Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:50
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 08:50:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32010.49 | 691.07 | 691.07 |
Net Site Energy | 32010.49 | 691.07 | 691.07 |
Total Source Energy | 99977.92 | 2158.40 | 2158.40 |
Net Source Energy | 99977.92 | 2158.40 | 2158.40 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 62.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6552.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2459.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 349.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1909.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2677.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 818.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1812.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19433.20 |
Humidification | 83.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.99 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 609.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31338.71 | 671.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21744.35 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 62.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 6552.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2459.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 349.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2677.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 818.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1812.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19433.20 |
Humidification | General | 83.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.99 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 609.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 62.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6552.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2459.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 349.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1909.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2677.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 818.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1812.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19433.20 |
Humidification | Unassigned | 83.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.99 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 609.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 257.86 | 14.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Other | 358.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 676.56 | 14.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 257.86 | 14.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Other | 358.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 676.56 | 14.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31338.715 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31338.715 | 100.00 |
Total On-Site and Utility Electric Sources | 31338.715 | 100.00 |
Total Electricity End Uses | 31338.715 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 21744.35 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 21744.35 | 100.00 |
Total Water End Uses | 21744.35 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1163.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:50 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:20 | 02-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 12-JUN-15:30 |
Heating | 0.00 | 710497.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 573957.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82829.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 244835.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 49401.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 84253.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2026463.93 | 717777.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 710497.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 573957.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 244835.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 49401.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 84253.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 7280.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 67.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20750.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7789.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1106.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6046.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8480.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2593.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 5739.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 263.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 660.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 99249.71 | 728.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 447.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 55.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 123.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2142.68 | 15.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 447.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 168.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 55.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 123.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2142.68 | 15.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.36 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.481982 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.60 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.465226 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.87 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.95 | 0.319524 | 0.272000 | 1.62 | 0.852064 | 0.500000 | 0.001192 | 0.000139 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 56.96 | 0.333954 | 0.284000 | 16.18 | 0.890543 | 0.500000 | 0.001141 | 0.003377 | 16.18 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.82 | 0.326762 | 0.278000 | 1.62 | 0.871366 | 0.500000 | 0.001166 | 0.000596 | 2.08 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.30 | 0.183014 | 0.156000 | 0.203570 | 0.488036 | 0.500000 | 0.002082 | 0.000060 | 0.209982 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.03 | 0.149213 | 0.127000 | 0.130994 | 0.397901 | 0.500000 | 0.002553 | 0.000044 | 0.153484 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.32 | 0.181343 | 0.154000 | 0.202815 | 0.483582 | 0.500000 | 0.002101 | 0.000080 | 0.280510 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.35 | 0.113935 | 0.097000 | 0.131030 | 0.303825 | 0.500000 | 0.003344 | 0.000029 | 0.131030 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 13.11 | 0.182206 | 0.155000 | 2.03 | 0.485883 | 0.500000 | 0.002091 | 0.001422 | 4.97 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.90 | 0.376594 | 0.500000 | 0.002698 | 0.000939 | 3.28 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 13.10 | 0.182251 | 0.155000 | 2.03 | 0.486003 | 0.500000 | 0.002091 | 0.001422 | 4.97 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.98 | 0.128450 | 0.109000 | 1.31 | 0.342533 | 0.500000 | 0.002966 | 0.000861 | 3.01 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.47 | 0.162177 | 0.138000 | 0.203218 | 0.432471 | 0.500000 | 0.002349 | 0.000176 | 0.616053 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.14 | 0.135547 | 0.115000 | 0.130575 | 0.361458 | 0.500000 | 0.002811 | 0.000116 | 0.404318 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.47 | 0.162566 | 0.138000 | 0.202736 | 0.433509 | 0.500000 | 0.002344 | 0.000176 | 0.616059 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.30 | 0.118203 | 0.100000 | 0.130204 | 0.315208 | 0.500000 | 0.003223 | 0.000110 | 0.384213 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 15891.53 | 0.000139 | 320.36 |
CORE_MID VAV BOX REHEAT COIL | 385983.24 | 0.003377 | 9077.81 |
CORE_TOP VAV BOX REHEAT COIL | 68090.67 | 0.000596 | 1798.70 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6894.62 | 0.000060 | 182.22 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5036.28 | 0.000044 | 133.07 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9195.50 | 0.000080 | 242.85 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3344.00 | 0.000029 | 80.26 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 162503.79 | 0.001422 | 4287.43 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 107364.33 | 0.000939 | 2832.56 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 162504.86 | 0.001422 | 4287.46 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 98464.27 | 0.000861 | 2598.03 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20140.35 | 0.000176 | 531.25 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13217.65 | 0.000116 | 348.64 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20140.54 | 0.000176 | 531.25 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12561.74 | 0.000110 | 331.35 |
VAV_BOT WITH REHEAT HEATING COIL | 20575.73 | 0.000180 | 361.60 |
VAV_MID WITH REHEAT HEATING COIL | 73237.61 | 0.000641 | 1322.86 |
VAV_TOP WITH REHEAT HEATING COIL | 8208.18 | 0.000072 | 148.33 |
CAV_BAS HEATING COIL | 244195.30 | 0.002136 | 5562.77 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.48 | 2.29 | 10.96 | 2.29 | 10.02 | 10.02 | 0.300000 | 0.228235 | 10.02 |
VAV_MID WITH REHEAT | 53.02 | 22.85 | 106.05 | 27.01 | 96.10 | 96.10 | 0.300000 | 0.281027 | 96.10 |
VAV_TOP WITH REHEAT | 5.60 | 2.28 | 11.20 | 4.10 | 11.06 | 11.06 | 0.300000 | 0.370412 | 11.06 |
CAV_BAS | 5.36 | 5.36 | 5.36 | 5.36 | 5.36 | 5.36 | 1.00 | 1.00 | 5.36 |
AIRLOOP DATACENTER BASEMENT | 21.87 | 21.87 | 21.87 | 21.87 | 21.87 | 21.87 | 1.00 | 0.999990 | 21.87 |
AIRLOOP DATACENTER BOT | 0.481982 | 0.481982 | 0.481982 | 0.481982 | 0.481982 | 0.481982 | 1.00 | 1.00 | 0.481982 |
AIRLOOP DATACENTER MID | 4.60 | 4.60 | 4.60 | 4.60 | 4.60 | 4.60 | 1.00 | 1.00 | 4.60 |
AIRLOOP DATACENTER TOP | 0.465226 | 0.465226 | 0.465226 | 0.465226 | 0.465226 | 0.465226 | 1.00 | 1.00 | 0.465226 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.02 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 96.10 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.06 | |
CAV_BAS_OA_CONTROLLER | 5.36 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.87 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.481982 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.60 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.465226 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.65 | 6.67 | 10.99 | 0.007702 | 0.007000 | 220524.68 | 0.006307 | 10.02 |
VAV_MID WITH REHEAT COOLING COIL | 27.90 | 6.67 | 10.99 | 0.007757 | 0.007000 | 2159235.10 | 0.061754 | 96.10 |
VAV_TOP WITH REHEAT COOLING COIL | 27.29 | 6.67 | 11.00 | 0.007658 | 0.007000 | 237054.68 | 0.006780 | 11.06 |
CAV_BAS COOLING COIL | 27.84 | 6.67 | 11.38 | 0.007912 | 0.007000 | 120181.96 | 0.003437 | 5.36 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.02 |
VAV_MID WITH REHEAT FAN | 96.10 |
VAV_TOP WITH REHEAT FAN | 11.06 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006307 | 0.000076 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000180 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.061754 | 0.000008 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.000641 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006780 | 0.000070 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000072 | |
CAV_BAS_COOLC_CONTROLLER | 0.003437 | 0.000139 |
CAV_BAS_HEATC_CONTROLLER | 0.002136 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.36 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.87 | 450505.06 | 280539.33 | 0.011033 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.481982 | 9911.25 | 6164.78 | 0.000243 |
AIRLOOP DATACENTER MID COOLING COIL | 4.60 | 92262.15 | 58126.40 | 0.002259 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.465226 | 9573.50 | 5952.57 | 0.000234 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.87 | 21.87 | 21.87 | 21.87 | 450505.06 | 450505.06 | 13450.69 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.481982 | 0.481982 | 0.481982 | 0.481982 | 9911.25 | 9911.25 | 621.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.60 | 4.60 | 4.60 | 4.60 | 92262.15 | 92262.15 | 6213.66 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.465226 | 0.465226 | 0.465226 | 0.465226 | 9573.50 | 9573.50 | 621.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.87 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.481982 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.60 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.465226 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.87 | 450505.06 | 0.011033 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.481982 | 9911.25 | 0.000243 |
AIRLOOP DATACENTER MID HEATING COIL | 4.60 | 92262.15 | 0.002259 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.465226 | 9573.50 | 0.000234 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 13450.69 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 621.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6213.66 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 621.37 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000048 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.078278 | 12653.83 | |
HEATSYS1 PUMP | 0.012576 | 3749.93 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.078278 | 9.39 |
HEATSYS1 | 0.012576 | 1.51 |
COOLSYS1_SUPPLY | 0.078278 | 9.39 |
SINGLE WATER PLANT LOOP | 0.013770 | 1.65 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.078278 | 0.078278 | 328571.00 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1437550.20 | 1437550.20 | 0.012576 |
CENTRAL BOILER | 567185.94 | 556188.92 | 0.013770 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.039139 | 4380.34 |
COOLSYS1 CHILLER2 PUMP | 0.039139 | 4380.34 |
PLANT CIRC PUMP | 0.013770 | 3477.14 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.078278 | 0.039543 | 1386014.37 | 1392589.28 | 0.068914 |
COOLSYS1 CHILLER2 | 0.078278 | 0.039543 | 1386014.37 | 1392589.28 | 0.068914 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013770 | 139666.47 | 57509.82 | 69833.23 | 7004.20 | 21235.74 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.137828 | 16.54 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.137828 | 33785.35 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 54.64 | 1652273.19 | 10.93 | 206534.15 |
TOWERWATERSYS COOLTOWER 2 | 54.64 | 1652273.19 | 10.93 | 206534.15 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.071580 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.229 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.229 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.230 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.14029 | 0.63148 | 0.63148 | 0.25190 | 0.16103 | 0.23774 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4306E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4319E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6212E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6222E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7737E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7744E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6123E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6128E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4593E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5392E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6446E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7116E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7921E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8461E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6259E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6600E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.5698E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4573E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.3962E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6486E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7735E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4606E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8968E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0048E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4651E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5672E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6508E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7417E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7978E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8678E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6263E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6610E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4305E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4320E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6211E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6223E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7737E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7746E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.6122E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6127E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5778E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7177E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4166E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5609E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2396E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3127E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7571E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7807E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0105E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8837E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7658E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7088E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8360E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5461E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0167E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.1262E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5454E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6026E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3763E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4182E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2176E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2352E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7572E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7811E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5795E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5808E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3590E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3601E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2057E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2065E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6123E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6128E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6088E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6812E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3831E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4407E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2248E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2661E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6263E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6611E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4232E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2556E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8773E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.5976E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6679E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.4991E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8968E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0045E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6068E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6786E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3805E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4355E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2203E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2526E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6260E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6601E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5794E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5806E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3589E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3599E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2056E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2062E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6123E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6128E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0666E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1262E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7967E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8398E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7693E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7851E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7572E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7811E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1848E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5773E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7761E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3423E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0214E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2396E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0167E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1262E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0924E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2024E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8293E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9373E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7898E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8541E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7570E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7806E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.9629E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.0849E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.6005E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.3564E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.5176E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.7626E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.5538E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.7566E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7829E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7353E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5105E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5228E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5624E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3125E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6430E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7769E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0510E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0150E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4296E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6083E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.1934E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2154E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.5538E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7563E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.8473E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3098E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3878E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.0123E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6469E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8983E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6430E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7769E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.9738E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.0958E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.6136E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.3687E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.5313E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.7720E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.5614E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.7605E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7875E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7397E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5157E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5270E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5701E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3174E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6507E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7808E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0515E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0172E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4303E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6102E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.1969E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2175E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.5614E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7602E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.8499E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3131E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3906E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0152E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6529E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9021E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6507E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7808E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 72448.55391 | 72448.55391 | 5.36490 | 5.36490 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 6.30000 | 6.07234E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 80375.85774 | 80375.85774 | 5.95274 | 5.95274 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 769180.85883 | 769180.85883 | 56.95531 | 56.95531 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 227226.30141 | 227226.30141 | 9.81660 | 10.77825 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 77880.80667 | 77880.80667 | 5.82088 | 5.82088 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 41.90300 | 9.15774E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 47714.70394 | 47714.70394 | 2.07605 | 2.07605 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 17459.53335 | 17459.53335 | 1.30493 | 1.30493 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 41.51500 | 9.15709E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 4834.09693 | 4834.09693 | 0.20998 | 0.20998 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 13800.39495 | 13800.39495 | 1.03145 | 1.03145 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 38.79900 | 9.15255E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3530.13919 | 3530.13919 | 0.15348 | 0.15348 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 17620.74485 | 17620.74485 | 1.31698 | 1.31698 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6442.73413 | 6442.73413 | 0.28051 | 0.28051 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18073.59859 | 18073.59859 | 1.35082 | 1.35082 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2058.38127 | 2058.38127 | 8.89428E-002 | 8.89428E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 175366.49002 | 175366.49002 | 13.10717 | 13.10717 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | 41.41800 | 9.15693E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 113748.48389 | 113748.48389 | 4.96805 | 4.96805 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 145810.16429 | 145810.16429 | 10.89805 | 10.89805 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 39.04150 | 9.15295E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 75150.00462 | 75150.00462 | 3.28256 | 3.28256 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 175326.83107 | 175326.83107 | 13.10420 | 13.10420 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 113749.23511 | 113749.23511 | 4.96809 | 4.96809 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 160309.32265 | 160309.32265 | 11.98172 | 11.98172 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 68927.77742 | 68927.77742 | 3.00976 | 3.00976 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 19702.40521 | 19702.40521 | 1.47259 | 1.47259 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 41.51500 | 9.15709E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 14094.39711 | 14094.39711 | 0.61605 | 0.61605 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15191.49254 | 15191.49254 | 1.13544 | 1.13544 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 39.52650 | 9.15377E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9249.66612 | 9249.66612 | 0.40432 | 0.40432 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 19655.65608 | 19655.65608 | 1.46910 | 1.46910 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 14094.53361 | 14094.53361 | 0.61606 | 0.61606 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17420.53685 | 17420.53685 | 1.30204 | 1.30204 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8791.10993 | 8791.10993 | 0.38421 | 0.38421 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8176.98478 | 8176.98478 | 0.48198 | 0.48198 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 78086.29164 | 78086.29164 | 4.60270 | 4.60270 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7891.77817 | 7891.77817 | 0.46523 | 0.46523 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 40.77133 | 9.15585E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371001.36778 | 371001.36778 | 21.87031 | 21.87031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 33.17300 | 9.14325E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 6.30000 | 6.07234E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 175336.96 | 10.02280 | 10.02280 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 13882.38 | 1.81074 | 1.81074 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1668331.07 | 96.09996 | 96.09996 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 152170.03 | 27.00671 | 27.00671 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 188612.23 | 11.05984 | 11.05984 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 15351.72 | 4.09670 | 4.09670 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
7 | CAV_BAS | Cooling | Sensible | 87324.75 | 5.36490 | 5.36490 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 47704.73 | 1.20016 | 1.20016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 371793.25 | 21.87054 | 21.87054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 13450.69 | 0.33839 | 0.33839 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8177.02 | 0.48198 | 0.48198 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78078.58 | 4.60270 | 4.60270 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6213.66 | 0.15632 | 0.15632 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8048.39 | 0.46523 | 0.46523 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.36490 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.95274 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31952 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27200 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61915 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85206 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19240E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.39026E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61915 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15891.53350 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.39026E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 320.36084 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.95531 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33395 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28400 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.17531 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89054 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14088E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.37675E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.17531 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 385983.24008 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.37675E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9077.80827 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.82088 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32676 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27800 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61820 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87137 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.16598E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.95687E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.07605 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 68090.66860 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.95687E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1798.69994 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30493 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18301 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15600 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20357 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48804 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08181E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.03171E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20998 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6894.61686 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.03171E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 182.22231 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03145 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14921 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12700 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13099 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39790 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55340E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.40596E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.15348 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5036.28343 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.40596E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 133.06765 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31698 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18134 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15400 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20282 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48358 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10099E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.04462E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28051 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9195.49737 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.04462E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 242.85333 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35082 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11393 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.70000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13103 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30383 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34403E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.92548E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13103 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3344.00274 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.92548E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 80.26365 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.10717 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18221 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03161 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48588 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09104E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.42165E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.96805 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 162503.79331 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42165E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4287.42690 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.89805 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37659 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69787E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.39270E-004 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.28256 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 107364.32780 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.39270E-004 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2832.56293 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.10420 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18225 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15500 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03115 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48600 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09052E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.42166E-003 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.96809 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 162504.86341 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42166E-003 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4287.45521 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.98172 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12845 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10900 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30601 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34253 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96614E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.61408E-004 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.00976 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 98464.27144 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.61408E-004 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2598.02932 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.47259 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16218 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13800 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20322 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43247 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34929E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.76197E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61605 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20140.34748 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.76197E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 531.24599 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13544 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13555 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11500 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13058 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36146 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81084E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15634E-004 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40432 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13217.64794 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15634E-004 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 348.63797 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46910 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16257 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13800 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20274 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43351 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34366E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.76198E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61606 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20140.54229 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.76198E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 531.25114 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30204 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11820 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10000 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13020 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31521 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22326E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09896E-004 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38421 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12561.74300 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09896E-004 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 331.35364 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48198 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.60270 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46523 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.87031 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.47846 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28755 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.95692 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28755 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.02280 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.02280 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.22823 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 53.02322 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.85184 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 106.04645 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 27.00671 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 96.09996 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 96.09996 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28103 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.60003 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28494 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.20005 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.09670 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.05984 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.05984 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.37041 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.36490 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.36490 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.36490 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.36490 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.36490 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.36490 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.87031 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.87031 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.87031 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.87031 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.87054 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.87054 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48198 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48198 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48198 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48198 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48198 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.48198 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.60270 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.60270 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.60270 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.60270 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.60270 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.60270 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46523 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46523 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46523 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46523 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46523 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46523 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.02280 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 96.09996 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.05984 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.36490 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.87054 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.48198 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.60270 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46523 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.02280 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.65012 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.99360 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.70165E-003 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 220524.68282 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.30698E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.02280 |
294 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 20575.73482 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80006E-004 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 361.60422 |
297 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.02280 |
298 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.30698E-003 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.55022E-005 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.80006E-004 |
301 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 96.09996 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.90125 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.99378 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.75710E-003 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2159235.10169 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.17538E-002 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 96.09996 |
310 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 73237.60688 |
311 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.40715E-004 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1322.86257 |
313 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 96.09996 |
314 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.17538E-002 |
315 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.71111E-006 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.40715E-004 |
317 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.05984 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.29372 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00305 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.65797E-003 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 237054.67562 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.77973E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.05984 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 8208.17761 |
327 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.18087E-005 |
328 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 148.32572 |
329 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.05984 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.77973E-003 |
331 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.02373E-005 |
332 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.18087E-005 |
333 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.36490 |
334 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.84477 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.38310 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.91249E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 120181.96491 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.43719E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.36490 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 244195.30450 |
344 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13633E-003 |
345 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5562.76545 |
346 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.36490 |
347 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.43719E-003 |
348 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.38541E-004 |
349 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.13633E-003 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.87054 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.87054 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 450505.05766 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 280539.32648 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10328E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.87054 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.87054 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.87054 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.87054 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 450505.05766 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 450505.05766 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 13450.69260 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.87054 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.87054 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 450505.05766 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10328E-002 |
368 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 13450.69260 |
369 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 4.77521E-005 |
370 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48198 |
374 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
375 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48198 |
376 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9911.24892 |
377 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6164.78053 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42726E-004 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48198 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48198 |
381 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48198 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48198 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9911.24892 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9911.24892 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48198 |
388 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48198 |
389 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9911.24892 |
390 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42726E-004 |
391 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.60270 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
394 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.60270 |
395 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92262.14776 |
396 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 58126.39996 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25949E-003 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.60270 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.60270 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.60270 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.60270 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92262.14776 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92262.14776 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6213.66275 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
406 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.60270 |
407 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.60270 |
408 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92262.14776 |
409 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25949E-003 |
410 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6213.66275 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46523 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
413 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46523 |
414 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9573.50315 |
415 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5952.56674 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34454E-004 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46523 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46523 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46523 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46523 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9573.50315 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9573.50315 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
425 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46523 |
426 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46523 |
427 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9573.50315 |
428 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34454E-004 |
429 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
430 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.82778E-002 |
431 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 12653.82661 |
432 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.82778E-002 |
433 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.39333 |
434 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.82778E-002 |
435 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.82778E-002 |
436 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 328570.99940 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
438 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.25763E-002 |
439 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.50916 |
440 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.25763E-002 |
441 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3749.93483 |
442 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
443 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1437550.20307 |
444 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1437550.20000 |
445 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.25763E-002 |
446 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.82778E-002 |
447 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.39333 |
448 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.91389E-002 |
449 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4380.33545 |
450 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.91389E-002 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4380.33545 |
452 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.82778E-002 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.95427E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1386014.36578 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1392589.28500 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.89141E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.82778E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.95427E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1386014.36578 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1392589.28500 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.89141E-002 |
462 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.37695E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.65234 |
464 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.37695E-002 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3477.14328 |
466 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.37695E-002 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 57509.82268 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21235.73778 |
472 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 567185.94045 |
473 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 556188.92000 |
474 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.37695E-002 |
475 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
476 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
477 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
479 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
480 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13783 |
481 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.53938 |
482 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13783 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 33785.35068 |
484 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 54.64445 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1652273.18667 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.92889 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 206534.14833 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 54.64445 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1652273.18667 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.92889 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 206534.14833 |
492 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.15800E-002 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.15800E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15068.56 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 365695.23 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 64534.00 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6535.10 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4773.40 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8714.80 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3167.97 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 153979.99 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 101732.16 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 153981.01 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 93300.82 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19083.07 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12523.74 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19083.25 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11902.37 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 18004.95 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 67375.07 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 7557.08 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 198932.24 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 281397.64 | 188354.25 | 93043.38 | 0.67 | 72165.58 | 731.94 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2719387.62 | 1814871.13 | 904516.49 | 0.67 | 680968.37 | 6906.76 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 307472.30 | 206576.27 | 100896.04 | 0.67 | 81541.59 | 827.04 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 149740.89 | 100433.96 | 49306.93 | 0.67 | 35016.44 | 355.16 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.47 | 22.07 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.47 | 22.07 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.229 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.229 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3014013721 | 0.1871569752 | Pass | Pass | 0.1592467994 | 0.3551536194 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.8988226577E-003 | 5.4590051052E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.4874162322E-003 | 5.9038193641E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.4826666446E-002 | 6.2867636063E-002 | Pass | Pass | 0.1555229786 | 0.3587490201 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.6802342616E-002 | 1.7707311179E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.5990551191E-002 | 3.8382867417E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.0782259186E-002 | 4.5641877044E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.1887464845E-002 | 3.6324744510E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.0061074769E-002 | 1.8807115582E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.0162915879E-002 | 3.8417087703E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.9983082613E-002 | 5.0143371619E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.6478474893E-002 | 3.8006505038E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.5268045099E-002 | 0.1262257787 | Pass | Pass | 0.4269483548 | 1.1331650219 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.9575030289E-002 | 8.1557466990E-002 | Pass | Pass | 0.3076784195 | 0.7726539449 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.9766638927E-002 | 6.4931603005E-002 | Pass | Pass | 4.2980117132 | 44.4864603942 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.8771108078E-002 | 5.3761042424E-002 | Pass | Pass | 0.3759596705 | 1.4504182648 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.3407561265E-003 | 4.7507595189E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.6764517443E-003 | 5.0863638022E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.9669597005E-002 | 5.6946247067E-002 | Pass | Pass | 0.1629011355 | 0.3621897003 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.8081231757E-005 | 7.3048021562E-005 | Pass | Pass | 4.4600645534E-003 | 2.5835134141E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.9046081945E-003 | 1.0361284461E-002 | Pass | Pass | 0.1605935893 | 0.6286779368 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.0167722689E-002 | 1.9677435602E-002 | Pass | Pass | 1.2946456940E-002 | 9.1608503576E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.1068533312E-004 | 2.2128915323E-004 | Pass | Pass | 7.7390427335E-005 | 1.1033423434E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4333.64 | -42.1 | 0.00 | -5179.2 | 42224.58 | 41336.97 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.504_SHGC_NORTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.504_SHGC_EAST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.504_SHGC_WEST_0.229 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.230 | 0.253 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.230 | 0.253 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.229 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.229 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.230 | 0.253 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.865 | 0.230 | 0.253 | |||||||||||||||||
North Total or Average | 1390.74 | 2.865 | 0.230 | 0.253 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.865 | 0.230 | 0.253 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.36 | 0.0000 | Y | 10.62 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.23 | 0.0000 | Y | 6.81 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.06 | 0.0000 | Y | 10.51 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.22 | 0.0000 | Y | 6.81 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.31 | 0.0000 | Y | 106.05 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.20 | 0.0000 | Y | 68.06 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.04 | 0.0000 | Y | 104.98 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.18 | 0.0000 | Y | 68.00 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.31 | 0.0000 | Y | 10.60 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.20 | 0.0000 | Y | 6.81 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.03 | 0.0000 | Y | 10.50 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.17 | 0.0000 | Y | 6.80 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 774.90 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 41.75 | 41.75 | 104.02 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.75 | 62.75 | 11.66 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.75 | 46.80 | 233.63 | |
Exterior Lighting Total | 40855.88 | 349.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2728566.23 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1437550.20 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1392589.28 | 6.28 | 1219157.63 | 5.58 | 6.47 | 22.07 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1392589.28 | 6.28 | 1219157.63 | 5.58 | 6.47 | 22.07 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 556188.92 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1652273.19 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1652273.19 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 220524.68 | 281397.64 | 188354.25 | 93043.38 | 0.67 | - | 72165.58 | 731.94 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2159235.10 | 2719387.62 | 1814871.13 | 904516.49 | 0.67 | - | 680968.37 | 6906.76 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 237054.68 | 307472.30 | 206576.27 | 100896.04 | 0.67 | - | 81541.59 | 827.04 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 120181.96 | 149740.89 | 100433.96 | 49306.93 | 0.67 | - | 35016.44 | 355.16 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 450505.06 | 280539.33 | 169965.73 | 0.62 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9911.25 | 6164.78 | 3746.47 | 0.62 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92262.15 | 58126.40 | 34135.75 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9573.50 | 5952.57 | 3620.94 | 0.62 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 15891.53 | 15068.56 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 385983.24 | 365695.23 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 68090.67 | 64534.00 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 6894.62 | 6535.10 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5036.28 | 4773.40 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9195.50 | 8714.80 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3344.00 | 3167.97 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 162503.79 | 153979.99 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 107364.33 | 101732.16 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 162504.86 | 153981.01 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 98464.27 | 93300.82 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20140.35 | 19083.07 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13217.65 | 12523.74 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 20140.54 | 19083.25 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12561.74 | 11902.37 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 20575.73 | 18004.95 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 73237.61 | 67375.07 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 8208.18 | 7557.08 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 244195.30 | 198932.24 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 450505.06 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9911.25 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92262.15 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9573.50 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 13450.69 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6213.66 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.02 | 21658.74 | 2160.95 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 96.10 | 207666.89 | 2160.95 | 1.00 | 1.08 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.06 | 23772.72 | 2149.46 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.36 | 9097.01 | 1695.65 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.87 | 36069.92 | 1649.25 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 539.87 | 1120.11 | 1.00 | 1.62 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.60 | 5155.52 | 1120.11 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 521.10 | 1120.11 | 1.00 | 1.64 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.078278 | 12653.83 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.012576 | 3749.93 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.039139 | 4380.34 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.039139 | 4380.34 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013770 | 3477.14 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.137828 | 33785.35 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 72448.55 | 72448.55 | 26.07 | 5.365 | 5.365 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00748 | 34.82 | 0.00915 | 1.200 | 0.00 |
CORE_BOTTOM | 80375.86 | 80375.86 | 32.20 | 5.953 | 5.953 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 34.82 | 0.00915 | 1.078 | 0.00 |
CORE_MID | 769180.86 | 769180.86 | 308.15 | 56.955 | 56.955 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 34.82 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 77880.81 | 77880.81 | 31.20 | 5.821 | 5.821 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | 24.00 | 24.00 | 0.00739 | 41.90 | 0.00916 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 17459.53 | 17459.53 | 55.71 | 1.305 | 1.305 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 24.00 | 24.00 | 0.00724 | 41.52 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 13800.39 | 13800.39 | 68.33 | 1.031 | 1.031 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 24.00 | 24.00 | 0.00720 | 38.80 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17620.74 | 17620.74 | 56.22 | 1.317 | 1.317 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:20:00 | 24.00 | 24.00 | 0.00724 | 42.00 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18073.60 | 18073.60 | 89.48 | 1.351 | 1.351 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00715 | 41.16 | 0.00916 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 175366.49 | 175366.49 | 559.54 | 13.107 | 13.107 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | 24.00 | 24.00 | 0.00728 | 41.42 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 145810.16 | 145810.16 | 721.92 | 10.898 | 10.898 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:30:00 | 24.00 | 24.00 | 0.00722 | 39.04 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 175326.83 | 175326.83 | 559.40 | 13.104 | 13.104 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 24.00 | 24.00 | 0.00728 | 42.00 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 160309.32 | 160309.32 | 793.71 | 11.982 | 11.982 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00720 | 41.03 | 0.00916 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 19702.41 | 19702.41 | 62.86 | 1.473 | 1.473 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:50:00 | 24.00 | 24.00 | 0.00726 | 41.52 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15191.49 | 15191.49 | 75.21 | 1.135 | 1.135 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:50:00 | 24.00 | 24.00 | 0.00722 | 39.53 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 19655.66 | 19655.66 | 62.71 | 1.469 | 1.469 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 24.00 | 24.00 | 0.00726 | 42.00 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17420.54 | 17420.54 | 86.25 | 1.302 | 1.302 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00719 | 41.03 | 0.00916 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8176.98 | 8176.98 | 225.87 | 0.482 | 0.482 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78086.29 | 78086.29 | 2156.92 | 4.603 | 4.603 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7891.78 | 7891.78 | 217.99 | 0.465 | 0.465 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 27.00 | 27.00 | 0.00709 | 40.77 | 0.00916 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371001.37 | 371001.37 | 473.41 | 21.870 | 21.870 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.17 | 0.00914 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 24.82 | 0.00607 | 6.30 | 0.00607 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.20 | 0.00607 | 6.30 | 0.00607 | 1.078 | 0.00 | |
CORE_MID | 227226.30 | 227226.30 | 91.03 | 9.817 | 10.778 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 10.778 | 0.00 |
CORE_TOP | 47714.70 | 47714.70 | 19.12 | 2.076 | 2.076 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 4834.10 | 4834.10 | 15.42 | 0.210 | 0.210 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3530.14 | 3530.14 | 17.48 | 0.153 | 0.153 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6442.73 | 6442.73 | 20.56 | 0.281 | 0.281 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00793 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2058.38 | 2058.38 | 10.19 | 0.089 | 0.089 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 113748.48 | 113748.48 | 362.93 | 4.968 | 4.968 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 75150.00 | 75150.00 | 372.08 | 3.283 | 3.283 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 113749.24 | 113749.24 | 362.93 | 4.968 | 4.968 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 68927.78 | 68927.78 | 341.27 | 3.010 | 3.010 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14094.40 | 14094.40 | 44.97 | 0.616 | 0.616 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9249.67 | 9249.67 | 45.80 | 0.404 | 0.404 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14094.53 | 14094.53 | 44.97 | 0.616 | 0.616 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8791.11 | 8791.11 | 43.53 | 0.384 | 0.384 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | 6.30 | 0.00607 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 26.92 | 0.00700 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.60 | 0.00661 | 6.30 | 0.00607 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.76 | 0.00614 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 6.30 | 0.00607 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.02 | 10.02 | 1.81 | 1.81 | 10.0228 | 2.2876 | 10.0228 | 0.2282 | 0.3000 |
VAV_MID WITH REHEAT | 96.10 | 96.10 | 27.01 | 27.01 | 96.1000 | 27.0067 | 96.1000 | 0.2810 | 0.3000 |
VAV_TOP WITH REHEAT | 11.06 | 11.06 | 4.10 | 4.10 | 11.0598 | 4.0967 | 11.0598 | 0.3704 | 0.3000 |
CAV_BAS | 5.36 | 5.36 | 1.20 | 1.20 | 5.3649 | 5.3649 | 5.3649 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.87 | 21.87 | 0.34 | 0.34 | 21.8705 | 21.8703 | 21.8705 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.48 | 0.48 | 0.02 | 0.02 | 0.4820 | 0.4820 | 0.4820 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.60 | 4.60 | 0.16 | 0.16 | 4.6027 | 4.6027 | 4.6027 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.47 | 0.47 | 0.02 | 0.02 | 0.4652 | 0.4652 | 0.4652 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 15891.533 | 15891.533 | 1.619145 | 0.00013903 | 320.361 | 1/21 00:10:00 | 1/21 00:10:00 | 15891.53 | 15891.53 | 1.619145 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 15950.13 | 15950.13 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 385983.240 | 385983.240 | 16.175308 | 0.00337675 | 9077.808 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 385983.24 | 385983.24 | 16.175308 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 227226.30 | 0.00 | 387247.77 | 387247.77 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 68090.669 | 68090.669 | 2.076052 | 0.00059569 | 1798.700 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 68090.67 | 68090.67 | 2.076052 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 47714.70 | 0.00 | 68335.39 | 68335.39 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6894.617 | 6894.617 | 0.209982 | 0.00006032 | 182.222 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6894.62 | 6894.62 | 0.209982 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00790352 | 49.8127 | 4834.10 | 0.00 | 6920.06 | 6920.06 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5036.283 | 5036.283 | 0.153484 | 0.00004406 | 133.068 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5036.28 | 5036.28 | 0.153484 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00791529 | 49.8859 | 3530.14 | 0.00 | 5054.58 | 5054.58 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9195.497 | 9195.497 | 0.280510 | 0.00008045 | 242.853 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9195.50 | 9195.50 | 0.280510 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00793473 | 50.0068 | 6442.73 | 0.00 | 9228.14 | 9228.14 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3344.003 | 3344.003 | 0.131030 | 0.00002925 | 80.264 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3344.00 | 3344.00 | 0.131030 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00783945 | 49.4139 | 2058.38 | 0.00 | 3354.85 | 3354.85 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 162503.793 | 162503.793 | 4.968054 | 0.00142165 | 4287.427 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 162503.79 | 162503.79 | 4.968054 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00795529 | 50.1349 | 113748.48 | 0.00 | 163049.71 | 163049.71 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 107364.328 | 107364.328 | 3.282560 | 0.00093927 | 2832.563 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 107364.33 | 107364.33 | 3.282560 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00795616 | 50.1403 | 75150.00 | 0.00 | 107724.37 | 107724.37 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 162504.863 | 162504.863 | 4.968087 | 0.00142166 | 4287.455 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 162504.86 | 162504.86 | 4.968087 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00795529 | 50.1349 | 113749.24 | 0.00 | 163050.79 | 163050.79 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 98464.271 | 98464.271 | 3.009756 | 0.00086141 | 2598.029 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 98464.27 | 98464.27 | 3.009756 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794681 | 50.0821 | 68927.78 | 0.00 | 98796.44 | 98796.44 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 20140.347 | 20140.347 | 0.616053 | 0.00017620 | 531.246 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20140.35 | 20140.35 | 0.616053 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796696 | 50.2074 | 14094.40 | 0.00 | 20207.09 | 20207.09 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13217.648 | 13217.648 | 0.404318 | 0.00011563 | 348.638 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13217.65 | 13217.65 | 0.404318 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796694 | 50.2073 | 9249.67 | 0.00 | 13261.40 | 13261.40 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 20140.542 | 20140.542 | 0.616059 | 0.00017620 | 531.251 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20140.54 | 20140.54 | 0.616059 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796696 | 50.2074 | 14094.53 | 0.00 | 20207.28 | 20207.28 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12561.743 | 12561.743 | 0.384213 | 0.00010990 | 331.354 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12561.74 | 12561.74 | 0.384213 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00796245 | 50.1794 | 8791.11 | 0.00 | 12603.44 | 12603.44 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 220524.683 | -999.000 | 10.022802 | 0.00630698 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 220524.68 | 202095.97 | 10.022802 | 27.65 | 16.72 | 0.00770165 | 10.99 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 20.2588 | 24.00 | 0.00733110 | 38.5426 | 133934.67 | 0.00 | 225045.90 | 216493.21 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 20575.735 | 20575.735 | 3.006840 | 0.00018001 | 361.604 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20575.73 | 20575.73 | 3.006840 | 7.00 | 6.93 | 0.00631388 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 67.5294 | 21.43 | 0.00720384 | 44.2639 | 16865.35 | 0.00 | 21798.64 | 21798.64 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2159235.102 | -999.000 | 96.099956 | 0.06175385 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 2159235.10 | 1968045.18 | 96.099956 | 27.90 | 16.86 | 0.00775710 | 10.99 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 21.1301 | 24.00 | 0.00736935 | 38.7415 | 1253184.69 | 0.00 | 2202801.50 | 2104873.78 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 73237.607 | 73237.607 | 28.829987 | 0.00064071 | 1322.863 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 73237.61 | 73237.61 | 28.829987 | 10.65 | 9.00 | 0.00663618 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 70.4336 | 20.23 | 0.00796993 | 52.6522 | 309872.88 | 0.00 | 81570.71 | 81570.71 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 237054.676 | -999.000 | 11.059836 | 0.00677973 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 237054.68 | 218061.92 | 11.059836 | 27.29 | 16.56 | 0.00765797 | 11.00 | 9.55 | 0.00700000 | 41.90 | 0.00915774 | 22.24 | 18.3592 | 24.00 | 0.00731971 | 38.4836 | 147616.68 | 0.00 | 242079.67 | 234128.93 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 8208.178 | 8208.178 | 3.317951 | 0.00007181 | 148.326 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8208.18 | 8208.18 | 3.317951 | 10.70 | 9.20 | 0.00679566 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 61.1974 | 19.48 | 0.00791021 | 54.7582 | 39144.30 | 0.00 | 9149.37 | 9149.37 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 120181.965 | -999.000 | 5.364898 | 0.00343719 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 120181.96 | 107553.00 | 5.364898 | 27.84 | 16.97 | 0.00791249 | 11.38 | 9.72 | 0.00700000 | 39.77 | 0.00915417 | 21.63 | 22.3705 | 24.00 | 0.00751199 | 39.4825 | 65841.27 | 0.00 | 122582.34 | 116032.63 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 244195.305 | 244195.305 | 5.364898 | 0.00213633 | 5562.765 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 244195.30 | 244195.30 | 5.364898 | 1.41 | 1.41 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 22.3705 | 24.82 | 0.00607234 | 30.4449 | 0.00 | 0.00 | 210522.62 | 210522.62 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 450505.058 | 280539.326 | 21.870538 | 0.01103284 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | 404648.07 | 400931.02 | -999.0 | 28.66 | 16.55 | 0.00707502 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | -999.0000 | 27.00 | 0.00704224 | 30.9984 | 370535.56 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9911.249 | 6164.781 | 0.481982 | 0.00024273 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 8900.44 | 8727.65 | -999.0 | 28.43 | 16.54 | 0.00715843 | 12.80 | 10.34 | 0.00700000 | 41.03 | 0.00915628 | 21.99 | -999.0000 | 27.00 | 0.00709012 | 31.2049 | 8020.69 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92262.148 | 58126.400 | 4.602702 | 0.00225949 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 82453.50 | 81700.44 | -999.0 | 28.15 | 16.37 | 0.00707275 | 12.80 | 10.34 | 0.00700000 | 32.36 | 0.00914193 | 19.41 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 76477.78 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9573.503 | 5952.567 | 0.465226 | 0.00023445 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | 8598.31 | 8428.80 | -999.0 | 28.44 | 16.54 | 0.00716100 | 12.80 | 10.34 | 0.00700000 | 41.03 | 0.00915628 | 21.99 | -999.0000 | 27.00 | 0.00709161 | 31.2114 | 7890.40 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 450505.058 | 450505.058 | 21.870538 | 0.01103284 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 450505.06 | 450505.06 | 21.870538 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5473 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9911.249 | 9911.249 | 0.481982 | 0.00024273 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9911.25 | 9911.25 | 0.481982 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2433 | 26.92 | 0.00700000 | 30.9571 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92262.148 | 92262.148 | 4.602702 | 0.00225949 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 92262.15 | 92262.15 | 4.602702 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3963 | 24.60 | 0.00661303 | 33.5823 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9573.503 | 9573.503 | 0.465226 | 0.00023445 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9573.50 | 9573.50 | 0.465226 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3602 | 23.76 | 0.00614020 | 32.8135 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 13450.69 | 13450.69 | 21.870538 | 0.10 | 0.10 | 0.00698565 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5473 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.481982 | 0.20 | 0.20 | 0.00696991 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2433 | 26.92 | 0.00700000 | 30.9571 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6213.66 | 6213.66 | 4.602702 | 0.21 | 0.21 | 0.00659466 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3963 | 24.60 | 0.00661303 | 33.5823 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.465226 | 0.21 | 0.21 | 0.00613792 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3602 | 23.76 | 0.00614020 | 32.8135 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 15891.533 | 15891.533 | 1.619145 | 0.00013903 | 320.361 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 1.0837 | 1.105459 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 15891.53 | 15891.53 | 1.0000 | 1.90052941 | 1.619145 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.13901189 | 60.00 | 32.22 | 27.78 | 0.000 | 15891.53 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 15950.13 | 15950.13 | 1.90052941 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 385983.240 | 385983.240 | 16.175308 | 0.00337675 | 9077.808 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 26.3204 | 26.850070 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 385983.24 | 385983.24 | 1.0000 | 18.98634131 | 16.175308 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 3.37640530 | 60.00 | 32.22 | 27.78 | 0.000 | 385983.24 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.88 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 227226.30 | 0.00 | 387247.77 | 387247.77 | 18.98634131 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.80 | 18.96 | 0.00800000 | 53456.0 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 68090.669 | 68090.669 | 2.076052 | 0.00059569 | 1798.700 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 4.6431 | 4.736577 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 68090.67 | 68090.67 | 1.0000 | 2.43683973 | 2.076052 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.59562611 | 60.00 | 32.22 | 27.78 | 0.000 | 68090.67 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 47714.70 | 0.00 | 68335.39 | 68335.39 | 2.43683973 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61102.5 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6894.617 | 6894.617 | 0.209982 | 0.00006032 | 182.222 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 0.4701 | 0.479609 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6894.62 | 6894.62 | 1.0000 | 0.24647386 | 0.209982 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.06031096 | 60.00 | 32.22 | 27.78 | 0.000 | 6894.62 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00790352 | 21.00 | 0.00790352 | 49.8127 | 4834.10 | 0.00 | 6920.06 | 6920.06 | 0.24647386 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.33 | 21.28 | 0.00800000 | 61136.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5036.283 | 5036.283 | 0.153484 | 0.00004406 | 133.068 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 0.3434 | 0.350338 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5036.28 | 5036.28 | 1.0000 | 0.18015705 | 0.153484 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.04405511 | 60.00 | 32.22 | 27.78 | 0.000 | 5036.28 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00791529 | 21.00 | 0.00791529 | 49.8859 | 3530.14 | 0.00 | 5054.58 | 5054.58 | 0.18015705 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.31 | 21.28 | 0.00800000 | 61116.4 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9195.497 | 9195.497 | 0.280510 | 0.00008045 | 242.853 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 0.6270 | 0.639664 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9195.50 | 9195.50 | 1.0000 | 0.32925859 | 0.280510 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08043802 | 60.00 | 32.22 | 27.78 | 0.000 | 9195.50 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.92 | 0.00793473 | 21.00 | 0.00793473 | 50.0068 | 6442.73 | 0.00 | 9228.14 | 9228.14 | 0.32925859 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.29 | 21.27 | 0.00800000 | 61086.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3344.003 | 3344.003 | 0.131030 | 0.00002925 | 80.264 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 0.2280 | 0.232618 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3344.00 | 3344.00 | 1.0000 | 0.15380056 | 0.131030 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.02925181 | 60.00 | 32.22 | 27.78 | 0.000 | 3344.00 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.82 | 0.00783945 | 21.00 | 0.00783945 | 49.4139 | 2058.38 | 0.00 | 3354.85 | 3354.85 | 0.15380056 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.19 | 19.40 | 0.00800000 | 54872.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 162503.793 | 162503.793 | 4.968054 | 0.00142165 | 4287.427 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 11.0812 | 11.304217 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 162503.79 | 162503.79 | 1.0000 | 5.83142984 | 4.968054 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.42150905 | 60.00 | 32.22 | 27.78 | 0.000 | 162503.79 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00795529 | 21.00 | 0.00795529 | 50.1349 | 113748.48 | 0.00 | 163049.71 | 163049.71 | 5.83142984 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61020.3 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 107364.328 | 107364.328 | 3.282560 | 0.00093927 | 2832.563 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 7.3212 | 7.468562 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 107364.33 | 107364.33 | 1.0000 | 3.85302131 | 3.282560 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.93917416 | 60.00 | 32.22 | 27.78 | 0.000 | 107364.33 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00795616 | 21.00 | 0.00795616 | 50.1403 | 75150.00 | 0.00 | 107724.37 | 107724.37 | 3.85302131 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61018.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 162504.863 | 162504.863 | 4.968087 | 0.00142166 | 4287.455 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 11.0813 | 11.304291 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 162504.86 | 162504.86 | 1.0000 | 5.83146798 | 4.968087 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.42151841 | 60.00 | 32.22 | 27.78 | 0.000 | 162504.86 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00795529 | 21.00 | 0.00795529 | 50.1349 | 113749.24 | 0.00 | 163050.79 | 163050.79 | 5.83146798 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61020.3 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 98464.271 | 98464.271 | 3.009756 | 0.00086141 | 2598.029 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 6.7143 | 6.849449 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 98464.27 | 98464.27 | 1.0000 | 3.53280786 | 3.009756 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.86132053 | 60.00 | 32.22 | 27.78 | 0.000 | 98464.27 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00794681 | 21.00 | 0.00794681 | 50.0821 | 68927.78 | 0.00 | 98796.44 | 98796.44 | 3.53280786 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61025.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20140.347 | 20140.347 | 0.616053 | 0.00017620 | 531.246 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 1.3734 | 1.401019 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20140.35 | 20140.35 | 1.0000 | 0.72311415 | 0.616053 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.17617857 | 60.00 | 32.22 | 27.78 | 0.000 | 20140.35 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00796696 | 21.00 | 0.00796696 | 50.2074 | 14094.40 | 0.00 | 20207.09 | 20207.09 | 0.72311415 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13217.648 | 13217.648 | 0.404318 | 0.00011563 | 348.638 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 0.9013 | 0.919456 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13217.65 | 13217.65 | 1.0000 | 0.47458282 | 0.404318 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.11562195 | 60.00 | 32.22 | 27.78 | 0.000 | 13217.65 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00796694 | 21.00 | 0.00796694 | 50.2073 | 9249.67 | 0.00 | 13261.40 | 13261.40 | 0.47458282 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61003.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20140.542 | 20140.542 | 0.616059 | 0.00017620 | 531.251 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 1.3734 | 1.401032 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20140.54 | 20140.54 | 1.0000 | 0.72312113 | 0.616059 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.17618028 | 60.00 | 32.22 | 27.78 | 0.000 | 20140.54 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00796696 | 21.00 | 0.00796696 | 50.2074 | 14094.53 | 0.00 | 20207.28 | 20207.28 | 0.72312113 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12561.743 | 12561.743 | 0.384213 | 0.00010990 | 331.354 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 0.8566 | 0.873830 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12561.74 | 12561.74 | 1.0000 | 0.45098397 | 0.384213 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10988440 | 60.00 | 32.22 | 27.78 | 0.000 | 12561.74 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00796245 | 21.00 | 0.00796245 | 50.1794 | 8791.11 | 0.00 | 12603.44 | 12603.44 | 0.45098397 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61006.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 220524.683 | -999.000 | 10.022802 | 0.00630698 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1570 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.022802 | 11.76461872 | 4197.9300 | 999.8980 | 78.26976615 | 15.00 | 6.67 | 8.33 | 2736996.43 | 8.0572 | 8.057178 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | Sensible | 220524.68 | 202095.97 | 1.0000 | 11.76461872 | 10.022802 | 27.65 | 16.72 | 0.00770165 | 47441.2 | 10.99 | 9.55 | 0.00700000 | 28696.4 | 6.30633464 | 6.67 | 15.00 | 8.33 | 21658.740 | 198865.94 | 42.00 | 0.00915790 | 22.26 | 2.03050000 | 20.2588 | 24.00 | 0.00733110 | 24.00 | 0.00733110 | 38.5426 | 133934.67 | 0.00 | 225045.90 | 216493.21 | 11.76461872 | 27.65 | 16.99 | 0.00770165 | 47441.2 | 9.59 | 9.58 | 0.00741303 | 28312.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20575.735 | 20575.735 | 3.006840 | 0.00018001 | 361.604 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.022802 | 11.76461872 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 1.4031 | 1.431305 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20575.73 | 20575.73 | 1.0000 | 3.52938562 | 3.006840 | 7.00 | 6.93 | 0.00631388 | 22905.0 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.17998714 | 60.00 | 32.22 | 27.78 | 0.000 | 20575.73 | 6.30 | 0.00607234 | 6.30 | 2.03050000 | 67.5294 | 8.45 | 0.00681622 | 21.43 | 0.00720384 | 44.2639 | 16865.35 | 0.00 | 21798.64 | 21798.64 | 3.52938562 | 2.80 | 2.80 | 0.00631388 | 18637.1 | 8.88 | 8.02 | 0.00631388 | 24813.4 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2159235.102 | -999.000 | 96.099956 | 0.06175385 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2601 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 96.099956 | 112.80073152 | 4197.9300 | 999.8980 | 78.26976615 | 15.00 | 6.67 | 8.33 | 2736996.43 | 78.8907 | 78.890680 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 2159235.10 | 1968045.18 | 1.0000 | 112.80073152 | 96.099956 | 27.90 | 16.86 | 0.00775710 | 47838.7 | 10.99 | 9.55 | 0.00700000 | 28696.6 | 61.74755105 | 6.67 | 15.00 | 8.33 | 207666.888 | 1951568.21 | 42.00 | 0.00915790 | 22.26 | 20.30600000 | 21.1301 | 24.00 | 0.00736935 | 24.00 | 0.00736935 | 38.7415 | 1253184.69 | 0.00 | 2202801.50 | 2104873.78 | 112.80073152 | 27.90 | 17.12 | 0.00775710 | 47838.7 | 9.59 | 9.58 | 0.00741243 | 28310.4 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 73237.607 | 73237.607 | 28.829987 | 0.00064071 | 1322.863 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 96.099956 | 112.80073152 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 4.9941 | 5.094612 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 73237.61 | 73237.61 | 1.0000 | 33.84021945 | 28.829987 | 10.65 | 9.00 | 0.00663618 | 27425.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.64064917 | 60.00 | 32.22 | 27.78 | 0.000 | 73237.61 | 6.30 | 0.00607234 | 6.30 | 20.30600000 | 70.4336 | 21.00 | 0.00797935 | 20.23 | 0.00796993 | 52.6522 | 309872.88 | 0.00 | 81570.71 | 81570.71 | 33.84021945 | 2.80 | 2.80 | 0.00663618 | 19444.8 | 5.17 | 5.17 | 0.00663618 | 21855.2 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 237054.676 | -999.000 | 11.059836 | 0.00677973 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.0758 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.059836 | 12.98187420 | 4197.9300 | 999.8980 | 78.26976615 | 15.00 | 6.67 | 8.33 | 2736996.43 | 8.6611 | 8.661125 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | Sensible | 237054.68 | 218061.92 | 1.0000 | 12.98187420 | 11.059836 | 27.29 | 16.56 | 0.00765797 | 46966.5 | 11.00 | 9.55 | 0.00700000 | 28706.1 | 6.77904211 | 6.67 | 15.00 | 8.33 | 23772.725 | 213281.95 | 41.90 | 0.00915774 | 22.24 | 2.03050000 | 18.3592 | 24.00 | 0.00731971 | 24.00 | 0.00731971 | 38.4836 | 147616.68 | 0.00 | 242079.67 | 234128.93 | 12.98187420 | 27.29 | 16.83 | 0.00765797 | 46966.5 | 9.60 | 9.59 | 0.00741482 | 28319.0 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 8208.178 | 8208.178 | 3.317951 | 0.00007181 | 148.326 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.059836 | 12.98187420 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 0.5597 | 0.570984 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8208.18 | 8208.18 | 1.0000 | 3.89456226 | 3.317951 | 10.70 | 9.20 | 0.00679566 | 27885.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.07180139 | 60.00 | 32.22 | 27.78 | 0.000 | 8208.18 | 6.30 | 0.00607234 | 6.30 | 2.03050000 | 61.1974 | 17.65 | 0.00793645 | 19.48 | 0.00791021 | 54.7582 | 39144.30 | 0.00 | 9149.37 | 9149.37 | 3.89456226 | 2.80 | 2.80 | 0.00679566 | 19844.5 | 5.11 | 5.11 | 0.00679566 | 22193.7 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 120181.965 | -999.000 | 5.364898 | 0.00343719 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5489 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 5.364898 | 6.29723928 | 4197.9300 | 999.8980 | 78.26976615 | 15.00 | 6.67 | 8.33 | 2736996.43 | 4.3910 | 4.391017 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 120181.96 | 107553.00 | 1.0000 | 6.29723928 | 5.364898 | 27.84 | 16.97 | 0.00791249 | 48177.8 | 11.38 | 9.72 | 0.00700000 | 29092.9 | 3.43683835 | 6.67 | 15.00 | 8.33 | 9097.013 | 111084.95 | 39.77 | 0.00915417 | 21.63 | 1.20015641 | 22.3705 | 24.00 | 0.00751199 | 24.00 | 0.00751199 | 39.4825 | 65841.27 | 0.00 | 122582.34 | 116032.63 | 6.29723928 | 27.84 | 17.23 | 0.00791249 | 48177.8 | 9.77 | 9.76 | 0.00749961 | 28711.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 244195.305 | 244195.305 | 5.364898 | 0.00213633 | 5562.765 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 5.364898 | 6.29723928 | 4197.9300 | 999.8980 | 12.57503338 | 54.44 | 82.22 | 27.78 | 1466481.47 | 16.6518 | 16.986906 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 244195.30 | 244195.30 | 1.0000 | 6.29723928 | 5.364898 | 1.41 | 1.41 | 0.00607234 | 16618.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.13610912 | 60.00 | 32.22 | 27.78 | 0.000 | 244195.30 | 6.30 | 0.00607234 | 6.30 | 1.20015641 | 22.3705 | 0.00 | 0.00607234 | 24.82 | 0.00607234 | 30.4449 | 0.00 | 0.00 | 210522.62 | 210522.62 | 6.29723928 | 12.80 | 9.56 | 0.00607234 | 28193.0 | 45.70 | 21.47 | 0.00607234 | 61623.9 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 450505.058 | 280539.326 | 21.870538 | 0.01103284 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9921 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | Sensible | 404648.07 | 400931.02 | 0.8982 | -999.0 | -999.0 | 28.66 | 16.55 | 0.00707502 | 46869.9 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 404648.07 | 42.00 | 0.00915790 | 22.26 | 0.33839277 | -999.0000 | 27.00 | 0.00704224 | 27.00 | 0.00704224 | 30.9984 | 370535.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9911.249 | 6164.781 | 0.481982 | 0.00024273 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.1472 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 8900.44 | 8727.65 | 0.8980 | -999.0 | -999.0 | 28.43 | 16.54 | 0.00715843 | 46853.2 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8900.44 | 41.03 | 0.00915628 | 21.99 | 0.01563234 | -999.0000 | 27.00 | 0.00709012 | 27.00 | 0.00709012 | 31.2049 | 8020.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92262.148 | 58126.400 | 4.602702 | 0.00225949 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9879 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 82453.50 | 81700.44 | 0.8937 | -999.0 | -999.0 | 28.15 | 16.37 | 0.00707275 | 46348.4 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82453.50 | 32.36 | 0.00914193 | 19.41 | 0.15632344 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 76477.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9573.503 | 5952.567 | 0.465226 | 0.00023445 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.1519 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:50:00 | Sensible | 8598.31 | 8428.80 | 0.8981 | -999.0 | -999.0 | 28.44 | 16.54 | 0.00716100 | 46867.6 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8598.31 | 41.03 | 0.00915628 | 21.99 | 0.01563234 | -999.0000 | 27.00 | 0.00709161 | 27.00 | 0.00709161 | 31.2114 | 7890.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 450505.058 | 450505.058 | 21.870538 | 0.01103284 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 450505.06 | 450505.06 | 1.0000 | 25.67131898 | 21.870538 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 450505.06 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.5473 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9911.249 | 9911.249 | 0.481982 | 0.00024273 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9911.25 | 9911.25 | 1.0000 | 0.56574397 | 0.481982 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9911.25 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.2433 | 0.00 | 0.00700000 | 26.92 | 0.00700000 | 30.9571 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92262.148 | 92262.148 | 4.602702 | 0.00225949 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 92262.15 | 92262.15 | 1.0000 | 5.40258418 | 4.602702 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92262.15 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.3963 | 0.00 | 0.00661303 | 24.60 | 0.00661303 | 33.5823 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9573.503 | 9573.503 | 0.465226 | 0.00023445 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9573.50 | 9573.50 | 1.0000 | 0.54607537 | 0.465226 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9573.50 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.3602 | 0.00 | 0.00614020 | 23.76 | 0.00614020 | 32.8135 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.870538 | 25.67131898 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 13450.69 | 13450.69 | 1.0000 | 25.67131898 | 21.870538 | 0.10 | 0.10 | 0.00698565 | 17569.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13450.69 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.5473 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.481982 | 0.56574397 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.56574397 | 0.481982 | 0.20 | 0.20 | 0.00696991 | 17639.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.2433 | 0.00 | 0.00700000 | 26.92 | 0.00700000 | 30.9571 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.602702 | 5.40258418 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6213.66 | 6213.66 | 1.0000 | 5.40258418 | 4.602702 | 0.21 | 0.21 | 0.00659466 | 16710.5 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6213.66 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.3963 | 0.00 | 0.00661303 | 24.60 | 0.00661303 | 33.5823 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.465226 | 0.54607537 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.54607537 | 0.465226 | 0.21 | 0.21 | 0.00613792 | 15565.7 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.3602 | 0.00 | 0.00614020 | 23.76 | 0.00614020 | 32.8135 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5297.33 | 1575.83 | 1574.83 |
CORE_BOTTOM | 5294.67 | 27.50 | 17.00 |
CORE_MID | 4548.00 | 484.50 | 27.00 |
CORE_TOP | 4240.50 | 1120.00 | 49.00 |
PERIMETER_BOT_ZN_3 | 4433.83 | 1147.33 | 274.67 |
PERIMETER_BOT_ZN_2 | 4680.50 | 1007.83 | 373.67 |
PERIMETER_BOT_ZN_1 | 5166.00 | 829.50 | 447.17 |
PERIMETER_BOT_ZN_4 | 5355.83 | 957.83 | 783.83 |
PERIMETER_MID_ZN_3 | 3979.17 | 1939.17 | 395.17 |
PERIMETER_MID_ZN_2 | 3651.67 | 1454.33 | 492.17 |
PERIMETER_MID_ZN_1 | 4952.50 | 1082.33 | 511.17 |
PERIMETER_MID_ZN_4 | 4451.33 | 1586.50 | 560.50 |
PERIMETER_TOP_ZN_3 | 4057.17 | 2162.00 | 616.50 |
PERIMETER_TOP_ZN_2 | 4345.00 | 1820.33 | 621.33 |
PERIMETER_TOP_ZN_1 | 4800.67 | 1348.67 | 604.33 |
PERIMETER_TOP_ZN_4 | 4404.67 | 1827.67 | 677.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1473.50 | 1473.50 |
DATACENTER_MID_ZN_6 | 5935.50 | 578.67 | 578.67 |
DATACENTER_TOP_ZN_6 | 5884.17 | 763.50 | 736.67 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 85.17 | 0.00 | 7.67 |
CORE_BOTTOM | 0.00 | 10.83 | 0.00 | 0.67 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.67 | 2.17 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 123.83 | 0.00 | 47.50 |
PERIMETER_BOT_ZN_2 | 0.00 | 152.67 | 0.00 | 78.67 |
PERIMETER_BOT_ZN_1 | 0.00 | 194.33 | 0.00 | 97.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 469.33 | 0.00 | 155.00 |
PERIMETER_MID_ZN_3 | 0.17 | 101.83 | 0.00 | 40.50 |
PERIMETER_MID_ZN_2 | 0.17 | 172.00 | 0.00 | 80.00 |
PERIMETER_MID_ZN_1 | 0.00 | 175.17 | 0.00 | 92.17 |
PERIMETER_MID_ZN_4 | 0.00 | 253.17 | 0.00 | 82.50 |
PERIMETER_TOP_ZN_3 | 2.17 | 136.33 | 0.00 | 50.67 |
PERIMETER_TOP_ZN_2 | 1.33 | 203.00 | 0.00 | 85.00 |
PERIMETER_TOP_ZN_1 | 0.50 | 197.17 | 0.00 | 89.50 |
PERIMETER_TOP_ZN_4 | 0.50 | 266.00 | 0.00 | 87.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 478.17 | 0.00 | 380.17 |
DATACENTER_MID_ZN_6 | 0.00 | 564.00 | 0.00 | 462.50 |
DATACENTER_TOP_ZN_6 | 0.00 | 356.33 | 0.00 | 299.50 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1293.83 | 0.00 | 925.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.33 | 1896.33 | 0.00 | 1163.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.50 | 149.60 | 6779.02 | 0.533 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.23 | 134.35 | 6849.35 | 0.493 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.23 | 134.35 | 6849.35 | 0.468 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.23 | 134.35 | 6849.35 | 0.454 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.93 | 16.87 | 860.00 | 0.604 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.47 | 10.87 | 554.22 | 0.727 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.93 | 16.87 | 860.02 | 0.845 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.47 | 10.87 | 554.22 | 1.102 | 0.017 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.93 | 16.87 | 860.00 | 0.645 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.90 | 10.87 | 554.22 | 0.820 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.93 | 16.87 | 860.02 | 0.974 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.47 | 10.87 | 554.22 | 0.907 | 0.041 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.93 | 16.87 | 860.00 | 0.630 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.47 | 10.87 | 554.22 | 0.826 | 0.051 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.93 | 16.87 | 860.02 | 0.932 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.47 | 10.87 | 554.22 | 0.863 | 0.051 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.34 | 42.18 | 1911.37 | 0.665 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.50 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.23 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.23 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.23 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.93 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.47 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.93 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.47 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.93 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.90 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.93 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.47 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.93 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.47 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.93 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.47 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.34 | 42.18 | 1911.37 | 0.613 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.50 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.23 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.23 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.23 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.93 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.47 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.93 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.47 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.93 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.90 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.93 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.47 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.93 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.47 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.93 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.47 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.34 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1019.15 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 23414307.26 | 0.00 | 23414307.26 | 0.00 | 23414307.26 | 37848132.68 | 3340.73 | 5419.27 | 0.00 | 618.93 |
CORE_BOTTOM | 24161473.57 | 0.00 | 24161473.57 | 0.00 | 24161473.57 | 33990283.35 | 6757.03 | 765.18 | 1237.79 | 1275.47 |
CORE_MID | 0.22E+09 | 0.00 | 0.22E+09 | 0.00 | 0.22E+09 | 0.34E+09 | 6711.34 | 1027.80 | 1020.86 | 908.22 |
CORE_TOP | 21173741.67 | 0.00 | 21173741.67 | 0.00 | 21173741.67 | 33990283.35 | 6871.55 | 1238.39 | 650.06 | 899.01 |
PERIMETER_BOT_ZN_3 | 3630960.78 | 0.00 | 3630960.78 | 135485.55 | 3766446.33 | 4267819.30 | 4953.42 | 816.20 | 2990.38 | 1275.47 |
PERIMETER_BOT_ZN_2 | 2731582.85 | 0.00 | 2731582.85 | 90323.64 | 2821906.49 | 2750345.05 | 4257.08 | 778.92 | 3724.00 | 1275.47 |
PERIMETER_BOT_ZN_1 | 4853229.38 | 0.00 | 4853229.38 | 135485.55 | 4988714.93 | 4267912.63 | 3596.89 | 575.48 | 4587.63 | 1275.47 |
PERIMETER_BOT_ZN_4 | 4246667.19 | 0.00 | 4246667.19 | 90323.64 | 4336990.83 | 2750345.05 | 2551.32 | 663.54 | 5545.13 | 1275.47 |
PERIMETER_MID_ZN_3 | 36604107.52 | 0.00 | 36604107.52 | 317743.67 | 36921851.19 | 42678193.03 | 4778.80 | 1034.34 | 2946.86 | 908.22 |
PERIMETER_MID_ZN_2 | 29338245.18 | 0.00 | 29338245.18 | 211828.97 | 29550074.14 | 27503450.52 | 3988.29 | 936.21 | 3835.50 | 1744.22 |
PERIMETER_MID_ZN_1 | 53185160.44 | 0.00 | 53185160.44 | 317743.67 | 53502904.11 | 42679126.28 | 3327.46 | 920.48 | 4512.06 | 908.22 |
PERIMETER_MID_ZN_4 | 33024113.77 | 0.00 | 33024113.77 | 211828.97 | 33235942.74 | 27503450.52 | 3725.44 | 808.54 | 4226.02 | 908.22 |
PERIMETER_TOP_ZN_3 | 3607689.65 | 0.00 | 3607689.65 | 394502.81 | 4002192.46 | 4267819.30 | 4426.97 | 1208.61 | 3124.42 | 899.01 |
PERIMETER_TOP_ZN_2 | 2974323.85 | 0.00 | 2974323.85 | 263001.69 | 3237325.55 | 2750345.05 | 3637.16 | 1171.72 | 3951.12 | 899.01 |
PERIMETER_TOP_ZN_1 | 5137134.73 | 0.00 | 5137134.73 | 394502.81 | 5531637.53 | 4267912.63 | 3201.96 | 1120.30 | 4437.74 | 899.01 |
PERIMETER_TOP_ZN_4 | 3177932.88 | 0.00 | 3177932.88 | 263001.69 | 3440934.57 | 2750345.05 | 3631.96 | 949.13 | 4178.91 | 899.01 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.39E+10 | 0.00 | 0.39E+10 | 12358080.11 | 0.39E+10 | 0.50E+10 | 8700.86 | 8760.00 | 6138.70 | 3653.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9694 | 0.0000 | 0.9694 | 0.0000 | 0.9694 | 1.2002 | 1142.66 | 4800.34 | 0.00 |
CORE_BOTTOM | 0.9070 | 0.0000 | 0.9070 | 0.0000 | 0.9070 | 1.0778 | 4457.21 | 277.19 | 1208.60 |
CORE_MID | 8.6221 | 0.0000 | 8.6221 | 0.0000 | 8.6221 | 10.7782 | 4327.86 | 601.37 | 1013.77 |
CORE_TOP | 0.8356 | 0.0000 | 0.8356 | 0.0000 | 0.8356 | 1.0778 | 4511.05 | 797.49 | 634.46 |
PERIMETER_BOT_ZN_3 | 0.1392 | 0.0000 | 0.1392 | 0.0039 | 0.1431 | 0.1353 | 2823.03 | 295.71 | 2824.26 |
PERIMETER_BOT_ZN_2 | 0.1080 | 0.0000 | 0.1080 | 0.0026 | 0.1106 | 0.0872 | 2077.33 | 296.95 | 3568.72 |
PERIMETER_BOT_ZN_1 | 0.1952 | 0.0000 | 0.1952 | 0.0039 | 0.1991 | 0.1353 | 1362.37 | 209.37 | 4371.26 |
PERIMETER_BOT_ZN_4 | 0.1636 | 0.0000 | 0.1636 | 0.0026 | 0.1662 | 0.0872 | 919.08 | 226.41 | 4797.51 |
PERIMETER_MID_ZN_3 | 1.4867 | 0.0000 | 1.4867 | 0.0091 | 1.4958 | 1.3533 | 2524.23 | 599.78 | 2819.00 |
PERIMETER_MID_ZN_2 | 1.2171 | 0.0000 | 1.2171 | 0.0062 | 1.2234 | 0.8721 | 1456.75 | 557.35 | 3019.90 |
PERIMETER_MID_ZN_1 | 2.2489 | 0.0000 | 2.2489 | 0.0091 | 2.2580 | 1.3533 | 1128.62 | 491.31 | 4323.08 |
PERIMETER_MID_ZN_4 | 1.3468 | 0.0000 | 1.3468 | 0.0060 | 1.3528 | 0.8721 | 1553.16 | 546.60 | 3843.24 |
PERIMETER_TOP_ZN_3 | 0.1452 | 0.0000 | 0.1452 | 0.0113 | 0.1565 | 0.1353 | 2248.79 | 765.04 | 2929.17 |
PERIMETER_TOP_ZN_2 | 0.1227 | 0.0000 | 0.1227 | 0.0075 | 0.1302 | 0.0872 | 1432.50 | 815.91 | 3694.59 |
PERIMETER_TOP_ZN_1 | 0.2153 | 0.0000 | 0.2153 | 0.0113 | 0.2266 | 0.1353 | 1020.46 | 733.69 | 4188.86 |
PERIMETER_TOP_ZN_4 | 0.1282 | 0.0000 | 0.1282 | 0.0075 | 0.1357 | 0.0872 | 1414.51 | 762.33 | 3766.17 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 155.0787 | 0.0000 | 155.0787 | 0.3545 | 155.4332 | 158.4706 | 5899.28 | 5943.00 | 5202.16 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 54592753.35 | 0.00 | 54592753.35 | 48026705.38 | 2258.07 | 3.73 | 6498.19 | 1275.47 |
VAV_MID WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.48E+09 | 2745.75 | 2.17 | 6012.08 | 908.22 |
VAV_TOP WITH REHEAT | 49697382.51 | 0.00 | 49697382.51 | 48026705.38 | 2779.55 | 2.49 | 5977.96 | 899.01 |
CAV_BAS | 32259584.12 | 0.00 | 32259584.12 | 37848132.68 | 3340.73 | 0.00 | 5419.27 | 618.93 |
AIRLOOP DATACENTER BASEMENT | 14702971.99 | 0.00 | 14702971.99 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 6792163.95 | 0.00 | 6792163.95 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.0846 | 0.0000 | 2.0846 | 1.5229 | 683.04 | 2.36 | 5257.60 |
VAV_MID WITH REHEAT | 20.5567 | 0.0000 | 20.5567 | 15.2292 | 814.91 | 1.25 | 5126.84 |
VAV_TOP WITH REHEAT | 1.9937 | 0.0000 | 1.9937 | 1.5229 | 836.64 | 1.51 | 5104.85 |
CAV_BAS | 1.3356 | 0.0000 | 1.3356 | 1.2002 | 1142.66 | 0.00 | 4800.34 |
AIRLOOP DATACENTER BASEMENT | 0.4662 | 0.0000 | 0.4662 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2154 | 0.0000 | 0.2154 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 646.52 | 0.00 | 0.00 | 0.00 | 0.00 | 5923.60 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 752.51 | 0.00 | 0.00 | 0.00 | 0.00 | 5310.57 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 414.22 | 0.00 | 0.00 | 0.00 | 0.00 | 5614.92 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5419.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.5840 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3107 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 26.4422 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 23.2726 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.5391 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.2933 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6537 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4662 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1515 |
Defaulted Fields | 1183 |
Fields with Defaults | 3871 |
Autosized Fields | 333 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31338.71 | 345017.22 | 01-JAN-04:00 | 2026463.93 | 07-AUG-15:20 |
Electricity:Building | 17135.85 | 216479.19 | 21-MAY-17:20 | 1015041.04 | 29-DEC-17:00 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17135.85 | 216479.19 | 21-MAY-17:20 | 1015041.04 | 29-DEC-17:00 |
InteriorLights:Electricity | 2459.46 | 9223.03 | 21-MAY-17:20 | 239082.52 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2459.46 | 9223.03 | 21-MAY-17:20 | 239082.52 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 2459.46 | 9223.03 | 21-MAY-17:20 | 239082.52 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2459.46 | 9223.03 | 21-MAY-17:20 | 239082.52 | 11-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 46.99 | 603.11 | 12-MAR-17:10 | 3626.39 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.62 | 43.94 | 01-JAN-09:20 | 1465.83 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.62 | 43.94 | 01-JAN-09:20 | 1465.83 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.25 | 388.67 | 23-APR-17:10 | 2334.01 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.81 | 28.32 | 01-JAN-07:50 | 941.67 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.81 | 28.32 | 01-JAN-07:50 | 941.67 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 46.87 | 603.12 | 12-MAR-17:10 | 3618.21 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.51 | 43.94 | 01-JAN-08:00 | 1457.63 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.51 | 43.94 | 01-JAN-08:00 | 1457.63 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.25 | 388.67 | 12-MAR-17:10 | 2341.98 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.81 | 28.32 | 01-JAN-09:20 | 949.65 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.81 | 28.32 | 01-JAN-09:20 | 949.65 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 469.71 | 6031.15 | 12-MAR-17:10 | 36241.40 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 106.05 | 439.44 | 01-JAN-09:10 | 14635.89 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 106.05 | 439.44 | 01-JAN-09:10 | 14635.89 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 302.41 | 3886.70 | 23-APR-17:10 | 23306.76 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.06 | 283.19 | 01-JAN-07:50 | 9383.34 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 68.06 | 283.19 | 01-JAN-07:50 | 9383.34 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 468.64 | 6031.24 | 12-MAR-17:10 | 36159.18 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.98 | 439.45 | 01-JAN-08:00 | 14553.33 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.98 | 439.45 | 01-JAN-08:00 | 14553.33 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 302.35 | 3886.68 | 12-MAR-17:10 | 23387.96 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 68.00 | 283.19 | 01-JAN-09:10 | 9464.63 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 68.00 | 283.19 | 01-JAN-09:10 | 9464.63 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 46.97 | 603.11 | 12-MAR-17:10 | 3623.73 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.60 | 43.94 | 01-JAN-09:10 | 1463.18 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.60 | 43.94 | 01-JAN-09:10 | 1463.18 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.24 | 388.67 | 23-APR-17:10 | 2330.45 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.81 | 28.32 | 01-JAN-07:50 | 938.11 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.81 | 28.32 | 01-JAN-07:50 | 938.11 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 46.86 | 603.12 | 12-MAR-17:10 | 3615.49 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.50 | 43.94 | 01-JAN-08:00 | 1454.91 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.50 | 43.94 | 01-JAN-08:00 | 1454.91 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.23 | 388.67 | 12-MAR-17:10 | 2338.54 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.80 | 28.32 | 01-JAN-09:10 | 946.21 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.80 | 28.32 | 01-JAN-09:10 | 946.21 | 11-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6050.65 | 7481.20 | 05-JAN-05:50 | 555201.52 | 22-JUN-15:40 |
HeatRejection:Electricity | 1812.21 | 3902.71 | 05-JAN-07:00 | 84253.44 | 06-MAR-13:30 |
General:HeatRejection:Electricity | 1812.21 | 3902.71 | 05-JAN-07:00 | 84253.44 | 06-MAR-13:30 |
Electricity:HVAC | 5948.29 | 77515.92 | 01-JAN-12:50 | 445129.42 | 06-JUL-14:30 |
ExteriorEquipment:Electricity | 1909.29 | 28161.90 | 01-JAN-00:10 | 116886.62 | 11-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.68 | 979.82 | 01-JAN-00:10 | 3408.66 | 11-OCT-07:20 |
ElectricityPurchased:Facility | 31338.71 | 345017.22 | 01-JAN-04:00 | 2026463.93 | 07-AUG-15:20 |
ElectricityPurchased:Plant | 31338.71 | 345017.22 | 01-JAN-04:00 | 2026463.93 | 07-AUG-15:20 |
Cogeneration:ElectricityPurchased | 31338.71 | 345017.22 | 01-JAN-04:00 | 2026463.93 | 07-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 31338.71 | 345017.22 | 01-JAN-04:00 | 2026463.93 | 07-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31338.71 | 345017.22 | 01-JAN-04:00 | 2026463.93 | 07-AUG-15:20 |
ElectricityNet:Plant | 31338.71 | 345017.22 | 01-JAN-04:00 | 2026463.93 | 07-AUG-15:20 |
Cogeneration:ElectricityNet | 31338.71 | 345017.22 | 01-JAN-04:00 | 2026463.93 | 07-AUG-15:20 |
General:Cogeneration:ElectricityNet | 31338.71 | 345017.22 | 01-JAN-04:00 | 2026463.93 | 07-AUG-15:20 |
Fans:Electricity | 2677.71 | 42286.42 | 01-JAN-09:30 | 271533.23 | 05-JUL-16:00 |
General:Fans:Electricity | 2677.71 | 42286.42 | 01-JAN-09:30 | 271533.23 | 05-JUL-16:00 |
ExteriorLights:Electricity | 349.31 | 0.00 | 01-JAN-07:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 349.31 | 0.00 | 01-JAN-07:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 6552.22 | 28725.66 | 01-JAN-05:40 | 580696.71 | 28-AUG-14:30 |
General:Cooling:Electricity | 6552.22 | 28725.66 | 01-JAN-05:40 | 580696.71 | 28-AUG-14:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 83.30 | 0.00 | 12-JAN-13:10 | 28624.24 | 22-DEC-06:00 |
General:Humidifier:Electricity | 83.30 | 0.00 | 12-JAN-13:10 | 28624.24 | 22-DEC-06:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 818.82 | 3477.14 | 19-APR-05:00 | 51499.04 | 05-MAY-08:00 |
General:Pumps:Electricity | 818.82 | 3477.14 | 19-APR-05:00 | 51499.04 | 05-MAY-08:00 |
WIRED_LTG_ELECTRICITY | 69.11 | 0.00 | 01-JAN-00:10 | 6718.22 | 11-OCT-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 671.78 | 7280.88 | 02-APR-15:20 | 717777.95 | 02-JAN-06:10 |
NaturalGas:Plant | 671.78 | 7280.88 | 02-APR-15:20 | 717777.95 | 02-JAN-06:10 |
Heating:NaturalGas | 62.68 | 0.00 | 01-JAN-00:10 | 710497.07 | 02-JAN-06:10 |
Boiler:Heating:NaturalGas | 62.68 | 0.00 | 01-JAN-00:10 | 710497.07 | 02-JAN-06:10 |
WaterSystems:NaturalGas | 609.10 | 7280.88 | 02-JAN-05:20 | 74451.23 | 17-JAN-13:00 |
Water Heater:WaterSystems:NaturalGas | 609.10 | 7280.88 | 02-JAN-05:20 | 74451.23 | 17-JAN-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 35884.01 | 152240.47 | 01-JAN-05:00 | 3234188.37 | 28-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 35884.01 | 152240.47 | 01-JAN-05:00 | 3234188.37 | 28-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 35884.01 | 152240.47 | 01-JAN-05:00 | 3234188.37 | 28-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 21744.35 | 0.00 | 11-MAR-00:30 | 0.00 | 12-JUN-15:30 |
Water:HVAC | 30.99 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Humidifier:Water | 30.99 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
General:Humidifier:Water | 30.99 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
MainsWater:Facility | 21744.35 | 0.00 | 11-MAR-00:30 | 0.00 | 12-JUN-15:30 |
MainsWater:HVAC | 30.99 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Humidifier:MainsWater | 30.99 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
General:Humidifier:MainsWater | 30.99 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Water:Plant | 21713.36 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 21713.36 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 19433.20 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
General:HeatRejection:Water | 19433.20 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
HeatRejection:MainsWater | 19433.20 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
General:HeatRejection:MainsWater | 19433.20 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JUN-15:30 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 127845.59 | 214463.43 | 03-JAN-05:50 | 12821353.85 | 22-JUN-15:40 |
EnergyTransfer:Building | 23201.03 | 89987.62 | 03-JAN-04:30 | 1769505.52 | 28-APR-15:40 |
EnergyTransfer:Zone:BASEMENT | 743.34 | 0.00 | 01-JAN-00:40 | 76854.99 | 13-NOV-06:10 |
Heating:EnergyTransfer | 38.67 | 0.00 | 03-JAN-22:10 | 404732.77 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.36 | 0.00 | 01-JAN-00:10 | 33157.90 | 10-JUN-16:10 |
General:Heating:EnergyTransfer | 38.67 | 0.00 | 03-JAN-22:10 | 404732.77 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.36 | 0.00 | 01-JAN-00:10 | 33157.90 | 10-JUN-16:10 |
Cooling:EnergyTransfer | 23162.35 | 89625.84 | 01-JAN-06:00 | 1769505.52 | 28-APR-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 738.98 | 0.00 | 01-JAN-00:40 | 76854.99 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 23162.35 | 89625.84 | 01-JAN-06:00 | 1769505.52 | 28-APR-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 738.98 | 0.00 | 01-JAN-00:40 | 76854.99 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 737.31 | 0.00 | 01-JAN-00:10 | 62406.50 | 07-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 737.31 | 0.00 | 01-JAN-00:10 | 62406.50 | 07-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 737.31 | 0.00 | 01-JAN-00:10 | 62406.50 | 07-AUG-07:20 |
EnergyTransfer:Zone:CORE_MID | 5626.76 | 0.00 | 01-JAN-00:10 | 449849.45 | 30-MAY-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.02 | 0.00 | 01-JAN-00:10 | 38022.23 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.02 | 0.00 | 01-JAN-00:10 | 38022.23 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5626.74 | 0.00 | 01-JAN-00:10 | 449849.45 | 30-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5626.74 | 0.00 | 01-JAN-00:10 | 449849.45 | 30-MAY-13:10 |
EnergyTransfer:Zone:CORE_TOP | 574.38 | 0.00 | 01-JAN-00:10 | 65003.54 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.58 | 0.00 | 01-JAN-00:10 | 65003.54 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.58 | 0.00 | 01-JAN-00:10 | 65003.54 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 573.81 | 0.00 | 01-JAN-00:10 | 57449.75 | 12-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 573.81 | 0.00 | 01-JAN-00:10 | 57449.75 | 12-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 122.65 | 0.00 | 01-JAN-00:10 | 14745.74 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 122.65 | 0.00 | 01-JAN-00:10 | 14745.74 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 122.65 | 0.00 | 01-JAN-00:10 | 14745.74 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 94.66 | 0.00 | 01-JAN-00:10 | 14113.68 | 12-JUN-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 94.66 | 0.00 | 01-JAN-00:10 | 14113.68 | 12-JUN-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 94.66 | 0.00 | 01-JAN-00:10 | 14113.68 | 12-JUN-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 165.12 | 0.00 | 01-JAN-00:10 | 18633.85 | 02-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1259.98 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1259.98 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 165.12 | 0.00 | 01-JAN-00:10 | 18633.85 | 02-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 165.12 | 0.00 | 01-JAN-00:10 | 18633.85 | 02-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 142.58 | 0.00 | 01-JAN-00:10 | 18432.70 | 27-APR-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 142.58 | 0.00 | 01-JAN-00:10 | 18432.70 | 27-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 142.58 | 0.00 | 01-JAN-00:10 | 18432.70 | 27-APR-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1046.58 | 0.00 | 01-JAN-00:10 | 145799.98 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.36 | 0.00 | 01-JAN-00:10 | 80798.75 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.36 | 0.00 | 01-JAN-00:10 | 80798.75 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1043.22 | 0.00 | 01-JAN-00:10 | 145799.98 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1043.22 | 0.00 | 01-JAN-00:10 | 145799.98 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 881.71 | 0.00 | 01-JAN-00:10 | 149528.82 | 12-JUN-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.07 | 0.00 | 01-JAN-00:10 | 48897.33 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.07 | 0.00 | 01-JAN-00:10 | 48897.33 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 880.63 | 0.00 | 01-JAN-00:10 | 149528.82 | 12-JUN-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 880.63 | 0.00 | 01-JAN-00:10 | 149528.82 | 12-JUN-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1516.95 | 0.00 | 01-JAN-00:10 | 187555.51 | 02-OCT-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.49 | 0.00 | 01-JAN-00:10 | 52222.33 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.49 | 0.00 | 01-JAN-00:10 | 52222.33 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1516.47 | 0.00 | 01-JAN-00:10 | 187555.51 | 02-OCT-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1516.47 | 0.00 | 01-JAN-00:10 | 187555.51 | 02-OCT-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 968.20 | 0.00 | 01-JAN-00:10 | 162065.07 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.54 | 0.00 | 01-JAN-00:10 | 37175.44 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.54 | 0.00 | 01-JAN-00:10 | 37175.44 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 967.66 | 0.00 | 01-JAN-00:10 | 162065.07 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 967.66 | 0.00 | 01-JAN-00:10 | 162065.07 | 06-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 110.37 | 0.00 | 01-JAN-00:10 | 16343.49 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.00 | 0.00 | 01-JAN-00:10 | 16343.49 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.00 | 0.00 | 01-JAN-00:10 | 16343.49 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 108.37 | 0.00 | 01-JAN-00:10 | 16044.06 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 108.37 | 0.00 | 01-JAN-00:10 | 16044.06 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 94.03 | 0.00 | 01-JAN-00:10 | 15401.20 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.74 | 0.00 | 01-JAN-00:10 | 10331.84 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.74 | 0.00 | 01-JAN-00:10 | 10331.84 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 93.29 | 0.00 | 01-JAN-00:10 | 15401.20 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 93.29 | 0.00 | 01-JAN-00:10 | 15401.20 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 153.63 | 0.00 | 01-JAN-00:10 | 20478.55 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.57 | 0.00 | 01-JAN-00:10 | 13460.26 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.57 | 0.00 | 01-JAN-00:10 | 13460.26 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 153.07 | 0.00 | 01-JAN-00:10 | 20478.55 | 02-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 153.07 | 0.00 | 01-JAN-00:10 | 20478.55 | 02-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 99.64 | 0.00 | 01-JAN-00:10 | 17441.23 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.53 | 0.00 | 01-JAN-00:10 | 8971.24 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.53 | 0.00 | 01-JAN-00:10 | 8971.24 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 99.12 | 0.00 | 01-JAN-00:10 | 17441.23 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 99.12 | 0.00 | 01-JAN-00:10 | 17441.23 | 06-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 132.12 | 0.00 | 01-JAN-00:10 | 20006.03 | 05-JUL-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.79 | 0.00 | 01-JAN-00:10 | 3943.95 | 31-DEC-11:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.79 | 0.00 | 01-JAN-00:10 | 3943.95 | 31-DEC-11:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 131.33 | 0.00 | 01-JAN-00:10 | 20006.03 | 05-JUL-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 131.33 | 0.00 | 01-JAN-00:10 | 20006.03 | 05-JUL-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1050.60 | 0.00 | 01-JAN-00:10 | 147622.54 | 12-JUN-14:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.01 | 0.00 | 01-JAN-00:10 | 44637.02 | 03-JAN-15:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 16.01 | 0.00 | 01-JAN-00:10 | 44637.02 | 03-JAN-15:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1034.60 | 0.00 | 01-JAN-00:10 | 147622.54 | 12-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1034.60 | 0.00 | 01-JAN-00:10 | 147622.54 | 12-JUN-14:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 173.10 | 0.00 | 01-JAN-00:10 | 34081.56 | 12-JUN-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 7.33 | 0.00 | 01-JAN-00:10 | 21760.21 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 7.33 | 0.00 | 01-JAN-00:10 | 21760.21 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 165.77 | 0.00 | 01-JAN-00:10 | 34081.56 | 12-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 165.77 | 0.00 | 01-JAN-00:10 | 34081.56 | 12-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.22 | 1041.84 | 03-JAN-08:00 | 7873.36 | 17-APR-00:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.22 | 1041.84 | 03-JAN-08:00 | 7873.36 | 17-APR-00:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.22 | 1041.84 | 03-JAN-08:00 | 7873.36 | 17-APR-00:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1318.29 | 31.45 | 03-JAN-04:30 | 72766.63 | 16-APR-22:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.17 | 0.00 | 01-JAN-15:00 | 2722.82 | 01-JAN-12:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.17 | 0.00 | 01-JAN-15:00 | 2722.82 | 01-JAN-12:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1318.12 | 0.00 | 01-JAN-00:10 | 72766.63 | 16-APR-22:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1318.12 | 0.00 | 01-JAN-00:10 | 72766.63 | 16-APR-22:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.65 | 0.79 | 05-JAN-03:50 | 7543.63 | 16-APR-21:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.13 | 0.00 | 02-JAN-13:20 | 349.25 | 01-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.13 | 0.00 | 02-JAN-13:20 | 349.25 | 01-JAN-13:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.52 | 0.00 | 01-JAN-00:10 | 7543.63 | 16-APR-21:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.52 | 0.00 | 01-JAN-00:10 | 7543.63 | 16-APR-21:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.13 | 88228.61 | 08-JAN-06:00 | 369545.36 | 15-AUG-24:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.13 | 88228.61 | 08-JAN-06:00 | 369545.36 | 15-AUG-24:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.13 | 88228.61 | 08-JAN-06:00 | 369545.36 | 15-AUG-24:00 |
PlantLoopHeatingDemand:Facility | 338.19 | 0.00 | 01-JAN-00:10 | 595951.49 | 02-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 293.17 | 0.00 | 01-JAN-00:10 | 40155.84 | 18-JAN-12:50 |
WaterSystems:PlantLoopHeatingDemand | 293.17 | 0.00 | 01-JAN-00:10 | 40155.84 | 18-JAN-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 293.17 | 0.00 | 01-JAN-00:10 | 40155.84 | 18-JAN-12:50 |
EnergyTransfer:HVAC | 32796.42 | 123525.28 | 01-JAN-05:20 | 3054178.24 | 28-AUG-14:30 |
HeatingCoils:EnergyTransfer | 45.02 | 0.00 | 01-JAN-00:10 | 591125.38 | 02-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 45.02 | 0.00 | 01-JAN-00:10 | 591125.38 | 02-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 45.02 | 0.00 | 01-JAN-00:10 | 591125.38 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 32751.41 | 123514.21 | 01-JAN-05:00 | 3054178.24 | 28-AUG-14:30 |
EnergyTransfer:Plant | 71848.14 | 0.00 | 01-JAN-00:20 | 8381037.62 | 22-JUN-15:40 |
LoopToLoop:EnergyTransfer | 22801.77 | 0.00 | 01-JAN-00:20 | 2646285.70 | 22-JUN-15:30 |
WaterSystems:EnergyTransfer | 293.17 | 0.00 | 01-JAN-00:10 | 40155.84 | 18-JAN-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 293.17 | 0.00 | 01-JAN-00:10 | 40155.84 | 18-JAN-12:50 |
Boilers:EnergyTransfer | 44.48 | 0.00 | 01-JAN-00:10 | 585054.40 | 02-JAN-06:10 |
Chillers:EnergyTransfer | 22644.55 | 0.00 | 01-JAN-00:20 | 2647249.60 | 22-JUN-15:40 |
HeatRejection:EnergyTransfer | 26064.17 | 0.00 | 01-JAN-00:20 | 3068414.29 | 22-JUN-15:40 |
General:HeatRejection:EnergyTransfer | 26064.17 | 0.00 | 01-JAN-00:20 | 3068414.29 | 22-JUN-15:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.362 | -738.974 | 0.000 | 0.000 | 92.668 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 51.817 | 0.000 | 0.000 | 0.000 | 0.000 | -0.005 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -737.308 | 0.000 | 0.000 | 83.404 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 215.453 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_MID | 0.000 | 0.000 | 0.023 | -5626.728 | 0.000 | 0.000 | 836.220 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 405.992 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_TOP | 0.000 | 0.000 | 0.575 | -573.803 | 0.000 | 0.000 | 84.307 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 50.471 | 0.000 | 0.000 | 0.000 | 0.000 | -0.008 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -122.646 | 0.000 | 0.000 | 10.524 | 10.623 | 36.365 | 51.777 | 0.000 | 0.609 | 40.856 | 0.000 | -27.757 | 0.000 | -0.351 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -94.657 | 0.000 | 0.000 | 6.760 | 6.814 | 23.435 | 61.113 | 0.000 | 0.403 | 13.460 | 0.000 | -17.089 | 0.000 | -0.239 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.001 | -165.116 | 0.000 | 0.000 | 10.477 | 10.509 | 36.366 | 110.075 | 0.000 | 0.599 | 24.760 | 0.000 | -27.281 | 0.000 | -0.390 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -142.583 | 0.000 | 0.000 | 6.738 | 6.810 | 23.435 | 59.626 | 0.000 | 0.381 | 67.533 | 0.000 | -21.653 | 0.000 | -0.288 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.363 | -1043.209 | 0.000 | 0.000 | 107.045 | 106.054 | 363.654 | 533.277 | 0.000 | 14.057 | 171.361 | 0.000 | -248.556 | 0.000 | -7.047 | -0.008 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.071 | -880.628 | 0.000 | 0.000 | 49.839 | 68.061 | 234.352 | 608.854 | 0.000 | 8.971 | 78.571 | 0.000 | -163.768 | 0.000 | -5.324 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.485 | -1516.452 | 0.000 | 0.000 | 105.054 | 104.979 | 363.660 | 1102.135 | 0.000 | 13.672 | 102.124 | 0.000 | -266.725 | 0.000 | -8.933 | -0.026 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.540 | -967.650 | 0.000 | 0.000 | 68.260 | 68.003 | 234.351 | 615.377 | 0.000 | 8.921 | 160.999 | 0.000 | -183.271 | 0.000 | -5.531 | -0.004 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.000 | -108.373 | 0.000 | 0.000 | 10.797 | 10.605 | 36.365 | 52.995 | 0.000 | 1.699 | 18.075 | 0.000 | -23.365 | 0.000 | -0.799 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.742 | -93.292 | 0.000 | 0.000 | 6.842 | 6.806 | 23.435 | 61.005 | 0.000 | 1.097 | 9.474 | 0.000 | -15.503 | 0.000 | -0.606 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.567 | -153.064 | 0.000 | 0.000 | 10.561 | 10.497 | 36.366 | 109.816 | 0.000 | 1.653 | 10.044 | 0.000 | -25.395 | 0.000 | -1.045 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.527 | -99.116 | 0.000 | 0.000 | 6.873 | 6.800 | 23.435 | 61.248 | 0.000 | 1.084 | 17.249 | 0.000 | -17.455 | 0.000 | -0.646 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -143.222 | 0.000 | 0.000 | 0.941 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -15.225 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.168 | -1318.119 | 0.000 | 0.000 | 9.381 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -266.499 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.132 | -129.519 | 0.000 | 0.000 | 0.943 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -29.063 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7176.142 | 0.000 | 0.000 | 19.428 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -385.755 |
GROUNDFLOOR_PLENUM | 0.786 | -131.333 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.102 | 130.243 | 0.000 | 0.000 | 0.000 | -0.797 | -0.000 |
MIDFLOOR_PLENUM | 16.007 | -1034.590 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 20.081 | 1011.920 | 0.000 | 0.000 | 0.000 | -13.418 | -0.006 |
TOPFLOOR_PLENUM | 7.326 | -165.768 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.071 | 157.724 | 0.000 | 0.000 | 0.000 | -1.353 | -0.001 |
Total Facility | 24.118 | -1331.691 | 14.556 | -21830.599 | 0.000 | 0.000 | 1527.062 | 2459.457 | 14676.396 | 3427.299 | 0.000 | 76.400 | 2738.127 | 0.000 | -1037.817 | 0.000 | -46.767 | -696.609 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-JAN-05:11 | 0.00 | 0.00 | 0.00 | -105203.60 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 91147.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 30-OCT-04:13 | 0.00 | 0.00 | 0.00 | -96503.52 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 90028.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 10-APR-04:13 | 0.00 | 0.00 | 0.00 | -882880.92 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 818131.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 03-JUL-05:04 | 0.00 | 0.00 | 0.00 | -87091.21 | 0.00 | 0.00 | 795.83 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 78110.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-JUL-17:01 | 0.00 | 0.00 | 0.00 | -23882.87 | 0.00 | 0.00 | 0.00 | 43.94 | 559.17 | 6223.27 | 0.00 | 113.30 | 16943.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-APR-09:41 | 0.00 | 0.00 | 0.00 | -19456.14 | 0.00 | 0.00 | 20.67 | 28.32 | 464.11 | 12656.87 | 0.00 | 16.74 | 6269.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-12:51 | 0.00 | 0.00 | 0.00 | -25127.71 | 0.00 | 0.00 | 32.29 | 43.94 | 720.19 | 17177.53 | 0.00 | 11.19 | 7142.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-APR-16:21 | 0.00 | 0.00 | 0.00 | -28688.52 | 0.00 | 0.00 | 13.56 | 28.32 | 464.11 | 13699.63 | 0.00 | 112.41 | 14370.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUN-16:11 | 0.00 | 0.00 | 0.00 | -235816.49 | 0.00 | 0.00 | 379.65 | 439.44 | 7201.84 | 72173.13 | 0.00 | 4929.88 | 150692.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-10:01 | 0.00 | 0.00 | 0.00 | -198379.26 | 0.00 | 0.00 | 177.09 | 283.19 | 4641.14 | 107131.47 | 0.00 | 6109.88 | 80036.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 29-OCT-13:01 | 0.00 | 0.00 | 0.00 | -255145.71 | 0.00 | 0.00 | 320.84 | 439.45 | 7201.95 | 183235.59 | 0.00 | 0.00 | 63951.34 | 0.00 | -0.00 | 0.00 | -3.46 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUN-16:11 | 0.00 | 0.00 | 0.00 | -246400.79 | 0.00 | 0.00 | 163.65 | 283.19 | 4641.11 | 137475.06 | 0.00 | 2780.99 | 101056.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 30-APR-15:41 | 0.00 | 0.00 | 0.00 | -26440.53 | 0.00 | 0.00 | 37.48 | 43.94 | 720.18 | 4876.98 | 0.00 | 689.31 | 20072.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 30-APR-09:41 | 0.00 | 0.00 | 0.00 | -22041.32 | 0.00 | 0.00 | 19.43 | 28.32 | 464.11 | 12486.39 | 0.00 | 36.75 | 9006.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 29-OCT-13:31 | 0.00 | 0.00 | 0.00 | -28473.79 | 0.00 | 0.00 | 31.68 | 43.94 | 720.19 | 17037.44 | 0.00 | 0.44 | 10640.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-APR-15:41 | 0.00 | 0.00 | 0.00 | -27179.76 | 0.00 | 0.00 | 14.96 | 28.32 | 464.11 | 14594.23 | 0.00 | 341.18 | 11736.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 17-APR-00:23 | 0.00 | 0.00 | 0.00 | -7875.59 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 63.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-22:23 | 0.00 | 0.00 | 0.00 | -72801.15 | 0.00 | 0.00 | 0.00 | 175.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5318.98 |
DATACENTER_TOP_ZN_6 | 16-APR-21:32 | 0.00 | 0.00 | 0.00 | -7546.88 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -265.13 |
DATACENTER_BASEMENT_ZN_6 | 15-AUG-23:53 | 0.00 | 0.00 | 0.00 | -369724.41 | 0.00 | 0.00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10139.05 |
GROUNDFLOOR_PLENUM | 30-MAY-05:15 | 0.00 | -23113.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 | 23094.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 12-JUN-05:15 | 0.00 | -192648.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984.77 | 191663.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-13:50 | 0.00 | -34083.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.28 | 33719.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:01 | 0.00 | -118332.41 | 0.00 | -2214035.41 | 0.00 | 0.00 | 15261.69 | 10593.62 | 616289.16 | 8843.55 | 0.00 | 1061.49 | 1680463.99 | 0.00 | -145.69 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-JUN-16:01 | 0.00 | 0.00 | 35117.53 | 0.00 | 0.00 | 0.00 | 520.12 | 819.05 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -49914.25 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-06:03 | 0.00 | 0.00 | 152073.08 | 0.00 | 0.00 | 0.00 | 11313.95 | 5373.60 | 76473.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -245234.24 |
CORE_TOP | 02-JAN-05:11 | 0.00 | 0.00 | 70817.88 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -77292.86 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 02-JAN-06:03 | 0.00 | 0.00 | 4204.81 | 0.00 | 0.00 | 0.00 | 141.27 | 67.47 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4191.46 | 0.00 | 0.00 | -1182.35 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 159095.27 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34486.15 | 0.00 | 0.00 | -132739.43 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 112449.04 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23447.13 | 0.00 | 0.00 | -94241.40 |
PERIMETER_MID_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 148657.76 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37885.31 | 0.00 | 0.00 | -118902.90 |
PERIMETER_MID_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 102126.94 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24990.16 | 0.00 | 0.00 | -82376.24 |
PERIMETER_TOP_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 20383.39 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2763.01 | 0.00 | 0.00 | -18433.41 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 14310.25 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1864.97 | 0.00 | 0.00 | -12969.22 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 20011.62 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2919.86 | 0.00 | 0.00 | -17904.81 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 14378.95 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1954.56 | 0.00 | 0.00 | -12948.33 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-12:50 | 0.00 | 0.00 | 2722.95 | 0.00 | 0.00 | 0.00 | 53.38 | 175.92 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22438.30 |
DATACENTER_TOP_ZN_6 | 01-JAN-13:45 | 0.00 | 0.00 | 352.89 | 0.00 | 0.00 | 0.00 | 6.96 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2326.05 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 11-DEC-05:12 | 12091.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12091.22 |
MIDFLOOR_PLENUM | 04-JUN-16:12 | 74535.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8222.17 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -82758.09 |
TOPFLOOR_PLENUM | 02-JAN-06:03 | 23616.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23616.36 |
Total Facility | 02-JAN-06:03 | -234978.47 | 260933.33 | 752568.79 | -260933.33 | 0.00 | 0.00 | 20414.90 | 10593.62 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -151960.06 | 0.00 | 0.00 | -658053.74 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.9569 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.0228 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 106.0464 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 96.1000 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.2001 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.0598 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.3649 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.3649 | 0.2237 | 1.0000 | Not calculated | 1.2002 | 0.2237 | ||
AIRLOOP DATACENTER BASEMENT | 21.8703 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.8705 | 0.0155 | 1.0000 | Not calculated | 0.3384 | 0.0155 | ||
AIRLOOP DATACENTER BOT | 0.4820 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4820 | 0.0324 | 1.0000 | Not calculated | 0.0156 | 0.0324 | ||
AIRLOOP DATACENTER MID | 4.6027 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6027 | 0.0340 | 1.0000 | Not calculated | 0.1563 | 0.0340 | ||
AIRLOOP DATACENTER TOP | 0.4652 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4652 | 0.0336 | 1.0000 | Not calculated | 0.0156 | 0.0336 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.4785 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2876 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 53.0232 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8518 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.6000 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2849 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.3649 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.3649 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2237 | ||
AIRLOOP DATACENTER BASEMENT | 21.8703 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.8703 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0155 | ||
AIRLOOP DATACENTER BOT | 0.4820 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4820 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0324 | ||
AIRLOOP DATACENTER MID | 4.6027 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6027 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0340 | ||
AIRLOOP DATACENTER TOP | 0.4652 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4652 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0336 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.3649 | 5.3649 | 5.3649 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9527 | 5.9527 | 1.6191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.9553 | 56.9553 | 16.1753 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8209 | 5.8209 | 1.6182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3049 | 1.3049 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0314 | 1.0314 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3170 | 1.3170 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3508 | 1.3508 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.1072 | 13.1072 | 2.0316 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.8981 | 10.8981 | 1.3078 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.1042 | 13.1042 | 2.0312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.9817 | 11.9817 | 1.3060 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4726 | 1.4726 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1354 | 1.1354 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4691 | 1.4691 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3020 | 1.3020 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4820 | 0.4820 | 0.4820 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6027 | 4.6027 | 4.6027 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4652 | 0.4652 | 0.4652 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.8703 | 21.8703 | 21.8703 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.9569 | 10.0228 | 10.9569 | 2.2876 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 106.0464 | 96.1000 | 106.0464 | 22.8518 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.2001 | 11.0598 | 11.2001 | 2.2849 | 0.0000 | 1.0000 |
CAV_BAS | 5.3649 | 5.3649 | 5.3649 | 5.3649 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.8703 | 21.8705 | 21.8703 | 21.8703 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4820 | 0.4820 | 0.4820 | 0.4820 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6027 | 4.6027 | 4.6027 | 4.6027 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4652 | 0.4652 | 0.4652 | 0.4652 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.3649 | 5.3649 | 5.3649 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9764 | 2.9764 | 1.6191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.4777 | 28.4777 | 16.1753 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9104 | 2.9104 | 1.6182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6525 | 0.6525 | 0.2036 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5157 | 0.5157 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6585 | 0.6585 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6754 | 0.6754 | 0.1310 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5536 | 6.5536 | 2.0316 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4490 | 5.4490 | 1.3078 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5521 | 6.5521 | 2.0312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9909 | 5.9909 | 1.3060 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7363 | 0.7363 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5677 | 0.5677 | 0.1306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7346 | 0.7346 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6510 | 0.6510 | 0.1302 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4820 | 0.4820 | 0.4820 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6027 | 4.6027 | 4.6027 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4652 | 0.4652 | 0.4652 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.8703 | 21.8703 | 21.8703 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.4785 | 2.2876 | 2.2876 | 2.2876 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 53.0232 | 22.8518 | 22.8518 | 22.8518 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.6000 | 2.2849 | 2.2849 | 2.2849 | 0.0000 | 1.0000 |
CAV_BAS | 5.3649 | 5.3649 | 5.3649 | 5.3649 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.8703 | 21.8703 | 21.8703 | 21.8703 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4820 | 0.4820 | 0.4820 | 0.4820 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6027 | 4.6027 | 4.6027 | 4.6027 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4652 | 0.4652 | 0.4652 | 0.4652 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1163.50 |
Number of hours not met | 1163.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 62.68 | 710497.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6552.22 | 580696.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2459.46 | 239082.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 349.31 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.68 | 3408.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2677.71 | 271533.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 818.82 | 51499.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1812.21 | 84253.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 83.30 | 28624.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 609.10 | 74451.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 31338.71 |
Natural Gas | 0.00 | 671.78 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 32010.49 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.10 |
Space Heating | 0.00 |
Space Cooling | 141.45 |
Fans (All) | 57.81 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 676.56 |
Subtotal | 676.56 |
Natural Gas [MJ/m2] | |
Space Heating | 1.35 |
Service Water Heating | 13.15 |
Miscellaneous (All) | 14.50 |
Subtotal | 14.50 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.68 |
Space Heating | 0.20 |
Space Cooling | 20.47 |
Fans (All) | 8.37 |
Service Water Heating | 1.90 |
Receptacle Equipment | 45.85 |
Miscellaneous | 15.54 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 939. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7448.67 | 1311.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8683.83 | 76.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8751.33 | 8.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8452.67 | 307.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8367.50 | 392.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8285.67 | 474.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7138.00 | 1622.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8370.33 | 389.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8108.17 | 651.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8031.67 | 728.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7704.17 | 1055.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8254.00 | 506.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8040.17 | 719.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7962.33 | 797.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7686.67 | 1073.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6650.17 | 2109.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6114.00 | 2646.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6720.67 | 2039.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7287.17 | 1472.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8354.50 | 405.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8645.17 | 114.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7913.67 | 846.33 | 0.00 | 0.00 | 0.00 |
Min | 6114.00 | 0.67 | 0.00 | 0.00 | 0.00 |
Max | 8759.33 | 2646.00 | 0.00 | 0.00 | 0.00 |
Average | 7901.30 | 858.70 | 0.00 | 0.00 | 0.00 |
Sum | 181729.83 | 19750.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 365214.00 | 3402.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330683.00 | 130.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330809.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330778.00 | 35.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1501.83 | 766.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1343.50 | 924.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1498.17 | 769.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 82138.17 | 21256.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 365214.00 | 21256.83 | 0.00 | 0.00 | 0.00 |
Average | 79148.46 | 1186.45 | 0.00 | 0.00 | 0.00 |
Sum | 1820414.67 | 27288.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 5429.50 | 3330.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7063.00 | 1697.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7720.17 | 1039.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7391.17 | 1368.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6782.33 | 1977.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6743.17 | 2016.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6492.00 | 2268.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6174.17 | 2585.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6810.83 | 1949.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6636.33 | 2123.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6491.83 | 2268.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6534.33 | 2225.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6800.83 | 1959.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6666.33 | 2093.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6536.00 | 2224.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6573.67 | 2186.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7462.33 | 1297.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7077.00 | 1683.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7474.83 | 1285.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7538.00 | 1222.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 5116.17 | 3643.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 4804.50 | 3955.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4486.50 | 4273.50 | 0.00 | 0.00 | 0.00 |
Min | 4486.50 | 1039.83 | 0.00 | 0.00 | 0.00 |
Max | 7720.17 | 4273.50 | 0.00 | 0.00 | 0.00 |
Average | 6556.74 | 2203.26 | 0.00 | 0.00 | 0.00 |
Sum | 150805.00 | 50675.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 336090.17 | 32525.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 327524.17 | 3288.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328851.00 | 1962.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 328065.50 | 2747.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38920.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18349.83 | 4.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38920.67 | 4.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24906.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38917.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24902.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38917.67 | 7.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24904.00 | 5.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1785.67 | 482.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1637.67 | 630.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1781.83 | 486.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 87319.00 | 16076.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 336090.17 | 32525.83 | 0.00 | 0.00 | 0.00 |
Average | 77802.69 | 2532.22 | 0.00 | 0.00 | 0.00 |
Sum | 1789461.83 | 58241.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:51
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.538827E+11 | 105203.79 | 23-JAN-05:11 | 6.33 | 5.49 | 0.566761E+10 | 7499.22 | 04-JAN-10:20 | 6.33 | 5.49 |
February | 0.493060E+11 | 101665.64 | 20-FEB-14:42 | 26.32 | 13.93 | 0.514053E+10 | 7499.25 | 02-FEB-10:20 | 26.32 | 13.93 |
March | 0.578350E+11 | 99348.56 | 06-MAR-05:12 | 15.13 | 13.89 | 0.613419E+10 | 7499.19 | 16-MAR-09:20 | 18.63 | 14.21 |
April | 0.561357E+11 | 100990.29 | 30-APR-17:34 | 35.90 | 17.54 | 0.545202E+10 | 7499.21 | 04-APR-09:20 | 35.90 | 17.54 |
May | 0.594536E+11 | 97992.44 | 01-MAY-03:02 | 30.53 | 18.79 | 0.590333E+10 | 7499.05 | 05-MAY-09:20 | 35.77 | 19.27 |
June | 0.624362E+11 | 93732.98 | 04-JUN-23:08 | 33.67 | 20.75 | 0.588470E+10 | 7499.05 | 07-JUN-09:20 | 37.90 | 20.70 |
July | 0.665127E+11 | 86780.55 | 04-JUL-20:17 | 39.70 | 24.42 | 0.547668E+10 | 7498.92 | 27-JUL-13:20 | 30.70 | 26.49 |
August | 0.762062E+11 | 83841.88 | 29-AUG-03:02 | 27.75 | 24.39 | 0.614001E+10 | 7498.90 | 16-AUG-13:20 | 27.75 | 24.39 |
September | 0.648406E+11 | 83552.10 | 26-SEP-03:02 | 25.65 | 21.91 | 0.545548E+10 | 7498.92 | 08-SEP-13:20 | 25.65 | 21.91 |
October | 0.673856E+11 | 97182.10 | 29-OCT-14:16 | 29.23 | 17.90 | 0.567362E+10 | 7499.05 | 24-OCT-09:20 | 29.23 | 17.90 |
November | 0.644771E+11 | 101161.15 | 12-NOV-13:51 | 28.20 | 15.95 | 0.561731E+10 | 7499.13 | 16-NOV-10:20 | 22.00 | 16.54 |
December | 0.605071E+11 | 101196.62 | 18-DEC-05:12 | 11.27 | 8.23 | 0.547341E+10 | 7499.13 | 18-DEC-10:20 | 20.37 | 13.79 |
Annual Sum or Average | 0.738978E+12 | 0.680189E+11 | ||||||||
Minimum of Months | 0.493060E+11 | 83552.10 | 6.33 | 5.49 | 0.514053E+10 | 7498.90 | 6.33 | 5.49 | ||
Maximum of Months | 0.762062E+11 | 105203.79 | 39.70 | 24.42 | 0.614001E+10 | 7499.25 | 37.90 | 26.49 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397613E+11 | 89548.17 | 02-JAN-05:11 | 6.47 | 6.24 | 0.507716E+10 | 6734.81 | 04-JAN-10:20 | 13.03 | 10.49 |
February | 0.433675E+11 | 95169.16 | 21-FEB-05:12 | 11.87 | 10.80 | 0.460616E+10 | 6734.82 | 02-FEB-10:39 | 11.87 | 10.80 |
March | 0.621691E+11 | 92744.81 | 06-MAR-05:13 | 15.13 | 13.89 | 0.549880E+10 | 6734.82 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.707986E+11 | 88323.63 | 03-APR-05:05 | 22.60 | 18.05 | 0.488097E+10 | 6734.81 | 04-APR-09:20 | 27.13 | 18.13 |
May | 0.680471E+11 | 86917.08 | 01-MAY-05:04 | 32.45 | 19.07 | 0.528326E+10 | 6734.69 | 08-MAY-13:20 | 38.70 | 20.91 |
June | 0.692168E+11 | 86252.08 | 19-JUN-05:03 | 27.98 | 23.01 | 0.526799E+10 | 6734.75 | 05-JUN-13:20 | 27.98 | 23.01 |
July | 0.713945E+11 | 87268.05 | 05-JUL-05:06 | 32.57 | 24.73 | 0.489681E+10 | 6734.68 | 18-JUL-09:20 | 27.40 | 26.41 |
August | 0.803845E+11 | 87782.17 | 28-AUG-05:06 | 29.10 | 27.38 | 0.549936E+10 | 6753.19 | 14-AUG-13:50 | 29.10 | 27.38 |
September | 0.614746E+11 | 86225.46 | 18-SEP-05:04 | 26.72 | 24.18 | 0.488061E+10 | 6734.68 | 05-SEP-09:20 | 26.72 | 24.18 |
October | 0.634370E+11 | 96533.01 | 30-OCT-04:13 | 16.40 | 14.90 | 0.507856E+10 | 6734.76 | 24-OCT-09:20 | 16.40 | 14.90 |
November | 0.565535E+11 | 96182.77 | 20-NOV-05:12 | 12.73 | 11.55 | 0.503234E+10 | 6734.78 | 16-NOV-10:20 | 12.73 | 11.55 |
December | 0.507036E+11 | 95702.06 | 26-DEC-05:12 | 10.17 | 8.84 | 0.490273E+10 | 6734.79 | 27-DEC-10:20 | 17.47 | 12.54 |
Annual Sum or Average | 0.737308E+12 | 0.609047E+11 | ||||||||
Minimum of Months | 0.397613E+11 | 86225.46 | 6.47 | 6.24 | 0.460616E+10 | 6734.68 | 11.87 | 10.49 | ||
Maximum of Months | 0.803845E+11 | 96533.01 | 32.57 | 27.38 | 0.549936E+10 | 6753.19 | 38.70 | 27.38 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275461E+11 | 76637.08 | 27-JAN-06:03 | 11.07 | 9.85 | 0.497532E+10 | 6734.77 | 05-JAN-10:09 | 11.07 | 9.85 |
February | 0.315903E+11 | 82186.00 | 27-FEB-05:12 | 11.13 | 10.43 | 0.458283E+10 | 6734.80 | 02-FEB-10:39 | 11.13 | 10.43 |
March | 0.469045E+11 | 84342.08 | 08-MAR-05:12 | 15.77 | 13.75 | 0.549452E+10 | 6734.82 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.527658E+11 | 88288.19 | 10-APR-04:13 | 18.47 | 13.25 | 0.487432E+10 | 6734.81 | 04-APR-09:20 | 18.47 | 13.25 |
May | 0.596447E+11 | 72492.62 | 30-MAY-05:02 | 30.25 | 21.57 | 0.527825E+10 | 6734.80 | 01-MAY-09:20 | 30.25 | 21.57 |
June | 0.578898E+11 | 75495.64 | 12-JUN-05:02 | 34.12 | 19.12 | 0.526493E+10 | 6734.76 | 05-JUN-13:20 | 34.12 | 19.12 |
July | 0.560328E+11 | 71363.46 | 10-JUL-05:02 | 30.80 | 25.35 | 0.488963E+10 | 6734.74 | 06-JUL-09:20 | 30.80 | 25.35 |
August | 0.574035E+11 | 72334.97 | 24-AUG-05:03 | 25.45 | 24.92 | 0.549290E+10 | 6734.71 | 21-AUG-13:20 | 25.45 | 24.92 |
September | 0.506350E+11 | 73572.83 | 29-SEP-03:02 | 24.60 | 20.85 | 0.487832E+10 | 6734.71 | 11-SEP-13:20 | 24.60 | 20.85 |
October | 0.498094E+11 | 84651.19 | 24-OCT-04:12 | 18.37 | 13.98 | 0.507458E+10 | 6734.76 | 24-OCT-09:20 | 24.07 | 16.08 |
November | 0.410527E+11 | 84452.74 | 13-NOV-05:12 | 14.87 | 12.34 | 0.502024E+10 | 6734.78 | 06-NOV-10:20 | 14.87 | 12.34 |
December | 0.313993E+11 | 80132.92 | 01-DEC-06:02 | 11.02 | 8.79 | 0.486062E+10 | 6734.75 | 27-DEC-10:20 | 17.47 | 12.54 |
Annual Sum or Average | 0.562674E+12 | 0.606865E+11 | ||||||||
Minimum of Months | 0.275461E+11 | 71363.46 | 11.02 | 8.79 | 0.458283E+10 | 6734.71 | 11.07 | 9.85 | ||
Maximum of Months | 0.596447E+11 | 88288.19 | 34.12 | 25.35 | 0.549452E+10 | 6734.82 | 34.12 | 25.35 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214204E+11 | 32341.05 | 26-JAN-16:30 | 19.40 | 12.94 | 0.464486E+10 | 6734.69 | 13-JAN-14:20 | 19.40 | 12.94 |
February | 0.265425E+11 | 78233.72 | 23-FEB-06:02 | 15.05 | 13.57 | 0.447697E+10 | 6734.73 | 15-FEB-10:20 | 15.05 | 13.57 |
March | 0.452479E+11 | 84961.34 | 13-MAR-04:12 | 20.87 | 16.21 | 0.548057E+10 | 6734.81 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.574399E+11 | 85531.22 | 10-APR-04:11 | 18.47 | 13.25 | 0.487849E+10 | 6734.80 | 04-APR-09:20 | 18.47 | 13.25 |
May | 0.681872E+11 | 85312.43 | 30-MAY-05:03 | 30.25 | 21.57 | 0.528556E+10 | 6734.70 | 08-MAY-13:20 | 30.25 | 21.57 |
June | 0.666345E+11 | 86678.82 | 12-JUN-05:02 | 34.12 | 19.12 | 0.526999E+10 | 6734.75 | 05-JUN-13:20 | 34.12 | 19.12 |
July | 0.631825E+11 | 87112.91 | 03-JUL-05:04 | 29.37 | 24.69 | 0.489677E+10 | 6734.68 | 18-JUL-09:20 | 27.40 | 26.41 |
August | 0.632879E+11 | 85696.65 | 07-AUG-05:04 | 29.53 | 24.79 | 0.549719E+10 | 6734.68 | 16-AUG-09:20 | 25.07 | 24.43 |
September | 0.539973E+11 | 83478.31 | 11-SEP-03:02 | 26.07 | 25.28 | 0.488126E+10 | 6734.68 | 05-SEP-09:20 | 26.07 | 25.28 |
October | 0.490018E+11 | 84789.67 | 10-OCT-04:12 | 19.83 | 18.10 | 0.507136E+10 | 6734.75 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.351336E+11 | 79913.32 | 01-NOV-05:02 | 15.60 | 12.04 | 0.497304E+10 | 6734.75 | 06-NOV-10:20 | 23.67 | 17.41 |
December | 0.237304E+11 | 33570.38 | 01-DEC-16:30 | 21.75 | 14.01 | 0.464503E+10 | 6734.72 | 29-DEC-10:20 | 18.10 | 13.45 |
Annual Sum or Average | 0.573806E+12 | 0.600011E+11 | ||||||||
Minimum of Months | 0.214204E+11 | 32341.05 | 15.05 | 12.04 | 0.447697E+10 | 6734.68 | 15.05 | 12.94 | ||
Maximum of Months | 0.681872E+11 | 87112.91 | 34.12 | 25.28 | 0.549719E+10 | 6734.81 | 34.12 | 26.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291860E+10 | 4464.00 | 26-JAN-14:10 | 22.35 | 13.84 | 0.604290E+09 | 845.62 | 13-JAN-14:20 | 22.35 | 13.84 |
February | 0.405645E+10 | 6599.13 | 23-FEB-14:30 | 26.10 | 14.00 | 0.567309E+09 | 845.62 | 13-FEB-10:20 | 26.10 | 14.00 |
March | 0.835256E+10 | 12582.37 | 14-MAR-05:02 | 20.70 | 16.42 | 0.689323E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.130799E+11 | 22864.39 | 30-APR-16:21 | 37.45 | 18.00 | 0.614273E+09 | 845.63 | 04-APR-09:20 | 37.45 | 18.00 |
May | 0.155498E+11 | 22032.52 | 29-MAY-16:21 | 41.10 | 21.45 | 0.665813E+09 | 845.62 | 08-MAY-13:20 | 41.10 | 21.45 |
June | 0.162700E+11 | 23268.28 | 04-JUN-16:21 | 42.05 | 22.41 | 0.663503E+09 | 845.63 | 05-JUN-13:20 | 42.30 | 22.45 |
July | 0.155988E+11 | 23893.65 | 04-JUL-17:01 | 39.95 | 24.24 | 0.617377E+09 | 845.61 | 11-JUL-13:20 | 32.03 | 26.25 |
August | 0.160912E+11 | 21767.49 | 27-AUG-15:01 | 35.43 | 29.15 | 0.692119E+09 | 849.10 | 14-AUG-13:50 | 35.43 | 29.15 |
September | 0.114231E+11 | 21907.06 | 24-SEP-15:01 | 35.05 | 24.91 | 0.614219E+09 | 845.62 | 08-SEP-13:20 | 35.05 | 24.91 |
October | 0.947358E+10 | 21302.60 | 09-OCT-14:51 | 32.80 | 19.85 | 0.637876E+09 | 845.62 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.595620E+10 | 7223.95 | 09-NOV-14:20 | 29.33 | 17.81 | 0.628543E+09 | 845.62 | 16-NOV-10:20 | 22.00 | 16.54 |
December | 0.387634E+10 | 5342.70 | 26-DEC-14:10 | 22.68 | 14.39 | 0.601184E+09 | 845.62 | 29-DEC-14:20 | 19.70 | 14.83 |
Annual Sum or Average | 0.122647E+12 | 0.759583E+10 | ||||||||
Minimum of Months | 0.291860E+10 | 4464.00 | 20.70 | 13.84 | 0.567309E+09 | 845.61 | 19.70 | 13.84 | ||
Maximum of Months | 0.162700E+11 | 23893.65 | 42.05 | 29.15 | 0.692119E+09 | 849.10 | 42.30 | 29.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252677E+10 | 4385.75 | 26-JAN-10:20 | 18.10 | 12.94 | 0.402408E+09 | 544.95 | 04-JAN-10:39 | 18.10 | 12.94 |
February | 0.363646E+10 | 8449.57 | 20-FEB-10:43 | 21.85 | 12.76 | 0.368854E+09 | 544.96 | 02-FEB-10:39 | 21.85 | 12.76 |
March | 0.720269E+10 | 14561.16 | 12-MAR-14:32 | 31.40 | 19.53 | 0.444795E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.108626E+11 | 19455.67 | 30-APR-09:41 | 30.90 | 15.93 | 0.396144E+09 | 545.36 | 28-APR-09:50 | 30.90 | 15.93 |
May | 0.130365E+11 | 18434.28 | 29-MAY-09:02 | 34.05 | 21.14 | 0.429399E+09 | 545.81 | 04-MAY-09:09 | 34.05 | 21.14 |
June | 0.120643E+11 | 18273.46 | 04-JUN-16:21 | 42.05 | 22.41 | 0.427735E+09 | 555.78 | 12-JUN-09:39 | 39.50 | 22.03 |
July | 0.106663E+11 | 18963.82 | 04-JUL-15:41 | 39.65 | 24.77 | 0.397861E+09 | 545.08 | 07-JUL-09:00 | 36.90 | 24.55 |
August | 0.103007E+11 | 16961.73 | 06-AUG-16:21 | 36.15 | 26.34 | 0.445858E+09 | 547.11 | 14-AUG-13:50 | 32.52 | 27.52 |
September | 0.864845E+10 | 17531.33 | 24-SEP-15:01 | 35.05 | 24.91 | 0.395945E+09 | 544.95 | 08-SEP-13:20 | 35.05 | 24.91 |
October | 0.778849E+10 | 17429.52 | 01-OCT-08:32 | 26.43 | 18.60 | 0.411595E+09 | 544.98 | 02-OCT-09:20 | 30.57 | 20.21 |
November | 0.494061E+10 | 9189.75 | 05-NOV-10:32 | 24.63 | 16.65 | 0.405948E+09 | 544.95 | 16-NOV-10:20 | 22.00 | 16.54 |
December | 0.298398E+10 | 4960.42 | 01-DEC-10:00 | 18.30 | 11.37 | 0.390602E+09 | 544.95 | 18-DEC-10:20 | 20.37 | 13.79 |
Annual Sum or Average | 0.946580E+11 | 0.491714E+10 | ||||||||
Minimum of Months | 0.252677E+10 | 4385.75 | 18.10 | 11.37 | 0.368854E+09 | 544.95 | 18.10 | 12.76 | ||
Maximum of Months | 0.130365E+11 | 19455.67 | 42.05 | 26.34 | 0.445858E+09 | 555.78 | 39.50 | 27.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.729459E+10 | 13438.12 | 12-JAN-13:50 | 23.12 | 13.90 | 0.624781E+09 | 845.81 | 12-JAN-14:39 | 23.50 | 14.13 |
February | 0.864095E+10 | 24182.75 | 20-FEB-14:02 | 26.38 | 13.56 | 0.573468E+09 | 846.13 | 07-FEB-14:50 | 26.38 | 13.56 |
March | 0.136094E+11 | 23973.41 | 12-MAR-13:52 | 31.20 | 19.38 | 0.691011E+09 | 846.10 | 08-MAR-14:50 | 31.20 | 19.38 |
April | 0.163731E+11 | 24200.74 | 30-APR-15:41 | 37.82 | 18.21 | 0.614860E+09 | 845.97 | 06-APR-13:00 | 37.82 | 18.21 |
May | 0.163945E+11 | 22410.45 | 29-MAY-15:41 | 41.30 | 21.63 | 0.665946E+09 | 845.90 | 08-MAY-13:00 | 41.30 | 21.63 |
June | 0.161787E+11 | 23479.51 | 04-JUN-16:21 | 42.05 | 22.41 | 0.663513E+09 | 845.82 | 07-JUN-13:00 | 43.90 | 21.57 |
July | 0.156751E+11 | 24086.77 | 04-JUL-16:21 | 39.80 | 24.49 | 0.617399E+09 | 845.82 | 03-JUL-13:00 | 39.80 | 24.49 |
August | 0.168097E+11 | 22237.21 | 27-AUG-15:01 | 35.43 | 29.15 | 0.692226E+09 | 849.26 | 14-AUG-13:50 | 35.43 | 29.15 |
September | 0.142761E+11 | 23917.03 | 24-SEP-15:01 | 35.05 | 24.91 | 0.614744E+09 | 850.85 | 28-SEP-13:39 | 35.37 | 22.75 |
October | 0.165282E+11 | 25130.91 | 09-OCT-12:51 | 32.30 | 19.97 | 0.641039E+09 | 894.02 | 02-OCT-13:39 | 32.30 | 19.97 |
November | 0.140751E+11 | 23476.90 | 26-NOV-11:42 | 24.83 | 14.08 | 0.632889E+09 | 860.91 | 13-NOV-14:09 | 24.83 | 14.08 |
December | 0.926131E+10 | 22701.94 | 24-DEC-13:23 | 23.40 | 13.38 | 0.611189E+09 | 846.18 | 04-DEC-14:00 | 23.40 | 13.38 |
Annual Sum or Average | 0.165117E+12 | 0.764307E+10 | ||||||||
Minimum of Months | 0.729459E+10 | 13438.12 | 23.12 | 13.38 | 0.573468E+09 | 845.81 | 23.40 | 13.38 | ||
Maximum of Months | 0.168097E+11 | 25130.91 | 42.05 | 29.15 | 0.692226E+09 | 894.02 | 43.90 | 29.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364574E+10 | 7307.67 | 31-JAN-15:50 | 21.15 | 11.24 | 0.404783E+09 | 544.95 | 04-JAN-10:39 | 21.15 | 11.24 |
February | 0.556923E+10 | 23177.81 | 20-FEB-15:22 | 25.95 | 14.09 | 0.372659E+09 | 544.96 | 02-FEB-10:39 | 25.95 | 14.09 |
March | 0.113772E+11 | 24084.08 | 12-MAR-14:32 | 31.40 | 19.53 | 0.446310E+09 | 544.97 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.179024E+11 | 28686.47 | 30-APR-16:21 | 37.45 | 18.00 | 0.397114E+09 | 544.96 | 04-APR-09:20 | 37.45 | 18.00 |
May | 0.154969E+11 | 24687.91 | 28-MAY-16:21 | 42.00 | 19.52 | 0.429729E+09 | 544.95 | 08-MAY-13:20 | 42.00 | 19.52 |
June | 0.165638E+11 | 27574.57 | 04-JUN-16:21 | 42.05 | 22.41 | 0.428233E+09 | 544.96 | 05-JUN-13:20 | 42.30 | 22.45 |
July | 0.157545E+11 | 27527.02 | 04-JUL-16:21 | 39.80 | 24.49 | 0.398569E+09 | 544.95 | 11-JUL-09:20 | 28.23 | 25.15 |
August | 0.187336E+11 | 24612.36 | 06-AUG-16:21 | 36.15 | 26.34 | 0.446892E+09 | 548.09 | 14-AUG-13:50 | 32.52 | 27.52 |
September | 0.111654E+11 | 24960.69 | 24-SEP-15:01 | 35.05 | 24.91 | 0.396630E+09 | 544.95 | 08-SEP-13:20 | 35.05 | 24.91 |
October | 0.109930E+11 | 24997.08 | 15-OCT-15:21 | 32.35 | 19.26 | 0.412583E+09 | 544.95 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.866858E+10 | 19813.86 | 06-NOV-05:12 | 14.67 | 13.54 | 0.408228E+09 | 544.96 | 17-NOV-14:30 | 28.10 | 17.83 |
December | 0.671277E+10 | 18446.09 | 24-DEC-15:23 | 23.45 | 13.85 | 0.397245E+09 | 544.95 | 18-DEC-10:20 | 23.45 | 13.85 |
Annual Sum or Average | 0.142583E+12 | 0.493898E+10 | ||||||||
Minimum of Months | 0.364574E+10 | 7307.67 | 14.67 | 11.24 | 0.372659E+09 | 544.95 | 21.15 | 11.24 | ||
Maximum of Months | 0.187336E+11 | 28686.47 | 42.05 | 26.34 | 0.446892E+09 | 548.09 | 42.30 | 27.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190686E+10 | 2803.75 | 26-JAN-15:00 | 21.60 | 13.66 | 0.535138E+09 | 845.61 | 26-JAN-14:20 | 21.60 | 13.66 |
February | 0.272719E+10 | 5396.05 | 24-FEB-15:00 | 26.40 | 17.38 | 0.536507E+09 | 845.62 | 24-FEB-14:20 | 26.40 | 17.38 |
March | 0.623031E+10 | 12223.18 | 14-MAR-05:02 | 20.70 | 16.42 | 0.683421E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.108695E+11 | 21718.36 | 16-APR-15:21 | 39.50 | 22.49 | 0.613874E+09 | 845.63 | 04-APR-09:20 | 39.50 | 22.49 |
May | 0.153340E+11 | 22543.83 | 28-MAY-16:41 | 41.80 | 19.54 | 0.665899E+09 | 845.65 | 04-MAY-09:30 | 41.80 | 19.54 |
June | 0.155448E+11 | 23583.78 | 04-JUN-16:11 | 42.13 | 22.34 | 0.663585E+09 | 845.65 | 12-JUN-09:30 | 39.25 | 21.97 |
July | 0.141441E+11 | 22332.04 | 02-JUL-17:01 | 40.18 | 26.57 | 0.617481E+09 | 845.64 | 07-JUL-09:30 | 36.30 | 24.34 |
August | 0.133001E+11 | 21648.43 | 13-AUG-15:21 | 34.80 | 28.33 | 0.692015E+09 | 845.62 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.102945E+11 | 18933.70 | 01-SEP-03:02 | 27.13 | 25.13 | 0.614373E+09 | 845.62 | 08-SEP-13:20 | 28.50 | 25.85 |
October | 0.766887E+10 | 15775.51 | 02-OCT-04:12 | 21.73 | 17.70 | 0.636550E+09 | 845.62 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.405789E+10 | 5987.22 | 09-NOV-14:30 | 29.30 | 17.79 | 0.613910E+09 | 845.62 | 06-NOV-10:20 | 29.30 | 17.79 |
December | 0.224382E+10 | 2614.94 | 28-DEC-15:30 | 24.15 | 15.30 | 0.542074E+09 | 845.62 | 29-DEC-14:20 | 19.70 | 14.83 |
Annual Sum or Average | 0.104322E+12 | 0.741483E+10 | ||||||||
Minimum of Months | 0.190686E+10 | 2614.94 | 20.70 | 13.66 | 0.535138E+09 | 845.61 | 19.70 | 13.66 | ||
Maximum of Months | 0.155448E+11 | 23583.78 | 42.13 | 28.33 | 0.692015E+09 | 845.65 | 41.80 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145020E+10 | 5203.86 | 26-JAN-11:05 | 19.98 | 13.28 | 0.279736E+09 | 548.49 | 05-JAN-11:09 | 19.98 | 13.28 |
February | 0.271060E+10 | 8025.81 | 22-FEB-11:05 | 23.90 | 14.68 | 0.266730E+09 | 548.49 | 15-FEB-11:09 | 23.90 | 14.68 |
March | 0.643636E+10 | 16765.64 | 12-MAR-11:23 | 28.95 | 18.26 | 0.327372E+09 | 548.50 | 27-MAR-10:09 | 25.97 | 17.24 |
April | 0.106239E+11 | 19450.10 | 16-APR-09:22 | 33.85 | 21.42 | 0.293182E+09 | 548.66 | 28-APR-10:09 | 33.92 | 18.49 |
May | 0.134234E+11 | 19841.97 | 29-MAY-10:01 | 36.10 | 22.32 | 0.317553E+09 | 548.85 | 03-MAY-10:09 | 36.10 | 22.32 |
June | 0.121808E+11 | 19700.52 | 04-JUN-16:11 | 42.13 | 22.34 | 0.315873E+09 | 548.85 | 05-JUN-10:09 | 38.78 | 22.11 |
July | 0.104143E+11 | 18995.08 | 04-JUL-10:32 | 36.00 | 24.99 | 0.294932E+09 | 548.60 | 07-JUL-10:09 | 37.08 | 24.60 |
August | 0.966883E+10 | 17917.75 | 13-AUG-15:21 | 34.80 | 28.33 | 0.329241E+09 | 548.48 | 24-AUG-12:09 | 33.63 | 28.08 |
September | 0.821424E+10 | 17989.31 | 24-SEP-09:13 | 30.10 | 25.28 | 0.293003E+09 | 548.49 | 14-SEP-12:09 | 30.10 | 25.28 |
October | 0.715983E+10 | 18586.95 | 15-OCT-10:42 | 30.53 | 17.65 | 0.304493E+09 | 548.50 | 10-OCT-14:09 | 30.53 | 17.65 |
November | 0.399773E+10 | 8471.40 | 01-NOV-10:05 | 23.77 | 15.01 | 0.297864E+09 | 548.50 | 06-NOV-15:09 | 28.20 | 18.14 |
December | 0.178326E+10 | 5516.43 | 01-DEC-11:05 | 20.45 | 12.21 | 0.277805E+09 | 548.49 | 18-DEC-11:09 | 21.85 | 14.75 |
Annual Sum or Average | 0.880635E+11 | 0.359778E+10 | ||||||||
Minimum of Months | 0.145020E+10 | 5203.86 | 19.98 | 12.21 | 0.266730E+09 | 548.48 | 19.98 | 13.28 | ||
Maximum of Months | 0.134234E+11 | 19841.97 | 42.13 | 28.33 | 0.329241E+09 | 548.85 | 38.78 | 28.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.656657E+10 | 14902.80 | 08-JAN-15:53 | 22.20 | 14.15 | 0.612262E+09 | 845.89 | 12-JAN-14:20 | 23.40 | 14.05 |
February | 0.779671E+10 | 23398.80 | 19-FEB-14:42 | 25.87 | 14.25 | 0.566326E+09 | 846.47 | 23-FEB-14:20 | 26.20 | 13.97 |
March | 0.122499E+11 | 22727.75 | 05-MAR-13:23 | 28.45 | 17.08 | 0.689709E+09 | 848.62 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.145431E+11 | 22704.59 | 16-APR-15:21 | 39.50 | 22.49 | 0.614812E+09 | 846.64 | 04-APR-13:20 | 39.50 | 22.49 |
May | 0.161604E+11 | 22619.03 | 28-MAY-16:01 | 42.20 | 19.49 | 0.666048E+09 | 846.80 | 30-MAY-13:20 | 39.27 | 24.02 |
June | 0.153992E+11 | 23515.72 | 04-JUN-16:11 | 42.13 | 22.34 | 0.663592E+09 | 846.79 | 06-JUN-13:20 | 43.17 | 22.46 |
July | 0.142684E+11 | 22284.12 | 02-JUL-16:21 | 40.35 | 26.46 | 0.617516E+09 | 846.85 | 05-JUL-13:20 | 37.90 | 25.56 |
August | 0.142451E+11 | 21952.63 | 13-AUG-15:21 | 34.80 | 28.33 | 0.692199E+09 | 846.76 | 08-AUG-13:20 | 34.80 | 28.33 |
September | 0.135007E+11 | 22527.27 | 24-SEP-13:52 | 35.10 | 24.61 | 0.615190E+09 | 866.82 | 28-SEP-13:50 | 35.43 | 22.76 |
October | 0.158610E+11 | 25511.20 | 29-OCT-13:01 | 29.13 | 18.04 | 0.642077E+09 | 904.99 | 02-OCT-13:50 | 29.13 | 18.04 |
November | 0.132804E+11 | 25426.81 | 12-NOV-13:11 | 27.87 | 16.14 | 0.631717E+09 | 870.46 | 01-NOV-13:50 | 27.87 | 16.14 |
December | 0.777539E+10 | 23566.03 | 03-DEC-13:02 | 24.08 | 14.17 | 0.602906E+09 | 846.01 | 01-DEC-14:20 | 24.08 | 14.17 |
Annual Sum or Average | 0.151647E+12 | 0.761435E+10 | ||||||||
Minimum of Months | 0.656657E+10 | 14902.80 | 22.20 | 14.15 | 0.566326E+09 | 845.89 | 23.40 | 13.97 | ||
Maximum of Months | 0.161604E+11 | 25511.20 | 42.20 | 28.33 | 0.692199E+09 | 904.99 | 43.17 | 28.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197245E+10 | 5132.83 | 31-JAN-16:10 | 20.95 | 11.21 | 0.368790E+09 | 544.95 | 27-JAN-14:20 | 20.95 | 11.21 |
February | 0.298529E+10 | 11439.78 | 19-FEB-16:03 | 25.38 | 13.68 | 0.357244E+09 | 544.95 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.696846E+10 | 19377.39 | 12-MAR-16:02 | 31.18 | 19.88 | 0.444130E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.115168E+11 | 21981.54 | 30-APR-16:31 | 37.33 | 17.93 | 0.396518E+09 | 544.96 | 04-APR-09:20 | 37.33 | 17.93 |
May | 0.139436E+11 | 22758.05 | 28-MAY-16:01 | 42.20 | 19.49 | 0.429644E+09 | 544.97 | 04-MAY-09:30 | 42.20 | 19.49 |
June | 0.136135E+11 | 24644.09 | 04-JUN-16:11 | 42.13 | 22.34 | 0.428036E+09 | 544.97 | 12-JUN-09:30 | 39.25 | 21.97 |
July | 0.113019E+11 | 22109.07 | 02-JUL-16:21 | 40.35 | 26.46 | 0.398287E+09 | 544.96 | 07-JUL-09:30 | 36.30 | 24.34 |
August | 0.108449E+11 | 20926.13 | 06-AUG-16:21 | 36.15 | 26.34 | 0.446369E+09 | 544.95 | 21-AUG-13:20 | 29.43 | 27.58 |
September | 0.896953E+10 | 20554.84 | 17-SEP-15:52 | 34.10 | 26.13 | 0.396470E+09 | 544.95 | 08-SEP-13:20 | 34.10 | 26.13 |
October | 0.766422E+10 | 21906.90 | 15-OCT-15:21 | 32.35 | 19.26 | 0.411763E+09 | 544.95 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.462574E+10 | 20124.72 | 12-NOV-15:12 | 27.97 | 15.72 | 0.403007E+09 | 544.95 | 15-NOV-14:20 | 26.37 | 17.60 |
December | 0.235949E+10 | 5842.89 | 01-DEC-15:30 | 22.85 | 13.56 | 0.370526E+09 | 544.95 | 29-DEC-14:20 | 19.70 | 14.83 |
Annual Sum or Average | 0.967658E+11 | 0.485078E+10 | ||||||||
Minimum of Months | 0.197245E+10 | 5132.83 | 20.95 | 11.21 | 0.357244E+09 | 544.95 | 19.70 | 11.21 | ||
Maximum of Months | 0.139436E+11 | 24644.09 | 42.20 | 26.46 | 0.446369E+09 | 544.97 | 42.20 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146144E+10 | 2720.52 | 26-JAN-15:00 | 21.60 | 13.66 | 0.513266E+09 | 845.61 | 26-JAN-14:20 | 21.60 | 13.66 |
February | 0.241651E+10 | 5644.53 | 23-FEB-14:50 | 25.90 | 14.07 | 0.517775E+09 | 845.62 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.619368E+10 | 21452.10 | 12-MAR-15:41 | 31.33 | 19.85 | 0.676372E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.116037E+11 | 26438.94 | 30-APR-15:41 | 37.82 | 18.21 | 0.613873E+09 | 845.63 | 04-APR-09:20 | 37.82 | 18.21 |
May | 0.167088E+11 | 25935.34 | 28-MAY-16:41 | 41.80 | 19.54 | 0.666080E+09 | 845.62 | 08-MAY-13:20 | 41.80 | 19.54 |
June | 0.168076E+11 | 25709.21 | 11-JUN-15:41 | 43.37 | 23.26 | 0.663678E+09 | 845.63 | 05-JUN-13:20 | 43.37 | 23.26 |
July | 0.152128E+11 | 25647.79 | 02-JUL-17:01 | 40.18 | 26.57 | 0.617667E+09 | 845.61 | 10-JUL-09:20 | 33.27 | 26.53 |
August | 0.141163E+11 | 24991.84 | 13-AUG-15:31 | 34.80 | 28.33 | 0.692155E+09 | 845.61 | 28-AUG-09:20 | 31.07 | 27.59 |
September | 0.107437E+11 | 25763.38 | 24-SEP-15:31 | 34.90 | 25.12 | 0.614488E+09 | 845.61 | 08-SEP-13:20 | 34.90 | 25.12 |
October | 0.767788E+10 | 23957.59 | 09-OCT-16:01 | 32.13 | 20.30 | 0.634362E+09 | 845.62 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.367896E+10 | 6464.85 | 09-NOV-14:40 | 29.27 | 17.76 | 0.598595E+09 | 845.62 | 15-NOV-14:20 | 26.37 | 17.60 |
December | 0.175227E+10 | 2518.61 | 28-DEC-16:00 | 23.80 | 15.20 | 0.514317E+09 | 845.61 | 28-DEC-14:39 | 23.80 | 15.20 |
Annual Sum or Average | 0.108374E+12 | 0.732263E+10 | ||||||||
Minimum of Months | 0.146144E+10 | 2518.61 | 21.60 | 13.66 | 0.513266E+09 | 845.61 | 21.60 | 13.66 | ||
Maximum of Months | 0.168076E+11 | 26438.94 | 43.37 | 28.33 | 0.692155E+09 | 845.63 | 43.37 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138849E+10 | 2953.53 | 26-JAN-14:20 | 22.20 | 13.80 | 0.364102E+09 | 544.95 | 13-JAN-14:20 | 22.20 | 13.80 |
February | 0.257003E+10 | 6139.10 | 23-FEB-10:40 | 22.80 | 14.32 | 0.355989E+09 | 544.95 | 15-FEB-14:20 | 22.80 | 14.32 |
March | 0.659918E+10 | 19179.13 | 12-MAR-15:41 | 31.33 | 19.85 | 0.442982E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.114195E+11 | 22041.02 | 30-APR-09:41 | 30.90 | 15.93 | 0.396415E+09 | 545.24 | 28-APR-09:50 | 30.90 | 15.93 |
May | 0.146154E+11 | 20939.36 | 29-MAY-10:01 | 36.10 | 22.32 | 0.429631E+09 | 545.21 | 26-MAY-09:00 | 36.10 | 22.32 |
June | 0.132842E+11 | 20178.48 | 11-JUN-10:22 | 37.75 | 25.19 | 0.427925E+09 | 550.78 | 12-JUN-09:50 | 39.75 | 22.08 |
July | 0.113743E+11 | 19956.94 | 04-JUL-10:32 | 36.00 | 24.99 | 0.398235E+09 | 545.04 | 07-JUL-09:00 | 36.90 | 24.55 |
August | 0.104978E+11 | 19262.16 | 13-AUG-15:31 | 34.80 | 28.33 | 0.446223E+09 | 544.94 | 28-AUG-09:20 | 31.07 | 27.59 |
September | 0.877792E+10 | 20274.60 | 24-SEP-15:31 | 34.90 | 25.12 | 0.396266E+09 | 544.95 | 08-SEP-13:20 | 34.90 | 25.12 |
October | 0.736925E+10 | 19439.96 | 09-OCT-10:42 | 29.52 | 20.50 | 0.410995E+09 | 544.95 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.382856E+10 | 6410.20 | 09-NOV-10:20 | 25.33 | 18.04 | 0.400392E+09 | 544.96 | 06-NOV-14:50 | 25.33 | 18.04 |
December | 0.156853E+10 | 2987.88 | 01-DEC-14:40 | 23.43 | 13.26 | 0.365376E+09 | 544.95 | 29-DEC-14:20 | 19.70 | 14.83 |
Annual Sum or Average | 0.932932E+11 | 0.483453E+10 | ||||||||
Minimum of Months | 0.138849E+10 | 2953.53 | 22.20 | 13.26 | 0.355989E+09 | 544.94 | 19.70 | 13.80 | ||
Maximum of Months | 0.146154E+11 | 22041.02 | 37.75 | 28.33 | 0.446223E+09 | 550.78 | 39.75 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.541966E+10 | 13331.22 | 12-JAN-14:20 | 23.40 | 14.05 | 0.593819E+09 | 845.64 | 25-JAN-14:50 | 22.98 | 13.31 |
February | 0.703363E+10 | 26890.29 | 20-FEB-14:12 | 26.37 | 13.66 | 0.554868E+09 | 845.94 | 22-FEB-14:00 | 27.10 | 16.20 |
March | 0.120842E+11 | 27246.95 | 12-MAR-13:42 | 31.12 | 19.32 | 0.686367E+09 | 846.07 | 08-MAR-14:50 | 31.12 | 19.32 |
April | 0.153380E+11 | 27833.26 | 30-APR-15:41 | 37.82 | 18.21 | 0.614784E+09 | 845.95 | 21-APR-13:00 | 37.82 | 18.21 |
May | 0.175416E+11 | 25981.00 | 28-MAY-16:01 | 42.20 | 19.49 | 0.666193E+09 | 845.92 | 08-MAY-13:00 | 42.20 | 19.49 |
June | 0.166573E+11 | 25628.45 | 11-JUN-15:41 | 43.37 | 23.26 | 0.663676E+09 | 845.81 | 12-JUN-13:50 | 43.80 | 22.37 |
July | 0.153326E+11 | 25553.18 | 02-JUL-16:21 | 40.35 | 26.46 | 0.617691E+09 | 845.75 | 05-JUL-13:00 | 37.90 | 25.56 |
August | 0.150716E+11 | 25297.94 | 13-AUG-14:51 | 34.80 | 28.33 | 0.692318E+09 | 845.81 | 07-AUG-13:00 | 34.80 | 28.33 |
September | 0.139651E+11 | 27689.28 | 24-SEP-15:31 | 34.90 | 25.12 | 0.615057E+09 | 845.99 | 19-SEP-13:00 | 34.90 | 25.12 |
October | 0.157666E+11 | 28471.45 | 29-OCT-13:31 | 29.23 | 17.90 | 0.639696E+09 | 879.96 | 02-OCT-13:50 | 29.23 | 17.90 |
November | 0.124395E+11 | 28355.61 | 05-NOV-13:41 | 29.32 | 17.20 | 0.626456E+09 | 846.05 | 15-NOV-14:00 | 26.50 | 17.83 |
December | 0.641598E+10 | 19872.02 | 24-DEC-14:43 | 24.38 | 14.05 | 0.588072E+09 | 845.80 | 01-DEC-14:39 | 24.38 | 14.05 |
Annual Sum or Average | 0.153066E+12 | 0.755900E+10 | ||||||||
Minimum of Months | 0.541966E+10 | 13331.22 | 23.40 | 13.66 | 0.554868E+09 | 845.64 | 22.98 | 13.31 | ||
Maximum of Months | 0.175416E+11 | 28471.45 | 43.37 | 28.33 | 0.692318E+09 | 879.96 | 43.80 | 28.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167028E+10 | 5033.64 | 12-JAN-15:50 | 23.35 | 14.44 | 0.355470E+09 | 544.95 | 13-JAN-14:20 | 21.30 | 15.27 |
February | 0.274287E+10 | 19038.77 | 20-FEB-16:12 | 25.27 | 14.30 | 0.347178E+09 | 544.95 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.690598E+10 | 23948.50 | 12-MAR-16:21 | 30.95 | 19.85 | 0.441685E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.120164E+11 | 27178.31 | 30-APR-15:41 | 37.82 | 18.21 | 0.396547E+09 | 544.96 | 04-APR-09:20 | 37.82 | 18.21 |
May | 0.148598E+11 | 25183.97 | 28-MAY-16:01 | 42.20 | 19.49 | 0.429695E+09 | 544.95 | 08-MAY-13:20 | 42.20 | 19.49 |
June | 0.144242E+11 | 24591.41 | 11-JUN-15:41 | 43.37 | 23.26 | 0.428046E+09 | 544.96 | 05-JUN-13:20 | 43.37 | 23.26 |
July | 0.119752E+11 | 24421.37 | 02-JUL-16:21 | 40.35 | 26.46 | 0.398357E+09 | 544.94 | 10-JUL-09:20 | 33.27 | 26.53 |
August | 0.113258E+11 | 23336.05 | 06-AUG-16:21 | 36.15 | 26.34 | 0.446407E+09 | 544.94 | 28-AUG-09:20 | 31.07 | 27.59 |
September | 0.927310E+10 | 25278.48 | 24-SEP-15:31 | 34.90 | 25.12 | 0.396480E+09 | 544.95 | 08-SEP-13:20 | 34.90 | 25.12 |
October | 0.763867E+10 | 23883.60 | 09-OCT-16:01 | 32.13 | 20.30 | 0.411188E+09 | 544.95 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.432032E+10 | 21964.81 | 05-NOV-15:42 | 28.08 | 17.72 | 0.396799E+09 | 544.96 | 06-NOV-14:50 | 28.48 | 18.19 |
December | 0.196411E+10 | 5714.87 | 28-DEC-15:40 | 24.03 | 15.27 | 0.355701E+09 | 544.95 | 29-DEC-14:20 | 19.70 | 14.83 |
Annual Sum or Average | 0.991167E+11 | 0.480355E+10 | ||||||||
Minimum of Months | 0.167028E+10 | 5033.64 | 23.35 | 14.30 | 0.347178E+09 | 544.94 | 19.70 | 14.83 | ||
Maximum of Months | 0.148598E+11 | 27178.31 | 43.37 | 26.46 | 0.446407E+09 | 544.96 | 43.37 | 27.59 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165903E+10 | 3117.44 | 12-JAN-17:00 | 22.30 | 14.53 | 0.00 | 0.00 | 01-JAN-00:10 | 22.30 | 14.53 |
February | 0.389306E+10 | 8952.39 | 21-FEB-06:15 | 11.70 | 10.89 | 0.00 | 0.00 | 01-FEB-00:10 | 11.70 | 10.89 |
March | 0.923886E+10 | 10479.45 | 13-MAR-16:00 | 32.50 | 18.65 | 0.00 | 0.00 | 01-MAR-00:10 | 32.50 | 18.65 |
April | 0.147384E+11 | 19076.24 | 17-APR-05:15 | 24.33 | 18.88 | 0.00 | 0.00 | 01-APR-00:10 | 24.33 | 18.88 |
May | 0.171437E+11 | 23115.79 | 30-MAY-05:15 | 30.30 | 21.64 | 0.00 | 0.00 | 01-MAY-00:10 | 30.30 | 21.64 |
June | 0.170075E+11 | 22023.47 | 12-JUN-05:15 | 34.23 | 19.16 | 0.00 | 0.00 | 01-JUN-00:10 | 34.23 | 19.16 |
July | 0.161181E+11 | 22792.22 | 05-JUL-05:25 | 32.70 | 24.64 | 0.00 | 0.00 | 01-JUL-00:10 | 32.70 | 24.64 |
August | 0.168521E+11 | 21051.34 | 07-AUG-05:13 | 29.57 | 24.74 | 0.00 | 0.00 | 01-AUG-00:10 | 29.57 | 24.74 |
September | 0.120015E+11 | 19059.40 | 18-SEP-05:15 | 26.73 | 24.13 | 0.00 | 0.00 | 01-SEP-00:10 | 26.73 | 24.13 |
October | 0.112742E+11 | 15746.90 | 10-OCT-05:15 | 19.90 | 18.09 | 0.00 | 0.00 | 01-OCT-00:10 | 19.90 | 18.09 |
November | 0.757802E+10 | 11585.52 | 13-NOV-06:15 | 15.27 | 12.05 | 0.00 | 0.00 | 01-NOV-00:10 | 15.27 | 12.05 |
December | 0.382859E+10 | 6896.61 | 26-DEC-06:15 | 10.23 | 8.49 | 0.00 | 0.00 | 01-DEC-00:10 | 10.23 | 8.49 |
Annual Sum or Average | 0.131333E+12 | 0.00 | ||||||||
Minimum of Months | 0.165903E+10 | 3117.44 | 10.23 | 8.49 | 0.00 | 0.00 | 10.23 | 8.49 | ||
Maximum of Months | 0.171437E+11 | 23115.79 | 34.23 | 24.74 | 0.00 | 0.00 | 34.23 | 24.74 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.560097E+09 | 2905.89 | 04-JAN-06:02 | 5.65 | 5.27 | 0.00 | 0.00 | 01-JAN-00:10 | 5.65 | 5.27 |
February | 0.196113E+10 | 4979.05 | 22-FEB-16:50 | 25.83 | 15.78 | 0.00 | 0.00 | 01-FEB-00:10 | 25.83 | 15.78 |
March | 0.668209E+10 | 9099.66 | 29-MAR-16:00 | 32.90 | 18.66 | 0.00 | 0.00 | 01-MAR-00:10 | 32.90 | 18.66 |
April | 0.118312E+11 | 14818.14 | 17-APR-05:03 | 24.22 | 18.83 | 0.00 | 0.00 | 01-APR-00:10 | 24.22 | 18.83 |
May | 0.156108E+11 | 18113.41 | 30-MAY-05:15 | 30.30 | 21.64 | 0.00 | 0.00 | 01-MAY-00:10 | 30.30 | 21.64 |
June | 0.151686E+11 | 19268.98 | 12-JUN-05:15 | 34.23 | 19.16 | 0.00 | 0.00 | 01-JUN-00:10 | 34.23 | 19.16 |
July | 0.134909E+11 | 19052.34 | 05-JUL-05:13 | 32.63 | 24.69 | 0.00 | 0.00 | 01-JUL-00:10 | 32.63 | 24.69 |
August | 0.127730E+11 | 15606.78 | 07-AUG-05:13 | 29.57 | 24.74 | 0.00 | 0.00 | 01-AUG-00:10 | 29.57 | 24.74 |
September | 0.103064E+11 | 12421.23 | 18-SEP-05:02 | 26.72 | 24.18 | 0.00 | 0.00 | 01-SEP-00:10 | 26.72 | 24.18 |
October | 0.909856E+10 | 13016.54 | 10-OCT-05:02 | 19.80 | 18.03 | 0.00 | 0.00 | 01-OCT-00:10 | 19.80 | 18.03 |
November | 0.478445E+10 | 6829.52 | 09-NOV-16:20 | 28.03 | 17.54 | 0.00 | 0.00 | 01-NOV-00:10 | 28.03 | 17.54 |
December | 0.119236E+10 | 3130.75 | 01-DEC-06:10 | 11.02 | 8.79 | 0.00 | 0.00 | 01-DEC-00:10 | 11.02 | 8.79 |
Annual Sum or Average | 0.103460E+12 | 0.00 | ||||||||
Minimum of Months | 0.560097E+09 | 2905.89 | 5.65 | 5.27 | 0.00 | 0.00 | 5.65 | 5.27 | ||
Maximum of Months | 0.156108E+11 | 19268.98 | 34.23 | 24.74 | 0.00 | 0.00 | 34.23 | 24.74 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106049E+10 | 5914.31 | 12-JAN-15:00 | 23.60 | 14.20 | 0.00 | 0.00 | 01-JAN-00:10 | 23.60 | 14.20 |
February | 0.337486E+10 | 13335.63 | 22-FEB-15:05 | 27.00 | 16.16 | 0.00 | 0.00 | 01-FEB-00:10 | 27.00 | 16.16 |
March | 0.105450E+11 | 22319.93 | 28-MAR-15:40 | 35.53 | 18.66 | 0.00 | 0.00 | 01-MAR-00:10 | 35.53 | 18.66 |
April | 0.201007E+11 | 28028.53 | 28-APR-15:00 | 39.20 | 20.99 | 0.00 | 0.00 | 01-APR-00:10 | 39.20 | 20.99 |
May | 0.268443E+11 | 32189.29 | 01-MAY-14:20 | 43.93 | 22.01 | 0.00 | 0.00 | 01-MAY-00:10 | 43.93 | 22.01 |
June | 0.267018E+11 | 34081.56 | 12-JUN-13:50 | 43.80 | 22.37 | 0.00 | 0.00 | 01-JUN-00:10 | 43.80 | 22.37 |
July | 0.216915E+11 | 30271.21 | 07-JUL-14:00 | 40.30 | 24.54 | 0.00 | 0.00 | 01-JUL-00:10 | 40.30 | 24.54 |
August | 0.197853E+11 | 26903.94 | 07-AUG-14:40 | 37.27 | 26.48 | 0.00 | 0.00 | 01-AUG-00:10 | 37.27 | 26.48 |
September | 0.152526E+11 | 22746.89 | 26-SEP-15:00 | 36.10 | 22.69 | 0.00 | 0.00 | 01-SEP-00:10 | 36.10 | 22.69 |
October | 0.126760E+11 | 22057.43 | 02-OCT-14:20 | 36.40 | 21.05 | 0.00 | 0.00 | 01-OCT-00:10 | 36.40 | 21.05 |
November | 0.618871E+10 | 14556.37 | 09-NOV-14:40 | 29.27 | 17.76 | 0.00 | 0.00 | 01-NOV-00:10 | 29.27 | 17.76 |
December | 0.154849E+10 | 7579.94 | 01-DEC-14:40 | 23.43 | 13.26 | 0.00 | 0.00 | 01-DEC-00:10 | 23.43 | 13.26 |
Annual Sum or Average | 0.165770E+12 | 0.00 | ||||||||
Minimum of Months | 0.106049E+10 | 5914.31 | 23.43 | 13.26 | 0.00 | 0.00 | 23.43 | 13.26 | ||
Maximum of Months | 0.268443E+11 | 34081.56 | 43.93 | 26.48 | 0.00 | 0.00 | 43.93 | 26.48 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.375098E+10 | 1831.46 | 12-JAN-17:00 | 22.30 | 14.53 | 95236461.13 | 126.84 | 18-JAN-14:20 | 17.97 | 14.61 |
February | 0.836301E+10 | 3967.83 | 20-FEB-17:37 | 23.53 | 14.36 | 86404200.33 | 126.84 | 09-FEB-14:00 | 23.53 | 14.36 |
March | 0.146427E+11 | 7218.55 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 29-MAR-09:09 | 23.70 | 16.75 |
April | 0.193038E+11 | 7875.61 | 17-APR-00:23 | 26.75 | 20.02 | 94175555.29 | 142.19 | 27-APR-13:00 | 39.60 | 19.54 |
May | 0.489782E+10 | 3531.25 | 31-MAY-23:53 | 28.10 | 22.60 | 99238870.22 | 126.85 | 30-MAY-13:09 | 28.10 | 22.60 |
June | 0.960349E+10 | 5476.55 | 30-JUN-24:00 | 33.10 | 24.67 | 98979766.25 | 126.88 | 27-JUN-09:09 | 33.10 | 24.67 |
July | 0.149774E+11 | 7370.14 | 31-JUL-23:57 | 29.40 | 26.34 | 91894390.05 | 126.85 | 28-JUL-09:09 | 29.40 | 26.34 |
August | 0.198064E+11 | 7674.39 | 20-AUG-18:35 | 26.23 | 25.45 | 0.110196E+09 | 148.58 | 07-AUG-13:00 | 26.23 | 25.45 |
September | 0.459304E+10 | 3526.81 | 30-SEP-24:00 | 26.60 | 21.92 | 91605534.55 | 126.85 | 27-SEP-13:09 | 26.60 | 21.92 |
October | 0.975795E+10 | 5382.02 | 31-OCT-24:00 | 17.80 | 15.13 | 95245081.73 | 126.86 | 06-OCT-09:00 | 17.80 | 15.13 |
November | 0.141583E+11 | 5889.76 | 12-NOV-16:25 | 26.95 | 15.49 | 94305414.74 | 126.84 | 10-NOV-10:09 | 26.95 | 15.49 |
December | 0.193674E+11 | 7566.16 | 28-DEC-17:00 | 22.80 | 14.91 | 91882579.28 | 126.83 | 11-DEC-10:09 | 22.80 | 14.91 |
Annual Sum or Average | 0.143222E+12 | 0.115241E+10 | ||||||||
Minimum of Months | 0.375098E+10 | 1831.46 | 17.80 | 14.36 | 86404200.33 | 126.83 | 17.80 | 14.36 | ||
Maximum of Months | 0.198064E+11 | 7875.61 | 33.10 | 26.34 | 0.110196E+09 | 148.58 | 39.60 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226916E+10 | 1670.37 | 12-JAN-17:00 | 22.30 | 14.53 | 95217511.73 | 126.84 | 13-JAN-14:00 | 21.50 | 15.25 |
February | 0.730847E+10 | 3588.62 | 21-FEB-17:00 | 25.40 | 15.70 | 86403173.54 | 126.84 | 09-FEB-14:00 | 25.40 | 15.70 |
March | 0.137911E+11 | 6972.05 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103241E+09 | 126.84 | 29-MAR-09:09 | 23.70 | 16.75 |
April | 0.181573E+11 | 7280.15 | 16-APR-22:23 | 27.65 | 19.99 | 95345195.55 | 144.43 | 27-APR-13:00 | 39.60 | 19.54 |
May | 0.458383E+10 | 3403.97 | 31-MAY-23:53 | 28.10 | 22.60 | 99238358.35 | 126.85 | 30-MAY-13:09 | 28.10 | 22.60 |
June | 0.911611E+10 | 5262.31 | 30-JUN-24:00 | 33.10 | 24.67 | 98978308.91 | 126.87 | 27-JUN-09:00 | 33.10 | 24.67 |
July | 0.141944E+11 | 6941.54 | 31-JUL-23:53 | 29.40 | 26.34 | 91893672.54 | 126.85 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.184757E+11 | 7134.55 | 20-AUG-17:55 | 26.30 | 25.51 | 0.111527E+09 | 148.56 | 07-AUG-13:00 | 26.30 | 25.51 |
September | 0.421948E+10 | 3400.01 | 30-SEP-23:50 | 26.60 | 21.97 | 91605382.39 | 126.82 | 27-SEP-13:09 | 26.60 | 21.97 |
October | 0.915001E+10 | 5090.60 | 31-OCT-24:00 | 17.80 | 15.13 | 95243404.04 | 126.86 | 13-OCT-09:09 | 17.80 | 15.13 |
November | 0.130798E+11 | 5435.29 | 08-NOV-16:40 | 28.33 | 18.82 | 94304689.71 | 126.83 | 09-NOV-10:09 | 24.92 | 17.98 |
December | 0.174664E+11 | 7161.21 | 01-DEC-17:00 | 21.20 | 14.26 | 91882313.45 | 126.83 | 11-DEC-10:09 | 8.92 | 8.81 |
Annual Sum or Average | 0.131812E+12 | 0.115488E+10 | ||||||||
Minimum of Months | 0.226916E+10 | 1670.37 | 17.80 | 14.26 | 86403173.54 | 126.82 | 8.92 | 8.81 | ||
Maximum of Months | 0.184757E+11 | 7280.15 | 33.10 | 26.34 | 0.111527E+09 | 148.56 | 39.60 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129282E+10 | 1696.65 | 12-JAN-17:00 | 22.30 | 14.53 | 94699611.94 | 128.55 | 23-JAN-10:09 | 12.65 | 9.23 |
February | 0.667931E+10 | 3638.47 | 22-FEB-17:00 | 25.70 | 15.75 | 86403875.41 | 126.84 | 09-FEB-14:00 | 25.70 | 15.75 |
March | 0.136220E+11 | 6926.57 | 31-MAR-23:55 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 29-MAR-09:09 | 23.70 | 16.75 |
April | 0.183270E+11 | 7546.90 | 16-APR-21:32 | 28.07 | 20.03 | 93947604.41 | 141.98 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.479134E+10 | 3349.95 | 31-MAY-23:53 | 28.10 | 22.60 | 99238902.34 | 126.85 | 30-MAY-13:09 | 28.10 | 22.60 |
June | 0.930349E+10 | 5331.85 | 30-JUN-24:00 | 33.10 | 24.67 | 98979660.19 | 126.88 | 26-JUN-09:00 | 33.10 | 24.67 |
July | 0.143938E+11 | 7060.90 | 31-JUL-23:57 | 29.40 | 26.34 | 91895448.51 | 126.85 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.188109E+11 | 7366.17 | 20-AUG-17:33 | 26.43 | 25.55 | 0.108396E+09 | 146.01 | 07-AUG-13:00 | 26.43 | 25.55 |
September | 0.429847E+10 | 3417.94 | 30-SEP-23:40 | 26.60 | 22.02 | 91605410.05 | 126.82 | 27-SEP-13:09 | 26.60 | 22.02 |
October | 0.906605E+10 | 4959.07 | 31-OCT-24:00 | 17.80 | 15.13 | 95244521.91 | 126.86 | 06-OCT-09:00 | 17.80 | 15.13 |
November | 0.125937E+11 | 5481.76 | 09-NOV-16:40 | 27.67 | 17.53 | 94305417.27 | 126.83 | 09-NOV-10:09 | 27.67 | 17.53 |
December | 0.163396E+11 | 7166.87 | 28-DEC-17:00 | 22.80 | 14.91 | 91882913.69 | 126.83 | 11-DEC-10:09 | 22.80 | 14.91 |
Annual Sum or Average | 0.129518E+12 | 0.114984E+10 | ||||||||
Minimum of Months | 0.129282E+10 | 1696.65 | 17.80 | 14.53 | 86403875.41 | 126.82 | 12.65 | 9.23 | ||
Maximum of Months | 0.188109E+11 | 7546.90 | 33.10 | 26.34 | 0.108396E+09 | 146.01 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240125E+12 | 92210.78 | 26-JAN-17:00 | 18.60 | 12.70 | 0.206234E+10 | 2748.29 | 26-JAN-10:09 | 18.60 | 12.70 |
February | 0.437071E+12 | 183793.54 | 21-FEB-17:00 | 25.40 | 15.70 | 0.187099E+10 | 2749.18 | 09-FEB-14:09 | 25.40 | 15.70 |
March | 0.729231E+12 | 358632.65 | 31-MAR-23:55 | 23.70 | 16.75 | 0.223523E+10 | 2749.92 | 21-MAR-09:09 | 23.70 | 16.75 |
April | 0.934433E+12 | 368926.98 | 30-APR-04:53 | 22.70 | 16.37 | 0.240977E+10 | 4019.32 | 28-APR-13:00 | 22.70 | 16.37 |
May | 0.242404E+12 | 176148.05 | 31-MAY-23:53 | 28.10 | 22.60 | 0.214879E+10 | 2747.24 | 24-MAY-09:09 | 28.10 | 22.60 |
June | 0.472005E+12 | 268359.73 | 30-JUN-23:53 | 33.10 | 24.67 | 0.214273E+10 | 2746.91 | 27-JUN-09:09 | 33.10 | 24.67 |
July | 0.735225E+12 | 356945.93 | 31-JUL-23:13 | 29.40 | 26.34 | 0.198925E+10 | 2746.00 | 18-JUL-09:09 | 29.40 | 26.34 |
August | 0.967079E+12 | 369732.45 | 15-AUG-23:53 | 23.40 | 22.91 | 0.294209E+10 | 4097.70 | 07-AUG-13:00 | 23.40 | 22.91 |
September | 0.239178E+12 | 177625.41 | 30-SEP-24:00 | 26.60 | 21.92 | 0.198362E+10 | 2747.27 | 01-SEP-09:09 | 26.60 | 21.92 |
October | 0.490352E+12 | 269348.56 | 31-OCT-24:00 | 17.80 | 15.13 | 0.206189E+10 | 2746.43 | 13-OCT-09:09 | 17.80 | 15.13 |
November | 0.710794E+12 | 277063.71 | 13-NOV-17:00 | 26.40 | 16.65 | 0.204190E+10 | 2749.50 | 28-NOV-10:09 | 18.13 | 13.76 |
December | 0.978234E+12 | 368199.74 | 18-DEC-17:00 | 20.00 | 14.42 | 0.199047E+10 | 2817.33 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.717613E+13 | 0.258791E+11 | ||||||||
Minimum of Months | 0.239178E+12 | 92210.78 | 17.80 | 12.70 | 0.187099E+10 | 2746.00 | 17.80 | 12.70 | ||
Maximum of Months | 0.978234E+12 | 369732.45 | 33.10 | 26.34 | 0.294209E+10 | 4097.70 | 33.10 | 26.34 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2746512.67 | 2188.43 | 14-JAN-17:03 | 20.55 |
February | 49984420.76 | 10133.21 | 20-FEB-14:03 | 26.38 |
March | 0.122293E+09 | 15903.13 | 11-MAR-17:01 | 29.70 |
April | 0.427884E+09 | 29926.19 | 15-APR-16:01 | 39.58 |
May | 0.588326E+09 | 33278.91 | 27-MAY-16:01 | 42.00 |
June | 0.648987E+09 | 35117.00 | 10-JUN-16:01 | 43.12 |
July | 0.754727E+09 | 29446.29 | 02-JUL-16:20 | 40.37 |
August | 0.448697E+09 | 24581.22 | 05-AUG-16:01 | 35.70 |
September | 0.669837E+09 | 22896.19 | 30-SEP-16:01 | 34.78 |
October | 0.481621E+09 | 22411.00 | 01-OCT-15:13 | 35.83 |
November | 0.151434E+09 | 14936.25 | 11-NOV-14:42 | 28.45 |
December | 15510492.90 | 6099.84 | 25-DEC-14:07 | 24.43 |
Annual Sum or Average | 0.436205E+10 | |||
Minimum of Months | 2746512.67 | 2188.43 | 20.55 | |
Maximum of Months | 0.754727E+09 | 35117.00 | 43.12 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2281333.74 | 15208.89 | 02-JAN-06:03 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 2281333.74 | |||
Minimum of Months | 0.00 | 0.00 | 6.45 | |
Maximum of Months | 2281333.74 | 15208.89 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.575360E+09 | 70817.91 | 02-JAN-05:11 | 6.47 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.575360E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 0.575360E+09 | 70817.91 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 918335.51 | 4205.04 | 02-JAN-06:03 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 918335.51 | |||
Minimum of Months | 0.00 | 0.00 | 6.45 | |
Maximum of Months | 918335.51 | 4205.04 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279631E+09 | 15911.02 | 02-JAN-05:11 | 6.47 |
February | 13589960.23 | 11334.87 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 43114767.41 | 14203.51 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.336336E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.279631E+09 | 15911.02 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 92397124.21 | 11246.31 | 02-JAN-05:11 | 6.47 |
February | 3374317.78 | 8449.70 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 11309197.03 | 6754.96 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.107081E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 92397124.21 | 11246.31 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43962449.78 | 14867.42 | 02-JAN-05:11 | 6.47 |
February | 4573116.59 | 10841.58 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 48535566.37 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 43962449.78 | 14867.42 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 48511028.65 | 10214.13 | 02-JAN-05:11 | 6.47 |
February | 1771521.99 | 4287.97 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 3750498.80 | 3994.82 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 54033049.44 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 48511028.65 | 10214.13 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123795E+10 | 20383.41 | 02-JAN-05:11 | 6.47 |
February | 0.208058E+09 | 17008.78 | 03-FEB-06:02 | 8.48 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 14687997.46 | 9759.06 | 27-NOV-06:03 | 9.55 |
December | 0.539536E+09 | 18321.66 | 22-DEC-05:12 | 11.37 |
Annual Sum or Average | 0.200024E+10 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 0.123795E+10 | 20383.41 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.483866E+09 | 14310.28 | 02-JAN-05:11 | 6.47 |
February | 70270222.05 | 11599.27 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 590216.19 | 512.29 | 27-NOV-06:03 | 9.55 |
December | 0.186807E+09 | 12588.91 | 22-DEC-05:12 | 11.37 |
Annual Sum or Average | 0.741534E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 0.483866E+09 | 14310.28 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404066E+09 | 20011.66 | 02-JAN-05:11 | 6.47 |
February | 66607038.10 | 16749.31 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 96100217.43 | 16644.99 | 30-DEC-06:02 | 10.48 |
Annual Sum or Average | 0.566774E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.47 | |
Maximum of Months | 0.404066E+09 | 20011.66 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374951E+09 | 14378.99 | 02-JAN-05:11 | 6.47 |
February | 47330053.93 | 11509.81 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.105008E+09 | 10613.27 | 23-DEC-05:12 | 5.10 |
Annual Sum or Average | 0.527289E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.10 | |
Maximum of Months | 0.374951E+09 | 14378.99 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 85647460.78 | 11273.15 | 02-JAN-05:11 | 6.47 |
February | 94806079.46 | 9442.29 | 11-FEB-06:02 | 9.30 |
March | 63810138.83 | 8280.00 | 20-MAR-04:12 | 15.40 |
April | 48010342.73 | 6656.66 | 02-APR-15:02 | 33.82 |
May | 28938752.19 | 5509.06 | 14-MAY-15:42 | 36.18 |
June | 29923922.02 | 7586.27 | 04-JUN-15:01 | 42.30 |
July | 36622848.24 | 5361.87 | 30-JUL-14:22 | 34.60 |
August | 43895550.15 | 6338.58 | 27-AUG-13:42 | 35.50 |
September | 28314081.56 | 6155.73 | 08-SEP-03:02 | 25.00 |
October | 57605075.09 | 6729.92 | 15-OCT-14:41 | 32.65 |
November | 91871486.17 | 8928.60 | 27-NOV-05:12 | 9.77 |
December | 0.176089E+09 | 12090.41 | 11-DEC-05:12 | 10.13 |
Annual Sum or Average | 0.785535E+09 | |||
Minimum of Months | 28314081.56 | 5361.87 | 6.47 | |
Maximum of Months | 0.176089E+09 | 12090.41 | 42.30 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.943945E+09 | 6931.16 | 25-JAN-06:02 | 10.10 |
February | 0.134246E+09 | 7168.09 | 10-FEB-06:02 | 12.33 |
March | 42549999.85 | 5767.68 | 26-MAR-16:12 | 29.73 |
April | 31054029.17 | 6184.25 | 16-APR-15:21 | 39.50 |
May | 32280055.53 | 6002.93 | 28-MAY-16:01 | 42.20 |
June | 27568312.14 | 7453.80 | 04-JUN-16:12 | 42.13 |
July | 38671469.54 | 5646.88 | 02-JUL-16:21 | 40.35 |
August | 27916436.87 | 6433.14 | 13-AUG-15:21 | 34.80 |
September | 26867077.71 | 6233.01 | 11-SEP-03:02 | 26.07 |
October | 47166638.79 | 6329.11 | 15-OCT-14:01 | 32.85 |
November | 55410127.55 | 5528.12 | 28-NOV-05:12 | 15.20 |
December | 0.192959E+09 | 6703.99 | 13-DEC-06:03 | 11.83 |
Annual Sum or Average | 0.160063E+10 | |||
Minimum of Months | 26867077.71 | 5528.12 | 10.10 | |
Maximum of Months | 0.943945E+09 | 7453.80 | 42.20 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265016E+10 | 23616.61 | 02-JAN-06:03 | 6.45 |
February | 0.123122E+10 | 14561.29 | 24-FEB-06:03 | 15.00 |
March | 0.449288E+09 | 14957.84 | 31-MAR-05:03 | 16.93 |
April | 51126353.56 | 13970.31 | 10-APR-04:11 | 18.47 |
May | 6455277.47 | 6636.25 | 25-MAY-03:02 | 26.60 |
June | 5192389.92 | 6456.11 | 01-JUN-03:02 | 27.32 |
July | 5175663.56 | 6449.39 | 19-JUL-04:03 | 24.72 |
August | 6701845.14 | 6457.01 | 21-AUG-03:02 | 25.87 |
September | 20413635.75 | 7551.76 | 11-SEP-03:02 | 26.07 |
October | 0.198622E+09 | 13587.04 | 31-OCT-05:03 | 15.53 |
November | 0.779309E+09 | 15137.19 | 14-NOV-06:03 | 14.57 |
December | 0.192232E+10 | 8865.56 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.732598E+10 | |||
Minimum of Months | 5175663.56 | 6449.39 | 5.43 | |
Maximum of Months | 0.265016E+10 | 23616.61 | 27.32 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16762035.47 | 272.28 | 01-JAN-12:50 | 14.73 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 16762035.47 | |||
Minimum of Months | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 16762035.47 | 272.28 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131828E+09 | 352.88 | 01-JAN-13:45 | 16.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.131828E+09 | |||
Minimum of Months | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 0.131828E+09 | 352.88 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:05 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.940365E+09 | 1365.60 | 18-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.829509E+09 | 1334.84 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.940812E+09 | 1347.93 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.822203E+09 | 871.10 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.869443E+09 | 927.00 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.866259E+09 | 925.30 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.826987E+09 | 1292.19 | 26-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.931486E+09 | 1338.07 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.847034E+09 | 1384.03 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.901842E+09 | 1465.83 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.923986E+09 | 1426.82 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.923300E+09 | 1441.86 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106232E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.822203E+09 | 871.10 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.940812E+09 | 1465.83 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.597426E+09 | 870.03 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.530331E+09 | 865.23 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.603430E+09 | 754.29 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.529216E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.562928E+09 | 578.13 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.560508E+09 | 578.51 | 23-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.533564E+09 | 800.32 | 26-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.599338E+09 | 832.44 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.543714E+09 | 864.82 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.575445E+09 | 927.86 | 11-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.591249E+09 | 941.67 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.587244E+09 | 936.94 | 29-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.681439E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.529216E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.603430E+09 | 941.67 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.906505E+09 | 1307.00 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.812138E+09 | 1288.00 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.935193E+09 | 1330.25 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.823964E+09 | 880.11 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.876436E+09 | 1069.79 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.873021E+09 | 1081.30 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.833058E+09 | 1313.45 | 26-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.933849E+09 | 1347.51 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.844613E+09 | 1381.27 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.889996E+09 | 1457.63 | 11-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.895741E+09 | 1259.70 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.884461E+09 | 1367.23 | 29-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.105090E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.812138E+09 | 880.11 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.935193E+09 | 1457.63 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.593148E+09 | 887.46 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.526655E+09 | 871.36 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.606064E+09 | 900.36 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.530734E+09 | 697.90 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.564011E+09 | 734.71 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.561374E+09 | 736.32 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.536948E+09 | 858.59 | 26-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.604298E+09 | 881.20 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.546544E+09 | 904.09 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.581156E+09 | 949.65 | 11-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.581731E+09 | 842.70 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.577693E+09 | 857.26 | 29-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.681035E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.526655E+09 | 697.90 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.606064E+09 | 949.65 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.937666E+09 | 1361.88 | 18-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.827704E+09 | 1330.80 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.939542E+09 | 1343.96 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.821661E+09 | 862.01 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.868978E+09 | 921.60 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.865093E+09 | 919.82 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.826009E+09 | 1287.83 | 26-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.930285E+09 | 1334.28 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.845755E+09 | 1380.81 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.900297E+09 | 1463.59 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.921825E+09 | 1423.49 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.920563E+09 | 1439.14 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106054E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.821661E+09 | 862.01 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.939542E+09 | 1463.59 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596354E+09 | 864.77 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.529453E+09 | 859.83 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.602958E+09 | 747.22 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.528964E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.562545E+09 | 574.29 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.559991E+09 | 574.75 | 23-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.532888E+09 | 793.93 | 26-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.598447E+09 | 827.17 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.543090E+09 | 860.37 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.574773E+09 | 924.43 | 11-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.590398E+09 | 938.33 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.586242E+09 | 933.45 | 29-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.680610E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.528964E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.602958E+09 | 938.33 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.906111E+09 | 1303.04 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.811461E+09 | 1283.63 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.934410E+09 | 1326.14 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.823410E+09 | 871.65 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.875802E+09 | 1062.03 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.872066E+09 | 1073.58 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.831729E+09 | 1309.26 | 26-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.932529E+09 | 1343.80 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.843714E+09 | 1378.02 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.888677E+09 | 1455.33 | 11-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.893890E+09 | 1254.40 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.884119E+09 | 1363.72 | 29-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104979E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.811461E+09 | 871.65 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.934410E+09 | 1455.33 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.592121E+09 | 882.67 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.525807E+09 | 866.12 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.605281E+09 | 895.79 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.530274E+09 | 688.60 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.563345E+09 | 725.76 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.560586E+09 | 727.43 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.535859E+09 | 853.00 | 26-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.603076E+09 | 876.20 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.545657E+09 | 899.69 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.580142E+09 | 946.46 | 11-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.581182E+09 | 837.30 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.576992E+09 | 852.12 | 29-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.680032E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.525807E+09 | 688.60 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.605281E+09 | 946.46 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.937583E+09 | 1361.28 | 18-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.827540E+09 | 1330.13 | 10-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.939505E+09 | 1343.36 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.821646E+09 | 861.71 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.868958E+09 | 921.38 | 24-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.865053E+09 | 919.60 | 23-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.825962E+09 | 1287.06 | 26-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.930205E+09 | 1333.61 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.845662E+09 | 1380.23 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.900248E+09 | 1463.18 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.921691E+09 | 1423.09 | 27-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.920501E+09 | 1438.70 | 29-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.106046E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.821646E+09 | 861.71 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.939505E+09 | 1463.18 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.596334E+09 | 864.39 | 17-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.529425E+09 | 859.41 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.602942E+09 | 746.76 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.528956E+09 | 509.78 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.562525E+09 | 574.11 | 24-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.559971E+09 | 574.57 | 23-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.532858E+09 | 793.40 | 26-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.598382E+09 | 826.71 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.543055E+09 | 859.97 | 08-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.574737E+09 | 924.15 | 11-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.590373E+09 | 938.11 | 27-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.586216E+09 | 933.18 | 29-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.680577E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.528956E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.602942E+09 | 938.11 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.906101E+09 | 1302.35 | 18-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.811434E+09 | 1282.89 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.934342E+09 | 1325.51 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.823375E+09 | 871.37 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.875762E+09 | 1060.84 | 24-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.872023E+09 | 1072.41 | 23-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.831653E+09 | 1308.53 | 26-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.932464E+09 | 1343.14 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.843663E+09 | 1377.43 | 08-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.888651E+09 | 1454.91 | 11-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.893875E+09 | 1253.85 | 27-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.884110E+09 | 1363.22 | 29-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104975E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.811434E+09 | 871.37 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.934342E+09 | 1454.91 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.592104E+09 | 882.30 | 18-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.525769E+09 | 865.71 | 10-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.605245E+09 | 895.45 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.530214E+09 | 688.15 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.563327E+09 | 725.08 | 24-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.560510E+09 | 726.74 | 23-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.535821E+09 | 852.55 | 26-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.602963E+09 | 875.80 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.545610E+09 | 899.34 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.580114E+09 | 946.21 | 11-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.581165E+09 | 836.98 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.576927E+09 | 851.78 | 29-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.679977E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.525769E+09 | 688.15 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.605245E+09 | 946.21 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.940365E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87331594.11 |
February | 0.136985E+10 | 0.829509E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1176637.75 | 93157186.74 |
March | 0.163685E+10 | 0.940812E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17151281.31 | 57390648.74 |
April | 0.145243E+10 | 0.822203E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68213417.78 | 4159071.72 |
May | 0.157338E+10 | 0.869443E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150619E+09 | 1304288.07 |
June | 0.156900E+10 | 0.866259E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101816E+09 | 609190.11 |
July | 0.145680E+10 | 0.826987E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128112E+09 | 261153.92 |
August | 0.163685E+10 | 0.931486E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72024293.82 | 516836.87 |
September | 0.145243E+10 | 0.847034E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42823284.88 | 1166244.62 |
October | 0.150991E+10 | 0.901842E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22154113.97 | 4874832.52 |
November | 0.149516E+10 | 0.923986E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4585503.47 | 19926006.60 |
December | 0.145680E+10 | 0.923300E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66274.80 | 80586791.81 |
Annual Sum or Average | 0.181194E+11 | 0.106232E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608742E+09 | 0.351284E+09 |
Minimum of Months | 0.136985E+10 | 0.822203E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261153.92 |
Maximum of Months | 0.163685E+10 | 0.940812E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150619E+09 | 93157186.74 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.597426E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59718659.44 |
February | 0.882782E+09 | 0.530331E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 603832.69 | 64289568.44 |
March | 0.105485E+10 | 0.603430E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10538876.53 | 38857995.59 |
April | 0.936002E+09 | 0.529216E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44705616.46 | 2840024.09 |
May | 0.101394E+10 | 0.562928E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98823927.63 | 899217.86 |
June | 0.101113E+10 | 0.560508E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67803324.14 | 363250.42 |
July | 0.938820E+09 | 0.533564E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86221692.70 | 127012.17 |
August | 0.105485E+10 | 0.599338E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49221795.72 | 258934.82 |
September | 0.936002E+09 | 0.543714E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28361222.93 | 640139.93 |
October | 0.973041E+09 | 0.575445E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14131783.66 | 3405620.49 |
November | 0.963541E+09 | 0.591249E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2746206.87 | 13889503.38 |
December | 0.938820E+09 | 0.587244E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14734.46 | 54079991.27 |
Annual Sum or Average | 0.116768E+11 | 0.681439E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403173E+09 | 0.239370E+09 |
Minimum of Months | 0.882782E+09 | 0.529216E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127012.17 |
Maximum of Months | 0.105485E+10 | 0.603430E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98823927.63 | 64289568.44 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.906505E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94160623.21 |
February | 0.136988E+10 | 0.812138E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 871737.75 | 0.103764E+09 |
March | 0.163688E+10 | 0.935193E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15140054.53 | 64365117.74 |
April | 0.145246E+10 | 0.823964E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66471788.85 | 4853113.40 |
May | 0.157341E+10 | 0.876436E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149691E+09 | 1332897.61 |
June | 0.156904E+10 | 0.873021E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101743E+09 | 622016.96 |
July | 0.145684E+10 | 0.833058E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127988E+09 | 254432.60 |
August | 0.163688E+10 | 0.933849E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71680336.31 | 546394.49 |
September | 0.145246E+10 | 0.844613E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41568217.18 | 1160078.13 |
October | 0.150994E+10 | 0.889996E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20265380.12 | 5615399.58 |
November | 0.149520E+10 | 0.895741E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3717817.62 | 23152703.53 |
December | 0.145684E+10 | 0.884461E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17202.07 | 89842706.67 |
Annual Sum or Average | 0.181198E+11 | 0.105090E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599155E+09 | 0.389669E+09 |
Minimum of Months | 0.136988E+10 | 0.812138E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254432.60 |
Maximum of Months | 0.163688E+10 | 0.935193E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149691E+09 | 0.103764E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.593148E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65511734.69 |
February | 0.882782E+09 | 0.526655E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 581743.27 | 74492419.68 |
March | 0.105485E+10 | 0.606064E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9928698.56 | 51362500.72 |
April | 0.936002E+09 | 0.530734E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42896614.14 | 5487233.55 |
May | 0.101394E+10 | 0.564011E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95895122.10 | 1397220.69 |
June | 0.101113E+10 | 0.561374E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64796492.90 | 863804.71 |
July | 0.938820E+09 | 0.536948E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79765920.98 | 427497.86 |
August | 0.105485E+10 | 0.604298E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44333335.59 | 848210.84 |
September | 0.936002E+09 | 0.546544E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26401476.50 | 1649681.36 |
October | 0.973041E+09 | 0.581156E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13651854.09 | 4347094.08 |
November | 0.963541E+09 | 0.581731E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2511959.03 | 16386297.00 |
December | 0.938820E+09 | 0.577693E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11544.26 | 65069669.28 |
Annual Sum or Average | 0.116768E+11 | 0.681035E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380775E+09 | 0.287843E+09 |
Minimum of Months | 0.882782E+09 | 0.526655E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427497.86 |
Maximum of Months | 0.105485E+10 | 0.606064E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95895122.10 | 74492419.68 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.937666E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 227006.96 | 0.165732E+09 |
February | 0.136985E+10 | 0.827704E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5471423.22 | 0.186407E+09 |
March | 0.163685E+10 | 0.939542E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41632882.88 | 0.127406E+09 |
April | 0.145243E+10 | 0.821661E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160541E+09 | 11509083.26 |
May | 0.157338E+10 | 0.868978E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345237E+09 | 3207777.64 |
June | 0.156900E+10 | 0.865093E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233113E+09 | 2216616.46 |
July | 0.145680E+10 | 0.826009E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289102E+09 | 951758.33 |
August | 0.163685E+10 | 0.930285E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166025E+09 | 1965435.53 |
September | 0.145243E+10 | 0.845755E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97006427.42 | 3043819.74 |
October | 0.150991E+10 | 0.900297E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52380249.65 | 11127952.48 |
November | 0.149516E+10 | 0.921825E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13177670.44 | 39767192.07 |
December | 0.145680E+10 | 0.920563E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1829790.39 | 0.151397E+09 |
Annual Sum or Average | 0.181194E+11 | 0.106054E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140574E+10 | 0.704731E+09 |
Minimum of Months | 0.136985E+10 | 0.821661E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 227006.96 | 951758.33 |
Maximum of Months | 0.163685E+10 | 0.939542E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345237E+09 | 0.186407E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.596354E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.16 | 0.124199E+09 |
February | 0.649041E+09 | 0.529453E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1189320.75 | 0.141161E+09 |
March | 0.773965E+09 | 0.602958E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22792687.78 | 95714225.72 |
April | 0.688021E+09 | 0.528964E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100893E+09 | 9916236.80 |
May | 0.744847E+09 | 0.562545E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223555E+09 | 2499964.62 |
June | 0.742030E+09 | 0.559991E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152542E+09 | 1618545.97 |
July | 0.690839E+09 | 0.532888E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189011E+09 | 666802.58 |
August | 0.773965E+09 | 0.598447E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107382E+09 | 1442965.29 |
September | 0.688021E+09 | 0.543090E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61887138.76 | 2167368.73 |
October | 0.715730E+09 | 0.574773E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31650183.96 | 8595483.90 |
November | 0.708685E+09 | 0.590398E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5950167.77 | 30883666.63 |
December | 0.690839E+09 | 0.586242E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 254756.44 | 0.113529E+09 |
Annual Sum or Average | 0.858171E+10 | 0.680610E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897108E+09 | 0.532393E+09 |
Minimum of Months | 0.649041E+09 | 0.528964E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.16 | 666802.58 |
Maximum of Months | 0.773965E+09 | 0.602958E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223555E+09 | 0.141161E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.906111E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210223E+09 |
February | 0.136988E+10 | 0.811461E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1853888.88 | 0.235223E+09 |
March | 0.163688E+10 | 0.934410E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34093254.55 | 0.153833E+09 |
April | 0.145246E+10 | 0.823410E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153903E+09 | 14102925.52 |
May | 0.157341E+10 | 0.875802E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343353E+09 | 3303471.39 |
June | 0.156904E+10 | 0.872066E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233189E+09 | 2177280.66 |
July | 0.145684E+10 | 0.831729E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288844E+09 | 951841.88 |
August | 0.163688E+10 | 0.932529E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164128E+09 | 2088144.33 |
September | 0.145246E+10 | 0.843714E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93472653.54 | 3387137.47 |
October | 0.150994E+10 | 0.888677E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46110752.22 | 13796270.51 |
November | 0.149520E+10 | 0.893890E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8256422.53 | 53286187.04 |
December | 0.145684E+10 | 0.884119E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29221.27 | 0.200924E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104979E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136723E+10 | 0.893296E+09 |
Minimum of Months | 0.136988E+10 | 0.811461E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951841.88 |
Maximum of Months | 0.163688E+10 | 0.934410E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343353E+09 | 0.235223E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.592121E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126904E+09 |
February | 0.882782E+09 | 0.525807E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1378502.37 | 0.144402E+09 |
March | 0.105485E+10 | 0.605281E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23813426.22 | 0.104005E+09 |
April | 0.936002E+09 | 0.530274E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100897E+09 | 11368061.83 |
May | 0.101394E+10 | 0.563345E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222361E+09 | 3115889.95 |
June | 0.101113E+10 | 0.560586E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151102E+09 | 1990259.23 |
July | 0.938820E+09 | 0.535859E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186756E+09 | 842244.21 |
August | 0.105485E+10 | 0.603076E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105810E+09 | 1824783.73 |
September | 0.936002E+09 | 0.545657E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61228548.24 | 2875929.05 |
October | 0.973041E+09 | 0.580142E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32186647.92 | 8609464.85 |
November | 0.963541E+09 | 0.581182E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6436667.65 | 30831074.04 |
December | 0.938820E+09 | 0.576992E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108111.30 | 0.116327E+09 |
Annual Sum or Average | 0.116768E+11 | 0.680032E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892077E+09 | 0.553095E+09 |
Minimum of Months | 0.882782E+09 | 0.525807E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 842244.21 |
Maximum of Months | 0.105485E+10 | 0.605281E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222361E+09 | 0.144402E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.937583E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 543210.40 | 0.179452E+09 |
February | 0.136985E+10 | 0.827540E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7724958.08 | 0.211220E+09 |
March | 0.163685E+10 | 0.939505E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48878283.66 | 0.153691E+09 |
April | 0.145243E+10 | 0.821646E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192212E+09 | 15061617.12 |
May | 0.157338E+10 | 0.868958E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418089E+09 | 4585606.65 |
June | 0.156900E+10 | 0.865053E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283269E+09 | 3102521.08 |
July | 0.145680E+10 | 0.825962E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349303E+09 | 1232627.73 |
August | 0.163685E+10 | 0.930205E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199175E+09 | 2820596.76 |
September | 0.145243E+10 | 0.845662E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115917E+09 | 4181610.02 |
October | 0.150991E+10 | 0.900248E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62889546.94 | 13429249.86 |
November | 0.149516E+10 | 0.921691E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16966637.94 | 44838043.39 |
December | 0.145680E+10 | 0.920501E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3801770.41 | 0.165243E+09 |
Annual Sum or Average | 0.181194E+11 | 0.106046E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169877E+10 | 0.798858E+09 |
Minimum of Months | 0.136985E+10 | 0.821646E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 543210.40 | 1232627.73 |
Maximum of Months | 0.163685E+10 | 0.939505E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418089E+09 | 0.211220E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.596334E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65494.28 | 0.134687E+09 |
February | 0.882782E+09 | 0.529425E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1636669.24 | 0.161077E+09 |
March | 0.105485E+10 | 0.602942E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27941323.97 | 0.115767E+09 |
April | 0.936002E+09 | 0.528956E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123725E+09 | 12813524.21 |
May | 0.101394E+10 | 0.562525E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273047E+09 | 3458756.73 |
June | 0.101113E+10 | 0.559971E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186930E+09 | 2232610.11 |
July | 0.938820E+09 | 0.532858E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230471E+09 | 861048.06 |
August | 0.105485E+10 | 0.598382E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130583E+09 | 2010004.60 |
September | 0.936002E+09 | 0.543055E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75471822.64 | 2953007.10 |
October | 0.973041E+09 | 0.574737E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38902442.99 | 10398154.51 |
November | 0.963541E+09 | 0.590373E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7771315.79 | 35203176.55 |
December | 0.938820E+09 | 0.586216E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 889332.41 | 0.124995E+09 |
Annual Sum or Average | 0.116768E+11 | 0.680577E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109743E+10 | 0.606456E+09 |
Minimum of Months | 0.882782E+09 | 0.528956E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65494.28 | 861048.06 |
Maximum of Months | 0.105485E+10 | 0.602942E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273047E+09 | 0.161077E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.906101E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238152E+09 |
February | 0.136988E+10 | 0.811434E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2076688.04 | 0.275189E+09 |
March | 0.163688E+10 | 0.934342E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40780421.23 | 0.186620E+09 |
April | 0.145246E+10 | 0.823375E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186578E+09 | 18332148.07 |
May | 0.157341E+10 | 0.875762E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416082E+09 | 4706321.70 |
June | 0.156904E+10 | 0.872023E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283313E+09 | 3056171.96 |
July | 0.145684E+10 | 0.831653E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349023E+09 | 1236671.14 |
August | 0.163688E+10 | 0.932464E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197188E+09 | 2962546.54 |
September | 0.145246E+10 | 0.843663E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112321E+09 | 4689034.00 |
October | 0.150994E+10 | 0.888651E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56110247.33 | 16826423.61 |
November | 0.149520E+10 | 0.893875E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9882212.18 | 63156363.40 |
December | 0.145684E+10 | 0.884110E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24852.00 | 0.229816E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104975E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165338E+10 | 0.104474E+10 |
Minimum of Months | 0.136988E+10 | 0.811434E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1236671.14 |
Maximum of Months | 0.163688E+10 | 0.934342E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416082E+09 | 0.275189E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.592104E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2085.88 | 0.143491E+09 |
February | 0.882782E+09 | 0.525769E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1637491.21 | 0.168388E+09 |
March | 0.105485E+10 | 0.605245E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28622578.89 | 0.126359E+09 |
April | 0.936002E+09 | 0.530214E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122645E+09 | 14627667.16 |
May | 0.101394E+10 | 0.563327E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270830E+09 | 4173543.63 |
June | 0.101113E+10 | 0.560510E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184414E+09 | 2634148.15 |
July | 0.938820E+09 | 0.535821E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226614E+09 | 1126500.55 |
August | 0.105485E+10 | 0.602963E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127888E+09 | 2480498.42 |
September | 0.936002E+09 | 0.545610E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73854233.88 | 3923118.48 |
October | 0.973041E+09 | 0.580114E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39105728.98 | 10504156.21 |
November | 0.963541E+09 | 0.581165E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7981679.68 | 35922641.39 |
December | 0.938820E+09 | 0.576927E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 433148.26 | 0.132128E+09 |
Annual Sum or Average | 0.116768E+11 | 0.679977E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108403E+10 | 0.645758E+09 |
Minimum of Months | 0.882782E+09 | 0.525769E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2085.88 | 1126500.55 |
Maximum of Months | 0.105485E+10 | 0.605245E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270830E+09 | 0.168388E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193316E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 987097.72 | 0.209174E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27901317.40 | 0.133994E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123685E+09 | 12073282.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277053E+09 | 3459967.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189244E+09 | 1775789.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234512E+09 | 795183.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127500E+09 | 1407314.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75674293.90 | 2281050.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38601720.11 | 11892932.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6365044.71 | 46187026.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.27 | 0.180552E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110152E+10 | 0.796908E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 795183.49 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277053E+09 | 0.209174E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319470E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2724289.10 | 0.352941E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51859617.43 | 0.234553E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228159E+09 | 21908379.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501192E+09 | 6010368.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340817E+09 | 3453220.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427186E+09 | 1479794.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236495E+09 | 2632770.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136350E+09 | 3930263.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70050341.17 | 21317140.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12807993.85 | 77968620.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463867.95 | 0.296094E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200811E+10 | 0.134176E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1479794.55 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501192E+09 | 0.352941E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312414E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507502.94 | 0.364152E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41253255.19 | 0.249819E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223622E+09 | 22700540.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531077E+09 | 7213643.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366882E+09 | 3651731.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447599E+09 | 1347432.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246586E+09 | 4555301.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138168E+09 | 4738963.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65336993.27 | 20609312.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9073598.74 | 76735569.88 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 638860.90 | 0.285543E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207074E+10 | 0.135348E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1347432.44 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531077E+09 | 0.364152E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1365.60 | 18-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 223.69 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1334.84 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.76 | 19-FEB-15:10 | 303.64 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1347.93 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.44 | 26-MAR-15:00 | 656.85 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 871.10 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 332.81 | 15-APR-17:04 | 99.83 | 22-APR-18:30 |
May | 2010.79 | 01-MAY-09:09 | 927.00 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 603.39 | 28-MAY-14:23 | 46.80 | 15-MAY-03:40 |
June | 2010.79 | 01-JUN-09:09 | 925.30 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.68 | 17-JUN-20:40 | 46.59 | 18-JUN-04:10 |
July | 2010.79 | 03-JUL-09:09 | 1292.19 | 26-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.71 | 02-JUL-11:44 | 38.88 | 19-JUL-02:40 |
August | 2010.79 | 01-AUG-09:09 | 1338.07 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.01 | 06-AUG-13:43 | 48.01 | 15-AUG-23:50 |
September | 2010.79 | 01-SEP-09:09 | 1384.03 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.00 | 24-SEP-14:25 | 26.50 | 08-SEP-22:10 |
October | 2010.79 | 02-OCT-09:09 | 1465.83 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.72 | 15-OCT-12:10 | 94.57 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1426.82 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.77 | 12-NOV-14:10 | 158.14 | 28-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 1441.86 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 24-DEC-14:13 | 344.69 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 871.10 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | |||||
Maximum of Months | 2010.79 | 1465.83 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 603.39 | 656.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 870.03 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 145.64 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 865.23 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.72 | 19-FEB-15:10 | 195.30 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 754.29 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 102.84 | 26-MAR-15:18 | 439.48 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.54 | 15-APR-17:04 | 64.80 | 22-APR-18:30 |
May | 1295.83 | 01-MAY-09:09 | 578.13 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.30 | 28-MAY-14:43 | 34.10 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 578.51 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.08 | 17-JUN-20:40 | 28.45 | 18-JUN-04:10 |
July | 1295.83 | 03-JUL-09:09 | 800.32 | 26-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.65 | 02-JUL-11:44 | 22.03 | 19-JUL-02:40 |
August | 1295.83 | 01-AUG-09:09 | 832.44 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.93 | 06-AUG-13:43 | 27.64 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 864.82 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.85 | 24-SEP-14:25 | 15.73 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 927.86 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.00 | 15-OCT-12:04 | 59.29 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 941.67 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 12-NOV-14:10 | 103.33 | 28-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 936.94 | 29-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 24-DEC-14:13 | 217.05 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 | |||||
Maximum of Months | 1295.83 | 941.67 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 398.30 | 439.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1307.00 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 245.86 | 22-JAN-14:00 |
February | 2010.83 | 01-FEB-10:09 | 1288.00 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 | 21-FEB-15:00 | 299.90 | 09-FEB-22:10 |
March | 2010.83 | 01-MAR-10:09 | 1330.25 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 148.00 | 26-MAR-15:14 | 733.57 | 24-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 880.11 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.96 | 15-APR-17:04 | 107.03 | 22-APR-18:30 |
May | 2010.83 | 01-MAY-09:09 | 1069.79 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 597.46 | 28-MAY-14:44 | 50.64 | 15-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 1081.30 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.96 | 03-JUN-17:10 | 47.54 | 18-JUN-04:10 |
July | 2010.83 | 03-JUL-09:09 | 1313.45 | 26-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.42 | 02-JUL-11:44 | 38.36 | 19-JUL-02:40 |
August | 2010.83 | 01-AUG-09:09 | 1347.51 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.74 | 06-AUG-14:00 | 49.35 | 15-AUG-23:50 |
September | 2010.83 | 01-SEP-09:09 | 1381.27 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.03 | 24-SEP-14:25 | 25.95 | 08-SEP-22:10 |
October | 2010.83 | 02-OCT-09:09 | 1457.63 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.66 | 15-OCT-12:44 | 94.26 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1259.70 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.89 | 13-NOV-14:00 | 167.97 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1367.23 | 29-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 28-DEC-14:00 | 413.02 | 31-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 880.11 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 | |||||
Maximum of Months | 2010.83 | 1457.63 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 597.46 | 733.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 887.46 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 161.39 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 871.36 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 | 21-FEB-15:00 | 228.49 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 900.36 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.76 | 26-MAR-14:34 | 603.87 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 697.90 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.39 | 15-APR-17:10 | 112.17 | 22-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 734.71 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.31 | 28-MAY-14:43 | 50.85 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 736.32 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.08 | 17-JUN-20:25 | 47.97 | 18-JUN-04:10 |
July | 1295.83 | 03-JUL-09:09 | 858.59 | 26-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.07 | 02-JUL-11:44 | 41.48 | 19-JUL-02:40 |
August | 1295.83 | 01-AUG-09:09 | 881.20 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.82 | 06-AUG-14:00 | 52.84 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 904.09 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.54 | 24-SEP-14:25 | 25.72 | 08-SEP-22:10 |
October | 1295.83 | 02-OCT-09:09 | 949.65 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.93 | 15-OCT-12:04 | 78.23 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 842.70 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.49 | 12-NOV-14:04 | 127.01 | 28-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 857.26 | 29-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 | 28-DEC-14:00 | 275.89 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 697.90 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.72 | |||||
Maximum of Months | 1295.83 | 949.65 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 398.31 | 603.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1361.88 | 18-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.10 | 08-JAN-14:53 | 435.73 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1330.80 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.64 | 19-FEB-14:54 | 630.68 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1343.96 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.84 | 26-MAR-14:40 | 1283.94 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 862.01 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 782.46 | 15-APR-17:07 | 214.83 | 22-APR-17:53 |
May | 2010.79 | 01-MAY-09:09 | 921.60 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.74 | 28-MAY-14:53 | 104.83 | 13-MAY-04:10 |
June | 2010.79 | 01-JUN-09:09 | 919.82 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.15 | 04-JUN-12:56 | 115.46 | 18-JUN-04:45 |
July | 2010.79 | 03-JUL-09:09 | 1287.83 | 26-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 686.20 | 02-JUL-11:44 | 99.40 | 19-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 1334.28 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.56 | 06-AUG-13:45 | 126.87 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1380.81 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 376.56 | 24-SEP-14:36 | 52.94 | 08-SEP-22:10 |
October | 2010.79 | 02-OCT-09:09 | 1463.59 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.92 | 15-OCT-12:30 | 195.26 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1423.49 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.74 | 12-NOV-14:00 | 308.56 | 28-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 1439.14 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 147.07 | 24-DEC-13:54 | 664.61 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 862.01 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 36.10 | 52.94 | |||||
Maximum of Months | 2010.79 | 1463.59 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.74 | 1283.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 864.77 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 08-JAN-14:53 | 290.19 | 15-JAN-17:00 |
February | 1239.33 | 01-FEB-08:09 | 859.83 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 19-FEB-15:00 | 419.64 | 09-FEB-22:10 |
March | 1239.33 | 01-MAR-08:09 | 747.22 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 236.59 | 26-MAR-14:58 | 934.76 | 24-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 521.76 | 15-APR-17:06 | 177.75 | 22-APR-17:53 |
May | 1239.33 | 01-MAY-07:10 | 574.29 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 930.49 | 28-MAY-14:53 | 82.92 | 15-MAY-03:00 |
June | 1239.33 | 01-JUN-07:10 | 574.75 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.41 | 03-JUN-17:08 | 79.72 | 18-JUN-03:55 |
July | 1239.33 | 03-JUL-07:10 | 793.93 | 26-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.90 | 02-JUL-11:44 | 66.11 | 19-JUL-02:55 |
August | 1239.33 | 01-AUG-07:10 | 827.17 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.71 | 06-AUG-13:43 | 88.82 | 15-AUG-24:00 |
September | 1239.33 | 01-SEP-07:10 | 860.37 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.97 | 24-SEP-14:34 | 35.65 | 08-SEP-22:10 |
October | 1239.33 | 02-OCT-07:10 | 924.43 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.02 | 15-OCT-12:04 | 131.52 | 12-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 938.33 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.58 | 12-NOV-14:40 | 217.19 | 28-NOV-05:00 |
December | 1239.33 | 01-DEC-08:09 | 933.45 | 29-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.59 | 24-DEC-14:00 | 445.18 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 35.65 | |||||
Maximum of Months | 1239.33 | 938.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 930.49 | 934.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1303.04 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 592.96 | 22-JAN-14:10 |
February | 2010.83 | 01-FEB-10:09 | 1283.63 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.20 | 21-FEB-15:00 | 651.46 | 18-FEB-05:55 |
March | 2010.83 | 01-MAR-10:09 | 1326.14 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 339.66 | 26-MAR-14:55 | 1520.85 | 24-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 871.65 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 782.59 | 15-APR-17:06 | 250.20 | 22-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 1062.03 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.74 | 28-MAY-14:53 | 110.89 | 15-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 1073.58 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 630.23 | 03-JUN-17:02 | 114.59 | 18-JUN-04:45 |
July | 2010.83 | 03-JUL-09:09 | 1309.26 | 26-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 685.74 | 02-JUL-11:44 | 99.05 | 19-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 1343.80 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 437.41 | 06-AUG-14:00 | 131.28 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1378.02 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.89 | 24-SEP-15:00 | 53.70 | 08-SEP-22:10 |
October | 2010.83 | 02-OCT-09:09 | 1455.33 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.45 | 15-OCT-13:00 | 202.11 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1254.40 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.30 | 13-NOV-14:00 | 369.08 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1363.72 | 29-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 28-DEC-14:00 | 955.94 | 31-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 871.65 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.70 | |||||
Maximum of Months | 2010.83 | 1455.33 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1395.74 | 1520.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 882.67 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 306.42 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 866.12 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 | 19-FEB-13:43 | 438.34 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 895.79 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 224.88 | 26-MAR-14:55 | 1036.93 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 688.60 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 512.10 | 15-APR-17:06 | 174.22 | 22-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 725.76 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 930.49 | 28-MAY-14:56 | 108.63 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 727.43 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.51 | 04-JUN-12:54 | 94.23 | 18-JUN-03:45 |
July | 1295.83 | 03-JUL-09:09 | 853.00 | 26-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.05 | 02-JUL-11:44 | 71.26 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 876.20 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.40 | 06-AUG-13:43 | 96.30 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 899.69 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.38 | 24-SEP-13:54 | 39.18 | 08-SEP-22:10 |
October | 1295.83 | 02-OCT-09:09 | 946.46 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.60 | 15-OCT-12:06 | 137.87 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 837.30 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.25 | 12-NOV-12:51 | 228.56 | 28-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 852.12 | 29-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 | 24-DEC-13:52 | 466.27 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 688.60 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | |||||
Maximum of Months | 1295.83 | 946.46 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 930.49 | 1036.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1361.28 | 18-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 67.98 | 08-JAN-14:53 | 469.45 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1330.13 | 10-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 198.59 | 19-FEB-15:00 | 727.34 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1343.36 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 516.58 | 26-MAR-14:53 | 1506.20 | 24-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 861.71 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 961.89 | 15-APR-17:06 | 251.74 | 22-APR-17:53 |
May | 2010.79 | 01-MAY-09:09 | 921.38 | 24-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1721.57 | 28-MAY-14:44 | 177.49 | 15-MAY-02:45 |
June | 2010.79 | 01-JUN-09:09 | 919.60 | 23-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 778.39 | 03-JUN-17:08 | 154.87 | 18-JUN-03:45 |
July | 2010.79 | 03-JUL-09:09 | 1287.06 | 26-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 846.79 | 02-JUL-11:44 | 118.18 | 19-JUL-02:55 |
August | 2010.79 | 01-AUG-09:09 | 1333.61 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 550.73 | 06-AUG-13:43 | 165.76 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1380.23 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 468.07 | 24-SEP-14:54 | 64.19 | 08-SEP-22:10 |
October | 2010.79 | 02-OCT-09:09 | 1463.18 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 533.41 | 15-OCT-11:51 | 228.49 | 12-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 1423.09 | 27-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.21 | 12-NOV-14:00 | 350.48 | 29-NOV-24:00 |
December | 2010.79 | 01-DEC-10:09 | 1438.70 | 29-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 245.73 | 24-DEC-13:52 | 753.51 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 861.71 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 67.98 | 64.19 | |||||
Maximum of Months | 2010.79 | 1463.18 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1721.57 | 1506.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 864.39 | 17-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | 08-JAN-14:53 | 312.44 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 859.41 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.10 | 19-FEB-15:00 | 482.49 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 746.76 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 282.26 | 26-MAR-15:16 | 1102.44 | 24-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 509.78 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 641.79 | 15-APR-17:06 | 205.11 | 22-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 574.11 | 24-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1149.17 | 28-MAY-14:44 | 134.35 | 15-MAY-02:45 |
June | 1295.83 | 01-JUN-09:09 | 574.57 | 23-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.69 | 03-JUN-17:07 | 106.08 | 18-JUN-03:45 |
July | 1295.83 | 03-JUL-09:09 | 793.40 | 26-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.55 | 02-JUL-11:44 | 78.23 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 826.71 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.69 | 06-AUG-13:43 | 115.02 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 859.97 | 08-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.57 | 24-SEP-14:13 | 42.69 | 08-SEP-22:10 |
October | 1295.83 | 02-OCT-09:09 | 924.15 | 11-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.00 | 15-OCT-12:56 | 153.46 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 938.11 | 27-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.80 | 12-NOV-13:53 | 248.14 | 29-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 933.18 | 29-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.74 | 24-DEC-13:52 | 504.95 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | 42.69 | |||||
Maximum of Months | 1295.83 | 938.11 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1149.17 | 1102.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1302.35 | 18-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 686.58 | 22-JAN-15:00 |
February | 2010.83 | 01-FEB-10:09 | 1282.89 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.26 | 21-FEB-15:00 | 744.65 | 09-FEB-22:10 |
March | 2010.83 | 01-MAR-10:09 | 1325.51 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 398.20 | 26-MAR-15:14 | 1806.00 | 24-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 871.37 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 960.66 | 15-APR-17:06 | 293.75 | 22-APR-17:53 |
May | 2010.83 | 01-MAY-09:09 | 1060.84 | 24-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1725.62 | 28-MAY-14:44 | 187.40 | 15-MAY-02:45 |
June | 2010.83 | 01-JUN-09:09 | 1072.41 | 23-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 777.90 | 03-JUN-17:08 | 153.80 | 18-JUN-03:45 |
July | 2010.83 | 03-JUL-09:09 | 1308.53 | 26-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 846.18 | 02-JUL-11:44 | 117.75 | 19-JUL-02:55 |
August | 2010.83 | 01-AUG-09:09 | 1343.14 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 536.56 | 06-AUG-14:00 | 170.91 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1377.43 | 08-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.33 | 24-SEP-14:54 | 65.12 | 08-SEP-22:10 |
October | 2010.83 | 02-OCT-09:09 | 1454.91 | 11-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 462.40 | 15-OCT-13:00 | 236.81 | 12-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 1253.85 | 27-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.34 | 13-NOV-14:00 | 437.15 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1363.22 | 29-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 28-DEC-14:00 | 1108.51 | 31-DEC-14:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 871.37 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.12 | |||||
Maximum of Months | 2010.83 | 1454.91 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1725.62 | 1806.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 882.30 | 18-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 08-JAN-13:53 | 342.55 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 865.71 | 10-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.54 | 19-FEB-13:52 | 512.49 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 895.45 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 273.93 | 26-MAR-14:34 | 1230.83 | 24-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 688.15 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 629.50 | 15-APR-17:10 | 205.58 | 22-APR-17:53 |
May | 1295.83 | 01-MAY-09:09 | 725.08 | 24-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.07 | 28-MAY-14:57 | 159.14 | 15-MAY-02:45 |
June | 1295.83 | 01-JUN-09:09 | 726.74 | 23-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 519.00 | 17-JUN-20:25 | 124.97 | 18-JUN-02:65 |
July | 1295.83 | 03-JUL-09:09 | 852.55 | 26-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 565.13 | 02-JUL-11:44 | 85.18 | 19-JUL-02:55 |
August | 1295.83 | 01-AUG-09:09 | 875.80 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.18 | 06-AUG-13:43 | 124.10 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 899.34 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.64 | 24-SEP-14:13 | 47.59 | 08-SEP-22:10 |
October | 1295.83 | 02-OCT-09:09 | 946.21 | 11-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.76 | 15-OCT-12:54 | 162.50 | 12-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 836.98 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.79 | 12-NOV-12:42 | 269.69 | 29-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 851.78 | 29-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.80 | 24-DEC-13:52 | 537.83 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 688.15 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 47.59 | |||||
Maximum of Months | 1295.83 | 946.21 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.07 | 1230.83 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 470.62 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.44 | 19-FEB-14:52 | 682.45 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.26 | 26-MAR-15:00 | 1474.39 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 670.63 | 15-APR-17:01 | 214.75 | 22-APR-18:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.28 | 28-MAY-14:50 | 99.18 | 15-MAY-03:43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.57 | 03-JUN-17:02 | 100.44 | 18-JUN-04:15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.20 | 02-JUL-12:00 | 83.02 | 19-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.88 | 06-AUG-14:10 | 92.82 | 15-AUG-23:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.73 | 24-SEP-14:10 | 40.34 | 19-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.65 | 15-OCT-12:31 | 188.89 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.76 | 12-NOV-13:51 | 353.33 | 28-NOV-05:14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 | 28-DEC-14:00 | 743.45 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.34 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1176.28 | 1474.39 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 783.41 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.15 | 19-FEB-15:00 | 1187.16 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.20 | 26-MAR-14:42 | 2500.41 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1226.18 | 15-APR-17:01 | 377.70 | 22-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2128.07 | 28-MAY-15:00 | 164.94 | 13-MAY-04:12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 986.55 | 03-JUN-17:02 | 185.32 | 18-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.62 | 02-JUL-12:00 | 151.45 | 19-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 696.00 | 06-AUG-14:10 | 174.04 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.33 | 24-SEP-14:20 | 76.29 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.19 | 15-OCT-12:31 | 328.56 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.54 | 12-NOV-13:41 | 587.87 | 28-NOV-05:14 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.81 | 24-DEC-14:10 | 1253.14 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.29 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2128.07 | 2500.41 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 766.29 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 24-FEB-15:00 | 1229.23 | 09-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.72 | 26-MAR-15:00 | 2516.96 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1247.14 | 15-APR-17:01 | 312.89 | 22-APR-18:33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2075.34 | 28-MAY-15:00 | 216.77 | 15-MAY-02:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.19 | 03-JUN-17:10 | 199.92 | 18-JUN-03:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966.09 | 02-JUL-11:30 | 147.81 | 19-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.17 | 06-AUG-08:52 | 237.29 | 15-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.54 | 24-SEP-14:00 | 68.66 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.25 | 15-OCT-11:51 | 335.23 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.98 | 12-NOV-14:00 | 548.30 | 28-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.94 | 24-DEC-13:52 | 1201.54 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.66 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2075.34 | 2516.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 105203.79 | 23-JAN-05:11 | 0.00 | 4786.80 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 101665.64 | 20-FEB-14:42 | 5385.68 | 4914.31 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 99348.56 | 06-MAR-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 100990.29 | 30-APR-17:34 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97992.44 | 01-MAY-03:02 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 93732.98 | 04-JUN-23:08 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 86780.55 | 04-JUL-20:17 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83841.88 | 29-AUG-03:02 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83552.10 | 26-SEP-03:02 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97182.10 | 29-OCT-14:16 | 6283.29 | 5733.36 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 101161.15 | 12-NOV-13:51 | 6283.29 | 5733.36 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 101196.62 | 18-DEC-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 83552.10 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 105203.79 | 6283.29 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 89548.17 | 02-JAN-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95169.16 | 21-FEB-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 92744.81 | 06-MAR-05:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88323.63 | 03-APR-05:05 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86917.08 | 01-MAY-05:04 | 11285.67 | 3761.52 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86252.08 | 19-JUN-05:03 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87268.05 | 05-JUL-05:06 | 11285.67 | 3761.52 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87782.17 | 28-AUG-05:06 | 11285.67 | 3761.52 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86225.46 | 18-SEP-05:04 | 8061.19 | 2686.80 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96533.01 | 30-OCT-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 96182.77 | 20-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 95702.06 | 26-DEC-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 86225.46 | 0.00 | 2686.80 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96533.01 | 11285.67 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 76637.08 | 27-JAN-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82186.00 | 27-FEB-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84342.08 | 08-MAR-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88288.19 | 10-APR-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72492.62 | 30-MAY-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75495.64 | 12-JUN-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71363.46 | 10-JUL-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72334.97 | 24-AUG-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73572.83 | 29-SEP-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84651.19 | 24-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84452.74 | 13-NOV-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80132.92 | 01-DEC-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 71363.46 | 0.00 | 2149.44 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88288.19 | 9673.43 | 3761.52 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 32341.05 | 26-JAN-16:30 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78233.72 | 23-FEB-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84961.34 | 13-MAR-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85531.22 | 10-APR-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85312.43 | 30-MAY-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86678.82 | 12-JUN-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87112.91 | 03-JUL-05:04 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85696.65 | 07-AUG-05:04 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83478.31 | 11-SEP-03:02 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84789.67 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 79913.32 | 01-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 33570.38 | 01-DEC-16:30 | 15316.26 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 32341.05 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87112.91 | 15316.26 | 13241.18 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4464.00 | 26-JAN-14:10 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
February | 6599.13 | 23-FEB-14:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 | 0.00 |
March | 12582.37 | 14-MAR-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 |
April | 22864.39 | 30-APR-16:21 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 248.69 | 0.00 |
May | 22032.52 | 29-MAY-16:21 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 180.15 | 0.00 |
June | 23268.28 | 04-JUN-16:21 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 209.51 | 0.00 |
July | 23893.65 | 04-JUL-17:01 | 0.00 | 439.44 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 113.30 | 0.00 |
August | 21767.49 | 27-AUG-15:01 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 77.50 | 0.00 |
September | 21907.06 | 24-SEP-15:01 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 144.06 | 0.00 |
October | 21302.60 | 09-OCT-14:51 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 36.80 | 0.00 |
November | 7223.95 | 09-NOV-14:20 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.87 | 0.00 |
December | 5342.70 | 26-DEC-14:10 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4464.00 | 0.00 | 307.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23893.65 | 4021.58 | 1582.09 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 248.69 | 9.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4385.75 | 26-JAN-10:20 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 |
February | 8449.57 | 20-FEB-10:43 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.66 |
March | 14561.16 | 12-MAR-14:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 16.75 | 0.00 |
April | 19455.67 | 30-APR-09:41 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 16.74 | 0.00 |
May | 18434.28 | 29-MAY-09:02 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 262.76 | 0.00 |
June | 18273.46 | 04-JUN-16:21 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 140.61 | 0.00 |
July | 18963.82 | 04-JUL-15:41 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 73.35 | 0.00 |
August | 16961.73 | 06-AUG-16:21 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 100.04 | 0.00 |
September | 17531.33 | 24-SEP-15:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 93.93 | 0.00 |
October | 17429.52 | 01-OCT-08:32 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 |
November | 9189.75 | 05-NOV-10:32 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.45 |
December | 4960.42 | 01-DEC-10:00 | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4385.75 | 195.68 | 84.96 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19455.67 | 1295.83 | 509.78 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 262.76 | 31.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13438.12 | 12-JAN-13:50 | 1923.15 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 |
February | 24182.75 | 20-FEB-14:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 |
March | 23973.41 | 12-MAR-13:52 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 | 0.00 |
April | 24200.74 | 30-APR-15:41 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 232.62 | 0.00 |
May | 22410.45 | 29-MAY-15:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 243.42 | 0.00 |
June | 23479.51 | 04-JUN-16:21 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 209.54 | 0.00 |
July | 24086.77 | 04-JUL-16:21 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 112.18 | 0.00 |
August | 22237.21 | 27-AUG-15:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 75.94 | 0.00 |
September | 23917.03 | 24-SEP-15:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 123.41 | 0.00 |
October | 25130.91 | 09-OCT-12:51 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 11.19 | 0.00 |
November | 23476.90 | 26-NOV-11:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 |
December | 22701.94 | 24-DEC-13:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13438.12 | 404.87 | 175.78 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25130.91 | 1923.15 | 791.06 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 243.42 | 89.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7307.67 | 31-JAN-15:50 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 |
February | 23177.81 | 20-FEB-15:22 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
March | 24084.08 | 12-MAR-14:32 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 | 0.00 |
April | 28686.47 | 30-APR-16:21 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 112.41 | 0.00 |
May | 24687.91 | 28-MAY-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 321.79 | 0.00 |
June | 27574.57 | 04-JUN-16:21 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 118.36 | 0.00 |
July | 27527.02 | 04-JUL-16:21 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 63.55 | 0.00 |
August | 24612.36 | 06-AUG-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 84.14 | 0.00 |
September | 24960.69 | 24-SEP-15:01 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 79.10 | 0.00 |
October | 24997.08 | 15-OCT-15:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 55.39 | 0.00 |
November | 19813.86 | 06-NOV-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18446.09 | 24-DEC-15:23 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7307.67 | 0.00 | 113.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28686.47 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 321.79 | 39.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2803.75 | 26-JAN-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.75 |
February | 5396.05 | 24-FEB-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 0.00 |
March | 12223.18 | 14-MAR-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.90 |
April | 21718.36 | 16-APR-15:21 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 124.78 | 0.00 |
May | 22543.83 | 28-MAY-16:41 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.50 | 0.00 |
June | 23583.78 | 04-JUN-16:11 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 492.99 | 0.00 |
July | 22332.04 | 02-JUL-17:01 | 0.00 | 307.61 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 398.63 | 0.00 |
August | 21648.43 | 13-AUG-15:21 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 256.00 | 0.00 |
September | 18933.70 | 01-SEP-03:02 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 26.35 | 0.00 |
October | 15775.51 | 02-OCT-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5987.22 | 09-NOV-14:30 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 0.00 |
December | 2614.94 | 28-DEC-15:30 | 1923.11 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2614.94 | 0.00 | 307.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23583.78 | 2010.79 | 791.05 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1158.50 | 28.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5203.86 | 26-JAN-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 |
February | 8025.81 | 22-FEB-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
March | 16765.64 | 12-MAR-11:23 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 | 0.00 |
April | 19450.10 | 16-APR-09:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 22.04 | 0.00 |
May | 19841.97 | 29-MAY-10:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 610.99 | 0.00 |
June | 19700.52 | 04-JUN-16:11 | 652.28 | 283.19 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 326.99 | 0.00 |
July | 18995.08 | 04-JUL-10:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 195.83 | 0.00 |
August | 17917.75 | 13-AUG-15:21 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 171.93 | 0.00 |
September | 17989.31 | 24-SEP-09:13 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 49.81 | 0.00 |
October | 18586.95 | 15-OCT-10:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 141.91 | 0.00 |
November | 8471.40 | 01-NOV-10:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
December | 5516.43 | 01-DEC-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5203.86 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19841.97 | 2478.65 | 1019.56 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 610.99 | 35.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14902.80 | 08-JAN-15:53 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.38 |
February | 23398.80 | 19-FEB-14:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.30 |
March | 22727.75 | 05-MAR-13:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 | 0.00 |
April | 22704.59 | 16-APR-15:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 118.52 | 0.00 |
May | 22619.03 | 28-MAY-16:01 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1245.42 | 0.00 |
June | 23515.72 | 04-JUN-16:11 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 494.39 | 0.00 |
July | 22284.12 | 02-JUL-16:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 414.94 | 0.00 |
August | 21952.63 | 13-AUG-15:21 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 249.43 | 0.00 |
September | 22527.27 | 24-SEP-13:52 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 339.03 | 0.00 |
October | 25511.20 | 29-OCT-13:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
November | 25426.81 | 12-NOV-13:11 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.20 |
December | 23566.03 | 03-DEC-13:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14902.80 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25511.20 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1245.42 | 134.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5132.83 | 31-JAN-16:10 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 |
February | 11439.78 | 19-FEB-16:03 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.61 |
March | 19377.39 | 12-MAR-16:02 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 85.84 | 0.00 |
April | 21981.54 | 30-APR-16:31 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 353.65 | 0.00 |
May | 22758.05 | 28-MAY-16:01 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 747.74 | 0.00 |
June | 24644.09 | 04-JUN-16:11 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 278.10 | 0.00 |
July | 22109.07 | 02-JUL-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 251.09 | 0.00 |
August | 20926.13 | 06-AUG-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 206.94 | 0.00 |
September | 20554.84 | 17-SEP-15:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 139.07 | 0.00 |
October | 21906.90 | 15-OCT-15:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 | 0.00 |
November | 20124.72 | 12-NOV-15:12 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 25.06 | 0.00 |
December | 5842.89 | 01-DEC-15:30 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5132.83 | 260.91 | 113.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24644.09 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 747.74 | 65.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2720.52 | 26-JAN-15:00 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 |
February | 5644.53 | 23-FEB-14:50 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 | 0.00 |
March | 21452.10 | 12-MAR-15:41 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 142.13 | 0.00 |
April | 26438.94 | 30-APR-15:41 | 1012.16 | 439.44 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 689.31 | 0.00 |
May | 25935.34 | 28-MAY-16:41 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1396.14 | 0.00 |
June | 25709.21 | 11-JUN-15:41 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 324.52 | 0.00 |
July | 25647.79 | 02-JUL-17:01 | 0.00 | 307.61 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 480.57 | 0.00 |
August | 24991.84 | 13-AUG-15:31 | 910.95 | 395.49 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 300.86 | 0.00 |
September | 25763.38 | 24-SEP-15:31 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 338.46 | 0.00 |
October | 23957.59 | 09-OCT-16:01 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 0.00 |
November | 6464.85 | 09-NOV-14:40 | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 0.00 |
December | 2518.61 | 28-DEC-16:00 | 1923.11 | 839.49 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2518.61 | 0.00 | 307.61 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26438.94 | 2010.79 | 839.49 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1396.14 | 37.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2953.53 | 26-JAN-14:20 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 |
February | 6139.10 | 23-FEB-10:40 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 |
March | 19179.13 | 12-MAR-15:41 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 85.25 | 0.00 |
April | 22041.02 | 30-APR-09:41 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 36.75 | 0.00 |
May | 20939.36 | 29-MAY-10:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 732.78 | 0.00 |
June | 20178.48 | 11-JUN-10:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 167.09 | 0.00 |
July | 19956.94 | 04-JUL-10:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 237.21 | 0.00 |
August | 19262.16 | 13-AUG-15:31 | 587.05 | 254.87 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 200.66 | 0.00 |
September | 20274.60 | 24-SEP-15:31 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 216.00 | 0.00 |
October | 19439.96 | 09-OCT-10:42 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6410.20 | 09-NOV-10:20 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.00 |
December | 2987.88 | 01-DEC-14:40 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2953.53 | 326.14 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22041.02 | 1295.83 | 509.78 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 732.78 | 20.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13331.22 | 12-JAN-14:20 | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 |
February | 26890.29 | 20-FEB-14:12 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 |
March | 27246.95 | 12-MAR-13:42 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 0.00 |
April | 27833.26 | 30-APR-15:41 | 1012.19 | 439.45 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 628.96 | 0.00 |
May | 25981.00 | 28-MAY-16:01 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1501.27 | 0.00 |
June | 25628.45 | 11-JUN-15:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 324.75 | 0.00 |
July | 25553.18 | 02-JUL-16:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 500.08 | 0.00 |
August | 25297.94 | 13-AUG-14:51 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 292.24 | 0.00 |
September | 27689.28 | 24-SEP-15:31 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 284.55 | 0.00 |
October | 28471.45 | 29-OCT-13:31 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
November | 28355.61 | 05-NOV-13:41 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 | 0.00 |
December | 19872.02 | 24-DEC-14:43 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13331.22 | 404.87 | 175.78 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28471.45 | 2010.83 | 791.06 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1501.27 | 147.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5033.64 | 12-JAN-15:50 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 |
February | 19038.77 | 20-FEB-16:12 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.98 |
March | 23948.50 | 12-MAR-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 68.23 | 0.00 |
April | 27178.31 | 30-APR-15:41 | 652.28 | 283.19 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 341.18 | 0.00 |
May | 25183.97 | 28-MAY-16:01 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 902.92 | 0.00 |
June | 24591.41 | 11-JUN-15:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 199.88 | 0.00 |
July | 24421.37 | 02-JUL-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 303.57 | 0.00 |
August | 23336.05 | 06-AUG-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 248.92 | 0.00 |
September | 25278.48 | 24-SEP-15:31 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 174.65 | 0.00 |
October | 23883.60 | 09-OCT-16:01 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 35.35 | 0.00 |
November | 21964.81 | 05-NOV-15:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | 0.00 |
December | 5714.87 | 28-DEC-15:40 | 1239.33 | 509.78 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5033.64 | 326.14 | 141.60 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27178.31 | 1239.33 | 509.78 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 902.92 | 25.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3117.44 | 12-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 |
February | 8952.39 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 |
March | 10479.45 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.47 | 0.00 |
April | 19076.24 | 17-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
May | 23115.79 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 | 0.00 |
June | 22023.47 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.82 | 0.00 |
July | 22792.22 | 05-JUL-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.10 | 0.00 |
August | 21051.34 | 07-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.65 | 0.00 |
September | 19059.40 | 18-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 | 0.00 |
October | 15746.90 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11585.52 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 |
December | 6896.61 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3117.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23115.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.10 | 24.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2905.89 | 04-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4979.05 | 22-FEB-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 0.00 |
March | 9099.66 | 29-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.98 | 0.00 |
April | 14818.14 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
May | 18113.41 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.44 | 0.00 |
June | 19268.98 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.48 | 0.00 |
July | 19052.34 | 05-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.15 | 0.00 |
August | 15606.78 | 07-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.10 | 0.00 |
September | 12421.23 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.02 | 0.00 |
October | 13016.54 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6829.52 | 09-NOV-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 0.00 |
December | 3130.75 | 01-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2905.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19268.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.98 | 86.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5914.31 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.31 |
February | 13335.63 | 22-FEB-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.18 | 0.00 |
March | 22319.93 | 28-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28028.53 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.98 | 0.00 |
May | 32189.29 | 01-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.60 | 0.00 |
June | 34081.56 | 12-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.28 | 0.00 |
July | 30271.21 | 07-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.37 | 0.00 |
August | 26903.94 | 07-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.01 | 0.00 |
September | 22746.89 | 26-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.77 | 0.00 |
October | 22057.43 | 02-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.99 | 0.00 |
November | 14556.37 | 09-NOV-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.07 | 0.00 |
December | 7579.94 | 01-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5914.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34081.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.28 | 46.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1831.46 | 12-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3967.83 | 20-FEB-17:37 | 35.07 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7218.55 | 31-MAR-23:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7875.61 | 17-APR-00:23 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3531.25 | 31-MAY-23:53 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5476.55 | 30-JUN-24:00 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7370.14 | 31-JUL-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7674.39 | 20-AUG-18:35 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3526.81 | 30-SEP-24:00 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5382.02 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5889.76 | 12-NOV-16:25 | 46.77 | 70.37 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7566.16 | 28-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1831.46 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7875.61 | 222.14 | 316.63 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1670.37 | 12-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3588.62 | 21-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6972.05 | 31-MAR-23:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7280.15 | 16-APR-22:23 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3403.97 | 31-MAY-23:53 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5262.31 | 30-JUN-24:00 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6941.54 | 31-JUL-23:53 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7134.55 | 20-AUG-17:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3400.01 | 30-SEP-23:50 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5090.60 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5435.29 | 08-NOV-16:40 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7161.21 | 01-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1670.37 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7280.15 | 222.14 | 316.63 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1696.65 | 12-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3638.47 | 22-FEB-17:00 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6926.57 | 31-MAR-23:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7546.90 | 16-APR-21:32 | 0.00 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3349.95 | 31-MAY-23:53 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5331.85 | 30-JUN-24:00 | 0.00 | 52.77 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7060.90 | 31-JUL-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7366.17 | 20-AUG-17:33 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3417.94 | 30-SEP-23:40 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4959.07 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5481.76 | 09-NOV-16:40 | 222.14 | 316.63 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7166.87 | 28-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1696.65 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7546.90 | 222.14 | 316.63 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92210.78 | 26-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183793.54 | 21-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358632.65 | 31-MAR-23:55 | 0.00 | 461.88 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368926.98 | 30-APR-04:53 | 0.00 | 692.81 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176148.05 | 31-MAY-23:53 | 0.00 | 692.81 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268359.73 | 30-JUN-23:53 | 0.00 | 692.81 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 356945.93 | 31-JUL-23:13 | 0.00 | 692.81 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369732.45 | 15-AUG-23:53 | 0.00 | 692.81 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177625.41 | 30-SEP-24:00 | 0.00 | 461.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269348.56 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277063.71 | 13-NOV-17:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368199.74 | 18-DEC-17:00 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92210.78 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369732.45 | 4808.68 | 4157.19 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.159380E+13 | 1039665.06 | 12-JAN-16:10 | 0.100742E+12 | 717777.95 | 02-JAN-06:10 |
February | 0.189004E+13 | 1313183.41 | 22-FEB-16:10 | 0.592133E+11 | 284759.42 | 11-FEB-06:10 |
March | 0.270103E+13 | 1632042.84 | 28-MAR-15:00 | 0.575196E+11 | 72266.21 | 01-MAR-12:20 |
April | 0.320994E+13 | 1898824.76 | 18-APR-15:09 | 0.500085E+11 | 67377.62 | 04-APR-11:20 |
May | 0.230121E+13 | 1497541.29 | 30-MAY-15:09 | 0.489766E+11 | 61590.22 | 02-MAY-11:50 |
June | 0.276867E+13 | 1730436.76 | 22-JUN-15:09 | 0.451638E+11 | 54619.55 | 01-JUN-11:30 |
July | 0.325985E+13 | 1922872.88 | 05-JUL-15:00 | 0.434731E+11 | 48991.52 | 07-JUL-11:20 |
August | 0.369173E+13 | 2026463.93 | 07-AUG-15:20 | 0.465425E+11 | 53552.05 | 31-AUG-11:50 |
September | 0.217840E+13 | 1496089.84 | 14-SEP-15:30 | 0.459713E+11 | 60256.66 | 29-SEP-11:20 |
October | 0.238238E+13 | 1506845.74 | 03-OCT-15:09 | 0.510080E+11 | 67098.43 | 31-OCT-11:50 |
November | 0.252163E+13 | 1592128.85 | 08-NOV-16:30 | 0.535830E+11 | 71309.75 | 27-NOV-12:39 |
December | 0.284005E+13 | 1513222.85 | 28-DEC-16:10 | 0.695764E+11 | 297522.96 | 23-DEC-06:10 |
Annual Sum or Average | 0.313387E+14 | 0.671778E+12 | ||||
Minimum of Months | 0.159380E+13 | 1039665.06 | 0.434731E+11 | 48991.52 | ||
Maximum of Months | 0.369173E+13 | 2026463.93 | 0.100742E+12 | 717777.95 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.206783E+12 | 0.361832E+11 | 0.766053E+12 | 0.162121E+12 | 0.162642E+12 | 0.410099E+11 | 0.00 | 0.149154E+12 | 0.578953E+11 | 0.119614E+11 | 0.00 | 0.00 | 0.00 |
February | 0.186910E+12 | 0.303449E+11 | 0.978954E+12 | 0.146439E+12 | 0.160275E+12 | 0.395385E+11 | 0.00 | 0.244270E+12 | 0.901196E+11 | 0.131848E+11 | 0.00 | 0.00 | 0.00 |
March | 0.220926E+12 | 0.301927E+11 | 0.141687E+13 | 0.162292E+12 | 0.214074E+12 | 0.563244E+11 | 0.00 | 0.464774E+12 | 0.128583E+12 | 0.699579E+10 | 0.00 | 0.00 | 0.00 |
April | 0.196482E+12 | 0.260362E+11 | 0.165903E+13 | 0.156876E+12 | 0.247619E+12 | 0.750358E+11 | 0.00 | 0.699921E+12 | 0.148031E+12 | 0.915760E+09 | 0.00 | 0.00 | 0.00 |
May | 0.211614E+12 | 0.240896E+11 | 0.774844E+12 | 0.162206E+12 | 0.278379E+12 | 0.867587E+11 | 0.00 | 0.573438E+12 | 0.189862E+12 | 15773178.50 | 0.00 | 0.00 | 0.00 |
June | 0.210701E+12 | 0.218994E+11 | 0.106252E+13 | 0.157035E+12 | 0.275788E+12 | 0.898056E+11 | 0.00 | 0.750453E+12 | 0.200473E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197509E+12 | 0.235907E+11 | 0.139340E+13 | 0.162046E+12 | 0.263010E+12 | 0.946903E+11 | 0.00 | 0.912141E+12 | 0.213455E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.220711E+12 | 0.257509E+11 | 0.173200E+13 | 0.162292E+12 | 0.267595E+12 | 0.968062E+11 | 0.00 | 0.973369E+12 | 0.213203E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197370E+12 | 0.276816E+11 | 0.740713E+12 | 0.156875E+12 | 0.231236E+12 | 0.818939E+11 | 0.00 | 0.546914E+12 | 0.195712E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205724E+12 | 0.320159E+11 | 0.108340E+13 | 0.162121E+12 | 0.219968E+12 | 0.650952E+11 | 0.00 | 0.461989E+12 | 0.150699E+12 | 0.136535E+10 | 0.00 | 0.00 | 0.00 |
November | 0.204319E+12 | 0.341881E+11 | 0.135889E+13 | 0.156940E+12 | 0.187141E+12 | 0.485525E+11 | 0.00 | 0.401663E+12 | 0.116010E+12 | 0.139231E+11 | 0.00 | 0.00 | 0.00 |
December | 0.200409E+12 | 0.373354E+11 | 0.170972E+13 | 0.162046E+12 | 0.169985E+12 | 0.433102E+11 | 0.00 | 0.374140E+12 | 0.108161E+12 | 0.349397E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245946E+13 | 0.349309E+12 | 0.146764E+14 | 0.190929E+13 | 0.267771E+13 | 0.818821E+12 | 0.00 | 0.655222E+13 | 0.181221E+13 | 0.833016E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.186910E+12 | 0.218994E+11 | 0.740713E+12 | 0.146439E+12 | 0.160275E+12 | 0.395385E+11 | 0.00 | 0.149154E+12 | 0.578953E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220926E+12 | 0.373354E+11 | 0.173200E+13 | 0.162292E+12 | 0.278379E+12 | 0.968062E+11 | 0.00 | 0.973369E+12 | 0.213455E+12 | 0.349397E+11 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.423172E+11 | 0.00 | 0.584247E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.695091E+10 | 0.00 | 0.522623E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 258839.46 | 0.00 | 0.575193E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.500085E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.489766E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.451638E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.434731E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.465425E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.459713E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.510080E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.284917E+09 | 0.00 | 0.532981E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.131261E+11 | 0.00 | 0.564502E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.626794E+11 | 0.00 | 0.609098E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.434731E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.423172E+11 | 0.00 | 0.584247E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 233997.28 | 18-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 116883.93 | 18-JAN-08:20 | 108255.39 | 12-JAN-15:30 | 26939.00 | 02-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 232898.07 | 10-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 116883.34 | 10-FEB-08:20 | 149236.55 | 22-FEB-15:00 | 26507.40 | 23-FEB-13:00 | 0.00 | 01-FEB-00:10 |
March | 233370.01 | 14-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 116883.59 | 14-MAR-07:19 | 187844.65 | 13-MAR-15:00 | 48815.07 | 24-MAR-15:30 | 0.00 | 01-MAR-00:10 |
April | 216805.19 | 03-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 116874.83 | 03-APR-07:19 | 226631.24 | 17-APR-15:20 | 49364.92 | 28-APR-07:00 | 0.00 | 01-APR-00:10 |
May | 221022.76 | 24-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 116877.06 | 24-MAY-07:19 | 261755.79 | 30-MAY-14:20 | 51499.04 | 05-MAY-07:00 | 0.00 | 01-MAY-00:10 |
June | 221165.50 | 23-JUN-07:10 | 40855.88 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 116877.13 | 23-JUN-07:19 | 260412.47 | 13-JUN-14:20 | 49851.74 | 13-JUN-15:30 | 0.00 | 01-JUN-00:10 |
July | 232541.22 | 26-JUL-07:10 | 40855.88 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 116883.16 | 26-JUL-07:19 | 271533.23 | 05-JUL-15:00 | 50823.81 | 05-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 234187.88 | 16-AUG-07:10 | 40855.88 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 116884.03 | 16-AUG-07:19 | 244835.93 | 07-AUG-15:20 | 49454.83 | 07-AUG-15:50 | 0.00 | 01-AUG-00:10 |
September | 235834.97 | 08-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 116884.90 | 08-SEP-07:19 | 214420.61 | 21-SEP-15:00 | 48818.82 | 14-SEP-14:30 | 0.00 | 01-SEP-00:10 |
October | 239082.52 | 11-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 116886.62 | 11-OCT-07:19 | 195884.25 | 10-OCT-15:20 | 49922.66 | 24-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 234185.02 | 27-NOV-16:00 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 116878.08 | 03-NOV-07:19 | 157923.43 | 09-NOV-16:19 | 49984.01 | 01-NOV-14:50 | 0.00 | 01-NOV-00:10 |
December | 236669.35 | 29-DEC-16:00 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 116877.17 | 29-DEC-08:20 | 124612.45 | 01-DEC-15:39 | 25786.29 | 23-DEC-06:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 216805.19 | 40855.88 | 423497.50 | 116874.83 | 108255.39 | 25786.29 | 0.00 | |||||||
Maximum of Months | 239082.52 | 40855.88 | 778371.69 | 116886.62 | 271533.23 | 51499.04 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 148536.58 | 12-JAN-15:09 | 44954.30 | 12-JAN-15:50 | 7516.09 | 21-JAN-17:40 | 0.00 | 0.00 | 0.00 |
February | 260809.86 | 22-FEB-15:30 | 64014.84 | 24-FEB-14:00 | 11130.16 | 04-FEB-05:00 | 0.00 | 0.00 | 0.00 |
March | 376928.80 | 10-MAR-13:09 | 84253.44 | 06-MAR-13:30 | 13983.22 | 01-MAR-05:00 | 0.00 | 0.00 | 0.00 |
April | 483519.89 | 18-APR-15:50 | 84253.44 | 01-APR-14:30 | 9594.95 | 15-APR-11:09 | 0.00 | 0.00 | 0.00 |
May | 438791.47 | 30-MAY-15:09 | 84253.44 | 01-MAY-06:49 | 2109.57 | 28-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 549898.85 | 22-JUN-15:39 | 84253.44 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 561817.52 | 05-JUL-15:00 | 84253.44 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 580696.71 | 28-AUG-14:30 | 84253.44 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 438208.63 | 14-SEP-15:30 | 84253.44 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 390444.81 | 03-OCT-14:00 | 84253.44 | 02-OCT-07:00 | 7282.20 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 |
November | 361704.30 | 02-NOV-14:00 | 84253.44 | 06-NOV-11:39 | 15172.82 | 30-NOV-22:00 | 0.00 | 0.00 | 0.00 |
December | 260250.05 | 28-DEC-15:09 | 45629.64 | 28-DEC-14:00 | 28624.24 | 22-DEC-05:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 148536.58 | 44954.30 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 580696.71 | 84253.44 | 28624.24 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1039665.06 | 12-JAN-16:10 | 213980.32 | 423497.50 | 0.00 | 82829.33 | 104367.48 | 25165.44 | 0.00 | 144898.84 | 44926.14 |
February | 1313183.41 | 22-FEB-16:10 | 212815.01 | 541788.89 | 0.00 | 82829.33 | 147338.48 | 26036.97 | 0.00 | 255164.26 | 47210.47 |
March | 1632042.84 | 28-MAR-15:00 | 212815.01 | 660080.29 | 0.00 | 82829.33 | 171186.85 | 47709.61 | 0.00 | 373168.30 | 84253.44 |
April | 1898824.76 | 18-APR-15:09 | 212815.01 | 778371.69 | 0.00 | 82829.33 | 213692.28 | 48282.84 | 0.00 | 478580.16 | 84253.44 |
May | 1497541.29 | 30-MAY-15:09 | 212815.01 | 423497.50 | 0.00 | 82829.33 | 205752.94 | 49601.60 | 0.00 | 438791.47 | 84253.44 |
June | 1730436.76 | 22-JUN-15:09 | 212815.01 | 541788.89 | 0.00 | 82829.33 | 216748.05 | 49567.61 | 0.00 | 542434.42 | 84253.44 |
July | 1922872.88 | 05-JUL-15:00 | 212815.01 | 660080.29 | 0.00 | 82829.33 | 271533.23 | 49544.05 | 0.00 | 561817.52 | 84253.44 |
August | 2026463.93 | 07-AUG-15:20 | 212815.01 | 778371.69 | 0.00 | 82829.33 | 244835.93 | 49401.22 | 0.00 | 573957.31 | 84253.44 |
September | 1496089.84 | 14-SEP-15:30 | 212815.01 | 423497.50 | 0.00 | 82829.33 | 205686.41 | 48799.52 | 0.00 | 438208.63 | 84253.44 |
October | 1506845.74 | 03-OCT-15:09 | 212815.01 | 541788.89 | 0.00 | 82829.33 | 147192.71 | 48662.66 | 0.00 | 389303.69 | 84253.44 |
November | 1592128.85 | 08-NOV-16:30 | 215154.03 | 660080.29 | 0.00 | 82830.25 | 150976.54 | 47178.83 | 0.00 | 351655.45 | 84253.44 |
December | 1513222.85 | 28-DEC-16:10 | 214134.75 | 778371.69 | 0.00 | 82829.86 | 114111.49 | 25210.95 | 0.00 | 253134.70 | 45429.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1039665.06 | 212815.01 | 423497.50 | 0.00 | 82829.33 | 104367.48 | 25165.44 | 0.00 | 144898.84 | 44926.14 | |
Maximum of Months | 2026463.93 | 215154.03 | 778371.69 | 0.00 | 82830.25 | 271533.23 | 49601.60 | 0.00 | 573957.31 | 84253.44 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 710497.07 | 02-JAN-06:10 | 0.00 | 74451.23 | 17-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 256619.57 | 11-FEB-06:10 | 0.00 | 74164.99 | 02-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 287.59 | 01-MAR-06:49 | 0.00 | 72266.21 | 01-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 67377.62 | 04-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 61590.22 | 02-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 54619.55 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 48991.52 | 07-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 53552.05 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 60256.66 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 67098.43 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 43693.81 | 27-NOV-06:30 | 0.00 | 71309.75 | 27-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 290242.08 | 23-DEC-06:10 | 0.00 | 73608.65 | 22-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 48991.52 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 710497.07 | 0.00 | 74451.23 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.76 | 1.00 | 26.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.52 | 0.50 | 26.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.89 | 0.00 | 25.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.44 | 0.00 | 26.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 26.24 | 0.17 | 26.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.30 | 0.00 | 26.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.10 | 0.33 | 26.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 25.76 | 1.33 | 25.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 26.56 | 1.33 | 26.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.68 | 0.50 | 26.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 26.93 | 1.17 | 26.96 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.00 | 1.33 | 27.00 |
Annual Sum or Average | 0.00 | 0.00 | 85.17 | 26.48 | 7.67 | 26.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.76 | 0.00 | 25.71 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 27.00 | 1.33 | 27.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.81 | 0.00 | 25.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.78 | 0.00 | 25.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.62 | 0.00 | 25.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.65 | 0.17 | 25.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.63 | 0.50 | 25.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.72 | 0.00 | 25.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 10.83 | 25.67 | 0.67 | 25.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 25.81 | 0.50 | 25.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.93 | 0.00 | 25.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.70 | 0.00 | 25.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.96 | 0.00 | 25.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.65 | 0.00 | 25.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.96 | 0.00 | 18.96 | 2.17 | 24.24 | 0.00 | 24.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.96 | 0.00 | 18.96 | 0.83 | 25.96 | 0.00 | 25.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.00 | 6.00 | 27.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 27.18 | 10.00 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 26.97 | 6.83 | 27.12 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 27.25 | 12.83 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.00 | 8.33 | 27.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.86 | 2.83 | 27.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.31 | 0.67 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 123.83 | 27.09 | 47.50 | 27.24 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 27.31 | 12.83 | 27.37 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.35 | 0.50 | 27.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.49 | 4.50 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 27.45 | 12.50 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 27.48 | 13.33 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 27.14 | 10.50 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 27.44 | 13.50 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.15 | 8.33 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.27 | 5.00 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.53 | 9.50 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.31 | 1.00 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 152.67 | 27.36 | 78.67 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 27.53 | 13.50 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.42 | 1.50 | 27.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.79 | 5.50 | 27.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.72 | 6.50 | 27.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.32 | 10.50 | 27.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.25 | 10.33 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 26.99 | 7.33 | 27.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 27.27 | 12.67 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.07 | 8.33 | 27.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.18 | 4.50 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.68 | 12.83 | 27.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.00 | 11.50 | 28.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.64 | 5.67 | 27.64 |
Annual Sum or Average | 0.00 | 0.00 | 194.33 | 27.34 | 97.17 | 27.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.99 | 1.50 | 27.14 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 28.00 | 12.83 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.75 | 3.67 | 27.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.37 | 7.50 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 77.67 | 27.84 | 23.50 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 65.33 | 27.60 | 19.00 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 27.63 | 18.00 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 80.83 | 27.75 | 24.17 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 | 27.81 | 22.33 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 27.12 | 11.67 | 27.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 27.47 | 12.00 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.52 | 8.33 | 27.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.48 | 4.83 | 27.52 |
Annual Sum or Average | 0.00 | 0.00 | 469.33 | 27.65 | 155.00 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 80.83 | 27.84 | 24.17 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.19 | 3.83 | 27.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.26 | 10.00 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.02 | 6.17 | 27.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.24 | 11.67 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 26.88 | 6.00 | 27.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.10 | 2.33 | 27.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.20 | 0.00 | 19.20 | 101.83 | 27.12 | 40.50 | 27.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.20 | 0.00 | 19.20 | 27.33 | 27.29 | 11.67 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.56 | 4.83 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.56 | 12.33 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 27.53 | 13.50 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 27.25 | 11.17 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 27.45 | 15.17 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.13 | 8.33 | 27.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.23 | 4.83 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.69 | 9.83 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.28 | 0.00 | 19.28 | 172.00 | 27.40 | 80.00 | 27.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.28 | 0.00 | 19.28 | 36.00 | 27.69 | 15.17 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.47 | 1.67 | 27.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.88 | 4.83 | 27.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.82 | 6.17 | 27.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.39 | 8.67 | 27.55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 27.28 | 10.17 | 27.43 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 27.00 | 6.33 | 27.16 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.25 | 11.67 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.04 | 7.00 | 27.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.16 | 4.33 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.47 | 15.33 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.04 | 11.67 | 28.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.66 | 4.33 | 27.66 |
Annual Sum or Average | 0.00 | 0.00 | 175.17 | 27.35 | 92.17 | 27.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.00 | 1.67 | 27.16 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 28.04 | 15.33 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.50 | 1.17 | 27.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.78 | 3.33 | 27.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.49 | 10.17 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 | 27.57 | 16.00 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 27.47 | 12.33 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 | 27.49 | 15.83 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 27.19 | 8.67 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.07 | 6.17 | 27.25 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.73 | 6.33 | 27.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.54 | 2.50 | 27.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 253.17 | 27.45 | 82.50 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 55.50 | 27.78 | 16.00 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.39 | 6.00 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 27.48 | 10.67 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 27.25 | 8.00 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 27.41 | 13.33 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 27.14 | 7.17 | 27.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.25 | 3.83 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.46 | 1.67 | 27.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Annual Sum or Average | 2.17 | 19.08 | 0.00 | 19.08 | 136.33 | 27.21 | 50.67 | 27.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.36 | 0.00 | 19.36 | 34.17 | 27.48 | 13.33 | 27.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.55 | 5.33 | 27.56 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 27.74 | 12.83 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 27.68 | 14.17 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 27.42 | 11.17 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 27.56 | 16.17 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 27.27 | 8.83 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.40 | 6.50 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 27.73 | 10.00 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Annual Sum or Average | 1.33 | 19.05 | 0.00 | 19.05 | 203.00 | 27.49 | 85.00 | 27.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.42 | 0.00 | 19.42 | 44.00 | 27.74 | 16.17 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.82 | 0.00 | 18.82 | 0.17 | 20.95 | 0.17 | 22.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.83 | 4.00 | 27.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.89 | 6.00 | 27.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.59 | 9.33 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 27.48 | 11.00 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27.24 | 7.83 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 | 27.42 | 13.00 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.22 | 7.67 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.36 | 6.67 | 27.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 28.15 | 11.67 | 28.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 28.04 | 10.33 | 28.05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.59 | 1.83 | 27.59 |
Annual Sum or Average | 0.50 | 18.82 | 0.00 | 18.82 | 197.17 | 27.50 | 89.50 | 27.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 20.95 | 0.17 | 22.22 |
Maximum of Months | 0.50 | 18.82 | 0.00 | 18.82 | 34.50 | 28.15 | 13.00 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.52 | 1.00 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.86 | 3.67 | 27.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 27.62 | 11.17 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 27.69 | 16.33 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 27.60 | 12.83 | 27.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 27.61 | 16.17 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 27.34 | 9.33 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 27.24 | 7.50 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.95 | 6.83 | 28.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.62 | 2.17 | 27.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 18.85 | 0.00 | 18.85 | 266.00 | 27.57 | 87.00 | 27.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.85 | 0.00 | 18.85 | 57.50 | 27.95 | 16.33 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 128.33 | 28.21 | 110.50 | 28.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 349.83 | 28.17 | 269.67 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 478.17 | 28.18 | 380.17 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 349.83 | 28.21 | 269.67 | 28.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 176.33 | 28.24 | 154.33 | 28.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 387.67 | 28.19 | 308.17 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 564.00 | 28.21 | 462.50 | 28.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 387.67 | 28.24 | 308.17 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 117.83 | 28.27 | 101.50 | 28.25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 238.50 | 28.15 | 198.00 | 28.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 356.33 | 28.19 | 299.50 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 238.50 | 28.27 | 198.00 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 549.67 | 29.51 | 411.17 | 29.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.32 | 0.00 | 28.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 30.29 | 514.00 | 30.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1293.83 | 29.96 | 925.17 | 30.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 30.29 | 514.00 | 30.37 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 24.82 | 278.50 | 24.97 | 0.33 | 24.98 |
February | 12.17 | 26.68 | 351.83 | 24.74 | 12.17 | 24.80 |
March | 34.83 | 25.05 | 432.67 | 24.55 | 34.83 | 24.59 |
April | 29.83 | 24.23 | 412.17 | 24.60 | 29.83 | 24.58 |
May | 281.17 | 24.47 | 492.33 | 24.51 | 281.17 | 24.50 |
June | 325.83 | 24.60 | 496.00 | 24.53 | 325.83 | 24.55 |
July | 286.83 | 25.11 | 497.00 | 24.81 | 286.83 | 24.89 |
August | 229.83 | 25.09 | 514.00 | 24.68 | 229.83 | 24.78 |
September | 275.67 | 25.02 | 485.00 | 24.74 | 275.67 | 24.81 |
October | 97.67 | 25.25 | 502.00 | 24.73 | 97.67 | 24.80 |
November | 0.67 | 27.33 | 466.33 | 24.66 | 0.67 | 24.66 |
December | 0.00 | 0.00 | 369.50 | 24.81 | 0.00 | 24.81 |
Annual Sum or Average | 1575.83 | 24.87 | 5297.33 | 24.68 | 1574.83 | 24.71 |
Minimum of Months | 0.00 | 0.00 | 278.50 | 24.51 | 0.00 | 24.50 |
Maximum of Months | 325.83 | 27.33 | 514.00 | 24.97 | 325.83 | 24.98 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.83 | 25.09 | 218.17 | 24.78 | 12.83 | 24.83 |
February | 3.00 | 26.34 | 352.67 | 24.44 | 3.00 | 24.46 |
March | 0.83 | 26.58 | 458.67 | 24.30 | 0.83 | 24.31 |
April | 0.00 | 0.00 | 452.00 | 24.29 | 0.00 | 24.29 |
May | 0.00 | 0.00 | 499.50 | 24.22 | 0.00 | 24.22 |
June | 0.00 | 0.00 | 496.00 | 24.21 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 497.00 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 514.00 | 24.26 | 0.00 | 24.26 |
September | 0.33 | 26.56 | 485.00 | 24.27 | 0.33 | 24.28 |
October | 0.00 | 0.00 | 502.00 | 24.36 | 0.00 | 24.36 |
November | 0.00 | 0.00 | 468.17 | 24.44 | 0.00 | 24.44 |
December | 3.50 | 24.00 | 351.50 | 24.54 | 0.00 | 24.54 |
Annual Sum or Average | 27.50 | 25.15 | 5294.67 | 24.34 | 17.00 | 24.35 |
Minimum of Months | 0.00 | 0.00 | 218.17 | 24.21 | 0.00 | 24.21 |
Maximum of Months | 19.83 | 26.58 | 514.00 | 24.78 | 12.83 | 24.83 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 239.67 | 23.27 | 83.50 | 23.46 | 12.50 | 23.39 |
February | 82.50 | 23.72 | 217.33 | 24.14 | 8.67 | 24.18 |
March | 4.33 | 24.70 | 396.17 | 24.26 | 2.17 | 24.27 |
April | 0.00 | 0.00 | 406.83 | 24.19 | 0.00 | 24.19 |
May | 0.00 | 0.00 | 491.50 | 24.14 | 0.00 | 24.14 |
June | 1.17 | 26.31 | 496.00 | 24.17 | 1.17 | 24.17 |
July | 0.00 | 0.00 | 497.00 | 24.17 | 0.00 | 24.17 |
August | 0.00 | 0.00 | 514.00 | 24.17 | 0.00 | 24.17 |
September | 2.50 | 26.02 | 485.00 | 24.24 | 2.50 | 24.25 |
October | 0.00 | 0.00 | 494.67 | 24.30 | 0.00 | 24.30 |
November | 10.17 | 23.69 | 373.67 | 24.29 | 0.00 | 24.29 |
December | 144.17 | 23.53 | 92.33 | 23.86 | 0.00 | 23.86 |
Annual Sum or Average | 484.50 | 23.47 | 4548.00 | 24.14 | 27.00 | 24.14 |
Minimum of Months | 0.00 | 0.00 | 83.50 | 23.46 | 0.00 | 23.39 |
Maximum of Months | 239.67 | 26.31 | 514.00 | 24.30 | 12.50 | 24.30 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 418.17 | 22.37 | 36.00 | 22.27 | 22.17 | 22.13 |
February | 207.17 | 23.03 | 135.33 | 23.47 | 8.50 | 23.50 |
March | 31.83 | 23.62 | 364.17 | 24.17 | 3.50 | 24.18 |
April | 0.33 | 26.64 | 424.33 | 24.28 | 0.33 | 24.28 |
May | 4.00 | 26.54 | 503.83 | 24.28 | 4.00 | 24.30 |
June | 3.50 | 26.38 | 496.00 | 24.26 | 3.50 | 24.28 |
July | 0.83 | 26.58 | 497.00 | 24.29 | 0.83 | 24.30 |
August | 0.00 | 0.00 | 514.00 | 24.24 | 0.00 | 24.24 |
September | 2.17 | 25.97 | 484.67 | 24.29 | 2.17 | 24.30 |
October | 0.00 | 0.00 | 486.33 | 24.29 | 0.00 | 24.29 |
November | 94.17 | 23.20 | 263.00 | 23.92 | 0.00 | 23.92 |
December | 357.83 | 22.70 | 35.83 | 22.79 | 4.00 | 22.77 |
Annual Sum or Average | 1120.00 | 22.74 | 4240.50 | 23.91 | 49.00 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 35.83 | 22.27 | 0.00 | 22.13 |
Maximum of Months | 418.17 | 26.64 | 514.00 | 24.29 | 22.17 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 372.50 | 22.88 | 22.67 | 22.94 | 0.00 | 22.94 |
February | 164.33 | 23.18 | 160.83 | 23.68 | 0.00 | 23.68 |
March | 19.83 | 23.58 | 396.83 | 24.25 | 0.33 | 24.25 |
April | 22.50 | 26.93 | 462.33 | 24.59 | 22.50 | 24.70 |
May | 43.33 | 26.89 | 508.00 | 24.70 | 43.33 | 24.86 |
June | 47.67 | 26.73 | 496.00 | 24.67 | 47.67 | 24.83 |
July | 71.67 | 26.83 | 497.00 | 24.88 | 71.67 | 25.10 |
August | 42.50 | 26.85 | 514.00 | 24.63 | 42.50 | 24.79 |
September | 37.83 | 26.52 | 485.00 | 24.61 | 37.83 | 24.74 |
October | 8.83 | 26.79 | 494.83 | 24.44 | 8.83 | 24.48 |
November | 46.50 | 23.49 | 336.67 | 24.18 | 0.00 | 24.18 |
December | 269.83 | 23.24 | 59.67 | 23.40 | 0.00 | 23.40 |
Annual Sum or Average | 1147.33 | 23.98 | 4433.83 | 24.34 | 274.67 | 24.45 |
Minimum of Months | 8.83 | 22.88 | 22.67 | 22.94 | 0.00 | 22.94 |
Maximum of Months | 372.50 | 26.93 | 514.00 | 24.88 | 71.67 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 257.67 | 23.01 | 54.17 | 23.21 | 0.00 | 23.21 |
February | 99.67 | 23.06 | 233.83 | 23.98 | 0.33 | 23.99 |
March | 33.17 | 25.10 | 435.17 | 24.42 | 15.83 | 24.50 |
April | 43.83 | 27.01 | 468.67 | 24.74 | 43.83 | 24.91 |
May | 58.50 | 27.02 | 508.00 | 24.82 | 58.50 | 25.03 |
June | 54.17 | 26.81 | 496.00 | 24.71 | 54.17 | 24.90 |
July | 70.50 | 26.91 | 497.00 | 24.88 | 70.50 | 25.10 |
August | 38.17 | 26.90 | 514.00 | 24.59 | 38.17 | 24.74 |
September | 43.17 | 26.57 | 485.00 | 24.65 | 43.17 | 24.79 |
October | 43.67 | 26.85 | 495.50 | 24.68 | 43.67 | 24.85 |
November | 44.67 | 23.82 | 376.33 | 24.35 | 5.50 | 24.38 |
December | 220.67 | 23.14 | 116.83 | 23.57 | 0.00 | 23.57 |
Annual Sum or Average | 1007.83 | 24.50 | 4680.50 | 24.48 | 373.67 | 24.62 |
Minimum of Months | 33.17 | 23.01 | 54.17 | 23.21 | 0.00 | 23.21 |
Maximum of Months | 257.67 | 27.02 | 514.00 | 24.88 | 70.50 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 184.33 | 23.01 | 205.67 | 23.71 | 1.17 | 23.72 |
February | 91.50 | 23.65 | 310.83 | 24.31 | 14.83 | 24.40 |
March | 37.33 | 25.94 | 452.00 | 24.54 | 25.67 | 24.66 |
April | 41.50 | 26.98 | 473.50 | 24.73 | 41.50 | 24.90 |
May | 45.33 | 26.93 | 508.00 | 24.73 | 45.33 | 24.89 |
June | 46.83 | 26.75 | 496.00 | 24.66 | 46.83 | 24.83 |
July | 70.17 | 26.84 | 497.00 | 24.88 | 70.17 | 25.09 |
August | 43.67 | 26.89 | 514.00 | 24.65 | 43.67 | 24.81 |
September | 47.50 | 26.65 | 485.00 | 24.71 | 47.50 | 24.87 |
October | 52.33 | 27.09 | 502.00 | 24.85 | 52.33 | 25.04 |
November | 57.83 | 26.25 | 436.67 | 24.79 | 44.50 | 24.98 |
December | 111.17 | 23.65 | 285.33 | 24.30 | 13.67 | 24.39 |
Annual Sum or Average | 829.50 | 25.14 | 5166.00 | 24.61 | 447.17 | 24.77 |
Minimum of Months | 37.33 | 23.01 | 205.67 | 23.71 | 1.17 | 23.72 |
Maximum of Months | 184.33 | 27.09 | 514.00 | 24.88 | 70.17 | 25.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 144.17 | 23.31 | 179.33 | 23.91 | 0.00 | 23.91 |
February | 34.83 | 24.96 | 347.50 | 24.58 | 14.67 | 24.67 |
March | 38.83 | 26.97 | 500.50 | 24.72 | 38.83 | 24.87 |
April | 105.83 | 26.83 | 485.00 | 25.06 | 105.83 | 25.33 |
May | 100.50 | 26.95 | 508.00 | 25.02 | 100.50 | 25.29 |
June | 94.33 | 26.87 | 496.00 | 24.95 | 94.33 | 25.21 |
July | 117.67 | 26.97 | 497.00 | 25.15 | 117.67 | 25.44 |
August | 99.17 | 26.99 | 514.00 | 24.98 | 99.17 | 25.26 |
September | 85.33 | 26.85 | 485.00 | 24.95 | 85.33 | 25.19 |
October | 75.83 | 26.95 | 502.00 | 24.97 | 75.83 | 25.20 |
November | 37.67 | 26.98 | 470.67 | 24.82 | 37.67 | 24.97 |
December | 23.67 | 25.70 | 370.83 | 24.73 | 14.00 | 24.81 |
Annual Sum or Average | 957.83 | 26.28 | 5355.83 | 24.87 | 783.83 | 25.10 |
Minimum of Months | 23.67 | 23.31 | 179.33 | 23.91 | 0.00 | 23.91 |
Maximum of Months | 144.17 | 26.99 | 514.00 | 25.15 | 117.67 | 25.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.33 | 21.74 | 41.33 | 21.61 | 41.33 | 21.49 |
February | 326.67 | 22.53 | 55.00 | 22.75 | 1.33 | 22.74 |
March | 97.33 | 23.28 | 302.67 | 23.99 | 0.00 | 23.99 |
April | 14.50 | 26.66 | 438.33 | 24.53 | 13.33 | 24.60 |
May | 45.67 | 26.88 | 508.00 | 24.72 | 45.67 | 24.89 |
June | 58.00 | 26.63 | 496.00 | 24.71 | 58.00 | 24.89 |
July | 96.83 | 26.58 | 497.00 | 24.94 | 96.83 | 25.17 |
August | 57.67 | 26.49 | 514.00 | 24.66 | 57.67 | 24.83 |
September | 54.67 | 26.31 | 485.00 | 24.66 | 54.67 | 24.81 |
October | 16.83 | 24.01 | 469.17 | 24.34 | 4.33 | 24.36 |
November | 199.00 | 22.95 | 150.67 | 23.44 | 0.00 | 23.44 |
December | 478.67 | 22.13 | 22.00 | 22.05 | 22.00 | 21.98 |
Annual Sum or Average | 1939.17 | 23.01 | 3979.17 | 23.93 | 395.17 | 24.03 |
Minimum of Months | 14.50 | 21.74 | 22.00 | 21.61 | 0.00 | 21.49 |
Maximum of Months | 493.33 | 26.88 | 514.00 | 24.94 | 96.83 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 376.33 | 22.34 | 19.83 | 22.27 | 15.17 | 22.19 |
February | 163.50 | 22.73 | 124.67 | 23.45 | 0.00 | 23.45 |
March | 49.17 | 24.42 | 329.00 | 24.48 | 16.00 | 24.58 |
April | 47.67 | 27.02 | 390.67 | 24.95 | 47.67 | 25.15 |
May | 68.17 | 27.03 | 430.00 | 25.02 | 68.17 | 25.26 |
June | 68.50 | 26.80 | 418.00 | 24.93 | 68.50 | 25.16 |
July | 103.00 | 26.72 | 422.00 | 25.15 | 103.00 | 25.41 |
August | 59.83 | 26.68 | 433.00 | 24.84 | 59.83 | 25.04 |
September | 64.00 | 26.50 | 410.00 | 24.88 | 64.00 | 25.07 |
October | 48.67 | 26.59 | 411.17 | 24.84 | 45.33 | 25.02 |
November | 90.00 | 23.20 | 256.33 | 24.14 | 1.50 | 24.15 |
December | 315.50 | 22.59 | 7.00 | 22.59 | 3.00 | 22.57 |
Annual Sum or Average | 1454.33 | 23.96 | 3651.67 | 24.42 | 492.17 | 24.61 |
Minimum of Months | 47.67 | 22.34 | 7.00 | 22.27 | 0.00 | 22.19 |
Maximum of Months | 376.33 | 27.03 | 433.00 | 25.15 | 103.00 | 25.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 237.67 | 22.55 | 173.00 | 23.26 | 6.50 | 23.24 |
February | 127.50 | 23.15 | 264.00 | 24.06 | 14.33 | 24.17 |
March | 56.83 | 24.89 | 420.33 | 24.49 | 24.00 | 24.61 |
April | 34.17 | 26.99 | 461.00 | 24.72 | 34.17 | 24.86 |
May | 47.00 | 26.92 | 508.00 | 24.74 | 47.00 | 24.91 |
June | 56.33 | 26.63 | 496.00 | 24.70 | 56.33 | 24.88 |
July | 95.50 | 26.59 | 497.00 | 24.94 | 95.50 | 25.17 |
August | 58.83 | 26.58 | 514.00 | 24.69 | 58.83 | 24.86 |
September | 65.33 | 26.51 | 485.00 | 24.78 | 65.33 | 24.97 |
October | 55.33 | 27.09 | 499.50 | 24.89 | 55.33 | 25.09 |
November | 77.33 | 25.36 | 409.67 | 24.71 | 42.83 | 24.91 |
December | 170.50 | 23.02 | 225.00 | 23.91 | 11.00 | 23.99 |
Annual Sum or Average | 1082.33 | 24.61 | 4952.50 | 24.55 | 511.17 | 24.72 |
Minimum of Months | 34.17 | 22.55 | 173.00 | 23.26 | 6.50 | 23.24 |
Maximum of Months | 237.67 | 27.09 | 514.00 | 24.94 | 95.50 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 398.17 | 22.27 | 40.50 | 22.33 | 13.50 | 22.27 |
February | 193.17 | 22.73 | 162.83 | 23.48 | 1.17 | 23.49 |
March | 47.17 | 24.50 | 397.33 | 24.42 | 14.50 | 24.50 |
April | 53.33 | 26.99 | 477.50 | 24.84 | 53.33 | 25.03 |
May | 89.17 | 26.95 | 508.00 | 24.97 | 89.17 | 25.22 |
June | 85.50 | 26.84 | 496.00 | 24.89 | 85.50 | 25.14 |
July | 108.33 | 26.82 | 497.00 | 25.06 | 108.33 | 25.33 |
August | 73.00 | 26.81 | 514.00 | 24.81 | 73.00 | 25.03 |
September | 76.17 | 26.66 | 485.00 | 24.86 | 76.17 | 25.08 |
October | 33.17 | 26.92 | 492.33 | 24.69 | 33.17 | 24.83 |
November | 89.17 | 23.54 | 312.00 | 24.18 | 9.17 | 24.24 |
December | 340.17 | 22.64 | 68.83 | 22.87 | 3.50 | 22.85 |
Annual Sum or Average | 1586.50 | 24.04 | 4451.33 | 24.40 | 560.50 | 24.59 |
Minimum of Months | 33.17 | 22.27 | 40.50 | 22.33 | 1.17 | 22.27 |
Maximum of Months | 398.17 | 26.99 | 514.00 | 25.06 | 108.33 | 25.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.50 | 21.19 | 123.17 | 20.92 | 123.17 | 20.74 |
February | 356.50 | 22.15 | 68.83 | 22.25 | 23.67 | 22.14 |
March | 133.17 | 23.02 | 289.17 | 23.85 | 2.33 | 23.87 |
April | 30.33 | 26.14 | 436.00 | 24.60 | 23.17 | 24.71 |
May | 56.17 | 26.89 | 508.00 | 24.78 | 56.17 | 24.97 |
June | 65.50 | 26.67 | 496.00 | 24.75 | 65.50 | 24.95 |
July | 105.00 | 26.60 | 497.00 | 24.98 | 105.00 | 25.22 |
August | 65.50 | 26.52 | 514.00 | 24.70 | 65.50 | 24.88 |
September | 59.67 | 26.35 | 485.00 | 24.69 | 59.67 | 24.86 |
October | 43.50 | 24.11 | 439.83 | 24.34 | 13.83 | 24.40 |
November | 263.00 | 22.56 | 125.00 | 23.02 | 3.33 | 22.99 |
December | 487.17 | 21.55 | 75.17 | 21.32 | 75.17 | 21.14 |
Annual Sum or Average | 2162.00 | 22.72 | 4057.17 | 23.69 | 616.50 | 23.73 |
Minimum of Months | 30.33 | 21.19 | 68.83 | 20.92 | 2.33 | 20.74 |
Maximum of Months | 496.50 | 26.89 | 514.00 | 24.98 | 123.17 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 462.67 | 21.83 | 69.17 | 21.58 | 66.00 | 21.37 |
February | 226.83 | 22.46 | 145.33 | 23.06 | 8.17 | 23.00 |
March | 67.00 | 23.76 | 389.83 | 24.29 | 13.67 | 24.37 |
April | 55.83 | 26.86 | 463.50 | 24.84 | 53.17 | 25.04 |
May | 76.00 | 27.02 | 508.00 | 24.92 | 76.00 | 25.16 |
June | 73.83 | 26.80 | 496.00 | 24.82 | 73.83 | 25.05 |
July | 109.33 | 26.71 | 497.00 | 25.03 | 109.33 | 25.29 |
August | 68.83 | 26.67 | 514.00 | 24.75 | 68.83 | 24.95 |
September | 69.33 | 26.50 | 485.00 | 24.78 | 69.33 | 24.97 |
October | 61.67 | 25.82 | 475.00 | 24.67 | 45.00 | 24.84 |
November | 132.17 | 22.75 | 265.50 | 23.78 | 1.33 | 23.77 |
December | 416.83 | 22.18 | 36.67 | 22.02 | 36.67 | 21.88 |
Annual Sum or Average | 1820.33 | 23.49 | 4345.00 | 24.13 | 621.33 | 24.26 |
Minimum of Months | 55.83 | 21.83 | 36.67 | 21.58 | 1.33 | 21.37 |
Maximum of Months | 462.67 | 27.02 | 514.00 | 25.03 | 109.33 | 25.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 290.67 | 21.96 | 170.83 | 22.41 | 44.33 | 22.19 |
February | 163.00 | 22.56 | 232.83 | 23.64 | 15.00 | 23.69 |
March | 81.17 | 24.18 | 396.00 | 24.38 | 23.67 | 24.51 |
April | 43.83 | 26.70 | 456.00 | 24.75 | 39.83 | 24.91 |
May | 59.50 | 26.91 | 508.00 | 24.80 | 59.50 | 25.00 |
June | 65.17 | 26.66 | 496.00 | 24.74 | 65.17 | 24.94 |
July | 105.00 | 26.60 | 497.00 | 24.98 | 105.00 | 25.22 |
August | 67.17 | 26.59 | 514.00 | 24.73 | 67.17 | 24.92 |
September | 70.33 | 26.52 | 485.00 | 24.81 | 70.33 | 25.00 |
October | 62.00 | 26.67 | 484.33 | 24.85 | 55.67 | 25.06 |
November | 108.83 | 24.30 | 368.67 | 24.49 | 38.50 | 24.69 |
December | 232.00 | 22.39 | 192.00 | 23.19 | 20.17 | 23.11 |
Annual Sum or Average | 1348.67 | 24.07 | 4800.67 | 24.39 | 604.33 | 24.53 |
Minimum of Months | 43.83 | 21.96 | 170.83 | 22.41 | 15.00 | 22.19 |
Maximum of Months | 290.67 | 26.91 | 514.00 | 24.98 | 105.00 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 420.33 | 21.76 | 89.50 | 21.59 | 70.17 | 21.38 |
February | 237.00 | 22.36 | 143.00 | 23.05 | 7.33 | 23.02 |
March | 83.17 | 23.89 | 378.00 | 24.31 | 15.83 | 24.39 |
April | 55.50 | 26.99 | 468.50 | 24.86 | 55.33 | 25.07 |
May | 91.50 | 26.98 | 508.00 | 24.99 | 91.50 | 25.25 |
June | 89.50 | 26.78 | 496.00 | 24.90 | 89.50 | 25.15 |
July | 113.17 | 26.81 | 497.00 | 25.08 | 113.17 | 25.35 |
August | 78.17 | 26.81 | 514.00 | 24.83 | 78.17 | 25.06 |
September | 80.17 | 26.66 | 485.00 | 24.88 | 80.17 | 25.10 |
October | 46.17 | 26.03 | 476.17 | 24.66 | 35.17 | 24.80 |
November | 152.67 | 23.08 | 269.83 | 23.89 | 8.50 | 23.95 |
December | 380.33 | 22.12 | 79.67 | 22.18 | 32.50 | 22.05 |
Annual Sum or Average | 1827.67 | 23.64 | 4404.67 | 24.20 | 677.33 | 24.35 |
Minimum of Months | 46.17 | 21.76 | 79.67 | 21.59 | 7.33 | 21.38 |
Maximum of Months | 420.33 | 26.99 | 514.00 | 25.08 | 113.17 | 25.35 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 42.50 | 27.00 | 514.00 | 27.00 | 42.50 | 27.00 |
April | 362.50 | 27.43 | 485.00 | 27.37 | 362.50 | 27.39 |
May | 48.33 | 27.00 | 508.00 | 27.00 | 48.33 | 27.00 |
June | 156.33 | 27.00 | 496.00 | 27.00 | 156.33 | 27.00 |
July | 273.50 | 27.00 | 497.00 | 27.00 | 273.50 | 27.00 |
August | 489.00 | 27.73 | 514.00 | 27.71 | 489.00 | 27.72 |
September | 28.50 | 27.00 | 485.00 | 27.00 | 28.50 | 27.00 |
October | 29.67 | 27.00 | 502.00 | 27.00 | 29.67 | 27.00 |
November | 31.00 | 27.00 | 489.00 | 27.00 | 31.00 | 27.00 |
December | 12.17 | 27.00 | 497.00 | 27.00 | 12.17 | 27.00 |
Annual Sum or Average | 1473.50 | 27.35 | 5943.00 | 27.14 | 1473.50 | 27.17 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 489.00 | 27.73 | 514.00 | 27.71 | 489.00 | 27.72 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 494.50 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.33 | 27.00 | 514.00 | 27.00 | 0.33 | 27.00 |
April | 181.00 | 28.12 | 485.00 | 27.63 | 181.00 | 27.73 |
May | 8.17 | 27.00 | 508.00 | 27.00 | 8.17 | 27.00 |
June | 24.67 | 27.00 | 496.00 | 27.00 | 24.67 | 27.00 |
July | 28.50 | 27.00 | 497.00 | 27.00 | 28.50 | 27.00 |
August | 329.17 | 28.18 | 514.00 | 27.95 | 329.17 | 28.02 |
September | 3.50 | 27.00 | 485.00 | 27.00 | 3.50 | 27.00 |
October | 3.33 | 27.00 | 502.00 | 27.00 | 3.33 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 578.67 | 28.02 | 5935.50 | 27.19 | 578.67 | 27.26 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 329.17 | 28.18 | 514.00 | 27.95 | 329.17 | 28.02 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.00 | 24.63 | 450.50 | 26.80 | 4.17 | 26.76 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 5.67 | 27.00 | 514.00 | 27.00 | 5.67 | 27.00 |
April | 160.83 | 27.88 | 485.00 | 27.44 | 160.83 | 27.53 |
May | 81.17 | 27.00 | 508.00 | 27.00 | 81.17 | 27.00 |
June | 109.67 | 27.00 | 496.00 | 27.00 | 109.67 | 27.00 |
July | 94.83 | 27.00 | 497.00 | 27.00 | 94.83 | 27.00 |
August | 244.17 | 28.01 | 514.00 | 27.67 | 244.17 | 27.75 |
September | 19.83 | 27.00 | 485.00 | 27.00 | 19.83 | 27.00 |
October | 16.33 | 27.00 | 502.00 | 27.00 | 16.33 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 489.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 763.50 | 27.41 | 5884.17 | 27.11 | 736.67 | 27.14 |
Minimum of Months | 0.00 | 0.00 | 450.50 | 26.80 | 0.00 | 26.76 |
Maximum of Months | 244.17 | 28.01 | 514.00 | 27.67 | 244.17 | 27.75 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.01 | 454.00 | 27.01 | 454.00 | 27.01 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 29.35 | 485.00 | 29.35 | 485.00 | 29.35 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 30.49 | 514.00 | 30.49 | 514.00 | 30.49 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5943.00 | 27.50 | 5943.00 | 27.50 | 5943.00 | 27.50 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 30.49 | 514.00 | 30.49 | 514.00 | 30.49 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00072 | 28.70915 | 0.83782 | 19.84668 |
February | 454.00000 | 27.00095 | 29.00360 | 0.89758 | 22.04611 |
March | 514.00000 | 27.00062 | 30.54570 | 0.97014 | 24.90885 |
April | 485.00000 | 27.32305 | 31.98716 | 1.10744 | 31.08363 |
May | 508.00000 | 27.00058 | 36.81677 | 0.33938 | 7.44472 |
June | 496.00000 | 27.00248 | 36.51542 | 0.38301 | 8.09742 |
July | 497.00000 | 27.00168 | 35.67327 | 0.41557 | 8.65109 |
August | 514.00000 | 27.69284 | 34.10707 | 0.63797 | 14.28171 |
September | 485.00000 | 27.00005 | 39.61958 | 0.34096 | 7.45538 |
October | 502.00000 | 27.00170 | 32.56311 | 0.97069 | 24.92993 |
November | 489.00000 | 27.00067 | 29.78979 | 0.96200 | 24.58058 |
December | 497.00000 | 27.00021 | 27.65859 | 0.94531 | 23.90943 |
Annual Sum or Average | 5943.00000 | 27.08709 | 32.76877 | 0.73255 | 18.05870 |
Minimum of Months | 454.00000 | 27.00005 | 27.65859 | 0.33938 | 7.44472 |
Maximum of Months | 514.00000 | 27.69284 | 39.61958 | 1.10744 | 31.08363 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99125 | 29.75808 | 0.75226 | 17.02923 |
February | 454.00000 | 27.00082 | 29.72445 | 0.81989 | 19.24576 |
March | 514.00000 | 27.00052 | 31.21136 | 0.90137 | 22.19970 |
April | 485.00000 | 27.44676 | 32.46500 | 1.04358 | 28.31341 |
May | 508.00000 | 27.00052 | 37.58385 | 0.30048 | 6.92532 |
June | 496.00000 | 27.00231 | 37.28381 | 0.32150 | 7.19522 |
July | 497.00000 | 27.00155 | 36.45281 | 0.32494 | 7.24218 |
August | 514.00000 | 27.80859 | 34.84023 | 0.52289 | 11.47106 |
September | 485.00000 | 27.00004 | 40.72141 | 0.29605 | 6.85577 |
October | 502.00000 | 27.00151 | 33.30806 | 0.91992 | 22.90508 |
November | 489.00000 | 27.00056 | 30.47142 | 0.87580 | 21.24067 |
December | 497.00000 | 27.00017 | 28.23185 | 0.81119 | 18.95553 |
Annual Sum or Average | 5943.00000 | 27.10632 | 33.52418 | 0.65598 | 15.75673 |
Minimum of Months | 454.00000 | 26.99125 | 28.23185 | 0.29605 | 6.85577 |
Maximum of Months | 514.00000 | 27.80859 | 40.72141 | 1.04358 | 28.31341 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.82027 | 30.44532 | 0.66631 | 15.19882 |
February | 454.00000 | 27.00091 | 29.22773 | 0.78275 | 18.07104 |
March | 514.00000 | 27.00060 | 30.58424 | 0.89149 | 21.87778 |
April | 485.00000 | 27.29946 | 32.02118 | 1.02765 | 27.63219 |
May | 508.00000 | 27.00059 | 36.93989 | 0.32709 | 7.34117 |
June | 496.00000 | 27.00246 | 36.62112 | 0.34715 | 7.61584 |
July | 497.00000 | 27.00176 | 35.78281 | 0.34692 | 7.60802 |
August | 514.00000 | 27.50491 | 34.32967 | 0.46402 | 10.30561 |
September | 485.00000 | 27.00004 | 40.04951 | 0.30545 | 7.01450 |
October | 502.00000 | 27.00164 | 32.70083 | 0.91449 | 22.73437 |
November | 489.00000 | 27.00065 | 29.85944 | 0.84644 | 20.24185 |
December | 497.00000 | 27.00024 | 27.69153 | 0.75069 | 17.05611 |
Annual Sum or Average | 5943.00000 | 27.05367 | 33.04162 | 0.63772 | 15.18690 |
Minimum of Months | 454.00000 | 26.82027 | 27.69153 | 0.30545 | 7.01450 |
Maximum of Months | 514.00000 | 27.50491 | 40.04951 | 1.02765 | 27.63219 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00494 | 30.03520 | 1.07441 | 29.35999 |
February | 454.00000 | 27.00578 | 30.18943 | 1.22580 | 36.52316 |
March | 514.00000 | 27.00306 | 31.00152 | 1.37162 | 44.00880 |
April | 485.00000 | 29.34702 | 31.12719 | 1.98669 | 74.48484 |
May | 508.00000 | 27.00336 | 34.94331 | 0.55329 | 11.47830 |
June | 496.00000 | 27.00307 | 35.05494 | 0.78052 | 17.85742 |
July | 497.00000 | 27.00167 | 34.45416 | 0.99499 | 25.92254 |
August | 514.00000 | 30.48749 | 31.85501 | 2.20785 | 83.60493 |
September | 485.00000 | 27.00402 | 35.50123 | 0.62384 | 13.22770 |
October | 502.00000 | 27.00274 | 31.97913 | 1.29320 | 39.92402 |
November | 489.00000 | 27.00426 | 30.62599 | 1.41131 | 46.11748 |
December | 497.00000 | 27.00640 | 30.04706 | 1.52027 | 52.00290 |
Annual Sum or Average | 5943.00000 | 27.49642 | 32.24498 | 1.25516 | 39.62052 |
Minimum of Months | 454.00000 | 27.00167 | 30.03520 | 0.55329 | 11.47830 |
Maximum of Months | 514.00000 | 30.48749 | 35.50123 | 2.20785 | 83.60493 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54511 | 39.87051 | 0.49927 | 10.80572 |
February | 454.00000 | 24.52200 | 44.47212 | 0.52849 | 11.37247 |
March | 514.00000 | 24.43235 | 48.22371 | 0.53903 | 11.55389 |
April | 485.00000 | 24.53754 | 47.40069 | 0.55930 | 12.13197 |
May | 508.00000 | 24.51747 | 58.24853 | -0.2153 | 7.00843 |
June | 496.00000 | 24.48756 | 61.64625 | -0.1870 | 6.95977 |
July | 497.00000 | 24.63994 | 62.31357 | -0.1194 | 7.27565 |
August | 514.00000 | 24.49769 | 61.04304 | -0.1538 | 7.12586 |
September | 485.00000 | 24.57957 | 62.51198 | -0.1375 | 7.20441 |
October | 502.00000 | 24.62701 | 55.44842 | 0.65807 | 14.82434 |
November | 489.00000 | 24.62723 | 47.04279 | 0.59420 | 13.08564 |
December | 497.00000 | 24.60702 | 39.97506 | 0.52841 | 11.48228 |
Annual Sum or Average | 5943.00000 | 24.55130 | 52.41786 | 0.25496 | 10.05264 |
Minimum of Months | 454.00000 | 24.43235 | 39.87051 | -0.2153 | 6.95977 |
Maximum of Months | 514.00000 | 24.63994 | 62.51198 | 0.65807 | 14.82434 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.33708 | 42.57379 | 0.45984 | 9.98490 |
February | 454.00000 | 24.33422 | 45.23378 | 0.49982 | 10.50910 |
March | 514.00000 | 24.26979 | 48.92349 | 0.53534 | 11.21775 |
April | 485.00000 | 24.27282 | 48.52187 | 0.55513 | 11.66699 |
May | 508.00000 | 24.21770 | 54.31082 | -0.2885 | 6.95548 |
June | 496.00000 | 24.20980 | 56.02591 | -0.2701 | 6.72737 |
July | 497.00000 | 24.28594 | 56.26764 | -0.2384 | 6.51792 |
August | 514.00000 | 24.26075 | 56.05065 | -0.2292 | 6.44382 |
September | 485.00000 | 24.27265 | 56.94556 | -0.2629 | 6.78281 |
October | 502.00000 | 24.35860 | 54.16282 | 0.59924 | 12.80299 |
November | 489.00000 | 24.42448 | 47.89265 | 0.56374 | 12.02418 |
December | 497.00000 | 24.39717 | 40.62049 | 0.48963 | 10.35063 |
Annual Sum or Average | 5943.00000 | 24.30287 | 50.67440 | 0.19816 | 9.31693 |
Minimum of Months | 454.00000 | 24.20980 | 40.62049 | -0.2885 | 6.44382 |
Maximum of Months | 514.00000 | 24.42448 | 56.94556 | 0.59924 | 12.80299 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.71586 | 44.18519 | 0.27835 | 7.05919 |
February | 454.00000 | 24.06981 | 45.87896 | 0.40474 | 8.74670 |
March | 514.00000 | 24.20215 | 49.02616 | 0.48915 | 10.19508 |
April | 485.00000 | 24.16426 | 49.11359 | 0.49653 | 10.27921 |
May | 508.00000 | 24.13735 | 54.79565 | -0.3393 | 7.50853 |
June | 496.00000 | 24.16214 | 56.69537 | -0.3170 | 7.26041 |
July | 497.00000 | 24.16965 | 57.50779 | -0.3164 | 7.22794 |
August | 514.00000 | 24.16928 | 57.77378 | -0.3146 | 7.23640 |
September | 485.00000 | 24.23121 | 57.47726 | -0.3058 | 7.23223 |
October | 502.00000 | 24.29402 | 54.61091 | 0.55992 | 11.77440 |
November | 489.00000 | 24.22411 | 48.35479 | 0.48110 | 10.05222 |
December | 497.00000 | 23.93864 | 42.02777 | 0.33706 | 7.64581 |
Annual Sum or Average | 5943.00000 | 24.12333 | 51.50398 | 0.11825 | 8.51448 |
Minimum of Months | 454.00000 | 23.71586 | 42.02777 | -0.3393 | 7.05919 |
Maximum of Months | 514.00000 | 24.29402 | 57.77378 | 0.55992 | 11.77440 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.64444 | 45.84963 | -0.0007 | 7.34273 |
February | 454.00000 | 23.57479 | 47.62554 | 0.27587 | 7.55944 |
March | 514.00000 | 24.12793 | 49.61037 | 0.47226 | 9.92094 |
April | 485.00000 | 24.24131 | 49.19226 | 0.53057 | 11.11699 |
May | 508.00000 | 24.25784 | 54.40390 | -0.2666 | 6.90753 |
June | 496.00000 | 24.24918 | 56.31835 | -0.2540 | 6.75973 |
July | 497.00000 | 24.28761 | 57.08290 | -0.2500 | 6.71342 |
August | 514.00000 | 24.23817 | 57.60067 | -0.2686 | 6.82895 |
September | 485.00000 | 24.28537 | 57.52206 | -0.2714 | 6.94427 |
October | 502.00000 | 24.26984 | 55.28991 | 0.55861 | 11.72264 |
November | 489.00000 | 23.92177 | 49.81730 | 0.39978 | 8.75867 |
December | 497.00000 | 23.05806 | 44.83936 | 0.11048 | 6.60529 |
Annual Sum or Average | 5943.00000 | 23.93213 | 52.13597 | 0.08421 | 8.09965 |
Minimum of Months | 454.00000 | 22.64444 | 44.83936 | -0.2714 | 6.60529 |
Maximum of Months | 514.00000 | 24.28761 | 57.60067 | 0.55861 | 11.72264 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.16571 | 44.06980 | 0.13482 | 6.23170 |
February | 454.00000 | 23.77638 | 46.16737 | 0.32793 | 7.89042 |
March | 514.00000 | 24.20265 | 48.29705 | 0.50377 | 10.62008 |
April | 485.00000 | 24.45618 | 47.05372 | 0.63161 | 13.99027 |
May | 508.00000 | 24.51880 | 52.41036 | -0.0871 | 6.41018 |
June | 496.00000 | 24.46853 | 54.35471 | -0.0701 | 6.23174 |
July | 497.00000 | 24.59928 | 54.85778 | -0.0366 | 6.73922 |
August | 514.00000 | 24.45113 | 54.93689 | -0.0859 | 6.37162 |
September | 485.00000 | 24.45717 | 55.94056 | -0.1492 | 6.51057 |
October | 502.00000 | 24.38890 | 53.27711 | 0.60501 | 13.07169 |
November | 489.00000 | 24.14198 | 48.18568 | 0.45746 | 9.66963 |
December | 497.00000 | 23.61255 | 42.37718 | 0.25019 | 6.89610 |
Annual Sum or Average | 5943.00000 | 24.18923 | 50.19613 | 0.20525 | 8.37989 |
Minimum of Months | 454.00000 | 23.16571 | 42.37718 | -0.1492 | 6.23170 |
Maximum of Months | 514.00000 | 24.59928 | 55.94056 | 0.63161 | 13.99027 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.51333 | 42.76662 | 0.23072 | 6.86773 |
February | 454.00000 | 23.98617 | 45.30927 | 0.40439 | 9.21400 |
March | 514.00000 | 24.28897 | 47.76815 | 0.56461 | 12.30547 |
April | 485.00000 | 24.50450 | 46.68404 | 0.69491 | 16.01251 |
May | 508.00000 | 24.56648 | 52.08223 | 0.00973 | 6.73719 |
June | 496.00000 | 24.48007 | 54.19451 | -0.0240 | 6.34464 |
July | 497.00000 | 24.59346 | 54.84445 | -0.0212 | 6.96026 |
August | 514.00000 | 24.41697 | 55.04317 | -0.0966 | 6.44200 |
September | 485.00000 | 24.47857 | 55.72575 | -0.1044 | 6.42756 |
October | 502.00000 | 24.48438 | 52.67574 | 0.66353 | 14.96549 |
November | 489.00000 | 24.26819 | 47.53353 | 0.51441 | 11.16041 |
December | 497.00000 | 23.71434 | 41.90173 | 0.28864 | 7.49681 |
Annual Sum or Average | 5943.00000 | 24.27633 | 49.74949 | 0.25862 | 9.23357 |
Minimum of Months | 454.00000 | 23.51333 | 41.90173 | -0.1044 | 6.34464 |
Maximum of Months | 514.00000 | 24.59346 | 55.72575 | 0.69491 | 16.01251 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.78074 | 41.50848 | 0.33812 | 8.73693 |
February | 454.00000 | 24.17374 | 44.50648 | 0.49279 | 11.33318 |
March | 514.00000 | 24.36394 | 47.43456 | 0.61311 | 13.61612 |
April | 485.00000 | 24.52125 | 46.71531 | 0.69012 | 15.80838 |
May | 508.00000 | 24.53102 | 52.33920 | -0.0689 | 6.46056 |
June | 496.00000 | 24.46760 | 54.35950 | -0.0721 | 6.26732 |
July | 497.00000 | 24.59963 | 54.85434 | -0.0353 | 6.76677 |
August | 514.00000 | 24.46060 | 54.87252 | -0.0706 | 6.41811 |
September | 485.00000 | 24.51587 | 55.58561 | -0.0759 | 6.49875 |
October | 502.00000 | 24.61270 | 52.09696 | 0.75035 | 17.85438 |
November | 489.00000 | 24.52335 | 46.29407 | 0.66153 | 15.27595 |
December | 497.00000 | 24.17653 | 40.18741 | 0.45888 | 10.66755 |
Annual Sum or Average | 5943.00000 | 24.39484 | 49.27172 | 0.30458 | 10.45533 |
Minimum of Months | 454.00000 | 23.78074 | 40.18741 | -0.0759 | 6.26732 |
Maximum of Months | 514.00000 | 24.61270 | 55.58561 | 0.75035 | 17.85438 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.96005 | 41.26842 | 0.35558 | 8.29991 |
February | 454.00000 | 24.40013 | 43.83685 | 0.54302 | 11.91539 |
March | 514.00000 | 24.52934 | 46.90639 | 0.69755 | 16.05366 |
April | 485.00000 | 24.67611 | 46.12074 | 0.84641 | 21.17140 |
May | 508.00000 | 24.63446 | 51.87108 | 0.08279 | 7.25484 |
June | 496.00000 | 24.58244 | 53.77145 | 0.11347 | 7.18710 |
July | 497.00000 | 24.72198 | 54.14754 | 0.13808 | 7.90601 |
August | 514.00000 | 24.59117 | 54.13641 | 0.14643 | 7.50020 |
September | 485.00000 | 24.61337 | 55.14255 | 0.00565 | 6.76722 |
October | 502.00000 | 24.66891 | 51.98103 | 0.76561 | 18.29879 |
November | 489.00000 | 24.62436 | 46.09195 | 0.67248 | 15.37243 |
December | 497.00000 | 24.50704 | 39.18434 | 0.54571 | 11.94307 |
Annual Sum or Average | 5943.00000 | 24.54284 | 48.74776 | 0.40778 | 11.61895 |
Minimum of Months | 454.00000 | 23.96005 | 39.18434 | 0.00565 | 6.76722 |
Maximum of Months | 514.00000 | 24.72198 | 55.14255 | 0.84641 | 21.17140 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.77899 | 46.91359 | -0.2145 | 7.38817 |
February | 454.00000 | 22.94631 | 48.07156 | 0.11009 | 6.70387 |
March | 514.00000 | 23.99891 | 48.62853 | 0.42752 | 9.35796 |
April | 485.00000 | 24.41608 | 47.17660 | 0.59463 | 12.96453 |
May | 508.00000 | 24.52989 | 52.61090 | -0.0896 | 6.49743 |
June | 496.00000 | 24.48233 | 55.14096 | -0.0735 | 6.33390 |
July | 497.00000 | 24.61767 | 56.33683 | -0.0472 | 6.84652 |
August | 514.00000 | 24.45339 | 56.76963 | -0.1199 | 6.49973 |
September | 485.00000 | 24.47431 | 57.08523 | -0.1559 | 6.71359 |
October | 502.00000 | 24.30805 | 53.70333 | 0.56403 | 12.05898 |
November | 489.00000 | 23.57966 | 49.66375 | 0.29784 | 7.57311 |
December | 497.00000 | 22.19978 | 45.57268 | -0.1043 | 6.58600 |
Annual Sum or Average | 5943.00000 | 23.82177 | 51.50373 | 0.09840 | 7.96269 |
Minimum of Months | 454.00000 | 21.77899 | 45.57268 | -0.2145 | 6.33390 |
Maximum of Months | 514.00000 | 24.61767 | 57.08523 | 0.59463 | 12.96453 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.53038 | 44.57451 | -0.0282 | 6.60558 |
February | 385.00000 | 23.59752 | 45.39292 | 0.28269 | 8.07085 |
March | 433.00000 | 24.32364 | 46.72824 | 0.54495 | 12.14356 |
April | 410.00000 | 24.66507 | 45.69120 | 0.71341 | 16.79647 |
May | 430.00000 | 24.70587 | 51.78372 | 0.04722 | 7.28773 |
June | 418.00000 | 24.61952 | 54.54398 | 0.01630 | 6.76725 |
July | 422.00000 | 24.77119 | 55.81734 | 0.02997 | 7.52939 |
August | 433.00000 | 24.58050 | 56.25717 | -0.0566 | 6.77102 |
September | 410.00000 | 24.63115 | 56.60120 | -0.0673 | 6.82265 |
October | 427.00000 | 24.60076 | 52.39629 | 0.67064 | 15.40285 |
November | 417.00000 | 24.09919 | 47.35513 | 0.44485 | 10.07653 |
December | 422.00000 | 22.95377 | 43.16877 | 0.08234 | 6.52779 |
Annual Sum or Average | 5034.00000 | 24.17576 | 50.05979 | 0.22239 | 9.23226 |
Minimum of Months | 385.00000 | 22.53038 | 43.16877 | -0.0673 | 6.52779 |
Maximum of Months | 433.00000 | 24.77119 | 56.60120 | 0.71341 | 16.79647 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.42799 | 41.76558 | 0.24152 | 8.41630 |
February | 454.00000 | 23.96359 | 44.46542 | 0.42739 | 10.64773 |
March | 514.00000 | 24.31515 | 47.13396 | 0.58442 | 13.07512 |
April | 485.00000 | 24.52246 | 46.69920 | 0.66987 | 15.23611 |
May | 508.00000 | 24.54208 | 52.53436 | -0.0713 | 6.52534 |
June | 496.00000 | 24.47999 | 55.14991 | -0.0769 | 6.34912 |
July | 497.00000 | 24.61872 | 56.31898 | -0.0445 | 6.86705 |
August | 514.00000 | 24.47207 | 56.60914 | -0.0970 | 6.53743 |
September | 485.00000 | 24.54781 | 56.56978 | -0.0707 | 6.72263 |
October | 502.00000 | 24.64497 | 52.04222 | 0.75119 | 18.00534 |
November | 489.00000 | 24.43747 | 45.94319 | 0.62807 | 14.62256 |
December | 497.00000 | 23.87723 | 40.37704 | 0.36683 | 9.80260 |
Annual Sum or Average | 5943.00000 | 24.32268 | 49.68100 | 0.27367 | 10.21838 |
Minimum of Months | 454.00000 | 23.42799 | 40.37704 | -0.0970 | 6.34912 |
Maximum of Months | 514.00000 | 24.64497 | 56.60914 | 0.75119 | 18.00534 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.63759 | 44.35485 | 0.00657 | 6.80905 |
February | 454.00000 | 23.58541 | 45.89607 | 0.28920 | 8.34635 |
March | 514.00000 | 24.27749 | 47.43047 | 0.55477 | 12.23414 |
April | 485.00000 | 24.58925 | 46.52567 | 0.72356 | 17.02064 |
May | 508.00000 | 24.61987 | 52.18832 | 0.03817 | 7.20676 |
June | 496.00000 | 24.55311 | 54.74060 | 0.03908 | 6.91450 |
July | 497.00000 | 24.68097 | 55.89083 | 0.02771 | 7.42620 |
August | 514.00000 | 24.52462 | 56.26949 | -0.0387 | 6.74368 |
September | 485.00000 | 24.57761 | 56.48634 | -0.0561 | 6.86739 |
October | 502.00000 | 24.53071 | 52.70305 | 0.67262 | 15.33308 |
November | 489.00000 | 24.10152 | 47.56700 | 0.46438 | 10.35234 |
December | 497.00000 | 23.09888 | 42.86303 | 0.12600 | 6.87012 |
Annual Sum or Average | 5943.00000 | 24.15177 | 50.28208 | 0.23616 | 9.33924 |
Minimum of Months | 454.00000 | 22.63759 | 42.86303 | -0.0561 | 6.74368 |
Maximum of Months | 514.00000 | 24.68097 | 56.48634 | 0.72356 | 17.02064 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.22139 | 47.80359 | -0.3750 | 10.38830 |
February | 454.00000 | 22.53836 | 49.11972 | 0.00200 | 7.21279 |
March | 514.00000 | 23.86682 | 49.25448 | 0.39893 | 9.30814 |
April | 485.00000 | 24.43130 | 47.55925 | 0.61331 | 13.62405 |
May | 508.00000 | 24.54808 | 52.71006 | -0.0554 | 6.68786 |
June | 496.00000 | 24.49506 | 55.25596 | -0.0413 | 6.48603 |
July | 497.00000 | 24.63373 | 56.54438 | -0.0171 | 7.11743 |
August | 514.00000 | 24.46695 | 57.00525 | -0.0956 | 6.60324 |
September | 485.00000 | 24.49110 | 57.44174 | -0.1360 | 6.81070 |
October | 502.00000 | 24.24406 | 54.48388 | 0.55438 | 12.05041 |
November | 489.00000 | 23.22995 | 50.96610 | 0.21071 | 7.36725 |
December | 497.00000 | 21.59432 | 46.90550 | -0.2707 | 8.68388 |
Annual Sum or Average | 5943.00000 | 23.65501 | 52.11380 | 0.06559 | 8.53079 |
Minimum of Months | 454.00000 | 21.22139 | 46.90550 | -0.3750 | 6.48603 |
Maximum of Months | 514.00000 | 24.63373 | 57.44174 | 0.61331 | 13.62405 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.00160 | 45.86263 | -0.1729 | 8.40010 |
February | 454.00000 | 23.29533 | 46.61886 | 0.20677 | 7.86420 |
March | 514.00000 | 24.18677 | 47.82212 | 0.53057 | 11.97587 |
April | 485.00000 | 24.56167 | 46.89067 | 0.72532 | 17.10837 |
May | 508.00000 | 24.60578 | 52.31063 | 0.06477 | 7.29196 |
June | 496.00000 | 24.52634 | 54.93030 | 0.03311 | 6.76635 |
July | 497.00000 | 24.66199 | 56.26716 | 0.03384 | 7.53211 |
August | 514.00000 | 24.49475 | 56.69618 | -0.0501 | 6.72059 |
September | 485.00000 | 24.54018 | 57.01794 | -0.0655 | 6.78651 |
October | 502.00000 | 24.45841 | 53.34156 | 0.65714 | 15.02195 |
November | 489.00000 | 23.83088 | 48.52961 | 0.38460 | 9.39259 |
December | 497.00000 | 22.47279 | 44.61768 | -0.0499 | 7.28630 |
Annual Sum or Average | 5943.00000 | 23.97439 | 50.94624 | 0.19071 | 9.34635 |
Minimum of Months | 454.00000 | 22.00160 | 44.61768 | -0.1729 | 6.72059 |
Maximum of Months | 514.00000 | 24.66199 | 57.01794 | 0.72532 | 17.10837 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.90437 | 42.69437 | 0.08766 | 9.03929 |
February | 454.00000 | 23.65296 | 45.32718 | 0.33887 | 10.18207 |
March | 514.00000 | 24.21803 | 47.70827 | 0.56227 | 12.90517 |
April | 485.00000 | 24.52321 | 47.14548 | 0.68501 | 15.82110 |
May | 508.00000 | 24.55838 | 52.64885 | -0.0381 | 6.75434 |
June | 496.00000 | 24.49283 | 55.26599 | -0.0447 | 6.49989 |
July | 497.00000 | 24.63463 | 56.53162 | -0.0145 | 7.14663 |
August | 514.00000 | 24.48339 | 56.86082 | -0.0736 | 6.67061 |
September | 485.00000 | 24.55653 | 56.97497 | -0.0538 | 6.90923 |
October | 502.00000 | 24.58450 | 52.82976 | 0.74183 | 17.83376 |
November | 489.00000 | 24.24237 | 46.85651 | 0.57150 | 13.76990 |
December | 497.00000 | 23.41931 | 41.48159 | 0.23175 | 9.24931 |
Annual Sum or Average | 5943.00000 | 24.19241 | 50.23751 | 0.24794 | 10.21984 |
Minimum of Months | 454.00000 | 22.90437 | 41.48159 | -0.0736 | 6.49989 |
Maximum of Months | 514.00000 | 24.63463 | 56.97497 | 0.74183 | 17.83376 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.12340 | 45.16164 | -0.1375 | 8.54688 |
February | 454.00000 | 23.24394 | 46.79917 | 0.19926 | 8.30655 |
March | 514.00000 | 24.18164 | 47.98848 | 0.53366 | 12.10226 |
April | 485.00000 | 24.58999 | 46.97065 | 0.73731 | 17.58203 |
May | 508.00000 | 24.62608 | 52.33819 | 0.06579 | 7.55361 |
June | 496.00000 | 24.55679 | 54.89990 | 0.06642 | 7.19997 |
July | 497.00000 | 24.68660 | 56.13260 | 0.05261 | 7.73773 |
August | 514.00000 | 24.52734 | 56.54995 | -0.0206 | 6.90166 |
September | 485.00000 | 24.58255 | 56.88655 | -0.0407 | 7.02774 |
October | 502.00000 | 24.47660 | 53.45115 | 0.66513 | 15.24700 |
November | 489.00000 | 23.84893 | 48.63230 | 0.39947 | 9.83271 |
December | 497.00000 | 22.57508 | 44.04056 | -0.0150 | 7.54437 |
Annual Sum or Average | 5943.00000 | 24.00680 | 50.85636 | 0.20819 | 9.63003 |
Minimum of Months | 454.00000 | 22.12340 | 44.04056 | -0.1375 | 6.90166 |
Maximum of Months | 514.00000 | 24.68660 | 56.88655 | 0.73731 | 17.58203 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.598433E+11 | 104457.24 | 12-JAN-15:05 | 410.98 | 0.318409E+12 | 0.00 | 0.378252E+12 | 2.68 | 7.22 | 12-JAN-15:05 | 0.00 | 0.00 |
February | 0.897749E+11 | 174832.36 | 22-FEB-15:30 | 403.13 | 0.551244E+12 | 0.00 | 0.641019E+12 | 3.29 | 7.57 | 21-FEB-13:50 | 0.00 | 0.00 |
March | 0.165598E+12 | 185823.34 | 28-MAR-16:20 | 558.21 | 0.112267E+13 | 0.00 | 0.128827E+13 | 4.63 | 7.57 | 15-MAR-12:50 | 0.00 | 0.00 |
April | 0.218857E+12 | 191714.23 | 26-APR-17:30 | 675.10 | 0.150904E+13 | 0.00 | 0.172789E+13 | 5.99 | 7.57 | 11-APR-16:50 | 0.00 | 0.00 |
May | 0.277472E+12 | 202836.01 | 20-MAY-18:23 | 689.93 | 0.189654E+13 | 0.00 | 0.217401E+13 | 6.17 | 7.57 | 15-MAY-05:04 | 0.00 | 0.00 |
June | 0.303212E+12 | 214420.99 | 26-JUN-05:03 | 671.65 | 0.201796E+13 | 0.00 | 0.232117E+13 | 6.05 | 7.71 | 12-JUN-05:03 | 0.00 | 0.00 |
July | 0.332989E+12 | 217921.29 | 16-JUL-13:42 | 689.86 | 0.215918E+13 | 0.00 | 0.249217E+13 | 5.83 | 7.55 | 05-JUL-05:03 | 0.00 | 0.00 |
August | 0.325162E+12 | 220015.20 | 25-AUG-05:05 | 702.06 | 0.210359E+13 | 0.00 | 0.242876E+13 | 5.86 | 7.51 | 29-AUG-05:03 | 0.00 | 0.00 |
September | 0.267502E+12 | 209766.70 | 17-SEP-19:33 | 631.78 | 0.176938E+13 | 0.00 | 0.203688E+13 | 5.55 | 7.51 | 29-SEP-03:04 | 0.00 | 0.00 |
October | 0.193804E+12 | 192278.93 | 12-OCT-13:40 | 586.94 | 0.133759E+13 | 0.00 | 0.153139E+13 | 5.05 | 7.57 | 02-OCT-04:13 | 0.00 | 0.00 |
November | 0.137813E+12 | 185430.53 | 13-NOV-16:50 | 481.22 | 0.913586E+12 | 0.00 | 0.105140E+13 | 4.00 | 7.57 | 14-NOV-15:40 | 0.00 | 0.00 |
December | 0.764831E+11 | 116814.21 | 01-DEC-15:05 | 441.75 | 0.436334E+12 | 0.00 | 0.512817E+12 | 3.04 | 7.38 | 01-DEC-15:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.244851E+13 | 6942.61 | 0.161355E+14 | 0.00 | 0.185840E+14 | 4.85 | 0.00 | 0.00 | ||||
Minimum of Months | 0.598433E+11 | 104457.24 | 403.13 | 0.318409E+12 | 0.00 | 0.378252E+12 | 2.68 | 7.22 | 0.00 | 0.00 | ||
Maximum of Months | 0.332989E+12 | 220015.20 | 702.06 | 0.215918E+13 | 0.00 | 0.249217E+13 | 6.17 | 7.71 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.158267E+11 | 133737.03 | 10-MAR-13:05 | 42.75 | 0.112709E+12 | 0.00 | 0.128535E+12 | 0.41 | 7.45 | 07-MAR-15:05 | 0.00 | 0.00 |
April | 0.647370E+11 | 147980.94 | 18-APR-14:05 | 163.19 | 0.459983E+12 | 0.00 | 0.524720E+12 | 1.60 | 7.52 | 10-APR-13:05 | 0.00 | 0.00 |
May | 0.129164E+12 | 195923.66 | 30-MAY-05:03 | 288.50 | 0.891194E+12 | 0.00 | 0.102036E+13 | 2.67 | 7.45 | 06-MAY-17:43 | 0.00 | 0.00 |
June | 0.170541E+12 | 214420.99 | 26-JUN-05:03 | 347.60 | 0.113979E+13 | 0.00 | 0.131033E+13 | 3.22 | 7.71 | 12-JUN-05:03 | 0.00 | 0.00 |
July | 0.196661E+12 | 217921.29 | 16-JUL-13:42 | 384.09 | 0.128440E+13 | 0.00 | 0.148106E+13 | 3.36 | 7.55 | 05-JUL-05:03 | 0.00 | 0.00 |
August | 0.205382E+12 | 220015.20 | 25-AUG-05:05 | 401.21 | 0.133948E+13 | 0.00 | 0.154486E+13 | 3.51 | 7.51 | 29-AUG-05:03 | 0.00 | 0.00 |
September | 0.131844E+12 | 205421.01 | 05-SEP-05:04 | 289.75 | 0.878860E+12 | 0.00 | 0.101070E+13 | 2.67 | 7.24 | 29-SEP-05:06 | 0.00 | 0.00 |
October | 0.477720E+11 | 169188.40 | 12-OCT-05:02 | 120.82 | 0.337418E+12 | 0.00 | 0.385190E+12 | 1.14 | 7.46 | 24-OCT-14:05 | 0.00 | 0.00 |
November | 0.918427E+10 | 120453.99 | 09-NOV-15:05 | 25.58 | 0.651953E+11 | 0.00 | 0.743796E+11 | 0.25 | 7.39 | 08-NOV-15:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.971112E+12 | 2063.48 | 0.650903E+13 | 0.00 | 0.748014E+13 | 1.58 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.205382E+12 | 220015.20 | 401.21 | 0.133948E+13 | 0.00 | 0.154486E+13 | 3.51 | 7.71 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.576958E+11 | 744.00 | 43776.24 | 02-JAN-13:40 | 208319.29 | 12-JAN-17:00 | 22.52 | 19.05 | 14.67 |
February | 0.892175E+11 | 672.00 | 43776.24 | 01-FEB-10:20 | 368992.70 | 24-FEB-16:10 | 27.83 | 21.36 | 14.67 |
March | 0.117204E+12 | 744.00 | 43776.24 | 01-MAR-00:10 | 636525.67 | 31-MAR-24:00 | 36.65 | 27.06 | 14.67 |
April | 0.113468E+12 | 720.00 | 43776.24 | 01-APR-00:05 | 702615.04 | 16-APR-17:11 | 48.16 | 35.47 | 14.67 |
May | 0.117250E+12 | 744.00 | 43776.24 | 01-MAY-00:05 | 372583.34 | 31-MAY-23:30 | 39.72 | 35.20 | 14.67 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:05 | 545538.66 | 30-JUN-23:35 | 45.09 | 37.41 | 14.67 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:10 | 673174.96 | 31-JUL-24:00 | 47.65 | 36.99 | 14.67 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:05 | 705928.78 | 25-AUG-14:05 | 49.67 | 36.58 | 14.67 |
September | 0.113468E+12 | 720.00 | 43776.24 | 01-SEP-00:10 | 370374.22 | 30-SEP-23:20 | 35.55 | 30.98 | 14.67 |
October | 0.117250E+12 | 744.00 | 43776.24 | 01-OCT-00:05 | 478887.86 | 31-OCT-23:40 | 35.57 | 28.53 | 14.67 |
November | 0.111412E+12 | 720.00 | 43776.24 | 01-NOV-00:10 | 536411.13 | 08-NOV-16:20 | 33.91 | 24.42 | 14.67 |
December | 0.107791E+12 | 744.00 | 43776.24 | 01-DEC-07:05 | 654831.06 | 28-DEC-16:30 | 33.25 | 21.33 | 14.67 |
Annual Sum or Average | 0.129273E+13 | 8760.00 | 38.02 | 29.57 | 14.67 | ||||
Minimum of Months | 0.576958E+11 | 672.00 | 43776.24 | 208319.29 | 22.52 | 19.05 | 14.67 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 705928.78 | 49.67 | 37.41 | 14.67 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.199457E+09 | 238.58 | 1178.06 | 12-JAN-15:50 | 865149.10 | 12-JAN-15:05 | 21.67 | 21.14 | 30.48 |
February | 0.902148E+09 | 319.42 | 20238.60 | 24-FEB-15:00 | 1504768.62 | 22-FEB-15:40 | 22.27 | 21.31 | 37.81 |
March | 0.920282E+10 | 489.79 | 20238.60 | 06-MAR-11:05 | 1588925.21 | 15-MAR-15:00 | 23.09 | 21.35 | 48.87 |
April | 0.244120E+11 | 616.88 | 20238.60 | 01-APR-09:00 | 1585764.76 | 10-APR-11:50 | 24.16 | 21.74 | 61.72 |
May | 0.455744E+11 | 689.68 | 20238.60 | 01-MAY-04:03 | 1530943.47 | 06-MAY-08:50 | 26.97 | 24.12 | 59.85 |
June | 0.486653E+11 | 671.65 | 20238.60 | 01-JUN-00:05 | 1551866.68 | 22-JUN-15:40 | 29.30 | 26.15 | 55.53 |
July | 0.502624E+11 | 689.86 | 20238.60 | 01-JUL-00:10 | 1550158.89 | 05-JUL-05:04 | 31.17 | 27.90 | 52.39 |
August | 0.511515E+11 | 702.06 | 20238.60 | 01-AUG-00:05 | 1531546.40 | 25-AUG-05:05 | 30.81 | 27.62 | 54.95 |
September | 0.459459E+11 | 631.78 | 20238.60 | 01-SEP-00:10 | 1411756.08 | 12-SEP-05:04 | 29.26 | 26.51 | 50.33 |
October | 0.243112E+11 | 549.37 | 20238.60 | 01-OCT-00:05 | 1550815.81 | 24-OCT-10:50 | 24.03 | 21.99 | 52.38 |
November | 0.427064E+10 | 429.53 | 20238.60 | 06-NOV-10:30 | 1585012.99 | 02-NOV-13:40 | 22.80 | 21.34 | 44.28 |
December | 0.370056E+09 | 287.18 | 1853.40 | 28-DEC-15:00 | 986967.42 | 01-DEC-15:05 | 21.84 | 21.14 | 34.73 |
Annual Sum or Average | 0.305268E+12 | 6315.78 | 25.63 | 23.54 | 48.65 | ||||
Minimum of Months | 0.199457E+09 | 238.58 | 1178.06 | 865149.10 | 21.67 | 21.14 | 30.48 | ||
Maximum of Months | 0.511515E+11 | 702.06 | 20238.60 | 1588925.21 | 31.17 | 27.90 | 61.72 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.67 | 21.67 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 22.27 | 22.27 | 0.00 |
March | 0.217605E+10 | 33.08 | 20238.60 | 06-MAR-13:30 | 1307937.45 | 08-MAR-14:05 | 23.09 | 22.93 | 3.03 |
April | 0.101507E+11 | 155.97 | 20238.60 | 01-APR-14:30 | 1419048.45 | 10-APR-13:40 | 24.16 | 23.38 | 14.52 |
May | 0.270371E+11 | 371.09 | 20238.60 | 01-MAY-05:03 | 1399972.99 | 30-MAY-15:10 | 26.97 | 25.17 | 30.43 |
June | 0.383402E+11 | 526.22 | 20238.60 | 01-JUN-05:04 | 1551866.68 | 22-JUN-15:40 | 29.30 | 26.56 | 41.67 |
July | 0.459428E+11 | 630.57 | 20238.60 | 01-JUL-00:10 | 1550158.89 | 05-JUL-05:04 | 31.17 | 27.97 | 46.92 |
August | 0.448015E+11 | 614.91 | 20238.60 | 01-AUG-00:05 | 1531546.40 | 25-AUG-05:05 | 30.81 | 27.72 | 46.91 |
September | 0.362979E+11 | 498.19 | 20238.60 | 01-SEP-00:10 | 1411756.08 | 12-SEP-05:04 | 29.26 | 26.78 | 37.59 |
October | 0.913764E+10 | 127.23 | 20238.60 | 02-OCT-08:00 | 1342647.25 | 24-OCT-15:30 | 24.03 | 23.43 | 10.94 |
November | 0.328148E+09 | 9.17 | 20238.60 | 06-NOV-11:05 | 1346665.36 | 13-NOV-15:05 | 22.80 | 22.75 | 0.87 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.84 | 21.84 | 0.00 |
Annual Sum or Average | 0.214212E+12 | 2966.43 | 25.63 | 24.38 | 19.52 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 21.67 | 0.00 | ||
Maximum of Months | 0.459428E+11 | 630.57 | 20238.60 | 1551866.68 | 31.17 | 27.97 | 46.92 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.308149E+11 | 0.00 | 183.64 | 1120390.31 | 02-JAN-06:03 | 0.00 | 36.18 | 46.60 | 0.08 | 0.00 | 0.01 | 0.78 | 02-JAN-06:03 |
February | 0.462760E+10 | 0.00 | 57.76 | 711580.41 | 11-FEB-06:02 | 0.00 | 29.68 | 33.87 | 0.01 | 0.00 | 0.00 | 0.49 | 11-FEB-06:02 |
March | 163658.41 | 0.00 | 0.33 | 181.84 | 01-MAR-06:50 | 0.00 | 25.80 | 25.82 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-06:50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.180147E+09 | 0.00 | 13.13 | 30436.34 | 27-NOV-06:03 | 0.00 | 26.20 | 27.22 | 0.00 | 0.00 | 0.00 | 0.02 | 27-NOV-06:03 |
December | 0.885618E+10 | 0.00 | 120.28 | 510028.34 | 23-DEC-06:03 | 0.00 | 30.38 | 38.26 | 0.02 | 0.00 | 0.00 | 0.35 | 23-DEC-06:03 |
Annual Sum or Average | 0.444790E+11 | 0.00 | 375.14 | 0.00 | 27.40 | 29.36 | 0.01 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.308149E+11 | 0.00 | 183.64 | 1120390.31 | 0.00 | 36.18 | 46.60 | 0.08 | 0.00 | 0.01 | 0.78 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 22.52 | 22.52 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 27.83 | 27.83 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 36.65 | 36.65 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 48.16 | 48.16 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 39.72 | 39.72 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 45.09 | 45.09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 47.65 | 47.65 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 49.67 | 49.67 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 35.55 | 35.55 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 35.57 | 35.57 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 33.91 | 33.91 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 33.25 | 33.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 38.02 | 38.02 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.52 | 22.52 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 49.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.353548E+11 | 0.00 | 356.44 | 0.353113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75774.23 | 18-JAN-06:03 | 72176.36 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.573693E+11 | 0.00 | 383.33 | 0.572511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153177.74 | 25-FEB-06:02 | 105770.06 | 25-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.118679E+12 | 0.00 | 542.64 | 0.116733E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 187348.84 | 14-MAR-05:02 | 153217.47 | 14-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.183300E+12 | 0.00 | 627.18 | 0.176337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 248176.19 | 17-APR-04:22 | 185847.30 | 28-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.230600E+12 | 0.00 | 643.07 | 0.196219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 279905.13 | 22-MAY-05:03 | 198865.54 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.269042E+12 | 0.00 | 626.15 | 0.200805E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 290518.72 | 26-JUN-05:02 | 206982.73 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.304134E+12 | 0.00 | 648.93 | 0.189775E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 307324.94 | 03-JUL-03:02 | 200084.90 | 05-JUL-04:23 | 0.00 | 0.00 | 0.00 |
August | 0.325617E+12 | 0.00 | 660.38 | 0.200303E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 311088.73 | 28-AUG-03:01 | 190787.96 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.230672E+12 | 0.00 | 581.78 | 0.146464E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 291531.40 | 05-SEP-05:02 | 181052.51 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.150565E+12 | 0.00 | 555.14 | 0.133580E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 244735.97 | 12-OCT-04:12 | 162876.21 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.951329E+11 | 0.00 | 456.56 | 0.938362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 164593.85 | 09-NOV-05:12 | 119327.48 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 0.563994E+11 | 0.00 | 418.81 | 0.563992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91896.42 | 04-DEC-15:00 | 91896.42 | 04-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205687E+13 | 0.00 | 6500.40 | 0.160301E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.353548E+11 | 0.00 | 356.44 | 0.353113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75774.23 | 72176.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.325617E+12 | 0.00 | 660.38 | 0.200805E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 311088.73 | 206982.73 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.213288E+12 | 0.00 | 323.53 | 0.213288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 588141.59 | 12-JAN-15:05 | 588141.59 | 12-JAN-15:05 | 0.00 | 0.00 | 0.00 |
February | 0.394497E+12 | 0.00 | 356.44 | 0.393704E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1076508.51 | 25-FEB-06:02 | 865758.60 | 22-FEB-15:05 | 0.00 | 0.00 | 0.00 |
March | 0.912140E+12 | 0.00 | 472.94 | 0.897960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1924950.97 | 29-MAR-04:12 | 1518121.15 | 29-MAR-04:12 | 0.00 | 0.00 | 0.00 |
April | 0.148036E+13 | 0.00 | 555.85 | 0.142542E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2130435.16 | 24-APR-04:12 | 1610473.39 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.217701E+13 | 0.00 | 631.37 | 0.184075E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2768830.43 | 24-MAY-05:02 | 1860951.34 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.246879E+13 | 0.00 | 597.23 | 0.181242E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2876590.89 | 26-JUN-05:02 | 1960080.40 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.268963E+13 | 0.00 | 602.54 | 0.160437E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3039488.95 | 25-JUL-05:02 | 1819978.28 | 05-JUL-05:01 | 0.00 | 0.00 | 0.00 |
August | 0.265652E+13 | 0.00 | 588.50 | 0.152303E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2981316.20 | 11-AUG-05:03 | 1757990.53 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.205024E+13 | 0.00 | 526.31 | 0.127442E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2876489.92 | 05-SEP-05:02 | 1669990.94 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.125583E+13 | 0.00 | 486.89 | 0.110820E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2461236.33 | 12-OCT-05:02 | 1552648.07 | 02-OCT-04:12 | 0.00 | 0.00 | 0.00 |
November | 0.688929E+12 | 0.00 | 428.22 | 0.680390E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1392913.19 | 09-NOV-06:03 | 984959.76 | 08-NOV-15:05 | 0.00 | 0.00 | 0.00 |
December | 0.295893E+12 | 0.00 | 365.07 | 0.295893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 671074.29 | 01-DEC-15:05 | 671074.29 | 01-DEC-15:05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172831E+14 | 0.00 | 5934.89 | 0.130698E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.213288E+12 | 0.00 | 323.53 | 0.213288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 588141.59 | 588141.59 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.268963E+13 | 0.00 | 631.37 | 0.184075E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3039488.95 | 1960080.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.171369E+11 | 0.00 | 294.81 | 0.171369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57212.66 | 12-JAN-15:30 | 57212.66 | 12-JAN-15:30 | 0.00 | 0.00 | 0.00 |
February | 0.355236E+11 | 0.00 | 337.46 | 0.354464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98115.58 | 25-FEB-06:02 | 96108.23 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.927577E+11 | 0.00 | 460.32 | 0.914510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 189433.72 | 29-MAR-04:12 | 152027.36 | 29-MAR-04:12 | 0.00 | 0.00 | 0.00 |
April | 0.161998E+12 | 0.00 | 550.36 | 0.156417E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 225640.74 | 03-APR-05:02 | 188526.43 | 30-APR-16:21 | 0.00 | 0.00 | 0.00 |
May | 0.240181E+12 | 0.00 | 631.45 | 0.206206E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 310120.70 | 24-MAY-05:02 | 230746.95 | 29-MAY-16:41 | 0.00 | 0.00 | 0.00 |
June | 0.269394E+12 | 0.00 | 599.61 | 0.203495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 317078.71 | 26-JUN-05:02 | 227184.86 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.286653E+12 | 0.00 | 607.25 | 0.177493E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 349287.92 | 03-JUL-03:02 | 219409.71 | 03-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.279913E+12 | 0.00 | 591.66 | 0.166247E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 332004.30 | 17-AUG-05:02 | 203451.03 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.213511E+12 | 0.00 | 525.44 | 0.136188E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 319587.03 | 05-SEP-05:02 | 189499.84 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.126691E+12 | 0.00 | 478.31 | 0.112804E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 224390.84 | 02-OCT-04:12 | 165601.44 | 02-OCT-04:12 | 0.00 | 0.00 | 0.00 |
November | 0.633493E+11 | 0.00 | 407.36 | 0.628760E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 117390.37 | 09-NOV-06:03 | 109833.46 | 09-NOV-14:50 | 0.00 | 0.00 | 0.00 |
December | 0.225841E+11 | 0.00 | 330.44 | 0.225841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65883.36 | 01-DEC-15:00 | 65883.36 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180969E+13 | 0.00 | 5814.47 | 0.138834E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.171369E+11 | 0.00 | 294.81 | 0.171369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57212.66 | 57212.66 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.286653E+12 | 0.00 | 631.45 | 0.206206E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 349287.92 | 230746.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.477690E+11 | 0.00 | 391.55 | 0.476712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119346.72 | 18-JAN-05:13 | 89651.71 | 14-JAN-05:13 | 0.00 | 0.00 | 0.00 |
February | 0.507354E+11 | 0.00 | 363.53 | 0.506179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132912.00 | 25-FEB-05:12 | 112305.05 | 20-FEB-14:42 | 0.00 | 0.00 | 0.00 |
March | 0.717589E+11 | 0.00 | 427.82 | 0.714611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151129.42 | 11-MAR-05:03 | 97886.77 | 27-MAR-04:12 | 0.00 | 0.00 | 0.00 |
April | 0.856445E+11 | 0.00 | 419.22 | 0.835343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158885.69 | 27-APR-03:02 | 125971.78 | 30-APR-16:30 | 0.00 | 0.00 | 0.00 |
May | 0.110139E+12 | 0.00 | 456.61 | 0.978079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 192396.55 | 22-MAY-03:13 | 122404.64 | 29-MAY-12:15 | 0.00 | 0.00 | 0.00 |
June | 0.130149E+12 | 0.00 | 455.55 | 0.101841E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 207183.45 | 26-JUN-03:02 | 124843.76 | 04-JUN-16:14 | 0.00 | 0.00 | 0.00 |
July | 0.151440E+12 | 0.00 | 469.50 | 0.100986E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 217792.34 | 23-JUL-22:30 | 116455.25 | 04-JUL-19:37 | 0.00 | 0.00 | 0.00 |
August | 0.170051E+12 | 0.00 | 506.32 | 0.109528E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 225639.32 | 27-AUG-12:20 | 101176.63 | 06-AUG-15:36 | 0.00 | 0.00 | 0.00 |
September | 0.131707E+12 | 0.00 | 460.23 | 0.921998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 209626.25 | 17-SEP-19:02 | 104679.94 | 24-SEP-14:28 | 0.00 | 0.00 | 0.00 |
October | 0.946407E+11 | 0.00 | 455.15 | 0.875863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 166530.35 | 01-OCT-11:49 | 117053.86 | 01-OCT-15:50 | 0.00 | 0.00 | 0.00 |
November | 0.722175E+11 | 0.00 | 418.20 | 0.718108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141499.59 | 09-NOV-05:12 | 114615.40 | 05-NOV-14:26 | 0.00 | 0.00 | 0.00 |
December | 0.564779E+11 | 0.00 | 398.58 | 0.564221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112087.71 | 30-DEC-05:12 | 94688.30 | 29-DEC-05:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117273E+13 | 0.00 | 5222.26 | 0.971466E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.477690E+11 | 0.00 | 363.53 | 0.476712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112087.71 | 89651.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.170051E+12 | 0.00 | 506.32 | 0.109528E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 225639.32 | 125971.78 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.336305E+12 | 0.799796E+11 | 744.00 | 0.322693E+12 | 0.136121E+11 | 0.00 | 0.35 | 12-JAN-16:00 | 0.32 | 22-JAN-06:00 | 131184.95 | 17-JAN-17:00 | 126739.75 | 12-JAN-15:00 | 6906.39 | 17-JAN-17:00 | 37609.11 | 12-JAN-15:00 | 0.00 |
February | 0.532262E+12 | 0.129745E+12 | 672.00 | 0.515284E+12 | 0.169777E+11 | 0.00 | 0.60 | 22-FEB-15:00 | 0.53 | 01-FEB-00:10 | 224903.54 | 24-FEB-17:00 | 219559.39 | 22-FEB-15:00 | 10326.03 | 27-FEB-08:65 | 70928.04 | 22-FEB-15:00 | 0.00 |
March | 0.835510E+12 | 0.232579E+12 | 744.00 | 0.821249E+12 | 0.142613E+11 | 0.00 | 0.98 | 31-MAR-24:00 | 0.74 | 01-MAR-02:00 | 395654.11 | 31-MAR-24:00 | 393384.79 | 31-MAR-23:55 | 13907.44 | 05-MAR-06:00 | 124598.12 | 28-MAR-15:30 | 0.00 |
April | 0.103429E+13 | 0.337519E+12 | 720.00 | 0.102795E+13 | 0.633913E+10 | 0.00 | 1.00 | 01-APR-08:70 | 0.42 | 30-APR-23:17 | 409377.10 | 22-APR-17:00 | 403853.67 | 30-APR-04:57 | 9029.59 | 11-APR-05:00 | 158554.43 | 15-APR-15:00 | 0.00 |
May | 0.362635E+12 | 0.136271E+12 | 744.00 | 0.345670E+12 | 0.169648E+11 | 0.00 | 0.60 | 31-MAY-23:05 | 0.35 | 28-MAY-05:00 | 226214.86 | 31-MAY-23:05 | 212771.02 | 31-MAY-23:53 | 15173.39 | 22-MAY-23:10 | 72538.97 | 31-MAY-23:15 | 0.00 |
June | 0.598526E+12 | 0.224831E+12 | 720.00 | 0.572714E+12 | 0.258124E+11 | 0.00 | 0.85 | 30-JUN-24:00 | 0.58 | 18-JUN-04:55 | 318509.19 | 30-JUN-23:03 | 307024.88 | 30-JUN-24:00 | 18670.75 | 28-JUN-13:10 | 116749.40 | 30-JUN-23:13 | 0.00 |
July | 0.873995E+12 | 0.310463E+12 | 744.00 | 0.837309E+12 | 0.366860E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.80 | 19-JUL-03:00 | 401100.92 | 31-JUL-24:00 | 389748.53 | 31-JUL-24:00 | 19567.45 | 18-JUL-08:30 | 143866.65 | 07-JUL-15:00 | 0.00 |
August | 0.109922E+13 | 0.357451E+12 | 744.00 | 0.106360E+13 | 0.356139E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.45 | 31-AUG-23:17 | 421065.73 | 10-AUG-14:00 | 404467.05 | 15-AUG-23:57 | 20787.34 | 31-AUG-23:13 | 151862.04 | 07-AUG-15:00 | 0.00 |
September | 0.366153E+12 | 0.121139E+12 | 720.00 | 0.334810E+12 | 0.313436E+11 | 0.00 | 0.60 | 30-SEP-23:05 | 0.36 | 27-SEP-05:00 | 227621.65 | 30-SEP-23:05 | 213614.99 | 30-SEP-24:00 | 18079.79 | 12-SEP-16:00 | 69979.94 | 30-SEP-23:15 | 0.00 |
October | 0.601573E+12 | 0.181056E+12 | 744.00 | 0.585066E+12 | 0.165072E+11 | 0.00 | 0.76 | 31-OCT-23:30 | 0.55 | 31-OCT-05:00 | 310675.35 | 31-OCT-24:00 | 302060.59 | 31-OCT-24:00 | 11638.92 | 06-OCT-09:10 | 93058.90 | 02-OCT-15:00 | 0.00 |
November | 0.817176E+12 | 0.210178E+12 | 720.00 | 0.797370E+12 | 0.198064E+11 | 0.00 | 0.84 | 08-NOV-15:10 | 0.75 | 26-NOV-06:00 | 321273.46 | 24-NOV-08:25 | 313885.13 | 08-NOV-15:00 | 14611.47 | 23-NOV-08:00 | 108304.85 | 08-NOV-15:00 | 0.00 |
December | 0.109837E+13 | 0.247058E+12 | 744.00 | 0.106331E+13 | 0.350593E+11 | 0.00 | 1.00 | 03-DEC-13:53 | 0.93 | 01-DEC-00:10 | 421496.40 | 22-DEC-06:03 | 403221.79 | 28-DEC-17:00 | 25641.78 | 22-DEC-06:03 | 118945.75 | 28-DEC-14:10 | 0.00 |
Annual Sum or Average | 0.855601E+13 | 0.256827E+13 | 8760.00 | 0.828702E+13 | 0.268984E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.336305E+12 | 0.799796E+11 | 672.00 | 0.322693E+12 | 0.633913E+10 | 0.00 | 0.35 | 0.32 | 131184.95 | 126739.75 | 6906.39 | 37609.11 | 0.00 | ||||||
Maximum of Months | 0.109922E+13 | 0.357451E+12 | 744.00 | 0.106360E+13 | 0.366860E+11 | 0.00 | 1.00 | 0.93 | 421496.40 | 404467.05 | 25641.78 | 158554.43 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.467578E+10 | 0.113556E+10 | 744.00 | 0.451807E+10 | 0.157711E+09 | 0.00 | 0.30 | 12-JAN-17:00 | 0.16 | 03-JAN-08:00 | 2419.52 | 12-JAN-17:00 | 2284.41 | 12-JAN-17:00 | 255.08 | 17-JAN-17:00 | 670.73 | 12-JAN-16:00 | 0.00 |
February | 0.945940E+10 | 0.231700E+10 | 672.00 | 0.921753E+10 | 0.241877E+09 | 0.00 | 0.56 | 20-FEB-16:53 | 0.39 | 01-FEB-07:00 | 4491.92 | 21-FEB-17:00 | 4446.77 | 20-FEB-17:15 | 263.80 | 15-FEB-17:00 | 1375.96 | 22-FEB-15:00 | 0.00 |
March | 0.162099E+11 | 0.448055E+10 | 744.00 | 0.158590E+11 | 0.350868E+09 | 0.00 | 0.90 | 31-MAR-24:00 | 0.62 | 01-MAR-07:00 | 7806.45 | 31-MAR-24:00 | 7697.64 | 31-MAR-23:55 | 343.50 | 10-MAR-17:10 | 2525.09 | 28-MAR-16:00 | 0.00 |
April | 0.211233E+11 | 0.696492E+10 | 720.00 | 0.207967E+11 | 0.326590E+09 | 0.00 | 1.00 | 01-APR-15:30 | 0.40 | 30-APR-23:05 | 8663.90 | 17-APR-00:23 | 8416.80 | 17-APR-00:07 | 389.97 | 26-APR-08:00 | 3360.26 | 15-APR-15:00 | 0.00 |
May | 0.733398E+10 | 0.268122E+10 | 744.00 | 0.665113E+10 | 0.682852E+09 | 0.00 | 0.56 | 31-MAY-23:05 | 0.28 | 13-MAY-07:00 | 4667.48 | 31-MAY-23:05 | 4096.09 | 31-MAY-23:53 | 650.69 | 22-MAY-23:10 | 1499.10 | 01-MAY-15:50 | 0.00 |
June | 0.124376E+11 | 0.453057E+10 | 720.00 | 0.113357E+11 | 0.110197E+10 | 0.00 | 0.81 | 30-JUN-23:13 | 0.53 | 18-JUN-04:55 | 6627.70 | 30-JUN-23:03 | 6136.24 | 30-JUN-24:00 | 818.61 | 28-JUN-13:40 | 2379.37 | 11-JUN-16:10 | 0.00 |
July | 0.183080E+11 | 0.630623E+10 | 744.00 | 0.166765E+11 | 0.163153E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.74 | 19-JUL-02:50 | 8721.68 | 31-JUL-23:03 | 7961.96 | 31-JUL-23:57 | 851.82 | 18-JUL-08:20 | 3100.40 | 02-JUL-16:50 | 0.00 |
August | 0.231099E+11 | 0.756585E+10 | 744.00 | 0.213902E+11 | 0.171971E+10 | 0.00 | 1.00 | 01-AUG-08:70 | 0.39 | 31-AUG-23:05 | 8898.63 | 10-AUG-14:00 | 8205.93 | 29-AUG-03:25 | 874.71 | 21-AUG-14:00 | 3223.26 | 07-AUG-15:00 | 0.00 |
September | 0.737764E+10 | 0.234532E+10 | 720.00 | 0.608996E+10 | 0.128769E+10 | 0.00 | 0.55 | 30-SEP-23:05 | 0.30 | 27-SEP-06:00 | 4667.63 | 30-SEP-23:05 | 4062.76 | 30-SEP-24:00 | 736.21 | 12-SEP-16:00 | 1381.27 | 30-SEP-23:15 | 0.00 |
October | 0.117509E+11 | 0.347882E+10 | 744.00 | 0.111128E+11 | 0.638037E+09 | 0.00 | 0.68 | 31-OCT-23:20 | 0.46 | 28-OCT-07:00 | 5973.67 | 31-OCT-23:10 | 5751.01 | 31-OCT-24:00 | 500.50 | 06-OCT-09:50 | 1894.09 | 02-OCT-15:10 | 0.00 |
November | 0.155319E+11 | 0.398822E+10 | 720.00 | 0.152025E+11 | 0.329316E+09 | 0.00 | 0.79 | 08-NOV-16:20 | 0.62 | 25-NOV-08:00 | 6549.24 | 08-NOV-16:50 | 6428.63 | 12-NOV-16:25 | 290.20 | 08-NOV-20:00 | 2148.14 | 08-NOV-15:00 | 0.00 |
December | 0.203775E+11 | 0.463277E+10 | 744.00 | 0.201903E+11 | 0.187226E+09 | 0.00 | 0.94 | 25-DEC-14:25 | 0.78 | 23-DEC-08:00 | 8196.09 | 28-DEC-17:00 | 8027.93 | 28-DEC-17:00 | 260.62 | 29-DEC-17:10 | 2358.30 | 25-DEC-14:03 | 0.00 |
Annual Sum or Average | 0.167696E+12 | 0.504270E+11 | 8760.00 | 0.159040E+12 | 0.865538E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.467578E+10 | 0.113556E+10 | 672.00 | 0.451807E+10 | 0.157711E+09 | 0.00 | 0.30 | 0.16 | 2419.52 | 2284.41 | 255.08 | 670.73 | 0.00 | ||||||
Maximum of Months | 0.231099E+11 | 0.756585E+10 | 744.00 | 0.213902E+11 | 0.171971E+10 | 0.00 | 1.00 | 0.78 | 8898.63 | 8416.80 | 874.71 | 3360.26 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.308234E+11 | 0.767928E+10 | 721.00 | 0.295455E+11 | 0.127792E+10 | 0.00 | 0.30 | 12-JAN-17:00 | 0.00 | 01-JAN-00:05 | 22249.24 | 12-JAN-17:00 | 20989.01 | 12-JAN-17:00 | 2401.14 | 17-JAN-16:40 | 6105.58 | 12-JAN-17:00 | 0.00 |
February | 0.832671E+11 | 0.204991E+11 | 672.00 | 0.810392E+11 | 0.222789E+10 | 0.00 | 0.55 | 22-FEB-17:00 | 0.33 | 11-FEB-07:40 | 42305.26 | 22-FEB-17:00 | 40782.94 | 22-FEB-17:00 | 2550.50 | 15-FEB-17:00 | 12912.23 | 22-FEB-15:00 | 0.00 |
March | 0.152724E+12 | 0.420755E+11 | 744.00 | 0.149420E+12 | 0.330328E+10 | 0.00 | 0.92 | 31-MAR-24:00 | 0.61 | 01-MAR-07:00 | 75286.51 | 31-MAR-24:00 | 74267.26 | 31-MAR-23:55 | 3345.20 | 10-MAR-17:10 | 23933.25 | 28-MAR-16:00 | 0.00 |
April | 0.198910E+12 | 0.651934E+11 | 720.00 | 0.195824E+12 | 0.308576E+10 | 0.00 | 1.00 | 01-APR-13:05 | 0.35 | 30-APR-23:05 | 80568.28 | 16-APR-20:53 | 78175.54 | 12-APR-16:10 | 3833.21 | 26-APR-08:00 | 31286.49 | 15-APR-15:00 | 0.00 |
May | 0.692963E+11 | 0.252243E+11 | 744.00 | 0.627158E+11 | 0.658052E+10 | 0.00 | 0.57 | 31-MAY-23:05 | 0.28 | 13-MAY-07:00 | 45051.34 | 31-MAY-23:05 | 39442.40 | 31-MAY-23:53 | 6313.09 | 22-MAY-23:20 | 13866.42 | 28-MAY-16:51 | 0.00 |
June | 0.118628E+12 | 0.429372E+11 | 720.00 | 0.107848E+12 | 0.107799E+11 | 0.00 | 0.83 | 30-JUN-23:13 | 0.54 | 24-JUN-13:20 | 63853.11 | 30-JUN-23:03 | 58975.05 | 30-JUN-24:00 | 8090.37 | 28-JUN-13:20 | 22521.51 | 08-JUN-16:00 | 0.00 |
July | 0.174350E+12 | 0.596361E+11 | 744.00 | 0.158276E+12 | 0.160741E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.76 | 19-JUL-03:00 | 81605.56 | 31-JUL-23:03 | 74987.05 | 31-JUL-24:00 | 8418.57 | 18-JUL-08:20 | 29057.06 | 02-JUL-16:50 | 0.00 |
August | 0.216836E+12 | 0.705513E+11 | 744.00 | 0.199898E+12 | 0.169382E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.34 | 31-AUG-23:05 | 83546.74 | 10-AUG-14:05 | 76426.74 | 20-AUG-17:55 | 8608.04 | 21-AUG-14:00 | 30012.57 | 07-AUG-15:00 | 0.00 |
September | 0.690689E+11 | 0.218498E+11 | 720.00 | 0.565271E+11 | 0.125418E+11 | 0.00 | 0.57 | 30-SEP-23:05 | 0.29 | 08-SEP-21:20 | 45179.77 | 30-SEP-23:05 | 39115.88 | 30-SEP-23:50 | 7212.22 | 12-SEP-16:00 | 13241.17 | 30-SEP-23:15 | 0.00 |
October | 0.110534E+12 | 0.326028E+11 | 744.00 | 0.104394E+12 | 0.613979E+10 | 0.00 | 0.68 | 31-OCT-23:20 | 0.45 | 31-OCT-06:00 | 56529.71 | 31-OCT-23:10 | 54351.19 | 31-OCT-24:00 | 4918.86 | 06-OCT-09:50 | 17892.24 | 02-OCT-15:10 | 0.00 |
November | 0.143700E+12 | 0.368778E+11 | 720.00 | 0.140607E+12 | 0.309246E+10 | 0.00 | 0.80 | 08-NOV-16:20 | 0.59 | 26-NOV-07:00 | 62316.24 | 08-NOV-17:00 | 59801.94 | 08-NOV-16:30 | 2787.36 | 08-NOV-20:00 | 20268.21 | 08-NOV-15:00 | 0.00 |
December | 0.183948E+12 | 0.419530E+11 | 744.00 | 0.182240E+12 | 0.170810E+10 | 0.00 | 0.94 | 28-DEC-16:50 | 0.73 | 24-DEC-06:00 | 77418.07 | 28-DEC-17:00 | 75819.38 | 28-DEC-17:00 | 2521.18 | 29-DEC-17:10 | 22115.24 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.155209E+13 | 0.467080E+12 | 8737.00 | 0.146834E+13 | 0.837497E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.308234E+11 | 0.767928E+10 | 672.00 | 0.295455E+11 | 0.127792E+10 | 0.00 | 0.30 | 0.00 | 22249.24 | 20989.01 | 2401.14 | 6105.58 | 0.00 | ||||||
Maximum of Months | 0.216836E+12 | 0.705513E+11 | 744.00 | 0.199898E+12 | 0.169382E+11 | 0.00 | 1.00 | 0.76 | 83546.74 | 78175.54 | 8608.04 | 31286.49 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.200185E+10 | 0.516330E+09 | 600.61 | 0.188809E+10 | 0.113763E+09 | 0.00 | 0.29 | 12-JAN-17:00 | 0.00 | 01-JAN-00:05 | 2265.61 | 12-JAN-17:00 | 2130.83 | 12-JAN-17:00 | 262.41 | 17-JAN-15:05 | 624.24 | 12-JAN-17:00 | 0.00 |
February | 0.772377E+10 | 0.193388E+10 | 672.00 | 0.748839E+10 | 0.235385E+09 | 0.00 | 0.54 | 22-FEB-17:00 | 0.23 | 11-FEB-05:55 | 4296.18 | 22-FEB-17:00 | 4136.03 | 22-FEB-17:00 | 262.38 | 15-FEB-17:00 | 1319.81 | 22-FEB-15:00 | 0.00 |
March | 0.151369E+11 | 0.421390E+10 | 744.00 | 0.147880E+11 | 0.348881E+09 | 0.00 | 0.90 | 31-MAR-24:00 | 0.55 | 01-MAR-07:00 | 7495.85 | 31-MAR-24:00 | 7386.89 | 31-MAR-23:55 | 342.10 | 10-MAR-17:10 | 2458.92 | 28-MAR-16:00 | 0.00 |
April | 0.200987E+11 | 0.664930E+10 | 720.00 | 0.197722E+11 | 0.326457E+09 | 0.00 | 1.00 | 01-APR-15:00 | 0.36 | 30-APR-24:00 | 8345.14 | 16-APR-20:53 | 8090.27 | 16-APR-21:12 | 390.03 | 26-APR-08:00 | 3245.79 | 15-APR-15:00 | 0.00 |
May | 0.717301E+10 | 0.262487E+10 | 744.00 | 0.649435E+10 | 0.678659E+09 | 0.00 | 0.55 | 31-MAY-23:05 | 0.26 | 13-MAY-07:00 | 4467.85 | 31-MAY-23:05 | 3895.95 | 31-MAY-23:53 | 640.14 | 31-MAY-23:05 | 1594.90 | 28-MAY-16:51 | 0.00 |
June | 0.120849E+11 | 0.440165E+10 | 720.00 | 0.109870E+11 | 0.109792E+10 | 0.00 | 0.81 | 30-JUN-23:13 | 0.52 | 24-JUN-13:40 | 6464.06 | 30-JUN-23:03 | 5972.76 | 30-JUN-24:00 | 819.10 | 28-JUN-13:40 | 2470.35 | 11-JUN-16:50 | 0.00 |
July | 0.176700E+11 | 0.608539E+10 | 744.00 | 0.160425E+11 | 0.162755E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.73 | 19-JUL-03:00 | 8415.25 | 31-JUL-23:03 | 7633.93 | 31-JUL-23:57 | 848.64 | 18-JUL-08:20 | 3113.47 | 02-JUL-16:50 | 0.00 |
August | 0.220781E+11 | 0.725718E+10 | 744.00 | 0.203551E+11 | 0.172294E+10 | 0.00 | 1.00 | 01-AUG-09:00 | 0.34 | 31-AUG-23:13 | 8555.23 | 10-AUG-14:00 | 7884.40 | 20-AUG-17:55 | 873.06 | 21-AUG-14:00 | 3112.87 | 07-AUG-15:00 | 0.00 |
September | 0.702066E+10 | 0.223406E+10 | 720.00 | 0.574654E+10 | 0.127412E+10 | 0.00 | 0.56 | 30-SEP-23:05 | 0.28 | 27-SEP-07:00 | 4553.85 | 30-SEP-23:05 | 3935.39 | 30-SEP-23:40 | 727.96 | 12-SEP-16:00 | 1343.45 | 30-SEP-23:15 | 0.00 |
October | 0.110025E+11 | 0.327567E+10 | 744.00 | 0.103706E+11 | 0.631827E+09 | 0.00 | 0.66 | 01-OCT-16:55 | 0.41 | 31-OCT-07:00 | 5557.85 | 31-OCT-23:10 | 5310.20 | 31-OCT-23:50 | 500.78 | 06-OCT-10:05 | 1862.35 | 01-OCT-16:15 | 0.00 |
November | 0.139156E+11 | 0.362119E+10 | 720.00 | 0.135893E+11 | 0.326334E+09 | 0.00 | 0.78 | 08-NOV-16:20 | 0.49 | 26-NOV-07:40 | 6286.74 | 08-NOV-16:50 | 6032.75 | 08-NOV-16:20 | 285.82 | 08-NOV-20:00 | 2061.80 | 08-NOV-15:00 | 0.00 |
December | 0.172984E+11 | 0.401309E+10 | 744.00 | 0.171123E+11 | 0.186102E+09 | 0.00 | 0.92 | 28-DEC-16:50 | 0.59 | 31-DEC-08:70 | 7777.18 | 28-DEC-17:00 | 7609.89 | 28-DEC-17:00 | 258.89 | 29-DEC-17:10 | 2238.68 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.153204E+12 | 0.468265E+11 | 8616.61 | 0.144634E+12 | 0.856993E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.200185E+10 | 0.516330E+09 | 600.61 | 0.188809E+10 | 0.113763E+09 | 0.00 | 0.29 | 0.00 | 2265.61 | 2130.83 | 258.89 | 624.24 | 0.00 | ||||||
Maximum of Months | 0.220781E+11 | 0.725718E+10 | 744.00 | 0.203551E+11 | 0.172294E+10 | 0.00 | 1.00 | 0.73 | 8555.23 | 8090.27 | 873.06 | 3245.79 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.64 | 0.00 | 105.64 | 55.70 | 466.95 | 0.00 | 0.00 | 0.00 |
February | 125.27 | 0.00 | 125.27 | 118.77 | 360.76 | 0.00 | 0.00 | 0.00 |
March | 150.95 | 0.00 | 150.95 | 238.46 | 211.08 | 0.00 | 0.00 | 0.00 |
April | 163.80 | 0.56 | 163.24 | 417.17 | 74.46 | 0.00 | 0.00 | 0.00 |
May | 181.47 | 5.09 | 176.38 | 588.40 | 12.51 | 0.00 | 0.00 | 0.00 |
June | 187.85 | 6.96 | 180.90 | 638.28 | 9.07 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 2.93 | 182.33 | 562.93 | 2.16 | 0.00 | 0.00 | 0.00 |
August | 170.08 | 0.53 | 169.55 | 469.49 | 8.99 | 0.00 | 0.00 | 0.00 |
September | 151.55 | 0.01 | 151.54 | 371.89 | 29.04 | 0.00 | 0.00 | 0.00 |
October | 131.29 | 0.00 | 131.29 | 267.36 | 161.82 | 0.00 | 0.00 | 0.00 |
November | 111.20 | 0.00 | 111.20 | 139.42 | 322.81 | 0.00 | 0.00 | 0.00 |
December | 103.05 | 0.00 | 103.05 | 60.46 | 461.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.40 | 1.35 | 146.05 | 328.37 | 176.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.05 | 0.00 | 103.05 | 55.70 | 2.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.85 | 6.96 | 182.33 | 638.28 | 466.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.64 | 0.00 | 105.64 | 55.70 | 466.95 | 0.00 | 0.00 | 0.00 |
February | 125.27 | 0.00 | 125.27 | 118.77 | 360.76 | 0.00 | 0.00 | 0.00 |
March | 150.95 | 0.00 | 150.95 | 238.46 | 211.08 | 0.00 | 0.00 | 0.00 |
April | 163.80 | 0.56 | 163.24 | 417.17 | 74.46 | 0.00 | 0.00 | 0.00 |
May | 181.47 | 5.09 | 176.38 | 588.40 | 12.51 | 0.00 | 0.00 | 0.00 |
June | 187.85 | 6.96 | 180.90 | 638.28 | 9.07 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 2.93 | 182.33 | 562.93 | 2.16 | 0.00 | 0.00 | 0.00 |
August | 170.08 | 0.53 | 169.55 | 469.49 | 8.99 | 0.00 | 0.00 | 0.00 |
September | 151.55 | 0.01 | 151.54 | 371.89 | 29.04 | 0.00 | 0.00 | 0.00 |
October | 131.29 | 0.00 | 131.29 | 267.36 | 161.82 | 0.00 | 0.00 | 0.00 |
November | 111.20 | 0.00 | 111.20 | 139.42 | 322.81 | 0.00 | 0.00 | 0.00 |
December | 103.05 | 0.00 | 103.05 | 60.46 | 461.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.40 | 1.35 | 146.05 | 328.37 | 176.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.05 | 0.00 | 103.05 | 55.70 | 2.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.85 | 6.96 | 182.33 | 638.28 | 466.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.64 | 0.00 | 105.64 | 55.70 | 466.95 | 0.00 | 0.00 | 0.00 |
February | 125.27 | 0.00 | 125.27 | 118.77 | 360.76 | 0.00 | 0.00 | 0.00 |
March | 150.95 | 0.00 | 150.95 | 238.46 | 211.08 | 0.00 | 0.00 | 0.00 |
April | 163.80 | 0.56 | 163.24 | 417.17 | 74.46 | 0.00 | 0.00 | 0.00 |
May | 181.47 | 5.09 | 176.38 | 588.40 | 12.51 | 0.00 | 0.00 | 0.00 |
June | 187.85 | 6.96 | 180.90 | 638.28 | 9.07 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 2.93 | 182.33 | 562.93 | 2.16 | 0.00 | 0.00 | 0.00 |
August | 170.08 | 0.53 | 169.55 | 469.49 | 8.99 | 0.00 | 0.00 | 0.00 |
September | 151.55 | 0.01 | 151.54 | 371.89 | 29.04 | 0.00 | 0.00 | 0.00 |
October | 131.29 | 0.00 | 131.29 | 267.36 | 161.82 | 0.00 | 0.00 | 0.00 |
November | 111.20 | 0.00 | 111.20 | 139.42 | 322.81 | 0.00 | 0.00 | 0.00 |
December | 103.05 | 0.00 | 103.05 | 60.46 | 461.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.40 | 1.35 | 146.05 | 328.37 | 176.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.05 | 0.00 | 103.05 | 55.70 | 2.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.85 | 6.96 | 182.33 | 638.28 | 466.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.64 | 0.00 | 105.64 | 55.70 | 466.95 | 0.00 | 0.00 | 0.00 |
February | 125.27 | 0.00 | 125.27 | 118.77 | 360.76 | 0.00 | 0.00 | 0.00 |
March | 150.95 | 0.00 | 150.95 | 238.46 | 211.08 | 0.00 | 0.00 | 0.00 |
April | 163.80 | 0.56 | 163.24 | 417.17 | 74.46 | 0.00 | 0.00 | 0.00 |
May | 181.47 | 5.09 | 176.38 | 588.40 | 12.51 | 0.00 | 0.00 | 0.00 |
June | 187.85 | 6.96 | 180.90 | 638.28 | 9.07 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 2.93 | 182.33 | 562.93 | 2.16 | 0.00 | 0.00 | 0.00 |
August | 170.08 | 0.53 | 169.55 | 469.49 | 8.99 | 0.00 | 0.00 | 0.00 |
September | 151.55 | 0.01 | 151.54 | 371.89 | 29.04 | 0.00 | 0.00 | 0.00 |
October | 131.29 | 0.00 | 131.29 | 267.36 | 161.82 | 0.00 | 0.00 | 0.00 |
November | 111.20 | 0.00 | 111.20 | 139.42 | 322.81 | 0.00 | 0.00 | 0.00 |
December | 103.05 | 0.00 | 103.05 | 60.46 | 461.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.40 | 1.35 | 146.05 | 328.37 | 176.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.05 | 0.00 | 103.05 | 55.70 | 2.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.85 | 6.96 | 182.33 | 638.28 | 466.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 105.64 | 0.00 | 105.64 | 55.70 | 466.93 | 0.00 | 0.00 | 0.00 |
February | 125.27 | 0.00 | 125.27 | 118.76 | 360.75 | 0.00 | 0.00 | 0.00 |
March | 150.95 | 0.00 | 150.95 | 238.45 | 211.07 | 0.00 | 0.00 | 0.00 |
April | 163.79 | 0.56 | 163.23 | 417.16 | 74.45 | 0.00 | 0.00 | 0.00 |
May | 181.47 | 5.09 | 176.37 | 588.38 | 12.51 | 0.00 | 0.00 | 0.00 |
June | 187.85 | 6.96 | 180.89 | 638.26 | 9.07 | 0.00 | 0.00 | 0.00 |
July | 185.26 | 2.93 | 182.33 | 562.91 | 2.16 | 0.00 | 0.00 | 0.00 |
August | 170.07 | 0.53 | 169.54 | 469.47 | 8.99 | 0.00 | 0.00 | 0.00 |
September | 151.54 | 0.01 | 151.53 | 371.87 | 29.04 | 0.00 | 0.00 | 0.00 |
October | 131.28 | 0.00 | 131.28 | 267.35 | 161.81 | 0.00 | 0.00 | 0.00 |
November | 111.20 | 0.00 | 111.20 | 139.41 | 322.80 | 0.00 | 0.00 | 0.00 |
December | 103.05 | 0.00 | 103.05 | 60.46 | 461.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 147.39 | 1.35 | 146.05 | 328.36 | 176.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 103.05 | 0.00 | 103.05 | 55.70 | 2.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 187.85 | 6.96 | 182.33 | 638.26 | 466.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 251.44 | 100.93 | 150.52 | 256.23 | 472.54 | 0.00 | 0.00 | 0.00 |
February | 305.47 | 126.11 | 179.36 | 404.76 | 369.53 | 0.00 | 0.00 | 0.00 |
March | 372.64 | 153.81 | 218.83 | 631.99 | 219.44 | 0.00 | 0.00 | 0.00 |
April | 443.35 | 206.71 | 236.64 | 951.13 | 79.36 | 0.00 | 0.00 | 0.00 |
May | 436.38 | 193.47 | 242.91 | 1085.86 | 14.28 | 0.00 | 0.00 | 0.00 |
June | 355.15 | 117.84 | 237.31 | 984.43 | 9.52 | 0.00 | 0.00 | 0.00 |
July | 298.50 | 63.03 | 235.46 | 805.61 | 1.65 | 0.00 | 0.00 | 0.00 |
August | 268.96 | 46.81 | 222.15 | 681.59 | 7.15 | 0.00 | 0.00 | 0.00 |
September | 287.35 | 80.14 | 207.22 | 635.14 | 31.67 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 126.97 | 187.36 | 609.43 | 174.07 | 0.00 | 0.00 | 0.00 |
November | 278.70 | 119.63 | 159.07 | 425.41 | 332.42 | 0.00 | 0.00 | 0.00 |
December | 243.01 | 96.28 | 146.73 | 270.00 | 465.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.19 | 119.13 | 202.06 | 645.97 | 180.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 243.01 | 46.81 | 146.73 | 256.23 | 1.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.35 | 206.71 | 242.91 | 1085.86 | 472.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 251.44 | 100.93 | 150.52 | 256.23 | 472.54 | 0.00 | 0.00 | 0.00 |
February | 305.47 | 126.11 | 179.36 | 404.76 | 369.53 | 0.00 | 0.00 | 0.00 |
March | 372.64 | 153.81 | 218.83 | 631.99 | 219.44 | 0.00 | 0.00 | 0.00 |
April | 443.35 | 206.71 | 236.64 | 951.13 | 79.36 | 0.00 | 0.00 | 0.00 |
May | 436.38 | 193.47 | 242.91 | 1085.86 | 14.28 | 0.00 | 0.00 | 0.00 |
June | 355.15 | 117.84 | 237.31 | 984.43 | 9.52 | 0.00 | 0.00 | 0.00 |
July | 298.50 | 63.03 | 235.46 | 805.61 | 1.65 | 0.00 | 0.00 | 0.00 |
August | 268.96 | 46.81 | 222.15 | 681.59 | 7.15 | 0.00 | 0.00 | 0.00 |
September | 287.35 | 80.14 | 207.22 | 635.14 | 31.67 | 0.00 | 0.00 | 0.00 |
October | 314.33 | 126.97 | 187.36 | 609.43 | 174.07 | 0.00 | 0.00 | 0.00 |
November | 278.70 | 119.63 | 159.07 | 425.41 | 332.42 | 0.00 | 0.00 | 0.00 |
December | 243.01 | 96.28 | 146.73 | 270.00 | 465.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.19 | 119.13 | 202.06 | 645.97 | 180.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 243.01 | 46.81 | 146.73 | 256.23 | 1.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.35 | 206.71 | 242.91 | 1085.86 | 472.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 251.44 | 100.92 | 150.52 | 256.23 | 472.53 | 0.00 | 0.00 | 0.00 |
February | 305.47 | 126.11 | 179.36 | 404.75 | 369.52 | 0.00 | 0.00 | 0.00 |
March | 372.64 | 153.81 | 218.83 | 631.98 | 219.43 | 0.00 | 0.00 | 0.00 |
April | 443.34 | 206.71 | 236.63 | 951.11 | 79.36 | 0.00 | 0.00 | 0.00 |
May | 436.37 | 193.46 | 242.91 | 1085.84 | 14.28 | 0.00 | 0.00 | 0.00 |
June | 355.15 | 117.84 | 237.31 | 984.41 | 9.52 | 0.00 | 0.00 | 0.00 |
July | 298.49 | 63.03 | 235.46 | 805.59 | 1.65 | 0.00 | 0.00 | 0.00 |
August | 268.95 | 46.80 | 222.15 | 681.57 | 7.15 | 0.00 | 0.00 | 0.00 |
September | 287.35 | 80.13 | 207.21 | 635.13 | 31.67 | 0.00 | 0.00 | 0.00 |
October | 314.32 | 126.97 | 187.36 | 609.42 | 174.07 | 0.00 | 0.00 | 0.00 |
November | 278.69 | 119.63 | 159.07 | 425.40 | 332.41 | 0.00 | 0.00 | 0.00 |
December | 243.01 | 96.28 | 146.73 | 269.99 | 465.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 321.18 | 119.12 | 202.06 | 645.96 | 180.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 243.01 | 46.80 | 146.73 | 256.23 | 1.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.34 | 206.71 | 242.91 | 1085.84 | 472.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.45 | 291.93 | 188.52 | 683.87 | 431.15 | 0.00 | 0.00 | 0.00 |
February | 456.84 | 253.74 | 203.10 | 710.29 | 352.07 | 0.00 | 0.00 | 0.00 |
March | 390.61 | 172.53 | 218.08 | 715.59 | 218.88 | 0.00 | 0.00 | 0.00 |
April | 274.36 | 77.43 | 196.93 | 672.54 | 81.44 | 0.00 | 0.00 | 0.00 |
May | 197.30 | 14.61 | 182.70 | 629.66 | 12.82 | 0.00 | 0.00 | 0.00 |
June | 180.48 | 3.08 | 177.40 | 623.14 | 9.13 | 0.00 | 0.00 | 0.00 |
July | 188.26 | 2.59 | 185.67 | 571.58 | 1.99 | 0.00 | 0.00 | 0.00 |
August | 199.70 | 10.67 | 189.04 | 534.26 | 9.18 | 0.00 | 0.00 | 0.00 |
September | 267.72 | 69.49 | 198.23 | 608.40 | 33.28 | 0.00 | 0.00 | 0.00 |
October | 460.58 | 257.19 | 203.40 | 898.66 | 174.98 | 0.00 | 0.00 | 0.00 |
November | 575.29 | 380.26 | 195.04 | 975.84 | 326.42 | 0.00 | 0.00 | 0.00 |
December | 513.44 | 321.73 | 191.70 | 757.31 | 434.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 348.13 | 154.03 | 194.10 | 698.10 | 173.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 180.48 | 2.59 | 177.40 | 534.26 | 1.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 575.29 | 380.26 | 218.08 | 975.84 | 434.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.45 | 291.93 | 188.52 | 683.87 | 431.15 | 0.00 | 0.00 | 0.00 |
February | 456.84 | 253.74 | 203.10 | 710.29 | 352.07 | 0.00 | 0.00 | 0.00 |
March | 390.61 | 172.53 | 218.08 | 715.59 | 218.88 | 0.00 | 0.00 | 0.00 |
April | 274.36 | 77.43 | 196.93 | 672.54 | 81.44 | 0.00 | 0.00 | 0.00 |
May | 197.30 | 14.61 | 182.70 | 629.66 | 12.82 | 0.00 | 0.00 | 0.00 |
June | 180.48 | 3.08 | 177.40 | 623.14 | 9.13 | 0.00 | 0.00 | 0.00 |
July | 188.26 | 2.59 | 185.67 | 571.58 | 1.99 | 0.00 | 0.00 | 0.00 |
August | 199.70 | 10.67 | 189.04 | 534.26 | 9.18 | 0.00 | 0.00 | 0.00 |
September | 267.72 | 69.49 | 198.23 | 608.40 | 33.28 | 0.00 | 0.00 | 0.00 |
October | 460.58 | 257.19 | 203.40 | 898.66 | 174.98 | 0.00 | 0.00 | 0.00 |
November | 575.29 | 380.26 | 195.04 | 975.84 | 326.42 | 0.00 | 0.00 | 0.00 |
December | 513.44 | 321.73 | 191.70 | 757.31 | 434.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 348.13 | 154.03 | 194.10 | 698.09 | 173.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 180.48 | 2.59 | 177.40 | 534.26 | 1.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 575.29 | 380.26 | 218.08 | 975.84 | 434.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.45 | 291.93 | 188.52 | 683.87 | 431.15 | 0.00 | 0.00 | 0.00 |
February | 456.84 | 253.74 | 203.10 | 710.29 | 352.07 | 0.00 | 0.00 | 0.00 |
March | 390.61 | 172.53 | 218.08 | 715.59 | 218.88 | 0.00 | 0.00 | 0.00 |
April | 274.36 | 77.43 | 196.93 | 672.54 | 81.44 | 0.00 | 0.00 | 0.00 |
May | 197.30 | 14.61 | 182.70 | 629.66 | 12.82 | 0.00 | 0.00 | 0.00 |
June | 180.48 | 3.08 | 177.40 | 623.14 | 9.13 | 0.00 | 0.00 | 0.00 |
July | 188.26 | 2.59 | 185.67 | 571.58 | 1.99 | 0.00 | 0.00 | 0.00 |
August | 199.70 | 10.67 | 189.04 | 534.26 | 9.18 | 0.00 | 0.00 | 0.00 |
September | 267.72 | 69.49 | 198.23 | 608.40 | 33.28 | 0.00 | 0.00 | 0.00 |
October | 460.58 | 257.19 | 203.40 | 898.66 | 174.98 | 0.00 | 0.00 | 0.00 |
November | 575.29 | 380.26 | 195.04 | 975.84 | 326.42 | 0.00 | 0.00 | 0.00 |
December | 513.44 | 321.73 | 191.70 | 757.31 | 434.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 348.13 | 154.03 | 194.10 | 698.10 | 173.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 180.48 | 2.59 | 177.40 | 534.26 | 1.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 575.29 | 380.26 | 218.08 | 975.84 | 434.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.45 | 291.93 | 188.52 | 683.87 | 431.15 | 0.00 | 0.00 | 0.00 |
February | 456.84 | 253.74 | 203.10 | 710.29 | 352.07 | 0.00 | 0.00 | 0.00 |
March | 390.61 | 172.53 | 218.08 | 715.59 | 218.88 | 0.00 | 0.00 | 0.00 |
April | 274.36 | 77.43 | 196.93 | 672.54 | 81.44 | 0.00 | 0.00 | 0.00 |
May | 197.30 | 14.61 | 182.70 | 629.66 | 12.82 | 0.00 | 0.00 | 0.00 |
June | 180.48 | 3.08 | 177.40 | 623.14 | 9.13 | 0.00 | 0.00 | 0.00 |
July | 188.26 | 2.59 | 185.67 | 571.58 | 1.99 | 0.00 | 0.00 | 0.00 |
August | 199.70 | 10.67 | 189.04 | 534.26 | 9.18 | 0.00 | 0.00 | 0.00 |
September | 267.72 | 69.49 | 198.23 | 608.40 | 33.28 | 0.00 | 0.00 | 0.00 |
October | 460.58 | 257.19 | 203.40 | 898.66 | 174.98 | 0.00 | 0.00 | 0.00 |
November | 575.29 | 380.26 | 195.04 | 975.84 | 326.42 | 0.00 | 0.00 | 0.00 |
December | 513.44 | 321.73 | 191.70 | 757.31 | 434.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 348.13 | 154.03 | 194.10 | 698.09 | 173.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 180.48 | 2.59 | 177.40 | 534.26 | 1.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 575.29 | 380.26 | 218.08 | 975.84 | 434.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.43 | 291.92 | 188.51 | 683.85 | 431.14 | 0.00 | 0.00 | 0.00 |
February | 456.82 | 253.73 | 203.09 | 710.26 | 352.05 | 0.00 | 0.00 | 0.00 |
March | 390.59 | 172.52 | 218.07 | 715.56 | 218.87 | 0.00 | 0.00 | 0.00 |
April | 274.35 | 77.43 | 196.92 | 672.51 | 81.44 | 0.00 | 0.00 | 0.00 |
May | 197.30 | 14.61 | 182.69 | 629.63 | 12.82 | 0.00 | 0.00 | 0.00 |
June | 180.48 | 3.08 | 177.40 | 623.12 | 9.13 | 0.00 | 0.00 | 0.00 |
July | 188.25 | 2.59 | 185.66 | 571.56 | 1.99 | 0.00 | 0.00 | 0.00 |
August | 199.70 | 10.67 | 189.03 | 534.24 | 9.18 | 0.00 | 0.00 | 0.00 |
September | 267.71 | 69.48 | 198.22 | 608.37 | 33.28 | 0.00 | 0.00 | 0.00 |
October | 460.57 | 257.18 | 203.39 | 898.63 | 174.97 | 0.00 | 0.00 | 0.00 |
November | 575.27 | 380.24 | 195.03 | 975.80 | 326.41 | 0.00 | 0.00 | 0.00 |
December | 513.41 | 321.72 | 191.69 | 757.28 | 434.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 348.12 | 154.02 | 194.09 | 698.07 | 173.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 180.48 | 2.59 | 177.40 | 534.24 | 1.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 575.27 | 380.24 | 218.07 | 975.80 | 434.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 246.00 | 95.73 | 150.26 | 278.64 | 553.06 | 0.00 | 0.00 | 0.00 |
February | 281.30 | 103.67 | 177.64 | 378.06 | 449.28 | 0.00 | 0.00 | 0.00 |
March | 364.78 | 145.82 | 218.96 | 613.42 | 284.65 | 0.00 | 0.00 | 0.00 |
April | 443.39 | 207.93 | 235.46 | 921.79 | 125.22 | 0.00 | 0.00 | 0.00 |
May | 419.85 | 178.09 | 241.76 | 1037.41 | 25.16 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 153.18 | 241.17 | 1023.27 | 18.59 | 0.00 | 0.00 | 0.00 |
July | 292.63 | 56.92 | 235.71 | 746.09 | 9.25 | 0.00 | 0.00 | 0.00 |
August | 268.75 | 47.76 | 220.98 | 627.79 | 29.97 | 0.00 | 0.00 | 0.00 |
September | 295.42 | 86.73 | 208.70 | 635.29 | 52.89 | 0.00 | 0.00 | 0.00 |
October | 307.49 | 122.44 | 185.05 | 592.55 | 218.78 | 0.00 | 0.00 | 0.00 |
November | 278.18 | 118.56 | 159.62 | 434.05 | 413.21 | 0.00 | 0.00 | 0.00 |
December | 238.04 | 90.77 | 147.27 | 266.10 | 577.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 319.12 | 117.14 | 201.98 | 630.25 | 228.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 238.04 | 47.76 | 147.27 | 266.10 | 9.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.39 | 207.93 | 241.76 | 1037.41 | 577.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 246.00 | 95.73 | 150.26 | 278.64 | 553.06 | 0.00 | 0.00 | 0.00 |
February | 281.30 | 103.67 | 177.64 | 378.06 | 449.28 | 0.00 | 0.00 | 0.00 |
March | 364.78 | 145.82 | 218.96 | 613.42 | 284.65 | 0.00 | 0.00 | 0.00 |
April | 443.39 | 207.93 | 235.46 | 921.79 | 125.22 | 0.00 | 0.00 | 0.00 |
May | 419.85 | 178.09 | 241.76 | 1037.41 | 25.16 | 0.00 | 0.00 | 0.00 |
June | 394.35 | 153.18 | 241.17 | 1023.27 | 18.59 | 0.00 | 0.00 | 0.00 |
July | 292.63 | 56.92 | 235.71 | 746.09 | 9.25 | 0.00 | 0.00 | 0.00 |
August | 268.75 | 47.76 | 220.98 | 627.79 | 29.97 | 0.00 | 0.00 | 0.00 |
September | 295.42 | 86.73 | 208.70 | 635.29 | 52.89 | 0.00 | 0.00 | 0.00 |
October | 307.49 | 122.44 | 185.05 | 592.55 | 218.78 | 0.00 | 0.00 | 0.00 |
November | 278.18 | 118.56 | 159.62 | 434.05 | 413.21 | 0.00 | 0.00 | 0.00 |
December | 238.04 | 90.77 | 147.27 | 266.10 | 577.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 319.12 | 117.14 | 201.98 | 630.25 | 228.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 238.04 | 47.76 | 147.27 | 266.10 | 9.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.39 | 207.93 | 241.76 | 1037.41 | 577.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 245.99 | 95.73 | 150.26 | 278.63 | 553.05 | 0.00 | 0.00 | 0.00 |
February | 281.30 | 103.67 | 177.63 | 378.05 | 449.27 | 0.00 | 0.00 | 0.00 |
March | 364.77 | 145.81 | 218.96 | 613.41 | 284.65 | 0.00 | 0.00 | 0.00 |
April | 443.38 | 207.93 | 235.45 | 921.77 | 125.22 | 0.00 | 0.00 | 0.00 |
May | 419.84 | 178.09 | 241.75 | 1037.39 | 25.16 | 0.00 | 0.00 | 0.00 |
June | 394.34 | 153.17 | 241.17 | 1023.25 | 18.59 | 0.00 | 0.00 | 0.00 |
July | 292.62 | 56.91 | 235.71 | 746.07 | 9.25 | 0.00 | 0.00 | 0.00 |
August | 268.74 | 47.76 | 220.98 | 627.77 | 29.97 | 0.00 | 0.00 | 0.00 |
September | 295.42 | 86.73 | 208.69 | 635.28 | 52.89 | 0.00 | 0.00 | 0.00 |
October | 307.48 | 122.44 | 185.04 | 592.54 | 218.77 | 0.00 | 0.00 | 0.00 |
November | 278.17 | 118.55 | 159.62 | 434.05 | 413.20 | 0.00 | 0.00 | 0.00 |
December | 238.03 | 90.77 | 147.26 | 266.09 | 577.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 319.12 | 117.14 | 201.97 | 630.23 | 228.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 238.03 | 47.76 | 147.26 | 266.09 | 9.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 443.38 | 207.93 | 241.75 | 1037.39 | 577.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 528.19 | 0.00 | 528.19 | 370.20 | 2014.99 | 0.00 | 0.00 | 0.00 |
February | 626.35 | 0.00 | 626.35 | 663.80 | 1609.53 | 0.00 | 0.00 | 0.00 |
March | 754.75 | 0.00 | 754.75 | 1226.92 | 990.48 | 0.00 | 0.00 | 0.00 |
April | 818.97 | 2.78 | 816.19 | 2138.40 | 348.31 | 0.00 | 0.00 | 0.00 |
May | 907.36 | 25.46 | 881.90 | 2965.31 | 64.20 | 0.00 | 0.00 | 0.00 |
June | 939.26 | 34.79 | 904.47 | 3215.43 | 48.72 | 0.00 | 0.00 | 0.00 |
July | 926.33 | 14.67 | 911.66 | 2847.34 | 12.62 | 0.00 | 0.00 | 0.00 |
August | 850.39 | 2.65 | 847.74 | 2404.79 | 41.31 | 0.00 | 0.00 | 0.00 |
September | 757.72 | 0.05 | 757.67 | 1873.78 | 145.12 | 0.00 | 0.00 | 0.00 |
October | 656.43 | 0.00 | 656.43 | 1366.29 | 780.01 | 0.00 | 0.00 | 0.00 |
November | 556.01 | 0.00 | 556.01 | 756.60 | 1463.91 | 0.00 | 0.00 | 0.00 |
December | 515.26 | 0.00 | 515.26 | 403.21 | 1981.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 736.98 | 6.73 | 730.25 | 1691.01 | 788.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 515.26 | 0.00 | 515.26 | 370.20 | 12.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 939.26 | 34.79 | 911.66 | 3215.43 | 2014.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 754.32 | 302.78 | 451.55 | 811.63 | 1282.55 | 0.00 | 0.00 | 0.00 |
February | 916.41 | 378.34 | 538.07 | 1223.70 | 1048.25 | 0.00 | 0.00 | 0.00 |
March | 1117.92 | 461.44 | 656.48 | 1878.50 | 659.89 | 0.00 | 0.00 | 0.00 |
April | 1330.04 | 620.13 | 709.91 | 2829.03 | 254.14 | 0.00 | 0.00 | 0.00 |
May | 1309.12 | 580.39 | 728.73 | 3230.22 | 48.93 | 0.00 | 0.00 | 0.00 |
June | 1065.45 | 353.52 | 711.94 | 2925.63 | 35.26 | 0.00 | 0.00 | 0.00 |
July | 895.49 | 189.10 | 706.38 | 2391.55 | 8.09 | 0.00 | 0.00 | 0.00 |
August | 806.87 | 140.41 | 666.46 | 2023.87 | 29.98 | 0.00 | 0.00 | 0.00 |
September | 862.05 | 240.40 | 621.64 | 1884.64 | 107.86 | 0.00 | 0.00 | 0.00 |
October | 942.98 | 380.90 | 562.08 | 1813.09 | 533.27 | 0.00 | 0.00 | 0.00 |
November | 836.09 | 358.89 | 477.20 | 1280.18 | 962.10 | 0.00 | 0.00 | 0.00 |
December | 729.03 | 288.85 | 440.19 | 846.11 | 1289.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 963.55 | 357.37 | 606.18 | 1930.66 | 519.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 729.03 | 140.41 | 440.19 | 811.63 | 8.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1330.04 | 620.13 | 728.73 | 3230.22 | 1289.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2402.22 | 1459.65 | 942.57 | 3414.99 | 2076.15 | 0.00 | 0.00 | 0.00 |
February | 2284.16 | 1268.69 | 1015.47 | 3534.75 | 1710.14 | 0.00 | 0.00 | 0.00 |
March | 1953.02 | 862.63 | 1090.39 | 3563.23 | 1081.74 | 0.00 | 0.00 | 0.00 |
April | 1371.80 | 387.17 | 984.64 | 3376.83 | 399.85 | 0.00 | 0.00 | 0.00 |
May | 986.51 | 73.03 | 913.48 | 3168.11 | 64.73 | 0.00 | 0.00 | 0.00 |
June | 902.40 | 15.40 | 887.00 | 3141.28 | 48.37 | 0.00 | 0.00 | 0.00 |
July | 941.29 | 12.95 | 928.34 | 2891.24 | 11.25 | 0.00 | 0.00 | 0.00 |
August | 998.51 | 53.33 | 945.18 | 2715.17 | 43.61 | 0.00 | 0.00 | 0.00 |
September | 1338.58 | 347.43 | 991.15 | 3033.05 | 174.82 | 0.00 | 0.00 | 0.00 |
October | 2302.89 | 1285.93 | 1016.97 | 4470.31 | 889.84 | 0.00 | 0.00 | 0.00 |
November | 2876.44 | 1901.26 | 975.17 | 4856.53 | 1607.78 | 0.00 | 0.00 | 0.00 |
December | 2567.15 | 1608.65 | 958.50 | 3790.35 | 2087.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1740.64 | 770.14 | 970.49 | 3494.85 | 845.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 902.40 | 12.95 | 887.00 | 2715.17 | 11.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2876.44 | 1901.26 | 1090.39 | 4856.53 | 2087.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 737.99 | 287.20 | 450.79 | 895.44 | 1432.31 | 0.00 | 0.00 | 0.00 |
February | 843.91 | 311.00 | 532.90 | 1187.06 | 1165.74 | 0.00 | 0.00 | 0.00 |
March | 1094.33 | 437.44 | 656.89 | 1881.86 | 743.64 | 0.00 | 0.00 | 0.00 |
April | 1330.15 | 623.79 | 706.36 | 2835.03 | 299.49 | 0.00 | 0.00 | 0.00 |
May | 1259.53 | 534.27 | 725.26 | 3142.39 | 64.89 | 0.00 | 0.00 | 0.00 |
June | 1183.03 | 459.52 | 723.51 | 3127.88 | 44.28 | 0.00 | 0.00 | 0.00 |
July | 877.87 | 170.75 | 707.12 | 2327.13 | 13.00 | 0.00 | 0.00 | 0.00 |
August | 806.23 | 143.29 | 662.94 | 2004.33 | 38.88 | 0.00 | 0.00 | 0.00 |
September | 886.26 | 260.18 | 626.08 | 1930.33 | 131.79 | 0.00 | 0.00 | 0.00 |
October | 922.46 | 367.32 | 555.14 | 1809.42 | 590.30 | 0.00 | 0.00 | 0.00 |
November | 834.52 | 355.67 | 478.85 | 1357.10 | 1069.73 | 0.00 | 0.00 | 0.00 |
December | 714.10 | 272.30 | 441.80 | 890.87 | 1411.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 957.36 | 351.43 | 605.93 | 1951.35 | 581.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 714.10 | 143.29 | 441.80 | 890.87 | 13.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1330.15 | 623.79 | 725.26 | 3142.39 | 1432.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 528.19 | 0.00 | 528.19 | 417.68 | 1829.69 | 0.00 | 0.00 | 0.00 |
February | 626.35 | 0.00 | 626.35 | 696.45 | 1500.47 | 0.00 | 0.00 | 0.00 |
March | 754.75 | 0.00 | 754.75 | 1222.59 | 959.36 | 0.00 | 0.00 | 0.00 |
April | 818.97 | 2.78 | 816.19 | 2104.18 | 354.65 | 0.00 | 0.00 | 0.00 |
May | 907.36 | 25.46 | 881.90 | 2916.43 | 72.39 | 0.00 | 0.00 | 0.00 |
June | 939.26 | 34.79 | 904.47 | 3163.93 | 52.87 | 0.00 | 0.00 | 0.00 |
July | 926.33 | 14.67 | 911.66 | 2790.99 | 13.74 | 0.00 | 0.00 | 0.00 |
August | 850.39 | 2.65 | 847.74 | 2358.70 | 45.40 | 0.00 | 0.00 | 0.00 |
September | 757.72 | 0.05 | 757.67 | 1843.52 | 155.05 | 0.00 | 0.00 | 0.00 |
October | 656.43 | 0.00 | 656.43 | 1354.18 | 764.73 | 0.00 | 0.00 | 0.00 |
November | 556.01 | 0.00 | 556.01 | 781.32 | 1376.98 | 0.00 | 0.00 | 0.00 |
December | 515.26 | 0.00 | 515.26 | 458.28 | 1805.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 736.98 | 6.73 | 730.25 | 1680.48 | 740.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 515.26 | 0.00 | 515.26 | 417.68 | 13.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 939.26 | 34.79 | 911.66 | 3163.93 | 1829.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 754.32 | 302.78 | 451.55 | 870.06 | 1167.60 | 0.00 | 0.00 | 0.00 |
February | 916.41 | 378.34 | 538.07 | 1255.35 | 986.81 | 0.00 | 0.00 | 0.00 |
March | 1117.92 | 461.44 | 656.48 | 1882.11 | 643.45 | 0.00 | 0.00 | 0.00 |
April | 1330.04 | 620.13 | 709.91 | 2814.61 | 257.11 | 0.00 | 0.00 | 0.00 |
May | 1309.12 | 580.39 | 728.73 | 3205.88 | 53.70 | 0.00 | 0.00 | 0.00 |
June | 1065.45 | 353.52 | 711.94 | 2900.29 | 37.70 | 0.00 | 0.00 | 0.00 |
July | 895.49 | 189.10 | 706.38 | 2363.25 | 8.61 | 0.00 | 0.00 | 0.00 |
August | 806.87 | 140.41 | 666.46 | 2002.65 | 32.49 | 0.00 | 0.00 | 0.00 |
September | 862.05 | 240.40 | 621.64 | 1872.84 | 113.57 | 0.00 | 0.00 | 0.00 |
October | 942.98 | 380.90 | 562.08 | 1812.77 | 524.18 | 0.00 | 0.00 | 0.00 |
November | 836.09 | 358.89 | 477.20 | 1303.84 | 915.09 | 0.00 | 0.00 | 0.00 |
December | 729.03 | 288.85 | 440.19 | 901.43 | 1185.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 963.55 | 357.37 | 606.18 | 1934.47 | 491.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 729.03 | 140.41 | 440.19 | 870.06 | 8.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1330.04 | 620.13 | 728.73 | 3205.88 | 1185.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2402.22 | 1459.65 | 942.57 | 3472.42 | 1907.94 | 0.00 | 0.00 | 0.00 |
February | 2284.16 | 1268.69 | 1015.47 | 3557.59 | 1616.30 | 0.00 | 0.00 | 0.00 |
March | 1953.02 | 862.63 | 1090.39 | 3551.50 | 1053.33 | 0.00 | 0.00 | 0.00 |
April | 1371.80 | 387.17 | 984.64 | 3342.96 | 405.00 | 0.00 | 0.00 | 0.00 |
May | 986.51 | 73.03 | 913.48 | 3119.56 | 72.44 | 0.00 | 0.00 | 0.00 |
June | 902.40 | 15.40 | 887.00 | 3089.42 | 52.69 | 0.00 | 0.00 | 0.00 |
July | 941.29 | 12.95 | 928.34 | 2834.67 | 12.20 | 0.00 | 0.00 | 0.00 |
August | 998.51 | 53.33 | 945.18 | 2669.68 | 47.82 | 0.00 | 0.00 | 0.00 |
September | 1338.58 | 347.43 | 991.15 | 3002.32 | 184.56 | 0.00 | 0.00 | 0.00 |
October | 2302.89 | 1285.93 | 1016.97 | 4455.24 | 875.05 | 0.00 | 0.00 | 0.00 |
November | 2876.44 | 1901.26 | 975.17 | 4866.05 | 1538.10 | 0.00 | 0.00 | 0.00 |
December | 2567.15 | 1608.65 | 958.50 | 3844.73 | 1942.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1740.64 | 770.14 | 970.49 | 3482.24 | 805.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 902.40 | 12.95 | 887.00 | 2669.68 | 12.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2876.44 | 1901.26 | 1090.39 | 4866.05 | 1942.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 737.99 | 287.20 | 450.79 | 919.80 | 1323.32 | 0.00 | 0.00 | 0.00 |
February | 843.91 | 311.00 | 532.90 | 1198.18 | 1102.58 | 0.00 | 0.00 | 0.00 |
March | 1094.33 | 437.44 | 656.89 | 1872.71 | 723.92 | 0.00 | 0.00 | 0.00 |
April | 1330.15 | 623.79 | 706.36 | 2813.07 | 301.09 | 0.00 | 0.00 | 0.00 |
May | 1259.53 | 534.27 | 725.26 | 3113.64 | 69.32 | 0.00 | 0.00 | 0.00 |
June | 1183.03 | 459.52 | 723.51 | 3096.29 | 46.56 | 0.00 | 0.00 | 0.00 |
July | 877.87 | 170.75 | 707.12 | 2293.98 | 14.03 | 0.00 | 0.00 | 0.00 |
August | 806.23 | 143.29 | 662.94 | 1979.01 | 41.91 | 0.00 | 0.00 | 0.00 |
September | 886.26 | 260.18 | 626.08 | 1911.60 | 137.51 | 0.00 | 0.00 | 0.00 |
October | 922.46 | 367.32 | 555.14 | 1799.56 | 579.86 | 0.00 | 0.00 | 0.00 |
November | 834.52 | 355.67 | 478.85 | 1363.77 | 1020.15 | 0.00 | 0.00 | 0.00 |
December | 714.10 | 272.30 | 441.80 | 917.85 | 1311.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 957.36 | 351.43 | 605.93 | 1942.15 | 553.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 714.10 | 143.29 | 441.80 | 917.85 | 14.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1330.15 | 623.79 | 725.26 | 3113.64 | 1323.32 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282947E+09 | 0.00 | 0.282947E+09 | 0.149192E+09 | 0.125069E+10 |
February | 0.303056E+09 | 0.00 | 0.303056E+09 | 0.287323E+09 | 0.872750E+09 |
March | 0.404311E+09 | 0.00 | 0.404311E+09 | 0.638680E+09 | 0.565347E+09 |
April | 0.424558E+09 | 1439819.52 | 0.423118E+09 | 0.108132E+10 | 0.192992E+09 |
May | 0.486059E+09 | 13639734.17 | 0.472420E+09 | 0.157598E+10 | 33518228.33 |
June | 0.486918E+09 | 18035552.38 | 0.468883E+09 | 0.165443E+10 | 23513274.06 |
July | 0.496220E+09 | 7857944.09 | 0.488362E+09 | 0.150776E+10 | 5796784.38 |
August | 0.455544E+09 | 1419727.41 | 0.454125E+09 | 0.125747E+10 | 24074718.90 |
September | 0.392809E+09 | 27582.24 | 0.392782E+09 | 0.963932E+09 | 75275381.51 |
October | 0.351643E+09 | 0.00 | 0.351643E+09 | 0.716105E+09 | 0.433407E+09 |
November | 0.288237E+09 | 0.00 | 0.288237E+09 | 0.361367E+09 | 0.836735E+09 |
December | 0.276020E+09 | 0.00 | 0.276020E+09 | 0.161939E+09 | 0.123732E+10 |
Annual Sum or Average | 0.464832E+10 | 42420359.81 | 0.460590E+10 | 0.103555E+11 | 0.555141E+10 |
Minimum of Months | 0.276020E+09 | 0.00 | 0.276020E+09 | 0.149192E+09 | 5796784.38 |
Maximum of Months | 0.496220E+09 | 18035552.38 | 0.488362E+09 | 0.165443E+10 | 0.125069E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282947E+09 | 0.00 | 0.282947E+09 | 0.149192E+09 | 0.125069E+10 |
February | 0.303056E+09 | 0.00 | 0.303056E+09 | 0.287323E+09 | 0.872750E+09 |
March | 0.404311E+09 | 0.00 | 0.404311E+09 | 0.638680E+09 | 0.565347E+09 |
April | 0.424558E+09 | 1439817.79 | 0.423118E+09 | 0.108132E+10 | 0.192992E+09 |
May | 0.486059E+09 | 13639717.81 | 0.472419E+09 | 0.157598E+10 | 33518164.93 |
June | 0.486918E+09 | 18035530.74 | 0.468882E+09 | 0.165443E+10 | 23513251.31 |
July | 0.496220E+09 | 7857934.66 | 0.488362E+09 | 0.150776E+10 | 5796770.92 |
August | 0.455544E+09 | 1419725.71 | 0.454124E+09 | 0.125747E+10 | 24074681.20 |
September | 0.392809E+09 | 27582.20 | 0.392781E+09 | 0.963932E+09 | 75275278.52 |
October | 0.351643E+09 | 0.00 | 0.351643E+09 | 0.716105E+09 | 0.433406E+09 |
November | 0.288237E+09 | 0.00 | 0.288237E+09 | 0.361367E+09 | 0.836734E+09 |
December | 0.276019E+09 | 0.00 | 0.276019E+09 | 0.161938E+09 | 0.123732E+10 |
Annual Sum or Average | 0.464832E+10 | 42420308.91 | 0.460590E+10 | 0.103555E+11 | 0.555141E+10 |
Minimum of Months | 0.276019E+09 | 0.00 | 0.276019E+09 | 0.149192E+09 | 5796770.92 |
Maximum of Months | 0.496220E+09 | 18035530.74 | 0.488362E+09 | 0.165443E+10 | 0.125069E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282947E+09 | 0.00 | 0.282947E+09 | 0.149192E+09 | 0.125069E+10 |
February | 0.303056E+09 | 0.00 | 0.303056E+09 | 0.287323E+09 | 0.872750E+09 |
March | 0.404311E+09 | 0.00 | 0.404311E+09 | 0.638680E+09 | 0.565347E+09 |
April | 0.424558E+09 | 1439819.52 | 0.423118E+09 | 0.108132E+10 | 0.192992E+09 |
May | 0.486059E+09 | 13639734.17 | 0.472420E+09 | 0.157598E+10 | 33518228.33 |
June | 0.486918E+09 | 18035552.38 | 0.468883E+09 | 0.165443E+10 | 23513274.06 |
July | 0.496220E+09 | 7857944.09 | 0.488362E+09 | 0.150776E+10 | 5796784.38 |
August | 0.455544E+09 | 1419727.41 | 0.454125E+09 | 0.125747E+10 | 24074718.90 |
September | 0.392809E+09 | 27582.24 | 0.392782E+09 | 0.963932E+09 | 75275381.51 |
October | 0.351643E+09 | 0.00 | 0.351643E+09 | 0.716105E+09 | 0.433407E+09 |
November | 0.288237E+09 | 0.00 | 0.288237E+09 | 0.361367E+09 | 0.836735E+09 |
December | 0.276020E+09 | 0.00 | 0.276020E+09 | 0.161939E+09 | 0.123732E+10 |
Annual Sum or Average | 0.464832E+10 | 42420359.81 | 0.460590E+10 | 0.103555E+11 | 0.555141E+10 |
Minimum of Months | 0.276020E+09 | 0.00 | 0.276020E+09 | 0.149192E+09 | 5796784.38 |
Maximum of Months | 0.496220E+09 | 18035552.38 | 0.488362E+09 | 0.165443E+10 | 0.125069E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282947E+09 | 0.00 | 0.282947E+09 | 0.149192E+09 | 0.125069E+10 |
February | 0.303056E+09 | 0.00 | 0.303056E+09 | 0.287323E+09 | 0.872750E+09 |
March | 0.404311E+09 | 0.00 | 0.404311E+09 | 0.638680E+09 | 0.565347E+09 |
April | 0.424558E+09 | 1439817.79 | 0.423118E+09 | 0.108132E+10 | 0.192992E+09 |
May | 0.486059E+09 | 13639717.81 | 0.472419E+09 | 0.157598E+10 | 33518164.93 |
June | 0.486918E+09 | 18035530.74 | 0.468882E+09 | 0.165443E+10 | 23513251.31 |
July | 0.496220E+09 | 7857934.66 | 0.488362E+09 | 0.150776E+10 | 5796770.92 |
August | 0.455544E+09 | 1419725.71 | 0.454124E+09 | 0.125747E+10 | 24074681.20 |
September | 0.392809E+09 | 27582.20 | 0.392781E+09 | 0.963932E+09 | 75275278.52 |
October | 0.351643E+09 | 0.00 | 0.351643E+09 | 0.716105E+09 | 0.433406E+09 |
November | 0.288237E+09 | 0.00 | 0.288237E+09 | 0.361367E+09 | 0.836734E+09 |
December | 0.276019E+09 | 0.00 | 0.276019E+09 | 0.161938E+09 | 0.123732E+10 |
Annual Sum or Average | 0.464832E+10 | 42420308.91 | 0.460590E+10 | 0.103555E+11 | 0.555141E+10 |
Minimum of Months | 0.276019E+09 | 0.00 | 0.276019E+09 | 0.149192E+09 | 5796770.92 |
Maximum of Months | 0.496220E+09 | 18035530.74 | 0.488362E+09 | 0.165443E+10 | 0.125069E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.282935E+09 | 0.00 | 0.282935E+09 | 0.149186E+09 | 0.125064E+10 |
February | 0.303044E+09 | 0.00 | 0.303044E+09 | 0.287312E+09 | 0.872715E+09 |
March | 0.404295E+09 | 0.00 | 0.404295E+09 | 0.638654E+09 | 0.565324E+09 |
April | 0.424541E+09 | 1439761.49 | 0.423101E+09 | 0.108127E+10 | 0.192984E+09 |
May | 0.486040E+09 | 13639184.43 | 0.472401E+09 | 0.157592E+10 | 33516877.40 |
June | 0.486899E+09 | 18034825.47 | 0.468864E+09 | 0.165437E+10 | 23512326.37 |
July | 0.496200E+09 | 7857627.38 | 0.488342E+09 | 0.150770E+10 | 5796550.75 |
August | 0.455526E+09 | 1419670.19 | 0.454106E+09 | 0.125742E+10 | 24073748.58 |
September | 0.392793E+09 | 27581.12 | 0.392766E+09 | 0.963894E+09 | 75272347.59 |
October | 0.351629E+09 | 0.00 | 0.351629E+09 | 0.716076E+09 | 0.433389E+09 |
November | 0.288226E+09 | 0.00 | 0.288226E+09 | 0.361352E+09 | 0.836701E+09 |
December | 0.276008E+09 | 0.00 | 0.276008E+09 | 0.161932E+09 | 0.123727E+10 |
Annual Sum or Average | 0.464814E+10 | 42418650.09 | 0.460572E+10 | 0.103551E+11 | 0.555119E+10 |
Minimum of Months | 0.276008E+09 | 0.00 | 0.276008E+09 | 0.149186E+09 | 5796550.75 |
Maximum of Months | 0.496200E+09 | 18034825.47 | 0.488342E+09 | 0.165437E+10 | 0.125064E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.673468E+09 | 0.270321E+09 | 0.403147E+09 | 0.686290E+09 | 0.126565E+10 |
February | 0.739000E+09 | 0.305094E+09 | 0.433906E+09 | 0.979200E+09 | 0.893959E+09 |
March | 0.998091E+09 | 0.411977E+09 | 0.586114E+09 | 0.169271E+10 | 0.587737E+09 |
April | 0.114916E+10 | 0.535799E+09 | 0.613365E+09 | 0.246533E+10 | 0.205701E+09 |
May | 0.116880E+10 | 0.518180E+09 | 0.650615E+09 | 0.290837E+10 | 38248958.72 |
June | 0.920561E+09 | 0.305441E+09 | 0.615119E+09 | 0.255165E+10 | 24681497.07 |
July | 0.799498E+09 | 0.168833E+09 | 0.630665E+09 | 0.215774E+10 | 4406749.94 |
August | 0.720381E+09 | 0.125363E+09 | 0.595018E+09 | 0.182556E+10 | 19153546.73 |
September | 0.744818E+09 | 0.207711E+09 | 0.537106E+09 | 0.164628E+10 | 82091253.89 |
October | 0.841901E+09 | 0.340072E+09 | 0.501828E+09 | 0.163230E+10 | 0.466233E+09 |
November | 0.722388E+09 | 0.310081E+09 | 0.412306E+09 | 0.110266E+10 | 0.861634E+09 |
December | 0.650888E+09 | 0.257886E+09 | 0.393003E+09 | 0.723164E+09 | 0.124691E+10 |
Annual Sum or Average | 0.101290E+11 | 0.375676E+10 | 0.637219E+10 | 0.203713E+11 | 0.569641E+10 |
Minimum of Months | 0.650888E+09 | 0.125363E+09 | 0.393003E+09 | 0.686290E+09 | 4406749.94 |
Maximum of Months | 0.116880E+10 | 0.535799E+09 | 0.650615E+09 | 0.290837E+10 | 0.126565E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.673468E+09 | 0.270321E+09 | 0.403147E+09 | 0.686290E+09 | 0.126565E+10 |
February | 0.739000E+09 | 0.305094E+09 | 0.433906E+09 | 0.979200E+09 | 0.893959E+09 |
March | 0.998091E+09 | 0.411977E+09 | 0.586114E+09 | 0.169271E+10 | 0.587737E+09 |
April | 0.114916E+10 | 0.535799E+09 | 0.613365E+09 | 0.246533E+10 | 0.205701E+09 |
May | 0.116880E+10 | 0.518180E+09 | 0.650615E+09 | 0.290837E+10 | 38248958.72 |
June | 0.920561E+09 | 0.305441E+09 | 0.615119E+09 | 0.255165E+10 | 24681497.07 |
July | 0.799498E+09 | 0.168833E+09 | 0.630665E+09 | 0.215774E+10 | 4406749.94 |
August | 0.720381E+09 | 0.125363E+09 | 0.595018E+09 | 0.182556E+10 | 19153546.73 |
September | 0.744818E+09 | 0.207711E+09 | 0.537106E+09 | 0.164628E+10 | 82091253.89 |
October | 0.841901E+09 | 0.340072E+09 | 0.501828E+09 | 0.163230E+10 | 0.466233E+09 |
November | 0.722388E+09 | 0.310081E+09 | 0.412306E+09 | 0.110266E+10 | 0.861634E+09 |
December | 0.650888E+09 | 0.257886E+09 | 0.393003E+09 | 0.723164E+09 | 0.124691E+10 |
Annual Sum or Average | 0.101290E+11 | 0.375676E+10 | 0.637219E+10 | 0.203713E+11 | 0.569641E+10 |
Minimum of Months | 0.650888E+09 | 0.125363E+09 | 0.393003E+09 | 0.686290E+09 | 4406749.94 |
Maximum of Months | 0.116880E+10 | 0.535799E+09 | 0.650615E+09 | 0.290837E+10 | 0.126565E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.673456E+09 | 0.270316E+09 | 0.403140E+09 | 0.686277E+09 | 0.126563E+10 |
February | 0.738986E+09 | 0.305088E+09 | 0.433898E+09 | 0.979182E+09 | 0.893943E+09 |
March | 0.998073E+09 | 0.411970E+09 | 0.586103E+09 | 0.169268E+10 | 0.587726E+09 |
April | 0.114914E+10 | 0.535789E+09 | 0.613354E+09 | 0.246529E+10 | 0.205697E+09 |
May | 0.116877E+10 | 0.518171E+09 | 0.650603E+09 | 0.290831E+10 | 38248259.83 |
June | 0.920544E+09 | 0.305436E+09 | 0.615108E+09 | 0.255160E+10 | 24681046.08 |
July | 0.799483E+09 | 0.168830E+09 | 0.630654E+09 | 0.215770E+10 | 4406669.42 |
August | 0.720368E+09 | 0.125361E+09 | 0.595007E+09 | 0.182553E+10 | 19153196.75 |
September | 0.744804E+09 | 0.207707E+09 | 0.537097E+09 | 0.164625E+10 | 82089753.90 |
October | 0.841885E+09 | 0.340066E+09 | 0.501819E+09 | 0.163227E+10 | 0.466224E+09 |
November | 0.722374E+09 | 0.310076E+09 | 0.412299E+09 | 0.110264E+10 | 0.861618E+09 |
December | 0.650876E+09 | 0.257881E+09 | 0.392995E+09 | 0.723151E+09 | 0.124689E+10 |
Annual Sum or Average | 0.101288E+11 | 0.375669E+10 | 0.637208E+10 | 0.203709E+11 | 0.569630E+10 |
Minimum of Months | 0.650876E+09 | 0.125361E+09 | 0.392995E+09 | 0.686277E+09 | 4406669.42 |
Maximum of Months | 0.116877E+10 | 0.535789E+09 | 0.650603E+09 | 0.290831E+10 | 0.126563E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128684E+10 | 0.781916E+09 | 0.504922E+09 | 0.183169E+10 | 0.115480E+10 |
February | 0.110518E+10 | 0.613850E+09 | 0.491333E+09 | 0.171832E+10 | 0.851716E+09 |
March | 0.104620E+10 | 0.462100E+09 | 0.584105E+09 | 0.191663E+10 | 0.586253E+09 |
April | 0.711152E+09 | 0.200709E+09 | 0.510443E+09 | 0.174322E+10 | 0.211105E+09 |
May | 0.528459E+09 | 39120360.68 | 0.489339E+09 | 0.168647E+10 | 34346712.34 |
June | 0.467811E+09 | 7983059.50 | 0.459828E+09 | 0.161519E+10 | 23653467.23 |
July | 0.504237E+09 | 6935363.78 | 0.497301E+09 | 0.153093E+10 | 5326185.70 |
August | 0.534888E+09 | 28567075.68 | 0.506321E+09 | 0.143096E+10 | 24582540.85 |
September | 0.693930E+09 | 0.180111E+09 | 0.513819E+09 | 0.157697E+10 | 86270956.55 |
October | 0.123363E+10 | 0.688853E+09 | 0.544776E+09 | 0.240698E+10 | 0.468664E+09 |
November | 0.149116E+10 | 0.985627E+09 | 0.505536E+09 | 0.252937E+10 | 0.846080E+09 |
December | 0.137519E+10 | 0.861730E+09 | 0.513456E+09 | 0.202839E+10 | 0.116347E+10 |
Annual Sum or Average | 0.109787E+11 | 0.485750E+10 | 0.612118E+10 | 0.220151E+11 | 0.545627E+10 |
Minimum of Months | 0.467811E+09 | 6935363.78 | 0.459828E+09 | 0.143096E+10 | 5326185.70 |
Maximum of Months | 0.149116E+10 | 0.985627E+09 | 0.584105E+09 | 0.252937E+10 | 0.116347E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128684E+10 | 0.781915E+09 | 0.504922E+09 | 0.183169E+10 | 0.115480E+10 |
February | 0.110518E+10 | 0.613849E+09 | 0.491333E+09 | 0.171832E+10 | 0.851716E+09 |
March | 0.104620E+10 | 0.462099E+09 | 0.584104E+09 | 0.191663E+10 | 0.586253E+09 |
April | 0.711152E+09 | 0.200709E+09 | 0.510443E+09 | 0.174322E+10 | 0.211105E+09 |
May | 0.528459E+09 | 39120313.74 | 0.489339E+09 | 0.168647E+10 | 34346649.67 |
June | 0.467810E+09 | 7983049.92 | 0.459827E+09 | 0.161519E+10 | 23653445.99 |
July | 0.504236E+09 | 6935355.45 | 0.497301E+09 | 0.153093E+10 | 5326173.70 |
August | 0.534888E+09 | 28567041.40 | 0.506321E+09 | 0.143096E+10 | 24582503.41 |
September | 0.693929E+09 | 0.180111E+09 | 0.513819E+09 | 0.157697E+10 | 86270846.07 |
October | 0.123363E+10 | 0.688853E+09 | 0.544775E+09 | 0.240698E+10 | 0.468664E+09 |
November | 0.149116E+10 | 0.985626E+09 | 0.505535E+09 | 0.252937E+10 | 0.846080E+09 |
December | 0.137518E+10 | 0.861729E+09 | 0.513456E+09 | 0.202839E+10 | 0.116347E+10 |
Annual Sum or Average | 0.109787E+11 | 0.485750E+10 | 0.612117E+10 | 0.220151E+11 | 0.545627E+10 |
Minimum of Months | 0.467810E+09 | 6935355.45 | 0.459827E+09 | 0.143096E+10 | 5326173.70 |
Maximum of Months | 0.149116E+10 | 0.985626E+09 | 0.584104E+09 | 0.252937E+10 | 0.116347E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128684E+10 | 0.781916E+09 | 0.504922E+09 | 0.183169E+10 | 0.115480E+10 |
February | 0.110518E+10 | 0.613850E+09 | 0.491333E+09 | 0.171832E+10 | 0.851716E+09 |
March | 0.104620E+10 | 0.462100E+09 | 0.584105E+09 | 0.191663E+10 | 0.586253E+09 |
April | 0.711152E+09 | 0.200709E+09 | 0.510443E+09 | 0.174322E+10 | 0.211105E+09 |
May | 0.528459E+09 | 39120360.68 | 0.489339E+09 | 0.168647E+10 | 34346712.34 |
June | 0.467811E+09 | 7983059.50 | 0.459828E+09 | 0.161519E+10 | 23653467.23 |
July | 0.504237E+09 | 6935363.78 | 0.497301E+09 | 0.153093E+10 | 5326185.70 |
August | 0.534888E+09 | 28567075.68 | 0.506321E+09 | 0.143096E+10 | 24582540.85 |
September | 0.693930E+09 | 0.180111E+09 | 0.513819E+09 | 0.157697E+10 | 86270956.55 |
October | 0.123363E+10 | 0.688853E+09 | 0.544776E+09 | 0.240698E+10 | 0.468664E+09 |
November | 0.149116E+10 | 0.985627E+09 | 0.505536E+09 | 0.252937E+10 | 0.846080E+09 |
December | 0.137519E+10 | 0.861730E+09 | 0.513456E+09 | 0.202839E+10 | 0.116347E+10 |
Annual Sum or Average | 0.109787E+11 | 0.485750E+10 | 0.612118E+10 | 0.220151E+11 | 0.545627E+10 |
Minimum of Months | 0.467811E+09 | 6935363.78 | 0.459828E+09 | 0.143096E+10 | 5326185.70 |
Maximum of Months | 0.149116E+10 | 0.985627E+09 | 0.584105E+09 | 0.252937E+10 | 0.116347E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128684E+10 | 0.781915E+09 | 0.504922E+09 | 0.183169E+10 | 0.115480E+10 |
February | 0.110518E+10 | 0.613849E+09 | 0.491333E+09 | 0.171832E+10 | 0.851716E+09 |
March | 0.104620E+10 | 0.462099E+09 | 0.584104E+09 | 0.191663E+10 | 0.586253E+09 |
April | 0.711152E+09 | 0.200709E+09 | 0.510443E+09 | 0.174322E+10 | 0.211105E+09 |
May | 0.528459E+09 | 39120313.74 | 0.489339E+09 | 0.168647E+10 | 34346649.67 |
June | 0.467810E+09 | 7983049.92 | 0.459827E+09 | 0.161519E+10 | 23653445.99 |
July | 0.504236E+09 | 6935355.45 | 0.497301E+09 | 0.153093E+10 | 5326173.70 |
August | 0.534888E+09 | 28567041.40 | 0.506321E+09 | 0.143096E+10 | 24582503.41 |
September | 0.693929E+09 | 0.180111E+09 | 0.513819E+09 | 0.157697E+10 | 86270846.07 |
October | 0.123363E+10 | 0.688853E+09 | 0.544775E+09 | 0.240698E+10 | 0.468664E+09 |
November | 0.149116E+10 | 0.985626E+09 | 0.505535E+09 | 0.252937E+10 | 0.846080E+09 |
December | 0.137518E+10 | 0.861729E+09 | 0.513456E+09 | 0.202839E+10 | 0.116347E+10 |
Annual Sum or Average | 0.109787E+11 | 0.485750E+10 | 0.612117E+10 | 0.220151E+11 | 0.545627E+10 |
Minimum of Months | 0.467810E+09 | 6935355.45 | 0.459827E+09 | 0.143096E+10 | 5326173.70 |
Maximum of Months | 0.149116E+10 | 0.985626E+09 | 0.584104E+09 | 0.252937E+10 | 0.116347E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128679E+10 | 0.781885E+09 | 0.504902E+09 | 0.183161E+10 | 0.115476E+10 |
February | 0.110514E+10 | 0.613825E+09 | 0.491313E+09 | 0.171826E+10 | 0.851682E+09 |
March | 0.104616E+10 | 0.462081E+09 | 0.584081E+09 | 0.191655E+10 | 0.586229E+09 |
April | 0.711124E+09 | 0.200701E+09 | 0.510423E+09 | 0.174315E+10 | 0.211096E+09 |
May | 0.528438E+09 | 39118783.96 | 0.489319E+09 | 0.168640E+10 | 34345328.02 |
June | 0.467792E+09 | 7982737.74 | 0.459809E+09 | 0.161513E+10 | 23652513.89 |
July | 0.504216E+09 | 6935084.25 | 0.497281E+09 | 0.153087E+10 | 5325971.03 |
August | 0.534867E+09 | 28565924.30 | 0.506301E+09 | 0.143090E+10 | 24581550.07 |
September | 0.693902E+09 | 0.180104E+09 | 0.513798E+09 | 0.157691E+10 | 86267479.45 |
October | 0.123358E+10 | 0.688826E+09 | 0.544754E+09 | 0.240689E+10 | 0.468645E+09 |
November | 0.149110E+10 | 0.985587E+09 | 0.505515E+09 | 0.252927E+10 | 0.846046E+09 |
December | 0.137513E+10 | 0.861695E+09 | 0.513436E+09 | 0.202831E+10 | 0.116342E+10 |
Annual Sum or Average | 0.109782E+11 | 0.485731E+10 | 0.612093E+10 | 0.220142E+11 | 0.545605E+10 |
Minimum of Months | 0.467792E+09 | 6935084.25 | 0.459809E+09 | 0.143090E+10 | 5325971.03 |
Maximum of Months | 0.149110E+10 | 0.985587E+09 | 0.584081E+09 | 0.252927E+10 | 0.116342E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.658880E+09 | 0.256411E+09 | 0.402469E+09 | 0.746309E+09 | 0.148131E+10 |
February | 0.680533E+09 | 0.250795E+09 | 0.429738E+09 | 0.914605E+09 | 0.108689E+10 |
March | 0.977029E+09 | 0.390553E+09 | 0.586476E+09 | 0.164299E+10 | 0.762409E+09 |
April | 0.114926E+10 | 0.538959E+09 | 0.610301E+09 | 0.238928E+10 | 0.324573E+09 |
May | 0.112452E+10 | 0.476997E+09 | 0.647519E+09 | 0.277859E+10 | 67395900.26 |
June | 0.102215E+10 | 0.397030E+09 | 0.625119E+09 | 0.265231E+10 | 48174185.58 |
July | 0.783770E+09 | 0.152444E+09 | 0.631326E+09 | 0.199832E+10 | 24769754.47 |
August | 0.719810E+09 | 0.127932E+09 | 0.591878E+09 | 0.168146E+10 | 80282344.29 |
September | 0.765736E+09 | 0.224798E+09 | 0.540938E+09 | 0.164667E+10 | 0.137081E+09 |
October | 0.823580E+09 | 0.327948E+09 | 0.495632E+09 | 0.158708E+10 | 0.585969E+09 |
November | 0.721030E+09 | 0.307299E+09 | 0.413731E+09 | 0.112507E+10 | 0.107103E+10 |
December | 0.637556E+09 | 0.243115E+09 | 0.394442E+09 | 0.712718E+09 | 0.154778E+10 |
Annual Sum or Average | 0.100638E+11 | 0.369428E+10 | 0.636957E+10 | 0.198754E+11 | 0.721767E+10 |
Minimum of Months | 0.637556E+09 | 0.127932E+09 | 0.394442E+09 | 0.712718E+09 | 24769754.47 |
Maximum of Months | 0.114926E+10 | 0.538959E+09 | 0.647519E+09 | 0.277859E+10 | 0.154778E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.658880E+09 | 0.256411E+09 | 0.402469E+09 | 0.746309E+09 | 0.148131E+10 |
February | 0.680533E+09 | 0.250795E+09 | 0.429738E+09 | 0.914605E+09 | 0.108689E+10 |
March | 0.977029E+09 | 0.390553E+09 | 0.586476E+09 | 0.164299E+10 | 0.762409E+09 |
April | 0.114926E+10 | 0.538959E+09 | 0.610301E+09 | 0.238928E+10 | 0.324573E+09 |
May | 0.112452E+10 | 0.476997E+09 | 0.647519E+09 | 0.277859E+10 | 67395900.26 |
June | 0.102215E+10 | 0.397030E+09 | 0.625119E+09 | 0.265231E+10 | 48174185.58 |
July | 0.783770E+09 | 0.152444E+09 | 0.631326E+09 | 0.199832E+10 | 24769754.47 |
August | 0.719810E+09 | 0.127932E+09 | 0.591878E+09 | 0.168146E+10 | 80282344.29 |
September | 0.765736E+09 | 0.224798E+09 | 0.540938E+09 | 0.164667E+10 | 0.137081E+09 |
October | 0.823580E+09 | 0.327948E+09 | 0.495632E+09 | 0.158708E+10 | 0.585969E+09 |
November | 0.721030E+09 | 0.307299E+09 | 0.413731E+09 | 0.112507E+10 | 0.107103E+10 |
December | 0.637556E+09 | 0.243115E+09 | 0.394442E+09 | 0.712718E+09 | 0.154778E+10 |
Annual Sum or Average | 0.100638E+11 | 0.369428E+10 | 0.636957E+10 | 0.198754E+11 | 0.721767E+10 |
Minimum of Months | 0.637556E+09 | 0.127932E+09 | 0.394442E+09 | 0.712718E+09 | 24769754.47 |
Maximum of Months | 0.114926E+10 | 0.538959E+09 | 0.647519E+09 | 0.277859E+10 | 0.154778E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.658868E+09 | 0.256406E+09 | 0.402462E+09 | 0.746296E+09 | 0.148128E+10 |
February | 0.680520E+09 | 0.250790E+09 | 0.429730E+09 | 0.914589E+09 | 0.108687E+10 |
March | 0.977011E+09 | 0.390546E+09 | 0.586465E+09 | 0.164296E+10 | 0.762395E+09 |
April | 0.114924E+10 | 0.538949E+09 | 0.610290E+09 | 0.238923E+10 | 0.324568E+09 |
May | 0.112450E+10 | 0.476988E+09 | 0.647507E+09 | 0.277854E+10 | 67394668.79 |
June | 0.102213E+10 | 0.397023E+09 | 0.625107E+09 | 0.265226E+10 | 48173305.33 |
July | 0.783756E+09 | 0.152441E+09 | 0.631315E+09 | 0.199828E+10 | 24769301.87 |
August | 0.719797E+09 | 0.127930E+09 | 0.591867E+09 | 0.168143E+10 | 80280877.35 |
September | 0.765722E+09 | 0.224794E+09 | 0.540928E+09 | 0.164664E+10 | 0.137079E+09 |
October | 0.823565E+09 | 0.327942E+09 | 0.495623E+09 | 0.158705E+10 | 0.585958E+09 |
November | 0.721017E+09 | 0.307293E+09 | 0.413724E+09 | 0.112505E+10 | 0.107102E+10 |
December | 0.637545E+09 | 0.243110E+09 | 0.394434E+09 | 0.712705E+09 | 0.154775E+10 |
Annual Sum or Average | 0.100637E+11 | 0.369421E+10 | 0.636945E+10 | 0.198750E+11 | 0.721754E+10 |
Minimum of Months | 0.637545E+09 | 0.127930E+09 | 0.394434E+09 | 0.712705E+09 | 24769301.87 |
Maximum of Months | 0.114924E+10 | 0.538949E+09 | 0.647507E+09 | 0.277854E+10 | 0.154775E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141472E+10 | 0.00 | 0.141472E+10 | 0.991539E+09 | 0.539696E+10 |
February | 0.151526E+10 | 0.00 | 0.151526E+10 | 0.160587E+10 | 0.389377E+10 |
March | 0.202153E+10 | 0.00 | 0.202153E+10 | 0.328618E+10 | 0.265291E+10 |
April | 0.212276E+10 | 7199010.56 | 0.211556E+10 | 0.554272E+10 | 0.902821E+09 |
May | 0.243027E+10 | 68197846.21 | 0.236207E+10 | 0.794227E+10 | 0.171962E+09 |
June | 0.243456E+10 | 90176671.47 | 0.234438E+10 | 0.833439E+10 | 0.126290E+09 |
July | 0.248107E+10 | 39289245.38 | 0.244178E+10 | 0.762631E+10 | 33806089.67 |
August | 0.227769E+10 | 7098551.23 | 0.227060E+10 | 0.644100E+10 | 0.110652E+09 |
September | 0.196402E+10 | 137909.51 | 0.196388E+10 | 0.485685E+10 | 0.376144E+09 |
October | 0.175819E+10 | 0.00 | 0.175819E+10 | 0.365947E+10 | 0.208918E+10 |
November | 0.144117E+10 | 0.00 | 0.144117E+10 | 0.196111E+10 | 0.379444E+10 |
December | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.107997E+10 | 0.530662E+10 |
Annual Sum or Average | 0.232413E+11 | 0.212099E+09 | 0.230292E+11 | 0.533277E+11 | 0.248556E+11 |
Minimum of Months | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.991539E+09 | 33806089.67 |
Maximum of Months | 0.248107E+10 | 90176671.47 | 0.244178E+10 | 0.833439E+10 | 0.539696E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202038E+10 | 0.810954E+09 | 0.120943E+10 | 0.217386E+10 | 0.343519E+10 |
February | 0.221698E+10 | 0.915271E+09 | 0.130170E+10 | 0.296037E+10 | 0.253593E+10 |
March | 0.299424E+10 | 0.123592E+10 | 0.175832E+10 | 0.503137E+10 | 0.176746E+10 |
April | 0.344746E+10 | 0.160738E+10 | 0.184008E+10 | 0.733284E+10 | 0.658729E+09 |
May | 0.350635E+10 | 0.155453E+10 | 0.195183E+10 | 0.865183E+10 | 0.131054E+09 |
June | 0.276165E+10 | 0.916315E+09 | 0.184534E+10 | 0.758324E+10 | 91397932.78 |
July | 0.239847E+10 | 0.506493E+09 | 0.189198E+10 | 0.640553E+10 | 21656199.26 |
August | 0.216112E+10 | 0.376086E+09 | 0.178503E+10 | 0.542073E+10 | 80287966.58 |
September | 0.223443E+10 | 0.623127E+09 | 0.161130E+10 | 0.488499E+10 | 0.279582E+09 |
October | 0.252568E+10 | 0.102021E+10 | 0.150547E+10 | 0.485619E+10 | 0.142832E+10 |
November | 0.216714E+10 | 0.930235E+09 | 0.123691E+10 | 0.331823E+10 | 0.249377E+10 |
December | 0.195264E+10 | 0.773649E+09 | 0.117900E+10 | 0.226622E+10 | 0.345340E+10 |
Annual Sum or Average | 0.303865E+11 | 0.112702E+11 | 0.191164E+11 | 0.608854E+11 | 0.163768E+11 |
Minimum of Months | 0.195264E+10 | 0.376086E+09 | 0.117900E+10 | 0.217386E+10 | 21656199.26 |
Maximum of Months | 0.350635E+10 | 0.160738E+10 | 0.195183E+10 | 0.865183E+10 | 0.345340E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643411E+10 | 0.390953E+10 | 0.252458E+10 | 0.914671E+10 | 0.556077E+10 |
February | 0.552585E+10 | 0.306921E+10 | 0.245664E+10 | 0.855126E+10 | 0.413717E+10 |
March | 0.523096E+10 | 0.231047E+10 | 0.292049E+10 | 0.954376E+10 | 0.289733E+10 |
April | 0.355572E+10 | 0.100353E+10 | 0.255218E+10 | 0.875275E+10 | 0.103640E+10 |
May | 0.264227E+10 | 0.195599E+09 | 0.244667E+10 | 0.848548E+10 | 0.173370E+09 |
June | 0.233902E+10 | 39914814.84 | 0.229911E+10 | 0.814220E+10 | 0.125367E+09 |
July | 0.252115E+10 | 34676399.57 | 0.248648E+10 | 0.774390E+10 | 30141267.61 |
August | 0.267441E+10 | 0.142834E+09 | 0.253158E+10 | 0.727232E+10 | 0.116797E+09 |
September | 0.346961E+10 | 0.900544E+09 | 0.256906E+10 | 0.786166E+10 | 0.453127E+09 |
October | 0.616807E+10 | 0.344423E+10 | 0.272385E+10 | 0.119733E+11 | 0.238334E+10 |
November | 0.745572E+10 | 0.492808E+10 | 0.252765E+10 | 0.125881E+11 | 0.416735E+10 |
December | 0.687585E+10 | 0.430860E+10 | 0.256725E+10 | 0.101521E+11 | 0.559128E+10 |
Annual Sum or Average | 0.548927E+11 | 0.242872E+11 | 0.306055E+11 | 0.110213E+12 | 0.266725E+11 |
Minimum of Months | 0.233902E+10 | 34676399.57 | 0.229911E+10 | 0.727232E+10 | 30141267.61 |
Maximum of Months | 0.745572E+10 | 0.492808E+10 | 0.292049E+10 | 0.125881E+11 | 0.559128E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197662E+10 | 0.769225E+09 | 0.120739E+10 | 0.239835E+10 | 0.383631E+10 |
February | 0.204158E+10 | 0.752376E+09 | 0.128920E+10 | 0.287174E+10 | 0.282016E+10 |
March | 0.293106E+10 | 0.117165E+10 | 0.175941E+10 | 0.504037E+10 | 0.199175E+10 |
April | 0.344774E+10 | 0.161686E+10 | 0.183088E+10 | 0.734841E+10 | 0.776269E+09 |
May | 0.337351E+10 | 0.143098E+10 | 0.194254E+10 | 0.841657E+10 | 0.173809E+09 |
June | 0.306642E+10 | 0.119108E+10 | 0.187534E+10 | 0.810747E+10 | 0.114762E+09 |
July | 0.235129E+10 | 0.457326E+09 | 0.189396E+10 | 0.623298E+10 | 34817138.38 |
August | 0.215941E+10 | 0.383793E+09 | 0.177562E+10 | 0.536840E+10 | 0.104129E+09 |
September | 0.229718E+10 | 0.674388E+09 | 0.162280E+10 | 0.500341E+10 | 0.341606E+09 |
October | 0.247072E+10 | 0.983835E+09 | 0.148688E+10 | 0.484636E+10 | 0.158106E+10 |
November | 0.216307E+10 | 0.921886E+09 | 0.124118E+10 | 0.351759E+10 | 0.277275E+10 |
December | 0.191265E+10 | 0.729337E+09 | 0.118331E+10 | 0.238610E+10 | 0.377970E+10 |
Annual Sum or Average | 0.301912E+11 | 0.110827E+11 | 0.191085E+11 | 0.615377E+11 | 0.183271E+11 |
Minimum of Months | 0.191265E+10 | 0.383793E+09 | 0.118331E+10 | 0.238610E+10 | 34817138.38 |
Maximum of Months | 0.344774E+10 | 0.161686E+10 | 0.194254E+10 | 0.841657E+10 | 0.383631E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.141472E+10 | 0.00 | 0.141472E+10 | 0.111871E+10 | 0.490064E+10 |
February | 0.151526E+10 | 0.00 | 0.151526E+10 | 0.168486E+10 | 0.362993E+10 |
March | 0.202153E+10 | 0.00 | 0.202153E+10 | 0.327457E+10 | 0.256954E+10 |
April | 0.212276E+10 | 7199010.56 | 0.211556E+10 | 0.545403E+10 | 0.919260E+09 |
May | 0.243027E+10 | 68197846.21 | 0.236207E+10 | 0.781138E+10 | 0.193877E+09 |
June | 0.243456E+10 | 90176671.47 | 0.234438E+10 | 0.820090E+10 | 0.137047E+09 |
July | 0.248107E+10 | 39289245.38 | 0.244178E+10 | 0.747540E+10 | 36795893.53 |
August | 0.227769E+10 | 7098551.23 | 0.227060E+10 | 0.631755E+10 | 0.121599E+09 |
September | 0.196402E+10 | 137909.51 | 0.196388E+10 | 0.477841E+10 | 0.401901E+09 |
October | 0.175819E+10 | 0.00 | 0.175819E+10 | 0.362703E+10 | 0.204824E+10 |
November | 0.144117E+10 | 0.00 | 0.144117E+10 | 0.202517E+10 | 0.356913E+10 |
December | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.122747E+10 | 0.483699E+10 |
Annual Sum or Average | 0.232413E+11 | 0.212099E+09 | 0.230292E+11 | 0.529955E+11 | 0.233650E+11 |
Minimum of Months | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.111871E+10 | 36795893.53 |
Maximum of Months | 0.248107E+10 | 90176671.47 | 0.244178E+10 | 0.820090E+10 | 0.490064E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202038E+10 | 0.810954E+09 | 0.120943E+10 | 0.233036E+10 | 0.312729E+10 |
February | 0.221698E+10 | 0.915271E+09 | 0.130170E+10 | 0.303695E+10 | 0.238730E+10 |
March | 0.299424E+10 | 0.123592E+10 | 0.175832E+10 | 0.504104E+10 | 0.172341E+10 |
April | 0.344746E+10 | 0.160738E+10 | 0.184008E+10 | 0.729548E+10 | 0.666435E+09 |
May | 0.350635E+10 | 0.155453E+10 | 0.195183E+10 | 0.858662E+10 | 0.143839E+09 |
June | 0.276165E+10 | 0.916315E+09 | 0.184534E+10 | 0.751755E+10 | 97722837.92 |
July | 0.239847E+10 | 0.506493E+09 | 0.189198E+10 | 0.632974E+10 | 23059416.11 |
August | 0.216112E+10 | 0.376086E+09 | 0.178503E+10 | 0.536389E+10 | 87014305.05 |
September | 0.223443E+10 | 0.623127E+09 | 0.161130E+10 | 0.485440E+10 | 0.294367E+09 |
October | 0.252568E+10 | 0.102021E+10 | 0.150547E+10 | 0.485533E+10 | 0.140397E+10 |
November | 0.216714E+10 | 0.930235E+09 | 0.123691E+10 | 0.337955E+10 | 0.237191E+10 |
December | 0.195264E+10 | 0.773649E+09 | 0.117900E+10 | 0.241440E+10 | 0.317657E+10 |
Annual Sum or Average | 0.303865E+11 | 0.112702E+11 | 0.191164E+11 | 0.610053E+11 | 0.155029E+11 |
Minimum of Months | 0.195264E+10 | 0.376086E+09 | 0.117900E+10 | 0.233036E+10 | 23059416.11 |
Maximum of Months | 0.350635E+10 | 0.160738E+10 | 0.195183E+10 | 0.858662E+10 | 0.317657E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643411E+10 | 0.390953E+10 | 0.252458E+10 | 0.930053E+10 | 0.511023E+10 |
February | 0.552585E+10 | 0.306921E+10 | 0.245664E+10 | 0.860652E+10 | 0.391016E+10 |
March | 0.523096E+10 | 0.231047E+10 | 0.292049E+10 | 0.951233E+10 | 0.282123E+10 |
April | 0.355572E+10 | 0.100353E+10 | 0.255218E+10 | 0.866497E+10 | 0.104975E+10 |
May | 0.264227E+10 | 0.195599E+09 | 0.244667E+10 | 0.835542E+10 | 0.194035E+09 |
June | 0.233902E+10 | 39914814.84 | 0.229911E+10 | 0.800778E+10 | 0.136576E+09 |
July | 0.252115E+10 | 34676399.57 | 0.248648E+10 | 0.759238E+10 | 32676515.80 |
August | 0.267441E+10 | 0.142834E+09 | 0.253158E+10 | 0.715048E+10 | 0.128072E+09 |
September | 0.346961E+10 | 0.900544E+09 | 0.256906E+10 | 0.778200E+10 | 0.478380E+09 |
October | 0.616807E+10 | 0.344423E+10 | 0.272385E+10 | 0.119329E+11 | 0.234373E+10 |
November | 0.745572E+10 | 0.492808E+10 | 0.252765E+10 | 0.126128E+11 | 0.398675E+10 |
December | 0.687585E+10 | 0.430860E+10 | 0.256725E+10 | 0.102977E+11 | 0.520340E+10 |
Annual Sum or Average | 0.548927E+11 | 0.242872E+11 | 0.306055E+11 | 0.109816E+12 | 0.253950E+11 |
Minimum of Months | 0.233902E+10 | 34676399.57 | 0.229911E+10 | 0.715048E+10 | 32676515.80 |
Maximum of Months | 0.745572E+10 | 0.492808E+10 | 0.292049E+10 | 0.126128E+11 | 0.520340E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.197662E+10 | 0.769225E+09 | 0.120739E+10 | 0.246359E+10 | 0.354437E+10 |
February | 0.204158E+10 | 0.752376E+09 | 0.128920E+10 | 0.289865E+10 | 0.266737E+10 |
March | 0.293106E+10 | 0.117165E+10 | 0.175941E+10 | 0.501585E+10 | 0.193896E+10 |
April | 0.344774E+10 | 0.161686E+10 | 0.183088E+10 | 0.729148E+10 | 0.780429E+09 |
May | 0.337351E+10 | 0.143098E+10 | 0.194254E+10 | 0.833957E+10 | 0.185655E+09 |
June | 0.306642E+10 | 0.119108E+10 | 0.187534E+10 | 0.802560E+10 | 0.120692E+09 |
July | 0.235129E+10 | 0.457326E+09 | 0.189396E+10 | 0.614420E+10 | 37564733.92 |
August | 0.215941E+10 | 0.383793E+09 | 0.177562E+10 | 0.530059E+10 | 0.112251E+09 |
September | 0.229718E+10 | 0.674388E+09 | 0.162280E+10 | 0.495486E+10 | 0.356421E+09 |
October | 0.247072E+10 | 0.983835E+09 | 0.148688E+10 | 0.481995E+10 | 0.155309E+10 |
November | 0.216307E+10 | 0.921886E+09 | 0.124118E+10 | 0.353490E+10 | 0.264423E+10 |
December | 0.191265E+10 | 0.729337E+09 | 0.118331E+10 | 0.245837E+10 | 0.351374E+10 |
Annual Sum or Average | 0.301912E+11 | 0.110827E+11 | 0.191085E+11 | 0.612476E+11 | 0.174548E+11 |
Minimum of Months | 0.191265E+10 | 0.383793E+09 | 0.118331E+10 | 0.245837E+10 | 37564733.92 |
Maximum of Months | 0.344774E+10 | 0.161686E+10 | 0.194254E+10 | 0.833957E+10 | 0.354437E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 278.51 | 2334.75 | 528.20 | 0.00 | 528.20 | 0.00 | 0.00 |
February | 593.83 | 1803.79 | 626.35 | 0.00 | 626.35 | 0.00 | 0.00 |
March | 1192.27 | 1055.37 | 754.76 | 0.00 | 754.76 | 0.00 | 0.00 |
April | 2085.86 | 372.28 | 818.97 | 2.78 | 816.19 | 0.00 | 0.00 |
May | 2942.00 | 62.57 | 907.36 | 25.46 | 881.90 | 0.00 | 0.00 |
June | 3191.39 | 45.36 | 939.26 | 34.79 | 904.47 | 0.00 | 0.00 |
July | 2814.64 | 10.82 | 926.33 | 14.67 | 911.66 | 0.00 | 0.00 |
August | 2347.42 | 44.94 | 850.40 | 2.65 | 847.75 | 0.00 | 0.00 |
September | 1859.42 | 145.21 | 757.73 | 0.05 | 757.67 | 0.00 | 0.00 |
October | 1336.80 | 809.07 | 656.44 | 0.00 | 656.44 | 0.00 | 0.00 |
November | 697.08 | 1614.06 | 556.01 | 0.00 | 556.01 | 0.00 | 0.00 |
December | 302.30 | 2309.79 | 515.27 | 0.00 | 515.27 | 0.00 | 0.00 |
Annual Sum or Average | 1641.84 | 880.16 | 736.98 | 6.73 | 730.26 | 0.00 | 0.00 |
Minimum of Months | 278.51 | 10.82 | 515.27 | 0.00 | 515.27 | 0.00 | 0.00 |
Maximum of Months | 3191.39 | 2334.75 | 939.26 | 34.79 | 911.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 768.69 | 1417.61 | 754.33 | 302.78 | 451.55 | 0.00 | 0.00 |
February | 1214.28 | 1108.57 | 916.41 | 378.34 | 538.07 | 0.00 | 0.00 |
March | 1895.95 | 658.30 | 1117.93 | 461.44 | 656.49 | 0.00 | 0.00 |
April | 2853.37 | 238.08 | 1330.04 | 620.13 | 709.91 | 0.00 | 0.00 |
May | 3257.56 | 42.84 | 1309.13 | 580.40 | 728.73 | 0.00 | 0.00 |
June | 2953.28 | 28.57 | 1065.46 | 353.52 | 711.94 | 0.00 | 0.00 |
July | 2416.80 | 4.94 | 895.49 | 189.10 | 706.39 | 0.00 | 0.00 |
August | 2044.75 | 21.45 | 806.87 | 140.41 | 666.46 | 0.00 | 0.00 |
September | 1905.40 | 95.01 | 862.05 | 240.41 | 621.65 | 0.00 | 0.00 |
October | 1828.28 | 522.21 | 942.98 | 380.90 | 562.08 | 0.00 | 0.00 |
November | 1276.22 | 997.26 | 836.09 | 358.89 | 477.20 | 0.00 | 0.00 |
December | 809.99 | 1396.62 | 729.04 | 288.85 | 440.19 | 0.00 | 0.00 |
Annual Sum or Average | 1937.89 | 541.89 | 963.55 | 357.38 | 606.18 | 0.00 | 0.00 |
Minimum of Months | 768.69 | 4.94 | 729.04 | 140.41 | 440.19 | 0.00 | 0.00 |
Maximum of Months | 3257.56 | 1417.61 | 1330.04 | 620.13 | 728.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3419.34 | 2155.75 | 2402.23 | 1459.66 | 942.57 | 0.00 | 0.00 |
February | 3551.40 | 1760.31 | 2284.17 | 1268.69 | 1015.48 | 0.00 | 0.00 |
March | 3577.91 | 1094.40 | 1953.02 | 862.63 | 1090.39 | 0.00 | 0.00 |
April | 3362.66 | 407.22 | 1371.81 | 387.17 | 984.64 | 0.00 | 0.00 |
May | 3148.26 | 64.12 | 986.51 | 73.03 | 913.48 | 0.00 | 0.00 |
June | 3115.70 | 45.63 | 902.40 | 15.40 | 887.01 | 0.00 | 0.00 |
July | 2857.89 | 9.94 | 941.29 | 12.95 | 928.35 | 0.00 | 0.00 |
August | 2671.27 | 45.89 | 998.51 | 53.33 | 945.19 | 0.00 | 0.00 |
September | 3041.97 | 166.42 | 1338.59 | 347.43 | 991.15 | 0.00 | 0.00 |
October | 4493.29 | 874.89 | 2302.90 | 1285.93 | 1016.97 | 0.00 | 0.00 |
November | 4879.15 | 1632.09 | 2876.45 | 1901.27 | 975.18 | 0.00 | 0.00 |
December | 3786.54 | 2171.93 | 2567.16 | 1608.65 | 958.51 | 0.00 | 0.00 |
Annual Sum or Average | 3490.45 | 865.08 | 1740.64 | 770.15 | 970.50 | 0.00 | 0.00 |
Minimum of Months | 2671.27 | 9.94 | 902.40 | 12.95 | 887.01 | 0.00 | 0.00 |
Maximum of Months | 4879.15 | 2171.93 | 2876.45 | 1901.27 | 1090.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 835.91 | 1659.17 | 737.99 | 287.20 | 450.79 | 0.00 | 0.00 |
February | 1134.18 | 1347.82 | 843.91 | 311.00 | 532.91 | 0.00 | 0.00 |
March | 1840.26 | 853.95 | 1094.34 | 437.44 | 656.89 | 0.00 | 0.00 |
April | 2765.35 | 375.66 | 1330.15 | 623.79 | 706.36 | 0.00 | 0.00 |
May | 3112.21 | 75.49 | 1259.53 | 534.27 | 725.26 | 0.00 | 0.00 |
June | 3069.79 | 55.76 | 1183.04 | 459.52 | 723.51 | 0.00 | 0.00 |
July | 2238.24 | 27.74 | 877.87 | 170.75 | 707.13 | 0.00 | 0.00 |
August | 1883.34 | 89.92 | 806.23 | 143.29 | 662.94 | 0.00 | 0.00 |
September | 1905.86 | 158.66 | 886.26 | 260.18 | 626.08 | 0.00 | 0.00 |
October | 1777.64 | 656.32 | 922.46 | 367.32 | 555.14 | 0.00 | 0.00 |
November | 1302.16 | 1239.62 | 834.52 | 355.67 | 478.85 | 0.00 | 0.00 |
December | 798.29 | 1733.61 | 714.10 | 272.30 | 441.80 | 0.00 | 0.00 |
Annual Sum or Average | 1890.72 | 686.61 | 957.36 | 351.43 | 605.93 | 0.00 | 0.00 |
Minimum of Months | 798.29 | 27.74 | 714.10 | 143.29 | 441.80 | 0.00 | 0.00 |
Maximum of Months | 3112.21 | 1733.61 | 1330.15 | 623.79 | 725.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 370.20 | 2014.99 | 528.19 | 0.00 | 528.19 | 0.00 | 0.00 |
February | 663.80 | 1609.53 | 626.35 | 0.00 | 626.35 | 0.00 | 0.00 |
March | 1226.92 | 990.48 | 754.75 | 0.00 | 754.75 | 0.00 | 0.00 |
April | 2138.40 | 348.31 | 818.97 | 2.78 | 816.19 | 0.00 | 0.00 |
May | 2965.31 | 64.20 | 907.36 | 25.46 | 881.90 | 0.00 | 0.00 |
June | 3215.43 | 48.72 | 939.26 | 34.79 | 904.47 | 0.00 | 0.00 |
July | 2847.34 | 12.62 | 926.33 | 14.67 | 911.66 | 0.00 | 0.00 |
August | 2404.79 | 41.31 | 850.39 | 2.65 | 847.74 | 0.00 | 0.00 |
September | 1873.78 | 145.12 | 757.72 | 0.05 | 757.67 | 0.00 | 0.00 |
October | 1366.29 | 780.01 | 656.43 | 0.00 | 656.43 | 0.00 | 0.00 |
November | 756.60 | 1463.91 | 556.01 | 0.00 | 556.01 | 0.00 | 0.00 |
December | 403.21 | 1981.26 | 515.26 | 0.00 | 515.26 | 0.00 | 0.00 |
Annual Sum or Average | 1691.01 | 788.16 | 736.98 | 6.73 | 730.25 | 0.00 | 0.00 |
Minimum of Months | 370.20 | 12.62 | 515.26 | 0.00 | 515.26 | 0.00 | 0.00 |
Maximum of Months | 3215.43 | 2014.99 | 939.26 | 34.79 | 911.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 811.63 | 1282.55 | 754.32 | 302.78 | 451.55 | 0.00 | 0.00 |
February | 1223.70 | 1048.25 | 916.41 | 378.34 | 538.07 | 0.00 | 0.00 |
March | 1878.50 | 659.89 | 1117.92 | 461.44 | 656.48 | 0.00 | 0.00 |
April | 2829.03 | 254.14 | 1330.04 | 620.13 | 709.91 | 0.00 | 0.00 |
May | 3230.22 | 48.93 | 1309.12 | 580.39 | 728.73 | 0.00 | 0.00 |
June | 2925.63 | 35.26 | 1065.45 | 353.52 | 711.94 | 0.00 | 0.00 |
July | 2391.55 | 8.09 | 895.49 | 189.10 | 706.38 | 0.00 | 0.00 |
August | 2023.87 | 29.98 | 806.87 | 140.41 | 666.46 | 0.00 | 0.00 |
September | 1884.64 | 107.86 | 862.05 | 240.40 | 621.64 | 0.00 | 0.00 |
October | 1813.09 | 533.27 | 942.98 | 380.90 | 562.08 | 0.00 | 0.00 |
November | 1280.18 | 962.10 | 836.09 | 358.89 | 477.20 | 0.00 | 0.00 |
December | 846.11 | 1289.35 | 729.03 | 288.85 | 440.19 | 0.00 | 0.00 |
Annual Sum or Average | 1930.66 | 519.30 | 963.55 | 357.37 | 606.18 | 0.00 | 0.00 |
Minimum of Months | 811.63 | 8.09 | 729.03 | 140.41 | 440.19 | 0.00 | 0.00 |
Maximum of Months | 3230.22 | 1289.35 | 1330.04 | 620.13 | 728.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3414.99 | 2076.15 | 2402.22 | 1459.65 | 942.57 | 0.00 | 0.00 |
February | 3534.75 | 1710.14 | 2284.16 | 1268.69 | 1015.47 | 0.00 | 0.00 |
March | 3563.23 | 1081.74 | 1953.02 | 862.63 | 1090.39 | 0.00 | 0.00 |
April | 3376.83 | 399.85 | 1371.80 | 387.17 | 984.64 | 0.00 | 0.00 |
May | 3168.11 | 64.73 | 986.51 | 73.03 | 913.48 | 0.00 | 0.00 |
June | 3141.28 | 48.37 | 902.40 | 15.40 | 887.00 | 0.00 | 0.00 |
July | 2891.24 | 11.25 | 941.29 | 12.95 | 928.34 | 0.00 | 0.00 |
August | 2715.17 | 43.61 | 998.51 | 53.33 | 945.18 | 0.00 | 0.00 |
September | 3033.05 | 174.82 | 1338.58 | 347.43 | 991.15 | 0.00 | 0.00 |
October | 4470.31 | 889.84 | 2302.89 | 1285.93 | 1016.97 | 0.00 | 0.00 |
November | 4856.53 | 1607.78 | 2876.44 | 1901.26 | 975.17 | 0.00 | 0.00 |
December | 3790.35 | 2087.55 | 2567.15 | 1608.65 | 958.50 | 0.00 | 0.00 |
Annual Sum or Average | 3494.85 | 845.78 | 1740.64 | 770.14 | 970.49 | 0.00 | 0.00 |
Minimum of Months | 2715.17 | 11.25 | 902.40 | 12.95 | 887.00 | 0.00 | 0.00 |
Maximum of Months | 4856.53 | 2087.55 | 2876.44 | 1901.26 | 1090.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 895.44 | 1432.31 | 737.99 | 287.20 | 450.79 | 0.00 | 0.00 |
February | 1187.06 | 1165.74 | 843.91 | 311.00 | 532.90 | 0.00 | 0.00 |
March | 1881.86 | 743.64 | 1094.33 | 437.44 | 656.89 | 0.00 | 0.00 |
April | 2835.03 | 299.49 | 1330.15 | 623.79 | 706.36 | 0.00 | 0.00 |
May | 3142.39 | 64.89 | 1259.53 | 534.27 | 725.26 | 0.00 | 0.00 |
June | 3127.88 | 44.28 | 1183.03 | 459.52 | 723.51 | 0.00 | 0.00 |
July | 2327.13 | 13.00 | 877.87 | 170.75 | 707.12 | 0.00 | 0.00 |
August | 2004.33 | 38.88 | 806.23 | 143.29 | 662.94 | 0.00 | 0.00 |
September | 1930.33 | 131.79 | 886.26 | 260.18 | 626.08 | 0.00 | 0.00 |
October | 1809.42 | 590.30 | 922.46 | 367.32 | 555.14 | 0.00 | 0.00 |
November | 1357.10 | 1069.73 | 834.52 | 355.67 | 478.85 | 0.00 | 0.00 |
December | 890.87 | 1411.18 | 714.10 | 272.30 | 441.80 | 0.00 | 0.00 |
Annual Sum or Average | 1951.35 | 581.15 | 957.36 | 351.43 | 605.93 | 0.00 | 0.00 |
Minimum of Months | 890.87 | 13.00 | 714.10 | 143.29 | 441.80 | 0.00 | 0.00 |
Maximum of Months | 3142.39 | 1432.31 | 1330.15 | 623.79 | 725.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 417.68 | 1829.69 | 528.19 | 0.00 | 528.19 | 0.00 | 0.00 |
February | 696.45 | 1500.47 | 626.35 | 0.00 | 626.35 | 0.00 | 0.00 |
March | 1222.59 | 959.36 | 754.75 | 0.00 | 754.75 | 0.00 | 0.00 |
April | 2104.18 | 354.65 | 818.97 | 2.78 | 816.19 | 0.00 | 0.00 |
May | 2916.43 | 72.39 | 907.36 | 25.46 | 881.90 | 0.00 | 0.00 |
June | 3163.93 | 52.87 | 939.26 | 34.79 | 904.47 | 0.00 | 0.00 |
July | 2790.99 | 13.74 | 926.33 | 14.67 | 911.66 | 0.00 | 0.00 |
August | 2358.70 | 45.40 | 850.39 | 2.65 | 847.74 | 0.00 | 0.00 |
September | 1843.52 | 155.05 | 757.72 | 0.05 | 757.67 | 0.00 | 0.00 |
October | 1354.18 | 764.73 | 656.43 | 0.00 | 656.43 | 0.00 | 0.00 |
November | 781.32 | 1376.98 | 556.01 | 0.00 | 556.01 | 0.00 | 0.00 |
December | 458.28 | 1805.93 | 515.26 | 0.00 | 515.26 | 0.00 | 0.00 |
Annual Sum or Average | 1680.48 | 740.90 | 736.98 | 6.73 | 730.25 | 0.00 | 0.00 |
Minimum of Months | 417.68 | 13.74 | 515.26 | 0.00 | 515.26 | 0.00 | 0.00 |
Maximum of Months | 3163.93 | 1829.69 | 939.26 | 34.79 | 911.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 870.06 | 1167.60 | 754.32 | 302.78 | 451.55 | 0.00 | 0.00 |
February | 1255.35 | 986.81 | 916.41 | 378.34 | 538.07 | 0.00 | 0.00 |
March | 1882.11 | 643.45 | 1117.92 | 461.44 | 656.48 | 0.00 | 0.00 |
April | 2814.61 | 257.11 | 1330.04 | 620.13 | 709.91 | 0.00 | 0.00 |
May | 3205.88 | 53.70 | 1309.12 | 580.39 | 728.73 | 0.00 | 0.00 |
June | 2900.29 | 37.70 | 1065.45 | 353.52 | 711.94 | 0.00 | 0.00 |
July | 2363.25 | 8.61 | 895.49 | 189.10 | 706.38 | 0.00 | 0.00 |
August | 2002.65 | 32.49 | 806.87 | 140.41 | 666.46 | 0.00 | 0.00 |
September | 1872.84 | 113.57 | 862.05 | 240.40 | 621.64 | 0.00 | 0.00 |
October | 1812.77 | 524.18 | 942.98 | 380.90 | 562.08 | 0.00 | 0.00 |
November | 1303.84 | 915.09 | 836.09 | 358.89 | 477.20 | 0.00 | 0.00 |
December | 901.43 | 1185.99 | 729.03 | 288.85 | 440.19 | 0.00 | 0.00 |
Annual Sum or Average | 1934.47 | 491.59 | 963.55 | 357.37 | 606.18 | 0.00 | 0.00 |
Minimum of Months | 870.06 | 8.61 | 729.03 | 140.41 | 440.19 | 0.00 | 0.00 |
Maximum of Months | 3205.88 | 1185.99 | 1330.04 | 620.13 | 728.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3472.42 | 1907.94 | 2402.22 | 1459.65 | 942.57 | 0.00 | 0.00 |
February | 3557.59 | 1616.30 | 2284.16 | 1268.69 | 1015.47 | 0.00 | 0.00 |
March | 3551.50 | 1053.33 | 1953.02 | 862.63 | 1090.39 | 0.00 | 0.00 |
April | 3342.96 | 405.00 | 1371.80 | 387.17 | 984.64 | 0.00 | 0.00 |
May | 3119.56 | 72.44 | 986.51 | 73.03 | 913.48 | 0.00 | 0.00 |
June | 3089.42 | 52.69 | 902.40 | 15.40 | 887.00 | 0.00 | 0.00 |
July | 2834.67 | 12.20 | 941.29 | 12.95 | 928.34 | 0.00 | 0.00 |
August | 2669.68 | 47.82 | 998.51 | 53.33 | 945.18 | 0.00 | 0.00 |
September | 3002.32 | 184.56 | 1338.58 | 347.43 | 991.15 | 0.00 | 0.00 |
October | 4455.24 | 875.05 | 2302.89 | 1285.93 | 1016.97 | 0.00 | 0.00 |
November | 4866.05 | 1538.10 | 2876.44 | 1901.26 | 975.17 | 0.00 | 0.00 |
December | 3844.73 | 1942.73 | 2567.15 | 1608.65 | 958.50 | 0.00 | 0.00 |
Annual Sum or Average | 3482.24 | 805.27 | 1740.64 | 770.14 | 970.49 | 0.00 | 0.00 |
Minimum of Months | 2669.68 | 12.20 | 902.40 | 12.95 | 887.00 | 0.00 | 0.00 |
Maximum of Months | 4866.05 | 1942.73 | 2876.44 | 1901.26 | 1090.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 919.80 | 1323.32 | 737.99 | 287.20 | 450.79 | 0.00 | 0.00 |
February | 1198.18 | 1102.58 | 843.91 | 311.00 | 532.90 | 0.00 | 0.00 |
March | 1872.71 | 723.92 | 1094.33 | 437.44 | 656.89 | 0.00 | 0.00 |
April | 2813.07 | 301.09 | 1330.15 | 623.79 | 706.36 | 0.00 | 0.00 |
May | 3113.64 | 69.32 | 1259.53 | 534.27 | 725.26 | 0.00 | 0.00 |
June | 3096.29 | 46.56 | 1183.03 | 459.52 | 723.51 | 0.00 | 0.00 |
July | 2293.98 | 14.03 | 877.87 | 170.75 | 707.12 | 0.00 | 0.00 |
August | 1979.01 | 41.91 | 806.23 | 143.29 | 662.94 | 0.00 | 0.00 |
September | 1911.60 | 137.51 | 886.26 | 260.18 | 626.08 | 0.00 | 0.00 |
October | 1799.56 | 579.86 | 922.46 | 367.32 | 555.14 | 0.00 | 0.00 |
November | 1363.77 | 1020.15 | 834.52 | 355.67 | 478.85 | 0.00 | 0.00 |
December | 917.85 | 1311.88 | 714.10 | 272.30 | 441.80 | 0.00 | 0.00 |
Annual Sum or Average | 1942.15 | 553.49 | 957.36 | 351.43 | 605.93 | 0.00 | 0.00 |
Minimum of Months | 917.85 | 14.03 | 714.10 | 143.29 | 441.80 | 0.00 | 0.00 |
Maximum of Months | 3113.64 | 1323.32 | 1330.15 | 623.79 | 725.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.745952E+09 | 0.625338E+10 | 0.141472E+10 | 0.00 | 0.141472E+10 | 0.00 | 0.00 |
February | 0.143661E+10 | 0.436372E+10 | 0.151527E+10 | 0.00 | 0.151527E+10 | 0.00 | 0.00 |
March | 0.319337E+10 | 0.282671E+10 | 0.202154E+10 | 0.00 | 0.202154E+10 | 0.00 | 0.00 |
April | 0.540654E+10 | 0.964953E+09 | 0.212277E+10 | 7199036.12 | 0.211557E+10 | 0.00 | 0.00 |
May | 0.787984E+10 | 0.167590E+09 | 0.243028E+10 | 68198088.39 | 0.236208E+10 | 0.00 | 0.00 |
June | 0.827209E+10 | 0.117565E+09 | 0.243457E+10 | 90176991.69 | 0.234439E+10 | 0.00 | 0.00 |
July | 0.753873E+10 | 28983661.35 | 0.248108E+10 | 39289384.90 | 0.244179E+10 | 0.00 | 0.00 |
August | 0.628732E+10 | 0.120373E+09 | 0.227770E+10 | 7098576.44 | 0.227060E+10 | 0.00 | 0.00 |
September | 0.481962E+10 | 0.376374E+09 | 0.196403E+10 | 137910.00 | 0.196389E+10 | 0.00 | 0.00 |
October | 0.358050E+10 | 0.216702E+10 | 0.175820E+10 | 0.00 | 0.175820E+10 | 0.00 | 0.00 |
November | 0.180682E+10 | 0.418364E+10 | 0.144117E+10 | 0.00 | 0.144117E+10 | 0.00 | 0.00 |
December | 0.809686E+09 | 0.618654E+10 | 0.138009E+10 | 0.00 | 0.138009E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.517771E+11 | 0.277568E+11 | 0.232414E+11 | 0.212100E+09 | 0.230293E+11 | 0.00 | 0.00 |
Minimum of Months | 0.745952E+09 | 28983661.35 | 0.138009E+10 | 0.00 | 0.138009E+10 | 0.00 | 0.00 |
Maximum of Months | 0.827209E+10 | 0.625338E+10 | 0.248108E+10 | 90176991.69 | 0.244179E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205886E+10 | 0.379694E+10 | 0.202039E+10 | 0.810957E+09 | 0.120943E+10 | 0.00 | 0.00 |
February | 0.293758E+10 | 0.268186E+10 | 0.221699E+10 | 0.915275E+09 | 0.130171E+10 | 0.00 | 0.00 |
March | 0.507811E+10 | 0.176320E+10 | 0.299425E+10 | 0.123592E+10 | 0.175833E+10 | 0.00 | 0.00 |
April | 0.739595E+10 | 0.617098E+09 | 0.344747E+10 | 0.160739E+10 | 0.184008E+10 | 0.00 | 0.00 |
May | 0.872504E+10 | 0.114746E+09 | 0.350637E+10 | 0.155453E+10 | 0.195183E+10 | 0.00 | 0.00 |
June | 0.765489E+10 | 74044040.22 | 0.276167E+10 | 0.916318E+09 | 0.184535E+10 | 0.00 | 0.00 |
July | 0.647317E+10 | 13220169.29 | 0.239848E+10 | 0.506495E+09 | 0.189198E+10 | 0.00 | 0.00 |
August | 0.547666E+10 | 57460290.21 | 0.216113E+10 | 0.376087E+09 | 0.178504E+10 | 0.00 | 0.00 |
September | 0.493881E+10 | 0.246272E+09 | 0.223444E+10 | 0.623130E+09 | 0.161131E+10 | 0.00 | 0.00 |
October | 0.489688E+10 | 0.139869E+10 | 0.252569E+10 | 0.102021E+10 | 0.150548E+10 | 0.00 | 0.00 |
November | 0.330797E+10 | 0.258489E+10 | 0.216715E+10 | 0.930239E+09 | 0.123691E+10 | 0.00 | 0.00 |
December | 0.216948E+10 | 0.374071E+10 | 0.195265E+10 | 0.773652E+09 | 0.117900E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.611134E+11 | 0.170891E+11 | 0.303867E+11 | 0.112702E+11 | 0.191165E+11 | 0.00 | 0.00 |
Minimum of Months | 0.205886E+10 | 13220169.29 | 0.195265E+10 | 0.376087E+09 | 0.117900E+10 | 0.00 | 0.00 |
Maximum of Months | 0.872504E+10 | 0.379694E+10 | 0.350637E+10 | 0.160739E+10 | 0.195183E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.915836E+10 | 0.577397E+10 | 0.643414E+10 | 0.390955E+10 | 0.252459E+10 | 0.00 | 0.00 |
February | 0.859155E+10 | 0.425855E+10 | 0.552587E+10 | 0.306922E+10 | 0.245665E+10 | 0.00 | 0.00 |
March | 0.958308E+10 | 0.293124E+10 | 0.523098E+10 | 0.231048E+10 | 0.292050E+10 | 0.00 | 0.00 |
April | 0.871601E+10 | 0.105551E+10 | 0.355573E+10 | 0.100354E+10 | 0.255219E+10 | 0.00 | 0.00 |
May | 0.843230E+10 | 0.171732E+09 | 0.264228E+10 | 0.195600E+09 | 0.244667E+10 | 0.00 | 0.00 |
June | 0.807589E+10 | 0.118266E+09 | 0.233903E+10 | 39914956.58 | 0.229912E+10 | 0.00 | 0.00 |
July | 0.765458E+10 | 26630689.84 | 0.252116E+10 | 34676522.71 | 0.248649E+10 | 0.00 | 0.00 |
August | 0.715474E+10 | 0.122912E+09 | 0.267442E+10 | 0.142834E+09 | 0.253159E+10 | 0.00 | 0.00 |
September | 0.788479E+10 | 0.431351E+09 | 0.346962E+10 | 0.900548E+09 | 0.256907E+10 | 0.00 | 0.00 |
October | 0.120348E+11 | 0.234330E+10 | 0.616809E+10 | 0.344424E+10 | 0.272386E+10 | 0.00 | 0.00 |
November | 0.126468E+11 | 0.423037E+10 | 0.745575E+10 | 0.492809E+10 | 0.252766E+10 | 0.00 | 0.00 |
December | 0.101419E+11 | 0.581731E+10 | 0.687587E+10 | 0.430861E+10 | 0.256726E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110075E+12 | 0.272811E+11 | 0.548929E+11 | 0.242873E+11 | 0.306056E+11 | 0.00 | 0.00 |
Minimum of Months | 0.715474E+10 | 26630689.84 | 0.233903E+10 | 34676522.71 | 0.229912E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126468E+11 | 0.581731E+10 | 0.745575E+10 | 0.492809E+10 | 0.292050E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.223891E+10 | 0.444391E+10 | 0.197663E+10 | 0.769228E+09 | 0.120740E+10 | 0.00 | 0.00 |
February | 0.274380E+10 | 0.326066E+10 | 0.204159E+10 | 0.752379E+09 | 0.128921E+10 | 0.00 | 0.00 |
March | 0.492895E+10 | 0.228721E+10 | 0.293107E+10 | 0.117165E+10 | 0.175942E+10 | 0.00 | 0.00 |
April | 0.716779E+10 | 0.973714E+09 | 0.344776E+10 | 0.161687E+10 | 0.183089E+10 | 0.00 | 0.00 |
May | 0.833573E+10 | 0.202186E+09 | 0.337353E+10 | 0.143098E+10 | 0.194255E+10 | 0.00 | 0.00 |
June | 0.795689E+10 | 0.144522E+09 | 0.306643E+10 | 0.119108E+10 | 0.187535E+10 | 0.00 | 0.00 |
July | 0.599491E+10 | 74308810.81 | 0.235130E+10 | 0.457328E+09 | 0.189397E+10 | 0.00 | 0.00 |
August | 0.504435E+10 | 0.240846E+09 | 0.215942E+10 | 0.383794E+09 | 0.177562E+10 | 0.00 | 0.00 |
September | 0.493999E+10 | 0.411242E+09 | 0.229719E+10 | 0.674391E+09 | 0.162280E+10 | 0.00 | 0.00 |
October | 0.476122E+10 | 0.175789E+10 | 0.247073E+10 | 0.983839E+09 | 0.148689E+10 | 0.00 | 0.00 |
November | 0.337519E+10 | 0.321309E+10 | 0.216308E+10 | 0.921890E+09 | 0.124119E+10 | 0.00 | 0.00 |
December | 0.213814E+10 | 0.464331E+10 | 0.191266E+10 | 0.729340E+09 | 0.118332E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.596259E+11 | 0.216529E+11 | 0.301914E+11 | 0.110828E+11 | 0.191086E+11 | 0.00 | 0.00 |
Minimum of Months | 0.213814E+10 | 74308810.81 | 0.191266E+10 | 0.383794E+09 | 0.118332E+10 | 0.00 | 0.00 |
Maximum of Months | 0.833573E+10 | 0.464331E+10 | 0.344776E+10 | 0.161687E+10 | 0.194255E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.991539E+09 | 0.539696E+10 | 0.141472E+10 | 0.00 | 0.141472E+10 | 0.00 | 0.00 |
February | 0.160587E+10 | 0.389377E+10 | 0.151526E+10 | 0.00 | 0.151526E+10 | 0.00 | 0.00 |
March | 0.328618E+10 | 0.265291E+10 | 0.202153E+10 | 0.00 | 0.202153E+10 | 0.00 | 0.00 |
April | 0.554272E+10 | 0.902821E+09 | 0.212276E+10 | 7199010.56 | 0.211556E+10 | 0.00 | 0.00 |
May | 0.794227E+10 | 0.171962E+09 | 0.243027E+10 | 68197846.21 | 0.236207E+10 | 0.00 | 0.00 |
June | 0.833439E+10 | 0.126290E+09 | 0.243456E+10 | 90176671.47 | 0.234438E+10 | 0.00 | 0.00 |
July | 0.762631E+10 | 33806089.67 | 0.248107E+10 | 39289245.38 | 0.244178E+10 | 0.00 | 0.00 |
August | 0.644100E+10 | 0.110652E+09 | 0.227769E+10 | 7098551.23 | 0.227060E+10 | 0.00 | 0.00 |
September | 0.485685E+10 | 0.376144E+09 | 0.196402E+10 | 137909.51 | 0.196388E+10 | 0.00 | 0.00 |
October | 0.365947E+10 | 0.208918E+10 | 0.175819E+10 | 0.00 | 0.175819E+10 | 0.00 | 0.00 |
November | 0.196111E+10 | 0.379444E+10 | 0.144117E+10 | 0.00 | 0.144117E+10 | 0.00 | 0.00 |
December | 0.107997E+10 | 0.530662E+10 | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.533277E+11 | 0.248556E+11 | 0.232413E+11 | 0.212099E+09 | 0.230292E+11 | 0.00 | 0.00 |
Minimum of Months | 0.991539E+09 | 33806089.67 | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.00 | 0.00 |
Maximum of Months | 0.833439E+10 | 0.539696E+10 | 0.248107E+10 | 90176671.47 | 0.244178E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.217386E+10 | 0.343519E+10 | 0.202038E+10 | 0.810954E+09 | 0.120943E+10 | 0.00 | 0.00 |
February | 0.296037E+10 | 0.253593E+10 | 0.221698E+10 | 0.915271E+09 | 0.130170E+10 | 0.00 | 0.00 |
March | 0.503137E+10 | 0.176746E+10 | 0.299424E+10 | 0.123592E+10 | 0.175832E+10 | 0.00 | 0.00 |
April | 0.733284E+10 | 0.658729E+09 | 0.344746E+10 | 0.160738E+10 | 0.184008E+10 | 0.00 | 0.00 |
May | 0.865183E+10 | 0.131054E+09 | 0.350635E+10 | 0.155453E+10 | 0.195183E+10 | 0.00 | 0.00 |
June | 0.758324E+10 | 91397932.78 | 0.276165E+10 | 0.916315E+09 | 0.184534E+10 | 0.00 | 0.00 |
July | 0.640553E+10 | 21656199.26 | 0.239847E+10 | 0.506493E+09 | 0.189198E+10 | 0.00 | 0.00 |
August | 0.542073E+10 | 80287966.58 | 0.216112E+10 | 0.376086E+09 | 0.178503E+10 | 0.00 | 0.00 |
September | 0.488499E+10 | 0.279582E+09 | 0.223443E+10 | 0.623127E+09 | 0.161130E+10 | 0.00 | 0.00 |
October | 0.485619E+10 | 0.142832E+10 | 0.252568E+10 | 0.102021E+10 | 0.150547E+10 | 0.00 | 0.00 |
November | 0.331823E+10 | 0.249377E+10 | 0.216714E+10 | 0.930235E+09 | 0.123691E+10 | 0.00 | 0.00 |
December | 0.226622E+10 | 0.345340E+10 | 0.195264E+10 | 0.773649E+09 | 0.117900E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.608854E+11 | 0.163768E+11 | 0.303865E+11 | 0.112702E+11 | 0.191164E+11 | 0.00 | 0.00 |
Minimum of Months | 0.217386E+10 | 21656199.26 | 0.195264E+10 | 0.376086E+09 | 0.117900E+10 | 0.00 | 0.00 |
Maximum of Months | 0.865183E+10 | 0.345340E+10 | 0.350635E+10 | 0.160738E+10 | 0.195183E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.914671E+10 | 0.556077E+10 | 0.643411E+10 | 0.390953E+10 | 0.252458E+10 | 0.00 | 0.00 |
February | 0.855126E+10 | 0.413717E+10 | 0.552585E+10 | 0.306921E+10 | 0.245664E+10 | 0.00 | 0.00 |
March | 0.954376E+10 | 0.289733E+10 | 0.523096E+10 | 0.231047E+10 | 0.292049E+10 | 0.00 | 0.00 |
April | 0.875275E+10 | 0.103640E+10 | 0.355572E+10 | 0.100353E+10 | 0.255218E+10 | 0.00 | 0.00 |
May | 0.848548E+10 | 0.173370E+09 | 0.264227E+10 | 0.195599E+09 | 0.244667E+10 | 0.00 | 0.00 |
June | 0.814220E+10 | 0.125367E+09 | 0.233902E+10 | 39914814.84 | 0.229911E+10 | 0.00 | 0.00 |
July | 0.774390E+10 | 30141267.61 | 0.252115E+10 | 34676399.57 | 0.248648E+10 | 0.00 | 0.00 |
August | 0.727232E+10 | 0.116797E+09 | 0.267441E+10 | 0.142834E+09 | 0.253158E+10 | 0.00 | 0.00 |
September | 0.786166E+10 | 0.453127E+09 | 0.346961E+10 | 0.900544E+09 | 0.256906E+10 | 0.00 | 0.00 |
October | 0.119733E+11 | 0.238334E+10 | 0.616807E+10 | 0.344423E+10 | 0.272385E+10 | 0.00 | 0.00 |
November | 0.125881E+11 | 0.416735E+10 | 0.745572E+10 | 0.492808E+10 | 0.252765E+10 | 0.00 | 0.00 |
December | 0.101521E+11 | 0.559128E+10 | 0.687585E+10 | 0.430860E+10 | 0.256725E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110213E+12 | 0.266725E+11 | 0.548927E+11 | 0.242872E+11 | 0.306055E+11 | 0.00 | 0.00 |
Minimum of Months | 0.727232E+10 | 30141267.61 | 0.233902E+10 | 34676399.57 | 0.229911E+10 | 0.00 | 0.00 |
Maximum of Months | 0.125881E+11 | 0.559128E+10 | 0.745572E+10 | 0.492808E+10 | 0.292049E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.239835E+10 | 0.383631E+10 | 0.197662E+10 | 0.769225E+09 | 0.120739E+10 | 0.00 | 0.00 |
February | 0.287174E+10 | 0.282016E+10 | 0.204158E+10 | 0.752376E+09 | 0.128920E+10 | 0.00 | 0.00 |
March | 0.504037E+10 | 0.199175E+10 | 0.293106E+10 | 0.117165E+10 | 0.175941E+10 | 0.00 | 0.00 |
April | 0.734841E+10 | 0.776269E+09 | 0.344774E+10 | 0.161686E+10 | 0.183088E+10 | 0.00 | 0.00 |
May | 0.841657E+10 | 0.173809E+09 | 0.337351E+10 | 0.143098E+10 | 0.194254E+10 | 0.00 | 0.00 |
June | 0.810747E+10 | 0.114762E+09 | 0.306642E+10 | 0.119108E+10 | 0.187534E+10 | 0.00 | 0.00 |
July | 0.623298E+10 | 34817138.38 | 0.235129E+10 | 0.457326E+09 | 0.189396E+10 | 0.00 | 0.00 |
August | 0.536840E+10 | 0.104129E+09 | 0.215941E+10 | 0.383793E+09 | 0.177562E+10 | 0.00 | 0.00 |
September | 0.500341E+10 | 0.341606E+09 | 0.229718E+10 | 0.674388E+09 | 0.162280E+10 | 0.00 | 0.00 |
October | 0.484636E+10 | 0.158106E+10 | 0.247072E+10 | 0.983835E+09 | 0.148688E+10 | 0.00 | 0.00 |
November | 0.351759E+10 | 0.277275E+10 | 0.216307E+10 | 0.921886E+09 | 0.124118E+10 | 0.00 | 0.00 |
December | 0.238610E+10 | 0.377970E+10 | 0.191265E+10 | 0.729337E+09 | 0.118331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.615377E+11 | 0.183271E+11 | 0.301912E+11 | 0.110827E+11 | 0.191085E+11 | 0.00 | 0.00 |
Minimum of Months | 0.238610E+10 | 34817138.38 | 0.191265E+10 | 0.383793E+09 | 0.118331E+10 | 0.00 | 0.00 |
Maximum of Months | 0.841657E+10 | 0.383631E+10 | 0.344774E+10 | 0.161686E+10 | 0.194254E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111871E+10 | 0.490064E+10 | 0.141472E+10 | 0.00 | 0.141472E+10 | 0.00 | 0.00 |
February | 0.168486E+10 | 0.362993E+10 | 0.151526E+10 | 0.00 | 0.151526E+10 | 0.00 | 0.00 |
March | 0.327457E+10 | 0.256954E+10 | 0.202153E+10 | 0.00 | 0.202153E+10 | 0.00 | 0.00 |
April | 0.545403E+10 | 0.919260E+09 | 0.212276E+10 | 7199010.56 | 0.211556E+10 | 0.00 | 0.00 |
May | 0.781138E+10 | 0.193877E+09 | 0.243027E+10 | 68197846.21 | 0.236207E+10 | 0.00 | 0.00 |
June | 0.820090E+10 | 0.137047E+09 | 0.243456E+10 | 90176671.47 | 0.234438E+10 | 0.00 | 0.00 |
July | 0.747540E+10 | 36795893.53 | 0.248107E+10 | 39289245.38 | 0.244178E+10 | 0.00 | 0.00 |
August | 0.631755E+10 | 0.121599E+09 | 0.227769E+10 | 7098551.23 | 0.227060E+10 | 0.00 | 0.00 |
September | 0.477841E+10 | 0.401901E+09 | 0.196402E+10 | 137909.51 | 0.196388E+10 | 0.00 | 0.00 |
October | 0.362703E+10 | 0.204824E+10 | 0.175819E+10 | 0.00 | 0.175819E+10 | 0.00 | 0.00 |
November | 0.202517E+10 | 0.356913E+10 | 0.144117E+10 | 0.00 | 0.144117E+10 | 0.00 | 0.00 |
December | 0.122747E+10 | 0.483699E+10 | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.529955E+11 | 0.233650E+11 | 0.232413E+11 | 0.212099E+09 | 0.230292E+11 | 0.00 | 0.00 |
Minimum of Months | 0.111871E+10 | 36795893.53 | 0.138008E+10 | 0.00 | 0.138008E+10 | 0.00 | 0.00 |
Maximum of Months | 0.820090E+10 | 0.490064E+10 | 0.248107E+10 | 90176671.47 | 0.244178E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.233036E+10 | 0.312729E+10 | 0.202038E+10 | 0.810954E+09 | 0.120943E+10 | 0.00 | 0.00 |
February | 0.303695E+10 | 0.238730E+10 | 0.221698E+10 | 0.915271E+09 | 0.130170E+10 | 0.00 | 0.00 |
March | 0.504104E+10 | 0.172341E+10 | 0.299424E+10 | 0.123592E+10 | 0.175832E+10 | 0.00 | 0.00 |
April | 0.729548E+10 | 0.666435E+09 | 0.344746E+10 | 0.160738E+10 | 0.184008E+10 | 0.00 | 0.00 |
May | 0.858662E+10 | 0.143839E+09 | 0.350635E+10 | 0.155453E+10 | 0.195183E+10 | 0.00 | 0.00 |
June | 0.751755E+10 | 97722837.92 | 0.276165E+10 | 0.916315E+09 | 0.184534E+10 | 0.00 | 0.00 |
July | 0.632974E+10 | 23059416.11 | 0.239847E+10 | 0.506493E+09 | 0.189198E+10 | 0.00 | 0.00 |
August | 0.536389E+10 | 87014305.05 | 0.216112E+10 | 0.376086E+09 | 0.178503E+10 | 0.00 | 0.00 |
September | 0.485440E+10 | 0.294367E+09 | 0.223443E+10 | 0.623127E+09 | 0.161130E+10 | 0.00 | 0.00 |
October | 0.485533E+10 | 0.140397E+10 | 0.252568E+10 | 0.102021E+10 | 0.150547E+10 | 0.00 | 0.00 |
November | 0.337955E+10 | 0.237191E+10 | 0.216714E+10 | 0.930235E+09 | 0.123691E+10 | 0.00 | 0.00 |
December | 0.241440E+10 | 0.317657E+10 | 0.195264E+10 | 0.773649E+09 | 0.117900E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.610053E+11 | 0.155029E+11 | 0.303865E+11 | 0.112702E+11 | 0.191164E+11 | 0.00 | 0.00 |
Minimum of Months | 0.233036E+10 | 23059416.11 | 0.195264E+10 | 0.376086E+09 | 0.117900E+10 | 0.00 | 0.00 |
Maximum of Months | 0.858662E+10 | 0.317657E+10 | 0.350635E+10 | 0.160738E+10 | 0.195183E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.930053E+10 | 0.511023E+10 | 0.643411E+10 | 0.390953E+10 | 0.252458E+10 | 0.00 | 0.00 |
February | 0.860652E+10 | 0.391016E+10 | 0.552585E+10 | 0.306921E+10 | 0.245664E+10 | 0.00 | 0.00 |
March | 0.951233E+10 | 0.282123E+10 | 0.523096E+10 | 0.231047E+10 | 0.292049E+10 | 0.00 | 0.00 |
April | 0.866497E+10 | 0.104975E+10 | 0.355572E+10 | 0.100353E+10 | 0.255218E+10 | 0.00 | 0.00 |
May | 0.835542E+10 | 0.194035E+09 | 0.264227E+10 | 0.195599E+09 | 0.244667E+10 | 0.00 | 0.00 |
June | 0.800778E+10 | 0.136576E+09 | 0.233902E+10 | 39914814.84 | 0.229911E+10 | 0.00 | 0.00 |
July | 0.759238E+10 | 32676515.80 | 0.252115E+10 | 34676399.57 | 0.248648E+10 | 0.00 | 0.00 |
August | 0.715048E+10 | 0.128072E+09 | 0.267441E+10 | 0.142834E+09 | 0.253158E+10 | 0.00 | 0.00 |
September | 0.778200E+10 | 0.478380E+09 | 0.346961E+10 | 0.900544E+09 | 0.256906E+10 | 0.00 | 0.00 |
October | 0.119329E+11 | 0.234373E+10 | 0.616807E+10 | 0.344423E+10 | 0.272385E+10 | 0.00 | 0.00 |
November | 0.126128E+11 | 0.398675E+10 | 0.745572E+10 | 0.492808E+10 | 0.252765E+10 | 0.00 | 0.00 |
December | 0.102977E+11 | 0.520340E+10 | 0.687585E+10 | 0.430860E+10 | 0.256725E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.109816E+12 | 0.253950E+11 | 0.548927E+11 | 0.242872E+11 | 0.306055E+11 | 0.00 | 0.00 |
Minimum of Months | 0.715048E+10 | 32676515.80 | 0.233902E+10 | 34676399.57 | 0.229911E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126128E+11 | 0.520340E+10 | 0.745572E+10 | 0.492808E+10 | 0.292049E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246359E+10 | 0.354437E+10 | 0.197662E+10 | 0.769225E+09 | 0.120739E+10 | 0.00 | 0.00 |
February | 0.289865E+10 | 0.266737E+10 | 0.204158E+10 | 0.752376E+09 | 0.128920E+10 | 0.00 | 0.00 |
March | 0.501585E+10 | 0.193896E+10 | 0.293106E+10 | 0.117165E+10 | 0.175941E+10 | 0.00 | 0.00 |
April | 0.729148E+10 | 0.780429E+09 | 0.344774E+10 | 0.161686E+10 | 0.183088E+10 | 0.00 | 0.00 |
May | 0.833957E+10 | 0.185655E+09 | 0.337351E+10 | 0.143098E+10 | 0.194254E+10 | 0.00 | 0.00 |
June | 0.802560E+10 | 0.120692E+09 | 0.306642E+10 | 0.119108E+10 | 0.187534E+10 | 0.00 | 0.00 |
July | 0.614420E+10 | 37564733.92 | 0.235129E+10 | 0.457326E+09 | 0.189396E+10 | 0.00 | 0.00 |
August | 0.530059E+10 | 0.112251E+09 | 0.215941E+10 | 0.383793E+09 | 0.177562E+10 | 0.00 | 0.00 |
September | 0.495486E+10 | 0.356421E+09 | 0.229718E+10 | 0.674388E+09 | 0.162280E+10 | 0.00 | 0.00 |
October | 0.481995E+10 | 0.155309E+10 | 0.247072E+10 | 0.983835E+09 | 0.148688E+10 | 0.00 | 0.00 |
November | 0.353490E+10 | 0.264423E+10 | 0.216307E+10 | 0.921886E+09 | 0.124118E+10 | 0.00 | 0.00 |
December | 0.245837E+10 | 0.351374E+10 | 0.191265E+10 | 0.729337E+09 | 0.118331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.612476E+11 | 0.174548E+11 | 0.301912E+11 | 0.110827E+11 | 0.191085E+11 | 0.00 | 0.00 |
Minimum of Months | 0.245837E+10 | 37564733.92 | 0.191265E+10 | 0.383793E+09 | 0.118331E+10 | 0.00 | 0.00 |
Maximum of Months | 0.833957E+10 | 0.354437E+10 | 0.344774E+10 | 0.161686E+10 | 0.194254E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.312949E+11 | -0.302736E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102131E+10 | 58.97 | 0.00 | 0.00 |
February | 0.278510E+11 | -0.269281E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -922981889.2 | 58.97 | 0.00 | 0.00 |
March | 0.305692E+11 | -0.295445E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102472E+10 | 58.98 | 0.00 | 0.00 |
April | 0.250271E+11 | -0.240391E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987997024.2 | 58.97 | 0.00 | 0.00 |
May | 0.236954E+11 | -0.226731E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102228E+10 | 58.97 | 0.00 | 0.00 |
June | 0.211384E+11 | -0.201485E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989825642.0 | 58.96 | 0.00 | 0.00 |
July | 0.192751E+11 | -0.182583E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101680E+10 | 58.95 | 0.00 | 0.00 |
August | 0.217349E+11 | -0.207134E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102148E+10 | 58.97 | 0.00 | 0.00 |
September | 0.217883E+11 | -0.208024E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985976621.3 | 58.96 | 0.00 | 0.00 |
October | 0.253239E+11 | -0.243069E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101697E+10 | 58.98 | 0.00 | 0.00 |
November | 0.276747E+11 | -0.266901E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -984528228.1 | 58.97 | 0.00 | 0.00 |
December | 0.297103E+11 | -0.286923E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101801E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.305083E+12 | -0.293070E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120129E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.192751E+11 | -0.302736E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102472E+10 | 58.95 | 0.00 | 0.00 |
Maximum of Months | 0.312949E+11 | -0.182583E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -922981889.2 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5587.00 | 35.39 | 298.33 | 287.33 | 1241.27 | 25.72 | 289.83 | 266.00 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3361.53 | 29.30 | 203.33 | 271.17 | 1099.85 | 21.65 | 213.67 | 243.83 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1746.34 | 20.45 | 79.17 | 323.67 | 946.86 | 21.50 | 247.50 | 291.33 |
April | 379.83 | 0.53 | 0.48 | 01-APR-07:30 | 1185.67 | 18.87 | 9.67 | 328.83 | 700.32 | 20.16 | 180.17 | 296.17 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:10 | 1006.26 | 18.69 | 0.00 | 349.83 | 590.02 | 20.07 | 144.67 | 309.67 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 995.79 | 18.34 | 0.00 | 334.33 | 570.38 | 19.69 | 136.17 | 292.00 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1113.23 | 18.84 | 0.33 | 333.17 | 578.71 | 20.10 | 146.33 | 281.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1250.72 | 18.83 | 18.50 | 321.67 | 627.42 | 20.07 | 172.33 | 271.00 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:19 | 1523.47 | 19.57 | 66.67 | 302.17 | 788.20 | 20.88 | 210.50 | 263.00 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2574.74 | 21.53 | 109.17 | 305.33 | 1062.27 | 21.12 | 226.50 | 278.33 |
November | 317.83 | 0.51 | 0.48 | 01-NOV-07:19 | 7555.70 | 36.61 | 310.50 | 287.83 | 1296.96 | 23.62 | 260.83 | 265.00 |
December | 315.50 | 0.50 | 0.48 | 01-DEC-07:30 | 5899.83 | 36.71 | 308.83 | 286.00 | 1459.62 | 27.89 | 308.67 | 278.67 |
Annual Sum or Average | 4237.50 | 0.52 | 2656.38 | 23.86 | 1404.50 | 3731.33 | 889.30 | 21.71 | 2537.17 | 3336.33 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 995.79 | 18.34 | 0.00 | 271.17 | 570.38 | 19.69 | 136.17 | 243.83 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 7555.70 | 36.71 | 310.50 | 349.83 | 1459.62 | 27.89 | 308.67 | 309.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1654.05 | 23.82 | 107.17 | 267.67 | 872.87 | 23.89 | 165.83 | 223.67 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2049.04 | 23.96 | 100.33 | 257.50 | 1081.03 | 24.07 | 154.83 | 219.83 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:30 | 1971.01 | 23.44 | 101.50 | 319.17 | 1019.94 | 23.69 | 165.17 | 287.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-06:49 | 2387.77 | 22.87 | 110.33 | 328.00 | 1256.65 | 23.21 | 118.00 | 300.00 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2476.59 | 23.26 | 128.50 | 357.33 | 965.45 | 22.42 | 123.50 | 323.50 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 1978.26 | 21.99 | 108.00 | 337.83 | 831.36 | 21.50 | 124.83 | 299.67 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1637.28 | 21.95 | 102.00 | 337.50 | 731.31 | 21.54 | 125.50 | 286.67 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1499.77 | 21.42 | 98.33 | 322.83 | 692.23 | 21.07 | 133.50 | 267.83 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1674.99 | 22.42 | 90.50 | 298.00 | 848.32 | 22.83 | 152.17 | 257.67 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-06:49 | 1842.26 | 23.15 | 102.67 | 297.50 | 932.82 | 23.23 | 161.67 | 265.00 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-07:10 | 1663.43 | 23.57 | 94.83 | 268.67 | 846.23 | 23.55 | 154.50 | 238.83 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-07:30 | 1729.72 | 24.45 | 112.50 | 262.33 | 919.78 | 24.44 | 169.17 | 226.83 |
Annual Sum or Average | 4237.50 | 0.52 | 1892.20 | 22.97 | 1256.67 | 3654.33 | 915.77 | 22.88 | 1748.67 | 3196.67 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1499.77 | 21.42 | 90.50 | 257.50 | 692.23 | 21.07 | 118.00 | 219.83 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2476.59 | 24.45 | 128.50 | 357.33 | 1256.65 | 24.44 | 169.17 | 323.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:20 | 554.70 | 16.48 | 0.00 | 248.17 | 340.77 | 18.00 | 0.00 | 167.50 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-08:50 | 639.90 | 17.35 | 0.00 | 249.00 | 392.01 | 18.81 | 0.00 | 183.33 |
March | 364.50 | 0.52 | 0.48 | 01-MAR-08:20 | 756.72 | 18.45 | 0.00 | 313.67 | 462.82 | 19.83 | 0.33 | 262.83 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 817.80 | 18.47 | 0.00 | 332.67 | 508.17 | 19.78 | 48.83 | 298.50 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:30 | 970.86 | 19.17 | 6.17 | 365.50 | 570.02 | 20.49 | 149.67 | 336.33 |
June | 386.67 | 0.51 | 0.48 | 01-JUN-07:19 | 1072.99 | 20.78 | 64.00 | 348.33 | 599.84 | 20.33 | 170.67 | 311.17 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:40 | 1086.46 | 20.41 | 40.33 | 345.00 | 568.04 | 20.99 | 144.17 | 297.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 971.60 | 18.52 | 0.00 | 325.67 | 507.87 | 19.72 | 90.17 | 271.33 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 848.14 | 18.39 | 0.00 | 299.17 | 471.66 | 19.64 | 35.33 | 245.17 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:40 | 671.39 | 17.30 | 0.00 | 288.50 | 420.34 | 18.78 | 0.00 | 235.50 |
November | 317.83 | 0.54 | 0.48 | 01-NOV-08:09 | 572.50 | 16.88 | 0.00 | 252.50 | 371.70 | 18.55 | 0.00 | 191.67 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-08:39 | 546.82 | 16.57 | 0.00 | 243.33 | 338.97 | 18.16 | 0.00 | 165.00 |
Annual Sum or Average | 4237.50 | 0.52 | 807.41 | 18.33 | 110.50 | 3611.50 | 469.96 | 19.50 | 639.17 | 2965.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 546.82 | 16.48 | 0.00 | 243.33 | 338.97 | 18.00 | 0.00 | 165.00 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1086.46 | 20.78 | 64.00 | 365.50 | 599.84 | 20.99 | 170.67 | 336.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:20 | 1657.27 | 23.60 | 104.33 | 266.50 | 860.01 | 23.62 | 165.83 | 223.50 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-09:09 | 1962.25 | 23.60 | 103.67 | 262.00 | 788.60 | 22.39 | 150.00 | 223.17 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:30 | 1923.06 | 23.35 | 101.17 | 319.83 | 990.90 | 23.59 | 174.83 | 288.67 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:00 | 2188.74 | 21.13 | 84.50 | 332.00 | 1142.84 | 21.60 | 90.50 | 302.17 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:19 | 2100.92 | 17.39 | 0.00 | 352.00 | 1089.87 | 19.52 | 80.67 | 322.17 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:00 | 2089.78 | 17.41 | 0.00 | 337.67 | 865.07 | 19.36 | 87.83 | 302.50 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-07:30 | 1585.75 | 18.11 | 3.67 | 336.17 | 722.72 | 19.68 | 97.00 | 287.67 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1479.98 | 19.38 | 54.17 | 321.83 | 736.93 | 19.55 | 97.17 | 272.50 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-08:09 | 1644.12 | 21.62 | 81.00 | 301.33 | 827.96 | 21.98 | 150.83 | 257.67 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:00 | 1954.50 | 23.25 | 105.00 | 293.67 | 986.71 | 23.34 | 149.83 | 263.33 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-08:20 | 1713.61 | 23.69 | 97.17 | 270.00 | 862.85 | 23.66 | 155.83 | 240.33 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-08:39 | 1510.17 | 23.76 | 101.00 | 268.83 | 781.18 | 23.73 | 170.00 | 231.67 |
Annual Sum or Average | 4237.50 | 0.52 | 1826.18 | 21.16 | 835.67 | 3661.83 | 892.98 | 21.71 | 1570.33 | 3215.33 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1479.98 | 17.39 | 0.00 | 262.00 | 722.72 | 19.36 | 80.67 | 223.17 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2188.74 | 23.76 | 105.00 | 352.00 | 1142.84 | 23.73 | 174.83 | 322.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5621.98 | 34.87 | 296.67 | 287.33 | 1323.48 | 21.54 | 84.50 | 268.33 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3400.83 | 26.56 | 195.33 | 271.33 | 1177.88 | 16.80 | 0.00 | 246.83 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1780.18 | 14.28 | 7.50 | 323.67 | 1013.47 | 17.40 | 0.00 | 294.67 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 1213.00 | 13.17 | 0.00 | 329.17 | 749.46 | 16.56 | 0.00 | 299.67 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:10 | 1025.74 | 12.79 | 0.00 | 350.17 | 629.34 | 16.24 | 0.00 | 315.17 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1012.82 | 12.35 | 0.00 | 334.67 | 607.46 | 15.73 | 0.00 | 296.17 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1125.18 | 12.41 | 0.00 | 333.83 | 614.53 | 15.74 | 0.00 | 287.00 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1260.65 | 12.37 | 0.00 | 322.00 | 665.37 | 15.63 | 0.00 | 277.00 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-07:19 | 1541.26 | 13.13 | 0.00 | 302.67 | 838.23 | 16.51 | 0.00 | 267.50 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2623.77 | 15.66 | 42.67 | 307.67 | 1141.33 | 16.87 | 10.00 | 282.00 |
November | 317.83 | 0.50 | 0.48 | 01-NOV-07:19 | 7610.53 | 36.19 | 310.33 | 288.00 | 1400.77 | 20.73 | 74.33 | 272.67 |
December | 315.50 | 0.50 | 0.48 | 01-DEC-07:30 | 5935.37 | 36.29 | 308.00 | 286.50 | 1547.51 | 24.15 | 123.17 | 279.67 |
Annual Sum or Average | 4237.50 | 0.51 | 2684.78 | 19.26 | 1160.50 | 3737.00 | 949.80 | 17.66 | 292.00 | 3386.67 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 1012.82 | 12.35 | 0.00 | 271.33 | 607.46 | 15.63 | 0.00 | 246.83 | |
Maximum of Months | 406.00 | 0.52 | 0.48 | 7610.53 | 36.29 | 310.33 | 350.17 | 1547.51 | 24.15 | 123.17 | 315.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1680.21 | 21.38 | 106.83 | 269.00 | 910.14 | 22.03 | 77.33 | 228.33 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2085.42 | 21.32 | 100.00 | 258.67 | 1124.62 | 22.06 | 74.00 | 226.33 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:30 | 2019.42 | 20.47 | 101.50 | 320.17 | 1070.72 | 21.36 | 70.67 | 291.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-06:49 | 2415.04 | 19.97 | 110.17 | 328.83 | 1311.20 | 20.89 | 81.17 | 303.67 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2495.02 | 19.31 | 117.00 | 357.50 | 1020.01 | 19.76 | 66.50 | 327.33 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 2006.53 | 18.92 | 107.17 | 338.83 | 878.60 | 18.86 | 51.33 | 304.00 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1658.37 | 18.33 | 96.33 | 338.83 | 776.08 | 18.92 | 48.17 | 294.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1520.80 | 18.31 | 97.67 | 324.00 | 788.56 | 19.50 | 69.00 | 274.83 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1707.75 | 19.41 | 90.00 | 298.50 | 889.48 | 20.50 | 64.50 | 263.33 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-06:49 | 1881.16 | 20.26 | 100.83 | 298.17 | 978.22 | 21.14 | 72.17 | 268.00 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1687.61 | 20.02 | 87.83 | 269.67 | 888.77 | 21.58 | 64.83 | 242.50 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-07:30 | 1754.95 | 22.08 | 112.50 | 263.83 | 956.81 | 22.70 | 81.67 | 231.83 |
Annual Sum or Average | 4237.50 | 0.52 | 1921.01 | 19.90 | 1227.83 | 3666.00 | 966.00 | 20.68 | 821.33 | 3255.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1520.80 | 18.31 | 87.83 | 258.67 | 776.08 | 18.86 | 48.17 | 226.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2495.02 | 22.08 | 117.00 | 357.50 | 1311.20 | 22.70 | 81.67 | 327.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:09 | 563.11 | 10.87 | 0.00 | 248.83 | 362.60 | 14.39 | 0.00 | 179.50 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-08:50 | 650.48 | 11.78 | 0.00 | 249.17 | 417.37 | 15.28 | 0.00 | 193.17 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:09 | 770.61 | 13.10 | 0.00 | 314.67 | 493.14 | 16.57 | 0.00 | 270.33 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 835.40 | 13.26 | 0.00 | 332.83 | 542.33 | 16.67 | 0.00 | 304.83 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:30 | 990.58 | 13.32 | 1.17 | 365.83 | 607.96 | 16.86 | 1.17 | 339.33 |
June | 386.67 | 0.51 | 0.48 | 01-JUN-07:19 | 1092.44 | 15.58 | 39.17 | 348.33 | 641.54 | 18.75 | 40.50 | 317.50 |
July | 379.83 | 0.50 | 0.48 | 01-JUL-06:30 | 1100.51 | 14.66 | 29.17 | 345.17 | 603.84 | 17.82 | 29.67 | 303.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 983.79 | 12.28 | 0.00 | 325.67 | 539.16 | 15.55 | 0.00 | 279.00 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:30 | 860.48 | 12.56 | 0.00 | 299.33 | 501.37 | 15.88 | 0.00 | 252.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:30 | 683.34 | 11.88 | 0.00 | 289.00 | 447.84 | 15.32 | 0.00 | 242.00 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-08:09 | 582.02 | 11.29 | 0.00 | 253.33 | 395.97 | 14.95 | 0.00 | 203.33 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-08:30 | 554.92 | 10.92 | 0.00 | 244.50 | 360.64 | 14.52 | 0.00 | 178.00 |
Annual Sum or Average | 4237.50 | 0.52 | 820.86 | 12.73 | 69.50 | 3616.67 | 500.59 | 16.14 | 71.33 | 3062.67 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 554.92 | 10.87 | 0.00 | 244.50 | 360.64 | 14.39 | 0.00 | 178.00 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1100.51 | 15.58 | 39.17 | 365.83 | 641.54 | 18.75 | 40.50 | 339.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:09 | 1683.35 | 21.17 | 104.00 | 267.50 | 897.15 | 21.75 | 74.33 | 227.33 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:00 | 1994.86 | 21.06 | 103.17 | 263.00 | 829.67 | 20.10 | 48.00 | 228.17 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1969.55 | 20.39 | 101.17 | 320.00 | 1040.65 | 21.25 | 69.33 | 292.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:49 | 2215.82 | 17.89 | 84.50 | 332.50 | 1196.61 | 18.98 | 54.67 | 305.33 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-07:19 | 2125.59 | 12.79 | 0.00 | 352.83 | 1143.43 | 16.23 | 0.00 | 326.67 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:49 | 2120.42 | 12.88 | 0.00 | 338.00 | 916.29 | 16.11 | 0.00 | 306.83 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-07:19 | 1607.93 | 13.62 | 3.50 | 337.17 | 762.81 | 16.49 | 0.00 | 293.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1501.09 | 15.64 | 52.17 | 323.00 | 774.40 | 16.45 | 4.67 | 277.83 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-08:09 | 1676.84 | 18.44 | 80.17 | 302.33 | 869.67 | 19.48 | 52.00 | 263.00 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:49 | 1994.05 | 20.60 | 104.67 | 294.50 | 1031.45 | 21.29 | 74.17 | 267.33 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-08:20 | 1742.92 | 20.93 | 95.83 | 270.50 | 905.10 | 21.73 | 67.17 | 244.67 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-08:30 | 1524.19 | 20.16 | 90.17 | 269.17 | 817.76 | 21.90 | 70.00 | 236.50 |
Annual Sum or Average | 4237.50 | 0.52 | 1855.06 | 17.72 | 819.33 | 3670.50 | 937.47 | 19.15 | 514.33 | 3269.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1501.09 | 12.79 | 0.00 | 263.00 | 762.81 | 16.11 | 0.00 | 227.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2215.82 | 21.17 | 104.67 | 352.83 | 1196.61 | 21.90 | 74.33 | 326.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.51 | 0.48 | 01-JAN-07:00 | 5624.00 | 34.86 | 296.67 | 287.33 | 1325.45 | 21.53 | 84.50 | 268.33 |
February | 303.83 | 0.51 | 0.48 | 01-FEB-08:09 | 3403.50 | 26.55 | 195.33 | 271.33 | 1179.69 | 16.78 | 0.00 | 246.83 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:49 | 1782.61 | 14.25 | 7.50 | 323.67 | 1014.98 | 17.39 | 0.00 | 294.83 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 1214.45 | 13.14 | 0.00 | 329.17 | 750.44 | 16.55 | 0.00 | 299.67 |
May | 406.00 | 0.52 | 0.48 | 01-MAY-07:10 | 1026.96 | 12.76 | 0.00 | 350.17 | 630.18 | 16.22 | 0.00 | 315.17 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:30 | 1014.13 | 12.32 | 0.00 | 334.67 | 608.33 | 15.71 | 0.00 | 296.17 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:00 | 1127.12 | 12.38 | 0.00 | 333.83 | 615.60 | 15.72 | 0.00 | 287.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:10 | 1262.97 | 12.35 | 0.00 | 322.33 | 666.63 | 15.61 | 0.00 | 277.33 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-07:19 | 1543.85 | 13.11 | 0.00 | 302.67 | 839.72 | 16.50 | 0.00 | 267.67 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-07:10 | 2626.21 | 15.64 | 42.67 | 307.67 | 1142.95 | 16.85 | 10.00 | 282.17 |
November | 317.83 | 0.50 | 0.48 | 01-NOV-07:19 | 7612.61 | 36.19 | 310.33 | 288.00 | 1402.62 | 20.72 | 74.33 | 272.67 |
December | 315.50 | 0.50 | 0.48 | 01-DEC-07:30 | 5937.38 | 36.28 | 308.00 | 286.50 | 1549.59 | 24.14 | 123.17 | 279.67 |
Annual Sum or Average | 4237.50 | 0.51 | 2686.79 | 19.24 | 1160.50 | 3737.33 | 951.21 | 17.65 | 292.00 | 3387.83 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 1014.13 | 12.32 | 0.00 | 271.33 | 608.33 | 15.61 | 0.00 | 246.83 | |
Maximum of Months | 406.00 | 0.52 | 0.48 | 7612.61 | 36.28 | 310.33 | 350.17 | 1549.59 | 24.14 | 123.17 | 315.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-07:49 | 1681.15 | 21.35 | 106.83 | 269.00 | 911.10 | 22.02 | 77.33 | 228.50 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2086.60 | 21.29 | 100.00 | 258.67 | 1125.72 | 22.05 | 74.00 | 226.33 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-07:30 | 2020.70 | 20.44 | 101.50 | 320.17 | 1071.92 | 21.34 | 70.67 | 291.17 |
April | 379.83 | 0.52 | 0.48 | 01-APR-06:49 | 2416.28 | 19.95 | 110.17 | 328.83 | 1312.36 | 20.87 | 81.17 | 304.00 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:10 | 2496.37 | 19.28 | 117.00 | 357.83 | 1021.17 | 19.75 | 66.50 | 327.33 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-06:00 | 2008.17 | 18.89 | 107.17 | 338.83 | 879.79 | 18.84 | 51.33 | 304.00 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-06:10 | 1660.51 | 18.31 | 96.33 | 338.83 | 777.38 | 18.91 | 48.17 | 294.33 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:30 | 1522.99 | 18.28 | 97.50 | 324.17 | 789.87 | 19.49 | 69.00 | 275.17 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-06:49 | 1709.62 | 19.39 | 90.00 | 298.50 | 890.79 | 20.48 | 64.50 | 263.33 |
October | 347.33 | 0.52 | 0.48 | 01-OCT-06:49 | 1882.26 | 20.23 | 100.83 | 298.17 | 979.31 | 21.13 | 72.17 | 268.00 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1688.45 | 19.99 | 87.83 | 269.67 | 889.71 | 21.57 | 64.83 | 242.83 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-07:30 | 1755.86 | 22.05 | 112.50 | 264.00 | 957.76 | 22.69 | 81.67 | 232.50 |
Annual Sum or Average | 4237.50 | 0.52 | 1922.43 | 19.88 | 1227.67 | 3666.67 | 967.15 | 20.67 | 821.33 | 3257.50 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1522.99 | 18.28 | 87.83 | 258.67 | 777.38 | 18.84 | 48.17 | 226.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2496.37 | 22.05 | 117.00 | 357.83 | 1312.36 | 22.69 | 81.67 | 327.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.55 | 0.48 | 01-JAN-09:09 | 563.55 | 10.84 | 0.00 | 249.00 | 363.04 | 14.37 | 0.00 | 179.83 |
February | 303.83 | 0.53 | 0.48 | 01-FEB-08:50 | 651.03 | 11.75 | 0.00 | 249.33 | 417.89 | 15.27 | 0.00 | 193.33 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:09 | 771.28 | 13.07 | 0.00 | 314.83 | 493.75 | 16.56 | 0.00 | 270.50 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:19 | 836.09 | 13.23 | 0.00 | 332.83 | 542.96 | 16.65 | 0.00 | 304.83 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-06:30 | 991.60 | 13.29 | 1.17 | 365.83 | 608.75 | 16.84 | 1.17 | 339.67 |
June | 386.67 | 0.51 | 0.48 | 01-JUN-07:19 | 1093.78 | 15.55 | 39.17 | 348.33 | 642.47 | 18.74 | 40.50 | 317.83 |
July | 379.83 | 0.50 | 0.48 | 01-JUL-06:30 | 1102.28 | 14.64 | 29.17 | 345.33 | 604.89 | 17.80 | 29.67 | 303.17 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-06:00 | 985.40 | 12.26 | 0.00 | 325.67 | 540.12 | 15.54 | 0.00 | 279.33 |
September | 344.33 | 0.52 | 0.48 | 01-SEP-07:19 | 861.62 | 12.53 | 0.00 | 299.33 | 502.16 | 15.87 | 0.00 | 252.50 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:30 | 683.85 | 11.85 | 0.00 | 289.17 | 448.37 | 15.31 | 0.00 | 242.17 |
November | 317.83 | 0.53 | 0.48 | 01-NOV-08:09 | 582.32 | 11.25 | 0.00 | 253.33 | 396.38 | 14.93 | 0.00 | 204.17 |
December | 315.50 | 0.54 | 0.48 | 01-DEC-08:30 | 555.32 | 10.89 | 0.00 | 244.67 | 361.08 | 14.51 | 0.00 | 178.33 |
Annual Sum or Average | 4237.50 | 0.52 | 821.76 | 12.70 | 69.50 | 3617.67 | 501.28 | 16.12 | 71.33 | 3065.67 | ||
Minimum of Months | 303.83 | 0.50 | 0.48 | 555.32 | 10.84 | 0.00 | 244.67 | 361.08 | 14.37 | 0.00 | 178.33 | |
Maximum of Months | 406.00 | 0.55 | 0.48 | 1102.28 | 15.55 | 39.17 | 365.83 | 642.47 | 18.74 | 40.50 | 339.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.53 | 0.48 | 01-JAN-09:09 | 1684.31 | 21.14 | 104.00 | 267.83 | 898.11 | 21.74 | 74.33 | 227.33 |
February | 303.83 | 0.52 | 0.48 | 01-FEB-08:00 | 1996.07 | 21.04 | 103.17 | 263.00 | 830.75 | 20.08 | 48.00 | 228.33 |
March | 364.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1970.84 | 20.36 | 101.17 | 320.00 | 1041.84 | 21.24 | 69.33 | 292.33 |
April | 379.83 | 0.52 | 0.48 | 01-APR-07:49 | 2217.04 | 17.86 | 84.50 | 332.50 | 1197.74 | 18.97 | 54.67 | 305.50 |
May | 406.00 | 0.51 | 0.48 | 01-MAY-07:19 | 2126.96 | 12.76 | 0.00 | 352.83 | 1144.61 | 16.21 | 0.00 | 326.67 |
June | 386.67 | 0.52 | 0.48 | 01-JUN-07:49 | 2122.05 | 12.84 | 0.00 | 338.00 | 917.51 | 16.10 | 0.00 | 306.83 |
July | 379.83 | 0.51 | 0.48 | 01-JUL-07:19 | 1610.11 | 13.58 | 3.50 | 337.17 | 764.11 | 16.47 | 0.00 | 293.50 |
August | 372.50 | 0.52 | 0.48 | 01-AUG-07:40 | 1503.29 | 15.61 | 52.00 | 323.00 | 775.71 | 16.44 | 4.67 | 278.00 |
September | 344.33 | 0.51 | 0.48 | 01-SEP-07:00 | 1678.75 | 18.41 | 80.17 | 302.33 | 870.98 | 19.47 | 52.00 | 263.00 |
October | 347.33 | 0.53 | 0.48 | 01-OCT-07:49 | 1995.21 | 20.57 | 104.67 | 294.67 | 1032.53 | 21.27 | 74.17 | 267.33 |
November | 317.83 | 0.52 | 0.48 | 01-NOV-08:20 | 1743.76 | 20.90 | 95.83 | 270.50 | 906.03 | 21.72 | 67.17 | 244.67 |
December | 315.50 | 0.52 | 0.48 | 01-DEC-08:30 | 1525.13 | 20.13 | 90.17 | 269.33 | 818.70 | 21.89 | 70.00 | 236.67 |
Annual Sum or Average | 4237.50 | 0.52 | 1856.49 | 17.69 | 819.17 | 3671.17 | 938.61 | 19.13 | 514.33 | 3270.17 | ||
Minimum of Months | 303.83 | 0.51 | 0.48 | 1503.29 | 12.76 | 0.00 | 263.00 | 764.11 | 16.10 | 0.00 | 227.33 | |
Maximum of Months | 406.00 | 0.53 | 0.48 | 2217.04 | 21.14 | 104.67 | 352.83 | 1197.74 | 21.89 | 74.33 | 326.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.860555E+09 | 11029.28 | 05-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133680E+09 | 6626.89 | 02-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 132.82 | 1.33 | 27-NOV-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180409E+09 | 10018.33 | 23-DEC-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.860555E+09 | 11029.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6810533.42 | 6123.15 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6810533.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6810533.42 | 6123.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113257E+11 | 83079.88 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.199879E+10 | 66083.51 | 02-FEB-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 56623638.90 | 16656.91 | 27-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.332830E+10 | 74278.84 | 21-DEC-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113257E+11 | 83079.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.318224E+09 | 256051.34 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318224E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.318224E+09 | 256051.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.613583E+10 | 183506.21 | 02-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.821489E+09 | 143179.87 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183387E+10 | 180302.80 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.879119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.613583E+10 | 183506.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205893E+10 | 134656.87 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184320E+09 | 106697.69 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.374543E+09 | 85520.05 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205893E+10 | 134656.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.115501E+10 | 182215.43 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154627E+09 | 136977.67 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115199E+09 | 14347.96 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115501E+10 | 182215.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167840E+10 | 132024.35 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123154E+09 | 54211.91 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296825E+09 | 50610.07 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167840E+10 | 132024.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205456E+10 | 9986.89 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.484509E+09 | 8933.38 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 48241383.91 | 5191.98 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.892291E+09 | 9031.18 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205456E+10 | 9986.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135338E+10 | 79854.13 | 02-JAN-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54894596.40 | 5856.16 | 23-DEC-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135338E+10 | 79854.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.201710E+10 | 21930.51 | 03-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.415994E+09 | 21479.38 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 192621.73 | 213.65 | 01-MAR-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53622543.67 | 12538.96 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100090E+10 | 22011.20 | 21-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.201710E+10 | 22011.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.769388E+09 | 15584.38 | 03-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145583E+09 | 15261.56 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10290862.77 | 1363.01 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.353817E+09 | 15598.67 | 23-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.769388E+09 | 15598.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.737179E+09 | 21876.75 | 03-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153931E+09 | 21353.38 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.263016E+09 | 21348.96 | 30-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.737179E+09 | 21876.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.680909E+09 | 16090.86 | 03-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115779E+09 | 15697.86 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1821765.74 | 363.59 | 27-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.267643E+09 | 14818.33 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.680909E+09 | 16090.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.353548E+11 | 0.353113E+11 | 75774.23 | 18-JAN-06:03 | 61498.02 | 0.38 |
February | 0.00 | 0.00 | 0.573693E+11 | 0.572511E+11 | 153177.74 | 25-FEB-06:02 | 105770.06 | 0.52 |
March | 0.00 | 0.00 | 0.118679E+12 | 0.116733E+12 | 187348.84 | 14-MAR-05:02 | 153217.47 | 0.72 |
April | 0.00 | 0.00 | 0.183300E+12 | 0.176337E+12 | 248176.19 | 17-APR-04:22 | 179450.23 | 0.82 |
May | 0.00 | 0.00 | 0.230600E+12 | 0.196219E+12 | 279905.13 | 22-MAY-05:03 | 179432.79 | 0.86 |
June | 0.00 | 0.00 | 0.269042E+12 | 0.200805E+12 | 290518.72 | 26-JUN-05:02 | 175150.12 | 0.87 |
July | 0.00 | 0.00 | 0.304134E+12 | 0.189775E+12 | 307324.94 | 03-JUL-03:02 | 195623.03 | 0.87 |
August | 0.00 | 0.00 | 0.325617E+12 | 0.200303E+12 | 311088.73 | 28-AUG-03:01 | 189296.58 | 0.89 |
September | 0.00 | 0.00 | 0.230672E+12 | 0.146464E+12 | 291531.40 | 05-SEP-05:02 | 175476.48 | 0.81 |
October | 0.00 | 0.00 | 0.150565E+12 | 0.133580E+12 | 244735.97 | 12-OCT-04:12 | 154251.95 | 0.75 |
November | 0.00 | 0.00 | 0.951329E+11 | 0.938362E+11 | 164593.85 | 09-NOV-05:12 | 111409.13 | 0.62 |
December | 0.00 | 0.00 | 0.563994E+11 | 0.563992E+11 | 91896.42 | 04-DEC-15:00 | 91896.42 | 0.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.205687E+13 | 0.160301E+13 | 0.72 | |||
Minimum of Months | 0.00 | 0.00 | 0.353548E+11 | 0.353113E+11 | 75774.23 | 61498.02 | 0.38 | |
Maximum of Months | 0.00 | 0.00 | 0.325617E+12 | 0.200805E+12 | 311088.73 | 195623.03 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.213288E+12 | 0.213288E+12 | 588141.59 | 12-JAN-15:05 | 588141.59 | 0.33 |
February | 0.00 | 0.00 | 0.394497E+12 | 0.393704E+12 | 1076508.51 | 25-FEB-06:02 | 734921.64 | 0.48 |
March | 0.00 | 0.00 | 0.912140E+12 | 0.897960E+12 | 1924950.97 | 29-MAR-04:12 | 1518121.15 | 0.62 |
April | 0.00 | 0.00 | 0.148036E+13 | 0.142542E+13 | 2130435.16 | 24-APR-04:12 | 1507656.16 | 0.72 |
May | 0.00 | 0.00 | 0.217701E+13 | 0.184075E+13 | 2768830.43 | 24-MAY-05:02 | 1615636.68 | 0.84 |
June | 0.00 | 0.00 | 0.246879E+13 | 0.181242E+13 | 2876590.89 | 26-JUN-05:02 | 1637677.78 | 0.83 |
July | 0.00 | 0.00 | 0.268963E+13 | 0.160437E+13 | 3039488.95 | 25-JUL-05:02 | 1634609.44 | 0.81 |
August | 0.00 | 0.00 | 0.265652E+13 | 0.152303E+13 | 2981316.20 | 11-AUG-05:03 | 1609545.70 | 0.79 |
September | 0.00 | 0.00 | 0.205024E+13 | 0.127442E+13 | 2876489.92 | 05-SEP-05:02 | 1669990.94 | 0.73 |
October | 0.00 | 0.00 | 0.125583E+13 | 0.110820E+13 | 2461236.33 | 12-OCT-05:02 | 1446390.60 | 0.65 |
November | 0.00 | 0.00 | 0.688929E+12 | 0.680390E+12 | 1392913.19 | 09-NOV-06:03 | 920183.72 | 0.58 |
December | 0.00 | 0.00 | 0.295893E+12 | 0.295893E+12 | 671074.29 | 01-DEC-15:05 | 671074.29 | 0.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.172831E+14 | 0.130698E+14 | 0.65 | |||
Minimum of Months | 0.00 | 0.00 | 0.213288E+12 | 0.213288E+12 | 588141.59 | 588141.59 | 0.33 | |
Maximum of Months | 0.00 | 0.00 | 0.268963E+13 | 0.184075E+13 | 3039488.95 | 1669990.94 | 0.84 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.171369E+11 | 0.171369E+11 | 57212.66 | 12-JAN-15:30 | 57212.66 | 0.30 |
February | 0.00 | 0.00 | 0.355236E+11 | 0.354464E+11 | 98115.58 | 25-FEB-06:02 | 65638.04 | 0.46 |
March | 0.00 | 0.00 | 0.927577E+11 | 0.914510E+11 | 189433.72 | 29-MAR-04:12 | 152027.36 | 0.60 |
April | 0.00 | 0.00 | 0.161998E+12 | 0.156417E+12 | 225640.74 | 03-APR-05:02 | 164462.39 | 0.72 |
May | 0.00 | 0.00 | 0.240181E+12 | 0.206206E+12 | 310120.70 | 24-MAY-05:02 | 182842.76 | 0.84 |
June | 0.00 | 0.00 | 0.269394E+12 | 0.203495E+12 | 317078.71 | 26-JUN-05:02 | 186929.03 | 0.83 |
July | 0.00 | 0.00 | 0.286653E+12 | 0.177493E+12 | 349287.92 | 03-JUL-03:02 | 219409.71 | 0.82 |
August | 0.00 | 0.00 | 0.279913E+12 | 0.166247E+12 | 332004.30 | 17-AUG-05:02 | 181312.63 | 0.80 |
September | 0.00 | 0.00 | 0.213511E+12 | 0.136188E+12 | 319587.03 | 05-SEP-05:02 | 189499.84 | 0.73 |
October | 0.00 | 0.00 | 0.126691E+12 | 0.112804E+12 | 224390.84 | 02-OCT-04:12 | 165601.44 | 0.64 |
November | 0.00 | 0.00 | 0.633493E+11 | 0.628760E+11 | 117390.37 | 09-NOV-06:03 | 75669.73 | 0.55 |
December | 0.00 | 0.00 | 0.225841E+11 | 0.225841E+11 | 65883.36 | 01-DEC-15:00 | 65883.36 | 0.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.180969E+13 | 0.138834E+13 | 0.64 | |||
Minimum of Months | 0.00 | 0.00 | 0.171369E+11 | 0.171369E+11 | 57212.66 | 57212.66 | 0.30 | |
Maximum of Months | 0.00 | 0.00 | 0.286653E+12 | 0.206206E+12 | 349287.92 | 219409.71 | 0.84 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.477690E+11 | 0.476712E+11 | 119346.72 | 18-JAN-05:13 | 86996.63 | 0.46 |
February | 0.00 | 0.00 | 0.507354E+11 | 0.506179E+11 | 132912.00 | 25-FEB-05:12 | 87989.73 | 0.52 |
March | 0.00 | 0.00 | 0.717589E+11 | 0.714611E+11 | 151129.42 | 11-MAR-05:03 | 91759.75 | 0.56 |
April | 0.00 | 0.00 | 0.856445E+11 | 0.835343E+11 | 158885.69 | 27-APR-03:02 | 96296.04 | 0.54 |
May | 0.00 | 0.00 | 0.110139E+12 | 0.978079E+11 | 192396.55 | 22-MAY-03:13 | 89688.39 | 0.61 |
June | 0.00 | 0.00 | 0.130149E+12 | 0.101841E+12 | 207183.45 | 26-JUN-03:02 | 84263.71 | 0.63 |
July | 0.00 | 0.00 | 0.151440E+12 | 0.100986E+12 | 217792.34 | 23-JUL-22:30 | 85317.08 | 0.63 |
August | 0.00 | 0.00 | 0.170051E+12 | 0.109528E+12 | 225639.32 | 27-AUG-12:20 | 90651.39 | 0.68 |
September | 0.00 | 0.00 | 0.131707E+12 | 0.921998E+11 | 209626.25 | 17-SEP-19:02 | 98759.26 | 0.64 |
October | 0.00 | 0.00 | 0.946407E+11 | 0.875863E+11 | 166530.35 | 01-OCT-11:49 | 109228.28 | 0.61 |
November | 0.00 | 0.00 | 0.722175E+11 | 0.718108E+11 | 141499.59 | 09-NOV-05:12 | 87521.94 | 0.58 |
December | 0.00 | 0.00 | 0.564779E+11 | 0.564221E+11 | 112087.71 | 30-DEC-05:12 | 84044.44 | 0.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.117273E+13 | 0.971466E+12 | 0.58 | |||
Minimum of Months | 0.00 | 0.00 | 0.477690E+11 | 0.476712E+11 | 112087.71 | 84044.44 | 0.46 | |
Maximum of Months | 0.00 | 0.00 | 0.170051E+12 | 0.109528E+12 | 225639.32 | 109228.28 | 0.68 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.336305E+12 | 0.322693E+12 | 131184.95 | 17-JAN-17:00 | 124278.55 | 0.00 |
February | 0.00 | 0.00 | 0.532262E+12 | 0.515284E+12 | 224903.54 | 24-FEB-17:00 | 218877.04 | 0.00 |
March | 0.00 | 0.00 | 0.835510E+12 | 0.821249E+12 | 395654.11 | 31-MAR-24:00 | 393382.32 | 0.00 |
April | 0.00 | 0.00 | 0.103429E+13 | 0.102795E+13 | 409377.10 | 22-APR-17:00 | 401343.78 | 0.00 |
May | 0.00 | 0.00 | 0.362635E+12 | 0.345670E+12 | 226214.86 | 31-MAY-23:05 | 212138.66 | 0.00 |
June | 0.00 | 0.00 | 0.598526E+12 | 0.572714E+12 | 318509.19 | 30-JUN-23:03 | 306371.34 | 0.00 |
July | 0.00 | 0.00 | 0.873995E+12 | 0.837309E+12 | 401100.92 | 31-JUL-24:00 | 389748.53 | 0.00 |
August | 0.00 | 0.00 | 0.109922E+13 | 0.106360E+13 | 421065.73 | 10-AUG-14:00 | 401353.04 | 0.00 |
September | 0.00 | 0.00 | 0.366153E+12 | 0.334810E+12 | 227621.65 | 30-SEP-23:05 | 212959.44 | 0.00 |
October | 0.00 | 0.00 | 0.601573E+12 | 0.585066E+12 | 310675.35 | 31-OCT-24:00 | 302060.59 | 0.00 |
November | 0.00 | 0.00 | 0.817176E+12 | 0.797370E+12 | 321273.46 | 24-NOV-08:25 | 307297.37 | 0.00 |
December | 0.00 | 0.00 | 0.109837E+13 | 0.106331E+13 | 421496.40 | 22-DEC-06:03 | 395854.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.855601E+13 | 0.828702E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.336305E+12 | 0.322693E+12 | 131184.95 | 124278.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109922E+13 | 0.106360E+13 | 421496.40 | 401353.04 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.467578E+10 | 0.451807E+10 | 2419.52 | 12-JAN-17:00 | 2284.41 | 0.00 |
February | 0.00 | 0.00 | 0.945940E+10 | 0.921753E+10 | 4491.92 | 21-FEB-17:00 | 4335.56 | 0.00 |
March | 0.00 | 0.00 | 0.162099E+11 | 0.158590E+11 | 7806.45 | 31-MAR-24:00 | 7697.54 | 0.00 |
April | 0.00 | 0.00 | 0.211233E+11 | 0.207967E+11 | 8663.90 | 17-APR-00:23 | 8415.94 | 0.00 |
May | 0.00 | 0.00 | 0.733398E+10 | 0.665113E+10 | 4667.48 | 31-MAY-23:05 | 4046.43 | 0.00 |
June | 0.00 | 0.00 | 0.124376E+11 | 0.113357E+11 | 6627.70 | 30-JUN-23:03 | 6102.42 | 0.00 |
July | 0.00 | 0.00 | 0.183080E+11 | 0.166765E+11 | 8721.68 | 31-JUL-23:03 | 7907.86 | 0.00 |
August | 0.00 | 0.00 | 0.231099E+11 | 0.213902E+11 | 8898.63 | 10-AUG-14:00 | 8064.71 | 0.00 |
September | 0.00 | 0.00 | 0.737764E+10 | 0.608996E+10 | 4667.63 | 30-SEP-23:05 | 4035.67 | 0.00 |
October | 0.00 | 0.00 | 0.117509E+11 | 0.111128E+11 | 5973.67 | 31-OCT-23:10 | 5713.97 | 0.00 |
November | 0.00 | 0.00 | 0.155319E+11 | 0.152025E+11 | 6549.24 | 08-NOV-16:50 | 6279.87 | 0.00 |
December | 0.00 | 0.00 | 0.203775E+11 | 0.201903E+11 | 8196.09 | 28-DEC-17:00 | 8027.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.167696E+12 | 0.159040E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.467578E+10 | 0.451807E+10 | 2419.52 | 2284.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.231099E+11 | 0.213902E+11 | 8898.63 | 8415.94 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.308234E+11 | 0.295455E+11 | 22249.24 | 12-JAN-17:00 | 20989.01 | 0.00 |
February | 0.00 | 0.00 | 0.832671E+11 | 0.810392E+11 | 42305.26 | 22-FEB-17:00 | 40782.94 | 0.00 |
March | 0.00 | 0.00 | 0.152724E+12 | 0.149420E+12 | 75286.51 | 31-MAR-24:00 | 74266.30 | 0.00 |
April | 0.00 | 0.00 | 0.198910E+12 | 0.195824E+12 | 80568.28 | 16-APR-20:53 | 78023.11 | 0.00 |
May | 0.00 | 0.00 | 0.692963E+11 | 0.627158E+11 | 45051.34 | 31-MAY-23:05 | 38798.83 | 0.00 |
June | 0.00 | 0.00 | 0.118628E+12 | 0.107848E+12 | 63853.11 | 30-JUN-23:03 | 58661.22 | 0.00 |
July | 0.00 | 0.00 | 0.174350E+12 | 0.158276E+12 | 81605.56 | 31-JUL-23:03 | 73701.97 | 0.00 |
August | 0.00 | 0.00 | 0.216836E+12 | 0.199898E+12 | 83546.74 | 10-AUG-14:05 | 75412.50 | 0.00 |
September | 0.00 | 0.00 | 0.690689E+11 | 0.565271E+11 | 45179.77 | 30-SEP-23:05 | 38867.46 | 0.00 |
October | 0.00 | 0.00 | 0.110534E+12 | 0.104394E+12 | 56529.71 | 31-OCT-23:10 | 53971.84 | 0.00 |
November | 0.00 | 0.00 | 0.143700E+12 | 0.140607E+12 | 62316.24 | 08-NOV-17:00 | 59634.38 | 0.00 |
December | 0.00 | 0.00 | 0.183948E+12 | 0.182240E+12 | 77418.07 | 28-DEC-17:00 | 75819.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.155209E+13 | 0.146834E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.308234E+11 | 0.295455E+11 | 22249.24 | 20989.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216836E+12 | 0.199898E+12 | 83546.74 | 78023.11 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.200185E+10 | 0.188809E+10 | 2265.61 | 12-JAN-17:00 | 2130.83 | 0.00 |
February | 0.00 | 0.00 | 0.772377E+10 | 0.748839E+10 | 4296.18 | 22-FEB-17:00 | 4136.03 | 0.00 |
March | 0.00 | 0.00 | 0.151369E+11 | 0.147880E+11 | 7495.85 | 31-MAR-24:00 | 7386.80 | 0.00 |
April | 0.00 | 0.00 | 0.200987E+11 | 0.197722E+11 | 8345.14 | 16-APR-20:53 | 8083.09 | 0.00 |
May | 0.00 | 0.00 | 0.717301E+10 | 0.649435E+10 | 4467.85 | 31-MAY-23:05 | 3827.70 | 0.00 |
June | 0.00 | 0.00 | 0.120849E+11 | 0.109870E+11 | 6464.06 | 30-JUN-23:03 | 5935.38 | 0.00 |
July | 0.00 | 0.00 | 0.176700E+11 | 0.160425E+11 | 8415.25 | 31-JUL-23:03 | 7595.48 | 0.00 |
August | 0.00 | 0.00 | 0.220781E+11 | 0.203551E+11 | 8555.23 | 10-AUG-14:00 | 7719.99 | 0.00 |
September | 0.00 | 0.00 | 0.702066E+10 | 0.574654E+10 | 4553.85 | 30-SEP-23:05 | 3918.07 | 0.00 |
October | 0.00 | 0.00 | 0.110025E+11 | 0.103706E+11 | 5557.85 | 31-OCT-23:10 | 5290.87 | 0.00 |
November | 0.00 | 0.00 | 0.139156E+11 | 0.135893E+11 | 6286.74 | 08-NOV-16:50 | 6019.41 | 0.00 |
December | 0.00 | 0.00 | 0.172984E+11 | 0.171123E+11 | 7777.18 | 28-DEC-17:00 | 7609.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153204E+12 | 0.144634E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.200185E+10 | 0.188809E+10 | 2265.61 | 2130.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220781E+11 | 0.203551E+11 | 8555.23 | 8083.09 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 11504.98 | 1120390.31 | 02-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1912.86 | 711580.41 | 11-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.06 | 181.84 | 01-MAR-06:50 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 69.50 | 30436.34 | 27-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 3306.52 | 510028.34 | 23-DEC-06:03 |
Annual Sum or Average | 0.00 | 1410.42 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 11504.98 | 1120390.31 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 118880.29 | 754203.61 | 12-JAN-15:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 227862.11 | 1320826.76 | 22-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 472977.29 | 1973705.60 | 10-MAR-13:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 775371.75 | 2129363.37 | 10-APR-13:05 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1061365.01 | 2942154.80 | 07-MAY-15:01 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1236575.64 | 3582787.11 | 10-JUN-17:42 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1308786.68 | 3858522.18 | 05-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1304661.38 | 4131277.03 | 10-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1048620.14 | 3345127.32 | 12-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 643945.80 | 2519787.65 | 12-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 381342.08 | 1758524.58 | 10-NOV-12:05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 162908.52 | 862308.75 | 01-DEC-15:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 731278.64 | 0.00 | ||||
Minimum of Months | 118880.29 | 754203.61 | 0.00 | 0.00 | ||
Maximum of Months | 1308786.68 | 4131277.03 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 116766.05 | 795969.93 | 14-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 225750.17 | 1510929.05 | 25-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 469890.47 | 3363172.02 | 14-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 771909.16 | 3950631.67 | 26-APR-05:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1056730.57 | 4261910.84 | 23-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1231571.48 | 4400531.33 | 14-JUN-03:12 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1301579.18 | 4665453.82 | 16-JUL-17:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1300005.00 | 4690408.77 | 07-AUG-03:01 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1043022.66 | 4424584.84 | 09-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 642196.28 | 4011140.13 | 04-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 379717.20 | 2005360.28 | 09-NOV-06:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 160682.50 | 975721.83 | 01-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 727646.50 | 0.00 | ||||
Minimum of Months | 116766.05 | 795969.93 | 0.00 | 0.00 | ||
Maximum of Months | 1301579.18 | 4690408.77 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 213650.09 | 572846.15 | 12-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 487553.03 | 1000889.20 | 22-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 948024.51 | 1734629.46 | 28-MAR-15:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1560102.02 | 2189874.65 | 15-APR-15:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1109986.68 | 1763569.12 | 01-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1395210.69 | 2041467.80 | 08-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1532147.59 | 2059121.58 | 02-JUL-16:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1640477.82 | 2053370.97 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 889385.52 | 1385442.83 | 17-SEP-20:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 891599.52 | 1556475.63 | 02-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 804530.50 | 1400186.04 | 08-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 769546.57 | 1297123.70 | 28-DEC-14:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1023004.83 | 0.00 | ||||
Minimum of Months | 213650.09 | 572846.15 | 0.00 | 0.00 | ||
Maximum of Months | 1640477.82 | 2189874.65 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 12727.62 | 41927.91 | 17-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12553.77 | 41702.34 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 12447.44 | 39943.21 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:05 | 10697.24 | 36268.59 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 9896.71 | 32590.21 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 9208.25 | 28959.07 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 8257.21 | 26805.45 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 9169.95 | 28568.80 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 9457.79 | 31757.54 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 10503.37 | 35896.41 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11719.47 | 39407.03 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12135.45 | 41506.46 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 10721.25 | ||||
Minimum of Months | 0.00 | 0.00 | 8257.21 | 26805.45 | ||
Maximum of Months | 0.00 | 0.00 | 12727.62 | 41927.91 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 134744.02 | 865149.10 | 12-JAN-15:05 | 4513.33 | 139024.59 | 05-JAN-07:00 |
February | 266251.06 | 1504768.62 | 22-FEB-15:40 | 1459.36 | 129529.38 | 02-FEB-06:50 |
March | 591176.11 | 2955950.26 | 10-MAR-17:00 | 562.60 | 75615.70 | 19-MAR-24:00 |
April | 1181365.59 | 5077734.77 | 18-APR-14:05 | 634.25 | 79350.87 | 11-APR-04:10 |
May | 2416754.31 | 6744135.82 | 17-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 3516419.06 | 7769164.25 | 22-JUN-15:40 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 4285029.86 | 7730570.99 | 08-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 4315494.17 | 7710579.15 | 25-AUG-05:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 3128696.96 | 7271800.91 | 14-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 1010015.18 | 4646673.78 | 04-OCT-12:10 | 82.13 | 29041.38 | 30-OCT-00:10 |
November | 458376.24 | 2693330.72 | 13-NOV-15:05 | 367.23 | 65752.59 | 27-NOV-01:25 |
December | 185869.25 | 986967.42 | 01-DEC-15:05 | 3358.91 | 150466.75 | 20-DEC-07:10 |
Annual Sum or Average | 1800307.77 | 917.62 | ||||
Minimum of Months | 134744.02 | 865149.10 | 0.00 | 0.00 | ||
Maximum of Months | 4315494.17 | 7769164.25 | 4513.33 | 150466.75 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138584E+11 | 0.81 | 9097.01 | 01-JAN-00:05 | 1.42 |
February | 0.125430E+11 | 0.81 | 9097.01 | 01-FEB-05:13 | 1.42 |
March | 0.143251E+11 | 0.83 | 9097.01 | 01-MAR-05:12 | 1.42 |
April | 0.139833E+11 | 0.84 | 9097.01 | 01-APR-04:12 | 1.42 |
May | 0.151541E+11 | 0.88 | 9097.01 | 01-MAY-00:20 | 1.42 |
June | 0.151574E+11 | 0.90 | 9097.01 | 01-JUN-03:02 | 1.41 |
July | 0.156105E+11 | 0.90 | 9097.01 | 01-JUL-03:03 | 1.41 |
August | 0.167288E+11 | 0.97 | 9097.01 | 01-AUG-03:03 | 1.41 |
September | 0.154565E+11 | 0.92 | 9097.01 | 01-SEP-03:02 | 1.41 |
October | 0.154986E+11 | 0.90 | 9097.01 | 01-OCT-10:45 | 1.40 |
November | 0.148059E+11 | 0.89 | 9097.01 | 01-NOV-04:12 | 1.42 |
December | 0.143555E+11 | 0.84 | 9097.01 | 01-DEC-05:12 | 1.42 |
Annual Sum or Average | 0.177477E+12 | 0.87 | |||
Minimum of Months | 0.125430E+11 | 0.81 | 9097.01 | 1.40 | |
Maximum of Months | 0.167288E+11 | 0.97 | 9097.01 | 1.42 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.430393E+10 | 0.33 | 7999.77 | 26-JAN-06:03 | 0.97 |
February | 0.570203E+10 | 0.40 | 12668.43 | 23-FEB-06:02 | 1.29 |
March | 0.101832E+11 | 0.56 | 21650.08 | 14-MAR-05:02 | 1.80 |
April | 0.142576E+11 | 0.74 | 21650.08 | 03-APR-04:21 | 1.80 |
May | 0.140055E+11 | 0.72 | 21650.08 | 01-MAY-03:02 | 1.81 |
June | 0.150482E+11 | 0.76 | 21650.08 | 01-JUN-03:02 | 1.80 |
July | 0.148912E+11 | 0.74 | 21650.08 | 03-JUL-03:02 | 1.80 |
August | 0.181200E+11 | 0.82 | 21650.08 | 01-AUG-05:03 | 1.80 |
September | 0.107714E+11 | 0.62 | 21650.08 | 01-SEP-05:02 | 1.80 |
October | 0.100575E+11 | 0.57 | 21650.08 | 03-OCT-05:03 | 1.80 |
November | 0.809471E+10 | 0.47 | 14578.77 | 06-NOV-05:12 | 1.40 |
December | 0.653578E+10 | 0.40 | 10929.57 | 18-DEC-14:40 | 1.17 |
Annual Sum or Average | 0.131971E+12 | 0.60 | |||
Minimum of Months | 0.430393E+10 | 0.33 | 7999.77 | 0.97 | |
Maximum of Months | 0.181200E+11 | 0.82 | 21650.08 | 1.81 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.284888E+11 | 0.30 | 81896.99 | 21-JAN-06:02 | 1.02 |
February | 0.365225E+11 | 0.34 | 79755.72 | 22-FEB-16:00 | 1.00 |
March | 0.697523E+11 | 0.44 | 207583.82 | 14-MAR-05:02 | 1.80 |
April | 0.992102E+11 | 0.59 | 207583.82 | 05-APR-05:02 | 1.81 |
May | 0.122479E+12 | 0.68 | 207583.82 | 01-MAY-05:01 | 1.80 |
June | 0.122460E+12 | 0.68 | 207583.82 | 01-JUN-03:02 | 1.80 |
July | 0.107713E+12 | 0.62 | 207583.82 | 03-JUL-05:01 | 1.80 |
August | 0.108312E+12 | 0.61 | 207583.82 | 02-AUG-05:03 | 1.80 |
September | 0.865482E+11 | 0.54 | 207583.82 | 01-SEP-05:02 | 1.80 |
October | 0.740325E+11 | 0.46 | 207583.82 | 03-OCT-04:12 | 1.80 |
November | 0.502172E+11 | 0.38 | 104162.69 | 01-NOV-05:02 | 1.17 |
December | 0.330306E+11 | 0.31 | 88595.01 | 22-DEC-06:03 | 1.07 |
Annual Sum or Average | 0.938767E+12 | 0.50 | |||
Minimum of Months | 0.284888E+11 | 0.30 | 79755.72 | 1.00 | |
Maximum of Months | 0.122479E+12 | 0.68 | 207583.82 | 1.81 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.273062E+10 | 0.33 | 4497.18 | 02-JAN-05:11 | 0.67 |
February | 0.320840E+10 | 0.33 | 7705.97 | 22-FEB-15:30 | 0.90 |
March | 0.655323E+10 | 0.41 | 19037.34 | 29-MAR-04:12 | 1.56 |
April | 0.105617E+11 | 0.58 | 23763.22 | 15-APR-05:02 | 1.79 |
May | 0.134805E+11 | 0.68 | 23763.22 | 11-MAY-05:02 | 1.79 |
June | 0.135163E+11 | 0.68 | 23763.22 | 05-JUN-05:02 | 1.79 |
July | 0.115352E+11 | 0.62 | 23763.22 | 08-JUL-05:02 | 1.79 |
August | 0.111741E+11 | 0.60 | 23763.22 | 07-AUG-05:03 | 1.79 |
September | 0.885346E+10 | 0.52 | 23763.22 | 05-SEP-03:02 | 1.79 |
October | 0.711950E+10 | 0.43 | 23763.22 | 04-OCT-05:02 | 1.79 |
November | 0.441676E+10 | 0.35 | 8927.84 | 09-NOV-15:50 | 0.98 |
December | 0.280344E+10 | 0.32 | 4749.45 | 01-DEC-15:00 | 0.69 |
Annual Sum or Average | 0.959532E+11 | 0.49 | |||
Minimum of Months | 0.273062E+10 | 0.32 | 4497.18 | 0.67 | |
Maximum of Months | 0.135163E+11 | 0.68 | 23763.22 | 1.79 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.966097E+11 | 1.38 | 36069.92 | 01-JAN-00:05 | 1.38 |
February | 0.872603E+11 | 1.38 | 36069.92 | 01-FEB-00:10 | 1.38 |
March | 0.966097E+11 | 1.38 | 36069.92 | 01-MAR-00:10 | 1.38 |
April | 0.934932E+11 | 1.38 | 36069.92 | 01-APR-00:05 | 1.38 |
May | 0.966097E+11 | 1.38 | 36069.92 | 01-MAY-00:05 | 1.38 |
June | 0.934932E+11 | 1.38 | 36069.92 | 01-JUN-00:05 | 1.38 |
July | 0.966097E+11 | 1.38 | 36069.92 | 01-JUL-00:10 | 1.38 |
August | 0.966097E+11 | 1.38 | 36069.92 | 01-AUG-00:05 | 1.38 |
September | 0.934932E+11 | 1.38 | 36069.92 | 01-SEP-00:10 | 1.38 |
October | 0.966097E+11 | 1.38 | 36069.92 | 01-OCT-00:05 | 1.38 |
November | 0.934932E+11 | 1.38 | 36069.92 | 01-NOV-00:10 | 1.38 |
December | 0.966097E+11 | 1.38 | 36069.92 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.113750E+13 | 1.38 | |||
Minimum of Months | 0.872603E+11 | 1.38 | 36069.92 | 1.38 | |
Maximum of Months | 0.966097E+11 | 1.38 | 36069.92 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144599E+10 | 0.94 | 539.87 | 01-JAN-00:05 | 0.94 |
February | 0.130606E+10 | 0.94 | 539.87 | 01-FEB-00:10 | 0.94 |
March | 0.144599E+10 | 0.94 | 539.87 | 01-MAR-00:10 | 0.94 |
April | 0.139935E+10 | 0.94 | 539.87 | 01-APR-00:05 | 0.94 |
May | 0.144599E+10 | 0.93 | 539.87 | 01-MAY-00:05 | 0.94 |
June | 0.139935E+10 | 0.93 | 539.87 | 01-JUN-00:05 | 0.94 |
July | 0.144599E+10 | 0.93 | 539.87 | 01-JUL-00:10 | 0.94 |
August | 0.144599E+10 | 0.93 | 539.87 | 01-AUG-00:05 | 0.94 |
September | 0.139935E+10 | 0.93 | 539.87 | 01-SEP-00:10 | 0.93 |
October | 0.144599E+10 | 0.94 | 539.87 | 01-OCT-00:05 | 0.94 |
November | 0.139935E+10 | 0.94 | 539.87 | 01-NOV-00:10 | 0.94 |
December | 0.144599E+10 | 0.94 | 539.87 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.170254E+11 | 0.94 | |||
Minimum of Months | 0.130606E+10 | 0.93 | 539.87 | 0.93 | |
Maximum of Months | 0.144599E+10 | 0.94 | 539.87 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138086E+11 | 0.94 | 5155.52 | 01-JAN-00:05 | 0.94 |
February | 0.124722E+11 | 0.94 | 5155.52 | 01-FEB-00:10 | 0.94 |
March | 0.138086E+11 | 0.94 | 5155.52 | 01-MAR-00:10 | 0.94 |
April | 0.133631E+11 | 0.94 | 5155.52 | 01-APR-00:05 | 0.94 |
May | 0.138086E+11 | 0.93 | 5155.52 | 01-MAY-00:05 | 0.94 |
June | 0.133631E+11 | 0.93 | 5155.52 | 01-JUN-00:05 | 0.94 |
July | 0.138086E+11 | 0.93 | 5155.52 | 01-JUL-00:10 | 0.93 |
August | 0.138086E+11 | 0.93 | 5155.52 | 01-AUG-00:05 | 0.93 |
September | 0.133631E+11 | 0.93 | 5155.52 | 01-SEP-00:10 | 0.93 |
October | 0.138086E+11 | 0.94 | 5155.52 | 01-OCT-00:05 | 0.94 |
November | 0.133631E+11 | 0.94 | 5155.52 | 01-NOV-00:10 | 0.94 |
December | 0.138086E+11 | 0.94 | 5155.52 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.162585E+12 | 0.94 | |||
Minimum of Months | 0.124722E+11 | 0.93 | 5155.52 | 0.93 | |
Maximum of Months | 0.138086E+11 | 0.94 | 5155.52 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139572E+10 | 0.94 | 521.10 | 01-JAN-00:05 | 0.94 |
February | 0.126065E+10 | 0.94 | 521.10 | 01-FEB-00:10 | 0.94 |
March | 0.139572E+10 | 0.94 | 521.10 | 01-MAR-00:10 | 0.94 |
April | 0.135070E+10 | 0.94 | 521.10 | 01-APR-00:05 | 0.94 |
May | 0.139572E+10 | 0.93 | 521.10 | 01-MAY-00:05 | 0.94 |
June | 0.135070E+10 | 0.93 | 521.10 | 01-JUN-00:05 | 0.94 |
July | 0.139572E+10 | 0.93 | 521.10 | 01-JUL-00:10 | 0.94 |
August | 0.139572E+10 | 0.93 | 521.10 | 01-AUG-00:05 | 0.94 |
September | 0.135070E+10 | 0.93 | 521.10 | 01-SEP-00:10 | 0.93 |
October | 0.139572E+10 | 0.94 | 521.10 | 01-OCT-00:05 | 0.94 |
November | 0.135070E+10 | 0.94 | 521.10 | 01-NOV-00:10 | 0.94 |
December | 0.139572E+10 | 0.94 | 521.10 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.164335E+11 | 0.94 | |||
Minimum of Months | 0.126065E+10 | 0.93 | 521.10 | 0.93 | |
Maximum of Months | 0.139572E+10 | 0.94 | 521.10 | 0.94 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.172633E+09 | 0.156924E+09 | 3009.51 | 02-JAN-06:03 | 2735.64 | 2735.64 | 48.98 | 8.12 |
February | 25399169.18 | 23087844.79 | 2403.18 | 11-FEB-06:02 | 2184.49 | 2184.49 | 39.94 | 4.05 |
March | 677.07 | 615.45 | 0.75 | 01-MAR-06:50 | 0.68 | 0.68 | 25.80 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 25.80 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 25.80 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 25.80 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 25.80 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 25.80 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 25.80 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 25.80 | 0.00 |
November | 763329.03 | 693866.09 | 125.51 | 27-NOV-06:10 | 114.09 | 114.09 | 26.74 | 0.13 |
December | 47616595.16 | 43283485.00 | 2066.08 | 23-DEC-06:03 | 1878.07 | 1878.07 | 42.36 | 3.08 |
Annual Sum or Average | 0.246413E+09 | 0.223989E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 | 0.00 | |
Maximum of Months | 0.172633E+09 | 0.156924E+09 | 3009.51 | 2735.64 | 2735.64 | 48.98 | 8.12 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.106563E+09 | 96865871.71 | 815.84 | 12-JAN-06:03 | 741.60 | 741.60 | 6.70 | 24.54 |
February | 0.280123E+09 | 0.254632E+09 | 1785.04 | 25-FEB-06:02 | 1622.60 | 1622.60 | 6.70 | 34.83 |
March | 0.802955E+09 | 0.729886E+09 | 12442.84 | 14-MAR-05:02 | 11310.54 | 11310.54 | 9.61 | 77.56 |
April | 0.148758E+10 | 0.135221E+10 | 12728.48 | 15-APR-05:02 | 11570.19 | 11570.19 | 9.50 | 78.27 |
May | 0.207341E+10 | 0.188473E+10 | 12728.48 | 08-MAY-05:02 | 11570.19 | 11570.19 | 9.65 | 78.27 |
June | 0.240378E+10 | 0.218504E+10 | 12728.48 | 05-JUN-05:02 | 11570.19 | 11570.19 | 9.78 | 78.27 |
July | 0.252070E+10 | 0.229132E+10 | 12728.48 | 02-JUL-19:02 | 11570.19 | 11570.19 | 10.41 | 78.27 |
August | 0.258823E+10 | 0.235270E+10 | 12728.48 | 02-AUG-05:03 | 11570.19 | 11570.19 | 10.84 | 78.27 |
September | 0.181836E+10 | 0.165289E+10 | 12728.48 | 01-SEP-05:02 | 11570.19 | 11570.19 | 10.50 | 78.27 |
October | 0.118921E+10 | 0.108099E+10 | 12728.48 | 03-OCT-05:03 | 11570.19 | 11570.19 | 10.20 | 78.27 |
November | 0.705138E+09 | 0.640970E+09 | 4079.08 | 01-NOV-14:50 | 3707.89 | 3707.89 | 10.18 | 49.48 |
December | 0.183805E+09 | 0.167078E+09 | 1129.11 | 01-DEC-06:02 | 1026.36 | 1026.36 | 6.70 | 28.44 |
Annual Sum or Average | 0.161598E+11 | 0.146893E+11 | ||||||
Minimum of Months | 0.106563E+09 | 96865871.71 | 815.84 | 741.60 | 741.60 | 6.70 | 24.54 | |
Maximum of Months | 0.258823E+10 | 0.235270E+10 | 12728.48 | 11570.19 | 11570.19 | 10.84 | 78.27 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.648089E+10 | 0.589113E+10 | 4380.34 | 01-JAN-00:05 | 3981.72 | 3981.72 | 6.80 | 39.13 |
February | 0.635705E+10 | 0.577856E+10 | 4380.34 | 01-FEB-05:13 | 3981.72 | 3981.72 | 7.15 | 39.13 |
March | 0.880250E+10 | 0.800148E+10 | 4380.34 | 01-MAR-05:12 | 3981.72 | 3981.72 | 8.74 | 39.13 |
April | 0.106458E+11 | 0.967701E+10 | 4380.34 | 01-APR-00:05 | 3981.72 | 3981.72 | 6.87 | 39.13 |
May | 0.108796E+11 | 0.988960E+10 | 4380.34 | 01-MAY-00:05 | 3981.72 | 3981.72 | 9.73 | 39.13 |
June | 0.105914E+11 | 0.962759E+10 | 4380.34 | 01-JUN-00:05 | 3981.72 | 3981.72 | 7.05 | 39.13 |
July | 0.108785E+11 | 0.988858E+10 | 4380.34 | 01-JUL-00:10 | 3981.72 | 3981.72 | 12.21 | 39.13 |
August | 0.110710E+11 | 0.100635E+11 | 4380.34 | 01-AUG-00:05 | 3981.72 | 3981.72 | 12.74 | 39.13 |
September | 0.996263E+10 | 0.905604E+10 | 4380.34 | 01-SEP-00:10 | 3981.72 | 3981.72 | 13.09 | 39.13 |
October | 0.925555E+10 | 0.841329E+10 | 4380.34 | 01-OCT-00:05 | 3981.72 | 3981.72 | 7.24 | 39.13 |
November | 0.758849E+10 | 0.689794E+10 | 4380.34 | 01-NOV-04:12 | 3981.72 | 3981.72 | 10.90 | 39.13 |
December | 0.696600E+10 | 0.633210E+10 | 4380.34 | 01-DEC-05:12 | 3981.72 | 3981.72 | 7.78 | 39.13 |
Annual Sum or Average | 0.109479E+12 | 0.995168E+11 | ||||||
Minimum of Months | 0.635705E+10 | 0.577856E+10 | 4380.34 | 3981.72 | 3981.72 | 6.80 | 39.13 | |
Maximum of Months | 0.110710E+11 | 0.100635E+11 | 4380.34 | 3981.72 | 3981.72 | 13.09 | 39.13 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.80 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.82 | 0.00 |
March | 0.913300E+09 | 0.830190E+09 | 4380.34 | 06-MAR-13:20 | 3981.72 | 3981.72 | 15.24 | 19.57 |
April | 0.286374E+10 | 0.260314E+10 | 4380.34 | 03-APR-08:00 | 3981.72 | 3981.72 | 14.91 | 19.57 |
May | 0.492388E+10 | 0.447580E+10 | 4380.34 | 01-MAY-05:01 | 3981.72 | 3981.72 | 12.41 | 39.13 |
June | 0.578442E+10 | 0.525804E+10 | 4380.34 | 01-JUN-05:04 | 3981.72 | 3981.72 | 15.88 | 19.57 |
July | 0.649047E+10 | 0.589983E+10 | 4380.34 | 01-JUL-03:53 | 3981.72 | 3981.72 | 15.23 | 19.57 |
August | 0.667129E+10 | 0.606421E+10 | 4380.34 | 01-AUG-05:03 | 3981.72 | 3981.72 | 15.43 | 39.13 |
September | 0.500180E+10 | 0.454663E+10 | 4380.34 | 01-SEP-05:04 | 3981.72 | 3981.72 | 16.66 | 19.57 |
October | 0.227190E+10 | 0.206516E+10 | 4380.34 | 02-OCT-07:40 | 3981.72 | 3981.72 | 15.07 | 19.57 |
November | 0.452051E+09 | 0.410914E+09 | 4380.34 | 01-NOV-12:40 | 3981.72 | 3981.72 | 15.40 | 19.57 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 7.38 | 0.00 |
Annual Sum or Average | 0.353729E+11 | 0.321539E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 | 0.00 | |
Maximum of Months | 0.667129E+10 | 0.606421E+10 | 4380.34 | 3981.72 | 3981.72 | 16.66 | 39.13 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.931318E+10 | 0.846568E+10 | 3477.14 | 01-JAN-00:05 | 3160.72 | 3160.72 | 21.41 | 14.67 |
February | 0.841191E+10 | 0.764642E+10 | 3477.14 | 01-FEB-00:10 | 3160.72 | 3160.72 | 24.12 | 14.67 |
March | 0.931318E+10 | 0.846568E+10 | 3477.14 | 01-MAR-00:10 | 3160.72 | 3160.72 | 28.36 | 14.67 |
April | 0.901276E+10 | 0.819259E+10 | 3477.14 | 01-APR-00:05 | 3160.72 | 3160.72 | 42.02 | 14.67 |
May | 0.931318E+10 | 0.846568E+10 | 3477.14 | 01-MAY-00:05 | 3160.72 | 3160.72 | 37.71 | 14.67 |
June | 0.901276E+10 | 0.819259E+10 | 3477.14 | 01-JUN-00:05 | 3160.72 | 3160.72 | 38.72 | 14.67 |
July | 0.931318E+10 | 0.846568E+10 | 3477.14 | 01-JUL-00:10 | 3160.72 | 3160.72 | 48.64 | 14.67 |
August | 0.931318E+10 | 0.846568E+10 | 3477.14 | 01-AUG-00:05 | 3160.72 | 3160.72 | 48.66 | 14.67 |
September | 0.901276E+10 | 0.819259E+10 | 3477.14 | 01-SEP-00:10 | 3160.72 | 3160.72 | 36.16 | 14.67 |
October | 0.931318E+10 | 0.846568E+10 | 3477.14 | 01-OCT-00:05 | 3160.72 | 3160.72 | 37.14 | 14.67 |
November | 0.901276E+10 | 0.819259E+10 | 3477.14 | 01-NOV-00:10 | 3160.72 | 3160.72 | 31.55 | 14.67 |
December | 0.931318E+10 | 0.846568E+10 | 3477.14 | 01-DEC-00:10 | 3160.72 | 3160.72 | 29.76 | 14.67 |
Annual Sum or Average | 0.109655E+12 | 0.996766E+11 | ||||||
Minimum of Months | 0.841191E+10 | 0.764642E+10 | 3477.14 | 3160.72 | 3160.72 | 21.41 | 14.67 | |
Maximum of Months | 0.931318E+10 | 0.846568E+10 | 3477.14 | 3160.72 | 3160.72 | 48.66 | 14.67 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.22 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 57.10 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.08 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 57.14 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 57.56 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 56.72 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 58.16 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.31 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 58.03 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:05 | 16.86 | 16.86 | 57.08 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 56.47 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 56.33 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.08 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.16 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.248237E+11 | 0.225648E+11 | 16804.47 | 12-JAN-15:05 | 15275.27 | 15275.27 | 24.12 | 68.63 |
February | 0.243620E+11 | 0.221451E+11 | 16834.18 | 22-FEB-15:40 | 15302.27 | 15302.27 | 26.35 | 68.63 |
March | 0.363796E+11 | 0.330690E+11 | 33665.77 | 10-MAR-17:00 | 30602.18 | 30602.18 | 26.25 | 137.27 |
April | 0.509166E+11 | 0.462832E+11 | 33738.05 | 17-APR-10:05 | 30667.89 | 30667.89 | 28.83 | 137.27 |
May | 0.594557E+11 | 0.540452E+11 | 33738.05 | 01-MAY-14:30 | 30667.89 | 30667.89 | 28.91 | 137.27 |
June | 0.619040E+11 | 0.562707E+11 | 33738.05 | 05-JUN-13:00 | 30667.89 | 30667.89 | 28.83 | 137.27 |
July | 0.653745E+11 | 0.594254E+11 | 33738.05 | 01-JUL-03:53 | 30667.89 | 30667.89 | 29.14 | 137.27 |
August | 0.670496E+11 | 0.609481E+11 | 33738.05 | 01-AUG-05:03 | 30667.89 | 30667.89 | 31.87 | 137.27 |
September | 0.559891E+11 | 0.508941E+11 | 33738.05 | 01-SEP-05:04 | 30667.89 | 30667.89 | 29.17 | 137.27 |
October | 0.429525E+11 | 0.390438E+11 | 33738.05 | 03-OCT-14:50 | 30667.89 | 30667.89 | 28.82 | 137.27 |
November | 0.306840E+11 | 0.278918E+11 | 33652.85 | 13-NOV-15:05 | 30590.44 | 30590.44 | 25.79 | 137.27 |
December | 0.266866E+11 | 0.242582E+11 | 16809.61 | 01-DEC-15:05 | 15279.94 | 15279.94 | 24.54 | 68.63 |
Annual Sum or Average | 0.546578E+12 | 0.496839E+12 | ||||||
Minimum of Months | 0.243620E+11 | 0.221451E+11 | 16804.47 | 15275.27 | 15275.27 | 24.12 | 68.63 | |
Maximum of Months | 0.670496E+11 | 0.609481E+11 | 33738.05 | 30667.89 | 30667.89 | 31.87 | 137.27 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 52.35 | 52.35 | 11504.98 | 1120390.31 | 02-JAN-06:03 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 44.03 | 44.03 | 1912.86 | 711580.41 | 11-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.80 | 25.80 | 0.06 | 181.84 | 01-MAR-06:50 |
April | 0.00 | 0.00 | 01-APR-00:05 | 25.80 | 25.80 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 25.80 | 25.80 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 25.80 | 25.80 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.80 | 25.80 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.80 | 25.80 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25.80 | 25.80 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 25.80 | 25.80 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.80 | 25.80 | 69.50 | 30436.34 | 27-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 29.32 | 29.32 | 3306.52 | 510028.34 | 23-DEC-06:03 |
Annual Sum or Average | 0.00 | 1410.42 | ||||||
Minimum of Months | 0.00 | 0.00 | 25.80 | 25.80 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 52.35 | 52.35 | 11504.98 | 1120390.31 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 118880.29 | 754203.61 | 12-JAN-15:05 | 11.30 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 227862.11 | 1320826.76 | 22-FEB-15:30 | 14.76 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 472977.29 | 1973705.60 | 10-MAR-13:05 | 12.72 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 775371.75 | 2129363.37 | 10-APR-13:05 | 13.20 | 6.70 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1061365.01 | 2942154.80 | 07-MAY-15:01 | 15.68 | 7.18 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1236575.64 | 3582787.11 | 10-JUN-17:42 | 17.64 | 9.14 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1308786.68 | 3858522.18 | 05-JUL-05:03 | 18.49 | 9.98 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1304661.38 | 4131277.03 | 10-AUG-05:03 | 19.32 | 10.81 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1048620.14 | 3345127.32 | 12-SEP-05:02 | 16.92 | 8.41 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 643945.80 | 2519787.65 | 12-OCT-05:02 | 14.39 | 6.70 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 381342.08 | 1758524.58 | 10-NOV-12:05 | 12.06 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 162908.52 | 862308.75 | 01-DEC-15:05 | 11.96 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 731278.64 | 0.00 | ||||||
Minimum of Months | 118880.29 | 754203.61 | 11.30 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1308786.68 | 4131277.03 | 19.32 | 10.81 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 116766.05 | 795969.93 | 14-JAN-06:03 | 15.21 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 225750.17 | 1510929.05 | 25-FEB-06:02 | 17.07 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 469890.47 | 3363172.02 | 14-MAR-05:02 | 17.07 | 11.82 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 771909.16 | 3950631.67 | 26-APR-05:02 | 18.77 | 12.72 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1056730.57 | 4261910.84 | 23-MAY-05:02 | 19.72 | 13.19 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1231571.48 | 4400531.33 | 14-JUN-03:12 | 20.59 | 13.39 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1301579.18 | 4665453.82 | 16-JUL-17:02 | 20.96 | 13.80 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1300005.00 | 4690408.77 | 07-AUG-03:01 | 21.03 | 13.84 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1043022.66 | 4424584.84 | 09-SEP-05:02 | 20.22 | 13.44 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 642196.28 | 4011140.13 | 04-OCT-05:02 | 18.95 | 12.81 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 379717.20 | 2005360.28 | 09-NOV-06:03 | 17.05 | 8.28 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 160682.50 | 975721.83 | 01-DEC-06:02 | 14.90 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 727646.50 | 0.00 | ||||||
Minimum of Months | 116766.05 | 795969.93 | 14.90 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1301579.18 | 4690408.77 | 21.03 | 13.84 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 213650.09 | 572846.15 | 12-JAN-15:00 | 29.49 | 25.52 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 487553.03 | 1000889.20 | 22-FEB-15:00 | 37.68 | 30.58 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 948024.51 | 1734629.46 | 28-MAR-15:20 | 51.42 | 40.86 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1560102.02 | 2189874.65 | 15-APR-15:00 | 59.79 | 46.86 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1109986.68 | 1763569.12 | 01-MAY-15:00 | 51.96 | 46.79 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1395210.69 | 2041467.80 | 08-JUN-16:00 | 57.08 | 48.79 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1532147.59 | 2059121.58 | 02-JUL-16:10 | 57.40 | 46.10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1640477.82 | 2053370.97 | 07-AUG-15:00 | 57.30 | 44.02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 889385.52 | 1385442.83 | 17-SEP-20:00 | 44.92 | 39.96 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 891599.52 | 1556475.63 | 02-OCT-15:00 | 48.12 | 40.30 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 804530.50 | 1400186.04 | 08-NOV-15:00 | 45.20 | 34.98 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 769546.57 | 1297123.70 | 28-DEC-14:20 | 43.27 | 30.76 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1023004.83 | 0.00 | ||||||
Minimum of Months | 213650.09 | 572846.15 | 29.49 | 25.52 | 0.00 | 0.00 | ||
Maximum of Months | 1640477.82 | 2189874.65 | 59.79 | 48.79 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.86 | 57.86 | 12727.62 | 41927.91 | 17-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.51 | 57.51 | 12553.77 | 41702.34 | 01-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.60 | 56.60 | 12447.44 | 39943.21 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:05 | 57.54 | 57.54 | 10697.24 | 36268.59 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.06 | 58.06 | 9896.71 | 32590.21 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 57.00 | 57.00 | 9208.25 | 28959.07 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.38 | 58.38 | 8257.21 | 26805.45 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.56 | 57.56 | 9169.95 | 28568.80 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.29 | 58.29 | 9457.79 | 31757.54 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 57.51 | 57.51 | 10503.37 | 35896.41 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.97 | 56.97 | 11719.47 | 39407.03 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.91 | 56.91 | 12135.45 | 41506.46 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 10721.25 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.60 | 56.60 | 8257.21 | 26805.45 | ||
Maximum of Months | 0.00 | 0.00 | 58.38 | 58.38 | 12727.62 | 41927.91 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 134744.02 | 865149.10 | 12-JAN-15:05 | 24.12 | 21.10 | 4513.33 | 139024.59 | 05-JAN-07:00 |
February | 266251.06 | 1504768.62 | 22-FEB-15:40 | 26.35 | 21.10 | 1459.36 | 129529.38 | 02-FEB-06:50 |
March | 591176.11 | 2955950.26 | 10-MAR-17:00 | 26.25 | 23.25 | 562.60 | 75615.70 | 19-MAR-24:00 |
April | 1181365.59 | 5077734.77 | 18-APR-14:05 | 29.95 | 25.83 | 634.25 | 79350.87 | 11-APR-04:10 |
May | 2416754.31 | 6744135.82 | 17-MAY-15:30 | 32.85 | 28.09 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 3516419.06 | 7769164.25 | 22-JUN-15:40 | 34.64 | 29.23 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 4285029.86 | 7730570.99 | 08-JUL-05:03 | 34.57 | 29.21 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 4315494.17 | 7710579.15 | 25-AUG-05:05 | 34.54 | 29.20 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 3128696.96 | 7271800.91 | 14-SEP-15:30 | 33.77 | 28.96 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 1010015.18 | 4646673.78 | 04-OCT-12:10 | 29.20 | 25.30 | 82.13 | 29041.38 | 30-OCT-00:10 |
November | 458376.24 | 2693330.72 | 13-NOV-15:05 | 25.79 | 21.10 | 367.23 | 65752.59 | 27-NOV-01:25 |
December | 185869.25 | 986967.42 | 01-DEC-15:05 | 24.54 | 21.10 | 3358.91 | 150466.75 | 20-DEC-07:10 |
Annual Sum or Average | 1800307.77 | 917.62 | ||||||
Minimum of Months | 134744.02 | 865149.10 | 24.12 | 21.10 | 0.00 | 0.00 | ||
Maximum of Months | 4315494.17 | 7769164.25 | 34.64 | 29.23 | 4513.33 | 150466.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.867365E+09 | 0.00 | 0.353548E+11 | 0.430393E+10 | 0.00 | 0.00 |
February | 0.133680E+09 | 0.00 | 0.573693E+11 | 0.570203E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.118679E+12 | 0.101832E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.183300E+12 | 0.142576E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.230600E+12 | 0.140055E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.269042E+12 | 0.150482E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.304134E+12 | 0.148912E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.325617E+12 | 0.181200E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.230672E+12 | 0.107714E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.150565E+12 | 0.100575E+11 | 0.00 | 0.00 |
November | 132.82 | 0.00 | 0.951329E+11 | 0.809471E+10 | 0.00 | 0.00 |
December | 0.180409E+09 | 0.00 | 0.563994E+11 | 0.653578E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.118146E+10 | 0.00 | 0.205687E+13 | 0.131971E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.353548E+11 | 0.430393E+10 | 0.00 | 0.00 |
Maximum of Months | 0.867365E+09 | 0.00 | 0.325617E+12 | 0.181200E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.226721E+11 | 0.00 | 0.213288E+12 | 0.284888E+11 | 0.00 | 0.00 |
February | 0.328238E+10 | 0.00 | 0.394497E+12 | 0.365225E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.912140E+12 | 0.697523E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.148036E+13 | 0.992102E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.217701E+13 | 0.122479E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.246879E+13 | 0.122460E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.268963E+13 | 0.107713E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.265652E+13 | 0.108312E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.205024E+13 | 0.865482E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125583E+13 | 0.740325E+11 | 0.00 | 0.00 |
November | 56623638.90 | 0.00 | 0.688929E+12 | 0.502172E+11 | 0.00 | 0.00 |
December | 0.594874E+10 | 0.00 | 0.295893E+12 | 0.330306E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.319598E+11 | 0.00 | 0.172831E+14 | 0.938767E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.213288E+12 | 0.284888E+11 | 0.00 | 0.00 |
Maximum of Months | 0.226721E+11 | 0.00 | 0.268963E+13 | 0.122479E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.761252E+10 | 0.00 | 0.171369E+11 | 0.273062E+10 | 0.00 | 0.00 |
February | 0.131580E+10 | 0.00 | 0.355236E+11 | 0.320840E+10 | 0.00 | 0.00 |
March | 192621.73 | 0.00 | 0.927577E+11 | 0.655323E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.161998E+12 | 0.105617E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.240181E+12 | 0.134805E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.269394E+12 | 0.135163E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.286653E+12 | 0.115352E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.279913E+12 | 0.111741E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.213511E+12 | 0.885346E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126691E+12 | 0.711950E+10 | 0.00 | 0.00 |
November | 0.113977E+09 | 0.00 | 0.633493E+11 | 0.441676E+10 | 0.00 | 0.00 |
December | 0.283256E+10 | 0.00 | 0.225841E+11 | 0.280344E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.118750E+11 | 0.00 | 0.180969E+13 | 0.959532E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.171369E+11 | 0.273062E+10 | 0.00 | 0.00 |
Maximum of Months | 0.761252E+10 | 0.00 | 0.286653E+12 | 0.135163E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.477690E+11 | 0.138584E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.507354E+11 | 0.125430E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.717589E+11 | 0.143251E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.856445E+11 | 0.139833E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.110139E+12 | 0.151541E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.130149E+12 | 0.151574E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.151440E+12 | 0.156105E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.170051E+12 | 0.167288E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.131707E+12 | 0.154565E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.946407E+11 | 0.154986E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.722175E+11 | 0.148059E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.564779E+11 | 0.143555E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117273E+13 | 0.177477E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.477690E+11 | 0.125430E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.170051E+12 | 0.167288E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.416285E+12 | 0.188551E+12 | 0.00 | 4.45 |
February | 0.00 | 0.00 | 0.662007E+12 | 0.230190E+12 | 0.00 | 4.90 |
March | 0.00 | 0.00 | 0.106809E+13 | 0.336184E+12 | 0.00 | 2.60 |
April | 0.00 | 0.00 | 0.137181E+13 | 0.431928E+12 | 0.00 | 0.34 |
May | 0.00 | 0.00 | 0.498906E+12 | 0.232896E+12 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.823357E+12 | 0.318324E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.118446E+13 | 0.407073E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.145667E+13 | 0.454060E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.487292E+12 | 0.214632E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.782628E+12 | 0.279031E+12 | 0.00 | 0.51 |
November | 0.00 | 0.00 | 0.102735E+13 | 0.317595E+12 | 0.00 | 5.18 |
December | 0.00 | 0.00 | 0.134543E+13 | 0.378607E+12 | 0.00 | 13.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.111243E+14 | 0.378907E+13 | 0.00 | 30.99 |
Minimum of Months | 0.00 | 0.00 | 0.416285E+12 | 0.188551E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.145667E+13 | 0.454060E+12 | 0.00 | 13.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.581134E+10 | 0.258155E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.117764E+11 | 0.362306E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.206905E+11 | 0.592654E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.280882E+11 | 0.836426E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.100152E+11 | 0.412721E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.169682E+11 | 0.592991E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.246142E+11 | 0.775222E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.306757E+11 | 0.901184E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.972297E+10 | 0.374467E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.152297E+11 | 0.492482E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.195201E+11 | 0.538756E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.250103E+11 | 0.607876E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.218123E+12 | 0.674524E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.581134E+10 | 0.258155E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.306757E+11 | 0.901184E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.385027E+11 | 0.214878E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.103766E+12 | 0.329714E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.194799E+12 | 0.558840E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.264103E+12 | 0.785565E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.945206E+11 | 0.390329E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.161565E+12 | 0.563003E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.233986E+12 | 0.734447E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.287387E+12 | 0.843598E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.909187E+11 | 0.352129E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.143137E+12 | 0.464113E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.180578E+12 | 0.502409E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.225901E+12 | 0.557615E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.201917E+13 | 0.629664E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.385027E+11 | 0.214878E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.287387E+12 | 0.843598E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.251818E+10 | 0.191205E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.965765E+10 | 0.319453E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.193508E+11 | 0.560962E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.267480E+11 | 0.800000E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.979788E+10 | 0.402059E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.164865E+11 | 0.575235E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.237554E+11 | 0.748112E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.293353E+11 | 0.865291E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.925472E+10 | 0.358476E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.142781E+11 | 0.467139E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.175368E+11 | 0.497189E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.213115E+11 | 0.540882E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200031E+12 | 0.632600E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.251818E+10 | 0.191205E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.293353E+11 | 0.865291E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.430393E+10 | 0.353548E+11 | 0.867365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.570203E+10 | 0.573693E+11 | 0.133680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101832E+11 | 0.118679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142576E+11 | 0.183300E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140055E+11 | 0.230600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150482E+11 | 0.269042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148912E+11 | 0.304134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181200E+11 | 0.325617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107714E+11 | 0.230672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100575E+11 | 0.150565E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.809471E+10 | 0.951329E+11 | 132.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.653578E+10 | 0.563994E+11 | 0.180409E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131971E+12 | 0.205687E+13 | 0.118146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.430393E+10 | 0.353548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181200E+11 | 0.325617E+12 | 0.867365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.284888E+11 | 0.213288E+12 | 0.226721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.365225E+11 | 0.394497E+12 | 0.328238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.697523E+11 | 0.912140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.992102E+11 | 0.148036E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122479E+12 | 0.217701E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122460E+12 | 0.246879E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107713E+12 | 0.268963E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108312E+12 | 0.265652E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.865482E+11 | 0.205024E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.740325E+11 | 0.125583E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.502172E+11 | 0.688929E+12 | 56623638.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330306E+11 | 0.295893E+12 | 0.594874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.938767E+12 | 0.172831E+14 | 0.319598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.284888E+11 | 0.213288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122479E+12 | 0.268963E+13 | 0.226721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.273062E+10 | 0.171369E+11 | 0.761252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.320840E+10 | 0.355236E+11 | 0.131580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.655323E+10 | 0.927577E+11 | 192621.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105617E+11 | 0.161998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134805E+11 | 0.240181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135163E+11 | 0.269394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115352E+11 | 0.286653E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111741E+11 | 0.279913E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.885346E+10 | 0.213511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.711950E+10 | 0.126691E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.441676E+10 | 0.633493E+11 | 0.113977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280344E+10 | 0.225841E+11 | 0.283256E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.959532E+11 | 0.180969E+13 | 0.118750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.273062E+10 | 0.171369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135163E+11 | 0.286653E+12 | 0.761252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138584E+11 | 0.477690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125430E+11 | 0.507354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143251E+11 | 0.717589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139833E+11 | 0.856445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151541E+11 | 0.110139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151574E+11 | 0.130149E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156105E+11 | 0.151440E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167288E+11 | 0.170051E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154565E+11 | 0.131707E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154986E+11 | 0.946407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148059E+11 | 0.722175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143555E+11 | 0.564779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177477E+12 | 0.117273E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125430E+11 | 0.477690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167288E+11 | 0.170051E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.966097E+11 | 0.336305E+12 | 0.00 | 0.00 | 0.00 | 0.119078E+11 | 0.00 | 0.00 |
February | 0.872603E+11 | 0.532262E+12 | 0.00 | 0.00 | 0.00 | 0.131257E+11 | 0.00 | 0.00 |
March | 0.966097E+11 | 0.835510E+12 | 0.00 | 0.00 | 0.00 | 0.696444E+10 | 0.00 | 0.00 |
April | 0.934932E+11 | 0.103429E+13 | 0.00 | 0.00 | 0.00 | 0.911656E+09 | 0.00 | 0.00 |
May | 0.966097E+11 | 0.362635E+12 | 0.00 | 0.00 | 0.00 | 15702495.21 | 0.00 | 0.00 |
June | 0.934932E+11 | 0.598526E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.966097E+11 | 0.873995E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.966097E+11 | 0.109922E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.934932E+11 | 0.366153E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.966097E+11 | 0.601573E+12 | 0.00 | 0.00 | 0.00 | 0.135924E+10 | 0.00 | 0.00 |
November | 0.934932E+11 | 0.817176E+12 | 0.00 | 0.00 | 0.00 | 0.138607E+11 | 0.00 | 0.00 |
December | 0.966097E+11 | 0.109837E+13 | 0.00 | 0.00 | 0.00 | 0.347831E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.113750E+13 | 0.855601E+13 | 0.00 | 0.00 | 0.00 | 0.829283E+11 | 0.00 | 0.00 |
Minimum of Months | 0.872603E+11 | 0.336305E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.966097E+11 | 0.109922E+13 | 0.00 | 0.00 | 0.00 | 0.347831E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144599E+10 | 0.467578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130606E+10 | 0.945940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144599E+10 | 0.162099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139935E+10 | 0.211233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144599E+10 | 0.733398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139935E+10 | 0.124376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144599E+10 | 0.183080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144599E+10 | 0.231099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139935E+10 | 0.737764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144599E+10 | 0.117509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139935E+10 | 0.155319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144599E+10 | 0.203775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170254E+11 | 0.167696E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130606E+10 | 0.467578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144599E+10 | 0.231099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138086E+11 | 0.308234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124722E+11 | 0.832671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138086E+11 | 0.152724E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133631E+11 | 0.198910E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138086E+11 | 0.692963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133631E+11 | 0.118628E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138086E+11 | 0.174350E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138086E+11 | 0.216836E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133631E+11 | 0.690689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138086E+11 | 0.110534E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133631E+11 | 0.143700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138086E+11 | 0.183948E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162585E+12 | 0.155209E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124722E+11 | 0.308234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138086E+11 | 0.216836E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139572E+10 | 0.200185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126065E+10 | 0.772377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139572E+10 | 0.151369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135070E+10 | 0.200987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139572E+10 | 0.717301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135070E+10 | 0.120849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139572E+10 | 0.176700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139572E+10 | 0.220781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135070E+10 | 0.702066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139572E+10 | 0.110025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135070E+10 | 0.139156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139572E+10 | 0.172984E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164335E+11 | 0.153204E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126065E+10 | 0.200185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139572E+10 | 0.220781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.430393E+10 | 0.867365E+09 | 0.353548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.570203E+10 | 0.133680E+09 | 0.573693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101832E+11 | 0.00 | 0.118679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142576E+11 | 0.00 | 0.183300E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140055E+11 | 0.00 | 0.230600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150482E+11 | 0.00 | 0.269042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148912E+11 | 0.00 | 0.304134E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181200E+11 | 0.00 | 0.325617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107714E+11 | 0.00 | 0.230672E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100575E+11 | 0.00 | 0.150565E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.809471E+10 | 132.82 | 0.951329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.653578E+10 | 0.180409E+09 | 0.563994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131971E+12 | 0.118146E+10 | 0.205687E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.430393E+10 | 0.00 | 0.353548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181200E+11 | 0.867365E+09 | 0.325617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.284888E+11 | 0.226721E+11 | 0.213288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.365225E+11 | 0.328238E+10 | 0.394497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.697523E+11 | 0.00 | 0.912140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.992102E+11 | 0.00 | 0.148036E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122479E+12 | 0.00 | 0.217701E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122460E+12 | 0.00 | 0.246879E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107713E+12 | 0.00 | 0.268963E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108312E+12 | 0.00 | 0.265652E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.865482E+11 | 0.00 | 0.205024E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.740325E+11 | 0.00 | 0.125583E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.502172E+11 | 56623638.90 | 0.688929E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.330306E+11 | 0.594874E+10 | 0.295893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.938767E+12 | 0.319598E+11 | 0.172831E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.284888E+11 | 0.00 | 0.213288E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.122479E+12 | 0.226721E+11 | 0.268963E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.273062E+10 | 0.761252E+10 | 0.171369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.320840E+10 | 0.131580E+10 | 0.355236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.655323E+10 | 192621.73 | 0.927577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105617E+11 | 0.00 | 0.161998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134805E+11 | 0.00 | 0.240181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135163E+11 | 0.00 | 0.269394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115352E+11 | 0.00 | 0.286653E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111741E+11 | 0.00 | 0.279913E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.885346E+10 | 0.00 | 0.213511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.711950E+10 | 0.00 | 0.126691E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.441676E+10 | 0.113977E+09 | 0.633493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280344E+10 | 0.283256E+10 | 0.225841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.959532E+11 | 0.118750E+11 | 0.180969E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.273062E+10 | 0.00 | 0.171369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135163E+11 | 0.761252E+10 | 0.286653E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138584E+11 | 0.00 | 0.477690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125430E+11 | 0.00 | 0.507354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143251E+11 | 0.00 | 0.717589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139833E+11 | 0.00 | 0.856445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151541E+11 | 0.00 | 0.110139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151574E+11 | 0.00 | 0.130149E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156105E+11 | 0.00 | 0.151440E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167288E+11 | 0.00 | 0.170051E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154565E+11 | 0.00 | 0.131707E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154986E+11 | 0.00 | 0.946407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148059E+11 | 0.00 | 0.722175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143555E+11 | 0.00 | 0.564779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177477E+12 | 0.00 | 0.117273E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125430E+11 | 0.00 | 0.477690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167288E+11 | 0.00 | 0.170051E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.966097E+11 | 0.00 | 0.416285E+12 | 0.00 | 0.799796E+11 | 0.00 | 0.00 | 0.00 | 0.119614E+11 | 0.00 | 0.00 | 0.00 |
February | 0.872603E+11 | 0.00 | 0.662007E+12 | 0.00 | 0.129745E+12 | 0.00 | 0.00 | 0.00 | 0.131848E+11 | 0.00 | 0.00 | 0.00 |
March | 0.966097E+11 | 0.00 | 0.106809E+13 | 0.00 | 0.232579E+12 | 0.00 | 0.00 | 0.00 | 0.699579E+10 | 0.00 | 0.00 | 0.00 |
April | 0.934932E+11 | 0.00 | 0.137181E+13 | 0.00 | 0.337519E+12 | 0.00 | 0.00 | 0.00 | 0.915760E+09 | 0.00 | 0.00 | 0.00 |
May | 0.966097E+11 | 0.00 | 0.498906E+12 | 0.00 | 0.136271E+12 | 0.00 | 0.00 | 0.00 | 15773178.50 | 0.00 | 0.00 | 0.00 |
June | 0.934932E+11 | 0.00 | 0.823357E+12 | 0.00 | 0.224831E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.966097E+11 | 0.00 | 0.118446E+13 | 0.00 | 0.310463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.966097E+11 | 0.00 | 0.145667E+13 | 0.00 | 0.357451E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.934932E+11 | 0.00 | 0.487292E+12 | 0.00 | 0.121139E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.966097E+11 | 0.00 | 0.782628E+12 | 0.00 | 0.181056E+12 | 0.00 | 0.00 | 0.00 | 0.136535E+10 | 0.00 | 0.00 | 0.00 |
November | 0.934932E+11 | 0.00 | 0.102735E+13 | 0.00 | 0.210178E+12 | 0.00 | 0.00 | 0.00 | 0.139231E+11 | 0.00 | 0.00 | 0.00 |
December | 0.966097E+11 | 0.00 | 0.134543E+13 | 0.00 | 0.247058E+12 | 0.00 | 0.00 | 0.00 | 0.349397E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113750E+13 | 0.00 | 0.111243E+14 | 0.00 | 0.256827E+13 | 0.00 | 0.00 | 0.00 | 0.833016E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.872603E+11 | 0.00 | 0.416285E+12 | 0.00 | 0.799796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.966097E+11 | 0.00 | 0.145667E+13 | 0.00 | 0.357451E+12 | 0.00 | 0.00 | 0.00 | 0.349397E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144599E+10 | 0.00 | 0.581134E+10 | 0.00 | 0.113556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130606E+10 | 0.00 | 0.117764E+11 | 0.00 | 0.231700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144599E+10 | 0.00 | 0.206905E+11 | 0.00 | 0.448055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139935E+10 | 0.00 | 0.280882E+11 | 0.00 | 0.696492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144599E+10 | 0.00 | 0.100152E+11 | 0.00 | 0.268122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139935E+10 | 0.00 | 0.169682E+11 | 0.00 | 0.453057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144599E+10 | 0.00 | 0.246142E+11 | 0.00 | 0.630623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144599E+10 | 0.00 | 0.306757E+11 | 0.00 | 0.756585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139935E+10 | 0.00 | 0.972297E+10 | 0.00 | 0.234532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144599E+10 | 0.00 | 0.152297E+11 | 0.00 | 0.347882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139935E+10 | 0.00 | 0.195201E+11 | 0.00 | 0.398822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144599E+10 | 0.00 | 0.250103E+11 | 0.00 | 0.463277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170254E+11 | 0.00 | 0.218123E+12 | 0.00 | 0.504270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130606E+10 | 0.00 | 0.581134E+10 | 0.00 | 0.113556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144599E+10 | 0.00 | 0.306757E+11 | 0.00 | 0.756585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138086E+11 | 0.00 | 0.385027E+11 | 0.00 | 0.767928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124722E+11 | 0.00 | 0.103766E+12 | 0.00 | 0.204991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138086E+11 | 0.00 | 0.194799E+12 | 0.00 | 0.420755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133631E+11 | 0.00 | 0.264103E+12 | 0.00 | 0.651934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138086E+11 | 0.00 | 0.945206E+11 | 0.00 | 0.252243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133631E+11 | 0.00 | 0.161565E+12 | 0.00 | 0.429372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138086E+11 | 0.00 | 0.233986E+12 | 0.00 | 0.596361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138086E+11 | 0.00 | 0.287387E+12 | 0.00 | 0.705513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133631E+11 | 0.00 | 0.909187E+11 | 0.00 | 0.218498E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138086E+11 | 0.00 | 0.143137E+12 | 0.00 | 0.326028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133631E+11 | 0.00 | 0.180578E+12 | 0.00 | 0.368778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138086E+11 | 0.00 | 0.225901E+12 | 0.00 | 0.419530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162585E+12 | 0.00 | 0.201917E+13 | 0.00 | 0.467080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124722E+11 | 0.00 | 0.385027E+11 | 0.00 | 0.767928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138086E+11 | 0.00 | 0.287387E+12 | 0.00 | 0.705513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.139572E+10 | 0.00 | 0.251818E+10 | 0.00 | 0.516330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126065E+10 | 0.00 | 0.965765E+10 | 0.00 | 0.193388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139572E+10 | 0.00 | 0.193508E+11 | 0.00 | 0.421390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135070E+10 | 0.00 | 0.267480E+11 | 0.00 | 0.664930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139572E+10 | 0.00 | 0.979788E+10 | 0.00 | 0.262487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135070E+10 | 0.00 | 0.164865E+11 | 0.00 | 0.440165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139572E+10 | 0.00 | 0.237554E+11 | 0.00 | 0.608539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139572E+10 | 0.00 | 0.293353E+11 | 0.00 | 0.725718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135070E+10 | 0.00 | 0.925472E+10 | 0.00 | 0.223406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139572E+10 | 0.00 | 0.142781E+11 | 0.00 | 0.327567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135070E+10 | 0.00 | 0.175368E+11 | 0.00 | 0.362119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139572E+10 | 0.00 | 0.213115E+11 | 0.00 | 0.401309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164335E+11 | 0.00 | 0.200031E+12 | 0.00 | 0.468265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126065E+10 | 0.00 | 0.251818E+10 | 0.00 | 0.516330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139572E+10 | 0.00 | 0.293353E+11 | 0.00 | 0.725718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168020E+10 | 0.00 | 0.00 | 0.112168E+09 | 0.00 | 0.00 | 0.242161E+11 | 0.00 | 0.37 |
February | 0.576298E+09 | 0.00 | 0.00 | 0.104515E+09 | 0.00 | 0.00 | 0.156938E+11 | 0.00 | 0.37 |
March | 0.174566E+09 | 0.152274E+10 | 0.00 | 94409895.08 | 27104569.01 | 0.00 | 0.785669E+10 | 0.00 | 0.39 |
April | 26100822.26 | 0.109257E+11 | 0.00 | 24473434.98 | 0.285441E+09 | 0.00 | 0.529483E+09 | 0.00 | 0.39 |
May | 10476109.81 | 0.302970E+11 | 0.00 | 3388102.87 | 0.537874E+09 | 0.00 | 58517546.87 | 0.00 | 0.41 |
June | 0.00 | 0.470691E+11 | 0.00 | 190300.18 | 0.842525E+09 | 0.00 | 106500.05 | 0.00 | 0.43 |
July | 0.00 | 0.645582E+11 | 0.00 | 0.00 | 0.153502E+10 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.719470E+11 | 0.00 | 0.00 | 0.112284E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.466888E+11 | 0.00 | 0.00 | 0.109925E+10 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.229255E+09 | 0.905862E+10 | 0.00 | 58074481.57 | 0.139597E+09 | 0.00 | 0.254178E+10 | 0.00 | 0.42 |
November | 0.112665E+10 | 0.242446E+09 | 0.00 | 0.137775E+09 | 20982239.87 | 0.00 | 0.121313E+11 | 0.00 | 0.41 |
December | 0.124048E+10 | 0.00 | 0.00 | 0.128990E+09 | 0.00 | 0.00 | 0.229402E+11 | 0.00 | 0.38 |
Annual Sum or Average | 0.506402E+10 | 0.282310E+12 | 0.00 | 0.663984E+09 | 0.561063E+10 | 0.00 | 0.859679E+11 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.168020E+10 | 0.719470E+11 | 0.00 | 0.137775E+09 | 0.153502E+10 | 0.00 | 0.242161E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121013E+10 | 0.00 | 0.00 | 75599440.96 | 0.00 | 0.00 | 0.253638E+11 | 0.00 | 0.38 |
February | 0.110946E+10 | 0.00 | 0.00 | 83016601.85 | 840609.06 | 0.00 | 0.168263E+11 | 0.00 | 0.38 |
March | 0.175900E+10 | 0.106928E+10 | 0.00 | 89507041.37 | 0.352960E+09 | 0.00 | 0.885380E+10 | 0.00 | 0.41 |
April | 0.810046E+09 | 0.655304E+10 | 0.00 | 27932229.29 | 0.348361E+10 | 0.00 | 0.846556E+09 | 0.00 | 0.44 |
May | 29305065.58 | 0.224489E+11 | 0.00 | 910256.17 | 0.106752E+11 | 0.00 | 16627746.34 | 0.00 | 0.43 |
June | 0.00 | 0.342802E+11 | 0.00 | 0.00 | 0.189242E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.442854E+11 | 0.00 | 0.00 | 0.317074E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.505723E+11 | 0.00 | 0.00 | 0.282277E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.341289E+11 | 0.00 | 0.00 | 0.197159E+11 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 0.738477E+09 | 0.723820E+10 | 0.00 | 35275509.16 | 0.180673E+10 | 0.00 | 0.246750E+10 | 0.00 | 0.40 |
November | 0.148798E+10 | 0.166064E+09 | 0.00 | 0.101259E+09 | 73574516.26 | 0.00 | 0.126800E+11 | 0.00 | 0.39 |
December | 0.141342E+10 | 0.00 | 0.00 | 99860700.25 | 0.00 | 0.00 | 0.245125E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.855781E+10 | 0.200742E+12 | 0.00 | 0.513360E+09 | 0.114968E+12 | 0.00 | 0.915671E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.175900E+10 | 0.505723E+11 | 0.00 | 0.101259E+09 | 0.317074E+11 | 0.00 | 0.253638E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.866874E+11 | 0.00 | 0.00 | 0.330628E+09 | 0.00 | 38030790.24 | 0.127476E+12 | 0.00 | 0.33 |
February | 0.208261E+11 | 0.00 | 0.00 | 0.523033E+09 | 90965112.52 | 0.00 | 0.129148E+12 | 0.00 | 0.35 |
March | 0.682761E+10 | 0.105922E+11 | 0.00 | 0.698212E+09 | 0.359422E+10 | 0.00 | 0.818390E+11 | 0.00 | 0.36 |
April | 0.263924E+10 | 0.616926E+11 | 0.00 | 0.210325E+09 | 0.362346E+11 | 0.00 | 0.671668E+10 | 0.00 | 0.39 |
May | 0.288315E+09 | 0.214937E+12 | 0.00 | 5011448.46 | 0.103997E+12 | 0.00 | 0.125132E+09 | 0.00 | 0.42 |
June | 0.00 | 0.325538E+12 | 0.00 | 0.00 | 0.171174E+12 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.412817E+12 | 0.00 | 0.00 | 0.275609E+12 | 0.00 | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.470581E+12 | 0.00 | 0.00 | 0.219705E+12 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.330194E+12 | 0.00 | 0.00 | 0.145915E+12 | 0.00 | 0.00 | 0.00 | 0.38 |
October | 0.245250E+10 | 0.700963E+11 | 0.00 | 0.284009E+09 | 0.144134E+11 | 0.00 | 0.235542E+11 | 0.00 | 0.35 |
November | 0.106025E+11 | 0.149826E+10 | 0.00 | 0.687135E+09 | 0.106134E+10 | 0.00 | 0.106905E+12 | 0.00 | 0.36 |
December | 0.367007E+11 | 0.00 | 0.00 | 0.469941E+09 | 30282339.82 | 0.00 | 0.164711E+12 | 0.00 | 0.35 |
Annual Sum or Average | 0.167024E+12 | 0.189795E+13 | 0.00 | 0.320829E+10 | 0.971825E+12 | 38030790.24 | 0.640474E+12 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.866874E+11 | 0.470581E+12 | 0.00 | 0.698212E+09 | 0.275609E+12 | 38030790.24 | 0.164711E+12 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130900E+11 | 0.00 | 0.00 | 12665305.24 | 0.00 | 0.451565E+09 | 0.515423E+10 | 0.00 | 0.32 |
February | 0.526887E+10 | 0.00 | 0.00 | 32008238.40 | 427230.64 | 0.00 | 0.765465E+10 | 0.00 | 0.33 |
March | 0.107251E+10 | 0.771526E+09 | 0.00 | 60259322.28 | 0.213502E+09 | 0.00 | 0.685376E+10 | 0.00 | 0.34 |
April | 0.239440E+09 | 0.551691E+10 | 0.00 | 24920082.81 | 0.312720E+10 | 0.00 | 0.720233E+09 | 0.00 | 0.38 |
May | 23172331.31 | 0.212410E+11 | 0.00 | 509162.18 | 0.921805E+10 | 0.00 | 12415452.45 | 0.00 | 0.42 |
June | 0.00 | 0.325319E+11 | 0.00 | 0.00 | 0.160834E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.415495E+11 | 0.00 | 0.00 | 0.263881E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.469957E+11 | 0.00 | 0.00 | 0.212306E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.326744E+11 | 0.00 | 0.00 | 0.140744E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
October | 0.250957E+09 | 0.626863E+10 | 0.00 | 24628796.07 | 0.121254E+10 | 0.00 | 0.184637E+10 | 0.00 | 0.34 |
November | 0.290135E+10 | 45804910.01 | 0.00 | 49706317.71 | 65620112.99 | 0.00 | 0.681895E+10 | 0.00 | 0.33 |
December | 0.102152E+11 | 0.00 | 0.00 | 19988288.16 | 963444.86 | 0.00 | 0.649304E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.330615E+11 | 0.187595E+12 | 0.00 | 0.224686E+09 | 0.916147E+11 | 0.451565E+09 | 0.355537E+11 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.130900E+11 | 0.469957E+11 | 0.00 | 60259322.28 | 0.263881E+11 | 0.451565E+09 | 0.765465E+10 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177279E+10 | 0.00 | 0.00 | 2010201.95 | 0.00 | 0.00 | 0.510651E+09 | 0.00 | 0.26 |
February | 0.815795E+09 | 0.00 | 0.00 | 5225813.12 | 105686.89 | 0.00 | 0.782651E+09 | 0.00 | 0.29 |
March | 0.348357E+09 | 0.204092E+09 | 0.00 | 9381330.94 | 43596126.46 | 0.00 | 0.802181E+09 | 0.00 | 0.42 |
April | 0.106666E+09 | 0.164531E+10 | 0.00 | 4401520.84 | 0.310032E+09 | 0.00 | 0.110709E+09 | 0.00 | 0.60 |
May | 3071301.05 | 0.634303E+10 | 0.00 | 290206.49 | 0.844286E+09 | 0.00 | 4870719.71 | 0.00 | 0.71 |
June | 0.00 | 0.997277E+10 | 0.00 | 0.00 | 0.144408E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
July | 0.00 | 0.131042E+11 | 0.00 | 0.00 | 0.211315E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.124279E+11 | 0.00 | 0.00 | 0.241056E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.732713E+10 | 0.00 | 0.00 | 0.209170E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 0.118615E+09 | 0.128490E+10 | 0.00 | 3301963.45 | 0.209097E+09 | 0.00 | 0.207053E+09 | 0.00 | 0.45 |
November | 0.467403E+09 | 25101756.91 | 0.00 | 8007496.21 | 9250271.43 | 0.00 | 0.778109E+09 | 0.00 | 0.31 |
December | 0.126561E+10 | 0.00 | 0.00 | 4275968.25 | 0.00 | 0.00 | 0.755780E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.489830E+10 | 0.523344E+11 | 0.00 | 36894501.25 | 0.947586E+10 | 0.00 | 0.395200E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.177279E+10 | 0.131042E+11 | 0.00 | 9381330.94 | 0.241056E+10 | 0.00 | 0.802181E+09 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.868186E+09 | 0.00 | 0.00 | 3199213.78 | 0.00 | 0.00 | 0.891750E+09 | 0.00 | 0.31 |
February | 0.416710E+09 | 0.00 | 0.00 | 5761620.46 | 68007.72 | 0.00 | 0.939028E+09 | 0.00 | 0.38 |
March | 0.216676E+09 | 0.168567E+09 | 0.00 | 9057638.13 | 19721662.87 | 0.00 | 0.759588E+09 | 0.00 | 0.54 |
April | 62001484.43 | 0.137953E+10 | 0.00 | 4380519.41 | 0.182215E+09 | 0.00 | 0.114803E+09 | 0.00 | 0.74 |
May | 1816325.92 | 0.532946E+10 | 0.00 | 213512.78 | 0.463584E+09 | 0.00 | 3609369.37 | 0.00 | 0.90 |
June | 0.00 | 0.729761E+10 | 0.00 | 0.00 | 0.895712E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
July | 0.00 | 0.879031E+10 | 0.00 | 0.00 | 0.148462E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
August | 0.00 | 0.762778E+10 | 0.00 | 0.00 | 0.175519E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.552421E+10 | 0.00 | 0.00 | 0.130886E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
October | 69909735.75 | 0.103678E+10 | 0.00 | 3470794.55 | 0.112289E+09 | 0.00 | 0.198924E+09 | 0.00 | 0.56 |
November | 0.281397E+09 | 18883003.98 | 0.00 | 7366511.41 | 5952392.49 | 0.00 | 0.724076E+09 | 0.00 | 0.39 |
December | 0.756046E+09 | 0.00 | 0.00 | 3943949.00 | 0.00 | 0.00 | 0.726242E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.267274E+10 | 0.371731E+11 | 0.00 | 37393759.52 | 0.622822E+10 | 0.00 | 0.435802E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.868186E+09 | 0.879031E+10 | 0.00 | 9057638.13 | 0.175519E+10 | 0.00 | 0.939028E+09 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.978317E+09 | 0.00 | 0.00 | 12206625.32 | 0.00 | 4458468.79 | 0.311858E+10 | 0.00 | 0.53 |
February | 0.565667E+09 | 202142.28 | 0.00 | 16679211.09 | 12937.09 | 0.00 | 0.214723E+10 | 0.00 | 0.55 |
March | 0.279396E+09 | 0.394897E+09 | 0.00 | 16802290.56 | 17207336.37 | 0.00 | 0.136756E+10 | 0.00 | 0.64 |
April | 98025572.49 | 0.225346E+10 | 0.00 | 5940010.08 | 0.211138E+09 | 0.00 | 0.141608E+09 | 0.00 | 0.73 |
May | 3054874.69 | 0.678860E+10 | 0.00 | 305654.97 | 0.779592E+09 | 0.00 | 4994641.51 | 0.00 | 0.75 |
June | 0.00 | 0.993162E+10 | 0.00 | 0.00 | 0.143581E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
July | 0.00 | 0.131713E+11 | 0.00 | 0.00 | 0.212093E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
August | 0.00 | 0.131742E+11 | 0.00 | 0.00 | 0.229758E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
September | 0.00 | 0.959912E+10 | 0.00 | 0.00 | 0.169403E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
October | 87978870.56 | 0.236445E+10 | 0.00 | 8661993.73 | 0.107401E+09 | 0.00 | 0.369363E+09 | 0.00 | 0.75 |
November | 0.258592E+09 | 77167074.49 | 0.00 | 27711500.58 | 2392316.02 | 0.00 | 0.212031E+10 | 0.00 | 0.68 |
December | 0.681668E+09 | 0.00 | 0.00 | 17078212.41 | 0.00 | 0.00 | 0.303057E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.295270E+10 | 0.577550E+11 | 0.00 | 0.105385E+09 | 0.866610E+10 | 4458468.79 | 0.123002E+11 | 0.00 | 0.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.978317E+09 | 0.131742E+11 | 0.00 | 27711500.58 | 0.229758E+10 | 4458468.79 | 0.311858E+10 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.567467E+09 | 0.00 | 0.00 | 5626345.79 | 0.00 | 0.00 | 0.157791E+10 | 0.00 | 0.42 |
February | 0.170052E+09 | 208861.52 | 0.00 | 10608578.62 | 0.00 | 0.00 | 0.168095E+10 | 0.00 | 0.57 |
March | 78736430.55 | 0.347630E+09 | 0.00 | 16220649.71 | 2458106.71 | 0.00 | 0.147924E+10 | 0.00 | 0.87 |
April | 9744154.07 | 0.277123E+10 | 0.00 | 9297767.92 | 16672217.19 | 0.00 | 0.264991E+09 | 0.00 | 1.30 |
May | 110806.01 | 0.712113E+10 | 0.00 | 422324.12 | 0.145255E+09 | 0.00 | 7272465.57 | 0.00 | 1.12 |
June | 0.00 | 0.115559E+11 | 0.00 | 0.00 | 0.263970E+09 | 0.00 | 0.00 | 0.00 | 1.19 |
July | 0.00 | 0.155658E+11 | 0.00 | 0.00 | 0.244958E+09 | 0.00 | 0.00 | 0.00 | 1.14 |
August | 0.00 | 0.178276E+11 | 0.00 | 0.00 | 0.183119E+09 | 0.00 | 0.00 | 0.00 | 1.27 |
September | 0.00 | 0.860127E+10 | 0.00 | 0.00 | 0.501186E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
October | 39773279.28 | 0.166684E+10 | 0.00 | 5837973.86 | 38170312.77 | 0.00 | 0.335595E+09 | 0.00 | 0.80 |
November | 80317334.93 | 50605804.28 | 0.00 | 16422749.51 | 682066.13 | 0.00 | 0.167845E+10 | 0.00 | 0.69 |
December | 0.120723E+09 | 0.00 | 0.00 | 12995910.87 | 0.00 | 0.00 | 0.288115E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.106692E+10 | 0.655082E+11 | 0.00 | 77432300.41 | 0.139647E+10 | 0.00 | 0.990556E+10 | 0.00 | 0.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.567467E+09 | 0.178276E+11 | 0.00 | 16422749.51 | 0.501186E+09 | 0.00 | 0.288115E+10 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179431E+11 | 0.00 | 0.00 | 1507354.49 | 0.00 | 0.512957E+10 | 0.367731E+09 | 0.00 | 0.28 |
February | 0.108754E+11 | 0.00 | 0.00 | 20275727.96 | 11425172.58 | 0.823247E+09 | 0.310322E+10 | 0.00 | 0.28 |
March | 0.362786E+10 | 0.216122E+10 | 0.00 | 63266923.88 | 0.451432E+09 | 0.00 | 0.576791E+10 | 0.00 | 0.37 |
April | 0.345654E+09 | 0.174082E+11 | 0.00 | 32248643.43 | 0.360910E+10 | 0.00 | 0.921926E+09 | 0.00 | 0.58 |
May | 25211576.65 | 0.697444E+11 | 0.00 | 2659326.55 | 0.747182E+10 | 0.00 | 55894154.44 | 0.00 | 0.76 |
June | 0.00 | 0.110196E+12 | 0.00 | 0.00 | 0.113002E+11 | 0.00 | 0.00 | 0.00 | 0.78 |
July | 0.00 | 0.142288E+12 | 0.00 | 0.00 | 0.165173E+11 | 0.00 | 0.00 | 0.00 | 0.74 |
August | 0.00 | 0.132144E+12 | 0.00 | 0.00 | 0.182447E+11 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 0.00 | 0.774351E+11 | 0.00 | 0.00 | 0.145533E+11 | 0.00 | 0.00 | 0.00 | 0.57 |
October | 0.118796E+10 | 0.129830E+11 | 0.00 | 22109218.54 | 0.168589E+10 | 0.00 | 0.132551E+10 | 0.00 | 0.41 |
November | 0.786911E+10 | 0.211902E+09 | 0.00 | 39631441.89 | 0.129356E+09 | 0.00 | 0.344066E+10 | 0.00 | 0.30 |
December | 0.179651E+11 | 0.00 | 0.00 | 3575440.66 | 3803446.72 | 0.104829E+10 | 0.119632E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.598394E+11 | 0.564571E+12 | 0.00 | 0.185274E+09 | 0.739783E+11 | 0.700110E+10 | 0.161792E+11 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.179651E+11 | 0.142288E+12 | 0.00 | 63266923.88 | 0.182447E+11 | 0.512957E+10 | 0.576791E+10 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.857450E+10 | 0.00 | 0.00 | 11369087.61 | 0.00 | 0.185866E+10 | 0.366020E+10 | 0.00 | 0.26 |
February | 0.473143E+10 | 0.00 | 0.00 | 39272432.76 | 7354486.48 | 75055204.79 | 0.724877E+10 | 0.00 | 0.37 |
March | 0.152178E+10 | 0.210312E+10 | 0.00 | 82150446.72 | 0.166251E+09 | 0.00 | 0.802308E+10 | 0.00 | 0.57 |
April | 0.131034E+09 | 0.176482E+11 | 0.00 | 39842240.64 | 0.155366E+10 | 0.00 | 0.120508E+10 | 0.00 | 0.85 |
May | 11674119.71 | 0.612866E+11 | 0.00 | 2290078.82 | 0.305878E+10 | 0.00 | 46541690.16 | 0.00 | 1.01 |
June | 0.00 | 0.863674E+11 | 0.00 | 0.00 | 0.529007E+10 | 0.00 | 0.00 | 0.00 | 0.93 |
July | 0.00 | 0.107134E+12 | 0.00 | 0.00 | 0.790865E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
August | 0.00 | 0.973906E+11 | 0.00 | 0.00 | 0.953470E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 0.00 | 0.626709E+11 | 0.00 | 0.00 | 0.715184E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.407667E+09 | 0.116319E+11 | 0.00 | 31147217.31 | 0.702009E+09 | 0.00 | 0.209244E+10 | 0.00 | 0.57 |
November | 0.341996E+10 | 0.200086E+09 | 0.00 | 56518238.14 | 83208323.88 | 0.00 | 0.646136E+10 | 0.00 | 0.41 |
December | 0.840560E+10 | 0.00 | 0.00 | 17484794.03 | 2448312.90 | 0.321530E+09 | 0.417008E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.272037E+11 | 0.446433E+12 | 0.00 | 0.280075E+09 | 0.354590E+11 | 0.225524E+10 | 0.329076E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.857450E+10 | 0.107134E+12 | 0.00 | 82150446.72 | 0.953470E+10 | 0.185866E+10 | 0.802308E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108687E+11 | 0.00 | 0.00 | 0.107020E+09 | 0.00 | 0.958484E+09 | 0.309237E+11 | 0.00 | 0.61 |
February | 0.621876E+10 | 27072473.30 | 0.00 | 0.148047E+09 | 525977.25 | 0.147874E+09 | 0.217820E+11 | 0.00 | 0.64 |
March | 0.228203E+10 | 0.476849E+10 | 0.00 | 0.150779E+09 | 0.110937E+09 | 0.00 | 0.138338E+11 | 0.00 | 0.68 |
April | 0.314869E+09 | 0.253757E+11 | 0.00 | 47791430.24 | 0.246159E+10 | 0.00 | 0.124648E+10 | 0.00 | 0.76 |
May | 24708634.46 | 0.745088E+11 | 0.00 | 2793009.08 | 0.668382E+10 | 0.00 | 57577534.78 | 0.00 | 0.80 |
June | 0.00 | 0.109171E+12 | 0.00 | 0.00 | 0.113531E+11 | 0.00 | 0.00 | 0.00 | 0.78 |
July | 0.00 | 0.144039E+12 | 0.00 | 0.00 | 0.161270E+11 | 0.00 | 0.00 | 0.00 | 0.75 |
August | 0.00 | 0.144604E+12 | 0.00 | 0.00 | 0.159968E+11 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 0.00 | 0.105852E+12 | 0.00 | 0.00 | 0.979810E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
October | 0.306502E+09 | 0.272128E+11 | 0.00 | 73667408.60 | 0.473399E+09 | 0.00 | 0.406606E+10 | 0.00 | 0.81 |
November | 0.320990E+10 | 0.102233E+10 | 0.00 | 0.268703E+09 | 24947302.11 | 0.00 | 0.227037E+11 | 0.00 | 0.84 |
December | 0.847153E+10 | 5977116.35 | 0.00 | 0.139789E+09 | 695643.25 | 0.00 | 0.314926E+11 | 0.00 | 0.65 |
Annual Sum or Average | 0.316970E+11 | 0.636589E+12 | 0.00 | 0.938590E+09 | 0.630308E+11 | 0.110636E+10 | 0.126106E+12 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.108687E+11 | 0.144604E+12 | 0.00 | 0.268703E+09 | 0.161270E+11 | 0.958484E+09 | 0.314926E+11 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108523E+11 | 0.00 | 0.00 | 17144647.05 | 0.00 | 0.147117E+10 | 0.461830E+10 | 0.00 | 0.34 |
February | 0.555723E+10 | 13103038.56 | 0.00 | 41109731.55 | 360425.10 | 0.103505E+09 | 0.628867E+10 | 0.00 | 0.40 |
March | 0.138637E+10 | 0.298411E+10 | 0.00 | 83191942.72 | 96015413.49 | 0.00 | 0.785462E+10 | 0.00 | 0.62 |
April | 0.135595E+09 | 0.221554E+11 | 0.00 | 38877164.19 | 0.675392E+09 | 0.00 | 0.103262E+10 | 0.00 | 0.95 |
May | 2781321.03 | 0.697628E+11 | 0.00 | 3207619.15 | 0.135068E+10 | 0.00 | 61738047.13 | 0.00 | 1.08 |
June | 0.00 | 0.104046E+12 | 0.00 | 0.00 | 0.265859E+10 | 0.00 | 0.00 | 0.00 | 1.07 |
July | 0.00 | 0.123075E+12 | 0.00 | 0.00 | 0.500066E+10 | 0.00 | 0.00 | 0.00 | 0.93 |
August | 0.00 | 0.117953E+12 | 0.00 | 0.00 | 0.612398E+10 | 0.00 | 0.00 | 0.00 | 0.88 |
September | 0.00 | 0.746790E+11 | 0.00 | 0.00 | 0.470829E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
October | 0.332727E+09 | 0.140335E+11 | 0.00 | 27269380.83 | 0.484406E+09 | 0.00 | 0.182932E+10 | 0.00 | 0.62 |
November | 0.314655E+10 | 0.398376E+09 | 0.00 | 65644310.16 | 44686816.16 | 0.00 | 0.635412E+10 | 0.00 | 0.46 |
December | 0.969001E+10 | 0.00 | 0.00 | 23868994.93 | 2445020.68 | 0.162563E+09 | 0.524913E+10 | 0.00 | 0.34 |
Annual Sum or Average | 0.311036E+11 | 0.529101E+12 | 0.00 | 0.300314E+09 | 0.211455E+11 | 0.173723E+10 | 0.332885E+11 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.108523E+11 | 0.123075E+12 | 0.00 | 83191942.72 | 0.612398E+10 | 0.147117E+10 | 0.785462E+10 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.141511E+10 | 0.00 | 0.00 | 102800.56 | 0.00 | 0.885430E+09 | 32583053.72 | 0.00 | 0.31 |
February | 0.100139E+10 | 0.00 | 0.00 | 1669803.05 | 53652.69 | 0.211655E+09 | 0.240478E+09 | 0.00 | 0.29 |
March | 0.348694E+09 | 0.150193E+09 | 0.00 | 6325651.00 | 25380403.74 | 0.00 | 0.569318E+09 | 0.00 | 0.36 |
April | 30912420.32 | 0.147912E+10 | 0.00 | 4309505.58 | 0.290986E+09 | 0.00 | 0.115391E+09 | 0.00 | 0.57 |
May | 2156614.77 | 0.643766E+10 | 0.00 | 241759.30 | 0.591370E+09 | 0.00 | 4571507.80 | 0.00 | 0.74 |
June | 0.00 | 0.102836E+11 | 0.00 | 0.00 | 0.951809E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
July | 0.00 | 0.137004E+11 | 0.00 | 0.00 | 0.137525E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 0.00 | 0.128019E+11 | 0.00 | 0.00 | 0.154556E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.746912E+10 | 0.00 | 0.00 | 0.129168E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.120544E+09 | 0.111346E+10 | 0.00 | 2451708.47 | 0.146505E+09 | 0.00 | 0.115461E+09 | 0.00 | 0.40 |
November | 0.738987E+09 | 6869097.76 | 0.00 | 3712658.98 | 8189740.03 | 34418656.99 | 0.293524E+09 | 0.00 | 0.29 |
December | 0.137320E+10 | 0.00 | 0.00 | 155559.99 | 120991.80 | 0.552766E+09 | 41468278.17 | 0.00 | 0.29 |
Annual Sum or Average | 0.503100E+10 | 0.534423E+11 | 0.00 | 18969446.92 | 0.622691E+10 | 0.168427E+10 | 0.141280E+10 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.141511E+10 | 0.137004E+11 | 0.00 | 6325651.00 | 0.154556E+10 | 0.885430E+09 | 0.569318E+09 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.917817E+09 | 0.00 | 0.00 | 698405.38 | 0.00 | 0.353214E+09 | 0.247513E+09 | 0.00 | 0.31 |
February | 0.447388E+09 | 0.00 | 0.00 | 3553913.32 | 34473.93 | 82626758.55 | 0.700545E+09 | 0.00 | 0.39 |
March | 0.132277E+09 | 0.143036E+09 | 0.00 | 8707716.17 | 9925577.57 | 0.00 | 0.864126E+09 | 0.00 | 0.58 |
April | 9640171.24 | 0.150178E+10 | 0.00 | 5384700.87 | 0.136883E+09 | 0.00 | 0.150818E+09 | 0.00 | 0.85 |
May | 723338.52 | 0.566238E+10 | 0.00 | 210716.58 | 0.256778E+09 | 0.00 | 4018032.76 | 0.00 | 0.99 |
June | 0.00 | 0.816529E+10 | 0.00 | 0.00 | 0.448255E+09 | 0.00 | 0.00 | 0.00 | 0.90 |
July | 0.00 | 0.103909E+11 | 0.00 | 0.00 | 0.728783E+09 | 0.00 | 0.00 | 0.00 | 0.83 |
August | 0.00 | 0.963507E+10 | 0.00 | 0.00 | 0.845884E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
September | 0.00 | 0.622335E+10 | 0.00 | 0.00 | 0.636426E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 53377246.10 | 0.103589E+10 | 0.00 | 3737209.42 | 62616034.93 | 0.00 | 0.193596E+09 | 0.00 | 0.58 |
November | 0.318494E+09 | 7596254.53 | 0.00 | 5643598.72 | 5200710.46 | 4662657.27 | 0.643985E+09 | 0.00 | 0.42 |
December | 0.765693E+09 | 0.00 | 0.00 | 1106684.10 | 77741.92 | 0.222205E+09 | 0.322958E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.264541E+10 | 0.427653E+11 | 0.00 | 29042944.55 | 0.313086E+10 | 0.662709E+09 | 0.312756E+10 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.917817E+09 | 0.103909E+11 | 0.00 | 8707716.17 | 0.845884E+09 | 0.353214E+09 | 0.864126E+09 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.898136E+09 | 0.00 | 0.00 | 8385102.97 | 0.00 | 0.408429E+09 | 0.268905E+10 | 0.00 | 0.58 |
February | 0.573998E+09 | 100496.17 | 0.00 | 13511656.39 | 13705.27 | 92495312.38 | 0.212662E+10 | 0.00 | 0.62 |
March | 0.205442E+09 | 0.297901E+09 | 0.00 | 15464651.51 | 8843027.58 | 0.00 | 0.143468E+10 | 0.00 | 0.65 |
April | 25837834.79 | 0.204990E+10 | 0.00 | 6394807.75 | 0.217599E+09 | 0.00 | 0.164144E+09 | 0.00 | 0.73 |
May | 1874642.68 | 0.680815E+10 | 0.00 | 260672.27 | 0.532076E+09 | 0.00 | 4935000.30 | 0.00 | 0.77 |
June | 0.00 | 0.101663E+11 | 0.00 | 0.00 | 0.973083E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
July | 0.00 | 0.138232E+11 | 0.00 | 0.00 | 0.135458E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
August | 0.00 | 0.138441E+11 | 0.00 | 0.00 | 0.140353E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 0.00 | 0.100002E+11 | 0.00 | 0.00 | 0.835210E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
October | 49996156.81 | 0.220530E+10 | 0.00 | 10844114.22 | 45884971.63 | 0.00 | 0.390472E+09 | 0.00 | 0.79 |
November | 0.310683E+09 | 41783686.51 | 0.00 | 26961212.36 | 2210692.67 | 0.00 | 0.231207E+10 | 0.00 | 0.82 |
December | 0.795934E+09 | 148920.26 | 0.00 | 10907991.64 | 24162.87 | 0.168476E+09 | 0.276743E+10 | 0.00 | 0.62 |
Annual Sum or Average | 0.286190E+10 | 0.592371E+11 | 0.00 | 92730209.11 | 0.537306E+10 | 0.669400E+09 | 0.118894E+11 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.898136E+09 | 0.138441E+11 | 0.00 | 26961212.36 | 0.140353E+10 | 0.408429E+09 | 0.276743E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.846304E+09 | 0.00 | 0.00 | 1412092.34 | 0.00 | 0.359766E+09 | 0.454644E+09 | 0.00 | 0.35 |
February | 0.509175E+09 | 55928.23 | 0.00 | 3794346.41 | 8801.99 | 76777069.16 | 0.601573E+09 | 0.00 | 0.40 |
March | 0.141263E+09 | 0.195907E+09 | 0.00 | 8322224.40 | 5724802.01 | 0.00 | 0.778174E+09 | 0.00 | 0.59 |
April | 10743341.84 | 0.176278E+10 | 0.00 | 5114313.49 | 64430722.99 | 0.00 | 0.127624E+09 | 0.00 | 0.90 |
May | 188588.11 | 0.613823E+10 | 0.00 | 282601.58 | 0.136340E+09 | 0.00 | 5126188.04 | 0.00 | 1.03 |
June | 0.00 | 0.939210E+10 | 0.00 | 0.00 | 0.226918E+09 | 0.00 | 0.00 | 0.00 | 1.01 |
July | 0.00 | 0.114687E+11 | 0.00 | 0.00 | 0.487128E+09 | 0.00 | 0.00 | 0.00 | 0.89 |
August | 0.00 | 0.110318E+11 | 0.00 | 0.00 | 0.582151E+09 | 0.00 | 0.00 | 0.00 | 0.84 |
September | 0.00 | 0.700783E+10 | 0.00 | 0.00 | 0.442770E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
October | 50786473.57 | 0.116213E+10 | 0.00 | 3692874.25 | 43323912.71 | 0.00 | 0.149877E+09 | 0.00 | 0.60 |
November | 0.325069E+09 | 16653437.54 | 0.00 | 6631915.44 | 3248885.31 | 0.00 | 0.593835E+09 | 0.00 | 0.45 |
December | 0.805223E+09 | 0.00 | 0.00 | 1866218.99 | 77520.67 | 0.181493E+09 | 0.466251E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.268875E+10 | 0.481762E+11 | 0.00 | 31116586.90 | 0.199212E+10 | 0.618036E+09 | 0.317710E+10 | 0.00 | 0.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.846304E+09 | 0.114687E+11 | 0.00 | 8322224.40 | 0.582151E+09 | 0.359766E+09 | 0.778174E+09 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 7500403.12 | 0.00 | 0.00 | 0.612185E+09 | 0.00 | 0.58 |
February | 0.00 | 6941747.60 | 0.00 | 16316422.02 | 0.00 | 0.00 | 0.294770E+09 | 0.00 | 0.59 |
March | 0.00 | 0.115822E+09 | 0.00 | 15664542.31 | 0.00 | 0.00 | 0.100432E+09 | 0.00 | 0.59 |
April | 0.00 | 0.342991E+09 | 0.00 | 6962093.75 | 0.00 | 0.00 | 8448157.16 | 0.00 | 0.59 |
May | 0.00 | 0.857800E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.129883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.177031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.175109E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.126527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.421971E+09 | 0.00 | 1587043.27 | 0.00 | 0.00 | 4875876.30 | 0.00 | 0.59 |
November | 0.00 | 42766459.33 | 0.00 | 22280718.58 | 0.00 | 0.00 | 0.153369E+09 | 0.00 | 0.59 |
December | 0.00 | 43649.63 | 0.00 | 41468026.94 | 0.00 | 0.00 | 0.489698E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.787384E+10 | 0.00 | 0.111779E+09 | 0.00 | 0.00 | 0.166378E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.177031E+10 | 0.00 | 41468026.94 | 0.00 | 0.00 | 0.612185E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.406912E+09 | 0.00 | 0.00 | 43919497.74 | 0.00 | 0.00 | 0.604535E+10 | 0.00 | 0.58 |
February | 0.00 | 53483751.76 | 0.00 | 0.144606E+09 | 0.00 | 0.00 | 0.313556E+10 | 0.00 | 0.59 |
March | 0.00 | 0.106437E+10 | 0.00 | 0.154990E+09 | 0.00 | 0.00 | 0.110456E+10 | 0.00 | 0.59 |
April | 0.00 | 0.321591E+10 | 0.00 | 75782423.94 | 0.00 | 0.00 | 0.103052E+09 | 0.00 | 0.59 |
May | 0.00 | 0.835485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.127687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.174722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.171977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.123366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.402032E+10 | 0.00 | 16718908.58 | 0.00 | 0.00 | 65442777.89 | 0.00 | 0.59 |
November | 0.00 | 0.372064E+09 | 0.00 | 0.211645E+09 | 0.00 | 0.00 | 0.168206E+10 | 0.00 | 0.59 |
December | 0.00 | 50513.90 | 0.00 | 0.374132E+09 | 0.00 | 0.00 | 0.510281E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.406912E+09 | 0.768562E+11 | 0.00 | 0.102179E+10 | 0.00 | 0.00 | 0.172388E+11 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.406912E+09 | 0.174722E+11 | 0.00 | 0.374132E+09 | 0.00 | 0.00 | 0.604535E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.244681E+09 | 0.00 | 0.00 | 2422678.25 | 0.00 | 0.00 | 0.405020E+09 | 0.00 | 0.58 |
February | 0.00 | 6482124.16 | 0.00 | 12926823.85 | 0.00 | 0.00 | 0.303716E+09 | 0.00 | 0.59 |
March | 0.00 | 0.115218E+09 | 0.00 | 14415857.75 | 0.00 | 0.00 | 0.102268E+09 | 0.00 | 0.59 |
April | 0.00 | 0.343754E+09 | 0.00 | 6663211.08 | 0.00 | 0.00 | 8685406.33 | 0.00 | 0.59 |
May | 0.00 | 0.854463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.129588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.176717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.176640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.125297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.418233E+09 | 0.00 | 1447162.67 | 0.00 | 0.00 | 5502289.62 | 0.00 | 0.59 |
November | 0.00 | 42238827.23 | 0.00 | 19483877.53 | 0.00 | 0.00 | 0.157903E+09 | 0.00 | 0.59 |
December | 0.00 | 37130.11 | 0.00 | 34817846.52 | 0.00 | 0.00 | 0.497295E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.244681E+09 | 0.786285E+10 | 0.00 | 92177457.65 | 0.00 | 0.00 | 0.148039E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.244681E+09 | 0.176717E+10 | 0.00 | 34817846.52 | 0.00 | 0.00 | 0.497295E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.484058E+09 | 0.00 | 0.00 | 0.140094E+11 | 0.00 | 0.66 |
February | 0.00 | 0.162520E+09 | 0.00 | 0.848603E+09 | 0.00 | 0.00 | 0.677505E+10 | 0.00 | 0.66 |
March | 0.00 | 0.247745E+10 | 0.00 | 0.753912E+09 | 0.00 | 0.00 | 0.214616E+10 | 0.00 | 0.66 |
April | 0.00 | 0.459933E+10 | 0.00 | 0.604694E+09 | 0.00 | 0.00 | 0.409065E+09 | 0.00 | 0.67 |
May | 0.00 | 0.196986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
June | 0.00 | 0.289946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.390589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.329266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.299012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.950177E+10 | 0.00 | 76653093.61 | 0.00 | 0.00 | 0.100419E+09 | 0.00 | 0.66 |
November | 0.00 | 0.896259E+09 | 0.00 | 0.109018E+10 | 0.00 | 0.00 | 0.339724E+10 | 0.00 | 0.66 |
December | 0.00 | 0.00 | 0.00 | 0.205876E+10 | 0.00 | 0.00 | 0.111931E+11 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.168217E+12 | 0.00 | 0.591686E+10 | 0.00 | 0.00 | 0.380304E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.390589E+11 | 0.00 | 0.205876E+10 | 0.00 | 0.00 | 0.140094E+11 | 0.00 | 0.68 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:50:51
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.282655E+12 | 0.283433E+10 | 0.00 | 0.805313E+12 | 0.948166E+12 |
February | 0.323502E+12 | 0.342061E+10 | 0.00 | 0.543078E+12 | 0.155968E+13 |
March | 0.429448E+12 | 0.209786E+10 | 0.00 | 0.262224E+12 | 0.292038E+13 |
April | 0.458427E+12 | -0.146586E+10 | 0.00 | -0.249473E+12 | 0.421737E+13 |
May | 0.491735E+12 | -0.709658E+10 | 0.00 | -0.900004E+12 | 0.405881E+13 |
June | 0.459800E+12 | -0.814374E+10 | 0.00 | -0.141082E+13 | 0.491933E+13 |
July | 0.369700E+12 | -0.175525E+11 | 0.00 | -0.194321E+13 | 0.573696E+13 |
August | 0.310215E+12 | -0.122404E+11 | 0.00 | -0.195368E+13 | 0.607890E+13 |
September | 0.338953E+12 | -0.706845E+10 | 0.00 | -0.142161E+13 | 0.389650E+13 |
October | 0.325200E+12 | -588801184.6 | 0.00 | -0.135712E+12 | 0.307885E+13 |
November | 0.287162E+12 | 0.872448E+09 | 0.00 | 0.450743E+12 | 0.251167E+13 |
December | 0.256841E+12 | 0.286538E+10 | 0.00 | 0.773854E+12 | 0.229791E+13 |
Annual Sum or Average | 0.433364E+13 | -0.420658E+11 | 0.00 | -0.517929E+13 | 0.422245E+14 |
Minimum of Months | 0.256841E+12 | -0.175525E+11 | 0.00 | -0.195368E+13 | 0.948166E+12 |
Maximum of Months | 0.491735E+12 | 0.342061E+10 | 0.00 | 0.805313E+12 | 0.607890E+13 |