Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:50
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:50:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31381.39 | 677.49 | 677.49 |
Net Site Energy | 31381.39 | 677.49 | 677.49 |
Total Source Energy | 98097.23 | 2117.80 | 2117.80 |
Net Source Energy | 98097.23 | 2117.80 | 2117.80 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5922.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2457.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 349.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1909.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2563.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 797.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1987.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15085.13 |
Humidification | 1.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Heat Recovery | 99.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 613.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30763.23 | 618.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17365.73 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 4.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 5922.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2457.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 349.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2563.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 797.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1987.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15085.13 |
Humidification | General | 1.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Heat Recovery | General | 99.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 613.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 4.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5922.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2457.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 349.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1909.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2563.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 797.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1987.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15085.13 |
Humidification | Unassigned | 1.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Heat Recovery | Unassigned | 99.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 613.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 243.35 | 13.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Other | 360.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 664.14 | 13.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 243.35 | 13.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Other | 360.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 664.14 | 13.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 30763.228 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30763.228 | 100.00 |
Total On-Site and Utility Electric Sources | 30763.228 | 100.00 |
Total Electricity End Uses | 30763.228 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 3290.10 | 99.61 |
Air to Air Heat Recovery for Heating | 12.89 | 0.39 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3302.99 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 17365.73 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 17365.73 | 100.00 |
Total Water End Uses | 17365.73 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1114.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:50 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 21-AUG-15:00 | 04-FEB-06:10 | - | - | - | - | - | - | - | - | - | - | 07-JUL-12:09 |
Heating | 0.00 | 308365.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 438119.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82829.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 198046.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 50246.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 86109.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1851059.15 | 315646.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 308365.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 438119.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 198046.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 50246.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 86109.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 5.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18757.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7781.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1106.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6046.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8117.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2524.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6294.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 314.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 665.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 97427.14 | 670.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 404.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 175.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 54.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 135.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 6.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2103.33 | 14.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 404.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 175.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 54.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 135.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 6.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2103.33 | 14.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.18 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.462941 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.42 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.450710 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.28 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.53 | 0.344120 | 0.293000 | 1.62 | 0.917654 | 0.500000 | 0.001107 | 0.000142 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 52.09 | 0.365153 | 0.310000 | 16.15 | 0.973740 | 0.500000 | 0.001043 | 0.003193 | 16.15 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.19 | 0.366596 | 0.312000 | 1.62 | 0.977589 | 0.500000 | 0.001039 | 0.000531 | 1.80 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.992690 | 0.240579 | 0.204000 | 0.202509 | 0.641544 | 0.500000 | 0.001584 | 0.000052 | 0.202509 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.996678 | 0.154418 | 0.131000 | 0.130565 | 0.411781 | 0.500000 | 0.002467 | 0.000037 | 0.130565 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.988873 | 0.241513 | 0.205000 | 0.202719 | 0.644035 | 0.500000 | 0.001578 | 0.000068 | 0.230759 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.31 | 0.117208 | 0.100000 | 0.131310 | 0.312554 | 0.500000 | 0.003251 | 0.000025 | 0.131310 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.56 | 0.249772 | 0.212000 | 2.03 | 0.666058 | 0.500000 | 0.001525 | 0.001363 | 4.65 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.40 | 0.394623 | 0.500000 | 0.002575 | 0.000900 | 3.07 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 9.46 | 0.252367 | 0.215000 | 2.03 | 0.672979 | 0.500000 | 0.001510 | 0.001352 | 4.61 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.56 | 0.133120 | 0.113000 | 1.31 | 0.354987 | 0.500000 | 0.002862 | 0.000821 | 2.80 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.07 | 0.222363 | 0.189000 | 0.202988 | 0.592968 | 0.500000 | 0.001713 | 0.000170 | 0.578572 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.06 | 0.145650 | 0.124000 | 0.131028 | 0.388399 | 0.500000 | 0.002616 | 0.000111 | 0.379739 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.07 | 0.222457 | 0.189000 | 0.202907 | 0.593219 | 0.500000 | 0.001713 | 0.000169 | 0.575211 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.24 | 0.124440 | 0.106000 | 0.131099 | 0.331841 | 0.500000 | 0.003062 | 0.000105 | 0.358997 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16286.97 | 0.000142 | 328.33 |
CORE_MID VAV BOX REHEAT COIL | 364986.58 | 0.003193 | 8400.98 |
CORE_TOP VAV BOX REHEAT COIL | 60662.91 | 0.000531 | 1603.10 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5903.52 | 0.000052 | 147.06 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4177.05 | 0.000037 | 107.97 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7759.18 | 0.000068 | 205.02 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2807.16 | 0.000025 | 63.72 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 155767.50 | 0.001363 | 4109.95 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 102838.26 | 0.000900 | 2713.32 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 154500.63 | 0.001352 | 4076.55 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 93809.89 | 0.000821 | 2475.34 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19383.41 | 0.000170 | 511.30 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12721.51 | 0.000111 | 335.57 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19271.08 | 0.000169 | 508.34 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12028.15 | 0.000105 | 317.29 |
VAV_BOT WITH REHEAT HEATING COIL | 14380.68 | 0.000126 | 255.32 |
VAV_MID WITH REHEAT HEATING COIL | 60458.69 | 0.000529 | 1093.54 |
VAV_TOP WITH REHEAT HEATING COIL | 4866.79 | 0.000043 | 88.39 |
CAV_BAS HEATING COIL | 237617.72 | 0.002079 | 5445.91 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.91 | 2.29 | 9.82 | 2.29 | 9.01 | 9.01 | 0.300000 | 0.253814 | 9.01 |
VAV_MID WITH REHEAT | 46.54 | 22.83 | 93.08 | 25.90 | 84.34 | 84.34 | 0.300000 | 0.307087 | 84.34 |
VAV_TOP WITH REHEAT | 4.81 | 2.29 | 9.63 | 3.70 | 9.25 | 9.25 | 0.300000 | 0.399640 | 9.25 |
CAV_BAS | 5.18 | 5.18 | 5.18 | 5.18 | 5.18 | 5.18 | 1.00 | 1.00 | 5.18 |
AIRLOOP DATACENTER BASEMENT | 21.28 | 21.28 | 21.28 | 21.28 | 21.28 | 21.28 | 1.00 | 0.999990 | 21.28 |
AIRLOOP DATACENTER BOT | 0.462941 | 0.462941 | 0.462941 | 0.462941 | 0.462941 | 0.462941 | 1.00 | 1.00 | 0.462941 |
AIRLOOP DATACENTER MID | 4.42 | 4.42 | 4.42 | 4.42 | 4.42 | 4.42 | 1.00 | 1.00 | 4.42 |
AIRLOOP DATACENTER TOP | 0.450710 | 0.450710 | 0.450710 | 0.450710 | 0.450710 | 0.450710 | 1.00 | 1.00 | 0.450710 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.01 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 84.34 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.25 | |
CAV_BAS_OA_CONTROLLER | 5.18 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.28 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.462941 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.42 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.450710 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.03 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 20.31 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.03 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.13 | 6.67 | 11.05 | 0.010878 | 0.008500 | 232535.92 | 0.006650 | 9.01 |
VAV_MID WITH REHEAT COOLING COIL | 26.31 | 6.67 | 11.05 | 0.011185 | 0.008500 | 2274537.60 | 0.065051 | 84.34 |
VAV_TOP WITH REHEAT COOLING COIL | 25.96 | 6.67 | 11.05 | 0.010833 | 0.008500 | 235481.47 | 0.006735 | 9.25 |
CAV_BAS COOLING COIL | 25.08 | 6.67 | 11.42 | 0.010888 | 0.008500 | 124671.51 | 0.003566 | 5.18 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.01 |
VAV_MID WITH REHEAT FAN | 84.34 |
VAV_TOP WITH REHEAT FAN | 9.25 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006650 | 0.000072 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000126 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.065051 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.000529 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006735 | 0.000071 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000043 | |
CAV_BAS_COOLC_CONTROLLER | 0.003566 | 0.000134 |
CAV_BAS_HEATC_CONTROLLER | 0.002079 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.18 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.28 | 433606.52 | 311537.73 | 0.010619 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.462941 | 9467.70 | 6784.62 | 0.000232 |
AIRLOOP DATACENTER MID COOLING COIL | 4.42 | 90557.68 | 64802.78 | 0.002218 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.450710 | 9231.48 | 6610.10 | 0.000226 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.28 | 21.28 | 21.28 | 21.28 | 433606.52 | 433606.52 | 12800.94 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.462941 | 0.462941 | 0.462941 | 0.462941 | 9467.70 | 9467.70 | 591.35 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.42 | 4.42 | 4.42 | 4.42 | 90557.68 | 90557.68 | 5913.50 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.450710 | 0.450710 | 0.450710 | 0.450710 | 9231.48 | 9231.48 | 591.35 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.28 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.462941 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.42 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.450710 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.28 | 433606.52 | 0.010619 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.462941 | 9467.70 | 0.000232 |
AIRLOOP DATACENTER MID HEATING COIL | 4.42 | 90557.68 | 0.002218 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.450710 | 9231.48 | 0.000226 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 12800.94 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 591.35 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 5913.50 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 591.35 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000037 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.082002 | 13255.91 | |
HEATSYS1 PUMP | 0.011812 | 3522.15 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.082002 | 9.84 |
HEATSYS1 | 0.011812 | 1.42 |
COOLSYS1_SUPPLY | 0.082002 | 9.84 |
SINGLE WATER PLANT LOOP | 0.013295 | 1.60 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.082002 | 0.082002 | 344204.86 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1350227.70 | 1350227.70 | 0.011812 |
CENTRAL BOILER | 547627.22 | 537059.79 | 0.013295 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.041001 | 4588.76 |
COOLSYS1 CHILLER2 PUMP | 0.041001 | 4588.76 |
PLANT CIRC PUMP | 0.013295 | 3357.24 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.082002 | 0.041357 | 1449593.52 | 1456468.99 | 0.072075 |
COOLSYS1 CHILLER2 | 0.082002 | 0.041357 | 1449593.52 | 1456468.99 | 0.072075 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013295 | 139666.47 | 59268.19 | 69833.23 | 7004.20 | 21414.62 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.144151 | 17.30 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.144151 | 35335.12 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 55.77 | 1728042.77 | 11.15 | 216005.35 |
TOWERWATERSYS COOLTOWER 2 | 55.77 | 1728042.77 | 11.15 | 216005.35 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.074862 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.229 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.229 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2988E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3001E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4566E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4576E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7183E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7190E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6123E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6128E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3271E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4056E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4797E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5453E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7360E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7877E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6259E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6600E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0846E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1999E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.7784E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3272E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5571E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3481E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8968E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0048E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3328E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4327E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4858E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5742E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7417E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8093E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6263E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6610E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2988E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3002E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4566E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4578E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7182E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7191E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6122E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6127E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5360E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6636E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3688E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4980E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1974E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2667E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7571E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7807E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9434E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8460E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6870E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6665E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7504E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5037E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0167E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.1262E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5081E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5637E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3343E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3752E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1769E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1940E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7572E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7811E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5631E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5644E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3492E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3502E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1951E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1958E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6123E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6128E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5922E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6638E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3730E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4300E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2135E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2538E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6263E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6611E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3829E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2284E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8525E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.4206E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6320E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.3573E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8968E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0045E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5901E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6609E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3703E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4245E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2091E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2403E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6260E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6601E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5630E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5642E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3491E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3500E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1950E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1956E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6123E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6128E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0356E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0934E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7661E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8081E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7218E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7372E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7572E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7811E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1340E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5489E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7243E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3143E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9284E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1978E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0167E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1262E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0579E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1603E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7943E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8932E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7409E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8021E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7570E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7806E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5713E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.7652E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.1075E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.9575E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.3053E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.6231E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.5538E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7566E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7079E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6862E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4226E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4675E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4681E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2597E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6430E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7769E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0064E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9796E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4023E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5856E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.1524E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1956E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.5538E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7563E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.7897E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2724E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3291E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9751E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5435E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8445E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6430E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7769E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5829E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.7753E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.1214E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.9687E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.3192E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.6321E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.5614E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7605E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7126E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6905E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4279E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4716E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4758E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2645E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6507E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7808E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0070E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9818E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4030E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5874E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.1559E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1977E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.5614E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7602E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.7924E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2757E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3320E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9780E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5494E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8482E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6507E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7808E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 71831.33511 | 71831.33511 | 5.17625 | 5.17625 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 8.70000 | 6.99286E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 76701.62669 | 76701.62669 | 5.52726 | 5.52726 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 723033.53914 | 723033.53914 | 52.08902 | 52.08902 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 202592.28686 | 202592.28686 | 8.52716 | 10.77825 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 71325.66369 | 71325.66369 | 5.18839 | 5.18839 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.20000 | 1.71672E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 42524.82651 | 42524.82651 | 1.80355 | 1.80355 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13645.86408 | 13645.86408 | 0.99269 | 0.99269 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.92700 | 1.71648E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 3868.08183 | 3868.08183 | 0.16599 | 0.16599 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 13700.76257 | 13700.76257 | 0.99668 | 0.99668 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 30.27433 | 1.71616E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2864.76356 | 2864.76356 | 0.12132 | 0.12132 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 13593.38899 | 13593.38899 | 0.98887 | 0.98887 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 5439.59257 | 5439.59257 | 0.23076 | 0.23076 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18050.50127 | 18050.50127 | 1.31310 | 1.31310 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1487.83268 | 1487.83268 | 6.29564E-002 | 8.72129E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 131424.12456 | 131424.12456 | 9.56155 | 9.56155 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 31.81533 | 1.71646E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 109049.15679 | 109049.15679 | 4.64687 | 4.64687 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 142951.35445 | 142951.35445 | 10.40013 | 10.40013 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 30.46417 | 1.71620E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 71992.58889 | 71992.58889 | 3.06807 | 3.06807 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 130075.50215 | 130075.50215 | 9.46343 | 9.46343 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 108163.24749 | 108163.24749 | 4.60899 | 4.60899 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 158913.47794 | 158913.47794 | 11.56138 | 11.56138 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 32.15033 | 1.71652E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 65679.02487 | 65679.02487 | 2.79817 | 2.79817 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14761.89332 | 14761.89332 | 1.07401 | 1.07401 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 13566.35799 | 13566.35799 | 0.57857 | 0.57857 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14523.66749 | 14523.66749 | 1.05668 | 1.05668 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 30.65400 | 1.71624E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 8903.56150 | 8903.56150 | 0.37974 | 0.37974 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 14755.96001 | 14755.96001 | 1.07358 | 1.07358 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.20000 | 1.71672E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 13487.83738 | 13487.83738 | 0.57521 | 0.57521 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16999.16059 | 16999.16059 | 1.23678 | 1.23678 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8418.82023 | 8418.82023 | 0.35900 | 0.35900 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8068.80577 | 8068.80577 | 0.46294 | 0.46294 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.75450 | 1.71626E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76969.51320 | 76969.51320 | 4.41610 | 4.41610 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.75450 | 1.71626E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7855.58673 | 7855.58673 | 0.45071 | 0.45071 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.92200 | 1.71629E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 8.70000 | 6.99286E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370977.52053 | 370977.52053 | 21.28413 | 21.28413 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.10300 | 1.71556E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 8.70000 | 6.99286E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 138966.22 | 9.00894 | 9.00894 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 8326.78 | 1.68042 | 1.68042 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1281049.13 | 84.34211 | 84.34211 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 97893.41 | 25.90034 | 25.90034 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 146866.08 | 9.24849 | 9.24849 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 9665.84 | 3.69607 | 3.69607 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
7 | CAV_BAS | Cooling | Sensible | 76594.69 | 5.17625 | 5.17625 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 45400.28 | 1.20016 | 1.20016 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 367284.31 | 21.28433 | 21.28433 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 12800.94 | 0.33839 | 0.33839 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8017.57 | 0.46294 | 0.46294 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 591.35 | 1.56323E-002 | 1.56323E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 76497.85 | 4.41610 | 4.41610 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 5913.50 | 0.15632 | 0.15632 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7808.24 | 0.45071 | 0.45071 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 591.35 | 1.56323E-002 | 1.56323E-002 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.17625 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.52726 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34412 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29300 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61949 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91765 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10717E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.42486E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61949 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16286.97444 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42486E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 328.33262 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 52.08902 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36515 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.14760 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97374 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04340E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.19306E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.14760 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 364986.58454 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.19306E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8400.98095 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.18839 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36660 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31200 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61878 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97759 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.03929E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.30706E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.80355 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 60662.91289 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.30706E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1603.10193 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99269 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24058 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20400 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20251 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64154 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58368E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.16466E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20251 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5903.52021 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.16466E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 147.06396 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99668 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15442 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13100 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13056 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41178 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.46733E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.65426E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13056 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4177.04552 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.65426E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 107.97264 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98887 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24151 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20500 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20272 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64404 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57755E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.78807E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23076 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7759.18298 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.78807E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 205.01746 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31310 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11721 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13131 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31255 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.25064E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.45582E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13131 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2807.15770 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.45582E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 63.72263 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.56155 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24977 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21200 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02705 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66606 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52539E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36272E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.64687 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 155767.50353 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36272E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4109.94616 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.40013 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39462 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57461E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.99674E-004 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.06807 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 102838.26281 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.99674E-004 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2713.32219 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.46343 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25237 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21500 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03464 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67298 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.50971E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35164E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.60899 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 154500.63033 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35164E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4076.55347 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.56138 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13312 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11300 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30644 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35499 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.86208E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.20690E-004 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.79817 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 93809.89344 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.20690E-004 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2475.33894 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07401 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22236 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18900 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20299 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59297 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71342E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69575E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57857 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19383.40911 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69575E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 511.30235 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05668 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14565 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12400 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13103 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38840 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.61586E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.11293E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37974 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12721.50712 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.11293E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 335.56561 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07358 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22246 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.18900 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20291 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59322 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71269E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.68592E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57521 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19271.08386 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.68592E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 508.34283 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23678 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12444 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10600 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13110 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33184 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.06171E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05227E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35900 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12028.14883 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05227E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 317.29432 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46294 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.41610 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45071 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.28413 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.90930 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28659 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.81860 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28659 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.00894 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.00894 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.25381 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 46.53776 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.82614 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 93.07552 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.90034 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 84.34211 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 84.34211 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.30709 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.81472 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28680 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.62945 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.69607 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.24849 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.24849 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.39964 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.17625 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.17625 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.17625 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.17625 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.17625 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.17625 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.28413 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.28413 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.28413 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.28413 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.28433 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.28433 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46294 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46294 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46294 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46294 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46294 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46294 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.41610 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.41610 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.41610 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.41610 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.41610 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.41610 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45071 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45071 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45071 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45071 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45071 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45071 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.00894 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 84.34211 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.24849 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.17625 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.28433 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46294 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.41610 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45071 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.00894 |
286 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.13347 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04724 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.08781E-002 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 232535.92036 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.65050E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.00894 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 14380.68481 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25809E-004 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 255.31860 |
298 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.00894 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.65050E-003 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.16022E-005 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.25809E-004 |
302 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 84.34211 |
303 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 20.30600 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.31024 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04821 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.11845E-002 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2274537.60226 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.50515E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 84.34211 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 60458.68517 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.28919E-004 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1093.53684 |
315 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 84.34211 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.50515E-002 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.32021E-006 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.28919E-004 |
319 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.24849 |
320 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.03050 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.96280 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04709 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.08325E-002 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 235481.46622 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.73474E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.24849 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 4866.78725 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.25768E-005 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 88.39476 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.24849 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.73474E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.07066E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.25768E-005 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.17625 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.08448 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42467 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.08880E-002 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 124671.51323 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.56559E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.17625 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 237617.72102 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07878E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5445.91296 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.17625 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.56559E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.33552E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.07878E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.28433 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.28433 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 433606.51648 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 311537.72579 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06190E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.28433 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.28433 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.28433 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.28433 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 433606.51648 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 433606.51648 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 12800.93607 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.28433 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.28433 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 433606.51648 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06190E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 12800.93607 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 3.71524E-005 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46294 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46294 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9467.69941 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6784.61949 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31863E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46294 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46294 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46294 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46294 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9467.69941 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9467.69941 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 591.35022 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46294 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46294 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9467.69941 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31863E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 591.35022 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.41610 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.41610 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 90557.68354 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 64802.77538 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21775E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.41610 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.41610 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.41610 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.41610 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 90557.68354 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 90557.68354 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 5913.50215 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.41610 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.41610 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 90557.68354 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21775E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5913.50215 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45071 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45071 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9231.48213 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6610.10089 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26078E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45071 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45071 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45071 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45071 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9231.48213 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9231.48213 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 591.35022 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45071 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45071 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9231.48213 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26078E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 591.35022 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.20023E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 13255.91319 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.20023E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.84028 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.20023E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.20023E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 344204.86219 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.18124E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.41749 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.18124E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3522.14890 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1350227.69556 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1350227.70000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.18124E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.20023E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.84028 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.10012E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4588.75787 |
453 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.10012E-002 |
454 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4588.75787 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.20023E-002 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.13566E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1449593.52093 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1456468.98500 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.20753E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.20023E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.13566E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1449593.52093 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1456468.98500 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.20753E-002 |
465 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.32947E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.59536 |
467 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.32947E-002 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3357.23822 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.32947E-002 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59268.19053 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21414.62342 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 547627.22210 |
476 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 537059.79000 |
477 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.32947E-002 |
478 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
479 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
480 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
482 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
483 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14415 |
484 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.29806 |
485 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14415 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 35335.12425 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 55.77454 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1728042.76944 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.15491 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 216005.34618 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 55.77454 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1728042.76944 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.15491 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 216005.34618 |
495 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.48625E-002 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.48625E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15443.23 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 345819.86 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 57495.63 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5591.22 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3955.47 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7353.87 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2660.08 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 147591.82 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 97440.12 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 146391.67 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 88887.17 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18365.16 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12053.18 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18258.76 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11396.37 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 12823.26 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 55756.64 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 4521.83 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 194957.55 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 241615.59 | 166620.09 | 74995.50 | 0.69 | 36203.54 | 367.20 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2303392.90 | 1577646.77 | 725746.13 | 0.68 | 341965.44 | 3468.40 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 246767.88 | 170516.11 | 76251.76 | 0.69 | 37156.37 | 376.86 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 133990.29 | 93625.49 | 40364.80 | 0.70 | 20046.61 | 203.32 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.47 | 22.07 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.47 | 22.07 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2065445056 | 0.1951860523 | Pass | Pass | 2.8073522605 | 16.5789121220 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2971945467 | 0.2205540201 | Pass | Pass | 0.3293323218 | 0.4737967026 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1707465700 | 0.1889763733 | Pass | Pass | 0.2738375671 | 0.4440502929 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1411406213 | 0.1875432688 | Pass | Pass | 0.2382399293 | 0.4236851926 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2508468196 | 0.2002185384 | Pass | Pass | 0.3165813337 | 0.4622426766 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3628542484 | 0.3554698794 | Pass | Pass | 0.3634472627 | 0.5307140861 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4268737229 | 0.4734802918 | Pass | Pass | 0.3830044407 | 0.5576809626 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3207424548 | 0.2935063140 | Pass | Pass | 0.3609351787 | 0.5148770739 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1594777382 | 0.1832814468 | Pass | Pass | 0.2731866325 | 0.4422222486 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2718939014 | 0.3310284880 | Pass | Pass | 0.3133597680 | 0.4941223744 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3517408391 | 0.4872478318 | Pass | Pass | 0.3307217322 | 0.5215289333 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1892427630 | 0.2204040630 | Pass | Pass | 0.2743420124 | 0.4414305467 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1406095541 | 0.1718698919 | Pass | Pass | 0.2375618261 | 0.4221209089 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2437423065 | 0.3054292974 | Pass | Pass | 0.2816072881 | 0.5051864191 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3163869209 | 0.4928238240 | Pass | Pass | 0.2839792118 | 0.5080224315 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1686496321 | 0.2142988454 | Pass | Pass | 0.2409990134 | 0.4208221021 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.5059795343E-002 | 4.3682725713E-002 | Pass | Pass | 0.3798435526 | 0.6302696551 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.0482331565E-002 | 4.1325414943E-002 | Pass | Pass | 0.3279337434 | 0.5571981951 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.3689286033E-002 | 6.5992147590E-002 | Pass | Pass | 1.2565544397 | 10.8123722467 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.9562636263E-004 | 2.7748582226E-004 | Pass | Pass | 2.0729318589E-003 | 1.7407052164E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.0219701638E-006 | 6.9006901114E-006 | Pass | Pass | 2.4149322272E-003 | 1.8510632816E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.3802787942E-006 | 5.7951044889E-006 | Pass | Pass | 4.8828372976E-003 | 2.9951286185E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.8138340519E-004 | 1.8938732217E-004 | Pass | Pass | 4.7859715322E-005 | 1.0152382846E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5324.70 | -93.9 | 0.00 | -7019.3 | 38992.06 | 37203.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.504_SHGC_EAST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.504_SHGC_WEST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.865 | 0.230 | 0.253 | |||||||||||||||||
North Total or Average | 1390.74 | 2.865 | 0.230 | 0.253 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.865 | 0.230 | 0.253 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.19 | 0.0000 | Y | 10.56 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.10 | 0.0000 | Y | 6.78 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.92 | 0.0000 | Y | 10.45 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.04 | 0.0000 | Y | 6.77 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.14 | 0.0000 | Y | 105.39 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.07 | 0.0000 | Y | 67.73 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.89 | 0.0000 | Y | 104.43 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.00 | 0.0000 | Y | 67.55 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.14 | 0.0000 | Y | 10.54 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.07 | 0.0000 | Y | 6.77 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.89 | 0.0000 | Y | 10.44 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.00 | 0.0000 | Y | 6.76 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 774.31 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 41.82 | 41.82 | 104.19 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.82 | 62.82 | 11.67 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.82 | 46.78 | 233.52 | |
Exterior Lighting Total | 40855.88 | 349.39 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2858395.19 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1350227.70 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1456468.99 | 6.28 | 1275082.08 | 5.58 | 6.47 | 22.07 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1456468.99 | 6.28 | 1275082.08 | 5.58 | 6.47 | 22.07 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 537059.79 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1728042.77 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1728042.77 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 232535.92 | 241615.59 | 166620.09 | 74995.50 | 0.69 | - | 36203.54 | 367.20 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2274537.60 | 2303392.90 | 1577646.77 | 725746.13 | 0.68 | - | 341965.44 | 3468.40 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 235481.47 | 246767.88 | 170516.11 | 76251.76 | 0.69 | - | 37156.37 | 376.86 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 124671.51 | 133990.29 | 93625.49 | 40364.80 | 0.70 | - | 20046.61 | 203.32 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 433606.52 | 311537.73 | 122068.79 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9467.70 | 6784.62 | 2683.08 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 90557.68 | 64802.78 | 25754.91 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9231.48 | 6610.10 | 2621.38 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16286.97 | 15443.23 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 364986.58 | 345819.86 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 60662.91 | 57495.63 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5903.52 | 5591.22 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4177.05 | 3955.47 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7759.18 | 7353.87 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 2807.16 | 2660.08 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 155767.50 | 147591.82 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 102838.26 | 97440.12 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 154500.63 | 146391.67 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 93809.89 | 88887.17 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19383.41 | 18365.16 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12721.51 | 12053.18 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19271.08 | 18258.76 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12028.15 | 11396.37 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 14380.68 | 12823.26 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 60458.69 | 55756.64 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 4866.79 | 4521.83 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 237617.72 | 194957.55 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 433606.52 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9467.70 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 90557.68 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9231.48 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 12800.94 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 591.35 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 5913.50 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 591.35 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.01 | 19467.83 | 2160.95 | 1.00 | 1.12 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 84.34 | 182258.81 | 2160.95 | 1.00 | 1.08 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.25 | 19985.50 | 2160.95 | 1.00 | 1.12 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.18 | 8777.13 | 1695.65 | 1.00 | 1.16 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.28 | 35288.85 | 1657.97 | 1.00 | 1.13 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 518.54 | 1120.11 | 1.00 | 1.64 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.42 | 4946.51 | 1120.11 | 1.00 | 1.16 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 504.84 | 1120.11 | 1.00 | 1.65 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.082002 | 13255.91 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.011812 | 3522.15 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041001 | 4588.76 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041001 | 4588.76 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013295 | 3357.24 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.144151 | 35335.12 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 71831.34 | 71831.34 | 25.84 | 5.176 | 5.176 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00899 | 28.24 | 0.01716 | 1.200 | 0.00 |
CORE_BOTTOM | 76701.63 | 76701.63 | 30.73 | 5.527 | 5.527 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 28.24 | 0.01716 | 1.078 | 0.00 |
CORE_MID | 723033.54 | 723033.54 | 289.66 | 52.089 | 52.089 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.24 | 0.01716 | 10.778 | 0.00 |
CORE_TOP | 71325.66 | 71325.66 | 28.57 | 5.188 | 5.188 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00893 | 33.20 | 0.01717 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13645.86 | 13645.86 | 43.54 | 0.993 | 0.993 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00899 | 31.93 | 0.01716 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 13700.76 | 13700.76 | 67.83 | 0.997 | 0.997 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00882 | 30.27 | 0.01716 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 13593.39 | 13593.39 | 43.37 | 0.989 | 0.989 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00899 | 33.20 | 0.01717 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18050.50 | 18050.50 | 89.37 | 1.313 | 1.313 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00874 | 32.26 | 0.01717 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 131424.12 | 131424.12 | 419.33 | 9.562 | 9.562 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00928 | 31.82 | 0.01716 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 142951.35 | 142951.35 | 707.77 | 10.400 | 10.400 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00898 | 30.46 | 0.01716 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 130075.50 | 130075.50 | 415.02 | 9.463 | 9.463 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00928 | 33.20 | 0.01717 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 158913.48 | 158913.48 | 786.80 | 11.561 | 11.561 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00893 | 32.15 | 0.01717 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14761.89 | 14761.89 | 47.10 | 1.074 | 1.074 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00929 | 32.26 | 0.01717 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14523.67 | 14523.67 | 71.91 | 1.057 | 1.057 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00904 | 30.65 | 0.01716 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14755.96 | 14755.96 | 47.08 | 1.074 | 1.074 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00929 | 33.20 | 0.01717 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16999.16 | 16999.16 | 84.16 | 1.237 | 1.237 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00896 | 32.26 | 0.01717 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8068.81 | 8068.81 | 222.88 | 0.463 | 0.463 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 30.75 | 0.01716 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76969.51 | 76969.51 | 2126.07 | 4.416 | 4.416 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 30.75 | 0.01716 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7855.59 | 7855.59 | 216.99 | 0.451 | 0.451 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 30.92 | 0.01716 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370977.52 | 370977.52 | 473.38 | 21.284 | 21.284 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 27.10 | 0.01716 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.10 | 0.00699 | 8.70 | 0.00699 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.50 | 0.00699 | 8.70 | 0.00699 | 1.078 | 0.00 | |
CORE_MID | 202592.29 | 202592.29 | 81.16 | 8.527 | 10.778 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 10.778 | 0.00 |
CORE_TOP | 42524.83 | 42524.83 | 17.04 | 1.804 | 1.804 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 3868.08 | 3868.08 | 12.34 | 0.166 | 0.166 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00771 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2864.76 | 2864.76 | 14.18 | 0.121 | 0.121 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00770 | 8.70 | 0.00699 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 5439.59 | 5439.59 | 17.36 | 0.231 | 0.231 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1487.83 | 1487.83 | 7.37 | 0.063 | 0.087 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | 8.70 | 0.00699 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 109049.16 | 109049.16 | 347.94 | 4.647 | 4.647 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | 8.70 | 0.00699 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 71992.59 | 71992.59 | 356.44 | 3.068 | 3.068 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | 8.70 | 0.00699 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 108163.25 | 108163.25 | 345.11 | 4.609 | 4.609 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | 8.70 | 0.00699 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 65679.02 | 65679.02 | 325.18 | 2.798 | 2.798 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 8.70 | 0.00699 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13566.36 | 13566.36 | 43.29 | 0.579 | 0.579 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 8903.56 | 8903.56 | 44.08 | 0.380 | 0.380 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13487.84 | 13487.84 | 43.03 | 0.575 | 0.575 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 8.70 | 0.00699 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8418.82 | 8418.82 | 41.68 | 0.359 | 0.359 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | 8.70 | 0.00699 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 8.70 | 0.00699 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.77 | 0.00793 | 8.70 | 0.00699 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.03 | 0.00708 | 8.70 | 0.00699 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 8.70 | 0.00699 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.01 | 9.01 | 1.68 | 1.68 | 9.0089 | 2.2866 | 9.0089 | 0.2538 | 0.3000 |
VAV_MID WITH REHEAT | 84.34 | 84.34 | 25.90 | 25.90 | 84.3421 | 25.9003 | 84.3421 | 0.3071 | 0.3000 |
VAV_TOP WITH REHEAT | 9.25 | 9.25 | 3.70 | 3.70 | 9.2485 | 3.6961 | 9.2485 | 0.3996 | 0.3000 |
CAV_BAS | 5.18 | 5.18 | 1.20 | 1.20 | 5.1762 | 5.1762 | 5.1762 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.28 | 21.28 | 0.34 | 0.34 | 21.2843 | 21.2841 | 21.2843 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.46 | 0.46 | 0.02 | 0.02 | 0.4629 | 0.4629 | 0.4629 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.42 | 4.42 | 0.16 | 0.16 | 4.4161 | 4.4161 | 4.4161 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4507 | 0.4507 | 0.4507 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16286.974 | 16286.974 | 1.619488 | 0.00014249 | 328.333 | 1/21 00:10:00 | 1/21 00:10:00 | 16286.97 | 16286.97 | 1.619488 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 16347.03 | 16347.03 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 364986.585 | 364986.585 | 16.147597 | 0.00319306 | 8400.981 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 364986.58 | 364986.58 | 16.147597 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 202592.29 | 0.00 | 366197.17 | 366197.17 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 60662.913 | 60662.913 | 1.803553 | 0.00053071 | 1603.102 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60662.91 | 60662.91 | 1.803553 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 42524.83 | 0.00 | 60885.33 | 60885.33 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5903.520 | 5903.520 | 0.202509 | 0.00005165 | 147.064 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5903.52 | 5903.52 | 0.202509 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00771112 | 49.8148 | 3868.08 | 0.00 | 5921.96 | 5921.96 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4177.046 | 4177.046 | 0.130565 | 0.00003654 | 107.973 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4177.05 | 4177.05 | 0.130565 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00770089 | 49.7497 | 2864.76 | 0.00 | 4189.86 | 4189.86 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7759.183 | 7759.183 | 0.230759 | 0.00006788 | 205.017 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7759.18 | 7759.18 | 0.230759 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00776459 | 50.1561 | 5439.59 | 0.00 | 7787.42 | 7787.42 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2807.158 | 2807.158 | 0.131310 | 0.00002456 | 63.723 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2807.16 | 2807.16 | 0.131310 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00750913 | 48.5253 | 1487.83 | 0.00 | 2816.72 | 2816.72 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 155767.504 | 155767.504 | 4.646866 | 0.00136272 | 4109.946 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 155767.50 | 155767.50 | 4.646866 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00786075 | 50.7696 | 109049.16 | 0.00 | 156292.57 | 156292.57 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 102838.263 | 102838.263 | 3.068073 | 0.00089967 | 2713.322 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 102838.26 | 102838.26 | 3.068073 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00786241 | 50.7802 | 71992.59 | 0.00 | 103184.34 | 103184.34 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 154500.630 | 154500.630 | 4.608989 | 0.00135164 | 4076.553 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 154500.63 | 154500.63 | 4.608989 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00785905 | 50.7588 | 108163.25 | 0.00 | 155021.67 | 155021.67 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 93809.893 | 93809.893 | 2.798166 | 0.00082069 | 2475.339 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 93809.89 | 93809.89 | 2.798166 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00784108 | 50.6443 | 65679.02 | 0.00 | 94127.21 | 94127.21 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19383.409 | 19383.409 | 0.578572 | 0.00016957 | 511.302 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19383.41 | 19383.41 | 0.578572 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788253 | 50.9085 | 13566.36 | 0.00 | 19447.80 | 19447.80 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12721.507 | 12721.507 | 0.379739 | 0.00011129 | 335.566 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12721.51 | 12721.51 | 0.379739 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788203 | 50.9053 | 8903.56 | 0.00 | 12763.72 | 12763.72 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19271.084 | 19271.084 | 0.575211 | 0.00016859 | 508.343 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19271.08 | 19271.08 | 0.575211 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00788167 | 50.9030 | 13487.84 | 0.00 | 19335.13 | 19335.13 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12028.149 | 12028.149 | 0.358997 | 0.00010523 | 317.294 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12028.15 | 12028.15 | 0.358997 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00787156 | 50.8386 | 8418.82 | 0.00 | 12068.19 | 12068.19 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 232535.920 | -999.000 | 9.008936 | 0.00665050 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 232535.92 | 165129.80 | 9.008936 | 26.13 | 19.04 | 0.01087815 | 11.05 | 11.05 | 0.00850000 | 33.07 | 0.01716695 | 25.29 | 22.5387 | 24.00 | 0.00894137 | 48.0460 | 118547.31 | 0.00 | 232893.10 | 163102.76 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 14380.685 | 14380.685 | 2.702681 | 0.00012581 | 255.319 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14380.68 | 14380.68 | 2.702681 | 8.40 | 8.40 | 0.00705484 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 75.1291 | 21.64 | 0.00738516 | 45.9035 | 13655.89 | 0.00 | 15525.95 | 15525.95 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2274537.602 | -999.000 | 84.342111 | 0.06505149 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2274537.60 | 1562917.32 | 84.342111 | 26.31 | 19.33 | 0.01118451 | 11.05 | 11.05 | 0.00850000 | 32.93 | 0.01716670 | 25.26 | 24.0758 | 24.00 | 0.00909553 | 48.8639 | 1078470.36 | 0.00 | 2277973.32 | 1546835.67 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 60458.685 | 60458.685 | 25.302633 | 0.00052892 | 1093.537 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 60458.69 | 60458.69 | 25.302633 | 10.82 | 9.85 | 0.00716118 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 80.2525 | 19.60 | 0.00772361 | 54.4048 | 293187.79 | 0.00 | 67505.54 | 67505.54 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 235481.466 | -999.000 | 9.248493 | 0.00673474 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 235481.47 | 167593.98 | 9.248493 | 25.96 | 18.95 | 0.01083253 | 11.05 | 11.05 | 0.00850000 | 32.93 | 0.01716670 | 25.26 | 21.9549 | 24.00 | 0.00904659 | 48.6050 | 126903.68 | 0.00 | 235847.05 | 165487.95 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 4866.787 | 4866.787 | 2.774548 | 0.00004258 | 88.395 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4866.79 | 4866.79 | 2.774548 | 11.35 | 10.15 | 0.00722091 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 73.1831 | 19.46 | 0.00775545 | 55.1111 | 34187.79 | 0.00 | 5474.62 | 5474.62 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 124671.513 | -999.000 | 5.176249 | 0.00356559 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 124671.51 | 86493.68 | 5.176249 | 25.08 | 18.71 | 0.01088800 | 11.42 | 11.42 | 0.00850000 | 28.67 | 0.01715859 | 24.15 | 23.1858 | 24.00 | 0.00898702 | 48.2871 | 70920.90 | 0.00 | 124889.95 | 85990.84 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 237617.721 | 237617.721 | 5.176249 | 0.00207878 | 5445.913 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 237617.72 | 237617.72 | 5.176249 | 2.02 | 2.02 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 23.1858 | 25.10 | 0.00699286 | 35.2826 | 0.00 | 0.00 | 206412.18 | 206412.18 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 433606.516 | 311537.726 | 21.284331 | 0.01061900 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 406274.74 | 395758.01 | -999.0 | 28.50 | 18.07 | 0.00867966 | 12.80 | 12.09 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | -999.0000 | 27.00 | 0.00854237 | 38.4373 | 370476.39 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9467.699 | 6784.619 | 0.462941 | 0.00023186 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8876.01 | 8393.38 | -999.0 | 28.08 | 18.09 | 0.00887923 | 12.80 | 12.09 | 0.00850000 | 30.92 | 0.01716288 | 24.74 | -999.0000 | 27.00 | 0.00858971 | 38.6452 | 8068.20 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90557.684 | 64802.775 | 4.416100 | 0.00221775 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 84936.87 | 80110.91 | -999.0 | 28.08 | 18.11 | 0.00889745 | 12.80 | 12.09 | 0.00850000 | 30.92 | 0.01716288 | 24.74 | -999.0000 | 27.00 | 0.00859403 | 38.6646 | 76946.39 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9231.482 | 6610.101 | 0.450710 | 0.00022608 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8656.77 | 8174.17 | -999.0 | 28.08 | 18.10 | 0.00888946 | 12.80 | 12.09 | 0.00850000 | 30.92 | 0.01716288 | 24.74 | -999.0000 | 27.00 | 0.00859219 | 38.6563 | 7855.59 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 433606.516 | 433606.516 | 21.284331 | 0.01061900 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 433606.52 | 433606.52 | 21.284331 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 1.5899 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9467.699 | 9467.699 | 0.462941 | 0.00023186 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9467.70 | 9467.70 | 0.462941 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.3767 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90557.684 | 90557.684 | 4.416100 | 0.00221775 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 90557.68 | 90557.68 | 4.416100 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.5399 | 24.77 | 0.00792917 | 40.7380 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9231.482 | 9231.482 | 0.450710 | 0.00022608 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9231.48 | 9231.48 | 0.450710 | 8.70 | 8.70 | 0.00699286 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.4684 | 24.03 | 0.00707501 | 38.0536 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 12800.936 | 12800.936 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 12800.94 | 12800.94 | 21.284331 | 0.14 | 0.14 | 0.00847604 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 1.5899 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 591.35 | 591.35 | 0.462941 | 0.29 | 0.29 | 0.00844911 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.3767 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 5913.502 | 5913.502 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 5913.50 | 5913.50 | 4.416100 | 0.31 | 0.31 | 0.00789603 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.5399 | 24.77 | 0.00792917 | 40.7380 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 591.35 | 591.35 | 0.450710 | 0.30 | 0.30 | 0.00707216 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 3.4684 | 24.03 | 0.00707501 | 38.0536 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16286.974 | 16286.974 | 1.619488 | 0.00014249 | 328.333 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 1.1824 | 1.206239 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 16286.97 | 16286.97 | 1.0000 | 1.94782171 | 1.619488 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.14247102 | 60.00 | 32.22 | 27.78 | 0.000 | 16286.97 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 0.00 | 0.00 | 16347.03 | 16347.03 | 1.94782171 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 364986.585 | 364986.585 | 16.147597 | 0.00319306 | 8400.981 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 26.4982 | 27.031484 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 364986.58 | 364986.58 | 1.0000 | 19.42134388 | 16.147597 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 3.19273614 | 60.00 | 32.22 | 27.78 | 0.000 | 364986.58 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 202592.29 | 0.00 | 366197.17 | 366197.17 | 19.42134388 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.29 | 18.47 | 0.00800000 | 51915.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 60662.913 | 60662.913 | 1.803553 | 0.00053071 | 1603.102 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 4.4042 | 4.492791 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 60662.91 | 60662.91 | 1.0000 | 2.16920329 | 1.803553 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.53065149 | 60.00 | 32.22 | 27.78 | 0.000 | 60662.91 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 42524.83 | 0.00 | 60885.33 | 60885.33 | 2.16920329 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.33 | 21.28 | 0.00800000 | 61127.9 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5903.520 | 5903.520 | 0.202509 | 0.00005165 | 147.064 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 0.4286 | 0.437224 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 5903.52 | 5903.52 | 1.0000 | 0.24356525 | 0.202509 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.05164130 | 60.00 | 32.22 | 27.78 | 0.000 | 5903.52 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 21.00 | 0.00771112 | 21.00 | 0.00771112 | 49.8148 | 3868.08 | 0.00 | 5921.96 | 5921.96 | 0.24356525 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.64 | 20.17 | 0.00800000 | 57373.5 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4177.046 | 4177.046 | 0.130565 | 0.00003654 | 107.973 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 0.3033 | 0.309359 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4177.05 | 4177.05 | 1.0000 | 0.15703542 | 0.130565 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03653889 | 60.00 | 32.22 | 27.78 | 0.000 | 4177.05 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.87 | 0.00770089 | 21.00 | 0.00770089 | 49.7497 | 2864.76 | 0.00 | 4189.86 | 4189.86 | 0.15703542 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.97 | 20.87 | 0.00800000 | 59740.8 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7759.183 | 7759.183 | 0.230759 | 0.00006788 | 205.017 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 0.5633 | 0.574657 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7759.18 | 7759.18 | 1.0000 | 0.27754274 | 0.230759 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.06787379 | 60.00 | 32.22 | 27.78 | 0.000 | 7759.18 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00776459 | 21.00 | 0.00776459 | 50.1561 | 5439.59 | 0.00 | 7787.42 | 7787.42 | 0.27754274 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.32 | 21.28 | 0.00800000 | 61118.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2807.158 | 2807.158 | 0.131310 | 0.00002456 | 63.723 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 0.2038 | 0.207903 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2807.16 | 2807.16 | 1.0000 | 0.15793122 | 0.131310 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.02455573 | 60.00 | 32.22 | 27.78 | 0.000 | 2807.16 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.88 | 0.00750913 | 21.00 | 0.00750913 | 48.5253 | 1487.83 | 0.00 | 2816.72 | 2816.72 | 0.15793122 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.29 | 18.13 | 0.00800000 | 50894.9 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 155767.504 | 155767.504 | 4.646866 | 0.00136272 | 4109.946 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 11.3088 | 11.536388 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 155767.50 | 155767.50 | 1.0000 | 5.58896681 | 4.646866 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.36258306 | 60.00 | 32.22 | 27.78 | 0.000 | 155767.50 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00786075 | 21.00 | 0.00786075 | 50.7696 | 109049.16 | 0.00 | 156292.57 | 156292.57 | 5.58896681 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61024.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 102838.263 | 102838.263 | 3.068073 | 0.00089967 | 2713.322 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 7.4661 | 7.616364 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 102838.26 | 102838.26 | 1.0000 | 3.69009035 | 3.068073 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.89958221 | 60.00 | 32.22 | 27.78 | 0.000 | 102838.26 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00786241 | 21.00 | 0.00786241 | 50.7802 | 71992.59 | 0.00 | 103184.34 | 103184.34 | 3.69009035 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61022.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 154500.630 | 154500.630 | 4.608989 | 0.00135164 | 4076.553 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 11.2168 | 11.442561 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 154500.63 | 154500.63 | 1.0000 | 5.54341045 | 4.608989 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.35150103 | 60.00 | 32.22 | 27.78 | 0.000 | 154500.63 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00785905 | 21.00 | 0.00785905 | 50.7588 | 108163.25 | 0.00 | 155021.67 | 155021.67 | 5.54341045 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61024.9 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 93809.893 | 93809.893 | 2.798166 | 0.00082069 | 2475.339 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 6.8106 | 6.947709 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 93809.89 | 93809.89 | 1.0000 | 3.36546359 | 2.798166 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.82060615 | 60.00 | 32.22 | 27.78 | 0.000 | 93809.89 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00784108 | 21.00 | 0.00784108 | 50.6443 | 65679.02 | 0.00 | 94127.21 | 94127.21 | 3.36546359 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61028.4 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19383.409 | 19383.409 | 0.578572 | 0.00016957 | 511.302 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 1.4072 | 1.435566 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19383.41 | 19383.41 | 1.0000 | 0.69587095 | 0.578572 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.16955722 | 60.00 | 32.22 | 27.78 | 0.000 | 19383.41 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788253 | 21.00 | 0.00788253 | 50.9085 | 13566.36 | 0.00 | 19447.80 | 19447.80 | 0.69587095 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12721.507 | 12721.507 | 0.379739 | 0.00011129 | 335.566 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 0.9236 | 0.942175 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12721.51 | 12721.51 | 1.0000 | 0.45672651 | 0.379739 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.11128194 | 60.00 | 32.22 | 27.78 | 0.000 | 12721.51 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788203 | 21.00 | 0.00788203 | 50.9053 | 8903.56 | 0.00 | 12763.72 | 12763.72 | 0.45672651 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61005.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19271.084 | 19271.084 | 0.575211 | 0.00016859 | 508.343 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 1.3991 | 1.427247 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19271.08 | 19271.08 | 1.0000 | 0.69182823 | 0.575211 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.16857465 | 60.00 | 32.22 | 27.78 | 0.000 | 19271.08 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788167 | 21.00 | 0.00788167 | 50.9030 | 13487.84 | 0.00 | 19335.13 | 19335.13 | 0.69182823 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.7 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12028.149 | 12028.149 | 0.358997 | 0.00010523 | 317.294 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 0.8732 | 0.890824 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12028.15 | 12028.15 | 1.0000 | 0.43178013 | 0.358997 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.10521676 | 60.00 | 32.22 | 27.78 | 0.000 | 12028.15 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.95 | 0.00787156 | 21.00 | 0.00787156 | 50.8386 | 8418.82 | 0.00 | 12068.19 | 12068.19 | 0.43178013 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61009.7 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 232535.920 | -999.000 | 9.008936 | 0.00665050 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0619 | 1004.8586 | 1.2027 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.008936 | 10.83539783 | 4197.9300 | 999.8980 | 81.99394992 | 15.00 | 6.67 | 8.33 | 2867226.50 | 8.1101 | 8.110134 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 232535.92 | 165129.80 | 1.0000 | 10.83539783 | 9.008936 | 26.13 | 19.04 | 0.01087815 | 53994.0 | 11.05 | 11.05 | 0.00850000 | 32533.3 | 6.64981947 | 6.67 | 15.00 | 8.33 | 19467.830 | 213068.09 | 33.07 | 0.01716695 | 25.29 | 2.03050000 | 22.5387 | 24.00 | 0.00894137 | 24.00 | 0.00894137 | 48.0460 | 118547.31 | 0.00 | 232893.10 | 163102.76 | 10.83539783 | 26.13 | 19.05 | 0.01087815 | 53994.0 | 11.45 | 11.36 | 0.00832447 | 32500.3 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 14380.685 | 14380.685 | 2.702681 | 0.00012581 | 255.319 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.008936 | 10.83539783 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 1.0440 | 1.065056 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14380.68 | 14380.68 | 1.0000 | 3.25061935 | 2.702681 | 8.40 | 8.40 | 0.00705484 | 26191.9 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.12579567 | 60.00 | 32.22 | 27.78 | 0.000 | 14380.68 | 8.70 | 0.00699286 | 8.70 | 2.03050000 | 75.1291 | 7.48 | 0.00724209 | 21.64 | 0.00738516 | 45.9035 | 13655.89 | 0.00 | 15525.95 | 15525.95 | 3.25061935 | 2.80 | 2.80 | 0.00705484 | 20494.0 | 7.49 | 7.49 | 0.00705484 | 25270.3 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2274537.602 | -999.000 | 84.342111 | 0.06505149 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6314 | 1004.8586 | 1.2027 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 84.342111 | 101.44154047 | 4197.9300 | 999.8980 | 81.99394992 | 15.00 | 6.67 | 8.33 | 2867226.50 | 79.3288 | 79.328843 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2274537.60 | 1562917.32 | 1.0000 | 101.44154047 | 84.342111 | 26.31 | 19.33 | 0.01118451 | 54956.4 | 11.05 | 11.05 | 0.00850000 | 32534.2 | 65.04485157 | 6.67 | 15.00 | 8.33 | 182258.810 | 2092278.79 | 32.93 | 0.01716670 | 25.26 | 20.30600000 | 24.0758 | 24.00 | 0.00909553 | 24.00 | 0.00909553 | 48.8639 | 1078470.36 | 0.00 | 2277973.32 | 1546835.67 | 101.44154047 | 26.31 | 19.34 | 0.01118451 | 54956.4 | 11.44 | 11.36 | 0.00832691 | 32500.4 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 60458.685 | 60458.685 | 25.302633 | 0.00052892 | 1093.537 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 84.342111 | 101.44154047 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 4.3893 | 4.477666 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 60458.69 | 60458.69 | 1.0000 | 30.43246214 | 25.302633 | 10.82 | 9.85 | 0.00716118 | 28929.1 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.52886500 | 60.00 | 32.22 | 27.78 | 0.000 | 60458.69 | 8.70 | 0.00699286 | 8.70 | 20.30600000 | 80.2525 | 19.45 | 0.00784523 | 19.60 | 0.00772361 | 54.4048 | 293187.79 | 0.00 | 67505.54 | 67505.54 | 30.43246214 | 2.80 | 2.80 | 0.00716118 | 20760.5 | 4.98 | 4.98 | 0.00716118 | 22978.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 235481.466 | -999.000 | 9.248493 | 0.00673474 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9771 | 1004.8586 | 1.2027 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.248493 | 11.12352311 | 4197.9300 | 999.8980 | 81.99394992 | 15.00 | 6.67 | 8.33 | 2867226.50 | 8.2129 | 8.212866 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 235481.47 | 167593.98 | 1.0000 | 11.12352311 | 9.248493 | 25.96 | 18.95 | 0.01083253 | 53702.8 | 11.05 | 11.05 | 0.00850000 | 32533.1 | 6.73405311 | 6.67 | 15.00 | 8.33 | 19985.502 | 215495.96 | 32.93 | 0.01716670 | 25.26 | 2.03050000 | 21.9549 | 24.00 | 0.00904659 | 24.00 | 0.00904659 | 48.6050 | 126903.68 | 0.00 | 235847.05 | 165487.95 | 11.12352311 | 25.96 | 18.96 | 0.01083253 | 53702.8 | 11.45 | 11.36 | 0.00832472 | 32500.2 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 4866.787 | 4866.787 | 2.774548 | 0.00004258 | 88.395 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.248493 | 11.12352311 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 0.3533 | 0.360442 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4866.79 | 4866.79 | 1.0000 | 3.33705693 | 2.774548 | 11.35 | 10.15 | 0.00722091 | 29615.0 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.04257243 | 60.00 | 32.22 | 27.78 | 0.000 | 4866.79 | 8.70 | 0.00699286 | 8.70 | 2.03050000 | 73.1831 | 18.58 | 0.00784327 | 19.46 | 0.00775545 | 55.1111 | 34187.79 | 0.00 | 5474.62 | 5474.62 | 3.33705693 | 2.80 | 2.80 | 0.00722091 | 20910.2 | 4.41 | 4.41 | 0.00722091 | 22550.8 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 124671.513 | -999.000 | 5.176249 | 0.00356559 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0803 | 1004.8586 | 1.2027 | CAV_BAS FAN | Fan:ConstantVolume | 5.176249 | 6.22567618 | 4197.9300 | 999.8980 | 81.99394992 | 15.00 | 6.67 | 8.33 | 2867226.50 | 4.3482 | 4.348157 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 124671.51 | 86493.68 | 1.0000 | 6.22567618 | 5.176249 | 25.08 | 18.71 | 0.01088800 | 52943.9 | 11.42 | 11.42 | 0.00850000 | 32918.5 | 3.56522577 | 6.67 | 15.00 | 8.33 | 8777.129 | 115894.38 | 28.67 | 0.01715859 | 24.15 | 1.20015641 | 23.1858 | 24.00 | 0.00898702 | 24.00 | 0.00898702 | 48.2871 | 70920.90 | 0.00 | 124889.95 | 85990.84 | 6.22567618 | 25.08 | 18.72 | 0.01088800 | 52943.9 | 11.61 | 11.51 | 0.00841105 | 32883.4 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 237617.721 | 237617.721 | 5.176249 | 0.00207878 | 5445.913 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | CAV_BAS FAN | Fan:ConstantVolume | 5.176249 | 6.22567618 | 4197.9300 | 999.8980 | 11.81117592 | 54.44 | 82.22 | 27.78 | 1377401.56 | 17.2512 | 17.598344 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 237617.72 | 237617.72 | 1.0000 | 6.22567618 | 5.176249 | 2.02 | 2.02 | 0.00699286 | 19541.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 2.07857142 | 60.00 | 32.22 | 27.78 | 0.000 | 237617.72 | 8.70 | 0.00699286 | 8.70 | 1.20015641 | 23.1858 | 0.00 | 0.00699286 | 25.10 | 0.00699286 | 35.2826 | 0.00 | 0.00 | 206412.18 | 206412.18 | 6.22567618 | 12.80 | 10.55 | 0.00699286 | 30517.1 | 45.37 | 22.03 | 0.00699286 | 63672.0 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 433606.516 | 311537.726 | 21.284331 | 0.01061900 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9751 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 406274.74 | 395758.01 | 0.9370 | -999.0 | -999.0 | 28.50 | 18.07 | 0.00867966 | 50803.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 406274.74 | 33.20 | 0.01716721 | 25.32 | 0.33839277 | -999.0000 | 27.00 | 0.00854237 | 27.00 | 0.00854237 | 38.4373 | 370476.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9467.699 | 6784.619 | 0.462941 | 0.00023186 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3460 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8876.01 | 8393.38 | 0.9375 | -999.0 | -999.0 | 28.08 | 18.09 | 0.00887923 | 50884.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8876.01 | 30.92 | 0.01716288 | 24.74 | 0.01563234 | -999.0000 | 27.00 | 0.00858971 | 27.00 | 0.00858971 | 38.6452 | 8068.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 90557.684 | 64802.775 | 4.416100 | 0.00221775 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3799 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 84936.87 | 80110.91 | 0.9379 | -999.0 | -999.0 | 28.08 | 18.11 | 0.00889745 | 50937.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84936.87 | 30.92 | 0.01716288 | 24.74 | 0.15632344 | -999.0000 | 27.00 | 0.00859403 | 27.00 | 0.00859403 | 38.6646 | 76946.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9231.482 | 6610.101 | 0.450710 | 0.00022608 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3651 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8656.77 | 8174.17 | 0.9377 | -999.0 | -999.0 | 28.08 | 18.10 | 0.00888946 | 50913.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8656.77 | 30.92 | 0.01716288 | 24.74 | 0.01563234 | -999.0000 | 27.00 | 0.00859219 | 27.00 | 0.00859219 | 38.6563 | 7855.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 433606.516 | 433606.516 | 21.284331 | 0.01061900 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 433606.52 | 433606.52 | 1.0000 | 25.59949404 | 21.284331 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 433606.52 | 8.70 | 0.00699286 | 8.70 | 0.33839277 | 1.5899 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9467.699 | 9467.699 | 0.462941 | 0.00023186 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9467.70 | 9467.70 | 1.0000 | 0.55679751 | 0.462941 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9467.70 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.3767 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90557.684 | 90557.684 | 4.416100 | 0.00221775 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 90557.68 | 90557.68 | 1.0000 | 5.31141513 | 4.416100 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90557.68 | 8.70 | 0.00699286 | 8.70 | 0.15632344 | 3.5399 | 0.00 | 0.00792917 | 24.77 | 0.00792917 | 40.7380 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9231.482 | 9231.482 | 0.450710 | 0.00022608 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9231.48 | 9231.48 | 1.0000 | 0.54208604 | 0.450710 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9231.48 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.4684 | 0.00 | 0.00707501 | 24.03 | 0.00707501 | 38.0536 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 12800.936 | 12800.936 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.284331 | 25.59949404 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 12800.94 | 12800.94 | 1.0000 | 25.59949404 | 21.284331 | 0.14 | 0.14 | 0.00847604 | 21339.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12800.94 | 8.70 | 0.00699286 | 8.70 | 0.33839277 | 1.5899 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.462941 | 0.55679751 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 591.35 | 591.35 | 1.0000 | 0.55679751 | 0.462941 | 0.29 | 0.29 | 0.00844911 | 21430.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 591.35 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.3767 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2434 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5913.502 | 5913.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.416100 | 5.31141513 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 5913.50 | 5913.50 | 1.0000 | 5.31141513 | 4.416100 | 0.31 | 0.31 | 0.00789603 | 20061.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5913.50 | 8.70 | 0.00699286 | 8.70 | 0.15632344 | 3.5399 | 0.00 | 0.00792917 | 24.77 | 0.00792917 | 40.7380 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 591.350 | 591.350 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.450710 | 0.54208604 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 591.35 | 591.35 | 1.0000 | 0.54208604 | 0.450710 | 0.30 | 0.30 | 0.00707216 | 17994.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 591.35 | 8.70 | 0.00699286 | 8.70 | 0.01563234 | 3.4684 | 0.00 | 0.00707501 | 24.03 | 0.00707501 | 38.0536 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5686.17 | 2322.50 | 2321.50 |
CORE_BOTTOM | 5678.33 | 10.17 | 0.50 |
CORE_MID | 5412.17 | 103.50 | 5.50 |
CORE_TOP | 5234.17 | 361.17 | 6.33 |
PERIMETER_BOT_ZN_3 | 5325.17 | 558.67 | 234.17 |
PERIMETER_BOT_ZN_2 | 5446.50 | 611.33 | 398.00 |
PERIMETER_BOT_ZN_1 | 5627.83 | 568.67 | 447.50 |
PERIMETER_BOT_ZN_4 | 5697.83 | 927.33 | 882.17 |
PERIMETER_MID_ZN_3 | 4908.50 | 1417.33 | 650.83 |
PERIMETER_MID_ZN_2 | 4421.67 | 1076.33 | 715.83 |
PERIMETER_MID_ZN_1 | 5497.33 | 988.67 | 760.17 |
PERIMETER_MID_ZN_4 | 5316.50 | 1169.00 | 758.00 |
PERIMETER_TOP_ZN_3 | 4853.50 | 1665.00 | 797.33 |
PERIMETER_TOP_ZN_2 | 5167.50 | 1315.33 | 819.33 |
PERIMETER_TOP_ZN_1 | 5378.50 | 1186.00 | 848.50 |
PERIMETER_TOP_ZN_4 | 5218.00 | 1363.00 | 848.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 2183.67 | 2183.67 |
DATACENTER_MID_ZN_6 | 5943.00 | 253.17 | 253.17 |
DATACENTER_TOP_ZN_6 | 5933.33 | 680.00 | 680.00 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 104.83 | 0.00 | 9.00 |
CORE_BOTTOM | 0.00 | 5.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 31.33 | 0.00 | 19.17 |
PERIMETER_BOT_ZN_2 | 0.00 | 80.83 | 0.00 | 68.33 |
PERIMETER_BOT_ZN_1 | 0.00 | 208.00 | 0.00 | 185.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 401.17 | 0.00 | 144.00 |
PERIMETER_MID_ZN_3 | 0.00 | 22.50 | 0.00 | 16.67 |
PERIMETER_MID_ZN_2 | 0.00 | 90.50 | 0.00 | 73.83 |
PERIMETER_MID_ZN_1 | 0.00 | 249.50 | 0.00 | 235.67 |
PERIMETER_MID_ZN_4 | 0.00 | 136.33 | 0.00 | 61.17 |
PERIMETER_TOP_ZN_3 | 0.17 | 46.50 | 0.00 | 32.17 |
PERIMETER_TOP_ZN_2 | 0.17 | 105.67 | 0.00 | 79.33 |
PERIMETER_TOP_ZN_1 | 0.17 | 169.67 | 0.00 | 146.17 |
PERIMETER_TOP_ZN_4 | 0.17 | 154.67 | 0.00 | 70.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 61.50 | 0.00 | 57.17 |
DATACENTER_MID_ZN_6 | 0.00 | 34.00 | 0.00 | 32.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 20.33 | 0.00 | 17.17 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 921.50 | 0.00 | 705.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.17 | 1673.33 | 0.00 | 1114.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.523 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.488 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.464 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.455 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.593 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.735 | 0.047 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.786 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 1.100 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.603 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.808 | 0.115 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.862 | 0.106 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.892 | 0.109 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.588 | 0.131 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.827 | 0.136 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.837 | 0.131 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.852 | 0.136 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.584 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.658 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.572 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.645 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.22 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.95 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.54 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1031.21 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 23305819.40 | 0.00 | 23305819.40 | 0.00 | 23305819.40 | 37848132.68 | 3365.84 | 5394.16 | 0.00 | 639.82 |
CORE_BOTTOM | 24965648.84 | 0.00 | 24965648.84 | 0.00 | 24965648.84 | 33990283.35 | 6432.43 | 1453.99 | 873.58 | 1440.56 |
CORE_MID | 0.21E+09 | 0.00 | 0.21E+09 | 0.00 | 0.21E+09 | 0.34E+09 | 6960.56 | 899.90 | 899.54 | 666.42 |
CORE_TOP | 20553826.16 | 0.00 | 20553826.16 | 0.00 | 20553826.16 | 33990283.35 | 7095.70 | 1006.82 | 657.49 | 644.93 |
PERIMETER_BOT_ZN_3 | 3655746.94 | 0.00 | 3655746.94 | 419809.91 | 4075556.86 | 4267819.30 | 4123.33 | 1422.53 | 3214.15 | 1440.56 |
PERIMETER_BOT_ZN_2 | 2811369.13 | 0.00 | 2811369.13 | 279873.08 | 3091242.21 | 2750345.05 | 3451.31 | 1385.17 | 3923.52 | 1440.56 |
PERIMETER_BOT_ZN_1 | 4631698.41 | 0.00 | 4631698.41 | 419809.91 | 5051508.33 | 4267912.63 | 2851.73 | 1365.07 | 4543.20 | 1440.56 |
PERIMETER_BOT_ZN_4 | 4230153.63 | 0.00 | 4230153.63 | 279873.08 | 4510026.71 | 2750345.05 | 2139.27 | 983.35 | 5637.38 | 1440.56 |
PERIMETER_MID_ZN_3 | 33318295.43 | 0.00 | 33318295.43 | 984550.17 | 34302845.60 | 42678193.03 | 4729.16 | 903.51 | 3127.33 | 666.42 |
PERIMETER_MID_ZN_2 | 28480936.32 | 0.00 | 28480936.32 | 656366.33 | 29137302.65 | 27503450.52 | 3731.06 | 847.49 | 4181.45 | 1557.25 |
PERIMETER_MID_ZN_1 | 46425711.70 | 0.00 | 46425711.70 | 984550.17 | 47410261.87 | 42679126.28 | 3409.62 | 803.63 | 4546.75 | 666.42 |
PERIMETER_MID_ZN_4 | 31414348.98 | 0.00 | 31414348.98 | 656366.33 | 32070715.31 | 27503450.52 | 3522.45 | 750.21 | 4487.34 | 666.42 |
PERIMETER_TOP_ZN_3 | 3256397.20 | 0.00 | 3256397.20 | 1222397.02 | 4478794.23 | 4267819.30 | 4616.17 | 1029.98 | 3113.85 | 644.93 |
PERIMETER_TOP_ZN_2 | 2877885.34 | 0.00 | 2877885.34 | 814930.79 | 3692816.13 | 2750345.05 | 3526.68 | 930.12 | 4303.20 | 644.93 |
PERIMETER_TOP_ZN_1 | 4513904.20 | 0.00 | 4513904.20 | 1222397.02 | 5736301.23 | 4267912.63 | 3402.73 | 920.65 | 4436.62 | 644.93 |
PERIMETER_TOP_ZN_4 | 3013712.29 | 0.00 | 3013712.29 | 814930.79 | 3828643.09 | 2750345.05 | 3449.67 | 803.19 | 4507.15 | 644.93 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.37E+10 | 0.00 | 0.37E+10 | 38292351.59 | 0.37E+10 | 0.50E+10 | 8671.02 | 8760.00 | 6054.18 | 3707.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9601 | 0.0000 | 0.9601 | 0.0000 | 0.9601 | 1.2002 | 1188.66 | 4754.34 | 0.00 |
CORE_BOTTOM | 0.9075 | 0.0000 | 0.9075 | 0.0000 | 0.9075 | 1.0778 | 4655.20 | 461.48 | 826.32 |
CORE_MID | 8.6199 | 0.0000 | 8.6199 | 0.0000 | 8.6199 | 10.7782 | 4646.65 | 409.95 | 886.39 |
CORE_TOP | 0.8460 | 0.0000 | 0.8460 | 0.0000 | 0.8460 | 1.0778 | 4753.04 | 542.31 | 647.65 |
PERIMETER_BOT_ZN_3 | 0.1383 | 0.0000 | 0.1383 | 0.0105 | 0.1488 | 0.1353 | 2292.77 | 484.22 | 3166.02 |
PERIMETER_BOT_ZN_2 | 0.1104 | 0.0000 | 0.1104 | 0.0070 | 0.1174 | 0.0872 | 1623.46 | 438.38 | 3881.16 |
PERIMETER_BOT_ZN_1 | 0.1833 | 0.0000 | 0.1833 | 0.0105 | 0.1938 | 0.1353 | 1071.54 | 407.37 | 4464.09 |
PERIMETER_BOT_ZN_4 | 0.1653 | 0.0000 | 0.1653 | 0.0070 | 0.1723 | 0.0872 | 717.52 | 287.10 | 4938.38 |
PERIMETER_MID_ZN_3 | 1.4051 | 0.0000 | 1.4051 | 0.0246 | 1.4297 | 1.3533 | 2433.81 | 414.46 | 3094.73 |
PERIMETER_MID_ZN_2 | 1.2136 | 0.0000 | 1.2136 | 0.0173 | 1.2309 | 0.8721 | 1293.39 | 334.53 | 3406.08 |
PERIMETER_MID_ZN_1 | 2.0109 | 0.0000 | 2.0109 | 0.0246 | 2.0355 | 1.3533 | 1164.91 | 303.98 | 4474.11 |
PERIMETER_MID_ZN_4 | 1.3397 | 0.0000 | 1.3397 | 0.0164 | 1.3561 | 0.8721 | 1339.66 | 339.49 | 4263.85 |
PERIMETER_TOP_ZN_3 | 0.1372 | 0.0000 | 0.1372 | 0.0306 | 0.1677 | 0.1353 | 2307.26 | 570.98 | 3064.76 |
PERIMETER_TOP_ZN_2 | 0.1243 | 0.0000 | 0.1243 | 0.0204 | 0.1446 | 0.0872 | 1264.44 | 466.92 | 4211.64 |
PERIMETER_TOP_ZN_1 | 0.1952 | 0.0000 | 0.1952 | 0.0306 | 0.2258 | 0.1353 | 1123.18 | 469.47 | 4350.35 |
PERIMETER_TOP_ZN_4 | 0.1279 | 0.0000 | 0.1279 | 0.0204 | 0.1483 | 0.0872 | 1249.31 | 422.85 | 4270.84 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 151.7200 | 0.0000 | 151.7200 | 0.9663 | 152.6863 | 158.4706 | 5912.50 | 5943.00 | 5218.80 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 58289430.09 | 0.00 | 58289430.09 | 48026705.38 | 2011.80 | 2.55 | 6745.65 | 1440.56 |
VAV_MID WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.48E+09 | 3035.19 | 1.59 | 5723.22 | 666.42 |
VAV_TOP WITH REHEAT | 49495818.10 | 0.00 | 49495818.10 | 48026705.38 | 3066.97 | 1.97 | 5691.06 | 644.93 |
CAV_BAS | 33713754.27 | 0.00 | 33713754.27 | 37848132.68 | 3365.84 | 0.00 | 5394.16 | 639.82 |
AIRLOOP DATACENTER BASEMENT | 15437267.12 | 0.00 | 15437267.12 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 713137.79 | 0.00 | 713137.79 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7131377.88 | 0.00 | 7131377.88 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 713137.79 | 0.00 | 713137.79 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1768 | 0.0000 | 2.1768 | 1.5229 | 617.53 | 2.14 | 5323.33 |
VAV_MID WITH REHEAT | 21.1258 | 0.0000 | 21.1258 | 15.2292 | 872.37 | 1.09 | 5069.54 |
VAV_TOP WITH REHEAT | 2.0694 | 0.0000 | 2.0694 | 1.5229 | 882.47 | 1.44 | 5059.09 |
CAV_BAS | 1.3889 | 0.0000 | 1.3889 | 1.2002 | 1188.66 | 0.00 | 4754.34 |
AIRLOOP DATACENTER BASEMENT | 0.4895 | 0.0000 | 0.4895 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2261 | 0.0000 | 0.2261 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 419.46 | 0.00 | 0.00 | 0.00 | 0.00 | 6374.18 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 604.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5154.50 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 342.66 | 0.00 | 0.00 | 0.00 | 0.00 | 5383.09 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5394.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.6197 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4020 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 27.3838 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.3079 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.6246 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4075 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7362 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4895 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2261 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1521 |
Defaulted Fields | 1183 |
Fields with Defaults | 3931 |
Autosized Fields | 336 |
Autosizable Fields | 414 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30763.23 | 343941.28 | 22-JAN-05:00 | 1851059.15 | 21-AUG-16:00 |
Electricity:Building | 17133.47 | 216479.19 | 29-MAY-17:20 | 1021023.01 | 15-DEC-17:00 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17133.47 | 216479.19 | 29-MAY-17:20 | 1021023.01 | 15-DEC-17:00 |
InteriorLights:Electricity | 2457.08 | 9223.03 | 29-MAY-17:20 | 247210.90 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2457.08 | 9223.03 | 29-MAY-17:20 | 247210.90 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity | 2457.08 | 9223.03 | 29-MAY-17:20 | 247210.90 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2457.08 | 9223.03 | 29-MAY-17:20 | 247210.90 | 27-SEP-07:10 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 46.92 | 603.11 | 19-MAR-17:10 | 3823.11 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.56 | 43.94 | 01-JAN-09:20 | 1662.56 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.56 | 43.94 | 01-JAN-09:20 | 1662.56 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.22 | 388.67 | 23-APR-17:10 | 2463.76 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.78 | 28.32 | 01-JAN-07:40 | 1071.42 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.78 | 28.32 | 01-JAN-07:40 | 1071.42 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 46.82 | 603.12 | 12-MAR-17:10 | 3823.18 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.45 | 43.94 | 01-JAN-07:40 | 1662.60 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.45 | 43.94 | 01-JAN-07:40 | 1662.60 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.20 | 388.67 | 12-MAR-17:10 | 2463.75 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.77 | 28.32 | 01-JAN-09:20 | 1071.42 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.77 | 28.32 | 01-JAN-09:20 | 1071.42 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 469.04 | 6031.15 | 19-MAR-17:10 | 38231.14 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 105.39 | 439.44 | 01-JAN-09:10 | 16625.62 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 105.39 | 439.44 | 01-JAN-09:10 | 16625.62 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 302.09 | 3886.70 | 09-APR-17:10 | 24637.60 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 67.73 | 283.19 | 01-JAN-07:40 | 10714.18 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 67.73 | 283.19 | 01-JAN-07:40 | 10714.18 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 468.09 | 6031.24 | 12-MAR-17:10 | 38231.83 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.43 | 439.45 | 01-JAN-07:40 | 16625.99 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.43 | 439.45 | 01-JAN-07:40 | 16625.99 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 301.91 | 3886.68 | 12-MAR-17:10 | 24637.51 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 67.55 | 283.19 | 01-JAN-09:10 | 10714.18 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 67.55 | 283.19 | 01-JAN-09:10 | 10714.18 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 46.90 | 603.11 | 19-MAR-17:10 | 3823.11 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.54 | 43.94 | 01-JAN-09:10 | 1662.56 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.54 | 43.94 | 01-JAN-09:10 | 1662.56 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.21 | 388.67 | 09-APR-17:10 | 2463.76 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.77 | 28.32 | 01-JAN-07:40 | 1071.42 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.77 | 28.32 | 01-JAN-07:40 | 1071.42 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 46.81 | 603.12 | 12-MAR-17:10 | 3823.18 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.44 | 43.94 | 01-JAN-07:40 | 1662.60 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.44 | 43.94 | 01-JAN-07:40 | 1662.60 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.19 | 388.67 | 12-MAR-17:10 | 2463.75 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.76 | 28.32 | 01-JAN-09:10 | 1071.42 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.76 | 28.32 | 01-JAN-09:10 | 1071.42 | 27-SEP-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 5783.25 | 8725.62 | 25-JAN-05:50 | 431548.89 | 17-AUG-12:10 |
HeatRejection:Electricity | 1987.39 | 5341.54 | 25-JAN-07:00 | 86109.64 | 24-MAY-05:00 |
General:HeatRejection:Electricity | 1987.39 | 5341.54 | 25-JAN-07:00 | 86109.64 | 24-MAY-05:00 |
Electricity:HVAC | 5642.51 | 72449.43 | 22-JAN-06:00 | 380217.56 | 02-AUG-16:00 |
ExteriorEquipment:Electricity | 1909.29 | 28161.90 | 01-JAN-00:10 | 116890.93 | 27-SEP-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.67 | 979.82 | 01-JAN-00:10 | 3412.97 | 27-SEP-07:20 |
ElectricityPurchased:Facility | 30763.23 | 343941.28 | 22-JAN-05:00 | 1851059.15 | 21-AUG-16:00 |
ElectricityPurchased:Plant | 30763.23 | 343941.28 | 22-JAN-05:00 | 1851059.15 | 21-AUG-16:00 |
Cogeneration:ElectricityPurchased | 30763.23 | 343941.28 | 22-JAN-05:00 | 1851059.15 | 21-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 30763.23 | 343941.28 | 22-JAN-05:00 | 1851059.15 | 21-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30763.23 | 343941.28 | 22-JAN-05:00 | 1851059.15 | 21-AUG-16:00 |
ElectricityNet:Plant | 30763.23 | 343941.28 | 22-JAN-05:00 | 1851059.15 | 21-AUG-16:00 |
Cogeneration:ElectricityNet | 30763.23 | 343941.28 | 22-JAN-05:00 | 1851059.15 | 21-AUG-16:00 |
General:Cogeneration:ElectricityNet | 30763.23 | 343941.28 | 22-JAN-05:00 | 1851059.15 | 21-AUG-16:00 |
Fans:Electricity | 2563.31 | 41258.75 | 01-JAN-00:10 | 221222.39 | 07-JUL-15:30 |
General:Fans:Electricity | 2563.31 | 41258.75 | 01-JAN-00:10 | 221222.39 | 07-JUL-15:30 |
ExteriorLights:Electricity | 349.39 | 0.00 | 01-JAN-07:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 349.39 | 0.00 | 01-JAN-07:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 99.16 | 0.00 | 01-JAN-00:10 | 4520.72 | 01-JAN-08:50 |
General:HeatRecovery:Electricity | 99.16 | 0.00 | 01-JAN-00:10 | 4520.72 | 01-JAN-08:50 |
Cooling:Electricity | 5922.93 | 30179.28 | 31-JAN-05:50 | 458739.71 | 17-AUG-12:10 |
General:Cooling:Electricity | 5922.93 | 30179.28 | 31-JAN-05:50 | 458739.71 | 17-AUG-12:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1.15 | 0.00 | 01-JAN-00:10 | 4076.66 | 04-FEB-06:00 |
General:Humidifier:Electricity | 1.15 | 0.00 | 01-JAN-00:10 | 4076.66 | 04-FEB-06:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 797.15 | 3357.24 | 01-JAN-00:10 | 54487.80 | 16-FEB-13:50 |
General:Pumps:Electricity | 797.15 | 3357.24 | 01-JAN-00:10 | 54487.80 | 16-FEB-13:50 |
WIRED_LTG_ELECTRICITY | 69.04 | 0.00 | 01-JAN-00:10 | 6946.63 | 27-SEP-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 618.16 | 7280.88 | 01-APR-16:10 | 315646.84 | 04-FEB-06:10 |
NaturalGas:Plant | 618.16 | 7280.88 | 01-APR-16:10 | 315646.84 | 04-FEB-06:10 |
Heating:NaturalGas | 4.62 | 0.00 | 01-JAN-00:10 | 308365.96 | 04-FEB-06:10 |
Boiler:Heating:NaturalGas | 4.62 | 0.00 | 01-JAN-00:10 | 308365.96 | 04-FEB-06:10 |
WaterSystems:NaturalGas | 613.54 | 7280.88 | 01-APR-16:10 | 69759.54 | 17-JAN-13:00 |
Water Heater:WaterSystems:NaturalGas | 613.54 | 7280.88 | 01-APR-16:10 | 69759.54 | 17-JAN-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 32551.86 | 159290.86 | 25-JAN-05:50 | 2480710.06 | 21-AUG-12:10 |
PlantLoopCoolingDemand:HVAC | 32551.86 | 159290.86 | 25-JAN-05:50 | 2480710.06 | 21-AUG-12:10 |
CoolingCoils:PlantLoopCoolingDemand | 32551.86 | 159290.86 | 25-JAN-05:50 | 2480710.06 | 21-AUG-12:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 17365.73 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JUL-12:10 |
Water:HVAC | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
Humidifier:Water | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
General:Humidifier:Water | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
MainsWater:Facility | 17365.73 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JUL-12:10 |
MainsWater:HVAC | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
Humidifier:MainsWater | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
General:Humidifier:MainsWater | 0.43 | 0.00 | 01-JAN-00:10 | 0.00 | 04-FEB-06:00 |
Water:Plant | 17365.30 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JUL-12:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 17365.30 | 0.00 | 01-JAN-00:10 | 0.00 | 07-JUL-12:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 15085.13 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:00 |
General:HeatRejection:Water | 15085.13 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:00 |
HeatRejection:MainsWater | 15085.13 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:00 |
General:HeatRejection:MainsWater | 15085.13 | 0.00 | 01-JAN-00:10 | 0.00 | 17-APR-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 118952.34 | 227959.38 | 25-JAN-05:50 | 10101707.10 | 21-AUG-12:10 |
EnergyTransfer:Building | 22491.74 | 98686.95 | 26-JAN-05:50 | 1623519.01 | 21-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 734.56 | 0.00 | 01-JAN-00:10 | 75837.24 | 13-NOV-06:20 |
Heating:EnergyTransfer | 13.07 | 0.00 | 01-JAN-00:10 | 160553.27 | 04-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.96 | 0.00 | 01-JAN-00:10 | 22702.55 | 29-JUL-16:10 |
General:Heating:EnergyTransfer | 13.07 | 0.00 | 01-JAN-00:10 | 160553.27 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.96 | 0.00 | 01-JAN-00:10 | 22702.55 | 29-JUL-16:10 |
Cooling:EnergyTransfer | 22478.67 | 98686.95 | 26-JAN-05:50 | 1623519.01 | 21-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 730.60 | 0.00 | 01-JAN-00:10 | 75837.24 | 13-NOV-06:20 |
General:Cooling:EnergyTransfer | 22478.67 | 98686.95 | 26-JAN-05:50 | 1623519.01 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 730.60 | 0.00 | 01-JAN-00:10 | 75837.24 | 13-NOV-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 745.73 | 0.00 | 01-JAN-00:10 | 57607.24 | 21-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 745.73 | 0.00 | 01-JAN-00:10 | 57607.24 | 21-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 745.73 | 0.00 | 01-JAN-00:10 | 57607.24 | 21-AUG-07:20 |
EnergyTransfer:Zone:CORE_MID | 5584.18 | 0.00 | 01-JAN-00:10 | 427696.51 | 06-NOV-14:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5584.18 | 0.00 | 01-JAN-00:10 | 427696.51 | 06-NOV-14:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5584.18 | 0.00 | 01-JAN-00:10 | 427696.51 | 06-NOV-14:10 |
EnergyTransfer:Zone:CORE_TOP | 573.05 | 0.00 | 01-JAN-00:10 | 49670.49 | 18-SEP-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 573.05 | 0.00 | 01-JAN-00:10 | 49670.49 | 18-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 573.05 | 0.00 | 01-JAN-00:10 | 49670.49 | 18-SEP-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 116.63 | 0.00 | 01-JAN-00:10 | 11617.73 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 116.63 | 0.00 | 01-JAN-00:10 | 11617.73 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 116.63 | 0.00 | 01-JAN-00:10 | 11617.73 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 92.67 | 0.00 | 01-JAN-00:10 | 11585.31 | 12-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 92.67 | 0.00 | 01-JAN-00:10 | 11585.31 | 12-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 92.67 | 0.00 | 01-JAN-00:10 | 11585.31 | 12-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 151.81 | 0.00 | 01-JAN-00:10 | 15672.72 | 04-DEC-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 151.81 | 0.00 | 01-JAN-00:10 | 15672.72 | 04-DEC-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 151.81 | 0.00 | 01-JAN-00:10 | 15672.72 | 04-DEC-14:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 136.83 | 0.00 | 01-JAN-00:10 | 15771.81 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 136.83 | 0.00 | 01-JAN-00:10 | 15771.81 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 136.83 | 0.00 | 01-JAN-00:10 | 15771.81 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 937.58 | 0.00 | 01-JAN-00:10 | 107995.20 | 01-JUN-14:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.43 | 0.00 | 01-JAN-00:10 | 40602.66 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.43 | 0.00 | 01-JAN-00:10 | 40602.66 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 937.15 | 0.00 | 01-JAN-00:10 | 107995.20 | 01-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 937.15 | 0.00 | 01-JAN-00:10 | 107995.20 | 01-JUN-14:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 833.41 | 0.00 | 01-JAN-00:10 | 119510.82 | 25-JUL-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.10 | 0.00 | 01-JAN-00:10 | 30129.35 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.10 | 0.00 | 01-JAN-00:10 | 30129.35 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 833.31 | 0.00 | 01-JAN-00:10 | 119510.82 | 25-JUL-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 833.31 | 0.00 | 01-JAN-00:10 | 119510.82 | 25-JUL-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1326.24 | 0.00 | 01-JAN-00:10 | 157884.99 | 03-DEC-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.06 | 0.00 | 01-JAN-00:10 | 32679.90 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.06 | 0.00 | 01-JAN-00:10 | 32679.90 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1326.18 | 0.00 | 01-JAN-00:10 | 157884.99 | 03-DEC-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1326.18 | 0.00 | 01-JAN-00:10 | 157884.99 | 03-DEC-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 893.14 | 0.00 | 01-JAN-00:10 | 131231.61 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 26510.75 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 26510.75 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 893.06 | 0.00 | 01-JAN-00:10 | 131231.61 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 893.06 | 0.00 | 01-JAN-00:10 | 131231.61 | 17-MAY-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 96.93 | 0.00 | 01-JAN-00:10 | 11785.79 | 27-JUL-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.32 | 0.00 | 01-JAN-00:10 | 9395.42 | 04-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.32 | 0.00 | 01-JAN-00:10 | 9395.42 | 04-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 96.61 | 0.00 | 01-JAN-00:10 | 11785.79 | 27-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 96.61 | 0.00 | 01-JAN-00:10 | 11785.79 | 27-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 87.90 | 0.00 | 01-JAN-00:10 | 12272.67 | 25-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.11 | 0.00 | 01-JAN-00:10 | 5751.09 | 04-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.11 | 0.00 | 01-JAN-00:10 | 5751.09 | 04-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 87.79 | 0.00 | 01-JAN-00:10 | 12272.67 | 25-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 87.79 | 0.00 | 01-JAN-00:10 | 12272.67 | 25-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 134.91 | 0.00 | 01-JAN-00:10 | 16945.00 | 07-NOV-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.07 | 0.00 | 01-JAN-00:10 | 5880.58 | 04-FEB-06:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.07 | 0.00 | 01-JAN-00:10 | 5880.58 | 04-FEB-06:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 134.84 | 0.00 | 01-JAN-00:10 | 16945.00 | 07-NOV-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 134.84 | 0.00 | 01-JAN-00:10 | 16945.00 | 07-NOV-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 91.16 | 0.00 | 01-JAN-00:10 | 13798.95 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 4540.68 | 04-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.08 | 0.00 | 01-JAN-00:10 | 4540.68 | 04-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 91.08 | 0.00 | 01-JAN-00:10 | 13798.95 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 91.08 | 0.00 | 01-JAN-00:10 | 13798.95 | 17-MAY-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 117.07 | 0.00 | 01-JAN-00:10 | 13582.52 | 21-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.71 | 0.00 | 01-JAN-00:10 | 3509.16 | 05-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.71 | 0.00 | 01-JAN-00:10 | 3509.16 | 05-FEB-11:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 116.36 | 0.00 | 01-JAN-00:10 | 13582.52 | 21-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 116.36 | 0.00 | 01-JAN-00:10 | 13582.52 | 21-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 887.04 | 0.00 | 01-JAN-00:10 | 96371.53 | 31-JUL-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.26 | 0.00 | 01-JAN-00:10 | 27045.55 | 05-FEB-12:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.26 | 0.00 | 01-JAN-00:10 | 27045.55 | 05-FEB-12:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 882.78 | 0.00 | 01-JAN-00:10 | 96371.53 | 31-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 882.78 | 0.00 | 01-JAN-00:10 | 96371.53 | 31-JUL-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 141.28 | 0.00 | 01-JAN-00:10 | 23553.14 | 28-JUL-15:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.88 | 0.00 | 01-JAN-00:10 | 7255.59 | 04-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.88 | 0.00 | 01-JAN-00:10 | 7255.59 | 04-FEB-05:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 138.40 | 0.00 | 01-JAN-00:10 | 23553.14 | 28-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 138.40 | 0.00 | 01-JAN-00:10 | 23553.14 | 28-JUL-15:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.63 | 1221.67 | 26-JAN-08:00 | 8003.49 | 09-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.63 | 1221.67 | 26-JAN-08:00 | 8003.49 | 09-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.63 | 1221.67 | 26-JAN-08:00 | 8003.49 | 09-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1345.71 | 7182.41 | 25-JAN-08:00 | 75386.76 | 09-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1345.71 | 7182.41 | 25-JAN-08:00 | 75386.76 | 09-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1345.71 | 7182.41 | 25-JAN-08:00 | 75386.76 | 09-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.72 | 36.04 | 25-JAN-07:00 | 7808.74 | 09-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.72 | 36.04 | 25-JAN-07:00 | 7808.74 | 09-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 133.72 | 36.04 | 25-JAN-07:00 | 7808.74 | 09-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7186.56 | 88781.46 | 27-MAY-20:00 | 369761.39 | 28-AUG-12:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7186.56 | 88781.46 | 27-MAY-20:00 | 369761.39 | 28-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7186.56 | 88781.46 | 27-MAY-20:00 | 369761.39 | 28-AUG-12:10 |
PlantLoopHeatingDemand:Facility | 300.02 | 0.00 | 01-JAN-00:10 | 222025.98 | 04-FEB-06:10 |
PlantLoopHeatingDemand:Plant | 296.73 | 0.00 | 01-JAN-00:10 | 36112.03 | 17-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 296.73 | 0.00 | 01-JAN-00:10 | 36112.03 | 17-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 296.73 | 0.00 | 01-JAN-00:10 | 36112.03 | 17-JAN-12:10 |
EnergyTransfer:HVAC | 32933.92 | 129065.91 | 25-JAN-05:50 | 2759457.62 | 21-AUG-16:00 |
HeatingCoils:EnergyTransfer | 3.29 | 0.00 | 01-JAN-00:10 | 217648.64 | 04-FEB-06:10 |
PlantLoopHeatingDemand:HVAC | 3.29 | 0.00 | 01-JAN-00:10 | 217648.64 | 04-FEB-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 3.29 | 0.00 | 01-JAN-00:10 | 217648.64 | 04-FEB-06:10 |
CoolingCoils:EnergyTransfer | 29627.64 | 129065.91 | 25-JAN-05:50 | 2326372.34 | 21-AUG-12:10 |
HeatRecoveryForHeating:EnergyTransfer | 12.89 | 0.00 | 01-JAN-00:10 | 162426.59 | 04-FEB-07:00 |
HeatRecoveryForCooling:EnergyTransfer | 3290.10 | 0.00 | 01-JAN-00:10 | 526106.11 | 22-JUL-15:00 |
EnergyTransfer:Plant | 63526.68 | 0.00 | 01-JAN-00:10 | 6038843.70 | 23-AUG-12:10 |
LoopToLoop:EnergyTransfer | 20184.89 | 0.00 | 01-JAN-00:10 | 1838491.94 | 18-AUG-12:00 |
WaterSystems:EnergyTransfer | 296.73 | 0.00 | 01-JAN-00:10 | 36112.03 | 17-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 296.73 | 0.00 | 01-JAN-00:10 | 36112.03 | 17-JAN-12:10 |
Boilers:EnergyTransfer | 3.09 | 0.00 | 01-JAN-00:10 | 246232.35 | 04-FEB-06:10 |
Chillers:EnergyTransfer | 20021.63 | 0.00 | 01-JAN-00:10 | 1976836.19 | 23-AUG-12:10 |
HeatRejection:EnergyTransfer | 23020.34 | 0.00 | 01-JAN-00:10 | 2272106.83 | 17-AUG-12:10 |
General:HeatRejection:EnergyTransfer | 23020.34 | 0.00 | 01-JAN-00:10 | 2272106.83 | 17-AUG-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.963 | -730.597 | 0.000 | 0.000 | 92.664 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 43.843 | 0.000 | 0.000 | 0.000 | 0.000 | -0.012 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -745.731 | 0.000 | 0.000 | 83.426 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 223.854 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5584.167 | 0.000 | 0.000 | 834.810 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 364.864 | 0.000 | 0.000 | 0.000 | 0.000 | -0.015 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -573.045 | 0.000 | 0.000 | 83.629 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 50.966 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -116.629 | 0.000 | 0.000 | 10.486 | 10.559 | 36.365 | 43.694 | 0.000 | 0.611 | 34.851 | 0.000 | -18.882 | 0.000 | -1.055 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -92.667 | 0.000 | 0.000 | 6.748 | 6.782 | 23.435 | 59.084 | 0.000 | 0.400 | 8.638 | 0.000 | -11.711 | 0.000 | -0.710 | -0.001 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -151.805 | 0.000 | 0.000 | 10.427 | 10.454 | 36.366 | 91.531 | 0.000 | 0.580 | 22.735 | 0.000 | -19.102 | 0.000 | -1.186 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -136.828 | 0.000 | 0.000 | 6.732 | 6.765 | 23.435 | 55.291 | 0.000 | 0.344 | 61.540 | 0.000 | -16.313 | 0.000 | -0.966 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.428 | -937.133 | 0.000 | 0.000 | 105.699 | 105.390 | 363.654 | 444.187 | 0.000 | 13.584 | 98.982 | 0.000 | -172.061 | 0.000 | -22.729 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.097 | -833.296 | 0.000 | 0.000 | 49.480 | 67.734 | 234.352 | 582.586 | 0.000 | 8.162 | 24.645 | 0.000 | -116.533 | 0.000 | -17.229 | -0.012 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.057 | -1326.155 | 0.000 | 0.000 | 104.211 | 104.431 | 363.660 | 910.648 | 0.000 | 12.652 | 45.665 | 0.000 | -186.876 | 0.000 | -28.292 | -0.009 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.085 | -893.049 | 0.000 | 0.000 | 67.691 | 67.554 | 234.351 | 564.579 | 0.000 | 7.977 | 105.189 | 0.000 | -135.398 | 0.000 | -18.979 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.321 | -96.611 | 0.000 | 0.000 | 10.616 | 10.538 | 36.365 | 43.865 | 0.000 | 1.574 | 12.734 | 0.000 | -16.693 | 0.000 | -2.709 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.107 | -87.790 | 0.000 | 0.000 | 6.768 | 6.773 | 23.435 | 58.073 | 0.000 | 0.984 | 5.036 | 0.000 | -11.334 | 0.000 | -2.053 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.073 | -134.837 | 0.000 | 0.000 | 10.474 | 10.443 | 36.366 | 90.438 | 0.000 | 1.489 | 7.196 | 0.000 | -18.239 | 0.000 | -3.402 | -0.002 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.079 | -91.076 | 0.000 | 0.000 | 6.793 | 6.755 | 23.435 | 56.016 | 0.000 | 0.947 | 12.532 | 0.000 | -13.194 | 0.000 | -2.286 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -143.630 | 0.000 | 0.000 | 0.948 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -14.825 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1345.710 | 0.000 | 0.000 | 9.484 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -238.843 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -133.720 | 0.000 | 0.000 | 0.949 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -24.736 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7186.567 | 0.000 | 0.000 | 20.011 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -375.912 |
GROUNDFLOOR_PLENUM | 0.713 | -116.356 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.998 | 117.122 | 0.000 | 0.000 | 0.000 | -2.477 | -0.000 |
MIDFLOOR_PLENUM | 4.261 | -882.770 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.016 | 902.997 | 0.000 | 0.000 | 0.000 | -42.504 | -0.000 |
TOPFLOOR_PLENUM | 2.884 | -138.398 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.542 | 138.544 | 0.000 | 0.000 | 0.000 | -4.572 | -0.000 |
Total Facility | 7.858 | -1137.524 | 5.209 | -21341.044 | 0.000 | 0.000 | 1522.046 | 2457.076 | 14676.396 | 2999.991 | 0.000 | 69.858 | 2281.934 | 0.000 | -736.336 | 0.000 | -151.147 | -654.375 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | -98248.29 | 0.00 | 0.00 | 847.23 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 83345.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 21-FEB-05:13 | 0.00 | 0.00 | 0.00 | -91990.15 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 85515.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | -814097.32 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 749347.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 01-MAY-04:12 | 0.00 | 0.00 | 0.00 | -80105.24 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 73630.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-16:21 | 0.00 | 0.00 | 0.00 | -17354.92 | 0.00 | 0.00 | 41.55 | 43.94 | 720.18 | 4295.60 | 0.00 | 68.07 | 12185.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUN-08:32 | 0.00 | 0.00 | 0.00 | -18351.45 | 0.00 | 0.00 | 23.45 | 28.32 | 464.11 | 9955.88 | 0.00 | 16.05 | 7863.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-DEC-12:41 | 0.00 | 0.00 | 0.00 | -19726.84 | 0.00 | 0.00 | 33.09 | 43.94 | 720.19 | 19403.65 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -40.24 | -433.80 |
PERIMETER_BOT_ZN_4 | 10-DEC-15:21 | 0.00 | 0.00 | 0.00 | -25294.65 | 0.00 | 0.00 | 20.49 | 28.32 | 464.11 | 9719.26 | 0.00 | 1.59 | 15060.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JUL-16:51 | 0.00 | 0.00 | 0.00 | -170120.24 | 0.00 | 0.00 | 411.53 | 439.44 | 7201.84 | 45019.97 | 0.00 | 2208.87 | 114838.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-09:41 | 0.00 | 0.00 | 0.00 | -201088.99 | 0.00 | 0.00 | 214.30 | 283.19 | 4641.14 | 106522.76 | 0.00 | 611.26 | 88816.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 03-DEC-13:51 | 0.00 | 0.00 | 0.00 | -196267.21 | 0.00 | 0.00 | 306.29 | 439.45 | 7201.95 | 184382.26 | 0.00 | 0.00 | 6282.24 | 0.00 | -0.00 | 0.00 | -2344.98 | 0.00 |
PERIMETER_MID_ZN_4 | 09-JUL-16:51 | 0.00 | 0.00 | 0.00 | -229576.37 | 0.00 | 0.00 | 195.97 | 283.19 | 4641.11 | 107758.40 | 0.00 | 409.07 | 116288.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 09-JUL-16:51 | 0.00 | 0.00 | 0.00 | -19652.31 | 0.00 | 0.00 | 38.99 | 43.94 | 720.18 | 4311.17 | 0.00 | 218.07 | 14319.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 11-JUN-09:32 | 0.00 | 0.00 | 0.00 | -20059.60 | 0.00 | 0.00 | 21.64 | 28.32 | 464.11 | 10590.58 | 0.00 | 81.43 | 8873.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 20-FEB-14:31 | 0.00 | 0.00 | 0.00 | -21374.76 | 0.00 | 0.00 | 32.71 | 43.94 | 720.19 | 15546.04 | 0.00 | 0.00 | 5409.70 | 0.00 | -0.00 | 0.00 | -377.83 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-16:51 | 0.00 | 0.00 | 0.00 | -25033.40 | 0.00 | 0.00 | 18.38 | 28.32 | 464.11 | 10646.08 | 0.00 | 21.39 | 13855.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 09-APR-17:53 | 0.00 | 0.00 | 0.00 | -8003.60 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 191.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 09-APR-17:53 | 0.00 | 0.00 | 0.00 | -75387.83 | 0.00 | 0.00 | 0.00 | 175.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2732.31 |
DATACENTER_TOP_ZN_6 | 09-APR-17:53 | 0.00 | 0.00 | 0.00 | -7808.85 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3.17 |
DATACENTER_BASEMENT_ZN_6 | 28-AUG-12:05 | 0.00 | 0.00 | 0.00 | -369859.49 | 0.00 | 0.00 | 2148.25 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16078.46 |
GROUNDFLOOR_PLENUM | 21-AUG-05:15 | 0.00 | -15894.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 15881.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-SEP-05:15 | 0.00 | -119272.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119419.94 | 0.00 | -0.00 | 0.00 | -147.47 | 0.00 |
TOPFLOOR_PLENUM | 28-JUL-15:20 | 0.00 | -23552.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.81 | 23373.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-AUG-05:02 | 0.00 | -39613.11 | 0.00 | -1937500.05 | 0.00 | 0.00 | 15381.11 | 10593.62 | 616289.16 | 0.00 | 0.00 | 92.15 | 1338033.24 | 0.00 | -3276.11 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 29-JUL-16:01 | 0.00 | 0.00 | 24345.05 | 0.00 | 0.00 | 0.00 | 520.12 | 819.05 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -39141.77 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-FEB-05:11 | 0.00 | 0.00 | 117936.49 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -44635.97 | 0.00 | -16378.50 | -63188.43 |
PERIMETER_MID_ZN_2 | 04-FEB-06:03 | 0.00 | 0.00 | 90417.52 | 0.00 | 0.00 | 0.00 | 941.48 | 434.81 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30290.19 | 0.00 | -2861.78 | -64830.03 |
PERIMETER_MID_ZN_1 | 04-FEB-06:03 | 0.00 | 0.00 | 110254.37 | 0.00 | 0.00 | 0.00 | 1460.99 | 674.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46521.88 | 0.00 | -4258.98 | -71211.82 |
PERIMETER_MID_ZN_4 | 04-FEB-06:03 | 0.00 | 0.00 | 86885.18 | 0.00 | 0.00 | 0.00 | 941.49 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31514.21 | 0.00 | -2860.72 | -60074.69 |
PERIMETER_TOP_ZN_3 | 04-FEB-05:11 | 0.00 | 0.00 | 14339.45 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3982.43 | 0.00 | -1803.20 | -9180.46 |
PERIMETER_TOP_ZN_2 | 04-FEB-05:11 | 0.00 | 0.00 | 12688.19 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2644.17 | 0.00 | -1244.05 | -9203.79 |
PERIMETER_TOP_ZN_1 | 04-FEB-05:11 | 0.00 | 0.00 | 13676.01 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 559.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4176.83 | 0.00 | -1948.46 | -8177.36 |
PERIMETER_TOP_ZN_4 | 04-FEB-05:11 | 0.00 | 0.00 | 12521.54 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2821.37 | 0.00 | -1300.75 | -8803.25 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:12 | 12752.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -269.65 | -12483.33 |
MIDFLOOR_PLENUM | 13-NOV-05:12 | 73283.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -18921.21 | -54362.75 |
TOPFLOOR_PLENUM | 15-MAR-05:02 | 17535.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -612.02 | -16923.43 |
Total Facility | 04-FEB-06:03 | -557648.41 | 521226.92 | 446331.41 | -521226.92 | 0.00 | 0.00 | 18649.12 | 10593.62 | 379706.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -185895.20 | 0.00 | -25190.86 | -86546.05 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 9.8186 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.0089 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 93.0755 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 84.3421 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.6294 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.2485 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.1762 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.1762 | 0.2319 | 1.0000 | Not calculated | 1.2002 | 0.2319 | ||
AIRLOOP DATACENTER BASEMENT | 21.2841 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.2843 | 0.0159 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4629 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4629 | 0.0338 | 1.0000 | Not calculated | 0.0156 | 0.0338 | ||
AIRLOOP DATACENTER MID | 4.4161 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4161 | 0.0354 | 1.0000 | Not calculated | 0.1563 | 0.0354 | ||
AIRLOOP DATACENTER TOP | 0.4507 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4507 | 0.0347 | 1.0000 | Not calculated | 0.0156 | 0.0347 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.9093 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2866 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 46.5378 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8261 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.8147 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2868 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.1762 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.1762 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2319 | ||
AIRLOOP DATACENTER BASEMENT | 21.2841 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.2841 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4629 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4629 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0338 | ||
AIRLOOP DATACENTER MID | 4.4161 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4161 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0354 | ||
AIRLOOP DATACENTER TOP | 0.4507 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4507 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0347 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1762 | 5.1762 | 5.1762 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5273 | 5.5273 | 1.6195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 52.0890 | 52.0890 | 16.1476 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1884 | 5.1884 | 1.6188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9927 | 0.9927 | 0.2025 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9967 | 0.9967 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9889 | 0.9889 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3131 | 1.3131 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5615 | 9.5615 | 2.0270 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.4001 | 10.4001 | 1.3104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.4634 | 9.4634 | 2.0346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.5614 | 11.5614 | 1.3064 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0740 | 1.0740 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0567 | 1.0567 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0736 | 1.0736 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2368 | 1.2368 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4629 | 0.4629 | 0.4629 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4161 | 4.4161 | 4.4161 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4507 | 0.4507 | 0.4507 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.2841 | 21.2841 | 21.2841 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 9.8186 | 9.0089 | 9.8186 | 2.2866 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 93.0755 | 84.3421 | 93.0755 | 22.8261 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.6294 | 9.2485 | 9.6294 | 2.2868 | 0.0000 | 1.0000 |
CAV_BAS | 5.1762 | 5.1762 | 5.1762 | 5.1762 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2841 | 21.2843 | 21.2841 | 21.2841 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4629 | 0.4629 | 0.4629 | 0.4629 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4161 | 4.4161 | 4.4161 | 4.4161 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4507 | 0.4507 | 0.4507 | 0.4507 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1762 | 5.1762 | 5.1762 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7636 | 2.7636 | 1.6195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 26.0445 | 26.0445 | 16.1476 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5942 | 2.5942 | 1.6188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4963 | 0.4963 | 0.2025 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4983 | 0.4983 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4944 | 0.4944 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6565 | 0.6565 | 0.1313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7808 | 4.7808 | 2.0270 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2001 | 5.2001 | 1.3104 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7317 | 4.7317 | 2.0346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7807 | 5.7807 | 1.3064 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5370 | 0.5370 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5283 | 0.5283 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5368 | 0.5368 | 0.2029 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6184 | 0.6184 | 0.1311 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4629 | 0.4629 | 0.4629 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4161 | 4.4161 | 4.4161 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4507 | 0.4507 | 0.4507 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.2841 | 21.2841 | 21.2841 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.9093 | 2.2866 | 2.2866 | 2.2866 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 46.5378 | 22.8261 | 22.8261 | 22.8261 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.8147 | 2.2868 | 2.2868 | 2.2868 | 0.0000 | 1.0000 |
CAV_BAS | 5.1762 | 5.1762 | 5.1762 | 5.1762 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2841 | 21.2841 | 21.2841 | 21.2841 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4629 | 0.4629 | 0.4629 | 0.4629 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4161 | 4.4161 | 4.4161 | 4.4161 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4507 | 0.4507 | 0.4507 | 0.4507 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1114.33 |
Number of hours not met | 1114.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 4.62 | 308365.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5922.93 | 458739.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2457.08 | 247210.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 349.39 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.67 | 3412.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2563.31 | 221222.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 797.15 | 54487.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1987.39 | 86109.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1.15 | 4076.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 99.16 | 4520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 613.54 | 69759.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 30763.23 |
Natural Gas | 0.00 | 618.16 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31381.39 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.05 |
Space Heating | 0.00 |
Space Cooling | 127.87 |
Fans (All) | 55.34 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 664.14 |
Subtotal | 664.14 |
Natural Gas [MJ/m2] | |
Space Heating | 0.10 |
Service Water Heating | 13.25 |
Miscellaneous (All) | 13.35 |
Subtotal | 13.35 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.83 |
Space Heating | 0.01 |
Space Cooling | 18.87 |
Fans (All) | 8.17 |
Service Water Heating | 1.96 |
Receptacle Equipment | 46.77 |
Miscellaneous | 16.39 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 986. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 6986.17 | 1773.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8688.83 | 71.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8747.33 | 12.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8631.83 | 128.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8467.50 | 292.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8388.17 | 371.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6848.67 | 1911.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8407.50 | 352.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7969.50 | 790.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7895.50 | 864.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7251.67 | 1508.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8288.17 | 471.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7903.33 | 856.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7823.83 | 936.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7274.33 | 1485.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1286.17 | 7473.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1286.33 | 7473.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1252.67 | 7507.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 1065.50 | 7694.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8706.67 | 53.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8236.50 | 523.50 | 0.00 | 0.00 | 0.00 |
Min | 1065.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 7694.50 | 0.00 | 0.00 | 0.00 |
Average | 6909.83 | 1850.17 | 0.00 | 0.00 | 0.00 |
Sum | 158926.17 | 42553.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 363588.83 | 5027.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330739.00 | 74.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330796.00 | 17.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 218.00 | 2050.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 218.50 | 2049.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 212.50 | 2055.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 9421.83 | 93973.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 363588.83 | 93973.17 | 0.00 | 0.00 | 0.00 |
Average | 75758.99 | 4575.93 | 0.00 | 0.00 | 0.00 |
Sum | 1742456.67 | 105246.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 3407.83 | 5352.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 6417.33 | 2342.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 6440.00 | 2320.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 6078.83 | 2681.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 5653.83 | 3106.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 5716.00 | 3044.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5386.00 | 3374.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5146.83 | 3613.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 5464.67 | 3295.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5345.67 | 3414.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5254.33 | 3505.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5314.00 | 3446.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 5440.33 | 3319.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5363.17 | 3396.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5270.33 | 3489.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5320.50 | 3439.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2476.50 | 6283.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2428.50 | 6331.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2353.17 | 6406.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 2502.00 | 6258.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3976.00 | 4784.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3152.50 | 5607.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 2760.67 | 5999.33 | 0.00 | 0.00 | 0.00 |
Min | 2353.17 | 2320.00 | 0.00 | 0.00 | 0.00 |
Max | 6440.00 | 6406.83 | 0.00 | 0.00 | 0.00 |
Average | 4637.78 | 4122.22 | 0.00 | 0.00 | 0.00 |
Sum | 106669.00 | 94811.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 310092.33 | 58523.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 326018.00 | 4795.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 326833.00 | 3980.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 324204.50 | 6608.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38919.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24902.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38920.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38833.17 | 91.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18285.33 | 68.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38857.67 | 67.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24861.17 | 47.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38596.17 | 328.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24807.67 | 101.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38812.83 | 112.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24799.83 | 109.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 399.00 | 1869.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 396.67 | 1871.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 378.17 | 1889.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 19894.00 | 83501.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 326833.00 | 83501.00 | 0.00 | 0.00 | 0.00 |
Average | 73205.22 | 7129.69 | 0.00 | 0.00 | 0.00 |
Sum | 1683720.17 | 163982.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.604484E+11 | 95616.25 | 17-JAN-05:11 | 13.13 | 11.78 | 0.567077E+10 | 7499.23 | 27-JAN-10:20 | 19.43 | 12.83 |
February | 0.537787E+11 | 98136.24 | 04-FEB-05:11 | 5.93 | 2.51 | 0.514286E+10 | 7499.30 | 23-FEB-10:20 | 23.33 | 17.54 |
March | 0.605951E+11 | 95799.35 | 16-MAR-04:12 | 7.43 | 4.89 | 0.613525E+10 | 7499.26 | 17-MAR-13:20 | 21.30 | 14.88 |
April | 0.561946E+11 | 92694.20 | 19-APR-04:12 | 15.00 | 11.82 | 0.545203E+10 | 7499.28 | 20-APR-09:20 | 24.40 | 17.64 |
May | 0.594318E+11 | 77997.41 | 09-MAY-03:02 | 24.40 | 19.56 | 0.590322E+10 | 7498.96 | 26-MAY-09:20 | 26.47 | 22.84 |
June | 0.596172E+11 | 73265.34 | 13-JUN-03:02 | 24.32 | 22.73 | 0.588318E+10 | 7498.95 | 23-JUN-09:20 | 28.67 | 25.03 |
July | 0.616210E+11 | 76638.92 | 04-JUL-15:31 | 32.07 | 24.88 | 0.547577E+10 | 7498.94 | 13-JUL-09:20 | 28.50 | 25.13 |
August | 0.693079E+11 | 75952.93 | 22-AUG-03:02 | 27.12 | 24.30 | 0.613955E+10 | 7498.93 | 09-AUG-09:20 | 27.12 | 24.30 |
September | 0.610044E+11 | 74398.35 | 04-SEP-10:53 | 28.90 | 23.70 | 0.545446E+10 | 7498.94 | 07-SEP-09:20 | 26.83 | 24.30 |
October | 0.639954E+11 | 79739.09 | 15-OCT-16:35 | 28.50 | 20.76 | 0.567358E+10 | 7499.09 | 19-OCT-13:20 | 28.13 | 20.06 |
November | 0.629166E+11 | 98248.03 | 13-NOV-06:03 | 12.20 | 7.52 | 0.561774E+10 | 7502.13 | 15-NOV-10:30 | 25.00 | 17.25 |
December | 0.616896E+11 | 96138.02 | 21-DEC-05:12 | 10.77 | 9.99 | 0.547452E+10 | 7506.22 | 11-DEC-14:39 | 10.77 | 9.99 |
Annual Sum or Average | 0.730601E+12 | 0.680229E+11 | ||||||||
Minimum of Months | 0.537787E+11 | 73265.34 | 5.93 | 2.51 | 0.514286E+10 | 7498.93 | 10.77 | 9.99 | ||
Maximum of Months | 0.693079E+11 | 98248.03 | 32.07 | 24.88 | 0.613955E+10 | 7506.22 | 28.67 | 25.13 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.495486E+11 | 91939.23 | 17-JAN-05:11 | 13.13 | 11.78 | 0.507896E+10 | 6734.90 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.484367E+11 | 92008.01 | 21-FEB-05:13 | 16.33 | 15.55 | 0.460697E+10 | 6734.87 | 14-FEB-14:39 | 16.33 | 15.55 |
March | 0.627440E+11 | 88766.02 | 20-MAR-04:12 | 12.20 | 9.24 | 0.549678E+10 | 6734.82 | 01-MAR-10:20 | 12.20 | 9.24 |
April | 0.657847E+11 | 86275.10 | 19-APR-04:12 | 15.00 | 11.82 | 0.487814E+10 | 6734.85 | 20-APR-09:20 | 24.40 | 17.64 |
May | 0.609497E+11 | 82065.90 | 09-MAY-03:02 | 24.40 | 19.56 | 0.528431E+10 | 6734.71 | 15-MAY-09:20 | 28.90 | 23.15 |
June | 0.652387E+11 | 76816.74 | 19-JUN-04:33 | 24.40 | 23.01 | 0.526668E+10 | 6734.70 | 26-JUN-13:20 | 29.63 | 24.41 |
July | 0.690738E+11 | 77281.21 | 03-JUL-05:04 | 25.10 | 24.21 | 0.489421E+10 | 6734.69 | 31-JUL-09:20 | 30.57 | 25.52 |
August | 0.760450E+11 | 78929.66 | 28-AUG-05:03 | 26.02 | 24.78 | 0.549598E+10 | 6757.64 | 21-AUG-09:09 | 26.02 | 24.78 |
September | 0.607662E+11 | 76442.33 | 28-SEP-03:02 | 23.90 | 23.16 | 0.487959E+10 | 6734.84 | 11-SEP-13:39 | 23.90 | 23.16 |
October | 0.645795E+11 | 81559.59 | 02-OCT-05:04 | 26.70 | 25.31 | 0.507401E+10 | 6735.05 | 26-OCT-13:30 | 25.55 | 22.33 |
November | 0.614226E+11 | 91628.54 | 27-NOV-05:12 | 10.00 | 8.82 | 0.502799E+10 | 6734.90 | 30-NOV-14:39 | 27.20 | 24.74 |
December | 0.611420E+11 | 90102.20 | 18-DEC-05:12 | 17.20 | 17.20 | 0.489849E+10 | 6734.98 | 22-DEC-14:39 | 24.27 | 20.02 |
Annual Sum or Average | 0.745732E+12 | 0.608821E+11 | ||||||||
Minimum of Months | 0.484367E+11 | 76442.33 | 10.00 | 8.82 | 0.460697E+10 | 6734.69 | 12.20 | 9.24 | ||
Maximum of Months | 0.760450E+11 | 92008.01 | 26.70 | 25.31 | 0.549678E+10 | 6757.64 | 30.57 | 25.52 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388226E+11 | 79174.40 | 03-JAN-05:12 | 20.00 | 19.44 | 0.506529E+10 | 6734.90 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.365357E+11 | 81430.18 | 13-FEB-05:12 | 20.20 | 19.29 | 0.459400E+10 | 6734.85 | 23-FEB-10:20 | 23.33 | 17.54 |
March | 0.445403E+11 | 79337.15 | 07-MAR-05:12 | 20.40 | 19.02 | 0.549398E+10 | 6734.82 | 01-MAR-10:20 | 20.40 | 19.02 |
April | 0.451582E+11 | 78925.58 | 18-APR-04:12 | 19.03 | 14.99 | 0.487829E+10 | 6734.84 | 20-APR-09:20 | 24.40 | 17.64 |
May | 0.508261E+11 | 78426.67 | 26-MAY-05:04 | 23.98 | 22.02 | 0.528304E+10 | 6734.73 | 18-MAY-09:20 | 23.98 | 22.02 |
June | 0.522577E+11 | 68374.48 | 13-JUN-03:02 | 24.32 | 22.73 | 0.526640E+10 | 6734.75 | 09-JUN-09:20 | 24.32 | 22.73 |
July | 0.526106E+11 | 68340.12 | 06-JUL-04:04 | 23.90 | 22.27 | 0.489063E+10 | 6734.75 | 25-JUL-09:20 | 30.93 | 25.34 |
August | 0.539868E+11 | 74272.65 | 28-AUG-05:03 | 26.02 | 24.78 | 0.549352E+10 | 6734.80 | 07-AUG-13:20 | 26.02 | 24.78 |
September | 0.505363E+11 | 78091.19 | 26-SEP-05:04 | 23.30 | 22.01 | 0.487730E+10 | 6734.82 | 11-SEP-13:39 | 23.30 | 22.01 |
October | 0.498561E+11 | 77324.63 | 28-OCT-04:12 | 21.30 | 20.37 | 0.507259E+10 | 6734.89 | 26-OCT-13:39 | 21.30 | 20.37 |
November | 0.439939E+11 | 79309.85 | 01-NOV-04:12 | 19.80 | 18.44 | 0.502648E+10 | 6734.92 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.392934E+11 | 78398.39 | 04-DEC-05:11 | 16.87 | 15.18 | 0.488598E+10 | 6734.97 | 18-DEC-14:39 | 25.00 | 19.68 |
Annual Sum or Average | 0.558418E+12 | 0.608275E+11 | ||||||||
Minimum of Months | 0.365357E+11 | 68340.12 | 16.87 | 14.99 | 0.459400E+10 | 6734.73 | 20.40 | 15.05 | ||
Maximum of Months | 0.539868E+11 | 81430.18 | 26.02 | 24.78 | 0.549398E+10 | 6734.97 | 30.93 | 25.34 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339836E+11 | 77188.14 | 02-JAN-05:12 | 18.67 | 18.56 | 0.500439E+10 | 6734.85 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.344522E+11 | 77682.69 | 13-FEB-05:12 | 20.20 | 19.29 | 0.456422E+10 | 6734.83 | 23-FEB-10:20 | 23.33 | 17.54 |
March | 0.436768E+11 | 77260.96 | 31-MAR-04:12 | 22.60 | 19.02 | 0.547180E+10 | 6734.80 | 01-MAR-10:20 | 22.60 | 19.02 |
April | 0.470750E+11 | 77291.51 | 28-APR-04:12 | 22.40 | 18.25 | 0.487868E+10 | 6734.83 | 20-APR-09:20 | 22.40 | 18.25 |
May | 0.552575E+11 | 80119.37 | 01-MAY-04:12 | 20.93 | 19.77 | 0.528671E+10 | 6734.68 | 25-MAY-09:20 | 24.23 | 23.36 |
June | 0.574685E+11 | 75952.79 | 13-JUN-04:03 | 23.90 | 22.65 | 0.526998E+10 | 6734.69 | 05-JUN-13:20 | 23.90 | 22.65 |
July | 0.585093E+11 | 76439.20 | 24-JUL-05:03 | 23.90 | 23.53 | 0.489683E+10 | 6734.68 | 14-JUL-13:20 | 23.90 | 23.53 |
August | 0.586229E+11 | 76853.35 | 28-AUG-05:03 | 26.02 | 24.78 | 0.549588E+10 | 6734.72 | 07-AUG-13:20 | 26.02 | 24.78 |
September | 0.545303E+11 | 72309.61 | 26-SEP-04:12 | 23.30 | 22.40 | 0.488137E+10 | 6734.81 | 11-SEP-13:39 | 23.30 | 22.40 |
October | 0.512764E+11 | 76184.95 | 27-OCT-04:12 | 22.80 | 21.75 | 0.507622E+10 | 6734.94 | 26-OCT-13:39 | 22.80 | 21.75 |
November | 0.427185E+11 | 76685.09 | 18-NOV-05:11 | 20.60 | 19.09 | 0.501303E+10 | 6734.87 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.354761E+11 | 75230.69 | 01-DEC-05:12 | 22.57 | 18.22 | 0.484002E+10 | 6734.86 | 22-DEC-14:39 | 24.27 | 20.02 |
Annual Sum or Average | 0.573047E+12 | 0.606791E+11 | ||||||||
Minimum of Months | 0.339836E+11 | 72309.61 | 18.67 | 18.22 | 0.456422E+10 | 6734.68 | 21.70 | 15.05 | ||
Maximum of Months | 0.586229E+11 | 80119.37 | 26.02 | 24.78 | 0.549588E+10 | 6734.94 | 26.02 | 24.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500919E+10 | 11870.13 | 02-JAN-05:12 | 18.67 | 18.56 | 0.629416E+09 | 845.63 | 11-JAN-14:39 | 23.17 | 17.75 |
February | 0.582466E+10 | 11761.60 | 18-FEB-05:11 | 23.30 | 20.65 | 0.574811E+09 | 845.65 | 14-FEB-14:39 | 23.30 | 20.65 |
March | 0.799623E+10 | 12634.15 | 07-MAR-05:12 | 20.40 | 19.02 | 0.686734E+09 | 845.63 | 17-MAR-13:20 | 21.30 | 14.88 |
April | 0.996461E+10 | 16639.53 | 16-APR-13:02 | 31.70 | 20.63 | 0.612942E+09 | 845.63 | 20-APR-09:39 | 24.40 | 17.85 |
May | 0.112607E+11 | 16898.47 | 29-MAY-13:23 | 32.75 | 25.26 | 0.664914E+09 | 845.62 | 15-MAY-09:20 | 32.75 | 25.26 |
June | 0.128693E+11 | 16716.20 | 04-JUN-10:32 | 30.93 | 25.16 | 0.662890E+09 | 845.91 | 26-JUN-13:09 | 30.37 | 24.69 |
July | 0.135805E+11 | 17358.58 | 16-JUL-16:21 | 30.00 | 23.47 | 0.616677E+09 | 845.61 | 03-JUL-13:20 | 30.00 | 23.47 |
August | 0.137581E+11 | 16901.65 | 20-AUG-14:22 | 32.20 | 25.18 | 0.691384E+09 | 849.36 | 21-AUG-09:09 | 30.68 | 26.07 |
September | 0.110226E+11 | 16701.36 | 24-SEP-15:12 | 30.60 | 24.16 | 0.614125E+09 | 845.65 | 11-SEP-13:39 | 30.60 | 24.16 |
October | 0.101435E+11 | 12772.97 | 30-OCT-05:02 | 27.12 | 25.55 | 0.638146E+09 | 845.68 | 26-OCT-13:30 | 27.12 | 25.55 |
November | 0.844482E+10 | 12523.69 | 22-NOV-06:02 | 23.30 | 21.20 | 0.630657E+09 | 845.65 | 30-NOV-14:39 | 27.20 | 24.74 |
December | 0.675588E+10 | 13074.34 | 11-DEC-05:22 | 22.20 | 21.61 | 0.611028E+09 | 845.66 | 18-DEC-14:30 | 25.00 | 19.78 |
Annual Sum or Average | 0.116630E+12 | 0.763373E+10 | ||||||||
Minimum of Months | 0.500919E+10 | 11761.60 | 18.67 | 18.56 | 0.574811E+09 | 845.61 | 21.30 | 14.88 | ||
Maximum of Months | 0.137581E+11 | 17358.58 | 32.75 | 25.55 | 0.691384E+09 | 849.36 | 32.75 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453561E+10 | 12389.58 | 01-JAN-09:43 | 24.63 | 21.02 | 0.409305E+09 | 544.97 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.503803E+10 | 11614.82 | 20-FEB-09:23 | 19.45 | 16.01 | 0.371912E+09 | 544.97 | 14-FEB-14:39 | 19.45 | 16.01 |
March | 0.703000E+10 | 10190.11 | 27-MAR-08:40 | 23.17 | 21.01 | 0.444218E+09 | 544.96 | 01-MAR-10:09 | 23.17 | 21.01 |
April | 0.828259E+10 | 18089.48 | 16-APR-08:22 | 24.45 | 21.59 | 0.395335E+09 | 545.86 | 17-APR-09:50 | 23.95 | 20.74 |
May | 0.925672E+10 | 17853.07 | 07-MAY-08:52 | 26.70 | 21.74 | 0.428723E+09 | 545.44 | 17-MAY-09:00 | 29.40 | 23.47 |
June | 0.983153E+10 | 18358.84 | 04-JUN-08:32 | 29.27 | 25.11 | 0.427309E+09 | 546.03 | 12-JUN-09:00 | 30.60 | 24.52 |
July | 0.102844E+11 | 18299.36 | 30-JUL-09:02 | 30.18 | 24.67 | 0.397620E+09 | 545.37 | 24-JUL-09:00 | 30.18 | 24.67 |
August | 0.996325E+10 | 17433.88 | 27-AUG-09:42 | 30.82 | 25.64 | 0.445531E+09 | 548.38 | 21-AUG-09:09 | 30.82 | 25.64 |
September | 0.902363E+10 | 17871.43 | 24-SEP-09:12 | 29.40 | 25.34 | 0.396134E+09 | 544.97 | 11-SEP-13:39 | 29.40 | 25.34 |
October | 0.824907E+10 | 17367.84 | 09-OCT-07:53 | 27.20 | 24.01 | 0.411553E+09 | 544.99 | 26-OCT-13:30 | 25.55 | 22.33 |
November | 0.640440E+10 | 9396.75 | 20-NOV-06:02 | 24.40 | 20.29 | 0.406743E+09 | 544.97 | 30-NOV-14:39 | 27.20 | 24.74 |
December | 0.476855E+10 | 12111.06 | 11-DEC-06:02 | 22.20 | 21.65 | 0.394064E+09 | 544.98 | 22-DEC-14:39 | 24.27 | 20.02 |
Annual Sum or Average | 0.926677E+11 | 0.492845E+10 | ||||||||
Minimum of Months | 0.453561E+10 | 9396.75 | 19.45 | 16.01 | 0.371912E+09 | 544.96 | 19.45 | 15.05 | ||
Maximum of Months | 0.102844E+11 | 18358.84 | 30.82 | 25.64 | 0.445531E+09 | 548.38 | 30.82 | 25.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109965E+11 | 19103.39 | 15-JAN-13:52 | 25.60 | 16.48 | 0.643197E+09 | 965.75 | 02-JAN-14:39 | 25.60 | 16.48 |
February | 0.105853E+11 | 18075.00 | 20-FEB-14:02 | 26.20 | 17.78 | 0.583708E+09 | 941.72 | 21-FEB-14:39 | 25.93 | 14.05 |
March | 0.120192E+11 | 17530.01 | 12-MAR-13:32 | 24.80 | 18.27 | 0.690039E+09 | 900.97 | 01-MAR-14:39 | 24.80 | 18.27 |
April | 0.116251E+11 | 17387.72 | 16-APR-13:02 | 31.70 | 20.63 | 0.613528E+09 | 846.19 | 25-APR-13:00 | 27.20 | 24.01 |
May | 0.112144E+11 | 16972.90 | 29-MAY-13:23 | 32.75 | 25.26 | 0.664875E+09 | 845.93 | 22-MAY-13:00 | 32.75 | 25.26 |
June | 0.122170E+11 | 14333.77 | 08-JUN-04:12 | 28.70 | 25.26 | 0.662699E+09 | 845.64 | 12-JUN-09:00 | 30.60 | 24.52 |
July | 0.131967E+11 | 17300.26 | 16-JUL-14:21 | 31.10 | 24.42 | 0.616501E+09 | 845.94 | 26-JUL-13:00 | 31.70 | 25.48 |
August | 0.146237E+11 | 17130.32 | 20-AUG-14:22 | 32.20 | 25.18 | 0.691672E+09 | 861.41 | 31-AUG-13:20 | 31.70 | 24.32 |
September | 0.137543E+11 | 18237.42 | 24-SEP-12:32 | 31.10 | 24.23 | 0.615203E+09 | 876.04 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.150870E+11 | 18045.57 | 29-OCT-12:22 | 30.30 | 25.36 | 0.645645E+09 | 915.59 | 19-OCT-13:39 | 30.30 | 25.36 |
November | 0.137933E+11 | 18220.86 | 23-NOV-12:42 | 27.20 | 24.02 | 0.643419E+09 | 983.78 | 07-NOV-14:09 | 27.20 | 24.02 |
December | 0.126937E+11 | 19721.10 | 10-DEC-12:41 | 28.22 | 23.46 | 0.622525E+09 | 985.39 | 04-DEC-14:30 | 28.22 | 23.46 |
Annual Sum or Average | 0.151806E+12 | 0.769301E+10 | ||||||||
Minimum of Months | 0.105853E+11 | 14333.77 | 24.80 | 16.48 | 0.583708E+09 | 845.64 | 24.80 | 14.05 | ||
Maximum of Months | 0.150870E+11 | 19721.10 | 32.75 | 25.36 | 0.691672E+09 | 985.39 | 32.75 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.584362E+10 | 17564.39 | 15-JAN-14:32 | 25.60 | 16.84 | 0.410780E+09 | 544.97 | 11-JAN-14:39 | 25.60 | 16.84 |
February | 0.748373E+10 | 22977.47 | 19-FEB-16:32 | 26.87 | 21.78 | 0.373436E+09 | 544.99 | 14-FEB-14:39 | 26.87 | 21.78 |
March | 0.112392E+11 | 23551.90 | 12-MAR-16:12 | 24.40 | 18.45 | 0.446264E+09 | 544.96 | 24-MAR-13:00 | 26.10 | 19.80 |
April | 0.138975E+11 | 24315.89 | 02-APR-16:21 | 26.15 | 18.17 | 0.396769E+09 | 544.96 | 20-APR-09:39 | 24.40 | 17.85 |
May | 0.114545E+11 | 23265.55 | 29-MAY-16:02 | 33.03 | 24.50 | 0.429425E+09 | 544.95 | 15-MAY-09:20 | 33.03 | 24.50 |
June | 0.126533E+11 | 22252.00 | 10-JUN-17:04 | 30.60 | 24.10 | 0.427992E+09 | 544.96 | 12-JUN-09:00 | 30.60 | 24.52 |
July | 0.146800E+11 | 25186.61 | 16-JUL-16:21 | 30.00 | 23.47 | 0.398387E+09 | 544.95 | 31-JUL-09:20 | 30.57 | 25.52 |
August | 0.171076E+11 | 24052.35 | 20-AUG-16:22 | 30.60 | 24.86 | 0.446651E+09 | 548.39 | 21-AUG-09:09 | 30.68 | 26.07 |
September | 0.108253E+11 | 22862.18 | 10-SEP-15:22 | 31.10 | 25.13 | 0.396649E+09 | 544.97 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.113926E+11 | 20908.82 | 09-OCT-16:32 | 29.07 | 23.73 | 0.412564E+09 | 545.00 | 26-OCT-13:30 | 25.55 | 22.33 |
November | 0.102991E+11 | 22675.69 | 23-NOV-14:02 | 27.20 | 24.01 | 0.408355E+09 | 544.99 | 30-NOV-14:39 | 27.20 | 24.74 |
December | 0.995156E+10 | 25307.48 | 10-DEC-15:21 | 28.60 | 22.59 | 0.398014E+09 | 545.01 | 22-DEC-14:39 | 24.27 | 20.02 |
Annual Sum or Average | 0.136828E+12 | 0.494529E+10 | ||||||||
Minimum of Months | 0.584362E+10 | 17564.39 | 24.40 | 16.84 | 0.373436E+09 | 544.95 | 24.27 | 16.84 | ||
Maximum of Months | 0.171076E+11 | 25307.48 | 33.03 | 25.13 | 0.446651E+09 | 548.39 | 33.03 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380863E+10 | 9310.06 | 14-JAN-06:02 | 23.62 | 21.60 | 0.601601E+09 | 845.62 | 11-JAN-14:50 | 23.62 | 21.60 |
February | 0.421685E+10 | 11192.06 | 11-FEB-06:02 | 23.90 | 22.27 | 0.563668E+09 | 845.63 | 14-FEB-14:39 | 24.23 | 20.09 |
March | 0.562016E+10 | 11193.67 | 10-MAR-06:02 | 23.30 | 22.07 | 0.671312E+09 | 845.62 | 23-MAR-09:20 | 23.17 | 17.42 |
April | 0.712844E+10 | 11549.70 | 12-APR-05:02 | 24.50 | 22.52 | 0.612106E+09 | 845.63 | 20-APR-09:20 | 24.40 | 17.64 |
May | 0.101476E+11 | 16415.61 | 29-MAY-13:02 | 33.12 | 25.44 | 0.665025E+09 | 845.62 | 18-MAY-09:20 | 33.12 | 25.44 |
June | 0.115185E+11 | 16292.60 | 25-JUN-17:12 | 29.40 | 24.47 | 0.663218E+09 | 846.60 | 29-JUN-13:20 | 31.10 | 25.19 |
July | 0.117853E+11 | 17012.05 | 09-JUL-16:51 | 30.00 | 25.18 | 0.616878E+09 | 845.63 | 25-JUL-09:20 | 30.93 | 25.34 |
August | 0.110537E+11 | 16416.64 | 13-AUG-16:01 | 30.50 | 25.69 | 0.691484E+09 | 845.63 | 07-AUG-13:20 | 30.50 | 25.69 |
September | 0.994148E+10 | 16036.58 | 24-SEP-16:42 | 30.10 | 24.71 | 0.614293E+09 | 845.64 | 11-SEP-13:39 | 30.10 | 24.71 |
October | 0.823371E+10 | 15508.83 | 08-OCT-14:22 | 29.40 | 23.97 | 0.638217E+09 | 845.64 | 26-OCT-13:39 | 24.27 | 21.92 |
November | 0.609417E+10 | 11401.82 | 22-NOV-06:02 | 23.30 | 21.20 | 0.625984E+09 | 845.63 | 30-NOV-14:39 | 27.20 | 24.74 |
December | 0.416668E+10 | 11629.39 | 07-DEC-06:02 | 22.88 | 21.29 | 0.585648E+09 | 845.64 | 18-DEC-14:39 | 25.00 | 19.68 |
Annual Sum or Average | 0.937152E+11 | 0.754943E+10 | ||||||||
Minimum of Months | 0.380863E+10 | 9310.06 | 22.88 | 21.20 | 0.563668E+09 | 845.62 | 23.17 | 17.42 | ||
Maximum of Months | 0.117853E+11 | 17012.05 | 33.12 | 25.69 | 0.691484E+09 | 846.60 | 33.12 | 25.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357385E+10 | 18005.21 | 01-JAN-10:02 | 25.28 | 21.21 | 0.299459E+09 | 548.52 | 27-JAN-11:09 | 21.88 | 15.22 |
February | 0.413561E+10 | 10388.94 | 26-FEB-10:33 | 23.33 | 16.17 | 0.272962E+09 | 548.49 | 06-FEB-13:09 | 23.33 | 16.17 |
March | 0.586492E+10 | 11704.97 | 27-MAR-10:05 | 25.28 | 21.59 | 0.326587E+09 | 548.50 | 22-MAR-10:09 | 25.28 | 21.59 |
April | 0.728005E+10 | 18953.38 | 09-APR-09:22 | 25.00 | 18.86 | 0.292447E+09 | 548.50 | 20-APR-10:09 | 24.68 | 18.29 |
May | 0.885160E+10 | 18917.04 | 07-MAY-10:22 | 28.60 | 21.92 | 0.316930E+09 | 548.49 | 22-MAY-14:09 | 33.35 | 23.88 |
June | 0.947536E+10 | 19503.95 | 04-JUN-08:32 | 29.27 | 25.11 | 0.315688E+09 | 548.48 | 30-JUN-10:09 | 29.72 | 25.17 |
July | 0.989175E+10 | 20115.68 | 04-JUL-09:41 | 30.40 | 24.81 | 0.294817E+09 | 548.49 | 26-JUL-14:09 | 31.42 | 25.29 |
August | 0.927567E+10 | 18200.06 | 27-AUG-09:23 | 30.25 | 25.24 | 0.329052E+09 | 548.49 | 08-AUG-10:09 | 30.25 | 25.24 |
September | 0.871378E+10 | 18825.23 | 24-SEP-08:42 | 29.03 | 25.60 | 0.293170E+09 | 548.49 | 07-SEP-14:09 | 29.03 | 25.60 |
October | 0.754094E+10 | 16758.58 | 08-OCT-14:22 | 29.40 | 23.97 | 0.304830E+09 | 548.50 | 26-OCT-14:09 | 22.07 | 21.01 |
November | 0.535236E+10 | 10820.98 | 19-NOV-11:12 | 26.70 | 21.59 | 0.300351E+09 | 548.50 | 27-NOV-11:09 | 22.38 | 16.72 |
December | 0.337534E+10 | 11501.42 | 03-DEC-10:32 | 21.83 | 17.84 | 0.287385E+09 | 548.50 | 18-DEC-15:09 | 25.00 | 19.47 |
Annual Sum or Average | 0.833312E+11 | 0.363368E+10 | ||||||||
Minimum of Months | 0.337534E+10 | 10388.94 | 21.83 | 16.17 | 0.272962E+09 | 548.48 | 21.88 | 15.22 | ||
Maximum of Months | 0.989175E+10 | 20115.68 | 30.40 | 25.60 | 0.329052E+09 | 548.52 | 33.35 | 25.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102894E+11 | 17414.76 | 01-JAN-10:02 | 25.28 | 21.21 | 0.644840E+09 | 1001.44 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.953285E+10 | 17971.74 | 26-FEB-13:52 | 25.60 | 16.51 | 0.583635E+09 | 965.25 | 21-FEB-14:50 | 25.60 | 16.51 |
March | 0.992886E+10 | 16637.35 | 26-MAR-14:32 | 27.80 | 21.96 | 0.686695E+09 | 921.86 | 01-MAR-14:39 | 27.80 | 21.96 |
April | 0.899076E+10 | 16190.51 | 16-APR-14:32 | 31.70 | 21.16 | 0.613333E+09 | 846.48 | 25-APR-13:20 | 27.93 | 23.68 |
May | 0.100843E+11 | 16335.10 | 29-MAY-13:02 | 33.12 | 25.44 | 0.664967E+09 | 846.67 | 23-MAY-13:20 | 33.12 | 25.44 |
June | 0.108051E+11 | 15876.70 | 25-JUN-17:12 | 29.40 | 24.47 | 0.662960E+09 | 846.55 | 29-JUN-13:20 | 31.10 | 25.19 |
July | 0.113921E+11 | 16620.10 | 09-JUL-16:11 | 30.73 | 25.05 | 0.616678E+09 | 846.63 | 11-JUL-13:20 | 31.10 | 24.96 |
August | 0.121201E+11 | 16438.19 | 13-AUG-16:01 | 30.50 | 25.69 | 0.691874E+09 | 861.47 | 31-AUG-13:00 | 31.70 | 23.81 |
September | 0.129880E+11 | 17475.59 | 24-SEP-12:02 | 31.10 | 24.78 | 0.616412E+09 | 898.74 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.138146E+11 | 18194.58 | 15-OCT-14:32 | 29.23 | 21.31 | 0.650065E+09 | 947.17 | 25-OCT-13:00 | 30.60 | 22.69 |
November | 0.121610E+11 | 18605.49 | 19-NOV-13:12 | 26.70 | 21.27 | 0.646949E+09 | 1019.02 | 07-NOV-14:09 | 26.70 | 21.27 |
December | 0.105109E+11 | 19621.91 | 03-DEC-13:51 | 24.40 | 18.35 | 0.620289E+09 | 1016.53 | 04-DEC-14:39 | 25.93 | 17.99 |
Annual Sum or Average | 0.132618E+12 | 0.769870E+10 | ||||||||
Minimum of Months | 0.899076E+10 | 15876.70 | 24.40 | 16.51 | 0.583635E+09 | 846.48 | 25.60 | 16.51 | ||
Maximum of Months | 0.138146E+11 | 19621.91 | 33.12 | 25.69 | 0.691874E+09 | 1019.02 | 33.12 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.376732E+10 | 10107.91 | 14-JAN-06:02 | 23.62 | 21.60 | 0.399785E+09 | 544.96 | 11-JAN-14:39 | 23.62 | 21.60 |
February | 0.458064E+10 | 19967.85 | 19-FEB-16:12 | 27.03 | 21.82 | 0.368471E+09 | 544.97 | 14-FEB-14:39 | 27.03 | 21.82 |
March | 0.656649E+10 | 20037.72 | 12-MAR-16:22 | 24.40 | 18.50 | 0.439595E+09 | 544.96 | 17-MAR-13:20 | 21.30 | 14.88 |
April | 0.807937E+10 | 22245.42 | 09-APR-17:21 | 26.15 | 18.42 | 0.396006E+09 | 544.96 | 20-APR-09:39 | 24.40 | 17.85 |
May | 0.935499E+10 | 20916.96 | 29-MAY-16:22 | 32.50 | 24.46 | 0.429246E+09 | 544.95 | 18-MAY-09:20 | 32.50 | 24.46 |
June | 0.940011E+10 | 19951.02 | 25-JUN-17:12 | 29.40 | 24.47 | 0.427813E+09 | 544.95 | 12-JUN-09:20 | 29.40 | 24.47 |
July | 0.102516E+11 | 22960.62 | 09-JUL-16:51 | 30.00 | 25.18 | 0.398108E+09 | 544.95 | 25-JUL-09:20 | 30.93 | 25.34 |
August | 0.102472E+11 | 21888.78 | 13-AUG-16:01 | 30.50 | 25.69 | 0.446285E+09 | 544.96 | 07-AUG-13:20 | 30.50 | 25.69 |
September | 0.873345E+10 | 20929.29 | 17-SEP-16:21 | 31.10 | 24.77 | 0.396505E+09 | 544.96 | 11-SEP-13:39 | 31.10 | 24.77 |
October | 0.795563E+10 | 20800.21 | 15-OCT-16:32 | 28.50 | 20.76 | 0.412208E+09 | 544.97 | 26-OCT-13:39 | 24.27 | 21.92 |
November | 0.594090E+10 | 19886.96 | 05-NOV-16:12 | 27.80 | 24.12 | 0.405558E+09 | 544.97 | 30-NOV-14:39 | 27.20 | 24.74 |
December | 0.442821E+10 | 21311.68 | 10-DEC-15:31 | 28.50 | 22.56 | 0.388091E+09 | 544.98 | 18-DEC-14:39 | 25.00 | 19.68 |
Annual Sum or Average | 0.893060E+11 | 0.490767E+10 | ||||||||
Minimum of Months | 0.376732E+10 | 10107.91 | 23.62 | 18.42 | 0.368471E+09 | 544.95 | 21.30 | 14.88 | ||
Maximum of Months | 0.102516E+11 | 22960.62 | 32.50 | 25.69 | 0.446285E+09 | 544.98 | 32.50 | 25.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.346361E+10 | 10412.89 | 14-JAN-06:02 | 23.62 | 21.60 | 0.587667E+09 | 845.62 | 11-JAN-14:20 | 23.62 | 21.60 |
February | 0.408300E+10 | 12159.27 | 11-FEB-06:02 | 23.90 | 22.27 | 0.556090E+09 | 845.63 | 14-FEB-14:39 | 24.23 | 20.09 |
March | 0.562607E+10 | 11537.17 | 06-MAR-05:12 | 22.80 | 22.08 | 0.663623E+09 | 845.63 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.736716E+10 | 12686.08 | 12-APR-05:02 | 24.50 | 22.52 | 0.611025E+09 | 845.63 | 20-APR-09:20 | 24.40 | 17.64 |
May | 0.107096E+11 | 18741.38 | 29-MAY-13:02 | 33.12 | 25.44 | 0.665127E+09 | 845.61 | 23-MAY-13:20 | 33.12 | 25.44 |
June | 0.122004E+11 | 19360.11 | 11-JUN-16:11 | 30.93 | 24.21 | 0.663340E+09 | 845.68 | 02-JUN-13:50 | 30.93 | 24.21 |
July | 0.125915E+11 | 19652.89 | 09-JUL-16:51 | 30.00 | 25.18 | 0.617087E+09 | 845.61 | 03-JUL-13:20 | 30.00 | 25.18 |
August | 0.116526E+11 | 18404.26 | 13-AUG-17:32 | 29.27 | 25.27 | 0.691553E+09 | 845.62 | 07-AUG-13:20 | 29.27 | 25.27 |
September | 0.104971E+11 | 18526.49 | 04-SEP-13:42 | 30.00 | 24.10 | 0.614393E+09 | 845.63 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.845324E+10 | 18381.25 | 08-OCT-14:22 | 29.40 | 23.97 | 0.638123E+09 | 845.65 | 26-OCT-13:39 | 24.27 | 21.92 |
November | 0.602840E+10 | 11715.67 | 29-NOV-06:02 | 25.00 | 19.84 | 0.622032E+09 | 845.63 | 13-NOV-14:20 | 25.00 | 19.84 |
December | 0.394076E+10 | 11204.70 | 11-DEC-06:02 | 22.20 | 21.65 | 0.573106E+09 | 845.63 | 18-DEC-14:30 | 25.00 | 19.78 |
Annual Sum or Average | 0.966135E+11 | 0.750317E+10 | ||||||||
Minimum of Months | 0.346361E+10 | 10412.89 | 22.20 | 19.84 | 0.556090E+09 | 845.61 | 23.30 | 17.64 | ||
Maximum of Months | 0.125915E+11 | 19652.89 | 33.12 | 25.44 | 0.691553E+09 | 845.68 | 33.12 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344050E+10 | 10238.58 | 01-JAN-11:43 | 26.20 | 21.28 | 0.403052E+09 | 544.98 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.419345E+10 | 8004.74 | 11-FEB-06:02 | 23.90 | 22.27 | 0.368008E+09 | 544.97 | 23-FEB-10:39 | 23.87 | 17.94 |
March | 0.600213E+10 | 10703.56 | 26-MAR-10:43 | 25.60 | 21.37 | 0.442315E+09 | 544.96 | 17-MAR-09:09 | 25.60 | 21.37 |
April | 0.766914E+10 | 19191.63 | 09-APR-09:32 | 25.37 | 18.85 | 0.395412E+09 | 544.96 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.949038E+10 | 18498.01 | 07-MAY-08:32 | 26.33 | 21.77 | 0.428958E+09 | 545.38 | 17-MAY-09:00 | 29.40 | 23.47 |
June | 0.101873E+11 | 20065.70 | 11-JUN-09:32 | 30.40 | 23.99 | 0.427746E+09 | 545.81 | 12-JUN-09:00 | 30.60 | 24.52 |
July | 0.106905E+11 | 19900.21 | 30-JUL-09:42 | 30.92 | 24.62 | 0.398111E+09 | 545.29 | 25-JUL-09:00 | 30.92 | 24.62 |
August | 0.995128E+10 | 18349.35 | 27-AUG-09:13 | 29.97 | 25.04 | 0.445977E+09 | 545.34 | 31-AUG-09:30 | 30.30 | 24.08 |
September | 0.933798E+10 | 18411.18 | 10-SEP-09:42 | 29.72 | 24.76 | 0.396405E+09 | 544.96 | 11-SEP-13:39 | 28.73 | 24.51 |
October | 0.794807E+10 | 18055.89 | 08-OCT-14:22 | 29.40 | 23.97 | 0.411891E+09 | 544.98 | 26-OCT-13:30 | 25.55 | 22.33 |
November | 0.548836E+10 | 9470.16 | 29-NOV-06:02 | 25.00 | 19.84 | 0.405477E+09 | 544.97 | 27-NOV-10:00 | 25.00 | 19.84 |
December | 0.339297E+10 | 9532.43 | 11-DEC-06:02 | 22.20 | 21.65 | 0.385615E+09 | 544.97 | 22-DEC-14:39 | 24.27 | 20.02 |
Annual Sum or Average | 0.877920E+11 | 0.490897E+10 | ||||||||
Minimum of Months | 0.339297E+10 | 8004.74 | 22.20 | 18.85 | 0.368008E+09 | 544.96 | 21.70 | 15.05 | ||
Maximum of Months | 0.106905E+11 | 20065.70 | 30.92 | 25.04 | 0.445977E+09 | 545.81 | 30.92 | 24.62 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.967922E+10 | 20823.07 | 15-JAN-14:22 | 25.60 | 16.75 | 0.632231E+09 | 956.70 | 02-JAN-14:39 | 25.60 | 16.75 |
February | 0.929721E+10 | 21376.82 | 20-FEB-14:31 | 26.50 | 17.84 | 0.575965E+09 | 926.36 | 21-FEB-14:50 | 26.02 | 13.83 |
March | 0.980874E+10 | 18803.65 | 12-MAR-13:32 | 24.80 | 18.27 | 0.680601E+09 | 882.30 | 01-MAR-14:39 | 24.80 | 18.27 |
April | 0.922257E+10 | 18526.80 | 23-APR-14:02 | 26.60 | 21.71 | 0.612452E+09 | 846.08 | 14-APR-13:39 | 26.60 | 21.71 |
May | 0.106383E+11 | 18816.37 | 29-MAY-13:02 | 33.12 | 25.44 | 0.665038E+09 | 845.93 | 22-MAY-13:00 | 33.12 | 25.44 |
June | 0.114744E+11 | 19095.90 | 11-JUN-16:11 | 30.93 | 24.21 | 0.663122E+09 | 845.63 | 21-JUN-13:20 | 29.40 | 23.58 |
July | 0.121949E+11 | 19408.51 | 09-JUL-16:11 | 30.73 | 25.05 | 0.616901E+09 | 845.91 | 26-JUL-13:00 | 31.70 | 25.48 |
August | 0.127173E+11 | 18806.96 | 06-AUG-13:23 | 32.75 | 25.17 | 0.691755E+09 | 846.83 | 31-AUG-13:00 | 31.70 | 23.81 |
September | 0.135906E+11 | 19325.73 | 04-SEP-13:42 | 30.00 | 24.10 | 0.615375E+09 | 877.22 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.141455E+11 | 20776.01 | 15-OCT-14:32 | 29.23 | 21.31 | 0.644849E+09 | 918.02 | 25-OCT-13:00 | 30.60 | 22.69 |
November | 0.120395E+11 | 20118.89 | 05-NOV-13:32 | 27.20 | 24.11 | 0.638484E+09 | 980.70 | 07-NOV-14:09 | 28.30 | 20.78 |
December | 0.100313E+11 | 20190.67 | 03-DEC-14:02 | 24.40 | 18.40 | 0.609446E+09 | 972.02 | 04-DEC-14:39 | 25.93 | 17.99 |
Annual Sum or Average | 0.134840E+12 | 0.764622E+10 | ||||||||
Minimum of Months | 0.922257E+10 | 18526.80 | 24.40 | 16.75 | 0.575965E+09 | 845.63 | 24.80 | 13.83 | ||
Maximum of Months | 0.141455E+11 | 21376.82 | 33.12 | 25.44 | 0.691755E+09 | 980.70 | 33.12 | 25.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.352066E+10 | 11959.68 | 14-JAN-06:02 | 23.62 | 21.60 | 0.392029E+09 | 544.95 | 11-JAN-14:20 | 23.62 | 21.60 |
February | 0.448297E+10 | 21873.94 | 20-FEB-16:31 | 26.70 | 17.88 | 0.365095E+09 | 544.97 | 21-FEB-14:00 | 26.10 | 13.62 |
March | 0.653967E+10 | 21749.26 | 12-MAR-16:52 | 24.40 | 18.65 | 0.435156E+09 | 544.96 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.822346E+10 | 22914.28 | 09-APR-16:11 | 27.03 | 18.57 | 0.395754E+09 | 544.96 | 20-APR-09:39 | 24.40 | 17.85 |
May | 0.972942E+10 | 22602.00 | 29-MAY-16:22 | 32.50 | 24.46 | 0.429241E+09 | 544.94 | 23-MAY-13:20 | 32.50 | 24.46 |
June | 0.985990E+10 | 23484.73 | 11-JUN-14:51 | 31.10 | 24.60 | 0.427841E+09 | 544.95 | 21-JUN-13:20 | 29.40 | 23.58 |
July | 0.107874E+11 | 25036.29 | 09-JUL-16:51 | 30.00 | 25.18 | 0.398159E+09 | 544.94 | 17-JUL-13:20 | 25.97 | 23.85 |
August | 0.106354E+11 | 22259.46 | 13-AUG-16:11 | 30.40 | 25.65 | 0.446277E+09 | 544.95 | 07-AUG-13:20 | 30.40 | 25.65 |
September | 0.911283E+10 | 22563.22 | 17-SEP-16:21 | 31.10 | 24.77 | 0.396485E+09 | 544.96 | 11-SEP-13:39 | 31.10 | 24.77 |
October | 0.810285E+10 | 22409.50 | 08-OCT-15:42 | 28.98 | 23.77 | 0.412140E+09 | 544.97 | 26-OCT-13:39 | 24.27 | 21.92 |
November | 0.586406E+10 | 21284.28 | 05-NOV-16:12 | 27.80 | 24.12 | 0.403754E+09 | 544.96 | 30-NOV-14:30 | 27.20 | 24.74 |
December | 0.421896E+10 | 17190.94 | 10-DEC-15:42 | 28.40 | 22.53 | 0.381744E+09 | 544.98 | 18-DEC-14:30 | 25.00 | 19.78 |
Annual Sum or Average | 0.910776E+11 | 0.488368E+10 | ||||||||
Minimum of Months | 0.352066E+10 | 11959.68 | 23.62 | 17.88 | 0.365095E+09 | 544.94 | 23.30 | 13.62 | ||
Maximum of Months | 0.107874E+11 | 25036.29 | 32.50 | 25.65 | 0.446277E+09 | 544.98 | 32.50 | 25.65 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.540848E+10 | 13511.97 | 02-JAN-06:15 | 19.23 | 19.01 | 0.00 | 0.00 | 01-JAN-00:10 | 19.23 | 19.01 |
February | 0.601895E+10 | 11283.24 | 21-FEB-06:15 | 15.60 | 15.30 | 0.00 | 0.00 | 01-FEB-00:10 | 15.60 | 15.30 |
March | 0.800825E+10 | 10523.06 | 27-MAR-05:15 | 20.40 | 20.06 | 0.00 | 0.00 | 01-MAR-00:10 | 20.40 | 20.06 |
April | 0.976076E+10 | 13387.91 | 17-APR-05:15 | 18.90 | 16.76 | 0.00 | 0.00 | 01-APR-00:10 | 18.90 | 16.76 |
May | 0.107327E+11 | 15877.01 | 30-MAY-05:13 | 24.03 | 22.53 | 0.00 | 0.00 | 01-MAY-00:10 | 24.03 | 22.53 |
June | 0.121331E+11 | 15136.86 | 12-JUN-05:15 | 25.60 | 24.44 | 0.00 | 0.00 | 01-JUN-00:10 | 25.60 | 24.44 |
July | 0.133450E+11 | 15850.19 | 31-JUL-05:13 | 26.10 | 24.39 | 0.00 | 0.00 | 01-JUL-00:10 | 26.10 | 24.39 |
August | 0.135873E+11 | 15895.94 | 21-AUG-05:15 | 27.20 | 24.60 | 0.00 | 0.00 | 01-AUG-00:10 | 27.20 | 24.60 |
September | 0.113945E+11 | 15050.91 | 11-SEP-05:15 | 27.03 | 24.29 | 0.00 | 0.00 | 01-SEP-00:10 | 27.03 | 24.29 |
October | 0.105786E+11 | 14673.06 | 30-OCT-05:15 | 27.03 | 25.52 | 0.00 | 0.00 | 01-OCT-00:10 | 27.03 | 25.52 |
November | 0.868883E+10 | 11825.33 | 20-NOV-06:15 | 24.40 | 20.29 | 0.00 | 0.00 | 01-NOV-00:10 | 24.40 | 20.29 |
December | 0.669989E+10 | 12869.07 | 11-DEC-06:15 | 22.20 | 21.45 | 0.00 | 0.00 | 01-DEC-00:10 | 22.20 | 21.45 |
Annual Sum or Average | 0.116356E+12 | 0.00 | ||||||||
Minimum of Months | 0.540848E+10 | 10523.06 | 15.60 | 15.30 | 0.00 | 0.00 | 15.60 | 15.30 | ||
Maximum of Months | 0.135873E+11 | 15895.94 | 27.20 | 25.52 | 0.00 | 0.00 | 27.20 | 25.52 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.337066E+10 | 9636.09 | 02-JAN-06:15 | 19.23 | 19.01 | 0.00 | 0.00 | 01-JAN-00:10 | 19.23 | 19.01 |
February | 0.373197E+10 | 6016.88 | 17-FEB-16:30 | 25.85 | 21.29 | 0.00 | 0.00 | 01-FEB-00:10 | 25.85 | 21.29 |
March | 0.537664E+10 | 7776.14 | 06-MAR-06:15 | 22.80 | 21.91 | 0.00 | 0.00 | 01-MAR-00:10 | 22.80 | 21.91 |
April | 0.699800E+10 | 8350.43 | 17-APR-05:02 | 18.90 | 16.76 | 0.00 | 0.00 | 01-APR-00:10 | 18.90 | 16.76 |
May | 0.921438E+10 | 10062.10 | 30-MAY-05:03 | 24.22 | 22.51 | 0.00 | 0.00 | 01-MAY-00:10 | 24.22 | 22.51 |
June | 0.102535E+11 | 11386.45 | 05-JUN-05:13 | 25.40 | 23.71 | 0.00 | 0.00 | 01-JUN-00:10 | 25.40 | 23.71 |
July | 0.107527E+11 | 11093.97 | 10-JUL-05:02 | 26.78 | 24.63 | 0.00 | 0.00 | 01-JUL-00:10 | 26.78 | 24.63 |
August | 0.102415E+11 | 10869.49 | 21-AUG-05:01 | 27.20 | 24.67 | 0.00 | 0.00 | 01-AUG-00:10 | 27.20 | 24.67 |
September | 0.973726E+10 | 11928.91 | 05-SEP-05:15 | 22.93 | 21.59 | 0.00 | 0.00 | 01-SEP-00:10 | 22.93 | 21.59 |
October | 0.860086E+10 | 9613.23 | 23-OCT-05:15 | 23.53 | 21.79 | 0.00 | 0.00 | 01-OCT-00:10 | 23.53 | 21.79 |
November | 0.613379E+10 | 9733.50 | 06-NOV-06:15 | 20.93 | 19.77 | 0.00 | 0.00 | 01-NOV-00:10 | 20.93 | 19.77 |
December | 0.386656E+10 | 8640.16 | 11-DEC-06:15 | 22.20 | 21.45 | 0.00 | 0.00 | 01-DEC-00:10 | 22.20 | 21.45 |
Annual Sum or Average | 0.882778E+11 | 0.00 | ||||||||
Minimum of Months | 0.337066E+10 | 6016.88 | 18.90 | 16.76 | 0.00 | 0.00 | 18.90 | 16.76 | ||
Maximum of Months | 0.107527E+11 | 11928.91 | 27.20 | 24.67 | 0.00 | 0.00 | 27.20 | 24.67 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425543E+10 | 12891.60 | 02-JAN-15:00 | 28.90 | 23.37 | 0.00 | 0.00 | 01-JAN-00:10 | 28.90 | 23.37 |
February | 0.590833E+10 | 12991.81 | 16-FEB-15:00 | 26.10 | 20.75 | 0.00 | 0.00 | 01-FEB-00:10 | 26.10 | 20.75 |
March | 0.862767E+10 | 17007.75 | 30-MAR-14:00 | 26.70 | 20.63 | 0.00 | 0.00 | 01-MAR-00:10 | 26.70 | 20.63 |
April | 0.118608E+11 | 19785.05 | 13-APR-14:20 | 28.90 | 24.03 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 24.03 |
May | 0.156509E+11 | 21670.59 | 18-MAY-13:50 | 30.78 | 23.04 | 0.00 | 0.00 | 01-MAY-00:10 | 30.78 | 23.04 |
June | 0.169012E+11 | 22704.43 | 09-JUN-13:50 | 31.02 | 24.94 | 0.00 | 0.00 | 01-JUN-00:10 | 31.02 | 24.94 |
July | 0.183448E+11 | 23553.14 | 28-JUL-15:20 | 35.00 | 25.13 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.13 |
August | 0.165819E+11 | 21871.55 | 23-AUG-14:00 | 32.20 | 25.37 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 25.37 |
September | 0.151649E+11 | 19648.14 | 08-SEP-15:40 | 32.20 | 23.29 | 0.00 | 0.00 | 01-SEP-00:10 | 32.20 | 23.29 |
October | 0.119993E+11 | 18467.69 | 06-OCT-13:05 | 29.82 | 23.71 | 0.00 | 0.00 | 01-OCT-00:10 | 29.82 | 23.71 |
November | 0.824183E+10 | 14922.26 | 07-NOV-14:00 | 28.30 | 20.78 | 0.00 | 0.00 | 01-NOV-00:10 | 28.30 | 20.78 |
December | 0.486292E+10 | 12726.84 | 08-DEC-14:40 | 27.40 | 22.79 | 0.00 | 0.00 | 01-DEC-00:10 | 27.40 | 22.79 |
Annual Sum or Average | 0.138400E+12 | 0.00 | ||||||||
Minimum of Months | 0.425543E+10 | 12726.84 | 26.10 | 20.63 | 0.00 | 0.00 | 26.10 | 20.63 | ||
Maximum of Months | 0.183448E+11 | 23553.14 | 35.00 | 25.37 | 0.00 | 0.00 | 35.00 | 25.37 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.431276E+10 | 2027.39 | 22-JAN-17:33 | 19.80 | 14.31 | 95234649.16 | 126.85 | 23-JAN-14:00 | 25.60 | 19.68 |
February | 0.859547E+10 | 4333.05 | 20-FEB-17:42 | 25.28 | 17.48 | 86407844.08 | 126.86 | 02-FEB-10:00 | 25.28 | 17.48 |
March | 0.146174E+11 | 7230.16 | 31-MAR-24:00 | 22.60 | 17.97 | 0.103245E+09 | 126.85 | 14-MAR-09:09 | 22.60 | 17.97 |
April | 0.191400E+11 | 8003.63 | 09-APR-17:53 | 25.60 | 18.39 | 91665981.34 | 128.48 | 14-APR-13:00 | 30.60 | 24.51 |
May | 0.467914E+10 | 3514.17 | 31-MAY-24:00 | 26.70 | 24.69 | 99234146.83 | 126.85 | 22-MAY-13:09 | 26.70 | 24.69 |
June | 0.940040E+10 | 5390.60 | 30-JUN-23:55 | 26.90 | 23.74 | 98985330.13 | 126.87 | 05-JUN-13:00 | 26.90 | 23.74 |
July | 0.148464E+11 | 7355.53 | 31-JUL-23:57 | 28.60 | 26.07 | 91893796.52 | 126.85 | 12-JUL-09:09 | 28.60 | 26.07 |
August | 0.199265E+11 | 7773.21 | 06-AUG-18:12 | 26.13 | 23.54 | 0.105341E+09 | 136.29 | 23-AUG-13:50 | 32.48 | 25.39 |
September | 0.456695E+10 | 3522.14 | 30-SEP-24:00 | 28.00 | 23.53 | 91605139.66 | 126.82 | 07-SEP-13:00 | 28.00 | 23.53 |
October | 0.972222E+10 | 5375.54 | 31-OCT-24:00 | 22.50 | 21.29 | 95253347.23 | 126.87 | 04-OCT-09:09 | 22.50 | 21.29 |
November | 0.142050E+11 | 5922.05 | 07-NOV-17:00 | 27.80 | 22.39 | 94311457.13 | 126.85 | 30-NOV-10:09 | 26.70 | 24.69 |
December | 0.196180E+11 | 7895.82 | 03-DEC-17:00 | 23.90 | 16.19 | 91883419.09 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.143630E+12 | 0.114506E+10 | ||||||||
Minimum of Months | 0.431276E+10 | 2027.39 | 19.80 | 14.31 | 86407844.08 | 126.82 | 19.27 | 17.48 | ||
Maximum of Months | 0.199265E+11 | 8003.63 | 28.60 | 26.07 | 0.105341E+09 | 136.29 | 32.48 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353066E+10 | 1859.63 | 02-JAN-17:00 | 25.00 | 20.39 | 95232454.22 | 126.84 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.776436E+10 | 3953.87 | 20-FEB-17:42 | 25.28 | 17.48 | 86407201.52 | 126.85 | 02-FEB-10:09 | 25.28 | 17.48 |
March | 0.137318E+11 | 6968.07 | 31-MAR-24:00 | 22.60 | 17.97 | 0.103245E+09 | 126.85 | 10-MAR-10:00 | 22.60 | 17.97 |
April | 0.182026E+11 | 7538.81 | 09-APR-17:53 | 25.60 | 18.39 | 91640385.79 | 128.16 | 14-APR-13:00 | 30.60 | 24.51 |
May | 0.435663E+10 | 3410.82 | 31-MAY-24:00 | 26.70 | 24.69 | 99233483.53 | 126.82 | 24-MAY-09:00 | 26.70 | 24.69 |
June | 0.892518E+10 | 5205.96 | 30-JUN-23:40 | 27.00 | 23.83 | 98984159.66 | 126.87 | 23-JUN-13:00 | 27.00 | 23.83 |
July | 0.141174E+11 | 7030.75 | 31-JUL-23:57 | 28.60 | 26.07 | 91894596.32 | 126.85 | 10-JUL-09:09 | 28.60 | 26.07 |
August | 0.188441E+11 | 7318.55 | 13-AUG-18:52 | 27.20 | 23.57 | 0.104906E+09 | 135.29 | 23-AUG-13:00 | 32.20 | 25.37 |
September | 0.422098E+10 | 3387.41 | 30-SEP-24:00 | 28.00 | 23.53 | 91605140.74 | 126.82 | 25-SEP-09:09 | 28.00 | 23.53 |
October | 0.919383E+10 | 5095.30 | 31-OCT-24:00 | 22.50 | 21.29 | 95252359.56 | 126.87 | 04-OCT-09:09 | 22.50 | 21.29 |
November | 0.133630E+11 | 5639.37 | 07-NOV-17:00 | 27.80 | 22.39 | 94311414.43 | 126.85 | 29-NOV-10:00 | 26.10 | 24.93 |
December | 0.183205E+11 | 7430.93 | 06-DEC-17:00 | 25.60 | 21.66 | 91882933.35 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.134571E+12 | 0.114459E+10 | ||||||||
Minimum of Months | 0.353066E+10 | 1859.63 | 22.50 | 17.48 | 86407201.52 | 126.82 | 19.27 | 17.48 | ||
Maximum of Months | 0.188441E+11 | 7538.81 | 28.60 | 26.07 | 0.104906E+09 | 135.29 | 32.20 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305031E+10 | 1891.78 | 02-JAN-17:00 | 25.00 | 20.39 | 95232247.59 | 126.84 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.748513E+10 | 4094.73 | 20-FEB-17:42 | 25.28 | 17.48 | 86407520.97 | 126.85 | 02-FEB-14:00 | 25.28 | 17.48 |
March | 0.135725E+11 | 6914.40 | 31-MAR-24:00 | 22.60 | 17.97 | 0.103245E+09 | 126.85 | 10-MAR-10:00 | 22.60 | 17.97 |
April | 0.182192E+11 | 7808.87 | 09-APR-17:53 | 25.60 | 18.39 | 91622568.67 | 127.02 | 14-APR-13:00 | 30.60 | 24.51 |
May | 0.444535E+10 | 3441.07 | 31-MAY-24:00 | 26.70 | 24.69 | 99233868.28 | 126.85 | 22-MAY-13:09 | 26.70 | 24.69 |
June | 0.903114E+10 | 5210.38 | 30-JUN-23:40 | 27.00 | 23.83 | 98985306.74 | 126.87 | 23-JUN-13:00 | 27.00 | 23.83 |
July | 0.142614E+11 | 7040.54 | 31-JUL-23:57 | 28.60 | 26.07 | 91894932.37 | 126.85 | 17-JUL-13:09 | 28.60 | 26.07 |
August | 0.189445E+11 | 7567.24 | 06-AUG-18:12 | 26.13 | 23.54 | 0.104113E+09 | 133.98 | 23-AUG-13:00 | 32.20 | 25.37 |
September | 0.430991E+10 | 3450.96 | 30-SEP-24:00 | 28.00 | 23.53 | 91605142.69 | 126.82 | 07-SEP-13:00 | 28.00 | 23.53 |
October | 0.921716E+10 | 5022.19 | 31-OCT-24:00 | 22.50 | 21.29 | 95252912.55 | 126.87 | 04-OCT-13:09 | 22.50 | 21.29 |
November | 0.131994E+11 | 5702.11 | 07-NOV-17:00 | 27.80 | 22.39 | 94311917.86 | 126.85 | 30-NOV-14:09 | 27.20 | 24.74 |
December | 0.179844E+11 | 7491.67 | 06-DEC-17:00 | 25.60 | 21.66 | 91883371.63 | 126.83 | 29-DEC-10:09 | 19.27 | 17.74 |
Annual Sum or Average | 0.133720E+12 | 0.114379E+10 | ||||||||
Minimum of Months | 0.305031E+10 | 1891.78 | 22.50 | 17.48 | 86407520.97 | 126.82 | 19.27 | 17.48 | ||
Maximum of Months | 0.189445E+11 | 7808.87 | 28.60 | 26.07 | 0.104113E+09 | 133.98 | 32.20 | 26.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242449E+12 | 93487.74 | 02-JAN-17:00 | 25.00 | 20.39 | 0.206186E+10 | 2746.70 | 30-JAN-14:09 | 16.60 | 15.83 |
February | 0.439203E+12 | 184607.08 | 21-FEB-17:00 | 25.60 | 14.07 | 0.187053E+10 | 2746.28 | 02-FEB-10:09 | 25.60 | 14.07 |
March | 0.731060E+12 | 359462.20 | 31-MAR-23:55 | 22.60 | 17.97 | 0.223499E+10 | 2746.66 | 16-MAR-13:09 | 22.60 | 17.97 |
April | 0.942425E+12 | 368959.14 | 17-APR-21:02 | 23.22 | 17.86 | 0.208438E+10 | 3280.07 | 14-APR-13:00 | 23.22 | 17.86 |
May | 0.242491E+12 | 176465.86 | 31-MAY-24:00 | 26.70 | 24.69 | 0.214902E+10 | 2747.06 | 24-MAY-09:09 | 26.70 | 24.69 |
June | 0.470885E+12 | 268012.56 | 30-JUN-23:55 | 26.90 | 23.74 | 0.214287E+10 | 2746.57 | 23-JUN-13:00 | 26.90 | 23.74 |
July | 0.732908E+12 | 357679.29 | 31-JUL-23:13 | 28.67 | 25.64 | 0.198924E+10 | 2745.88 | 10-JUL-09:09 | 28.67 | 25.64 |
August | 0.970931E+12 | 369857.28 | 28-AUG-12:05 | 22.20 | 21.91 | 0.265155E+10 | 3604.04 | 23-AUG-13:39 | 22.20 | 21.91 |
September | 0.237062E+12 | 176815.47 | 30-SEP-23:55 | 28.00 | 23.53 | 0.198400E+10 | 2747.19 | 22-SEP-09:09 | 28.00 | 23.53 |
October | 0.488803E+12 | 268708.87 | 31-OCT-24:00 | 22.50 | 21.29 | 0.206205E+10 | 2746.73 | 04-OCT-09:09 | 22.50 | 21.29 |
November | 0.710149E+12 | 276699.72 | 06-NOV-17:00 | 27.80 | 20.36 | 0.204155E+10 | 2745.86 | 30-NOV-10:09 | 26.70 | 24.69 |
December | 0.978198E+12 | 368906.03 | 11-DEC-17:00 | 22.80 | 16.83 | 0.202401E+10 | 3085.88 | 08-DEC-14:00 | 22.80 | 16.83 |
Annual Sum or Average | 0.718656E+13 | 0.252961E+11 | ||||||||
Minimum of Months | 0.237062E+12 | 93487.74 | 22.20 | 14.07 | 0.187053E+10 | 2745.86 | 16.60 | 14.07 | ||
Maximum of Months | 0.978198E+12 | 369857.28 | 28.67 | 25.64 | 0.265155E+10 | 3604.04 | 28.67 | 25.64 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 99689072.81 | 9912.81 | 01-JAN-12:53 | 27.20 |
February | 0.105838E+09 | 11772.11 | 11-FEB-17:02 | 27.02 |
March | 0.144204E+09 | 10118.99 | 04-MAR-17:02 | 26.02 |
April | 0.245336E+09 | 18992.39 | 15-APR-16:01 | 31.70 |
May | 0.422471E+09 | 17655.06 | 29-MAY-14:13 | 32.40 |
June | 0.392952E+09 | 18784.88 | 10-JUN-16:01 | 31.52 |
July | 0.538080E+09 | 24344.55 | 29-JUL-16:01 | 35.40 |
August | 0.438137E+09 | 20441.56 | 06-AUG-13:13 | 32.93 |
September | 0.617647E+09 | 17700.50 | 30-SEP-16:01 | 31.02 |
October | 0.521815E+09 | 17438.63 | 14-OCT-16:02 | 31.23 |
November | 0.273359E+09 | 12822.48 | 05-NOV-16:12 | 27.80 |
December | 0.163034E+09 | 12838.98 | 10-DEC-13:53 | 28.90 |
Annual Sum or Average | 0.396256E+10 | |||
Minimum of Months | 99689072.81 | 9912.81 | 26.02 | |
Maximum of Months | 0.617647E+09 | 24344.55 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5267292.23 | 8460.24 | 25-JAN-06:03 | 9.40 |
February | 26877203.83 | 11793.67 | 04-FEB-05:11 | 5.93 |
March | 6972927.68 | 9872.60 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 3645844.14 | 9492.52 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 42763267.88 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 26877203.83 | 11793.67 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24499.20 | 163.33 | 25-JAN-06:03 | 9.40 |
February | 9351856.43 | 9041.63 | 04-FEB-06:03 | 5.50 |
March | 59973.50 | 399.82 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 297366.25 | 2448.07 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 9733695.39 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 9351856.43 | 9041.63 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 5715108.25 | 11025.34 | 04-FEB-06:03 | 5.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 5715108.25 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 5715108.25 | 11025.34 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 8456228.25 | 8688.39 | 04-FEB-06:03 | 5.50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 8456228.25 | |||
Minimum of Months | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 8456228.25 | 8688.39 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76667555.38 | 12786.78 | 26-JAN-06:02 | 10.60 |
February | 89847508.79 | 14339.33 | 04-FEB-05:11 | 5.93 |
March | 46857971.99 | 13169.59 | 16-MAR-04:12 | 7.43 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 17012715.99 | 12718.01 | 13-NOV-06:03 | 12.20 |
December | 90648879.53 | 12850.58 | 27-DEC-06:02 | 8.90 |
Annual Sum or Average | 0.321035E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 90648879.53 | 14339.33 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20792764.65 | 10043.52 | 26-JAN-06:02 | 10.60 |
February | 31386962.19 | 12688.02 | 04-FEB-05:11 | 5.93 |
March | 12396578.33 | 9585.37 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 3959030.00 | 9920.68 | 13-NOV-06:03 | 12.20 |
December | 38552780.20 | 11173.16 | 21-DEC-06:02 | 11.20 |
Annual Sum or Average | 0.107088E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 38552780.20 | 12688.02 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5243977.62 | 9320.39 | 25-JAN-06:03 | 9.40 |
February | 39410297.26 | 13675.90 | 04-FEB-05:11 | 5.93 |
March | 13251852.80 | 12505.56 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 3328908.07 | 10138.14 | 13-NOV-06:03 | 12.20 |
December | 11849060.61 | 12567.27 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 73084096.35 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 39410297.26 | 13675.90 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10817469.57 | 8696.27 | 25-JAN-06:03 | 9.40 |
February | 38125659.37 | 12521.34 | 04-FEB-05:11 | 5.93 |
March | 7073978.16 | 8562.84 | 16-MAR-05:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 3480085.78 | 7463.06 | 13-NOV-06:03 | 12.20 |
December | 19079691.20 | 10800.62 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 78576884.08 | |||
Minimum of Months | 0.00 | 0.00 | 5.93 | |
Maximum of Months | 38125659.37 | 12521.34 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82498555.74 | 8412.23 | 23-JAN-05:12 | 12.57 |
February | 78570760.98 | 9593.91 | 06-FEB-05:12 | 17.97 |
March | 86593036.12 | 9842.43 | 20-MAR-04:12 | 12.20 |
April | 64621816.99 | 7990.73 | 19-APR-04:12 | 15.00 |
May | 34898599.76 | 5808.61 | 08-MAY-04:12 | 23.50 |
June | 21238040.82 | 3906.81 | 11-JUN-14:22 | 31.40 |
July | 38472082.72 | 5290.10 | 16-JUL-14:21 | 31.10 |
August | 40396082.62 | 6809.27 | 13-AUG-15:42 | 30.50 |
September | 31056235.24 | 4585.59 | 15-SEP-03:02 | 24.40 |
October | 38885000.00 | 6656.44 | 27-OCT-04:12 | 22.80 |
November | 77017282.11 | 9030.80 | 15-NOV-05:12 | 20.03 |
December | 0.119126E+09 | 12753.26 | 18-DEC-05:12 | 17.20 |
Annual Sum or Average | 0.713374E+09 | |||
Minimum of Months | 21238040.82 | 3906.81 | 12.20 | |
Maximum of Months | 0.119126E+09 | 12753.26 | 31.40 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50905539.25 | 6208.45 | 31-JAN-06:02 | 12.20 |
February | 59503998.13 | 6557.67 | 13-FEB-05:12 | 20.20 |
March | 28802527.41 | 7157.54 | 20-MAR-04:12 | 12.20 |
April | 34039337.16 | 4512.08 | 09-APR-15:21 | 27.50 |
May | 25000878.36 | 4775.73 | 01-MAY-04:12 | 20.93 |
June | 23403768.16 | 4326.03 | 19-JUN-03:02 | 24.40 |
July | 33917676.27 | 4881.66 | 04-JUL-15:41 | 31.88 |
August | 29642463.61 | 6018.11 | 13-AUG-16:01 | 30.50 |
September | 28325650.77 | 5127.67 | 17-SEP-15:01 | 31.10 |
October | 31904911.81 | 4945.54 | 02-OCT-03:02 | 26.70 |
November | 34993509.91 | 7322.62 | 13-NOV-05:12 | 12.60 |
December | 45637558.41 | 6351.88 | 18-DEC-06:03 | 17.30 |
Annual Sum or Average | 0.426078E+09 | |||
Minimum of Months | 23403768.16 | 4326.03 | 12.20 | |
Maximum of Months | 59503998.13 | 7322.62 | 31.88 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.789537E+09 | 12970.04 | 12-JAN-06:02 | 16.20 |
February | 0.480622E+09 | 15974.42 | 22-FEB-06:03 | 11.70 |
March | 0.499716E+09 | 17532.74 | 15-MAR-05:02 | 12.12 |
April | 86642836.00 | 14267.46 | 19-APR-05:03 | 15.10 |
May | 34454433.01 | 10786.65 | 01-MAY-04:12 | 20.93 |
June | 19154310.28 | 9052.85 | 06-JUN-04:11 | 23.50 |
July | 24296216.77 | 9480.16 | 07-JUL-04:12 | 23.30 |
August | 20177648.84 | 7106.27 | 31-AUG-03:02 | 25.68 |
September | 29543132.68 | 10934.41 | 05-SEP-04:12 | 23.30 |
October | 43078096.48 | 10810.63 | 16-OCT-04:12 | 21.87 |
November | 0.189312E+09 | 10912.19 | 02-NOV-05:02 | 19.90 |
December | 0.666930E+09 | 15208.60 | 12-DEC-06:03 | 12.02 |
Annual Sum or Average | 0.288346E+10 | |||
Minimum of Months | 19154310.28 | 7106.27 | 11.70 | |
Maximum of Months | 0.789537E+09 | 17532.74 | 25.68 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.944433E+09 | 1392.86 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.821895E+09 | 1115.08 | 07-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.940062E+09 | 1218.06 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.824681E+09 | 1143.27 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.870136E+09 | 903.22 | 25-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.863564E+09 | 1383.04 | 15-JUN-07:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.804272E+09 | 894.21 | 05-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.911298E+09 | 1142.29 | 28-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.838394E+09 | 1662.56 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.895255E+09 | 1403.01 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.917396E+09 | 1345.62 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.927772E+09 | 1552.97 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.105592E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.804272E+09 | 894.21 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.944433E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.599114E+09 | 907.77 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.525826E+09 | 755.45 | 13-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.601075E+09 | 582.25 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.531857E+09 | 592.32 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.564009E+09 | 567.47 | 25-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.560731E+09 | 870.81 | 15-JUN-07:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.521814E+09 | 560.90 | 05-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.587723E+09 | 593.82 | 28-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.540582E+09 | 1071.42 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.570882E+09 | 858.04 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.587051E+09 | 888.59 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.591630E+09 | 1001.74 | 15-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.678229E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.521814E+09 | 560.90 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.601075E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905517E+09 | 1333.09 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.803864E+09 | 918.04 | 08-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.931481E+09 | 1133.18 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.826700E+09 | 1157.23 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.878493E+09 | 915.48 | 25-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.877762E+09 | 1414.46 | 15-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.813140E+09 | 912.66 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.915649E+09 | 1177.30 | 28-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.836359E+09 | 1662.60 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.880308E+09 | 1366.45 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.891603E+09 | 1236.15 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.893161E+09 | 1545.92 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104540E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.803864E+09 | 912.66 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.931481E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.592450E+09 | 836.13 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.521553E+09 | 722.87 | 07-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.604430E+09 | 822.32 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.530712E+09 | 799.30 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.564660E+09 | 600.03 | 25-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.562306E+09 | 930.30 | 15-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.522826E+09 | 598.43 | 05-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.590552E+09 | 803.81 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.540929E+09 | 1071.42 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.574209E+09 | 915.45 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.579660E+09 | 831.46 | 24-NOV-08:09 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.581152E+09 | 993.13 | 15-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.676544E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.521553E+09 | 598.43 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.604430E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.940663E+09 | 1389.51 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.819735E+09 | 1099.19 | 07-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.938024E+09 | 1206.64 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.824023E+09 | 1136.65 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.869672E+09 | 896.51 | 25-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.861987E+09 | 1379.81 | 15-JUN-07:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.803770E+09 | 887.03 | 05-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.910515E+09 | 1135.67 | 28-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.837266E+09 | 1662.56 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.893053E+09 | 1399.84 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.914756E+09 | 1341.46 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.925555E+09 | 1551.75 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.105390E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.803770E+09 | 887.03 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.940663E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.597850E+09 | 903.52 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.524901E+09 | 746.87 | 13-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.600514E+09 | 578.88 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.531457E+09 | 589.21 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.563464E+09 | 562.19 | 25-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.559912E+09 | 865.91 | 15-JUN-07:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.521359E+09 | 555.24 | 05-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.587287E+09 | 590.71 | 28-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.539963E+09 | 1071.42 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.570258E+09 | 853.25 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.585841E+09 | 883.88 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.590614E+09 | 999.92 | 15-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.677342E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.521359E+09 | 555.24 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.600514E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905022E+09 | 1329.58 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.803268E+09 | 912.26 | 08-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.930414E+09 | 1117.21 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.826086E+09 | 1150.69 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.877546E+09 | 909.36 | 25-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.876539E+09 | 1411.07 | 15-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.812180E+09 | 906.37 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.914612E+09 | 1170.95 | 28-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.835582E+09 | 1662.60 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.879158E+09 | 1363.13 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.890117E+09 | 1231.86 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.892568E+09 | 1544.69 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104431E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.803268E+09 | 906.37 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.930414E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.591208E+09 | 830.95 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.520709E+09 | 713.94 | 07-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.603521E+09 | 815.64 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.530191E+09 | 792.06 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.563911E+09 | 596.76 | 25-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.561493E+09 | 926.55 | 15-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.522111E+09 | 595.08 | 05-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.589887E+09 | 796.70 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.540157E+09 | 1071.42 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.573200E+09 | 911.39 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.578847E+09 | 825.17 | 24-NOV-08:09 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.580208E+09 | 991.22 | 15-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.675544E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.520709E+09 | 595.08 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.603521E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.940571E+09 | 1388.97 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.819693E+09 | 1098.94 | 07-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.937982E+09 | 1206.40 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.823932E+09 | 1135.64 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.869653E+09 | 896.24 | 25-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.861961E+09 | 1379.21 | 15-JUN-07:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.803751E+09 | 886.74 | 05-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.910463E+09 | 1134.66 | 28-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.837233E+09 | 1662.56 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.893013E+09 | 1399.32 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.914683E+09 | 1340.87 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.925483E+09 | 1551.52 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.105384E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.803751E+09 | 886.74 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.940571E+09 | 1662.56 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.597807E+09 | 903.19 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.524862E+09 | 746.31 | 13-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.600496E+09 | 578.71 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.531442E+09 | 589.06 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.563433E+09 | 562.04 | 25-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.559891E+09 | 865.51 | 15-JUN-07:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.521327E+09 | 555.08 | 05-JUL-15:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.587262E+09 | 590.56 | 28-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.539941E+09 | 1071.42 | 27-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.570237E+09 | 852.87 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.585814E+09 | 883.54 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.590563E+09 | 999.78 | 15-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.677307E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.521327E+09 | 555.08 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.600496E+09 | 1071.42 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905007E+09 | 1328.96 | 04-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.803244E+09 | 912.02 | 08-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.930383E+09 | 1116.91 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.826068E+09 | 1149.71 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.877519E+09 | 909.12 | 25-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.876470E+09 | 1410.58 | 15-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.812149E+09 | 906.13 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.914570E+09 | 1169.99 | 28-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.835555E+09 | 1662.60 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.879141E+09 | 1362.56 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.890073E+09 | 1231.13 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.892512E+09 | 1544.45 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104427E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.803244E+09 | 906.13 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.930383E+09 | 1662.60 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.591170E+09 | 830.53 | 04-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.520695E+09 | 713.86 | 07-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.603506E+09 | 815.17 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.530170E+09 | 791.52 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.563877E+09 | 596.63 | 25-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.561450E+09 | 926.26 | 15-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.522095E+09 | 594.95 | 05-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.589866E+09 | 796.16 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.540138E+09 | 1071.42 | 27-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.573158E+09 | 911.07 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.578743E+09 | 824.68 | 24-NOV-08:09 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.580182E+09 | 991.06 | 15-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.675505E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.520695E+09 | 594.95 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.603506E+09 | 1071.42 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.944433E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5500258.68 | 0.173732E+09 |
February | 0.136985E+10 | 0.821895E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11029875.89 | 0.235067E+09 |
March | 0.163685E+10 | 0.940062E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12848817.67 | 0.195708E+09 |
April | 0.145243E+10 | 0.824681E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28007908.79 | 73814037.12 |
May | 0.157338E+10 | 0.870136E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76949828.99 | 27941592.81 |
June | 0.156900E+10 | 0.863564E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95809079.70 | 5409770.11 |
July | 0.145680E+10 | 0.804272E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84759383.28 | 6085020.97 |
August | 0.163685E+10 | 0.911298E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100809E+09 | 3674448.16 |
September | 0.145243E+10 | 0.838394E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95612129.99 | 8339913.39 |
October | 0.150991E+10 | 0.895255E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62736615.19 | 15136346.85 |
November | 0.149516E+10 | 0.917396E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28975002.23 | 0.137349E+09 |
December | 0.145680E+10 | 0.927772E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8171246.19 | 0.172994E+09 |
Annual Sum or Average | 0.181194E+11 | 0.105592E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611209E+09 | 0.105525E+10 |
Minimum of Months | 0.136985E+10 | 0.804272E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5500258.68 | 3674448.16 |
Maximum of Months | 0.163685E+10 | 0.944433E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100809E+09 | 0.235067E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.599114E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2952631.72 | 0.121314E+09 |
February | 0.882782E+09 | 0.525826E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6906672.36 | 0.160346E+09 |
March | 0.105485E+10 | 0.601075E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8324635.70 | 0.130213E+09 |
April | 0.936002E+09 | 0.531857E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17254946.42 | 48360188.75 |
May | 0.101394E+10 | 0.564009E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49686794.57 | 19316218.60 |
June | 0.101113E+10 | 0.560731E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64132113.43 | 3483795.58 |
July | 0.938820E+09 | 0.521814E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56199920.43 | 4014916.63 |
August | 0.105485E+10 | 0.587723E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68799575.49 | 2068081.69 |
September | 0.936002E+09 | 0.540582E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61258220.68 | 6033216.89 |
October | 0.973041E+09 | 0.570882E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39842015.56 | 10175587.56 |
November | 0.963541E+09 | 0.587051E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19366792.27 | 92982282.75 |
December | 0.938820E+09 | 0.591630E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5217119.94 | 0.111395E+09 |
Annual Sum or Average | 0.116768E+11 | 0.678229E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399941E+09 | 0.709702E+09 |
Minimum of Months | 0.882782E+09 | 0.521814E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2952631.72 | 2068081.69 |
Maximum of Months | 0.105485E+10 | 0.601075E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68799575.49 | 0.160346E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.905517E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3974973.79 | 0.197886E+09 |
February | 0.136988E+10 | 0.803864E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9014048.47 | 0.264284E+09 |
March | 0.163688E+10 | 0.931481E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11848436.62 | 0.214135E+09 |
April | 0.145246E+10 | 0.826700E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25288631.35 | 80444625.98 |
May | 0.157341E+10 | 0.878493E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77307861.77 | 27901964.54 |
June | 0.156904E+10 | 0.877762E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97693041.63 | 5369772.38 |
July | 0.145684E+10 | 0.813140E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86050966.26 | 5839105.22 |
August | 0.163688E+10 | 0.915649E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99684583.60 | 3778577.71 |
September | 0.145246E+10 | 0.836359E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88577794.48 | 9822882.42 |
October | 0.150994E+10 | 0.880308E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52254022.34 | 22344046.74 |
November | 0.149520E+10 | 0.891603E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22461293.75 | 0.160388E+09 |
December | 0.145684E+10 | 0.893161E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5580176.59 | 0.193619E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104540E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579736E+09 | 0.118581E+10 |
Minimum of Months | 0.136988E+10 | 0.803864E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3974973.79 | 3778577.71 |
Maximum of Months | 0.163688E+10 | 0.931481E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99684583.60 | 0.264284E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.592450E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2925420.12 | 0.135312E+09 |
February | 0.882782E+09 | 0.521553E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6439812.03 | 0.197878E+09 |
March | 0.105485E+10 | 0.604430E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7772354.50 | 0.180144E+09 |
April | 0.936002E+09 | 0.530712E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16129619.87 | 86514564.27 |
May | 0.101394E+10 | 0.564660E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44337212.79 | 34254593.21 |
June | 0.101113E+10 | 0.562306E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53456669.72 | 8479006.42 |
July | 0.938820E+09 | 0.522826E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49823087.35 | 9066811.39 |
August | 0.105485E+10 | 0.590552E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56445275.21 | 6199806.76 |
September | 0.936002E+09 | 0.540929E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54667098.12 | 9528608.72 |
October | 0.973041E+09 | 0.574209E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33294595.16 | 22645796.79 |
November | 0.963541E+09 | 0.579660E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14287892.07 | 0.124509E+09 |
December | 0.938820E+09 | 0.581152E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4136261.15 | 0.151226E+09 |
Annual Sum or Average | 0.116768E+11 | 0.676544E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343715E+09 | 0.965757E+09 |
Minimum of Months | 0.882782E+09 | 0.521553E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2925420.12 | 6199806.76 |
Maximum of Months | 0.105485E+10 | 0.604430E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56445275.21 | 0.197878E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.940663E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16440345.35 | 0.345799E+09 |
February | 0.136985E+10 | 0.819735E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28462702.15 | 0.460011E+09 |
March | 0.163685E+10 | 0.938024E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29454482.33 | 0.427680E+09 |
April | 0.145243E+10 | 0.824023E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68222499.89 | 0.191125E+09 |
May | 0.157338E+10 | 0.869672E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167198E+09 | 81430617.74 |
June | 0.156900E+10 | 0.861987E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203049E+09 | 23750292.46 |
July | 0.145680E+10 | 0.803770E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189897E+09 | 21579972.26 |
August | 0.163685E+10 | 0.910515E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227543E+09 | 12164647.64 |
September | 0.145243E+10 | 0.837266E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211324E+09 | 24540753.26 |
October | 0.150991E+10 | 0.893053E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136103E+09 | 49647922.23 |
November | 0.149516E+10 | 0.914756E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59153713.49 | 0.284529E+09 |
December | 0.145680E+10 | 0.925555E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21509405.39 | 0.350632E+09 |
Annual Sum or Average | 0.181194E+11 | 0.105390E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135836E+10 | 0.227289E+10 |
Minimum of Months | 0.136985E+10 | 0.803770E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16440345.35 | 12164647.64 |
Maximum of Months | 0.163685E+10 | 0.940663E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227543E+09 | 0.460011E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.597850E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5727139.05 | 0.263522E+09 |
February | 0.649041E+09 | 0.524901E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13616999.61 | 0.345895E+09 |
March | 0.773965E+09 | 0.600514E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16073470.48 | 0.320955E+09 |
April | 0.688021E+09 | 0.531457E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35695974.25 | 0.150133E+09 |
May | 0.744847E+09 | 0.563464E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103192E+09 | 63010869.06 |
June | 0.742030E+09 | 0.559912E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128572E+09 | 18677986.69 |
July | 0.690839E+09 | 0.521359E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118939E+09 | 17480335.12 |
August | 0.773965E+09 | 0.587287E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142092E+09 | 9460639.34 |
September | 0.688021E+09 | 0.539963E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129792E+09 | 19647722.60 |
October | 0.715730E+09 | 0.570258E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79111208.05 | 40850157.21 |
November | 0.708685E+09 | 0.585841E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33064831.06 | 0.217063E+09 |
December | 0.690839E+09 | 0.590614E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10314265.18 | 0.256200E+09 |
Annual Sum or Average | 0.858171E+10 | 0.677342E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816190E+09 | 0.172290E+10 |
Minimum of Months | 0.649041E+09 | 0.521359E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5727139.05 | 9460639.34 |
Maximum of Months | 0.773965E+09 | 0.600514E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142092E+09 | 0.345895E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.905022E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8052189.21 | 0.447970E+09 |
February | 0.136988E+10 | 0.803268E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18923014.39 | 0.584049E+09 |
March | 0.163688E+10 | 0.930414E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25720210.06 | 0.506283E+09 |
April | 0.145246E+10 | 0.826086E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57953743.06 | 0.215752E+09 |
May | 0.157341E+10 | 0.877546E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169222E+09 | 80815269.76 |
June | 0.156904E+10 | 0.876539E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208939E+09 | 22458804.89 |
July | 0.145684E+10 | 0.812180E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193711E+09 | 20373138.36 |
August | 0.163688E+10 | 0.914612E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222738E+09 | 12805953.34 |
September | 0.145246E+10 | 0.835582E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193396E+09 | 29560596.68 |
October | 0.150994E+10 | 0.879158E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110117E+09 | 77595124.69 |
November | 0.149520E+10 | 0.890117E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44755563.97 | 0.381235E+09 |
December | 0.145684E+10 | 0.892568E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11651400.08 | 0.450274E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104431E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126518E+10 | 0.282917E+10 |
Minimum of Months | 0.136988E+10 | 0.803268E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8052189.21 | 12805953.34 |
Maximum of Months | 0.163688E+10 | 0.930414E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222738E+09 | 0.584049E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.591208E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8101581.89 | 0.265577E+09 |
February | 0.882782E+09 | 0.520709E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14220427.50 | 0.368101E+09 |
March | 0.105485E+10 | 0.603521E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17354360.14 | 0.358699E+09 |
April | 0.936002E+09 | 0.530191E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37553799.53 | 0.182620E+09 |
May | 0.101394E+10 | 0.563911E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101408E+09 | 82212408.02 |
June | 0.101113E+10 | 0.561493E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122985E+09 | 22440283.71 |
July | 0.938820E+09 | 0.522111E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116320E+09 | 21686634.15 |
August | 0.105485E+10 | 0.589887E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133743E+09 | 12753203.17 |
September | 0.936002E+09 | 0.540157E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124848E+09 | 22605585.31 |
October | 0.973041E+09 | 0.573200E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77114775.23 | 53199478.47 |
November | 0.963541E+09 | 0.578847E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33548597.71 | 0.226211E+09 |
December | 0.938820E+09 | 0.580208E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10484662.30 | 0.281803E+09 |
Annual Sum or Average | 0.116768E+11 | 0.675544E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.797682E+09 | 0.189791E+10 |
Minimum of Months | 0.882782E+09 | 0.520709E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8101581.89 | 12753203.17 |
Maximum of Months | 0.105485E+10 | 0.603521E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133743E+09 | 0.368101E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.940571E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19767374.48 | 0.396094E+09 |
February | 0.136985E+10 | 0.819693E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31362692.06 | 0.532302E+09 |
March | 0.163685E+10 | 0.937982E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31643538.23 | 0.514372E+09 |
April | 0.145243E+10 | 0.823932E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75545685.71 | 0.244095E+09 |
May | 0.157338E+10 | 0.869653E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193350E+09 | 0.109759E+09 |
June | 0.156900E+10 | 0.861961E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238657E+09 | 33242082.35 |
July | 0.145680E+10 | 0.803751E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222981E+09 | 30795577.34 |
August | 0.163685E+10 | 0.910463E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268334E+09 | 16762105.14 |
September | 0.145243E+10 | 0.837233E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247145E+09 | 32317667.52 |
October | 0.150991E+10 | 0.893013E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154832E+09 | 64338967.02 |
November | 0.149516E+10 | 0.914683E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66562091.37 | 0.325868E+09 |
December | 0.145680E+10 | 0.925483E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23534079.16 | 0.409436E+09 |
Annual Sum or Average | 0.181194E+11 | 0.105384E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157372E+10 | 0.270938E+10 |
Minimum of Months | 0.136985E+10 | 0.803751E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19767374.48 | 16762105.14 |
Maximum of Months | 0.163685E+10 | 0.940571E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268334E+09 | 0.532302E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.597807E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7445078.62 | 0.304708E+09 |
February | 0.882782E+09 | 0.524862E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16994554.91 | 0.402016E+09 |
March | 0.105485E+10 | 0.600496E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19768015.55 | 0.385972E+09 |
April | 0.936002E+09 | 0.531442E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43917315.80 | 0.188753E+09 |
May | 0.101394E+10 | 0.563433E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124042E+09 | 82417440.61 |
June | 0.101113E+10 | 0.559891E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154771E+09 | 25165437.95 |
July | 0.938820E+09 | 0.521327E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143103E+09 | 23848858.33 |
August | 0.105485E+10 | 0.587262E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171621E+09 | 12443268.68 |
September | 0.936002E+09 | 0.539941E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155796E+09 | 25155836.75 |
October | 0.973041E+09 | 0.570237E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94853431.79 | 52063469.18 |
November | 0.963541E+09 | 0.585814E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39655282.93 | 0.251080E+09 |
December | 0.938820E+09 | 0.590563E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11971829.71 | 0.299276E+09 |
Annual Sum or Average | 0.116768E+11 | 0.677307E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983939E+09 | 0.205290E+10 |
Minimum of Months | 0.882782E+09 | 0.521327E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7445078.62 | 12443268.68 |
Maximum of Months | 0.105485E+10 | 0.600496E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171621E+09 | 0.402016E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.905007E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9944069.40 | 0.525909E+09 |
February | 0.136988E+10 | 0.803244E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23054866.18 | 0.687483E+09 |
March | 0.163688E+10 | 0.930383E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29217594.94 | 0.610274E+09 |
April | 0.145246E+10 | 0.826068E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66838091.18 | 0.273969E+09 |
May | 0.157341E+10 | 0.877519E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195374E+09 | 0.108640E+09 |
June | 0.156904E+10 | 0.876470E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244391E+09 | 31693863.07 |
July | 0.145684E+10 | 0.812149E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226579E+09 | 29248213.97 |
August | 0.163688E+10 | 0.914570E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263374E+09 | 17461182.96 |
September | 0.145246E+10 | 0.835555E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229231E+09 | 38013046.62 |
October | 0.150994E+10 | 0.879141E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131974E+09 | 98175463.87 |
November | 0.149520E+10 | 0.890073E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54556666.51 | 0.447515E+09 |
December | 0.145684E+10 | 0.892512E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14259621.22 | 0.533334E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104427E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148879E+10 | 0.340172E+10 |
Minimum of Months | 0.136988E+10 | 0.803244E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9944069.40 | 17461182.96 |
Maximum of Months | 0.163688E+10 | 0.930383E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263374E+09 | 0.687483E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.591170E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9518198.55 | 0.311217E+09 |
February | 0.882782E+09 | 0.520695E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16308940.34 | 0.434583E+09 |
March | 0.105485E+10 | 0.603506E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19593859.71 | 0.433010E+09 |
April | 0.936002E+09 | 0.530170E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43971452.75 | 0.227981E+09 |
May | 0.101394E+10 | 0.563877E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120671E+09 | 0.106795E+09 |
June | 0.101113E+10 | 0.561450E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146263E+09 | 30004125.16 |
July | 0.938820E+09 | 0.522095E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139336E+09 | 29004841.56 |
August | 0.105485E+10 | 0.589866E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159918E+09 | 16761389.16 |
September | 0.936002E+09 | 0.540138E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148677E+09 | 28746051.22 |
October | 0.973041E+09 | 0.573158E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91175903.89 | 67266009.89 |
November | 0.963541E+09 | 0.578743E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39195916.20 | 0.265528E+09 |
December | 0.938820E+09 | 0.580182E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11892776.81 | 0.334767E+09 |
Annual Sum or Average | 0.116768E+11 | 0.675505E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.946523E+09 | 0.228566E+10 |
Minimum of Months | 0.882782E+09 | 0.520695E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9518198.55 | 16761389.16 |
Maximum of Months | 0.105485E+10 | 0.603506E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159918E+09 | 0.434583E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6074475.80 | 0.394586E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12027806.56 | 0.530193E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16768409.58 | 0.460089E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42839953.48 | 0.193496E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124346E+09 | 66563673.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164335E+09 | 14696628.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149962E+09 | 17215764.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173833E+09 | 10686143.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163855E+09 | 22831243.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95869765.93 | 47433166.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36353901.42 | 0.321615E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11468357.19 | 0.397265E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997734E+09 | 0.247667E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6074475.80 | 10686143.23 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173833E+09 | 0.530193E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13190425.22 | 0.670779E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24147957.96 | 0.886046E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30577341.95 | 0.795527E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79969049.14 | 0.344689E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220500E+09 | 0.124154E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287578E+09 | 29954672.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274623E+09 | 31460290.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320686E+09 | 19724252.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293333E+09 | 42301672.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170889E+09 | 90662916.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63429033.07 | 0.549013E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22682935.61 | 0.666100E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180160E+10 | 0.425041E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13190425.22 | 19724252.16 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320686E+09 | 0.886046E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7430357.21 | 0.685304E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10376169.16 | 0.917619E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11699454.86 | 0.873551E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46207781.21 | 0.415164E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180905E+09 | 0.154737E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270077E+09 | 44488474.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239545E+09 | 46330691.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309226E+09 | 26812497.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265561E+09 | 47489715.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142429E+09 | 93096284.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48344567.13 | 0.561081E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10351964.52 | 0.706013E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154215E+10 | 0.457169E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7430357.21 | 26812497.97 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309226E+09 | 0.917619E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1392.86 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 75.26 | 29-JAN-12:25 | 478.53 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1115.08 | 07-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.56 | 02-FEB-14:00 | 803.36 | 04-FEB-05:00 |
March | 2010.79 | 01-MAR-10:09 | 1218.06 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.58 | 05-MAR-14:10 | 787.35 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1143.27 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.98 | 15-APR-17:01 | 252.78 | 19-APR-03:00 |
May | 2010.79 | 01-MAY-09:09 | 903.22 | 25-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.79 | 29-MAY-16:05 | 164.96 | 25-MAY-04:10 |
June | 2010.79 | 01-JUN-09:09 | 1383.04 | 15-JUN-07:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.76 | 16-JUN-21:02 | 128.88 | 18-JUN-20:00 |
July | 2010.79 | 03-JUL-09:09 | 894.21 | 05-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.95 | 30-JUL-15:46 | 133.90 | 02-JUL-15:40 |
August | 2010.79 | 01-AUG-09:09 | 1142.29 | 28-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.29 | 13-AUG-12:28 | 199.07 | 14-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1662.56 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 268.10 | 17-SEP-14:00 | 75.75 | 03-SEP-14:00 |
October | 2010.79 | 02-OCT-09:09 | 1403.01 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 191.90 | 29-OCT-12:00 | 138.84 | 16-OCT-04:50 |
November | 2010.79 | 01-NOV-09:09 | 1345.62 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.83 | 22-NOV-22:02 | 798.95 | 11-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 1552.97 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.69 | 10-DEC-14:51 | 752.84 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 894.21 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 70.56 | 75.75 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 385.79 | 803.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 907.77 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 | 07-JAN-13:00 | 319.77 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 755.45 | 13-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 | 02-FEB-14:00 | 529.38 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 582.25 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 66.03 | 05-MAR-14:00 | 528.69 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 592.32 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.53 | 15-APR-17:10 | 165.35 | 19-APR-03:00 |
May | 1295.83 | 01-MAY-09:09 | 567.47 | 25-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.94 | 29-MAY-16:05 | 104.80 | 07-MAY-18:50 |
June | 1295.83 | 01-JUN-09:09 | 870.81 | 15-JUN-07:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.24 | 16-JUN-21:02 | 79.70 | 18-JUN-20:00 |
July | 1295.83 | 03-JUL-09:09 | 560.90 | 05-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.21 | 30-JUL-15:44 | 100.84 | 02-JUL-15:40 |
August | 1295.83 | 01-AUG-09:09 | 593.82 | 28-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.18 | 13-AUG-12:28 | 122.44 | 14-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1071.42 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.06 | 17-SEP-13:58 | 57.77 | 03-SEP-14:00 |
October | 1295.83 | 02-OCT-09:09 | 858.04 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.60 | 29-OCT-13:46 | 90.76 | 16-OCT-04:50 |
November | 1295.83 | 01-NOV-09:09 | 888.59 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.65 | 22-NOV-22:02 | 610.27 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 1001.74 | 15-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.93 | 10-DEC-14:51 | 491.91 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 560.90 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 | 57.77 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 260.94 | 610.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1333.09 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.47 | 07-JAN-13:00 | 507.24 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 918.04 | 08-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.56 | 02-FEB-14:00 | 813.34 | 04-FEB-05:00 |
March | 2010.83 | 01-MAR-10:09 | 1133.18 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.22 | 05-MAR-14:00 | 816.99 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1157.23 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.96 | 15-APR-17:10 | 256.07 | 19-APR-03:00 |
May | 2010.83 | 01-MAY-09:09 | 915.48 | 25-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.88 | 29-MAY-16:05 | 162.72 | 25-MAY-04:10 |
June | 2010.83 | 01-JUN-09:09 | 1414.46 | 15-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.39 | 16-JUN-21:02 | 133.15 | 18-JUN-20:00 |
July | 2010.83 | 03-JUL-09:09 | 912.66 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.70 | 30-JUL-15:46 | 133.51 | 02-JUL-15:40 |
August | 2010.83 | 01-AUG-09:09 | 1177.30 | 28-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.50 | 13-AUG-12:28 | 198.74 | 14-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1662.60 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.46 | 17-SEP-13:55 | 100.41 | 03-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 1366.45 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.09 | 29-OCT-14:00 | 157.36 | 16-OCT-04:50 |
November | 2010.83 | 01-NOV-09:09 | 1236.15 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.66 | 22-NOV-22:02 | 903.83 | 11-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 1545.92 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 126.46 | 10-DEC-15:00 | 777.41 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 912.66 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 58.47 | 100.41 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 386.88 | 903.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 836.13 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 | 07-JAN-13:00 | 355.42 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 722.87 | 07-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 | 02-FEB-14:00 | 587.59 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 822.32 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.80 | 05-MAR-13:57 | 610.25 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 799.30 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.96 | 15-APR-17:10 | 214.64 | 18-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 600.03 | 25-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.54 | 29-MAY-16:10 | 140.86 | 25-MAY-04:10 |
June | 1295.83 | 01-JUN-09:09 | 930.30 | 15-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.50 | 25-JUN-13:52 | 132.23 | 18-JUN-20:00 |
July | 1295.83 | 03-JUL-09:09 | 598.43 | 05-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.01 | 30-JUL-15:44 | 117.63 | 02-JUL-15:40 |
August | 1295.83 | 01-AUG-09:09 | 803.81 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.25 | 13-AUG-12:25 | 192.43 | 14-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1071.42 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.24 | 17-SEP-13:55 | 90.12 | 19-SEP-23:05 |
October | 1295.83 | 02-OCT-09:09 | 915.45 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.55 | 29-OCT-13:44 | 118.80 | 16-OCT-04:50 |
November | 1295.83 | 01-NOV-09:09 | 831.46 | 24-NOV-08:09 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.97 | 22-NOV-22:02 | 617.27 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 993.13 | 15-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 92.39 | 10-DEC-14:03 | 573.91 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 598.43 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 | 90.12 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 244.54 | 617.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1389.51 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 288.02 | 15-JAN-14:10 | 977.55 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1099.19 | 07-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 268.63 | 20-FEB-15:00 | 1668.69 | 04-FEB-05:19 |
March | 2010.79 | 01-MAR-10:09 | 1206.64 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 231.61 | 05-MAR-14:00 | 1605.75 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1136.65 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 593.79 | 15-APR-17:01 | 559.87 | 18-APR-23:55 |
May | 2010.79 | 01-MAY-09:09 | 896.51 | 25-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 861.66 | 29-MAY-15:51 | 363.07 | 25-MAY-03:55 |
June | 2010.79 | 01-JUN-09:09 | 1379.81 | 15-JUN-07:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 545.42 | 25-JUN-13:56 | 376.59 | 18-JUN-19:55 |
July | 2010.79 | 03-JUL-09:09 | 887.03 | 05-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 647.63 | 30-JUL-15:58 | 306.49 | 02-JUL-15:50 |
August | 2010.79 | 01-AUG-09:09 | 1135.67 | 28-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 604.48 | 20-AUG-12:08 | 434.14 | 14-AUG-02:57 |
September | 2010.79 | 01-SEP-09:09 | 1662.56 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 606.31 | 17-SEP-13:46 | 211.07 | 19-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1399.84 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.77 | 29-OCT-12:00 | 310.18 | 16-OCT-02:55 |
November | 2010.79 | 01-NOV-09:09 | 1341.46 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.27 | 22-NOV-22:02 | 1621.98 | 11-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 1551.75 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 399.43 | 10-DEC-14:40 | 1519.28 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 887.03 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 231.61 | 211.07 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 861.66 | 1668.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 903.52 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 | 07-JAN-13:10 | 705.27 | 08-JAN-09:55 |
February | 1239.33 | 01-FEB-08:09 | 746.87 | 13-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 107.53 | 02-FEB-14:00 | 1123.88 | 04-FEB-05:12 |
March | 1239.33 | 01-MAR-08:09 | 578.88 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 134.19 | 05-MAR-14:00 | 1133.44 | 16-MAR-02:00 |
April | 1239.33 | 03-APR-07:10 | 589.21 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.25 | 15-APR-17:01 | 395.31 | 18-APR-23:55 |
May | 1239.33 | 01-MAY-07:10 | 562.19 | 25-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 593.30 | 29-MAY-15:43 | 293.56 | 07-MAY-19:10 |
June | 1239.33 | 01-JUN-07:10 | 865.91 | 15-JUN-07:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.09 | 25-JUN-13:54 | 257.33 | 18-JUN-19:55 |
July | 1239.33 | 03-JUL-07:10 | 555.24 | 05-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 430.11 | 30-JUL-15:55 | 251.84 | 02-JUL-15:50 |
August | 1239.33 | 01-AUG-07:10 | 590.71 | 28-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 402.31 | 20-AUG-12:05 | 306.97 | 14-AUG-02:57 |
September | 1239.33 | 01-SEP-07:10 | 1071.42 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 406.13 | 17-SEP-13:44 | 159.53 | 19-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 853.25 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.08 | 29-OCT-13:46 | 221.27 | 16-OCT-02:55 |
November | 1239.33 | 01-NOV-07:10 | 883.88 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.46 | 22-NOV-22:02 | 1305.12 | 11-NOV-09:00 |
December | 1239.33 | 01-DEC-08:09 | 999.92 | 15-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 248.25 | 10-DEC-14:57 | 1038.40 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 555.24 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 | 159.53 | |||||
Maximum of Months | 1239.33 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 593.30 | 1305.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1329.58 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.66 | 07-JAN-13:00 | 1110.68 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 912.26 | 08-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.30 | 02-FEB-14:00 | 1739.91 | 04-FEB-05:00 |
March | 2010.83 | 01-MAR-10:09 | 1117.21 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.76 | 05-MAR-14:00 | 1768.49 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1150.69 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 540.49 | 15-APR-17:01 | 592.19 | 18-APR-23:55 |
May | 2010.83 | 01-MAY-09:09 | 909.36 | 25-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 861.69 | 29-MAY-15:51 | 364.51 | 25-MAY-03:55 |
June | 2010.83 | 01-JUN-09:09 | 1411.07 | 15-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 544.73 | 25-JUN-13:56 | 381.00 | 18-JUN-19:55 |
July | 2010.83 | 03-JUL-09:09 | 906.37 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 647.16 | 30-JUL-15:58 | 300.72 | 02-JUL-15:50 |
August | 2010.83 | 01-AUG-09:09 | 1170.95 | 28-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 599.69 | 20-AUG-12:05 | 444.39 | 14-AUG-02:57 |
September | 2010.83 | 01-SEP-09:09 | 1662.60 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 576.76 | 17-SEP-13:58 | 260.20 | 19-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1363.13 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.77 | 29-OCT-14:00 | 387.28 | 16-OCT-02:55 |
November | 2010.83 | 01-NOV-09:09 | 1231.86 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.25 | 22-NOV-22:02 | 1919.42 | 11-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 1544.69 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 281.89 | 10-DEC-15:00 | 1677.21 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 906.37 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 133.66 | 260.20 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 861.69 | 1919.42 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 830.95 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 130.35 | 15-JAN-12:10 | 710.62 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 713.94 | 07-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 107.53 | 02-FEB-14:00 | 1130.28 | 04-FEB-05:00 |
March | 1295.83 | 01-MAR-10:09 | 815.64 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 134.82 | 05-MAR-14:00 | 1191.61 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 792.06 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 322.94 | 15-APR-17:10 | 437.65 | 18-APR-23:55 |
May | 1295.83 | 01-MAY-09:09 | 596.76 | 25-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 574.42 | 29-MAY-16:00 | 296.25 | 07-MAY-19:10 |
June | 1295.83 | 01-JUN-09:09 | 926.55 | 15-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.06 | 25-JUN-13:54 | 301.54 | 18-JUN-19:55 |
July | 1295.83 | 03-JUL-09:09 | 595.08 | 05-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.24 | 30-JUL-15:55 | 236.82 | 02-JUL-15:50 |
August | 1295.83 | 01-AUG-09:09 | 796.70 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.82 | 20-AUG-12:05 | 366.47 | 14-AUG-02:57 |
September | 1295.83 | 01-SEP-09:09 | 1071.42 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 401.26 | 17-SEP-13:44 | 205.23 | 19-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 911.39 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.41 | 29-OCT-13:44 | 254.70 | 16-OCT-02:55 |
November | 1295.83 | 01-NOV-09:09 | 825.17 | 24-NOV-08:09 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.69 | 22-NOV-22:02 | 1121.00 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 991.22 | 15-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 219.25 | 10-DEC-14:14 | 1069.43 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 595.08 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 107.53 | 205.23 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 574.42 | 1191.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1388.97 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 342.66 | 15-JAN-11:52 | 1136.96 | 24-JAN-03:00 |
February | 2010.79 | 01-FEB-10:09 | 1098.94 | 07-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 245.47 | 20-FEB-15:00 | 2087.80 | 04-FEB-05:20 |
March | 2010.79 | 01-MAR-10:09 | 1206.40 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 233.10 | 05-MAR-13:50 | 1817.66 | 16-MAR-02:00 |
April | 2010.79 | 03-APR-09:09 | 1135.64 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 672.03 | 15-APR-17:01 | 662.66 | 18-APR-23:55 |
May | 2010.79 | 01-MAY-09:09 | 896.24 | 25-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.83 | 29-MAY-15:54 | 456.39 | 07-MAY-19:20 |
June | 2010.79 | 01-JUN-09:09 | 1379.21 | 15-JUN-07:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 635.34 | 16-JUN-21:02 | 500.97 | 18-JUN-20:00 |
July | 2010.79 | 03-JUL-09:09 | 886.74 | 05-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 827.66 | 30-JUL-15:46 | 441.18 | 02-JUL-15:50 |
August | 2010.79 | 01-AUG-09:09 | 1134.66 | 28-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 737.27 | 20-AUG-12:05 | 599.78 | 14-AUG-02:53 |
September | 2010.79 | 01-SEP-09:09 | 1662.56 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.04 | 17-SEP-13:46 | 274.39 | 19-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1399.32 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 535.27 | 29-OCT-13:46 | 390.43 | 01-OCT-06:55 |
November | 2010.79 | 01-NOV-09:09 | 1340.87 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 307.32 | 22-NOV-22:02 | 1832.59 | 11-NOV-09:00 |
December | 2010.79 | 01-DEC-10:09 | 1551.52 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 432.11 | 10-DEC-14:30 | 1842.20 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 886.74 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 233.10 | 274.39 | |||||
Maximum of Months | 2010.79 | 1662.56 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.83 | 2087.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 903.19 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 107.76 | 07-JAN-13:00 | 793.67 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 746.31 | 13-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 130.04 | 02-FEB-14:00 | 1391.86 | 04-FEB-05:17 |
March | 1295.83 | 01-MAR-10:09 | 578.71 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 152.37 | 05-MAR-13:50 | 1290.16 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 589.06 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.07 | 15-APR-17:06 | 468.75 | 18-APR-23:55 |
May | 1295.83 | 01-MAY-09:09 | 562.04 | 25-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 731.95 | 29-MAY-15:43 | 381.09 | 07-MAY-19:20 |
June | 1295.83 | 01-JUN-09:09 | 865.51 | 15-JUN-07:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.98 | 16-JUN-21:02 | 339.35 | 18-JUN-19:55 |
July | 1295.83 | 03-JUL-09:09 | 555.08 | 05-JUL-15:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 558.44 | 30-JUL-15:44 | 338.04 | 02-JUL-15:50 |
August | 1295.83 | 01-AUG-09:09 | 590.56 | 28-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.26 | 20-AUG-12:05 | 418.03 | 14-AUG-02:53 |
September | 1295.83 | 01-SEP-09:09 | 1071.42 | 27-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 500.33 | 17-SEP-16:24 | 203.47 | 19-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 852.87 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.77 | 29-OCT-13:46 | 276.50 | 01-OCT-06:55 |
November | 1295.83 | 01-NOV-09:09 | 883.54 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.07 | 22-NOV-22:02 | 1492.04 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 999.78 | 15-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 265.80 | 10-DEC-14:28 | 1228.17 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 555.08 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 107.76 | 203.47 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 731.95 | 1492.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1328.96 | 04-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.64 | 07-JAN-13:00 | 1304.52 | 24-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 912.02 | 08-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 195.06 | 02-FEB-14:00 | 2087.78 | 04-FEB-05:16 |
March | 2010.83 | 01-MAR-10:09 | 1116.91 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 222.10 | 13-MAR-17:00 | 2021.54 | 16-MAR-02:00 |
April | 2010.83 | 03-APR-09:09 | 1149.71 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 608.28 | 15-APR-17:01 | 704.19 | 18-APR-23:55 |
May | 2010.83 | 01-MAY-09:09 | 909.12 | 25-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.82 | 29-MAY-15:54 | 467.75 | 07-MAY-19:20 |
June | 2010.83 | 01-JUN-09:09 | 1410.58 | 15-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 637.03 | 16-JUN-21:02 | 507.65 | 18-JUN-20:00 |
July | 2010.83 | 03-JUL-09:09 | 906.13 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 812.61 | 30-JUL-15:46 | 435.24 | 02-JUL-15:50 |
August | 2010.83 | 01-AUG-09:09 | 1169.99 | 28-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 734.08 | 20-AUG-12:05 | 610.38 | 14-AUG-02:53 |
September | 2010.83 | 01-SEP-09:09 | 1662.60 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 697.92 | 17-SEP-14:00 | 332.99 | 19-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1362.56 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.15 | 29-OCT-14:00 | 470.38 | 16-OCT-02:55 |
November | 2010.83 | 01-NOV-09:09 | 1231.13 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.17 | 22-NOV-22:02 | 2185.99 | 11-NOV-09:00 |
December | 2010.83 | 01-DEC-10:09 | 1544.45 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 328.41 | 10-DEC-14:50 | 1908.78 | 15-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 906.13 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 161.64 | 332.99 | |||||
Maximum of Months | 2010.83 | 1662.60 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.82 | 2185.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 830.53 | 04-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.98 | 15-JAN-11:52 | 839.60 | 24-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 713.86 | 07-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 130.04 | 02-FEB-14:00 | 1411.30 | 04-FEB-05:14 |
March | 1295.83 | 01-MAR-10:09 | 815.17 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.26 | 05-MAR-13:48 | 1370.14 | 16-MAR-02:00 |
April | 1295.83 | 03-APR-09:09 | 791.52 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 391.47 | 15-APR-17:10 | 522.77 | 18-APR-23:55 |
May | 1295.83 | 01-MAY-09:09 | 596.63 | 25-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 701.21 | 29-MAY-16:00 | 387.07 | 07-MAY-18:35 |
June | 1295.83 | 01-JUN-09:09 | 926.26 | 15-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 413.91 | 16-JUN-21:02 | 389.79 | 18-JUN-19:55 |
July | 1295.83 | 03-JUL-09:09 | 594.95 | 05-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 556.03 | 30-JUL-15:44 | 323.63 | 02-JUL-15:50 |
August | 1295.83 | 01-AUG-09:09 | 796.16 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.81 | 20-AUG-12:05 | 488.36 | 14-AUG-02:53 |
September | 1295.83 | 01-SEP-09:09 | 1071.42 | 27-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.15 | 17-SEP-13:44 | 259.85 | 19-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 911.07 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.88 | 29-OCT-13:44 | 317.19 | 01-OCT-06:55 |
November | 1295.83 | 01-NOV-09:09 | 824.68 | 24-NOV-08:09 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.39 | 22-NOV-22:02 | 1277.01 | 11-NOV-09:00 |
December | 1295.83 | 01-DEC-10:09 | 991.06 | 15-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 251.26 | 10-DEC-14:24 | 1228.23 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 594.95 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 130.04 | 259.85 | |||||
Maximum of Months | 1295.83 | 1071.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 701.21 | 1411.30 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.78 | 29-JAN-11:55 | 1045.83 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.98 | 02-FEB-14:00 | 1833.21 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.51 | 05-MAR-13:53 | 1782.56 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.90 | 15-APR-17:01 | 564.70 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.30 | 29-MAY-15:51 | 319.13 | 25-MAY-04:14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.95 | 25-JUN-14:00 | 239.80 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.90 | 30-JUL-15:32 | 233.11 | 02-JUL-15:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.15 | 13-AUG-12:52 | 378.66 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.39 | 17-SEP-14:00 | 157.81 | 19-SEP-23:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.86 | 29-OCT-14:00 | 327.91 | 16-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.55 | 22-NOV-22:02 | 1687.11 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.34 | 10-DEC-15:00 | 1711.63 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.98 | 157.81 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.30 | 1833.21 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.66 | 29-JAN-12:20 | 1772.21 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.68 | 02-FEB-14:00 | 3183.86 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.37 | 05-MAR-13:53 | 3106.41 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 907.12 | 15-APR-17:01 | 1010.57 | 18-APR-23:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.93 | 29-MAY-16:00 | 571.44 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867.73 | 25-JUN-14:00 | 481.90 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1043.09 | 30-JUL-15:42 | 410.03 | 04-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1057.70 | 13-AUG-13:00 | 633.77 | 14-AUG-02:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 999.42 | 17-SEP-14:00 | 308.27 | 19-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 749.85 | 29-OCT-14:00 | 588.12 | 16-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.83 | 04-NOV-17:03 | 2938.88 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.54 | 10-DEC-14:40 | 2952.31 | 15-DEC-05:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.68 | 308.27 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.93 | 3183.86 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.06 | 29-JAN-12:10 | 1859.82 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.98 | 02-FEB-14:00 | 2920.79 | 04-FEB-05:20 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.51 | 13-MAR-17:00 | 2987.07 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.55 | 15-APR-17:01 | 1009.44 | 18-APR-23:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1069.18 | 29-MAY-16:00 | 713.30 | 07-MAY-13:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.16 | 16-JUN-21:02 | 675.93 | 18-JUN-19:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 846.96 | 29-JUL-18:00 | 716.97 | 02-JUL-15:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.33 | 20-AUG-11:52 | 824.04 | 14-AUG-02:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 683.87 | 16-SEP-17:02 | 450.34 | 03-SEP-13:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.23 | 29-OCT-11:32 | 577.53 | 16-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.67 | 22-NOV-22:02 | 2963.87 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.34 | 10-DEC-14:50 | 2799.64 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.98 | 450.34 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1069.18 | 2987.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 95616.25 | 17-JAN-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 98136.24 | 04-FEB-05:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95799.35 | 16-MAR-04:12 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92694.20 | 19-APR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77997.41 | 09-MAY-03:02 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73265.34 | 13-JUN-03:02 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76638.92 | 04-JUL-15:31 | 6283.29 | 5733.36 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75952.93 | 22-AUG-03:02 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74398.35 | 04-SEP-10:53 | 3590.45 | 3276.21 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79739.09 | 15-OCT-16:35 | 5385.68 | 4914.31 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98248.03 | 13-NOV-06:03 | 7180.90 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 96138.02 | 21-DEC-05:12 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 73265.34 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98248.03 | 7180.90 | 5733.36 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91939.23 | 17-JAN-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92008.01 | 21-FEB-05:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88766.02 | 20-MAR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86275.10 | 19-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82065.90 | 09-MAY-03:02 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76816.74 | 19-JUN-04:33 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77281.21 | 03-JUL-05:04 | 8061.19 | 2686.80 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78929.66 | 28-AUG-05:03 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76442.33 | 28-SEP-03:02 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81559.59 | 02-OCT-05:04 | 8061.19 | 2686.80 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91628.54 | 27-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90102.20 | 18-DEC-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 76442.33 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92008.01 | 9673.43 | 3761.52 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 79174.40 | 03-JAN-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81430.18 | 13-FEB-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 79337.15 | 07-MAR-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78925.58 | 18-APR-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78426.67 | 26-MAY-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 68374.48 | 13-JUN-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 68340.12 | 06-JUL-04:04 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 74272.65 | 28-AUG-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78091.19 | 26-SEP-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 77324.63 | 28-OCT-04:12 | 0.00 | 2686.80 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79309.85 | 01-NOV-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78398.39 | 04-DEC-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 68340.12 | 0.00 | 2149.44 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81430.18 | 9673.43 | 3761.52 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 77188.14 | 02-JAN-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77682.69 | 13-FEB-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77260.96 | 31-MAR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77291.51 | 28-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80119.37 | 01-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75952.79 | 13-JUN-04:03 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76439.20 | 24-JUL-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76853.35 | 28-AUG-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72309.61 | 26-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76184.95 | 27-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76685.09 | 18-NOV-05:11 | 0.00 | 3761.52 | 31172.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 75230.69 | 01-DEC-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 72309.61 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80119.37 | 9673.43 | 3761.52 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11870.13 | 02-JAN-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.73 |
February | 11761.60 | 18-FEB-05:11 | 0.00 | 472.30 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.84 |
March | 12634.15 | 07-MAR-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.66 |
April | 16639.53 | 16-APR-13:02 | 506.08 | 219.72 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 170.11 | 0.00 |
May | 16898.47 | 29-MAY-13:23 | 404.87 | 175.78 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 273.00 | 0.00 |
June | 16716.20 | 04-JUN-10:32 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.39 | 0.00 |
July | 17358.58 | 16-JUL-16:21 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 68.07 | 0.00 |
August | 16901.65 | 20-AUG-14:22 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.31 | 0.00 |
September | 16701.36 | 24-SEP-15:12 | 506.08 | 219.72 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 129.21 | 0.00 |
October | 12772.97 | 30-OCT-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 | 0.00 |
November | 12523.69 | 22-NOV-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 |
December | 13074.34 | 11-DEC-05:22 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11761.60 | 0.00 | 175.78 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17358.58 | 1012.16 | 472.30 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 273.00 | 126.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12389.58 | 01-JAN-09:43 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.34 |
February | 11614.82 | 20-FEB-09:23 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.16 |
March | 10190.11 | 27-MAR-08:40 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 |
April | 18089.48 | 16-APR-08:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 |
May | 17853.07 | 07-MAY-08:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.71 |
June | 18358.84 | 04-JUN-08:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 16.05 | 0.00 |
July | 18299.36 | 30-JUL-09:02 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 31.85 | 0.00 |
August | 17433.88 | 27-AUG-09:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 80.95 | 0.00 |
September | 17871.43 | 24-SEP-09:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 31.22 | 0.00 |
October | 17367.84 | 09-OCT-07:53 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 0.00 |
November | 9396.75 | 20-NOV-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 0.00 |
December | 12111.06 | 11-DEC-06:02 | 782.73 | 260.89 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9396.75 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18358.84 | 1239.33 | 509.78 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 80.95 | 212.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19103.39 | 15-JAN-13:52 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.80 |
February | 18075.00 | 20-FEB-14:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.94 |
March | 17530.01 | 12-MAR-13:32 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.10 |
April | 17387.72 | 16-APR-13:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 147.12 | 0.00 |
May | 16972.90 | 29-MAY-13:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 267.64 | 0.00 |
June | 14333.77 | 08-JUN-04:12 | 0.00 | 269.89 | 2982.29 | 0.00 | 0.00 | 0.00 | 0.00 | 107.57 | 0.00 |
July | 17300.26 | 16-JUL-14:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 143.45 | 0.00 |
August | 17130.32 | 20-AUG-14:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 154.88 | 0.00 |
September | 18237.42 | 24-SEP-12:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 119.45 | 0.00 |
October | 18045.57 | 29-OCT-12:22 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 120.59 | 0.00 |
November | 18220.86 | 23-NOV-12:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 |
December | 19721.10 | 10-DEC-12:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14333.77 | 0.00 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19721.10 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 267.64 | 191.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17564.39 | 15-JAN-14:32 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 |
February | 22977.47 | 19-FEB-16:32 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 |
March | 23551.90 | 12-MAR-16:12 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.25 |
April | 24315.89 | 02-APR-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.82 |
May | 23265.55 | 29-MAY-16:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 216.28 | 0.00 |
June | 22252.00 | 10-JUN-17:04 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 55.04 | 0.00 |
July | 25186.61 | 16-JUL-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 22.08 | 0.00 |
August | 24052.35 | 20-AUG-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 61.78 | 0.00 |
September | 22862.18 | 10-SEP-15:22 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 106.37 | 0.00 |
October | 20908.82 | 09-OCT-16:32 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 39.08 | 0.00 |
November | 22675.69 | 23-NOV-14:02 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 | 0.00 |
December | 25307.48 | 10-DEC-15:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17564.39 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25307.48 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 216.28 | 80.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9310.06 | 14-JAN-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 |
February | 11192.06 | 11-FEB-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 |
March | 11193.67 | 10-MAR-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.58 |
April | 11549.70 | 12-APR-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 0.00 |
May | 16415.61 | 29-MAY-13:02 | 404.87 | 175.78 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 654.44 | 0.00 |
June | 16292.60 | 25-JUN-17:12 | 0.00 | 219.72 | 2795.85 | 0.00 | 0.00 | 0.00 | 0.00 | 124.56 | 0.00 |
July | 17012.05 | 09-JUL-16:51 | 910.95 | 395.49 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 220.89 | 0.00 |
August | 16416.64 | 13-AUG-16:01 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 346.68 | 0.00 |
September | 16036.58 | 24-SEP-16:42 | 506.08 | 219.72 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 218.72 | 0.00 |
October | 15508.83 | 08-OCT-14:22 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.30 | 0.00 |
November | 11401.82 | 22-NOV-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.58 |
December | 11629.39 | 07-DEC-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9310.06 | 0.00 | 175.78 | 2795.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17012.05 | 1012.16 | 395.49 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 654.44 | 27.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18005.21 | 01-JAN-10:02 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.17 |
February | 10388.94 | 26-FEB-10:33 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.20 |
March | 11704.97 | 27-MAR-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 0.00 |
April | 18953.38 | 09-APR-09:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 |
May | 18917.04 | 07-MAY-10:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 49.05 | 0.00 |
June | 19503.95 | 04-JUN-08:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 29.10 | 0.00 |
July | 20115.68 | 04-JUL-09:41 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 61.13 | 0.00 |
August | 18200.06 | 27-AUG-09:23 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 150.46 | 0.00 |
September | 18825.23 | 24-SEP-08:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 54.08 | 0.00 |
October | 16758.58 | 08-OCT-14:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 120.65 | 0.00 |
November | 10820.98 | 19-NOV-11:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 |
December | 11501.42 | 03-DEC-10:32 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10388.94 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20115.68 | 2478.65 | 1019.56 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 150.46 | 194.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17414.76 | 01-JAN-10:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.49 |
February | 17971.74 | 26-FEB-13:52 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.34 |
March | 16637.35 | 26-MAR-14:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 56.01 | 0.00 |
April | 16190.51 | 16-APR-14:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 280.11 | 0.00 |
May | 16335.10 | 29-MAY-13:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 646.25 | 0.00 |
June | 15876.70 | 25-JUN-17:12 | 0.00 | 219.72 | 2795.90 | 0.00 | 0.00 | 0.00 | 0.00 | 136.21 | 0.00 |
July | 16620.10 | 09-JUL-16:11 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 325.20 | 0.00 |
August | 16438.19 | 13-AUG-16:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 328.96 | 0.00 |
September | 17475.59 | 24-SEP-12:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 293.30 | 0.00 |
October | 18194.58 | 15-OCT-14:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 52.97 | 0.00 |
November | 18605.49 | 19-NOV-13:12 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.84 |
December | 19621.91 | 03-DEC-13:51 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15876.70 | 0.00 | 175.78 | 2795.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19621.91 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 646.25 | 271.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10107.91 | 14-JAN-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 |
February | 19967.85 | 19-FEB-16:12 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 0.00 |
March | 20037.72 | 12-MAR-16:22 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.28 |
April | 22245.42 | 09-APR-17:21 | 0.00 | 198.23 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.16 |
May | 20916.96 | 29-MAY-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 443.12 | 0.00 |
June | 19951.02 | 25-JUN-17:12 | 0.00 | 141.60 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 76.42 | 0.00 |
July | 22960.62 | 09-JUL-16:51 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.91 | 0.00 |
August | 21888.78 | 13-AUG-16:01 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 130.10 | 0.00 |
September | 20929.29 | 17-SEP-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 275.41 | 0.00 |
October | 20800.21 | 15-OCT-16:32 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 39.70 | 0.00 |
November | 19886.96 | 05-NOV-16:12 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 0.00 |
December | 21311.68 | 10-DEC-15:31 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 37.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10107.91 | 0.00 | 141.60 | 1801.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22960.62 | 652.28 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.12 | 168.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10412.89 | 14-JAN-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 |
February | 12159.27 | 11-FEB-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 |
March | 11537.17 | 06-MAR-05:12 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.30 |
April | 12686.08 | 12-APR-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 | 0.00 |
May | 18741.38 | 29-MAY-13:02 | 404.87 | 175.78 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 767.10 | 0.00 |
June | 19360.11 | 11-JUN-16:11 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 358.79 | 0.00 |
July | 19652.89 | 09-JUL-16:51 | 910.95 | 395.49 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 218.07 | 0.00 |
August | 18404.26 | 13-AUG-17:32 | 0.00 | 263.66 | 3355.02 | 0.00 | 0.00 | 0.00 | 0.00 | 308.13 | 0.00 |
September | 18526.49 | 04-SEP-13:42 | 506.08 | 219.72 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 272.80 | 0.00 |
October | 18381.25 | 08-OCT-14:22 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.04 | 0.00 |
November | 11715.67 | 29-NOV-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 18.30 | 0.00 |
December | 11204.70 | 11-DEC-06:02 | 1214.60 | 404.83 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10412.89 | 0.00 | 175.78 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19652.89 | 1214.60 | 404.83 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 767.10 | 254.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10238.58 | 01-JAN-11:43 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 |
February | 8004.74 | 11-FEB-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 |
March | 10703.56 | 26-MAR-10:43 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.17 |
April | 19191.63 | 09-APR-09:32 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 |
May | 18498.01 | 07-MAY-08:32 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.51 |
June | 20065.70 | 11-JUN-09:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 81.43 | 0.00 |
July | 19900.21 | 30-JUL-09:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 85.54 | 0.00 |
August | 18349.35 | 27-AUG-09:13 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 160.67 | 0.00 |
September | 18411.18 | 10-SEP-09:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 131.16 | 0.00 |
October | 18055.89 | 08-OCT-14:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 131.22 | 0.00 |
November | 9470.16 | 29-NOV-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 0.00 |
December | 9532.43 | 11-DEC-06:02 | 782.73 | 260.89 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8004.74 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20065.70 | 782.73 | 260.89 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 160.67 | 144.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20823.07 | 15-JAN-14:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.02 |
February | 21376.82 | 20-FEB-14:31 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.83 |
March | 18803.65 | 12-MAR-13:32 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.34 |
April | 18526.80 | 23-APR-14:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.10 |
May | 18816.37 | 29-MAY-13:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 758.70 | 0.00 |
June | 19095.90 | 11-JUN-16:11 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 382.17 | 0.00 |
July | 19408.51 | 09-JUL-16:11 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 343.54 | 0.00 |
August | 18806.96 | 06-AUG-13:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 381.03 | 0.00 |
September | 19325.73 | 04-SEP-13:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 210.04 | 0.00 |
October | 20776.01 | 15-OCT-14:32 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 | 0.00 |
November | 20118.89 | 05-NOV-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.15 |
December | 20190.67 | 03-DEC-14:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18526.80 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21376.82 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 758.70 | 597.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11959.68 | 14-JAN-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 |
February | 21873.94 | 20-FEB-16:31 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.45 |
March | 21749.26 | 12-MAR-16:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.09 |
April | 22914.28 | 09-APR-16:11 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.71 |
May | 22602.00 | 29-MAY-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 520.30 | 0.00 |
June | 23484.73 | 11-JUN-14:51 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 99.70 | 0.00 |
July | 25036.29 | 09-JUL-16:51 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 | 0.00 |
August | 22259.46 | 13-AUG-16:11 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 215.25 | 0.00 |
September | 22563.22 | 17-SEP-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 315.48 | 0.00 |
October | 22409.50 | 08-OCT-15:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 53.63 | 0.00 |
November | 21284.28 | 05-NOV-16:12 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 0.00 |
December | 17190.94 | 10-DEC-15:42 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 110.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11959.68 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25036.29 | 652.28 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.30 | 254.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13511.97 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.08 |
February | 11283.24 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.81 |
March | 10523.06 | 27-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.52 |
April | 13387.91 | 17-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.18 |
May | 15877.01 | 30-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 |
June | 15136.86 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
July | 15850.19 | 31-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 | 0.00 |
August | 15895.94 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 0.00 |
September | 15050.91 | 11-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 0.00 |
October | 14673.06 | 30-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.38 | 0.00 |
November | 11825.33 | 20-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.27 |
December | 12869.07 | 11-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 10523.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15895.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.38 | 134.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9636.09 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.91 |
February | 6016.88 | 17-FEB-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.92 | 0.00 |
March | 7776.14 | 06-MAR-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.11 |
April | 8350.43 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.49 |
May | 10062.10 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.93 |
June | 11386.45 | 05-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11093.97 | 10-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.71 | 0.00 |
August | 10869.49 | 21-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.18 | 0.00 |
September | 11928.91 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.75 |
October | 9613.23 | 23-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 |
November | 9733.50 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.20 |
December | 8640.16 | 11-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6016.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11928.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.92 | 157.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12891.60 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.34 | 0.00 |
February | 12991.81 | 16-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 0.00 |
March | 17007.75 | 30-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 | 0.00 |
April | 19785.05 | 13-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.58 | 0.00 |
May | 21670.59 | 18-MAY-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.60 | 0.00 |
June | 22704.43 | 09-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.71 | 0.00 |
July | 23553.14 | 28-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.81 | 0.00 |
August | 21871.55 | 23-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.04 | 0.00 |
September | 19648.14 | 08-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.42 | 0.00 |
October | 18467.69 | 06-OCT-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.16 | 0.00 |
November | 14922.26 | 07-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.94 | 0.00 |
December | 12726.84 | 08-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 12726.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 | 0.00 | |
Maximum of Months | 23553.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.04 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2027.39 | 22-JAN-17:33 | 35.07 | 52.77 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4333.05 | 20-FEB-17:42 | 58.46 | 87.96 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7230.16 | 31-MAR-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8003.63 | 09-APR-17:53 | 0.00 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3514.17 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5390.60 | 30-JUN-23:55 | 0.00 | 35.18 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7355.53 | 31-JUL-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7773.21 | 06-AUG-18:12 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3522.14 | 30-SEP-24:00 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5375.54 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5922.05 | 07-NOV-17:00 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7895.82 | 03-DEC-17:00 | 11.69 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2027.39 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8003.63 | 222.14 | 316.63 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1859.63 | 02-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3953.87 | 20-FEB-17:42 | 58.46 | 87.96 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6968.07 | 31-MAR-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7538.81 | 09-APR-17:53 | 0.00 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3410.82 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5205.96 | 30-JUN-23:40 | 0.00 | 35.18 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7030.75 | 31-JUL-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7318.55 | 13-AUG-18:52 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3387.41 | 30-SEP-24:00 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5095.30 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5639.37 | 07-NOV-17:00 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7430.93 | 06-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1859.63 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7538.81 | 222.14 | 316.63 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1891.78 | 02-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4094.73 | 20-FEB-17:42 | 58.46 | 87.96 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6914.40 | 31-MAR-24:00 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7808.87 | 09-APR-17:53 | 0.00 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3441.07 | 31-MAY-24:00 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5210.38 | 30-JUN-23:40 | 0.00 | 35.18 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7040.54 | 31-JUL-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7567.24 | 06-AUG-18:12 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3450.96 | 30-SEP-24:00 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5022.19 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5702.11 | 07-NOV-17:00 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7491.67 | 06-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1891.78 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7808.87 | 222.14 | 316.63 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 93487.74 | 02-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184607.08 | 21-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359462.20 | 31-MAR-23:55 | 0.00 | 461.88 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368959.14 | 17-APR-21:02 | 1518.53 | 2771.56 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176465.86 | 31-MAY-24:00 | 0.00 | 230.94 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268012.56 | 30-JUN-23:55 | 0.00 | 461.88 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 357679.29 | 31-JUL-23:13 | 0.00 | 692.81 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369857.28 | 28-AUG-12:05 | 9617.36 | 8314.37 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176815.47 | 30-SEP-23:55 | 0.00 | 461.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268708.87 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276699.72 | 06-NOV-17:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368906.03 | 11-DEC-17:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93487.74 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369857.28 | 9617.36 | 8314.37 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.176206E+13 | 1289796.17 | 02-JAN-08:50 | 0.552804E+11 | 94651.30 | 25-JAN-06:10 |
February | 0.199855E+13 | 1431862.63 | 10-FEB-16:10 | 0.512246E+11 | 315646.84 | 04-FEB-06:10 |
March | 0.270306E+13 | 1607312.65 | 09-MAR-16:49 | 0.561896E+11 | 197706.63 | 16-MAR-05:10 |
April | 0.305570E+13 | 1801106.51 | 14-APR-15:00 | 0.501496E+11 | 66475.46 | 03-APR-11:39 |
May | 0.209540E+13 | 1382023.18 | 30-MAY-15:30 | 0.512709E+11 | 63912.81 | 01-MAY-11:50 |
June | 0.252674E+13 | 1553552.50 | 08-JUN-15:00 | 0.491194E+11 | 61136.40 | 05-JUN-11:20 |
July | 0.298674E+13 | 1719424.75 | 24-JUL-15:39 | 0.478540E+11 | 59665.15 | 03-JUL-11:50 |
August | 0.343863E+13 | 1851059.15 | 21-AUG-15:00 | 0.507952E+11 | 60986.89 | 31-AUG-11:20 |
September | 0.206932E+13 | 1365825.28 | 11-SEP-07:40 | 0.483792E+11 | 62699.64 | 22-SEP-11:00 |
October | 0.246943E+13 | 1509222.45 | 03-OCT-07:00 | 0.514477E+11 | 65119.81 | 19-OCT-11:39 |
November | 0.267333E+13 | 1632839.43 | 10-NOV-08:30 | 0.518405E+11 | 67188.98 | 13-NOV-12:30 |
December | 0.298427E+13 | 1743811.91 | 08-DEC-08:50 | 0.546139E+11 | 147714.86 | 15-DEC-06:10 |
Annual Sum or Average | 0.307632E+14 | 0.618165E+12 | ||||
Minimum of Months | 0.176206E+13 | 1289796.17 | 0.478540E+11 | 59665.15 | ||
Maximum of Months | 0.343863E+13 | 1851059.15 | 0.561896E+11 | 315646.84 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.206815E+12 | 0.357910E+11 | 0.766053E+12 | 0.162121E+12 | 0.177278E+12 | 0.487770E+11 | 0.00 | 0.242069E+12 | 0.115878E+12 | 0.334813E+09 | 0.694745E+10 | 0.00 | 0.00 |
February | 0.186601E+12 | 0.298547E+11 | 0.978954E+12 | 0.146439E+12 | 0.168381E+12 | 0.451464E+11 | 0.00 | 0.317470E+12 | 0.118916E+12 | 0.354257E+09 | 0.643457E+10 | 0.00 | 0.00 |
March | 0.220810E+12 | 0.300946E+11 | 0.141687E+13 | 0.162292E+12 | 0.203003E+12 | 0.601920E+11 | 0.00 | 0.457460E+12 | 0.144079E+12 | 0.294262E+09 | 0.796588E+10 | 0.00 | 0.00 |
April | 0.196571E+12 | 0.263315E+11 | 0.165903E+13 | 0.156876E+12 | 0.213426E+12 | 0.663966E+11 | 0.00 | 0.576120E+12 | 0.152595E+12 | 0.00 | 0.835475E+10 | 0.00 | 0.00 |
May | 0.211661E+12 | 0.246398E+11 | 0.774844E+12 | 0.162206E+12 | 0.241352E+12 | 0.709252E+11 | 0.00 | 0.417805E+12 | 0.183263E+12 | 0.00 | 0.870190E+10 | 0.00 | 0.00 |
June | 0.210728E+12 | 0.228338E+11 | 0.106252E+13 | 0.157035E+12 | 0.245009E+12 | 0.768231E+11 | 0.00 | 0.548341E+12 | 0.194287E+12 | 0.00 | 0.916336E+10 | 0.00 | 0.00 |
July | 0.196703E+12 | 0.240667E+11 | 0.139340E+13 | 0.162046E+12 | 0.252307E+12 | 0.806235E+11 | 0.00 | 0.666867E+12 | 0.201135E+12 | 0.00 | 0.959099E+10 | 0.00 | 0.00 |
August | 0.219965E+12 | 0.262184E+11 | 0.173200E+13 | 0.162291E+12 | 0.250740E+12 | 0.818761E+11 | 0.00 | 0.751678E+12 | 0.204291E+12 | 0.00 | 0.956891E+10 | 0.00 | 0.00 |
September | 0.197067E+12 | 0.277803E+11 | 0.740713E+12 | 0.156875E+12 | 0.223349E+12 | 0.735403E+11 | 0.00 | 0.450549E+12 | 0.190658E+12 | 0.00 | 0.878207E+10 | 0.00 | 0.00 |
October | 0.205386E+12 | 0.316727E+11 | 0.108340E+13 | 0.162121E+12 | 0.214893E+12 | 0.729601E+11 | 0.00 | 0.506125E+12 | 0.184323E+12 | 0.00 | 0.854808E+10 | 0.00 | 0.00 |
November | 0.204107E+12 | 0.336733E+11 | 0.135889E+13 | 0.156940E+12 | 0.192843E+12 | 0.625876E+11 | 0.00 | 0.497634E+12 | 0.159017E+12 | 89498440.77 | 0.754772E+10 | 0.00 | 0.00 |
December | 0.200661E+12 | 0.364284E+11 | 0.170972E+13 | 0.162046E+12 | 0.180724E+12 | 0.573038E+11 | 0.00 | 0.490816E+12 | 0.138945E+12 | 72541547.79 | 0.755239E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.245708E+13 | 0.349385E+12 | 0.146764E+14 | 0.190929E+13 | 0.256331E+13 | 0.797152E+12 | 0.00 | 0.592293E+13 | 0.198739E+13 | 0.114537E+10 | 0.991581E+11 | 0.00 | 0.00 |
Minimum of Months | 0.186601E+12 | 0.228338E+11 | 0.740713E+12 | 0.146439E+12 | 0.168381E+12 | 0.451464E+11 | 0.00 | 0.242069E+12 | 0.115878E+12 | 0.00 | 0.643457E+10 | 0.00 | 0.00 |
Maximum of Months | 0.220810E+12 | 0.364284E+11 | 0.173200E+13 | 0.162292E+12 | 0.252307E+12 | 0.818761E+11 | 0.00 | 0.751678E+12 | 0.204291E+12 | 0.354257E+09 | 0.959099E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.636521E+09 | 0.00 | 0.546438E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.197073E+10 | 0.00 | 0.492539E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.652540E+09 | 0.00 | 0.555371E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.501496E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.512709E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.491194E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.478540E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.507952E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.483792E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.514477E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.127713E+09 | 0.00 | 0.517128E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.123541E+10 | 0.00 | 0.533785E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.462292E+10 | 0.00 | 0.613542E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.478540E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.197073E+10 | 0.00 | 0.555371E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 235052.03 | 04-JAN-16:00 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 116877.04 | 30-JAN-08:20 | 146667.99 | 02-JAN-08:00 | 52573.56 | 02-JAN-16:49 | 0.00 | 01-JAN-00:10 |
February | 221541.66 | 08-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 116875.98 | 07-FEB-08:20 | 154923.57 | 17-FEB-16:30 | 54487.80 | 16-FEB-13:50 | 0.00 | 01-FEB-00:10 |
March | 225337.75 | 14-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 116879.34 | 14-MAR-07:19 | 173247.37 | 09-MAR-16:30 | 52907.02 | 31-MAR-15:09 | 0.00 | 01-MAR-00:10 |
April | 225639.15 | 12-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 116879.50 | 12-APR-07:19 | 200816.64 | 24-APR-15:20 | 52788.86 | 17-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 217074.59 | 25-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 116874.97 | 25-MAY-07:19 | 218597.60 | 30-MAY-15:50 | 50718.97 | 01-MAY-15:50 | 0.00 | 01-MAY-00:10 |
June | 236027.22 | 15-JUN-07:30 | 40855.88 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 116885.00 | 15-JUN-07:40 | 215998.14 | 08-JUN-15:50 | 49986.83 | 26-JUN-10:09 | 0.00 | 01-JUN-00:10 |
July | 216789.04 | 05-JUL-07:10 | 40855.88 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 116874.82 | 05-JUL-07:19 | 221222.39 | 07-JUL-15:30 | 50540.88 | 31-JUL-14:09 | 0.00 | 01-JUL-00:10 |
August | 225943.85 | 28-AUG-07:10 | 40855.88 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 116879.66 | 28-AUG-07:19 | 210608.46 | 02-AUG-15:00 | 50874.16 | 31-AUG-15:20 | 0.00 | 01-AUG-00:10 |
September | 247210.90 | 27-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 116890.93 | 27-SEP-07:19 | 188602.64 | 11-SEP-15:00 | 51358.15 | 29-SEP-11:39 | 0.00 | 01-SEP-00:10 |
October | 235939.85 | 31-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 116884.96 | 31-OCT-07:19 | 173479.04 | 10-OCT-15:00 | 52804.24 | 06-OCT-16:19 | 0.00 | 01-OCT-00:10 |
November | 232091.36 | 29-NOV-16:00 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 116881.71 | 24-NOV-08:20 | 160015.48 | 21-NOV-16:30 | 53230.13 | 22-NOV-12:50 | 0.00 | 01-NOV-00:10 |
December | 242651.33 | 15-DEC-16:00 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 116883.23 | 29-DEC-08:39 | 156041.85 | 11-DEC-11:30 | 54370.27 | 07-DEC-12:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 216789.04 | 40855.88 | 423497.50 | 116874.82 | 146667.99 | 49986.83 | 0.00 | |||||||
Maximum of Months | 247210.90 | 40855.88 | 778371.69 | 116890.93 | 221222.39 | 54487.80 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 300476.60 | 13-JAN-13:00 | 86109.64 | 02-JAN-08:30 | 3672.88 | 25-JAN-01:00 | 4520.72 | 01-JAN-08:50 | 0.00 | 0.00 |
February | 325158.94 | 09-FEB-15:39 | 86109.64 | 02-FEB-08:20 | 4076.66 | 04-FEB-05:00 | 4520.72 | 01-FEB-06:10 | 0.00 | 0.00 |
March | 371618.27 | 09-MAR-15:09 | 86109.64 | 03-MAR-11:30 | 2982.20 | 16-MAR-17:00 | 4520.72 | 01-MAR-06:10 | 0.00 | 0.00 |
April | 423594.34 | 13-APR-12:09 | 86109.64 | 01-APR-14:09 | 0.00 | 01-APR-00:10 | 4520.72 | 01-APR-04:19 | 0.00 | 0.00 |
May | 331675.96 | 10-MAY-12:09 | 86109.64 | 24-MAY-04:00 | 0.00 | 01-MAY-00:10 | 4520.72 | 01-MAY-04:19 | 0.00 | 0.00 |
June | 373478.55 | 08-JUN-12:09 | 86109.64 | 03-JUN-17:49 | 0.00 | 01-JUN-00:10 | 4520.72 | 01-JUN-03:09 | 0.00 | 0.00 |
July | 418751.22 | 05-JUL-12:09 | 86109.64 | 03-JUL-03:20 | 0.00 | 01-JUL-00:10 | 4520.72 | 01-JUL-03:20 | 0.00 | 0.00 |
August | 458739.71 | 17-AUG-12:09 | 86109.64 | 01-AUG-03:09 | 0.00 | 01-AUG-00:10 | 4520.72 | 01-AUG-00:10 | 0.00 | 0.00 |
September | 333679.92 | 07-SEP-12:09 | 86109.64 | 03-SEP-08:39 | 0.00 | 01-SEP-00:10 | 4520.72 | 01-SEP-00:40 | 0.00 | 0.00 |
October | 370797.14 | 02-OCT-12:09 | 86109.64 | 01-OCT-11:00 | 0.00 | 01-OCT-00:10 | 4520.72 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 396655.38 | 30-NOV-13:09 | 86109.64 | 04-NOV-03:20 | 2338.08 | 13-NOV-05:00 | 4520.72 | 01-NOV-04:19 | 0.00 | 0.00 |
December | 395493.92 | 07-DEC-13:09 | 86109.64 | 01-DEC-11:50 | 2536.20 | 20-DEC-19:30 | 4520.72 | 01-DEC-05:19 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 300476.60 | 86109.64 | 0.00 | 4520.72 | 0.00 | 0.00 | ||||
Maximum of Months | 458739.71 | 86109.64 | 4076.66 | 4520.72 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1289796.17 | 02-JAN-08:50 | 214075.53 | 423497.50 | 0.00 | 116873.53 | 144532.67 | 49251.03 | 0.00 | 250935.56 | 86109.64 |
February | 1431862.63 | 10-FEB-16:10 | 212815.01 | 541788.89 | 0.00 | 82829.33 | 144646.20 | 49629.95 | 0.00 | 309522.89 | 86109.64 |
March | 1607312.65 | 09-MAR-16:49 | 212815.01 | 660080.29 | 0.00 | 82829.33 | 167868.41 | 49039.79 | 0.00 | 344049.46 | 86109.64 |
April | 1801106.51 | 14-APR-15:00 | 212815.01 | 778371.69 | 0.00 | 82829.33 | 198483.36 | 49455.74 | 0.00 | 388521.02 | 86109.64 |
May | 1382023.18 | 30-MAY-15:30 | 212815.01 | 423497.50 | 0.00 | 82829.33 | 218589.32 | 49708.73 | 0.00 | 303952.93 | 86109.64 |
June | 1553552.50 | 08-JUN-15:00 | 212815.01 | 541788.89 | 0.00 | 82829.33 | 215646.73 | 49859.02 | 0.00 | 359983.15 | 86109.64 |
July | 1719424.75 | 24-JUL-15:39 | 212815.01 | 660080.29 | 0.00 | 82829.33 | 218686.31 | 50057.55 | 0.00 | 404325.89 | 86109.64 |
August | 1851059.15 | 21-AUG-15:00 | 212815.01 | 778371.69 | 0.00 | 82829.33 | 198046.55 | 50246.92 | 0.00 | 438119.29 | 86109.64 |
September | 1365825.28 | 11-SEP-07:40 | 212815.01 | 423497.50 | 0.00 | 116872.72 | 159996.62 | 49394.99 | 0.00 | 312618.08 | 86109.64 |
October | 1509222.45 | 03-OCT-07:00 | 212815.01 | 541788.89 | 0.00 | 116872.72 | 149216.16 | 49271.35 | 0.00 | 348627.95 | 86109.64 |
November | 1632839.43 | 10-NOV-08:30 | 212815.01 | 660080.29 | 0.00 | 116872.72 | 138891.54 | 49206.65 | 0.00 | 364342.86 | 86109.64 |
December | 1743811.91 | 08-DEC-08:50 | 212815.01 | 778371.69 | 0.00 | 116872.72 | 136653.83 | 49055.23 | 0.00 | 359413.07 | 86109.64 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1289796.17 | 212815.01 | 423497.50 | 0.00 | 82829.33 | 136653.83 | 49039.79 | 0.00 | 250935.56 | 86109.64 | |
Maximum of Months | 1851059.15 | 214075.53 | 778371.69 | 0.00 | 116873.53 | 218686.31 | 50246.92 | 0.00 | 438119.29 | 86109.64 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 74559.01 | 25-JAN-06:10 | 0.00 | 69759.54 | 17-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 308365.96 | 04-FEB-06:10 | 0.00 | 69473.88 | 08-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 169769.32 | 16-MAR-05:10 | 0.00 | 68638.06 | 02-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 66475.46 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 63912.81 | 01-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 61136.40 | 05-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 59665.15 | 03-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 60986.89 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 62699.64 | 22-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 65119.81 | 19-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 37823.54 | 13-NOV-06:10 | 0.00 | 67188.98 | 13-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 140433.98 | 15-DEC-06:10 | 0.00 | 69504.46 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 59665.15 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 308365.96 | 0.00 | 69759.54 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.04 | 1.33 | 27.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.03 | 0.67 | 26.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.65 | 0.00 | 26.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.70 | 0.00 | 26.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.58 | 0.83 | 26.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.34 | 0.33 | 26.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 26.20 | 0.67 | 26.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 26.35 | 1.00 | 26.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.61 | 0.83 | 26.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 26.91 | 0.50 | 26.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.00 | 2.17 | 26.97 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.04 | 0.67 | 27.06 |
Annual Sum or Average | 0.00 | 0.00 | 104.83 | 26.74 | 9.00 | 26.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.20 | 0.00 | 26.09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.04 | 2.17 | 27.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.62 | 0.00 | 25.62 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.66 | 0.00 | 25.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.58 | 0.00 | 25.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.67 | 0.00 | 25.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.83 | 0.00 | 25.83 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.62 | 0.00 | 25.62 |
Annual Sum or Average | 0.00 | 0.00 | 5.00 | 25.63 | 0.00 | 25.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.83 | 0.00 | 25.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.31 | 1.00 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.32 | 1.50 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.92 | 2.33 | 27.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.10 | 7.67 | 27.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.74 | 4.67 | 26.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.83 | 2.00 | 27.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 31.33 | 26.95 | 19.17 | 27.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.32 | 7.67 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.51 | 2.67 | 27.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.53 | 1.67 | 27.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.41 | 1.00 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.64 | 7.17 | 27.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.53 | 7.17 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.43 | 7.67 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.57 | 14.67 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.33 | 7.67 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.39 | 10.33 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.37 | 7.50 | 27.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.33 | 0.67 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
Annual Sum or Average | 0.00 | 0.00 | 80.83 | 27.47 | 68.33 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.64 | 14.67 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 25.74 | 25.50 | 25.73 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 25.70 | 22.50 | 25.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.57 | 5.50 | 26.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.36 | 5.17 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.32 | 2.17 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 26.83 | 2.17 | 27.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.12 | 7.33 | 27.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 26.88 | 5.33 | 27.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.26 | 8.17 | 27.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 26.07 | 25.67 | 26.02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 25.51 | 44.00 | 25.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 25.78 | 31.50 | 25.76 |
Annual Sum or Average | 0.00 | 0.00 | 208.00 | 26.07 | 185.00 | 26.05 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.51 | 2.17 | 25.50 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 27.36 | 44.00 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.27 | 3.17 | 27.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.50 | 4.83 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.32 | 6.50 | 27.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 | 27.55 | 16.67 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 27.11 | 11.33 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 27.17 | 12.33 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 71.17 | 27.50 | 22.83 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 71.00 | 27.60 | 19.00 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 27.18 | 11.50 | 27.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 27.23 | 13.83 | 27.38 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 27.16 | 10.33 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.40 | 11.67 | 27.53 |
Annual Sum or Average | 0.00 | 0.00 | 401.17 | 27.38 | 144.00 | 27.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.11 | 3.17 | 27.27 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 71.17 | 27.60 | 22.83 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.24 | 1.67 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.93 | 2.17 | 27.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.21 | 6.17 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.21 | 2.83 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.12 | 3.83 | 27.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.50 | 27.15 | 16.67 | 27.26 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.24 | 6.17 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.51 | 1.83 | 27.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.41 | 1.00 | 27.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.38 | 1.67 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.73 | 7.67 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.55 | 7.83 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.41 | 8.00 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.70 | 14.67 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.55 | 8.00 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.47 | 11.83 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.54 | 10.50 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.50 | 27.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
Annual Sum or Average | 0.00 | 0.00 | 90.50 | 27.56 | 73.83 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.73 | 14.67 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 41.17 | 25.48 | 41.17 | 25.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 25.54 | 29.83 | 25.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.14 | 5.83 | 26.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.44 | 3.00 | 27.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.45 | 2.17 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.00 | 1.17 | 27.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.30 | 5.83 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.39 | 4.00 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 26.86 | 11.67 | 26.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 47.00 | 25.67 | 43.50 | 25.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 25.55 | 52.00 | 25.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 25.82 | 35.50 | 25.81 |
Annual Sum or Average | 0.00 | 0.00 | 249.50 | 25.84 | 235.67 | 25.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.48 | 1.17 | 25.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 27.45 | 52.00 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.93 | 2.83 | 27.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.75 | 2.33 | 27.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.65 | 4.67 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.20 | 7.17 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 26.97 | 6.17 | 27.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 27.21 | 10.50 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 27.01 | 6.00 | 27.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.27 | 8.50 | 27.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.45 | 6.33 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.58 | 3.33 | 27.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.68 | 3.00 | 27.68 |
Annual Sum or Average | 0.00 | 0.00 | 136.33 | 27.26 | 61.17 | 27.43 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.97 | 0.33 | 27.15 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 27.93 | 10.50 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.36 | 1.00 | 27.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.40 | 4.33 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.29 | 5.00 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.45 | 9.50 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.36 | 4.33 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.30 | 5.83 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.33 | 2.17 | 27.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 18.95 | 0.00 | 18.95 | 46.50 | 27.34 | 32.17 | 27.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.95 | 0.00 | 18.95 | 14.17 | 27.45 | 9.50 | 27.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.43 | 1.83 | 27.43 |
February | 0.17 | 19.02 | 0.00 | 19.02 | 0.17 | 23.15 | 0.17 | 24.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.40 | 2.33 | 27.40 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.76 | 8.67 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.61 | 10.17 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.57 | 8.83 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.85 | 15.17 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.60 | 8.67 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.51 | 12.17 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.60 | 10.83 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
Annual Sum or Average | 0.17 | 19.02 | 0.00 | 19.02 | 105.67 | 27.63 | 79.33 | 27.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 23.15 | 0.17 | 24.53 |
Maximum of Months | 0.17 | 19.02 | 0.00 | 19.02 | 22.50 | 27.85 | 15.17 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.19 | 13.50 | 26.19 |
February | 0.17 | 19.24 | 0.00 | 19.24 | 16.17 | 25.82 | 15.67 | 25.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.59 | 4.00 | 27.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.55 | 4.83 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.42 | 4.50 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.28 | 3.50 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.49 | 8.67 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.45 | 5.33 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.44 | 9.50 | 27.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 26.41 | 22.17 | 26.35 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 25.61 | 35.67 | 25.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 26.25 | 18.83 | 26.23 |
Annual Sum or Average | 0.17 | 19.24 | 0.00 | 19.24 | 169.67 | 26.50 | 146.17 | 26.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.61 | 3.50 | 25.60 |
Maximum of Months | 0.17 | 19.24 | 0.00 | 19.24 | 36.17 | 27.59 | 35.67 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.34 | 0.50 | 27.34 |
February | 0.17 | 19.21 | 0.00 | 19.21 | 3.33 | 27.53 | 2.83 | 27.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.74 | 3.33 | 27.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.82 | 5.33 | 27.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.44 | 8.50 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.11 | 7.00 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 27.37 | 11.67 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.17 | 7.50 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.38 | 9.50 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.56 | 7.50 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.65 | 3.67 | 27.66 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.76 | 3.17 | 27.76 |
Annual Sum or Average | 0.17 | 19.21 | 0.00 | 19.21 | 154.67 | 27.40 | 70.50 | 27.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.11 | 0.50 | 27.29 |
Maximum of Months | 0.17 | 19.21 | 0.00 | 19.21 | 32.50 | 27.82 | 11.67 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 61.50 | 27.73 | 57.17 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 61.50 | 27.73 | 57.17 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 61.50 | 27.73 | 57.17 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 27.66 | 32.83 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 34.00 | 27.66 | 32.83 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 27.66 | 32.83 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.71 | 17.17 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 20.33 | 27.71 | 17.17 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.71 | 17.17 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 164.17 | 28.19 | 151.67 | 28.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.87 | 0.00 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 685.00 | 28.86 | 485.17 | 28.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 | 27.95 | 68.50 | 27.95 |
Annual Sum or Average | 0.00 | 0.00 | 921.50 | 28.67 | 705.33 | 28.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 685.00 | 28.86 | 485.17 | 28.95 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.00 | 25.41 | 424.67 | 24.86 | 124.17 | 24.96 |
February | 105.33 | 25.10 | 386.50 | 24.75 | 105.17 | 24.81 |
March | 136.67 | 25.11 | 442.50 | 24.66 | 136.67 | 24.74 |
April | 201.33 | 25.14 | 478.00 | 24.73 | 201.33 | 24.82 |
May | 275.17 | 24.95 | 508.00 | 24.67 | 275.17 | 24.74 |
June | 267.00 | 24.88 | 496.00 | 24.62 | 267.00 | 24.68 |
July | 253.50 | 25.23 | 497.00 | 24.83 | 253.50 | 24.93 |
August | 199.33 | 25.18 | 514.00 | 24.68 | 199.33 | 24.79 |
September | 241.17 | 25.13 | 485.00 | 24.76 | 241.17 | 24.85 |
October | 209.50 | 25.43 | 502.00 | 24.86 | 209.50 | 24.99 |
November | 173.33 | 25.42 | 487.00 | 24.84 | 173.33 | 24.96 |
December | 135.17 | 25.62 | 465.50 | 24.88 | 135.17 | 25.01 |
Annual Sum or Average | 2322.50 | 25.19 | 5686.17 | 24.76 | 2321.50 | 24.85 |
Minimum of Months | 105.33 | 24.88 | 386.50 | 24.62 | 105.17 | 24.68 |
Maximum of Months | 275.17 | 25.62 | 514.00 | 24.88 | 275.17 | 25.01 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 24.29 | 421.50 | 24.43 | 0.50 | 24.43 |
February | 4.83 | 24.00 | 387.17 | 24.41 | 0.00 | 24.41 |
March | 0.00 | 0.00 | 443.83 | 24.27 | 0.00 | 24.27 |
April | 0.00 | 0.00 | 480.83 | 24.23 | 0.00 | 24.23 |
May | 0.00 | 0.00 | 508.00 | 24.24 | 0.00 | 24.24 |
June | 0.00 | 0.00 | 496.00 | 24.19 | 0.00 | 24.19 |
July | 0.00 | 0.00 | 497.00 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 514.00 | 24.22 | 0.00 | 24.22 |
September | 0.00 | 0.00 | 485.00 | 24.26 | 0.00 | 24.26 |
October | 0.00 | 0.00 | 502.00 | 24.28 | 0.00 | 24.28 |
November | 0.00 | 0.00 | 484.67 | 24.35 | 0.00 | 24.35 |
December | 0.00 | 0.00 | 458.33 | 24.35 | 0.00 | 24.35 |
Annual Sum or Average | 10.17 | 24.15 | 5678.33 | 24.28 | 0.50 | 24.28 |
Minimum of Months | 0.00 | 0.00 | 387.17 | 24.19 | 0.00 | 24.19 |
Maximum of Months | 5.33 | 24.29 | 514.00 | 24.43 | 0.50 | 24.43 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.17 | 23.77 | 359.67 | 24.24 | 0.00 | 24.24 |
February | 37.50 | 23.56 | 335.33 | 24.23 | 0.00 | 24.23 |
March | 18.00 | 24.34 | 403.50 | 24.27 | 4.17 | 24.29 |
April | 1.33 | 26.25 | 474.33 | 24.25 | 1.33 | 24.25 |
May | 0.00 | 0.00 | 508.00 | 24.22 | 0.00 | 24.22 |
June | 0.00 | 0.00 | 496.00 | 24.19 | 0.00 | 24.19 |
July | 0.00 | 0.00 | 497.00 | 24.19 | 0.00 | 24.19 |
August | 0.00 | 0.00 | 514.00 | 24.18 | 0.00 | 24.18 |
September | 0.00 | 0.00 | 481.00 | 24.23 | 0.00 | 24.23 |
October | 0.00 | 0.00 | 487.00 | 24.29 | 0.00 | 24.29 |
November | 0.00 | 0.00 | 475.33 | 24.33 | 0.00 | 24.33 |
December | 19.50 | 23.56 | 381.00 | 24.25 | 0.00 | 24.25 |
Annual Sum or Average | 103.50 | 23.78 | 5412.17 | 24.24 | 5.50 | 24.24 |
Minimum of Months | 0.00 | 0.00 | 335.33 | 24.18 | 0.00 | 24.18 |
Maximum of Months | 37.50 | 26.25 | 514.00 | 24.33 | 4.17 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 111.67 | 23.26 | 277.17 | 23.90 | 0.00 | 23.90 |
February | 78.17 | 22.94 | 319.67 | 24.00 | 0.17 | 24.00 |
March | 66.00 | 23.65 | 388.33 | 24.19 | 4.17 | 24.20 |
April | 3.00 | 24.37 | 469.33 | 24.27 | 0.83 | 24.28 |
May | 0.00 | 0.00 | 508.00 | 24.28 | 0.00 | 24.28 |
June | 0.00 | 0.00 | 496.00 | 24.25 | 0.00 | 24.25 |
July | 0.00 | 0.00 | 497.00 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 512.00 | 24.23 | 0.00 | 24.23 |
September | 0.00 | 0.00 | 485.00 | 24.29 | 0.00 | 24.29 |
October | 0.00 | 0.00 | 502.00 | 24.33 | 0.00 | 24.33 |
November | 9.50 | 23.14 | 456.33 | 24.26 | 0.00 | 24.26 |
December | 92.83 | 23.16 | 323.33 | 23.99 | 1.17 | 23.99 |
Annual Sum or Average | 361.17 | 23.24 | 5234.17 | 24.20 | 6.33 | 24.20 |
Minimum of Months | 0.00 | 0.00 | 277.17 | 23.90 | 0.00 | 23.90 |
Maximum of Months | 111.67 | 24.37 | 512.00 | 24.33 | 4.17 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.00 | 23.32 | 301.17 | 23.98 | 5.17 | 23.99 |
February | 74.83 | 23.44 | 334.17 | 24.12 | 8.00 | 24.15 |
March | 71.17 | 23.62 | 392.00 | 24.17 | 6.00 | 24.19 |
April | 10.00 | 26.10 | 470.00 | 24.34 | 8.00 | 24.38 |
May | 39.67 | 26.35 | 508.00 | 24.56 | 39.67 | 24.68 |
June | 33.67 | 26.49 | 496.00 | 24.53 | 33.67 | 24.65 |
July | 47.67 | 26.75 | 497.00 | 24.72 | 47.67 | 24.88 |
August | 29.83 | 26.77 | 514.00 | 24.51 | 29.83 | 24.62 |
September | 25.00 | 26.68 | 485.00 | 24.56 | 25.00 | 24.66 |
October | 20.50 | 26.52 | 502.00 | 24.50 | 20.50 | 24.57 |
November | 16.33 | 24.74 | 467.83 | 24.32 | 10.50 | 24.35 |
December | 65.00 | 23.33 | 358.00 | 24.15 | 0.17 | 24.16 |
Annual Sum or Average | 558.67 | 24.62 | 5325.17 | 24.39 | 234.17 | 24.47 |
Minimum of Months | 10.00 | 23.32 | 301.17 | 23.98 | 0.17 | 23.99 |
Maximum of Months | 125.00 | 26.77 | 514.00 | 24.72 | 47.67 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 97.33 | 24.01 | 349.67 | 24.32 | 21.50 | 24.42 |
February | 50.17 | 24.06 | 367.17 | 24.33 | 15.67 | 24.39 |
March | 45.83 | 24.30 | 429.00 | 24.29 | 16.00 | 24.35 |
April | 35.83 | 26.71 | 471.67 | 24.53 | 34.17 | 24.68 |
May | 52.83 | 26.56 | 508.00 | 24.66 | 52.83 | 24.82 |
June | 44.50 | 26.65 | 496.00 | 24.60 | 44.50 | 24.76 |
July | 62.00 | 26.93 | 497.00 | 24.82 | 62.00 | 25.03 |
August | 36.33 | 26.85 | 514.00 | 24.53 | 36.33 | 24.68 |
September | 49.17 | 26.84 | 485.00 | 24.73 | 49.17 | 24.91 |
October | 46.17 | 26.70 | 502.00 | 24.66 | 46.17 | 24.82 |
November | 18.17 | 25.73 | 475.50 | 24.40 | 15.50 | 24.46 |
December | 73.00 | 23.40 | 351.50 | 24.16 | 4.17 | 24.18 |
Annual Sum or Average | 611.33 | 25.48 | 5446.50 | 24.52 | 398.00 | 24.65 |
Minimum of Months | 18.17 | 23.40 | 349.67 | 24.16 | 4.17 | 24.18 |
Maximum of Months | 97.33 | 26.93 | 514.00 | 24.82 | 62.00 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 82.67 | 25.05 | 401.50 | 24.67 | 41.67 | 24.83 |
February | 54.67 | 25.12 | 395.67 | 24.62 | 29.83 | 24.75 |
March | 53.50 | 24.82 | 438.00 | 24.42 | 25.33 | 24.52 |
April | 27.00 | 26.60 | 475.33 | 24.49 | 25.00 | 24.60 |
May | 41.67 | 26.33 | 508.00 | 24.56 | 41.67 | 24.68 |
June | 29.33 | 26.45 | 496.00 | 24.49 | 29.33 | 24.59 |
July | 41.33 | 26.76 | 497.00 | 24.67 | 41.33 | 24.82 |
August | 31.17 | 26.82 | 514.00 | 24.53 | 31.17 | 24.65 |
September | 41.50 | 26.88 | 485.00 | 24.71 | 41.50 | 24.87 |
October | 49.33 | 26.91 | 502.00 | 24.82 | 49.33 | 24.99 |
November | 51.17 | 26.47 | 479.67 | 24.79 | 47.67 | 24.94 |
December | 65.33 | 25.66 | 435.67 | 24.70 | 43.67 | 24.88 |
Annual Sum or Average | 568.67 | 25.99 | 5627.83 | 24.62 | 447.50 | 24.76 |
Minimum of Months | 27.00 | 24.82 | 395.67 | 24.42 | 25.00 | 24.52 |
Maximum of Months | 82.67 | 26.91 | 514.00 | 24.82 | 49.33 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.33 | 24.98 | 400.50 | 24.56 | 21.33 | 24.65 |
February | 49.17 | 26.03 | 401.33 | 24.75 | 35.33 | 24.92 |
March | 63.67 | 26.69 | 463.67 | 24.84 | 60.00 | 25.04 |
April | 89.17 | 26.91 | 485.00 | 24.99 | 89.17 | 25.25 |
May | 81.67 | 26.84 | 508.00 | 24.90 | 81.67 | 25.14 |
June | 82.00 | 26.84 | 496.00 | 24.88 | 82.00 | 25.12 |
July | 116.67 | 26.89 | 497.00 | 25.12 | 116.67 | 25.40 |
August | 96.83 | 26.92 | 514.00 | 24.94 | 96.83 | 25.21 |
September | 76.67 | 26.87 | 485.00 | 24.92 | 76.67 | 25.16 |
October | 88.67 | 26.88 | 502.00 | 25.00 | 88.67 | 25.24 |
November | 64.33 | 26.89 | 482.17 | 24.92 | 64.33 | 25.13 |
December | 71.17 | 26.83 | 463.17 | 24.97 | 69.50 | 25.20 |
Annual Sum or Average | 927.33 | 26.72 | 5697.83 | 24.91 | 882.17 | 25.14 |
Minimum of Months | 47.33 | 24.98 | 400.50 | 24.56 | 21.33 | 24.65 |
Maximum of Months | 116.67 | 26.92 | 514.00 | 25.12 | 116.67 | 25.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 270.50 | 22.76 | 188.83 | 23.30 | 22.33 | 23.33 |
February | 161.50 | 22.93 | 267.00 | 23.62 | 33.33 | 23.63 |
March | 175.17 | 23.37 | 344.17 | 23.94 | 43.33 | 24.02 |
April | 45.00 | 25.11 | 451.00 | 24.37 | 35.17 | 24.45 |
May | 77.67 | 26.03 | 508.00 | 24.65 | 77.67 | 24.81 |
June | 60.00 | 26.36 | 496.00 | 24.65 | 60.00 | 24.82 |
July | 64.83 | 26.49 | 497.00 | 24.77 | 64.83 | 24.95 |
August | 60.33 | 26.12 | 514.00 | 24.58 | 60.33 | 24.72 |
September | 66.00 | 26.16 | 485.00 | 24.67 | 66.00 | 24.83 |
October | 74.50 | 25.83 | 502.00 | 24.62 | 74.50 | 24.76 |
November | 102.00 | 24.25 | 406.33 | 24.27 | 50.50 | 24.38 |
December | 259.83 | 23.09 | 249.17 | 23.64 | 62.83 | 23.75 |
Annual Sum or Average | 1417.33 | 24.06 | 4908.50 | 24.29 | 650.83 | 24.42 |
Minimum of Months | 45.00 | 22.76 | 188.83 | 23.30 | 22.33 | 23.33 |
Maximum of Months | 270.50 | 26.49 | 514.00 | 24.77 | 77.67 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 144.67 | 23.45 | 248.83 | 24.07 | 29.00 | 24.19 |
February | 91.33 | 23.71 | 276.67 | 24.18 | 34.00 | 24.24 |
March | 87.67 | 24.35 | 338.33 | 24.39 | 43.17 | 24.52 |
April | 62.33 | 26.31 | 395.50 | 24.79 | 58.33 | 24.99 |
May | 81.50 | 26.39 | 430.00 | 24.88 | 81.50 | 25.09 |
June | 61.50 | 26.69 | 418.00 | 24.86 | 61.50 | 25.07 |
July | 72.50 | 26.90 | 422.00 | 25.06 | 72.50 | 25.30 |
August | 61.33 | 26.50 | 433.00 | 24.78 | 61.33 | 24.97 |
September | 72.83 | 26.66 | 410.00 | 24.97 | 72.83 | 25.19 |
October | 86.83 | 26.40 | 427.00 | 24.95 | 86.83 | 25.16 |
November | 65.00 | 25.34 | 377.00 | 24.60 | 50.67 | 24.75 |
December | 188.83 | 23.64 | 245.33 | 24.10 | 64.17 | 24.26 |
Annual Sum or Average | 1076.33 | 25.13 | 4421.67 | 24.67 | 715.83 | 24.85 |
Minimum of Months | 61.33 | 23.45 | 245.33 | 24.07 | 29.00 | 24.19 |
Maximum of Months | 188.83 | 26.90 | 433.00 | 25.06 | 86.83 | 25.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 124.50 | 24.48 | 384.50 | 24.57 | 52.83 | 24.74 |
February | 80.67 | 24.57 | 375.50 | 24.52 | 44.50 | 24.65 |
March | 96.00 | 24.40 | 415.17 | 24.38 | 45.83 | 24.51 |
April | 50.17 | 25.92 | 461.83 | 24.55 | 46.17 | 24.68 |
May | 77.83 | 25.97 | 508.00 | 24.63 | 77.83 | 24.79 |
June | 58.33 | 26.16 | 496.00 | 24.59 | 58.33 | 24.74 |
July | 62.50 | 26.36 | 497.00 | 24.73 | 62.50 | 24.89 |
August | 58.83 | 26.23 | 514.00 | 24.60 | 58.83 | 24.75 |
September | 72.00 | 26.58 | 485.00 | 24.83 | 72.00 | 25.03 |
October | 87.83 | 26.64 | 502.00 | 24.99 | 87.83 | 25.20 |
November | 86.67 | 26.00 | 466.50 | 24.88 | 76.33 | 25.06 |
December | 133.33 | 24.85 | 391.83 | 24.67 | 77.17 | 24.87 |
Annual Sum or Average | 988.67 | 25.52 | 5497.33 | 24.67 | 760.17 | 24.84 |
Minimum of Months | 50.17 | 24.40 | 375.50 | 24.38 | 44.50 | 24.51 |
Maximum of Months | 133.33 | 26.64 | 514.00 | 24.99 | 87.83 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 166.67 | 23.24 | 298.17 | 23.92 | 23.00 | 23.97 |
February | 100.67 | 23.68 | 343.50 | 24.18 | 34.00 | 24.28 |
March | 111.50 | 24.26 | 418.00 | 24.39 | 43.67 | 24.52 |
April | 56.33 | 26.48 | 478.17 | 24.72 | 54.17 | 24.89 |
May | 88.50 | 26.56 | 508.00 | 24.86 | 88.50 | 25.08 |
June | 72.33 | 26.72 | 496.00 | 24.80 | 72.33 | 25.02 |
July | 90.33 | 26.79 | 497.00 | 24.98 | 90.33 | 25.22 |
August | 69.33 | 26.74 | 514.00 | 24.78 | 69.33 | 24.99 |
September | 78.33 | 26.71 | 485.00 | 24.88 | 78.33 | 25.11 |
October | 86.67 | 26.56 | 502.00 | 24.89 | 86.67 | 25.11 |
November | 75.00 | 25.24 | 445.00 | 24.54 | 53.50 | 24.69 |
December | 173.33 | 23.93 | 331.67 | 24.27 | 64.17 | 24.44 |
Annual Sum or Average | 1169.00 | 25.19 | 5316.50 | 24.63 | 758.00 | 24.82 |
Minimum of Months | 56.33 | 23.24 | 298.17 | 23.92 | 23.00 | 23.97 |
Maximum of Months | 173.33 | 26.79 | 514.00 | 24.98 | 90.33 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 311.50 | 22.45 | 186.17 | 22.96 | 42.17 | 22.96 |
February | 192.17 | 22.66 | 261.00 | 23.37 | 44.17 | 23.35 |
March | 192.67 | 23.13 | 338.67 | 23.81 | 52.17 | 23.90 |
April | 65.00 | 24.79 | 432.00 | 24.38 | 43.83 | 24.47 |
May | 89.50 | 26.02 | 508.00 | 24.69 | 89.50 | 24.86 |
June | 73.17 | 26.32 | 496.00 | 24.69 | 73.17 | 24.88 |
July | 75.17 | 26.55 | 497.00 | 24.83 | 75.17 | 25.03 |
August | 68.33 | 26.10 | 514.00 | 24.60 | 68.33 | 24.76 |
September | 79.33 | 26.13 | 485.00 | 24.72 | 79.33 | 24.89 |
October | 94.17 | 25.84 | 496.67 | 24.68 | 94.17 | 24.84 |
November | 134.83 | 23.86 | 391.00 | 24.16 | 60.50 | 24.27 |
December | 289.17 | 22.78 | 248.00 | 23.39 | 74.83 | 23.49 |
Annual Sum or Average | 1665.00 | 23.88 | 4853.50 | 24.23 | 797.33 | 24.36 |
Minimum of Months | 65.00 | 22.45 | 186.17 | 22.96 | 42.17 | 22.96 |
Maximum of Months | 311.50 | 26.55 | 514.00 | 24.83 | 94.17 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 193.67 | 23.12 | 281.50 | 23.78 | 42.00 | 23.87 |
February | 121.00 | 23.21 | 315.50 | 23.92 | 39.33 | 23.95 |
March | 107.67 | 24.02 | 395.17 | 24.25 | 48.33 | 24.35 |
April | 70.67 | 26.06 | 462.50 | 24.66 | 64.50 | 24.85 |
May | 92.00 | 26.30 | 508.00 | 24.78 | 92.00 | 24.98 |
June | 74.33 | 26.57 | 496.00 | 24.77 | 74.33 | 24.98 |
July | 79.00 | 26.90 | 497.00 | 24.95 | 79.00 | 25.19 |
August | 69.17 | 26.41 | 514.00 | 24.69 | 69.17 | 24.87 |
September | 83.17 | 26.54 | 485.00 | 24.86 | 83.17 | 25.07 |
October | 94.00 | 26.28 | 501.67 | 24.82 | 94.00 | 25.02 |
November | 98.17 | 24.71 | 430.00 | 24.44 | 61.00 | 24.58 |
December | 232.50 | 23.28 | 281.17 | 23.86 | 72.50 | 23.99 |
Annual Sum or Average | 1315.33 | 24.77 | 5167.50 | 24.51 | 819.33 | 24.69 |
Minimum of Months | 69.17 | 23.12 | 281.17 | 23.78 | 39.33 | 23.87 |
Maximum of Months | 232.50 | 26.90 | 514.00 | 24.95 | 94.00 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 150.67 | 23.83 | 360.83 | 24.28 | 53.83 | 24.44 |
February | 103.00 | 23.94 | 358.67 | 24.28 | 51.33 | 24.37 |
March | 115.33 | 24.00 | 401.17 | 24.26 | 52.50 | 24.37 |
April | 65.50 | 25.62 | 448.83 | 24.55 | 55.50 | 24.70 |
May | 90.00 | 25.97 | 508.00 | 24.67 | 90.00 | 24.84 |
June | 72.00 | 26.16 | 496.00 | 24.65 | 72.00 | 24.82 |
July | 72.33 | 26.43 | 497.00 | 24.79 | 72.33 | 24.97 |
August | 68.17 | 26.19 | 514.00 | 24.63 | 68.17 | 24.79 |
September | 83.67 | 26.49 | 485.00 | 24.85 | 83.67 | 25.06 |
October | 96.67 | 26.51 | 501.33 | 24.95 | 96.67 | 25.17 |
November | 96.17 | 25.45 | 449.00 | 24.73 | 73.50 | 24.92 |
December | 172.50 | 24.21 | 358.67 | 24.43 | 79.00 | 24.64 |
Annual Sum or Average | 1186.00 | 25.14 | 5378.50 | 24.60 | 848.50 | 24.78 |
Minimum of Months | 65.50 | 23.83 | 358.67 | 24.26 | 51.33 | 24.37 |
Maximum of Months | 172.50 | 26.51 | 514.00 | 24.95 | 96.67 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 208.67 | 22.87 | 269.83 | 23.63 | 36.00 | 23.67 |
February | 128.83 | 23.33 | 330.67 | 23.96 | 47.67 | 24.01 |
March | 123.17 | 23.90 | 407.67 | 24.27 | 50.00 | 24.40 |
April | 61.83 | 26.36 | 468.67 | 24.71 | 58.83 | 24.89 |
May | 94.67 | 26.52 | 508.00 | 24.87 | 94.67 | 25.09 |
June | 79.33 | 26.66 | 496.00 | 24.82 | 79.33 | 25.04 |
July | 94.67 | 26.81 | 497.00 | 25.00 | 94.67 | 25.25 |
August | 74.33 | 26.70 | 514.00 | 24.79 | 74.33 | 25.00 |
September | 86.83 | 26.63 | 485.00 | 24.90 | 86.83 | 25.13 |
October | 96.00 | 26.44 | 501.67 | 24.89 | 96.00 | 25.11 |
November | 99.67 | 24.67 | 431.50 | 24.46 | 59.50 | 24.61 |
December | 215.00 | 23.53 | 308.00 | 24.06 | 70.50 | 24.22 |
Annual Sum or Average | 1363.00 | 24.85 | 5218.00 | 24.56 | 848.33 | 24.75 |
Minimum of Months | 61.83 | 22.87 | 269.83 | 23.63 | 36.00 | 23.67 |
Maximum of Months | 215.00 | 26.81 | 514.00 | 25.00 | 96.00 | 25.25 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.83 | 27.00 | 502.00 | 27.00 | 7.83 | 27.00 |
February | 28.33 | 27.00 | 454.00 | 27.00 | 28.33 | 27.00 |
March | 134.00 | 27.00 | 514.00 | 27.00 | 134.00 | 27.00 |
April | 358.33 | 27.01 | 485.00 | 27.01 | 358.33 | 27.01 |
May | 51.33 | 27.00 | 508.00 | 27.00 | 51.33 | 27.00 |
June | 139.83 | 27.00 | 496.00 | 27.00 | 139.83 | 27.00 |
July | 345.33 | 27.00 | 497.00 | 27.00 | 345.33 | 27.00 |
August | 499.00 | 27.17 | 514.00 | 27.17 | 499.00 | 27.17 |
September | 75.00 | 27.00 | 485.00 | 27.00 | 75.00 | 27.00 |
October | 133.67 | 27.00 | 502.00 | 27.00 | 133.67 | 27.00 |
November | 183.33 | 27.00 | 489.00 | 27.00 | 183.33 | 27.00 |
December | 227.67 | 27.00 | 497.00 | 27.00 | 227.67 | 27.00 |
Annual Sum or Average | 2183.67 | 27.04 | 5943.00 | 27.02 | 2183.67 | 27.03 |
Minimum of Months | 7.83 | 27.00 | 454.00 | 27.00 | 7.83 | 27.00 |
Maximum of Months | 499.00 | 27.17 | 514.00 | 27.17 | 499.00 | 27.17 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 2.67 | 27.00 | 454.00 | 27.00 | 2.67 | 27.00 |
March | 1.00 | 27.00 | 514.00 | 27.00 | 1.00 | 27.00 |
April | 36.00 | 27.03 | 485.00 | 27.01 | 36.00 | 27.01 |
May | 3.33 | 27.00 | 508.00 | 27.00 | 3.33 | 27.00 |
June | 4.17 | 27.00 | 496.00 | 27.00 | 4.17 | 27.00 |
July | 22.17 | 27.00 | 497.00 | 27.00 | 22.17 | 27.00 |
August | 144.00 | 27.40 | 514.00 | 27.18 | 144.00 | 27.22 |
September | 8.50 | 27.00 | 485.00 | 27.00 | 8.50 | 27.00 |
October | 12.50 | 27.00 | 502.00 | 27.00 | 12.50 | 27.00 |
November | 5.83 | 27.00 | 489.00 | 27.00 | 5.83 | 27.00 |
December | 13.00 | 27.00 | 497.00 | 27.00 | 13.00 | 27.00 |
Annual Sum or Average | 253.17 | 27.23 | 5943.00 | 27.02 | 253.17 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 144.00 | 27.40 | 514.00 | 27.18 | 144.00 | 27.22 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 500.00 | 27.00 | 0.00 | 27.00 |
February | 5.67 | 27.00 | 446.33 | 27.00 | 5.67 | 27.00 |
March | 24.50 | 27.00 | 514.00 | 27.00 | 24.50 | 27.00 |
April | 86.00 | 27.02 | 485.00 | 27.00 | 86.00 | 27.01 |
May | 57.50 | 27.00 | 508.00 | 27.00 | 57.50 | 27.00 |
June | 57.17 | 27.00 | 496.00 | 27.00 | 57.17 | 27.00 |
July | 127.67 | 27.00 | 497.00 | 27.00 | 127.67 | 27.00 |
August | 161.33 | 27.23 | 514.00 | 27.11 | 161.33 | 27.14 |
September | 60.00 | 27.00 | 485.00 | 27.00 | 60.00 | 27.00 |
October | 46.50 | 27.00 | 502.00 | 27.00 | 46.50 | 27.00 |
November | 30.67 | 27.00 | 489.00 | 27.00 | 30.67 | 27.00 |
December | 23.00 | 27.00 | 497.00 | 27.00 | 23.00 | 27.00 |
Annual Sum or Average | 680.00 | 27.06 | 5933.33 | 27.01 | 680.00 | 27.02 |
Minimum of Months | 0.00 | 0.00 | 446.33 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 161.33 | 27.23 | 514.00 | 27.11 | 161.33 | 27.14 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.46 | 485.00 | 27.46 | 485.00 | 27.46 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 28.96 | 514.00 | 28.96 | 514.00 | 28.96 |
September | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.18 | 497.00 | 27.18 | 497.00 | 27.18 |
Annual Sum or Average | 5943.00 | 27.22 | 5943.00 | 27.22 | 5943.00 | 27.22 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 28.96 | 514.00 | 28.96 | 514.00 | 28.96 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00052 | 37.46428 | 0.94638 | 23.99427 |
February | 454.00000 | 27.00135 | 36.27749 | 0.97966 | 25.35514 |
March | 514.00000 | 27.00092 | 36.42063 | 1.01657 | 26.87741 |
April | 485.00000 | 27.00674 | 38.01530 | 1.07390 | 29.35660 |
May | 508.00000 | 27.00018 | 43.40199 | 0.36430 | 7.79799 |
June | 496.00000 | 27.00303 | 41.62257 | 0.39555 | 8.28921 |
July | 497.00000 | 27.00153 | 40.48722 | 0.44340 | 9.13829 |
August | 514.00000 | 27.16956 | 39.60908 | 0.53186 | 11.11667 |
September | 485.00000 | 27.00000 | 44.78872 | 0.37922 | 8.02864 |
October | 502.00000 | 27.00260 | 40.84658 | 1.03743 | 27.74098 |
November | 489.00000 | 27.00132 | 38.28206 | 1.03934 | 27.83016 |
December | 497.00000 | 27.00048 | 36.54643 | 1.04269 | 27.99331 |
Annual Sum or Average | 5943.00000 | 27.01621 | 39.49519 | 0.76887 | 19.39750 |
Minimum of Months | 454.00000 | 27.00000 | 36.27749 | 0.36430 | 7.79799 |
Maximum of Months | 514.00000 | 27.16956 | 44.78872 | 1.07390 | 29.35660 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00029 | 37.74212 | 0.89158 | 21.89217 |
February | 454.00000 | 27.00128 | 36.34520 | 0.90813 | 22.54334 |
March | 514.00000 | 27.00091 | 36.41775 | 0.94024 | 23.75674 |
April | 485.00000 | 27.00300 | 37.98986 | 0.98957 | 25.71022 |
May | 508.00000 | 27.00007 | 43.68290 | 0.31978 | 7.16338 |
June | 496.00000 | 27.00292 | 41.74405 | 0.32751 | 7.26084 |
July | 497.00000 | 27.00159 | 40.53461 | 0.34956 | 7.57754 |
August | 514.00000 | 27.12307 | 39.66726 | 0.38905 | 8.30073 |
September | 485.00000 | 27.00000 | 45.16031 | 0.33133 | 7.31712 |
October | 502.00000 | 27.00252 | 40.95660 | 0.98716 | 25.60365 |
November | 489.00000 | 27.00130 | 38.30615 | 0.96238 | 24.61416 |
December | 497.00000 | 27.00028 | 36.52000 | 0.93650 | 23.59759 |
Annual Sum or Average | 5943.00000 | 27.01182 | 39.60404 | 0.69224 | 17.05269 |
Minimum of Months | 454.00000 | 27.00000 | 36.34520 | 0.31978 | 7.16338 |
Maximum of Months | 514.00000 | 27.12307 | 45.16031 | 0.98957 | 25.71022 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00025 | 37.93068 | 0.87048 | 21.18523 |
February | 454.00000 | 27.00131 | 36.39133 | 0.89725 | 22.22665 |
March | 514.00000 | 27.00094 | 36.45532 | 0.93631 | 23.66931 |
April | 485.00000 | 27.00302 | 38.03034 | 0.99658 | 26.03471 |
May | 508.00000 | 27.00014 | 43.61250 | 0.33742 | 7.45116 |
June | 496.00000 | 27.00303 | 41.73833 | 0.34778 | 7.58562 |
July | 497.00000 | 27.00163 | 40.55346 | 0.37494 | 8.01660 |
August | 514.00000 | 27.07418 | 39.73765 | 0.39487 | 8.44383 |
September | 485.00000 | 27.00001 | 45.08904 | 0.34752 | 7.59190 |
October | 502.00000 | 27.00257 | 40.98621 | 0.99397 | 25.90887 |
November | 489.00000 | 27.00135 | 38.35485 | 0.95759 | 24.47541 |
December | 497.00000 | 27.00034 | 36.57523 | 0.91983 | 23.01955 |
Annual Sum or Average | 5943.00000 | 27.00762 | 39.63652 | 0.69579 | 17.07694 |
Minimum of Months | 454.00000 | 27.00001 | 36.39133 | 0.33742 | 7.45116 |
Maximum of Months | 514.00000 | 27.07418 | 45.08904 | 0.99658 | 26.03471 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00231 | 36.95259 | 1.15802 | 33.24031 |
February | 454.00000 | 27.00208 | 36.63129 | 1.29985 | 40.27591 |
March | 514.00000 | 27.00137 | 36.91540 | 1.43404 | 47.33864 |
April | 485.00000 | 27.45507 | 37.97754 | 1.66599 | 59.81177 |
May | 508.00000 | 27.00473 | 40.72169 | 0.60406 | 12.68171 |
June | 496.00000 | 27.00374 | 40.14281 | 0.80727 | 18.75229 |
July | 497.00000 | 27.00156 | 39.84047 | 1.01443 | 26.74230 |
August | 514.00000 | 28.96425 | 38.20614 | 1.77719 | 65.44096 |
September | 485.00000 | 27.00556 | 41.49094 | 0.64612 | 13.81178 |
October | 502.00000 | 27.00316 | 39.68246 | 1.34452 | 42.58283 |
November | 489.00000 | 27.00135 | 38.15375 | 1.46834 | 49.18570 |
December | 497.00000 | 27.17841 | 36.93441 | 1.61737 | 57.26157 |
Annual Sum or Average | 5943.00000 | 27.22409 | 38.64510 | 1.23703 | 38.96513 |
Minimum of Months | 454.00000 | 27.00135 | 36.63129 | 0.60406 | 12.68171 |
Maximum of Months | 514.00000 | 28.96425 | 41.49094 | 1.77719 | 65.44096 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.58805 | 53.02168 | 0.61928 | 14.04034 |
February | 454.00000 | 24.56171 | 53.48019 | 0.61376 | 13.76148 |
March | 514.00000 | 24.44830 | 55.20755 | 0.59940 | 13.28509 |
April | 485.00000 | 24.54184 | 60.88982 | 0.65989 | 14.91105 |
May | 508.00000 | 24.51744 | 64.13578 | -0.1705 | 6.96504 |
June | 496.00000 | 24.47339 | 63.95876 | -0.1827 | 6.89277 |
July | 497.00000 | 24.62968 | 62.38234 | -0.1384 | 7.06125 |
August | 514.00000 | 24.49013 | 61.88620 | -0.1711 | 6.98052 |
September | 485.00000 | 24.56909 | 62.75544 | -0.1515 | 7.08676 |
October | 502.00000 | 24.62187 | 61.54453 | 0.69463 | 16.10895 |
November | 489.00000 | 24.62864 | 59.31435 | 0.68065 | 15.58240 |
December | 497.00000 | 24.62096 | 55.06725 | 0.64564 | 14.79872 |
Annual Sum or Average | 5943.00000 | 24.55699 | 59.50329 | 0.30502 | 11.42678 |
Minimum of Months | 454.00000 | 24.44830 | 53.02168 | -0.1827 | 6.89277 |
Maximum of Months | 514.00000 | 24.62968 | 64.13578 | 0.69463 | 16.10895 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36744 | 50.27281 | 0.54904 | 11.73841 |
February | 454.00000 | 24.35458 | 50.46507 | 0.55555 | 11.87095 |
March | 514.00000 | 24.23762 | 51.45863 | 0.54399 | 11.43432 |
April | 485.00000 | 24.22747 | 55.59665 | 0.58003 | 12.16445 |
May | 508.00000 | 24.23968 | 57.26778 | -0.2803 | 6.90708 |
June | 496.00000 | 24.19228 | 57.13206 | -0.2846 | 6.85634 |
July | 497.00000 | 24.24674 | 56.46604 | -0.2607 | 6.64413 |
August | 514.00000 | 24.21506 | 55.95262 | -0.2609 | 6.64631 |
September | 485.00000 | 24.25629 | 56.08724 | -0.2764 | 6.89078 |
October | 502.00000 | 24.27913 | 55.14357 | 0.58591 | 12.37347 |
November | 489.00000 | 24.34601 | 54.08839 | 0.59393 | 12.65350 |
December | 497.00000 | 24.32489 | 51.58715 | 0.56681 | 12.01362 |
Annual Sum or Average | 5943.00000 | 24.27314 | 54.31389 | 0.21432 | 9.82649 |
Minimum of Months | 454.00000 | 24.19228 | 50.27281 | -0.2846 | 6.64413 |
Maximum of Months | 514.00000 | 24.36744 | 57.26778 | 0.59393 | 12.65350 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18458 | 51.23281 | 0.48300 | 10.17332 |
February | 454.00000 | 24.18238 | 51.53964 | 0.48802 | 10.41823 |
March | 514.00000 | 24.21017 | 52.24224 | 0.50762 | 10.69286 |
April | 485.00000 | 24.23594 | 56.75709 | 0.55265 | 11.56761 |
May | 508.00000 | 24.22029 | 57.62484 | -0.3110 | 7.26155 |
June | 496.00000 | 24.18983 | 57.62038 | -0.3167 | 7.30391 |
July | 497.00000 | 24.18843 | 57.46434 | -0.3188 | 7.28905 |
August | 514.00000 | 24.18155 | 57.42265 | -0.3217 | 7.35031 |
September | 485.00000 | 24.22211 | 56.42304 | -0.3155 | 7.34478 |
October | 502.00000 | 24.27013 | 55.52192 | 0.56037 | 11.78406 |
November | 489.00000 | 24.32573 | 55.18908 | 0.56146 | 11.86926 |
December | 497.00000 | 24.18351 | 52.75925 | 0.49583 | 10.40173 |
Annual Sum or Average | 5943.00000 | 24.21618 | 55.16939 | 0.16883 | 9.44088 |
Minimum of Months | 454.00000 | 24.18155 | 51.23281 | -0.3217 | 7.26155 |
Maximum of Months | 514.00000 | 24.32573 | 57.62484 | 0.56146 | 11.86926 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.89163 | 52.78681 | 0.40638 | 9.05048 |
February | 454.00000 | 23.99895 | 52.44479 | 0.44366 | 10.12552 |
March | 514.00000 | 24.14238 | 52.84164 | 0.49334 | 10.62332 |
April | 485.00000 | 24.25932 | 56.75499 | 0.56649 | 11.92896 |
May | 508.00000 | 24.28310 | 57.33946 | -0.2720 | 6.92102 |
June | 496.00000 | 24.25078 | 57.30198 | -0.2757 | 6.93120 |
July | 497.00000 | 24.29478 | 56.95238 | -0.2606 | 6.80593 |
August | 514.00000 | 24.22378 | 57.34398 | -0.2883 | 7.01961 |
September | 485.00000 | 24.29115 | 56.48245 | -0.2742 | 6.97091 |
October | 502.00000 | 24.32647 | 55.94059 | 0.58230 | 12.34954 |
November | 489.00000 | 24.23947 | 56.19444 | 0.54441 | 11.49618 |
December | 497.00000 | 23.97945 | 54.10575 | 0.44298 | 9.72020 |
Annual Sum or Average | 5943.00000 | 24.18270 | 55.55643 | 0.17277 | 9.14750 |
Minimum of Months | 454.00000 | 23.89163 | 52.44479 | -0.2883 | 6.80593 |
Maximum of Months | 514.00000 | 24.32647 | 57.34398 | 0.58230 | 12.34954 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.97102 | 51.05380 | 0.42040 | 9.51051 |
February | 454.00000 | 24.08676 | 50.84769 | 0.47298 | 10.53827 |
March | 514.00000 | 24.14001 | 51.58764 | 0.50473 | 11.03167 |
April | 485.00000 | 24.29540 | 55.02309 | 0.60118 | 12.92965 |
May | 508.00000 | 24.42054 | 56.79379 | -0.1666 | 6.55022 |
June | 496.00000 | 24.40091 | 56.22549 | -0.1439 | 6.33153 |
July | 497.00000 | 24.52239 | 55.26381 | -0.0968 | 6.47258 |
August | 514.00000 | 24.37553 | 55.25739 | -0.1544 | 6.44212 |
September | 485.00000 | 24.44671 | 55.28839 | -0.1659 | 6.58988 |
October | 502.00000 | 24.41577 | 54.73679 | 0.62989 | 13.82946 |
November | 489.00000 | 24.29048 | 53.86624 | 0.57250 | 12.20176 |
December | 497.00000 | 24.12179 | 52.32169 | 0.48684 | 10.64646 |
Annual Sum or Average | 5943.00000 | 24.29163 | 54.04018 | 0.24414 | 9.40473 |
Minimum of Months | 454.00000 | 23.97102 | 50.84769 | -0.1666 | 6.33153 |
Maximum of Months | 514.00000 | 24.52239 | 56.79379 | 0.62989 | 13.82946 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18112 | 49.86142 | 0.49932 | 11.29422 |
February | 454.00000 | 24.24062 | 50.13974 | 0.54128 | 11.98843 |
March | 514.00000 | 24.20259 | 50.96404 | 0.56140 | 12.30782 |
April | 485.00000 | 24.35866 | 54.55895 | 0.65786 | 14.77472 |
May | 508.00000 | 24.46002 | 56.37070 | -0.0973 | 6.47237 |
June | 496.00000 | 24.41855 | 55.94976 | -0.0936 | 6.35718 |
July | 497.00000 | 24.55254 | 54.92075 | -0.0409 | 6.85364 |
August | 514.00000 | 24.36815 | 55.13121 | -0.1245 | 6.47796 |
September | 485.00000 | 24.51392 | 54.65968 | -0.0862 | 6.64704 |
October | 502.00000 | 24.47146 | 54.14628 | 0.67832 | 15.35467 |
November | 489.00000 | 24.34003 | 53.45976 | 0.60614 | 13.13736 |
December | 497.00000 | 24.09637 | 52.19462 | 0.49303 | 10.96837 |
Annual Sum or Average | 5943.00000 | 24.35057 | 53.54953 | 0.29683 | 10.19498 |
Minimum of Months | 454.00000 | 24.09637 | 49.86142 | -0.1245 | 6.35718 |
Maximum of Months | 514.00000 | 24.55254 | 56.37070 | 0.67832 | 15.35467 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.42137 | 48.72720 | 0.60914 | 14.12952 |
February | 454.00000 | 24.43891 | 49.26959 | 0.62901 | 14.51393 |
March | 514.00000 | 24.28474 | 50.60940 | 0.59439 | 13.23387 |
April | 485.00000 | 24.36471 | 54.62860 | 0.64098 | 14.16821 |
May | 508.00000 | 24.41304 | 56.82827 | -0.1705 | 6.58946 |
June | 496.00000 | 24.37499 | 56.38314 | -0.1657 | 6.39810 |
July | 497.00000 | 24.49765 | 55.38333 | -0.1127 | 6.48437 |
August | 514.00000 | 24.38811 | 55.13349 | -0.1350 | 6.40331 |
September | 485.00000 | 24.52851 | 54.68738 | -0.0860 | 6.64341 |
October | 502.00000 | 24.61021 | 53.52292 | 0.74099 | 17.43191 |
November | 489.00000 | 24.59546 | 52.27099 | 0.71814 | 16.70977 |
December | 497.00000 | 24.46068 | 50.33319 | 0.64836 | 15.13221 |
Annual Sum or Average | 5943.00000 | 24.44749 | 53.17255 | 0.32260 | 11.45141 |
Minimum of Months | 454.00000 | 24.28474 | 48.72720 | -0.1705 | 6.39810 |
Maximum of Months | 514.00000 | 24.61021 | 56.82827 | 0.74099 | 17.43191 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.39851 | 49.03747 | 0.57560 | 12.79586 |
February | 454.00000 | 24.52471 | 48.89959 | 0.66028 | 15.29923 |
March | 514.00000 | 24.52490 | 49.63750 | 0.71271 | 16.76395 |
April | 485.00000 | 24.63607 | 53.34201 | 0.82183 | 20.22773 |
May | 508.00000 | 24.59268 | 55.72931 | 0.00195 | 6.77610 |
June | 496.00000 | 24.55090 | 55.28852 | 0.01823 | 6.64532 |
July | 497.00000 | 24.70062 | 54.22368 | 0.10979 | 7.44228 |
August | 514.00000 | 24.57127 | 53.97702 | 0.10472 | 7.11671 |
September | 485.00000 | 24.61379 | 54.24819 | -0.0078 | 6.89104 |
October | 502.00000 | 24.66273 | 53.23653 | 0.77963 | 18.79339 |
November | 489.00000 | 24.64734 | 51.99801 | 0.75236 | 17.77173 |
December | 497.00000 | 24.64165 | 49.61947 | 0.71799 | 17.06205 |
Annual Sum or Average | 5943.00000 | 24.58869 | 52.45696 | 0.43486 | 12.76094 |
Minimum of Months | 454.00000 | 24.39851 | 48.89959 | -0.0078 | 6.64532 |
Maximum of Months | 514.00000 | 24.70062 | 55.72931 | 0.82183 | 20.22773 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.32538 | 53.31614 | 0.25689 | 7.96180 |
February | 454.00000 | 23.63167 | 53.12308 | 0.34876 | 9.28947 |
March | 514.00000 | 23.83602 | 53.95696 | 0.41834 | 10.26355 |
April | 485.00000 | 24.25708 | 56.95810 | 0.57183 | 12.26019 |
May | 508.00000 | 24.43666 | 58.50876 | -0.1671 | 6.73664 |
June | 496.00000 | 24.44264 | 57.79928 | -0.1398 | 6.56388 |
July | 497.00000 | 24.55096 | 56.90143 | -0.1059 | 6.63574 |
August | 514.00000 | 24.39407 | 57.87931 | -0.1755 | 6.67902 |
September | 485.00000 | 24.47009 | 56.72571 | -0.1680 | 6.80214 |
October | 502.00000 | 24.43797 | 56.82959 | 0.62839 | 13.93914 |
November | 489.00000 | 24.12271 | 56.53967 | 0.51970 | 11.56311 |
December | 497.00000 | 23.52315 | 56.11440 | 0.33194 | 8.98933 |
Annual Sum or Average | 5943.00000 | 24.12168 | 56.24082 | 0.19110 | 8.96236 |
Minimum of Months | 454.00000 | 23.32538 | 53.12308 | -0.1755 | 6.56388 |
Maximum of Months | 514.00000 | 24.55096 | 58.50876 | 0.62839 | 13.93914 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.92455 | 50.78395 | 0.41958 | 10.41435 |
February | 385.00000 | 24.08464 | 51.22393 | 0.48492 | 11.33576 |
March | 433.00000 | 24.21343 | 52.34377 | 0.54968 | 12.64508 |
April | 410.00000 | 24.52670 | 55.52417 | 0.68445 | 15.83154 |
May | 430.00000 | 24.59767 | 57.76675 | -0.0597 | 6.87259 |
June | 418.00000 | 24.58847 | 57.09439 | -0.0441 | 6.85053 |
July | 422.00000 | 24.74806 | 55.87829 | 0.01331 | 7.49859 |
August | 433.00000 | 24.54177 | 57.12845 | -0.0769 | 6.80743 |
September | 410.00000 | 24.67076 | 55.80301 | -0.0440 | 7.15821 |
October | 427.00000 | 24.65361 | 55.97814 | 0.71868 | 16.93469 |
November | 417.00000 | 24.39183 | 55.43240 | 0.61129 | 13.86721 |
December | 422.00000 | 23.89662 | 54.72439 | 0.43608 | 10.87710 |
Annual Sum or Average | 5034.00000 | 24.40442 | 54.99584 | 0.30601 | 10.57746 |
Minimum of Months | 385.00000 | 23.89662 | 50.78395 | -0.0769 | 6.80743 |
Maximum of Months | 433.00000 | 24.74806 | 57.76675 | 0.71868 | 16.93469 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32929 | 49.16104 | 0.58167 | 13.85699 |
February | 454.00000 | 24.32973 | 50.14479 | 0.59398 | 14.00550 |
March | 514.00000 | 24.21465 | 52.05546 | 0.56671 | 12.98459 |
April | 485.00000 | 24.37439 | 56.23893 | 0.62626 | 13.84546 |
May | 508.00000 | 24.42643 | 58.57334 | -0.1721 | 6.74883 |
June | 496.00000 | 24.40920 | 58.05701 | -0.1652 | 6.59305 |
July | 497.00000 | 24.52176 | 57.07224 | -0.1233 | 6.62025 |
August | 514.00000 | 24.41577 | 57.61874 | -0.1489 | 6.60689 |
September | 485.00000 | 24.57150 | 55.79900 | -0.0766 | 6.88105 |
October | 502.00000 | 24.70248 | 54.87038 | 0.76217 | 18.35768 |
November | 489.00000 | 24.61527 | 53.76007 | 0.71797 | 17.11161 |
December | 497.00000 | 24.35657 | 51.97033 | 0.61320 | 14.83768 |
Annual Sum or Average | 5943.00000 | 24.43874 | 54.64156 | 0.31144 | 11.50654 |
Minimum of Months | 454.00000 | 24.21465 | 49.16104 | -0.1721 | 6.59305 |
Maximum of Months | 514.00000 | 24.70248 | 58.57334 | 0.76217 | 18.35768 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.86097 | 51.24397 | 0.41010 | 9.89118 |
February | 454.00000 | 24.06262 | 51.22762 | 0.49406 | 11.83022 |
March | 514.00000 | 24.22405 | 52.10759 | 0.57070 | 13.35985 |
April | 485.00000 | 24.50211 | 55.52659 | 0.70230 | 16.29513 |
May | 508.00000 | 24.56130 | 57.56751 | -0.0497 | 6.93646 |
June | 496.00000 | 24.51910 | 57.19145 | -0.0619 | 6.75461 |
July | 497.00000 | 24.65407 | 56.14978 | -0.0019 | 7.08446 |
August | 514.00000 | 24.51323 | 56.86710 | -0.0534 | 6.76111 |
September | 485.00000 | 24.58937 | 55.78465 | -0.0637 | 7.11029 |
October | 502.00000 | 24.60577 | 55.55891 | 0.72034 | 16.98988 |
November | 489.00000 | 24.34468 | 55.08204 | 0.61484 | 14.00312 |
December | 497.00000 | 24.04800 | 53.72361 | 0.49205 | 11.81816 |
Annual Sum or Average | 5943.00000 | 24.37542 | 54.85862 | 0.31225 | 10.71431 |
Minimum of Months | 454.00000 | 23.86097 | 51.22762 | -0.0637 | 6.75461 |
Maximum of Months | 514.00000 | 24.65407 | 57.56751 | 0.72034 | 16.98988 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.02794 | 54.62095 | 0.18231 | 8.03755 |
February | 454.00000 | 23.44148 | 53.97909 | 0.30407 | 9.57383 |
March | 514.00000 | 23.71305 | 54.66547 | 0.39297 | 10.49944 |
April | 485.00000 | 24.23420 | 57.28078 | 0.57463 | 12.51993 |
May | 508.00000 | 24.45196 | 58.78673 | -0.1451 | 6.83622 |
June | 496.00000 | 24.45536 | 57.96743 | -0.1175 | 6.62913 |
July | 497.00000 | 24.57379 | 56.99972 | -0.0768 | 6.83176 |
August | 514.00000 | 24.40446 | 58.27351 | -0.1547 | 6.73479 |
September | 485.00000 | 24.48614 | 57.33565 | -0.1446 | 6.89029 |
October | 502.00000 | 24.44533 | 57.79044 | 0.64141 | 14.42103 |
November | 489.00000 | 24.01318 | 57.69539 | 0.49924 | 11.61570 |
December | 497.00000 | 23.28334 | 57.50084 | 0.27469 | 9.09237 |
Annual Sum or Average | 5943.00000 | 24.04756 | 56.92612 | 0.18393 | 9.12810 |
Minimum of Months | 454.00000 | 23.02794 | 53.97909 | -0.1547 | 6.62913 |
Maximum of Months | 514.00000 | 24.57379 | 58.78673 | 0.64141 | 14.42103 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.70557 | 52.00872 | 0.36904 | 10.00250 |
February | 454.00000 | 23.90237 | 52.04609 | 0.45094 | 11.21060 |
March | 514.00000 | 24.10476 | 52.81350 | 0.53625 | 12.53914 |
April | 485.00000 | 24.41535 | 55.96737 | 0.68080 | 15.70707 |
May | 508.00000 | 24.50649 | 57.99894 | -0.0549 | 6.80265 |
June | 496.00000 | 24.49871 | 57.29559 | -0.0381 | 6.73457 |
July | 497.00000 | 24.64319 | 56.14658 | 0.01864 | 7.43392 |
August | 514.00000 | 24.45452 | 57.47258 | -0.0719 | 6.72367 |
September | 485.00000 | 24.56802 | 56.26501 | -0.0427 | 7.04889 |
October | 502.00000 | 24.54585 | 56.51754 | 0.71467 | 16.74940 |
November | 489.00000 | 24.24292 | 56.26096 | 0.58824 | 13.48590 |
December | 497.00000 | 23.69432 | 55.78107 | 0.39033 | 10.61111 |
Annual Sum or Average | 5943.00000 | 24.27553 | 55.56968 | 0.29294 | 10.40146 |
Minimum of Months | 454.00000 | 23.69432 | 52.00872 | -0.0719 | 6.72367 |
Maximum of Months | 514.00000 | 24.64319 | 57.99894 | 0.71467 | 16.74940 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.07406 | 50.34270 | 0.51525 | 12.95434 |
February | 454.00000 | 24.14249 | 51.03321 | 0.54922 | 13.52460 |
March | 514.00000 | 24.10458 | 52.80892 | 0.54351 | 12.96564 |
April | 485.00000 | 24.34397 | 56.60482 | 0.62737 | 14.04173 |
May | 508.00000 | 24.44098 | 58.86895 | -0.1505 | 6.85325 |
June | 496.00000 | 24.42698 | 58.21766 | -0.1412 | 6.64695 |
July | 497.00000 | 24.54856 | 57.17006 | -0.0930 | 6.81209 |
August | 514.00000 | 24.42237 | 58.04061 | -0.1297 | 6.69821 |
September | 485.00000 | 24.56508 | 56.49690 | -0.0605 | 7.05737 |
October | 502.00000 | 24.64927 | 55.97120 | 0.76206 | 18.42280 |
November | 489.00000 | 24.47451 | 54.96247 | 0.69044 | 16.57445 |
December | 497.00000 | 24.13637 | 53.33800 | 0.56006 | 14.18362 |
Annual Sum or Average | 5943.00000 | 24.36140 | 55.35086 | 0.30312 | 11.36630 |
Minimum of Months | 454.00000 | 24.07406 | 50.34270 | -0.1505 | 6.64695 |
Maximum of Months | 514.00000 | 24.64927 | 58.86895 | 0.76206 | 18.42280 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.60319 | 52.41532 | 0.34619 | 9.65108 |
February | 454.00000 | 23.90098 | 52.03913 | 0.45652 | 11.82378 |
March | 514.00000 | 24.11035 | 52.78912 | 0.54739 | 13.40841 |
April | 485.00000 | 24.47573 | 55.84963 | 0.70353 | 16.44077 |
May | 508.00000 | 24.56079 | 57.88452 | -0.0339 | 7.08878 |
June | 496.00000 | 24.52124 | 57.39743 | -0.0438 | 6.86497 |
July | 497.00000 | 24.66068 | 56.31145 | 0.02049 | 7.34990 |
August | 514.00000 | 24.51252 | 57.28382 | -0.0377 | 6.89056 |
September | 485.00000 | 24.58841 | 56.44878 | -0.0469 | 7.25910 |
October | 502.00000 | 24.59473 | 56.53215 | 0.72876 | 17.30940 |
November | 489.00000 | 24.25332 | 56.15990 | 0.59842 | 13.98775 |
December | 497.00000 | 23.84602 | 54.97997 | 0.44415 | 11.62756 |
Annual Sum or Average | 5943.00000 | 24.30452 | 55.52887 | 0.30489 | 10.78718 |
Minimum of Months | 454.00000 | 23.60319 | 52.03913 | -0.0469 | 6.86497 |
Maximum of Months | 514.00000 | 24.66068 | 57.88452 | 0.72876 | 17.30940 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.134586E+12 | 203965.12 | 03-JAN-14:20 | 468.53 | 0.871556E+12 | 0.00 | 0.100614E+13 | 3.71 | 7.57 | 02-JAN-05:13 | 0.00 | 0.00 |
February | 0.145864E+12 | 205976.50 | 02-FEB-12:00 | 431.74 | 0.985542E+12 | 0.00 | 0.113141E+13 | 3.98 | 7.57 | 21-FEB-10:50 | 0.00 | 0.00 |
March | 0.172360E+12 | 208100.40 | 13-MAR-12:00 | 573.78 | 0.115402E+13 | 0.00 | 0.132638E+13 | 4.63 | 7.57 | 08-MAR-06:04 | 0.00 | 0.00 |
April | 0.196798E+12 | 212762.04 | 14-APR-16:20 | 641.59 | 0.133710E+13 | 0.00 | 0.153390E+13 | 5.42 | 7.57 | 28-APR-05:05 | 0.00 | 0.00 |
May | 0.235592E+12 | 215031.86 | 31-MAY-05:02 | 620.10 | 0.159550E+13 | 0.00 | 0.183109E+13 | 5.31 | 7.57 | 08-MAY-04:13 | 0.00 | 0.00 |
June | 0.256851E+12 | 217835.37 | 05-JUN-11:30 | 659.10 | 0.170232E+13 | 0.00 | 0.195917E+13 | 5.70 | 7.38 | 17-JUN-03:04 | 0.00 | 0.00 |
July | 0.267969E+12 | 218378.09 | 14-JUL-07:30 | 698.78 | 0.175829E+13 | 0.00 | 0.202626E+13 | 5.78 | 7.50 | 07-JUL-04:13 | 0.00 | 0.00 |
August | 0.268958E+12 | 219714.23 | 21-AUG-16:10 | 700.84 | 0.177080E+13 | 0.00 | 0.203976E+13 | 5.78 | 7.35 | 14-AUG-04:13 | 0.00 | 0.00 |
September | 0.251089E+12 | 221112.00 | 18-SEP-16:50 | 622.71 | 0.166838E+13 | 0.00 | 0.191947E+13 | 5.45 | 7.45 | 05-SEP-04:13 | 0.00 | 0.00 |
October | 0.230879E+12 | 220854.14 | 04-OCT-11:10 | 634.34 | 0.155479E+13 | 0.00 | 0.178567E+13 | 5.30 | 7.57 | 19-OCT-04:14 | 0.00 | 0.00 |
November | 0.189984E+12 | 212622.38 | 30-NOV-12:10 | 565.12 | 0.128362E+13 | 0.00 | 0.147360E+13 | 4.82 | 7.57 | 02-NOV-05:04 | 0.00 | 0.00 |
December | 0.150974E+12 | 204325.05 | 07-DEC-12:10 | 567.00 | 0.984361E+12 | 0.00 | 0.113534E+13 | 4.37 | 7.57 | 04-DEC-09:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.250191E+13 | 7183.63 | 0.166663E+14 | 0.00 | 0.191682E+14 | 5.03 | 0.00 | 0.00 | ||||
Minimum of Months | 0.134586E+12 | 203965.12 | 431.74 | 0.871556E+12 | 0.00 | 0.100614E+13 | 3.71 | 7.35 | 0.00 | 0.00 | ||
Maximum of Months | 0.268958E+12 | 221112.00 | 700.84 | 0.177080E+13 | 0.00 | 0.203976E+13 | 5.78 | 7.57 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.719095E+10 | 140820.14 | 14-JAN-06:06 | 18.73 | 0.503061E+11 | 0.00 | 0.574971E+11 | 0.17 | 7.32 | 12-JAN-16:40 | 0.00 | 0.00 |
February | 0.669283E+10 | 197424.29 | 11-FEB-06:04 | 18.09 | 0.470388E+11 | 0.00 | 0.537316E+11 | 0.18 | 7.33 | 15-FEB-15:05 | 0.00 | 0.00 |
March | 0.199463E+11 | 202457.02 | 10-MAR-06:04 | 50.11 | 0.139183E+12 | 0.00 | 0.159129E+12 | 0.47 | 7.31 | 30-MAR-13:32 | 0.00 | 0.00 |
April | 0.247965E+11 | 148773.44 | 12-APR-05:02 | 61.84 | 0.171796E+12 | 0.00 | 0.196593E+12 | 0.59 | 7.32 | 17-APR-14:05 | 0.00 | 0.00 |
May | 0.518378E+11 | 215031.86 | 31-MAY-05:02 | 126.08 | 0.354268E+12 | 0.00 | 0.406106E+12 | 1.16 | 7.38 | 25-MAY-05:02 | 0.00 | 0.00 |
June | 0.696760E+11 | 196897.63 | 22-JUN-05:02 | 165.78 | 0.466252E+12 | 0.00 | 0.535928E+12 | 1.54 | 7.16 | 02-JUN-05:02 | 0.00 | 0.00 |
July | 0.732998E+11 | 187289.99 | 24-JUL-05:03 | 169.45 | 0.486353E+12 | 0.00 | 0.559653E+12 | 1.51 | 7.16 | 06-JUL-05:03 | 0.00 | 0.00 |
August | 0.777949E+11 | 213900.83 | 28-AUG-05:03 | 180.50 | 0.517748E+12 | 0.00 | 0.595543E+12 | 1.61 | 7.15 | 14-AUG-05:02 | 0.00 | 0.00 |
September | 0.666522E+11 | 211074.99 | 20-SEP-05:02 | 155.66 | 0.446755E+12 | 0.00 | 0.513407E+12 | 1.45 | 7.26 | 05-SEP-04:17 | 0.00 | 0.00 |
October | 0.556278E+11 | 210528.63 | 03-OCT-05:02 | 134.17 | 0.377594E+12 | 0.00 | 0.433222E+12 | 1.22 | 7.39 | 17-OCT-10:05 | 0.00 | 0.00 |
November | 0.334945E+11 | 202318.70 | 22-NOV-06:04 | 82.24 | 0.229919E+12 | 0.00 | 0.263414E+12 | 0.78 | 7.50 | 09-NOV-06:03 | 0.00 | 0.00 |
December | 0.979617E+10 | 203101.05 | 11-DEC-06:03 | 25.06 | 0.681387E+11 | 0.00 | 0.779349E+11 | 0.23 | 7.54 | 04-DEC-15:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.496806E+12 | 1187.72 | 0.335535E+13 | 0.00 | 0.385216E+13 | 0.91 | 0.00 | 0.00 | ||||
Minimum of Months | 0.669283E+10 | 140820.14 | 18.09 | 0.470388E+11 | 0.00 | 0.537316E+11 | 0.17 | 7.15 | 0.00 | 0.00 | ||
Maximum of Months | 0.777949E+11 | 215031.86 | 180.50 | 0.517748E+12 | 0.00 | 0.595543E+12 | 1.61 | 7.54 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.999747E+11 | 744.00 | 43776.24 | 01-JAN-00:05 | 239529.75 | 02-JAN-15:05 | 25.67 | 21.82 | 14.16 |
February | 0.100523E+12 | 672.00 | 43776.24 | 01-FEB-00:10 | 382621.95 | 02-FEB-15:05 | 31.05 | 24.24 | 14.16 |
March | 0.114776E+12 | 744.00 | 43776.24 | 01-MAR-00:10 | 626493.35 | 31-MAR-23:45 | 35.83 | 26.06 | 14.16 |
April | 0.113468E+12 | 720.00 | 43776.24 | 01-APR-00:05 | 682932.31 | 16-APR-18:12 | 42.60 | 29.79 | 14.16 |
May | 0.117250E+12 | 744.00 | 43776.24 | 01-MAY-00:05 | 370280.27 | 31-MAY-23:15 | 32.67 | 28.31 | 14.16 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:05 | 513378.97 | 30-JUN-23:15 | 38.43 | 30.97 | 14.16 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:10 | 663072.98 | 31-JUL-24:00 | 43.23 | 32.77 | 14.16 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 694944.76 | 23-AUG-16:20 | 47.10 | 33.88 | 14.16 |
September | 0.113468E+12 | 720.00 | 43776.24 | 01-SEP-00:05 | 366874.52 | 30-SEP-23:15 | 33.94 | 29.45 | 14.16 |
October | 0.117250E+12 | 744.00 | 43776.24 | 01-OCT-00:05 | 493349.64 | 31-OCT-23:30 | 36.92 | 29.57 | 14.16 |
November | 0.112667E+12 | 720.00 | 43776.24 | 01-NOV-00:10 | 541208.85 | 03-NOV-14:05 | 38.07 | 28.06 | 14.16 |
December | 0.115206E+12 | 744.00 | 43776.24 | 01-DEC-00:05 | 672823.01 | 08-DEC-16:50 | 38.52 | 26.01 | 14.16 |
Annual Sum or Average | 0.135255E+13 | 8760.00 | 37.04 | 28.43 | 14.16 | ||||
Minimum of Months | 0.999747E+11 | 672.00 | 43776.24 | 239529.75 | 25.67 | 21.82 | 14.16 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 694944.76 | 47.10 | 33.88 | 14.16 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.129676E+11 | 411.33 | 21166.70 | 01-JAN-08:47 | 1549863.67 | 12-JAN-10:30 | 23.16 | 21.88 | 42.69 |
February | 0.140509E+11 | 388.40 | 21166.70 | 01-FEB-11:05 | 1615501.22 | 23-FEB-11:50 | 23.58 | 22.01 | 42.17 |
March | 0.231976E+11 | 528.64 | 21166.70 | 02-MAR-13:30 | 1619121.63 | 23-MAR-13:40 | 23.66 | 21.98 | 52.46 |
April | 0.300642E+11 | 592.56 | 21166.70 | 01-APR-00:55 | 1606677.52 | 21-APR-16:00 | 24.19 | 22.19 | 59.46 |
May | 0.454115E+11 | 616.21 | 21166.70 | 01-MAY-04:13 | 1445557.01 | 08-MAY-07:30 | 26.38 | 24.10 | 53.07 |
June | 0.502233E+11 | 659.10 | 21166.70 | 01-JUN-00:25 | 1295717.72 | 05-JUN-14:40 | 27.97 | 25.43 | 54.11 |
July | 0.528143E+11 | 698.78 | 21166.70 | 01-JUL-00:10 | 1259480.93 | 20-JUL-12:05 | 28.12 | 25.57 | 56.08 |
August | 0.534040E+11 | 700.84 | 21166.70 | 01-AUG-00:05 | 1371338.79 | 28-AUG-05:03 | 28.22 | 25.66 | 55.21 |
September | 0.474507E+11 | 622.71 | 21166.70 | 01-SEP-00:05 | 1405854.17 | 26-SEP-05:04 | 28.02 | 25.53 | 50.73 |
October | 0.447421E+11 | 632.01 | 21166.70 | 01-OCT-00:05 | 1642352.24 | 17-OCT-08:40 | 26.54 | 24.29 | 53.62 |
November | 0.326037E+11 | 541.27 | 21166.70 | 01-NOV-04:12 | 1625879.28 | 01-NOV-04:15 | 24.99 | 23.07 | 50.38 |
December | 0.193842E+11 | 505.92 | 21166.70 | 01-DEC-06:05 | 1633586.33 | 11-DEC-15:40 | 23.39 | 21.94 | 51.21 |
Annual Sum or Average | 0.426314E+12 | 6897.76 | 25.69 | 23.65 | 51.82 | ||||
Minimum of Months | 0.129676E+11 | 388.40 | 21166.70 | 1259480.93 | 23.16 | 21.88 | 42.17 | ||
Maximum of Months | 0.534040E+11 | 700.84 | 21166.70 | 1642352.24 | 28.22 | 25.66 | 59.46 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.293561E+10 | 38.52 | 21166.70 | 02-JAN-08:30 | 1205672.35 | 19-JAN-15:30 | 23.16 | 22.95 | 2.75 |
February | 0.434256E+10 | 56.99 | 21166.70 | 02-FEB-08:20 | 1198726.07 | 16-FEB-15:05 | 23.58 | 23.22 | 3.99 |
March | 0.610527E+10 | 80.27 | 21166.70 | 03-MAR-11:30 | 1282285.51 | 10-MAR-06:04 | 23.66 | 23.26 | 6.34 |
April | 0.906265E+10 | 118.93 | 21166.70 | 01-APR-14:05 | 1172948.41 | 11-APR-12:05 | 24.19 | 23.56 | 9.06 |
May | 0.206017E+11 | 270.36 | 21166.70 | 01-MAY-07:30 | 1417499.66 | 31-MAY-05:04 | 26.38 | 25.08 | 19.34 |
June | 0.305952E+11 | 401.51 | 21166.70 | 01-JUN-05:04 | 1251320.86 | 28-JUN-12:05 | 27.97 | 25.99 | 28.43 |
July | 0.310706E+11 | 407.75 | 21166.70 | 01-JUL-03:20 | 1259480.93 | 20-JUL-12:05 | 28.12 | 26.16 | 28.01 |
August | 0.336371E+11 | 441.43 | 21166.70 | 01-AUG-00:05 | 1371338.79 | 28-AUG-05:03 | 28.22 | 26.12 | 30.18 |
September | 0.297398E+11 | 390.29 | 21166.70 | 01-SEP-07:10 | 1405854.17 | 26-SEP-05:04 | 28.02 | 26.07 | 27.56 |
October | 0.223304E+11 | 293.05 | 21166.70 | 01-OCT-01:05 | 1368890.39 | 02-OCT-05:04 | 26.54 | 25.13 | 20.69 |
November | 0.137465E+11 | 180.40 | 21166.70 | 01-NOV-04:12 | 1384459.76 | 22-NOV-06:04 | 24.99 | 24.08 | 13.13 |
December | 0.435458E+10 | 57.29 | 21166.70 | 01-DEC-11:50 | 1264470.36 | 11-DEC-06:03 | 23.39 | 23.08 | 3.90 |
Annual Sum or Average | 0.208522E+12 | 2736.80 | 25.69 | 24.57 | 16.18 | ||||
Minimum of Months | 0.293561E+10 | 38.52 | 21166.70 | 1172948.41 | 23.16 | 22.95 | 2.75 | ||
Maximum of Months | 0.336371E+11 | 441.43 | 21166.70 | 1417499.66 | 28.22 | 26.16 | 30.18 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.406804E+09 | 0.00 | 30.43 | 156849.10 | 25-JAN-06:03 | 0.00 | 63.45 | 64.67 | 0.00 | 0.00 | 0.00 | 0.12 | 25-JAN-06:03 |
February | 0.136845E+10 | 0.00 | 23.01 | 734069.89 | 04-FEB-06:03 | 0.00 | 25.06 | 26.95 | 0.00 | 0.00 | 0.00 | 0.54 | 04-FEB-06:03 |
March | 0.433544E+09 | 0.00 | 15.06 | 358364.59 | 16-MAR-05:03 | 0.00 | 25.83 | 26.92 | 0.00 | 0.00 | 0.00 | 0.27 | 16-MAR-05:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 26.77 | 26.77 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 26.77 | 26.77 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 26.77 | 26.77 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 26.77 | 26.77 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 26.77 | 26.77 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 26.77 | 26.77 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 26.77 | 26.77 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 81719283.78 | 0.00 | 5.44 | 90124.36 | 13-NOV-06:03 | 0.00 | 27.44 | 27.85 | 0.00 | 0.00 | 0.00 | 0.07 | 13-NOV-06:03 |
December | 0.801154E+09 | 0.00 | 27.57 | 375846.89 | 15-DEC-06:02 | 0.00 | 26.32 | 28.38 | 0.00 | 0.00 | 0.00 | 0.28 | 15-DEC-06:02 |
Annual Sum or Average | 0.309167E+10 | 0.00 | 101.51 | 0.00 | 29.69 | 30.24 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 26.77 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.136845E+10 | 0.00 | 30.43 | 734069.89 | 0.00 | 63.45 | 64.67 | 0.00 | 0.00 | 0.00 | 0.54 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 25.67 | 25.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 31.05 | 31.05 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 35.83 | 35.83 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 42.60 | 42.60 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 32.67 | 32.67 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 38.43 | 38.43 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 43.23 | 43.23 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 47.10 | 47.10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 33.94 | 33.94 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 36.92 | 36.92 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 38.07 | 38.07 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 38.52 | 38.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 37.04 | 37.04 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 25.67 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.10 | 47.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.847869E+11 | 0.00 | 439.85 | 0.715382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205125.85 | 07-JAN-05:12 | 136652.65 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.957804E+11 | 0.00 | 414.60 | 0.807416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 235559.27 | 11-FEB-06:02 | 136192.33 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.130628E+12 | 0.00 | 559.51 | 0.106402E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 233683.87 | 06-MAR-06:03 | 139869.67 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 |
April | 0.152436E+12 | 0.00 | 615.67 | 0.125204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 242054.00 | 12-APR-05:02 | 150527.58 | 12-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.166468E+12 | 0.00 | 578.57 | 0.127317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256251.06 | 27-MAY-05:02 | 150700.91 | 31-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.188139E+12 | 0.00 | 617.62 | 0.140623E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 253627.20 | 12-JUN-04:23 | 156354.56 | 12-JUN-04:23 | 0.00 | 0.00 | 0.00 |
July | 0.201836E+12 | 0.00 | 648.31 | 0.151654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 255697.50 | 31-JUL-04:23 | 157947.82 | 31-JUL-04:23 | 0.00 | 0.00 | 0.00 |
August | 0.217001E+12 | 0.00 | 659.63 | 0.163921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 247282.94 | 14-AUG-05:02 | 165552.76 | 21-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.176705E+12 | 0.00 | 574.57 | 0.129567E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 250078.36 | 20-SEP-05:02 | 153961.67 | 23-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.174182E+12 | 0.00 | 598.50 | 0.130526E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 245102.03 | 02-OCT-05:02 | 158344.09 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.147239E+12 | 0.00 | 536.97 | 0.113153E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 234462.89 | 22-NOV-06:02 | 145404.72 | 22-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.117284E+12 | 0.00 | 543.55 | 0.928015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 238836.29 | 11-DEC-06:02 | 149949.16 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185248E+13 | 0.00 | 6787.37 | 0.143345E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.847869E+11 | 0.00 | 414.60 | 0.715382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205125.85 | 136192.33 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.217001E+12 | 0.00 | 659.63 | 0.163921E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256251.06 | 165552.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.667192E+12 | 0.00 | 421.56 | 0.543879E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1929256.37 | 14-JAN-06:02 | 1115830.52 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.735324E+12 | 0.00 | 387.26 | 0.598716E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2522921.32 | 11-FEB-06:02 | 1309348.57 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.932331E+12 | 0.00 | 452.78 | 0.750190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2502973.23 | 10-MAR-06:02 | 1312611.16 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.109508E+13 | 0.00 | 465.69 | 0.886054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2402475.50 | 12-APR-05:02 | 1388366.61 | 12-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.145168E+13 | 0.00 | 512.93 | 0.109678E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2662512.72 | 27-MAY-05:02 | 1389132.76 | 13-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.160116E+13 | 0.00 | 534.37 | 0.117016E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2528302.85 | 19-JUN-05:03 | 1444846.80 | 03-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.165077E+13 | 0.00 | 558.97 | 0.120939E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2490563.00 | 03-JUL-05:02 | 1450548.84 | 12-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.166530E+13 | 0.00 | 551.21 | 0.120515E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2464605.44 | 14-AUG-05:02 | 1447206.31 | 28-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.156607E+13 | 0.00 | 520.24 | 0.111858E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2515213.52 | 20-SEP-05:02 | 1443713.89 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.142035E+13 | 0.00 | 489.00 | 0.104761E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2554687.50 | 02-OCT-05:02 | 1401763.05 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.110321E+13 | 0.00 | 429.64 | 0.826447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2501916.00 | 22-NOV-06:02 | 1338775.55 | 09-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.739035E+12 | 0.00 | 422.56 | 0.580022E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2407570.40 | 07-DEC-06:02 | 1350559.33 | 07-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146275E+14 | 0.00 | 5746.20 | 0.110330E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.667192E+12 | 0.00 | 387.26 | 0.543879E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1929256.37 | 1115830.52 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.166530E+13 | 0.00 | 558.97 | 0.120939E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2662512.72 | 1450548.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.619223E+11 | 0.00 | 412.43 | 0.499780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207617.01 | 14-JAN-06:02 | 117248.31 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.737786E+11 | 0.00 | 373.66 | 0.602281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 265747.76 | 11-FEB-06:02 | 133858.11 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.966864E+11 | 0.00 | 445.86 | 0.777867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 258387.38 | 10-MAR-06:02 | 129099.04 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.117905E+12 | 0.00 | 458.73 | 0.966179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 255820.67 | 12-APR-05:02 | 146158.64 | 12-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.159630E+12 | 0.00 | 512.57 | 0.123014E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 288500.50 | 27-MAY-05:02 | 144724.20 | 31-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.176110E+12 | 0.00 | 537.15 | 0.131801E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 266365.19 | 19-JUN-05:03 | 154099.24 | 02-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.183225E+12 | 0.00 | 560.69 | 0.137898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 259645.26 | 03-JUL-05:02 | 154194.76 | 12-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.181191E+12 | 0.00 | 553.06 | 0.134320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 263413.58 | 14-AUG-05:02 | 157106.75 | 28-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.169133E+12 | 0.00 | 524.04 | 0.123834E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 268051.56 | 20-SEP-05:02 | 153290.19 | 23-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.147821E+12 | 0.00 | 488.22 | 0.110777E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 270287.07 | 02-OCT-05:02 | 150377.38 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.111377E+12 | 0.00 | 422.81 | 0.838394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 261133.47 | 22-NOV-06:02 | 132152.82 | 22-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.712302E+11 | 0.00 | 413.02 | 0.552438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 251731.82 | 11-DEC-06:02 | 137924.85 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155001E+13 | 0.00 | 5702.24 | 0.118534E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.619223E+11 | 0.00 | 373.66 | 0.499780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207617.01 | 117248.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.183225E+12 | 0.00 | 560.69 | 0.137898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 288500.50 | 157106.75 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.712654E+11 | 0.00 | 421.17 | 0.645935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157806.68 | 01-JAN-16:12 | 89983.79 | 27-JAN-05:13 | 0.00 | 0.00 | 0.00 |
February | 0.686124E+11 | 0.00 | 377.92 | 0.615059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144498.97 | 11-FEB-06:02 | 94530.49 | 06-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.794363E+11 | 0.00 | 433.31 | 0.696871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152146.65 | 06-MAR-05:53 | 90624.22 | 17-MAR-04:12 | 0.00 | 0.00 | 0.00 |
April | 0.821524E+11 | 0.00 | 406.11 | 0.705007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159726.11 | 16-APR-16:22 | 95686.19 | 16-APR-17:36 | 0.00 | 0.00 | 0.00 |
May | 0.104497E+12 | 0.00 | 444.76 | 0.805707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182861.71 | 29-MAY-10:40 | 92085.59 | 29-MAY-14:51 | 0.00 | 0.00 | 0.00 |
June | 0.118588E+12 | 0.00 | 444.46 | 0.829685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 174334.81 | 26-JUN-03:15 | 85881.02 | 08-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.125039E+12 | 0.00 | 444.67 | 0.866678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 177828.72 | 09-JUL-21:00 | 96118.48 | 30-JUL-14:57 | 0.00 | 0.00 | 0.00 |
August | 0.138036E+12 | 0.00 | 479.68 | 0.955137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 184986.85 | 21-AUG-03:15 | 93344.97 | 06-AUG-13:10 | 0.00 | 0.00 | 0.00 |
September | 0.119528E+12 | 0.00 | 443.33 | 0.838455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178370.75 | 17-SEP-21:10 | 89674.03 | 10-SEP-16:35 | 0.00 | 0.00 | 0.00 |
October | 0.113557E+12 | 0.00 | 451.36 | 0.847055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180685.71 | 29-OCT-17:00 | 93224.19 | 15-OCT-16:35 | 0.00 | 0.00 | 0.00 |
November | 0.974660E+11 | 0.00 | 418.21 | 0.766013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176235.65 | 05-NOV-15:22 | 92284.09 | 13-NOV-05:23 | 0.00 | 0.00 | 0.00 |
December | 0.761846E+11 | 0.00 | 423.57 | 0.672468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170207.59 | 26-DEC-02:43 | 93054.66 | 03-DEC-16:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119436E+13 | 0.00 | 5188.55 | 0.924407E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.686124E+11 | 0.00 | 377.92 | 0.615059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144498.97 | 85881.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.138036E+12 | 0.00 | 479.68 | 0.955137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 184986.85 | 96118.48 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.338192E+12 | 0.854164E+11 | 744.00 | 0.328619E+12 | 0.957290E+10 | 0.00 | 0.39 | 02-JAN-15:00 | 0.31 | 23-JAN-05:00 | 139395.19 | 02-JAN-15:00 | 129569.26 | 02-JAN-15:00 | 10200.81 | 06-JAN-17:00 | 44550.32 | 02-JAN-15:00 | 0.00 |
February | 0.528374E+12 | 0.136643E+12 | 672.00 | 0.518496E+12 | 0.987779E+10 | 0.00 | 0.61 | 02-FEB-14:00 | 0.52 | 01-FEB-00:10 | 229391.98 | 02-FEB-15:05 | 219753.55 | 22-FEB-16:00 | 11147.08 | 02-FEB-15:40 | 72363.10 | 11-FEB-14:00 | 0.00 |
March | 0.832403E+12 | 0.217305E+12 | 744.00 | 0.819635E+12 | 0.127677E+11 | 0.00 | 0.97 | 31-MAR-23:30 | 0.72 | 01-MAR-04:20 | 396026.23 | 31-MAR-23:05 | 392943.24 | 31-MAR-23:55 | 12515.51 | 13-MAR-10:00 | 105657.68 | 31-MAR-23:20 | 0.00 |
April | 0.104357E+13 | 0.288604E+12 | 720.00 | 0.103050E+13 | 0.130737E+11 | 0.00 | 1.00 | 01-APR-12:50 | 0.37 | 30-APR-23:53 | 423926.01 | 25-APR-16:00 | 405697.39 | 25-APR-16:00 | 18228.63 | 25-APR-16:00 | 132146.79 | 17-APR-15:00 | 0.00 |
May | 0.358117E+12 | 0.107397E+12 | 744.00 | 0.336528E+12 | 0.215889E+11 | 0.00 | 0.60 | 31-MAY-23:03 | 0.34 | 07-MAY-05:00 | 228579.87 | 31-MAY-23:03 | 211717.46 | 31-MAY-24:00 | 17343.45 | 31-MAY-23:03 | 67403.73 | 31-MAY-23:15 | 0.00 |
June | 0.590059E+12 | 0.180888E+12 | 720.00 | 0.563327E+12 | 0.267314E+11 | 0.00 | 0.81 | 30-JUN-23:15 | 0.58 | 01-JUN-06:00 | 315994.97 | 30-JUN-23:05 | 303345.26 | 30-JUN-23:55 | 16143.94 | 23-JUN-14:00 | 94354.00 | 30-JUN-23:15 | 0.00 |
July | 0.856157E+12 | 0.264782E+12 | 744.00 | 0.828928E+12 | 0.272288E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.79 | 04-JUL-04:40 | 401069.98 | 31-JUL-24:00 | 390976.24 | 31-JUL-24:00 | 16364.95 | 25-JUL-15:00 | 123547.44 | 31-JUL-23:50 | 0.00 |
August | 0.109039E+13 | 0.327260E+12 | 744.00 | 0.106475E+13 | 0.256420E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.42 | 31-AUG-23:17 | 424234.21 | 23-AUG-17:00 | 405856.42 | 23-AUG-17:00 | 18377.79 | 23-AUG-17:00 | 136565.64 | 23-AUG-13:00 | 0.00 |
September | 0.354522E+12 | 0.109196E+12 | 720.00 | 0.329282E+12 | 0.252394E+11 | 0.00 | 0.60 | 30-SEP-23:05 | 0.35 | 05-SEP-06:00 | 224589.71 | 30-SEP-23:05 | 212599.38 | 30-SEP-24:00 | 13490.22 | 07-SEP-14:00 | 69278.35 | 30-SEP-23:15 | 0.00 |
October | 0.606564E+12 | 0.179564E+12 | 744.00 | 0.582787E+12 | 0.237774E+11 | 0.00 | 0.78 | 31-OCT-23:10 | 0.57 | 20-OCT-04:20 | 312352.52 | 31-OCT-23:10 | 302182.89 | 31-OCT-24:00 | 15426.67 | 04-OCT-08:30 | 83243.44 | 31-OCT-23:20 | 0.00 |
November | 0.816103E+12 | 0.224291E+12 | 720.00 | 0.798082E+12 | 0.180210E+11 | 0.00 | 0.84 | 03-NOV-14:00 | 0.73 | 11-NOV-07:30 | 325188.60 | 30-NOV-17:00 | 312858.53 | 17-NOV-15:00 | 14013.58 | 29-NOV-11:00 | 103979.46 | 17-NOV-15:00 | 0.00 |
December | 0.107723E+13 | 0.270221E+12 | 744.00 | 0.106520E+13 | 0.120290E+11 | 0.00 | 1.00 | 01-DEC-09:20 | 0.91 | 16-DEC-04:00 | 412227.95 | 08-DEC-17:10 | 403500.96 | 11-DEC-16:30 | 12016.20 | 08-DEC-17:10 | 124320.56 | 10-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.849168E+13 | 0.239157E+13 | 8760.00 | 0.826613E+13 | 0.225550E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.338192E+12 | 0.854164E+11 | 672.00 | 0.328619E+12 | 0.957290E+10 | 0.00 | 0.39 | 0.31 | 139395.19 | 129569.26 | 10200.81 | 44550.32 | 0.00 | ||||||
Maximum of Months | 0.109039E+13 | 0.327260E+12 | 744.00 | 0.106520E+13 | 0.272288E+11 | 0.00 | 1.00 | 0.91 | 424234.21 | 405856.42 | 18377.79 | 136565.64 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.569109E+10 | 0.143240E+10 | 744.00 | 0.531551E+10 | 0.375588E+09 | 0.00 | 0.36 | 02-JAN-15:00 | 0.19 | 26-JAN-07:00 | 2877.44 | 02-JAN-15:00 | 2477.36 | 01-JAN-16:43 | 404.29 | 06-JAN-17:00 | 886.12 | 02-JAN-15:00 | 0.00 |
February | 0.997846E+10 | 0.255585E+10 | 672.00 | 0.956848E+10 | 0.409970E+09 | 0.00 | 0.60 | 19-FEB-17:22 | 0.41 | 04-FEB-07:40 | 4940.38 | 19-FEB-17:22 | 4819.25 | 20-FEB-17:42 | 440.18 | 11-FEB-17:35 | 1413.07 | 19-FEB-17:01 | 0.00 |
March | 0.162874E+11 | 0.420256E+10 | 744.00 | 0.157313E+11 | 0.556054E+09 | 0.00 | 0.89 | 31-MAR-23:35 | 0.63 | 11-MAR-08:00 | 7827.53 | 31-MAR-23:05 | 7665.69 | 31-MAR-23:50 | 527.52 | 14-MAR-09:10 | 2070.05 | 13-MAR-16:00 | 0.00 |
April | 0.209653E+11 | 0.573781E+10 | 720.00 | 0.203448E+11 | 0.620487E+09 | 0.00 | 1.00 | 01-APR-17:42 | 0.32 | 30-APR-23:53 | 8677.76 | 01-APR-18:10 | 8496.18 | 09-APR-17:53 | 550.53 | 25-APR-15:30 | 2785.63 | 17-APR-15:00 | 0.00 |
May | 0.691923E+10 | 0.201706E+10 | 744.00 | 0.604565E+10 | 0.873589E+09 | 0.00 | 0.56 | 31-MAY-23:03 | 0.28 | 27-MAY-13:00 | 4761.79 | 31-MAY-23:03 | 4031.06 | 31-MAY-24:00 | 761.58 | 31-MAY-23:03 | 1344.19 | 31-MAY-23:15 | 0.00 |
June | 0.119334E+11 | 0.355643E+10 | 720.00 | 0.107890E+11 | 0.114437E+10 | 0.00 | 0.76 | 30-JUN-23:05 | 0.52 | 17-JUN-06:50 | 6484.94 | 30-JUN-23:05 | 5911.12 | 30-JUN-24:00 | 631.66 | 23-JUN-14:00 | 1878.11 | 30-JUN-23:15 | 0.00 |
July | 0.175149E+11 | 0.528380E+10 | 744.00 | 0.163050E+11 | 0.120994E+10 | 0.00 | 0.98 | 31-JUL-24:00 | 0.72 | 14-JUL-20:00 | 8489.36 | 31-JUL-23:03 | 7910.74 | 31-JUL-23:53 | 683.52 | 25-JUL-15:00 | 2566.15 | 31-JUL-24:00 | 0.00 |
August | 0.226147E+11 | 0.677312E+10 | 744.00 | 0.213712E+11 | 0.124353E+10 | 0.00 | 1.00 | 01-AUG-09:20 | 0.37 | 31-AUG-23:13 | 8831.85 | 23-AUG-16:50 | 8286.47 | 06-AUG-18:14 | 662.78 | 21-AUG-12:50 | 2877.92 | 23-AUG-13:00 | 0.00 |
September | 0.697517E+10 | 0.207882E+10 | 720.00 | 0.594531E+10 | 0.102986E+10 | 0.00 | 0.56 | 30-SEP-23:05 | 0.29 | 16-SEP-07:00 | 4584.61 | 30-SEP-23:05 | 4063.60 | 30-SEP-24:00 | 548.29 | 30-SEP-23:05 | 1366.44 | 30-SEP-23:15 | 0.00 |
October | 0.120980E+11 | 0.349376E+10 | 744.00 | 0.110861E+11 | 0.101188E+10 | 0.00 | 0.72 | 31-OCT-23:10 | 0.49 | 28-OCT-07:00 | 6254.45 | 31-OCT-23:10 | 5810.15 | 31-OCT-24:00 | 653.46 | 04-OCT-08:20 | 1627.35 | 31-OCT-23:20 | 0.00 |
November | 0.161772E+11 | 0.437179E+10 | 720.00 | 0.153855E+11 | 0.791620E+09 | 0.00 | 0.81 | 07-NOV-17:00 | 0.64 | 27-NOV-08:00 | 6873.80 | 07-NOV-17:00 | 6459.15 | 07-NOV-17:00 | 618.37 | 29-NOV-11:05 | 2084.68 | 17-NOV-15:00 | 0.00 |
December | 0.212296E+11 | 0.528026E+10 | 744.00 | 0.206664E+11 | 0.563263E+09 | 0.00 | 1.00 | 08-DEC-16:20 | 0.80 | 16-DEC-08:00 | 8783.14 | 08-DEC-17:00 | 8354.96 | 03-DEC-17:00 | 500.33 | 07-DEC-17:00 | 2622.76 | 10-DEC-14:57 | 0.00 |
Annual Sum or Average | 0.168384E+12 | 0.467837E+11 | 8760.00 | 0.158554E+12 | 0.983016E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.569109E+10 | 0.143240E+10 | 672.00 | 0.531551E+10 | 0.375588E+09 | 0.00 | 0.36 | 0.19 | 2877.44 | 2477.36 | 404.29 | 886.12 | 0.00 | ||||||
Maximum of Months | 0.226147E+11 | 0.677312E+10 | 744.00 | 0.213712E+11 | 0.124353E+10 | 0.00 | 1.00 | 0.80 | 8831.85 | 8496.18 | 761.58 | 2877.92 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.483290E+11 | 0.123127E+11 | 744.00 | 0.446910E+11 | 0.363802E+10 | 0.00 | 0.36 | 02-JAN-15:00 | 0.13 | 26-JAN-08:00 | 27092.96 | 02-JAN-15:00 | 23185.38 | 02-JAN-17:00 | 4006.01 | 02-JAN-15:05 | 8341.93 | 02-JAN-15:00 | 0.00 |
February | 0.908540E+11 | 0.234212E+11 | 672.00 | 0.867957E+11 | 0.405831E+10 | 0.00 | 0.58 | 19-FEB-17:22 | 0.33 | 05-FEB-07:00 | 46149.12 | 19-FEB-17:22 | 44161.90 | 20-FEB-17:42 | 4367.25 | 11-FEB-17:35 | 13250.74 | 19-FEB-17:01 | 0.00 |
March | 0.153366E+12 | 0.396931E+11 | 744.00 | 0.147818E+12 | 0.554817E+10 | 0.00 | 0.90 | 31-MAR-23:55 | 0.58 | 21-MAR-07:00 | 75303.62 | 31-MAR-23:05 | 73793.45 | 31-MAR-24:00 | 5269.97 | 14-MAR-09:10 | 19798.36 | 31-MAR-23:15 | 0.00 |
April | 0.199670E+12 | 0.546876E+11 | 720.00 | 0.193457E+12 | 0.621321E+10 | 0.00 | 1.00 | 12-APR-14:00 | 0.30 | 30-APR-23:53 | 82791.22 | 01-APR-18:00 | 80074.79 | 09-APR-17:53 | 5478.54 | 25-APR-15:30 | 26641.24 | 17-APR-15:00 | 0.00 |
May | 0.652276E+11 | 0.190221E+11 | 744.00 | 0.565891E+11 | 0.863844E+10 | 0.00 | 0.57 | 31-MAY-23:03 | 0.26 | 01-MAY-06:00 | 46619.31 | 31-MAY-23:03 | 39038.45 | 31-MAY-24:00 | 7824.12 | 31-MAY-23:03 | 13111.34 | 31-MAY-23:15 | 0.00 |
June | 0.113913E+12 | 0.339329E+11 | 720.00 | 0.102518E+12 | 0.113945E+11 | 0.00 | 0.77 | 30-JUN-23:05 | 0.51 | 21-JUN-21:05 | 62857.30 | 30-JUN-23:05 | 57047.91 | 30-JUN-23:40 | 6269.12 | 23-JUN-14:00 | 18166.93 | 30-JUN-23:15 | 0.00 |
July | 0.167194E+12 | 0.504308E+11 | 744.00 | 0.155119E+12 | 0.120756E+11 | 0.00 | 0.99 | 31-JUL-24:00 | 0.71 | 14-JUL-21:20 | 81647.65 | 31-JUL-23:03 | 75620.60 | 31-JUL-23:57 | 6807.62 | 25-JUL-15:00 | 24590.04 | 31-JUL-23:13 | 0.00 |
August | 0.214709E+12 | 0.643965E+11 | 744.00 | 0.202268E+12 | 0.124408E+11 | 0.00 | 1.00 | 01-AUG-09:10 | 0.32 | 31-AUG-23:13 | 83893.47 | 23-AUG-16:30 | 78340.49 | 06-AUG-16:53 | 6642.55 | 21-AUG-12:50 | 27525.12 | 23-AUG-13:00 | 0.00 |
September | 0.655506E+11 | 0.195411E+11 | 720.00 | 0.553726E+11 | 0.101780E+11 | 0.00 | 0.56 | 30-SEP-23:05 | 0.28 | 26-SEP-07:00 | 44424.49 | 30-SEP-23:05 | 39050.11 | 30-SEP-23:47 | 5591.86 | 30-SEP-23:05 | 13185.10 | 30-SEP-23:15 | 0.00 |
October | 0.115006E+12 | 0.332163E+11 | 744.00 | 0.104937E+12 | 0.100689E+11 | 0.00 | 0.72 | 31-OCT-23:10 | 0.48 | 28-OCT-07:00 | 59580.06 | 31-OCT-23:10 | 55060.21 | 31-OCT-24:00 | 6505.27 | 04-OCT-08:20 | 15495.53 | 31-OCT-23:20 | 0.00 |
November | 0.152713E+12 | 0.413730E+11 | 720.00 | 0.144816E+12 | 0.789720E+10 | 0.00 | 0.81 | 07-NOV-17:00 | 0.59 | 27-NOV-07:00 | 65662.38 | 07-NOV-17:00 | 61525.78 | 07-NOV-17:00 | 6173.08 | 29-NOV-11:05 | 19940.16 | 03-NOV-14:00 | 0.00 |
December | 0.198685E+12 | 0.496289E+11 | 744.00 | 0.193049E+12 | 0.563536E+10 | 0.00 | 1.00 | 08-DEC-16:50 | 0.74 | 16-DEC-08:00 | 83710.08 | 08-DEC-17:00 | 79013.12 | 06-DEC-17:00 | 5043.92 | 08-DEC-16:50 | 24742.40 | 10-DEC-15:02 | 0.00 |
Annual Sum or Average | 0.158522E+13 | 0.441656E+12 | 8760.00 | 0.148743E+13 | 0.977866E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.483290E+11 | 0.123127E+11 | 672.00 | 0.446910E+11 | 0.363802E+10 | 0.00 | 0.36 | 0.13 | 27092.96 | 23185.38 | 4006.01 | 8341.93 | 0.00 | ||||||
Maximum of Months | 0.214709E+12 | 0.643965E+11 | 744.00 | 0.202268E+12 | 0.124408E+11 | 0.00 | 1.00 | 0.74 | 83893.47 | 80074.79 | 7824.12 | 27525.12 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.437245E+10 | 0.113022E+10 | 744.00 | 0.401605E+10 | 0.356393E+09 | 0.00 | 0.36 | 02-JAN-15:00 | 0.04 | 25-JAN-07:00 | 2764.04 | 02-JAN-15:00 | 2363.32 | 02-JAN-15:00 | 403.16 | 02-JAN-15:05 | 851.30 | 02-JAN-15:00 | 0.00 |
February | 0.882899E+10 | 0.229194E+10 | 672.00 | 0.842498E+10 | 0.404000E+09 | 0.00 | 0.60 | 19-FEB-17:12 | 0.21 | 05-FEB-07:50 | 4805.44 | 19-FEB-17:22 | 4567.23 | 20-FEB-17:42 | 438.80 | 02-FEB-11:00 | 1376.88 | 19-FEB-17:01 | 0.00 |
March | 0.152032E+11 | 0.395332E+10 | 744.00 | 0.146497E+11 | 0.553487E+09 | 0.00 | 0.88 | 31-MAR-23:15 | 0.50 | 16-MAR-06:00 | 7491.69 | 31-MAR-23:05 | 7335.86 | 31-MAR-24:00 | 526.74 | 14-MAR-09:10 | 1999.91 | 13-MAR-16:00 | 0.00 |
April | 0.200087E+11 | 0.549540E+10 | 720.00 | 0.193886E+11 | 0.620095E+09 | 0.00 | 1.00 | 12-APR-16:00 | 0.29 | 30-APR-23:53 | 8465.00 | 23-APR-18:13 | 8287.73 | 09-APR-17:53 | 547.40 | 25-APR-15:30 | 2705.38 | 17-APR-15:00 | 0.00 |
May | 0.664122E+10 | 0.193945E+10 | 744.00 | 0.577504E+10 | 0.866182E+09 | 0.00 | 0.57 | 31-MAY-23:03 | 0.25 | 01-MAY-06:00 | 4671.74 | 31-MAY-23:03 | 3944.26 | 31-MAY-24:00 | 778.89 | 31-MAY-23:03 | 1317.72 | 31-MAY-23:15 | 0.00 |
June | 0.115242E+11 | 0.343722E+10 | 720.00 | 0.103842E+11 | 0.113996E+10 | 0.00 | 0.76 | 30-JUN-23:05 | 0.50 | 14-JUN-06:00 | 6299.95 | 30-JUN-23:05 | 5719.41 | 30-JUN-23:40 | 628.55 | 23-JUN-14:00 | 1824.70 | 30-JUN-23:15 | 0.00 |
July | 0.168905E+11 | 0.510235E+10 | 744.00 | 0.156833E+11 | 0.120720E+10 | 0.00 | 0.97 | 31-JUL-23:13 | 0.70 | 14-JUL-21:20 | 8184.30 | 31-JUL-23:03 | 7582.03 | 31-JUL-23:57 | 681.06 | 25-JUL-15:00 | 2471.63 | 31-JUL-23:13 | 0.00 |
August | 0.215998E+11 | 0.649544E+10 | 744.00 | 0.203561E+11 | 0.124366E+10 | 0.00 | 1.00 | 01-AUG-11:50 | 0.32 | 31-AUG-23:13 | 8533.33 | 23-AUG-16:30 | 8068.63 | 06-AUG-18:14 | 665.09 | 22-AUG-15:00 | 2805.32 | 23-AUG-13:00 | 0.00 |
September | 0.667298E+10 | 0.199245E+10 | 720.00 | 0.565264E+10 | 0.102033E+10 | 0.00 | 0.56 | 30-SEP-23:05 | 0.26 | 26-SEP-07:00 | 4509.83 | 30-SEP-23:05 | 3978.71 | 30-SEP-24:00 | 550.79 | 30-SEP-23:05 | 1340.98 | 30-SEP-23:15 | 0.00 |
October | 0.115504E+11 | 0.334288E+10 | 744.00 | 0.105443E+11 | 0.100606E+10 | 0.00 | 0.70 | 31-OCT-23:10 | 0.45 | 28-OCT-07:00 | 5901.52 | 31-OCT-23:10 | 5443.10 | 31-OCT-24:00 | 650.33 | 04-OCT-08:20 | 1578.63 | 03-OCT-15:00 | 0.00 |
November | 0.151325E+11 | 0.411929E+10 | 720.00 | 0.143444E+11 | 0.788026E+09 | 0.00 | 0.81 | 07-NOV-17:00 | 0.51 | 13-NOV-06:55 | 6638.84 | 07-NOV-17:00 | 6225.52 | 07-NOV-17:00 | 617.79 | 29-NOV-11:05 | 2019.26 | 03-NOV-14:00 | 0.00 |
December | 0.195579E+11 | 0.491573E+10 | 744.00 | 0.189962E+11 | 0.561746E+09 | 0.00 | 0.99 | 10-DEC-16:02 | 0.67 | 16-DEC-07:30 | 8446.29 | 08-DEC-17:00 | 8002.41 | 10-DEC-16:14 | 504.12 | 08-DEC-16:50 | 2521.81 | 10-DEC-15:11 | 0.00 |
Annual Sum or Average | 0.157983E+12 | 0.442157E+11 | 8760.00 | 0.148216E+12 | 0.976714E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.437245E+10 | 0.113022E+10 | 672.00 | 0.401605E+10 | 0.356393E+09 | 0.00 | 0.36 | 0.04 | 2764.04 | 2363.32 | 403.16 | 851.30 | 0.00 | ||||||
Maximum of Months | 0.215998E+11 | 0.649544E+10 | 744.00 | 0.203561E+11 | 0.124366E+10 | 0.00 | 1.00 | 0.70 | 8533.33 | 8287.73 | 778.89 | 2805.32 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.20 | 0.00 | 102.20 | 103.75 | 271.43 | 0.00 | 0.00 | 0.00 |
February | 120.97 | 0.00 | 120.97 | 159.33 | 226.20 | 0.00 | 0.00 | 0.00 |
March | 144.27 | 0.00 | 144.27 | 193.05 | 185.27 | 0.00 | 0.00 | 0.00 |
April | 161.66 | 0.73 | 160.93 | 271.35 | 116.56 | 0.00 | 0.00 | 0.00 |
May | 184.60 | 8.26 | 176.35 | 380.66 | 59.26 | 0.00 | 0.00 | 0.00 |
June | 197.20 | 14.20 | 183.00 | 437.70 | 25.86 | 0.00 | 0.00 | 0.00 |
July | 199.56 | 9.78 | 189.78 | 462.15 | 39.98 | 0.00 | 0.00 | 0.00 |
August | 176.61 | 1.62 | 174.98 | 386.15 | 28.78 | 0.00 | 0.00 | 0.00 |
September | 156.67 | 0.01 | 156.66 | 359.89 | 43.56 | 0.00 | 0.00 | 0.00 |
October | 131.25 | 0.00 | 131.25 | 264.83 | 69.62 | 0.00 | 0.00 | 0.00 |
November | 114.13 | 0.00 | 114.13 | 183.49 | 140.03 | 0.00 | 0.00 | 0.00 |
December | 101.09 | 0.00 | 101.09 | 116.19 | 235.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.32 | 2.90 | 146.43 | 277.11 | 119.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.09 | 0.00 | 101.09 | 103.75 | 25.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 199.56 | 14.20 | 189.78 | 462.15 | 271.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.20 | 0.00 | 102.20 | 103.75 | 271.43 | 0.00 | 0.00 | 0.00 |
February | 120.97 | 0.00 | 120.97 | 159.33 | 226.20 | 0.00 | 0.00 | 0.00 |
March | 144.27 | 0.00 | 144.27 | 193.05 | 185.27 | 0.00 | 0.00 | 0.00 |
April | 161.66 | 0.73 | 160.93 | 271.35 | 116.56 | 0.00 | 0.00 | 0.00 |
May | 184.60 | 8.26 | 176.35 | 380.66 | 59.26 | 0.00 | 0.00 | 0.00 |
June | 197.20 | 14.20 | 183.00 | 437.70 | 25.86 | 0.00 | 0.00 | 0.00 |
July | 199.55 | 9.78 | 189.78 | 462.15 | 39.98 | 0.00 | 0.00 | 0.00 |
August | 176.61 | 1.62 | 174.98 | 386.15 | 28.78 | 0.00 | 0.00 | 0.00 |
September | 156.67 | 0.01 | 156.66 | 359.89 | 43.56 | 0.00 | 0.00 | 0.00 |
October | 131.25 | 0.00 | 131.25 | 264.83 | 69.62 | 0.00 | 0.00 | 0.00 |
November | 114.13 | 0.00 | 114.13 | 183.49 | 140.03 | 0.00 | 0.00 | 0.00 |
December | 101.09 | 0.00 | 101.09 | 116.19 | 235.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.32 | 2.90 | 146.43 | 277.11 | 119.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.09 | 0.00 | 101.09 | 103.75 | 25.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 199.55 | 14.20 | 189.78 | 462.15 | 271.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.20 | 0.00 | 102.20 | 103.75 | 271.43 | 0.00 | 0.00 | 0.00 |
February | 120.97 | 0.00 | 120.97 | 159.33 | 226.20 | 0.00 | 0.00 | 0.00 |
March | 144.27 | 0.00 | 144.27 | 193.05 | 185.27 | 0.00 | 0.00 | 0.00 |
April | 161.66 | 0.73 | 160.93 | 271.35 | 116.56 | 0.00 | 0.00 | 0.00 |
May | 184.60 | 8.26 | 176.35 | 380.66 | 59.26 | 0.00 | 0.00 | 0.00 |
June | 197.20 | 14.20 | 183.00 | 437.70 | 25.86 | 0.00 | 0.00 | 0.00 |
July | 199.56 | 9.78 | 189.78 | 462.15 | 39.98 | 0.00 | 0.00 | 0.00 |
August | 176.61 | 1.62 | 174.98 | 386.15 | 28.78 | 0.00 | 0.00 | 0.00 |
September | 156.67 | 0.01 | 156.66 | 359.89 | 43.56 | 0.00 | 0.00 | 0.00 |
October | 131.25 | 0.00 | 131.25 | 264.83 | 69.62 | 0.00 | 0.00 | 0.00 |
November | 114.13 | 0.00 | 114.13 | 183.49 | 140.03 | 0.00 | 0.00 | 0.00 |
December | 101.09 | 0.00 | 101.09 | 116.19 | 235.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.32 | 2.90 | 146.43 | 277.11 | 119.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.09 | 0.00 | 101.09 | 103.75 | 25.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 199.56 | 14.20 | 189.78 | 462.15 | 271.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.20 | 0.00 | 102.20 | 103.75 | 271.43 | 0.00 | 0.00 | 0.00 |
February | 120.97 | 0.00 | 120.97 | 159.33 | 226.20 | 0.00 | 0.00 | 0.00 |
March | 144.27 | 0.00 | 144.27 | 193.05 | 185.27 | 0.00 | 0.00 | 0.00 |
April | 161.66 | 0.73 | 160.93 | 271.35 | 116.56 | 0.00 | 0.00 | 0.00 |
May | 184.60 | 8.26 | 176.35 | 380.66 | 59.26 | 0.00 | 0.00 | 0.00 |
June | 197.20 | 14.20 | 183.00 | 437.70 | 25.86 | 0.00 | 0.00 | 0.00 |
July | 199.55 | 9.78 | 189.78 | 462.15 | 39.98 | 0.00 | 0.00 | 0.00 |
August | 176.61 | 1.62 | 174.98 | 386.15 | 28.78 | 0.00 | 0.00 | 0.00 |
September | 156.67 | 0.01 | 156.66 | 359.89 | 43.56 | 0.00 | 0.00 | 0.00 |
October | 131.25 | 0.00 | 131.25 | 264.83 | 69.62 | 0.00 | 0.00 | 0.00 |
November | 114.13 | 0.00 | 114.13 | 183.49 | 140.03 | 0.00 | 0.00 | 0.00 |
December | 101.09 | 0.00 | 101.09 | 116.19 | 235.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.32 | 2.90 | 146.43 | 277.11 | 119.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.09 | 0.00 | 101.09 | 103.75 | 25.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 199.55 | 14.20 | 189.78 | 462.15 | 271.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.20 | 0.00 | 102.20 | 103.75 | 271.42 | 0.00 | 0.00 | 0.00 |
February | 120.97 | 0.00 | 120.97 | 159.32 | 226.19 | 0.00 | 0.00 | 0.00 |
March | 144.26 | 0.00 | 144.26 | 193.04 | 185.26 | 0.00 | 0.00 | 0.00 |
April | 161.65 | 0.73 | 160.92 | 271.34 | 116.56 | 0.00 | 0.00 | 0.00 |
May | 184.60 | 8.26 | 176.34 | 380.64 | 59.26 | 0.00 | 0.00 | 0.00 |
June | 197.19 | 14.20 | 182.99 | 437.68 | 25.86 | 0.00 | 0.00 | 0.00 |
July | 199.55 | 9.78 | 189.77 | 462.13 | 39.98 | 0.00 | 0.00 | 0.00 |
August | 176.60 | 1.62 | 174.98 | 386.14 | 28.78 | 0.00 | 0.00 | 0.00 |
September | 156.67 | 0.01 | 156.65 | 359.87 | 43.56 | 0.00 | 0.00 | 0.00 |
October | 131.25 | 0.00 | 131.25 | 264.82 | 69.62 | 0.00 | 0.00 | 0.00 |
November | 114.12 | 0.00 | 114.12 | 183.48 | 140.02 | 0.00 | 0.00 | 0.00 |
December | 101.08 | 0.00 | 101.08 | 116.18 | 235.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 149.32 | 2.90 | 146.42 | 277.10 | 119.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.08 | 0.00 | 101.08 | 103.75 | 25.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 199.55 | 14.20 | 189.77 | 462.13 | 271.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 273.42 | 130.99 | 142.44 | 388.47 | 282.06 | 0.00 | 0.00 | 0.00 |
February | 315.71 | 146.14 | 169.57 | 489.76 | 233.48 | 0.00 | 0.00 | 0.00 |
March | 385.46 | 182.23 | 203.23 | 604.85 | 186.11 | 0.00 | 0.00 | 0.00 |
April | 418.32 | 186.65 | 231.67 | 736.72 | 124.93 | 0.00 | 0.00 | 0.00 |
May | 395.75 | 157.60 | 238.15 | 764.21 | 64.19 | 0.00 | 0.00 | 0.00 |
June | 390.61 | 150.03 | 240.58 | 793.90 | 26.92 | 0.00 | 0.00 | 0.00 |
July | 401.35 | 144.74 | 256.62 | 842.33 | 42.42 | 0.00 | 0.00 | 0.00 |
August | 367.00 | 122.72 | 244.29 | 748.65 | 25.94 | 0.00 | 0.00 | 0.00 |
September | 353.82 | 127.91 | 225.91 | 731.02 | 48.79 | 0.00 | 0.00 | 0.00 |
October | 325.67 | 140.25 | 185.42 | 625.25 | 75.09 | 0.00 | 0.00 | 0.00 |
November | 264.33 | 105.40 | 158.93 | 451.91 | 141.45 | 0.00 | 0.00 | 0.00 |
December | 213.52 | 75.38 | 138.14 | 311.04 | 239.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.14 | 139.08 | 203.06 | 624.52 | 123.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.52 | 75.38 | 138.14 | 311.04 | 25.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.32 | 186.65 | 256.62 | 842.33 | 282.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 273.42 | 130.99 | 142.44 | 388.47 | 282.06 | 0.00 | 0.00 | 0.00 |
February | 315.71 | 146.14 | 169.57 | 489.76 | 233.48 | 0.00 | 0.00 | 0.00 |
March | 385.46 | 182.23 | 203.23 | 604.85 | 186.11 | 0.00 | 0.00 | 0.00 |
April | 418.32 | 186.65 | 231.67 | 736.72 | 124.93 | 0.00 | 0.00 | 0.00 |
May | 395.75 | 157.60 | 238.15 | 764.21 | 64.19 | 0.00 | 0.00 | 0.00 |
June | 390.61 | 150.03 | 240.58 | 793.90 | 26.92 | 0.00 | 0.00 | 0.00 |
July | 401.35 | 144.74 | 256.62 | 842.33 | 42.42 | 0.00 | 0.00 | 0.00 |
August | 367.00 | 122.72 | 244.29 | 748.65 | 25.94 | 0.00 | 0.00 | 0.00 |
September | 353.82 | 127.91 | 225.91 | 731.02 | 48.79 | 0.00 | 0.00 | 0.00 |
October | 325.67 | 140.25 | 185.42 | 625.25 | 75.09 | 0.00 | 0.00 | 0.00 |
November | 264.33 | 105.40 | 158.93 | 451.91 | 141.45 | 0.00 | 0.00 | 0.00 |
December | 213.52 | 75.38 | 138.14 | 311.04 | 239.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.14 | 139.08 | 203.06 | 624.52 | 123.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.52 | 75.38 | 138.14 | 311.04 | 25.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.32 | 186.65 | 256.62 | 842.33 | 282.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 273.42 | 130.98 | 142.43 | 388.46 | 282.06 | 0.00 | 0.00 | 0.00 |
February | 315.70 | 146.14 | 169.56 | 489.75 | 233.47 | 0.00 | 0.00 | 0.00 |
March | 385.45 | 182.22 | 203.23 | 604.84 | 186.10 | 0.00 | 0.00 | 0.00 |
April | 418.31 | 186.65 | 231.66 | 736.71 | 124.93 | 0.00 | 0.00 | 0.00 |
May | 395.74 | 157.59 | 238.15 | 764.19 | 64.19 | 0.00 | 0.00 | 0.00 |
June | 390.60 | 150.03 | 240.57 | 793.88 | 26.92 | 0.00 | 0.00 | 0.00 |
July | 401.35 | 144.73 | 256.61 | 842.31 | 42.42 | 0.00 | 0.00 | 0.00 |
August | 367.00 | 122.72 | 244.28 | 748.64 | 25.94 | 0.00 | 0.00 | 0.00 |
September | 353.81 | 127.90 | 225.91 | 731.00 | 48.79 | 0.00 | 0.00 | 0.00 |
October | 325.67 | 140.25 | 185.41 | 625.24 | 75.09 | 0.00 | 0.00 | 0.00 |
November | 264.32 | 105.40 | 158.93 | 451.90 | 141.45 | 0.00 | 0.00 | 0.00 |
December | 213.51 | 75.38 | 138.13 | 311.04 | 239.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 342.13 | 139.07 | 203.06 | 624.50 | 123.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.51 | 75.38 | 138.13 | 311.04 | 25.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 418.31 | 186.65 | 256.61 | 842.31 | 282.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.33 | 312.06 | 168.27 | 766.09 | 263.63 | 0.00 | 0.00 | 0.00 |
February | 434.53 | 251.43 | 183.10 | 732.71 | 224.86 | 0.00 | 0.00 | 0.00 |
March | 333.62 | 141.05 | 192.57 | 570.40 | 184.44 | 0.00 | 0.00 | 0.00 |
April | 226.86 | 39.78 | 187.07 | 426.27 | 123.19 | 0.00 | 0.00 | 0.00 |
May | 181.79 | 3.93 | 177.86 | 376.41 | 58.82 | 0.00 | 0.00 | 0.00 |
June | 173.32 | 0.33 | 172.99 | 386.04 | 26.13 | 0.00 | 0.00 | 0.00 |
July | 185.58 | 1.72 | 183.86 | 431.99 | 39.71 | 0.00 | 0.00 | 0.00 |
August | 210.63 | 17.77 | 192.85 | 465.06 | 29.32 | 0.00 | 0.00 | 0.00 |
September | 269.63 | 66.07 | 203.56 | 596.09 | 47.86 | 0.00 | 0.00 | 0.00 |
October | 370.79 | 173.97 | 196.83 | 727.78 | 81.14 | 0.00 | 0.00 | 0.00 |
November | 421.88 | 235.46 | 186.43 | 741.20 | 144.68 | 0.00 | 0.00 | 0.00 |
December | 462.91 | 291.98 | 170.93 | 755.01 | 235.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 312.09 | 127.41 | 184.68 | 580.49 | 121.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 173.32 | 0.33 | 168.27 | 376.41 | 26.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 480.33 | 312.06 | 203.56 | 766.09 | 263.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.33 | 312.06 | 168.27 | 766.09 | 263.63 | 0.00 | 0.00 | 0.00 |
February | 434.53 | 251.43 | 183.10 | 732.71 | 224.86 | 0.00 | 0.00 | 0.00 |
March | 333.62 | 141.05 | 192.57 | 570.40 | 184.44 | 0.00 | 0.00 | 0.00 |
April | 226.86 | 39.78 | 187.07 | 426.27 | 123.19 | 0.00 | 0.00 | 0.00 |
May | 181.79 | 3.93 | 177.86 | 376.41 | 58.82 | 0.00 | 0.00 | 0.00 |
June | 173.32 | 0.33 | 172.99 | 386.04 | 26.13 | 0.00 | 0.00 | 0.00 |
July | 185.58 | 1.72 | 183.86 | 431.99 | 39.71 | 0.00 | 0.00 | 0.00 |
August | 210.63 | 17.77 | 192.85 | 465.06 | 29.32 | 0.00 | 0.00 | 0.00 |
September | 269.63 | 66.07 | 203.56 | 596.09 | 47.86 | 0.00 | 0.00 | 0.00 |
October | 370.79 | 173.97 | 196.83 | 727.77 | 81.14 | 0.00 | 0.00 | 0.00 |
November | 421.88 | 235.46 | 186.43 | 741.20 | 144.68 | 0.00 | 0.00 | 0.00 |
December | 462.91 | 291.98 | 170.93 | 755.00 | 235.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 312.09 | 127.41 | 184.68 | 580.49 | 121.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 173.32 | 0.33 | 168.27 | 376.41 | 26.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 480.33 | 312.06 | 203.56 | 766.09 | 263.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.33 | 312.06 | 168.27 | 766.09 | 263.63 | 0.00 | 0.00 | 0.00 |
February | 434.53 | 251.43 | 183.10 | 732.71 | 224.86 | 0.00 | 0.00 | 0.00 |
March | 333.62 | 141.05 | 192.57 | 570.40 | 184.44 | 0.00 | 0.00 | 0.00 |
April | 226.86 | 39.78 | 187.07 | 426.27 | 123.19 | 0.00 | 0.00 | 0.00 |
May | 181.79 | 3.93 | 177.86 | 376.41 | 58.82 | 0.00 | 0.00 | 0.00 |
June | 173.32 | 0.33 | 172.99 | 386.04 | 26.13 | 0.00 | 0.00 | 0.00 |
July | 185.58 | 1.72 | 183.86 | 431.99 | 39.71 | 0.00 | 0.00 | 0.00 |
August | 210.63 | 17.77 | 192.85 | 465.06 | 29.32 | 0.00 | 0.00 | 0.00 |
September | 269.63 | 66.07 | 203.56 | 596.09 | 47.86 | 0.00 | 0.00 | 0.00 |
October | 370.79 | 173.97 | 196.83 | 727.78 | 81.14 | 0.00 | 0.00 | 0.00 |
November | 421.88 | 235.46 | 186.43 | 741.20 | 144.68 | 0.00 | 0.00 | 0.00 |
December | 462.91 | 291.98 | 170.93 | 755.01 | 235.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 312.09 | 127.41 | 184.68 | 580.49 | 121.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 173.32 | 0.33 | 168.27 | 376.41 | 26.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 480.33 | 312.06 | 203.56 | 766.09 | 263.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.33 | 312.06 | 168.27 | 766.09 | 263.63 | 0.00 | 0.00 | 0.00 |
February | 434.53 | 251.43 | 183.10 | 732.71 | 224.86 | 0.00 | 0.00 | 0.00 |
March | 333.62 | 141.05 | 192.57 | 570.40 | 184.44 | 0.00 | 0.00 | 0.00 |
April | 226.86 | 39.78 | 187.07 | 426.27 | 123.19 | 0.00 | 0.00 | 0.00 |
May | 181.79 | 3.93 | 177.86 | 376.41 | 58.82 | 0.00 | 0.00 | 0.00 |
June | 173.32 | 0.33 | 172.99 | 386.04 | 26.13 | 0.00 | 0.00 | 0.00 |
July | 185.58 | 1.72 | 183.86 | 431.99 | 39.71 | 0.00 | 0.00 | 0.00 |
August | 210.63 | 17.77 | 192.85 | 465.06 | 29.32 | 0.00 | 0.00 | 0.00 |
September | 269.63 | 66.07 | 203.56 | 596.09 | 47.86 | 0.00 | 0.00 | 0.00 |
October | 370.79 | 173.97 | 196.83 | 727.77 | 81.14 | 0.00 | 0.00 | 0.00 |
November | 421.88 | 235.46 | 186.43 | 741.20 | 144.68 | 0.00 | 0.00 | 0.00 |
December | 462.91 | 291.98 | 170.93 | 755.00 | 235.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 312.09 | 127.41 | 184.68 | 580.49 | 121.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 173.32 | 0.33 | 168.27 | 376.41 | 26.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 480.33 | 312.06 | 203.56 | 766.09 | 263.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.31 | 312.05 | 168.26 | 766.06 | 263.62 | 0.00 | 0.00 | 0.00 |
February | 434.51 | 251.42 | 183.09 | 732.68 | 224.85 | 0.00 | 0.00 | 0.00 |
March | 333.61 | 141.05 | 192.56 | 570.37 | 184.44 | 0.00 | 0.00 | 0.00 |
April | 226.85 | 39.78 | 187.07 | 426.26 | 123.19 | 0.00 | 0.00 | 0.00 |
May | 181.78 | 3.93 | 177.85 | 376.39 | 58.82 | 0.00 | 0.00 | 0.00 |
June | 173.31 | 0.33 | 172.99 | 386.02 | 26.12 | 0.00 | 0.00 | 0.00 |
July | 185.57 | 1.72 | 183.85 | 431.97 | 39.71 | 0.00 | 0.00 | 0.00 |
August | 210.62 | 17.77 | 192.84 | 465.04 | 29.32 | 0.00 | 0.00 | 0.00 |
September | 269.62 | 66.07 | 203.55 | 596.07 | 47.85 | 0.00 | 0.00 | 0.00 |
October | 370.78 | 173.96 | 196.82 | 727.75 | 81.14 | 0.00 | 0.00 | 0.00 |
November | 421.87 | 235.45 | 186.42 | 741.17 | 144.68 | 0.00 | 0.00 | 0.00 |
December | 462.89 | 291.96 | 170.92 | 754.98 | 235.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 312.08 | 127.41 | 184.67 | 580.47 | 121.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 173.31 | 0.33 | 168.26 | 376.39 | 26.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 480.31 | 312.05 | 203.55 | 766.06 | 263.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 245.62 | 105.89 | 139.73 | 345.04 | 332.22 | 0.00 | 0.00 | 0.00 |
February | 307.15 | 139.00 | 168.14 | 479.91 | 295.74 | 0.00 | 0.00 | 0.00 |
March | 382.49 | 174.66 | 207.82 | 601.09 | 257.06 | 0.00 | 0.00 | 0.00 |
April | 421.01 | 194.94 | 226.07 | 722.22 | 185.25 | 0.00 | 0.00 | 0.00 |
May | 383.81 | 147.75 | 236.06 | 736.72 | 94.24 | 0.00 | 0.00 | 0.00 |
June | 325.20 | 91.22 | 233.98 | 654.48 | 53.38 | 0.00 | 0.00 | 0.00 |
July | 363.44 | 112.44 | 251.00 | 749.31 | 75.72 | 0.00 | 0.00 | 0.00 |
August | 362.61 | 118.18 | 244.44 | 706.87 | 72.32 | 0.00 | 0.00 | 0.00 |
September | 309.33 | 91.21 | 218.12 | 635.20 | 68.53 | 0.00 | 0.00 | 0.00 |
October | 307.73 | 119.96 | 187.76 | 580.23 | 115.41 | 0.00 | 0.00 | 0.00 |
November | 253.84 | 93.11 | 160.73 | 424.96 | 203.82 | 0.00 | 0.00 | 0.00 |
December | 254.30 | 113.69 | 140.60 | 370.18 | 321.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.52 | 125.14 | 201.38 | 584.43 | 172.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.62 | 91.21 | 139.73 | 345.04 | 53.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.01 | 194.94 | 251.00 | 749.31 | 332.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 245.62 | 105.89 | 139.73 | 345.04 | 332.22 | 0.00 | 0.00 | 0.00 |
February | 307.15 | 139.00 | 168.14 | 479.91 | 295.74 | 0.00 | 0.00 | 0.00 |
March | 382.49 | 174.66 | 207.82 | 601.09 | 257.06 | 0.00 | 0.00 | 0.00 |
April | 421.01 | 194.94 | 226.07 | 722.22 | 185.25 | 0.00 | 0.00 | 0.00 |
May | 383.81 | 147.75 | 236.06 | 736.72 | 94.24 | 0.00 | 0.00 | 0.00 |
June | 325.20 | 91.22 | 233.98 | 654.48 | 53.38 | 0.00 | 0.00 | 0.00 |
July | 363.44 | 112.44 | 251.00 | 749.31 | 75.72 | 0.00 | 0.00 | 0.00 |
August | 362.61 | 118.18 | 244.44 | 706.87 | 72.32 | 0.00 | 0.00 | 0.00 |
September | 309.33 | 91.21 | 218.12 | 635.20 | 68.53 | 0.00 | 0.00 | 0.00 |
October | 307.73 | 119.96 | 187.76 | 580.23 | 115.41 | 0.00 | 0.00 | 0.00 |
November | 253.84 | 93.11 | 160.73 | 424.96 | 203.82 | 0.00 | 0.00 | 0.00 |
December | 254.30 | 113.69 | 140.60 | 370.18 | 321.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.52 | 125.14 | 201.38 | 584.43 | 172.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.62 | 91.21 | 139.73 | 345.04 | 53.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.01 | 194.94 | 251.00 | 749.31 | 332.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 245.62 | 105.89 | 139.73 | 345.03 | 332.22 | 0.00 | 0.00 | 0.00 |
February | 307.14 | 139.00 | 168.14 | 479.90 | 295.73 | 0.00 | 0.00 | 0.00 |
March | 382.48 | 174.66 | 207.82 | 601.08 | 257.05 | 0.00 | 0.00 | 0.00 |
April | 421.00 | 194.94 | 226.06 | 722.21 | 185.25 | 0.00 | 0.00 | 0.00 |
May | 383.80 | 147.74 | 236.05 | 736.70 | 94.24 | 0.00 | 0.00 | 0.00 |
June | 325.19 | 91.22 | 233.97 | 654.46 | 53.38 | 0.00 | 0.00 | 0.00 |
July | 363.43 | 112.44 | 251.00 | 749.29 | 75.72 | 0.00 | 0.00 | 0.00 |
August | 362.61 | 118.17 | 244.43 | 706.86 | 72.32 | 0.00 | 0.00 | 0.00 |
September | 309.32 | 91.21 | 218.11 | 635.19 | 68.53 | 0.00 | 0.00 | 0.00 |
October | 307.72 | 119.96 | 187.76 | 580.22 | 115.40 | 0.00 | 0.00 | 0.00 |
November | 253.84 | 93.11 | 160.73 | 424.95 | 203.81 | 0.00 | 0.00 | 0.00 |
December | 254.29 | 113.69 | 140.60 | 370.17 | 321.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 326.52 | 125.14 | 201.38 | 584.42 | 172.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.62 | 91.21 | 139.73 | 345.03 | 53.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.00 | 194.94 | 251.00 | 749.29 | 332.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 510.99 | 0.00 | 510.99 | 564.50 | 1206.42 | 0.00 | 0.00 | 0.00 |
February | 604.84 | 0.00 | 604.84 | 842.62 | 999.28 | 0.00 | 0.00 | 0.00 |
March | 721.32 | 0.00 | 721.32 | 992.48 | 841.94 | 0.00 | 0.00 | 0.00 |
April | 808.27 | 3.63 | 804.64 | 1377.15 | 552.17 | 0.00 | 0.00 | 0.00 |
May | 923.00 | 41.29 | 881.72 | 1900.83 | 296.39 | 0.00 | 0.00 | 0.00 |
June | 985.97 | 70.99 | 914.97 | 2187.84 | 137.20 | 0.00 | 0.00 | 0.00 |
July | 997.76 | 48.89 | 948.87 | 2323.59 | 195.28 | 0.00 | 0.00 | 0.00 |
August | 883.03 | 8.12 | 874.91 | 1964.85 | 128.67 | 0.00 | 0.00 | 0.00 |
September | 783.36 | 0.06 | 783.30 | 1806.06 | 215.49 | 0.00 | 0.00 | 0.00 |
October | 656.26 | 0.00 | 656.26 | 1337.40 | 336.55 | 0.00 | 0.00 | 0.00 |
November | 570.62 | 0.00 | 570.62 | 944.17 | 631.54 | 0.00 | 0.00 | 0.00 |
December | 505.44 | 0.00 | 505.44 | 627.78 | 1029.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 746.61 | 14.49 | 732.13 | 1408.51 | 545.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.44 | 0.00 | 505.44 | 564.50 | 128.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 997.76 | 70.99 | 948.87 | 2323.59 | 1206.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 820.25 | 392.95 | 427.30 | 1162.24 | 799.20 | 0.00 | 0.00 | 0.00 |
February | 947.12 | 438.42 | 508.70 | 1457.61 | 660.86 | 0.00 | 0.00 | 0.00 |
March | 1156.36 | 546.68 | 609.68 | 1781.40 | 551.35 | 0.00 | 0.00 | 0.00 |
April | 1254.95 | 559.95 | 695.00 | 2169.18 | 392.95 | 0.00 | 0.00 | 0.00 |
May | 1187.23 | 472.78 | 714.45 | 2255.39 | 204.26 | 0.00 | 0.00 | 0.00 |
June | 1171.81 | 450.09 | 721.73 | 2341.18 | 97.24 | 0.00 | 0.00 | 0.00 |
July | 1204.05 | 434.21 | 769.85 | 2494.33 | 144.59 | 0.00 | 0.00 | 0.00 |
August | 1101.00 | 368.15 | 732.85 | 2217.84 | 93.58 | 0.00 | 0.00 | 0.00 |
September | 1061.44 | 383.71 | 677.72 | 2159.57 | 156.02 | 0.00 | 0.00 | 0.00 |
October | 977.01 | 420.76 | 556.25 | 1847.27 | 242.37 | 0.00 | 0.00 | 0.00 |
November | 792.97 | 316.19 | 476.78 | 1336.90 | 419.21 | 0.00 | 0.00 | 0.00 |
December | 640.55 | 226.14 | 414.40 | 927.68 | 687.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1026.40 | 417.22 | 609.17 | 1847.37 | 369.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 640.55 | 226.14 | 414.40 | 927.68 | 93.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1254.95 | 559.95 | 769.85 | 2494.33 | 799.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2401.64 | 1560.29 | 841.35 | 3790.75 | 1288.96 | 0.00 | 0.00 | 0.00 |
February | 2172.64 | 1257.14 | 915.50 | 3629.71 | 1082.81 | 0.00 | 0.00 | 0.00 |
March | 1668.09 | 705.26 | 962.83 | 2825.72 | 893.74 | 0.00 | 0.00 | 0.00 |
April | 1134.27 | 198.91 | 935.36 | 2127.50 | 600.47 | 0.00 | 0.00 | 0.00 |
May | 908.93 | 19.66 | 889.27 | 1880.77 | 289.68 | 0.00 | 0.00 | 0.00 |
June | 866.59 | 1.64 | 864.96 | 1939.70 | 135.21 | 0.00 | 0.00 | 0.00 |
July | 927.88 | 8.60 | 919.28 | 2176.39 | 191.78 | 0.00 | 0.00 | 0.00 |
August | 1053.12 | 88.87 | 964.25 | 2348.81 | 136.17 | 0.00 | 0.00 | 0.00 |
September | 1348.13 | 330.36 | 1017.77 | 2960.01 | 243.94 | 0.00 | 0.00 | 0.00 |
October | 1853.95 | 869.82 | 984.13 | 3603.20 | 419.89 | 0.00 | 0.00 | 0.00 |
November | 2109.39 | 1177.27 | 932.12 | 3669.45 | 712.23 | 0.00 | 0.00 | 0.00 |
December | 2314.51 | 1459.86 | 854.65 | 3744.02 | 1141.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1560.43 | 637.06 | 923.37 | 2887.65 | 592.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 866.59 | 1.64 | 841.35 | 1880.77 | 135.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2401.64 | 1560.29 | 1017.77 | 3790.75 | 1288.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 736.86 | 317.67 | 419.19 | 1065.07 | 874.57 | 0.00 | 0.00 | 0.00 |
February | 921.43 | 417.00 | 504.43 | 1479.42 | 752.12 | 0.00 | 0.00 | 0.00 |
March | 1147.46 | 523.99 | 623.47 | 1837.21 | 652.48 | 0.00 | 0.00 | 0.00 |
April | 1263.02 | 584.82 | 678.20 | 2212.46 | 465.82 | 0.00 | 0.00 | 0.00 |
May | 1151.40 | 443.24 | 708.17 | 2217.15 | 256.84 | 0.00 | 0.00 | 0.00 |
June | 975.59 | 273.66 | 701.93 | 1994.89 | 125.85 | 0.00 | 0.00 | 0.00 |
July | 1090.31 | 337.31 | 753.00 | 2292.32 | 176.48 | 0.00 | 0.00 | 0.00 |
August | 1087.83 | 354.52 | 733.31 | 2190.18 | 134.52 | 0.00 | 0.00 | 0.00 |
September | 927.98 | 273.63 | 654.35 | 1922.42 | 179.91 | 0.00 | 0.00 | 0.00 |
October | 923.17 | 359.88 | 563.29 | 1765.94 | 292.50 | 0.00 | 0.00 | 0.00 |
November | 761.52 | 279.33 | 482.19 | 1319.91 | 487.70 | 0.00 | 0.00 | 0.00 |
December | 762.88 | 341.08 | 421.80 | 1165.46 | 769.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 979.56 | 375.42 | 604.15 | 1790.27 | 429.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 736.86 | 273.63 | 419.19 | 1065.07 | 125.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1263.02 | 584.82 | 753.00 | 2292.32 | 874.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 510.99 | 0.00 | 510.99 | 581.61 | 1127.40 | 0.00 | 0.00 | 0.00 |
February | 604.84 | 0.00 | 604.84 | 847.11 | 948.44 | 0.00 | 0.00 | 0.00 |
March | 721.32 | 0.00 | 721.32 | 983.04 | 812.16 | 0.00 | 0.00 | 0.00 |
April | 808.27 | 3.63 | 804.64 | 1352.17 | 552.45 | 0.00 | 0.00 | 0.00 |
May | 923.00 | 41.29 | 881.72 | 1868.53 | 306.42 | 0.00 | 0.00 | 0.00 |
June | 985.97 | 70.99 | 914.97 | 2148.66 | 144.98 | 0.00 | 0.00 | 0.00 |
July | 997.76 | 48.89 | 948.87 | 2284.55 | 210.64 | 0.00 | 0.00 | 0.00 |
August | 883.03 | 8.12 | 874.91 | 1932.62 | 136.72 | 0.00 | 0.00 | 0.00 |
September | 783.36 | 0.06 | 783.30 | 1769.22 | 220.64 | 0.00 | 0.00 | 0.00 |
October | 656.26 | 0.00 | 656.26 | 1314.84 | 340.01 | 0.00 | 0.00 | 0.00 |
November | 570.62 | 0.00 | 570.62 | 940.44 | 600.62 | 0.00 | 0.00 | 0.00 |
December | 505.44 | 0.00 | 505.44 | 636.68 | 972.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 746.61 | 14.49 | 732.13 | 1390.94 | 529.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.44 | 0.00 | 505.44 | 581.61 | 136.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 997.76 | 70.99 | 948.87 | 2284.55 | 1127.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 820.25 | 392.95 | 427.30 | 1179.33 | 754.71 | 0.00 | 0.00 | 0.00 |
February | 947.12 | 438.42 | 508.70 | 1466.80 | 631.16 | 0.00 | 0.00 | 0.00 |
March | 1156.36 | 546.68 | 609.68 | 1778.25 | 535.37 | 0.00 | 0.00 | 0.00 |
April | 1254.95 | 559.95 | 695.00 | 2157.05 | 391.40 | 0.00 | 0.00 | 0.00 |
May | 1187.23 | 472.78 | 714.45 | 2238.96 | 208.66 | 0.00 | 0.00 | 0.00 |
June | 1171.81 | 450.09 | 721.73 | 2321.99 | 101.10 | 0.00 | 0.00 | 0.00 |
July | 1204.05 | 434.21 | 769.85 | 2475.24 | 152.65 | 0.00 | 0.00 | 0.00 |
August | 1101.00 | 368.15 | 732.85 | 2203.57 | 97.26 | 0.00 | 0.00 | 0.00 |
September | 1061.44 | 383.71 | 677.72 | 2142.73 | 158.30 | 0.00 | 0.00 | 0.00 |
October | 977.01 | 420.76 | 556.25 | 1838.26 | 242.30 | 0.00 | 0.00 | 0.00 |
November | 792.97 | 316.19 | 476.78 | 1339.80 | 400.88 | 0.00 | 0.00 | 0.00 |
December | 640.55 | 226.14 | 414.40 | 938.89 | 652.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1026.40 | 417.22 | 609.17 | 1841.49 | 359.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 640.55 | 226.14 | 414.40 | 938.89 | 97.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1254.95 | 559.95 | 769.85 | 2475.24 | 754.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2401.64 | 1560.29 | 841.35 | 3803.90 | 1223.80 | 0.00 | 0.00 | 0.00 |
February | 2172.64 | 1257.14 | 915.50 | 3629.07 | 1037.32 | 0.00 | 0.00 | 0.00 |
March | 1668.09 | 705.26 | 962.83 | 2809.61 | 866.53 | 0.00 | 0.00 | 0.00 |
April | 1134.27 | 198.91 | 935.36 | 2100.60 | 599.66 | 0.00 | 0.00 | 0.00 |
May | 908.93 | 19.66 | 889.27 | 1847.29 | 299.25 | 0.00 | 0.00 | 0.00 |
June | 866.59 | 1.64 | 864.96 | 1899.71 | 143.09 | 0.00 | 0.00 | 0.00 |
July | 927.88 | 8.60 | 919.28 | 2136.91 | 207.99 | 0.00 | 0.00 | 0.00 |
August | 1053.12 | 88.87 | 964.25 | 2315.04 | 143.79 | 0.00 | 0.00 | 0.00 |
September | 1348.13 | 330.36 | 1017.77 | 2925.16 | 249.08 | 0.00 | 0.00 | 0.00 |
October | 1853.95 | 869.82 | 984.13 | 3581.44 | 418.78 | 0.00 | 0.00 | 0.00 |
November | 2109.39 | 1177.27 | 932.12 | 3664.11 | 683.75 | 0.00 | 0.00 | 0.00 |
December | 2314.51 | 1459.86 | 854.65 | 3745.61 | 1091.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1560.43 | 637.06 | 923.37 | 2867.77 | 578.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 866.59 | 1.64 | 841.35 | 1847.29 | 143.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2401.64 | 1560.29 | 1017.77 | 3803.90 | 1223.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 736.86 | 317.67 | 419.19 | 1069.03 | 827.95 | 0.00 | 0.00 | 0.00 |
February | 921.43 | 417.00 | 504.43 | 1475.56 | 721.28 | 0.00 | 0.00 | 0.00 |
March | 1147.46 | 523.99 | 623.47 | 1824.63 | 631.70 | 0.00 | 0.00 | 0.00 |
April | 1263.02 | 584.82 | 678.20 | 2192.88 | 462.53 | 0.00 | 0.00 | 0.00 |
May | 1151.40 | 443.24 | 708.17 | 2194.50 | 260.16 | 0.00 | 0.00 | 0.00 |
June | 975.59 | 273.66 | 701.93 | 1971.67 | 131.25 | 0.00 | 0.00 | 0.00 |
July | 1090.31 | 337.31 | 753.00 | 2267.51 | 183.01 | 0.00 | 0.00 | 0.00 |
August | 1087.83 | 354.52 | 733.31 | 2169.51 | 139.03 | 0.00 | 0.00 | 0.00 |
September | 927.98 | 273.63 | 654.35 | 1901.04 | 182.52 | 0.00 | 0.00 | 0.00 |
October | 923.17 | 359.88 | 563.29 | 1750.26 | 291.88 | 0.00 | 0.00 | 0.00 |
November | 761.52 | 279.33 | 482.19 | 1313.57 | 469.10 | 0.00 | 0.00 | 0.00 |
December | 762.88 | 341.08 | 421.80 | 1164.65 | 735.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 979.56 | 375.42 | 604.15 | 1776.26 | 418.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 736.86 | 273.63 | 419.19 | 1069.03 | 131.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1263.02 | 584.82 | 753.00 | 2267.51 | 827.95 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273732E+09 | 0.00 | 0.273732E+09 | 0.277892E+09 | 0.726988E+09 |
February | 0.292651E+09 | 0.00 | 0.292651E+09 | 0.385442E+09 | 0.547231E+09 |
March | 0.386400E+09 | 0.00 | 0.386400E+09 | 0.517063E+09 | 0.496232E+09 |
April | 0.419012E+09 | 1882250.16 | 0.417130E+09 | 0.703345E+09 | 0.302129E+09 |
May | 0.494441E+09 | 22117471.28 | 0.472323E+09 | 0.101956E+10 | 0.158722E+09 |
June | 0.511131E+09 | 36802961.59 | 0.474328E+09 | 0.113452E+10 | 67030866.23 |
July | 0.534488E+09 | 26190968.73 | 0.508297E+09 | 0.123781E+10 | 0.107078E+09 |
August | 0.473030E+09 | 4350573.31 | 0.468679E+09 | 0.103428E+10 | 77084989.64 |
September | 0.406098E+09 | 32126.15 | 0.406066E+09 | 0.932829E+09 | 0.112910E+09 |
October | 0.351551E+09 | 0.00 | 0.351551E+09 | 0.709311E+09 | 0.186479E+09 |
November | 0.295815E+09 | 0.00 | 0.295815E+09 | 0.475596E+09 | 0.362951E+09 |
December | 0.270756E+09 | 0.00 | 0.270756E+09 | 0.311199E+09 | 0.631520E+09 |
Annual Sum or Average | 0.470911E+10 | 91376351.23 | 0.461773E+10 | 0.873884E+10 | 0.377636E+10 |
Minimum of Months | 0.270756E+09 | 0.00 | 0.270756E+09 | 0.277892E+09 | 67030866.23 |
Maximum of Months | 0.534488E+09 | 36802961.59 | 0.508297E+09 | 0.123781E+10 | 0.726988E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273732E+09 | 0.00 | 0.273732E+09 | 0.277892E+09 | 0.726988E+09 |
February | 0.292650E+09 | 0.00 | 0.292650E+09 | 0.385442E+09 | 0.547231E+09 |
March | 0.386400E+09 | 0.00 | 0.386400E+09 | 0.517062E+09 | 0.496232E+09 |
April | 0.419012E+09 | 1882247.90 | 0.417130E+09 | 0.703345E+09 | 0.302129E+09 |
May | 0.494440E+09 | 22117444.74 | 0.472323E+09 | 0.101956E+10 | 0.158722E+09 |
June | 0.511131E+09 | 36802917.43 | 0.474328E+09 | 0.113452E+10 | 67030787.37 |
July | 0.534488E+09 | 26190937.31 | 0.508297E+09 | 0.123781E+10 | 0.107078E+09 |
August | 0.473029E+09 | 4350568.09 | 0.468679E+09 | 0.103428E+10 | 77084890.14 |
September | 0.406098E+09 | 32126.11 | 0.406066E+09 | 0.932828E+09 | 0.112910E+09 |
October | 0.351551E+09 | 0.00 | 0.351551E+09 | 0.709311E+09 | 0.186479E+09 |
November | 0.295815E+09 | 0.00 | 0.295815E+09 | 0.475596E+09 | 0.362951E+09 |
December | 0.270755E+09 | 0.00 | 0.270755E+09 | 0.311198E+09 | 0.631520E+09 |
Annual Sum or Average | 0.470910E+10 | 91376241.58 | 0.461773E+10 | 0.873884E+10 | 0.377636E+10 |
Minimum of Months | 0.270755E+09 | 0.00 | 0.270755E+09 | 0.277892E+09 | 67030787.37 |
Maximum of Months | 0.534488E+09 | 36802917.43 | 0.508297E+09 | 0.123781E+10 | 0.726988E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273732E+09 | 0.00 | 0.273732E+09 | 0.277892E+09 | 0.726988E+09 |
February | 0.292651E+09 | 0.00 | 0.292651E+09 | 0.385442E+09 | 0.547231E+09 |
March | 0.386400E+09 | 0.00 | 0.386400E+09 | 0.517063E+09 | 0.496232E+09 |
April | 0.419012E+09 | 1882250.16 | 0.417130E+09 | 0.703345E+09 | 0.302129E+09 |
May | 0.494441E+09 | 22117471.28 | 0.472323E+09 | 0.101956E+10 | 0.158722E+09 |
June | 0.511131E+09 | 36802961.59 | 0.474328E+09 | 0.113452E+10 | 67030866.23 |
July | 0.534488E+09 | 26190968.73 | 0.508297E+09 | 0.123781E+10 | 0.107078E+09 |
August | 0.473030E+09 | 4350573.31 | 0.468679E+09 | 0.103428E+10 | 77084989.64 |
September | 0.406098E+09 | 32126.15 | 0.406066E+09 | 0.932829E+09 | 0.112910E+09 |
October | 0.351551E+09 | 0.00 | 0.351551E+09 | 0.709311E+09 | 0.186479E+09 |
November | 0.295815E+09 | 0.00 | 0.295815E+09 | 0.475596E+09 | 0.362951E+09 |
December | 0.270756E+09 | 0.00 | 0.270756E+09 | 0.311199E+09 | 0.631520E+09 |
Annual Sum or Average | 0.470911E+10 | 91376351.23 | 0.461773E+10 | 0.873884E+10 | 0.377636E+10 |
Minimum of Months | 0.270756E+09 | 0.00 | 0.270756E+09 | 0.277892E+09 | 67030866.23 |
Maximum of Months | 0.534488E+09 | 36802961.59 | 0.508297E+09 | 0.123781E+10 | 0.726988E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273732E+09 | 0.00 | 0.273732E+09 | 0.277892E+09 | 0.726988E+09 |
February | 0.292650E+09 | 0.00 | 0.292650E+09 | 0.385442E+09 | 0.547231E+09 |
March | 0.386400E+09 | 0.00 | 0.386400E+09 | 0.517062E+09 | 0.496232E+09 |
April | 0.419012E+09 | 1882247.90 | 0.417130E+09 | 0.703345E+09 | 0.302129E+09 |
May | 0.494440E+09 | 22117444.74 | 0.472323E+09 | 0.101956E+10 | 0.158722E+09 |
June | 0.511131E+09 | 36802917.43 | 0.474328E+09 | 0.113452E+10 | 67030787.37 |
July | 0.534488E+09 | 26190937.31 | 0.508297E+09 | 0.123781E+10 | 0.107078E+09 |
August | 0.473029E+09 | 4350568.09 | 0.468679E+09 | 0.103428E+10 | 77084890.14 |
September | 0.406098E+09 | 32126.11 | 0.406066E+09 | 0.932828E+09 | 0.112910E+09 |
October | 0.351551E+09 | 0.00 | 0.351551E+09 | 0.709311E+09 | 0.186479E+09 |
November | 0.295815E+09 | 0.00 | 0.295815E+09 | 0.475596E+09 | 0.362951E+09 |
December | 0.270755E+09 | 0.00 | 0.270755E+09 | 0.311198E+09 | 0.631520E+09 |
Annual Sum or Average | 0.470910E+10 | 91376241.58 | 0.461773E+10 | 0.873884E+10 | 0.377636E+10 |
Minimum of Months | 0.270755E+09 | 0.00 | 0.270755E+09 | 0.277892E+09 | 67030787.37 |
Maximum of Months | 0.534488E+09 | 36802917.43 | 0.508297E+09 | 0.123781E+10 | 0.726988E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.273721E+09 | 0.00 | 0.273721E+09 | 0.277881E+09 | 0.726958E+09 |
February | 0.292639E+09 | 0.00 | 0.292639E+09 | 0.385427E+09 | 0.547209E+09 |
March | 0.386385E+09 | 0.00 | 0.386385E+09 | 0.517042E+09 | 0.496212E+09 |
April | 0.418995E+09 | 1882174.30 | 0.417113E+09 | 0.703317E+09 | 0.302117E+09 |
May | 0.494421E+09 | 22116579.85 | 0.472304E+09 | 0.101952E+10 | 0.158716E+09 |
June | 0.511110E+09 | 36801478.27 | 0.474309E+09 | 0.113447E+10 | 67028164.59 |
July | 0.534467E+09 | 26189913.12 | 0.508277E+09 | 0.123776E+10 | 0.107073E+09 |
August | 0.473011E+09 | 4350397.96 | 0.468660E+09 | 0.103424E+10 | 77081882.78 |
September | 0.406082E+09 | 32124.86 | 0.406050E+09 | 0.932791E+09 | 0.112906E+09 |
October | 0.351537E+09 | 0.00 | 0.351537E+09 | 0.709282E+09 | 0.186471E+09 |
November | 0.295803E+09 | 0.00 | 0.295803E+09 | 0.475577E+09 | 0.362936E+09 |
December | 0.270745E+09 | 0.00 | 0.270745E+09 | 0.311186E+09 | 0.631495E+09 |
Annual Sum or Average | 0.470892E+10 | 91372668.36 | 0.461754E+10 | 0.873849E+10 | 0.377620E+10 |
Minimum of Months | 0.270745E+09 | 0.00 | 0.270745E+09 | 0.277881E+09 | 67028164.59 |
Maximum of Months | 0.534467E+09 | 36801478.27 | 0.508277E+09 | 0.123776E+10 | 0.726958E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.732330E+09 | 0.350831E+09 | 0.381499E+09 | 0.104047E+10 | 0.755473E+09 |
February | 0.763767E+09 | 0.353549E+09 | 0.410218E+09 | 0.118483E+10 | 0.564828E+09 |
March | 0.103241E+10 | 0.488080E+09 | 0.544332E+09 | 0.162003E+10 | 0.498473E+09 |
April | 0.108429E+10 | 0.483803E+09 | 0.600482E+09 | 0.190959E+10 | 0.323821E+09 |
May | 0.105997E+10 | 0.422105E+09 | 0.637865E+09 | 0.204685E+10 | 0.171927E+09 |
June | 0.101246E+10 | 0.388878E+09 | 0.623580E+09 | 0.205778E+10 | 69770321.05 |
July | 0.107499E+10 | 0.387663E+09 | 0.687325E+09 | 0.225610E+10 | 0.113617E+09 |
August | 0.982983E+09 | 0.328689E+09 | 0.654294E+09 | 0.200519E+10 | 69479400.10 |
September | 0.917090E+09 | 0.331532E+09 | 0.585558E+09 | 0.189479E+10 | 0.126467E+09 |
October | 0.872282E+09 | 0.375658E+09 | 0.496624E+09 | 0.167468E+10 | 0.201128E+09 |
November | 0.685133E+09 | 0.273189E+09 | 0.411944E+09 | 0.117134E+10 | 0.366643E+09 |
December | 0.571887E+09 | 0.201904E+09 | 0.369983E+09 | 0.833097E+09 | 0.642151E+09 |
Annual Sum or Average | 0.107896E+11 | 0.438588E+10 | 0.640370E+10 | 0.196947E+11 | 0.390378E+10 |
Minimum of Months | 0.571887E+09 | 0.201904E+09 | 0.369983E+09 | 0.833097E+09 | 69479400.10 |
Maximum of Months | 0.108429E+10 | 0.488080E+09 | 0.687325E+09 | 0.225610E+10 | 0.755473E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.732330E+09 | 0.350831E+09 | 0.381499E+09 | 0.104047E+10 | 0.755473E+09 |
February | 0.763767E+09 | 0.353549E+09 | 0.410218E+09 | 0.118483E+10 | 0.564828E+09 |
March | 0.103241E+10 | 0.488080E+09 | 0.544332E+09 | 0.162003E+10 | 0.498473E+09 |
April | 0.108429E+10 | 0.483803E+09 | 0.600482E+09 | 0.190959E+10 | 0.323821E+09 |
May | 0.105997E+10 | 0.422105E+09 | 0.637865E+09 | 0.204685E+10 | 0.171927E+09 |
June | 0.101246E+10 | 0.388878E+09 | 0.623580E+09 | 0.205778E+10 | 69770321.05 |
July | 0.107499E+10 | 0.387663E+09 | 0.687325E+09 | 0.225610E+10 | 0.113617E+09 |
August | 0.982983E+09 | 0.328689E+09 | 0.654294E+09 | 0.200519E+10 | 69479400.10 |
September | 0.917090E+09 | 0.331532E+09 | 0.585558E+09 | 0.189479E+10 | 0.126467E+09 |
October | 0.872282E+09 | 0.375658E+09 | 0.496624E+09 | 0.167468E+10 | 0.201128E+09 |
November | 0.685133E+09 | 0.273189E+09 | 0.411944E+09 | 0.117134E+10 | 0.366643E+09 |
December | 0.571887E+09 | 0.201904E+09 | 0.369983E+09 | 0.833097E+09 | 0.642151E+09 |
Annual Sum or Average | 0.107896E+11 | 0.438588E+10 | 0.640370E+10 | 0.196947E+11 | 0.390378E+10 |
Minimum of Months | 0.571887E+09 | 0.201904E+09 | 0.369983E+09 | 0.833097E+09 | 69479400.10 |
Maximum of Months | 0.108429E+10 | 0.488080E+09 | 0.687325E+09 | 0.225610E+10 | 0.755473E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.732316E+09 | 0.350825E+09 | 0.381492E+09 | 0.104045E+10 | 0.755459E+09 |
February | 0.763753E+09 | 0.353543E+09 | 0.410210E+09 | 0.118480E+10 | 0.564818E+09 |
March | 0.103239E+10 | 0.488071E+09 | 0.544322E+09 | 0.162000E+10 | 0.498464E+09 |
April | 0.108427E+10 | 0.483794E+09 | 0.600471E+09 | 0.190955E+10 | 0.323815E+09 |
May | 0.105995E+10 | 0.422097E+09 | 0.637853E+09 | 0.204681E+10 | 0.171923E+09 |
June | 0.101244E+10 | 0.388871E+09 | 0.623569E+09 | 0.205774E+10 | 69769046.20 |
July | 0.107497E+10 | 0.387656E+09 | 0.687312E+09 | 0.225605E+10 | 0.113615E+09 |
August | 0.982965E+09 | 0.328683E+09 | 0.654282E+09 | 0.200516E+10 | 69478130.56 |
September | 0.917073E+09 | 0.331525E+09 | 0.585547E+09 | 0.189476E+10 | 0.126464E+09 |
October | 0.872266E+09 | 0.375651E+09 | 0.496615E+09 | 0.167465E+10 | 0.201124E+09 |
November | 0.685121E+09 | 0.273184E+09 | 0.411937E+09 | 0.117132E+10 | 0.366637E+09 |
December | 0.571876E+09 | 0.201900E+09 | 0.369976E+09 | 0.833082E+09 | 0.642140E+09 |
Annual Sum or Average | 0.107894E+11 | 0.438580E+10 | 0.640359E+10 | 0.196944E+11 | 0.390371E+10 |
Minimum of Months | 0.571876E+09 | 0.201900E+09 | 0.369976E+09 | 0.833082E+09 | 69478130.56 |
Maximum of Months | 0.108427E+10 | 0.488071E+09 | 0.687312E+09 | 0.225605E+10 | 0.755459E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128653E+10 | 0.835827E+09 | 0.450699E+09 | 0.205190E+10 | 0.706115E+09 |
February | 0.105122E+10 | 0.608260E+09 | 0.442960E+09 | 0.177257E+10 | 0.543983E+09 |
March | 0.893573E+09 | 0.377796E+09 | 0.515778E+09 | 0.152775E+10 | 0.494017E+09 |
April | 0.588013E+09 | 0.103115E+09 | 0.484898E+09 | 0.110490E+10 | 0.319310E+09 |
May | 0.486904E+09 | 10534055.38 | 0.476370E+09 | 0.100817E+10 | 0.157552E+09 |
June | 0.449246E+09 | 847802.49 | 0.448398E+09 | 0.100062E+10 | 67716800.96 |
July | 0.497055E+09 | 4607261.48 | 0.492447E+09 | 0.115704E+10 | 0.106366E+09 |
August | 0.564141E+09 | 47605303.16 | 0.516536E+09 | 0.124561E+10 | 78539212.30 |
September | 0.698880E+09 | 0.171262E+09 | 0.527618E+09 | 0.154507E+10 | 0.124042E+09 |
October | 0.993136E+09 | 0.465949E+09 | 0.527187E+09 | 0.194927E+10 | 0.217336E+09 |
November | 0.109352E+10 | 0.610305E+09 | 0.483215E+09 | 0.192119E+10 | 0.375021E+09 |
December | 0.123985E+10 | 0.782028E+09 | 0.457823E+09 | 0.202221E+10 | 0.630340E+09 |
Annual Sum or Average | 0.984206E+10 | 0.401814E+10 | 0.582393E+10 | 0.183063E+11 | 0.382034E+10 |
Minimum of Months | 0.449246E+09 | 847802.49 | 0.442960E+09 | 0.100062E+10 | 67716800.96 |
Maximum of Months | 0.128653E+10 | 0.835827E+09 | 0.527618E+09 | 0.205190E+10 | 0.706115E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128652E+10 | 0.835826E+09 | 0.450698E+09 | 0.205190E+10 | 0.706115E+09 |
February | 0.105122E+10 | 0.608260E+09 | 0.442960E+09 | 0.177256E+10 | 0.543983E+09 |
March | 0.893572E+09 | 0.377795E+09 | 0.515777E+09 | 0.152775E+10 | 0.494016E+09 |
April | 0.588013E+09 | 0.103115E+09 | 0.484898E+09 | 0.110490E+10 | 0.319310E+09 |
May | 0.486904E+09 | 10534042.74 | 0.476370E+09 | 0.100817E+10 | 0.157552E+09 |
June | 0.449246E+09 | 847801.48 | 0.448398E+09 | 0.100062E+10 | 67716722.18 |
July | 0.497054E+09 | 4607255.96 | 0.492447E+09 | 0.115704E+10 | 0.106366E+09 |
August | 0.564141E+09 | 47605246.03 | 0.516535E+09 | 0.124561E+10 | 78539115.52 |
September | 0.698879E+09 | 0.171262E+09 | 0.527617E+09 | 0.154507E+10 | 0.124042E+09 |
October | 0.993135E+09 | 0.465948E+09 | 0.527186E+09 | 0.194927E+10 | 0.217336E+09 |
November | 0.109352E+10 | 0.610304E+09 | 0.483214E+09 | 0.192119E+10 | 0.375021E+09 |
December | 0.123985E+10 | 0.782027E+09 | 0.457823E+09 | 0.202220E+10 | 0.630340E+09 |
Annual Sum or Average | 0.984205E+10 | 0.401813E+10 | 0.582392E+10 | 0.183063E+11 | 0.382034E+10 |
Minimum of Months | 0.449246E+09 | 847801.48 | 0.442960E+09 | 0.100062E+10 | 67716722.18 |
Maximum of Months | 0.128652E+10 | 0.835826E+09 | 0.527617E+09 | 0.205190E+10 | 0.706115E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128653E+10 | 0.835827E+09 | 0.450699E+09 | 0.205190E+10 | 0.706115E+09 |
February | 0.105122E+10 | 0.608260E+09 | 0.442960E+09 | 0.177257E+10 | 0.543983E+09 |
March | 0.893573E+09 | 0.377796E+09 | 0.515778E+09 | 0.152775E+10 | 0.494017E+09 |
April | 0.588013E+09 | 0.103115E+09 | 0.484898E+09 | 0.110490E+10 | 0.319310E+09 |
May | 0.486904E+09 | 10534055.38 | 0.476370E+09 | 0.100817E+10 | 0.157552E+09 |
June | 0.449246E+09 | 847802.49 | 0.448398E+09 | 0.100062E+10 | 67716800.96 |
July | 0.497055E+09 | 4607261.48 | 0.492447E+09 | 0.115704E+10 | 0.106366E+09 |
August | 0.564141E+09 | 47605303.16 | 0.516536E+09 | 0.124561E+10 | 78539212.30 |
September | 0.698880E+09 | 0.171262E+09 | 0.527618E+09 | 0.154507E+10 | 0.124042E+09 |
October | 0.993136E+09 | 0.465949E+09 | 0.527187E+09 | 0.194927E+10 | 0.217336E+09 |
November | 0.109352E+10 | 0.610305E+09 | 0.483215E+09 | 0.192119E+10 | 0.375021E+09 |
December | 0.123985E+10 | 0.782028E+09 | 0.457823E+09 | 0.202221E+10 | 0.630340E+09 |
Annual Sum or Average | 0.984206E+10 | 0.401814E+10 | 0.582393E+10 | 0.183063E+11 | 0.382034E+10 |
Minimum of Months | 0.449246E+09 | 847802.49 | 0.442960E+09 | 0.100062E+10 | 67716800.96 |
Maximum of Months | 0.128653E+10 | 0.835827E+09 | 0.527618E+09 | 0.205190E+10 | 0.706115E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128652E+10 | 0.835826E+09 | 0.450698E+09 | 0.205190E+10 | 0.706115E+09 |
February | 0.105122E+10 | 0.608260E+09 | 0.442960E+09 | 0.177256E+10 | 0.543983E+09 |
March | 0.893572E+09 | 0.377795E+09 | 0.515777E+09 | 0.152775E+10 | 0.494016E+09 |
April | 0.588013E+09 | 0.103115E+09 | 0.484898E+09 | 0.110490E+10 | 0.319310E+09 |
May | 0.486904E+09 | 10534042.74 | 0.476370E+09 | 0.100817E+10 | 0.157552E+09 |
June | 0.449246E+09 | 847801.48 | 0.448398E+09 | 0.100062E+10 | 67716722.18 |
July | 0.497054E+09 | 4607255.96 | 0.492447E+09 | 0.115704E+10 | 0.106366E+09 |
August | 0.564141E+09 | 47605246.03 | 0.516535E+09 | 0.124561E+10 | 78539115.52 |
September | 0.698879E+09 | 0.171262E+09 | 0.527617E+09 | 0.154507E+10 | 0.124042E+09 |
October | 0.993135E+09 | 0.465948E+09 | 0.527186E+09 | 0.194927E+10 | 0.217336E+09 |
November | 0.109352E+10 | 0.610304E+09 | 0.483214E+09 | 0.192119E+10 | 0.375021E+09 |
December | 0.123985E+10 | 0.782027E+09 | 0.457823E+09 | 0.202220E+10 | 0.630340E+09 |
Annual Sum or Average | 0.984205E+10 | 0.401813E+10 | 0.582392E+10 | 0.183063E+11 | 0.382034E+10 |
Minimum of Months | 0.449246E+09 | 847801.48 | 0.442960E+09 | 0.100062E+10 | 67716722.18 |
Maximum of Months | 0.128652E+10 | 0.835826E+09 | 0.527617E+09 | 0.205190E+10 | 0.706115E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128647E+10 | 0.835793E+09 | 0.450681E+09 | 0.205182E+10 | 0.706086E+09 |
February | 0.105118E+10 | 0.608236E+09 | 0.442942E+09 | 0.177250E+10 | 0.543961E+09 |
March | 0.893537E+09 | 0.377780E+09 | 0.515757E+09 | 0.152769E+10 | 0.493997E+09 |
April | 0.587989E+09 | 0.103111E+09 | 0.484879E+09 | 0.110486E+10 | 0.319297E+09 |
May | 0.486885E+09 | 10533630.81 | 0.476351E+09 | 0.100813E+10 | 0.157546E+09 |
June | 0.449228E+09 | 847768.32 | 0.448380E+09 | 0.100058E+10 | 67714071.67 |
July | 0.497034E+09 | 4607075.79 | 0.492427E+09 | 0.115699E+10 | 0.106362E+09 |
August | 0.564118E+09 | 47603384.45 | 0.516515E+09 | 0.124556E+10 | 78536046.82 |
September | 0.698851E+09 | 0.171255E+09 | 0.527596E+09 | 0.154501E+10 | 0.124037E+09 |
October | 0.993096E+09 | 0.465930E+09 | 0.527166E+09 | 0.194919E+10 | 0.217328E+09 |
November | 0.109348E+10 | 0.610280E+09 | 0.483195E+09 | 0.192111E+10 | 0.375006E+09 |
December | 0.123980E+10 | 0.781996E+09 | 0.457805E+09 | 0.202213E+10 | 0.630315E+09 |
Annual Sum or Average | 0.984167E+10 | 0.401797E+10 | 0.582369E+10 | 0.183056E+11 | 0.382019E+10 |
Minimum of Months | 0.449228E+09 | 847768.32 | 0.442942E+09 | 0.100058E+10 | 67714071.67 |
Maximum of Months | 0.128647E+10 | 0.835793E+09 | 0.527596E+09 | 0.205182E+10 | 0.706086E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.657877E+09 | 0.283620E+09 | 0.374257E+09 | 0.924142E+09 | 0.889825E+09 |
February | 0.743045E+09 | 0.336271E+09 | 0.406775E+09 | 0.116099E+10 | 0.715447E+09 |
March | 0.102446E+10 | 0.467822E+09 | 0.556638E+09 | 0.160996E+10 | 0.688505E+09 |
April | 0.109126E+10 | 0.505288E+09 | 0.585970E+09 | 0.187201E+10 | 0.480179E+09 |
May | 0.102798E+10 | 0.395726E+09 | 0.632258E+09 | 0.197322E+10 | 0.252409E+09 |
June | 0.842920E+09 | 0.236447E+09 | 0.606473E+09 | 0.169640E+10 | 0.138356E+09 |
July | 0.973440E+09 | 0.301152E+09 | 0.672288E+09 | 0.200695E+10 | 0.202818E+09 |
August | 0.971227E+09 | 0.316521E+09 | 0.654705E+09 | 0.189329E+10 | 0.193693E+09 |
September | 0.801782E+09 | 0.236420E+09 | 0.565362E+09 | 0.164643E+10 | 0.177629E+09 |
October | 0.824213E+09 | 0.321304E+09 | 0.502909E+09 | 0.155409E+10 | 0.309102E+09 |
November | 0.657957E+09 | 0.241343E+09 | 0.416615E+09 | 0.110150E+10 | 0.528296E+09 |
December | 0.681106E+09 | 0.304517E+09 | 0.376589E+09 | 0.991484E+09 | 0.861588E+09 |
Annual Sum or Average | 0.102973E+11 | 0.394643E+10 | 0.635084E+10 | 0.184305E+11 | 0.543785E+10 |
Minimum of Months | 0.657877E+09 | 0.236420E+09 | 0.374257E+09 | 0.924142E+09 | 0.138356E+09 |
Maximum of Months | 0.109126E+10 | 0.505288E+09 | 0.672288E+09 | 0.200695E+10 | 0.889825E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.657877E+09 | 0.283620E+09 | 0.374257E+09 | 0.924142E+09 | 0.889825E+09 |
February | 0.743045E+09 | 0.336271E+09 | 0.406775E+09 | 0.116099E+10 | 0.715447E+09 |
March | 0.102446E+10 | 0.467822E+09 | 0.556638E+09 | 0.160996E+10 | 0.688505E+09 |
April | 0.109126E+10 | 0.505288E+09 | 0.585970E+09 | 0.187201E+10 | 0.480179E+09 |
May | 0.102798E+10 | 0.395726E+09 | 0.632258E+09 | 0.197322E+10 | 0.252409E+09 |
June | 0.842920E+09 | 0.236447E+09 | 0.606473E+09 | 0.169640E+10 | 0.138356E+09 |
July | 0.973440E+09 | 0.301152E+09 | 0.672288E+09 | 0.200695E+10 | 0.202818E+09 |
August | 0.971227E+09 | 0.316521E+09 | 0.654705E+09 | 0.189329E+10 | 0.193693E+09 |
September | 0.801782E+09 | 0.236420E+09 | 0.565362E+09 | 0.164643E+10 | 0.177629E+09 |
October | 0.824213E+09 | 0.321304E+09 | 0.502909E+09 | 0.155409E+10 | 0.309102E+09 |
November | 0.657957E+09 | 0.241343E+09 | 0.416615E+09 | 0.110150E+10 | 0.528296E+09 |
December | 0.681106E+09 | 0.304517E+09 | 0.376589E+09 | 0.991484E+09 | 0.861588E+09 |
Annual Sum or Average | 0.102973E+11 | 0.394643E+10 | 0.635084E+10 | 0.184305E+11 | 0.543785E+10 |
Minimum of Months | 0.657877E+09 | 0.236420E+09 | 0.374257E+09 | 0.924142E+09 | 0.138356E+09 |
Maximum of Months | 0.109126E+10 | 0.505288E+09 | 0.672288E+09 | 0.200695E+10 | 0.889825E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.657865E+09 | 0.283615E+09 | 0.374250E+09 | 0.924126E+09 | 0.889809E+09 |
February | 0.743032E+09 | 0.336264E+09 | 0.406767E+09 | 0.116097E+10 | 0.715434E+09 |
March | 0.102444E+10 | 0.467814E+09 | 0.556628E+09 | 0.160993E+10 | 0.688492E+09 |
April | 0.109124E+10 | 0.505279E+09 | 0.585959E+09 | 0.187197E+10 | 0.480170E+09 |
May | 0.102796E+10 | 0.395719E+09 | 0.632246E+09 | 0.197318E+10 | 0.252404E+09 |
June | 0.842904E+09 | 0.236442E+09 | 0.606462E+09 | 0.169637E+10 | 0.138353E+09 |
July | 0.973423E+09 | 0.301147E+09 | 0.672276E+09 | 0.200691E+10 | 0.202814E+09 |
August | 0.971209E+09 | 0.316515E+09 | 0.654693E+09 | 0.189326E+10 | 0.193689E+09 |
September | 0.801768E+09 | 0.236416E+09 | 0.565352E+09 | 0.164640E+10 | 0.177626E+09 |
October | 0.824198E+09 | 0.321298E+09 | 0.502900E+09 | 0.155406E+10 | 0.309096E+09 |
November | 0.657945E+09 | 0.241338E+09 | 0.416607E+09 | 0.110148E+10 | 0.528287E+09 |
December | 0.681093E+09 | 0.304512E+09 | 0.376582E+09 | 0.991466E+09 | 0.861572E+09 |
Annual Sum or Average | 0.102971E+11 | 0.394636E+10 | 0.635072E+10 | 0.184301E+11 | 0.543775E+10 |
Minimum of Months | 0.657865E+09 | 0.236416E+09 | 0.374250E+09 | 0.924126E+09 | 0.138353E+09 |
Maximum of Months | 0.109124E+10 | 0.505279E+09 | 0.672276E+09 | 0.200691E+10 | 0.889809E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136865E+10 | 0.00 | 0.136865E+10 | 0.151196E+10 | 0.323128E+10 |
February | 0.146324E+10 | 0.00 | 0.146324E+10 | 0.203846E+10 | 0.241746E+10 |
March | 0.193198E+10 | 0.00 | 0.193198E+10 | 0.265825E+10 | 0.225505E+10 |
April | 0.209504E+10 | 9411137.01 | 0.208563E+10 | 0.356958E+10 | 0.143122E+10 |
May | 0.247217E+10 | 0.110586E+09 | 0.236159E+10 | 0.509119E+10 | 0.793860E+09 |
June | 0.255562E+10 | 0.184013E+09 | 0.237161E+10 | 0.567089E+10 | 0.355628E+09 |
July | 0.267241E+10 | 0.130953E+09 | 0.254146E+10 | 0.622349E+10 | 0.523044E+09 |
August | 0.236512E+10 | 21752603.50 | 0.234337E+10 | 0.526265E+10 | 0.344632E+09 |
September | 0.203047E+10 | 160628.81 | 0.203031E+10 | 0.468131E+10 | 0.558543E+09 |
October | 0.175774E+10 | 0.00 | 0.175774E+10 | 0.358210E+10 | 0.901402E+09 |
November | 0.147906E+10 | 0.00 | 0.147906E+10 | 0.244730E+10 | 0.163696E+10 |
December | 0.135376E+10 | 0.00 | 0.135376E+10 | 0.168146E+10 | 0.275700E+10 |
Annual Sum or Average | 0.235452E+11 | 0.456876E+09 | 0.230884E+11 | 0.444187E+11 | 0.172061E+11 |
Minimum of Months | 0.135376E+10 | 0.00 | 0.135376E+10 | 0.151196E+10 | 0.344632E+09 |
Maximum of Months | 0.267241E+10 | 0.184013E+09 | 0.254146E+10 | 0.622349E+10 | 0.323128E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219697E+10 | 0.105248E+10 | 0.114448E+10 | 0.311296E+10 | 0.214057E+10 |
February | 0.229128E+10 | 0.106064E+10 | 0.123064E+10 | 0.352626E+10 | 0.159875E+10 |
March | 0.309720E+10 | 0.146422E+10 | 0.163298E+10 | 0.477131E+10 | 0.147673E+10 |
April | 0.325282E+10 | 0.145139E+10 | 0.180143E+10 | 0.562251E+10 | 0.101852E+10 |
May | 0.317988E+10 | 0.126630E+10 | 0.191358E+10 | 0.604084E+10 | 0.547100E+09 |
June | 0.303734E+10 | 0.116662E+10 | 0.187072E+10 | 0.606835E+10 | 0.252034E+09 |
July | 0.322493E+10 | 0.116298E+10 | 0.206195E+10 | 0.668081E+10 | 0.387280E+09 |
August | 0.294892E+10 | 0.986056E+09 | 0.196286E+10 | 0.594027E+10 | 0.250655E+09 |
September | 0.275124E+10 | 0.994584E+09 | 0.175666E+10 | 0.559760E+10 | 0.404410E+09 |
October | 0.261682E+10 | 0.112696E+10 | 0.148986E+10 | 0.494772E+10 | 0.649167E+09 |
November | 0.205538E+10 | 0.819560E+09 | 0.123582E+10 | 0.346525E+10 | 0.108659E+10 |
December | 0.171564E+10 | 0.605705E+09 | 0.110994E+10 | 0.248471E+10 | 0.184147E+10 |
Annual Sum or Average | 0.323684E+11 | 0.131575E+11 | 0.192109E+11 | 0.582586E+11 | 0.116533E+11 |
Minimum of Months | 0.171564E+10 | 0.605705E+09 | 0.110994E+10 | 0.248471E+10 | 0.250655E+09 |
Maximum of Months | 0.325282E+10 | 0.146422E+10 | 0.206195E+10 | 0.668081E+10 | 0.214057E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643255E+10 | 0.417908E+10 | 0.225347E+10 | 0.101532E+11 | 0.345235E+10 |
February | 0.525604E+10 | 0.304127E+10 | 0.221477E+10 | 0.878100E+10 | 0.261953E+10 |
March | 0.446781E+10 | 0.188896E+10 | 0.257886E+10 | 0.756841E+10 | 0.239379E+10 |
April | 0.294003E+10 | 0.515568E+09 | 0.242446E+10 | 0.551449E+10 | 0.155641E+10 |
May | 0.243449E+10 | 52669640.00 | 0.238182E+10 | 0.503745E+10 | 0.775877E+09 |
June | 0.224620E+10 | 4238961.21 | 0.224196E+10 | 0.502769E+10 | 0.350457E+09 |
July | 0.248524E+10 | 23036028.87 | 0.246221E+10 | 0.582925E+10 | 0.513672E+09 |
August | 0.282067E+10 | 0.238024E+09 | 0.258265E+10 | 0.629104E+10 | 0.364718E+09 |
September | 0.349436E+10 | 0.856299E+09 | 0.263806E+10 | 0.767235E+10 | 0.632297E+09 |
October | 0.496562E+10 | 0.232972E+10 | 0.263590E+10 | 0.965082E+10 | 0.112463E+10 |
November | 0.546753E+10 | 0.305149E+10 | 0.241604E+10 | 0.951121E+10 | 0.184609E+10 |
December | 0.619918E+10 | 0.391009E+10 | 0.228909E+10 | 0.100280E+11 | 0.305781E+10 |
Annual Sum or Average | 0.492097E+11 | 0.200904E+11 | 0.291193E+11 | 0.910648E+11 | 0.186876E+11 |
Minimum of Months | 0.224620E+10 | 4238961.21 | 0.221477E+10 | 0.502769E+10 | 0.350457E+09 |
Maximum of Months | 0.643255E+10 | 0.417908E+10 | 0.263806E+10 | 0.101532E+11 | 0.345235E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197361E+10 | 0.850852E+09 | 0.112276E+10 | 0.285268E+10 | 0.234245E+10 |
February | 0.222911E+10 | 0.100880E+10 | 0.122031E+10 | 0.357901E+10 | 0.181952E+10 |
March | 0.307335E+10 | 0.140345E+10 | 0.166990E+10 | 0.492079E+10 | 0.174760E+10 |
April | 0.327374E+10 | 0.151585E+10 | 0.175789E+10 | 0.573470E+10 | 0.120741E+10 |
May | 0.308392E+10 | 0.118717E+10 | 0.189675E+10 | 0.593841E+10 | 0.687910E+09 |
June | 0.252873E+10 | 0.709333E+09 | 0.181940E+10 | 0.517075E+10 | 0.326197E+09 |
July | 0.292029E+10 | 0.903447E+09 | 0.201684E+10 | 0.613976E+10 | 0.472678E+09 |
August | 0.291365E+10 | 0.949554E+09 | 0.196410E+10 | 0.586618E+10 | 0.360291E+09 |
September | 0.240532E+10 | 0.709254E+09 | 0.169607E+10 | 0.498292E+10 | 0.466329E+09 |
October | 0.247261E+10 | 0.963901E+09 | 0.150871E+10 | 0.472989E+10 | 0.783436E+09 |
November | 0.197385E+10 | 0.724020E+09 | 0.124983E+10 | 0.342121E+10 | 0.126412E+10 |
December | 0.204330E+10 | 0.913543E+09 | 0.112975E+10 | 0.312157E+10 | 0.206184E+10 |
Annual Sum or Average | 0.308915E+11 | 0.118392E+11 | 0.190523E+11 | 0.564579E+11 | 0.135398E+11 |
Minimum of Months | 0.197361E+10 | 0.709254E+09 | 0.112276E+10 | 0.285268E+10 | 0.326197E+09 |
Maximum of Months | 0.327374E+10 | 0.151585E+10 | 0.201684E+10 | 0.613976E+10 | 0.234245E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136865E+10 | 0.00 | 0.136865E+10 | 0.155779E+10 | 0.301964E+10 |
February | 0.146324E+10 | 0.00 | 0.146324E+10 | 0.204932E+10 | 0.229446E+10 |
March | 0.193198E+10 | 0.00 | 0.193198E+10 | 0.263298E+10 | 0.217528E+10 |
April | 0.209504E+10 | 9411137.01 | 0.208563E+10 | 0.350482E+10 | 0.143194E+10 |
May | 0.247217E+10 | 0.110586E+09 | 0.236159E+10 | 0.500468E+10 | 0.820705E+09 |
June | 0.255562E+10 | 0.184013E+09 | 0.237161E+10 | 0.556933E+10 | 0.375793E+09 |
July | 0.267241E+10 | 0.130953E+09 | 0.254146E+10 | 0.611893E+10 | 0.564191E+09 |
August | 0.236512E+10 | 21752603.50 | 0.234337E+10 | 0.517633E+10 | 0.366180E+09 |
September | 0.203047E+10 | 160628.81 | 0.203031E+10 | 0.458581E+10 | 0.571888E+09 |
October | 0.175774E+10 | 0.00 | 0.175774E+10 | 0.352166E+10 | 0.910691E+09 |
November | 0.147906E+10 | 0.00 | 0.147906E+10 | 0.243762E+10 | 0.155682E+10 |
December | 0.135376E+10 | 0.00 | 0.135376E+10 | 0.170530E+10 | 0.260505E+10 |
Annual Sum or Average | 0.235452E+11 | 0.456876E+09 | 0.230884E+11 | 0.438646E+11 | 0.166926E+11 |
Minimum of Months | 0.135376E+10 | 0.00 | 0.135376E+10 | 0.155779E+10 | 0.366180E+09 |
Maximum of Months | 0.267241E+10 | 0.184013E+09 | 0.254146E+10 | 0.611893E+10 | 0.301964E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.219697E+10 | 0.105248E+10 | 0.114448E+10 | 0.315871E+10 | 0.202140E+10 |
February | 0.229128E+10 | 0.106064E+10 | 0.123064E+10 | 0.354849E+10 | 0.152691E+10 |
March | 0.309720E+10 | 0.146422E+10 | 0.163298E+10 | 0.476286E+10 | 0.143393E+10 |
April | 0.325282E+10 | 0.145139E+10 | 0.180143E+10 | 0.559106E+10 | 0.101451E+10 |
May | 0.317988E+10 | 0.126630E+10 | 0.191358E+10 | 0.599683E+10 | 0.558878E+09 |
June | 0.303734E+10 | 0.116662E+10 | 0.187072E+10 | 0.601860E+10 | 0.262046E+09 |
July | 0.322493E+10 | 0.116298E+10 | 0.206195E+10 | 0.662967E+10 | 0.408845E+09 |
August | 0.294892E+10 | 0.986056E+09 | 0.196286E+10 | 0.590205E+10 | 0.260501E+09 |
September | 0.275124E+10 | 0.994584E+09 | 0.175666E+10 | 0.555396E+10 | 0.410320E+09 |
October | 0.261682E+10 | 0.112696E+10 | 0.148986E+10 | 0.492359E+10 | 0.648968E+09 |
November | 0.205538E+10 | 0.819560E+09 | 0.123582E+10 | 0.347276E+10 | 0.103909E+10 |
December | 0.171564E+10 | 0.605705E+09 | 0.110994E+10 | 0.251471E+10 | 0.174854E+10 |
Annual Sum or Average | 0.323684E+11 | 0.131575E+11 | 0.192109E+11 | 0.580733E+11 | 0.113339E+11 |
Minimum of Months | 0.171564E+10 | 0.605705E+09 | 0.110994E+10 | 0.251471E+10 | 0.260501E+09 |
Maximum of Months | 0.325282E+10 | 0.146422E+10 | 0.206195E+10 | 0.662967E+10 | 0.202140E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643255E+10 | 0.417908E+10 | 0.225347E+10 | 0.101884E+11 | 0.327783E+10 |
February | 0.525604E+10 | 0.304127E+10 | 0.221477E+10 | 0.877944E+10 | 0.250947E+10 |
March | 0.446781E+10 | 0.188896E+10 | 0.257886E+10 | 0.752527E+10 | 0.232090E+10 |
April | 0.294003E+10 | 0.515568E+09 | 0.242446E+10 | 0.544477E+10 | 0.155431E+10 |
May | 0.243449E+10 | 52669640.00 | 0.238182E+10 | 0.494779E+10 | 0.801516E+09 |
June | 0.224620E+10 | 4238961.21 | 0.224196E+10 | 0.492406E+10 | 0.370884E+09 |
July | 0.248524E+10 | 23036028.87 | 0.246221E+10 | 0.572349E+10 | 0.557087E+09 |
August | 0.282067E+10 | 0.238024E+09 | 0.258265E+10 | 0.620060E+10 | 0.385121E+09 |
September | 0.349436E+10 | 0.856299E+09 | 0.263806E+10 | 0.758201E+10 | 0.645622E+09 |
October | 0.496562E+10 | 0.232972E+10 | 0.263590E+10 | 0.959252E+10 | 0.112166E+10 |
November | 0.546753E+10 | 0.305149E+10 | 0.241604E+10 | 0.949738E+10 | 0.177228E+10 |
December | 0.619918E+10 | 0.391009E+10 | 0.228909E+10 | 0.100322E+11 | 0.292247E+10 |
Annual Sum or Average | 0.492097E+11 | 0.200904E+11 | 0.291193E+11 | 0.904379E+11 | 0.182392E+11 |
Minimum of Months | 0.224620E+10 | 4238961.21 | 0.221477E+10 | 0.492406E+10 | 0.370884E+09 |
Maximum of Months | 0.643255E+10 | 0.417908E+10 | 0.263806E+10 | 0.101884E+11 | 0.327783E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197361E+10 | 0.850852E+09 | 0.112276E+10 | 0.286330E+10 | 0.221758E+10 |
February | 0.222911E+10 | 0.100880E+10 | 0.122031E+10 | 0.356968E+10 | 0.174492E+10 |
March | 0.307335E+10 | 0.140345E+10 | 0.166990E+10 | 0.488710E+10 | 0.169195E+10 |
April | 0.327374E+10 | 0.151585E+10 | 0.175789E+10 | 0.568394E+10 | 0.119888E+10 |
May | 0.308392E+10 | 0.118717E+10 | 0.189675E+10 | 0.587774E+10 | 0.696824E+09 |
June | 0.252873E+10 | 0.709333E+09 | 0.181940E+10 | 0.511056E+10 | 0.340196E+09 |
July | 0.292029E+10 | 0.903447E+09 | 0.201684E+10 | 0.607329E+10 | 0.490176E+09 |
August | 0.291365E+10 | 0.949554E+09 | 0.196410E+10 | 0.581081E+10 | 0.372368E+09 |
September | 0.240532E+10 | 0.709254E+09 | 0.169607E+10 | 0.492750E+10 | 0.473087E+09 |
October | 0.247261E+10 | 0.963901E+09 | 0.150871E+10 | 0.468790E+10 | 0.781779E+09 |
November | 0.197385E+10 | 0.724020E+09 | 0.124983E+10 | 0.340477E+10 | 0.121589E+10 |
December | 0.204330E+10 | 0.913543E+09 | 0.112975E+10 | 0.311939E+10 | 0.197070E+10 |
Annual Sum or Average | 0.308915E+11 | 0.118392E+11 | 0.190523E+11 | 0.560160E+11 | 0.131943E+11 |
Minimum of Months | 0.197361E+10 | 0.709254E+09 | 0.112276E+10 | 0.286330E+10 | 0.340196E+09 |
Maximum of Months | 0.327374E+10 | 0.151585E+10 | 0.201684E+10 | 0.607329E+10 | 0.221758E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 518.76 | 1357.12 | 511.00 | 0.00 | 511.00 | 0.00 | 0.00 |
February | 796.63 | 1131.01 | 604.84 | 0.00 | 604.84 | 0.00 | 0.00 |
March | 965.24 | 926.35 | 721.32 | 0.00 | 721.32 | 0.00 | 0.00 |
April | 1356.75 | 582.81 | 808.27 | 3.63 | 804.64 | 0.00 | 0.00 |
May | 1903.29 | 296.30 | 923.01 | 41.29 | 881.72 | 0.00 | 0.00 |
June | 2188.48 | 129.30 | 985.97 | 70.99 | 914.98 | 0.00 | 0.00 |
July | 2310.71 | 199.89 | 997.77 | 48.89 | 948.87 | 0.00 | 0.00 |
August | 1930.76 | 143.90 | 883.04 | 8.12 | 874.92 | 0.00 | 0.00 |
September | 1799.42 | 217.80 | 783.36 | 0.06 | 783.30 | 0.00 | 0.00 |
October | 1324.12 | 348.11 | 656.27 | 0.00 | 656.27 | 0.00 | 0.00 |
November | 917.42 | 700.13 | 570.63 | 0.00 | 570.63 | 0.00 | 0.00 |
December | 580.94 | 1178.90 | 505.44 | 0.00 | 505.44 | 0.00 | 0.00 |
Annual Sum or Average | 1385.52 | 598.73 | 746.62 | 14.49 | 732.13 | 0.00 | 0.00 |
Minimum of Months | 518.76 | 129.30 | 505.44 | 0.00 | 505.44 | 0.00 | 0.00 |
Maximum of Months | 2310.71 | 1357.12 | 997.77 | 70.99 | 948.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1165.39 | 846.18 | 820.26 | 392.95 | 427.30 | 0.00 | 0.00 |
February | 1469.27 | 700.43 | 947.13 | 438.43 | 508.70 | 0.00 | 0.00 |
March | 1814.54 | 558.32 | 1156.37 | 546.68 | 609.69 | 0.00 | 0.00 |
April | 2210.16 | 374.79 | 1254.95 | 559.95 | 695.00 | 0.00 | 0.00 |
May | 2292.60 | 192.57 | 1187.23 | 472.78 | 714.45 | 0.00 | 0.00 |
June | 2381.68 | 80.75 | 1171.82 | 450.09 | 721.73 | 0.00 | 0.00 |
July | 2526.97 | 127.26 | 1204.06 | 434.21 | 769.85 | 0.00 | 0.00 |
August | 2245.95 | 77.82 | 1101.00 | 368.15 | 732.85 | 0.00 | 0.00 |
September | 2193.03 | 146.37 | 1061.44 | 383.71 | 677.73 | 0.00 | 0.00 |
October | 1875.75 | 225.28 | 977.01 | 420.76 | 556.25 | 0.00 | 0.00 |
November | 1355.71 | 424.35 | 792.97 | 316.19 | 476.78 | 0.00 | 0.00 |
December | 933.12 | 719.25 | 640.55 | 226.15 | 414.40 | 0.00 | 0.00 |
Annual Sum or Average | 1873.54 | 371.36 | 1026.40 | 417.22 | 609.18 | 0.00 | 0.00 |
Minimum of Months | 933.12 | 77.82 | 640.55 | 226.15 | 414.40 | 0.00 | 0.00 |
Maximum of Months | 2526.97 | 846.18 | 1254.95 | 559.95 | 769.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3830.43 | 1318.15 | 2401.65 | 1560.30 | 841.35 | 0.00 | 0.00 |
February | 3663.51 | 1124.29 | 2172.64 | 1257.14 | 915.50 | 0.00 | 0.00 |
March | 2851.96 | 922.22 | 1668.10 | 705.26 | 962.84 | 0.00 | 0.00 |
April | 2131.35 | 615.95 | 1134.28 | 198.91 | 935.37 | 0.00 | 0.00 |
May | 1882.03 | 294.11 | 908.94 | 19.66 | 889.27 | 0.00 | 0.00 |
June | 1930.18 | 130.63 | 866.59 | 1.64 | 864.96 | 0.00 | 0.00 |
July | 2159.92 | 198.56 | 927.89 | 8.60 | 919.29 | 0.00 | 0.00 |
August | 2325.27 | 146.61 | 1053.12 | 88.87 | 964.25 | 0.00 | 0.00 |
September | 2980.44 | 239.28 | 1348.14 | 330.36 | 1017.77 | 0.00 | 0.00 |
October | 3638.85 | 405.72 | 1853.96 | 869.82 | 984.14 | 0.00 | 0.00 |
November | 3705.97 | 723.41 | 2109.39 | 1177.28 | 932.12 | 0.00 | 0.00 |
December | 3775.00 | 1176.70 | 2314.52 | 1459.87 | 854.65 | 0.00 | 0.00 |
Annual Sum or Average | 2902.42 | 605.71 | 1560.44 | 637.07 | 923.37 | 0.00 | 0.00 |
Minimum of Months | 1882.03 | 130.63 | 866.59 | 1.64 | 841.35 | 0.00 | 0.00 |
Maximum of Months | 3830.43 | 1318.15 | 2401.65 | 1560.30 | 1017.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1035.10 | 996.66 | 736.86 | 317.67 | 419.19 | 0.00 | 0.00 |
February | 1439.71 | 887.21 | 921.43 | 417.00 | 504.43 | 0.00 | 0.00 |
March | 1803.26 | 771.17 | 1147.46 | 523.99 | 623.47 | 0.00 | 0.00 |
April | 2166.66 | 555.76 | 1263.02 | 584.82 | 678.20 | 0.00 | 0.00 |
May | 2210.13 | 282.71 | 1151.41 | 443.24 | 708.17 | 0.00 | 0.00 |
June | 1963.42 | 160.13 | 975.60 | 273.66 | 701.93 | 0.00 | 0.00 |
July | 2247.91 | 227.17 | 1090.32 | 337.31 | 753.01 | 0.00 | 0.00 |
August | 2120.61 | 216.95 | 1087.84 | 354.52 | 733.31 | 0.00 | 0.00 |
September | 1905.58 | 205.59 | 927.98 | 273.63 | 654.35 | 0.00 | 0.00 |
October | 1740.68 | 346.21 | 923.17 | 359.88 | 563.29 | 0.00 | 0.00 |
November | 1274.87 | 611.45 | 761.52 | 279.33 | 482.19 | 0.00 | 0.00 |
December | 1110.53 | 965.03 | 762.88 | 341.08 | 421.80 | 0.00 | 0.00 |
Annual Sum or Average | 1753.27 | 517.30 | 979.57 | 375.42 | 604.15 | 0.00 | 0.00 |
Minimum of Months | 1035.10 | 160.13 | 736.86 | 273.63 | 419.19 | 0.00 | 0.00 |
Maximum of Months | 2247.91 | 996.66 | 1263.02 | 584.82 | 753.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 564.50 | 1206.42 | 510.99 | 0.00 | 510.99 | 0.00 | 0.00 |
February | 842.62 | 999.28 | 604.84 | 0.00 | 604.84 | 0.00 | 0.00 |
March | 992.48 | 841.94 | 721.32 | 0.00 | 721.32 | 0.00 | 0.00 |
April | 1377.15 | 552.17 | 808.27 | 3.63 | 804.64 | 0.00 | 0.00 |
May | 1900.83 | 296.39 | 923.00 | 41.29 | 881.72 | 0.00 | 0.00 |
June | 2187.84 | 137.20 | 985.97 | 70.99 | 914.97 | 0.00 | 0.00 |
July | 2323.59 | 195.28 | 997.76 | 48.89 | 948.87 | 0.00 | 0.00 |
August | 1964.85 | 128.67 | 883.03 | 8.12 | 874.91 | 0.00 | 0.00 |
September | 1806.06 | 215.49 | 783.36 | 0.06 | 783.30 | 0.00 | 0.00 |
October | 1337.40 | 336.55 | 656.26 | 0.00 | 656.26 | 0.00 | 0.00 |
November | 944.17 | 631.54 | 570.62 | 0.00 | 570.62 | 0.00 | 0.00 |
December | 627.78 | 1029.35 | 505.44 | 0.00 | 505.44 | 0.00 | 0.00 |
Annual Sum or Average | 1408.51 | 545.60 | 746.61 | 14.49 | 732.13 | 0.00 | 0.00 |
Minimum of Months | 564.50 | 128.67 | 505.44 | 0.00 | 505.44 | 0.00 | 0.00 |
Maximum of Months | 2323.59 | 1206.42 | 997.76 | 70.99 | 948.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1162.24 | 799.20 | 820.25 | 392.95 | 427.30 | 0.00 | 0.00 |
February | 1457.61 | 660.86 | 947.12 | 438.42 | 508.70 | 0.00 | 0.00 |
March | 1781.40 | 551.35 | 1156.36 | 546.68 | 609.68 | 0.00 | 0.00 |
April | 2169.18 | 392.95 | 1254.95 | 559.95 | 695.00 | 0.00 | 0.00 |
May | 2255.39 | 204.26 | 1187.23 | 472.78 | 714.45 | 0.00 | 0.00 |
June | 2341.18 | 97.24 | 1171.81 | 450.09 | 721.73 | 0.00 | 0.00 |
July | 2494.33 | 144.59 | 1204.05 | 434.21 | 769.85 | 0.00 | 0.00 |
August | 2217.84 | 93.58 | 1101.00 | 368.15 | 732.85 | 0.00 | 0.00 |
September | 2159.57 | 156.02 | 1061.44 | 383.71 | 677.72 | 0.00 | 0.00 |
October | 1847.27 | 242.37 | 977.01 | 420.76 | 556.25 | 0.00 | 0.00 |
November | 1336.90 | 419.21 | 792.97 | 316.19 | 476.78 | 0.00 | 0.00 |
December | 927.68 | 687.53 | 640.55 | 226.14 | 414.40 | 0.00 | 0.00 |
Annual Sum or Average | 1847.37 | 369.52 | 1026.40 | 417.22 | 609.17 | 0.00 | 0.00 |
Minimum of Months | 927.68 | 93.58 | 640.55 | 226.14 | 414.40 | 0.00 | 0.00 |
Maximum of Months | 2494.33 | 799.20 | 1254.95 | 559.95 | 769.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3790.75 | 1288.96 | 2401.64 | 1560.29 | 841.35 | 0.00 | 0.00 |
February | 3629.71 | 1082.81 | 2172.64 | 1257.14 | 915.50 | 0.00 | 0.00 |
March | 2825.72 | 893.74 | 1668.09 | 705.26 | 962.83 | 0.00 | 0.00 |
April | 2127.50 | 600.47 | 1134.27 | 198.91 | 935.36 | 0.00 | 0.00 |
May | 1880.77 | 289.68 | 908.93 | 19.66 | 889.27 | 0.00 | 0.00 |
June | 1939.70 | 135.21 | 866.59 | 1.64 | 864.96 | 0.00 | 0.00 |
July | 2176.39 | 191.78 | 927.88 | 8.60 | 919.28 | 0.00 | 0.00 |
August | 2348.81 | 136.17 | 1053.12 | 88.87 | 964.25 | 0.00 | 0.00 |
September | 2960.01 | 243.94 | 1348.13 | 330.36 | 1017.77 | 0.00 | 0.00 |
October | 3603.20 | 419.89 | 1853.95 | 869.82 | 984.13 | 0.00 | 0.00 |
November | 3669.45 | 712.23 | 2109.39 | 1177.27 | 932.12 | 0.00 | 0.00 |
December | 3744.02 | 1141.66 | 2314.51 | 1459.86 | 854.65 | 0.00 | 0.00 |
Annual Sum or Average | 2887.65 | 592.58 | 1560.43 | 637.06 | 923.37 | 0.00 | 0.00 |
Minimum of Months | 1880.77 | 135.21 | 866.59 | 1.64 | 841.35 | 0.00 | 0.00 |
Maximum of Months | 3790.75 | 1288.96 | 2401.64 | 1560.29 | 1017.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1065.07 | 874.57 | 736.86 | 317.67 | 419.19 | 0.00 | 0.00 |
February | 1479.42 | 752.12 | 921.43 | 417.00 | 504.43 | 0.00 | 0.00 |
March | 1837.21 | 652.48 | 1147.46 | 523.99 | 623.47 | 0.00 | 0.00 |
April | 2212.46 | 465.82 | 1263.02 | 584.82 | 678.20 | 0.00 | 0.00 |
May | 2217.15 | 256.84 | 1151.40 | 443.24 | 708.17 | 0.00 | 0.00 |
June | 1994.89 | 125.85 | 975.59 | 273.66 | 701.93 | 0.00 | 0.00 |
July | 2292.32 | 176.48 | 1090.31 | 337.31 | 753.00 | 0.00 | 0.00 |
August | 2190.18 | 134.52 | 1087.83 | 354.52 | 733.31 | 0.00 | 0.00 |
September | 1922.42 | 179.91 | 927.98 | 273.63 | 654.35 | 0.00 | 0.00 |
October | 1765.94 | 292.50 | 923.17 | 359.88 | 563.29 | 0.00 | 0.00 |
November | 1319.91 | 487.70 | 761.52 | 279.33 | 482.19 | 0.00 | 0.00 |
December | 1165.46 | 769.80 | 762.88 | 341.08 | 421.80 | 0.00 | 0.00 |
Annual Sum or Average | 1790.27 | 429.34 | 979.56 | 375.42 | 604.15 | 0.00 | 0.00 |
Minimum of Months | 1065.07 | 125.85 | 736.86 | 273.63 | 419.19 | 0.00 | 0.00 |
Maximum of Months | 2292.32 | 874.57 | 1263.02 | 584.82 | 753.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 581.61 | 1127.40 | 510.99 | 0.00 | 510.99 | 0.00 | 0.00 |
February | 847.11 | 948.44 | 604.84 | 0.00 | 604.84 | 0.00 | 0.00 |
March | 983.04 | 812.16 | 721.32 | 0.00 | 721.32 | 0.00 | 0.00 |
April | 1352.17 | 552.45 | 808.27 | 3.63 | 804.64 | 0.00 | 0.00 |
May | 1868.53 | 306.42 | 923.00 | 41.29 | 881.72 | 0.00 | 0.00 |
June | 2148.66 | 144.98 | 985.97 | 70.99 | 914.97 | 0.00 | 0.00 |
July | 2284.55 | 210.64 | 997.76 | 48.89 | 948.87 | 0.00 | 0.00 |
August | 1932.62 | 136.72 | 883.03 | 8.12 | 874.91 | 0.00 | 0.00 |
September | 1769.22 | 220.64 | 783.36 | 0.06 | 783.30 | 0.00 | 0.00 |
October | 1314.84 | 340.01 | 656.26 | 0.00 | 656.26 | 0.00 | 0.00 |
November | 940.44 | 600.62 | 570.62 | 0.00 | 570.62 | 0.00 | 0.00 |
December | 636.68 | 972.61 | 505.44 | 0.00 | 505.44 | 0.00 | 0.00 |
Annual Sum or Average | 1390.94 | 529.32 | 746.61 | 14.49 | 732.13 | 0.00 | 0.00 |
Minimum of Months | 581.61 | 136.72 | 505.44 | 0.00 | 505.44 | 0.00 | 0.00 |
Maximum of Months | 2284.55 | 1127.40 | 997.76 | 70.99 | 948.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1179.33 | 754.71 | 820.25 | 392.95 | 427.30 | 0.00 | 0.00 |
February | 1466.80 | 631.16 | 947.12 | 438.42 | 508.70 | 0.00 | 0.00 |
March | 1778.25 | 535.37 | 1156.36 | 546.68 | 609.68 | 0.00 | 0.00 |
April | 2157.05 | 391.40 | 1254.95 | 559.95 | 695.00 | 0.00 | 0.00 |
May | 2238.96 | 208.66 | 1187.23 | 472.78 | 714.45 | 0.00 | 0.00 |
June | 2321.99 | 101.10 | 1171.81 | 450.09 | 721.73 | 0.00 | 0.00 |
July | 2475.24 | 152.65 | 1204.05 | 434.21 | 769.85 | 0.00 | 0.00 |
August | 2203.57 | 97.26 | 1101.00 | 368.15 | 732.85 | 0.00 | 0.00 |
September | 2142.73 | 158.30 | 1061.44 | 383.71 | 677.72 | 0.00 | 0.00 |
October | 1838.26 | 242.30 | 977.01 | 420.76 | 556.25 | 0.00 | 0.00 |
November | 1339.80 | 400.88 | 792.97 | 316.19 | 476.78 | 0.00 | 0.00 |
December | 938.89 | 652.83 | 640.55 | 226.14 | 414.40 | 0.00 | 0.00 |
Annual Sum or Average | 1841.49 | 359.40 | 1026.40 | 417.22 | 609.17 | 0.00 | 0.00 |
Minimum of Months | 938.89 | 97.26 | 640.55 | 226.14 | 414.40 | 0.00 | 0.00 |
Maximum of Months | 2475.24 | 754.71 | 1254.95 | 559.95 | 769.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3803.90 | 1223.80 | 2401.64 | 1560.29 | 841.35 | 0.00 | 0.00 |
February | 3629.07 | 1037.32 | 2172.64 | 1257.14 | 915.50 | 0.00 | 0.00 |
March | 2809.61 | 866.53 | 1668.09 | 705.26 | 962.83 | 0.00 | 0.00 |
April | 2100.60 | 599.66 | 1134.27 | 198.91 | 935.36 | 0.00 | 0.00 |
May | 1847.29 | 299.25 | 908.93 | 19.66 | 889.27 | 0.00 | 0.00 |
June | 1899.71 | 143.09 | 866.59 | 1.64 | 864.96 | 0.00 | 0.00 |
July | 2136.91 | 207.99 | 927.88 | 8.60 | 919.28 | 0.00 | 0.00 |
August | 2315.04 | 143.79 | 1053.12 | 88.87 | 964.25 | 0.00 | 0.00 |
September | 2925.16 | 249.08 | 1348.13 | 330.36 | 1017.77 | 0.00 | 0.00 |
October | 3581.44 | 418.78 | 1853.95 | 869.82 | 984.13 | 0.00 | 0.00 |
November | 3664.11 | 683.75 | 2109.39 | 1177.27 | 932.12 | 0.00 | 0.00 |
December | 3745.61 | 1091.13 | 2314.51 | 1459.86 | 854.65 | 0.00 | 0.00 |
Annual Sum or Average | 2867.77 | 578.36 | 1560.43 | 637.06 | 923.37 | 0.00 | 0.00 |
Minimum of Months | 1847.29 | 143.09 | 866.59 | 1.64 | 841.35 | 0.00 | 0.00 |
Maximum of Months | 3803.90 | 1223.80 | 2401.64 | 1560.29 | 1017.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1069.03 | 827.95 | 736.86 | 317.67 | 419.19 | 0.00 | 0.00 |
February | 1475.56 | 721.28 | 921.43 | 417.00 | 504.43 | 0.00 | 0.00 |
March | 1824.63 | 631.70 | 1147.46 | 523.99 | 623.47 | 0.00 | 0.00 |
April | 2192.88 | 462.53 | 1263.02 | 584.82 | 678.20 | 0.00 | 0.00 |
May | 2194.50 | 260.16 | 1151.40 | 443.24 | 708.17 | 0.00 | 0.00 |
June | 1971.67 | 131.25 | 975.59 | 273.66 | 701.93 | 0.00 | 0.00 |
July | 2267.51 | 183.01 | 1090.31 | 337.31 | 753.00 | 0.00 | 0.00 |
August | 2169.51 | 139.03 | 1087.83 | 354.52 | 733.31 | 0.00 | 0.00 |
September | 1901.04 | 182.52 | 927.98 | 273.63 | 654.35 | 0.00 | 0.00 |
October | 1750.26 | 291.88 | 923.17 | 359.88 | 563.29 | 0.00 | 0.00 |
November | 1313.57 | 469.10 | 761.52 | 279.33 | 482.19 | 0.00 | 0.00 |
December | 1164.65 | 735.77 | 762.88 | 341.08 | 421.80 | 0.00 | 0.00 |
Annual Sum or Average | 1776.26 | 418.39 | 979.56 | 375.42 | 604.15 | 0.00 | 0.00 |
Minimum of Months | 1069.03 | 131.25 | 736.86 | 273.63 | 419.19 | 0.00 | 0.00 |
Maximum of Months | 2267.51 | 827.95 | 1263.02 | 584.82 | 753.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138945E+10 | 0.363491E+10 | 0.136865E+10 | 0.00 | 0.136865E+10 | 0.00 | 0.00 |
February | 0.192720E+10 | 0.273613E+10 | 0.146324E+10 | 0.00 | 0.146324E+10 | 0.00 | 0.00 |
March | 0.258529E+10 | 0.248114E+10 | 0.193199E+10 | 0.00 | 0.193199E+10 | 0.00 | 0.00 |
April | 0.351670E+10 | 0.151063E+10 | 0.209504E+10 | 9411170.43 | 0.208563E+10 | 0.00 | 0.00 |
May | 0.509776E+10 | 0.793606E+09 | 0.247218E+10 | 0.110586E+09 | 0.236160E+10 | 0.00 | 0.00 |
June | 0.567255E+10 | 0.335151E+09 | 0.255563E+10 | 0.184013E+09 | 0.237162E+10 | 0.00 | 0.00 |
July | 0.618900E+10 | 0.535384E+09 | 0.267242E+10 | 0.130954E+09 | 0.254147E+10 | 0.00 | 0.00 |
August | 0.517134E+10 | 0.385422E+09 | 0.236513E+10 | 21752680.74 | 0.234338E+10 | 0.00 | 0.00 |
September | 0.466411E+10 | 0.564547E+09 | 0.203047E+10 | 160629.38 | 0.203031E+10 | 0.00 | 0.00 |
October | 0.354653E+10 | 0.932387E+09 | 0.175774E+10 | 0.00 | 0.175774E+10 | 0.00 | 0.00 |
November | 0.237796E+10 | 0.181474E+10 | 0.147906E+10 | 0.00 | 0.147906E+10 | 0.00 | 0.00 |
December | 0.155598E+10 | 0.315758E+10 | 0.135377E+10 | 0.00 | 0.135377E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.436939E+11 | 0.188816E+11 | 0.235453E+11 | 0.456878E+09 | 0.230885E+11 | 0.00 | 0.00 |
Minimum of Months | 0.138945E+10 | 0.335151E+09 | 0.135377E+10 | 0.00 | 0.135377E+10 | 0.00 | 0.00 |
Maximum of Months | 0.618900E+10 | 0.363491E+10 | 0.267242E+10 | 0.184013E+09 | 0.254147E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.312138E+10 | 0.226641E+10 | 0.219698E+10 | 0.105249E+10 | 0.114449E+10 | 0.00 | 0.00 |
February | 0.355445E+10 | 0.169448E+10 | 0.229129E+10 | 0.106064E+10 | 0.123065E+10 | 0.00 | 0.00 |
March | 0.486007E+10 | 0.149541E+10 | 0.309722E+10 | 0.146423E+10 | 0.163298E+10 | 0.00 | 0.00 |
April | 0.572873E+10 | 0.971458E+09 | 0.325284E+10 | 0.145140E+10 | 0.180143E+10 | 0.00 | 0.00 |
May | 0.614050E+10 | 0.515777E+09 | 0.317989E+10 | 0.126631E+10 | 0.191358E+10 | 0.00 | 0.00 |
June | 0.617331E+10 | 0.209310E+09 | 0.303736E+10 | 0.116663E+10 | 0.187073E+10 | 0.00 | 0.00 |
July | 0.676824E+10 | 0.340850E+09 | 0.322494E+10 | 0.116298E+10 | 0.206196E+10 | 0.00 | 0.00 |
August | 0.601555E+10 | 0.208437E+09 | 0.294893E+10 | 0.986060E+09 | 0.196287E+10 | 0.00 | 0.00 |
September | 0.568435E+10 | 0.379398E+09 | 0.275125E+10 | 0.994588E+09 | 0.175666E+10 | 0.00 | 0.00 |
October | 0.502400E+10 | 0.603380E+09 | 0.261683E+10 | 0.112697E+10 | 0.148986E+10 | 0.00 | 0.00 |
November | 0.351400E+10 | 0.109992E+10 | 0.205539E+10 | 0.819563E+09 | 0.123582E+10 | 0.00 | 0.00 |
December | 0.249928E+10 | 0.192644E+10 | 0.171565E+10 | 0.605707E+09 | 0.110994E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.590839E+11 | 0.117113E+11 | 0.323686E+11 | 0.131576E+11 | 0.192110E+11 | 0.00 | 0.00 |
Minimum of Months | 0.249928E+10 | 0.208437E+09 | 0.171565E+10 | 0.605707E+09 | 0.110994E+10 | 0.00 | 0.00 |
Maximum of Months | 0.676824E+10 | 0.226641E+10 | 0.325284E+10 | 0.146423E+10 | 0.206196E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102594E+11 | 0.353055E+10 | 0.643257E+10 | 0.417910E+10 | 0.225347E+10 | 0.00 | 0.00 |
February | 0.886276E+10 | 0.271989E+10 | 0.525606E+10 | 0.304128E+10 | 0.221478E+10 | 0.00 | 0.00 |
March | 0.763868E+10 | 0.247006E+10 | 0.446783E+10 | 0.188896E+10 | 0.257887E+10 | 0.00 | 0.00 |
April | 0.552446E+10 | 0.159654E+10 | 0.294004E+10 | 0.515570E+09 | 0.242447E+10 | 0.00 | 0.00 |
May | 0.504082E+10 | 0.787755E+09 | 0.243450E+10 | 52669827.03 | 0.238183E+10 | 0.00 | 0.00 |
June | 0.500304E+10 | 0.338581E+09 | 0.224621E+10 | 4238976.26 | 0.224197E+10 | 0.00 | 0.00 |
July | 0.578514E+10 | 0.531827E+09 | 0.248525E+10 | 23036110.68 | 0.246222E+10 | 0.00 | 0.00 |
August | 0.622801E+10 | 0.392693E+09 | 0.282068E+10 | 0.238024E+09 | 0.258266E+10 | 0.00 | 0.00 |
September | 0.772529E+10 | 0.620207E+09 | 0.349437E+10 | 0.856302E+09 | 0.263807E+10 | 0.00 | 0.00 |
October | 0.974629E+10 | 0.108667E+10 | 0.496564E+10 | 0.232972E+10 | 0.263591E+10 | 0.00 | 0.00 |
November | 0.960587E+10 | 0.187509E+10 | 0.546755E+10 | 0.305150E+10 | 0.241605E+10 | 0.00 | 0.00 |
December | 0.101109E+11 | 0.315168E+10 | 0.619920E+10 | 0.391011E+10 | 0.228910E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.915307E+11 | 0.191015E+11 | 0.492099E+11 | 0.200905E+11 | 0.291194E+11 | 0.00 | 0.00 |
Minimum of Months | 0.500304E+10 | 0.338581E+09 | 0.224621E+10 | 4238976.26 | 0.221478E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102594E+11 | 0.353055E+10 | 0.643257E+10 | 0.417910E+10 | 0.263807E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.277241E+10 | 0.266946E+10 | 0.197362E+10 | 0.850855E+09 | 0.112276E+10 | 0.00 | 0.00 |
February | 0.348295E+10 | 0.214633E+10 | 0.222912E+10 | 0.100881E+10 | 0.122032E+10 | 0.00 | 0.00 |
March | 0.482985E+10 | 0.206550E+10 | 0.307336E+10 | 0.140346E+10 | 0.166990E+10 | 0.00 | 0.00 |
April | 0.561599E+10 | 0.144053E+10 | 0.327375E+10 | 0.151585E+10 | 0.175790E+10 | 0.00 | 0.00 |
May | 0.591962E+10 | 0.757221E+09 | 0.308393E+10 | 0.118717E+10 | 0.189676E+10 | 0.00 | 0.00 |
June | 0.508918E+10 | 0.415065E+09 | 0.252874E+10 | 0.709336E+09 | 0.181941E+10 | 0.00 | 0.00 |
July | 0.602081E+10 | 0.608449E+09 | 0.292030E+10 | 0.903451E+09 | 0.201685E+10 | 0.00 | 0.00 |
August | 0.567984E+10 | 0.581075E+09 | 0.291366E+10 | 0.949558E+09 | 0.196410E+10 | 0.00 | 0.00 |
September | 0.493927E+10 | 0.532885E+09 | 0.240533E+10 | 0.709256E+09 | 0.169608E+10 | 0.00 | 0.00 |
October | 0.466223E+10 | 0.927300E+09 | 0.247262E+10 | 0.963905E+09 | 0.150872E+10 | 0.00 | 0.00 |
November | 0.330447E+10 | 0.158488E+10 | 0.197386E+10 | 0.724023E+09 | 0.124984E+10 | 0.00 | 0.00 |
December | 0.297443E+10 | 0.258475E+10 | 0.204331E+10 | 0.913547E+09 | 0.112976E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.552910E+11 | 0.163134E+11 | 0.308916E+11 | 0.118392E+11 | 0.190524E+11 | 0.00 | 0.00 |
Minimum of Months | 0.277241E+10 | 0.415065E+09 | 0.197362E+10 | 0.709256E+09 | 0.112276E+10 | 0.00 | 0.00 |
Maximum of Months | 0.602081E+10 | 0.266946E+10 | 0.327375E+10 | 0.151585E+10 | 0.201685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.151196E+10 | 0.323128E+10 | 0.136865E+10 | 0.00 | 0.136865E+10 | 0.00 | 0.00 |
February | 0.203846E+10 | 0.241746E+10 | 0.146324E+10 | 0.00 | 0.146324E+10 | 0.00 | 0.00 |
March | 0.265825E+10 | 0.225505E+10 | 0.193198E+10 | 0.00 | 0.193198E+10 | 0.00 | 0.00 |
April | 0.356958E+10 | 0.143122E+10 | 0.209504E+10 | 9411137.01 | 0.208563E+10 | 0.00 | 0.00 |
May | 0.509119E+10 | 0.793860E+09 | 0.247217E+10 | 0.110586E+09 | 0.236159E+10 | 0.00 | 0.00 |
June | 0.567089E+10 | 0.355628E+09 | 0.255562E+10 | 0.184013E+09 | 0.237161E+10 | 0.00 | 0.00 |
July | 0.622349E+10 | 0.523044E+09 | 0.267241E+10 | 0.130953E+09 | 0.254146E+10 | 0.00 | 0.00 |
August | 0.526265E+10 | 0.344632E+09 | 0.236512E+10 | 21752603.50 | 0.234337E+10 | 0.00 | 0.00 |
September | 0.468131E+10 | 0.558543E+09 | 0.203047E+10 | 160628.81 | 0.203031E+10 | 0.00 | 0.00 |
October | 0.358210E+10 | 0.901402E+09 | 0.175774E+10 | 0.00 | 0.175774E+10 | 0.00 | 0.00 |
November | 0.244730E+10 | 0.163696E+10 | 0.147906E+10 | 0.00 | 0.147906E+10 | 0.00 | 0.00 |
December | 0.168146E+10 | 0.275700E+10 | 0.135376E+10 | 0.00 | 0.135376E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.444187E+11 | 0.172061E+11 | 0.235452E+11 | 0.456876E+09 | 0.230884E+11 | 0.00 | 0.00 |
Minimum of Months | 0.151196E+10 | 0.344632E+09 | 0.135376E+10 | 0.00 | 0.135376E+10 | 0.00 | 0.00 |
Maximum of Months | 0.622349E+10 | 0.323128E+10 | 0.267241E+10 | 0.184013E+09 | 0.254146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.311296E+10 | 0.214057E+10 | 0.219697E+10 | 0.105248E+10 | 0.114448E+10 | 0.00 | 0.00 |
February | 0.352626E+10 | 0.159875E+10 | 0.229128E+10 | 0.106064E+10 | 0.123064E+10 | 0.00 | 0.00 |
March | 0.477131E+10 | 0.147673E+10 | 0.309720E+10 | 0.146422E+10 | 0.163298E+10 | 0.00 | 0.00 |
April | 0.562251E+10 | 0.101852E+10 | 0.325282E+10 | 0.145139E+10 | 0.180143E+10 | 0.00 | 0.00 |
May | 0.604084E+10 | 0.547100E+09 | 0.317988E+10 | 0.126630E+10 | 0.191358E+10 | 0.00 | 0.00 |
June | 0.606835E+10 | 0.252034E+09 | 0.303734E+10 | 0.116662E+10 | 0.187072E+10 | 0.00 | 0.00 |
July | 0.668081E+10 | 0.387280E+09 | 0.322493E+10 | 0.116298E+10 | 0.206195E+10 | 0.00 | 0.00 |
August | 0.594027E+10 | 0.250655E+09 | 0.294892E+10 | 0.986056E+09 | 0.196286E+10 | 0.00 | 0.00 |
September | 0.559760E+10 | 0.404410E+09 | 0.275124E+10 | 0.994584E+09 | 0.175666E+10 | 0.00 | 0.00 |
October | 0.494772E+10 | 0.649167E+09 | 0.261682E+10 | 0.112696E+10 | 0.148986E+10 | 0.00 | 0.00 |
November | 0.346525E+10 | 0.108659E+10 | 0.205538E+10 | 0.819560E+09 | 0.123582E+10 | 0.00 | 0.00 |
December | 0.248471E+10 | 0.184147E+10 | 0.171564E+10 | 0.605705E+09 | 0.110994E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.582586E+11 | 0.116533E+11 | 0.323684E+11 | 0.131575E+11 | 0.192109E+11 | 0.00 | 0.00 |
Minimum of Months | 0.248471E+10 | 0.250655E+09 | 0.171564E+10 | 0.605705E+09 | 0.110994E+10 | 0.00 | 0.00 |
Maximum of Months | 0.668081E+10 | 0.214057E+10 | 0.325282E+10 | 0.146422E+10 | 0.206195E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101532E+11 | 0.345235E+10 | 0.643255E+10 | 0.417908E+10 | 0.225347E+10 | 0.00 | 0.00 |
February | 0.878100E+10 | 0.261953E+10 | 0.525604E+10 | 0.304127E+10 | 0.221477E+10 | 0.00 | 0.00 |
March | 0.756841E+10 | 0.239379E+10 | 0.446781E+10 | 0.188896E+10 | 0.257886E+10 | 0.00 | 0.00 |
April | 0.551449E+10 | 0.155641E+10 | 0.294003E+10 | 0.515568E+09 | 0.242446E+10 | 0.00 | 0.00 |
May | 0.503745E+10 | 0.775877E+09 | 0.243449E+10 | 52669640.00 | 0.238182E+10 | 0.00 | 0.00 |
June | 0.502769E+10 | 0.350457E+09 | 0.224620E+10 | 4238961.21 | 0.224196E+10 | 0.00 | 0.00 |
July | 0.582925E+10 | 0.513672E+09 | 0.248524E+10 | 23036028.87 | 0.246221E+10 | 0.00 | 0.00 |
August | 0.629104E+10 | 0.364718E+09 | 0.282067E+10 | 0.238024E+09 | 0.258265E+10 | 0.00 | 0.00 |
September | 0.767235E+10 | 0.632297E+09 | 0.349436E+10 | 0.856299E+09 | 0.263806E+10 | 0.00 | 0.00 |
October | 0.965082E+10 | 0.112463E+10 | 0.496562E+10 | 0.232972E+10 | 0.263590E+10 | 0.00 | 0.00 |
November | 0.951121E+10 | 0.184609E+10 | 0.546753E+10 | 0.305149E+10 | 0.241604E+10 | 0.00 | 0.00 |
December | 0.100280E+11 | 0.305781E+10 | 0.619918E+10 | 0.391009E+10 | 0.228909E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.910648E+11 | 0.186876E+11 | 0.492097E+11 | 0.200904E+11 | 0.291193E+11 | 0.00 | 0.00 |
Minimum of Months | 0.502769E+10 | 0.350457E+09 | 0.224620E+10 | 4238961.21 | 0.221477E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101532E+11 | 0.345235E+10 | 0.643255E+10 | 0.417908E+10 | 0.263806E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.285268E+10 | 0.234245E+10 | 0.197361E+10 | 0.850852E+09 | 0.112276E+10 | 0.00 | 0.00 |
February | 0.357901E+10 | 0.181952E+10 | 0.222911E+10 | 0.100880E+10 | 0.122031E+10 | 0.00 | 0.00 |
March | 0.492079E+10 | 0.174760E+10 | 0.307335E+10 | 0.140345E+10 | 0.166990E+10 | 0.00 | 0.00 |
April | 0.573470E+10 | 0.120741E+10 | 0.327374E+10 | 0.151585E+10 | 0.175789E+10 | 0.00 | 0.00 |
May | 0.593841E+10 | 0.687910E+09 | 0.308392E+10 | 0.118717E+10 | 0.189675E+10 | 0.00 | 0.00 |
June | 0.517075E+10 | 0.326197E+09 | 0.252873E+10 | 0.709333E+09 | 0.181940E+10 | 0.00 | 0.00 |
July | 0.613976E+10 | 0.472678E+09 | 0.292029E+10 | 0.903447E+09 | 0.201684E+10 | 0.00 | 0.00 |
August | 0.586618E+10 | 0.360291E+09 | 0.291365E+10 | 0.949554E+09 | 0.196410E+10 | 0.00 | 0.00 |
September | 0.498292E+10 | 0.466329E+09 | 0.240532E+10 | 0.709254E+09 | 0.169607E+10 | 0.00 | 0.00 |
October | 0.472989E+10 | 0.783436E+09 | 0.247261E+10 | 0.963901E+09 | 0.150871E+10 | 0.00 | 0.00 |
November | 0.342121E+10 | 0.126412E+10 | 0.197385E+10 | 0.724020E+09 | 0.124983E+10 | 0.00 | 0.00 |
December | 0.312157E+10 | 0.206184E+10 | 0.204330E+10 | 0.913543E+09 | 0.112975E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.564579E+11 | 0.135398E+11 | 0.308915E+11 | 0.118392E+11 | 0.190523E+11 | 0.00 | 0.00 |
Minimum of Months | 0.285268E+10 | 0.326197E+09 | 0.197361E+10 | 0.709254E+09 | 0.112276E+10 | 0.00 | 0.00 |
Maximum of Months | 0.613976E+10 | 0.234245E+10 | 0.327374E+10 | 0.151585E+10 | 0.201684E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.155779E+10 | 0.301964E+10 | 0.136865E+10 | 0.00 | 0.136865E+10 | 0.00 | 0.00 |
February | 0.204932E+10 | 0.229446E+10 | 0.146324E+10 | 0.00 | 0.146324E+10 | 0.00 | 0.00 |
March | 0.263298E+10 | 0.217528E+10 | 0.193198E+10 | 0.00 | 0.193198E+10 | 0.00 | 0.00 |
April | 0.350482E+10 | 0.143194E+10 | 0.209504E+10 | 9411137.01 | 0.208563E+10 | 0.00 | 0.00 |
May | 0.500468E+10 | 0.820705E+09 | 0.247217E+10 | 0.110586E+09 | 0.236159E+10 | 0.00 | 0.00 |
June | 0.556933E+10 | 0.375793E+09 | 0.255562E+10 | 0.184013E+09 | 0.237161E+10 | 0.00 | 0.00 |
July | 0.611893E+10 | 0.564191E+09 | 0.267241E+10 | 0.130953E+09 | 0.254146E+10 | 0.00 | 0.00 |
August | 0.517633E+10 | 0.366180E+09 | 0.236512E+10 | 21752603.50 | 0.234337E+10 | 0.00 | 0.00 |
September | 0.458581E+10 | 0.571888E+09 | 0.203047E+10 | 160628.81 | 0.203031E+10 | 0.00 | 0.00 |
October | 0.352166E+10 | 0.910691E+09 | 0.175774E+10 | 0.00 | 0.175774E+10 | 0.00 | 0.00 |
November | 0.243762E+10 | 0.155682E+10 | 0.147906E+10 | 0.00 | 0.147906E+10 | 0.00 | 0.00 |
December | 0.170530E+10 | 0.260505E+10 | 0.135376E+10 | 0.00 | 0.135376E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.438646E+11 | 0.166926E+11 | 0.235452E+11 | 0.456876E+09 | 0.230884E+11 | 0.00 | 0.00 |
Minimum of Months | 0.155779E+10 | 0.366180E+09 | 0.135376E+10 | 0.00 | 0.135376E+10 | 0.00 | 0.00 |
Maximum of Months | 0.611893E+10 | 0.301964E+10 | 0.267241E+10 | 0.184013E+09 | 0.254146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.315871E+10 | 0.202140E+10 | 0.219697E+10 | 0.105248E+10 | 0.114448E+10 | 0.00 | 0.00 |
February | 0.354849E+10 | 0.152691E+10 | 0.229128E+10 | 0.106064E+10 | 0.123064E+10 | 0.00 | 0.00 |
March | 0.476286E+10 | 0.143393E+10 | 0.309720E+10 | 0.146422E+10 | 0.163298E+10 | 0.00 | 0.00 |
April | 0.559106E+10 | 0.101451E+10 | 0.325282E+10 | 0.145139E+10 | 0.180143E+10 | 0.00 | 0.00 |
May | 0.599683E+10 | 0.558878E+09 | 0.317988E+10 | 0.126630E+10 | 0.191358E+10 | 0.00 | 0.00 |
June | 0.601860E+10 | 0.262046E+09 | 0.303734E+10 | 0.116662E+10 | 0.187072E+10 | 0.00 | 0.00 |
July | 0.662967E+10 | 0.408845E+09 | 0.322493E+10 | 0.116298E+10 | 0.206195E+10 | 0.00 | 0.00 |
August | 0.590205E+10 | 0.260501E+09 | 0.294892E+10 | 0.986056E+09 | 0.196286E+10 | 0.00 | 0.00 |
September | 0.555396E+10 | 0.410320E+09 | 0.275124E+10 | 0.994584E+09 | 0.175666E+10 | 0.00 | 0.00 |
October | 0.492359E+10 | 0.648968E+09 | 0.261682E+10 | 0.112696E+10 | 0.148986E+10 | 0.00 | 0.00 |
November | 0.347276E+10 | 0.103909E+10 | 0.205538E+10 | 0.819560E+09 | 0.123582E+10 | 0.00 | 0.00 |
December | 0.251471E+10 | 0.174854E+10 | 0.171564E+10 | 0.605705E+09 | 0.110994E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.580733E+11 | 0.113339E+11 | 0.323684E+11 | 0.131575E+11 | 0.192109E+11 | 0.00 | 0.00 |
Minimum of Months | 0.251471E+10 | 0.260501E+09 | 0.171564E+10 | 0.605705E+09 | 0.110994E+10 | 0.00 | 0.00 |
Maximum of Months | 0.662967E+10 | 0.202140E+10 | 0.325282E+10 | 0.146422E+10 | 0.206195E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101884E+11 | 0.327783E+10 | 0.643255E+10 | 0.417908E+10 | 0.225347E+10 | 0.00 | 0.00 |
February | 0.877944E+10 | 0.250947E+10 | 0.525604E+10 | 0.304127E+10 | 0.221477E+10 | 0.00 | 0.00 |
March | 0.752527E+10 | 0.232090E+10 | 0.446781E+10 | 0.188896E+10 | 0.257886E+10 | 0.00 | 0.00 |
April | 0.544477E+10 | 0.155431E+10 | 0.294003E+10 | 0.515568E+09 | 0.242446E+10 | 0.00 | 0.00 |
May | 0.494779E+10 | 0.801516E+09 | 0.243449E+10 | 52669640.00 | 0.238182E+10 | 0.00 | 0.00 |
June | 0.492406E+10 | 0.370884E+09 | 0.224620E+10 | 4238961.21 | 0.224196E+10 | 0.00 | 0.00 |
July | 0.572349E+10 | 0.557087E+09 | 0.248524E+10 | 23036028.87 | 0.246221E+10 | 0.00 | 0.00 |
August | 0.620060E+10 | 0.385121E+09 | 0.282067E+10 | 0.238024E+09 | 0.258265E+10 | 0.00 | 0.00 |
September | 0.758201E+10 | 0.645622E+09 | 0.349436E+10 | 0.856299E+09 | 0.263806E+10 | 0.00 | 0.00 |
October | 0.959252E+10 | 0.112166E+10 | 0.496562E+10 | 0.232972E+10 | 0.263590E+10 | 0.00 | 0.00 |
November | 0.949738E+10 | 0.177228E+10 | 0.546753E+10 | 0.305149E+10 | 0.241604E+10 | 0.00 | 0.00 |
December | 0.100322E+11 | 0.292247E+10 | 0.619918E+10 | 0.391009E+10 | 0.228909E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.904379E+11 | 0.182392E+11 | 0.492097E+11 | 0.200904E+11 | 0.291193E+11 | 0.00 | 0.00 |
Minimum of Months | 0.492406E+10 | 0.370884E+09 | 0.224620E+10 | 4238961.21 | 0.221477E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101884E+11 | 0.327783E+10 | 0.643255E+10 | 0.417908E+10 | 0.263806E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.286330E+10 | 0.221758E+10 | 0.197361E+10 | 0.850852E+09 | 0.112276E+10 | 0.00 | 0.00 |
February | 0.356968E+10 | 0.174492E+10 | 0.222911E+10 | 0.100880E+10 | 0.122031E+10 | 0.00 | 0.00 |
March | 0.488710E+10 | 0.169195E+10 | 0.307335E+10 | 0.140345E+10 | 0.166990E+10 | 0.00 | 0.00 |
April | 0.568394E+10 | 0.119888E+10 | 0.327374E+10 | 0.151585E+10 | 0.175789E+10 | 0.00 | 0.00 |
May | 0.587774E+10 | 0.696824E+09 | 0.308392E+10 | 0.118717E+10 | 0.189675E+10 | 0.00 | 0.00 |
June | 0.511056E+10 | 0.340196E+09 | 0.252873E+10 | 0.709333E+09 | 0.181940E+10 | 0.00 | 0.00 |
July | 0.607329E+10 | 0.490176E+09 | 0.292029E+10 | 0.903447E+09 | 0.201684E+10 | 0.00 | 0.00 |
August | 0.581081E+10 | 0.372368E+09 | 0.291365E+10 | 0.949554E+09 | 0.196410E+10 | 0.00 | 0.00 |
September | 0.492750E+10 | 0.473087E+09 | 0.240532E+10 | 0.709254E+09 | 0.169607E+10 | 0.00 | 0.00 |
October | 0.468790E+10 | 0.781779E+09 | 0.247261E+10 | 0.963901E+09 | 0.150871E+10 | 0.00 | 0.00 |
November | 0.340477E+10 | 0.121589E+10 | 0.197385E+10 | 0.724020E+09 | 0.124983E+10 | 0.00 | 0.00 |
December | 0.311939E+10 | 0.197070E+10 | 0.204330E+10 | 0.913543E+09 | 0.112975E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.560160E+11 | 0.131943E+11 | 0.308915E+11 | 0.118392E+11 | 0.190523E+11 | 0.00 | 0.00 |
Minimum of Months | 0.286330E+10 | 0.340196E+09 | 0.197361E+10 | 0.709254E+09 | 0.112276E+10 | 0.00 | 0.00 |
Maximum of Months | 0.607329E+10 | 0.221758E+10 | 0.327374E+10 | 0.151585E+10 | 0.201684E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.282573E+11 | -0.272386E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101870E+10 | 58.96 | 0.00 | 0.00 |
February | 0.254364E+11 | -0.245154E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -921021194.4 | 58.97 | 0.00 | 0.00 |
March | 0.289663E+11 | -0.279427E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102357E+10 | 58.97 | 0.00 | 0.00 |
April | 0.251503E+11 | -0.241630E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987291342.1 | 58.97 | 0.00 | 0.00 |
May | 0.255395E+11 | -0.245177E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102185E+10 | 58.97 | 0.00 | 0.00 |
June | 0.243108E+11 | -0.233204E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990405780.6 | 58.96 | 0.00 | 0.00 |
July | 0.227912E+11 | -0.217734E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101785E+10 | 58.96 | 0.00 | 0.00 |
August | 0.251591E+11 | -0.241368E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102235E+10 | 58.97 | 0.00 | 0.00 |
September | 0.237204E+11 | -0.227335E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986892671.2 | 58.97 | 0.00 | 0.00 |
October | 0.256831E+11 | -0.246652E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101790E+10 | 58.97 | 0.00 | 0.00 |
November | 0.264042E+11 | -0.254194E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984791154.3 | 58.97 | 0.00 | 0.00 |
December | 0.272329E+11 | -0.262155E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101739E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.308652E+12 | -0.296642E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120100E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.227912E+11 | -0.279427E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102357E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.289663E+11 | -0.217734E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -921021194.4 | 58.97 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.50 | 0.48 | 01-JAN-07:40 | 6560.61 | 35.98 | 274.83 | 291.83 | 1277.84 | 25.56 | 224.50 | 272.67 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2442.67 | 25.99 | 148.67 | 277.17 | 997.47 | 21.15 | 162.83 | 248.17 |
March | 362.67 | 0.50 | 0.48 | 01-MAR-07:49 | 1513.70 | 20.11 | 57.50 | 326.00 | 827.95 | 21.16 | 201.00 | 289.17 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:30 | 1185.31 | 19.47 | 11.83 | 325.00 | 668.82 | 20.75 | 164.83 | 286.17 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-07:10 | 1018.22 | 18.99 | 0.00 | 344.83 | 567.63 | 20.30 | 134.67 | 288.33 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-07:10 | 961.24 | 18.36 | 1.00 | 322.83 | 531.02 | 19.67 | 117.83 | 269.50 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1077.11 | 19.21 | 2.17 | 352.33 | 595.45 | 20.54 | 196.17 | 298.17 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1276.97 | 19.68 | 21.00 | 342.17 | 691.49 | 21.00 | 219.83 | 299.00 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:10 | 1527.41 | 19.94 | 70.67 | 315.00 | 804.96 | 21.27 | 229.67 | 276.17 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-07:40 | 2007.16 | 21.68 | 104.00 | 313.33 | 989.45 | 21.84 | 233.17 | 282.50 |
November | 314.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3749.75 | 31.52 | 253.33 | 290.67 | 1097.86 | 23.51 | 239.17 | 265.00 |
December | 282.67 | 0.49 | 0.48 | 01-DEC-08:39 | 6237.59 | 36.24 | 278.83 | 278.00 | 1486.38 | 26.90 | 237.83 | 259.17 |
Annual Sum or Average | 4111.50 | 0.51 | 2280.21 | 23.29 | 1223.83 | 3779.17 | 847.69 | 21.77 | 2361.50 | 3334.00 | ||
Minimum of Months | 282.67 | 0.49 | 0.48 | 961.24 | 18.36 | 0.00 | 277.17 | 531.02 | 19.67 | 117.83 | 248.17 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 6560.61 | 36.24 | 278.83 | 352.33 | 1486.38 | 26.90 | 239.17 | 299.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.52 | 0.48 | 01-JAN-07:40 | 2091.48 | 24.28 | 102.67 | 266.50 | 1098.38 | 24.09 | 134.50 | 223.00 |
February | 304.33 | 0.52 | 0.48 | 01-FEB-07:49 | 2187.31 | 23.59 | 101.67 | 259.50 | 826.48 | 22.23 | 118.00 | 223.00 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:19 | 2083.37 | 23.03 | 98.83 | 321.83 | 1094.27 | 23.28 | 139.67 | 284.83 |
April | 357.50 | 0.51 | 0.48 | 01-APR-06:00 | 2418.66 | 22.83 | 100.00 | 323.67 | 1287.63 | 23.22 | 121.00 | 287.50 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2236.71 | 22.85 | 112.67 | 355.33 | 944.49 | 22.34 | 126.67 | 307.00 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-05:00 | 2174.43 | 23.32 | 122.33 | 340.50 | 922.98 | 22.61 | 139.00 | 295.33 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:10 | 2150.95 | 23.33 | 123.50 | 361.50 | 947.01 | 22.76 | 163.00 | 314.83 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2114.31 | 22.93 | 97.17 | 344.17 | 1115.31 | 23.40 | 147.83 | 302.83 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-06:40 | 2073.74 | 23.51 | 104.83 | 310.00 | 1068.99 | 23.74 | 171.83 | 266.83 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-07:10 | 2049.05 | 23.63 | 97.67 | 301.83 | 1078.50 | 23.77 | 158.00 | 265.50 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1645.87 | 23.28 | 95.33 | 271.67 | 832.18 | 23.25 | 151.33 | 227.83 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-08:39 | 1765.93 | 23.11 | 88.00 | 253.33 | 724.40 | 21.97 | 119.17 | 206.50 |
Annual Sum or Average | 4111.50 | 0.51 | 2094.30 | 23.28 | 1244.67 | 3709.83 | 999.64 | 23.04 | 1690.00 | 3205.00 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 1645.87 | 22.83 | 88.00 | 253.33 | 724.40 | 21.97 | 118.00 | 206.50 | |
Maximum of Months | 403.83 | 0.52 | 0.48 | 2418.66 | 24.28 | 123.50 | 361.50 | 1287.63 | 24.09 | 171.83 | 314.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:20 | 540.51 | 16.32 | 0.00 | 245.00 | 341.56 | 17.92 | 0.00 | 149.67 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-08:00 | 614.59 | 17.14 | 0.00 | 248.67 | 378.40 | 18.58 | 0.00 | 173.67 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-08:00 | 734.09 | 18.30 | 0.00 | 310.83 | 442.90 | 19.65 | 6.83 | 252.33 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:19 | 875.83 | 19.15 | 0.00 | 330.33 | 520.25 | 20.40 | 66.50 | 288.50 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-06:30 | 1036.62 | 20.55 | 35.00 | 364.67 | 577.32 | 21.69 | 172.50 | 328.50 |
June | 388.17 | 0.50 | 0.48 | 01-JUN-06:30 | 1101.19 | 21.86 | 95.00 | 354.17 | 588.95 | 20.72 | 167.50 | 301.00 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:30 | 1156.41 | 20.86 | 59.33 | 372.50 | 632.00 | 22.14 | 252.33 | 332.83 |
August | 348.33 | 0.50 | 0.48 | 01-AUG-07:10 | 1043.84 | 19.63 | 2.33 | 348.33 | 588.27 | 20.93 | 160.50 | 308.83 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:10 | 878.16 | 18.82 | 0.00 | 313.00 | 501.18 | 20.11 | 70.33 | 256.00 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-11:39 | 702.86 | 17.93 | 0.00 | 292.50 | 427.30 | 19.34 | 2.17 | 220.50 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-07:00 | 617.89 | 17.31 | 0.00 | 254.17 | 368.83 | 18.74 | 0.00 | 170.50 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:00 | 588.06 | 17.04 | 0.00 | 239.83 | 360.13 | 18.60 | 0.00 | 154.50 |
Annual Sum or Average | 4111.50 | 0.51 | 845.92 | 18.91 | 191.67 | 3674.00 | 487.54 | 20.03 | 898.67 | 2936.83 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 540.51 | 16.32 | 0.00 | 239.83 | 341.56 | 17.92 | 0.00 | 149.67 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1156.41 | 21.86 | 95.00 | 372.50 | 632.00 | 22.14 | 252.33 | 332.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.52 | 0.48 | 01-JAN-09:20 | 1806.03 | 23.32 | 92.17 | 269.83 | 978.55 | 23.47 | 129.67 | 220.17 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:00 | 1663.77 | 21.78 | 72.17 | 264.83 | 843.96 | 21.99 | 118.67 | 225.50 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-08:00 | 2031.44 | 23.08 | 99.83 | 318.83 | 1046.74 | 23.35 | 147.17 | 285.17 |
April | 357.50 | 0.50 | 0.48 | 01-APR-08:50 | 2214.16 | 21.77 | 80.83 | 333.33 | 1184.99 | 22.32 | 95.17 | 297.83 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-07:30 | 1997.21 | 17.82 | 0.00 | 349.33 | 1033.83 | 19.90 | 81.50 | 306.83 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-07:19 | 1680.23 | 17.47 | 2.67 | 333.00 | 757.01 | 19.47 | 89.83 | 286.33 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-07:10 | 1901.27 | 18.37 | 3.67 | 356.67 | 853.10 | 20.24 | 118.83 | 315.50 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:49 | 2048.57 | 20.70 | 57.50 | 341.17 | 1056.12 | 20.62 | 124.17 | 302.00 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:30 | 1701.57 | 21.77 | 81.83 | 313.67 | 874.81 | 22.24 | 148.67 | 273.50 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-11:39 | 2032.75 | 23.95 | 106.83 | 299.83 | 1068.20 | 24.17 | 165.67 | 263.00 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-08:09 | 1609.05 | 23.32 | 99.50 | 272.33 | 831.17 | 23.49 | 158.17 | 230.83 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:00 | 1846.98 | 24.82 | 100.33 | 264.17 | 969.87 | 24.64 | 140.50 | 226.17 |
Annual Sum or Average | 4111.50 | 0.51 | 1883.67 | 21.29 | 797.33 | 3717.00 | 957.46 | 22.01 | 1518.00 | 3232.83 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 1609.05 | 17.47 | 0.00 | 264.17 | 757.01 | 19.47 | 81.50 | 220.17 | |
Maximum of Months | 403.83 | 0.52 | 0.48 | 2214.16 | 24.82 | 106.83 | 356.67 | 1184.99 | 24.64 | 165.67 | 315.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.50 | 0.48 | 01-JAN-07:40 | 6610.22 | 35.43 | 274.67 | 292.33 | 1365.02 | 21.38 | 81.00 | 275.50 |
February | 304.33 | 0.50 | 0.48 | 01-FEB-08:09 | 2482.07 | 21.91 | 134.17 | 277.17 | 1071.19 | 16.37 | 0.00 | 251.33 |
March | 362.67 | 0.50 | 0.48 | 01-MAR-07:49 | 1543.82 | 13.96 | 5.67 | 326.33 | 886.51 | 17.12 | 0.00 | 293.00 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:19 | 1206.16 | 13.71 | 0.00 | 325.33 | 713.54 | 17.13 | 0.00 | 292.50 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-07:10 | 1033.38 | 13.14 | 0.00 | 345.83 | 604.15 | 16.53 | 0.00 | 298.50 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-07:10 | 974.81 | 12.37 | 0.00 | 323.33 | 564.91 | 15.79 | 0.00 | 276.00 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1092.26 | 13.27 | 0.00 | 352.33 | 633.28 | 16.69 | 0.00 | 305.00 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1294.49 | 13.81 | 0.00 | 342.67 | 735.55 | 17.19 | 0.00 | 303.67 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-06:00 | 1547.64 | 13.68 | 0.00 | 315.67 | 856.62 | 17.08 | 0.00 | 280.00 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-07:40 | 2051.95 | 15.77 | 31.67 | 315.50 | 1059.04 | 17.85 | 9.17 | 287.17 |
November | 314.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3777.86 | 29.69 | 244.67 | 291.00 | 1184.45 | 20.74 | 71.33 | 272.50 |
December | 282.67 | 0.49 | 0.48 | 01-DEC-08:39 | 6277.26 | 35.83 | 278.50 | 278.00 | 1574.27 | 22.89 | 92.50 | 260.67 |
Annual Sum or Average | 4111.50 | 0.51 | 2306.87 | 18.54 | 969.33 | 3785.50 | 904.93 | 17.87 | 254.00 | 3395.83 | ||
Minimum of Months | 282.67 | 0.49 | 0.48 | 974.81 | 12.37 | 0.00 | 277.17 | 564.91 | 15.79 | 0.00 | 251.33 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 6610.22 | 35.83 | 278.50 | 352.33 | 1574.27 | 22.89 | 92.50 | 305.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.52 | 0.48 | 01-JAN-07:40 | 2124.65 | 21.84 | 102.50 | 267.83 | 1141.47 | 22.21 | 74.17 | 228.83 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-07:49 | 2226.69 | 20.86 | 99.83 | 260.33 | 871.02 | 19.79 | 45.50 | 227.33 |
March | 362.67 | 0.50 | 0.48 | 01-MAR-07:19 | 2131.78 | 19.96 | 98.83 | 322.00 | 1146.53 | 20.85 | 67.50 | 289.83 |
April | 357.50 | 0.51 | 0.48 | 01-APR-06:00 | 2441.43 | 19.78 | 99.83 | 324.17 | 1341.25 | 20.78 | 70.67 | 292.00 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-06:10 | 2252.01 | 19.13 | 103.83 | 355.83 | 994.62 | 19.68 | 57.67 | 312.33 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-05:00 | 2208.46 | 20.32 | 121.50 | 341.33 | 970.90 | 20.01 | 65.00 | 301.67 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:10 | 2174.99 | 19.65 | 115.50 | 362.00 | 996.95 | 20.17 | 63.67 | 320.83 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2133.52 | 19.94 | 97.17 | 345.17 | 1165.31 | 21.08 | 71.00 | 308.33 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-06:40 | 2108.30 | 20.54 | 103.50 | 310.83 | 1117.45 | 21.43 | 74.67 | 272.17 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-07:10 | 2092.44 | 20.71 | 94.33 | 302.83 | 1125.89 | 21.59 | 67.33 | 270.50 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1660.22 | 19.56 | 84.17 | 272.67 | 872.70 | 21.08 | 59.00 | 234.17 |
December | 282.67 | 0.51 | 0.48 | 01-DEC-08:39 | 1792.09 | 20.52 | 87.00 | 254.17 | 761.67 | 19.74 | 34.50 | 213.50 |
Annual Sum or Average | 4111.50 | 0.51 | 2123.68 | 20.18 | 1208.00 | 3719.17 | 1047.14 | 20.67 | 750.67 | 3271.50 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 1660.22 | 19.13 | 84.17 | 254.17 | 761.67 | 19.68 | 34.50 | 213.50 | |
Maximum of Months | 403.83 | 0.52 | 0.48 | 2441.43 | 21.84 | 121.50 | 362.00 | 1341.25 | 22.21 | 74.67 | 320.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:09 | 550.11 | 10.66 | 0.00 | 247.00 | 363.92 | 14.27 | 0.00 | 163.83 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-08:50 | 625.82 | 11.50 | 0.00 | 250.17 | 403.23 | 15.03 | 0.00 | 186.17 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-08:50 | 747.91 | 12.86 | 0.00 | 312.33 | 472.07 | 16.33 | 0.00 | 261.00 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:19 | 892.83 | 13.75 | 0.00 | 331.17 | 554.71 | 17.19 | 0.00 | 295.50 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-06:30 | 1054.17 | 15.09 | 26.67 | 364.67 | 615.05 | 18.29 | 25.67 | 334.33 |
June | 388.17 | 0.50 | 0.48 | 01-JUN-06:10 | 1119.73 | 16.91 | 65.67 | 355.00 | 637.40 | 18.41 | 32.83 | 316.83 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:30 | 1204.12 | 15.27 | 26.00 | 373.50 | 672.23 | 18.58 | 26.17 | 339.17 |
August | 348.33 | 0.50 | 0.48 | 01-AUG-06:00 | 1060.99 | 13.98 | 0.00 | 349.33 | 625.91 | 17.39 | 0.00 | 314.00 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:10 | 892.43 | 13.15 | 0.00 | 313.83 | 533.21 | 16.52 | 0.00 | 264.83 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-11:39 | 715.04 | 12.55 | 0.00 | 293.00 | 455.04 | 16.00 | 0.00 | 231.83 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-07:49 | 627.77 | 11.51 | 0.00 | 255.83 | 392.47 | 15.05 | 0.00 | 185.83 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-08:00 | 597.35 | 11.27 | 0.00 | 240.33 | 383.29 | 14.88 | 0.00 | 171.67 |
Annual Sum or Average | 4111.50 | 0.51 | 863.23 | 13.39 | 118.33 | 3686.17 | 520.10 | 16.65 | 84.67 | 3065.00 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 550.11 | 10.66 | 0.00 | 240.33 | 363.92 | 14.27 | 0.00 | 163.83 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1204.12 | 16.91 | 65.67 | 373.50 | 672.23 | 18.58 | 32.83 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.52 | 0.48 | 01-JAN-09:09 | 1836.09 | 20.75 | 91.17 | 270.83 | 1018.16 | 21.53 | 65.83 | 226.67 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:00 | 1700.88 | 18.73 | 70.83 | 265.50 | 887.06 | 19.60 | 46.33 | 230.17 |
March | 362.67 | 0.50 | 0.48 | 01-MAR-08:50 | 2081.05 | 19.99 | 99.17 | 320.17 | 1098.44 | 20.90 | 69.00 | 289.83 |
April | 357.50 | 0.50 | 0.48 | 01-APR-08:50 | 2238.16 | 18.39 | 80.67 | 334.00 | 1237.63 | 19.60 | 51.83 | 302.00 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-07:19 | 2022.83 | 13.25 | 0.00 | 350.17 | 1083.19 | 16.61 | 0.00 | 312.00 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-07:19 | 1709.32 | 12.98 | 0.00 | 334.17 | 799.02 | 16.25 | 0.00 | 292.00 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-07:10 | 1928.53 | 13.93 | 3.67 | 357.50 | 899.72 | 17.06 | 0.00 | 321.00 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:49 | 2068.80 | 17.04 | 56.83 | 341.83 | 1106.48 | 17.48 | 5.50 | 306.67 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:30 | 1733.30 | 18.56 | 80.50 | 314.50 | 918.68 | 19.74 | 51.67 | 278.50 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-11:39 | 2074.94 | 21.27 | 105.17 | 300.50 | 1113.42 | 22.08 | 76.33 | 267.67 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:00 | 1637.47 | 20.56 | 96.50 | 273.33 | 870.08 | 21.39 | 67.33 | 237.33 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:00 | 1877.96 | 22.31 | 96.50 | 265.17 | 1012.01 | 22.72 | 66.83 | 231.33 |
Annual Sum or Average | 4111.50 | 0.51 | 1914.87 | 17.85 | 781.00 | 3727.67 | 1003.21 | 19.38 | 500.67 | 3295.17 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 1637.47 | 12.98 | 0.00 | 265.17 | 799.02 | 16.25 | 0.00 | 226.67 | |
Maximum of Months | 403.83 | 0.52 | 0.48 | 2238.16 | 22.31 | 105.17 | 357.50 | 1237.63 | 22.72 | 76.33 | 321.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.50 | 0.48 | 01-JAN-07:40 | 6612.09 | 35.43 | 274.67 | 292.33 | 1366.72 | 21.37 | 81.00 | 275.50 |
February | 304.33 | 0.50 | 0.48 | 01-FEB-08:09 | 2484.38 | 21.89 | 134.00 | 277.17 | 1072.71 | 16.35 | 0.00 | 251.50 |
March | 362.67 | 0.50 | 0.48 | 01-MAR-07:49 | 1545.93 | 13.93 | 5.67 | 326.33 | 887.81 | 17.11 | 0.00 | 293.17 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:19 | 1207.80 | 13.68 | 0.00 | 325.33 | 714.58 | 17.11 | 0.00 | 292.50 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-07:10 | 1034.82 | 13.11 | 0.00 | 345.83 | 605.05 | 16.51 | 0.00 | 298.83 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-07:10 | 976.23 | 12.34 | 0.00 | 323.50 | 565.77 | 15.77 | 0.00 | 276.17 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1093.79 | 13.24 | 0.00 | 352.33 | 634.25 | 16.68 | 0.00 | 305.33 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:19 | 1296.43 | 13.78 | 0.00 | 342.67 | 736.73 | 17.17 | 0.00 | 303.83 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-06:00 | 1550.13 | 13.65 | 0.00 | 315.67 | 858.08 | 17.07 | 0.00 | 280.00 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-07:40 | 2054.58 | 15.74 | 31.67 | 315.50 | 1060.71 | 17.83 | 9.17 | 287.50 |
November | 314.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3780.39 | 29.68 | 244.67 | 291.00 | 1186.31 | 20.73 | 71.33 | 272.50 |
December | 282.67 | 0.49 | 0.48 | 01-DEC-08:39 | 6279.40 | 35.82 | 278.50 | 278.00 | 1576.25 | 22.88 | 92.50 | 260.67 |
Annual Sum or Average | 4111.50 | 0.51 | 2308.85 | 18.52 | 969.17 | 3785.67 | 906.27 | 17.86 | 254.00 | 3397.50 | ||
Minimum of Months | 282.67 | 0.49 | 0.48 | 976.23 | 12.34 | 0.00 | 277.17 | 565.77 | 15.77 | 0.00 | 251.50 | |
Maximum of Months | 403.83 | 0.53 | 0.48 | 6612.09 | 35.82 | 278.50 | 352.33 | 1576.25 | 22.88 | 92.50 | 305.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.52 | 0.48 | 01-JAN-07:40 | 2125.50 | 21.82 | 102.50 | 267.83 | 1142.38 | 22.19 | 74.17 | 229.00 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-07:49 | 2227.84 | 20.84 | 99.83 | 260.33 | 872.02 | 19.78 | 45.50 | 227.33 |
March | 362.67 | 0.50 | 0.48 | 01-MAR-07:19 | 2132.94 | 19.93 | 98.83 | 322.00 | 1147.62 | 20.84 | 67.50 | 290.00 |
April | 357.50 | 0.51 | 0.48 | 01-APR-06:00 | 2442.92 | 19.75 | 99.83 | 324.17 | 1342.49 | 20.77 | 70.67 | 292.17 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-06:10 | 2253.61 | 19.10 | 103.83 | 355.83 | 995.85 | 19.67 | 57.67 | 312.50 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-05:00 | 2210.20 | 20.29 | 121.50 | 341.50 | 972.12 | 20.00 | 65.00 | 301.83 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:10 | 2176.85 | 19.62 | 115.50 | 362.00 | 998.31 | 20.16 | 63.67 | 320.83 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2135.40 | 19.91 | 97.17 | 345.33 | 1166.72 | 21.07 | 71.00 | 308.67 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-06:40 | 2110.18 | 20.52 | 103.50 | 310.83 | 1118.87 | 21.42 | 74.67 | 272.33 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-07:10 | 2093.60 | 20.68 | 94.33 | 302.83 | 1127.05 | 21.58 | 67.33 | 270.50 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1661.40 | 19.53 | 84.17 | 272.67 | 873.74 | 21.06 | 59.00 | 234.17 |
December | 282.67 | 0.51 | 0.48 | 01-DEC-08:39 | 1793.13 | 20.49 | 87.00 | 254.17 | 762.65 | 19.73 | 34.50 | 213.67 |
Annual Sum or Average | 4111.50 | 0.51 | 2125.13 | 20.16 | 1208.00 | 3719.50 | 1048.32 | 20.66 | 750.67 | 3273.00 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 1661.40 | 19.10 | 84.17 | 254.17 | 762.65 | 19.67 | 34.50 | 213.67 | |
Maximum of Months | 403.83 | 0.52 | 0.48 | 2442.92 | 21.82 | 121.50 | 362.00 | 1342.49 | 22.19 | 74.67 | 320.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-09:09 | 550.50 | 10.62 | 0.00 | 247.00 | 364.33 | 14.26 | 0.00 | 164.17 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-08:50 | 626.37 | 11.47 | 0.00 | 250.17 | 403.72 | 15.01 | 0.00 | 186.33 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-08:50 | 748.64 | 12.83 | 0.00 | 312.33 | 472.68 | 16.31 | 0.00 | 261.67 |
April | 357.50 | 0.51 | 0.48 | 01-APR-07:19 | 893.76 | 13.72 | 0.00 | 331.17 | 555.44 | 17.18 | 0.00 | 295.83 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-06:30 | 1055.50 | 15.06 | 26.67 | 364.83 | 615.96 | 18.28 | 25.67 | 334.33 |
June | 388.17 | 0.50 | 0.48 | 01-JUN-06:10 | 1121.28 | 16.89 | 65.67 | 355.50 | 638.38 | 18.40 | 32.83 | 317.00 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:30 | 1205.67 | 15.24 | 26.00 | 373.50 | 673.27 | 18.57 | 26.17 | 339.50 |
August | 348.33 | 0.50 | 0.48 | 01-AUG-06:00 | 1062.32 | 13.95 | 0.00 | 349.33 | 626.85 | 17.38 | 0.00 | 314.50 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:10 | 893.50 | 13.12 | 0.00 | 313.83 | 533.99 | 16.50 | 0.00 | 265.00 |
October | 323.50 | 0.52 | 0.48 | 02-OCT-11:39 | 715.67 | 12.52 | 0.00 | 293.17 | 455.61 | 15.99 | 0.00 | 232.17 |
November | 314.83 | 0.52 | 0.48 | 01-NOV-07:49 | 628.38 | 11.48 | 0.00 | 256.00 | 392.99 | 15.03 | 0.00 | 186.00 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-08:00 | 597.84 | 11.24 | 0.00 | 240.33 | 383.77 | 14.86 | 0.00 | 171.83 |
Annual Sum or Average | 4111.50 | 0.51 | 864.21 | 13.37 | 118.33 | 3687.17 | 520.83 | 16.64 | 84.67 | 3068.33 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 550.50 | 10.62 | 0.00 | 240.33 | 364.33 | 14.26 | 0.00 | 164.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1205.67 | 16.89 | 65.67 | 373.50 | 673.27 | 18.57 | 32.83 | 339.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.52 | 0.48 | 01-JAN-09:09 | 1836.95 | 20.72 | 91.17 | 271.00 | 1019.04 | 21.51 | 65.83 | 226.83 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:00 | 1701.98 | 18.70 | 70.83 | 265.50 | 888.05 | 19.58 | 46.33 | 230.17 |
March | 362.67 | 0.50 | 0.48 | 01-MAR-08:50 | 2082.25 | 19.96 | 99.17 | 320.17 | 1099.56 | 20.88 | 69.00 | 290.00 |
April | 357.50 | 0.50 | 0.48 | 01-APR-08:50 | 2239.54 | 18.36 | 80.67 | 334.00 | 1238.79 | 19.58 | 51.83 | 302.17 |
May | 389.00 | 0.50 | 0.48 | 01-MAY-07:19 | 2024.44 | 13.21 | 0.00 | 350.17 | 1084.41 | 16.59 | 0.00 | 312.00 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-07:19 | 1711.12 | 12.94 | 0.00 | 334.17 | 800.20 | 16.24 | 0.00 | 292.17 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-07:10 | 1930.40 | 13.90 | 3.67 | 357.67 | 901.04 | 17.05 | 0.00 | 321.17 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:49 | 2070.76 | 17.01 | 56.83 | 342.00 | 1107.91 | 17.47 | 5.50 | 306.67 |
September | 349.67 | 0.51 | 0.48 | 01-SEP-07:30 | 1735.15 | 18.54 | 80.50 | 314.67 | 919.99 | 19.72 | 51.67 | 278.67 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-11:39 | 2076.36 | 21.25 | 105.17 | 300.50 | 1114.63 | 22.06 | 76.33 | 268.00 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:00 | 1638.67 | 20.53 | 96.50 | 273.33 | 871.14 | 21.38 | 67.33 | 237.50 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:00 | 1878.99 | 22.28 | 96.50 | 265.33 | 1013.01 | 22.71 | 66.83 | 231.33 |
Annual Sum or Average | 4111.50 | 0.51 | 1916.34 | 17.82 | 781.00 | 3728.50 | 1004.37 | 19.36 | 500.67 | 3296.67 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 1638.67 | 12.94 | 0.00 | 265.33 | 800.20 | 16.24 | 0.00 | 226.83 | |
Maximum of Months | 403.83 | 0.52 | 0.48 | 2239.54 | 22.28 | 105.17 | 357.67 | 1238.79 | 22.71 | 76.33 | 321.17 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1855813.59 | 2233.59 | 25-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5827795.40 | 9197.72 | 04-FEB-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6005867.65 | 7170.53 | 16-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46828.36 | 198.47 | 27-NOV-05:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5089055.07 | 5041.77 | 15-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18825360.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6005867.65 | 9197.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 44140.58 | 73.57 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44140.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44140.58 | 73.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17591427.16 | 28413.42 | 25-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17671662.21 | 36048.78 | 04-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45565224.00 | 57618.13 | 16-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13753643.67 | 9845.66 | 27-NOV-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 42590933.23 | 56457.95 | 15-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45565224.00 | 57618.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.228156E+09 | 119446.23 | 25-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.508890E+09 | 141987.28 | 04-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167708E+09 | 139772.82 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.332190E+09 | 134628.66 | 15-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.508890E+09 | 141987.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 29768344.74 | 14141.98 | 25-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161824E+09 | 118552.72 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34415059.81 | 16641.55 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71672638.78 | 37180.19 | 15-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161824E+09 | 118552.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155758E+09 | 140055.63 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1840884.37 | 1005.97 | 16-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155758E+09 | 140055.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2508253.20 | 1541.83 | 25-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204441E+09 | 118254.37 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1797321.16 | 1470.42 | 15-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204441E+09 | 118254.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 837377.82 | 1486.62 | 25-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2168134.20 | 2640.20 | 04-FEB-05:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1258047.46 | 2012.87 | 16-MAR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 200773.95 | 531.25 | 13-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2151847.76 | 3484.57 | 15-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6616181.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2168134.20 | 3484.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181831E+09 | 16060.21 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166266E+09 | 15968.65 | 04-FEB-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 97241882.98 | 15965.28 | 16-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36586975.05 | 16000.73 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183909E+09 | 16051.51 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.665836E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.183909E+09 | 16060.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 50332535.88 | 12882.57 | 26-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46078254.28 | 14526.41 | 04-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26153469.02 | 12270.75 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10041082.35 | 12692.97 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 76862817.45 | 14539.73 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76862817.45 | 14539.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 29987442.15 | 11949.81 | 25-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 59087117.47 | 15947.47 | 04-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32654964.30 | 15945.60 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9264425.63 | 12998.03 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 48548378.97 | 15947.56 | 15-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59087117.47 | 15947.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 32280931.03 | 11144.47 | 25-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 59979031.17 | 15095.05 | 04-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17842587.94 | 10969.77 | 16-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9942861.08 | 9562.27 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 50661073.55 | 14400.92 | 15-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59979031.17 | 15095.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.847869E+11 | 0.715382E+11 | 205125.85 | 07-JAN-05:12 | 104044.28 | 0.53 |
February | 0.00 | 0.00 | 0.957804E+11 | 0.807416E+11 | 235559.27 | 11-FEB-06:02 | 136192.33 | 0.56 |
March | 0.00 | 0.00 | 0.130628E+12 | 0.106402E+12 | 233683.87 | 06-MAR-06:03 | 139869.67 | 0.70 |
April | 0.00 | 0.00 | 0.152436E+12 | 0.125204E+12 | 242054.00 | 12-APR-05:02 | 150527.58 | 0.86 |
May | 0.00 | 0.00 | 0.166468E+12 | 0.127317E+12 | 256251.06 | 27-MAY-05:02 | 141209.17 | 0.78 |
June | 0.00 | 0.00 | 0.188139E+12 | 0.140623E+12 | 253627.20 | 12-JUN-04:23 | 156354.56 | 0.86 |
July | 0.00 | 0.00 | 0.201836E+12 | 0.151654E+12 | 255697.50 | 31-JUL-04:23 | 157947.82 | 0.87 |
August | 0.00 | 0.00 | 0.217001E+12 | 0.163921E+12 | 247282.94 | 14-AUG-05:02 | 150920.57 | 0.89 |
September | 0.00 | 0.00 | 0.176705E+12 | 0.129567E+12 | 250078.36 | 20-SEP-05:02 | 149142.56 | 0.80 |
October | 0.00 | 0.00 | 0.174182E+12 | 0.130526E+12 | 245102.03 | 02-OCT-05:02 | 154156.29 | 0.80 |
November | 0.00 | 0.00 | 0.147239E+12 | 0.113153E+12 | 234462.89 | 22-NOV-06:02 | 145404.72 | 0.74 |
December | 0.00 | 0.00 | 0.117284E+12 | 0.928015E+11 | 238836.29 | 11-DEC-06:02 | 149949.16 | 0.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.185248E+13 | 0.143345E+13 | 0.76 | |||
Minimum of Months | 0.00 | 0.00 | 0.847869E+11 | 0.715382E+11 | 205125.85 | 104044.28 | 0.53 | |
Maximum of Months | 0.00 | 0.00 | 0.217001E+12 | 0.163921E+12 | 256251.06 | 157947.82 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.667192E+12 | 0.543879E+12 | 1929256.37 | 14-JAN-06:02 | 1115830.52 | 0.51 |
February | 0.00 | 0.00 | 0.735324E+12 | 0.598716E+12 | 2522921.32 | 11-FEB-06:02 | 1309348.57 | 0.52 |
March | 0.00 | 0.00 | 0.932331E+12 | 0.750190E+12 | 2502973.23 | 10-MAR-06:02 | 1312611.16 | 0.55 |
April | 0.00 | 0.00 | 0.109508E+13 | 0.886054E+12 | 2402475.50 | 12-APR-05:02 | 1388366.61 | 0.65 |
May | 0.00 | 0.00 | 0.145168E+13 | 0.109678E+13 | 2662512.72 | 27-MAY-05:02 | 1281048.62 | 0.69 |
June | 0.00 | 0.00 | 0.160116E+13 | 0.117016E+13 | 2528302.85 | 19-JUN-05:03 | 1370291.81 | 0.74 |
July | 0.00 | 0.00 | 0.165077E+13 | 0.120939E+13 | 2490563.00 | 03-JUL-05:02 | 1392399.17 | 0.75 |
August | 0.00 | 0.00 | 0.166530E+13 | 0.120515E+13 | 2464605.44 | 14-AUG-05:02 | 1357118.05 | 0.74 |
September | 0.00 | 0.00 | 0.156607E+13 | 0.111858E+13 | 2515213.52 | 20-SEP-05:02 | 1370076.03 | 0.72 |
October | 0.00 | 0.00 | 0.142035E+13 | 0.104761E+13 | 2554687.50 | 02-OCT-05:02 | 1380228.52 | 0.66 |
November | 0.00 | 0.00 | 0.110321E+13 | 0.826447E+12 | 2501916.00 | 22-NOV-06:02 | 1334357.77 | 0.59 |
December | 0.00 | 0.00 | 0.739035E+12 | 0.580022E+12 | 2407570.40 | 07-DEC-06:02 | 1350559.33 | 0.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.146275E+14 | 0.110330E+14 | 0.64 | |||
Minimum of Months | 0.00 | 0.00 | 0.667192E+12 | 0.543879E+12 | 1929256.37 | 1115830.52 | 0.51 | |
Maximum of Months | 0.00 | 0.00 | 0.166530E+13 | 0.120939E+13 | 2662512.72 | 1392399.17 | 0.75 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.619223E+11 | 0.499780E+11 | 207617.01 | 14-JAN-06:02 | 117248.31 | 0.50 |
February | 0.00 | 0.00 | 0.737786E+11 | 0.602281E+11 | 265747.76 | 11-FEB-06:02 | 133858.11 | 0.50 |
March | 0.00 | 0.00 | 0.966864E+11 | 0.777867E+11 | 258387.38 | 10-MAR-06:02 | 129099.04 | 0.54 |
April | 0.00 | 0.00 | 0.117905E+12 | 0.966179E+11 | 255820.67 | 12-APR-05:02 | 146158.64 | 0.64 |
May | 0.00 | 0.00 | 0.159630E+12 | 0.123014E+12 | 288500.50 | 27-MAY-05:02 | 137250.09 | 0.69 |
June | 0.00 | 0.00 | 0.176110E+12 | 0.131801E+12 | 266365.19 | 19-JUN-05:03 | 144573.86 | 0.75 |
July | 0.00 | 0.00 | 0.183225E+12 | 0.137898E+12 | 259645.26 | 03-JUL-05:02 | 148660.82 | 0.75 |
August | 0.00 | 0.00 | 0.181191E+12 | 0.134320E+12 | 263413.58 | 14-AUG-05:02 | 147034.20 | 0.74 |
September | 0.00 | 0.00 | 0.169133E+12 | 0.123834E+12 | 268051.56 | 20-SEP-05:02 | 144831.82 | 0.73 |
October | 0.00 | 0.00 | 0.147821E+12 | 0.110777E+12 | 270287.07 | 02-OCT-05:02 | 144525.51 | 0.66 |
November | 0.00 | 0.00 | 0.111377E+12 | 0.838394E+11 | 261133.47 | 22-NOV-06:02 | 132152.82 | 0.58 |
December | 0.00 | 0.00 | 0.712302E+11 | 0.552438E+11 | 251731.82 | 11-DEC-06:02 | 137924.85 | 0.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.155001E+13 | 0.118534E+13 | 0.63 | |||
Minimum of Months | 0.00 | 0.00 | 0.619223E+11 | 0.499780E+11 | 207617.01 | 117248.31 | 0.50 | |
Maximum of Months | 0.00 | 0.00 | 0.183225E+12 | 0.137898E+12 | 288500.50 | 148660.82 | 0.75 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.712654E+11 | 0.645935E+11 | 157806.68 | 01-JAN-16:12 | 86254.92 | 0.52 |
February | 0.00 | 0.00 | 0.686124E+11 | 0.615059E+11 | 144498.97 | 11-FEB-06:02 | 77127.14 | 0.51 |
March | 0.00 | 0.00 | 0.794363E+11 | 0.696871E+11 | 152146.65 | 06-MAR-05:53 | 77027.01 | 0.53 |
April | 0.00 | 0.00 | 0.821524E+11 | 0.705007E+11 | 159726.11 | 16-APR-16:22 | 94339.14 | 0.56 |
May | 0.00 | 0.00 | 0.104497E+12 | 0.805707E+11 | 182861.71 | 29-MAY-10:40 | 87189.73 | 0.60 |
June | 0.00 | 0.00 | 0.118588E+12 | 0.829685E+11 | 174334.81 | 26-JUN-03:15 | 75456.11 | 0.62 |
July | 0.00 | 0.00 | 0.125039E+12 | 0.866678E+11 | 177828.72 | 09-JUL-21:00 | 85116.52 | 0.60 |
August | 0.00 | 0.00 | 0.138036E+12 | 0.955137E+11 | 184986.85 | 21-AUG-03:15 | 79300.97 | 0.64 |
September | 0.00 | 0.00 | 0.119528E+12 | 0.838455E+11 | 178370.75 | 17-SEP-21:10 | 86179.96 | 0.62 |
October | 0.00 | 0.00 | 0.113557E+12 | 0.847055E+11 | 180685.71 | 29-OCT-17:00 | 83615.53 | 0.61 |
November | 0.00 | 0.00 | 0.974660E+11 | 0.766013E+11 | 176235.65 | 05-NOV-15:22 | 84797.97 | 0.57 |
December | 0.00 | 0.00 | 0.761846E+11 | 0.672468E+11 | 170207.59 | 26-DEC-02:43 | 73636.38 | 0.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.119436E+13 | 0.924407E+12 | 0.58 | |||
Minimum of Months | 0.00 | 0.00 | 0.686124E+11 | 0.615059E+11 | 144498.97 | 73636.38 | 0.51 | |
Maximum of Months | 0.00 | 0.00 | 0.138036E+12 | 0.955137E+11 | 184986.85 | 94339.14 | 0.64 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.338192E+12 | 0.328619E+12 | 139395.19 | 02-JAN-15:00 | 129569.26 | 0.00 |
February | 0.00 | 0.00 | 0.528374E+12 | 0.518496E+12 | 229391.98 | 02-FEB-15:05 | 218469.16 | 0.00 |
March | 0.00 | 0.00 | 0.832403E+12 | 0.819635E+12 | 396026.23 | 31-MAR-23:05 | 392284.64 | 0.00 |
April | 0.00 | 0.00 | 0.104357E+13 | 0.103050E+13 | 423926.01 | 25-APR-16:00 | 405697.39 | 0.00 |
May | 0.00 | 0.00 | 0.358117E+12 | 0.336528E+12 | 228579.87 | 31-MAY-23:03 | 211236.42 | 0.00 |
June | 0.00 | 0.00 | 0.590059E+12 | 0.563327E+12 | 315994.97 | 30-JUN-23:05 | 302782.53 | 0.00 |
July | 0.00 | 0.00 | 0.856157E+12 | 0.828928E+12 | 401069.98 | 31-JUL-24:00 | 390976.24 | 0.00 |
August | 0.00 | 0.00 | 0.109039E+13 | 0.106475E+13 | 424234.21 | 23-AUG-17:00 | 405856.42 | 0.00 |
September | 0.00 | 0.00 | 0.354522E+12 | 0.329282E+12 | 224589.71 | 30-SEP-23:05 | 212059.67 | 0.00 |
October | 0.00 | 0.00 | 0.606564E+12 | 0.582787E+12 | 312352.52 | 31-OCT-23:10 | 301669.43 | 0.00 |
November | 0.00 | 0.00 | 0.816103E+12 | 0.798082E+12 | 325188.60 | 30-NOV-17:00 | 312004.02 | 0.00 |
December | 0.00 | 0.00 | 0.107723E+13 | 0.106520E+13 | 412227.95 | 08-DEC-17:10 | 400211.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.849168E+13 | 0.826613E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.338192E+12 | 0.328619E+12 | 139395.19 | 129569.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109039E+13 | 0.106520E+13 | 424234.21 | 405856.42 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.569109E+10 | 0.531551E+10 | 2877.44 | 02-JAN-15:00 | 2476.15 | 0.00 |
February | 0.00 | 0.00 | 0.997846E+10 | 0.956848E+10 | 4940.38 | 19-FEB-17:22 | 4644.07 | 0.00 |
March | 0.00 | 0.00 | 0.162874E+11 | 0.157313E+11 | 7827.53 | 31-MAR-23:05 | 7642.36 | 0.00 |
April | 0.00 | 0.00 | 0.209653E+11 | 0.203448E+11 | 8677.76 | 01-APR-18:10 | 8271.51 | 0.00 |
May | 0.00 | 0.00 | 0.691923E+10 | 0.604565E+10 | 4761.79 | 31-MAY-23:03 | 4000.21 | 0.00 |
June | 0.00 | 0.00 | 0.119334E+11 | 0.107890E+11 | 6484.94 | 30-JUN-23:05 | 5886.45 | 0.00 |
July | 0.00 | 0.00 | 0.175149E+11 | 0.163050E+11 | 8489.36 | 31-JUL-23:03 | 7861.21 | 0.00 |
August | 0.00 | 0.00 | 0.226147E+11 | 0.213712E+11 | 8831.85 | 23-AUG-16:50 | 8218.86 | 0.00 |
September | 0.00 | 0.00 | 0.697517E+10 | 0.594531E+10 | 4584.61 | 30-SEP-23:05 | 4036.32 | 0.00 |
October | 0.00 | 0.00 | 0.120980E+11 | 0.110861E+11 | 6254.45 | 31-OCT-23:10 | 5772.42 | 0.00 |
November | 0.00 | 0.00 | 0.161772E+11 | 0.153855E+11 | 6873.80 | 07-NOV-17:00 | 6459.15 | 0.00 |
December | 0.00 | 0.00 | 0.212296E+11 | 0.206664E+11 | 8783.14 | 08-DEC-17:00 | 8283.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168384E+12 | 0.158554E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.569109E+10 | 0.531551E+10 | 2877.44 | 2476.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.226147E+11 | 0.213712E+11 | 8831.85 | 8283.24 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.483290E+11 | 0.446910E+11 | 27092.96 | 02-JAN-15:00 | 23113.21 | 0.00 |
February | 0.00 | 0.00 | 0.908540E+11 | 0.867957E+11 | 46149.12 | 19-FEB-17:22 | 43205.09 | 0.00 |
March | 0.00 | 0.00 | 0.153366E+12 | 0.147818E+12 | 75303.62 | 31-MAR-23:05 | 73419.58 | 0.00 |
April | 0.00 | 0.00 | 0.199670E+12 | 0.193457E+12 | 82791.22 | 01-APR-18:00 | 78627.80 | 0.00 |
May | 0.00 | 0.00 | 0.652276E+11 | 0.565891E+11 | 46619.31 | 31-MAY-23:03 | 38795.19 | 0.00 |
June | 0.00 | 0.00 | 0.113913E+12 | 0.102518E+12 | 62857.30 | 30-JUN-23:05 | 56789.11 | 0.00 |
July | 0.00 | 0.00 | 0.167194E+12 | 0.155119E+12 | 81647.65 | 31-JUL-23:03 | 75313.02 | 0.00 |
August | 0.00 | 0.00 | 0.214709E+12 | 0.202268E+12 | 83893.47 | 23-AUG-16:30 | 77729.93 | 0.00 |
September | 0.00 | 0.00 | 0.655506E+11 | 0.553726E+11 | 44424.49 | 30-SEP-23:05 | 38832.62 | 0.00 |
October | 0.00 | 0.00 | 0.115006E+12 | 0.104937E+12 | 59580.06 | 31-OCT-23:10 | 54672.01 | 0.00 |
November | 0.00 | 0.00 | 0.152713E+12 | 0.144816E+12 | 65662.38 | 07-NOV-17:00 | 61525.78 | 0.00 |
December | 0.00 | 0.00 | 0.198685E+12 | 0.193049E+12 | 83710.08 | 08-DEC-17:00 | 78666.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158522E+13 | 0.148743E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.483290E+11 | 0.446910E+11 | 27092.96 | 23113.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.214709E+12 | 0.202268E+12 | 83893.47 | 78666.98 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.437245E+10 | 0.401605E+10 | 2764.04 | 02-JAN-15:00 | 2363.32 | 0.00 |
February | 0.00 | 0.00 | 0.882899E+10 | 0.842498E+10 | 4805.44 | 19-FEB-17:22 | 4509.20 | 0.00 |
March | 0.00 | 0.00 | 0.152032E+11 | 0.146497E+11 | 7491.69 | 31-MAR-23:05 | 7303.70 | 0.00 |
April | 0.00 | 0.00 | 0.200087E+11 | 0.193886E+11 | 8465.00 | 23-APR-18:13 | 8213.78 | 0.00 |
May | 0.00 | 0.00 | 0.664122E+10 | 0.577504E+10 | 4671.74 | 31-MAY-23:03 | 3892.85 | 0.00 |
June | 0.00 | 0.00 | 0.115242E+11 | 0.103842E+11 | 6299.95 | 30-JUN-23:05 | 5694.58 | 0.00 |
July | 0.00 | 0.00 | 0.168905E+11 | 0.156833E+11 | 8184.30 | 31-JUL-23:03 | 7552.42 | 0.00 |
August | 0.00 | 0.00 | 0.215998E+11 | 0.203561E+11 | 8533.33 | 23-AUG-16:30 | 7912.09 | 0.00 |
September | 0.00 | 0.00 | 0.667298E+10 | 0.565264E+10 | 4509.83 | 30-SEP-23:05 | 3959.04 | 0.00 |
October | 0.00 | 0.00 | 0.115504E+11 | 0.105443E+11 | 5901.52 | 31-OCT-23:10 | 5410.06 | 0.00 |
November | 0.00 | 0.00 | 0.151325E+11 | 0.143444E+11 | 6638.84 | 07-NOV-17:00 | 6225.52 | 0.00 |
December | 0.00 | 0.00 | 0.195579E+11 | 0.189962E+11 | 8446.29 | 08-DEC-17:00 | 7942.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157983E+12 | 0.148216E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.437245E+10 | 0.401605E+10 | 2764.04 | 2363.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215998E+11 | 0.203561E+11 | 8533.33 | 8213.78 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 151.88 | 156849.10 | 25-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 565.66 | 734069.89 | 04-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 161.87 | 358364.59 | 16-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 31.53 | 90124.36 | 13-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 299.12 | 375846.89 | 15-DEC-06:02 |
Annual Sum or Average | 0.00 | 98.04 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 565.66 | 734069.89 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 347357.59 | 2038172.78 | 14-JAN-06:06 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 433687.69 | 2827101.71 | 11-FEB-06:04 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 492197.75 | 2869427.09 | 10-MAR-06:04 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 595204.04 | 2158088.50 | 12-APR-05:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 750194.00 | 3407357.99 | 27-MAY-05:04 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 850337.24 | 2719573.08 | 22-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 848940.87 | 2637721.28 | 24-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 867210.44 | 3136372.92 | 28-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 828893.82 | 2970639.61 | 26-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 734338.79 | 2803541.49 | 03-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 599159.70 | 2994101.80 | 22-NOV-06:04 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 397735.92 | 2972302.60 | 11-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 646379.00 | 0.00 | ||||
Minimum of Months | 347357.59 | 2038172.78 | 0.00 | 0.00 | ||
Maximum of Months | 867210.44 | 3407357.99 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 351727.84 | 3936228.73 | 14-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 435938.48 | 3945083.81 | 11-FEB-05:01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 494235.09 | 3955041.51 | 06-MAR-05:12 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 594585.96 | 3902780.81 | 13-APR-05:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 749196.80 | 3939426.56 | 25-MAY-04:12 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 849409.20 | 4010447.10 | 06-JUN-04:11 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 848098.16 | 4037536.41 | 03-JUL-03:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 866459.59 | 4122653.01 | 28-AUG-03:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 829491.99 | 4033355.92 | 13-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 746511.76 | 4118736.14 | 02-OCT-03:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 617170.68 | 4003286.65 | 04-NOV-05:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 402041.84 | 4021331.11 | 26-DEC-05:12 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 649677.85 | 0.00 | ||||
Minimum of Months | 351727.84 | 3902780.81 | 0.00 | 0.00 | ||
Maximum of Months | 866459.59 | 4122653.01 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 363079.26 | 860511.54 | 02-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 632360.70 | 1085557.39 | 11-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 873196.10 | 1324336.38 | 13-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1218749.54 | 1668501.59 | 17-APR-15:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 713197.44 | 1144974.53 | 22-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1004866.51 | 1243350.38 | 11-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1250885.73 | 1665134.47 | 29-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1450151.54 | 1773051.90 | 23-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 777471.37 | 1043945.67 | 20-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 928424.68 | 1245984.32 | 09-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 987025.17 | 1354844.62 | 17-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1010147.05 | 1494450.88 | 10-DEC-14:59 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 935920.58 | 0.00 | ||||
Minimum of Months | 363079.26 | 860511.54 | 0.00 | 0.00 | ||
Maximum of Months | 1450151.54 | 1773051.90 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 11593.90 | 37936.24 | 19-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11558.74 | 37797.54 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11853.91 | 37064.09 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:05 | 10746.54 | 35486.96 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10580.80 | 33953.24 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 10424.16 | 32403.81 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 9561.35 | 31477.05 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 10437.88 | 32166.26 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 10198.03 | 33530.13 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 10635.38 | 35279.45 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11231.24 | 36791.35 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 11212.89 | 37679.12 | 28-DEC-12:30 |
Annual Sum or Average | 0.00 | 10832.34 | ||||
Minimum of Months | 0.00 | 0.00 | 9561.35 | 31477.05 | ||
Maximum of Months | 0.00 | 0.00 | 11853.91 | 37936.24 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 529176.81 | 4869711.10 | 02-JAN-14:10 | 542.34 | 127805.95 | 26-JAN-06:30 |
February | 665385.50 | 4177555.60 | 11-FEB-06:04 | 1025.53 | 155737.97 | 04-FEB-07:50 |
March | 826334.85 | 5342572.37 | 14-MAR-10:05 | 565.78 | 151094.25 | 16-MAR-05:50 |
April | 1056609.15 | 5123559.84 | 13-APR-12:05 | 387.02 | 83171.91 | 02-APR-01:30 |
May | 1787746.25 | 6306660.65 | 31-MAY-05:04 | 2.52 | 11266.31 | 08-MAY-04:10 |
June | 2515354.10 | 6588940.56 | 28-JUN-12:05 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 2633385.11 | 6448873.36 | 20-JUL-12:05 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2691316.26 | 6433134.66 | 28-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2417269.75 | 5900378.65 | 20-SEP-05:04 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1878598.17 | 6691683.34 | 02-OCT-05:04 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1301148.36 | 5711239.10 | 30-NOV-13:05 | 386.13 | 108777.99 | 13-NOV-05:50 |
December | 691770.27 | 4663240.78 | 08-DEC-14:05 | 713.39 | 140596.30 | 15-DEC-07:00 |
Annual Sum or Average | 1587754.50 | 297.14 | ||||
Minimum of Months | 529176.81 | 4177555.60 | 0.00 | 0.00 | ||
Maximum of Months | 2691316.26 | 6691683.34 | 1025.53 | 155737.97 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142891E+11 | 0.84 | 8777.13 | 01-JAN-00:15 | 1.37 |
February | 0.126762E+11 | 0.82 | 8777.13 | 01-FEB-05:13 | 1.38 |
March | 0.140689E+11 | 0.82 | 8777.13 | 01-MAR-05:12 | 1.38 |
April | 0.131557E+11 | 0.79 | 8777.13 | 01-APR-04:12 | 1.38 |
May | 0.144525E+11 | 0.84 | 8777.13 | 01-MAY-00:35 | 1.37 |
June | 0.143129E+11 | 0.86 | 8777.13 | 01-JUN-03:02 | 1.38 |
July | 0.143613E+11 | 0.84 | 8777.13 | 01-JUL-03:02 | 1.38 |
August | 0.154769E+11 | 0.90 | 8777.13 | 01-AUG-03:03 | 1.38 |
September | 0.144632E+11 | 0.87 | 8777.13 | 01-SEP-03:02 | 1.38 |
October | 0.147600E+11 | 0.86 | 8777.13 | 01-OCT-15:05 | 1.36 |
November | 0.142317E+11 | 0.86 | 8777.13 | 01-NOV-04:12 | 1.38 |
December | 0.141945E+11 | 0.83 | 8777.13 | 01-DEC-05:12 | 1.38 |
Annual Sum or Average | 0.170443E+12 | 0.85 | |||
Minimum of Months | 0.126762E+11 | 0.79 | 8777.13 | 1.36 | |
Maximum of Months | 0.154769E+11 | 0.90 | 8777.13 | 1.38 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.603393E+10 | 0.40 | 19460.04 | 02-JAN-06:03 | 1.76 |
February | 0.678248E+10 | 0.45 | 19460.04 | 10-FEB-06:02 | 1.76 |
March | 0.963278E+10 | 0.57 | 19460.04 | 04-MAR-06:02 | 1.76 |
April | 0.114755E+11 | 0.67 | 19460.04 | 01-APR-05:02 | 1.76 |
May | 0.111390E+11 | 0.62 | 19460.04 | 02-MAY-04:12 | 1.76 |
June | 0.124762E+11 | 0.70 | 19460.04 | 01-JUN-05:02 | 1.76 |
July | 0.139263E+11 | 0.73 | 19460.04 | 01-JUL-05:02 | 1.76 |
August | 0.152444E+11 | 0.77 | 19460.04 | 01-AUG-05:03 | 1.75 |
September | 0.101193E+11 | 0.61 | 19460.04 | 01-SEP-05:02 | 1.76 |
October | 0.960757E+10 | 0.59 | 19460.04 | 03-OCT-05:02 | 1.76 |
November | 0.876953E+10 | 0.55 | 19460.04 | 01-NOV-05:02 | 1.76 |
December | 0.788265E+10 | 0.51 | 19460.04 | 08-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.123090E+12 | 0.60 | |||
Minimum of Months | 0.603393E+10 | 0.40 | 19460.04 | 1.75 | |
Maximum of Months | 0.152444E+11 | 0.77 | 19460.04 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.426967E+11 | 0.35 | 182185.91 | 14-JAN-06:02 | 1.75 |
February | 0.448102E+11 | 0.37 | 182185.91 | 17-FEB-06:03 | 1.76 |
March | 0.625878E+11 | 0.43 | 182185.91 | 06-MAR-05:12 | 1.75 |
April | 0.740257E+11 | 0.48 | 182185.91 | 01-APR-05:02 | 1.76 |
May | 0.949182E+11 | 0.55 | 182185.91 | 01-MAY-05:03 | 1.76 |
June | 0.100310E+12 | 0.60 | 182185.91 | 01-JUN-03:02 | 1.76 |
July | 0.102053E+12 | 0.60 | 182185.91 | 03-JUL-04:23 | 1.75 |
August | 0.986283E+11 | 0.58 | 182185.91 | 02-AUG-05:02 | 1.76 |
September | 0.827597E+11 | 0.54 | 182185.91 | 01-SEP-05:02 | 1.76 |
October | 0.725706E+11 | 0.47 | 182185.91 | 02-OCT-03:02 | 1.75 |
November | 0.572939E+11 | 0.41 | 182185.91 | 04-NOV-05:03 | 1.75 |
December | 0.440596E+11 | 0.35 | 182185.91 | 01-DEC-06:03 | 1.76 |
Annual Sum or Average | 0.876714E+12 | 0.48 | |||
Minimum of Months | 0.426967E+11 | 0.35 | 182185.91 | 1.75 | |
Maximum of Months | 0.102053E+12 | 0.60 | 182185.91 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.375109E+10 | 0.32 | 19977.51 | 14-JAN-06:02 | 1.75 |
February | 0.429941E+10 | 0.35 | 17997.46 | 11-FEB-06:02 | 1.64 |
March | 0.620603E+10 | 0.41 | 19977.51 | 06-MAR-05:12 | 1.75 |
April | 0.782688E+10 | 0.47 | 19977.51 | 12-APR-05:02 | 1.76 |
May | 0.103348E+11 | 0.55 | 19977.51 | 03-MAY-05:02 | 1.76 |
June | 0.109669E+11 | 0.60 | 19977.51 | 01-JUN-05:02 | 1.76 |
July | 0.114594E+11 | 0.61 | 19977.51 | 01-JUL-05:02 | 1.76 |
August | 0.108827E+11 | 0.59 | 19977.51 | 02-AUG-05:02 | 1.76 |
September | 0.906454E+10 | 0.54 | 19977.51 | 01-SEP-05:02 | 1.76 |
October | 0.744764E+10 | 0.46 | 19977.51 | 03-OCT-05:02 | 1.76 |
November | 0.560484E+10 | 0.39 | 19977.51 | 10-NOV-06:02 | 1.76 |
December | 0.407988E+10 | 0.33 | 19977.51 | 11-DEC-05:12 | 1.75 |
Annual Sum or Average | 0.919241E+11 | 0.47 | |||
Minimum of Months | 0.375109E+10 | 0.32 | 17997.46 | 1.64 | |
Maximum of Months | 0.114594E+11 | 0.61 | 19977.51 | 1.76 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.945177E+11 | 1.35 | 35288.85 | 01-JAN-00:05 | 1.35 |
February | 0.853708E+11 | 1.35 | 35288.85 | 01-FEB-00:10 | 1.35 |
March | 0.945177E+11 | 1.35 | 35288.85 | 01-MAR-00:10 | 1.35 |
April | 0.914687E+11 | 1.35 | 35288.85 | 01-APR-00:05 | 1.35 |
May | 0.945177E+11 | 1.35 | 35288.85 | 01-MAY-00:05 | 1.35 |
June | 0.914687E+11 | 1.35 | 35288.85 | 01-JUN-00:05 | 1.35 |
July | 0.945177E+11 | 1.35 | 35288.85 | 01-JUL-00:10 | 1.35 |
August | 0.945177E+11 | 1.35 | 35288.85 | 01-AUG-00:05 | 1.35 |
September | 0.914687E+11 | 1.35 | 35288.85 | 01-SEP-00:05 | 1.35 |
October | 0.945177E+11 | 1.35 | 35288.85 | 01-OCT-00:05 | 1.35 |
November | 0.914687E+11 | 1.35 | 35288.85 | 01-NOV-00:10 | 1.35 |
December | 0.945177E+11 | 1.35 | 35288.85 | 01-DEC-00:05 | 1.35 |
Annual Sum or Average | 0.111287E+13 | 1.35 | |||
Minimum of Months | 0.853708E+11 | 1.35 | 35288.85 | 1.35 | |
Maximum of Months | 0.945177E+11 | 1.35 | 35288.85 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138887E+10 | 0.91 | 518.54 | 01-JAN-00:05 | 0.91 |
February | 0.125446E+10 | 0.91 | 518.54 | 01-FEB-00:10 | 0.91 |
March | 0.138887E+10 | 0.91 | 518.54 | 01-MAR-00:10 | 0.91 |
April | 0.134407E+10 | 0.91 | 518.54 | 01-APR-00:05 | 0.91 |
May | 0.138887E+10 | 0.91 | 518.54 | 01-MAY-00:05 | 0.91 |
June | 0.134407E+10 | 0.91 | 518.54 | 01-JUN-00:05 | 0.91 |
July | 0.138887E+10 | 0.91 | 518.54 | 01-JUL-00:10 | 0.91 |
August | 0.138887E+10 | 0.91 | 518.54 | 01-AUG-00:05 | 0.91 |
September | 0.134407E+10 | 0.91 | 518.54 | 01-SEP-00:05 | 0.91 |
October | 0.138887E+10 | 0.91 | 518.54 | 01-OCT-00:05 | 0.91 |
November | 0.134407E+10 | 0.91 | 518.54 | 01-NOV-00:10 | 0.91 |
December | 0.138887E+10 | 0.91 | 518.54 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.163528E+11 | 0.91 | |||
Minimum of Months | 0.125446E+10 | 0.91 | 518.54 | 0.91 | |
Maximum of Months | 0.138887E+10 | 0.91 | 518.54 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132487E+11 | 0.91 | 4946.51 | 01-JAN-00:05 | 0.91 |
February | 0.119666E+11 | 0.91 | 4946.51 | 01-FEB-00:10 | 0.91 |
March | 0.132487E+11 | 0.91 | 4946.51 | 01-MAR-00:10 | 0.91 |
April | 0.128214E+11 | 0.91 | 4946.51 | 01-APR-00:05 | 0.91 |
May | 0.132487E+11 | 0.91 | 4946.51 | 01-MAY-00:05 | 0.91 |
June | 0.128214E+11 | 0.91 | 4946.51 | 01-JUN-00:05 | 0.91 |
July | 0.132487E+11 | 0.91 | 4946.51 | 01-JUL-00:10 | 0.91 |
August | 0.132487E+11 | 0.91 | 4946.51 | 01-AUG-00:05 | 0.91 |
September | 0.128214E+11 | 0.91 | 4946.51 | 01-SEP-00:05 | 0.91 |
October | 0.132487E+11 | 0.91 | 4946.51 | 01-OCT-00:05 | 0.91 |
November | 0.128214E+11 | 0.91 | 4946.51 | 01-NOV-00:10 | 0.91 |
December | 0.132487E+11 | 0.91 | 4946.51 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.155993E+12 | 0.91 | |||
Minimum of Months | 0.119666E+11 | 0.91 | 4946.51 | 0.91 | |
Maximum of Months | 0.132487E+11 | 0.91 | 4946.51 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135217E+10 | 0.91 | 504.84 | 01-JAN-00:05 | 0.91 |
February | 0.122132E+10 | 0.91 | 504.84 | 01-FEB-00:10 | 0.91 |
March | 0.135217E+10 | 0.91 | 504.84 | 01-MAR-00:10 | 0.91 |
April | 0.130855E+10 | 0.91 | 504.84 | 01-APR-00:05 | 0.91 |
May | 0.135217E+10 | 0.91 | 504.84 | 01-MAY-00:05 | 0.91 |
June | 0.130855E+10 | 0.91 | 504.84 | 01-JUN-00:05 | 0.91 |
July | 0.135217E+10 | 0.91 | 504.84 | 01-JUL-00:10 | 0.91 |
August | 0.135217E+10 | 0.91 | 504.84 | 01-AUG-00:05 | 0.91 |
September | 0.130855E+10 | 0.91 | 504.84 | 01-SEP-00:05 | 0.91 |
October | 0.135217E+10 | 0.91 | 504.84 | 01-OCT-00:05 | 0.91 |
November | 0.130855E+10 | 0.91 | 504.84 | 01-NOV-00:10 | 0.91 |
December | 0.135217E+10 | 0.91 | 504.84 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.159207E+11 | 0.91 | |||
Minimum of Months | 0.122132E+10 | 0.91 | 504.84 | 0.91 | |
Maximum of Months | 0.135217E+10 | 0.91 | 504.84 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 2416218.45 | 2196342.57 | 1150.12 | 25-JAN-06:03 | 1045.46 | 1045.46 | 55.23 | 1.40 |
February | 6018320.35 | 5470653.20 | 2415.95 | 04-FEB-06:03 | 2196.10 | 2196.10 | 42.22 | 4.41 |
March | 1907428.52 | 1733852.52 | 1308.15 | 16-MAR-05:03 | 1189.11 | 1189.11 | 30.40 | 1.66 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 26.77 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 26.77 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 26.77 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 26.77 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 26.77 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 26.77 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 26.77 | 0.00 |
November | 349717.52 | 317893.23 | 367.93 | 13-NOV-06:03 | 334.45 | 334.45 | 27.78 | 0.40 |
December | 3383266.15 | 3075388.93 | 1385.86 | 15-DEC-06:02 | 1259.75 | 1259.75 | 31.74 | 1.79 |
Annual Sum or Average | 14074950.99 | 12794130.45 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.77 | 0.00 | |
Maximum of Months | 6018320.35 | 5470653.20 | 2415.95 | 2196.10 | 2196.10 | 55.23 | 4.41 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.712481E+09 | 0.647645E+09 | 13334.12 | 02-JAN-06:03 | 12120.72 | 12120.72 | 9.86 | 81.99 |
February | 0.809986E+09 | 0.736277E+09 | 13334.12 | 02-FEB-06:03 | 12120.72 | 12120.72 | 10.10 | 81.99 |
March | 0.973948E+09 | 0.885318E+09 | 13334.12 | 04-MAR-06:02 | 12120.72 | 12120.72 | 9.87 | 81.99 |
April | 0.103966E+10 | 0.945052E+09 | 13334.12 | 01-APR-05:02 | 12120.72 | 12120.72 | 9.76 | 81.99 |
May | 0.142329E+10 | 0.129377E+10 | 13334.12 | 01-MAY-05:03 | 12120.72 | 12120.72 | 10.04 | 81.99 |
June | 0.157393E+10 | 0.143071E+10 | 13334.12 | 01-JUN-05:02 | 12120.72 | 12120.72 | 9.93 | 81.99 |
July | 0.165150E+10 | 0.150121E+10 | 13334.12 | 01-JUL-05:02 | 12120.72 | 12120.72 | 9.89 | 81.99 |
August | 0.178123E+10 | 0.161914E+10 | 13334.12 | 01-AUG-05:03 | 12120.72 | 12120.72 | 10.65 | 81.99 |
September | 0.177798E+10 | 0.161619E+10 | 13334.12 | 01-SEP-05:02 | 12120.72 | 12120.72 | 9.82 | 81.99 |
October | 0.198682E+10 | 0.180602E+10 | 13334.12 | 02-OCT-05:02 | 12120.72 | 12120.72 | 6.72 | 81.99 |
November | 0.167130E+10 | 0.151921E+10 | 13334.12 | 02-NOV-05:02 | 12120.72 | 12120.72 | 9.60 | 81.99 |
December | 0.860562E+09 | 0.782251E+09 | 13334.12 | 01-DEC-06:03 | 12120.72 | 12120.72 | 10.02 | 81.99 |
Annual Sum or Average | 0.162627E+11 | 0.147828E+11 | ||||||
Minimum of Months | 0.712481E+09 | 0.647645E+09 | 13334.12 | 12120.72 | 12120.72 | 6.72 | 81.99 | |
Maximum of Months | 0.198682E+10 | 0.180602E+10 | 13334.12 | 12120.72 | 12120.72 | 10.65 | 81.99 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.773986E+10 | 0.703553E+10 | 4588.76 | 01-JAN-00:15 | 4171.18 | 4171.18 | 6.91 | 41.00 |
February | 0.713208E+10 | 0.648306E+10 | 4588.76 | 01-FEB-05:13 | 4171.18 | 4171.18 | 7.49 | 41.00 |
March | 0.947854E+10 | 0.861599E+10 | 4588.76 | 01-MAR-05:12 | 4171.18 | 4171.18 | 9.52 | 41.00 |
April | 0.105988E+11 | 0.963429E+10 | 4588.76 | 01-APR-00:05 | 4171.18 | 4171.18 | 6.88 | 41.00 |
May | 0.102438E+11 | 0.931158E+10 | 4588.76 | 01-MAY-00:05 | 4171.18 | 4171.18 | 6.95 | 41.00 |
June | 0.108880E+11 | 0.989716E+10 | 4588.76 | 01-JUN-00:25 | 4171.18 | 4171.18 | 7.01 | 41.00 |
July | 0.115435E+11 | 0.104931E+11 | 4588.76 | 01-JUL-00:10 | 4171.18 | 4171.18 | 6.99 | 41.00 |
August | 0.115775E+11 | 0.105240E+11 | 4588.76 | 01-AUG-00:05 | 4171.18 | 4171.18 | 10.24 | 41.00 |
September | 0.102869E+11 | 0.935079E+10 | 4588.76 | 01-SEP-00:05 | 4171.18 | 4171.18 | 8.13 | 41.00 |
October | 0.104790E+11 | 0.952540E+10 | 4588.76 | 01-OCT-00:05 | 4171.18 | 4171.18 | 9.06 | 41.00 |
November | 0.933560E+10 | 0.848606E+10 | 4588.76 | 01-NOV-04:12 | 4171.18 | 4171.18 | 13.80 | 41.00 |
December | 0.936662E+10 | 0.851426E+10 | 4588.76 | 01-DEC-00:05 | 4171.18 | 4171.18 | 6.99 | 41.00 |
Annual Sum or Average | 0.118670E+12 | 0.107871E+12 | ||||||
Minimum of Months | 0.713208E+10 | 0.648306E+10 | 4588.76 | 4171.18 | 4171.18 | 6.88 | 41.00 | |
Maximum of Months | 0.115775E+11 | 0.105240E+11 | 4588.76 | 4171.18 | 4171.18 | 13.80 | 41.00 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.361778E+09 | 0.328856E+09 | 4588.76 | 02-JAN-08:50 | 4171.18 | 4171.18 | 15.27 | 20.50 |
February | 0.400782E+09 | 0.364311E+09 | 4588.76 | 02-FEB-09:20 | 4171.18 | 4171.18 | 15.01 | 20.50 |
March | 0.102182E+10 | 0.928839E+09 | 4588.76 | 03-MAR-13:05 | 4171.18 | 4171.18 | 11.29 | 41.00 |
April | 0.128040E+10 | 0.116388E+10 | 4588.76 | 03-APR-10:40 | 4171.18 | 4171.18 | 15.16 | 20.50 |
May | 0.255020E+10 | 0.231813E+10 | 4588.76 | 01-MAY-07:50 | 4171.18 | 4171.18 | 15.42 | 20.50 |
June | 0.301080E+10 | 0.273682E+10 | 4588.76 | 01-JUN-05:04 | 4171.18 | 4171.18 | 15.25 | 20.50 |
July | 0.301445E+10 | 0.274013E+10 | 4588.76 | 03-JUL-05:02 | 4171.18 | 4171.18 | 12.99 | 41.00 |
August | 0.324562E+10 | 0.295026E+10 | 4588.76 | 01-AUG-05:07 | 4171.18 | 4171.18 | 15.37 | 20.50 |
September | 0.283016E+10 | 0.257262E+10 | 4588.76 | 01-SEP-07:30 | 4171.18 | 4171.18 | 15.29 | 20.50 |
October | 0.246697E+10 | 0.224247E+10 | 4588.76 | 02-OCT-03:04 | 4171.18 | 4171.18 | 15.79 | 20.50 |
November | 0.165737E+10 | 0.150655E+10 | 4588.76 | 01-NOV-09:40 | 4171.18 | 4171.18 | 15.56 | 20.50 |
December | 0.497972E+09 | 0.452657E+09 | 4588.76 | 01-DEC-13:20 | 4171.18 | 4171.18 | 15.29 | 20.50 |
Annual Sum or Average | 0.223383E+11 | 0.203055E+11 | ||||||
Minimum of Months | 0.361778E+09 | 0.328856E+09 | 4588.76 | 4171.18 | 4171.18 | 11.29 | 20.50 | |
Maximum of Months | 0.324562E+10 | 0.295026E+10 | 4588.76 | 4171.18 | 4171.18 | 15.79 | 41.00 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.899203E+10 | 0.817375E+10 | 3357.24 | 01-JAN-00:05 | 3051.73 | 3051.73 | 26.31 | 14.16 |
February | 0.812183E+10 | 0.738274E+10 | 3357.24 | 01-FEB-00:10 | 3051.73 | 3051.73 | 24.88 | 14.16 |
March | 0.899203E+10 | 0.817375E+10 | 3357.24 | 01-MAR-00:10 | 3051.73 | 3051.73 | 29.89 | 14.16 |
April | 0.870196E+10 | 0.791008E+10 | 3357.24 | 01-APR-00:05 | 3051.73 | 3051.73 | 40.60 | 14.16 |
May | 0.899203E+10 | 0.817375E+10 | 3357.24 | 01-MAY-00:05 | 3051.73 | 3051.73 | 28.35 | 14.16 |
June | 0.870196E+10 | 0.791008E+10 | 3357.24 | 01-JUN-00:05 | 3051.73 | 3051.73 | 37.21 | 14.16 |
July | 0.899203E+10 | 0.817375E+10 | 3357.24 | 01-JUL-00:10 | 3051.73 | 3051.73 | 41.54 | 14.16 |
August | 0.899203E+10 | 0.817375E+10 | 3357.24 | 01-AUG-00:05 | 3051.73 | 3051.73 | 47.62 | 14.16 |
September | 0.870196E+10 | 0.791008E+10 | 3357.24 | 01-SEP-00:05 | 3051.73 | 3051.73 | 34.11 | 14.16 |
October | 0.899203E+10 | 0.817375E+10 | 3357.24 | 01-OCT-00:05 | 3051.73 | 3051.73 | 38.44 | 14.16 |
November | 0.870196E+10 | 0.791008E+10 | 3357.24 | 01-NOV-00:10 | 3051.73 | 3051.73 | 36.57 | 14.16 |
December | 0.899203E+10 | 0.817375E+10 | 3357.24 | 01-DEC-00:05 | 3051.73 | 3051.73 | 41.36 | 14.16 |
Annual Sum or Average | 0.105874E+12 | 0.962393E+11 | ||||||
Minimum of Months | 0.812183E+10 | 0.738274E+10 | 3357.24 | 3051.73 | 3051.73 | 24.88 | 14.16 | |
Maximum of Months | 0.899203E+10 | 0.817375E+10 | 3357.24 | 3051.73 | 3051.73 | 47.62 | 14.16 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.42 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.89 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 56.87 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 57.13 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.92 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 57.05 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 56.78 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 56.66 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 56.56 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:05 | 16.86 | 16.86 | 56.35 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 56.38 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.14 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.35 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.14 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.308555E+11 | 0.280477E+11 | 35285.66 | 02-JAN-14:00 | 32074.66 | 32074.66 | 29.12 | 143.56 |
February | 0.285737E+11 | 0.259735E+11 | 35263.57 | 11-FEB-06:04 | 32054.58 | 32054.58 | 28.06 | 143.56 |
March | 0.396108E+11 | 0.360062E+11 | 35285.66 | 10-MAR-06:04 | 32074.66 | 32074.66 | 29.09 | 143.56 |
April | 0.446665E+11 | 0.406018E+11 | 35285.66 | 13-APR-12:05 | 32074.66 | 32074.66 | 29.64 | 143.56 |
May | 0.476030E+11 | 0.432712E+11 | 35285.66 | 10-MAY-09:40 | 32074.66 | 32074.66 | 28.91 | 143.56 |
June | 0.525392E+11 | 0.477581E+11 | 35285.66 | 01-JUN-12:05 | 32074.66 | 32074.66 | 29.50 | 143.56 |
July | 0.553091E+11 | 0.502760E+11 | 35285.66 | 03-JUL-05:04 | 32074.66 | 32074.66 | 29.77 | 143.56 |
August | 0.561668E+11 | 0.510556E+11 | 35285.66 | 01-AUG-05:07 | 32074.66 | 32074.66 | 29.53 | 143.56 |
September | 0.498340E+11 | 0.452991E+11 | 35285.66 | 01-SEP-08:70 | 32074.66 | 32074.66 | 28.81 | 143.56 |
October | 0.489224E+11 | 0.444705E+11 | 35285.66 | 02-OCT-03:06 | 32074.66 | 32074.66 | 29.61 | 143.56 |
November | 0.411118E+11 | 0.373706E+11 | 35285.66 | 02-NOV-14:05 | 32074.66 | 32074.66 | 29.05 | 143.56 |
December | 0.374703E+11 | 0.340605E+11 | 35285.66 | 08-DEC-14:05 | 32074.66 | 32074.66 | 28.87 | 143.56 |
Annual Sum or Average | 0.532663E+12 | 0.484191E+12 | ||||||
Minimum of Months | 0.285737E+11 | 0.259735E+11 | 35263.57 | 32054.58 | 32054.58 | 28.06 | 143.56 | |
Maximum of Months | 0.561668E+11 | 0.510556E+11 | 35285.66 | 32074.66 | 32074.66 | 29.77 | 143.56 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 82.00 | 82.00 | 151.88 | 156849.10 | 25-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.87 | 26.87 | 565.66 | 734069.89 | 04-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24.48 | 24.48 | 161.87 | 358364.59 | 16-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:05 | 26.77 | 26.77 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.77 | 26.77 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26.77 | 26.77 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.77 | 26.77 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 26.77 | 26.77 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.77 | 26.77 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.77 | 26.77 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26.77 | 26.77 | 31.53 | 90124.36 | 13-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 27.65 | 27.65 | 299.12 | 375846.89 | 15-DEC-06:02 |
Annual Sum or Average | 0.00 | 98.04 | ||||||
Minimum of Months | 0.00 | 0.00 | 24.48 | 24.48 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 82.00 | 82.00 | 565.66 | 734069.89 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 347357.59 | 2038172.78 | 14-JAN-06:06 | 12.64 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 433687.69 | 2827101.71 | 11-FEB-06:04 | 14.94 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 492197.75 | 2869427.09 | 10-MAR-06:04 | 15.06 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 595204.04 | 2158088.50 | 12-APR-05:02 | 12.99 | 6.70 | 0.00 | 0.00 | 01-APR-00:05 |
May | 750194.00 | 3407357.99 | 27-MAY-05:04 | 16.63 | 8.14 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 850337.24 | 2719573.08 | 22-JUN-05:02 | 14.62 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 848940.87 | 2637721.28 | 24-JUL-05:03 | 14.39 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 867210.44 | 3136372.92 | 28-AUG-05:03 | 15.84 | 7.35 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 828893.82 | 2970639.61 | 26-SEP-05:02 | 15.36 | 6.87 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 734338.79 | 2803541.49 | 03-OCT-05:02 | 14.87 | 6.70 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 599159.70 | 2994101.80 | 22-NOV-06:04 | 15.43 | 6.94 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 397735.92 | 2972302.60 | 11-DEC-06:03 | 15.36 | 6.87 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 646379.00 | 0.00 | ||||||
Minimum of Months | 347357.59 | 2038172.78 | 12.64 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 867210.44 | 3407357.99 | 16.63 | 8.14 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 351727.84 | 3936228.73 | 14-JAN-06:02 | 18.18 | 12.42 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 435938.48 | 3945083.81 | 11-FEB-05:01 | 18.20 | 12.43 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 494235.09 | 3955041.51 | 06-MAR-05:12 | 18.74 | 12.44 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 594585.96 | 3902780.81 | 13-APR-05:02 | 18.08 | 12.37 | 0.00 | 0.00 | 01-APR-00:05 |
May | 749196.80 | 3939426.56 | 25-MAY-04:12 | 18.19 | 12.43 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 849409.20 | 4010447.10 | 06-JUN-04:11 | 18.39 | 12.53 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 848098.16 | 4037536.41 | 03-JUL-03:02 | 19.02 | 12.55 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 866459.59 | 4122653.01 | 28-AUG-03:02 | 18.75 | 12.69 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 829491.99 | 4033355.92 | 13-SEP-03:02 | 18.46 | 12.56 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 746511.76 | 4118736.14 | 02-OCT-03:02 | 19.47 | 12.66 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 617170.68 | 4003286.65 | 04-NOV-05:03 | 18.38 | 12.52 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 402041.84 | 4021331.11 | 26-DEC-05:12 | 18.43 | 12.54 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 649677.85 | 0.00 | ||||||
Minimum of Months | 351727.84 | 3902780.81 | 18.08 | 12.37 | 0.00 | 0.00 | ||
Maximum of Months | 866459.59 | 4122653.01 | 19.47 | 12.69 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 363079.26 | 860511.54 | 02-JAN-15:00 | 35.59 | 30.94 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 632360.70 | 1085557.39 | 11-FEB-14:00 | 40.01 | 32.65 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 873196.10 | 1324336.38 | 13-MAR-16:00 | 44.67 | 34.10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1218749.54 | 1668501.59 | 17-APR-15:00 | 51.30 | 38.12 | 0.00 | 0.00 | 01-APR-00:05 |
May | 713197.44 | 1144974.53 | 22-MAY-13:00 | 41.18 | 36.48 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1004866.51 | 1243350.38 | 11-JUN-13:00 | 43.09 | 35.55 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1250885.73 | 1665134.47 | 29-JUL-16:00 | 51.24 | 40.45 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1450151.54 | 1773051.90 | 23-AUG-13:00 | 53.31 | 39.93 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 777471.37 | 1043945.67 | 20-SEP-16:00 | 39.20 | 34.34 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 928424.68 | 1245984.32 | 09-OCT-11:00 | 43.14 | 35.56 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 987025.17 | 1354844.62 | 17-NOV-15:00 | 45.26 | 34.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1010147.05 | 1494450.88 | 10-DEC-14:59 | 47.96 | 34.79 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 935920.58 | 0.00 | ||||||
Minimum of Months | 363079.26 | 860511.54 | 35.59 | 30.94 | 0.00 | 0.00 | ||
Maximum of Months | 1450151.54 | 1773051.90 | 53.31 | 40.45 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.89 | 57.89 | 11593.90 | 37936.24 | 19-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.34 | 57.34 | 11558.74 | 37797.54 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.26 | 57.26 | 11853.91 | 37064.09 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:05 | 57.86 | 57.86 | 10746.54 | 35486.96 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 57.46 | 57.46 | 10580.80 | 33953.24 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 57.35 | 57.35 | 10424.16 | 32403.81 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.27 | 57.27 | 9561.35 | 31477.05 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.00 | 57.00 | 10437.88 | 32166.26 | 31-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 56.89 | 56.89 | 10198.03 | 33530.13 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 56.79 | 56.79 | 10635.38 | 35279.45 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.76 | 56.76 | 11231.24 | 36791.35 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 57.54 | 57.54 | 11212.89 | 37679.12 | 28-DEC-12:30 |
Annual Sum or Average | 0.00 | 10832.34 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.76 | 56.76 | 9561.35 | 31477.05 | ||
Maximum of Months | 0.00 | 0.00 | 57.89 | 57.89 | 11853.91 | 37936.24 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 529176.81 | 4869711.10 | 02-JAN-14:10 | 29.22 | 26.19 | 542.34 | 127805.95 | 26-JAN-06:30 |
February | 665385.50 | 4177555.60 | 11-FEB-06:04 | 28.06 | 24.51 | 1025.53 | 155737.97 | 04-FEB-07:50 |
March | 826334.85 | 5342572.37 | 14-MAR-10:05 | 30.00 | 26.05 | 565.78 | 151094.25 | 16-MAR-05:50 |
April | 1056609.15 | 5123559.84 | 13-APR-12:05 | 29.64 | 26.01 | 387.02 | 83171.91 | 02-APR-01:30 |
May | 1787746.25 | 6306660.65 | 31-MAY-05:04 | 31.61 | 26.89 | 2.52 | 11266.31 | 08-MAY-04:10 |
June | 2515354.10 | 6588940.56 | 28-JUN-12:05 | 32.08 | 27.91 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 2633385.11 | 6448873.36 | 20-JUL-12:05 | 31.85 | 27.65 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 2691316.26 | 6433134.66 | 28-AUG-05:03 | 31.82 | 27.25 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2417269.75 | 5900378.65 | 20-SEP-05:04 | 30.93 | 26.36 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1878598.17 | 6691683.34 | 02-OCT-05:04 | 32.25 | 27.69 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1301148.36 | 5711239.10 | 30-NOV-13:05 | 30.62 | 26.80 | 386.13 | 108777.99 | 13-NOV-05:50 |
December | 691770.27 | 4663240.78 | 08-DEC-14:05 | 28.87 | 25.07 | 713.39 | 140596.30 | 15-DEC-07:00 |
Annual Sum or Average | 1587754.50 | 297.14 | ||||||
Minimum of Months | 529176.81 | 4177555.60 | 28.06 | 24.51 | 0.00 | 0.00 | ||
Maximum of Months | 2691316.26 | 6691683.34 | 32.25 | 27.91 | 1025.53 | 155737.97 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 1855813.59 | 0.00 | 0.847869E+11 | 0.603393E+10 | 0.00 | 0.00 |
February | 5871935.99 | 0.00 | 0.957804E+11 | 0.678248E+10 | 0.00 | 0.00 |
March | 6005867.65 | 0.00 | 0.130628E+12 | 0.963278E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.152436E+12 | 0.114755E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.166468E+12 | 0.111390E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.188139E+12 | 0.124762E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.201836E+12 | 0.139263E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.217001E+12 | 0.152444E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.176705E+12 | 0.101193E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.174182E+12 | 0.960757E+10 | 0.00 | 0.00 |
November | 46828.36 | 0.00 | 0.147239E+12 | 0.876953E+10 | 0.00 | 0.00 |
December | 5089055.07 | 0.00 | 0.117284E+12 | 0.788265E+10 | 0.00 | 0.00 |
Annual Sum or Average | 18869500.66 | 0.00 | 0.185248E+13 | 0.123090E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.847869E+11 | 0.603393E+10 | 0.00 | 0.00 |
Maximum of Months | 6005867.65 | 0.00 | 0.217001E+12 | 0.152444E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.278024E+09 | 0.00 | 0.667192E+12 | 0.426967E+11 | 0.00 | 0.00 |
February | 0.104858E+10 | 0.00 | 0.735324E+12 | 0.448102E+11 | 0.00 | 0.00 |
March | 0.249530E+09 | 0.00 | 0.932331E+12 | 0.625878E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.109508E+13 | 0.740257E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.145168E+13 | 0.949182E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.160116E+13 | 0.100310E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.165077E+13 | 0.102053E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.166530E+13 | 0.986283E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.156607E+13 | 0.827597E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.142035E+13 | 0.725706E+11 | 0.00 | 0.00 |
November | 13753643.67 | 0.00 | 0.110321E+13 | 0.572939E+11 | 0.00 | 0.00 |
December | 0.448251E+09 | 0.00 | 0.739035E+12 | 0.440596E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.203814E+10 | 0.00 | 0.146275E+14 | 0.876714E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.667192E+12 | 0.426967E+11 | 0.00 | 0.00 |
Maximum of Months | 0.104858E+10 | 0.00 | 0.166530E+13 | 0.102053E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.295270E+09 | 0.00 | 0.619223E+11 | 0.375109E+10 | 0.00 | 0.00 |
February | 0.333578E+09 | 0.00 | 0.737786E+11 | 0.429941E+10 | 0.00 | 0.00 |
March | 0.175151E+09 | 0.00 | 0.966864E+11 | 0.620603E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.117905E+12 | 0.782688E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.159630E+12 | 0.103348E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.176110E+12 | 0.109669E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.183225E+12 | 0.114594E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.181191E+12 | 0.108827E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.169133E+12 | 0.906454E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.147821E+12 | 0.744764E+10 | 0.00 | 0.00 |
November | 66036118.05 | 0.00 | 0.111377E+12 | 0.560484E+10 | 0.00 | 0.00 |
December | 0.362134E+09 | 0.00 | 0.712302E+11 | 0.407988E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123217E+10 | 0.00 | 0.155001E+13 | 0.919241E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.619223E+11 | 0.375109E+10 | 0.00 | 0.00 |
Maximum of Months | 0.362134E+09 | 0.00 | 0.183225E+12 | 0.114594E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.712654E+11 | 0.142891E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.686124E+11 | 0.126762E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.794363E+11 | 0.140689E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.821524E+11 | 0.131557E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.104497E+12 | 0.144525E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.118588E+12 | 0.143129E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.125039E+12 | 0.143613E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.138036E+12 | 0.154769E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.119528E+12 | 0.144632E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.113557E+12 | 0.147600E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.974660E+11 | 0.142317E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.761846E+11 | 0.141945E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119436E+13 | 0.170443E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.686124E+11 | 0.126762E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.138036E+12 | 0.154769E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.423608E+12 | 0.180269E+12 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.665017E+12 | 0.222368E+12 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.104971E+13 | 0.312117E+12 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.133218E+13 | 0.380073E+12 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.465514E+12 | 0.201915E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.770947E+12 | 0.272357E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.112094E+13 | 0.359299E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.141765E+13 | 0.421777E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.463718E+12 | 0.200665E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.786129E+12 | 0.274082E+12 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.104039E+13 | 0.315849E+12 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.134745E+13 | 0.364811E+12 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.108832E+14 | 0.350558E+13 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.00 | 0.423608E+12 | 0.180269E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.141765E+13 | 0.421777E+12 | 0.00 | 0.13 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.712349E+10 | 0.282127E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.125343E+11 | 0.381031E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.204899E+11 | 0.559143E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.267031E+11 | 0.708188E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.893629E+10 | 0.340593E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.154898E+11 | 0.490050E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.227987E+11 | 0.667267E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.293878E+11 | 0.816199E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.905399E+10 | 0.342289E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.155918E+11 | 0.488263E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.205489E+11 | 0.571585E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.265099E+11 | 0.666913E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.215168E+12 | 0.631365E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.712349E+10 | 0.282127E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.293878E+11 | 0.816199E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.606417E+11 | 0.255614E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.114275E+12 | 0.353878E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.193059E+12 | 0.529418E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.254358E+12 | 0.675089E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.842497E+11 | 0.322709E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.147846E+12 | 0.467542E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.217625E+12 | 0.636795E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.279105E+12 | 0.776452E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.850917E+11 | 0.323624E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.148222E+12 | 0.464651E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.194086E+12 | 0.541944E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.248314E+12 | 0.628776E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.202687E+13 | 0.597649E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.606417E+11 | 0.255614E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.279105E+12 | 0.776452E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.550267E+10 | 0.248240E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.111209E+11 | 0.351326E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.191565E+11 | 0.530549E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.255041E+11 | 0.680395E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.858067E+10 | 0.329162E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149614E+11 | 0.474578E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.219928E+11 | 0.645452E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.280952E+11 | 0.784761E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.866543E+10 | 0.330101E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.148933E+11 | 0.469505E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.192517E+11 | 0.542784E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.244736E+11 | 0.626790E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.202198E+12 | 0.601364E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.550267E+10 | 0.248240E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.280952E+11 | 0.784761E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.603393E+10 | 0.847869E+11 | 1855813.59 | 46406046.14 | 0.254899E+10 | 0.00 | 0.00 | 0.00 |
February | 0.678248E+10 | 0.957804E+11 | 5871935.99 | 0.585069E+09 | 0.338443E+10 | 0.00 | 0.00 | 0.00 |
March | 0.963278E+10 | 0.130628E+12 | 6005867.65 | 0.125485E+09 | 0.500099E+10 | 0.00 | 0.00 | 0.00 |
April | 0.114755E+11 | 0.152436E+12 | 0.00 | 45179424.16 | 0.967834E+10 | 0.00 | 0.00 | 0.00 |
May | 0.111390E+11 | 0.166468E+12 | 0.00 | 0.00 | 0.257215E+11 | 0.00 | 0.00 | 0.00 |
June | 0.124762E+11 | 0.188139E+12 | 0.00 | 0.00 | 0.455899E+11 | 0.00 | 0.00 | 0.00 |
July | 0.139263E+11 | 0.201836E+12 | 0.00 | 0.00 | 0.508042E+11 | 0.00 | 0.00 | 0.00 |
August | 0.152444E+11 | 0.217001E+12 | 0.00 | 0.00 | 0.535166E+11 | 0.00 | 0.00 | 0.00 |
September | 0.101193E+11 | 0.176705E+12 | 0.00 | 0.00 | 0.409881E+11 | 0.00 | 0.00 | 0.00 |
October | 0.960757E+10 | 0.174182E+12 | 0.00 | 720069.80 | 0.310871E+11 | 0.00 | 0.00 | 0.00 |
November | 0.876953E+10 | 0.147239E+12 | 46828.36 | 16022330.36 | 0.181252E+11 | 0.00 | 0.00 | 0.00 |
December | 0.788265E+10 | 0.117284E+12 | 5089055.07 | 30153635.47 | 0.508151E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123090E+12 | 0.185248E+13 | 18869500.66 | 0.849035E+09 | 0.291527E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.603393E+10 | 0.847869E+11 | 0.00 | 0.00 | 0.254899E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152444E+11 | 0.217001E+12 | 6005867.65 | 0.585069E+09 | 0.535166E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.426967E+11 | 0.667192E+12 | 0.278024E+09 | 0.829472E+09 | 0.278598E+11 | 0.00 | 0.00 | 0.00 |
February | 0.448102E+11 | 0.735324E+12 | 0.104858E+10 | 0.662273E+10 | 0.341278E+11 | 0.00 | 0.00 | 0.00 |
March | 0.625878E+11 | 0.932331E+12 | 0.249530E+09 | 0.158656E+10 | 0.502180E+11 | 0.00 | 0.00 | 0.00 |
April | 0.740257E+11 | 0.109508E+13 | 0.00 | 0.548868E+09 | 0.937110E+11 | 0.00 | 0.00 | 0.00 |
May | 0.949182E+11 | 0.145168E+13 | 0.00 | 0.00 | 0.252244E+12 | 0.00 | 0.00 | 0.00 |
June | 0.100310E+12 | 0.160116E+13 | 0.00 | 0.00 | 0.418780E+12 | 0.00 | 0.00 | 0.00 |
July | 0.102053E+12 | 0.165077E+13 | 0.00 | 0.00 | 0.483574E+12 | 0.00 | 0.00 | 0.00 |
August | 0.986283E+11 | 0.166530E+13 | 0.00 | 0.00 | 0.477837E+12 | 0.00 | 0.00 | 0.00 |
September | 0.827597E+11 | 0.156607E+13 | 0.00 | 0.00 | 0.396909E+12 | 0.00 | 0.00 | 0.00 |
October | 0.725706E+11 | 0.142035E+13 | 0.00 | 18288008.20 | 0.289581E+12 | 0.00 | 0.00 | 0.00 |
November | 0.572939E+11 | 0.110321E+13 | 13753643.67 | 0.343893E+09 | 0.166263E+12 | 0.00 | 0.00 | 0.00 |
December | 0.440596E+11 | 0.739035E+12 | 0.448251E+09 | 0.742331E+09 | 0.517981E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876714E+12 | 0.146275E+14 | 0.203814E+10 | 0.106921E+11 | 0.274290E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.426967E+11 | 0.667192E+12 | 0.00 | 0.00 | 0.278598E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102053E+12 | 0.166530E+13 | 0.104858E+10 | 0.662273E+10 | 0.483574E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.375109E+10 | 0.619223E+11 | 0.295270E+09 | 0.116734E+09 | 0.201292E+10 | 0.00 | 0.00 | 0.00 |
February | 0.429941E+10 | 0.737786E+11 | 0.333578E+09 | 0.640326E+09 | 0.257409E+10 | 0.00 | 0.00 | 0.00 |
March | 0.620603E+10 | 0.966864E+11 | 0.175151E+09 | 0.262590E+09 | 0.345291E+10 | 0.00 | 0.00 | 0.00 |
April | 0.782688E+10 | 0.117905E+12 | 0.00 | 15921670.00 | 0.780540E+10 | 0.00 | 0.00 | 0.00 |
May | 0.103348E+11 | 0.159630E+12 | 0.00 | 0.00 | 0.233534E+11 | 0.00 | 0.00 | 0.00 |
June | 0.109669E+11 | 0.176110E+12 | 0.00 | 0.00 | 0.401069E+11 | 0.00 | 0.00 | 0.00 |
July | 0.114594E+11 | 0.183225E+12 | 0.00 | 0.00 | 0.459600E+11 | 0.00 | 0.00 | 0.00 |
August | 0.108827E+11 | 0.181191E+12 | 0.00 | 0.00 | 0.458749E+11 | 0.00 | 0.00 | 0.00 |
September | 0.906454E+10 | 0.169133E+12 | 0.00 | 0.00 | 0.378900E+11 | 0.00 | 0.00 | 0.00 |
October | 0.744764E+10 | 0.147821E+12 | 0.00 | 3536827.07 | 0.276186E+11 | 0.00 | 0.00 | 0.00 |
November | 0.560484E+10 | 0.111377E+12 | 66036118.05 | 75851050.61 | 0.151912E+11 | 0.00 | 0.00 | 0.00 |
December | 0.407988E+10 | 0.712302E+11 | 0.362134E+09 | 0.229464E+09 | 0.383308E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919241E+11 | 0.155001E+13 | 0.123217E+10 | 0.134442E+10 | 0.255673E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.375109E+10 | 0.619223E+11 | 0.00 | 0.00 | 0.201292E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114594E+11 | 0.183225E+12 | 0.362134E+09 | 0.640326E+09 | 0.459600E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142891E+11 | 0.712654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126762E+11 | 0.686124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140689E+11 | 0.794363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131557E+11 | 0.821524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144525E+11 | 0.104497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143129E+11 | 0.118588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143613E+11 | 0.125039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154769E+11 | 0.138036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144632E+11 | 0.119528E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147600E+11 | 0.113557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142317E+11 | 0.974660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141945E+11 | 0.761846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170443E+12 | 0.119436E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126762E+11 | 0.686124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154769E+11 | 0.138036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.945177E+11 | 0.338192E+12 | 0.00 | 0.00 | 0.00 | 0.333312E+09 | 0.00 | 0.00 |
February | 0.853708E+11 | 0.528374E+12 | 0.00 | 0.00 | 0.00 | 0.352669E+09 | 0.00 | 0.00 |
March | 0.945177E+11 | 0.832403E+12 | 0.00 | 0.00 | 0.00 | 0.292943E+09 | 0.00 | 0.00 |
April | 0.914687E+11 | 0.104357E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.945177E+11 | 0.358117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.914687E+11 | 0.590059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.945177E+11 | 0.856157E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.945177E+11 | 0.109039E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.914687E+11 | 0.354522E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.945177E+11 | 0.606564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.914687E+11 | 0.816103E+12 | 0.00 | 0.00 | 0.00 | 89097377.36 | 0.00 | 0.00 |
December | 0.945177E+11 | 0.107723E+13 | 0.00 | 0.00 | 0.00 | 72216472.17 | 0.00 | 0.00 |
Annual Sum or Average | 0.111287E+13 | 0.849168E+13 | 0.00 | 0.00 | 0.00 | 0.114024E+10 | 0.00 | 0.00 |
Minimum of Months | 0.853708E+11 | 0.338192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.945177E+11 | 0.109039E+13 | 0.00 | 0.00 | 0.00 | 0.352669E+09 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138887E+10 | 0.569109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125446E+10 | 0.997846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138887E+10 | 0.162874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134407E+10 | 0.209653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138887E+10 | 0.691923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134407E+10 | 0.119334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138887E+10 | 0.175149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138887E+10 | 0.226147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134407E+10 | 0.697517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138887E+10 | 0.120980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134407E+10 | 0.161772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138887E+10 | 0.212296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163528E+11 | 0.168384E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125446E+10 | 0.569109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138887E+10 | 0.226147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132487E+11 | 0.483290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119666E+11 | 0.908540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132487E+11 | 0.153366E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128214E+11 | 0.199670E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132487E+11 | 0.652276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128214E+11 | 0.113913E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132487E+11 | 0.167194E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132487E+11 | 0.214709E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128214E+11 | 0.655506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132487E+11 | 0.115006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128214E+11 | 0.152713E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132487E+11 | 0.198685E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155993E+12 | 0.158522E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119666E+11 | 0.483290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132487E+11 | 0.214709E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135217E+10 | 0.437245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122132E+10 | 0.882899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135217E+10 | 0.152032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130855E+10 | 0.200087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135217E+10 | 0.664122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130855E+10 | 0.115242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135217E+10 | 0.168905E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135217E+10 | 0.215998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130855E+10 | 0.667298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135217E+10 | 0.115504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130855E+10 | 0.151325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135217E+10 | 0.195579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159207E+11 | 0.157983E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122132E+10 | 0.437245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135217E+10 | 0.215998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.603393E+10 | 1855813.59 | 0.847869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.678248E+10 | 5871935.99 | 0.957804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.963278E+10 | 6005867.65 | 0.130628E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114755E+11 | 0.00 | 0.152436E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111390E+11 | 0.00 | 0.166468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124762E+11 | 0.00 | 0.188139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139263E+11 | 0.00 | 0.201836E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152444E+11 | 0.00 | 0.217001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.101193E+11 | 0.00 | 0.176705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.960757E+10 | 0.00 | 0.174182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.876953E+10 | 46828.36 | 0.147239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.788265E+10 | 5089055.07 | 0.117284E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123090E+12 | 18869500.66 | 0.185248E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.603393E+10 | 0.00 | 0.847869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152444E+11 | 6005867.65 | 0.217001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.426967E+11 | 0.278024E+09 | 0.667192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.448102E+11 | 0.104858E+10 | 0.735324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.625878E+11 | 0.249530E+09 | 0.932331E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.740257E+11 | 0.00 | 0.109508E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.949182E+11 | 0.00 | 0.145168E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100310E+12 | 0.00 | 0.160116E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.102053E+12 | 0.00 | 0.165077E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.986283E+11 | 0.00 | 0.166530E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.827597E+11 | 0.00 | 0.156607E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.725706E+11 | 0.00 | 0.142035E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.572939E+11 | 13753643.67 | 0.110321E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440596E+11 | 0.448251E+09 | 0.739035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876714E+12 | 0.203814E+10 | 0.146275E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.426967E+11 | 0.00 | 0.667192E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.102053E+12 | 0.104858E+10 | 0.166530E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.375109E+10 | 0.295270E+09 | 0.619223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.429941E+10 | 0.333578E+09 | 0.737786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.620603E+10 | 0.175151E+09 | 0.966864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.782688E+10 | 0.00 | 0.117905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103348E+11 | 0.00 | 0.159630E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109669E+11 | 0.00 | 0.176110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.114594E+11 | 0.00 | 0.183225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108827E+11 | 0.00 | 0.181191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.906454E+10 | 0.00 | 0.169133E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.744764E+10 | 0.00 | 0.147821E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.560484E+10 | 66036118.05 | 0.111377E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.407988E+10 | 0.362134E+09 | 0.712302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.919241E+11 | 0.123217E+10 | 0.155001E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.375109E+10 | 0.00 | 0.619223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114594E+11 | 0.362134E+09 | 0.183225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142891E+11 | 0.00 | 0.712654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126762E+11 | 0.00 | 0.686124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140689E+11 | 0.00 | 0.794363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131557E+11 | 0.00 | 0.821524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144525E+11 | 0.00 | 0.104497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143129E+11 | 0.00 | 0.118588E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143613E+11 | 0.00 | 0.125039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154769E+11 | 0.00 | 0.138036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144632E+11 | 0.00 | 0.119528E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147600E+11 | 0.00 | 0.113557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142317E+11 | 0.00 | 0.974660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141945E+11 | 0.00 | 0.761846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170443E+12 | 0.00 | 0.119436E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126762E+11 | 0.00 | 0.686124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154769E+11 | 0.00 | 0.138036E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.945177E+11 | 0.00 | 0.423608E+12 | 0.00 | 0.854164E+11 | 0.00 | 0.00 | 0.00 | 0.334813E+09 | 0.00 | 0.00 | 0.00 |
February | 0.853708E+11 | 0.00 | 0.665017E+12 | 0.00 | 0.136643E+12 | 0.00 | 0.00 | 0.00 | 0.354257E+09 | 0.00 | 0.00 | 0.00 |
March | 0.945177E+11 | 0.00 | 0.104971E+13 | 0.00 | 0.217305E+12 | 0.00 | 0.00 | 0.00 | 0.294262E+09 | 0.00 | 0.00 | 0.00 |
April | 0.914687E+11 | 0.00 | 0.133218E+13 | 0.00 | 0.288604E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.945177E+11 | 0.00 | 0.465514E+12 | 0.00 | 0.107397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.914687E+11 | 0.00 | 0.770947E+12 | 0.00 | 0.180888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.945177E+11 | 0.00 | 0.112094E+13 | 0.00 | 0.264782E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.945177E+11 | 0.00 | 0.141765E+13 | 0.00 | 0.327260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.914687E+11 | 0.00 | 0.463718E+12 | 0.00 | 0.109196E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.945177E+11 | 0.00 | 0.786129E+12 | 0.00 | 0.179564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.914687E+11 | 0.00 | 0.104039E+13 | 0.00 | 0.224291E+12 | 0.00 | 0.00 | 0.00 | 89498440.77 | 0.00 | 0.00 | 0.00 |
December | 0.945177E+11 | 0.00 | 0.134745E+13 | 0.00 | 0.270221E+12 | 0.00 | 0.00 | 0.00 | 72541547.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111287E+13 | 0.00 | 0.108832E+14 | 0.00 | 0.239157E+13 | 0.00 | 0.00 | 0.00 | 0.114537E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.853708E+11 | 0.00 | 0.423608E+12 | 0.00 | 0.854164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.945177E+11 | 0.00 | 0.141765E+13 | 0.00 | 0.327260E+12 | 0.00 | 0.00 | 0.00 | 0.354257E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138887E+10 | 0.00 | 0.712349E+10 | 0.00 | 0.143240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125446E+10 | 0.00 | 0.125343E+11 | 0.00 | 0.255585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138887E+10 | 0.00 | 0.204899E+11 | 0.00 | 0.420256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134407E+10 | 0.00 | 0.267031E+11 | 0.00 | 0.573781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138887E+10 | 0.00 | 0.893629E+10 | 0.00 | 0.201706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134407E+10 | 0.00 | 0.154898E+11 | 0.00 | 0.355643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138887E+10 | 0.00 | 0.227987E+11 | 0.00 | 0.528380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138887E+10 | 0.00 | 0.293878E+11 | 0.00 | 0.677312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134407E+10 | 0.00 | 0.905399E+10 | 0.00 | 0.207882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138887E+10 | 0.00 | 0.155918E+11 | 0.00 | 0.349376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134407E+10 | 0.00 | 0.205489E+11 | 0.00 | 0.437179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138887E+10 | 0.00 | 0.265099E+11 | 0.00 | 0.528026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163528E+11 | 0.00 | 0.215168E+12 | 0.00 | 0.467837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125446E+10 | 0.00 | 0.712349E+10 | 0.00 | 0.143240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138887E+10 | 0.00 | 0.293878E+11 | 0.00 | 0.677312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132487E+11 | 0.00 | 0.606417E+11 | 0.00 | 0.123127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119666E+11 | 0.00 | 0.114275E+12 | 0.00 | 0.234212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132487E+11 | 0.00 | 0.193059E+12 | 0.00 | 0.396931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128214E+11 | 0.00 | 0.254358E+12 | 0.00 | 0.546876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132487E+11 | 0.00 | 0.842497E+11 | 0.00 | 0.190221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128214E+11 | 0.00 | 0.147846E+12 | 0.00 | 0.339329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132487E+11 | 0.00 | 0.217625E+12 | 0.00 | 0.504308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132487E+11 | 0.00 | 0.279105E+12 | 0.00 | 0.643965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128214E+11 | 0.00 | 0.850917E+11 | 0.00 | 0.195411E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132487E+11 | 0.00 | 0.148222E+12 | 0.00 | 0.332163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128214E+11 | 0.00 | 0.194086E+12 | 0.00 | 0.413730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132487E+11 | 0.00 | 0.248314E+12 | 0.00 | 0.496289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155993E+12 | 0.00 | 0.202687E+13 | 0.00 | 0.441656E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119666E+11 | 0.00 | 0.606417E+11 | 0.00 | 0.123127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132487E+11 | 0.00 | 0.279105E+12 | 0.00 | 0.643965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135217E+10 | 0.00 | 0.550267E+10 | 0.00 | 0.113022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122132E+10 | 0.00 | 0.111209E+11 | 0.00 | 0.229194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135217E+10 | 0.00 | 0.191565E+11 | 0.00 | 0.395332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130855E+10 | 0.00 | 0.255041E+11 | 0.00 | 0.549540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135217E+10 | 0.00 | 0.858067E+10 | 0.00 | 0.193945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130855E+10 | 0.00 | 0.149614E+11 | 0.00 | 0.343722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135217E+10 | 0.00 | 0.219928E+11 | 0.00 | 0.510235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135217E+10 | 0.00 | 0.280952E+11 | 0.00 | 0.649544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130855E+10 | 0.00 | 0.866543E+10 | 0.00 | 0.199245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135217E+10 | 0.00 | 0.148933E+11 | 0.00 | 0.334288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130855E+10 | 0.00 | 0.192517E+11 | 0.00 | 0.411929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135217E+10 | 0.00 | 0.244736E+11 | 0.00 | 0.491573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159207E+11 | 0.00 | 0.202198E+12 | 0.00 | 0.442157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122132E+10 | 0.00 | 0.550267E+10 | 0.00 | 0.113022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135217E+10 | 0.00 | 0.280952E+11 | 0.00 | 0.649544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.959164E+09 | 0.417510E+10 | 0.00 | 93206445.92 | 20722470.36 | 0.00 | 0.125985E+11 | 0.00 | 0.40 |
February | 0.659956E+09 | 0.443082E+10 | 0.00 | 74979646.74 | 80570328.92 | 0.00 | 0.672662E+10 | 0.00 | 0.39 |
March | 0.159643E+09 | 0.694514E+10 | 0.00 | 70001924.09 | 71318116.16 | 0.00 | 0.790983E+10 | 0.00 | 0.39 |
April | 0.158574E+09 | 0.100003E+11 | 0.00 | 38626421.67 | 0.161021E+09 | 0.00 | 0.213042E+10 | 0.00 | 0.38 |
May | 70460183.59 | 0.253942E+11 | 0.00 | 4944565.63 | 0.372971E+09 | 0.00 | 0.199124E+09 | 0.00 | 0.40 |
June | 0.00 | 0.394238E+11 | 0.00 | 177845.55 | 0.612892E+09 | 0.00 | 170808.35 | 0.00 | 0.41 |
July | 2114905.69 | 0.438337E+11 | 0.00 | 408146.78 | 0.834050E+09 | 0.00 | 9175298.08 | 0.00 | 0.40 |
August | 0.00 | 0.477108E+11 | 0.00 | 192900.25 | 0.748754E+09 | 0.00 | 826281.75 | 0.00 | 0.43 |
September | 388690.14 | 0.391831E+11 | 0.00 | 1725959.77 | 0.815623E+09 | 0.00 | 8693150.59 | 0.00 | 0.42 |
October | 29383741.14 | 0.297205E+11 | 0.00 | 7727223.92 | 0.567262E+09 | 0.00 | 0.130051E+09 | 0.00 | 0.41 |
November | 0.100874E+10 | 0.189017E+11 | 0.00 | 42184790.06 | 0.259830E+09 | 0.00 | 0.310485E+10 | 0.00 | 0.41 |
December | 0.492671E+09 | 0.600273E+10 | 0.00 | 90667544.91 | 0.146351E+09 | 0.00 | 0.104993E+11 | 0.00 | 0.39 |
Annual Sum or Average | 0.354110E+10 | 0.275722E+12 | 0.00 | 0.424843E+09 | 0.469137E+10 | 0.00 | 0.433176E+11 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.417510E+10 | 0.00 | 177845.55 | 20722470.36 | 0.00 | 170808.35 | 0.00 | 0.38 |
Maximum of Months | 0.100874E+10 | 0.477108E+11 | 0.00 | 93206445.92 | 0.834050E+09 | 0.00 | 0.125985E+11 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103319E+10 | 0.316400E+10 | 0.00 | 58803549.83 | 0.541859E+09 | 0.00 | 0.117335E+11 | 0.00 | 0.37 |
February | 0.745632E+09 | 0.341512E+10 | 0.00 | 47617485.63 | 0.426491E+09 | 0.00 | 0.606918E+10 | 0.00 | 0.36 |
March | 0.555591E+09 | 0.495293E+10 | 0.00 | 49101969.02 | 0.329650E+10 | 0.00 | 0.803143E+10 | 0.00 | 0.43 |
April | 0.110501E+10 | 0.550079E+10 | 0.00 | 19268867.64 | 0.383753E+10 | 0.00 | 0.147671E+10 | 0.00 | 0.46 |
May | 21590786.56 | 0.104970E+11 | 0.00 | 464511.03 | 0.642675E+10 | 0.00 | 372239.30 | 0.00 | 0.41 |
June | 0.00 | 0.137198E+11 | 0.00 | 0.00 | 0.922156E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.139377E+11 | 0.00 | 0.00 | 0.113050E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.158625E+11 | 0.00 | 0.00 | 0.102918E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.147079E+11 | 0.00 | 0.00 | 0.800605E+10 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 14580546.97 | 0.117026E+11 | 0.00 | 1941817.30 | 0.826471E+10 | 0.00 | 13161539.44 | 0.00 | 0.43 |
November | 0.892527E+09 | 0.860881E+10 | 0.00 | 18756986.71 | 0.506864E+10 | 0.00 | 0.168530E+10 | 0.00 | 0.41 |
December | 0.736436E+09 | 0.399008E+10 | 0.00 | 61212267.75 | 0.464655E+10 | 0.00 | 0.107655E+11 | 0.00 | 0.45 |
Annual Sum or Average | 0.510455E+10 | 0.110059E+12 | 0.00 | 0.257167E+09 | 0.713335E+11 | 0.00 | 0.397751E+11 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.316400E+10 | 0.00 | 0.00 | 0.426491E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.110501E+10 | 0.158625E+11 | 0.00 | 61212267.75 | 0.113050E+11 | 0.00 | 0.117335E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.948861E+10 | 0.295249E+11 | 0.00 | 0.409589E+09 | 0.478310E+10 | 0.00 | 0.100784E+12 | 0.00 | 0.35 |
February | 0.864744E+10 | 0.308198E+11 | 0.00 | 0.307862E+09 | 0.314408E+10 | 0.00 | 0.486930E+11 | 0.00 | 0.34 |
March | 0.216495E+10 | 0.448846E+11 | 0.00 | 0.362485E+09 | 0.727726E+10 | 0.00 | 0.719378E+11 | 0.00 | 0.35 |
April | 0.194989E+10 | 0.496604E+11 | 0.00 | 0.161096E+09 | 0.140419E+11 | 0.00 | 0.153412E+11 | 0.00 | 0.35 |
May | 13413695.26 | 0.100138E+12 | 0.00 | 6923731.70 | 0.323981E+11 | 0.00 | 17210643.48 | 0.00 | 0.36 |
June | 0.00 | 0.131537E+12 | 0.00 | 0.00 | 0.497392E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.128180E+12 | 0.00 | 0.00 | 0.680719E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.145926E+12 | 0.00 | 0.00 | 0.518565E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.141815E+12 | 0.00 | 0.00 | 0.500192E+11 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.160462E+09 | 0.113026E+12 | 0.00 | 22574938.15 | 0.329952E+11 | 0.00 | 0.243518E+09 | 0.00 | 0.35 |
November | 0.550030E+10 | 0.829461E+11 | 0.00 | 0.135472E+09 | 0.112419E+11 | 0.00 | 0.147231E+11 | 0.00 | 0.33 |
December | 0.499399E+10 | 0.350325E+11 | 0.00 | 0.378808E+09 | 0.125108E+11 | 0.00 | 0.933308E+11 | 0.00 | 0.35 |
Annual Sum or Average | 0.329191E+11 | 0.103349E+13 | 0.00 | 0.178481E+10 | 0.338079E+12 | 0.00 | 0.345071E+12 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.295249E+11 | 0.00 | 0.00 | 0.314408E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.948861E+10 | 0.145926E+12 | 0.00 | 0.409589E+09 | 0.680719E+11 | 0.00 | 0.100784E+12 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.327717E+10 | 0.279857E+10 | 0.00 | 24749941.58 | 0.517513E+09 | 0.00 | 0.632203E+10 | 0.00 | 0.33 |
February | 0.141703E+10 | 0.292532E+10 | 0.00 | 23140727.31 | 0.318895E+09 | 0.00 | 0.344505E+10 | 0.00 | 0.32 |
March | 0.144990E+10 | 0.450543E+10 | 0.00 | 25965224.95 | 0.860450E+09 | 0.00 | 0.504445E+10 | 0.00 | 0.34 |
April | 0.254570E+09 | 0.483503E+10 | 0.00 | 14763024.72 | 0.131519E+10 | 0.00 | 0.141729E+10 | 0.00 | 0.34 |
May | 996858.60 | 0.963506E+10 | 0.00 | 436030.08 | 0.328211E+10 | 0.00 | 1233210.36 | 0.00 | 0.36 |
June | 0.00 | 0.129460E+11 | 0.00 | 0.00 | 0.492619E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.126912E+11 | 0.00 | 0.00 | 0.666004E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.142137E+11 | 0.00 | 0.00 | 0.518246E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.136189E+11 | 0.00 | 0.00 | 0.501162E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 10830522.62 | 0.104051E+11 | 0.00 | 2100547.87 | 0.333889E+10 | 0.00 | 21636051.00 | 0.00 | 0.34 |
November | 0.772777E+09 | 0.768745E+10 | 0.00 | 7911026.95 | 0.150503E+10 | 0.00 | 0.892260E+09 | 0.00 | 0.32 |
December | 0.217773E+10 | 0.334818E+10 | 0.00 | 23824753.35 | 0.134634E+10 | 0.00 | 0.622731E+10 | 0.00 | 0.33 |
Annual Sum or Average | 0.936100E+10 | 0.996099E+11 | 0.00 | 0.122891E+09 | 0.342647E+11 | 0.00 | 0.233713E+11 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.279857E+10 | 0.00 | 0.00 | 0.318895E+09 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.327717E+10 | 0.142137E+11 | 0.00 | 25965224.95 | 0.666004E+10 | 0.00 | 0.632203E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.622143E+09 | 0.400736E+09 | 0.00 | 2754549.10 | 70868108.28 | 0.00 | 0.465014E+09 | 0.00 | 0.30 |
February | 0.304401E+09 | 0.489480E+09 | 0.00 | 3196757.32 | 56448304.06 | 0.00 | 0.315731E+09 | 0.00 | 0.34 |
March | 0.310449E+09 | 0.747123E+09 | 0.00 | 3205450.92 | 0.414536E+09 | 0.00 | 0.400185E+09 | 0.00 | 0.42 |
April | 0.148352E+09 | 0.892337E+09 | 0.00 | 2187846.93 | 0.479380E+09 | 0.00 | 0.165368E+09 | 0.00 | 0.53 |
May | 2689036.95 | 0.210006E+10 | 0.00 | 44882.27 | 0.736966E+09 | 0.00 | 45388.60 | 0.00 | 0.56 |
June | 0.00 | 0.307973E+10 | 0.00 | 0.00 | 0.100345E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.326454E+10 | 0.00 | 0.00 | 0.117484E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
August | 0.00 | 0.316895E+10 | 0.00 | 0.00 | 0.114539E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.286106E+10 | 0.00 | 0.00 | 0.912986E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
October | 1967575.30 | 0.191759E+10 | 0.00 | 244361.28 | 0.100619E+10 | 0.00 | 1547758.06 | 0.00 | 0.51 |
November | 0.157774E+09 | 0.129414E+10 | 0.00 | 1365616.11 | 0.638161E+09 | 0.00 | 91155643.21 | 0.00 | 0.44 |
December | 0.385210E+09 | 0.551647E+09 | 0.00 | 3444307.72 | 0.583905E+09 | 0.00 | 0.553107E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.193298E+10 | 0.207674E+11 | 0.00 | 16443771.64 | 0.822313E+10 | 0.00 | 0.199215E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.400736E+09 | 0.00 | 0.00 | 56448304.06 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.622143E+09 | 0.326454E+10 | 0.00 | 3444307.72 | 0.117484E+10 | 0.00 | 0.553107E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301776E+09 | 0.347748E+09 | 0.00 | 3854208.18 | 28786012.89 | 0.00 | 0.679752E+09 | 0.00 | 0.40 |
February | 0.147142E+09 | 0.368913E+09 | 0.00 | 3971974.37 | 37594286.35 | 0.00 | 0.419047E+09 | 0.00 | 0.44 |
March | 0.139022E+09 | 0.601948E+09 | 0.00 | 4236780.05 | 0.260245E+09 | 0.00 | 0.678047E+09 | 0.00 | 0.56 |
April | 95505803.48 | 0.767840E+09 | 0.00 | 2169238.47 | 0.292506E+09 | 0.00 | 0.149596E+09 | 0.00 | 0.65 |
May | 1606007.64 | 0.171067E+10 | 0.00 | 31332.46 | 0.446206E+09 | 0.00 | 157579.93 | 0.00 | 0.69 |
June | 0.00 | 0.239768E+10 | 0.00 | 0.00 | 0.626177E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
July | 0.00 | 0.253924E+10 | 0.00 | 0.00 | 0.721870E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
August | 0.00 | 0.226518E+10 | 0.00 | 0.00 | 0.753370E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.245427E+10 | 0.00 | 0.00 | 0.509647E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 1294954.84 | 0.160449E+10 | 0.00 | 220179.75 | 0.611111E+09 | 0.00 | 1149841.34 | 0.00 | 0.61 |
November | 89606985.32 | 0.961298E+09 | 0.00 | 1307737.15 | 0.413507E+09 | 0.00 | 0.102307E+09 | 0.00 | 0.50 |
December | 0.264544E+09 | 0.374846E+09 | 0.00 | 2689049.80 | 0.376590E+09 | 0.00 | 0.420870E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.104050E+10 | 0.163941E+11 | 0.00 | 18480500.22 | 0.507761E+10 | 0.00 | 0.245093E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.347748E+09 | 0.00 | 0.00 | 28786012.89 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.301776E+09 | 0.253924E+10 | 0.00 | 4236780.05 | 0.753370E+09 | 0.00 | 0.679752E+09 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.293621E+09 | 0.805763E+09 | 0.00 | 13218013.09 | 31845387.11 | 0.00 | 0.200670E+10 | 0.00 | 0.61 |
February | 0.192531E+09 | 0.790484E+09 | 0.00 | 11050524.95 | 37341913.56 | 0.00 | 0.879073E+09 | 0.00 | 0.58 |
March | 0.227483E+09 | 0.104446E+10 | 0.00 | 7271739.94 | 0.377980E+09 | 0.00 | 0.950549E+09 | 0.00 | 0.60 |
April | 0.145919E+09 | 0.107591E+10 | 0.00 | 3047695.95 | 0.454486E+09 | 0.00 | 0.199847E+09 | 0.00 | 0.60 |
May | 2691826.21 | 0.207717E+10 | 0.00 | 45887.39 | 0.733178E+09 | 0.00 | 46639.70 | 0.00 | 0.56 |
June | 0.00 | 0.286547E+10 | 0.00 | 0.00 | 0.103234E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.312162E+10 | 0.00 | 0.00 | 0.120955E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.00 | 0.339541E+10 | 0.00 | 0.00 | 0.111656E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.383194E+10 | 0.00 | 0.00 | 0.713914E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 1410053.88 | 0.315755E+10 | 0.00 | 391027.79 | 0.788016E+09 | 0.00 | 2684499.95 | 0.00 | 0.72 |
November | 87086439.32 | 0.217947E+10 | 0.00 | 4424464.67 | 0.541903E+09 | 0.00 | 0.323019E+09 | 0.00 | 0.66 |
December | 0.215382E+09 | 0.122447E+10 | 0.00 | 11133125.46 | 0.445986E+09 | 0.00 | 0.161388E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.116613E+10 | 0.255697E+11 | 0.00 | 50582479.24 | 0.748311E+10 | 0.00 | 0.597580E+10 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.790484E+09 | 0.00 | 0.00 | 31845387.11 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.293621E+09 | 0.383194E+10 | 0.00 | 13218013.09 | 0.120955E+10 | 0.00 | 0.200670E+10 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143763E+09 | 0.487432E+09 | 0.00 | 5696599.95 | 28389318.13 | 0.00 | 0.104272E+10 | 0.00 | 0.52 |
February | 71493050.88 | 0.644570E+09 | 0.00 | 7082488.01 | 12762570.48 | 0.00 | 0.699665E+09 | 0.00 | 0.66 |
March | 32180928.30 | 0.125817E+10 | 0.00 | 7858057.83 | 85801423.45 | 0.00 | 0.112074E+10 | 0.00 | 0.90 |
April | 27318403.12 | 0.179453E+10 | 0.00 | 7383824.07 | 54953315.60 | 0.00 | 0.382476E+09 | 0.00 | 1.11 |
May | 1440594.83 | 0.253641E+10 | 0.00 | 62948.58 | 0.239050E+09 | 0.00 | 487928.68 | 0.00 | 0.89 |
June | 0.00 | 0.376453E+10 | 0.00 | 0.00 | 0.221676E+09 | 0.00 | 0.00 | 0.00 | 0.99 |
July | 0.00 | 0.467469E+10 | 0.00 | 0.00 | 0.106944E+09 | 0.00 | 0.00 | 0.00 | 1.09 |
August | 0.00 | 0.529093E+10 | 0.00 | 0.00 | 76492708.51 | 0.00 | 0.00 | 0.00 | 1.20 |
September | 0.00 | 0.339614E+10 | 0.00 | 0.00 | 0.262292E+09 | 0.00 | 0.00 | 0.00 | 0.86 |
October | 281512.32 | 0.284422E+10 | 0.00 | 406866.16 | 0.264972E+09 | 0.00 | 3689875.94 | 0.00 | 0.86 |
November | 53098659.32 | 0.200776E+10 | 0.00 | 2884503.03 | 0.160340E+09 | 0.00 | 0.236144E+09 | 0.00 | 0.80 |
December | 40464461.69 | 0.132909E+10 | 0.00 | 9044198.35 | 96955446.83 | 0.00 | 0.144339E+10 | 0.00 | 0.84 |
Annual Sum or Average | 0.370040E+09 | 0.300285E+11 | 0.00 | 40419485.98 | 0.161063E+10 | 0.00 | 0.492932E+10 | 0.00 | 0.89 |
Minimum of Months | 0.00 | 0.487432E+09 | 0.00 | 0.00 | 12762570.48 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.143763E+09 | 0.529093E+10 | 0.00 | 9044198.35 | 0.264972E+09 | 0.00 | 0.144339E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.930859E+10 | 0.339542E+10 | 0.00 | 8057263.36 | 0.816359E+09 | 0.163090E+09 | 0.134126E+10 | 0.00 | 0.30 |
February | 0.389822E+10 | 0.416168E+10 | 0.00 | 13866819.17 | 0.565655E+09 | 0.328423E+09 | 0.147248E+10 | 0.00 | 0.32 |
March | 0.496454E+10 | 0.672303E+10 | 0.00 | 13998484.30 | 0.963859E+09 | 0.150902E+09 | 0.166688E+10 | 0.00 | 0.35 |
April | 0.471211E+09 | 0.833291E+10 | 0.00 | 15239026.45 | 0.178136E+10 | 0.00 | 0.150976E+10 | 0.00 | 0.42 |
May | 1317727.71 | 0.215648E+11 | 0.00 | 389829.69 | 0.332432E+10 | 0.00 | 2254345.91 | 0.00 | 0.54 |
June | 0.00 | 0.328714E+11 | 0.00 | 0.00 | 0.461213E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
July | 0.00 | 0.342276E+11 | 0.00 | 0.00 | 0.642878E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
August | 0.00 | 0.325506E+11 | 0.00 | 0.00 | 0.537640E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.298181E+11 | 0.00 | 0.00 | 0.534716E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 23725117.19 | 0.190469E+11 | 0.00 | 2474014.31 | 0.393066E+10 | 0.00 | 25703123.13 | 0.00 | 0.44 |
November | 0.159994E+10 | 0.125688E+11 | 0.00 | 5865180.62 | 0.148019E+10 | 0.00 | 0.498781E+09 | 0.00 | 0.36 |
December | 0.735268E+10 | 0.437191E+10 | 0.00 | 8656878.87 | 0.190643E+10 | 0.127722E+09 | 0.186238E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.276202E+11 | 0.209633E+12 | 0.00 | 68547496.76 | 0.365333E+11 | 0.770138E+09 | 0.837950E+10 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.339542E+10 | 0.00 | 0.00 | 0.565655E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.930859E+10 | 0.342276E+11 | 0.00 | 15239026.45 | 0.642878E+10 | 0.328423E+09 | 0.186238E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.356614E+10 | 0.331184E+10 | 0.00 | 24600149.17 | 0.265180E+09 | 1797168.00 | 0.516542E+10 | 0.00 | 0.39 |
February | 0.151232E+10 | 0.366181E+10 | 0.00 | 29831621.06 | 0.243969E+09 | 0.113347E+09 | 0.356584E+10 | 0.00 | 0.45 |
March | 0.138662E+10 | 0.640843E+10 | 0.00 | 34462386.41 | 0.439167E+09 | 1824076.31 | 0.672384E+10 | 0.00 | 0.54 |
April | 0.224225E+09 | 0.859459E+10 | 0.00 | 25058020.51 | 0.894479E+09 | 0.00 | 0.189321E+10 | 0.00 | 0.64 |
May | 929418.92 | 0.184909E+11 | 0.00 | 374650.58 | 0.168497E+10 | 0.00 | 1690239.26 | 0.00 | 0.71 |
June | 0.00 | 0.277860E+11 | 0.00 | 0.00 | 0.235297E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
July | 0.00 | 0.301869E+11 | 0.00 | 0.00 | 0.298580E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
August | 0.00 | 0.279039E+11 | 0.00 | 0.00 | 0.272056E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
September | 0.00 | 0.274681E+11 | 0.00 | 0.00 | 0.233791E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 14326495.84 | 0.180582E+11 | 0.00 | 2637219.75 | 0.189203E+10 | 0.00 | 24295375.87 | 0.00 | 0.60 |
November | 0.745871E+09 | 0.108155E+11 | 0.00 | 9364500.60 | 0.846469E+09 | 0.00 | 0.950861E+09 | 0.00 | 0.47 |
December | 0.318036E+10 | 0.395519E+10 | 0.00 | 16235567.52 | 0.997779E+09 | 2021777.48 | 0.323068E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.106308E+11 | 0.186641E+12 | 0.00 | 0.142564E+09 | 0.176613E+11 | 0.118990E+09 | 0.215558E+11 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.331184E+10 | 0.00 | 0.00 | 0.243969E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.356614E+10 | 0.301869E+11 | 0.00 | 34462386.41 | 0.298580E+10 | 0.113347E+09 | 0.672384E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.339242E+10 | 0.855605E+10 | 0.00 | 0.124139E+09 | 0.221467E+09 | 0.00 | 0.208719E+11 | 0.00 | 0.68 |
February | 0.208753E+10 | 0.809090E+10 | 0.00 | 0.104723E+09 | 0.220952E+09 | 0.116670E+09 | 0.881804E+10 | 0.00 | 0.64 |
March | 0.259808E+10 | 0.106124E+11 | 0.00 | 61405881.46 | 0.574462E+09 | 0.00 | 0.943379E+10 | 0.00 | 0.59 |
April | 0.383945E+09 | 0.106167E+11 | 0.00 | 23946293.73 | 0.160164E+10 | 0.00 | 0.209593E+10 | 0.00 | 0.52 |
May | 1322661.46 | 0.211135E+11 | 0.00 | 481554.14 | 0.342978E+10 | 0.00 | 2205826.74 | 0.00 | 0.54 |
June | 0.00 | 0.300243E+11 | 0.00 | 0.00 | 0.513306E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.325766E+11 | 0.00 | 0.00 | 0.673891E+10 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.358926E+11 | 0.00 | 0.00 | 0.508283E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
September | 0.00 | 0.412695E+11 | 0.00 | 0.00 | 0.344706E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
October | 9643444.51 | 0.341503E+11 | 0.00 | 4746584.78 | 0.192308E+10 | 0.00 | 53908479.51 | 0.00 | 0.71 |
November | 0.679879E+09 | 0.240773E+11 | 0.00 | 41004521.67 | 0.686842E+09 | 0.00 | 0.335297E+10 | 0.00 | 0.68 |
December | 0.247233E+10 | 0.120652E+11 | 0.00 | 0.101343E+09 | 0.591621E+09 | 0.00 | 0.176073E+11 | 0.00 | 0.68 |
Annual Sum or Average | 0.116252E+11 | 0.269045E+12 | 0.00 | 0.461789E+09 | 0.296517E+11 | 0.116670E+09 | 0.622360E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.809090E+10 | 0.00 | 0.00 | 0.220952E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.339242E+10 | 0.412695E+11 | 0.00 | 0.124139E+09 | 0.673891E+10 | 0.116670E+09 | 0.208719E+11 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.423788E+10 | 0.371372E+10 | 0.00 | 23140894.79 | 0.293479E+09 | 0.00 | 0.466417E+10 | 0.00 | 0.41 |
February | 0.177164E+10 | 0.459568E+10 | 0.00 | 32910957.15 | 0.149862E+09 | 0.170251E+09 | 0.328260E+10 | 0.00 | 0.50 |
March | 0.223885E+10 | 0.783684E+10 | 0.00 | 34809513.42 | 0.261247E+09 | 0.00 | 0.513168E+10 | 0.00 | 0.62 |
April | 0.187135E+09 | 0.106680E+11 | 0.00 | 38515804.26 | 0.534200E+09 | 0.00 | 0.213951E+10 | 0.00 | 0.75 |
May | 926595.99 | 0.211702E+11 | 0.00 | 494509.05 | 0.104910E+10 | 0.00 | 1834578.06 | 0.00 | 0.78 |
June | 0.00 | 0.288342E+11 | 0.00 | 0.00 | 0.175408E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
July | 0.00 | 0.331925E+11 | 0.00 | 0.00 | 0.211317E+10 | 0.00 | 0.00 | 0.00 | 0.86 |
August | 0.00 | 0.334108E+11 | 0.00 | 0.00 | 0.166645E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
September | 0.00 | 0.289894E+11 | 0.00 | 0.00 | 0.167819E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
October | 6348413.32 | 0.202703E+11 | 0.00 | 2841524.63 | 0.128798E+10 | 0.00 | 35158160.58 | 0.00 | 0.65 |
November | 0.781443E+09 | 0.126203E+11 | 0.00 | 10683150.68 | 0.618391E+09 | 0.00 | 0.932889E+09 | 0.00 | 0.53 |
December | 0.306871E+10 | 0.574244E+10 | 0.00 | 23649342.71 | 0.714930E+09 | 0.00 | 0.463479E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.122929E+11 | 0.211044E+12 | 0.00 | 0.167046E+09 | 0.121211E+11 | 0.170251E+09 | 0.208226E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.371372E+10 | 0.00 | 0.00 | 0.149862E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.423788E+10 | 0.334108E+11 | 0.00 | 38515804.26 | 0.211317E+10 | 0.170251E+09 | 0.513168E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.848003E+09 | 0.312658E+09 | 0.00 | 726050.35 | 98283159.13 | 80806577.20 | 0.113081E+09 | 0.00 | 0.30 |
February | 0.352808E+09 | 0.381101E+09 | 53075.78 | 1381073.32 | 70893562.65 | 35317341.38 | 0.140531E+09 | 5189.45 | 0.31 |
March | 0.460830E+09 | 0.665665E+09 | 0.00 | 1436780.16 | 0.109407E+09 | 39810306.24 | 0.175615E+09 | 0.00 | 0.35 |
April | 63453990.50 | 0.769298E+09 | 0.00 | 1518113.37 | 0.179036E+09 | 0.00 | 0.137006E+09 | 0.00 | 0.41 |
May | 127320.90 | 0.204399E+10 | 0.00 | 20603.54 | 0.305454E+09 | 0.00 | 128082.46 | 0.00 | 0.52 |
June | 0.00 | 0.311703E+10 | 0.00 | 0.00 | 0.428476E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.328353E+10 | 0.00 | 0.00 | 0.564051E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.308900E+10 | 0.00 | 0.00 | 0.500948E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.284003E+10 | 0.00 | 0.00 | 0.488763E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 1584547.42 | 0.176098E+10 | 0.00 | 232503.03 | 0.391376E+09 | 0.00 | 2394783.89 | 0.00 | 0.43 |
November | 0.114657E+09 | 0.113770E+10 | 0.00 | 442327.92 | 0.211175E+09 | 27465420.43 | 50752589.97 | 0.00 | 0.35 |
December | 0.683486E+09 | 0.408116E+09 | 0.00 | 804388.93 | 0.222232E+09 | 59204392.78 | 0.146161E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.252495E+10 | 0.198091E+11 | 53075.78 | 6561840.63 | 0.357010E+10 | 0.242604E+09 | 0.765671E+09 | 5189.45 | 0.44 |
Minimum of Months | 0.00 | 0.312658E+09 | 0.00 | 0.00 | 70893562.65 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.848003E+09 | 0.328353E+10 | 53075.78 | 1518113.37 | 0.564051E+09 | 80806577.20 | 0.175615E+09 | 5189.45 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.343008E+09 | 0.338318E+09 | 0.00 | 2183333.34 | 29843331.41 | 17421689.76 | 0.490532E+09 | 0.00 | 0.40 |
February | 0.150388E+09 | 0.361764E+09 | 0.00 | 2874683.85 | 30535771.38 | 9584843.63 | 0.339146E+09 | 0.00 | 0.46 |
March | 0.119665E+09 | 0.680146E+09 | 0.00 | 3290268.92 | 43673043.80 | 6497503.81 | 0.692867E+09 | 0.00 | 0.56 |
April | 19442093.48 | 0.842891E+09 | 0.00 | 2737456.81 | 79955440.28 | 0.00 | 0.204353E+09 | 0.00 | 0.64 |
May | 63896.96 | 0.179738E+10 | 0.00 | 23336.50 | 0.158047E+09 | 0.00 | 111306.14 | 0.00 | 0.71 |
June | 0.00 | 0.268696E+10 | 0.00 | 0.00 | 0.224043E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
July | 0.00 | 0.293480E+10 | 0.00 | 0.00 | 0.274488E+09 | 0.00 | 0.00 | 0.00 | 0.80 |
August | 0.00 | 0.272151E+10 | 0.00 | 0.00 | 0.259987E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 0.00 | 0.265855E+10 | 0.00 | 0.00 | 0.220465E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 974949.96 | 0.173688E+10 | 0.00 | 285082.46 | 0.188107E+09 | 0.00 | 2533611.63 | 0.00 | 0.61 |
November | 63090363.46 | 0.106019E+10 | 0.00 | 764090.11 | 0.102184E+09 | 7570149.91 | 87649652.49 | 0.00 | 0.48 |
December | 0.301889E+09 | 0.382953E+09 | 0.00 | 1464448.00 | 0.125066E+09 | 31999505.13 | 0.304242E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.998522E+09 | 0.182024E+11 | 0.00 | 13622700.00 | 0.173639E+10 | 73073692.24 | 0.212144E+10 | 0.00 | 0.61 |
Minimum of Months | 0.00 | 0.338318E+09 | 0.00 | 0.00 | 29843331.41 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.343008E+09 | 0.293480E+10 | 0.00 | 3290268.92 | 0.274488E+09 | 31999505.13 | 0.692867E+09 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.323954E+09 | 0.841217E+09 | 0.00 | 11089947.49 | 24472518.14 | 16164878.52 | 0.209902E+10 | 0.00 | 0.68 |
February | 0.178075E+09 | 0.746976E+09 | 0.00 | 10152282.62 | 27232132.23 | 14922321.13 | 0.888082E+09 | 0.00 | 0.62 |
March | 0.256751E+09 | 0.105018E+10 | 0.00 | 6105071.30 | 56693839.60 | 11073510.86 | 0.957670E+09 | 0.00 | 0.57 |
April | 39773459.23 | 0.986309E+09 | 0.00 | 2806611.83 | 0.143931E+09 | 0.00 | 0.212462E+09 | 0.00 | 0.49 |
May | 98949.21 | 0.199705E+10 | 0.00 | 25250.66 | 0.313850E+09 | 0.00 | 151696.23 | 0.00 | 0.52 |
June | 0.00 | 0.285565E+10 | 0.00 | 0.00 | 0.473800E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.311311E+10 | 0.00 | 0.00 | 0.607305E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.338464E+10 | 0.00 | 0.00 | 0.462631E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.386709E+10 | 0.00 | 0.00 | 0.319541E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 1275610.05 | 0.316413E+10 | 0.00 | 429433.79 | 0.185047E+09 | 0.00 | 4226938.87 | 0.00 | 0.70 |
November | 46112809.20 | 0.230626E+10 | 0.00 | 3465268.11 | 84318933.44 | 5995211.92 | 0.342491E+09 | 0.00 | 0.66 |
December | 0.232238E+09 | 0.119046E+10 | 0.00 | 8952356.46 | 61598413.41 | 29887340.74 | 0.169906E+10 | 0.00 | 0.67 |
Annual Sum or Average | 0.107828E+10 | 0.255031E+11 | 0.00 | 43026222.26 | 0.276042E+10 | 78043263.16 | 0.620316E+10 | 0.00 | 0.61 |
Minimum of Months | 0.00 | 0.746976E+09 | 0.00 | 0.00 | 24472518.14 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.323954E+09 | 0.386709E+10 | 0.00 | 11089947.49 | 0.607305E+09 | 29887340.74 | 0.209902E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.424695E+09 | 0.354155E+09 | 0.00 | 2098324.33 | 36447017.16 | 13752571.06 | 0.432138E+09 | 0.00 | 0.40 |
February | 0.157540E+09 | 0.427743E+09 | 0.00 | 3375257.68 | 19311036.81 | 14686465.20 | 0.328209E+09 | 0.00 | 0.48 |
March | 0.220286E+09 | 0.771361E+09 | 0.00 | 3801218.09 | 28874269.25 | 6402642.61 | 0.525850E+09 | 0.00 | 0.60 |
April | 14122781.95 | 0.983793E+09 | 0.00 | 4259076.15 | 45230211.88 | 0.00 | 0.226926E+09 | 0.00 | 0.70 |
May | 63931.25 | 0.196329E+10 | 0.00 | 24910.32 | 0.100427E+09 | 0.00 | 117474.07 | 0.00 | 0.74 |
June | 0.00 | 0.268242E+10 | 0.00 | 0.00 | 0.165535E+09 | 0.00 | 0.00 | 0.00 | 0.77 |
July | 0.00 | 0.308182E+10 | 0.00 | 0.00 | 0.199173E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
August | 0.00 | 0.310057E+10 | 0.00 | 0.00 | 0.157994E+09 | 0.00 | 0.00 | 0.00 | 0.81 |
September | 0.00 | 0.270200E+10 | 0.00 | 0.00 | 0.167891E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 613833.39 | 0.186968E+10 | 0.00 | 237533.28 | 0.127447E+09 | 0.00 | 2823118.13 | 0.00 | 0.63 |
November | 55052375.39 | 0.118536E+10 | 0.00 | 892037.52 | 74223187.83 | 10459978.80 | 0.101991E+09 | 0.00 | 0.51 |
December | 0.310076E+09 | 0.571146E+09 | 0.00 | 2116339.78 | 71214416.69 | 26459929.33 | 0.395088E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.118245E+10 | 0.196934E+11 | 0.00 | 16804697.14 | 0.119377E+10 | 71761587.01 | 0.201314E+10 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 0.354155E+09 | 0.00 | 0.00 | 19311036.81 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.424695E+09 | 0.310057E+10 | 0.00 | 4259076.15 | 0.199173E+09 | 26459929.33 | 0.525850E+09 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.144538E+09 | 0.00 | 5487788.13 | 0.00 | 0.00 | 0.270911E+09 | 0.00 | 0.58 |
February | 0.00 | 0.191995E+09 | 0.00 | 8935286.37 | 0.00 | 0.00 | 0.171402E+09 | 0.00 | 0.58 |
March | 0.00 | 0.325449E+09 | 0.00 | 11248334.68 | 0.00 | 0.00 | 0.163330E+09 | 0.00 | 0.58 |
April | 0.00 | 0.424438E+09 | 0.00 | 5444212.50 | 0.00 | 0.00 | 31016694.94 | 0.00 | 0.58 |
May | 0.00 | 0.722790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.105451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.116442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.119539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.943980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.854221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.577076E+09 | 0.00 | 7077047.81 | 0.00 | 0.00 | 61227602.30 | 0.00 | 0.58 |
December | 0.00 | 0.316470E+09 | 0.00 | 16283094.53 | 0.00 | 0.00 | 0.176341E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.791528E+10 | 0.00 | 54475764.03 | 0.00 | 0.00 | 0.874229E+09 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.144538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.119539E+10 | 0.00 | 16283094.53 | 0.00 | 0.00 | 0.270911E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.138758E+10 | 0.00 | 43277430.38 | 0.00 | 0.00 | 0.274921E+10 | 0.00 | 0.58 |
February | 0.00 | 0.190117E+10 | 0.00 | 79083523.33 | 0.00 | 0.00 | 0.172287E+10 | 0.00 | 0.58 |
March | 0.00 | 0.325246E+10 | 0.00 | 0.103979E+09 | 0.00 | 0.00 | 0.163716E+10 | 0.00 | 0.58 |
April | 0.00 | 0.425449E+10 | 0.00 | 51587888.57 | 0.00 | 0.00 | 0.310792E+09 | 0.00 | 0.58 |
May | 0.00 | 0.715020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.105134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.116313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.119856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.933831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.851254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.576411E+10 | 0.00 | 64576364.06 | 0.00 | 0.00 | 0.616699E+09 | 0.00 | 0.58 |
December | 0.00 | 0.316555E+10 | 0.00 | 0.150445E+09 | 0.00 | 0.00 | 0.176888E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.788568E+11 | 0.00 | 0.492949E+09 | 0.00 | 0.00 | 0.880561E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.138758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.119856E+11 | 0.00 | 0.150445E+09 | 0.00 | 0.00 | 0.274921E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.136171E+09 | 0.00 | 3453928.77 | 0.00 | 0.00 | 0.279355E+09 | 0.00 | 0.58 |
February | 0.00 | 0.189266E+09 | 0.00 | 7355157.19 | 0.00 | 0.00 | 0.173390E+09 | 0.00 | 0.58 |
March | 0.00 | 0.324419E+09 | 0.00 | 10062296.16 | 0.00 | 0.00 | 0.164441E+09 | 0.00 | 0.58 |
April | 0.00 | 0.424313E+09 | 0.00 | 5120489.02 | 0.00 | 0.00 | 31245956.48 | 0.00 | 0.58 |
May | 0.00 | 0.716773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.105143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.116256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.120058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.935815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.850288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.575083E+09 | 0.00 | 6166480.57 | 0.00 | 0.00 | 62146732.22 | 0.00 | 0.58 |
December | 0.00 | 0.315471E+09 | 0.00 | 14502962.41 | 0.00 | 0.00 | 0.178052E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.788217E+10 | 0.00 | 46661314.11 | 0.00 | 0.00 | 0.888631E+09 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.136171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.120058E+10 | 0.00 | 14502962.41 | 0.00 | 0.00 | 0.279355E+09 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.368373E+10 | 0.00 | 0.300960E+09 | 0.00 | 0.00 | 0.597477E+10 | 0.00 | 0.66 |
February | 0.00 | 0.434682E+10 | 0.00 | 0.448725E+09 | 0.00 | 0.00 | 0.388263E+10 | 0.00 | 0.66 |
March | 0.00 | 0.709301E+10 | 0.00 | 0.553268E+09 | 0.00 | 0.00 | 0.362745E+10 | 0.00 | 0.66 |
April | 0.00 | 0.836728E+10 | 0.00 | 0.260067E+09 | 0.00 | 0.00 | 0.590582E+09 | 0.00 | 0.66 |
May | 0.00 | 0.172474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
June | 0.00 | 0.236777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.255582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.224589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.223406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
October | 0.00 | 0.191839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
November | 0.00 | 0.126480E+11 | 0.00 | 0.332927E+09 | 0.00 | 0.00 | 0.128001E+10 | 0.00 | 0.66 |
December | 0.00 | 0.648913E+10 | 0.00 | 0.798764E+09 | 0.00 | 0.00 | 0.363206E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.173095E+12 | 0.00 | 0.269471E+10 | 0.00 | 0.00 | 0.189875E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.368373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.255582E+11 | 0.00 | 0.798764E+09 | 0.00 | 0.00 | 0.597477E+10 | 0.00 | 0.66 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:50:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.352628E+12 | 0.376612E+10 | 0.00 | 0.261321E+12 | 0.171411E+13 |
February | 0.373105E+12 | 0.402933E+10 | 0.00 | 0.109173E+12 | 0.214480E+13 |
March | 0.515230E+12 | 0.919386E+09 | 0.00 | 0.891067E+10 | 0.296892E+13 |
April | 0.556691E+12 | -0.315389E+10 | 0.00 | -0.241484E+12 | 0.358309E+13 |
May | 0.524742E+12 | -0.148465E+11 | 0.00 | -0.786387E+12 | 0.303154E+13 |
June | 0.466144E+12 | -0.172517E+11 | 0.00 | -0.119622E+13 | 0.369534E+13 |
July | 0.509040E+12 | -0.157773E+11 | 0.00 | -0.131856E+13 | 0.423922E+13 |
August | 0.558399E+12 | -0.183090E+11 | 0.00 | -0.134080E+13 | 0.466788E+13 |
September | 0.412542E+12 | -0.166341E+11 | 0.00 | -0.119244E+13 | 0.324580E+13 |
October | 0.413166E+12 | -0.134209E+11 | 0.00 | -0.926075E+12 | 0.342190E+13 |
November | 0.305394E+12 | -0.382206E+10 | 0.00 | -0.440325E+12 | 0.321906E+13 |
December | 0.337615E+12 | 0.552458E+09 | 0.00 | 0.435448E+11 | 0.306032E+13 |
Annual Sum or Average | 0.532470E+13 | -0.939482E+11 | 0.00 | -0.701934E+13 | 0.389920E+14 |
Minimum of Months | 0.305394E+12 | -0.183090E+11 | 0.00 | -0.134080E+13 | 0.171411E+13 |
Maximum of Months | 0.558399E+12 | 0.402933E+10 | 0.00 | 0.261321E+12 | 0.466788E+13 |