Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:50
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:50:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 33266.70 | 718.19 | 718.19 |
Net Site Energy | 33266.70 | 718.19 | 718.19 |
Total Source Energy | 104158.83 | 2248.66 | 2248.66 |
Net Source Energy | 104158.83 | 2248.66 | 2248.66 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7496.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2456.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 348.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1909.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2828.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 925.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2039.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24368.68 |
Humidification | 10.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 574.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32692.14 | 574.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26652.85 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 7496.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2456.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 348.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 54.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2828.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 925.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2039.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24368.68 |
Humidification | General | 10.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 574.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 7496.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2456.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 348.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1909.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2828.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 925.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 2039.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24368.68 |
Humidification | Unassigned | 10.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 574.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 287.15 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Other | 358.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 705.78 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 60.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 287.15 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Other | 358.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 705.78 | 12.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 32692.142 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 32692.142 | 100.00 |
Total On-Site and Utility Electric Sources | 32692.142 | 100.00 |
Total Electricity End Uses | 32692.142 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 26652.85 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 26652.85 | 100.00 |
Total Water End Uses | 26652.85 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1198.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:50 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 6.5999 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.5999 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 6.5999 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 6.5999 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.7790 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 6.5999 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 6.6297 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 6.5999 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 6.5999 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 6.5999 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 6.5999 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 6.5999 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 6.5999 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 6.5999 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 9.7790 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 6.5999 | 18.58 | 484.4232 | |
Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 6.6297 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.0382 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:20 | 11-JAN-12:20 | - | - | - | - | - | - | - | - | - | - | 21-JUL-11:00 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 680882.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 82829.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 261953.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 53922.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 87148.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 69578.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2157924.09 | 69578.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 680882.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 212815.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3394.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 261953.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 53922.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 87148.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 69578.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23742.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7779.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1105.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6046.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8957.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2931.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6458.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 34.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 622.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 103536.01 | 622.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 512.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 193.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 63.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 139.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2235.22 | 13.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 512.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 167.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 193.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 63.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 139.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2235.22 | 13.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.50 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.472007 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.50 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.454158 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.40 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.90 | 0.322456 | 0.274000 | 1.62 | 0.859883 | 0.500000 | 0.001182 | 0.000142 | 1.62 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 56.28 | 0.337965 | 0.287000 | 16.15 | 0.901239 | 0.500000 | 0.001127 | 0.002826 | 16.15 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.68 | 0.334869 | 0.285000 | 1.62 | 0.892984 | 0.500000 | 0.001138 | 0.000395 | 1.62 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.29 | 0.184499 | 0.157000 | 0.203225 | 0.491997 | 0.500000 | 0.002065 | 0.000020 | 0.203225 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.08 | 0.142382 | 0.121000 | 0.130793 | 0.379685 | 0.500000 | 0.002676 | 0.000015 | 0.130793 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.45 | 0.164838 | 0.140000 | 0.202840 | 0.439567 | 0.500000 | 0.002311 | 0.000035 | 0.202840 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.41 | 0.109091 | 0.093000 | 0.131203 | 0.300000 | 0.500000 | 0.003492 | 0.000012 | 0.131203 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 13.22 | 0.180654 | 0.154000 | 2.04 | 0.481745 | 0.500000 | 0.002109 | 0.000924 | 3.14 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.51 | 0.356675 | 0.500000 | 0.002849 | 0.000616 | 2.10 | 12.80 | 0.008000 | |||
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.74 | 0.161989 | 0.138000 | 2.03 | 0.431970 | 0.500000 | 0.002352 | 0.000923 | 3.14 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.77 | 0.120538 | 0.102000 | 1.30 | 0.321435 | 0.500000 | 0.003161 | 0.000519 | 1.76 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.47 | 0.162562 | 0.138000 | 0.202736 | 0.433499 | 0.500000 | 0.002344 | 0.000117 | 0.397463 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.19 | 0.129490 | 0.110000 | 0.130741 | 0.345306 | 0.500000 | 0.002942 | 0.000077 | 0.262951 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.61 | 0.147905 | 0.126000 | 0.203456 | 0.394413 | 0.500000 | 0.002576 | 0.000117 | 0.396826 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.37 | 0.112160 | 0.095000 | 0.130358 | 0.300000 | 0.500000 | 0.003397 | 0.000068 | 0.231439 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16265.68 | 0.000142 | 327.90 |
CORE_MID VAV BOX REHEAT COIL | 322982.77 | 0.002826 | 7217.92 |
CORE_TOP VAV BOX REHEAT COIL | 45159.36 | 0.000395 | 1107.08 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 2255.27 | 0.000020 | 45.93 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 1762.51 | 0.000015 | 36.76 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 4008.09 | 0.000035 | 89.34 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 1320.43 | 0.000012 | 26.62 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 105602.83 | 0.000924 | 2788.38 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 70390.67 | 0.000616 | 1858.48 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 105464.42 | 0.000923 | 2784.73 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 59299.84 | 0.000519 | 1566.35 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13341.24 | 0.000117 | 352.11 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8825.48 | 0.000077 | 232.92 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13319.92 | 0.000117 | 351.55 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7771.33 | 0.000068 | 205.14 |
VAV_BOT WITH REHEAT HEATING COIL | 9848.42 | 0.000086 | 177.14 |
VAV_MID WITH REHEAT HEATING COIL | 0.000000 | 0.000000 | 1.00 |
VAV_TOP WITH REHEAT HEATING COIL | 0.000000 | 0.000000 | 1.00 |
CAV_BAS HEATING COIL | 247421.50 | 0.002165 | 5710.13 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.57 | 2.28 | 11.13 | 2.28 | 10.13 | 10.13 | 0.300000 | 0.225422 | 10.13 |
VAV_MID WITH REHEAT | 54.26 | 22.84 | 108.52 | 22.84 | 95.98 | 95.98 | 0.300000 | 0.237927 | 95.98 |
VAV_TOP WITH REHEAT | 5.66 | 2.29 | 11.32 | 2.51 | 11.02 | 11.02 | 0.300000 | 0.227526 | 11.02 |
CAV_BAS | 5.50 | 5.50 | 5.50 | 5.50 | 5.50 | 5.50 | 1.00 | 1.00 | 5.50 |
AIRLOOP DATACENTER BASEMENT | 21.40 | 21.40 | 21.40 | 21.40 | 21.40 | 21.40 | 1.00 | 0.999992 | 21.40 |
AIRLOOP DATACENTER BOT | 0.472007 | 0.472007 | 0.472007 | 0.472007 | 0.472007 | 0.472007 | 1.00 | 1.00 | 0.472007 |
AIRLOOP DATACENTER MID | 4.50 | 4.50 | 4.50 | 4.50 | 4.50 | 4.50 | 1.00 | 1.00 | 4.50 |
AIRLOOP DATACENTER TOP | 0.454158 | 0.454158 | 0.454158 | 0.454158 | 0.454158 | 0.454158 | 1.00 | 1.00 | 0.454158 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.13 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 95.98 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.02 | |
CAV_BAS_OA_CONTROLLER | 5.50 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.40 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.472007 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.50 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.454158 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.77 | 6.67 | 11.05 | 0.008030 | 0.007000 | 239610.45 | 0.006853 | 10.13 |
VAV_MID WITH REHEAT COOLING COIL | 27.99 | 6.67 | 11.04 | 0.008119 | 0.007000 | 2322704.10 | 0.066429 | 95.98 |
VAV_TOP WITH REHEAT COOLING COIL | 27.47 | 6.67 | 11.05 | 0.007998 | 0.007000 | 255450.26 | 0.007306 | 11.02 |
CAV_BAS COOLING COIL | 27.94 | 6.67 | 11.42 | 0.008270 | 0.007000 | 132688.31 | 0.003795 | 5.50 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.13 |
VAV_MID WITH REHEAT FAN | 95.98 |
VAV_TOP WITH REHEAT FAN | 11.02 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006853 | 0.000069 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000086 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.066429 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.000000 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007306 | 0.000065 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000000 | |
CAV_BAS_COOLC_CONTROLLER | 0.003795 | 0.000125 |
CAV_BAS_HEATC_CONTROLLER | 0.002165 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.50 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.40 | 450095.81 | 286785.17 | 0.011023 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.472007 | 9955.12 | 6321.30 | 0.000244 |
AIRLOOP DATACENTER MID COOLING COIL | 4.50 | 95057.60 | 60337.94 | 0.002328 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.454158 | 9591.70 | 6086.43 | 0.000235 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.40 | 21.40 | 21.40 | 21.40 | 450095.81 | 450095.81 | 11172.98 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.472007 | 0.472007 | 0.472007 | 0.472007 | 9955.12 | 9955.12 | 516.15 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.50 | 4.50 | 4.50 | 4.50 | 95057.60 | 95057.60 | 5161.45 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.454158 | 0.454158 | 0.454158 | 0.454158 | 9591.70 | 9591.70 | 516.15 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.40 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.472007 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.50 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.454158 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.40 | 450095.81 | 0.011023 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.472007 | 9955.12 | 0.000244 |
AIRLOOP DATACENTER MID HEATING COIL | 4.50 | 95057.60 | 0.002328 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.454158 | 9591.70 | 0.000235 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 11172.98 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 516.15 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 5161.45 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 516.15 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000022 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.084383 | 13640.69 | |
HEATSYS1 PUMP | 0.009055 | 2699.96 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.084383 | 10.13 |
HEATSYS1 | 0.009055 | 1.09 |
COOLSYS1_SUPPLY | 0.084383 | 10.13 |
SINGLE WATER PLANT LOOP | 0.013829 | 1.66 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.084383 | 0.084383 | 354196.05 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1035039.75 | 1035039.75 | 0.009055 |
CENTRAL BOILER | 569655.70 | 558805.65 | 0.013829 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.042191 | 4721.96 |
COOLSYS1 CHILLER2 PUMP | 0.042191 | 4721.96 |
PLANT CIRC PUMP | 0.013829 | 3492.28 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.084383 | 0.042598 | 1493093.66 | 1500175.26 | 0.074238 |
COOLSYS1 CHILLER2 | 0.084383 | 0.042598 | 1493093.66 | 1500175.26 | 0.074238 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013829 | 139666.47 | 57306.04 | 69833.23 | 7004.20 | 21214.21 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.148476 | 17.82 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.148476 | 36395.47 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 57.10 | 1779921.56 | 11.42 | 222490.20 |
TOWERWATERSYS COOLTOWER 2 | 57.10 | 1779921.56 | 11.42 | 222490.20 |
Design Water Flow Rate [m3/s] Equipment # 45 | |
WSHPPLANT OPERATION SCHEME | 0.077110 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 6.600 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 11.442 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 6.600 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.670 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 9.779 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 225.078 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 6.600 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 491.023 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 18343.827 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 18343.827 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 16474.046 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16474.046 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2068.481 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.481 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2068.526 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2068.526 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1333.008 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1333.008 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5172.174 | 6.600 | 122.617 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5172.174 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 354.027 | 9.779 | 181.682 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 354.027 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 35 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 36 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 37 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 | ||
4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 38 | 1 | VerySmooth | 2.865 | 2.865 | 1.000 | 0.220 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.91956E-002 | 0.13026 | 0.64144 | 0.64144 | 0.24090 | 0.16342 | 0.24379 | 0.00000 | 0.84000 | 0.84000 | 0.10739 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.486 | 6.0748E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1309E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1321E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2756E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2766E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5896E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5903E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5426E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5431E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1580E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2332E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2977E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3606E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6066E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6560E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5556E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5883E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6239E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0110E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2576E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1206E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2225E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2224E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7703E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.6101E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1630E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2571E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3030E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3860E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6116E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6751E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5560E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5892E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1308E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1322E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2755E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2767E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5896E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5904E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5426E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5430E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3510E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4698E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1851E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3048E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0297E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0949E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6379E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6605E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7168E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7424E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4614E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5672E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5307E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4151E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8851E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0771E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3252E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3782E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1533E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1922E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0104E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0266E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6380E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6608E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4920E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4932E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2886E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2896E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1402E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1409E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5426E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5431E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5197E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5879E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3112E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3654E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1575E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1953E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5560E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5893E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2700E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1690E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7659E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.9711E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5501E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0381E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7703E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6072E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5177E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5850E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3088E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3605E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1536E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1834E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5557E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5883E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4919E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4931E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2885E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2894E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1401E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1406E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5426E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5431E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9101E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9651E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6550E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6949E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6076E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6224E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6381E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6609E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0075E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4827E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6194E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2600E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8049E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1457E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8851E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0771E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9312E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0285E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6814E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7753E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6258E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6839E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6379E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6604E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.0793E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4954E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5602E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.6640E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.9294E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4364E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.3990E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6803E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4413E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5383E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1569E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3241E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.2109E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1313E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.4843E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6997E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.8655E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8859E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2913E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5116E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0465E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1378E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3990E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6800E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6364E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1762E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2002E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8941E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3942E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7652E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4843E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6997E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.0903E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.5049E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5734E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.6745E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.9427E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4449E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.4063E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6840E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4457E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5423E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1618E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3279E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.2183E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1358E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.4917E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7034E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.8661E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8880E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2920E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5133E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0498E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1398E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4063E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6837E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6391E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1793E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2031E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8969E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3999E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7687E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4917E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7034E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 76089.85794 | 76089.85794 | 5.49542 | 5.49542 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 12.70000 | 9.15345E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 81670.77728 | 81670.77728 | 5.89862 | 5.89862 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 779392.73997 | 779392.73997 | 56.27935 | 56.27935 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 160426.92456 | 160426.92456 | 6.70499 | 10.77825 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 78657.09022 | 78657.09022 | 5.67996 | 5.67996 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 28867.83045 | 28867.83045 | 1.21801 | 1.21801 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 17758.47263 | 17758.47263 | 1.29443 | 1.29443 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 206.67511 | 206.67511 | 8.84845E-003 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14829.50304 | 14829.50304 | 1.08093 | 1.08093 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 39.35650 | 1.07759E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 444.64758 | 444.64758 | 1.89597E-002 | 8.72129E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19877.09260 | 19877.09260 | 1.44886 | 1.44886 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 1965.00048 | 1965.00048 | 8.29513E-002 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19354.96811 | 19354.96811 | 1.41079 | 1.41079 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 181356.22291 | 181356.22291 | 13.21976 | 13.21976 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 73954.43019 | 73954.43019 | 3.14310 | 3.14310 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 157855.43127 | 157855.43127 | 11.50666 | 11.50666 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 49291.74581 | 49291.74581 | 2.09542 | 2.09542 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 202258.11977 | 202258.11977 | 14.74335 | 14.74335 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 73857.64790 | 73857.64790 | 3.13896 | 3.13896 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 175162.11817 | 175162.11817 | 12.76818 | 12.76818 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07801E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 41540.30297 | 41540.30297 | 1.76356 | 1.76356 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 20153.72764 | 20153.72764 | 1.46910 | 1.46910 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 42.60600 | 1.07815E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 9339.53575 | 9339.53575 | 0.39746 | 0.39746 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16304.99863 | 16304.99863 | 1.18855 | 1.18855 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 39.84150 | 1.07767E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 6178.06950 | 6178.06950 | 0.26295 | 0.26295 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 22151.46209 | 22151.46209 | 1.61473 | 1.61473 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 9324.62611 | 9324.62611 | 0.39683 | 0.39683 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18824.24841 | 18824.24841 | 1.37219 | 1.37219 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 5440.96491 | 5440.96491 | 0.23144 | 0.23144 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8211.11336 | 8211.11336 | 0.47201 | 0.47201 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 78363.08403 | 78363.08403 | 4.50462 | 4.50462 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7899.68876 | 7899.68876 | 0.45416 | 0.45416 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 40.63367 | 1.07781E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372316.77929 | 372316.77929 | 21.40424 | 21.40424 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 33.97300 | 1.07667E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 12.70000 | 9.15345E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 183361.48 | 10.13338 | 10.13338 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 184.19 | 1.52292 | 1.52292 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1758425.24 | 95.98216 | 95.98216 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 2452.33 | 20.91929 | 20.91929 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 194971.52 | 11.01713 | 11.01713 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 245.38 | 2.50668 | 2.50668 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
7 | CAV_BAS | Cooling | Sensible | 92360.10 | 5.49542 | 5.49542 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 39626.51 | 1.20016 | 1.20016 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 373555.67 | 21.40442 | 21.40442 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 11172.98 | 0.33839 | 0.33839 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8242.81 | 0.47201 | 0.47201 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 516.15 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78694.41 | 4.50462 | 4.50462 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 5161.45 | 0.15632 | 0.15632 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8071.80 | 0.45416 | 0.45416 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 516.15 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.49542 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.89862 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32246 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27400 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61622 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85988 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18156E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.42299E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61622 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16265.68118 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42299E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 327.90336 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.27935 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33796 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28700 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 16.15217 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90124 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12734E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.82559E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 16.15217 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 322982.77057 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.82559E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7217.91821 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.67996 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33487 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28500 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.61879 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89298 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13776E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.95074E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.61879 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 45159.35835 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.95074E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1107.08011 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29443 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18450 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15700 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20323 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49200 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06505E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.97301E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20323 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2255.26996 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97301E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 45.92767 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.08093 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14238 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12100 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13079 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37968 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67590E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54192E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13079 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1762.51117 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54192E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 36.75850 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44886 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16484 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.14000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20284 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43957 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.31137E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.50645E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.20284 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4008.09318 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.50645E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 89.33762 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41079 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10909 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.30000E-002 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13120 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49248E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15517E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13120 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1320.43350 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15517E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 26.61890 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.21976 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18065 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.15400 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03584 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48174 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10900E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.23860E-004 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.14310 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 105602.82521 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.23860E-004 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2788.37861 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.50666 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35667 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84853E-003 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.15808E-004 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.09542 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
122 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 70390.66537 |
123 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.15808E-004 |
124 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1858.47978 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.74335 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16199 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13800 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.03458 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43197 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35201E-003 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.22649E-004 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.13896 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
136 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 105464.41661 |
137 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.22649E-004 |
138 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2784.73187 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.76818 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12054 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.10200 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30235 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32143 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16083E-003 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.18781E-004 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.76356 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
150 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 59299.83617 |
151 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.18781E-004 |
152 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1566.35204 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46910 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16256 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.13800 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20274 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43350 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34372E-003 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.16715E-004 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39746 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
164 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13341.23809 |
165 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16715E-004 |
166 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 352.11218 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18855 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12949 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.11000 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13074 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34531 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.94232E-003 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.72091E-005 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26295 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
178 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8825.47513 |
179 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.72091E-005 |
180 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 232.91972 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61473 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14790 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.12600 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20346 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39441 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57598E-003 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.16529E-004 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39683 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
192 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13319.92442 |
193 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16529E-004 |
194 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 351.55036 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.37219 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11216 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 9.50000E-002 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13036 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.39692E-003 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.79870E-005 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23144 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
206 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7771.32784 |
207 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.79870E-005 |
208 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 205.14135 |
209 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47201 |
210 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.50462 |
211 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45416 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.40424 |
213 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.56681 |
214 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28428 |
215 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.13362 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.28428 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.13338 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.13338 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.22542 |
221 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 54.25865 |
222 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 22.83671 |
223 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 108.51730 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 22.83671 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 95.98216 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 95.98216 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.23793 |
229 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.66227 |
230 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.28608 |
231 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.32453 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.50668 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.01713 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.01713 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.22753 |
237 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.49542 |
238 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.49542 |
239 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.49542 |
240 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.49542 |
241 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.49542 |
242 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.49542 |
243 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.40424 |
246 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.40424 |
247 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.40424 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.40424 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.40442 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.40442 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47201 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47201 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47201 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47201 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47201 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.47201 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
261 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.50462 |
262 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.50462 |
263 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.50462 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.50462 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.50462 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.50462 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
269 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45416 |
270 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45416 |
271 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45416 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45416 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45416 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45416 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
277 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.13338 |
278 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 95.98216 |
279 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.01713 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.49542 |
281 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.40442 |
282 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.47201 |
283 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.50462 |
284 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45416 |
285 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.13338 |
286 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.76762 |
287 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
288 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04875 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.02976E-003 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 239610.44721 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.85283E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.13338 |
294 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 9848.42218 |
295 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.61583E-005 |
296 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 177.13992 |
297 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.13338 |
298 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.85283E-003 |
299 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.94882E-005 |
300 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.61583E-005 |
301 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 95.98216 |
302 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.98615 |
303 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
304 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03968 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.11904E-003 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2322704.10043 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.64290E-002 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 95.98216 |
310 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 0.00000 |
311 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 0.00000 |
312 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1.00000 |
313 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 95.98216 |
314 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.64290E-002 |
315 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.16841E-006 |
316 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.00000 |
317 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.01713 |
318 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.47320 |
319 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
320 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04864 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.99792E-003 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 255450.25873 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.30584E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.01713 |
326 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 0.00000 |
327 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 0.00000 |
328 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1.00000 |
329 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.01713 |
330 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.30584E-003 |
331 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.51794E-005 |
332 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.00000 |
333 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.49542 |
334 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
335 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.94190 |
336 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
337 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.41909 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.27039E-003 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 132688.30792 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.79487E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.49542 |
343 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 247421.50362 |
344 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.16455E-003 |
345 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5710.13216 |
346 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.49542 |
347 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.79487E-003 |
348 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.25483E-004 |
349 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.16455E-003 |
350 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.40442 |
351 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
352 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.40442 |
353 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 450095.80842 |
354 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 286785.16735 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10228E-002 |
356 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.40442 |
357 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.40442 |
358 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.40442 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.40442 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 450095.80842 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 450095.80842 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11172.98038 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
364 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.40442 |
365 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.40442 |
366 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 450095.80842 |
367 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10228E-002 |
368 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11172.98038 |
369 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.23395E-005 |
370 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
371 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
373 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47201 |
374 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
375 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47201 |
376 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9955.12301 |
377 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6321.30334 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.43800E-004 |
379 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47201 |
380 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47201 |
381 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47201 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47201 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9955.12301 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9955.12301 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.14541 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
387 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47201 |
388 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47201 |
389 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9955.12301 |
390 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.43800E-004 |
391 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.14541 |
392 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.50462 |
393 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
394 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.50462 |
395 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 95057.59816 |
396 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 60337.94211 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32795E-003 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.50462 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.50462 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.50462 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.50462 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 95057.59816 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 95057.59816 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 5161.45407 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
406 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.50462 |
407 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.50462 |
408 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 95057.59816 |
409 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32795E-003 |
410 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5161.45407 |
411 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45416 |
412 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
413 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45416 |
414 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9591.70235 |
415 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6086.42919 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34900E-004 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45416 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45416 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45416 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45416 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9591.70235 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9591.70235 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.14541 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
425 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45416 |
426 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45416 |
427 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9591.70235 |
428 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34900E-004 |
429 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.14541 |
430 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.43826E-002 |
431 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 13640.69087 |
432 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.43826E-002 |
433 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.12591 |
434 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.43826E-002 |
435 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.43826E-002 |
436 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 354196.05214 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
438 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 9.05498E-003 |
439 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.08660 |
440 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 9.05498E-003 |
441 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2699.96249 |
442 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
443 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1035039.75253 |
444 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1035039.75000 |
445 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 9.05498E-003 |
446 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.43826E-002 |
447 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.12591 |
448 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.21913E-002 |
449 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4721.95515 |
450 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.21913E-002 |
451 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4721.95515 |
452 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.43826E-002 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.25977E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1493093.66454 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1500175.26500 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.42381E-002 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.43826E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.25977E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1493093.66454 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1500175.26500 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.42381E-002 |
462 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.38295E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.65954 |
464 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.38295E-002 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3492.28418 |
466 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.38295E-002 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 57306.04012 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7004.19857 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21214.21254 |
472 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 569655.69947 |
473 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 558805.65000 |
474 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.38295E-002 |
475 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
476 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
477 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
479 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
480 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14848 |
481 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.81715 |
482 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14848 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 36395.47421 |
484 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 57.10309 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1779921.56222 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.42062 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 222490.19528 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 57.10309 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1779921.56222 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.42062 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 222490.19528 |
492 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 7.71100E-002 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 45 | 7.71100E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15423.03 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 306080.79 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 42773.47 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 2138.33 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 1670.94 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 3798.39 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 1252.03 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 100073.57 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 66704.13 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 99942.46 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 56198.80 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 12641.67 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8362.64 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 12621.48 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7364.06 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 8992.73 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 0.00 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 0.00 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 204757.81 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 289593.39 | 196109.84 | 93483.55 | 0.68 | 64794.45 | 657.18 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2766693.61 | 1867618.61 | 899075.00 | 0.68 | 608898.49 | 6175.79 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 312798.09 | 212346.09 | 100452.00 | 0.68 | 71364.84 | 723.82 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 156366.89 | 106031.58 | 50335.30 | 0.68 | 32567.98 | 330.32 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.47 | 22.07 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.47 | 22.07 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_NORTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_EAST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_SOUTH_0.219 | N/A | 2.865 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.504_SHGC_WEST_0.219 | N/A | 2.865 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2909902112 | 0.2206427434 | Pass | Pass | 1.5177849591 | 4.4854454635 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 9.4936534674E-002 | 0.1847592892 | Pass | Pass | 9.8325664707E-002 | 0.2957613004 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.2096574720E-002 | 8.8338896157E-002 | Pass | Pass | 7.1486786181E-003 | 8.4226184193E-002 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.7583366568E-002 | 1.1270985844E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.1731117630E-002 | 0.1434387323 | Pass | Pass | 9.8045530729E-002 | 0.2959818478 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.6667334290E-002 | 0.1443826074 | Pass | Pass | 9.8142179990E-002 | 0.2961576797 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1113174382 | 0.1609733791 | Pass | Pass | 0.1317470173 | 0.4170413988 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1013377368 | 0.1653140464 | Pass | Pass | 0.1149571027 | 0.3662753744 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.2161248179E-002 | 6.3493810767E-002 | Pass | Pass | 6.9449344060E-003 | 8.2890132724E-002 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.5932308392E-002 | 6.4391599909E-002 | Pass | Pass | 6.9445312779E-003 | 8.3016250583E-002 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.4357176707E-002 | 8.7112296008E-002 | Pass | Pass | 2.2778648441E-002 | 0.2002254228 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.9865177348E-002 | 7.3773594041E-002 | Pass | Pass | 6.9453388010E-003 | 8.2516325855E-002 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 4.0292785679E-002 | 2.9893416827E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.2691373941E-002 | 2.8464406477E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.8714845473E-002 | 5.8560707860E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.9405158522E-002 | 4.2469305804E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.4315268603E-002 | 2.2762400949E-002 | Pass | Pass | 0.2622361840 | 1.1261036387 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.7401101296E-003 | 1.3226342172E-002 | Pass | Pass | 5.2260925361E-002 | 0.4742863785 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.0808682800E-002 | 3.5931255758E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1474122276E-004 | 1.2697006494E-004 | Pass | Pass | 1.7804799186E-003 | 1.4115571305E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.6545213742E-005 | 9.1824820825E-005 | Pass | Pass | 6.0458709826E-003 | 3.0245856132E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.2384848067E-005 | 8.8763976867E-005 | Pass | Pass | 2.0576067783E-002 | 9.3127771600E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.8074085264E-004 | 4.4874321272E-004 | Pass | Pass | 7.9443491186E-005 | 1.1437415340E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3636.60 | -133.3 | 0.00 | -8723.6 | 48186.05 | 42965.83 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.504_SHGC_NORTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.504_SHGC_EAST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.504_SHGC_WEST_0.219 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.865 | 0.220 | 0.242 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.865 | 0.220 | 0.242 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.504_SHGC_NORTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.504_SHGC_EAST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.504_SHGC_SOUTH_0.219 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.504_SHGC_WEST_0.219 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.865 | 0.220 | 0.242 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
North Total or Average | 1390.74 | 2.865 | 0.220 | 0.242 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.865 | 0.220 | 0.242 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 6.5999 | 2779.43 | 18343.83 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 165.73 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 6.5999 | 24961.20 | 164740.46 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 1488.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 6.5999 | 2496.12 | 16474.05 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 48.13 | 0.0000 | Y | 148.84 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.13 | 0.0000 | Y | 10.53 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.07 | 0.0000 | Y | 6.77 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.89 | 0.0000 | Y | 10.44 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.03 | 0.0000 | Y | 6.76 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 6.5999 | 3134.13 | 20684.81 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.08 | 0.0000 | Y | 105.17 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.04 | 0.0000 | Y | 67.65 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 6.5999 | 3134.20 | 20685.26 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.87 | 0.0000 | Y | 104.32 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 6.5999 | 2019.75 | 13330.08 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.99 | 0.0000 | Y | 67.54 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 6.5999 | 313.41 | 2068.48 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.08 | 0.0000 | Y | 10.52 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.03 | 0.0000 | Y | 6.76 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 6.5999 | 313.42 | 2068.53 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.87 | 0.0000 | Y | 10.43 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 6.5999 | 201.98 | 1333.01 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.99 | 0.0000 | Y | 6.75 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 6.5999 | 783.68 | 5172.17 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 47.61 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 9.7790 | 362.03 | 3540.27 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 36.26 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 9.7790 | 36.20 | 354.03 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 3.63 |
Interior Lighting Total | 6.6297 | 46320.38 | 307089.14 | 774.17 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.53 | 797.83 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.53 | 286.49 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2068.48 | 797.81 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 2068.48 | 286.48 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1333.01 | 514.14 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1333.01 | 184.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 41.85 | 41.85 | 104.26 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.85 | 62.85 | 11.67 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.85 | 46.68 | 233.05 | |
Exterior Lighting Total | 40855.88 | 348.98 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2941365.45 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1035039.75 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1500175.26 | 6.28 | 1313345.27 | 5.58 | 6.47 | 22.07 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1500175.26 | 6.28 | 1313345.27 | 5.58 | 6.47 | 22.07 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 558805.65 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1779921.56 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1779921.56 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 239610.45 | 289593.39 | 196109.84 | 93483.55 | 0.68 | - | 64794.45 | 657.18 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2322704.10 | 2766693.61 | 1867618.61 | 899075.00 | 0.68 | - | 608898.49 | 6175.79 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 255450.26 | 312798.09 | 212346.09 | 100452.00 | 0.68 | - | 71364.84 | 723.82 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 132688.31 | 156366.89 | 106031.58 | 50335.30 | 0.68 | - | 32567.98 | 330.32 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 450095.81 | 286785.17 | 163310.64 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9955.12 | 6321.30 | 3633.82 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 95057.60 | 60337.94 | 34719.66 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9591.70 | 6086.43 | 3505.27 | 0.63 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16265.68 | 15423.03 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 322982.77 | 306080.79 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 45159.36 | 42773.47 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 2255.27 | 2138.33 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 1762.51 | 1670.94 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4008.09 | 3798.39 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 1320.43 | 1252.03 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 105602.83 | 100073.57 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 70390.67 | 66704.13 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 105464.42 | 99942.46 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 59299.84 | 56198.80 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13341.24 | 12641.67 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 8825.48 | 8362.64 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13319.92 | 12621.48 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 7771.33 | 7364.06 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 9848.42 | 8992.73 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 0.00 | 0.00 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 0.00 | 0.00 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 247421.50 | 204757.81 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 450095.81 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9955.12 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 95057.60 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9591.70 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 11172.98 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 516.15 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 5161.45 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 516.15 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.13 | 21781.34 | 2149.46 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 95.98 | 207412.33 | 2160.95 | 1.00 | 1.08 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.02 | 23680.94 | 2149.46 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.50 | 9318.33 | 1695.65 | 1.00 | 1.16 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.40 | 35487.96 | 1657.97 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 528.70 | 1120.11 | 1.00 | 1.63 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.50 | 5045.66 | 1120.11 | 1.00 | 1.16 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 508.71 | 1120.11 | 1.00 | 1.65 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.084383 | 13640.69 | 161652.92 | 0.91 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.009055 | 2699.96 | 298174.34 | 0.91 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.042191 | 4721.96 | 111917.77 | 0.91 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.042191 | 4721.96 | 111917.77 | 0.91 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013829 | 3492.28 | 252524.76 | 0.91 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.148476 | 36395.47 | 245126.60 | 0.91 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.49 | 0.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 76089.86 | 76089.86 | 27.38 | 5.495 | 5.495 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00746 | 35.62 | 0.01077 | 1.200 | 0.00 |
CORE_BOTTOM | 81670.78 | 81670.78 | 32.72 | 5.899 | 5.899 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 35.62 | 0.01077 | 1.078 | 0.00 |
CORE_MID | 779392.74 | 779392.74 | 312.24 | 56.279 | 56.279 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 35.62 | 0.01077 | 10.778 | 0.00 |
CORE_TOP | 78657.09 | 78657.09 | 31.51 | 5.680 | 5.680 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 35.62 | 0.01077 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 17758.47 | 17758.47 | 56.66 | 1.294 | 1.294 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00729 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14829.50 | 14829.50 | 73.42 | 1.081 | 1.081 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00723 | 39.36 | 0.01078 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19877.09 | 19877.09 | 63.42 | 1.449 | 1.449 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00726 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19354.97 | 19354.97 | 95.83 | 1.411 | 1.411 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00717 | 41.96 | 0.01078 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 181356.22 | 181356.22 | 578.65 | 13.220 | 13.220 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00737 | 42.70 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 157855.43 | 157855.43 | 781.56 | 11.507 | 11.507 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00729 | 39.60 | 0.01078 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 202258.12 | 202258.12 | 645.33 | 14.743 | 14.743 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00734 | 42.80 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 175162.12 | 175162.12 | 867.25 | 12.768 | 12.768 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00726 | 41.83 | 0.01078 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 20153.73 | 20153.73 | 64.30 | 1.469 | 1.469 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00737 | 42.61 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16305.00 | 16305.00 | 80.73 | 1.189 | 1.189 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 24.00 | 24.00 | 0.00731 | 39.84 | 0.01078 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 22151.46 | 22151.46 | 70.68 | 1.615 | 1.615 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00734 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18824.25 | 18824.25 | 93.20 | 1.372 | 1.372 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00726 | 41.96 | 0.01078 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8211.11 | 8211.11 | 226.81 | 0.472 | 0.472 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78363.08 | 78363.08 | 2164.56 | 4.505 | 4.505 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7899.69 | 7899.69 | 218.21 | 0.454 | 0.454 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 27.00 | 27.00 | 0.00709 | 40.63 | 0.01078 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372316.78 | 372316.78 | 475.09 | 21.404 | 21.404 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.97 | 0.01077 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.43 | 0.00915 | 12.70 | 0.00915 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.79 | 0.00915 | 12.70 | 0.00915 | 1.078 | 0.00 | |
CORE_MID | 160426.92 | 160426.92 | 64.27 | 6.705 | 10.778 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 28867.83 | 28867.83 | 11.57 | 1.218 | 1.218 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 206.68 | 206.68 | 0.66 | 0.009 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00889 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 444.65 | 444.65 | 2.20 | 0.019 | 0.087 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00864 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 1965.00 | 1965.00 | 6.27 | 0.083 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00844 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 21.54 | 0.00915 | 12.70 | 0.00915 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 73954.43 | 73954.43 | 235.96 | 3.143 | 3.143 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00824 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 49291.75 | 49291.75 | 244.05 | 2.095 | 2.095 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00824 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 73857.65 | 73857.65 | 235.65 | 3.139 | 3.139 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00824 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 41540.30 | 41540.30 | 205.67 | 1.764 | 1.764 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00830 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 9339.54 | 9339.54 | 29.80 | 0.397 | 0.397 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00819 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 6178.07 | 6178.07 | 30.59 | 0.263 | 0.263 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00818 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 9324.63 | 9324.63 | 29.75 | 0.397 | 0.397 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00819 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 5440.96 | 5440.96 | 26.94 | 0.231 | 0.231 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00823 | 12.70 | 0.00915 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.29 | 0.00702 | 12.70 | 0.00915 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.78 | 0.00833 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.13 | 10.13 | 1.52 | 1.52 | 10.1334 | 2.2843 | 10.1334 | 0.2254 | 0.3000 |
VAV_MID WITH REHEAT | 95.98 | 95.98 | 20.92 | 20.92 | 95.9822 | 22.8367 | 95.9822 | 0.2379 | 0.3000 |
VAV_TOP WITH REHEAT | 11.02 | 11.02 | 2.51 | 2.51 | 11.0171 | 2.5067 | 11.0171 | 0.2275 | 0.3000 |
CAV_BAS | 5.50 | 5.50 | 1.20 | 1.20 | 5.4954 | 5.4954 | 5.4954 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.40 | 21.40 | 0.34 | 0.34 | 21.4044 | 21.4042 | 21.4044 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4720 | 0.4720 | 0.4720 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.50 | 4.50 | 0.16 | 0.16 | 4.5046 | 4.5046 | 4.5046 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4542 | 0.4542 | 0.4542 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16265.681 | 16265.681 | 1.616221 | 0.00014230 | 327.903 | 1/21 00:10:00 | 1/21 00:10:00 | 16265.68 | 16265.68 | 1.616221 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 16325.66 | 16325.66 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 322982.771 | 322982.771 | 16.152174 | 0.00282559 | 7217.918 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 322982.77 | 322982.77 | 16.152174 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 160426.92 | 0.00 | 324090.10 | 324090.10 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 45159.358 | 45159.358 | 1.618789 | 0.00039507 | 1107.080 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 45159.36 | 45159.36 | 1.618789 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 28867.83 | 0.00 | 45301.76 | 45301.76 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 2255.270 | 2255.270 | 0.203225 | 0.00001973 | 45.928 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2255.27 | 2255.27 | 0.203225 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00888907 | 57.3565 | 206.68 | 0.00 | 2263.54 | 2263.54 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 1762.511 | 1762.511 | 0.130793 | 0.00001542 | 36.758 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1762.51 | 1762.51 | 0.130793 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00864167 | 55.7817 | 444.65 | 0.00 | 1768.90 | 1768.90 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 4008.093 | 4008.093 | 0.202840 | 0.00003506 | 89.338 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4008.09 | 4008.09 | 0.202840 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00844177 | 54.5082 | 1965.00 | 0.00 | 4021.85 | 4021.85 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 1320.433 | 1320.433 | 0.131203 | 0.00001155 | 26.619 | 1/21 00:10:00 | 1/21 00:10:00 | 1320.43 | 1320.43 | 0.131203 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1325.30 | 1325.30 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 105602.825 | 105602.825 | 3.143104 | 0.00092386 | 2788.379 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 105602.83 | 105602.83 | 3.143104 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00824047 | 53.2244 | 73954.43 | 0.00 | 105973.40 | 105973.40 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 70390.665 | 70390.665 | 2.095420 | 0.00061581 | 1858.480 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 70390.67 | 70390.67 | 2.095420 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00823540 | 53.1920 | 49291.75 | 0.00 | 70636.65 | 70636.65 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 105464.417 | 105464.417 | 3.138965 | 0.00092265 | 2784.732 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 105464.42 | 105464.42 | 3.138965 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00824121 | 53.2291 | 73857.65 | 0.00 | 105834.56 | 105834.56 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 59299.836 | 59299.836 | 1.763556 | 0.00051878 | 1566.352 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 59299.84 | 59299.84 | 1.763556 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00829904 | 53.5975 | 41540.30 | 0.00 | 59512.05 | 59512.05 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 13341.238 | 13341.238 | 0.397463 | 0.00011671 | 352.112 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13341.24 | 13341.24 | 0.397463 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00818639 | 52.8797 | 9339.54 | 0.00 | 13386.94 | 13386.94 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8825.475 | 8825.475 | 0.262951 | 0.00007721 | 232.920 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8825.48 | 8825.48 | 0.262951 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00818289 | 52.8574 | 6178.07 | 0.00 | 8855.64 | 8855.64 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 13319.924 | 13319.924 | 0.396826 | 0.00011653 | 351.550 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13319.92 | 13319.92 | 0.396826 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00818718 | 52.8848 | 9324.63 | 0.00 | 13365.56 | 13365.56 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7771.328 | 7771.328 | 0.231439 | 0.00006799 | 205.141 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7771.33 | 7771.33 | 0.231439 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00823064 | 53.1616 | 5440.96 | 0.00 | 7798.20 | 7798.20 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 239610.447 | -999.000 | 10.133377 | 0.00685283 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 239610.45 | 210996.12 | 10.133377 | 27.77 | 17.30 | 0.00802976 | 11.05 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 20.0377 | 24.00 | 0.00733976 | 39.5678 | 138963.66 | 0.00 | 239932.03 | 223707.62 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 9848.422 | 9848.422 | 3.040013 | 0.00008616 | 177.140 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9848.42 | 9848.42 | 3.040013 | 10.12 | 10.12 | 0.00910556 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 66.7925 | 21.44 | 0.00878190 | 55.1720 | 0.00 | 0.00 | 10888.63 | 10888.63 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2322704.100 | -999.000 | 95.982156 | 0.06642904 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2322704.10 | 2027279.88 | 95.982156 | 27.99 | 17.45 | 0.00811904 | 11.04 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 21.1560 | 24.00 | 0.00740224 | 39.9013 | 1313445.26 | 0.00 | 2325775.80 | 2145436.18 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 0.000 | 0.000 | 28.794647 | 0.00000000 | 1.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 28.794647 | 15.15 | 13.37 | 0.00883791 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 70.5201 | 21.00 | 0.00810865 | 52.3850 | 361679.65 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 255450.259 | -999.000 | 11.017134 | 0.00730584 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 255450.26 | 225372.57 | 11.017134 | 27.47 | 17.17 | 0.00799792 | 11.05 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 18.4304 | 24.00 | 0.00736676 | 39.7124 | 150723.03 | 0.00 | 255802.00 | 239238.27 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 0.000 | 0.000 | 3.305140 | 0.00000000 | 1.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 3.305140 | 15.90 | 13.57 | 0.00873110 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 61.4346 | 21.00 | 0.00806688 | 52.1190 | 41245.59 | 0.00 | 0.00 | 0.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 132688.308 | -999.000 | 5.495420 | 0.00379487 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 132688.31 | 113816.47 | 5.495420 | 27.94 | 17.56 | 0.00827039 | 11.42 | 9.94 | 0.00700000 | 40.57 | 0.01077797 | 23.25 | 21.8392 | 24.00 | 0.00748732 | 40.3537 | 69191.27 | 0.00 | 132857.95 | 121399.33 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 247421.504 | 247421.504 | 5.495420 | 0.00216455 | 5710.132 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 247421.50 | 247421.50 | 5.495420 | 2.77 | 2.77 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 21.8392 | 26.43 | 0.00915345 | 42.5676 | 0.00 | 0.00 | 216985.48 | 216985.48 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 450095.808 | 286785.167 | 21.404421 | 0.01102282 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 407450.86 | 402318.48 | -999.0 | 28.65 | 16.82 | 0.00710129 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | -999.0000 | 27.00 | 0.00704210 | 31.7848 | 371835.10 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9955.123 | 6321.303 | 0.472007 | 0.00024380 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 9017.79 | 8778.76 | -999.0 | 28.44 | 16.85 | 0.00721398 | 12.80 | 10.55 | 0.00700000 | 41.70 | 0.01077992 | 23.56 | -999.0000 | 27.00 | 0.00708960 | 31.9950 | 8067.84 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 95057.598 | 60337.942 | 4.504617 | 0.00232795 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 86114.74 | 83730.19 | -999.0 | 28.43 | 16.85 | 0.00722363 | 12.80 | 10.55 | 0.00700000 | 40.63 | 0.01077808 | 23.27 | -999.0000 | 27.00 | 0.00709369 | 32.0135 | 77100.73 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9591.702 | 6086.429 | 0.454158 | 0.00023490 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 8690.87 | 8455.78 | -999.0 | 28.46 | 16.86 | 0.00721865 | 12.80 | 10.55 | 0.00700000 | 41.83 | 0.01078014 | 23.60 | -999.0000 | 27.00 | 0.00709157 | 32.0039 | 7894.61 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 450095.808 | 450095.808 | 21.404421 | 0.01102282 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 450095.81 | 450095.81 | 21.404421 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 1.5809 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9955.123 | 9955.123 | 0.472007 | 0.00024380 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9955.12 | 9955.12 | 0.472007 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3119 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 95057.598 | 95057.598 | 4.504617 | 0.00232795 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 95057.60 | 95057.60 | 4.504617 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4703 | 25.29 | 0.00701680 | 35.0378 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9591.702 | 9591.702 | 0.454158 | 0.00023490 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9591.70 | 9591.70 | 0.454158 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4421 | 24.78 | 0.00833028 | 42.7848 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 11172.980 | 11172.980 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11172.98 | 11172.98 | 21.404421 | 0.20 | 0.20 | 0.00703404 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 1.5809 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.15 | 516.15 | 0.472007 | 0.42 | 0.42 | 0.00707132 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3119 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 5161.454 | 5161.454 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 5161.45 | 5161.45 | 4.504617 | 0.44 | 0.44 | 0.00709094 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4703 | 25.29 | 0.00701680 | 35.0378 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.15 | 516.15 | 0.454158 | 0.44 | 0.44 | 0.00835861 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4421 | 24.78 | 0.00833028 | 42.7848 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16265.681 | 16265.681 | 1.616221 | 0.00014230 | 327.903 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 1.5405 | 1.571503 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 16265.68 | 16265.68 | 1.0000 | 1.94527517 | 1.616221 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.14228476 | 60.00 | 32.22 | 27.78 | 0.000 | 16265.68 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 16325.66 | 16325.66 | 1.94527517 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 322982.771 | 322982.771 | 16.152174 | 0.00282559 | 7217.918 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 30.5892 | 31.204866 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 322982.77 | 322982.77 | 1.0000 | 19.44067570 | 16.152174 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.82530593 | 60.00 | 32.22 | 27.78 | 0.000 | 322982.77 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.59 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 160426.92 | 0.00 | 324090.10 | 324090.10 | 19.44067570 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.15 | 17.75 | 0.00800000 | 49730.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 45159.358 | 45159.358 | 1.618789 | 0.00039507 | 1107.080 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 4.2770 | 4.363055 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 45159.36 | 45159.36 | 1.0000 | 1.94836628 | 1.618789 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.39503347 | 60.00 | 32.22 | 27.78 | 0.000 | 45159.36 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 28867.83 | 0.00 | 45301.76 | 45301.76 | 1.94836628 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.60 | 19.85 | 0.00800000 | 56311.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2255.270 | 2255.270 | 0.203225 | 0.00001973 | 45.928 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 0.2136 | 0.217892 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2255.27 | 2255.27 | 1.0000 | 0.24460111 | 0.203225 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01972807 | 60.00 | 32.22 | 27.78 | 0.000 | 2255.27 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.99 | 0.00888907 | 21.00 | 0.00888907 | 57.3565 | 206.68 | 0.00 | 2263.54 | 2263.54 | 0.24460111 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.88 | 15.18 | 0.00800000 | 42313.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1762.511 | 1762.511 | 0.130793 | 0.00001542 | 36.758 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 0.1669 | 0.170284 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1762.51 | 1762.51 | 1.0000 | 0.15742152 | 0.130793 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01541764 | 60.00 | 32.22 | 27.78 | 0.000 | 1762.51 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.97 | 0.00864167 | 21.00 | 0.00864167 | 55.7817 | 444.65 | 0.00 | 1768.90 | 1768.90 | 0.15742152 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.82 | 15.89 | 0.00800000 | 44296.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4008.093 | 4008.093 | 0.202840 | 0.00003506 | 89.338 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 0.3796 | 0.387241 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4008.09 | 4008.09 | 1.0000 | 0.24413688 | 0.202840 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.03506097 | 60.00 | 32.22 | 27.78 | 0.000 | 4008.09 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.90 | 0.00844177 | 21.00 | 0.00844177 | 54.5082 | 1965.00 | 0.00 | 4021.85 | 4021.85 | 0.24413688 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.96 | 17.69 | 0.00800000 | 49533.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1320.433 | 1320.433 | 0.131203 | 0.00001155 | 26.619 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 0.1251 | 0.127573 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 1320.43 | 1320.43 | 1.0000 | 0.15791570 | 0.131203 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.01155055 | 60.00 | 32.22 | 27.78 | 0.000 | 1320.43 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 1325.30 | 1325.30 | 0.15791570 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 105602.825 | 105602.825 | 3.143104 | 0.00092386 | 2788.379 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 10.0015 | 10.202780 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 105602.83 | 105602.83 | 1.0000 | 3.78302391 | 3.143104 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.92376534 | 60.00 | 32.22 | 27.78 | 0.000 | 105602.83 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00824047 | 21.00 | 0.00824047 | 53.2244 | 73954.43 | 0.00 | 105973.40 | 105973.40 | 3.78302391 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.27 | 21.26 | 0.00800000 | 61072.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 70390.665 | 70390.665 | 2.095420 | 0.00061581 | 1858.480 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 6.6666 | 6.800769 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 70390.67 | 70390.67 | 1.0000 | 2.52203697 | 2.095420 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.61574543 | 60.00 | 32.22 | 27.78 | 0.000 | 70390.67 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00823540 | 21.00 | 0.00823540 | 53.1920 | 49291.75 | 0.00 | 70636.65 | 70636.65 | 2.52203697 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.27 | 21.26 | 0.00800000 | 61067.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 105464.417 | 105464.417 | 3.138965 | 0.00092265 | 2784.732 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 9.9884 | 10.189407 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 105464.42 | 105464.42 | 1.0000 | 3.77804247 | 3.138965 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.92255460 | 60.00 | 32.22 | 27.78 | 0.000 | 105464.42 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00824121 | 21.00 | 0.00824121 | 53.2291 | 73857.65 | 0.00 | 105834.56 | 105834.56 | 3.77804247 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.27 | 21.26 | 0.00800000 | 61072.9 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 59299.836 | 59299.836 | 1.763556 | 0.00051878 | 1566.352 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 5.6162 | 5.729233 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 59299.84 | 59299.84 | 1.0000 | 2.12260655 | 1.763556 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.51872791 | 60.00 | 32.22 | 27.78 | 0.000 | 59299.84 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.92 | 0.00829904 | 21.00 | 0.00829904 | 53.5975 | 41540.30 | 0.00 | 59512.05 | 59512.05 | 2.12260655 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61097.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13341.238 | 13341.238 | 0.397463 | 0.00011671 | 352.112 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 1.2635 | 1.288959 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13341.24 | 13341.24 | 1.0000 | 0.47838397 | 0.397463 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.11670306 | 60.00 | 32.22 | 27.78 | 0.000 | 13341.24 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00818639 | 21.00 | 0.00818639 | 52.8797 | 9339.54 | 0.00 | 13386.94 | 13386.94 | 0.47838397 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61043.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8825.475 | 8825.475 | 0.262951 | 0.00007721 | 232.920 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 0.8358 | 0.852670 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8825.48 | 8825.48 | 1.0000 | 0.31648645 | 0.262951 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07720123 | 60.00 | 32.22 | 27.78 | 0.000 | 8825.48 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00818289 | 21.00 | 0.00818289 | 52.8574 | 6178.07 | 0.00 | 8855.64 | 8855.64 | 0.31648645 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61040.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13319.924 | 13319.924 | 0.396826 | 0.00011653 | 351.550 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 1.2615 | 1.286900 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13319.92 | 13319.92 | 1.0000 | 0.47761761 | 0.396826 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.11651662 | 60.00 | 32.22 | 27.78 | 0.000 | 13319.92 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00818718 | 21.00 | 0.00818718 | 52.8848 | 9324.63 | 0.00 | 13365.56 | 13365.56 | 0.47761761 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61043.6 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7771.328 | 7771.328 | 0.231439 | 0.00006799 | 205.141 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 0.7360 | 0.750824 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7771.33 | 7771.33 | 1.0000 | 0.27855848 | 0.231439 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.06798003 | 60.00 | 32.22 | 27.78 | 0.000 | 7771.33 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00823064 | 21.00 | 0.00823064 | 53.1616 | 5440.96 | 0.00 | 7798.20 | 7798.20 | 0.27855848 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61054.7 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 239610.447 | -999.000 | 10.133377 | 0.00685283 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7669 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.133377 | 12.19648217 | 4197.9300 | 999.8980 | 84.37397768 | 15.00 | 6.67 | 8.33 | 2950453.11 | 8.1211 | 8.121141 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 239610.45 | 210996.12 | 1.0000 | 12.19648217 | 10.133377 | 27.77 | 17.30 | 0.00802976 | 48398.4 | 11.05 | 9.78 | 0.00700000 | 28752.6 | 6.85212940 | 6.67 | 15.00 | 8.33 | 21781.336 | 217829.11 | 42.80 | 0.01078182 | 23.86 | 2.03050000 | 20.0377 | 24.00 | 0.00733976 | 24.00 | 0.00733976 | 39.5678 | 138963.66 | 0.00 | 239932.03 | 223707.62 | 12.19648217 | 27.77 | 17.31 | 0.00802976 | 48398.4 | 9.78 | 9.76 | 0.00750170 | 28726.2 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9848.422 | 9848.422 | 3.040013 | 0.00008616 | 177.140 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.133377 | 12.19648217 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 0.9327 | 0.951502 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9848.42 | 9848.42 | 1.0000 | 3.65894465 | 3.040013 | 10.12 | 10.12 | 0.00910556 | 33114.2 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.08614950 | 60.00 | 32.22 | 27.78 | 0.000 | 9848.42 | 12.70 | 0.00915345 | 12.70 | 2.03050000 | 66.7925 | 4.93 | 0.00900923 | 21.44 | 0.00878190 | 55.1720 | 0.00 | 0.00 | 10888.63 | 10888.63 | 3.65894465 | 2.80 | 2.80 | 0.00910556 | 25633.4 | 5.71 | 5.71 | 0.00910556 | 28609.3 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2322704.100 | -999.000 | 95.982156 | 0.06642904 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9329 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.982156 | 115.52364164 | 4197.9300 | 999.8980 | 84.37397768 | 15.00 | 6.67 | 8.33 | 2950453.11 | 78.7236 | 78.723640 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 2322704.10 | 2027279.88 | 1.0000 | 115.52364164 | 95.982156 | 27.99 | 17.45 | 0.00811904 | 48849.2 | 11.04 | 9.78 | 0.00700000 | 28743.3 | 66.42226680 | 6.67 | 15.00 | 8.33 | 207412.328 | 2115291.77 | 42.80 | 0.01078182 | 23.86 | 20.30600000 | 21.1560 | 24.00 | 0.00740224 | 24.00 | 0.00740224 | 39.9013 | 1313445.26 | 0.00 | 2325775.80 | 2145436.18 | 115.52364164 | 27.99 | 17.46 | 0.00811904 | 48849.2 | 9.78 | 9.76 | 0.00749935 | 28716.8 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 0.000 | 0.000 | 28.794647 | 0.00000000 | 1.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.982156 | 115.52364164 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 0.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 34.65709249 | 28.794647 | 15.15 | 13.37 | 0.00883791 | 37572.2 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.00000000 | 60.00 | 32.22 | 27.78 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 20.30600000 | 70.5201 | 21.00 | 0.00808311 | 21.00 | 0.00810865 | 52.3850 | 361679.65 | 0.00 | 0.00 | 0.00 | 34.65709249 | 2.80 | 2.80 | 0.00883791 | 24962.6 | 2.80 | 2.80 | 0.00883791 | 24962.6 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 255450.259 | -999.000 | 11.017134 | 0.00730584 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7077 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.017134 | 13.26016712 | 4197.9300 | 999.8980 | 84.37397768 | 15.00 | 6.67 | 8.33 | 2950453.11 | 8.6580 | 8.658001 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 255450.26 | 225372.57 | 1.0000 | 13.26016712 | 11.017134 | 27.47 | 17.17 | 0.00799792 | 48017.0 | 11.05 | 9.78 | 0.00700000 | 28752.5 | 7.30509979 | 6.67 | 15.00 | 8.33 | 23680.939 | 231769.32 | 42.80 | 0.01078182 | 23.86 | 2.03050000 | 18.4304 | 24.00 | 0.00736676 | 24.00 | 0.00736676 | 39.7124 | 150723.03 | 0.00 | 255802.00 | 239238.27 | 13.26016712 | 27.47 | 17.18 | 0.00799792 | 48017.0 | 9.78 | 9.76 | 0.00750206 | 28725.9 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 0.000 | 0.000 | 3.305140 | 0.00000000 | 1.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.017134 | 13.26016712 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 0.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 3.97805013 | 3.305140 | 15.90 | 13.57 | 0.00873110 | 38072.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.00000000 | 60.00 | 32.22 | 27.78 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 2.03050000 | 61.4346 | 21.00 | 0.00805831 | 21.00 | 0.00806688 | 52.1190 | 41245.59 | 0.00 | 0.00 | 0.00 | 3.97805013 | 2.80 | 2.80 | 0.00873110 | 24695.0 | 2.80 | 2.80 | 0.00873110 | 24695.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 132688.308 | -999.000 | 5.495420 | 0.00379487 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2142 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.495420 | 6.61425937 | 4197.9300 | 999.8980 | 84.37397768 | 15.00 | 6.67 | 8.33 | 2950453.11 | 4.4972 | 4.497218 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 132688.31 | 113816.47 | 1.0000 | 6.61425937 | 5.495420 | 27.94 | 17.56 | 0.00827039 | 49190.5 | 11.42 | 9.94 | 0.00700000 | 29129.5 | 3.79448169 | 6.67 | 15.00 | 8.33 | 9318.332 | 123369.98 | 40.57 | 0.01077797 | 23.25 | 1.20015641 | 21.8392 | 24.00 | 0.00748732 | 24.00 | 0.00748732 | 40.3537 | 69191.27 | 0.00 | 132857.95 | 121399.33 | 6.61425937 | 27.94 | 17.57 | 0.00827039 | 49190.5 | 9.95 | 9.93 | 0.00758277 | 29103.9 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 247421.504 | 247421.504 | 5.495420 | 0.00216455 | 5710.132 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.495420 | 6.61425937 | 4197.9300 | 999.8980 | 9.05405558 | 54.44 | 82.22 | 27.78 | 1055870.34 | 23.4329 | 23.904541 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 247421.50 | 247421.50 | 1.0000 | 6.61425937 | 5.495420 | 2.77 | 2.77 | 0.00915345 | 25726.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.16433044 | 60.00 | 32.22 | 27.78 | 0.000 | 247421.50 | 12.70 | 0.00915345 | 12.70 | 1.20015641 | 21.8392 | 0.00 | 0.00915345 | 26.43 | 0.00915345 | 42.5676 | 0.00 | 0.00 | 216985.48 | 216985.48 | 6.61425937 | 12.80 | 12.75 | 0.00915345 | 35972.0 | 44.90 | 23.37 | 0.00915345 | 68777.7 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 450095.808 | 286785.167 | 21.404421 | 0.01102282 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0409 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 407450.86 | 402318.48 | 0.9053 | -999.0 | -999.0 | 28.65 | 16.82 | 0.00710129 | 46926.7 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 407450.86 | 42.80 | 0.01078182 | 23.86 | 0.33839277 | -999.0000 | 27.00 | 0.00704210 | 27.00 | 0.00704210 | 31.7848 | 371835.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9955.123 | 6321.303 | 0.472007 | 0.00024380 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2504 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 9017.79 | 8778.76 | 0.9058 | -999.0 | -999.0 | 28.44 | 16.85 | 0.00721398 | 47002.9 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9017.79 | 41.70 | 0.01077992 | 23.56 | 0.01563234 | -999.0000 | 27.00 | 0.00708960 | 27.00 | 0.00708960 | 31.9950 | 8067.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 95057.598 | 60337.942 | 4.504617 | 0.00232795 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2684 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 86114.74 | 83730.19 | 0.9059 | -999.0 | -999.0 | 28.43 | 16.85 | 0.00722363 | 47012.5 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86114.74 | 40.63 | 0.01077808 | 23.27 | 0.15632344 | -999.0000 | 27.00 | 0.00709369 | 27.00 | 0.00709369 | 32.0135 | 77100.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9591.702 | 6086.429 | 0.454158 | 0.00023490 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2591 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | Sensible | 8690.87 | 8455.78 | 0.9061 | -999.0 | -999.0 | 28.46 | 16.86 | 0.00721865 | 47030.6 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8690.87 | 41.83 | 0.01078014 | 23.60 | 0.01563234 | -999.0000 | 27.00 | 0.00709157 | 27.00 | 0.00709157 | 32.0039 | 7894.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 450095.808 | 450095.808 | 21.404421 | 0.01102282 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 450095.81 | 450095.81 | 1.0000 | 25.76225375 | 21.404421 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 450095.81 | 12.70 | 0.00915345 | 12.70 | 0.33839277 | 1.5809 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9955.123 | 9955.123 | 0.472007 | 0.00024380 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9955.12 | 9955.12 | 1.0000 | 0.56810524 | 0.472007 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9955.12 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.3119 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 95057.598 | 95057.598 | 4.504617 | 0.00232795 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 95057.60 | 95057.60 | 1.0000 | 5.42173471 | 4.504617 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 95057.60 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 3.4703 | 0.00 | 0.00701680 | 25.29 | 0.00701680 | 35.0378 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9591.702 | 9591.702 | 0.454158 | 0.00023490 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9591.70 | 9591.70 | 1.0000 | 0.54662188 | 0.454158 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9591.70 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.4421 | 0.00 | 0.00833028 | 24.78 | 0.00833028 | 42.7848 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11172.980 | 11172.980 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.404421 | 25.76225375 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11172.98 | 11172.98 | 1.0000 | 25.76225375 | 21.404421 | 0.20 | 0.20 | 0.00703404 | 17796.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11172.98 | 12.70 | 0.00915345 | 12.70 | 0.33839277 | 1.5809 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.472007 | 0.56810524 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.15 | 516.15 | 1.0000 | 0.56810524 | 0.472007 | 0.42 | 0.42 | 0.00707132 | 18113.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.15 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.3119 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5161.454 | 5161.454 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.504617 | 5.42173471 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 5161.45 | 5161.45 | 1.0000 | 5.42173471 | 4.504617 | 0.44 | 0.44 | 0.00709094 | 18182.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5161.45 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 3.4703 | 0.00 | 0.00701680 | 25.29 | 0.00701680 | 35.0378 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.454158 | 0.54662188 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.15 | 516.15 | 1.0000 | 0.54662188 | 0.454158 | 0.44 | 0.44 | 0.00835861 | 21350.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.15 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.4421 | 0.00 | 0.00833028 | 24.78 | 0.00833028 | 42.7848 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5730.67 | 1787.83 | 1787.83 |
CORE_BOTTOM | 5749.83 | 1.00 | 1.00 |
CORE_MID | 5467.00 | 51.00 | 12.67 |
CORE_TOP | 5213.67 | 279.50 | 14.00 |
PERIMETER_BOT_ZN_3 | 5463.67 | 482.83 | 355.67 |
PERIMETER_BOT_ZN_2 | 5551.50 | 542.00 | 434.83 |
PERIMETER_BOT_ZN_1 | 5689.67 | 603.00 | 533.50 |
PERIMETER_BOT_ZN_4 | 5833.17 | 943.50 | 934.67 |
PERIMETER_MID_ZN_3 | 4903.50 | 1014.33 | 413.33 |
PERIMETER_MID_ZN_2 | 4429.50 | 825.33 | 547.50 |
PERIMETER_MID_ZN_1 | 5520.33 | 779.33 | 589.33 |
PERIMETER_MID_ZN_4 | 5370.83 | 916.00 | 641.50 |
PERIMETER_TOP_ZN_3 | 4768.33 | 1281.33 | 477.67 |
PERIMETER_TOP_ZN_2 | 5121.67 | 1045.50 | 589.17 |
PERIMETER_TOP_ZN_1 | 5385.83 | 941.33 | 625.67 |
PERIMETER_TOP_ZN_4 | 5212.33 | 1098.83 | 671.83 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1589.00 | 1589.00 |
DATACENTER_MID_ZN_6 | 5943.00 | 555.00 | 555.00 |
DATACENTER_TOP_ZN_6 | 5943.00 | 814.83 | 814.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 111.67 | 0.00 | 11.50 |
CORE_BOTTOM | 0.00 | 16.00 | 0.00 | 0.50 |
CORE_MID | 0.00 | 0.33 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 1.33 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 187.83 | 0.00 | 71.33 |
PERIMETER_BOT_ZN_2 | 0.00 | 201.33 | 0.00 | 94.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 252.50 | 0.00 | 117.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 543.33 | 0.00 | 178.17 |
PERIMETER_MID_ZN_3 | 0.00 | 161.67 | 0.00 | 63.83 |
PERIMETER_MID_ZN_2 | 0.00 | 238.33 | 0.00 | 101.33 |
PERIMETER_MID_ZN_1 | 0.00 | 223.67 | 0.00 | 103.50 |
PERIMETER_MID_ZN_4 | 0.00 | 318.67 | 0.00 | 103.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 202.00 | 0.00 | 74.17 |
PERIMETER_TOP_ZN_2 | 0.00 | 269.67 | 0.00 | 106.50 |
PERIMETER_TOP_ZN_1 | 0.00 | 255.67 | 0.00 | 107.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 338.17 | 0.00 | 109.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 738.67 | 0.00 | 511.67 |
DATACENTER_MID_ZN_6 | 0.00 | 626.33 | 0.00 | 442.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 604.17 | 0.00 | 433.17 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1236.00 | 0.00 | 933.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 1991.33 | 0.00 | 1198.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.538 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.477 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.458 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.453 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.670 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.770 | 0.038 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.826 | 0.037 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.154 | 0.038 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.718 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.884 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.936 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.972 | 0.090 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.697 | 0.108 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.890 | 0.112 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.902 | 0.108 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.929 | 0.112 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.664 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.576 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.648 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 24039895.07 | 0.00 | 24039895.07 | 0.00 | 24039895.07 | 37848132.68 | 3195.93 | 5564.07 | 0.00 | 721.93 |
CORE_BOTTOM | 24608297.75 | 0.00 | 24608297.75 | 0.00 | 24608297.75 | 33990283.35 | 7094.52 | 964.74 | 700.74 | 1561.61 |
CORE_MID | 0.22E+09 | 0.00 | 0.22E+09 | 0.00 | 0.22E+09 | 0.34E+09 | 7035.88 | 970.09 | 754.04 | 1092.93 |
CORE_TOP | 21691585.37 | 0.00 | 21691585.37 | 0.00 | 21691585.37 | 33990283.35 | 7080.79 | 1116.79 | 562.42 | 1059.93 |
PERIMETER_BOT_ZN_3 | 4121264.41 | 0.00 | 4121264.41 | 322129.40 | 4443393.82 | 4267819.30 | 3986.34 | 1078.83 | 3694.82 | 1561.61 |
PERIMETER_BOT_ZN_2 | 2968962.08 | 0.00 | 2968962.08 | 214752.79 | 3183714.87 | 2750345.05 | 3621.54 | 983.11 | 4155.35 | 1561.61 |
PERIMETER_BOT_ZN_1 | 4915142.19 | 0.00 | 4915142.19 | 322129.40 | 5237271.60 | 4267912.63 | 2993.72 | 910.89 | 4855.39 | 1561.61 |
PERIMETER_BOT_ZN_4 | 4555139.84 | 0.00 | 4555139.84 | 214752.79 | 4769892.63 | 2750345.05 | 1969.40 | 862.72 | 5927.88 | 1561.61 |
PERIMETER_MID_ZN_3 | 41347877.77 | 0.00 | 41347877.77 | 755463.31 | 42103341.08 | 42678193.03 | 4060.38 | 1032.15 | 3667.47 | 1092.93 |
PERIMETER_MID_ZN_2 | 32302036.20 | 0.00 | 32302036.20 | 503641.86 | 32805678.07 | 27503450.52 | 3258.63 | 994.73 | 4506.64 | 1989.43 |
PERIMETER_MID_ZN_1 | 52464699.35 | 0.00 | 52464699.35 | 755463.31 | 53220162.66 | 42679126.28 | 3002.98 | 903.73 | 4853.28 | 1092.93 |
PERIMETER_MID_ZN_4 | 35869420.56 | 0.00 | 35869420.56 | 503641.86 | 36373062.42 | 27503450.52 | 3191.87 | 677.29 | 4890.84 | 1092.93 |
PERIMETER_TOP_ZN_3 | 4042679.71 | 0.00 | 4042679.71 | 937962.89 | 4980642.60 | 4267819.30 | 4198.31 | 978.23 | 3583.46 | 1059.93 |
PERIMETER_TOP_ZN_2 | 3250783.37 | 0.00 | 3250783.37 | 625308.16 | 3876091.54 | 2750345.05 | 3170.77 | 988.05 | 4601.18 | 1059.93 |
PERIMETER_TOP_ZN_1 | 5090569.43 | 0.00 | 5090569.43 | 937962.89 | 6028532.31 | 4267912.63 | 2950.01 | 975.93 | 4834.06 | 1059.93 |
PERIMETER_TOP_ZN_4 | 3460076.29 | 0.00 | 3460076.29 | 625308.16 | 4085384.45 | 2750345.05 | 3112.88 | 798.91 | 4848.20 | 1059.93 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.40E+10 | 0.00 | 0.40E+10 | 29382409.93 | 0.40E+10 | 0.50E+10 | 8708.61 | 8760.00 | 6376.44 | 3713.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9778 | 0.0000 | 0.9778 | 0.0000 | 0.9778 | 1.2002 | 1100.86 | 4842.14 | 0.00 |
CORE_BOTTOM | 0.8786 | 0.0000 | 0.8786 | 0.0000 | 0.8786 | 1.0778 | 4926.59 | 336.91 | 679.49 |
CORE_MID | 8.4300 | 0.0000 | 8.4300 | 0.0000 | 8.4300 | 10.7782 | 4722.68 | 473.14 | 747.18 |
CORE_TOP | 0.8328 | 0.0000 | 0.8328 | 0.0000 | 0.8328 | 1.0778 | 4773.77 | 608.95 | 560.28 |
PERIMETER_BOT_ZN_3 | 0.1545 | 0.0000 | 0.1545 | 0.0086 | 0.1630 | 0.1353 | 2083.61 | 390.21 | 3469.18 |
PERIMETER_BOT_ZN_2 | 0.1144 | 0.0000 | 0.1144 | 0.0057 | 0.1201 | 0.0872 | 1652.87 | 343.41 | 3946.73 |
PERIMETER_BOT_ZN_1 | 0.1907 | 0.0000 | 0.1907 | 0.0086 | 0.1992 | 0.1353 | 1067.61 | 288.45 | 4586.94 |
PERIMETER_BOT_ZN_4 | 0.1714 | 0.0000 | 0.1714 | 0.0057 | 0.1771 | 0.0872 | 639.06 | 257.51 | 5046.43 |
PERIMETER_MID_ZN_3 | 1.6540 | 0.0000 | 1.6540 | 0.0201 | 1.6741 | 1.3533 | 2041.45 | 427.76 | 3473.79 |
PERIMETER_MID_ZN_2 | 1.3119 | 0.0000 | 1.3119 | 0.0141 | 1.3260 | 0.8721 | 1124.92 | 381.80 | 3527.28 |
PERIMETER_MID_ZN_1 | 2.1599 | 0.0000 | 2.1599 | 0.0201 | 2.1800 | 1.3533 | 1028.50 | 315.23 | 4599.26 |
PERIMETER_MID_ZN_4 | 1.4427 | 0.0000 | 1.4427 | 0.0134 | 1.4561 | 0.8721 | 1173.63 | 353.20 | 4416.17 |
PERIMETER_TOP_ZN_3 | 0.1606 | 0.0000 | 0.1606 | 0.0249 | 0.1855 | 0.1353 | 2009.39 | 598.38 | 3335.23 |
PERIMETER_TOP_ZN_2 | 0.1321 | 0.0000 | 0.1321 | 0.0166 | 0.1487 | 0.0872 | 1104.05 | 575.19 | 4263.76 |
PERIMETER_TOP_ZN_1 | 0.2081 | 0.0000 | 0.2081 | 0.0249 | 0.2330 | 0.1353 | 964.43 | 453.74 | 4524.83 |
PERIMETER_TOP_ZN_4 | 0.1379 | 0.0000 | 0.1379 | 0.0166 | 0.1545 | 0.0872 | 1094.47 | 512.70 | 4335.84 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 155.8774 | 0.0000 | 155.8774 | 0.7874 | 156.6648 | 158.4706 | 5919.02 | 5943.00 | 5275.38 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 59638830.81 | 0.00 | 59638830.81 | 48026705.38 | 1867.78 | 3.97 | 6888.25 | 1561.61 |
VAV_MID WITH REHEAT | 0.55E+09 | 0.00 | 0.55E+09 | 0.48E+09 | 2497.94 | 2.48 | 6259.58 | 1092.93 |
VAV_TOP WITH REHEAT | 54375743.18 | 0.00 | 54375743.18 | 48026705.38 | 2546.27 | 2.37 | 6211.36 | 1059.93 |
CAV_BAS | 34825174.75 | 0.00 | 34825174.75 | 37848132.68 | 3195.93 | 0.00 | 5564.07 | 721.93 |
AIRLOOP DATACENTER BASEMENT | 15459249.82 | 0.00 | 15459249.82 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7141532.97 | 0.00 | 7141532.97 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1867 | 0.0000 | 2.1867 | 1.5229 | 577.22 | 2.34 | 5363.43 |
VAV_MID WITH REHEAT | 21.7336 | 0.0000 | 21.7336 | 15.2292 | 746.46 | 1.12 | 5195.42 |
VAV_TOP WITH REHEAT | 2.1316 | 0.0000 | 2.1316 | 1.5229 | 759.06 | 0.98 | 5182.95 |
CAV_BAS | 1.4165 | 0.0000 | 1.4165 | 1.2002 | 1100.86 | 0.00 | 4842.14 |
AIRLOOP DATACENTER BASEMENT | 0.4902 | 0.0000 | 0.4902 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2265 | 0.0000 | 0.2265 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 342.61 | 0.00 | 0.00 | 0.00 | 0.00 | 6617.70 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 556.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5762.87 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 323.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5948.30 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5564.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 2.3789 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4089 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 26.5612 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.5301 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 2.4205 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4316 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7386 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4902 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1515 |
Defaulted Fields | 1183 |
Fields with Defaults | 3871 |
Autosized Fields | 333 |
Autosizable Fields | 411 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 32692.14 | 352994.18 | 21-JAN-04:00 | 2157924.09 | 10-AUG-15:20 |
Electricity:Building | 17132.95 | 216480.96 | 29-MAY-17:20 | 1013929.88 | 15-DEC-17:00 |
Electricity:Zone:BASEMENT | 590.13 | 14055.89 | 01-JAN-00:10 | 28201.58 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17132.95 | 216480.96 | 29-MAY-17:20 | 1013929.88 | 15-DEC-17:00 |
InteriorLights:Electricity | 2456.55 | 9224.80 | 29-MAY-17:20 | 240337.66 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2456.55 | 9224.80 | 29-MAY-17:20 | 240337.66 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 2456.55 | 9224.80 | 29-MAY-17:20 | 240337.66 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 165.73 | 598.35 | 01-JAN-00:10 | 14744.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2456.55 | 9224.80 | 29-MAY-17:20 | 240337.66 | 15-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 438.45 | 4990.59 | 01-JAN-00:10 | 30447.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4384.49 | 49905.77 | 01-JAN-00:10 | 304477.41 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1488.37 | 5373.60 | 01-JAN-00:10 | 132411.79 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 438.45 | 4990.58 | 01-JAN-00:10 | 30447.74 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 148.84 | 537.36 | 01-JAN-00:10 | 13241.18 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 46.90 | 603.11 | 26-MAR-17:10 | 3655.10 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.53 | 43.94 | 01-JAN-09:30 | 1494.55 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 10.53 | 43.94 | 01-JAN-09:30 | 1494.55 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 30.21 | 388.67 | 21-MAY-17:10 | 2341.43 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.77 | 28.32 | 01-JAN-08:00 | 949.09 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 6.77 | 28.32 | 01-JAN-08:00 | 949.09 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 46.81 | 603.12 | 12-MAR-17:10 | 3651.78 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.44 | 43.94 | 01-JAN-08:00 | 1491.19 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 10.44 | 43.94 | 01-JAN-08:00 | 1491.19 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 30.20 | 388.67 | 12-MAR-17:10 | 2361.62 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.76 | 28.32 | 01-JAN-09:30 | 969.29 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 6.76 | 28.32 | 01-JAN-09:30 | 969.29 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 468.82 | 6031.15 | 19-MAR-17:10 | 36531.88 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 105.17 | 439.44 | 01-JAN-09:20 | 14926.37 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 105.17 | 439.44 | 01-JAN-09:20 | 14926.37 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 302.00 | 3886.70 | 21-MAY-17:10 | 23386.54 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 67.65 | 283.19 | 01-JAN-08:00 | 9463.12 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 67.65 | 283.19 | 01-JAN-08:00 | 9463.12 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 467.98 | 6031.24 | 12-MAR-17:10 | 36498.44 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.32 | 439.45 | 01-JAN-08:00 | 14892.59 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 104.32 | 439.45 | 01-JAN-08:00 | 14892.59 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 301.89 | 3886.68 | 12-MAR-17:10 | 23589.44 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 67.54 | 283.19 | 01-JAN-09:30 | 9666.11 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 67.54 | 283.19 | 01-JAN-09:30 | 9666.11 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 46.88 | 603.11 | 19-MAR-17:10 | 3652.84 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.52 | 43.94 | 01-JAN-09:20 | 1492.29 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 10.52 | 43.94 | 01-JAN-09:20 | 1492.29 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 30.20 | 388.67 | 21-MAY-17:10 | 2338.41 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.76 | 28.32 | 01-JAN-08:00 | 946.07 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 6.76 | 28.32 | 01-JAN-08:00 | 946.07 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 46.80 | 603.12 | 12-MAR-17:10 | 3649.49 | 15-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.43 | 43.94 | 01-JAN-08:00 | 1488.90 | 15-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 10.43 | 43.94 | 01-JAN-08:00 | 1488.90 | 15-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 30.19 | 388.67 | 12-MAR-17:10 | 2358.73 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.75 | 28.32 | 01-JAN-09:30 | 966.40 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 6.75 | 28.32 | 01-JAN-09:30 | 966.40 | 14-MAR-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7542.47 | 95139.07 | 01-JAN-00:10 | 383789.71 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 47.61 | 230.94 | 01-JAN-00:10 | 4157.19 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1575.07 | 19661.97 | 01-JAN-00:10 | 81110.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 36.26 | 175.92 | 01-JAN-00:10 | 3166.31 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 157.51 | 1966.20 | 01-JAN-00:10 | 8111.05 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 3.63 | 17.59 | 01-JAN-00:10 | 316.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 7097.27 | 11553.50 | 20-JAN-05:50 | 621051.64 | 03-AUG-14:50 |
HeatRejection:Electricity | 2039.27 | 7917.33 | 20-JAN-07:00 | 87148.87 | 30-APR-14:30 |
General:HeatRejection:Electricity | 2039.27 | 7917.33 | 20-JAN-07:00 | 87148.87 | 30-APR-14:30 |
Electricity:HVAC | 6258.33 | 76501.28 | 10-JAN-02:40 | 473577.18 | 04-AUG-12:50 |
ExteriorEquipment:Electricity | 1909.29 | 28161.90 | 01-JAN-00:10 | 116887.29 | 15-MAR-07:20 |
Transformer:ExteriorEquipment:Electricity | 54.67 | 979.82 | 01-JAN-00:10 | 3409.32 | 15-MAR-07:20 |
ElectricityPurchased:Facility | 32692.14 | 352994.18 | 21-JAN-04:00 | 2157924.09 | 10-AUG-15:20 |
ElectricityPurchased:Plant | 32692.14 | 352994.18 | 21-JAN-04:00 | 2157924.09 | 10-AUG-15:20 |
Cogeneration:ElectricityPurchased | 32692.14 | 352994.18 | 21-JAN-04:00 | 2157924.09 | 10-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 32692.14 | 352994.18 | 21-JAN-04:00 | 2157924.09 | 10-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 32692.14 | 352994.18 | 21-JAN-04:00 | 2157924.09 | 10-AUG-15:20 |
ElectricityNet:Plant | 32692.14 | 352994.18 | 21-JAN-04:00 | 2157924.09 | 10-AUG-15:20 |
Cogeneration:ElectricityNet | 32692.14 | 352994.18 | 21-JAN-04:00 | 2157924.09 | 10-AUG-15:20 |
General:Cogeneration:ElectricityNet | 32692.14 | 352994.18 | 21-JAN-04:00 | 2157924.09 | 10-AUG-15:20 |
Fans:Electricity | 2828.33 | 41571.02 | 13-JAN-04:30 | 273398.84 | 05-SEP-16:00 |
General:Fans:Electricity | 2828.33 | 41571.02 | 13-JAN-04:30 | 273398.84 | 05-SEP-16:00 |
ExteriorLights:Electricity | 348.98 | 0.00 | 01-JAN-07:10 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 348.98 | 0.00 | 01-JAN-07:10 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 7496.94 | 32024.98 | 21-JAN-05:50 | 683244.40 | 10-AUG-15:30 |
General:Cooling:Electricity | 7496.94 | 32024.98 | 21-JAN-05:50 | 683244.40 | 10-AUG-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 10.74 | 0.00 | 01-JAN-12:00 | 14438.86 | 26-APR-10:10 |
General:Humidifier:Electricity | 10.74 | 0.00 | 01-JAN-12:00 | 14438.86 | 26-APR-10:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 925.64 | 3492.28 | 03-JAN-05:50 | 55499.53 | 10-AUG-16:00 |
General:Pumps:Electricity | 925.64 | 3492.28 | 03-JAN-05:50 | 55499.53 | 10-AUG-16:00 |
WIRED_LTG_ELECTRICITY | 69.03 | 0.00 | 01-JAN-00:10 | 6753.49 | 15-MAR-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 574.56 | 7280.88 | 29-APR-16:10 | 69578.68 | 11-JAN-12:20 |
NaturalGas:Plant | 574.56 | 7280.88 | 29-APR-16:10 | 69578.68 | 11-JAN-12:20 |
Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 463.53 | 20-JAN-07:00 |
Boiler:Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 463.53 | 20-JAN-07:00 |
WaterSystems:NaturalGas | 574.55 | 7280.88 | 29-APR-16:10 | 69578.68 | 11-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 574.55 | 7280.88 | 29-APR-16:10 | 69578.68 | 11-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 40867.39 | 169530.64 | 21-JAN-05:50 | 3767885.43 | 10-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 40867.39 | 169530.64 | 21-JAN-05:50 | 3767885.43 | 10-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 40867.39 | 169530.64 | 21-JAN-05:50 | 3767885.43 | 10-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 26652.85 | 0.00 | 09-JAN-00:10 | 0.00 | 21-JUL-12:00 |
Water:HVAC | 4.00 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
Humidifier:Water | 4.00 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
General:Humidifier:Water | 4.00 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
MainsWater:Facility | 26652.85 | 0.00 | 09-JAN-00:10 | 0.00 | 21-JUL-12:00 |
MainsWater:HVAC | 4.00 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
Humidifier:MainsWater | 4.00 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
General:Humidifier:MainsWater | 4.00 | 0.00 | 01-JAN-12:00 | 0.00 | 26-APR-10:10 |
Water:Plant | 26648.85 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-12:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 26648.85 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-12:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 24368.68 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-12:00 |
General:HeatRejection:Water | 24368.68 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-12:00 |
HeatRejection:MainsWater | 24368.68 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-12:00 |
General:HeatRejection:MainsWater | 24368.68 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-12:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 148949.45 | 238783.50 | 21-JAN-05:50 | 14885083.18 | 10-AUG-16:00 |
EnergyTransfer:Building | 24775.64 | 101211.19 | 22-JAN-06:00 | 1854640.16 | 07-AUG-15:40 |
EnergyTransfer:Zone:BASEMENT | 780.75 | 0.00 | 01-JAN-00:10 | 79172.81 | 13-NOV-06:10 |
Heating:EnergyTransfer | 12.79 | 0.00 | 01-JAN-00:10 | 30145.71 | 29-JUL-16:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 5.78 | 0.00 | 01-JAN-00:10 | 30145.71 | 29-JUL-16:10 |
General:Heating:EnergyTransfer | 12.79 | 0.00 | 01-JAN-00:10 | 30145.71 | 29-JUL-16:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 5.78 | 0.00 | 01-JAN-00:10 | 30145.71 | 29-JUL-16:10 |
Cooling:EnergyTransfer | 24762.86 | 101211.19 | 22-JAN-06:00 | 1854640.16 | 07-AUG-15:40 |
Cooling:EnergyTransfer:Zone:BASEMENT | 774.97 | 0.00 | 01-JAN-00:10 | 79172.81 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 24762.86 | 101211.19 | 22-JAN-06:00 | 1854640.16 | 07-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 774.97 | 0.00 | 01-JAN-00:10 | 79172.81 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 785.81 | 0.00 | 01-JAN-00:10 | 66516.02 | 07-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 785.81 | 0.00 | 01-JAN-00:10 | 66516.02 | 07-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 785.81 | 0.00 | 01-JAN-00:10 | 66516.02 | 07-AUG-07:20 |
EnergyTransfer:Zone:CORE_MID | 6056.72 | 0.00 | 01-JAN-00:10 | 452817.74 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 6056.72 | 0.00 | 01-JAN-00:10 | 452817.74 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 6056.72 | 0.00 | 01-JAN-00:10 | 452817.74 | 05-SEP-13:10 |
EnergyTransfer:Zone:CORE_TOP | 627.77 | 0.00 | 01-JAN-00:10 | 53544.47 | 07-AUG-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 627.77 | 0.00 | 01-JAN-00:10 | 53544.47 | 07-AUG-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 627.77 | 0.00 | 01-JAN-00:10 | 53544.47 | 07-AUG-05:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 145.57 | 0.00 | 01-JAN-00:10 | 14973.04 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 145.57 | 0.00 | 01-JAN-00:10 | 14973.04 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 145.57 | 0.00 | 01-JAN-00:10 | 14973.04 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 106.89 | 0.00 | 01-JAN-00:10 | 12390.33 | 31-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 106.89 | 0.00 | 01-JAN-00:10 | 12390.33 | 31-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 106.89 | 0.00 | 01-JAN-00:10 | 12390.33 | 31-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 175.13 | 0.00 | 01-JAN-00:10 | 17010.04 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 175.13 | 0.00 | 01-JAN-00:10 | 17010.04 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 175.13 | 0.00 | 01-JAN-00:10 | 17010.04 | 05-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 158.92 | 0.00 | 01-JAN-00:10 | 17309.43 | 10-AUG-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 158.92 | 0.00 | 01-JAN-00:10 | 17309.43 | 10-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 158.92 | 0.00 | 01-JAN-00:10 | 17309.43 | 10-AUG-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1270.80 | 0.00 | 01-JAN-00:10 | 145503.61 | 21-JUL-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1270.80 | 0.00 | 01-JAN-00:10 | 145503.61 | 21-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1270.80 | 0.00 | 01-JAN-00:10 | 145503.61 | 21-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1016.24 | 0.00 | 01-JAN-00:10 | 132032.49 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1016.24 | 0.00 | 01-JAN-00:10 | 132032.49 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1016.24 | 0.00 | 01-JAN-00:10 | 132032.49 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1605.31 | 0.00 | 01-JAN-00:10 | 170069.20 | 19-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1605.31 | 0.00 | 01-JAN-00:10 | 170069.20 | 19-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1605.31 | 0.00 | 01-JAN-00:10 | 170069.20 | 19-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1105.47 | 0.00 | 01-JAN-00:10 | 135443.02 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1105.47 | 0.00 | 01-JAN-00:10 | 135443.02 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1105.47 | 0.00 | 01-JAN-00:10 | 135443.02 | 10-AUG-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 131.87 | 0.00 | 01-JAN-00:10 | 15720.31 | 21-JUL-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 180.32 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 180.32 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 131.87 | 0.00 | 01-JAN-00:10 | 15720.31 | 21-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 131.87 | 0.00 | 01-JAN-00:10 | 15720.31 | 21-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 107.52 | 0.00 | 01-JAN-00:10 | 13290.79 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 42.10 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 42.10 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 107.52 | 0.00 | 01-JAN-00:10 | 13290.79 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 107.52 | 0.00 | 01-JAN-00:10 | 13290.79 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 164.25 | 0.00 | 01-JAN-00:10 | 17815.82 | 05-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 164.25 | 0.00 | 01-JAN-00:10 | 17815.82 | 05-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 164.25 | 0.00 | 01-JAN-00:10 | 17815.82 | 05-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 113.35 | 0.00 | 01-JAN-00:10 | 14264.45 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 113.35 | 0.00 | 01-JAN-00:10 | 14264.45 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 113.35 | 0.00 | 01-JAN-00:10 | 14264.45 | 10-AUG-15:50 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 156.37 | 0.00 | 01-JAN-00:10 | 22267.74 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.67 | 0.00 | 01-JAN-00:10 | 3010.65 | 12-FEB-11:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.67 | 0.00 | 01-JAN-00:10 | 3010.65 | 12-FEB-11:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 155.70 | 0.00 | 01-JAN-00:10 | 22267.74 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 155.70 | 0.00 | 01-JAN-00:10 | 22267.74 | 07-AUG-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1266.27 | 0.00 | 01-JAN-00:10 | 157785.09 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.55 | 0.00 | 01-JAN-00:10 | 25111.16 | 16-JAN-11:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 4.55 | 0.00 | 01-JAN-00:10 | 25111.16 | 16-JAN-11:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1261.72 | 0.00 | 01-JAN-00:10 | 157785.09 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1261.72 | 0.00 | 01-JAN-00:10 | 157785.09 | 07-AUG-05:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 182.30 | 0.00 | 01-JAN-00:10 | 28101.39 | 16-AUG-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.78 | 0.00 | 01-JAN-00:10 | 5638.46 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.78 | 0.00 | 01-JAN-00:10 | 5638.46 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 180.52 | 0.00 | 01-JAN-00:10 | 28101.39 | 16-AUG-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 180.52 | 0.00 | 01-JAN-00:10 | 28101.39 | 16-AUG-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.25 | 1275.62 | 21-JAN-08:00 | 7832.76 | 23-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.25 | 1275.62 | 21-JAN-08:00 | 7832.76 | 23-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 144.25 | 1275.62 | 21-JAN-08:00 | 7832.76 | 23-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1350.34 | 8428.80 | 21-JAN-08:00 | 73807.99 | 23-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1350.34 | 8428.80 | 21-JAN-08:00 | 73807.99 | 23-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1350.34 | 8428.80 | 21-JAN-08:00 | 73807.99 | 23-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 134.71 | 288.82 | 01-JAN-08:40 | 7568.20 | 02-APR-16:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 134.71 | 288.82 | 01-JAN-08:40 | 7568.20 | 02-APR-16:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 134.71 | 288.82 | 01-JAN-08:40 | 7568.20 | 02-APR-16:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7189.02 | 89046.67 | 06-MAY-16:20 | 369105.82 | 30-APR-03:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7189.02 | 89046.67 | 06-MAY-16:20 | 369105.82 | 30-APR-03:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7189.02 | 89046.67 | 06-MAY-16:20 | 369105.82 | 30-APR-03:10 |
PlantLoopHeatingDemand:Facility | 265.49 | 0.00 | 01-JAN-00:10 | 35983.72 | 12-JAN-13:00 |
PlantLoopHeatingDemand:Plant | 265.45 | 0.00 | 01-JAN-00:10 | 35983.72 | 12-JAN-13:00 |
WaterSystems:PlantLoopHeatingDemand | 265.45 | 0.00 | 01-JAN-00:10 | 35983.72 | 12-JAN-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 265.45 | 0.00 | 01-JAN-00:10 | 35983.72 | 12-JAN-13:00 |
EnergyTransfer:HVAC | 37502.85 | 137505.67 | 21-JAN-05:50 | 3564692.51 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.04 | 0.00 | 01-JAN-00:10 | 2541.32 | 02-JAN-07:00 |
PlantLoopHeatingDemand:HVAC | 0.04 | 0.00 | 01-JAN-00:10 | 2541.32 | 02-JAN-07:00 |
HeatingCoils:PlantLoopHeatingDemand | 0.04 | 0.00 | 01-JAN-00:10 | 2541.32 | 02-JAN-07:00 |
CoolingCoils:EnergyTransfer | 37502.81 | 137505.67 | 21-JAN-05:50 | 3564692.51 | 10-AUG-16:00 |
EnergyTransfer:Plant | 86670.95 | 0.00 | 01-JAN-00:10 | 9511818.90 | 03-AUG-14:10 |
LoopToLoop:EnergyTransfer | 27589.97 | 0.00 | 01-JAN-00:10 | 3031529.26 | 03-AUG-14:10 |
WaterSystems:EnergyTransfer | 265.45 | 0.00 | 01-JAN-00:10 | 35983.72 | 12-JAN-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 265.45 | 0.00 | 01-JAN-00:10 | 35983.72 | 12-JAN-13:00 |
Boilers:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 293.08 | 20-JAN-07:00 |
Chillers:EnergyTransfer | 27341.58 | 0.00 | 01-JAN-00:10 | 3000279.83 | 10-AUG-16:00 |
HeatRejection:EnergyTransfer | 31473.94 | 0.00 | 01-JAN-00:10 | 3477565.30 | 19-JUL-15:00 |
General:HeatRejection:EnergyTransfer | 31473.94 | 0.00 | 01-JAN-00:10 | 3477565.30 | 19-JUL-15:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 5.781 | -774.966 | 0.000 | 0.000 | 92.653 | 165.729 | 424.397 | 0.000 | 0.000 | 0.000 | 86.405 | 0.000 | 0.000 | 0.000 | 0.000 | -0.005 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -785.811 | 0.000 | 0.000 | 83.410 | 148.837 | 289.614 | 0.000 | 0.000 | 0.000 | 263.951 | 0.000 | 0.000 | 0.000 | 0.000 | -0.005 |
CORE_MID | 0.000 | 0.000 | 0.000 | -6056.734 | 0.000 | 0.000 | 834.926 | 1488.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 837.314 | 0.000 | 0.000 | 0.000 | 0.000 | -0.009 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -627.774 | 0.000 | 0.000 | 83.571 | 148.837 | 289.613 | 0.000 | 0.000 | 0.000 | 105.754 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -145.574 | 0.000 | 0.000 | 10.467 | 10.532 | 36.365 | 63.061 | 0.000 | 1.741 | 40.131 | 0.000 | -16.173 | 0.000 | -0.550 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -106.895 | 0.000 | 0.000 | 6.742 | 6.773 | 23.435 | 64.691 | 0.000 | 1.154 | 14.351 | 0.000 | -9.889 | 0.000 | -0.363 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -175.132 | 0.000 | 0.000 | 10.456 | 10.441 | 36.366 | 100.780 | 0.000 | 1.714 | 32.187 | 0.000 | -16.204 | 0.000 | -0.608 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -158.918 | 0.000 | 0.000 | 6.728 | 6.764 | 23.435 | 63.125 | 0.000 | 1.104 | 71.583 | 0.000 | -13.340 | 0.000 | -0.482 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -1270.791 | 0.000 | 0.000 | 105.087 | 105.166 | 363.654 | 645.246 | 0.000 | 40.205 | 171.391 | 0.000 | -148.247 | 0.000 | -11.711 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -1016.236 | 0.000 | 0.000 | 49.416 | 67.649 | 234.352 | 643.512 | 0.000 | 26.021 | 101.385 | 0.000 | -97.481 | 0.000 | -8.619 | -0.005 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1605.301 | 0.000 | 0.000 | 104.651 | 104.323 | 363.660 | 1012.238 | 0.000 | 39.367 | 153.751 | 0.000 | -158.296 | 0.000 | -14.392 | -0.008 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -1105.464 | 0.000 | 0.000 | 67.503 | 67.541 | 234.351 | 651.567 | 0.000 | 25.862 | 179.084 | 0.000 | -111.158 | 0.000 | -9.286 | -0.003 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -131.865 | 0.000 | 0.000 | 10.545 | 10.516 | 36.365 | 63.936 | 0.000 | 4.870 | 21.360 | 0.000 | -14.342 | 0.000 | -1.385 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -107.523 | 0.000 | 0.000 | 6.759 | 6.765 | 23.435 | 64.195 | 0.000 | 3.182 | 13.669 | 0.000 | -9.463 | 0.000 | -1.020 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -164.245 | 0.000 | 0.000 | 10.483 | 10.432 | 36.366 | 100.500 | 0.000 | 4.778 | 18.830 | 0.000 | -15.418 | 0.000 | -1.726 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -113.352 | 0.000 | 0.000 | 6.767 | 6.754 | 23.435 | 64.689 | 0.000 | 3.149 | 20.502 | 0.000 | -10.827 | 0.000 | -1.117 | -0.002 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -144.249 | 0.000 | 0.000 | 0.934 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -14.191 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1350.346 | 0.000 | 0.000 | 9.368 | 36.263 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -234.090 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -134.711 | 0.000 | 0.000 | 0.937 | 3.626 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -23.732 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7189.035 | 0.000 | 0.000 | 19.175 | 47.611 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -372.608 |
GROUNDFLOOR_PLENUM | 0.673 | -155.696 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.188 | 153.105 | 0.000 | 0.000 | 0.000 | -1.270 | 0.000 |
MIDFLOOR_PLENUM | 4.550 | -1261.716 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 58.189 | 1220.593 | 0.000 | 0.000 | 0.000 | -21.616 | 0.000 |
TOPFLOOR_PLENUM | 1.783 | -180.515 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.247 | 174.776 | 0.000 | 0.000 | 0.000 | -2.292 | 0.000 |
Total Facility | 7.006 | -1597.926 | 5.781 | -23164.922 | 0.000 | 0.000 | 1520.577 | 2456.550 | 14676.396 | 3537.540 | 0.000 | 220.771 | 3680.122 | 0.000 | -620.837 | 0.000 | -76.437 | -644.660 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 18-DEC-05:11 | 0.00 | 0.00 | 0.00 | -108486.12 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 94430.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 21-FEB-05:11 | 0.00 | 0.00 | 0.00 | -99610.14 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 93135.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 21-OCT-04:13 | 0.00 | 0.00 | 0.00 | -894333.10 | 0.00 | 0.00 | 0.00 | 5373.60 | 44532.17 | 0.00 | 0.00 | 0.00 | 844427.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-05:04 | 0.00 | 0.00 | 0.00 | -87248.77 | 0.00 | 0.00 | 800.44 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 78263.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-JUL-15:51 | 0.00 | 0.00 | 0.00 | -24098.67 | 0.00 | 0.00 | 37.05 | 43.94 | 720.18 | 6150.77 | 0.00 | 389.34 | 16757.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-15:11 | 0.00 | 0.00 | 0.00 | -20068.62 | 0.00 | 0.00 | 23.28 | 28.32 | 464.11 | 4093.82 | 0.00 | 249.80 | 15209.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-13:52 | 0.00 | 0.00 | 0.00 | -26805.38 | 0.00 | 0.00 | 35.21 | 43.94 | 720.19 | 11005.25 | 0.00 | 214.77 | 14786.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-JUL-15:51 | 0.00 | 0.00 | 0.00 | -28293.24 | 0.00 | 0.00 | 18.20 | 28.32 | 464.11 | 8507.68 | 0.00 | 229.82 | 19045.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-SEP-14:51 | 0.00 | 0.00 | 0.00 | -248077.45 | 0.00 | 0.00 | 362.07 | 439.44 | 7201.84 | 65840.21 | 0.00 | 10045.97 | 164187.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-SEP-14:11 | 0.00 | 0.00 | 0.00 | -219044.03 | 0.00 | 0.00 | 216.31 | 283.19 | 4641.14 | 43708.99 | 0.00 | 7104.34 | 163090.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-14:11 | 0.00 | 0.00 | 0.00 | -290106.68 | 0.00 | 0.00 | 319.94 | 439.45 | 7201.95 | 101563.76 | 0.00 | 10210.21 | 170371.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-SEP-14:51 | 0.00 | 0.00 | 0.00 | -254350.41 | 0.00 | 0.00 | 187.64 | 283.19 | 4641.11 | 100970.44 | 0.00 | 6197.61 | 142070.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-SEP-14:01 | 0.00 | 0.00 | 0.00 | -28075.11 | 0.00 | 0.00 | 33.90 | 43.94 | 720.18 | 6708.03 | 0.00 | 1319.87 | 19249.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-SEP-14:01 | 0.00 | 0.00 | 0.00 | -23110.53 | 0.00 | 0.00 | 20.11 | 28.32 | 464.11 | 4281.37 | 0.00 | 860.18 | 17456.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-14:01 | 0.00 | 0.00 | 0.00 | -32348.59 | 0.00 | 0.00 | 29.56 | 43.94 | 720.19 | 10276.66 | 0.00 | 1238.37 | 20039.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-SEP-15:21 | 0.00 | 0.00 | 0.00 | -27407.28 | 0.00 | 0.00 | 16.89 | 28.32 | 464.11 | 10208.10 | 0.00 | 712.58 | 15977.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 23-APR-18:10 | 0.00 | 0.00 | 0.00 | -7834.57 | 0.00 | 0.00 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 22.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 23-APR-17:42 | 0.00 | 0.00 | 0.00 | -73807.79 | 0.00 | 0.00 | 0.00 | 175.92 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4312.35 |
DATACENTER_TOP_ZN_6 | 02-APR-16:22 | 0.00 | 0.00 | 0.00 | -7574.09 | 0.00 | 0.00 | 5.29 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -243.21 |
DATACENTER_BASEMENT_ZN_6 | 30-APR-03:07 | 0.00 | 0.00 | 0.00 | -369407.59 | 0.00 | 0.00 | 0.00 | 230.94 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10455.87 |
GROUNDFLOOR_PLENUM | 07-AUG-05:13 | 0.00 | -24587.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 | 24547.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 07-AUG-05:13 | 0.00 | -220874.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 752.02 | 220122.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 16-AUG-13:50 | 0.00 | -28100.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.77 | 27473.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:01 | 0.00 | -153947.55 | 0.00 | -2392258.92 | 0.00 | 0.00 | 14759.22 | 10593.62 | 616289.16 | 30345.15 | 0.00 | 2850.50 | 1871368.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-JUL-11:33 | 0.00 | 0.00 | 34799.67 | 0.00 | 0.00 | 0.00 | 397.73 | 819.05 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -49474.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:03 | 0.00 | 0.00 | 514.40 | 0.00 | 0.00 | 0.00 | 140.03 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 1074.91 | 0.00 | -2712.55 | 0.00 | -44.51 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:03 | 0.00 | 0.00 | 126.29 | 0.00 | 0.00 | 0.00 | 90.12 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 977.92 | 0.00 | -1826.95 | 0.00 | -29.67 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:11 | 11326.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -355.59 | -10970.75 |
MIDFLOOR_PLENUM | 21-FEB-05:11 | 75390.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9244.06 | -66146.28 |
TOPFLOOR_PLENUM | 01-FEB-06:03 | 14571.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -72.64 | -14498.50 |
Total Facility | 21-FEB-05:11 | -1285622.99 | 1370807.40 | 0.00 | -1370807.40 | 0.00 | 0.00 | 0.00 | 10593.62 | 350716.63 | 0.00 | 0.00 | 0.00 | 1066060.43 | 0.00 | -112017.23 | 0.00 | -29730.45 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.1336 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.1334 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 108.5173 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 95.9822 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.3245 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.0171 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.4954 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.4954 | 0.2184 | 1.0000 | Not calculated | 1.2002 | 0.2184 | ||
AIRLOOP DATACENTER BASEMENT | 21.4042 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.4044 | 0.0158 | 1.0000 | Not calculated | 0.3384 | 0.0158 | ||
AIRLOOP DATACENTER BOT | 0.4720 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4720 | 0.0331 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.5046 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5046 | 0.0347 | 1.0000 | Not calculated | 0.1563 | 0.0347 | ||
AIRLOOP DATACENTER TOP | 0.4542 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4542 | 0.0344 | 1.0000 | Not calculated | 0.0156 | 0.0344 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.5668 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2843 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 54.2587 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 22.8367 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.6623 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.2861 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.4954 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.4954 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2184 | ||
AIRLOOP DATACENTER BASEMENT | 21.4042 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.4042 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0158 | ||
AIRLOOP DATACENTER BOT | 0.4720 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4720 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.5046 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5046 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0347 | ||
AIRLOOP DATACENTER TOP | 0.4542 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4542 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0344 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4954 | 5.4954 | 5.4954 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8986 | 5.8986 | 1.6162 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.2794 | 56.2794 | 16.1522 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6800 | 5.6800 | 1.6188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2944 | 1.2944 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0809 | 1.0809 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4489 | 1.4489 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4108 | 1.4108 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.2198 | 13.2198 | 2.0358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.5067 | 11.5067 | 1.3118 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.7434 | 14.7434 | 2.0346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.7682 | 12.7682 | 1.3024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4691 | 1.4691 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1886 | 1.1886 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6147 | 1.6147 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3722 | 1.3722 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4720 | 0.4720 | 0.4720 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5046 | 4.5046 | 4.5046 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4542 | 0.4542 | 0.4542 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.4042 | 21.4042 | 21.4042 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.1336 | 10.1334 | 11.1336 | 2.2843 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 108.5173 | 95.9822 | 108.5173 | 22.8367 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.3245 | 11.0171 | 11.3245 | 2.2861 | 0.0000 | 1.0000 |
CAV_BAS | 5.4954 | 5.4954 | 5.4954 | 5.4954 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.4042 | 21.4044 | 21.4042 | 21.4042 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4720 | 0.4720 | 0.4720 | 0.4720 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5046 | 4.5046 | 4.5046 | 4.5046 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4542 | 0.4542 | 0.4542 | 0.4542 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4954 | 5.4954 | 5.4954 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9493 | 2.9493 | 1.6162 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.1397 | 28.1397 | 16.1522 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8400 | 2.8400 | 1.6188 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6472 | 0.6472 | 0.2032 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5405 | 0.5405 | 0.1308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7244 | 0.7244 | 0.2028 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7054 | 0.7054 | 0.1312 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6099 | 6.6099 | 2.0358 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7533 | 5.7533 | 1.3118 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.3717 | 7.3717 | 2.0346 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3841 | 6.3841 | 1.3024 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7346 | 0.7346 | 0.2027 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5943 | 0.5943 | 0.1307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8074 | 0.8074 | 0.2035 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6861 | 0.6861 | 0.1304 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4720 | 0.4720 | 0.4720 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5046 | 4.5046 | 4.5046 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4542 | 0.4542 | 0.4542 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.4042 | 21.4042 | 21.4042 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.5668 | 2.2843 | 2.2843 | 2.2843 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 54.2587 | 22.8367 | 22.8367 | 22.8367 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.6623 | 2.2861 | 2.2861 | 2.2861 | 0.0000 | 1.0000 |
CAV_BAS | 5.4954 | 5.4954 | 5.4954 | 5.4954 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.4042 | 21.4042 | 21.4042 | 21.4042 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4720 | 0.4720 | 0.4720 | 0.4720 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5046 | 4.5046 | 4.5046 | 4.5046 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4542 | 0.4542 | 0.4542 | 0.4542 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1198.83 |
Number of hours not met | 1198.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 0.01 | 463.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 7496.94 | 683244.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2456.55 | 240337.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 348.98 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 54.67 | 3409.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2828.33 | 273398.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 925.64 | 55499.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 2039.27 | 87148.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 10.74 | 14438.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 574.55 | 69578.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 32692.14 |
Natural Gas | 0.00 | 574.56 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 33266.70 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 53.03 |
Space Heating | 0.00 |
Space Cooling | 161.85 |
Fans (All) | 61.06 |
Service Water Heating | 0.00 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 705.78 |
Subtotal | 705.78 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 12.40 |
Miscellaneous (All) | 12.40 |
Subtotal | 12.40 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.38 |
Space Heating | 0.00 |
Space Cooling | 22.54 |
Fans (All) | 8.50 |
Service Water Heating | 1.73 |
Receptacle Equipment | 44.12 |
Miscellaneous | 15.73 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 892. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | January | 20.44 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_W_SB | PERIMETER_MID_ZN_2 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 6913.33 | 1846.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8690.67 | 69.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8241.33 | 518.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8187.83 | 572.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8068.17 | 691.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6715.33 | 2044.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8201.33 | 558.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7802.50 | 957.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7784.00 | 976.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7387.50 | 1372.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8030.67 | 729.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7693.67 | 1066.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7658.50 | 1101.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7349.50 | 1410.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 5843.50 | 2916.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 5731.33 | 3028.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 5790.50 | 2969.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6702.17 | 1929.67 | 128.17 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8061.83 | 698.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8478.50 | 281.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7729.33 | 1030.67 | 0.00 | 0.00 | 0.00 |
Min | 5731.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3028.67 | 128.17 | 0.00 | 0.00 |
Average | 7590.49 | 1163.94 | 5.57 | 0.00 | 0.00 |
Sum | 174581.17 | 26770.67 | 128.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 364024.00 | 4592.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330703.00 | 110.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330811.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1358.83 | 909.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1333.83 | 934.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1340.50 | 927.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 71787.83 | 28279.17 | 3328.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 364024.00 | 28279.17 | 3328.00 | 0.00 | 0.00 |
Average | 78635.70 | 1554.52 | 144.70 | 0.00 | 0.00 |
Sum | 1808621.00 | 35754.00 | 3328.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 3975.67 | 4784.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 6620.00 | 2140.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7381.50 | 1378.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 6922.50 | 1837.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6125.17 | 2634.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6186.17 | 2573.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5772.50 | 2987.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5340.00 | 3420.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6040.33 | 2719.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 5865.00 | 2895.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5725.17 | 3034.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5748.00 | 3012.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6065.00 | 2695.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 5915.17 | 2844.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5788.00 | 2972.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5805.83 | 2954.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6896.33 | 1863.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6834.17 | 1925.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6894.67 | 1865.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7528.50 | 1231.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3566.00 | 5194.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3203.00 | 5557.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3173.33 | 5586.67 | 0.00 | 0.00 | 0.00 |
Min | 3173.33 | 1231.50 | 0.00 | 0.00 | 0.00 |
Max | 7528.50 | 5586.67 | 0.00 | 0.00 | 0.00 |
Average | 5798.78 | 2961.22 | 0.00 | 0.00 | 0.00 |
Sum | 133372.00 | 68108.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 307056.00 | 61560.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 326694.00 | 4119.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328494.33 | 2318.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 326969.00 | 3844.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38920.17 | 4.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18351.17 | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38838.33 | 86.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24878.17 | 30.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38900.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1676.17 | 591.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1638.17 | 629.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1652.50 | 615.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 85373.33 | 18021.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 328494.33 | 61560.00 | 0.00 | 0.00 | 0.00 |
Average | 76341.18 | 3993.73 | 0.00 | 0.00 | 0.00 |
Sum | 1755847.17 | 91855.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:50:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.617047E+11 | 107522.61 | 02-JAN-05:11 | 13.67 | 11.10 | 0.567159E+10 | 7499.22 | 12-JAN-10:20 | 20.87 | 17.11 |
February | 0.549162E+11 | 101090.34 | 13-FEB-05:23 | 13.00 | 10.82 | 0.514380E+10 | 7499.57 | 15-FEB-14:20 | 25.33 | 18.17 |
March | 0.618032E+11 | 104973.68 | 06-MAR-05:12 | 16.67 | 12.96 | 0.613622E+10 | 7499.55 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.572843E+11 | 100161.40 | 24-APR-04:12 | 23.00 | 14.49 | 0.545291E+10 | 7499.98 | 25-APR-09:39 | 31.00 | 20.82 |
May | 0.612190E+11 | 95222.55 | 29-MAY-12:00 | 36.00 | 20.85 | 0.590431E+10 | 7499.81 | 08-MAY-13:39 | 36.00 | 20.85 |
June | 0.628308E+11 | 87710.65 | 02-JUN-04:28 | 27.80 | 17.94 | 0.588502E+10 | 7499.75 | 02-JUN-13:20 | 39.07 | 23.99 |
July | 0.663126E+11 | 99383.28 | 03-JUL-03:02 | 29.83 | 17.19 | 0.547649E+10 | 7500.05 | 21-JUL-13:09 | 42.25 | 27.34 |
August | 0.787994E+11 | 91820.29 | 06-AUG-09:00 | 37.00 | 23.69 | 0.613966E+10 | 7498.92 | 24-AUG-13:20 | 38.00 | 27.21 |
September | 0.659923E+11 | 92977.51 | 04-SEP-16:51 | 40.00 | 22.93 | 0.545537E+10 | 7499.25 | 26-SEP-13:00 | 39.00 | 23.79 |
October | 0.699799E+11 | 102022.84 | 29-OCT-13:00 | 35.10 | 15.03 | 0.567488E+10 | 7499.34 | 27-OCT-13:09 | 35.10 | 15.03 |
November | 0.683793E+11 | 99833.70 | 05-NOV-14:50 | 32.17 | 20.87 | 0.561842E+10 | 7499.11 | 17-NOV-14:20 | 29.00 | 19.48 |
December | 0.657465E+11 | 108489.57 | 18-DEC-05:11 | 13.00 | 10.66 | 0.547545E+10 | 7499.22 | 01-DEC-14:20 | 13.00 | 10.66 |
Annual Sum or Average | 0.774968E+12 | 0.680341E+11 | ||||||||
Minimum of Months | 0.549162E+11 | 87710.65 | 13.00 | 10.66 | 0.514380E+10 | 7498.92 | 13.00 | 10.66 | ||
Maximum of Months | 0.787994E+11 | 108489.57 | 40.00 | 23.69 | 0.613966E+10 | 7500.05 | 42.25 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482669E+11 | 99275.83 | 02-JAN-05:11 | 13.67 | 11.10 | 0.508015E+10 | 6734.85 | 09-JAN-10:20 | 16.40 | 15.51 |
February | 0.477400E+11 | 99626.34 | 21-FEB-05:11 | 14.67 | 13.69 | 0.460910E+10 | 6734.92 | 15-FEB-14:09 | 14.67 | 13.69 |
March | 0.628557E+11 | 96126.88 | 06-MAR-05:12 | 16.67 | 12.96 | 0.549908E+10 | 6735.14 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.676906E+11 | 89595.21 | 01-APR-04:12 | 18.13 | 16.90 | 0.487822E+10 | 6735.18 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.672736E+11 | 94958.34 | 01-MAY-04:23 | 21.65 | 21.48 | 0.528262E+10 | 6735.03 | 08-MAY-13:30 | 35.75 | 23.54 |
June | 0.701347E+11 | 87184.29 | 05-JUN-05:03 | 29.00 | 23.92 | 0.526741E+10 | 6734.88 | 02-JUN-13:09 | 29.00 | 23.92 |
July | 0.738109E+11 | 89059.33 | 31-JUL-05:05 | 30.83 | 27.07 | 0.489662E+10 | 6735.17 | 03-JUL-09:09 | 30.83 | 27.07 |
August | 0.863129E+11 | 90907.68 | 07-AUG-05:05 | 32.82 | 23.16 | 0.550402E+10 | 6786.59 | 07-AUG-09:00 | 38.70 | 24.39 |
September | 0.664216E+11 | 88264.04 | 25-SEP-05:04 | 23.00 | 22.27 | 0.487835E+10 | 6734.76 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.691622E+11 | 88179.95 | 10-OCT-05:03 | 26.83 | 24.08 | 0.507366E+10 | 6734.73 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.650951E+11 | 93836.23 | 28-NOV-05:13 | 19.00 | 15.91 | 0.502759E+10 | 6734.77 | 22-NOV-10:20 | 19.00 | 15.91 |
December | 0.610447E+11 | 96858.21 | 18-DEC-05:11 | 13.00 | 10.66 | 0.490162E+10 | 6734.81 | 20-DEC-10:20 | 21.60 | 16.49 |
Annual Sum or Average | 0.785809E+12 | 0.608984E+11 | ||||||||
Minimum of Months | 0.477400E+11 | 87184.29 | 13.00 | 10.66 | 0.460910E+10 | 6734.73 | 14.67 | 13.69 | ||
Maximum of Months | 0.863129E+11 | 99626.34 | 32.82 | 27.07 | 0.550402E+10 | 6786.59 | 38.70 | 27.07 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.368205E+11 | 84010.58 | 02-JAN-05:11 | 13.67 | 11.10 | 0.506508E+10 | 6734.85 | 09-JAN-10:20 | 16.40 | 15.51 |
February | 0.358529E+11 | 85698.15 | 21-FEB-05:11 | 14.67 | 13.69 | 0.459988E+10 | 6734.97 | 15-FEB-14:09 | 14.67 | 13.69 |
March | 0.460945E+11 | 86264.57 | 06-MAR-05:12 | 16.67 | 12.96 | 0.549651E+10 | 6735.15 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.477804E+11 | 86267.54 | 13-APR-04:12 | 19.07 | 15.51 | 0.487850E+10 | 6735.19 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.578265E+11 | 80930.93 | 04-MAY-04:13 | 23.53 | 18.44 | 0.527835E+10 | 6735.06 | 08-MAY-13:30 | 35.75 | 23.54 |
June | 0.591472E+11 | 67995.49 | 12-JUN-05:02 | 29.02 | 24.10 | 0.526130E+10 | 6734.93 | 02-JUN-13:09 | 29.02 | 24.10 |
July | 0.600943E+11 | 70181.12 | 10-JUL-05:02 | 32.00 | 25.13 | 0.488642E+10 | 6735.19 | 03-JUL-09:09 | 32.00 | 25.13 |
August | 0.642050E+11 | 76833.53 | 07-AUG-05:04 | 32.82 | 23.16 | 0.548901E+10 | 6734.72 | 07-AUG-13:20 | 36.93 | 28.94 |
September | 0.566230E+11 | 76564.34 | 05-SEP-05:03 | 30.17 | 24.66 | 0.487347E+10 | 6734.76 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.545683E+11 | 89457.11 | 21-OCT-04:13 | 22.40 | 15.15 | 0.507140E+10 | 6734.73 | 20-OCT-09:20 | 22.40 | 15.15 |
November | 0.470852E+11 | 86385.73 | 27-NOV-05:12 | 18.00 | 16.14 | 0.502487E+10 | 6734.77 | 22-NOV-10:20 | 18.00 | 16.14 |
December | 0.395743E+11 | 85456.60 | 04-DEC-05:12 | 17.77 | 16.55 | 0.489110E+10 | 6734.81 | 01-DEC-14:20 | 17.77 | 16.55 |
Annual Sum or Average | 0.605672E+12 | 0.608159E+11 | ||||||||
Minimum of Months | 0.358529E+11 | 67995.49 | 13.67 | 11.10 | 0.459988E+10 | 6734.72 | 14.67 | 13.69 | ||
Maximum of Months | 0.642050E+11 | 89457.11 | 32.82 | 25.13 | 0.549651E+10 | 6735.19 | 36.93 | 28.94 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322328E+11 | 79728.81 | 25-JAN-06:03 | 17.88 | 14.29 | 0.501677E+10 | 6734.82 | 09-JAN-10:20 | 17.88 | 14.29 |
February | 0.331133E+11 | 85318.81 | 08-FEB-05:12 | 22.00 | 18.65 | 0.457557E+10 | 6734.94 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.448112E+11 | 86044.63 | 24-MAR-04:11 | 20.07 | 19.04 | 0.548704E+10 | 6735.16 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.492930E+11 | 85863.97 | 10-APR-04:12 | 21.80 | 19.33 | 0.487937E+10 | 6735.17 | 28-APR-13:39 | 35.57 | 23.16 |
May | 0.632008E+11 | 86937.87 | 01-MAY-04:13 | 21.83 | 21.60 | 0.528378E+10 | 6735.03 | 08-MAY-13:30 | 35.75 | 23.54 |
June | 0.654806E+11 | 84737.48 | 12-JUN-05:03 | 29.02 | 24.10 | 0.526581E+10 | 6734.93 | 02-JUN-13:09 | 29.02 | 24.10 |
July | 0.678055E+11 | 85705.24 | 17-JUL-05:05 | 31.00 | 26.53 | 0.489416E+10 | 6735.18 | 03-JUL-09:09 | 31.00 | 26.53 |
August | 0.717584E+11 | 87268.34 | 07-AUG-05:04 | 32.82 | 23.16 | 0.549475E+10 | 6734.67 | 21-AUG-09:20 | 32.67 | 28.09 |
September | 0.614846E+11 | 85455.55 | 05-SEP-05:03 | 30.17 | 24.66 | 0.487836E+10 | 6734.75 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.568952E+11 | 86406.55 | 30-OCT-04:13 | 22.40 | 18.20 | 0.507437E+10 | 6734.73 | 20-OCT-09:20 | 22.40 | 18.20 |
November | 0.458068E+11 | 86541.94 | 13-NOV-05:12 | 21.00 | 17.39 | 0.502319E+10 | 6734.75 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.358915E+11 | 85449.69 | 11-DEC-05:12 | 22.00 | 18.87 | 0.486406E+10 | 6734.79 | 01-DEC-14:20 | 22.00 | 18.87 |
Annual Sum or Average | 0.627774E+12 | 0.607372E+11 | ||||||||
Minimum of Months | 0.322328E+11 | 79728.81 | 17.88 | 14.29 | 0.457557E+10 | 6734.67 | 17.88 | 14.29 | ||
Maximum of Months | 0.717584E+11 | 87268.34 | 32.82 | 26.53 | 0.549475E+10 | 6735.18 | 35.75 | 28.09 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491212E+10 | 12131.81 | 30-JAN-05:12 | 20.00 | 17.44 | 0.632483E+09 | 845.63 | 17-JAN-14:20 | 20.00 | 17.44 |
February | 0.568434E+10 | 15428.11 | 09-FEB-05:12 | 23.00 | 19.02 | 0.576514E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.899662E+10 | 19075.22 | 26-MAR-14:52 | 32.60 | 18.60 | 0.689962E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.115072E+11 | 17017.13 | 24-APR-04:21 | 22.75 | 14.38 | 0.613657E+09 | 845.69 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.149458E+11 | 23216.73 | 21-MAY-15:41 | 37.42 | 23.35 | 0.665660E+09 | 845.68 | 04-MAY-13:00 | 37.42 | 23.35 |
June | 0.167534E+11 | 23416.43 | 04-JUN-16:21 | 36.50 | 28.95 | 0.663685E+09 | 845.64 | 02-JUN-13:09 | 36.50 | 28.95 |
July | 0.183176E+11 | 24105.33 | 04-JUL-15:51 | 38.40 | 27.76 | 0.617878E+09 | 845.70 | 21-JUL-13:09 | 42.25 | 27.34 |
August | 0.204579E+11 | 23038.74 | 06-AUG-15:01 | 40.85 | 24.99 | 0.693443E+09 | 855.38 | 07-AUG-09:00 | 38.70 | 24.39 |
September | 0.145009E+11 | 22660.76 | 10-SEP-16:21 | 34.55 | 29.54 | 0.614799E+09 | 845.63 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.126978E+11 | 22172.75 | 01-OCT-13:52 | 35.00 | 26.13 | 0.638780E+09 | 845.62 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.970409E+10 | 15811.84 | 13-NOV-06:02 | 20.92 | 17.72 | 0.631613E+09 | 845.63 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.709653E+10 | 12870.89 | 12-DEC-06:03 | 23.03 | 17.89 | 0.613877E+09 | 845.63 | 01-DEC-14:20 | 23.03 | 17.89 |
Annual Sum or Average | 0.145574E+12 | 0.765235E+10 | ||||||||
Minimum of Months | 0.491212E+10 | 12131.81 | 20.00 | 14.38 | 0.576514E+09 | 845.62 | 20.00 | 17.44 | ||
Maximum of Months | 0.204579E+11 | 24105.33 | 40.85 | 29.54 | 0.693443E+09 | 855.38 | 42.25 | 28.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387003E+10 | 8584.69 | 30-JAN-05:12 | 20.00 | 17.44 | 0.409230E+09 | 544.96 | 24-JAN-10:00 | 20.00 | 17.44 |
February | 0.428444E+10 | 10632.24 | 05-FEB-15:02 | 32.00 | 19.31 | 0.372039E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.650143E+10 | 16106.92 | 26-MAR-14:52 | 32.60 | 18.60 | 0.444657E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.836542E+10 | 18313.11 | 30-APR-10:23 | 31.50 | 22.64 | 0.395578E+09 | 545.01 | 25-APR-09:09 | 31.50 | 22.64 |
May | 0.116871E+11 | 19827.99 | 29-MAY-09:52 | 37.10 | 22.97 | 0.429213E+09 | 545.29 | 22-MAY-09:00 | 37.10 | 22.97 |
June | 0.122828E+11 | 19404.97 | 04-JUN-15:41 | 36.83 | 28.78 | 0.427777E+09 | 544.96 | 02-JUN-13:09 | 36.83 | 28.78 |
July | 0.131055E+11 | 20077.26 | 04-JUL-15:11 | 39.47 | 27.45 | 0.398271E+09 | 545.08 | 31-JUL-09:00 | 39.90 | 23.78 |
August | 0.141595E+11 | 18941.72 | 06-AUG-15:01 | 40.85 | 24.99 | 0.446888E+09 | 552.89 | 07-AUG-09:00 | 38.70 | 24.39 |
September | 0.112282E+11 | 18898.38 | 10-SEP-16:21 | 34.55 | 29.54 | 0.396440E+09 | 545.02 | 05-SEP-09:00 | 34.55 | 29.54 |
October | 0.964669E+10 | 18528.82 | 01-OCT-13:52 | 35.00 | 26.13 | 0.411944E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.701082E+10 | 10870.12 | 12-NOV-13:52 | 30.00 | 18.61 | 0.407320E+09 | 544.95 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.475275E+10 | 5870.63 | 04-DEC-10:10 | 24.67 | 20.70 | 0.395407E+09 | 544.96 | 01-DEC-14:20 | 24.67 | 20.70 |
Annual Sum or Average | 0.106895E+12 | 0.493476E+10 | ||||||||
Minimum of Months | 0.387003E+10 | 5870.63 | 20.00 | 17.44 | 0.372039E+09 | 544.95 | 20.00 | 17.44 | ||
Maximum of Months | 0.141595E+11 | 20077.26 | 40.85 | 29.54 | 0.446888E+09 | 552.89 | 39.90 | 29.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.874776E+10 | 19868.93 | 30-JAN-05:12 | 20.00 | 17.44 | 0.636383E+09 | 845.66 | 24-JAN-10:00 | 20.00 | 17.44 |
February | 0.912000E+10 | 26264.61 | 05-FEB-13:42 | 31.52 | 19.39 | 0.578131E+09 | 845.69 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.119255E+11 | 25604.12 | 26-MAR-14:52 | 32.60 | 18.60 | 0.690759E+09 | 845.92 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.128734E+11 | 20500.00 | 30-APR-13:02 | 36.58 | 21.44 | 0.614049E+09 | 845.71 | 25-APR-09:09 | 36.58 | 21.44 |
May | 0.150127E+11 | 25946.13 | 21-MAY-15:41 | 37.42 | 23.35 | 0.665664E+09 | 845.70 | 04-MAY-13:00 | 37.42 | 23.35 |
June | 0.159622E+11 | 25806.28 | 04-JUN-15:41 | 36.83 | 28.78 | 0.663568E+09 | 845.66 | 02-JUN-13:09 | 36.83 | 28.78 |
July | 0.180171E+11 | 26692.14 | 04-JUL-15:11 | 39.47 | 27.45 | 0.617826E+09 | 845.71 | 03-JUL-09:09 | 39.47 | 27.45 |
August | 0.214256E+11 | 25800.63 | 06-AUG-15:01 | 40.85 | 24.99 | 0.693549E+09 | 855.52 | 07-AUG-09:00 | 38.70 | 24.39 |
September | 0.176218E+11 | 26400.35 | 10-SEP-13:42 | 35.07 | 29.55 | 0.615292E+09 | 846.03 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.178258E+11 | 26817.24 | 01-OCT-13:52 | 35.00 | 26.13 | 0.639826E+09 | 846.21 | 20-OCT-13:00 | 34.00 | 18.77 |
November | 0.151039E+11 | 26312.49 | 12-NOV-13:52 | 30.00 | 18.61 | 0.633104E+09 | 846.30 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.114959E+11 | 26542.79 | 03-DEC-12:42 | 29.50 | 17.81 | 0.615897E+09 | 845.72 | 04-DEC-14:09 | 27.00 | 21.00 |
Annual Sum or Average | 0.175132E+12 | 0.766405E+10 | ||||||||
Minimum of Months | 0.874776E+10 | 19868.93 | 20.00 | 17.44 | 0.578131E+09 | 845.66 | 20.00 | 16.45 | ||
Maximum of Months | 0.214256E+11 | 26817.24 | 40.85 | 29.55 | 0.693549E+09 | 855.52 | 39.47 | 28.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.542431E+10 | 18661.45 | 30-JAN-05:12 | 20.00 | 17.44 | 0.411109E+09 | 544.96 | 17-JAN-14:20 | 20.00 | 17.44 |
February | 0.688633E+10 | 24371.00 | 05-FEB-15:42 | 32.00 | 19.00 | 0.373716E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.110977E+11 | 25412.50 | 26-MAR-14:52 | 32.60 | 18.60 | 0.446344E+09 | 545.00 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.142805E+11 | 24869.05 | 23-APR-16:22 | 31.75 | 18.84 | 0.396839E+09 | 545.01 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.140171E+11 | 27168.81 | 21-MAY-15:41 | 37.42 | 23.35 | 0.429612E+09 | 545.00 | 04-MAY-13:00 | 37.42 | 23.35 |
June | 0.162949E+11 | 27304.20 | 04-JUN-16:21 | 36.50 | 28.95 | 0.428189E+09 | 544.96 | 02-JUN-13:09 | 36.50 | 28.95 |
July | 0.185167E+11 | 28305.20 | 04-JUL-15:51 | 38.40 | 27.76 | 0.398726E+09 | 545.00 | 03-JUL-09:09 | 38.40 | 27.76 |
August | 0.242230E+11 | 27032.20 | 06-AUG-15:41 | 40.25 | 25.55 | 0.447657E+09 | 553.47 | 07-AUG-09:00 | 38.70 | 24.39 |
September | 0.138486E+11 | 26083.43 | 10-SEP-16:21 | 34.55 | 29.54 | 0.396840E+09 | 544.95 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.132673E+11 | 25552.86 | 01-OCT-14:32 | 34.33 | 25.99 | 0.412692E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.113258E+11 | 24641.09 | 12-NOV-14:32 | 29.33 | 18.12 | 0.408548E+09 | 544.96 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.973603E+10 | 24426.66 | 03-DEC-14:42 | 27.00 | 20.88 | 0.398100E+09 | 544.96 | 01-DEC-14:09 | 27.00 | 20.88 |
Annual Sum or Average | 0.158918E+12 | 0.494837E+10 | ||||||||
Minimum of Months | 0.542431E+10 | 18661.45 | 20.00 | 17.44 | 0.373716E+09 | 544.95 | 20.00 | 17.44 | ||
Maximum of Months | 0.242230E+11 | 28305.20 | 40.25 | 29.54 | 0.447657E+09 | 553.47 | 38.70 | 28.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351589E+10 | 5299.71 | 23-JAN-14:10 | 27.50 | 16.66 | 0.614983E+09 | 845.63 | 17-JAN-14:20 | 27.50 | 16.66 |
February | 0.410789E+10 | 11614.10 | 09-FEB-06:02 | 22.92 | 19.06 | 0.567036E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.672305E+10 | 16764.24 | 26-MAR-14:52 | 32.60 | 18.60 | 0.686339E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.896288E+10 | 22302.80 | 30-APR-16:02 | 31.42 | 25.51 | 0.613412E+09 | 845.69 | 25-APR-09:09 | 31.42 | 25.51 |
May | 0.145117E+11 | 23703.09 | 29-MAY-16:41 | 35.85 | 24.03 | 0.665884E+09 | 845.68 | 04-MAY-13:00 | 35.85 | 24.03 |
June | 0.162756E+11 | 22689.61 | 11-JUN-15:02 | 36.90 | 27.61 | 0.663727E+09 | 845.64 | 02-JUN-13:09 | 36.90 | 27.61 |
July | 0.175837E+11 | 23404.59 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617836E+09 | 846.76 | 21-JUL-13:20 | 42.50 | 25.87 |
August | 0.183534E+11 | 23394.72 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692568E+09 | 846.89 | 04-AUG-13:20 | 40.85 | 24.99 |
September | 0.141598E+11 | 24817.36 | 04-SEP-14:51 | 41.00 | 24.23 | 0.614990E+09 | 845.63 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.112071E+11 | 22375.02 | 01-OCT-16:42 | 33.95 | 26.56 | 0.639105E+09 | 845.62 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.732775E+10 | 15770.32 | 05-NOV-15:22 | 31.70 | 21.27 | 0.630709E+09 | 845.62 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.435118E+10 | 9893.36 | 12-DEC-06:03 | 23.03 | 17.89 | 0.604063E+09 | 845.63 | 01-DEC-14:20 | 23.03 | 17.89 |
Annual Sum or Average | 0.127080E+12 | 0.761065E+10 | ||||||||
Minimum of Months | 0.351589E+10 | 5299.71 | 22.92 | 16.66 | 0.567036E+09 | 845.62 | 23.03 | 16.66 | ||
Maximum of Months | 0.183534E+11 | 24817.36 | 42.50 | 27.61 | 0.692568E+09 | 846.89 | 42.50 | 27.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.283409E+10 | 6378.20 | 24-JAN-11:05 | 24.00 | 18.08 | 0.298505E+09 | 548.51 | 24-JAN-11:09 | 24.00 | 18.08 |
February | 0.338621E+10 | 11529.09 | 05-FEB-14:52 | 32.00 | 19.39 | 0.272910E+09 | 548.50 | 16-FEB-15:09 | 24.78 | 18.41 |
March | 0.552873E+10 | 19179.46 | 26-MAR-14:52 | 32.60 | 18.60 | 0.327161E+09 | 548.54 | 28-MAR-10:09 | 27.17 | 20.40 |
April | 0.766225E+10 | 20447.33 | 23-APR-10:12 | 32.80 | 16.75 | 0.292837E+09 | 548.53 | 28-APR-14:09 | 35.00 | 23.22 |
May | 0.117911E+11 | 21003.60 | 29-MAY-09:22 | 35.55 | 23.00 | 0.317448E+09 | 548.56 | 11-MAY-12:09 | 35.55 | 23.00 |
June | 0.125335E+11 | 19842.07 | 11-JUN-10:22 | 38.50 | 26.61 | 0.315912E+09 | 548.52 | 02-JUN-12:09 | 38.50 | 26.61 |
July | 0.134352E+11 | 20620.09 | 30-JUL-09:42 | 41.80 | 21.60 | 0.295189E+09 | 548.49 | 13-JUL-10:09 | 41.80 | 21.60 |
August | 0.143733E+11 | 20302.64 | 06-AUG-15:01 | 40.85 | 24.99 | 0.329641E+09 | 548.49 | 24-AUG-12:09 | 37.25 | 26.69 |
September | 0.114248E+11 | 21915.58 | 04-SEP-14:11 | 41.00 | 24.86 | 0.293437E+09 | 548.49 | 26-SEP-14:09 | 39.00 | 24.02 |
October | 0.925334E+10 | 19800.58 | 01-OCT-12:02 | 34.50 | 25.92 | 0.305278E+09 | 548.50 | 11-OCT-12:09 | 34.35 | 20.55 |
November | 0.601562E+10 | 17247.64 | 05-NOV-15:22 | 31.70 | 21.27 | 0.301408E+09 | 548.49 | 06-NOV-15:09 | 31.90 | 21.82 |
December | 0.338593E+10 | 7086.74 | 04-DEC-11:05 | 26.25 | 20.62 | 0.290401E+09 | 548.50 | 01-DEC-13:09 | 26.25 | 20.62 |
Annual Sum or Average | 0.101624E+12 | 0.364013E+10 | ||||||||
Minimum of Months | 0.283409E+10 | 6378.20 | 24.00 | 16.75 | 0.272910E+09 | 548.49 | 24.00 | 18.08 | ||
Maximum of Months | 0.143733E+11 | 21915.58 | 41.80 | 26.61 | 0.329641E+09 | 548.56 | 41.80 | 26.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.770082E+10 | 16823.94 | 22-JAN-14:33 | 26.00 | 16.51 | 0.632845E+09 | 845.66 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.793666E+10 | 26917.35 | 05-FEB-13:32 | 31.43 | 19.44 | 0.575391E+09 | 845.70 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.100665E+11 | 26178.37 | 26-MAR-13:32 | 33.67 | 18.36 | 0.689381E+09 | 846.81 | 27-MAR-13:20 | 35.67 | 19.65 |
April | 0.105802E+11 | 25527.26 | 30-APR-13:22 | 35.55 | 22.14 | 0.614097E+09 | 845.71 | 25-APR-09:09 | 35.55 | 22.14 |
May | 0.145706E+11 | 26070.97 | 29-MAY-16:41 | 35.85 | 24.03 | 0.665878E+09 | 845.70 | 04-MAY-13:00 | 35.85 | 24.03 |
June | 0.154685E+11 | 24978.87 | 11-JUN-15:02 | 36.90 | 27.61 | 0.663595E+09 | 845.66 | 02-JUN-13:09 | 36.90 | 27.61 |
July | 0.173197E+11 | 26103.39 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617786E+09 | 845.72 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.196114E+11 | 26130.73 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692722E+09 | 846.95 | 17-AUG-13:20 | 43.33 | 25.24 |
September | 0.176571E+11 | 29023.84 | 04-SEP-14:11 | 41.00 | 24.86 | 0.615519E+09 | 846.85 | 01-SEP-13:20 | 41.00 | 24.86 |
October | 0.170406E+11 | 27108.17 | 01-OCT-12:02 | 34.50 | 25.92 | 0.640348E+09 | 846.76 | 16-OCT-13:20 | 32.93 | 25.16 |
November | 0.134181E+11 | 27667.60 | 05-NOV-12:02 | 33.90 | 17.83 | 0.633240E+09 | 846.72 | 03-NOV-13:20 | 33.90 | 17.83 |
December | 0.916073E+10 | 25779.54 | 03-DEC-15:02 | 26.85 | 20.89 | 0.613852E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.160531E+12 | 0.765465E+10 | ||||||||
Minimum of Months | 0.770082E+10 | 16823.94 | 26.00 | 16.51 | 0.575391E+09 | 845.66 | 23.00 | 17.31 | ||
Maximum of Months | 0.196114E+11 | 29023.84 | 42.50 | 27.61 | 0.692722E+09 | 846.95 | 43.33 | 27.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322859E+10 | 7883.88 | 30-JAN-06:03 | 20.03 | 17.43 | 0.402792E+09 | 544.96 | 17-JAN-14:20 | 20.03 | 17.43 |
February | 0.396837E+10 | 19324.52 | 05-FEB-15:32 | 32.00 | 19.08 | 0.369370E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.649872E+10 | 22413.42 | 26-MAR-16:52 | 31.20 | 18.81 | 0.444608E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.827760E+10 | 22832.24 | 30-APR-16:42 | 31.08 | 25.68 | 0.396294E+09 | 545.00 | 25-APR-09:09 | 31.08 | 25.68 |
May | 0.122122E+11 | 24699.54 | 29-MAY-16:41 | 35.85 | 24.03 | 0.429546E+09 | 545.00 | 04-MAY-13:00 | 35.85 | 24.03 |
June | 0.133891E+11 | 22487.51 | 18-JUN-16:02 | 35.98 | 27.42 | 0.428048E+09 | 544.96 | 02-JUN-13:09 | 35.98 | 27.42 |
July | 0.143450E+11 | 23017.53 | 30-JUL-15:02 | 40.45 | 27.73 | 0.398467E+09 | 545.00 | 03-JUL-09:09 | 40.45 | 27.73 |
August | 0.156346E+11 | 23522.50 | 06-AUG-15:41 | 40.25 | 25.55 | 0.446658E+09 | 544.95 | 04-AUG-13:20 | 40.25 | 25.55 |
September | 0.121457E+11 | 25449.46 | 04-SEP-14:51 | 41.00 | 24.23 | 0.396775E+09 | 544.95 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.992728E+10 | 22777.59 | 01-OCT-16:42 | 33.95 | 26.56 | 0.412520E+09 | 544.95 | 20-OCT-09:20 | 29.47 | 17.82 |
November | 0.675932E+10 | 22434.72 | 05-NOV-15:22 | 31.70 | 21.27 | 0.407570E+09 | 544.95 | 16-NOV-14:20 | 30.67 | 19.24 |
December | 0.416032E+10 | 9691.54 | 03-DEC-15:02 | 26.85 | 20.89 | 0.393827E+09 | 544.96 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.110547E+12 | 0.492648E+10 | ||||||||
Minimum of Months | 0.322859E+10 | 7883.88 | 20.03 | 17.43 | 0.369370E+09 | 544.95 | 20.03 | 17.31 | ||
Maximum of Months | 0.156346E+11 | 25449.46 | 41.00 | 27.73 | 0.446658E+09 | 545.00 | 40.45 | 27.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318363E+10 | 5514.39 | 23-JAN-14:10 | 27.50 | 16.66 | 0.600006E+09 | 845.63 | 17-JAN-14:20 | 27.50 | 16.66 |
February | 0.390542E+10 | 13179.60 | 06-FEB-06:02 | 21.88 | 19.06 | 0.558769E+09 | 845.66 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.664719E+10 | 18072.04 | 02-MAR-06:02 | 28.80 | 15.43 | 0.682445E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.918766E+10 | 24489.51 | 30-APR-16:11 | 31.33 | 25.55 | 0.612754E+09 | 845.69 | 25-APR-09:09 | 31.33 | 25.55 |
May | 0.154026E+11 | 26684.69 | 21-MAY-12:52 | 38.00 | 22.80 | 0.666026E+09 | 845.68 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.172631E+11 | 25616.67 | 11-JUN-15:02 | 36.90 | 27.61 | 0.663855E+09 | 845.65 | 02-JUN-13:09 | 36.90 | 27.61 |
July | 0.188889E+11 | 26553.27 | 30-JUL-14:22 | 42.50 | 25.87 | 0.618014E+09 | 845.70 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.195853E+11 | 26477.62 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692736E+09 | 845.90 | 16-AUG-13:00 | 44.00 | 25.56 |
September | 0.149702E+11 | 28085.15 | 04-SEP-14:01 | 41.00 | 25.01 | 0.615119E+09 | 845.63 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.115641E+11 | 25778.23 | 08-OCT-15:31 | 32.87 | 26.11 | 0.639177E+09 | 845.63 | 11-OCT-13:39 | 35.37 | 21.08 |
November | 0.721764E+10 | 22121.80 | 05-NOV-15:32 | 31.60 | 21.44 | 0.629734E+09 | 845.62 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.405013E+10 | 9949.91 | 11-DEC-06:03 | 21.90 | 19.23 | 0.595917E+09 | 845.63 | 01-DEC-14:20 | 21.90 | 19.23 |
Annual Sum or Average | 0.131866E+12 | 0.757455E+10 | ||||||||
Minimum of Months | 0.318363E+10 | 5514.39 | 21.88 | 15.43 | 0.558769E+09 | 845.62 | 21.90 | 16.66 | ||
Maximum of Months | 0.195853E+11 | 28085.15 | 42.50 | 27.61 | 0.692736E+09 | 845.90 | 44.00 | 27.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274842E+10 | 4292.22 | 24-JAN-11:00 | 24.00 | 17.69 | 0.400799E+09 | 544.97 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.340968E+10 | 11130.58 | 06-FEB-06:02 | 21.88 | 19.06 | 0.367774E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.569446E+10 | 14139.01 | 27-MAR-04:12 | 22.43 | 13.90 | 0.442913E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.802601E+10 | 21102.17 | 30-APR-10:52 | 34.00 | 21.75 | 0.395825E+09 | 545.01 | 25-APR-09:09 | 34.00 | 21.75 |
May | 0.126726E+11 | 21927.55 | 21-MAY-08:52 | 35.00 | 18.56 | 0.429513E+09 | 544.99 | 04-MAY-13:00 | 35.00 | 18.56 |
June | 0.134592E+11 | 20689.99 | 11-JUN-10:22 | 38.50 | 26.61 | 0.427980E+09 | 544.97 | 02-JUN-13:09 | 38.50 | 26.61 |
July | 0.145677E+11 | 21612.94 | 30-JUL-14:22 | 42.50 | 25.87 | 0.398496E+09 | 545.14 | 21-JUL-09:30 | 42.50 | 25.87 |
August | 0.154850E+11 | 21437.57 | 06-AUG-15:01 | 40.85 | 24.99 | 0.446624E+09 | 545.22 | 03-AUG-09:50 | 40.85 | 24.99 |
September | 0.122192E+11 | 23120.52 | 04-SEP-14:01 | 41.00 | 25.01 | 0.396706E+09 | 544.96 | 26-SEP-09:39 | 35.93 | 21.30 |
October | 0.971412E+10 | 21067.28 | 08-OCT-15:31 | 32.87 | 26.11 | 0.412412E+09 | 544.96 | 11-OCT-13:39 | 35.37 | 21.08 |
November | 0.617369E+10 | 19772.23 | 05-NOV-15:32 | 31.60 | 21.44 | 0.407219E+09 | 544.95 | 22-NOV-10:20 | 23.93 | 17.19 |
December | 0.335331E+10 | 7551.51 | 11-DEC-06:03 | 21.90 | 19.23 | 0.391143E+09 | 544.96 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.107523E+12 | 0.491741E+10 | ||||||||
Minimum of Months | 0.274842E+10 | 4292.22 | 21.88 | 13.90 | 0.367774E+09 | 544.95 | 21.90 | 17.19 | ||
Maximum of Months | 0.154850E+11 | 23120.52 | 42.50 | 26.61 | 0.446624E+09 | 545.22 | 42.50 | 26.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.702067E+10 | 15818.10 | 29-JAN-15:13 | 25.33 | 19.76 | 0.625702E+09 | 845.66 | 24-JAN-10:00 | 25.33 | 19.76 |
February | 0.754492E+10 | 28066.44 | 05-FEB-12:32 | 31.07 | 19.40 | 0.571122E+09 | 845.70 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.987604E+10 | 27868.09 | 26-MAR-12:23 | 34.50 | 17.70 | 0.686954E+09 | 845.70 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.107763E+11 | 28016.23 | 30-APR-12:12 | 37.03 | 20.80 | 0.613494E+09 | 845.71 | 25-APR-09:09 | 37.03 | 20.80 |
May | 0.154607E+11 | 29274.90 | 21-MAY-12:52 | 38.00 | 22.80 | 0.666014E+09 | 845.70 | 04-MAY-13:00 | 38.00 | 22.80 |
June | 0.164501E+11 | 27812.96 | 11-JUN-15:02 | 36.90 | 27.61 | 0.663746E+09 | 845.66 | 02-JUN-13:09 | 36.90 | 27.61 |
July | 0.186255E+11 | 29193.79 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617977E+09 | 845.71 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.208519E+11 | 29238.36 | 13-AUG-14:21 | 40.00 | 25.61 | 0.692867E+09 | 845.87 | 16-AUG-13:39 | 44.07 | 25.61 |
September | 0.184734E+11 | 32361.40 | 04-SEP-14:01 | 41.00 | 25.01 | 0.615575E+09 | 845.99 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.173320E+11 | 30305.32 | 08-OCT-14:12 | 32.93 | 26.17 | 0.640330E+09 | 846.10 | 10-OCT-13:00 | 34.50 | 20.13 |
November | 0.132549E+11 | 30353.11 | 05-NOV-12:12 | 33.80 | 18.48 | 0.632827E+09 | 845.81 | 06-NOV-14:09 | 32.83 | 20.61 |
December | 0.858006E+10 | 29351.73 | 03-DEC-12:52 | 29.80 | 17.63 | 0.610622E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.164246E+12 | 0.763723E+10 | ||||||||
Minimum of Months | 0.702067E+10 | 15818.10 | 25.33 | 17.63 | 0.571122E+09 | 845.66 | 23.00 | 17.31 | ||
Maximum of Months | 0.208519E+11 | 32361.40 | 42.50 | 27.61 | 0.692867E+09 | 846.10 | 44.07 | 27.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298827E+10 | 6689.77 | 29-JAN-15:53 | 26.00 | 20.02 | 0.395315E+09 | 544.96 | 17-JAN-14:20 | 26.00 | 20.02 |
February | 0.379746E+10 | 16942.92 | 05-FEB-16:33 | 31.33 | 18.61 | 0.365593E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.639198E+10 | 19031.82 | 27-MAR-04:12 | 22.43 | 13.90 | 0.443261E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.837922E+10 | 23827.06 | 30-APR-16:11 | 31.33 | 25.55 | 0.396076E+09 | 545.00 | 25-APR-09:09 | 31.33 | 25.55 |
May | 0.127930E+11 | 26033.88 | 28-MAY-15:11 | 35.07 | 23.32 | 0.429592E+09 | 544.99 | 04-MAY-13:00 | 35.07 | 23.32 |
June | 0.140154E+11 | 24482.60 | 11-JUN-16:22 | 36.70 | 26.39 | 0.428085E+09 | 544.97 | 02-JUN-13:09 | 36.70 | 26.39 |
July | 0.151832E+11 | 25177.68 | 30-JUL-15:02 | 40.45 | 27.73 | 0.398537E+09 | 545.00 | 03-JUL-09:09 | 40.45 | 27.73 |
August | 0.164411E+11 | 25728.47 | 06-AUG-15:41 | 40.25 | 25.55 | 0.446722E+09 | 544.94 | 15-AUG-13:20 | 39.87 | 23.44 |
September | 0.126538E+11 | 27422.56 | 04-SEP-15:21 | 40.85 | 24.13 | 0.396803E+09 | 544.95 | 26-SEP-09:20 | 34.97 | 20.80 |
October | 0.101241E+11 | 25579.36 | 08-OCT-15:31 | 32.87 | 26.11 | 0.412524E+09 | 544.96 | 11-OCT-13:39 | 35.37 | 21.08 |
November | 0.667587E+10 | 24310.74 | 05-NOV-15:32 | 31.60 | 21.44 | 0.407269E+09 | 544.95 | 16-NOV-14:00 | 30.00 | 19.03 |
December | 0.390926E+10 | 10260.99 | 11-DEC-06:03 | 21.90 | 19.23 | 0.390511E+09 | 544.96 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.113353E+12 | 0.491029E+10 | ||||||||
Minimum of Months | 0.298827E+10 | 6689.77 | 21.90 | 13.90 | 0.365593E+09 | 544.94 | 23.00 | 17.31 | ||
Maximum of Months | 0.164411E+11 | 27422.56 | 40.85 | 27.73 | 0.446722E+09 | 545.00 | 40.45 | 27.73 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493209E+10 | 9349.14 | 30-JAN-06:15 | 20.07 | 17.42 | 0.00 | 0.00 | 01-JAN-00:10 | 20.07 | 17.42 |
February | 0.585185E+10 | 10341.98 | 06-FEB-06:15 | 21.77 | 18.83 | 0.00 | 0.00 | 01-FEB-00:10 | 21.77 | 18.83 |
March | 0.895689E+10 | 11466.92 | 27-MAR-16:00 | 35.00 | 18.85 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.85 |
April | 0.112885E+11 | 12563.46 | 10-APR-05:15 | 22.70 | 19.47 | 0.00 | 0.00 | 01-APR-00:10 | 22.70 | 19.47 |
May | 0.154208E+11 | 19369.94 | 30-MAY-05:15 | 27.00 | 24.83 | 0.00 | 0.00 | 01-MAY-00:10 | 27.00 | 24.83 |
June | 0.174287E+11 | 16831.34 | 12-JUN-05:25 | 29.25 | 23.98 | 0.00 | 0.00 | 01-JUN-00:10 | 29.25 | 23.98 |
July | 0.199110E+11 | 21517.19 | 24-JUL-05:15 | 32.67 | 27.85 | 0.00 | 0.00 | 01-JUL-00:10 | 32.67 | 27.85 |
August | 0.234637E+11 | 24589.81 | 07-AUG-05:13 | 32.63 | 23.12 | 0.00 | 0.00 | 01-AUG-00:10 | 32.63 | 23.12 |
September | 0.162962E+11 | 23564.45 | 05-SEP-05:15 | 30.33 | 24.49 | 0.00 | 0.00 | 01-SEP-00:10 | 30.33 | 24.49 |
October | 0.143170E+11 | 20156.53 | 10-OCT-05:15 | 26.67 | 24.04 | 0.00 | 0.00 | 01-OCT-00:10 | 26.67 | 24.04 |
November | 0.106201E+11 | 14643.04 | 06-NOV-06:13 | 20.03 | 17.51 | 0.00 | 0.00 | 01-NOV-00:10 | 20.03 | 17.51 |
December | 0.720869E+10 | 10139.96 | 26-DEC-06:13 | 14.60 | 14.60 | 0.00 | 0.00 | 01-DEC-00:10 | 14.60 | 14.60 |
Annual Sum or Average | 0.155695E+12 | 0.00 | ||||||||
Minimum of Months | 0.493209E+10 | 9349.14 | 14.60 | 14.60 | 0.00 | 0.00 | 14.60 | 14.60 | ||
Maximum of Months | 0.234637E+11 | 24589.81 | 35.00 | 27.85 | 0.00 | 0.00 | 35.00 | 27.85 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270623E+10 | 4503.59 | 30-JAN-06:15 | 20.07 | 17.42 | 0.00 | 0.00 | 01-JAN-00:10 | 20.07 | 17.42 |
February | 0.361161E+10 | 6847.97 | 06-FEB-15:30 | 31.95 | 17.43 | 0.00 | 0.00 | 01-FEB-00:10 | 31.95 | 17.43 |
March | 0.635426E+10 | 9914.27 | 27-MAR-16:00 | 35.00 | 18.85 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.85 |
April | 0.853365E+10 | 10720.04 | 24-APR-05:02 | 21.83 | 13.96 | 0.00 | 0.00 | 01-APR-00:10 | 21.83 | 13.96 |
May | 0.138748E+11 | 13804.25 | 22-MAY-05:02 | 27.90 | 21.10 | 0.00 | 0.00 | 01-MAY-00:10 | 27.90 | 21.10 |
June | 0.154890E+11 | 14157.79 | 05-JUN-05:02 | 29.00 | 23.92 | 0.00 | 0.00 | 01-JUN-00:10 | 29.00 | 23.92 |
July | 0.174331E+11 | 19106.06 | 24-JUL-05:15 | 32.67 | 27.85 | 0.00 | 0.00 | 01-JUL-00:10 | 32.67 | 27.85 |
August | 0.191561E+11 | 22090.11 | 07-AUG-05:13 | 32.63 | 23.12 | 0.00 | 0.00 | 01-AUG-00:10 | 32.63 | 23.12 |
September | 0.146270E+11 | 20062.66 | 05-SEP-05:15 | 30.33 | 24.49 | 0.00 | 0.00 | 01-SEP-00:10 | 30.33 | 24.49 |
October | 0.120788E+11 | 13977.16 | 10-OCT-05:02 | 26.83 | 24.08 | 0.00 | 0.00 | 01-OCT-00:10 | 26.83 | 24.08 |
November | 0.814295E+10 | 10916.50 | 13-NOV-06:02 | 20.92 | 17.72 | 0.00 | 0.00 | 01-NOV-00:10 | 20.92 | 17.72 |
December | 0.416449E+10 | 6362.86 | 04-DEC-15:30 | 26.60 | 21.10 | 0.00 | 0.00 | 01-DEC-00:10 | 26.60 | 21.10 |
Annual Sum or Average | 0.126172E+12 | 0.00 | ||||||||
Minimum of Months | 0.270623E+10 | 4503.59 | 20.07 | 13.96 | 0.00 | 0.00 | 20.07 | 13.96 | ||
Maximum of Months | 0.191561E+11 | 22090.11 | 35.00 | 27.85 | 0.00 | 0.00 | 35.00 | 27.85 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.314143E+10 | 8600.21 | 23-JAN-14:10 | 27.50 | 16.66 | 0.00 | 0.00 | 01-JAN-00:10 | 27.50 | 16.66 |
February | 0.473254E+10 | 13793.96 | 06-FEB-15:00 | 32.50 | 17.28 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 17.28 |
March | 0.865188E+10 | 19436.81 | 27-MAR-14:30 | 35.00 | 19.13 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 19.13 |
April | 0.124153E+11 | 21624.52 | 28-APR-12:45 | 37.58 | 22.61 | 0.00 | 0.00 | 01-APR-00:10 | 37.58 | 22.61 |
May | 0.210291E+11 | 24395.27 | 10-MAY-14:40 | 40.00 | 20.07 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.07 |
June | 0.236354E+11 | 25435.58 | 09-JUN-15:00 | 42.00 | 24.89 | 0.00 | 0.00 | 01-JUN-00:10 | 42.00 | 24.89 |
July | 0.268960E+11 | 27756.28 | 21-JUL-13:05 | 42.25 | 27.34 | 0.00 | 0.00 | 01-JUL-00:10 | 42.25 | 27.34 |
August | 0.287552E+11 | 28101.39 | 16-AUG-13:50 | 44.03 | 25.58 | 0.00 | 0.00 | 01-AUG-00:10 | 44.03 | 25.58 |
September | 0.211774E+11 | 26475.98 | 04-SEP-15:21 | 40.85 | 24.13 | 0.00 | 0.00 | 01-SEP-00:10 | 40.85 | 24.13 |
October | 0.159800E+11 | 20182.55 | 05-OCT-14:40 | 36.00 | 22.65 | 0.00 | 0.00 | 01-OCT-00:10 | 36.00 | 22.65 |
November | 0.958395E+10 | 16014.89 | 01-NOV-14:00 | 33.00 | 26.24 | 0.00 | 0.00 | 01-NOV-00:10 | 33.00 | 26.24 |
December | 0.451705E+10 | 11035.16 | 04-DEC-14:05 | 27.00 | 21.00 | 0.00 | 0.00 | 01-DEC-00:10 | 27.00 | 21.00 |
Annual Sum or Average | 0.180515E+12 | 0.00 | ||||||||
Minimum of Months | 0.314143E+10 | 8600.21 | 27.00 | 16.66 | 0.00 | 0.00 | 27.00 | 16.66 | ||
Maximum of Months | 0.287552E+11 | 28101.39 | 44.03 | 27.34 | 0.00 | 0.00 | 44.03 | 27.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.429216E+10 | 1900.51 | 29-JAN-17:40 | 24.33 | 19.64 | 95238717.90 | 126.85 | 17-JAN-14:00 | 24.33 | 19.64 |
February | 0.858692E+10 | 3850.24 | 05-FEB-17:17 | 31.00 | 18.60 | 86408774.32 | 126.85 | 09-FEB-10:09 | 23.92 | 19.44 |
March | 0.146339E+11 | 7206.49 | 31-MAR-23:50 | 22.37 | 20.31 | 0.103244E+09 | 126.85 | 29-MAR-09:09 | 22.37 | 20.31 |
April | 0.191867E+11 | 7834.61 | 23-APR-18:10 | 29.83 | 19.17 | 92502085.25 | 144.56 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.481521E+10 | 3602.80 | 31-MAY-23:57 | 32.70 | 23.39 | 99239134.21 | 126.85 | 17-MAY-13:09 | 32.70 | 23.39 |
June | 0.960014E+10 | 5438.38 | 30-JUN-24:00 | 31.70 | 26.86 | 98978404.14 | 126.88 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.151124E+11 | 7245.16 | 31-JUL-23:57 | 33.30 | 28.31 | 91890218.67 | 126.84 | 26-JUL-09:09 | 33.30 | 28.31 |
August | 0.195240E+11 | 7671.38 | 15-AUG-04:03 | 29.75 | 23.27 | 0.118643E+09 | 158.31 | 10-AUG-13:00 | 29.75 | 23.27 |
September | 0.473627E+10 | 3545.27 | 30-SEP-24:00 | 29.00 | 26.44 | 91606817.10 | 126.85 | 25-SEP-13:50 | 29.00 | 26.44 |
October | 0.983904E+10 | 5404.22 | 31-OCT-24:00 | 27.40 | 21.22 | 95250879.76 | 126.88 | 17-OCT-09:09 | 27.40 | 21.22 |
November | 0.142778E+11 | 5941.63 | 12-NOV-16:53 | 29.00 | 17.88 | 94310696.10 | 126.85 | 01-NOV-09:09 | 29.00 | 17.88 |
December | 0.196444E+11 | 7706.11 | 25-DEC-16:55 | 24.00 | 19.34 | 91883582.89 | 126.83 | 15-DEC-10:09 | 24.00 | 19.34 |
Annual Sum or Average | 0.144249E+12 | 0.115920E+10 | ||||||||
Minimum of Months | 0.429216E+10 | 1900.51 | 22.37 | 17.88 | 86408774.32 | 126.83 | 22.37 | 17.88 | ||
Maximum of Months | 0.196444E+11 | 7834.61 | 33.30 | 28.31 | 0.118643E+09 | 158.31 | 37.33 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344652E+10 | 1709.80 | 31-JAN-17:00 | 23.00 | 17.31 | 95234369.54 | 126.84 | 31-JAN-14:00 | 23.00 | 17.31 |
February | 0.776753E+10 | 3581.47 | 06-FEB-16:10 | 30.50 | 18.50 | 86408063.35 | 126.85 | 09-FEB-10:09 | 23.92 | 19.44 |
March | 0.137830E+11 | 6934.80 | 31-MAR-23:55 | 22.30 | 20.22 | 0.103244E+09 | 126.84 | 02-MAR-14:00 | 22.30 | 20.22 |
April | 0.182078E+11 | 7380.80 | 23-APR-17:44 | 30.17 | 19.07 | 92385563.34 | 143.23 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.449330E+10 | 3473.89 | 31-MAY-23:57 | 32.70 | 23.39 | 99237570.77 | 126.85 | 11-MAY-13:00 | 32.70 | 23.39 |
June | 0.908520E+10 | 5227.87 | 30-JUN-24:00 | 31.70 | 26.86 | 98978479.50 | 126.87 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.143115E+11 | 6916.48 | 31-JUL-23:42 | 33.37 | 28.37 | 91891388.84 | 126.85 | 18-JUL-09:09 | 33.37 | 28.37 |
August | 0.183936E+11 | 7168.88 | 14-AUG-03:23 | 31.00 | 24.29 | 0.115806E+09 | 154.34 | 10-AUG-13:00 | 31.00 | 24.29 |
September | 0.437321E+10 | 3409.72 | 30-SEP-23:40 | 29.00 | 26.39 | 91606095.85 | 126.85 | 05-SEP-13:00 | 29.00 | 26.39 |
October | 0.929538E+10 | 5230.00 | 31-OCT-24:00 | 27.40 | 21.22 | 95250128.24 | 126.87 | 06-OCT-09:09 | 27.40 | 21.22 |
November | 0.135062E+11 | 5536.60 | 12-NOV-17:02 | 28.83 | 17.83 | 94310809.03 | 126.84 | 01-NOV-09:09 | 28.83 | 17.83 |
December | 0.183711E+11 | 7202.34 | 04-DEC-17:00 | 26.00 | 20.50 | 91883757.43 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.135034E+12 | 0.115624E+10 | ||||||||
Minimum of Months | 0.344652E+10 | 1709.80 | 22.30 | 17.31 | 86408063.35 | 126.83 | 19.67 | 17.31 | ||
Maximum of Months | 0.183936E+11 | 7380.80 | 33.37 | 28.37 | 0.115806E+09 | 154.34 | 37.33 | 28.37 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297448E+10 | 1735.84 | 31-JAN-17:00 | 23.00 | 17.31 | 95233917.17 | 126.84 | 31-JAN-14:00 | 23.00 | 17.31 |
February | 0.751194E+10 | 3660.10 | 05-FEB-17:23 | 31.00 | 18.68 | 86408241.61 | 126.85 | 07-FEB-14:00 | 28.00 | 22.41 |
March | 0.136599E+11 | 6880.83 | 31-MAR-23:55 | 22.30 | 20.22 | 0.103244E+09 | 126.85 | 02-MAR-14:00 | 22.30 | 20.22 |
April | 0.182275E+11 | 7574.02 | 02-APR-16:22 | 30.20 | 18.30 | 92367968.57 | 143.89 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.462822E+10 | 3530.15 | 31-MAY-23:57 | 32.70 | 23.39 | 99238481.04 | 126.85 | 17-MAY-13:09 | 32.70 | 23.39 |
June | 0.922703E+10 | 5243.40 | 30-JUN-24:00 | 31.70 | 26.86 | 98978472.57 | 126.87 | 08-JUN-13:09 | 31.70 | 26.86 |
July | 0.145318E+11 | 6976.26 | 31-JUL-23:42 | 33.37 | 28.37 | 91891098.11 | 126.85 | 18-JUL-09:09 | 33.37 | 28.37 |
August | 0.185783E+11 | 7269.31 | 14-AUG-03:01 | 31.00 | 24.41 | 0.115817E+09 | 155.85 | 10-AUG-13:00 | 31.00 | 24.41 |
September | 0.450239E+10 | 3449.16 | 30-SEP-24:00 | 29.00 | 26.44 | 91606472.68 | 126.85 | 25-SEP-13:09 | 29.00 | 26.44 |
October | 0.935776E+10 | 5226.51 | 31-OCT-24:00 | 27.40 | 21.22 | 95250405.30 | 126.87 | 17-OCT-13:09 | 27.40 | 21.22 |
November | 0.134331E+11 | 5696.01 | 05-NOV-17:05 | 30.83 | 21.62 | 94311046.06 | 126.84 | 01-NOV-09:09 | 30.83 | 21.62 |
December | 0.180789E+11 | 7224.54 | 06-DEC-17:00 | 26.00 | 20.50 | 91884068.93 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.134711E+12 | 0.115623E+10 | ||||||||
Minimum of Months | 0.297448E+10 | 1735.84 | 22.30 | 17.31 | 86408241.61 | 126.83 | 19.67 | 17.31 | ||
Maximum of Months | 0.185783E+11 | 7574.02 | 33.37 | 28.37 | 0.115817E+09 | 155.85 | 37.33 | 28.37 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243312E+12 | 93459.62 | 02-JAN-17:00 | 21.00 | 13.15 | 0.206200E+10 | 2747.72 | 20-JAN-10:09 | 17.42 | 12.06 |
February | 0.439771E+12 | 184499.45 | 06-FEB-17:00 | 26.00 | 21.11 | 0.187065E+10 | 2746.69 | 13-FEB-10:09 | 19.50 | 13.91 |
March | 0.731500E+12 | 359448.86 | 31-MAR-23:55 | 22.30 | 20.22 | 0.223503E+10 | 2745.97 | 16-MAR-09:09 | 22.30 | 20.22 |
April | 0.939203E+12 | 369419.76 | 30-APR-03:07 | 21.82 | 21.19 | 0.225900E+10 | 4111.74 | 28-APR-12:20 | 21.82 | 21.19 |
May | 0.243158E+12 | 176743.09 | 31-MAY-23:57 | 32.70 | 23.39 | 0.214869E+10 | 2747.14 | 30-MAY-09:09 | 32.70 | 23.39 |
June | 0.472233E+12 | 268328.29 | 30-JUN-24:00 | 31.70 | 26.86 | 0.214268E+10 | 2746.76 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.734818E+12 | 353299.68 | 31-JUL-23:23 | 33.50 | 28.49 | 0.198916E+10 | 2745.85 | 26-JUL-09:09 | 33.50 | 28.49 |
August | 0.960753E+12 | 366877.63 | 15-AUG-07:10 | 29.58 | 21.34 | 0.330491E+10 | 4632.53 | 16-AUG-13:00 | 44.00 | 25.56 |
September | 0.239595E+12 | 177559.45 | 30-SEP-24:00 | 29.00 | 26.44 | 0.198368E+10 | 2747.23 | 22-SEP-09:09 | 29.00 | 26.44 |
October | 0.491663E+12 | 269845.39 | 31-OCT-24:00 | 27.40 | 21.22 | 0.206197E+10 | 2746.66 | 17-OCT-09:09 | 27.40 | 21.22 |
November | 0.712916E+12 | 277817.20 | 13-NOV-17:00 | 29.00 | 22.60 | 0.204154E+10 | 2745.80 | 01-NOV-09:09 | 29.00 | 22.60 |
December | 0.980101E+12 | 369187.02 | 06-DEC-22:02 | 22.25 | 18.77 | 0.203311E+10 | 3076.32 | 04-DEC-14:00 | 22.25 | 18.77 |
Annual Sum or Average | 0.718902E+13 | 0.261324E+11 | ||||||||
Minimum of Months | 0.239595E+12 | 93459.62 | 21.00 | 13.15 | 0.187065E+10 | 2745.80 | 17.42 | 12.06 | ||
Maximum of Months | 0.980101E+12 | 369419.76 | 33.50 | 28.49 | 0.330491E+10 | 4632.53 | 44.00 | 28.49 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120397E+09 | 8262.44 | 16-JAN-12:57 | 25.60 |
February | 0.128526E+09 | 17800.80 | 05-FEB-16:10 | 31.83 |
March | 0.176296E+09 | 15938.26 | 02-MAR-05:05 | 29.08 |
April | 0.416438E+09 | 24618.72 | 29-APR-16:01 | 35.33 |
May | 0.619837E+09 | 25524.75 | 20-MAY-16:01 | 36.17 |
June | 0.645546E+09 | 27071.60 | 03-JUN-16:01 | 37.08 |
July | 0.883546E+09 | 34803.06 | 30-JUL-11:33 | 43.67 |
August | 0.619963E+09 | 31506.67 | 05-AUG-16:01 | 40.08 |
September | 0.745764E+09 | 29845.08 | 04-SEP-16:12 | 40.47 |
October | 0.712423E+09 | 22906.32 | 07-OCT-16:01 | 34.33 |
November | 0.444112E+09 | 20537.64 | 05-NOV-11:53 | 34.00 |
December | 0.268110E+09 | 16691.90 | 03-DEC-12:42 | 29.50 |
Annual Sum or Average | 0.578096E+10 | |||
Minimum of Months | 0.120397E+09 | 8262.44 | 25.60 | |
Maximum of Months | 0.883546E+09 | 34803.06 | 43.67 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 206862.58 | 514.42 | 02-JAN-06:03 | 13.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 206862.58 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 206862.58 | 514.42 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 59381.07 | 126.30 | 02-JAN-06:03 | 13.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 59381.07 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 59381.07 | 126.30 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82480004.28 | 8848.81 | 23-JAN-05:11 | 18.67 |
February | 78561569.45 | 9794.01 | 21-FEB-05:11 | 14.67 |
March | 68204532.59 | 10668.25 | 06-MAR-05:12 | 16.67 |
April | 52117137.15 | 7032.88 | 02-APR-14:02 | 33.83 |
May | 26491402.87 | 5168.04 | 07-MAY-14:32 | 37.00 |
June | 24025967.05 | 4953.49 | 04-JUN-13:41 | 37.92 |
July | 36346924.84 | 5785.97 | 30-JUL-11:02 | 44.67 |
August | 39523347.07 | 5214.98 | 27-AUG-11:02 | 37.83 |
September | 26098922.21 | 4678.63 | 10-SEP-14:21 | 35.00 |
October | 38079680.61 | 5328.96 | 01-OCT-13:52 | 35.00 |
November | 67947369.85 | 8121.34 | 30-NOV-05:12 | 19.67 |
December | 0.133132E+09 | 11326.55 | 18-DEC-05:11 | 13.00 |
Annual Sum or Average | 0.673009E+09 | |||
Minimum of Months | 24025967.05 | 4678.63 | 13.00 | |
Maximum of Months | 0.133132E+09 | 11326.55 | 44.67 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 46357822.82 | 6973.16 | 02-JAN-05:11 | 13.67 |
February | 42572850.99 | 7538.15 | 21-FEB-05:11 | 14.67 |
March | 33692542.89 | 7303.54 | 26-MAR-14:52 | 32.60 |
April | 38395821.13 | 7197.18 | 02-APR-14:31 | 33.33 |
May | 35799758.73 | 5986.58 | 07-MAY-13:52 | 37.00 |
June | 28578238.22 | 5407.84 | 18-JUN-15:22 | 36.05 |
July | 42479257.55 | 6489.63 | 30-JUL-11:02 | 44.67 |
August | 27751765.04 | 5775.48 | 27-AUG-14:22 | 37.00 |
September | 34957676.92 | 6712.55 | 17-SEP-13:32 | 36.87 |
October | 42925810.19 | 6330.73 | 01-OCT-14:01 | 34.83 |
November | 39464432.20 | 5157.93 | 05-NOV-14:41 | 32.17 |
December | 42029257.20 | 6013.51 | 18-DEC-06:02 | 13.17 |
Annual Sum or Average | 0.455005E+09 | |||
Minimum of Months | 27751765.04 | 5157.93 | 13.17 | |
Maximum of Months | 46357822.82 | 7538.15 | 44.67 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.646355E+09 | 14272.29 | 13-JAN-06:02 | 13.93 |
February | 0.373053E+09 | 14570.51 | 01-FEB-06:03 | 13.02 |
March | 0.220350E+09 | 14006.06 | 06-MAR-06:02 | 15.97 |
April | 65226086.97 | 12036.68 | 05-APR-05:02 | 17.00 |
May | 10167222.48 | 8036.00 | 02-MAY-04:12 | 22.87 |
June | 669016.33 | 2264.04 | 20-JUN-03:02 | 27.88 |
July | 327181.61 | 1158.53 | 30-JUL-08:22 | 36.90 |
August | 12783.93 | 106.53 | 27-AUG-09:02 | 35.25 |
September | 3783725.08 | 3825.41 | 30-SEP-03:02 | 26.62 |
October | 18855694.65 | 10725.09 | 30-OCT-04:11 | 22.40 |
November | 73112260.68 | 12010.46 | 22-NOV-06:03 | 16.98 |
December | 0.370991E+09 | 14501.98 | 28-DEC-06:03 | 14.95 |
Annual Sum or Average | 0.178290E+10 | |||
Minimum of Months | 12783.93 | 106.53 | 13.02 | |
Maximum of Months | 0.646355E+09 | 14570.51 | 36.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:05 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138227E+11 | 14744.03 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.125395E+11 | 14744.03 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.149226E+11 | 14744.03 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.133065E+11 | 14744.03 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.143726E+11 | 14744.03 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.143114E+11 | 14744.03 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.133677E+11 | 14744.03 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.149224E+11 | 14744.03 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.133065E+11 | 14744.03 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.138228E+11 | 14744.03 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.136668E+11 | 14744.03 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.133678E+11 | 14744.03 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.165729E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.125395E+11 | 14744.03 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.149226E+11 | 14744.03 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124138E+11 | 13241.18 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.112614E+11 | 13241.18 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.134015E+11 | 13241.18 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.119501E+11 | 13241.18 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.129076E+11 | 13241.18 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.128527E+11 | 13241.18 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.120051E+11 | 13241.18 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.134014E+11 | 13241.18 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.119501E+11 | 13241.18 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.124139E+11 | 13241.18 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.122737E+11 | 13241.18 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.120052E+11 | 13241.18 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.148837E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.112614E+11 | 13241.18 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.134015E+11 | 13241.18 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.933590E+09 | 1238.63 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.819018E+09 | 1276.00 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.950450E+09 | 1494.55 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.827557E+09 | 1229.48 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.869102E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.856744E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.814146E+09 | 923.62 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.912899E+09 | 870.17 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.833294E+09 | 892.88 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.888312E+09 | 1102.95 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.911821E+09 | 1387.48 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.915503E+09 | 1425.05 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.105324E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.814146E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.950450E+09 | 1494.55 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.594899E+09 | 839.76 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.525423E+09 | 841.46 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.610093E+09 | 949.09 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.533221E+09 | 719.94 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.563352E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.555924E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.526790E+09 | 573.74 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.589462E+09 | 509.78 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.536606E+09 | 509.78 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.568312E+09 | 552.37 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.585418E+09 | 919.61 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.583138E+09 | 930.96 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.677264E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.525423E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.610093E+09 | 949.09 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.904139E+09 | 1093.21 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.804415E+09 | 1207.59 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.944747E+09 | 1491.19 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.829231E+09 | 1238.10 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.877305E+09 | 844.67 | 23-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.865491E+09 | 860.31 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.820966E+09 | 1086.98 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.916749E+09 | 864.26 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.832132E+09 | 888.58 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.878157E+09 | 882.27 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.886496E+09 | 1203.88 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.880983E+09 | 1333.08 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104408E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.804415E+09 | 844.67 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.944747E+09 | 1491.19 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.590340E+09 | 794.30 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.521946E+09 | 753.00 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.613543E+09 | 969.29 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.535867E+09 | 831.29 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.564862E+09 | 575.15 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.556075E+09 | 577.69 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.529213E+09 | 749.03 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.591615E+09 | 595.30 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.537857E+09 | 704.14 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.571952E+09 | 770.56 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.575642E+09 | 772.88 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.574792E+09 | 887.77 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.676370E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.521946E+09 | 575.15 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.613543E+09 | 969.29 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.931091E+09 | 1231.93 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.817108E+09 | 1271.19 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.949108E+09 | 1492.64 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.826780E+09 | 1224.14 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.868687E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.855728E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.813663E+09 | 918.07 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.912338E+09 | 861.58 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.832388E+09 | 885.59 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.886960E+09 | 1093.74 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.909834E+09 | 1383.60 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.912899E+09 | 1422.04 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.105166E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.813663E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.949108E+09 | 1492.64 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.593631E+09 | 833.97 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.524591E+09 | 835.41 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.609263E+09 | 946.31 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.532801E+09 | 713.38 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.562980E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.555529E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.526451E+09 | 569.85 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.589039E+09 | 509.78 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.536222E+09 | 509.78 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.567834E+09 | 546.66 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.584583E+09 | 915.69 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.582008E+09 | 927.32 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.676493E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.524591E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.609263E+09 | 946.31 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.903638E+09 | 1087.04 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.803834E+09 | 1202.43 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.943834E+09 | 1489.26 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.828484E+09 | 1232.82 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.876667E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.864762E+09 | 850.96 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.820152E+09 | 1079.08 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.916051E+09 | 855.38 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.831355E+09 | 881.07 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.876997E+09 | 873.60 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.886065E+09 | 1198.15 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.880438E+09 | 1329.14 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104323E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.803834E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.943834E+09 | 1489.26 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.589394E+09 | 787.08 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.521089E+09 | 744.57 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.612518E+09 | 966.61 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.534907E+09 | 824.93 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.564164E+09 | 570.42 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.555398E+09 | 573.12 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.528430E+09 | 740.45 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.590966E+09 | 591.77 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.537314E+09 | 693.86 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.571284E+09 | 763.66 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.574982E+09 | 766.20 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.573641E+09 | 882.98 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.675409E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.521089E+09 | 570.42 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.612518E+09 | 966.61 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.930973E+09 | 1231.27 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.817006E+09 | 1270.41 | 09-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.949033E+09 | 1492.29 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.826756E+09 | 1223.27 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.868674E+09 | 791.05 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.855711E+09 | 791.05 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.813639E+09 | 917.85 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.912305E+09 | 861.26 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.832363E+09 | 885.31 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.886900E+09 | 1092.97 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.909784E+09 | 1383.13 | 29-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.912827E+09 | 1421.59 | 15-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.105160E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.813639E+09 | 791.05 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.949033E+09 | 1492.29 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.593603E+09 | 833.61 | 04-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.524567E+09 | 834.95 | 09-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.609241E+09 | 946.07 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.532787E+09 | 712.74 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.562953E+09 | 509.78 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.555516E+09 | 509.78 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.526434E+09 | 569.66 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.589005E+09 | 509.78 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.536209E+09 | 509.78 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.567795E+09 | 546.49 | 27-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.584560E+09 | 915.42 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.581927E+09 | 927.04 | 14-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.676460E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.524567E+09 | 509.78 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.609241E+09 | 946.07 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.903623E+09 | 1086.03 | 23-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.803808E+09 | 1201.56 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.943796E+09 | 1488.90 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.828458E+09 | 1231.97 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.876625E+09 | 791.06 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.864724E+09 | 850.61 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.820122E+09 | 1077.95 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.916015E+09 | 855.03 | 29-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.831324E+09 | 880.78 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.876982E+09 | 873.32 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.886055E+09 | 1197.50 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.880419E+09 | 1328.60 | 15-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.104319E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.803808E+09 | 791.06 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.943796E+09 | 1488.90 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.589349E+09 | 786.53 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.521068E+09 | 743.95 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.612583E+09 | 966.40 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.534888E+09 | 824.44 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.564149E+09 | 570.26 | 23-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.555362E+09 | 572.96 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.528402E+09 | 739.80 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.590930E+09 | 591.64 | 29-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.537268E+09 | 693.20 | 06-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.571264E+09 | 763.26 | 31-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.574970E+09 | 765.83 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.573570E+09 | 882.60 | 15-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.675380E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.521068E+09 | 570.26 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.612583E+09 | 966.40 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.302573E+09 | 316.63 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.274456E+09 | 316.63 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.326130E+09 | 316.63 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.291301E+09 | 316.63 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.314351E+09 | 316.63 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.312831E+09 | 316.63 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.292821E+09 | 316.63 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.326130E+09 | 316.63 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.291301E+09 | 316.63 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.302573E+09 | 316.63 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.299026E+09 | 316.63 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.292821E+09 | 316.63 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.362631E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.274456E+09 | 316.63 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.326130E+09 | 316.63 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.397259E+10 | 4157.19 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.360343E+10 | 4157.19 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.428189E+10 | 4157.19 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.382459E+10 | 4157.19 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.412724E+10 | 4157.19 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.410728E+10 | 4157.19 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.384455E+10 | 4157.19 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.428189E+10 | 4157.19 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.382459E+10 | 4157.19 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.397259E+10 | 4157.19 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.392603E+10 | 4157.19 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.384455E+10 | 4157.19 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.476112E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.360343E+10 | 4157.19 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.428189E+10 | 4157.19 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.138227E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.143726E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.143114E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.133677E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.149224E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.133065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.138228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.136668E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.133678E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.165729E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.125395E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.149226E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.124138E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.119501E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.129076E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.128527E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.120051E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.134014E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.119501E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.124139E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.122737E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.120052E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.148837E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.112614E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.134015E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.933590E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1298275.46 | 0.148725E+09 |
February | 0.136985E+10 | 0.819018E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12931727.01 | 0.147789E+09 |
March | 0.163685E+10 | 0.950450E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34395733.83 | 77463541.91 |
April | 0.145243E+10 | 0.827557E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81249113.33 | 29124731.16 |
May | 0.157338E+10 | 0.869102E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204529E+09 | 2357404.33 |
June | 0.156900E+10 | 0.856744E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255435E+09 | 112718.83 |
July | 0.145680E+10 | 0.814146E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356835E+09 | 0.00 |
August | 0.163685E+10 | 0.912899E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338647E+09 | 0.00 |
September | 0.145243E+10 | 0.833294E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247319E+09 | 252529.71 |
October | 0.150991E+10 | 0.888312E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142289E+09 | 3149621.54 |
November | 0.149516E+10 | 0.911821E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57343947.45 | 33396334.34 |
December | 0.145680E+10 | 0.915503E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8305401.45 | 0.107326E+09 |
Annual Sum or Average | 0.181194E+11 | 0.105324E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174058E+10 | 0.549696E+09 |
Minimum of Months | 0.136985E+10 | 0.814146E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1298275.46 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.950450E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356835E+09 | 0.148725E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.594899E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 570880.89 | 0.101896E+09 |
February | 0.882782E+09 | 0.525423E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7986825.81 | 98605279.97 |
March | 0.105485E+10 | 0.610093E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22839328.48 | 50395505.49 |
April | 0.936002E+09 | 0.533221E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53569046.87 | 18267987.98 |
May | 0.101394E+10 | 0.563352E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134892E+09 | 1627321.49 |
June | 0.101113E+10 | 0.555924E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170327E+09 | 86887.82 |
July | 0.938820E+09 | 0.526790E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238057E+09 | 0.00 |
August | 0.105485E+10 | 0.589462E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226745E+09 | 0.00 |
September | 0.936002E+09 | 0.536606E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163056E+09 | 185271.69 |
October | 0.973041E+09 | 0.568312E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93561236.98 | 2171247.95 |
November | 0.963541E+09 | 0.585418E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37089268.80 | 21989438.21 |
December | 0.938820E+09 | 0.583138E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5478459.89 | 68132536.93 |
Annual Sum or Average | 0.116768E+11 | 0.677264E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115417E+10 | 0.363357E+09 |
Minimum of Months | 0.882782E+09 | 0.525423E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 570880.89 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.610093E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238057E+09 | 0.101896E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.904139E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 733857.75 | 0.165429E+09 |
February | 0.136988E+10 | 0.804415E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11368986.14 | 0.160401E+09 |
March | 0.163688E+10 | 0.944747E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32926194.50 | 84143694.04 |
April | 0.145246E+10 | 0.829231E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78953343.21 | 30912561.95 |
May | 0.157341E+10 | 0.877305E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204397E+09 | 2425749.75 |
June | 0.156904E+10 | 0.865491E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256796E+09 | 93076.04 |
July | 0.145684E+10 | 0.820966E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357582E+09 | 0.00 |
August | 0.163688E+10 | 0.916749E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338183E+09 | 0.00 |
September | 0.145246E+10 | 0.832132E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242212E+09 | 325817.26 |
October | 0.150994E+10 | 0.878157E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134305E+09 | 4721271.80 |
November | 0.149520E+10 | 0.886496E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50156155.86 | 40446765.43 |
December | 0.145684E+10 | 0.880983E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6717826.70 | 0.119481E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104408E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171433E+10 | 0.608380E+09 |
Minimum of Months | 0.136988E+10 | 0.804415E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 733857.75 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.944747E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357582E+09 | 0.165429E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.590340E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530044.04 | 0.116063E+09 |
February | 0.882782E+09 | 0.521946E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7683898.99 | 0.121467E+09 |
March | 0.105485E+10 | 0.613543E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21072128.58 | 71730909.27 |
April | 0.936002E+09 | 0.535867E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49666248.51 | 32240132.03 |
May | 0.101394E+10 | 0.564862E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130547E+09 | 2738361.04 |
June | 0.101113E+10 | 0.556075E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163798E+09 | 230126.62 |
July | 0.938820E+09 | 0.529213E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231691E+09 | 0.00 |
August | 0.105485E+10 | 0.591615E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219629E+09 | 0.00 |
September | 0.936002E+09 | 0.537857E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156740E+09 | 347394.41 |
October | 0.973041E+09 | 0.571952E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86141410.28 | 4880312.24 |
November | 0.963541E+09 | 0.575642E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32535363.81 | 35100996.26 |
December | 0.938820E+09 | 0.574792E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4387056.41 | 97055860.43 |
Annual Sum or Average | 0.116768E+11 | 0.676370E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110442E+10 | 0.481854E+09 |
Minimum of Months | 0.882782E+09 | 0.521946E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530044.04 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.613543E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231691E+09 | 0.121467E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.931091E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5585409.87 | 0.292557E+09 |
February | 0.136985E+10 | 0.817108E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32462151.26 | 0.299740E+09 |
March | 0.163685E+10 | 0.949108E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77473860.14 | 0.171779E+09 |
April | 0.145243E+10 | 0.826780E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187711E+09 | 82425979.57 |
May | 0.157338E+10 | 0.868687E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467002E+09 | 7778625.26 |
June | 0.156900E+10 | 0.855728E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587774E+09 | 377857.72 |
July | 0.145680E+10 | 0.813663E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827960E+09 | 0.00 |
August | 0.163685E+10 | 0.912338E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792262E+09 | 0.00 |
September | 0.145243E+10 | 0.832388E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565663E+09 | 914760.01 |
October | 0.150991E+10 | 0.886960E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319701E+09 | 12283450.03 |
November | 0.149516E+10 | 0.909834E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134828E+09 | 84248517.97 |
December | 0.145680E+10 | 0.912899E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22092574.20 | 0.218997E+09 |
Annual Sum or Average | 0.181194E+11 | 0.105166E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402051E+10 | 0.117110E+10 |
Minimum of Months | 0.136985E+10 | 0.813663E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5585409.87 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.949108E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827960E+09 | 0.299740E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.593631E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1402300.44 | 0.216776E+09 |
February | 0.649041E+09 | 0.524591E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17531807.47 | 0.218317E+09 |
March | 0.773965E+09 | 0.609263E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48045881.67 | 0.125940E+09 |
April | 0.688021E+09 | 0.532801E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117003E+09 | 60874217.15 |
May | 0.744847E+09 | 0.562980E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303969E+09 | 6083185.56 |
June | 0.742030E+09 | 0.555529E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385750E+09 | 340986.57 |
July | 0.690839E+09 | 0.526451E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545465E+09 | 0.00 |
August | 0.773965E+09 | 0.589039E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521493E+09 | 0.00 |
September | 0.688021E+09 | 0.536222E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367587E+09 | 751524.79 |
October | 0.715730E+09 | 0.567834E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203786E+09 | 10343035.90 |
November | 0.708685E+09 | 0.584583E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78707931.01 | 63584299.75 |
December | 0.690839E+09 | 0.582008E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11324634.35 | 0.158858E+09 |
Annual Sum or Average | 0.858171E+10 | 0.676493E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260207E+10 | 0.861869E+09 |
Minimum of Months | 0.649041E+09 | 0.524591E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1402300.44 | 0.00 |
Maximum of Months | 0.773965E+09 | 0.609263E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545465E+09 | 0.218317E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.903638E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1562375.03 | 0.372175E+09 |
February | 0.136988E+10 | 0.803834E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25760103.29 | 0.358678E+09 |
March | 0.163688E+10 | 0.943834E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72857694.56 | 0.201277E+09 |
April | 0.145246E+10 | 0.828484E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180538E+09 | 89422311.38 |
May | 0.157341E+10 | 0.876667E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467150E+09 | 8002586.54 |
June | 0.156904E+10 | 0.864762E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591311E+09 | 314963.50 |
July | 0.145684E+10 | 0.820152E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829609E+09 | 0.00 |
August | 0.163688E+10 | 0.916051E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789345E+09 | 0.00 |
September | 0.145246E+10 | 0.831355E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552889E+09 | 1182771.54 |
October | 0.150994E+10 | 0.876997E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299662E+09 | 19084894.80 |
November | 0.149520E+10 | 0.886065E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111279E+09 | 0.111032E+09 |
December | 0.145684E+10 | 0.880438E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14695788.22 | 0.278023E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104323E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393666E+10 | 0.143919E+10 |
Minimum of Months | 0.136988E+10 | 0.803834E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1562375.03 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.943834E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829609E+09 | 0.372175E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.589394E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2013572.81 | 0.225270E+09 |
February | 0.882782E+09 | 0.521089E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18847057.85 | 0.230148E+09 |
March | 0.105485E+10 | 0.612518E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48553991.08 | 0.139367E+09 |
April | 0.936002E+09 | 0.534907E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116675E+09 | 69094394.12 |
May | 0.101394E+10 | 0.564164E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302194E+09 | 7153230.39 |
June | 0.101113E+10 | 0.555398E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382182E+09 | 444689.08 |
July | 0.938820E+09 | 0.528430E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543124E+09 | 0.00 |
August | 0.105485E+10 | 0.590966E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519300E+09 | 0.00 |
September | 0.936002E+09 | 0.537314E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363955E+09 | 932322.36 |
October | 0.973041E+09 | 0.571284E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200303E+09 | 12668242.20 |
November | 0.963541E+09 | 0.574982E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77820965.37 | 70028137.01 |
December | 0.938820E+09 | 0.573641E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11196935.62 | 0.173458E+09 |
Annual Sum or Average | 0.116768E+11 | 0.675409E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258617E+10 | 0.928564E+09 |
Minimum of Months | 0.882782E+09 | 0.521089E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2013572.81 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.612518E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543124E+09 | 0.230148E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.930973E+09 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6824236.46 | 0.333100E+09 |
February | 0.136985E+10 | 0.817006E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38235194.26 | 0.354257E+09 |
March | 0.163685E+10 | 0.949033E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92860544.36 | 0.207754E+09 |
April | 0.145243E+10 | 0.826756E+09 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223127E+09 | 0.102932E+09 |
May | 0.157338E+10 | 0.868674E+09 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565511E+09 | 10374713.85 |
June | 0.156900E+10 | 0.855711E+09 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714035E+09 | 573323.10 |
July | 0.145680E+10 | 0.813639E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100827E+10 | 0.00 |
August | 0.163685E+10 | 0.912305E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966141E+09 | 0.00 |
September | 0.145243E+10 | 0.832363E+09 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.685697E+09 | 1256230.45 |
October | 0.150991E+10 | 0.886900E+09 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384524E+09 | 16588945.85 |
November | 0.149516E+10 | 0.909784E+09 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158312E+09 | 0.102317E+09 |
December | 0.145680E+10 | 0.912827E+09 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26193395.79 | 0.255581E+09 |
Annual Sum or Average | 0.181194E+11 | 0.105160E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486973E+10 | 0.138473E+10 |
Minimum of Months | 0.136985E+10 | 0.813639E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6824236.46 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.949033E+09 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100827E+10 | 0.354257E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.593603E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1883964.50 | 0.248444E+09 |
February | 0.882782E+09 | 0.524567E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21305908.58 | 0.257974E+09 |
March | 0.105485E+10 | 0.609241E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59482827.69 | 0.151826E+09 |
April | 0.936002E+09 | 0.532787E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142816E+09 | 75642393.84 |
May | 0.101394E+10 | 0.562953E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371352E+09 | 8005543.73 |
June | 0.101113E+10 | 0.555516E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472019E+09 | 497383.25 |
July | 0.938820E+09 | 0.526434E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667444E+09 | 0.00 |
August | 0.105485E+10 | 0.589005E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639569E+09 | 0.00 |
September | 0.936002E+09 | 0.536209E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448867E+09 | 1012629.01 |
October | 0.973041E+09 | 0.567795E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248057E+09 | 13675902.21 |
November | 0.963541E+09 | 0.584560E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95525244.96 | 77172138.32 |
December | 0.938820E+09 | 0.581927E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13820573.59 | 0.185416E+09 |
Annual Sum or Average | 0.116768E+11 | 0.676460E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318214E+10 | 0.101967E+10 |
Minimum of Months | 0.882782E+09 | 0.524567E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1883964.50 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.609241E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667444E+09 | 0.257974E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.903623E+09 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1796519.36 | 0.436069E+09 |
February | 0.136988E+10 | 0.803808E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30838425.17 | 0.429249E+09 |
March | 0.163688E+10 | 0.943796E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87738774.31 | 0.244485E+09 |
April | 0.145246E+10 | 0.828458E+09 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216598E+09 | 0.111523E+09 |
May | 0.157341E+10 | 0.876625E+09 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565737E+09 | 10616290.25 |
June | 0.156904E+10 | 0.864724E+09 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717579E+09 | 481504.13 |
July | 0.145684E+10 | 0.820122E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100990E+10 | 0.00 |
August | 0.163688E+10 | 0.916015E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963311E+09 | 0.00 |
September | 0.145246E+10 | 0.831324E+09 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672052E+09 | 1609730.58 |
October | 0.150994E+10 | 0.876982E+09 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362687E+09 | 25077348.44 |
November | 0.149520E+10 | 0.886055E+09 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133094E+09 | 0.135585E+09 |
December | 0.145684E+10 | 0.880419E+09 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16933195.12 | 0.331523E+09 |
Annual Sum or Average | 0.181198E+11 | 0.104319E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477827E+10 | 0.172622E+10 |
Minimum of Months | 0.136988E+10 | 0.803808E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1796519.36 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.943796E+09 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100990E+10 | 0.436069E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.589349E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2347094.17 | 0.264461E+09 |
February | 0.882782E+09 | 0.521068E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22503897.00 | 0.276384E+09 |
March | 0.105485E+10 | 0.612583E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58582860.29 | 0.169987E+09 |
April | 0.936002E+09 | 0.534888E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140809E+09 | 85923527.46 |
May | 0.101394E+10 | 0.564149E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367652E+09 | 9314820.03 |
June | 0.101113E+10 | 0.555362E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466048E+09 | 656128.71 |
July | 0.938820E+09 | 0.528402E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663487E+09 | 0.00 |
August | 0.105485E+10 | 0.590930E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635267E+09 | 0.00 |
September | 0.936002E+09 | 0.537268E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443316E+09 | 1251601.85 |
October | 0.973041E+09 | 0.571264E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242731E+09 | 16650648.42 |
November | 0.963541E+09 | 0.574970E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93167534.12 | 85694120.49 |
December | 0.938820E+09 | 0.573570E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12923583.37 | 0.206933E+09 |
Annual Sum or Average | 0.116768E+11 | 0.675380E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314883E+10 | 0.111726E+10 |
Minimum of Months | 0.882782E+09 | 0.521068E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2347094.17 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.612583E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663487E+09 | 0.276384E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.302573E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.274456E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.326130E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.291301E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.314351E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.312831E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.292821E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.326130E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.291301E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.302573E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.299026E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.292821E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.362631E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.274456E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.326130E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.397259E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.360343E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.428189E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.382459E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.412724E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.410728E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.384455E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.428189E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.382459E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.397259E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.392603E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.384455E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.476112E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.360343E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.428189E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1715071.30 | 0.332818E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22655987.15 | 0.327340E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57015877.08 | 0.179442E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146393E+09 | 75545170.98 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380215E+09 | 7416119.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471041E+09 | 690898.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670450E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627292E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453055E+09 | 987204.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251155E+09 | 12366814.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94754201.77 | 85821563.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12298373.81 | 0.247561E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318804E+10 | 0.126999E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1715071.30 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670450E+09 | 0.332818E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5020829.47 | 0.550854E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43933705.49 | 0.550700E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103166E+09 | 0.309989E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265649E+09 | 0.140796E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686999E+09 | 13866532.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856875E+09 | 1190747.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122795E+10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115869E+10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819808E+09 | 1812302.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452416E+09 | 24819598.22 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173443E+09 | 0.154479E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24984355.13 | 0.413131E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581894E+10 | 0.216164E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5020829.47 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122795E+10 | 0.550854E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2765512.65 | 0.575132E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40659483.16 | 0.594370E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102057E+09 | 0.345433E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249412E+09 | 0.151710E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724272E+09 | 14671672.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936520E+09 | 1129285.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133921E+10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128467E+10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892820E+09 | 1880561.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483346E+09 | 25681902.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172489E+09 | 0.151374E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19176570.08 | 0.430615E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624739E+10 | 0.229200E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2765512.65 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133921E+10 | 0.594370E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 14744.03 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 14744.03 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 14744.03 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 14744.03 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 14744.03 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 14744.03 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 14744.03 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 14744.03 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 14744.03 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 14744.03 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 14744.03 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 14744.03 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 14744.03 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13241.18 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13241.18 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13241.18 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13241.18 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13241.18 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13241.18 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13241.18 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13241.18 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13241.18 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13241.18 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13241.18 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13241.18 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13241.18 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1238.63 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.59 | 29-JAN-11:50 | 393.38 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1276.00 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 286.56 | 05-FEB-15:10 | 326.20 | 13-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1494.55 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 252.37 | 02-MAR-04:00 | 281.47 | 06-MAR-05:53 |
April | 2010.79 | 03-APR-09:09 | 1229.48 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.01 | 30-APR-13:04 | 206.05 | 05-APR-01:00 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2022.63 | 21-MAY-12:52 | 64.04 | 01-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.54 | 11-JUN-13:04 | 34.16 | 07-JUN-04:30 |
July | 2010.79 | 03-JUL-09:09 | 923.62 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 778.45 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 870.17 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 727.74 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 892.88 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 563.42 | 03-SEP-15:43 | 43.95 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1102.95 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.96 | 09-OCT-15:04 | 88.54 | 20-OCT-04:50 |
November | 2010.79 | 01-NOV-09:09 | 1387.48 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.84 | 19-NOV-14:00 | 163.59 | 22-NOV-05:55 |
December | 2010.79 | 01-DEC-10:09 | 1425.05 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 121.34 | 10-DEC-11:53 | 254.18 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 84.59 | 0.00 | |||||
Maximum of Months | 2010.79 | 1494.55 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2022.63 | 393.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 839.76 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.76 | 23-JAN-13:00 | 261.54 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 841.46 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 194.79 | 05-FEB-15:06 | 215.63 | 13-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 949.09 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.03 | 02-MAR-04:00 | 178.80 | 06-MAR-05:53 |
April | 1295.83 | 03-APR-09:09 | 719.94 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.11 | 30-APR-13:04 | 131.70 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1337.57 | 21-MAY-12:52 | 41.83 | 01-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.48 | 11-JUN-13:04 | 21.52 | 07-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 573.74 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.96 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 509.78 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.16 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 509.78 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.64 | 03-SEP-15:43 | 29.80 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 552.37 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.83 | 09-OCT-15:04 | 56.79 | 20-OCT-04:50 |
November | 1295.83 | 01-NOV-09:09 | 919.61 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.00 | 19-NOV-14:00 | 104.20 | 22-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 930.96 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 79.81 | 10-DEC-12:33 | 158.24 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 24.76 | 0.00 | |||||
Maximum of Months | 1295.83 | 949.09 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1337.57 | 261.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1093.21 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.14 | 23-JAN-13:00 | 411.57 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1207.59 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 263.77 | 05-FEB-15:06 | 347.52 | 10-FEB-23:20 |
March | 2010.83 | 01-MAR-10:09 | 1491.19 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 247.60 | 26-MAR-14:00 | 291.58 | 17-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1238.10 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.61 | 30-APR-13:04 | 210.32 | 05-APR-01:00 |
May | 2010.83 | 01-MAY-09:09 | 844.67 | 23-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2016.93 | 21-MAY-12:52 | 64.36 | 01-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 860.31 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 512.13 | 11-JUN-13:04 | 32.73 | 07-JUN-04:30 |
July | 2010.83 | 03-JUL-09:09 | 1086.98 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 778.45 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 864.26 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 727.74 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 888.58 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 555.83 | 03-SEP-16:00 | 46.12 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 882.27 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.33 | 09-OCT-15:08 | 99.98 | 20-OCT-04:50 |
November | 2010.83 | 01-NOV-09:09 | 1203.88 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.85 | 19-NOV-13:55 | 167.59 | 22-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1333.08 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 109.70 | 10-DEC-12:17 | 248.04 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 844.67 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.14 | 0.00 | |||||
Maximum of Months | 2010.83 | 1491.19 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2016.93 | 411.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 794.30 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.76 | 29-JAN-11:50 | 300.91 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 753.00 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 196.19 | 05-FEB-15:04 | 266.87 | 10-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 969.29 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 165.07 | 26-MAR-14:00 | 245.12 | 17-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 831.29 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.24 | 30-APR-13:04 | 185.76 | 05-APR-01:00 |
May | 1295.83 | 01-MAY-09:09 | 575.15 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1331.30 | 21-MAY-12:52 | 55.25 | 01-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 577.69 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.65 | 11-JUN-13:04 | 37.37 | 07-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 749.03 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.96 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 595.30 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 485.15 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 704.14 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.55 | 03-SEP-16:00 | 34.74 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 770.56 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.47 | 09-OCT-15:04 | 84.00 | 20-OCT-04:10 |
November | 1295.83 | 01-NOV-09:09 | 772.88 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.80 | 19-NOV-13:55 | 135.58 | 22-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 887.77 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.92 | 10-DEC-12:17 | 208.43 | 16-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 575.15 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 25.76 | 0.00 | |||||
Maximum of Months | 1295.83 | 969.29 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1331.30 | 300.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1231.93 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.84 | 29-JAN-11:53 | 742.91 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1271.19 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 707.76 | 05-FEB-15:10 | 640.96 | 13-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1492.64 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 595.68 | 02-MAR-04:06 | 610.49 | 05-MAR-14:55 |
April | 2010.79 | 03-APR-09:09 | 1224.14 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 833.83 | 30-APR-12:52 | 458.60 | 05-APR-00:55 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4833.15 | 21-MAY-13:00 | 137.29 | 02-MAY-02:55 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1183.65 | 11-JUN-13:04 | 99.05 | 07-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 918.07 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1812.19 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 861.58 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.73 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 885.59 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1296.39 | 04-SEP-16:54 | 69.05 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1093.74 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.03 | 09-OCT-15:23 | 247.26 | 20-OCT-04:05 |
November | 2010.79 | 01-NOV-09:09 | 1383.60 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 695.92 | 19-NOV-14:00 | 359.92 | 22-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1422.04 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 320.41 | 10-DEC-11:53 | 500.56 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 289.84 | 0.00 | |||||
Maximum of Months | 2010.79 | 1492.64 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4833.15 | 742.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 833.97 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.08 | 29-JAN-12:00 | 520.16 | 18-JAN-04:00 |
February | 1239.33 | 01-FEB-08:09 | 835.41 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.50 | 05-FEB-14:56 | 447.84 | 10-FEB-23:10 |
March | 1239.33 | 01-MAR-08:09 | 946.31 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 398.23 | 02-MAR-04:06 | 424.49 | 05-MAR-14:55 |
April | 1239.33 | 03-APR-07:10 | 713.38 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 555.92 | 30-APR-12:52 | 317.54 | 05-APR-00:55 |
May | 1239.33 | 01-MAY-07:10 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3222.10 | 21-MAY-13:00 | 98.41 | 02-MAY-02:55 |
June | 1239.33 | 01-JUN-07:10 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 791.51 | 11-JUN-13:04 | 69.01 | 07-JUN-05:00 |
July | 1239.33 | 03-JUL-07:10 | 569.85 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.12 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1239.33 | 01-AUG-07:10 | 509.78 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1128.48 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1239.33 | 01-SEP-07:10 | 509.78 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 881.14 | 04-SEP-16:54 | 49.27 | 25-SEP-05:00 |
October | 1239.33 | 02-OCT-07:10 | 546.66 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 743.56 | 09-OCT-15:23 | 174.09 | 20-OCT-04:05 |
November | 1239.33 | 01-NOV-07:10 | 915.69 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 422.43 | 19-NOV-13:58 | 242.28 | 22-NOV-06:00 |
December | 1239.33 | 01-DEC-08:09 | 927.32 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.75 | 10-DEC-12:40 | 331.87 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 82.08 | 0.00 | |||||
Maximum of Months | 1239.33 | 946.31 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3222.10 | 520.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1087.04 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.30 | 23-JAN-13:00 | 849.93 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1202.43 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 611.45 | 05-FEB-14:56 | 742.91 | 10-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1489.26 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 584.46 | 02-MAR-04:06 | 726.90 | 05-MAR-14:55 |
April | 2010.83 | 03-APR-09:09 | 1232.82 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 833.84 | 30-APR-12:52 | 474.76 | 05-APR-00:55 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4833.15 | 21-MAY-13:00 | 141.40 | 01-MAY-03:10 |
June | 2010.83 | 01-JUN-09:09 | 850.96 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1187.69 | 11-JUN-13:04 | 95.98 | 07-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 1079.08 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1812.18 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 855.38 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1692.72 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 881.07 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1290.28 | 03-SEP-16:00 | 73.94 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 873.60 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1088.06 | 09-OCT-15:00 | 283.58 | 20-OCT-04:05 |
November | 2010.83 | 01-NOV-09:09 | 1198.15 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 614.46 | 19-NOV-13:55 | 381.89 | 22-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 1329.14 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 247.09 | 10-DEC-12:17 | 507.89 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 84.30 | 0.00 | |||||
Maximum of Months | 2010.83 | 1489.26 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4833.15 | 849.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 787.08 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 153.58 | 29-JAN-11:53 | 541.58 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 744.57 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 452.49 | 05-FEB-14:56 | 484.43 | 10-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 966.61 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 405.60 | 02-MAR-04:06 | 484.09 | 05-MAR-14:55 |
April | 1295.83 | 03-APR-09:09 | 824.93 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 555.90 | 30-APR-12:52 | 343.43 | 05-APR-00:55 |
May | 1295.83 | 01-MAY-09:09 | 570.42 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3222.10 | 21-MAY-13:00 | 108.46 | 02-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 573.12 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 789.76 | 11-JUN-13:04 | 77.01 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 740.45 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1208.12 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 591.77 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1128.48 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 693.86 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 860.19 | 03-SEP-16:00 | 54.74 | 24-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 763.66 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 725.39 | 09-OCT-14:51 | 193.55 | 20-OCT-04:05 |
November | 1295.83 | 01-NOV-09:09 | 766.20 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 416.69 | 19-NOV-13:55 | 256.36 | 22-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 882.98 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 192.64 | 10-DEC-11:53 | 347.74 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 570.42 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 153.58 | 0.00 | |||||
Maximum of Months | 1295.83 | 966.61 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3222.10 | 541.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1231.27 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 354.35 | 29-JAN-11:35 | 841.47 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1270.41 | 09-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 833.46 | 05-FEB-15:00 | 744.07 | 10-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1492.29 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 732.83 | 26-MAR-14:00 | 740.72 | 05-MAR-15:10 |
April | 2010.79 | 03-APR-09:09 | 1223.27 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.28 | 30-APR-12:53 | 548.47 | 05-APR-00:55 |
May | 2010.79 | 01-MAY-09:09 | 791.05 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5942.19 | 21-MAY-13:00 | 167.97 | 02-MAY-02:55 |
June | 2010.79 | 01-JUN-09:09 | 791.05 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1461.79 | 11-JUN-13:04 | 109.79 | 07-JUN-04:40 |
July | 2010.79 | 03-JUL-09:09 | 917.85 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2233.25 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.79 | 01-AUG-09:09 | 861.26 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2084.26 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.79 | 01-SEP-09:09 | 885.31 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1579.03 | 04-SEP-17:00 | 91.49 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1092.97 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1360.69 | 09-OCT-15:23 | 310.65 | 20-OCT-04:05 |
November | 2010.79 | 01-NOV-09:09 | 1383.13 | 29-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 790.44 | 19-NOV-14:00 | 429.73 | 22-NOV-05:55 |
December | 2010.79 | 01-DEC-10:09 | 1421.59 | 15-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 385.38 | 10-DEC-12:13 | 573.79 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 791.05 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 354.35 | 0.00 | |||||
Maximum of Months | 2010.79 | 1492.29 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5942.19 | 841.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 833.61 | 04-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.02 | 29-JAN-12:00 | 589.86 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 834.95 | 09-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 505.44 | 05-FEB-15:18 | 521.64 | 10-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 946.07 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 464.06 | 26-MAR-14:00 | 513.11 | 05-MAR-14:55 |
April | 1295.83 | 03-APR-09:09 | 712.74 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 709.04 | 30-APR-12:53 | 378.99 | 05-APR-00:55 |
May | 1295.83 | 01-MAY-09:09 | 509.78 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.46 | 21-MAY-13:00 | 119.70 | 02-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 509.78 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 975.01 | 11-JUN-13:04 | 79.01 | 07-JUN-04:40 |
July | 1295.83 | 03-JUL-09:09 | 569.66 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.83 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 509.78 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1389.50 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 509.78 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1052.68 | 04-SEP-17:00 | 64.34 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 546.49 | 27-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 914.94 | 09-OCT-15:23 | 217.08 | 20-OCT-04:05 |
November | 1295.83 | 01-NOV-09:09 | 915.42 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 505.96 | 05-NOV-15:35 | 289.15 | 22-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 927.04 | 14-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 219.98 | 10-DEC-12:13 | 379.55 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 85.02 | 0.00 | |||||
Maximum of Months | 1295.83 | 946.07 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.46 | 589.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1086.03 | 23-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.20 | 23-JAN-13:00 | 974.65 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1201.56 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 742.66 | 05-FEB-15:15 | 876.80 | 10-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1488.90 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 696.02 | 26-MAR-14:00 | 879.04 | 05-MAR-14:55 |
April | 2010.83 | 03-APR-09:09 | 1231.97 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.44 | 30-APR-12:53 | 567.46 | 05-APR-00:55 |
May | 2010.83 | 01-MAY-09:09 | 791.06 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5942.19 | 21-MAY-13:00 | 171.89 | 02-MAY-02:55 |
June | 2010.83 | 01-JUN-09:09 | 850.61 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1466.45 | 11-JUN-13:04 | 106.27 | 07-JUN-04:40 |
July | 2010.83 | 03-JUL-09:09 | 1077.95 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2233.25 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 2010.83 | 01-AUG-09:09 | 855.03 | 29-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2084.26 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 2010.83 | 01-SEP-09:09 | 880.78 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1579.03 | 04-SEP-17:00 | 96.54 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 873.32 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1336.44 | 09-OCT-15:00 | 353.45 | 20-OCT-04:05 |
November | 2010.83 | 01-NOV-09:09 | 1197.50 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 731.42 | 19-NOV-13:44 | 458.07 | 22-NOV-05:55 |
December | 2010.83 | 01-DEC-10:09 | 1328.60 | 15-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 300.81 | 10-DEC-12:37 | 583.06 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 791.06 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 101.20 | 0.00 | |||||
Maximum of Months | 2010.83 | 1488.90 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 5942.19 | 974.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 786.53 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.74 | 29-JAN-11:35 | 623.20 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 743.95 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 499.84 | 05-FEB-15:15 | 571.59 | 10-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 966.40 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 464.03 | 26-MAR-14:00 | 589.97 | 05-MAR-14:55 |
April | 1295.83 | 03-APR-09:09 | 824.44 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 706.54 | 30-APR-12:53 | 411.88 | 05-APR-00:55 |
May | 1295.83 | 01-MAY-09:09 | 570.26 | 23-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.45 | 21-MAY-13:00 | 131.89 | 02-MAY-02:55 |
June | 1295.83 | 01-JUN-09:09 | 572.96 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 974.26 | 11-JUN-13:04 | 90.47 | 07-JUN-04:40 |
July | 1295.83 | 03-JUL-09:09 | 739.80 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1488.83 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 1295.83 | 01-AUG-09:09 | 591.64 | 29-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1389.50 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 1295.83 | 01-SEP-09:09 | 693.20 | 06-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1052.68 | 04-SEP-17:00 | 69.78 | 24-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 763.26 | 31-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 891.17 | 09-OCT-14:44 | 241.27 | 20-OCT-04:05 |
November | 1295.83 | 01-NOV-09:09 | 765.83 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.41 | 05-NOV-14:53 | 309.24 | 22-NOV-05:55 |
December | 1295.83 | 01-DEC-10:09 | 882.60 | 15-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 228.75 | 10-DEC-12:13 | 403.36 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 570.26 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 182.74 | 0.00 | |||||
Maximum of Months | 1295.83 | 966.40 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 3961.45 | 623.20 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 316.63 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 316.63 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 316.63 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 316.63 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 316.63 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 316.63 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 316.63 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 316.63 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 316.63 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 316.63 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 316.63 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 316.63 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4157.19 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4157.19 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4157.19 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4157.19 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4157.19 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4157.19 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4157.19 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4157.19 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4157.19 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4157.19 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4157.19 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4157.19 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.48 | 29-JAN-11:53 | 865.39 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.92 | 05-FEB-14:52 | 710.37 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.88 | 26-MAR-14:00 | 624.59 | 06-MAR-05:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.77 | 30-APR-12:52 | 442.15 | 05-APR-01:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4109.96 | 21-MAY-12:52 | 137.64 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 984.06 | 11-JUN-12:52 | 93.32 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1502.12 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1368.22 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1069.54 | 03-SEP-16:00 | 97.59 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 890.68 | 09-OCT-14:51 | 204.63 | 20-OCT-04:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.92 | 19-NOV-14:00 | 381.05 | 22-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.78 | 10-DEC-12:40 | 536.77 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.48 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4109.96 | 865.39 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.35 | 29-JAN-12:00 | 1409.49 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1128.12 | 05-FEB-14:42 | 1192.17 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 988.33 | 26-MAR-14:00 | 1079.82 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1338.58 | 30-APR-13:00 | 794.22 | 05-APR-00:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7352.58 | 21-MAY-12:52 | 226.16 | 01-MAY-04:52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1804.55 | 11-JUN-12:52 | 173.75 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2751.22 | 30-JUL-14:50 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2560.11 | 13-AUG-14:00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1950.96 | 03-SEP-16:00 | 158.05 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1663.16 | 09-OCT-15:00 | 400.72 | 20-OCT-04:12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1066.14 | 19-NOV-14:00 | 672.29 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.65 | 10-DEC-12:40 | 917.95 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.35 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7352.58 | 1409.49 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.26 | 29-JAN-11:43 | 1413.00 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1023.71 | 05-FEB-15:00 | 1163.35 | 13-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 848.52 | 26-MAR-14:00 | 1269.25 | 05-MAR-15:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1276.60 | 30-APR-13:00 | 825.65 | 05-APR-00:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7114.54 | 21-MAY-13:00 | 259.65 | 01-MAY-04:52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1728.40 | 11-JUN-12:52 | 162.44 | 07-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2827.32 | 30-JUL-14:10 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2553.21 | 13-AUG-14:10 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1967.49 | 04-SEP-17:00 | 172.79 | 25-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1645.33 | 09-OCT-15:10 | 465.30 | 20-OCT-04:14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.17 | 19-NOV-14:00 | 650.71 | 22-NOV-05:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.98 | 10-DEC-12:13 | 914.50 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.26 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7114.54 | 1413.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 107522.61 | 02-JAN-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 101090.34 | 13-FEB-05:23 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 104973.68 | 06-MAR-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 100161.40 | 24-APR-04:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95222.55 | 29-MAY-12:00 | 5385.68 | 4914.31 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87710.65 | 02-JUN-04:28 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 99383.28 | 03-JUL-03:02 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91820.29 | 06-AUG-09:00 | 6283.29 | 5733.36 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92977.51 | 04-SEP-16:51 | 7180.90 | 6552.41 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 102022.84 | 29-OCT-13:00 | 6283.29 | 5733.36 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99833.70 | 05-NOV-14:50 | 6283.29 | 5733.36 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 108489.57 | 18-DEC-05:11 | 0.00 | 4188.45 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 87710.65 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 108489.57 | 7180.90 | 6552.41 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 99275.83 | 02-JAN-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99626.34 | 21-FEB-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96126.88 | 06-MAR-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 89595.21 | 01-APR-04:12 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94958.34 | 01-MAY-04:23 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87184.29 | 05-JUN-05:03 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89059.33 | 31-JUL-05:05 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 90907.68 | 07-AUG-05:05 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88264.04 | 25-SEP-05:04 | 8061.19 | 2686.80 | 38236.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88179.95 | 10-OCT-05:03 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93836.23 | 28-NOV-05:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 96858.21 | 18-DEC-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 87184.29 | 0.00 | 2686.80 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99626.34 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84010.58 | 02-JAN-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85698.15 | 21-FEB-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86264.57 | 06-MAR-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86267.54 | 13-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80930.93 | 04-MAY-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67995.49 | 12-JUN-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70181.12 | 10-JUL-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76833.53 | 07-AUG-05:04 | 12897.91 | 4298.88 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76564.34 | 05-SEP-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89457.11 | 21-OCT-04:13 | 0.00 | 3761.52 | 31172.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86385.73 | 27-NOV-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85456.60 | 04-DEC-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 67995.49 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89457.11 | 12897.91 | 4298.88 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 79728.81 | 25-JAN-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 85318.81 | 08-FEB-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86044.63 | 24-MAR-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85863.97 | 10-APR-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86937.87 | 01-MAY-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84737.48 | 12-JUN-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85705.24 | 17-JUL-05:05 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87268.34 | 07-AUG-05:04 | 12897.91 | 4298.88 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85455.55 | 05-SEP-05:03 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86406.55 | 30-OCT-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86541.94 | 13-NOV-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85449.69 | 11-DEC-05:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 79728.81 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87268.34 | 12897.91 | 4298.88 | 61178.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12131.81 | 30-JAN-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.48 |
February | 15428.11 | 09-FEB-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.67 |
March | 19075.22 | 26-MAR-14:52 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.64 | 0.00 |
April | 17017.13 | 24-APR-04:21 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 |
May | 23216.73 | 21-MAY-15:41 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 479.18 | 0.00 |
June | 23416.43 | 04-JUN-16:21 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 240.30 | 0.00 |
July | 24105.33 | 04-JUL-15:51 | 910.95 | 395.49 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 389.34 | 0.00 |
August | 23038.74 | 06-AUG-15:01 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 446.69 | 0.00 |
September | 22660.76 | 10-SEP-16:21 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 304.40 | 0.00 |
October | 22172.75 | 01-OCT-13:52 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.04 | 0.00 |
November | 15811.84 | 13-NOV-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 |
December | 12870.89 | 12-DEC-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12131.81 | 0.00 | 263.66 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24105.33 | 1012.16 | 472.30 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 479.18 | 60.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8584.69 | 30-JAN-05:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 |
February | 10632.24 | 05-FEB-15:02 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 173.24 | 0.00 |
March | 16106.92 | 26-MAR-14:52 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 142.42 | 0.00 |
April | 18313.11 | 30-APR-10:23 | 260.91 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 55.36 | 0.00 |
May | 19827.99 | 29-MAY-09:52 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 | 0.00 |
June | 19404.97 | 04-JUN-15:41 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 171.67 | 0.00 |
July | 20077.26 | 04-JUL-15:11 | 587.05 | 254.87 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 249.80 | 0.00 |
August | 18941.72 | 06-AUG-15:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 302.71 | 0.00 |
September | 18898.38 | 10-SEP-16:21 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 203.35 | 0.00 |
October | 18528.82 | 01-OCT-13:52 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 166.41 | 0.00 |
November | 10870.12 | 12-NOV-13:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 86.46 | 0.00 |
December | 5870.63 | 04-DEC-10:10 | 2591.66 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5870.63 | 0.00 | 113.28 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20077.26 | 2591.66 | 1019.56 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 302.71 | 28.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19868.93 | 30-JAN-05:12 | 0.00 | 404.83 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.92 |
February | 26264.61 | 05-FEB-13:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 185.69 | 0.00 |
March | 25604.12 | 26-MAR-14:52 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 184.16 | 0.00 |
April | 20500.00 | 30-APR-13:02 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 343.61 | 0.00 |
May | 25946.13 | 21-MAY-15:41 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 480.29 | 0.00 |
June | 25806.28 | 04-JUN-15:41 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 260.75 | 0.00 |
July | 26692.14 | 04-JUL-15:11 | 910.97 | 395.50 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 378.75 | 0.00 |
August | 25800.63 | 06-AUG-15:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 446.42 | 0.00 |
September | 26400.35 | 10-SEP-13:42 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 272.48 | 0.00 |
October | 26817.24 | 01-OCT-13:52 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 214.77 | 0.00 |
November | 26312.49 | 12-NOV-13:52 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 87.62 | 0.00 |
December | 26542.79 | 03-DEC-12:42 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 13.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19868.93 | 0.00 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26817.24 | 910.97 | 404.83 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 480.29 | 42.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18661.45 | 30-JAN-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.13 |
February | 24371.00 | 05-FEB-15:42 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 155.00 | 0.00 |
March | 25412.50 | 26-MAR-14:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 116.01 | 0.00 |
April | 24869.05 | 23-APR-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 125.82 | 0.00 |
May | 27168.81 | 21-MAY-15:41 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 284.29 | 0.00 |
June | 27304.20 | 04-JUN-16:21 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 141.23 | 0.00 |
July | 28305.20 | 04-JUL-15:51 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.82 | 0.00 |
August | 27032.20 | 06-AUG-15:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 242.75 | 0.00 |
September | 26083.43 | 10-SEP-16:21 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 180.21 | 0.00 |
October | 25552.86 | 01-OCT-14:32 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 126.31 | 0.00 |
November | 24641.09 | 12-NOV-14:32 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 48.60 | 0.00 |
December | 24426.66 | 03-DEC-14:42 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18661.45 | 0.00 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28305.20 | 587.05 | 260.89 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.29 | 29.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5299.71 | 23-JAN-14:10 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.59 | 0.00 |
February | 11614.10 | 09-FEB-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.65 |
March | 16764.24 | 26-MAR-14:52 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.98 | 0.00 |
April | 22302.80 | 30-APR-16:02 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.77 | 0.00 |
May | 23703.09 | 29-MAY-16:41 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 478.68 | 0.00 |
June | 22689.61 | 11-JUN-15:02 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1095.52 | 0.00 |
July | 23404.59 | 30-JUL-14:22 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1726.94 | 0.00 |
August | 23394.72 | 06-AUG-15:01 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1042.24 | 0.00 |
September | 24817.36 | 04-SEP-14:51 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.60 | 0.00 |
October | 22375.02 | 01-OCT-16:42 | 607.30 | 279.22 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 417.47 | 0.00 |
November | 15770.32 | 05-NOV-15:22 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 532.79 | 0.00 |
December | 9893.36 | 12-DEC-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5299.71 | 607.30 | 263.66 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24817.36 | 4021.58 | 1582.09 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1726.94 | 22.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6378.20 | 24-JAN-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
February | 11529.09 | 05-FEB-14:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 402.19 | 0.00 |
March | 19179.46 | 26-MAR-14:52 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 325.76 | 0.00 |
April | 20447.33 | 23-APR-10:12 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 158.35 | 0.00 |
May | 21003.60 | 29-MAY-09:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 59.48 | 0.00 |
June | 19842.07 | 11-JUN-10:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 460.80 | 0.00 |
July | 20620.09 | 30-JUL-09:42 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 518.08 | 0.00 |
August | 20302.64 | 06-AUG-15:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 696.93 | 0.00 |
September | 21915.58 | 04-SEP-14:11 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 710.43 | 0.00 |
October | 19800.58 | 01-OCT-12:02 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 317.32 | 0.00 |
November | 17247.64 | 05-NOV-15:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 351.46 | 0.00 |
December | 7086.74 | 04-DEC-11:05 | 2478.65 | 1019.56 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6378.20 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21915.58 | 2478.65 | 1019.56 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 710.43 | 1.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16823.94 | 22-JAN-14:33 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.77 |
February | 26917.35 | 05-FEB-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 405.38 | 0.00 |
March | 26178.37 | 26-MAR-13:32 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 435.95 | 0.00 |
April | 25527.26 | 30-APR-13:22 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 701.61 | 0.00 |
May | 26070.97 | 29-MAY-16:41 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 490.64 | 0.00 |
June | 24978.87 | 11-JUN-15:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.71 | 0.00 |
July | 26103.39 | 30-JUL-14:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1726.90 | 0.00 |
August | 26130.73 | 06-AUG-15:01 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1040.44 | 0.00 |
September | 29023.84 | 04-SEP-14:11 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1021.02 | 0.00 |
October | 27108.17 | 01-OCT-12:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 412.97 | 0.00 |
November | 27667.60 | 05-NOV-12:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 226.08 | 0.00 |
December | 25779.54 | 03-DEC-15:02 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16823.94 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29023.84 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1726.90 | 31.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7883.88 | 30-JAN-06:03 | 521.82 | 173.92 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 |
February | 19324.52 | 05-FEB-15:32 | 326.14 | 141.60 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 377.84 | 0.00 |
March | 22413.42 | 26-MAR-16:52 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 177.71 | 0.00 |
April | 22832.24 | 30-APR-16:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 187.23 | 0.00 |
May | 24699.54 | 29-MAY-16:41 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 273.12 | 0.00 |
June | 22487.51 | 18-JUN-16:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 542.35 | 0.00 |
July | 23017.53 | 30-JUL-15:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1079.89 | 0.00 |
August | 23522.50 | 06-AUG-15:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 589.48 | 0.00 |
September | 25449.46 | 04-SEP-14:51 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 619.76 | 0.00 |
October | 22777.59 | 01-OCT-16:42 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 247.92 | 0.00 |
November | 22434.72 | 05-NOV-15:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 304.46 | 0.00 |
December | 9691.54 | 03-DEC-15:02 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7883.88 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25449.46 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1079.89 | 17.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5514.39 | 23-JAN-14:10 | 4021.58 | 1582.09 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.82 | 0.00 |
February | 13179.60 | 06-FEB-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.85 |
March | 18072.04 | 02-MAR-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 164.04 | 0.00 |
April | 24489.51 | 30-APR-16:11 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 539.92 | 0.00 |
May | 26684.69 | 21-MAY-12:52 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 5422.53 | 0.00 |
June | 25616.67 | 11-JUN-15:02 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1324.02 | 0.00 |
July | 26553.27 | 30-JUL-14:22 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 2093.95 | 0.00 |
August | 26477.62 | 06-AUG-15:01 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1262.38 | 0.00 |
September | 28085.15 | 04-SEP-14:01 | 809.73 | 351.55 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1319.87 | 0.00 |
October | 25778.23 | 08-OCT-15:31 | 708.51 | 307.61 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 608.01 | 0.00 |
November | 22121.80 | 05-NOV-15:32 | 607.30 | 263.66 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 629.51 | 0.00 |
December | 9949.91 | 11-DEC-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5514.39 | 607.30 | 263.66 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28085.15 | 4021.58 | 1582.09 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 5422.53 | 74.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4292.22 | 24-JAN-11:00 | 1295.83 | 509.78 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 |
February | 11130.58 | 06-FEB-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 |
March | 14139.01 | 27-MAR-04:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.04 |
April | 21102.17 | 30-APR-10:52 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 222.96 | 0.00 |
May | 21927.55 | 21-MAY-08:52 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 501.56 | 0.00 |
June | 20689.99 | 11-JUN-10:22 | 326.14 | 141.60 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 561.69 | 0.00 |
July | 21612.94 | 30-JUL-14:22 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1387.60 | 0.00 |
August | 21437.57 | 06-AUG-15:01 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 840.76 | 0.00 |
September | 23120.52 | 04-SEP-14:01 | 521.82 | 226.55 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 860.18 | 0.00 |
October | 21067.28 | 08-OCT-15:31 | 456.59 | 198.23 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 393.80 | 0.00 |
November | 19772.23 | 05-NOV-15:32 | 391.37 | 169.91 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 415.37 | 0.00 |
December | 7551.51 | 11-DEC-06:03 | 521.82 | 173.92 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4292.22 | 0.00 | 141.60 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23120.52 | 1295.83 | 509.78 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1387.60 | 49.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15818.10 | 29-JAN-15:13 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.46 |
February | 28066.44 | 05-FEB-12:32 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 516.37 | 0.00 |
March | 27868.09 | 26-MAR-12:23 | 404.87 | 175.78 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 262.62 | 0.00 |
April | 28016.23 | 30-APR-12:12 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 588.35 | 0.00 |
May | 29274.90 | 21-MAY-12:52 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 5437.43 | 0.00 |
June | 27812.96 | 11-JUN-15:02 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 1348.03 | 0.00 |
July | 29193.79 | 30-JUL-14:22 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2093.38 | 0.00 |
August | 29238.36 | 13-AUG-14:21 | 708.53 | 307.61 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1867.39 | 0.00 |
September | 32361.40 | 04-SEP-14:01 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 1238.37 | 0.00 |
October | 30305.32 | 08-OCT-14:12 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 471.08 | 0.00 |
November | 30353.11 | 05-NOV-12:12 | 607.31 | 263.67 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 312.00 | 0.00 |
December | 29351.73 | 03-DEC-12:52 | 506.09 | 219.72 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 40.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15818.10 | 303.66 | 131.83 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32361.40 | 809.75 | 351.56 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 5437.43 | 84.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6689.77 | 29-JAN-15:53 | 195.68 | 84.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 |
February | 16942.92 | 05-FEB-16:33 | 260.91 | 113.28 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 348.31 | 0.00 |
March | 19031.82 | 27-MAR-04:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.79 |
April | 23827.06 | 30-APR-16:11 | 521.82 | 226.55 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 321.86 | 0.00 |
May | 26033.88 | 28-MAY-15:11 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 384.21 | 0.00 |
June | 24482.60 | 11-JUN-16:22 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 753.51 | 0.00 |
July | 25177.68 | 30-JUL-15:02 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 1308.28 | 0.00 |
August | 25728.47 | 06-AUG-15:41 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 714.11 | 0.00 |
September | 27422.56 | 04-SEP-15:21 | 587.05 | 254.87 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.58 | 0.00 |
October | 25579.36 | 08-OCT-15:31 | 456.59 | 198.23 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 336.66 | 0.00 |
November | 24310.74 | 05-NOV-15:32 | 391.37 | 169.91 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 350.27 | 0.00 |
December | 10260.99 | 11-DEC-06:03 | 521.82 | 173.92 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6689.77 | 0.00 | 84.96 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27422.56 | 587.05 | 260.89 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1308.28 | 50.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9349.14 | 30-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.87 |
February | 10341.98 | 06-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.24 |
March | 11466.92 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.88 | 0.00 |
April | 12563.46 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.22 |
May | 19369.94 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 | 0.00 |
June | 16831.34 | 12-JUN-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 | 0.00 |
July | 21517.19 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.71 | 0.00 |
August | 24589.81 | 07-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 | 0.00 |
September | 23564.45 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 | 0.00 |
October | 20156.53 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 | 0.00 |
November | 14643.04 | 06-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.37 |
December | 10139.96 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9349.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24589.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.88 | 60.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4503.59 | 30-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 |
February | 6847.97 | 06-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.45 | 0.00 |
March | 9914.27 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.31 | 0.00 |
April | 10720.04 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 |
May | 13804.25 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 | 0.00 |
June | 14157.79 | 05-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.26 | 0.00 |
July | 19106.06 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.47 | 0.00 |
August | 22090.11 | 07-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.20 | 0.00 |
September | 20062.66 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.44 | 0.00 |
October | 13977.16 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 | 0.00 |
November | 10916.50 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.55 |
December | 6362.86 | 04-DEC-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4503.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22090.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.31 | 65.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8600.21 | 23-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.73 | 0.00 |
February | 13793.96 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.75 | 0.00 |
March | 19436.81 | 27-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.60 | 0.00 |
April | 21624.52 | 28-APR-12:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 798.81 | 0.00 |
May | 24395.27 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.97 | 0.00 |
June | 25435.58 | 09-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 935.71 | 0.00 |
July | 27756.28 | 21-JUL-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.45 | 0.00 |
August | 28101.39 | 16-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.77 | 0.00 |
September | 26475.98 | 04-SEP-15:21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1576.82 | 0.00 |
October | 20182.55 | 05-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.49 | 0.00 |
November | 16014.89 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.92 | 0.00 |
December | 11035.16 | 04-DEC-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8600.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.33 | 0.00 | |
Maximum of Months | 28101.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1576.82 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1900.51 | 29-JAN-17:40 | 23.38 | 35.18 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3850.24 | 05-FEB-17:17 | 35.07 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7206.49 | 31-MAR-23:50 | 0.00 | 17.59 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7834.61 | 23-APR-18:10 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3602.80 | 31-MAY-23:57 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5438.38 | 30-JUN-24:00 | 0.00 | 35.18 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7245.16 | 31-JUL-23:57 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7671.38 | 15-AUG-04:03 | 0.00 | 105.54 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3545.27 | 30-SEP-24:00 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5404.22 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5941.63 | 12-NOV-16:53 | 46.77 | 70.37 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7706.11 | 25-DEC-16:55 | 23.38 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1900.51 | 0.00 | 17.59 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7834.61 | 46.77 | 105.54 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1709.80 | 31-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3581.47 | 06-FEB-16:10 | 222.14 | 316.63 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6934.80 | 31-MAR-23:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7380.80 | 23-APR-17:44 | 0.00 | 87.96 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3473.89 | 31-MAY-23:57 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5227.87 | 30-JUN-24:00 | 0.00 | 35.18 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6916.48 | 31-JUL-23:42 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7168.88 | 14-AUG-03:23 | 0.00 | 52.77 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3409.72 | 30-SEP-23:40 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5230.00 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5536.60 | 12-NOV-17:02 | 58.46 | 87.96 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7202.34 | 04-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1709.80 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7380.80 | 222.14 | 316.63 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1735.84 | 31-JAN-17:00 | 222.14 | 316.63 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3660.10 | 05-FEB-17:23 | 35.07 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6880.83 | 31-MAR-23:55 | 0.00 | 35.18 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7574.02 | 02-APR-16:22 | 70.15 | 105.55 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3530.15 | 31-MAY-23:57 | 0.00 | 52.77 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5243.40 | 30-JUN-24:00 | 0.00 | 35.18 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6976.26 | 31-JUL-23:42 | 0.00 | 70.37 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7269.31 | 14-AUG-03:01 | 0.00 | 123.14 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3449.16 | 30-SEP-24:00 | 0.00 | 35.18 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5226.51 | 31-OCT-24:00 | 0.00 | 17.59 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5696.01 | 05-NOV-17:05 | 0.00 | 70.37 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7224.54 | 06-DEC-17:00 | 222.14 | 316.63 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1735.84 | 0.00 | 17.59 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7574.02 | 222.14 | 316.63 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 93459.62 | 02-JAN-17:00 | 4808.68 | 4157.19 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 184499.45 | 06-FEB-17:00 | 4808.68 | 4157.19 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 359448.86 | 31-MAR-23:55 | 0.00 | 461.88 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369419.76 | 30-APR-03:07 | 0.00 | 692.81 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176743.09 | 31-MAY-23:57 | 0.00 | 692.81 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268328.29 | 30-JUN-24:00 | 0.00 | 461.88 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 353299.68 | 31-JUL-23:23 | 0.00 | 692.81 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366877.63 | 15-AUG-07:10 | 4808.68 | 4157.19 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177559.45 | 30-SEP-24:00 | 0.00 | 461.88 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269845.39 | 31-OCT-24:00 | 0.00 | 230.94 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277817.20 | 13-NOV-17:00 | 4808.68 | 4157.19 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369187.02 | 06-DEC-22:02 | 1265.44 | 2309.63 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93459.62 | 0.00 | 230.94 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369419.76 | 4808.68 | 4157.19 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.171961E+13 | 1134758.32 | 30-JAN-13:00 | 0.544862E+11 | 69578.68 | 11-JAN-12:20 |
February | 0.196742E+13 | 1449109.28 | 07-FEB-16:10 | 0.485282E+11 | 69104.48 | 01-FEB-12:00 |
March | 0.270616E+13 | 1688851.35 | 27-MAR-15:20 | 0.533286E+11 | 65496.04 | 10-MAR-12:50 |
April | 0.311745E+13 | 1879455.53 | 28-APR-15:09 | 0.466079E+11 | 60758.66 | 06-APR-11:39 |
May | 0.225796E+13 | 1537866.58 | 31-MAY-15:00 | 0.459784E+11 | 55099.20 | 01-MAY-11:00 |
June | 0.280715E+13 | 1736073.98 | 12-JUN-15:09 | 0.428149E+11 | 47835.25 | 01-JUN-11:30 |
July | 0.341169E+13 | 1983493.25 | 19-JUL-15:20 | 0.416931E+11 | 43824.51 | 31-JUL-11:20 |
August | 0.394748E+13 | 2157924.09 | 10-AUG-15:20 | 0.447308E+11 | 48858.51 | 30-AUG-11:30 |
September | 0.237851E+13 | 1602902.92 | 07-SEP-15:20 | 0.441792E+11 | 56011.87 | 29-SEP-11:50 |
October | 0.264979E+13 | 1650213.29 | 06-OCT-15:39 | 0.487162E+11 | 62860.91 | 31-OCT-11:00 |
November | 0.273886E+13 | 1750515.34 | 01-NOV-15:09 | 0.504483E+11 | 67136.79 | 29-NOV-12:30 |
December | 0.299006E+13 | 1737137.06 | 06-DEC-16:49 | 0.530439E+11 | 69368.59 | 29-DEC-12:30 |
Annual Sum or Average | 0.326921E+14 | 0.574556E+12 | ||||
Minimum of Months | 0.171961E+13 | 1134758.32 | 0.416931E+11 | 43824.51 | ||
Maximum of Months | 0.394748E+13 | 2157924.09 | 0.544862E+11 | 69578.68 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.206609E+12 | 0.353743E+11 | 0.766053E+12 | 0.162121E+12 | 0.175295E+12 | 0.468631E+11 | 0.00 | 0.217489E+12 | 0.107081E+12 | 0.272687E+10 | 0.00 | 0.00 | 0.00 |
February | 0.186576E+12 | 0.297811E+11 | 0.978954E+12 | 0.146439E+12 | 0.167965E+12 | 0.441899E+11 | 0.00 | 0.298669E+12 | 0.112302E+12 | 0.254650E+10 | 0.00 | 0.00 | 0.00 |
March | 0.221317E+12 | 0.301448E+11 | 0.141687E+13 | 0.162292E+12 | 0.206604E+12 | 0.590080E+11 | 0.00 | 0.475625E+12 | 0.132687E+12 | 0.160792E+10 | 0.00 | 0.00 | 0.00 |
April | 0.196707E+12 | 0.262757E+11 | 0.165903E+13 | 0.156876E+12 | 0.216762E+12 | 0.709736E+11 | 0.00 | 0.640060E+12 | 0.150118E+12 | 0.649210E+09 | 0.00 | 0.00 | 0.00 |
May | 0.211636E+12 | 0.247812E+11 | 0.774844E+12 | 0.162206E+12 | 0.263286E+12 | 0.872553E+11 | 0.00 | 0.543755E+12 | 0.190192E+12 | 6654117.42 | 0.00 | 0.00 | 0.00 |
June | 0.210384E+12 | 0.230488E+11 | 0.106252E+13 | 0.157035E+12 | 0.273253E+12 | 0.965152E+11 | 0.00 | 0.774207E+12 | 0.210194E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197054E+12 | 0.242828E+11 | 0.139340E+13 | 0.162046E+12 | 0.289827E+12 | 0.103903E+12 | 0.00 | 0.102095E+13 | 0.220224E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.220038E+12 | 0.262287E+11 | 0.173200E+13 | 0.162291E+12 | 0.318481E+12 | 0.109337E+12 | 0.00 | 0.115184E+13 | 0.227259E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196878E+12 | 0.277324E+11 | 0.740713E+12 | 0.156875E+12 | 0.264059E+12 | 0.962033E+11 | 0.00 | 0.683777E+12 | 0.212271E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205233E+12 | 0.316237E+11 | 0.108340E+13 | 0.162121E+12 | 0.250059E+12 | 0.864687E+11 | 0.00 | 0.635898E+12 | 0.194913E+12 | 71871831.39 | 0.00 | 0.00 | 0.00 |
November | 0.203936E+12 | 0.334772E+11 | 0.135889E+13 | 0.156940E+12 | 0.215977E+12 | 0.689616E+11 | 0.00 | 0.548547E+12 | 0.151953E+12 | 0.180557E+09 | 0.00 | 0.00 | 0.00 |
December | 0.200182E+12 | 0.362323E+11 | 0.170972E+13 | 0.162046E+12 | 0.186764E+12 | 0.559602E+11 | 0.00 | 0.506123E+12 | 0.130078E+12 | 0.295298E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.245655E+13 | 0.348983E+12 | 0.146764E+14 | 0.190929E+13 | 0.282833E+13 | 0.925638E+12 | 0.00 | 0.749694E+13 | 0.203927E+13 | 0.107426E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.186576E+12 | 0.230488E+11 | 0.740713E+12 | 0.146439E+12 | 0.167965E+12 | 0.441899E+11 | 0.00 | 0.217489E+12 | 0.107081E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.221317E+12 | 0.362323E+11 | 0.173200E+13 | 0.162292E+12 | 0.318481E+12 | 0.109337E+12 | 0.00 | 0.115184E+13 | 0.227259E+12 | 0.295298E+10 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 6147766.18 | 0.00 | 0.544801E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 809652.65 | 0.00 | 0.485274E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.533286E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.466079E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.459784E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.428149E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.416931E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.447308E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.441792E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.487162E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.504483E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 78299.80 | 0.00 | 0.530438E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7035718.64 | 0.00 | 0.574549E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.416931E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 6147766.18 | 0.00 | 0.544801E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 226111.18 | 23-JAN-16:00 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 116878.32 | 09-JAN-08:20 | 124922.50 | 23-JAN-13:30 | 28242.98 | 30-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 229973.87 | 09-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 116877.26 | 09-FEB-08:20 | 168968.80 | 06-FEB-15:09 | 51330.67 | 06-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 240337.66 | 15-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 116887.29 | 15-MAR-07:19 | 212759.60 | 27-MAR-14:50 | 53720.97 | 23-MAR-12:00 | 0.00 | 01-MAR-00:10 |
April | 229558.90 | 18-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 116881.58 | 18-APR-07:19 | 214843.47 | 28-APR-15:20 | 52869.11 | 24-APR-11:00 | 0.00 | 01-APR-00:10 |
May | 213600.87 | 23-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 116873.13 | 23-MAY-07:19 | 235381.03 | 22-MAY-14:30 | 52521.29 | 08-MAY-08:30 | 0.00 | 01-MAY-00:10 |
June | 214307.22 | 08-JUN-07:10 | 40855.88 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 116873.51 | 08-JUN-07:19 | 246078.65 | 09-JUN-14:50 | 52921.24 | 09-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 221308.06 | 20-JUL-07:10 | 40855.88 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 116877.21 | 20-JUL-07:19 | 270588.78 | 31-JUL-15:39 | 54922.35 | 24-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 215437.24 | 29-AUG-07:10 | 40855.88 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 116874.11 | 29-AUG-07:19 | 268567.15 | 07-AUG-15:20 | 55499.53 | 10-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 217262.40 | 06-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 116875.07 | 06-SEP-07:19 | 273398.84 | 05-SEP-15:00 | 54662.72 | 05-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 219508.73 | 31-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 116876.26 | 31-OCT-07:19 | 224974.87 | 10-OCT-15:20 | 52332.10 | 19-OCT-16:19 | 0.00 | 01-OCT-00:10 |
November | 231953.64 | 29-NOV-16:00 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 116876.55 | 29-NOV-08:20 | 192770.03 | 06-NOV-15:09 | 51589.93 | 01-NOV-14:09 | 0.00 | 01-NOV-00:10 |
December | 235558.19 | 15-DEC-16:00 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 116884.18 | 15-DEC-08:20 | 154165.64 | 04-DEC-13:00 | 50798.87 | 06-DEC-14:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 213600.87 | 40855.88 | 423497.50 | 116873.13 | 124922.50 | 28242.98 | 0.00 | |||||||
Maximum of Months | 240337.66 | 40855.88 | 778371.69 | 116887.29 | 273398.84 | 55499.53 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 233568.92 | 30-JAN-13:00 | 87148.87 | 30-JAN-13:30 | 5534.43 | 01-JAN-05:00 | 0.00 | 0.00 | 0.00 |
February | 344449.05 | 07-FEB-13:09 | 87148.87 | 06-FEB-10:00 | 7079.18 | 15-FEB-05:00 | 0.00 | 0.00 | 0.00 |
March | 414281.15 | 27-MAR-12:09 | 87148.87 | 01-MAR-13:20 | 9756.30 | 08-MAR-05:00 | 0.00 | 0.00 | 0.00 |
April | 454542.53 | 28-APR-14:00 | 87148.87 | 30-APR-14:30 | 14438.86 | 26-APR-10:09 | 0.00 | 0.00 | 0.00 |
May | 457943.57 | 31-MAY-15:00 | 87148.87 | 21-MAY-12:00 | 1439.22 | 07-MAY-10:00 | 0.00 | 0.00 | 0.00 |
June | 526531.42 | 12-JUN-14:09 | 87148.87 | 03-JUN-16:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 647873.76 | 19-JUL-14:00 | 87148.87 | 01-JUL-03:09 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 683244.40 | 10-AUG-15:30 | 87148.87 | 01-AUG-03:09 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 525619.52 | 07-SEP-14:09 | 87148.87 | 02-SEP-16:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 469418.86 | 06-OCT-15:00 | 87148.87 | 01-OCT-10:09 | 4473.31 | 29-OCT-12:00 | 0.00 | 0.00 | 0.00 |
November | 481711.11 | 01-NOV-14:09 | 87148.87 | 01-NOV-05:40 | 4096.58 | 22-NOV-05:49 | 0.00 | 0.00 | 0.00 |
December | 422878.75 | 05-DEC-13:09 | 87148.87 | 04-DEC-09:20 | 13510.11 | 18-DEC-05:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 233568.92 | 87148.87 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 683244.40 | 87148.87 | 14438.86 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1134758.32 | 30-JAN-13:00 | 212815.01 | 423497.50 | 0.00 | 37438.14 | 112992.94 | 27296.93 | 0.00 | 233568.92 | 87148.87 |
February | 1449109.28 | 07-FEB-16:10 | 212815.01 | 541788.89 | 0.00 | 82829.33 | 148379.74 | 50425.44 | 0.00 | 325722.00 | 87148.87 |
March | 1688851.35 | 27-MAR-15:20 | 212815.01 | 660080.29 | 0.00 | 82829.33 | 212578.92 | 51078.59 | 0.00 | 382320.34 | 87148.87 |
April | 1879455.53 | 28-APR-15:09 | 212815.01 | 778371.69 | 0.00 | 82829.33 | 214207.98 | 51047.19 | 0.00 | 453035.46 | 87148.87 |
May | 1537866.58 | 31-MAY-15:00 | 212815.01 | 423497.50 | 0.00 | 82829.33 | 221399.13 | 52233.17 | 0.00 | 457943.57 | 87148.87 |
June | 1736073.98 | 12-JUN-15:09 | 212815.01 | 541788.89 | 0.00 | 82829.33 | 238502.65 | 52603.39 | 0.00 | 520385.83 | 87148.87 |
July | 1983493.25 | 19-JUL-15:20 | 212815.01 | 660080.29 | 0.00 | 82829.33 | 239465.13 | 53848.11 | 0.00 | 647306.51 | 87148.87 |
August | 2157924.09 | 10-AUG-15:20 | 212815.01 | 778371.69 | 0.00 | 82829.33 | 261953.67 | 53922.95 | 0.00 | 680882.57 | 87148.87 |
September | 1602902.92 | 07-SEP-15:20 | 212815.01 | 423497.50 | 0.00 | 82829.33 | 227138.07 | 53071.63 | 0.00 | 516402.51 | 87148.87 |
October | 1650213.29 | 06-OCT-15:39 | 212815.01 | 541788.89 | 0.00 | 82829.33 | 206160.95 | 51813.69 | 0.00 | 467656.55 | 87148.87 |
November | 1750515.34 | 01-NOV-15:09 | 212815.01 | 660080.29 | 0.00 | 82829.33 | 188259.39 | 51410.59 | 0.00 | 467971.85 | 87148.87 |
December | 1737137.06 | 06-DEC-16:49 | 220406.23 | 778371.69 | 0.00 | 82832.35 | 130199.60 | 50357.57 | 0.00 | 387820.75 | 87148.87 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1134758.32 | 212815.01 | 423497.50 | 0.00 | 37438.14 | 112992.94 | 27296.93 | 0.00 | 233568.92 | 87148.87 | |
Maximum of Months | 2157924.09 | 220406.23 | 778371.69 | 0.00 | 82832.35 | 261953.67 | 53922.95 | 0.00 | 680882.57 | 87148.87 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 463.53 | 20-JAN-06:00 | 0.00 | 69578.68 | 11-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 178.69 | 13-FEB-06:00 | 0.00 | 69104.48 | 01-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 65496.04 | 10-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 60758.66 | 06-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 55099.20 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 47835.25 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 43824.51 | 31-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 48858.51 | 30-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 56011.87 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 62860.91 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 67136.79 | 29-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 70.60 | 18-DEC-06:49 | 0.00 | 69368.59 | 29-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43824.51 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 463.53 | 0.00 | 69578.68 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.20 | 2.17 | 27.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.18 | 3.00 | 27.22 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.75 | 0.00 | 26.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.59 | 0.00 | 26.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.57 | 0.00 | 26.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.01 | 0.00 | 26.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.24 | 1.00 | 26.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 25.81 | 0.50 | 25.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.14 | 0.50 | 26.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.20 | 0.33 | 26.20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.66 | 0.83 | 26.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.00 | 3.17 | 27.04 |
Annual Sum or Average | 0.00 | 0.00 | 111.67 | 26.62 | 11.50 | 26.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.81 | 0.00 | 25.80 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 27.20 | 3.17 | 27.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.71 | 0.00 | 25.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.73 | 0.00 | 25.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.61 | 0.00 | 25.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.75 | 0.00 | 25.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.66 | 0.50 | 25.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.65 | 0.00 | 25.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.67 | 0.00 | 25.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.71 | 0.00 | 25.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
Annual Sum or Average | 0.00 | 0.00 | 16.00 | 25.67 | 0.50 | 25.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 25.75 | 0.50 | 25.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.63 | 0.00 | 25.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 25.62 | 0.00 | 25.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.66 | 0.00 | 25.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.68 | 0.00 | 25.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.14 | 3.17 | 27.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.22 | 9.17 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.06 | 9.67 | 27.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 49.00 | 27.33 | 16.67 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 | 27.29 | 16.33 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 27.14 | 10.00 | 27.30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.05 | 6.33 | 27.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.71 | 0.00 | 25.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 187.83 | 27.23 | 71.33 | 27.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 | 27.33 | 16.67 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.33 | 0.67 | 27.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.44 | 2.00 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.48 | 9.33 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 27.45 | 12.17 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.24 | 10.83 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 27.46 | 17.00 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 43.17 | 27.29 | 13.67 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.37 | 12.83 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.40 | 13.33 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.27 | 2.83 | 27.32 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 201.33 | 27.37 | 94.83 | 27.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 27.48 | 17.00 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.40 | 4.50 | 27.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.57 | 4.83 | 27.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.33 | 4.00 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.30 | 8.17 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.22 | 9.33 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 27.04 | 8.83 | 27.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 27.33 | 15.67 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 27.33 | 17.00 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 27.29 | 11.33 | 27.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 27.44 | 13.00 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 27.69 | 12.17 | 27.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.63 | 8.17 | 27.63 |
Annual Sum or Average | 0.00 | 0.00 | 252.50 | 27.34 | 117.00 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.04 | 4.00 | 27.21 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 | 27.69 | 17.00 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.46 | 1.50 | 27.46 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.28 | 4.17 | 27.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.16 | 7.00 | 27.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 27.61 | 18.67 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 48.33 | 27.41 | 14.50 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 75.50 | 27.55 | 20.00 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 88.17 | 27.93 | 26.17 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 83.33 | 28.27 | 25.50 | 28.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 27.46 | 17.17 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 52.50 | 27.39 | 17.33 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 27.35 | 15.00 | 27.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.24 | 11.17 | 27.39 |
Annual Sum or Average | 0.00 | 0.00 | 543.33 | 27.65 | 178.17 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.16 | 1.50 | 27.32 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 88.17 | 28.27 | 26.17 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.38 | 2.67 | 27.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 27.27 | 9.17 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.09 | 9.17 | 27.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 27.34 | 15.67 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 27.20 | 11.17 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.21 | 9.67 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.37 | 6.33 | 27.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 161.67 | 27.25 | 63.83 | 27.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 27.38 | 15.67 | 27.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.67 | 27.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.42 | 2.00 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.65 | 11.00 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 27.48 | 13.00 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 31.67 | 27.27 | 10.83 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 55.83 | 27.54 | 18.17 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 | 27.40 | 14.17 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 27.36 | 12.67 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.50 | 13.67 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.39 | 5.17 | 27.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 238.33 | 27.44 | 101.33 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 55.83 | 27.65 | 18.17 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.40 | 3.17 | 27.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.68 | 3.17 | 27.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.43 | 3.33 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.55 | 7.00 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.27 | 9.00 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.02 | 8.67 | 27.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 27.32 | 15.17 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 27.27 | 11.83 | 27.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 27.32 | 11.83 | 27.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.47 | 12.67 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.79 | 11.83 | 27.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.64 | 5.83 | 27.64 |
Annual Sum or Average | 0.00 | 0.00 | 223.67 | 27.35 | 103.50 | 27.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.02 | 3.17 | 27.22 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 27.79 | 15.17 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.60 | 1.00 | 27.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.26 | 2.33 | 27.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 27.49 | 7.67 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 27.38 | 11.67 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 43.50 | 27.36 | 11.17 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 73.67 | 27.59 | 21.50 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 70.00 | 27.56 | 18.33 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 41.33 | 27.38 | 12.67 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.29 | 10.50 | 27.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.55 | 5.83 | 27.61 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
Annual Sum or Average | 0.00 | 0.00 | 318.67 | 27.47 | 103.00 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 73.67 | 27.60 | 21.50 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.31 | 1.00 | 27.31 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.51 | 3.83 | 27.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.45 | 10.33 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 27.28 | 9.67 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 56.17 | 27.50 | 17.17 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 | 27.37 | 12.67 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 27.37 | 10.33 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.43 | 8.33 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.33 | 0.83 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 202.00 | 27.41 | 74.17 | 27.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 56.17 | 27.51 | 17.17 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.37 | 1.00 | 27.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.52 | 2.00 | 27.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.71 | 10.83 | 27.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 | 27.61 | 13.00 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 27.41 | 11.17 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 63.00 | 27.67 | 19.67 | 27.84 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 27.51 | 15.83 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.50 | 13.00 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.58 | 13.50 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.43 | 6.50 | 27.43 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 269.67 | 27.56 | 106.50 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 63.00 | 27.71 | 19.67 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.41 | 2.00 | 27.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.75 | 2.67 | 27.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.58 | 3.50 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.62 | 7.83 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.45 | 10.17 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.26 | 9.00 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 54.33 | 27.49 | 16.67 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 27.41 | 13.67 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 27.46 | 11.83 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 27.63 | 13.17 | 27.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 27.84 | 11.50 | 27.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.62 | 5.00 | 27.62 |
Annual Sum or Average | 0.00 | 0.00 | 255.67 | 27.49 | 107.00 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.26 | 2.00 | 27.41 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 54.33 | 27.84 | 16.67 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.68 | 1.17 | 27.68 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.42 | 2.67 | 27.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.57 | 8.17 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 39.33 | 27.52 | 12.83 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 | 27.46 | 12.00 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 77.17 | 27.71 | 22.17 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 72.00 | 27.66 | 19.33 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 27.48 | 13.50 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 27.42 | 10.50 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.59 | 6.67 | 27.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.50 | 27.31 |
Annual Sum or Average | 0.00 | 0.00 | 338.17 | 27.57 | 109.50 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 77.17 | 27.71 | 22.17 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 28.01 | 25.17 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.64 | 0.00 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 710.67 | 28.58 | 486.50 | 28.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 738.67 | 28.56 | 511.67 | 28.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 710.67 | 28.58 | 486.50 | 28.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.99 | 19.83 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.72 | 0.00 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 604.33 | 28.33 | 423.00 | 28.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 626.33 | 28.32 | 442.83 | 28.38 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 604.33 | 28.33 | 423.00 | 28.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 28.01 | 21.67 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.72 | 0.00 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 579.67 | 28.41 | 411.50 | 28.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 604.17 | 28.40 | 433.17 | 28.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 579.67 | 28.41 | 411.50 | 28.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 401.83 | 28.87 | 330.83 | 28.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 29.14 | 0.00 | 29.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.85 | 514.00 | 31.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 90.00 | 27.95 | 88.17 | 27.95 |
Annual Sum or Average | 0.00 | 0.00 | 1236.00 | 30.60 | 933.00 | 30.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.85 | 514.00 | 31.96 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 24.00 | 445.17 | 24.68 | 1.17 | 24.67 |
February | 56.17 | 24.97 | 432.17 | 24.65 | 56.17 | 24.68 |
March | 79.00 | 24.43 | 474.33 | 24.49 | 79.00 | 24.48 |
April | 153.17 | 24.97 | 447.00 | 24.69 | 153.17 | 24.75 |
May | 186.17 | 24.66 | 482.17 | 24.59 | 186.17 | 24.60 |
June | 316.67 | 24.77 | 496.00 | 24.60 | 316.67 | 24.65 |
July | 246.00 | 25.01 | 497.00 | 24.76 | 246.00 | 24.82 |
August | 196.00 | 25.20 | 514.00 | 24.69 | 196.00 | 24.80 |
September | 253.67 | 25.11 | 485.00 | 24.76 | 253.67 | 24.85 |
October | 138.67 | 25.32 | 490.33 | 24.80 | 138.67 | 24.89 |
November | 84.17 | 25.13 | 484.17 | 24.72 | 84.17 | 24.77 |
December | 77.00 | 25.84 | 483.33 | 24.81 | 77.00 | 24.94 |
Annual Sum or Average | 1787.83 | 25.00 | 5730.67 | 24.69 | 1787.83 | 24.75 |
Minimum of Months | 1.17 | 24.00 | 432.17 | 24.49 | 1.17 | 24.48 |
Maximum of Months | 316.67 | 25.84 | 514.00 | 24.81 | 316.67 | 24.94 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 434.17 | 24.44 | 0.00 | 24.44 |
February | 1.00 | 27.09 | 429.67 | 24.42 | 1.00 | 24.43 |
March | 0.00 | 0.00 | 480.67 | 24.29 | 0.00 | 24.29 |
April | 0.00 | 0.00 | 469.17 | 24.23 | 0.00 | 24.23 |
May | 0.00 | 0.00 | 490.33 | 24.22 | 0.00 | 24.22 |
June | 0.00 | 0.00 | 496.00 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 497.00 | 24.28 | 0.00 | 24.28 |
August | 0.00 | 0.00 | 514.00 | 24.29 | 0.00 | 24.29 |
September | 0.00 | 0.00 | 485.00 | 24.23 | 0.00 | 24.23 |
October | 0.00 | 0.00 | 492.50 | 24.28 | 0.00 | 24.28 |
November | 0.00 | 0.00 | 483.17 | 24.34 | 0.00 | 24.34 |
December | 0.00 | 0.00 | 478.17 | 24.39 | 0.00 | 24.39 |
Annual Sum or Average | 1.00 | 27.09 | 5749.83 | 24.30 | 1.00 | 24.30 |
Minimum of Months | 0.00 | 0.00 | 429.67 | 24.20 | 0.00 | 24.20 |
Maximum of Months | 1.00 | 27.09 | 514.00 | 24.44 | 1.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.33 | 24.28 | 344.17 | 24.30 | 12.67 | 24.33 |
February | 5.00 | 23.68 | 388.83 | 24.29 | 0.00 | 24.29 |
March | 0.83 | 23.63 | 424.67 | 24.29 | 0.00 | 24.29 |
April | 1.00 | 23.83 | 438.17 | 24.26 | 0.00 | 24.26 |
May | 0.00 | 0.00 | 480.50 | 24.15 | 0.00 | 24.15 |
June | 0.00 | 0.00 | 495.50 | 24.10 | 0.00 | 24.10 |
July | 0.00 | 0.00 | 496.83 | 24.11 | 0.00 | 24.11 |
August | 0.00 | 0.00 | 514.00 | 24.10 | 0.00 | 24.10 |
September | 0.00 | 0.00 | 485.00 | 24.15 | 0.00 | 24.15 |
October | 0.00 | 0.00 | 486.00 | 24.24 | 0.00 | 24.24 |
November | 0.00 | 0.00 | 481.33 | 24.30 | 0.00 | 24.30 |
December | 8.83 | 23.59 | 432.00 | 24.25 | 0.00 | 24.25 |
Annual Sum or Average | 51.00 | 24.08 | 5467.00 | 24.21 | 12.67 | 24.21 |
Minimum of Months | 0.00 | 0.00 | 344.17 | 24.10 | 0.00 | 24.10 |
Maximum of Months | 35.33 | 24.28 | 514.00 | 24.30 | 12.67 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 145.50 | 23.39 | 236.33 | 23.83 | 13.33 | 23.82 |
February | 60.50 | 23.41 | 327.50 | 24.10 | 0.00 | 24.10 |
March | 12.67 | 23.46 | 406.00 | 24.24 | 0.00 | 24.24 |
April | 0.00 | 0.00 | 444.33 | 24.29 | 0.00 | 24.29 |
May | 0.00 | 0.00 | 486.83 | 24.24 | 0.00 | 24.24 |
June | 0.00 | 0.00 | 496.00 | 24.18 | 0.00 | 24.18 |
July | 0.00 | 0.00 | 497.00 | 24.24 | 0.00 | 24.24 |
August | 0.33 | 26.60 | 514.00 | 24.20 | 0.33 | 24.20 |
September | 0.33 | 26.69 | 485.00 | 24.24 | 0.33 | 24.24 |
October | 0.00 | 0.00 | 489.50 | 24.29 | 0.00 | 24.29 |
November | 0.00 | 0.00 | 476.00 | 24.29 | 0.00 | 24.29 |
December | 60.17 | 23.42 | 355.17 | 24.07 | 0.00 | 24.07 |
Annual Sum or Average | 279.50 | 23.41 | 5213.67 | 24.19 | 14.00 | 24.19 |
Minimum of Months | 0.00 | 0.00 | 236.33 | 23.83 | 0.00 | 23.82 |
Maximum of Months | 145.50 | 26.69 | 514.00 | 24.29 | 13.33 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 80.50 | 23.38 | 277.50 | 24.06 | 0.00 | 24.06 |
February | 26.67 | 23.40 | 364.67 | 24.25 | 0.00 | 24.25 |
March | 7.00 | 23.83 | 448.00 | 24.28 | 0.50 | 24.28 |
April | 16.00 | 26.81 | 472.17 | 24.47 | 16.00 | 24.55 |
May | 40.83 | 26.87 | 506.50 | 24.68 | 40.83 | 24.83 |
June | 46.50 | 26.87 | 496.00 | 24.70 | 46.50 | 24.87 |
July | 87.83 | 26.89 | 497.00 | 24.99 | 87.83 | 25.24 |
August | 82.33 | 26.90 | 514.00 | 24.87 | 82.33 | 25.12 |
September | 47.00 | 26.86 | 485.00 | 24.73 | 47.00 | 24.90 |
October | 33.00 | 26.79 | 497.67 | 24.64 | 33.00 | 24.76 |
November | 1.67 | 27.03 | 483.83 | 24.40 | 1.67 | 24.41 |
December | 13.50 | 23.62 | 421.33 | 24.27 | 0.00 | 24.27 |
Annual Sum or Average | 482.83 | 25.96 | 5463.67 | 24.56 | 355.67 | 24.69 |
Minimum of Months | 1.67 | 23.38 | 277.50 | 24.06 | 0.00 | 24.06 |
Maximum of Months | 87.83 | 27.03 | 514.00 | 24.99 | 87.83 | 25.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.67 | 23.40 | 332.00 | 24.22 | 0.67 | 24.23 |
February | 27.33 | 23.86 | 392.50 | 24.32 | 4.00 | 24.34 |
March | 16.50 | 24.60 | 452.50 | 24.32 | 5.33 | 24.35 |
April | 37.00 | 26.86 | 471.00 | 24.60 | 37.00 | 24.76 |
May | 54.50 | 26.97 | 507.83 | 24.78 | 54.50 | 24.97 |
June | 48.67 | 26.96 | 496.00 | 24.72 | 48.67 | 24.91 |
July | 85.17 | 26.97 | 497.00 | 25.00 | 85.17 | 25.25 |
August | 73.00 | 26.94 | 514.00 | 24.84 | 73.00 | 25.07 |
September | 55.67 | 26.97 | 485.00 | 24.81 | 55.67 | 25.01 |
October | 52.67 | 26.88 | 500.00 | 24.76 | 52.67 | 24.95 |
November | 18.17 | 26.83 | 485.17 | 24.54 | 18.17 | 24.62 |
December | 18.67 | 23.34 | 418.50 | 24.24 | 0.00 | 24.24 |
Annual Sum or Average | 542.00 | 26.23 | 5551.50 | 24.63 | 434.83 | 24.78 |
Minimum of Months | 16.50 | 23.34 | 332.00 | 24.22 | 0.00 | 24.23 |
Maximum of Months | 85.17 | 26.97 | 514.00 | 25.00 | 85.17 | 25.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.33 | 24.38 | 382.00 | 24.49 | 16.33 | 24.58 |
February | 37.00 | 25.20 | 404.83 | 24.52 | 18.67 | 24.62 |
March | 22.50 | 25.99 | 470.33 | 24.44 | 16.33 | 24.52 |
April | 32.50 | 26.87 | 474.67 | 24.59 | 32.50 | 24.73 |
May | 39.50 | 26.89 | 506.50 | 24.67 | 39.50 | 24.82 |
June | 41.67 | 26.87 | 496.00 | 24.66 | 41.67 | 24.82 |
July | 80.50 | 26.89 | 497.00 | 24.96 | 80.50 | 25.20 |
August | 85.17 | 26.91 | 514.00 | 24.89 | 85.17 | 25.14 |
September | 56.83 | 26.95 | 485.00 | 24.83 | 56.83 | 25.03 |
October | 57.33 | 27.00 | 502.00 | 24.85 | 57.33 | 25.05 |
November | 51.83 | 26.95 | 488.33 | 24.80 | 51.83 | 24.98 |
December | 42.83 | 26.42 | 469.00 | 24.65 | 36.83 | 24.80 |
Annual Sum or Average | 603.00 | 26.51 | 5689.67 | 24.71 | 533.50 | 24.88 |
Minimum of Months | 22.50 | 24.38 | 382.00 | 24.44 | 16.33 | 24.52 |
Maximum of Months | 85.17 | 27.00 | 514.00 | 24.96 | 85.17 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.17 | 25.31 | 412.33 | 24.55 | 9.33 | 24.60 |
February | 25.50 | 26.93 | 442.17 | 24.70 | 25.50 | 24.82 |
March | 41.17 | 26.98 | 507.50 | 24.73 | 41.17 | 24.88 |
April | 96.67 | 26.93 | 485.00 | 25.03 | 96.67 | 25.30 |
May | 92.33 | 26.90 | 508.00 | 24.97 | 92.33 | 25.22 |
June | 96.33 | 26.92 | 496.00 | 24.96 | 96.33 | 25.24 |
July | 119.00 | 27.04 | 497.00 | 25.19 | 119.00 | 25.49 |
August | 103.33 | 27.12 | 514.00 | 25.05 | 103.33 | 25.35 |
September | 103.17 | 26.89 | 485.00 | 25.04 | 103.17 | 25.31 |
October | 105.17 | 26.89 | 502.00 | 25.06 | 105.17 | 25.33 |
November | 79.67 | 26.94 | 489.00 | 25.00 | 79.67 | 25.24 |
December | 63.00 | 26.94 | 495.17 | 24.93 | 63.00 | 25.13 |
Annual Sum or Average | 943.50 | 26.93 | 5833.17 | 24.95 | 934.67 | 25.19 |
Minimum of Months | 18.17 | 25.31 | 412.33 | 24.55 | 9.33 | 24.60 |
Maximum of Months | 119.00 | 27.12 | 514.00 | 25.19 | 119.00 | 25.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 277.33 | 23.03 | 123.33 | 23.34 | 0.00 | 23.34 |
February | 118.83 | 23.07 | 226.67 | 23.78 | 1.33 | 23.79 |
March | 57.17 | 23.24 | 365.33 | 24.11 | 0.00 | 24.11 |
April | 29.83 | 25.68 | 451.50 | 24.52 | 26.33 | 24.60 |
May | 45.00 | 26.84 | 506.50 | 24.72 | 45.00 | 24.88 |
June | 57.17 | 26.74 | 496.00 | 24.73 | 57.17 | 24.92 |
July | 89.50 | 26.84 | 497.00 | 24.99 | 89.50 | 25.23 |
August | 70.50 | 26.80 | 514.00 | 24.79 | 70.50 | 25.00 |
September | 64.00 | 26.69 | 485.00 | 24.80 | 64.00 | 24.99 |
October | 49.67 | 26.47 | 495.50 | 24.71 | 49.67 | 24.86 |
November | 5.67 | 24.32 | 464.00 | 24.35 | 2.17 | 24.35 |
December | 149.67 | 23.16 | 278.67 | 23.78 | 7.67 | 23.78 |
Annual Sum or Average | 1014.33 | 24.53 | 4903.50 | 24.46 | 413.33 | 24.60 |
Minimum of Months | 5.67 | 23.03 | 123.33 | 23.34 | 0.00 | 23.34 |
Maximum of Months | 277.33 | 26.84 | 514.00 | 24.99 | 89.50 | 25.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 127.50 | 23.08 | 178.17 | 23.78 | 0.17 | 23.78 |
February | 56.50 | 23.21 | 274.67 | 24.16 | 3.17 | 24.18 |
March | 38.33 | 24.09 | 344.00 | 24.39 | 8.83 | 24.45 |
April | 56.50 | 26.66 | 395.33 | 24.90 | 55.00 | 25.10 |
May | 63.00 | 26.97 | 430.00 | 24.99 | 63.00 | 25.21 |
June | 63.17 | 26.89 | 418.00 | 24.93 | 63.17 | 25.16 |
July | 99.17 | 26.95 | 422.00 | 25.22 | 99.17 | 25.50 |
August | 82.50 | 26.90 | 433.00 | 25.01 | 82.50 | 25.27 |
September | 71.50 | 26.92 | 410.00 | 25.05 | 71.50 | 25.29 |
October | 67.83 | 26.83 | 426.50 | 25.02 | 67.83 | 25.24 |
November | 26.17 | 26.66 | 409.50 | 24.72 | 25.17 | 24.83 |
December | 73.17 | 23.29 | 288.33 | 24.10 | 8.00 | 24.11 |
Annual Sum or Average | 825.33 | 25.59 | 4429.50 | 24.76 | 547.50 | 24.96 |
Minimum of Months | 26.17 | 23.08 | 178.17 | 23.78 | 0.17 | 23.78 |
Maximum of Months | 127.50 | 26.97 | 433.00 | 25.22 | 99.17 | 25.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 95.17 | 23.68 | 344.17 | 24.30 | 14.50 | 24.38 |
February | 62.50 | 24.09 | 375.33 | 24.36 | 17.17 | 24.46 |
March | 36.83 | 24.46 | 430.83 | 24.39 | 12.00 | 24.45 |
April | 46.00 | 26.35 | 462.00 | 24.67 | 44.50 | 24.81 |
May | 41.83 | 26.85 | 506.33 | 24.71 | 41.83 | 24.86 |
June | 53.33 | 26.67 | 496.00 | 24.70 | 53.33 | 24.87 |
July | 87.50 | 26.82 | 497.00 | 24.97 | 87.50 | 25.21 |
August | 76.17 | 26.83 | 514.00 | 24.82 | 76.17 | 25.05 |
September | 74.33 | 26.86 | 485.00 | 24.91 | 74.33 | 25.14 |
October | 77.17 | 26.93 | 502.00 | 24.97 | 77.17 | 25.20 |
November | 52.83 | 26.93 | 487.00 | 24.82 | 52.17 | 25.01 |
December | 75.67 | 24.92 | 420.67 | 24.55 | 38.67 | 24.70 |
Annual Sum or Average | 779.33 | 25.91 | 5520.33 | 24.70 | 589.33 | 24.88 |
Minimum of Months | 36.83 | 23.68 | 344.17 | 24.30 | 12.00 | 24.38 |
Maximum of Months | 95.17 | 26.93 | 514.00 | 24.97 | 87.50 | 25.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 146.17 | 23.17 | 255.17 | 23.87 | 2.17 | 23.88 |
February | 62.17 | 23.38 | 341.67 | 24.17 | 5.17 | 24.20 |
March | 29.67 | 24.62 | 435.67 | 24.41 | 10.67 | 24.46 |
April | 48.50 | 26.68 | 475.17 | 24.76 | 48.50 | 24.92 |
May | 72.67 | 26.95 | 507.67 | 24.90 | 72.67 | 25.13 |
June | 86.67 | 26.87 | 496.00 | 24.90 | 86.67 | 25.16 |
July | 114.33 | 26.93 | 497.00 | 25.12 | 114.33 | 25.41 |
August | 97.33 | 26.92 | 514.00 | 24.94 | 97.33 | 25.22 |
September | 91.67 | 26.90 | 485.00 | 24.99 | 91.67 | 25.25 |
October | 72.33 | 26.87 | 499.33 | 24.93 | 72.33 | 25.15 |
November | 29.33 | 26.77 | 486.50 | 24.63 | 28.33 | 24.75 |
December | 65.17 | 23.56 | 377.67 | 24.21 | 11.67 | 24.24 |
Annual Sum or Average | 916.00 | 25.74 | 5370.83 | 24.71 | 641.50 | 24.91 |
Minimum of Months | 29.33 | 23.17 | 255.17 | 23.87 | 2.17 | 23.88 |
Maximum of Months | 146.17 | 26.95 | 514.00 | 25.12 | 114.33 | 25.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 328.33 | 22.66 | 104.67 | 22.99 | 0.00 | 22.99 |
February | 173.67 | 22.84 | 199.83 | 23.53 | 1.67 | 23.54 |
March | 87.33 | 23.10 | 344.00 | 24.00 | 1.17 | 24.01 |
April | 50.33 | 25.32 | 438.00 | 24.54 | 37.00 | 24.65 |
May | 53.33 | 26.86 | 505.50 | 24.77 | 53.33 | 24.95 |
June | 62.50 | 26.75 | 496.00 | 24.76 | 62.50 | 24.96 |
July | 95.83 | 26.89 | 497.00 | 25.03 | 95.83 | 25.29 |
August | 78.33 | 26.82 | 514.00 | 24.83 | 78.33 | 25.07 |
September | 72.00 | 26.69 | 485.00 | 24.84 | 72.00 | 25.05 |
October | 55.00 | 26.48 | 492.67 | 24.74 | 55.00 | 24.90 |
November | 26.83 | 23.99 | 448.67 | 24.33 | 8.00 | 24.35 |
December | 197.83 | 22.84 | 243.00 | 23.52 | 12.83 | 23.52 |
Annual Sum or Average | 1281.33 | 24.21 | 4768.33 | 24.40 | 477.67 | 24.56 |
Minimum of Months | 26.83 | 22.66 | 104.67 | 22.99 | 0.00 | 22.99 |
Maximum of Months | 328.33 | 26.89 | 514.00 | 25.03 | 95.83 | 25.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 195.67 | 22.82 | 184.67 | 23.48 | 0.00 | 23.48 |
February | 91.83 | 23.02 | 287.67 | 23.96 | 5.83 | 24.00 |
March | 62.17 | 23.62 | 401.00 | 24.23 | 8.50 | 24.28 |
April | 63.50 | 26.28 | 463.50 | 24.75 | 55.83 | 24.94 |
May | 66.00 | 27.00 | 508.00 | 24.87 | 66.00 | 25.09 |
June | 70.00 | 26.87 | 496.00 | 24.83 | 70.00 | 25.05 |
July | 104.00 | 26.99 | 497.00 | 25.10 | 104.00 | 25.38 |
August | 86.33 | 26.94 | 514.00 | 24.90 | 86.33 | 25.16 |
September | 77.00 | 26.91 | 485.00 | 24.93 | 77.00 | 25.17 |
October | 71.00 | 26.83 | 501.33 | 24.90 | 71.00 | 25.11 |
November | 36.33 | 26.13 | 471.67 | 24.61 | 30.67 | 24.72 |
December | 121.67 | 23.08 | 311.83 | 23.88 | 14.00 | 23.89 |
Annual Sum or Average | 1045.50 | 25.10 | 5121.67 | 24.61 | 589.17 | 24.80 |
Minimum of Months | 36.33 | 22.82 | 184.67 | 23.48 | 0.00 | 23.48 |
Maximum of Months | 195.67 | 27.00 | 514.00 | 25.10 | 104.00 | 25.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 132.50 | 23.11 | 310.50 | 24.03 | 12.33 | 24.11 |
February | 85.67 | 23.55 | 351.17 | 24.21 | 17.17 | 24.31 |
March | 65.67 | 23.93 | 408.50 | 24.31 | 14.33 | 24.38 |
April | 59.00 | 25.81 | 450.67 | 24.65 | 47.50 | 24.80 |
May | 51.33 | 26.87 | 505.17 | 24.76 | 51.33 | 24.94 |
June | 60.00 | 26.67 | 496.00 | 24.73 | 60.00 | 24.92 |
July | 94.17 | 26.87 | 497.00 | 25.02 | 94.17 | 25.27 |
August | 82.67 | 26.86 | 514.00 | 24.86 | 82.67 | 25.11 |
September | 79.83 | 26.87 | 485.00 | 24.93 | 79.83 | 25.17 |
October | 78.83 | 26.92 | 502.00 | 24.97 | 78.83 | 25.21 |
November | 54.67 | 26.80 | 478.50 | 24.80 | 52.67 | 24.99 |
December | 97.00 | 24.11 | 387.33 | 24.38 | 34.83 | 24.51 |
Annual Sum or Average | 941.33 | 25.47 | 5385.83 | 24.67 | 625.67 | 24.86 |
Minimum of Months | 51.33 | 23.11 | 310.50 | 24.03 | 12.33 | 24.11 |
Maximum of Months | 132.50 | 26.92 | 514.00 | 25.02 | 94.17 | 25.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 196.67 | 22.81 | 215.33 | 23.56 | 2.67 | 23.58 |
February | 97.00 | 23.10 | 316.67 | 24.01 | 6.17 | 24.05 |
March | 55.17 | 24.00 | 408.33 | 24.33 | 11.50 | 24.39 |
April | 52.83 | 26.55 | 464.50 | 24.77 | 51.33 | 24.94 |
May | 77.00 | 26.97 | 507.00 | 24.93 | 77.00 | 25.16 |
June | 90.17 | 26.88 | 496.00 | 24.92 | 90.17 | 25.18 |
July | 115.00 | 26.97 | 497.00 | 25.14 | 115.00 | 25.43 |
August | 97.33 | 26.96 | 514.00 | 24.96 | 97.33 | 25.23 |
September | 95.00 | 26.90 | 485.00 | 25.01 | 95.00 | 25.27 |
October | 74.17 | 26.84 | 498.50 | 24.94 | 74.17 | 25.15 |
November | 35.50 | 26.47 | 473.33 | 24.63 | 32.17 | 24.76 |
December | 113.00 | 23.32 | 336.67 | 24.05 | 19.33 | 24.10 |
Annual Sum or Average | 1098.83 | 25.30 | 5212.33 | 24.67 | 671.83 | 24.87 |
Minimum of Months | 35.50 | 22.81 | 215.33 | 23.56 | 2.67 | 23.58 |
Maximum of Months | 196.67 | 26.97 | 514.00 | 25.14 | 115.00 | 25.43 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 2.17 | 27.00 | 454.00 | 27.00 | 2.17 | 27.00 |
March | 15.17 | 27.00 | 514.00 | 27.00 | 15.17 | 27.00 |
April | 229.67 | 27.17 | 485.00 | 27.11 | 229.67 | 27.12 |
May | 20.50 | 27.00 | 508.00 | 27.00 | 20.50 | 27.00 |
June | 142.17 | 27.00 | 496.00 | 27.00 | 142.17 | 27.00 |
July | 367.67 | 27.00 | 497.00 | 27.00 | 367.67 | 27.00 |
August | 514.00 | 28.61 | 514.00 | 28.61 | 514.00 | 28.61 |
September | 82.17 | 27.00 | 485.00 | 27.00 | 82.17 | 27.00 |
October | 58.00 | 27.00 | 502.00 | 27.00 | 58.00 | 27.00 |
November | 75.83 | 27.00 | 489.00 | 27.00 | 75.83 | 27.00 |
December | 81.67 | 27.00 | 497.00 | 27.00 | 81.67 | 27.00 |
Annual Sum or Average | 1589.00 | 27.55 | 5943.00 | 27.23 | 1589.00 | 27.29 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 514.00 | 28.61 | 514.00 | 28.61 | 514.00 | 28.61 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 34.50 | 27.73 | 485.00 | 27.10 | 34.50 | 27.14 |
May | 3.17 | 27.00 | 508.00 | 27.00 | 3.17 | 27.00 |
June | 10.67 | 27.00 | 496.00 | 27.00 | 10.67 | 27.00 |
July | 40.17 | 27.00 | 497.00 | 27.00 | 40.17 | 27.00 |
August | 450.67 | 28.42 | 514.00 | 28.34 | 450.67 | 28.36 |
September | 13.50 | 27.00 | 485.00 | 27.00 | 13.50 | 27.00 |
October | 2.33 | 27.00 | 502.00 | 27.00 | 2.33 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 555.00 | 28.20 | 5943.00 | 27.21 | 555.00 | 27.29 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 450.67 | 28.42 | 514.00 | 28.34 | 450.67 | 28.36 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 1.83 | 27.00 | 514.00 | 27.00 | 1.83 | 27.00 |
April | 52.83 | 27.56 | 485.00 | 27.11 | 52.83 | 27.15 |
May | 26.67 | 27.00 | 508.00 | 27.00 | 26.67 | 27.00 |
June | 56.33 | 27.00 | 496.00 | 27.00 | 56.33 | 27.00 |
July | 149.50 | 27.00 | 497.00 | 27.00 | 149.50 | 27.00 |
August | 447.17 | 28.45 | 514.00 | 28.36 | 447.17 | 28.39 |
September | 52.33 | 27.00 | 485.00 | 27.00 | 52.33 | 27.00 |
October | 20.83 | 27.00 | 502.00 | 27.00 | 20.83 | 27.00 |
November | 7.33 | 27.00 | 489.00 | 27.00 | 7.33 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 814.83 | 27.83 | 5943.00 | 27.20 | 814.83 | 27.27 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 447.17 | 28.45 | 514.00 | 28.36 | 447.17 | 28.39 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 28.41 | 485.00 | 28.41 | 485.00 | 28.41 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 32.12 | 514.00 | 32.12 | 514.00 | 32.12 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.21 | 497.00 | 27.21 | 497.00 | 27.21 |
Annual Sum or Average | 5943.00 | 27.58 | 5943.00 | 27.58 | 5943.00 | 27.58 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 32.12 | 514.00 | 32.12 | 514.00 | 32.12 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00100 | 31.66751 | 0.89560 | 21.96491 |
February | 454.00000 | 27.00155 | 31.35865 | 0.93624 | 23.53906 |
March | 514.00000 | 27.00085 | 31.27471 | 0.97499 | 25.10075 |
April | 485.00000 | 27.07892 | 32.13472 | 1.04395 | 28.08091 |
May | 508.00000 | 27.00060 | 36.73052 | 0.32836 | 7.29709 |
June | 496.00000 | 27.00250 | 37.00898 | 0.38677 | 8.15624 |
July | 497.00000 | 27.00116 | 36.83336 | 0.44376 | 9.15040 |
August | 514.00000 | 28.61214 | 35.38652 | 0.91947 | 23.57072 |
September | 485.00000 | 27.00017 | 40.41942 | 0.36904 | 7.88276 |
October | 502.00000 | 27.00229 | 35.10985 | 1.00117 | 26.19471 |
November | 489.00000 | 27.00118 | 32.70048 | 1.00036 | 26.15770 |
December | 497.00000 | 27.00035 | 30.84766 | 0.99790 | 26.05437 |
Annual Sum or Average | 5943.00000 | 27.14684 | 34.30174 | 0.77412 | 19.41152 |
Minimum of Months | 454.00000 | 27.00017 | 30.84766 | 0.32836 | 7.29709 |
Maximum of Months | 514.00000 | 28.61214 | 40.41942 | 1.04395 | 28.08091 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00047 | 32.05872 | 0.83820 | 19.86841 |
February | 454.00000 | 27.00147 | 31.50156 | 0.86548 | 20.84605 |
March | 514.00000 | 27.00082 | 31.31436 | 0.90001 | 22.13694 |
April | 485.00000 | 27.06060 | 32.18363 | 0.95504 | 24.33360 |
May | 508.00000 | 27.00046 | 36.95964 | 0.28314 | 6.71756 |
June | 496.00000 | 27.00249 | 37.17424 | 0.31660 | 7.12482 |
July | 497.00000 | 27.00126 | 36.95268 | 0.35036 | 7.59599 |
August | 514.00000 | 28.26847 | 35.72051 | 0.67736 | 15.46275 |
September | 485.00000 | 27.00010 | 40.84410 | 0.31934 | 7.16636 |
October | 502.00000 | 27.00221 | 35.26153 | 0.94987 | 24.08323 |
November | 489.00000 | 27.00117 | 32.76871 | 0.92751 | 23.19646 |
December | 497.00000 | 27.00036 | 30.88217 | 0.89102 | 21.79640 |
Annual Sum or Average | 5943.00000 | 27.11555 | 34.48134 | 0.68833 | 16.66314 |
Minimum of Months | 454.00000 | 27.00010 | 30.88217 | 0.28314 | 6.71756 |
Maximum of Months | 514.00000 | 28.26847 | 40.84410 | 0.95504 | 24.33360 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00040 | 32.30826 | 0.81670 | 19.16066 |
February | 454.00000 | 27.00148 | 31.54082 | 0.85269 | 20.41971 |
March | 514.00000 | 27.00084 | 31.30999 | 0.89610 | 22.01962 |
April | 485.00000 | 27.06617 | 32.16388 | 0.96109 | 24.61822 |
May | 508.00000 | 27.00054 | 36.87506 | 0.30412 | 7.02348 |
June | 496.00000 | 27.00250 | 37.11224 | 0.33980 | 7.48752 |
July | 497.00000 | 27.00124 | 36.90493 | 0.37969 | 8.09006 |
August | 514.00000 | 28.28293 | 35.67211 | 0.70529 | 16.59191 |
September | 485.00000 | 27.00014 | 40.71293 | 0.33852 | 7.47535 |
October | 502.00000 | 27.00224 | 35.23811 | 0.95738 | 24.40459 |
November | 489.00000 | 27.00119 | 32.76612 | 0.92512 | 23.12498 |
December | 497.00000 | 27.00040 | 30.88583 | 0.87502 | 21.23406 |
Annual Sum or Average | 5943.00000 | 27.11727 | 34.47025 | 0.69496 | 16.77872 |
Minimum of Months | 454.00000 | 27.00014 | 30.88583 | 0.30412 | 7.02348 |
Maximum of Months | 514.00000 | 28.28293 | 40.71293 | 0.96109 | 24.61822 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00347 | 30.98863 | 1.11712 | 31.30799 |
February | 454.00000 | 27.00328 | 31.16862 | 1.25991 | 38.22983 |
March | 514.00000 | 27.00186 | 31.59710 | 1.39368 | 45.17776 |
April | 485.00000 | 28.41143 | 31.62055 | 1.80450 | 66.46868 |
May | 508.00000 | 27.00316 | 34.92439 | 0.56499 | 11.74423 |
June | 496.00000 | 27.00305 | 35.61274 | 0.78771 | 18.09246 |
July | 497.00000 | 27.00117 | 35.97125 | 1.00440 | 26.31835 |
August | 514.00000 | 32.12072 | 32.85188 | 2.71543 | 95.75428 |
September | 485.00000 | 27.00385 | 36.93277 | 0.64163 | 13.71627 |
October | 502.00000 | 27.00281 | 34.05000 | 1.32086 | 41.35093 |
November | 489.00000 | 27.00130 | 32.48847 | 1.44221 | 47.77503 |
December | 497.00000 | 27.21281 | 31.09355 | 1.58918 | 55.73640 |
Annual Sum or Average | 5943.00000 | 27.57785 | 33.28263 | 1.30680 | 41.09760 |
Minimum of Months | 454.00000 | 27.00117 | 30.98863 | 0.56499 | 11.74423 |
Maximum of Months | 514.00000 | 32.12072 | 36.93277 | 2.71543 | 95.75428 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.60100 | 49.02582 | 0.59403 | 13.03964 |
February | 454.00000 | 24.57597 | 54.02432 | 0.62209 | 13.77246 |
March | 514.00000 | 24.45983 | 52.51200 | 0.58370 | 12.68285 |
April | 485.00000 | 24.55253 | 56.08793 | 0.62861 | 14.04245 |
May | 508.00000 | 24.52847 | 57.73553 | -0.2099 | 7.17271 |
June | 496.00000 | 24.49186 | 62.64423 | -0.1764 | 7.03137 |
July | 497.00000 | 24.63677 | 61.49172 | -0.1285 | 7.04751 |
August | 514.00000 | 24.49265 | 60.88907 | -0.1495 | 6.91488 |
September | 485.00000 | 24.58010 | 62.68879 | -0.1339 | 7.07622 |
October | 502.00000 | 24.63330 | 58.16400 | 0.68348 | 15.76048 |
November | 489.00000 | 24.63811 | 56.71670 | 0.67359 | 15.19115 |
December | 497.00000 | 24.63232 | 54.46912 | 0.65042 | 14.67630 |
Annual Sum or Average | 5943.00000 | 24.56793 | 57.21006 | 0.29977 | 11.16989 |
Minimum of Months | 454.00000 | 24.45983 | 49.02582 | -0.2099 | 6.91488 |
Maximum of Months | 514.00000 | 24.63811 | 62.68879 | 0.68348 | 15.76048 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.38296 | 49.94446 | 0.54729 | 11.62104 |
February | 454.00000 | 24.39133 | 53.36782 | 0.58324 | 12.49230 |
March | 514.00000 | 24.27371 | 51.17821 | 0.55257 | 11.61107 |
April | 485.00000 | 24.22724 | 52.89662 | 0.56658 | 11.87201 |
May | 508.00000 | 24.20957 | 54.44457 | -0.2947 | 7.04400 |
June | 496.00000 | 24.20350 | 56.35246 | -0.2690 | 6.71433 |
July | 497.00000 | 24.28027 | 55.59490 | -0.2351 | 6.45956 |
August | 514.00000 | 24.29254 | 55.01237 | -0.2042 | 6.32711 |
September | 485.00000 | 24.22895 | 56.73827 | -0.2644 | 6.71220 |
October | 502.00000 | 24.27211 | 55.18357 | 0.59283 | 12.53778 |
November | 489.00000 | 24.34033 | 55.83713 | 0.60971 | 13.01065 |
December | 497.00000 | 24.37865 | 53.65543 | 0.59527 | 12.72258 |
Annual Sum or Average | 5943.00000 | 24.28944 | 54.17610 | 0.22829 | 9.90025 |
Minimum of Months | 454.00000 | 24.20350 | 49.94446 | -0.2947 | 6.32711 |
Maximum of Months | 514.00000 | 24.39133 | 56.73827 | 0.60971 | 13.01065 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18131 | 51.50076 | 0.47823 | 10.07546 |
February | 454.00000 | 24.23743 | 54.11062 | 0.51748 | 10.81469 |
March | 514.00000 | 24.23599 | 51.69129 | 0.51338 | 10.71193 |
April | 485.00000 | 24.23733 | 53.57243 | 0.53668 | 11.22524 |
May | 508.00000 | 24.13923 | 54.81941 | -0.3433 | 7.58936 |
June | 496.00000 | 24.10104 | 57.09542 | -0.3346 | 7.38791 |
July | 497.00000 | 24.11191 | 56.78712 | -0.3293 | 7.31086 |
August | 514.00000 | 24.10360 | 57.30250 | -0.3216 | 7.20718 |
September | 485.00000 | 24.15023 | 57.34248 | -0.3204 | 7.24422 |
October | 502.00000 | 24.23699 | 55.71895 | 0.55961 | 11.70306 |
November | 489.00000 | 24.29361 | 56.50202 | 0.57094 | 12.00823 |
December | 497.00000 | 24.21743 | 54.77762 | 0.51994 | 10.85897 |
Annual Sum or Average | 5943.00000 | 24.18650 | 55.09874 | 0.16708 | 9.49571 |
Minimum of Months | 454.00000 | 24.10104 | 51.50076 | -0.3433 | 7.20718 |
Maximum of Months | 514.00000 | 24.29361 | 57.34248 | 0.57094 | 12.00823 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.87537 | 53.42991 | 0.40040 | 8.72165 |
February | 454.00000 | 24.06871 | 55.01064 | 0.47361 | 9.95739 |
March | 514.00000 | 24.17654 | 52.16168 | 0.50002 | 10.42916 |
April | 485.00000 | 24.26403 | 53.67627 | 0.55005 | 11.54694 |
May | 508.00000 | 24.23170 | 54.63997 | -0.2909 | 7.10068 |
June | 496.00000 | 24.17937 | 56.90601 | -0.2829 | 6.88547 |
July | 497.00000 | 24.24258 | 56.37804 | -0.2559 | 6.70293 |
August | 514.00000 | 24.19525 | 57.07581 | -0.2619 | 6.70071 |
September | 485.00000 | 24.23524 | 57.19552 | -0.2714 | 6.88065 |
October | 502.00000 | 24.28627 | 55.80360 | 0.58013 | 12.24479 |
November | 489.00000 | 24.27647 | 56.95609 | 0.56717 | 11.88435 |
December | 497.00000 | 24.02531 | 55.75705 | 0.46865 | 9.88464 |
Annual Sum or Average | 5943.00000 | 24.17173 | 55.40907 | 0.17832 | 9.06373 |
Minimum of Months | 454.00000 | 23.87537 | 52.16168 | -0.2909 | 6.70071 |
Maximum of Months | 514.00000 | 24.28627 | 57.19552 | 0.58013 | 12.24479 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04300 | 50.34900 | 0.43132 | 9.23714 |
February | 454.00000 | 24.20770 | 53.27073 | 0.51486 | 10.86641 |
March | 514.00000 | 24.23721 | 50.57909 | 0.53742 | 11.29860 |
April | 485.00000 | 24.38344 | 51.87828 | 0.62396 | 13.65647 |
May | 508.00000 | 24.50111 | 52.70057 | -0.1032 | 6.51016 |
June | 496.00000 | 24.49377 | 54.87915 | -0.0500 | 6.39310 |
July | 497.00000 | 24.65698 | 53.99743 | 0.02444 | 6.84542 |
August | 514.00000 | 24.54478 | 53.82560 | 0.01129 | 6.61289 |
September | 485.00000 | 24.52137 | 55.44512 | -0.0733 | 6.53755 |
October | 502.00000 | 24.48808 | 53.99991 | 0.67723 | 15.22699 |
November | 489.00000 | 24.38724 | 55.05246 | 0.62005 | 13.39593 |
December | 497.00000 | 24.22955 | 53.72988 | 0.53018 | 11.15278 |
Annual Sum or Average | 5943.00000 | 24.39225 | 53.29581 | 0.30977 | 9.79115 |
Minimum of Months | 454.00000 | 24.04300 | 50.34900 | -0.1032 | 6.39310 |
Maximum of Months | 514.00000 | 24.65698 | 55.44512 | 0.67723 | 15.22699 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.16627 | 49.75616 | 0.47777 | 10.26316 |
February | 454.00000 | 24.26742 | 52.92169 | 0.54596 | 11.70237 |
March | 514.00000 | 24.25356 | 50.42317 | 0.55740 | 11.90483 |
April | 485.00000 | 24.41106 | 51.66442 | 0.65277 | 14.60356 |
May | 508.00000 | 24.54011 | 52.38886 | -0.0342 | 6.61014 |
June | 496.00000 | 24.50370 | 54.70794 | -0.0061 | 6.47899 |
July | 497.00000 | 24.66688 | 53.87973 | 0.06387 | 7.14415 |
August | 514.00000 | 24.53685 | 53.76404 | 0.03780 | 6.67248 |
September | 485.00000 | 24.56303 | 55.09383 | -0.0060 | 6.74357 |
October | 502.00000 | 24.53763 | 53.57151 | 0.71879 | 16.60970 |
November | 489.00000 | 24.44510 | 54.74966 | 0.65151 | 14.41666 |
December | 497.00000 | 24.20383 | 53.78125 | 0.53180 | 11.26253 |
Annual Sum or Average | 5943.00000 | 24.42539 | 53.04656 | 0.34703 | 10.34403 |
Minimum of Months | 454.00000 | 24.16627 | 49.75616 | -0.0342 | 6.47899 |
Maximum of Months | 514.00000 | 24.66688 | 55.09383 | 0.71879 | 16.60970 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.33960 | 48.90263 | 0.55680 | 12.32625 |
February | 454.00000 | 24.38361 | 52.31180 | 0.61100 | 13.50381 |
March | 514.00000 | 24.32808 | 50.06257 | 0.59872 | 12.99968 |
April | 485.00000 | 24.42879 | 51.64798 | 0.65412 | 14.60346 |
May | 508.00000 | 24.49903 | 52.70840 | -0.1030 | 6.53089 |
June | 496.00000 | 24.47762 | 54.97984 | -0.0700 | 6.39032 |
July | 497.00000 | 24.64837 | 54.03403 | 0.01612 | 6.81529 |
August | 514.00000 | 24.55134 | 53.76052 | 0.02925 | 6.68086 |
September | 485.00000 | 24.57796 | 55.06395 | 0.00247 | 6.76827 |
October | 502.00000 | 24.60624 | 53.28458 | 0.77039 | 18.37282 |
November | 489.00000 | 24.56560 | 54.10153 | 0.73806 | 17.23857 |
December | 497.00000 | 24.45080 | 52.59050 | 0.64561 | 14.52398 |
Annual Sum or Average | 5943.00000 | 24.48840 | 52.77836 | 0.36810 | 11.36552 |
Minimum of Months | 454.00000 | 24.32808 | 48.90263 | -0.1030 | 6.39032 |
Maximum of Months | 514.00000 | 24.64837 | 55.06395 | 0.77039 | 18.37282 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.41836 | 48.68735 | 0.56858 | 12.33721 |
February | 454.00000 | 24.55656 | 51.62049 | 0.67235 | 15.20667 |
March | 514.00000 | 24.53561 | 49.20590 | 0.70996 | 16.34927 |
April | 485.00000 | 24.64689 | 50.63127 | 0.81317 | 19.92184 |
May | 508.00000 | 24.61572 | 52.14046 | 0.04397 | 6.96093 |
June | 496.00000 | 24.58162 | 54.29896 | 0.11070 | 7.17657 |
July | 497.00000 | 24.74196 | 53.41442 | 0.20538 | 8.34913 |
August | 514.00000 | 24.63659 | 53.16099 | 0.27188 | 8.87538 |
September | 485.00000 | 24.64390 | 54.70568 | 0.08384 | 7.22902 |
October | 502.00000 | 24.68141 | 53.00780 | 0.81418 | 19.92097 |
November | 489.00000 | 24.67834 | 53.70374 | 0.78927 | 18.96467 |
December | 497.00000 | 24.66671 | 51.74092 | 0.73685 | 17.32890 |
Annual Sum or Average | 5943.00000 | 24.61693 | 52.18486 | 0.48302 | 13.18568 |
Minimum of Months | 454.00000 | 24.41836 | 48.68735 | 0.04397 | 6.96093 |
Maximum of Months | 514.00000 | 24.74196 | 54.70568 | 0.81418 | 19.92184 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.45158 | 52.03026 | 0.27223 | 7.28116 |
February | 454.00000 | 23.79514 | 54.78279 | 0.39470 | 8.82341 |
March | 514.00000 | 24.08727 | 51.26482 | 0.47528 | 10.12048 |
April | 485.00000 | 24.39732 | 52.91870 | 0.60368 | 13.19081 |
May | 508.00000 | 24.53012 | 52.93266 | -0.1024 | 6.66286 |
June | 496.00000 | 24.50047 | 55.73505 | -0.0555 | 6.51439 |
July | 497.00000 | 24.65311 | 55.11492 | 0.01140 | 6.90219 |
August | 514.00000 | 24.51300 | 56.04483 | -0.0253 | 6.52770 |
September | 485.00000 | 24.54728 | 56.45841 | -0.0712 | 6.70746 |
October | 502.00000 | 24.53118 | 54.97645 | 0.67511 | 15.26654 |
November | 489.00000 | 24.31796 | 56.00306 | 0.58104 | 12.36996 |
December | 497.00000 | 23.78683 | 55.87028 | 0.39809 | 8.88131 |
Annual Sum or Average | 5943.00000 | 24.26193 | 54.49661 | 0.26122 | 9.09335 |
Minimum of Months | 454.00000 | 23.45158 | 51.26482 | -0.1024 | 6.51439 |
Maximum of Months | 514.00000 | 24.65311 | 56.45841 | 0.67511 | 15.26654 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.83543 | 50.13878 | 0.37328 | 8.68840 |
February | 385.00000 | 24.10230 | 53.31520 | 0.48184 | 10.55564 |
March | 433.00000 | 24.28441 | 50.19548 | 0.54028 | 11.75266 |
April | 410.00000 | 24.61402 | 52.16591 | 0.68822 | 15.93055 |
May | 430.00000 | 24.69539 | 52.42113 | 0.00798 | 7.12100 |
June | 418.00000 | 24.63357 | 55.33831 | 0.03235 | 6.98822 |
July | 422.00000 | 24.81649 | 54.45886 | 0.10849 | 7.86274 |
August | 433.00000 | 24.65278 | 55.50250 | 0.07209 | 7.15706 |
September | 410.00000 | 24.72049 | 55.74910 | 0.03814 | 7.35763 |
October | 427.00000 | 24.73399 | 54.11047 | 0.75579 | 18.06313 |
November | 417.00000 | 24.57793 | 54.78937 | 0.66369 | 14.92586 |
December | 422.00000 | 24.06057 | 54.51757 | 0.47359 | 10.32401 |
Annual Sum or Average | 5034.00000 | 24.47883 | 53.54805 | 0.35160 | 10.54924 |
Minimum of Months | 385.00000 | 23.83543 | 50.13878 | 0.00798 | 6.98822 |
Maximum of Months | 433.00000 | 24.81649 | 55.74910 | 0.75579 | 18.06313 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.18564 | 49.03084 | 0.50493 | 11.44784 |
February | 454.00000 | 24.24021 | 52.70166 | 0.56053 | 12.45822 |
March | 514.00000 | 24.28045 | 50.28521 | 0.56719 | 12.36344 |
April | 485.00000 | 24.46555 | 52.51236 | 0.64299 | 14.38871 |
May | 508.00000 | 24.52694 | 52.94245 | -0.1027 | 6.66579 |
June | 496.00000 | 24.48258 | 55.87259 | -0.0761 | 6.50118 |
July | 497.00000 | 24.64520 | 55.15605 | 0.00405 | 6.87091 |
August | 514.00000 | 24.52705 | 55.89076 | 0.00030 | 6.60927 |
September | 485.00000 | 24.60590 | 55.91582 | 0.01113 | 6.97352 |
October | 502.00000 | 24.66780 | 53.96970 | 0.78075 | 18.86886 |
November | 489.00000 | 24.58958 | 54.52726 | 0.73144 | 17.12215 |
December | 497.00000 | 24.33884 | 53.28579 | 0.59711 | 13.50594 |
Annual Sum or Average | 5943.00000 | 24.46384 | 53.50192 | 0.34921 | 11.12208 |
Minimum of Months | 454.00000 | 24.18564 | 49.03084 | -0.1027 | 6.50118 |
Maximum of Months | 514.00000 | 24.66780 | 55.91582 | 0.78075 | 18.86886 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.87996 | 50.35438 | 0.39390 | 9.05609 |
February | 454.00000 | 24.12293 | 53.32381 | 0.50422 | 10.96794 |
March | 514.00000 | 24.30488 | 50.24036 | 0.57231 | 12.45221 |
April | 485.00000 | 24.55297 | 52.09435 | 0.69251 | 15.98324 |
May | 508.00000 | 24.60602 | 52.51312 | -0.0051 | 7.01425 |
June | 496.00000 | 24.55985 | 55.27318 | 0.03556 | 6.94295 |
July | 497.00000 | 24.70766 | 54.66835 | 0.10305 | 7.59952 |
August | 514.00000 | 24.57046 | 55.50706 | 0.08432 | 7.14649 |
September | 485.00000 | 24.63236 | 55.76262 | 0.03483 | 7.22237 |
October | 502.00000 | 24.65108 | 54.24759 | 0.75465 | 17.97964 |
November | 489.00000 | 24.50058 | 55.06041 | 0.66922 | 15.03187 |
December | 497.00000 | 24.15642 | 54.21494 | 0.51497 | 11.19851 |
Annual Sum or Average | 5943.00000 | 24.43866 | 53.59510 | 0.36096 | 10.69830 |
Minimum of Months | 454.00000 | 23.87996 | 50.24036 | -0.0051 | 6.94295 |
Maximum of Months | 514.00000 | 24.70766 | 55.76262 | 0.75465 | 17.97964 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.11339 | 53.13949 | 0.18755 | 7.08197 |
February | 454.00000 | 23.58356 | 55.57470 | 0.34302 | 8.47380 |
March | 514.00000 | 23.98920 | 51.74838 | 0.45356 | 9.93048 |
April | 485.00000 | 24.37934 | 53.23785 | 0.60650 | 13.39801 |
May | 508.00000 | 24.54634 | 53.15349 | -0.0776 | 6.82701 |
June | 496.00000 | 24.51375 | 56.02685 | -0.0290 | 6.67392 |
July | 497.00000 | 24.67235 | 55.38216 | 0.04491 | 7.24853 |
August | 514.00000 | 24.52967 | 56.37976 | 0.00534 | 6.75536 |
September | 485.00000 | 24.56202 | 56.84305 | -0.0464 | 6.90021 |
October | 502.00000 | 24.53765 | 55.41940 | 0.68644 | 15.67822 |
November | 489.00000 | 24.28328 | 56.54001 | 0.57391 | 12.32350 |
December | 497.00000 | 23.56714 | 56.82321 | 0.34338 | 8.47151 |
Annual Sum or Average | 5943.00000 | 24.19332 | 55.00589 | 0.25607 | 9.13870 |
Minimum of Months | 454.00000 | 23.11339 | 51.74838 | -0.0776 | 6.67392 |
Maximum of Months | 514.00000 | 24.67235 | 56.84305 | 0.68644 | 15.67822 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.59534 | 51.32797 | 0.31674 | 8.29643 |
February | 454.00000 | 23.91860 | 54.09737 | 0.44421 | 10.04664 |
March | 514.00000 | 24.16151 | 50.88034 | 0.52458 | 11.48711 |
April | 485.00000 | 24.49929 | 52.41363 | 0.68011 | 15.65999 |
May | 508.00000 | 24.59604 | 52.72780 | 0.01284 | 7.06221 |
June | 496.00000 | 24.54071 | 55.65521 | 0.04179 | 6.90541 |
July | 497.00000 | 24.70638 | 55.04987 | 0.11810 | 7.85610 |
August | 514.00000 | 24.55988 | 55.97568 | 0.08576 | 7.12310 |
September | 485.00000 | 24.61499 | 56.25174 | 0.04162 | 7.26657 |
October | 502.00000 | 24.62466 | 54.60863 | 0.75157 | 17.86898 |
November | 489.00000 | 24.45611 | 55.61639 | 0.64865 | 14.47768 |
December | 497.00000 | 23.87978 | 55.47428 | 0.43365 | 9.77872 |
Annual Sum or Average | 5943.00000 | 24.34832 | 54.16199 | 0.33996 | 10.30423 |
Minimum of Months | 454.00000 | 23.59534 | 50.88034 | 0.01284 | 6.90541 |
Maximum of Months | 514.00000 | 24.70638 | 56.25174 | 0.75157 | 17.86898 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.95642 | 49.82172 | 0.44094 | 10.73148 |
February | 454.00000 | 24.08965 | 53.31630 | 0.52003 | 11.92364 |
March | 514.00000 | 24.19990 | 50.73476 | 0.54841 | 12.13289 |
April | 485.00000 | 24.44379 | 52.84254 | 0.64457 | 14.55208 |
May | 508.00000 | 24.54283 | 53.16538 | -0.0781 | 6.83605 |
June | 496.00000 | 24.49863 | 56.15571 | -0.0486 | 6.64809 |
July | 497.00000 | 24.66540 | 55.42224 | 0.03797 | 7.21411 |
August | 514.00000 | 24.54167 | 56.23477 | 0.02990 | 6.86856 |
September | 485.00000 | 24.61399 | 56.32149 | 0.03292 | 7.24717 |
October | 502.00000 | 24.66683 | 54.42766 | 0.78913 | 19.22298 |
November | 489.00000 | 24.55492 | 55.02564 | 0.72360 | 16.95380 |
December | 497.00000 | 24.20046 | 53.96230 | 0.55733 | 12.84038 |
Annual Sum or Average | 5943.00000 | 24.41604 | 53.94558 | 0.34753 | 11.07480 |
Minimum of Months | 454.00000 | 23.95642 | 49.82172 | -0.0781 | 6.64809 |
Maximum of Months | 514.00000 | 24.66683 | 56.32149 | 0.78913 | 19.22298 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.61402 | 51.23825 | 0.32584 | 8.61716 |
February | 454.00000 | 23.96366 | 53.95912 | 0.46382 | 10.53457 |
March | 514.00000 | 24.23177 | 50.66406 | 0.55554 | 12.22911 |
April | 485.00000 | 24.53262 | 52.40052 | 0.69374 | 16.10554 |
May | 508.00000 | 24.61418 | 52.76640 | 0.01498 | 7.25311 |
June | 496.00000 | 24.56456 | 55.59358 | 0.05740 | 7.16844 |
July | 497.00000 | 24.71802 | 54.96556 | 0.13108 | 8.00548 |
August | 514.00000 | 24.57855 | 55.86544 | 0.10963 | 7.46005 |
September | 485.00000 | 24.63591 | 56.17376 | 0.05422 | 7.47441 |
October | 502.00000 | 24.64835 | 54.70911 | 0.76279 | 18.30700 |
November | 489.00000 | 24.46613 | 55.56921 | 0.66226 | 14.91264 |
December | 497.00000 | 23.99810 | 54.96589 | 0.47337 | 10.67343 |
Annual Sum or Average | 5943.00000 | 24.38269 | 54.06137 | 0.35707 | 10.71361 |
Minimum of Months | 454.00000 | 23.61402 | 50.66406 | 0.01498 | 7.16844 |
Maximum of Months | 514.00000 | 24.71802 | 56.17376 | 0.76279 | 18.30700 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.114946E+12 | 187038.01 | 30-JAN-14:00 | 452.25 | 0.701977E+12 | 0.00 | 0.816923E+12 | 3.41 | 7.53 | 23-JAN-06:04 | 0.00 | 0.00 |
February | 0.125941E+12 | 205589.40 | 07-FEB-16:40 | 421.33 | 0.821462E+12 | 0.00 | 0.947403E+12 | 3.76 | 7.57 | 06-FEB-13:50 | 0.00 | 0.00 |
March | 0.175339E+12 | 206124.13 | 29-MAR-10:40 | 561.10 | 0.118362E+13 | 0.00 | 0.135896E+13 | 4.61 | 7.57 | 28-MAR-05:04 | 0.00 | 0.00 |
April | 0.214834E+12 | 210704.78 | 27-APR-16:10 | 655.06 | 0.146905E+13 | 0.00 | 0.168389E+13 | 5.59 | 7.57 | 06-APR-10:00 | 0.00 | 0.00 |
May | 0.288279E+12 | 229175.76 | 29-MAY-14:30 | 699.52 | 0.195130E+13 | 0.00 | 0.223958E+13 | 6.10 | 7.57 | 08-MAY-07:20 | 0.00 | 0.00 |
June | 0.333785E+12 | 232528.17 | 19-JUN-05:03 | 688.59 | 0.220846E+13 | 0.00 | 0.254225E+13 | 6.21 | 7.56 | 02-JUN-08:70 | 0.00 | 0.00 |
July | 0.378465E+12 | 239935.54 | 19-JUL-15:30 | 697.45 | 0.246591E+13 | 0.00 | 0.284438E+13 | 6.04 | 7.57 | 03-JUL-05:05 | 0.00 | 0.00 |
August | 0.402621E+12 | 240066.01 | 03-AUG-13:50 | 722.43 | 0.260619E+13 | 0.00 | 0.300882E+13 | 6.19 | 7.49 | 07-AUG-05:04 | 0.00 | 0.00 |
September | 0.340676E+12 | 233866.11 | 09-SEP-17:42 | 681.65 | 0.223603E+13 | 0.00 | 0.257671E+13 | 6.07 | 7.57 | 26-SEP-05:04 | 0.00 | 0.00 |
October | 0.282762E+12 | 229436.94 | 01-OCT-15:40 | 692.21 | 0.190054E+13 | 0.00 | 0.218330E+13 | 5.89 | 7.58 | 30-OCT-04:13 | 0.00 | 0.00 |
November | 0.200826E+12 | 218720.15 | 07-NOV-17:10 | 603.93 | 0.136477E+13 | 0.00 | 0.156560E+13 | 5.16 | 7.57 | 13-NOV-05:14 | 0.00 | 0.00 |
December | 0.147700E+12 | 200731.83 | 04-DEC-14:40 | 547.60 | 0.965003E+12 | 0.00 | 0.111270E+13 | 4.29 | 7.57 | 12-DEC-06:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.300617E+13 | 7423.11 | 0.198743E+14 | 0.00 | 0.228805E+14 | 5.28 | 0.00 | 0.00 | ||||
Minimum of Months | 0.114946E+12 | 187038.01 | 421.33 | 0.701977E+12 | 0.00 | 0.816923E+12 | 3.41 | 7.49 | 0.00 | 0.00 | ||
Maximum of Months | 0.402621E+12 | 240066.01 | 722.43 | 0.260619E+13 | 0.00 | 0.300882E+13 | 6.21 | 7.58 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.291855E+10 | 138999.56 | 07-FEB-13:05 | 7.30 | 0.204102E+11 | 0.00 | 0.233287E+11 | 0.08 | 7.29 | 09-FEB-06:06 | 0.00 | 0.00 |
March | 0.115285E+11 | 145261.64 | 28-MAR-12:05 | 29.07 | 0.814445E+11 | 0.00 | 0.929730E+11 | 0.27 | 7.45 | 23-MAR-11:05 | 0.00 | 0.00 |
April | 0.314478E+11 | 144267.91 | 10-APR-12:05 | 77.99 | 0.220130E+12 | 0.00 | 0.251578E+12 | 0.75 | 7.50 | 24-APR-12:05 | 0.00 | 0.00 |
May | 0.976295E+11 | 222422.67 | 30-MAY-05:03 | 215.76 | 0.667034E+12 | 0.00 | 0.764663E+12 | 1.98 | 7.44 | 04-MAY-12:05 | 0.00 | 0.00 |
June | 0.169349E+12 | 232528.17 | 19-JUN-05:03 | 338.28 | 0.112749E+13 | 0.00 | 0.129684E+13 | 3.13 | 7.29 | 15-JUN-16:00 | 0.00 | 0.00 |
July | 0.226829E+12 | 239935.54 | 19-JUL-15:30 | 401.88 | 0.147826E+13 | 0.00 | 0.170509E+13 | 3.51 | 7.35 | 10-JUL-05:03 | 0.00 | 0.00 |
August | 0.259305E+12 | 240066.01 | 03-AUG-13:50 | 437.07 | 0.168314E+13 | 0.00 | 0.194244E+13 | 3.81 | 7.49 | 07-AUG-05:04 | 0.00 | 0.00 |
September | 0.178414E+12 | 233866.11 | 09-SEP-17:42 | 340.36 | 0.117471E+13 | 0.00 | 0.135312E+13 | 3.11 | 7.28 | 05-SEP-05:03 | 0.00 | 0.00 |
October | 0.997493E+11 | 219018.23 | 10-OCT-05:02 | 216.66 | 0.677599E+12 | 0.00 | 0.777349E+12 | 1.97 | 7.48 | 19-OCT-12:05 | 0.00 | 0.00 |
November | 0.440553E+11 | 168263.80 | 01-NOV-14:05 | 104.38 | 0.302753E+12 | 0.00 | 0.346809E+12 | 0.99 | 7.41 | 13-NOV-15:05 | 0.00 | 0.00 |
December | 0.495918E+10 | 152064.47 | 05-DEC-13:05 | 12.50 | 0.342717E+11 | 0.00 | 0.392309E+11 | 0.11 | 7.20 | 04-DEC-11:05 | 0.00 | 0.00 |
Annual Sum or Average | 0.112618E+13 | 2181.25 | 0.746725E+13 | 0.00 | 0.859343E+13 | 1.65 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.259305E+12 | 240066.01 | 437.07 | 0.168314E+13 | 0.00 | 0.194244E+13 | 3.81 | 7.50 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.103709E+12 | 744.00 | 43776.24 | 01-JAN-09:35 | 223207.57 | 23-JAN-14:05 | 25.32 | 21.59 | 14.73 |
February | 0.104462E+12 | 672.00 | 43776.24 | 01-FEB-00:10 | 393153.70 | 07-FEB-14:05 | 30.74 | 24.10 | 14.73 |
March | 0.117250E+12 | 744.00 | 43776.24 | 01-MAR-00:10 | 642444.16 | 31-MAR-23:25 | 37.46 | 27.88 | 14.73 |
April | 0.113468E+12 | 720.00 | 43776.24 | 01-APR-00:05 | 710532.45 | 28-APR-12:45 | 45.39 | 32.81 | 14.73 |
May | 0.117250E+12 | 744.00 | 43776.24 | 01-MAY-00:05 | 384894.17 | 31-MAY-23:23 | 37.98 | 33.56 | 14.73 |
June | 0.113468E+12 | 720.00 | 43776.24 | 01-JUN-00:05 | 545823.29 | 30-JUN-24:00 | 44.41 | 36.79 | 14.73 |
July | 0.117250E+12 | 744.00 | 43776.24 | 01-JUL-00:05 | 685722.48 | 31-JUL-23:53 | 51.40 | 40.58 | 14.73 |
August | 0.117250E+12 | 744.00 | 43776.24 | 01-AUG-00:03 | 739205.94 | 04-AUG-14:00 | 55.31 | 42.07 | 14.73 |
September | 0.113468E+12 | 720.00 | 43776.24 | 01-SEP-00:05 | 391025.63 | 30-SEP-23:15 | 39.53 | 34.83 | 14.73 |
October | 0.117250E+12 | 744.00 | 43776.24 | 01-OCT-00:05 | 516927.51 | 31-OCT-24:00 | 40.58 | 33.21 | 14.73 |
November | 0.113468E+12 | 720.00 | 43776.24 | 01-NOV-00:05 | 568375.93 | 01-NOV-14:05 | 40.34 | 30.46 | 14.73 |
December | 0.117250E+12 | 744.00 | 43776.24 | 01-DEC-00:05 | 676734.55 | 03-DEC-13:52 | 39.47 | 27.23 | 14.73 |
Annual Sum or Average | 0.136554E+13 | 8760.00 | 40.72 | 32.14 | 14.73 | ||||
Minimum of Months | 0.103709E+12 | 672.00 | 43776.24 | 223207.57 | 25.32 | 21.59 | 14.73 | ||
Maximum of Months | 0.117250E+12 | 744.00 | 43776.24 | 739205.94 | 55.31 | 42.07 | 14.73 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.323604E+10 | 398.50 | 21686.31 | 09-JAN-13:00 | 1428462.25 | 30-JAN-12:00 | 22.44 | 21.42 | 43.38 |
February | 0.715129E+10 | 388.75 | 21686.31 | 01-FEB-16:30 | 1611319.88 | 06-FEB-13:20 | 22.89 | 21.59 | 45.33 |
March | 0.128131E+11 | 498.51 | 21686.31 | 01-MAR-06:04 | 1691659.34 | 13-MAR-13:40 | 23.19 | 21.51 | 52.69 |
April | 0.279865E+11 | 602.12 | 21686.31 | 03-APR-05:03 | 1683374.90 | 07-APR-12:40 | 24.21 | 22.06 | 63.10 |
May | 0.465891E+11 | 696.21 | 21686.31 | 01-MAY-00:05 | 1660832.40 | 08-MAY-07:50 | 26.75 | 24.01 | 63.21 |
June | 0.526383E+11 | 688.59 | 21686.31 | 01-JUN-00:05 | 1652573.03 | 02-JUN-07:40 | 29.66 | 26.45 | 59.06 |
July | 0.533156E+11 | 697.45 | 21686.31 | 01-JUL-00:05 | 1754956.57 | 19-JUL-15:20 | 31.07 | 27.61 | 57.80 |
August | 0.563951E+11 | 722.43 | 21686.31 | 01-AUG-00:03 | 1754574.06 | 03-AUG-14:50 | 31.58 | 27.91 | 59.48 |
September | 0.530043E+11 | 681.65 | 21686.31 | 01-SEP-00:05 | 1666959.91 | 11-SEP-05:03 | 30.34 | 27.10 | 57.39 |
October | 0.481550E+11 | 682.57 | 21686.31 | 01-OCT-00:05 | 1643964.83 | 20-OCT-09:50 | 27.13 | 24.46 | 60.42 |
November | 0.271141E+11 | 542.15 | 21686.31 | 01-NOV-03:02 | 1645126.58 | 20-NOV-10:00 | 24.28 | 22.30 | 58.12 |
December | 0.111496E+11 | 473.59 | 21686.31 | 01-DEC-13:00 | 1539244.83 | 26-DEC-14:50 | 22.84 | 21.46 | 51.58 |
Annual Sum or Average | 0.399548E+12 | 7072.51 | 26.39 | 24.01 | 56.01 | ||||
Minimum of Months | 0.323604E+10 | 388.75 | 21686.31 | 1428462.25 | 22.44 | 21.42 | 43.38 | ||
Maximum of Months | 0.563951E+11 | 722.43 | 21686.31 | 1754956.57 | 31.58 | 27.91 | 63.21 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.136624E+09 | 1.75 | 21686.31 | 30-JAN-13:30 | 761740.69 | 30-JAN-14:30 | 22.44 | 22.43 | 0.09 |
February | 0.688984E+09 | 9.65 | 21686.31 | 06-FEB-06:06 | 1405708.62 | 06-FEB-14:05 | 22.89 | 22.84 | 0.88 |
March | 0.262343E+10 | 35.12 | 21686.31 | 01-MAR-06:06 | 1403595.95 | 23-MAR-14:20 | 23.19 | 23.02 | 2.98 |
April | 0.866393E+10 | 112.58 | 21686.31 | 03-APR-07:10 | 1486782.08 | 27-APR-09:40 | 24.21 | 23.65 | 9.47 |
May | 0.263527E+11 | 338.66 | 21686.31 | 01-MAY-05:03 | 1512228.46 | 30-MAY-05:03 | 26.75 | 25.15 | 27.41 |
June | 0.440879E+11 | 565.01 | 21686.31 | 01-JUN-05:07 | 1628576.88 | 10-JUN-05:03 | 29.66 | 26.84 | 46.36 |
July | 0.496584E+11 | 636.07 | 21686.31 | 01-JUL-00:05 | 1754956.57 | 19-JUL-15:20 | 31.07 | 27.79 | 51.70 |
August | 0.536133E+11 | 686.73 | 21686.31 | 01-AUG-00:03 | 1754574.06 | 03-AUG-14:50 | 31.58 | 28.01 | 55.93 |
September | 0.457989E+11 | 586.63 | 21686.31 | 01-SEP-00:05 | 1666959.91 | 11-SEP-05:03 | 30.34 | 27.36 | 47.64 |
October | 0.295078E+11 | 379.27 | 21686.31 | 01-OCT-00:05 | 1437394.40 | 02-OCT-05:03 | 27.13 | 25.31 | 29.54 |
November | 0.113708E+11 | 146.33 | 21686.31 | 01-NOV-04:15 | 1395956.99 | 13-NOV-13:40 | 24.28 | 23.55 | 12.77 |
December | 0.167852E+10 | 21.50 | 21686.31 | 04-DEC-09:20 | 1167951.83 | 06-DEC-13:05 | 22.84 | 22.73 | 1.69 |
Annual Sum or Average | 0.274181E+12 | 3519.30 | 26.39 | 24.90 | 24.00 | ||||
Minimum of Months | 0.136624E+09 | 1.75 | 21686.31 | 761740.69 | 22.44 | 22.43 | 0.09 | ||
Maximum of Months | 0.536133E+11 | 686.73 | 21686.31 | 1754956.57 | 31.58 | 28.01 | 55.93 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 3887095.21 | 0.00 | 12.04 | 293.08 | 20-JAN-07:00 | 0.00 | 72.13 | 72.27 | 0.00 | 0.00 | 0.00 | 0.00 | 20-JAN-07:00 |
February | 511925.28 | 0.00 | 1.81 | 112.98 | 13-FEB-07:00 | 0.00 | 68.00 | 68.04 | 0.00 | 0.00 | 0.00 | 0.00 | 13-FEB-07:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 67.64 | 67.64 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 67.64 | 67.64 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 67.64 | 67.64 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 67.64 | 67.64 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 67.64 | 67.64 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 67.64 | 67.64 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 67.64 | 67.64 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 67.64 | 67.64 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 67.64 | 67.64 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 49507.22 | 0.00 | 0.67 | 44.64 | 18-DEC-06:50 | 0.00 | 67.61 | 67.62 | 0.00 | 0.00 | 0.00 | 0.00 | 18-DEC-06:50 |
Annual Sum or Average | 4448527.71 | 0.00 | 14.51 | 0.00 | 68.05 | 68.06 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.61 | 67.62 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 3887095.21 | 0.00 | 12.04 | 293.08 | 0.00 | 72.13 | 72.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 25.32 | 25.32 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 30.74 | 30.74 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 37.46 | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 45.39 | 45.39 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 37.98 | 37.98 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 44.41 | 44.41 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 51.40 | 51.40 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 55.31 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 39.53 | 39.53 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 40.58 | 40.58 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 40.34 | 40.34 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 39.47 | 39.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 40.72 | 40.72 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.32 | 25.32 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.31 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.700880E+11 | 0.00 | 428.89 | 0.672540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 233337.18 | 30-JAN-05:12 | 161817.75 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.831882E+11 | 0.00 | 405.83 | 0.772381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 258694.75 | 09-FEB-05:12 | 165456.40 | 09-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.124336E+12 | 0.00 | 545.89 | 0.116146E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 211193.34 | 15-MAR-05:02 | 174643.61 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.164922E+12 | 0.00 | 623.21 | 0.144904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 215113.23 | 03-APR-05:03 | 175567.02 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.219062E+12 | 0.00 | 641.32 | 0.180891E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 296089.95 | 30-MAY-05:03 | 182468.70 | 30-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.278953E+12 | 0.00 | 638.09 | 0.200131E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 308362.75 | 09-JUN-04:32 | 195445.54 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.332863E+12 | 0.00 | 652.23 | 0.225645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 331537.03 | 05-JUL-03:12 | 203070.97 | 22-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.380959E+12 | 0.00 | 659.33 | 0.261428E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 334855.11 | 29-AUG-05:04 | 212261.20 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.282229E+12 | 0.00 | 628.19 | 0.187196E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 313439.20 | 10-SEP-16:21 | 197225.43 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.228234E+12 | 0.00 | 639.07 | 0.170476E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 294928.78 | 02-OCT-05:03 | 192265.38 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.159555E+12 | 0.00 | 572.81 | 0.133940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 231116.03 | 14-NOV-05:11 | 166885.01 | 13-NOV-05:22 | 0.00 | 0.00 | 0.00 |
December | 0.110047E+12 | 0.00 | 525.47 | 0.983615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 225389.24 | 11-DEC-06:03 | 150364.15 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243444E+13 | 0.00 | 6960.32 | 0.186361E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.700880E+11 | 0.00 | 405.83 | 0.672540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 211193.34 | 150364.15 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.380959E+12 | 0.00 | 659.33 | 0.261428E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 334855.11 | 212261.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.505474E+12 | 0.00 | 411.67 | 0.482523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1713587.45 | 30-JAN-06:03 | 1116560.40 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.611574E+12 | 0.00 | 381.89 | 0.562102E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2105738.14 | 09-FEB-06:02 | 1393825.25 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.930041E+12 | 0.00 | 460.25 | 0.864009E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2045361.25 | 29-MAR-05:02 | 1686189.74 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.124950E+13 | 0.00 | 485.99 | 0.109549E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2540336.06 | 30-APR-16:42 | 1638967.36 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.203337E+13 | 0.00 | 608.70 | 0.166547E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2844819.16 | 24-MAY-05:02 | 1638150.29 | 24-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.261870E+13 | 0.00 | 626.83 | 0.182297E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2990224.84 | 19-JUN-05:02 | 1798026.70 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.311437E+13 | 0.00 | 648.34 | 0.202048E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3359189.40 | 30-JUL-16:22 | 1863370.67 | 10-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.337492E+13 | 0.00 | 657.27 | 0.217118E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3267414.71 | 08-AUG-05:01 | 1968706.32 | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.267955E+13 | 0.00 | 606.02 | 0.173006E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3094030.07 | 28-SEP-05:02 | 1843726.30 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.197861E+13 | 0.00 | 557.11 | 0.145347E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2953863.44 | 07-OCT-05:02 | 1695191.95 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.124634E+13 | 0.00 | 453.31 | 0.102667E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2237592.38 | 02-NOV-04:12 | 1547413.87 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.710101E+12 | 0.00 | 422.08 | 0.625701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1864737.84 | 12-DEC-06:03 | 1313476.69 | 12-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210526E+14 | 0.00 | 6319.44 | 0.155201E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.505474E+12 | 0.00 | 381.89 | 0.482523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1713587.45 | 1116560.40 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.337492E+13 | 0.00 | 657.27 | 0.217118E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3359189.40 | 1968706.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.457480E+11 | 0.00 | 401.08 | 0.434702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146777.70 | 30-JAN-06:03 | 93268.25 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.590262E+11 | 0.00 | 372.08 | 0.541009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 222517.01 | 06-FEB-06:02 | 148485.02 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.933779E+11 | 0.00 | 451.42 | 0.867704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 211787.29 | 29-MAR-05:02 | 181240.86 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.129947E+12 | 0.00 | 483.69 | 0.114432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 275287.60 | 30-APR-16:11 | 178905.29 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.217345E+12 | 0.00 | 608.89 | 0.180215E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 318407.39 | 24-MAY-05:02 | 195322.12 | 22-MAY-04:53 | 0.00 | 0.00 | 0.00 |
June | 0.278241E+12 | 0.00 | 628.74 | 0.198042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 334767.99 | 19-JUN-05:02 | 206053.03 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.330957E+12 | 0.00 | 648.94 | 0.221050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 367699.71 | 30-JUL-16:22 | 213088.62 | 10-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.356513E+12 | 0.00 | 657.27 | 0.235920E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 365680.68 | 08-AUG-05:01 | 222849.18 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.280951E+12 | 0.00 | 608.02 | 0.185316E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 352995.15 | 10-SEP-16:31 | 243337.52 | 04-SEP-15:21 | 0.00 | 0.00 | 0.00 |
October | 0.204024E+12 | 0.00 | 554.86 | 0.151273E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 326464.88 | 07-OCT-05:02 | 191831.01 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.123441E+12 | 0.00 | 446.50 | 0.101627E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 241472.89 | 01-NOV-04:12 | 172403.63 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.667624E+11 | 0.00 | 410.08 | 0.584826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 217246.84 | 11-DEC-06:03 | 135034.55 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218633E+13 | 0.00 | 6271.57 | 0.163070E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.457480E+11 | 0.00 | 372.08 | 0.434702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146777.70 | 93268.25 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.356513E+12 | 0.00 | 657.27 | 0.235920E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 367699.71 | 243337.52 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.674824E+11 | 0.00 | 413.20 | 0.660146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151273.09 | 30-JAN-05:12 | 101736.50 | 18-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.646954E+11 | 0.00 | 374.78 | 0.626195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156748.55 | 07-FEB-05:12 | 104658.55 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.791900E+11 | 0.00 | 439.77 | 0.766280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163379.68 | 31-MAR-04:12 | 107652.76 | 02-MAR-04:02 | 0.00 | 0.00 | 0.00 |
April | 0.836422E+11 | 0.00 | 414.63 | 0.786812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 189159.14 | 30-APR-15:16 | 113942.30 | 30-APR-14:10 | 0.00 | 0.00 | 0.00 |
May | 0.109253E+12 | 0.00 | 459.48 | 0.962850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 225077.38 | 30-MAY-03:12 | 120547.25 | 29-MAY-12:00 | 0.00 | 0.00 | 0.00 |
June | 0.130355E+12 | 0.00 | 458.53 | 0.101959E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 234979.25 | 04-JUN-19:48 | 108407.00 | 18-JUN-14:31 | 0.00 | 0.00 | 0.00 |
July | 0.155137E+12 | 0.00 | 467.91 | 0.110705E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 239123.51 | 30-JUL-22:20 | 132411.56 | 30-JUL-11:31 | 0.00 | 0.00 | 0.00 |
August | 0.182087E+12 | 0.00 | 512.54 | 0.128184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 235559.74 | 20-AUG-21:31 | 122350.85 | 06-AUG-11:38 | 0.00 | 0.00 | 0.00 |
September | 0.142477E+12 | 0.00 | 467.95 | 0.104043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243463.17 | 10-SEP-17:36 | 122134.08 | 04-SEP-16:51 | 0.00 | 0.00 | 0.00 |
October | 0.125024E+12 | 0.00 | 478.53 | 0.101315E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 225299.15 | 08-OCT-11:48 | 125785.03 | 15-OCT-11:38 | 0.00 | 0.00 | 0.00 |
November | 0.101654E+12 | 0.00 | 450.80 | 0.888506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173817.90 | 03-NOV-03:02 | 119529.51 | 05-NOV-14:50 | 0.00 | 0.00 | 0.00 |
December | 0.797639E+11 | 0.00 | 432.95 | 0.751964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160253.31 | 06-DEC-05:12 | 101186.72 | 03-DEC-12:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132076E+13 | 0.00 | 5371.07 | 0.109048E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.646954E+11 | 0.00 | 374.78 | 0.626195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151273.09 | 101186.72 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.182087E+12 | 0.00 | 512.54 | 0.128184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243463.17 | 132411.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.340790E+12 | 0.876803E+11 | 744.00 | 0.329939E+12 | 0.108513E+11 | 0.00 | 0.37 | 23-JAN-14:00 | 0.32 | 21-JAN-05:55 | 137816.14 | 30-JAN-15:00 | 128975.51 | 23-JAN-14:00 | 11054.69 | 30-JAN-15:00 | 43110.53 | 23-JAN-14:00 | 0.00 |
February | 0.532522E+12 | 0.140752E+12 | 672.00 | 0.519550E+12 | 0.129717E+11 | 0.00 | 0.62 | 06-FEB-15:00 | 0.53 | 01-FEB-05:00 | 232165.78 | 07-FEB-16:10 | 222170.71 | 06-FEB-15:00 | 11792.22 | 07-FEB-16:10 | 81881.38 | 06-FEB-15:00 | 0.00 |
March | 0.834457E+12 | 0.236558E+12 | 744.00 | 0.822385E+12 | 0.120721E+11 | 0.00 | 0.98 | 31-MAR-23:15 | 0.74 | 08-MAR-06:00 | 402701.41 | 31-MAR-23:05 | 393040.29 | 31-MAR-23:55 | 11976.49 | 28-MAR-16:00 | 133326.44 | 27-MAR-11:00 | 0.00 |
April | 0.104194E+13 | 0.319417E+12 | 720.00 | 0.102949E+13 | 0.124459E+11 | 0.00 | 1.00 | 01-APR-09:40 | 0.42 | 30-APR-23:20 | 420458.48 | 10-APR-10:05 | 405232.65 | 10-APR-10:05 | 17573.94 | 10-APR-10:00 | 162576.59 | 28-APR-12:00 | 0.00 |
May | 0.361292E+12 | 0.129246E+12 | 744.00 | 0.343243E+12 | 0.180486E+11 | 0.00 | 0.62 | 31-MAY-23:13 | 0.34 | 03-MAY-06:00 | 225064.13 | 31-MAY-23:03 | 214692.65 | 31-MAY-23:57 | 15784.08 | 30-MAY-00:53 | 81968.74 | 31-MAY-23:13 | 0.00 |
June | 0.598732E+12 | 0.220019E+12 | 720.00 | 0.570961E+12 | 0.277716E+11 | 0.00 | 0.84 | 30-JUN-24:00 | 0.58 | 07-JUN-05:10 | 322939.07 | 30-JUN-23:03 | 305935.87 | 30-JUN-24:00 | 18831.11 | 08-JUN-13:00 | 112912.30 | 30-JUN-24:00 | 0.00 |
July | 0.872211E+12 | 0.336437E+12 | 744.00 | 0.839282E+12 | 0.329290E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.81 | 03-JUL-06:00 | 398687.08 | 31-JUL-24:00 | 386613.47 | 31-JUL-24:00 | 22118.17 | 20-JUL-11:00 | 160589.01 | 21-JUL-12:00 | 0.00 |
August | 0.109003E+13 | 0.393363E+12 | 744.00 | 0.105975E+13 | 0.302827E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.46 | 31-AUG-24:00 | 421987.70 | 04-AUG-14:00 | 402194.41 | 15-AUG-07:00 | 23944.12 | 31-AUG-23:13 | 173042.99 | 16-AUG-12:00 | 0.00 |
September | 0.368525E+12 | 0.134179E+12 | 720.00 | 0.337848E+12 | 0.306774E+11 | 0.00 | 0.62 | 30-SEP-23:05 | 0.36 | 30-SEP-05:30 | 235752.53 | 30-SEP-23:05 | 214032.15 | 30-SEP-24:00 | 22448.29 | 30-SEP-23:05 | 76243.65 | 30-SEP-23:15 | 0.00 |
October | 0.614014E+12 | 0.206669E+12 | 744.00 | 0.589758E+12 | 0.242555E+11 | 0.00 | 0.81 | 31-OCT-23:45 | 0.56 | 29-OCT-07:00 | 313806.73 | 31-OCT-23:05 | 305559.16 | 31-OCT-24:00 | 19189.98 | 07-OCT-10:10 | 99424.79 | 31-OCT-23:20 | 0.00 |
November | 0.820262E+12 | 0.248123E+12 | 720.00 | 0.803454E+12 | 0.168080E+11 | 0.00 | 0.87 | 01-NOV-14:00 | 0.75 | 26-NOV-05:10 | 329184.19 | 01-NOV-15:00 | 315741.52 | 13-NOV-15:00 | 15356.72 | 01-NOV-15:00 | 119785.41 | 01-NOV-14:00 | 0.00 |
December | 0.108318E+13 | 0.289363E+12 | 744.00 | 0.106870E+13 | 0.144760E+11 | 0.00 | 1.00 | 01-DEC-09:40 | 0.93 | 31-DEC-07:00 | 412772.29 | 05-DEC-22:00 | 404174.87 | 06-DEC-22:02 | 12925.39 | 18-DEC-05:00 | 132560.57 | 10-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.855795E+13 | 0.274181E+13 | 8760.00 | 0.831436E+13 | 0.243590E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.340790E+12 | 0.876803E+11 | 672.00 | 0.329939E+12 | 0.108513E+11 | 0.00 | 0.37 | 0.32 | 137816.14 | 128975.51 | 11054.69 | 43110.53 | 0.00 | ||||||
Maximum of Months | 0.109003E+13 | 0.393363E+12 | 744.00 | 0.106870E+13 | 0.329290E+11 | 0.00 | 1.00 | 0.93 | 421987.70 | 405232.65 | 23944.12 | 173042.99 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.565338E+10 | 0.145148E+10 | 744.00 | 0.531242E+10 | 0.340961E+09 | 0.00 | 0.32 | 29-JAN-17:40 | 0.20 | 21-JAN-08:00 | 2673.74 | 30-JAN-14:50 | 2381.83 | 29-JAN-17:40 | 423.39 | 30-JAN-15:05 | 797.81 | 23-JAN-14:00 | 0.00 |
February | 0.100299E+11 | 0.262489E+10 | 672.00 | 0.957901E+10 | 0.450845E+09 | 0.00 | 0.58 | 07-FEB-16:10 | 0.42 | 01-FEB-07:00 | 4805.38 | 07-FEB-16:10 | 4456.27 | 05-FEB-17:17 | 490.17 | 07-FEB-16:10 | 1608.39 | 06-FEB-15:00 | 0.00 |
March | 0.163147E+11 | 0.457934E+10 | 744.00 | 0.158538E+11 | 0.460830E+09 | 0.00 | 0.90 | 31-MAR-23:05 | 0.63 | 08-MAR-07:00 | 8099.66 | 31-MAR-23:05 | 7648.82 | 31-MAR-23:50 | 489.41 | 28-MAR-16:10 | 2639.12 | 27-MAR-11:00 | 0.00 |
April | 0.211151E+11 | 0.648492E+10 | 720.00 | 0.205333E+11 | 0.581846E+09 | 0.00 | 1.00 | 02-APR-10:25 | 0.39 | 30-APR-23:42 | 8775.93 | 29-APR-20:00 | 8431.41 | 23-APR-16:53 | 585.74 | 29-APR-19:55 | 3463.40 | 28-APR-12:00 | 0.00 |
May | 0.719737E+10 | 0.250449E+10 | 744.00 | 0.646364E+10 | 0.733726E+09 | 0.00 | 0.58 | 31-MAY-23:13 | 0.27 | 03-MAY-06:50 | 4662.57 | 31-MAY-23:03 | 4245.09 | 31-MAY-23:57 | 654.72 | 30-MAY-02:00 | 1645.94 | 31-MAY-23:13 | 0.00 |
June | 0.124750E+11 | 0.444318E+10 | 720.00 | 0.112816E+11 | 0.119343E+10 | 0.00 | 0.80 | 30-JUN-23:15 | 0.52 | 03-JUN-06:40 | 6814.72 | 30-JUN-23:03 | 6064.85 | 30-JUN-24:00 | 797.70 | 08-JUN-13:10 | 2291.86 | 30-JUN-24:00 | 0.00 |
July | 0.184394E+11 | 0.689624E+10 | 744.00 | 0.169637E+11 | 0.147569E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.74 | 03-JUL-06:30 | 8569.07 | 31-JUL-24:00 | 7885.82 | 31-JUL-24:00 | 955.95 | 20-JUL-14:00 | 3231.03 | 21-JUL-12:00 | 0.00 |
August | 0.228258E+11 | 0.839272E+10 | 744.00 | 0.213064E+11 | 0.151940E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.40 | 31-AUG-23:05 | 8881.40 | 08-AUG-03:55 | 8263.74 | 15-AUG-05:40 | 950.36 | 30-AUG-20:00 | 3690.12 | 16-AUG-12:00 | 0.00 |
September | 0.766655E+10 | 0.268096E+10 | 720.00 | 0.639525E+10 | 0.127130E+10 | 0.00 | 0.59 | 30-SEP-23:05 | 0.29 | 26-SEP-07:00 | 5084.28 | 30-SEP-23:05 | 4119.03 | 30-SEP-24:00 | 990.97 | 30-SEP-23:05 | 1560.38 | 30-SEP-23:15 | 0.00 |
October | 0.124231E+11 | 0.407733E+10 | 744.00 | 0.113952E+11 | 0.102791E+10 | 0.00 | 0.74 | 31-OCT-24:00 | 0.48 | 21-OCT-07:00 | 6294.41 | 31-OCT-23:05 | 5943.36 | 31-OCT-24:00 | 848.69 | 07-OCT-10:10 | 1951.84 | 31-OCT-23:20 | 0.00 |
November | 0.163036E+11 | 0.485476E+10 | 720.00 | 0.155810E+11 | 0.722625E+09 | 0.00 | 0.83 | 01-NOV-14:05 | 0.66 | 22-NOV-07:00 | 6955.11 | 01-NOV-16:00 | 6509.27 | 12-NOV-16:53 | 666.85 | 01-NOV-15:00 | 2443.03 | 01-NOV-14:00 | 0.00 |
December | 0.213159E+11 | 0.565645E+10 | 744.00 | 0.207626E+11 | 0.553261E+09 | 0.00 | 0.98 | 05-DEC-17:00 | 0.81 | 30-DEC-07:30 | 8679.03 | 05-DEC-17:00 | 8184.26 | 03-DEC-17:07 | 567.28 | 05-DEC-17:00 | 2728.26 | 10-DEC-12:33 | 0.00 |
Annual Sum or Average | 0.171760E+12 | 0.546468E+11 | 8760.00 | 0.161428E+12 | 0.103318E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.565338E+10 | 0.145148E+10 | 672.00 | 0.531242E+10 | 0.340961E+09 | 0.00 | 0.32 | 0.20 | 2673.74 | 2381.83 | 423.39 | 797.81 | 0.00 | ||||||
Maximum of Months | 0.228258E+11 | 0.839272E+10 | 744.00 | 0.213064E+11 | 0.151940E+10 | 0.00 | 1.00 | 0.81 | 8881.40 | 8431.41 | 990.97 | 3690.12 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.472885E+11 | 0.122891E+11 | 744.00 | 0.440181E+11 | 0.327038E+10 | 0.00 | 0.31 | 30-JAN-14:20 | 0.15 | 21-JAN-08:00 | 24594.26 | 30-JAN-15:00 | 21407.68 | 23-JAN-14:05 | 4141.81 | 30-JAN-15:05 | 7274.41 | 23-JAN-14:00 | 0.00 |
February | 0.914628E+11 | 0.240767E+11 | 672.00 | 0.870121E+11 | 0.445073E+10 | 0.00 | 0.57 | 07-FEB-16:10 | 0.38 | 13-FEB-07:00 | 45846.23 | 07-FEB-16:10 | 41739.63 | 06-FEB-15:00 | 4867.94 | 07-FEB-16:10 | 15275.33 | 06-FEB-15:00 | 0.00 |
March | 0.153965E+12 | 0.433078E+11 | 744.00 | 0.149383E+12 | 0.458276E+10 | 0.00 | 0.91 | 31-MAR-23:15 | 0.60 | 08-MAR-07:00 | 77965.00 | 31-MAR-23:05 | 73517.96 | 31-MAR-23:55 | 4869.18 | 28-MAR-16:10 | 25197.39 | 27-MAR-11:00 | 0.00 |
April | 0.200736E+12 | 0.616881E+11 | 720.00 | 0.194925E+12 | 0.581165E+10 | 0.00 | 1.00 | 02-APR-11:02 | 0.33 | 30-APR-23:25 | 83326.95 | 30-APR-17:56 | 79545.89 | 23-APR-16:28 | 5834.12 | 30-APR-15:00 | 33066.17 | 28-APR-12:00 | 0.00 |
May | 0.680178E+11 | 0.236747E+11 | 744.00 | 0.607690E+11 | 0.724884E+10 | 0.00 | 0.58 | 31-MAY-23:13 | 0.27 | 03-MAY-07:00 | 45187.70 | 31-MAY-23:03 | 40921.71 | 31-MAY-23:43 | 6452.80 | 30-MAY-02:00 | 15896.96 | 31-MAY-23:13 | 0.00 |
June | 0.118905E+12 | 0.423221E+11 | 720.00 | 0.107040E+12 | 0.118654E+11 | 0.00 | 0.81 | 30-JUN-23:03 | 0.51 | 07-JUN-06:00 | 65923.09 | 30-JUN-23:03 | 58301.83 | 30-JUN-24:00 | 7993.94 | 30-JUN-23:03 | 22068.02 | 30-JUN-24:00 | 0.00 |
July | 0.175691E+12 | 0.656657E+11 | 744.00 | 0.160981E+12 | 0.147099E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.73 | 03-JUL-06:00 | 82083.27 | 31-JUL-24:00 | 75293.17 | 31-JUL-24:00 | 9524.67 | 20-JUL-14:00 | 30861.39 | 21-JUL-12:00 | 0.00 |
August | 0.216616E+12 | 0.800831E+11 | 744.00 | 0.201318E+12 | 0.152981E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.35 | 31-AUG-23:05 | 84223.31 | 08-AUG-03:55 | 77840.28 | 06-AUG-05:00 | 9529.86 | 30-AUG-20:00 | 35224.87 | 16-AUG-12:00 | 0.00 |
September | 0.722623E+11 | 0.252499E+11 | 720.00 | 0.596938E+11 | 0.125685E+11 | 0.00 | 0.60 | 30-SEP-23:05 | 0.28 | 26-SEP-07:00 | 49442.95 | 30-SEP-23:05 | 39591.47 | 30-SEP-23:40 | 10082.27 | 30-SEP-23:05 | 15094.65 | 30-SEP-23:15 | 0.00 |
October | 0.118080E+12 | 0.387376E+11 | 744.00 | 0.107868E+12 | 0.102121E+11 | 0.00 | 0.75 | 31-OCT-24:00 | 0.47 | 21-OCT-07:00 | 60898.18 | 31-OCT-23:05 | 57450.02 | 31-OCT-24:00 | 8442.11 | 07-OCT-10:10 | 18843.91 | 31-OCT-23:20 | 0.00 |
November | 0.154661E+12 | 0.460863E+11 | 720.00 | 0.147469E+12 | 0.719231E+10 | 0.00 | 0.83 | 01-NOV-14:00 | 0.64 | 22-NOV-07:00 | 66792.58 | 01-NOV-16:00 | 61130.47 | 05-NOV-16:54 | 6642.27 | 01-NOV-15:00 | 23443.82 | 01-NOV-14:00 | 0.00 |
December | 0.199767E+12 | 0.531793E+11 | 744.00 | 0.194247E+12 | 0.552006E+10 | 0.00 | 0.98 | 05-DEC-17:00 | 0.78 | 30-DEC-07:40 | 82553.44 | 05-DEC-17:00 | 76902.65 | 04-DEC-17:00 | 5657.83 | 05-DEC-17:00 | 25608.23 | 10-DEC-12:10 | 0.00 |
Annual Sum or Average | 0.161745E+13 | 0.516361E+12 | 8760.00 | 0.151472E+13 | 0.102731E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.472885E+11 | 0.122891E+11 | 672.00 | 0.440181E+11 | 0.327038E+10 | 0.00 | 0.31 | 0.15 | 24594.26 | 21407.68 | 4141.81 | 7274.41 | 0.00 | ||||||
Maximum of Months | 0.216616E+12 | 0.800831E+11 | 744.00 | 0.201318E+12 | 0.152981E+11 | 0.00 | 1.00 | 0.78 | 84223.31 | 79545.89 | 10082.27 | 35224.87 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.425951E+10 | 0.112175E+10 | 744.00 | 0.394084E+10 | 0.318673E+09 | 0.00 | 0.31 | 24-JAN-17:00 | 0.08 | 01-JAN-07:55 | 2489.88 | 30-JAN-15:00 | 2194.26 | 23-JAN-14:05 | 416.82 | 30-JAN-15:05 | 743.95 | 23-JAN-14:00 | 0.00 |
February | 0.889925E+10 | 0.235611E+10 | 672.00 | 0.845562E+10 | 0.443626E+09 | 0.00 | 0.58 | 07-FEB-16:10 | 0.34 | 13-FEB-07:50 | 4634.16 | 07-FEB-16:10 | 4246.16 | 05-FEB-17:30 | 487.87 | 07-FEB-16:10 | 1545.53 | 06-FEB-15:00 | 0.00 |
March | 0.152844E+11 | 0.431294E+10 | 744.00 | 0.148262E+11 | 0.458204E+09 | 0.00 | 0.90 | 31-MAR-23:15 | 0.57 | 08-MAR-07:00 | 7752.29 | 31-MAR-23:05 | 7301.97 | 31-MAR-23:55 | 487.41 | 28-MAR-16:10 | 2530.13 | 27-MAR-11:00 | 0.00 |
April | 0.201040E+11 | 0.618819E+10 | 720.00 | 0.195226E+11 | 0.581351E+09 | 0.00 | 1.00 | 02-APR-11:40 | 0.34 | 30-APR-23:25 | 8448.71 | 30-APR-17:56 | 8149.34 | 02-APR-16:23 | 579.49 | 30-APR-15:00 | 3336.61 | 28-APR-12:00 | 0.00 |
May | 0.695162E+10 | 0.242101E+10 | 744.00 | 0.622302E+10 | 0.728603E+09 | 0.00 | 0.59 | 31-MAY-23:13 | 0.25 | 03-MAY-07:00 | 4573.09 | 31-MAY-23:03 | 4152.46 | 31-MAY-23:57 | 650.41 | 30-MAY-02:00 | 1609.62 | 31-MAY-23:13 | 0.00 |
June | 0.120456E+11 | 0.428897E+10 | 720.00 | 0.108566E+11 | 0.118904E+10 | 0.00 | 0.80 | 30-JUN-23:03 | 0.50 | 07-JUN-06:00 | 6612.09 | 30-JUN-23:03 | 5849.86 | 30-JUN-24:00 | 799.06 | 30-JUN-23:03 | 2215.63 | 30-JUN-24:00 | 0.00 |
July | 0.178024E+11 | 0.665386E+10 | 744.00 | 0.163295E+11 | 0.147290E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.73 | 03-JUL-06:00 | 8274.87 | 31-JUL-24:00 | 7594.68 | 31-JUL-24:00 | 955.25 | 20-JUL-14:00 | 3179.23 | 30-JUL-14:00 | 0.00 |
August | 0.218559E+11 | 0.807944E+10 | 744.00 | 0.203262E+11 | 0.152973E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.35 | 31-AUG-23:05 | 8489.02 | 20-AUG-21:04 | 7868.40 | 06-AUG-05:00 | 958.16 | 30-AUG-20:00 | 3554.51 | 16-AUG-12:00 | 0.00 |
September | 0.737146E+10 | 0.257762E+10 | 720.00 | 0.610940E+10 | 0.126207E+10 | 0.00 | 0.60 | 30-SEP-23:05 | 0.27 | 26-SEP-07:00 | 4991.68 | 30-SEP-23:05 | 4002.88 | 30-SEP-24:00 | 997.36 | 30-SEP-23:05 | 1524.75 | 30-SEP-23:10 | 0.00 |
October | 0.118826E+11 | 0.390251E+10 | 744.00 | 0.108603E+11 | 0.102229E+10 | 0.00 | 0.74 | 31-OCT-24:00 | 0.46 | 21-OCT-07:00 | 6086.91 | 31-OCT-23:05 | 5745.65 | 31-OCT-24:00 | 846.81 | 07-OCT-10:10 | 1886.25 | 09-OCT-15:02 | 0.00 |
November | 0.154035E+11 | 0.460105E+10 | 720.00 | 0.146844E+11 | 0.719108E+09 | 0.00 | 0.83 | 01-NOV-14:05 | 0.61 | 22-NOV-07:00 | 6729.36 | 01-NOV-16:00 | 6281.31 | 05-NOV-16:54 | 665.07 | 01-NOV-15:00 | 2362.27 | 01-NOV-14:00 | 0.00 |
December | 0.196953E+11 | 0.526461E+10 | 744.00 | 0.191435E+11 | 0.551738E+09 | 0.00 | 0.97 | 05-DEC-17:00 | 0.73 | 31-DEC-07:30 | 8280.96 | 05-DEC-17:00 | 7716.61 | 06-DEC-17:00 | 565.91 | 05-DEC-17:00 | 2570.13 | 10-DEC-12:53 | 0.00 |
Annual Sum or Average | 0.161556E+12 | 0.517680E+11 | 8760.00 | 0.151278E+12 | 0.102773E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.425951E+10 | 0.112175E+10 | 672.00 | 0.394084E+10 | 0.318673E+09 | 0.00 | 0.31 | 0.08 | 2489.88 | 2194.26 | 416.82 | 743.95 | 0.00 | ||||||
Maximum of Months | 0.218559E+11 | 0.807944E+10 | 744.00 | 0.203262E+11 | 0.152973E+10 | 0.00 | 1.00 | 0.73 | 8489.02 | 8149.34 | 997.36 | 3554.51 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 119.85 | 279.18 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 169.33 | 234.82 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 248.83 | 175.58 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 362.84 | 107.50 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 557.81 | 25.22 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 641.28 | 6.68 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 711.04 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 690.93 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 531.53 | 8.80 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 377.93 | 43.00 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 236.52 | 125.05 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.52 | 232.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 399.93 | 102.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 119.85 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 711.04 | 279.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 119.85 | 279.18 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 169.33 | 234.82 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 248.83 | 175.58 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 362.84 | 107.50 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 557.81 | 25.22 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 641.28 | 6.68 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 711.04 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 690.93 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 531.53 | 8.80 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 377.93 | 43.00 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 236.52 | 125.05 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.52 | 232.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 399.93 | 102.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 119.85 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 711.04 | 279.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 119.85 | 279.18 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 169.33 | 234.82 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 248.83 | 175.58 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 362.84 | 107.50 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 557.81 | 25.22 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 641.28 | 6.68 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 711.04 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 690.93 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 531.53 | 8.80 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 377.93 | 43.00 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 236.52 | 125.05 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.52 | 232.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 399.93 | 102.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 119.85 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 711.04 | 279.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 119.85 | 279.18 | 0.00 | 0.00 | 0.00 |
February | 128.47 | 0.00 | 128.47 | 169.33 | 234.82 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 248.83 | 175.58 | 0.00 | 0.00 | 0.00 |
April | 166.26 | 0.34 | 165.91 | 362.84 | 107.50 | 0.00 | 0.00 | 0.00 |
May | 187.14 | 5.49 | 181.65 | 557.81 | 25.22 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.24 | 641.28 | 6.68 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.56 | 711.04 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.74 | 690.93 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.89 | 531.53 | 8.80 | 0.00 | 0.00 | 0.00 |
October | 138.21 | 0.00 | 138.21 | 377.93 | 43.00 | 0.00 | 0.00 | 0.00 |
November | 118.65 | 0.00 | 118.65 | 236.52 | 125.05 | 0.00 | 0.00 | 0.00 |
December | 104.61 | 0.00 | 104.61 | 134.52 | 232.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 399.93 | 102.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.61 | 0.00 | 104.61 | 119.85 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.24 | 711.04 | 279.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.07 | 0.00 | 112.07 | 119.84 | 279.16 | 0.00 | 0.00 | 0.00 |
February | 128.46 | 0.00 | 128.46 | 169.32 | 234.81 | 0.00 | 0.00 | 0.00 |
March | 147.56 | 0.00 | 147.56 | 248.82 | 175.57 | 0.00 | 0.00 | 0.00 |
April | 166.25 | 0.34 | 165.91 | 362.83 | 107.50 | 0.00 | 0.00 | 0.00 |
May | 187.13 | 5.49 | 181.64 | 557.78 | 25.21 | 0.00 | 0.00 | 0.00 |
June | 200.36 | 11.12 | 189.23 | 641.26 | 6.68 | 0.00 | 0.00 | 0.00 |
July | 183.85 | 5.30 | 178.55 | 711.01 | 0.26 | 0.00 | 0.00 | 0.00 |
August | 171.15 | 1.42 | 169.73 | 690.90 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 155.90 | 0.02 | 155.88 | 531.51 | 8.80 | 0.00 | 0.00 | 0.00 |
October | 138.20 | 0.00 | 138.20 | 377.92 | 42.99 | 0.00 | 0.00 | 0.00 |
November | 118.64 | 0.00 | 118.64 | 236.51 | 125.05 | 0.00 | 0.00 | 0.00 |
December | 104.60 | 0.00 | 104.60 | 134.52 | 232.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 151.27 | 1.98 | 149.29 | 399.91 | 102.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 104.60 | 0.00 | 104.60 | 119.84 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 200.36 | 11.12 | 189.23 | 711.01 | 279.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 299.76 | 287.28 | 0.00 | 0.00 | 0.00 |
February | 245.49 | 66.53 | 178.96 | 367.78 | 241.51 | 0.00 | 0.00 | 0.00 |
March | 271.17 | 66.83 | 204.33 | 474.31 | 180.11 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.20 | 233.96 | 681.60 | 109.20 | 0.00 | 0.00 | 0.00 |
May | 368.96 | 117.55 | 251.41 | 922.61 | 26.94 | 0.00 | 0.00 | 0.00 |
June | 361.34 | 110.50 | 250.84 | 972.73 | 6.09 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1047.45 | 0.18 | 0.00 | 0.00 | 0.00 |
August | 345.34 | 105.99 | 239.35 | 1077.84 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 324.66 | 100.35 | 224.31 | 879.84 | 8.85 | 0.00 | 0.00 | 0.00 |
October | 294.60 | 96.24 | 198.35 | 688.03 | 42.98 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.68 | 475.81 | 126.52 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 145.00 | 295.95 | 232.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.11 | 88.31 | 207.80 | 683.79 | 104.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 145.00 | 295.95 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.96 | 117.55 | 251.41 | 1077.84 | 287.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 299.76 | 287.28 | 0.00 | 0.00 | 0.00 |
February | 245.49 | 66.53 | 178.96 | 367.78 | 241.51 | 0.00 | 0.00 | 0.00 |
March | 271.17 | 66.83 | 204.33 | 474.31 | 180.11 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.20 | 233.96 | 681.60 | 109.20 | 0.00 | 0.00 | 0.00 |
May | 368.96 | 117.55 | 251.41 | 922.61 | 26.94 | 0.00 | 0.00 | 0.00 |
June | 361.34 | 110.50 | 250.84 | 972.73 | 6.09 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1047.45 | 0.18 | 0.00 | 0.00 | 0.00 |
August | 345.34 | 105.99 | 239.35 | 1077.84 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 324.66 | 100.35 | 224.31 | 879.84 | 8.85 | 0.00 | 0.00 | 0.00 |
October | 294.60 | 96.24 | 198.35 | 688.03 | 42.98 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.68 | 475.81 | 126.52 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 145.00 | 295.95 | 232.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.11 | 88.31 | 207.80 | 683.79 | 104.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 145.00 | 295.95 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.96 | 117.55 | 251.41 | 1077.84 | 287.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 225.26 | 68.15 | 157.11 | 299.76 | 287.27 | 0.00 | 0.00 | 0.00 |
February | 245.48 | 66.53 | 178.96 | 367.77 | 241.51 | 0.00 | 0.00 | 0.00 |
March | 271.16 | 66.83 | 204.33 | 474.30 | 180.11 | 0.00 | 0.00 | 0.00 |
April | 330.15 | 96.19 | 233.95 | 681.58 | 109.20 | 0.00 | 0.00 | 0.00 |
May | 368.95 | 117.55 | 251.40 | 922.60 | 26.94 | 0.00 | 0.00 | 0.00 |
June | 361.33 | 110.50 | 250.83 | 972.72 | 6.09 | 0.00 | 0.00 | 0.00 |
July | 337.25 | 97.23 | 240.02 | 1047.43 | 0.18 | 0.00 | 0.00 | 0.00 |
August | 345.33 | 105.99 | 239.35 | 1077.82 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 324.65 | 100.35 | 224.31 | 879.83 | 8.85 | 0.00 | 0.00 | 0.00 |
October | 294.59 | 96.24 | 198.35 | 688.02 | 42.98 | 0.00 | 0.00 | 0.00 |
November | 246.87 | 78.20 | 168.67 | 475.81 | 126.51 | 0.00 | 0.00 | 0.00 |
December | 199.82 | 54.82 | 144.99 | 295.95 | 232.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 296.10 | 88.30 | 207.80 | 683.77 | 104.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.82 | 54.82 | 144.99 | 295.95 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 368.95 | 117.55 | 251.40 | 1077.82 | 287.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 566.95 | 268.86 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 567.61 | 232.85 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 523.55 | 180.33 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 487.26 | 111.96 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 556.07 | 25.95 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 587.37 | 5.29 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 690.03 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 765.44 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 771.68 | 9.84 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 802.59 | 47.54 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 745.47 | 129.83 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 600.01 | 228.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.55 | 82.51 | 193.03 | 639.15 | 102.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 487.26 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 802.59 | 268.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 566.95 | 268.86 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 567.61 | 232.85 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 523.55 | 180.33 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 487.26 | 111.96 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 556.07 | 25.95 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 587.37 | 5.29 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 690.03 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 765.44 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 771.67 | 9.84 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 802.58 | 47.54 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 745.47 | 129.83 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 600.01 | 228.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.54 | 82.51 | 193.03 | 639.15 | 102.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 487.26 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 802.58 | 268.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 566.95 | 268.86 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 567.61 | 232.85 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 523.55 | 180.33 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 487.26 | 111.96 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 556.07 | 25.95 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 587.37 | 5.29 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 690.03 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 765.44 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 771.68 | 9.84 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 802.59 | 47.54 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 745.47 | 129.83 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 600.01 | 228.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.55 | 82.51 | 193.03 | 639.15 | 102.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 487.26 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 802.59 | 268.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.21 | 170.29 | 191.92 | 566.95 | 268.86 | 0.00 | 0.00 | 0.00 |
February | 340.13 | 139.13 | 201.00 | 567.61 | 232.85 | 0.00 | 0.00 | 0.00 |
March | 279.94 | 76.00 | 203.94 | 523.55 | 180.33 | 0.00 | 0.00 | 0.00 |
April | 220.06 | 23.33 | 196.73 | 487.26 | 111.96 | 0.00 | 0.00 | 0.00 |
May | 186.41 | 2.85 | 183.55 | 556.07 | 25.95 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.34 | 587.37 | 5.29 | 0.00 | 0.00 | 0.00 |
July | 175.55 | 1.49 | 174.06 | 690.03 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 203.62 | 14.43 | 189.19 | 765.44 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 268.48 | 61.53 | 206.95 | 771.67 | 9.84 | 0.00 | 0.00 | 0.00 |
October | 351.49 | 139.74 | 211.75 | 802.58 | 47.54 | 0.00 | 0.00 | 0.00 |
November | 387.76 | 186.93 | 200.83 | 745.47 | 129.83 | 0.00 | 0.00 | 0.00 |
December | 359.96 | 177.81 | 182.15 | 600.01 | 228.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.54 | 82.51 | 193.03 | 639.15 | 102.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.55 | 0.22 | 174.06 | 487.26 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.76 | 186.93 | 211.75 | 802.58 | 268.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.20 | 170.29 | 191.91 | 566.92 | 268.85 | 0.00 | 0.00 | 0.00 |
February | 340.12 | 139.12 | 200.99 | 567.59 | 232.84 | 0.00 | 0.00 | 0.00 |
March | 279.93 | 76.00 | 203.93 | 523.53 | 180.32 | 0.00 | 0.00 | 0.00 |
April | 220.05 | 23.33 | 196.72 | 487.25 | 111.96 | 0.00 | 0.00 | 0.00 |
May | 186.40 | 2.85 | 183.55 | 556.04 | 25.95 | 0.00 | 0.00 | 0.00 |
June | 175.55 | 0.22 | 175.33 | 587.35 | 5.29 | 0.00 | 0.00 | 0.00 |
July | 175.54 | 1.49 | 174.05 | 690.00 | 0.15 | 0.00 | 0.00 | 0.00 |
August | 203.61 | 14.43 | 189.19 | 765.41 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 268.47 | 61.53 | 206.94 | 771.64 | 9.84 | 0.00 | 0.00 | 0.00 |
October | 351.48 | 139.73 | 211.74 | 802.55 | 47.53 | 0.00 | 0.00 | 0.00 |
November | 387.75 | 186.92 | 200.83 | 745.44 | 129.82 | 0.00 | 0.00 | 0.00 |
December | 359.95 | 177.80 | 182.14 | 599.98 | 228.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.53 | 82.51 | 193.03 | 639.12 | 102.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 175.54 | 0.22 | 174.05 | 487.25 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 387.75 | 186.92 | 211.74 | 802.55 | 268.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 300.49 | 339.41 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.33 | 379.16 | 299.60 | 0.00 | 0.00 | 0.00 |
March | 298.81 | 88.46 | 210.35 | 512.94 | 240.51 | 0.00 | 0.00 | 0.00 |
April | 326.55 | 91.74 | 234.81 | 648.93 | 168.53 | 0.00 | 0.00 | 0.00 |
May | 355.45 | 106.40 | 249.05 | 881.73 | 43.09 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 955.57 | 15.80 | 0.00 | 0.00 | 0.00 |
July | 336.98 | 96.40 | 240.58 | 998.21 | 1.45 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 999.19 | 1.56 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.32 | 225.54 | 862.56 | 18.03 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.41 | 197.85 | 665.56 | 74.03 | 0.00 | 0.00 | 0.00 |
November | 251.16 | 82.14 | 169.02 | 474.80 | 182.93 | 0.00 | 0.00 | 0.00 |
December | 210.26 | 63.56 | 146.70 | 308.55 | 316.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.76 | 667.23 | 141.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.26 | 63.45 | 146.70 | 300.49 | 1.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 999.19 | 339.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 300.49 | 339.41 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.33 | 379.16 | 299.60 | 0.00 | 0.00 | 0.00 |
March | 298.81 | 88.46 | 210.35 | 512.94 | 240.51 | 0.00 | 0.00 | 0.00 |
April | 326.55 | 91.74 | 234.81 | 648.93 | 168.53 | 0.00 | 0.00 | 0.00 |
May | 355.45 | 106.40 | 249.05 | 881.73 | 43.09 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 955.57 | 15.80 | 0.00 | 0.00 | 0.00 |
July | 336.98 | 96.40 | 240.58 | 998.21 | 1.45 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 999.19 | 1.56 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.32 | 225.54 | 862.56 | 18.03 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.41 | 197.85 | 665.56 | 74.03 | 0.00 | 0.00 | 0.00 |
November | 251.16 | 82.14 | 169.02 | 474.80 | 182.93 | 0.00 | 0.00 | 0.00 |
December | 210.26 | 63.56 | 146.70 | 308.55 | 316.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.76 | 667.23 | 141.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.26 | 63.45 | 146.70 | 300.49 | 1.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 999.19 | 339.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 220.91 | 63.45 | 157.46 | 300.49 | 339.40 | 0.00 | 0.00 | 0.00 |
February | 252.26 | 71.93 | 180.32 | 379.15 | 299.59 | 0.00 | 0.00 | 0.00 |
March | 298.80 | 88.46 | 210.34 | 512.93 | 240.50 | 0.00 | 0.00 | 0.00 |
April | 326.54 | 91.74 | 234.80 | 648.91 | 168.53 | 0.00 | 0.00 | 0.00 |
May | 355.44 | 106.40 | 249.04 | 881.72 | 43.09 | 0.00 | 0.00 | 0.00 |
June | 367.32 | 115.79 | 251.53 | 955.55 | 15.80 | 0.00 | 0.00 | 0.00 |
July | 336.97 | 96.40 | 240.57 | 998.19 | 1.45 | 0.00 | 0.00 | 0.00 |
August | 345.70 | 105.11 | 240.59 | 999.17 | 1.56 | 0.00 | 0.00 | 0.00 |
September | 328.85 | 103.31 | 225.53 | 862.55 | 18.03 | 0.00 | 0.00 | 0.00 |
October | 292.25 | 94.40 | 197.84 | 665.55 | 74.03 | 0.00 | 0.00 | 0.00 |
November | 251.15 | 82.13 | 169.02 | 474.79 | 182.93 | 0.00 | 0.00 | 0.00 |
December | 210.25 | 63.56 | 146.70 | 308.55 | 316.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 299.04 | 90.29 | 208.75 | 667.22 | 141.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.25 | 63.45 | 146.70 | 300.49 | 1.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 367.32 | 115.79 | 251.53 | 999.17 | 339.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 560.36 | 0.00 | 560.36 | 647.56 | 1242.94 | 0.00 | 0.00 | 0.00 |
February | 642.34 | 0.00 | 642.34 | 887.12 | 1051.33 | 0.00 | 0.00 | 0.00 |
March | 737.81 | 0.00 | 737.81 | 1271.86 | 817.77 | 0.00 | 0.00 | 0.00 |
April | 831.27 | 1.71 | 829.56 | 1845.19 | 522.38 | 0.00 | 0.00 | 0.00 |
May | 935.67 | 27.44 | 908.23 | 2811.25 | 129.46 | 0.00 | 0.00 | 0.00 |
June | 1001.81 | 55.62 | 946.19 | 3247.06 | 31.34 | 0.00 | 0.00 | 0.00 |
July | 919.26 | 26.49 | 892.77 | 3621.14 | 0.77 | 0.00 | 0.00 | 0.00 |
August | 855.75 | 7.08 | 848.67 | 3568.89 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 779.51 | 0.09 | 779.42 | 2697.60 | 43.84 | 0.00 | 0.00 | 0.00 |
October | 691.02 | 0.00 | 691.02 | 1928.15 | 214.13 | 0.00 | 0.00 | 0.00 |
November | 593.23 | 0.00 | 593.23 | 1219.79 | 591.79 | 0.00 | 0.00 | 0.00 |
December | 523.03 | 0.00 | 523.03 | 721.60 | 1029.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.36 | 9.90 | 746.46 | 2046.06 | 470.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 523.03 | 0.00 | 523.03 | 647.56 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.81 | 55.62 | 946.19 | 3621.14 | 1242.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 675.79 | 204.46 | 471.33 | 907.84 | 805.80 | 0.00 | 0.00 | 0.00 |
February | 736.45 | 199.58 | 536.87 | 1101.52 | 688.11 | 0.00 | 0.00 | 0.00 |
March | 813.49 | 200.49 | 612.99 | 1408.58 | 539.02 | 0.00 | 0.00 | 0.00 |
April | 990.45 | 288.59 | 701.87 | 2020.42 | 353.86 | 0.00 | 0.00 | 0.00 |
May | 1106.86 | 352.65 | 754.21 | 2744.82 | 89.21 | 0.00 | 0.00 | 0.00 |
June | 1084.00 | 331.50 | 752.50 | 2900.96 | 20.72 | 0.00 | 0.00 | 0.00 |
July | 1011.74 | 291.68 | 720.06 | 3131.85 | 0.49 | 0.00 | 0.00 | 0.00 |
August | 1036.01 | 317.97 | 718.04 | 3233.25 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 973.97 | 301.04 | 672.93 | 2622.98 | 29.34 | 0.00 | 0.00 | 0.00 |
October | 883.78 | 288.73 | 595.05 | 2047.71 | 143.21 | 0.00 | 0.00 | 0.00 |
November | 740.61 | 234.59 | 506.02 | 1412.80 | 391.02 | 0.00 | 0.00 | 0.00 |
December | 599.45 | 164.47 | 434.99 | 888.78 | 670.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 888.31 | 264.91 | 623.39 | 2040.56 | 309.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.45 | 164.47 | 434.99 | 888.78 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.86 | 352.65 | 754.21 | 3233.25 | 805.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1811.03 | 851.45 | 959.59 | 2816.59 | 1303.31 | 0.00 | 0.00 | 0.00 |
February | 1700.64 | 695.64 | 1005.00 | 2823.01 | 1117.36 | 0.00 | 0.00 | 0.00 |
March | 1399.70 | 380.01 | 1019.69 | 2610.05 | 878.32 | 0.00 | 0.00 | 0.00 |
April | 1100.27 | 116.65 | 983.62 | 2446.86 | 555.23 | 0.00 | 0.00 | 0.00 |
May | 932.02 | 14.27 | 917.75 | 2801.34 | 131.40 | 0.00 | 0.00 | 0.00 |
June | 877.75 | 1.09 | 876.67 | 2986.15 | 23.34 | 0.00 | 0.00 | 0.00 |
July | 877.73 | 7.46 | 870.27 | 3511.84 | 0.31 | 0.00 | 0.00 | 0.00 |
August | 1018.10 | 72.14 | 945.96 | 3921.18 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 1342.37 | 307.64 | 1034.73 | 3867.80 | 50.58 | 0.00 | 0.00 | 0.00 |
October | 1757.43 | 698.68 | 1058.75 | 4003.63 | 247.62 | 0.00 | 0.00 | 0.00 |
November | 1938.80 | 934.65 | 1004.15 | 3706.20 | 651.99 | 0.00 | 0.00 | 0.00 |
December | 1799.79 | 889.04 | 910.75 | 2990.78 | 1100.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1377.71 | 412.56 | 965.15 | 3209.79 | 501.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 877.73 | 1.09 | 870.27 | 2446.86 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1938.80 | 934.65 | 1058.75 | 4003.63 | 1303.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 662.73 | 190.34 | 472.39 | 936.20 | 891.31 | 0.00 | 0.00 | 0.00 |
February | 756.77 | 215.80 | 540.97 | 1177.40 | 759.98 | 0.00 | 0.00 | 0.00 |
March | 896.42 | 265.39 | 631.03 | 1580.17 | 607.92 | 0.00 | 0.00 | 0.00 |
April | 979.63 | 275.22 | 704.41 | 2004.53 | 412.80 | 0.00 | 0.00 | 0.00 |
May | 1066.33 | 319.19 | 747.13 | 2674.72 | 114.38 | 0.00 | 0.00 | 0.00 |
June | 1101.96 | 347.37 | 754.59 | 2932.74 | 29.69 | 0.00 | 0.00 | 0.00 |
July | 1010.93 | 289.21 | 721.72 | 3103.20 | 1.19 | 0.00 | 0.00 | 0.00 |
August | 1037.10 | 315.32 | 721.78 | 3188.00 | 0.42 | 0.00 | 0.00 | 0.00 |
September | 986.55 | 309.95 | 676.60 | 2632.87 | 43.05 | 0.00 | 0.00 | 0.00 |
October | 876.75 | 283.22 | 593.54 | 2042.71 | 184.04 | 0.00 | 0.00 | 0.00 |
November | 753.46 | 246.41 | 507.05 | 1472.18 | 452.68 | 0.00 | 0.00 | 0.00 |
December | 630.76 | 190.67 | 440.10 | 987.64 | 756.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 897.12 | 270.86 | 626.26 | 2066.11 | 352.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 630.76 | 190.34 | 440.10 | 936.20 | 0.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1101.96 | 347.37 | 754.59 | 3188.00 | 891.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 560.36 | 0.00 | 560.36 | 670.57 | 1166.20 | 0.00 | 0.00 | 0.00 |
February | 642.34 | 0.00 | 642.34 | 896.18 | 1005.05 | 0.00 | 0.00 | 0.00 |
March | 737.81 | 0.00 | 737.81 | 1265.98 | 796.23 | 0.00 | 0.00 | 0.00 |
April | 831.27 | 1.71 | 829.56 | 1825.45 | 524.43 | 0.00 | 0.00 | 0.00 |
May | 935.67 | 27.44 | 908.23 | 2775.20 | 136.19 | 0.00 | 0.00 | 0.00 |
June | 1001.81 | 55.62 | 946.19 | 3207.59 | 34.88 | 0.00 | 0.00 | 0.00 |
July | 919.26 | 26.49 | 892.77 | 3568.78 | 1.23 | 0.00 | 0.00 | 0.00 |
August | 855.75 | 7.08 | 848.67 | 3521.62 | 0.13 | 0.00 | 0.00 | 0.00 |
September | 779.51 | 0.09 | 779.42 | 2660.58 | 46.58 | 0.00 | 0.00 | 0.00 |
October | 691.02 | 0.00 | 691.02 | 1906.60 | 220.87 | 0.00 | 0.00 | 0.00 |
November | 593.23 | 0.00 | 593.23 | 1212.60 | 579.48 | 0.00 | 0.00 | 0.00 |
December | 523.03 | 0.00 | 523.03 | 733.70 | 978.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 756.36 | 9.90 | 746.46 | 2027.39 | 454.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 523.03 | 0.00 | 523.03 | 670.57 | 0.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1001.81 | 55.62 | 946.19 | 3568.78 | 1166.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 675.79 | 204.46 | 471.33 | 930.91 | 763.19 | 0.00 | 0.00 | 0.00 |
February | 736.45 | 199.58 | 536.87 | 1114.20 | 661.64 | 0.00 | 0.00 | 0.00 |
March | 813.49 | 200.49 | 612.99 | 1411.78 | 526.01 | 0.00 | 0.00 | 0.00 |
April | 990.45 | 288.59 | 701.87 | 2014.58 | 353.78 | 0.00 | 0.00 | 0.00 |
May | 1106.86 | 352.65 | 754.21 | 2728.52 | 92.63 | 0.00 | 0.00 | 0.00 |
June | 1084.00 | 331.50 | 752.50 | 2882.81 | 22.60 | 0.00 | 0.00 | 0.00 |
July | 1011.74 | 291.68 | 720.06 | 3105.24 | 0.72 | 0.00 | 0.00 | 0.00 |
August | 1036.01 | 317.97 | 718.04 | 3210.84 | 0.07 | 0.00 | 0.00 | 0.00 |
September | 973.97 | 301.04 | 672.93 | 2606.10 | 30.66 | 0.00 | 0.00 | 0.00 |
October | 883.78 | 288.73 | 595.05 | 2039.89 | 146.00 | 0.00 | 0.00 | 0.00 |
November | 740.61 | 234.59 | 506.02 | 1414.68 | 383.10 | 0.00 | 0.00 | 0.00 |
December | 599.45 | 164.47 | 434.99 | 903.54 | 642.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 888.31 | 264.91 | 623.39 | 2035.60 | 300.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.45 | 164.47 | 434.99 | 903.54 | 0.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1106.86 | 352.65 | 754.21 | 3210.84 | 763.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1811.03 | 851.45 | 959.59 | 2830.42 | 1241.30 | 0.00 | 0.00 | 0.00 |
February | 1700.64 | 695.64 | 1005.00 | 2822.27 | 1077.48 | 0.00 | 0.00 | 0.00 |
March | 1399.70 | 380.01 | 1019.69 | 2598.33 | 857.60 | 0.00 | 0.00 | 0.00 |
April | 1100.27 | 116.65 | 983.62 | 2425.76 | 555.43 | 0.00 | 0.00 | 0.00 |
May | 932.02 | 14.27 | 917.75 | 2764.97 | 137.45 | 0.00 | 0.00 | 0.00 |
June | 877.75 | 1.09 | 876.67 | 2945.99 | 25.84 | 0.00 | 0.00 | 0.00 |
July | 877.73 | 7.46 | 870.27 | 3458.53 | 0.56 | 0.00 | 0.00 | 0.00 |
August | 1018.10 | 72.14 | 945.96 | 3873.76 | 0.10 | 0.00 | 0.00 | 0.00 |
September | 1342.37 | 307.64 | 1034.73 | 3829.29 | 53.18 | 0.00 | 0.00 | 0.00 |
October | 1757.43 | 698.68 | 1058.75 | 3977.26 | 252.18 | 0.00 | 0.00 | 0.00 |
November | 1938.80 | 934.65 | 1004.15 | 3691.50 | 640.39 | 0.00 | 0.00 | 0.00 |
December | 1799.79 | 889.04 | 910.75 | 2993.44 | 1060.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1377.71 | 412.56 | 965.15 | 3186.84 | 488.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 877.73 | 1.09 | 870.27 | 2425.76 | 0.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1938.80 | 934.65 | 1058.75 | 3977.26 | 1241.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 662.73 | 190.34 | 472.39 | 942.58 | 848.12 | 0.00 | 0.00 | 0.00 |
February | 756.77 | 215.80 | 540.97 | 1176.10 | 733.39 | 0.00 | 0.00 | 0.00 |
March | 896.42 | 265.39 | 631.03 | 1570.41 | 594.49 | 0.00 | 0.00 | 0.00 |
April | 979.63 | 275.22 | 704.41 | 1988.48 | 411.59 | 0.00 | 0.00 | 0.00 |
May | 1066.33 | 319.19 | 747.13 | 2651.22 | 117.67 | 0.00 | 0.00 | 0.00 |
June | 1101.96 | 347.37 | 754.59 | 2907.97 | 31.48 | 0.00 | 0.00 | 0.00 |
July | 1010.93 | 289.21 | 721.72 | 3071.18 | 1.58 | 0.00 | 0.00 | 0.00 |
August | 1037.10 | 315.32 | 721.78 | 3158.07 | 0.53 | 0.00 | 0.00 | 0.00 |
September | 986.55 | 309.95 | 676.60 | 2609.53 | 45.04 | 0.00 | 0.00 | 0.00 |
October | 876.75 | 283.22 | 593.54 | 2027.49 | 186.80 | 0.00 | 0.00 | 0.00 |
November | 753.46 | 246.41 | 507.05 | 1464.00 | 444.30 | 0.00 | 0.00 | 0.00 |
December | 630.76 | 190.67 | 440.10 | 988.43 | 728.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 897.12 | 270.86 | 626.26 | 2051.29 | 343.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 630.76 | 190.34 | 440.10 | 942.58 | 0.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1101.96 | 347.37 | 754.59 | 3158.07 | 848.12 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.320996E+09 | 0.747745E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.409647E+09 | 0.568080E+09 |
March | 0.395235E+09 | 0.00 | 0.395235E+09 | 0.666458E+09 | 0.470265E+09 |
April | 0.430936E+09 | 887921.69 | 0.430048E+09 | 0.940491E+09 | 0.278653E+09 |
May | 0.501225E+09 | 14700635.90 | 0.486525E+09 | 0.149403E+10 | 67536009.71 |
June | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.166220E+10 | 17322625.40 |
July | 0.492435E+09 | 14188242.10 | 0.478247E+09 | 0.190445E+10 | 700607.82 |
August | 0.458415E+09 | 3791545.17 | 0.454623E+09 | 0.185058E+10 | 195284.33 |
September | 0.404104E+09 | 46306.58 | 0.404057E+09 | 0.137774E+10 | 22821291.41 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.101226E+10 | 0.115162E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.613056E+09 | 0.324139E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.360301E+09 | 0.622060E+09 |
Annual Sum or Average | 0.477055E+10 | 62447133.55 | 0.470810E+10 | 0.126122E+11 | 0.323468E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.320996E+09 | 195284.33 |
Maximum of Months | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.190445E+10 | 0.747745E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.320995E+09 | 0.747745E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.409647E+09 | 0.568080E+09 |
March | 0.395234E+09 | 0.00 | 0.395234E+09 | 0.666458E+09 | 0.470265E+09 |
April | 0.430936E+09 | 887920.63 | 0.430048E+09 | 0.940491E+09 | 0.278652E+09 |
May | 0.501225E+09 | 14700618.26 | 0.486524E+09 | 0.149403E+10 | 67535917.98 |
June | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.166220E+10 | 17322574.67 |
July | 0.492435E+09 | 14188225.07 | 0.478246E+09 | 0.190445E+10 | 700602.90 |
August | 0.458414E+09 | 3791540.62 | 0.454623E+09 | 0.185058E+10 | 195282.61 |
September | 0.404103E+09 | 46306.53 | 0.404057E+09 | 0.137774E+10 | 22821246.49 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.101226E+10 | 0.115161E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.613056E+09 | 0.324139E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.360301E+09 | 0.622060E+09 |
Annual Sum or Average | 0.477054E+10 | 62447058.62 | 0.470809E+10 | 0.126122E+11 | 0.323468E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.320995E+09 | 195282.61 |
Maximum of Months | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.190445E+10 | 0.747745E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.320996E+09 | 0.747745E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.409647E+09 | 0.568080E+09 |
March | 0.395235E+09 | 0.00 | 0.395235E+09 | 0.666458E+09 | 0.470265E+09 |
April | 0.430936E+09 | 887921.69 | 0.430048E+09 | 0.940491E+09 | 0.278653E+09 |
May | 0.501225E+09 | 14700635.90 | 0.486525E+09 | 0.149403E+10 | 67536009.71 |
June | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.166220E+10 | 17322625.40 |
July | 0.492435E+09 | 14188242.10 | 0.478247E+09 | 0.190445E+10 | 700607.82 |
August | 0.458415E+09 | 3791545.17 | 0.454623E+09 | 0.185058E+10 | 195284.33 |
September | 0.404104E+09 | 46306.58 | 0.404057E+09 | 0.137774E+10 | 22821291.41 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.101226E+10 | 0.115162E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.613056E+09 | 0.324139E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.360301E+09 | 0.622060E+09 |
Annual Sum or Average | 0.477055E+10 | 62447133.55 | 0.470810E+10 | 0.126122E+11 | 0.323468E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.320996E+09 | 195284.33 |
Maximum of Months | 0.519345E+09 | 28832482.11 | 0.490513E+09 | 0.190445E+10 | 0.747745E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300179E+09 | 0.00 | 0.300179E+09 | 0.320995E+09 | 0.747745E+09 |
February | 0.310792E+09 | 0.00 | 0.310792E+09 | 0.409647E+09 | 0.568080E+09 |
March | 0.395234E+09 | 0.00 | 0.395234E+09 | 0.666458E+09 | 0.470265E+09 |
April | 0.430936E+09 | 887920.63 | 0.430048E+09 | 0.940491E+09 | 0.278652E+09 |
May | 0.501225E+09 | 14700618.26 | 0.486524E+09 | 0.149403E+10 | 67535917.98 |
June | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.166220E+10 | 17322574.67 |
July | 0.492435E+09 | 14188225.07 | 0.478246E+09 | 0.190445E+10 | 700602.90 |
August | 0.458414E+09 | 3791540.62 | 0.454623E+09 | 0.185058E+10 | 195282.61 |
September | 0.404103E+09 | 46306.53 | 0.404057E+09 | 0.137774E+10 | 22821246.49 |
October | 0.370170E+09 | 0.00 | 0.370170E+09 | 0.101226E+10 | 0.115161E+09 |
November | 0.307532E+09 | 0.00 | 0.307532E+09 | 0.613056E+09 | 0.324139E+09 |
December | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.360301E+09 | 0.622060E+09 |
Annual Sum or Average | 0.477054E+10 | 62447058.62 | 0.470809E+10 | 0.126122E+11 | 0.323468E+10 |
Minimum of Months | 0.280178E+09 | 0.00 | 0.280178E+09 | 0.320995E+09 | 195282.61 |
Maximum of Months | 0.519345E+09 | 28832447.51 | 0.490512E+09 | 0.190445E+10 | 0.747745E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.300167E+09 | 0.00 | 0.300167E+09 | 0.320983E+09 | 0.747715E+09 |
February | 0.310779E+09 | 0.00 | 0.310779E+09 | 0.409631E+09 | 0.568057E+09 |
March | 0.395219E+09 | 0.00 | 0.395219E+09 | 0.666431E+09 | 0.470246E+09 |
April | 0.430919E+09 | 887885.91 | 0.430031E+09 | 0.940453E+09 | 0.278641E+09 |
May | 0.501205E+09 | 14700043.40 | 0.486505E+09 | 0.149397E+10 | 67533287.71 |
June | 0.519324E+09 | 28831320.03 | 0.490493E+09 | 0.166213E+10 | 17321927.22 |
July | 0.492415E+09 | 14187670.25 | 0.478227E+09 | 0.190437E+10 | 700579.59 |
August | 0.458396E+09 | 3791392.35 | 0.454605E+09 | 0.185051E+10 | 195276.46 |
September | 0.404087E+09 | 46304.72 | 0.404041E+09 | 0.137768E+10 | 22820371.61 |
October | 0.370155E+09 | 0.00 | 0.370155E+09 | 0.101222E+10 | 0.115157E+09 |
November | 0.307520E+09 | 0.00 | 0.307520E+09 | 0.613032E+09 | 0.324126E+09 |
December | 0.280167E+09 | 0.00 | 0.280167E+09 | 0.360287E+09 | 0.622035E+09 |
Annual Sum or Average | 0.477035E+10 | 62444616.66 | 0.470791E+10 | 0.126117E+11 | 0.323455E+10 |
Minimum of Months | 0.280167E+09 | 0.00 | 0.280167E+09 | 0.320983E+09 | 195276.46 |
Maximum of Months | 0.519324E+09 | 28831320.03 | 0.490493E+09 | 0.190437E+10 | 0.747715E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603349E+09 | 0.182543E+09 | 0.420806E+09 | 0.802883E+09 | 0.769450E+09 |
February | 0.593881E+09 | 0.160945E+09 | 0.432936E+09 | 0.889728E+09 | 0.584264E+09 |
March | 0.726289E+09 | 0.179004E+09 | 0.547285E+09 | 0.127038E+10 | 0.482417E+09 |
April | 0.855761E+09 | 0.249341E+09 | 0.606421E+09 | 0.176670E+10 | 0.283039E+09 |
May | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.247113E+10 | 72165227.72 |
June | 0.936584E+09 | 0.286418E+09 | 0.650166E+09 | 0.252133E+10 | 15795385.56 |
July | 0.903295E+09 | 0.260418E+09 | 0.642877E+09 | 0.280549E+10 | 492499.28 |
August | 0.924959E+09 | 0.283882E+09 | 0.641076E+09 | 0.288689E+10 | 18831.21 |
September | 0.841518E+09 | 0.260103E+09 | 0.581415E+09 | 0.228055E+10 | 22945811.86 |
October | 0.789047E+09 | 0.257782E+09 | 0.531265E+09 | 0.184283E+10 | 0.115112E+09 |
November | 0.639894E+09 | 0.202686E+09 | 0.437208E+09 | 0.123331E+10 | 0.327931E+09 |
December | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.792675E+09 | 0.622596E+09 |
Annual Sum or Average | 0.933799E+10 | 0.278481E+10 | 0.655318E+10 | 0.215639E+11 | 0.329623E+10 |
Minimum of Months | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.792675E+09 | 18831.21 |
Maximum of Months | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.288689E+10 | 0.769450E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603349E+09 | 0.182543E+09 | 0.420806E+09 | 0.802883E+09 | 0.769450E+09 |
February | 0.593881E+09 | 0.160945E+09 | 0.432936E+09 | 0.889728E+09 | 0.584264E+09 |
March | 0.726289E+09 | 0.179004E+09 | 0.547285E+09 | 0.127038E+10 | 0.482417E+09 |
April | 0.855761E+09 | 0.249341E+09 | 0.606421E+09 | 0.176670E+10 | 0.283039E+09 |
May | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.247113E+10 | 72165227.72 |
June | 0.936584E+09 | 0.286418E+09 | 0.650166E+09 | 0.252133E+10 | 15795385.56 |
July | 0.903295E+09 | 0.260418E+09 | 0.642877E+09 | 0.280549E+10 | 492499.28 |
August | 0.924959E+09 | 0.283882E+09 | 0.641076E+09 | 0.288689E+10 | 18831.21 |
September | 0.841518E+09 | 0.260103E+09 | 0.581415E+09 | 0.228055E+10 | 22945811.86 |
October | 0.789047E+09 | 0.257782E+09 | 0.531265E+09 | 0.184283E+10 | 0.115112E+09 |
November | 0.639894E+09 | 0.202686E+09 | 0.437208E+09 | 0.123331E+10 | 0.327931E+09 |
December | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.792675E+09 | 0.622596E+09 |
Annual Sum or Average | 0.933799E+10 | 0.278481E+10 | 0.655318E+10 | 0.215639E+11 | 0.329623E+10 |
Minimum of Months | 0.535197E+09 | 0.146836E+09 | 0.388361E+09 | 0.792675E+09 | 18831.21 |
Maximum of Months | 0.988214E+09 | 0.314850E+09 | 0.673364E+09 | 0.288689E+10 | 0.769450E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603338E+09 | 0.182539E+09 | 0.420799E+09 | 0.802868E+09 | 0.769436E+09 |
February | 0.593870E+09 | 0.160942E+09 | 0.432929E+09 | 0.889712E+09 | 0.584253E+09 |
March | 0.726276E+09 | 0.179000E+09 | 0.547275E+09 | 0.127036E+10 | 0.482408E+09 |
April | 0.855746E+09 | 0.249336E+09 | 0.606409E+09 | 0.176667E+10 | 0.283034E+09 |
May | 0.988196E+09 | 0.314844E+09 | 0.673351E+09 | 0.247108E+10 | 72163909.10 |
June | 0.936567E+09 | 0.286413E+09 | 0.650155E+09 | 0.252128E+10 | 15795096.95 |
July | 0.903278E+09 | 0.260414E+09 | 0.642865E+09 | 0.280544E+10 | 492490.28 |
August | 0.924942E+09 | 0.283877E+09 | 0.641065E+09 | 0.288684E+10 | 18830.86 |
September | 0.841503E+09 | 0.260099E+09 | 0.581404E+09 | 0.228051E+10 | 22945392.59 |
October | 0.789033E+09 | 0.257777E+09 | 0.531255E+09 | 0.184280E+10 | 0.115110E+09 |
November | 0.639882E+09 | 0.202682E+09 | 0.437200E+09 | 0.123329E+10 | 0.327925E+09 |
December | 0.535187E+09 | 0.146834E+09 | 0.388353E+09 | 0.792660E+09 | 0.622585E+09 |
Annual Sum or Average | 0.933782E+10 | 0.278476E+10 | 0.655306E+10 | 0.215635E+11 | 0.329617E+10 |
Minimum of Months | 0.535187E+09 | 0.146834E+09 | 0.388353E+09 | 0.792660E+09 | 18830.86 |
Maximum of Months | 0.988196E+09 | 0.314844E+09 | 0.673351E+09 | 0.288684E+10 | 0.769436E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970147E+09 | 0.456110E+09 | 0.514037E+09 | 0.151851E+10 | 0.720119E+09 |
February | 0.822847E+09 | 0.336580E+09 | 0.486266E+09 | 0.137316E+10 | 0.563305E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.140227E+10 | 0.482997E+09 |
April | 0.570387E+09 | 60471832.51 | 0.509915E+09 | 0.126299E+10 | 0.290202E+09 |
May | 0.499273E+09 | 7645866.55 | 0.491627E+09 | 0.148937E+10 | 69512088.46 |
June | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.152247E+10 | 13705779.89 |
July | 0.470187E+09 | 3995158.92 | 0.466192E+09 | 0.184816E+10 | 398419.71 |
August | 0.545380E+09 | 38642379.00 | 0.506738E+09 | 0.205015E+10 | 150646.13 |
September | 0.695894E+09 | 0.159484E+09 | 0.536409E+09 | 0.200018E+10 | 25498559.51 |
October | 0.941430E+09 | 0.374271E+09 | 0.567158E+09 | 0.214965E+10 | 0.127321E+09 |
November | 0.100509E+10 | 0.484526E+09 | 0.520559E+09 | 0.193225E+10 | 0.336515E+09 |
December | 0.964125E+09 | 0.476248E+09 | 0.487876E+09 | 0.160706E+10 | 0.611131E+09 |
Annual Sum or Average | 0.868959E+10 | 0.260211E+10 | 0.608748E+10 | 0.201562E+11 | 0.324086E+10 |
Minimum of Months | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.126299E+10 | 150646.13 |
Maximum of Months | 0.100509E+10 | 0.484526E+09 | 0.567158E+09 | 0.214965E+10 | 0.720119E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970145E+09 | 0.456109E+09 | 0.514036E+09 | 0.151851E+10 | 0.720119E+09 |
February | 0.822846E+09 | 0.336580E+09 | 0.486266E+09 | 0.137316E+10 | 0.563305E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.140227E+10 | 0.482997E+09 |
April | 0.570387E+09 | 60471759.95 | 0.509915E+09 | 0.126299E+10 | 0.290202E+09 |
May | 0.499272E+09 | 7645857.37 | 0.491627E+09 | 0.148937E+10 | 69511996.88 |
June | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.152247E+10 | 13705739.86 |
July | 0.470187E+09 | 3995154.13 | 0.466192E+09 | 0.184816E+10 | 398416.61 |
August | 0.545380E+09 | 38642332.63 | 0.506737E+09 | 0.205015E+10 | 150644.57 |
September | 0.695893E+09 | 0.159484E+09 | 0.536409E+09 | 0.200018E+10 | 25498511.03 |
October | 0.941429E+09 | 0.374271E+09 | 0.567158E+09 | 0.214964E+10 | 0.127321E+09 |
November | 0.100508E+10 | 0.484525E+09 | 0.520559E+09 | 0.193225E+10 | 0.336515E+09 |
December | 0.964123E+09 | 0.476248E+09 | 0.487876E+09 | 0.160706E+10 | 0.611131E+09 |
Annual Sum or Average | 0.868958E+10 | 0.260210E+10 | 0.608748E+10 | 0.201562E+11 | 0.324085E+10 |
Minimum of Months | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.126299E+10 | 150644.57 |
Maximum of Months | 0.100508E+10 | 0.484525E+09 | 0.567158E+09 | 0.214964E+10 | 0.720119E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970147E+09 | 0.456110E+09 | 0.514037E+09 | 0.151851E+10 | 0.720119E+09 |
February | 0.822847E+09 | 0.336580E+09 | 0.486266E+09 | 0.137316E+10 | 0.563305E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.140227E+10 | 0.482997E+09 |
April | 0.570387E+09 | 60471832.51 | 0.509915E+09 | 0.126299E+10 | 0.290202E+09 |
May | 0.499273E+09 | 7645866.55 | 0.491627E+09 | 0.148937E+10 | 69512088.46 |
June | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.152247E+10 | 13705779.89 |
July | 0.470187E+09 | 3995158.92 | 0.466192E+09 | 0.184816E+10 | 398419.71 |
August | 0.545380E+09 | 38642379.00 | 0.506738E+09 | 0.205015E+10 | 150646.13 |
September | 0.695894E+09 | 0.159484E+09 | 0.536409E+09 | 0.200018E+10 | 25498559.51 |
October | 0.941430E+09 | 0.374271E+09 | 0.567158E+09 | 0.214965E+10 | 0.127321E+09 |
November | 0.100509E+10 | 0.484526E+09 | 0.520559E+09 | 0.193225E+10 | 0.336515E+09 |
December | 0.964125E+09 | 0.476248E+09 | 0.487876E+09 | 0.160706E+10 | 0.611131E+09 |
Annual Sum or Average | 0.868959E+10 | 0.260211E+10 | 0.608748E+10 | 0.201562E+11 | 0.324086E+10 |
Minimum of Months | 0.455032E+09 | 563119.71 | 0.454469E+09 | 0.126299E+10 | 150646.13 |
Maximum of Months | 0.100509E+10 | 0.484526E+09 | 0.567158E+09 | 0.214965E+10 | 0.720119E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970145E+09 | 0.456109E+09 | 0.514036E+09 | 0.151851E+10 | 0.720119E+09 |
February | 0.822846E+09 | 0.336580E+09 | 0.486266E+09 | 0.137316E+10 | 0.563305E+09 |
March | 0.749801E+09 | 0.203567E+09 | 0.546234E+09 | 0.140227E+10 | 0.482997E+09 |
April | 0.570387E+09 | 60471759.95 | 0.509915E+09 | 0.126299E+10 | 0.290202E+09 |
May | 0.499272E+09 | 7645857.37 | 0.491627E+09 | 0.148937E+10 | 69511996.88 |
June | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.152247E+10 | 13705739.86 |
July | 0.470187E+09 | 3995154.13 | 0.466192E+09 | 0.184816E+10 | 398416.61 |
August | 0.545380E+09 | 38642332.63 | 0.506737E+09 | 0.205015E+10 | 150644.57 |
September | 0.695893E+09 | 0.159484E+09 | 0.536409E+09 | 0.200018E+10 | 25498511.03 |
October | 0.941429E+09 | 0.374271E+09 | 0.567158E+09 | 0.214964E+10 | 0.127321E+09 |
November | 0.100508E+10 | 0.484525E+09 | 0.520559E+09 | 0.193225E+10 | 0.336515E+09 |
December | 0.964123E+09 | 0.476248E+09 | 0.487876E+09 | 0.160706E+10 | 0.611131E+09 |
Annual Sum or Average | 0.868958E+10 | 0.260210E+10 | 0.608748E+10 | 0.201562E+11 | 0.324085E+10 |
Minimum of Months | 0.455032E+09 | 563119.04 | 0.454469E+09 | 0.126299E+10 | 150644.57 |
Maximum of Months | 0.100508E+10 | 0.484525E+09 | 0.567158E+09 | 0.214964E+10 | 0.720119E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.970107E+09 | 0.456091E+09 | 0.514016E+09 | 0.151845E+10 | 0.720090E+09 |
February | 0.822813E+09 | 0.336567E+09 | 0.486247E+09 | 0.137311E+10 | 0.563283E+09 |
March | 0.749771E+09 | 0.203559E+09 | 0.546212E+09 | 0.140221E+10 | 0.482978E+09 |
April | 0.570364E+09 | 60469395.23 | 0.509895E+09 | 0.126294E+10 | 0.290190E+09 |
May | 0.499253E+09 | 7645558.38 | 0.491607E+09 | 0.148931E+10 | 69509286.82 |
June | 0.455014E+09 | 563097.02 | 0.454451E+09 | 0.152241E+10 | 13705227.49 |
July | 0.470168E+09 | 3994997.90 | 0.466173E+09 | 0.184809E+10 | 398403.65 |
August | 0.545358E+09 | 38640821.54 | 0.506717E+09 | 0.205007E+10 | 150640.06 |
September | 0.695866E+09 | 0.159478E+09 | 0.536388E+09 | 0.200010E+10 | 25497531.81 |
October | 0.941392E+09 | 0.374256E+09 | 0.567135E+09 | 0.214956E+10 | 0.127316E+09 |
November | 0.100504E+10 | 0.484506E+09 | 0.520538E+09 | 0.193217E+10 | 0.336501E+09 |
December | 0.964086E+09 | 0.476229E+09 | 0.487857E+09 | 0.160700E+10 | 0.611107E+09 |
Annual Sum or Average | 0.868924E+10 | 0.260200E+10 | 0.608724E+10 | 0.201554E+11 | 0.324073E+10 |
Minimum of Months | 0.455014E+09 | 563097.02 | 0.454451E+09 | 0.126294E+10 | 150640.06 |
Maximum of Months | 0.100504E+10 | 0.484506E+09 | 0.567135E+09 | 0.214956E+10 | 0.720090E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591693E+09 | 0.169939E+09 | 0.421754E+09 | 0.804838E+09 | 0.909079E+09 |
February | 0.610267E+09 | 0.174024E+09 | 0.436243E+09 | 0.917266E+09 | 0.724786E+09 |
March | 0.800331E+09 | 0.236940E+09 | 0.563391E+09 | 0.137385E+10 | 0.644169E+09 |
April | 0.846411E+09 | 0.237796E+09 | 0.608615E+09 | 0.168201E+10 | 0.436838E+09 |
May | 0.952025E+09 | 0.284979E+09 | 0.667045E+09 | 0.236164E+10 | 0.115425E+09 |
June | 0.952101E+09 | 0.300128E+09 | 0.651974E+09 | 0.247684E+10 | 40959309.16 |
July | 0.902565E+09 | 0.258206E+09 | 0.644359E+09 | 0.267360E+10 | 3893671.97 |
August | 0.925932E+09 | 0.281523E+09 | 0.644409E+09 | 0.267622E+10 | 4176628.12 |
September | 0.852387E+09 | 0.267796E+09 | 0.584591E+09 | 0.223577E+10 | 46724852.09 |
October | 0.782772E+09 | 0.252857E+09 | 0.529915E+09 | 0.178264E+10 | 0.198295E+09 |
November | 0.650996E+09 | 0.212897E+09 | 0.438100E+09 | 0.123067E+10 | 0.474164E+09 |
December | 0.563152E+09 | 0.170231E+09 | 0.392921E+09 | 0.826424E+09 | 0.848108E+09 |
Annual Sum or Average | 0.943063E+10 | 0.284732E+10 | 0.658332E+10 | 0.210418E+11 | 0.444662E+10 |
Minimum of Months | 0.563152E+09 | 0.169939E+09 | 0.392921E+09 | 0.804838E+09 | 3893671.97 |
Maximum of Months | 0.952101E+09 | 0.300128E+09 | 0.667045E+09 | 0.267622E+10 | 0.909079E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591693E+09 | 0.169939E+09 | 0.421754E+09 | 0.804838E+09 | 0.909079E+09 |
February | 0.610267E+09 | 0.174024E+09 | 0.436243E+09 | 0.917266E+09 | 0.724786E+09 |
March | 0.800331E+09 | 0.236940E+09 | 0.563391E+09 | 0.137385E+10 | 0.644169E+09 |
April | 0.846411E+09 | 0.237796E+09 | 0.608615E+09 | 0.168201E+10 | 0.436838E+09 |
May | 0.952025E+09 | 0.284979E+09 | 0.667045E+09 | 0.236164E+10 | 0.115425E+09 |
June | 0.952101E+09 | 0.300128E+09 | 0.651974E+09 | 0.247684E+10 | 40959309.16 |
July | 0.902565E+09 | 0.258206E+09 | 0.644359E+09 | 0.267360E+10 | 3893671.97 |
August | 0.925932E+09 | 0.281523E+09 | 0.644409E+09 | 0.267622E+10 | 4176628.12 |
September | 0.852387E+09 | 0.267796E+09 | 0.584591E+09 | 0.223577E+10 | 46724852.09 |
October | 0.782772E+09 | 0.252857E+09 | 0.529915E+09 | 0.178264E+10 | 0.198295E+09 |
November | 0.650996E+09 | 0.212897E+09 | 0.438100E+09 | 0.123067E+10 | 0.474164E+09 |
December | 0.563152E+09 | 0.170231E+09 | 0.392921E+09 | 0.826424E+09 | 0.848108E+09 |
Annual Sum or Average | 0.943063E+10 | 0.284732E+10 | 0.658332E+10 | 0.210418E+11 | 0.444662E+10 |
Minimum of Months | 0.563152E+09 | 0.169939E+09 | 0.392921E+09 | 0.804838E+09 | 3893671.97 |
Maximum of Months | 0.952101E+09 | 0.300128E+09 | 0.667045E+09 | 0.267622E+10 | 0.909079E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.591682E+09 | 0.169936E+09 | 0.421746E+09 | 0.804824E+09 | 0.909062E+09 |
February | 0.610256E+09 | 0.174020E+09 | 0.436235E+09 | 0.917249E+09 | 0.724773E+09 |
March | 0.800316E+09 | 0.236936E+09 | 0.563381E+09 | 0.137382E+10 | 0.644157E+09 |
April | 0.846395E+09 | 0.237792E+09 | 0.608604E+09 | 0.168198E+10 | 0.436830E+09 |
May | 0.952007E+09 | 0.284974E+09 | 0.667033E+09 | 0.236160E+10 | 0.115423E+09 |
June | 0.952084E+09 | 0.300122E+09 | 0.651962E+09 | 0.247679E+10 | 40958560.74 |
July | 0.902549E+09 | 0.258201E+09 | 0.644348E+09 | 0.267355E+10 | 3893600.82 |
August | 0.925915E+09 | 0.281518E+09 | 0.644397E+09 | 0.267617E+10 | 4176551.80 |
September | 0.852371E+09 | 0.267791E+09 | 0.584581E+09 | 0.223572E+10 | 46723998.32 |
October | 0.782758E+09 | 0.252852E+09 | 0.529905E+09 | 0.178261E+10 | 0.198291E+09 |
November | 0.650984E+09 | 0.212893E+09 | 0.438092E+09 | 0.123065E+10 | 0.474156E+09 |
December | 0.563141E+09 | 0.170228E+09 | 0.392914E+09 | 0.826409E+09 | 0.848092E+09 |
Annual Sum or Average | 0.943046E+10 | 0.284726E+10 | 0.658320E+10 | 0.210414E+11 | 0.444654E+10 |
Minimum of Months | 0.563141E+09 | 0.169936E+09 | 0.392914E+09 | 0.804824E+09 | 3893600.82 |
Maximum of Months | 0.952084E+09 | 0.300122E+09 | 0.667033E+09 | 0.267617E+10 | 0.909062E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.173442E+10 | 0.332908E+10 |
February | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.214613E+10 | 0.254338E+10 |
March | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.340655E+10 | 0.219031E+10 |
April | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.478274E+10 | 0.135400E+10 |
May | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.752966E+10 | 0.346739E+09 |
June | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.841637E+10 | 81235090.93 |
July | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.969886E+10 | 2055378.40 |
August | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.955891E+10 | 175674.91 |
September | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.699219E+10 | 0.113641E+09 |
October | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.516435E+10 | 0.573514E+09 |
November | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.316170E+10 | 0.153393E+10 |
December | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.193273E+10 | 0.275662E+10 |
Annual Sum or Average | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.645246E+11 | 0.148247E+11 |
Minimum of Months | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.173442E+10 | 175674.91 |
Maximum of Months | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.969886E+10 | 0.332908E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.243155E+10 | 0.215825E+10 |
February | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.266480E+10 | 0.166467E+10 |
March | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.377273E+10 | 0.144372E+10 |
April | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.523694E+10 | 0.917201E+09 |
May | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.735173E+10 | 0.238944E+09 |
June | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.751928E+10 | 53714880.28 |
July | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.838834E+10 | 1309390.04 |
August | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.865995E+10 | 103002.94 |
September | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.679877E+10 | 76059631.39 |
October | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.548459E+10 | 0.383569E+09 |
November | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.366197E+10 | 0.101352E+10 |
December | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.238051E+10 | 0.179703E+10 |
Annual Sum or Average | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.643512E+11 | 0.974809E+10 |
Minimum of Months | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.238051E+10 | 103002.94 |
Maximum of Months | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.865995E+10 | 0.215825E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.754395E+10 | 0.349078E+10 |
February | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.682943E+10 | 0.270311E+10 |
March | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.699076E+10 | 0.235250E+10 |
April | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.634226E+10 | 0.143915E+10 |
May | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.750311E+10 | 0.351948E+09 |
June | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.774010E+10 | 60510087.06 |
July | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.940612E+10 | 823123.79 |
August | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.105025E+11 | 134372.51 |
September | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.100253E+11 | 0.131112E+09 |
October | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.107233E+11 | 0.663217E+09 |
November | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.960646E+10 | 0.168996E+10 |
December | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.801049E+10 | 0.294631E+10 |
Annual Sum or Average | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.101224E+12 | 0.158296E+11 |
Minimum of Months | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.634226E+10 | 134372.51 |
Maximum of Months | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.107233E+11 | 0.349078E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.250751E+10 | 0.238728E+10 |
February | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.284838E+10 | 0.183855E+10 |
March | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.423232E+10 | 0.162826E+10 |
April | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.519575E+10 | 0.106998E+10 |
May | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.716396E+10 | 0.306343E+09 |
June | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.760167E+10 | 76949902.39 |
July | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.831160E+10 | 3177700.92 |
August | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.853875E+10 | 1123106.65 |
September | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.682440E+10 | 0.111580E+09 |
October | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.547118E+10 | 0.492928E+09 |
November | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.381589E+10 | 0.117335E+10 |
December | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.264529E+10 | 0.202629E+10 |
Annual Sum or Average | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.651567E+11 | 0.111158E+11 |
Minimum of Months | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.250751E+10 | 1123106.65 |
Maximum of Months | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.853875E+10 | 0.238728E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.179605E+10 | 0.312354E+10 |
February | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.216804E+10 | 0.243142E+10 |
March | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.339079E+10 | 0.213261E+10 |
April | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.473158E+10 | 0.135934E+10 |
May | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.743309E+10 | 0.364760E+09 |
June | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.831408E+10 | 90397820.31 |
July | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.955861E+10 | 3282562.09 |
August | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.943232E+10 | 345978.73 |
September | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.689624E+10 | 0.120734E+09 |
October | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.510664E+10 | 0.591575E+09 |
November | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.314305E+10 | 0.150202E+10 |
December | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.196515E+10 | 0.262201E+10 |
Annual Sum or Average | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.639356E+11 | 0.143420E+11 |
Minimum of Months | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.179605E+10 | 345978.73 |
Maximum of Months | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.955861E+10 | 0.312354E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.249336E+10 | 0.204413E+10 |
February | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.269547E+10 | 0.160063E+10 |
March | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.378130E+10 | 0.140886E+10 |
April | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.522180E+10 | 0.916991E+09 |
May | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.730806E+10 | 0.248090E+09 |
June | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.747225E+10 | 58584996.13 |
July | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.831707E+10 | 1915994.32 |
August | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.859991E+10 | 186116.04 |
September | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.675502E+10 | 79471979.38 |
October | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.546363E+10 | 0.391052E+09 |
November | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.366686E+10 | 0.992986E+09 |
December | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.242005E+10 | 0.172051E+10 |
Annual Sum or Average | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.641948E+11 | 0.946341E+10 |
Minimum of Months | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.242005E+10 | 186116.04 |
Maximum of Months | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.859991E+10 | 0.204413E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.758099E+10 | 0.332471E+10 |
February | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.682765E+10 | 0.260663E+10 |
March | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.695935E+10 | 0.229699E+10 |
April | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.628757E+10 | 0.143966E+10 |
May | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.740571E+10 | 0.368138E+09 |
June | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.763600E+10 | 66989923.27 |
July | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.926333E+10 | 1509080.70 |
August | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.103755E+11 | 274349.08 |
September | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.992552E+10 | 0.137833E+09 |
October | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.106527E+11 | 0.675442E+09 |
November | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.956837E+10 | 0.165990E+10 |
December | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.801764E+10 | 0.283964E+10 |
Annual Sum or Average | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.100500E+12 | 0.154177E+11 |
Minimum of Months | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.628757E+10 | 274349.08 |
Maximum of Months | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.106527E+11 | 0.332471E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.252460E+10 | 0.227159E+10 |
February | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.284522E+10 | 0.177422E+10 |
March | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.420618E+10 | 0.159228E+10 |
April | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.515415E+10 | 0.106684E+10 |
May | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.710104E+10 | 0.315166E+09 |
June | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.753746E+10 | 81591499.25 |
July | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.822584E+10 | 4219137.33 |
August | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.845856E+10 | 1411525.21 |
September | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.676389E+10 | 0.116753E+09 |
October | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.543044E+10 | 0.500318E+09 |
November | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.379469E+10 | 0.115164E+10 |
December | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.264740E+10 | 0.195059E+10 |
Annual Sum or Average | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.646895E+11 | 0.108266E+11 |
Minimum of Months | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.252460E+10 | 1411525.21 |
Maximum of Months | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.845856E+10 | 0.227159E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 599.23 | 1395.87 | 560.37 | 0.00 | 560.37 | 0.00 | 0.00 |
February | 846.65 | 1174.10 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1244.12 | 877.88 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1814.20 | 537.52 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2789.00 | 126.07 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3206.38 | 33.42 | 1001.81 | 55.62 | 946.20 | 0.00 | 0.00 |
July | 3555.17 | 1.31 | 919.26 | 26.49 | 892.78 | 0.00 | 0.00 |
August | 3454.62 | 0.36 | 855.76 | 7.08 | 848.68 | 0.00 | 0.00 |
September | 2657.65 | 44.02 | 779.51 | 0.09 | 779.43 | 0.00 | 0.00 |
October | 1889.66 | 214.98 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1182.58 | 625.26 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 672.60 | 1161.24 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 1999.64 | 512.85 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 599.23 | 0.36 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3555.17 | 1395.87 | 1001.81 | 55.62 | 946.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 899.28 | 861.83 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1103.33 | 724.53 | 736.46 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1422.91 | 540.34 | 813.49 | 200.50 | 612.99 | 0.00 | 0.00 |
April | 2044.78 | 327.59 | 990.46 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2767.82 | 80.83 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2918.19 | 18.28 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3142.33 | 0.55 | 1011.75 | 291.69 | 720.06 | 0.00 | 0.00 |
August | 3233.51 | 0.02 | 1036.01 | 317.97 | 718.05 | 0.00 | 0.00 |
September | 2639.51 | 26.56 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2064.09 | 128.93 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1427.43 | 379.55 | 740.61 | 234.59 | 506.03 | 0.00 | 0.00 |
December | 887.85 | 697.35 | 599.46 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2051.35 | 313.57 | 888.31 | 264.92 | 623.40 | 0.00 | 0.00 |
Minimum of Months | 887.85 | 0.02 | 599.46 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3233.51 | 861.83 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2834.71 | 1344.30 | 1811.04 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2838.02 | 1164.23 | 1700.64 | 695.64 | 1005.01 | 0.00 | 0.00 |
March | 2617.72 | 901.64 | 1399.71 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2436.30 | 559.80 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2780.31 | 129.76 | 932.03 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2936.84 | 26.44 | 877.76 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3450.10 | 0.74 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3827.16 | 0.28 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3858.34 | 49.19 | 1342.38 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 4012.89 | 237.68 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3727.31 | 649.14 | 1938.81 | 934.65 | 1004.16 | 0.00 | 0.00 |
December | 3000.02 | 1140.84 | 1799.80 | 889.05 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3195.72 | 513.83 | 1377.71 | 412.56 | 965.16 | 0.00 | 0.00 |
Minimum of Months | 2436.30 | 0.28 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 4012.89 | 1344.30 | 1938.81 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 901.47 | 1018.23 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1137.48 | 898.79 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1538.80 | 721.51 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 1946.76 | 505.60 | 979.64 | 275.23 | 704.41 | 0.00 | 0.00 |
May | 2645.19 | 129.28 | 1066.33 | 319.20 | 747.13 | 0.00 | 0.00 |
June | 2866.69 | 47.41 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 2994.61 | 4.36 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 2997.54 | 4.68 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2587.68 | 54.08 | 986.55 | 309.95 | 676.61 | 0.00 | 0.00 |
October | 1996.67 | 222.10 | 876.76 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1424.38 | 548.80 | 753.46 | 246.41 | 507.06 | 0.00 | 0.00 |
December | 925.65 | 949.94 | 630.77 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 2001.68 | 423.00 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 901.47 | 4.36 | 630.77 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 2997.54 | 1018.23 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 647.56 | 1242.94 | 560.36 | 0.00 | 560.36 | 0.00 | 0.00 |
February | 887.12 | 1051.33 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1271.86 | 817.77 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1845.19 | 522.38 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2811.25 | 129.46 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3247.06 | 31.34 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
July | 3621.14 | 0.77 | 919.26 | 26.49 | 892.77 | 0.00 | 0.00 |
August | 3568.89 | 0.07 | 855.75 | 7.08 | 848.67 | 0.00 | 0.00 |
September | 2697.60 | 43.84 | 779.51 | 0.09 | 779.42 | 0.00 | 0.00 |
October | 1928.15 | 214.13 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1219.79 | 591.79 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 721.60 | 1029.20 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 2046.06 | 470.09 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 647.56 | 0.07 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3621.14 | 1242.94 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 907.84 | 805.80 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1101.52 | 688.11 | 736.45 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1408.58 | 539.02 | 813.49 | 200.49 | 612.99 | 0.00 | 0.00 |
April | 2020.42 | 353.86 | 990.45 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2744.82 | 89.21 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2900.96 | 20.72 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3131.85 | 0.49 | 1011.74 | 291.68 | 720.06 | 0.00 | 0.00 |
August | 3233.25 | 0.04 | 1036.01 | 317.97 | 718.04 | 0.00 | 0.00 |
September | 2622.98 | 29.34 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2047.71 | 143.21 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1412.80 | 391.02 | 740.61 | 234.59 | 506.02 | 0.00 | 0.00 |
December | 888.78 | 670.93 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2040.56 | 309.11 | 888.31 | 264.91 | 623.39 | 0.00 | 0.00 |
Minimum of Months | 888.78 | 0.04 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3233.25 | 805.80 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2816.59 | 1303.31 | 1811.03 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2823.01 | 1117.36 | 1700.64 | 695.64 | 1005.00 | 0.00 | 0.00 |
March | 2610.05 | 878.32 | 1399.70 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2446.86 | 555.23 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2801.34 | 131.40 | 932.02 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2986.15 | 23.34 | 877.75 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3511.84 | 0.31 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3921.18 | 0.05 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3867.80 | 50.58 | 1342.37 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 4003.63 | 247.62 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3706.20 | 651.99 | 1938.80 | 934.65 | 1004.15 | 0.00 | 0.00 |
December | 2990.78 | 1100.03 | 1799.79 | 889.04 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3209.79 | 501.95 | 1377.71 | 412.56 | 965.15 | 0.00 | 0.00 |
Minimum of Months | 2446.86 | 0.05 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 4003.63 | 1303.31 | 1938.80 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 936.20 | 891.31 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1177.40 | 759.98 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1580.17 | 607.92 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 2004.53 | 412.80 | 979.63 | 275.22 | 704.41 | 0.00 | 0.00 |
May | 2674.72 | 114.38 | 1066.33 | 319.19 | 747.13 | 0.00 | 0.00 |
June | 2932.74 | 29.69 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 3103.20 | 1.19 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 3188.00 | 0.42 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2632.87 | 43.05 | 986.55 | 309.95 | 676.60 | 0.00 | 0.00 |
October | 2042.71 | 184.04 | 876.75 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1472.18 | 452.68 | 753.46 | 246.41 | 507.05 | 0.00 | 0.00 |
December | 987.64 | 756.53 | 630.76 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 2066.11 | 352.48 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 936.20 | 0.42 | 630.76 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 3188.00 | 891.31 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 670.57 | 1166.20 | 560.36 | 0.00 | 560.36 | 0.00 | 0.00 |
February | 896.18 | 1005.05 | 642.34 | 0.00 | 642.34 | 0.00 | 0.00 |
March | 1265.98 | 796.23 | 737.81 | 0.00 | 737.81 | 0.00 | 0.00 |
April | 1825.45 | 524.43 | 831.27 | 1.71 | 829.56 | 0.00 | 0.00 |
May | 2775.20 | 136.19 | 935.67 | 27.44 | 908.23 | 0.00 | 0.00 |
June | 3207.59 | 34.88 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
July | 3568.78 | 1.23 | 919.26 | 26.49 | 892.77 | 0.00 | 0.00 |
August | 3521.62 | 0.13 | 855.75 | 7.08 | 848.67 | 0.00 | 0.00 |
September | 2660.58 | 46.58 | 779.51 | 0.09 | 779.42 | 0.00 | 0.00 |
October | 1906.60 | 220.87 | 691.02 | 0.00 | 691.02 | 0.00 | 0.00 |
November | 1212.60 | 579.48 | 593.23 | 0.00 | 593.23 | 0.00 | 0.00 |
December | 733.70 | 978.95 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Annual Sum or Average | 2027.39 | 454.78 | 756.36 | 9.90 | 746.46 | 0.00 | 0.00 |
Minimum of Months | 670.57 | 0.13 | 523.03 | 0.00 | 523.03 | 0.00 | 0.00 |
Maximum of Months | 3568.78 | 1166.20 | 1001.81 | 55.62 | 946.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 930.91 | 763.19 | 675.79 | 204.46 | 471.33 | 0.00 | 0.00 |
February | 1114.20 | 661.64 | 736.45 | 199.58 | 536.87 | 0.00 | 0.00 |
March | 1411.78 | 526.01 | 813.49 | 200.49 | 612.99 | 0.00 | 0.00 |
April | 2014.58 | 353.78 | 990.45 | 288.59 | 701.87 | 0.00 | 0.00 |
May | 2728.52 | 92.63 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
June | 2882.81 | 22.60 | 1084.00 | 331.50 | 752.50 | 0.00 | 0.00 |
July | 3105.24 | 0.72 | 1011.74 | 291.68 | 720.06 | 0.00 | 0.00 |
August | 3210.84 | 0.07 | 1036.01 | 317.97 | 718.04 | 0.00 | 0.00 |
September | 2606.10 | 30.66 | 973.97 | 301.04 | 672.93 | 0.00 | 0.00 |
October | 2039.89 | 146.00 | 883.78 | 288.73 | 595.05 | 0.00 | 0.00 |
November | 1414.68 | 383.10 | 740.61 | 234.59 | 506.02 | 0.00 | 0.00 |
December | 903.54 | 642.36 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Annual Sum or Average | 2035.60 | 300.08 | 888.31 | 264.91 | 623.39 | 0.00 | 0.00 |
Minimum of Months | 903.54 | 0.07 | 599.45 | 164.47 | 434.99 | 0.00 | 0.00 |
Maximum of Months | 3210.84 | 763.19 | 1106.86 | 352.65 | 754.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2830.42 | 1241.30 | 1811.03 | 851.45 | 959.59 | 0.00 | 0.00 |
February | 2822.27 | 1077.48 | 1700.64 | 695.64 | 1005.00 | 0.00 | 0.00 |
March | 2598.33 | 857.60 | 1399.70 | 380.01 | 1019.69 | 0.00 | 0.00 |
April | 2425.76 | 555.43 | 1100.27 | 116.65 | 983.62 | 0.00 | 0.00 |
May | 2764.97 | 137.45 | 932.02 | 14.27 | 917.75 | 0.00 | 0.00 |
June | 2945.99 | 25.84 | 877.75 | 1.09 | 876.67 | 0.00 | 0.00 |
July | 3458.53 | 0.56 | 877.73 | 7.46 | 870.27 | 0.00 | 0.00 |
August | 3873.76 | 0.10 | 1018.10 | 72.14 | 945.96 | 0.00 | 0.00 |
September | 3829.29 | 53.18 | 1342.37 | 307.64 | 1034.73 | 0.00 | 0.00 |
October | 3977.26 | 252.18 | 1757.43 | 698.68 | 1058.75 | 0.00 | 0.00 |
November | 3691.50 | 640.39 | 1938.80 | 934.65 | 1004.15 | 0.00 | 0.00 |
December | 2993.44 | 1060.20 | 1799.79 | 889.04 | 910.75 | 0.00 | 0.00 |
Annual Sum or Average | 3186.84 | 488.89 | 1377.71 | 412.56 | 965.15 | 0.00 | 0.00 |
Minimum of Months | 2425.76 | 0.10 | 877.73 | 1.09 | 870.27 | 0.00 | 0.00 |
Maximum of Months | 3977.26 | 1241.30 | 1938.80 | 934.65 | 1058.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 942.58 | 848.12 | 662.73 | 190.34 | 472.39 | 0.00 | 0.00 |
February | 1176.10 | 733.39 | 756.77 | 215.80 | 540.97 | 0.00 | 0.00 |
March | 1570.41 | 594.49 | 896.42 | 265.39 | 631.03 | 0.00 | 0.00 |
April | 1988.48 | 411.59 | 979.63 | 275.22 | 704.41 | 0.00 | 0.00 |
May | 2651.22 | 117.67 | 1066.33 | 319.19 | 747.13 | 0.00 | 0.00 |
June | 2907.97 | 31.48 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
July | 3071.18 | 1.58 | 1010.93 | 289.21 | 721.72 | 0.00 | 0.00 |
August | 3158.07 | 0.53 | 1037.10 | 315.32 | 721.78 | 0.00 | 0.00 |
September | 2609.53 | 45.04 | 986.55 | 309.95 | 676.60 | 0.00 | 0.00 |
October | 2027.49 | 186.80 | 876.75 | 283.22 | 593.54 | 0.00 | 0.00 |
November | 1464.00 | 444.30 | 753.46 | 246.41 | 507.05 | 0.00 | 0.00 |
December | 988.43 | 728.27 | 630.76 | 190.67 | 440.10 | 0.00 | 0.00 |
Annual Sum or Average | 2051.29 | 343.31 | 897.12 | 270.86 | 626.26 | 0.00 | 0.00 |
Minimum of Months | 942.58 | 0.53 | 630.76 | 190.34 | 440.10 | 0.00 | 0.00 |
Maximum of Months | 3158.07 | 848.12 | 1101.96 | 347.37 | 754.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.160497E+10 | 0.373869E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.204822E+10 | 0.284038E+10 | 0.155395E+10 | 0.00 | 0.155395E+10 | 0.00 | 0.00 |
March | 0.333226E+10 | 0.235130E+10 | 0.197616E+10 | 0.00 | 0.197616E+10 | 0.00 | 0.00 |
April | 0.470242E+10 | 0.139325E+10 | 0.215466E+10 | 4439570.55 | 0.215022E+10 | 0.00 | 0.00 |
May | 0.747007E+10 | 0.337677E+09 | 0.250611E+10 | 73502551.72 | 0.243260E+10 | 0.00 | 0.00 |
June | 0.831093E+10 | 86612327.37 | 0.259670E+10 | 0.144161E+09 | 0.245254E+10 | 0.00 | 0.00 |
July | 0.952218E+10 | 3503001.03 | 0.246215E+10 | 70940604.60 | 0.239121E+10 | 0.00 | 0.00 |
August | 0.925285E+10 | 976410.33 | 0.229205E+10 | 18957563.92 | 0.227310E+10 | 0.00 | 0.00 |
September | 0.688863E+10 | 0.114105E+09 | 0.202050E+10 | 231530.94 | 0.202027E+10 | 0.00 | 0.00 |
October | 0.506126E+10 | 0.575803E+09 | 0.185084E+10 | 0.00 | 0.185084E+10 | 0.00 | 0.00 |
November | 0.306526E+10 | 0.162068E+10 | 0.153765E+10 | 0.00 | 0.153765E+10 | 0.00 | 0.00 |
December | 0.180149E+10 | 0.311027E+10 | 0.140088E+10 | 0.00 | 0.140088E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.630605E+11 | 0.161733E+11 | 0.238525E+11 | 0.312233E+09 | 0.235403E+11 | 0.00 | 0.00 |
Minimum of Months | 0.160497E+10 | 976410.33 | 0.140088E+10 | 0.00 | 0.140088E+10 | 0.00 | 0.00 |
Maximum of Months | 0.952218E+10 | 0.373869E+10 | 0.259670E+10 | 0.144161E+09 | 0.245254E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.240863E+10 | 0.230834E+10 | 0.181004E+10 | 0.547624E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.266917E+10 | 0.175278E+10 | 0.178163E+10 | 0.482831E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.381113E+10 | 0.144724E+10 | 0.217885E+10 | 0.537008E+09 | 0.164185E+10 | 0.00 | 0.00 |
April | 0.530006E+10 | 0.849113E+09 | 0.256727E+10 | 0.748018E+09 | 0.181925E+10 | 0.00 | 0.00 |
May | 0.741334E+10 | 0.216494E+09 | 0.296462E+10 | 0.944545E+09 | 0.202008E+10 | 0.00 | 0.00 |
June | 0.756394E+10 | 47385868.07 | 0.280974E+10 | 0.859248E+09 | 0.195049E+10 | 0.00 | 0.00 |
July | 0.841642E+10 | 1477488.84 | 0.270987E+10 | 0.781250E+09 | 0.192862E+10 | 0.00 | 0.00 |
August | 0.866063E+10 | 56493.28 | 0.277486E+10 | 0.851642E+09 | 0.192322E+10 | 0.00 | 0.00 |
September | 0.684161E+10 | 68837016.30 | 0.252454E+10 | 0.780305E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.552846E+10 | 0.345334E+09 | 0.236713E+10 | 0.773342E+09 | 0.159379E+10 | 0.00 | 0.00 |
November | 0.369991E+10 | 0.983787E+09 | 0.191967E+10 | 0.608054E+09 | 0.131162E+10 | 0.00 | 0.00 |
December | 0.237801E+10 | 0.186778E+10 | 0.160558E+10 | 0.440507E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.646913E+11 | 0.988862E+10 | 0.280138E+11 | 0.835437E+10 | 0.196594E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237801E+10 | 56493.28 | 0.160558E+10 | 0.440507E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.866063E+10 | 0.230834E+10 | 0.296462E+10 | 0.944545E+09 | 0.202008E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.759248E+10 | 0.360057E+10 | 0.485069E+10 | 0.228053E+10 | 0.257016E+10 | 0.00 | 0.00 |
February | 0.686574E+10 | 0.281650E+10 | 0.411420E+10 | 0.168289E+10 | 0.243131E+10 | 0.00 | 0.00 |
March | 0.701129E+10 | 0.241497E+10 | 0.374897E+10 | 0.101783E+10 | 0.273115E+10 | 0.00 | 0.00 |
April | 0.631490E+10 | 0.145100E+10 | 0.285191E+10 | 0.302357E+09 | 0.254956E+10 | 0.00 | 0.00 |
May | 0.744678E+10 | 0.347557E+09 | 0.249634E+10 | 38229006.22 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.761228E+10 | 68528267.01 | 0.227514E+10 | 2815574.52 | 0.227233E+10 | 0.00 | 0.00 |
July | 0.924075E+10 | 1992076.28 | 0.235092E+10 | 19975623.99 | 0.233094E+10 | 0.00 | 0.00 |
August | 0.102507E+11 | 753221.48 | 0.272688E+10 | 0.193210E+09 | 0.253367E+10 | 0.00 | 0.00 |
September | 0.100008E+11 | 0.127492E+09 | 0.347944E+10 | 0.797415E+09 | 0.268202E+10 | 0.00 | 0.00 |
October | 0.107481E+11 | 0.636599E+09 | 0.470711E+10 | 0.187134E+10 | 0.283577E+10 | 0.00 | 0.00 |
November | 0.966118E+10 | 0.168256E+10 | 0.502538E+10 | 0.242261E+10 | 0.260278E+10 | 0.00 | 0.00 |
December | 0.803525E+10 | 0.305563E+10 | 0.482058E+10 | 0.238122E+10 | 0.243936E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100780E+12 | 0.162041E+11 | 0.434476E+11 | 0.130104E+11 | 0.304372E+11 | 0.00 | 0.00 |
Minimum of Months | 0.631490E+10 | 753221.48 | 0.227514E+10 | 2815574.52 | 0.227233E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107481E+11 | 0.360057E+10 | 0.502538E+10 | 0.242261E+10 | 0.283577E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.241450E+10 | 0.272722E+10 | 0.177507E+10 | 0.509815E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.275178E+10 | 0.217435E+10 | 0.183079E+10 | 0.522068E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.412151E+10 | 0.193249E+10 | 0.240098E+10 | 0.710816E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.504601E+10 | 0.131051E+10 | 0.253922E+10 | 0.713384E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.708487E+10 | 0.346273E+09 | 0.285606E+10 | 0.854933E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.743047E+10 | 0.122877E+09 | 0.285629E+10 | 0.900378E+09 | 0.195591E+10 | 0.00 | 0.00 |
July | 0.802075E+10 | 11680944.76 | 0.270768E+10 | 0.774614E+09 | 0.193307E+10 | 0.00 | 0.00 |
August | 0.802861E+10 | 12529808.03 | 0.277778E+10 | 0.844564E+09 | 0.193322E+10 | 0.00 | 0.00 |
September | 0.670726E+10 | 0.140174E+09 | 0.255715E+10 | 0.803382E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.534789E+10 | 0.594881E+09 | 0.234830E+10 | 0.758567E+09 | 0.158974E+10 | 0.00 | 0.00 |
November | 0.369199E+10 | 0.142248E+10 | 0.195298E+10 | 0.638686E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.247926E+10 | 0.254431E+10 | 0.168944E+10 | 0.510689E+09 | 0.117876E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.631249E+11 | 0.133398E+11 | 0.282917E+11 | 0.854189E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.241450E+10 | 11680944.76 | 0.168944E+10 | 0.509815E+09 | 0.117876E+10 | 0.00 | 0.00 |
Maximum of Months | 0.802861E+10 | 0.272722E+10 | 0.285629E+10 | 0.900378E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.173442E+10 | 0.332908E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.214613E+10 | 0.254338E+10 | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.00 | 0.00 |
March | 0.340655E+10 | 0.219031E+10 | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.00 | 0.00 |
April | 0.478274E+10 | 0.135400E+10 | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.00 | 0.00 |
May | 0.752966E+10 | 0.346739E+09 | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.00 | 0.00 |
June | 0.841637E+10 | 81235090.93 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
July | 0.969886E+10 | 2055378.40 | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.00 | 0.00 |
August | 0.955891E+10 | 175674.91 | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.00 | 0.00 |
September | 0.699219E+10 | 0.113641E+09 | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.00 | 0.00 |
October | 0.516435E+10 | 0.573514E+09 | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.00 | 0.00 |
November | 0.316170E+10 | 0.153393E+10 | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.00 | 0.00 |
December | 0.193273E+10 | 0.275662E+10 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.645246E+11 | 0.148247E+11 | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.173442E+10 | 175674.91 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.969886E+10 | 0.332908E+10 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.243155E+10 | 0.215825E+10 | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.266480E+10 | 0.166467E+10 | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.377273E+10 | 0.144372E+10 | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.00 | 0.00 |
April | 0.523694E+10 | 0.917201E+09 | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.00 | 0.00 |
May | 0.735173E+10 | 0.238944E+09 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
June | 0.751928E+10 | 53714880.28 | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.00 | 0.00 |
July | 0.838834E+10 | 1309390.04 | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.00 | 0.00 |
August | 0.865995E+10 | 103002.94 | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.00 | 0.00 |
September | 0.679877E+10 | 76059631.39 | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.548459E+10 | 0.383569E+09 | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.00 | 0.00 |
November | 0.366197E+10 | 0.101352E+10 | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.00 | 0.00 |
December | 0.238051E+10 | 0.179703E+10 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.643512E+11 | 0.974809E+10 | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.00 | 0.00 |
Minimum of Months | 0.238051E+10 | 103002.94 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.865995E+10 | 0.215825E+10 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.754395E+10 | 0.349078E+10 | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.00 | 0.00 |
February | 0.682943E+10 | 0.270311E+10 | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.00 | 0.00 |
March | 0.699076E+10 | 0.235250E+10 | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.00 | 0.00 |
April | 0.634226E+10 | 0.143915E+10 | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.00 | 0.00 |
May | 0.750311E+10 | 0.351948E+09 | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.774010E+10 | 60510087.06 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
July | 0.940612E+10 | 823123.79 | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.00 | 0.00 |
August | 0.105025E+11 | 134372.51 | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.00 | 0.00 |
September | 0.100253E+11 | 0.131112E+09 | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.00 | 0.00 |
October | 0.107233E+11 | 0.663217E+09 | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.00 | 0.00 |
November | 0.960646E+10 | 0.168996E+10 | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.00 | 0.00 |
December | 0.801049E+10 | 0.294631E+10 | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101224E+12 | 0.158296E+11 | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.00 | 0.00 |
Minimum of Months | 0.634226E+10 | 134372.51 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107233E+11 | 0.349078E+10 | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.250751E+10 | 0.238728E+10 | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.284838E+10 | 0.183855E+10 | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.423232E+10 | 0.162826E+10 | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.519575E+10 | 0.106998E+10 | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.716396E+10 | 0.306343E+09 | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.760167E+10 | 76949902.39 | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.00 | 0.00 |
July | 0.831160E+10 | 3177700.92 | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.00 | 0.00 |
August | 0.853875E+10 | 1123106.65 | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.00 | 0.00 |
September | 0.682440E+10 | 0.111580E+09 | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.547118E+10 | 0.492928E+09 | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.00 | 0.00 |
November | 0.381589E+10 | 0.117335E+10 | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.264529E+10 | 0.202629E+10 | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.651567E+11 | 0.111158E+11 | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250751E+10 | 1123106.65 | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.853875E+10 | 0.238728E+10 | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.179605E+10 | 0.312354E+10 | 0.150088E+10 | 0.00 | 0.150088E+10 | 0.00 | 0.00 |
February | 0.216804E+10 | 0.243142E+10 | 0.155394E+10 | 0.00 | 0.155394E+10 | 0.00 | 0.00 |
March | 0.339079E+10 | 0.213261E+10 | 0.197615E+10 | 0.00 | 0.197615E+10 | 0.00 | 0.00 |
April | 0.473158E+10 | 0.135934E+10 | 0.215465E+10 | 4439554.79 | 0.215021E+10 | 0.00 | 0.00 |
May | 0.743309E+10 | 0.364760E+09 | 0.250610E+10 | 73502290.71 | 0.243259E+10 | 0.00 | 0.00 |
June | 0.831408E+10 | 90397820.31 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
July | 0.955861E+10 | 3282562.09 | 0.246214E+10 | 70940352.69 | 0.239120E+10 | 0.00 | 0.00 |
August | 0.943232E+10 | 345978.73 | 0.229205E+10 | 18957496.60 | 0.227309E+10 | 0.00 | 0.00 |
September | 0.689624E+10 | 0.120734E+09 | 0.202049E+10 | 231530.12 | 0.202026E+10 | 0.00 | 0.00 |
October | 0.510664E+10 | 0.591575E+09 | 0.185083E+10 | 0.00 | 0.185083E+10 | 0.00 | 0.00 |
November | 0.314305E+10 | 0.150202E+10 | 0.153764E+10 | 0.00 | 0.153764E+10 | 0.00 | 0.00 |
December | 0.196515E+10 | 0.262201E+10 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.639356E+11 | 0.143420E+11 | 0.238524E+11 | 0.312232E+09 | 0.235402E+11 | 0.00 | 0.00 |
Minimum of Months | 0.179605E+10 | 345978.73 | 0.140087E+10 | 0.00 | 0.140087E+10 | 0.00 | 0.00 |
Maximum of Months | 0.955861E+10 | 0.312354E+10 | 0.259669E+10 | 0.144161E+09 | 0.245253E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.249336E+10 | 0.204413E+10 | 0.181003E+10 | 0.547622E+09 | 0.126241E+10 | 0.00 | 0.00 |
February | 0.269547E+10 | 0.160063E+10 | 0.178163E+10 | 0.482829E+09 | 0.129880E+10 | 0.00 | 0.00 |
March | 0.378130E+10 | 0.140886E+10 | 0.217884E+10 | 0.537005E+09 | 0.164184E+10 | 0.00 | 0.00 |
April | 0.522180E+10 | 0.916991E+09 | 0.256726E+10 | 0.748014E+09 | 0.181924E+10 | 0.00 | 0.00 |
May | 0.730806E+10 | 0.248090E+09 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
June | 0.747225E+10 | 58584996.13 | 0.280972E+10 | 0.859245E+09 | 0.195048E+10 | 0.00 | 0.00 |
July | 0.831707E+10 | 1915994.32 | 0.270986E+10 | 0.781247E+09 | 0.192861E+10 | 0.00 | 0.00 |
August | 0.859991E+10 | 186116.04 | 0.277485E+10 | 0.851639E+09 | 0.192321E+10 | 0.00 | 0.00 |
September | 0.675502E+10 | 79471979.38 | 0.252453E+10 | 0.780302E+09 | 0.174423E+10 | 0.00 | 0.00 |
October | 0.546363E+10 | 0.391052E+09 | 0.236712E+10 | 0.773339E+09 | 0.159378E+10 | 0.00 | 0.00 |
November | 0.366686E+10 | 0.992986E+09 | 0.191966E+10 | 0.608051E+09 | 0.131161E+10 | 0.00 | 0.00 |
December | 0.242005E+10 | 0.172051E+10 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.641948E+11 | 0.946341E+10 | 0.280137E+11 | 0.835434E+10 | 0.196593E+11 | 0.00 | 0.00 |
Minimum of Months | 0.242005E+10 | 186116.04 | 0.160557E+10 | 0.440505E+09 | 0.116507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.859991E+10 | 0.204413E+10 | 0.296461E+10 | 0.944541E+09 | 0.202007E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.758099E+10 | 0.332471E+10 | 0.485067E+10 | 0.228052E+10 | 0.257015E+10 | 0.00 | 0.00 |
February | 0.682765E+10 | 0.260663E+10 | 0.411418E+10 | 0.168288E+10 | 0.243130E+10 | 0.00 | 0.00 |
March | 0.695935E+10 | 0.229699E+10 | 0.374896E+10 | 0.101782E+10 | 0.273114E+10 | 0.00 | 0.00 |
April | 0.628757E+10 | 0.143966E+10 | 0.285190E+10 | 0.302356E+09 | 0.254955E+10 | 0.00 | 0.00 |
May | 0.740571E+10 | 0.368138E+09 | 0.249633E+10 | 38228870.47 | 0.245811E+10 | 0.00 | 0.00 |
June | 0.763600E+10 | 66989923.27 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
July | 0.926333E+10 | 1509080.70 | 0.235091E+10 | 19975553.05 | 0.233093E+10 | 0.00 | 0.00 |
August | 0.103755E+11 | 274349.08 | 0.272687E+10 | 0.193210E+09 | 0.253366E+10 | 0.00 | 0.00 |
September | 0.992552E+10 | 0.137833E+09 | 0.347943E+10 | 0.797412E+09 | 0.268201E+10 | 0.00 | 0.00 |
October | 0.106527E+11 | 0.675442E+09 | 0.470709E+10 | 0.187133E+10 | 0.283576E+10 | 0.00 | 0.00 |
November | 0.956837E+10 | 0.165990E+10 | 0.502537E+10 | 0.242260E+10 | 0.260277E+10 | 0.00 | 0.00 |
December | 0.801764E+10 | 0.283964E+10 | 0.482056E+10 | 0.238121E+10 | 0.243935E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100500E+12 | 0.154177E+11 | 0.434474E+11 | 0.130104E+11 | 0.304370E+11 | 0.00 | 0.00 |
Minimum of Months | 0.628757E+10 | 274349.08 | 0.227513E+10 | 2815564.53 | 0.227232E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106527E+11 | 0.332471E+10 | 0.502537E+10 | 0.242260E+10 | 0.283576E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.252460E+10 | 0.227159E+10 | 0.177506E+10 | 0.509812E+09 | 0.126525E+10 | 0.00 | 0.00 |
February | 0.284522E+10 | 0.177422E+10 | 0.183078E+10 | 0.522065E+09 | 0.130872E+10 | 0.00 | 0.00 |
March | 0.420618E+10 | 0.159228E+10 | 0.240097E+10 | 0.710813E+09 | 0.169016E+10 | 0.00 | 0.00 |
April | 0.515415E+10 | 0.106684E+10 | 0.253921E+10 | 0.713381E+09 | 0.182583E+10 | 0.00 | 0.00 |
May | 0.710104E+10 | 0.315166E+09 | 0.285604E+10 | 0.854929E+09 | 0.200112E+10 | 0.00 | 0.00 |
June | 0.753746E+10 | 81591499.25 | 0.285628E+10 | 0.900374E+09 | 0.195590E+10 | 0.00 | 0.00 |
July | 0.822584E+10 | 4219137.33 | 0.270767E+10 | 0.774611E+09 | 0.193306E+10 | 0.00 | 0.00 |
August | 0.845856E+10 | 1411525.21 | 0.277777E+10 | 0.844560E+09 | 0.193321E+10 | 0.00 | 0.00 |
September | 0.676389E+10 | 0.116753E+09 | 0.255713E+10 | 0.803378E+09 | 0.175376E+10 | 0.00 | 0.00 |
October | 0.543044E+10 | 0.500318E+09 | 0.234829E+10 | 0.758564E+09 | 0.158973E+10 | 0.00 | 0.00 |
November | 0.379469E+10 | 0.115164E+10 | 0.195297E+10 | 0.638684E+09 | 0.131429E+10 | 0.00 | 0.00 |
December | 0.264740E+10 | 0.195059E+10 | 0.168944E+10 | 0.510687E+09 | 0.117875E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.646895E+11 | 0.108266E+11 | 0.282916E+11 | 0.854186E+10 | 0.197498E+11 | 0.00 | 0.00 |
Minimum of Months | 0.252460E+10 | 1411525.21 | 0.168944E+10 | 0.509812E+09 | 0.117875E+10 | 0.00 | 0.00 |
Maximum of Months | 0.845856E+10 | 0.227159E+10 | 0.285628E+10 | 0.900374E+09 | 0.200112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.281206E+11 | -0.271024E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101816E+10 | 58.97 | 0.00 | 0.00 |
February | 0.248586E+11 | -0.239380E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -920560792.1 | 58.97 | 0.00 | 0.00 |
March | 0.271882E+11 | -0.261648E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102343E+10 | 58.97 | 0.00 | 0.00 |
April | 0.223000E+11 | -0.213129E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987151123.7 | 58.97 | 0.00 | 0.00 |
May | 0.212852E+11 | -0.202636E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102163E+10 | 58.97 | 0.00 | 0.00 |
June | 0.192514E+11 | -0.182618E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989630527.8 | 58.96 | 0.00 | 0.00 |
July | 0.178336E+11 | -0.168161E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101750E+10 | 58.97 | 0.00 | 0.00 |
August | 0.202890E+11 | -0.192680E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102101E+10 | 58.96 | 0.00 | 0.00 |
September | 0.203451E+11 | -0.193592E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985945459.0 | 58.96 | 0.00 | 0.00 |
October | 0.234793E+11 | -0.224619E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101744E+10 | 58.97 | 0.00 | 0.00 |
November | 0.253889E+11 | -0.244051E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -983750757.2 | 58.98 | 0.00 | 0.00 |
December | 0.269665E+11 | -0.259502E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101632E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.277306E+12 | -0.265304E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120025E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.178336E+11 | -0.271024E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102343E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.281206E+11 | -0.168161E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -920560792.1 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4187.85 | 34.38 | 311.00 | 293.00 | 1081.44 | 25.75 | 306.67 | 280.33 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-08:09 | 2168.98 | 26.03 | 160.50 | 274.83 | 966.54 | 21.70 | 215.67 | 244.00 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1604.46 | 20.06 | 41.33 | 314.33 | 827.56 | 21.23 | 242.50 | 277.17 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:40 | 1258.39 | 18.99 | 0.67 | 322.83 | 663.56 | 20.27 | 226.17 | 284.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1073.66 | 18.93 | 0.00 | 349.67 | 586.61 | 20.25 | 186.33 | 304.17 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:10 | 1029.03 | 18.86 | 0.00 | 344.33 | 571.46 | 20.21 | 187.33 | 298.67 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1080.69 | 18.79 | 0.00 | 345.17 | 592.75 | 20.13 | 219.83 | 304.00 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1265.49 | 19.26 | 13.67 | 343.17 | 675.68 | 20.59 | 261.50 | 304.00 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 1577.57 | 20.02 | 71.00 | 318.67 | 826.79 | 21.36 | 258.00 | 284.83 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:19 | 2096.10 | 21.89 | 116.83 | 316.67 | 992.90 | 22.22 | 272.33 | 287.83 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3529.96 | 32.29 | 257.33 | 298.17 | 1121.01 | 25.39 | 312.67 | 281.83 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4175.93 | 34.74 | 308.17 | 289.00 | 1154.67 | 26.89 | 301.00 | 275.17 |
Annual Sum or Average | 4323.33 | 0.51 | 1994.77 | 23.19 | 1280.50 | 3809.83 | 819.08 | 21.99 | 2990.00 | 3426.67 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1029.03 | 18.79 | 0.00 | 274.83 | 571.46 | 20.13 | 186.33 | 244.00 | |
Maximum of Months | 405.33 | 0.53 | 0.48 | 4187.85 | 34.74 | 311.00 | 349.67 | 1154.67 | 26.89 | 312.67 | 304.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1543.18 | 23.78 | 112.00 | 275.33 | 805.53 | 23.84 | 173.00 | 236.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-07:40 | 1668.33 | 23.48 | 102.67 | 263.33 | 715.93 | 22.41 | 155.00 | 227.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1572.14 | 22.75 | 97.50 | 309.17 | 797.96 | 23.01 | 167.50 | 271.33 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1825.70 | 22.64 | 109.33 | 320.50 | 929.51 | 22.97 | 150.83 | 284.33 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2071.31 | 23.40 | 129.50 | 359.00 | 877.24 | 22.68 | 159.00 | 321.33 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 1995.88 | 23.32 | 126.50 | 353.33 | 866.27 | 22.77 | 164.67 | 318.33 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1880.79 | 23.06 | 123.67 | 348.33 | 828.03 | 22.45 | 167.33 | 312.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1928.76 | 22.77 | 114.17 | 341.50 | 860.57 | 22.16 | 173.50 | 307.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1926.22 | 23.59 | 107.00 | 311.50 | 986.87 | 23.89 | 183.67 | 285.50 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-06:49 | 1793.52 | 23.59 | 107.00 | 305.33 | 921.91 | 23.79 | 194.17 | 275.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1550.71 | 23.61 | 93.83 | 279.17 | 794.12 | 23.73 | 179.17 | 244.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1276.48 | 22.56 | 86.00 | 269.33 | 660.28 | 22.67 | 161.33 | 225.33 |
Annual Sum or Average | 4323.33 | 0.52 | 1770.70 | 23.20 | 1309.17 | 3735.83 | 841.75 | 23.01 | 2029.17 | 3310.50 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1276.48 | 22.56 | 86.00 | 263.33 | 660.28 | 22.16 | 150.83 | 225.33 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2071.31 | 23.78 | 129.50 | 359.00 | 986.87 | 23.89 | 194.17 | 321.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:30 | 604.68 | 16.87 | 0.00 | 260.33 | 347.02 | 18.18 | 0.00 | 179.83 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-08:50 | 687.65 | 17.71 | 0.00 | 253.33 | 393.69 | 19.02 | 0.00 | 192.67 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 801.27 | 18.34 | 0.00 | 306.17 | 452.43 | 19.60 | 1.50 | 254.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 917.28 | 18.58 | 0.00 | 327.00 | 510.74 | 19.81 | 75.83 | 286.50 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:49 | 1080.04 | 19.60 | 3.50 | 368.50 | 592.15 | 20.81 | 186.00 | 333.50 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:40 | 1193.52 | 22.45 | 96.17 | 366.00 | 641.39 | 21.25 | 236.00 | 332.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1154.75 | 20.50 | 41.00 | 358.50 | 625.87 | 21.84 | 252.83 | 327.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1047.22 | 19.26 | 0.17 | 350.17 | 581.18 | 20.57 | 187.00 | 315.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 915.14 | 18.96 | 0.00 | 317.00 | 520.50 | 20.27 | 69.67 | 275.33 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:40 | 758.30 | 18.10 | 0.00 | 300.00 | 441.46 | 19.43 | 1.50 | 247.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:00 | 656.68 | 17.78 | 0.00 | 262.33 | 383.67 | 19.16 | 0.00 | 198.67 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:39 | 586.35 | 16.99 | 0.00 | 250.00 | 336.97 | 18.33 | 0.00 | 160.17 |
Annual Sum or Average | 4323.33 | 0.52 | 886.27 | 18.88 | 140.83 | 3719.33 | 495.31 | 19.95 | 1010.33 | 3104.00 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 586.35 | 16.87 | 0.00 | 250.00 | 336.97 | 18.18 | 0.00 | 160.17 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1193.52 | 22.45 | 96.17 | 368.50 | 641.39 | 21.84 | 252.83 | 333.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1497.00 | 23.48 | 108.17 | 274.33 | 774.48 | 23.58 | 175.50 | 235.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1468.10 | 22.28 | 76.33 | 262.33 | 736.75 | 22.43 | 159.00 | 223.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:00 | 1683.72 | 22.95 | 96.67 | 309.83 | 849.71 | 23.13 | 176.00 | 273.17 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:20 | 1701.17 | 19.62 | 55.00 | 324.67 | 878.74 | 19.49 | 116.83 | 288.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:40 | 1784.67 | 17.87 | 0.00 | 350.17 | 921.79 | 19.83 | 119.50 | 315.50 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-07:30 | 1898.82 | 18.06 | 0.00 | 345.83 | 974.28 | 20.01 | 130.00 | 313.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:40 | 1818.30 | 18.03 | 3.67 | 348.17 | 822.90 | 19.77 | 130.50 | 310.33 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1856.27 | 20.11 | 59.83 | 342.67 | 953.72 | 20.16 | 142.83 | 309.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1797.39 | 22.21 | 87.17 | 318.17 | 920.63 | 22.58 | 174.33 | 287.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:00 | 1856.26 | 23.81 | 110.33 | 303.33 | 954.88 | 24.01 | 192.50 | 273.83 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-08:09 | 1614.74 | 24.02 | 99.50 | 278.33 | 828.72 | 24.12 | 180.83 | 245.33 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:39 | 1411.20 | 23.62 | 101.83 | 269.67 | 723.64 | 23.69 | 172.67 | 227.83 |
Annual Sum or Average | 4323.33 | 0.52 | 1712.02 | 21.14 | 798.50 | 3727.50 | 867.49 | 21.75 | 1870.50 | 3303.17 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1411.20 | 17.87 | 0.00 | 262.33 | 723.64 | 19.49 | 116.83 | 223.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1898.82 | 24.02 | 110.33 | 350.17 | 974.28 | 24.12 | 192.50 | 315.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4207.91 | 33.84 | 310.17 | 293.00 | 1147.14 | 21.84 | 91.50 | 280.83 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:00 | 2187.98 | 22.15 | 140.67 | 274.83 | 1028.84 | 16.93 | 0.00 | 246.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1621.56 | 13.67 | 5.00 | 315.00 | 880.29 | 16.86 | 0.00 | 280.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 1273.61 | 13.01 | 0.00 | 323.50 | 705.34 | 16.29 | 0.00 | 289.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1088.63 | 13.09 | 0.00 | 350.00 | 623.76 | 16.45 | 0.00 | 310.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:00 | 1044.00 | 12.93 | 0.00 | 344.33 | 607.73 | 16.34 | 0.00 | 304.33 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1095.74 | 12.76 | 0.00 | 345.17 | 630.14 | 16.11 | 0.00 | 308.17 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1281.34 | 13.32 | 0.00 | 343.83 | 718.02 | 16.66 | 0.00 | 308.33 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1597.22 | 13.91 | 0.00 | 318.83 | 879.22 | 17.30 | 0.00 | 289.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:10 | 2125.39 | 15.99 | 34.50 | 317.50 | 1057.25 | 18.02 | 10.50 | 291.17 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3549.26 | 30.55 | 255.33 | 298.33 | 1191.68 | 21.59 | 76.33 | 283.67 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4186.97 | 34.28 | 305.83 | 289.50 | 1220.80 | 23.26 | 113.00 | 276.50 |
Annual Sum or Average | 4323.33 | 0.51 | 2012.28 | 18.47 | 1051.50 | 3813.83 | 870.36 | 17.97 | 291.33 | 3469.83 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1044.00 | 12.76 | 0.00 | 274.83 | 607.73 | 16.11 | 0.00 | 246.67 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 4207.91 | 34.28 | 310.17 | 350.00 | 1220.80 | 23.26 | 113.00 | 310.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1568.52 | 21.25 | 111.83 | 276.17 | 840.23 | 21.89 | 80.67 | 241.00 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:40 | 1697.93 | 20.78 | 102.33 | 263.67 | 753.19 | 20.04 | 47.17 | 231.00 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1609.16 | 19.71 | 97.33 | 310.33 | 838.78 | 20.65 | 66.00 | 275.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1848.78 | 19.73 | 109.33 | 321.17 | 973.06 | 20.70 | 79.67 | 288.67 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2087.84 | 19.65 | 119.33 | 359.83 | 924.35 | 20.19 | 67.83 | 325.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 2026.25 | 20.36 | 125.83 | 354.50 | 912.39 | 20.26 | 66.67 | 321.83 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1904.55 | 19.24 | 114.17 | 348.83 | 873.59 | 19.89 | 61.83 | 315.67 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1948.28 | 19.86 | 113.67 | 342.33 | 907.08 | 19.63 | 56.00 | 311.17 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1959.49 | 20.70 | 106.83 | 311.83 | 1033.19 | 21.66 | 77.33 | 288.17 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-06:49 | 1830.29 | 20.66 | 104.67 | 306.33 | 964.93 | 21.65 | 75.83 | 278.67 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1567.55 | 19.85 | 84.33 | 279.33 | 832.76 | 21.60 | 63.00 | 249.00 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1298.71 | 19.72 | 85.17 | 270.67 | 692.34 | 20.52 | 55.67 | 231.50 |
Annual Sum or Average | 4323.33 | 0.52 | 1796.81 | 20.10 | 1274.83 | 3745.00 | 883.97 | 20.69 | 797.67 | 3358.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1298.71 | 19.24 | 84.33 | 263.67 | 692.34 | 19.63 | 47.17 | 231.00 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2087.84 | 21.25 | 125.83 | 359.83 | 1033.19 | 21.89 | 80.67 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:20 | 614.13 | 11.11 | 0.00 | 260.50 | 368.96 | 14.50 | 0.00 | 193.17 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:39 | 698.63 | 11.86 | 0.00 | 253.67 | 418.67 | 15.30 | 0.00 | 201.00 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 814.23 | 12.56 | 0.00 | 306.50 | 481.19 | 15.93 | 0.00 | 260.50 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 931.92 | 12.94 | 0.00 | 327.33 | 543.18 | 16.24 | 0.00 | 291.17 |
May | 405.33 | 0.50 | 0.48 | 01-MAY-06:40 | 1097.14 | 13.76 | 2.83 | 368.67 | 629.82 | 17.15 | 1.17 | 339.00 |
June | 403.50 | 0.50 | 0.48 | 01-JUN-06:19 | 1211.82 | 17.75 | 77.33 | 366.33 | 685.81 | 18.84 | 34.17 | 339.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1172.02 | 14.89 | 26.83 | 359.00 | 665.11 | 18.16 | 27.17 | 331.00 |
August | 395.83 | 0.51 | 0.48 | 01-AUG-06:00 | 1063.49 | 13.49 | 0.00 | 350.50 | 617.87 | 16.89 | 0.00 | 319.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 929.92 | 13.46 | 0.00 | 317.33 | 553.57 | 16.82 | 0.00 | 280.67 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 770.75 | 12.66 | 0.00 | 300.67 | 469.62 | 16.06 | 0.00 | 253.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:49 | 667.01 | 12.11 | 0.00 | 263.17 | 408.02 | 15.62 | 0.00 | 209.67 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:30 | 595.17 | 11.06 | 0.00 | 251.00 | 358.19 | 14.54 | 0.00 | 174.33 |
Annual Sum or Average | 4323.33 | 0.52 | 900.17 | 13.27 | 107.00 | 3724.67 | 527.04 | 16.45 | 62.50 | 3192.67 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 595.17 | 11.06 | 0.00 | 251.00 | 358.19 | 14.50 | 0.00 | 174.33 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1211.82 | 17.75 | 77.33 | 368.67 | 685.81 | 18.84 | 34.17 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1522.02 | 20.93 | 108.17 | 275.83 | 808.86 | 21.62 | 77.17 | 240.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1498.38 | 19.17 | 76.33 | 263.00 | 774.95 | 20.04 | 48.33 | 227.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:50 | 1723.73 | 19.87 | 96.67 | 311.17 | 893.37 | 20.74 | 65.67 | 277.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:09 | 1722.67 | 15.98 | 55.00 | 325.67 | 921.42 | 16.37 | 0.00 | 292.50 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1808.02 | 13.42 | 0.00 | 351.00 | 967.92 | 16.65 | 0.00 | 320.67 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-07:19 | 1930.46 | 13.59 | 0.00 | 346.50 | 1020.90 | 16.84 | 0.00 | 317.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1844.22 | 13.63 | 3.67 | 349.33 | 868.43 | 16.63 | 0.00 | 314.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1874.15 | 16.45 | 59.83 | 342.83 | 1000.35 | 17.08 | 5.50 | 312.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1823.98 | 19.10 | 86.83 | 318.00 | 966.96 | 20.14 | 57.33 | 289.67 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:49 | 1894.84 | 21.12 | 110.33 | 304.50 | 997.79 | 21.90 | 79.33 | 277.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-07:00 | 1642.75 | 21.30 | 98.67 | 279.00 | 867.81 | 22.05 | 69.00 | 249.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:30 | 1434.89 | 20.94 | 101.83 | 270.17 | 757.06 | 21.66 | 71.00 | 233.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1739.59 | 17.70 | 797.33 | 3737.00 | 910.00 | 19.12 | 473.33 | 3354.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1434.89 | 13.42 | 0.00 | 263.00 | 757.06 | 16.37 | 0.00 | 227.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1930.46 | 21.30 | 110.33 | 351.00 | 1020.90 | 22.05 | 79.33 | 320.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.51 | 0.48 | 01-JAN-07:00 | 4210.55 | 33.83 | 310.17 | 293.00 | 1149.14 | 21.83 | 91.50 | 280.83 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:00 | 2190.99 | 22.13 | 140.67 | 274.83 | 1030.70 | 16.91 | 0.00 | 246.67 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:20 | 1624.28 | 13.64 | 5.00 | 315.00 | 881.86 | 16.84 | 0.00 | 281.00 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 1275.69 | 12.98 | 0.00 | 323.50 | 706.54 | 16.28 | 0.00 | 289.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1090.23 | 13.06 | 0.00 | 350.17 | 624.74 | 16.43 | 0.00 | 310.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:00 | 1045.45 | 12.90 | 0.00 | 344.33 | 608.65 | 16.33 | 0.00 | 304.50 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:10 | 1097.32 | 12.73 | 0.00 | 345.33 | 631.12 | 16.09 | 0.00 | 308.50 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:10 | 1283.33 | 13.29 | 0.00 | 343.83 | 719.21 | 16.64 | 0.00 | 308.50 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:10 | 1599.80 | 13.88 | 0.00 | 318.83 | 880.74 | 17.29 | 0.00 | 289.50 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-07:10 | 2128.39 | 15.96 | 34.50 | 317.50 | 1059.10 | 18.01 | 10.50 | 291.50 |
November | 318.83 | 0.49 | 0.48 | 01-NOV-07:10 | 3552.16 | 30.54 | 255.33 | 298.33 | 1193.74 | 21.58 | 76.33 | 283.67 |
December | 319.00 | 0.50 | 0.48 | 01-DEC-07:19 | 4189.43 | 34.27 | 305.83 | 289.50 | 1222.82 | 23.25 | 113.00 | 276.50 |
Annual Sum or Average | 4323.33 | 0.51 | 2014.57 | 18.44 | 1051.50 | 3814.17 | 871.84 | 17.95 | 291.33 | 3471.00 | ||
Minimum of Months | 308.33 | 0.49 | 0.48 | 1045.45 | 12.73 | 0.00 | 274.83 | 608.65 | 16.09 | 0.00 | 246.67 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 4210.55 | 34.27 | 310.17 | 350.17 | 1222.82 | 23.25 | 113.00 | 310.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-07:00 | 1569.87 | 21.22 | 111.83 | 276.17 | 841.33 | 21.88 | 80.67 | 241.00 |
February | 308.33 | 0.51 | 0.48 | 01-FEB-07:40 | 1699.51 | 20.75 | 102.33 | 263.67 | 754.37 | 20.03 | 47.17 | 231.33 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-07:00 | 1611.04 | 19.68 | 97.33 | 310.33 | 840.02 | 20.64 | 66.00 | 275.83 |
April | 375.00 | 0.52 | 0.48 | 01-APR-06:00 | 1850.67 | 19.70 | 109.33 | 321.17 | 974.33 | 20.68 | 79.67 | 288.67 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:19 | 2089.68 | 19.62 | 119.33 | 359.83 | 925.65 | 20.18 | 67.83 | 325.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-06:10 | 2028.13 | 20.33 | 125.83 | 354.50 | 913.70 | 20.24 | 66.67 | 321.83 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:30 | 1906.50 | 19.22 | 114.17 | 348.83 | 874.91 | 19.88 | 61.83 | 316.00 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-06:30 | 1950.27 | 19.83 | 113.67 | 342.33 | 908.46 | 19.62 | 56.00 | 311.17 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-06:49 | 1961.44 | 20.68 | 106.83 | 312.00 | 1034.60 | 21.65 | 77.33 | 288.17 |
October | 351.17 | 0.51 | 0.48 | 01-OCT-06:49 | 1831.86 | 20.63 | 104.67 | 306.33 | 966.24 | 21.64 | 75.83 | 278.83 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-06:00 | 1568.95 | 19.83 | 84.33 | 279.33 | 833.93 | 21.59 | 63.00 | 249.00 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-07:19 | 1299.98 | 19.70 | 85.17 | 270.67 | 693.38 | 20.50 | 55.67 | 231.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1798.54 | 20.07 | 1274.83 | 3745.17 | 885.23 | 20.67 | 797.67 | 3359.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1299.98 | 19.22 | 84.33 | 263.67 | 693.38 | 19.62 | 47.17 | 231.33 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 2089.68 | 21.22 | 125.83 | 359.83 | 1034.60 | 21.88 | 80.67 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:20 | 614.83 | 11.08 | 0.00 | 260.50 | 369.50 | 14.48 | 0.00 | 193.33 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:39 | 699.46 | 11.83 | 0.00 | 253.67 | 419.29 | 15.28 | 0.00 | 201.33 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:39 | 815.27 | 12.53 | 0.00 | 306.67 | 481.92 | 15.92 | 0.00 | 260.67 |
April | 375.00 | 0.52 | 0.48 | 01-APR-07:40 | 933.17 | 12.91 | 0.00 | 327.33 | 544.02 | 16.23 | 0.00 | 291.50 |
May | 405.33 | 0.50 | 0.48 | 01-MAY-06:40 | 1098.62 | 13.73 | 2.83 | 368.67 | 630.80 | 17.14 | 1.17 | 339.00 |
June | 403.50 | 0.50 | 0.48 | 01-JUN-06:19 | 1213.48 | 17.72 | 77.33 | 366.33 | 686.90 | 18.82 | 34.17 | 339.17 |
July | 405.00 | 0.51 | 0.48 | 01-JUL-06:49 | 1173.65 | 14.86 | 26.83 | 359.00 | 666.18 | 18.15 | 27.17 | 331.17 |
August | 395.83 | 0.51 | 0.48 | 01-AUG-06:00 | 1064.89 | 13.46 | 0.00 | 350.50 | 618.83 | 16.87 | 0.00 | 319.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:19 | 931.04 | 13.43 | 0.00 | 317.33 | 554.39 | 16.80 | 0.00 | 280.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 771.59 | 12.63 | 0.00 | 300.67 | 470.28 | 16.05 | 0.00 | 253.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-07:49 | 667.71 | 12.08 | 0.00 | 263.17 | 408.59 | 15.61 | 0.00 | 209.83 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:30 | 595.84 | 11.03 | 0.00 | 251.00 | 358.72 | 14.52 | 0.00 | 174.83 |
Annual Sum or Average | 4323.33 | 0.52 | 901.32 | 13.24 | 107.00 | 3724.83 | 527.85 | 16.43 | 62.50 | 3194.83 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 595.84 | 11.03 | 0.00 | 251.00 | 358.72 | 14.48 | 0.00 | 174.83 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1213.48 | 17.72 | 77.33 | 368.67 | 686.90 | 18.82 | 34.17 | 339.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-09:30 | 1523.37 | 20.91 | 108.17 | 276.00 | 809.96 | 21.61 | 77.17 | 240.83 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:00 | 1499.99 | 19.14 | 76.33 | 263.00 | 776.15 | 20.03 | 48.33 | 227.83 |
March | 357.50 | 0.51 | 0.48 | 01-MAR-08:50 | 1715.05 | 18.72 | 85.83 | 310.17 | 894.66 | 20.72 | 65.67 | 278.17 |
April | 375.00 | 0.52 | 0.48 | 01-APR-08:09 | 1724.59 | 15.95 | 55.00 | 326.00 | 922.72 | 16.36 | 0.00 | 292.67 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:30 | 1809.90 | 13.39 | 0.00 | 351.00 | 969.23 | 16.64 | 0.00 | 320.83 |
June | 403.50 | 0.51 | 0.48 | 01-JUN-07:19 | 1932.40 | 13.56 | 0.00 | 346.83 | 1022.24 | 16.82 | 0.00 | 317.00 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-07:30 | 1846.21 | 13.60 | 3.67 | 349.33 | 869.78 | 16.61 | 0.00 | 314.83 |
August | 395.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1876.18 | 16.42 | 59.83 | 343.00 | 1001.77 | 17.06 | 5.50 | 312.67 |
September | 358.83 | 0.51 | 0.48 | 01-SEP-07:49 | 1826.01 | 19.07 | 86.83 | 318.17 | 968.39 | 20.13 | 57.33 | 289.83 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:49 | 1896.53 | 21.09 | 110.33 | 304.50 | 999.08 | 21.89 | 79.33 | 277.50 |
November | 318.83 | 0.51 | 0.48 | 01-NOV-07:00 | 1644.13 | 21.27 | 98.67 | 279.17 | 868.98 | 22.04 | 69.00 | 249.50 |
December | 319.00 | 0.52 | 0.48 | 01-DEC-08:30 | 1436.18 | 20.92 | 101.83 | 270.17 | 758.12 | 21.65 | 71.00 | 233.67 |
Annual Sum or Average | 4323.33 | 0.52 | 1740.49 | 17.58 | 786.50 | 3737.33 | 911.28 | 19.10 | 473.33 | 3355.33 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 1436.18 | 13.39 | 0.00 | 263.00 | 758.12 | 16.36 | 0.00 | 227.83 | |
Maximum of Months | 405.33 | 0.52 | 0.48 | 1932.40 | 21.27 | 110.33 | 351.00 | 1022.24 | 22.04 | 79.33 | 320.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 100490.93 | 153.37 | 06-JAN-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 100490.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100490.93 | 153.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 28041994.54 | 1855.49 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2383280.08 | 523.29 | 13-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226296.53 | 203.87 | 18-DEC-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30651571.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28041994.54 | 1855.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 6637932.03 | 991.57 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6637932.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6637932.03 | 991.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 145551.03 | 226.72 | 02-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145551.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 145551.03 | 226.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.700880E+11 | 0.672540E+11 | 233337.18 | 30-JAN-05:12 | 161817.75 | 0.56 |
February | 0.00 | 0.00 | 0.831882E+11 | 0.772381E+11 | 258694.75 | 09-FEB-05:12 | 165456.40 | 0.60 |
March | 0.00 | 0.00 | 0.124336E+12 | 0.116146E+12 | 211193.34 | 15-MAR-05:02 | 155822.45 | 0.70 |
April | 0.00 | 0.00 | 0.164922E+12 | 0.144904E+12 | 215113.23 | 03-APR-05:03 | 166081.61 | 0.84 |
May | 0.00 | 0.00 | 0.219062E+12 | 0.180891E+12 | 296089.95 | 30-MAY-05:03 | 182468.70 | 0.86 |
June | 0.00 | 0.00 | 0.278953E+12 | 0.200131E+12 | 308362.75 | 09-JUN-04:32 | 183742.10 | 0.89 |
July | 0.00 | 0.00 | 0.332863E+12 | 0.225645E+12 | 331537.03 | 05-JUL-03:12 | 197900.67 | 0.88 |
August | 0.00 | 0.00 | 0.380959E+12 | 0.261428E+12 | 334855.11 | 29-AUG-05:04 | 178344.21 | 0.89 |
September | 0.00 | 0.00 | 0.282229E+12 | 0.187196E+12 | 313439.20 | 10-SEP-16:21 | 152188.59 | 0.87 |
October | 0.00 | 0.00 | 0.228234E+12 | 0.170476E+12 | 294928.78 | 02-OCT-05:03 | 178169.01 | 0.85 |
November | 0.00 | 0.00 | 0.159555E+12 | 0.133940E+12 | 231116.03 | 14-NOV-05:11 | 162744.46 | 0.79 |
December | 0.00 | 0.00 | 0.110047E+12 | 0.983615E+11 | 225389.24 | 11-DEC-06:03 | 150364.15 | 0.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.243444E+13 | 0.186361E+13 | 0.79 | |||
Minimum of Months | 0.00 | 0.00 | 0.700880E+11 | 0.672540E+11 | 211193.34 | 150364.15 | 0.56 | |
Maximum of Months | 0.00 | 0.00 | 0.380959E+12 | 0.261428E+12 | 334855.11 | 197900.67 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.505474E+12 | 0.482523E+12 | 1713587.45 | 30-JAN-06:03 | 1116560.40 | 0.54 |
February | 0.00 | 0.00 | 0.611574E+12 | 0.562102E+12 | 2105738.14 | 09-FEB-06:02 | 1377815.12 | 0.57 |
March | 0.00 | 0.00 | 0.930041E+12 | 0.864009E+12 | 2045361.25 | 29-MAR-05:02 | 1366304.91 | 0.60 |
April | 0.00 | 0.00 | 0.124950E+13 | 0.109549E+13 | 2540336.06 | 30-APR-16:42 | 1365590.95 | 0.66 |
May | 0.00 | 0.00 | 0.203337E+13 | 0.166547E+13 | 2844819.16 | 24-MAY-05:02 | 1638150.29 | 0.81 |
June | 0.00 | 0.00 | 0.261870E+13 | 0.182297E+13 | 2990224.84 | 19-JUN-05:02 | 1696268.29 | 0.87 |
July | 0.00 | 0.00 | 0.311437E+13 | 0.202048E+13 | 3359189.40 | 30-JUL-16:22 | 1623309.19 | 0.87 |
August | 0.00 | 0.00 | 0.337492E+13 | 0.217118E+13 | 3267414.71 | 08-AUG-05:01 | 1699446.85 | 0.88 |
September | 0.00 | 0.00 | 0.267955E+13 | 0.173006E+13 | 3094030.07 | 28-SEP-05:02 | 1688514.22 | 0.84 |
October | 0.00 | 0.00 | 0.197861E+13 | 0.145347E+13 | 2953863.44 | 07-OCT-05:02 | 1662826.65 | 0.74 |
November | 0.00 | 0.00 | 0.124634E+13 | 0.102667E+13 | 2237592.38 | 02-NOV-04:12 | 1433390.91 | 0.63 |
December | 0.00 | 0.00 | 0.710101E+12 | 0.625701E+12 | 1864737.84 | 12-DEC-06:03 | 1313476.69 | 0.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.210526E+14 | 0.155201E+14 | 0.72 | |||
Minimum of Months | 0.00 | 0.00 | 0.505474E+12 | 0.482523E+12 | 1713587.45 | 1116560.40 | 0.54 | |
Maximum of Months | 0.00 | 0.00 | 0.337492E+13 | 0.217118E+13 | 3359189.40 | 1699446.85 | 0.88 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.457480E+11 | 0.434702E+11 | 146777.70 | 30-JAN-06:03 | 93268.25 | 0.53 |
February | 0.00 | 0.00 | 0.590262E+11 | 0.541009E+11 | 222517.01 | 06-FEB-06:02 | 148485.02 | 0.55 |
March | 0.00 | 0.00 | 0.933779E+11 | 0.867704E+11 | 211787.29 | 29-MAR-05:02 | 133323.78 | 0.59 |
April | 0.00 | 0.00 | 0.129947E+12 | 0.114432E+12 | 275287.60 | 30-APR-16:11 | 155148.16 | 0.65 |
May | 0.00 | 0.00 | 0.217345E+12 | 0.180215E+12 | 318407.39 | 24-MAY-05:02 | 183304.99 | 0.81 |
June | 0.00 | 0.00 | 0.278241E+12 | 0.198042E+12 | 334767.99 | 19-JUN-05:02 | 192200.39 | 0.87 |
July | 0.00 | 0.00 | 0.330957E+12 | 0.221050E+12 | 367699.71 | 30-JUL-16:22 | 184742.63 | 0.87 |
August | 0.00 | 0.00 | 0.356513E+12 | 0.235920E+12 | 365680.68 | 08-AUG-05:01 | 191380.75 | 0.88 |
September | 0.00 | 0.00 | 0.280951E+12 | 0.185316E+12 | 352995.15 | 10-SEP-16:31 | 169886.61 | 0.84 |
October | 0.00 | 0.00 | 0.204024E+12 | 0.151273E+12 | 326464.88 | 07-OCT-05:02 | 185119.31 | 0.74 |
November | 0.00 | 0.00 | 0.123441E+12 | 0.101627E+12 | 241472.89 | 01-NOV-04:12 | 152810.37 | 0.62 |
December | 0.00 | 0.00 | 0.667624E+11 | 0.584826E+11 | 217246.84 | 11-DEC-06:03 | 135034.55 | 0.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.218633E+13 | 0.163070E+13 | 0.71 | |||
Minimum of Months | 0.00 | 0.00 | 0.457480E+11 | 0.434702E+11 | 146777.70 | 93268.25 | 0.53 | |
Maximum of Months | 0.00 | 0.00 | 0.356513E+12 | 0.235920E+12 | 367699.71 | 192200.39 | 0.88 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.674824E+11 | 0.660146E+11 | 151273.09 | 30-JAN-05:12 | 93574.96 | 0.54 |
February | 0.00 | 0.00 | 0.646954E+11 | 0.626195E+11 | 156748.55 | 07-FEB-05:12 | 91372.05 | 0.56 |
March | 0.00 | 0.00 | 0.791900E+11 | 0.766280E+11 | 163379.68 | 31-MAR-04:12 | 87903.17 | 0.58 |
April | 0.00 | 0.00 | 0.836422E+11 | 0.786812E+11 | 189159.14 | 30-APR-15:16 | 106441.95 | 0.56 |
May | 0.00 | 0.00 | 0.109253E+12 | 0.962850E+11 | 225077.38 | 30-MAY-03:12 | 87468.40 | 0.61 |
June | 0.00 | 0.00 | 0.130355E+12 | 0.101959E+12 | 234979.25 | 04-JUN-19:48 | 89861.88 | 0.64 |
July | 0.00 | 0.00 | 0.155137E+12 | 0.110705E+12 | 239123.51 | 30-JUL-22:20 | 95196.03 | 0.63 |
August | 0.00 | 0.00 | 0.182087E+12 | 0.128184E+12 | 235559.74 | 20-AUG-21:31 | 90879.90 | 0.69 |
September | 0.00 | 0.00 | 0.142477E+12 | 0.104043E+12 | 243463.17 | 10-SEP-17:36 | 93310.81 | 0.65 |
October | 0.00 | 0.00 | 0.125024E+12 | 0.101315E+12 | 225299.15 | 08-OCT-11:48 | 99496.10 | 0.63 |
November | 0.00 | 0.00 | 0.101654E+12 | 0.888506E+11 | 173817.90 | 03-NOV-03:02 | 96012.78 | 0.62 |
December | 0.00 | 0.00 | 0.797639E+11 | 0.751964E+11 | 160253.31 | 06-DEC-05:12 | 91005.20 | 0.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.132076E+13 | 0.109048E+13 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.646954E+11 | 0.626195E+11 | 151273.09 | 87468.40 | 0.54 | |
Maximum of Months | 0.00 | 0.00 | 0.182087E+12 | 0.128184E+12 | 243463.17 | 106441.95 | 0.69 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.340790E+12 | 0.329939E+12 | 137816.14 | 30-JAN-15:00 | 126761.45 | 0.00 |
February | 0.00 | 0.00 | 0.532522E+12 | 0.519550E+12 | 232165.78 | 07-FEB-16:10 | 220373.56 | 0.00 |
March | 0.00 | 0.00 | 0.834457E+12 | 0.822385E+12 | 402701.41 | 31-MAR-23:05 | 392458.89 | 0.00 |
April | 0.00 | 0.00 | 0.104194E+13 | 0.102949E+13 | 420458.48 | 10-APR-10:05 | 405232.65 | 0.00 |
May | 0.00 | 0.00 | 0.361292E+12 | 0.343243E+12 | 225064.13 | 31-MAY-23:03 | 214219.59 | 0.00 |
June | 0.00 | 0.00 | 0.598732E+12 | 0.570961E+12 | 322939.07 | 30-JUN-23:03 | 305111.26 | 0.00 |
July | 0.00 | 0.00 | 0.872211E+12 | 0.839282E+12 | 398687.08 | 31-JUL-24:00 | 386613.47 | 0.00 |
August | 0.00 | 0.00 | 0.109003E+13 | 0.105975E+13 | 421987.70 | 04-AUG-14:00 | 398945.39 | 0.00 |
September | 0.00 | 0.00 | 0.368525E+12 | 0.337848E+12 | 235752.53 | 30-SEP-23:05 | 213304.23 | 0.00 |
October | 0.00 | 0.00 | 0.614014E+12 | 0.589758E+12 | 313806.73 | 31-OCT-23:05 | 304931.63 | 0.00 |
November | 0.00 | 0.00 | 0.820262E+12 | 0.803454E+12 | 329184.19 | 01-NOV-15:00 | 313827.46 | 0.00 |
December | 0.00 | 0.00 | 0.108318E+13 | 0.106870E+13 | 412772.29 | 05-DEC-22:00 | 402600.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.855795E+13 | 0.831436E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.340790E+12 | 0.329939E+12 | 137816.14 | 126761.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109003E+13 | 0.106870E+13 | 421987.70 | 405232.65 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.565338E+10 | 0.531242E+10 | 2673.74 | 30-JAN-14:50 | 2254.84 | 0.00 |
February | 0.00 | 0.00 | 0.100299E+11 | 0.957901E+10 | 4805.38 | 07-FEB-16:10 | 4315.21 | 0.00 |
March | 0.00 | 0.00 | 0.163147E+11 | 0.158538E+11 | 8099.66 | 31-MAR-23:05 | 7628.48 | 0.00 |
April | 0.00 | 0.00 | 0.211151E+11 | 0.205333E+11 | 8775.93 | 29-APR-20:00 | 8191.37 | 0.00 |
May | 0.00 | 0.00 | 0.719737E+10 | 0.646364E+10 | 4662.57 | 31-MAY-23:03 | 4214.53 | 0.00 |
June | 0.00 | 0.00 | 0.124750E+11 | 0.112816E+11 | 6814.72 | 30-JUN-23:03 | 6022.61 | 0.00 |
July | 0.00 | 0.00 | 0.184394E+11 | 0.169637E+11 | 8569.07 | 31-JUL-24:00 | 7885.82 | 0.00 |
August | 0.00 | 0.00 | 0.228258E+11 | 0.213064E+11 | 8881.40 | 08-AUG-03:55 | 8025.97 | 0.00 |
September | 0.00 | 0.00 | 0.766655E+10 | 0.639525E+10 | 5084.28 | 30-SEP-23:05 | 4093.31 | 0.00 |
October | 0.00 | 0.00 | 0.124231E+11 | 0.113952E+11 | 6294.41 | 31-OCT-23:05 | 5909.79 | 0.00 |
November | 0.00 | 0.00 | 0.163036E+11 | 0.155810E+11 | 6955.11 | 01-NOV-16:00 | 6309.96 | 0.00 |
December | 0.00 | 0.00 | 0.213159E+11 | 0.207626E+11 | 8679.03 | 05-DEC-17:00 | 8111.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.171760E+12 | 0.161428E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.565338E+10 | 0.531242E+10 | 2673.74 | 2254.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.228258E+11 | 0.213064E+11 | 8881.40 | 8191.37 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.472885E+11 | 0.440181E+11 | 24594.26 | 30-JAN-15:00 | 20459.21 | 0.00 |
February | 0.00 | 0.00 | 0.914628E+11 | 0.870121E+11 | 45846.23 | 07-FEB-16:10 | 40978.30 | 0.00 |
March | 0.00 | 0.00 | 0.153965E+12 | 0.149383E+12 | 77965.00 | 31-MAR-23:05 | 73198.54 | 0.00 |
April | 0.00 | 0.00 | 0.200736E+12 | 0.194925E+12 | 83326.95 | 30-APR-17:56 | 77906.42 | 0.00 |
May | 0.00 | 0.00 | 0.680178E+11 | 0.607690E+11 | 45187.70 | 31-MAY-23:03 | 40669.99 | 0.00 |
June | 0.00 | 0.00 | 0.118905E+12 | 0.107040E+12 | 65923.09 | 30-JUN-23:03 | 57929.16 | 0.00 |
July | 0.00 | 0.00 | 0.175691E+12 | 0.160981E+12 | 82083.27 | 31-JUL-24:00 | 75293.17 | 0.00 |
August | 0.00 | 0.00 | 0.216616E+12 | 0.201318E+12 | 84223.31 | 08-AUG-03:55 | 75623.36 | 0.00 |
September | 0.00 | 0.00 | 0.722623E+11 | 0.596938E+11 | 49442.95 | 30-SEP-23:05 | 39360.68 | 0.00 |
October | 0.00 | 0.00 | 0.118080E+12 | 0.107868E+12 | 60898.18 | 31-OCT-23:05 | 57000.23 | 0.00 |
November | 0.00 | 0.00 | 0.154661E+12 | 0.147469E+12 | 66792.58 | 01-NOV-16:00 | 60361.07 | 0.00 |
December | 0.00 | 0.00 | 0.199767E+12 | 0.194247E+12 | 82553.44 | 05-DEC-17:00 | 76895.61 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161745E+13 | 0.151472E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.472885E+11 | 0.440181E+11 | 24594.26 | 20459.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216616E+12 | 0.201318E+12 | 84223.31 | 77906.42 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.425951E+10 | 0.394084E+10 | 2489.88 | 30-JAN-15:00 | 2073.48 | 0.00 |
February | 0.00 | 0.00 | 0.889925E+10 | 0.845562E+10 | 4634.16 | 07-FEB-16:10 | 4146.29 | 0.00 |
March | 0.00 | 0.00 | 0.152844E+11 | 0.148262E+11 | 7752.29 | 31-MAR-23:05 | 7275.24 | 0.00 |
April | 0.00 | 0.00 | 0.201040E+11 | 0.195226E+11 | 8448.71 | 30-APR-17:56 | 7910.95 | 0.00 |
May | 0.00 | 0.00 | 0.695162E+10 | 0.622302E+10 | 4573.09 | 31-MAY-23:03 | 4121.97 | 0.00 |
June | 0.00 | 0.00 | 0.120456E+11 | 0.108566E+11 | 6612.09 | 30-JUN-23:03 | 5813.03 | 0.00 |
July | 0.00 | 0.00 | 0.178024E+11 | 0.163295E+11 | 8274.87 | 31-JUL-24:00 | 7594.68 | 0.00 |
August | 0.00 | 0.00 | 0.218559E+11 | 0.203262E+11 | 8489.02 | 20-AUG-21:04 | 7650.90 | 0.00 |
September | 0.00 | 0.00 | 0.737146E+10 | 0.610940E+10 | 4991.68 | 30-SEP-23:05 | 3994.32 | 0.00 |
October | 0.00 | 0.00 | 0.118826E+11 | 0.108603E+11 | 6086.91 | 31-OCT-23:05 | 5696.65 | 0.00 |
November | 0.00 | 0.00 | 0.154035E+11 | 0.146844E+11 | 6729.36 | 01-NOV-16:00 | 6085.66 | 0.00 |
December | 0.00 | 0.00 | 0.196953E+11 | 0.191435E+11 | 8280.96 | 05-DEC-17:00 | 7715.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161556E+12 | 0.151278E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.425951E+10 | 0.394084E+10 | 2489.88 | 2073.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218559E+11 | 0.203262E+11 | 8489.02 | 7910.95 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1.45 | 293.08 | 20-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.21 | 112.98 | 13-FEB-07:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.02 | 44.64 | 18-DEC-06:50 |
Annual Sum or Average | 0.00 | 0.14 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1.45 | 293.08 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 262088.17 | 1348111.43 | 30-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 351093.00 | 2008507.09 | 07-FEB-13:05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 483215.93 | 2117694.90 | 01-MAR-15:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 672674.84 | 2141724.09 | 24-APR-12:05 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1006989.71 | 3075117.26 | 24-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1308491.67 | 3618548.16 | 11-JUN-16:22 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1505295.71 | 4320275.58 | 20-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1631155.39 | 4157510.50 | 05-AUG-17:42 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1337366.73 | 3930638.01 | 08-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 985765.65 | 3100241.08 | 10-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 670070.32 | 2205291.03 | 01-NOV-14:05 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 376260.47 | 2147509.32 | 05-DEC-13:05 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 885650.99 | 0.00 | ||||
Minimum of Months | 262088.17 | 1348111.43 | 0.00 | 0.00 | ||
Maximum of Months | 1631155.39 | 4320275.58 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 259842.65 | 2873707.45 | 30-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 349333.91 | 4065464.36 | 09-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 480788.90 | 4013691.90 | 29-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 669274.19 | 4146966.04 | 12-APR-05:02 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1001989.64 | 4439565.48 | 02-MAY-04:12 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1303075.35 | 4800054.31 | 11-JUN-15:42 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1495625.10 | 5055748.62 | 17-JUL-03:02 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1623726.86 | 5002314.84 | 19-AUG-03:01 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1332601.94 | 4771407.45 | 05-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 981093.75 | 4613544.01 | 18-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 666887.39 | 4373885.17 | 01-NOV-04:12 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 373455.51 | 3828940.56 | 12-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 881229.34 | 0.00 | ||||
Minimum of Months | 259842.65 | 2873707.45 | 0.00 | 0.00 | ||
Maximum of Months | 1623726.86 | 5055748.62 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 359302.50 | 822021.25 | 23-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 641432.51 | 1314430.78 | 06-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 994678.76 | 1877984.29 | 27-MAR-11:05 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1417431.94 | 2290861.83 | 28-APR-12:00 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1022371.46 | 1619078.16 | 31-MAY-19:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1364677.08 | 1950936.91 | 12-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1741308.90 | 2382719.38 | 21-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1954100.20 | 2541135.04 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1104442.14 | 1583663.56 | 26-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1160258.87 | 1636887.87 | 04-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1147279.47 | 1633198.98 | 05-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1100887.05 | 1609988.94 | 10-DEC-12:00 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 1170671.70 | 0.00 | ||||
Minimum of Months | 359302.50 | 822021.25 | 0.00 | 0.00 | ||
Maximum of Months | 1954100.20 | 2541135.04 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 11546.21 | 37766.13 | 13-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11321.22 | 37357.33 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11196.08 | 35679.69 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:05 | 9653.97 | 32339.04 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 9001.76 | 29270.91 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 8483.34 | 26276.57 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 7726.02 | 24923.32 | 31-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 8633.15 | 26752.24 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8904.67 | 29628.20 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 9815.15 | 33180.85 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 10840.61 | 36039.47 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 11114.03 | 37589.90 | 28-DEC-12:10 |
Annual Sum or Average | 0.00 | 9845.14 | ||||
Minimum of Months | 0.00 | 0.00 | 7726.02 | 24923.32 | ||
Maximum of Months | 0.00 | 0.00 | 11546.21 | 37766.13 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 321121.99 | 2406771.49 | 30-JAN-14:00 | 436.16 | 78598.16 | 06-JAN-05:40 |
February | 454353.15 | 4297981.31 | 07-FEB-16:00 | 164.57 | 67824.27 | 04-FEB-05:40 |
March | 651867.53 | 4542537.62 | 29-MAR-10:05 | 648.11 | 68630.41 | 23-MAR-00:50 |
April | 1106846.15 | 4791203.18 | 28-APR-15:00 | 454.43 | 76914.78 | 26-APR-02:20 |
May | 2311062.48 | 7705246.28 | 31-MAY-16:00 | 4.03 | 7689.12 | 07-MAY-04:45 |
June | 3849823.28 | 7986495.46 | 10-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 4679097.26 | 8608102.88 | 19-JUL-15:20 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 5176486.63 | 8607009.27 | 03-AUG-14:50 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 4167620.75 | 8355557.19 | 11-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2493811.47 | 7416296.96 | 06-OCT-16:00 | 22.79 | 28768.91 | 21-OCT-02:15 |
November | 1217994.49 | 6978859.58 | 01-NOV-14:05 | 163.05 | 30338.17 | 05-NOV-04:20 |
December | 517235.29 | 4686300.17 | 05-DEC-13:05 | 411.70 | 77498.25 | 30-DEC-05:40 |
Annual Sum or Average | 2256607.10 | 192.71 | ||||
Minimum of Months | 321121.99 | 2406771.49 | 0.00 | 0.00 | ||
Maximum of Months | 5176486.63 | 8608102.88 | 648.11 | 78598.16 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154256E+11 | 0.85 | 9318.33 | 01-JAN-00:30 | 1.38 |
February | 0.136523E+11 | 0.83 | 9318.33 | 01-FEB-05:12 | 1.38 |
March | 0.152280E+11 | 0.84 | 9318.33 | 01-MAR-04:02 | 1.38 |
April | 0.142575E+11 | 0.81 | 9318.33 | 01-APR-04:12 | 1.38 |
May | 0.156994E+11 | 0.86 | 9318.33 | 01-MAY-00:05 | 1.36 |
June | 0.156010E+11 | 0.89 | 9318.33 | 01-JUN-03:03 | 1.37 |
July | 0.159103E+11 | 0.87 | 9318.33 | 01-JUL-03:02 | 1.38 |
August | 0.173357E+11 | 0.95 | 9318.33 | 01-AUG-03:02 | 1.38 |
September | 0.159195E+11 | 0.90 | 9318.33 | 01-SEP-03:02 | 1.38 |
October | 0.164308E+11 | 0.90 | 9318.33 | 01-OCT-10:40 | 1.36 |
November | 0.156439E+11 | 0.89 | 9318.33 | 01-NOV-03:02 | 1.38 |
December | 0.155481E+11 | 0.86 | 9318.33 | 01-DEC-05:12 | 1.38 |
Annual Sum or Average | 0.186652E+12 | 0.87 | |||
Minimum of Months | 0.136523E+11 | 0.81 | 9318.33 | 1.36 | |
Maximum of Months | 0.173357E+11 | 0.95 | 9318.33 | 1.38 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.580061E+10 | 0.37 | 21764.85 | 30-JAN-05:12 | 1.75 |
February | 0.654583E+10 | 0.42 | 21772.62 | 06-FEB-06:02 | 1.75 |
March | 0.957169E+10 | 0.53 | 21772.62 | 01-MAR-06:02 | 1.75 |
April | 0.115674E+11 | 0.65 | 21772.62 | 03-APR-04:02 | 1.75 |
May | 0.127042E+11 | 0.67 | 21772.62 | 01-MAY-04:21 | 1.75 |
June | 0.147405E+11 | 0.74 | 21772.62 | 03-JUN-05:02 | 1.75 |
July | 0.170785E+11 | 0.77 | 21772.62 | 01-JUL-05:03 | 1.75 |
August | 0.227479E+11 | 0.90 | 21772.62 | 01-AUG-04:22 | 1.75 |
September | 0.132725E+11 | 0.69 | 21772.62 | 01-SEP-05:02 | 1.75 |
October | 0.126431E+11 | 0.66 | 21772.62 | 03-OCT-05:02 | 1.75 |
November | 0.108381E+11 | 0.60 | 21772.62 | 01-NOV-04:12 | 1.75 |
December | 0.858457E+10 | 0.50 | 19732.38 | 12-DEC-06:03 | 1.64 |
Annual Sum or Average | 0.146095E+12 | 0.63 | |||
Minimum of Months | 0.580061E+10 | 0.37 | 19732.38 | 1.64 | |
Maximum of Months | 0.227479E+11 | 0.90 | 21772.62 | 1.75 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.393184E+11 | 0.32 | 123425.10 | 30-JAN-06:03 | 1.27 |
February | 0.433405E+11 | 0.35 | 207329.36 | 06-FEB-06:02 | 1.76 |
March | 0.645455E+11 | 0.41 | 207329.36 | 28-MAR-03:02 | 1.76 |
April | 0.758641E+11 | 0.47 | 207329.36 | 07-APR-05:02 | 1.76 |
May | 0.112067E+12 | 0.62 | 207329.36 | 02-MAY-04:12 | 1.75 |
June | 0.122460E+12 | 0.68 | 207329.36 | 06-JUN-05:03 | 1.75 |
July | 0.131595E+12 | 0.69 | 207329.36 | 01-JUL-05:03 | 1.76 |
August | 0.151391E+12 | 0.75 | 207329.36 | 01-AUG-05:02 | 1.76 |
September | 0.115435E+12 | 0.65 | 207329.36 | 01-SEP-05:02 | 1.75 |
October | 0.999772E+11 | 0.56 | 207329.36 | 03-OCT-05:02 | 1.75 |
November | 0.750965E+11 | 0.45 | 207329.36 | 01-NOV-04:12 | 1.75 |
December | 0.472027E+11 | 0.35 | 167162.88 | 12-DEC-06:03 | 1.53 |
Annual Sum or Average | 0.107829E+13 | 0.53 | |||
Minimum of Months | 0.393184E+11 | 0.32 | 123425.10 | 1.27 | |
Maximum of Months | 0.151391E+12 | 0.75 | 207329.36 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.340609E+10 | 0.31 | 8298.82 | 30-JAN-06:03 | 0.92 |
February | 0.385776E+10 | 0.33 | 21220.82 | 06-FEB-06:02 | 1.63 |
March | 0.591497E+10 | 0.38 | 23455.05 | 28-MAR-05:02 | 1.75 |
April | 0.732095E+10 | 0.45 | 23671.47 | 17-APR-05:02 | 1.75 |
May | 0.114723E+11 | 0.60 | 23671.47 | 01-MAY-04:11 | 1.75 |
June | 0.126987E+11 | 0.66 | 23671.47 | 05-JUN-05:02 | 1.75 |
July | 0.138993E+11 | 0.68 | 23671.47 | 03-JUL-05:02 | 1.75 |
August | 0.156627E+11 | 0.72 | 23671.47 | 02-AUG-05:02 | 1.75 |
September | 0.116802E+11 | 0.63 | 23671.47 | 01-SEP-05:02 | 1.74 |
October | 0.966391E+10 | 0.53 | 23671.47 | 03-OCT-05:02 | 1.75 |
November | 0.664614E+10 | 0.41 | 23671.47 | 20-NOV-06:02 | 1.75 |
December | 0.408446E+10 | 0.33 | 13367.14 | 11-DEC-06:03 | 1.22 |
Annual Sum or Average | 0.106307E+12 | 0.50 | |||
Minimum of Months | 0.340609E+10 | 0.31 | 8298.82 | 0.92 | |
Maximum of Months | 0.156627E+11 | 0.72 | 23671.47 | 1.75 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.950509E+11 | 1.35 | 35487.96 | 01-JAN-00:10 | 1.35 |
February | 0.858525E+11 | 1.35 | 35487.96 | 01-FEB-00:20 | 1.35 |
March | 0.950509E+11 | 1.35 | 35487.96 | 01-MAR-00:10 | 1.35 |
April | 0.919848E+11 | 1.35 | 35487.96 | 01-APR-00:05 | 1.35 |
May | 0.950509E+11 | 1.35 | 35487.96 | 01-MAY-00:05 | 1.35 |
June | 0.919848E+11 | 1.35 | 35487.96 | 01-JUN-00:05 | 1.35 |
July | 0.950509E+11 | 1.35 | 35487.96 | 01-JUL-00:05 | 1.35 |
August | 0.950509E+11 | 1.35 | 35487.96 | 01-AUG-00:03 | 1.35 |
September | 0.919848E+11 | 1.35 | 35487.96 | 01-SEP-00:05 | 1.35 |
October | 0.950509E+11 | 1.35 | 35487.96 | 01-OCT-00:05 | 1.35 |
November | 0.919848E+11 | 1.35 | 35487.96 | 01-NOV-00:05 | 1.35 |
December | 0.950509E+11 | 1.35 | 35487.96 | 01-DEC-00:05 | 1.35 |
Annual Sum or Average | 0.111915E+13 | 1.35 | |||
Minimum of Months | 0.858525E+11 | 1.35 | 35487.96 | 1.35 | |
Maximum of Months | 0.950509E+11 | 1.35 | 35487.96 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141607E+10 | 0.91 | 528.70 | 01-JAN-00:10 | 0.92 |
February | 0.127903E+10 | 0.91 | 528.70 | 01-FEB-00:10 | 0.91 |
March | 0.141607E+10 | 0.91 | 528.70 | 01-MAR-00:10 | 0.91 |
April | 0.137039E+10 | 0.91 | 528.70 | 01-APR-00:05 | 0.91 |
May | 0.141607E+10 | 0.91 | 528.70 | 01-MAY-00:05 | 0.91 |
June | 0.137039E+10 | 0.91 | 528.70 | 01-JUN-00:05 | 0.91 |
July | 0.141607E+10 | 0.91 | 528.70 | 01-JUL-00:05 | 0.91 |
August | 0.141607E+10 | 0.91 | 528.70 | 01-AUG-00:03 | 0.91 |
September | 0.137039E+10 | 0.91 | 528.70 | 01-SEP-00:05 | 0.91 |
October | 0.141607E+10 | 0.91 | 528.70 | 01-OCT-00:05 | 0.91 |
November | 0.137039E+10 | 0.91 | 528.70 | 01-NOV-00:05 | 0.91 |
December | 0.141607E+10 | 0.91 | 528.70 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.166730E+11 | 0.91 | |||
Minimum of Months | 0.127903E+10 | 0.91 | 528.70 | 0.91 | |
Maximum of Months | 0.141607E+10 | 0.91 | 528.70 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135143E+11 | 0.91 | 5045.66 | 01-JAN-00:10 | 0.91 |
February | 0.122065E+11 | 0.91 | 5045.66 | 01-FEB-00:10 | 0.91 |
March | 0.135143E+11 | 0.91 | 5045.66 | 01-MAR-00:10 | 0.91 |
April | 0.130783E+11 | 0.91 | 5045.66 | 01-APR-00:05 | 0.91 |
May | 0.135143E+11 | 0.91 | 5045.66 | 01-MAY-00:05 | 0.91 |
June | 0.130783E+11 | 0.91 | 5045.66 | 01-JUN-00:05 | 0.91 |
July | 0.135143E+11 | 0.91 | 5045.66 | 01-JUL-00:05 | 0.91 |
August | 0.135143E+11 | 0.91 | 5045.66 | 01-AUG-00:03 | 0.91 |
September | 0.130783E+11 | 0.91 | 5045.66 | 01-SEP-00:05 | 0.91 |
October | 0.135143E+11 | 0.91 | 5045.66 | 01-OCT-00:05 | 0.91 |
November | 0.130783E+11 | 0.91 | 5045.66 | 01-NOV-00:05 | 0.91 |
December | 0.135143E+11 | 0.91 | 5045.66 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.159120E+12 | 0.91 | |||
Minimum of Months | 0.122065E+11 | 0.91 | 5045.66 | 0.91 | |
Maximum of Months | 0.135143E+11 | 0.91 | 5045.66 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136252E+10 | 0.91 | 508.71 | 01-JAN-00:10 | 0.91 |
February | 0.123066E+10 | 0.91 | 508.71 | 01-FEB-00:10 | 0.91 |
March | 0.136252E+10 | 0.91 | 508.71 | 01-MAR-00:10 | 0.91 |
April | 0.131856E+10 | 0.91 | 508.71 | 01-APR-00:05 | 0.91 |
May | 0.136252E+10 | 0.91 | 508.71 | 01-MAY-00:05 | 0.91 |
June | 0.131856E+10 | 0.91 | 508.71 | 01-JUN-00:05 | 0.91 |
July | 0.136252E+10 | 0.91 | 508.71 | 01-JUL-00:05 | 0.91 |
August | 0.136252E+10 | 0.91 | 508.71 | 01-AUG-00:03 | 0.91 |
September | 0.131856E+10 | 0.91 | 508.71 | 01-SEP-00:05 | 0.91 |
October | 0.136252E+10 | 0.91 | 508.71 | 01-OCT-00:05 | 0.91 |
November | 0.131856E+10 | 0.91 | 508.71 | 01-NOV-00:05 | 0.91 |
December | 0.136252E+10 | 0.91 | 508.71 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.160425E+11 | 0.91 | |||
Minimum of Months | 0.123066E+10 | 0.91 | 508.71 | 0.91 | |
Maximum of Months | 0.136252E+10 | 0.91 | 508.71 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 131885.33 | 119883.77 | 11.40 | 02-JAN-06:03 | 10.36 | 10.36 | 81.88 | 0.01 |
February | 8662.51 | 7874.22 | 1.92 | 13-FEB-07:00 | 1.74 | 1.74 | 68.08 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 67.64 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 67.64 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 67.64 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 67.64 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 67.64 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 67.64 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 67.64 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 67.64 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 67.64 | 0.00 |
December | 811.75 | 737.88 | 0.73 | 18-DEC-06:50 | 0.67 | 0.67 | 67.62 | 0.00 |
Annual Sum or Average | 141359.60 | 128495.87 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.62 | 0.00 | |
Maximum of Months | 131885.33 | 119883.77 | 11.40 | 10.36 | 10.36 | 81.88 | 0.01 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.262951E+09 | 0.239022E+09 | 6993.35 | 30-JAN-06:03 | 6356.95 | 6356.95 | 8.77 | 64.51 |
February | 0.375951E+09 | 0.341739E+09 | 13721.17 | 06-FEB-06:02 | 12472.54 | 12472.54 | 9.97 | 84.37 |
March | 0.750597E+09 | 0.682293E+09 | 13721.17 | 01-MAR-06:02 | 12472.54 | 12472.54 | 9.89 | 84.37 |
April | 0.107792E+10 | 0.979829E+09 | 13721.17 | 04-APR-05:02 | 12472.54 | 12472.54 | 9.83 | 84.37 |
May | 0.173536E+10 | 0.157744E+10 | 13721.17 | 01-MAY-05:02 | 12472.54 | 12472.54 | 9.78 | 84.37 |
June | 0.228571E+10 | 0.207771E+10 | 13721.17 | 03-JUN-05:02 | 12472.54 | 12472.54 | 9.98 | 84.37 |
July | 0.306253E+10 | 0.278384E+10 | 13721.17 | 03-JUL-05:03 | 12472.54 | 12472.54 | 10.96 | 84.37 |
August | 0.363578E+10 | 0.330492E+10 | 13721.17 | 01-AUG-05:02 | 12472.54 | 12472.54 | 7.13 | 84.37 |
September | 0.240314E+10 | 0.218445E+10 | 13721.17 | 01-SEP-05:02 | 12472.54 | 12472.54 | 10.05 | 84.37 |
October | 0.166210E+10 | 0.151085E+10 | 13721.17 | 03-OCT-05:02 | 12472.54 | 12472.54 | 10.24 | 84.37 |
November | 0.102489E+10 | 0.931628E+09 | 13721.17 | 01-NOV-04:12 | 12472.54 | 12472.54 | 9.89 | 84.37 |
December | 0.431177E+09 | 0.391940E+09 | 13676.80 | 12-DEC-06:03 | 12432.21 | 12432.21 | 10.18 | 84.25 |
Annual Sum or Average | 0.187081E+11 | 0.170057E+11 | ||||||
Minimum of Months | 0.262951E+09 | 0.239022E+09 | 6993.35 | 6356.95 | 6356.95 | 7.13 | 64.51 | |
Maximum of Months | 0.363578E+10 | 0.330492E+10 | 13721.17 | 12472.54 | 12472.54 | 10.96 | 84.37 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.768782E+10 | 0.698822E+10 | 4721.96 | 01-JAN-00:35 | 4292.26 | 4292.26 | 6.90 | 42.19 |
February | 0.716226E+10 | 0.651050E+10 | 4721.96 | 01-FEB-05:12 | 4292.26 | 4292.26 | 9.00 | 42.19 |
March | 0.953811E+10 | 0.867014E+10 | 4721.96 | 01-MAR-04:02 | 4292.26 | 4292.26 | 8.65 | 42.19 |
April | 0.111353E+11 | 0.101220E+11 | 4721.96 | 01-APR-00:20 | 4292.26 | 4292.26 | 6.94 | 42.19 |
May | 0.118912E+11 | 0.108091E+11 | 4721.96 | 01-MAY-00:05 | 4292.26 | 4292.26 | 9.77 | 42.19 |
June | 0.117054E+11 | 0.106402E+11 | 4721.96 | 01-JUN-00:05 | 4292.26 | 4292.26 | 9.47 | 42.19 |
July | 0.118559E+11 | 0.107770E+11 | 4721.96 | 01-JUL-00:05 | 4292.26 | 4292.26 | 12.50 | 42.19 |
August | 0.122807E+11 | 0.111631E+11 | 4721.96 | 01-AUG-00:03 | 4292.26 | 4292.26 | 12.61 | 42.19 |
September | 0.115874E+11 | 0.105329E+11 | 4721.96 | 01-SEP-00:05 | 4292.26 | 4292.26 | 9.05 | 42.19 |
October | 0.117669E+11 | 0.106961E+11 | 4721.96 | 01-OCT-00:05 | 4292.26 | 4292.26 | 12.83 | 42.19 |
November | 0.102662E+11 | 0.933201E+10 | 4721.96 | 01-NOV-00:20 | 4292.26 | 4292.26 | 6.97 | 42.19 |
December | 0.930863E+10 | 0.846154E+10 | 4721.96 | 01-DEC-05:12 | 4292.26 | 4292.26 | 9.02 | 42.19 |
Annual Sum or Average | 0.126186E+12 | 0.114703E+12 | ||||||
Minimum of Months | 0.716226E+10 | 0.651050E+10 | 4721.96 | 4292.26 | 4292.26 | 6.90 | 42.19 | |
Maximum of Months | 0.122807E+11 | 0.111631E+11 | 4721.96 | 4292.26 | 4292.26 | 12.83 | 42.19 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 6.89 | 0.00 |
February | 0.180756E+09 | 0.164308E+09 | 4721.96 | 06-FEB-06:04 | 4292.26 | 4292.26 | 15.74 | 21.09 |
March | 0.708010E+09 | 0.643581E+09 | 4721.96 | 01-MAR-06:04 | 4292.26 | 4292.26 | 15.23 | 21.09 |
April | 0.172951E+10 | 0.157213E+10 | 4721.96 | 03-APR-07:20 | 4292.26 | 4292.26 | 15.14 | 21.09 |
May | 0.424499E+10 | 0.385870E+10 | 4721.96 | 01-MAY-05:03 | 4292.26 | 4292.26 | 15.87 | 21.09 |
June | 0.613445E+10 | 0.557621E+10 | 4721.96 | 01-JUN-07:20 | 4292.26 | 4292.26 | 14.74 | 21.09 |
July | 0.740389E+10 | 0.673013E+10 | 4721.96 | 01-JUL-03:02 | 4292.26 | 4292.26 | 13.50 | 42.19 |
August | 0.797853E+10 | 0.725248E+10 | 4721.96 | 01-AUG-01:42 | 4292.26 | 4292.26 | 11.62 | 42.19 |
September | 0.615482E+10 | 0.559473E+10 | 4721.96 | 01-SEP-05:03 | 4292.26 | 4292.26 | 16.39 | 21.09 |
October | 0.411299E+10 | 0.373871E+10 | 4721.96 | 01-OCT-13:42 | 4292.26 | 4292.26 | 12.31 | 42.19 |
November | 0.227008E+10 | 0.206350E+10 | 4721.96 | 01-NOV-04:13 | 4292.26 | 4292.26 | 15.30 | 21.09 |
December | 0.271985E+09 | 0.247234E+09 | 4721.96 | 04-DEC-09:50 | 4292.26 | 4292.26 | 14.89 | 21.09 |
Annual Sum or Average | 0.411900E+11 | 0.374417E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 | 0.00 | |
Maximum of Months | 0.797853E+10 | 0.725248E+10 | 4721.96 | 4292.26 | 4292.26 | 16.39 | 42.19 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.935373E+10 | 0.850254E+10 | 3492.28 | 01-JAN-00:10 | 3174.49 | 3174.49 | 21.90 | 14.73 |
February | 0.844853E+10 | 0.767972E+10 | 3492.28 | 01-FEB-00:10 | 3174.49 | 3174.49 | 25.89 | 14.73 |
March | 0.935373E+10 | 0.850254E+10 | 3492.28 | 01-MAR-00:10 | 3174.49 | 3174.49 | 36.18 | 14.73 |
April | 0.905200E+10 | 0.822827E+10 | 3492.28 | 01-APR-00:05 | 3174.49 | 3174.49 | 40.57 | 14.73 |
May | 0.935373E+10 | 0.850254E+10 | 3492.28 | 01-MAY-00:05 | 3174.49 | 3174.49 | 34.17 | 14.73 |
June | 0.905200E+10 | 0.822827E+10 | 3492.28 | 01-JUN-00:05 | 3174.49 | 3174.49 | 43.63 | 14.73 |
July | 0.935373E+10 | 0.850254E+10 | 3492.28 | 01-JUL-00:05 | 3174.49 | 3174.49 | 47.38 | 14.73 |
August | 0.935373E+10 | 0.850254E+10 | 3492.28 | 01-AUG-00:03 | 3174.49 | 3174.49 | 52.89 | 14.73 |
September | 0.905200E+10 | 0.822827E+10 | 3492.28 | 01-SEP-00:05 | 3174.49 | 3174.49 | 39.92 | 14.73 |
October | 0.935373E+10 | 0.850254E+10 | 3492.28 | 01-OCT-00:05 | 3174.49 | 3174.49 | 40.06 | 14.73 |
November | 0.905200E+10 | 0.822827E+10 | 3492.28 | 01-NOV-00:05 | 3174.49 | 3174.49 | 42.09 | 14.73 |
December | 0.935373E+10 | 0.850254E+10 | 3492.28 | 01-DEC-00:05 | 3174.49 | 3174.49 | 37.94 | 14.73 |
Annual Sum or Average | 0.110133E+12 | 0.100111E+12 | ||||||
Minimum of Months | 0.844853E+10 | 0.767972E+10 | 3492.28 | 3174.49 | 3174.49 | 21.90 | 14.73 | |
Maximum of Months | 0.935373E+10 | 0.850254E+10 | 3492.28 | 3174.49 | 3174.49 | 52.89 | 14.73 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:10 | 16.86 | 16.86 | 56.36 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.27 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 56.75 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.47 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 58.12 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 58.15 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.46 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 56.86 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 57.26 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:05 | 16.86 | 16.86 | 56.85 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.42 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.92 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.27 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.15 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.294456E+11 | 0.267660E+11 | 18172.26 | 30-JAN-14:00 | 16518.58 | 16518.58 | 28.89 | 73.94 |
February | 0.279204E+11 | 0.253796E+11 | 36321.53 | 07-FEB-16:00 | 33016.27 | 33016.27 | 28.05 | 147.87 |
March | 0.385447E+11 | 0.350371E+11 | 36333.60 | 29-MAR-10:05 | 33027.24 | 33027.24 | 28.45 | 147.87 |
April | 0.478696E+11 | 0.435135E+11 | 36344.52 | 28-APR-15:00 | 33037.17 | 33037.17 | 28.85 | 147.87 |
May | 0.599172E+11 | 0.544647E+11 | 36344.52 | 03-MAY-13:00 | 33037.17 | 33037.17 | 29.20 | 147.87 |
June | 0.672284E+11 | 0.611106E+11 | 36344.52 | 01-JUN-15:30 | 33037.17 | 33037.17 | 28.85 | 147.87 |
July | 0.721136E+11 | 0.655512E+11 | 36344.52 | 01-JUL-03:02 | 33037.17 | 33037.17 | 31.19 | 147.87 |
August | 0.759750E+11 | 0.690613E+11 | 36344.52 | 01-AUG-01:42 | 33037.17 | 33037.17 | 32.24 | 147.87 |
September | 0.668967E+11 | 0.608091E+11 | 36344.52 | 01-SEP-05:05 | 33037.17 | 33037.17 | 29.52 | 147.87 |
October | 0.594601E+11 | 0.540492E+11 | 36344.52 | 01-OCT-13:42 | 33037.17 | 33037.17 | 32.61 | 147.87 |
November | 0.462391E+11 | 0.420314E+11 | 36344.52 | 01-NOV-09:30 | 33037.17 | 33037.17 | 29.05 | 147.87 |
December | 0.364818E+11 | 0.331619E+11 | 36340.70 | 05-DEC-13:05 | 33033.69 | 33033.69 | 28.68 | 147.87 |
Annual Sum or Average | 0.628092E+12 | 0.570936E+12 | ||||||
Minimum of Months | 0.279204E+11 | 0.253796E+11 | 18172.26 | 16518.58 | 16518.58 | 28.05 | 73.94 | |
Maximum of Months | 0.759750E+11 | 0.690613E+11 | 36344.52 | 33037.17 | 33037.17 | 32.61 | 147.87 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 82.00 | 82.00 | 1.45 | 293.08 | 20-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 68.46 | 68.46 | 0.21 | 112.98 | 13-FEB-07:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 67.64 | 67.64 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 01-APR-00:05 | 67.64 | 67.64 | 0.00 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 67.64 | 67.64 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 67.64 | 67.64 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 67.64 | 67.64 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 67.64 | 67.64 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 67.64 | 67.64 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 67.64 | 67.64 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 67.64 | 67.64 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 67.64 | 67.64 | 0.02 | 44.64 | 18-DEC-06:50 |
Annual Sum or Average | 0.00 | 0.14 | ||||||
Minimum of Months | 0.00 | 0.00 | 67.64 | 67.64 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 82.00 | 82.00 | 1.45 | 293.08 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 262088.17 | 1348111.43 | 30-JAN-14:00 | 14.33 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 351093.00 | 2008507.09 | 07-FEB-13:05 | 12.38 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 483215.93 | 2117694.90 | 01-MAR-15:05 | 12.69 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 672674.84 | 2141724.09 | 24-APR-12:05 | 12.76 | 6.70 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1006989.71 | 3075117.26 | 24-MAY-05:02 | 15.41 | 6.91 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1308491.67 | 3618548.16 | 11-JUN-16:22 | 16.95 | 8.45 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1505295.71 | 4320275.58 | 20-JUL-05:03 | 18.94 | 10.44 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1631155.39 | 4157510.50 | 05-AUG-17:42 | 18.48 | 9.98 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1337366.73 | 3930638.01 | 08-SEP-05:03 | 17.84 | 9.34 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 985765.65 | 3100241.08 | 10-OCT-05:02 | 15.48 | 6.98 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 670070.32 | 2205291.03 | 01-NOV-14:05 | 12.94 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 376260.47 | 2147509.32 | 05-DEC-13:05 | 12.78 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 885650.99 | 0.00 | ||||||
Minimum of Months | 262088.17 | 1348111.43 | 12.38 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1631155.39 | 4320275.58 | 18.94 | 10.44 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 259842.65 | 2873707.45 | 30-JAN-06:03 | 17.35 | 10.36 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 349333.91 | 4065464.36 | 09-FEB-06:02 | 18.22 | 12.44 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 480788.90 | 4013691.90 | 29-MAR-05:02 | 18.07 | 12.37 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 669274.19 | 4146966.04 | 12-APR-05:02 | 18.45 | 12.56 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1001989.64 | 4439565.48 | 02-MAY-04:12 | 19.28 | 12.97 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1303075.35 | 4800054.31 | 11-JUN-15:42 | 20.83 | 13.47 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1495625.10 | 5055748.62 | 17-JUL-03:02 | 21.03 | 13.84 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1623726.86 | 5002314.84 | 19-AUG-03:01 | 20.88 | 13.77 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1332601.94 | 4771407.45 | 05-SEP-03:02 | 20.23 | 13.44 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 981093.75 | 4613544.01 | 18-OCT-05:02 | 19.78 | 13.22 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 666887.39 | 4373885.17 | 01-NOV-04:12 | 19.10 | 12.88 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 373455.51 | 3828940.56 | 12-DEC-06:03 | 17.57 | 12.11 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 881229.34 | 0.00 | ||||||
Minimum of Months | 259842.65 | 2873707.45 | 17.35 | 10.36 | 0.00 | 0.00 | ||
Maximum of Months | 1623726.86 | 5055748.62 | 21.03 | 13.84 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 359302.50 | 822021.25 | 23-JAN-14:00 | 34.20 | 30.05 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 641432.51 | 1314430.78 | 06-FEB-15:00 | 43.49 | 36.17 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 994678.76 | 1877984.29 | 27-MAR-11:05 | 53.92 | 43.30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1417431.94 | 2290861.83 | 28-APR-12:00 | 61.45 | 48.61 | 0.00 | 0.00 | 01-APR-00:05 |
May | 1022371.46 | 1619078.16 | 31-MAY-19:00 | 49.15 | 44.47 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1364677.08 | 1950936.91 | 12-JUN-12:00 | 55.26 | 47.15 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1741308.90 | 2382719.38 | 21-JUL-12:00 | 63.10 | 51.83 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1954100.20 | 2541135.04 | 16-AUG-12:00 | 65.95 | 52.82 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1104442.14 | 1583663.56 | 26-SEP-13:00 | 48.50 | 43.65 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1160258.87 | 1636887.87 | 04-OCT-12:00 | 49.48 | 41.86 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 1147279.47 | 1633198.98 | 05-NOV-12:00 | 49.41 | 39.18 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 1100887.05 | 1609988.94 | 10-DEC-12:00 | 48.98 | 36.38 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 1170671.70 | 0.00 | ||||||
Minimum of Months | 359302.50 | 822021.25 | 34.20 | 30.05 | 0.00 | 0.00 | ||
Maximum of Months | 1954100.20 | 2541135.04 | 65.95 | 52.82 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.60 | 57.60 | 11546.21 | 37766.13 | 13-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.82 | 56.82 | 11321.22 | 37357.33 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.12 | 57.12 | 11196.08 | 35679.69 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:05 | 56.80 | 56.80 | 9653.97 | 32339.04 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.47 | 58.47 | 9001.76 | 29270.91 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 58.47 | 58.47 | 8483.34 | 26276.57 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.68 | 57.68 | 7726.02 | 24923.32 | 31-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.04 | 57.04 | 8633.15 | 26752.24 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.46 | 57.46 | 8904.67 | 29628.20 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 57.21 | 57.21 | 9815.15 | 33180.85 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 56.96 | 56.96 | 10840.61 | 36039.47 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 57.30 | 57.30 | 11114.03 | 37589.90 | 28-DEC-12:10 |
Annual Sum or Average | 0.00 | 9845.14 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.80 | 56.80 | 7726.02 | 24923.32 | ||
Maximum of Months | 0.00 | 0.00 | 58.47 | 58.47 | 11546.21 | 37766.13 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 321121.99 | 2406771.49 | 30-JAN-14:00 | 28.89 | 23.96 | 436.16 | 78598.16 | 06-JAN-05:40 |
February | 454353.15 | 4297981.31 | 07-FEB-16:00 | 28.05 | 24.99 | 164.57 | 67824.27 | 04-FEB-05:40 |
March | 651867.53 | 4542537.62 | 29-MAR-10:05 | 28.45 | 24.57 | 648.11 | 68630.41 | 23-MAR-00:50 |
April | 1106846.15 | 4791203.18 | 28-APR-15:00 | 28.85 | 25.31 | 454.43 | 76914.78 | 26-APR-02:20 |
May | 2311062.48 | 7705246.28 | 31-MAY-16:00 | 33.57 | 28.89 | 4.03 | 7689.12 | 07-MAY-04:45 |
June | 3849823.28 | 7986495.46 | 10-JUN-05:03 | 34.02 | 28.75 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 4679097.26 | 8608102.88 | 19-JUL-15:20 | 35.03 | 29.35 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 5176486.63 | 8607009.27 | 03-AUG-14:50 | 35.02 | 29.35 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 4167620.75 | 8355557.19 | 11-SEP-05:03 | 34.62 | 29.22 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2493811.47 | 7416296.96 | 06-OCT-16:00 | 33.10 | 28.74 | 22.79 | 28768.91 | 21-OCT-02:15 |
November | 1217994.49 | 6978859.58 | 01-NOV-14:05 | 32.39 | 28.25 | 163.05 | 30338.17 | 05-NOV-04:20 |
December | 517235.29 | 4686300.17 | 05-DEC-13:05 | 28.68 | 24.93 | 411.70 | 77498.25 | 30-DEC-05:40 |
Annual Sum or Average | 2256607.10 | 192.71 | ||||||
Minimum of Months | 321121.99 | 2406771.49 | 28.05 | 23.96 | 0.00 | 0.00 | ||
Maximum of Months | 5176486.63 | 8608102.88 | 35.03 | 29.35 | 648.11 | 78598.16 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 100490.93 | 0.00 | 0.700880E+11 | 0.580061E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.831882E+11 | 0.654583E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.124336E+12 | 0.957169E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.164922E+12 | 0.115674E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.219062E+12 | 0.127042E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.278953E+12 | 0.147405E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.332863E+12 | 0.170785E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.380959E+12 | 0.227479E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.282229E+12 | 0.132725E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.228234E+12 | 0.126431E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.159555E+12 | 0.108381E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.110047E+12 | 0.858457E+10 | 0.00 | 0.00 |
Annual Sum or Average | 100490.93 | 0.00 | 0.243444E+13 | 0.146095E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.700880E+11 | 0.580061E+10 | 0.00 | 0.00 |
Maximum of Months | 100490.93 | 0.00 | 0.380959E+12 | 0.227479E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.505474E+12 | 0.393184E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.611574E+12 | 0.433405E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.930041E+12 | 0.645455E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.124950E+13 | 0.758641E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.203337E+13 | 0.112067E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.261870E+13 | 0.122460E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.311437E+13 | 0.131595E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.337492E+13 | 0.151391E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.267955E+13 | 0.115435E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.197861E+13 | 0.999772E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.124634E+13 | 0.750965E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.710101E+12 | 0.472027E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.210526E+14 | 0.107829E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.505474E+12 | 0.393184E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.337492E+13 | 0.151391E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 34825477.60 | 0.00 | 0.457480E+11 | 0.340609E+10 | 0.00 | 0.00 |
February | 2383280.08 | 0.00 | 0.590262E+11 | 0.385776E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.933779E+11 | 0.591497E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.129947E+12 | 0.732095E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.217345E+12 | 0.114723E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.278241E+12 | 0.126987E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.330957E+12 | 0.138993E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.356513E+12 | 0.156627E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.280951E+12 | 0.116802E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.204024E+12 | 0.966391E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.123441E+12 | 0.664614E+10 | 0.00 | 0.00 |
December | 226296.53 | 0.00 | 0.667624E+11 | 0.408446E+10 | 0.00 | 0.00 |
Annual Sum or Average | 37435054.21 | 0.00 | 0.218633E+13 | 0.106307E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.457480E+11 | 0.340609E+10 | 0.00 | 0.00 |
Maximum of Months | 34825477.60 | 0.00 | 0.356513E+12 | 0.156627E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.674824E+11 | 0.154256E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.646954E+11 | 0.136523E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.791900E+11 | 0.152280E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.836422E+11 | 0.142575E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.109253E+12 | 0.156994E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.130355E+12 | 0.156010E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.155137E+12 | 0.159103E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.182087E+12 | 0.173357E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.142477E+12 | 0.159195E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125024E+12 | 0.164308E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.101654E+12 | 0.156439E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.797639E+11 | 0.155481E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132076E+13 | 0.186652E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.646954E+11 | 0.136523E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.182087E+12 | 0.173357E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.428470E+12 | 0.185458E+12 | 0.00 | 1.01 |
February | 0.00 | 0.00 | 0.673273E+12 | 0.229151E+12 | 0.00 | 0.95 |
March | 0.00 | 0.00 | 0.107101E+13 | 0.333217E+12 | 0.00 | 0.60 |
April | 0.00 | 0.00 | 0.136136E+13 | 0.412051E+12 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.490538E+12 | 0.224303E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.818751E+12 | 0.312004E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.120865E+13 | 0.431488E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.148339E+13 | 0.488414E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.502704E+12 | 0.226163E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.820683E+12 | 0.301792E+12 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.106838E+13 | 0.340288E+12 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.137254E+13 | 0.387367E+12 | 0.00 | 1.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.112998E+14 | 0.387170E+13 | 0.00 | 4.00 |
Minimum of Months | 0.00 | 0.00 | 0.428470E+12 | 0.185458E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.148339E+13 | 0.488414E+12 | 0.00 | 1.10 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.710486E+10 | 0.286755E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.126547E+11 | 0.390392E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.208940E+11 | 0.599541E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.276000E+11 | 0.785530E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.970185E+10 | 0.392055E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.169182E+11 | 0.581356E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.253356E+11 | 0.831231E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.312186E+11 | 0.980879E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.103475E+11 | 0.405135E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.165005E+11 | 0.549340E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.211584E+11 | 0.622515E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.269723E+11 | 0.707252E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.226407E+12 | 0.713198E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.710486E+10 | 0.286755E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.312186E+11 | 0.980879E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.595776E+11 | 0.258034E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.115539E+12 | 0.362832E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.197273E+12 | 0.568221E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.262425E+12 | 0.747665E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.916925E+11 | 0.371890E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.161227E+12 | 0.554005E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.241356E+12 | 0.791800E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.296699E+12 | 0.935974E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.975122E+11 | 0.383283E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.156818E+12 | 0.522519E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.200747E+12 | 0.591647E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.252947E+12 | 0.666936E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.213381E+13 | 0.675480E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.595776E+11 | 0.258034E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.296699E+12 | 0.935974E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.538126E+10 | 0.248426E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112554E+11 | 0.358677E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.195973E+11 | 0.567545E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.262922E+11 | 0.750675E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.937263E+10 | 0.378353E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.163346E+11 | 0.560753E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.244562E+11 | 0.801638E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.299353E+11 | 0.944196E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.994908E+10 | 0.389618E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.157851E+11 | 0.526503E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.200046E+11 | 0.591961E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.249599E+11 | 0.662712E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.213324E+12 | 0.678106E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.538126E+10 | 0.248426E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.299353E+11 | 0.944196E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.580061E+10 | 0.700880E+11 | 100490.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.654583E+10 | 0.831882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.957169E+10 | 0.124336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115674E+11 | 0.164922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127042E+11 | 0.219062E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147405E+11 | 0.278953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170785E+11 | 0.332863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227479E+11 | 0.380959E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132725E+11 | 0.282229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126431E+11 | 0.228234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108381E+11 | 0.159555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.858457E+10 | 0.110047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146095E+12 | 0.243444E+13 | 100490.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.580061E+10 | 0.700880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227479E+11 | 0.380959E+12 | 100490.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.393184E+11 | 0.505474E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.433405E+11 | 0.611574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.645455E+11 | 0.930041E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.758641E+11 | 0.124950E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112067E+12 | 0.203337E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122460E+12 | 0.261870E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131595E+12 | 0.311437E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151391E+12 | 0.337492E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115435E+12 | 0.267955E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.999772E+11 | 0.197861E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.750965E+11 | 0.124634E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.472027E+11 | 0.710101E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107829E+13 | 0.210526E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.393184E+11 | 0.505474E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151391E+12 | 0.337492E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.340609E+10 | 0.457480E+11 | 34825477.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385776E+10 | 0.590262E+11 | 2383280.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.591497E+10 | 0.933779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.732095E+10 | 0.129947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114723E+11 | 0.217345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126987E+11 | 0.278241E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138993E+11 | 0.330957E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156627E+11 | 0.356513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116802E+11 | 0.280951E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.966391E+10 | 0.204024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.664614E+10 | 0.123441E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408446E+10 | 0.667624E+11 | 226296.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106307E+12 | 0.218633E+13 | 37435054.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.340609E+10 | 0.457480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156627E+11 | 0.356513E+12 | 34825477.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154256E+11 | 0.674824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136523E+11 | 0.646954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152280E+11 | 0.791900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142575E+11 | 0.836422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156994E+11 | 0.109253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156010E+11 | 0.130355E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159103E+11 | 0.155137E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173357E+11 | 0.182087E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159195E+11 | 0.142477E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164308E+11 | 0.125024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156439E+11 | 0.101654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155481E+11 | 0.797639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186652E+12 | 0.132076E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136523E+11 | 0.646954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173357E+11 | 0.182087E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.950509E+11 | 0.340790E+12 | 0.00 | 0.00 | 0.00 | 0.271465E+10 | 0.00 | 0.00 |
February | 0.858525E+11 | 0.532522E+12 | 0.00 | 0.00 | 0.00 | 0.253509E+10 | 0.00 | 0.00 |
March | 0.950509E+11 | 0.834457E+12 | 0.00 | 0.00 | 0.00 | 0.160071E+10 | 0.00 | 0.00 |
April | 0.919848E+11 | 0.104194E+13 | 0.00 | 0.00 | 0.00 | 0.646301E+09 | 0.00 | 0.00 |
May | 0.950509E+11 | 0.361292E+12 | 0.00 | 0.00 | 0.00 | 6624298.76 | 0.00 | 0.00 |
June | 0.919848E+11 | 0.598732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.950509E+11 | 0.872211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.950509E+11 | 0.109003E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.919848E+11 | 0.368525E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.950509E+11 | 0.614014E+12 | 0.00 | 0.00 | 0.00 | 71549756.93 | 0.00 | 0.00 |
November | 0.919848E+11 | 0.820262E+12 | 0.00 | 0.00 | 0.00 | 0.179748E+09 | 0.00 | 0.00 |
December | 0.950509E+11 | 0.108318E+13 | 0.00 | 0.00 | 0.00 | 0.293975E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.111915E+13 | 0.855795E+13 | 0.00 | 0.00 | 0.00 | 0.106944E+11 | 0.00 | 0.00 |
Minimum of Months | 0.858525E+11 | 0.340790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.950509E+11 | 0.109003E+13 | 0.00 | 0.00 | 0.00 | 0.293975E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141607E+10 | 0.565338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127903E+10 | 0.100299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141607E+10 | 0.163147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137039E+10 | 0.211151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141607E+10 | 0.719737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137039E+10 | 0.124750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141607E+10 | 0.184394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141607E+10 | 0.228258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137039E+10 | 0.766655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141607E+10 | 0.124231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137039E+10 | 0.163036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141607E+10 | 0.213159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166730E+11 | 0.171760E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127903E+10 | 0.565338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141607E+10 | 0.228258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135143E+11 | 0.472885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122065E+11 | 0.914628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135143E+11 | 0.153965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130783E+11 | 0.200736E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135143E+11 | 0.680178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130783E+11 | 0.118905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135143E+11 | 0.175691E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135143E+11 | 0.216616E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130783E+11 | 0.722623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135143E+11 | 0.118080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130783E+11 | 0.154661E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135143E+11 | 0.199767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159120E+12 | 0.161745E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122065E+11 | 0.472885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135143E+11 | 0.216616E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136252E+10 | 0.425951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123066E+10 | 0.889925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136252E+10 | 0.152844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131856E+10 | 0.201040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136252E+10 | 0.695162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131856E+10 | 0.120456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136252E+10 | 0.178024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136252E+10 | 0.218559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131856E+10 | 0.737146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136252E+10 | 0.118826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131856E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136252E+10 | 0.196953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160425E+11 | 0.161556E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123066E+10 | 0.425951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136252E+10 | 0.218559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.580061E+10 | 100490.93 | 0.700880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.654583E+10 | 0.00 | 0.831882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.957169E+10 | 0.00 | 0.124336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115674E+11 | 0.00 | 0.164922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.127042E+11 | 0.00 | 0.219062E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147405E+11 | 0.00 | 0.278953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170785E+11 | 0.00 | 0.332863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.227479E+11 | 0.00 | 0.380959E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132725E+11 | 0.00 | 0.282229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126431E+11 | 0.00 | 0.228234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.108381E+11 | 0.00 | 0.159555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.858457E+10 | 0.00 | 0.110047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146095E+12 | 100490.93 | 0.243444E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.580061E+10 | 0.00 | 0.700880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.227479E+11 | 100490.93 | 0.380959E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.393184E+11 | 0.00 | 0.505474E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.433405E+11 | 0.00 | 0.611574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.645455E+11 | 0.00 | 0.930041E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.758641E+11 | 0.00 | 0.124950E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.112067E+12 | 0.00 | 0.203337E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122460E+12 | 0.00 | 0.261870E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131595E+12 | 0.00 | 0.311437E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151391E+12 | 0.00 | 0.337492E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115435E+12 | 0.00 | 0.267955E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.999772E+11 | 0.00 | 0.197861E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.750965E+11 | 0.00 | 0.124634E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.472027E+11 | 0.00 | 0.710101E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107829E+13 | 0.00 | 0.210526E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.393184E+11 | 0.00 | 0.505474E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151391E+12 | 0.00 | 0.337492E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.340609E+10 | 34825477.60 | 0.457480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385776E+10 | 2383280.08 | 0.590262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.591497E+10 | 0.00 | 0.933779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.732095E+10 | 0.00 | 0.129947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114723E+11 | 0.00 | 0.217345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126987E+11 | 0.00 | 0.278241E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138993E+11 | 0.00 | 0.330957E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156627E+11 | 0.00 | 0.356513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116802E+11 | 0.00 | 0.280951E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.966391E+10 | 0.00 | 0.204024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.664614E+10 | 0.00 | 0.123441E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408446E+10 | 226296.53 | 0.667624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106307E+12 | 37435054.21 | 0.218633E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.340609E+10 | 0.00 | 0.457480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156627E+11 | 34825477.60 | 0.356513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154256E+11 | 0.00 | 0.674824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136523E+11 | 0.00 | 0.646954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152280E+11 | 0.00 | 0.791900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142575E+11 | 0.00 | 0.836422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156994E+11 | 0.00 | 0.109253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156010E+11 | 0.00 | 0.130355E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159103E+11 | 0.00 | 0.155137E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173357E+11 | 0.00 | 0.182087E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159195E+11 | 0.00 | 0.142477E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164308E+11 | 0.00 | 0.125024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156439E+11 | 0.00 | 0.101654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155481E+11 | 0.00 | 0.797639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186652E+12 | 0.00 | 0.132076E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136523E+11 | 0.00 | 0.646954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173357E+11 | 0.00 | 0.182087E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.950509E+11 | 0.00 | 0.428470E+12 | 0.00 | 0.876803E+11 | 0.00 | 0.00 | 0.00 | 0.272687E+10 | 0.00 | 0.00 | 0.00 |
February | 0.858525E+11 | 0.00 | 0.673273E+12 | 0.00 | 0.140752E+12 | 0.00 | 0.00 | 0.00 | 0.254650E+10 | 0.00 | 0.00 | 0.00 |
March | 0.950509E+11 | 0.00 | 0.107101E+13 | 0.00 | 0.236558E+12 | 0.00 | 0.00 | 0.00 | 0.160792E+10 | 0.00 | 0.00 | 0.00 |
April | 0.919848E+11 | 0.00 | 0.136136E+13 | 0.00 | 0.319417E+12 | 0.00 | 0.00 | 0.00 | 0.649210E+09 | 0.00 | 0.00 | 0.00 |
May | 0.950509E+11 | 0.00 | 0.490538E+12 | 0.00 | 0.129246E+12 | 0.00 | 0.00 | 0.00 | 6654117.42 | 0.00 | 0.00 | 0.00 |
June | 0.919848E+11 | 0.00 | 0.818751E+12 | 0.00 | 0.220019E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.950509E+11 | 0.00 | 0.120865E+13 | 0.00 | 0.336437E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.950509E+11 | 0.00 | 0.148339E+13 | 0.00 | 0.393363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.919848E+11 | 0.00 | 0.502704E+12 | 0.00 | 0.134179E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.950509E+11 | 0.00 | 0.820683E+12 | 0.00 | 0.206669E+12 | 0.00 | 0.00 | 0.00 | 71871831.39 | 0.00 | 0.00 | 0.00 |
November | 0.919848E+11 | 0.00 | 0.106838E+13 | 0.00 | 0.248123E+12 | 0.00 | 0.00 | 0.00 | 0.180557E+09 | 0.00 | 0.00 | 0.00 |
December | 0.950509E+11 | 0.00 | 0.137254E+13 | 0.00 | 0.289363E+12 | 0.00 | 0.00 | 0.00 | 0.295298E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111915E+13 | 0.00 | 0.112998E+14 | 0.00 | 0.274181E+13 | 0.00 | 0.00 | 0.00 | 0.107426E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.858525E+11 | 0.00 | 0.428470E+12 | 0.00 | 0.876803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.950509E+11 | 0.00 | 0.148339E+13 | 0.00 | 0.393363E+12 | 0.00 | 0.00 | 0.00 | 0.295298E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141607E+10 | 0.00 | 0.710486E+10 | 0.00 | 0.145148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127903E+10 | 0.00 | 0.126547E+11 | 0.00 | 0.262489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141607E+10 | 0.00 | 0.208940E+11 | 0.00 | 0.457934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137039E+10 | 0.00 | 0.276000E+11 | 0.00 | 0.648492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141607E+10 | 0.00 | 0.970185E+10 | 0.00 | 0.250449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137039E+10 | 0.00 | 0.169182E+11 | 0.00 | 0.444318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141607E+10 | 0.00 | 0.253356E+11 | 0.00 | 0.689624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141607E+10 | 0.00 | 0.312186E+11 | 0.00 | 0.839272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137039E+10 | 0.00 | 0.103475E+11 | 0.00 | 0.268096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141607E+10 | 0.00 | 0.165005E+11 | 0.00 | 0.407733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137039E+10 | 0.00 | 0.211584E+11 | 0.00 | 0.485476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141607E+10 | 0.00 | 0.269723E+11 | 0.00 | 0.565645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166730E+11 | 0.00 | 0.226407E+12 | 0.00 | 0.546468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127903E+10 | 0.00 | 0.710486E+10 | 0.00 | 0.145148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141607E+10 | 0.00 | 0.312186E+11 | 0.00 | 0.839272E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135143E+11 | 0.00 | 0.595776E+11 | 0.00 | 0.122891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122065E+11 | 0.00 | 0.115539E+12 | 0.00 | 0.240767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135143E+11 | 0.00 | 0.197273E+12 | 0.00 | 0.433078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130783E+11 | 0.00 | 0.262425E+12 | 0.00 | 0.616881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135143E+11 | 0.00 | 0.916925E+11 | 0.00 | 0.236747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130783E+11 | 0.00 | 0.161227E+12 | 0.00 | 0.423221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135143E+11 | 0.00 | 0.241356E+12 | 0.00 | 0.656657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135143E+11 | 0.00 | 0.296699E+12 | 0.00 | 0.800831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130783E+11 | 0.00 | 0.975122E+11 | 0.00 | 0.252499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135143E+11 | 0.00 | 0.156818E+12 | 0.00 | 0.387376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130783E+11 | 0.00 | 0.200747E+12 | 0.00 | 0.460863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135143E+11 | 0.00 | 0.252947E+12 | 0.00 | 0.531793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159120E+12 | 0.00 | 0.213381E+13 | 0.00 | 0.516361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122065E+11 | 0.00 | 0.595776E+11 | 0.00 | 0.122891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135143E+11 | 0.00 | 0.296699E+12 | 0.00 | 0.800831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136252E+10 | 0.00 | 0.538126E+10 | 0.00 | 0.112175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123066E+10 | 0.00 | 0.112554E+11 | 0.00 | 0.235611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136252E+10 | 0.00 | 0.195973E+11 | 0.00 | 0.431294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131856E+10 | 0.00 | 0.262922E+11 | 0.00 | 0.618819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136252E+10 | 0.00 | 0.937263E+10 | 0.00 | 0.242101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131856E+10 | 0.00 | 0.163346E+11 | 0.00 | 0.428897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136252E+10 | 0.00 | 0.244562E+11 | 0.00 | 0.665386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136252E+10 | 0.00 | 0.299353E+11 | 0.00 | 0.807944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131856E+10 | 0.00 | 0.994908E+10 | 0.00 | 0.257762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136252E+10 | 0.00 | 0.157851E+11 | 0.00 | 0.390251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131856E+10 | 0.00 | 0.200046E+11 | 0.00 | 0.460105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136252E+10 | 0.00 | 0.249599E+11 | 0.00 | 0.526461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160425E+11 | 0.00 | 0.213324E+12 | 0.00 | 0.517680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123066E+10 | 0.00 | 0.538126E+10 | 0.00 | 0.112175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136252E+10 | 0.00 | 0.299353E+11 | 0.00 | 0.807944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106402E+10 | 0.480652E+09 | 0.00 | 0.126509E+09 | 11949692.41 | 0.00 | 0.148889E+11 | 0.00 | 0.40 |
February | 0.104018E+10 | 0.125334E+10 | 0.00 | 0.100682E+09 | 32766153.28 | 0.00 | 0.935496E+10 | 0.00 | 0.40 |
March | 0.396136E+09 | 0.359929E+10 | 0.00 | 89496317.15 | 27056639.92 | 0.00 | 0.708707E+10 | 0.00 | 0.40 |
April | 0.240604E+09 | 0.991345E+10 | 0.00 | 47373629.21 | 0.174994E+09 | 0.00 | 0.280252E+10 | 0.00 | 0.39 |
May | 45826195.55 | 0.271838E+11 | 0.00 | 15712150.35 | 0.619559E+09 | 0.00 | 0.477551E+09 | 0.00 | 0.42 |
June | 7168237.24 | 0.468210E+11 | 0.00 | 2732379.05 | 0.919313E+09 | 0.00 | 70063220.50 | 0.00 | 0.43 |
July | 5601822.03 | 0.682799E+11 | 0.00 | 2260114.31 | 0.145137E+10 | 0.00 | 40218258.21 | 0.00 | 0.43 |
August | 553857.91 | 0.807761E+11 | 0.00 | 151979.31 | 0.128854E+10 | 0.00 | 3595230.29 | 0.00 | 0.46 |
September | 684672.70 | 0.559061E+11 | 0.00 | 1597240.05 | 0.135590E+10 | 0.00 | 12681787.12 | 0.00 | 0.44 |
October | 40464888.17 | 0.338672E+11 | 0.00 | 12086418.13 | 0.839209E+09 | 0.00 | 0.428766E+09 | 0.00 | 0.43 |
November | 0.154074E+09 | 0.141894E+11 | 0.00 | 46751084.83 | 0.135401E+09 | 0.00 | 0.165606E+10 | 0.00 | 0.42 |
December | 0.744317E+09 | 0.277134E+10 | 0.00 | 0.117428E+09 | 43040592.44 | 0.00 | 0.910236E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.373963E+10 | 0.345042E+12 | 0.00 | 0.562781E+09 | 0.689910E+10 | 0.00 | 0.459247E+11 | 0.00 | 0.42 |
Minimum of Months | 553857.91 | 0.480652E+09 | 0.00 | 151979.31 | 11949692.41 | 0.00 | 3595230.29 | 0.00 | 0.39 |
Maximum of Months | 0.106402E+10 | 0.807761E+11 | 0.00 | 0.126509E+09 | 0.145137E+10 | 0.00 | 0.148889E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.884103E+09 | 0.308917E+09 | 0.00 | 88056504.74 | 0.153629E+09 | 0.00 | 0.142052E+11 | 0.00 | 0.37 |
February | 0.724469E+09 | 0.127310E+10 | 0.00 | 73394072.66 | 0.318047E+09 | 0.00 | 0.894396E+10 | 0.00 | 0.36 |
March | 0.173417E+10 | 0.337759E+10 | 0.00 | 69750368.66 | 0.815972E+09 | 0.00 | 0.683388E+10 | 0.00 | 0.41 |
April | 0.165154E+10 | 0.827269E+10 | 0.00 | 26719263.39 | 0.521344E+10 | 0.00 | 0.196709E+10 | 0.00 | 0.46 |
May | 0.230011E+09 | 0.194423E+11 | 0.00 | 7485536.03 | 0.132296E+11 | 0.00 | 0.305840E+09 | 0.00 | 0.44 |
June | 25613817.39 | 0.332558E+11 | 0.00 | 1039596.10 | 0.237137E+11 | 0.00 | 22128716.43 | 0.00 | 0.44 |
July | 95983314.16 | 0.449520E+11 | 0.00 | 1645034.10 | 0.321305E+11 | 0.00 | 23470454.36 | 0.00 | 0.43 |
August | 0.00 | 0.534201E+11 | 0.00 | 0.00 | 0.288276E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 545143.43 | 0.375710E+11 | 0.00 | 873988.30 | 0.279099E+11 | 0.00 | 16636023.56 | 0.00 | 0.44 |
October | 0.286862E+09 | 0.229217E+11 | 0.00 | 5707958.86 | 0.170343E+11 | 0.00 | 0.286177E+09 | 0.00 | 0.44 |
November | 0.100165E+10 | 0.108045E+11 | 0.00 | 24075531.44 | 0.279720E+10 | 0.00 | 0.111739E+10 | 0.00 | 0.43 |
December | 0.166965E+10 | 0.230148E+10 | 0.00 | 80362959.72 | 0.102867E+10 | 0.00 | 0.831442E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.830459E+10 | 0.237901E+12 | 0.00 | 0.379111E+09 | 0.153173E+12 | 0.00 | 0.420362E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.308917E+09 | 0.00 | 0.00 | 0.153629E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.173417E+10 | 0.534201E+11 | 0.00 | 88056504.74 | 0.321305E+11 | 0.00 | 0.142052E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.799056E+10 | 0.287974E+10 | 0.00 | 0.612430E+09 | 0.180119E+10 | 0.00 | 0.127432E+12 | 0.00 | 0.35 |
February | 0.655017E+10 | 0.122462E+11 | 0.00 | 0.518563E+09 | 0.256775E+10 | 0.00 | 0.788799E+11 | 0.00 | 0.34 |
March | 0.714430E+10 | 0.327763E+11 | 0.00 | 0.524086E+09 | 0.327263E+10 | 0.00 | 0.643231E+11 | 0.00 | 0.35 |
April | 0.593702E+10 | 0.789706E+11 | 0.00 | 0.237717E+09 | 0.316268E+11 | 0.00 | 0.212993E+11 | 0.00 | 0.36 |
May | 0.212839E+10 | 0.187350E+12 | 0.00 | 56383249.41 | 0.116666E+12 | 0.00 | 0.281351E+10 | 0.00 | 0.41 |
June | 0.284687E+09 | 0.312187E+12 | 0.00 | 7241572.74 | 0.231002E+12 | 0.00 | 0.223442E+09 | 0.00 | 0.43 |
July | 0.914157E+09 | 0.409760E+12 | 0.00 | 5797776.43 | 0.332188E+12 | 0.00 | 0.104692E+09 | 0.00 | 0.42 |
August | 0.00 | 0.476876E+12 | 0.00 | 0.00 | 0.314365E+12 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 2809627.20 | 0.355078E+12 | 0.00 | 6636843.15 | 0.251366E+12 | 0.00 | 0.164914E+09 | 0.00 | 0.41 |
October | 0.167895E+10 | 0.215884E+12 | 0.00 | 52826374.24 | 0.128240E+12 | 0.00 | 0.320996E+10 | 0.00 | 0.38 |
November | 0.153061E+10 | 0.103617E+12 | 0.00 | 0.208602E+09 | 0.131291E+11 | 0.00 | 0.115546E+11 | 0.00 | 0.34 |
December | 0.622925E+10 | 0.219907E+11 | 0.00 | 0.533924E+09 | 0.534961E+10 | 0.00 | 0.746092E+11 | 0.00 | 0.35 |
Annual Sum or Average | 0.403909E+11 | 0.220962E+13 | 0.00 | 0.276421E+10 | 0.143157E+13 | 0.00 | 0.384615E+12 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.287974E+10 | 0.00 | 0.00 | 0.180119E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.799056E+10 | 0.476876E+12 | 0.00 | 0.612430E+09 | 0.332188E+12 | 0.00 | 0.127432E+12 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.357375E+10 | 0.191725E+09 | 0.00 | 42499999.13 | 0.188368E+09 | 0.00 | 0.836807E+10 | 0.00 | 0.33 |
February | 0.197964E+10 | 0.110843E+10 | 0.00 | 39913180.20 | 0.246858E+09 | 0.00 | 0.559608E+10 | 0.00 | 0.32 |
March | 0.935083E+09 | 0.296948E+10 | 0.00 | 43898707.13 | 0.258952E+09 | 0.00 | 0.544796E+10 | 0.00 | 0.34 |
April | 0.544436E+09 | 0.744557E+10 | 0.00 | 21991444.50 | 0.283589E+10 | 0.00 | 0.183424E+10 | 0.00 | 0.35 |
May | 0.198374E+09 | 0.183156E+11 | 0.00 | 5698894.66 | 0.108156E+11 | 0.00 | 0.250263E+09 | 0.00 | 0.41 |
June | 27796497.44 | 0.309793E+11 | 0.00 | 776643.67 | 0.221211E+11 | 0.00 | 20239229.10 | 0.00 | 0.43 |
July | 91100926.04 | 0.414381E+11 | 0.00 | 974419.68 | 0.310521E+11 | 0.00 | 11648084.12 | 0.00 | 0.43 |
August | 0.00 | 0.480808E+11 | 0.00 | 0.00 | 0.295837E+11 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.354289E+11 | 0.00 | 567242.90 | 0.242673E+11 | 0.00 | 9971003.16 | 0.00 | 0.42 |
October | 0.170258E+09 | 0.211810E+11 | 0.00 | 5122161.84 | 0.123114E+11 | 0.00 | 0.287625E+09 | 0.00 | 0.38 |
November | 0.147174E+09 | 0.998126E+10 | 0.00 | 16422766.93 | 0.112815E+10 | 0.00 | 0.925006E+09 | 0.00 | 0.33 |
December | 0.167381E+10 | 0.195789E+10 | 0.00 | 39358788.43 | 0.557187E+09 | 0.00 | 0.533060E+10 | 0.00 | 0.33 |
Annual Sum or Average | 0.934143E+10 | 0.219078E+12 | 0.00 | 0.217224E+09 | 0.135367E+12 | 0.00 | 0.280817E+11 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.191725E+09 | 0.00 | 0.00 | 0.188368E+09 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.357375E+10 | 0.480808E+11 | 0.00 | 43898707.13 | 0.310521E+11 | 0.00 | 0.836807E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.504862E+09 | 43245027.96 | 0.00 | 6479306.90 | 19317486.36 | 0.00 | 0.909306E+09 | 0.00 | 0.29 |
February | 0.306853E+09 | 0.195132E+09 | 0.00 | 6599488.32 | 39594894.08 | 0.00 | 0.646399E+09 | 0.00 | 0.33 |
March | 0.293910E+09 | 0.612040E+09 | 0.00 | 7413424.22 | 93911720.13 | 0.00 | 0.647359E+09 | 0.00 | 0.45 |
April | 0.216219E+09 | 0.182180E+10 | 0.00 | 3479348.79 | 0.540001E+09 | 0.00 | 0.227402E+09 | 0.00 | 0.58 |
May | 25183648.53 | 0.570530E+10 | 0.00 | 1631581.64 | 0.112612E+10 | 0.00 | 60754179.32 | 0.00 | 0.70 |
June | 3044185.97 | 0.107852E+11 | 0.00 | 277961.80 | 0.165912E+10 | 0.00 | 4981408.88 | 0.00 | 0.76 |
July | 6824012.17 | 0.158369E+11 | 0.00 | 413610.96 | 0.144553E+10 | 0.00 | 11109607.85 | 0.00 | 0.77 |
August | 0.00 | 0.172138E+11 | 0.00 | 0.00 | 0.915779E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 23461.21 | 0.106132E+11 | 0.00 | 144091.63 | 0.249685E+10 | 0.00 | 2780739.77 | 0.00 | 0.69 |
October | 34536339.26 | 0.505469E+10 | 0.00 | 903960.09 | 0.178391E+10 | 0.00 | 42941009.92 | 0.00 | 0.60 |
November | 0.138353E+09 | 0.181580E+10 | 0.00 | 2454863.47 | 0.343341E+09 | 0.00 | 0.106900E+09 | 0.00 | 0.49 |
December | 0.340725E+09 | 0.323428E+09 | 0.00 | 7118919.24 | 0.129603E+09 | 0.00 | 0.643231E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.187053E+10 | 0.700205E+11 | 0.00 | 36916557.05 | 0.105931E+11 | 0.00 | 0.330316E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 43245027.96 | 0.00 | 0.00 | 19317486.36 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.504862E+09 | 0.172138E+11 | 0.00 | 7413424.22 | 0.249685E+10 | 0.00 | 0.909306E+09 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.268510E+09 | 33204983.07 | 0.00 | 5694914.03 | 11514533.15 | 0.00 | 0.816780E+09 | 0.00 | 0.35 |
February | 0.178912E+09 | 0.139349E+09 | 0.00 | 5326802.65 | 20038174.98 | 0.00 | 0.540241E+09 | 0.00 | 0.38 |
March | 0.196774E+09 | 0.447049E+09 | 0.00 | 5433048.22 | 58392705.79 | 0.00 | 0.455307E+09 | 0.00 | 0.49 |
April | 0.148193E+09 | 0.136018E+10 | 0.00 | 2603907.63 | 0.308484E+09 | 0.00 | 0.159345E+09 | 0.00 | 0.64 |
May | 13247651.21 | 0.445393E+10 | 0.00 | 1446811.49 | 0.649421E+09 | 0.00 | 52842330.26 | 0.00 | 0.83 |
June | 1959191.39 | 0.781354E+10 | 0.00 | 196236.17 | 0.106668E+10 | 0.00 | 3463419.60 | 0.00 | 0.85 |
July | 5618090.62 | 0.109653E+11 | 0.00 | 236408.67 | 0.106447E+10 | 0.00 | 5652665.12 | 0.00 | 0.84 |
August | 0.00 | 0.112377E+11 | 0.00 | 0.00 | 0.911850E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.834418E+10 | 0.00 | 112183.68 | 0.144947E+10 | 0.00 | 2164669.25 | 0.00 | 0.81 |
October | 14969074.51 | 0.403402E+10 | 0.00 | 1037548.18 | 0.104043E+10 | 0.00 | 48361565.10 | 0.00 | 0.68 |
November | 85974421.59 | 0.132074E+10 | 0.00 | 1857975.25 | 0.211164E+09 | 0.00 | 84474394.12 | 0.00 | 0.53 |
December | 0.241958E+09 | 0.209890E+09 | 0.00 | 4767270.24 | 83193725.24 | 0.00 | 0.424025E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.115612E+10 | 0.503591E+11 | 0.00 | 28713106.22 | 0.687510E+10 | 0.00 | 0.259266E+10 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 33204983.07 | 0.00 | 0.00 | 11514533.15 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.268510E+09 | 0.112377E+11 | 0.00 | 5694914.03 | 0.144947E+10 | 0.00 | 0.816780E+09 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.366531E+09 | 94911833.83 | 0.00 | 14155020.42 | 8602386.01 | 0.00 | 0.182813E+10 | 0.00 | 0.50 |
February | 0.260015E+09 | 0.342196E+09 | 0.00 | 11973541.57 | 14334982.06 | 0.00 | 0.110948E+10 | 0.00 | 0.51 |
March | 0.271081E+09 | 0.852469E+09 | 0.00 | 10558661.12 | 78738593.69 | 0.00 | 0.868543E+09 | 0.00 | 0.57 |
April | 0.213726E+09 | 0.220968E+10 | 0.00 | 3876302.51 | 0.454743E+09 | 0.00 | 0.243798E+09 | 0.00 | 0.64 |
May | 25000869.79 | 0.572045E+10 | 0.00 | 1605931.46 | 0.112479E+10 | 0.00 | 58979548.17 | 0.00 | 0.70 |
June | 3038408.39 | 0.100580E+11 | 0.00 | 257534.35 | 0.182574E+10 | 0.00 | 4568283.78 | 0.00 | 0.73 |
July | 8541599.38 | 0.154400E+11 | 0.00 | 379504.24 | 0.157532E+10 | 0.00 | 8960947.53 | 0.00 | 0.76 |
August | 0.00 | 0.180921E+11 | 0.00 | 0.00 | 0.847949E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.137807E+11 | 0.00 | 161164.84 | 0.186349E+10 | 0.00 | 3065250.74 | 0.00 | 0.82 |
October | 21676265.71 | 0.797385E+10 | 0.00 | 2200113.00 | 0.121478E+10 | 0.00 | 84987822.60 | 0.00 | 0.81 |
November | 0.121633E+09 | 0.302196E+10 | 0.00 | 4901148.73 | 0.244477E+09 | 0.00 | 0.186419E+09 | 0.00 | 0.71 |
December | 0.272407E+09 | 0.653354E+09 | 0.00 | 13659372.01 | 79399416.51 | 0.00 | 0.113303E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.156365E+10 | 0.782396E+11 | 0.00 | 63728294.25 | 0.933235E+10 | 0.00 | 0.552997E+10 | 0.00 | 0.68 |
Minimum of Months | 0.00 | 94911833.83 | 0.00 | 0.00 | 8602386.01 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.366531E+09 | 0.180921E+11 | 0.00 | 14155020.42 | 0.186349E+10 | 0.00 | 0.182813E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111700E+09 | 58121577.31 | 0.00 | 8895069.26 | 7053987.91 | 0.00 | 0.133320E+10 | 0.00 | 0.49 |
February | 55922750.25 | 0.261105E+09 | 0.00 | 9768807.52 | 8279781.18 | 0.00 | 0.108857E+10 | 0.00 | 0.62 |
March | 72167589.41 | 0.823803E+09 | 0.00 | 12426042.49 | 18033014.76 | 0.00 | 0.115215E+10 | 0.00 | 0.85 |
April | 37099247.95 | 0.297474E+10 | 0.00 | 7074597.35 | 29933946.93 | 0.00 | 0.520934E+09 | 0.00 | 1.11 |
May | 7081661.34 | 0.633947E+10 | 0.00 | 1985151.40 | 0.213229E+09 | 0.00 | 70710652.15 | 0.00 | 1.03 |
June | 11683.24 | 0.123150E+11 | 0.00 | 315275.26 | 0.225289E+09 | 0.00 | 7671472.72 | 0.00 | 1.18 |
July | 1051898.77 | 0.180213E+11 | 0.00 | 561967.69 | 0.142181E+09 | 0.00 | 19468298.47 | 0.00 | 1.26 |
August | 0.00 | 0.229493E+11 | 0.00 | 0.00 | 64377041.41 | 0.00 | 0.00 | 0.00 | 1.48 |
September | 0.00 | 0.123918E+11 | 0.00 | 143370.83 | 0.313703E+09 | 0.00 | 2693402.37 | 0.00 | 1.03 |
October | 10526278.75 | 0.691192E+10 | 0.00 | 1447858.74 | 0.212492E+09 | 0.00 | 68199607.98 | 0.00 | 0.96 |
November | 44299948.84 | 0.240454E+10 | 0.00 | 4943879.30 | 60863780.05 | 0.00 | 0.221732E+09 | 0.00 | 0.85 |
December | 82834158.69 | 0.569113E+09 | 0.00 | 13517822.09 | 17459013.15 | 0.00 | 0.131973E+10 | 0.00 | 0.79 |
Annual Sum or Average | 0.422695E+09 | 0.860201E+11 | 0.00 | 61079841.93 | 0.131289E+10 | 0.00 | 0.580506E+10 | 0.00 | 0.97 |
Minimum of Months | 0.00 | 58121577.31 | 0.00 | 0.00 | 7053987.91 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.111700E+09 | 0.229493E+11 | 0.00 | 13517822.09 | 0.313703E+09 | 0.00 | 0.133320E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.942156E+10 | 0.381382E+09 | 0.00 | 29002484.98 | 0.208169E+09 | 0.00 | 0.423559E+10 | 0.00 | 0.29 |
February | 0.510600E+10 | 0.184267E+10 | 0.00 | 35570277.42 | 0.401702E+09 | 0.00 | 0.394870E+10 | 0.00 | 0.31 |
March | 0.329722E+10 | 0.627443E+10 | 0.00 | 48500121.26 | 0.354756E+09 | 0.00 | 0.462248E+10 | 0.00 | 0.39 |
April | 0.112309E+10 | 0.191218E+11 | 0.00 | 27895644.26 | 0.323852E+10 | 0.00 | 0.218157E+10 | 0.00 | 0.50 |
May | 0.198558E+09 | 0.636150E+11 | 0.00 | 16177000.32 | 0.835386E+10 | 0.00 | 0.694813E+09 | 0.00 | 0.74 |
June | 29537286.70 | 0.120842E+12 | 0.00 | 2643748.19 | 0.144499E+11 | 0.00 | 67490609.47 | 0.00 | 0.84 |
July | 85795204.64 | 0.175347E+12 | 0.00 | 3163245.27 | 0.157986E+11 | 0.00 | 77234807.62 | 0.00 | 0.87 |
August | 0.00 | 0.184758E+12 | 0.00 | 0.00 | 0.179943E+11 | 0.00 | 0.00 | 0.00 | 0.86 |
September | 157515.81 | 0.118924E+12 | 0.00 | 1349421.38 | 0.198587E+11 | 0.00 | 31594343.01 | 0.00 | 0.74 |
October | 0.211686E+09 | 0.538929E+11 | 0.00 | 8345985.25 | 0.123442E+11 | 0.00 | 0.465507E+09 | 0.00 | 0.57 |
November | 0.546216E+09 | 0.182087E+11 | 0.00 | 17257662.19 | 0.166060E+10 | 0.00 | 0.858646E+09 | 0.00 | 0.40 |
December | 0.505479E+10 | 0.291875E+10 | 0.00 | 34118726.96 | 0.696081E+09 | 0.00 | 0.341571E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.250746E+11 | 0.766127E+12 | 0.00 | 0.224024E+09 | 0.953594E+11 | 0.00 | 0.205993E+11 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.381382E+09 | 0.00 | 0.00 | 0.208169E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.942156E+10 | 0.184758E+12 | 0.00 | 48500121.26 | 0.198587E+11 | 0.00 | 0.462248E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401816E+10 | 0.295370E+09 | 0.00 | 35804827.57 | 0.122849E+09 | 0.00 | 0.595587E+10 | 0.00 | 0.34 |
February | 0.232540E+10 | 0.150246E+10 | 0.00 | 38748166.70 | 0.141326E+09 | 0.00 | 0.478630E+10 | 0.00 | 0.38 |
March | 0.160565E+10 | 0.509203E+10 | 0.00 | 46407456.36 | 0.173387E+09 | 0.00 | 0.459972E+10 | 0.00 | 0.49 |
April | 0.572460E+09 | 0.170104E+11 | 0.00 | 30344830.75 | 0.129763E+10 | 0.00 | 0.227782E+10 | 0.00 | 0.66 |
May | 73090869.32 | 0.517419E+11 | 0.00 | 16127102.82 | 0.385317E+10 | 0.00 | 0.681224E+09 | 0.00 | 0.91 |
June | 18790150.52 | 0.937966E+11 | 0.00 | 2123985.62 | 0.748560E+10 | 0.00 | 52288905.04 | 0.00 | 0.98 |
July | 44479741.64 | 0.135558E+12 | 0.00 | 2241938.27 | 0.627270E+10 | 0.00 | 64900722.55 | 0.00 | 1.01 |
August | 0.00 | 0.146569E+12 | 0.00 | 0.00 | 0.736834E+10 | 0.00 | 0.00 | 0.00 | 1.02 |
September | 101492.58 | 0.994814E+11 | 0.00 | 1113031.12 | 0.857100E+10 | 0.00 | 26404019.34 | 0.00 | 0.91 |
October | 41106558.74 | 0.477705E+11 | 0.00 | 12415741.32 | 0.541740E+10 | 0.00 | 0.638320E+09 | 0.00 | 0.72 |
November | 0.212500E+09 | 0.148301E+11 | 0.00 | 18336823.69 | 0.799676E+09 | 0.00 | 0.976161E+09 | 0.00 | 0.50 |
December | 0.223459E+10 | 0.226938E+10 | 0.00 | 33691114.95 | 0.429768E+09 | 0.00 | 0.391968E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.111463E+11 | 0.615917E+12 | 0.00 | 0.237355E+09 | 0.419328E+11 | 0.00 | 0.239787E+11 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.295370E+09 | 0.00 | 0.00 | 0.122849E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.401816E+10 | 0.146569E+12 | 0.00 | 46407456.36 | 0.857100E+10 | 0.00 | 0.595587E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.459662E+10 | 0.111832E+10 | 0.00 | 0.121025E+09 | 54603914.19 | 0.00 | 0.186384E+11 | 0.00 | 0.56 |
February | 0.323280E+10 | 0.387415E+10 | 0.00 | 0.101239E+09 | 80874708.84 | 0.00 | 0.113351E+11 | 0.00 | 0.56 |
March | 0.229128E+10 | 0.947992E+10 | 0.00 | 87277611.64 | 0.184247E+09 | 0.00 | 0.842413E+10 | 0.00 | 0.57 |
April | 0.952861E+09 | 0.242753E+11 | 0.00 | 34465749.86 | 0.237395E+10 | 0.00 | 0.265321E+10 | 0.00 | 0.59 |
May | 0.198298E+09 | 0.634679E+11 | 0.00 | 16083134.74 | 0.844747E+10 | 0.00 | 0.678141E+09 | 0.00 | 0.74 |
June | 29706973.09 | 0.112172E+12 | 0.00 | 2457687.61 | 0.164794E+11 | 0.00 | 62738995.81 | 0.00 | 0.80 |
July | 88388733.10 | 0.171563E+12 | 0.00 | 2960986.84 | 0.167502E+11 | 0.00 | 73347611.35 | 0.00 | 0.85 |
August | 0.00 | 0.200468E+12 | 0.00 | 0.00 | 0.153577E+11 | 0.00 | 0.00 | 0.00 | 0.91 |
September | 157418.34 | 0.157705E+12 | 0.00 | 1555144.75 | 0.124700E+11 | 0.00 | 36210668.21 | 0.00 | 0.91 |
October | 58796136.15 | 0.907171E+11 | 0.00 | 24070530.24 | 0.602795E+10 | 0.00 | 0.101113E+10 | 0.00 | 0.85 |
November | 0.270829E+09 | 0.340000E+11 | 0.00 | 44605752.42 | 0.521469E+09 | 0.00 | 0.196753E+10 | 0.00 | 0.71 |
December | 0.260774E+10 | 0.752219E+10 | 0.00 | 0.109956E+09 | 0.229131E+09 | 0.00 | 0.115818E+11 | 0.00 | 0.60 |
Annual Sum or Average | 0.143275E+11 | 0.876363E+12 | 0.00 | 0.545696E+09 | 0.789770E+11 | 0.00 | 0.564618E+11 | 0.00 | 0.72 |
Minimum of Months | 0.00 | 0.111832E+10 | 0.00 | 0.00 | 54603914.19 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.459662E+10 | 0.200468E+12 | 0.00 | 0.121025E+09 | 0.167502E+11 | 0.00 | 0.186384E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.401715E+10 | 0.431693E+09 | 0.00 | 41378166.80 | 0.103472E+09 | 0.00 | 0.660886E+10 | 0.00 | 0.38 |
February | 0.234017E+10 | 0.198720E+10 | 0.00 | 45395416.33 | 0.140343E+09 | 0.00 | 0.525193E+10 | 0.00 | 0.44 |
March | 0.121972E+10 | 0.648296E+10 | 0.00 | 55888786.17 | 67127776.61 | 0.00 | 0.580484E+10 | 0.00 | 0.58 |
April | 0.367308E+09 | 0.209176E+11 | 0.00 | 29551675.78 | 0.789755E+09 | 0.00 | 0.237392E+10 | 0.00 | 0.73 |
May | 66393442.86 | 0.599845E+11 | 0.00 | 15606931.48 | 0.239436E+10 | 0.00 | 0.632697E+09 | 0.00 | 0.97 |
June | 1129190.20 | 0.110129E+12 | 0.00 | 2173256.97 | 0.334155E+10 | 0.00 | 70199790.83 | 0.00 | 1.08 |
July | 13393661.34 | 0.154717E+12 | 0.00 | 3085176.21 | 0.273723E+10 | 0.00 | 0.107780E+09 | 0.00 | 1.10 |
August | 0.00 | 0.171956E+12 | 0.00 | 0.00 | 0.358053E+10 | 0.00 | 0.00 | 0.00 | 1.14 |
September | 0.00 | 0.116178E+12 | 0.00 | 1062755.40 | 0.493782E+10 | 0.00 | 26069979.87 | 0.00 | 0.98 |
October | 0.101516E+09 | 0.548016E+11 | 0.00 | 8920013.30 | 0.395862E+10 | 0.00 | 0.451275E+09 | 0.00 | 0.78 |
November | 0.225330E+09 | 0.177113E+11 | 0.00 | 20104099.87 | 0.547189E+09 | 0.00 | 0.969069E+09 | 0.00 | 0.57 |
December | 0.205264E+10 | 0.328038E+10 | 0.00 | 42253491.90 | 0.371194E+09 | 0.00 | 0.478371E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.104047E+11 | 0.718577E+12 | 0.00 | 0.265420E+09 | 0.229692E+11 | 0.00 | 0.270803E+11 | 0.00 | 0.77 |
Minimum of Months | 0.00 | 0.431693E+09 | 0.00 | 0.00 | 67127776.61 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.401715E+10 | 0.171956E+12 | 0.00 | 55888786.17 | 0.493782E+10 | 0.00 | 0.660886E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.924512E+09 | 23463822.63 | 0.00 | 2401641.76 | 23591108.02 | 9310794.89 | 0.363244E+09 | 0.00 | 0.29 |
February | 0.485153E+09 | 0.160784E+09 | 0.00 | 3241349.38 | 40788263.09 | 0.00 | 0.370251E+09 | 0.00 | 0.31 |
March | 0.318265E+09 | 0.546728E+09 | 0.00 | 4593840.19 | 30064405.83 | 0.00 | 0.441246E+09 | 0.00 | 0.38 |
April | 0.135190E+09 | 0.174821E+10 | 0.00 | 2858404.01 | 0.256588E+09 | 0.00 | 0.176106E+09 | 0.00 | 0.49 |
May | 18600248.47 | 0.601980E+10 | 0.00 | 1624541.46 | 0.695157E+09 | 0.00 | 60975567.31 | 0.00 | 0.72 |
June | 2943272.94 | 0.115427E+11 | 0.00 | 277399.68 | 0.123567E+10 | 0.00 | 6150234.70 | 0.00 | 0.82 |
July | 7685732.93 | 0.169139E+11 | 0.00 | 356577.67 | 0.121046E+10 | 0.00 | 8195141.90 | 0.00 | 0.85 |
August | 0.00 | 0.177895E+11 | 0.00 | 0.00 | 0.144344E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
September | 12673.46 | 0.116033E+11 | 0.00 | 111799.43 | 0.172649E+10 | 0.00 | 1925544.40 | 0.00 | 0.73 |
October | 19972083.87 | 0.525114E+10 | 0.00 | 933226.42 | 0.110155E+10 | 0.00 | 44609653.47 | 0.00 | 0.56 |
November | 58375695.73 | 0.172967E+10 | 0.00 | 1645213.98 | 0.135740E+09 | 0.00 | 72805542.65 | 0.00 | 0.39 |
December | 0.461647E+09 | 0.255564E+09 | 0.00 | 2960126.51 | 71668028.57 | 0.00 | 0.317741E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.243236E+10 | 0.735848E+11 | 0.00 | 21004120.48 | 0.797121E+10 | 9310794.89 | 0.186325E+10 | 0.00 | 0.56 |
Minimum of Months | 0.00 | 23463822.63 | 0.00 | 0.00 | 23591108.02 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.924512E+09 | 0.177895E+11 | 0.00 | 4593840.19 | 0.172649E+10 | 9310794.89 | 0.441246E+09 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.417078E+09 | 28174314.89 | 0.00 | 3365603.95 | 9098197.19 | 2778652.94 | 0.571226E+09 | 0.00 | 0.35 |
February | 0.217664E+09 | 0.140730E+09 | 0.00 | 3916521.39 | 12625335.53 | 0.00 | 0.492652E+09 | 0.00 | 0.40 |
March | 0.161078E+09 | 0.467115E+09 | 0.00 | 4715739.21 | 13545155.89 | 0.00 | 0.460466E+09 | 0.00 | 0.50 |
April | 67207407.05 | 0.157453E+10 | 0.00 | 3230001.33 | 0.108812E+09 | 0.00 | 0.211996E+09 | 0.00 | 0.66 |
May | 6396072.32 | 0.496323E+10 | 0.00 | 1656571.97 | 0.319699E+09 | 0.00 | 61958015.36 | 0.00 | 0.91 |
June | 1588640.58 | 0.908277E+10 | 0.00 | 224278.98 | 0.651468E+09 | 0.00 | 5229223.81 | 0.00 | 0.97 |
July | 3245052.22 | 0.132197E+11 | 0.00 | 251893.06 | 0.435509E+09 | 0.00 | 7399114.73 | 0.00 | 1.00 |
August | 0.00 | 0.142494E+11 | 0.00 | 0.00 | 0.575911E+09 | 0.00 | 0.00 | 0.00 | 1.01 |
September | 17745.33 | 0.979459E+10 | 0.00 | 93241.61 | 0.737400E+09 | 0.00 | 1565405.03 | 0.00 | 0.91 |
October | 3323473.81 | 0.473681E+10 | 0.00 | 1330393.67 | 0.493132E+09 | 0.00 | 62586539.99 | 0.00 | 0.72 |
November | 23061968.00 | 0.148082E+10 | 0.00 | 1978772.62 | 69242346.67 | 0.00 | 86829891.41 | 0.00 | 0.52 |
December | 0.213725E+09 | 0.227420E+09 | 0.00 | 3213032.20 | 35412537.69 | 0.00 | 0.378318E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.111438E+10 | 0.599653E+11 | 0.00 | 23976050.00 | 0.346186E+10 | 2778652.94 | 0.234023E+10 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 28174314.89 | 0.00 | 0.00 | 9098197.19 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.417078E+09 | 0.142494E+11 | 0.00 | 4715739.21 | 0.737400E+09 | 2778652.94 | 0.571226E+09 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.477985E+09 | 90769922.05 | 0.00 | 10837339.29 | 5400602.01 | 0.00 | 0.177459E+10 | 0.00 | 0.54 |
February | 0.291387E+09 | 0.333869E+09 | 0.00 | 9698785.43 | 8390283.80 | 0.00 | 0.114055E+10 | 0.00 | 0.54 |
March | 0.243361E+09 | 0.801294E+09 | 0.00 | 8477606.65 | 15477013.65 | 0.00 | 0.805114E+09 | 0.00 | 0.55 |
April | 0.125144E+09 | 0.216043E+10 | 0.00 | 3588107.14 | 0.197542E+09 | 0.00 | 0.217251E+09 | 0.00 | 0.57 |
May | 18830154.71 | 0.598633E+10 | 0.00 | 1611627.72 | 0.712225E+09 | 0.00 | 59515784.73 | 0.00 | 0.72 |
June | 2984436.23 | 0.107732E+11 | 0.00 | 256482.84 | 0.139866E+10 | 0.00 | 5717140.61 | 0.00 | 0.78 |
July | 7882361.30 | 0.165602E+11 | 0.00 | 331719.07 | 0.130646E+10 | 0.00 | 7825579.28 | 0.00 | 0.83 |
August | 0.00 | 0.192460E+11 | 0.00 | 0.00 | 0.114381E+10 | 0.00 | 0.00 | 0.00 | 0.88 |
September | 12718.42 | 0.150683E+11 | 0.00 | 131523.06 | 0.105925E+10 | 0.00 | 2215493.82 | 0.00 | 0.88 |
October | 6025908.16 | 0.852962E+10 | 0.00 | 2585088.72 | 0.566467E+09 | 0.00 | 99703990.67 | 0.00 | 0.83 |
November | 24747441.72 | 0.314794E+10 | 0.00 | 5235244.40 | 51560549.96 | 0.00 | 0.187318E+09 | 0.00 | 0.70 |
December | 0.246714E+09 | 0.678906E+09 | 0.00 | 10088436.97 | 21371214.46 | 0.00 | 0.109945E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.144507E+10 | 0.833769E+11 | 0.00 | 52841961.30 | 0.648661E+10 | 0.00 | 0.539925E+10 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 90769922.05 | 0.00 | 0.00 | 5400602.01 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.477985E+09 | 0.192460E+11 | 0.00 | 10837339.29 | 0.139866E+10 | 0.00 | 0.177459E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.433091E+09 | 36432650.49 | 0.00 | 3596514.00 | 7258018.46 | 0.00 | 0.596702E+09 | 0.00 | 0.37 |
February | 0.223198E+09 | 0.177266E+09 | 0.00 | 4295339.79 | 11128141.06 | 0.00 | 0.511604E+09 | 0.00 | 0.43 |
March | 0.143140E+09 | 0.551400E+09 | 0.00 | 5368914.20 | 4691359.65 | 0.00 | 0.536172E+09 | 0.00 | 0.56 |
April | 43566511.84 | 0.183233E+10 | 0.00 | 3006972.99 | 71450461.60 | 0.00 | 0.209595E+09 | 0.00 | 0.70 |
May | 5848254.11 | 0.549651E+10 | 0.00 | 1525495.99 | 0.213569E+09 | 0.00 | 56147916.90 | 0.00 | 0.93 |
June | 43809.27 | 0.102109E+11 | 0.00 | 224848.75 | 0.324863E+09 | 0.00 | 6552216.73 | 0.00 | 1.03 |
July | 864126.96 | 0.144449E+11 | 0.00 | 324612.29 | 0.254361E+09 | 0.00 | 10959197.22 | 0.00 | 1.06 |
August | 0.00 | 0.160761E+11 | 0.00 | 0.00 | 0.327885E+09 | 0.00 | 0.00 | 0.00 | 1.10 |
September | 10631.88 | 0.109526E+11 | 0.00 | 92302.24 | 0.462465E+09 | 0.00 | 1593311.75 | 0.00 | 0.95 |
October | 10031351.23 | 0.517516E+10 | 0.00 | 954675.06 | 0.368893E+09 | 0.00 | 42815747.88 | 0.00 | 0.76 |
November | 22716495.80 | 0.165974E+10 | 0.00 | 2143694.21 | 49767384.58 | 0.00 | 86564044.87 | 0.00 | 0.56 |
December | 0.205216E+09 | 0.300944E+09 | 0.00 | 3752193.10 | 31502002.95 | 0.00 | 0.435072E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.108773E+10 | 0.669144E+11 | 0.00 | 25285562.61 | 0.212783E+10 | 0.00 | 0.249378E+10 | 0.00 | 0.74 |
Minimum of Months | 0.00 | 36432650.49 | 0.00 | 0.00 | 4691359.65 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.433091E+09 | 0.160761E+11 | 0.00 | 5368914.20 | 0.462465E+09 | 0.00 | 0.596702E+09 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 49714636.35 | 0.00 | 6347452.14 | 0.00 | 0.00 | 0.211667E+09 | 0.00 | 0.58 |
February | 0.00 | 0.133496E+09 | 0.00 | 7760634.48 | 0.00 | 0.00 | 74750528.35 | 0.00 | 0.58 |
March | 0.00 | 0.203698E+09 | 0.00 | 12897767.76 | 0.00 | 0.00 | 57546233.12 | 0.00 | 0.59 |
April | 0.00 | 0.481818E+09 | 0.00 | 5376145.42 | 0.00 | 0.00 | 10256911.27 | 0.00 | 0.59 |
May | 0.00 | 0.835989E+09 | 0.00 | 122375.49 | 0.00 | 0.00 | 654510.61 | 0.00 | 0.59 |
June | 0.00 | 0.136893E+10 | 0.00 | 7330.82 | 0.00 | 0.00 | 1464.69 | 0.00 | 0.60 |
July | 0.00 | 0.180155E+10 | 0.00 | 13294.69 | 0.00 | 0.00 | 1919.69 | 0.00 | 0.60 |
August | 0.00 | 0.177332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.143986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.103133E+10 | 0.00 | 380826.22 | 0.00 | 0.00 | 914384.53 | 0.00 | 0.59 |
November | 0.00 | 0.533039E+09 | 0.00 | 1175983.45 | 0.00 | 0.00 | 1962182.85 | 0.00 | 0.58 |
December | 0.00 | 0.231317E+09 | 0.00 | 14919113.52 | 0.00 | 0.00 | 57592506.85 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.988406E+10 | 0.00 | 49000924.00 | 0.00 | 0.00 | 0.415347E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 49714636.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.180155E+10 | 0.00 | 14919113.52 | 0.00 | 0.00 | 0.211667E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.457391E+09 | 0.00 | 50291163.34 | 0.00 | 0.00 | 0.220805E+10 | 0.00 | 0.58 |
February | 0.00 | 0.131131E+10 | 0.00 | 69592953.51 | 0.00 | 0.00 | 0.770994E+09 | 0.00 | 0.58 |
March | 0.00 | 0.202827E+10 | 0.00 | 0.121375E+09 | 0.00 | 0.00 | 0.584425E+09 | 0.00 | 0.59 |
April | 0.00 | 0.482091E+10 | 0.00 | 51445911.10 | 0.00 | 0.00 | 0.104308E+09 | 0.00 | 0.59 |
May | 0.00 | 0.828843E+10 | 0.00 | 1164605.10 | 0.00 | 0.00 | 6700016.79 | 0.00 | 0.59 |
June | 0.00 | 0.136378E+11 | 0.00 | 69333.14 | 0.00 | 0.00 | 23116.30 | 0.00 | 0.60 |
July | 0.00 | 0.179762E+11 | 0.00 | 127534.90 | 0.00 | 0.00 | 22419.69 | 0.00 | 0.60 |
August | 0.00 | 0.180708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.142719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.102678E+11 | 0.00 | 3628470.24 | 0.00 | 0.00 | 9342023.01 | 0.00 | 0.59 |
November | 0.00 | 0.531320E+10 | 0.00 | 11125198.76 | 0.00 | 0.00 | 20602861.26 | 0.00 | 0.58 |
December | 0.00 | 0.230489E+10 | 0.00 | 0.139569E+09 | 0.00 | 0.00 | 0.586666E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.987490E+11 | 0.00 | 0.448390E+09 | 0.00 | 0.00 | 0.429113E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.457391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.180708E+11 | 0.00 | 0.139569E+09 | 0.00 | 0.00 | 0.220805E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 44520717.92 | 0.00 | 4114657.01 | 0.00 | 0.00 | 0.228373E+09 | 0.00 | 0.58 |
February | 0.00 | 0.130745E+09 | 0.00 | 6568152.35 | 0.00 | 0.00 | 78412182.08 | 0.00 | 0.58 |
March | 0.00 | 0.202935E+09 | 0.00 | 11904043.73 | 0.00 | 0.00 | 58763544.06 | 0.00 | 0.59 |
April | 0.00 | 0.481982E+09 | 0.00 | 5112559.74 | 0.00 | 0.00 | 10444955.89 | 0.00 | 0.59 |
May | 0.00 | 0.831896E+09 | 0.00 | 114693.26 | 0.00 | 0.00 | 668015.08 | 0.00 | 0.59 |
June | 0.00 | 0.136584E+10 | 0.00 | 6981.89 | 0.00 | 0.00 | 2081.63 | 0.00 | 0.60 |
July | 0.00 | 0.179934E+10 | 0.00 | 12468.67 | 0.00 | 0.00 | 2097.69 | 0.00 | 0.60 |
August | 0.00 | 0.180568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.143180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.102767E+10 | 0.00 | 357757.84 | 0.00 | 0.00 | 940506.90 | 0.00 | 0.59 |
November | 0.00 | 0.531341E+09 | 0.00 | 1086616.92 | 0.00 | 0.00 | 2115771.42 | 0.00 | 0.58 |
December | 0.00 | 0.230365E+09 | 0.00 | 13621704.80 | 0.00 | 0.00 | 59084484.63 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.988411E+10 | 0.00 | 42899636.22 | 0.00 | 0.00 | 0.438807E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 44520717.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.180568E+10 | 0.00 | 13621704.80 | 0.00 | 0.00 | 0.228373E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.140571E+10 | 0.00 | 0.340187E+09 | 0.00 | 0.00 | 0.443212E+10 | 0.00 | 0.66 |
February | 0.00 | 0.305449E+10 | 0.00 | 0.382953E+09 | 0.00 | 0.00 | 0.155859E+10 | 0.00 | 0.66 |
March | 0.00 | 0.439592E+10 | 0.00 | 0.607574E+09 | 0.00 | 0.00 | 0.117471E+10 | 0.00 | 0.66 |
April | 0.00 | 0.854150E+10 | 0.00 | 0.347717E+09 | 0.00 | 0.00 | 0.269347E+09 | 0.00 | 0.66 |
May | 0.00 | 0.193051E+11 | 0.00 | 5885889.45 | 0.00 | 0.00 | 13934034.31 | 0.00 | 0.66 |
June | 0.00 | 0.305243E+11 | 0.00 | 176857.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.395467E+11 | 0.00 | 958257.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.315287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.333501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.230340E+11 | 0.00 | 21563880.41 | 0.00 | 0.00 | 15609448.16 | 0.00 | 0.66 |
November | 0.00 | 0.116394E+11 | 0.00 | 54075914.89 | 0.00 | 0.00 | 33303939.44 | 0.00 | 0.66 |
December | 0.00 | 0.464330E+10 | 0.00 | 0.696713E+09 | 0.00 | 0.00 | 0.109996E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.210969E+12 | 0.00 | 0.245780E+10 | 0.00 | 0.00 | 0.859758E+10 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.140571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.395467E+11 | 0.00 | 0.696713E+09 | 0.00 | 0.00 | 0.443212E+10 | 0.00 | 0.68 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:50:17
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.255316E+12 | 0.516888E+10 | 0.00 | 0.466248E+12 | 0.146557E+13 |
February | 0.287626E+12 | 0.416800E+10 | 0.00 | 0.279388E+12 | 0.193713E+13 |
March | 0.352569E+12 | 0.183290E+10 | 0.00 | 0.153915E+12 | 0.294824E+13 |
April | 0.370703E+12 | -0.403692E+10 | 0.00 | -0.231014E+12 | 0.383355E+13 |
May | 0.376819E+12 | -0.122664E+11 | 0.00 | -0.848915E+12 | 0.385710E+13 |
June | 0.358629E+12 | -0.240941E+11 | 0.00 | -0.150290E+13 | 0.513624E+13 |
July | 0.349024E+12 | -0.328211E+11 | 0.00 | -0.207515E+13 | 0.635883E+13 |
August | 0.332333E+12 | -0.325464E+11 | 0.00 | -0.221337E+13 | 0.712086E+13 |
September | 0.290441E+12 | -0.254862E+11 | 0.00 | -0.172215E+13 | 0.483347E+13 |
October | 0.245597E+12 | -0.129962E+11 | 0.00 | -0.992049E+12 | 0.424205E+13 |
November | 0.201972E+12 | -0.277019E+10 | 0.00 | -0.260557E+12 | 0.343357E+13 |
December | 0.215567E+12 | 0.259079E+10 | 0.00 | 0.222765E+12 | 0.301931E+13 |
Annual Sum or Average | 0.363660E+13 | -0.133257E+12 | 0.00 | -0.872378E+13 | 0.481859E+14 |
Minimum of Months | 0.201972E+12 | -0.328211E+11 | 0.00 | -0.221337E+13 | 0.146557E+13 |
Maximum of Months | 0.376819E+12 | 0.516888E+10 | 0.00 | 0.466248E+12 | 0.712086E+13 |