Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:51

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2023-10-16 08:51:38


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 30043.96 648.61 648.61
Net Site Energy 30043.96 648.61 648.61
Total Source Energy 93620.76 2021.16 2021.16
Net Source Energy 93620.76 2021.16 2021.16


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 86.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3858.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2457.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 350.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1909.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2725.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 564.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1158.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13739.15
Humidification 1609.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 598.80
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 647.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 29310.18 733.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 16618.12
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 86.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 3858.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2457.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 350.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5334.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 54.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2725.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 564.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1158.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13739.15
Humidification General 1609.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 598.80
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 647.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 86.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 3858.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 2457.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 350.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 14676.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1909.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2725.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 564.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1158.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13739.15
Humidification Unassigned 1609.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 598.80
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 647.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 60.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 214.08 15.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36
Other 358.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 632.77 15.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 60.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 214.08 15.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36
Other 358.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 632.77 15.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 29310.182 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 29310.182 100.00
     
Total On-Site and Utility Electric Sources 29310.182 100.00
Total Electricity End Uses 29310.182 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 16618.12 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 16618.12 100.00
Total Water End Uses 16618.12 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.17
Time Setpoint Not Met During Occupied Cooling 1140.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 5789.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:51
RunPeriod RUNPERIOD 1
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 4635.80 1390.74 927.16 1390.74 927.16
Gross Window-Wall Ratio [%] 38.05 38.05 38.05 38.05 38.05
Above Ground Window-Wall Ratio [%] 40.00 40.00 40.00 40.00 40.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 6.5999 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 6.5999 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 115.90 115.90 6.5999 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 77.26 77.26 6.5999 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 9.7790 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 6.5999 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 6.6297 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 4635.80 4635.80 6.6297 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 6.5999 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 6.5999 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 6.5999 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 6.5999 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 6.5999 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 6.5999 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 6.5999 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 6.5999 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 6.5999 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 6.5999 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 6.5999 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 6.5999 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 6.5999 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 6.5999 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 6.5999 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 6.5999 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 9.7790 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 9.7790 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 9.7790 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 6.5999 18.58 484.4232  
Total 46320.38             6.6297 9.29 17.8789  
Conditioned Total 46320.38             6.6297 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.0382 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 25-AUG-15:09 06-DEC-07:10 - - - - - - - - - - 27-JUN-11:00
Heating 0.00 531907.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 432855.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 212815.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 778371.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 82829.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 248049.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 39745.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 77358.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 30046.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1972025.41 561954.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 531907.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 432855.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 212815.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3394.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 248049.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 39745.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 77358.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 30046.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 94.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 12219.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 7783.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1110.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 46480.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6046.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8630.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1787.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 3669.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 5097.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 701.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 92825.35 795.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 2.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 263.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 168.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 23.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 186.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 38.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 79.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 110.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2003.99 17.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 2.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 263.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 168.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 23.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1003.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 186.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 38.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 79.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 110.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2003.99 17.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.68
DATACENTER_BOT_ZN_6 DIRECT AIR 0.510289
DATACENTER_MID_ZN_6 DIRECT AIR 4.87
DATACENTER_TOP_ZN_6 DIRECT AIR 0.498535
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 23.41
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 6.06 0.313807 0.267000 1.62 0.836820 0.500000 0.001214 0.000129 1.62 12.80 0.008000
CORE_MID VAV BOX COMPONENT 57.18 0.332665 0.283000 16.18 0.887108 0.500000 0.001145 0.003053 16.18 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.71 0.333388 0.283000 1.61 0.889035 0.500000 0.001143 0.000611 2.29 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.18 0.203229 0.173000 0.203297 0.541945 0.500000 0.001875 0.000055 0.205410 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.17 0.131975 0.112000 0.130611 0.351933 0.500000 0.002887 0.000041 0.155265 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.32 0.180849 0.154000 0.203369 0.482265 0.500000 0.002107 0.000080 0.298428 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.50 0.102470 0.087000 0.130669 0.300000 0.500000 0.003718 0.000027 0.130669 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 11.61 0.205686 0.175000 2.03 0.548497 0.500000 0.001852 0.001487 5.58 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 12.37       0.331787 0.500000 0.003062 0.000996 3.74 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 13.04 0.183211 0.156000 2.03 0.488561 0.500000 0.002080 0.001499 5.63 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 13.45 0.114441 0.097000 1.30 0.305175 0.500000 0.003329 0.000912 3.42 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.33 0.179177 0.152000 0.202597 0.477805 0.500000 0.002126 0.000191 0.718683 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.27 0.120956 0.103000 0.131058 0.322549 0.500000 0.003150 0.000127 0.477475 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.46 0.163109 0.139000 0.203526 0.434957 0.500000 0.002336 0.000193 0.723597 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.46 0.105545 0.090000 0.131237 0.300000 0.500000 0.003610 0.000120 0.451934 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 14793.03 0.000129 298.22
CORE_MID VAV BOX REHEAT COIL 348924.61 0.003053 8136.47
CORE_TOP VAV BOX REHEAT COIL 69854.32 0.000611 1844.78
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 6280.03 0.000055 165.96
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 4743.01 0.000041 125.30
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 9106.45 0.000080 240.44
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 3123.49 0.000027 75.11
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 169975.23 0.001487 4483.71
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 113858.05 0.000996 3003.29
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 171359.31 0.001499 4520.18
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 104241.24 0.000912 2749.87
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 21873.29 0.000191 576.85
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 14531.20 0.000127 383.21
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 22022.54 0.000193 580.78
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 13755.20 0.000120 362.76
VAV_BOT WITH REHEAT HEATING COIL 31993.74 0.000280 547.55
VAV_MID WITH REHEAT HEATING COIL 216417.78 0.001893 3772.86
VAV_TOP WITH REHEAT HEATING COIL 20993.96 0.000184 368.70
CAV_BAS HEATING COIL 248933.04 0.002178 5597.64
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.61 2.29 11.23 2.29 10.03 10.03 0.300000 0.227921 10.03
VAV_MID WITH REHEAT 53.82 22.86 107.64 29.15 94.45 94.45 0.300000 0.308617 94.45
VAV_TOP WITH REHEAT 5.62 2.28 11.23 4.66 10.78 10.78 0.300000 0.432169 10.78
CAV_BAS 5.68 5.68 5.68 5.68 5.68 5.68 1.00 1.00 5.68
AIRLOOP DATACENTER BASEMENT 23.41 23.41 23.41 23.41 23.41 23.41 1.00 0.999989 23.41
AIRLOOP DATACENTER BOT 0.510289 0.510289 0.510289 0.510289 0.510289 0.510289 1.00 1.00 0.510289
AIRLOOP DATACENTER MID 4.87 4.87 4.87 4.87 4.87 4.87 1.00 1.00 4.87
AIRLOOP DATACENTER TOP 0.498535 0.498535 0.498535 0.498535 0.498535 0.498535 1.00 1.00 0.498535
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 10.03  
VAV_MID WITH REHEAT_OA_CONTROLLER 94.45  
VAV_TOP WITH REHEAT_OA_CONTROLLER 10.78  
CAV_BAS_OA_CONTROLLER 5.68 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 23.41 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.510289 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.87 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.498535 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 27.46 6.67 10.86 0.008164 0.008164 185653.92 0.005310 10.03
VAV_MID WITH REHEAT COOLING COIL 27.76 6.67 10.86 0.008100 0.008100 1779365.98 0.050890 94.45
VAV_TOP WITH REHEAT COOLING COIL 27.18 6.67 10.87 0.008160 0.008160 196088.44 0.005608 10.78
CAV_BAS COOLING COIL 27.86 6.67 11.28 0.008224 0.008224 105042.04 0.003004 5.68
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 10.03
VAV_MID WITH REHEAT FAN 94.45
VAV_TOP WITH REHEAT FAN 10.78
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.005310 0.000090
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000280  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.050890 0.000009
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.001893  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.005608 0.000085
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000184  
CAV_BAS_COOLC_CONTROLLER 0.003004 0.000159
CAV_BAS_HEATC_CONTROLLER 0.002178  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.68
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 23.41 440678.32 288368.91 0.010792
AIRLOOP DATACENTER BOT COOLING COIL 0.510289 9391.96 6211.81 0.000230
AIRLOOP DATACENTER MID COOLING COIL 4.87 89724.67 59321.21 0.002197
AIRLOOP DATACENTER TOP COOLING COIL 0.498535 9178.76 6069.72 0.000225
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 23.41 23.41 23.41 23.41 440678.32 440678.32 14683.19 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.510289 0.510289 0.510289 0.510289 9391.96 9391.96 678.30 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.87 4.87 4.87 4.87 89724.67 89724.67 6783.03 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.498535 0.498535 0.498535 0.498535 9178.76 9178.76 678.30 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 23.41
AIRLOOP DATACENTER BOT SUPPLY FAN 0.510289
AIRLOOP DATACENTER MID SUPPLY FAN 4.87
AIRLOOP DATACENTER TOP SUPPLY FAN 0.498535
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 23.41 440678.32 0.010792
AIRLOOP DATACENTER BOT HEATING COIL 0.510289 9391.96 0.000230
AIRLOOP DATACENTER MID HEATING COIL 4.87 89724.67 0.002197
AIRLOOP DATACENTER TOP HEATING COIL 0.498535 9178.76 0.000225
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 14683.19
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 678.30
AIRLOOP DATACENTER MID_SUPPHEATCOIL 6783.03
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 678.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000103 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.064812 10476.99  
HEATSYS1 PUMP 0.014057 4191.38 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.064812 7.78
HEATSYS1 0.014057 1.69
COOLSYS1_SUPPLY 0.064812 7.78
SINGLE WATER PLANT LOOP 0.013444 1.61
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.064812 0.064812 272046.86 8.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1606779.52 1606779.52 0.014057
CENTRAL BOILER 553791.17 541988.62 0.013444
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 CHILLER1 PUMP 0.032406 3626.79
COOLSYS1 CHILLER2 PUMP 0.032406 3626.79
PLANT CIRC PUMP 0.013444 3395.03
SWHSYS1 PUMP 0.000440 56.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.064812 0.032807 1149936.58 1155391.87 0.057176
COOLSYS1 CHILLER2 0.064812 0.032807 1149936.58 1155391.87 0.057176
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013444 139666.47 58688.01 69833.23 7004.20 21356.73
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.114352 13.72
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.114352 28030.75
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 48.68 1371359.74 9.74 171419.97
TOWERWATERSYS COOLTOWER 2 48.68 1371359.74 9.74 171419.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.059388
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 20.90 15.40 11.90 14.80 12.70 15.40 23.30 26.30 31.20 30.40 29.80 27.80


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 32.17 -110.88 -7.00 809.00 91976 1.0932


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.66 19.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 76.91 115.90 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 76.91 115.90 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 52.57 77.26 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 84.71 115.90 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 84.71 115.90 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 56.47 77.26 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 6.600 4.842 0.000 0.000 0.000 0.000 11.442 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 6.600 8.070 0.000 0.000 0.000 0.000 14.670 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 9.779 215.299 0.000 0.000 0.000 0.000 225.078 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 6.600 484.423 0.000 0.000 0.000 0.000 491.023 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 18343.827 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 18343.827
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 16474.046 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 16474.046
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2068.481 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.481
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2068.526 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2068.526
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1333.008 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1333.008
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 5172.174 6.600 122.617 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5172.174
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 354.027 9.779 181.682 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 354.027


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.452 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.400 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.662 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.5215
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5467
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4343
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.81534556E-15 0.47534309E-16 -0.12491808E-09 -0.15651055E-17
51 8 0.18376575E-07 0.18892299E-12 0.33997552E-03 -0.20894799E-09
52 7 -0.11109444E-01 0.10222184E-07 -0.21454547E-01 0.12631841E-03
53 6 0.37458360 0.36213810E-05 0.44579641 -0.43850983E-02
54 5 -4.8902522 0.13734403E-03 -4.2389002 0.59460182E-01
55 4 31.674104 0.11393769E-02 20.648451 -0.40448134
56 3 -108.39803 0.25142476E-02 -54.058051 1.4743366
57 2 194.32686 0.14299560E-02 76.440274 -2.8561868
58 1 -170.12819 0.15421596E-03 -54.840647 2.7274244
59 0 57.057407 0.88766417E-06 15.629571  
60 9 0.15527634E-14 0.48972640E-16 -0.12737755E-09 -0.48559044E-17
61 8 0.18724477E-07 0.18300980E-12 0.34384059E-03 -0.21290374E-09
62 7 -0.11225506E-01 0.98577958E-08 -0.21621905E-01 0.12763808E-03
63 6 0.37773826 0.34860306E-05 0.44850155 -0.44222837E-02
64 5 -4.9210508 0.13200769E-03 -4.2597582 0.59842059E-01
65 4 31.810414 0.10936068E-02 20.730162 -0.40629104
66 3 -108.68827 0.24103335E-02 -54.219675 1.4785295
67 2 194.61479 0.13693941E-02 76.588171 -2.8607587
68 1 -170.23464 0.14753937E-03 -54.883028 2.7292902
69 0 57.057407 0.84836289E-06 15.622061  
70 9 0.10580992E-14 0.52916478E-16 -0.11479962E-09 -0.26242945E-17
71 8 0.16943687E-07 0.21219816E-12 0.32378363E-03 -0.19265555E-09
72 7 -0.10622292E-01 0.11706466E-07 -0.20751735E-01 0.12077931E-03
73 6 0.36134106 0.41796623E-05 0.43441658 -0.42290030E-02
74 5 -4.7609497 0.15957712E-03 -4.1510514 0.57856955E-01
75 4 31.101728 0.13316855E-02 20.304070 -0.39688243
76 3 -107.17897 0.29539374E-02 -53.376774 1.4567269
77 2 193.11717 0.16877407E-02 75.817308 -2.8369794
78 1 -169.68078 0.18278585E-03 -54.662957 2.7195831
79 0 57.057407 0.10570564E-05 15.661738  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.455_SHGC_EAST_0.249 35 1 VerySmooth 2.586 2.586 1.000 0.250    
2 WINDOW_U_0.455_SHGC_SOUTH_0.249 36 1 VerySmooth 2.586 2.586 1.000 0.250    
3 WINDOW_U_0.455_SHGC_WEST_0.249 37 1 VerySmooth 2.586 2.586 1.000 0.250    
4 WINDOW_U_0.455_SHGC_NORTH_0.249 38 1 VerySmooth 2.586 2.586 1.000 0.250    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.60359E-002 0.16038 0.61766 0.61766 0.27390 0.15652 0.22642 0.00000 0.84000 0.84000 0.12071 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.486 6.0748E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.58 5 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.58 5 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.58 5 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.58 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.58 5 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.58 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1376E-003
2 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1391E-003
3 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.4572E-003
4 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.4584E-003
5 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1322E-003
6 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1331E-003
7 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7516E-003
8 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7521E-003
9 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1706E-003
10 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.2646E-003
11 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.4846E-003
12 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5652E-003
13 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1550E-003
14 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2218E-003
15 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7664E-003
16 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8035E-003
17 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1044
18 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5954E-002
19 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1167
20 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.0313E-002
21 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.7338E-002
22 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9424E-002
23 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1496E-002
24 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.0924E-002
25 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1750E-003
26 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.2864E-003
27 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.4893E-003
28 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5885E-003
29 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1591E-003
30 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2376E-003
31 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7668E-003
32 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8046E-003
33 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.1375E-003
34 Clear Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.1391E-003
35 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.4570E-003
36 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.4584E-003
37 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.1321E-003
38 Intermediate Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1331E-003
39 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7515E-003
40 Overcast Sky 12/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7521E-003
41 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8889E-003
42 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.0741E-003
43 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.7066E-003
44 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.9049E-003
45 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5250E-003
46 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.6121E-003
47 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9952E-003
48 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0209E-003
49 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.3314E-002
50 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.0727E-002
51 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.0514E-002
52 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.8793E-002
53 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.1911E-002
54 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.7152E-002
55 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.2799E-002
56 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.2243E-002
57 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8387E-003
58 Clear Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.9061E-003
59 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.6426E-003
60 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.6916E-003
61 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4977E-003
62 Intermediate Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5174E-003
63 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9953E-003
64 Overcast Sky 12/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0213E-003
65 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7708E-003
66 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7722E-003
67 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5123E-003
68 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5135E-003
69 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3404E-003
70 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3412E-003
71 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7516E-003
72 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7522E-003
73 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8031E-003
74 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8840E-003
75 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5387E-003
76 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6029E-003
77 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3616E-003
78 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4079E-003
79 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7668E-003
80 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8046E-003
81 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.7726E-002
82 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4518E-002
83 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.1327E-002
84 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1023E-002
85 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9123E-002
86 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 7.4449E-003
87 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.1496E-002
88 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0921E-002
89 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8016E-003
90 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8823E-003
91 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5368E-003
92 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5993E-003
93 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3584E-003
94 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3981E-003
95 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7664E-003
96 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8035E-003
97 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7707E-003
98 Clear Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7721E-003
99 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5122E-003
100 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5133E-003
101 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3403E-003
102 Intermediate Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3410E-003
103 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7515E-003
104 Overcast Sky 12/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7521E-003
105 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4967E-003
106 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.5662E-003
107 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2212E-003
108 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.2714E-003
109 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2028E-003
110 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.2211E-003
111 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9954E-003
112 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0213E-003
113 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7376E-002
114 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.8453E-002
115 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.3255E-002
116 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.6013E-002
117 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.6503E-002
118 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.5058E-002
119 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2799E-002
120 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.2243E-002
121 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.5392E-003
122 Clear Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.6917E-003
123 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2758E-003
124 Clear Turbid Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4333E-003
125 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.2287E-003
126 Intermediate Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.3087E-003
127 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.9952E-003
128 Overcast Sky 12/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0208E-003
129 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1045
130 Clear Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 6.5255E-002
131 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1133
132 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 7.0913E-002
133 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.5061E-002
134 Intermediate Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.4104E-002
135 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.8633E-002
136 Overcast Sky 12/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.9092E-002
137 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.1664E-002
138 Clear Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.0021E-002
139 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.8539E-002
140 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.7668E-002
141 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.9793E-002
142 Intermediate Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.5498E-002
143 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.9603E-002
144 Overcast Sky 12/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9312E-002
145 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.4692E-002
146 Clear Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.3039E-002
147 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.7423E-002
148 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.8249E-002
149 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.4975E-002
150 Intermediate Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.3745E-002
151 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.8633E-002
152 Overcast Sky 12/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.9088E-002
153 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.4944E-002
154 Clear Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.6875E-002
155 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.0317E-002
156 Clear Turbid Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.3811E-002
157 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.3724E-002
158 Intermediate Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.2693E-002
159 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.9603E-002
160 Overcast Sky 12/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.9312E-002
161 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1046
162 Clear Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 6.5397E-002
163 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1134
164 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 7.1077E-002
165 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.5201E-002
166 Intermediate Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.4215E-002
167 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.8716E-002
168 Overcast Sky 12/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.9134E-002
169 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.1707E-002
170 Clear Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.0067E-002
171 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.8587E-002
172 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.7712E-002
173 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.9874E-002
174 Intermediate Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.5552E-002
175 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.9686E-002
176 Overcast Sky 12/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9354E-002
177 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.4696E-002
178 Clear Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.3065E-002
179 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.7429E-002
180 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.8270E-002
181 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.5015E-002
182 Intermediate Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.3770E-002
183 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.8716E-002
184 Overcast Sky 12/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.9131E-002
185 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.4974E-002
186 Clear Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.6914E-002
187 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.0350E-002
188 Clear Turbid Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.3847E-002
189 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.3794E-002
190 Intermediate Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.2740E-002
191 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.9686E-002
192 Overcast Sky 12/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.9354E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 71618.58861 71618.58861 5.68027 5.68027 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 30.95800 5.61598E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016   00:10:00 0.50000 4.31558E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 76422.65451 76422.65451 6.06118 6.06118 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 30.95800 5.61598E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782   00:10:00 0.50000 4.31558E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 721080.22553 721080.22553 57.17589 57.17589 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 30.95800 5.61598E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 201017.79884 201017.79884 9.31992 10.77825 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 71950.70224 71950.70224 5.70519 5.70519 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 30.95800 5.61598E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 48938.09311 48938.09311 2.28820 2.28820 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 14683.86419 14683.86419 1.17513 1.17513 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80000 5.63111E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 4404.86292 4404.86292 0.20541 0.20541 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 14572.00628 14572.00628 1.16617 1.16617 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 34.99233 5.62211E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 3325.32531 3325.32531 0.15526 0.15526 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 16501.38258 16501.38258 1.32058 1.32058 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 40.57833 5.63076E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 6380.69067 6380.69067 0.29843 0.29843 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 18767.79579 18767.79579 1.50195 1.50195 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 39.11533 5.62848E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 1931.56185 1931.56185 8.95945E-002 8.95945E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 145089.66688 145089.66688 11.61090 11.61090 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80000 5.63111E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 118978.37238 118978.37238 5.58184 5.58184 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 154573.76490 154573.76490 12.36980 12.36980 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 35.36917 5.62269E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 79694.10005 79694.10005 3.73935 3.73935 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 162892.66203 162892.66203 13.03559 13.03559 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 40.68917 5.63093E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 119945.86499 119945.86499 5.62740 5.62740 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 168052.69262 168052.69262 13.44847 13.44847 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.93800 5.62821E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 72971.49380 72971.49380 3.42283 3.42283 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 16655.83015 16655.83015 1.33288 1.33288 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 40.53400 5.63070E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 15306.88182 15306.88182 0.71868 0.71868 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 15900.28390 15900.28390 1.27241 1.27241 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 36.07850 5.62379E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 10168.64893 10168.64893 0.47747 0.47747 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 18297.04775 18297.04775 1.46421 1.46421 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 40.80000 5.63111E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 15411.22240 15411.22240 0.72360 0.72360 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 18221.87024 18221.87024 1.45819 1.45819 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.93800 5.62821E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 9626.11889 9626.11889 0.45193 0.45193 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50000 4.31558E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8083.94932 8083.94932 0.51029 0.51029 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 35.94550 5.62358E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 0.50000 4.31558E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 77173.58100 77173.58100 4.87153 4.87153 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 35.94550 5.62358E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632   00:10:00 0.50000 4.31558E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7897.71319 7897.71319 0.49853 0.49853 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 36.27800 5.62409E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 0.50000 4.31558E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 370895.54164 370895.54164 23.41185 23.41185 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 28.69700 5.61258E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839   00:10:00 0.50000 4.31558E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 158730.91 10.03102 10.03102 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 24679.27 1.82652 1.82652 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1491197.18 94.45246 94.45246 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 272529.10 29.14968 29.14968 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00
5 VAV_TOP WITH REHEAT Cooling Sensible 169358.46 10.78258 10.78258 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 27309.24 4.65989 4.65989 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 05:50:00
7 CAV_BAS Cooling Sensible 82943.65 5.68027 5.68027 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 52075.95 1.20016 1.20016 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 369829.61 23.41211 23.41211 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 14683.19 0.33839 0.33839 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8114.89 0.51029 0.51029 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 678.30 1.56323E-002 1.56323E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 77521.97 4.87153 4.87153 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 6783.03 0.15632 0.15632 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 7934.94 0.49853 0.49853 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 678.30 1.56323E-002 1.56323E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.68027
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 6.06118
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31381
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26700
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61834
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.83682
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.21412E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.29416E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.61834
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14793.02670
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.29416E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 298.21581
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 57.17589
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33267
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28300
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 16.18078
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.88711
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.14530E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.05254E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 16.18078
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 348924.61074
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.05254E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8136.46949
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.70519
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33339
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.28300
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.61457
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.88903
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.14281E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.11116E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.28820
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 69854.32448
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.11116E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1844.78225
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.17513
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20323
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.17300
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20330
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54195
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.87473E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.49404E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.20541
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 6280.02816
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.49404E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 165.96195
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.16617
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13197
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.11200
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13061
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35193
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.88691E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.14939E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.15526
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4743.01109
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.14939E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 125.29573
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.32058
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18085
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15400
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20337
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.48226
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.10673E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.96672E-005
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.29843
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9106.44661
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.96672E-005
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 240.44389
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.50195
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10247
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 8.70000E-002
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13067
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.71815E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.73256E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.13067
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3123.48523
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.73256E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 75.10612
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.61090
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20569
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.17500
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.03191
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54850
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.85233E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.48702E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.58184
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 169975.23064
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.48702E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4483.71000
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 12.36980
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33179
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.06221E-003
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.96080E-004
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.73935
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
122 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 113858.04841
123 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.96080E-004
124 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3003.28904
125 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 13.03559
126 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18321
127 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15600
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.03355
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.48856
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.07957E-003
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.49913E-003
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.62740
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
136 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 171359.31312
137 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.49913E-003
138 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4520.17975
139 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 13.44847
140 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11444
141 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 9.70000E-002
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.30450
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30517
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.32924E-003
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.11948E-004
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.42283
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
150 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 104241.24200
151 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.11948E-004
152 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2749.87226
153 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.33288
154 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17918
155 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.15200
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20260
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.47781
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.12639E-003
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.91357E-004
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.71868
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
164 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 21873.29058
165 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.91357E-004
166 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 576.84628
167 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.27241
168 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12096
169 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.10300
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13106
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.32255
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.14991E-003
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.27125E-004
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.47747
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
178 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14531.19719
179 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.27125E-004
180 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 383.20893
181 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.46421
182 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16311
183 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.13900
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20353
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43496
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.33587E-003
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.92663E-004
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.72360
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
192 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22022.54018
193 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.92663E-004
194 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 580.77888
195 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.45819
196 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10555
197 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 9.00000E-002
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.13124
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.60983E-003
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.20337E-004
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.45193
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
206 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13755.20284
207 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.20337E-004
208 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 362.76039
209 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.51029
210 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.87153
211 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.49853
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 23.41185
213 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.61250
214 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28628
215 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.22500
216 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.28628
217 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.03102
218 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.03102
219 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
220 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.22792
221 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 53.82033
222 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 22.86194
223 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 107.64067
224 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 29.14968
225 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 94.45246
226 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 94.45246
227 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
228 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.30862
229 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.61644
230 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.28299
231 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.23288
232 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 4.65989
233 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.78258
234 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.78258
235 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
236 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.43217
237 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.68027
238 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.68027
239 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.68027
240 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.68027
241 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.68027
242 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.68027
243 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
244 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
245 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 23.41185
246 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 23.41185
247 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 23.41185
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 23.41185
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 23.41211
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 23.41211
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
253 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.51029
254 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.51029
255 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.51029
256 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.51029
257 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.51029
258 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.51029
259 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
260 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
261 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.87153
262 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.87153
263 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.87153
264 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.87153
265 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.87153
266 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.87153
267 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
268 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
269 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.49853
270 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.49853
271 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.49853
272 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.49853
273 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.49853
274 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.49853
275 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
276 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
277 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.03102
278 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 94.45246
279 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.78258
280 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.68027
281 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 23.41211
282 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.51029
283 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.87153
284 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.49853
285 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.03102
286 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.46000
287 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
288 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.86206
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.16435E-003
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.16435E-003
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 185653.91635
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.30968E-003
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.03102
294 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 31993.73836
295 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.79895E-004
296 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 547.55028
297 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.03102
298 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.30968E-003
299 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 8.96835E-005
300 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.79895E-004
301 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 94.45246
302 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.75840
303 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
304 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.86184
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.09969E-003
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.09969E-003
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1779365.97815
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.08896E-002
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 94.45246
310 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 216417.77716
311 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.89332E-003
312 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 3772.86149
313 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 94.45246
314 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.08896E-002
315 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 9.35732E-006
316 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.89332E-003
317 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.78258
318 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.18136
319 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
320 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.87235
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.16013E-003
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.16013E-003
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 196088.43665
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.60810E-003
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.78258
326 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 20993.96087
327 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.83664E-004
328 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 368.70215
329 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.78258
330 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.60810E-003
331 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 8.49111E-005
332 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.83664E-004
333 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.68027
334 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
335 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 27.86172
336 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
337 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.27950
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.22360E-003
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.22360E-003
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 105042.04097
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.00419E-003
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.68027
343 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 248933.04305
344 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.17777E-003
345 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 5597.64287
346 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.68027
347 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.00419E-003
348 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.58509E-004
349 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.17777E-003
350 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 23.41211
351 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
352 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 23.41211
353 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 440678.31912
354 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 288368.90816
355 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.07922E-002
356 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 23.41211
357 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 23.41211
358 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 23.41211
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 23.41211
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 440678.31912
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 440678.31912
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 14683.19080
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
364 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 23.41211
365 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 23.41211
366 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 440678.31912
367 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.07922E-002
368 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 14683.19080
369 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.03122E-004
370 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
371 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
372 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
373 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.51029
374 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
375 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.51029
376 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9391.96124
377 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6211.81275
378 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.30009E-004
379 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.51029
380 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.51029
381 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.51029
382 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.51029
383 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9391.96124
384 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9391.96124
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 678.30259
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
387 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.51029
388 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.51029
389 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9391.96124
390 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.30009E-004
391 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 678.30259
392 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.87153
393 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
394 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.87153
395 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 89724.66907
396 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 59321.20636
397 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.19735E-003
398 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.87153
399 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.87153
400 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.87153
401 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.87153
402 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 89724.66907
403 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 89724.66907
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 6783.02586
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
406 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.87153
407 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.87153
408 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 89724.66907
409 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.19735E-003
410 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 6783.02586
411 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.49853
412 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
413 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.49853
414 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9178.75948
415 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6069.71638
416 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.24787E-004
417 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.49853
418 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.49853
419 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.49853
420 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.49853
421 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9178.75948
422 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9178.75948
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 678.30259
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
425 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.49853
426 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.49853
427 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9178.75948
428 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.24787E-004
429 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 678.30259
430 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 6.48116E-002
431 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 10476.98624
432 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 6.48116E-002
433 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 7.77739
434 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 6.48116E-002
435 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 6.48116E-002
436 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 272046.86340
437 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 8.33000
438 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.40568E-002
439 PlantLoop HEATSYS1 Plant Loop Volume [m3] 1.68682
440 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.40568E-002
441 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 4191.37952
442 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
443 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1606779.51741
444 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1606779.52000
445 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.40568E-002
446 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 6.48116E-002
447 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 7.77739
448 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Flow Rate [m3/s] 3.24058E-002
449 Pump:ConstantSpeed COOLSYS1 CHILLER1 PUMP Design Power Consumption [W] 3626.78545
450 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Flow Rate [m3/s] 3.24058E-002
451 Pump:ConstantSpeed COOLSYS1 CHILLER2 PUMP Design Power Consumption [W] 3626.78545
452 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 6.48116E-002
453 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.28075E-002
454 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1149936.57501
455 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1155391.87000
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 5.71761E-002
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 6.48116E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 3.28075E-002
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1149936.57501
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1155391.87000
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 5.71761E-002
462 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.34443E-002
463 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.61332
464 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.34443E-002
465 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3395.02641
466 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.34443E-002
467 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
468 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 58688.01476
469 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
470 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7004.19857
471 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21356.73356
472 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 553791.16998
473 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 541988.62000
474 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.34443E-002
475 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
476 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
477 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
478 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 56.20530
479 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
480 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.11435
481 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 13.72226
482 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.11435
483 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 28030.74813
484 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 48.67890
485 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1371359.73852
486 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 9.73578
487 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 171419.96732
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 48.67890
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1371359.73852
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 9.73578
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 171419.96732
492 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.93875E-002
493 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.93875E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 14027.75
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 330644.64
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 66211.62
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 5953.30
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 4495.93
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 8631.25
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 2959.52
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 161076.83
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 107896.59
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 162388.18
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 98784.99
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 20727.25
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 13769.77
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 20868.66
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 13034.54
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 26623.24
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 186533.39
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 18346.65
19 Coil:Heating:Water CAV_BAS HEATING COIL 199745.72


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 246417.83 164365.25 82052.58 0.67 55580.34 563.73
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2348116.94 1558564.38 789552.56 0.66 531605.27 5391.84
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 263008.21 175969.87 87038.34 0.67 60842.53 617.10
4 Coil:Cooling:Water CAV_BAS COOLING COIL 136696.53 91903.80 44792.73 0.67 27683.55 280.78


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.47 22.07
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.47 22.07


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   76.91 200.61 76.91 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 23.18 23.18 23.18 0.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   52.57 133.74 52.57 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 25.75 25.75 25.75 90.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   76.91 200.61 76.91 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 23.18 23.18 23.18 180.00 90.00 13.65 1.70 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   52.57 133.74 52.57 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 25.75 25.75 25.75 270.00 90.00 15.43 1.67 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   84.71 200.61 84.71 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_NORTH_0.249 N/A 2.586 No 115.90 115.90 115.90 0.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   56.47 133.74 56.47 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_EAST_0.249 N/A 2.586 No 77.26 77.26 77.26 90.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   84.71 200.61 84.71 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_SOUTH_0.249 N/A 2.586 No 115.90 115.90 115.90 180.00 90.00 73.11 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   56.47 133.74 56.47 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.455_SHGC_WEST_0.249 N/A 2.586 No 77.26 77.26 77.26 270.00 90.00 48.74 1.59 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.452 1.193   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.400 1.158   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.662 1.331   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.3381214283 0.2655321521 Pass Pass 1.4280453725 4.7372137383 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 7.0082530768E-002 0.1339640106 Pass Pass 0.1188249371 0.3228745611 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 3.6262016636E-002 7.9350027024E-002 Pass Pass 7.7464100500E-002 0.2665843874 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 4.9715423552E-002 3.7006958005E-002 Pass Pass 0.1778148926 0.3780912968 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 6.3946371731E-002 8.7287281501E-002 Pass Pass 0.1179924910 0.3210667815 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.1046769078 0.1325032126 Pass Pass 0.1191883001 0.3242484000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1877459340 0.2944907566 Pass Pass 0.1483273467 0.4054013429 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.1222594652 0.2356998764 Pass Pass 0.1290578367 0.3668130393 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 4.4432538782E-002 4.0294796904E-002 Pass Pass 7.6007603998E-002 0.2636446939 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 8.0783441491E-002 0.1002752042 Pass Pass 7.7007333949E-002 0.2662171701 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.1909293791 0.2513082413 Pass Pass 9.8055629757E-002 0.3183915179 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.1028114406 0.1355539443 Pass Pass 7.3475829420E-002 0.2530931133 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.1231427613 0.1609013714 Pass Pass 10.2156874955 118.7772379151 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 9.3693183587E-002 0.1136853023 Pass Pass 0.5001303396 3.5804203031 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.1553004949 0.1168634193 Pass Pass 0.1867369374 0.3896618047 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.1228606799 0.1179465035 Pass Pass 0.2963723246 1.2971337644 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.5786159265E-002 2.4650243190E-002 Pass Pass 0.7898795541 4.9651901642 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 1.9798038288E-002 3.3286258374E-002 Pass Pass 0.1223829446 0.3819077367 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 9.1283807196E-002 6.1271505404E-002 Pass Pass 0.1837700416 0.3839690485 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 4.2848182741E-006 5.1518460125E-006 Pass Pass 6.9920477325E-003 7.6194284655E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 4.5249432706E-006 6.4749914462E-006 Pass Pass 0.2121677884 0.9447370535 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 4.4168457538E-002 3.5638117624E-002 Pass Pass 0.1107690236 0.4897622531 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 1.7828220911E-005 2.5307929617E-005 Pass Pass 7.9103366814E-005 1.0593549381E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 5173.47 41.86 0.00 15816.75 25114.18 46146.28



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 0.50 0.00 0.50 Wetbulb [C] 2.10 140.00
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 40.80 13.30 18.50 Wetbulb [C] 4.80 310.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 2      
Feb 34.00 28      
Mar 40.00 18      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 81.00 18      
Aug 71.00 20      
Sep 27.00 12      
Oct 9.00 6      
Nov 35.00 14      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 200.61 76.91 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 133.74 52.57 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 200.61 76.91 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 133.74 52.57 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 2006.06 847.11 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.158 1.400 1337.37 564.74 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 2006.06 847.11 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.158 1.400 1337.37 564.74 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 200.61 84.71 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 133.74 56.47 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 200.61 84.71 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 133.74 56.47 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.193 1.452 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.193 1.452 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.158 1.400 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.158 1.400 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.158 1.400 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.331 1.662 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.331 1.662 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.455_SHGC_NORTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.455_SHGC_EAST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.455_SHGC_EAST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.455_SHGC_EAST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.455_SHGC_SOUTH_0.249   23.18 0.00 0.00 23.18 23.18 2.586 0.250 0.275             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.455_SHGC_WEST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.455_SHGC_WEST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.455_SHGC_WEST_0.249   25.75 0.00 0.00 25.75 25.75 2.586 0.250 0.275             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.455_SHGC_NORTH_0.249   115.90 0.00 0.00 115.90 1158.95 2.586 0.250 0.275             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.455_SHGC_EAST_0.249   77.26 0.00 0.00 77.26 772.63 2.586 0.250 0.275             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.455_SHGC_SOUTH_0.249   115.90 0.00 0.00 115.90 1158.95 2.586 0.250 0.275             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.455_SHGC_WEST_0.249   77.26 0.00 0.00 77.26 772.63 2.586 0.250 0.275             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.455_SHGC_NORTH_0.249   115.90 0.00 0.00 115.90 115.90 2.586 0.250 0.275             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.455_SHGC_EAST_0.249   77.26 0.00 0.00 77.26 77.26 2.586 0.250 0.275             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.455_SHGC_SOUTH_0.249   115.90 0.00 0.00 115.90 115.90 2.586 0.250 0.275             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.455_SHGC_WEST_0.249   77.26 0.00 0.00 77.26 77.26 2.586 0.250 0.275             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             4635.80 2.586 0.250 0.275                      
North Total or Average             1390.74 2.586 0.250 0.275                      
Non-North Total or Average             3245.06 2.586 0.250 0.275                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 6.5999 2779.43 18343.83 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 165.73
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 6.5999 2496.12 16474.05 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 148.84
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 6.5999 24961.20 164740.46 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 1488.36
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 6.5999 2496.12 16474.05 LightsWired LTG_SCH_OFFICE 50.34 168.00 48.13 0.0000 Y 148.84
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 6.5999 313.41 2068.48 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.33 0.0000 Y 10.61
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.98 0.0000 Y 6.75
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 6.5999 313.42 2068.53 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.89 0.0000 Y 10.44
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.18 0.0000 Y 6.80
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 6.5999 3134.13 20684.81 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.27 0.0000 Y 105.88
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 6.5999 2019.75 13330.08 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.95 0.0000 Y 67.42
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 6.5999 3134.20 20685.26 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.86 0.0000 Y 104.30
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 6.5999 2019.75 13330.08 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.13 0.0000 Y 67.88
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 6.5999 313.41 2068.48 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.27 0.0000 Y 10.59
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.94 0.0000 Y 6.74
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 6.5999 313.42 2068.53 LightsWired LTG_SCH_OFFICE 50.34 168.00 26.86 0.0000 Y 10.43
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 6.5999 201.98 1333.01 LightsWired LTG_SCH_OFFICE 50.34 168.00 27.13 0.0000 Y 6.79
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 6.5999 783.68 5172.17 LightsWired LTG_SCH_OFFICE 50.34 168.00 49.04 0.0000 Y 47.61
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 9.7790 36.20 354.03 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.63
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 9.7790 362.03 3540.27 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 36.26
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 9.7790 36.20 354.03 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 3.63
Interior Lighting Total       6.6297 46320.38 307089.14               774.43


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.53 797.83
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.53 286.49
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2068.48 797.81
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.14 2068.48 286.48
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1333.01 514.14
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.14 1333.01 184.62


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 13271.55 AstronomicalClock -   41.79 41.79 104.10
EXTERIOR_LIGHTS_B 989.48 AstronomicalClock -   83.79 62.79 11.66
EXTERIOR_LIGHTS_C 26594.85 AstronomicalClock -   83.79 47.06 234.94
Exterior Lighting Total 40855.88           350.70



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2259170.43          
HEATSYS1 BOILER Boiler:HotWater 1606779.52 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1155391.87 6.28 1011500.47 5.58 6.47 22.07
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1155391.87 6.28 1011500.47 5.58 6.47 22.07
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 541988.62 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1371359.74          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1371359.74          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 185653.92 246417.83 164365.25 82052.58 0.67 - 55580.34 563.73
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1779365.98 2348116.94 1558564.38 789552.56 0.66 - 531605.27 5391.84
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 196088.44 263008.21 175969.87 87038.34 0.67 - 60842.53 617.10
CAV_BAS COOLING COIL Coil:Cooling:Water 105042.04 136696.53 91903.80 44792.73 0.67 - 27683.55 280.78
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   440678.32 288368.91 152309.41 0.65 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9391.96 6211.81 3180.15 0.66 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   89724.67 59321.21 30403.46 0.66 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9178.76 6069.72 3109.04 0.66 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 14793.03 14027.75 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 348924.61 330644.64 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 69854.32 66211.62 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 6280.03 5953.30 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 4743.01 4495.93 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 9106.45 8631.25 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 3123.49 2959.52 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 169975.23 161076.83 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 113858.05 107896.59 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 171359.31 162388.18 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 104241.24 98784.99 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 21873.29 20727.25 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 14531.20 13769.77 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 22022.54 20868.66 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 13755.20 13034.54 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 31993.74 26623.24 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 216417.78 186533.39 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 20993.96 18346.65 -
CAV_BAS HEATING COIL Coil:Heating:Water 248933.04 199745.72 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   440678.32 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9391.96 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   89724.67 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9178.76 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   14683.19 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   678.30 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   6783.03 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   678.30 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.03 21676.51 2160.95 1.00 1.12 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 94.45 204106.75 2160.95 1.00 1.08 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.78 23176.78 2149.46 1.00 1.12 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.68 9631.77 1695.65 1.00 1.16 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 23.41 38612.35 1649.25 1.00 1.14 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.51 571.58 1120.11 1.00 1.60 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.87 5456.63 1120.11 1.00 1.16 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.50 558.41 1120.11 1.00 1.61 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 105797.75 0.064812 10476.99 161652.92 0.91 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.014057 4191.38 298174.34 0.91 General
COOLSYS1 CHILLER1 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.032406 3626.79 111917.77 0.91 General
COOLSYS1 CHILLER2 PUMP Pump:ConstantSpeed Intermittent 73247.35 0.032406 3626.79 111917.77 0.91 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013444 3395.03 252524.76 0.91 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.000440 56.21 127739.32 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 148556.62 0.114352 28030.75 245126.60 0.91 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.49 0.06



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 71618.59 71618.59 25.77 5.680 5.680 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00899 30.96 0.00562 1.200 0.00
CORE_BOTTOM 76422.65 76422.65 30.62 6.061 6.061 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00891 30.96 0.00562 1.078 0.00
CORE_MID 721080.23 721080.23 288.88 57.176 57.176 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00893 30.96 0.00562 10.778 0.00
CORE_TOP 71950.70 71950.70 28.83 5.705 5.705 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00893 30.96 0.00562 1.078 0.00
PERIMETER_BOT_ZN_3 14683.86 14683.86 46.85 1.175 1.175 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00869 40.80 0.00563 0.135 0.00
PERIMETER_BOT_ZN_2 14572.01 14572.01 72.15 1.166 1.166 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 24.00 24.00 0.00862 34.99 0.00562 0.087 0.00
PERIMETER_BOT_ZN_1 16501.38 16501.38 52.65 1.321 1.321 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:40:00 24.00 24.00 0.00867 40.58 0.00563 0.135 0.00
PERIMETER_BOT_ZN_4 18767.80 18767.80 92.92 1.502 1.502 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 24.00 24.00 0.00860 39.12 0.00563 0.087 0.00
PERIMETER_MID_ZN_3 145089.67 145089.67 462.93 11.611 11.611 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00860 40.80 0.00563 1.353 0.00
PERIMETER_MID_ZN_2 154573.76 154573.76 765.31 12.370 12.370 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 24.00 24.00 0.00856 35.37 0.00562 0.872 0.00
PERIMETER_MID_ZN_1 162892.66 162892.66 519.73 13.036 13.036 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00859 40.69 0.00563 1.353 0.00
PERIMETER_MID_ZN_4 168052.69 168052.69 832.05 13.448 13.448 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00856 38.94 0.00563 0.872 0.00
PERIMETER_TOP_ZN_3 16655.83 16655.83 53.14 1.333 1.333 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 24.00 24.00 0.00856 40.53 0.00563 0.135 0.00
PERIMETER_TOP_ZN_2 15900.28 15900.28 78.72 1.272 1.272 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 24.00 24.00 0.00854 36.08 0.00562 0.087 0.00
PERIMETER_TOP_ZN_1 18297.05 18297.05 58.38 1.464 1.464 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00855 40.80 0.00563 0.135 0.00
PERIMETER_TOP_ZN_4 18221.87 18221.87 90.22 1.458 1.458 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 24.00 24.00 0.00853 38.94 0.00563 0.087 0.00
DATACENTER_BOT_ZN_6 8083.95 8083.95 223.30 0.510 0.510 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 27.00 27.00 0.00859 35.95 0.00562 0.016 0.00
DATACENTER_MID_ZN_6 77173.58 77173.58 2131.71 4.872 4.872 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 27.00 27.00 0.00859 35.95 0.00562 0.156 0.00
DATACENTER_TOP_ZN_6 7897.71 7897.71 218.15 0.499 0.499 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 27.00 27.00 0.00859 36.28 0.00562 0.016 0.00
DATACENTER_BASEMENT_ZN_6 370895.54 370895.54 473.27 23.412 23.412 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00854 28.70 0.00561 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200   00:10:00 15.60 25.34 0.00432 0.50 0.00432 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078   00:10:00 15.60 22.76 0.00432 0.50 0.00432 1.078 0.00
CORE_MID 201017.80 201017.80 80.53 9.320 10.778 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 0.50 0.00432 10.778 0.00
CORE_TOP 48938.09 48938.09 19.61 2.288 2.288 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00800 0.50 0.00432 1.078 0.00
PERIMETER_BOT_ZN_3 4404.86 4404.86 14.05 0.205 0.205 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00735 0.50 0.00432 0.135 0.00
PERIMETER_BOT_ZN_2 3325.33 3325.33 16.46 0.155 0.155 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00746 0.50 0.00432 0.087 0.00
PERIMETER_BOT_ZN_1 6380.69 6380.69 20.36 0.298 0.298 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00763 0.50 0.00432 0.135 0.00
PERIMETER_BOT_ZN_4 1931.56 1931.56 9.56 0.090 0.090 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00692 0.50 0.00432 0.087 0.00
PERIMETER_MID_ZN_3 118978.37 118978.37 379.62 5.582 5.582 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00777 0.50 0.00432 1.353 0.00
PERIMETER_MID_ZN_2 79694.10 79694.10 394.57 3.739 3.739 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00778 0.50 0.00432 0.872 0.00
PERIMETER_MID_ZN_1 119945.86 119945.86 382.70 5.627 5.627 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00778 0.50 0.00432 1.353 0.00
PERIMETER_MID_ZN_4 72971.49 72971.49 361.29 3.423 3.423 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00775 0.50 0.00432 0.872 0.00
PERIMETER_TOP_ZN_3 15306.88 15306.88 48.84 0.719 0.719 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00781 0.50 0.00432 0.135 0.00
PERIMETER_TOP_ZN_2 10168.65 10168.65 50.35 0.477 0.477 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00781 0.50 0.00432 0.087 0.00
PERIMETER_TOP_ZN_1 15411.22 15411.22 49.17 0.724 0.724 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00781 0.50 0.00432 0.135 0.00
PERIMETER_TOP_ZN_4 9626.12 9626.12 47.66 0.452 0.452 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21.00 21.00 0.00779 0.50 0.00432 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 27.00 0.00850 0.50 0.00432 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156   00:10:00 18.00 24.65 0.00672 0.50 0.00432 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 23.63 0.00459 0.50 0.00432 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338   00:10:00 18.00 27.00 0.00850 0.50 0.00432 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 10.03 10.03 1.83 1.83 10.0310 2.2863 10.0310 0.2279 0.3000
VAV_MID WITH REHEAT 94.45 94.45 29.15 29.15 94.4525 29.1497 94.4525 0.3086 0.3000
VAV_TOP WITH REHEAT 10.78 10.78 4.66 4.66 10.7826 4.6599 10.7826 0.4322 0.3000
CAV_BAS 5.68 5.68 1.20 1.20 5.6803 5.6803 5.6803 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 23.41 23.41 0.34 0.34 23.4121 23.4119 23.4121 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.51 0.51 0.02 0.02 0.5103 0.5103 0.5103 1.0000 1.0000
AIRLOOP DATACENTER MID 4.87 4.87 0.16 0.16 4.8715 4.8715 4.8715 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.50 0.50 0.02 0.02 0.4985 0.4985 0.4985 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 14793.027 14793.027 1.618335 0.00012942 298.216   12/21 00:10:00   12/21 00:10:00 14793.03 14793.03 1.618335 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00800000 46.9512 0.00 0.00 14847.57 14847.57
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 348924.611 348924.611 16.180778 0.00305254 8136.469 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 348924.61 348924.61 16.180778 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00800000 46.9512 201017.80 0.00 350073.12 350073.12
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 69854.324 69854.324 2.288205 0.00061112 1844.782 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 69854.32 69854.32 2.288205 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00800000 46.9512 48938.09 0.00 70101.75 70101.75
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 6280.028 6280.028 0.205410 0.00005494 165.962 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 6280.03 6280.03 0.205410 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00735091 43.1891 4404.86 0.00 6303.08 6303.08
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 4743.011 4743.011 0.155265 0.00004149 125.296 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 4743.01 4743.01 0.155265 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00746318 43.8409 3325.33 0.00 4760.08 4760.08
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 9106.447 9106.447 0.298428 0.00007967 240.444 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 9106.45 9106.45 0.298428 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00762684 44.7901 6380.69 0.00 9138.36 9138.36
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 3123.485 3123.485 0.130669 0.00002733 75.106 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 3123.49 3123.49 0.130669 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00691939 40.6817 1931.56 0.00 3133.61 3133.61
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 169975.231 169975.231 5.581843 0.00148702 4483.710 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 169975.23 169975.23 5.581843 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00777456 45.6468 118978.37 0.00 170540.21 170540.21
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 113858.048 113858.048 3.739350 0.00099608 3003.289 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 113858.05 113858.05 3.739350 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00778157 45.6875 79694.10 0.00 114235.58 114235.58
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 171359.313 171359.313 5.627405 0.00149913 4520.180 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 171359.31 171359.31 5.627405 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00777757 45.6643 119945.86 0.00 171928.60 171928.60
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 104241.242 104241.242 3.422831 0.00091195 2749.872 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 104241.24 104241.24 3.422831 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00774593 45.4810 72971.49 0.00 104588.69 104588.69
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 21873.291 21873.291 0.718683 0.00019136 576.846 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 21873.29 21873.29 0.718683 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00780558 45.8267 15306.88 0.00 21944.98 21944.98
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 14531.197 14531.197 0.477475 0.00012713 383.209 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 14531.20 14531.20 0.477475 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00780574 45.8277 10168.65 0.00 14578.75 14578.75
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 22022.540 22022.540 0.723597 0.00019266 580.779 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 22022.54 22022.54 0.723597 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00780701 45.8350 15411.22 0.00 22094.70 22094.70
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 13755.203 13755.203 0.451934 0.00012034 362.760 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 13755.20 13755.20 0.451934 12.80 10.74 0.00800000 40.00 20.06 0.00800000 0.50 0.00431558 0.50 0.0000 21.00 0.00779308 45.7543 9626.12 0.00 13800.33 13800.33
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 185653.916 -999.000 10.031023 0.00530968 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 185653.92 185653.92 10.031023 27.46 16.30 0.00816435 10.86 10.10 0.00816435 40.80 0.00563111 18.58 20.2422 24.00 0.00882161 43.0921 123160.23 0.00 200663.21 190959.11
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 31993.738 31993.738 3.009307 0.00027990 547.550 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 31993.74 31993.74 3.009307 3.12 2.50 0.00473115 12.80 10.74 0.00800000 0.50 0.00431558 0.50 67.4740 21.64 0.00625069 35.3634 16042.44 0.00 32224.32 32224.32
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1779365.978 -999.000 94.452465 0.05088964 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 1779365.98 1779365.98 94.452465 27.76 16.35 0.00809969 10.86 10.04 0.00809969 40.80 0.00563111 18.58 21.4986 24.00 0.00881128 43.0418 1133966.31 0.00 1922023.58 1837302.20
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 216417.777 216417.777 28.335739 0.00189332 3772.861 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 216417.78 216417.78 28.335739 5.85 4.58 0.00526200 12.80 10.74 0.00800000 0.50 0.00431558 0.50 71.6621 19.61 0.00732612 46.8939 249429.73 0.00 225803.61 225803.61
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 196088.437 -999.000 10.782583 0.00560810 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 196088.44 196088.43 10.782583 27.18 16.20 0.00816013 10.87 10.10 0.00816013 40.80 0.00563111 18.58 18.8313 24.00 0.00875107 42.7516 133955.29 0.00 212147.52 201904.99
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 20993.961 20993.961 3.234775 0.00018366 368.702 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 05:50:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 20993.96 20993.96 3.234775 6.89 5.47 0.00557598 12.80 10.74 0.00800000 0.50 0.00431558 0.50 62.7710 17.60 0.00746132 54.1694 28471.41 0.00 22210.09 22210.09
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 105042.041 -999.000 5.680268 0.00300419 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 105042.04 105042.04 5.680268 27.86 16.48 0.00822360 11.28 10.34 0.00822360 40.13 0.00563007 18.37 21.1285 24.00 0.00903993 44.1440 62638.36 0.00 113371.81 108962.98
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 248933.043 248933.043 5.680268 0.00217777 5597.643 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 248933.04 248933.04 5.680268 0.11 0.11 0.00431558 40.00 20.06 0.00800000 0.50 0.00431558 0.50 21.1285 25.34 0.00431558 19.6025 0.00 0.00 211170.36 211170.36
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 440678.319 288368.908 23.412109 0.01079218 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 400754.58 400741.56 -999.0 28.73 16.99 0.00850024 12.80 11.23 0.00850000 40.80 0.00563111 18.58 -999.0000 27.00 0.00854237 34.9368 370426.78 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9391.961 6211.813 0.510289 0.00023001 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 8509.22 8509.22 -999.0 28.33 16.85 0.00849868 12.80 11.23 0.00849868 36.28 0.00562409 17.15 -999.0000 27.00 0.00858957 35.1250 8080.49 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 89724.669 59321.206 4.871525 0.00219735 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 81301.12 81301.12 -999.0 28.34 16.86 0.00849845 12.80 11.23 0.00849845 36.28 0.00562409 17.15 -999.0000 27.00 0.00859381 35.1423 77120.96 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9178.759 6069.716 0.498535 0.00022479 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 8316.54 8316.54 -999.0 28.33 16.86 0.00849863 12.80 11.23 0.00849863 36.28 0.00562409 17.15 -999.0000 27.00 0.00859168 35.1336 7897.71 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 440678.319 440678.319 23.412109 0.01079218 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 440678.32 440678.32 23.412109 0.50 0.50 0.00431558 40.00 20.06 0.00800000 0.50 0.00431558 0.50 1.4454 27.00 0.00850000 34.7602 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9391.961 9391.961 0.510289 0.00023001 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 9391.96 9391.96 0.510289 0.50 0.50 0.00431558 40.00 20.06 0.00800000 0.50 0.00431558 0.50 3.0634 27.00 0.00850000 34.7602 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 89724.669 89724.669 4.871525 0.00219735 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 89724.67 89724.67 4.871525 0.50 0.50 0.00431558 40.00 20.06 0.00800000 0.50 0.00431558 0.50 3.2089 24.65 0.00672007 31.6777 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9178.759 9178.759 0.498535 0.00022479 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 9178.76 9178.76 0.498535 0.50 0.50 0.00431558 40.00 20.06 0.00800000 0.50 0.00431558 0.50 3.1357 23.63 0.00458893 23.0671 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 14683.191 14683.191 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 14683.19 14683.19 23.412109 0.01 0.01 0.00843952 40.00 20.06 0.00800000 0.50 0.00431558 0.50 1.4454 27.00 0.00850000 34.7602 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 678.303 678.303 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 678.30 678.30 0.510289 0.02 0.02 0.00837181 40.00 20.06 0.00800000 0.50 0.00431558 0.50 3.0634 27.00 0.00850000 34.7602 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 6783.026 6783.026 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 6783.03 6783.03 4.871525 0.02 0.02 0.00664291 40.00 20.06 0.00800000 0.50 0.00431558 0.50 3.2089 24.65 0.00672007 31.6777 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 678.303 678.303 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 678.30 678.30 0.498535 0.02 0.02 0.00458036 40.00 20.06 0.00800000 0.50 0.00431558 0.50 3.1357 23.63 0.00458893 23.0671 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 14793.027 14793.027 1.618335 0.00012942 298.216 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 0.9025 0.920663   12/21 00:10:00 unknown unknown   12/21 00:10:00 Sensible 14793.03 14793.03 1.0000 1.76915477 1.618335 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.12940265 60.00 32.22 27.78 0.000 14793.03 0.50 0.00431558 0.50 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 46.9512 0.00 0.00 14847.57 14847.57 1.76915477 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 348924.611 348924.611 16.180778 0.00305254 8136.469 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 21.2874 21.715774 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 348924.61 348924.61 1.0000 17.68873284 16.180778 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 3.05223332 60.00 32.22 27.78 0.000 348924.61 0.50 0.00431558 0.50 0.00000000 0.0000 20.90 0.00800000 21.00 0.00800000 46.9512 201017.80 0.00 350073.12 350073.12 17.68873284 12.80 11.60 0.00800000 33059.8 32.21 18.76 0.00800000 52850.6
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 69854.324 69854.324 2.288205 0.00061112 1844.782 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 4.2617 4.347474 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 69854.32 69854.32 1.0000 2.50145230 2.288205 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.61105376 60.00 32.22 27.78 0.000 69854.32 0.50 0.00431558 0.50 0.00000000 0.0000 20.92 0.00800000 21.00 0.00800000 46.9512 48938.09 0.00 70101.75 70101.75 2.50145230 12.80 11.60 0.00800000 33059.8 40.28 21.27 0.00800000 61084.2
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 6280.028 6280.028 0.205410 0.00005494 165.962 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 0.3831 0.390846 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 6280.03 6280.03 1.0000 0.22455302 0.205410 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.05493482 60.00 32.22 27.78 0.000 6280.03 0.50 0.00431558 0.50 0.00000000 0.0000 20.87 0.00735091 21.00 0.00735091 43.1891 4404.86 0.00 6303.08 6303.08 0.22455302 12.80 11.60 0.00800000 33059.8 40.33 21.28 0.00800000 61129.3
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 4743.011 4743.011 0.155265 0.00004149 125.296 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 0.2894 0.295187 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 4743.01 4743.01 1.0000 0.16973429 0.155265 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.04148970 60.00 32.22 27.78 0.000 4743.01 0.50 0.00431558 0.50 0.00000000 0.0000 20.86 0.00746318 21.00 0.00746318 43.8409 3325.33 0.00 4760.08 4760.08 0.16973429 12.80 11.60 0.00800000 33059.8 40.30 21.27 0.00800000 61104.1
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 9106.447 9106.447 0.298428 0.00007967 240.444 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 0.5556 0.566751 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 9106.45 9106.45 1.0000 0.32624010 0.298428 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.07965904 60.00 32.22 27.78 0.000 9106.45 0.50 0.00431558 0.50 0.00000000 0.0000 20.91 0.00762684 21.00 0.00762684 44.7901 6380.69 0.00 9138.36 9138.36 0.32624010 12.80 11.60 0.00800000 33059.8 40.27 21.26 0.00800000 61071.0
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 3123.485 3123.485 0.130669 0.00002733 75.106 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 0.1906 0.194394 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 3123.49 3123.49 1.0000 0.14284706 0.130669 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.02732282 60.00 32.22 27.78 0.000 3123.49 0.50 0.00431558 0.50 0.00000000 0.0000 20.87 0.00691939 21.00 0.00691939 40.6817 1931.56 0.00 3133.61 3133.61 0.14284706 12.80 11.60 0.00800000 33059.8 34.31 19.44 0.00800000 54996.6
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 169975.231 169975.231 5.581843 0.00148702 4483.710 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 10.3699 10.578628 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 169975.23 169975.23 1.0000 6.10203796 5.581843 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 1.48686578 60.00 32.22 27.78 0.000 169975.23 0.50 0.00431558 0.50 0.00000000 0.0000 20.95 0.00777456 21.00 0.00777456 45.6468 118978.37 0.00 170540.21 170540.21 6.10203796 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61007.9
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 113858.048 113858.048 3.739350 0.00099608 3003.289 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 6.9463 7.086103 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 113858.05 113858.05 1.0000 4.08783528 3.739350 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.99597827 60.00 32.22 27.78 0.000 113858.05 0.50 0.00431558 0.50 0.00000000 0.0000 20.95 0.00778157 21.00 0.00778157 45.6875 79694.10 0.00 114235.58 114235.58 4.08783528 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61005.1
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 171359.313 171359.313 5.627405 0.00149913 4520.180 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 10.4544 10.664768 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 171359.31 171359.31 1.0000 6.15184613 5.627405 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 1.49897310 60.00 32.22 27.78 0.000 171359.31 0.50 0.00431558 0.50 0.00000000 0.0000 20.95 0.00777757 21.00 0.00777757 45.6643 119945.86 0.00 171928.60 171928.60 6.15184613 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61007.3
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 104241.242 104241.242 3.422831 0.00091195 2749.872 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 6.3596 6.487588 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 104241.24 104241.24 1.0000 3.74181930 3.422831 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.91185483 60.00 32.22 27.78 0.000 104241.24 0.50 0.00431558 0.50 0.00000000 0.0000 20.95 0.00774593 21.00 0.00774593 45.4810 72971.49 0.00 104588.69 104588.69 3.74181930 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61011.1
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 21873.291 21873.291 0.718683 0.00019136 576.846 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 1.3345 1.361313 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 21873.29 21873.29 1.0000 0.78566048 0.718683 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.19133757 60.00 32.22 27.78 0.000 21873.29 0.50 0.00431558 0.50 0.00000000 0.0000 20.95 0.00780558 21.00 0.00780558 45.8267 15306.88 0.00 21944.98 21944.98 0.78566048 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60991.7
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 14531.197 14531.197 0.477475 0.00012713 383.209 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 0.8865 0.904368 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 14531.20 14531.20 1.0000 0.52197281 0.477475 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.12711228 60.00 32.22 27.78 0.000 14531.20 0.50 0.00431558 0.50 0.00000000 0.0000 20.95 0.00780574 21.00 0.00780574 45.8277 10168.65 0.00 14578.75 14578.75 0.52197281 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60989.9
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 22022.540 22022.540 0.723597 0.00019266 580.779 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 1.3436 1.370601 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 22022.54 22022.54 1.0000 0.79103157 0.723597 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.19264314 60.00 32.22 27.78 0.000 22022.54 0.50 0.00431558 0.50 0.00000000 0.0000 20.95 0.00780701 21.00 0.00780701 45.8350 15411.22 0.00 22094.70 22094.70 0.79103157 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60991.3
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 13755.203 13755.203 0.451934 0.00012034 362.760 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 0.8392 0.856073 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 13755.20 13755.20 1.0000 0.49405207 0.451934 12.80 10.74 0.00800000 33059.8 40.00 20.06 0.00800000 60796.0 0.12032424 60.00 32.22 27.78 0.000 13755.20 0.50 0.00431558 0.50 0.00000000 0.0000 20.95 0.00779308 21.00 0.00779308 45.7543 9626.12 0.00 13800.33 13800.33 0.49405207 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60992.8
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 185653.916 -999.000 10.031023 0.00530968 -999.000 -999.0000 1.00000 1.00000 1020.0171 1004.8586 1.0932 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.031023 10.96585673   4197.9300 999.8980 64.80500232 15.00 6.67 8.33 2266150.37 8.1925 8.192480 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 185653.92 185653.92 1.0000 10.96585673 10.031023 27.46 16.30 0.00816435 48428.2 10.86 10.10 0.00816435 31498.1 5.30913686 6.67 15.00 8.33 21676.507 163977.41 40.80 0.00563111 18.58 2.03050000 20.2422 24.00 0.00882161 24.00 0.00882161 43.0921 123160.23 0.00 200663.21 190959.11 10.96585673 27.46 17.31 0.00816435 48428.2 10.39 10.37 0.00781322 30129.3
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 31993.738 31993.738 3.009307 0.00027990 547.550 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 10.031023 10.96585673   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 1.9519 1.991172 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 31993.74 31993.74 1.0000 3.28975702 3.009307 3.12 2.50 0.00473115 14996.7 12.80 10.74 0.00800000 33059.8 0.27986663 60.00 32.22 27.78 0.000 31993.74 0.50 0.00431558 0.50 2.03050000 67.4740 8.56 0.00559323 21.64 0.00625069 35.3634 16042.44 0.00 32224.32 32224.32 3.28975702 2.80 2.80 0.00473115 14670.5 12.46 7.88 0.00473115 24465.9
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1779365.978 -999.000 94.452465 0.05088964 -999.000 -999.0000 1.00000 1.00000 1019.8969 1004.8586 1.0932 VAV_MID WITH REHEAT FAN Fan:VariableVolume 94.452465 103.25488843   4197.9300 999.8980 64.80500232 15.00 6.67 8.33 2266150.37 78.5193 78.519325 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 1779365.98 1779365.98 1.0000 103.25488843 94.452465 27.76 16.35 0.00809969 48567.6 10.86 10.04 0.00809969 31334.8 50.88445046 6.67 15.00 8.33 204106.747 1575259.23 40.80 0.00563111 18.58 20.30600000 21.4986 24.00 0.00881128 24.00 0.00881128 43.0418 1133966.31 0.00 1922023.58 1837302.20 103.25488843 27.76 17.36 0.00809969 48567.6 10.31 10.29 0.00777411 29953.2
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 216417.777 216417.777 28.335739 0.00189332 3772.861 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 VAV_MID WITH REHEAT FAN Fan:VariableVolume 94.452465 103.25488843   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 13.2033 13.469040 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 216417.78 216417.78 1.0000 30.97646653 28.335739 5.85 4.58 0.00526200 19092.7 12.80 10.74 0.00800000 33059.8 1.89312399 60.00 32.22 27.78 0.000 216417.78 0.50 0.00431558 0.50 20.30600000 71.6621 19.37 0.00765532 19.61 0.00732612 46.8939 249429.73 0.00 225803.61 225803.61 30.97646653 2.80 2.80 0.00526200 16000.9 9.98 7.32 0.00526200 23290.4
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 196088.437 -999.000 10.782583 0.00560810 -999.000 -999.0000 1.00000 1.00000 1020.0093 1004.8586 1.0932 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.782583 11.78745744   4197.9300 999.8980 64.80500232 15.00 6.67 8.33 2266150.37 8.6529 8.652931 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 Sensible 196088.44 196088.43 1.0000 11.78745744 10.782583 27.18 16.20 0.00816013 48133.2 10.87 10.10 0.00816013 31497.9 5.60753238 6.67 15.00 8.33 23176.780 172911.66 40.80 0.00563111 18.58 2.03050000 18.8313 24.00 0.00875107 24.00 0.00875107 42.7516 133955.29 0.00 212147.52 201904.99 11.78745744 27.18 17.21 0.00816013 48133.2 10.39 10.37 0.00781535 30135.5
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 20993.961 20993.961 3.234775 0.00018366 368.702 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.782583 11.78745744   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 1.2808 1.306586 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 05:50:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 Sensible 20993.96 20993.96 1.0000 3.53623723 3.234775 6.89 5.47 0.00557598 20941.9 12.80 10.74 0.00800000 33059.8 0.18364559 60.00 32.22 27.78 0.000 20993.96 0.50 0.00431558 0.50 2.03050000 62.7710 17.67 0.00770111 17.60 0.00746132 54.1694 28471.41 0.00 22210.09 22210.09 3.53623723 2.80 2.80 0.00557598 16787.8 8.99 7.21 0.00557598 23068.5
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 105042.041 -999.000 5.680268 0.00300419 -999.000 -999.0000 1.00000 1.00000 1020.1273 1004.8586 1.0932 CAV_BAS FAN Fan:ConstantVolume 5.680268 6.20963574   4197.9300 999.8980 64.80500232 15.00 6.67 8.33 2266150.37 4.6353 4.635263 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 105042.04 105042.04 1.0000 6.20963574 5.680268 27.86 16.48 0.00822360 48989.2 11.28 10.34 0.00822360 32073.3 3.00388262 6.67 15.00 8.33 9631.771 95410.27 40.13 0.00563007 18.37 1.20015641 21.1285 24.00 0.00903993 24.00 0.00903993 44.1440 62638.36 0.00 113371.81 108962.98 6.20963574 27.86 17.50 0.00822360 48989.2 10.66 10.62 0.00794194 30731.8
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 248933.043 248933.043 5.680268 0.00217777 5597.643 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 CAV_BAS FAN Fan:ConstantVolume 5.680268 6.20963574   4197.9300 999.8980 14.05537422 54.44 82.22 27.78 1639116.59 15.1870 15.492670 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 248933.04 248933.04 1.0000 6.20963574 5.680268 0.11 0.11 0.00431558 10900.0 40.00 20.06 0.00800000 60796.0 2.17755270 60.00 32.22 27.78 0.000 248933.04 0.50 0.00431558 0.50 1.20015641 21.1285 0.00 0.00431558 25.34 0.00431558 19.6025 0.00 0.00 211170.36 211170.36 6.20963574 12.80 7.56 0.00431558 23757.7 46.38 20.38 0.00431558 57764.5
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 440678.319 288368.908 23.412109 0.01079218 -999.000 -999.0000 -999.00000 -999.00000 1020.6415 1004.8586 1.0932 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 400754.58 400741.56 0.9094 -999.0 -999.0 28.73 16.99 0.00850024 50583.8 12.80 11.23 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 400754.58 40.80 0.00563111 18.58 0.33839277 -999.0000 27.00 0.00854237 27.00 0.00854237 34.9368 370426.78 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9391.961 6211.813 0.510289 0.00023001 -999.000 -999.0000 -999.00000 -999.00000 1020.6386 1004.8586 1.0932 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 Sensible 8509.22 8509.22 0.9060 -999.0 -999.0 28.33 16.85 0.00849868 50164.9 12.80 11.23 0.00849868 34318.9 -999.0 -999.00 -999.00 -999.00 0.000 8509.22 36.28 0.00562409 17.15 0.01563234 -999.0000 27.00 0.00858957 27.00 0.00858957 35.1250 8080.49 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 89724.669 59321.206 4.871525 0.00219735 -999.000 -999.0000 -999.00000 -999.00000 1020.6382 1004.8586 1.0932 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 Sensible 81301.12 81301.12 0.9061 -999.0 -999.0 28.34 16.86 0.00849845 50178.1 12.80 11.23 0.00849845 34318.3 -999.0 -999.00 -999.00 -999.00 0.000 81301.12 36.28 0.00562409 17.15 0.15632344 -999.0000 27.00 0.00859381 27.00 0.00859381 35.1423 77120.96 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9178.759 6069.716 0.498535 0.00022479 -999.000 -999.0000 -999.00000 -999.00000 1020.6385 1004.8586 1.0932 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 8316.54 8316.54 0.9061 -999.0 -999.0 28.33 16.86 0.00849863 50171.5 12.80 11.23 0.00849863 34318.7 -999.0 -999.00 -999.00 -999.00 0.000 8316.54 36.28 0.00562409 17.15 0.01563234 -999.0000 27.00 0.00859168 27.00 0.00859168 35.1336 7897.71 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 440678.319 440678.319 23.412109 0.01079218 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 440678.32 440678.32 1.0000 25.59398240 23.412109 0.50 0.50 0.00431558 11299.5 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 440678.32 0.50 0.00431558 0.50 0.33839277 1.4454 0.00 0.00850000 27.00 0.00850000 34.7602 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9391.961 9391.961 0.510289 0.00023001 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 9391.96 9391.96 1.0000 0.55784502 0.510289 0.50 0.50 0.00431558 11299.5 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9391.96 0.50 0.00431558 0.50 0.01563234 3.0634 0.00 0.00850000 27.00 0.00850000 34.7602 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 89724.669 89724.669 4.871525 0.00219735 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 89724.67 89724.67 1.0000 5.32552337 4.871525 0.50 0.50 0.00431558 11299.5 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 89724.67 0.50 0.00431558 0.50 0.15632344 3.2089 0.00 0.00672007 24.65 0.00672007 31.6777 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9178.759 9178.759 0.498535 0.00022479 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.0932 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 9178.76 9178.76 1.0000 0.54499526 0.498535 0.50 0.50 0.00431558 11299.5 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9178.76 0.50 0.00431558 0.50 0.01563234 3.1357 0.00 0.00458893 23.63 0.00458893 23.0671 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 14683.191 14683.191 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 23.412109 25.59398240   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 14683.19 14683.19 1.0000 25.59398240 23.412109 0.01 0.01 0.00843952 21114.1 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 14683.19 0.50 0.00431558 0.50 0.33839277 1.4454 0.00 0.00850000 27.00 0.00850000 34.7602 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 678.303 678.303 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.510289 0.55784502   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 678.30 678.30 1.0000 0.55784502 0.510289 0.02 0.02 0.00837181 20953.0 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 678.30 0.50 0.00431558 0.50 0.01563234 3.0634 0.00 0.00850000 27.00 0.00850000 34.7602 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 6783.026 6783.026 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.871525 5.32552337   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 6783.03 6783.03 1.0000 5.32552337 4.871525 0.02 0.02 0.00664291 16629.8 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6783.03 0.50 0.00431558 0.50 0.15632344 3.2089 0.00 0.00672007 24.65 0.00672007 31.6777 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 678.303 678.303 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.498535 0.54499526   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 678.30 678.30 1.0000 0.54499526 0.498535 0.02 0.02 0.00458036 11471.1 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 678.30 0.50 0.00431558 0.50 0.01563234 3.1357 0.00 0.00458893 23.63 0.00458893 23.0671 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 10.03 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 94.45 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 10.78 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 5.68 -      
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER DifferentialDryBulb 0.34 23.41 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2464.83 1164.83 437.83
CORE_BOTTOM 2295.67 627.67 24.67
CORE_MID 1680.17 1899.17 137.17
CORE_TOP 1684.00 2648.83 249.33
PERIMETER_BOT_ZN_3 2116.33 2246.17 124.17
PERIMETER_BOT_ZN_2 2816.50 1732.33 253.17
PERIMETER_BOT_ZN_1 3152.67 1302.17 250.83
PERIMETER_BOT_ZN_4 3790.17 922.50 451.17
PERIMETER_MID_ZN_3 2024.33 3000.17 358.33
PERIMETER_MID_ZN_2 2262.83 2006.33 374.83
PERIMETER_MID_ZN_1 2983.17 1699.83 326.83
PERIMETER_MID_ZN_4 2759.00 2222.17 355.67
PERIMETER_TOP_ZN_3 2535.67 3190.67 843.67
PERIMETER_TOP_ZN_2 2912.00 2540.00 620.00
PERIMETER_TOP_ZN_1 3035.50 2025.33 503.83
PERIMETER_TOP_ZN_4 2928.33 2521.33 629.17
DATACENTER_BOT_ZN_6 5943.00 1295.50 1295.50
DATACENTER_MID_ZN_6 5943.00 508.67 508.67
DATACENTER_TOP_ZN_6 5790.67 635.50 624.00
DATACENTER_BASEMENT_ZN_6 5943.00 5756.33 5756.33
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5913.67 5789.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 70.00 0.00 6.83
CORE_BOTTOM 0.00 7.00 0.00 0.33
CORE_MID 0.00 0.17 0.00 0.00
CORE_TOP 0.17 0.50 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 47.17 0.00 25.00
PERIMETER_BOT_ZN_2 0.00 95.67 0.00 77.67
PERIMETER_BOT_ZN_1 0.00 133.67 0.00 105.67
PERIMETER_BOT_ZN_4 0.00 331.00 0.00 125.50
PERIMETER_MID_ZN_3 0.33 35.83 0.00 21.17
PERIMETER_MID_ZN_2 0.33 102.50 0.00 77.67
PERIMETER_MID_ZN_1 0.00 164.33 0.00 145.67
PERIMETER_MID_ZN_4 0.00 126.67 0.00 53.33
PERIMETER_TOP_ZN_3 5.00 63.50 0.17 36.00
PERIMETER_TOP_ZN_2 3.50 120.33 0.00 78.17
PERIMETER_TOP_ZN_1 1.83 109.67 0.00 74.67
PERIMETER_TOP_ZN_4 1.83 142.17 0.00 57.67
DATACENTER_BOT_ZN_6 0.00 721.00 0.00 586.00
DATACENTER_MID_ZN_6 0.00 625.17 0.00 515.50
DATACENTER_TOP_ZN_6 0.00 522.67 0.00 427.50
DATACENTER_BASEMENT_ZN_6 0.00 1033.00 0.00 796.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 5.33 1667.50 0.17 1140.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.29 149.60 6779.02 1.263 0.000 0.000 0.000
CORE_BOTTOM 55.04 134.35 6849.35 0.887 0.000 0.000 0.000
CORE_MID 55.04 134.35 6849.35 0.647 0.000 0.000 0.000
CORE_TOP 55.04 134.35 6849.35 0.606 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.91 16.87 860.00 0.821 0.035 0.000 0.000
PERIMETER_BOT_ZN_2 4.45 10.87 554.22 1.228 0.036 0.000 0.000
PERIMETER_BOT_ZN_1 6.91 16.87 860.02 1.433 0.035 0.000 0.000
PERIMETER_BOT_ZN_4 4.45 10.87 554.22 1.784 0.036 0.000 0.000
PERIMETER_MID_ZN_3 6.91 16.87 860.00 0.679 0.081 0.000 0.000
PERIMETER_MID_ZN_2 3.88 10.87 554.22 1.084 0.091 0.000 0.000
PERIMETER_MID_ZN_1 6.91 16.87 860.02 1.263 0.082 0.000 0.000
PERIMETER_MID_ZN_4 4.45 10.87 554.22 1.083 0.084 0.000 0.000
PERIMETER_TOP_ZN_3 6.91 16.87 860.00 0.666 0.101 0.000 0.000
PERIMETER_TOP_ZN_2 4.45 10.87 554.22 1.090 0.105 0.000 0.000
PERIMETER_TOP_ZN_1 6.91 16.87 860.02 1.308 0.101 0.000 0.000
PERIMETER_TOP_ZN_4 4.45 10.87 554.22 1.073 0.105 0.000 0.000
DATACENTER_BOT_ZN_6 0.80 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.80 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.80 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.28 42.18 1911.37 27.035 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.29 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.04 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.04 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.04 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.91 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.45 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.91 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.45 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.91 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.88 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.91 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.45 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.91 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.45 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.91 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.45 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.28 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 61.29 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.04 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.04 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.04 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.91 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.45 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.91 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.45 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.91 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.88 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.91 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.45 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.91 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.45 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.91 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.45 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.80 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.80 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.80 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.28 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1015.76 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 53724097.52 0.00 53724097.52 0.00 53724097.52 37848132.68 3848.79 2333.17 2578.04 362.01
CORE_BOTTOM 38816127.41 0.00 38816127.41 0.00 38816127.41 33990283.35 5551.43 14.23 3194.33 576.85
CORE_MID 0.27E+09 0.00 0.27E+09 0.00 0.27E+09 0.34E+09 6113.11 110.02 2536.87 155.74
CORE_TOP 25144317.42 0.00 25144317.42 0.00 25144317.42 33990283.35 6181.31 223.15 2355.55 183.37
PERIMETER_BOT_ZN_3 4523366.57 0.00 4523366.57 347995.63 4871362.19 4267819.30 3889.09 54.14 4816.77 576.85
PERIMETER_BOT_ZN_2 4226751.84 0.00 4226751.84 231996.93 4458748.76 2750345.05 3710.10 37.77 5012.13 576.85
PERIMETER_BOT_ZN_1 7599587.54 0.00 7599587.54 347995.63 7947583.17 4267912.63 3642.96 29.91 5087.13 576.85
PERIMETER_BOT_ZN_4 6188403.31 0.00 6188403.31 231996.93 6420400.24 2750345.05 3467.97 12.61 5279.42 576.85
PERIMETER_MID_ZN_3 35189632.02 0.00 35189632.02 816132.14 36005764.16 42678193.03 4573.91 129.62 4056.47 155.74
PERIMETER_MID_ZN_2 36272969.07 0.00 36272969.07 544087.72 36817056.79 27503450.52 4341.23 90.79 4327.97 1009.24
PERIMETER_MID_ZN_1 64493851.89 0.00 64493851.89 816132.14 65309984.03 42679126.28 4038.32 92.20 4629.49 155.74
PERIMETER_MID_ZN_4 35907026.51 0.00 35907026.51 544087.72 36451114.23 27503450.52 4141.18 161.03 4457.79 155.74
PERIMETER_TOP_ZN_3 3464644.61 0.00 3464644.61 1013296.28 4477940.89 4267819.30 4276.20 249.27 4234.53 183.37
PERIMETER_TOP_ZN_2 3602295.44 0.00 3602295.44 675530.39 4277825.83 2750345.05 4041.45 135.60 4582.95 183.37
PERIMETER_TOP_ZN_1 6688549.16 0.00 6688549.16 1013296.28 7701845.44 4267912.63 4055.54 132.81 4571.65 183.37
PERIMETER_TOP_ZN_4 3569582.16 0.00 3569582.16 675530.39 4245112.55 2750345.05 4031.26 123.10 4605.64 183.37
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.46E+09 0.00 0.46E+09 0.00 0.46E+09 10671554.30 694.45 1549.50 6516.05 2479.53
Total Facility 0.50E+10 0.00 0.50E+10 31742035.64 0.51E+10 0.50E+10 7254.45 4360.88 8063.10 3333.70


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.3314 0.0000 2.3314 0.0000 2.3314 1.2002 1299.24 2330.96 2312.80
CORE_BOTTOM 1.6537 0.0000 1.6537 0.0000 1.6537 1.0778 3270.03 10.22 2662.74
CORE_MID 12.0510 0.0000 12.0510 0.0000 12.0510 10.7782 3444.73 109.85 2388.42
CORE_TOP 1.1293 0.0000 1.1293 0.0000 1.1293 1.0778 3510.85 223.15 2209.01
PERIMETER_BOT_ZN_3 0.1922 0.0000 0.1922 0.0081 0.2003 0.1353 1600.25 49.53 4293.22
PERIMETER_BOT_ZN_2 0.1853 0.0000 0.1853 0.0054 0.1907 0.0872 1421.15 32.76 4489.08
PERIMETER_BOT_ZN_1 0.3357 0.0000 0.3357 0.0081 0.3438 0.1353 1354.12 25.34 4563.54
PERIMETER_BOT_ZN_4 0.2690 0.0000 0.2690 0.0054 0.2745 0.0872 1180.79 8.25 4753.97
PERIMETER_MID_ZN_3 1.5900 0.0000 1.5900 0.0191 1.6090 1.3533 1905.74 129.46 3907.80
PERIMETER_MID_ZN_2 1.6353 0.0000 1.6353 0.0137 1.6490 0.8721 1457.38 86.13 3490.49
PERIMETER_MID_ZN_1 2.9576 0.0000 2.9576 0.0191 2.9767 1.3533 1369.82 92.03 4481.15
PERIMETER_MID_ZN_4 1.6331 0.0000 1.6331 0.0127 1.6458 0.8721 1472.74 160.86 4309.39
PERIMETER_TOP_ZN_3 0.1561 0.0000 0.1561 0.0237 0.1798 0.1353 1607.93 249.07 4086.00
PERIMETER_TOP_ZN_2 0.1644 0.0000 0.1644 0.0158 0.1802 0.0872 1372.80 135.38 4434.82
PERIMETER_TOP_ZN_1 0.3066 0.0000 0.3066 0.0237 0.3303 0.1353 1385.40 132.81 4424.79
PERIMETER_TOP_ZN_4 0.1619 0.0000 0.1619 0.0158 0.1777 0.0872 1361.33 123.10 4458.57
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 13.8832 0.0000 13.8832 0.0000 13.8832 0.3384 356.98 1549.50 4036.52
Total Facility 220.6033 0.0000 220.6033 0.7512 221.3545 158.4706 4437.45 4352.94 5582.90


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 73322842.68 0.00 73322842.68 48026705.38 3338.63 4.02 5417.35 576.85
VAV_MID WITH REHEAT 0.53E+09 0.00 0.53E+09 0.48E+09 3905.35 4.85 4849.80 155.74
VAV_TOP WITH REHEAT 50754048.19 0.00 50754048.19 48026705.38 3990.04 2.64 4767.32 183.37
CAV_BAS 64204250.39 0.00 64204250.39 37848132.68 3828.34 1.89 4929.77 362.01
AIRLOOP DATACENTER BASEMENT 0.55E+09 0.00 0.55E+09 10671554.30 694.45 0.00 8065.55 2479.53
AIRLOOP DATACENTER BOT 291951.72 0.00 291951.72 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 2919517.21 0.00 2919517.21 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 291951.72 0.00 291951.72 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.1500 0.0000 3.1500 1.5229 1081.10 0.92 4860.98
VAV_MID WITH REHEAT 23.7698 0.0000 23.7698 15.2292 1239.03 4.64 4699.32
VAV_TOP WITH REHEAT 2.2925 0.0000 2.2925 1.5229 1320.11 2.58 4620.31
CAV_BAS 2.7862 0.0000 2.7862 1.2002 1296.97 0.31 4645.72
AIRLOOP DATACENTER BASEMENT 16.5914 0.0000 16.5914 0.3384 356.98 0.00 5586.02
AIRLOOP DATACENTER BOT 0.0136 0.0000 0.0136 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1365 0.0000 0.1365 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0136 0.0000 0.0136 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 155.98 3096.08 0.00 0.00 0.00 2195.51 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 551.68 2192.90 0.00 0.00 0.00 2163.39 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 95.88 2429.52 0.00 0.00 0.00 2377.15 0.00 0.00 0.00
CAV_BAS 0.00 2330.58 2683.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 1549.50 6516.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 2.3873 5.5436 0.0000 0.0000 0.0000 1.9824 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 24.0693 41.3248 0.0000 0.0000 0.0000 20.2285 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 2.3209 3.8662 0.0000 0.0000 0.0000 1.9834 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.4346 5.6939 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4045 24.2755 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0187 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.1869 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0187 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1515
Defaulted Fields 1183
Fields with Defaults 3871
Autosized Fields 333
Autosizable Fields 411
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 29310.18 313969.00 21-JAN-04:00 1972025.41 25-AUG-15:10
Electricity:Building 17133.94 216479.19 07-MAY-17:20 1025582.59 01-DEC-16:30
Electricity:Zone:BASEMENT 590.13 14055.89 01-JAN-00:10 28201.58 02-JAN-08:10
Electricity:SpaceType:GENERAL 17133.94 216479.19 07-MAY-17:20 1025582.59 01-DEC-16:30
InteriorLights:Electricity 2457.54 9223.03 02-APR-17:20 247210.90 28-NOV-16:30
InteriorLights:Electricity:Zone:BASEMENT 165.73 598.35 01-JAN-00:10 14744.03 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2457.54 9223.03 02-APR-17:20 247210.90 28-NOV-16:30
LightsWired:InteriorLights:Electricity 2457.54 9223.03 02-APR-17:20 247210.90 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 165.73 598.35 01-JAN-00:10 14744.03 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2457.54 9223.03 02-APR-17:20 247210.90 28-NOV-16:30
Electricity:Zone:CORE_BOTTOM 438.45 4990.59 01-JAN-00:10 30447.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
Electricity:Zone:CORE_MID 4384.49 49905.77 01-JAN-00:10 304477.41 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1488.37 5373.60 01-JAN-00:10 132411.79 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1488.37 5373.60 01-JAN-00:10 132411.79 02-JAN-08:10
Electricity:Zone:CORE_TOP 438.45 4990.58 01-JAN-00:10 30447.74 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 148.84 537.36 01-JAN-00:10 13241.18 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 46.98 603.11 02-APR-17:10 3823.11 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 10.61 43.94 01-JAN-09:30 1662.56 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 10.61 43.94 01-JAN-09:30 1662.56 28-NOV-16:30
Electricity:Zone:PERIMETER_BOT_ZN_2 30.19 388.67 02-APR-17:10 2463.76 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 6.75 28.32 01-JAN-07:50 1071.42 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 6.75 28.32 01-JAN-07:50 1071.42 28-NOV-16:30
Electricity:Zone:PERIMETER_BOT_ZN_1 46.81 603.12 12-MAR-17:10 3823.18 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 10.44 43.94 01-JAN-07:50 1662.60 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 10.44 43.94 01-JAN-07:50 1662.60 28-NOV-16:30
Electricity:Zone:PERIMETER_BOT_ZN_4 30.24 388.67 12-MAR-17:10 2463.75 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 6.80 28.32 01-JAN-09:30 1071.42 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 6.80 28.32 01-JAN-09:30 1071.42 28-NOV-16:30
Electricity:Zone:PERIMETER_MID_ZN_3 469.53 6031.15 02-APR-17:10 38231.14 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 105.88 439.44 01-JAN-09:30 16625.62 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 105.88 439.44 01-JAN-09:30 16625.62 28-NOV-16:30
Electricity:Zone:PERIMETER_MID_ZN_2 301.78 3886.70 02-APR-17:10 24637.60 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 67.42 283.19 01-JAN-07:50 10714.18 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 67.42 283.19 01-JAN-07:50 10714.18 28-NOV-16:30
Electricity:Zone:PERIMETER_MID_ZN_1 467.96 6031.24 12-MAR-17:10 38231.83 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 104.30 439.45 01-JAN-07:50 16625.99 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 104.30 439.45 01-JAN-07:50 16625.99 28-NOV-16:30
Electricity:Zone:PERIMETER_MID_ZN_4 302.23 3886.68 12-MAR-17:10 24637.51 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 67.88 283.19 01-JAN-09:20 10714.18 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 67.88 283.19 01-JAN-09:20 10714.18 28-NOV-16:30
Electricity:Zone:PERIMETER_TOP_ZN_3 46.95 603.11 02-APR-17:10 3823.11 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 10.59 43.94 01-JAN-09:30 1662.56 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 10.59 43.94 01-JAN-09:30 1662.56 28-NOV-16:30
Electricity:Zone:PERIMETER_TOP_ZN_2 30.18 388.67 02-APR-17:10 2463.76 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 6.74 28.32 01-JAN-07:50 1071.42 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 6.74 28.32 01-JAN-07:50 1071.42 28-NOV-16:30
Electricity:Zone:PERIMETER_TOP_ZN_1 46.80 603.12 12-MAR-17:10 3823.18 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 10.43 43.94 01-JAN-07:50 1662.60 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 10.43 43.94 01-JAN-07:50 1662.60 28-NOV-16:30
Electricity:Zone:PERIMETER_TOP_ZN_4 30.22 388.67 12-MAR-17:10 2463.75 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 6.79 28.32 01-JAN-09:20 1071.42 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 6.79 28.32 01-JAN-09:20 1071.42 28-NOV-16:30
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7542.47 95139.07 01-JAN-00:10 383789.71 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 47.61 230.94 01-JAN-00:10 4157.19 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 47.61 230.94 01-JAN-00:10 4157.19 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 157.51 1966.20 01-JAN-00:10 8111.05 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1575.07 19661.97 01-JAN-00:10 81110.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 36.26 175.92 01-JAN-00:10 3166.31 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 36.26 175.92 01-JAN-00:10 3166.31 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 157.51 1966.20 01-JAN-00:10 8111.05 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 3.63 17.59 01-JAN-00:10 316.63 02-JAN-08:10
InteriorEquipment:Electricity 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 14676.40 207256.16 01-JAN-00:10 778371.69 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5334.97 88964.76 01-JAN-00:10 305206.10 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 289.61 4453.23 01-JAN-00:10 17206.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 2896.13 44532.17 01-JAN-00:10 172065.63 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 289.61 4453.22 01-JAN-00:10 17206.56 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 363.65 5591.71 01-JAN-00:10 21605.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 234.35 3603.51 01-JAN-00:10 13923.42 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 363.66 5591.79 01-JAN-00:10 21605.85 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 234.35 3603.49 01-JAN-00:10 13923.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 36.37 559.17 01-JAN-00:10 2160.55 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 23.44 360.35 01-JAN-00:10 1392.34 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 36.37 559.18 01-JAN-00:10 2160.58 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 23.44 360.35 01-JAN-00:10 1392.33 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 3554.45 3711.47 01-JAN-05:50 408768.07 05-SEP-07:40
HeatRejection:Electricity 1158.60 296.07 01-JAN-08:00 77358.81 13-JUL-18:00
General:HeatRejection:Electricity 1158.60 296.07 01-JAN-08:00 77358.81 13-JUL-18:00
Electricity:HVAC 6416.48 51260.97 21-JAN-04:00 543236.38 25-AUG-15:10
ExteriorEquipment:Electricity 1909.29 28161.90 01-JAN-00:10 116885.78 20-JAN-08:40
Transformer:ExteriorEquipment:Electricity 54.68 979.82 01-JAN-00:10 3412.97 01-DEC-16:40
ElectricityPurchased:Facility 29310.18 313969.00 21-JAN-04:00 1972025.41 25-AUG-15:10
ElectricityPurchased:Plant 29310.18 313969.00 21-JAN-04:00 1972025.41 25-AUG-15:10
Cogeneration:ElectricityPurchased 29310.18 313969.00 21-JAN-04:00 1972025.41 25-AUG-15:10
General:Cogeneration:ElectricityPurchased 29310.18 313969.00 21-JAN-04:00 1972025.41 25-AUG-15:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 29310.18 313969.00 21-JAN-04:00 1972025.41 25-AUG-15:10
ElectricityNet:Plant 29310.18 313969.00 21-JAN-04:00 1972025.41 25-AUG-15:10
Cogeneration:ElectricityNet 29310.18 313969.00 21-JAN-04:00 1972025.41 25-AUG-15:10
General:Cogeneration:ElectricityNet 29310.18 313969.00 21-JAN-04:00 1972025.41 25-AUG-15:10
Fans:Electricity 2725.16 45198.98 01-JAN-21:30 268224.52 19-JUN-15:00
General:Fans:Electricity 2725.16 45198.98 01-JAN-21:30 268224.52 19-JUN-15:00
ExteriorLights:Electricity 350.70 0.00 01-JAN-07:30 40855.88 01-JAN-06:10
General:ExteriorLights:Electricity 350.70 0.00 01-JAN-07:30 40855.88 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
Cooling:Electricity 3858.36 2548.03 02-JAN-07:10 446424.21 11-AUG-15:50
General:Cooling:Electricity 3858.36 2548.03 02-JAN-07:10 446424.21 11-AUG-15:50
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 1609.69 0.00 08-JAN-06:00 100000.00 01-JAN-13:30
General:Humidifier:Electricity 1609.69 0.00 08-JAN-06:00 100000.00 01-JAN-13:30
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 564.44 3395.03 01-JAN-00:30 47736.35 02-NOV-13:30
General:Pumps:Electricity 564.44 3395.03 01-JAN-00:30 47736.35 02-NOV-13:30
WIRED_LTG_ELECTRICITY 69.06 0.00 01-JAN-00:10 6946.63 28-NOV-16:40
WIRED_INT_EQUIP 5334.97 88964.76 31-MAR-23:10 305206.10 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 733.78 7280.88 18-MAR-16:10 561954.11 06-DEC-07:10
NaturalGas:Plant 733.78 7280.88 18-MAR-16:10 561954.11 06-DEC-07:10
Heating:NaturalGas 86.74 0.00 01-JAN-00:10 531907.45 06-DEC-07:10
Boiler:Heating:NaturalGas 86.74 0.00 01-JAN-00:10 531907.45 06-DEC-07:10
WaterSystems:NaturalGas 647.04 7280.88 02-JAN-05:20 76823.81 23-JAN-12:20
Water Heater:WaterSystems:NaturalGas 647.04 7280.88 02-JAN-05:20 76823.81 23-JAN-12:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 20718.15 8730.27 02-JAN-07:10 2485224.17 11-AUG-15:50
PlantLoopCoolingDemand:HVAC 20718.15 8730.27 02-JAN-07:10 2485224.17 11-AUG-15:50
CoolingCoils:PlantLoopCoolingDemand 20718.15 8730.27 02-JAN-07:10 2485224.17 11-AUG-15:50


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 16618.12 0.00 08-JAN-06:00 0.00 27-JUN-12:00
Water:HVAC 598.80 0.00 08-JAN-06:00 0.00 15-JAN-13:00
Humidifier:Water 598.80 0.00 08-JAN-06:00 0.00 15-JAN-13:00
General:Humidifier:Water 598.80 0.00 08-JAN-06:00 0.00 15-JAN-13:00
MainsWater:Facility 16618.12 0.00 08-JAN-06:00 0.00 27-JUN-12:00
MainsWater:HVAC 598.80 0.00 08-JAN-06:00 0.00 15-JAN-13:00
Humidifier:MainsWater 598.80 0.00 08-JAN-06:00 0.00 15-JAN-13:00
General:Humidifier:MainsWater 598.80 0.00 08-JAN-06:00 0.00 15-JAN-13:00
Water:Plant 16019.32 0.00 01-JAN-00:10 0.00 27-JUN-12:00
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 16019.32 0.00 01-JAN-00:10 0.00 27-JUN-12:00
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 13739.15 0.00 01-JAN-00:10 0.00 27-JUN-15:00
General:HeatRejection:Water 13739.15 0.00 01-JAN-00:10 0.00 27-JUN-15:00
HeatRejection:MainsWater 13739.15 0.00 01-JAN-00:10 0.00 27-JUN-15:00
General:HeatRejection:MainsWater 13739.15 0.00 01-JAN-00:10 0.00 27-JUN-15:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 79853.91 100989.79 02-JAN-02:50 9621376.08 28-AUG-12:30
EnergyTransfer:Building 21042.12 90822.57 02-JAN-02:50 1658359.84 14-AUG-15:20
EnergyTransfer:Zone:BASEMENT 706.57 0.00 01-JAN-00:10 76317.04 26-DEC-06:10
Heating:EnergyTransfer 39.49 0.00 01-JAN-17:10 270747.87 02-JAN-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.32 0.00 01-JAN-00:10 28415.63 26-AUG-16:10
General:Heating:EnergyTransfer 39.49 0.00 01-JAN-17:10 270747.87 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.32 0.00 01-JAN-00:10 28415.63 26-AUG-16:10
Cooling:EnergyTransfer 21002.64 90030.19 01-JAN-10:50 1658359.84 14-AUG-15:20
Cooling:EnergyTransfer:Zone:BASEMENT 702.24 0.00 01-JAN-00:10 76317.04 26-DEC-06:10
General:Cooling:EnergyTransfer 21002.64 90030.19 01-JAN-10:50 1658359.84 14-AUG-15:20
General:Cooling:EnergyTransfer:Zone:BASEMENT 702.24 0.00 01-JAN-00:10 76317.04 26-DEC-06:10
EnergyTransfer:Zone:CORE_BOTTOM 684.34 0.00 01-JAN-00:10 61415.50 14-AUG-07:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 684.34 0.00 01-JAN-00:10 61415.50 14-AUG-07:20
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 684.34 0.00 01-JAN-00:10 61415.50 14-AUG-07:20
EnergyTransfer:Zone:CORE_MID 5013.05 0.00 01-JAN-00:10 423544.92 11-SEP-10:00
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 5013.05 0.00 01-JAN-00:10 423544.92 11-SEP-10:00
General:Cooling:EnergyTransfer:Zone:CORE_MID 5013.05 0.00 01-JAN-00:10 423544.92 11-SEP-10:00
EnergyTransfer:Zone:CORE_TOP 488.03 0.00 01-JAN-00:10 50146.49 19-JUN-14:00
Heating:EnergyTransfer:Zone:CORE_TOP 0.36 0.00 01-JAN-00:10 41311.15 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 0.36 0.00 01-JAN-00:10 41311.15 02-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_TOP 487.67 0.00 01-JAN-00:10 50146.49 19-JUN-14:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 487.67 0.00 01-JAN-00:10 50146.49 19-JUN-14:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 97.40 0.00 01-JAN-00:10 11952.99 28-AUG-12:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 97.40 0.00 01-JAN-00:10 11952.99 28-AUG-12:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 97.40 0.00 01-JAN-00:10 11952.99 28-AUG-12:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 87.70 0.00 01-JAN-00:10 13681.41 19-JUN-08:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 375.21 07-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 375.21 07-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 87.70 0.00 01-JAN-00:10 13681.41 19-JUN-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 87.70 0.00 01-JAN-00:10 13681.41 19-JUN-08:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 145.16 0.00 01-JAN-00:10 17637.18 20-NOV-14:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 145.16 0.00 01-JAN-00:10 17637.18 20-NOV-14:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 145.16 0.00 01-JAN-00:10 17637.18 20-NOV-14:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 129.97 0.00 01-JAN-00:10 18787.82 25-AUG-17:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 129.97 0.00 01-JAN-00:10 18787.82 25-AUG-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 129.97 0.00 01-JAN-00:10 18787.82 25-AUG-17:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 774.44 0.00 01-JAN-00:10 113216.50 28-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 3.08 0.00 01-JAN-00:10 67437.55 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 3.08 0.00 01-JAN-00:10 67437.55 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 771.35 0.00 01-JAN-00:10 113216.50 28-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 771.35 0.00 01-JAN-00:10 113216.50 28-JUN-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 796.76 0.00 01-JAN-00:10 141324.92 19-JUN-08:50
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.13 0.00 01-JAN-00:10 40002.14 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.13 0.00 01-JAN-00:10 40002.14 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 795.64 0.00 01-JAN-00:10 141324.92 19-JUN-08:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 795.64 0.00 01-JAN-00:10 141324.92 19-JUN-08:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1302.92 0.00 01-JAN-00:10 177499.29 01-NOV-14:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.42 0.00 01-JAN-00:10 37210.79 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.42 0.00 01-JAN-00:10 37210.79 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1302.51 0.00 01-JAN-00:10 177499.29 01-NOV-14:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1302.51 0.00 01-JAN-00:10 177499.29 01-NOV-14:10
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 841.04 0.00 01-JAN-00:10 154359.85 29-JUN-17:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.55 0.00 01-JAN-00:10 26394.56 18-DEC-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.55 0.00 01-JAN-00:10 26394.56 18-DEC-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 840.49 0.00 01-JAN-00:10 154359.85 29-JUN-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 840.49 0.00 01-JAN-00:10 154359.85 29-JUN-17:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 81.66 0.00 01-JAN-00:10 13724.46 02-JAN-06:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.75 0.00 01-JAN-00:10 13724.46 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.75 0.00 01-JAN-00:10 13724.46 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 78.91 0.00 01-JAN-00:10 12774.84 28-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 78.91 0.00 01-JAN-00:10 12774.84 28-JUN-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 83.67 0.00 01-JAN-00:10 14378.59 19-JUN-09:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 1.10 0.00 01-JAN-00:10 8726.53 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 1.10 0.00 01-JAN-00:10 8726.53 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 82.56 0.00 01-JAN-00:10 14378.59 19-JUN-09:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 82.56 0.00 01-JAN-00:10 14378.59 19-JUN-09:10
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 129.72 0.00 01-JAN-00:10 19376.02 28-SEP-13:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.87 0.00 01-JAN-00:10 9335.58 02-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.87 0.00 01-JAN-00:10 9335.58 02-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 128.85 0.00 01-JAN-00:10 19376.02 28-SEP-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 128.85 0.00 01-JAN-00:10 19376.02 28-SEP-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 85.79 0.00 01-JAN-00:10 16388.97 29-JUN-17:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.66 0.00 01-JAN-00:10 6819.02 02-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.66 0.00 01-JAN-00:10 6819.02 02-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 85.13 0.00 01-JAN-00:10 16388.97 29-JUN-17:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 85.13 0.00 01-JAN-00:10 16388.97 29-JUN-17:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 94.20 0.00 01-JAN-00:10 15368.08 28-AUG-05:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.13 0.00 01-JAN-00:10 3320.37 17-DEC-10:40
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.13 0.00 01-JAN-00:10 3320.37 17-DEC-10:40
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 93.07 0.00 01-JAN-00:10 15368.08 28-AUG-05:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 93.07 0.00 01-JAN-00:10 15368.08 28-AUG-05:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 653.72 0.00 01-JAN-00:10 94533.42 19-JUN-14:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 13.24 0.00 01-JAN-00:10 43902.27 02-JAN-16:10
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 13.24 0.00 01-JAN-00:10 43902.27 02-JAN-16:10
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 640.48 0.00 01-JAN-00:10 94533.42 19-JUN-14:20
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 640.48 0.00 01-JAN-00:10 94533.42 19-JUN-14:20
EnergyTransfer:Zone:TOPFLOOR_PLENUM 121.34 0.00 01-JAN-00:10 24168.65 28-JUN-14:40
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 9.72 0.00 01-JAN-00:10 14438.91 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 9.72 0.00 01-JAN-00:10 14438.91 02-JAN-06:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 111.61 0.00 01-JAN-00:10 24168.65 28-JUN-14:40
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 111.61 0.00 01-JAN-00:10 24168.65 28-JUN-14:40
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.79 1197.88 21-JAN-08:00 7940.85 28-DEC-17:00
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.79 1197.88 21-JAN-08:00 7940.85 28-DEC-17:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 141.79 1197.88 21-JAN-08:00 7940.85 28-DEC-17:00
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1298.51 5.77 02-JAN-07:40 74715.14 28-DEC-17:00
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.07 0.00 01-JAN-00:10 2639.76 01-JAN-08:30
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.07 0.00 01-JAN-00:10 2639.76 01-JAN-08:30
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1298.44 0.00 01-JAN-02:00 74715.14 28-DEC-17:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1298.44 0.00 01-JAN-02:00 74715.14 28-DEC-17:00
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 125.42 6.04 16-JAN-10:10 7533.02 26-APR-18:30
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.07 0.00 01-JAN-16:40 578.26 01-JAN-21:20
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.07 0.00 01-JAN-16:40 578.26 01-JAN-21:20
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 125.35 0.00 01-JAN-00:10 7533.02 26-APR-18:30
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 125.35 0.00 01-JAN-00:10 7533.02 26-APR-18:30
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7158.94 88052.37 14-MAY-05:00 382885.91 26-AUG-03:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7158.94 88052.37 14-MAY-05:00 382885.91 26-AUG-03:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7158.94 88052.37 14-MAY-05:00 382885.91 26-AUG-03:00
PlantLoopHeatingDemand:Facility 384.79 0.00 01-JAN-00:10 380109.54 06-DEC-07:10
PlantLoopHeatingDemand:Plant 323.62 0.00 01-JAN-00:10 42572.21 23-JAN-12:50
WaterSystems:PlantLoopHeatingDemand 323.62 0.00 01-JAN-00:10 42572.21 23-JAN-12:50
General:WaterSystems:PlantLoopHeatingDemand 323.62 0.00 01-JAN-00:10 42572.21 23-JAN-12:50
EnergyTransfer:HVAC 18752.36 7426.03 01-JAN-07:50 2300694.08 11-AUG-15:50
HeatingCoils:EnergyTransfer 61.17 0.00 01-JAN-00:10 366728.48 06-DEC-07:10
PlantLoopHeatingDemand:HVAC 61.17 0.00 01-JAN-00:10 366728.48 06-DEC-07:10
HeatingCoils:PlantLoopHeatingDemand 61.17 0.00 01-JAN-00:10 366728.48 06-DEC-07:10
CoolingCoils:EnergyTransfer 18691.20 6182.24 02-JAN-07:10 2300694.08 11-AUG-15:50
EnergyTransfer:Plant 40059.43 0.00 01-JAN-00:10 6327401.87 05-SEP-07:50
LoopToLoop:EnergyTransfer 12719.21 0.00 01-JAN-00:10 2005453.98 05-SEP-07:40
WaterSystems:EnergyTransfer 323.62 0.00 01-JAN-00:10 42572.21 23-JAN-12:50
WaterUse:WaterSystems:EnergyTransfer 323.62 0.00 01-JAN-00:10 42572.21 23-JAN-12:50
Boilers:EnergyTransfer 60.58 0.00 01-JAN-00:10 442648.09 06-DEC-07:10
Chillers:EnergyTransfer 12562.30 0.00 01-JAN-00:10 2007022.51 05-SEP-07:50
HeatRejection:EnergyTransfer 14393.71 0.00 01-JAN-00:10 2296675.92 05-SEP-07:50
General:HeatRejection:EnergyTransfer 14393.71 0.00 01-JAN-00:10 2296675.92 05-SEP-07:50
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.324 -702.239 0.000 0.000 92.679 165.729 424.397 0.000 0.000 0.000 15.110 0.000 0.000 0.000 0.000 -0.013
CORE_BOTTOM 0.000 0.000 0.000 -684.338 0.000 0.000 83.399 148.837 289.614 0.000 0.000 0.000 162.488 0.000 0.000 0.000 0.000 -0.001
CORE_MID 0.000 0.000 0.000 -5013.039 0.000 0.000 835.630 1488.366 2896.128 0.000 0.000 0.000 0.029 0.000 0.000 0.000 0.000 -207.085
CORE_TOP 0.000 0.000 0.363 -487.665 0.000 0.000 84.394 148.837 289.613 0.000 0.000 0.000 0.004 0.000 0.000 0.000 0.000 -35.541
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -97.394 0.000 0.000 10.528 10.613 36.365 42.897 0.000 0.786 38.781 0.000 -40.555 0.000 -2.021 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -87.702 0.000 0.000 6.763 6.750 23.435 76.300 0.000 0.520 0.020 0.000 -24.730 0.000 -1.357 -0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.000 -145.157 0.000 0.000 10.475 10.441 36.366 125.392 0.000 0.772 2.827 0.000 -38.994 0.000 -2.121 -0.000
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -129.968 0.000 0.000 6.736 6.800 23.435 71.562 0.000 0.478 53.645 0.000 -31.106 0.000 -1.582 0.000
PERIMETER_MID_ZN_3 0.000 0.000 3.084 -771.345 0.000 0.000 107.717 105.880 363.654 445.253 0.000 18.166 135.721 0.000 -366.069 0.000 -42.061 0.000
PERIMETER_MID_ZN_2 0.000 0.000 1.128 -795.636 0.000 0.000 49.862 67.424 234.352 759.213 0.000 11.471 0.017 0.000 -236.947 0.000 -30.301 -60.567
PERIMETER_MID_ZN_1 0.000 0.000 0.418 -1302.485 0.000 0.000 105.071 104.304 363.660 1252.979 0.000 17.556 0.056 0.000 -378.609 0.000 -48.221 -114.672
PERIMETER_MID_ZN_4 0.000 0.000 0.553 -840.466 0.000 0.000 68.461 67.884 234.351 729.801 0.000 11.194 28.305 0.000 -268.396 0.000 -31.685 -0.005
PERIMETER_TOP_ZN_3 0.000 0.000 2.754 -78.905 0.000 0.000 10.927 10.587 36.365 44.665 0.000 2.186 10.540 0.000 -34.305 0.000 -4.814 -0.001
PERIMETER_TOP_ZN_2 0.000 0.000 1.104 -82.561 0.000 0.000 6.847 6.742 23.435 76.195 0.000 1.396 0.001 0.000 -22.408 0.000 -3.497 -7.255
PERIMETER_TOP_ZN_1 0.000 0.000 0.866 -128.848 0.000 0.000 10.604 10.430 36.366 125.295 0.000 2.112 0.001 0.000 -36.054 0.000 -5.639 -15.133
PERIMETER_TOP_ZN_4 0.000 0.000 0.661 -85.126 0.000 0.000 6.927 6.788 23.435 72.870 0.000 1.360 2.311 0.000 -25.520 0.000 -3.707 -0.001
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -141.791 0.000 0.000 0.933 3.626 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -16.649
DATACENTER_MID_ZN_6 0.000 0.000 0.068 -1298.444 0.000 0.000 9.363 36.263 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -286.056
DATACENTER_TOP_ZN_6 0.000 0.000 0.073 -125.346 0.000 0.000 0.939 3.626 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -33.172
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7158.945 0.000 0.000 19.181 47.611 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -402.705
GROUNDFLOOR_PLENUM 1.130 -93.068 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.475 94.941 0.000 0.000 0.000 -4.478 0.000
MIDFLOOR_PLENUM 13.237 -640.482 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 26.980 676.883 0.000 0.000 0.000 -76.618 -0.004
TOPFLOOR_PLENUM 9.725 -111.613 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.731 106.926 0.000 0.000 0.000 -7.769 -0.000
Total Facility 24.092 -845.163 15.396 -20157.401 0.000 0.000 1527.436 2457.540 14676.396 3822.423 0.000 99.184 1328.604 0.000 -1503.694 0.000 -265.870 -1178.860


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 03-JUL-04:11 0.00 0.00 0.00 -105302.62 0.00 0.00 0.00 598.35 13457.54 0.00 0.00 0.00 91246.72 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 30-MAY-04:13 0.00 0.00 0.00 -90682.66 0.00 0.00 0.00 537.36 5937.65 0.00 0.00 0.00 84207.65 0.00 -0.00 0.00 0.00 0.00
CORE_MID 01-JUN-04:13 0.00 0.00 0.00 -830102.69 0.00 0.00 0.00 5373.60 59376.23 0.00 0.00 0.00 765352.86 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 19-JUN-04:13 0.00 0.00 0.00 -85326.48 0.00 0.00 0.00 537.36 5937.62 0.00 0.00 0.00 78851.49 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 25-JUN-18:31 0.00 0.00 0.00 -19291.16 0.00 0.00 0.00 43.94 559.17 7247.82 0.00 369.15 11071.07 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 29-MAY-09:31 0.00 0.00 0.00 -20301.51 0.00 0.00 20.90 28.32 464.11 12846.15 0.00 0.00 6967.41 0.00 -0.00 0.00 -25.38 0.00
PERIMETER_BOT_ZN_1 15-OCT-13:21 0.00 0.00 0.00 -23503.13 0.00 0.00 32.18 43.94 720.19 19825.58 0.00 38.19 2843.04 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 23-APR-16:21 0.00 0.00 0.00 -28896.54 0.00 0.00 14.00 28.32 464.11 15505.62 0.00 63.19 12821.30 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 25-JUN-18:01 0.00 0.00 0.00 -193600.53 0.00 0.00 0.00 439.44 5591.71 78543.10 0.00 9643.08 99383.20 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 13-AUG-08:51 0.00 0.00 0.00 -223990.27 0.00 0.00 194.62 283.19 4641.14 145928.08 0.00 580.72 72362.51 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 09-OCT-12:31 0.00 0.00 0.00 -236069.17 0.00 0.00 316.55 439.45 7201.95 204967.46 0.00 443.54 22700.22 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 13-AUG-16:51 0.00 0.00 0.00 -262510.99 0.00 0.00 146.84 283.19 4641.11 155324.49 0.00 5442.74 96672.61 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 16-JUL-17:31 0.00 0.00 0.00 -22919.98 0.00 0.00 0.00 43.94 559.17 6083.12 0.00 1215.86 15017.89 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 18-JUN-08:11 0.00 0.00 0.00 -23108.92 0.00 0.00 18.58 28.32 464.11 15199.23 0.00 91.60 7307.06 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 09-OCT-13:41 0.00 0.00 0.00 -26566.30 0.00 0.00 30.74 43.94 720.19 18620.19 0.00 53.71 7097.51 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 30-JUL-17:31 0.00 0.00 0.00 -28833.69 0.00 0.00 0.00 28.32 360.35 15158.20 0.00 630.01 12656.81 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 28-DEC-17:00 0.00 0.00 0.00 -7940.84 0.00 0.00 100.85 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -271.07
DATACENTER_MID_ZN_6 28-DEC-17:00 0.00 0.00 0.00 -74714.95 0.00 0.00 1008.50 3166.31 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -7404.08
DATACENTER_TOP_ZN_6 26-APR-18:30 0.00 0.00 0.00 -7532.90 0.00 0.00 10.41 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -377.48
DATACENTER_BASEMENT_ZN_6 23-AUG-22:53 0.00 0.00 0.00 -386587.40 0.00 0.00 105.71 230.94 379632.52 0.00 0.00 0.00 6618.22 0.00 -0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 28-AUG-05:13 0.00 -17219.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.37 17196.36 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 28-AUG-05:13 0.00 -128128.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 508.34 127619.70 0.00 -0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 28-JUN-14:40 0.00 -24169.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 616.99 23552.44 0.00 -0.00 0.00 0.00 0.00
Total Facility 28-AUG-05:01 0.00 -73520.89 0.00 -2053805.41 0.00 0.00 15311.66 10593.62 616289.16 8250.51 0.00 2068.18 1475000.31 0.00 -187.13 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 26-AUG-16:01 0.00 0.00 30163.03 0.00 0.00 0.00 520.13 819.05 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -44959.75
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 02-JAN-05:11 0.00 0.00 67034.54 0.00 0.00 0.00 0.00 537.36 5937.62 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -73509.52
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 07-DEC-06:01 0.00 0.00 2626.48 0.00 0.00 0.00 91.56 43.48 618.82 0.00 0.00 0.00 627.67 0.00 -3931.58 0.00 -76.42 0.00
PERIMETER_BOT_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 02-JAN-05:11 0.00 0.00 138380.12 0.00 0.00 0.00 0.00 674.71 7455.61 0.00 0.00 0.00 0.00 0.00 -39298.04 0.00 -2771.59 -104440.81
PERIMETER_MID_ZN_2 02-JAN-05:11 0.00 0.00 117169.74 0.00 0.00 0.00 0.00 434.81 4804.68 0.00 0.00 0.00 0.00 0.00 -27351.66 0.00 -1926.06 -93131.51
PERIMETER_MID_ZN_1 07-DEC-06:01 0.00 0.00 138785.07 0.00 0.00 0.00 1460.99 674.72 9602.60 0.00 0.00 0.00 0.00 0.00 -57694.65 0.00 -2656.90 -90171.83
PERIMETER_MID_ZN_4 07-DEC-06:01 0.00 0.00 100676.15 0.00 0.00 0.00 941.50 434.81 6188.15 0.00 0.00 0.00 0.00 0.00 -37200.77 0.00 -1775.69 -69264.15
PERIMETER_TOP_ZN_3 02-JAN-05:11 0.00 0.00 17622.22 0.00 0.00 0.00 0.00 67.47 745.56 0.00 0.00 0.00 0.00 0.00 -3281.38 0.00 -292.47 -14861.40
PERIMETER_TOP_ZN_2 02-JAN-05:11 0.00 0.00 15757.07 0.00 0.00 0.00 0.00 43.48 480.47 0.00 0.00 0.00 0.00 0.00 -2250.55 0.00 -198.76 -13831.71
PERIMETER_TOP_ZN_1 02-JAN-05:11 0.00 0.00 17983.75 0.00 0.00 0.00 0.00 67.47 745.57 0.00 0.00 0.00 0.00 0.00 -3812.30 0.00 -331.24 -14653.25
PERIMETER_TOP_ZN_4 02-JAN-05:11 0.00 0.00 15224.50 0.00 0.00 0.00 0.00 43.48 480.46 0.00 0.00 0.00 0.00 0.00 -2453.24 0.00 -218.60 -13076.61
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 01-JAN-08:30 0.00 0.00 2639.77 0.00 0.00 0.00 53.08 175.92 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -22354.82
DATACENTER_TOP_ZN_6 01-JAN-02:65 0.00 0.00 583.89 0.00 0.00 0.00 0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2550.09
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 23-APR-15:41 10752.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 454.53 0.00 0.00 -0.00 0.00 0.00 -11207.38
MIDFLOOR_PLENUM 30-JUL-16:11 93265.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13302.38 0.00 0.00 -0.00 0.00 0.00 -106568.13
TOPFLOOR_PLENUM 02-JAN-06:03 17586.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -159.48 -17426.59
Total Facility 07-DEC-06:01 -797238.98 742645.46 572172.90 -742645.46 0.00 0.00 18892.42 10593.62 616289.16 0.00 0.00 0.00 0.00 0.00 -224649.00 0.00 -15464.92 -180595.19



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 11.2250 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.0310 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 107.6407 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 94.4525 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 11.2329 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.7826 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.6803 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.6803 0.2113 1.0000 Not calculated 1.2002 0.2113    
AIRLOOP DATACENTER BASEMENT 23.4119 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 23.4121 0.0145 1.0000 Not calculated 0.3384 0.0145    
AIRLOOP DATACENTER BOT 0.5103 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5103 0.0306 1.0000 Not calculated 0.0156 0.0306    
AIRLOOP DATACENTER MID 4.8715 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.8715 0.0321 1.0000 Not calculated 0.1563 0.0321    
AIRLOOP DATACENTER TOP 0.4985 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4985 0.0314 1.0000 Not calculated 0.0156 0.0314    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.6125 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2863 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 53.8203 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 22.8619 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.6164 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.2830 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.6803 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.6803 1.0000 1.0000 Not calculated 1.2002 0.2113    
AIRLOOP DATACENTER BASEMENT 23.4119 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 23.4119 1.0000 1.0000 Not calculated 0.3384 0.0145    
AIRLOOP DATACENTER BOT 0.5103 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5103 1.0000 1.0000 Not calculated 0.0156 0.0306    
AIRLOOP DATACENTER MID 4.8715 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.8715 1.0000 1.0000 Not calculated 0.1563 0.0321    
AIRLOOP DATACENTER TOP 0.4985 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4985 1.0000 1.0000 Not calculated 0.0156 0.0314    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.6803 5.6803 5.6803 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.0612 6.0612 1.6183 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 57.1759 57.1759 16.1808 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.7052 5.7052 1.6146 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1751 1.1751 0.2033 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1662 1.1662 0.1306 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3206 1.3206 0.2034 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.5019 1.5019 0.1307 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.6109 11.6109 2.0319 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.3698 12.3698 1.3112 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 13.0356 13.0356 2.0336 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 13.4485 13.4485 1.3045 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3329 1.3329 0.2026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2724 1.2724 0.1311 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4642 1.4642 0.2035 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4582 1.4582 0.1312 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5103 0.5103 0.5103 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.8715 4.8715 4.8715 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4985 0.4985 0.4985 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 23.4119 23.4119 23.4119 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 11.2250 10.0310 11.2250 2.2863 0.0000 1.0000
VAV_MID WITH REHEAT 107.6407 94.4525 107.6407 22.8619 0.0000 1.0000
VAV_TOP WITH REHEAT 11.2329 10.7826 11.2329 2.2830 0.0000 1.0000
CAV_BAS 5.6803 5.6803 5.6803 5.6803 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 23.4119 23.4121 23.4119 23.4119 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5103 0.5103 0.5103 0.5103 0.0156 1.0000
AIRLOOP DATACENTER MID 4.8715 4.8715 4.8715 4.8715 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4985 0.4985 0.4985 0.4985 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.6803 5.6803 5.6803 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 3.0306 3.0306 1.6183 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 28.5879 28.5879 16.1808 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8526 2.8526 1.6146 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5876 0.5876 0.2033 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5831 0.5831 0.1306 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6603 0.6603 0.2034 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7510 0.7510 0.1307 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.8055 5.8055 2.0319 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.1849 6.1849 1.3112 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.5178 6.5178 2.0336 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.7242 6.7242 1.3045 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6664 0.6664 0.2026 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6362 0.6362 0.1311 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7321 0.7321 0.2035 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7291 0.7291 0.1312 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5103 0.5103 0.5103 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.8715 4.8715 4.8715 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4985 0.4985 0.4985 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 23.4119 23.4119 23.4119 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.6125 2.2863 2.2863 2.2863 0.0000 1.0000
VAV_MID WITH REHEAT 53.8203 22.8619 22.8619 22.8619 0.0000 1.0000
VAV_TOP WITH REHEAT 5.6164 2.2830 2.2830 2.2830 0.0000 1.0000
CAV_BAS 5.6803 5.6803 5.6803 5.6803 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 23.4119 23.4119 23.4119 23.4119 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5103 0.5103 0.5103 0.5103 0.0156 1.0000
AIRLOOP DATACENTER MID 4.8715 4.8715 4.8715 4.8715 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4985 0.4985 0.4985 0.4985 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.17
Number of hours cooling loads not met 1140.17
Number of hours not met 1140.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 86.74 531907.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 3858.36 446424.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 2457.54 247210.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 350.70 40855.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5334.97 305206.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 54.68 3412.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2725.16 268224.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 564.44 47736.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1158.60 77358.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 1609.69 100000.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 647.04 76823.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 14676.40 29310.18
Natural Gas 0.00 733.78
Additional 0.00 0.00
Total 14676.40 30043.96


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 53.06
Space Heating 0.00
Space Cooling 83.30
Fans (All) 58.83
Service Water Heating 0.00
Receptacle Equipment 316.85
Miscellaneous (All) 632.77
Subtotal 632.77


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 1.87
Service Water Heating 13.97
Miscellaneous (All) 15.84
Subtotal 15.84


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 8.18
Space Heating 0.29
Space Cooling 12.84
Fans (All) 9.07
Service Water Heating 2.15
Receptacle Equipment 48.85
Miscellaneous 18.62


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2625. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4049. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 829. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365
HTGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL January 20.44 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM_W_SB PERIMETER_MID_ZN_2 DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8410.83 349.17 0.00 0.00 0.00
CORE_BOTTOM 8733.50 26.50 0.00 0.00 0.00
CORE_MID 8758.17 1.83 0.00 0.00 0.00
CORE_TOP 8742.33 17.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8698.50 61.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8650.33 109.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8639.33 120.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8252.50 507.50 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8697.67 62.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8566.33 193.67 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8589.67 170.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8434.83 325.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8655.00 105.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8540.67 219.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8566.00 194.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8435.17 324.83 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7508.83 1251.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7605.17 1154.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7663.83 1096.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 6631.17 2044.67 84.17 0.00 0.00
GROUNDFLOOR_PLENUM 8745.33 14.67 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8521.17 238.83 0.00 0.00 0.00
Min 6631.17 0.00 0.00 0.00 0.00
Max 8760.00 2044.67 84.17 0.00 0.00
Average 8382.88 373.46 3.66 0.00 0.00
Sum 192806.33 8589.50 84.17 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 367527.50 1088.50 0.00 0.00 0.00
CORE_BOTTOM 330773.00 40.00 0.00 0.00 0.00
CORE_MID 330802.00 11.00 0.00 0.00 0.00
CORE_TOP 330791.00 22.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1696.50 571.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1704.50 563.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1724.33 543.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 74186.00 27768.33 1440.67 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367527.50 27768.33 1440.67 0.00 0.00
Average 78941.47 1330.80 62.64 0.00 0.00
Sum 1815653.83 30608.50 1440.67 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8046.33 713.67 0.00 0.00 0.00
CORE_BOTTOM 8383.17 376.83 0.00 0.00 0.00
CORE_MID 8439.17 320.83 0.00 0.00 0.00
CORE_TOP 8416.67 343.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8298.17 461.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8340.67 419.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8261.17 498.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8066.33 693.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8260.50 499.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8194.00 566.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8212.83 547.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8141.50 618.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8253.50 506.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8201.00 559.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8213.83 546.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8160.17 599.83 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8191.50 568.50 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8233.33 526.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8267.00 493.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7162.33 1593.33 4.33 0.00 0.00
GROUNDFLOOR_PLENUM 8192.00 568.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8201.67 558.33 0.00 0.00 0.00
TOPFLOOR_PLENUM 7789.17 970.83 0.00 0.00 0.00
Min 7162.33 320.83 0.00 0.00 0.00
Max 8439.17 1593.33 4.33 0.00 0.00
Average 8170.70 589.12 0.19 0.00 0.00
Sum 187926.00 13549.67 4.33 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 365838.50 2777.50 0.00 0.00 0.00
CORE_BOTTOM 329979.00 834.00 0.00 0.00 0.00
CORE_MID 330269.00 544.00 0.00 0.00 0.00
CORE_TOP 330180.00 633.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38924.67 0.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24908.83 0.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38924.67 0.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24898.17 10.83 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1927.67 340.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1928.50 339.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1949.00 319.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 82912.50 20373.83 108.67 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 365838.50 20373.83 108.67 0.00 0.00
Average 79192.24 1137.95 4.72 0.00 0.00
Sum 1821421.50 26172.83 108.67 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:51:38

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.549391E+11 102750.74 02-JAN-05:11 4.00 1.01 0.566889E+10 7499.23 23-JAN-14:20 21.67 11.33
February 0.456864E+11 101989.06 21-FEB-05:12 9.33 8.41 0.513842E+10 7499.28 15-FEB-14:00 9.33 8.41
March 0.536142E+11 103219.98 20-MAR-04:12 11.83 7.65 0.613197E+10 7499.22 10-MAR-14:20 11.83 7.65
April 0.543241E+11 102337.13 24-APR-04:21 16.00 5.06 0.545135E+10 7499.22 06-APR-09:20 16.00 5.06
May 0.547333E+11 103380.18 08-MAY-04:11 22.00 10.09 0.590117E+10 7499.17 11-MAY-09:20 26.33 13.51
June 0.562778E+11 103419.32 19-JUN-04:12 22.67 10.74 0.588198E+10 7499.27 29-JUN-09:20 33.33 18.14
July 0.612846E+11 105301.79 03-JUL-04:11 20.67 7.71 0.547549E+10 7499.38 21-JUL-09:20 31.33 20.88
August 0.709876E+11 103144.26 27-AUG-16:16 40.00 18.14 0.613922E+10 7499.16 15-AUG-09:20 40.00 18.14
September 0.634091E+11 100241.87 28-SEP-04:12 21.83 12.80 0.545575E+10 7499.23 22-SEP-09:20 21.83 12.80
October 0.650312E+11 103627.22 23-OCT-04:12 11.00 9.66 0.567345E+10 7505.68 10-OCT-09:09 11.00 9.66
November 0.621103E+11 102362.40 06-NOV-05:12 7.67 2.51 0.561711E+10 7499.39 16-NOV-14:20 18.00 11.91
December 0.598438E+11 102973.40 11-DEC-05:11 8.33 1.55 0.547379E+10 7499.11 21-DEC-14:20 25.33 10.67
                     
Annual Sum or Average 0.702241E+12         0.680086E+11        
Minimum of Months 0.456864E+11 100241.87   4.00 1.01 0.513842E+10 7499.11   9.33 5.06
Maximum of Months 0.709876E+11 105301.79   40.00 18.14 0.613922E+10 7505.68   40.00 20.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.455183E+11 86351.38 17-JAN-05:12 11.33 3.83 0.507725E+10 6734.80 23-JAN-14:20 21.67 11.33
February 0.404734E+11 86575.69 21-FEB-05:12 9.33 8.41 0.460659E+10 6735.04 15-FEB-14:00 9.33 8.41
March 0.527648E+11 87676.09 20-MAR-04:12 11.83 7.65 0.550035E+10 6734.87 17-MAR-09:00 11.83 7.65
April 0.644930E+11 84404.17 28-APR-04:13 14.33 7.25 0.487965E+10 6734.83 10-APR-09:09 14.33 7.25
May 0.567469E+11 90694.21 30-MAY-04:13 18.00 9.08 0.528632E+10 6734.80 30-MAY-09:20 27.33 13.67
June 0.644396E+11 88323.36 01-JUN-04:13 22.33 12.88 0.526646E+10 6734.81 29-JUN-09:20 33.33 18.14
July 0.670763E+11 80507.23 29-JUL-04:12 21.00 17.45 0.489536E+10 6734.85 05-JUL-09:09 21.00 17.45
August 0.766746E+11 83930.17 21-AUG-05:05 24.67 16.53 0.549892E+10 6772.71 28-AUG-09:09 31.50 20.35
September 0.569656E+11 88309.23 29-SEP-04:13 20.53 11.28 0.488323E+10 6734.80 15-SEP-09:20 20.53 11.28
October 0.559739E+11 90651.56 10-OCT-04:13 18.00 12.03 0.508038E+10 6734.81 10-OCT-09:09 26.50 15.73
November 0.522973E+11 88358.68 06-NOV-05:12 7.67 2.51 0.503116E+10 6734.99 22-NOV-10:00 20.00 11.57
December 0.509148E+11 89460.58 04-DEC-05:12 3.00 0.78 0.490371E+10 6734.75 19-DEC-10:20 13.00 5.14
                     
Annual Sum or Average 0.684339E+12         0.609094E+11        
Minimum of Months 0.404734E+11 80507.23   3.00 0.78 0.460659E+10 6734.75   9.33 5.14
Maximum of Months 0.766746E+11 90694.21   24.67 17.45 0.550035E+10 6772.71   33.33 20.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.333953E+11 74714.05 27-JAN-06:02 12.83 5.24 0.504106E+10 6734.78 11-JAN-10:20 12.83 5.24
February 0.286476E+11 74311.25 01-FEB-06:02 5.00 3.59 0.458142E+10 6734.88 15-FEB-14:00 20.00 13.98
March 0.371318E+11 75592.85 20-MAR-04:12 11.83 7.65 0.548620E+10 6734.83 17-MAR-09:00 11.83 7.65
April 0.435141E+11 77300.54 18-APR-04:12 16.67 9.88 0.487550E+10 6734.82 03-APR-09:30 16.67 9.88
May 0.483417E+11 77558.79 31-MAY-04:12 19.00 9.54 0.528291E+10 6734.80 30-MAY-09:20 19.00 9.54
June 0.527512E+11 82977.06 01-JUN-04:13 22.33 12.88 0.526337E+10 6734.81 29-JUN-09:20 33.33 18.14
July 0.506143E+11 82680.20 03-JUL-04:13 20.67 7.71 0.489160E+10 6734.86 21-JUL-09:20 31.33 20.88
August 0.527044E+11 76487.84 05-AUG-04:12 21.67 17.87 0.549348E+10 6734.89 28-AUG-09:20 32.00 20.57
September 0.465086E+11 78389.02 26-SEP-04:12 20.00 15.92 0.488129E+10 6734.79 15-SEP-09:20 20.00 15.92
October 0.420643E+11 78264.18 11-OCT-04:12 18.00 10.82 0.507124E+10 6734.85 03-OCT-13:39 18.00 10.82
November 0.350364E+11 78525.92 13-NOV-05:12 17.00 17.00 0.501427E+10 6734.93 16-NOV-14:09 18.00 11.84
December 0.305951E+11 73507.84 28-DEC-06:02 8.67 3.60 0.486313E+10 6734.78 13-DEC-10:20 8.67 3.60
                     
Annual Sum or Average 0.501305E+12         0.607455E+11        
Minimum of Months 0.286476E+11 73507.84   5.00 3.59 0.458142E+10 6734.78   8.67 3.60
Maximum of Months 0.527512E+11 82977.06   22.33 17.87 0.549348E+10 6734.93   33.33 20.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.259273E+11 35728.87 27-JAN-17:00 26.00 9.22 0.488506E+10 6734.73 09-JAN-10:20 26.00 9.22
February 0.218771E+11 33878.84 23-FEB-15:00 18.00 10.35 0.442421E+10 6734.78 15-FEB-14:00 18.00 10.35
March 0.307444E+11 72024.86 17-MAR-05:03 13.48 9.60 0.539168E+10 6734.80 17-MAR-09:00 21.60 14.25
April 0.439130E+11 76307.29 26-APR-04:12 20.00 10.45 0.486766E+10 6734.81 03-APR-09:20 20.00 10.45
May 0.512461E+11 84595.62 08-MAY-04:13 22.00 10.09 0.528393E+10 6734.79 30-MAY-09:20 27.33 13.67
June 0.600559E+11 85336.75 19-JUN-04:13 22.67 10.74 0.526760E+10 6734.81 29-JUN-09:20 33.33 18.14
July 0.578334E+11 84818.26 03-JUL-04:13 20.67 7.71 0.489735E+10 6734.85 05-JUL-09:09 31.33 16.71
August 0.585246E+11 78759.68 21-AUG-05:03 24.67 16.53 0.549646E+10 6734.89 28-AUG-09:20 32.00 20.57
September 0.497982E+11 80378.48 05-SEP-04:13 22.53 18.57 0.488372E+10 6734.78 15-SEP-09:20 25.90 16.61
October 0.381850E+11 77012.85 05-OCT-04:12 19.67 13.65 0.503559E+10 6734.80 10-OCT-09:09 26.50 15.73
November 0.279500E+11 72255.06 03-NOV-05:03 16.00 12.46 0.490124E+10 6734.86 16-NOV-14:09 18.00 11.84
December 0.216135E+11 33733.37 22-DEC-16:50 24.17 9.62 0.457986E+10 6734.71 12-DEC-14:30 24.17 9.62
                     
Annual Sum or Average 0.487668E+12         0.599144E+11        
Minimum of Months 0.216135E+11 33733.37   13.48 7.71 0.442421E+10 6734.71   18.00 9.22
Maximum of Months 0.600559E+11 85336.75   26.00 18.57 0.549646E+10 6734.89   33.33 20.57



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.379996E+10 5236.82 31-JAN-16:30 29.00 10.73 0.623619E+09 845.63 23-JAN-14:20 29.00 10.73
February 0.322725E+10 5211.48 22-FEB-14:00 21.00 12.01 0.565471E+09 845.66 15-FEB-14:00 21.00 12.01
March 0.519902E+10 7397.15 20-MAR-14:00 27.70 14.42 0.682129E+09 845.64 17-MAR-09:00 27.70 14.42
April 0.922886E+10 18073.25 30-APR-16:21 32.50 11.88 0.612590E+09 845.63 27-APR-13:39 32.50 11.88
May 0.988732E+10 18146.72 29-MAY-18:11 30.67 13.66 0.664572E+09 845.63 30-MAY-09:20 27.33 13.67
June 0.138105E+11 19291.97 25-JUN-18:31 36.67 14.58 0.663109E+09 845.74 19-JUN-13:00 36.67 14.58
July 0.132670E+11 18952.81 04-JUL-18:11 36.00 14.97 0.616672E+09 845.66 17-JUL-13:50 36.67 20.83
August 0.138988E+11 18500.01 13-AUG-16:21 38.00 20.26 0.691596E+09 851.55 28-AUG-09:09 31.50 20.35
September 0.989074E+10 18053.44 10-SEP-16:42 34.00 19.47 0.614086E+09 845.63 15-SEP-09:20 25.90 16.61
October 0.676857E+10 14031.51 02-OCT-04:23 26.00 17.05 0.634419E+09 845.66 03-OCT-13:39 33.00 20.21
November 0.474807E+10 9271.52 13-NOV-06:03 16.83 16.83 0.624586E+09 845.65 16-NOV-14:09 18.00 11.84
December 0.366903E+10 5465.25 26-DEC-15:30 23.00 10.56 0.598727E+09 845.62 19-DEC-10:20 23.00 10.56
                     
Annual Sum or Average 0.973951E+11         0.759158E+10        
Minimum of Months 0.322725E+10 5211.48   16.83 10.56 0.565471E+09 845.62   18.00 10.56
Maximum of Months 0.138988E+11 19291.97   38.00 20.26 0.691596E+09 851.55   36.67 20.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.391059E+10 7730.19 17-JAN-09:30 16.50 6.15 0.407017E+09 544.96 23-JAN-14:09 21.83 11.36
February 0.315368E+10 10671.26 20-FEB-09:03 12.33 11.58 0.367868E+09 544.97 15-FEB-14:00 12.33 11.58
March 0.483583E+10 17217.37 19-MAR-09:32 21.80 12.11 0.441935E+09 544.97 14-MAR-09:00 21.80 12.11
April 0.873138E+10 19626.92 23-APR-08:22 23.50 8.72 0.395365E+09 545.91 24-APR-09:50 26.83 10.74
May 0.996235E+10 20301.77 29-MAY-09:31 27.33 12.10 0.428959E+09 545.77 11-MAY-09:00 27.33 12.10
June 0.122030E+11 20170.01 25-JUN-07:51 28.00 13.23 0.427661E+09 545.64 09-JUN-09:00 28.00 13.23
July 0.111006E+11 19067.67 04-JUL-08:51 30.00 12.88 0.397694E+09 545.58 13-JUL-09:50 31.83 20.83
August 0.112496E+11 19027.73 13-AUG-09:02 32.17 20.93 0.445826E+09 550.93 28-AUG-09:09 31.50 20.35
September 0.861408E+10 19940.70 10-SEP-09:21 30.20 19.40 0.396012E+09 546.33 08-SEP-09:00 30.20 19.40
October 0.658691E+10 18792.06 15-OCT-08:42 23.33 9.51 0.410196E+09 545.45 05-OCT-09:09 23.33 9.51
November 0.421198E+10 9026.42 19-NOV-09:33 21.33 10.18 0.404243E+09 544.98 22-NOV-10:50 20.00 11.34
December 0.314236E+10 6784.77 26-DEC-09:40 16.33 7.28 0.390540E+09 544.95 13-DEC-10:09 16.33 7.28
                     
Annual Sum or Average 0.877023E+11         0.491332E+10        
Minimum of Months 0.314236E+10 6784.77   12.33 6.15 0.367868E+09 544.95   12.33 7.28
Maximum of Months 0.122030E+11 20301.77   32.17 20.93 0.445826E+09 550.93   31.83 20.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.124594E+11 22628.36 22-JAN-13:32 18.67 11.29 0.637316E+09 904.01 17-JAN-14:20 18.67 11.29
February 0.738373E+10 17043.02 26-FEB-11:13 14.67 9.92 0.571380E+09 847.69 28-FEB-14:09 18.17 7.92
March 0.880800E+10 15819.24 26-MAR-14:53 17.20 5.56 0.683943E+09 847.31 17-MAR-13:09 17.20 5.56
April 0.125804E+11 21341.38 23-APR-15:41 33.25 12.77 0.613299E+09 847.04 25-APR-13:30 31.00 14.65
May 0.107429E+11 20488.08 07-MAY-16:21 36.00 14.22 0.664709E+09 845.65 30-MAY-09:20 27.33 13.67
June 0.132874E+11 21118.35 04-JUN-15:51 38.00 16.06 0.662931E+09 845.66 19-JUN-13:09 38.17 18.27
July 0.134797E+11 20976.40 04-JUL-16:51 37.00 15.96 0.616693E+09 846.05 31-JUL-13:00 37.00 19.00
August 0.158860E+11 21055.45 27-AUG-13:41 39.67 18.22 0.691876E+09 851.84 28-AUG-09:09 31.50 20.35
September 0.137726E+11 22735.38 10-SEP-12:41 34.22 18.96 0.615333E+09 901.20 28-SEP-13:39 36.47 16.05
October 0.137053E+11 23503.15 15-OCT-13:21 30.50 12.34 0.640852E+09 903.94 31-OCT-13:50 26.50 11.92
November 0.119732E+11 22547.24 26-NOV-12:42 18.00 8.27 0.634199E+09 913.83 20-NOV-14:20 18.00 8.27
December 0.110807E+11 22616.59 10-DEC-14:02 21.00 8.00 0.612658E+09 894.90 27-DEC-14:09 19.17 9.79
                     
Annual Sum or Average 0.145159E+12         0.764519E+10        
Minimum of Months 0.738373E+10 15819.24   14.67 5.56 0.571380E+09 845.65   17.20 5.56
Maximum of Months 0.158860E+11 23503.15   39.67 18.96 0.691876E+09 913.83   38.17 20.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.564841E+10 24377.94 29-JAN-16:22 24.50 9.40 0.409641E+09 544.98 30-JAN-14:00 25.00 9.66
February 0.485623E+10 18040.19 20-FEB-16:22 17.50 9.63 0.372305E+09 545.00 15-FEB-14:00 17.50 9.63
March 0.827379E+10 23157.96 26-MAR-16:12 18.30 6.21 0.445669E+09 544.97 09-MAR-14:00 18.30 6.21
April 0.151014E+11 28896.48 23-APR-16:21 33.15 12.72 0.396888E+09 544.97 27-APR-13:39 25.33 11.96
May 0.118607E+11 27513.08 28-MAY-17:01 32.83 12.78 0.429389E+09 544.96 12-MAY-09:09 32.83 12.78
June 0.156842E+11 28754.76 25-JUN-17:11 38.00 15.21 0.428130E+09 544.96 19-JUN-13:09 38.00 15.21
July 0.150310E+11 28193.33 04-JUL-16:51 37.00 15.96 0.398465E+09 544.97 05-JUL-09:09 31.33 16.71
August 0.188149E+11 27085.93 13-AUG-16:21 38.00 20.26 0.446904E+09 550.57 28-AUG-09:09 31.50 20.35
September 0.104356E+11 24248.60 04-SEP-15:42 31.60 21.45 0.396628E+09 544.96 15-SEP-09:09 25.45 16.44
October 0.920321E+10 24844.17 15-OCT-14:01 31.00 12.59 0.412149E+09 544.99 03-OCT-13:39 31.00 12.59
November 0.795557E+10 23052.91 26-NOV-14:42 18.97 9.07 0.407745E+09 544.99 27-NOV-14:39 24.97 9.27
December 0.710469E+10 24160.14 25-DEC-16:12 25.33 11.74 0.397184E+09 544.95 13-DEC-10:09 25.33 11.74
                     
Annual Sum or Average 0.129970E+12         0.494110E+10        
Minimum of Months 0.485623E+10 18040.19   17.50 6.21 0.372305E+09 544.95   17.50 6.21
Maximum of Months 0.188149E+11 28896.48   38.00 21.45 0.446904E+09 550.57   38.00 20.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.263335E+10 3953.37 31-JAN-16:30 29.00 10.73 0.577529E+09 845.62 23-JAN-14:20 29.00 10.73
February 0.208253E+10 3210.13 22-FEB-14:10 21.00 11.95 0.521805E+09 845.62 15-FEB-14:00 21.00 11.95
March 0.331970E+10 5661.58 16-MAR-16:00 28.80 13.95 0.650834E+09 845.63 17-MAR-09:00 21.60 14.25
April 0.638414E+10 17456.02 30-APR-16:31 32.33 11.86 0.608773E+09 845.63 27-APR-13:30 32.33 11.86
May 0.890570E+10 18044.12 07-MAY-17:01 35.83 14.32 0.664199E+09 845.63 30-MAY-09:20 27.33 13.67
June 0.127888E+11 19361.15 25-JUN-18:01 37.67 14.86 0.663229E+09 845.64 19-JUN-13:09 37.67 14.86
July 0.114924E+11 18950.27 30-JUL-18:11 37.33 18.54 0.616834E+09 845.65 21-JUL-09:20 37.33 18.54
August 0.108173E+11 19202.53 13-AUG-16:11 38.00 20.37 0.691289E+09 845.64 28-AUG-09:39 33.00 21.02
September 0.866268E+10 18029.02 10-SEP-16:42 34.00 19.47 0.613895E+09 845.63 08-SEP-09:20 34.00 19.47
October 0.504322E+10 17753.53 01-OCT-13:32 37.00 19.01 0.619824E+09 845.67 03-OCT-13:39 33.00 20.21
November 0.291462E+10 5624.07 02-NOV-14:00 27.00 15.44 0.592548E+09 845.63 16-NOV-14:09 18.00 11.84
December 0.209077E+10 2770.66 22-DEC-16:10 24.83 10.00 0.526879E+09 845.49 22-DEC-14:00 24.83 10.00
                     
Annual Sum or Average 0.771352E+11         0.734764E+10        
Minimum of Months 0.208253E+10 2770.66   21.00 10.00 0.521805E+09 845.49   18.00 10.00
Maximum of Months 0.127888E+11 19361.15   38.00 20.37 0.691289E+09 845.67   37.67 21.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.278562E+10 7073.99 27-JAN-11:05 22.33 7.96 0.294073E+09 548.50 26-JAN-13:09 22.33 7.96
February 0.217624E+10 7228.57 23-FEB-11:05 15.83 10.67 0.265483E+09 548.50 21-FEB-13:09 15.83 10.67
March 0.373654E+10 13982.39 19-MAR-09:23 21.35 11.96 0.320689E+09 548.51 16-MAR-10:09 21.35 11.96
April 0.796331E+10 21496.07 30-APR-09:51 28.00 10.47 0.292227E+09 548.51 28-APR-10:09 28.00 10.47
May 0.990685E+10 21787.53 07-MAY-09:01 27.17 11.80 0.317026E+09 548.52 22-MAY-10:09 25.33 9.96
June 0.124050E+11 22394.03 25-JUN-08:41 30.50 14.32 0.315884E+09 548.51 29-JUN-10:09 34.33 18.62
July 0.109717E+11 21714.92 30-JUL-08:11 27.00 19.19 0.294875E+09 548.51 03-JUL-14:09 27.00 19.19
August 0.107324E+11 22403.74 13-AUG-08:51 32.00 20.88 0.329207E+09 548.51 22-AUG-10:09 32.17 19.35
September 0.825948E+10 21577.46 10-SEP-10:01 31.88 19.21 0.292929E+09 548.51 22-SEP-10:09 25.37 17.42
October 0.576292E+10 19560.72 09-OCT-09:52 25.00 14.42 0.301319E+09 548.50 18-OCT-10:09 26.33 11.01
November 0.303708E+10 8610.25 01-NOV-10:05 23.33 16.05 0.294341E+09 548.52 22-NOV-11:09 19.33 11.05
December 0.182653E+10 5666.45 27-DEC-11:05 16.33 7.91 0.277497E+09 548.49 27-DEC-13:09 19.00 10.04
                     
Annual Sum or Average 0.795637E+11         0.359555E+10        
Minimum of Months 0.182653E+10 5666.45   15.83 7.91 0.265483E+09 548.49   15.83 7.96
Maximum of Months 0.124050E+11 22403.74   32.00 20.88 0.329207E+09 548.52   34.33 19.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.121945E+11 21650.21 29-JAN-13:52 24.00 9.34 0.637089E+09 931.25 30-JAN-14:39 24.67 9.55
February 0.670911E+10 17093.60 20-FEB-15:13 18.00 10.13 0.563479E+09 863.80 28-FEB-14:20 18.33 7.88
March 0.740762E+10 15714.64 26-MAR-14:03 17.20 5.96 0.672784E+09 846.80 17-MAR-13:09 17.20 5.96
April 0.101909E+11 21137.67 30-APR-12:32 33.00 12.07 0.611432E+09 847.05 25-APR-13:20 33.00 12.07
May 0.992168E+10 20422.76 07-MAY-16:21 36.00 14.22 0.664375E+09 845.65 30-MAY-09:20 27.33 13.67
June 0.121643E+11 20874.83 25-JUN-18:01 37.67 14.86 0.663009E+09 845.66 19-JUN-13:09 37.67 14.86
July 0.117561E+11 21594.69 30-JUL-14:51 38.00 18.95 0.616842E+09 846.65 31-JUL-13:20 37.00 19.00
August 0.131341E+11 22063.58 13-AUG-16:11 38.00 20.37 0.691748E+09 847.07 28-AUG-13:09 37.83 20.53
September 0.130704E+11 22784.35 10-SEP-12:41 34.22 18.96 0.615933E+09 928.86 28-SEP-13:50 36.83 16.07
October 0.128884E+11 23606.86 09-OCT-12:31 30.33 16.96 0.640279E+09 930.50 31-OCT-13:00 27.00 12.18
November 0.109199E+11 21330.51 19-NOV-13:32 26.00 11.06 0.631647E+09 926.91 20-NOV-14:20 27.00 11.68
December 0.989354E+10 22752.83 03-DEC-14:32 21.00 10.61 0.604038E+09 907.38 28-DEC-14:09 19.47 8.47
                     
Annual Sum or Average 0.130251E+12         0.761266E+10        
Minimum of Months 0.670911E+10 15714.64   17.20 5.96 0.563479E+09 845.65   17.20 5.96
Maximum of Months 0.131341E+11 23606.86   38.00 20.37 0.691748E+09 931.25   37.83 20.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.361844E+10 14447.62 29-JAN-16:32 24.33 9.38 0.390745E+09 544.95 23-JAN-14:20 24.33 9.38
February 0.246807E+10 10774.24 22-FEB-16:30 20.50 11.47 0.351157E+09 544.96 15-FEB-14:00 20.50 11.47
March 0.412716E+10 15884.79 18-MAR-17:05 26.92 12.85 0.430397E+09 544.96 17-MAR-09:00 26.92 12.85
April 0.867369E+10 24766.66 30-APR-16:31 32.33 11.86 0.395248E+09 544.96 27-APR-13:30 32.33 11.86
May 0.100773E+11 24975.43 07-MAY-16:21 36.00 14.22 0.428970E+09 544.96 30-MAY-09:20 27.33 13.67
June 0.128222E+11 26070.20 25-JUN-17:21 38.00 15.15 0.427926E+09 544.96 19-JUN-13:09 38.00 15.15
July 0.106068E+11 25936.65 30-JUL-17:31 38.00 19.05 0.398098E+09 544.97 21-JUL-09:20 38.00 19.05
August 0.108279E+11 26257.94 13-AUG-16:51 38.00 19.94 0.446165E+09 544.96 28-AUG-09:39 33.00 21.02
September 0.830802E+10 23543.97 04-SEP-16:51 31.60 21.23 0.396259E+09 544.96 08-SEP-09:20 30.73 20.63
October 0.597070E+10 22827.49 09-OCT-16:31 32.33 17.29 0.405484E+09 544.99 03-OCT-13:39 32.33 17.29
November 0.393415E+10 14254.25 19-NOV-15:32 27.00 11.63 0.394998E+09 544.97 16-NOV-14:09 27.00 11.63
December 0.261418E+10 14962.26 25-DEC-16:32 24.67 11.46 0.365284E+09 544.95 12-DEC-14:00 24.67 11.46
                     
Annual Sum or Average 0.840486E+11         0.483073E+10        
Minimum of Months 0.246807E+10 10774.24   20.50 9.38 0.351157E+09 544.95   20.50 9.38
Maximum of Months 0.128222E+11 26257.94   38.00 21.23 0.446165E+09 544.99   38.00 21.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.208391E+10 3725.45 31-JAN-16:30 29.00 10.73 0.549847E+09 845.61 27-JAN-14:20 29.00 10.73
February 0.160644E+10 2962.35 22-FEB-16:20 20.67 11.54 0.492454E+09 845.57 22-FEB-14:20 20.67 11.54
March 0.286660E+10 6119.57 16-MAR-16:00 28.80 13.95 0.626250E+09 845.63 17-MAR-09:00 21.60 14.25
April 0.656260E+10 17346.66 30-APR-16:01 32.83 11.93 0.604465E+09 845.63 27-APR-13:00 32.83 11.93
May 0.939259E+10 20763.89 28-MAY-16:51 33.00 12.91 0.663870E+09 845.63 30-MAY-09:20 27.33 13.67
June 0.140539E+11 21426.58 25-JUN-18:11 37.33 14.77 0.663397E+09 845.64 19-JUN-13:09 37.33 14.77
July 0.127784E+11 22924.31 16-JUL-17:31 36.33 21.35 0.617018E+09 845.64 05-JUL-09:09 36.33 21.35
August 0.117501E+11 21400.62 13-AUG-16:21 38.00 20.26 0.691403E+09 845.64 28-AUG-09:30 32.50 20.80
September 0.919967E+10 20594.63 24-SEP-15:32 33.80 18.53 0.613659E+09 845.63 19-SEP-13:20 33.80 18.53
October 0.480640E+10 14762.44 02-OCT-03:02 25.17 16.69 0.605566E+09 845.66 03-OCT-13:39 33.00 20.21
November 0.238116E+10 5852.17 01-NOV-15:30 28.50 15.96 0.568968E+09 845.63 16-NOV-14:20 18.00 11.91
December 0.142373E+10 2556.13 22-DEC-16:40 24.33 9.71 0.495627E+09 833.45 22-DEC-14:00 24.33 9.71
                     
Annual Sum or Average 0.789056E+11         0.719253E+10        
Minimum of Months 0.142373E+10 2556.13   20.67 9.71 0.492454E+09 833.45   18.00 9.71
Maximum of Months 0.140539E+11 22924.31   38.00 21.35 0.691403E+09 845.66   37.33 21.35



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235266E+10 4929.59 27-JAN-10:30 21.00 7.83 0.393502E+09 544.95 23-JAN-14:20 21.00 7.83
February 0.177988E+10 5608.34 23-FEB-10:20 14.67 11.08 0.353640E+09 544.95 15-FEB-14:00 14.67 11.08
March 0.344246E+10 7425.87 23-MAR-10:20 22.33 10.61 0.430879E+09 544.97 14-MAR-13:50 22.33 10.61
April 0.832809E+10 20384.74 09-APR-10:22 26.00 9.74 0.394981E+09 544.99 11-APR-09:09 25.50 10.76
May 0.105086E+11 21475.26 28-MAY-10:12 29.67 12.59 0.428993E+09 545.60 11-MAY-09:00 29.67 12.59
June 0.135516E+11 23110.51 18-JUN-08:11 30.67 17.10 0.427966E+09 545.51 08-JUN-09:00 30.67 17.10
July 0.121605E+11 22388.96 30-JUL-08:11 27.00 19.19 0.398154E+09 545.47 28-JUL-09:00 27.00 19.19
August 0.116911E+11 21209.80 13-AUG-09:42 32.83 21.13 0.446160E+09 545.50 01-AUG-09:00 32.83 21.13
September 0.888975E+10 20288.81 10-SEP-10:12 32.17 19.22 0.396143E+09 546.04 08-SEP-09:00 32.17 19.22
October 0.568674E+10 19843.37 15-OCT-09:22 25.00 10.12 0.405799E+09 544.99 17-OCT-09:30 25.00 10.00
November 0.268801E+10 6508.86 01-NOV-10:00 23.00 16.02 0.393893E+09 544.98 22-NOV-10:50 20.00 11.34
December 0.148177E+10 3126.63 22-DEC-10:40 20.33 8.51 0.359843E+09 544.95 13-DEC-10:20 20.33 8.51
                     
Annual Sum or Average 0.825611E+11         0.482995E+10        
Minimum of Months 0.148177E+10 3126.63   14.67 7.83 0.353640E+09 544.95   14.67 7.83
Maximum of Months 0.135516E+11 23110.51   32.83 21.13 0.446160E+09 546.04   32.83 21.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109213E+11 25863.50 29-JAN-14:11 24.00 9.34 0.619057E+09 872.92 24-JAN-14:00 24.00 9.34
February 0.565047E+10 19554.80 26-FEB-14:43 17.00 9.72 0.547802E+09 846.72 23-FEB-14:00 17.00 9.72
March 0.658945E+10 14425.96 23-MAR-14:00 25.50 11.67 0.657471E+09 845.98 16-MAR-13:00 25.50 11.67
April 0.104448E+11 23532.25 02-APR-16:21 31.00 12.54 0.607993E+09 846.68 25-APR-13:09 31.00 14.74
May 0.104495E+11 22939.21 28-MAY-16:51 33.00 12.91 0.663651E+09 845.65 30-MAY-09:20 27.33 13.67
June 0.133995E+11 22962.87 18-JUN-17:32 38.00 19.14 0.663188E+09 845.66 19-JUN-13:09 38.17 18.27
July 0.130549E+11 25170.12 30-JUL-14:51 38.00 18.95 0.616983E+09 846.02 31-JUL-13:00 37.00 19.00
August 0.141297E+11 23822.36 13-AUG-16:21 38.00 20.26 0.691791E+09 847.36 28-AUG-13:09 37.83 20.53
September 0.136972E+11 24307.75 10-SEP-13:32 34.80 19.48 0.615224E+09 901.84 28-SEP-13:50 36.83 16.07
October 0.125352E+11 26565.62 09-OCT-13:41 31.83 17.27 0.629750E+09 890.31 02-OCT-13:09 31.83 17.27
November 0.982083E+10 23910.90 26-NOV-13:22 18.40 8.55 0.617628E+09 885.34 01-NOV-13:00 18.40 8.55
December 0.815809E+10 24612.10 03-DEC-14:32 21.00 10.61 0.585246E+09 857.15 22-DEC-14:09 25.17 10.15
                     
Annual Sum or Average 0.128851E+12         0.751578E+10        
Minimum of Months 0.565047E+10 14425.96   17.00 8.55 0.547802E+09 845.65   17.00 8.55
Maximum of Months 0.141297E+11 26565.62   38.00 20.26 0.691791E+09 901.84   38.17 20.53



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.317439E+10 20076.17 29-JAN-16:12 24.67 9.41 0.375406E+09 544.95 23-JAN-14:20 24.67 9.41
February 0.210531E+10 10715.77 22-FEB-16:30 20.50 11.47 0.335593E+09 544.96 15-FEB-14:00 20.50 11.47
March 0.375676E+10 17199.12 18-MAR-17:05 26.92 12.85 0.417382E+09 544.97 10-MAR-14:00 26.92 12.85
April 0.884191E+10 27165.16 02-APR-16:21 31.00 12.54 0.393781E+09 544.97 27-APR-13:00 26.00 12.23
May 0.104488E+11 27621.87 28-MAY-16:51 33.00 12.91 0.428841E+09 544.96 30-MAY-09:20 27.33 13.67
June 0.136869E+11 25805.27 25-JUN-17:31 38.00 15.08 0.427987E+09 544.96 19-JUN-13:09 38.00 15.08
July 0.115410E+11 28835.49 30-JUL-17:31 38.00 19.05 0.398145E+09 544.97 05-JUL-09:09 38.00 19.05
August 0.114926E+11 26035.31 13-AUG-16:21 38.00 20.26 0.446178E+09 544.97 28-AUG-09:30 32.50 20.80
September 0.870188E+10 23850.78 24-SEP-15:32 33.80 18.53 0.396212E+09 544.96 15-SEP-09:20 33.80 18.53
October 0.580521E+10 25120.30 09-OCT-15:41 32.83 17.35 0.398369E+09 544.98 03-OCT-13:30 32.83 17.35
November 0.348013E+10 12446.44 01-NOV-16:00 28.00 15.72 0.383783E+09 544.97 16-NOV-14:09 18.00 11.84
December 0.209324E+10 13088.74 25-DEC-16:12 25.33 11.74 0.347869E+09 544.95 22-DEC-14:20 25.33 11.74
                     
Annual Sum or Average 0.851281E+11         0.474955E+10        
Minimum of Months 0.209324E+10 10715.77   20.50 9.41 0.335593E+09 544.95   18.00 9.41
Maximum of Months 0.136869E+11 28835.49   38.00 20.26 0.446178E+09 544.98   38.00 20.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.398051E+10 6159.60 17-JAN-17:00 24.00 9.10 0.00 0.00 01-JAN-00:10 24.00 9.10
February 0.302598E+10 5299.93 21-FEB-16:00 21.00 11.18 0.00 0.00 01-FEB-00:10 21.00 11.18
March 0.487319E+10 7383.93 20-MAR-05:15 11.27 7.51 0.00 0.00 01-MAR-00:10 11.27 7.51
April 0.882027E+10 9319.85 24-APR-14:50 33.00 13.29 0.00 0.00 01-APR-00:10 33.00 13.29
May 0.930571E+10 11964.53 30-MAY-05:15 18.00 8.93 0.00 0.00 01-MAY-00:10 18.00 8.93
June 0.118780E+11 12046.87 05-JUN-05:10 23.33 12.92 0.00 0.00 01-JUN-00:10 23.33 12.92
July 0.117630E+11 15132.12 05-JUL-05:15 23.00 11.31 0.00 0.00 01-JUL-00:10 23.00 11.31
August 0.131770E+11 17219.69 28-AUG-05:13 28.67 19.85 0.00 0.00 01-AUG-00:10 28.67 19.85
September 0.952833E+10 13994.52 05-SEP-05:15 21.63 18.84 0.00 0.00 01-SEP-00:10 21.63 18.84
October 0.738933E+10 13452.12 02-OCT-05:15 25.67 16.91 0.00 0.00 01-OCT-00:10 25.67 16.91
November 0.535549E+10 9054.68 13-NOV-06:15 16.67 16.67 0.00 0.00 01-NOV-00:10 16.67 16.67
December 0.397146E+10 8889.90 26-DEC-06:15 8.67 3.13 0.00 0.00 01-DEC-00:10 8.67 3.13
                     
Annual Sum or Average 0.930682E+11         0.00        
Minimum of Months 0.302598E+10 5299.93   8.67 3.13 0.00 0.00   8.67 3.13
Maximum of Months 0.131770E+11 17219.69   33.00 19.85 0.00 0.00   33.00 19.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.172992E+10 3329.77 27-JAN-17:00 26.00 9.22 0.00 0.00 01-JAN-00:10 26.00 9.22
February 0.113776E+10 3183.66 01-FEB-06:08 5.00 3.59 0.00 0.00 01-FEB-00:10 5.00 3.59
March 0.219080E+10 4310.14 27-MAR-05:03 2.52 -0.8 0.00 0.00 01-MAR-00:10 2.52 -0.8
April 0.595789E+10 7044.22 25-APR-15:20 33.00 15.00 0.00 0.00 01-APR-00:10 33.00 15.00
May 0.776701E+10 7672.61 08-MAY-16:00 34.00 13.77 0.00 0.00 01-MAY-00:10 34.00 13.77
June 0.101724E+11 9638.34 26-JUN-05:02 22.17 10.13 0.00 0.00 01-JUN-00:10 22.17 10.13
July 0.936587E+10 9663.86 31-JUL-05:02 25.83 15.57 0.00 0.00 01-JUL-00:10 25.83 15.57
August 0.945419E+10 12812.67 28-AUG-05:13 28.67 19.85 0.00 0.00 01-AUG-00:10 28.67 19.85
September 0.789798E+10 10573.04 05-SEP-05:15 21.63 18.84 0.00 0.00 01-SEP-00:10 21.63 18.84
October 0.497491E+10 8845.45 02-OCT-05:15 25.67 16.91 0.00 0.00 01-OCT-00:10 25.67 16.91
November 0.237000E+10 4619.41 02-NOV-16:00 26.00 15.13 0.00 0.00 01-NOV-00:10 26.00 15.13
December 0.102966E+10 7311.35 06-DEC-06:01 0.67 -4.3 0.00 0.00 01-DEC-00:10 0.67 -4.3
                     
Annual Sum or Average 0.640484E+11         0.00        
Minimum of Months 0.102966E+10 3183.66   0.67 -4.3 0.00 0.00   0.67 -4.3
Maximum of Months 0.101724E+11 12812.67   34.00 19.85 0.00 0.00   34.00 19.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242422E+10 8574.41 31-JAN-16:00 29.00 10.73 0.00 0.00 01-JAN-00:10 29.00 10.73
February 0.137376E+10 7726.42 23-FEB-14:50 18.00 10.42 0.00 0.00 01-FEB-00:10 18.00 10.42
March 0.362260E+10 12062.91 16-MAR-15:20 28.80 13.79 0.00 0.00 01-MAR-00:10 28.80 13.79
April 0.110112E+11 19394.92 14-APR-15:10 35.00 14.57 0.00 0.00 01-APR-00:10 35.00 14.57
May 0.142776E+11 19868.37 19-MAY-14:00 36.00 14.39 0.00 0.00 01-MAY-00:10 36.00 14.39
June 0.200515E+11 24168.65 28-JUN-14:40 41.67 19.29 0.00 0.00 01-JUN-00:10 41.67 19.29
July 0.176925E+11 22619.36 20-JUL-14:00 39.00 20.25 0.00 0.00 01-JUL-00:10 39.00 20.25
August 0.172928E+11 22243.24 15-AUG-15:10 39.00 18.89 0.00 0.00 01-AUG-00:10 39.00 18.89
September 0.129386E+11 19760.21 07-SEP-15:20 37.37 19.77 0.00 0.00 01-SEP-00:10 37.37 19.77
October 0.702377E+10 17355.82 02-OCT-14:20 35.00 19.60 0.00 0.00 01-OCT-00:10 35.00 19.60
November 0.285150E+10 11084.33 01-NOV-15:20 28.67 16.04 0.00 0.00 01-NOV-00:10 28.67 16.04
December 0.105486E+10 6487.88 22-DEC-16:00 25.00 10.09 0.00 0.00 01-DEC-00:10 25.00 10.09
                     
Annual Sum or Average 0.111615E+12         0.00        
Minimum of Months 0.105486E+10 6487.88   18.00 10.09 0.00 0.00   18.00 10.09
Maximum of Months 0.200515E+11 24168.65   41.67 20.25 0.00 0.00   41.67 20.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.414151E+10 2269.16 29-JAN-17:15 23.00 8.84 95230214.27 126.83 09-JAN-10:00 23.00 8.84
February 0.823446E+10 4068.56 27-FEB-17:40 15.67 8.53 86398657.49 126.84 16-FEB-10:00 15.67 8.53
March 0.144140E+11 7149.80 31-MAR-24:00 15.30 7.49 0.103237E+09 126.84 06-MAR-10:00 15.30 7.49
April 0.185555E+11 7785.51 26-APR-18:50 19.33 9.57 99322857.61 159.69 24-APR-13:00 19.33 9.57
May 0.471936E+10 3493.39 31-MAY-23:55 26.00 10.61 99233117.34 126.82 19-MAY-09:09 26.00 10.61
June 0.954770E+10 5429.60 30-JUN-24:00 28.10 15.37 98957378.99 126.83 30-JUN-09:00 28.10 15.37
July 0.148976E+11 7341.07 31-JUL-23:57 29.60 17.96 91883958.92 126.84 27-JUL-09:09 29.60 17.96
August 0.196111E+11 7782.77 20-AUG-23:50 26.17 16.39 0.112105E+09 169.89 25-AUG-13:00 41.00 17.20
September 0.458685E+10 3492.33 30-SEP-24:00 25.20 15.49 91612397.87 126.85 01-SEP-09:00 25.20 15.49
October 0.963715E+10 5321.31 31-OCT-24:00 17.10 9.96 95231184.19 126.85 03-OCT-09:00 17.10 9.96
November 0.140766E+11 6268.13 26-NOV-16:53 18.00 8.58 94301954.55 126.84 13-NOV-10:09 18.00 8.58
December 0.193696E+11 7940.85 28-DEC-17:00 18.60 7.88 92185077.12 135.84 22-DEC-16:00 18.60 7.88
                     
Annual Sum or Average 0.141791E+12         0.115970E+10        
Minimum of Months 0.414151E+10 2269.16   15.30 7.49 86398657.49 126.82   15.30 7.49
Maximum of Months 0.196111E+11 7940.85   29.60 17.96 0.112105E+09 169.89   41.00 17.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.304665E+10 2061.23 24-JAN-17:00 24.00 10.79 95230207.77 126.83 09-JAN-10:00 24.00 10.79
February 0.699125E+10 3810.85 27-FEB-17:40 15.67 8.53 86398559.28 126.84 16-FEB-10:00 15.67 8.53
March 0.131340E+11 6696.05 31-MAR-23:40 15.33 7.15 0.103237E+09 126.83 06-MAR-10:00 15.33 7.15
April 0.175603E+11 7420.90 26-APR-18:50 19.33 9.57 98233959.39 155.90 24-APR-13:00 19.33 9.57
May 0.435302E+10 3404.56 31-MAY-23:55 26.00 10.61 99233117.44 126.82 26-MAY-09:50 26.00 10.61
June 0.908428E+10 5222.19 30-JUN-24:00 28.10 15.37 98957379.66 126.83 30-JUN-09:00 28.10 15.37
July 0.141506E+11 7013.90 31-JUL-23:57 29.60 17.96 91883937.55 126.83 14-JUL-09:09 29.60 17.96
August 0.184517E+11 7274.42 20-AUG-20:52 29.00 16.20 0.110316E+09 164.74 25-AUG-13:00 41.00 17.20
September 0.419680E+10 3408.00 30-SEP-24:00 25.20 15.49 91611518.36 126.85 05-SEP-13:09 25.20 15.49
October 0.877414E+10 4928.06 31-OCT-24:00 17.10 9.96 95231146.58 126.84 03-OCT-09:00 17.10 9.96
November 0.127148E+11 5827.19 14-NOV-17:00 19.00 14.11 94301864.40 126.84 13-NOV-14:00 19.00 14.11
December 0.173868E+11 7471.51 28-DEC-17:00 18.60 7.88 92033127.78 133.78 22-DEC-16:00 18.60 7.88
                     
Annual Sum or Average 0.129844E+12         0.115667E+10        
Minimum of Months 0.304665E+10 2061.23   15.33 7.15 86398559.28 126.82   15.33 7.15
Maximum of Months 0.184517E+11 7471.51   29.60 17.96 0.110316E+09 164.74   41.00 17.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.216409E+10 2077.23 24-JAN-17:00 24.00 10.79 95099918.31 126.83 09-JAN-10:00 24.00 10.79
February 0.597386E+10 3784.95 27-FEB-17:40 15.67 8.53 86398550.42 126.84 16-FEB-10:00 15.67 8.53
March 0.124763E+11 6523.96 31-MAR-23:20 15.37 6.81 0.103237E+09 126.83 06-MAR-10:00 15.37 6.81
April 0.175939E+11 7533.02 26-APR-18:30 20.00 9.88 97223852.71 155.75 24-APR-13:00 20.00 9.88
May 0.438273E+10 3403.52 31-MAY-23:55 26.00 10.61 99233117.55 126.82 04-MAY-09:39 26.00 10.61
June 0.924050E+10 5274.16 30-JUN-24:00 28.10 15.37 98957381.71 126.83 30-JUN-09:00 28.10 15.37
July 0.143263E+11 7058.14 31-JUL-23:57 29.60 17.96 91884983.79 126.84 14-JUL-09:00 29.60 17.96
August 0.186273E+11 7475.90 20-AUG-21:03 28.83 16.12 0.109183E+09 164.95 25-AUG-13:00 41.00 17.20
September 0.426440E+10 3436.68 30-SEP-24:00 25.20 15.49 91611852.07 126.85 05-SEP-13:09 25.20 15.49
October 0.840363E+10 4740.24 31-OCT-23:40 16.87 9.55 95231171.27 126.84 03-OCT-09:00 16.87 9.55
November 0.118700E+11 5847.14 21-NOV-17:00 24.00 10.76 94301923.86 126.84 13-NOV-14:00 24.00 10.76
December 0.160235E+11 7433.67 28-DEC-17:00 18.60 7.88 91934076.93 130.43 22-DEC-16:00 18.60 7.88
                     
Annual Sum or Average 0.125346E+12         0.115430E+10        
Minimum of Months 0.216409E+10 2077.23   15.37 6.81 86398550.42 126.82   15.37 6.81
Maximum of Months 0.186273E+11 7533.02   29.60 17.96 0.109183E+09 164.95   41.00 17.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.240106E+12 92349.85 17-JAN-17:00 24.00 9.10 0.206145E+10 2745.41 02-JAN-14:09 24.00 9.10
February 0.435269E+12 182944.37 21-FEB-17:00 19.00 10.37 0.187024E+10 2746.75 17-FEB-14:00 19.00 10.37
March 0.727234E+12 358012.76 31-MAR-24:00 15.30 7.49 0.223501E+10 2748.84 16-MAR-13:00 15.30 7.49
April 0.934645E+12 380835.57 03-APR-21:01 22.83 9.11 0.248370E+10 4982.13 14-APR-13:00 34.00 14.07
May 0.240612E+12 175605.43 31-MAY-24:00 26.00 10.61 0.214826E+10 2747.10 15-MAY-13:00 26.00 10.61
June 0.469374E+12 267480.47 30-JUN-23:57 28.10 15.37 0.214272E+10 2748.03 22-JUN-09:09 28.10 15.37
July 0.732400E+12 356506.24 31-JUL-23:13 30.33 18.19 0.200146E+10 3312.68 14-JUL-09:00 30.33 18.19
August 0.963396E+12 386584.44 23-AUG-22:53 24.00 10.56 0.310100E+10 5027.92 23-AUG-13:09 24.00 10.56
September 0.238418E+12 177154.08 30-SEP-24:00 25.20 15.49 0.198321E+10 2746.81 15-SEP-09:09 25.20 15.49
October 0.489388E+12 269011.04 31-OCT-24:00 17.10 9.96 0.206169E+10 2748.14 16-OCT-13:00 17.10 9.96
November 0.710151E+12 276954.62 20-NOV-17:00 26.00 12.00 0.204173E+10 2751.10 13-NOV-10:09 26.00 12.00
December 0.977947E+12 372186.93 25-DEC-16:41 24.33 11.32 0.199499E+10 3133.56 22-DEC-14:00 24.33 11.32
                     
Annual Sum or Average 0.715894E+13         0.261255E+11        
Minimum of Months 0.238418E+12 92349.85   15.30 7.49 0.187024E+10 2745.41   15.30 7.49
Maximum of Months 0.977947E+12 386584.44   30.33 18.19 0.310100E+10 5027.92   34.00 18.19



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.345531E+09 11480.72 24-JAN-05:17 13.33
February 0.114212E+09 11457.45 23-FEB-05:15 8.67
March 0.109796E+09 12834.19 18-MAR-16:01 27.20
April 0.358108E+09 19795.75 29-APR-16:01 32.67
May 0.364403E+09 22668.93 20-MAY-16:01 34.83
June 0.414399E+09 29562.88 17-JUN-16:02 40.50
July 0.606171E+09 26754.97 22-JUL-16:01 38.00
August 0.429520E+09 30163.10 26-AUG-16:01 40.83
September 0.595242E+09 21939.16 23-SEP-16:01 34.30
October 0.430570E+09 17556.14 14-OCT-16:01 31.00
November 0.292775E+09 11064.69 01-NOV-04:57 20.00
December 0.263541E+09 12048.59 03-DEC-15:12 21.00
         
Annual Sum or Average 0.432427E+10      
Minimum of Months 0.109796E+09 11064.69   8.67
Maximum of Months 0.606171E+09 30163.10   40.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234595E+09 67034.84 02-JAN-05:11 4.00
February 20012395.13 59420.34 13-FEB-06:03 8.00
March 6468118.00 43120.79 27-MAR-05:03 2.52
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 7686140.74 51240.94 24-NOV-06:03 3.17
December 94282657.12 62254.29 18-DEC-05:11 4.00
         
Annual Sum or Average 0.363045E+09      
Minimum of Months 0.00 0.00   2.52
Maximum of Months 0.234595E+09 67034.84   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 225126.21 2626.47 07-DEC-06:01 -0.7
         
Annual Sum or Average 225126.21      
Minimum of Months 0.00 0.00   -0.7
Maximum of Months 225126.21 2626.47   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 58849591.67 13838.04 02-JAN-05:11 4.00
February 10857130.59 8416.82 03-FEB-06:02 6.83
March 28685826.61 12903.71 27-MAR-04:11 2.37
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 17431990.92 12216.02 24-NOV-06:03 3.17
December 0.192557E+09 13258.20 07-DEC-05:01 -1.1
         
Annual Sum or Average 0.308381E+09      
Minimum of Months 0.00 0.00   -1.1
Maximum of Months 0.192557E+09 13838.04   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 22948094.39 11717.02 02-JAN-05:11 4.00
February 2737005.38 5687.94 13-FEB-06:03 8.00
March 7211623.46 8012.33 27-MAR-05:03 2.52
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 4616443.52 8162.62 24-NOV-06:03 3.17
December 75282466.87 11284.82 07-DEC-05:01 -1.1
         
Annual Sum or Average 0.112796E+09      
Minimum of Months 0.00 0.00   -1.1
Maximum of Months 75282466.87 11717.02   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6561180.29 12309.42 02-JAN-06:03 4.33
February 2862509.95 7393.08 13-FEB-06:03 8.00
March 3956493.25 10407.65 27-MAR-05:03 2.52
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 376042.79 2506.95 24-NOV-06:03 3.17
December 28086606.34 13878.41 07-DEC-06:01 -0.7
         
Annual Sum or Average 41842832.61      
Minimum of Months 0.00 0.00   -0.7
Maximum of Months 28086606.34 13878.41   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 9766344.70 8365.44 02-JAN-06:03 4.33
February 670115.72 2652.12 13-FEB-06:03 8.00
March 779704.00 4728.04 27-MAR-05:03 2.52
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 1375945.65 5938.77 24-NOV-06:03 3.17
December 42677287.00 10067.51 07-DEC-06:01 -0.7
         
Annual Sum or Average 55269397.07      
Minimum of Months 0.00 0.00   -0.7
Maximum of Months 42677287.00 10067.51   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.511390E+09 17622.08 02-JAN-05:11 4.00
February 0.404352E+09 15990.18 13-FEB-05:11 8.00
March 0.272978E+09 16579.41 27-MAR-04:11 2.37
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 40671639.58 14349.37 26-OCT-05:02 7.17
November 0.311626E+09 16785.64 24-NOV-05:11 3.67
December 0.121247E+10 17544.53 18-DEC-05:11 4.00
         
Annual Sum or Average 0.275348E+10      
Minimum of Months 0.00 0.00   2.37
Maximum of Months 0.121247E+10 17622.08   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.197345E+09 15756.87 02-JAN-05:11 4.00
February 0.161348E+09 14097.34 13-FEB-05:11 8.00
March 0.111958E+09 14283.72 27-MAR-04:11 2.37
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 12458711.56 9671.21 26-OCT-05:02 7.17
November 0.113104E+09 14738.38 24-NOV-05:11 3.67
December 0.507905E+09 15461.31 18-DEC-05:11 4.00
         
Annual Sum or Average 0.110412E+10      
Minimum of Months 0.00 0.00   2.37
Maximum of Months 0.507905E+09 15756.87   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 98382799.71 17983.60 02-JAN-05:11 4.00
February 0.138413E+09 17435.08 13-FEB-05:11 8.00
March 0.136918E+09 16956.91 27-MAR-04:11 2.37
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 4206499.09 6483.74 26-OCT-05:02 7.17
November 64409358.89 16784.12 24-NOV-05:11 3.67
December 0.424132E+09 17666.19 18-DEC-05:11 4.00
         
Annual Sum or Average 0.866462E+09      
Minimum of Months 0.00 0.00   2.37
Maximum of Months 0.424132E+09 17983.60   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 94560222.23 15224.29 02-JAN-05:11 4.00
February 90244716.29 13617.56 13-FEB-05:11 8.00
March 50957321.74 13520.39 27-MAR-04:11 2.37
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 2220810.58 4506.69 26-OCT-05:02 7.17
November 54972830.83 14035.83 24-NOV-05:11 3.67
December 0.368021E+09 14989.32 18-DEC-05:11 4.00
         
Annual Sum or Average 0.660977E+09      
Minimum of Months 0.00 0.00   2.37
Maximum of Months 0.368021E+09 15224.29   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.108086E+09 8361.41 29-JAN-16:22 24.50
February 76987569.43 9218.00 13-FEB-05:11 8.00
March 93106914.35 9082.76 27-MAR-04:11 2.37
April 0.107292E+09 10752.99 23-APR-15:41 33.25
May 69576910.04 8837.77 07-MAY-15:41 35.83
June 52586428.24 8572.95 25-JUN-16:31 38.00
July 77087589.22 9184.09 30-JUL-16:21 38.00
August 95016740.13 9203.88 27-AUG-15:41 40.00
September 58187279.18 7714.02 10-SEP-14:01 35.18
October 92483828.22 8398.70 15-OCT-14:01 31.00
November 0.130956E+09 9209.28 24-NOV-05:11 3.67
December 0.168585E+09 10730.75 11-DEC-05:11 8.33
         
Annual Sum or Average 0.112995E+10      
Minimum of Months 52586428.24 7714.02   2.37
Maximum of Months 0.168585E+09 10752.99   40.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.334017E+09 7989.79 01-JAN-13:33 14.17
February 0.129325E+09 6192.75 14-FEB-06:02 7.83
March 64694194.10 7936.06 26-MAR-16:01 18.30
April 62176280.95 9157.64 30-APR-15:51 33.00
May 59238549.45 9287.68 07-MAY-15:41 35.83
June 58235657.91 8826.02 04-JUN-16:41 38.00
July 73512636.37 9326.46 30-JUL-16:11 38.00
August 52717249.60 9065.39 27-AUG-15:41 40.00
September 48724971.06 7981.96 10-SEP-14:01 35.18
October 63662675.90 7762.50 15-OCT-15:32 31.00
November 69429358.84 7417.06 19-NOV-15:32 27.00
December 0.307945E+09 7504.69 25-DEC-16:32 24.67
         
Annual Sum or Average 0.132368E+10      
Minimum of Months 48724971.06 6192.75   7.83
Maximum of Months 0.334017E+09 9326.46   40.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.175548E+10 17586.12 02-JAN-06:03 4.33
February 0.145718E+10 9011.32 13-FEB-06:03 8.00
March 0.133369E+10 12657.49 21-MAR-05:03 13.53
April 0.402951E+09 13589.05 27-APR-05:03 12.00
May 0.164702E+09 12227.14 01-MAY-04:12 12.33
June 40923042.58 11634.08 12-JUN-04:12 20.00
July 31112667.66 12621.14 03-JUL-04:11 20.67
August 30347356.73 8683.62 25-AUG-04:12 22.00
September 48720311.13 10580.54 11-SEP-04:11 22.37
October 0.721551E+09 12494.69 18-OCT-05:03 15.83
November 0.119634E+10 11018.84 02-NOV-05:03 16.00
December 0.254148E+10 15625.54 18-DEC-06:03 3.83
         
Annual Sum or Average 0.972448E+10      
Minimum of Months 30347356.73 8683.62   3.83
Maximum of Months 0.254148E+10 17586.12   22.37



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 6754451.68 263.98 01-JAN-08:30 3.10
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 6754451.68      
Minimum of Months 0.00 0.00   3.10
Maximum of Months 6754451.68 263.98   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 73102594.11 583.89 01-JAN-02:65 4.45
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 73102594.11      
Minimum of Months 0.00 0.00   4.45
Maximum of Months 73102594.11 583.89   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:05 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:05 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.138227E+11 14744.03 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.125395E+11 14744.03 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.149226E+11 14744.03 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.133065E+11 14744.03 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.143726E+11 14744.03 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.143114E+11 14744.03 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.133677E+11 14744.03 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.149224E+11 14744.03 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.133065E+11 14744.03 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.138228E+11 14744.03 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.136668E+11 14744.03 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.133678E+11 14744.03 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.165729E+12     0.424397E+12    
Minimum of Months 0.125395E+11 14744.03   0.325565E+11 13457.54  
Maximum of Months 0.149226E+11 14744.03   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243681E+11 17206.63 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.63 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253549E+11 17206.63 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235306E+11 17206.63 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248615E+11 17206.63 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244160E+11 17206.63 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239708E+11 17206.63 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253549E+11 17206.63 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235199E+11 17206.63 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243735E+11 17206.63 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238373E+11 17206.63 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239654E+11 17206.63 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289614E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.63  
Maximum of Months 0.134015E+11 13241.18   0.253549E+11 17206.63  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289613E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.56  
Maximum of Months 0.134015E+11 13241.18   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.124138E+11 13241.18 02-JAN-08:09 0.243680E+11 17206.56 02-JAN-08:09
February 0.112614E+11 13241.18 01-FEB-08:09 0.220609E+11 17206.56 01-FEB-08:09
March 0.134015E+11 13241.18 01-MAR-08:09 0.253548E+11 17206.56 01-MAR-08:09
April 0.119501E+11 13241.18 03-APR-07:10 0.235305E+11 17206.56 03-APR-07:10
May 0.129076E+11 13241.18 01-MAY-07:10 0.248614E+11 17206.56 01-MAY-07:10
June 0.128527E+11 13241.18 01-JUN-07:10 0.244159E+11 17206.56 01-JUN-07:10
July 0.120051E+11 13241.18 03-JUL-07:10 0.239707E+11 17206.56 03-JUL-07:10
August 0.134014E+11 13241.18 01-AUG-07:10 0.253548E+11 17206.56 01-AUG-07:10
September 0.119501E+11 13241.18 01-SEP-07:10 0.235198E+11 17206.56 01-SEP-07:10
October 0.124139E+11 13241.18 02-OCT-07:10 0.243734E+11 17206.56 02-OCT-07:10
November 0.122737E+11 13241.18 01-NOV-07:10 0.238372E+11 17206.56 01-NOV-07:10
December 0.120052E+11 13241.18 01-DEC-08:09 0.239653E+11 17206.56 01-DEC-08:09
             
Annual Sum or Average 0.148837E+12     0.289613E+12    
Minimum of Months 0.112614E+11 13241.18   0.220609E+11 17206.56  
Maximum of Months 0.134015E+11 13241.18   0.253548E+11 17206.56  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.960530E+09 1483.93 20-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.850741E+09 1384.14 03-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.945721E+09 1291.50 21-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.815169E+09 888.77 04-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.861333E+09 852.41 26-MAY-08:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.839595E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.795360E+09 875.04 13-JUL-15:00 0.300989E+10 2160.55 03-JUL-07:10
August 0.911639E+09 1305.75 04-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.833039E+09 1137.97 29-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.913581E+09 1424.65 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.937834E+09 1662.56 28-NOV-16:30 0.299314E+10 2160.55 01-NOV-07:10
December 0.948426E+09 1662.56 01-DEC-16:30 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.106130E+11     0.363654E+11    
Minimum of Months 0.795360E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.960530E+09 1662.56   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.596966E+09 947.23 20-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.535436E+09 857.16 10-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.603834E+09 589.31 08-MAR-16:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.522248E+09 509.78 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.557115E+09 509.78 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.544036E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.516111E+09 572.03 13-JUL-15:00 0.193969E+10 1392.34 03-JUL-07:10
August 0.586256E+09 816.23 04-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.533831E+09 568.78 29-SEP-14:30 0.190321E+10 1392.34 01-SEP-07:10
October 0.572478E+09 685.59 31-OCT-15:00 0.197228E+10 1392.34 02-OCT-07:10
November 0.589729E+09 1071.42 28-NOV-16:30 0.192889E+10 1392.34 01-NOV-07:10
December 0.592213E+09 1071.42 01-DEC-16:30 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.675025E+10     0.234352E+11    
Minimum of Months 0.516111E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.603834E+09 1071.42   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.911008E+09 1447.58 20-JAN-16:00 0.305983E+10 2160.58 02-JAN-08:09
February 0.821898E+09 1355.67 10-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.933626E+09 1237.32 21-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.818346E+09 896.29 04-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.870419E+09 852.41 26-MAY-08:30 0.312179E+10 2160.58 01-MAY-07:10
June 0.850874E+09 839.02 27-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.806485E+09 880.24 27-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.916923E+09 1312.97 04-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.830153E+09 906.35 19-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.878990E+09 1236.87 27-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.901388E+09 1662.60 28-NOV-16:30 0.299318E+10 2160.58 01-NOV-07:10
December 0.901245E+09 1662.60 01-DEC-16:30 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.104414E+11     0.363660E+11    
Minimum of Months 0.806485E+09 839.02   0.277013E+10 2160.58  
Maximum of Months 0.933626E+09 1662.60   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.606536E+09 968.51 20-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.541169E+09 897.70 10-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.607010E+09 905.19 21-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.525768E+09 702.14 04-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.559137E+09 569.32 26-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.545430E+09 543.10 27-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.517353E+09 570.33 24-JUL-08:20 0.193968E+10 1392.33 03-JUL-07:10
August 0.589490E+09 856.93 04-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.536910E+09 805.87 29-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.580099E+09 932.09 27-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.593398E+09 1071.42 28-NOV-16:30 0.192888E+10 1392.33 01-NOV-07:10
December 0.598140E+09 1071.42 01-DEC-16:30 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.680044E+10     0.234351E+11    
Minimum of Months 0.517353E+09 543.10   0.178514E+10 1392.33  
Maximum of Months 0.607010E+09 1071.42   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.956508E+09 1480.95 20-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.847726E+09 1379.52 10-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.943341E+09 1286.17 21-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.814286E+09 879.57 04-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.861125E+09 842.61 26-MAY-08:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.839374E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.794857E+09 866.52 13-JUL-15:00 0.300989E+10 2160.55 03-JUL-07:10
August 0.910329E+09 1301.67 04-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.831871E+09 1130.38 29-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.909964E+09 1420.76 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.934337E+09 1662.56 28-NOV-16:30 0.299314E+10 2160.55 01-NOV-07:10
December 0.944273E+09 1662.56 01-DEC-16:30 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.105880E+11     0.363654E+11    
Minimum of Months 0.794857E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.956508E+09 1662.56   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.596262E+09 944.01 20-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.534387E+09 851.98 10-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.603301E+09 585.39 08-MAR-16:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.522101E+09 509.78 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.556862E+09 509.78 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.543673E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.515475E+09 567.16 13-JUL-15:00 0.193969E+10 1392.34 03-JUL-07:10
August 0.585501E+09 810.47 04-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.533458E+09 563.69 29-SEP-14:30 0.190321E+10 1392.34 01-SEP-07:10
October 0.571481E+09 671.44 31-OCT-15:00 0.197228E+10 1392.34 02-OCT-07:10
November 0.588833E+09 1071.42 28-NOV-16:30 0.192889E+10 1392.34 01-NOV-07:10
December 0.591086E+09 1071.42 01-DEC-16:30 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.674242E+10     0.234352E+11    
Minimum of Months 0.515475E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.603301E+09 1071.42   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.910792E+09 1445.32 20-JAN-16:00 0.305983E+10 2160.58 02-JAN-08:09
February 0.821194E+09 1352.22 10-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.932693E+09 1231.58 21-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.817506E+09 887.78 04-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.869677E+09 842.61 26-MAY-08:30 0.312179E+10 2160.58 01-MAY-07:10
June 0.849956E+09 791.06 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.805263E+09 870.46 27-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.915522E+09 1308.95 04-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.829257E+09 899.61 29-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.876999E+09 1182.61 27-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.900557E+09 1662.60 28-NOV-16:30 0.299318E+10 2160.58 01-NOV-07:10
December 0.900950E+09 1662.60 01-DEC-16:30 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.104304E+11     0.363660E+11    
Minimum of Months 0.805263E+09 791.06   0.277013E+10 2160.58  
Maximum of Months 0.932693E+09 1662.60   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.604826E+09 966.14 20-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.539646E+09 893.17 10-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.605903E+09 900.60 21-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.525321E+09 693.99 04-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.558634E+09 564.31 26-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.545020E+09 509.78 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.516639E+09 565.16 24-JUL-08:20 0.193968E+10 1392.33 03-JUL-07:10
August 0.588567E+09 851.30 04-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.536202E+09 798.69 29-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.578763E+09 929.22 27-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.592169E+09 1071.42 28-NOV-16:30 0.192888E+10 1392.33 01-NOV-07:10
December 0.596707E+09 1071.42 01-DEC-16:30 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.678840E+10     0.234351E+11    
Minimum of Months 0.516639E+09 509.78   0.178514E+10 1392.33  
Maximum of Months 0.605903E+09 1071.42   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.956467E+09 1480.71 20-JAN-08:09 0.305979E+10 2160.55 02-JAN-08:09
February 0.847675E+09 1378.94 10-FEB-08:09 0.277008E+10 2160.55 01-FEB-08:09
March 0.943221E+09 1285.55 21-MAR-07:10 0.318369E+10 2160.55 01-MAR-08:09
April 0.814276E+09 879.40 04-APR-07:10 0.295462E+10 2160.55 03-APR-07:10
May 0.861120E+09 842.22 26-MAY-08:30 0.312174E+10 2160.55 01-MAY-07:10
June 0.839373E+09 791.05 01-JUN-07:10 0.306580E+10 2160.55 01-JUN-07:10
July 0.794835E+09 866.18 13-JUL-15:00 0.300989E+10 2160.55 03-JUL-07:10
August 0.910303E+09 1300.93 04-AUG-07:10 0.318369E+10 2160.55 01-AUG-07:10
September 0.831805E+09 1129.45 29-SEP-07:10 0.295328E+10 2160.55 01-SEP-07:10
October 0.909899E+09 1420.64 31-OCT-07:10 0.306046E+10 2160.55 02-OCT-07:10
November 0.934294E+09 1662.56 28-NOV-16:30 0.299314E+10 2160.55 01-NOV-07:10
December 0.944194E+09 1662.56 01-DEC-16:30 0.300922E+10 2160.55 01-DEC-08:09
             
Annual Sum or Average 0.105875E+11     0.363654E+11    
Minimum of Months 0.794835E+09 791.05   0.277008E+10 2160.55  
Maximum of Months 0.956467E+09 1662.56   0.318369E+10 2160.55  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.596252E+09 943.75 20-JAN-16:00 0.197184E+10 1392.34 02-JAN-08:09
February 0.534349E+09 851.56 10-FEB-08:09 0.178515E+10 1392.34 01-FEB-08:09
March 0.603278E+09 585.26 08-MAR-16:00 0.205169E+10 1392.34 01-MAR-08:09
April 0.522092E+09 509.78 03-APR-07:10 0.190407E+10 1392.34 03-APR-07:10
May 0.556858E+09 509.78 01-MAY-07:10 0.201177E+10 1392.34 01-MAY-07:10
June 0.543663E+09 509.78 01-JUN-07:10 0.197572E+10 1392.34 01-JUN-07:10
July 0.515425E+09 566.96 13-JUL-15:00 0.193969E+10 1392.34 03-JUL-07:10
August 0.585491E+09 809.96 04-AUG-07:10 0.205169E+10 1392.34 01-AUG-07:10
September 0.533443E+09 563.52 29-SEP-14:30 0.190321E+10 1392.34 01-SEP-07:10
October 0.571445E+09 671.36 31-OCT-15:00 0.197228E+10 1392.34 02-OCT-07:10
November 0.588810E+09 1071.42 28-NOV-16:30 0.192889E+10 1392.34 01-NOV-07:10
December 0.591073E+09 1071.42 01-DEC-16:30 0.193926E+10 1392.34 01-DEC-08:09
             
Annual Sum or Average 0.674218E+10     0.234352E+11    
Minimum of Months 0.515425E+09 509.78   0.178515E+10 1392.34  
Maximum of Months 0.603278E+09 1071.42   0.205169E+10 1392.34  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.910758E+09 1444.89 20-JAN-16:00 0.305983E+10 2160.58 02-JAN-08:09
February 0.821173E+09 1351.59 10-FEB-08:09 0.277013E+10 2160.58 01-FEB-08:09
March 0.932663E+09 1230.90 21-MAR-07:10 0.318374E+10 2160.58 01-MAR-08:09
April 0.817468E+09 887.62 04-APR-07:10 0.295467E+10 2160.58 03-APR-07:10
May 0.869664E+09 842.22 26-MAY-08:30 0.312179E+10 2160.58 01-MAY-07:10
June 0.849944E+09 791.06 01-JUN-07:10 0.306585E+10 2160.58 01-JUN-07:10
July 0.805239E+09 870.31 27-JUL-07:10 0.300994E+10 2160.58 03-JUL-07:10
August 0.915486E+09 1308.21 04-AUG-07:10 0.318374E+10 2160.58 01-AUG-07:10
September 0.829239E+09 899.40 29-SEP-07:10 0.295333E+10 2160.58 01-SEP-07:10
October 0.876992E+09 1182.19 27-OCT-07:10 0.306051E+10 2160.58 02-OCT-07:10
November 0.900548E+09 1662.60 28-NOV-16:30 0.299318E+10 2160.58 01-NOV-07:10
December 0.900943E+09 1662.60 01-DEC-16:30 0.300927E+10 2160.58 01-DEC-08:09
             
Annual Sum or Average 0.104301E+11     0.363660E+11    
Minimum of Months 0.805239E+09 791.06   0.277013E+10 2160.58  
Maximum of Months 0.932663E+09 1662.60   0.318374E+10 2160.58  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.604762E+09 966.01 20-JAN-08:09 0.197183E+10 1392.33 02-JAN-08:09
February 0.539622E+09 892.81 10-FEB-08:09 0.178514E+10 1392.33 01-FEB-08:09
March 0.605886E+09 900.31 21-MAR-07:10 0.205168E+10 1392.33 01-MAR-08:09
April 0.525315E+09 693.91 04-APR-07:10 0.190406E+10 1392.33 03-APR-07:10
May 0.558611E+09 564.12 26-MAY-07:10 0.201175E+10 1392.33 01-MAY-07:10
June 0.545021E+09 509.78 01-JUN-07:10 0.197570E+10 1392.33 01-JUN-07:10
July 0.516636E+09 565.00 24-JUL-08:20 0.193968E+10 1392.33 03-JUL-07:10
August 0.588548E+09 850.85 04-AUG-07:10 0.205168E+10 1392.33 01-AUG-07:10
September 0.536170E+09 798.21 29-SEP-07:10 0.190319E+10 1392.33 01-SEP-07:10
October 0.578752E+09 929.08 27-OCT-07:10 0.197226E+10 1392.33 02-OCT-07:10
November 0.592155E+09 1071.42 28-NOV-16:30 0.192888E+10 1392.33 01-NOV-07:10
December 0.596642E+09 1071.42 01-DEC-16:30 0.193924E+10 1392.33 01-DEC-08:09
             
Annual Sum or Average 0.678812E+10     0.234351E+11    
Minimum of Months 0.516636E+09 509.78   0.178514E+10 1392.33  
Maximum of Months 0.605886E+09 1071.42   0.205168E+10 1392.33  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.302573E+09 316.63 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.274456E+09 316.63 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.326130E+09 316.63 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.291301E+09 316.63 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.314351E+09 316.63 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.312831E+09 316.63 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.292821E+09 316.63 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.326130E+09 316.63 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.291301E+09 316.63 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.302573E+09 316.63 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.299026E+09 316.63 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.292821E+09 316.63 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.362631E+10     0.153881E+12    
Minimum of Months 0.274456E+09 316.63   0.505780E+10 1948.61  
Maximum of Months 0.326130E+09 316.63   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.397259E+10 4157.19 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.360343E+10 4157.19 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.428189E+10 4157.19 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.382459E+10 4157.19 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.412724E+10 4157.19 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.410728E+10 4157.19 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.384455E+10 4157.19 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.428189E+10 4157.19 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.382459E+10 4157.19 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.397259E+10 4157.19 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.392603E+10 4157.19 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.384455E+10 4157.19 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.476112E+11     0.749486E+13    
Minimum of Months 0.360343E+10 4157.19   0.246344E+12 94908.13  
Maximum of Months 0.428189E+10 4157.19   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.138227E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.125395E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.149226E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.133065E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.143726E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.143114E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.133677E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.149224E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.133065E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.138228E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.136668E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.133678E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.165729E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.125395E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.149226E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243681E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235306E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248615E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244160E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239708E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235199E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243735E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238373E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239654E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289614E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253549E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.124138E+11 0.243680E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.119501E+11 0.235305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.129076E+11 0.248614E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.128527E+11 0.244159E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.120051E+11 0.239707E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.134014E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.119501E+11 0.235198E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.124139E+11 0.243734E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.122737E+11 0.238372E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.120052E+11 0.239653E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.148837E+12 0.289613E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.112614E+11 0.220609E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.134015E+11 0.253548E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.960530E+09 0.305979E+10 0.00 0.00 0.00 0.00 1024404.48 0.335734E+09
February 0.136985E+10 0.850741E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.268422E+09
March 0.163685E+10 0.945721E+09 0.318369E+10 0.00 0.00 0.00 0.00 2848744.38 0.342667E+09
April 0.145243E+10 0.815169E+09 0.295462E+10 0.00 0.00 0.00 0.00 51089651.87 0.105764E+09
May 0.157338E+10 0.861333E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.100148E+09 68316089.63
June 0.156900E+10 0.839595E+09 0.306580E+10 0.00 0.00 0.00 0.00 0.185300E+09 15440727.64
July 0.145680E+10 0.795360E+09 0.300989E+10 0.00 0.00 0.00 0.00 0.183779E+09 12456947.41
August 0.163685E+10 0.911639E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.127642E+09 19658835.66
September 0.145243E+10 0.833039E+09 0.295328E+10 0.00 0.00 0.00 0.00 97146646.75 44114248.50
October 0.150991E+10 0.913581E+09 0.306046E+10 0.00 0.00 0.00 0.00 34136345.21 0.172700E+09
November 0.149516E+10 0.937834E+09 0.299314E+10 0.00 0.00 0.00 0.00 2713995.98 0.306141E+09
December 0.145680E+10 0.948426E+09 0.300922E+10 0.00 0.00 0.00 0.00 187435.93 0.329574E+09
                   
Annual Sum or Average 0.181194E+11 0.106130E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.786016E+09 0.202099E+10
Minimum of Months 0.136985E+10 0.795360E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 12456947.41
Maximum of Months 0.163685E+10 0.960530E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.185300E+09 0.342667E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.596966E+09 0.197184E+10 0.00 0.00 0.00 0.00 644770.16 0.230156E+09
February 0.882782E+09 0.535436E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.179764E+09
March 0.105485E+10 0.603834E+09 0.205169E+10 0.00 0.00 0.00 0.00 1838343.93 0.228632E+09
April 0.936002E+09 0.522248E+09 0.190407E+10 0.00 0.00 0.00 0.00 33575010.96 70943105.62
May 0.101394E+10 0.557115E+09 0.201177E+10 0.00 0.00 0.00 0.00 64670988.30 47321892.74
June 0.101113E+10 0.544036E+09 0.197572E+10 0.00 0.00 0.00 0.00 0.123315E+09 10341726.66
July 0.938820E+09 0.516111E+09 0.193969E+10 0.00 0.00 0.00 0.00 0.123003E+09 8045736.85
August 0.105485E+10 0.586256E+09 0.205169E+10 0.00 0.00 0.00 0.00 86562877.07 11795100.63
September 0.936002E+09 0.533831E+09 0.190321E+10 0.00 0.00 0.00 0.00 63440295.09 29906269.65
October 0.973041E+09 0.572478E+09 0.197228E+10 0.00 0.00 0.00 0.00 21705856.83 0.116831E+09
November 0.963541E+09 0.589729E+09 0.192889E+10 0.00 0.00 0.00 0.00 1447707.73 0.204573E+09
December 0.938820E+09 0.592213E+09 0.193926E+10 0.00 0.00 0.00 0.00 87480.51 0.218555E+09
                   
Annual Sum or Average 0.116768E+11 0.675025E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.520291E+09 0.135686E+10
Minimum of Months 0.882782E+09 0.516111E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 8045736.85
Maximum of Months 0.105485E+10 0.603834E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.123315E+09 0.230156E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.911008E+09 0.305983E+10 0.00 0.00 0.00 0.00 869231.93 0.364138E+09
February 0.136988E+10 0.821898E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.275433E+09
March 0.163688E+10 0.933626E+09 0.318374E+10 0.00 0.00 0.00 0.00 2618527.60 0.350783E+09
April 0.145246E+10 0.818346E+09 0.295467E+10 0.00 0.00 0.00 0.00 48359880.10 0.110222E+09
May 0.157341E+10 0.870419E+09 0.312179E+10 0.00 0.00 0.00 0.00 98844299.12 68535617.86
June 0.156904E+10 0.850874E+09 0.306585E+10 0.00 0.00 0.00 0.00 0.186845E+09 14981740.93
July 0.145684E+10 0.806485E+09 0.300994E+10 0.00 0.00 0.00 0.00 0.183757E+09 12261161.78
August 0.163688E+10 0.916923E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.125814E+09 20244179.12
September 0.145246E+10 0.830153E+09 0.295333E+10 0.00 0.00 0.00 0.00 92161225.22 48305067.75
October 0.150994E+10 0.878990E+09 0.306051E+10 0.00 0.00 0.00 0.00 30595612.33 0.185775E+09
November 0.149520E+10 0.901388E+09 0.299318E+10 0.00 0.00 0.00 0.00 1566349.42 0.324795E+09
December 0.145684E+10 0.901245E+09 0.300927E+10 0.00 0.00 0.00 0.00 72036.38 0.345606E+09
                   
Annual Sum or Average 0.181198E+11 0.104414E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.771503E+09 0.212108E+10
Minimum of Months 0.136988E+10 0.806485E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 12261161.78
Maximum of Months 0.163688E+10 0.933626E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.186845E+09 0.364138E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.606536E+09 0.197183E+10 0.00 0.00 0.00 0.00 644141.81 0.249244E+09
February 0.882782E+09 0.541169E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.199997E+09
March 0.105485E+10 0.607010E+09 0.205168E+10 0.00 0.00 0.00 0.00 1729587.86 0.262831E+09
April 0.936002E+09 0.525768E+09 0.190406E+10 0.00 0.00 0.00 0.00 29800906.59 93022675.38
May 0.101394E+10 0.559137E+09 0.201175E+10 0.00 0.00 0.00 0.00 61015756.20 56812928.83
June 0.101113E+10 0.545430E+09 0.197570E+10 0.00 0.00 0.00 0.00 0.115800E+09 15170618.55
July 0.938820E+09 0.517353E+09 0.193968E+10 0.00 0.00 0.00 0.00 0.112697E+09 14547081.11
August 0.105485E+10 0.589490E+09 0.205168E+10 0.00 0.00 0.00 0.00 76980658.20 23658918.97
September 0.936002E+09 0.536910E+09 0.190319E+10 0.00 0.00 0.00 0.00 58351083.86 39113462.48
October 0.973041E+09 0.580099E+09 0.197226E+10 0.00 0.00 0.00 0.00 20092362.04 0.136518E+09
November 0.963541E+09 0.593398E+09 0.192888E+10 0.00 0.00 0.00 0.00 1151206.72 0.237901E+09
December 0.938820E+09 0.598140E+09 0.193924E+10 0.00 0.00 0.00 0.00 58655.89 0.253334E+09
                   
Annual Sum or Average 0.116768E+11 0.680044E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.478321E+09 0.158215E+10
Minimum of Months 0.882782E+09 0.517353E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 14547081.11
Maximum of Months 0.105485E+10 0.607010E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.115800E+09 0.262831E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.956508E+09 0.305979E+10 0.00 0.00 0.00 0.00 5410054.47 0.672383E+09
February 0.136985E+10 0.847726E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.547224E+09
March 0.163685E+10 0.943341E+09 0.318369E+10 0.00 0.00 0.00 0.00 6948606.21 0.713765E+09
April 0.145243E+10 0.814286E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.125004E+09 0.242323E+09
May 0.157338E+10 0.861125E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.230339E+09 0.156967E+09
June 0.156900E+10 0.839374E+09 0.306580E+10 0.00 0.00 0.00 0.00 0.422873E+09 44136345.77
July 0.145680E+10 0.794857E+09 0.300989E+10 0.00 0.00 0.00 0.00 0.417722E+09 38240129.51
August 0.163685E+10 0.910329E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.295870E+09 53138504.30
September 0.145243E+10 0.831871E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.216409E+09 0.104342E+09
October 0.150991E+10 0.909964E+09 0.306046E+10 0.00 0.00 0.00 0.00 83150250.04 0.364805E+09
November 0.149516E+10 0.934337E+09 0.299314E+10 0.00 0.00 0.00 0.00 10415561.78 0.616656E+09
December 0.145680E+10 0.944273E+09 0.300922E+10 0.00 0.00 0.00 0.00 2478921.96 0.652128E+09
                   
Annual Sum or Average 0.181194E+11 0.105880E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.181662E+10 0.420611E+10
Minimum of Months 0.136985E+10 0.794857E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 38240129.51
Maximum of Months 0.163685E+10 0.956508E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.422873E+09 0.713765E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.596262E+09 0.197184E+10 0.00 0.00 0.00 0.00 1259619.60 0.487042E+09
February 0.649041E+09 0.534387E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.389796E+09
March 0.773965E+09 0.603301E+09 0.205169E+10 0.00 0.00 0.00 0.00 3685935.14 0.508661E+09
April 0.688021E+09 0.522101E+09 0.190407E+10 0.00 0.00 0.00 0.00 73928407.39 0.180140E+09
May 0.744847E+09 0.556862E+09 0.201177E+10 0.00 0.00 0.00 0.00 0.144401E+09 0.114453E+09
June 0.742030E+09 0.543673E+09 0.197572E+10 0.00 0.00 0.00 0.00 0.276136E+09 31972344.40
July 0.690839E+09 0.515475E+09 0.193969E+10 0.00 0.00 0.00 0.00 0.270660E+09 28551429.30
August 0.773965E+09 0.585501E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.188236E+09 40627770.93
September 0.688021E+09 0.533458E+09 0.190321E+10 0.00 0.00 0.00 0.00 0.137075E+09 76701046.59
October 0.715730E+09 0.571481E+09 0.197228E+10 0.00 0.00 0.00 0.00 47839251.00 0.265144E+09
November 0.708685E+09 0.588833E+09 0.192889E+10 0.00 0.00 0.00 0.00 3437854.48 0.442037E+09
December 0.690839E+09 0.591086E+09 0.193926E+10 0.00 0.00 0.00 0.00 470429.48 0.464930E+09
                   
Annual Sum or Average 0.858171E+10 0.674242E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.114713E+10 0.303006E+10
Minimum of Months 0.649041E+09 0.515475E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 28551429.30
Maximum of Months 0.773965E+09 0.603301E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.276136E+09 0.508661E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.910792E+09 0.305983E+10 0.00 0.00 0.00 0.00 1569631.18 0.823977E+09
February 0.136988E+10 0.821194E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.615943E+09
March 0.163688E+10 0.932693E+09 0.318374E+10 0.00 0.00 0.00 0.00 5782888.79 0.780960E+09
April 0.145246E+10 0.817506E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.111642E+09 0.262731E+09
May 0.157341E+10 0.869677E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.226544E+09 0.159677E+09
June 0.156904E+10 0.849956E+09 0.306585E+10 0.00 0.00 0.00 0.00 0.427375E+09 42445338.44
July 0.145684E+10 0.805263E+09 0.300994E+10 0.00 0.00 0.00 0.00 0.418007E+09 37602876.71
August 0.163688E+10 0.915522E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.288568E+09 57063058.35
September 0.145246E+10 0.829257E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.204233E+09 0.119162E+09
October 0.150994E+10 0.876999E+09 0.306051E+10 0.00 0.00 0.00 0.00 68528367.57 0.426581E+09
November 0.149520E+10 0.900557E+09 0.299318E+10 0.00 0.00 0.00 0.00 3263231.24 0.726593E+09
December 0.145684E+10 0.900950E+09 0.300927E+10 0.00 0.00 0.00 0.00 132909.06 0.769363E+09
                   
Annual Sum or Average 0.181198E+11 0.104304E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.175565E+10 0.482210E+10
Minimum of Months 0.136988E+10 0.805263E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 37602876.71
Maximum of Months 0.163688E+10 0.932693E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.427375E+09 0.823977E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.604826E+09 0.197183E+10 0.00 0.00 0.00 0.00 1615772.07 0.506852E+09
February 0.882782E+09 0.539646E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.398226E+09
March 0.105485E+10 0.605903E+09 0.205168E+10 0.00 0.00 0.00 0.00 3828303.71 0.525291E+09
April 0.936002E+09 0.525321E+09 0.190406E+10 0.00 0.00 0.00 0.00 70365291.16 0.196107E+09
May 0.101394E+10 0.558634E+09 0.201175E+10 0.00 0.00 0.00 0.00 0.141539E+09 0.124716E+09
June 0.101113E+10 0.545020E+09 0.197570E+10 0.00 0.00 0.00 0.00 0.269753E+09 36915866.33
July 0.938820E+09 0.516639E+09 0.193968E+10 0.00 0.00 0.00 0.00 0.263277E+09 33230991.18
August 0.105485E+10 0.588567E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.182971E+09 45803333.31
September 0.936002E+09 0.536202E+09 0.190319E+10 0.00 0.00 0.00 0.00 0.134268E+09 83409475.34
October 0.973041E+09 0.578763E+09 0.197226E+10 0.00 0.00 0.00 0.00 47935260.23 0.277218E+09
November 0.963541E+09 0.592169E+09 0.192888E+10 0.00 0.00 0.00 0.00 3577248.68 0.461144E+09
December 0.938820E+09 0.596707E+09 0.193924E+10 0.00 0.00 0.00 0.00 221652.92 0.479636E+09
                   
Annual Sum or Average 0.116768E+11 0.678840E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.111935E+10 0.316855E+10
Minimum of Months 0.882782E+09 0.516639E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 33230991.18
Maximum of Months 0.105485E+10 0.605903E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.269753E+09 0.525291E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.956467E+09 0.305979E+10 0.00 0.00 0.00 0.00 9957052.40 0.746035E+09
February 0.136985E+10 0.847675E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 0.608029E+09
March 0.163685E+10 0.943221E+09 0.318369E+10 0.00 0.00 0.00 0.00 7994853.29 0.823553E+09
April 0.145243E+10 0.814276E+09 0.295462E+10 0.00 0.00 0.00 0.00 0.144659E+09 0.295565E+09
May 0.157338E+10 0.861120E+09 0.312174E+10 0.00 0.00 0.00 0.00 0.273980E+09 0.195075E+09
June 0.156900E+10 0.839373E+09 0.306580E+10 0.00 0.00 0.00 0.00 0.512328E+09 57151464.55
July 0.145680E+10 0.794835E+09 0.300989E+10 0.00 0.00 0.00 0.00 0.501251E+09 50061461.47
August 0.163685E+10 0.910303E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.355227E+09 67823398.02
September 0.145243E+10 0.831805E+09 0.295328E+10 0.00 0.00 0.00 0.00 0.258811E+09 0.133753E+09
October 0.150991E+10 0.909899E+09 0.306046E+10 0.00 0.00 0.00 0.00 0.100011E+09 0.424825E+09
November 0.149516E+10 0.934294E+09 0.299314E+10 0.00 0.00 0.00 0.00 15788896.37 0.689121E+09
December 0.145680E+10 0.944194E+09 0.300922E+10 0.00 0.00 0.00 0.00 5711295.45 0.723199E+09
                   
Annual Sum or Average 0.181194E+11 0.105875E+11 0.363654E+11 0.00 0.00 0.00 0.00 0.218572E+10 0.481419E+10
Minimum of Months 0.136985E+10 0.794835E+09 0.277008E+10 0.00 0.00 0.00 0.00 0.00 50061461.47
Maximum of Months 0.163685E+10 0.956467E+09 0.318369E+10 0.00 0.00 0.00 0.00 0.512328E+09 0.823553E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.596252E+09 0.197184E+10 0.00 0.00 0.00 0.00 2307211.48 0.544996E+09
February 0.882782E+09 0.534349E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 0.438547E+09
March 0.105485E+10 0.603278E+09 0.205169E+10 0.00 0.00 0.00 0.00 4671670.87 0.593278E+09
April 0.936002E+09 0.522092E+09 0.190407E+10 0.00 0.00 0.00 0.00 89058823.81 0.221667E+09
May 0.101394E+10 0.556858E+09 0.201177E+10 0.00 0.00 0.00 0.00 0.175055E+09 0.142576E+09
June 0.101113E+10 0.543663E+09 0.197572E+10 0.00 0.00 0.00 0.00 0.337135E+09 41254943.63
July 0.938820E+09 0.515425E+09 0.193969E+10 0.00 0.00 0.00 0.00 0.328151E+09 37094056.31
August 0.105485E+10 0.585491E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.228645E+09 51716579.13
September 0.936002E+09 0.533443E+09 0.190321E+10 0.00 0.00 0.00 0.00 0.166454E+09 97800552.88
October 0.973041E+09 0.571445E+09 0.197228E+10 0.00 0.00 0.00 0.00 58243584.31 0.312784E+09
November 0.963541E+09 0.588810E+09 0.192889E+10 0.00 0.00 0.00 0.00 5257024.78 0.498433E+09
December 0.938820E+09 0.591073E+09 0.193926E+10 0.00 0.00 0.00 0.00 1261864.31 0.516532E+09
                   
Annual Sum or Average 0.116768E+11 0.674218E+10 0.234352E+11 0.00 0.00 0.00 0.00 0.139624E+10 0.349668E+10
Minimum of Months 0.882782E+09 0.515425E+09 0.178515E+10 0.00 0.00 0.00 0.00 0.00 37094056.31
Maximum of Months 0.105485E+10 0.603278E+09 0.205169E+10 0.00 0.00 0.00 0.00 0.337135E+09 0.593278E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.910758E+09 0.305983E+10 0.00 0.00 0.00 0.00 2293830.23 0.945452E+09
February 0.136988E+10 0.821173E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 0.701012E+09
March 0.163688E+10 0.932663E+09 0.318374E+10 0.00 0.00 0.00 0.00 6738531.26 0.916371E+09
April 0.145246E+10 0.817468E+09 0.295467E+10 0.00 0.00 0.00 0.00 0.132651E+09 0.322067E+09
May 0.157341E+10 0.869664E+09 0.312179E+10 0.00 0.00 0.00 0.00 0.270817E+09 0.198196E+09
June 0.156904E+10 0.849944E+09 0.306585E+10 0.00 0.00 0.00 0.00 0.516531E+09 54991500.72
July 0.145684E+10 0.805239E+09 0.300994E+10 0.00 0.00 0.00 0.00 0.501611E+09 49233601.10
August 0.163688E+10 0.915486E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.347668E+09 72891462.50
September 0.145246E+10 0.829239E+09 0.295333E+10 0.00 0.00 0.00 0.00 0.246285E+09 0.152196E+09
October 0.150994E+10 0.876992E+09 0.306051E+10 0.00 0.00 0.00 0.00 82976335.26 0.507678E+09
November 0.149520E+10 0.900548E+09 0.299318E+10 0.00 0.00 0.00 0.00 4216364.22 0.838811E+09
December 0.145684E+10 0.900943E+09 0.300927E+10 0.00 0.00 0.00 0.00 192424.03 0.879606E+09
                   
Annual Sum or Average 0.181198E+11 0.104301E+11 0.363660E+11 0.00 0.00 0.00 0.00 0.211198E+10 0.563850E+10
Minimum of Months 0.136988E+10 0.805239E+09 0.277013E+10 0.00 0.00 0.00 0.00 0.00 49233601.10
Maximum of Months 0.163688E+10 0.932663E+09 0.318374E+10 0.00 0.00 0.00 0.00 0.516531E+09 0.945452E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.604762E+09 0.197183E+10 0.00 0.00 0.00 0.00 2471248.27 0.577954E+09
February 0.882782E+09 0.539622E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 0.455224E+09
March 0.105485E+10 0.605886E+09 0.205168E+10 0.00 0.00 0.00 0.00 4481042.87 0.618681E+09
April 0.936002E+09 0.525315E+09 0.190406E+10 0.00 0.00 0.00 0.00 84762079.29 0.240044E+09
May 0.101394E+10 0.558611E+09 0.201175E+10 0.00 0.00 0.00 0.00 0.171332E+09 0.154694E+09
June 0.101113E+10 0.545021E+09 0.197570E+10 0.00 0.00 0.00 0.00 0.328952E+09 46934425.17
July 0.938820E+09 0.516636E+09 0.193968E+10 0.00 0.00 0.00 0.00 0.319827E+09 42423215.77
August 0.105485E+10 0.588548E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.222129E+09 57848779.16
September 0.936002E+09 0.536170E+09 0.190319E+10 0.00 0.00 0.00 0.00 0.162424E+09 0.105805E+09
October 0.973041E+09 0.578752E+09 0.197226E+10 0.00 0.00 0.00 0.00 57905018.65 0.329383E+09
November 0.963541E+09 0.592155E+09 0.192888E+10 0.00 0.00 0.00 0.00 5038596.68 0.531119E+09
December 0.938820E+09 0.596642E+09 0.193924E+10 0.00 0.00 0.00 0.00 531066.20 0.546487E+09
                   
Annual Sum or Average 0.116768E+11 0.678812E+10 0.234351E+11 0.00 0.00 0.00 0.00 0.135985E+10 0.370660E+10
Minimum of Months 0.882782E+09 0.516636E+09 0.178514E+10 0.00 0.00 0.00 0.00 0.00 42423215.77
Maximum of Months 0.105485E+10 0.605886E+09 0.205168E+10 0.00 0.00 0.00 0.00 0.328952E+09 0.618681E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.302573E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.274456E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.326130E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.291301E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.314351E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.312831E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.292821E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.326130E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.291301E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.302573E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.299026E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.292821E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.362631E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.274456E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.326130E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.397259E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.360343E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.428189E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.382459E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.412724E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.410728E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.384455E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.428189E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.382459E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.397259E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.392603E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.384455E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.476112E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.360343E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.428189E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1181345.54 0.752196E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.585185E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3985094.40 0.746166E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 93800948.58 0.242776E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.188686E+09 0.149353E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.355442E+09 38218355.74
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.353362E+09 32690949.75
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.236777E+09 51853127.23
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.178637E+09 95252727.31
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59856086.62 0.384032E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3127719.98 0.675082E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79701.86 0.725147E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.147493E+10 0.447795E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32690949.75
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.355442E+09 0.752196E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2378891.79 0.126363E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.100089E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7935774.80 0.128440E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.177477E+09 0.427057E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.343436E+09 0.264225E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.639863E+09 70988099.56
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.644011E+09 59616961.43
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.441015E+09 90987032.54
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.320629E+09 0.169438E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.112034E+09 0.664036E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8351035.37 0.114637E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 883099.56 0.122017E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.269801E+10 0.766180E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59616961.43
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.644011E+09 0.128440E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2037516.40 0.124245E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.100786E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4881148.38 0.134044E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.154417E+09 0.461046E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.328819E+09 0.273697E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.681481E+09 75817733.69
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.653615E+09 67992835.77
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.461325E+09 98392306.77
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.326451E+09 0.193186E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.109607E+09 0.687498E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7591022.91 0.113928E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1003496.19 0.118093E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.273123E+10 0.776860E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67992835.77
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.681481E+09 0.134044E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 14744.03 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 14744.03 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 14744.03 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 14744.03 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 14744.03 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 14744.03 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 14744.03 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 14744.03 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 14744.03 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 14744.03 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 14744.03 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 14744.03 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   14744.03   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   14744.03   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.63 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.63 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.63 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.63 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.63 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.63 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.63 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.63 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.63 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.63 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.63 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.63 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.63   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.63   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13241.18 02-JAN-08:09 17206.56 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13241.18 01-FEB-08:09 17206.56 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13241.18 01-MAR-08:09 17206.56 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13241.18 03-APR-07:10 17206.56 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13241.18 01-MAY-07:10 17206.56 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13241.18 01-JUN-07:10 17206.56 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13241.18 03-JUL-07:10 17206.56 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13241.18 01-AUG-07:10 17206.56 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13241.18 01-SEP-07:10 17206.56 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13241.18 02-OCT-07:10 17206.56 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13241.18 01-NOV-07:10 17206.56 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13241.18 01-DEC-08:09 17206.56 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13241.18   17206.56   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1483.93 20-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 19.90 31-JAN-14:00 726.58 01-JAN-00:55
February 2010.79 01-FEB-10:09 1384.14 03-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 764.10 02-FEB-23:00
March 2010.79 01-MAR-10:09 1291.50 21-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 53.63 18-MAR-17:10 663.19 28-MAR-04:00
April 2010.79 03-APR-09:09 888.77 04-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 390.52 30-APR-15:43 323.97 21-APR-04:53
May 2010.79 01-MAY-09:09 852.41 26-MAY-08:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 363.59 20-MAY-17:30 252.75 23-MAY-04:53
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 571.78 17-JUN-17:10 125.86 13-JUN-04:10
July 2010.79 03-JUL-09:09 875.04 13-JUL-15:00 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 722.15 22-JUL-18:00 183.09 26-JUL-24:00
August 2010.79 01-AUG-09:09 1305.75 04-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 649.76 13-AUG-16:00 306.62 05-AUG-17:40
September 2010.79 01-SEP-09:09 1137.97 29-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 462.08 17-SEP-12:38 232.91 03-SEP-05:00
October 2010.79 02-OCT-09:09 1424.65 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 292.67 01-OCT-14:40 648.25 22-OCT-14:00
November 2010.79 01-NOV-09:09 1662.56 28-NOV-16:30 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 94.26 19-NOV-15:00 660.24 29-NOV-02:00
December 2010.79 01-DEC-10:09 1662.56 01-DEC-16:30 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 16.76 25-DEC-16:00 552.27 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 0.00   125.86  
Maximum of Months 2010.79   1662.56   2160.55   0.00 0.00 0.00 0.00 722.15   764.10  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 947.23 20-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 13.27 31-JAN-14:00 490.53 01-JAN-00:55
February 1295.83 01-FEB-10:09 857.16 10-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 508.96 02-FEB-23:00
March 1295.83 01-MAR-10:09 589.31 08-MAR-16:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 32.96 18-MAR-17:10 436.59 28-MAR-04:00
April 1295.83 03-APR-09:09 509.78 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 264.03 30-APR-15:43 311.31 16-APR-09:00
May 1295.83 01-MAY-09:09 509.78 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 233.82 20-MAY-17:30 168.23 23-MAY-04:53
June 1295.83 01-JUN-09:09 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 383.13 17-JUN-17:10 92.65 11-JUN-06:50
July 1295.83 03-JUL-09:09 572.03 13-JUL-15:00 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 490.20 22-JUL-18:00 117.54 26-JUL-24:00
August 1295.83 01-AUG-09:09 816.23 04-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 433.56 13-AUG-15:55 197.65 05-AUG-17:40
September 1295.83 01-SEP-09:09 568.78 29-SEP-14:30 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 309.26 17-SEP-12:38 150.42 03-SEP-05:00
October 1295.83 02-OCT-09:09 685.59 31-OCT-15:00 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 193.61 01-OCT-14:28 452.67 22-OCT-14:00
November 1295.83 01-NOV-09:09 1071.42 28-NOV-16:30 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 46.28 19-NOV-15:00 432.09 29-NOV-02:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:30 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 6.90 25-DEC-16:00 361.93 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   509.78   1392.34   0.00 0.00 0.00 0.00 0.00   92.65  
Maximum of Months 1295.83   1071.42   1392.34   0.00 0.00 0.00 0.00 490.20   508.96  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1447.58 20-JAN-16:00 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 19.86 31-JAN-15:00 733.68 01-JAN-00:55
February 2010.83 01-FEB-10:09 1355.67 10-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 812.85 02-FEB-23:00
March 2010.83 01-MAR-10:09 1237.32 21-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 42.11 15-MAR-13:00 660.80 28-MAR-04:00
April 2010.83 03-APR-09:09 896.29 04-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 372.31 30-APR-15:43 327.88 16-APR-09:00
May 2010.83 01-MAY-09:09 852.41 26-MAY-08:30 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 358.50 20-MAY-17:30 250.52 01-MAY-05:00
June 2010.83 01-JUN-09:09 839.02 27-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 572.13 17-JUN-17:10 124.78 13-JUN-04:10
July 2010.83 03-JUL-09:09 880.24 27-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 734.94 22-JUL-18:00 183.04 26-JUL-24:00
August 2010.83 01-AUG-09:09 1312.97 04-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 649.75 13-AUG-16:00 317.39 05-AUG-17:40
September 2010.83 01-SEP-09:09 906.35 19-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 462.46 17-SEP-12:35 239.09 03-SEP-05:00
October 2010.83 02-OCT-09:09 1236.87 27-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 288.55 01-OCT-14:25 722.92 22-OCT-14:00
November 2010.83 01-NOV-09:09 1662.60 28-NOV-16:30 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 31.30 01-NOV-16:00 679.40 29-NOV-02:00
December 2010.83 01-DEC-10:09 1662.60 01-DEC-16:30 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 7.78 21-DEC-15:00 560.59 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   839.02   2160.58   0.00 0.00 0.00 0.00 0.00   124.78  
Maximum of Months 2010.83   1662.60   2160.58   0.00 0.00 0.00 0.00 734.94   812.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 968.51 20-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 13.27 31-JAN-14:00 519.37 01-JAN-00:55
February 1295.83 01-FEB-10:09 897.70 10-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 580.24 02-FEB-23:00
March 1295.83 01-MAR-10:09 905.19 21-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 28.07 15-MAR-13:00 491.61 28-MAR-04:00
April 1295.83 03-APR-09:09 702.14 04-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 244.70 30-APR-15:49 276.60 16-APR-09:00
May 1295.83 01-MAY-09:09 569.32 26-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 227.11 20-MAY-17:45 187.72 01-MAY-05:00
June 1295.83 01-JUN-09:09 543.10 27-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 381.69 17-JUN-17:10 108.19 13-JUN-04:10
July 1295.83 03-JUL-09:09 570.33 24-JUL-08:20 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 478.98 22-JUL-18:00 171.52 26-JUL-23:50
August 1295.83 01-AUG-09:09 856.93 04-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 432.74 13-AUG-16:00 270.73 05-AUG-17:40
September 1295.83 01-SEP-09:09 805.87 29-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 312.22 17-SEP-12:35 185.00 03-SEP-05:00
October 1295.83 02-OCT-09:09 932.09 27-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 191.15 01-OCT-14:25 502.58 22-OCT-14:00
November 1295.83 01-NOV-09:09 1071.42 28-NOV-16:30 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 21.69 01-NOV-16:00 499.09 29-NOV-02:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:30 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 5.60 21-DEC-15:00 408.38 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   543.10   1392.33   0.00 0.00 0.00 0.00 0.00   108.19  
Maximum of Months 1295.83   1071.42   1392.33   0.00 0.00 0.00 0.00 478.98   580.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1480.95 20-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 132.45 16-JAN-11:53 1240.26 01-JAN-00:55
February 2010.79 01-FEB-10:09 1379.52 10-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1559.56 02-FEB-23:00
March 2010.79 01-MAR-10:09 1286.17 21-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 149.12 18-MAR-17:02 1364.08 28-MAR-04:00
April 2010.79 03-APR-09:09 879.57 04-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 891.92 30-APR-15:53 710.26 21-APR-05:00
May 2010.79 01-MAY-09:09 842.61 26-MAY-08:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 838.05 20-MAY-17:01 585.53 23-MAY-05:00
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 1328.27 17-JUN-17:10 311.19 13-JUN-03:55
July 2010.79 03-JUL-09:09 866.52 13-JUL-15:00 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 1668.69 22-JUL-18:00 473.10 26-JUL-24:00
August 2010.79 01-AUG-09:09 1301.67 04-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 1509.14 13-AUG-16:00 698.13 05-AUG-17:45
September 2010.79 01-SEP-09:09 1130.38 29-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 1068.09 17-SEP-12:35 502.35 03-SEP-05:00
October 2010.79 02-OCT-09:09 1420.76 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 690.40 01-OCT-14:56 1313.19 22-OCT-13:55
November 2010.79 01-NOV-09:09 1662.56 28-NOV-16:30 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 364.75 19-NOV-15:00 1325.60 29-NOV-02:00
December 2010.79 01-DEC-10:09 1662.56 01-DEC-16:30 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 143.16 25-DEC-16:00 1141.64 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 0.00   311.19  
Maximum of Months 2010.79   1662.56   2160.55   0.00 0.00 0.00 0.00 1668.69   1559.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 944.01 20-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 30.27 31-JAN-14:00 872.90 01-JAN-00:55
February 1239.33 01-FEB-08:09 851.98 10-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1092.12 02-FEB-23:00
March 1239.33 01-MAR-08:09 585.39 08-MAR-16:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 73.04 18-MAR-17:02 931.45 28-MAR-04:00
April 1239.33 03-APR-07:10 509.78 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 611.81 30-APR-15:53 728.22 16-APR-08:50
May 1239.33 01-MAY-07:10 509.78 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 520.26 20-MAY-17:01 397.78 23-MAY-05:00
June 1239.33 01-JUN-07:10 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 889.26 17-JUN-17:10 232.89 25-JUN-06:00
July 1239.33 03-JUL-07:10 567.16 13-JUL-15:00 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 1123.71 22-JUL-17:43 327.36 26-JUL-24:00
August 1239.33 01-AUG-07:10 810.47 04-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 1006.09 13-AUG-16:00 488.30 05-AUG-17:45
September 1239.33 01-SEP-07:10 563.69 29-SEP-14:30 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 718.68 17-SEP-12:35 342.60 03-SEP-05:00
October 1239.33 02-OCT-07:10 671.44 31-OCT-15:00 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 472.79 01-OCT-14:56 1008.13 22-OCT-13:55
November 1239.33 01-NOV-07:10 1071.42 28-NOV-16:30 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 135.76 19-NOV-15:00 909.29 29-NOV-02:00
December 1239.33 01-DEC-08:09 1071.42 01-DEC-16:30 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 57.11 25-DEC-16:00 776.70 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   509.78   1392.34   0.00 0.00 0.00 0.00 0.00   232.89  
Maximum of Months 1239.33   1071.42   1392.34   0.00 0.00 0.00 0.00 1123.71   1092.12  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1445.32 20-JAN-16:00 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 42.83 31-JAN-15:10 1552.74 01-JAN-00:55
February 2010.83 01-FEB-10:09 1352.22 10-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1784.06 02-FEB-23:00
March 2010.83 01-MAR-10:09 1231.58 21-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 95.39 15-MAR-13:00 1437.20 28-MAR-04:00
April 2010.83 03-APR-09:09 887.78 04-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 865.56 30-APR-15:53 726.07 21-APR-05:00
May 2010.83 01-MAY-09:09 842.61 26-MAY-08:30 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 820.03 20-MAY-17:01 587.47 23-MAY-05:00
June 2010.83 01-JUN-09:09 791.06 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 1329.10 17-JUN-17:10 306.42 13-JUN-03:55
July 2010.83 03-JUL-09:09 870.46 27-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 1693.30 22-JUL-18:00 471.48 26-JUL-24:00
August 2010.83 01-AUG-09:09 1308.95 04-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 1509.13 13-AUG-16:00 732.72 05-AUG-17:45
September 2010.83 01-SEP-09:09 899.61 29-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 1049.35 17-SEP-12:35 524.05 03-SEP-05:00
October 2010.83 02-OCT-09:09 1182.61 27-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 655.04 01-OCT-14:40 1634.27 22-OCT-13:55
November 2010.83 01-NOV-09:09 1662.60 28-NOV-16:30 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 69.11 01-NOV-16:10 1458.46 29-NOV-02:00
December 2010.83 01-DEC-10:09 1662.60 01-DEC-16:30 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 15.32 21-DEC-15:00 1235.37 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   791.06   2160.58   0.00 0.00 0.00 0.00 0.00   306.42  
Maximum of Months 2010.83   1662.60   2160.58   0.00 0.00 0.00 0.00 1693.30   1784.06  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 966.14 20-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 44.50 16-JAN-11:53 962.34 01-JAN-00:55
February 1295.83 01-FEB-10:09 893.17 10-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1154.56 02-FEB-23:00
March 1295.83 01-MAR-10:09 900.60 21-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 63.59 15-MAR-13:00 973.95 28-MAR-04:00
April 1295.83 03-APR-09:09 693.99 04-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 571.72 30-APR-15:13 511.90 26-APR-21:20
May 1295.83 01-MAY-09:09 564.31 26-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 515.77 20-MAY-17:45 421.67 23-MAY-05:00
June 1295.83 01-JUN-09:09 509.78 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 889.23 17-JUN-17:10 238.33 13-JUN-03:55
July 1295.83 03-JUL-09:09 565.16 24-JUL-08:20 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 1112.46 22-JUL-18:00 375.59 26-JUL-24:00
August 1295.83 01-AUG-09:09 851.30 04-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 1006.06 13-AUG-16:00 511.26 05-AUG-17:45
September 1295.83 01-SEP-09:09 798.69 29-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 718.33 17-SEP-12:35 353.32 03-SEP-05:00
October 1295.83 02-OCT-09:09 929.22 27-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 468.51 01-OCT-14:54 941.10 22-OCT-14:00
November 1295.83 01-NOV-09:09 1071.42 28-NOV-16:30 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 147.34 19-NOV-12:32 933.44 29-NOV-02:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:30 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 25.22 25-DEC-13:41 796.08 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   509.78   1392.33   0.00 0.00 0.00 0.00 0.00   238.33  
Maximum of Months 1295.83   1071.42   1392.33   0.00 0.00 0.00 0.00 1112.46   1154.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1480.71 20-JAN-08:09 2160.55 02-JAN-08:09 0.00 0.00 0.00 0.00 289.05 16-JAN-12:00 1287.75 01-JAN-01:07
February 2010.79 01-FEB-10:09 1378.94 10-FEB-08:09 2160.55 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1772.88 02-FEB-23:00
March 2010.79 01-MAR-10:09 1285.55 21-MAR-07:10 2160.55 01-MAR-08:09 0.00 0.00 0.00 0.00 164.66 18-MAR-17:02 1539.52 28-MAR-04:00
April 2010.79 03-APR-09:09 879.40 04-APR-07:10 2160.55 03-APR-07:10 0.00 0.00 0.00 0.00 1084.66 30-APR-15:25 841.74 26-APR-21:10
May 2010.79 01-MAY-09:09 842.22 26-MAY-08:30 2160.55 01-MAY-07:10 0.00 0.00 0.00 0.00 967.09 20-MAY-17:01 695.47 23-MAY-05:00
June 2010.79 01-JUN-09:09 791.05 01-JUN-07:10 2160.55 01-JUN-07:10 0.00 0.00 0.00 0.00 1641.17 17-JUN-17:10 383.63 13-JUN-03:55
July 2010.79 03-JUL-09:09 866.18 13-JUL-15:00 2160.55 03-JUL-07:10 0.00 0.00 0.00 0.00 2051.60 22-JUL-18:00 604.67 26-JUL-24:00
August 2010.79 01-AUG-09:09 1300.93 04-AUG-07:10 2160.55 01-AUG-07:10 0.00 0.00 0.00 0.00 1855.35 13-AUG-16:00 891.31 05-AUG-17:45
September 2010.79 01-SEP-09:09 1129.45 29-SEP-07:10 2160.55 01-SEP-07:10 0.00 0.00 0.00 0.00 1311.28 17-SEP-12:35 637.73 03-SEP-05:00
October 2010.79 02-OCT-09:09 1420.64 31-OCT-07:10 2160.55 02-OCT-07:10 0.00 0.00 0.00 0.00 825.58 01-OCT-14:25 1577.72 22-OCT-13:55
November 2010.79 01-NOV-09:09 1662.56 28-NOV-16:30 2160.55 01-NOV-07:10 0.00 0.00 0.00 0.00 546.01 19-NOV-12:52 1501.30 29-NOV-02:00
December 2010.79 01-DEC-10:09 1662.56 01-DEC-16:30 2160.55 01-DEC-08:09 0.00 0.00 0.00 0.00 224.02 25-DEC-15:52 1350.92 07-DEC-05:06
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   791.05   2160.55   0.00 0.00 0.00 0.00 0.00   383.63  
Maximum of Months 2010.79   1662.56   2160.55   0.00 0.00 0.00 0.00 2051.60   1772.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 943.75 20-JAN-16:00 1392.34 02-JAN-08:09 0.00 0.00 0.00 0.00 46.42 16-JAN-14:00 863.27 01-JAN-00:55
February 1295.83 01-FEB-10:09 851.56 10-FEB-08:09 1392.34 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1247.54 02-FEB-23:00
March 1295.83 01-MAR-10:09 585.26 08-MAR-16:00 1392.34 01-MAR-08:09 0.00 0.00 0.00 0.00 76.26 18-MAR-17:02 1059.22 28-MAR-04:00
April 1295.83 03-APR-09:09 509.78 03-APR-07:10 1392.34 03-APR-07:10 0.00 0.00 0.00 0.00 735.41 30-APR-15:23 850.83 16-APR-08:30
May 1295.83 01-MAY-09:09 509.78 01-MAY-07:10 1392.34 01-MAY-07:10 0.00 0.00 0.00 0.00 636.88 20-MAY-17:07 472.79 23-MAY-05:00
June 1295.83 01-JUN-09:09 509.78 01-JUN-07:10 1392.34 01-JUN-07:10 0.00 0.00 0.00 0.00 1091.26 17-JUN-17:10 288.95 25-JUN-06:00
July 1295.83 03-JUL-09:09 566.96 13-JUL-15:00 1392.34 03-JUL-07:10 0.00 0.00 0.00 0.00 1383.93 22-JUL-17:43 416.55 26-JUL-24:00
August 1295.83 01-AUG-09:09 809.96 04-AUG-07:10 1392.34 01-AUG-07:10 0.00 0.00 0.00 0.00 1236.88 13-AUG-16:00 619.21 05-AUG-17:45
September 1295.83 01-SEP-09:09 563.52 29-SEP-14:30 1392.34 01-SEP-07:10 0.00 0.00 0.00 0.00 885.81 17-SEP-12:35 432.71 03-SEP-05:00
October 1295.83 02-OCT-09:09 671.36 31-OCT-15:00 1392.34 02-OCT-07:10 0.00 0.00 0.00 0.00 550.65 01-OCT-14:25 1219.04 22-OCT-13:55
November 1295.83 01-NOV-09:09 1071.42 28-NOV-16:30 1392.34 01-NOV-07:10 0.00 0.00 0.00 0.00 203.55 19-NOV-15:00 1037.67 29-NOV-02:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:30 1392.34 01-DEC-08:09 0.00 0.00 0.00 0.00 98.34 25-DEC-16:00 909.82 07-DEC-05:04
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   509.78   1392.34   0.00 0.00 0.00 0.00 0.00   288.95  
Maximum of Months 1295.83   1071.42   1392.34   0.00 0.00 0.00 0.00 1383.93   1247.54  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1444.89 20-JAN-16:00 2160.58 02-JAN-08:09 0.00 0.00 0.00 0.00 54.78 31-JAN-14:10 1618.74 01-JAN-00:55
February 2010.83 01-FEB-10:09 1351.59 10-FEB-08:09 2160.58 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2067.96 02-FEB-23:00
March 2010.83 01-MAR-10:09 1230.90 21-MAR-07:10 2160.58 01-MAR-08:09 0.00 0.00 0.00 0.00 114.26 15-MAR-13:00 1641.81 28-MAR-04:00
April 2010.83 03-APR-09:09 887.62 04-APR-07:10 2160.58 03-APR-07:10 0.00 0.00 0.00 0.00 1031.79 30-APR-14:55 879.48 26-APR-21:10
May 2010.83 01-MAY-09:09 842.22 26-MAY-08:30 2160.58 01-MAY-07:10 0.00 0.00 0.00 0.00 950.64 20-MAY-17:47 697.67 23-MAY-05:00
June 2010.83 01-JUN-09:09 791.06 01-JUN-07:10 2160.58 01-JUN-07:10 0.00 0.00 0.00 0.00 1641.22 17-JUN-17:10 377.55 13-JUN-03:55
July 2010.83 03-JUL-09:09 870.31 27-JUL-07:10 2160.58 03-JUL-07:10 0.00 0.00 0.00 0.00 2057.23 22-JUL-17:43 602.59 26-JUL-24:00
August 2010.83 01-AUG-09:09 1308.21 04-AUG-07:10 2160.58 01-AUG-07:10 0.00 0.00 0.00 0.00 1855.27 13-AUG-16:00 934.76 05-AUG-17:45
September 2010.83 01-SEP-09:09 899.40 29-SEP-07:10 2160.58 01-SEP-07:10 0.00 0.00 0.00 0.00 1280.94 17-SEP-12:35 664.43 03-SEP-05:00
October 2010.83 02-OCT-09:09 1182.19 27-OCT-07:10 2160.58 02-OCT-07:10 0.00 0.00 0.00 0.00 815.60 01-OCT-14:25 1979.74 22-OCT-13:55
November 2010.83 01-NOV-09:09 1662.60 28-NOV-16:30 2160.58 01-NOV-07:10 0.00 0.00 0.00 0.00 87.79 01-NOV-16:00 1681.86 29-NOV-02:00
December 2010.83 01-DEC-10:09 1662.60 01-DEC-16:30 2160.58 01-DEC-08:09 0.00 0.00 0.00 0.00 21.76 21-DEC-15:00 1404.36 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   791.06   2160.58   0.00 0.00 0.00 0.00 0.00   377.55  
Maximum of Months 2010.83   1662.60   2160.58   0.00 0.00 0.00 0.00 2057.23   2067.96  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 966.01 20-JAN-08:09 1392.33 02-JAN-08:09 0.00 0.00 0.00 0.00 118.34 16-JAN-12:00 1010.29 01-JAN-00:55
February 1295.83 01-FEB-10:09 892.81 10-FEB-08:09 1392.33 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1334.09 02-FEB-23:00
March 1295.83 01-MAR-10:09 900.31 21-MAR-07:10 1392.33 01-MAR-08:09 0.00 0.00 0.00 0.00 76.17 15-MAR-13:00 1124.48 28-MAR-04:00
April 1295.83 03-APR-09:09 693.91 04-APR-07:10 1392.33 03-APR-07:10 0.00 0.00 0.00 0.00 687.86 30-APR-15:00 633.84 26-APR-21:10
May 1295.83 01-MAY-09:09 564.12 26-MAY-07:10 1392.33 01-MAY-07:10 0.00 0.00 0.00 0.00 628.18 20-MAY-17:45 504.85 23-MAY-05:00
June 1295.83 01-JUN-09:09 509.78 01-JUN-07:10 1392.33 01-JUN-07:10 0.00 0.00 0.00 0.00 1091.14 17-JUN-17:10 293.32 13-JUN-03:55
July 1295.83 03-JUL-09:09 565.00 24-JUL-08:20 1392.33 03-JUL-07:10 0.00 0.00 0.00 0.00 1367.74 22-JUL-18:00 478.34 26-JUL-24:00
August 1295.83 01-AUG-09:09 850.85 04-AUG-07:10 1392.33 01-AUG-07:10 0.00 0.00 0.00 0.00 1236.02 13-AUG-16:00 649.79 05-AUG-17:45
September 1295.83 01-SEP-09:09 798.21 29-SEP-07:10 1392.33 01-SEP-07:10 0.00 0.00 0.00 0.00 885.13 17-SEP-12:35 445.19 03-SEP-05:00
October 1295.83 02-OCT-09:09 929.08 27-OCT-07:10 1392.33 02-OCT-07:10 0.00 0.00 0.00 0.00 545.65 01-OCT-14:25 1138.60 22-OCT-14:00
November 1295.83 01-NOV-09:09 1071.42 28-NOV-16:30 1392.33 01-NOV-07:10 0.00 0.00 0.00 0.00 235.19 19-NOV-12:13 1075.07 29-NOV-02:00
December 1295.83 01-DEC-10:09 1071.42 01-DEC-16:30 1392.33 01-DEC-08:09 0.00 0.00 0.00 0.00 58.63 25-DEC-13:52 909.80 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   509.78   1392.33   0.00 0.00 0.00 0.00 0.00   293.32  
Maximum of Months 1295.83   1071.42   1392.33   0.00 0.00 0.00 0.00 1367.74   1334.09  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 316.63 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 316.63 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 316.63 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 316.63 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 316.63 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 316.63 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 316.63 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 316.63 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 316.63 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 316.63 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 316.63 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 316.63 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   316.63   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   316.63   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 4157.19 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 4157.19 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 4157.19 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 4157.19 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 4157.19 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 4157.19 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 4157.19 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 4157.19 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 4157.19 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 4157.19 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 4157.19 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 4157.19 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   4157.19   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   4157.19   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.48 31-JAN-14:00 1636.90 01-JAN-00:55
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1700.72 02-FEB-23:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 80.97 18-MAR-17:02 1453.10 28-MAR-04:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 782.93 30-APR-14:51 722.13 21-APR-04:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 756.97 20-MAY-17:01 571.11 23-MAY-04:53
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1208.54 17-JUN-17:03 269.76 13-JUN-04:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1489.01 22-JUL-18:00 414.12 26-JUL-24:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1269.96 13-AUG-16:00 637.19 05-AUG-17:45
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 960.12 17-SEP-11:53 472.22 03-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 595.73 01-OCT-14:50 1281.39 22-OCT-14:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.00 19-NOV-14:52 1448.99 29-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.99 21-DEC-15:00 1218.64 07-DEC-02:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   269.76  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1489.01   1700.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61.87 31-JAN-14:00 2420.24 01-JAN-00:55
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2964.63 02-FEB-23:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 171.59 18-MAR-17:02 2489.17 28-MAR-04:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1470.74 30-APR-15:00 1277.63 21-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1363.10 20-MAY-17:01 1021.38 23-MAY-05:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2187.69 17-JUN-17:03 497.85 13-JUN-03:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2692.06 22-JUL-18:00 752.98 26-JUL-24:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2397.48 13-AUG-16:00 1126.56 05-AUG-17:50
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1734.00 17-SEP-12:00 827.03 03-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1082.00 01-OCT-14:40 2175.29 22-OCT-13:55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 340.37 19-NOV-14:52 2458.19 29-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86.14 25-DEC-16:00 2109.84 07-DEC-02:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   497.85  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2692.06   2964.63  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 123.13 16-JAN-11:53 2105.13 01-JAN-01:20
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2952.58 02-FEB-23:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 108.89 15-MAR-13:00 2467.17 28-MAR-04:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1193.02 30-APR-15:50 1291.82 26-APR-21:02
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1307.93 20-MAY-17:01 1062.99 23-MAY-04:53
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2344.34 17-JUN-17:03 526.99 13-JUN-03:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2756.65 22-JUL-18:00 915.85 26-JUL-24:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2244.05 13-AUG-16:00 1418.41 05-AUG-17:45
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1730.84 17-SEP-12:20 994.60 03-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1027.14 01-OCT-14:12 2786.82 22-OCT-13:55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 327.00 19-NOV-15:00 2453.23 29-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 111.27 25-DEC-13:52 2046.26 07-DEC-02:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   526.99  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2756.65   2952.58  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 102750.74 02-JAN-05:11 0.00 5983.50 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
February 101989.06 21-FEB-05:12 0.00 2991.75 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
March 103219.98 20-MAR-04:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
April 102337.13 24-APR-04:21 0.00 4188.45 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
May 103380.18 08-MAY-04:11 0.00 4188.45 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
June 103419.32 19-JUN-04:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
July 105301.79 03-JUL-04:11 0.00 4188.45 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
August 103144.26 27-AUG-16:16 8976.13 8190.52 134575.44 0.00 0.00 0.00 0.00 0.00 0.00
September 100241.87 28-SEP-04:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
October 103627.22 23-OCT-04:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
November 102362.40 06-NOV-05:12 0.00 3590.10 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
December 102973.40 11-DEC-05:11 0.00 4786.80 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 100241.87   0.00 2991.75 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 105301.79   8976.13 8190.52 134575.44 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 86351.38 17-JAN-05:12 0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
February 86575.69 21-FEB-05:12 0.00 2686.80 29688.23 0.00 0.00 0.00 0.00 0.00 0.00
March 87676.09 20-MAR-04:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
April 84404.17 28-APR-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
May 90694.21 30-MAY-04:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
June 88323.36 01-JUN-04:13 0.00 3761.52 41563.52 0.00 0.00 0.00 0.00 0.00 0.00
July 80507.23 29-JUL-04:12 0.00 3224.16 26719.40 0.00 0.00 0.00 0.00 0.00 0.00
August 83930.17 21-AUG-05:05 9673.43 3224.16 45884.34 0.00 0.00 0.00 0.00 0.00 0.00
September 88309.23 29-SEP-04:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
October 90651.56 10-OCT-04:13 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
November 88358.68 06-NOV-05:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
December 89460.58 04-DEC-05:12 0.00 3224.16 35625.87 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 80507.23   0.00 2686.80 26719.40 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 90694.21   9673.43 3761.52 45884.34 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 74714.05 27-JAN-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
February 74311.25 01-FEB-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
March 75592.85 20-MAR-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
April 77300.54 18-APR-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
May 77558.79 31-MAY-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
June 82977.06 01-JUN-04:13 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
July 82680.20 03-JUL-04:13 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
August 76487.84 05-AUG-04:12 0.00 3224.16 26719.30 0.00 0.00 0.00 0.00 0.00 0.00
September 78389.02 26-SEP-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
October 78264.18 11-OCT-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
November 78525.92 13-NOV-05:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
December 73507.84 28-DEC-06:02 8061.19 2686.80 38236.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 73507.84   0.00 2686.80 26719.30 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 82977.06   8061.19 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 35728.87 27-JAN-17:00 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
February 33878.84 23-FEB-15:00 16014.58 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
March 72024.86 17-MAR-05:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
April 76307.29 26-APR-04:12 0.00 2686.80 29688.11 0.00 0.00 0.00 0.00 0.00 0.00
May 84595.62 08-MAY-04:13 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
June 85336.75 19-JUN-04:13 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
July 84818.26 03-JUL-04:13 0.00 3761.52 41563.36 0.00 0.00 0.00 0.00 0.00 0.00
August 78759.68 21-AUG-05:03 9673.43 3224.16 45884.17 0.00 0.00 0.00 0.00 0.00 0.00
September 80378.48 05-SEP-04:13 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
October 77012.85 05-OCT-04:12 0.00 3224.16 35625.74 0.00 0.00 0.00 0.00 0.00 0.00
November 72255.06 03-NOV-05:03 6448.95 2149.44 30589.44 0.00 0.00 0.00 0.00 0.00 0.00
December 33733.37 22-DEC-16:50 15316.26 13241.18 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 33733.37   0.00 2149.44 17206.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 85336.75   16014.58 13241.18 45884.17 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5236.82 31-JAN-16:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 16.78 0.00
February 5211.48 22-FEB-14:00 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 35.18
March 7397.15 20-MAR-14:00 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 21.30 0.00
April 18073.25 30-APR-16:21 1012.16 439.44 7201.84 0.00 0.00 0.00 0.00 293.46 0.00
May 18146.72 29-MAY-18:11 0.00 395.49 5032.54 0.00 0.00 0.00 0.00 167.29 0.00
June 19291.97 25-JUN-18:31 0.00 439.44 5591.71 0.00 0.00 0.00 0.00 369.15 0.00
July 18952.81 04-JUL-18:11 0.00 439.44 5591.71 0.00 0.00 0.00 0.00 290.41 0.00
August 18500.01 13-AUG-16:21 809.73 351.55 5761.47 0.00 0.00 0.00 0.00 569.94 0.00
September 18053.44 10-SEP-16:42 607.30 263.66 4321.10 0.00 0.00 0.00 0.00 361.53 0.00
October 14031.51 02-OCT-04:23 0.00 269.88 2982.24 0.00 0.00 0.00 0.00 24.45 0.00
November 9271.52 13-NOV-06:03 809.73 269.88 3840.98 0.00 0.00 0.00 0.00 0.00 10.19
December 5465.25 26-DEC-15:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 3.82
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5211.48   0.00 263.66 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19291.97   2010.79 791.05 7201.84 0.00 0.00 0.00 0.00 569.94 35.18



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7730.19 17-JAN-09:30 1239.33 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 47.09
February 10671.26 20-FEB-09:03 195.68 84.96 1392.34 0.00 0.00 0.00 0.00 0.00 70.58
March 17217.37 19-MAR-09:32 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 70.68
April 19626.92 23-APR-08:22 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 0.00 25.12
May 20301.77 29-MAY-09:31 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 25.38
June 20170.01 25-JUN-07:51 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 1.00
July 19067.67 04-JUL-08:51 521.82 226.55 3712.91 0.00 0.00 0.00 0.00 14.93 0.00
August 19027.73 13-AUG-09:02 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 39.00 0.00
September 19940.70 10-SEP-09:21 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 25.23 0.00
October 18792.06 15-OCT-08:42 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 83.45
November 9026.42 19-NOV-09:33 195.68 84.96 1392.34 0.00 0.00 0.00 0.00 0.00 130.55
December 6784.77 26-DEC-09:40 1239.33 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 17.30
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6784.77   195.68 84.96 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20301.77   1239.33 509.78 3712.91 0.00 0.00 0.00 0.00 39.00 130.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 22628.36 22-JAN-13:32 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 239.45
February 17043.02 26-FEB-11:13 303.66 131.83 2160.58 0.00 0.00 0.00 0.00 0.00 151.08
March 15819.24 26-MAR-14:53 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 228.52
April 21341.38 23-APR-15:41 1012.19 439.45 7201.95 0.00 0.00 0.00 0.00 175.87 0.00
May 20488.08 07-MAY-16:21 1012.19 439.45 7201.95 0.00 0.00 0.00 0.00 236.84 0.00
June 21118.35 04-JUN-15:51 1012.19 439.45 7201.95 0.00 0.00 0.00 0.00 327.55 0.00
July 20976.40 04-JUL-16:51 1012.19 439.45 7201.95 0.00 0.00 0.00 0.00 363.28 0.00
August 21055.45 27-AUG-13:41 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 319.18 0.00
September 22735.38 10-SEP-12:41 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 165.49 0.00
October 23503.15 15-OCT-13:21 809.75 351.56 5761.56 0.00 0.00 0.00 0.00 38.19 0.00
November 22547.24 26-NOV-12:42 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 226.46
December 22616.59 10-DEC-14:02 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 110.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15819.24   303.66 131.83 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23503.15   1012.19 439.45 7201.95 0.00 0.00 0.00 0.00 363.28 239.45



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 24377.94 29-JAN-16:22 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 52.24
February 18040.19 20-FEB-16:22 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 97.91
March 23157.96 26-MAR-16:12 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 83.81
April 28896.48 23-APR-16:21 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 63.19 0.00
May 27513.08 28-MAY-17:01 0.00 283.19 3603.49 0.00 0.00 0.00 0.00 82.43 0.00
June 28754.76 25-JUN-17:11 0.00 283.19 3603.49 0.00 0.00 0.00 0.00 160.08 0.00
July 28193.33 04-JUL-16:51 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 175.24 0.00
August 27085.93 13-AUG-16:21 521.82 226.55 3712.89 0.00 0.00 0.00 0.00 308.36 0.00
September 24248.60 04-SEP-15:42 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 54.93 0.00
October 24844.17 15-OCT-14:01 521.82 226.55 3712.89 0.00 0.00 0.00 0.00 48.34 0.00
November 23052.91 26-NOV-14:42 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 156.85
December 24160.14 25-DEC-16:12 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 29.36
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 18040.19   0.00 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 28896.48   652.28 283.19 4641.11 0.00 0.00 0.00 0.00 308.36 156.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3953.37 31-JAN-16:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 38.49 0.00
February 3210.13 22-FEB-14:10 4021.58 1582.09 4321.10 0.00 0.00 0.00 0.00 0.00 82.55
March 5661.58 16-MAR-16:00 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 71.70 0.00
April 17456.02 30-APR-16:31 1012.16 439.44 7201.84 0.00 0.00 0.00 0.00 670.86 0.00
May 18044.12 07-MAY-17:01 0.00 439.44 5591.71 0.00 0.00 0.00 0.00 536.67 0.00
June 19361.15 25-JUN-18:01 0.00 439.44 5591.71 0.00 0.00 0.00 0.00 964.31 0.00
July 18950.27 30-JUL-18:11 0.00 439.44 5591.71 0.00 0.00 0.00 0.00 1050.70 0.00
August 19202.53 13-AUG-16:11 1012.16 439.44 7201.84 0.00 0.00 0.00 0.00 1271.87 0.00
September 18029.02 10-SEP-16:42 607.30 263.66 4321.10 0.00 0.00 0.00 0.00 813.42 0.00
October 17753.53 01-OCT-13:32 506.08 219.72 3600.92 0.00 0.00 0.00 0.00 594.91 0.00
November 5624.07 02-NOV-14:00 2010.79 791.05 2160.55 0.00 0.00 0.00 0.00 67.28 0.00
December 2770.66 22-DEC-16:10 1923.11 838.84 2160.55 0.00 0.00 0.00 0.00 2.11 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2770.66   0.00 219.72 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19361.15   4021.58 1582.09 7201.84 0.00 0.00 0.00 0.00 1271.87 82.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 7073.99 27-JAN-11:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 35.77
February 7228.57 23-FEB-11:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 67.21
March 13982.39 19-MAR-09:23 260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 188.55
April 21496.07 30-APR-09:51 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 3.47
May 21787.53 07-MAY-09:01 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 27.23
June 22394.03 25-JUN-08:41 521.82 226.55 3712.91 0.00 0.00 0.00 0.00 21.74 0.00
July 21714.92 30-JUL-08:11 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 36.44
August 22403.74 13-AUG-08:51 521.82 226.55 3712.91 0.00 0.00 0.00 0.00 58.07 0.00
September 21577.46 10-SEP-10:01 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 98.96 0.00
October 19560.72 09-OCT-09:52 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 47.63
November 8610.25 01-NOV-10:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 6.14
December 5666.45 27-DEC-11:05 2478.65 1019.56 2784.68 0.00 0.00 0.00 0.00 0.00 10.22
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5666.45   260.91 113.28 1856.46 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22403.74   2478.65 1019.56 3712.91 0.00 0.00 0.00 0.00 98.96 188.55



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 21650.21 29-JAN-13:52 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 127.23
February 17093.60 20-FEB-15:13 303.66 131.83 2160.58 0.00 0.00 0.00 0.00 0.00 290.28
March 15714.64 26-MAR-14:03 303.66 131.83 2160.58 0.00 0.00 0.00 0.00 0.00 279.39
April 21137.67 30-APR-12:32 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 409.88 0.00
May 20422.76 07-MAY-16:21 1012.19 439.45 7201.95 0.00 0.00 0.00 0.00 538.43 0.00
June 20874.83 25-JUN-18:01 0.00 439.45 5591.79 0.00 0.00 0.00 0.00 1025.85 0.00
July 21594.69 30-JUL-14:51 910.97 395.50 6481.75 0.00 0.00 0.00 0.00 657.29 0.00
August 22063.58 13-AUG-16:11 1012.19 439.45 7201.95 0.00 0.00 0.00 0.00 1227.91 0.00
September 22784.35 10-SEP-12:41 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 363.31 0.00
October 23606.86 09-OCT-12:31 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 44.35 0.00
November 21330.51 19-NOV-13:32 506.09 219.72 3600.97 0.00 0.00 0.00 0.00 0.00 202.01
December 22752.83 03-DEC-14:32 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 558.86
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 15714.64   0.00 131.83 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23606.86   1012.19 439.45 7201.95 0.00 0.00 0.00 0.00 1227.91 558.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14447.62 29-JAN-16:32 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 104.09
February 10774.24 22-FEB-16:30 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 46.97
March 15884.79 18-MAR-17:05 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 1.85
April 24766.66 30-APR-16:31 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 189.67 0.00
May 24975.43 07-MAY-16:21 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 247.66 0.00
June 26070.20 25-JUN-17:21 0.00 283.19 3603.49 0.00 0.00 0.00 0.00 394.83 0.00
July 25936.65 30-JUL-17:31 0.00 283.19 3603.49 0.00 0.00 0.00 0.00 541.60 0.00
August 26257.94 13-AUG-16:51 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 544.27 0.00
September 23543.97 04-SEP-16:51 521.82 226.55 3712.89 0.00 0.00 0.00 0.00 92.93 0.00
October 22827.49 09-OCT-16:31 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 159.51 0.00
November 14254.25 19-NOV-15:32 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 4.18 0.00
December 14962.26 25-DEC-16:32 326.14 141.60 2320.55 0.00 0.00 0.00 0.00 0.00 79.03
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10774.24   0.00 141.60 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26257.94   1239.33 509.78 4641.11 0.00 0.00 0.00 0.00 544.27 104.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3725.45 31-JAN-16:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 46.72 0.00
February 2962.35 22-FEB-16:20 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 0.00 86.02
March 6119.57 16-MAR-16:00 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 86.96 0.00
April 17346.66 30-APR-16:01 708.51 307.61 5041.29 0.00 0.00 0.00 0.00 976.47 0.00
May 20763.89 28-MAY-16:51 1012.16 439.44 7201.84 0.00 0.00 0.00 0.00 667.63 0.00
June 21426.58 25-JUN-18:11 0.00 351.55 4473.37 0.00 0.00 0.00 0.00 1205.29 0.00
July 22924.31 16-JUL-17:31 0.00 439.44 5591.71 0.00 0.00 0.00 0.00 1215.86 0.00
August 21400.62 13-AUG-16:21 809.73 351.55 5761.47 0.00 0.00 0.00 0.00 1590.18 0.00
September 20594.63 24-SEP-15:32 607.30 263.66 4321.10 0.00 0.00 0.00 0.00 651.42 0.00
October 14762.44 02-OCT-03:02 0.00 337.35 3727.80 0.00 0.00 0.00 0.00 0.00 52.31
November 5852.17 01-NOV-15:30 1923.11 791.05 2160.55 0.00 0.00 0.00 0.00 76.48 0.00
December 2556.13 22-DEC-16:40 1923.11 1060.58 2160.55 0.00 0.00 0.00 0.00 0.86 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2556.13   0.00 263.66 2160.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22924.31   1923.11 1060.58 7201.84 0.00 0.00 0.00 0.00 1590.18 86.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4929.59 27-JAN-10:30 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 73.91
February 5608.34 23-FEB-10:20 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 52.58
March 7425.87 23-MAR-10:20 1239.33 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 37.39
April 20384.74 09-APR-10:22 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 34.71
May 21475.26 28-MAY-10:12 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 39.52 0.00
June 23110.51 18-JUN-08:11 521.82 226.55 3712.91 0.00 0.00 0.00 0.00 91.60 0.00
July 22388.96 30-JUL-08:11 456.59 198.23 3248.80 0.00 0.00 0.00 0.00 0.00 48.88
August 21209.80 13-AUG-09:42 391.37 169.91 2784.68 0.00 0.00 0.00 0.00 95.62 0.00
September 20288.81 10-SEP-10:12 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 191.32 0.00
October 19843.37 15-OCT-09:22 326.14 141.60 2320.57 0.00 0.00 0.00 0.00 0.00 104.90
November 6508.86 01-NOV-10:00 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 11.92
December 3126.63 22-DEC-10:40 1295.83 509.78 1392.34 0.00 0.00 0.00 0.00 0.00 23.16
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3126.63   326.14 141.60 1392.34 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23110.51   1295.83 509.78 3712.91 0.00 0.00 0.00 0.00 191.32 104.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 25863.50 29-JAN-14:11 708.53 307.61 5041.36 0.00 0.00 0.00 0.00 0.00 216.50
February 19554.80 26-FEB-14:43 404.87 175.78 2880.78 0.00 0.00 0.00 0.00 0.00 773.53
March 14425.96 23-MAR-14:00 2010.83 791.06 2160.58 0.00 0.00 0.00 0.00 60.88 0.00
April 23532.25 02-APR-16:21 1012.19 439.45 7201.95 0.00 0.00 0.00 0.00 136.53 0.00
May 22939.21 28-MAY-16:51 1012.19 439.45 7201.95 0.00 0.00 0.00 0.00 657.90 0.00
June 22962.87 18-JUN-17:32 0.00 219.72 2795.90 0.00 0.00 0.00 0.00 320.17 0.00
July 25170.12 30-JUL-14:51 910.97 395.50 6481.75 0.00 0.00 0.00 0.00 767.57 0.00
August 23822.36 13-AUG-16:21 809.75 351.56 5761.56 0.00 0.00 0.00 0.00 1561.05 0.00
September 24307.75 10-SEP-13:32 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 706.66 0.00
October 26565.62 09-OCT-13:41 809.75 351.56 5761.56 0.00 0.00 0.00 0.00 53.71 0.00
November 23910.90 26-NOV-13:22 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 693.43
December 24612.10 03-DEC-14:32 607.31 263.67 4321.17 0.00 0.00 0.00 0.00 0.00 651.26
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 14425.96   0.00 175.78 2160.58 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26565.62   2010.83 791.06 7201.95 0.00 0.00 0.00 0.00 1561.05 773.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20076.17 29-JAN-16:12 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 111.77
February 10715.77 22-FEB-16:30 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 0.00 60.08
March 17199.12 18-MAR-17:05 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 6.04
April 27165.16 02-APR-16:21 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 24.45 0.00
May 27621.87 28-MAY-16:51 652.28 283.19 4641.11 0.00 0.00 0.00 0.00 197.41 0.00
June 25805.27 25-JUN-17:31 0.00 226.55 2882.79 0.00 0.00 0.00 0.00 645.36 0.00
July 28835.49 30-JUL-17:31 0.00 283.19 3603.49 0.00 0.00 0.00 0.00 630.01 0.00
August 26035.31 13-AUG-16:21 521.82 226.55 3712.89 0.00 0.00 0.00 0.00 896.52 0.00
September 23850.78 24-SEP-15:32 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 380.86 0.00
October 25120.30 09-OCT-15:41 456.59 198.23 3248.78 0.00 0.00 0.00 0.00 190.82 0.00
November 12446.44 01-NOV-16:00 1239.33 509.78 1392.33 0.00 0.00 0.00 0.00 59.72 0.00
December 13088.74 25-DEC-16:12 391.37 169.91 2784.67 0.00 0.00 0.00 0.00 0.00 67.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10715.77   0.00 169.91 1392.33 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 28835.49   1239.33 509.78 4641.11 0.00 0.00 0.00 0.00 896.52 111.77



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6159.60 17-JAN-17:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7.08
February 5299.93 21-FEB-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72.48
March 7383.93 20-MAR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 172.86
April 9319.85 24-APR-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 80.62 0.00
May 11964.53 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 55.12
June 12046.87 05-JUN-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.78
July 15132.12 05-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.89
August 17219.69 28-AUG-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.37 0.00
September 13994.52 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.16
October 13452.12 02-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.52 0.00
November 9054.68 13-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.95
December 8889.90 26-DEC-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 182.85
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5299.93   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17219.69   0.00 0.00 0.00 0.00 0.00 0.00 0.00 80.62 182.85



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3329.77 27-JAN-17:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.13 0.00
February 3183.66 01-FEB-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 433.16
March 4310.14 27-MAR-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 460.65
April 7044.22 25-APR-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 291.96 0.00
May 7672.61 08-MAY-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 234.33 0.00
June 9638.34 26-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.64
July 9663.86 31-JUL-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.08 0.00
August 12812.67 28-AUG-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.83 0.00
September 10573.04 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 23.02
October 8845.45 02-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.87 0.00
November 4619.41 02-NOV-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 50.08 0.00
December 7311.35 06-DEC-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 329.48
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3183.66   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12812.67   0.00 0.00 0.00 0.00 0.00 0.00 0.00 291.96 460.65



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8574.41 31-JAN-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52.06 0.00
February 7726.42 23-FEB-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 230.13
March 12062.91 16-MAR-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84.38 0.00
April 19394.92 14-APR-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 112.88 0.00
May 19868.37 19-MAY-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 518.34 0.00
June 24168.65 28-JUN-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 616.99 0.00
July 22619.36 20-JUL-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 440.32 0.00
August 22243.24 15-AUG-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 478.27 0.00
September 19760.21 07-SEP-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 226.93 0.00
October 17355.82 02-OCT-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 246.87 0.00
November 11084.33 01-NOV-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67.64 0.00
December 6487.88 22-DEC-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.99
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 6487.88   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24168.65   0.00 0.00 0.00 0.00 0.00 0.00 0.00 616.99 230.13



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2269.16 29-JAN-17:15 46.77 70.37 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
February 4068.56 27-FEB-17:40 70.15 175.91 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 7149.80 31-MAR-24:00 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7785.51 26-APR-18:50 23.38 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3493.39 31-MAY-23:55 0.00 35.18 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
June 5429.60 30-JUN-24:00 0.00 52.77 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7341.07 31-JUL-23:57 0.00 52.77 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7782.77 20-AUG-23:50 0.00 70.37 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3492.33 30-SEP-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5321.31 31-OCT-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 6268.13 26-NOV-16:53 35.07 52.77 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
December 7940.85 28-DEC-17:00 222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2269.16   0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7940.85   222.14 316.63 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2061.23 24-JAN-17:00 222.14 316.63 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3810.85 27-FEB-17:40 70.15 175.91 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6696.05 31-MAR-23:40 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7420.90 26-APR-18:50 23.38 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3404.56 31-MAY-23:55 0.00 35.18 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
June 5222.19 30-JUN-24:00 0.00 52.77 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7013.90 31-JUL-23:57 0.00 52.77 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7274.42 20-AUG-20:52 0.00 87.96 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
September 3408.00 30-SEP-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4928.06 31-OCT-24:00 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5827.19 14-NOV-17:00 222.14 316.63 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7471.51 28-DEC-17:00 222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2061.23   0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7471.51   222.14 316.63 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2077.23 24-JAN-17:00 222.14 316.63 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3784.95 27-FEB-17:40 70.15 175.91 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6523.96 31-MAR-23:20 0.00 17.59 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7533.02 26-APR-18:30 23.38 105.54 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3403.52 31-MAY-23:55 0.00 35.18 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
June 5274.16 30-JUN-24:00 0.00 52.77 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7058.14 31-JUL-23:57 0.00 52.77 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7475.90 20-AUG-21:03 0.00 70.37 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3436.68 30-SEP-24:00 0.00 17.59 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4740.24 31-OCT-23:40 0.00 17.59 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5847.14 21-NOV-17:00 222.14 316.63 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7433.67 28-DEC-17:00 222.14 316.63 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2077.23   0.00 17.59 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7533.02   222.14 316.63 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 92349.85 17-JAN-17:00 4808.68 4157.19 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 182944.37 21-FEB-17:00 4808.68 4157.19 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358012.76 31-MAR-24:00 0.00 230.94 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 380835.57 03-APR-21:01 1771.62 3233.49 2657427.65 0.00 0.00 0.00 0.00 0.00 0.00
May 175605.43 31-MAY-24:00 0.00 461.88 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
June 267480.47 30-JUN-23:57 0.00 692.81 854173.17 0.00 0.00 0.00 0.00 0.00 0.00
July 356506.24 31-JUL-23:13 0.00 692.81 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 386584.44 23-AUG-22:53 1012.35 923.75 1518530.09 0.00 0.00 0.00 0.00 0.00 0.00
September 177154.08 30-SEP-24:00 0.00 230.94 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 269011.04 31-OCT-24:00 0.00 230.94 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 276954.62 20-NOV-17:00 4808.68 4157.19 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 372186.93 25-DEC-16:41 2024.71 1847.50 3037060.17 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 92349.85   0.00 230.94 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 386584.44   4808.68 4157.19 3037060.17 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.171476E+13 1281223.64 27-JAN-16:00 0.718621E+11 440578.96 02-JAN-06:10
February 0.169726E+13 1265532.48 22-FEB-16:30 0.667565E+11 242095.69 13-FEB-06:10
March 0.248043E+13 1657513.44 17-MAR-15:30 0.722675E+11 434805.59 27-MAR-06:10
April 0.314970E+13 1871957.50 10-APR-15:00 0.536409E+11 71676.18 04-APR-11:30
May 0.204891E+13 1330275.91 08-MAY-07:00 0.532374E+11 68119.10 02-MAY-11:20
June 0.252401E+13 1573029.07 28-JUN-15:09 0.495258E+11 62657.83 05-JUN-11:20
July 0.293467E+13 1739824.55 20-JUL-15:09 0.474708E+11 59342.37 03-JUL-11:50
August 0.340205E+13 1972025.41 25-AUG-15:09 0.504413E+11 60833.97 30-AUG-11:30
September 0.193198E+13 1378812.99 05-SEP-07:00 0.489705E+11 64064.95 21-SEP-11:50
October 0.224925E+13 1479655.96 02-OCT-15:00 0.556417E+11 216027.10 25-OCT-06:10
November 0.238411E+13 1620699.60 09-NOV-16:00 0.617120E+11 294103.68 24-NOV-07:10
December 0.279305E+13 1682001.47 22-DEC-16:19 0.102254E+12 561954.11 06-DEC-07:10
             
Annual Sum or Average 0.293102E+14     0.733781E+12    
Minimum of Months 0.169726E+13 1265532.48   0.474708E+11 59342.37  
Maximum of Months 0.340205E+13 1972025.41   0.102254E+12 561954.11  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.207218E+12 0.373844E+11 0.766053E+12 0.162121E+12 0.185800E+12 0.296546E+11 0.00 0.938919E+11 0.445705E+11 0.188062E+12 0.00 0.00 0.00
February 0.187494E+12 0.309088E+11 0.978954E+12 0.146439E+12 0.164054E+12 0.214376E+11 0.00 0.556073E+11 0.198474E+11 0.925226E+11 0.00 0.00 0.00
March 0.220964E+12 0.303717E+11 0.141687E+13 0.162292E+12 0.197103E+12 0.319981E+11 0.00 0.168627E+12 0.606969E+11 0.191509E+12 0.00 0.00 0.00
April 0.196181E+12 0.256650E+11 0.165903E+13 0.156875E+12 0.237105E+12 0.538948E+11 0.00 0.457136E+12 0.109091E+12 0.254728E+12 0.00 0.00 0.00
May 0.211321E+12 0.232835E+11 0.774844E+12 0.162206E+12 0.260987E+12 0.553064E+11 0.00 0.306840E+12 0.114302E+12 0.139823E+12 0.00 0.00 0.00
June 0.209743E+12 0.213378E+11 0.106252E+13 0.157035E+12 0.286074E+12 0.702441E+11 0.00 0.513677E+12 0.137163E+12 0.662181E+11 0.00 0.00 0.00
July 0.196377E+12 0.226209E+11 0.139340E+13 0.162046E+12 0.276516E+12 0.698445E+11 0.00 0.633468E+12 0.160053E+12 0.203374E+11 0.00 0.00 0.00
August 0.219938E+12 0.251910E+11 0.173200E+13 0.162291E+12 0.285221E+12 0.711259E+11 0.00 0.701863E+12 0.161375E+12 0.430472E+11 0.00 0.00 0.00
September 0.196801E+12 0.275813E+11 0.740713E+12 0.156875E+12 0.245431E+12 0.573510E+11 0.00 0.340383E+12 0.147420E+12 0.194214E+11 0.00 0.00 0.00
October 0.205647E+12 0.325062E+11 0.108340E+13 0.162121E+12 0.216539E+12 0.446687E+11 0.00 0.253405E+12 0.939483E+11 0.157014E+12 0.00 0.00 0.00
November 0.204663E+12 0.352667E+11 0.135889E+13 0.156940E+12 0.188518E+12 0.314176E+11 0.00 0.172123E+12 0.618646E+11 0.174420E+12 0.00 0.00 0.00
December 0.201192E+12 0.385856E+11 0.170972E+13 0.162047E+12 0.181815E+12 0.274976E+11 0.00 0.161339E+12 0.482693E+11 0.262585E+12 0.00 0.00 0.00
                           
Annual Sum or Average 0.245754E+13 0.350703E+12 0.146764E+14 0.190929E+13 0.272516E+13 0.564441E+12 0.00 0.385836E+13 0.115860E+13 0.160969E+13 0.00 0.00 0.00
Minimum of Months 0.187494E+12 0.213378E+11 0.740713E+12 0.146439E+12 0.164054E+12 0.214376E+11 0.00 0.556073E+11 0.198474E+11 0.194214E+11 0.00 0.00 0.00
Maximum of Months 0.220964E+12 0.385856E+11 0.173200E+13 0.162292E+12 0.286074E+12 0.711259E+11 0.00 0.701863E+12 0.161375E+12 0.262585E+12 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.111892E+11 0.00 0.606730E+11 0.00 0.00
February 0.00 0.00 0.120931E+11 0.00 0.546634E+11 0.00 0.00
March 0.00 0.00 0.113148E+11 0.00 0.609527E+11 0.00 0.00
April 0.00 0.00 20108203.93 0.00 0.536208E+11 0.00 0.00
May 0.00 0.00 0.00 0.00 0.532374E+11 0.00 0.00
June 0.00 0.00 0.00 0.00 0.495258E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.474708E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.504413E+11 0.00 0.00
September 0.00 0.00 0.00 0.00 0.489705E+11 0.00 0.00
October 0.00 0.00 0.207547E+10 0.00 0.535662E+11 0.00 0.00
November 0.00 0.00 0.626402E+10 0.00 0.554480E+11 0.00 0.00
December 0.00 0.00 0.437819E+11 0.00 0.584724E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.867386E+11 0.00 0.647042E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.474708E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.437819E+11 0.00 0.609527E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 238914.26 20-JAN-16:00 40855.88 01-JAN-06:10 423497.50 02-JAN-08:09 116885.78 20-JAN-08:39 157711.12 31-JAN-16:00 39760.67 31-JAN-15:30 0.00 01-JAN-00:10
February 235332.08 10-FEB-08:09 40855.88 01-FEB-06:10 541788.89 01-FEB-08:09 116884.63 10-FEB-08:20 150691.39 22-FEB-16:30 21866.63 23-FEB-14:20 0.00 01-FEB-00:10
March 229209.04 21-MAR-07:10 40855.88 01-MAR-06:10 660080.29 01-MAR-08:09 116881.39 21-MAR-07:19 184306.18 16-MAR-15:50 41049.97 20-MAR-15:30 0.00 01-MAR-00:10
April 217273.89 04-APR-07:10 40855.88 01-APR-05:10 778371.69 03-APR-07:10 116875.08 04-APR-07:19 234029.31 25-APR-15:20 39448.69 14-APR-15:00 0.00 01-APR-00:10
May 214655.15 26-MAY-08:30 40855.88 01-MAY-05:10 423497.50 01-MAY-07:10 116873.38 26-MAY-07:19 236200.91 18-MAY-15:09 39422.05 10-MAY-15:00 0.00 01-MAY-00:10
June 212896.29 27-JUN-07:10 40855.88 01-JUN-05:10 541788.89 01-JUN-07:10 116872.76 27-JUN-07:19 268224.52 19-JUN-14:00 45104.71 19-JUN-14:50 0.00 01-JUN-00:10
July 215376.63 13-JUL-15:00 40855.88 01-JUL-05:10 660080.29 03-JUL-07:10 116873.57 27-JUL-07:19 259721.88 21-JUL-15:39 41895.69 22-JUL-13:39 0.00 01-JUL-00:10
August 232880.68 04-AUG-07:10 40855.88 01-AUG-05:10 778371.69 01-AUG-07:10 116883.34 04-AUG-07:19 255717.86 08-AUG-15:20 43410.67 23-AUG-15:20 0.00 01-AUG-00:10
September 221675.32 29-SEP-07:10 40855.88 01-SEP-05:10 423497.50 01-SEP-07:10 116877.40 29-SEP-07:19 237535.01 05-SEP-15:00 43741.82 28-SEP-13:30 0.00 01-SEP-00:10
October 229737.59 27-OCT-07:10 40855.88 01-OCT-05:10 541788.89 02-OCT-07:10 116881.67 27-OCT-07:19 213845.36 02-OCT-15:00 43716.17 05-OCT-15:00 0.00 01-OCT-00:10
November 247210.90 28-NOV-16:30 40855.88 01-NOV-05:10 660080.29 01-NOV-07:10 116882.02 01-NOV-07:19 171580.43 02-NOV-15:00 47736.35 02-NOV-13:30 0.00 01-NOV-00:10
December 247210.90 01-DEC-16:30 40855.88 01-DEC-06:10 778371.69 01-DEC-08:09 116884.26 12-DEC-08:20 144956.13 22-DEC-16:00 39670.91 22-DEC-15:50 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 212896.29   40855.88   423497.50   116872.76   144956.13   21866.63   0.00  
Maximum of Months 247210.90   40855.88   778371.69   116885.78   268224.52   47736.35   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 248121.44 31-JAN-16:10 46206.67 26-JAN-13:00 100000.00 01-JAN-13:30 0.00 0.00 0.00
February 136011.93 21-FEB-15:30 45331.80 21-FEB-14:00 100000.00 01-FEB-22:10 0.00 0.00 0.00
March 323597.61 20-MAR-14:39 77358.81 17-MAR-15:30 100000.00 08-MAR-05:00 0.00 0.00 0.00
April 379003.04 14-APR-15:20 77358.81 10-APR-12:00 100000.00 01-APR-04:19 0.00 0.00 0.00
May 275799.45 18-MAY-15:20 77358.81 04-MAY-14:20 100000.00 01-MAY-00:20 0.00 0.00 0.00
June 384899.65 19-JUN-14:50 77358.81 01-JUN-08:20 100000.00 02-JUN-02:49 0.00 0.00 0.00
July 430306.34 19-JUL-14:09 77358.81 13-JUL-17:00 100000.00 01-JUL-04:19 0.00 0.00 0.00
August 446424.21 11-AUG-15:50 77358.81 03-AUG-15:20 100000.00 22-AUG-20:49 0.00 0.00 0.00
September 334213.07 01-SEP-12:30 77358.81 04-SEP-09:20 100000.00 15-SEP-21:10 0.00 0.00 0.00
October 337092.26 02-OCT-14:09 77358.81 02-OCT-07:19 100000.00 05-OCT-21:19 0.00 0.00 0.00
November 319225.50 01-NOV-14:30 77358.81 01-NOV-12:20 100000.00 03-NOV-21:10 0.00 0.00 0.00
December 314755.21 22-DEC-15:00 45965.68 22-DEC-15:09 100000.00 01-DEC-05:00 0.00 0.00 0.00
                   
Annual Sum or Average             0.00 0.00 0.00
Minimum of Months 136011.93   45331.80   100000.00   0.00 0.00 0.00
Maximum of Months 446424.21   77358.81   100000.00   0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1281223.64 27-JAN-16:00 214564.27 423497.50 0.00 82829.92 145668.13 39100.64 0.00 229951.24 45611.95
February 1265532.48 22-FEB-16:30 212815.01 541788.89 0.00 82829.33 150691.39 21194.67 0.00 111338.52 44874.66
March 1657513.44 17-MAR-15:30 212815.01 660080.29 0.00 82829.33 174538.51 40470.91 0.00 315815.48 77358.81
April 1871957.50 10-APR-15:00 212815.01 778371.69 0.00 82829.33 220716.06 39340.77 0.00 360525.84 77358.81
May 1330275.91 08-MAY-07:00 212815.01 423497.50 0.00 116872.72 165597.94 39048.78 0.00 226976.53 45467.43
June 1573029.07 28-JUN-15:09 212815.01 541788.89 0.00 82829.33 232508.08 43491.96 0.00 382236.99 77358.81
July 1739824.55 20-JUL-15:09 212815.01 660080.29 0.00 82829.33 254159.40 41096.27 0.00 411485.44 77358.81
August 1972025.41 25-AUG-15:09 212815.01 778371.69 0.00 82829.33 248049.68 39745.71 0.00 432855.19 77358.81
September 1378812.99 05-SEP-07:00 212815.01 423497.50 0.00 116872.72 181960.21 41508.87 0.00 324799.87 77358.81
October 1479655.96 02-OCT-15:00 212815.01 541788.89 0.00 82829.33 213845.36 40434.06 0.00 310584.49 77358.81
November 1620699.60 09-NOV-16:00 222068.11 660080.29 0.00 82832.82 158544.73 39087.11 0.00 311453.46 46633.07
December 1682001.47 22-DEC-16:19 214131.18 778371.69 0.00 82829.66 116007.62 39394.20 0.00 306351.17 44915.96
                       
Annual Sum or Average                      
Minimum of Months 1265532.48   212815.01 423497.50 0.00 82829.33 116007.62 21194.67 0.00 111338.52 44874.66
Maximum of Months 1972025.41   222068.11 778371.69 0.00 116872.72 254159.40 43491.96 0.00 432855.19 77358.81



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 425728.41 02-JAN-06:10 0.00 76823.81 23-JAN-12:20 0.00
February 0.00 0.00 234814.81 13-FEB-06:10 0.00 76768.01 01-FEB-12:50 0.00
March 0.00 0.00 404907.69 27-MAR-06:10 0.00 75573.62 01-MAR-12:30 0.00
April 0.00 0.00 15057.97 21-APR-06:10 0.00 71676.18 04-APR-11:30 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 68119.10 02-MAY-11:20 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 62657.83 05-JUN-11:20 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 59342.37 03-JUL-11:50 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 60833.97 30-AUG-11:30 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 64064.95 21-SEP-11:50 0.00
October 0.00 0.00 186366.28 25-OCT-06:10 0.00 70270.44 30-OCT-11:30 0.00
November 0.00 0.00 271765.18 24-NOV-06:10 0.00 73022.71 20-NOV-12:20 0.00
December 0.00 0.00 531907.45 06-DEC-07:10 0.00 76246.16 29-DEC-12:20 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 59342.37   0.00
Maximum of Months 0.00 0.00 531907.45   0.00 76823.81   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 7.50 27.31 2.00 27.35
February 0.00 0.00 0.00 0.00 2.83 26.48 0.00 26.48
March 0.00 0.00 0.00 0.00 2.00 25.84 0.00 25.84
April 0.00 0.00 0.00 0.00 2.00 26.68 0.00 26.68
May 0.00 0.00 0.00 0.00 3.17 26.90 0.00 26.90
June 0.00 0.00 0.00 0.00 1.67 26.16 0.00 26.16
July 0.00 0.00 0.00 0.00 6.50 26.24 0.17 26.27
August 0.00 0.00 0.00 0.00 8.33 25.86 0.33 25.92
September 0.00 0.00 0.00 0.00 12.50 26.70 1.50 26.74
October 0.00 0.00 0.00 0.00 9.50 26.81 0.83 26.86
November 0.00 0.00 0.00 0.00 8.00 26.86 1.50 26.96
December 0.00 0.00 0.00 0.00 6.00 26.89 0.50 26.94
                 
Annual Sum or Average 0.00   0.00   70.00 26.63 6.83 26.70
Minimum of Months 0.00 0.00 0.00 0.00 1.67 25.84 0.00 25.84
Maximum of Months 0.00 0.00 0.00 0.00 12.50 27.31 2.00 27.35



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 25.57 0.00 25.57
April 0.00 0.00 0.00 0.00 0.83 25.69 0.00 25.69
May 0.00 0.00 0.00 0.00 0.17 25.90 0.00 25.90
June 0.00 0.00 0.00 0.00 0.50 25.63 0.00 25.63
July 0.00 0.00 0.00 0.00 1.17 25.61 0.00 25.61
August 0.00 0.00 0.00 0.00 2.17 25.66 0.33 25.52
September 0.00 0.00 0.00 0.00 0.50 25.76 0.00 25.76
October 0.00 0.00 0.00 0.00 0.50 25.60 0.00 25.60
November 0.00 0.00 0.00 0.00 0.17 25.67 0.00 25.67
December 0.00 0.00 0.00 0.00 0.50 25.61 0.00 25.61
                 
Annual Sum or Average 0.00   0.00   7.00 25.65 0.33 25.61
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.17 25.90 0.33 25.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 25.56 0.00 25.56
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.08 0.00 19.08 0.00 19.08 0.00 19.08
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 25.58 0.00 25.58
July 0.00 0.00 0.00 0.00 0.33 25.64 0.00 25.64
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 19.08 0.00 19.08 0.50 23.98 0.00 23.98
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.08 0.00 19.08 0.33 25.64 0.00 25.64



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.00 27.31 1.00 27.31
May 0.00 0.00 0.00 0.00 1.67 27.33 0.67 27.32
June 0.00 0.00 0.00 0.00 10.67 27.30 5.33 27.37
July 0.00 0.00 0.00 0.00 15.50 27.11 8.33 27.23
August 0.00 0.00 0.00 0.00 13.00 27.07 5.67 27.24
September 0.00 0.00 0.00 0.00 3.83 27.03 2.83 27.18
October 0.00 0.00 0.00 0.00 1.50 26.97 1.17 27.13
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   47.17 27.14 25.00 27.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 15.50 27.33 8.33 27.37



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 27.33 0.17 27.33
February 0.00 0.00 0.00 0.00 1.17 27.43 1.17 27.43
March 0.00 0.00 0.00 0.00 1.50 27.54 1.50 27.54
April 0.00 0.00 0.00 0.00 10.67 27.77 10.33 27.77
May 0.00 0.00 0.00 0.00 14.67 27.84 13.17 27.87
June 0.00 0.00 0.00 0.00 16.00 27.81 11.17 27.93
July 0.00 0.00 0.00 0.00 19.33 27.62 14.17 27.75
August 0.00 0.00 0.00 0.00 14.00 27.65 9.67 27.80
September 0.00 0.00 0.00 0.00 10.50 27.53 9.00 27.61
October 0.00 0.00 0.00 0.00 6.67 27.50 6.33 27.54
November 0.00 0.00 0.00 0.00 0.83 27.34 0.83 27.34
December 0.00 0.00 0.00 0.00 0.17 27.26 0.17 27.26
                 
Annual Sum or Average 0.00   0.00   95.67 27.68 77.67 27.76
Minimum of Months 0.00 0.00 0.00 0.00 0.17 27.26 0.17 27.26
Maximum of Months 0.00 0.00 0.00 0.00 19.33 27.84 14.17 27.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 11.50 27.20 11.50 27.20
February 0.00 0.00 0.00 0.00 2.33 27.62 2.33 27.62
March 0.00 0.00 0.00 0.00 1.50 27.38 1.50 27.38
April 0.00 0.00 0.00 0.00 8.83 27.72 7.67 27.74
May 0.00 0.00 0.00 0.00 6.83 27.41 6.50 27.41
June 0.00 0.00 0.00 0.00 10.33 27.27 6.00 27.37
July 0.00 0.00 0.00 0.00 16.83 27.23 9.83 27.38
August 0.00 0.00 0.00 0.00 18.00 27.23 7.33 27.42
September 0.00 0.00 0.00 0.00 12.17 27.19 9.33 27.26
October 0.00 0.00 0.00 0.00 16.33 26.86 14.67 26.85
November 0.00 0.00 0.00 0.00 16.17 26.08 16.17 26.08
December 0.00 0.00 0.00 0.00 12.83 26.91 12.83 26.91
                 
Annual Sum or Average 0.00   0.00   133.67 27.06 105.67 27.09
Minimum of Months 0.00 0.00 0.00 0.00 1.50 26.08 1.50 26.08
Maximum of Months 0.00 0.00 0.00 0.00 18.00 27.72 16.17 27.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 4.17 27.83 4.17 27.83
February 0.00 0.00 0.00 0.00 1.17 27.87 1.17 27.87
March 0.00 0.00 0.00 0.00 5.17 27.71 3.83 27.75
April 0.00 0.00 0.00 0.00 53.33 27.77 17.67 27.86
May 0.00 0.00 0.00 0.00 20.17 27.85 9.33 27.98
June 0.00 0.00 0.00 0.00 50.33 27.59 17.33 27.66
July 0.00 0.00 0.00 0.00 70.17 27.67 22.50 27.76
August 0.00 0.00 0.00 0.00 76.33 27.86 21.33 27.93
September 0.00 0.00 0.00 0.00 23.33 27.29 10.00 27.47
October 0.00 0.00 0.00 0.00 14.83 27.63 8.00 27.80
November 0.00 0.00 0.00 0.00 6.00 27.71 4.83 27.89
December 0.00 0.00 0.00 0.00 6.00 27.95 5.33 28.00
                 
Annual Sum or Average 0.00   0.00   331.00 27.71 125.50 27.80
Minimum of Months 0.00 0.00 0.00 0.00 1.17 27.29 1.17 27.47
Maximum of Months 0.00 0.00 0.00 0.00 76.33 27.95 22.50 28.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.26 0.00 19.26 0.00 19.26 0.00 19.26
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.83 27.33 0.67 27.34
June 0.00 0.00 0.00 0.00 12.00 27.38 5.83 27.43
July 0.00 0.00 0.00 0.00 12.00 27.37 7.33 27.41
August 0.00 0.00 0.00 0.00 5.83 27.27 3.67 27.38
September 0.00 0.00 0.00 0.00 3.17 27.42 2.83 27.42
October 0.00 0.00 0.00 0.00 1.00 27.10 0.83 27.24
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.38 0.00 19.38 0.00 19.38 0.00 19.38
                 
Annual Sum or Average 0.33 19.32 0.00 19.32 35.83 27.28 21.17 27.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.38 0.00 19.38 12.00 27.42 7.33 27.43



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.41 0.00 19.41 0.00 19.41 0.00 19.41
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.67 27.40 0.67 27.40
April 0.00 0.00 0.00 0.00 12.33 27.84 11.67 27.85
May 0.00 0.00 0.00 0.00 15.33 27.99 13.00 28.03
June 0.00 0.00 0.00 0.00 18.50 27.90 11.33 28.08
July 0.00 0.00 0.00 0.00 23.17 27.67 15.17 27.85
August 0.00 0.00 0.00 0.00 15.33 27.75 10.50 27.90
September 0.00 0.00 0.00 0.00 10.50 27.73 9.17 27.78
October 0.00 0.00 0.00 0.00 6.67 27.51 6.17 27.56
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 19.41 0.00 19.41 0.00 19.41 0.00 19.41
                 
Annual Sum or Average 0.33 19.41 0.00 19.41 102.50 27.76 77.67 27.88
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.41 0.00 19.41 23.17 27.99 15.17 28.08



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 30.67 25.67 30.67 25.67
February 0.00 0.00 0.00 0.00 2.00 27.64 2.00 27.64
March 0.00 0.00 0.00 0.00 0.83 27.42 0.83 27.42
April 0.00 0.00 0.00 0.00 7.33 27.70 6.50 27.72
May 0.00 0.00 0.00 0.00 7.00 27.42 6.33 27.43
June 0.00 0.00 0.00 0.00 9.83 27.35 5.67 27.43
July 0.00 0.00 0.00 0.00 14.00 27.37 9.17 27.47
August 0.00 0.00 0.00 0.00 9.50 27.51 5.83 27.67
September 0.00 0.00 0.00 0.00 13.33 27.03 10.67 27.04
October 0.00 0.00 0.00 0.00 28.83 25.94 27.17 25.91
November 0.00 0.00 0.00 0.00 24.50 25.70 24.33 25.70
December 0.00 0.00 0.00 0.00 16.50 26.31 16.50 26.31
                 
Annual Sum or Average 0.00   0.00   164.33 26.45 145.67 26.42
Minimum of Months 0.00 0.00 0.00 0.00 0.83 25.67 0.83 25.67
Maximum of Months 0.00 0.00 0.00 0.00 30.67 27.70 30.67 27.72



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.67 27.70 1.67 27.70
February 0.00 0.00 0.00 0.00 0.17 27.69 0.17 27.69
March 0.00 0.00 0.00 0.00 0.67 27.66 0.33 27.74
April 0.00 0.00 0.00 0.00 11.17 28.28 5.17 28.36
May 0.00 0.00 0.00 0.00 13.33 28.34 6.17 28.44
June 0.00 0.00 0.00 0.00 24.67 27.68 8.17 27.81
July 0.00 0.00 0.00 0.00 31.50 27.61 11.17 27.76
August 0.00 0.00 0.00 0.00 22.50 27.54 6.83 27.76
September 0.00 0.00 0.00 0.00 11.67 27.57 6.17 27.75
October 0.00 0.00 0.00 0.00 6.67 27.85 4.83 27.93
November 0.00 0.00 0.00 0.00 1.67 27.67 1.67 27.67
December 0.00 0.00 0.00 0.00 1.00 27.80 1.00 27.80
                 
Annual Sum or Average 0.00   0.00   126.67 27.76 53.33 27.90
Minimum of Months 0.00 0.00 0.00 0.00 0.17 27.54 0.17 27.67
Maximum of Months 0.00 0.00 0.00 0.00 31.50 28.34 11.17 28.44



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.83 17.95 0.17 17.46 0.00 17.46 0.00 17.46
February 0.33 19.26 0.00 19.26 0.00 19.26 0.00 19.26
March 0.50 19.18 0.00 19.18 0.00 19.18 0.00 19.18
April 0.00 0.00 0.00 0.00 2.00 27.38 1.33 27.39
May 0.00 0.00 0.00 0.00 6.83 27.48 4.33 27.46
June 0.00 0.00 0.00 0.00 16.17 27.59 8.00 27.65
July 0.00 0.00 0.00 0.00 20.17 27.46 10.33 27.55
August 0.00 0.00 0.00 0.00 9.83 27.54 5.33 27.62
September 0.00 0.00 0.00 0.00 6.83 27.50 5.17 27.54
October 0.00 0.00 0.00 0.00 1.67 27.36 1.50 27.45
November 0.50 19.12 0.00 19.12 0.00 19.12 0.00 19.12
December 2.83 18.83 0.00 18.83 0.00 18.83 0.00 18.83
                 
Annual Sum or Average 5.00 18.78 0.17 18.66 63.50 26.84 36.00 27.13
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.46 0.00 17.46
Maximum of Months 2.83 19.26 0.17 19.26 20.17 27.59 10.33 27.65



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.34 0.00 18.34 0.00 18.34 0.00 18.34
February 0.17 19.13 0.00 19.13 0.00 19.13 0.00 19.13
March 0.17 18.99 0.00 18.99 0.00 18.99 0.00 18.99
April 0.00 0.00 0.00 0.00 13.83 27.85 12.00 27.88
May 0.00 0.00 0.00 0.00 16.83 28.06 13.00 28.12
June 0.00 0.00 0.00 0.00 22.67 27.95 11.67 28.16
July 0.00 0.00 0.00 0.00 28.83 27.80 15.50 27.98
August 0.00 0.00 0.00 0.00 18.67 27.82 10.67 28.00
September 0.00 0.00 0.00 0.00 12.50 27.79 9.17 27.89
October 0.00 0.00 0.00 0.00 7.00 27.51 6.17 27.56
November 0.17 18.80 0.00 18.80 0.00 18.80 0.00 18.80
December 2.67 18.91 0.00 18.91 0.00 18.91 0.00 18.91
                 
Annual Sum or Average 3.50 18.86 0.00 18.86 120.33 27.60 78.17 27.83
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.34 0.00 18.34
Maximum of Months 2.67 19.13 0.00 19.13 28.83 28.06 15.50 28.16



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 18.50 0.00 18.50 5.83 27.90 5.83 28.03
February 0.17 19.17 0.00 19.17 1.17 26.42 1.17 26.90
March 0.17 19.23 0.00 19.23 0.00 19.23 0.00 19.23
April 0.00 0.00 0.00 0.00 9.00 27.79 7.33 27.82
May 0.00 0.00 0.00 0.00 9.33 27.61 6.83 27.63
June 0.00 0.00 0.00 0.00 14.67 27.57 7.33 27.65
July 0.00 0.00 0.00 0.00 20.17 27.52 10.50 27.65
August 0.00 0.00 0.00 0.00 13.83 27.65 6.83 27.80
September 0.00 0.00 0.00 0.00 14.33 27.44 9.50 27.52
October 0.00 0.00 0.00 0.00 10.83 27.89 8.83 27.96
November 0.17 19.36 0.00 19.36 5.33 27.62 5.33 27.75
December 1.17 19.04 0.00 19.04 5.17 26.42 5.17 27.17
                 
Annual Sum or Average 1.83 19.05 0.00 19.05 109.67 27.54 74.67 27.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 19.23 0.00 19.23
Maximum of Months 1.17 19.36 0.00 19.36 20.17 27.90 10.50 28.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 18.34 0.00 18.34 1.00 26.23 1.00 26.84
February 0.17 19.44 0.00 19.44 0.00 19.44 0.00 19.44
March 0.17 19.40 0.00 19.40 0.33 24.99 0.17 25.76
April 0.00 0.00 0.00 0.00 12.83 28.32 5.83 28.40
May 0.00 0.00 0.00 0.00 14.83 28.42 6.83 28.51
June 0.00 0.00 0.00 0.00 29.17 27.82 10.50 27.93
July 0.00 0.00 0.00 0.00 36.67 27.75 12.83 27.89
August 0.00 0.00 0.00 0.00 23.67 27.71 7.33 27.94
September 0.00 0.00 0.00 0.00 15.00 27.66 7.00 27.83
October 0.00 0.00 0.00 0.00 7.00 27.88 4.50 28.01
November 0.17 19.28 0.00 19.28 1.00 26.41 1.00 26.96
December 1.17 18.97 0.00 18.97 0.67 22.11 0.67 23.57
                 
Annual Sum or Average 1.83 19.02 0.00 19.02 142.17 27.76 57.67 27.93
Minimum of Months 0.00 0.00 0.00 0.00 0.00 19.44 0.00 19.44
Maximum of Months 1.17 19.44 0.00 19.44 36.67 28.42 12.83 28.51



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 366.67 28.93 286.67 28.91
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 328.50 28.84 274.33 28.79
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 25.83 28.13 25.00 28.14
                 
Annual Sum or Average 0.00   0.00   721.00 28.86 586.00 28.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 366.67 28.93 286.67 28.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 336.33 28.74 268.17 28.72
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 280.83 28.62 239.33 28.58
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 8.00 27.91 8.00 27.91
                 
Annual Sum or Average 0.00   0.00   625.17 28.67 515.50 28.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 336.33 28.74 268.17 28.72



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 280.33 28.82 223.50 28.78
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 2.00 27.80 0.00 27.80
August 0.00 0.00 0.00 0.00 239.17 28.72 202.83 28.66
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 1.17 27.79 1.17 27.79
                 
Annual Sum or Average 0.00   0.00   522.67 28.77 427.50 28.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 280.33 28.82 223.50 28.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 312.00 31.45 279.00 31.53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 44.33 28.31 20.83 28.37
August 0.00 0.00 0.00 0.00 667.33 31.07 486.83 31.27
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 9.33 28.13 9.33 28.13
                 
Annual Sum or Average 0.00   0.00   1033.00 31.04 796.00 31.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 667.33 31.45 486.83 31.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 92.17 24.00 112.83 25.25 0.00 25.25
February 25.00 24.00 194.50 24.96 0.00 24.96
March 89.17 24.00 101.83 24.90 0.00 24.90
April 103.67 24.00 89.83 25.15 0.00 25.15
May 129.83 24.00 78.33 24.93 0.00 24.93
June 36.17 24.00 115.33 25.38 0.00 25.38
July 160.50 24.39 412.83 24.65 149.00 24.60
August 147.83 24.54 452.50 24.55 145.67 24.55
September 109.83 24.88 390.50 24.75 109.83 24.78
October 66.33 24.07 211.33 25.09 13.83 25.05
November 61.67 24.64 202.17 25.26 19.50 25.31
December 142.67 24.00 102.83 25.07 0.00 25.07
             
Annual Sum or Average 1164.83 24.24 2464.83 24.89 437.83 24.87
Minimum of Months 25.00 24.00 78.33 24.55 0.00 24.55
Maximum of Months 160.50 24.88 452.50 25.38 149.00 25.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 108.17 24.00 74.33 24.65 0.00 24.65
February 23.17 23.99 198.17 24.66 0.00 24.66
March 55.17 24.01 111.17 24.73 0.00 24.73
April 59.83 24.01 42.67 24.47 0.00 24.47
May 80.67 24.02 36.83 24.57 0.00 24.57
June 10.33 24.00 104.33 24.56 0.00 24.56
July 11.33 24.01 402.17 24.27 0.00 24.27
August 0.00 0.00 458.50 24.28 0.00 24.28
September 15.50 25.74 395.50 24.44 15.50 24.49
October 50.17 24.01 204.33 24.67 1.17 24.67
November 60.00 24.26 185.33 24.72 8.00 24.76
December 153.33 24.01 82.33 24.66 0.00 24.66
             
Annual Sum or Average 627.67 24.07 2295.67 24.51 24.67 24.52
Minimum of Months 0.00 0.00 36.83 24.27 0.00 24.27
Maximum of Months 153.33 25.74 458.50 24.73 15.50 24.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 280.83 23.76 24.50 23.85 0.00 23.85
February 130.17 23.75 85.00 24.01 0.00 24.01
March 167.33 23.92 55.17 24.16 0.00 24.16
April 185.33 24.02 17.50 24.15 0.00 24.15
May 156.83 24.02 19.50 24.22 0.00 24.22
June 48.17 24.00 47.83 24.23 0.00 24.23
July 37.67 24.19 374.00 24.21 19.00 24.22
August 60.83 24.39 426.17 24.21 44.17 24.24
September 44.50 24.96 381.67 24.42 44.50 24.47
October 148.00 23.97 136.67 24.27 3.33 24.27
November 247.17 23.97 112.17 24.16 26.17 24.19
December 392.33 23.86 0.00 23.86 0.00 23.86
             
Annual Sum or Average 1899.17 23.95 1680.17 24.15 137.17 24.17
Minimum of Months 37.67 23.75 0.00 23.85 0.00 23.85
Maximum of Months 392.33 24.96 426.17 24.42 44.50 24.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 437.67 23.21 20.33 23.06 18.17 22.92
February 340.17 23.02 14.33 23.03 3.17 23.01
March 300.83 23.47 22.83 23.48 4.33 23.45
April 178.17 23.93 23.83 24.05 0.00 24.05
May 146.83 24.01 27.83 24.27 0.00 24.27
June 28.83 23.99 107.50 24.49 0.00 24.49
July 46.17 24.13 396.83 24.31 30.33 24.31
August 71.17 24.29 440.00 24.25 61.67 24.26
September 68.17 24.63 392.50 24.44 68.00 24.46
October 220.00 23.75 119.33 23.99 7.00 23.99
November 327.50 23.29 89.50 23.50 27.50 23.52
December 483.33 22.87 29.17 22.75 29.17 22.65
             
Annual Sum or Average 2648.83 23.39 1684.00 23.72 249.33 23.71
Minimum of Months 28.83 22.87 14.33 22.75 0.00 22.65
Maximum of Months 483.33 24.63 440.00 24.49 68.00 24.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 448.33 23.55 10.33 23.58 0.00 23.58
February 297.67 23.35 17.83 23.39 0.00 23.39
March 262.83 23.58 38.33 23.71 0.00 23.71
April 116.50 23.97 75.50 24.47 0.00 24.47
May 59.83 24.00 88.67 24.98 0.00 24.98
June 15.50 26.52 283.67 24.83 13.00 24.92
July 34.67 26.53 455.83 24.70 33.50 24.82
August 25.83 26.71 479.33 24.53 25.17 24.64
September 36.67 26.35 424.83 24.65 36.67 24.78
October 192.33 23.86 151.83 24.21 2.50 24.23
November 306.83 23.72 88.67 23.87 13.33 23.90
December 449.17 23.48 1.50 23.48 0.00 23.48
             
Annual Sum or Average 2246.17 23.75 2116.33 24.16 124.17 24.23
Minimum of Months 15.50 23.35 1.50 23.39 0.00 23.39
Maximum of Months 449.17 26.71 479.33 24.98 36.67 24.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 269.00 23.53 44.33 23.79 0.00 23.79
February 230.33 23.30 80.17 23.63 2.83 23.66
March 195.33 23.54 102.17 23.93 1.33 23.95
April 79.00 24.48 189.50 24.74 14.17 24.87
May 45.67 25.49 237.50 25.01 20.67 25.17
June 39.17 26.94 381.83 24.82 37.00 25.00
July 53.50 26.80 466.33 24.82 52.33 25.01
August 43.50 26.75 488.17 24.61 41.00 24.77
September 50.17 26.60 446.50 24.74 50.17 24.91
October 137.50 24.12 223.50 24.51 15.33 24.62
November 221.50 23.67 129.67 23.99 15.33 24.02
December 367.67 23.39 26.83 23.53 3.00 23.51
             
Annual Sum or Average 1732.33 23.98 2816.50 24.38 253.17 24.51
Minimum of Months 39.17 23.30 26.83 23.53 0.00 23.51
Maximum of Months 367.67 26.94 488.17 25.01 52.33 25.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 174.33 23.99 205.83 24.44 22.83 24.60
February 174.67 23.35 153.67 23.86 5.83 23.91
March 159.17 23.45 142.83 23.97 0.17 23.97
April 88.83 24.24 183.00 24.64 7.67 24.72
May 72.33 24.02 118.33 24.81 0.00 24.81
June 24.17 25.81 270.67 24.81 14.67 24.92
July 40.33 26.42 448.17 24.72 35.83 24.85
August 32.17 26.84 486.67 24.59 31.50 24.72
September 47.83 26.70 446.67 24.78 47.83 24.95
October 113.50 24.69 285.17 24.76 32.00 24.94
November 137.67 24.20 265.33 24.49 30.50 24.59
December 237.17 23.81 146.33 24.28 22.00 24.42
             
Annual Sum or Average 1302.17 24.19 3152.67 24.52 250.83 24.64
Minimum of Months 24.17 23.35 118.33 23.86 0.00 23.91
Maximum of Months 237.17 26.84 486.67 24.81 47.83 24.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 172.83 23.98 109.50 24.36 7.00 24.43
February 54.17 24.04 218.67 24.47 3.00 24.50
March 45.00 24.61 262.67 24.74 8.67 24.81
April 40.67 27.02 346.83 25.14 37.50 25.33
May 27.33 26.83 272.00 25.24 23.83 25.38
June 40.00 27.10 423.67 24.88 40.00 25.06
July 95.83 26.97 481.67 25.10 95.83 25.37
August 110.67 26.54 509.67 24.95 110.67 25.19
September 62.50 26.90 465.67 24.91 62.50 25.12
October 68.50 25.22 302.17 25.00 27.00 25.14
November 71.00 25.06 255.83 24.95 25.00 25.09
December 134.00 24.27 141.83 24.89 10.17 24.97
             
Annual Sum or Average 922.50 25.40 3790.17 24.91 451.17 25.09
Minimum of Months 27.33 23.98 109.50 24.36 3.00 24.43
Maximum of Months 172.83 27.10 509.67 25.24 110.67 25.38



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 501.17 22.54 30.33 22.39 30.33 22.26
February 422.50 22.34 6.83 22.32 5.33 22.30
March 407.33 22.86 23.83 22.80 16.00 22.72
April 209.17 23.76 39.00 24.00 0.00 24.00
May 102.00 23.96 62.33 24.74 0.00 24.74
June 14.33 26.34 251.67 24.94 11.00 25.03
July 47.50 26.01 447.33 24.73 45.00 24.85
August 45.67 25.35 458.67 24.49 39.33 24.57
September 48.00 25.81 406.00 24.66 44.17 24.78
October 284.67 23.34 108.33 23.65 5.33 23.67
November 420.83 22.74 80.67 22.80 52.50 22.77
December 497.00 21.97 109.33 21.75 109.33 21.60
             
Annual Sum or Average 3000.17 22.86 2024.33 23.42 358.33 23.39
Minimum of Months 14.33 21.97 6.83 21.75 0.00 21.60
Maximum of Months 501.17 26.34 458.67 24.94 109.33 25.03



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 308.50 22.93 31.50 22.97 11.83 22.88
February 264.00 22.63 41.33 22.86 2.83 22.84
March 235.33 23.09 65.67 23.42 6.83 23.36
April 88.67 24.48 157.33 24.94 17.83 25.10
May 55.67 25.49 201.33 25.25 25.67 25.44
June 42.00 27.07 311.83 25.08 40.67 25.29
July 69.83 26.70 394.00 25.09 69.17 25.30
August 60.33 26.51 409.17 24.84 58.17 25.03
September 57.67 26.60 366.33 24.96 57.33 25.15
October 162.17 23.75 162.67 24.36 15.50 24.47
November 271.50 23.14 76.83 23.37 26.83 23.38
December 390.67 22.74 44.83 22.57 42.17 22.41
             
Annual Sum or Average 2006.33 23.54 2262.83 24.15 374.83 24.26
Minimum of Months 42.00 22.63 31.50 22.57 2.83 22.41
Maximum of Months 390.67 27.07 409.17 25.25 69.17 25.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 216.83 23.66 210.33 24.21 29.33 24.32
February 233.67 22.85 142.33 23.45 6.50 23.48
March 229.33 23.05 121.33 23.52 5.83 23.47
April 124.83 23.88 155.17 24.46 4.50 24.51
May 97.67 23.93 101.67 24.71 0.00 24.71
June 25.00 25.27 240.67 24.86 10.33 24.95
July 58.83 25.86 440.33 24.74 52.50 24.87
August 55.00 25.78 476.67 24.58 48.83 24.70
September 56.00 26.52 438.83 24.82 56.00 24.99
October 143.00 24.32 266.50 24.64 34.33 24.82
November 190.00 23.69 241.50 24.20 41.67 24.29
December 269.67 23.24 147.83 23.72 37.00 23.76
             
Annual Sum or Average 1699.83 23.75 2983.17 24.33 326.83 24.42
Minimum of Months 25.00 22.85 101.67 23.45 0.00 23.47
Maximum of Months 269.67 26.52 476.67 24.86 56.00 24.99



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 359.83 23.02 72.67 23.17 13.33 23.10
February 327.83 22.75 47.83 22.95 0.17 22.96
March 264.83 23.12 90.00 23.43 7.00 23.40
April 104.17 24.43 197.50 24.77 18.83 24.92
May 72.83 24.95 222.33 25.07 21.17 25.22
June 30.17 26.84 342.50 24.95 27.33 25.10
July 71.33 26.64 464.50 24.96 69.67 25.16
August 53.33 26.47 488.00 24.71 53.33 24.86
September 55.67 26.51 437.67 24.82 55.67 24.99
October 183.17 23.82 195.17 24.26 16.17 24.37
November 283.67 23.22 136.00 23.59 30.83 23.62
December 415.33 22.67 64.83 22.63 42.17 22.49
             
Annual Sum or Average 2222.17 23.49 2759.00 24.10 355.67 24.20
Minimum of Months 30.17 22.67 47.83 22.63 0.17 22.49
Maximum of Months 415.33 26.84 488.00 25.07 69.67 25.22



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.95 106.83 21.62 106.83 21.40
February 442.50 21.70 77.00 21.48 77.00 21.31
March 434.33 22.42 53.67 22.23 48.67 22.06
April 215.67 23.52 54.83 23.85 2.00 23.83
May 105.67 23.88 89.00 24.64 0.33 24.65
June 28.33 26.33 307.00 24.87 21.67 25.01
July 66.00 25.99 451.17 24.79 61.67 24.93
August 68.00 25.29 470.17 24.52 60.50 24.62
September 84.33 25.26 412.67 24.65 68.83 24.77
October 307.50 22.97 131.50 23.25 32.67 23.19
November 439.33 22.18 132.67 22.03 114.33 21.88
December 497.00 21.26 249.17 20.99 249.17 20.85
             
Annual Sum or Average 3190.67 22.45 2535.67 22.96 843.67 22.83
Minimum of Months 28.33 21.26 53.67 20.99 0.33 20.85
Maximum of Months 502.00 26.33 470.17 24.87 249.17 25.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 431.33 22.78 53.67 22.50 50.83 22.26
February 346.50 22.28 56.50 22.17 40.33 22.00
March 295.17 22.86 70.50 23.00 17.67 22.88
April 99.33 24.35 214.17 24.72 20.83 24.87
May 65.50 25.55 279.00 24.99 32.67 25.19
June 46.50 27.05 409.67 24.88 44.50 25.08
July 78.17 26.69 469.50 24.97 77.17 25.18
August 64.67 26.42 494.00 24.72 62.00 24.90
September 67.17 26.34 442.50 24.82 62.00 25.01
October 202.83 23.48 199.83 24.02 26.00 24.03
November 348.67 22.77 95.83 22.77 59.17 22.66
December 494.17 22.24 126.83 21.89 126.83 21.66
             
Annual Sum or Average 2540.00 23.19 2912.00 23.75 620.00 23.75
Minimum of Months 46.50 22.24 53.67 21.89 17.67 21.66
Maximum of Months 494.17 27.05 494.00 24.99 126.83 25.19



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 247.17 22.97 190.33 23.49 38.50 23.45
February 277.50 22.22 130.17 22.64 27.17 22.50
March 271.17 22.66 115.83 22.97 23.83 22.83
April 149.83 23.77 167.50 24.34 10.83 24.43
May 109.33 23.92 134.67 24.61 3.50 24.65
June 40.50 25.58 284.67 24.84 21.00 24.97
July 72.17 25.86 443.83 24.78 65.50 24.93
August 71.67 25.54 481.50 24.59 64.33 24.71
September 71.83 26.02 436.17 24.81 67.00 24.97
October 172.33 23.83 258.50 24.32 39.67 24.46
November 229.67 23.00 224.00 23.52 57.00 23.45
December 312.17 22.63 168.33 22.80 85.50 22.62
             
Annual Sum or Average 2025.33 23.32 3035.50 23.97 503.83 23.99
Minimum of Months 40.50 22.22 115.83 22.64 3.50 22.50
Maximum of Months 312.17 26.02 481.50 24.84 85.50 24.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 381.17 22.42 92.17 22.36 53.17 22.14
February 363.67 22.16 52.17 22.19 24.67 22.08
March 314.50 22.71 100.17 22.91 26.83 22.78
April 132.00 24.26 198.17 24.64 22.33 24.81
May 92.00 24.83 231.83 24.96 24.17 25.12
June 36.67 26.76 362.83 24.93 32.00 25.10
July 83.17 26.46 464.50 24.97 79.83 25.17
August 66.17 26.12 489.67 24.70 63.83 24.86
September 70.83 26.11 437.83 24.82 69.00 24.98
October 223.50 23.43 195.33 23.96 26.83 24.03
November 317.67 22.67 148.50 22.88 65.17 22.76
December 440.00 22.05 155.17 21.79 141.33 21.57
             
Annual Sum or Average 2521.33 23.06 2928.33 23.71 629.17 23.70
Minimum of Months 36.67 22.05 52.17 21.79 22.33 21.57
Maximum of Months 440.00 26.76 489.67 24.97 141.33 25.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.50 27.00 502.00 27.00 2.50 27.00
February 6.33 27.00 454.00 27.00 6.33 27.00
March 16.50 27.00 514.00 27.00 16.50 27.00
April 295.50 28.81 485.00 28.39 295.50 28.51
May 0.00 0.00 508.00 27.00 0.00 27.00
June 30.33 27.00 496.00 27.00 30.33 27.00
July 269.50 27.00 497.00 27.00 269.50 27.00
August 506.67 27.98 514.00 27.98 506.67 27.98
September 44.50 27.00 485.00 27.00 44.50 27.00
October 37.17 27.00 502.00 27.00 37.17 27.00
November 51.83 27.00 489.00 27.00 51.83 27.00
December 34.67 27.78 497.00 27.12 34.67 27.16
             
Annual Sum or Average 1295.50 27.82 5943.00 27.30 1295.50 27.38
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 506.67 28.81 514.00 28.39 506.67 28.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 189.00 28.98 485.00 28.25 189.00 28.41
May 0.00 0.00 508.00 27.00 0.00 27.00
June 1.17 27.00 496.00 27.00 1.17 27.00
July 27.50 27.00 497.00 27.00 27.50 27.00
August 270.67 28.40 514.00 27.98 270.67 28.09
September 6.33 27.00 485.00 27.00 6.33 27.00
October 2.67 27.00 502.00 27.00 2.67 27.00
November 5.83 27.00 489.00 27.00 5.83 27.00
December 5.50 27.98 497.00 27.03 5.50 27.04
             
Annual Sum or Average 508.67 28.49 5943.00 27.25 508.67 27.34
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 270.67 28.98 514.00 28.25 270.67 28.41



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 11.50 24.57 464.67 26.94 0.00 26.94
February 0.00 0.00 447.67 27.00 0.00 27.00
March 0.00 0.00 501.17 27.00 0.00 27.00
April 172.50 28.97 485.00 28.14 172.50 28.31
May 0.00 0.00 508.00 27.00 0.00 27.00
June 27.00 27.00 496.00 27.00 27.00 27.00
July 111.50 27.00 497.00 27.00 111.50 27.00
August 258.00 28.31 514.00 27.89 258.00 27.99
September 34.67 27.00 485.00 27.00 34.67 27.00
October 12.33 27.00 502.00 27.00 12.33 27.00
November 7.00 27.00 476.17 27.00 7.00 27.00
December 1.00 27.83 414.00 27.01 1.00 27.01
             
Annual Sum or Average 635.50 28.02 5790.67 27.22 624.00 27.30
Minimum of Months 0.00 0.00 414.00 26.94 0.00 26.94
Maximum of Months 258.00 28.97 514.00 28.14 258.00 28.31



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 414.83 27.00 502.00 27.00 414.83 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 29.66 485.00 29.66 485.00 29.66
May 408.50 27.00 508.00 27.00 408.50 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.07 497.00 27.07 497.00 27.07
August 514.00 31.31 514.00 31.31 514.00 31.31
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.02 497.00 27.02 497.00 27.02
             
Annual Sum or Average 5756.33 27.62 5943.00 27.61 5756.33 27.61
Minimum of Months 408.50 27.00 454.00 27.00 408.50 27.00
Maximum of Months 514.00 31.31 514.00 31.31 514.00 31.31



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00001 22.79556 0.81812 19.20534
February 454.00000 27.00022 29.34135 0.89120 21.83103
March 514.00000 27.00003 26.49944 0.91427 22.73576
April 485.00000 28.13931 18.11040 1.11228 31.72160
May 508.00000 27.00000 17.52327 0.15330 5.55515
June 496.00000 27.00000 23.67504 0.26828 6.59703
July 497.00000 27.00047 33.24134 0.38590 8.20338
August 514.00000 27.97037 33.76002 0.69860 16.77258
September 485.00000 27.00067 34.57448 0.29861 6.93359
October 502.00000 27.00010 25.23280 0.89895 22.20388
November 489.00000 27.00014 24.63886 0.91251 22.70796
December 497.00000 27.07284 17.32343 0.87688 21.39296
           
Annual Sum or Average 5943.00000 27.18313 25.53937 0.68394 17.10609
Minimum of Months 454.00000 27.00000 17.32343 0.15330 5.55515
Maximum of Months 514.00000 28.13931 34.57448 1.11228 31.72160



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00001 22.77765 0.74643 16.86030
February 454.00000 27.00021 29.35685 0.79985 18.58388
March 514.00000 27.00003 26.47037 0.81845 19.25540
April 485.00000 27.96502 18.17105 0.98926 26.35454
May 508.00000 27.00000 17.49716 0.10368 5.30595
June 496.00000 27.00000 23.65465 0.20300 5.96418
July 497.00000 27.00030 33.25001 0.28986 6.84856
August 514.00000 27.76156 33.94892 0.49882 11.43706
September 485.00000 27.00059 34.64050 0.24365 6.31876
October 502.00000 27.00010 25.21068 0.82835 19.64882
November 489.00000 27.00013 24.62455 0.80788 18.94535
December 497.00000 27.02016 17.33322 0.72424 16.22992
           
Annual Sum or Average 5943.00000 27.14642 25.55776 0.58575 14.26469
Minimum of Months 454.00000 27.00000 17.33322 0.10368 5.30595
Maximum of Months 514.00000 27.96502 34.64050 0.98926 26.35454



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.94182 22.97398 0.68892 15.42011
February 454.00000 27.00021 29.40099 0.74736 16.96924
March 514.00000 27.00003 26.49139 0.78665 18.28126
April 485.00000 27.83823 18.25354 0.96698 25.60862
May 508.00000 27.00000 17.50870 0.11592 5.43813
June 496.00000 27.00000 23.66526 0.23114 6.28719
July 497.00000 27.00132 33.25424 0.31749 7.26052
August 514.00000 27.67253 34.02598 0.49696 11.62318
September 485.00000 27.00062 34.63468 0.25735 6.51654
October 502.00000 27.00010 25.22691 0.81135 19.15359
November 489.00000 27.00013 24.64446 0.76505 17.65125
December 497.00000 27.00526 17.35229 0.65342 14.28849
           
Annual Sum or Average 5943.00000 27.12230 25.59929 0.56810 13.66885
Minimum of Months 454.00000 26.94182 17.35229 0.11592 5.43813
Maximum of Months 514.00000 27.83823 34.63468 0.96698 25.60862



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99995 25.61923 1.03844 27.80996
February 454.00000 27.00015 31.01720 1.21377 35.94334
March 514.00000 27.00146 25.76938 1.31068 40.84948
April 485.00000 29.66361 16.72575 1.88084 67.79841
May 508.00000 27.00051 26.50517 0.45113 9.34811
June 496.00000 27.00303 29.56300 0.70027 15.34272
July 497.00000 27.07354 36.04589 1.00433 26.51282
August 514.00000 31.31246 32.11676 2.37732 84.41767
September 485.00000 27.00127 38.34287 0.63716 13.66609
October 502.00000 27.00117 27.41613 1.24666 37.61521
November 489.00000 27.00249 25.50139 1.36304 43.60384
December 497.00000 27.02458 17.87673 1.42129 46.66255
           
Annual Sum or Average 5943.00000 27.59939 27.69055 1.22221 37.54140
Minimum of Months 454.00000 26.99995 16.72575 0.45113 9.34811
Maximum of Months 514.00000 31.31246 38.34287 2.37732 84.41767



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.56094 20.54499 0.36820 8.46174
February 454.00000 24.48522 32.71344 0.42868 9.46361
March 514.00000 24.39428 26.07288 0.36391 8.19813
April 485.00000 24.52758 18.69869 0.34906 8.00732
May 508.00000 24.48659 18.09880 -0.5236 11.56746
June 496.00000 24.45330 25.57537 -0.4712 10.59146
July 497.00000 24.62699 45.42845 -0.2643 7.76171
August 514.00000 24.49262 47.90845 -0.2663 7.63703
September 485.00000 24.57848 47.01392 -0.2528 7.93828
October 502.00000 24.62096 26.63217 0.44513 10.05062
November 489.00000 24.62155 26.42303 0.44194 10.08443
December 497.00000 24.60830 14.63362 0.34706 8.21877
           
Annual Sum or Average 5943.00000 24.53775 29.12387 0.07696 8.99643
Minimum of Months 454.00000 24.39428 14.63362 -0.5236 7.63703
Maximum of Months 514.00000 24.62699 47.90845 0.44513 11.56746



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.33725 21.99624 0.33198 7.59343
February 454.00000 24.34236 34.10691 0.41498 8.98178
March 514.00000 24.29166 26.92444 0.36834 8.13171
April 485.00000 24.25478 19.94500 0.33575 7.50978
May 508.00000 24.27434 19.38346 -0.5407 11.42469
June 496.00000 24.18869 27.40767 -0.4941 10.36468
July 497.00000 24.26477 45.62088 -0.3352 7.72730
August 514.00000 24.25379 47.66819 -0.3015 7.29795
September 485.00000 24.32109 47.10528 -0.3227 7.80001
October 502.00000 24.38802 27.81068 0.40749 8.96404
November 489.00000 24.40340 27.16585 0.40346 8.98520
December 497.00000 24.41522 16.19345 0.32098 7.50879
           
Annual Sum or Average 5943.00000 24.31084 30.08488 0.04557 8.52371
Minimum of Months 454.00000 24.18869 16.19345 -0.5407 7.29795
Maximum of Months 514.00000 24.41522 47.66819 0.41498 11.42469



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.00662 23.80714 0.23194 6.53145
February 454.00000 24.04254 36.31447 0.32105 7.33957
March 514.00000 24.12976 28.21180 0.29881 7.09239
April 485.00000 24.18517 20.19483 0.28181 6.81222
May 508.00000 24.21337 19.42630 -0.5863 12.43609
June 496.00000 24.13621 27.17507 -0.5438 11.34079
July 497.00000 24.20475 46.13451 -0.3978 8.66136
August 514.00000 24.17860 48.86235 -0.3839 8.38413
September 485.00000 24.28671 47.33294 -0.3646 8.33950
October 502.00000 24.24688 28.47832 0.34667 7.89852
November 489.00000 24.17198 28.70900 0.31367 7.61983
December 497.00000 23.96321 18.22479 0.17543 5.86184
           
Annual Sum or Average 5943.00000 24.14765 31.04052 -0.0290 8.20566
Minimum of Months 454.00000 23.96321 18.22479 -0.5863 5.86184
Maximum of Months 514.00000 24.28671 48.86235 0.34667 12.43609



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.31779 24.63715 0.04588 6.61871
February 454.00000 23.26739 38.17261 0.11486 6.21092
March 514.00000 23.74210 29.19731 0.19145 6.48940
April 485.00000 24.16116 20.31946 0.27947 6.85295
May 508.00000 24.23501 19.53681 -0.5640 11.97464
June 496.00000 24.20697 27.12449 -0.4893 10.39267
July 497.00000 24.30328 45.94137 -0.3373 7.95902
August 514.00000 24.22697 48.91742 -0.3437 7.87335
September 485.00000 24.32988 47.53750 -0.3341 8.03618
October 502.00000 24.04937 28.94063 0.29095 7.43111
November 489.00000 23.58453 29.93552 0.15661 6.89609
December 497.00000 22.89711 19.31266 -0.1047 6.58291
           
Annual Sum or Average 5943.00000 23.86428 31.58946 -0.0935 7.79301
Minimum of Months 454.00000 22.89711 19.31266 -0.5640 6.21092
Maximum of Months 514.00000 24.32988 48.91742 0.29095 11.97464



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.62183 22.84264 0.12082 5.74621
February 454.00000 23.58350 35.35595 0.19051 6.26018
March 514.00000 23.86230 27.14775 0.22832 6.64557
April 485.00000 24.28018 19.19750 0.33474 7.76402
May 508.00000 24.38548 18.22230 -0.4734 10.42601
June 496.00000 24.42671 25.83762 -0.3286 8.41175
July 497.00000 24.52131 44.19102 -0.1823 6.90580
August 514.00000 24.39100 46.48355 -0.2065 6.89520
September 485.00000 24.44619 46.05337 -0.2486 7.44436
October 502.00000 24.18694 27.48484 0.33549 8.22177
November 489.00000 23.87987 27.59138 0.23319 6.89773
December 497.00000 23.56210 16.90503 0.06224 5.78101
           
Annual Sum or Average 5943.00000 24.09887 29.73893 0.00326 7.29212
Minimum of Months 454.00000 23.56210 16.90503 -0.4734 5.74621
Maximum of Months 514.00000 24.52131 46.48355 0.33549 10.42601



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.91345 21.65327 0.22298 6.83779
February 454.00000 23.73762 34.45307 0.25609 7.32590
March 514.00000 23.98075 26.51625 0.29222 7.65990
April 485.00000 24.38121 18.76504 0.42507 9.73702
May 508.00000 24.49689 17.88123 -0.3270 8.96712
June 496.00000 24.46354 25.62540 -0.2172 7.81309
July 497.00000 24.55854 43.96729 -0.0905 6.89589
August 514.00000 24.40076 46.28261 -0.1329 6.92397
September 485.00000 24.49379 45.66828 -0.1616 7.15858
October 502.00000 24.31725 26.83286 0.41760 9.97085
November 489.00000 23.99461 27.06090 0.28963 7.64164
December 497.00000 23.69048 16.38984 0.11431 6.43008
           
Annual Sum or Average 5943.00000 24.20539 29.22340 0.08870 7.78138
Minimum of Months 454.00000 23.69048 16.38984 -0.3270 6.43008
Maximum of Months 514.00000 24.55854 46.28261 0.42507 9.97085



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.23577 20.62274 0.38619 9.79526
February 454.00000 23.87169 33.77662 0.32312 8.33630
March 514.00000 24.02400 26.33374 0.31788 8.07090
April 485.00000 24.37012 18.88037 0.40560 9.24123
May 508.00000 24.39638 18.15977 -0.4532 10.30704
June 496.00000 24.40125 25.89602 -0.3483 8.71887
July 497.00000 24.51916 44.17014 -0.1787 7.08090
August 514.00000 24.41335 46.32651 -0.1625 6.79846
September 485.00000 24.52826 45.59182 -0.1418 7.12449
October 502.00000 24.45445 26.38972 0.49637 11.71584
November 489.00000 24.30251 26.10434 0.43660 10.33405
December 497.00000 24.12768 15.17121 0.30131 9.00936
           
Annual Sum or Average 5943.00000 24.30600 28.92116 0.11256 8.88006
Minimum of Months 454.00000 23.87169 15.17121 -0.4532 6.79846
Maximum of Months 514.00000 24.52826 46.32651 0.49637 11.71584



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.24879 21.05007 0.33677 8.14480
February 454.00000 24.29477 32.95332 0.42161 9.21651
March 514.00000 24.41308 25.47347 0.45911 10.14757
April 485.00000 24.65526 18.32676 0.59697 13.73856
May 508.00000 24.58570 17.76134 -0.2572 8.42653
June 496.00000 24.57300 25.42587 -0.1070 7.43561
July 497.00000 24.71134 43.53655 0.04178 7.37050
August 514.00000 24.59470 45.64005 0.09031 7.41335
September 485.00000 24.61849 45.32237 -0.0719 7.11578
October 502.00000 24.59473 26.22477 0.53060 12.19111
November 489.00000 24.52751 25.72477 0.49024 11.17052
December 497.00000 24.50099 14.80062 0.37985 8.94013
           
Annual Sum or Average 5943.00000 24.52756 28.49099 0.24053 9.26655
Minimum of Months 454.00000 24.24879 14.80062 -0.2572 7.11578
Maximum of Months 514.00000 24.71134 45.64005 0.59697 13.73856



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.53884 25.39695 -0.1408 6.99104
February 454.00000 22.45092 39.14104 -0.0810 6.23702
March 514.00000 23.10953 29.22512 0.03195 6.47522
April 485.00000 24.09270 19.30479 0.25603 6.89037
May 508.00000 24.34900 17.97998 -0.5089 11.16759
June 496.00000 24.44337 25.19668 -0.3458 8.66943
July 497.00000 24.54511 44.39435 -0.2061 7.16682
August 514.00000 24.36922 47.35861 -0.2622 7.32473
September 485.00000 24.43502 46.32933 -0.2760 7.81026
October 502.00000 23.74465 28.42862 0.21091 7.45846
November 489.00000 22.92568 30.04533 -0.0087 6.93068
December 497.00000 21.97088 19.18730 -0.3261 8.59167
           
Annual Sum or Average 5943.00000 23.58899 30.94577 -0.1394 7.65648
Minimum of Months 454.00000 21.97088 17.97998 -0.5089 6.23702
Maximum of Months 514.00000 24.54511 47.35861 0.25603 11.16759



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 23.30782 23.18704 0.06241 6.81508
February 385.00000 23.13160 36.69387 0.09983 6.84418
March 433.00000 23.66686 27.13537 0.19285 7.37730
April 410.00000 24.50155 17.96333 0.42592 10.07246
May 430.00000 24.61434 17.03988 -0.3112 9.27281
June 418.00000 24.60809 24.41715 -0.1863 8.07681
July 422.00000 24.75197 43.38610 -0.0489 7.34408
August 433.00000 24.56299 46.06521 -0.1091 7.25455
September 410.00000 24.62298 45.32934 -0.1459 7.56079
October 427.00000 24.20935 26.59936 0.36502 9.74302
November 417.00000 23.53384 28.25743 0.15900 7.08030
December 422.00000 22.86252 17.42773 -0.1046 7.15544
           
Annual Sum or Average 5034.00000 24.03603 29.40248 0.03215 7.88741
Minimum of Months 385.00000 22.86252 17.03988 -0.3112 6.81508
Maximum of Months 433.00000 24.75197 46.06521 0.42592 10.07246



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.07268 21.55026 0.35175 10.15438
February 454.00000 23.52128 35.51305 0.24160 8.19870
March 514.00000 23.72109 27.24159 0.23415 7.75363
April 485.00000 24.30121 18.71937 0.36254 8.69401
May 508.00000 24.37293 17.89596 -0.4803 10.91789
June 496.00000 24.41300 25.26680 -0.3694 9.02043
July 497.00000 24.54104 44.38391 -0.2021 7.32522
August 514.00000 24.41255 47.09570 -0.2032 7.09534
September 485.00000 24.54296 45.70513 -0.1495 7.34630
October 502.00000 24.36157 26.51115 0.46630 11.57105
November 489.00000 24.08320 26.90950 0.37734 10.01768
December 497.00000 23.78112 16.02248 0.21175 9.23589
           
Annual Sum or Average 5943.00000 24.18069 29.36382 0.06759 8.95006
Minimum of Months 454.00000 23.52128 16.02248 -0.4803 7.09534
Maximum of Months 514.00000 24.54296 47.09570 0.46630 11.57105



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.39753 23.47050 0.10233 7.18831
February 454.00000 23.13499 37.09236 0.10609 6.59049
March 514.00000 23.65184 27.76677 0.20283 7.37616
April 485.00000 24.42504 18.57529 0.43134 10.04749
May 508.00000 24.51056 17.61911 -0.3355 9.42531
June 496.00000 24.54124 24.92343 -0.1944 7.91989
July 497.00000 24.65290 44.03367 -0.0871 7.35616
August 514.00000 24.48782 46.85042 -0.1198 7.13705
September 485.00000 24.54827 45.82501 -0.1549 7.39665
October 502.00000 24.15515 27.29607 0.36590 9.47808
November 489.00000 23.65842 28.18098 0.20894 7.87042
December 497.00000 22.94140 17.63431 -0.0694 7.34900
           
Annual Sum or Average 5943.00000 24.01443 29.89301 0.03659 7.93408
Minimum of Months 454.00000 22.94140 17.61911 -0.3355 6.59049
Maximum of Months 514.00000 24.65290 46.85042 0.43134 10.04749



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.94513 25.61733 -0.3047 9.44155
February 454.00000 21.75429 40.14226 -0.2684 8.31746
March 514.00000 22.67499 29.80257 -0.0841 7.54016
April 485.00000 24.00181 19.55505 0.23969 7.20355
May 508.00000 24.33576 18.23228 -0.4987 11.31224
June 496.00000 24.46073 25.47488 -0.3104 8.43490
July 497.00000 24.56674 44.52395 -0.1715 7.21373
August 514.00000 24.38240 47.62182 -0.2353 7.28293
September 485.00000 24.43673 46.76523 -0.2591 7.87866
October 502.00000 23.46492 28.80282 0.13972 7.92207
November 489.00000 22.36923 30.76016 -0.1575 8.59059
December 497.00000 21.25709 19.10404 -0.5312 12.99373
           
Annual Sum or Average 5943.00000 23.31492 31.30865 -0.2039 8.68262
Minimum of Months 454.00000 21.25709 18.23228 -0.5312 7.20355
Maximum of Months 514.00000 24.56674 47.62182 0.23969 12.99373



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.95831 23.44215 -0.0403 7.58555
February 454.00000 22.70107 37.47981 -0.0245 7.36842
March 514.00000 23.42655 27.76173 0.13015 7.36755
April 485.00000 24.37705 18.54941 0.42203 10.06747
May 508.00000 24.51203 17.75548 -0.3037 9.02668
June 496.00000 24.52238 25.20195 -0.1589 7.71320
July 497.00000 24.64705 44.13090 -0.0293 7.27117
August 514.00000 24.47792 47.05059 -0.0852 7.04361
September 485.00000 24.52600 46.13648 -0.1359 7.40607
October 502.00000 24.01275 27.24839 0.32744 9.63865
November 489.00000 23.14493 28.91189 0.05469 7.32695
December 497.00000 22.25146 17.99263 -0.2762 9.25702
           
Annual Sum or Average 5943.00000 23.80419 30.08951 -0.0106 8.09061
Minimum of Months 454.00000 22.25146 17.75548 -0.3037 7.04361
Maximum of Months 514.00000 24.64705 47.05059 0.42203 10.06747



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.64832 21.52177 0.22447 9.78411
February 454.00000 22.99320 36.16533 0.08997 8.33989
March 514.00000 23.40251 27.72602 0.14242 7.97553
April 485.00000 24.20972 18.98669 0.34688 8.92806
May 508.00000 24.34318 18.17584 -0.4746 11.22757
June 496.00000 24.43197 25.54307 -0.3337 8.78638
July 497.00000 24.55927 44.53025 -0.1686 7.41510
August 514.00000 24.42028 47.39715 -0.1780 7.14446
September 485.00000 24.53733 46.20154 -0.1343 7.50982
October 502.00000 24.15461 26.83676 0.41129 11.32418
November 489.00000 23.69505 27.40648 0.26440 9.46015
December 497.00000 23.27380 15.84549 0.05028 9.60321
           
Annual Sum or Average 5943.00000 23.97841 29.65436 0.01829 8.96390
Minimum of Months 454.00000 22.99320 15.84549 -0.4746 7.14446
Maximum of Months 514.00000 24.55927 47.39715 0.41129 11.32418



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.88308 23.60783 -0.0383 8.34622
February 454.00000 22.54377 37.85054 -0.0525 7.36304
March 514.00000 23.29390 28.27501 0.10660 7.77633
April 485.00000 24.34980 18.83536 0.41810 10.19775
May 508.00000 24.49267 17.90084 -0.3273 9.67577
June 496.00000 24.54739 25.24845 -0.1639 7.97499
July 497.00000 24.65851 44.21417 -0.0592 7.56502
August 514.00000 24.48934 47.17220 -0.0981 7.28537
September 485.00000 24.54742 46.28707 -0.1393 7.52592
October 502.00000 23.93104 27.63374 0.30863 9.59457
November 489.00000 23.22033 28.72265 0.08969 8.30330
December 497.00000 22.31089 17.52096 -0.2476 9.63648
           
Annual Sum or Average 5943.00000 23.78052 30.22316 -0.0176 8.44138
Minimum of Months 454.00000 22.31089 17.52096 -0.3273 7.28537
Maximum of Months 514.00000 24.65851 47.17220 0.41810 10.19775



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.671526E+11 142405.74 17-JAN-15:30 312.19 0.442588E+12 0.00 0.509740E+12 2.45 7.57 18-JAN-14:40 0.00 0.00
February 0.285266E+11 102879.61 21-FEB-15:30 206.18 0.164483E+12 0.00 0.193010E+12 1.58 7.45 21-FEB-15:30 0.00 0.00
March 0.658225E+11 151690.22 17-MAR-12:50 350.75 0.421225E+12 0.00 0.487047E+12 2.64 7.57 15-MAR-13:40 0.00 0.00
April 0.127410E+12 148683.99 25-APR-17:00 592.55 0.873578E+12 0.00 0.100099E+13 4.92 7.57 17-APR-17:10 0.00 0.00
May 0.149200E+12 148808.74 30-MAY-09:20 543.25 0.103707E+13 0.00 0.118627E+13 4.75 7.57 30-MAY-19:00 0.00 0.00
June 0.178781E+12 160535.00 17-JUN-13:20 674.75 0.123604E+13 0.00 0.141482E+13 6.00 7.58 19-JUN-04:13 0.00 0.00
July 0.189087E+12 164496.66 15-JUL-10:20 693.26 0.128915E+13 0.00 0.147824E+13 5.85 7.57 01-JUL-09:40 0.00 0.00
August 0.189649E+12 161359.33 29-AUG-18:20 694.14 0.130289E+13 0.00 0.149254E+13 5.89 7.57 24-AUG-19:13 0.00 0.00
September 0.162514E+12 159136.59 12-SEP-07:30 552.54 0.112511E+13 0.00 0.128763E+13 4.97 7.57 28-SEP-08:20 0.00 0.00
October 0.108895E+12 159567.66 03-OCT-16:50 464.48 0.732049E+12 0.00 0.840944E+12 3.78 7.57 19-OCT-12:05 0.00 0.00
November 0.673163E+11 153440.60 01-NOV-16:50 337.36 0.440489E+12 0.00 0.507805E+12 2.64 7.57 20-NOV-17:00 0.00 0.00
December 0.459972E+11 153831.43 22-DEC-16:30 285.15 0.277407E+12 0.00 0.323405E+12 2.03 7.57 22-DEC-14:30 0.00 0.00
                         
Annual Sum or Average 0.138035E+13     5706.60 0.934208E+13 0.00 0.107224E+14 3.97     0.00 0.00
Minimum of Months 0.285266E+11 102879.61   206.18 0.164483E+12 0.00 0.193010E+12 1.58 7.45   0.00 0.00
Maximum of Months 0.189649E+12 164496.66   694.14 0.130289E+13 0.00 0.149254E+13 6.00 7.58   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.159406E+10 108115.70 31-JAN-15:05 6.08 0.109483E+11 0.00 0.125423E+11 0.05 7.45 31-JAN-15:05 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.137184E+10 105020.84 23-MAR-14:05 4.75 0.967184E+10 0.00 0.110437E+11 0.04 7.46 16-MAR-14:05 0.00 0.00
April 0.335551E+11 108306.76 03-APR-12:05 106.42 0.242207E+12 0.00 0.275762E+12 1.06 7.49 03-APR-12:05 0.00 0.00
May 0.537894E+11 110390.67 25-MAY-12:05 170.17 0.388482E+12 0.00 0.442271E+12 1.64 7.51 25-MAY-12:05 0.00 0.00
June 0.922441E+11 132660.43 19-JUN-14:50 271.92 0.667989E+12 0.00 0.760233E+12 2.72 7.50 05-JUN-15:10 0.00 0.00
July 0.836834E+11 160171.74 18-JUL-05:03 235.84 0.591107E+12 0.00 0.674791E+12 2.23 7.53 14-JUL-05:03 0.00 0.00
August 0.896971E+11 160145.86 01-AUG-05:02 250.64 0.634190E+12 0.00 0.723887E+12 2.37 7.50 24-AUG-15:20 0.00 0.00
September 0.646133E+11 153407.34 12-SEP-05:03 184.96 0.457792E+12 0.00 0.522405E+12 1.81 7.47 28-SEP-15:20 0.00 0.00
October 0.269180E+11 117760.02 03-OCT-11:00 81.56 0.192597E+12 0.00 0.219515E+12 0.78 7.52 10-OCT-08:55 0.00 0.00
November 0.346714E+10 113369.28 02-NOV-14:05 12.25 0.244085E+11 0.00 0.278756E+11 0.12 7.52 02-NOV-14:05 0.00 0.00
December 0.124429E+09 86903.84 22-DEC-16:00 0.50 0.834720E+09 0.00 0.959149E+09 0.00 7.21 22-DEC-16:00 0.00 0.00
                         
Annual Sum or Average 0.451058E+12     1325.07 0.322023E+13 0.00 0.367128E+13 1.07     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.922441E+11 160171.74   271.92 0.667989E+12 0.00 0.760233E+12 2.72 7.53   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.439980E+11 744.00 43776.24 02-JAN-12:10 232405.61 31-JAN-17:30 20.48 19.62 14.32
February 0.196643E+11 672.00 43776.24 06-FEB-14:00 184202.30 18-FEB-14:05 19.66 18.48 14.32
March 0.596797E+11 744.00 43776.24 01-MAR-10:00 522965.50 16-MAR-16:00 24.21 20.62 14.32
April 0.106049E+12 720.00 43776.24 01-APR-07:05 628853.07 25-APR-18:15 37.20 27.93 14.32
May 0.110613E+12 744.00 43776.24 01-MAY-00:10 355760.12 31-MAY-23:15 30.80 27.81 14.32
June 0.113468E+12 720.00 43776.24 01-JUN-00:05 516289.04 30-JUN-23:13 41.25 34.36 14.32
July 0.117250E+12 744.00 43776.24 01-JUL-00:05 711619.72 13-JUL-17:53 45.93 35.32 14.32
August 0.117250E+12 744.00 43776.24 01-AUG-00:05 739805.22 05-AUG-16:43 48.65 35.78 14.32
September 0.112995E+12 720.00 43776.24 01-SEP-00:10 338217.29 04-SEP-10:20 32.89 29.36 14.32
October 0.847264E+11 744.00 43776.24 01-OCT-00:10 500831.53 03-OCT-08:30 27.75 24.01 14.32
November 0.598819E+11 720.00 43776.24 01-NOV-00:10 541061.33 09-NOV-17:00 24.21 20.48 14.32
December 0.480202E+11 744.00 43776.24 01-DEC-09:50 597905.96 25-DEC-16:01 23.79 19.66 14.32
                   
Annual Sum or Average 0.993596E+12 8760.00         31.47 26.16 14.32
Minimum of Months 0.196643E+11 672.00 43776.24   184202.30   19.66 18.48 14.32
Maximum of Months 0.117250E+12 744.00 43776.24   739805.22   48.65 35.78 14.32



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.563790E+09 245.33 2430.43 26-JAN-14:00 1228644.01 30-JAN-15:40 22.00 21.17 21.64
February 0.183104E+09 137.78 1571.37 21-FEB-15:05 877050.92 21-FEB-15:30 21.44 21.09 14.71
March 0.994933E+09 255.99 16791.28 14-MAR-14:00 1275759.47 17-MAR-13:05 21.91 21.11 23.60
April 0.218734E+10 421.25 16791.28 10-APR-13:00 1243627.64 27-APR-15:30 22.90 21.07 38.86
May 0.259879E+10 496.82 16791.28 04-MAY-14:20 1249427.32 24-MAY-16:10 23.43 21.28 40.41
June 0.140102E+11 606.64 16791.28 01-JUN-08:00 1250306.97 20-JUN-07:30 23.94 21.40 51.42
July 0.281186E+11 663.72 16791.28 01-JUL-13:50 1243574.98 03-JUL-07:50 24.95 22.56 51.16
August 0.283497E+11 656.07 16791.28 01-AUG-00:23 1220450.75 26-AUG-10:00 24.87 22.48 51.38
September 0.232550E+11 538.14 16791.28 01-SEP-03:03 1245048.73 28-SEP-09:00 24.58 22.44 42.73
October 0.620420E+10 392.99 16791.28 01-OCT-10:00 1262920.53 18-OCT-12:50 22.72 21.32 33.06
November 0.177398E+10 246.92 16791.28 01-NOV-10:00 1254872.48 01-NOV-17:00 21.98 21.12 23.48
December 0.248494E+09 192.40 2257.92 22-DEC-15:05 1246587.47 22-DEC-16:30 21.63 21.11 17.87
                   
Annual Sum or Average 0.108488E+12 4854.04         23.04 21.52 34.30
Minimum of Months 0.183104E+09 137.78 1571.37   877050.92   21.44 21.07 14.71
Maximum of Months 0.283497E+11 663.72 16791.28   1275759.47   24.95 22.56 51.42



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 8619609.11 2.67 1268.52 31-JAN-15:05 1089591.52 27-JAN-15:30 22.00 21.98 0.20
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 21.44 21.44 0.00
March 22297418.96 2.25 16791.28 17-MAR-15:30 1140393.51 17-MAR-15:30 21.91 21.89 0.17
April 0.854753E+09 92.25 16791.28 10-APR-13:00 1180229.29 24-APR-14:20 22.90 22.34 7.30
May 0.109037E+10 151.75 16791.28 04-MAY-14:20 1185691.60 18-MAY-13:40 23.43 22.55 11.61
June 0.968432E+10 247.24 16791.28 01-JUN-08:20 1182848.21 05-JUN-10:40 23.94 22.58 19.52
July 0.146837E+11 258.80 16791.28 03-JUL-11:30 1184959.17 03-JUL-10:20 24.95 23.66 18.80
August 0.157749E+11 268.73 16791.28 01-AUG-05:02 1109666.69 25-AUG-08:15 24.87 23.55 19.73
September 0.111696E+11 192.95 16791.28 01-SEP-05:07 1170281.22 05-SEP-07:50 24.58 23.59 14.63
October 0.301768E+10 74.06 16791.28 02-OCT-07:20 1114748.97 20-OCT-12:30 22.72 22.34 5.64
November 0.208640E+09 7.83 16791.28 01-NOV-12:05 1108370.00 09-NOV-13:40 21.98 21.93 0.61
December 618297.44 0.17 1030.50 22-DEC-16:00 1070265.96 22-DEC-16:00 21.63 21.63 0.01
                   
Annual Sum or Average 0.565155E+11 1298.69         23.04 22.47 8.23
Minimum of Months 0.00 0.00 0.00   0.00   21.44 21.44 0.00
Maximum of Months 0.157749E+11 268.73 16791.28   1185691.60   24.95 23.66 19.73



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.773031E+10 0.00 96.94 808979.61 02-JAN-06:03 0.00 28.52 35.32 0.01 0.00 0.00 0.50 02-JAN-06:03
February 0.805807E+10 0.00 110.02 593950.10 13-FEB-06:03 0.00 29.11 37.63 0.02 0.00 0.00 0.37 13-FEB-06:03
March 0.795739E+10 0.00 60.18 768533.37 27-MAR-05:03 0.00 31.64 35.59 0.02 0.00 0.00 0.48 27-MAR-05:03
April 12883372.82 0.00 2.42 9692.30 21-APR-06:10 0.00 35.95 36.10 0.00 0.00 0.00 0.01 21-APR-06:10
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 35.34 35.34 0.00 0.00 0.00 0.00 01-MAY-00:10
June 0.00 0.00 0.00 0.00 01-JUN-00:05 0.00 35.34 35.34 0.00 0.00 0.00 0.00 01-JUN-00:05
July 0.00 0.00 0.00 0.00 01-JUL-00:05 0.00 35.34 35.34 0.00 0.00 0.00 0.00 01-JUL-00:05
August 0.00 0.00 0.00 0.00 01-AUG-00:05 0.00 35.34 35.34 0.00 0.00 0.00 0.00 01-AUG-00:05
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 35.34 35.34 0.00 0.00 0.00 0.00 01-SEP-00:10
October 0.137476E+10 0.00 24.48 135031.84 25-OCT-06:10 0.00 31.64 33.33 0.00 0.00 0.00 0.08 25-OCT-06:10
November 0.419354E+10 0.00 72.67 697355.66 24-NOV-06:03 0.00 28.32 33.64 0.01 0.00 0.00 0.43 24-NOV-06:03
December 0.312571E+11 0.00 181.07 915238.40 07-DEC-06:01 0.00 30.90 42.70 0.07 0.00 0.01 0.57 07-DEC-06:01
                           
Annual Sum or Average 0.605841E+11 0.00 547.77     0.00 32.75 35.91 0.01 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 28.32 33.33 0.00 0.00 0.00 0.00  
Maximum of Months 0.312571E+11 0.00 181.07 915238.40   0.00 35.95 42.70 0.07 0.00 0.01 0.57  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 20.48 20.48 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 19.66 19.66 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 24.21 24.21 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 37.20 37.20 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 30.80 30.80 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:05 0.00 41.25 41.25 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:05 0.00 45.93 45.93 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:05 0.00 48.65 48.65 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 32.89 32.89 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 27.75 27.75 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 24.21 24.21 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 23.79 23.79 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 31.47 31.47 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 19.66 19.66 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 48.65 48.65 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.400784E+11 0.00 290.75 0.400672E+11 0.00 0.00 0.00 0.00 96948.95 31-JAN-16:50 96948.95 31-JAN-16:50 0.00 0.00 0.00
February 0.111162E+11 0.00 176.90 0.111162E+11 0.00 0.00 0.00 0.00 64164.77 21-FEB-15:00 64164.77 21-FEB-15:00 0.00 0.00 0.00
March 0.435185E+11 0.00 332.88 0.435185E+11 0.00 0.00 0.00 0.00 107628.51 20-MAR-14:50 107628.51 20-MAR-14:50 0.00 0.00 0.00
April 0.112700E+12 0.00 567.52 0.112700E+12 0.00 0.00 0.00 0.00 137615.82 24-APR-15:00 137615.82 24-APR-15:00 0.00 0.00 0.00
May 0.123596E+12 0.00 518.92 0.123596E+12 0.00 0.00 0.00 0.00 127987.22 15-MAY-15:20 127987.22 15-MAY-15:20 0.00 0.00 0.00
June 0.166666E+12 0.00 627.74 0.166666E+12 0.00 0.00 0.00 0.00 152306.17 17-JUN-05:02 152306.17 17-JUN-05:02 0.00 0.00 0.00
July 0.173992E+12 0.00 645.50 0.163579E+12 0.00 0.00 0.00 0.00 280108.03 18-JUL-05:03 159330.51 10-JUL-04:02 0.00 0.00 0.00
August 0.193608E+12 0.00 658.66 0.182811E+12 0.00 0.00 0.00 0.00 260301.02 01-AUG-05:02 173030.84 28-AUG-05:01 0.00 0.00 0.00
September 0.138211E+12 0.00 524.37 0.129106E+12 0.00 0.00 0.00 0.00 241536.98 08-SEP-05:02 160101.82 19-SEP-05:02 0.00 0.00 0.00
October 0.850340E+11 0.00 434.90 0.836065E+11 0.00 0.00 0.00 0.00 180156.81 03-OCT-04:12 157127.26 02-OCT-04:23 0.00 0.00 0.00
November 0.467024E+11 0.00 315.74 0.440342E+11 0.00 0.00 0.00 0.00 135727.76 13-NOV-05:12 108093.11 20-NOV-16:00 0.00 0.00 0.00
December 0.297061E+11 0.00 256.88 0.297061E+11 0.00 0.00 0.00 0.00 95635.41 22-DEC-16:30 95635.41 22-DEC-16:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.116493E+13 0.00 5350.76 0.113051E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.111162E+11 0.00 176.90 0.111162E+11 0.00 0.00 0.00 0.00 64164.77   64164.77   0.00 0.00 0.00
Maximum of Months 0.193608E+12 0.00 658.66 0.182811E+12 0.00 0.00 0.00 0.00 280108.03   173030.84   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.347440E+12 0.00 293.16 0.347320E+12 0.00 0.00 0.00 0.00 855584.63 31-JAN-16:30 855584.63 31-JAN-16:30 0.00 0.00 0.00
February 0.140922E+12 0.00 192.37 0.140922E+12 0.00 0.00 0.00 0.00 580089.64 21-FEB-15:05 580089.64 21-FEB-15:05 0.00 0.00 0.00
March 0.331063E+12 0.00 322.94 0.331063E+12 0.00 0.00 0.00 0.00 910320.52 16-MAR-15:50 910320.52 16-MAR-15:50 0.00 0.00 0.00
April 0.851962E+12 0.00 438.68 0.851962E+12 0.00 0.00 0.00 0.00 1199266.85 14-APR-15:20 1199266.85 14-APR-15:20 0.00 0.00 0.00
May 0.111208E+13 0.00 488.52 0.111208E+13 0.00 0.00 0.00 0.00 1209990.38 18-MAY-15:10 1209990.38 18-MAY-15:10 0.00 0.00 0.00
June 0.148257E+13 0.00 559.98 0.148257E+13 0.00 0.00 0.00 0.00 1414742.62 09-JUN-05:02 1414742.62 09-JUN-05:02 0.00 0.00 0.00
July 0.141927E+13 0.00 552.37 0.134601E+13 0.00 0.00 0.00 0.00 2670412.88 18-JUL-05:03 1491611.03 07-JUL-05:02 0.00 0.00 0.00
August 0.144322E+13 0.00 546.08 0.137549E+13 0.00 0.00 0.00 0.00 2349338.88 01-AUG-05:02 1508331.81 28-AUG-05:01 0.00 0.00 0.00
September 0.119826E+13 0.00 470.24 0.112308E+13 0.00 0.00 0.00 0.00 2311933.47 08-SEP-05:02 1481274.09 19-SEP-05:02 0.00 0.00 0.00
October 0.703571E+12 0.00 397.56 0.691608E+12 0.00 0.00 0.00 0.00 1717620.31 03-OCT-04:12 1292920.89 02-OCT-05:02 0.00 0.00 0.00
November 0.343287E+12 0.00 299.88 0.330091E+12 0.00 0.00 0.00 0.00 977721.89 13-NOV-05:12 932070.46 01-NOV-15:20 0.00 0.00 0.00
December 0.214854E+12 0.00 236.72 0.214854E+12 0.00 0.00 0.00 0.00 744229.52 22-DEC-15:05 744229.52 22-DEC-15:05 0.00 0.00 0.00
                               
Annual Sum or Average 0.958849E+13 0.00 4798.51 0.934704E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.140922E+12 0.00 192.37 0.140922E+12 0.00 0.00 0.00 0.00 580089.64   580089.64   0.00 0.00 0.00
Maximum of Months 0.148257E+13 0.00 559.98 0.148257E+13 0.00 0.00 0.00 0.00 2670412.88   1508331.81   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.283735E+11 0.00 281.54 0.283656E+11 0.00 0.00 0.00 0.00 89351.45 31-JAN-16:30 89351.45 31-JAN-16:30 0.00 0.00 0.00
February 0.601059E+10 0.00 163.67 0.601059E+10 0.00 0.00 0.00 0.00 46684.32 22-FEB-16:00 46684.32 22-FEB-16:00 0.00 0.00 0.00
March 0.300810E+11 0.00 304.77 0.300810E+11 0.00 0.00 0.00 0.00 103528.63 16-MAR-15:30 103528.63 16-MAR-15:30 0.00 0.00 0.00
April 0.931120E+11 0.00 437.97 0.931120E+11 0.00 0.00 0.00 0.00 142760.61 14-APR-15:20 142760.61 14-APR-15:20 0.00 0.00 0.00
May 0.123028E+12 0.00 488.10 0.123028E+12 0.00 0.00 0.00 0.00 144111.97 18-MAY-15:20 144111.97 18-MAY-15:20 0.00 0.00 0.00
June 0.169010E+12 0.00 569.50 0.169010E+12 0.00 0.00 0.00 0.00 170210.03 28-JUN-14:50 170210.03 28-JUN-14:50 0.00 0.00 0.00
July 0.161834E+12 0.00 567.17 0.154244E+12 0.00 0.00 0.00 0.00 282624.52 18-JUL-05:03 168659.17 17-JUL-04:12 0.00 0.00 0.00
August 0.161121E+12 0.00 554.78 0.154140E+12 0.00 0.00 0.00 0.00 277698.34 01-AUG-05:02 178814.72 28-AUG-05:01 0.00 0.00 0.00
September 0.130021E+12 0.00 478.04 0.122655E+12 0.00 0.00 0.00 0.00 257179.95 08-SEP-05:02 164313.92 19-SEP-05:02 0.00 0.00 0.00
October 0.701805E+11 0.00 390.03 0.690767E+11 0.00 0.00 0.00 0.00 191406.78 03-OCT-04:12 147884.02 02-OCT-05:02 0.00 0.00 0.00
November 0.288837E+11 0.00 284.40 0.279932E+11 0.00 0.00 0.00 0.00 105529.25 01-NOV-15:20 105529.25 01-NOV-15:20 0.00 0.00 0.00
December 0.125874E+11 0.00 194.82 0.125874E+11 0.00 0.00 0.00 0.00 75608.92 22-DEC-16:30 75608.92 22-DEC-16:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.101424E+13 0.00 4714.78 0.990303E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.601059E+10 0.00 163.67 0.601059E+10 0.00 0.00 0.00 0.00 46684.32   46684.32   0.00 0.00 0.00
Maximum of Months 0.169010E+12 0.00 569.50 0.169010E+12 0.00 0.00 0.00 0.00 282624.52   178814.72   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.246559E+11 0.00 222.99 0.246519E+11 0.00 0.00 0.00 0.00 83325.99 16-JAN-12:20 83325.99 16-JAN-12:20 0.00 0.00 0.00
February 0.433835E+10 0.00 92.02 0.431611E+10 0.00 0.00 0.00 0.00 50183.89 17-FEB-06:03 47383.34 10-FEB-06:03 0.00 0.00 0.00
March 0.238974E+11 0.00 242.66 0.238921E+11 0.00 0.00 0.00 0.00 62904.85 20-MAR-13:20 62904.85 20-MAR-13:20 0.00 0.00 0.00
April 0.579223E+11 0.00 343.07 0.579223E+11 0.00 0.00 0.00 0.00 94211.98 25-APR-03:50 94211.98 25-APR-03:50 0.00 0.00 0.00
May 0.711567E+11 0.00 398.11 0.711567E+11 0.00 0.00 0.00 0.00 114979.42 29-MAY-18:27 114979.42 29-MAY-18:27 0.00 0.00 0.00
June 0.868675E+11 0.00 419.38 0.868675E+11 0.00 0.00 0.00 0.00 108670.38 17-JUN-04:03 108670.38 17-JUN-04:03 0.00 0.00 0.00
July 0.935453E+11 0.00 441.34 0.902792E+11 0.00 0.00 0.00 0.00 159468.80 14-JUL-04:33 115266.94 04-JUL-18:54 0.00 0.00 0.00
August 0.105143E+12 0.00 481.33 0.101123E+12 0.00 0.00 0.00 0.00 152774.24 01-AUG-03:02 115545.45 27-AUG-20:17 0.00 0.00 0.00
September 0.888709E+11 0.00 435.71 0.845644E+11 0.00 0.00 0.00 0.00 149135.94 02-SEP-03:02 107937.14 18-SEP-03:02 0.00 0.00 0.00
October 0.559904E+11 0.00 351.75 0.554512E+11 0.00 0.00 0.00 0.00 114747.35 15-OCT-13:15 114747.35 15-OCT-13:15 0.00 0.00 0.00
November 0.298360E+11 0.00 237.87 0.276546E+11 0.00 0.00 0.00 0.00 103586.05 13-NOV-05:42 84212.27 19-NOV-15:00 0.00 0.00 0.00
December 0.132625E+11 0.00 160.92 0.132602E+11 0.00 0.00 0.00 0.00 76991.29 24-DEC-14:40 76991.29 24-DEC-14:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.655486E+12 0.00 3827.13 0.641139E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.433835E+10 0.00 92.02 0.431611E+10 0.00 0.00 0.00 0.00 50183.89   47383.34   0.00 0.00 0.00
Maximum of Months 0.105143E+12 0.00 481.33 0.101123E+12 0.00 0.00 0.00 0.00 159468.80   115545.45   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.290146E+11 0.117469E+11 716.67 0.289859E+11 28664900.21 0.00 0.46 27-JAN-16:00 0.00 20-JAN-21:20 135188.37 27-JAN-16:00 135188.37 27-JAN-16:00 129.61 09-JAN-12:00 50792.86 27-JAN-16:00 0.00
February 0.101614E+11 0.530922E+10 481.36 0.957710E+10 0.584334E+09 0.00 0.29 18-FEB-14:00 0.00 12-FEB-14:20 100916.56 18-FEB-14:00 87817.27 18-FEB-15:00 13982.29 18-FEB-14:00 29051.41 18-FEB-14:00 0.00
March 0.193547E+12 0.610346E+11 722.34 0.189645E+12 0.390187E+10 0.00 0.91 15-MAR-12:40 0.00 04-MAR-22:50 316930.05 17-MAR-15:20 316930.05 17-MAR-15:20 25921.51 17-MAR-10:00 107047.36 16-MAR-12:40 0.00
April 0.671619E+12 0.230233E+12 720.00 0.669874E+12 0.174440E+10 0.00 1.00 01-APR-09:10 0.03 30-APR-24:00 376228.52 15-APR-09:00 376228.52 15-APR-09:00 34192.26 16-APR-06:23 139440.44 14-APR-16:10 0.00
May 0.217138E+12 0.797727E+11 743.50 0.217138E+12 469821.18 0.00 0.67 31-MAY-23:10 0.01 26-MAY-03:10 213492.39 31-MAY-23:10 213492.39 31-MAY-23:10 99.91 11-MAY-02:30 75902.33 31-MAY-23:10 0.00
June 0.518437E+12 0.195153E+12 720.00 0.518428E+12 9087349.09 0.00 0.83 30-JUN-23:13 0.03 21-JUN-06:00 306092.81 30-JUN-23:57 306092.81 30-JUN-23:57 2787.59 04-JUN-05:00 108558.90 16-JUN-16:00 0.00
July 0.870333E+12 0.295004E+12 744.00 0.787202E+12 0.831307E+11 0.00 1.00 08-JUL-20:25 0.29 01-JUL-06:00 467543.62 14-JUL-01:00 391570.33 31-JUL-24:00 312897.41 14-JUL-01:00 139971.79 05-JUL-16:00 0.00
August 0.106368E+13 0.342460E+12 744.00 0.932815E+12 0.130861E+12 0.00 1.00 01-AUG-00:05 0.37 31-AUG-23:53 451581.52 09-AUG-18:30 413024.51 27-AUG-13:34 260887.01 28-AUG-17:00 155095.75 25-AUG-16:10 0.00
September 0.265972E+12 0.906294E+11 679.30 0.239486E+12 0.264868E+11 0.00 0.55 04-SEP-10:20 0.01 27-SEP-04:53 233665.76 04-SEP-10:13 174705.80 30-SEP-23:10 111565.53 04-SEP-10:00 63953.40 04-SEP-10:20 0.00
October 0.251066E+12 0.838948E+11 717.17 0.240033E+12 0.110321E+11 0.00 0.79 03-OCT-08:30 0.00 10-OCT-02:43 336596.21 03-OCT-08:30 228622.38 16-OCT-10:05 128231.86 03-OCT-02:55 94559.68 03-OCT-08:30 0.00
November 0.202931E+12 0.620182E+11 685.21 0.175642E+12 0.272887E+11 0.00 0.97 09-NOV-13:00 0.01 02-NOV-02:70 320010.05 09-NOV-13:05 320010.05 09-NOV-13:05 171810.90 12-NOV-14:55 113919.33 09-NOV-17:00 0.00
December 0.202669E+12 0.643566E+11 737.31 0.202282E+12 0.386844E+09 0.00 1.00 02-DEC-13:00 0.01 13-DEC-05:10 347312.46 25-DEC-13:52 347312.46 25-DEC-13:52 18426.34 13-DEC-11:20 116806.81 25-DEC-16:00 0.00
                                       
Annual Sum or Average 0.449656E+13 0.152161E+13 8410.85 0.421111E+13 0.285455E+12 0.00                         0.00
Minimum of Months 0.101614E+11 0.530922E+10 481.36 0.957710E+10 469821.18 0.00 0.29   0.00   100916.56   87817.27   99.91   29051.41   0.00
Maximum of Months 0.106368E+13 0.342460E+12 744.00 0.932815E+12 0.130861E+12 0.00 1.00   0.37   467543.62   413024.51   312897.41   155095.75   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.547763E+10 0.138425E+10 744.00 0.547443E+10 3196841.55 0.00 0.41 29-JAN-17:12 0.19 21-JAN-08:00 2840.74 29-JAN-17:15 2840.74 29-JAN-17:15 97.66 09-JAN-11:20 942.24 31-JAN-17:00 0.00
February 0.940569E+10 0.207897E+10 672.00 0.936189E+10 43797068.88 0.00 0.55 25-FEB-18:10 0.42 08-FEB-07:10 4566.17 20-FEB-17:03 4545.75 20-FEB-17:08 171.85 16-FEB-10:20 1045.51 22-FEB-17:00 0.00
March 0.157473E+11 0.363961E+10 744.00 0.157357E+11 11591315.90 0.00 0.94 31-MAR-24:00 0.63 07-MAR-08:00 7721.38 31-MAR-24:00 7721.38 31-MAR-24:00 212.14 06-MAR-11:05 2074.09 16-MAR-16:00 0.00
April 0.199920E+11 0.574688E+10 720.00 0.199920E+11 0.00 0.00 1.00 01-APR-09:00 0.37 30-APR-23:05 8286.92 26-APR-18:50 8286.92 26-APR-18:50 0.00 11-APR-16:00 2875.93 14-APR-16:10 0.00
May 0.630701E+10 0.212992E+10 744.00 0.630701E+10 -0.0 0.00 0.59 31-MAY-23:15 0.26 13-MAY-06:30 4064.96 31-MAY-23:55 4064.96 31-MAY-23:55 0.00 02-MAY-12:00 1376.66 31-MAY-23:15 0.00
June 0.112014E+11 0.412853E+10 720.00 0.111999E+11 1546834.43 0.00 0.79 30-JUN-23:13 0.49 21-JUN-06:10 6001.18 30-JUN-24:00 6001.18 30-JUN-24:00 92.77 30-JUN-10:10 2316.54 16-JUN-16:00 0.00
July 0.167090E+11 0.572072E+10 744.00 0.165582E+11 0.150805E+09 0.00 1.00 02-JUL-15:52 0.69 01-JUL-06:10 7925.85 31-JUL-23:53 7912.67 31-JUL-23:57 413.29 13-JUL-18:00 2983.31 02-JUL-18:00 0.00
August 0.213937E+11 0.699834E+10 744.00 0.212431E+11 0.150638E+09 0.00 1.00 01-AUG-08:40 0.36 31-AUG-24:00 8769.85 28-AUG-16:45 8358.86 20-AUG-23:50 594.45 28-AUG-16:15 3186.17 25-AUG-16:10 0.00
September 0.628059E+10 0.201055E+10 720.00 0.614313E+10 0.137459E+09 0.00 0.54 30-SEP-24:00 0.25 22-SEP-06:10 4063.91 30-SEP-24:00 4063.91 30-SEP-24:00 298.04 11-SEP-15:10 1227.77 30-SEP-23:20 0.00
October 0.111175E+11 0.302567E+10 744.00 0.110869E+11 30540408.04 0.00 0.74 15-OCT-17:10 0.44 25-OCT-06:20 5892.89 31-OCT-24:00 5892.89 31-OCT-24:00 309.15 03-OCT-09:40 1855.21 15-OCT-17:10 0.00
November 0.154143E+11 0.356988E+10 720.00 0.153653E+11 48977757.31 0.00 0.90 09-NOV-17:00 0.63 18-NOV-07:25 6839.71 26-NOV-16:53 6839.71 26-NOV-16:53 404.98 13-NOV-16:10 2199.60 09-NOV-16:50 0.00
December 0.206259E+11 0.464366E+10 744.00 0.206254E+11 481613.58 0.00 1.00 01-DEC-14:50 0.85 14-DEC-07:10 8366.15 28-DEC-17:00 8366.15 28-DEC-17:00 71.24 13-DEC-11:20 2418.38 25-DEC-16:00 0.00
                                       
Annual Sum or Average 0.159672E+12 0.450770E+11 8760.00 0.159093E+12 0.579034E+09 0.00                         0.00
Minimum of Months 0.547763E+10 0.138425E+10 672.00 0.547443E+10 -0.0 0.00 0.41   0.19   2840.74   2840.74   0.00   942.24   0.00
Maximum of Months 0.213937E+11 0.699834E+10 744.00 0.212431E+11 0.150805E+09 0.00 1.00   0.85   8769.85   8366.15   594.45   3186.17   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.430650E+11 0.111150E+11 744.00 0.430344E+11 30590867.21 0.00 0.39 29-JAN-17:12 0.03 02-JAN-07:10 25547.41 24-JAN-17:00 25547.41 24-JAN-17:00 915.67 09-JAN-11:30 8819.98 31-JAN-17:00 0.00
February 0.809914E+11 0.180841E+11 672.00 0.805601E+11 0.431251E+09 0.00 0.53 25-FEB-18:10 0.33 13-FEB-07:10 42053.06 22-FEB-17:00 41595.71 27-FEB-17:40 1702.56 16-FEB-10:30 9853.13 22-FEB-17:00 0.00
March 0.143980E+12 0.335196E+11 744.00 0.143864E+12 0.116228E+09 0.00 0.93 31-MAR-23:50 0.58 07-MAR-08:00 72417.16 31-MAR-23:40 72417.16 31-MAR-23:40 2110.15 06-MAR-11:05 19725.54 16-MAR-16:00 0.00
April 0.189327E+12 0.546682E+11 720.00 0.189327E+12 0.00 0.00 1.00 01-APR-09:25 0.33 30-APR-23:05 78982.55 26-APR-18:50 78982.55 26-APR-18:50 0.00 05-APR-01:50 27468.78 14-APR-16:10 0.00
May 0.587126E+11 0.199223E+11 744.00 0.587126E+11 0.00 0.00 0.59 31-MAY-23:45 0.24 13-MAY-06:10 39502.21 31-MAY-23:55 39502.21 31-MAY-23:55 0.00 10-MAY-05:50 13303.48 31-MAY-23:15 0.00
June 0.106710E+12 0.393568E+11 720.00 0.106693E+12 17686006.56 0.00 0.79 30-JUN-23:13 0.49 21-JUN-06:10 57678.52 30-JUN-24:00 57678.52 30-JUN-24:00 943.21 30-JUN-10:00 22167.80 16-JUN-16:00 0.00
July 0.158919E+12 0.544456E+11 744.00 0.157418E+12 0.150139E+10 0.00 1.00 01-JUL-18:40 0.69 01-JUL-06:10 75724.87 31-JUL-23:53 75595.95 31-JUL-23:57 4107.26 13-JUL-18:00 28497.78 02-JUL-18:00 0.00
August 0.201718E+12 0.663315E+11 744.00 0.200195E+12 0.152348E+10 0.00 1.00 01-AUG-08:40 0.31 31-AUG-24:00 82772.61 28-AUG-16:25 78351.16 20-AUG-20:52 5809.31 28-AUG-16:15 30426.64 25-AUG-16:10 0.00
September 0.582084E+11 0.187069E+11 720.00 0.568589E+11 0.134955E+10 0.00 0.55 30-SEP-24:00 0.23 22-SEP-06:10 39536.66 30-SEP-24:00 39536.66 30-SEP-24:00 2944.21 11-SEP-15:10 11928.05 30-SEP-23:25 0.00
October 0.101848E+12 0.279397E+11 744.00 0.101545E+12 0.302755E+09 0.00 0.72 15-OCT-17:11 0.39 25-OCT-06:45 54737.28 31-OCT-24:00 54737.28 31-OCT-24:00 3077.70 03-OCT-09:40 17386.70 01-OCT-14:00 0.00
November 0.139850E+12 0.326414E+11 720.00 0.139364E+12 0.485974E+09 0.00 0.89 09-NOV-17:00 0.58 18-NOV-07:35 64584.75 14-NOV-17:00 63400.08 09-NOV-17:00 4001.62 13-NOV-16:10 20816.53 09-NOV-16:50 0.00
December 0.185735E+12 0.422393E+11 744.00 0.185729E+12 5559653.28 0.00 1.00 02-DEC-14:40 0.78 14-DEC-07:10 78709.06 28-DEC-17:00 78709.06 28-DEC-17:00 776.50 13-DEC-11:10 23073.32 25-DEC-16:00 0.00
                                       
Annual Sum or Average 0.146907E+13 0.418970E+12 8760.00 0.146330E+13 0.576447E+10 0.00                         0.00
Minimum of Months 0.430650E+11 0.111150E+11 672.00 0.430344E+11 0.00 0.00 0.39   0.03   25547.41   25547.41   0.00   8819.98   0.00
Maximum of Months 0.201718E+12 0.663315E+11 744.00 0.200195E+12 0.152348E+10 0.00 1.00   0.78   82772.61   78982.55   5809.31   30426.64   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.339174E+10 0.899074E+09 712.87 0.338894E+10 2795178.66 0.00 0.38 31-JAN-17:00 0.00 01-JAN-00:05 2583.50 24-JAN-17:00 2583.50 24-JAN-17:00 83.79 09-JAN-11:50 896.20 31-JAN-17:00 0.00
February 0.711197E+10 0.160835E+10 672.00 0.706948E+10 42490499.89 0.00 0.53 22-FEB-17:00 0.21 13-FEB-07:10 4242.70 22-FEB-17:00 4189.23 22-FEB-17:00 170.81 16-FEB-10:40 995.40 22-FEB-17:00 0.00
March 0.137743E+11 0.323909E+10 744.00 0.137628E+11 11439761.99 0.00 0.89 31-MAR-23:20 0.47 27-MAR-06:10 7082.37 31-MAR-23:20 7082.37 31-MAR-23:20 209.50 06-MAR-11:05 2000.42 16-MAR-16:00 0.00
April 0.190025E+11 0.552368E+10 720.00 0.190025E+11 -0.0 0.00 1.00 01-APR-10:30 0.34 30-APR-24:00 8013.25 26-APR-18:30 8013.25 26-APR-18:30 0.00 12-APR-14:10 2809.89 14-APR-16:10 0.00
May 0.593512E+10 0.202615E+10 744.00 0.593512E+10 -0.0 0.00 0.58 31-MAY-23:35 0.21 13-MAY-06:30 3961.93 31-MAY-23:55 3961.93 31-MAY-23:55 0.00 09-MAY-10:10 1335.83 31-MAY-23:15 0.00
June 0.108602E+11 0.401351E+10 720.00 0.108585E+11 1641194.03 0.00 0.78 30-JUN-23:13 0.47 21-JUN-06:10 5832.57 30-JUN-24:00 5832.57 30-JUN-24:00 93.39 30-JUN-10:10 2279.23 16-JUN-16:00 0.00
July 0.161018E+11 0.552733E+10 744.00 0.159516E+11 0.150143E+09 0.00 1.00 01-JUL-18:11 0.67 01-JUL-06:10 7629.59 31-JUL-23:53 7616.59 31-JUL-23:57 410.74 13-JUL-18:00 2916.51 02-JUL-18:00 0.00
August 0.203861E+11 0.672774E+10 744.00 0.202326E+11 0.153456E+09 0.00 1.00 01-AUG-09:30 0.31 31-AUG-24:00 8393.63 28-AUG-16:15 8050.13 20-AUG-21:03 597.75 28-AUG-16:15 3112.61 25-AUG-16:10 0.00
September 0.592197E+10 0.190911E+10 720.00 0.578655E+10 0.135426E+09 0.00 0.55 30-SEP-24:00 0.20 22-SEP-06:30 3995.09 30-SEP-24:00 3995.09 30-SEP-24:00 296.14 11-SEP-15:10 1206.92 30-SEP-23:25 0.00
October 0.984835E+10 0.273215E+10 744.00 0.981819E+10 30164834.49 0.00 0.73 15-OCT-17:11 0.32 25-OCT-06:55 5298.65 31-OCT-23:40 5298.65 31-OCT-23:40 308.44 03-OCT-09:40 1809.66 01-OCT-14:00 0.00
November 0.131729E+11 0.311035E+10 720.00 0.131247E+11 48221615.93 0.00 0.88 09-NOV-17:00 0.45 24-NOV-07:05 6486.42 14-NOV-17:00 6392.32 09-NOV-17:00 400.01 13-NOV-16:20 2103.56 09-NOV-16:50 0.00
December 0.172443E+11 0.397778E+10 744.00 0.172438E+11 519502.04 0.00 1.00 21-DEC-15:00 0.65 18-DEC-07:10 7924.14 26-DEC-17:10 7924.14 26-DEC-17:10 71.89 13-DEC-11:20 2358.09 25-DEC-16:00 0.00
                                       
Annual Sum or Average 0.142751E+12 0.412943E+11 8728.87 0.142175E+12 0.576298E+09 0.00                         0.00
Minimum of Months 0.339174E+10 0.899074E+09 672.00 0.338894E+10 -0.0 0.00 0.38   0.00   2583.50   2583.50   0.00   896.20   0.00
Maximum of Months 0.203861E+11 0.672774E+10 744.00 0.202326E+11 0.153456E+09 0.00 1.00   0.67   8393.63   8050.13   597.75   3112.61   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 100.37 0.00 100.37 68.33 445.21 0.00 0.00 0.00
February 114.37 0.00 114.37 46.75 449.02 0.00 0.00 0.00
March 152.00 0.00 152.00 132.02 386.26 0.00 0.00 0.00
April 185.19 1.92 183.27 296.44 202.80 0.00 0.00 0.00
May 216.79 17.36 199.43 413.41 133.34 0.00 0.00 0.00
June 251.92 45.77 206.15 642.81 52.97 0.00 0.00 0.00
July 214.84 22.38 192.46 546.56 41.27 0.00 0.00 0.00
August 173.41 4.31 169.11 446.60 56.17 0.00 0.00 0.00
September 163.61 0.04 163.57 377.58 82.36 0.00 0.00 0.00
October 126.58 0.00 126.58 177.41 274.56 0.00 0.00 0.00
November 105.47 0.00 105.47 70.28 415.46 0.00 0.00 0.00
December 93.76 0.00 93.76 34.31 556.63 0.00 0.00 0.00
                 
Annual Sum or Average 158.35 7.66 150.69 272.06 257.20 0.00 0.00 0.00
Minimum of Months 93.76 0.00 93.76 34.31 41.27 0.00 0.00 0.00
Maximum of Months 251.92 45.77 206.15 642.81 556.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 100.37 0.00 100.37 68.33 445.21 0.00 0.00 0.00
February 114.37 0.00 114.37 46.75 449.02 0.00 0.00 0.00
March 152.00 0.00 152.00 132.02 386.26 0.00 0.00 0.00
April 185.19 1.92 183.27 296.44 202.80 0.00 0.00 0.00
May 216.79 17.36 199.43 413.41 133.34 0.00 0.00 0.00
June 251.92 45.77 206.15 642.81 52.97 0.00 0.00 0.00
July 214.84 22.38 192.46 546.56 41.27 0.00 0.00 0.00
August 173.41 4.31 169.11 446.60 56.17 0.00 0.00 0.00
September 163.61 0.04 163.57 377.58 82.36 0.00 0.00 0.00
October 126.58 0.00 126.58 177.41 274.56 0.00 0.00 0.00
November 105.47 0.00 105.47 70.28 415.46 0.00 0.00 0.00
December 93.76 0.00 93.76 34.31 556.63 0.00 0.00 0.00
                 
Annual Sum or Average 158.35 7.66 150.69 272.06 257.20 0.00 0.00 0.00
Minimum of Months 93.76 0.00 93.76 34.31 41.27 0.00 0.00 0.00
Maximum of Months 251.92 45.77 206.15 642.81 556.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 100.37 0.00 100.37 68.33 445.21 0.00 0.00 0.00
February 114.37 0.00 114.37 46.75 449.02 0.00 0.00 0.00
March 152.00 0.00 152.00 132.02 386.26 0.00 0.00 0.00
April 185.19 1.92 183.27 296.44 202.80 0.00 0.00 0.00
May 216.79 17.36 199.43 413.41 133.34 0.00 0.00 0.00
June 251.92 45.77 206.15 642.81 52.97 0.00 0.00 0.00
July 214.84 22.38 192.46 546.56 41.27 0.00 0.00 0.00
August 173.41 4.31 169.11 446.60 56.17 0.00 0.00 0.00
September 163.61 0.04 163.57 377.58 82.36 0.00 0.00 0.00
October 126.58 0.00 126.58 177.41 274.56 0.00 0.00 0.00
November 105.47 0.00 105.47 70.28 415.46 0.00 0.00 0.00
December 93.76 0.00 93.76 34.31 556.63 0.00 0.00 0.00
                 
Annual Sum or Average 158.35 7.66 150.69 272.06 257.20 0.00 0.00 0.00
Minimum of Months 93.76 0.00 93.76 34.31 41.27 0.00 0.00 0.00
Maximum of Months 251.92 45.77 206.15 642.81 556.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 100.37 0.00 100.37 68.33 445.21 0.00 0.00 0.00
February 114.37 0.00 114.37 46.75 449.02 0.00 0.00 0.00
March 152.00 0.00 152.00 132.02 386.26 0.00 0.00 0.00
April 185.19 1.92 183.27 296.44 202.80 0.00 0.00 0.00
May 216.79 17.36 199.43 413.41 133.34 0.00 0.00 0.00
June 251.92 45.77 206.15 642.81 52.97 0.00 0.00 0.00
July 214.84 22.38 192.46 546.56 41.27 0.00 0.00 0.00
August 173.41 4.31 169.11 446.60 56.17 0.00 0.00 0.00
September 163.61 0.04 163.57 377.58 82.36 0.00 0.00 0.00
October 126.58 0.00 126.58 177.41 274.56 0.00 0.00 0.00
November 105.47 0.00 105.47 70.28 415.46 0.00 0.00 0.00
December 93.76 0.00 93.76 34.31 556.63 0.00 0.00 0.00
                 
Annual Sum or Average 158.35 7.66 150.69 272.06 257.20 0.00 0.00 0.00
Minimum of Months 93.76 0.00 93.76 34.31 41.27 0.00 0.00 0.00
Maximum of Months 251.92 45.77 206.15 642.81 556.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 100.37 0.00 100.37 68.33 445.19 0.00 0.00 0.00
February 114.37 0.00 114.37 46.74 449.01 0.00 0.00 0.00
March 152.00 0.00 152.00 132.02 386.25 0.00 0.00 0.00
April 185.18 1.92 183.26 296.43 202.79 0.00 0.00 0.00
May 216.78 17.36 199.42 413.39 133.34 0.00 0.00 0.00
June 251.91 45.77 206.14 642.78 52.97 0.00 0.00 0.00
July 214.83 22.38 192.45 546.53 41.26 0.00 0.00 0.00
August 173.41 4.31 169.10 446.58 56.17 0.00 0.00 0.00
September 163.61 0.04 163.56 377.57 82.36 0.00 0.00 0.00
October 126.58 0.00 126.58 177.40 274.55 0.00 0.00 0.00
November 105.46 0.00 105.46 70.27 415.44 0.00 0.00 0.00
December 93.75 0.00 93.75 34.31 556.61 0.00 0.00 0.00
                 
Annual Sum or Average 158.35 7.66 150.68 272.04 257.19 0.00 0.00 0.00
Minimum of Months 93.75 0.00 93.75 34.31 41.26 0.00 0.00 0.00
Maximum of Months 251.91 45.77 206.14 642.78 556.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 360.28 226.01 134.27 451.65 452.91 0.00 0.00 0.00
February 355.13 203.15 151.98 395.87 458.44 0.00 0.00 0.00
March 444.43 228.62 215.81 573.30 390.55 0.00 0.00 0.00
April 634.39 378.11 256.29 1043.57 206.35 0.00 0.00 0.00
May 657.46 389.74 267.72 1154.84 148.56 0.00 0.00 0.00
June 685.29 425.83 259.46 1382.65 56.19 0.00 0.00 0.00
July 578.77 326.34 252.42 1180.34 42.25 0.00 0.00 0.00
August 549.30 313.49 235.82 1110.89 54.58 0.00 0.00 0.00
September 450.74 217.26 233.47 877.50 85.69 0.00 0.00 0.00
October 452.74 275.53 177.21 704.68 279.13 0.00 0.00 0.00
November 348.13 208.99 139.14 435.05 420.39 0.00 0.00 0.00
December 317.41 191.66 125.75 344.32 551.85 0.00 0.00 0.00
                 
Annual Sum or Average 486.77 282.43 204.34 806.49 261.40 0.00 0.00 0.00
Minimum of Months 317.41 191.66 125.75 344.32 42.25 0.00 0.00 0.00
Maximum of Months 685.29 425.83 267.72 1382.65 551.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 360.28 226.01 134.27 451.65 452.91 0.00 0.00 0.00
February 355.13 203.15 151.98 395.87 458.44 0.00 0.00 0.00
March 444.43 228.62 215.81 573.30 390.55 0.00 0.00 0.00
April 634.39 378.11 256.29 1043.57 206.35 0.00 0.00 0.00
May 657.46 389.74 267.72 1154.84 148.56 0.00 0.00 0.00
June 685.29 425.83 259.46 1382.65 56.19 0.00 0.00 0.00
July 578.77 326.34 252.42 1180.34 42.25 0.00 0.00 0.00
August 549.30 313.49 235.82 1110.89 54.58 0.00 0.00 0.00
September 450.74 217.26 233.47 877.50 85.69 0.00 0.00 0.00
October 452.74 275.53 177.21 704.68 279.13 0.00 0.00 0.00
November 348.13 208.99 139.14 435.05 420.39 0.00 0.00 0.00
December 317.41 191.66 125.75 344.32 551.85 0.00 0.00 0.00
                 
Annual Sum or Average 486.77 282.43 204.34 806.49 261.40 0.00 0.00 0.00
Minimum of Months 317.41 191.66 125.75 344.32 42.25 0.00 0.00 0.00
Maximum of Months 685.29 425.83 267.72 1382.65 551.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 360.27 226.01 134.26 451.64 452.90 0.00 0.00 0.00
February 355.12 203.15 151.98 395.86 458.43 0.00 0.00 0.00
March 444.42 228.61 215.81 573.29 390.54 0.00 0.00 0.00
April 634.38 378.10 256.28 1043.55 206.34 0.00 0.00 0.00
May 657.45 389.73 267.72 1154.82 148.56 0.00 0.00 0.00
June 685.27 425.82 259.45 1382.63 56.19 0.00 0.00 0.00
July 578.76 326.34 252.42 1180.32 42.25 0.00 0.00 0.00
August 549.29 313.48 235.81 1110.87 54.58 0.00 0.00 0.00
September 450.73 217.26 233.47 877.49 85.69 0.00 0.00 0.00
October 452.73 275.53 177.20 704.67 279.12 0.00 0.00 0.00
November 348.13 208.98 139.14 435.04 420.39 0.00 0.00 0.00
December 317.40 191.66 125.74 344.31 551.84 0.00 0.00 0.00
                 
Annual Sum or Average 486.76 282.42 204.34 806.47 261.39 0.00 0.00 0.00
Minimum of Months 317.40 191.66 125.74 344.31 42.25 0.00 0.00 0.00
Maximum of Months 685.27 425.82 267.72 1382.63 551.84 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 826.48 660.09 166.39 1248.63 422.00 0.00 0.00 0.00
February 522.57 352.44 170.13 707.26 414.08 0.00 0.00 0.00
March 434.82 223.95 210.86 631.94 374.59 0.00 0.00 0.00
April 370.15 149.57 220.57 689.76 212.93 0.00 0.00 0.00
May 248.04 40.98 207.06 509.25 146.77 0.00 0.00 0.00
June 212.39 16.37 196.02 577.08 55.78 0.00 0.00 0.00
July 217.03 22.45 194.57 563.09 42.33 0.00 0.00 0.00
August 263.89 72.93 190.97 649.63 57.42 0.00 0.00 0.00
September 380.25 162.22 218.02 794.19 85.42 0.00 0.00 0.00
October 605.88 419.36 186.52 1007.15 265.86 0.00 0.00 0.00
November 706.08 540.82 165.26 1051.46 390.06 0.00 0.00 0.00
December 768.38 608.28 160.10 1102.69 508.59 0.00 0.00 0.00
                 
Annual Sum or Average 463.01 272.40 190.60 795.24 247.30 0.00 0.00 0.00
Minimum of Months 212.39 16.37 160.10 509.25 42.33 0.00 0.00 0.00
Maximum of Months 826.48 660.09 220.57 1248.63 508.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 826.48 660.09 166.39 1248.63 422.00 0.00 0.00 0.00
February 522.57 352.44 170.13 707.26 414.08 0.00 0.00 0.00
March 434.82 223.95 210.86 631.94 374.59 0.00 0.00 0.00
April 370.15 149.57 220.57 689.76 212.93 0.00 0.00 0.00
May 248.04 40.98 207.06 509.25 146.77 0.00 0.00 0.00
June 212.39 16.37 196.02 577.08 55.78 0.00 0.00 0.00
July 217.03 22.45 194.57 563.09 42.33 0.00 0.00 0.00
August 263.89 72.93 190.97 649.63 57.42 0.00 0.00 0.00
September 380.24 162.22 218.02 794.19 85.42 0.00 0.00 0.00
October 605.88 419.36 186.52 1007.15 265.86 0.00 0.00 0.00
November 706.08 540.82 165.26 1051.46 390.06 0.00 0.00 0.00
December 768.38 608.28 160.10 1102.69 508.59 0.00 0.00 0.00
                 
Annual Sum or Average 463.01 272.40 190.60 795.24 247.30 0.00 0.00 0.00
Minimum of Months 212.39 16.37 160.10 509.25 42.33 0.00 0.00 0.00
Maximum of Months 826.48 660.09 220.57 1248.63 508.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 826.48 660.09 166.39 1248.63 422.00 0.00 0.00 0.00
February 522.57 352.44 170.13 707.26 414.08 0.00 0.00 0.00
March 434.82 223.95 210.86 631.94 374.59 0.00 0.00 0.00
April 370.15 149.57 220.57 689.76 212.93 0.00 0.00 0.00
May 248.04 40.98 207.06 509.25 146.77 0.00 0.00 0.00
June 212.39 16.37 196.02 577.08 55.78 0.00 0.00 0.00
July 217.03 22.45 194.57 563.09 42.33 0.00 0.00 0.00
August 263.89 72.93 190.97 649.63 57.42 0.00 0.00 0.00
September 380.25 162.22 218.02 794.19 85.42 0.00 0.00 0.00
October 605.88 419.36 186.52 1007.15 265.86 0.00 0.00 0.00
November 706.08 540.82 165.26 1051.46 390.06 0.00 0.00 0.00
December 768.38 608.28 160.10 1102.69 508.59 0.00 0.00 0.00
                 
Annual Sum or Average 463.01 272.40 190.60 795.24 247.30 0.00 0.00 0.00
Minimum of Months 212.39 16.37 160.10 509.25 42.33 0.00 0.00 0.00
Maximum of Months 826.48 660.09 220.57 1248.63 508.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 826.48 660.09 166.39 1248.63 422.00 0.00 0.00 0.00
February 522.57 352.44 170.13 707.26 414.08 0.00 0.00 0.00
March 434.82 223.95 210.86 631.94 374.59 0.00 0.00 0.00
April 370.15 149.57 220.57 689.76 212.93 0.00 0.00 0.00
May 248.04 40.98 207.06 509.25 146.77 0.00 0.00 0.00
June 212.39 16.37 196.02 577.08 55.78 0.00 0.00 0.00
July 217.03 22.45 194.57 563.09 42.33 0.00 0.00 0.00
August 263.89 72.93 190.97 649.63 57.42 0.00 0.00 0.00
September 380.24 162.22 218.02 794.19 85.42 0.00 0.00 0.00
October 605.88 419.36 186.52 1007.15 265.86 0.00 0.00 0.00
November 706.08 540.82 165.26 1051.46 390.06 0.00 0.00 0.00
December 768.38 608.28 160.10 1102.69 508.59 0.00 0.00 0.00
                 
Annual Sum or Average 463.01 272.40 190.60 795.24 247.30 0.00 0.00 0.00
Minimum of Months 212.39 16.37 160.10 509.25 42.33 0.00 0.00 0.00
Maximum of Months 826.48 660.09 220.57 1248.63 508.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 826.45 660.06 166.39 1248.58 421.98 0.00 0.00 0.00
February 522.55 352.43 170.12 707.24 414.07 0.00 0.00 0.00
March 434.80 223.95 210.86 631.91 374.58 0.00 0.00 0.00
April 370.13 149.57 220.56 689.73 212.92 0.00 0.00 0.00
May 248.03 40.98 207.05 509.23 146.77 0.00 0.00 0.00
June 212.38 16.37 196.01 577.05 55.78 0.00 0.00 0.00
July 217.02 22.45 194.57 563.07 42.33 0.00 0.00 0.00
August 263.88 72.92 190.96 649.60 57.42 0.00 0.00 0.00
September 380.23 162.22 218.01 794.16 85.41 0.00 0.00 0.00
October 605.86 419.34 186.51 1007.11 265.85 0.00 0.00 0.00
November 706.05 540.80 165.25 1051.42 390.05 0.00 0.00 0.00
December 768.35 608.25 160.10 1102.65 508.57 0.00 0.00 0.00
                 
Annual Sum or Average 462.99 272.39 190.60 795.21 247.29 0.00 0.00 0.00
Minimum of Months 212.38 16.37 160.10 509.23 42.33 0.00 0.00 0.00
Maximum of Months 826.45 660.06 220.56 1248.58 508.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 376.74 234.15 142.59 525.89 533.34 0.00 0.00 0.00
February 305.20 147.54 157.65 336.69 543.64 0.00 0.00 0.00
March 404.24 192.71 211.53 517.66 475.29 0.00 0.00 0.00
April 620.72 354.08 266.64 1020.89 288.34 0.00 0.00 0.00
May 622.32 348.93 273.38 1108.13 191.44 0.00 0.00 0.00
June 661.59 389.12 272.47 1330.68 87.48 0.00 0.00 0.00
July 481.52 224.77 256.75 987.42 71.26 0.00 0.00 0.00
August 459.17 230.60 228.57 925.73 102.36 0.00 0.00 0.00
September 400.24 168.17 232.08 786.30 113.77 0.00 0.00 0.00
October 409.53 234.17 175.36 645.72 344.16 0.00 0.00 0.00
November 377.19 227.74 149.45 507.47 518.15 0.00 0.00 0.00
December 304.00 173.09 130.91 363.68 687.15 0.00 0.00 0.00
                 
Annual Sum or Average 452.39 244.10 208.29 756.41 328.79 0.00 0.00 0.00
Minimum of Months 304.00 147.54 130.91 336.69 71.26 0.00 0.00 0.00
Maximum of Months 661.59 389.12 273.38 1330.68 687.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 376.74 234.15 142.59 525.89 533.34 0.00 0.00 0.00
February 305.20 147.54 157.65 336.69 543.64 0.00 0.00 0.00
March 404.24 192.71 211.53 517.66 475.29 0.00 0.00 0.00
April 620.72 354.08 266.64 1020.89 288.34 0.00 0.00 0.00
May 622.32 348.93 273.38 1108.13 191.44 0.00 0.00 0.00
June 661.59 389.12 272.47 1330.68 87.48 0.00 0.00 0.00
July 481.52 224.77 256.75 987.42 71.26 0.00 0.00 0.00
August 459.17 230.60 228.57 925.73 102.36 0.00 0.00 0.00
September 400.24 168.17 232.08 786.30 113.77 0.00 0.00 0.00
October 409.53 234.17 175.36 645.72 344.16 0.00 0.00 0.00
November 377.19 227.74 149.45 507.47 518.15 0.00 0.00 0.00
December 304.00 173.09 130.91 363.68 687.15 0.00 0.00 0.00
                 
Annual Sum or Average 452.39 244.10 208.29 756.41 328.79 0.00 0.00 0.00
Minimum of Months 304.00 147.54 130.91 336.69 71.26 0.00 0.00 0.00
Maximum of Months 661.59 389.12 273.38 1330.68 687.15 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 376.73 234.15 142.59 525.88 533.33 0.00 0.00 0.00
February 305.19 147.54 157.65 336.69 543.63 0.00 0.00 0.00
March 404.23 192.70 211.53 517.65 475.28 0.00 0.00 0.00
April 620.71 354.07 266.64 1020.88 288.33 0.00 0.00 0.00
May 622.31 348.93 273.38 1108.11 191.43 0.00 0.00 0.00
June 661.57 389.11 272.46 1330.66 87.48 0.00 0.00 0.00
July 481.51 224.77 256.74 987.40 71.26 0.00 0.00 0.00
August 459.16 230.60 228.56 925.71 102.36 0.00 0.00 0.00
September 400.24 168.16 232.07 786.29 113.76 0.00 0.00 0.00
October 409.52 234.16 175.36 645.71 344.15 0.00 0.00 0.00
November 377.18 227.73 149.45 507.46 518.14 0.00 0.00 0.00
December 303.99 173.08 130.91 363.67 687.14 0.00 0.00 0.00
                 
Annual Sum or Average 452.38 244.09 208.28 756.39 328.78 0.00 0.00 0.00
Minimum of Months 303.99 147.54 130.91 336.69 71.26 0.00 0.00 0.00
Maximum of Months 661.57 389.11 273.38 1330.66 687.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 501.86 0.00 501.86 415.52 1985.78 0.00 0.00 0.00
February 571.86 0.00 571.86 283.82 1988.13 0.00 0.00 0.00
March 760.00 0.00 760.00 717.77 1751.88 0.00 0.00 0.00
April 925.95 9.61 916.34 1536.51 956.17 0.00 0.00 0.00
May 1083.92 86.79 997.13 2097.08 647.17 0.00 0.00 0.00
June 1259.58 228.85 1030.73 3247.02 268.05 0.00 0.00 0.00
July 1074.18 111.91 962.28 2771.39 204.13 0.00 0.00 0.00
August 867.06 21.54 845.52 2296.77 255.36 0.00 0.00 0.00
September 818.06 0.22 817.84 1912.60 398.78 0.00 0.00 0.00
October 632.91 0.00 632.91 934.98 1258.47 0.00 0.00 0.00
November 527.33 0.00 527.33 413.56 1838.05 0.00 0.00 0.00
December 468.78 0.00 468.78 253.62 2419.55 0.00 0.00 0.00
                 
Annual Sum or Average 791.75 38.32 753.43 1411.89 1160.80 0.00 0.00 0.00
Minimum of Months 468.78 0.00 468.78 253.62 204.13 0.00 0.00 0.00
Maximum of Months 1259.58 228.85 1030.73 3247.02 2419.55 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1080.83 678.04 402.80 1366.89 1269.59 0.00 0.00 0.00
February 1065.37 609.44 455.93 1188.50 1287.61 0.00 0.00 0.00
March 1333.26 685.84 647.42 1710.47 1124.05 0.00 0.00 0.00
April 1903.16 1134.31 768.85 3101.28 628.82 0.00 0.00 0.00
May 1972.36 1169.20 803.16 3436.09 446.65 0.00 0.00 0.00
June 2055.84 1277.47 778.37 4117.48 180.24 0.00 0.00 0.00
July 1736.29 979.02 757.26 3512.08 138.15 0.00 0.00 0.00
August 1647.89 940.45 707.44 3310.37 174.17 0.00 0.00 0.00
September 1352.20 651.79 700.42 2609.49 261.44 0.00 0.00 0.00
October 1358.21 826.60 531.61 2100.52 808.34 0.00 0.00 0.00
November 1044.39 626.96 417.43 1309.52 1184.06 0.00 0.00 0.00
December 952.21 574.97 377.24 1057.37 1540.81 0.00 0.00 0.00
                 
Annual Sum or Average 1460.30 847.28 613.02 2407.45 751.36 0.00 0.00 0.00
Minimum of Months 952.21 574.97 377.24 1057.37 138.15 0.00 0.00 0.00
Maximum of Months 2055.84 1277.47 803.16 4117.48 1540.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4132.36 3300.40 831.96 6194.45 2076.07 0.00 0.00 0.00
February 2612.84 1762.19 850.65 3511.47 1998.67 0.00 0.00 0.00
March 2174.07 1119.76 1054.31 3148.70 1804.32 0.00 0.00 0.00
April 1850.70 747.87 1102.84 3453.95 1034.11 0.00 0.00 0.00
May 1240.16 204.89 1035.28 2565.33 715.08 0.00 0.00 0.00
June 1061.94 81.86 980.08 2927.23 275.44 0.00 0.00 0.00
July 1085.12 112.26 972.85 2853.32 206.11 0.00 0.00 0.00
August 1319.45 364.63 954.82 3289.82 264.81 0.00 0.00 0.00
September 1901.20 811.10 1090.10 3960.44 421.34 0.00 0.00 0.00
October 3029.37 2096.77 932.59 5000.47 1298.77 0.00 0.00 0.00
November 3530.36 2704.07 826.29 5223.23 1890.89 0.00 0.00 0.00
December 3841.87 3041.36 800.51 5494.37 2460.28 0.00 0.00 0.00
                 
Annual Sum or Average 2315.01 1362.00 953.01 3973.17 1200.56 0.00 0.00 0.00
Minimum of Months 1061.94 81.86 800.51 2565.33 206.11 0.00 0.00 0.00
Maximum of Months 4132.36 3300.40 1102.84 6194.45 2460.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1130.21 702.44 427.76 1611.86 1438.49 0.00 0.00 0.00
February 915.58 442.63 472.95 1045.17 1396.51 0.00 0.00 0.00
March 1212.71 578.12 634.59 1604.72 1234.11 0.00 0.00 0.00
April 1862.16 1062.23 799.93 3113.02 750.06 0.00 0.00 0.00
May 1866.94 1046.79 820.14 3336.23 536.97 0.00 0.00 0.00
June 1984.74 1167.35 817.39 4026.36 234.54 0.00 0.00 0.00
July 1444.54 674.31 770.23 3024.52 174.04 0.00 0.00 0.00
August 1377.50 691.81 685.69 2867.92 216.14 0.00 0.00 0.00
September 1200.71 504.49 696.22 2381.47 303.30 0.00 0.00 0.00
October 1228.58 702.50 526.08 1971.60 911.68 0.00 0.00 0.00
November 1131.55 683.20 448.35 1567.26 1327.38 0.00 0.00 0.00
December 911.99 519.26 392.73 1156.35 1717.07 0.00 0.00 0.00
                 
Annual Sum or Average 1357.14 732.28 624.86 2314.18 851.08 0.00 0.00 0.00
Minimum of Months 911.99 442.63 392.73 1045.17 174.04 0.00 0.00 0.00
Maximum of Months 1984.74 1167.35 820.14 4026.36 1717.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 501.86 0.00 501.86 463.82 1823.91 0.00 0.00 0.00
February 571.86 0.00 571.86 324.13 1793.26 0.00 0.00 0.00
March 760.00 0.00 760.00 751.22 1644.77 0.00 0.00 0.00
April 925.95 9.61 916.34 1524.07 938.06 0.00 0.00 0.00
May 1083.92 86.79 997.13 2077.51 648.06 0.00 0.00 0.00
June 1259.58 228.85 1030.73 3208.59 277.09 0.00 0.00 0.00
July 1074.18 111.91 962.28 2727.34 214.72 0.00 0.00 0.00
August 867.06 21.54 845.52 2263.63 263.11 0.00 0.00 0.00
September 818.06 0.22 817.84 1887.19 404.46 0.00 0.00 0.00
October 632.91 0.00 632.91 947.05 1190.70 0.00 0.00 0.00
November 527.33 0.00 527.33 453.98 1686.60 0.00 0.00 0.00
December 468.78 0.00 468.78 307.19 2203.62 0.00 0.00 0.00
                 
Annual Sum or Average 791.75 38.32 753.43 1416.33 1087.82 0.00 0.00 0.00
Minimum of Months 468.78 0.00 468.78 307.19 214.72 0.00 0.00 0.00
Maximum of Months 1259.58 228.85 1030.73 3208.59 2203.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1080.83 678.04 402.80 1407.71 1180.79 0.00 0.00 0.00
February 1065.37 609.44 455.93 1221.22 1176.37 0.00 0.00 0.00
March 1333.26 685.84 647.42 1736.21 1067.82 0.00 0.00 0.00
April 1903.16 1134.31 768.85 3095.19 621.86 0.00 0.00 0.00
May 1972.36 1169.20 803.16 3424.33 446.65 0.00 0.00 0.00
June 2055.84 1277.47 778.37 4095.04 185.37 0.00 0.00 0.00
July 1736.29 979.02 757.26 3487.74 144.44 0.00 0.00 0.00
August 1647.89 940.45 707.44 3292.69 178.26 0.00 0.00 0.00
September 1352.20 651.79 700.42 2596.92 265.09 0.00 0.00 0.00
October 1358.21 826.60 531.61 2110.23 774.27 0.00 0.00 0.00
November 1044.39 626.96 417.43 1344.03 1098.93 0.00 0.00 0.00
December 952.21 574.97 377.24 1114.02 1410.22 0.00 0.00 0.00
                 
Annual Sum or Average 1460.30 847.28 613.02 2416.14 710.55 0.00 0.00 0.00
Minimum of Months 952.21 574.97 377.24 1114.02 144.44 0.00 0.00 0.00
Maximum of Months 2055.84 1277.47 803.16 4095.04 1410.22 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 4132.36 3300.40 831.96 6233.62 1953.60 0.00 0.00 0.00
February 2612.84 1762.19 850.65 3549.05 1838.98 0.00 0.00 0.00
March 2174.07 1119.76 1054.31 3170.07 1713.94 0.00 0.00 0.00
April 1850.70 747.87 1102.84 3435.61 1016.56 0.00 0.00 0.00
May 1240.16 204.89 1035.28 2544.00 712.02 0.00 0.00 0.00
June 1061.94 81.86 980.08 2888.67 283.02 0.00 0.00 0.00
July 1085.12 112.26 972.85 2809.15 215.67 0.00 0.00 0.00
August 1319.45 364.63 954.82 3254.98 271.36 0.00 0.00 0.00
September 1901.20 811.10 1090.10 3931.61 427.65 0.00 0.00 0.00
October 3029.37 2096.77 932.59 5001.91 1247.64 0.00 0.00 0.00
November 3530.36 2704.07 826.29 5256.37 1777.95 0.00 0.00 0.00
December 3841.87 3041.36 800.51 5548.75 2293.68 0.00 0.00 0.00
                 
Annual Sum or Average 2315.01 1362.00 953.01 3973.09 1143.27 0.00 0.00 0.00
Minimum of Months 1061.94 81.86 800.51 2544.00 215.67 0.00 0.00 0.00
Maximum of Months 4132.36 3300.40 1102.84 6233.62 2293.68 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1130.21 702.44 427.76 1631.51 1345.92 0.00 0.00 0.00
February 915.58 442.63 472.95 1062.20 1287.28 0.00 0.00 0.00
March 1212.71 578.12 634.59 1615.97 1173.11 0.00 0.00 0.00
April 1862.16 1062.23 799.93 3098.07 737.12 0.00 0.00 0.00
May 1866.94 1046.79 820.14 3317.47 534.12 0.00 0.00 0.00
June 1984.74 1167.35 817.39 3998.71 238.84 0.00 0.00 0.00
July 1444.54 674.31 770.23 2997.28 179.34 0.00 0.00 0.00
August 1377.50 691.81 685.69 2846.08 219.67 0.00 0.00 0.00
September 1200.71 504.49 696.22 2363.43 306.72 0.00 0.00 0.00
October 1228.58 702.50 526.08 1971.11 873.29 0.00 0.00 0.00
November 1131.55 683.20 448.35 1581.57 1243.81 0.00 0.00 0.00
December 911.99 519.26 392.73 1182.21 1594.74 0.00 0.00 0.00
                 
Annual Sum or Average 1357.14 732.28 624.86 2310.70 809.22 0.00 0.00 0.00
Minimum of Months 911.99 442.63 392.73 1062.20 179.34 0.00 0.00 0.00
Maximum of Months 1984.74 1167.35 820.14 3998.71 1594.74 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.268840E+09 0.00 0.268840E+09 0.183027E+09 0.119244E+10
February 0.276691E+09 0.00 0.276691E+09 0.113086E+09 0.108628E+10
March 0.407121E+09 0.00 0.407121E+09 0.353607E+09 0.103457E+10
April 0.480016E+09 4981337.40 0.475035E+09 0.768383E+09 0.525662E+09
May 0.580640E+09 46492323.30 0.534148E+09 0.110728E+10 0.357141E+09
June 0.652975E+09 0.118639E+09 0.534336E+09 0.166616E+10 0.137296E+09
July 0.575426E+09 59947998.39 0.515478E+09 0.146389E+10 0.110526E+09
August 0.464473E+09 11538584.38 0.452934E+09 0.119617E+10 0.150441E+09
September 0.424087E+09 113210.59 0.423974E+09 0.978699E+09 0.213486E+09
October 0.339043E+09 0.00 0.339043E+09 0.475169E+09 0.735390E+09
November 0.273373E+09 0.00 0.273373E+09 0.182160E+09 0.107687E+10
December 0.251121E+09 0.00 0.251121E+09 91904253.69 0.149089E+10
           
Annual Sum or Average 0.499381E+10 0.241712E+09 0.475209E+10 0.857954E+10 0.811099E+10
Minimum of Months 0.251121E+09 0.00 0.251121E+09 91904253.69 0.110526E+09
Maximum of Months 0.652975E+09 0.118639E+09 0.534336E+09 0.166616E+10 0.149089E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.268840E+09 0.00 0.268840E+09 0.183027E+09 0.119244E+10
February 0.276691E+09 0.00 0.276691E+09 0.113086E+09 0.108628E+10
March 0.407121E+09 0.00 0.407121E+09 0.353607E+09 0.103457E+10
April 0.480016E+09 4981331.42 0.475035E+09 0.768382E+09 0.525662E+09
May 0.580640E+09 46492267.52 0.534148E+09 0.110728E+10 0.357141E+09
June 0.652974E+09 0.118639E+09 0.534336E+09 0.166616E+10 0.137296E+09
July 0.575426E+09 59947926.46 0.515478E+09 0.146389E+10 0.110526E+09
August 0.464472E+09 11538570.53 0.452934E+09 0.119617E+10 0.150441E+09
September 0.424086E+09 113210.45 0.423973E+09 0.978699E+09 0.213486E+09
October 0.339043E+09 0.00 0.339043E+09 0.475169E+09 0.735390E+09
November 0.273373E+09 0.00 0.273373E+09 0.182160E+09 0.107687E+10
December 0.251121E+09 0.00 0.251121E+09 91904167.02 0.149089E+10
           
Annual Sum or Average 0.499380E+10 0.241712E+09 0.475209E+10 0.857954E+10 0.811099E+10
Minimum of Months 0.251121E+09 0.00 0.251121E+09 91904167.02 0.110526E+09
Maximum of Months 0.652974E+09 0.118639E+09 0.534336E+09 0.166616E+10 0.149089E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.268840E+09 0.00 0.268840E+09 0.183027E+09 0.119244E+10
February 0.276691E+09 0.00 0.276691E+09 0.113086E+09 0.108628E+10
March 0.407121E+09 0.00 0.407121E+09 0.353607E+09 0.103457E+10
April 0.480016E+09 4981337.40 0.475035E+09 0.768383E+09 0.525662E+09
May 0.580640E+09 46492323.30 0.534148E+09 0.110728E+10 0.357141E+09
June 0.652975E+09 0.118639E+09 0.534336E+09 0.166616E+10 0.137296E+09
July 0.575426E+09 59947998.39 0.515478E+09 0.146389E+10 0.110526E+09
August 0.464473E+09 11538584.38 0.452934E+09 0.119617E+10 0.150441E+09
September 0.424087E+09 113210.59 0.423974E+09 0.978699E+09 0.213486E+09
October 0.339043E+09 0.00 0.339043E+09 0.475169E+09 0.735390E+09
November 0.273373E+09 0.00 0.273373E+09 0.182160E+09 0.107687E+10
December 0.251121E+09 0.00 0.251121E+09 91904253.69 0.149089E+10
           
Annual Sum or Average 0.499381E+10 0.241712E+09 0.475209E+10 0.857954E+10 0.811099E+10
Minimum of Months 0.251121E+09 0.00 0.251121E+09 91904253.69 0.110526E+09
Maximum of Months 0.652975E+09 0.118639E+09 0.534336E+09 0.166616E+10 0.149089E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.268840E+09 0.00 0.268840E+09 0.183027E+09 0.119244E+10
February 0.276691E+09 0.00 0.276691E+09 0.113086E+09 0.108628E+10
March 0.407121E+09 0.00 0.407121E+09 0.353607E+09 0.103457E+10
April 0.480016E+09 4981331.42 0.475035E+09 0.768382E+09 0.525662E+09
May 0.580640E+09 46492267.52 0.534148E+09 0.110728E+10 0.357141E+09
June 0.652974E+09 0.118639E+09 0.534336E+09 0.166616E+10 0.137296E+09
July 0.575426E+09 59947926.46 0.515478E+09 0.146389E+10 0.110526E+09
August 0.464472E+09 11538570.53 0.452934E+09 0.119617E+10 0.150441E+09
September 0.424086E+09 113210.45 0.423973E+09 0.978699E+09 0.213486E+09
October 0.339043E+09 0.00 0.339043E+09 0.475169E+09 0.735390E+09
November 0.273373E+09 0.00 0.273373E+09 0.182160E+09 0.107687E+10
December 0.251121E+09 0.00 0.251121E+09 91904167.02 0.149089E+10
           
Annual Sum or Average 0.499380E+10 0.241712E+09 0.475209E+10 0.857954E+10 0.811099E+10
Minimum of Months 0.251121E+09 0.00 0.251121E+09 91904167.02 0.110526E+09
Maximum of Months 0.652974E+09 0.118639E+09 0.534336E+09 0.166616E+10 0.149089E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.268829E+09 0.00 0.268829E+09 0.183020E+09 0.119239E+10
February 0.276680E+09 0.00 0.276680E+09 0.113082E+09 0.108624E+10
March 0.407105E+09 0.00 0.407105E+09 0.353593E+09 0.103453E+10
April 0.479997E+09 4981136.63 0.475016E+09 0.768352E+09 0.525641E+09
May 0.580617E+09 46490449.46 0.534127E+09 0.110724E+10 0.357127E+09
June 0.652949E+09 0.118634E+09 0.534314E+09 0.166610E+10 0.137291E+09
July 0.575403E+09 59945582.22 0.515457E+09 0.146384E+10 0.110522E+09
August 0.464454E+09 11538119.32 0.452916E+09 0.119612E+10 0.150435E+09
September 0.424070E+09 113206.03 0.423956E+09 0.978660E+09 0.213477E+09
October 0.339029E+09 0.00 0.339029E+09 0.475150E+09 0.735360E+09
November 0.273362E+09 0.00 0.273362E+09 0.182153E+09 0.107683E+10
December 0.251111E+09 0.00 0.251111E+09 91900549.54 0.149083E+10
           
Annual Sum or Average 0.499361E+10 0.241703E+09 0.475190E+10 0.857919E+10 0.811066E+10
Minimum of Months 0.251111E+09 0.00 0.251111E+09 91900549.54 0.110522E+09
Maximum of Months 0.652949E+09 0.118634E+09 0.534314E+09 0.166610E+10 0.149083E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.964978E+09 0.605357E+09 0.359620E+09 0.120969E+10 0.121308E+10
February 0.859124E+09 0.491458E+09 0.367666E+09 0.957689E+09 0.110906E+10
March 0.119035E+10 0.612325E+09 0.578025E+09 0.153553E+10 0.104604E+10
April 0.164435E+10 0.980052E+09 0.664295E+09 0.270493E+10 0.534852E+09
May 0.176094E+10 0.104387E+10 0.717070E+09 0.309312E+10 0.397916E+09
June 0.177626E+10 0.110374E+10 0.672518E+09 0.358384E+10 0.145652E+09
July 0.155017E+10 0.874079E+09 0.676093E+09 0.316142E+10 0.113158E+09
August 0.147125E+10 0.839640E+09 0.631608E+09 0.297541E+10 0.146190E+09
September 0.116832E+10 0.563149E+09 0.605167E+09 0.227449E+10 0.222104E+09
October 0.121262E+10 0.737992E+09 0.474628E+09 0.188741E+10 0.747622E+09
November 0.902358E+09 0.541698E+09 0.360661E+09 0.112764E+10 0.108966E+10
December 0.850139E+09 0.513339E+09 0.336800E+09 0.922225E+09 0.147807E+10
           
Annual Sum or Average 0.153509E+11 0.890670E+10 0.644415E+10 0.254334E+11 0.824340E+10
Minimum of Months 0.850139E+09 0.491458E+09 0.336800E+09 0.922225E+09 0.113158E+09
Maximum of Months 0.177626E+10 0.110374E+10 0.717070E+09 0.358384E+10 0.147807E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.964978E+09 0.605357E+09 0.359620E+09 0.120969E+10 0.121308E+10
February 0.859124E+09 0.491458E+09 0.367666E+09 0.957689E+09 0.110906E+10
March 0.119035E+10 0.612325E+09 0.578025E+09 0.153553E+10 0.104604E+10
April 0.164435E+10 0.980052E+09 0.664295E+09 0.270493E+10 0.534852E+09
May 0.176094E+10 0.104387E+10 0.717070E+09 0.309312E+10 0.397916E+09
June 0.177626E+10 0.110374E+10 0.672518E+09 0.358384E+10 0.145652E+09
July 0.155017E+10 0.874079E+09 0.676093E+09 0.316142E+10 0.113158E+09
August 0.147125E+10 0.839640E+09 0.631608E+09 0.297541E+10 0.146190E+09
September 0.116832E+10 0.563149E+09 0.605167E+09 0.227449E+10 0.222104E+09
October 0.121262E+10 0.737992E+09 0.474628E+09 0.188741E+10 0.747622E+09
November 0.902358E+09 0.541698E+09 0.360661E+09 0.112764E+10 0.108966E+10
December 0.850139E+09 0.513339E+09 0.336800E+09 0.922225E+09 0.147807E+10
           
Annual Sum or Average 0.153509E+11 0.890670E+10 0.644415E+10 0.254334E+11 0.824340E+10
Minimum of Months 0.850139E+09 0.491458E+09 0.336800E+09 0.922225E+09 0.113158E+09
Maximum of Months 0.177626E+10 0.110374E+10 0.717070E+09 0.358384E+10 0.147807E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.964960E+09 0.605346E+09 0.359614E+09 0.120966E+10 0.121306E+10
February 0.859108E+09 0.491449E+09 0.367659E+09 0.957671E+09 0.110904E+10
March 0.119033E+10 0.612314E+09 0.578014E+09 0.153551E+10 0.104602E+10
April 0.164432E+10 0.980034E+09 0.664283E+09 0.270488E+10 0.534842E+09
May 0.176091E+10 0.104385E+10 0.717057E+09 0.309307E+10 0.397909E+09
June 0.177623E+10 0.110372E+10 0.672505E+09 0.358377E+10 0.145649E+09
July 0.155014E+10 0.874063E+09 0.676081E+09 0.316136E+10 0.113156E+09
August 0.147122E+10 0.839624E+09 0.631596E+09 0.297535E+10 0.146188E+09
September 0.116829E+10 0.563138E+09 0.605156E+09 0.227444E+10 0.222100E+09
October 0.121260E+10 0.737979E+09 0.474619E+09 0.188738E+10 0.747608E+09
November 0.902342E+09 0.541688E+09 0.360654E+09 0.112762E+10 0.108964E+10
December 0.850123E+09 0.513329E+09 0.336794E+09 0.922208E+09 0.147804E+10
           
Annual Sum or Average 0.153506E+11 0.890654E+10 0.644403E+10 0.254329E+11 0.824325E+10
Minimum of Months 0.850123E+09 0.491449E+09 0.336794E+09 0.922208E+09 0.113156E+09
Maximum of Months 0.177623E+10 0.110372E+10 0.717057E+09 0.358377E+10 0.147804E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.221365E+10 0.176798E+10 0.445670E+09 0.334434E+10 0.113027E+10
February 0.126421E+10 0.852627E+09 0.411583E+09 0.171101E+10 0.100175E+10
March 0.116462E+10 0.599841E+09 0.564780E+09 0.169258E+10 0.100331E+10
April 0.959417E+09 0.387698E+09 0.571719E+09 0.178785E+10 0.551913E+09
May 0.664339E+09 0.109757E+09 0.554583E+09 0.136397E+10 0.393114E+09
June 0.550516E+09 42437723.04 0.508079E+09 0.149578E+10 0.144578E+09
July 0.581283E+09 60138531.93 0.521144E+09 0.150817E+10 0.113386E+09
August 0.706812E+09 0.195328E+09 0.511484E+09 0.173996E+10 0.153799E+09
September 0.985596E+09 0.420480E+09 0.565116E+09 0.205854E+10 0.221396E+09
October 0.162279E+10 0.112321E+10 0.499577E+09 0.269756E+10 0.712092E+09
November 0.183016E+10 0.140181E+10 0.428351E+09 0.272538E+10 0.101105E+10
December 0.205804E+10 0.162921E+10 0.428824E+09 0.295345E+10 0.136222E+10
           
Annual Sum or Average 0.146014E+11 0.859052E+10 0.601091E+10 0.250786E+11 0.779887E+10
Minimum of Months 0.550516E+09 42437723.04 0.411583E+09 0.136397E+10 0.113386E+09
Maximum of Months 0.221365E+10 0.176798E+10 0.571719E+09 0.334434E+10 0.136222E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.221365E+10 0.176798E+10 0.445670E+09 0.334433E+10 0.113027E+10
February 0.126421E+10 0.852626E+09 0.411582E+09 0.171101E+10 0.100175E+10
March 0.116462E+10 0.599840E+09 0.564780E+09 0.169258E+10 0.100331E+10
April 0.959416E+09 0.387698E+09 0.571718E+09 0.178785E+10 0.551912E+09
May 0.664339E+09 0.109756E+09 0.554583E+09 0.136397E+10 0.393113E+09
June 0.550516E+09 42437672.12 0.508078E+09 0.149578E+10 0.144578E+09
July 0.581282E+09 60138459.77 0.521144E+09 0.150817E+10 0.113386E+09
August 0.706811E+09 0.195328E+09 0.511483E+09 0.173996E+10 0.153799E+09
September 0.985595E+09 0.420479E+09 0.565116E+09 0.205854E+10 0.221396E+09
October 0.162279E+10 0.112321E+10 0.499577E+09 0.269756E+10 0.712092E+09
November 0.183016E+10 0.140181E+10 0.428351E+09 0.272538E+10 0.101104E+10
December 0.205804E+10 0.162921E+10 0.428824E+09 0.295345E+10 0.136222E+10
           
Annual Sum or Average 0.146014E+11 0.859051E+10 0.601091E+10 0.250786E+11 0.779887E+10
Minimum of Months 0.550516E+09 42437672.12 0.411582E+09 0.136397E+10 0.113386E+09
Maximum of Months 0.221365E+10 0.176798E+10 0.571718E+09 0.334433E+10 0.136222E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.221365E+10 0.176798E+10 0.445670E+09 0.334434E+10 0.113027E+10
February 0.126421E+10 0.852627E+09 0.411583E+09 0.171101E+10 0.100175E+10
March 0.116462E+10 0.599841E+09 0.564780E+09 0.169258E+10 0.100331E+10
April 0.959417E+09 0.387698E+09 0.571719E+09 0.178785E+10 0.551913E+09
May 0.664339E+09 0.109757E+09 0.554583E+09 0.136397E+10 0.393114E+09
June 0.550516E+09 42437723.04 0.508079E+09 0.149578E+10 0.144578E+09
July 0.581283E+09 60138531.93 0.521144E+09 0.150817E+10 0.113386E+09
August 0.706812E+09 0.195328E+09 0.511484E+09 0.173996E+10 0.153799E+09
September 0.985596E+09 0.420480E+09 0.565116E+09 0.205854E+10 0.221396E+09
October 0.162279E+10 0.112321E+10 0.499577E+09 0.269756E+10 0.712092E+09
November 0.183016E+10 0.140181E+10 0.428351E+09 0.272538E+10 0.101105E+10
December 0.205804E+10 0.162921E+10 0.428824E+09 0.295345E+10 0.136222E+10
           
Annual Sum or Average 0.146014E+11 0.859052E+10 0.601091E+10 0.250786E+11 0.779887E+10
Minimum of Months 0.550516E+09 42437723.04 0.411583E+09 0.136397E+10 0.113386E+09
Maximum of Months 0.221365E+10 0.176798E+10 0.571719E+09 0.334434E+10 0.136222E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.221365E+10 0.176798E+10 0.445670E+09 0.334433E+10 0.113027E+10
February 0.126421E+10 0.852626E+09 0.411582E+09 0.171101E+10 0.100175E+10
March 0.116462E+10 0.599840E+09 0.564780E+09 0.169258E+10 0.100331E+10
April 0.959416E+09 0.387698E+09 0.571718E+09 0.178785E+10 0.551912E+09
May 0.664339E+09 0.109756E+09 0.554583E+09 0.136397E+10 0.393113E+09
June 0.550516E+09 42437672.12 0.508078E+09 0.149578E+10 0.144578E+09
July 0.581282E+09 60138459.77 0.521144E+09 0.150817E+10 0.113386E+09
August 0.706811E+09 0.195328E+09 0.511483E+09 0.173996E+10 0.153799E+09
September 0.985595E+09 0.420479E+09 0.565116E+09 0.205854E+10 0.221396E+09
October 0.162279E+10 0.112321E+10 0.499577E+09 0.269756E+10 0.712092E+09
November 0.183016E+10 0.140181E+10 0.428351E+09 0.272538E+10 0.101104E+10
December 0.205804E+10 0.162921E+10 0.428824E+09 0.295345E+10 0.136222E+10
           
Annual Sum or Average 0.146014E+11 0.859051E+10 0.601091E+10 0.250786E+11 0.779887E+10
Minimum of Months 0.550516E+09 42437672.12 0.411582E+09 0.136397E+10 0.113386E+09
Maximum of Months 0.221365E+10 0.176798E+10 0.571718E+09 0.334433E+10 0.136222E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.221356E+10 0.176791E+10 0.445652E+09 0.334420E+10 0.113023E+10
February 0.126416E+10 0.852593E+09 0.411566E+09 0.171095E+10 0.100171E+10
March 0.116457E+10 0.599817E+09 0.564758E+09 0.169252E+10 0.100327E+10
April 0.959378E+09 0.387682E+09 0.571696E+09 0.178778E+10 0.551890E+09
May 0.664313E+09 0.109752E+09 0.554561E+09 0.136392E+10 0.393098E+09
June 0.550494E+09 42436012.61 0.508058E+09 0.149572E+10 0.144572E+09
July 0.581259E+09 60136108.09 0.521123E+09 0.150811E+10 0.113381E+09
August 0.706783E+09 0.195320E+09 0.511463E+09 0.173989E+10 0.153793E+09
September 0.985556E+09 0.420463E+09 0.565093E+09 0.205846E+10 0.221387E+09
October 0.162273E+10 0.112317E+10 0.499557E+09 0.269745E+10 0.712064E+09
November 0.183009E+10 0.140175E+10 0.428334E+09 0.272527E+10 0.101100E+10
December 0.205795E+10 0.162915E+10 0.428807E+09 0.295333E+10 0.136216E+10
           
Annual Sum or Average 0.146008E+11 0.859018E+10 0.601067E+10 0.250776E+11 0.779856E+10
Minimum of Months 0.550494E+09 42436012.61 0.411566E+09 0.136392E+10 0.113381E+09
Maximum of Months 0.221356E+10 0.176791E+10 0.571696E+09 0.334420E+10 0.136216E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100906E+10 0.627146E+09 0.381912E+09 0.140854E+10 0.142849E+10
February 0.738329E+09 0.356937E+09 0.381392E+09 0.814530E+09 0.131518E+10
March 0.108272E+10 0.516149E+09 0.566569E+09 0.138650E+10 0.127302E+10
April 0.160892E+10 0.917776E+09 0.691142E+09 0.264616E+10 0.747368E+09
May 0.166682E+10 0.934586E+09 0.732231E+09 0.296801E+10 0.512747E+09
June 0.171483E+10 0.100860E+10 0.706234E+09 0.344913E+10 0.226740E+09
July 0.128970E+10 0.602026E+09 0.687671E+09 0.264471E+10 0.190854E+09
August 0.122984E+10 0.617651E+09 0.612190E+09 0.247947E+10 0.274161E+09
September 0.103743E+10 0.435885E+09 0.601543E+09 0.203809E+10 0.294880E+09
October 0.109689E+10 0.627199E+09 0.469690E+09 0.172949E+10 0.921792E+09
November 0.977673E+09 0.590291E+09 0.387383E+09 0.131535E+10 0.134305E+10
December 0.814229E+09 0.463597E+09 0.350632E+09 0.974070E+09 0.184047E+10
           
Annual Sum or Average 0.142664E+11 0.769784E+10 0.656859E+10 0.238540E+11 0.103687E+11
Minimum of Months 0.738329E+09 0.356937E+09 0.350632E+09 0.814530E+09 0.190854E+09
Maximum of Months 0.171483E+10 0.100860E+10 0.732231E+09 0.344913E+10 0.184047E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100906E+10 0.627146E+09 0.381912E+09 0.140854E+10 0.142849E+10
February 0.738329E+09 0.356937E+09 0.381392E+09 0.814530E+09 0.131518E+10
March 0.108272E+10 0.516149E+09 0.566569E+09 0.138650E+10 0.127302E+10
April 0.160892E+10 0.917776E+09 0.691142E+09 0.264616E+10 0.747368E+09
May 0.166682E+10 0.934586E+09 0.732231E+09 0.296801E+10 0.512747E+09
June 0.171483E+10 0.100860E+10 0.706234E+09 0.344913E+10 0.226740E+09
July 0.128970E+10 0.602026E+09 0.687671E+09 0.264471E+10 0.190854E+09
August 0.122984E+10 0.617651E+09 0.612190E+09 0.247947E+10 0.274161E+09
September 0.103743E+10 0.435885E+09 0.601543E+09 0.203809E+10 0.294880E+09
October 0.109689E+10 0.627199E+09 0.469690E+09 0.172949E+10 0.921792E+09
November 0.977673E+09 0.590291E+09 0.387383E+09 0.131535E+10 0.134305E+10
December 0.814229E+09 0.463597E+09 0.350632E+09 0.974070E+09 0.184047E+10
           
Annual Sum or Average 0.142664E+11 0.769784E+10 0.656859E+10 0.238540E+11 0.103687E+11
Minimum of Months 0.738329E+09 0.356937E+09 0.350632E+09 0.814530E+09 0.190854E+09
Maximum of Months 0.171483E+10 0.100860E+10 0.732231E+09 0.344913E+10 0.184047E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100904E+10 0.627134E+09 0.381906E+09 0.140851E+10 0.142846E+10
February 0.738315E+09 0.356930E+09 0.381385E+09 0.814515E+09 0.131516E+10
March 0.108270E+10 0.516140E+09 0.566559E+09 0.138648E+10 0.127300E+10
April 0.160889E+10 0.917759E+09 0.691130E+09 0.264611E+10 0.747354E+09
May 0.166679E+10 0.934569E+09 0.732217E+09 0.296795E+10 0.512738E+09
June 0.171480E+10 0.100858E+10 0.706221E+09 0.344906E+10 0.226736E+09
July 0.128967E+10 0.602015E+09 0.687658E+09 0.264466E+10 0.190850E+09
August 0.122982E+10 0.617640E+09 0.612179E+09 0.247943E+10 0.274156E+09
September 0.103741E+10 0.435877E+09 0.601532E+09 0.203805E+10 0.294875E+09
October 0.109687E+10 0.627187E+09 0.469682E+09 0.172946E+10 0.921775E+09
November 0.977655E+09 0.590280E+09 0.387376E+09 0.131533E+10 0.134303E+10
December 0.814214E+09 0.463589E+09 0.350626E+09 0.974052E+09 0.184043E+10
           
Annual Sum or Average 0.142662E+11 0.769770E+10 0.656847E+10 0.238536E+11 0.103686E+11
Minimum of Months 0.738315E+09 0.356930E+09 0.350626E+09 0.814515E+09 0.190850E+09
Maximum of Months 0.171480E+10 0.100858E+10 0.732217E+09 0.344906E+10 0.184043E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.134418E+10 0.00 0.134418E+10 0.111294E+10 0.531871E+10
February 0.138344E+10 0.00 0.138344E+10 0.686615E+09 0.480968E+10
March 0.203558E+10 0.00 0.203558E+10 0.192248E+10 0.469223E+10
April 0.240005E+10 24906385.81 0.237515E+10 0.398264E+10 0.247840E+10
May 0.290317E+10 0.232459E+09 0.267071E+10 0.561683E+10 0.173339E+10
June 0.326483E+10 0.593187E+09 0.267165E+10 0.841627E+10 0.694797E+09
July 0.287710E+10 0.299736E+09 0.257736E+10 0.742289E+10 0.546735E+09
August 0.232234E+10 57692224.27 0.226464E+10 0.615167E+10 0.683961E+09
September 0.212041E+10 566046.10 0.211984E+10 0.495745E+10 0.103363E+10
October 0.169519E+10 0.00 0.169519E+10 0.250426E+10 0.337069E+10
November 0.136685E+10 0.00 0.136685E+10 0.107195E+10 0.476422E+10
December 0.125559E+10 0.00 0.125559E+10 0.679298E+09 0.648052E+10
           
Annual Sum or Average 0.249687E+11 0.120855E+10 0.237602E+11 0.445253E+11 0.366069E+11
Minimum of Months 0.125559E+10 0.00 0.125559E+10 0.679298E+09 0.546735E+09
Maximum of Months 0.326483E+10 0.593187E+09 0.267165E+10 0.841627E+10 0.648052E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.289490E+10 0.181605E+10 0.107885E+10 0.366107E+10 0.340047E+10
February 0.257735E+10 0.147436E+10 0.110299E+10 0.287521E+10 0.311500E+10
March 0.357101E+10 0.183696E+10 0.173406E+10 0.458133E+10 0.301066E+10
April 0.493299E+10 0.294013E+10 0.199286E+10 0.803852E+10 0.162991E+10
May 0.528277E+10 0.313158E+10 0.215119E+10 0.920321E+10 0.119632E+10
June 0.532873E+10 0.331120E+10 0.201753E+10 0.106725E+11 0.467182E+09
July 0.465047E+10 0.262221E+10 0.202826E+10 0.940675E+10 0.370029E+09
August 0.441370E+10 0.251889E+10 0.189480E+10 0.886650E+10 0.466506E+09
September 0.350491E+10 0.168943E+10 0.181548E+10 0.676381E+10 0.677642E+09
October 0.363782E+10 0.221395E+10 0.142387E+10 0.562604E+10 0.216505E+10
November 0.270705E+10 0.162508E+10 0.108197E+10 0.339427E+10 0.306907E+10
December 0.255039E+10 0.154000E+10 0.101039E+10 0.283206E+10 0.412692E+10
           
Annual Sum or Average 0.460521E+11 0.267198E+11 0.193323E+11 0.759213E+11 0.236947E+11
Minimum of Months 0.255039E+10 0.147436E+10 0.101039E+10 0.283206E+10 0.370029E+09
Maximum of Months 0.532873E+10 0.331120E+10 0.215119E+10 0.106725E+11 0.412692E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.110681E+11 0.883980E+10 0.222832E+10 0.165912E+11 0.556055E+10
February 0.632097E+10 0.426308E+10 0.205789E+10 0.849495E+10 0.483518E+10
March 0.582304E+10 0.299917E+10 0.282387E+10 0.843348E+10 0.483269E+10
April 0.479703E+10 0.193847E+10 0.285856E+10 0.895263E+10 0.268041E+10
May 0.332166E+10 0.548776E+09 0.277288E+10 0.687098E+10 0.191527E+10
June 0.275255E+10 0.212186E+09 0.254036E+10 0.758738E+10 0.713931E+09
July 0.290638E+10 0.300689E+09 0.260569E+10 0.764233E+10 0.552057E+09
August 0.353402E+10 0.976628E+09 0.255739E+10 0.881145E+10 0.709264E+09
September 0.492792E+10 0.210237E+10 0.282555E+10 0.102655E+11 0.109213E+10
October 0.811386E+10 0.561600E+10 0.249786E+10 0.133932E+11 0.347863E+10
November 0.915068E+10 0.700895E+10 0.214173E+10 0.135386E+11 0.490119E+10
December 0.102901E+11 0.814597E+10 0.214409E+10 0.147161E+11 0.658963E+10
           
Annual Sum or Average 0.730063E+11 0.429521E+11 0.300542E+11 0.125298E+12 0.378609E+11
Minimum of Months 0.275255E+10 0.212186E+09 0.205789E+10 0.687098E+10 0.552057E+09
Maximum of Months 0.110681E+11 0.883980E+10 0.285856E+10 0.165912E+11 0.658963E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.302714E+10 0.188142E+10 0.114573E+10 0.431722E+10 0.385285E+10
February 0.221496E+10 0.107080E+10 0.114416E+10 0.252848E+10 0.337844E+10
March 0.324812E+10 0.154843E+10 0.169969E+10 0.429807E+10 0.330544E+10
April 0.482671E+10 0.275330E+10 0.207341E+10 0.806895E+10 0.194415E+10
May 0.500040E+10 0.280373E+10 0.219667E+10 0.893577E+10 0.143821E+10
June 0.514444E+10 0.302576E+10 0.211868E+10 0.104363E+11 0.607929E+09
July 0.386905E+10 0.180606E+10 0.206299E+10 0.810086E+10 0.466150E+09
August 0.368949E+10 0.185294E+10 0.183655E+10 0.768143E+10 0.578899E+09
September 0.311225E+10 0.130764E+10 0.180461E+10 0.617278E+10 0.786147E+09
October 0.329063E+10 0.188158E+10 0.140906E+10 0.528072E+10 0.244185E+10
November 0.293299E+10 0.177085E+10 0.116214E+10 0.406233E+10 0.344057E+10
December 0.244266E+10 0.139078E+10 0.105189E+10 0.309716E+10 0.459899E+10
           
Annual Sum or Average 0.427989E+11 0.230933E+11 0.197056E+11 0.729801E+11 0.268396E+11
Minimum of Months 0.221496E+10 0.107080E+10 0.105189E+10 0.252848E+10 0.466150E+09
Maximum of Months 0.514444E+10 0.302576E+10 0.219667E+10 0.104363E+11 0.459899E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.134418E+10 0.00 0.134418E+10 0.124230E+10 0.488517E+10
February 0.138344E+10 0.00 0.138344E+10 0.784128E+09 0.433825E+10
March 0.203558E+10 0.00 0.203558E+10 0.201206E+10 0.440534E+10
April 0.240005E+10 24906385.81 0.237515E+10 0.395040E+10 0.243145E+10
May 0.290317E+10 0.232459E+09 0.267071E+10 0.556439E+10 0.173577E+10
June 0.326483E+10 0.593187E+09 0.267165E+10 0.831667E+10 0.718211E+09
July 0.287710E+10 0.299736E+09 0.257736E+10 0.730490E+10 0.575111E+09
August 0.232234E+10 57692224.27 0.226464E+10 0.606292E+10 0.704719E+09
September 0.212041E+10 566046.10 0.211984E+10 0.489160E+10 0.104836E+10
October 0.169519E+10 0.00 0.169519E+10 0.253658E+10 0.318917E+10
November 0.136685E+10 0.00 0.136685E+10 0.117672E+10 0.437166E+10
December 0.125559E+10 0.00 0.125559E+10 0.822779E+09 0.590217E+10
           
Annual Sum or Average 0.249687E+11 0.120855E+10 0.237602E+11 0.446654E+11 0.343054E+11
Minimum of Months 0.125559E+10 0.00 0.125559E+10 0.784128E+09 0.575111E+09
Maximum of Months 0.326483E+10 0.593187E+09 0.267165E+10 0.831667E+10 0.590217E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.289490E+10 0.181605E+10 0.107885E+10 0.377041E+10 0.316262E+10
February 0.257735E+10 0.147436E+10 0.110299E+10 0.295438E+10 0.284588E+10
March 0.357101E+10 0.183696E+10 0.173406E+10 0.465025E+10 0.286005E+10
April 0.493299E+10 0.294013E+10 0.199286E+10 0.802274E+10 0.161186E+10
May 0.528277E+10 0.313158E+10 0.215119E+10 0.917174E+10 0.119632E+10
June 0.532873E+10 0.331120E+10 0.201753E+10 0.106143E+11 0.480473E+09
July 0.465047E+10 0.262221E+10 0.202826E+10 0.934157E+10 0.386875E+09
August 0.441370E+10 0.251889E+10 0.189480E+10 0.881914E+10 0.477440E+09
September 0.350491E+10 0.168943E+10 0.181548E+10 0.673122E+10 0.687125E+09
October 0.363782E+10 0.221395E+10 0.142387E+10 0.565203E+10 0.207380E+10
November 0.270705E+10 0.162508E+10 0.108197E+10 0.348373E+10 0.284843E+10
December 0.255039E+10 0.154000E+10 0.101039E+10 0.298379E+10 0.377713E+10
           
Annual Sum or Average 0.460521E+11 0.267198E+11 0.193323E+11 0.761953E+11 0.224080E+11
Minimum of Months 0.255039E+10 0.147436E+10 0.101039E+10 0.295438E+10 0.386875E+09
Maximum of Months 0.532873E+10 0.331120E+10 0.215119E+10 0.106143E+11 0.377713E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.110681E+11 0.883980E+10 0.222832E+10 0.166961E+11 0.523253E+10
February 0.632097E+10 0.426308E+10 0.205789E+10 0.858586E+10 0.444885E+10
March 0.582304E+10 0.299917E+10 0.282387E+10 0.849071E+10 0.459061E+10
April 0.479703E+10 0.193847E+10 0.285856E+10 0.890511E+10 0.263492E+10
May 0.332166E+10 0.548776E+09 0.277288E+10 0.681385E+10 0.190708E+10
June 0.275255E+10 0.212186E+09 0.254036E+10 0.748744E+10 0.733581E+09
July 0.290638E+10 0.300689E+09 0.260569E+10 0.752403E+10 0.577660E+09
August 0.353402E+10 0.976628E+09 0.255739E+10 0.871813E+10 0.726823E+09
September 0.492792E+10 0.210237E+10 0.282555E+10 0.101907E+11 0.110848E+10
October 0.811386E+10 0.561600E+10 0.249786E+10 0.133971E+11 0.334167E+10
November 0.915068E+10 0.700895E+10 0.214173E+10 0.136245E+11 0.460846E+10
December 0.102901E+11 0.814597E+10 0.214409E+10 0.148618E+11 0.614340E+10
           
Annual Sum or Average 0.730063E+11 0.429521E+11 0.300542E+11 0.125295E+12 0.360541E+11
Minimum of Months 0.275255E+10 0.212186E+09 0.205789E+10 0.681385E+10 0.577660E+09
Maximum of Months 0.110681E+11 0.883980E+10 0.285856E+10 0.166961E+11 0.614340E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.302714E+10 0.188142E+10 0.114573E+10 0.436983E+10 0.360491E+10
February 0.221496E+10 0.107080E+10 0.114416E+10 0.256967E+10 0.311418E+10
March 0.324812E+10 0.154843E+10 0.169969E+10 0.432822E+10 0.314206E+10
April 0.482671E+10 0.275330E+10 0.207341E+10 0.803019E+10 0.191061E+10
May 0.500040E+10 0.280373E+10 0.219667E+10 0.888551E+10 0.143060E+10
June 0.514444E+10 0.302576E+10 0.211868E+10 0.103647E+11 0.619068E+09
July 0.386905E+10 0.180606E+10 0.206299E+10 0.802792E+10 0.480348E+09
August 0.368949E+10 0.185294E+10 0.183655E+10 0.762293E+10 0.588362E+09
September 0.311225E+10 0.130764E+10 0.180461E+10 0.612600E+10 0.795025E+09
October 0.329063E+10 0.188158E+10 0.140906E+10 0.527942E+10 0.233903E+10
November 0.293299E+10 0.177085E+10 0.116214E+10 0.409943E+10 0.322396E+10
December 0.244266E+10 0.139078E+10 0.105189E+10 0.316643E+10 0.427136E+10
           
Annual Sum or Average 0.427989E+11 0.230933E+11 0.197056E+11 0.728702E+11 0.255195E+11
Minimum of Months 0.221496E+10 0.107080E+10 0.105189E+10 0.256967E+10 0.480348E+09
Maximum of Months 0.514444E+10 0.302576E+10 0.219667E+10 0.103647E+11 0.427136E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 341.67 2226.01 501.86 0.00 501.86 0.00 0.00
February 233.72 2245.11 571.86 0.00 571.86 0.00 0.00
March 660.10 1931.30 760.00 0.00 760.00 0.00 0.00
April 1482.21 1014.00 925.95 9.61 916.34 0.00 0.00
May 2067.04 666.70 1083.92 86.79 997.13 0.00 0.00
June 3214.02 264.84 1259.59 228.85 1030.73 0.00 0.00
July 2732.76 206.33 1074.19 111.91 962.28 0.00 0.00
August 2232.97 280.84 867.06 21.54 845.52 0.00 0.00
September 1887.91 411.81 818.06 0.22 817.84 0.00 0.00
October 887.03 1372.80 632.92 0.00 632.92 0.00 0.00
November 351.39 2077.28 527.34 0.00 527.34 0.00 0.00
December 171.56 2783.15 468.79 0.00 468.79 0.00 0.00
               
Annual Sum or Average 1360.27 1285.98 791.76 38.32 753.43 0.00 0.00
Minimum of Months 171.56 206.33 468.79 0.00 468.79 0.00 0.00
Maximum of Months 3214.02 2783.15 1259.59 228.85 1030.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1354.93 1358.73 1080.84 678.04 402.80 0.00 0.00
February 1187.60 1375.31 1065.38 609.44 455.93 0.00 0.00
March 1719.90 1171.63 1333.27 685.84 647.43 0.00 0.00
April 3130.69 619.04 1903.17 1134.31 768.86 0.00 0.00
May 3464.50 445.69 1972.37 1169.20 803.17 0.00 0.00
June 4147.94 168.58 2055.85 1277.47 778.37 0.00 0.00
July 3540.99 126.74 1736.29 979.02 757.27 0.00 0.00
August 3332.65 163.74 1647.89 940.45 707.44 0.00 0.00
September 2632.49 257.06 1352.21 651.79 700.42 0.00 0.00
October 2114.02 837.38 1358.21 826.60 531.61 0.00 0.00
November 1305.13 1261.18 1044.39 626.96 417.43 0.00 0.00
December 1032.95 1655.53 952.21 574.97 377.24 0.00 0.00
               
Annual Sum or Average 2419.45 784.19 1460.31 847.28 613.02 0.00 0.00
Minimum of Months 1032.95 126.74 952.21 574.97 377.24 0.00 0.00
Maximum of Months 4147.94 1655.53 2055.85 1277.47 803.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 6243.11 2109.96 4132.38 3300.42 831.96 0.00 0.00
February 3536.29 2070.41 2612.85 1762.19 850.65 0.00 0.00
March 3159.67 1872.94 2174.08 1119.77 1054.32 0.00 0.00
April 3448.76 1064.64 1850.71 747.87 1102.84 0.00 0.00
May 2546.23 733.85 1240.17 204.89 1035.28 0.00 0.00
June 2885.36 278.89 1061.94 81.86 980.08 0.00 0.00
July 2815.42 211.67 1085.12 112.26 972.86 0.00 0.00
August 3248.11 287.11 1319.45 364.63 954.82 0.00 0.00
September 3970.93 427.07 1901.21 811.10 1090.11 0.00 0.00
October 5035.72 1329.31 3029.38 2096.78 932.60 0.00 0.00
November 5257.25 1950.30 3530.37 2704.08 826.29 0.00 0.00
December 5513.42 2542.95 3841.88 3041.37 800.52 0.00 0.00
               
Annual Sum or Average 3976.16 1236.49 2315.02 1362.01 953.02 0.00 0.00
Minimum of Months 2546.23 211.67 1061.94 81.86 800.52 0.00 0.00
Maximum of Months 6243.11 2542.95 4132.38 3300.42 1102.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1577.65 1600.00 1130.21 702.44 427.77 0.00 0.00
February 1010.08 1630.92 915.58 442.63 472.95 0.00 0.00
March 1552.97 1425.86 1212.72 578.12 634.59 0.00 0.00
April 3062.66 865.00 1862.16 1062.23 799.93 0.00 0.00
May 3324.36 574.31 1866.94 1046.80 820.15 0.00 0.00
June 3992.02 262.43 1984.75 1167.35 817.40 0.00 0.00
July 2962.25 213.77 1444.54 674.31 770.24 0.00 0.00
August 2777.17 307.08 1377.50 691.81 685.69 0.00 0.00
September 2358.89 341.29 1200.72 504.49 696.23 0.00 0.00
October 1937.14 1032.47 1228.59 702.50 526.08 0.00 0.00
November 1522.39 1554.45 1131.56 683.20 448.36 0.00 0.00
December 1091.02 2061.44 911.99 519.26 392.73 0.00 0.00
               
Annual Sum or Average 2269.21 986.37 1357.15 732.29 624.86 0.00 0.00
Minimum of Months 1010.08 213.77 911.99 442.63 392.73 0.00 0.00
Maximum of Months 3992.02 2061.44 1984.75 1167.35 820.15 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 415.52 1985.78 501.86 0.00 501.86 0.00 0.00
February 283.82 1988.13 571.86 0.00 571.86 0.00 0.00
March 717.77 1751.88 760.00 0.00 760.00 0.00 0.00
April 1536.51 956.17 925.95 9.61 916.34 0.00 0.00
May 2097.08 647.17 1083.92 86.79 997.13 0.00 0.00
June 3247.02 268.05 1259.58 228.85 1030.73 0.00 0.00
July 2771.39 204.13 1074.18 111.91 962.28 0.00 0.00
August 2296.77 255.36 867.06 21.54 845.52 0.00 0.00
September 1912.60 398.78 818.06 0.22 817.84 0.00 0.00
October 934.98 1258.47 632.91 0.00 632.91 0.00 0.00
November 413.56 1838.05 527.33 0.00 527.33 0.00 0.00
December 253.62 2419.55 468.78 0.00 468.78 0.00 0.00
               
Annual Sum or Average 1411.89 1160.80 791.75 38.32 753.43 0.00 0.00
Minimum of Months 253.62 204.13 468.78 0.00 468.78 0.00 0.00
Maximum of Months 3247.02 2419.55 1259.58 228.85 1030.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1366.89 1269.59 1080.83 678.04 402.80 0.00 0.00
February 1188.50 1287.61 1065.37 609.44 455.93 0.00 0.00
March 1710.47 1124.05 1333.26 685.84 647.42 0.00 0.00
April 3101.28 628.82 1903.16 1134.31 768.85 0.00 0.00
May 3436.09 446.65 1972.36 1169.20 803.16 0.00 0.00
June 4117.48 180.24 2055.84 1277.47 778.37 0.00 0.00
July 3512.08 138.15 1736.29 979.02 757.26 0.00 0.00
August 3310.37 174.17 1647.89 940.45 707.44 0.00 0.00
September 2609.49 261.44 1352.20 651.79 700.42 0.00 0.00
October 2100.52 808.34 1358.21 826.60 531.61 0.00 0.00
November 1309.52 1184.06 1044.39 626.96 417.43 0.00 0.00
December 1057.37 1540.81 952.21 574.97 377.24 0.00 0.00
               
Annual Sum or Average 2407.45 751.36 1460.30 847.28 613.02 0.00 0.00
Minimum of Months 1057.37 138.15 952.21 574.97 377.24 0.00 0.00
Maximum of Months 4117.48 1540.81 2055.84 1277.47 803.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 6194.45 2076.07 4132.36 3300.40 831.96 0.00 0.00
February 3511.47 1998.67 2612.84 1762.19 850.65 0.00 0.00
March 3148.70 1804.32 2174.07 1119.76 1054.31 0.00 0.00
April 3453.95 1034.11 1850.70 747.87 1102.84 0.00 0.00
May 2565.33 715.08 1240.16 204.89 1035.28 0.00 0.00
June 2927.23 275.44 1061.94 81.86 980.08 0.00 0.00
July 2853.32 206.11 1085.12 112.26 972.85 0.00 0.00
August 3289.82 264.81 1319.45 364.63 954.82 0.00 0.00
September 3960.44 421.34 1901.20 811.10 1090.10 0.00 0.00
October 5000.47 1298.77 3029.37 2096.77 932.59 0.00 0.00
November 5223.23 1890.89 3530.36 2704.07 826.29 0.00 0.00
December 5494.37 2460.28 3841.87 3041.36 800.51 0.00 0.00
               
Annual Sum or Average 3973.17 1200.56 2315.01 1362.00 953.01 0.00 0.00
Minimum of Months 2565.33 206.11 1061.94 81.86 800.51 0.00 0.00
Maximum of Months 6194.45 2460.28 4132.36 3300.40 1102.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1611.86 1438.49 1130.21 702.44 427.76 0.00 0.00
February 1045.17 1396.51 915.58 442.63 472.95 0.00 0.00
March 1604.72 1234.11 1212.71 578.12 634.59 0.00 0.00
April 3113.02 750.06 1862.16 1062.23 799.93 0.00 0.00
May 3336.23 536.97 1866.94 1046.79 820.14 0.00 0.00
June 4026.36 234.54 1984.74 1167.35 817.39 0.00 0.00
July 3024.52 174.04 1444.54 674.31 770.23 0.00 0.00
August 2867.92 216.14 1377.50 691.81 685.69 0.00 0.00
September 2381.47 303.30 1200.71 504.49 696.22 0.00 0.00
October 1971.60 911.68 1228.58 702.50 526.08 0.00 0.00
November 1567.26 1327.38 1131.55 683.20 448.35 0.00 0.00
December 1156.35 1717.07 911.99 519.26 392.73 0.00 0.00
               
Annual Sum or Average 2314.18 851.08 1357.14 732.28 624.86 0.00 0.00
Minimum of Months 1045.17 174.04 911.99 442.63 392.73 0.00 0.00
Maximum of Months 4026.36 1717.07 1984.74 1167.35 820.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 463.82 1823.91 501.86 0.00 501.86 0.00 0.00
February 324.13 1793.26 571.86 0.00 571.86 0.00 0.00
March 751.22 1644.77 760.00 0.00 760.00 0.00 0.00
April 1524.07 938.06 925.95 9.61 916.34 0.00 0.00
May 2077.51 648.06 1083.92 86.79 997.13 0.00 0.00
June 3208.59 277.09 1259.58 228.85 1030.73 0.00 0.00
July 2727.34 214.72 1074.18 111.91 962.28 0.00 0.00
August 2263.63 263.11 867.06 21.54 845.52 0.00 0.00
September 1887.19 404.46 818.06 0.22 817.84 0.00 0.00
October 947.05 1190.70 632.91 0.00 632.91 0.00 0.00
November 453.98 1686.60 527.33 0.00 527.33 0.00 0.00
December 307.19 2203.62 468.78 0.00 468.78 0.00 0.00
               
Annual Sum or Average 1416.33 1087.82 791.75 38.32 753.43 0.00 0.00
Minimum of Months 307.19 214.72 468.78 0.00 468.78 0.00 0.00
Maximum of Months 3208.59 2203.62 1259.58 228.85 1030.73 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1407.71 1180.79 1080.83 678.04 402.80 0.00 0.00
February 1221.22 1176.37 1065.37 609.44 455.93 0.00 0.00
March 1736.21 1067.82 1333.26 685.84 647.42 0.00 0.00
April 3095.19 621.86 1903.16 1134.31 768.85 0.00 0.00
May 3424.33 446.65 1972.36 1169.20 803.16 0.00 0.00
June 4095.04 185.37 2055.84 1277.47 778.37 0.00 0.00
July 3487.74 144.44 1736.29 979.02 757.26 0.00 0.00
August 3292.69 178.26 1647.89 940.45 707.44 0.00 0.00
September 2596.92 265.09 1352.20 651.79 700.42 0.00 0.00
October 2110.23 774.27 1358.21 826.60 531.61 0.00 0.00
November 1344.03 1098.93 1044.39 626.96 417.43 0.00 0.00
December 1114.02 1410.22 952.21 574.97 377.24 0.00 0.00
               
Annual Sum or Average 2416.14 710.55 1460.30 847.28 613.02 0.00 0.00
Minimum of Months 1114.02 144.44 952.21 574.97 377.24 0.00 0.00
Maximum of Months 4095.04 1410.22 2055.84 1277.47 803.16 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 6233.62 1953.60 4132.36 3300.40 831.96 0.00 0.00
February 3549.05 1838.98 2612.84 1762.19 850.65 0.00 0.00
March 3170.07 1713.94 2174.07 1119.76 1054.31 0.00 0.00
April 3435.61 1016.56 1850.70 747.87 1102.84 0.00 0.00
May 2544.00 712.02 1240.16 204.89 1035.28 0.00 0.00
June 2888.67 283.02 1061.94 81.86 980.08 0.00 0.00
July 2809.15 215.67 1085.12 112.26 972.85 0.00 0.00
August 3254.98 271.36 1319.45 364.63 954.82 0.00 0.00
September 3931.61 427.65 1901.20 811.10 1090.10 0.00 0.00
October 5001.91 1247.64 3029.37 2096.77 932.59 0.00 0.00
November 5256.37 1777.95 3530.36 2704.07 826.29 0.00 0.00
December 5548.75 2293.68 3841.87 3041.36 800.51 0.00 0.00
               
Annual Sum or Average 3973.09 1143.27 2315.01 1362.00 953.01 0.00 0.00
Minimum of Months 2544.00 215.67 1061.94 81.86 800.51 0.00 0.00
Maximum of Months 6233.62 2293.68 4132.36 3300.40 1102.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1631.51 1345.92 1130.21 702.44 427.76 0.00 0.00
February 1062.20 1287.28 915.58 442.63 472.95 0.00 0.00
March 1615.97 1173.11 1212.71 578.12 634.59 0.00 0.00
April 3098.07 737.12 1862.16 1062.23 799.93 0.00 0.00
May 3317.47 534.12 1866.94 1046.79 820.14 0.00 0.00
June 3998.71 238.84 1984.74 1167.35 817.39 0.00 0.00
July 2997.28 179.34 1444.54 674.31 770.23 0.00 0.00
August 2846.08 219.67 1377.50 691.81 685.69 0.00 0.00
September 2363.43 306.72 1200.71 504.49 696.22 0.00 0.00
October 1971.11 873.29 1228.58 702.50 526.08 0.00 0.00
November 1581.57 1243.81 1131.55 683.20 448.35 0.00 0.00
December 1182.21 1594.74 911.99 519.26 392.73 0.00 0.00
               
Annual Sum or Average 2310.70 809.22 1357.14 732.28 624.86 0.00 0.00
Minimum of Months 1062.20 179.34 911.99 442.63 392.73 0.00 0.00
Maximum of Months 3998.71 1594.74 1984.74 1167.35 820.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.915130E+09 0.596216E+10 0.134419E+10 0.00 0.134419E+10 0.00 0.00
February 0.565426E+09 0.543136E+10 0.138344E+10 0.00 0.138344E+10 0.00 0.00
March 0.176802E+10 0.517279E+10 0.203559E+10 0.00 0.203559E+10 0.00 0.00
April 0.384188E+10 0.262829E+10 0.240006E+10 24906474.26 0.237516E+10 0.00 0.00
May 0.553635E+10 0.178569E+10 0.290318E+10 0.232460E+09 0.267072E+10 0.00 0.00
June 0.833075E+10 0.686476E+09 0.326485E+10 0.593189E+09 0.267166E+10 0.00 0.00
July 0.731941E+10 0.552627E+09 0.287711E+10 0.299737E+09 0.257737E+10 0.00 0.00
August 0.598078E+10 0.752198E+09 0.232234E+10 57692429.13 0.226465E+10 0.00 0.00
September 0.489346E+10 0.106742E+10 0.212042E+10 566048.11 0.211985E+10 0.00 0.00
October 0.237583E+10 0.367692E+10 0.169520E+10 0.00 0.169520E+10 0.00 0.00
November 0.910793E+09 0.538431E+10 0.136685E+10 0.00 0.136685E+10 0.00 0.00
December 0.459517E+09 0.745438E+10 0.125560E+10 0.00 0.125560E+10 0.00 0.00
               
Annual Sum or Average 0.428973E+11 0.405546E+11 0.249688E+11 0.120855E+10 0.237603E+11 0.00 0.00
Minimum of Months 0.459517E+09 0.552627E+09 0.125560E+10 0.00 0.125560E+10 0.00 0.00
Maximum of Months 0.833075E+10 0.745438E+10 0.326485E+10 0.593189E+09 0.267166E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.362904E+10 0.363922E+10 0.289492E+10 0.181606E+10 0.107885E+10 0.00 0.00
February 0.287305E+10 0.332715E+10 0.257736E+10 0.147437E+10 0.110299E+10 0.00 0.00
March 0.460658E+10 0.313811E+10 0.357103E+10 0.183696E+10 0.173406E+10 0.00 0.00
April 0.811475E+10 0.160454E+10 0.493301E+10 0.294014E+10 0.199287E+10 0.00 0.00
May 0.927931E+10 0.119374E+10 0.528279E+10 0.313159E+10 0.215120E+10 0.00 0.00
June 0.107515E+11 0.436953E+09 0.532875E+10 0.331121E+10 0.201754E+10 0.00 0.00
July 0.948420E+10 0.339471E+09 0.465049E+10 0.262222E+10 0.202827E+10 0.00 0.00
August 0.892616E+10 0.438569E+09 0.441372E+10 0.251890E+10 0.189481E+10 0.00 0.00
September 0.682342E+10 0.666309E+09 0.350492E+10 0.168944E+10 0.181549E+10 0.00 0.00
October 0.566220E+10 0.224285E+10 0.363784E+10 0.221396E+10 0.142388E+10 0.00 0.00
November 0.338289E+10 0.326897E+10 0.270706E+10 0.162508E+10 0.108198E+10 0.00 0.00
December 0.276666E+10 0.443418E+10 0.255040E+10 0.154001E+10 0.101039E+10 0.00 0.00
               
Annual Sum or Average 0.762997E+11 0.247301E+11 0.460523E+11 0.267199E+11 0.193323E+11 0.00 0.00
Minimum of Months 0.276666E+10 0.339471E+09 0.255040E+10 0.147437E+10 0.101039E+10 0.00 0.00
Maximum of Months 0.107515E+11 0.443418E+10 0.532875E+10 0.331121E+10 0.215120E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.167215E+11 0.565131E+10 0.110682E+11 0.883983E+10 0.222833E+10 0.00 0.00
February 0.855500E+10 0.500872E+10 0.632100E+10 0.426310E+10 0.205790E+10 0.00 0.00
March 0.846285E+10 0.501649E+10 0.582306E+10 0.299918E+10 0.282388E+10 0.00 0.00
April 0.893918E+10 0.275954E+10 0.479704E+10 0.193847E+10 0.285857E+10 0.00 0.00
May 0.681981E+10 0.196555E+10 0.332167E+10 0.548778E+09 0.277289E+10 0.00 0.00
June 0.747886E+10 0.722883E+09 0.275256E+10 0.212187E+09 0.254037E+10 0.00 0.00
July 0.754081E+10 0.566925E+09 0.290639E+10 0.300690E+09 0.260570E+10 0.00 0.00
August 0.869974E+10 0.768990E+09 0.353403E+10 0.976632E+09 0.255740E+10 0.00 0.00
September 0.102926E+11 0.110697E+10 0.492794E+10 0.210238E+10 0.282556E+10 0.00 0.00
October 0.134877E+11 0.356043E+10 0.811389E+10 0.561602E+10 0.249787E+10 0.00 0.00
November 0.136268E+11 0.505518E+10 0.915072E+10 0.700898E+10 0.214174E+10 0.00 0.00
December 0.147671E+11 0.681103E+10 0.102901E+11 0.814600E+10 0.214410E+10 0.00 0.00
               
Annual Sum or Average 0.125392E+12 0.389940E+11 0.730065E+11 0.429523E+11 0.300543E+11 0.00 0.00
Minimum of Months 0.681981E+10 0.566925E+09 0.275256E+10 0.212187E+09 0.205790E+10 0.00 0.00
Maximum of Months 0.167215E+11 0.681103E+10 0.110682E+11 0.883983E+10 0.285857E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.422558E+10 0.428543E+10 0.302716E+10 0.188143E+10 0.114573E+10 0.00 0.00
February 0.244358E+10 0.394552E+10 0.221497E+10 0.107080E+10 0.114417E+10 0.00 0.00
March 0.415948E+10 0.381904E+10 0.324814E+10 0.154844E+10 0.169970E+10 0.00 0.00
April 0.793842E+10 0.224209E+10 0.482673E+10 0.275331E+10 0.207341E+10 0.00 0.00
May 0.890397E+10 0.153823E+10 0.500042E+10 0.280374E+10 0.219668E+10 0.00 0.00
June 0.103473E+11 0.680217E+09 0.514446E+10 0.302577E+10 0.211869E+10 0.00 0.00
July 0.793409E+10 0.572558E+09 0.386907E+10 0.180607E+10 0.206300E+10 0.00 0.00
August 0.743837E+10 0.822477E+09 0.368950E+10 0.185294E+10 0.183656E+10 0.00 0.00
September 0.611424E+10 0.884636E+09 0.311227E+10 0.130765E+10 0.180462E+10 0.00 0.00
October 0.518844E+10 0.276536E+10 0.329065E+10 0.188158E+10 0.140906E+10 0.00 0.00
November 0.394603E+10 0.402912E+10 0.293300E+10 0.177086E+10 0.116214E+10 0.00 0.00
December 0.292219E+10 0.552137E+10 0.244267E+10 0.139078E+10 0.105189E+10 0.00 0.00
               
Annual Sum or Average 0.715617E+11 0.311061E+11 0.427990E+11 0.230934E+11 0.197056E+11 0.00 0.00
Minimum of Months 0.244358E+10 0.572558E+09 0.221497E+10 0.107080E+10 0.105189E+10 0.00 0.00
Maximum of Months 0.103473E+11 0.552137E+10 0.514446E+10 0.302577E+10 0.219668E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.111294E+10 0.531871E+10 0.134418E+10 0.00 0.134418E+10 0.00 0.00
February 0.686615E+09 0.480968E+10 0.138344E+10 0.00 0.138344E+10 0.00 0.00
March 0.192248E+10 0.469223E+10 0.203558E+10 0.00 0.203558E+10 0.00 0.00
April 0.398264E+10 0.247840E+10 0.240005E+10 24906385.81 0.237515E+10 0.00 0.00
May 0.561683E+10 0.173339E+10 0.290317E+10 0.232459E+09 0.267071E+10 0.00 0.00
June 0.841627E+10 0.694797E+09 0.326483E+10 0.593187E+09 0.267165E+10 0.00 0.00
July 0.742289E+10 0.546735E+09 0.287710E+10 0.299736E+09 0.257736E+10 0.00 0.00
August 0.615167E+10 0.683961E+09 0.232234E+10 57692224.27 0.226464E+10 0.00 0.00
September 0.495745E+10 0.103363E+10 0.212041E+10 566046.10 0.211984E+10 0.00 0.00
October 0.250426E+10 0.337069E+10 0.169519E+10 0.00 0.169519E+10 0.00 0.00
November 0.107195E+10 0.476422E+10 0.136685E+10 0.00 0.136685E+10 0.00 0.00
December 0.679298E+09 0.648052E+10 0.125559E+10 0.00 0.125559E+10 0.00 0.00
               
Annual Sum or Average 0.445253E+11 0.366069E+11 0.249687E+11 0.120855E+10 0.237602E+11 0.00 0.00
Minimum of Months 0.679298E+09 0.546735E+09 0.125559E+10 0.00 0.125559E+10 0.00 0.00
Maximum of Months 0.841627E+10 0.648052E+10 0.326483E+10 0.593187E+09 0.267165E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.366107E+10 0.340047E+10 0.289490E+10 0.181605E+10 0.107885E+10 0.00 0.00
February 0.287521E+10 0.311500E+10 0.257735E+10 0.147436E+10 0.110299E+10 0.00 0.00
March 0.458133E+10 0.301066E+10 0.357101E+10 0.183696E+10 0.173406E+10 0.00 0.00
April 0.803852E+10 0.162991E+10 0.493299E+10 0.294013E+10 0.199286E+10 0.00 0.00
May 0.920321E+10 0.119632E+10 0.528277E+10 0.313158E+10 0.215119E+10 0.00 0.00
June 0.106725E+11 0.467182E+09 0.532873E+10 0.331120E+10 0.201753E+10 0.00 0.00
July 0.940675E+10 0.370029E+09 0.465047E+10 0.262221E+10 0.202826E+10 0.00 0.00
August 0.886650E+10 0.466506E+09 0.441370E+10 0.251889E+10 0.189480E+10 0.00 0.00
September 0.676381E+10 0.677642E+09 0.350491E+10 0.168943E+10 0.181548E+10 0.00 0.00
October 0.562604E+10 0.216505E+10 0.363782E+10 0.221395E+10 0.142387E+10 0.00 0.00
November 0.339427E+10 0.306907E+10 0.270705E+10 0.162508E+10 0.108197E+10 0.00 0.00
December 0.283206E+10 0.412692E+10 0.255039E+10 0.154000E+10 0.101039E+10 0.00 0.00
               
Annual Sum or Average 0.759213E+11 0.236947E+11 0.460521E+11 0.267198E+11 0.193323E+11 0.00 0.00
Minimum of Months 0.283206E+10 0.370029E+09 0.255039E+10 0.147436E+10 0.101039E+10 0.00 0.00
Maximum of Months 0.106725E+11 0.412692E+10 0.532873E+10 0.331120E+10 0.215119E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.165912E+11 0.556055E+10 0.110681E+11 0.883980E+10 0.222832E+10 0.00 0.00
February 0.849495E+10 0.483518E+10 0.632097E+10 0.426308E+10 0.205789E+10 0.00 0.00
March 0.843348E+10 0.483269E+10 0.582304E+10 0.299917E+10 0.282387E+10 0.00 0.00
April 0.895263E+10 0.268041E+10 0.479703E+10 0.193847E+10 0.285856E+10 0.00 0.00
May 0.687098E+10 0.191527E+10 0.332166E+10 0.548776E+09 0.277288E+10 0.00 0.00
June 0.758738E+10 0.713931E+09 0.275255E+10 0.212186E+09 0.254036E+10 0.00 0.00
July 0.764233E+10 0.552057E+09 0.290638E+10 0.300689E+09 0.260569E+10 0.00 0.00
August 0.881145E+10 0.709264E+09 0.353402E+10 0.976628E+09 0.255739E+10 0.00 0.00
September 0.102655E+11 0.109213E+10 0.492792E+10 0.210237E+10 0.282555E+10 0.00 0.00
October 0.133932E+11 0.347863E+10 0.811386E+10 0.561600E+10 0.249786E+10 0.00 0.00
November 0.135386E+11 0.490119E+10 0.915068E+10 0.700895E+10 0.214173E+10 0.00 0.00
December 0.147161E+11 0.658963E+10 0.102901E+11 0.814597E+10 0.214409E+10 0.00 0.00
               
Annual Sum or Average 0.125298E+12 0.378609E+11 0.730063E+11 0.429521E+11 0.300542E+11 0.00 0.00
Minimum of Months 0.687098E+10 0.552057E+09 0.275255E+10 0.212186E+09 0.205789E+10 0.00 0.00
Maximum of Months 0.165912E+11 0.658963E+10 0.110681E+11 0.883980E+10 0.285856E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.431722E+10 0.385285E+10 0.302714E+10 0.188142E+10 0.114573E+10 0.00 0.00
February 0.252848E+10 0.337844E+10 0.221496E+10 0.107080E+10 0.114416E+10 0.00 0.00
March 0.429807E+10 0.330544E+10 0.324812E+10 0.154843E+10 0.169969E+10 0.00 0.00
April 0.806895E+10 0.194415E+10 0.482671E+10 0.275330E+10 0.207341E+10 0.00 0.00
May 0.893577E+10 0.143821E+10 0.500040E+10 0.280373E+10 0.219667E+10 0.00 0.00
June 0.104363E+11 0.607929E+09 0.514444E+10 0.302576E+10 0.211868E+10 0.00 0.00
July 0.810086E+10 0.466150E+09 0.386905E+10 0.180606E+10 0.206299E+10 0.00 0.00
August 0.768143E+10 0.578899E+09 0.368949E+10 0.185294E+10 0.183655E+10 0.00 0.00
September 0.617278E+10 0.786147E+09 0.311225E+10 0.130764E+10 0.180461E+10 0.00 0.00
October 0.528072E+10 0.244185E+10 0.329063E+10 0.188158E+10 0.140906E+10 0.00 0.00
November 0.406233E+10 0.344057E+10 0.293299E+10 0.177085E+10 0.116214E+10 0.00 0.00
December 0.309716E+10 0.459899E+10 0.244266E+10 0.139078E+10 0.105189E+10 0.00 0.00
               
Annual Sum or Average 0.729801E+11 0.268396E+11 0.427989E+11 0.230933E+11 0.197056E+11 0.00 0.00
Minimum of Months 0.252848E+10 0.466150E+09 0.221496E+10 0.107080E+10 0.105189E+10 0.00 0.00
Maximum of Months 0.104363E+11 0.459899E+10 0.514444E+10 0.302576E+10 0.219667E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.124230E+10 0.488517E+10 0.134418E+10 0.00 0.134418E+10 0.00 0.00
February 0.784128E+09 0.433825E+10 0.138344E+10 0.00 0.138344E+10 0.00 0.00
March 0.201206E+10 0.440534E+10 0.203558E+10 0.00 0.203558E+10 0.00 0.00
April 0.395040E+10 0.243145E+10 0.240005E+10 24906385.81 0.237515E+10 0.00 0.00
May 0.556439E+10 0.173577E+10 0.290317E+10 0.232459E+09 0.267071E+10 0.00 0.00
June 0.831667E+10 0.718211E+09 0.326483E+10 0.593187E+09 0.267165E+10 0.00 0.00
July 0.730490E+10 0.575111E+09 0.287710E+10 0.299736E+09 0.257736E+10 0.00 0.00
August 0.606292E+10 0.704719E+09 0.232234E+10 57692224.27 0.226464E+10 0.00 0.00
September 0.489160E+10 0.104836E+10 0.212041E+10 566046.10 0.211984E+10 0.00 0.00
October 0.253658E+10 0.318917E+10 0.169519E+10 0.00 0.169519E+10 0.00 0.00
November 0.117672E+10 0.437166E+10 0.136685E+10 0.00 0.136685E+10 0.00 0.00
December 0.822779E+09 0.590217E+10 0.125559E+10 0.00 0.125559E+10 0.00 0.00
               
Annual Sum or Average 0.446654E+11 0.343054E+11 0.249687E+11 0.120855E+10 0.237602E+11 0.00 0.00
Minimum of Months 0.784128E+09 0.575111E+09 0.125559E+10 0.00 0.125559E+10 0.00 0.00
Maximum of Months 0.831667E+10 0.590217E+10 0.326483E+10 0.593187E+09 0.267165E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.377041E+10 0.316262E+10 0.289490E+10 0.181605E+10 0.107885E+10 0.00 0.00
February 0.295438E+10 0.284588E+10 0.257735E+10 0.147436E+10 0.110299E+10 0.00 0.00
March 0.465025E+10 0.286005E+10 0.357101E+10 0.183696E+10 0.173406E+10 0.00 0.00
April 0.802274E+10 0.161186E+10 0.493299E+10 0.294013E+10 0.199286E+10 0.00 0.00
May 0.917174E+10 0.119632E+10 0.528277E+10 0.313158E+10 0.215119E+10 0.00 0.00
June 0.106143E+11 0.480473E+09 0.532873E+10 0.331120E+10 0.201753E+10 0.00 0.00
July 0.934157E+10 0.386875E+09 0.465047E+10 0.262221E+10 0.202826E+10 0.00 0.00
August 0.881914E+10 0.477440E+09 0.441370E+10 0.251889E+10 0.189480E+10 0.00 0.00
September 0.673122E+10 0.687125E+09 0.350491E+10 0.168943E+10 0.181548E+10 0.00 0.00
October 0.565203E+10 0.207380E+10 0.363782E+10 0.221395E+10 0.142387E+10 0.00 0.00
November 0.348373E+10 0.284843E+10 0.270705E+10 0.162508E+10 0.108197E+10 0.00 0.00
December 0.298379E+10 0.377713E+10 0.255039E+10 0.154000E+10 0.101039E+10 0.00 0.00
               
Annual Sum or Average 0.761953E+11 0.224080E+11 0.460521E+11 0.267198E+11 0.193323E+11 0.00 0.00
Minimum of Months 0.295438E+10 0.386875E+09 0.255039E+10 0.147436E+10 0.101039E+10 0.00 0.00
Maximum of Months 0.106143E+11 0.377713E+10 0.532873E+10 0.331120E+10 0.215119E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.166961E+11 0.523253E+10 0.110681E+11 0.883980E+10 0.222832E+10 0.00 0.00
February 0.858586E+10 0.444885E+10 0.632097E+10 0.426308E+10 0.205789E+10 0.00 0.00
March 0.849071E+10 0.459061E+10 0.582304E+10 0.299917E+10 0.282387E+10 0.00 0.00
April 0.890511E+10 0.263492E+10 0.479703E+10 0.193847E+10 0.285856E+10 0.00 0.00
May 0.681385E+10 0.190708E+10 0.332166E+10 0.548776E+09 0.277288E+10 0.00 0.00
June 0.748744E+10 0.733581E+09 0.275255E+10 0.212186E+09 0.254036E+10 0.00 0.00
July 0.752403E+10 0.577660E+09 0.290638E+10 0.300689E+09 0.260569E+10 0.00 0.00
August 0.871813E+10 0.726823E+09 0.353402E+10 0.976628E+09 0.255739E+10 0.00 0.00
September 0.101907E+11 0.110848E+10 0.492792E+10 0.210237E+10 0.282555E+10 0.00 0.00
October 0.133971E+11 0.334167E+10 0.811386E+10 0.561600E+10 0.249786E+10 0.00 0.00
November 0.136245E+11 0.460846E+10 0.915068E+10 0.700895E+10 0.214173E+10 0.00 0.00
December 0.148618E+11 0.614340E+10 0.102901E+11 0.814597E+10 0.214409E+10 0.00 0.00
               
Annual Sum or Average 0.125295E+12 0.360541E+11 0.730063E+11 0.429521E+11 0.300542E+11 0.00 0.00
Minimum of Months 0.681385E+10 0.577660E+09 0.275255E+10 0.212186E+09 0.205789E+10 0.00 0.00
Maximum of Months 0.166961E+11 0.614340E+10 0.110681E+11 0.883980E+10 0.285856E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.436983E+10 0.360491E+10 0.302714E+10 0.188142E+10 0.114573E+10 0.00 0.00
February 0.256967E+10 0.311418E+10 0.221496E+10 0.107080E+10 0.114416E+10 0.00 0.00
March 0.432822E+10 0.314206E+10 0.324812E+10 0.154843E+10 0.169969E+10 0.00 0.00
April 0.803019E+10 0.191061E+10 0.482671E+10 0.275330E+10 0.207341E+10 0.00 0.00
May 0.888551E+10 0.143060E+10 0.500040E+10 0.280373E+10 0.219667E+10 0.00 0.00
June 0.103647E+11 0.619068E+09 0.514444E+10 0.302576E+10 0.211868E+10 0.00 0.00
July 0.802792E+10 0.480348E+09 0.386905E+10 0.180606E+10 0.206299E+10 0.00 0.00
August 0.762293E+10 0.588362E+09 0.368949E+10 0.185294E+10 0.183655E+10 0.00 0.00
September 0.612600E+10 0.795025E+09 0.311225E+10 0.130764E+10 0.180461E+10 0.00 0.00
October 0.527942E+10 0.233903E+10 0.329063E+10 0.188158E+10 0.140906E+10 0.00 0.00
November 0.409943E+10 0.322396E+10 0.293299E+10 0.177085E+10 0.116214E+10 0.00 0.00
December 0.316643E+10 0.427136E+10 0.244266E+10 0.139078E+10 0.105189E+10 0.00 0.00
               
Annual Sum or Average 0.728702E+11 0.255195E+11 0.427989E+11 0.230933E+11 0.197056E+11 0.00 0.00
Minimum of Months 0.256967E+10 0.480348E+09 0.221496E+10 0.107080E+10 0.105189E+10 0.00 0.00
Maximum of Months 0.103647E+11 0.427136E+10 0.514444E+10 0.302576E+10 0.219667E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 14.83 7.47 -0.8 2.99 -0.8 34.08 283.26 0.00
February 12.72 9.35 6.24 2.64 2.53 52.02 191.85 0.02
March 15.42 8.67 1.96 3.53 3.02 74.19 207.67 0.01
April 23.31 10.14 -4.1 3.42 6.81 72.47 350.22 0.00
May 26.31 11.07 -4.9 3.62 8.60 75.22 359.64 0.00
June 31.20 14.28 0.18 3.69 15.53 67.31 396.02 0.00
July 30.42 17.99 9.86 3.72 19.28 82.46 278.62 0.02
August 29.82 18.15 11.14 3.33 18.26 71.82 270.19 0.02
September 27.75 17.59 11.45 3.72 17.29 82.54 200.28 0.01
October 20.87 10.99 1.63 3.42 6.03 49.01 269.00 0.00
November 15.43 8.80 1.49 3.02 1.83 40.49 251.35 0.01
December 11.86 4.25 -5.9 2.21 -4.3 34.74 244.35 0.00
                 
Annual Sum or Average 21.70 11.57 2.33 3.28 7.86 61.39 275.62 0.01
Minimum of Months 11.86 4.25 -5.9 2.21 -4.3 34.08 191.85 0.00
Maximum of Months 31.20 18.15 11.45 3.72 19.28 82.54 396.02 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 29.00 31-JAN-15:00 10.73 -14.0 2.10 7.75 109.00 697.00
February 22.00 18-FEB-14:09 14.42 9.67 5.20 14.10 264.00 225.33
March 28.80 16-MAR-15:20 13.79 1.47 3.77 14.35 156.17 666.17
April 35.00 14-APR-14:00 14.57 -4.0 1.50 19.70 150.00 819.50
May 37.00 15-MAY-16:00 15.57 -2.0 4.60 20.75 127.50 679.00
June 42.00 16-JUN-15:00 16.74 -5.0 5.70 25.49 135.00 753.50
July 40.00 12-JUL-13:00 19.40 7.00 2.10 27.95 147.00 3.00
August 41.00 25-AUG-14:09 17.27 -0.7 3.43 25.74 162.33 768.67
September 38.30 08-SEP-14:00 19.81 10.00 3.00 25.82 142.00 699.00
October 37.00 01-OCT-12:00 19.01 9.00 4.10 27.14 262.50 136.00
November 29.00 01-NOV-14:00 16.20 8.00 2.60 16.49 73.50 907.50
December 26.00 21-DEC-14:00 10.90 -5.0 2.60 7.35 68.50 756.50
                 
Annual Sum or Average                
Minimum of Months 22.00   10.73 -14.0 1.50 7.35 68.50 3.00
Maximum of Months 42.00   19.81 10.00 5.70 27.95 264.00 907.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.50 01-JAN-07:00 -1.2 -3.3 3.30 -16.2 17.50 352.00
February 5.00 01-FEB-04:00 3.59 2.00 3.10 -10.7 0.00 0.00
March 0.50 26-MAR-03:00 -2.4 -6.7 2.50 -17.0 0.00 0.00
April 8.00 21-APR-03:00 0.42 -14.0 1.00 -11.7 0.00 0.00
May 12.00 01-MAY-03:00 3.97 -7.0 2.60 -6.2 0.00 0.00
June 18.00 21-JUN-04:00 8.24 -2.0 1.50 3.48 0.00 0.00
July 18.00 01-JUL-05:00 6.53 -9.0 3.10 -1.2 16.00 325.00
August 17.00 05-AUG-17:00 15.02 14.00 5.70 11.46 29.00 0.00
September 16.60 22-SEP-05:00 13.83 12.20 3.00 4.92 0.00 0.00
October 5.00 25-OCT-05:00 0.48 -6.0 3.10 -12.7 0.00 0.00
November 0.00 23-NOV-05:00 -2.5 -6.0 2.10 -17.3 0.00 0.00
December -1.1 07-DEC-04:00 -5.6 -16.0 3.10 -20.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -5.6 -16.0 1.00 -20.8 0.00 0.00
Maximum of Months 18.00   15.02 14.00 5.70 11.46 29.00 352.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.66 08-JAN-15:00 18.00 16.00 4.60 11.46 102.00 332.00
February 14.73 18-FEB-17:00 16.00 14.00 6.20 10.50 0.00 0.00
March 15.18 17-MAR-10:00 25.50 8.30 2.50 18.46 167.50 459.00
April 15.71 11-APR-14:00 33.00 3.00 2.10 15.94 178.50 758.00
May 15.57 15-MAY-16:00 37.00 -2.0 4.60 20.75 127.50 679.00
June 23.18 17-JUN-15:00 41.00 16.00 3.60 31.13 257.00 9.00
July 23.11 13-JUL-17:00 26.00 22.00 4.60 22.13 79.00 56.50
August 22.19 16-AUG-10:00 35.00 17.00 2.10 24.33 140.50 837.00
September 22.23 01-SEP-11:00 34.40 17.20 4.60 23.82 193.50 725.50
October 21.53 01-OCT-17:00 32.00 17.00 2.10 25.33 30.50 1.50
November 18.59 12-NOV-14:00 20.00 18.00 3.10 15.39 115.00 0.00
December 12.06 12-DEC-12:00 20.00 6.00 1.50 12.60 182.50 6.00
                 
Annual Sum or Average                
Minimum of Months 12.06   16.00 -2.0 1.50 10.50 0.00 0.00
Maximum of Months 23.18   41.00 22.00 6.20 31.13 257.00 837.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.00 08-JAN-15:00 18.00 16.66 4.60 11.46 102.00 332.00
February 14.00 18-FEB-17:00 16.00 14.73 6.20 10.50 0.00 0.00
March 13.30 06-MAR-10:00 14.40 13.70 6.10 10.69 254.50 82.00
April 8.00 15-APR-20:00 23.00 14.00 6.20 7.75 0.00 0.00
May 9.00 26-MAY-02:00 21.00 13.75 3.60 16.30 0.00 0.00
June 16.00 17-JUN-15:00 41.00 23.18 3.60 31.13 257.00 9.00
July 22.00 13-JUL-17:00 26.00 23.11 4.60 22.13 79.00 56.50
August 20.00 09-AUG-17:00 25.00 21.44 5.10 19.17 35.00 0.00
September 20.50 02-SEP-22:10 22.62 21.05 3.18 20.17 0.00 0.00
October 19.00 03-OCT-02:00 23.00 20.15 2.10 10.30 0.00 0.00
November 18.00 12-NOV-14:00 20.00 18.59 3.10 15.39 115.00 0.00
December 10.00 12-DEC-23:00 12.00 10.87 1.50 7.55 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 8.00   12.00 10.87 1.50 7.55 0.00 0.00
Maximum of Months 22.00   41.00 23.18 6.20 31.13 257.00 332.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 18.65 31.23 0.00
February 18.00 13.00 16.00 19.06 29.93 0.00
March 18.00 13.00 16.00 20.99 39.76 0.00
April 18.00 13.00 16.00 24.03 60.89 0.00
May 18.00 13.00 16.00 27.32 65.75 0.00
June 18.00 13.00 16.00 29.99 69.24 0.00
July 18.00 13.00 16.00 31.31 56.42 0.00
August 18.00 13.00 16.00 30.91 52.05 0.00
September 18.00 13.00 16.00 28.91 42.71 0.00
October 18.00 13.00 16.00 25.85 39.20 0.00
November 18.00 13.00 16.00 22.56 30.64 0.00
December 18.00 13.00 16.00 19.93 27.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 24.99 45.50 0.00
Minimum of Months 18.00 13.00 16.00 18.65 27.41 0.00
Maximum of Months 18.00 13.00 16.00 31.31 69.24 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.331036E+11 -0.320831E+11 0.00 0.00 744.00 0.00 -0.102041E+10 58.97 0.00 0.00
February 0.297890E+11 -0.288642E+11 0.00 0.00 672.00 0.00 -924787838.5 58.97 0.00 0.00
March 0.333167E+11 -0.322895E+11 0.00 0.00 744.00 0.00 -0.102715E+10 58.98 0.00 0.00
April 0.279355E+11 -0.269473E+11 0.00 0.00 720.00 0.00 -988231299.4 58.98 0.00 0.00
May 0.271240E+11 -0.261007E+11 0.00 0.00 744.00 0.00 -0.102336E+10 58.98 0.00 0.00
June 0.246442E+11 -0.236532E+11 0.00 0.00 720.00 0.00 -991008761.5 58.97 0.00 0.00
July 0.224788E+11 -0.214609E+11 0.00 0.00 744.00 0.00 -0.101797E+10 58.97 0.00 0.00
August 0.248816E+11 -0.238596E+11 0.00 0.00 744.00 0.00 -0.102193E+10 58.97 0.00 0.00
September 0.241961E+11 -0.232103E+11 0.00 0.00 720.00 0.00 -985779608.8 58.97 0.00 0.00
October 0.273846E+11 -0.263672E+11 0.00 0.00 744.00 0.00 -0.101742E+10 58.97 0.00 0.00
November 0.294002E+11 -0.284152E+11 0.00 0.00 720.00 0.00 -984976351.4 58.97 0.00 0.00
December 0.313335E+11 -0.303150E+11 0.00 0.00 744.00 0.00 -0.101855E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.335588E+12 -0.323566E+12 0.00 0.00 8760.00 0.00 -0.120216E+11 58.97 0.00 0.00
Minimum of Months 0.224788E+11 -0.322895E+11 0.00 0.00 672.00 0.00 -0.102715E+10 58.97 0.00 0.00
Maximum of Months 0.333167E+11 -0.214609E+11 0.00 0.00 744.00 0.00 -924787838.5 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.50 0.48 01-JAN-07:49 9166.72 39.08 306.50 291.50 2382.83 29.16 193.00 287.17
February 241.00 0.50 0.48 01-FEB-07:49 8257.35 36.51 234.33 265.00 1310.38 23.39 146.00 223.33
March 344.33 0.51 0.48 01-MAR-07:30 1590.94 19.58 47.50 328.83 927.17 20.91 180.00 286.83
April 380.33 0.52 0.48 01-APR-07:40 1238.86 19.19 19.33 333.33 777.78 20.51 129.83 302.83
May 403.17 0.51 0.48 01-MAY-07:10 989.20 18.92 0.00 359.33 623.12 20.31 70.00 318.33
June 418.17 0.51 0.48 01-JUN-06:00 824.79 18.17 0.00 363.17 534.95 19.62 18.50 312.50
July 399.50 0.51 0.48 01-JUL-07:19 950.63 18.61 0.00 363.50 574.85 20.01 78.67 296.67
August 361.83 0.51 0.48 01-AUG-07:30 1087.34 18.97 3.33 337.50 662.74 20.33 90.83 288.17
September 350.17 0.51 0.48 01-SEP-06:00 1543.34 19.93 58.00 318.83 864.62 20.88 177.33 286.33
October 348.00 0.51 0.48 01-OCT-07:10 3150.25 25.23 154.67 314.67 1124.32 20.58 125.50 298.33
November 288.50 0.49 0.48 01-NOV-07:40 8680.98 37.78 282.50 285.33 1589.08 24.32 149.83 263.50
December 290.67 0.49 0.48 01-DEC-07:40 8492.09 39.07 289.33 280.00 2219.15 28.88 188.17 274.33
                         
Annual Sum or Average 4135.50 0.51     3379.43 24.78 1395.50 3841.00 1066.63 22.08 1547.67 3438.33
Minimum of Months 241.00 0.49 0.48   824.79 18.17 0.00 265.00 534.95 19.62 18.50 223.33
Maximum of Months 418.17 0.52 0.48   9166.72 39.08 306.50 363.50 2382.83 29.16 193.00 318.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.51 0.48 01-JAN-07:49 2183.39 24.58 107.50 274.67 1194.77 24.27 103.50 231.83
February 241.00 0.51 0.48 01-FEB-07:40 2630.64 25.04 87.83 254.33 1459.25 24.82 100.83 190.17
March 344.33 0.51 0.48 01-MAR-07:19 2206.07 23.47 100.17 316.00 1158.67 23.56 130.67 282.33
April 380.33 0.50 0.48 01-APR-06:40 3083.22 23.60 112.33 348.17 1725.66 23.89 101.00 326.83
May 403.17 0.49 0.48 01-MAY-05:00 3501.21 24.68 134.17 380.67 1396.04 23.54 84.83 357.33
June 418.17 0.50 0.48 01-JUN-05:49 3514.26 24.13 134.83 386.50 1379.14 23.02 78.00 353.33
July 399.50 0.50 0.48 01-JUL-05:49 3065.31 24.12 128.17 381.33 1243.94 23.02 90.00 325.17
August 361.83 0.50 0.48 01-AUG-06:10 2997.07 23.91 114.50 353.33 1655.91 24.09 109.67 310.17
September 350.17 0.51 0.48 01-SEP-06:30 2374.39 23.56 105.00 318.67 1267.12 23.75 126.33 278.83
October 348.00 0.52 0.48 01-OCT-06:49 2300.61 23.23 103.33 295.00 1232.82 23.16 114.67 256.67
November 288.50 0.50 0.48 01-NOV-07:30 1861.25 23.16 80.33 273.67 978.90 23.03 86.33 209.83
December 290.67 0.51 0.48 01-DEC-07:30 2172.99 25.14 106.33 260.50 1194.23 24.72 103.00 208.67
                         
Annual Sum or Average 4135.50 0.50     2716.37 24.02 1314.50 3842.83 1333.59 23.68 1228.83 3331.17
Minimum of Months 241.00 0.49 0.48   1861.25 23.16 80.33 254.33 978.90 23.02 78.00 190.17
Maximum of Months 418.17 0.52 0.48   3514.26 25.14 134.83 386.50 1725.66 24.82 130.67 357.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.55 0.48 01-JAN-09:30 478.98 15.61 0.00 229.50 329.10 17.49 0.00 145.67
February 241.00 0.54 0.48 01-FEB-09:50 585.71 16.55 0.00 227.33 376.36 18.13 0.00 135.17
March 344.33 0.52 0.48 01-MAR-07:00 669.33 17.76 0.00 303.83 417.59 19.14 3.17 232.17
April 380.33 0.51 0.48 01-APR-07:49 793.16 18.89 0.00 336.17 519.99 20.22 46.67 304.33
May 403.17 0.49 0.48 01-MAY-06:10 931.54 19.66 25.33 388.67 609.72 20.95 93.33 373.17
June 418.17 0.49 0.48 01-JUN-05:49 1074.96 22.44 108.00 400.00 633.70 22.52 139.83 391.17
July 399.50 0.49 0.48 01-JUL-05:00 954.44 21.81 82.67 394.17 604.04 23.01 150.83 360.50
August 361.83 0.50 0.48 01-AUG-07:10 800.66 18.98 0.33 348.50 507.62 20.30 48.00 295.33
September 350.17 0.52 0.48 01-SEP-06:00 759.28 18.31 0.00 315.00 464.10 19.64 12.33 256.67
October 348.00 0.54 0.48 01-OCT-07:49 551.52 16.47 0.00 263.83 367.52 18.06 1.00 190.50
November 288.50 0.54 0.48 01-NOV-08:20 518.34 16.32 0.00 238.50 343.65 18.10 0.00 138.17
December 290.67 0.54 0.48 01-DEC-08:00 481.42 15.79 0.00 216.17 322.82 17.68 0.00 117.00
                         
Annual Sum or Average 4135.50 0.52     741.16 18.49 216.33 3661.67 472.35 19.83 495.17 2939.83
Minimum of Months 241.00 0.49 0.48   478.98 15.61 0.00 216.17 322.82 17.49 0.00 117.00
Maximum of Months 418.17 0.55 0.48   1074.96 22.44 108.00 400.00 633.70 23.01 150.83 391.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.53 0.48 01-JAN-09:30 2347.22 23.99 107.83 248.67 1305.43 23.75 108.67 215.67
February 241.00 0.52 0.48 01-FEB-09:50 2378.79 23.28 82.50 239.50 927.32 21.81 93.17 179.50
March 344.33 0.51 0.48 01-MAR-08:20 2017.77 22.97 95.33 315.17 1090.39 23.26 142.33 277.50
April 380.33 0.51 0.48 01-APR-07:00 2880.93 21.65 85.00 335.00 1595.31 22.26 85.00 309.17
May 403.17 0.50 0.48 01-MAY-07:19 3088.07 19.73 54.50 365.33 1699.37 19.64 55.50 335.83
June 418.17 0.51 0.48 01-JUN-07:10 3142.63 16.66 0.00 372.50 1264.94 19.26 56.17 345.00
July 399.50 0.51 0.48 01-JUL-07:19 2353.83 17.39 3.67 371.83 1054.96 19.59 69.50 325.67
August 361.83 0.51 0.48 01-AUG-07:40 2411.80 19.54 49.17 343.33 1317.18 19.69 50.67 298.50
September 350.17 0.51 0.48 01-SEP-07:19 1927.63 21.72 82.83 318.33 1034.18 22.22 116.17 282.67
October 348.00 0.52 0.48 01-OCT-07:00 2335.20 23.53 112.00 288.50 1269.65 23.57 122.67 256.83
November 288.50 0.52 0.48 01-NOV-08:30 2180.53 23.73 93.00 254.67 1175.66 23.56 96.67 210.83
December 290.67 0.52 0.48 01-DEC-08:00 1833.59 23.24 91.83 241.33 973.90 22.92 102.33 201.83
                         
Annual Sum or Average 4135.50 0.51     2445.39 21.16 857.67 3694.17 1244.96 21.63 1098.83 3239.00
Minimum of Months 241.00 0.50 0.48   1833.59 16.66 0.00 239.50 927.32 19.26 50.67 179.50
Maximum of Months 418.17 0.53 0.48   3142.63 23.99 112.00 372.50 1699.37 23.75 142.33 345.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.50 0.48 01-JAN-07:49 9256.88 38.69 306.33 291.50 2505.87 25.50 145.33 288.17
February 241.00 0.50 0.48 01-FEB-07:49 8318.88 36.07 234.00 265.00 1407.09 19.01 38.33 226.67
March 344.33 0.51 0.48 01-MAR-07:30 1630.15 13.16 2.33 329.00 996.35 16.74 1.83 291.83
April 380.33 0.51 0.48 01-APR-07:30 1275.21 13.41 0.00 333.83 836.27 16.97 0.00 308.50
May 403.17 0.51 0.48 01-MAY-07:10 1014.24 13.30 0.00 360.50 667.29 16.87 0.00 325.17
June 418.17 0.51 0.48 01-JUN-06:49 846.30 12.61 0.00 363.83 572.67 16.21 0.00 322.50
July 399.50 0.51 0.48 01-JUL-07:10 970.53 12.87 0.00 364.83 614.13 16.41 0.00 305.83
August 361.83 0.51 0.48 01-AUG-07:19 1113.85 13.10 0.00 338.67 710.27 16.67 0.00 296.33
September 350.17 0.51 0.48 01-SEP-06:00 1577.54 13.87 10.83 320.00 926.40 16.82 0.00 290.50
October 348.00 0.51 0.48 01-OCT-07:10 3232.10 20.63 139.83 318.17 1220.89 16.33 13.17 300.83
November 288.50 0.49 0.48 01-NOV-07:40 8756.22 37.28 282.17 285.33 1739.06 21.55 89.17 268.67
December 290.67 0.49 0.48 01-DEC-07:40 8573.64 38.67 289.33 280.00 2341.09 25.02 130.50 275.33
                         
Annual Sum or Average 4135.50 0.51     3426.00 20.52 1264.83 3850.67 1141.08 18.36 418.33 3500.33
Minimum of Months 241.00 0.49 0.48   846.30 12.61 0.00 265.00 572.67 16.21 0.00 226.67
Maximum of Months 418.17 0.51 0.48   9256.88 38.69 306.33 364.83 2505.87 25.50 145.33 325.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.51 0.48 01-JAN-07:49 2223.78 22.19 105.17 275.00 1244.13 22.47 74.67 240.33
February 241.00 0.51 0.48 01-FEB-07:40 2678.60 22.49 85.83 255.33 1514.03 22.84 62.83 197.17
March 344.33 0.51 0.48 01-MAR-07:19 2214.85 19.02 86.17 316.50 1215.79 21.16 69.67 286.17
April 380.33 0.50 0.48 01-APR-06:40 3128.81 20.61 112.33 348.17 1794.46 21.46 82.33 330.50
May 403.17 0.49 0.48 01-MAY-05:00 3547.21 21.75 134.17 381.67 1469.49 20.84 72.33 361.00
June 418.17 0.50 0.48 01-JUN-05:49 3569.44 21.13 134.83 387.17 1449.36 20.30 74.83 358.00
July 399.50 0.50 0.48 01-JUL-05:49 3109.29 21.13 128.17 382.33 1309.21 20.31 68.33 331.33
August 361.83 0.50 0.48 01-AUG-06:10 3035.23 20.86 114.50 353.83 1721.37 21.61 83.50 314.67
September 350.17 0.51 0.48 01-SEP-06:30 2420.26 20.63 103.83 319.33 1323.34 21.45 75.17 283.67
October 348.00 0.52 0.48 01-OCT-06:49 2351.56 20.37 102.83 296.50 1288.59 20.89 72.17 263.33
November 288.50 0.50 0.48 01-NOV-07:30 1899.20 20.32 80.17 274.00 1026.09 20.86 52.83 217.33
December 290.67 0.50 0.48 01-DEC-07:30 2208.99 22.78 105.00 261.50 1240.38 22.98 74.00 215.33
                         
Annual Sum or Average 4135.50 0.50     2758.11 21.05 1293.00 3851.33 1393.85 21.33 862.67 3398.83
Minimum of Months 241.00 0.49 0.48   1899.20 19.02 80.17 255.33 1026.09 20.30 52.83 197.17
Maximum of Months 418.17 0.52 0.48   3569.44 22.78 134.83 387.17 1794.46 22.98 83.50 361.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.55 0.48 01-JAN-09:30 488.59 10.03 0.00 231.33 351.23 13.84 0.00 166.67
February 241.00 0.54 0.48 01-FEB-09:39 597.62 11.03 0.00 228.83 401.50 14.64 0.00 150.33
March 344.33 0.52 0.48 01-MAR-07:00 683.44 12.34 0.00 304.83 445.52 15.87 0.00 243.17
April 380.33 0.51 0.48 01-APR-07:30 813.24 13.74 0.00 337.33 556.13 17.32 0.00 310.50
May 403.17 0.49 0.48 01-MAY-06:10 955.77 14.15 2.67 389.50 651.37 17.80 2.67 375.00
June 418.17 0.49 0.48 01-JUN-05:49 1101.70 17.70 81.33 400.83 700.30 20.91 81.50 395.17
July 399.50 0.49 0.48 01-JUL-05:49 976.42 16.91 62.50 394.17 643.54 20.14 62.83 365.67
August 361.83 0.50 0.48 01-AUG-06:00 820.02 13.49 0.00 349.17 542.63 17.12 0.00 302.33
September 350.17 0.52 0.48 01-SEP-06:00 774.40 12.92 0.00 316.17 494.86 16.37 0.00 268.83
October 348.00 0.54 0.48 01-OCT-07:49 564.29 11.02 0.00 266.50 392.61 14.70 0.00 205.83
November 288.50 0.53 0.48 01-NOV-08:09 528.68 10.59 0.00 240.17 366.65 14.42 0.00 157.17
December 290.67 0.54 0.48 01-DEC-08:50 490.23 10.02 0.00 220.17 344.25 13.88 0.00 140.00
                         
Annual Sum or Average 4135.50 0.51     758.17 13.13 146.50 3679.00 506.62 16.70 147.00 3080.67
Minimum of Months 241.00 0.49 0.48   488.59 10.02 0.00 220.17 344.25 13.84 0.00 140.00
Maximum of Months 418.17 0.55 0.48   1101.70 17.70 81.33 400.83 700.30 20.91 81.50 395.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.53 0.48 01-JAN-09:20 2386.59 21.56 105.67 250.67 1356.66 21.90 74.67 221.50
February 241.00 0.52 0.48 01-FEB-09:30 2420.04 20.74 81.17 241.17 975.34 19.48 36.50 184.83
March 344.33 0.51 0.48 01-MAR-08:09 2064.46 19.91 93.67 317.50 1142.85 20.86 65.33 283.33
April 380.33 0.51 0.48 01-APR-07:00 2920.61 18.19 85.00 336.67 1663.66 19.43 55.00 313.67
May 403.17 0.50 0.48 01-MAY-07:19 3126.94 15.77 54.50 366.17 1769.88 16.17 0.00 341.67
June 418.17 0.50 0.48 01-JUN-06:00 3161.30 11.88 0.00 372.83 1333.80 15.73 0.00 350.33
July 399.50 0.51 0.48 01-JUL-07:19 2390.01 12.83 3.67 374.00 1110.62 16.24 0.00 333.00
August 361.83 0.51 0.48 01-AUG-07:30 2443.40 15.63 49.17 344.17 1374.51 16.39 5.00 304.00
September 350.17 0.51 0.48 01-SEP-07:19 1968.16 18.49 81.83 319.00 1085.15 19.66 53.83 286.50
October 348.00 0.52 0.48 01-OCT-07:00 2369.39 20.52 109.33 290.50 1321.06 21.41 81.17 263.50
November 288.50 0.52 0.48 01-NOV-08:20 2161.95 19.72 80.83 255.50 1228.36 21.48 62.50 216.83
December 290.67 0.52 0.48 01-DEC-08:50 1831.33 19.71 80.67 243.50 1020.30 21.01 57.50 208.50
                         
Annual Sum or Average 4135.50 0.51     2475.07 17.55 825.50 3711.67 1302.06 18.91 491.50 3307.67
Minimum of Months 241.00 0.50 0.48   1831.33 11.88 0.00 241.17 975.34 15.73 0.00 184.83
Maximum of Months 418.17 0.53 0.48   3161.30 21.56 109.33 374.00 1769.88 21.90 81.17 350.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.50 0.48 01-JAN-07:49 9257.89 38.68 306.33 291.50 2507.30 25.49 145.33 288.17
February 241.00 0.50 0.48 01-FEB-07:49 8320.89 36.06 234.00 265.17 1408.65 19.00 38.33 226.83
March 344.33 0.51 0.48 01-MAR-07:30 1632.26 13.13 2.33 329.17 997.69 16.72 1.83 292.00
April 380.33 0.51 0.48 01-APR-07:30 1276.52 13.38 0.00 333.83 837.21 16.96 0.00 308.83
May 403.17 0.51 0.48 01-MAY-07:10 1015.19 13.27 0.00 360.67 668.03 16.85 0.00 325.67
June 418.17 0.51 0.48 01-JUN-06:49 846.98 12.58 0.00 363.83 573.26 16.19 0.00 322.50
July 399.50 0.51 0.48 01-JUL-07:10 971.59 12.84 0.00 364.83 614.89 16.39 0.00 306.17
August 361.83 0.51 0.48 01-AUG-07:19 1115.10 13.07 0.00 338.67 711.13 16.65 0.00 296.50
September 350.17 0.51 0.48 01-SEP-06:00 1579.61 13.84 10.83 320.00 927.71 16.80 0.00 290.67
October 348.00 0.51 0.48 01-OCT-07:10 3233.79 20.61 139.83 318.17 1222.12 16.31 13.17 300.83
November 288.50 0.49 0.48 01-NOV-07:40 8757.50 37.27 282.17 285.33 1740.49 21.54 89.17 268.67
December 290.67 0.49 0.48 01-DEC-07:40 8574.53 38.67 289.33 280.00 2342.64 25.00 130.50 275.50
                         
Annual Sum or Average 4135.50 0.51     3427.33 20.50 1264.83 3851.17 1142.18 18.35 418.33 3502.33
Minimum of Months 241.00 0.49 0.48   846.98 12.58 0.00 265.17 573.26 16.19 0.00 226.83
Maximum of Months 418.17 0.51 0.48   9257.89 38.68 306.33 364.83 2507.30 25.49 145.33 325.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.51 0.48 01-JAN-07:49 2224.18 22.16 105.17 275.00 1244.74 22.45 74.67 240.33
February 241.00 0.51 0.48 01-FEB-07:40 2679.37 22.46 85.83 255.50 1514.90 22.83 62.83 197.33
March 344.33 0.51 0.48 01-MAR-07:19 2215.92 18.99 86.17 316.50 1216.82 21.15 69.67 286.17
April 380.33 0.50 0.48 01-APR-06:40 3129.66 20.59 112.33 348.17 1795.45 21.44 82.33 330.67
May 403.17 0.49 0.48 01-MAY-05:00 3548.04 21.72 134.17 381.67 1470.46 20.83 72.33 361.17
June 418.17 0.49 0.48 01-JUN-05:49 3570.07 21.10 134.83 387.17 1450.20 20.28 74.83 358.17
July 399.50 0.50 0.48 01-JUL-05:49 3110.32 21.10 128.17 382.33 1310.22 20.29 68.33 331.33
August 361.83 0.50 0.48 01-AUG-06:10 3036.27 20.83 114.50 353.83 1722.42 21.60 83.50 314.83
September 350.17 0.51 0.48 01-SEP-06:30 2421.59 20.60 103.83 319.50 1324.53 21.44 75.17 283.83
October 348.00 0.52 0.48 01-OCT-06:49 2352.20 20.34 102.83 296.50 1289.38 20.88 72.17 263.50
November 288.50 0.50 0.48 01-NOV-07:30 1899.76 20.29 80.17 274.00 1026.79 20.84 52.83 217.67
December 290.67 0.50 0.48 01-DEC-07:30 2209.47 22.75 105.00 261.50 1241.04 22.96 74.00 215.33
                         
Annual Sum or Average 4135.50 0.50     2758.93 21.03 1293.00 3851.67 1394.75 21.32 862.67 3400.33
Minimum of Months 241.00 0.49 0.48   1899.76 18.99 80.17 255.50 1026.79 20.28 52.83 197.33
Maximum of Months 418.17 0.52 0.48   3570.07 22.75 134.83 387.17 1795.45 22.96 83.50 361.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.55 0.48 01-JAN-09:30 488.74 9.99 0.00 231.33 351.54 13.82 0.00 166.83
February 241.00 0.54 0.48 01-FEB-09:39 598.03 11.00 0.00 228.83 401.94 14.62 0.00 150.67
March 344.33 0.52 0.48 01-MAR-07:00 684.02 12.31 0.00 304.83 446.05 15.85 0.00 243.50
April 380.33 0.51 0.48 01-APR-07:30 813.75 13.70 0.00 337.33 556.69 17.31 0.00 310.50
May 403.17 0.49 0.48 01-MAY-06:10 956.44 14.11 2.67 389.50 652.02 17.78 2.67 375.00
June 418.17 0.49 0.48 01-JUN-05:49 1102.34 17.67 81.33 400.83 700.94 20.90 81.50 395.33
July 399.50 0.49 0.48 01-JUL-05:49 977.27 16.89 62.50 394.17 644.27 20.12 62.83 365.67
August 361.83 0.50 0.48 01-AUG-06:00 820.68 13.46 0.00 349.17 543.23 17.10 0.00 302.67
September 350.17 0.52 0.48 01-SEP-06:00 775.11 12.89 0.00 316.17 495.47 16.35 0.00 269.00
October 348.00 0.54 0.48 01-OCT-07:49 564.60 10.99 0.00 266.50 392.98 14.69 0.00 206.50
November 288.50 0.53 0.48 01-NOV-08:09 528.95 10.56 0.00 240.17 367.02 14.41 0.00 158.33
December 290.67 0.54 0.48 01-DEC-08:50 490.44 9.99 0.00 220.33 344.58 13.86 0.00 140.33
                         
Annual Sum or Average 4135.50 0.51     758.69 13.10 146.50 3679.17 507.15 16.69 147.00 3084.33
Minimum of Months 241.00 0.49 0.48   488.74 9.99 0.00 220.33 344.58 13.82 0.00 140.33
Maximum of Months 418.17 0.55 0.48   1102.34 17.67 81.33 400.83 700.94 20.90 81.50 395.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.53 0.48 01-JAN-09:20 2386.99 21.54 105.67 250.67 1357.37 21.89 74.67 221.50
February 241.00 0.52 0.48 01-FEB-09:30 2420.95 20.71 81.17 241.50 976.29 19.47 36.50 184.83
March 344.33 0.51 0.48 01-MAR-08:09 2065.56 19.89 93.67 317.50 1143.87 20.85 65.33 283.83
April 380.33 0.51 0.48 01-APR-07:00 2921.58 18.16 85.00 336.67 1664.78 19.41 55.00 313.67
May 403.17 0.50 0.48 01-MAY-07:19 3127.85 15.73 54.50 366.17 1770.97 16.16 0.00 341.67
June 418.17 0.50 0.48 01-JUN-06:00 3160.48 11.84 0.00 372.83 1334.75 15.71 0.00 350.33
July 399.50 0.51 0.48 01-JUL-07:19 2369.07 12.80 3.67 373.83 1111.66 16.22 0.00 333.17
August 361.83 0.51 0.48 01-AUG-07:30 2444.37 15.60 49.17 344.33 1375.49 16.37 5.00 304.00
September 350.17 0.51 0.48 01-SEP-07:19 1969.47 18.47 81.83 319.17 1086.28 19.65 53.83 286.67
October 348.00 0.52 0.48 01-OCT-07:00 2370.07 20.49 109.33 290.50 1321.85 21.40 81.17 263.67
November 288.50 0.52 0.48 01-NOV-08:20 2162.47 19.69 80.83 255.50 1229.14 21.46 62.50 217.00
December 290.67 0.52 0.48 01-DEC-08:50 1831.80 19.68 80.67 243.67 1021.01 20.99 57.50 208.50
                         
Annual Sum or Average 4135.50 0.51     2473.64 17.52 825.50 3712.33 1303.01 18.90 491.50 3308.83
Minimum of Months 241.00 0.50 0.48   1831.80 11.84 0.00 241.50 976.29 15.71 0.00 184.83
Maximum of Months 418.17 0.53 0.48   3160.48 21.54 109.33 373.83 1770.97 21.89 81.17 350.33



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.122868E+09 8520.11 12-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.179773E+09 7838.75 01-FEB-07:55 0.00 0.00 0.00 0.00 0.00
March 0.235300E+09 13975.59 27-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 24992123.31 6770.67 25-OCT-06:55 0.00 0.00 0.00 0.00 0.00
November 40805840.24 7249.11 04-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 0.759768E+09 19606.24 06-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.136351E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.759768E+09 19606.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 2114787.22 3738.10 07-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2114787.22     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 2114787.22 3738.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.300260E+10 101344.80 02-JAN-07:20 0.00 0.00 0.00 0.00 0.00
February 0.411065E+10 149819.99 09-FEB-10:05 0.00 0.00 0.00 0.00 0.00
March 0.470790E+10 154483.19 27-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 5888775.72 8277.08 21-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.933276E+09 94008.20 25-OCT-06:55 0.00 0.00 0.00 0.00 0.00
November 0.194618E+10 109359.23 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.166034E+11 193891.33 06-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.313099E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.166034E+11 193891.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.136392E+10 156676.46 02-JAN-05:53 0.00 0.00 0.00 0.00 0.00
February 0.931468E+09 118489.75 03-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.726299E+09 170576.49 28-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 12942690.69 5115.51 26-OCT-05:08 0.00 0.00 0.00 0.00 0.00
November 0.562345E+09 156287.58 24-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.409521E+10 169805.15 05-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.769218E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409521E+10 170576.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.428555E+09 140551.19 02-JAN-05:12 0.00 0.00 0.00 0.00 0.00
February 0.221470E+09 73027.83 13-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.231338E+09 102683.93 27-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.115736E+09 104644.63 24-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.146938E+10 144498.33 05-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.246647E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146938E+10 144498.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.168375E+09 157481.91 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 97990431.30 94946.18 13-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.177097E+09 133532.93 27-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 18354154.51 37208.69 24-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.820729E+09 174377.38 06-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.128255E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.820729E+09 174377.38   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.204419E+09 106986.61 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 64296505.25 34401.30 13-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 50955830.46 60678.35 27-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 59725741.74 76228.93 24-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.105841E+10 137778.79 06-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.143781E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.105841E+10 137778.79   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.595069E+09 13082.81 02-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.826639E+09 11990.05 28-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.783057E+09 18378.65 27-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 9399234.81 4039.52 21-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.230049E+09 11740.78 25-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.424108E+09 14869.18 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.246446E+10 19228.96 06-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.533278E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.246446E+10 19228.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.366112E+09 75731.42 02-JAN-06:05 0.00 0.00 0.00 0.00 0.00
February 0.115823E+09 75627.08 13-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 42449708.54 55299.50 27-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 46632708.97 65501.25 24-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.347833E+09 75479.17 11-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.918851E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.366112E+09 75731.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.834937E+09 18164.82 21-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.740520E+09 18165.78 14-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.478935E+09 18167.24 02-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 993741.42 446.23 21-APR-05:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.120368E+09 18016.13 26-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.547663E+09 18158.62 18-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.189876E+10 18080.10 18-DEC-06:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.462218E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189876E+10 18167.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.324298E+09 16272.30 02-JAN-05:14 0.00 0.00 0.00 0.00 0.00
February 0.305658E+09 16279.54 06-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.190847E+09 16279.28 07-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 45893271.59 12436.74 26-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.191977E+09 16243.07 24-NOV-05:13 0.00 0.00 0.00 0.00 0.00
December 0.750334E+09 16271.90 18-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.180901E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.750334E+09 16279.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.208532E+09 19758.69 02-JAN-05:12 0.00 0.00 0.00 0.00 0.00
February 0.318836E+09 19955.68 13-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.271239E+09 19946.90 07-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 32923271.61 8354.54 26-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.146437E+09 19650.49 24-NOV-05:11 0.00 0.00 0.00 0.00 0.00
December 0.665801E+09 19860.62 18-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.164377E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.665801E+09 19955.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.202880E+09 16798.07 02-JAN-05:12 0.00 0.00 0.00 0.00 0.00
February 0.198322E+09 16810.26 13-FEB-05:11 0.00 0.00 0.00 0.00 0.00
March 0.126236E+09 16777.59 27-MAR-04:11 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 19765724.18 5803.29 26-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.133929E+09 16773.58 24-NOV-05:11 0.00 0.00 0.00 0.00 0.00
December 0.604944E+09 16822.64 18-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.128608E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.604944E+09 16822.64   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 478.65 0.96 31-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 833.03 0.98 21-MAR-04:12 0.00 0.00 0.00 0.00 0.00
April 1186.57 0.97 28-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 424.75 0.96 01-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 169.71 0.85 21-JUN-05:03 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 428.19 0.96 14-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 603.71 0.94 25-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 274.22 0.97 22-DEC-05:12 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4398.82     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1186.57 0.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.400784E+11 0.400672E+11 96948.95 31-JAN-16:50 96948.95 0.01
February 0.00 0.00 0.111162E+11 0.111162E+11 64164.77 21-FEB-15:00 64164.77 0.09
March 0.00 0.00 0.435185E+11 0.435185E+11 107628.51 20-MAR-14:50 107628.51 0.09
April 0.00 0.00 0.112700E+12 0.112700E+12 137615.82 24-APR-15:00 137615.82 0.02
May 0.00 0.00 0.123596E+12 0.123596E+12 127987.22 15-MAY-15:20 127987.22 0.00
June 0.00 0.00 0.166666E+12 0.166666E+12 152306.17 17-JUN-05:02 152306.17 0.11
July 0.00 0.00 0.173992E+12 0.163579E+12 280108.03 18-JUL-05:03 128551.35 0.66
August 0.00 0.00 0.193608E+12 0.182811E+12 260301.02 01-AUG-05:02 125324.90 0.75
September 0.00 0.00 0.138211E+12 0.129106E+12 241536.98 08-SEP-05:02 140972.23 0.58
October 0.00 0.00 0.850340E+11 0.836065E+11 180156.81 03-OCT-04:12 98546.62 0.20
November 0.00 0.00 0.467024E+11 0.440342E+11 135727.76 13-NOV-05:12 47962.66 0.15
December 0.00 0.00 0.297061E+11 0.297061E+11 95635.41 22-DEC-16:30 95635.41 0.00
                 
Annual Sum or Average 0.00 0.00 0.116493E+13 0.113051E+13       0.22
Minimum of Months 0.00 0.00 0.111162E+11 0.111162E+11 64164.77   47962.66 0.00
Maximum of Months 0.00 0.00 0.193608E+12 0.182811E+12 280108.03   152306.17 0.75



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.347440E+12 0.347320E+12 855584.63 31-JAN-16:30 855584.63 0.03
February 0.00 0.00 0.140922E+12 0.140922E+12 580089.64 21-FEB-15:05 580089.64 0.13
March 0.00 0.00 0.331063E+12 0.331063E+12 910320.52 16-MAR-15:50 910320.52 0.09
April 0.00 0.00 0.851962E+12 0.851962E+12 1199266.85 14-APR-15:20 1199266.85 0.01
May 0.00 0.00 0.111208E+13 0.111208E+13 1209990.38 18-MAY-15:10 1209990.38 0.00
June 0.00 0.00 0.148257E+13 0.148257E+13 1414742.62 09-JUN-05:02 1414742.62 0.09
July 0.00 0.00 0.141927E+13 0.134601E+13 2670412.88 18-JUL-05:03 1222635.99 0.57
August 0.00 0.00 0.144322E+13 0.137549E+13 2349338.88 01-AUG-05:02 1142066.98 0.62
September 0.00 0.00 0.119826E+13 0.112308E+13 2311933.47 08-SEP-05:02 1347486.38 0.52
October 0.00 0.00 0.703571E+12 0.691608E+12 1717620.31 03-OCT-04:12 935653.28 0.17
November 0.00 0.00 0.343287E+12 0.330091E+12 977721.89 13-NOV-05:12 343617.22 0.13
December 0.00 0.00 0.214854E+12 0.214854E+12 744229.52 22-DEC-15:05 744229.52 0.01
                 
Annual Sum or Average 0.00 0.00 0.958849E+13 0.934704E+13       0.20
Minimum of Months 0.00 0.00 0.140922E+12 0.140922E+12 580089.64   343617.22 0.00
Maximum of Months 0.00 0.00 0.148257E+13 0.148257E+13 2670412.88   1414742.62 0.62



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.283735E+11 0.283656E+11 89351.45 31-JAN-16:30 89351.45 0.01
February 0.00 0.00 0.601059E+10 0.601059E+10 46684.32 22-FEB-16:00 46684.32 0.10
March 0.00 0.00 0.300810E+11 0.300810E+11 103528.63 16-MAR-15:30 103528.63 0.08
April 0.00 0.00 0.931120E+11 0.931120E+11 142760.61 14-APR-15:20 142760.61 0.01
May 0.00 0.00 0.123028E+12 0.123028E+12 144111.97 18-MAY-15:20 144111.97 0.00
June 0.00 0.00 0.169010E+12 0.169010E+12 170210.03 28-JUN-14:50 170210.03 0.09
July 0.00 0.00 0.161834E+12 0.154244E+12 282624.52 18-JUL-05:03 127656.12 0.58
August 0.00 0.00 0.161121E+12 0.154140E+12 277698.34 01-AUG-05:02 133928.91 0.63
September 0.00 0.00 0.130021E+12 0.122655E+12 257179.95 08-SEP-05:02 150247.80 0.53
October 0.00 0.00 0.701805E+11 0.690767E+11 191406.78 03-OCT-04:12 104714.98 0.16
November 0.00 0.00 0.288837E+11 0.279932E+11 105529.25 01-NOV-15:20 105529.25 0.12
December 0.00 0.00 0.125874E+11 0.125874E+11 75608.92 22-DEC-16:30 75608.92 0.00
                 
Annual Sum or Average 0.00 0.00 0.101424E+13 0.990303E+12       0.19
Minimum of Months 0.00 0.00 0.601059E+10 0.601059E+10 46684.32   46684.32 0.00
Maximum of Months 0.00 0.00 0.169010E+12 0.169010E+12 282624.52   170210.03 0.63



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.246559E+11 0.246519E+11 83325.99 16-JAN-12:20 83325.99 0.00
February 0.00 0.00 0.433835E+10 0.431611E+10 50183.89 17-FEB-06:03 21166.76 0.06
March 0.00 0.00 0.238974E+11 0.238921E+11 62904.85 20-MAR-13:20 62904.85 0.05
April 0.00 0.00 0.579223E+11 0.579223E+11 94211.98 25-APR-03:50 94211.98 0.00
May 0.00 0.00 0.711567E+11 0.711567E+11 114979.42 29-MAY-18:27 114979.42 0.00
June 0.00 0.00 0.868675E+11 0.868675E+11 108670.38 17-JUN-04:03 108670.38 0.07
July 0.00 0.00 0.935453E+11 0.902792E+11 159468.80 14-JUL-04:33 63629.51 0.47
August 0.00 0.00 0.105143E+12 0.101123E+12 152774.24 01-AUG-03:02 80069.07 0.55
September 0.00 0.00 0.888709E+11 0.845644E+11 149135.94 02-SEP-03:02 79841.03 0.48
October 0.00 0.00 0.559904E+11 0.554512E+11 114747.35 15-OCT-13:15 114747.35 0.15
November 0.00 0.00 0.298360E+11 0.276546E+11 103586.05 13-NOV-05:42 37123.84 0.11
December 0.00 0.00 0.132625E+11 0.132602E+11 76991.29 24-DEC-14:40 76991.29 0.00
                 
Annual Sum or Average 0.00 0.00 0.655486E+12 0.641139E+12       0.16
Minimum of Months 0.00 0.00 0.433835E+10 0.431611E+10 50183.89   21166.76 0.00
Maximum of Months 0.00 0.00 0.105143E+12 0.101123E+12 159468.80   114979.42 0.55



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.290146E+11 0.289859E+11 135188.37 27-JAN-16:00 135188.37 0.00
February 0.00 0.00 0.101614E+11 0.957710E+10 100916.56 18-FEB-14:00 86934.26 0.00
March 0.00 0.00 0.193547E+12 0.189645E+12 316930.05 17-MAR-15:20 316930.05 0.00
April 0.00 0.00 0.671619E+12 0.669874E+12 376228.52 15-APR-09:00 376228.52 0.00
May 0.00 0.00 0.217138E+12 0.217138E+12 213492.39 31-MAY-23:10 213492.39 0.00
June 0.00 0.00 0.518437E+12 0.518428E+12 306092.81 30-JUN-23:57 306092.81 0.00
July 0.00 0.00 0.870333E+12 0.787202E+12 467543.62 14-JUL-01:00 154646.21 0.00
August 0.00 0.00 0.106368E+13 0.932815E+12 451581.52 09-AUG-18:30 232765.10 0.00
September 0.00 0.00 0.265972E+12 0.239486E+12 233665.76 04-SEP-10:13 129506.05 0.00
October 0.00 0.00 0.251066E+12 0.240033E+12 336596.21 03-OCT-08:30 223794.62 0.00
November 0.00 0.00 0.202931E+12 0.175642E+12 320010.05 09-NOV-13:05 320010.05 0.00
December 0.00 0.00 0.202669E+12 0.202282E+12 347312.46 25-DEC-13:52 347312.46 0.00
                 
Annual Sum or Average 0.00 0.00 0.449656E+13 0.421111E+13       0.00
Minimum of Months 0.00 0.00 0.101614E+11 0.957710E+10 100916.56   86934.26 0.00
Maximum of Months 0.00 0.00 0.106368E+13 0.932815E+12 467543.62   376228.52 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.547763E+10 0.547443E+10 2840.74 29-JAN-17:15 2840.74 0.00
February 0.00 0.00 0.940569E+10 0.936189E+10 4566.17 20-FEB-17:03 4545.75 0.00
March 0.00 0.00 0.157473E+11 0.157357E+11 7721.38 31-MAR-24:00 7721.38 0.00
April 0.00 0.00 0.199920E+11 0.199920E+11 8286.92 26-APR-18:50 8286.92 0.00
May 0.00 0.00 0.630701E+10 0.630701E+10 4064.96 31-MAY-23:55 4064.96 0.00
June 0.00 0.00 0.112014E+11 0.111999E+11 6001.18 30-JUN-24:00 6001.18 0.00
July 0.00 0.00 0.167090E+11 0.165582E+11 7925.85 31-JUL-23:53 7912.57 0.00
August 0.00 0.00 0.213937E+11 0.212431E+11 8769.85 28-AUG-16:45 8225.80 0.00
September 0.00 0.00 0.628059E+10 0.614313E+10 4063.91 30-SEP-24:00 4063.91 0.00
October 0.00 0.00 0.111175E+11 0.110869E+11 5892.89 31-OCT-24:00 5892.89 0.00
November 0.00 0.00 0.154143E+11 0.153653E+11 6839.71 26-NOV-16:53 6839.71 0.00
December 0.00 0.00 0.206259E+11 0.206254E+11 8366.15 28-DEC-17:00 8366.15 0.00
                 
Annual Sum or Average 0.00 0.00 0.159672E+12 0.159093E+12       0.00
Minimum of Months 0.00 0.00 0.547763E+10 0.547443E+10 2840.74   2840.74 0.00
Maximum of Months 0.00 0.00 0.213937E+11 0.212431E+11 8769.85   8366.15 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.430650E+11 0.430344E+11 25547.41 24-JAN-17:00 25547.41 0.00
February 0.00 0.00 0.809914E+11 0.805601E+11 42053.06 22-FEB-17:00 41521.74 0.00
March 0.00 0.00 0.143980E+12 0.143864E+12 72417.16 31-MAR-23:40 72417.16 0.00
April 0.00 0.00 0.189327E+12 0.189327E+12 78982.55 26-APR-18:50 78982.55 0.00
May 0.00 0.00 0.587126E+11 0.587126E+11 39502.21 31-MAY-23:55 39502.21 0.00
June 0.00 0.00 0.106710E+12 0.106693E+12 57678.52 30-JUN-24:00 57678.52 0.00
July 0.00 0.00 0.158919E+12 0.157418E+12 75724.87 31-JUL-23:53 75594.85 0.00
August 0.00 0.00 0.201718E+12 0.200195E+12 82772.61 28-AUG-16:25 77121.58 0.00
September 0.00 0.00 0.582084E+11 0.568589E+11 39536.66 30-SEP-24:00 39536.66 0.00
October 0.00 0.00 0.101848E+12 0.101545E+12 54737.28 31-OCT-24:00 54737.28 0.00
November 0.00 0.00 0.139850E+12 0.139364E+12 64584.75 14-NOV-17:00 62339.50 0.00
December 0.00 0.00 0.185735E+12 0.185729E+12 78709.06 28-DEC-17:00 78709.06 0.00
                 
Annual Sum or Average 0.00 0.00 0.146907E+13 0.146330E+13       0.00
Minimum of Months 0.00 0.00 0.430650E+11 0.430344E+11 25547.41   25547.41 0.00
Maximum of Months 0.00 0.00 0.201718E+12 0.200195E+12 82772.61   78982.55 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.339174E+10 0.338894E+10 2583.50 24-JAN-17:00 2583.50 0.00
February 0.00 0.00 0.711197E+10 0.706948E+10 4242.70 22-FEB-17:00 4189.23 0.00
March 0.00 0.00 0.137743E+11 0.137628E+11 7082.37 31-MAR-23:20 7082.37 0.00
April 0.00 0.00 0.190025E+11 0.190025E+11 8013.25 26-APR-18:30 8013.25 0.00
May 0.00 0.00 0.593512E+10 0.593512E+10 3961.93 31-MAY-23:55 3961.93 0.00
June 0.00 0.00 0.108602E+11 0.108585E+11 5832.57 30-JUN-24:00 5832.57 0.00
July 0.00 0.00 0.161018E+11 0.159516E+11 7629.59 31-JUL-23:53 7616.48 0.00
August 0.00 0.00 0.203861E+11 0.202326E+11 8393.63 28-AUG-16:15 7795.88 0.00
September 0.00 0.00 0.592197E+10 0.578655E+10 3995.09 30-SEP-24:00 3995.09 0.00
October 0.00 0.00 0.984835E+10 0.981819E+10 5298.65 31-OCT-23:40 5298.65 0.00
November 0.00 0.00 0.131729E+11 0.131247E+11 6486.42 14-NOV-17:00 6261.47 0.00
December 0.00 0.00 0.172443E+11 0.172438E+11 7924.14 26-DEC-17:10 7924.14 0.00
                 
Annual Sum or Average 0.00 0.00 0.142751E+12 0.142175E+12       0.00
Minimum of Months 0.00 0.00 0.339174E+10 0.338894E+10 2583.50   2583.50 0.00
Maximum of Months 0.00 0.00 0.203861E+11 0.202326E+11 8393.63   8013.25 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 2886.17 808979.61 02-JAN-06:03
February 0.00 0.00 01-FEB-00:10 3330.88 593950.10 13-FEB-06:03
March 0.00 0.00 01-MAR-00:10 2970.95 768533.37 27-MAR-05:03
April 0.00 0.00 01-APR-00:10 4.97 9692.30 21-APR-06:10
May 0.00 0.00 01-MAY-00:10 0.00 0.61 01-MAY-05:04
June 0.00 0.00 01-JUN-00:05 0.00 0.54 21-JUN-05:03
July 0.00 0.00 01-JUL-00:05 0.00 0.00 01-JUL-00:05
August 0.00 0.00 01-AUG-00:05 0.00 0.00 01-AUG-00:05
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 513.28 135031.84 25-OCT-06:10
November 0.00 0.00 01-NOV-00:10 1617.88 697355.66 24-NOV-06:03
December 0.00 0.00 01-DEC-00:10 11670.07 915238.40 07-DEC-06:01
             
Annual Sum or Average 0.00     1921.11    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   11670.07 915238.40  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 174523.31 1611526.39 31-JAN-15:05 0.00 0.00 01-JAN-00:05
February 67990.62 766158.57 21-FEB-15:30 0.00 0.00 01-FEB-00:10
March 166183.95 1565433.42 16-MAR-14:05 0.00 0.00 01-MAR-00:10
April 447649.28 1622840.76 03-APR-12:05 0.00 0.00 01-APR-00:10
May 554095.09 1657143.40 25-MAY-12:05 0.00 0.00 01-MAY-00:10
June 752095.20 1924392.65 19-JUN-14:50 0.00 0.00 01-JUN-00:05
July 716852.01 2957029.41 14-JUL-05:03 0.00 0.00 01-JUL-00:05
August 735001.15 2273954.68 01-AUG-05:02 0.00 0.00 01-AUG-00:05
September 627045.71 2271421.49 12-SEP-05:03 0.00 0.00 01-SEP-00:10
October 356331.64 1727923.12 10-OCT-08:55 0.00 0.00 01-OCT-00:10
November 184454.27 1704096.38 02-NOV-14:05 0.00 0.00 01-NOV-00:10
December 104444.51 1337172.75 22-DEC-15:50 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 408962.88     0.00    
Minimum of Months 67990.62 766158.57   0.00 0.00  
Maximum of Months 752095.20 2957029.41   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 172605.03 1437769.10 31-JAN-16:10 0.00 0.00 01-JAN-00:05
February 67039.05 765726.00 21-FEB-15:30 0.00 0.00 01-FEB-00:10
March 164790.57 1402622.78 17-MAR-14:50 0.00 0.00 01-MAR-00:10
April 442036.56 1649626.34 25-APR-05:03 0.00 0.00 01-APR-00:10
May 548191.13 1723602.22 08-MAY-04:11 0.00 0.00 01-MAY-00:10
June 745544.81 2296469.95 09-JUN-05:02 0.00 0.00 01-JUN-00:05
July 713575.23 3559500.46 14-JUL-05:03 0.00 0.00 01-JUL-00:05
August 732363.22 3326058.56 28-AUG-05:03 0.00 0.00 01-AUG-00:05
September 624461.24 3218488.66 02-SEP-05:03 0.00 0.00 01-SEP-00:10
October 353697.50 3245117.49 03-OCT-04:12 0.00 0.00 01-OCT-00:10
November 183393.90 2312927.84 02-NOV-13:30 0.00 0.00 01-NOV-00:10
December 103223.76 1311712.10 22-DEC-15:50 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 405978.16     0.00    
Minimum of Months 67039.05 765726.00   0.00 0.00  
Maximum of Months 745544.81 3559500.46   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 107519.01 861179.38 31-JAN-17:00 0.00 0.00 01-JAN-00:05
February 66044.38 450317.18 18-FEB-14:05 0.00 0.00 01-FEB-00:10
March 294892.00 1295566.46 16-MAR-16:00 0.00 0.00 01-MAR-00:10
April 956838.58 1753037.35 14-APR-16:10 0.00 0.00 01-APR-00:10
May 628601.87 1299445.08 31-MAY-16:00 0.00 0.00 01-MAY-00:10
June 1164572.57 1832979.62 28-JUN-16:00 0.00 0.00 01-JUN-00:05
July 1406839.33 1965679.74 19-JUL-14:00 0.00 0.00 01-JUL-00:05
August 1549124.87 2118031.03 27-AUG-14:05 0.00 0.00 01-AUG-00:05
September 734380.21 1379474.72 08-SEP-16:00 0.00 0.00 01-SEP-00:10
October 474994.03 1518168.65 01-OCT-14:00 0.00 0.00 01-OCT-00:10
November 295153.87 1304197.71 01-NOV-15:00 0.00 0.00 01-NOV-00:10
December 273399.75 1247943.21 25-DEC-16:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 666230.40     0.00    
Minimum of Months 66044.38 450317.18   0.00 0.00  
Maximum of Months 1549124.87 2118031.03   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 13394.82 44380.36 26-JAN-12:10
February 0.00 0.00 01-FEB-00:10 13350.03 44241.77 01-FEB-12:20
March 0.00 0.00 01-MAR-00:10 13472.40 43015.27 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 11814.45 39988.42 03-APR-11:50
May 0.00 0.00 01-MAY-00:10 11167.44 36793.50 01-MAY-11:40
June 0.00 0.00 01-JUN-00:05 10551.60 33479.91 01-JUN-11:30
July 0.00 0.00 01-JUL-00:05 9444.32 31298.69 03-JUL-11:10
August 0.00 0.00 01-AUG-00:05 10336.21 32147.64 31-AUG-12:00
September 0.00 0.00 01-SEP-00:10 10383.40 34804.43 29-SEP-11:10
October 0.00 0.00 01-OCT-00:10 11269.58 38404.75 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 12383.45 41623.34 30-NOV-12:10
December 0.00 0.00 01-DEC-00:10 12738.54 43718.67 29-DEC-12:40
             
Annual Sum or Average 0.00     11683.04    
Minimum of Months 0.00 0.00   9444.32 31298.69  
Maximum of Months 0.00 0.00   13472.40 44380.36  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 200113.36 2179183.04 27-JAN-15:30 946.06 96864.22 13-JAN-06:40
February 79174.00 877050.92 21-FEB-15:30 974.18 80760.29 03-FEB-11:40
March 189415.96 2301785.11 17-MAR-15:30 1264.73 120502.76 25-MAR-06:00
April 572822.32 2369736.00 12-APR-14:30 3543.69 96208.89 23-APR-02:40
May 738351.31 2377723.19 16-MAY-14:30 425.76 88139.56 01-MAY-01:30
June 1060650.41 3903263.11 28-JUN-16:00 596.98 55390.32 07-JUN-03:10
July 1338826.45 4725012.47 14-JUL-05:07 347.98 74690.05 02-JUL-00:50
August 1363792.62 4596172.62 16-AUG-11:00 317.41 75228.37 25-AUG-02:50
September 1078238.41 4758962.30 01-SEP-12:30 27.22 17668.36 20-SEP-00:47
October 493859.55 3783872.84 03-OCT-10:05 912.71 103199.60 12-OCT-06:40
November 220441.13 2227770.78 01-NOV-12:50 1181.42 79352.75 24-NOV-07:40
December 120347.43 2140531.93 22-DEC-16:00 2192.17 126354.47 14-DEC-08:07
             
Annual Sum or Average 624568.08     1058.54    
Minimum of Months 79174.00 877050.92   27.22 17668.36  
Maximum of Months 1363792.62 4758962.30   3543.69 126354.47  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.149887E+11 0.89 9631.77 01-JAN-00:20 1.53
February 0.129783E+11 0.85 9631.77 01-FEB-05:12 1.53
March 0.150256E+11 0.89 9631.77 01-MAR-05:12 1.52
April 0.142034E+11 0.87 9631.77 01-APR-04:12 1.53
May 0.149221E+11 0.89 9631.77 01-MAY-00:13 1.54
June 0.150063E+11 0.92 9631.77 01-JUN-04:11 1.53
July 0.157631E+11 0.93 9631.77 01-JUL-04:12 1.54
August 0.170677E+11 1.00 9631.77 01-AUG-03:02 1.51
September 0.159282E+11 0.97 9631.77 01-SEP-03:03 1.51
October 0.161748E+11 0.96 9631.77 01-OCT-11:22 1.53
November 0.153659E+11 0.94 9631.77 01-NOV-04:12 1.52
December 0.155604E+11 0.93 9631.77 01-DEC-05:12 1.53
           
Annual Sum or Average 0.182984E+12 0.92      
Minimum of Months 0.129783E+11 0.85 9631.77   1.51
Maximum of Months 0.170677E+11 1.00 9631.77   1.54



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.603735E+10 0.42 11900.81 17-JAN-17:00 1.34
February 0.547534E+10 0.41 12238.59 21-FEB-16:00 1.36
March 0.836378E+10 0.51 14638.04 20-MAR-15:00 1.51
April 0.132559E+11 0.76 21667.84 24-APR-05:02 1.96
May 0.121160E+11 0.65 21667.84 08-MAY-04:11 1.95
June 0.150238E+11 0.82 21667.84 01-JUN-04:11 1.94
July 0.153905E+11 0.81 21667.84 05-JUL-04:11 1.95
August 0.182741E+11 0.89 21667.84 01-AUG-05:02 1.93
September 0.113392E+11 0.65 21667.84 01-SEP-05:03 1.93
October 0.942396E+10 0.55 21667.84 02-OCT-04:23 1.93
November 0.793705E+10 0.49 15517.79 20-NOV-17:00 1.58
December 0.706253E+10 0.45 15338.84 26-DEC-17:00 1.57
           
Annual Sum or Average 0.129700E+12 0.62      
Minimum of Months 0.547534E+10 0.41 11900.81   1.34
Maximum of Months 0.182741E+11 0.89 21667.84   1.96



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.402678E+11 0.36 85267.52 31-JAN-17:00 1.14
February 0.334844E+11 0.35 78818.06 03-FEB-06:02 1.08
March 0.486298E+11 0.40 104901.39 16-MAR-15:50 1.28
April 0.842289E+11 0.54 196210.93 25-APR-05:03 1.90
May 0.102508E+12 0.59 204025.10 08-MAY-04:11 1.95
June 0.125121E+12 0.72 204025.10 01-JUN-04:11 1.94
July 0.112045E+12 0.65 204025.10 03-JUL-04:11 1.96
August 0.116337E+12 0.66 204025.10 01-AUG-05:02 1.93
September 0.916202E+11 0.56 204025.10 02-SEP-05:03 1.93
October 0.640942E+11 0.45 204025.10 02-OCT-05:02 1.93
November 0.444005E+11 0.38 97408.33 01-NOV-05:03 1.22
December 0.351743E+11 0.35 103972.58 05-DEC-06:02 1.28
           
Annual Sum or Average 0.897911E+12 0.50      
Minimum of Months 0.334844E+11 0.35 78818.06   1.08
Maximum of Months 0.125121E+12 0.72 204025.10   1.96



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.344562E+10 0.36 7474.25 31-JAN-16:40 0.97
February 0.277004E+10 0.34 6843.43 22-FEB-16:30 0.92
March 0.402323E+10 0.37 10515.79 16-MAR-15:30 1.18
April 0.826065E+10 0.51 16821.39 24-APR-15:20 1.58
May 0.103805E+11 0.57 23167.51 08-MAY-04:11 1.94
June 0.137669E+11 0.73 23167.51 09-JUN-05:02 1.94
July 0.122569E+11 0.66 23167.51 07-JUL-05:02 1.94
August 0.124808E+11 0.65 23167.51 01-AUG-05:02 1.92
September 0.938794E+10 0.55 23167.51 02-SEP-05:03 1.92
October 0.578477E+10 0.42 23167.51 02-OCT-05:02 1.92
November 0.365913E+10 0.36 9323.89 02-NOV-15:50 1.09
December 0.295655E+10 0.35 6760.23 22-DEC-16:50 0.92
           
Annual Sum or Average 0.891730E+11 0.49      
Minimum of Months 0.277004E+10 0.34 6760.23   0.92
Maximum of Months 0.137669E+11 0.73 23167.51   1.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.103419E+12 1.49 38612.35 01-JAN-00:05 1.48
February 0.934110E+11 1.48 38612.35 01-FEB-00:10 1.49
March 0.103419E+12 1.49 38612.35 01-MAR-00:10 1.48
April 0.100083E+12 1.49 38612.35 01-APR-00:10 1.49
May 0.103419E+12 1.49 38612.35 01-MAY-00:10 1.49
June 0.100083E+12 1.48 38612.35 01-JUN-00:05 1.49
July 0.103419E+12 1.48 38612.35 01-JUL-00:05 1.48
August 0.103419E+12 1.47 38612.35 01-AUG-00:05 1.48
September 0.100083E+12 1.47 38612.35 01-SEP-00:10 1.48
October 0.103419E+12 1.49 38612.35 01-OCT-00:10 1.48
November 0.100083E+12 1.49 38612.35 01-NOV-00:10 1.49
December 0.103419E+12 1.49 38612.35 01-DEC-00:10 1.49
           
Annual Sum or Average 0.121768E+13 1.48      
Minimum of Months 0.934110E+11 1.47 38612.35   1.48
Maximum of Months 0.103419E+12 1.49 38612.35   1.49



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.153092E+10 1.01 571.58 01-JAN-00:05 1.01
February 0.138276E+10 1.01 571.58 01-FEB-00:10 1.01
March 0.153092E+10 1.01 571.58 01-MAR-00:10 1.01
April 0.148153E+10 1.01 571.58 01-APR-00:10 1.01
May 0.153092E+10 1.01 571.58 01-MAY-00:10 1.01
June 0.148153E+10 1.01 571.58 01-JUN-00:05 1.01
July 0.153092E+10 1.00 571.58 01-JUL-00:05 1.01
August 0.153092E+10 1.00 571.58 01-AUG-00:05 1.00
September 0.148153E+10 1.00 571.58 01-SEP-00:10 1.00
October 0.153092E+10 1.01 571.58 01-OCT-00:10 1.01
November 0.148153E+10 1.01 571.58 01-NOV-00:10 1.01
December 0.153092E+10 1.01 571.58 01-DEC-00:10 1.01
           
Annual Sum or Average 0.180253E+11 1.01      
Minimum of Months 0.138276E+10 1.00 571.58   1.00
Maximum of Months 0.153092E+10 1.01 571.58   1.01



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.146150E+11 1.01 5456.63 01-JAN-00:05 1.01
February 0.132007E+11 1.01 5456.63 01-FEB-00:10 1.01
March 0.146150E+11 1.01 5456.63 01-MAR-00:10 1.01
April 0.141436E+11 1.01 5456.63 01-APR-00:10 1.01
May 0.146150E+11 1.01 5456.63 01-MAY-00:10 1.01
June 0.141436E+11 1.01 5456.63 01-JUN-00:05 1.01
July 0.146150E+11 1.00 5456.63 01-JUL-00:05 1.01
August 0.146150E+11 1.00 5456.63 01-AUG-00:05 1.00
September 0.141436E+11 1.00 5456.63 01-SEP-00:10 1.00
October 0.146150E+11 1.01 5456.63 01-OCT-00:10 1.01
November 0.141436E+11 1.01 5456.63 01-NOV-00:10 1.01
December 0.146150E+11 1.01 5456.63 01-DEC-00:10 1.01
           
Annual Sum or Average 0.172080E+12 1.01      
Minimum of Months 0.132007E+11 1.00 5456.63   1.00
Maximum of Months 0.146150E+11 1.01 5456.63   1.01



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.149565E+10 1.01 558.41 01-JAN-00:05 1.00
February 0.135091E+10 1.01 558.41 01-FEB-00:10 1.01
March 0.149565E+10 1.01 558.41 01-MAR-00:10 1.01
April 0.144741E+10 1.01 558.41 01-APR-00:10 1.01
May 0.149565E+10 1.01 558.41 01-MAY-00:10 1.01
June 0.144741E+10 1.01 558.41 01-JUN-00:05 1.01
July 0.149565E+10 1.00 558.41 01-JUL-00:05 1.01
August 0.149565E+10 1.00 558.41 01-AUG-00:05 1.00
September 0.144741E+10 1.00 558.41 01-SEP-00:10 1.00
October 0.149565E+10 1.01 558.41 01-OCT-00:10 1.01
November 0.144741E+10 1.01 558.41 01-NOV-00:10 1.01
December 0.149565E+10 1.01 558.41 01-DEC-00:10 1.01
           
Annual Sum or Average 0.176101E+11 1.01      
Minimum of Months 0.135091E+10 1.00 558.41   1.00
Maximum of Months 0.149565E+10 1.01 558.41   1.01



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 35127289.58 31930706.23 2934.50 02-JAN-06:03 2667.46 2667.46 46.94 5.52
February 35665278.96 32419738.58 2250.12 13-FEB-06:03 2045.36 2045.36 39.00 3.30
March 38231740.60 34752652.20 2658.67 27-MAR-05:03 2416.73 2416.73 40.50 4.43
April 64789.54 58893.69 48.72 21-APR-06:10 44.29 44.29 35.85 0.05
May 1.34 1.22 0.00 01-MAY-05:02 0.00 0.00 35.34 0.00
June 0.54 0.49 0.00 21-JUN-05:03 0.00 0.00 35.34 0.00
July 0.00 0.00 0.00 01-JUL-00:05 0.00 0.00 35.34 0.00
August 0.00 0.00 0.00 01-AUG-00:05 0.00 0.00 35.34 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 35.34 0.00
October 6266270.74 5696040.10 579.46 25-OCT-07:00 526.72 526.72 37.88 0.64
November 18842918.24 17128212.68 2473.07 24-NOV-06:03 2248.02 2248.02 38.89 3.87
December 0.153053E+09 0.139125E+09 2931.35 07-DEC-06:01 2664.60 2664.60 42.30 5.52
                 
Annual Sum or Average 0.287251E+09 0.261111E+09            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 35.34 0.00
Maximum of Months 0.153053E+09 0.139125E+09 2934.50   2667.46 2667.46 46.94 5.52



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.174599E+09 0.158711E+09 1165.06 31-JAN-15:30 1059.04 1059.04 7.73 25.98
February 60415084.12 54917311.46 847.90 23-FEB-14:20 770.74 770.74 6.71 22.54
March 0.177666E+09 0.161498E+09 3722.76 17-MAR-14:50 3383.99 3383.99 8.51 42.65
April 0.394355E+09 0.358469E+09 1489.64 25-APR-05:03 1354.09 1354.09 6.71 28.94
May 0.513962E+09 0.467192E+09 1296.25 08-MAY-04:11 1178.29 1178.29 6.70 27.23
June 0.108855E+10 0.989492E+09 6422.22 19-JUN-14:50 5837.80 5837.80 6.72 53.25
July 0.146098E+10 0.132803E+10 10538.80 10-JUL-05:02 9579.77 9579.77 9.74 64.81
August 0.170244E+10 0.154751E+10 10538.80 02-AUG-05:02 9579.77 9579.77 9.73 64.81
September 0.140105E+10 0.127355E+10 10538.80 02-SEP-05:03 9579.77 9579.77 10.47 64.81
October 0.658856E+09 0.598900E+09 10538.80 02-OCT-05:02 9579.77 9579.77 9.38 64.81
November 0.271692E+09 0.246968E+09 9142.84 02-NOV-13:30 8310.85 8310.85 11.24 61.26
December 78397442.05 71263274.82 1073.00 22-DEC-15:50 975.36 975.36 7.89 25.05
                 
Annual Sum or Average 0.798295E+10 0.725650E+10            
Minimum of Months 60415084.12 54917311.46 847.90   770.74 770.74 6.70 22.54
Maximum of Months 0.170244E+10 0.154751E+10 10538.80   9579.77 9579.77 11.24 64.81



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER1 PUMP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.407604E+10 0.370512E+10 3626.79 01-JAN-11:30 3296.75 3296.75 6.72 32.40
February 0.269202E+10 0.244704E+10 3626.79 01-FEB-08:07 3296.75 3296.75 6.75 32.40
March 0.457951E+10 0.416277E+10 3626.79 01-MAR-05:12 3296.75 3296.75 6.95 32.40
April 0.773662E+10 0.703259E+10 3626.79 01-APR-04:12 3296.75 3296.75 7.09 32.40
May 0.709286E+10 0.644741E+10 3626.79 01-MAY-00:10 3296.75 3296.75 6.82 32.40
June 0.880982E+10 0.800813E+10 3626.79 01-JUN-00:05 3296.75 3296.75 6.93 32.40
July 0.905150E+10 0.822781E+10 3626.79 01-JUL-00:05 3296.75 3296.75 7.68 32.40
August 0.906305E+10 0.823831E+10 3626.79 01-AUG-00:05 3296.75 3296.75 8.46 32.40
September 0.721418E+10 0.655769E+10 3626.79 01-SEP-00:10 3296.75 3296.75 6.93 32.40
October 0.606438E+10 0.551253E+10 3626.79 01-OCT-00:15 3296.75 3296.75 7.04 32.40
November 0.440473E+10 0.400390E+10 3626.79 01-NOV-04:12 3296.75 3296.75 9.05 32.40
December 0.372304E+10 0.338424E+10 3626.79 01-DEC-06:02 3296.75 3296.75 6.76 32.40
                 
Annual Sum or Average 0.745077E+11 0.677275E+11            
Minimum of Months 0.269202E+10 0.244704E+10 3626.79   3296.75 3296.75 6.72 32.40
Maximum of Months 0.906305E+10 0.823831E+10 3626.79   3296.75 3296.75 9.05 32.40



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 CHILLER2 PUMP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.175174E+09 0.159233E+09 3626.79 17-JAN-15:40 3296.75 3296.75 14.69 16.20
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 6.72 0.00
March 0.170822E+09 0.155277E+09 3626.79 10-MAR-15:00 3296.75 3296.75 14.48 16.20
April 0.172671E+10 0.156958E+10 3626.79 03-APR-09:35 3296.75 3296.75 11.13 32.40
May 0.266242E+10 0.242014E+10 3626.79 01-MAY-10:20 3296.75 3296.75 14.89 16.20
June 0.386470E+10 0.351301E+10 3626.79 01-JUN-07:20 3296.75 3296.75 14.34 16.20
July 0.335311E+10 0.304798E+10 3626.79 01-JUL-09:50 3296.75 3296.75 14.31 16.20
August 0.348458E+10 0.316749E+10 3626.79 01-AUG-05:02 3296.75 3296.75 15.08 32.40
September 0.270649E+10 0.246020E+10 3626.79 01-SEP-05:07 3296.75 3296.75 15.88 16.20
October 0.127917E+10 0.116276E+10 3626.79 02-OCT-07:20 3296.75 3296.75 16.02 16.20
November 0.245896E+09 0.223520E+09 3626.79 01-NOV-10:40 3296.75 3296.75 15.40 16.20
December 17408570.16 15824390.27 3626.79 22-DEC-15:30 3296.75 3296.75 14.85 16.20
                 
Annual Sum or Average 0.196865E+11 0.178950E+11            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.72 0.00
Maximum of Months 0.386470E+10 0.351301E+10 3626.79   3296.75 3296.75 16.02 32.40



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.909324E+10 0.826575E+10 3395.03 01-JAN-00:05 3086.08 3086.08 18.70 14.32
February 0.821325E+10 0.746584E+10 3395.03 01-FEB-00:10 3086.08 3086.08 19.55 14.32
March 0.909324E+10 0.826575E+10 3395.03 01-MAR-00:10 3086.08 3086.08 19.98 14.32
April 0.879991E+10 0.799912E+10 3395.03 01-APR-00:10 3086.08 3086.08 23.08 14.32
May 0.909324E+10 0.826575E+10 3395.03 01-MAY-00:10 3086.08 3086.08 20.52 14.32
June 0.879991E+10 0.799912E+10 3395.03 01-JUN-00:05 3086.08 3086.08 35.30 14.32
July 0.909324E+10 0.826575E+10 3395.03 01-JUL-00:05 3086.08 3086.08 42.42 14.32
August 0.909324E+10 0.826575E+10 3395.03 01-AUG-00:05 3086.08 3086.08 48.18 14.32
September 0.879991E+10 0.799912E+10 3395.03 01-SEP-00:10 3086.08 3086.08 32.55 14.32
October 0.909324E+10 0.826575E+10 3395.03 01-OCT-00:10 3086.08 3086.08 33.63 14.32
November 0.879991E+10 0.799912E+10 3395.03 01-NOV-00:10 3086.08 3086.08 21.88 14.32
December 0.909324E+10 0.826575E+10 3395.03 01-DEC-00:10 3086.08 3086.08 20.58 14.32
                 
Annual Sum or Average 0.107066E+12 0.973226E+11            
Minimum of Months 0.821325E+10 0.746584E+10 3395.03   3086.08 3086.08 18.70 14.32
Maximum of Months 0.909324E+10 0.826575E+10 3395.03   3086.08 3086.08 48.18 14.32



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.112905E+09 33871561.48 56.21 01-JAN-06:05 16.86 16.86 55.69 0.44
February 0.101979E+09 30593668.43 56.21 01-FEB-06:02 16.86 16.86 56.73 0.44
March 0.112905E+09 33871561.48 56.21 01-MAR-06:03 16.86 16.86 55.87 0.44
April 0.109263E+09 32778930.46 56.21 01-APR-05:03 16.86 16.86 56.25 0.44
May 0.112905E+09 33871561.48 56.21 01-MAY-05:02 16.86 16.86 56.54 0.44
June 0.109263E+09 32778930.46 56.21 01-JUN-05:03 16.86 16.86 57.30 0.44
July 0.112905E+09 33871561.48 56.21 01-JUL-05:03 16.86 16.86 57.23 0.44
August 0.112905E+09 33871561.48 56.21 01-AUG-05:02 16.86 16.86 56.70 0.44
September 0.109263E+09 32778930.46 56.21 01-SEP-05:03 16.86 16.86 56.79 0.44
October 0.112905E+09 33871561.48 56.21 01-OCT-05:10 16.86 16.86 56.48 0.44
November 0.109263E+09 32778930.46 56.21 01-NOV-05:03 16.86 16.86 56.77 0.44
December 0.112905E+09 33871561.48 56.21 01-DEC-06:02 16.86 16.86 57.10 0.44
                 
Annual Sum or Average 0.132937E+10 0.398810E+09            
Minimum of Months 0.101979E+09 30593668.43 56.21   16.86 16.86 55.69 0.44
Maximum of Months 0.112905E+09 33871561.48 56.21   16.86 16.86 57.30 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.159876E+11 0.145327E+11 27918.10 27-JAN-15:30 25377.55 25377.55 25.68 113.89
February 0.103343E+11 0.939385E+10 13948.91 21-FEB-15:30 12679.56 12679.56 24.79 56.94
March 0.178258E+11 0.162036E+11 27924.12 17-MAR-15:30 25383.03 25383.03 25.94 113.89
April 0.351279E+11 0.319313E+11 27927.46 12-APR-14:30 25386.07 25386.07 26.08 113.89
May 0.358311E+11 0.325704E+11 27927.86 16-MAY-14:30 25386.42 25386.42 26.10 113.89
June 0.475719E+11 0.432428E+11 27991.51 17-JUN-15:30 25444.28 25444.28 28.85 113.89
July 0.467727E+11 0.425164E+11 27991.51 13-JUL-10:05 25444.28 25444.28 29.18 113.89
August 0.476697E+11 0.433318E+11 27991.51 01-AUG-05:04 25444.28 25444.28 29.24 113.89
September 0.371201E+11 0.337422E+11 27991.51 01-SEP-09:10 25444.28 25444.28 28.82 113.89
October 0.274538E+11 0.249555E+11 27991.51 03-OCT-09:00 25444.28 25444.28 28.96 113.89
November 0.175672E+11 0.159686E+11 27920.48 01-NOV-12:50 25379.72 25379.72 25.78 113.89
December 0.143196E+11 0.130165E+11 27916.20 22-DEC-16:00 25375.82 25375.82 25.60 113.89
                 
Annual Sum or Average 0.353582E+12 0.321406E+12            
Minimum of Months 0.103343E+11 0.939385E+10 13948.91   12679.56 12679.56 24.79 56.94
Maximum of Months 0.476697E+11 0.433318E+11 27991.51   25444.28 25444.28 29.24 113.89



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 33.28 33.28 2886.17 808979.61 02-JAN-06:03
February 0.00 0.00 01-FEB-00:10 27.42 27.42 3330.88 593950.10 13-FEB-06:03
March 0.00 0.00 01-MAR-00:10 33.14 33.14 2970.95 768533.37 27-MAR-05:03
April 0.00 0.00 01-APR-00:10 36.26 36.26 4.97 9692.30 21-APR-06:10
May 0.00 0.00 01-MAY-00:10 35.34 35.34 0.00 0.61 01-MAY-05:04
June 0.00 0.00 01-JUN-00:05 35.34 35.34 0.00 0.54 21-JUN-05:03
July 0.00 0.00 01-JUL-00:05 35.34 35.34 0.00 0.00 01-JUL-00:05
August 0.00 0.00 01-AUG-00:05 35.34 35.34 0.00 0.00 01-AUG-00:05
September 0.00 0.00 01-SEP-00:10 35.34 35.34 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 35.34 35.34 513.28 135031.84 25-OCT-06:10
November 0.00 0.00 01-NOV-00:10 26.10 26.10 1617.88 697355.66 24-NOV-06:03
December 0.00 0.00 01-DEC-00:10 25.62 25.62 11670.07 915238.40 07-DEC-06:01
                 
Annual Sum or Average 0.00         1921.11    
Minimum of Months 0.00 0.00   25.62 25.62 0.00 0.00  
Maximum of Months 0.00 0.00   36.26 36.26 11670.07 915238.40  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 174523.31 1611526.39 31-JAN-15:05 12.64 6.70 0.00 0.00 01-JAN-00:05
February 67990.62 766158.57 21-FEB-15:30 12.35 6.70 0.00 0.00 01-FEB-00:10
March 166183.95 1565433.42 16-MAR-14:05 12.47 6.70 0.00 0.00 01-MAR-00:10
April 447649.28 1622840.76 03-APR-12:05 12.68 6.70 0.00 0.00 01-APR-00:10
May 554095.09 1657143.40 25-MAY-12:05 12.81 6.70 0.00 0.00 01-MAY-00:10
June 752095.20 1924392.65 19-JUN-14:50 13.79 6.70 0.00 0.00 01-JUN-00:05
July 716852.01 2957029.41 14-JUL-05:03 17.61 9.08 0.00 0.00 01-JUL-00:05
August 735001.15 2273954.68 01-AUG-05:02 15.08 6.70 0.00 0.00 01-AUG-00:05
September 627045.71 2271421.49 12-SEP-05:03 15.08 6.70 0.00 0.00 01-SEP-00:10
October 356331.64 1727923.12 10-OCT-08:55 13.07 6.70 0.00 0.00 01-OCT-00:10
November 184454.27 1704096.38 02-NOV-14:05 12.98 6.70 0.00 0.00 01-NOV-00:10
December 104444.51 1337172.75 22-DEC-15:50 16.56 9.44 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 408962.88         0.00    
Minimum of Months 67990.62 766158.57   12.35 6.70 0.00 0.00  
Maximum of Months 752095.20 2957029.41   17.61 9.44 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 172605.03 1437769.10 31-JAN-16:10 20.57 7.35 0.00 0.00 01-JAN-00:05
February 67039.05 765726.00 21-FEB-15:30 20.15 6.70 0.00 0.00 01-FEB-00:10
March 164790.57 1402622.78 17-MAR-14:50 14.56 8.57 0.00 0.00 01-MAR-00:10
April 442036.56 1649626.34 25-APR-05:03 20.33 6.70 0.00 0.00 01-APR-00:10
May 548191.13 1723602.22 08-MAY-04:11 21.84 6.70 0.00 0.00 01-MAY-00:10
June 745544.81 2296469.95 09-JUN-05:02 21.96 8.17 0.00 0.00 01-JUN-00:05
July 713575.23 3559500.46 14-JUL-05:03 20.03 8.39 0.00 0.00 01-JUL-00:05
August 732363.22 3326058.56 28-AUG-05:03 18.97 12.82 0.00 0.00 01-AUG-00:05
September 624461.24 3218488.66 02-SEP-05:03 18.58 12.62 0.00 0.00 01-SEP-00:10
October 353697.50 3245117.49 03-OCT-04:12 18.67 12.67 0.00 0.00 01-OCT-00:10
November 183393.90 2312927.84 02-NOV-13:30 15.72 11.29 0.00 0.00 01-NOV-00:10
December 103223.76 1311712.10 22-DEC-15:50 19.22 9.90 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 405978.16         0.00    
Minimum of Months 67039.05 765726.00   14.56 6.70 0.00 0.00  
Maximum of Months 745544.81 3559500.46   21.96 12.82 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 107519.01 861179.38 31-JAN-17:00 35.42 31.00 0.00 0.00 01-JAN-00:05
February 66044.38 450317.18 18-FEB-14:05 27.33 23.65 0.00 0.00 01-FEB-00:10
March 294892.00 1295566.46 16-MAR-16:00 43.83 33.54 0.00 0.00 01-MAR-00:10
April 956838.58 1753037.35 14-APR-16:10 52.55 40.58 0.00 0.00 01-APR-00:10
May 628601.87 1299445.08 31-MAY-16:00 43.90 39.18 0.00 0.00 01-MAY-00:10
June 1164572.57 1832979.62 28-JUN-16:00 54.06 45.84 0.00 0.00 01-JUN-00:05
July 1406839.33 1965679.74 19-JUL-14:00 56.56 45.29 0.00 0.00 01-JUL-00:05
August 1549124.87 2118031.03 27-AUG-14:05 59.41 46.22 0.00 0.00 01-AUG-00:05
September 734380.21 1379474.72 08-SEP-16:00 45.44 40.55 0.00 0.00 01-SEP-00:10
October 474994.03 1518168.65 01-OCT-14:00 48.09 40.51 0.00 0.00 01-OCT-00:10
November 295153.87 1304197.71 01-NOV-15:00 43.99 33.73 0.00 0.00 01-NOV-00:10
December 273399.75 1247943.21 25-DEC-16:00 42.91 31.32 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 666230.40         0.00    
Minimum of Months 66044.38 450317.18   27.33 23.65 0.00 0.00  
Maximum of Months 1549124.87 2118031.03   59.41 46.22 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 56.69 56.69 13394.82 44380.36 26-JAN-12:10
February 0.00 0.00 01-FEB-00:10 57.23 57.23 13350.03 44241.77 01-FEB-12:20
March 0.00 0.00 01-MAR-00:10 56.39 56.39 13472.40 43015.27 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 56.74 56.74 11814.45 39988.42 03-APR-11:50
May 0.00 0.00 01-MAY-00:10 57.05 57.05 11167.44 36793.50 01-MAY-11:40
June 0.00 0.00 01-JUN-00:05 57.70 57.70 10551.60 33479.91 01-JUN-11:30
July 0.00 0.00 01-JUL-00:05 57.60 57.60 9444.32 31298.69 03-JUL-11:10
August 0.00 0.00 01-AUG-00:05 56.96 56.96 10336.21 32147.64 31-AUG-12:00
September 0.00 0.00 01-SEP-00:10 57.20 57.20 10383.40 34804.43 29-SEP-11:10
October 0.00 0.00 01-OCT-00:10 57.12 57.12 11269.58 38404.75 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 57.23 57.23 12383.45 41623.34 30-NOV-12:10
December 0.00 0.00 01-DEC-00:10 57.51 57.51 12738.54 43718.67 29-DEC-12:40
                 
Annual Sum or Average 0.00         11683.04    
Minimum of Months 0.00 0.00   56.39 56.39 9444.32 31298.69  
Maximum of Months 0.00 0.00   57.70 57.70 13472.40 44380.36  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 200113.36 2179183.04 27-JAN-15:30 25.68 21.10 946.06 96864.22 13-JAN-06:40
February 79174.00 877050.92 21-FEB-15:30 24.79 21.10 974.18 80760.29 03-FEB-11:40
March 189415.96 2301785.11 17-MAR-15:30 25.94 21.14 1264.73 120502.76 25-MAR-06:00
April 572822.32 2369736.00 12-APR-14:30 26.08 21.41 3543.69 96208.89 23-APR-02:40
May 738351.31 2377723.19 16-MAY-14:30 26.10 21.58 425.76 88139.56 01-MAY-01:30
June 1060650.41 3903263.11 28-JUN-16:00 29.30 25.03 596.98 55390.32 07-JUN-03:10
July 1338826.45 4725012.47 14-JUL-05:07 31.03 26.45 347.98 74690.05 02-JUL-00:50
August 1363792.62 4596172.62 16-AUG-11:00 30.75 26.54 317.41 75228.37 25-AUG-02:50
September 1078238.41 4758962.30 01-SEP-12:30 31.10 26.65 27.22 17668.36 20-SEP-00:47
October 493859.55 3783872.84 03-OCT-10:05 29.05 25.05 912.71 103199.60 12-OCT-06:40
November 220441.13 2227770.78 01-NOV-12:50 25.78 21.88 1181.42 79352.75 24-NOV-07:40
December 120347.43 2140531.93 22-DEC-16:00 25.60 21.10 2192.17 126354.47 14-DEC-08:07
                 
Annual Sum or Average 624568.08         1058.54    
Minimum of Months 79174.00 877050.92   24.79 21.10 27.22 17668.36  
Maximum of Months 1363792.62 4758962.30   31.10 26.65 3543.69 126354.47  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.122868E+09 0.00 0.400784E+11 0.603735E+10 0.00 0.00
February 0.179773E+09 0.00 0.111162E+11 0.547534E+10 0.00 0.00
March 0.235300E+09 0.00 0.435185E+11 0.836378E+10 0.00 0.00
April 0.00 0.00 0.112700E+12 0.132559E+11 0.00 0.00
May 0.00 0.00 0.123596E+12 0.121160E+11 0.00 0.00
June 0.00 0.00 0.166666E+12 0.150238E+11 0.00 0.00
July 0.00 0.00 0.173992E+12 0.153905E+11 0.00 0.00
August 0.00 0.00 0.193608E+12 0.182741E+11 0.00 0.00
September 0.00 0.00 0.138211E+12 0.113392E+11 0.00 0.00
October 24992123.31 0.00 0.850340E+11 0.942396E+10 0.00 0.00
November 40805840.24 0.00 0.467024E+11 0.793705E+10 0.00 0.00
December 0.761882E+09 0.00 0.297061E+11 0.706253E+10 0.00 0.00
             
Annual Sum or Average 0.136562E+10 0.00 0.116493E+13 0.129700E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.111162E+11 0.547534E+10 0.00 0.00
Maximum of Months 0.761882E+09 0.00 0.193608E+12 0.182741E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.516787E+10 0.00 0.347440E+12 0.402678E+11 0.00 0.00
February 0.542588E+10 0.00 0.140922E+12 0.334844E+11 0.00 0.00
March 0.589359E+10 0.00 0.331063E+12 0.486298E+11 0.00 0.00
April 5888775.72 0.00 0.851962E+12 0.842289E+11 0.00 0.00
May 0.00 0.00 0.111208E+13 0.102508E+12 0.00 0.00
June 0.00 0.00 0.148257E+13 0.125121E+12 0.00 0.00
July 0.00 0.00 0.141927E+13 0.112045E+12 0.00 0.00
August 0.00 0.00 0.144322E+13 0.116337E+12 0.00 0.00
September 0.00 0.00 0.119826E+13 0.916202E+11 0.00 0.00
October 0.946218E+09 0.00 0.703571E+12 0.640942E+11 0.00 0.00
November 0.270234E+10 0.00 0.343287E+12 0.444005E+11 0.00 0.00
December 0.240471E+11 0.00 0.214854E+12 0.351743E+11 0.00 0.00
             
Annual Sum or Average 0.441889E+11 0.00 0.958849E+13 0.897911E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.140922E+12 0.334844E+11 0.00 0.00
Maximum of Months 0.240471E+11 0.00 0.148257E+13 0.125121E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.253183E+10 0.00 0.283735E+11 0.344562E+10 0.00 0.00
February 0.250580E+10 0.00 0.601059E+10 0.277004E+10 0.00 0.00
March 0.189276E+10 0.00 0.300810E+11 0.402323E+10 0.00 0.00
April 10392976.24 0.00 0.931120E+11 0.826065E+10 0.00 0.00
May 0.00 0.00 0.123028E+12 0.103805E+11 0.00 0.00
June 0.00 0.00 0.169010E+12 0.137669E+11 0.00 0.00
July 0.00 0.00 0.161834E+12 0.122569E+11 0.00 0.00
August 0.00 0.00 0.161121E+12 0.124808E+11 0.00 0.00
September 0.00 0.00 0.130021E+12 0.938794E+10 0.00 0.00
October 0.448999E+09 0.00 0.701805E+11 0.578477E+10 0.00 0.00
November 0.149075E+10 0.00 0.288837E+11 0.365913E+10 0.00 0.00
December 0.673213E+10 0.00 0.125874E+11 0.295655E+10 0.00 0.00
             
Annual Sum or Average 0.156127E+11 0.00 0.101424E+13 0.891730E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.601059E+10 0.277004E+10 0.00 0.00
Maximum of Months 0.673213E+10 0.00 0.169010E+12 0.137669E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 478.65 0.00 0.246559E+11 0.149887E+11 0.00 0.00
February 0.00 0.00 0.433835E+10 0.129783E+11 0.00 0.00
March 833.03 0.00 0.238974E+11 0.150256E+11 0.00 0.00
April 1186.57 0.00 0.579223E+11 0.142034E+11 0.00 0.00
May 424.75 0.00 0.711567E+11 0.149221E+11 0.00 0.00
June 169.71 0.00 0.868675E+11 0.150063E+11 0.00 0.00
July 0.00 0.00 0.935453E+11 0.157631E+11 0.00 0.00
August 0.00 0.00 0.105143E+12 0.170677E+11 0.00 0.00
September 0.00 0.00 0.888709E+11 0.159282E+11 0.00 0.00
October 428.19 0.00 0.559904E+11 0.161748E+11 0.00 0.00
November 603.71 0.00 0.298360E+11 0.153659E+11 0.00 0.00
December 274.22 0.00 0.132625E+11 0.155604E+11 0.00 0.00
             
Annual Sum or Average 4398.82 0.00 0.655486E+12 0.182984E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.433835E+10 0.129783E+11 0.00 0.00
Maximum of Months 1186.57 0.00 0.105143E+12 0.170677E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.407614E+11 0.303228E+12 0.00 69.96
February 0.00 0.00 0.154707E+11 0.191243E+12 0.00 34.42
March 0.00 0.00 0.254582E+12 0.355963E+12 0.00 71.24
April 0.00 0.00 0.901852E+12 0.585044E+12 0.00 94.76
May 0.00 0.00 0.296911E+12 0.323015E+12 0.00 52.01
June 0.00 0.00 0.713590E+12 0.361455E+12 0.00 24.63
July 0.00 0.00 0.116534E+13 0.418761E+12 0.00 7.57
August 0.00 0.00 0.140614E+13 0.488926E+12 0.00 16.01
September 0.00 0.00 0.356602E+12 0.210134E+12 0.00 7.22
October 0.00 0.00 0.334960E+12 0.344328E+12 0.00 58.41
November 0.00 0.00 0.264949E+12 0.336522E+12 0.00 64.88
December 0.00 0.00 0.267025E+12 0.430361E+12 0.00 97.68
             
Annual Sum or Average 0.00 0.00 0.601818E+13 0.434898E+13 0.00 598.80
Minimum of Months 0.00 0.00 0.154707E+11 0.191243E+12 0.00 7.22
Maximum of Months 0.00 0.00 0.140614E+13 0.585044E+12 0.00 97.68



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.686188E+10 0.291517E+10 0.00 0.00
February 0.00 0.00 0.114847E+11 0.346173E+10 0.00 0.00
March 0.00 0.00 0.193869E+11 0.517053E+10 0.00 0.00
April 0.00 0.00 0.257388E+11 0.722841E+10 0.00 0.00
May 0.00 0.00 0.843694E+10 0.366084E+10 0.00 0.00
June 0.00 0.00 0.153299E+11 0.561006E+10 0.00 0.00
July 0.00 0.00 0.224297E+11 0.725163E+10 0.00 0.00
August 0.00 0.00 0.283921E+11 0.852926E+10 0.00 0.00
September 0.00 0.00 0.829114E+10 0.349208E+10 0.00 0.00
October 0.00 0.00 0.141431E+11 0.455659E+10 0.00 0.00
November 0.00 0.00 0.189842E+11 0.505141E+10 0.00 0.00
December 0.00 0.00 0.252695E+11 0.617457E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.204749E+12 0.631023E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.686188E+10 0.291517E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.283921E+11 0.852926E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.541800E+11 0.257301E+11 0.00 0.00
February 0.00 0.00 0.990755E+11 0.312848E+11 0.00 0.00
March 0.00 0.00 0.177499E+12 0.481347E+11 0.00 0.00
April 0.00 0.00 0.243995E+12 0.688118E+11 0.00 0.00
May 0.00 0.00 0.786349E+11 0.345374E+11 0.00 0.00
June 0.00 0.00 0.146067E+12 0.535004E+11 0.00 0.00
July 0.00 0.00 0.213365E+12 0.690606E+11 0.00 0.00
August 0.00 0.00 0.268050E+12 0.809465E+11 0.00 0.00
September 0.00 0.00 0.769154E+11 0.328505E+11 0.00 0.00
October 0.00 0.00 0.129788E+12 0.425548E+11 0.00 0.00
November 0.00 0.00 0.172491E+12 0.467850E+11 0.00 0.00
December 0.00 0.00 0.227974E+12 0.568543E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.188804E+13 0.591051E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.541800E+11 0.257301E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.268050E+12 0.809465E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.429081E+10 0.239473E+10 0.00 0.00
February 0.00 0.00 0.872032E+10 0.295926E+10 0.00 0.00
March 0.00 0.00 0.170134E+11 0.473474E+10 0.00 0.00
April 0.00 0.00 0.245262E+11 0.697109E+10 0.00 0.00
May 0.00 0.00 0.796127E+10 0.352181E+10 0.00 0.00
June 0.00 0.00 0.148737E+11 0.546091E+10 0.00 0.00
July 0.00 0.00 0.216291E+11 0.702298E+10 0.00 0.00
August 0.00 0.00 0.271138E+11 0.822339E+10 0.00 0.00
September 0.00 0.00 0.783109E+10 0.335652E+10 0.00 0.00
October 0.00 0.00 0.125805E+11 0.422780E+10 0.00 0.00
November 0.00 0.00 0.162832E+11 0.455775E+10 0.00 0.00
December 0.00 0.00 0.212221E+11 0.547343E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.184045E+12 0.589044E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.429081E+10 0.239473E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.271138E+11 0.822339E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.603735E+10 0.400784E+11 0.122868E+09 0.00 0.00 0.00 0.00 0.00
February 0.547534E+10 0.111162E+11 0.179773E+09 0.00 0.00 0.00 0.00 0.00
March 0.836378E+10 0.435185E+11 0.235300E+09 0.00 0.00 0.00 0.00 0.00
April 0.132559E+11 0.112700E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.121160E+11 0.123596E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.150238E+11 0.166666E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153905E+11 0.173992E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.182741E+11 0.193608E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.113392E+11 0.138211E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.942396E+10 0.850340E+11 24992123.31 0.00 0.00 0.00 0.00 0.00
November 0.793705E+10 0.467024E+11 40805840.24 0.00 0.00 0.00 0.00 0.00
December 0.706253E+10 0.297061E+11 0.761882E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.129700E+12 0.116493E+13 0.136562E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.547534E+10 0.111162E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.182741E+11 0.193608E+12 0.761882E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.402678E+11 0.347440E+12 0.516787E+10 0.00 0.00 0.00 0.00 0.00
February 0.334844E+11 0.140922E+12 0.542588E+10 0.00 0.00 0.00 0.00 0.00
March 0.486298E+11 0.331063E+12 0.589359E+10 0.00 0.00 0.00 0.00 0.00
April 0.842289E+11 0.851962E+12 5888775.72 0.00 0.00 0.00 0.00 0.00
May 0.102508E+12 0.111208E+13 0.00 0.00 0.00 0.00 0.00 0.00
June 0.125121E+12 0.148257E+13 0.00 0.00 0.00 0.00 0.00 0.00
July 0.112045E+12 0.141927E+13 0.00 0.00 0.00 0.00 0.00 0.00
August 0.116337E+12 0.144322E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.916202E+11 0.119826E+13 0.00 0.00 0.00 0.00 0.00 0.00
October 0.640942E+11 0.703571E+12 0.946218E+09 0.00 0.00 0.00 0.00 0.00
November 0.444005E+11 0.343287E+12 0.270234E+10 0.00 0.00 0.00 0.00 0.00
December 0.351743E+11 0.214854E+12 0.240471E+11 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.897911E+12 0.958849E+13 0.441889E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.334844E+11 0.140922E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.125121E+12 0.148257E+13 0.240471E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.344562E+10 0.283735E+11 0.253183E+10 0.00 0.00 0.00 0.00 0.00
February 0.277004E+10 0.601059E+10 0.250580E+10 0.00 0.00 0.00 0.00 0.00
March 0.402323E+10 0.300810E+11 0.189276E+10 0.00 0.00 0.00 0.00 0.00
April 0.826065E+10 0.931120E+11 10392976.24 0.00 0.00 0.00 0.00 0.00
May 0.103805E+11 0.123028E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137669E+11 0.169010E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.122569E+11 0.161834E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.124808E+11 0.161121E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.938794E+10 0.130021E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.578477E+10 0.701805E+11 0.448999E+09 0.00 0.00 0.00 0.00 0.00
November 0.365913E+10 0.288837E+11 0.149075E+10 0.00 0.00 0.00 0.00 0.00
December 0.295655E+10 0.125874E+11 0.673213E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.891730E+11 0.101424E+13 0.156127E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.277004E+10 0.601059E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137669E+11 0.169010E+12 0.673213E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.149887E+11 0.246559E+11 478.65 0.00 0.00 0.00 0.00 0.00
February 0.129783E+11 0.433835E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.150256E+11 0.238974E+11 833.03 0.00 0.00 0.00 0.00 0.00
April 0.142034E+11 0.579223E+11 1186.57 0.00 0.00 0.00 0.00 0.00
May 0.149221E+11 0.711567E+11 424.75 0.00 0.00 0.00 0.00 0.00
June 0.150063E+11 0.868675E+11 169.71 0.00 0.00 0.00 0.00 0.00
July 0.157631E+11 0.935453E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.170677E+11 0.105143E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.159282E+11 0.888709E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.161748E+11 0.559904E+11 428.19 0.00 0.00 0.00 0.00 0.00
November 0.153659E+11 0.298360E+11 603.71 0.00 0.00 0.00 0.00 0.00
December 0.155604E+11 0.132625E+11 274.22 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.182984E+12 0.655486E+12 4398.82 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129783E+11 0.433835E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.170677E+11 0.105143E+12 1186.57 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.103419E+12 0.290146E+11 0.00 0.00 0.00 0.187219E+12 0.00 0.00
February 0.934110E+11 0.101614E+11 0.00 0.00 0.00 0.921080E+11 0.00 0.00
March 0.103419E+12 0.193547E+12 0.00 0.00 0.00 0.190651E+12 0.00 0.00
April 0.100083E+12 0.671619E+12 0.00 0.00 0.00 0.253587E+12 0.00 0.00
May 0.103419E+12 0.217138E+12 0.00 0.00 0.00 0.139196E+12 0.00 0.00
June 0.100083E+12 0.518437E+12 0.00 0.00 0.00 0.659214E+11 0.00 0.00
July 0.103419E+12 0.870333E+12 0.00 0.00 0.00 0.202462E+11 0.00 0.00
August 0.103419E+12 0.106368E+13 0.00 0.00 0.00 0.428543E+11 0.00 0.00
September 0.100083E+12 0.265972E+12 0.00 0.00 0.00 0.193344E+11 0.00 0.00
October 0.103419E+12 0.251066E+12 0.00 0.00 0.00 0.156310E+12 0.00 0.00
November 0.100083E+12 0.202931E+12 0.00 0.00 0.00 0.173639E+12 0.00 0.00
December 0.103419E+12 0.202669E+12 0.00 0.00 0.00 0.261408E+12 0.00 0.00
                 
Annual Sum or Average 0.121768E+13 0.449656E+13 0.00 0.00 0.00 0.160247E+13 0.00 0.00
Minimum of Months 0.934110E+11 0.101614E+11 0.00 0.00 0.00 0.193344E+11 0.00 0.00
Maximum of Months 0.103419E+12 0.106368E+13 0.00 0.00 0.00 0.261408E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.153092E+10 0.547763E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.138276E+10 0.940569E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.153092E+10 0.157473E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.148153E+10 0.199920E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.153092E+10 0.630701E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.148153E+10 0.112014E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153092E+10 0.167090E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.153092E+10 0.213937E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.148153E+10 0.628059E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.153092E+10 0.111175E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.148153E+10 0.154143E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153092E+10 0.206259E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.180253E+11 0.159672E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.138276E+10 0.547763E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153092E+10 0.213937E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.146150E+11 0.430650E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.132007E+11 0.809914E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.146150E+11 0.143980E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.141436E+11 0.189327E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.146150E+11 0.587126E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.141436E+11 0.106710E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.146150E+11 0.158919E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.146150E+11 0.201718E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.141436E+11 0.582084E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.146150E+11 0.101848E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.141436E+11 0.139850E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.146150E+11 0.185735E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.172080E+12 0.146907E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.132007E+11 0.430650E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146150E+11 0.201718E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.149565E+10 0.339174E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.135091E+10 0.711197E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.149565E+10 0.137743E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.144741E+10 0.190025E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.149565E+10 0.593512E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.144741E+10 0.108602E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.149565E+10 0.161018E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.149565E+10 0.203861E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.144741E+10 0.592197E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.149565E+10 0.984835E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.144741E+10 0.131729E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149565E+10 0.172443E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.176101E+11 0.142751E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.135091E+10 0.339174E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.149565E+10 0.203861E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.603735E+10 0.122868E+09 0.400784E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.547534E+10 0.179773E+09 0.111162E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.836378E+10 0.235300E+09 0.435185E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132559E+11 0.00 0.112700E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.121160E+11 0.00 0.123596E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.150238E+11 0.00 0.166666E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153905E+11 0.00 0.173992E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.182741E+11 0.00 0.193608E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.113392E+11 0.00 0.138211E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.942396E+10 24992123.31 0.850340E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.793705E+10 40805840.24 0.467024E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.706253E+10 0.761882E+09 0.297061E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.129700E+12 0.136562E+10 0.116493E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.547534E+10 0.00 0.111162E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.182741E+11 0.761882E+09 0.193608E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.402678E+11 0.516787E+10 0.347440E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.334844E+11 0.542588E+10 0.140922E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.486298E+11 0.589359E+10 0.331063E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.842289E+11 5888775.72 0.851962E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.102508E+12 0.00 0.111208E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.125121E+12 0.00 0.148257E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.112045E+12 0.00 0.141927E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.116337E+12 0.00 0.144322E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.916202E+11 0.00 0.119826E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.640942E+11 0.946218E+09 0.703571E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.444005E+11 0.270234E+10 0.343287E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.351743E+11 0.240471E+11 0.214854E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.897911E+12 0.441889E+11 0.958849E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.334844E+11 0.00 0.140922E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.125121E+12 0.240471E+11 0.148257E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.344562E+10 0.253183E+10 0.283735E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.277004E+10 0.250580E+10 0.601059E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.402323E+10 0.189276E+10 0.300810E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.826065E+10 10392976.24 0.931120E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.103805E+11 0.00 0.123028E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137669E+11 0.00 0.169010E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.122569E+11 0.00 0.161834E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.124808E+11 0.00 0.161121E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.938794E+10 0.00 0.130021E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.578477E+10 0.448999E+09 0.701805E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.365913E+10 0.149075E+10 0.288837E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.295655E+10 0.673213E+10 0.125874E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.891730E+11 0.156127E+11 0.101424E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.277004E+10 0.00 0.601059E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137669E+11 0.673213E+10 0.169010E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.149887E+11 478.65 0.246559E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.129783E+11 0.00 0.433835E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.150256E+11 833.03 0.238974E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142034E+11 1186.57 0.579223E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.149221E+11 424.75 0.711567E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.150063E+11 169.71 0.868675E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.157631E+11 0.00 0.935453E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.170677E+11 0.00 0.105143E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.159282E+11 0.00 0.888709E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.161748E+11 428.19 0.559904E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.153659E+11 603.71 0.298360E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.155604E+11 274.22 0.132625E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.182984E+12 4398.82 0.655486E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.129783E+11 0.00 0.433835E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.170677E+11 1186.57 0.105143E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.103419E+12 0.00 0.407614E+11 0.00 0.117469E+11 0.00 0.00 0.00 0.188062E+12 0.00 0.00 0.00
February 0.934110E+11 0.00 0.154707E+11 0.00 0.530922E+10 0.00 0.00 0.00 0.925226E+11 0.00 0.00 0.00
March 0.103419E+12 0.00 0.254582E+12 0.00 0.610346E+11 0.00 0.00 0.00 0.191509E+12 0.00 0.00 0.00
April 0.100083E+12 0.00 0.901852E+12 0.00 0.230233E+12 0.00 0.00 0.00 0.254728E+12 0.00 0.00 0.00
May 0.103419E+12 0.00 0.296911E+12 0.00 0.797727E+11 0.00 0.00 0.00 0.139823E+12 0.00 0.00 0.00
June 0.100083E+12 0.00 0.713590E+12 0.00 0.195153E+12 0.00 0.00 0.00 0.662181E+11 0.00 0.00 0.00
July 0.103419E+12 0.00 0.116534E+13 0.00 0.295004E+12 0.00 0.00 0.00 0.203374E+11 0.00 0.00 0.00
August 0.103419E+12 0.00 0.140614E+13 0.00 0.342460E+12 0.00 0.00 0.00 0.430472E+11 0.00 0.00 0.00
September 0.100083E+12 0.00 0.356602E+12 0.00 0.906294E+11 0.00 0.00 0.00 0.194214E+11 0.00 0.00 0.00
October 0.103419E+12 0.00 0.334960E+12 0.00 0.838948E+11 0.00 0.00 0.00 0.157014E+12 0.00 0.00 0.00
November 0.100083E+12 0.00 0.264949E+12 0.00 0.620182E+11 0.00 0.00 0.00 0.174420E+12 0.00 0.00 0.00
December 0.103419E+12 0.00 0.267025E+12 0.00 0.643566E+11 0.00 0.00 0.00 0.262585E+12 0.00 0.00 0.00
                         
Annual Sum or Average 0.121768E+13 0.00 0.601818E+13 0.00 0.152161E+13 0.00 0.00 0.00 0.160969E+13 0.00 0.00 0.00
Minimum of Months 0.934110E+11 0.00 0.154707E+11 0.00 0.530922E+10 0.00 0.00 0.00 0.194214E+11 0.00 0.00 0.00
Maximum of Months 0.103419E+12 0.00 0.140614E+13 0.00 0.342460E+12 0.00 0.00 0.00 0.262585E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.153092E+10 0.00 0.686188E+10 0.00 0.138425E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.138276E+10 0.00 0.114847E+11 0.00 0.207897E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.153092E+10 0.00 0.193869E+11 0.00 0.363961E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.148153E+10 0.00 0.257388E+11 0.00 0.574688E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.153092E+10 0.00 0.843694E+10 0.00 0.212992E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.148153E+10 0.00 0.153299E+11 0.00 0.412853E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153092E+10 0.00 0.224297E+11 0.00 0.572072E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.153092E+10 0.00 0.283921E+11 0.00 0.699834E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.148153E+10 0.00 0.829114E+10 0.00 0.201055E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.153092E+10 0.00 0.141431E+11 0.00 0.302567E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.148153E+10 0.00 0.189842E+11 0.00 0.356988E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153092E+10 0.00 0.252695E+11 0.00 0.464366E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.180253E+11 0.00 0.204749E+12 0.00 0.450770E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.138276E+10 0.00 0.686188E+10 0.00 0.138425E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153092E+10 0.00 0.283921E+11 0.00 0.699834E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.146150E+11 0.00 0.541800E+11 0.00 0.111150E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.132007E+11 0.00 0.990755E+11 0.00 0.180841E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.146150E+11 0.00 0.177499E+12 0.00 0.335196E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.141436E+11 0.00 0.243995E+12 0.00 0.546682E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.146150E+11 0.00 0.786349E+11 0.00 0.199223E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.141436E+11 0.00 0.146067E+12 0.00 0.393568E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.146150E+11 0.00 0.213365E+12 0.00 0.544456E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.146150E+11 0.00 0.268050E+12 0.00 0.663315E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.141436E+11 0.00 0.769154E+11 0.00 0.187069E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.146150E+11 0.00 0.129788E+12 0.00 0.279397E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.141436E+11 0.00 0.172491E+12 0.00 0.326414E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.146150E+11 0.00 0.227974E+12 0.00 0.422393E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.172080E+12 0.00 0.188804E+13 0.00 0.418970E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.132007E+11 0.00 0.541800E+11 0.00 0.111150E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.146150E+11 0.00 0.268050E+12 0.00 0.663315E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.149565E+10 0.00 0.429081E+10 0.00 0.899074E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.135091E+10 0.00 0.872032E+10 0.00 0.160835E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.149565E+10 0.00 0.170134E+11 0.00 0.323909E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.144741E+10 0.00 0.245262E+11 0.00 0.552368E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.149565E+10 0.00 0.796127E+10 0.00 0.202615E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.144741E+10 0.00 0.148737E+11 0.00 0.401351E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.149565E+10 0.00 0.216291E+11 0.00 0.552733E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.149565E+10 0.00 0.271138E+11 0.00 0.672774E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.144741E+10 0.00 0.783109E+10 0.00 0.190911E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.149565E+10 0.00 0.125805E+11 0.00 0.273215E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.144741E+10 0.00 0.162832E+11 0.00 0.311035E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.149565E+10 0.00 0.212221E+11 0.00 0.397778E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.176101E+11 0.00 0.184045E+12 0.00 0.412943E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.135091E+10 0.00 0.429081E+10 0.00 0.899074E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.149565E+10 0.00 0.271138E+11 0.00 0.672774E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.220983E+09 24002533.54 0.00 0.124791E+09 156540.77 0.00 0.505501E+11 0.00 1.25
February 0.232059E+09 0.00 0.00 0.102118E+09 0.00 0.00 0.591670E+11 0.00 1.21
March 0.150664E+09 35228637.48 0.00 0.113709E+09 790668.42 0.00 0.508285E+11 0.00 1.30
April 52901413.63 0.241461E+10 0.00 74872991.54 0.118060E+09 0.00 0.181533E+11 0.00 0.81
May 52708655.25 0.509023E+10 0.00 46608249.86 0.106748E+09 0.00 0.914489E+10 0.00 0.64
June 43974274.76 0.129442E+11 0.00 21069283.26 0.191881E+09 0.00 0.288779E+10 0.00 0.53
July 18486693.15 0.129331E+11 0.00 12904321.03 0.236092E+09 0.00 0.127476E+10 0.00 0.44
August 17502754.38 0.129957E+11 0.00 23198958.94 0.174444E+09 0.00 0.179435E+10 0.00 0.56
September 43683636.13 0.929672E+10 0.00 38840334.68 0.187109E+09 0.00 0.479524E+10 0.00 0.68
October 0.201067E+09 0.207474E+10 0.00 0.102723E+09 27738156.68 0.00 0.323680E+11 0.00 1.09
November 0.323169E+09 0.224034E+09 0.00 0.137685E+09 0.00 0.00 0.530608E+11 0.00 1.34
December 0.362642E+09 1283338.95 0.00 0.143361E+09 0.00 0.00 0.670328E+11 0.00 1.25
                   
Annual Sum or Average 0.171984E+10 0.580339E+11 0.00 0.941881E+09 0.104302E+10 0.00 0.351058E+12 0.00 0.92
Minimum of Months 17502754.38 0.00 0.00 12904321.03 0.00 0.00 0.127476E+10 0.00 0.44
Maximum of Months 0.362642E+09 0.129957E+11 0.00 0.143361E+09 0.236092E+09 0.00 0.670328E+11 0.00 1.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.183431E+10 1782383.36 0.00 92073331.82 23029253.20 0.00 0.324195E+11 0.00 0.77
February 0.173650E+10 0.00 0.00 83433907.57 0.00 0.00 0.427711E+11 0.00 0.83
March 0.213636E+10 12031330.70 0.00 0.103993E+09 591606.80 0.00 0.392303E+11 0.00 0.93
April 0.622888E+10 0.114667E+10 0.00 68550532.65 0.211449E+09 0.00 0.142902E+11 0.00 0.78
May 0.106999E+10 0.255820E+10 0.00 43099227.92 0.166959E+09 0.00 0.643194E+10 0.00 0.48
June 0.161097E+10 0.774302E+10 0.00 11687928.85 0.343579E+09 0.00 0.139713E+10 0.00 0.40
July 0.857948E+09 0.953260E+10 0.00 5993583.11 0.151236E+10 0.00 0.515754E+09 0.00 0.37
August 0.114529E+10 0.965307E+10 0.00 14870816.51 0.683473E+09 0.00 0.950268E+09 0.00 0.47
September 0.260123E+09 0.604276E+10 0.00 28984673.57 0.102271E+10 0.00 0.285262E+10 0.00 0.47
October 0.168156E+10 0.127046E+10 0.00 76951330.94 0.181192E+09 0.00 0.226524E+11 0.00 0.75
November 0.228384E+10 70779119.82 0.00 0.105974E+09 30222093.20 0.00 0.362207E+11 0.00 0.91
December 0.235513E+10 93477.48 0.00 0.108478E+09 1482988.63 0.00 0.439222E+11 0.00 0.79
                   
Annual Sum or Average 0.232009E+11 0.380315E+11 0.00 0.744090E+09 0.417704E+10 0.00 0.243654E+12 0.00 0.66
Minimum of Months 0.260123E+09 0.00 0.00 5993583.11 0.00 0.00 0.515754E+09 0.00 0.37
Maximum of Months 0.622888E+10 0.965307E+10 0.00 0.108478E+09 0.151236E+10 0.00 0.439222E+11 0.00 0.93



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.245816E+11 0.00 0.00 0.590319E+09 0.311935E+09 0.00 0.200028E+12 0.00 0.50
February 0.293861E+11 0.00 0.00 0.495785E+09 0.00 0.00 0.246685E+12 0.00 0.50
March 0.176649E+11 0.106212E+09 0.00 0.671839E+09 16971447.19 0.00 0.258804E+12 0.00 0.63
April 0.107602E+11 0.121491E+11 0.00 0.517643E+09 0.188876E+10 0.00 0.103902E+12 0.00 0.51
May 0.512501E+10 0.267537E+11 0.00 0.348543E+09 0.144933E+10 0.00 0.507228E+11 0.00 0.42
June 0.491090E+10 0.780233E+11 0.00 0.111626E+09 0.273509E+10 0.00 0.135883E+11 0.00 0.33
July 0.222402E+10 0.896935E+11 0.00 42544580.24 0.394538E+10 0.00 0.442954E+10 0.00 0.29
August 0.248695E+10 0.842890E+11 0.00 96828323.63 0.321725E+10 0.00 0.819770E+10 0.00 0.34
September 0.153870E+10 0.579906E+11 0.00 0.227381E+09 0.522622E+10 0.00 0.227708E+11 0.00 0.39
October 0.818580E+10 0.130951E+11 0.00 0.546093E+09 0.623790E+09 0.00 0.154787E+12 0.00 0.54
November 0.219631E+11 0.431281E+09 0.00 0.639127E+09 0.259682E+09 0.00 0.223057E+12 0.00 0.58
December 0.457807E+11 1695261.66 0.00 0.490153E+09 3749254.34 0.00 0.219642E+12 0.00 0.45
                   
Annual Sum or Average 0.174608E+12 0.362534E+12 0.00 0.477788E+10 0.196782E+11 0.00 0.150661E+13 0.00 0.46
Minimum of Months 0.153870E+10 0.00 0.00 42544580.24 0.00 0.00 0.442954E+10 0.00 0.29
Maximum of Months 0.457807E+11 0.896935E+11 0.00 0.671839E+09 0.522622E+10 0.00 0.258804E+12 0.00 0.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.745565E+10 0.00 0.00 28711998.41 19676442.91 93828697.35 0.107054E+11 0.00 0.48
February 0.898692E+10 0.00 0.00 22843870.35 0.00 34657356.44 0.158307E+11 0.00 0.49
March 0.612993E+10 3152874.44 0.00 42464186.08 441369.36 1057488.97 0.166764E+11 0.00 0.56
April 0.162202E+10 0.798270E+09 0.00 51089061.10 0.170561E+09 0.00 0.745544E+10 0.00 0.48
May 0.468025E+09 0.198671E+10 0.00 39148618.61 0.123778E+09 0.00 0.369698E+10 0.00 0.39
June 0.488615E+09 0.690550E+10 0.00 10104040.56 0.227146E+09 0.00 0.102774E+10 0.00 0.32
July 0.251705E+09 0.824241E+10 0.00 4125871.89 0.411358E+09 0.00 0.324091E+09 0.00 0.29
August 0.220716E+09 0.760748E+10 0.00 8775386.39 0.333131E+09 0.00 0.603770E+09 0.00 0.34
September 0.184977E+09 0.509869E+10 0.00 23452917.63 0.608759E+09 0.00 0.173635E+10 0.00 0.38
October 0.245321E+10 0.105093E+10 0.00 40214905.49 70715898.63 0.00 0.103396E+11 0.00 0.48
November 0.642789E+10 41454854.80 0.00 36880070.87 18576517.77 1273054.75 0.136741E+11 0.00 0.52
December 0.127573E+11 0.00 0.00 16033478.36 3469319.79 94683909.94 0.903521E+10 0.00 0.42
                   
Annual Sum or Average 0.474470E+11 0.317346E+11 0.00 0.323844E+09 0.198761E+10 0.225501E+09 0.911057E+11 0.00 0.43
Minimum of Months 0.184977E+09 0.00 0.00 4125871.89 0.00 0.00 0.324091E+09 0.00 0.29
Maximum of Months 0.127573E+11 0.824241E+10 0.00 51089061.10 0.608759E+09 94683909.94 0.166764E+11 0.00 0.56



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.139994E+10 208036.31 0.00 4466296.91 2895152.33 0.00 0.133794E+10 0.00 0.52
February 0.146387E+10 0.00 0.00 3704131.91 0.00 0.00 0.220366E+10 0.00 0.56
March 0.107029E+10 1837553.77 0.00 7308703.75 74318.31 0.00 0.257740E+10 0.00 0.72
April 0.954716E+09 0.218271E+09 0.00 7624848.62 26562470.96 0.00 0.124301E+10 0.00 0.78
May 0.199179E+09 0.559110E+09 0.00 5096650.92 21417080.58 0.00 0.708630E+09 0.00 0.60
June 0.199409E+09 0.199707E+10 0.00 1945565.45 37252330.49 0.00 0.228186E+09 0.00 0.65
July 0.109306E+09 0.210232E+10 0.00 935976.75 0.177093E+09 0.00 77571139.65 0.00 0.55
August 0.144209E+09 0.190848E+10 0.00 1944359.65 80947059.12 0.00 0.127986E+09 0.00 0.63
September 48514495.54 0.120316E+10 0.00 3528019.76 0.123603E+09 0.00 0.312139E+09 0.00 0.58
October 0.598772E+09 0.221703E+09 0.00 5922131.08 22986984.87 0.00 0.150857E+10 0.00 0.63
November 0.106384E+10 3345330.76 0.00 6714905.48 6277295.66 0.00 0.211293E+10 0.00 0.65
December 0.166493E+10 10709.14 0.00 3974229.51 186294.69 0.00 0.171080E+10 0.00 0.49
                   
Annual Sum or Average 0.891697E+10 0.821552E+10 0.00 53165819.79 0.499294E+09 0.00 0.141488E+11 0.00 0.61
Minimum of Months 48514495.54 0.00 0.00 935976.75 0.00 0.00 77571139.65 0.00 0.49
Maximum of Months 0.166493E+10 0.210232E+10 0.00 7624848.62 0.177093E+09 0.00 0.257740E+10 0.00 0.78



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.656287E+09 184207.93 0.00 6841481.99 1858621.63 0.00 0.236928E+10 0.00 0.84
February 0.761756E+09 0.00 0.00 5443434.56 0.00 0.00 0.285845E+10 0.00 0.81
March 0.585811E+09 1279185.28 0.00 8289876.80 47746.80 0.00 0.309792E+10 0.00 1.06
April 0.580502E+09 0.168726E+09 0.00 10231620.75 17011756.35 0.00 0.182549E+10 0.00 1.26
May 0.114711E+09 0.447365E+09 0.00 7502530.98 13224555.73 0.00 0.979658E+09 0.00 1.03
June 0.128839E+09 0.160218E+10 0.00 1872329.61 22862197.70 0.00 0.195523E+09 0.00 0.87
July 68862701.21 0.171404E+10 0.00 942594.52 0.118679E+09 0.00 67770116.26 0.00 0.70
August 94854647.99 0.153535E+10 0.00 1438427.10 53064553.11 0.00 98171659.15 0.00 0.76
September 32430415.12 0.106788E+10 0.00 3137276.51 70062185.16 0.00 0.297236E+09 0.00 0.79
October 0.333724E+09 0.191091E+09 0.00 7359602.74 13299389.62 0.00 0.205664E+10 0.00 1.02
November 0.600496E+09 1850366.14 0.00 7301260.31 4219867.98 0.00 0.243644E+10 0.00 0.90
December 0.934402E+09 7481.06 0.00 5012209.15 119687.54 153732.80 0.196793E+10 0.00 0.63
                   
Annual Sum or Average 0.489268E+10 0.672995E+10 0.00 65372645.00 0.314450E+09 153732.80 0.182505E+11 0.00 0.89
Minimum of Months 32430415.12 0.00 0.00 942594.52 0.00 0.00 67770116.26 0.00 0.63
Maximum of Months 0.934402E+09 0.171404E+10 0.00 10231620.75 0.118679E+09 153732.80 0.309792E+10 0.00 1.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.611534E+09 4678561.70 0.00 28763848.81 700024.05 0.00 0.676927E+10 0.00 1.62
February 0.862420E+09 0.00 0.00 13300330.06 0.00 0.00 0.723627E+10 0.00 1.25
March 0.858556E+09 2871906.99 0.00 14589390.93 0.00 0.00 0.492272E+10 0.00 1.21
April 0.961998E+09 0.332712E+09 0.00 10602755.46 24766119.04 0.00 0.151620E+10 0.00 0.97
May 0.200176E+09 0.627124E+09 0.00 5054312.15 21219957.63 0.00 0.615490E+09 0.00 0.61
June 0.201848E+09 0.194220E+10 0.00 1622400.90 37470826.58 0.00 0.183209E+09 0.00 0.60
July 0.109289E+09 0.213072E+10 0.00 845996.13 0.176884E+09 0.00 66463879.46 0.00 0.55
August 0.142860E+09 0.221492E+10 0.00 1977508.07 78634721.61 0.00 0.127958E+09 0.00 0.68
September 44808267.08 0.173413E+10 0.00 4665420.79 0.105354E+09 0.00 0.363592E+09 0.00 0.74
October 0.439703E+09 0.403754E+09 0.00 15704495.04 17980269.38 0.00 0.362767E+10 0.00 1.25
November 0.542969E+09 7111781.97 0.00 24668274.39 5124433.02 0.00 0.678406E+10 0.00 1.53
December 0.906171E+09 951343.65 0.00 24950560.72 0.00 0.00 0.737166E+10 0.00 1.36
                   
Annual Sum or Average 0.588233E+10 0.940117E+10 0.00 0.146745E+09 0.468135E+09 0.00 0.395846E+11 0.00 1.03
Minimum of Months 44808267.08 0.00 0.00 845996.13 0.00 0.00 66463879.46 0.00 0.55
Maximum of Months 0.961998E+09 0.221492E+10 0.00 28763848.81 0.176884E+09 0.00 0.737166E+10 0.00 1.62



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.355562E+09 4089604.11 0.00 10934006.56 0.00 0.00 0.292888E+10 0.00 1.14
February 0.220080E+09 0.00 0.00 9180155.92 0.00 0.00 0.493325E+10 0.00 1.28
March 0.128741E+09 2514204.26 0.00 15626851.64 0.00 0.00 0.536024E+10 0.00 1.77
April 0.125064E+09 0.433196E+09 0.00 18572781.25 1149269.66 0.00 0.306405E+10 0.00 1.83
May 64049187.32 0.787650E+09 0.00 6136034.65 3027746.28 0.00 0.856202E+09 0.00 1.03
June 50472184.09 0.240488E+10 0.00 3317584.09 8950407.41 0.00 0.384759E+09 0.00 1.10
July 15235254.78 0.253809E+10 0.00 1817775.96 13718788.58 0.00 0.173557E+09 0.00 0.93
August 11865751.43 0.256708E+10 0.00 5194905.18 7024111.87 0.00 0.354077E+09 0.00 1.27
September 16015874.98 0.135458E+10 0.00 4120182.45 38887175.74 0.00 0.367577E+09 0.00 0.92
October 0.111350E+09 0.273330E+09 0.00 11388144.31 9186022.37 0.00 0.275681E+10 0.00 1.33
November 0.149556E+09 14101889.81 0.00 15885874.63 1170038.42 0.00 0.491562E+10 0.00 1.62
December 0.180221E+09 452804.57 0.00 15449004.54 6454.37 0.00 0.559893E+10 0.00 1.40
                   
Annual Sum or Average 0.142821E+10 0.103800E+11 0.00 0.117623E+09 83120014.71 0.00 0.316940E+11 0.00 1.30
Minimum of Months 11865751.43 0.00 0.00 1817775.96 0.00 0.00 0.173557E+09 0.00 0.92
Maximum of Months 0.355562E+09 0.256708E+10 0.00 18572781.25 38887175.74 0.00 0.559893E+10 0.00 1.83



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.184636E+11 0.00 0.00 10838531.96 39171419.37 0.559761E+09 0.235681E+10 0.00 0.38
February 0.212829E+11 0.00 0.00 6188176.96 0.00 0.524280E+09 0.360497E+10 0.00 0.36
March 0.167236E+11 14900115.03 0.00 30455297.85 2131196.67 0.511002E+09 0.805261E+10 0.00 0.47
April 0.487456E+10 0.248987E+10 0.00 49642274.05 0.239501E+09 0.00 0.638435E+10 0.00 0.51
May 0.158262E+10 0.640767E+10 0.00 39556469.19 0.187113E+09 0.00 0.496603E+10 0.00 0.55
June 0.634188E+09 0.230880E+11 0.00 18352360.15 0.281048E+09 0.00 0.227453E+10 0.00 0.63
July 0.274897E+09 0.228681E+11 0.00 6225516.79 0.438009E+09 0.00 0.727869E+09 0.00 0.52
August 0.344712E+09 0.194317E+11 0.00 11860333.43 0.358870E+09 0.00 0.102922E+10 0.00 0.54
September 0.514228E+09 0.127386E+11 0.00 26633993.96 0.615192E+09 0.00 0.221721E+10 0.00 0.52
October 0.873820E+10 0.234317E+10 0.00 29781774.14 81082663.18 0.00 0.565685E+10 0.00 0.45
November 0.166628E+11 13232650.11 0.00 23656855.71 56903537.04 0.277989E+09 0.585050E+10 0.00 0.42
December 0.223162E+11 0.00 0.00 1955472.67 612390.05 0.328197E+10 0.641167E+09 0.00 0.35
                   
Annual Sum or Average 0.112412E+12 0.893952E+11 0.00 0.255147E+09 0.229964E+10 0.515500E+10 0.437621E+11 0.00 0.48
Minimum of Months 0.274897E+09 0.00 0.00 1955472.67 0.00 0.00 0.641167E+09 0.00 0.35
Maximum of Months 0.223162E+11 0.230880E+11 0.00 49642274.05 0.615192E+09 0.328197E+10 0.805261E+10 0.00 0.63



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.694663E+10 3379891.05 0.00 42164161.95 21889801.78 0.167117E+09 0.132233E+11 0.00 0.55
February 0.785411E+10 0.00 0.00 32712954.94 0.00 67858238.34 0.151808E+11 0.00 0.50
March 0.601189E+10 12001379.92 0.00 60486059.40 1375270.44 0.157164E+09 0.209506E+11 0.00 0.79
April 0.157146E+10 0.241094E+10 0.00 97449519.76 0.152093E+09 0.00 0.167508E+11 0.00 1.12
May 0.711164E+09 0.544796E+10 0.00 70060840.87 0.104998E+09 0.00 0.899613E+10 0.00 1.04
June 0.346299E+09 0.196092E+11 0.00 21262842.00 0.137954E+09 0.00 0.227320E+10 0.00 0.93
July 0.125109E+09 0.205956E+11 0.00 8925475.27 0.229132E+09 0.00 0.838862E+09 0.00 0.76
August 0.172946E+09 0.184413E+11 0.00 14988401.78 0.178468E+09 0.00 0.121213E+10 0.00 0.81
September 0.258912E+09 0.118439E+11 0.00 28758613.21 0.301781E+09 0.00 0.261343E+10 0.00 0.79
October 0.309602E+10 0.220154E+10 0.00 58454294.25 41155219.85 0.00 0.148485E+11 0.00 0.84
November 0.659474E+10 13095386.95 0.00 47478335.88 35362688.31 54860919.44 0.152019E+11 0.00 0.64
December 0.946272E+10 19257.93 0.00 21572581.69 260057.59 0.113388E+10 0.790318E+10 0.00 0.38
                   
Annual Sum or Average 0.431520E+11 0.805789E+11 0.00 0.504314E+09 0.120447E+10 0.158088E+10 0.119993E+12 0.00 0.76
Minimum of Months 0.125109E+09 0.00 0.00 8925475.27 0.00 0.00 0.838862E+09 0.00 0.38
Maximum of Months 0.946272E+10 0.205956E+11 0.00 97449519.76 0.301781E+09 0.113388E+10 0.209506E+11 0.00 1.12



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.583886E+10 62928348.90 0.00 0.285403E+09 12677473.85 0.110667E+09 0.549604E+11 0.00 1.32
February 0.967835E+10 0.00 0.00 0.116835E+09 0.00 93040719.06 0.505307E+11 0.00 0.88
March 0.992378E+10 30093690.64 0.00 0.119121E+09 0.00 0.150640E+09 0.359145E+11 0.00 0.97
April 0.382742E+10 0.440867E+10 0.00 84888988.10 0.235882E+09 0.00 0.109111E+11 0.00 0.76
May 0.160222E+10 0.728636E+10 0.00 40842415.95 0.187265E+09 0.00 0.453210E+10 0.00 0.58
June 0.683670E+09 0.222001E+11 0.00 14902098.18 0.292414E+09 0.00 0.176723E+10 0.00 0.58
July 0.287121E+09 0.233061E+11 0.00 5417577.66 0.442535E+09 0.00 0.601327E+09 0.00 0.52
August 0.314519E+09 0.238892E+11 0.00 13657408.53 0.295145E+09 0.00 0.112349E+10 0.00 0.63
September 0.400288E+09 0.195651E+11 0.00 39998029.69 0.500401E+09 0.00 0.291925E+10 0.00 0.73
October 0.425136E+10 0.485745E+10 0.00 0.138074E+09 34057999.04 0.00 0.286135E+11 0.00 1.11
November 0.610334E+10 59369132.90 0.00 0.225243E+09 34500359.85 2758143.37 0.559813E+11 0.00 1.29
December 0.985121E+10 1999129.41 0.00 0.217448E+09 0.00 0.653449E+09 0.574216E+11 0.00 1.10
                   
Annual Sum or Average 0.527621E+11 0.105667E+12 0.00 0.130183E+10 0.203488E+10 0.101055E+10 0.305276E+12 0.00 0.87
Minimum of Months 0.287121E+09 0.00 0.00 5417577.66 0.00 0.00 0.601327E+09 0.00 0.52
Maximum of Months 0.992378E+10 0.238892E+11 0.00 0.285403E+09 0.500401E+09 0.653449E+09 0.574216E+11 0.00 1.32



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.824729E+10 15599376.37 0.00 52484012.60 21777995.81 0.115670E+09 0.102659E+11 0.00 0.61
February 0.101522E+11 0.00 0.00 29813411.83 0.00 27061167.01 0.124044E+11 0.00 0.52
March 0.744823E+10 22097707.47 0.00 60443404.69 0.00 15732458.06 0.165664E+11 0.00 0.84
April 0.177140E+10 0.422250E+10 0.00 70686821.86 36478080.31 0.00 0.981505E+10 0.00 0.99
May 0.562434E+09 0.864960E+10 0.00 38289860.73 23111520.63 0.00 0.471266E+10 0.00 0.87
June 0.253773E+09 0.249710E+11 0.00 18760869.20 0.104233E+09 0.00 0.215318E+10 0.00 0.95
July 0.112626E+09 0.215157E+11 0.00 6897140.11 0.134242E+09 0.00 0.727007E+09 0.00 0.72
August 0.141566E+09 0.197325E+11 0.00 14203752.89 0.112368E+09 0.00 0.113058E+10 0.00 0.81
September 0.176258E+09 0.125910E+11 0.00 25421840.22 0.274147E+09 0.00 0.206328E+10 0.00 0.75
October 0.367163E+10 0.252258E+10 0.00 53833046.09 21200620.15 0.00 0.104614E+11 0.00 0.78
November 0.680545E+10 39768465.64 0.00 60717630.07 23553881.59 32408800.21 0.150443E+11 0.00 0.72
December 0.114264E+11 356280.00 0.00 31515526.17 170316.30 0.839483E+09 0.918413E+10 0.00 0.49
                   
Annual Sum or Average 0.507692E+11 0.942827E+11 0.00 0.463067E+09 0.751282E+09 0.103035E+10 0.945283E+11 0.00 0.76
Minimum of Months 0.112626E+09 0.00 0.00 6897140.11 0.00 0.00 0.727007E+09 0.00 0.49
Maximum of Months 0.114264E+11 0.249710E+11 0.00 70686821.86 0.274147E+09 0.839483E+09 0.165664E+11 0.00 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.152333E+10 0.00 0.00 627374.09 2469009.19 0.363035E+09 0.164634E+09 0.00 0.42
February 0.205121E+10 0.00 0.00 299643.39 0.00 0.320296E+09 0.240419E+09 0.00 0.41
March 0.154637E+10 389691.08 0.00 2508769.93 55383.23 0.248290E+09 0.604874E+09 0.00 0.47
April 0.460539E+09 0.156515E+09 0.00 6020165.18 21857390.75 0.00 0.538361E+09 0.00 0.49
May 0.159637E+09 0.449540E+09 0.00 5133838.63 14622607.88 0.00 0.352574E+09 0.00 0.51
June 63969106.40 0.186326E+10 0.00 1604189.27 19862740.90 0.00 0.166719E+09 0.00 0.58
July 32200688.46 0.195288E+10 0.00 658644.26 40840093.59 0.00 52002878.14 0.00 0.49
August 31393346.53 0.164741E+10 0.00 1119691.03 31880896.23 0.00 75856736.16 0.00 0.51
September 72412973.53 0.106203E+10 0.00 2993053.71 69608694.68 0.00 0.167208E+09 0.00 0.50
October 0.813896E+09 0.182673E+09 0.00 2961815.96 10248312.38 82696233.95 0.415141E+09 0.00 0.43
November 0.140645E+10 716979.35 0.00 1648839.58 6023430.71 0.243733E+09 0.464812E+09 0.00 0.43
December 0.176224E+10 0.00 0.00 78054.34 435331.86 0.839027E+09 20197814.89 0.00 0.39
                   
Annual Sum or Average 0.992365E+10 0.731541E+10 0.00 25654079.37 0.217904E+09 0.209708E+10 0.326280E+10 0.00 0.47
Minimum of Months 31393346.53 0.00 0.00 78054.34 0.00 0.00 20197814.89 0.00 0.39
Maximum of Months 0.205121E+10 0.195288E+10 0.00 6020165.18 69608694.68 0.839027E+09 0.604874E+09 0.00 0.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.580114E+09 152846.32 0.00 3215243.28 1444329.16 0.131793E+09 0.108558E+10 0.00 0.58
February 0.728925E+09 0.00 0.00 2287888.99 0.00 0.126255E+09 0.142351E+10 0.00 0.54
March 0.541966E+09 401953.06 0.00 5451565.85 35826.82 92531800.12 0.193149E+10 0.00 0.80
April 0.155718E+09 0.161167E+09 0.00 11092418.21 13147653.60 0.00 0.148586E+10 0.00 1.11
May 73192111.19 0.386872E+09 0.00 8309177.88 7592103.52 0.00 0.723085E+09 0.00 0.99
June 33039822.95 0.164780E+10 0.00 1842764.83 10269032.02 0.00 0.170285E+09 0.00 0.88
July 15556495.62 0.181904E+10 0.00 859662.36 22037808.69 0.00 60579156.36 0.00 0.73
August 16702980.80 0.163562E+10 0.00 1425485.44 18085998.49 0.00 90356383.39 0.00 0.79
September 29050325.81 0.105829E+10 0.00 3269645.44 26900151.33 0.00 0.218802E+09 0.00 0.77
October 0.267656E+09 0.185744E+09 0.00 5736466.25 4232256.51 29631665.72 0.132093E+10 0.00 0.82
November 0.618275E+09 639783.59 0.00 3875184.82 3896492.52 77719015.81 0.125351E+10 0.00 0.64
December 0.105940E+10 0.00 0.00 1075362.20 281611.49 0.274234E+09 0.467588E+09 0.00 0.43
                   
Annual Sum or Average 0.411960E+10 0.689572E+10 0.00 48440865.56 0.107923E+09 0.732165E+09 0.102316E+11 0.00 0.76
Minimum of Months 15556495.62 0.00 0.00 859662.36 0.00 0.00 60579156.36 0.00 0.43
Maximum of Months 0.105940E+10 0.181904E+10 0.00 11092418.21 26900151.33 0.274234E+09 0.193149E+10 0.00 1.11



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.558680E+09 2293981.83 0.00 23540402.05 1804073.71 84384161.52 0.578444E+10 0.00 1.55
February 0.954977E+09 0.00 0.00 9341649.63 0.00 0.135672E+09 0.587756E+10 0.00 1.05
March 0.839202E+09 878786.95 0.00 10645293.41 0.00 0.155864E+09 0.350455E+10 0.00 0.96
April 0.401189E+09 0.271553E+09 0.00 10592970.11 18752202.12 0.00 0.983423E+09 0.00 0.74
May 0.188576E+09 0.499069E+09 0.00 5515473.33 14214633.86 0.00 0.317008E+09 0.00 0.54
June 68916694.65 0.178438E+10 0.00 1320163.29 20730671.53 0.00 0.127814E+09 0.00 0.54
July 35350087.91 0.196940E+10 0.00 595326.97 41955445.53 0.00 41449411.48 0.00 0.49
August 29070072.71 0.197343E+10 0.00 1293383.30 28851259.09 0.00 82852181.06 0.00 0.59
September 46646465.72 0.160115E+10 0.00 4629169.27 40980864.15 0.00 0.250399E+09 0.00 0.69
October 0.391147E+09 0.373054E+09 0.00 14416971.07 5385474.79 16026294.06 0.288489E+10 0.00 1.11
November 0.569540E+09 2203685.54 0.00 18603174.58 5785728.03 72234583.47 0.556355E+10 0.00 1.37
December 0.863533E+09 784613.92 0.00 15984277.84 79428.15 0.253318E+09 0.602346E+10 0.00 1.23
                   
Annual Sum or Average 0.494683E+10 0.847820E+10 0.00 0.116478E+09 0.178540E+09 0.717499E+09 0.314414E+11 0.00 0.90
Minimum of Months 29070072.71 0.00 0.00 595326.97 0.00 0.00 41449411.48 0.00 0.49
Maximum of Months 0.954977E+09 0.197343E+10 0.00 23540402.05 41955445.53 0.253318E+09 0.602346E+10 0.00 1.55



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.778749E+09 771439.98 0.00 4365865.91 1441846.16 99907268.57 0.106133E+10 0.00 0.73
February 0.100212E+10 0.00 0.00 2352434.51 0.00 0.106792E+09 0.149059E+10 0.00 0.65
March 0.726380E+09 573038.96 0.00 5507725.95 0.00 72872171.58 0.156803E+10 0.00 0.84
April 0.171685E+09 0.264822E+09 0.00 9287926.15 2943998.13 0.00 0.882062E+09 0.00 0.95
May 51883375.42 0.584253E+09 0.00 5073481.79 2113220.72 0.00 0.358448E+09 0.00 0.79
June 20920384.67 0.190786E+10 0.00 1679783.25 7957191.65 0.00 0.172689E+09 0.00 0.85
July 11759078.92 0.177251E+10 0.00 739088.68 13312268.52 0.00 58223129.99 0.00 0.66
August 12602030.83 0.159030E+10 0.00 1343121.64 12301428.89 0.00 86722452.65 0.00 0.75
September 23650870.76 0.102233E+10 0.00 2948614.53 26855352.92 0.00 0.170498E+09 0.00 0.70
October 0.379154E+09 0.193357E+09 0.00 5633784.29 2786772.01 6701189.18 0.976710E+09 0.00 0.76
November 0.654952E+09 1691859.81 0.00 5119438.86 3593023.53 69447989.01 0.147373E+10 0.00 0.77
December 0.100259E+10 0.00 0.00 2352954.94 281996.87 0.259966E+09 0.986356E+09 0.00 0.56
                   
Annual Sum or Average 0.483645E+10 0.733847E+10 0.00 46404220.48 73587099.42 0.615687E+09 0.928539E+10 0.00 0.75
Minimum of Months 11759078.92 0.00 0.00 739088.68 0.00 0.00 58223129.99 0.00 0.56
Maximum of Months 0.100259E+10 0.190786E+10 0.00 9287926.15 26855352.92 0.259966E+09 0.156803E+10 0.00 0.95



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 4205833.07 0.00 0.00 0.293911E+09 0.00 0.28
February 0.00 0.00 0.00 8205217.07 0.00 0.00 0.293026E+09 0.00 0.29
March 0.00 0.00 0.00 14742646.21 0.00 0.00 0.292036E+09 0.00 0.31
April 0.00 227272.30 0.00 19652852.79 0.00 0.00 0.124951E+09 0.00 0.29
May 0.00 13885514.75 0.00 3018384.80 0.00 0.00 54620635.35 0.00 0.29
June 0.00 92052072.88 0.00 1627404.87 0.00 0.00 14586105.12 0.00 0.30
July 0.00 0.186322E+09 0.00 517701.23 0.00 0.00 4104085.79 0.00 0.28
August 0.00 0.152938E+09 0.00 3039186.64 0.00 0.00 5988373.97 0.00 0.31
September 0.00 0.112793E+09 0.00 713833.28 0.00 0.00 10798723.37 0.00 0.29
October 0.00 22325569.49 0.00 7229239.41 0.00 0.00 0.169290E+09 0.00 0.28
November 0.00 1931831.39 0.00 12850961.71 0.00 0.00 0.236117E+09 0.00 0.28
December 0.00 0.00 0.00 19158007.15 0.00 0.00 0.349597E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.582475E+09 0.00 94961268.23 0.00 0.00 0.184903E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 517701.23 0.00 0.00 4104085.79 0.00 0.28
Maximum of Months 0.00 0.186322E+09 0.00 19652852.79 0.00 0.00 0.349597E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 13410420.94 0.00 0.00 33484447.67 0.00 0.00 0.293263E+10 0.00 0.28
February 0.00 0.00 0.00 72028830.56 0.00 0.00 0.294406E+10 0.00 0.29
March 0.00 0.00 0.00 0.136093E+09 0.00 0.00 0.292957E+10 0.00 0.31
April 0.00 3770832.52 0.00 0.181741E+09 0.00 0.00 0.122439E+10 0.00 0.29
May 0.00 0.138509E+09 0.00 28010984.37 0.00 0.00 0.547157E+09 0.00 0.29
June 0.00 0.919581E+09 0.00 15390264.78 0.00 0.00 0.145161E+09 0.00 0.30
July 0.00 0.185977E+10 0.00 4923947.67 0.00 0.00 40471867.95 0.00 0.28
August 0.00 0.159675E+10 0.00 26046037.20 0.00 0.00 52406240.52 0.00 0.31
September 0.00 0.111530E+10 0.00 6559094.87 0.00 0.00 0.107973E+09 0.00 0.29
October 0.00 0.222108E+09 0.00 66191322.12 0.00 0.00 0.169608E+10 0.00 0.28
November 0.00 18726731.86 0.00 0.118206E+09 0.00 0.00 0.236991E+10 0.00 0.28
December 0.00 0.00 0.00 0.174658E+09 0.00 0.00 0.350625E+10 0.00 0.28
                   
Annual Sum or Average 13410420.94 0.587451E+10 0.00 0.863333E+09 0.00 0.00 0.184961E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 4923947.67 0.00 0.00 40471867.95 0.00 0.28
Maximum of Months 13410420.94 0.185977E+10 0.00 0.181741E+09 0.00 0.00 0.350625E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 9895542.83 0.00 0.00 2665537.57 0.00 0.00 0.285667E+09 0.00 0.28
February 0.00 0.00 0.00 6496381.03 0.00 0.00 0.295712E+09 0.00 0.29
March 0.00 0.00 0.00 13120550.50 0.00 0.00 0.293677E+09 0.00 0.31
April 0.00 510772.61 0.00 17628340.96 0.00 0.00 0.119120E+09 0.00 0.29
May 0.00 13866839.52 0.00 2812870.78 0.00 0.00 54739911.85 0.00 0.29
June 0.00 92003176.56 0.00 1539219.66 0.00 0.00 14594784.68 0.00 0.30
July 0.00 0.185985E+09 0.00 493920.65 0.00 0.00 4086954.84 0.00 0.28
August 0.00 0.164314E+09 0.00 2421585.70 0.00 0.00 4926846.59 0.00 0.31
September 0.00 0.111779E+09 0.00 650760.94 0.00 0.00 10875564.20 0.00 0.29
October 0.00 22222630.75 0.00 6346587.94 0.00 0.00 0.170060E+09 0.00 0.28
November 0.00 1824392.77 0.00 11275465.70 0.00 0.00 0.237758E+09 0.00 0.28
December 0.00 0.00 0.00 16450018.77 0.00 0.00 0.351411E+09 0.00 0.28
                   
Annual Sum or Average 9895542.83 0.592506E+09 0.00 81901240.20 0.00 0.00 0.184263E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 493920.65 0.00 0.00 4086954.84 0.00 0.28
Maximum of Months 9895542.83 0.185985E+09 0.00 17628340.96 0.00 0.00 0.351411E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.575026E+09 0.00 0.00 0.503135E+12 0.00 22.29
February 0.00 0.00 0.00 0.919033E+09 0.00 0.00 0.611517E+12 0.00 28.43
March 0.00 0.00 0.00 0.158309E+10 0.00 0.00 0.828489E+12 0.00 38.82
April 0.00 0.00 0.00 0.363764E+10 0.00 0.00 0.615562E+12 0.00 45.63
May 0.00 27822.13 0.00 0.475476E+09 0.00 0.00 0.267848E+12 0.00 19.15
June 0.00 0.913504E+09 0.00 0.595073E+09 0.00 0.00 0.118827E+12 0.00 12.10
July 0.00 0.520790E+11 0.00 0.323857E+09 0.00 0.00 0.403146E+11 0.00 13.79
August 0.00 0.250539E+11 0.00 0.141444E+10 0.00 0.00 0.724504E+11 0.00 29.61
September 0.00 0.102332E+11 0.00 0.268367E+09 0.00 0.00 0.104800E+12 0.00 21.08
October 0.00 0.306178E+10 0.00 0.101104E+10 0.00 0.00 0.502594E+12 0.00 31.27
November 0.00 19031548.85 0.00 0.168795E+10 0.00 0.00 0.781400E+12 0.00 39.76
December 0.00 0.00 0.00 0.240079E+10 0.00 0.00 0.113958E+13 0.00 40.65
                   
Annual Sum or Average 0.00 0.913605E+11 0.00 0.148918E+11 0.00 0.00 0.558652E+13 0.00 28.54
Minimum of Months 0.00 0.00 0.00 0.268367E+09 0.00 0.00 0.403146E+11 0.00 12.10
Maximum of Months 0.00 0.520790E+11 0.00 0.363764E+10 0.00 0.00 0.113958E+13 0.00 45.63



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:51:38

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.317711E+12 0.101481E+11 0.00 0.212265E+13 0.699313E+12
February 0.358395E+12 0.801214E+10 0.00 0.230252E+13 0.367351E+12
March 0.464830E+12 0.104866E+11 0.00 0.248973E+13 0.106128E+13
April 0.553182E+12 0.276811E+10 0.00 0.142840E+13 0.279278E+13
May 0.547582E+12 0.433021E+09 0.00 0.761693E+12 0.245422E+13
June 0.560288E+12 -0.294742E+10 0.00 0.375172E+11 0.344856E+13
July 0.531036E+12 -0.536054E+10 0.00 -0.256819E+12 0.383967E+13
August 0.475118E+12 -0.336324E+10 0.00 -0.846964E+11 0.418971E+13
September 0.396611E+12 -0.201420E+10 0.00 0.213656E+11 0.247152E+13
October 0.371511E+12 0.457902E+10 0.00 0.167161E+13 0.173443E+13
November 0.333350E+12 0.927962E+10 0.00 0.239171E+13 0.110468E+13
December 0.263852E+12 0.983776E+10 0.00 0.293080E+13 0.950654E+12
           
Annual Sum or Average 0.517347E+13 0.418590E+11 0.00 0.158165E+14 0.251142E+14
Minimum of Months 0.263852E+12 -0.536054E+10 0.00 -0.256819E+12 0.367351E+12
Maximum of Months 0.560288E+12 0.104866E+11 0.00 0.293080E+13 0.418971E+13