 | 27924.12 | 17-MAR-15:30 | 25383.03 | 25383.03 | 25.94 | 113.89 |
April | 0.351279E+11 | 0.319313E+11 | 27927.46 | 12-APR-14:30 | 25386.07 | 25386.07 | 26.08 | 113.89 |
May | 0.358311E+11 | 0.325704E+11 | 27927.86 | 16-MAY-14:30 | 25386.42 | 25386.42 | 26.10 | 113.89 |
June | 0.475719E+11 | 0.432428E+11 | 27991.51 | 17-JUN-15:30 | 25444.28 | 25444.28 | 28.85 | 113.89 |
July | 0.467727E+11 | 0.425164E+11 | 27991.51 | 13-JUL-10:05 | 25444.28 | 25444.28 | 29.18 | 113.89 |
August | 0.476697E+11 | 0.433318E+11 | 27991.51 | 01-AUG-05:04 | 25444.28 | 25444.28 | 29.24 | 113.89 |
September | 0.371201E+11 | 0.337422E+11 | 27991.51 | 01-SEP-09:10 | 25444.28 | 25444.28 | 28.82 | 113.89 |
October | 0.274538E+11 | 0.249555E+11 | 27991.51 | 03-OCT-09:00 | 25444.28 | 25444.28 | 28.96 | 113.89 |
November | 0.175672E+11 | 0.159686E+11 | 27920.48 | 01-NOV-12:50 | 25379.72 | 25379.72 | 25.78 | 113.89 |
December | 0.143196E+11 | 0.130165E+11 | 27916.20 | 22-DEC-16:00 | 25375.82 | 25375.82 | 25.60 | 113.89 |
Annual Sum or Average | 0.353582E+12 | 0.321406E+12 | ||||||
Minimum of Months | 0.103343E+11 | 0.939385E+10 | 13948.91 | 12679.56 | 12679.56 | 24.79 | 56.94 | |
Maximum of Months | 0.476697E+11 | 0.433318E+11 | 27991.51 | 25444.28 | 25444.28 | 29.24 | 113.89 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 33.28 | 33.28 | 2886.17 | 808979.61 | 02-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 27.42 | 27.42 | 3330.88 | 593950.10 | 13-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 33.14 | 33.14 | 2970.95 | 768533.37 | 27-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 36.26 | 36.26 | 4.97 | 9692.30 | 21-APR-06:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 35.34 | 35.34 | 0.00 | 0.61 | 01-MAY-05:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 35.34 | 35.34 | 0.00 | 0.54 | 21-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 35.34 | 35.34 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 35.34 | 35.34 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 35.34 | 35.34 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 35.34 | 35.34 | 513.28 | 135031.84 | 25-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26.10 | 26.10 | 1617.88 | 697355.66 | 24-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25.62 | 25.62 | 11670.07 | 915238.40 | 07-DEC-06:01 |
Annual Sum or Average | 0.00 | 1921.11 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.62 | 25.62 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 36.26 | 36.26 | 11670.07 | 915238.40 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 174523.31 | 1611526.39 | 31-JAN-15:05 | 12.64 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 67990.62 | 766158.57 | 21-FEB-15:30 | 12.35 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 166183.95 | 1565433.42 | 16-MAR-14:05 | 12.47 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 447649.28 | 1622840.76 | 03-APR-12:05 | 12.68 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 554095.09 | 1657143.40 | 25-MAY-12:05 | 12.81 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 752095.20 | 1924392.65 | 19-JUN-14:50 | 13.79 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 716852.01 | 2957029.41 | 14-JUL-05:03 | 17.61 | 9.08 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 735001.15 | 2273954.68 | 01-AUG-05:02 | 15.08 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 627045.71 | 2271421.49 | 12-SEP-05:03 | 15.08 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 356331.64 | 1727923.12 | 10-OCT-08:55 | 13.07 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 184454.27 | 1704096.38 | 02-NOV-14:05 | 12.98 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 104444.51 | 1337172.75 | 22-DEC-15:50 | 16.56 | 9.44 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 408962.88 | 0.00 | ||||||
Minimum of Months | 67990.62 | 766158.57 | 12.35 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 752095.20 | 2957029.41 | 17.61 | 9.44 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 172605.03 | 1437769.10 | 31-JAN-16:10 | 20.57 | 7.35 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 67039.05 | 765726.00 | 21-FEB-15:30 | 20.15 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 164790.57 | 1402622.78 | 17-MAR-14:50 | 14.56 | 8.57 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 442036.56 | 1649626.34 | 25-APR-05:03 | 20.33 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 548191.13 | 1723602.22 | 08-MAY-04:11 | 21.84 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 745544.81 | 2296469.95 | 09-JUN-05:02 | 21.96 | 8.17 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 713575.23 | 3559500.46 | 14-JUL-05:03 | 20.03 | 8.39 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 732363.22 | 3326058.56 | 28-AUG-05:03 | 18.97 | 12.82 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 624461.24 | 3218488.66 | 02-SEP-05:03 | 18.58 | 12.62 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 353697.50 | 3245117.49 | 03-OCT-04:12 | 18.67 | 12.67 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 183393.90 | 2312927.84 | 02-NOV-13:30 | 15.72 | 11.29 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 103223.76 | 1311712.10 | 22-DEC-15:50 | 19.22 | 9.90 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 405978.16 | 0.00 | ||||||
Minimum of Months | 67039.05 | 765726.00 | 14.56 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 745544.81 | 3559500.46 | 21.96 | 12.82 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 107519.01 | 861179.38 | 31-JAN-17:00 | 35.42 | 31.00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 66044.38 | 450317.18 | 18-FEB-14:05 | 27.33 | 23.65 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 294892.00 | 1295566.46 | 16-MAR-16:00 | 43.83 | 33.54 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 956838.58 | 1753037.35 | 14-APR-16:10 | 52.55 | 40.58 | 0.00 | 0.00 | 01-APR-00:10 |
May | 628601.87 | 1299445.08 | 31-MAY-16:00 | 43.90 | 39.18 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 1164572.57 | 1832979.62 | 28-JUN-16:00 | 54.06 | 45.84 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1406839.33 | 1965679.74 | 19-JUL-14:00 | 56.56 | 45.29 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1549124.87 | 2118031.03 | 27-AUG-14:05 | 59.41 | 46.22 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 734380.21 | 1379474.72 | 08-SEP-16:00 | 45.44 | 40.55 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 474994.03 | 1518168.65 | 01-OCT-14:00 | 48.09 | 40.51 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 295153.87 | 1304197.71 | 01-NOV-15:00 | 43.99 | 33.73 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 273399.75 | 1247943.21 | 25-DEC-16:00 | 42.91 | 31.32 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 666230.40 | 0.00 | ||||||
Minimum of Months | 66044.38 | 450317.18 | 27.33 | 23.65 | 0.00 | 0.00 | ||
Maximum of Months | 1549124.87 | 2118031.03 | 59.41 | 46.22 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.69 | 56.69 | 13394.82 | 44380.36 | 26-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.23 | 57.23 | 13350.03 | 44241.77 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.39 | 56.39 | 13472.40 | 43015.27 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.74 | 56.74 | 11814.45 | 39988.42 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.05 | 57.05 | 11167.44 | 36793.50 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 57.70 | 57.70 | 10551.60 | 33479.91 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.60 | 57.60 | 9444.32 | 31298.69 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 56.96 | 56.96 | 10336.21 | 32147.64 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.20 | 57.20 | 10383.40 | 34804.43 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.12 | 57.12 | 11269.58 | 38404.75 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.23 | 57.23 | 12383.45 | 41623.34 | 30-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.51 | 57.51 | 12738.54 | 43718.67 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 11683.04 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.39 | 56.39 | 9444.32 | 31298.69 | ||
Maximum of Months | 0.00 | 0.00 | 57.70 | 57.70 | 13472.40 | 44380.36 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 200113.36 | 2179183.04 | 27-JAN-15:30 | 25.68 | 21.10 | 946.06 | 96864.22 | 13-JAN-06:40 |
February | 79174.00 | 877050.92 | 21-FEB-15:30 | 24.79 | 21.10 | 974.18 | 80760.29 | 03-FEB-11:40 |
March | 189415.96 | 2301785.11 | 17-MAR-15:30 | 25.94 | 21.14 | 1264.73 | 120502.76 | 25-MAR-06:00 |
April | 572822.32 | 2369736.00 | 12-APR-14:30 | 26.08 | 21.41 | 3543.69 | 96208.89 | 23-APR-02:40 |
May | 738351.31 | 2377723.19 | 16-MAY-14:30 | 26.10 | 21.58 | 425.76 | 88139.56 | 01-MAY-01:30 |
June | 1060650.41 | 3903263.11 | 28-JUN-16:00 | 29.30 | 25.03 | 596.98 | 55390.32 | 07-JUN-03:10 |
July | 1338826.45 | 4725012.47 | 14-JUL-05:07 | 31.03 | 26.45 | 347.98 | 74690.05 | 02-JUL-00:50 |
August | 1363792.62 | 4596172.62 | 16-AUG-11:00 | 30.75 | 26.54 | 317.41 | 75228.37 | 25-AUG-02:50 |
September | 1078238.41 | 4758962.30 | 01-SEP-12:30 | 31.10 | 26.65 | 27.22 | 17668.36 | 20-SEP-00:47 |
October | 493859.55 | 3783872.84 | 03-OCT-10:05 | 29.05 | 25.05 | 912.71 | 103199.60 | 12-OCT-06:40 |
November | 220441.13 | 2227770.78 | 01-NOV-12:50 | 25.78 | 21.88 | 1181.42 | 79352.75 | 24-NOV-07:40 |
December | 120347.43 | 2140531.93 | 22-DEC-16:00 | 25.60 | 21.10 | 2192.17 | 126354.47 | 14-DEC-08:07 |
Annual Sum or Average | 624568.08 | 1058.54 | ||||||
Minimum of Months | 79174.00 | 877050.92 | 24.79 | 21.10 | 27.22 | 17668.36 | ||
Maximum of Months | 1363792.62 | 4758962.30 | 31.10 | 26.65 | 3543.69 | 126354.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.122868E+09 | 0.00 | 0.400784E+11 | 0.603735E+10 | 0.00 | 0.00 |
February | 0.179773E+09 | 0.00 | 0.111162E+11 | 0.547534E+10 | 0.00 | 0.00 |
March | 0.235300E+09 | 0.00 | 0.435185E+11 | 0.836378E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.112700E+12 | 0.132559E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.123596E+12 | 0.121160E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.166666E+12 | 0.150238E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.173992E+12 | 0.153905E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.193608E+12 | 0.182741E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.138211E+12 | 0.113392E+11 | 0.00 | 0.00 |
October | 24992123.31 | 0.00 | 0.850340E+11 | 0.942396E+10 | 0.00 | 0.00 |
November | 40805840.24 | 0.00 | 0.467024E+11 | 0.793705E+10 | 0.00 | 0.00 |
December | 0.761882E+09 | 0.00 | 0.297061E+11 | 0.706253E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136562E+10 | 0.00 | 0.116493E+13 | 0.129700E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.111162E+11 | 0.547534E+10 | 0.00 | 0.00 |
Maximum of Months | 0.761882E+09 | 0.00 | 0.193608E+12 | 0.182741E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.516787E+10 | 0.00 | 0.347440E+12 | 0.402678E+11 | 0.00 | 0.00 |
February | 0.542588E+10 | 0.00 | 0.140922E+12 | 0.334844E+11 | 0.00 | 0.00 |
March | 0.589359E+10 | 0.00 | 0.331063E+12 | 0.486298E+11 | 0.00 | 0.00 |
April | 5888775.72 | 0.00 | 0.851962E+12 | 0.842289E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.111208E+13 | 0.102508E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.148257E+13 | 0.125121E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.141927E+13 | 0.112045E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.144322E+13 | 0.116337E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.119826E+13 | 0.916202E+11 | 0.00 | 0.00 |
October | 0.946218E+09 | 0.00 | 0.703571E+12 | 0.640942E+11 | 0.00 | 0.00 |
November | 0.270234E+10 | 0.00 | 0.343287E+12 | 0.444005E+11 | 0.00 | 0.00 |
December | 0.240471E+11 | 0.00 | 0.214854E+12 | 0.351743E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.441889E+11 | 0.00 | 0.958849E+13 | 0.897911E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.140922E+12 | 0.334844E+11 | 0.00 | 0.00 |
Maximum of Months | 0.240471E+11 | 0.00 | 0.148257E+13 | 0.125121E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.253183E+10 | 0.00 | 0.283735E+11 | 0.344562E+10 | 0.00 | 0.00 |
February | 0.250580E+10 | 0.00 | 0.601059E+10 | 0.277004E+10 | 0.00 | 0.00 |
March | 0.189276E+10 | 0.00 | 0.300810E+11 | 0.402323E+10 | 0.00 | 0.00 |
April | 10392976.24 | 0.00 | 0.931120E+11 | 0.826065E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.123028E+12 | 0.103805E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.169010E+12 | 0.137669E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.161834E+12 | 0.122569E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.161121E+12 | 0.124808E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.130021E+12 | 0.938794E+10 | 0.00 | 0.00 |
October | 0.448999E+09 | 0.00 | 0.701805E+11 | 0.578477E+10 | 0.00 | 0.00 |
November | 0.149075E+10 | 0.00 | 0.288837E+11 | 0.365913E+10 | 0.00 | 0.00 |
December | 0.673213E+10 | 0.00 | 0.125874E+11 | 0.295655E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.156127E+11 | 0.00 | 0.101424E+13 | 0.891730E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.601059E+10 | 0.277004E+10 | 0.00 | 0.00 |
Maximum of Months | 0.673213E+10 | 0.00 | 0.169010E+12 | 0.137669E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 478.65 | 0.00 | 0.246559E+11 | 0.149887E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.433835E+10 | 0.129783E+11 | 0.00 | 0.00 |
March | 833.03 | 0.00 | 0.238974E+11 | 0.150256E+11 | 0.00 | 0.00 |
April | 1186.57 | 0.00 | 0.579223E+11 | 0.142034E+11 | 0.00 | 0.00 |
May | 424.75 | 0.00 | 0.711567E+11 | 0.149221E+11 | 0.00 | 0.00 |
June | 169.71 | 0.00 | 0.868675E+11 | 0.150063E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.935453E+11 | 0.157631E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.105143E+12 | 0.170677E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.888709E+11 | 0.159282E+11 | 0.00 | 0.00 |
October | 428.19 | 0.00 | 0.559904E+11 | 0.161748E+11 | 0.00 | 0.00 |
November | 603.71 | 0.00 | 0.298360E+11 | 0.153659E+11 | 0.00 | 0.00 |
December | 274.22 | 0.00 | 0.132625E+11 | 0.155604E+11 | 0.00 | 0.00 |
Annual Sum or Average | 4398.82 | 0.00 | 0.655486E+12 | 0.182984E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.433835E+10 | 0.129783E+11 | 0.00 | 0.00 |
Maximum of Months | 1186.57 | 0.00 | 0.105143E+12 | 0.170677E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.407614E+11 | 0.303228E+12 | 0.00 | 69.96 |
February | 0.00 | 0.00 | 0.154707E+11 | 0.191243E+12 | 0.00 | 34.42 |
March | 0.00 | 0.00 | 0.254582E+12 | 0.355963E+12 | 0.00 | 71.24 |
April | 0.00 | 0.00 | 0.901852E+12 | 0.585044E+12 | 0.00 | 94.76 |
May | 0.00 | 0.00 | 0.296911E+12 | 0.323015E+12 | 0.00 | 52.01 |
June | 0.00 | 0.00 | 0.713590E+12 | 0.361455E+12 | 0.00 | 24.63 |
July | 0.00 | 0.00 | 0.116534E+13 | 0.418761E+12 | 0.00 | 7.57 |
August | 0.00 | 0.00 | 0.140614E+13 | 0.488926E+12 | 0.00 | 16.01 |
September | 0.00 | 0.00 | 0.356602E+12 | 0.210134E+12 | 0.00 | 7.22 |
October | 0.00 | 0.00 | 0.334960E+12 | 0.344328E+12 | 0.00 | 58.41 |
November | 0.00 | 0.00 | 0.264949E+12 | 0.336522E+12 | 0.00 | 64.88 |
December | 0.00 | 0.00 | 0.267025E+12 | 0.430361E+12 | 0.00 | 97.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.601818E+13 | 0.434898E+13 | 0.00 | 598.80 |
Minimum of Months | 0.00 | 0.00 | 0.154707E+11 | 0.191243E+12 | 0.00 | 7.22 |
Maximum of Months | 0.00 | 0.00 | 0.140614E+13 | 0.585044E+12 | 0.00 | 97.68 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.686188E+10 | 0.291517E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.114847E+11 | 0.346173E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.193869E+11 | 0.517053E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.257388E+11 | 0.722841E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.843694E+10 | 0.366084E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.153299E+11 | 0.561006E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.224297E+11 | 0.725163E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.283921E+11 | 0.852926E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.829114E+10 | 0.349208E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.141431E+11 | 0.455659E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.189842E+11 | 0.505141E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.252695E+11 | 0.617457E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.204749E+12 | 0.631023E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.686188E+10 | 0.291517E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.283921E+11 | 0.852926E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.541800E+11 | 0.257301E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.990755E+11 | 0.312848E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.177499E+12 | 0.481347E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.243995E+12 | 0.688118E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.786349E+11 | 0.345374E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.146067E+12 | 0.535004E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.213365E+12 | 0.690606E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.268050E+12 | 0.809465E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.769154E+11 | 0.328505E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.129788E+12 | 0.425548E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.172491E+12 | 0.467850E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.227974E+12 | 0.568543E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188804E+13 | 0.591051E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.541800E+11 | 0.257301E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.268050E+12 | 0.809465E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.429081E+10 | 0.239473E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.872032E+10 | 0.295926E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.170134E+11 | 0.473474E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245262E+11 | 0.697109E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.796127E+10 | 0.352181E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.148737E+11 | 0.546091E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.216291E+11 | 0.702298E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.271138E+11 | 0.822339E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.783109E+10 | 0.335652E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125805E+11 | 0.422780E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.162832E+11 | 0.455775E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.212221E+11 | 0.547343E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184045E+12 | 0.589044E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.429081E+10 | 0.239473E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.271138E+11 | 0.822339E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.603735E+10 | 0.400784E+11 | 0.122868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.547534E+10 | 0.111162E+11 | 0.179773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.836378E+10 | 0.435185E+11 | 0.235300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132559E+11 | 0.112700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121160E+11 | 0.123596E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150238E+11 | 0.166666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153905E+11 | 0.173992E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182741E+11 | 0.193608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113392E+11 | 0.138211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.942396E+10 | 0.850340E+11 | 24992123.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.793705E+10 | 0.467024E+11 | 40805840.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.706253E+10 | 0.297061E+11 | 0.761882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129700E+12 | 0.116493E+13 | 0.136562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.547534E+10 | 0.111162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182741E+11 | 0.193608E+12 | 0.761882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.402678E+11 | 0.347440E+12 | 0.516787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334844E+11 | 0.140922E+12 | 0.542588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.486298E+11 | 0.331063E+12 | 0.589359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.842289E+11 | 0.851962E+12 | 5888775.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102508E+12 | 0.111208E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125121E+12 | 0.148257E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112045E+12 | 0.141927E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116337E+12 | 0.144322E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.916202E+11 | 0.119826E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.640942E+11 | 0.703571E+12 | 0.946218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444005E+11 | 0.343287E+12 | 0.270234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351743E+11 | 0.214854E+12 | 0.240471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.897911E+12 | 0.958849E+13 | 0.441889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.334844E+11 | 0.140922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125121E+12 | 0.148257E+13 | 0.240471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.344562E+10 | 0.283735E+11 | 0.253183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277004E+10 | 0.601059E+10 | 0.250580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.402323E+10 | 0.300810E+11 | 0.189276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.826065E+10 | 0.931120E+11 | 10392976.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103805E+11 | 0.123028E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137669E+11 | 0.169010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122569E+11 | 0.161834E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124808E+11 | 0.161121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.938794E+10 | 0.130021E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.578477E+10 | 0.701805E+11 | 0.448999E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365913E+10 | 0.288837E+11 | 0.149075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295655E+10 | 0.125874E+11 | 0.673213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.891730E+11 | 0.101424E+13 | 0.156127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277004E+10 | 0.601059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137669E+11 | 0.169010E+12 | 0.673213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149887E+11 | 0.246559E+11 | 478.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129783E+11 | 0.433835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150256E+11 | 0.238974E+11 | 833.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142034E+11 | 0.579223E+11 | 1186.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149221E+11 | 0.711567E+11 | 424.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150063E+11 | 0.868675E+11 | 169.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157631E+11 | 0.935453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170677E+11 | 0.105143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159282E+11 | 0.888709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161748E+11 | 0.559904E+11 | 428.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153659E+11 | 0.298360E+11 | 603.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155604E+11 | 0.132625E+11 | 274.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182984E+12 | 0.655486E+12 | 4398.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129783E+11 | 0.433835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170677E+11 | 0.105143E+12 | 1186.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.103419E+12 | 0.290146E+11 | 0.00 | 0.00 | 0.00 | 0.187219E+12 | 0.00 | 0.00 |
February | 0.934110E+11 | 0.101614E+11 | 0.00 | 0.00 | 0.00 | 0.921080E+11 | 0.00 | 0.00 |
March | 0.103419E+12 | 0.193547E+12 | 0.00 | 0.00 | 0.00 | 0.190651E+12 | 0.00 | 0.00 |
April | 0.100083E+12 | 0.671619E+12 | 0.00 | 0.00 | 0.00 | 0.253587E+12 | 0.00 | 0.00 |
May | 0.103419E+12 | 0.217138E+12 | 0.00 | 0.00 | 0.00 | 0.139196E+12 | 0.00 | 0.00 |
June | 0.100083E+12 | 0.518437E+12 | 0.00 | 0.00 | 0.00 | 0.659214E+11 | 0.00 | 0.00 |
July | 0.103419E+12 | 0.870333E+12 | 0.00 | 0.00 | 0.00 | 0.202462E+11 | 0.00 | 0.00 |
August | 0.103419E+12 | 0.106368E+13 | 0.00 | 0.00 | 0.00 | 0.428543E+11 | 0.00 | 0.00 |
September | 0.100083E+12 | 0.265972E+12 | 0.00 | 0.00 | 0.00 | 0.193344E+11 | 0.00 | 0.00 |
October | 0.103419E+12 | 0.251066E+12 | 0.00 | 0.00 | 0.00 | 0.156310E+12 | 0.00 | 0.00 |
November | 0.100083E+12 | 0.202931E+12 | 0.00 | 0.00 | 0.00 | 0.173639E+12 | 0.00 | 0.00 |
December | 0.103419E+12 | 0.202669E+12 | 0.00 | 0.00 | 0.00 | 0.261408E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.121768E+13 | 0.449656E+13 | 0.00 | 0.00 | 0.00 | 0.160247E+13 | 0.00 | 0.00 |
Minimum of Months | 0.934110E+11 | 0.101614E+11 | 0.00 | 0.00 | 0.00 | 0.193344E+11 | 0.00 | 0.00 |
Maximum of Months | 0.103419E+12 | 0.106368E+13 | 0.00 | 0.00 | 0.00 | 0.261408E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153092E+10 | 0.547763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138276E+10 | 0.940569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153092E+10 | 0.157473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148153E+10 | 0.199920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153092E+10 | 0.630701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148153E+10 | 0.112014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153092E+10 | 0.167090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153092E+10 | 0.213937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148153E+10 | 0.628059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153092E+10 | 0.111175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148153E+10 | 0.154143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153092E+10 | 0.206259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180253E+11 | 0.159672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138276E+10 | 0.547763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153092E+10 | 0.213937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146150E+11 | 0.430650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132007E+11 | 0.809914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146150E+11 | 0.143980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141436E+11 | 0.189327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146150E+11 | 0.587126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141436E+11 | 0.106710E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146150E+11 | 0.158919E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146150E+11 | 0.201718E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141436E+11 | 0.582084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146150E+11 | 0.101848E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141436E+11 | 0.139850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146150E+11 | 0.185735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172080E+12 | 0.146907E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132007E+11 | 0.430650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146150E+11 | 0.201718E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149565E+10 | 0.339174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135091E+10 | 0.711197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149565E+10 | 0.137743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144741E+10 | 0.190025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149565E+10 | 0.593512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144741E+10 | 0.108602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149565E+10 | 0.161018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149565E+10 | 0.203861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144741E+10 | 0.592197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149565E+10 | 0.984835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144741E+10 | 0.131729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149565E+10 | 0.172443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176101E+11 | 0.142751E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135091E+10 | 0.339174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149565E+10 | 0.203861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.603735E+10 | 0.122868E+09 | 0.400784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.547534E+10 | 0.179773E+09 | 0.111162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.836378E+10 | 0.235300E+09 | 0.435185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132559E+11 | 0.00 | 0.112700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121160E+11 | 0.00 | 0.123596E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150238E+11 | 0.00 | 0.166666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153905E+11 | 0.00 | 0.173992E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182741E+11 | 0.00 | 0.193608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.113392E+11 | 0.00 | 0.138211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.942396E+10 | 24992123.31 | 0.850340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.793705E+10 | 40805840.24 | 0.467024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.706253E+10 | 0.761882E+09 | 0.297061E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129700E+12 | 0.136562E+10 | 0.116493E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.547534E+10 | 0.00 | 0.111162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182741E+11 | 0.761882E+09 | 0.193608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.402678E+11 | 0.516787E+10 | 0.347440E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334844E+11 | 0.542588E+10 | 0.140922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.486298E+11 | 0.589359E+10 | 0.331063E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.842289E+11 | 5888775.72 | 0.851962E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102508E+12 | 0.00 | 0.111208E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.125121E+12 | 0.00 | 0.148257E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112045E+12 | 0.00 | 0.141927E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116337E+12 | 0.00 | 0.144322E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.916202E+11 | 0.00 | 0.119826E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.640942E+11 | 0.946218E+09 | 0.703571E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.444005E+11 | 0.270234E+10 | 0.343287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.351743E+11 | 0.240471E+11 | 0.214854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.897911E+12 | 0.441889E+11 | 0.958849E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.334844E+11 | 0.00 | 0.140922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.125121E+12 | 0.240471E+11 | 0.148257E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.344562E+10 | 0.253183E+10 | 0.283735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277004E+10 | 0.250580E+10 | 0.601059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.402323E+10 | 0.189276E+10 | 0.300810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.826065E+10 | 10392976.24 | 0.931120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103805E+11 | 0.00 | 0.123028E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137669E+11 | 0.00 | 0.169010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.122569E+11 | 0.00 | 0.161834E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124808E+11 | 0.00 | 0.161121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.938794E+10 | 0.00 | 0.130021E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.578477E+10 | 0.448999E+09 | 0.701805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.365913E+10 | 0.149075E+10 | 0.288837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295655E+10 | 0.673213E+10 | 0.125874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.891730E+11 | 0.156127E+11 | 0.101424E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.277004E+10 | 0.00 | 0.601059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137669E+11 | 0.673213E+10 | 0.169010E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149887E+11 | 478.65 | 0.246559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129783E+11 | 0.00 | 0.433835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150256E+11 | 833.03 | 0.238974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142034E+11 | 1186.57 | 0.579223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149221E+11 | 424.75 | 0.711567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150063E+11 | 169.71 | 0.868675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157631E+11 | 0.00 | 0.935453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170677E+11 | 0.00 | 0.105143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159282E+11 | 0.00 | 0.888709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161748E+11 | 428.19 | 0.559904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153659E+11 | 603.71 | 0.298360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155604E+11 | 274.22 | 0.132625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182984E+12 | 4398.82 | 0.655486E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129783E+11 | 0.00 | 0.433835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170677E+11 | 1186.57 | 0.105143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.103419E+12 | 0.00 | 0.407614E+11 | 0.00 | 0.117469E+11 | 0.00 | 0.00 | 0.00 | 0.188062E+12 | 0.00 | 0.00 | 0.00 |
February | 0.934110E+11 | 0.00 | 0.154707E+11 | 0.00 | 0.530922E+10 | 0.00 | 0.00 | 0.00 | 0.925226E+11 | 0.00 | 0.00 | 0.00 |
March | 0.103419E+12 | 0.00 | 0.254582E+12 | 0.00 | 0.610346E+11 | 0.00 | 0.00 | 0.00 | 0.191509E+12 | 0.00 | 0.00 | 0.00 |
April | 0.100083E+12 | 0.00 | 0.901852E+12 | 0.00 | 0.230233E+12 | 0.00 | 0.00 | 0.00 | 0.254728E+12 | 0.00 | 0.00 | 0.00 |
May | 0.103419E+12 | 0.00 | 0.296911E+12 | 0.00 | 0.797727E+11 | 0.00 | 0.00 | 0.00 | 0.139823E+12 | 0.00 | 0.00 | 0.00 |
June | 0.100083E+12 | 0.00 | 0.713590E+12 | 0.00 | 0.195153E+12 | 0.00 | 0.00 | 0.00 | 0.662181E+11 | 0.00 | 0.00 | 0.00 |
July | 0.103419E+12 | 0.00 | 0.116534E+13 | 0.00 | 0.295004E+12 | 0.00 | 0.00 | 0.00 | 0.203374E+11 | 0.00 | 0.00 | 0.00 |
August | 0.103419E+12 | 0.00 | 0.140614E+13 | 0.00 | 0.342460E+12 | 0.00 | 0.00 | 0.00 | 0.430472E+11 | 0.00 | 0.00 | 0.00 |
September | 0.100083E+12 | 0.00 | 0.356602E+12 | 0.00 | 0.906294E+11 | 0.00 | 0.00 | 0.00 | 0.194214E+11 | 0.00 | 0.00 | 0.00 |
October | 0.103419E+12 | 0.00 | 0.334960E+12 | 0.00 | 0.838948E+11 | 0.00 | 0.00 | 0.00 | 0.157014E+12 | 0.00 | 0.00 | 0.00 |
November | 0.100083E+12 | 0.00 | 0.264949E+12 | 0.00 | 0.620182E+11 | 0.00 | 0.00 | 0.00 | 0.174420E+12 | 0.00 | 0.00 | 0.00 |
December | 0.103419E+12 | 0.00 | 0.267025E+12 | 0.00 | 0.643566E+11 | 0.00 | 0.00 | 0.00 | 0.262585E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121768E+13 | 0.00 | 0.601818E+13 | 0.00 | 0.152161E+13 | 0.00 | 0.00 | 0.00 | 0.160969E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.934110E+11 | 0.00 | 0.154707E+11 | 0.00 | 0.530922E+10 | 0.00 | 0.00 | 0.00 | 0.194214E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103419E+12 | 0.00 | 0.140614E+13 | 0.00 | 0.342460E+12 | 0.00 | 0.00 | 0.00 | 0.262585E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153092E+10 | 0.00 | 0.686188E+10 | 0.00 | 0.138425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138276E+10 | 0.00 | 0.114847E+11 | 0.00 | 0.207897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153092E+10 | 0.00 | 0.193869E+11 | 0.00 | 0.363961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148153E+10 | 0.00 | 0.257388E+11 | 0.00 | 0.574688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153092E+10 | 0.00 | 0.843694E+10 | 0.00 | 0.212992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148153E+10 | 0.00 | 0.153299E+11 | 0.00 | 0.412853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153092E+10 | 0.00 | 0.224297E+11 | 0.00 | 0.572072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153092E+10 | 0.00 | 0.283921E+11 | 0.00 | 0.699834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148153E+10 | 0.00 | 0.829114E+10 | 0.00 | 0.201055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153092E+10 | 0.00 | 0.141431E+11 | 0.00 | 0.302567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148153E+10 | 0.00 | 0.189842E+11 | 0.00 | 0.356988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153092E+10 | 0.00 | 0.252695E+11 | 0.00 | 0.464366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180253E+11 | 0.00 | 0.204749E+12 | 0.00 | 0.450770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138276E+10 | 0.00 | 0.686188E+10 | 0.00 | 0.138425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153092E+10 | 0.00 | 0.283921E+11 | 0.00 | 0.699834E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146150E+11 | 0.00 | 0.541800E+11 | 0.00 | 0.111150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132007E+11 | 0.00 | 0.990755E+11 | 0.00 | 0.180841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146150E+11 | 0.00 | 0.177499E+12 | 0.00 | 0.335196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141436E+11 | 0.00 | 0.243995E+12 | 0.00 | 0.546682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146150E+11 | 0.00 | 0.786349E+11 | 0.00 | 0.199223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141436E+11 | 0.00 | 0.146067E+12 | 0.00 | 0.393568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146150E+11 | 0.00 | 0.213365E+12 | 0.00 | 0.544456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146150E+11 | 0.00 | 0.268050E+12 | 0.00 | 0.663315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141436E+11 | 0.00 | 0.769154E+11 | 0.00 | 0.187069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146150E+11 | 0.00 | 0.129788E+12 | 0.00 | 0.279397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141436E+11 | 0.00 | 0.172491E+12 | 0.00 | 0.326414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146150E+11 | 0.00 | 0.227974E+12 | 0.00 | 0.422393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172080E+12 | 0.00 | 0.188804E+13 | 0.00 | 0.418970E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132007E+11 | 0.00 | 0.541800E+11 | 0.00 | 0.111150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146150E+11 | 0.00 | 0.268050E+12 | 0.00 | 0.663315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149565E+10 | 0.00 | 0.429081E+10 | 0.00 | 0.899074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135091E+10 | 0.00 | 0.872032E+10 | 0.00 | 0.160835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149565E+10 | 0.00 | 0.170134E+11 | 0.00 | 0.323909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144741E+10 | 0.00 | 0.245262E+11 | 0.00 | 0.552368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149565E+10 | 0.00 | 0.796127E+10 | 0.00 | 0.202615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144741E+10 | 0.00 | 0.148737E+11 | 0.00 | 0.401351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149565E+10 | 0.00 | 0.216291E+11 | 0.00 | 0.552733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149565E+10 | 0.00 | 0.271138E+11 | 0.00 | 0.672774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144741E+10 | 0.00 | 0.783109E+10 | 0.00 | 0.190911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149565E+10 | 0.00 | 0.125805E+11 | 0.00 | 0.273215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144741E+10 | 0.00 | 0.162832E+11 | 0.00 | 0.311035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149565E+10 | 0.00 | 0.212221E+11 | 0.00 | 0.397778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176101E+11 | 0.00 | 0.184045E+12 | 0.00 | 0.412943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135091E+10 | 0.00 | 0.429081E+10 | 0.00 | 0.899074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149565E+10 | 0.00 | 0.271138E+11 | 0.00 | 0.672774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.220983E+09 | 24002533.54 | 0.00 | 0.124791E+09 | 156540.77 | 0.00 | 0.505501E+11 | 0.00 | 1.25 |
February | 0.232059E+09 | 0.00 | 0.00 | 0.102118E+09 | 0.00 | 0.00 | 0.591670E+11 | 0.00 | 1.21 |
March | 0.150664E+09 | 35228637.48 | 0.00 | 0.113709E+09 | 790668.42 | 0.00 | 0.508285E+11 | 0.00 | 1.30 |
April | 52901413.63 | 0.241461E+10 | 0.00 | 74872991.54 | 0.118060E+09 | 0.00 | 0.181533E+11 | 0.00 | 0.81 |
May | 52708655.25 | 0.509023E+10 | 0.00 | 46608249.86 | 0.106748E+09 | 0.00 | 0.914489E+10 | 0.00 | 0.64 |
June | 43974274.76 | 0.129442E+11 | 0.00 | 21069283.26 | 0.191881E+09 | 0.00 | 0.288779E+10 | 0.00 | 0.53 |
July | 18486693.15 | 0.129331E+11 | 0.00 | 12904321.03 | 0.236092E+09 | 0.00 | 0.127476E+10 | 0.00 | 0.44 |
August | 17502754.38 | 0.129957E+11 | 0.00 | 23198958.94 | 0.174444E+09 | 0.00 | 0.179435E+10 | 0.00 | 0.56 |
September | 43683636.13 | 0.929672E+10 | 0.00 | 38840334.68 | 0.187109E+09 | 0.00 | 0.479524E+10 | 0.00 | 0.68 |
October | 0.201067E+09 | 0.207474E+10 | 0.00 | 0.102723E+09 | 27738156.68 | 0.00 | 0.323680E+11 | 0.00 | 1.09 |
November | 0.323169E+09 | 0.224034E+09 | 0.00 | 0.137685E+09 | 0.00 | 0.00 | 0.530608E+11 | 0.00 | 1.34 |
December | 0.362642E+09 | 1283338.95 | 0.00 | 0.143361E+09 | 0.00 | 0.00 | 0.670328E+11 | 0.00 | 1.25 |
Annual Sum or Average | 0.171984E+10 | 0.580339E+11 | 0.00 | 0.941881E+09 | 0.104302E+10 | 0.00 | 0.351058E+12 | 0.00 | 0.92 |
Minimum of Months | 17502754.38 | 0.00 | 0.00 | 12904321.03 | 0.00 | 0.00 | 0.127476E+10 | 0.00 | 0.44 |
Maximum of Months | 0.362642E+09 | 0.129957E+11 | 0.00 | 0.143361E+09 | 0.236092E+09 | 0.00 | 0.670328E+11 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183431E+10 | 1782383.36 | 0.00 | 92073331.82 | 23029253.20 | 0.00 | 0.324195E+11 | 0.00 | 0.77 |
February | 0.173650E+10 | 0.00 | 0.00 | 83433907.57 | 0.00 | 0.00 | 0.427711E+11 | 0.00 | 0.83 |
March | 0.213636E+10 | 12031330.70 | 0.00 | 0.103993E+09 | 591606.80 | 0.00 | 0.392303E+11 | 0.00 | 0.93 |
April | 0.622888E+10 | 0.114667E+10 | 0.00 | 68550532.65 | 0.211449E+09 | 0.00 | 0.142902E+11 | 0.00 | 0.78 |
May | 0.106999E+10 | 0.255820E+10 | 0.00 | 43099227.92 | 0.166959E+09 | 0.00 | 0.643194E+10 | 0.00 | 0.48 |
June | 0.161097E+10 | 0.774302E+10 | 0.00 | 11687928.85 | 0.343579E+09 | 0.00 | 0.139713E+10 | 0.00 | 0.40 |
July | 0.857948E+09 | 0.953260E+10 | 0.00 | 5993583.11 | 0.151236E+10 | 0.00 | 0.515754E+09 | 0.00 | 0.37 |
August | 0.114529E+10 | 0.965307E+10 | 0.00 | 14870816.51 | 0.683473E+09 | 0.00 | 0.950268E+09 | 0.00 | 0.47 |
September | 0.260123E+09 | 0.604276E+10 | 0.00 | 28984673.57 | 0.102271E+10 | 0.00 | 0.285262E+10 | 0.00 | 0.47 |
October | 0.168156E+10 | 0.127046E+10 | 0.00 | 76951330.94 | 0.181192E+09 | 0.00 | 0.226524E+11 | 0.00 | 0.75 |
November | 0.228384E+10 | 70779119.82 | 0.00 | 0.105974E+09 | 30222093.20 | 0.00 | 0.362207E+11 | 0.00 | 0.91 |
December | 0.235513E+10 | 93477.48 | 0.00 | 0.108478E+09 | 1482988.63 | 0.00 | 0.439222E+11 | 0.00 | 0.79 |
Annual Sum or Average | 0.232009E+11 | 0.380315E+11 | 0.00 | 0.744090E+09 | 0.417704E+10 | 0.00 | 0.243654E+12 | 0.00 | 0.66 |
Minimum of Months | 0.260123E+09 | 0.00 | 0.00 | 5993583.11 | 0.00 | 0.00 | 0.515754E+09 | 0.00 | 0.37 |
Maximum of Months | 0.622888E+10 | 0.965307E+10 | 0.00 | 0.108478E+09 | 0.151236E+10 | 0.00 | 0.439222E+11 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245816E+11 | 0.00 | 0.00 | 0.590319E+09 | 0.311935E+09 | 0.00 | 0.200028E+12 | 0.00 | 0.50 |
February | 0.293861E+11 | 0.00 | 0.00 | 0.495785E+09 | 0.00 | 0.00 | 0.246685E+12 | 0.00 | 0.50 |
March | 0.176649E+11 | 0.106212E+09 | 0.00 | 0.671839E+09 | 16971447.19 | 0.00 | 0.258804E+12 | 0.00 | 0.63 |
April | 0.107602E+11 | 0.121491E+11 | 0.00 | 0.517643E+09 | 0.188876E+10 | 0.00 | 0.103902E+12 | 0.00 | 0.51 |
May | 0.512501E+10 | 0.267537E+11 | 0.00 | 0.348543E+09 | 0.144933E+10 | 0.00 | 0.507228E+11 | 0.00 | 0.42 |
June | 0.491090E+10 | 0.780233E+11 | 0.00 | 0.111626E+09 | 0.273509E+10 | 0.00 | 0.135883E+11 | 0.00 | 0.33 |
July | 0.222402E+10 | 0.896935E+11 | 0.00 | 42544580.24 | 0.394538E+10 | 0.00 | 0.442954E+10 | 0.00 | 0.29 |
August | 0.248695E+10 | 0.842890E+11 | 0.00 | 96828323.63 | 0.321725E+10 | 0.00 | 0.819770E+10 | 0.00 | 0.34 |
September | 0.153870E+10 | 0.579906E+11 | 0.00 | 0.227381E+09 | 0.522622E+10 | 0.00 | 0.227708E+11 | 0.00 | 0.39 |
October | 0.818580E+10 | 0.130951E+11 | 0.00 | 0.546093E+09 | 0.623790E+09 | 0.00 | 0.154787E+12 | 0.00 | 0.54 |
November | 0.219631E+11 | 0.431281E+09 | 0.00 | 0.639127E+09 | 0.259682E+09 | 0.00 | 0.223057E+12 | 0.00 | 0.58 |
December | 0.457807E+11 | 1695261.66 | 0.00 | 0.490153E+09 | 3749254.34 | 0.00 | 0.219642E+12 | 0.00 | 0.45 |
Annual Sum or Average | 0.174608E+12 | 0.362534E+12 | 0.00 | 0.477788E+10 | 0.196782E+11 | 0.00 | 0.150661E+13 | 0.00 | 0.46 |
Minimum of Months | 0.153870E+10 | 0.00 | 0.00 | 42544580.24 | 0.00 | 0.00 | 0.442954E+10 | 0.00 | 0.29 |
Maximum of Months | 0.457807E+11 | 0.896935E+11 | 0.00 | 0.671839E+09 | 0.522622E+10 | 0.00 | 0.258804E+12 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.745565E+10 | 0.00 | 0.00 | 28711998.41 | 19676442.91 | 93828697.35 | 0.107054E+11 | 0.00 | 0.48 |
February | 0.898692E+10 | 0.00 | 0.00 | 22843870.35 | 0.00 | 34657356.44 | 0.158307E+11 | 0.00 | 0.49 |
March | 0.612993E+10 | 3152874.44 | 0.00 | 42464186.08 | 441369.36 | 1057488.97 | 0.166764E+11 | 0.00 | 0.56 |
April | 0.162202E+10 | 0.798270E+09 | 0.00 | 51089061.10 | 0.170561E+09 | 0.00 | 0.745544E+10 | 0.00 | 0.48 |
May | 0.468025E+09 | 0.198671E+10 | 0.00 | 39148618.61 | 0.123778E+09 | 0.00 | 0.369698E+10 | 0.00 | 0.39 |
June | 0.488615E+09 | 0.690550E+10 | 0.00 | 10104040.56 | 0.227146E+09 | 0.00 | 0.102774E+10 | 0.00 | 0.32 |
July | 0.251705E+09 | 0.824241E+10 | 0.00 | 4125871.89 | 0.411358E+09 | 0.00 | 0.324091E+09 | 0.00 | 0.29 |
August | 0.220716E+09 | 0.760748E+10 | 0.00 | 8775386.39 | 0.333131E+09 | 0.00 | 0.603770E+09 | 0.00 | 0.34 |
September | 0.184977E+09 | 0.509869E+10 | 0.00 | 23452917.63 | 0.608759E+09 | 0.00 | 0.173635E+10 | 0.00 | 0.38 |
October | 0.245321E+10 | 0.105093E+10 | 0.00 | 40214905.49 | 70715898.63 | 0.00 | 0.103396E+11 | 0.00 | 0.48 |
November | 0.642789E+10 | 41454854.80 | 0.00 | 36880070.87 | 18576517.77 | 1273054.75 | 0.136741E+11 | 0.00 | 0.52 |
December | 0.127573E+11 | 0.00 | 0.00 | 16033478.36 | 3469319.79 | 94683909.94 | 0.903521E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.474470E+11 | 0.317346E+11 | 0.00 | 0.323844E+09 | 0.198761E+10 | 0.225501E+09 | 0.911057E+11 | 0.00 | 0.43 |
Minimum of Months | 0.184977E+09 | 0.00 | 0.00 | 4125871.89 | 0.00 | 0.00 | 0.324091E+09 | 0.00 | 0.29 |
Maximum of Months | 0.127573E+11 | 0.824241E+10 | 0.00 | 51089061.10 | 0.608759E+09 | 94683909.94 | 0.166764E+11 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139994E+10 | 208036.31 | 0.00 | 4466296.91 | 2895152.33 | 0.00 | 0.133794E+10 | 0.00 | 0.52 |
February | 0.146387E+10 | 0.00 | 0.00 | 3704131.91 | 0.00 | 0.00 | 0.220366E+10 | 0.00 | 0.56 |
March | 0.107029E+10 | 1837553.77 | 0.00 | 7308703.75 | 74318.31 | 0.00 | 0.257740E+10 | 0.00 | 0.72 |
April | 0.954716E+09 | 0.218271E+09 | 0.00 | 7624848.62 | 26562470.96 | 0.00 | 0.124301E+10 | 0.00 | 0.78 |
May | 0.199179E+09 | 0.559110E+09 | 0.00 | 5096650.92 | 21417080.58 | 0.00 | 0.708630E+09 | 0.00 | 0.60 |
June | 0.199409E+09 | 0.199707E+10 | 0.00 | 1945565.45 | 37252330.49 | 0.00 | 0.228186E+09 | 0.00 | 0.65 |
July | 0.109306E+09 | 0.210232E+10 | 0.00 | 935976.75 | 0.177093E+09 | 0.00 | 77571139.65 | 0.00 | 0.55 |
August | 0.144209E+09 | 0.190848E+10 | 0.00 | 1944359.65 | 80947059.12 | 0.00 | 0.127986E+09 | 0.00 | 0.63 |
September | 48514495.54 | 0.120316E+10 | 0.00 | 3528019.76 | 0.123603E+09 | 0.00 | 0.312139E+09 | 0.00 | 0.58 |
October | 0.598772E+09 | 0.221703E+09 | 0.00 | 5922131.08 | 22986984.87 | 0.00 | 0.150857E+10 | 0.00 | 0.63 |
November | 0.106384E+10 | 3345330.76 | 0.00 | 6714905.48 | 6277295.66 | 0.00 | 0.211293E+10 | 0.00 | 0.65 |
December | 0.166493E+10 | 10709.14 | 0.00 | 3974229.51 | 186294.69 | 0.00 | 0.171080E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.891697E+10 | 0.821552E+10 | 0.00 | 53165819.79 | 0.499294E+09 | 0.00 | 0.141488E+11 | 0.00 | 0.61 |
Minimum of Months | 48514495.54 | 0.00 | 0.00 | 935976.75 | 0.00 | 0.00 | 77571139.65 | 0.00 | 0.49 |
Maximum of Months | 0.166493E+10 | 0.210232E+10 | 0.00 | 7624848.62 | 0.177093E+09 | 0.00 | 0.257740E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.656287E+09 | 184207.93 | 0.00 | 6841481.99 | 1858621.63 | 0.00 | 0.236928E+10 | 0.00 | 0.84 |
February | 0.761756E+09 | 0.00 | 0.00 | 5443434.56 | 0.00 | 0.00 | 0.285845E+10 | 0.00 | 0.81 |
March | 0.585811E+09 | 1279185.28 | 0.00 | 8289876.80 | 47746.80 | 0.00 | 0.309792E+10 | 0.00 | 1.06 |
April | 0.580502E+09 | 0.168726E+09 | 0.00 | 10231620.75 | 17011756.35 | 0.00 | 0.182549E+10 | 0.00 | 1.26 |
May | 0.114711E+09 | 0.447365E+09 | 0.00 | 7502530.98 | 13224555.73 | 0.00 | 0.979658E+09 | 0.00 | 1.03 |
June | 0.128839E+09 | 0.160218E+10 | 0.00 | 1872329.61 | 22862197.70 | 0.00 | 0.195523E+09 | 0.00 | 0.87 |
July | 68862701.21 | 0.171404E+10 | 0.00 | 942594.52 | 0.118679E+09 | 0.00 | 67770116.26 | 0.00 | 0.70 |
August | 94854647.99 | 0.153535E+10 | 0.00 | 1438427.10 | 53064553.11 | 0.00 | 98171659.15 | 0.00 | 0.76 |
September | 32430415.12 | 0.106788E+10 | 0.00 | 3137276.51 | 70062185.16 | 0.00 | 0.297236E+09 | 0.00 | 0.79 |
October | 0.333724E+09 | 0.191091E+09 | 0.00 | 7359602.74 | 13299389.62 | 0.00 | 0.205664E+10 | 0.00 | 1.02 |
November | 0.600496E+09 | 1850366.14 | 0.00 | 7301260.31 | 4219867.98 | 0.00 | 0.243644E+10 | 0.00 | 0.90 |
December | 0.934402E+09 | 7481.06 | 0.00 | 5012209.15 | 119687.54 | 153732.80 | 0.196793E+10 | 0.00 | 0.63 |
Annual Sum or Average | 0.489268E+10 | 0.672995E+10 | 0.00 | 65372645.00 | 0.314450E+09 | 153732.80 | 0.182505E+11 | 0.00 | 0.89 |
Minimum of Months | 32430415.12 | 0.00 | 0.00 | 942594.52 | 0.00 | 0.00 | 67770116.26 | 0.00 | 0.63 |
Maximum of Months | 0.934402E+09 | 0.171404E+10 | 0.00 | 10231620.75 | 0.118679E+09 | 153732.80 | 0.309792E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.611534E+09 | 4678561.70 | 0.00 | 28763848.81 | 700024.05 | 0.00 | 0.676927E+10 | 0.00 | 1.62 |
February | 0.862420E+09 | 0.00 | 0.00 | 13300330.06 | 0.00 | 0.00 | 0.723627E+10 | 0.00 | 1.25 |
March | 0.858556E+09 | 2871906.99 | 0.00 | 14589390.93 | 0.00 | 0.00 | 0.492272E+10 | 0.00 | 1.21 |
April | 0.961998E+09 | 0.332712E+09 | 0.00 | 10602755.46 | 24766119.04 | 0.00 | 0.151620E+10 | 0.00 | 0.97 |
May | 0.200176E+09 | 0.627124E+09 | 0.00 | 5054312.15 | 21219957.63 | 0.00 | 0.615490E+09 | 0.00 | 0.61 |
June | 0.201848E+09 | 0.194220E+10 | 0.00 | 1622400.90 | 37470826.58 | 0.00 | 0.183209E+09 | 0.00 | 0.60 |
July | 0.109289E+09 | 0.213072E+10 | 0.00 | 845996.13 | 0.176884E+09 | 0.00 | 66463879.46 | 0.00 | 0.55 |
August | 0.142860E+09 | 0.221492E+10 | 0.00 | 1977508.07 | 78634721.61 | 0.00 | 0.127958E+09 | 0.00 | 0.68 |
September | 44808267.08 | 0.173413E+10 | 0.00 | 4665420.79 | 0.105354E+09 | 0.00 | 0.363592E+09 | 0.00 | 0.74 |
October | 0.439703E+09 | 0.403754E+09 | 0.00 | 15704495.04 | 17980269.38 | 0.00 | 0.362767E+10 | 0.00 | 1.25 |
November | 0.542969E+09 | 7111781.97 | 0.00 | 24668274.39 | 5124433.02 | 0.00 | 0.678406E+10 | 0.00 | 1.53 |
December | 0.906171E+09 | 951343.65 | 0.00 | 24950560.72 | 0.00 | 0.00 | 0.737166E+10 | 0.00 | 1.36 |
Annual Sum or Average | 0.588233E+10 | 0.940117E+10 | 0.00 | 0.146745E+09 | 0.468135E+09 | 0.00 | 0.395846E+11 | 0.00 | 1.03 |
Minimum of Months | 44808267.08 | 0.00 | 0.00 | 845996.13 | 0.00 | 0.00 | 66463879.46 | 0.00 | 0.55 |
Maximum of Months | 0.961998E+09 | 0.221492E+10 | 0.00 | 28763848.81 | 0.176884E+09 | 0.00 | 0.737166E+10 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.355562E+09 | 4089604.11 | 0.00 | 10934006.56 | 0.00 | 0.00 | 0.292888E+10 | 0.00 | 1.14 |
February | 0.220080E+09 | 0.00 | 0.00 | 9180155.92 | 0.00 | 0.00 | 0.493325E+10 | 0.00 | 1.28 |
March | 0.128741E+09 | 2514204.26 | 0.00 | 15626851.64 | 0.00 | 0.00 | 0.536024E+10 | 0.00 | 1.77 |
April | 0.125064E+09 | 0.433196E+09 | 0.00 | 18572781.25 | 1149269.66 | 0.00 | 0.306405E+10 | 0.00 | 1.83 |
May | 64049187.32 | 0.787650E+09 | 0.00 | 6136034.65 | 3027746.28 | 0.00 | 0.856202E+09 | 0.00 | 1.03 |
June | 50472184.09 | 0.240488E+10 | 0.00 | 3317584.09 | 8950407.41 | 0.00 | 0.384759E+09 | 0.00 | 1.10 |
July | 15235254.78 | 0.253809E+10 | 0.00 | 1817775.96 | 13718788.58 | 0.00 | 0.173557E+09 | 0.00 | 0.93 |
August | 11865751.43 | 0.256708E+10 | 0.00 | 5194905.18 | 7024111.87 | 0.00 | 0.354077E+09 | 0.00 | 1.27 |
September | 16015874.98 | 0.135458E+10 | 0.00 | 4120182.45 | 38887175.74 | 0.00 | 0.367577E+09 | 0.00 | 0.92 |
October | 0.111350E+09 | 0.273330E+09 | 0.00 | 11388144.31 | 9186022.37 | 0.00 | 0.275681E+10 | 0.00 | 1.33 |
November | 0.149556E+09 | 14101889.81 | 0.00 | 15885874.63 | 1170038.42 | 0.00 | 0.491562E+10 | 0.00 | 1.62 |
December | 0.180221E+09 | 452804.57 | 0.00 | 15449004.54 | 6454.37 | 0.00 | 0.559893E+10 | 0.00 | 1.40 |
Annual Sum or Average | 0.142821E+10 | 0.103800E+11 | 0.00 | 0.117623E+09 | 83120014.71 | 0.00 | 0.316940E+11 | 0.00 | 1.30 |
Minimum of Months | 11865751.43 | 0.00 | 0.00 | 1817775.96 | 0.00 | 0.00 | 0.173557E+09 | 0.00 | 0.92 |
Maximum of Months | 0.355562E+09 | 0.256708E+10 | 0.00 | 18572781.25 | 38887175.74 | 0.00 | 0.559893E+10 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184636E+11 | 0.00 | 0.00 | 10838531.96 | 39171419.37 | 0.559761E+09 | 0.235681E+10 | 0.00 | 0.38 |
February | 0.212829E+11 | 0.00 | 0.00 | 6188176.96 | 0.00 | 0.524280E+09 | 0.360497E+10 | 0.00 | 0.36 |
March | 0.167236E+11 | 14900115.03 | 0.00 | 30455297.85 | 2131196.67 | 0.511002E+09 | 0.805261E+10 | 0.00 | 0.47 |
April | 0.487456E+10 | 0.248987E+10 | 0.00 | 49642274.05 | 0.239501E+09 | 0.00 | 0.638435E+10 | 0.00 | 0.51 |
May | 0.158262E+10 | 0.640767E+10 | 0.00 | 39556469.19 | 0.187113E+09 | 0.00 | 0.496603E+10 | 0.00 | 0.55 |
June | 0.634188E+09 | 0.230880E+11 | 0.00 | 18352360.15 | 0.281048E+09 | 0.00 | 0.227453E+10 | 0.00 | 0.63 |
July | 0.274897E+09 | 0.228681E+11 | 0.00 | 6225516.79 | 0.438009E+09 | 0.00 | 0.727869E+09 | 0.00 | 0.52 |
August | 0.344712E+09 | 0.194317E+11 | 0.00 | 11860333.43 | 0.358870E+09 | 0.00 | 0.102922E+10 | 0.00 | 0.54 |
September | 0.514228E+09 | 0.127386E+11 | 0.00 | 26633993.96 | 0.615192E+09 | 0.00 | 0.221721E+10 | 0.00 | 0.52 |
October | 0.873820E+10 | 0.234317E+10 | 0.00 | 29781774.14 | 81082663.18 | 0.00 | 0.565685E+10 | 0.00 | 0.45 |
November | 0.166628E+11 | 13232650.11 | 0.00 | 23656855.71 | 56903537.04 | 0.277989E+09 | 0.585050E+10 | 0.00 | 0.42 |
December | 0.223162E+11 | 0.00 | 0.00 | 1955472.67 | 612390.05 | 0.328197E+10 | 0.641167E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.112412E+12 | 0.893952E+11 | 0.00 | 0.255147E+09 | 0.229964E+10 | 0.515500E+10 | 0.437621E+11 | 0.00 | 0.48 |
Minimum of Months | 0.274897E+09 | 0.00 | 0.00 | 1955472.67 | 0.00 | 0.00 | 0.641167E+09 | 0.00 | 0.35 |
Maximum of Months | 0.223162E+11 | 0.230880E+11 | 0.00 | 49642274.05 | 0.615192E+09 | 0.328197E+10 | 0.805261E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.694663E+10 | 3379891.05 | 0.00 | 42164161.95 | 21889801.78 | 0.167117E+09 | 0.132233E+11 | 0.00 | 0.55 |
February | 0.785411E+10 | 0.00 | 0.00 | 32712954.94 | 0.00 | 67858238.34 | 0.151808E+11 | 0.00 | 0.50 |
March | 0.601189E+10 | 12001379.92 | 0.00 | 60486059.40 | 1375270.44 | 0.157164E+09 | 0.209506E+11 | 0.00 | 0.79 |
April | 0.157146E+10 | 0.241094E+10 | 0.00 | 97449519.76 | 0.152093E+09 | 0.00 | 0.167508E+11 | 0.00 | 1.12 |
May | 0.711164E+09 | 0.544796E+10 | 0.00 | 70060840.87 | 0.104998E+09 | 0.00 | 0.899613E+10 | 0.00 | 1.04 |
June | 0.346299E+09 | 0.196092E+11 | 0.00 | 21262842.00 | 0.137954E+09 | 0.00 | 0.227320E+10 | 0.00 | 0.93 |
July | 0.125109E+09 | 0.205956E+11 | 0.00 | 8925475.27 | 0.229132E+09 | 0.00 | 0.838862E+09 | 0.00 | 0.76 |
August | 0.172946E+09 | 0.184413E+11 | 0.00 | 14988401.78 | 0.178468E+09 | 0.00 | 0.121213E+10 | 0.00 | 0.81 |
September | 0.258912E+09 | 0.118439E+11 | 0.00 | 28758613.21 | 0.301781E+09 | 0.00 | 0.261343E+10 | 0.00 | 0.79 |
October | 0.309602E+10 | 0.220154E+10 | 0.00 | 58454294.25 | 41155219.85 | 0.00 | 0.148485E+11 | 0.00 | 0.84 |
November | 0.659474E+10 | 13095386.95 | 0.00 | 47478335.88 | 35362688.31 | 54860919.44 | 0.152019E+11 | 0.00 | 0.64 |
December | 0.946272E+10 | 19257.93 | 0.00 | 21572581.69 | 260057.59 | 0.113388E+10 | 0.790318E+10 | 0.00 | 0.38 |
Annual Sum or Average | 0.431520E+11 | 0.805789E+11 | 0.00 | 0.504314E+09 | 0.120447E+10 | 0.158088E+10 | 0.119993E+12 | 0.00 | 0.76 |
Minimum of Months | 0.125109E+09 | 0.00 | 0.00 | 8925475.27 | 0.00 | 0.00 | 0.838862E+09 | 0.00 | 0.38 |
Maximum of Months | 0.946272E+10 | 0.205956E+11 | 0.00 | 97449519.76 | 0.301781E+09 | 0.113388E+10 | 0.209506E+11 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.583886E+10 | 62928348.90 | 0.00 | 0.285403E+09 | 12677473.85 | 0.110667E+09 | 0.549604E+11 | 0.00 | 1.32 |
February | 0.967835E+10 | 0.00 | 0.00 | 0.116835E+09 | 0.00 | 93040719.06 | 0.505307E+11 | 0.00 | 0.88 |
March | 0.992378E+10 | 30093690.64 | 0.00 | 0.119121E+09 | 0.00 | 0.150640E+09 | 0.359145E+11 | 0.00 | 0.97 |
April | 0.382742E+10 | 0.440867E+10 | 0.00 | 84888988.10 | 0.235882E+09 | 0.00 | 0.109111E+11 | 0.00 | 0.76 |
May | 0.160222E+10 | 0.728636E+10 | 0.00 | 40842415.95 | 0.187265E+09 | 0.00 | 0.453210E+10 | 0.00 | 0.58 |
June | 0.683670E+09 | 0.222001E+11 | 0.00 | 14902098.18 | 0.292414E+09 | 0.00 | 0.176723E+10 | 0.00 | 0.58 |
July | 0.287121E+09 | 0.233061E+11 | 0.00 | 5417577.66 | 0.442535E+09 | 0.00 | 0.601327E+09 | 0.00 | 0.52 |
August | 0.314519E+09 | 0.238892E+11 | 0.00 | 13657408.53 | 0.295145E+09 | 0.00 | 0.112349E+10 | 0.00 | 0.63 |
September | 0.400288E+09 | 0.195651E+11 | 0.00 | 39998029.69 | 0.500401E+09 | 0.00 | 0.291925E+10 | 0.00 | 0.73 |
October | 0.425136E+10 | 0.485745E+10 | 0.00 | 0.138074E+09 | 34057999.04 | 0.00 | 0.286135E+11 | 0.00 | 1.11 |
November | 0.610334E+10 | 59369132.90 | 0.00 | 0.225243E+09 | 34500359.85 | 2758143.37 | 0.559813E+11 | 0.00 | 1.29 |
December | 0.985121E+10 | 1999129.41 | 0.00 | 0.217448E+09 | 0.00 | 0.653449E+09 | 0.574216E+11 | 0.00 | 1.10 |
Annual Sum or Average | 0.527621E+11 | 0.105667E+12 | 0.00 | 0.130183E+10 | 0.203488E+10 | 0.101055E+10 | 0.305276E+12 | 0.00 | 0.87 |
Minimum of Months | 0.287121E+09 | 0.00 | 0.00 | 5417577.66 | 0.00 | 0.00 | 0.601327E+09 | 0.00 | 0.52 |
Maximum of Months | 0.992378E+10 | 0.238892E+11 | 0.00 | 0.285403E+09 | 0.500401E+09 | 0.653449E+09 | 0.574216E+11 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.824729E+10 | 15599376.37 | 0.00 | 52484012.60 | 21777995.81 | 0.115670E+09 | 0.102659E+11 | 0.00 | 0.61 |
February | 0.101522E+11 | 0.00 | 0.00 | 29813411.83 | 0.00 | 27061167.01 | 0.124044E+11 | 0.00 | 0.52 |
March | 0.744823E+10 | 22097707.47 | 0.00 | 60443404.69 | 0.00 | 15732458.06 | 0.165664E+11 | 0.00 | 0.84 |
April | 0.177140E+10 | 0.422250E+10 | 0.00 | 70686821.86 | 36478080.31 | 0.00 | 0.981505E+10 | 0.00 | 0.99 |
May | 0.562434E+09 | 0.864960E+10 | 0.00 | 38289860.73 | 23111520.63 | 0.00 | 0.471266E+10 | 0.00 | 0.87 |
June | 0.253773E+09 | 0.249710E+11 | 0.00 | 18760869.20 | 0.104233E+09 | 0.00 | 0.215318E+10 | 0.00 | 0.95 |
July | 0.112626E+09 | 0.215157E+11 | 0.00 | 6897140.11 | 0.134242E+09 | 0.00 | 0.727007E+09 | 0.00 | 0.72 |
August | 0.141566E+09 | 0.197325E+11 | 0.00 | 14203752.89 | 0.112368E+09 | 0.00 | 0.113058E+10 | 0.00 | 0.81 |
September | 0.176258E+09 | 0.125910E+11 | 0.00 | 25421840.22 | 0.274147E+09 | 0.00 | 0.206328E+10 | 0.00 | 0.75 |
October | 0.367163E+10 | 0.252258E+10 | 0.00 | 53833046.09 | 21200620.15 | 0.00 | 0.104614E+11 | 0.00 | 0.78 |
November | 0.680545E+10 | 39768465.64 | 0.00 | 60717630.07 | 23553881.59 | 32408800.21 | 0.150443E+11 | 0.00 | 0.72 |
December | 0.114264E+11 | 356280.00 | 0.00 | 31515526.17 | 170316.30 | 0.839483E+09 | 0.918413E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.507692E+11 | 0.942827E+11 | 0.00 | 0.463067E+09 | 0.751282E+09 | 0.103035E+10 | 0.945283E+11 | 0.00 | 0.76 |
Minimum of Months | 0.112626E+09 | 0.00 | 0.00 | 6897140.11 | 0.00 | 0.00 | 0.727007E+09 | 0.00 | 0.49 |
Maximum of Months | 0.114264E+11 | 0.249710E+11 | 0.00 | 70686821.86 | 0.274147E+09 | 0.839483E+09 | 0.165664E+11 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.152333E+10 | 0.00 | 0.00 | 627374.09 | 2469009.19 | 0.363035E+09 | 0.164634E+09 | 0.00 | 0.42 |
February | 0.205121E+10 | 0.00 | 0.00 | 299643.39 | 0.00 | 0.320296E+09 | 0.240419E+09 | 0.00 | 0.41 |
March | 0.154637E+10 | 389691.08 | 0.00 | 2508769.93 | 55383.23 | 0.248290E+09 | 0.604874E+09 | 0.00 | 0.47 |
April | 0.460539E+09 | 0.156515E+09 | 0.00 | 6020165.18 | 21857390.75 | 0.00 | 0.538361E+09 | 0.00 | 0.49 |
May | 0.159637E+09 | 0.449540E+09 | 0.00 | 5133838.63 | 14622607.88 | 0.00 | 0.352574E+09 | 0.00 | 0.51 |
June | 63969106.40 | 0.186326E+10 | 0.00 | 1604189.27 | 19862740.90 | 0.00 | 0.166719E+09 | 0.00 | 0.58 |
July | 32200688.46 | 0.195288E+10 | 0.00 | 658644.26 | 40840093.59 | 0.00 | 52002878.14 | 0.00 | 0.49 |
August | 31393346.53 | 0.164741E+10 | 0.00 | 1119691.03 | 31880896.23 | 0.00 | 75856736.16 | 0.00 | 0.51 |
September | 72412973.53 | 0.106203E+10 | 0.00 | 2993053.71 | 69608694.68 | 0.00 | 0.167208E+09 | 0.00 | 0.50 |
October | 0.813896E+09 | 0.182673E+09 | 0.00 | 2961815.96 | 10248312.38 | 82696233.95 | 0.415141E+09 | 0.00 | 0.43 |
November | 0.140645E+10 | 716979.35 | 0.00 | 1648839.58 | 6023430.71 | 0.243733E+09 | 0.464812E+09 | 0.00 | 0.43 |
December | 0.176224E+10 | 0.00 | 0.00 | 78054.34 | 435331.86 | 0.839027E+09 | 20197814.89 | 0.00 | 0.39 |
Annual Sum or Average | 0.992365E+10 | 0.731541E+10 | 0.00 | 25654079.37 | 0.217904E+09 | 0.209708E+10 | 0.326280E+10 | 0.00 | 0.47 |
Minimum of Months | 31393346.53 | 0.00 | 0.00 | 78054.34 | 0.00 | 0.00 | 20197814.89 | 0.00 | 0.39 |
Maximum of Months | 0.205121E+10 | 0.195288E+10 | 0.00 | 6020165.18 | 69608694.68 | 0.839027E+09 | 0.604874E+09 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.580114E+09 | 152846.32 | 0.00 | 3215243.28 | 1444329.16 | 0.131793E+09 | 0.108558E+10 | 0.00 | 0.58 |
February | 0.728925E+09 | 0.00 | 0.00 | 2287888.99 | 0.00 | 0.126255E+09 | 0.142351E+10 | 0.00 | 0.54 |
March | 0.541966E+09 | 401953.06 | 0.00 | 5451565.85 | 35826.82 | 92531800.12 | 0.193149E+10 | 0.00 | 0.80 |
April | 0.155718E+09 | 0.161167E+09 | 0.00 | 11092418.21 | 13147653.60 | 0.00 | 0.148586E+10 | 0.00 | 1.11 |
May | 73192111.19 | 0.386872E+09 | 0.00 | 8309177.88 | 7592103.52 | 0.00 | 0.723085E+09 | 0.00 | 0.99 |
June | 33039822.95 | 0.164780E+10 | 0.00 | 1842764.83 | 10269032.02 | 0.00 | 0.170285E+09 | 0.00 | 0.88 |
July | 15556495.62 | 0.181904E+10 | 0.00 | 859662.36 | 22037808.69 | 0.00 | 60579156.36 | 0.00 | 0.73 |
August | 16702980.80 | 0.163562E+10 | 0.00 | 1425485.44 | 18085998.49 | 0.00 | 90356383.39 | 0.00 | 0.79 |
September | 29050325.81 | 0.105829E+10 | 0.00 | 3269645.44 | 26900151.33 | 0.00 | 0.218802E+09 | 0.00 | 0.77 |
October | 0.267656E+09 | 0.185744E+09 | 0.00 | 5736466.25 | 4232256.51 | 29631665.72 | 0.132093E+10 | 0.00 | 0.82 |
November | 0.618275E+09 | 639783.59 | 0.00 | 3875184.82 | 3896492.52 | 77719015.81 | 0.125351E+10 | 0.00 | 0.64 |
December | 0.105940E+10 | 0.00 | 0.00 | 1075362.20 | 281611.49 | 0.274234E+09 | 0.467588E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.411960E+10 | 0.689572E+10 | 0.00 | 48440865.56 | 0.107923E+09 | 0.732165E+09 | 0.102316E+11 | 0.00 | 0.76 |
Minimum of Months | 15556495.62 | 0.00 | 0.00 | 859662.36 | 0.00 | 0.00 | 60579156.36 | 0.00 | 0.43 |
Maximum of Months | 0.105940E+10 | 0.181904E+10 | 0.00 | 11092418.21 | 26900151.33 | 0.274234E+09 | 0.193149E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.558680E+09 | 2293981.83 | 0.00 | 23540402.05 | 1804073.71 | 84384161.52 | 0.578444E+10 | 0.00 | 1.55 |
February | 0.954977E+09 | 0.00 | 0.00 | 9341649.63 | 0.00 | 0.135672E+09 | 0.587756E+10 | 0.00 | 1.05 |
March | 0.839202E+09 | 878786.95 | 0.00 | 10645293.41 | 0.00 | 0.155864E+09 | 0.350455E+10 | 0.00 | 0.96 |
April | 0.401189E+09 | 0.271553E+09 | 0.00 | 10592970.11 | 18752202.12 | 0.00 | 0.983423E+09 | 0.00 | 0.74 |
May | 0.188576E+09 | 0.499069E+09 | 0.00 | 5515473.33 | 14214633.86 | 0.00 | 0.317008E+09 | 0.00 | 0.54 |
June | 68916694.65 | 0.178438E+10 | 0.00 | 1320163.29 | 20730671.53 | 0.00 | 0.127814E+09 | 0.00 | 0.54 |
July | 35350087.91 | 0.196940E+10 | 0.00 | 595326.97 | 41955445.53 | 0.00 | 41449411.48 | 0.00 | 0.49 |
August | 29070072.71 | 0.197343E+10 | 0.00 | 1293383.30 | 28851259.09 | 0.00 | 82852181.06 | 0.00 | 0.59 |
September | 46646465.72 | 0.160115E+10 | 0.00 | 4629169.27 | 40980864.15 | 0.00 | 0.250399E+09 | 0.00 | 0.69 |
October | 0.391147E+09 | 0.373054E+09 | 0.00 | 14416971.07 | 5385474.79 | 16026294.06 | 0.288489E+10 | 0.00 | 1.11 |
November | 0.569540E+09 | 2203685.54 | 0.00 | 18603174.58 | 5785728.03 | 72234583.47 | 0.556355E+10 | 0.00 | 1.37 |
December | 0.863533E+09 | 784613.92 | 0.00 | 15984277.84 | 79428.15 | 0.253318E+09 | 0.602346E+10 | 0.00 | 1.23 |
Annual Sum or Average | 0.494683E+10 | 0.847820E+10 | 0.00 | 0.116478E+09 | 0.178540E+09 | 0.717499E+09 | 0.314414E+11 | 0.00 | 0.90 |
Minimum of Months | 29070072.71 | 0.00 | 0.00 | 595326.97 | 0.00 | 0.00 | 41449411.48 | 0.00 | 0.49 |
Maximum of Months | 0.954977E+09 | 0.197343E+10 | 0.00 | 23540402.05 | 41955445.53 | 0.253318E+09 | 0.602346E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.778749E+09 | 771439.98 | 0.00 | 4365865.91 | 1441846.16 | 99907268.57 | 0.106133E+10 | 0.00 | 0.73 |
February | 0.100212E+10 | 0.00 | 0.00 | 2352434.51 | 0.00 | 0.106792E+09 | 0.149059E+10 | 0.00 | 0.65 |
March | 0.726380E+09 | 573038.96 | 0.00 | 5507725.95 | 0.00 | 72872171.58 | 0.156803E+10 | 0.00 | 0.84 |
April | 0.171685E+09 | 0.264822E+09 | 0.00 | 9287926.15 | 2943998.13 | 0.00 | 0.882062E+09 | 0.00 | 0.95 |
May | 51883375.42 | 0.584253E+09 | 0.00 | 5073481.79 | 2113220.72 | 0.00 | 0.358448E+09 | 0.00 | 0.79 |
June | 20920384.67 | 0.190786E+10 | 0.00 | 1679783.25 | 7957191.65 | 0.00 | 0.172689E+09 | 0.00 | 0.85 |
July | 11759078.92 | 0.177251E+10 | 0.00 | 739088.68 | 13312268.52 | 0.00 | 58223129.99 | 0.00 | 0.66 |
August | 12602030.83 | 0.159030E+10 | 0.00 | 1343121.64 | 12301428.89 | 0.00 | 86722452.65 | 0.00 | 0.75 |
September | 23650870.76 | 0.102233E+10 | 0.00 | 2948614.53 | 26855352.92 | 0.00 | 0.170498E+09 | 0.00 | 0.70 |
October | 0.379154E+09 | 0.193357E+09 | 0.00 | 5633784.29 | 2786772.01 | 6701189.18 | 0.976710E+09 | 0.00 | 0.76 |
November | 0.654952E+09 | 1691859.81 | 0.00 | 5119438.86 | 3593023.53 | 69447989.01 | 0.147373E+10 | 0.00 | 0.77 |
December | 0.100259E+10 | 0.00 | 0.00 | 2352954.94 | 281996.87 | 0.259966E+09 | 0.986356E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.483645E+10 | 0.733847E+10 | 0.00 | 46404220.48 | 73587099.42 | 0.615687E+09 | 0.928539E+10 | 0.00 | 0.75 |
Minimum of Months | 11759078.92 | 0.00 | 0.00 | 739088.68 | 0.00 | 0.00 | 58223129.99 | 0.00 | 0.56 |
Maximum of Months | 0.100259E+10 | 0.190786E+10 | 0.00 | 9287926.15 | 26855352.92 | 0.259966E+09 | 0.156803E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 4205833.07 | 0.00 | 0.00 | 0.293911E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8205217.07 | 0.00 | 0.00 | 0.293026E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14742646.21 | 0.00 | 0.00 | 0.292036E+09 | 0.00 | 0.31 |
April | 0.00 | 227272.30 | 0.00 | 19652852.79 | 0.00 | 0.00 | 0.124951E+09 | 0.00 | 0.29 |
May | 0.00 | 13885514.75 | 0.00 | 3018384.80 | 0.00 | 0.00 | 54620635.35 | 0.00 | 0.29 |
June | 0.00 | 92052072.88 | 0.00 | 1627404.87 | 0.00 | 0.00 | 14586105.12 | 0.00 | 0.30 |
July | 0.00 | 0.186322E+09 | 0.00 | 517701.23 | 0.00 | 0.00 | 4104085.79 | 0.00 | 0.28 |
August | 0.00 | 0.152938E+09 | 0.00 | 3039186.64 | 0.00 | 0.00 | 5988373.97 | 0.00 | 0.31 |
September | 0.00 | 0.112793E+09 | 0.00 | 713833.28 | 0.00 | 0.00 | 10798723.37 | 0.00 | 0.29 |
October | 0.00 | 22325569.49 | 0.00 | 7229239.41 | 0.00 | 0.00 | 0.169290E+09 | 0.00 | 0.28 |
November | 0.00 | 1931831.39 | 0.00 | 12850961.71 | 0.00 | 0.00 | 0.236117E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 19158007.15 | 0.00 | 0.00 | 0.349597E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.582475E+09 | 0.00 | 94961268.23 | 0.00 | 0.00 | 0.184903E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 517701.23 | 0.00 | 0.00 | 4104085.79 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.186322E+09 | 0.00 | 19652852.79 | 0.00 | 0.00 | 0.349597E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13410420.94 | 0.00 | 0.00 | 33484447.67 | 0.00 | 0.00 | 0.293263E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 72028830.56 | 0.00 | 0.00 | 0.294406E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.136093E+09 | 0.00 | 0.00 | 0.292957E+10 | 0.00 | 0.31 |
April | 0.00 | 3770832.52 | 0.00 | 0.181741E+09 | 0.00 | 0.00 | 0.122439E+10 | 0.00 | 0.29 |
May | 0.00 | 0.138509E+09 | 0.00 | 28010984.37 | 0.00 | 0.00 | 0.547157E+09 | 0.00 | 0.29 |
June | 0.00 | 0.919581E+09 | 0.00 | 15390264.78 | 0.00 | 0.00 | 0.145161E+09 | 0.00 | 0.30 |
July | 0.00 | 0.185977E+10 | 0.00 | 4923947.67 | 0.00 | 0.00 | 40471867.95 | 0.00 | 0.28 |
August | 0.00 | 0.159675E+10 | 0.00 | 26046037.20 | 0.00 | 0.00 | 52406240.52 | 0.00 | 0.31 |
September | 0.00 | 0.111530E+10 | 0.00 | 6559094.87 | 0.00 | 0.00 | 0.107973E+09 | 0.00 | 0.29 |
October | 0.00 | 0.222108E+09 | 0.00 | 66191322.12 | 0.00 | 0.00 | 0.169608E+10 | 0.00 | 0.28 |
November | 0.00 | 18726731.86 | 0.00 | 0.118206E+09 | 0.00 | 0.00 | 0.236991E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.174658E+09 | 0.00 | 0.00 | 0.350625E+10 | 0.00 | 0.28 |
Annual Sum or Average | 13410420.94 | 0.587451E+10 | 0.00 | 0.863333E+09 | 0.00 | 0.00 | 0.184961E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 4923947.67 | 0.00 | 0.00 | 40471867.95 | 0.00 | 0.28 |
Maximum of Months | 13410420.94 | 0.185977E+10 | 0.00 | 0.181741E+09 | 0.00 | 0.00 | 0.350625E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9895542.83 | 0.00 | 0.00 | 2665537.57 | 0.00 | 0.00 | 0.285667E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6496381.03 | 0.00 | 0.00 | 0.295712E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 13120550.50 | 0.00 | 0.00 | 0.293677E+09 | 0.00 | 0.31 |
April | 0.00 | 510772.61 | 0.00 | 17628340.96 | 0.00 | 0.00 | 0.119120E+09 | 0.00 | 0.29 |
May | 0.00 | 13866839.52 | 0.00 | 2812870.78 | 0.00 | 0.00 | 54739911.85 | 0.00 | 0.29 |
June | 0.00 | 92003176.56 | 0.00 | 1539219.66 | 0.00 | 0.00 | 14594784.68 | 0.00 | 0.30 |
July | 0.00 | 0.185985E+09 | 0.00 | 493920.65 | 0.00 | 0.00 | 4086954.84 | 0.00 | 0.28 |
August | 0.00 | 0.164314E+09 | 0.00 | 2421585.70 | 0.00 | 0.00 | 4926846.59 | 0.00 | 0.31 |
September | 0.00 | 0.111779E+09 | 0.00 | 650760.94 | 0.00 | 0.00 | 10875564.20 | 0.00 | 0.29 |
October | 0.00 | 22222630.75 | 0.00 | 6346587.94 | 0.00 | 0.00 | 0.170060E+09 | 0.00 | 0.28 |
November | 0.00 | 1824392.77 | 0.00 | 11275465.70 | 0.00 | 0.00 | 0.237758E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16450018.77 | 0.00 | 0.00 | 0.351411E+09 | 0.00 | 0.28 |
Annual Sum or Average | 9895542.83 | 0.592506E+09 | 0.00 | 81901240.20 | 0.00 | 0.00 | 0.184263E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 493920.65 | 0.00 | 0.00 | 4086954.84 | 0.00 | 0.28 |
Maximum of Months | 9895542.83 | 0.185985E+09 | 0.00 | 17628340.96 | 0.00 | 0.00 | 0.351411E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.575026E+09 | 0.00 | 0.00 | 0.503135E+12 | 0.00 | 22.29 |
February | 0.00 | 0.00 | 0.00 | 0.919033E+09 | 0.00 | 0.00 | 0.611517E+12 | 0.00 | 28.43 |
March | 0.00 | 0.00 | 0.00 | 0.158309E+10 | 0.00 | 0.00 | 0.828489E+12 | 0.00 | 38.82 |
April | 0.00 | 0.00 | 0.00 | 0.363764E+10 | 0.00 | 0.00 | 0.615562E+12 | 0.00 | 45.63 |
May | 0.00 | 27822.13 | 0.00 | 0.475476E+09 | 0.00 | 0.00 | 0.267848E+12 | 0.00 | 19.15 |
June | 0.00 | 0.913504E+09 | 0.00 | 0.595073E+09 | 0.00 | 0.00 | 0.118827E+12 | 0.00 | 12.10 |
July | 0.00 | 0.520790E+11 | 0.00 | 0.323857E+09 | 0.00 | 0.00 | 0.403146E+11 | 0.00 | 13.79 |
August | 0.00 | 0.250539E+11 | 0.00 | 0.141444E+10 | 0.00 | 0.00 | 0.724504E+11 | 0.00 | 29.61 |
September | 0.00 | 0.102332E+11 | 0.00 | 0.268367E+09 | 0.00 | 0.00 | 0.104800E+12 | 0.00 | 21.08 |
October | 0.00 | 0.306178E+10 | 0.00 | 0.101104E+10 | 0.00 | 0.00 | 0.502594E+12 | 0.00 | 31.27 |
November | 0.00 | 19031548.85 | 0.00 | 0.168795E+10 | 0.00 | 0.00 | 0.781400E+12 | 0.00 | 39.76 |
December | 0.00 | 0.00 | 0.00 | 0.240079E+10 | 0.00 | 0.00 | 0.113958E+13 | 0.00 | 40.65 |
Annual Sum or Average | 0.00 | 0.913605E+11 | 0.00 | 0.148918E+11 | 0.00 | 0.00 | 0.558652E+13 | 0.00 | 28.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.268367E+09 | 0.00 | 0.00 | 0.403146E+11 | 0.00 | 12.10 |
Maximum of Months | 0.00 | 0.520790E+11 | 0.00 | 0.363764E+10 | 0.00 | 0.00 | 0.113958E+13 | 0.00 | 45.63 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:51:38
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.317711E+12 | 0.101481E+11 | 0.00 | 0.212265E+13 | 0.699313E+12 |
February | 0.358395E+12 | 0.801214E+10 | 0.00 | 0.230252E+13 | 0.367351E+12 |
March | 0.464830E+12 | 0.104866E+11 | 0.00 | 0.248973E+13 | 0.106128E+13 |
April | 0.553182E+12 | 0.276811E+10 | 0.00 | 0.142840E+13 | 0.279278E+13 |
May | 0.547582E+12 | 0.433021E+09 | 0.00 | 0.761693E+12 | 0.245422E+13 |
June | 0.560288E+12 | -0.294742E+10 | 0.00 | 0.375172E+11 | 0.344856E+13 |
July | 0.531036E+12 | -0.536054E+10 | 0.00 | -0.256819E+12 | 0.383967E+13 |
August | 0.475118E+12 | -0.336324E+10 | 0.00 | -0.846964E+11 | 0.418971E+13 |
September | 0.396611E+12 | -0.201420E+10 | 0.00 | 0.213656E+11 | 0.247152E+13 |
October | 0.371511E+12 | 0.457902E+10 | 0.00 | 0.167161E+13 | 0.173443E+13 |
November | 0.333350E+12 | 0.927962E+10 | 0.00 | 0.239171E+13 | 0.110468E+13 |
December | 0.263852E+12 | 0.983776E+10 | 0.00 | 0.293080E+13 | 0.950654E+12 |
Annual Sum or Average | 0.517347E+13 | 0.418590E+11 | 0.00 | 0.158165E+14 | 0.251142E+14 |
Minimum of Months | 0.263852E+12 | -0.536054E+10 | 0.00 | -0.256819E+12 | 0.367351E+12 |